Page 1 of 8
EMC Technologies Pty Ltd
ABN 82 057 105 549
Unit 3/87 Station Road
Seven Hills NSW 2147 Australia
Telephone
+61 2 9624 2777
Facsimile
+61 2 9838 4050
Email
syd@emctech.com.au
www.emctech.com.au
Test Report To IEC 61010-2-030:2010
Report No. T120122_SA
Manufacturer: Dynamic Ratings Pty Ltd
Test Sample Name: Electronic Control System for Power
Transformer
Model: DR-C50
Serial No.: N/A
Date of Issue: 28th June, 2012
EMC Technologies Pty Ltd reports apply only to the specific samples tested under stated test conditions. It is
the manufacturer’s responsibility to assure that additional production units of this model are manufactured with
identical electrical and mechanical components. EMC Technologies Pty Ltd shall have no liability for any
deductions; interferences or generalisations drawn by the client or others from EMC Technologies Pty Ltd
issued reports. This report shall not be used to claim, constitute or imply product endorsement by EMC
Technologies Pty Ltd.
Melbourne
176 Harrick Road
Keilor Park Vic 3042
Tel: +61 3 9365 1000
Fax: +61 3 9331 7455
Sydney
Unit 3/87 Station Road
Seven Hills NSW 2147
Tel: +61 2 9624 2777
Fax: +61 2 9838 4050
Auckland (NZ)
47 MacKelvie Street
Grey Lynn Auckland
Tel: +64 9 360 0862
Fax: +64 9 360 0861
EMC Technologies Report No. T120122_SA
Page 2 of 8
EMC Technologies Report No.: T120122_SA
Test Sample Name:
Model:
Serial Number:
Part Number:
Electronic Control System for Power Transformer
DR-C50
N/A
N/A
Nominal Supply Voltage:
85-276Vac / 85-288Vdc
Nominal Supply Frequency:
40/60Hz for AC supply
Manufacturer:
Dynamic Ratings Pty Ltd
Tested For:
Address:
Dynamic Ratings Pty Ltd
310 Springvale Road, Glen Waverley,
VIC 3150, Australia
Phone:
Fax:
Responsible Party:
Contact:
+61 3 9574 7722
+61 3 8544 2464
Dynamic Ratings Pty Ltd
Scott Andrew
Test Standard/s:
IEC 61010-2-030:2010
Safety requirement for electrical equipment for measurement, control, and
laboratory usePart 2-030: Particular requirements for testing and measuring circuits
Result of Test:
The test samples complied with all relevant clauses of
IEC 61010-2-030:2010.
Refer to Report no. T120122_SA for full details.
Test Date/s:
22 February, 2012 to 5 April, 2012
nd
th
Testing Officer:
Colin He
Authorised Signature:
James Chu
Safety Manager
EMC Technologies Pty Ltd
Issued by EMC Technologies Pty Ltd, Unit 3/87 Station Road, Seven Hills, NSW, 2147, Australia.
Phone: +61 2 9624 2777
Fax: +61 2 9838 4050
This document must not be copied or reproduced, except in full, without the written
permission of the Manager, EMC Technologies Pty Ltd
www.emctech.com.au
EMC Technologies Report No. T120122_SA
Page 3 of 8
PRODUCT DESCRIPTION SUMMARY
The equipment under test (EUT) is an Electronic Control System for Power Transformer. It incorporates a main unit
and an interface unit. The main unit has its power supply modules and other functional boards for measurement
and communication. It is a Class I product intended to be connected to AC or DC mains with detachable power
cord. It also supplies 24Vdc power to the interface unit.
The main unit is intended to be mounted inside a cabinet specified in the installation instruction. Any part of it is not
to be accessible to users during operation.
Information list for ports on individual functional boards –
Ports
Digital Input
Digital Output
Analog Input
Analog Output
RTD
CT Input
VT Input
Maximum operating voltage
±390VDC / 276VAC
±30VDC / 250VAC
24VDC
24VDC
5VDC
7VDC
300VAC
Maximum transient voltage
1500V
1500V
2500V
2500V
2500V
2500V
1500V
NOTE: The EUT has been tested against IEC 61010-1:2010 in our report T120122_S. The purpose of this report is
to verify the compliance to Part 2-030 for the measuring circuits.
This document must not be copied or reproduced, except in full, without the written
permission of the Manager, EMC Technologies Pty Ltd
www.emctech.com.au
EMC Technologies Report No. T120122_SA
Page 4 of 8
TEST RESULTS OF EN 61010-2-030
1
SCOPE AND OBJECT
NOTED
2
NORMATIVE REFERENCES
NOTED
3
TERM AND DEFINITIONS
NOTED
4
TESTS
NOTED
5
MARKING AND DOCUMENTATION
COMPLIES
Refer to our report T120122_S for general requirements.
5.1.5
Terminals, connections and operating devices
5.1.5.101
Measuring circuit terminals
5.1.5.101.1
General
NOT APPLICABLE
Measuring circuit terminals did not need to be marked. See 5.1.5.101.4.
5.1.5.101.2
Measuring circuit terminals rated for Measurement Categories
II, III or IV
NOT APPLICABLE
See 5.1.5.101.4.
5.1.5.101.3
Measuring circuit terminals rated for connection to voltages above
the Level of 6.3.1
NOT APPLICABLE
See 5.1.5.101.4.
5.1.5.101.4
Low voltage, permanently connected, or dedicated measuring
circuit terminals
COMPLIES
Measuring circuit terminals were permanently connected and not accessible to
operators.
5.4
5.4.1
Documentation
General
NOT APPLICABLE
Measuring circuit terminals did not need to be marked. See 5.1.5.101.4.
5.4.3
Equipment installation
COMPLIES
Information regarding the measurement category, rated maximum working
voltage, and rated maximum current was provided on installation manual.
This document must not be copied or reproduced, except in full, without the written
permission of the Manager, EMC Technologies Pty Ltd
www.emctech.com.au
EMC Technologies Report No. T120122_SA
6
PROTECTION AGAINST ELECTRIC SHOCK
Page 5 of 8
COMPLIES
Refer to our report T120122_S for general requirements.
6.1.2
Exceptions
NOT APPLICABLE
No such terminals
6.5.2
6.5.2.1
Protective bonding
General
COMPLIES
Refer to our report T120122_S for general requirements.
See 6.5.2.3 and 6.5.2.101 for other results.
6.5.2.3
Protective conductor terminals
NOT APPLICABLE
No such terminals
6.5.2.101
Indirect bonding for testing and measuring circuits
NOT APPLICABLE
Not such bonding
6.6
Connections to external circuits
6.6.101
Measuring circuit terminals
NOTED
COMPLIES
Unmated terminals were not accessible according to installation manual.
6.6.102
Specialized measuring circuit terminals
COMPLIES
Such terminals were not accessible according to installation manual.
6.9
Constructional requirements for protection against electric
shock
6.9.101
Over-range indication
NOTED
NOT APPLICABLE
Safety didn’t rely on the indication.
7
PROTECTION AGAINST MECHANICAL HAZARDS
COMPLIES
Refer to our report T120122_S.
8
MECHANICAL RESISTANCE TO SHOCK AND IMPACT
COMPLIES
Refer to our report T120122_S.
9
PROTECTION AGAINST THE SPREAD OF FIRE
COMPLIES
Refer to our report T120122_S.
10
EQUIPMENT TEMPERATURE LIMITS AND RESISTANCE TO
HEAT
COMPLIES
Refer to our report T120122_S.
This document must not be copied or reproduced, except in full, without the written
permission of the Manager, EMC Technologies Pty Ltd
www.emctech.com.au
EMC Technologies Report No. T120122_SA
11
PROTECTION AGAINST HAZARDS FROM FLUIDS
Page 6 of 8
COMPLIES
Refer to our report T120122_S.
12
PROTECTION AGAINST RADIATION, INCLUDING LASER
SOURCES, AND AGAINST SONIC AND ULTRASONIC
PRESSURE
NOT APPLICABLE
Refer to our report T120122_S.
13
PROTECTION AGAINST LIBERATED GASES AND
SUBSTANCES, EXPLOSION AND IMPLOSION
COMPLIES
Refer to our report T120122_S.
14
COMPONENTS
COMPLIES
Refer to our report T120122_S for general requirements.
14.101
Circuits or components used as transient overvoltage limiting
devices in measuring circuits used to measure mains
NOT APPLICABLE
No such devices
15
PROTECTION BY INTERLOCKS
NOT APPLICABLE
Refer to our report T120122_S.
16
HAZARDS RESULTING FROM APPLICATION
NOT APPLICABLE
Refer to our report T120122_S.
17
RISK ASSESSMENT
NOT APPLICABLE
Refer to our report T120122_S.
101
MEASURING CIRCUITS
101.1
General
COMPLIES
Refer to 101.2, 101.3, 6.6, 16 and 17 for results.
101.2
Current measuring circuits
NOT APPLICABLE
No such circuits
101.3
Protection against mismatches of inputs and ranges
NOT APPLICABLE
Mismatch of terminals was not possible after proper installation.
This document must not be copied or reproduced, except in full, without the written
permission of the Manager, EMC Technologies Pty Ltd
www.emctech.com.au
EMC Technologies Report No. T120122_SA
ANNEXES
Refer to our report T120122_S for other Annexes
ANNEX K.3
Insulation in circuits not addressed in 6.7, K.1 or K.2 and in
measuring circuits where measurement categories do not
apply
Page 7 of 8
COMPLIES
Refer to our report T120122_S for such circuits.
ANNEX K.101
Insulation requirements for measuring circuits of
Measurement Categories II, III and IV
NOT APPLICABLE
No such measurement circuits
ANNEX L
Index of defined terms
NOTED
ANNEX AA
Measurement categories
NOTED
ANNEX BB
Hazards pertaining to measurements performed in certain
environments
NOTED
This document must not be copied or reproduced, except in full, without the written
permission of the Manager, EMC Technologies Pty Ltd
www.emctech.com.au
EMC Technologies Report No. T120122_SA
APPENDIX I: IDENTIFICATION PHOTOGRAPHS*
Main unit
Interface unit
*_Refer to our report T120122_S for other photos.
This document must not be copied or reproduced, except in full, without the written
permission of the Manager, EMC Technologies Pty Ltd
www.emctech.com.au
Page 8 of 8