IG-541 INERT GAS FIRE EXTINGUISHING SYSTEM OWNER’S MANUAL Rev.3 PN: HSN-MNL-IG541-R3 15 Apr 2024 A Foreword This manual is written for those who own or are responsible for IG-541 Inert Gas Fire Extinguishing System. We assume no responsibility for the application of any systems other than those addressed in this manual. The technical data contained herein is limited strictly for information purposes only. We believe this data to be accurate, but it is published and presented without any guarantee or warranty whatsoever. We disclaim any liability for any use that may be made of the data and information contained herein by any and all other parties. The IG-541 Inert Gas Fire Extinguishing System is to be designed, installed, inspected, maintained, tested and recharged by qualified, trained personnel in accordance with the following: VdS 2344en: Procedure for the testing, approval and certification of products and systems for fire protection and security technologies EN15004-1: Fixed firefighting systems - Gas extinguishing systems Storage, handling, transportation, service, maintenance, recharge and test of agent storage containers shall be per-formed only by qualified and trained personnel in accordance with the information in this manual and TPED Directive 2010/35/EU. Any questions concerning the information presented in this manual should be addressed to: Honeywell Middle East FZE Jebel Ali Free Zone, Office No. LB15413, 18530 Jebel Ali, Dubai, UAE Phone: +971 4 450 5800 Fax: +971 4 450 5900 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 2 / 74 B Attention Installer This form must be signed by the system owner indicating that he/she has received a copy of this Owner’s Manual Copy. Have the system installer fill out this form. Note: Retain a copy of this form for your records. A System Installed: __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ B Listing of Major System Components: __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ C Description of Hazard Protected by System: __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ _____________________________________ Owner or Authorized Representative _________________ Date _____________________________________ Title Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 3 / 74 C History of Revisions Table C.1 History of Revisions Version Revision Date R.0 12 / 02 / 2024 R.1 01 / 04 / 2024 R.2 10 / 04 / 2024 R.3 15 / 04 / 2024 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s Revision Detail Document created. Layouts, CPR valve location, manifold details and cylinder codes have been revised. Layouts have been revised. The actuation pressure of the selector valve actuator information has been added. P/N: HSN-MNL-IG541-R3 15 Apr 2024 Revised by D. Cagli Gel D. Cagli Gel D. Cagli Gel D. Cagli Gel Page 4 / 74 IG-541 Inert Gas Fire Extinguishing System Table of Contents 0. General Introduction ................................................................................................. 8 1. Concept ..................................................................................................................... 9 1.1. Application ....................................................................................................................... 9 1.2. System Description ........................................................................................................... 9 1.2.1. General ....................................................................................................................................... 9 1.2.2. Extinguishing Agent .................................................................................................................. 10 1.2.2.1. Toxicity ........................................................................................................................................ 10 1.2.2.2. Environmentally Friendly ............................................................................................................ 11 1.2.2.3. Storage ....................................................................................................................................... 11 2. Component Descriptions.......................................................................................... 14 2.1. Introduction.................................................................................................................... 14 2.2. Component Descriptions ................................................................................................. 16 2.2.1. Seamless Cylinder ..................................................................................................................... 16 2.2.2. Valve Assembly ......................................................................................................................... 18 .................................................................................................................................................................. 21 2.2.3. Solenoid Actuator for DN12 valve system (P/N: HSN-ACT-S01) .................................................. 21 2.2.4. Electric Actuator Reset Tool (for ACT-S01) (P/N: HSN-RST-01) .................................................... 23 2.2.5. Manual Actuator (P/N: HSN-ACT-M01) ...................................................................................... 24 2.2.6. Pneumatic Actuator (P/N: HSN-ACT-P01) .................................................................................. 24 2.2.7. Discharge Hose (P/N: HSN-DH-12-400) ...................................................................................... 25 2.2.8. Pilot Line Hose (P/N: HSN-PLH-01-500) ..................................................................................... 25 2.2.9. Pilot Line Nipple Adaptor (P/N: HSN-PNA-01) ........................................................................... 25 2.2.10. Bleed Valve (P/N: HSN-BLD-01) ................................................................................................. 26 2.2.11. Check Valve (P/N: HSN-CHV-012) .............................................................................................. 26 2.2.12. Discharge Pressure Switch (P/N: HSN-DPS-01) .......................................................................... 26 2.2.13. Pressure Gauges ........................................................................................................................ 27 2.2.14. Discharge Nozzles ..................................................................................................................... 28 2.2.15. Pilot Cylinders ........................................................................................................................... 29 2.2.15.1. Master Pilot Cylinder System .................................................................................................. 30 2.2.15.2. Booster Pilot Cylinder System ................................................................................................. 30 2.2.16. Selector Directional Valves ........................................................................................................ 31 2.2.17. Pilot Line Non-Return Valve (P/N: HSN-NRV-01) ........................................................................ 33 2.2.18. Constant Pressure Regulator Valve (P/N: HSN-CPR-10).............................................................. 33 2.2.19. Pressure Reducer (P/N: HSN-PRD-01) ........................................................................................ 35 2.2.20. Manifold Pressure Safety Valve (P/N: HSN-PSV-01) ................................................................... 35 2.2.21. Vent Valve (P/N: HSN-VV-01)..................................................................................................... 35 2.2.22. Label (P/N: HSN-LBL-IG541) ...................................................................................................... 35 2.2.23. Caution Signs ............................................................................................................................ 36 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 5 / 74 3. Other Accessories .................................................................................................... 37 3.1. Pilot Cylinders (ATEX) ...................................................................................................... 37 4. System Design ......................................................................................................... 38 4.1. Introduction.................................................................................................................... 38 4.1.1. 4.1.2. 4.1.3. 4.1.4. 4.1.5. 4.1.6. 4.1.7. 4.1.8. 4.1.9. 4.1.10. 4.1.11. Hazard Analysis ......................................................................................................................... 38 Determine which components are required .............................................................................. 39 Positioning of cylinders ............................................................................................................. 39 Positioning of piping ................................................................................................................. 39 Pipe size and layout .................................................................................................................. 39 Manifolds .................................................................................................................................. 40 Super-pressurization ................................................................................................................. 40 Design criteria ........................................................................................................................... 40 Design example and calculations .............................................................................................. 40 Duration of discharge ................................................................................................................ 43 Room Integrity and Pressure Ventilation ................................................................................... 44 5. Installation .............................................................................................................. 47 5.1. General Equipment Installation ....................................................................................... 47 5.2. Order of Installation ........................................................................................................ 47 5.2.1. Container installation ................................................................................................................ 48 5.2.1.1. Single container installation ....................................................................................................... 48 5.2.1.2. Multiple container installation ................................................................................................... 49 5.2.2. Pipe installation ........................................................................................................................ 52 5.2.2.1. Pipe and fittings system .............................................................................................................. 53 5.2.2.2. Pipe hangers & fasteners ............................................................................................................ 53 5.2.2.3. Installation of pipe and fittings ................................................................................................... 53 5.2.2.4. Piping support installation .......................................................................................................... 54 5.2.3. Master / slave cylinder installation ........................................................................................... 54 5.2.4. Installation of pressure switch .................................................................................................. 55 5.2.5. Installation of nozzles ............................................................................................................... 55 5.2.6. Discharge piping pressure test .................................................................................................. 55 5.2.7. Hand-over procedures .............................................................................................................. 56 5.2.8. Warning notification ................................................................................................................. 56 6. System Operation ....................................................................................................... 58 6.1. General Comments ......................................................................................................... 58 6.2. System Actuation ............................................................................................................ 58 6.2.1. 6.2.2. 6.2.3. 6.3. Manual system.......................................................................................................................... 58 Fully automatic system ............................................................................................................. 58 Fully automatic system with manual intervention..................................................................... 59 Actions Following a Fire................................................................................................... 59 6.3.1. Actions immediately following a fire ......................................................................................... 59 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 6 / 74 6.4. Solenoid Functional Test.................................................................................................. 60 7. Maintenance .............................................................................................................. 61 7.1. Introduction.................................................................................................................... 61 7.2. Maintenance Procedure .................................................................................................. 61 7.2.1. 7.3. Agent Storage Cylinders .................................................................................................. 61 7.3.1. 7.4. General ..................................................................................................................................... 61 Container test ........................................................................................................................... 62 Hose Test ........................................................................................................................ 62 7.4.1. 7.4.2. General ..................................................................................................................................... 62 Testing ...................................................................................................................................... 62 7.5. Enclosure Inspection ....................................................................................................... 63 7.6. Training .......................................................................................................................... 63 7.7. Maintenance Procedures................................................................................................. 63 7.7.1. Daily.......................................................................................................................................... 63 7.7.1.1. Check agent cylinder pressure .................................................................................................... 63 7.7.2. Monthly .................................................................................................................................... 63 7.7.2.1. General inspection ...................................................................................................................... 63 7.7.2.2. Hazard access ............................................................................................................................. 64 7.7.2.3. Inspect hoses .............................................................................................................................. 64 7.7.2.4. Inspect pneumatic actuators ...................................................................................................... 64 7.7.2.5. Inspect solenoid actuators .......................................................................................................... 64 7.7.2.6. Inspect cylinder and valve assembly ........................................................................................... 64 7.7.2.7. Inspect straps and mounting hardware ...................................................................................... 64 7.7.2.8. Inspect discharge hoses .............................................................................................................. 64 7.7.2.9. Inspect discharge nozzles ........................................................................................................... 64 7.7.3. Inspection procedures, semi-annual ......................................................................................... 65 7.7.3.1. Discharge pressure switch test ................................................................................................... 65 7.7.3.2. Solenoid actuator test................................................................................................................. 65 7.7.3.3. Check cylinder weight ................................................................................................................. 65 7.7.4. Inspection procedures - 2 year .................................................................................................. 65 7.7.5. Inspection procedures - 5 year .................................................................................................. 66 7.7.5.1. Clean Agent Cylinders ................................................................................................................. 66 7.7.5.2. Flexible hose ............................................................................................................................... 66 7.7.5.3. Record ......................................................................................................................................... 66 7.8. Check List ....................................................................................................................... 66 8. Typical System Layout ................................................................................................. 67 8.1. General........................................................................................................................... 67 Appendix A / Material Safety Data sheet for IG-541 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 7 / 74 0. General Introduction This manual is a comprehensive guide the contains all the information needed to design, install and maintain the IG-541 Inert Gas Fire Extinguishing System. Users of this manual are assumed to be competent fire engineers with a basic knowledge of such systems. The contents are arranged in alogical order describing the various procedures in turn, alternatively specific sections can be referred to as required. Users who are not familiar with the equipment should first read the complete manual. IG-541 is a nature, safe firefighting agent for use in total flooding automatic extinguishing systems. Systems may be activated mechanically or electrically. Mechanical manual actuation is via a strike knob attached to the container valve. Electrical actuation is via a removable side mounted solenoid. The solenoid can be energized automatically by a signal from a detection and alarm control panel. Users of this manual should find that sufficient information is provided to plan, design, purchase components, install, operate and maintain the system. However, in the event that part of the document is not understood, or if there is any concern as to the suitability of the protection, do not hesitate to contact one of our specialist engineers for the matter to be quickly resolved. These include: • Data Processing Centers • Telecommunication Switch Centers • Process Control Rooms • Art and Historical Collections • MRI Room in Hospital • Process Control Station of Oil Refinery • Marine Engine Rooms and Drone Control Center of Military • An ideal supplement for sprinkler systems to protect any type of assets that could be damaged by water. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 8 / 74 1. 1.1. Concept Application IG-541 Inert gas fire extinguishing system is designed, installed, maintained and tested for total flooding in accordance EPA and EN15004 standards. This is the time-tested agent available in the market. IG-541 Inert gas fire extinguishing system are designed to extinguishes fires in specific hazards or equipment located where an electrically non-conductive agent is required, where agent cleanup creates a problem, where extinguishing capability with low weight is a factor and where the hazard is normally occupied by personnel. Features of IG-541 Inert gas: • Ozone Depleting Potential (ODP) of Zero • Requires minimal storage space • No post-fire residue or clean up • No damage to protected equipment • Is electrically non-conductive • Safe for use in a wide range of normally occupied hazard areas • SNAP List Approved • No atmospheric lifetime • No global warming potential Typical Application: • Telecommunication switch rooms • Computer and electronic control rooms • Banking Data Centre • Marine Engine Rooms and Drone Control Center of Military • Control Rooms in Power Generation Plants • Control Rooms in Petrochemical Installations 1.2. System Description 1.2.1. General IG-541 Inert gas fire extinguishing system is a time-tested natural inert gas agents alternative. It combines outstanding extinguishing performance with an excellent environmental profile. IG-541 Inert gas has zero ozone depletion potential and zero global warming potential of atmospheric lifetime, and a large margin of safety for occupied spaces. The IG-541 inert gas extinguishes fire by lowering the oxygen content below the level that supports combustion. It is also electrically non-conductive. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 9 / 74 Figure 1.1: Typical IG-541 Inert Gas Fire Extinguishing Systems IG-541 Inert Gas Systems are designed for the following classes of fire: • Class A; Surface Type Fires; Wood, cloth, rubber, paper and many plastics. • Class B; Flammable liquids • Class C; Energized electrical equipment 1.2.2. Extinguishing Agent IG-541 Inert gas agent, referenced as Nitrogen (%52), Argon (%40) & CO2(%8) in EN15004-10 and ISO 14520-12, the there gases Nitrogen, Argon and CO2 are mixed in proportions: %52, %40 & %8 Nitrogen, Argon and CO2 are natural components of air and theirs constituting approximately 0.79% of the earth’s atmosphere. They are a clear, colorless, odorless gases. These agents are discharged into a room, they introduces the proper natural of gases that still allows a person to breathe in a reduced oxygen atmosphere. This allows people to see and breathe, permitting them to leave the fire area safely. + + Figure 1.2.: IG-541 Monoatomic & Molecular noble gases 1.2.2.1. Toxicity It is commonly known that the reduction of oxygen had some side effects. It is important to understand that the Inert gases (He, Ne, Ar, N etc.) and nitrogen do not have any toxic effects at normal atmospheric pressures. (No toxicological effects from this product.) Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 10 / 74 Table 1.1. Design Concentrations Agent Extinguishment Minimum design % by volume % by volume Class B 31.7 Heptane (cup burner) 48.1 37.0 Heptane (room test) Surface Class A Wood crib 28.2 PMMA 30.7 PP 30.6 ABS 30.7 Higher Hazard Class A a 39.9 45.7 a: The minimum design concentration for Higher Hazard Class A fuels shall be the higher of the Surface Class A or 95 % of the Class B minimum design concentration Reference: EN15004-10, Table 4 — IG-541 reference extinguishing and design concentrations Table 1.2. Physiological information for IG-541 Agent LC50 or ALC (%) NOAEL LOAEL Nitrogen & Argon N/A 43.0 % 52.0 % CO2 470,000 ppm (Rat) 43.0 % 52.0 % NOTE.1: LC50 is the concentration lethal to 50 % of a rat population during a 4 h exposure. The ALC is the approximate lethal concentration. NOTE.2: The cardiac sensitization levels are based on the observance or non-observance of serious heart arrhythmias in a dog. The usual protocol is a 5 min exposure followed by a challenge with epinephrine. NOTE.3: High concentration values are determined with the addition of oxygen to prevent asphyxiation. Reference: EN15004-9, Table 5 — Physiological information for IG-541 1.2.2.2. Environmentally Friendly IG-541 has zero ozone depletion potential and zero atmospheric lifetime, IG-541 is the preferred naturally inert agents alternatives to offer a viable, long-term, sustainable technology for special hazards fire protection. Table 1.3. Environmental Properties Description IG-01 IG-55 IG-100 IG-541 Ozone Depletion Potential 0.0 0.0 0.0 0.0 Global Warming Potential N/A N/A N/A N/A Atmospheric Lifetime (Years) N/A N/A N/A N/A SNAP (YES/NO) Yes Yes Yes Yes Reference: World Meteorological Organization (WMO) 1998, Model-Derived Method Intergovernmental Panel on Climate Change (IPCC) 2007 Method, 100-year ITH (4th IPCC report) 1.2.2.3. Storage IG-541 Inert Gas Agent are stored as a gas in steel containers with storage pressure of 200 bar (2900 psi) or 300 bar (4350 psi) @ 15 ⁰C (60 ⁰F). To displace the extinguishing clean agent out of the steel containers through the pipelines to the nozzles in protected hazard, no added any other Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 11 / 74 component as a propellant to improve the discharge characteristics. IG-541 inert gas system is available in two variants. • 200 Bar system: IG-541 inert gas agent is stored in seamless cylinder as gas with nitrogen and argon to 200 Bar at 15°C (2900 psi at 60 °F). • 300 Bar system: IG-541 inert gas agent is stored in seamless cylinder as gas with nitrogen and argon to 300 Bar at 15°C (4350 psi at 60 °F). Table 1.4. Storage container characteristics tables for IG-541 200 Bar Property Unit Value Filling Pressure at 15°C a bar 200 Maximum container working pressure at 50°C bara 235 Reference should be made to Figure 1 for further data on pressure / temperature relationships. a 1 bar = 0,1 MPa = 10 5 Pa; 1 MPa = 1 N/mm2 Table 1.5. Storage container characteristics tables for IG-541 300 Bar Property Unit Filling Pressure at 15°C Maximum container working pressure at 50°C Value a bar 300 a 366 bar Reference should be made to Figure 1 for further data on pressure / temperature relationships. a 1 bar = 0,1 MPa = 10 5 Pa; 1 MPa = 1 N/mm2 Pressure/Temperature Graph (IG-541) Pressure/Temperature Graph (IG-541) 300 a: pressure at 15°C, bar 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150 PRESSURE (BARA) PRESSURE (BARA) 200 a: pressure at 15°C, bar -20 -10 0 10 20 30 40 50 60 70 80 90 450 400 350 300 250 200 150 100 50 0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 TEMPERATURE (°C) TEMPERATURE (°C) Figure 1.3.: Temperature/pressure graph for IG-541 to 200 bar and 300 bar Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 12 / 74 Table 1.6. Agent Container Fill Quantity for 13, 40, 80 & 140L Cylinders for 200 Bar 13 L 40 L 80 L 140 L Weight Volume Weight Volume Weight Volume Weight Volume IG-01 4.6 kg 2.7 m3 14.1 kg 8.4 m3 28.2 kg 16.7 m3 49.3 kg 29.2 m3 IG-55 3.7 kg 2.6 m3 11.4 kg 7.9 m3 22.8 kg 15.9 m3 39.9 kg 27.8 m3 IG-100 2.9 kg 2.4 m3 8.9 kg 7.5 m3 17.9 kg 15.1 m3 31.3 kg 26.4 m3 IG-541 3.9 kg 2.7m3 11.9 kg 8.2 m3 23.8 kg 16.5 m3 41.6 kg 28.9 m3 Table 1.7. Agent Container Fill Quantity for 13, 40, 80 & 140L Cylinders for 300 Bar 13 L 40 L 80 L 140 L Weight Volume Weight Volume Weight Volume Weight Volume IG-01 6.5 kg 3.9 m3 20.1 kg 11.9 m3 40.3 kg 23.8 m3 70.5 kg 41.7 m3 IG-55 5.3 kg 3.6 m3 16.1 kg 11.1 m3 32.1 kg 22.3 m3 56.2 kg 39.1 m3 IG-100 4.0 kg 3.4 m3 12.4 kg 10.5 m3 24.9 kg 21.0 m3 43.5 kg 36.7 m3 IG-541 5.4 kg 3.7 m3 16.5 kg 11.5 m3 33.1 kg 23.0 m3 57.9 kg 40.1 m3 Table 1.8. Inert Gas Density & Volume Quantity for 200 & 300 Bar Density 200 Bar@15°C IG-01 352.1 kg/m 3 IG-55 Volume 1 atm @15°C Density 300 Bar@15°C 3 Volume 1 atm @15°C 0.5920 m /kg 503.4 kg/m 3 0.5920 m3/kg 284.8 kg/m3 0.6969 m3/kg 401.1 kg/m3 0.6969 m3/kg IG-100 223.8 kg/m3 0.8463 m3/kg 311.0 kg/m3 0.8463 m3/kg IG-541 297.1 kg/m3 0.6938 m3/kg 413.2 kg/m3 0.6938 m3/kg Table 1.9. Physical Properties of IG-541 Properties IG-541 Chemical Name Nitrogen, Argon, Carbon dioxide Chemical Formula (%52) N2, (%40) Ar, (%8) CO2 Molecular Weight 34.00 g/mol Boiling Point @ 1 atm -196.0 ⁰C Critical Temperature -78.5 ⁰C (-109.3 ⁰F) Relative Density 1.4236 kg/m3@15 ⁰C Gas Density @ 1 atm N/A Vapor Pressure 20 °C 152 Solubility of Water in IG-541 @ 0 °C (32°F) 17.1 ml/L Ozone Depletion Potential 0.0 Global Warming Potential, GWP (100yr ITH.for Co₂, GWP=1) N/A Atmospheric Lifetime N/A TSCA Inventory Status Reported / Included European List of New Chemical Substances EINECS, Listed (231-147-0 & 231-783-0 &204-696-9) SNAP Status Listed Reference: IG-541 gas manufacturer’s MSDS Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 13 / 74 2. 2.1. Component Descriptions Introduction This chapter provides a functional description of the components and assemblies of the IG-541 Inert Gas Fire Extinguishing System. Table 2.1. Part List Description Part Number 200&300 Bar Cylinder Sets 13L Seamless Cylinder, TPED, 200bar (filled with IG-541 gas) (including DN12 valve, bracket and label) 13L Seamless Cylinder, TPED, 300bar (filled with IG-541 gas) (including DN12 valve, bracket and label) 40L Seamless Cylinder, TPED, 200bar (filled with IG-541 gas) (including DN12 valve, bracket and label) 40L Seamless Cylinder, TPED, 300bar (filled with IG-541 gas) (including DN12 valve, bracket and label) 80L Seamless Cylinder, TPED, 200bar (filled with IG-541 gas) (including DN12 valve, bracket and label) 80L Seamless Cylinder, TPED, 300bar (filled with IG-541 gas) (including DN12 valve, bracket and label) 140L Seamless Cylinder, TPED, 200bar (filled with IG-541 gas) (including DN12 valve, bracket and label) 140L Seamless Cylinder, TPED, 300bar (filled with IG-541 gas) (including DN12 valve, bracket and label) HSN-IG541-013-210E HSN-IG-541-013-310E HSN-IG-541-040-210E HSN-IG-541-040-310E HSN-IG-541-080-210E HSN-IG-541-080-310E HSN-IG-541-140-210E HSN-IG-541-140-310E Pressure Gauges 0-315 Bar Pressure gauge at 180bar, NO (with low pressure switch) HSN-IG-PGV-NOC-01 0-400 Bar Pressure gauge at 270bar, NO (with low pressure switch) HSN-IG-PGV-NOC-02 0-160 Bar Pressure gauge at 90bar, NO (with low pressure switch *Available for pilot cylinders) HSN-PGV-NOC-300 Pilot Cylinders 5L Seamless Pilot Cylinder, TPED (filled with N2 gas and including DN12 valve, bracket and label) 13L Seamless Pilot Cylinder, TPED (filled with N2 gas and including DN12 valve, bracket and label) 40L Seamless Pilot Cylinder, TPED (filled with N2 gas and including DN12 valve, bracket and label) HSN-PLT-EU-SM-005 HSN-PLT-EU-SM-013 HSN-PLT-EU-SM-040 Pilot Cylinders (ATEX) 5L Seamless Pilot Cylinder, TPED, ATEX (filled with N2 gas and including DN12 valve, bracket and label) 13L Seamless Pilot Cylinder, TPED, ATEX (filled with N2 gas and including DN12 valve, bracket and label) Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 HSN-PLTA-EU-SM-005 HSN-PLTA-EU-SM-013 Page 14 / 74 Table 2.1. Part List (continued) Description 40L Seamless Pilot Cylinder, TPED, ATEX (filled with N2 gas and including DN12 valve, bracket and label) Part Number HSN-PLTA-EU-SM-040 Actuators Manual Actuator HSN-ACT-M01 Manual Actuator, ATEX (for DN12 24VDC Solenoid Valve) HSN-ACT-M02 Solenoid Actuator, 24V DC (suitable with 12mm valve) HSN-ACT-S01 Pneumatic Actuator HSN-ACT-P01 Reset Tool for ACT-S01 Type (Electrical Actuator) HSN-RST-S01 Cylinder Discharge Line Hose Discharge Hose, L:400mm, 12mm (13L to 140L) HSN-DH-12-400 Check Valves Check Valve DN12, G3/4” x G3/4” HSN-CHV-012 Actuation Line Accessories Pilot Line Hose, DN5 500 mm - 360bar HSN-PLH-01-500 Pilot Line Nipple Adaptor HSN-PNA-01 Pilot Line Te Adaptor (Male x Female (Turnable) x Male) HSN-PTA-01 Pilot Line Elbow Adaptor HSN-PEA-01 Bleed Valve HSN-BLD-01 Pilot Line Non-return Valve HSN-NRV-01 Constant Pressure Regulator (PW max: 360bar) HSN-CPR-10 Discharge Nozzles DN10 (3/8") - 180 Degree Discharge Nozzle HSN-NOZ-01-10 DN10 (3/8") - 360 Degree Discharge Nozzle HSN-NOZ-02-10 DN15 (1/2") - 180 Degree Discharge Nozzle HSN-NOZ-01-15 DN15 (1/2") - 360 Degree Discharge Nozzle HSN-NOZ-02-15 DN20 (3/4") - 180 Degree Discharge Nozzle HSN-NOZ-01-20 DN20 (3/4") - 360 Degree Discharge Nozzle HSN-NOZ-02-20 DN25 (1") - 180 Degree Discharge Nozzle HSN-NOZ-01-25 DN25 (1") - 360 Degree Discharge Nozzle HSN-NOZ-02-25 DN32 (11/4") - 180 Degree Discharge Nozzle HSN-NOZ-01-32 DN32 (11/4") - 360 Degree Discharge Nozzle HSN-NOZ-02-32 DN40 (11/2") - 180 Degree Discharge Nozzle HSN-NOZ-01-40 DN40 (11/2") - 360 Degree Discharge Nozzle HSN-NOZ-02-40 DN50 (2") - 180 Degree Discharge Nozzle HSN-NOZ-01-50 DN50 (2") - 360 Degree Discharge Nozzle HSN-NOZ-02-50 Switches Discharge Pressure Switch HSN-DPS-01 Caution Signs Protected Room Caution Sign for IG-541 System HSN-CS-IG541-01 Manual Release Point Caution Sign HSN-CS-MRP-01 Selector Valves 3/4" Selector Valve, BSP Threaded (Pw max: 140bar) Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 HSN-SV-01-020 Page 15 / 74 Table 2.1. Part List (continued) Description Part Number 1" Selector Valve, BSP Threaded (PW max: 140bar) HSN-SV-01-025 1 1/4" Selector Valve, BSP Threaded (PW max: 140bar) HSN-SV-01-032 11/2" Selector Valve, BSP Threaded (PW max: 140bar) HSN-SV-01-040 2" Selector Valve, BSP Threaded (PW max: 140bar) HSN-SV-01-050 21/2" Selector Valve, ISO Flange Connection (PW max: 140bar) HSN-SV-01-065 3" Selector Valve, ISO Flange Connection (Pw max: 140bar) HSN-SV-01-080 4" Selector Valve, ISO Flange Connection (Pw max: 140bar) HSN-SV-01-100 Pressure Safety Valves Manifold Pressure Safety Valve (Factory set point: 100 bar, PW max: 1500bar) Pressure Reducer (Factory set point: 8bar, PW max: 100bar) HSN-PSV-01 HSN-PRD-01 Vent Valve Vent Valve, PW max: 360bar HSN-VV-01 Label IG-541 Label 2.2. HSN-LBL-IG541 Component Descriptions 2.2.1. Seamless Cylinder IG-541 Inert Gas Agent are stored as a gas in steel containers with storage pressure of 200 bar (2900 psi) or 300 bar (4350 psi) @ 15 ⁰C (60 ⁰F). To displace the extinguishing clean agent out of the steel containers through the pipelines to the nozzles in protected hazard, no added any other component as a propellant to improve the discharge characteristics. IG-541 inert gas system is available in two variants. • 200 Bar system: IG-541 inert gas agent is stored in seamless cylinder as gas with nitrogen, argon and carbon dioxide to 200 Bar at 15°C (2900 psi at 60 °F). • 300 Bar system: IG-541 inert gas agent is stored in seamless cylinder as gas with nitrogen, argon and carbon dioxide to 300 Bar at 15°C (4350 psi at 60 °F). An identification label is affixed to the cylinder body indicating the fill quantity of IG-541, charging pressure and date of fill. Many variations in cylinder capacities (Refer Table 2.1.) to select the best as per project requirement. Fire extinguishing systems utilizing IG-541 inert gas systems are designed to be discharged within 60-120 seconds into a room, area, or enclosure with the structural integrity to retain the agent. The IG-541 inert gas system uniformly mixes throughout the protected area achieving a minimum concentration level in accordance with EN15004-10. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 16 / 74 Discharge Valve N2&Ar&CO2 Inert Gas Stored at 200/300 Bar Figure 2.1.: Typical seamless cylinder & valve assembly Table 2.2. 200/300 Bar IG-541 Inert Gas Seamless Cylinders Cylinder Part Number HSN-IG541013-210E/310E HSN-IG541040-210E/310E HSN-IG541080-210E/310E HSN-IG541140-210E/310E Cylinder Empty System Agent Total System Agent Total Volume Diameter Weight Pressure Capacity Weight Pressure Capacity Weight liter mm* kg** bar kg (m3) kg bar kg (m3) kg 13 203 21.5 40 219 47.8 3.9 (2.7) 11.9 (8.2) 200 80 267 82.8 140 356 229.5 23.8 (16.5) 41.6 (28.9) 5.4 25.4 16.5 59.7 300 106.6 271.1 26.9 (3.7) 64.3 (11.5) 33.1 115.9 (23.0) 57.9 287.4 (40.1) * Cylinder diameters have tolerance +/- 1% according to cylinder manufacturer. * Cylinder weights are approximately. IG-541 inert gas fire extinguishing system equipment’s are designed for an operating temperature range of 0°C to 50°C (32°F to 122°F). Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 17 / 74 2.2.2. Valve Assembly The automatic release of IG-541 inert gas is controlled by a forged brass, differential pressure operated cylinder valve connected to the neck of the cylinder. Each cylinder and valve assembly are provided with a safety cap and a protection cap which is a safety feature to prevent uncontrolled, accidental discharge. Discharge valve assembly is available in size DN12. Figure 2.2.: General Arrangement of DN12 Discharge Valve. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 18 / 74 4 1 5 1 6 3 1 2 1 7 1 1 1 8 1 1 1 1 d f d f d 1 1 1 d f d f d H1 H2 H3 Ø H4 9* Figure 2.3.: Single Cylinder Configuration Arrangement of Assembly of 13, 40, 80 & 140L System. *: It is changeable quantities according to the size of cylinders. Table 2.3. Hardware for 13 & 40 & 80 & 140L Cylinders 200 bar & 300 bar No. Description Part Number 1 DN12 Discharge Valve 2.1 0-315 Bar Pressure gauge with low pressure switch 180bar (NO) 2.2 200 Bar 300 Bar HSN-VLV-IG-200-01E HSN-VLV-IG-300-01E HSN-IG-PGV-NOC-01 N/A N/A HSN-IG-PGV-NOC-02 0-400 Bar Pressure gauge with low pressure switch 270bar (NO) 3 Solenoid Actuator, 24V DC HSN-ACT-S01 4 Manual Actuator HSN-ACT-M01 5 Constant Pressure Regulator, PW max: 360bar HSN-CPR-10 6 Check Valve DN12, G3/4” x G3/4” HSN-CHV-012 7 Discharge Hose DN12, L:400mm HSN-DH-12-400 8.1 13L Seamless Cylinder, TPED HSN-IG541-013-210E HSN-IG541-013-310E 8.2 40L Seamless Cylinder, TPED HSN-IG541-040-210E HSN-IG541-040-310E 8.3 80L Seamless Cylinder, TPED HSN-IG541-080-210E HSN-IG541-080-310E 8.4 140L Seamless Cylinder, TPED HSN-IG541-140-210E HSN-IG541-140-310E 9.1 13L Seamless Cylinder Strap HSN-STP-EU-SM-013 9.2 40L Seamless Cylinder Strap HSN-STP-EU-SM-040 9.3 80L Seamless Cylinder Strap HSN-STP-EU-SM-080 9.4 140L Seamless Cylinder Strap HSN-STP-EU-SM-140 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 19 / 74 Table 2.4. Dimensions for 13 & 40 & 80 & 140L Cylinders for 200&300 Bar Type H1 (mm) H2 (mm) H3 (mm) H4 (mm) Ø (mm) 13L 405 - 603 997 203 40L 248 998 1323 1717 219 80L 375 1335 1753 2147 267 140L 325 1225 1632 2026 356 5 6 1 31 1 21 11d 11f 11 1d 1df d f1fd dd ff dd f d 1 1 1 d f d f d 1 71 1 1 1 1 d d f f d d f f d d 8 9 8 1 1 1 d f d f d 1 1 110 1 d11 1 f 1 1 d121 1d1 f 1f d d 1df df 13*d 1fd f 1d d 1f d f d f Figure 2.4.: Multiple Cylinder Configuration Arrangement of Assembly of 80 & 140L System. d *: It is changeable quantities according to the size of cylinders. 4 Table 2.5. Hardware for 80 & 140L Cylinders 200 bar & 300 bar No. Description Part Number 1 DN12 Discharge Valve 2.1 0-315 Bar Pressure gauge with low pressure switch 180bar (NO) 2.2 0-400 Bar Pressure gauge with low pressure switch 270bar (NO) 200 Bar 300 Bar HSN-VLV-IG-200-01E HSN-VLV-IG-300-01E HSN-IG-PGV-NOC-01 N/A N/A HSN-IG-PGV-NOC-02 3 Solenoid Actuator, 24V DC HSN-ACT-S01 4 Manual Actuator HSN-ACT-M01 5 Constant Pressure Regulator, PW max: 360bar HSN-CPR-10 6 Pilot Hose DN5, PW max: 360bar 7 Pneumatic Actuator, PW max: 360bar HSN-ACT-P01 8 G1/8" x G1/8" Nipple Adaptor, PW max:360bar HSN-PNA-01 9 G1/8" Bleed Valve, PW max: 360bar HSN-BLD-01 10 Check Valve DN12, G3/4” x G3/4” HSN-CHV-012 11 Discharge Hose DN12, L:400mm 12.1 80L Seamless Cylinder, TPED HSN-IG541-080-210E HSN-IG541-080-310E 12.2 140L Seamless Cylinder, TPED HSN-IG541-140-210E HSN-IG541-140-310E 13.1 80L Seamless Cylinder Strap HSN-STP-EU-SM-080 13.2 140L Seamless Cylinder Strap HSN-STP-EU-SM-140 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s HSN-PLH-01-500 HSN-DH-12-400 P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 20 / 74 Table 2.6. Dimensions for 80 & 140L Cylinders for 200&300 Bar Type H1 (mm) H2 (mm) H3 (mm) H4 (mm) Ø (mm) 80L 375 1335 1753 2147 267 140L 325 1225 1632 2026 356 Figure 2.5.: General Arrangement of Assembly of Single & Multiple Systems. 2.2.3. Solenoid Actuator for DN12 valve system (P/N: HSN-ACT-S01) The Solenoid Actuator attaches to the primary cylinder at the valve actuation connection and is utilized to automatically open the cylinder valve upon receipt of a signal from the control panel or other source. 1 2 3 1 Table 2.7. Solenoid Actuator for DN12 valve system No. 1 Description 1 Connection for manual actuator 2 Connector plug for wiring 3 Connection to cylinder valve 1 Figure 2.6: Solenoid actuator for DN12 valve system. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 21 / 74 Table 2.8. Solenoid Actuator Pin Position No. 1 Description Solenoid actuator falling pin 1 Before activation 1 After activation Figure 2.7.: Solenoid actuator activation before vs after. IMPORTANT NOTICE: After the solenoid actuator is activated, the pin will fall downwards. The falling pin must be reset by pushing up as before activation. Otherwise, if the solenoid actuator assembly to top on valve with falling pin, the system will discharge incorrectly. To avoid this, the falling pin must be reset by a special tool. IMPORTANT NOTICE: The Solenoid Actuator circuit must be supervised for a break in the wiring, a ground, or a short circuit. Make sure that the pilot wire is free of any voltage when assembling the connector; otherwise, an inadvertent activation of the extinguishing system could be caused. Figure 2.8.: Solenoid actuator wiring connection. Materials: Body, screws, cap nuts, seals: Brass, stainless steel, nickel-plated steel, elastomeric seals, plastic Table 2.9. Electrical Data of Solenoid Actuator for DN12 valve system Voltage 24 VDC (+/-10%) Temperature range -20 ºC to +50 ºC Max. current at 20 ºC 0.5 A Power input 4.5 W Duty cycle 100% ED Permanent magnet Nd-Fe-B Permanent diagnostic current 0.02 A Protection class (DIN VDE 0580) IP 65 (With assembled cable connector and attached sealing) Table 2.10. Features of Solenoid Actuator for DN12 valve system L1 160mm L2 108mm A Male connectors plug socket DIN EN 175301-803 Form A Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 22 / 74 1 L2 L1 A Figure 2.9.: Solenoid actuator dimensions 2.2.4. Electric Actuator Reset Tool (for ACT-S01) (P/N: HSN-RST-01) The installation, maintenance and inspection of this system may use specialized tools to attach or tighten various components. The reset tool, which is the lever-operated type, is one of them. Remove / unscrew the solenoid actuator. A special resetting tool must be used to re-insert the plunger. Screw the resetting tool to the plunger solenoid valve port whit a wrench of 41 mm. Operate the lever by pulling. Released electrical release device HSN-ACT-S01, see red marking at the push rod. Position A: Reset tool assembly. Position B: The reset tool HSN-RST-01 is mounted hand-tight to the electrical release device HSN-ACT-S01. Then pull the lever by 90° to tense the release device. Figure 2.10.: Reset tool for electric actuator. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 23 / 74 2.2.5. Manual Actuator (P/N: HSN-ACT-M01) The manual actuator allows manual activation of the cylinder valve. It is compulsory to always include such an actuator. Located on top of the cylinder valve or solenoid valve, the lever is manually operated to open the valve and activate the system. It includes a safety pin to prevent accidental activation and this safety pin incorporates a safety seal to avoid incorrect manipulation. 1 4 1 2 3 1 1 Table 2.11. Manual Actuator No. Description 1 Lever 2 Safety lock 3 Connection to cylinder valve or solenoid actuator 4 Safety pin 1 Figure 2.11.: Manual actuator 2.2.6. Pneumatic Actuator (P/N: HSN-ACT-P01) On multiple cylinder systems, the Solenoid Actuator will actuate the master (primary) cylinder and then, in a rapidly occurring sequence, the pneumatic actuator will actuate all other slave cylinders valve, using pressure of the master (primary) cylinder. The pneumatic actuator attaches to the valve actuation connection of each slave cylinder. It receives pressure from the actuation port of the master (primary) cylinder through the pilot actuation hose. The body of the pneumatic actuator is made from brass and an internal mechanism consists of brass piston and pin. 1 Table 2.12. Pneumatic Actuator 1 No. Description 1 Pilot actuation hose connection 2 Connection to cylinder valve 2 1 Figure 2.12.: Pneumatic actuator IMPORTANT NOTICE: After the pneumatic actuator is activated, the pin will fall downwards. The falling pin must be reset by pushing up as before activation. Otherwise, if the pneumatic actuator assembly to top on valve with Before activation After falling pin, the system will discharge incorrectly. Figure 2.13.: Pneumatic actuator activation before vs after Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 24 / 74 2.2.7. Discharge Hose (P/N: HSN-DH-12-400) The discharge hose is used to connect the cylinder valve to the manifold so to direct the agent flow to the pipe network. It is installed between the cylinder valve and the check valve. In case of a modular cylinder, it is installed directly to the discharge pipe. Discharge hose adaptors are used to supply easy connection between discharge hoses and check valves for multiple cylinders systems. 1 Table 2.13. Discharge Hose for DN12 Valve 1 31 2 2 No. Description 1 Inlet W21,8x1/14”" female turnable 2 Flexible hose, DN12, L: 400mm 3 Outlet G3/4” 12UN female turnable Figure 2.14.: Discharge hose for DN12 valve 2.2.8. Pilot Line Hose (P/N: HSN-PLH-01-500) The Pilot Line Hose is a flexible connection in the release circuit to activate the valves pneumatically. It is installed between the pilot line connection from the Master cylinder valve to the pneumatic actuators and/or pneumatic-manual actuator on the slave cylinders. Table 2.14. Pilot Line Hose 1 1 No. 3 2 2 1 Description 1 Swivel female M12x1.5 2 Flexible hose, DN5, L: 500mm 3 Swivel female M12x1.5 Figure 2.15.: Pilot line hose 2.2.9. Pilot Line Nipple Adaptor (P/N: HSN-PNA-01) The Pilot Line Nipple Adaptor is a flexible connection in the release circuit to activate the valves pneumatically. It is installed between the pilot line connection from the Master cylinder valve to the pneumatic actuators and/or pneumatic-manual actuator on the slave cylinders. The Pilot Line Nipple Adaptor available working pressure is 360bar. Table 2.15. Pilot Line Nipple Adaptor 1 1 2 1 No. Description 1 M12x1.5 male threaded connection 2 G1/8" male threaded connection Figure 2.16.: Pilot line nipple adaptor Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 25 / 74 2.2.10. Bleed Valve (P/N: HSN-BLD-01) The Bleed Valve vents pressure or release small leaking gas from the pilot line to protect the system from fault actuation when one or more cylinders leak gas into the pilot actuation line. Pwmax 360bar and Reseating Volume Flow ~30l/min Reseating Pressure 0,5bar (Static) / ~ 0,7bar (Dynamic) 1 Table 2.16. Bleed Valve 1 No. 1 Description G1/8" male threaded connection Figure 2.17.: Bleed valve 2.2.11. Check Valve (P/N: HSN-CHV-012) Check Valves are installed at the discharge manifold in a multiple cylinder arrangement to allow removal of any IG-541 cylinder from the manifold while still retaining a closed system. Check valves are used only in bank of cylinders. It prevents the gas backflowing from the manifold pipe into the cylinders, thus ensuring a complete discharge of all the cylinders. It also acts as a safety element during maintenance operations in case cylinders are disconnected from the manifold and an accidental discharge is produced it prevents the gas from being released and injuring personnel. 2 1 IMPORTANT NOTICE: Make sure that check valve flow direction is showing right position. To be sure about that, follow the flow direction arrow; it must be assembled while arrow showed the flow direction from downward to upward. 1 1 Figure 2.18.: Check valve Table 2.17. Check Valve Description Part Number 1 2 DN12 Check Valve HSN-CHV-012 G3/4” BSP Female Inlet G3/4” BSP Male Outlet 2.2.12. Discharge Pressure Switch (P/N: HSN-DPS-01) Discharge Pressure Switch closes or opens an electric circuit when a discharge from the manifold takes place. Notifying gas flow has occurred. The electric signal may be monitored by a control panel to operate and/or shut down other electrical devices. Once activated it is rearmed manually by pulling the rearming button which incorporates the latching mechanism. This switch can be mounted in any position though the preferred installation is upright. Wiring diagram for connection of switch is shown in below figure. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 26 / 74 1 1 Table 2.18. Discharge Pressure Switch 2 3 1 No. 1 Description 1 Electrical switch body 2 Reset button 3 Connection to manifold, G1/2" male thread Figure 2.19.: Discharge pressure switch IMPORTANT NOTICE: While installation of the Discharge Pressure Switch, gas leakage has to be prevented from the connection point. Discharge Pressure Switch maximum working pressure is 360 bar. Discharge Pressure Switch body material are brass, nickel-plated steel, elastomeric seals and plastic. Table 2.19. Electrical Data of Discharge Pressure Switch Max voltage 400V AC/DC Temperature range -20 ºC to +60 ºC Thermal current 10 A Conditional short circuit current 100 A acc. to EN 60947-5-1 Protection against short circuits Type aM fuse 10 A 500 V Pollution degree 3 IP 67 acc. to EN 60529 (With cable gland presenting Protection degree same or higher protection degree) 2.2.13. Pressure Gauges A pressure gauge is provided with each cylinder valve to indicate the pressure inside the cylinder. Its electrical contact allows real time monitoring notifying in case of leaks. 1 2 3 1 1 1 Table 2.20. Pressure Gauges No. Description 1 Contacted point indicator * 2 Gauge display screen 3 Connection to cylinder valve * There is contacted point indicator at low pressure switch type gauge models only. Figure 2.20.: Pressure gauge IMPORTANT NOTICE: • Use only pressure gauges supplied by Honeywell. • The pressure gauges can be assembled and disassembled under pressure. • Before mounting the pressure gauge, the plug screw at the pressure gauge connection on the valve shall be unscrewed. When dismounting the pressure gauge the plug screw shall be screwed back in place. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 27 / 74 Table 2.21. Available Types of Pressure Gauges Description Part Number 0-315 Bar Pressure gauge with low pressure switch *Available for 200bar storage system 0-400 Bar Pressure gauge with low pressure switch *Available for 300bar storage system Contacted Switch HSN-IG-PGV-NOC-01 HSN-IG-PGV-NOC-02 0-160 Bar Pressure gauge with low pressure switch at 90bar (NO) HSN-PGV-NOC-300 Gives NO contact at 180bar Gives NO contact at 270bar Gives NO contact * Available for pilot cylinders at 90bar Table 2.22. Electrical Data of Pressure Gauges Switching voltage 4.5 ... 24 V DC/AC Switching current 5 ... 100 mA Contact load max. 2.4 W Permissible temperature -20 ºC to +60 ºC Ingress protection IP 65 acc. to EN 60529 / lEC 529 2.2.14. Discharge Nozzles Discharge nozzles are used to uniformly distribute the IG-541 inert gas system. They are performance tested to ensure that the agent is discharged within 60-120 seconds and properly dispersed throughout the protected area. IG-541 inert gas agent is distributed within the protected area by the discharge nozzle which is sized to ensure the correct flow of agent for the risk. Nozzles are available with 180⁰ and 360⁰ discharge pattern. The 180⁰ nozzle is engineered to provide a 180⁰ discharge pattern for sidewall applications. The 360⁰ nozzle offers a full 360⁰ discharge pattern for installations where nozzles are located in the center of the hazard. Nozzles are supplied as standard in brass with BSPT female thread. The agent flow is controlled by a calibrated diaphragm disc inside the nozzle body, determined by the results from the hydraulic calculation software VdS approved. It guarantees a homogenous gas distribution throughout the volume. 1 1 Table 2.23. Discharge Nozzle Parts 2 2 No. Description 1 Circlip for Diaphragm Disc Assembly 2 Diaphragm Disc 3 180/360 Degree Nozzle 3 1 Figure 2.21.: Discharge nozzles 180 degree & 360 degree Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 28 / 74 Table 2.24. Discharge Nozzles Size Type Part Number Type Part Number DN10 (3/8”) HSN-NOZ-01-10 HSN-NOZ-02-10 DN15 (1/2”) HSN-NOZ-01-15 HSN-NOZ-02-15 DN20 (3/4”) HSN-NOZ-01-20 HSN-NOZ-02-20 DN25 (1”) 180 Degree HSN-NOZ-01-25 360 Degree HSN-NOZ-02-25 DN32 (11/4”) HSN-NOZ-01-32 HSN-NOZ-02-32 DN40 (11/2”) HSN-NOZ-01-40 HSN-NOZ-02-40 DN50 (2”) HSN-NOZ-01-50 HSN-NOZ-02-50 2.2.15. Pilot Cylinders The pilot cylinder is used for activating the slave cylinders in a selector valve system configuration. It can be activated manually or electrically. Cylinders which sole purpose is to activate the extinguishing system by supplying a pneumatic pressure. These cylinders can be placed remotely and be of different types and styles. Figure 2.22.: Pilot cylinder Table 2.25. Pilot Cylinders Part Number Cylinder Size Max. No. Of Cylinders Max. Actuation Line Length (m) HSN-PLT-EU-SM-005 5L 20 25 HSN-PLT-EU-SM-013 13L 35 35 HSN-PLT-EU-SM-040 40L 50 45 IMPORTANT NOTICE: * The actuation internal diameter should be at least 6mm. When it is necessary to place the pilot cylinder away from the main inert cylinder group, the diameter of the copper tube or other activation line element that can be used as an alternative to the pilot hose must be at least 6 mm. The pressure resistance of this tubing element must be at least 140 bar. The maximum activation line lengths specified in the table related to the design of the pilot line shall be valid. The maximum activation line lengths include the lengths of the pilot hoses. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 29 / 74 It’s possible to increase the maximum no. of 50 cylinders actuated by one master valve by using a “bypass” to power up the actuation line after a specific no. of cylinders. There are two different options for this bypass: 2.2.15.1. Master Pilot Cylinder System When it is necessary to use more than 10 Inert cylinders, activation with the master pilot cylinder system is required. The solenoid actuator 24V DC is used in the master pilot cylinder system. Table 2.25. shall be taken as reference for system limitations. Figure 2.23.: Master Pilot Cylinder System 2.2.15.2. Booster Pilot Cylinder System In systems with more than 50 cylinders, a booster pilot cylinder can be used as an alternative to the 2nd master pilot cylinder. The pneumatic actuator is used in the booster pilot cylinder system. Table 2.25. shall be taken as reference for system limitations. IMPORTANT NOTICE: After a certain no. of 49 cylinders, you place a T-fitting inside the pilot line. The additional connection will be connected with the pilot port (G1/8” slave valve port) of the prior cylinder valve as shown below. Figure 2.24.: Master & Booster pilot cylinders system Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 30 / 74 2.2.16. Selector Directional Valves Selector directional valves are used to protect multiple areas using a common cylinder bank. The valves act as blocking devices directing the gas flow only in the compartment which requires the system to be discharged. Selector Valves allow a single agent supply to be utilized for protection of multiple hazards, reducing the total amount of agent and number of containers required. When utilizing multiple containers to protect multiple hazards it is necessary to use selector valves to divert the flow of agent into the activated hazard. The selector valves may be activated electronically or manually by pneumatically connecting to the solenoid actuator provided with the selector valve. The selector valve pneumatic actuator working pressure should be at least 6 bar and maximum 10 bar. Where more than one zone is to be protected by a common Central Storage Bank the selector valve is used to direct the agent flow into the appropriate zone. When designing a system utilizing selector valves the designer must always calculate the largest zone of protection when sizing the container bank. Selector valves are 2-way ball valves with bore and it is installed in the discharge piping downstream of the extinguishant containers, to direct the extinguishant to the appropriate hazard enclosure. Selector valve sizes range from 3/4” to 4” (20 to 100 mm nominal). L4 1 1 1 31 1 4d 11 f1d 1 5d f11 d ffd1 6d dd ff11 1 fd dd 1 d ff d dd ff d d f d 21 L2 L3 Figure 2.25.: Selector valve L1 Figure 2.26.: Composition of the selector valve Table 2.26. Selector Valve Features Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s Position Designation 1 Limit switch box with optical indication 2 Wrench flats for manual actuation 3 Pneumatic connection 4 Actuator 5 Connecting shaft 6 Ball valve P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 31 / 74 Table 2.27. Selector Valves Details Part No Size L1 L2 L3 L4 HSN-SV-01-020 DN20 189 95 49 108 HSN-SV-01-025 DN25 189 113 58 108 HSN-SV-01-032 DN32 231 111 81 133 HSN-SV-01-040 DN40 257 130 100 154 HSN-SV-01-050 DN50 257 140 118 154 HSN-SV-01-065 DN63 334 150 208 161 HSN-SV-01-080 DN80 374 170 258 182 HSN-SV-01-100 DN100 519 200 260 242 Table 2.28. Selector Valves Part Number Description Thread Type HSN-SV-01-020 3/4" Selector Valve BSP Threaded HSN-SV-01-025 1" Selector Valve BSP Threaded HSN-SV-01-032 11/4" Selector Valve BSP Threaded HSN-SV-01-040 11/2" Selector Valve BSP Threaded HSN-SV-01-050 2" Selector Valve BSP Threaded HSN-SV-01-065 21/2" Selector Valve ISO Flanged HSN-SV-01-080 3" Selector Valve ISO Flanged HSN-SV-01-100 4" Selector Valve ISO Flanged To The Inert Gas Cylinder From The Pilot Cylinder Figure 2.27.: Selector valve system details Figure 2.28.: Selector valve completer kit details Table 2.29. Selector Valves Limitation Part Number HSN-SV-01-020/100 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s Size Max. No. of Selector Max. Actuation Pilot Valves Line Length (m) ** 45 3/4" to 4" P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 32 / 74 IMPORTANT NOTICE: ** The limitation of selector valve quantity is related to pilot line length and design. The selector valve pneumatic actuator working pressure should be at least 6 bar and maximum 10 bar. 2.2.17. Pilot Line Non-Return Valve (P/N: HSN-NRV-01) The Non-return Valve kits are used in the Selector Valve pneumatic actuation line. The correct placement of these kits within the actuation lines ensures that the required numbers of cylinders from a central bank are operated. The kits also protect against unwanted back pressure within the actuation line. The design of the Non-return Valve is such that it can be mounted in any orientation and does not require any maintenance. Figure 2.29.: Non-return valve 2 1 1 2 Table 2.30. Non-Return Valve No. Description 1 Inlet Thread, G1/8” EN ISO228 2 Outlet Thread, G1/8” EN ISO228 Figure 2.30.: Dimensions of Non-return valve Table 2.31. Technical Data of Non-Return Valve Nominal width 4mm (12,57mm²) Maximum pressure PW max 360 Bar Temperature range 20 ºC to +65 ºC Material valve body Stainless Steel Gasket materials Gasket materials must be compatible with used gases 2.2.18. Constant Pressure Regulator Valve (P/N: HSN-CPR-10) The Constant-pressure-regulator is intended for use as a pressure reducing device in fixed automatic fire suppression systems using inert gas agents. Figure 2.31.: Constant pressure regulator valve Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 33 / 74 IMPORTANT NOTICE: Pressure regulators are not assumed to be so called safety accessories in terms of directive 2014/68/EU of the European Parliament (“Pressure Equipment Directive”). Therefore usage of pressure regulators type HSN-CPR-10 does not supersede the installation of appropriate safety equipment to prevent components mounted to the outlet of the regulator from being over pressurized. In particular, but not exclusively, this refers to piping, fittings, selector valves and nozzles. The regulator must be installed directly to the cylinder valve and the outlet has to be connected to a suitable manifold by a hose. Table 2.32. Constant Pressure Regulator Valve 11 2 No. Description 1 1 1 1 Inlet Thread, W21,8X1/14” DIN 477, Female d d 2 Outlet Thread, W21,8X1/14” DIN 477, Male f f 3 L = 145mm, Ø64mm d L d f f d Figure 2.32.: Dimensions of constant pressure regulator valve d Table 2.33. Technical Data of Constant Pressure Regulator Valve Nominal size 12mm Permissible pressure at inlet Max.360 Bar Outlet pressure 60bar (+2/-6 bar) (static) - max. 60bar (dynamic) Temperature range TS -20 ºC to +50 ºC Body parts: brass, stainless steel Materials Gasket parts: EPDM, PUR, PA Mounting torque (inlet & outlet) 55Nm ±5 Smallest allowed nozzle diameter at outlet Ø 3mm The component must be screwed onto the outlet of the cylinder valve via the inlet connection thread. A flex hose must be connected to the regulator outlet by screwing on its swivel nut. The other end of the hose must be properly connected to the extinguishing system. Figure 2.33.: Assemblies of constant pressure regulator valve Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 34 / 74 2.2.19. Pressure Reducer (P/N: HSN-PRD-01) The pressure reducer can automatically relieve pressure in the pilot line. A close section of pipe requires a safety valve between the pilot cylinder and the pneumatic actuator of selector valves. It must be used only for selector valve systems. The set point is 8 bar and PW max: 100 bar. Pressure reducer is suitable with N2 gas and N2 gas inlet pressure should be max 100 bar. Pressure reducer will be setted 8 bar at the factory, it is not possible to change the set pressure in the field. 2.2.20. Manifold Pressure Safety Valve (P/N: HSN-PSV-01) The pressure safety valve can automatically relieve pressure in the pipework system or manifold. A close section of pipe requires a safety valve between the container valves and selector valves. It must be used only for selector valve systems. The set point is 100 bar and PW max: 1500 bar. 2.2.21. Vent Valve (P/N: HSN-VV-01) It is used to vent the air fills the actuator of the selector valve. And therefore, allows the valve to return to the its first position. It should be used for the selector valve systems. PW max: 360 bar. 2.2.22. Label (P/N: HSN-LBL-IG541) Figure 2.34.: Label for IG-541 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 35 / 74 Figure 2.35.: Label for pilot cylinder 2.2.23. Caution Signs Figure 2.36.: Caution signs Table 2.34. Caution Signs Description Part Number Protected Room Caution Sign HSN-CS-IG541-01 Manual Release Point Caution Sign HSN-CS-MRP-01 Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 36 / 74 3. 3.1. Other Accessories Pilot Cylinders (ATEX) The pilot cylinder is used for activating the slave cylinders in a selector valve system configuration. It can be activated manually or electrically. The electrical activation can be ATEX solenoid actuator. Table 3.1. Pilot Cylinder (ATEX) No. Description 1 Pilot valve 2 Solenoid actuator 3 Manual actuator 4 Pressure gauge Figure 3.1: Typical ATEX pilot cylinder & valve assembly Table 3.2. Pilot Cylinders (ATEX) Details Part Number Cylinder Size Max. No. Of Cylinders Max. Actuation Line Length (m) HSN-PLTA-EU-SM-005 5L 20 25 HSN-PLTA-EU-SM-013 13L 35 35 HSN-PLTA-EU-SM-040 40L 50 45 IMPORTANT NOTICE: * The actuation internal diameter should be at least 6mm. When it is necessary to place the pilot cylinder away from the main inert cylinder group, the diameter of the copper tube or other activation line element that can be used as an alternative to the pilot hose must be at least 6 mm. The pressure resistance of this tubing element must be at least 140 bar. The maximum activation line lengths specified in the table related to the design of the pilot line shall be valid. The maximum activation line lengths include the lengths of the pilot hoses. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 37 / 74 4. 4.1. System Design Introduction There are two main elements of system design. The first is the risk assessment, determining the type of protection required, considerations such as ventilation, openings and restrictions, equipment location etc. The second is calculating the quantity of IG-541 clean agent required, including floor and / or ceiling voids, positioning of nozzles, electrical requirements, etc. The system design is based on the requirements of EN15004-1 & EN15004-10 (current edition). 4.1.1. Hazard Analysis The following steps must be taken to design IG-541 inert gas system. 1. Perform a hazard analysis of protected area. 2. Determine the class of fire hazards. 3. Determine the minimum and maximum ambient temperature for the hazard. 4. Calculate IG-541 agent quantity to provide required design concentration at minimum expected ambient temperature in protected area. Calculate the quantity of IG-541 inert gas required to provide the proper design concentration at the minimum expected hazard temperature. All system design calculations are calculated at minimum design concentration to determine IG541 agent quantity. Agent quantity shall be adjusted if system is installed at altitudes > 1000m. If hazard altitude is not listed in the table, find the altitude next lower than the hazard altitude and determine the correction factor. See following to the altitude correction factor. Table 4.1. Altitude Correction Factors Altitude (m) -1000 Sea Level 1000 1500 2000 2500 3000 3500 4000 4500 Correction Factor 1.130 1.000 0.885 0.830 0.785 0.735 0.690 0.650 0.610 0.565 Maximum design concentration should be at the maximum anticipated enclosure temperature, for comparison see NOAEL / LOAEL values. IG-541 inert gas fire extinguishing system is suitable for use with the following materials. Surface Class A: Fires involving solid materials usually of an organic nature, in which combustion normally takes place with the formation of glowing embers. Class B: Fires involving flammable liquids or liquefiable solids and flammable gases. Higher Hazard Class A: Fires involving energized electrical equipment where the electrical no conductivity of the extinguishing media is of importance. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 38 / 74 Table 4.2. IG-541 reference extinguishing and design concentrations Fuel Class B Extinguishment Minimum design % by volume % by volume 31.7 Heptane (cup burner) 37.0 Heptane (room test) 48.1 Surface Class A Wood crib 28.2 PMMA 30.7 PP 30.6 ABS 30.7 Higher Hazard Class A a 39.9 45.7 The extinguishment values for the Class B and the Surface Class A fuels are determined by testing in accordance with EN 15004-1:2008, Annexes B and C. The minimum design concentration for the Class B fuel is the higher value of the heptane cup burner or room test heptane extinguishment concentration multiplied by 1,3. The minimum design concentration for Surface Class A fuel is the highest value of the wood crib, PMMA, PP or ABS extinguishment concentrations multiplied by 1,3. In the absence of any of the 4 extinguishment values, the minimum design concentration for Surface Class A shall be that of Higher Hazard Class A. See EN 15004-1:2008, 7.5.1.3, for guidance on Class A fuels. The extinguishing and design concentrations for room-scale test fires are for informational purposes only. Lower and higher extinguishing concentrations than those shown for room-scale test fires may be achieved and allowed when validated by test reports from İnternationally recognized laboratories a The minimum design concentration for Higher Hazard Class A fuels shall be the higher of the Surface Class A or 95 % of the Class B minimum design concentration. Reference: EN15004-10, Table 4 — IG-541 reference extinguishing and design concentrations 4.1.2. Determine which components are required Cylinder volume, quantity and fill requirements. Refer to Table 2.2 Cylinder framing, mounting brackets, etc. Detection and control equipment required. Other system requirements, such as reserve supply, pressure switches, etc. 4.1.3. Positioning of cylinders • Locate cylinders based on the following: Number of cylinders required. • Storage temperature/environmental considerations, such as weather, area classification and corrosive environment. • Floor loading. 4.1.4. Positioning of piping • Nozzle location. • Structural members for bracing the pipe. 4.1.5. Pipe size and layout • Draw piping isometric. • Dimensions of all pipe sections. • Locate all fittings. • Note all elevation changes. The preceding information will be entered into the computer program. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 39 / 74 4.1.6. Manifolds It may be necessary to manifold agent containers to provide the required amount of agent for a hazard or to make available the proper increments of agent weight for the protection of multiple hazards. Whenever containers are manifolded, the following rules must be observed. 1. All containers connected to the same manifold or pipe must be the same size and filled with the same agent weight, pressure and fill density. 2. Agent containers must be located in a single row and spaced according to section. 3. A connected reserve may be employed in some circumstances providing a secondary supply of agent. 4. Flexible discharge hoses and check valves must be used at each inlet. Figure 4.1: Manifold details IMPORTANT NOTICE: Manifold available working pressure have to be at least 100 bar (1450 psi). Class 150 and cast-iron fittings must not be used. Manifolds have to be tested at 1.5 times of available working pressure. 4.1.7. Super-pressurization Containers for IG-541 are not super-pressurized. 4.1.8. Design criteria The complexity of two-phase flow formulas does not allow for any simple method of manual calculation. For this reason, the flow calculations and design criteria described in this manual have been programmed into a computer software program. To determine the proper procedures for applying the input parameters to the IG-541 inert gas system computer program. There are a number of limitations to these input parameters which must be observed if accurate results are to be obtained. Most of these limitations are in the program. However, there are certain restrictions that must be addressed by the system designer before applying the input data. 4.1.9. Design example and calculations Minimum agent quantity is based on the hazard volume at the minimum anticipated temperature and concentration required. To determine the minimum agent quantity the following equation is used: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 40 / 74 𝑽 𝟏𝟎𝟎 m = 𝑺 xln(𝟏𝟎𝟎−𝒄)xCAlt [kg] m = Required Agent Quantity (m3) V = Hazard Net Volume (m3) (the enclosed volume minus the fixed structures imperious to the ext.) CAlt = Altitude Correction Factor (see Table 3.1) C = Required IG-541 concentration. (% by volume) SR = k1 + k2xTR S = k1 + k2xT SR= Specific Reference Volume @ 20 ⁰C [0.65799 + (0.002239x20) = 0.70277 (m3/kg)] S = Specific Volume (m3/kg) T = 20 ⁰C Design temperature in Hazard Area (⁰C) TR = Reference temperature (⁰C) Calculation for two rooms and floor void with the following dimensions: Switch Room: 3.5m x 3.0m x 3.0m = 31.50m3 Computer Room: 7.0m x 6.0m x 3.0m = 126.00m3 Floor Void: 7.0m x 6.0m x 0.30m = 12.60m3 Altitude (Sea Level) = 1.000 for calculation example Switch Room: (45.2 % required design concentration example only) m: 31.5 0.70277 100 xln(100−45.2)x1 = 26.96 kg Computer Room: (45.2 % required design concentration example only) m: 126.0 100 xln(100−45.2)x1 = 107.84 kg 0.70277 Floor Void: (45.2 % required design concentration example only) m: 12.6 0.70277 100 xln(100−45.2)x1 = 10.78 kg Q R = m x SR QRswitch= 26.96 x (0.65799 + (0.002239x20)) = 18.95 m3 QRcomputer= 107.84 x (0.65799 + (0.002239x20) = 75.78 m3 QRFloor= 10.78 x (0.65799 + (0.002239x20) = 7.57 m3 It is determined from the above that both the Switch Room and the Computer Room can be fed by one manifolded system using 5 x 80L IG-541 containers, each filled with 19.00 m3 of inert gas. The Floor Void would use 1 x 40L IG-541 container filled with 7.60 m3. (According to the Table 1.7. Agent Container Fill Quantity for 300Bar) Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 41 / 74 Figure 4.2: Example of system Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 42 / 74 Table 4.3. IG-541 total flooding quantity Temperature Specific IG-541 Volume Requirements per Unit Volume of Protected Space V/V (m3/m3) T Vapor This information refers only IG-541, and may not represent any other products ⁰C Volume containing nitrogen and argon as a component 3 Design Concentrations (% - by volume) S, (m /kg) 34,0 38,0 39,9 42,0 45,7 46,0 48,1 50,0 54,0 58,0 62,0 -20 0,6102 0,481 0,554 0,588 0,631 0,706 0,714 0,758 0,803 0,899 1,005 1,120 -15 0,6221 0,472 0,543 0,577 0,619 0,692 0,700 0,744 0,787 0,882 0,985 1,099 -10 0,6341 0,463 0,533 0,566 0,607 0,679 0,686 0,730 0,772 0,865 0,966 1,078 -5 0,6460 0,454 0,523 0,556 0,596 0,667 0,674 0,716 0,758 0,849 0,948 1,058 0 0,6580 0,446 0,513 0,546 0,585 0,665 0,661 0,703 0,744 0,833 0,931 1,038 5 0,6699 0,438 0,504 0,536 0,574 0,643 0,649 0,690 0,731 0,818 0,914 1,020 10 0,6819 0,430 0,495 0,527 0,564 0,632 0,638 0,678 0,718 0,804 0,898 1,002 15 0,6938 0,423 0,486 0,517 0,554 0,6211 0,627 0,667 0,705 0,790 0,883 0,984 20 0,7058 0,416 0,478 0,509 0,545 0,610 0,616 0,655 0,693 0,777 0,868 0,968 25 0,7177 0,409 0,470 0,500 0,536 0,600 0,606 0,644 0,682 0,764 0,853 0,951 30 0,7297 0,402 0,462 0,492 0,527 0,590 0,596 0,634 0,670 0,751 0,839 0,936 35 0,7416 0,395 0,455 0,484 0,518 0,581 0,586 0,624 0,659 0,739 0,825 0,920 40 0,7536 0,389 0,448 0,476 0,510 0,571 0,577 0,614 0,649 0,727 0,812 0,906 45 0,7655 0,383 0,440 0,469 0,502 0,562 0,568 0,604 0,639 0,716 0,799 0,892 50 0,7775 0,377 0,434 0,462 0,494 0,554 0,559 0,595 0,629 0,704 0,787 0,878 55 0,7894 0,371 0,427 0,452 0,487 0,545 0,550 0,586 0,619 0,694 0,775 0,864 60 0,8014 0,366 0,421 0,448 0,479 0,537 0,542 0,577 0,610 0,683 0,763 0,851 65 0,8133 0,360 0,414 0,441 0,472 0,529 0,534 0,569 0,601 0,673 0,752 0,839 70 0,8253 0,355 0,408 0,435 0,465 0,522 0,526 0,560 0,592 0,663 0,741 0,827 75 0,8372 0,350 0,403 0,429 0,459 0,514 0,519 0,552 0,584 0,654 0,730 0,815 80 0,8492 0,345 0,397 0,432 0,452 0,507 0,511 0,545 0,575 0,645 0,720 0,803 85 0,8611 0,340 0,391 0,417 0,446 0,500 0,504 0,537 0,567 0,636 0,710 0,792 90 0,8731 0,335 0,386 0,411 0,442 0,493 0,597 0,530 0,560 0,627 0,700 0,781 V/V is the agent volume requirement (in cubic meters per cubic meter); i.e. the quantity Q (in cubic meters) of agent required at a reference temperature of 20 °C and a pressure of 1,013 bar per cubic meter of protected volume to produce the indicated concentration at the temperature specified: QR = m⋅ SR where; SR is the specific reference volume (in cubic meters per kilogram); i.e. the specific vapour volume at the filling reference temperature for superheated IG-541 vapor at a pressure of 1,013 bar which may be approximated by the formula: SR = k1 + k2 ⋅TR where k1 = 0,65799; k2 = 0,002239; TR is the reference temperature (in degrees Celsius); i.e. filling temperature (20 °C in the table) m = V/S xln(100/(100-c)) V is the net volume of hazard (in cubic meters); i.e. the enclosed volume minus the fixed structures impervious to extinguishant. T is the temperature (in degrees Celsius); i.e. the design temperature in the hazard area. S is the specific volume (in cubic meters per kilogram); the specific volume of superheated IG-541 vapour at a pressure of 1,013 bar may be approximated by S = k1 + k2 ⋅T c is the concentration (in percent); i.e. the volumetric concentration of IG-541 in air at the temperature indicated, and a pressure of 1,013 bar absolute. 4.1.10. Duration of discharge The inert gases do not produce any decomposition products, the gas is discharged over longer time, but in such a way that the extinguishing concentration is reached within 60-120 seconds. And 95% of the minimum design concentration shall be achieved within the discharge times listed below. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 43 / 74 Table 4.4. Discharge time for inert gases Discharge Time ISO 14520 EN 15004 NFPA 2001 VdS 2380 2015 Edition 2019 Edition 2018 Edition 2016-06 Class A 120 seconds 120 seconds 120 seconds 120 seconds Class B 60 seconds 60 seconds 60 seconds 60 seconds Class C 60 seconds 60 seconds 120 seconds 60 seconds IMPORTANT NOTICE: The discharge time required to achieve 95 % of the design concentration shall not exceed the given values, or as otherwise required by the authority. 4.1.11. Room Integrity and Pressure Ventilation The designer of a fire suppression system should be aware that the discharge of any gaseous extinguishing agent into an enclosure will change the pressure within that enclosure. This could affect the structural integrity of the enclosure. In considering room integrity, the designer should consider that the discharge of any gaseous suppression agent into an enclosure gives rise to a change in the pressure within that enclosure. Under some conditions, this could affect the structural integrity of the enclosure. In some cases, the protected enclosure requires a pressure relief device and in all cases the customer must be made aware of the pressurization level expected, from calculation, within the enclosure. The natural leakiness of the enclosure may form the basis for these calculations, but that can only be accurately assessed with the room integrity test equipment. When conducting this test, look for the minimum amount of leakage and not the maximum amount of leakage, as required with a standard room integrity test. The two tests differ as the doors surrounding the protected room are left closed, as opposed to being held open during a standard room integrity test. Fire suppression systems that use inert gas extinguish fires by reducing the level of oxygen to a point where combustion of the flammables cannot be maintained. The amount of gas discharged into the hazard results in a positive pressure, which displaces the air from the room. Suitable means of pressure relief/vent shall always be employed to avoid structural damage to the building and equipment. To avoid personal and property damage, the fire and IG-541 released by the pressure relief device must not result in a hazard outside the extinguishing zone. For this reason, the pressure relief/vent should always be directed to free air. Although ‘cascade’ venting may be required in certain circumstances. If a duct cannot be avoided, the duct must be gas tight, and should lead directly into the open. The duct must be designed to make sure that during pressure relief the fire is not allowed to spread into other hazards or areas. The pressure relief device shall close after completed pressure relief. Preferably the pressure relief device should be equipped with its own power source and should be able to open and close automatically. Pressure relief devices, which depend on an external power supply, shall be triggered directly by the extinguishing system and shall be energized by the extinguishing system. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 44 / 74 (Preferably with non-electric energy) If electrically triggered pressure relief devices are used, the guidelines for triggering the extinguishing system shall be observed. If pressure relief takes place through a vent, or if ducted directly into free air, and there is no requirement for a fire-resistant segregation of the perimeter walls containing the pressure relief vent; louvered shutters can be used opening as a result of the over pressure, closing by their own weight or via springs at a certain overpressure in the room. If requirements in terms of structural segregation must be observed, the pressure relief device shall be designed accordingly. The pressure relief vent shall be installed to make sure that it is not positioned in the immediate discharge area of the nozzles. Pressure relief must not be provided in form of active exhaust suction devices. Each separate space within the flooded zone must be equipped with its own pressure relief vent device. The pressure relief device must be sufficiently dimensioned taking into account the allowable overpressure in the room, the mass flow during the release and the type of pressure relief device to be used. (Drag coefficient of the vent, pressure drop in duct, etc.). If the pressure relief vent is provided in form of a duct arrangement, the pressure drop of the duct must be calculated additionally and must be considered when dimensioning the cross-sectional surface of the vent. A duct shall always be suitable for taking the applied pressure and the gas flow. No enclosure is 100% tight; a certain amount of leakage to adjacent areas is to be anticipated during and following an IG-541 discharge. Pressure relief vents shall be installed by a qualified ventilating company. IMPORTANT NOTICE: It is the customer’s responsibility to determine the enclosure strength and not the fire protection system supplier. The customer must advise the allowable pressure differential that the enclosure can withstand without sustaining damage. If the customer does not communicate the allowable pressure that the enclosure can withstand, obtain the customer’s acceptance of the proposed figures used. To estimate the free venting area, use the following formula: A: MxSIG−541 √PxSH & SH: CxSIG−541 100 +( 100−C 100 )x SAIR Where: A = Is the total vent area (square meters) M = Is the mass flow of extinguishant (kgs/second) SIG-541 = Is the specific vapor volume of extinguishant (cubic meters/kg) P = Is the maximum room strength (pascals) SH = Is the specific vapor volume of the homogenous mix (cubic meters/kg) C = Is the design concentration (%) SAIR = Is the specific vapor volume of air given by: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 45 / 74 SAIR = 0.65799 + 0.002239xT T = is the temperature in degrees C IMPORTANT NOTICE: This calculation is for estimation purposes only. The final free vent area must be calculated by using hydraulic flow calculation software. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 46 / 74 5. 5.1. Installation General Equipment Installation IG-541 inert gas fire extinguishing system must be installed to facilitate proper inspection, testing, manual operation, recharging and any other required maintenance as may be necessary. Equipment must not be subject to severe weather conditions or mechanical, chemical or other damage that could render the equipment inoperative. Equipment must be installed in accordance with EN15004-1 (current edition). 5.2. Order of Installation • Container / cylinder installation • Piping and nozzles • Actuation controls • Ancillary equipment • Completion procedures Specific installation drawings must be prepared for the hazard area in accordance with system design as calculated by the IG-541 hydraulic flow program. These drawings should be followed closely in order to ensure the system meets its design criteria. The pipe network is sized in order to obtain correct discharge time, nozzle pressures, agent quantity and various other design considerations. If for any reason, the pipe network requires. Modifications the system must be recalculated before proceeding with installation. Installation drawings contain the following information. • Enclosure volumes • Agent quantities • Scaled pipe network plan • Pipe network isometric • Pipe diameters, pipe length drops and rises • Nozzle data • Container / cylinder data • Actuator technical data • Low pressure switch wiring chart • Fittings data Installation drawings shall be submitted for approval to the appropriate authority prior to system installation. The container weight is checked at the factory prior to dispatch and recorded on the label attached to the container. If there is any doubt regarding the weight, or leakage is suspected, the container should be weighed to confirm there is no weight loss. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 47 / 74 5.2.1. Container installation The container location is identified on the system drawings and should be protected from extremes of temperature and be accessible for service and maintenance. The containers must be installed vertically on the floor and firmly secured to a wall or bulkhead. No safety outlet and actuation caps should be removed at this stage. 5.2.1.1. Single container installation 1. Fix the back channels of the mounting brackets to the wall at the appropriate heights using suitable anchor type bolts. 2. Position the container against the back channel with the valve outlet pointing left. 3. Insert the container straps at top and bottom and secure with the bolts. 4. Remove the safety outlet cap from the valve outlet adaptor. 5. With the outlet cap removed from the valve outlet adaptor, connect flexible discharge hose or valve outlet adapter. 6. Remove the protection cap from the cylinder valve actuation port. 7. Install the manual and solenoid actuator to the cylinder valve actuation port. Figure 5.1: Single container assembly Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 48 / 74 5.2.1.2. Multiple container installation Containers are manifolded together for three main reasons: • To reduce the amount of piping required by connection to one feeder pipe. • For systems that require main and reserve system configuration. • Combining the correct containers to obtain the required quantity of agent within a specific hazard area. 1. Fix the back channels of the mounting brackets to the wall at the appropriate heights using suitable anchor type bolts. (see Figure 5.2) 2. Position the containers against the back channels with the valve outlets pointing left at the required spacing for the manifold ports. (see Figure 5.3) 3. Insert the container straps at top and bottom and secure with the nut bolts. (see Figure 5.3) 4. Remove the safety cap from one cylinder outlet port and connect the flexible discharge hose to the cylinder outlet port. (see Figure 5.4 and 5.5) 5. Remove the protection caps from the cylinder actuation ports. (see Figure 5.5) 6. Install the manual, solenoid and pneumatic actuators to the cylinder valve actuation ports. (see Figure 5.5 and 5.6) Figure 5.2: Manifold and strap assembly for multiple container Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 49 / 74 Figure 5.3.: Cylinder assembly with cylinder protection cap Figure 5.4.: Cylinder assembly after removing cylinder protection cap Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 50 / 74 Figure 5.5.: Discharge and actuation line assembly for multiple container Figure 5.6.: Assembly of discharge hose & check valve with container Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 51 / 74 A B C D Figure 5.7.: Multiple cylinder installation dimension Table 5.1. Multiple cylinder installation dimensions Type A (mm) B (mm) C (mm)* D (mm) E (mm) 80L 375 1335 2188 300 350 140L 325 1225 2067 400 436 *These can change according to manifold dimension and discharge hose length. 5.2.2. Pipe installation In general, the installation should commence at the union elbow/manifold assembly and progress along to the discharge nozzles. Install the pipework to the installation drawings provided, ensuring that the following is adhered to: 1. The piping material must conform to the requirements of EN15004-1 / Sec 6.3.2. 2. The pipe must be reamed, blown clear and swabbed with an appropriate solvent to remove mill varnish and cutting oil before assembly. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 52 / 74 5.2.2.1. Pipe and fittings system The pipe system is used for distributing the IG-541 to the protected enclosures. Typically the pipe is EN10220/10217 P235TR1, rated for the applicable working pressure (standard 80bar) and has material Charpy V test performed at -40°C. Typically the fittings are EN 10242/ 10226/ 1562 with special requirement per VdS standard. Fittings are type tested to 30MPa (300bar) and marked with a red dot and the letter “D” stamped into it. Fittings are suitable for use in installations with clean agent fire extinguishing systems and the low temperature generated during discharge of such system. Pipes to ASTM Sch40, 80, 160 may also be used. Fittings ASME 3000lb and above may also be used. Pipes should be threaded and screwed or welded. If other type of assembly is used, the manufacturer of the pipe components must declare that it is suitable for use in fire suppression system using inert gas (here taken into consideration pressure and temperature during use and discharge). Pipes and fittings may be Black, Galvanized or Stainless steel. IMPORTANT NOTICE: Cast iron or seamed steel and non-metallic pipes shall not be used. 5.2.2.2. Pipe hangers & fasteners All fasteners used must be of good quality and made from material suitable for the environment they are being used in. Installation hardware for the pipe system must be able to support the pipe system as well as the forces from nozzles during the discharge. General requirements are: Pipe must be allowed to move within the brackets due to length contraction during discharge due to the temperature change. If the temperature rises from +20°C to +200°C, the ultimate tensile strength of the material used shall not be reduced by more than 25%. Combustible materials shall not be used. Pipe supports shall be designed so that under extreme load there is no danger of the installation being damaged. Pipe brackets shall completely surround the pipe and be closed. The material from which a pipe support is manufactured shall be at least 3mm thick. If galvanized, a thickness of 2,5mm will suffice. This does not, however, apply to a pipe support made from hot-dip galvanized material, which may have a minimum size of 25mm x 1,5mm for pipes up to DN50 (12mm x 1,5mm, if type approved). Pipe supports shall connect the pipe work directly to the building structure. Building members, to which primary supports are attached, shall be strong enough to carry the load. If not, additional links to load-bearing members shall be created. 5.2.2.3. Installation of pipe and fittings Pipe and fittings must be installed in strict accordance with the system drawings and good commercial practices. The piping between the cylinder and the nozzles must be the shortest route possible, with a minimum of fittings. Any deviations in the routing or number of fittings must be approved by the design engineer before installation. Piping must be reamed free of burrs and ridges Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 53 / 74 after cutting, welding or threading. Joint compound or thread tape must be applied only to the male threads of the joint, excluding the first two threads. All piping must be blown clear with dry nitrogen or compressed air before installing the discharge nozzles. 5.2.2.4. Piping support installation Pipe supports shall be of a non-combustible material, shall be suitable for the expected temperature and shall be able to withstand the dynamic and static forces involved. Due allowance shall be made for the stresses induced in the pipe work by temperature variations (From -20 °C to +50 °C). Adequate environmental protection shall be given to supports and associated steelwork. The distance between pipe supports shall be as the following table: Table 5.2. Maximum pipework support distance Pipe Diameter Max. Distance (m) Pipe Diameter Max. Distance (m) 10mm (3/8”) 1.0 50mm (2”) 3.4 15mm (1/2”) 1.5 65mm (21/2”) 3.5 20mm (3/4”) 1.8 80mm (3”) 3.7 25mm (1”) 2.1 100mm (4”) 4.3 32mm (11/4”) 2.4 125mm (5”) 4.8 40mm (11/2”) 2.7 150mm (6”) 5.2 Reference: EN15004-1 Sec 6.3.4 Table-4 5.2.3. Master / slave cylinder installation 1. Position the cylinder in designated location and secure in place with cylinder strap and attaching hardware (see Figure 5.2 and Table 5.1) Orient cylinder with valve outlet angled toward system piping. 2. Remove the safety cap from the cylinder valve outlet port. 3. Connect a flexible discharge hose or valve outlet adapter to the cylinder outlet port. 4. Install the master / slave cylinder actuator kit. 5. Remove the protection cap from the cylinder valve actuation port. 6. Install pneumatic actuator and actuation line hose; do not attach solenoid actuator to slave cylinder valve actuation port at this time. 7. Install solenoid actuator and actuation line hose to slave cylinder. Figure 5.8.: Assembly of actuation line with master and slave containers Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 54 / 74 5.2.4. Installation of pressure switch Pressure switches must be connected to the discharge manifold or piping in an upright position. Pressure switches have DN15 (1/2") BSP pressure inlets to connect to the system piping. Figure 5.9.: Typical discharge pressure switch assembly on manifold or/and single cylinder 5.2.5. Installation of nozzles Nozzle type, style, and orifice diameter are determined based upon flow calculations made by the IG-541 inert gas flow software during the system design. Discharge nozzles are female BSP thread. Due to the thrust generated from a 180° corner or 360° sidewall nozzle, a rigid hanger or support must be located within 300mm (12") of the nozzle to prevent pipe movement and / or nozzle rotation during discharge. 5.2.6. Discharge piping pressure test All fittings be checked for tightness and pressure tested. Remove the nozzles and install pipe caps. Remove the discharge piping from the cylinder valve and install the safety cape onto the cylinder discharge outlet. Connect a source of dry compressed air or nitrogen to the distribution piping. Slowly increase the pressure in the piping to 3 Bar (43.5 psi) and then close the valve supplying pressure. Check the pressure after 10 minutes. If the pressure is above 2.7 Bar (39.2 psi) (80 % of test pressure) the system is considered sealed. If it drops below 2.7 Bar (39.2 psi) check and tighten all fittings then re-run the test. After completing the test remove pipe caps, reinstall nozzles, and reconnect discharge piping to cylinder. Dry compressed air or nitrogen must be discharged through the piping network and nozzles to verify the flow is continuous and that the piping and nozzles are unobstructed. Make certain air/nitrogen is discharging from all nozzles. Check all nozzles to be sure the correct nozzles are installed as shown on the installation drawing, installed securely to the pipe, properly anchored, and properly oriented. Check all nozzles for any obstructions or objects placed in the direct pattern of discharge. EN15004-1 / Sec 8.2.3 should be taken into account in all other matters not specified. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 55 / 74 Perform a full functional test of the control system in accordance with the appropriate technical manual and system design drawings including verification that all control functions such as damper and door closure, HVAC shut down, and power shut down occur as intended. If the HVAC is not being shutdown prior to system discharge it must be of the re-circulating close loop type and enough agent must be provided to compensate for the volume of the duct and plenum. 5.2.7. Hand-over procedures The entire system shall be thoroughly inspected to make sure that it is complete and that all tests required during installation have been properly carried out. EN15004-1 should also be consulted. Additional procedures may be required by the local Authority Having Jurisdiction (AHJ). In addition, the following items are particularly important. 1. Conduct a room integrity (door fan) test in accordance with EN15004-1. The results of this test will provide equivalent leakage area and, when conducted in accordance with the manufacturer’s instructions, will predict the timeline for a descending interface to fall to a given height and estimate how long the extinguishing concentration will be maintained in the protected room. 2. A container should be refilled or replaced when it shows a loss in agent quantity of more than 5 % or loss in pressure (please refer to the pressure temperature chart) of more than 10 %. 3. Check security and tightness of cylinder mounting brackets to a solid structure and cylinder bracket straps. 4. Piping should be checked for correct size, length, and grade and compared to the installation drawings, IG-541 inert gas flow calculation results, and manual limitations. 5. Check pipe supports for proper type, mounting, and spacing. 6. Check that nozzle location, size, and drill diameters of orifices match both installation / design drawings and calculations. 7. Check the container weight information label according to the system requirement. If there is any doubt or loss of pressure, the container must be weighed. 8. Ensure that the system is in operation and that the operating systems are functioning. Ensure that adequate escape routes are provided with directional signs. Issuance of appropriate documentation will mean that the handover procedure has been completed. Appropriate records will be issued by firefighting teams or area by insurance authorities on the hazard suitability, acceptability and availability of the system. 5.2.8. Warning notification Appropriate warning notices should be affixed inside protected room informing its occupants about the type of protection and modes of actuation in case of fire. All these signs should be clearly legible and resistant to environmental conditions. It is advisable to provide adhesive labels in red or green background and white letters. Notices should incorporate at least the following messages: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 56 / 74 Typical sign inside the protected enclosure: CAUTION AREA PROTECTED WITH FIRE EXTINGUISHING SYSTEM. WHEN ALARM SOUNDS EVACUATE THE AREA Typical sign outside the protected enclosure: CAUTION AREA PROTECTED WITH FIRE EXTINGUISHING SYSTEM. WHEN ALARM SOUNDS DO NOT ENTER UNTIL AREA VENTILATED Typical sign affixed near the protected areas: CAUTION THIS AREA IS PROTECTED BY FIRE EXTINGUISHING SYSTEM. UPON DISCHARGE, AN UNBREATHABLE ATMOSPHERE MAY BE PRODUCED IN THIS AREA. WHEN ALARM SOUNDS OR UPON GAS DISCHARGE Typical signs placed at every manual actuation device: CAUTION THE RELEASE OF THIS MECHANISM WILL PRODUCE A DISCHARGE OF THE FIRE EXTINGUISHING SYSTEM. ENSURE HAZARD AREA IS EVACUATED BEFORE RELEASING Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 57 / 74 6. System Operation 6.1. General Comments Personnel required to work in the protected area should be conversant with the detection and extinguishing equipment installed and trained in fire procedures. All life-saving equipment must be properly maintained. The method of system operation is chosen at the design stage to suit the protection required for the hazard area and the environmental factors appropriate to that area. This part of the document provides information relevant to all the standard operational systems to cover the eventuality of changes to, or expansion of the original design. 6.2. System Actuation Each system is designed to suit the hazard area, whether the area is normally manned or unmanned, and whether the detection / actuation devices are to be manual or automatic. The permutation of systems is large but from an operational point of view, the systems are best grouped as: • Manual • Fully Automatic • Automatic with Manual Intervention 6.2.1. Manual system Manual systems depend on human detection of a fire in the hazard area and prompt action to actuate the local or remote strike knob for the IG-541 system to discharge and flood the protected area and extinguish the fire. Where there fire alarm system is provided for the hazard. In case of fire, detection system will generate audio-video alarm and it will indicate person present in the hazard to evacuate from the hazard area. On the total evacuation, the system can be triggered with the help of manual actuator, mounted on the master cylinder of clean agent system unit. Since system is design for manual actuation. A nominated people has to be there, who should be fully aware of how to trigger of system manually. On periodic time fire drill to be perform with the staff, who are working in this hazard area or and around. All other instructions associated with manual operation form part of the user’s procedures on safety precautions and fire drill. 6.2.2. Fully automatic system Where a sensitive fire detection system is included for the automatic release of extinguishing agent, the system shall only be capable of automatic release when two or more sensors detect the fire. The number of detectors and their spacing is designed to ensure a satisfactory response time. To ensure personnel may safely evacuate the risk area an adjustable time delay should be fitted such that sufficient time may elapse prior to system discharge. Electrical automatic control and delay devices shall be approved in accordance with EN 12094-1. Prior to system discharge (and at the Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 58 / 74 commencement of any time delay period) a clearly audible alarm different from any other used shall sound and continue until the complete system is reset. In areas of high ambient noise level, a visual indication may also be required, in addition to the audible warning. 6.2.3. Fully automatic system with manual intervention Manual intervention of an automatic system may be included for the following condition; Where personnel are required to work within the protected area. In protected areas where personnel are present and the concentration is greater than NOAEL, it is recommended that the automatic feature of the system is isolated during occupation. This may be achieved either by an electrically contacted lock assembly or by a clearly marked key switch at a suitable location outside the risk area. 6.3. Actions Following a Fire These notes are only applicable to the hazard area(s) protected by a IG-541 inert gas fire extinguishing system. Where such a system may form part of or combine with other forms of fire protection systems then composite instructions for all systems are necessary to ensure the safety of personnel and property following a fire. 6.3.1. Actions immediately following a fire These actions should, at a minimum, include the following: 1. Advise the emergency services, Fire or Police if appropriate. 2. Organize a ‘roll-call’ of employees and any visitors. 3. Prevent unauthorized personnel from entering the hazard area. 4. In the case of deep-seated fires, the hazard space should be kept tightly closed for at least 60 minutes after discharge of the IG-541 inert gas extinguishing agent. It is essential that the fire be completely extinguished before ventilating the space. Before permitting anyone to enter the space, ventilate thoroughly or ensure self-contained breathing equipment is used. 5. Do not enter the hazard area in which fire has been extinguished with an open flame or lighted cigarettes the possible presence of flammable vapors may cause re-ignition or explosion. Should it be necessary to enter a space containing IG-541 inert gas or decomposition products the following precautions should be taken; 1. Use a fresh air mask or self-contained breathing equipment. 2. Do not use a filter mask or canister type mask. 3. Do not enter space unless you are under observation from outside the space or tethered by a lifeline. 4. Ensure that all pressurized equipment is isolated or safe from release. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 59 / 74 6.4. Solenoid Functional Test When a functional test is carried out by a system inspector typically disconnects the electrical actuator from master cylinder valve or pilot cylinder valve to do a functional test. After that the actuator is reset and reconnected the same onto the valve. The solenoid reset tool is used for the resetting process. Please follow the steps in the following Figure 6.1. The reset tool, which is the lever-operated type, is one of them. Remove / unscrew the solenoid actuator. A special resetting tool must be used to re-insert the plunger. Screw the resetting tool to the plunger solenoid valve port whit a wrench of 41 mm. Operate the lever by pulling. Released electrical release device HSN-ACT-S01, see red marking at the push rod. Position A: Reset tool assembly. Position B: The reset tool HSN-RST-01 is mounted hand-tight to the electrical release device HSN-ACT-S01. Then pull the lever by 90° to tense the release device. Figure 6.1.: Reset tool for electric actuator. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 60 / 74 7. Maintenance 7.1. Introduction This chapter contains maintenance instructions for IG-541 inert gas fire suppression system. 7.2. Maintenance Procedure IMPORTANT NOTICE: IG-541 inert gas agent fire suppression system cylinder must be handled, installed and inspected by qualified personnel in accordance with the manual. 7.2.1. General 1. A well planned and approved schedule is essential for the inspection and testing of the system, keeping in view the following. 2. At least once a year, all systems shall be thoroughly inspected and tested for proper operation by competent personnel. Discharge tests are not necessary. 3. The inspection report along with recommendations shall be filed and always available with the owner and the same shall be produced to the authorities concerned when demanded. 4. At least once in six months, the agent quantity and pressure of the containers shall be checked and details logged in a register. 5. For IG-541 inert gas agent container shows a loss in agent quantity of more than 5 percent or a loss in pressure (adjusted for room temperature) of more than 10 percent, it shall be refilled or replaced. 6. Date of inspection, gross weight of cylinder plus agent or net weight of agent, type of agent, person performing the inspection, and, where applicable, the pressure at a recorded temperature shall be recorded on a tag attached to the container. 7.3. Agent Storage Cylinders Agent storage cylinders, approved by Transportable Pressurized Equipment Directive (TPED), are pressurized cylinders containing IG-541 inert gas agent with nitrogen and argon at 200 Bar gauge at 15°C (2900 psi at 60°F) or 300 Bar gauge at 15°C (4350 psi at 60°F). This pressure causes considerable thrust if the discharge valve is actuated, thus, the safety cap supplied with the cylinder must be installed when handling or storing the cylinder, or whenever it is not securely fastened down. The safety cap prevents objects from striking the burst disc valve and reduces and redirects the thrust if the cylinder is accidentally discharged. Handle the cylinder carefully to prevent damaging the gauge and other attached fixtures. The cylinder must not be subjected to temperatures above 55 °C (130 °F), or the pressure relief device may operate, releasing the agent. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 61 / 74 7.3.1. Container test 1. Clean agent containers shall not be recharged without retesting if more than 5 years have elapsed since the date of the last test and inspection. 2. Transporting charged containers that have not been tested within 5 years shall not be allowed 3. Cylinders continuously in service without discharging shall be given a complete external visual inspection every 5 years or more frequently if required. The visual inspection shall be in accordance with the guidelines of TPED, that the cylinders need not be emptied or stamped while under pressure. Inspections shall be made only by competent personnel and the results recorded on both of the following: a) A record tag permanently attached to each cylinder, b) A suitable inspection report. 4. A completed copy of the inspection report shall be furnished to the owner of the system or an authorized representative. These records shall be retained by the owner for the life of the system. 7.4. Hose Test 7.4.1. General All system hose shall be examined annually for damage. If visual examination shows any deficiency, hose shall be immediately replaced or tested as specified below. 7.4.2. Testing a) All hoses shall be tested every 5 years. b) All hoses shall be tested at 1½ times the maximum container pressure at 50 ⁰C. The testing procedure shall be as follows: 1. The hose is removed from any attachment. 2. The hose assembly is then placed in a protective enclosure designed to permit visual observation of the test. 3. The hose must be completely filled with water before testing. 4. Pressure then is applied at a rate-of-pressure rise to reach the test pressure within a minimum of 1 min. The test pressure is maintained for 1 full min. Observations are then made to note any distortion or leakage. 5. If the test pressure has not dropped or if the couplings have not moved, the pressure is released. The hose assembly is then considered to have passed the hydrostatic test if no permanent distortion has taken place. 6. Hose assembly passing the test must be completely dried internally. If heat is used for drying, the temperature must not exceed the manufacturer’s specifications. 7. Hose assemblies failing a hydrostatic test must be marked and destroyed and be replaced with new assemblies. 8. Each hose assembly passing the hydrostatic test is marked to show the date of test. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 62 / 74 7.5. Enclosure Inspection At least every 12 months, the enclosure protected by these agents shall be thoroughly inspected to determine if penetrations or other changes have occurred that could adversely affect agent leakage or change volume of hazard or both. Where the inspection indicates conditions that could result in inability to maintain the clean agent concentration, they shall be corrected. If uncertainty still exists, the enclosures shall be retested for integrity. 7.6. Training All persons who could be expected to inspect, test, maintain, or operate fire extinguishing systems shall be thoroughly trained and kept thoroughly trained in the functions they are expected to perform. Personnel working in an enclosure protected by these agents shall receive training regarding agent safety issues. 7.7. Maintenance Procedures Table 7.1. Maintenance Procedures by Time Schedule Schedule Requirement Section Daily Check cylinder pressure Paragraph 6.7.1 Monthly Inspect hazard area system components Paragraph 6.7.2 Check cylinder pressure 200 Bar gauge at 15°C (2900 psi at 60°F) or 300 Bar gauge at 15°C (4350 psi at 60°F) Semi-Annually Test pressure switches Paragraph 6.3 Paragraph 6.7.3 Check Agent qty. and cylinder pressure Actuation functional test Every 2 Years Blow out distribution piping with nitrogen Paragraph 6.7.4 Every 5 Years Agent cylinder pressure test or inspection Paragraph 6.3 Flexible hose pressure test Paragraph 6.4 7.7.1. Daily 7.7.1.1. Check agent cylinder pressure Check the cylinder pressure gauges for proper operating pressure (refer to Table 2.2.). If the pressure gauge indicates a pressure loss (adjusted for temperature) of more than 10 %, it shall be refilled. Remove and recharge the cylinder. For other requirement related to periodic maintenance of IG-541 inert gas unit please refer manual clause 6.2.1. 7.7.2. Monthly 7.7.2.1. General inspection Make a general inspection survey of all cylinders and equipment for damaged or missing parts. If the equipment requires replacement. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 63 / 74 7.7.2.2. Hazard access Ensure access to hazard areas, manual pull stations, discharge nozzles, and cylinders are unobstructed and that nothing obstructs the operation of the equipment or distribution of IG-541 inert gas. 7.7.2.3. Inspect hoses Inspect flexible actuation hoses for loose fittings, damaged threads, cracks, distortion, cuts and dirt. Tighten loose fittings and replace hoses with stripped threads or other damage. If necessary, clean parts. Inspect the adapters, couplings and tees at the cylinder pilot outlets and tighten couplings if necessary. Replace any damaged parts. 7.7.2.4. Inspect pneumatic actuators Inspect the pressure actuators for physical damage, deterioration, corrosion, distortion, cracks, dirt and loose couplings. Tighten loose couplings. Replace damaged caps. Replace the control head if damaged. If necessary. 7.7.2.5. Inspect solenoid actuators Inspect the solenoid actuators for damage, corrosion, and dirt. Check the solenoid actuators flexible electrical line for wear and damage. Check the solenoid actuator for loose coupling and tighten if necessary. Check that the indicator is in the SET position, the pull pin is installed in the manual lever, and the seal wire is intact. Replace the solenoid actuator if damaged. 7.7.2.6. Inspect cylinder and valve assembly Inspect the Cylinder and Valve assembly for leakage and physical damage such as cracks, dents, distortion and worn parts. Check the burst disc and pressure gauges for damage. Replace damaged gauges or burst disc. 7.7.2.7. Inspect straps and mounting hardware Inspect the cylinder brackets, straps, cradles and mounting hardware for loose, damaged or broken parts. Check the cylinder brackets, straps and associated parts for corrosion, oil, grease and grime. Tighten any loose hardware. Replace damaged parts. If necessary. 7.7.2.8. Inspect discharge hoses Inspect the flexible discharge hoses for loose fittings, damaged threads, cracks, rust, kinks, distortion, dirt and frayed wire braid. Tighten loose fittings and replace hoses with stripped threads. If necessary. 7.7.2.9. Inspect discharge nozzles Inspect discharge nozzles for dirt and physical damage. Replace damaged nozzles. If nozzles are dirty or clogged. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 64 / 74 7.7.3. Inspection procedures, semi-annual 7.7.3.1. Discharge pressure switch test 1. Contact the appropriate personnel and obtain authorization for a shutdown. 2. Ensure that the hazard area operations controlled by the pressure switch are operative. 3. Manually operate the manifold switch by pulling up on the plunger and verify that the hazard area operations controlled by the pressure switch shut down. 4. Return the manifold pressure switch to the SET position. 5. Reactivate all systems that were shut down by the pressure switch (such as power, ventilation systems and compressors) 7.7.3.2. Solenoid actuator test Solenoid actuator must be tested semiannually for proper operation. This test can be performed without discharging the cylinders. Test one hazard area at a time before proceeding to the next, as follows: 1. Remove all solenoid actuators from all cylinders serving the hazard area being tested. Let the solenoid actuators hang freely from the flexible electric conduit connections. Leave all pneumatic actuators and pilot actuation hoses attached to the cylinders. 2. Operate the System electrically. This can be accomplished by actuation of the control panel or by manual operation of an electric pull station. 3. If manual actuator have not operated. Replace all damaged actuator. 4. Observe the instructions on the caution label attached to manual actuator. Replace any damaged heads which fail to reset properly before reconnecting to cylinders. Reattach all actuator to the threaded port on the cylinder valve or pressure operated control head. Tighten the swivel nut securely. Make certain each actuator is in SET position before reconnecting to cylinders. Failure to follow this procedure will result in accidental system discharge. 7.7.3.3. Check cylinder weight Cylinder weight shall be checked and compared to the gross weight marked on the cylinder. If the scale indicates a loss in agent quantity of more than 5 %, it shall be refilled. Remove and recharge the cylinder. For other requirement related to periodic maintenance of Clean Agent Unit please refer manual clause 6.2.1. 7.7.4. Inspection procedures - 2 year 1. Remove any nozzles from the piping to allow foreign matter to blow clear. 2. Remove all pneumatic actuators from the cylinders. 3. Blow out all distribution piping with air or nitrogen to ensure it is not obstructed. 4. Reconnect all control heads. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 65 / 74 7.7.5. Inspection procedures - 5 year 7.7.5.1. Clean Agent Cylinders IG-541 inert gas agent system is using TPED specification for their cylinders. Clean agent cylinders continuously in service for more than five years without discharge shall be removed from rack and given a complete external inspection incompliance with Authority Having Jurisdiction. Where external inspection indicates that the container has been damaged, the same shall be sent for hydraulic testing. However, hydraulic test shall be carried after discharge of cylinder. 7.7.5.2. Flexible hose All system hoses shall be visually inspected annually for damage. If visual examination shows any deficiency, hose shall be replaced or tested. As per the EN15004-1 hydrostatic test to be conducted at interval of every 5 years. 7.7.5.3. Record All inspection and test record to be maintain by end user. This record should be made available to Auditor during safety audit. 7.8. Check List Table 7.2. Check List for Maintenance Features of the installation Installation Date Type of the system Authorized Installer Country of Installation Maintenance Maintenance date Last maintenance date Authorized company Authorized person Maintenance type System working pressure Semi-annual Annual Every 2 years Every 5 years Visual inspection Functionality Revision of wear Cylinder and valve and tear parts testing or/and Control pressure refilling of the cylinders ….. bar Cylinders storage pressures verified Cylinder capacity Cylinders and labels are fine Safety valve in good state Electrical connections checked Revision of nozzles and Operation test of the solenoid internal discs satisfactory actuator satisfactory Extinguishing panel functional test is ok ….. L General visual inspection OK Blow out test with nitrogen to cleaning of the dirty and dusty ambient (each 2 years) General maintenance (each 5 years) Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 66 / 74 8. Typical System Layout 8.1. General The section is intended to illustrate typical system drawings. Single Cylinder Arrangement: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 67 / 74 Multiple Cylinders Arrangement Without Pilot Cylinder: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 68 / 74 Multiple Cylinders Arrangement with Pilot Cylinder: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 69 / 74 Multiple Cylinders Arrangement with Pilot Cylinder & Selector Valves: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 70 / 74 Appendix A / Material Safety Data sheet for IG-541 SAFETY DATA SHEET According to 91/155/EEC SECTION 1: Identification of the substance/mixture and of the company/undertaking 1.1 Product identifier Trade name: IG-541 1.2 Details of the supplier of the safety data sheet Supplier Honeywell Middle East FZE Telephone: +971 4 450 5800 Jebel Ali Free Zone, Office No. LB15413 Fax: +971 4 450 5900 18530, Jebel Ali, Dubai, UAE SECTION 2: Composition/information on ingredients 2.1 Substances Chemical formula: 52 Vol. % Nitrogen (N2) 40 Vol. % Argon (Ar) 8 Vol. % Carbon dioxide (CO2) Substances with exposure limits: Description Carbon dioxide % MAK-Value TRK-Value BAT-Value > 5 Vol. % 5000 ppm -- -- SECTION 3: Hazard identification For Human: See section 11 and 15. For Environment: None SECTION 4: First aid measures Inhalation: In high concentrations may cause asphyxiation. Symptoms may include loss of mobility/consciousness. Victim may not be aware of asphyxiation. Remove victim to uncontaminated area wearing self contained breathing apparatus. Keep victim warm and rested. Call a doctor. Apply artificial respiration if breathing stopped. Eye contact: Adverse effects not expected from this product. Skin contact: Adverse effects not expected from this product. Ingestion: N/A Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 71 / 74 SECTION 5: Firefighting measures N/A SECTION 6: Accidental release measures 6.1 Personal precautions, protective equipment and emergency procedures: Provide sufficient ventilation. Do not inhale gases/vapours/mist. If necessary, leave the room. 6.2 Environmental Precautions: N/A 6.3 Methods and material for containment and cleaning up: Provide adequate ventilation. SECTION 7: Handling and storage 7.1 Precautions for safe handling: Make sure container valve and connections are tight; Use in well ventilated areas. Only trained persons may handle compressed gas containers. 7.2 Conditions for safe storage: To be stored only in original containers. Protect containers from heating over 50°C. SECTION 8: Exposure controls/personal protection Inhalation: If oxygen level is below 10 Vol. %, or in case of long exposure, breathing apparatus (independent of circulating air) is necessary. Eye/face protection: N/A Skin protection Hand Protection: Guideline: EN 388 Protective gloves against mechanical risks. Additional Information: Wear working gloves while handling containers Body protection: Protective shoes. Other: Wear safety shoes while handling containers Guideline: ISO 20345 Personal protective equipment - Safety footwear. when using the product. Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 72 / 74 SECTION 9: Physical and chemical properties 9.1 Information on basic physical and chemical properties Appearance Physical state: Gas Form: Compressed gas Color: Colorless Odor: Odorless pH: Not applicable. Flash Point: Not applicable to gases and gas mixtures. Evaporation Rate: Not applicable to gases and gas mixtures. Flammability Limit - Upper (%): Not applicable. Flammability Limit - Lower (%): Not applicable. Vapor pressure: No reliable data available. Relative density: 1,4236 kg/m3 at 15°C Solubility(ies) Solubility in Water: 17,1 ml/l at 0°C Explosive properties: Not applicable. Oxidizing properties: Not applicable. 9.2 Other information: Not flammable. SECTION 10: Stability and reactivity 10.1 Conditions to avoid: Exposure of compressed gas containers to increased heat. Increased temperature will result in an increase in pressure which may cause the container burst. 10.2 Materials to avoid: No reaction with any common materials in dry or wet conditions. 10.3 Hazardous Decomposition Products: N/A SECTION 11: Toxicological information Toxicological Information: Asphyxiant in high concentrations. In pure IG-541 atmosphere there exists the danger of suffocation (through oxygen displacement). SECTION 12: Ecological information 12.1 Degradability: N/A Environmental impact rating: N/A Acute aquatic toxicity: Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s N/A P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 73 / 74 SECTION 13: Disposal considerations 13.1 Product: N/A SECTION 14: Transport information 14.1 Country transport: ADR/RID/GGVS/GGVE-Class 3, Number 2a, gas mixture. 14.2 Inland navigation: ADNR-Class 2, Number 12. 14.3 Maritime shipping: IMDG/GGVSea-Class 2, UN-No.: 1956, Page 2124. 14.4 Aviation: ICAO/IATA-Class 2.2. UN-No.: 1956, Page 220; compressed gases. 14.5 Transport in bulk according to Annex II of MARPOL and the IBC Code: Not applicable SECTION 15: Regulatory information 15.1 EEC- Labelling Symbols: N/A R-phrases: N/A S-phrases: N/A Other information: Identification of the compressed gas containers in conformity with the shipping instructions and ISO 7225. UUV-Gase (VBG 61) SECTION 16: Other information Other information: For application in fire extinguishing systems, the IG-541 quantity is mainly designed to create oxygen concentrations between 10% and 15% and CO2 concentrations between 2% and 5% and no hazards are known for the healthy human during short exposure in this atmosphere. However the combustion products from the fire itself could be highly toxic, therefore people shall always leave the room when it is flooded with IG-541. Note: The SDS document in this section is a sample reference only. Technically, SDS information is country and language specific. To find the SDS, enter the part number of a product containing agent. ------ End of Safety Data Sheet -------- Honeywell Nexus IG-541 Inert Gas Fire Extinguishing System Owner’s P/N: HSN-MNL-IG541-R3 15 Apr 2024 Page 74 / 74
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )