HVAC QUESTION AND ANSWER:1. 2. 3. 4. 5. 6. 7. 8. SAES-K-001-Design and Installation of Heating, Ventilating and Air Conditioning Systems. SAES-K-002 Air Conditioning Systems for Essential Operating Facilities SAES-K-003 Air Conditioning Systems for Communication Buildings SAES-K-100 Saudi Aramco Mechanical (HVAC) Code SAES-K-101 Regulated Vendor List for HVAC Equipment SAEP-379-Quality Issues Notification SAEP-380-Equipment Deficiency Report Any conflicts between this standard and other applicable Saudi Aramco Engineering Standards (SAESs), Saudi Aramco Materials System Specifications (SAMSSs), Industry Standards, Codes, Forms, and Saudi Aramco Standard Drawings (SASDs) shall be resolved in writing by the Company or Buyer Representative through the Manager, Consulting Services Department, Dhahran. 9. 27-SAMSS-011 Fire Dampers; Smoke Dampers & Combination Fire-Smoke Damper 10. 27-SAIP-01 HVAC Inspection Requirements Saudi Aramco Engineering Report 11. AMCA 99 Standards Handbook 12. AMCA 210 Laboratory Methods of Testing Fans for Rating 13. ANSI B31.5(American National Standards Institute) Refrigeration Piping 14. GI-0002.710 Mechanical Completion & Performance Acceptance of Facilities 15. American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc. 16. NADCA(National Air Duct Cleaners Association) General Specifications for the Cleaning of Commercial Heating, Ventilating and Air Conditioning Systems 17. NEBB(National Environmental Balancing Bureau) Testing, Adjusting and Balancing of Environmental Systems 18. NFPA 70(National Fire Protection Association ) National Electrical Code 19. NFPA 90A Installation of Air Conditioning and Ventilating Systems 20. SMACNA 2002(Sheet Metal and Air Conditioning Contractors' National Association, Inc. ) HVAC Systems-Testing, Adjusting and Balancing, 3rd edition 21. SMACNA 2005 HVAC Duct Construction Standards-Metal and Flexible, 3rd edition 22. SMACNA 2002 Fire, Smoke and Radiation Damper Installation Guide for HVAC Systems, 5th edition 23. International Mechanical Code, 2012(IMC) 24. Uniform Mechanical Code, 1997(UMC) 25. UL 181A(Underwriters Laboratories) Closure Systems for Use with Rigid Air Ducts 26. UL 181BUnderwriters Laboratories) Closure Systems for Use with Flexible Air Ducts and Air Connectors Definitions:1. AHRI: Air-Conditioning, Heating and Refrigeration Institute. 2. Air, Standard: Dry air at a pressure of 101.35 kPa (29.92 in Hg.) at 20°C (68°F) temperature. 3. Air-Conditioning, Comfort: The process of treating air to control its temperature, humidity, cleanliness, and distribution to meet the comfort requirements of the occupants of the conditioned space 4. Air-Conditioning Unit, Packaged: An air-conditioning unit having the means of air cooling, air heating, air circulation, air cleaning, and the controls thereof, in the same cabinet with the condensing unit. 5. Air Conditioning, Split: Air Conditioning system consisting of equipment provided in more than one enclosure, usually with supply air distribution equipment housed separately from the refrigeration equipment. 6. Main Duct - is the duct that serves the system’s major or entire flow 7. Sub-Main Duct - is the duct that serves two or more branch-mains. 8. Branch-Main Duct - is the duct that serves two or more branch ducts. 9. Branch Duct - is the duct supplying a single terminal 10. Air-Handling Unit: Device usually connected to ductwork, to move air, which also may clean and temper the air. 11. Air Terminal Device: is a generalized term used mainly for grilles, diffusers, weather louvers, displacement units and Chilled Beams that are commonly used to supply, extract or transfer air in a building. An Air Terminal Device, or ATD, is mounted in any of the surfaces of a room with the function of directing supply or exhaust air in such a way that comfortable and clean conditions are maintained in the occupied zone of the treated space. 12. British Thermal Unit (BTU): A BTU is a unit of heat energy. It is defined as 252.9957 calories (777.65 ft – lb) and it is the heat required to raise the temperature of one pound of water from 59°F to 60°F. 13. Building Management System (BMS): BMS is a description for products, software, and engineering services for remote and centralized automatic controls, monitoring and optimization, human intervention, and management to achieve energy efficient, economical, and safe operation of building services equipment 14. Chilled Water: Water used as a cooling medium at below ambient temperature. 15. Coil: A cooling or heating element made of pipe or tubing. 16. Constant Volume System: Operates on the principal of supplying a constant volume of air to a single zone of conditioned space. Capacity control of this type of system is achieved by varying the amount of heat removal from (or addition to) the air stream. 17. Cooling Tower: A cooling tower is a heat rejection device, which extracts waste heat to the atmosphere though the cooling of a water stream to a lower temperature. 18. Cycle, Refrigerating: A sequence of thermodynamic processes through which a refrigerant passes, in a closed or open system to absorb heat at a relatively low temperature level and reject heat at a relatively higher temperature level. 19. Damper: A device used to vary the volume of air passing through a confined cross section by varying the cross sectional area. 20. Dehumidification: Removal of water vapor from air by chemical or physical methods. 21. Diffuser: An outlet discharging supply air in various directions and planes. 22. Grill: A covering for any opening through which air passes. 23. Register: A grille equipped with a damper or control valve. 24. Duct: A passageway made of sheet metal or other suitable material, not necessarily leak tight, used for conveying air or other gas at low pressures 25. Evaporation: Change of state from liquid to vapor. 26. Fan Coil Unit: Fan and a heat exchanger for cooling and/or heating, assembled within a common casing. 27. Fins Per Inch (FPI): The number of fins in a coil per 25.4 mm (1 inch). 28. Humidity: Water vapor within a given space. 29. HVAC System: The equipment, distribution systems, and terminals that provide, either collectively or individually, the processes of heating, ventilating or air conditioning to a building or portion of a building. 30. Louver: Device comprising multiple blades which, when mounted in an opening, permits the flow of air but inhibits entrance of other elements in a reverse direction. 31. Plenums: A compartment or chamber to which one or more air ducts are connected and that forms part of the air distribution system. 32. Air-Handling Unit Room Plenum - An individual room containing an air-handling unit(s) used to gather air from various sources and combine the air within the room for returning to the air-handling unit. 33. Raised Floor Plenum - The space between the top of the finished floor and the underside of a raised floor where used to supply air to the occupied area, or to return or exhaust air from the occupied area. 34. Pressure Gauge: Pressure above atmospheric. 35. Psychrometry: The branch of physics relating to the measurement or determination of atmospheric conditions, particularly regarding the moisture mixed with the air. 36. Refrigerant: The fluid used for heat transfer in a refrigerating system, which absorbs heat at a low temperature and a low pressure of the fluid and rejects heat at a higher temperature and a higher pressure of the fluid, usually involving changes of state of the fluid. 37. Sound Attenuation: The reduction in sound power. 38. Suction Line: A tube or pipe that carries refrigerant vapor from the outlet of the evaporator to the compressor inlet. 39. Temperature, Dry Bulb: The temperature of a gas or mixture of gases indicated by an accurate thermometer after correction for radiation. 40. Temperature, Wet Bulb: Thermodynamic wet bulb temperature is the temperature at which liquid or sold water, by evaporating into air, can bring the air to saturation adiabatically at the same temperature. 41. Ton of Refrigeration (TR): The refrigerating effect equal to 3516 watts (12,000 Btu/hr). 42. VAV (Variable Air Volume): Operates on the principal of constant supply air temperature at varying supply airflow rate 43. BACNET: A Data Communication Protocol for Building Automation and Control Networks 44. Data Center: A building or portion of a building whose primary function is to house a computer room and its support areas 45. Hybrid Cooled Communication Shelter: Hybrid Cooled Communication Shelter is a Communications Shelter where grid power is not available and the cooling is provided by both passive cooling method and DC powered air conditioning units where the type of power supporting the air conditioning is DC type generated by solar system 46. Passively Cooled Communication Shelter: Passively Cooled Communication Shelter is a Communications Shelter where grid power is not available and the cooling is provided without the need for power source by natural heat transfer through an internal heat exchanger, accumulator and external heat exchanger. This system utilizes the difference in temperature between day and night times to cool the shelter. 47. Telecommunications Equipment Rooms: An environmentally controlled centralized space for telecommunications equipment that usually houses a main or intermediate cross-connection for telecommunications distribution cables 48. Telecommunications Room: Telecommunication Room (TR) is considered to be floor-serving facilities that provide a connection point between backbone and horizontal distribution pathways. 49. SAP: Systems, Applications & Products in data processing. 50. HEPA: High Efficiency Particulate Air 51. 9COM: “Commodity Classification Code”. 52. ACD: Agreed Completion Date 53. NCR Originator: Individual who creates the NCR in SAP QM module. 54. LBE: Logbook Entries (First level of reporting quality deficiency using Manual Logbook or the Quality Management Information System, QMIS). 55. NCR: Non Conformance Report (Issued by Saudi Aramco through SAP QM). An NCR can be issued directly without going through the LBE stage 56. Worksheet (WS): Mechanism for reporting MAJOR violations or escalating pending NCRs as stipulated in this Procedure. It is also a mechanism for escalating NCRs unapproved by PMT in the SAP system within working days of issuance per SAEP-381. 57. Corrective action: An action taken to eliminate the causes of an existing nonconformity. 58. Equipment Deficiency Report (EDR): SAP notification (type Q4) listing equipment deficiencies with sufficient detail reflecting procurement document, specifications, the equipment manufacturer and investigation result. 59. Responsible Inspection Office Inspector(RIO) 60. HVAC units re-circulating or recycling indoor air within a room (such as through the wall window units, fan coil units or mini-split direct expansion units) shall not be used within the following facilities unless prior written approval has been obtained from the HVAC Standards Committee: 4.3.1.10.1 Communication rooms, e.g., TER; TR or Computer Rooms Exception: Precision HVAC equipment. 61. All Building Management Systems (BMSs) shall be BAC net compatible as per SAES-K011. 62. For selection of air cooled units but not limited to the following: 63. Package Air Cooled Units 64. Air Cooled Condensers 65. Air Cooled Chillers 66. HVAC systems shall be capable of maintaining dry bulb temperature and relative humidity (if applicable) within the performance range given in Table 1 unless stricter indoor design conditions are required. 67. In remote locations, the use of water chillers is restricted to locations where adequate water supply for system make-up is available. 68. HVAC units shall automatically shut down when fire alarm system is activated, in accordance with SAES-M-100, NFPA 90A and NFPA 101. 69. For all electric resistance heaters airflow switches shall be provided. 70. All outdoor air supply and exhaust systems, vents, and ventilators shall be equipped with motorized dampers interlocked with the AHU that will automatically shut down when the system or spaces served are not in use. 71. Fans with motors greater than ¾ HP (0.5 kW) shall have automatic controls capable of shutting off fans when not required. 72. Adequate access space shall be provided for the removal of any coil or other equipment component, as per equipment manufacturer's recommendation. 73. The refrigerant lines of split condenser/compressor or compressor/evaporator units, separated by more than 3 m (9.84 feet), shall be sized in accordance with ASHRAE Fundamentals Handbook, Refrigerant Line Sizing section or as per HVAC equipment manufacturer recommendation. 74. Potable water make-up connection for all chilled water piping systems shall be equipped with an isolation / shut-off valve. 75. An analog type flow meter shall be installed in the make-up water line of the chilled water system to monitor water loss. Flow meter resolution readings range shall be in liters or gallons only. 76. The make-up water connection shall also include a reduced pressure type backflow preventer, manufactured and certified to AWWA C511 standard. 77. Chilled water piping shall be disinfected / chlorinated in accordance with Saudi Aramco Sanitary Code (GI-0151.006) before being put into service. 78. Dissimilar metal piping connections, shall comply with the following: 79. Be exposed and accessible, this shall include valved connections. 80. Provided with insulating unions or insulating flange sets. 81. All piping components for chilled and cooling water piping system components such as valves, flanges, etc., shall have a minimum pressure rating of 1035 kPa gauge (150 psig). 82. 2-way control valves are to be used in water coils with variable flow. 83. 3-way control valves are to be used in water coils with constant flow. 84. Globe Valve 85. By-Pass Valves 86. Flush Valves 87. Control Valves 88. Balancing Valves 89. Pressure gauges shall be installed on direct expansion air cooled condensing units at the following locations: 90. On the suction side of positive displacement compressors, complying with manufacturer's recommendations. 91. On the discharge side of positive displacement compressors, complying with manufacturer's recommendations. 92. On the oil side capable of measuring oil pump discharge pressure, complying with manufacturer's recommendations 93. Flexible pipe connectors shall not be used to correct misaligned piping installation. 94. Toilet rooms’ exhausts require the following: a) A mechanically operated exhaust system capable of providing a minimum of four (4) air changes per hour. b) Exhaust shall be directly to the outside with a point of discharge of at least 1.5 m away from any openable window or door, and a minimum of 1m above and 3 m away from any fresh air intake. 95. Re-circulation of air from rooms such as Telecommunication Equipment Rooms (TER), battery / UPS rooms, toilet rooms, janitor closets, locker rooms, etc., that houses equipment or materials that emit harmful; flammable or toxic fumes or gases are not allowed. 96. Noise shall comply with SAES-A-105, “Noise Control” 97. Automatic fire dampers shall not be used in laboratory hood exhaust systems. 98. Fire detection and alarm systems shall not be interlocked to automatically shut down laboratory hood exhaust fans. 99. All HVAC equipment shall be identified by mark/tag numbers and shall be listed with such identification on the HVAC Equipment Schedule of drawings. 100. An identification tag or name plate made of Brass, 316 stainless steel or better, and shall be attached to each equipment unit, securely with stainless steel or Monel fasteners. 101. The compressor capacity of packaged, air cooled, reciprocating water chillers shall not exceed 50 tons. 102. Each condensing unit shall be complete with all operational equipment, including solenoid valve, sight glass with cover, and cartridge type filter on liquid lines. It shall be mounted on a base frame 103. Number of rows per coil shall not exceed 10 rows. 104. Fin spacing of condenser coils shall not be closer than 12 fins per inch. 105. Copper fins on copper tubes shall be used for all condenser coils within ½ km of sea. Evaporator coils shall also have copper fins on copper tubes when introducing 20% or more outside air within ½ km of sea or within an industrial area. 106. Chilled water piping shall be insulated with closed cell material having an R value not less than 20°F-ft²-hr/Btu. 107. Valves and fittings shall be insulated with a foam-in place insulating material. 108. Pipe penetrations through wall / floors or roof slabs shall maintain the same thickness of the insulation material used. 109. Chilled Water Piping System – Dark Blue Color with white label and directional flow arrow, and shall be spaced not more than 3 meters apart. 110. Condenser / Cooling Water Piping System – Dark Green Color with white label and directional flow arrow and shall be spaced not more than 3 meters apart. 111. Underground piping, shall be provided with: a) Identification markings, e.g., directional flow arrows and label b) Identification markings shall be spaced not more than1 meters apart c) Identification markings shall be sized as per the table above. 112. AHU’s shall be tested, certified and in compliant with AHRI 430. 113. Exception: Not applicable for air handlers having less than 5000 cfm and DX Units. 114. AHUs shall consist of filters, cooling / dehumidifying coil, fan and the following, as required: a) Mixing box b) Humidifier c) Electric heater d) Face and bypass dampers 115. Electric Heater; controls and other electrical devices used to control the air handlers shall be UL Listed. 116. AHUs casings shall be manufactured, pre-painted backed enamel finish, 18 gauge minimum galvanized steel with structural steel frame and bracing. Casing panels shall be insulated with: a) Closed cell insulating material meeting NFPA 90A for flame and smoke spread rating shall be used for single wall panels. b) For double wall panels fibrous material may be used 117. Outside air/return air mixing plenum shall include opposed blade dampers for both the return and outside air streams. Automatic proportioning dampers shall be provided between the outside air and return air. Mixing plenum shall include baffles or other provisions to insure complete mixing of outside and return air streams at all flow rates. 118. Casings shall include doors to provide maintenance and removal access for all fans, motors, coils, filters, and humidifiers. Access doors or frames shall have resilient gasketing material to prevent air leakage. Access doors shall have corrosionresistant hinges and positive latches. 119. Casing filter mounts or filters shall have seals to prevent air bypass. 120. Drain pans shall extend completely under the coil sections and shall have minimum 1-¼ inch threaded drain connections. Drains pans shall be sealed, double wall steel construction with rigid glass fiber insulation and Type 316 stainless steel inner pan. Slope drain pans toward drain connection. Drain pans shall drain completely. 121. Fans shall be air-foil, backward-inclined, backward curved, or forward-curved and shall conform to AMCA 99 and AMCA 210 requirements. In variable air volume (VAV) systems a variable speed fan shall be provided. Propeller fans may be used for exhaust services. 122. Fans installed in parallel within a common system shall have back draft dampers, which open when the fan motor is energized. All exhaust fans shall have back draft dampers which shall close when fan is off. 123. Compressor motors, 10 tons and larger, shall have a separate overload relay protection, as described in Article 440 of the National Electric Code (NEC). This protection shall be in addition to other built-in compressor motor protection devices. 124. Condenser fan motors, 25 tons and larger units, shall have a separate overload relay protection, as described in Article 440 of the National Electric Code (NEC). This protection shall be in addition to other built-in compressor motor protection devices. 125. Each fan powered by a motor of 5 HP or larger shall have a variable-speed drive that automatically change the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat rejection device. 126. Heating equipment / EDH shall be UL listed and selected for the type of service required. 127. Pre-insulated double wall flexible ducts may be used at the connection of air diffusing devices, in accordance with the requirements of NFPA 90A. Flexible ducts shall not exceed 1. Foot (0.3 meter) in overall length and shall not have more than 1 bend no greater than 45°. 128. Turning vanes, as per SMACNA HVAC Duct Construction Standards, shall be provided in all rectangular elbows of low velocity systems. 129. Diffusers, registers, grilles and other similar air terminal devices shall not be installed directly on to main, sub-main and branch-main ducts. Branch ducts shall be provided to these air terminal devices, having a minimum length of two duct sizes. Exception: For commercial, public and unmanned industrial areas such as PIBs, storage, etc., where noise level is not critical this requirement is not applicable. 130. All materials in return air plenums shall be noncombustible or limited combustible and shall meet the requirements of 2.3.10 of NFPA 90A. 131. Ducts shall be insulated in accordance with the International Mechanical Code, Saudi Aramco Mechanical (HVAC) Code (SAES-K-100) and the following: All return air ducts, located outdoors or exposed to unconditioned air, shall be insulated. All Supply ducts shall be insulated. All exposed insulated ducts shall be protected in accordance with 4.8.13.5. Return air ducts shall be insulated. Exception: Insulation is not required for return air ducts which are located in a ceiling space, where both sides of the ceiling space are exposed to conditioned air and the ceiling space is not used as a return air plenum. 132. Internal duct lining of fibrous material shall not be used. Only NFPA rated closed cell material shall be permitted with prior approval of the HVAC Standards Committee Chairman. Exception: Fibrous Internal lining complying with UL 181 is permitted for air terminal boxes and air handling units. This liner shall include protective coating to prevent erosion, corrosion, and growth of molds, bacteria and fungus. Lining shall be installed in accordance with the latest requirements of SMACNA – Duct Liner Installation Metal nosing or sleeves shall be installed over exposed duct liner edges that is opposite to the direction of airflow. 133. Refrigerant suction lines shall be insulated from the evaporator to the compressor. 134. Chilled water lines shall be insulated with closed cell type PVC nitrile rubber insulation (such as Armaflex or an approved equivalent). Fiberglass shall not be used for chilled water lines. 135. Insulation installed or exposed outdoors shall be metal cladded or protected by an approved and acceptable method from moisture and sunlight degradation. 136. Identification. External duct insulation and factory- insulated flexible duct shall be legibly printed or identified at intervals not greater than 36 inches (914 mm) with the name of the manufacturer, the thermal resistance R-value at the specified installed thickness and the flame spread and smoke-developed indexes of the composite materials. 137. All fans shall be isolated from their ducts by flexible connections. 138. Provisions shall be made to control equipment induced vibration. The use of vibration isolators between equipment and foundations and/or building structures is required to minimize transmitted vibration. Fan casing and air handling units shall be attached to ducts with flexible connectors. 139. Reciprocating compressors shall be vibration isolated from the unit, and frame shall have vibration isolation (such as a vibration pad) between equipment and equipment base. 140. All piping and ductworks crossing building construction joints shall be provided with a flexible connection to sustain any structural or building settlements due to expansion or contraction and seismic effects. 141. Dirty pre-filter pressure drop shall not be greater than 125 Pa (0.50 in WC) or final filter pressure drop greater than 250 Pa (1.00 in WC). 142. Built-up central HVAC systems shall be provided with pre-filters and final filters. 143. Pre-filters and final-filters shall be upstream of coils and fans. 144. Each supply or return sub-main duct; main-branch duct and branch duct takeoffs shall be equipped with a volume damper. 145. Volume damper for sub-main and main-branch ducts take-offs shall be opposed blade type with blade linkages outside the air stream and with a locking quadrant damper for rectangular ducts. 146. Volume dampers shall be located a minimum of two duct sizes away from fittings. 147. Fire, smoke and combination fire-smoke dampers shall be UL Classified in accordance with all the requirements of UL555 for Fire Dampers; UL555S for Smoke Dampers and UL 555 & 555S for combination fire-smoke dampers. 148. Fire dampers shall be securely mounted in rated fire separation wall, ceiling or floor, such that ducts can break away without lessening fire separation rating. 149. Fire and smoke dampers shall be manufactured and installed in accordance with the latest issue of SMACNA, “Fire, Smoke and Radiation Damper Installation Guide”. 150. Inspection / access doors shall be provided to allow access to all fire dampers and other maintainable accessories and shall be located either adjacent or accessible to the device that will require resetting and maintenance. 151. Fire, Smoke and Combination Fire-Smoke damper shall be installed in an unobstructed and accessible location. This location shall allow free access for periodic functional testing, maintenance and replacement without any interruption or dismantling of other utilities such as cables, ducting, piping, cable-trays, etc. 152. Psychometric charts shall be shown on one of the HVAC drawings for each HVAC system of 10 tons and larger. This psychometric chart shall include, as a minimum, the data required by paragraph 4.3.4 of this standard. 153. HVAC sequence of operation shall be shown on one of the HVAC drawings, for each HVAC system of 10 tons and larger. 154. Air handlers, refrigeration condenser units, pumps, or any equipment mounted outside, shall be mounted on a concrete housekeeping pad, at a minimum of 100 mm (4”) above the floor or a minimum of 150 mm (6”) above unpaved ground. 155. Roof mounting of HVAC equipment is prohibited. Exception: Packaged rooftop units, especially manufactured for rooftop installation, or HVAC equipment located in penthouse may be used for other than residential HVAC systems. Provision of approved permanent stairs or a permanent jib crane sized to handle the heaviest single component shall be provided. 156. Access doors shall be provided to every valve, coil, filter, damper or mechanical device for inspection and/or adjustment and be within reachable distance. Access doors for fire dampers shall be positioned so that dampers can be reset and fusible links replaced, if necessary. 157. Equipment clearance shall be provided with a minimum of 1 m clearance on each side of equipment with openable panel or controls, unless equipment manufacturer requires greater clearances. Adequate space shall be provided for coil removal. 158. All HVAC Equipment shall be properly grounded in accordance with NFPA 70, National Electrical Code. 159. pressure type, anti-siphon valve shall be used on the raw water hose bib and shall be provided within close proximity (not to exceed 10 feet) of HVAC equipment that require periodic washing 160. After installation, all field-erected refrigerant piping, regardless of the quantity of refrigerant charge, shall be pressure-tested in accordance with the requirements of the Uniform Mechanical Code (UMC) and ASHRAE STD 16. The required test pressure shall be maintained for a minimum of 10 minutes. Exemption: Factory charged and sealed refrigerant tubing. 161. After installation, dehydrate system by placing a vacuum of 1.7 kPa (0.5 in. Hg) absolute pressure. Hold vacuum for 24 hours or cycle vacuum and dry nitrogen purge according to manufacturer's recommendations. Charge system with quantity and type of refrigerant as per manufacturers' requirements 162. Air-cooled condenser unit shall be mounted level. Vertical air-cooled condensers shall be provided with wind deflectors. 163. Evaporators of air handling units shall be mounted a minimum of 150 mm (6 inch) off the floor, to allow room for condensate trap. 164. Drain Pan a) A corrosion resistant drain pan shall be provided under each evaporator coil. b) The evaporator drain pan shall have a trapped drain pipe, attached to the bottom or to the side of the drain pan, flush with the bottom plate. c) The drain pan shall slope towards the drain outlet. d) The drain pipe trap shall have a water seal height equal to or larger than the fan's External Static Pressure (ESP) but not less than 50 mm (2”). 165. The drain pipe shall discharge to the nearest floor drain, in accordance with the requirements of ASHRAE Equipment Handbook. Exception: HVAC units installed outside of buildings may discharge condensate onto the ground or roof, but not onto walkways. 166. Record data on waterside and air side of all air handling units, fans, coils, water chillers, condensers, etc. Data shall include all water and airflow, motor, starter heaters, manufacturer, nameplate data. 167. Balance air distribution system within + 10% of air quantities shown on project drawings and record actual readings taken. 168. All TAB activities shall be performed and supervised by the NEBB certified engineer /personnel. 169. The TAB report shall be reviewed and approved by the concerned HVAC maintenance/operation organization. After which, random points may be selected by the concerned organizations for re-measurement to verify the accuracy of the TAB report. 170. Testing and balancing instruments shall be of types described in NEBB or AABC manuals. Instruments shall be calibrated every six months. Calibration shall be in accordance with NEBB and AABC procedures. 171. Alarms shall be provided for all HVAC systems covered by this standard to provide warning of power loss (from the normal supply) and failure of any portion of the HVAC system. 172. All alarm devices shall be independent of the normal power supply of the HVAC system. 173. In buildings which are located in Class I, Zone 2 or Class I, Division 2 areas, the HVAC system shall be designed to prevent the entry of flammable vapors or gases in accordance with the requirements of NFPA 496, Chapter 5, “Pressurized Control Rooms 174. These buildings shall be capable of maintaining an internal building pressure of not less than 0.25 inch water gauge. 175. All motorized isolation dampers, gas detectors, sensors and HVAC Direct Digital Controllers (DDCs) relevant to the operation of the pressurization system shall have an independent emergency power supply in addition to the normal power supply. 176. All electrical devices (e.g., Motorized Isolation Dampers, Exhaust Fans, Fan Motors) shall be UL listed. 177. Failure of the building pressurization system, as measured in 5.5.5 above, shall signal a visible and audible alarm. 178. Gas detectors shall be installed in the outside air intake stream to detect toxic or flammable gases. 179. Battery rooms shall be air conditioned to maintain a temperature of 22.5°C ± 2°C (72.5°F ± 3.6°F). 180. Battery rooms shall be ventilated to the outside of the building at a minimum rate of one air change every three hours. 181. Air shall not be recycled from battery rooms. 182. The bottom of the ventilation air inlet into the battery room shall not be higher than 150 mm above the floor, and the air outlet shall be located in the ceiling or its upper edge flush with the ceiling if it is located in a wall. Air inlets and outlets shall be located to provide effective cross ventilation over the batteries 183. No false ceilings are allowed in battery rooms. 184. Pockets for collection of flammable gas within battery room ceilings shall be avoided. However, if not possible, then means shall be provided to withdraw any collected flammable gas from the highest point within each ceiling pocket. 185. Battery room exhaust fans shall be spark resistant and certified for use in battery room applications. 186. Differential pressure gauges shall be provided across the filter assemblies. 187. When it is confirmed by the Proponent and/or Process Engineering Division that the concentration of corrosive gases in the local plant environment will exceed the G1 classification level, chemical filters shall be provided to limit the concentration of gases inside rooms containing electronic equipment, to G1 classification level. 188. The HVAC systems of Communication Facilities and Data Centers shall be designed for indoor air dry bulb temperature and indoor air relative humidity as per Table 1. 189. HVAC Systems of Communication Facilities and Data Centers shall have fresh air make-up filters (where fresh air make-up is used) and internal air recirculation filters. 190. Humidity control is not required in battery rooms. 191. Recirculation of conditioned air is prohibited within the battery room. 192. HVAC equipment in battery room shall be acid and hydrogen fumes resistant and shall be of explosion proof type. 193. Standby exhaust fan shall be provided in Battery Room to ensure continues ventilation. 194. For Communications Facilities direct expansion (DX) type HVAC systems shall be used. 195. For Communication Facilities and Data Centers, Computer Room Precision Type air conditioning units shall be used. 196. All fresh air intakes shall have the following: 197. Sand trap louver 198. Filter 199. Bird screen 200. Differential pressure gauge 201. Volume damper 202. Communication Facilities and Data Centers that have recirculation precision type air conditioning units with no fresh air make up shall be provided with separate pressurization air conditioning unit to provide the required pressurization. 203. Indoor air temperature and humidity levels shall be recorded on a digital recorder in each Communications Facility or Data Center. 204. The temperature and humidity measurements shall be performed at 1.5 m (±0.3 m) above the floor and 0.1 m (±0.3 m) away from the equipment 205. Automatic change over between the operating and standby units weekly, and/or in the event of operating unit failure. 206. Remote alarms to NOCC (Network Operations Control Center) in case of any HVAC equipment failure and/or any other alarms in the HVAC equipment. 207. Battery room shall be equipped with Hydrogen gas detector. 208. All pipe and fittings intended for condensate drain piping shall be of the Drainage Waste and Vent (DWV) type material. 209. Duct material for Supply, Return and Exhaust ducts and other air terminal devices, i.e., Volume Dampers, Air Diffusers, Grilles, etc., installed within a corrosive environment, such as battery rooms or any rooms emitting corrosive gas or vapor, shall either be coated with an anti-corrosive coating prior to insulation or the ducts shall be made of 316L stainless steel material or better. 210. Table 1 – Inside Design Conditions Offices, schools, theaters Shops, houses, apartments, trailers, dining halls and store Computer rooms, control rooms, communication facilities, process, interface buildings, analyzer houses Unattended equipment rooms (excluding communication rooms) Unattended electrical substations 24 24 22 29 35 Table 2 – Maximum Duct Air Velocities Main Duct Supply (Ft/min) 2,000 Main Duct Return (Ft/min) 1,500 Branch Duct Supply (Ft/min) 1,500 Branch Duct Return (Ft/min) 1,000
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )