16 Sizing & Selection Linear Actuator Sizing, Unbalanced Trim Introduction An important part of selecting the correct control valve is the proper sizing of its actuator. In throttling services, three questions must be answered: 1. Will the actuator handle the throttling differential pressure? 2. Will the actuator provide sufficient thrust to overcome application pressures to open or close the valve, and generate enough seat loading for tight shutoff? Table 16-I: Guardian Metal Bellows Effective Area Model Number Body Size (inches) Bellows Effective psi Rating Bellows Area 1-LP 1 ⁄2 , 3 ⁄4 , 1 160 .886 1-HP 1 3 310 .886 1 1 ⁄2 , 2 160 1.916 1 310 1.916 2-LP 2-HP ⁄2 , ⁄4 , 1 1 ⁄2 , 2 3. Will the spring fail the valve in the proper direction? 3-LP 3 160 2.835 With on/off services, only questions 2 and 3 must be answered. 3-HP 3 310 2.835 4-LP 4 160 3.343 The equations in this section use the following variables: AL = Lower cylinder area, in2 AU = Upper cylinder area, in2 AS = Area of the seat, in2 (see Table 16-IV or equation 16.1) AStem* = Plug stem cross-sectional area, in2 (see Table 16-IV or equation 16.3) AR = Area of the seat retainer bore, in2 (see equation 16.2) P1 = Pressure on upstream side of the valve, psig P2 = Pressure on downstream side of the valve, psig PS = Air supply pressure, psig SE = Spring force with the spring extended to full stroke, lbs (see Table 16-VI) SR = Spring force with the spring fully retracted, lbs (see Table 16-VI) SFC30 = Spring force at 30 percent of stroke in failclosed actuators, lbs (see Table 16-VI or equation 16.4) SFO30 = Spring force at 30 percent of stroke in failopen actuators, lbs (see Table 16-VI or equation 16.5) FP = Packing friction, lbs (see Table 16-V) RSL = Required seat load to achieve desired shutoff, lbs (see equation 16.6) 4-HP 4 310 3.343 Rev. 4/94 * Use effective bellows area for Guardian valves, see Table 16-I. For Guardian II valves, see page 16-15. When an actuator’s stroke length exceeds the longest stroke length shown for that size actuator on Table 16VI, the actuator will not have a spring. For actuators without a spring, SE= SR= 0. The areas of the seat, AS, and the seat retainer bore, AR, are calculated using the following equations. Note that the area of the seat retainer bore is not used when sizing actuators for valves with standard trim or when sizing actuators for Class 150 through 600 MegaStream valves. AS = AR = πdS2 (16.1) 4 π(dS+0.125)2 4 (16.2) Where: dS = The seat orifice diameter, inches (Trim Number) The plug stem cross-sectional area, Astem, is calculated using the following equation: Astem = πdstem2 4 (16.3) 16-1 Where: dstem =The plug stem diameter, inches (see Table 16IV) The spring forces at 30 percent of stroke in fail-closed and fail-open actuators, SFC30 and SFO30, are calculated using the following formulas: SFC30 = SE + RS (0.30) S (16.4) SFO30 = SR - RS (0.30) S (16.5) Where: RS = Spring rate, lb/in (from Table 16-VI) S = Stroke length, inches The required seat load, RSL, is calculated using the following equation: RSL = πdCLS (16.6) Where: LS = Seat load per circumferential inch to achieve desired shutoff, lbs/in (from Table 8-II) dC = The diameter of the seating contact surface, in (from the following table) Trim Type dC= Standard MegaStream Tiger-Tooth Trim Number CavControl ChannelStream Trim Number + 0.125 inch Step 1: Determine Actuator’s Maximum Allowable Throttling Pressure Drop (Not required for on/off service) Refer to Table 16-IV to find the standard actuator for the given body size. Determine the maximum allowable throttling pressure drop (∆Pa) that the selected actuator can handle by using equations (16.7) and (16.8): Air-to-open, flow-over: or air-to-close, flow-over: ACJO ∆Pa = ≈≈≈≈≈ AS (16.7) Air-to-close, flow-under; or air-to-open, flow-under: ACJC ∆Pa = ≈≈≈≈≈ AS 16-2 (16.8) Where: ∆Pa = Maximum allowable throttling pressure drop, psi AC = Area of cylinder actuator, square inches (see Table 16-III; for air-to-open flow, use the lower cylinder area; for air-to-close flow, use upper cylinder area) AS = Area of the seat, square inches JO = Air supply adjustment factor for flow-over (see Table 16-II) JC = Air supply adjustment factor for flow-under (see Table 16-II) Table 16-II: Air Supply Stiffness Factors Supply Pressure JC JO 30 45 60 80 100 150 14.1 28.2 37.6 56.4 75.2 118.0 14.1 20.7 28.2 35.8 42.4 61.2 Compare the maximum allowable throttling pressure drop to the actual pressure drop. If the actual throttling drop is less than ∆Pa, the selected actuator is sufficient. However, if the actual throttling drop is greater than ∆Pa, the next larger actuator size should be chosen and the above calculation should be repeated. The maximum allowable throttling pressure drop may also be selected by referring to the appendix at the end of this section. To use these tables, follow the procedure below: A) Select the correct table based on the trim size used on the valve. B) Find the correct air supply pressure in the left column. C) Looking to the right, find the allowable throttling drop (∆Pa) for the various actuator sizes and air actions (air-to-open or air-to-close). Table 16-III: Actuator Data Cylinder Size Cylinder Bore Dia.(in.) Upper Cylinder Area (sq. in.) Lower Cylinder Area (sq. in.) Stem Dia. (in.) Stem Area (sq. in.) Max. Vol. Over Piston (cu.in.) 25 5.50 23.76 22.97 1.00 0.79 100 50+ 7.75 47.17 46.39 1.00 0.79 331 50 7.75 47.17 45.67 1.38 1.50 331 100+ 11.00 95.03 93.26 1.50 1.77 1031 100 11.00 95.03 91.06 2.25 3.98 1031 200 15.50 188.7 184.7 2.25 3.98 2087 300 19.50 298.6 292.7 2.75 5.94 3733 400* 15.50 371.5 365.5 2.75 5.94 3033 500 25.25 500.7 494.8 2.75 5.94 5519 600* 19.50 590.2 583.1 3.00 7.07 5661 * Tandem, double piston configuration + Used as oversized actuators in place of the next smaller actuator Table 16-IV: Standard Unbalanced Valve/Actuator Data Valve Size (inches) Rating Class Full Area Trim Size Seat Area (sq. in.) Stem Dia. Stem Area (sq. in.) Std. Act. Size* Stroke (inches) 1 /2 150-600 .50 .196 .562 .248 25 .75 3 /4 150-2500 .72 .405 .562 .248 25 .75 1 1 1 150-600 900-1500 2500 .81 .81 .72 .518 .518 .405 .562 .562 .562 .248 .248 .248 25 25 25 .75 .75 .75 11/2 11/2 11/2 150-600 900-1500 2500 1.25 1.25 1.00 1.23 1.23 .785 .875 .875 .875 .601 .601 .601 25 50 50 1.00 1.00 .75 2 2 2 150-600 900-1500 2500 1.62 1.62 1.25 2.07 2.07 1.23 .875 .875 .875 .601 .601 .601 25 50 50 1.50 1.50 1.00 3 3 3 150-600 900-1500 2500 2.62 2.62 2.00 5.41 5.41 3.14 1.125 1.5 1.125 .99 1.77 .99 50 100 100 2.00 2.00 1.50 4 4 4 150-600 900-1500 2500 3.50 3.50 2.62 9.62 9.62 5.41 1.125 1.5 1.5 .99 1.77 1.77 50 100 100 2.50 2.50 2.00 6 6 6 150 300-1500 2500 5.00 5.00 4.00 19.63 19.63 12.57 1.125 2.0 2.0 .99 3.14 3.14 50 100 100 3.00 3.00 3.00 8 8 8 8 150 300-600 900-1500 2500 6.25 6.25 6.25 5.00 30.68 30.68 30.68 19.63 1.5 2.0 2.5 2.5 1.77 3.14 4.91 4.91 100 100 100 100 4.00 4.00 4.00 3.00 10 10 10 10 150 300-600 900-1500 2500 8.75 8.75 8.00 6.25 60.13 60.13 50.27 30.68 2.0 2.5 3.0 3.0 3.14 4.91 7.07 7.07 100 100 100 100 4.00 4.00 4.00 4.00 12 12 12 150 300-600 900-2500 9.50 9.50 8.00 70.88 70.88 50.27 2.0 3.0 3.0 3.14 7.07 7.07 100 100 100 4.00 4.00 4.00 14 14 150 300-600 11.00 11.00 95.03 95.03 3.0 3.0 7.07 7.07 100 100 4.00 4.00 * Minimum standard actuator size. Oversized actuators may be required for large pressure drops. 16-3 TABLE 16-V: Typical Stem Packing Friction Forces Note: All numbers in pounds-force Plug Stem Diameter* (inches) Teflon Single V Teflon Twin V Glass and Carbon-filled Teflon 0.56 0.88 1.13 1.50 2.00 2.50 3.00 44 49 54 64 82 105 133 49 54 50 60 75 90 105 45 63 78 103 141 184 232 Standard Twin Grafoil Grafoil 356 560 712 954 1272 1590 1908 642 842 1001 1239 1557 1875 2193 Braided PTFE Braided AFPI SafeGuard SureGuard Single V SafeGuard SureGuard Twin V 44 49 54 64 82 105 133 271 344 399 486 600 714 829 52 70 85 111 149 192 239 68 89 106 135 177 225 279 TABLE 16-VI: Cylinder Actuator Spring Data Air-to-open (Air-to-retract) Cylinder 25 50 100 thru 600 16-4 Stroke (inches) Spring Design Rate (lb/in) SE: Spring Extended (lbs) 3 ⁄4 1 1 1⁄2 STD STD STD 180 180 180 281 236 146 3 ⁄4 1 1 1⁄2 1 1⁄2 2 2 1⁄2 3 1 1⁄2 2 2 1⁄2 3 DUAL DUAL DUAL STD STD STD STD DUAL DUAL DUAL DUAL 447 447 447 164 164 164 164 447 447 447 447 2 2 1⁄2 3 4 2 2 1⁄2 3 4 2 21⁄2 3 4 STD STD STD STD HEAVY HEAVY HEAVY HEAVY DUAL DUAL DUAL DUAL 300 300 300 300 535 535 535 535 885 885 885 885 SFC30 (lbs) Air-to-close (Air-to-extend) SR: Spring Retracted (lbs) SR: Spring Retracted (lbs) SFO30 (lbs) SE: Spring Extended (lbs) 322 290 227 416 416 416 450 450 450 410 396 369 315 270 180 629 629 405 369 287 205 123 1194 970 747 523 728 762 606 443 385 328 271 1395 1238 1082 925 964 1075 1075 615 615 615 615 1864 1864 1864 1864 656 656 656 656 582 558 533 508 410 328 246 164 1125 975 825 525 2098 1831 1563 1028 3471 3029 2586 1701 1305 1200 1095 885 2419 2232 2045 1670 4002 3693 3383 2763 1725 1725 1725 1725 3168 3168 3168 3168 5241 5241 5241 5241 1725 1725 1725 1725 1545 1500 1455 1365 1125 975 825 525 Step 2: Determine Actuator Size For Actuation Thrust Calculate the actuator cylinder areas required by using the applicable group of equations in the following tables. Compare the calculated areas to the corresponding areas for the actuator size selected in Step 1. Actuator areas are listed in Table 16-III. If the calculated areas are less than or equal to the corresponding areas for the selected actuator, the actuator size is adequate. If the calculated areas are larger, an actuator with cylinder areas larger than the calculated areas must be selected. When determining the required actuator size, various service conditions should be considered. For each sizing equation, the conditions to be considered for that equation are listed with the equation. Each equation should be evaluated for each listed condition that will actually occur. The condition numbers refer to the following list. Service Conditions to be considered: 1. P1 and P2 for flow conditions. If more than one flow condition will occur, each should be evaluated. 2. P1 and P2 at shutoff. If more than one set of pressures will occur during shutoff, each set of pressures should be evaluated. The possibility of P2 dropping to atmospheric pressure (0 psig) should be considered. Pressures used to bench test the valve should also be considered. 3. P1 and P2 equal to the maximum value of P1. This condition may occur if the pipeline is pressurized and the pipe downstream from the valve is blocked. For this condition, set RSL= 0 in the sizing equations. 4. P1 and P2 equal to 0. This condition will occur if the pipeline is depressurized. This condition will also occur during bench testing of the valve. For this condition, set RSL= 0 in the sizing equations. NOTES: 1. On valves larger than 24-inch, the weight of the plug may need to be accounted for; contact factory. 2. A negative number calculated for AL or AU indicates that the smallest available actuator will work for the condition being evaluated. 3. For valves with a trim number smaller than the plug stem diameter, AS-AStem will be a negative number. In this case, the negative sign must be retained during the sizing calculations. Table 16-VII: Actuator Sizing - Standard Globe valves with Unbalanced Trim Valve Orientation Fail Action Actuator to . . . Service Condition stroke valve from full open to 30 percent open Equation AU > 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff Fail-closed (air-to-open) AU > P1Astem - SFC30 + FP PS P2 AS - P1(AS - Astem) - SE + FP + RSL PS 1 ( with RSL = 0 ), 2, 3, 4 lift plug off seat and stroke valve from closed to 30 percent open AL > P1 (AS - Astem) - P2AS + SFC30 + FP PS 1, 2, 3, 4 stroke valve from 30 percent open to full open 1, 3, 4 Flow-over stroke valve from full open to 30 percent open - P1Astem + SR + FP AL > z PS AU > 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff Fail-open (air-to-close) AU > 1 ( with RSL = 0 ), 2, 3, 4 lift plug off seat AL > 2, 3, 4 stroke valve from closed to 30 percent open 1, 3, 4 AL > P1 Astem + SF030 + FP PS (16.9) (16.10) (16.11) (16.12) (16.13) P2 AS - P1 (AS - Astem) + SR + FP + RSL (16.14) PS P1(AS - Astem) - P2 AS - SR + FP PS P1(AS - Astem) - P2 AS - SF030 + FP PS (16.15) (16.16) 16-5 Table 16-VIII: Actuator Sizing - Standard Globe Valves with Unbalanced Trim (and Class 150 to 600 MegaStream) Valve Orientation Fail Action Actuator to . . . Service Condition stroke valve closed and provide tight shutoff Equation AU > P1AS - P2(AS - Astem) - SE + FP + RSL PS 1 ( with R SL = 0 ), 2, 3, 4 lift plug off seat and stroke valve from closed to 30 percent open Flow-under Fail-closed (air-to-open) AL > PS 1, 2, 3, 4 stroke valve full open AL > 1, 3, 4 Fail-open (air-to-close) P2 (AS - Astem) - P1AS+ SFC30 + FP stroke valve closed and provide tight shutoff 1 ( with R SL = 0 ), 2, 3, 4 AU > - P2Astem + SR + FP (16.17) (16.18) (16.19) PS P1AS - P2(AS - Astem) + SR + FP + RSL PS (16.20) Table 16-IX: Actuator Sizing - ChannelStream and CavControl Valves with Unbalanced Trim Valve Orientation Fail Action Actuator to . . . Service Condition stroke valve closed and provide tight shutoff Fail-closed (air-to-open) Flow-over Equation AU > PS 1 ( with R SL = 0 ), 2, 3, 4 lift plug off seat and stroke valve full open AL > 1, 2, 3, 4 stroke valve closed and provide tight shutoff Fail-open (air-to-close) P2AR - P1(AR - Astem) - SE + FP + RSL 1 ( with R SL = 0 ), 2, 3, 4 lift plug off seat and stroke valve full open 1, 2, 3, 4 AU > AL > P1 (AR - Astem) - P2AR+ SR + FP PS P2AR - P1(AR - Astem) + SR + FP + RSL PS P1 (AR - Astem) - P2AR- SE + FP PS (16.21) (16.22) (16.23) (16.24) Table 16-X: Actuator Sizing - Tiger-Tooth and High Pressure MegaStream Valves with Unbalanced Trim Valve Orientation Fail Action Actuator to . . . Service Condition Equation stroke valve closed AU > 1, 3, 4 provide tight shutoff Fail-closed (air-to-open) AU > 2, 3, 4 lift plug off seat AL > Flow-under 2, 3, 4 stroke valve full open AL > 1, 3, 4 stroke valve closed Fail-open (air-to-close) 1, 3, 4 provide tight shutoff 2, 3, 4 16-6 AU > AU > P1AR - P2 (AR - Astem) - SE + FP PS P1AS - P2(AS - Astem) - SE + FP + RSL PS P2 (AS - Astem) - P1AS + SE + FP PS P2 (AR - Astem) - P1AR + SR + FP PS P1AR - P2 (AR - Astem) + SR + FP PS (16.25) (16.26) (16.27) (16.28) (16.29) P1AS - P2 (AS - Astem) + SR + FP + RSL (16.30) PS Step 3: Determine Spring Size If it will be necessary for the valve to stroke open or closed upon loss of air supply pressure, the fail-safe spring must be sized. The required spring force is calculated by using the applicable equations in the following tables. Each sizing equation should be evaluated for the listed conditions that will actually occur. The condition numbers refer to the service conditions listed in step 2. After the required spring force is calculated, it must be compared to the standard spring force for the actuator selected in steps 1 and 2. This spring force is listed in Table 16-VI. If the required spring force is less than the standard spring force of the selected actuator, a stan- dard spring will be sufficient. If the required spring force is greater than that of a standard spring force, compare the required spring with the dual (or heavyduty) spring force for the same size actuator (see Table 16-VI). If the dual spring force is larger than the required spring force, the dual spring should be used. If the dual spring force is not large enough, a volume tank or larger actuator will be required. Section 19 contains volume tank sizing information. If the spring or actuator size selected to provide sufficient spring force is different from that used during step 2, the calculations of step 2 must be verified using the new spring or actuator information. Table 16-XI: Spring Sizing - Standard Globe valves with Unbalanced Trim (and Class 150 to 600 MegaStream) Valve Orientation Fail Action Spring to . . . Service Condition stroke valve from full open to 30 percent open Fail-closed (air-to-open) Equation SFC30 > P1Astem + FP (16.31) SE > P2 AS - P1 (AS - Astem) + FP + RSL (16.32) SR > P1 (AS - Astem) - P2 AS + FP (16.33) SFO30 > P1(AS - Astem) - P2 AS + FP (16.34) SE > - P1Astem + FP (16.35) SFC30 > P2Astem + FP (16.36) SE > P1AS - P2 (AS - Astem) + FP + RSL (16.37) SFO30 > P2(AS - Astem) - P1AS + FP (16.38) SE > - P2Astem + FP (16.39) 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff 1 ( with RSL = 0 ), 2, 3, 4 lift plug off seat Flow-over 2, 3, 4 Fail-open (air-to-close) stroke valve from closed to 30 percent open 1, 3, 4 stroke valve from 30 percent open to full open 1, 3, 4 stroke valve from full open to 30 percent open Fail-closed (air-to-open) 1, 3, 4 stroke valve closed and provide tight shutoff 1 ( with RSL = 0 ), 2, 3, 4 Flow-under lift plug off seat and stroke valve from closed to 30 percent open Fail-open (air-to-close) 1, 2, 3, 4 stroke valve full open 1, 3, 4 16-7 Table 16-XII: Spring Sizing - ChannelStream and CavControl with Unbalanced Trim Valve Orientation Fail Action Fail-closed (air-to-open) Spring to . . . Service Condition stroke valve closed and provide tight shutoff Equation SE > P2 AR - P1 (AR - Astem) + FP + RSL (16.40) SR > P1 (AR - Astem) - P2 AR + FP (16.41) SE > P1(AR - Astem) - P2 AR + FP (16.42) 1 ( with RSL = 0 ), 2, 3, 4 lift plug off seat Flow-over Fail-open (air-to-close) 2, 3, 4 stroke valve full open 1, 3, 4 Table 16-XIII: Spring Sizing - Tiger-Tooth and High Pressure MegaStream Valves with Unbalanced Trim Valve Orientation Fail Action Spring to . . . Service Condition Equation stroke valve closed Fail-closed (air-to-open) SE > P1AR - P2 (AR - Astem) + FP (16.43) SE > P1AS - P2 (AS - Astem) + FP + RSL (16.44) SR > P2 (AS - Astem) - P1AS + FP (16.45) SE > P2(AR - Astem) - P1AR + FP (16.46) 1, 3, 4 provide tight shutoff 2, 3, 4 Flow-under lift plug off seat Fail-open (air-to-close) 2, 3, 4 stroke valve full open 1, 3, 4 16-8 Linear Actuator Sizing, Pressure-balanced Trim Introduction As noted in the procedure for unbalanced trim, in throttling services three questions must be answered: 1. Will the actuator handle the throttling differential pressure? 2. Will the actuator provide sufficient thrust to overcome application pressures to open or close the valve, and generate enough seat loading for tight shutoff with the given air supply pressure? 3. Will the spring fail the valve in the proper direction? ASl = Sleeve area, in2 (see Table 16-XIV or 16XV) When an actuator’s stroke length exceeds the longest stroke length shown for that size actuator in Table 16-VI, the actuator will not have a spring. For actuators without a spring, SE= SR= 0. The areas of the seat, AS, and the seat retainer bore, AR, are calculated using the following equations. Note that the area of the seat retainer bore is not used when sizing actuators for valves with standard trim or when sizing actuators for Class 150 through 600 MegaStream valves. With on/off services, only questions 2 and 3 must be answered. AS The equations in this section use the following variables: AL = Lower cylinder area, in2 AU = Upper cylinder area, in2 AS = Area of the seat, in2 (see Table 16-XIV or equation 16.47) Astem = Plug stem cross-sectional area, in2 (see Table 16-XIV or equation 16.49) AR = Area of the seat retainer bore, in2 (see equation 16.48) obO = Off-balance area tending to open the valve, in2; obO = ASl - AS (see Table 16-XIV) obC = Off-balance area tending to close the valve, in2; obC= ASl - Astem - AS (see Table 16-XIV) P1 = Pressure on upstream side of the valve, psig P2 = Pressure on downstream side of the valve, psig PS = Air supply pressure, psig SE = Spring force with the spring extended to full stroke, lbs (see Table 16-VI) SR = Spring force with the spring fully retracted, lbs (see Table 16-VI) SFC30 = Spring force at 30% of stroke in fail-closed actuators, lbs (see equation 16.50) SFO30 = Spring force at 30% of stroke in fail-open actuators, lbs (see equation 16.51) FP = Packing friction, lbs (see Table 16-V) FS = Pressure balance seal friction, lbs (see Table 16-XVI) RSL = Required seat load to achieve desired shutoff, lbs (see equation 16.52) AR = = πdS2 4 π(dS + 0.125)2 4 (16.47) (16.48) Where: dS = The seat orifice diameter, in (Trim Number) dS = T N + 0.125 for ChannelStream and CavControl The plug stem cross-sectional area, Astem, is calculated using the following equation: Astem = πdstem2 4 (16.49) Where: dstem = The plug stem diameter, in (see Table 16XIV) The spring forces at 30 percent of stroke in fail-closed and fail-open actuators, SFC30 and SFO30, are calculated using the following equations: SFC30 = SE + RS(0.30) S (16.50) SFO30 = SR - RS(0.30) S (16.51) Where: RS =Spring rate, lb/in (see Table 16-VI) S =Stroke length, inches The required seat load, RSL, is calculated using the following equation: RSL = πdCLS (16.52) Where: LS =Seat load per circumferential inch to achieve 16-9 TABLE 16-XIV: Standard Pressure-balanced Valve/Actuator Data (inches) Valve Rating Full Area Seat Stem Stem Sleeve Size Class Trim Area Dia. Area Area (inches) Size (sq. in.) (sq. in.) (sq. in.) (sq. in.) Off-balance Area sq.in. Standard Flow Under Flow Over To Close To Open Stroke Actuator (inches) Size 2 2 2 600 1500 2500 1.62 1.62 1.25 2.07 2.07 1.23 .562 .562 .562 .248 .248 .248 2.58 2.41 1.55 .26 .09 .07 .51 .34 .32 25 25 25 1 1 1 3 3 3 600 1500 2500 2.62 2.62 2.0 5.41 5.41 3.14 .875 .875 .875 .601 .601 .601 6.77 6.49 3.86 .76 .48 .12 1.36 1.08 .72 50 100 100 1.5 2 1.5 4 4 4 600 1500 2500 3.5 3.5 2.62 9.62 9.62 5.41 .875 1.125 1.125 .601 .994 .994 11.41 11.41 6.77 1.19 .80 .37 1.79 1.79 1.36 50 100 100 2 2 2 6 6 6 6 150 600 1500 2500 5.0 5.0 5.0 4.0 19.63 19.63 19.63 12.57 1.125 1.5 1.5 1.5 .994 1.77 1.77 1.77 22.69 23.76 22.69 15.03 2.06 2.36 1.29 .69 3.06 4.13 3.06 2.46 50 100 100 100 2.5 2.5 2.5 2.5 8 8 8 600 1500 2500 6.25 6.25 5.0 30.68 30.68 19.63 1.5 2.0 2.0 1.77 3.14 3.14 35.78 35.78 23.76 3.33 1.96 .99 5.10 5.10 4.13 100 100 100 3 4 4 10 10 10 600 1500 2500 8.0 8.0 6.25 50.27 50.27 30.68 2.0 2.5 2.5 3.14 4.91 4.91 58.36 58.36 37.12 4.95 3.18 1.53 8.09 8.09 6.44 100 100 100 3 4 4 12 12 12 600 1500 2500 9.5 9.5 8.0 70.88 70.88 50.27 2.5 2.5 2.5 4.91 4.91 4.91 78.54 78.54 56.75 2.75 2.75 1.57 7.66 7.66 6.48 100 100 100 4 4 4 14 14 14 150 600 1500 11.0 11.0 11.0 95.03 95.03 95.03 2.5 3.0 3.0 4.91 7.07 7.07 108.43 108.43 103.87 8.49 6.33 1.77 13.40 13.40 8.84 100 100 100 4 4 4 16 16 600 1500 12.75 12.75 127.68 127.68 3.0 3.0 7.07 7.07 140.50 137.89 5.75 3.14 12.82 10.21 100 100 4 4 Trim Type dC= Standard MegaStream Tiger-Tooth Trim Number CavControl ChannelStream Trim Number + 0.125 inch desired shutoff, lbs/in (see Table 8-II) dC =The diameter of the seating contact surface, in (see the following table) Step 1: Determine Actuator’s Maximum Allowable Throttling Pressure Drop Refer to Table 16-XIV to find the standard actuator for the given body size. Determine the maximum allowable throttling pressure drop (∆Pa) that the selected actuator can handle by using equations (16.53) and (16.54): Air-to-open, flow-over or air-to-close, flow-over: ∆Pa = ACJO obO (16.53) Air-to-open, flow-under or air-to-close, flow-under: ∆Pa = ACJC obC (16.54) Where: ∆Pa = Maximum allowable throttling pressure drop, psi AC = Area of cylinder actuator, square inches (see Table 16-III; for air-to-open flow use lower cylinder area; for air-to-close flow use upper cylinder area)) obC = Off-balance area tending to close the valve, in2; obC= ASl - Astem - AS (see Table 16-XIV) obO = Off-balance area (sq.in.) tending to open the valve obo= ASl - AS (see Table 16-XIV) JO = Air supply adjustment factor for flow-over 16-10 (see Table 16-II) JC = Air supply adjustment factor for flow-under (see Table 16-II) Compare the maximum allowable throttling pressure drop to the actual pressure drop. If the ∆Pactual is less than ∆Pa, the selected actuator is sufficient. However, if the ∆Pactual is greater than ∆Pa, the next larger actuator size should be chosen and the above calculation should be repeated. Step 2: Determine Actuator Size For Actuation Thrust Calculate the actuator cylinder areas required by using the applicable equations in the following tables. Compare the calculated areas to the corresponding areas for the actuator size selected for the throttling drop. These areas are listed in Table 16-III. If the calculated areas are less than or equal to the corresponding areas for the selected actuator, the actuator size is adequate. If the calculated areas are larger, an actuator with lower and upper cylinder areas larger than the calculated areas must be selected. When determining the required actuator size, various service conditions should be considered. For each sizing equation, the conditions to be considered for that equation are listed with the equation. Each equation should be evaluated for each listed condition that will actually occur. The condition numbers refer to the following list. Service Conditions to be considered: 1. P1 and P2 for flow conditions. If more than one flow condition will occur, each should be evaluated. 2. P1 and P2 at shutoff. If more than one set of pressures will occur during shutoff, each set of pressures should be evaluated. The possibility of P2 dropping to atmospheric pressure (0 psig) should be considered. 3. P1 and P2 equal to the maximum value of P1. This condition may occur if the pipeline is pressurized and the pipe downstream from the valve is blocked. 4. P1 and P2 equal to 0. This condition will occur if the pipeline is depressurized. This condition will also occur during bench testing of the valve. NOTES: 1. On valves larger than 24-inch, the weight of the plug may need to be accounted for; contact factory. 2. A negative number calculated for AL or AU indicates that the smallest available actuator will work for the condition being evaluated. Table 16-XV: Pressure-balanced Sleeve Area ChannelStream and CavControl ASI = AR = AS Valves other than ChannelStream and CavControl not listed in Table 16-XIV Pressure Class ASI 150 - 600 (1.10) AS + Astem 900 - 1500 (1.05) AS + Astem 2500 (1.03) AS + Astem Table 16-XVI: Seal Friction Forces Type of Seal Seal Friction, FS, (lbs) Teflon FS = 58(TN) + 12 O-Ring and Spring Energized Elastomer FS = 14(TN) + 0.029(P1 - P2) Muskegon Piston Rings FS = 0.00613(TN)(P1 - P2) NiResist Piston Rings FS = 0.0613(TN)(P1 - P2)HS Where: TN = Trim Number HS = Seal height = 0.13 for TN = 1.00 to TN = 2.25 = 0.19 for TN = 2.62 to TN = 5.00 = 0.25 for TN = 5.50 to TN = 9.50 = 0.38 for TN = 11.00 to TN = 22.00 16-11 Table 16-XVII: Actuator Sizing - Standard Globe Valves with Pressure-balanced Trim Valve Orientation Fail Action Actuator to . . . Service Condition stroke valve from full open to 30 percent open Equation AU > P1Astem - S FC30 + FP + FS PS 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff Fail-closed (air-to-open) 1 (with RSL = 0), 2, 3, 4 lift plug off seat and stroke valve from closed to 30 percent open 1, 2, 3, 4 stroke valve from 30 percent open to full open 1, 3, 4 Flow-over stroke valve from full open to 30 percent open 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff Fail-open (air-to-close) 1 (with RSL = 0), 2, 3, 4 lift plug off seat and open valve from closed to 30 percent open 1, 2, 3, 4 stroke valve from 30 percent open to full open 1, 3, 4 AU > AL > AL > AU > AU > AL > AL > (16.55) P1(obO) - P2(obC) - SE + FP + F S + R SL (16.56) PS P2(obC) - P 1(obO) + SFC30 + FP + FS PS - P1Astem + SR + FP + F S PS P1 Astem + SFO30 + FP + FS PS (16.57) (16.58) (16.59) P1(obO) - P 2(obC) + SR + FP + FS + RSL (16.60) PS P2(obC) - P1(obO) - SFO30 + FP + FS PS - P1Astem - SE + FP + F S PS (16.61) (16.62) Table 16-XVIII: Actuator Sizing - Standard Globe Valves (and Class 150 to 600 MegaStream) Valve Orientation Fail Action Actuator to . . . Service Condition stroke valve from full open to 30 percent open Equation AU > P2Astem - S FC30 + FP + FS PS 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff Fail-closed (air-to-open) 1 (with RSL = 0), 2, 3, 4 lift plug off seat and stroke valve from closed to 30 percent open 1, 2, 3, 4 stroke valve from 30 percent open to full open 1, 3, 4 Flow-under stroke valve from full open to 30 percent open 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff Fail-open (air-to-close) 1 (with RSL = 0), 2, 3, 4 lift plug off seat and open valve from closed to 30 percent open 1, 2, 3, 4 stroke valve from 30 percent open to full open 1, 3, 4 16-12 AU > AL > AL > AU > AU > AL > AL > (16.63) P2(obO) - P1(obC) - SE + FP + F S + R SL (16.64) PS P1(obC) - P 2(obO) + SFC30 + FP + FS PS - P2Astem + SR + FP + F S PS P2Astem + SFO30 + FP + FS PS (16.65) (16.66) (16.67) P2(obO) - P 1(obC) + SR + FP + FS + RSL (16.68) PS P1(obC) - P2(obO) - SFO30 + FP + FS PS - P2Astem - SE + FP + F S PS (16.69) (16.70) Table 16-XIX: Actuator Sizing - ChannelStream and CavControl Valves with Pressure-balanced Trim Valve Orientation Fail Action Actuator to . . . Service Condition Equation stroke valve closed and provide tight shutoff Fail-closed (air-to-open) AU > lift plug off seat and stroke valve full open stroke valve closed and provide tight shutoff Fail-open (air-to-close) PS 1 (with RSL = 0), 2, 3, 4 1, 2, 3, 4 Flow-over P2Astem - S E + FP + FS + RSL AU > 1 (with RSL = 0), 2, 3, 4 lift plug off seat and stroke valve full open 1, 2, 3, 4 AL > AL > - P2Astem + SR + FP + F S PS P2Astem + SR + FP + FS + RSL PS - P2Astem - SE + FP + FS PS (16.71) (16.72) (16.73) (16.74) Table 16-XX: Actuator Sizing - Tiger-Tooth and High Pressure MegaStream Valves with Pressure-balanced Trim Valve Orientation Fail Action Actuator to . . . Service Condition Equation stroke valve closed AU > 1, 3, 4 provide tight shutoff Fail-closed (air-to-open) AU > 2, 3, 4 lift plug off seat 2, 3, 4 AL > stroke valve full open AL > 1, 3, 4 Flow-under stroke valve closed AU > 1, 3, 4 provide tight shutoff Fail-open (air-to-close) 2, 3, 4 AU > lift plug off seat 2, 3, 4 AL > stroke valve full open 1, 3, 4 AL > P2(ASl - AR) - P1(ASl - AR - Astem) - SE + FP + FS PS (16.75) P2(ASl - AS) - P1(ASl - AS - Astem) - SE + FP + FS + RSL (16.76) PS P1(ASl - AS - Astem) - P2(ASl - AS) + SE + FP + FS PS P1(ASl - AR - Astem) - P2(ASl - AR) + SR + FP + FS PS P2(ASl - AR) - P1(ASl - AR - Astem) + SR + FP + FS PS (16.77) (16.78) (16.79) P2(ASl - AS) - P1(ASl - AS - Astem) + SR + FP + FS + RSL (16.80) PS P1(ASl - AS - Astem) - P2(ASl - AS) - SR + FP + FS PS P1(ASl - AR - Astem) - P2(ASl - AR) - SE + FP + FS PS (16.81) (16.82) 16-13 Step 3: Determine Spring Size If the valve is required to stroke open or closed upon loss of air supply pressure, the actuator fail-safe spring must be sized. The required spring force is calculated by using the applicable equations in the following tables. For each sizing equation, the conditions to be considered for that equation are listed. Each equation should be evaluated for the listed conditions that will actually occur. The condition numbers refer to the service conditions listed in Step 2. After the required spring force is calculated, it must be compared to the standard spring force for the actuator selected in steps 1 and 2. This spring force is listed in Table 16-VI. If the required spring force is less than the standard spring force for the selected actuator, a standard spring will be sufficient. If the required spring force is greater than that of a standard spring, compare the required spring force with the dual (or heavy-duty) spring force for the same size actuator (see Table 16VI). If the dual spring force is larger than the required spring force, the dual spring should be used. If the dual spring force is not large enough, a volume tank or larger actuator will be required. Section 19 contains volume tank sizing information. If the spring or actuator size selected to provide sufficient spring force is different from that used during step 2, the calculations of step 2 must be verified using the new spring or actuator information. Table 16-XXI: Spring Sizing - Standard Globe valves with Pressure-balanced Trim (and Class 150 to 600 MegaStream) Valve Orientation Fail Action Spring to . . . Service Condition stroke valve from full open to 30 percent open Fail-closed (air-to-open) 1, 3, 4 stroke valve closed from 30 percent open and provide tight shutoff 1 ( with RSL = 0 ), 2, 3, 4 Flow-under lift plug off seat and stroke valve from closed to 30 percent open Fail-open (air-to-close) 1, 2, 3, 4 stroke valve from 30 percent open to full open 1, 3, 4 stroke valve from full open to 30 percent open Fail-closed (air-to-open) 1, 3, 4 stroke valve closed and provide tight shutoff 1 ( with RSL = 0 ), 2, 3, 4 Flow-over lift plug off seat and stroke valve from closed to 30 percent open Fail-open (air-to-close) 1, 2, 3, 4 Equation SFC30 > P2Astem + FP+ FS (16.83) SE > P2(obO) - P1(obC) + F P + FS + R SL (16.84) SFO30 > P1(obC) - P2(obO) + FP + FS (16.85) SE > - P2Astem + FP + F S (16.86) SFC30 > P1Astem + FP + F S (16.87) SE > P1(obO) - P2(obC) + F P + FS + R SL (16.88) SFO30 > P2(obC) - P1(obO) + FP + FS (16.89) SE > - P1Astem + FP + F S (16.90) stroke valve full open 1, 2, 3, 4 Table 16-XXII: Spring Sizing - ChannelStream and CavControl with Pressure-balanced Trim Valve Orientation Fail Action Fail-closed (air-to-open) Flow-over 16-14 Fail-open (air-to-close) Spring to . . . Service Condition stroke valve closed and provide tight shutoff Equation SE > P2 Astem + FP + FS+ RSL (16.91) SE > - P2 Astem + FP + FS (16.92) 1 ( with RSL = 0 ), 2, 3, 4 lift plug off seat and stroke valve full open 1, 2, 3, 4 Table 16-XXIII: Spring Sizing - Tiger-Tooth and High Pressure MegaStream Valves with Pressure-balanced Trim Valve Orientation Fail Action Actuator to . . . Equation Service Condition stroke valve closed Fail-closed (air-to-open) SE > P2(ASl - AR) - P1(ASl - AR - Astem) + FP + FS (16.93) SE > P2(ASl - AS) - P1(ASl - AS - Astem) + FP + FS + RSL (16.94) SR > P1(ASl - AS - Astem) - P2(ASl - AS) + FP + FS (16.95) SE > P1(ASl - AR - Astem) - P2(ASl - AR) + FP + FS (16.96) 1, 3, 4 provide tight shutoff 2, 3, 4 Flow-under lift plug off seat Fail-open (air-to-close) 2, 3, 4 stroke valve full open 1, 3, 4 Linear Actuator Sizing, Guardian II Metal Bellows Seal Introduction The following data must be used when sizing actuators for Guardian II metal bellows valves. This information along with the previous equations listed in Sizing and Selection section 16 will be combined for accurate sizing. See Table XXIV for the initial sizing information needed. While sizing, the actuator pressure limits in Table XXV must not be exceeded. For valve and actuator combinations not listed, the actuator pressure limit is 150 psig. Table 16-XXIV: Guardian II Bellows Valve Actuator Sizing Information Max. Effective Relaxed Bellows Valve ANSI Stroke Bellows Position Spring Size Pressure Length Area (in. from Rate (inches) Class (inches) (sq. in.) seat) (lb/in) 1 ⁄2, 3⁄4, 1 150, 300 11⁄2, 2 150, 300 3 150, 300 4, 6 150 4, 6 300 8 150 8 300 0.5 1.0 1.5 2.5 2.5 3.0 3.0 0.75 1.35 1.35 2.38 2.18 4.53 4.75 0 0 0.25 0 0 0 0 36 26 26 15 42 20 112 To determine actuator spring forces, the stroke length of a valve must be known. Many Guardian II stroke lengths are given in Table XXVI. For the trims not listed in Table Table 16-XXV Guardian II Actuator Pressure Limits Valve Size (inches) ANSI Pressure Class Actuator Size (sq. in.) Max. Actuator Pressure (psig) 6 6 8 8 8 8 300 300 150 150 300 300 200 300 200 300 200 300 100 60 100 60 100 60 XXVI, the stroke length is determined by comparing the maximum stroke length listed in Table XXIV to the stroke length of a standard Mark One valve that is the same size and has the same trim. The actual stroke length of the valve with a Guardian II bellows seal will be the shorter of these two stroke lengths. Fluid pressure inside the valve acts on the effective bellows area. This area is listed in Table XXIV and should be substituted for the actuator stem area in the actuator sizing equations. The relaxed position of the bellows is the distance from the seat where the bellows is not in tension or 16-15 compression. The metal bellows acts as a spring that is compressed or stretched as the plug is moved from the relaxed position. To account for the spring force of the bellows, it is necessary to add a term to the sizing equations of Section 16 of the Sizing & Selection manual. The term is added to the numerator on the right side of the equations for actuator area and is added to the right side of equations for spring force. This additional term is designated SB. For equations used to determine the actuator or spring size required to close the valve, SB is calculated by using Equation 1. SB = RB(PR-PA) Table 16-XXVI: Cv Data (=% Trim, Flow Over) Valve Size (inches) 1 ⁄2 3 ⁄4 (Equation 1) 1 For equations used to determine the actuator or spring size required to open the valve, SB is calculated by using Equation 2. 11⁄2 SB = RB(PA-PR) (Equation 2) Where: SB = Spring force of the metal bellows, lbs. PA = Actual position of the plug, in. (If the equation from Sizing & Selection section 16 determines the force required to move the plug through a range of stroke values, use the position that gives the largest value for SB). 2 3 4 PR = Relaxed position of the plug, in. (See Table XXIV). 6 RB = Spring rate of the metal bellows, lb/in. (See Table XXIV). 8 Trim Number Stroke (inches) Full Cv .50 .31 .72 .50 .31 .81 .50 .31 1.25 1.00 .81 1.62 1.25 1.00 .81 2.62 1.62 3.50 2.25 5.00 3.50 6.25 5.00 .50 .50 .50 .50 .50 .50 .50 .50 1.00 .75 .75 1.00 1.00 .75 .75 1.50 1.50 2.50 2.00 2.50 2.50 3.00 3.00 4.2 2.3 7.5 5.4 2.6 11.0 5.7 2.6 30 22 18 44 33 23 19 107 49 206 113 405 236 698 474 Table 16-XXVII: Examples of Modifications to Actuator Sizing Equations Equation 16.9 16.10 16.11 16.12 Modified Equation AU > AU > AL > AL > P1Abellows - SFC30 + FP + SB SB Equation SB Evaluation Position (PA) 1 30 percent open (0.3 X Stroke Length) 1 On seat (0.0 inches) 2 30 percent open (0.3 X Stroke Length) 2 Full open (Stroke Length) PS P2 AS - P1(AS - Abellows) - SE + FP + RSL + SB PS P1 (AS - Abellows) - P2AS + SFC30 + FP +SB PS - P1Abellows + SR + FP + SB PS 16.31 SFC30 > P1Abellows + FP +SB 1 30 percent open (0.3 X Stroke Length) 16.32 SE > P2 AS - P1 (AS - Abellows) + FP + RSL + SB 1 On seat (0.0 inches) 16-16 Rotary Actuator Sizing, Valdisk and Valdisk 150 Introduction To select an actuator for a Valdisk or Valdisk 150 high performance butterfly valve, five sequential steps are necessary: 1. Determine the shaft orientation and actuator stiffness requirements. 2. Calculate the seating and breakout torque. 3. Calculate the dynamic torque. 4. Select an actuator capable of providing sufficient torque to overcome the seating/breakout torque and dynamic torque based on available air supply. 5. If a fail-open or fail-close action is required, select an actuator capable of providing sufficient torque to overcome the seating/breakout torque and dynamic torque based on available spring torque. Step 1: Determine the Shaft Orientation Because the disc in a Valdisk or Valdisk 150 is double offset, when the shaft is oriented upstream the dynamic torque created by the process fluid will force the disc into the seat. A disc with the shaft oriented downstream will move toward the open position when near the seat. As a general rule, a valve that is required to fail-close on loss of instrument air supply usually has the shaft upstream. A valve which is required to fail open has the shaft downstream. The above rule applies to all applications where the flowing fluid is a gas. On liquid applications with the shaft upstream, the actuator must be adequately stiff to prevent the disc from closing too rapidly, thus eliminating any potential pressure surge condition which would result in water hammer. To determine if the actuator has sufficient stiffness, calculate the following: ∆P (max) Actuator Stiffness (required) = (16.97) Sup. Press. Compare the required actuator stiffness with the maximum actuator stiffness values found in Table 16-XXVIII (according to valve size). Shaft upstream on a failclosed liquid service can be used, provided the required stiffness does not exceed the actuator stiffness (max) for the actuator size selected. Note that in all cases the standard actuator size for a given valve size is indicated first in the chart. A larger actuator size may be required to ensure adequate stiffness. If the required stiffness exceeds all those indicated for the actuator sizes available for a given valve size, shaft downstream orientation is required. Step 2: Find the Seating and Breakout Torque Using table 16-XXX and the following equations, calculate the seating and breakout torque. Table 16-XXVIII: Actuator Stiffness (max.) for Shaft Upstream, Liquid Applications Valve Size (inches) 2 3 4 6 8 10 12 14 16 18 20 24 Actuator Size Standard 25 3.1 3.1 1.7 0.81 Standard 50 8.8 4.3 2.4 1.3 Standard 100 Standard 200 Toggle-link 100 Toggle-link 200 6.9 6.0 3.4 2.4 1.4 0.98 0.84 0.53 0.39 15.9 13.8 7.8 5.5 3.2 2.2 1.9 1.2 0.87 13.2 7.5 5.3 3.1 2.16 1.85 1.17 .86 30.4 17.2 12.1 7.0 4.8 4.2 2.6 1.9 16-17 Table 16-XXIX: Dynamic Torque Factors vs. Disc Position Valve Size (in.) Dynamic Torque Factor vs. Disc Position (Degrees Open) 10o 20o 30o 2 A 0 B 0 A 0 B 0 A 0 3 0 0 0 0 0 4 6 0 0 0 0 0 0 0 1 0 1 40o B 50o A 0 B 0 A 0 0 1 0 1 0 1 0 60o B 70o 0 A 0 B 0 2 0 2 0 3 0 2 1 4 1 4 80o A 0 B 0 0 0 0 0 2 9 1 6 4 17 0 0 6 23 -4 -19 4 19 0 A 90o B A B 8 0 0 0 1 1 2 2 4 3 7 4 12 1 19 -8 28 -23 23 10 12 0 1 1 2 1 2 2 7 2 5 6 13 5 10 9 20 7 16 17 38 8 18 28 61 4 8 46 101 -18 -40 65 144 -55 -121 55 121 14 16 1 2 3 4 3 4 10 12 6 8 18 23 15 19 28 36 22 27 54 67 25 32 85 106 12 15 142 177 -56 -69 201 250 -168 -211 168 211 18 5 10 10 29 19 54 44 83 64 156 73 247 34 411 -161 582 -489 489 20 24 5 7 10 14 10 14 31 42 21 28 58 78 47 64 89 121 68 92 168 227 78 106 264 358 6 50 440 596 -173 -234 623 845 -524 -710 524 710 30 24 49 49 146 97 268 219 414 316 779 365 1230 170 2046 -804 2899 -2436 2436 A = Shaft Downstream B = Shaft Upstream NOTE: When degrees of opening are not known, use highest value of Cd for valve size. Shaft downstream: (Torque required to close valve) Tst = - TP - TS - ∆PMAX(CBT + COT) - TH (16.98) Shaft downstream: (Torque required to open valve) Tbo = TP + TS + ∆PMAX(CBT - COT) + TH (16.99) 70 to 80 degrees open, which could result in some controllability problems. To avoid this, change the shaft orientation to shaft upstream or limit the disc rotation to 70 degrees. For gas applications use Table 16-XXX and the following equations to find the required dynamic torque: Shaft upstream: (Torque required to close valve) Tst = - TP - TS - ∆PMAX(CBT - COT) - TH (16.100) Shaft upstream: (Torque required to open valve) Tbo = TP + TS + ∆PMAX(CBT + COT) + TH (16.101) Where: Tst = Seating torque Tbo = Breakout required TP = Packing torque TS = Seat torque ∆PMAX = Maximum pressure drop at shutoff CBT = Bearing torque factor COT = Off-balance torque factor TH = Handwheel torque. TH = O without handwheel (See Table 16 - XXXII) NOTE: Negative values calculated for Tc, Tbo, Tst, indicate the disc will tend to resist closing. Positive values indicate the disc will tend to resist opening. Step 3: Calculate the Dynamic Torque Since the net torque output of rotary actuators varies as disc position changes, it may be necessary to find the dynamic torque on the shaft at various degrees of opening. This is generally required only when a relatively high actual pressure drop is expected through part or all of the disc rotation. With the shaft oriented downstream a torque reversal occurs at approximately 16-18 To close the disc: TD = - TP - ∆Peff(CBT) (16.102) To open the disc: TD = TP + ∆Peff(CBT) (16.103) For liquid applications use Tables 16-XXIX, 16-XXX and the following equations to find the required dynamic torque: To close the disc TD = -TP - ∆Peff(CBT - Cd) (16.104) To open the disc TD = TP + ∆Peff(CBT - Cd) (16.105) Where: TD = Dynamic torque: (-)values indicate the disc will resist closing. (+) values indicate the disc will resist opening. Cd = Dynamic torque factor from Table 16XXIX for appropriate shaft orientation and degrees of opening. Use highest Cd value if degrees of opening are unknown. ∆Peff = ∆P(actual) at the flowing condition at the operating degrees of opening limited to ∆P (choked) TP = Packing torque factor, from Table 16-XXX Table 16-XXX: Static Breakout Torque = Sizing Valve Size (inches) ANSI Pressure Class 2 3 4 6 8 10 12 14 16 18 20 24 30 150,300,600 150,300* 150* TP = Packing Torque (in-lb) (1) (2) (3) (4) (5) TS = Seat Torque (in-lb) 50 50 57 64 79 79 104 104 122 122 141 141 182 280 477 280 477 333 533 385 590 490 702 490 702 648 870 648 870 753 983 753 983 858 1095 858 1095 1068 1319 350 350 399 448 543 543 691 691 789 789 886 886 1081 63 63 71 81 104 104 151 151 190 190 234 234 342 74 154 270 596 980 1612 2102 4338 5853 6639 9378 11829 19521 (1) TFE or filled TFE V-ring packing (2) Grafoil packing (3) Twin Grafoil Packing (4) Asbestos free packing CBT = Bearing Torque Factor (6) (7) COT = Off Balance Torque Factor 0.09 0.20 0.48 1.27 2.73 4.46 8.60 11.98 16.61 21.99 35.50 44.78 110.83 0.13 0.30 0.72 1.90 4.10 6.69 12.90 17.97 24.92 32.99 53.25 67.17 166.25 0.20 0.40 0.71 1.66 2.58 4.25 5.55 25.65 34.62 39.27 55.42 65.40 38.49 (5) Braided PTFE packing (6) Filament wound glass/TFE bearing (7) 316 stainless steel/solid film lubricant coated bearing and stellite bearings * For higher pressure class data, consult factory Table 16-XXXI: Valve/Actuator Compatibility - Valdisk/Valdisk 150 Actuator Size (sq.in.) Spring Size STD. 25 STD. STD. 25 H.D. STD. 50 STD. Valves Size (inches) 2 STD. 50 H.D. STD. 100 STD. STD. 100 H.D. STD. 200 STD. STD. 200 H.D. 3 4 6 8 10 12 14 16 18 20 24 30 NOTE: For Valdisk valve compatibility with Toggle-link actuators, contact factory. Table 16-XXXII: Declutchable Handwheel Torque (TH) Actuator Size (sq.in.) Handwheel Torque (in-lbs) 25 150 50 250 100 - 200 375 16-19 CBT = Bearing torque factor, from Table 16-XXX ∆P(choked) is shown as: ∆P(choked) = FL2 (P1 - FfPV) (16.106) Step 5: Select Actuator Based on Available Spring Torque Where: FL = Valves recovery coefficient P1 = Upstream pressure, psia Ff = Liquid critical pressure ratio PV = Vapor pressure of the liquid, psia If the spring must move the disc to a desired failure position upon air supply loss, select an actuator from table 16-XXXIII according to the following criteria. (Available actuator sizes are indicated in Table 16XXXI.) Step 4: Determine Actuator Size Based on Air Supply Select an actuator from Table 16-XXXIII with sufficient net torque to overcome the calculated seating/breakout and dynamic torque through the full stroke rotation of the valve based on the available air supply. After the actuator size has been selected, all gas and liquid applications with shaft downstream should be checked for sufficient actuator stiffness. Using the following equation, calculate corrected air supply: SC = 0.867Sa - 12.3 Where: (16.107) SC = Corrected supply pressure Sa = Actual supply pressure Using SC, consult Table 16-XXXIII and confirm that the actuator size selected has sufficient torque to overcome the dynamic torque values (calculated from step 3). Choose a larger actuator size if the torque available throughout the full stroke rotation is less than the dynamic torque calculated. 16-20 Finally, check the valve/actuator interface compatibility in Table 16-XXXI for the actuator chosen. For fail-closed valves, which do not require tight shutoff on air failure, the spring must provide sufficient torque to overcome the calculated dynamic torque through the full stroke rotation of the valve. For valves requiring tight shutoff, the spring must also provide sufficient torque at the 0 degree (closed) position to overcome the required seating torque. For fail-open valves, the spring must deliver sufficient torque at the 90 degrees (closed) position to overcome the calculated breakout torque. It must also have sufficient torque to overcome the dynamic torque throughout the full stroke rotation of the valve. Should the required torque be greater than the available springs can provide, a volume tank can be used to ensure failure on loss of air supply. For liquid applications with the shaft oriented upstream, the selected actuator should have adequate stiffness. It should also provide sufficient torque to overcome the seating/breakout torque and dynamic torque through the fall stroke rotation of the valve with the available air supply and available spring torque, if a failure mode is required. Table 16-XXXIII: Net Torque Output of Standard Actuators at Various Supply Pressures (inNOTE: For air-to-open/fail-closed actuators the 0 degreelb) position shown corresponds to the disc or ball being seated. For air-to-close/fail-open actuators the 90 degree position shown corresponds to the disc or ball being seated. Degrees from Fail Position on Air Supply Loss Actuaor Size Supply Pressure 0 10 20 30 40 50 60 70 80 90 STD 25 with STD Spring 150 140 120 100 80 60 40 Spring Torque 3013 2755 2397 1986 1574 1163 751 54 3399 3165 2695 2228 1759 1290 821 86 3700 3444 2928 2412 1896 1381 864 125 3907 3631 3080 2530 1979 1428 876 169 4000 3714 3145 2573 2002 1430 858 213 3970 3685 3110 2535 1961 1386 811 254 3811 3531 2972 2414 1856 1298 738 284 3514 3253 2731 2211 1688 1167 645 299 3084 2854 2390 1928 1463 1001 537 293 2532 2339 1962 1577 1191 806 420 262 STD 25 with HD Spring 150 140 120 100 80 60 Spring Torque 2647 2441 2030 1618 1206 795 440 2973 2738 2270 1802 1333 865 542 3223 2964 2450 1934 1418 902 647 3386 3110 2558 2009 1457 907 749 3448 3162 2590 2020 1448 877 839 3403 3115 2542 1967 1392 818 908 3246 2966 2409 1850 1292 733 945 2976 2716 2195 1673 1151 630 937 2600 2368 1905 1441 978 515 878 2124 1931 1552 1167 781 396 758 STD 50 with STD Spring 150 140 120 100 80 60 40 Spring Torque 10701 9970 8516 7059 5602 4147 2690 222 11981 11157 9513 7873 6227 4586 2942 343 13015 12114 10318 8515 6716 4913 3111 489 13751 12798 10874 8953 7033 5114 3192 651 14134 13136 11141 9153 7156 5166 3171 816 14089 13083 11075 9073 7062 5058 3049 966 13575 12596 10649 8693 6736 4784 2829 1081 12568 11653 9826 7999 6174 4347 2519 1134 11043 10232 8615 6995 5372 3755 2134 1107 9035 8365 7053 5712 4373 3034 1693 983 STD 50 with HD Spring 150 140 120 100 80 60 Spring Torque 9774 9044 7591 6133 4678 3223 1148 10898 10074 8430 6790 5148 3505 1428 11781 10880 9083 7281 5481 3681 1726 12380 11425 9502 7585 5660 3741 2026 12651 11652 9657 7668 5671 3680 2304 12533 11527 9519 7516 5508 3501 2529 12000 11021 9073 7117 5163 3209 2662 11036 10122 8300 6473 4646 2821 2667 9648 8837 7216 5597 3974 2356 2511 7850 7183 5865 4527 3186 1846 2167 STD 100 with STD Spring 150 140 120 100 80 60 40 Spring Torque 26194 24385 20805 17226 13640 10055 6469 704 29415 27397 23329 19271 15200 11139 7077 1049 32022 29784 25330 20859 16399 11929 7472 1461 33847 31459 26685 21914 17153 12391 7624 1913 34730 32253 27303 22368 17413 12472 7526 2370 34559 32069 27104 22119 17133 12159 7181 2783 33234 30831 25983 21134 16296 11447 6605 3088 30711 28446 23921 19394 14878 10350 5829 3225 26943 26936 20932 16920 12915 8901 4893 3135 22035 20378 17119 13808 10485 7167 3851 2775 STD 100 with HD Spring 150 140 120 100 80 60 Spring Torque 24678 22881 19304 15713 12130 8545 2217 27231 25195 21127 17070 12999 8939 3256 29008 26771 22317 17847 13385 8921 4485 29925 27539 22784 18012 13248 8483 5831 29917 27459 22507 17567 12612 7673 7185 28969 26475 21490 16518 11538 6558 8405 27058 24632 19782 14946 10101 5257 9299 24266 22001 17472 12956 8432 3910 9691 20699 18691 14680 10674 6662 2662 9407 16483 14832 11563 8245 4927 1611 8316 STD 200 with STD Spring 80 70 60 50 40 30 Spring Torque 27695 24156 20595 17051 13501 9951 704 31132 27119 23091 19072 15043 11022 1049 33903 29480 25069 20643 16227 11808 1461 35838 31134 26406 21696 16969 12253 1913 36820 31916 27014 22126 17223 12328 2370 36663 31730 26813 21876 16952 12015 2783 35280 30501 25699 20897 16109 11307 3088 32620 28139 24656 19173 14703 10219 3225 28633 25670 20697 16724 12760 8785 3135 23416 20206 16926 13646 10357 7071 2775 STD 200 with HD Spring 80 70 60 50 40 30 Spring Torque 26192 22636 19094 15538 11991 8441 2217 28930 24918 20889 16872 12842 8821 3256 30894 26467 22056 17629 13212 8792 4485 31940 27214 22505 17779 13064 8345 5831 32005 27122 22217 17326 12421 7530 7185 31052 26136 21198 16275 11346 6414 8405 29104 24302 19499 14709 9914 5116 9299 26177 21693 17208 12735 8257 3778 9691 22393 18420 14445 10478 6507 2536 9407 17887 14650 11370 8083 4799 1514 8316 (continued) 16-21 Table 16-XXXIII: (continued) Net Torque Output of Toggle-link Actuators at Various Supply Press. (in-lb) NOTE: For air-to-open/fail-closed actuators the 0 degree position shown corresponds to the disc or ball being seated. For air-to-close/fail-open actuators the 90 degree position shown corresponds to the disc or ball being seated. Degrees from Fail Position on Air Supply Loss Actuaor Size Supply Pressure 0 10 20 30 40 50 60 70 80 90 STD 100 with No Spring 150 140 120 100 80 70 60 55253 51566 44200 36835 29465 25783 22100 50511 47141 40407 33674 26937 23570 20203 48414 45183 38730 32276 25818 22591 19364 47688 44506 38149 31792 25431 22252 19074 47565 44390 38050 31709 25365 22195 19024 47596 44417 38072 31728 25380 22208 19035 47231 44077 37781 31486 25185 22038 18889 46243 43155 36991 30827 24659 21577 18494 44044 41094 35224 29357 23482 20548 17611 40216 37629 32255 26891 21504 18821 16126 STD 100 with STD 20" Spring 150 140 120 100 80 70 60 Spring Torque 46475 42763 35341 27996 20640 16973 13303 8764 41517 38174 31457 24741 18023 14671 11309 8854 39053 35847 29418 22967 16531 13318 10103 9234 37762 34581 28256 21923 15583 12409 9244 9802 37004 33832 27519 21185 14860 11702 8536 10469 36347 33173 26856 20532 14190 11029 7866 11161 35492 32336 26033 19745 13447 10295 7149 11775 34086 30996 24847 18676 12513 9427 6348 12185 31885 28927 23070 17192 11320 8381 5447 12209 28585 25968 20597 15219 9842 7156 4469 11625 STD 100 with HD 28" Spring 150 140 120 100 80 70 60 Spring Torque 42482 38800 31452 24099 16745 13077 9405 12677 37897 34552 27836 21123 14404 11049 7687 12491 35540 32330 25881 19447 13009 9794 6576 12773 34250 31070 24741 18393 12063 8889 5722 13330 33432 30261 23946 17627 11299 8139 4976 14038 32745 29572 23233 16909 10577 7414 4249 14783 31840 28686 22399 16095 9798 6652 3506 15436 30466 27398 21227 15068 8900 5815 2735 15804 28395 25457 19580 13712 7836 4900 1962 15699 25370 22747 17376 11997 6620 3930 1242 14847 STD 200 with No Spring 120 100 80 70 60 50 40 90138 75117 60092 52580 45067 37558 30046 82403 68671 54935 48067 41199 34335 27467 78982 65820 52655 46072 39489 32910 26327 77799 64834 51865 45381 38897 32416 25932 77597 64666 51731 45263 38796 32332 25864 77646 64705 51761 45291 38819 32352 25880 77052 64210 51365 44944 38521 32104 25682 75440 62867 50291 44004 37716 31433 25144 71847 59870 47891 41906 35915 29934 23944 65573 54840 43857 38384 32887 27419 21928 STD 200 with STD 20" Spring 120 100 80 70 60 50 40 Spring Torque 81372 66376 51346 43764 36215 28722 21221 8764 73545 59778 45950 39076 32250 25402 18554 8854 69667 56415 43301 36736 30176 23601 17039 9234 67776 54835 41931 35455 29000 22546 16083 9802 66960 54063 41139 34705 28245 21806 15359 10469 66341 53409 40508 34045 27602 21140 14689 11161 65317 52467 39606 33203 26775 20364 13944 11775 63265 50725 38139 31846 25573 19282 12999 12185 59683 47718 35730 29737 23761 17770 11784 12209 53947 43167 32194 26720 21229 15758 10272 11625 STD 200 with HD 28" Spring 120 100 80 70 60 50 40 Spring Torque 77455 62436 47376 39792 32321 24823 17326 12677 69905 56083 42304 35474 28628 21783 14934 12491 66066 52894 39777 33196 26640 20081 13517 12773 64242 51326 38398 31945 25488 19016 12555 13330 63370 50491 37592 31133 24692 18249 11798 14038 62710 49816 36886 30444 23979 17532 11077 14783 61663 48813 35982 29554 23141 16714 10294 15436 59644 47105 34519 28247 21953 15675 9380 15804 56196 44228 32240 26266 20271 14290 8299 15699 50755 39946 28972 23481 18007 12525 7043 14847 STD 200 with HD 34" Spring 120 100 80 70 60 50 40 Spring Torque 74734 59697 44588 37026 29543 22050 14567 15446 67370 53551 39793 32944 26095 19252 12404 15021 63658 50490 37353 30791 24212 17655 11099 15198 61889 48931 36033 29558 23099 16641 10175 15718 60983 46106 35208 28770 22310 15866 9416 16422 60326 47431 34501 28059 21609 15148 8698 17180 59298 46441 33610 27182 20769 14353 7929 17808 57364 44783 32197 25926 19632 13353 7065 18127 53986 42018 30030 24055 18059 12078 6087 17921 48740 37928 26953 21462 15977 10505 5019 16866 16-22 Rotary Actuator Sizing, ShearStream Where: Tbo = Seating/breakout torque (in-lb) is the torque required to close and open the valve. Introduction To select an actuator for a ShearStream high performance ball valve, three steps are necessary: 1. Determine seating/breakout torques. (Also determine the dynamic torque in liquid applications.) TP = Packing torque (in-lb) is the torque required to overcome the friction of the packing on the shaft. Packing torque varies with packing material. (See Table 16-XXXVI) 2. Select an actuator capable of providing sufficient torque to overcome the seating/breakout torque and dynamic torque based on available air supply. TS = Seat torque (in-lb) is the torque required to overcome the friction of the seat on the ball. (See Table 16-XXXVI) 3. If a failure action is required, select an actuator capable of providing sufficient torque to overcome the seating/breakout torque and dynamic torque based on available spring torque. Step 1: Determine Seating/Breakout Torques. Normally, ShearStream valves are installed with the shaft downstream. However, in an erosive service the valve should be installed with the shaft upstream. With the shaft upstream, erosive action will occur in the retainer and not the ball surface or the valve body. To determine the seating/breakout torque, use equation (16.108) or (16.109), according to the application. For shaft downstream, seating/breakout torque is shown as: Tbo = TP + TS + ∆Pmax (CB + Cs) + TH (16.108) For shaft upstream, seating/breakout torque is shown as: ∆Pmax = Pressure drop (lb/in2) across the valve when valve is in the closed position. TD = Dynamic torque (in-lb) is the torque required to overcome the torque on the closure member caused by the fluid-dynamic forces on the ball. ∆Peff = Actual pressure drop (lb/in2) across the valve at the flowing condition which occurs when the valve is in an open position. ∆Peff is less than or equal to ∆P(choked). ∆Pchoked = FL2(P1 - FfPV) (16.111) Where: FL = Valve recovery coefficient (See Table 16-XXXIV) P1 = Upstream pressure, psia Ff = Liquid critical pressure ratio Pv = Vapor pressure of liquid, psia CB = Bearing torque factor (in3). As the pressure across the valve increases, the force on the bearings increases proportionally. CB(∆P) = bearing torque (in-lb). (See Table 16-XXXVI) Tbo = TP + TS + ∆Pmax (CB) + A + TH (16.109) NOTE: A = (TS - ∆P(CS). If A is less than zero, enter zero for A. In liquid service applications, the dynamic torque must also be determined. Actuator sizing is based on the seating/breakout torque and dynamic torque. To determine dynamic torque, use the following equation: TD = TP + ∆Peff(CD + CB) (16.110) CS = Seat torque factor (in3). As the pressure across the valve increases, the force at which the seat pushes into the ball increases (shaft downstream) or decreases (shaft upstream). (See Table 16-XXXVI) CD = Dynamic torque factor. (See Table 16XXXVI) TH = Handwheel torque. TH = 0 without handwheel (See Table 16-XXXII) 16-23 Table 16-XXXIV: Approximate FL Percent of Rated CV Approximate FL 10 20 30 40 50 60 70 80 90 100 .90 .85 .82 .78 .73 .68 .65 .63 .62 .60 Table 16 - XXXV: Valve/Actuator Compatibility - ShearStream Actuator Size (in2) Spring Size Valve/Actuator Compatibility Valve Size (inches) 1 STD. 25 STD. STD. 25 STD. 50 H.D. STD. STD. 50 STD. 100 H.D. STD. STD. 100 STD. 200 H.D. STD. STD. 200 H.D. 1.5 2 3 4 6 8 10 12 Table 16-XXXVI: ShearStream Static Torques - Sizing Valve Size TP=Packing Torque (in-lb) TS=Seat Torque CB=Bearing Torque Factor (in.) (1) (2) (3) (4) (5) (in-lb) (6) (7) 1 11/2 2 3 4 6 8 10 12 43 50 50 57 57 71 71 104 104 228 280 280 333 333 438 438 648 648 421 477 477 533 533 646 646 870 870 301 350 350 399 399 496 496 691 691 57 63 63 71 71 92 92 151 151 20 40 60 150 360 540 670 1100 1300 0.06 0.06 0.06 0.19 0.38 0.97 1.58 4.38 5.61 0.09 0.09 0.09 0.28 0.58 1.45 2.37 6.57 8.41 (1) TFE or filled TFE V-ring packing (2) Grafoil (3) Twin Grafoil (4) Asbestos-free packing (AFP) 16-24 (5) Braided PTFE (6) TFE lined bearings (7) Metal bearings CS=Seat CD = Dynamic Torque Factor Torque Factor 60O 0.1 0.1 0.15 0.42 0.82 1.64 2.62 4.55 6.05 90O 0.25 0.6 0.5 1.0 1.0 2.1 4.5 8.0 10.0 17.0 19.5 30.5 52.0 75.5 108.0 165.5 191.0 218.5
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )