Uploaded by Niraj Yadav

Online Partial Discharge Testing Guidelines for Power Cables

advertisement
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
General Guidelines for Online Partial
Discharge Testing of Power Cables
Suitable Cable Termination for online PD measurement as individual earth shield of each cable is
connected to substation earth separately. Also heat shrink tubes can be seen over earth shields
Faults in the cable insulation
Online PD testing is becoming the topic of interest for power cable owners to ensure
the safe and continuous operation of power cables.
Partial Discharge is a localised discharge in the insulation medium due
to high voltage stress that does not bridge the space between the two
conductors. Partial Discharge testing of Power Cables is one of the
diagnostic methods to detect and locate incipient faults in the cable
insulation.
http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
1/8
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
If PD source is detected timely in the cable system, it could save the huge cost
of unplanned outage to Plant owners.
Regular periodic or continuous monitoring of PDs inside cables and their accessories
will help condition monitoring team to identify the location of incipient fault and then
planning a scheduled outage of the suspected cable circuit in order to perform
corrective measures.
Offline and Online PD
PD testing of power cables can be done offline and online. When doing offline testing,
cable is disconnected at the terminations and then connected to separate power
supply. There are different types of power supplies for this purpose i.e.
Very Low Frequency (going as low as 0.1Hz to 0.01Hz),
Resonant Voltage (frequency ranging from 20 Hz to 300Hz depending on the
voltage) or
Normal power frequency (50Hz or 60Hz) supply.
Online PD testing is done while the cable is in service under normal operating
condition by installing sensors at cable termination.
Example of HFCT clamped around Earth Shield of Power Cable
These sensors include but not limited to High Frequency Current Transformer (HFCT),
Transient Earth Voltage Sensor (TEV), High Voltage Coupling Capacitor or Acoustic
Sensor. Some of these sensors can be installed while the system is online while
others (/ or in some cases) require outage of cable system in order to install them.
http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
2/8
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
Online PD testing of power cables, sometimes, becomes challenging in the
presence of high noise.
Problem of high noise worsen the situation when PD signals are superimposed onto
noise signals. Simple pulse separation and classification techniques are not effective
in such situation. Signal needs to be analysed in frequency domain then.
Following are the guidelines when conducting Online Partial Discharge Testing
of Power Cables:
http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
3/8
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
Guideline #1
Cable earth shield coming out of the cable (whether single core or three core) must
not be touching any earthed metal except at terminating point to Substation Earth.
Earth shield at cable termination should be insulated using shrink tubes in order to get
access to individual cable earths.
This will help in easy installation and reliable measurement of PD in the cables.
Suitable Cable Termination for online PD measurement as individual earth
shield of each cable is connected to substation earth separately. Also
heat shrink tubes can be seen over earth shields.
Guideline #2
At cable terminations where access to the cable end is not permitted due to Health
and Safety Regulations, permanent sensors should be installed with termination box
near cable end providing access to the sensors connected to individual cable earths.
Guideline #3
Before doing online PD measurement, it is important to know the Cable Return
Time. Cable Return Time is defined as the time taken by a pulse for completing a
round trip along the circuit length. Cable Return Time improves the accuracy of PD
source localization after detection.
http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
4/8
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
Cable return time can be measured by injecting a pulse from one cable
end and then calculating the time difference between injected and return
pulse with the help of Oscilloscope.
Guideline #4
Online PD measurement should be conducted for longer time length in order to
improve the reliability of test. Although, online periodic measurement of PD in
power cables will be able to capture continuous discharge sources and if lucky, some
intermittent discharge sources.
It is better to perform PD measurement at both ends of the cable in order to
confirm test results.
Guideline #5
Most of the PD signals flowing along the length of cables have dominant frequency
component of less than 5MHz due to low pass nature of power cable and propagation
losses. It should be noted that filtering is not desirable in the range of 100 kHz to 5
MHz as applying such filtering may also filter PD signals.
Care must be taken when filtering is done within this range.
Guideline #6
PD signals are phase consistent. However, it is also observed that noise can be
phase consistent. This might effect PD analysis if analysis is only considering Phase
Resolved patterns. There are numerous analysis tools available in the market for PD
detection within high noise. One should not only rely on such sophisticated analysis
tools.
It is advised to stick to the conventional rules of identifying PD.
However, it does not ignore the efforts done behind those analysis tools and
their importance. Such tools can be used in conjunction with basic rules.
Example of noise activity during Online PD measurement in power
cables with phase resolved characteristic
Plan View of Noise Phase Resolved Activity
http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
5/8
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
Guideline #7
Basic rules in identifying
a PD signal in noisy data
are:
1. Pulse Shape: PD pulse
travelling along the length of
cable has bigger
peak followed by few
oscillations (in some cases).
2. PD activity should be phase
consistent.
3. If such activity is found
within the data, there should
be reflected pulse(s)
after main PD pulse. Such
reflections will help in
locating incipient defect site.
However, it is also possible
that there is no reflected pulses because of long cable lengths and attenuation.
Guideline #8
When PD is detected inside power cables, it is suggested to locate the defect
http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
6/8
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
source by further investigations. Once PD source is confirmed, it is advised to plan
a scheduled outage in order to perform corrective measures.
Guideline #9
9. After corrective measures, it is also advised to perform online PD measurement
regularly or continuously for some days or weeks in order to confirm the workmanship
done during repair.
Few words more //
These are the general guidelines that can be followed to perform online PD
measurements in power cables.
However, these guidelines do not favour
or reject any technology, system or
commercially available tools.
Online PD testing of power cables can be difficult or challenging but not
impossible. By using proper procedure and correct methodology, reliable online
PD measurements can be done even in the presence of noise. With the
Get
availability of huge research material, innovative analysis tools and sophisticated
PDF
software, reliable online PD testing in power cables is possible as compared to
TOP
the concept of PD testing 10 years before.
SHARE



Recommended
EE stuff //
 with engineers //
Share




http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
7/8
12/28/2015
General Guidelines for Online Partial Discharge Testing of Power Cables | EEP
About Author //
Ammar Anwar KHAN
Ammar Anwar KHAN ­ Ammar is Technical Application
Specialist for Power Cables Condition Based Maintenance. In
current position, he conducts training and education of Sales
Teams, Field Service Teams and Power Cable owners on the
topic of Online Partial Discharge Measurements in Power
Cables.
© 2015 EEP ­ Electrical Engineering Portal. All Rights Reserved | Privacy Policy | Terms of Service | 42 queries in 0.100
seconds.
Powered by CsanyiGroup
http://electrical­engineering­portal.com/general­guidelines­for­online­partial­discharge­testing­of­power­cables
8/8
Download