SERVICE BULLETIN TOPIC: IDENT NO: SUPERSEDES: DATE: SUBJECT: Accessories 1-2620F 1-2620E November 15, 2007 Engine Protection Shutdown MODELS AFFECTED: All Waukesha Engines The tables in this Service Bulletin list “Alarm” and “Shutdown” setpoints by engine series for various engine operation parameters. These values can be used as a guide when designing engine protection or monitoring systems. The “alarm” values shown are suggested values; they can be changed to suit a specific application or measurement device. By using controls that simultaneously shut off the fuel supply and ignition system upon reaching a “shutdown” value, the potential for engine damage is reduced. Alarm and shutdown values indicate deviation from designed operation and are not meant for continuous engine service. Engine and control systems must be designed to and operated at normal values. Disregarding this information could result in product damage and/or personal injury. CAUTION WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999 Alarm and shutdown values are based on using dry natural gas of 900 BTU/cu.ft. (35.38 MJ/m3 [25,V(0;101.325)]) Saturated Lower Heating Value (SLHV) as fuel. Refer to the “Gaseous Fuel Specification for Waukesha Engines” standard sheet, S-7884-7 or latest version, and the “Lubricating Oil Recommendations for Waukesha Engines” standard sheet, S-1015-29 or latest version, for typical changes to operating temperatures for jacket water and lube oil when running on landfill or digester gas fuels. Refer to the most recent version of the Gas Engine Price Book to determine which shutdown devices are included as standard equipment with any specific engine model. Page 1 of 8 Service Bulletin No. 1-2620F 12V/18V220GL AT25GL/AT27GL JACKET WATER (HT) OUTLET TEMPERATURE Normal 100° C (212° F) Alarm 103° C (217° F) 1 Shutdown 108° C (226° F) 1 JACKET WATER OUTLET TEMPERATURE Standard Cooling System LUBE OIL HEADER TEMPERATURE Normal 75° C (167° F) Alarm 77° C (171° F) Shutdown 80° C (176° F) Rated Speed (1200 or 1500 rpm) Normal 4.2 bar (61 psi) 5.3 bar (77 psi) Alarm 2.3 bar (33 psi)1 4.0 bar (58 psi)1 Shutdown 2.0 bar (29 psi)1 3.5 bar (51 psi)1 Up to 10° C (9° F) above design intercooler water inlet temperature. Alarm 10° C (18° F) above design intercooler water inlet temperature1. Shutdown 20° C (36° F) above design intercooler water inlet temperature1. 6.5 bar (94 psi)2 Shutdown Not to exceed 7% over governed speed. OVERSPEED The minimum fuel pressure at the regulator (from Tech Data Book) Shutdown 85% of the alarm value Normal 210° – 250° F (99° – 121° C) solid water Alarm 5° F (3° C) above normal/design temperature1 Shutdown 10° F (5.5° C) above normal/design temperature1 Normal 172° F (78° C) Alarm 187° F (86° C) 197° F (92° C) Normal 60 – 65 psi (415 – 450 kPa) Alarm 50 psi (345 kPa)3 Shutdown 45 psi (310 kPa)3 Normal Up to 10° F (5.5° C) above design intercooler water inlet temperature Alarm 20° F (11° C) above design intercooler water inlet temperature Shutdown 30° F (17° C) above design intercooler water inlet temperature INTAKE MANIFOLD TEMPERATURE – AT27GL MODEL FUEL PRESSURE Alarm 20° F (11° C) above normal/design temperature INTAKE MANIFOLD TEMPERATURE – AT25GL MODEL GAS PRESSURE AT GAS TRAIN INLET Alarm Shutdown LUBE OIL HEADER PRESSURE Contact Waukesha Sales Engineering 4 – 6 bar (58 – 87 psi) 10° F (5.5° C) above normal/design temperature Shutdown INTAKE MANIFOLD PRESSURE Normal Alarm LUBE OIL HEADER TEMPERATURE INTAKE MANIFOLD TEMPERATURE Normal 180° F (82° C) for continuous rating 200° F (93° C) for intermittent rating Elevated Temperature Solid Water Cooling System LUBE OIL HEADER PRESSURE Idle Normal Normal Up to 10° F (5.5° C) above design intercooler water inlet temperature Alarm 15° F (11° C) above design intercooler water inlet temperature Shutdown 20° F (17° C) above design intercooler water inlet temperature NOTES: INTAKE MANIFOLD PRESSURE 1Alarm and shutdown functionality provided by ESM. Contact Waukesha Sales Engineering 2Alarm functionality provided by Auxiliary Systems Interface. MAIN BEARING TEMPERATURE Shutdown 250° F (121° C) Shutdown Not to exceed 10% over governed speed. OVERSPEED FUEL PRESSURE Alarm The minimum fuel pressure at the regulator (from Tech Data Book) Shutdown 85% of the alarm value NOTES: 1 Waukesha Power Systems Engomatic® Control Model 1105, 1105A, or equivalent pressure/temperature shutdown system is recommended when jacket water temperature exceeds 210° F (99°C). 2 Do not revise any values on this page without revising the same values on the “AT General Operating Limits” and “Diagram Temperature/Pressure Test Points and Pump Settings” S-sheets for the 8L, 12V, and/or 16VATGL engines. 3 Waukesha Power Systems Control is required to have an 8 second delay after engine start. Page 2 of 8 WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999 Service Bulletin No. 1-2620F VHP VHP (continued) 1 INTAKE MANIFOLD TEMPERATURE2 JACKET WATER OUTLET TEMPERATURE Standard Cooling System 180° F (82° C) for continuous rating 200° F (93° C) for intermittent rating Normal 10° F (5.5° C) above normal/design temperature2 Alarm 20° F (11° C) above normal/design temperature2 Shutdown Normal Up to 10° F (5.5° C) above design intercooler water inlet temperature Alarm 15° F (8.5° C) above design intercooler water inlet temperature2 Shutdown 20° F (11° C) above design intercooler water inlet temperature2 INTAKE MANIFOLD PRESSURE Contact Waukesha Sales Engineering Waukesha Power Systems – Std. Alarm 205° F (96° C) Shutdown 215° F (102° C) MAIN BEARING TEMPERATURE Shutdown WED Code 6010, Eutectic alloy melting point is 252° F Oil pressure switch pressure setting is 20 Psig5 Note: Alarm and shutdown differ because of the 10% overload for 2 hours in 24. Elevated Temperature Solid Water Cooling System (All Applications) Normal 210° – 235° F (99° – 113° C) for solid water Alarm 5° F (3° C) above normal/design temperature2,3 Shutdown 10° F (5.5° C) above normal/design temperature2,3 OVERSPEED Shutdown 212° – 250° F (100 – 121° C) Alarm See Note 4 Shutdown See Note 4 Shutdown 10–15% over governed speed, not to exceed 1320 RPM Caution When setting engine overspeed shutdown, do not exceed the lesser of engine or driven equipment’s speed limits. To avoid equipment damage, consult the driven equipment manufacturer for maximum overspeed value. FUEL PRESSURE LUBE OIL HEADER TEMPERATURE Alarm The minimum fuel pressure at the regulator (from Tech Data Book) Shutdown 85% of the alarm value Normal 180° F (82° C) Alarm 195° F (91° C)2 NOTES: Shutdown 205° F (96° C) 1For 2 Naturally Aspirated Standby Rating with auxiliary cooling connected to jacket cooling. 200° F (93° C) Alarm 205° F (96° C) Shutdown 10% over governed speed2 Waukesha Power System Ebullient Water Cooling System (All Applications) Normal 250° F (121° C) engines equipped with ESM, refer to ECU calibration and appropriate S-08312-XX sheet to determine limits of operating conditions. 2 Alarm and shutdown functionality provided on engines equipped with ESM. Alarm 200° F (93° C) 3 Waukesha Power Systems Engomatic® Control Model 1105, 1105A, or equivalent shutdown system is recommended when jacket water temperature exceeds 210 ° F (99° C). Shutdown 205° F (96° C) 4Waukesha WED Code 1107 LUBE OIL HEADER PRESSURE 6 and 12 Cylinder Models Normal 50 – 60 psi (345 – 415 kPa) Alarm 35 psi (241 kPa)2, 5 Shutdown 30 psi (207 kPa)2, 5 Power Systems Engomatic® Control Model 1106, 1106A, or equivalent shutdown system is recommended for ebulliently cooled engines. 5 Waukesha Power Systems Control is required to have an 8 second delay after engine start. 16 Cylinder Models Normal 30 – 50 psi (207 – 345 kPa) Alarm 30 psi (207 kPa)5 Shutdown 25 psi (172 kPa)5 LUBE OIL FILTER DIFFERENTIAL PRESSURE Normal 2 – 15 psi (14 – 103 kPa differential) Alarm 15 psi (103 kPa differential)2 WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999 Page 3 of 8 Service Bulletin No. 1-2620F 16V150LTD F1197 JACKET WATER (HT) OUTLET TEMPERATURE Normal 99° C (210° F) Alarm Shutdown JACKET WATER OUTLET TEMPERATURE Normal 180° F (82° C) 105° C (220° F) 1 Alarm 200° F (93° C) 110° C (230° F) 1 Shutdown LUBE OIL HEADER TEMPERATURE Normal 88° C (190° F) Normal 160° – 210° F (71° – 99° C) Alarm 93° C (199° F) Alarm 225° F (107° C) 96° C (204° F) Shutdown Shutdown Idle Rated Speed (1500 or 1800 rpm) Normal 2.4 bar (35 psi) 3.6 bar (52 psi) Alarm 2.0 bar (29 psi)1 2.8 bar (40 psi)1 Shutdown 1.6 bar (24 psi)1 2.4 bar (35 psi)1 235° F (113° C) LUBE OIL HEADER PRESSURE LUBE OIL HEADER PRESSURE Normal 40 – 50 psi (276 – 345 kPa) Alarm 15 psi (103 kPa) Shutdown 10 psi (69 kPa) INTAKE MANIFOLD TEMPERATURE Not Applicable INTAKE MANIFOLD TEMPERATURE INTAKE MANIFOLD PRESSURE Normal Up to 10° C (9° F) above design intercooler water inlet temperature. Contact Waukesha Sales Engineering Alarm 11° C (20° F) above design intercooler water inlet temperature1. Contact Waukesha Sales Engineering Shutdown 14° C (25° C) above design intercooler water inlet temperature1. INTAKE MANIFOLD PRESSURE Contact Waukesha Sales Engineering. GAS PRESSURE AT GAS TRAIN INLET Normal 0.05 – 0.09 bar (0.75 – 1.25 psi) OVERSPEED Shutdown Alarm Shutdown 50 Hz: 1750 rpm 60 Hz: 1980 rpm MAIN BEARING TEMPERATURE OVERSPEED Shutdown Not to exceed 15% over governed speed F817 JACKET WATER OUTLET TEMPERATURE Normal 180° F (82° C) Alarm 195° F (91° C) Shutdown 205° F (96° C) LUBE OIL HEADER TEMPERATURE FUEL PRESSURE Normal 160° – 230° F (71° – 110° C) The minimum fuel pressure at the regulator (from Tech Data Book) Alarm 240° F (116° C) Shutdown 250° F (121° C) 85% of the alarm value NOTES: 1 210° F (99° C) LUBE OIL HEADER TEMPERATURE Alarm and shutdown functionality provided by ESM. LUBE OIL HEADER PRESSURE Normal 35 – 45 psi (241 – 310 kPa) Alarm 15 psi (103 kPa) Shutdown 10 psi (69 kPa) INTAKE MANIFOLD TEMPERATURE Not Applicable INTAKE MANIFOLD PRESSURE Contact Waukesha Sales Engineering OVERSPEED Shutdown Page 4 of 8 Not to exceed 15% over governed speed WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999 Service Bulletin No. 1-2620F VGF VGF (continued) JACKET WATER OUTLET TEMPERATURE LUBE OIL HEADER PRESSURE Standard Cooling System Engines less than or equal to 176 BMEP F18/H24 Models Normal 67 – 83 psi (462 – 572 kPa) Alarm 40 psi (276 kPa)2 10° F (5.5° C) above normal/design temperature Shutdown 35 psi (241 kPa)2 20° F (11° C) above normal/design temperature Normal 66 – 82psi (455 – 565 kPa) Alarm 40 psi (276 kPa)2 Shutdown 35 psi (241 kPa)2 Normal 180° F (82° C) for continuous rating 200° F (93° C) for intermittent rating Alarm Shutdown L36/P48 Models Waukesha Power Systems – Std Alarm 205° F (96° C) Normal 215° F (102° C) INTAKE MANIFOLD TEMPERATURE Alarm and Shutdown differ because of the 10% overload for 2 hours in 24 With Standard Intercooler Water Temperatures of 85° – 130° F (29° – 54° C) GL/GLD/GSI/GSID Engines with less than or equal to 176 BMEP Shutdown Elevated Temperature, Solid Water Cooling System Engines less than or equal to 176 BMEP – All Applications Normal Normal 210° – 265° F (99° – 130° C) for solid water Up to 10° F (5.5° C) above design intercooler water inlet temperature Alarm Alarm 5° F (3° C) above normal/design temperature1 15° F (8.5° C) above design intercooler water inlet temperature Shutdown Shutdown 10° F (5.5° C) above normal/design temperature1 20° F (11° C) above design intercooler water inlet temperature With Elevated Intercooler Water Temperatures of 131° – 176° F (55° – 80° C) Elevated Temperature, Solid Water Cooling System 200 BMEP Engines – All Applications Normal 210° F (99° C) solid water Alarm 10° F (5.5° C) above normal/design temperature1 Shutdown 15° F (8.5° C) above normal/design temperature1 Normal Up to 10° F (5.5° C) above design intercooler water inlet temperature Alarm 10° F (5.5° C) above design intercooler water inlet temperature Shutdown 15° F (8.5° C) above design intercooler water inlet temperature With Elevated Intercooler Water Temperatures of 158° – 176° F (70° – 80° C) 200 BMEP GLD Engines Only LUBE OIL HEADER TEMPERATURE Jacket Water Temperature of 180° F (82° C) and Intercooler Temperature of 85° – 130° F (29° – 54° C) Engines less than or equal to 176 BMEP – All Models Normal 170° – 195° F (76.5° – 90.5° C) Alarm 200° F (93° C) Shutdown 205° F (96° C) 170° – 195° F (76.5° – 90.5° C) Alarm 200° F (93° C) Shutdown 205° F (96° C) 190° F (88° C) Alarm 200° F (93° C) Shutdown 205° F (96° C) Alarm 10° F (5.5° C) above design intercooler water inlet temperature Shutdown 15° F (8.5° C) above design intercooler water inlet temperature Contact Waukesha Sales Engineering MAIN BEARING TEMPERATURE Contact Waukesha Sales Engineering OVERSPEED Shutdown Not to exceed 15% over governed speed. FUEL PRESSURE Jacket Water Temperature of 210° F (99° C) and Intercooler Temperature of 158° – 176° F (70° – 80° C) 200 BMEP GLD Engines Only Normal Up to 10° F (5.5° C) above design intercooler water inlet temperature INTAKE MANIFOLD PRESSURE Jacket Water Temperature of 265° F (129° C) and Intercooler Temperature of 85° – 130° F (29° – 54° C) Engines less than or equal to 176 BMEP – All Models Normal Normal Alarm The minimum fuel pressure at the regulator (from Tech Data Book) Shutdown 85% of the alarm value NOTES: 1Waukesha Power Systems Engomatic® Control Model 1105, 1105A, or equivalent pressure/temperature shutdown system is recommended when jacket water temperature exceeds 210 ° F (99° C). 2 Waukesha Power Systems Control is required to have an 8 second delay after engine start. 3 Waukesha Power Systems Control is required to have a 5 minute delay after engine start for all applications that run with (less than or equal to) 125° F intercooler water. WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999 Page 5 of 8 Service Bulletin No. 1-2620F VSG JACKET WATER OUTLET TEMPERATURE 180° F (82° C) Normal Alarm 200° F (93° C) Shutdown 210° F (99° C) LUBE OIL HEADER TEMPERATURE with a Jacket Water Temperature of 180° F (82° C) F11G Model Normal 205° F (96° C) Alarm 215° F (102° C) 225° F (107° C) Shutdown F11GSI Model 190° F (89° C) Normal Alarm 200° F (93° C) Shutdown 210° F (99° C) LUBE OIL HEADER PRESSURE Normal 65 – 87 psi (448 – 600 kPa) Alarm 40 psi (276 kPa) Shutdown 30 psi (207 kPa) INTAKE MANIFOLD TEMPERATURE (GSI) Normal Up to 15° F (8.5° C) above design intercooler water inlet temperature Alarm 20° F (11° C) above design intercooler water inlet temperature Shutdown 25° F (14° C) above design intercooler water inlet temperature INTAKE MANIFOLD PRESSURE Contact Waukesha Sales Engineering MAIN BEARING TEMPERATURE Contact Waukesha Sales Engineering OVERSPEED Shutdown Not to exceed 15% over governed speed. FUEL PRESSURE Alarm The minimum fuel pressure at the regulator (from Tech Data Book) Shutdown 85% of the alarm value Page 6 of 8 WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999 Service Bulletin No. 1-2620F GENERATOR ALARMS AND SHUTDOWNS KATO CLASS F INSULATION GENERATORS – See Kato drawing for setpoint recommendations on standby units Generator Winding (Prime Power) Alarm 311° F (155° C) Shutdown 329° F (165° C) Generator Bearing Alarm 185° F (85° C) Shutdown 203° F (95° C) MARATHON ELECTRIC MAGNAMAX DVR GENERATORS Prime Power (105° C) Generator Winding Alarm 293° F (145° C) Shutdown 311° F (155° C) Prime Power (105° C) Generator Bearing Alarm 230° F (110° C) Shutdown 248° F (120° C) Standby Power (130° C) Generator Winding Alarm 338° F (170° C) Shutdown 356° F (180° C) LEROY SOMER CLASS H INSULATION GENERATORS Prime Power (105° C) Generator Winding Alarm 194° F (90° C) Shutdown 203° F (95° C) Prime Power (105° C) Generator (Sleeve or Roller) Bearing Alarm 194° F (90° C) Shutdown 203° F (95° C) Standby Power (130° C) Generator Winding Alarm 392° F (200° C) Shutdown 401° F (205° C) Standby Power (130° C) Generator (Sleeve or Roller) Bearing 401° F (205° C) Comments: Class H is Leroy Somer standard. Only class H settings should be used for the LSA461 to LSA51 low voltage generators. These values are ISO standard and should be used as maximums only. LEROY SOMER NA (MAGNETEK) CLASS F INSULATION GENERATORS Standby Power (130° C) Generator Bearing Alarm 230° F (110° C) Shutdown 248° F (120° C) 392° F (200° C) Alarm Shutdown Generator Winding (Prime Power) Alarm Shutdown Prime or Standby Generator Winding Temperature Switch (GWTS) Shutdown Comments 302° ± 9° F (150° ± 5° C) Switch N.O. or N.C. GWTS is not located in the winding a lot like the RTD or thermocouple so a lower temperature device is used. No alarm GWTS is available at this time. 311° F (155° C) 329° F (165° C) Generator Bearing Alarm 185° F (85° C) Shutdown 194° F (90° C) LEROY SOMER CLASS F INSULATION GENERATORS Prime Power (105° C) Generator Winding Alarm 302° F (150° C) Shutdown 311° F (155° C) Prime Power (105° C) Generator (Sleeve or Roller) Bearing Alarm 194° F (90° C) Shutdown 203° F (95° C) Standby Power (130° C) Generator Winding Alarm 347° F (175° C) Shutdown 356° F (180° C) Standby Power (130° C) Generator (Sleeve or Roller) Bearing Alarm 239° F (115° C) Shutdown 248° F (120° C) WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999 Page 7 of 8 Service Bulletin No. 1-2620F NEWAGE GENERATORS GENERATOR WINDING INSULATION CLASS WARNING SHUTDOWN °F °C °F °C A 194 90 230 110 E 230 110 266 130 B 248 120 284 140 F 284 140 320 160 H 338 170 374 190 COMMENTS: These values are recommended by the British Standard BS4999 Part 72, which Newage Int. follow. Page 8 of 8 WAUKESHA ENGINE DRESSER, INC. WAUKESHA, WI 53188-4999