Friday, December 27, 2024, 01:33:54 Soil analysis report Station Name Untitled Project Study GP EarthingGrid 1 GP EarthingGrid 1 Parameters Title GP EarthingGrid 1 Soil Model Two-Layer Safety Model Body Weight Surface Layer Thickness Surface Layer Resistivity Shock Duration IEEE Std. 80-2000 50 kg 0.1 meters 3000 ohm-m 1 secs Output Results Upper Layer Thickness Upper Layer Resistivity Lower Layer Resistivity 4.44 meters 6.8 ohm-m 1.13 ohm-m Reduction Factor Cs Maximum Permissible Touch Maximum Permissible Step 0.690359 476.37 volts 1557.47 volts RMS Error 20.19 % Assumed Values Probe Distance (meters) 0.3 0.59 0.88 1.17 1.47 1.76 2.05 2.34 2.64 2.93 3.22 3.51 3.81 4.1 4.39 4.68 4.97 5.27 5.56 5.85 6.14 6.44 6.73 7.02 7.31 7.61 12/27/24 02:09:56 Calculated Resistivity (ohm-m) 6.8 6.79 6.77 6.74 6.69 6.62 6.52 6.41 6.28 6.13 5.97 5.8 5.61 5.42 5.23 5.03 4.84 4.65 4.46 4.27 4.09 3.92 3.76 3.6 3.45 3.3 1/3 7.9 8.19 8.48 8.78 9.07 9.36 9.65 9.95 10.24 10.53 10.82 11.12 11.41 11.7 11.99 12.29 12.58 12.87 13.16 13.46 13.75 14.04 14.33 14.63 14.92 15.21 15.5 15.8 16.09 16.38 16.67 16.97 17.26 17.55 17.84 18.14 18.43 18.72 19.01 19.31 19.6 19.89 20.18 20.48 20.77 21.06 21.35 21.65 21.94 22.23 22.52 22.82 23.11 23.4 23.69 23.99 24.28 24.57 24.86 12/27/24 02:09:57 3.17 3.04 2.92 2.8 2.69 2.59 2.5 2.41 2.33 2.25 2.18 2.11 2.05 1.99 1.94 1.89 1.84 1.79 1.75 1.71 1.68 1.65 1.62 1.59 1.56 1.54 1.51 1.49 1.47 1.45 1.43 1.42 1.4 1.39 1.38 1.36 1.35 1.34 1.33 1.32 1.31 1.3 1.3 1.29 1.28 1.28 1.27 1.26 1.26 1.25 1.25 1.24 1.24 1.24 1.23 1.23 1.23 1.22 1.22 2/3 25.16 25.45 25.74 26.03 26.33 26.62 26.91 27.2 27.5 27.79 28.08 28.37 28.67 28.96 29.25 1.22 1.21 1.21 1.21 1.21 1.2 1.2 1.2 1.2 1.2 1.19 1.19 1.19 1.19 1.19 Tabulated Values Probe Distance (meters) 1.5 3 4.5 6 9 15 20 12/27/24 02:09:57 Measured Resistivity (ohm-m) 5.46 6.75 6.9 4.99 2.49 1.29 1.84 Calculated Resistivity Error (ohm-m) (%) 6.68 22.35 6.09 -9.73 5.16 -25.29 4.18 -16.21 2.72 9.23 1.55 20.37 1.3 -29.27 3/3