Find voltages πππ and πππ and the source current πΌπ 3 . First, note that voltage ππ is directly across voltage source πΈ1 . Therefore, ππ = πΈ1 = 20 V The same is true for voltage ππ , which is directly across the voltage source πΈ3 . Therefore, ππ = πΈ3 = 8V To find voltage ππ , we must apply Kirchhoff's voltage law around loop 1 as: +πΈ1 − πΈ2 − π3 = 0 so, π3 = πΈ1 − πΈ2 = 20 V − 5 V = 15 V and, ππ = π3 = 15 V Voltage πππ , which is actually the voltage across resistor π 1 , can then be determined as: πππ = ππ − ππ = 20 V − 8 V = ππ π Similarly, voltage πππ , which is actually the voltage across resistor π 2 , can then be determined as follows: πππ = ππ − ππ = 15 V − 8 V = π π π π 7V Current πΌ2 can be determined using Ohm's law: πΌ2 = π 2 = π ππ = 4Ω = 1.75 A 2 2 The source current πΌπ 3 can be determined using Kirchhoff's current law at node π : ΣπΌπ = ΣπΌπ πΌ1 + πΌ2 + πΌπ 3 = 0 π1 πΌπ 3 = −πΌ1 − πΌ2 = − − πΌ2 π 1 with π1 = πππ = ππ − ππ = 20 V − 8 V = 12 V 12 V so that, πΌπ 3 = − 10Ω − 1.75 A = −1.2 A − 1.75 A = −π. ππ π Given that the circuit of the figure is a balanced bridge. a. Calculate the unknown impedance, Zπ₯ . b. Determine the values of πΏπ₯ and π π₯ if the circuit operates at a frequency of 1 kHz. a. The expression for the unknown impedance is determined by: Zπ₯ Z2 Z3 Z1 (10kΩ)(100Ω) = 30kΩ∠ − 20β = 33.3Ω∠20β = ππ. π + πππ. π π = b. From the preceding result, we have, π π₯ = ππ. π π π 11.4Ω πΏ and, πΏπ₯ = 2ππ = 2π(1000 Hz) = π. ππ π¦π A station operating at 33 kV is divided into sections A and B. Section A consists of three generators 15 MVA each having a reactance of 15% and section B is fed from the grid through a 75 MVA transformer of 8% reactance. The circuit breakers have each a rupturing capacity of 750 MVA. Determine the reactance of the reactor in ohm to prevent the breakers being overloaded if a symmetrical short circuit occurs on an outgoing feeder connected to A. Assume the base MVA as 75. 75 The p.u. reactance of each generator = 0.15 × 15 = π0.75 The p.u. reactance of transformer = π0.08 p.u. Let π₯% be the reactance of the reactor for base of 75 MVA. The equivalent circuit for a fault of π΄ is as shown in diagram. The per cent impedance between the fault point and the neutral bus is 0.25(π + 0.08) 0.25π + 0.0200 = 0.25 + π + 0.08 π + 0.33 Now S.C. MVA 750 187π + 15.00 112π π Base MVA p.u. impedance 75(π + 0.33) = 0.25π + 0.02 = 75π + 24.75 = 9.75 = 0.08705 p.u. = ∴ Actual value of reactance in ohms = 0.08705×332 75 = π. πππ π¨π‘π¦π¬ A 6.6kV, 5MVA star connected alternator has a reactance of 1.5 ohm per phase and negligible resistance. MerzPrice protection scheme is used which operates when the out of balance current exceeds 25% of the full load current. The neutral of the generator is grounded through a resistance of 8 ohms. Determine the proportion of the winding which remains unprotected against earth fault. Show that the effects of the alternator reactance can be ignored. First, we will show that the effect of the alternator reactance can be neglected. Since the reactance of the winding is ∝ square of the number of turns, i.e., π₯G ∝ π 2 , let π₯% be the winding that remains unprotected. The number or turns will be π₯π/100, i.e., the reactance will be proportional to π₯ 2 π 2 /1002 . 1.5π₯ 2 π 2 ∴ If 1.5 ohm is the reactance of the winding, the reactance of the un-protected winding will be 1002 . Since this reactance is to be added vectorially with resistance of 8 ohms and π₯ being small, the effect of the reactance can be neglected. The phase voltage will be, 6600 √3 = 3810 volts. π₯ The voltage of the unprotected portion = 3810 100 π₯ 1 amps 100 8 5000 = = 437.37 amps √3 × 6.6 The fault current = 3810 The out of balance current required for the operation of the relay = 437.37 × 0.25 = 109.34 amps Now, or, 3810π₯ 800 4.7625π₯ π₯ = 109.34 = 109.34 = ππ. ππ%. The difference amplifier in the figure has an input voltage π£π = 3 V. What range of π£π will ensure that the opamp operates in the linear region? The limits on the output voltage are determined by the power supply rail voltages. In this example, the supply voltages are +15 V and -15 V. Therefore, the output voltage must be, −15 V < π£π < +15 V π π π Since π π΄ = π πΆ the input voltage π£π can be calculated, π£π = π π΄ π£π + π£π π΅ π· π΅ Substituting π π΄ = 2.2 kΩ and π π΅ = 5.1 kΩ into the equation for π£π yields for the upper and lower limits of the output voltage, π£π = +15 V: π£π = 9.47 V And, π£π = −15 V: π£π = −3.47 V Then the input voltage range for π£π to ensure linear operation of the amplifier is, −π. ππ π < ππ < π. ππ π In a 25kVA. 1100/400 V, single phase transformer, the iron and copper losses at full load are 350 and 400 watts, respectively. Calculate the efficiency on unity power factor at half load. Determine the kVA at which maximum efficiency occurs. Transformer rating = 25kVA Iron losses, ππ = 350 W Full load copper losses, ππ = 400 W Load power factor cos π = 1 1 Fraction of the load π₯ = 2 = 0 ⋅ 5 Efficiency of transformer, ππ₯ π₯ × πππ΄ × 103 × cos π = × 100 π₯ × πππ΄ × 103 × cos π + ππ + π₯ 2 ππ 0.5 × 25 × 103 × 1 = × 100 = ππ. ππ % 0.5 × 25 × 103 × 1 + 350 + (0.5)2 × 400 π 350 Output kVA corresponding to maximum efficiency = Rated kVA √ππ = 25 × √400 = 23.385 kVA π Output power or load on maximum efficiency = output kVA for max efficiency × π. π. = 23.385 × 1 = ππ. πππ π€π What is the resolution of a 8 -bit ADC operating at 10 V range. Here, Operating Range, 2mp = 10 V No. of bit, π = 8 So, Quantization Level, πΏ = 2π = 28 = 256 2 mp 10 So, resulation, Δ = L = 256 = 0.0390625 V = ππ. ππππ π¦π 293