SPECIFICATIONS:
Part Number: IS200ATBAG1BAA1
Manufacturer: General Electric
Series: Drive Control
Product Type: Application Input/Output Terminal Board
Number of channels: 1 channels
Input span: 1 - 5 V dc
Outputs: 24 V dc
Power: 28 V
Generator current inputs: 0 to 5 A
Analog inputs Current inputs: 4-20 mA
Analog output current: 0-20 mA
Size: 15.9 cm high x 17.8 cm
Operating Temperature: 0 to +60°C
Frequency: 50 or 60 Hz
Repair: 3-7 Day
Availability: In Stock
Weight: 2 lbs
Country of Origin: United States
Manual: GEH-6385
FUNCTIONAL DESCRIPTION:
IS200ATBAG1BAA1 is an Application Input/Output Terminal Board Manufactured and
Designed by General Electric as part of the Mark VIe Series used in GE Drive Turbine
Control Systems. It is a crucial component within General Electric's Innovation Series,
incorporating features like a Windows 2000/XP-based operator interface, Ethernet and
DCS communications, and Cimplicity software. Terminal Board forms a critical part of
General Electric's Innovation Series, offering an operator interface, communication
capabilities, and software integration. The board features various connectors with
different voltage ratings for J6 and J7, necessitating attention to these variations during
handling or replacement. Additionally, adherence to safety protocols, such as electrical
circuit testing before replacement, is highly recommended to mitigate potential risks
during maintenance procedures involving the board.
FEATURES:
Terminal Block Configuration: Provides a single 60-position terminal block catering to all
J6 and J7 jumper connections to the CABP board.
1/3
Jumper Connection Details: No customizable hardware or manually movable jumpers are
present in the IS200ATBAG1B. However, two versions of this model exist, each featuring
different pin assignments for connectors J6 and J7.
Connector Ratings:
J7 Connector: Rated for 50V with a 1A maximum.
J6 Connectors: Generally rated for 225V with a 1A maximum, except for specific
connectors like CONA_NO, CONA_NC, CONA_C, RLY1COM, RLY1NC, RLY1NO,
RLY2COM, RLY2NC, RLY2NO, RLY3COM, RLY3NC, and RLY3NO, which have
different voltage ratings.
Connector Base Plate Ratings: Most connectors affixed to the base plate are rated for
176V with a 1A maximum, differing from the specific J6 connectors rated at 225V
maximum. All J7 connections maintain a rating of 50V with a 1A maximum.
Safety and Replacement Recommendations: Electrical Testing Before Replacement:
Before replacing the board, it is strongly advised to perform electrical circuit testing.
Ensure that no potentially dangerous voltages are present on the board's surface when
powered off to prevent accidental exposure to hazardous electrical currents.
WOC has the largest stock of GE Drive Turbine Control System Replacement Parts. We
can also repair your faulty boards. WORLD OF CONTROLS can also supply unused and
rebuilt backed-up with a warranty. Our team of experts is available round the clock to
support your OEM needs. Our team of experts at WOC is happy to assist you with any of
your automation requirements. For pricing and availability on any parts and repairs, kindly
contact our team by phone or email.
FREQUENTLY ASKED QUESTIONS:
What is an Application Input/Output Terminal Board?
An Application Input/Output Terminal Board, commonly referred to as an I/O Terminal
Board, is a hardware component used in various electronic systems to manage the input
and output functionalities. It acts as an interface between the system's central processing
unit and external devices or peripherals.
Where are I/O Terminal Boards commonly used?
I/O Terminal Boards find applications in various industries and systems, including
industrial automation, process control, robotics, automotive electronics, aerospace, and
instrumentation.
What types of input and output signals can an I/O Terminal Board handle?
2/3
Depending on the specific design and application requirements, an I/O Terminal Board
can handle a wide range of signals, including analog voltage/current, digital logic signals,
frequency/pulse inputs, temperature, pressure, and various sensor outputs.