Jeddah Central Development Company (JCD)
Technical Comparison Sheet
PROJECT TITLE: Main Utilities & Public Realm [Infrastructure]
SUBMITTAL TITLE: TECHNICAL SUBMITTAL FOR LV CABLE&WIRE
SPECIFICATIONS REFERENCE,
I.E. SECTION, PAGE NO. ETC
Detailed Master Planning
and Engineering--SECTION
260519 - LOW VOLTAGE
ELECTRICAL POWER
CONDUCTORS AND CABLES
(Pg 1-5)
MATERIAL. SOURCE
(MFR/SUPPLIER)
BAHRA ADVANCED
CABLES
TRANSMITTAL NO : TR-INFR-CHEC-JCDC-MTS-0060
DATE: 21-May-24
SPECIFICATION REQUIREMENT
PROPOSED MATERIAL
Drawings. Phases shall be color coded in
conformity with the Standards, and overall
cable sheath shall be extruded black LS0H
material. Cables shall comply with IEC
60332-3.
15)-Fire resistant LS0H Cable (abbreviated
as FR2 on the drawings): Multi core solid or
stranded plain annealed copper conductors
to IEC 60228 (in sizes up to 16 mm2), dual
layer insulation with fire resistant tape
primary insulation layer and XLPE secondary
insulation layer, category CWZ to BS 6387,
complying with BS EN 50363, LS0H
composite sheath with tinned earth continuity
conductor/drain wire to IEC 61034 and IEC
60754 or BS EN 50267-2-1. Cable shall
comply with IEC 60331 for fire resistant
characteristics at an enhanced temperature
of 950 deg. C. and shall comply with IEC
60332-1-2 for flame retardant properties.
Cable shall be rated 600/1000 V, capable of
accepting voltage surges up to 5 kV,
operating conductor temperature of 90 deg.
C.[Cable shall be LPCB and BASEC
certified, audited and marked by embossing
on cable sheath.]
16)-Fire resistant LS0H Cable (abbreviated
as FR3 on the drawings,) : Multi core solid or
stranded plain annealed copper conductors
to IEC 60228 (in sizes up to 4 mm2), fire
15)- Out of our product range
REMARKS
IDENTIFY ANY
DEVIATIONS FROM
SPECS AND JUSTIFY
Jeddah Central Development Company (JCD)
Technical Comparison Sheet
PROJECT TITLE: Main Utilities & Public Realm [Infrastructure]
SUBMITTAL TITLE: TECHNICAL SUBMITTAL FOR LV CABLE&WIRE
SPECIFICATIONS REFERENCE,
I.E. SECTION, PAGE NO. ETC
Detailed Master Planning
and Engineering--SECTION
260519 - LOW VOLTAGE
ELECTRICAL POWER
CONDUCTORS AND CABLES
(Pg 1-5)
Detailed Master Planning
and Engineering--SECTION
260519 - LOW VOLTAGE
MATERIAL. SOURCE
(MFR/SUPPLIER)
BAHRA ADVANCED
CABLES
BAHRA ADVANCED
TRANSMITTAL NO : TR-INFR-CHEC-JCDC-MTS-0060
DATE: 21-May-24
SPECIFICATION REQUIREMENT
resistant insulation, galvanized steel wire
armored, category CWZ to BS 6387, PH60
classified to BS EN 50200, and 30 minutes
rating when tested with additional water
spray in accordance BS EN 50200 Annex E
and complying with BS EN 50363, laminated
aluminum screen and LS0H composite
sheath with tinned earth continuity
conductor/drain wire to IEC 61034 and IEC
60754. Cable shall comply with IEC 60332-1
& 3 (category C) for flame retardant
properties. Cable shall be rated 300/500 V,
capable of accepting voltage surges up to 5
kV, operating conductor temperature of 70
deg. C. Cable shall be LPCB and BASEC
certified, audited and marked by embossing
on cable sheath.
17)-Fire resistant LS0H Cable 600/1000 V,
(abbreviated as FR5 on the drawings, similar
to Prysmian -Type FP-400, or approved
equal): Multi core plain copper stranded
circular or shaped conductor (sizes up to
400mm2) complying with IEC 60228 with fire
resistant insulation category CWZ to BS
6387, category F2 to BS 7846, PH60
classified to BS EN 50200 and 30 minutes
rating when tested with additional water
PROPOSED MATERIAL
16)- Out of our product range
17)-Complied as per category F2 to BS 7846
REMARKS
IDENTIFY ANY
DEVIATIONS FROM
SPECS AND JUSTIFY