Halton HELP Project: Location: Designed by: Date: 1 Madero 4 broilers RSantos 28/01/2019 LAYOUT OF ROOM "COZINHA" E 2.000 m3/s@307 Pa (st) #H_1 . . . With KSA HVF E 1.800 m3/s@256 Pa (st) Total E 3.800 m3/s #H_2 E 1.060 m3/s@240 Pa (st) Total E 1.060 m3/s . #_H_1.1 . . . . . 15.0 m 15.0 m . . with Blind Filter . . Air distribution: Mixing, supply from ceiling Tapered hoods: #H_2 h=610/460, #_H_1.1 h=760/610, #H_1 h=760/610 Halton HELP Project: Location: Designed by: Date: 2 Madero 4 broilers RSantos 28/01/2019 HOODS IN ROOM "COZINHA" Item Model L mm B mm H mm #H_2 KVE Total: 2750 1400 610/4601.060 1.060 #_H_1.1 #H_1 KVE KVE Total: 3450 3450 1400 1400 760/6101.800 760/6102.000 3.800 Total: Exh.Flow T.A.B dp m3/s Pa 4.860 CJ Flow m3/s CJ dp Pa 212 0.043 0.043 63 226 279 0.038 0.038 0.075 60 60 0.118 Air distribution: Mixing, supply from ceiling Hood length does not include the stand-off, hood width includes the stand off Sup.Flow Supply dp m3/s m3/s Halton HELP Project: Location: Designed by: Date: 3 Madero 4 broilers RSantos 28/01/2019 COOKING LINE SPECIFICATION 1 #H_2 . . . . Hood group enclosure: Back wall APPLIANCES Item . Description L mm B mm H mm Load kW k-sim Fuel Fryer (deep fat) 400 950 910 60.0 0.70 Gas 400 950 910 60.0 0.70 Gas 1090 360 880 730 910 1220 52.8 23.4 0.70 0.70 Gas Gas Pitco I Fritadeira a Gás I 35C+S e 45C+S . Fryer (deep fat) Pitco I Fritadeira a Gás I 35C+S e 45C+S . . Range Pasta Cooker Total: Size of the group: 2450 x 1000 mm 196.2 Halton HELP Project: Location: Designed by: Date: 4 Madero 4 broilers RSantos 28/01/2019 HOODS Item Model L mm B mm H mm #H_2 KVE 2750 1400 610/4601.060 2750 1400 610 Total: Exh.Flow T.A.B dp m3/s Pa 1.060 212 CJ Flow m3/s CJ dp Pa 0.043 63 0.043 Hood length does not include the stand-off, hood width includes the stand off Sup.Flow Supply dp m3/s m3/s Halton HELP Project: Location: Designed by: Date: 5 Madero 4 broilers RSantos 28/01/2019 COOKING LINE SPECIFICATION 2 #H_1 #_H_1.1 . . . . . . . . . Hood group enclosure: Back wall APPLIANCES Item . Description L mm B mm H mm Load kW k-sim Fuel Fryer (deep fat) 400 950 910 100.0 0.70 Gas 400 950 910 100.0 0.70 Gas 360 750 1040 - 0.00 None 400 950 910 100.0 0.70 Gas 400 950 910 100.0 0.70 Gas 914 686 910 35.0 1.00 Gas 914 686 910 35.0 1.00 Gas 914 686 910 35.0 1.00 Gas 914 686 910 35.0 1.00 Gas Pitco I Fritadeira a Gás I 35C+S e 45C+S . Fryer (deep fat) Pitco I Fritadeira a Gás I 35C+S e 45C+S . Dump Station . . Fryer (deep fat) Pitco I Fritadeira a Gás I 35C+S e 45C+S . Fryer (deep fat) Pitco I Fritadeira a Gás I 35C+S e 45C+S . Charbroiler Char Broiler a Gás Vulcan VCRB36 . Charbroiler Char Broiler a Gás Vulcan VCRB36 . Charbroiler Char Broiler a Gás Vulcan VCRB36 . Charbroiler Char Broiler a Gás Vulcan VCRB36 Total: Size of the group: 6596 x 1000 mm 540.0 Halton HELP Project: Location: Designed by: Date: 6 Madero 4 broilers RSantos 28/01/2019 HOODS Item Model L mm B mm H mm #_H_1.1 #H_1 KVE KVE 3450 3450 1400 1400 760/6101.800 760/6102.000 6900 1400 760 Total: Exh.Flow T.A.B dp m3/s Pa 3.800 226 279 CJ Flow m3/s CJ dp Pa 0.038 0.038 60 60 0.075 Hood length does not include the stand-off, hood width includes the stand off Sup.Flow Supply dp m3/s m3/s Halton HELP Project: Location: Designed by: Date: 7 Madero 4 broilers RSantos 28/01/2019 HOOD SPECIFICATION 1-1 L W H Model: Item number: Length (L): Width (B): Height (H): Installation height: Stand-off from back: Nmb of exhaust collars: Exhaust collar size: Exhaust collar centerdist: Exhaust system: Nmb of capture collars: Nmb of KSA filters: Nmb of blind filters: Calculated exhaust airflow: Min. airflow: Selected exhaust airflow: T.A.B reading: Hood static pressure drop: Capture airflow: Capture Ray: Short Cassettes: Long Cassettes: KVE (Canopy) #H_2 2750 mm 1400 mm 610/460 mm 2030 mm 80 mm 2 300x200 mm 688 mm 1 5 0 0.888 m3/s 0.566 m3/s 1.060 m3/s 212 Pa 240 Pa 0.043 m3/s Yes 2 - Hood length does not include the stand-off, hood width includes the stand off Halton HELP Project: Location: Designed by: Date: 8 Madero 4 broilers RSantos 28/01/2019 HOOD SPECIFICATION 2-1 L W H Model: Item number: Length (L): Width (B): Height (H): Installation height: Stand-off from back: Nmb of exhaust collars: Exhaust collar size: Exhaust collar centerdist: Exhaust system: Nmb of capture collars: Nmb of KSA filters: Nmb of blind filters: Nmb of short filters: Calculated exhaust airflow: Min. airflow: Selected exhaust airflow: T.A.B reading: Hood static pressure drop: Capture airflow: Capture Ray: Short Cassettes: Long Cassettes: KVE (Canopy) #_H_1.1 3450 mm 1400 mm 760/610 mm 1980 mm 80 mm 2 330x300 mm 863 mm 1 6 (high volume filter) 0 1 1.578 m3/s 1.229 m3/s 1.800 m3/s 226 Pa 256 Pa 0.038 m3/s Yes 1 1 Hood length does not include the stand-off, hood width includes the stand off Halton HELP Project: Location: Designed by: Date: 9 Madero 4 broilers RSantos 28/01/2019 HOOD SPECIFICATION 2-2 L W H Model: Item number: Length (L): Width (B): Height (H): Installation height: Stand-off from back: Nmb of exhaust collars: Exhaust collar size: Exhaust collar centerdist: Exhaust system: Nmb of capture collars: Nmb of KSA filters: Nmb of blind filters: Nmb of short filters: Calculated exhaust airflow: Min. airflow: Selected exhaust airflow: T.A.B reading: Hood static pressure drop: Capture airflow: Capture Ray: Short Cassettes: Long Cassettes: KVE (Canopy) #H_1 3450 mm 1400 mm 760/610 mm 1980 mm 80 mm 2 380x300 mm 863 mm 1 6 (high volume filter) 0 1 1.994 m3/s 1.229 m3/s 2.000 m3/s 279 Pa 307 Pa 0.038 m3/s Yes 1 1 Hood length does not include the stand-off, hood width includes the stand off Halton HELP Project: Location: Designed by: Date: 10 Madero 4 broilers RSantos 28/01/2019 FIRE SUPPRESSION SPECIFICATION FOR GROUP 1 APPLIANCES Item Description Hazard area mm Min H mm Nozzle Type Nozzle Qty Flow Points . . . . Fryer (deep fat) Fryer (deep fat) Range Pasta Cooker 324x620 324x620 1090x575 635 635 1016 3N 3N 245 1 1 2 3 3 4 Duct nozzles Type Qty Plenum nozzles Type Qty Dir Flow Points - - - HOODS Item #H_2 Model KVE L mm B mm H mm 2750 1400 610/460- ANSUL SYSTEMS System Nmb Flow Points 3 Gal Qty 1 10 1 - - Halton HELP Project: Location: Designed by: Date: 11 Madero 4 broilers RSantos 28/01/2019 FIRE SUPPRESSION SPECIFICATION FOR GROUP 2 APPLIANCES Item Description Hazard area mm Min H mm Nozzle Type Nozzle Qty Flow Points . . . . . . . . . Fryer (deep fat) Fryer (deep fat) Dump Station Fryer (deep fat) Fryer (deep fat) Charbroiler Charbroiler Charbroiler Charbroiler 324x620 324x620 635 635 3N 3N 1 1 3 3 324x620 324x620 889x508 889x508 889x508 889x508 635 635 381 381 381 381 3N 3N 1N 1N 1N 1N 1 1 1 1 1 1 3 3 1 1 1 1 Duct nozzles Type Qty Plenum nozzles Type Qty Dir Flow Points - - - HOODS Item #_H_1.1 #H_1 Model KVE KVE L mm B mm H mm 3450 3450 1400 1400 760/610760/610- ANSUL SYSTEMS System Nmb Flow Points 3 Gal Qty 1 16 2 - -