Gunter Klefenz Automatic Control of Steam Power Plants • ''-7 . ÿ ÿ1 1 i . .1 .. . ÿ_ . . .. - 1 J i i / 9 w- Mr ÿ Wissenschaftsverlag Bibliographisches Institut / ' A r ' CIP-Kurztitelaufnahme der Deutschen Bibliothek Klefenz, Gunter: Automatic control of steam power plants / by Gunter Klefenz. Transl. from German by Vladimir F. Tomek. - 3., rev. ed. - Mannheim; Wien; Zurich: Bibliographisches Institut, 1986. Einheitssacht.: Die Regelung von DampfkraftWerken <engl.> Preface to the English Edition The lively demand from foreign countries made it seem sensible to publish an English edition additionally to the French edition. Thus, the third revised edition of 1981 was translated by Dr. Vladimir F. Tomek, Dublin, to whom Iwould like to express my sincere gratitude for an excellent translation. Only the bibliography has been expanded by the subject lit¬ erature written in English. ISBN 3-411-01699-X In conclusion, grateful acknowledgement is due to the publishing company for their pleasant cooperation as well as for the care taken with the lay-out of this book. Minden, February, 1986 G. Klefenz Preface to the 3rd Revised Edition In comparison with the preceeding edition, the 3rd edition has been thor¬ oughly revised. This had become necessary due to the amount of new knowledge gained over the last ten years. Substantial supplementary chan¬ ges have been introduced in the areas of unit control, combustion control, and feedwater control. A review of bled-off steam control for rapid release of power has been incorporated for the first time, and the chapter on combined heat-and-power plants has been expanded. The passage dealing with the simulation of the drum level controlled systems has been com¬ pletely re-written. Finally, the bibliographical references have been supple¬ mented by the incorporation of important new publications on power plant control. All rights reserved, including of this publication may be those of translation. No part reproduced, stored in a retriev¬ al system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or other¬ wise, without the prior written permission of the publish¬ er. This also applies to the use of the publication for educational purposes, such as preparation of course notes. © Bibliographisches Institut, Zurich 1986 Printed in Germany by Druckerei Speyer; bound by Pilger-Druckerei GmbH,Krembel, Speyer ISBN Iwould like to thank in particular Mr. Rainer Seidel for the valuable sug¬ gestions and discussions, as well as for proofreading the revised manuscript. Further, Iam grateful to the publishers who were always willing to accomodate my requirements. Minden. August, 1981 3-411-01699-X i G. Klefenz Preface Preface to the 1st Edition It would be impossible to imagine our present highly technological era without power stations. At the same time, a modern power station which does not rely on automatic control is almost impossible to think of. This is because automation is a necessary condition for safe operation which minimizes material fatigue and can be conducted with minimum staff, enabling efficient management of a plant. The present book is intended to provide a survey of the current situation in power station control, as well as to facilitate an introduction into this particular field for students, plant engineers, and control technologists. The latter point is the main reason why particular emphasis has been put on descriptive representation, and why the text is accompanied by signal flow diagrams (= block diagrams) in addition to the many control loop diagrams. Basic knowledge of the fundamentals of control and plant engi¬ neering techniques had to be assumed. There is practically no mathema¬ tical description. Instead, the text provides rules-of-thumb and graphical methods for a sufficiently accurate determination of the various control characteristics, both dynamic and static. These are particularly important in the planning stages where it is often necessary to estimate control dynamics from only a few design data. Generally, for preliminary calcu¬ lations particular accuracy is not demanded. As to the arrangement of this book, power plants are at first considered as a unit. This is followed by individual descriptions of turbine controls and boiler controls. Naturally, the main part of the book is dedicated to boilers. An explanation of all the essential boiler control loops is followed by a discussion of the pertinent signal flow diagrams of the controlled systems. The relevant references to technical literature are listed at the end of each section. All the views expressed in the individual sections of the book are predo¬ minantly those of the control engineer. It is realised that architectural considerations should have preference if the object happens to be the construction of a plant. Unfortunately, such conflicting views can be touched upon only briefly. The interested reader is referred to the rele¬ vant literature. 7 As regards the symbols used in the book, it should be mentioned that as far as possible current standards are being adhered to. However, in order to avoid misunderstandings, some deviations have become unavoidable. Iam grateful to Director, Mr. G. Pressler, for accepting the book for inclusion in the Control Engineering Series, which is published by him. Iwould also like to express particular thanks to Mr. W. Opitz for his help in proofreading the manuscript as well as for the many indications of possible improvements. Finally, Iwould like to gratefully acknowledge the endeavour of the publishers to meet all my wishes. Minden, March, 1971 G. Klefenz r Table of Contents . 11 Introduction 13 Basic Design of a Power Plant 13 2.1 Unit Arrangement 14 2.2 Busbar Arrangement 17 Main Control Objectives 27 Generator Control 32 Turbine Control 34 Load Isolated Supplying 5.1 Nonreheat Turbine 37 Grid Power a to Connected 5.2 Nonreheat Turbine 40 5.3 Single-Reheat Turbine 44 5.4 Accessory Turbine Controls 46 5.5 Sliding Pressure Operation 50 Unit Master Control 57 a Control of Boilers on Busbar 62 Boiler Control 62 8.1 Types of Boilers 62 Boiler 8.1.1 Natural Circulation 64 Boiler 8.1.2 Forced Circulation 64 8.1.3 Benson Boilers 66 8.1.4 Sulzer Boilers 68 8.2 Control Loops 74 Loop Control Pressure Steam 8.2.1 Live 83 Control Loop Flow Air 8.2.2 99 8.2.3 Furnace Draught Control Loop 100 8.2.4 Steam Temperature Control Loop 109 8.2.5 Feedwater Control Loop 130 8.2.6 Reheat Steam Temperature Control Loop 134 8.2.7 Other Control Loops 138 8.3 Signal Flow Diagrams of Controlled Systems 8.3.1 Steam Pressure Controlled System in a Drum Boiler. . 139 8.3.2 Steam Pressure Controlled System in a Benson 150 Boiler 8.3.3 Steam Pressure Controlled System in a Sulzer Boiler . 155 158 8.3.4 Steam Temperature Controlled System 173 8.3.5 Level Controlled System in a Drum Boiler 10 _______ Table of Contents 8.4 Signal Flow Diagram of «a wvuouii Benson jDuner 0 Boiler InclllHinor Controls Cr»n +*•/-*! Including 8.5 Quality of Control 9 Combined Heat-and-Power Plant (CHP Plant) e 10 Nuclear Power Plants 10.1 Types of Reactors 10.2 Control in Nuclear Power Stations 10.3 Dynamic Behaviour of Nuclear Reactors 11 Appendix 11.1 Symbols 11.2 Bibliography 11.3 Subject Index ana a Turbine, and turbine, 180 183 191 196 196 198 202 212 212 217 247 1 Introduction Power plants are used to convert the raw energy available in nature into electrical energy. When the conversion has as an intermediate stage the production of thermal energy contained in steam, we talk about steam power plants. In a steam power plant the first step is the conversion of raw chemical energy into thermal energy. This process takes place in the so-called boiler or steam generator. The thermal energy is then transported by the carrier steam into the turbine where it is changed into mechanical energy. Finally, the mechanical energy is transformed into electrical energy in the generator (Fig. 1). Turbine Boiler Raw energy 5 U Thermal energy h Generator Mechanical energy Electrical energy as carrier) Fig. 1 Scheme of a steam power plant. Power plants may be designed to produce as their main product some form of thermal energy, and not necessarily electrical energy. The heatand-power plants provide steam needed for district heating, while many industrial plants (primarily power plants in the chemical industry) are used to produce process steam. In all such power stations the electrical energy is, to a certain degree, only a by-product. These variations in energy production give one possibility of classifying the power plants. They can be divided into: — condensing power plants (for pure power production), and — heat-and-power plants (primarily for heat production). Another frequently used classification criterion is the fuel which is fired. The main distinction is made between fossil and nuclear fuels. Fossil fuels can in turn be subdivided into solid fuels (coal, brown coal, etc.), liquid 12 1Introduction fuels (oil), and gaseous fuels (blast furnace gas, natural gas, etc.)- It is likewise possible, and also customary, to combine the individual fuels. As will be shown in more detail later, the above quoted characteristics are essential for control. Other criteria, such as the size of the plant, etc., are only of minor importance, and will not be discussed. 2 Basic Design of a Power Plant It appears expedient to start with a description of the most important plant designs; discussion will, however, be limited to such features as are neces¬ sary for the synthesis of the respective control loops. The two basic types of plant to be distinguished for control purposes are the unit arrangement (containing a single turbine and usually only one boiler), and the arrange¬ ment using a common live steam range (with one or more turbines and several steam generators, all units interconnected). 2.1 Unit Arrangement At present, the unit arrangement is the most common in use. As can be seen from Fig. 2, in a unit power plant the boiler, the turbine, the genera¬ tor, and all the auxiliaries are combined to form a unit. 1 2 3 4 5 6 7 8 9 10 11 Boiler Turbine Generator Condenser Condensate pump Low pressure preheater Feedwater storage tank Feedwater pump High pressure preheater Main transformer Transformer for station consumption Fig. 2 Basic design of a unit power plant. 14 15 2.2 Busbar Arrangement 2 Basic Design of a Power Plant Since the auxiliaries in each block also have a fully independent consump¬ tion, it is possible to operate each unit independently of other units in the station. In large units of 300 or more MW, a unit may also consist of two boilers feeding one turbine. This is sometimes called the 'blending unit arrange¬ ment' or the 'twin-boiler blending system'. Simple units have several advantages, even though a trip of one part of the plant may bring about total outage. For details and a full description of these advantages, which lie beyond the scope of this book, one should consult the pertinent technical literature (for instance, [11]). In this book will be mentioned only the most important facts from the point of view of automatic control. To begin with, there is the problem of steam re¬ heating. Since in the unit arrangement there is an unequivocal coupling between the turbine and the reheater, and since the reheater is always ex¬ pected to admit the right amount of steam in proportion to the supplied heat, the effect of disturbances is reduced making the reheat steam tempe¬ rature easier to control. Another point to consider is that the feedwater control is also favourably influenced. Since feedwater pumps are always associated with only one specific boiler, it is possible to control the speed of the pumps, and to minimize throttling losses across feedwater valves; in some cases the losses can be fully eliminated by omitting the control valves altogether. The third advantage of the unit arrangement is that it is particularly suitable for load control. As will be seen later, it is possible to optimise load control by a specific co-ordination of the boiler and the turbine. With such an arrangement it is also possible to apply variable pressure control. 2.2 Busbar Arrangement In the past, the prevalent layout was based on the'busbar arrangement shown on Fig. 3. Among the main reasons quoted for this approach were the low operational safety and the limited controllability of average steam generators. The characteristic of the busbar arrangement which is also known as the 'common live steam line arrangement', is that all boilers feed, in parallel, a common live steam line, and are themselves supplied from a common feedwater collecting line. Among the various disadvantages of the arrangement described (such as high specific unit costs, complicated heat distribution, increased danger of 1 Boiler 2 Turbine 3 Generator 4 Condenser 5 Condensate pump 6 Low pressure preheater 7 Feedwater storage tank 8 Feedwater pump 9 High pressure preheater 10 Main transformer 11 Transformer for station consumption Fig. 3 Basic structure of a power plant with a steam and feedwater busbar. -— - r - its Adverse effects feedwater pollution, etc.) it is also necessary to mention arrangement (see Section on automatic control. In contrast to the unit load control. It is a con¬ with are 2.1), the main difficulties experienced follow the overall load they that so siderable problem to bias the boilers relative individual their changing variations, without, at the same time, is con¬ arrangement busbar the disadvantages, loading. In spite of all the industrial in and stations, power sistently applied in two areas: In isolated steam. power stations primarily designed to produce process for ensuring the avail¬ It certainly appears logical to use the range system isolated power stations rare relatively the in ability of the necessary energy to a large grid connected not stations i.e. installed in small utility plants, In this situa¬ consumer. a particular to only system but supplying power cause a si¬ necessarily instance, for not, tion, the loss of a boiler should either be can load the of share lost multaneous loss of a turbine. The can be boiler stand-by a or picked up by the boilers still in operation, brought in. 16 2 Basic Design of a Power Plant In industrial power stations which are primarily designed to provide proc¬ ess steam, the arrangement appears to represent a logical development of standard practice. With several small boilers steaming in parallel, it is only natural to use a common main line from which the individual de¬ mands can be satisfied. Boiler of the topping plant Topping turboset (primary high-pressure turbine exhausting into the mediumpressure plant) Boilers of the medium-pressure plant Condensing turboset (medium-pressure plant) 3 Main Control Objectives At all times, power plants must provide the load required by the consumer, in other words, the main task of control is to match the energy generated to the energy consumed. In this respect it is immaterial whether the energy is produced in the form of pure electrical power (as in stations providing load for large power supply grids), or in the form of combined power and heat (as in industrial power stations or district heating plants). Further, the produced energy must have the required quality, i.e. electrical power must be provided with a given voltage and frequency, while thermal energy must be supplied in the form of steam with a given temperature and pressure. The twin control objectives are represented on the simplified control flow diagrams shown on Fig. 5 and Fig. 6. However, it should be pointed out already at this stage, that it would not be practicable to try and implement these simple forms in practice, since the quality of control that could be achieved would not be high. r" i Fig. 4 b-©- Basic structure of topping high pressure plant. In this context the topping high-pressure plants should also be mentioned. The topping arrangement is used to improve the economy of old mediumpressure plants which have been in operation for some time. As shown on Fig. 4, the required effect is achieved by supplying high-pressure steam into the old medium-pressure line, using a back-pressure turbine. Finally, it should be noted that the busbar system can frequently be found in district heating (power-and-heat) plants. References: [3] [11] [83] [92] [194] [243] [275] .J Fig. 5 Basic control objectives in a condensing power station isolated from the power grid. Fig. 5 illustrates, in a highly simplified form, the main control tasks in a condensing power plant designed for the exclusive production of electri¬ city, and operating in isolation from the network. The symbols used in the diagram mostly follow DIN 2481 (December, 1954). The terminal voltage u ist kept constant by changes in the excitation currents in the field winding of the synchronous generator. At the same time, the control of the turbine speed n keeps the frequency of the produced electrical power at the set point (i.e. maintains reference speed). 2 Klefenz A _ 3 Main Control Objectives 3 Main Control Objectives In this case, the controlling element for the turbine speed control is the energy supplied to the boiler in the form of fuel. A change in the con¬ sumption of electrical energy causes at first a change of voltage and of speed, then the controllers intervene, and, finally, in the new steady state, the equilibirum between consumption and production is established at an appropriately changed fuel flow level. As has been already pointed out, such simple configurations (as shown in Figures 5 and 6) have severe limitations. These are caused by the following two factors: Firstly, electrical energy cannot be stored in any substantial quantity, and, as a result, must be produced when needed and not before. This means that whenever it is necessary to prevent a drop of frequency to unacceptable levels due to an energy deficit (caused, for instance, by an extended energy expenditure), very fast control loops must be applied. Unfortunately, the speed control loop as shown on Fig. 5 is by no means fast. The reaction of the control circuit (which starts with the fuel-handling equipment and continues through the heat release in the furnace, steam production, and the acceleration of the turboset to the output ter¬ minals of the transformer) is always rather sluggish. This is due to unavoid¬ able storage processes and to the resistance to change which varies with each type of the boiler and type of fuel. The inherent inertia makes it impossible to remedy a frequency drop resulting from an increased load demand by an instantaneous change in the steam production. Fortunately, the situation can be redressed by turning the already mentioned detrimen¬ tal storage effect into an advantage. However, to achieve this it is neces¬ sary to modify the control diagram: The new control loop in which the delays in establishing the actual change in the steam production are reduced by way of by-passing the accumulation capacities, is shown in principle on Fig. 7. 18 Z Fig. 6 Basic control objectives in a power station designed for producing process steam. Fig. 6 shows, once again in the form of a highly simplified diagram, the basic control tasks in an industrial power plant which is primarily intended for providing process steam. The state of the steam, i.e. its pressure and temperature, is to be kept constant. The temperature d is controlled by injecting a variable quantity of attemperation water into the steam down¬ stream of the back-pressure turbine. The deviations of the steam pressure P from the set point are equalized by controlled changes in the fuel firing rate. Should, for instance, too much steam be withdrawn by consumers, pressure P would drop, and the controlling element would increase the fuel flow into the steam generator. The control action would continue until a new balance between consumption and production of steam is established, and pressure has again reached its original value. In a control loop of this kind it is, of course, not possible to provide special turbine controls, since the system would become over-controlled. It is, therefore, assumed that the generator is connected to the power grid. The effect of such a measure will be discussed later. It i Fig. 7 19 r*-i j ®u -Hf L. Simplified control scheme of a condensing power plant isolated from the power grid. In Fig. 7, the original slow speed control loop is split into two loops, a fast speed control loop and a slow pressure control loop. The mode of action is as follows: The speed, and with it the frequency, is now controlled by changing the opening of the turbine throttle valve. The action is very fast, well maintaining the frequency desired. 20 3 Main Control Objectives 3 Main Control Objectives The rapid changes in the flow of steam to the turbine are made possible by the fact that steam can be temporarily stored during load decreases, and withdrawn from the boiler during load increases. Unfortunately, such use of boiler storage causes steam pressure variations. As a countermeasure, the steam pressure should be introduced as an extra control variable, its variations controlling the fuel flow. This would cause the turbine to respond quickly to all load consumption requirements, while the steam generator would follow slowly, the steam pressure control being affected by the in¬ herent inertia of the boiler. A further possibility to solve the problem of maintaining constant frequen¬ cy is that of establishing a link with the power grid, which is, at present, but for a few exceptions the common approach. In such a system many power stations and many consumer units are linked together to form a large electrical network. The advantages are obvious: Should an individual power plant fail, the taking-up of the lost load by the remaining units can provide an uninterrupted continuation of supply to all consumers; the changes of the load, even though it remains dependent on consumption, become somewhat less pronounced. Frequency can be maintained con¬ stant with relative ease since the system contains quickly reacting units (e.g. hydro-electric power plants) which respond to disturbances with mi¬ nimum delay, while the remaining more sluggish units can adjust their contribution gradually. The variations in controllability of power plants resulted in the formation of various proposals as to the control of the power supply system: The following text illustrates this point. Two unit blocks linked to a common consumer system will be used as an example. In the discussion, the voltage control does not have to be dealt with since it is not affected by the considered modes of operation. a) Both Units Take Part in Frequency Control (Variable Load Operation) For this mode of operation both block power plants are equipped with control instrumentation corresponding to Fig. 7. However, two typical cases are to be distinguished: In the first case, the speed controllers are structured as purely proportional controllers. This is in agreement with one of the basic rules of control engineering, according to which (for reasons of stability) it is not allowed to use two or more controllers with proportional plus integral action for controlling the same controlled variable. 21 50 Hz Fig. 8 Control characteristic of a turboset with a P-controlIer. Nl = load of unit No. 1 IV2 = load of unit No. 2 /= frequency In each block, the use of P controllers results in a control characteristic similar to the one given in Fig. 8. The control characteristic reproduces the relationship between frequency and the unit electrical output. For the case of a proportionally acting speed controller, the characteristic considered here is a down-sloping straight line. The gradient is determined by the proportional band xp ad¬ justed on the controller. Due to the particularly favourable time behaviour of the con trolled system, a very small xp can be chosen (for instance, " 2.5„Jflz. Since xp is mostly stated as a percentage value, with the nominal frequency of 50 Hz as reference value, xp = 5%). As can be seen from Fig. 8, each load change is coupled with a frequency change. For example, for the same adjustments that were used for obtaining the characteristic in Fig. 8, a change in the consumer load of AN 20% would give a lowering of frequency of f y- K> (1) Af=~ xp AN 50Hz 100% 100% m = -0,25 Hz In the equation, m = 2 is the number of blocks taking part in the exercise. Naturally, the frequency can be again increased to 50 Hz by re-adjusting the set point setter. This would produce a parallel shift of the control characteristic, as is demonstrated in Fig. 9. It is evident that any frequency can be associated with any particular load by a simple shift of the set point. 0<j1 r 3 Main Control Objectives 3 Main Control Objectives 22 t 50 Hz Shift of the control characteristic of a turboset, caused by a change in the set point. Fig. 9 / Ahxunequal adjustment of the two set points would result in an unequal loading of the two power stations (see Fig. 10). However, grid load changes would be covered proportionally, i.e. each unit would contribute its pro¬ portional share. Should the two blocks be required to coastrrbtrte to the total load each at a different rate, different xp settings would be needed. Fig. 11 shows, for example, that due to a smaller xp, the speed controller for block No. 1 would tend to make block No. 1 contribute more than block No. 2. 23 In the second case, one of the blocks has a proportional plus integral speed controller, while the other is still fitted with a proportional controller. In steady state, this arrangement is adequate for keeping the frequency al¬ ways exactly at the same set value. The block with the P-controller does not participate permanently in load changes, since automatic control always returns its electrical' output to the originally set value. It does, however, temporarily participate in maintaining frequency. This is a typi¬ cal example of a frequency supporting operation which is extremely important, and should be applied in power systems as a matter of policy. An increased number of power plants contributing to frequency control will improve the quality of the performance as well as make the system more stable. In the above situation, the frequency controlling power sta¬ tion can be considered analogous to the fast reacting hydro-electric plants, particularly the pumped-storage plants, while the plant fitted with a pro¬ portional speed controller corresponds to the thermal power stations. The load set points of these thermal power stations are adjusted according to a time-table obtained from the daily load variation curves. This is done so as to enable the frequency controlling stations to keep the frequency at the set point. \ b) A Power Plant Unit Does Not Participate in Frequency Control (Constant Load Operation) 50 Hz 0 Fig. 10 N, N; 100V. N Differently set control characteristics of two turbosets. 1 Xp, Xp; UaNz-* Fig. 11 Control characteristics with different xp settings. Both block power plants discussed in paragraph a) were of the so-called active type, i.e. they were taking part in maintaining constant frequency. On the other hand, a passive (or inactive) block does not take part in such activity. As shown on Fig. 12 and Fig. 13, passive blocks can be applied according to two basic diagrams. In these or such diagrams block No. 1 is always active, block No. 2 passive. In the alternative presented on Fig. 12, the steam pressure upstream of the turbine of the block No. 2 is kept constant by the turbine throttle valves. This prevents any utilisation of boiler storage: The turbine feeds into the system only so much power as is produced by the boiler. Since fuel flow to the boiler is normally adjusted at a constant value, the boiler evaporation rate, and subsequently also the generator output, remain constant. The changes in frequency cause no changes in power production. The total load change required by the consumer side must be raised by the active blocks. The calculation of the resulting change in frequency A f, caused by a load change of AN = 20%, gives for the same proportional r _ 5 Main Control Objectives 24 I 3 Main Control Objectives 25 mode of operation should be full load (which is, of course, constant; i.e. the units are passive). f-® HZ]- 1 -00- OD- Fig. 12 Basic control scheme: One unit active, one unit passive band for speed control as was used before (5%) a frequency decrease of 0.5 Hz. A comparison with the previously calculated value for the case when both power plant blocks participated in maintaining constant fre¬ quency, shows that the original decrease of — 0.25 Hz has been doubled. This confirms the extremely important conclusion that in any electrical system as many power plants as possible should participate in frequency control. Only in this manner can the frequency be kept within narrow limits. Further, only in this manner is it also possible to guarantee the sta¬ bility of large electrical systems, as well as to guard against the situation where the failure of a specific part of a power system releases a chain re¬ action which then overloads the tie-line to the neighbouring system. Such an overloading may result in a spontaneous separation of the two systems, which further increases the probability of a total collapse of the first system. Participation in frequency control should be extended even to the relative¬ ly inert brown coal fired power plants, since as the installed capacity in¬ creases, the share of the storage power stations pÿcgdes more and more into the background. The increasing contribution by nuclear power plants brings no relief, since, due to initial high capital expenditure, their (revalent Fig. 13 Basic control scheme: One unit active, one unit passive. Fig. 13 depicts another variant of a passive unit application. This time, the turboset of block No. 2 is equipped with load control, i.e. the delivered electrical energy is controlled by turbine inlet valves, and the load is deter¬ mined by the set point setter. In this case, an increased or a decreased delivery of power can be achived only by adjusting the set point setter. In contrast to the alternative shown on Fig. 12, the boiler is controlled in the same manner as if it were in an active unit. In operation, the fuel flow is automatically adjusted so that the steam pressure at the boiler outlet is kept constant. This steam pressure serves as a measure of the imbalance between the boiler steam output and the steam taken up by the turbine. V T". t \W- J The main difference between the passive units presented in Figures 12 and 13, consists in the unit shown on Fig. 13 being faster in following an im¬ posed load change than the unit on Fig. 12. The reason for this being that the passive unit on Fig. 13 uses the boiler storage capacity.ÿThis comes aboutjwhen upon increasing the load set point, the turbine inlet valves open so wide that the new load is reached r 26 v 3 Main Control Objectives i-cÿ' A behaviour of the controlled sy¬ quickly. Due the favourable time to very stem, this process is very fast. The required increase of steam flow is brought about at the expense of boiler storage. This in turn causes the steam pressure to drop accordingly, while the pressure controller ensures that the storage is again refilled, and that more steam per time unit is pro¬ duced as power increases. In contrast to this, in the scheme on Fig. 12, the load increase must be initiated by an increase of energy in the fuel supplied. The steam pressure rises in dependence on the inertia of the firing and steam producing processes, and the pressure controller tends to open the turbine inlet valves accordingly. All this means that an actually increased steam production is a precondition to a load increase. Due to its sluggish behaviour, such circuit is at present only very rarely applied. Instead, preference is given to fast reacting arrangements for load control. As already explained in the preceeding chapter, one of the main control tasks is to maintain a constant,synchronous gerjemor terminal voltage both latter approach has the additional advantage of being easily extended - The shouldjhe needTtnsg* In order make the unit participate in frequency to 3 ÿcontrol, it is sufficient to introduce an additional frequency measurement, tÿderive)from it a suitable signal, and to let this signal affect the set point /for load control. The result is one of the most frequent control techniques ,( which will be discussed in some detail later. ÿ3 Finally, to complete this sub-section, it should be mentioned that naturally all turbines are equipped with speed control, even if it,is not shown in the diagrams. In all these cases the speed controller acts as a safety device against excessive speed. This can be achieved, for instance, by adjusting the set point in such manner that the controller can start acting only when the speed limit is exceeded. References: [3] [11] [66] [76] [83] [93] [117] dgrAc, - c J[iV£ ÿ•-1 4 Generator Control J under normal operating conditions and under fiauIt}/o ndit ions. This re¬ quires control of the excitation, and the respective control loop is presented in simplified form on Fig. 14. The control variable is the output voltage Ug of the excitation system the impedance (seen 'looking into' the network at the machine terminal) and/ or the generator reactive output act as distur¬ bances. The DC voltage which is applied to the generator field winding (i.e. the exciter output), can be produced by various methods. There are many options: The exciter voltage regulators can be electromechanical, solid-state, based on a rotating amplifier or a magnetic amplifier, etc., while the excitation control systems are manufactured with DC generator/ commutator exciters, alternator/rectifier exciters, compound/rectifier exciters, potential-source/rectifier exciters, etc. The most frequently em¬ ployed are exciters driven directly by the shaft of the main synchronous generator (i.e. of the DC generator/commutator type). Further, it is neces¬ sary to differentiate between the various interconnections of the field and the armature: There are, for instance, self-excited and separately excited machines, etc. Unfortunately, the various aspects of generator are too many and too diverse to be satisfactorily dealt with in this publication, and the readeris referred to special technical literature. Here the principles of ge¬ nerator control will be explained with the aid of Fig. 14; the scheme re¬ presents an exciter mounted on the main generator shaft, the exciter being separately excited and having its output fed into the rotor of the synchroi r ,i.i -0— "=•9-—© [™] -<i> Fig. 14 Control scheme of voltage control of a synchronous generator. ue -© ie — r 4 Generator Control 4 Generator Control 28 29 nous machine through slip rings. The generator terminal voltage u is compared with a reference voltage, and the resulting error voltage is fed into the amplifier of a P or PI acting controller. In accordance with the control deviation the controller adjusts the excitation of the exciter E which in turn provides the excitation voltage ue. The static relationship between the excitation current ie and the generator voltage u is shown in the form of a diagram on Fig. 15. The thick line re¬ presents the idling (no-load) characteristic, to the left and to the right of which are short sections of other characteristics corresponding to different loads. (Note that lagging, i.e. inductive loads, require overexcitation, whereas leading, i.e. capacitive loads, call for underexcitation.) Each cos ÿ is associated with a different characteristic. The diagram also illustrates the well known fact that a change in excitation may not only influence the voltage, but also the reactive power: In fact, if a generator is connected to a large and, from the point of voltage, stiff system, then a change in excitation will affect only the generator reactive output. idling characteristic capacitive cos/=0 0 inductive load characteristics u us i L Fig. 15 voltage voltage set point generator current exciter current Idling and load characteristics of a synchronous generator. An insight into the dynamic behaviour of the synchronous generator can be obtained from the transfer functions in Fig. 16. What Fig. 16 primarily shows is the time behaviour of the voltage u following a sudden load change. This load change is the result of a change in the network impedance 3, providing the excitation voltage Ug remains constant. A raise in load (or a decrease in impedance) is, in the first instance, followed by a sudden drop of the terminal voltage u, accompanied, since there is no initial change in the flux, by an equally sudden increase in the excitation current ie. Sub¬ sequently, the strength of the field slowly falls along a curve determined by a time constant. Meanwhile voltage behaves in a like manner, and, similarly, the excitation current gradually reverts to its original value. Fig. 16 Transfer functions of a synchronous generator. Following a load decrease, all these processes would develop in the opposite direction. The mentioned time constant lies approximately between one and twenty seconds, depending on the output of the machine, on its design, on its speed of rotation, and on its current load. In large turbogenerators with several hundred MVA it is necessary to assume a time constant of 20 seconds. The difficulty with control of these sets is that, following a load change, the output voltage of the excitation system must be very quickly adjusted. This is so because only a rapid application of a high excitation voltage can arrest the decay of the induced field cur¬ rent, and then build it up again in the shortest possible time. It follows that the quality of control predominantly depends on the dynamics of the cho¬ sen exciter arrangement. Separately-excited machines have shorter time constants than self-excited ones, and this makes them preferable from the control point of view. Fig. 17 shows a block diagram corresponding to the control scheme of Fig. 14. Blocks 1 and 2 represent the generator, 3 and 4 V 4 Generator Control 4 Generator Control the exciter. The letter 3 stands for load impedance which, in this case, is the main disturbance. The dotted line in the diagram indicates the path of the generator current signal iwhich appears to move the set point by combining with it in the manner of an auxiliary signal. This measure is needed when several gene¬ rators work together to supply the entire load of a power system, or in the case of several interconnected power systems. Such multi-area operation causes problem which are in principle quite similar to those that have been already encountered in the loading of parallel power stations, and were discussed in chapter 3. In practice, any parallel operation of the kind described above can be achieved by means of a suitable type of cross-current compensation. Such a method employs a resistor or an impedance in the voltage measuring circuit. A current proportional to the reactive current delivered by the generator is fed through the device, to produce a small load dependent voltage which is added to the terminal voltage. This gives a slight droop to the voltage held by the regulator on reactive loads, and causes the de¬ sired change in the characteristic (reactive currents are divided in proportion to load currents). Another method is not to use a PI controller but a P controller with the proportional band chosen so that it corresponds to the desired characteristic. In the latter case the generator current signal i would be superfluous. 30 In order to achieve stability of generators operating in parallel it is neces¬ sary to use a type of open loop control which will correct the characteristics of the individual generators. Such control will adjust all the prescribed re¬ lationships between the various generator variables, i.e. between the reactive and active current, between the reactive current and voltage, etc. Again, the ultimate aim is to have possibly all generators provided with excitation/ voltage regulating systems which will enable them to share the kVAr of the group load on a proportionate basis. Note that to enable the AC generators, operating in parallel, to share the kW of a group load on a proportionate basis, the turbines must be provided with suitable governors, as load sharing is not a function of the generator excitation/voltage regulating system. (Any adjustment of field excitation changes the kilovars, whereas prime mover characteristics must be adjusted to change the kilowatts). 31 In conclusion, a few words will be said about the actual instrumentation used in practice. Originally, electromechanical regulators were used, and some are still in service; they are generally not suitable for machines of about 75 MW and above owing to the high field current required for the main exciter. The voltage reference in these regulators was provided either by the spring tension against which the solenoid was to act, or by the use of relays as voltage sensitive elements. Voltage sensitive quick-response contacts were used to insert exciter field resistance elements in various combinations (series, bridges, etc.). This is, for instance, the basis for the design of the well known Tirrill controller, which is a vibrating-contact regulator. Purely electrically operated controllers have been introduced relatively recently. They use directly operated magnetic or electronic ro¬ tating amplifiers which, in turn, supply the control voltage for the exciters. References: [3] [4] [92] [182] [190] [202] [222] [225] [226] [238] [239] [240] [296] [303] [305] [309] [318] -ÿo- »s controller 1, 2 generator 3, 4 exciter u generator voltage ue exciter voltage uy controller output voltage i us (control variable) generator voltage set point generator current 3 load impedance <+; Fig. 17 Signal flow diagram of a voltage control loop of a synchronous generator. ÿ\ r dc 5 Turbine Control should the control stage be already fully commited, directly to either the first stage chamber or to a stage situated even further back. This is indi¬ cated on the diagram by dotted lines. 5 Turbine Control The basic principles of turbine control have been already commented upon in Chapter 3. The most important controlled variable is speed or rather frequency, followed by electrical power or load (the megawatt-frequency control channel); next in order of importance is steam pressure. The following text will be devoted to a more detailed discussion of turbine control. However, particulars will be mentioned only when such informa¬ tion should prove important for the description of the basic behaviour of the plant. Unfortunately, there is not enough scope to look into safety arrangements such as tripping mechanisms and other limit-value controls. t fixed guide ÿ wheel nozzles I First 1 stage I " chamber' Curtis wheel In what follows let us first consider the point of application of turbine control. To this effect, the electrical power Nwill be expressed as follows: (2) 33 2nd runner wheel N= mD Ah ÿ where mD = Ah = steam flow steam enthalpy drop Equation (2) shows that there are two possibilities to change the turbine electrical power. This can be done either by adjusting the steam flow (= the so-called nozzle group control governing) or by varying the enthalpy drop (= the so-called throttle governing). In practice, of course, it would be very difficult to find the two methods in pure form. Steam flow and enthalpy changes always occur together. In theory, the difference between the two methods can be explained with the aid of Fig. 18. In the upper part of the figure is a schematic presentation of nozzle group control governing which is, at present, the prevalent method for practical applica¬ tion. The nozzles are divided into groups under the control of separate valves which operate in sequence. Pure steam flow control without thrott¬ ling losses occurs only when the steam flows through fully open valves. In other ranges, i.e. when the control valves for one or more of the nozzle groups are only partially open, the particular steam flows are always more or less throttled. Generally, additional valves (the overload valves) are installed to make it possible to reach full load even under conditions of somewhat reduced steam pressure. These valves admit steam either to extra nozzles, or, Fig. 18 Nozzle group control governing and throttle governing of steam turbines. With throttle governing, the total steam consumption is controlled by throttling at only one point. This is shown in the lower part of Fig. 18. However, instead of a single common valve, large steam throughputs may require the application of two or more valves in parallel and these would open in sequence. The next sub-sections will deal with the most essential turbine control schemes. To begin with, it will be assumed that only constant pressure units are involved, i.e. that the boilers are controlled so that their outlet steam pressure is kept constant. References: (187] [226] [236] [237] [245] [258] [267] [268] [269] [272] [276] [302] [305] [306] 3 Klefenz r r 5 Turbine Control 34 5. 1Nonreheat Turbine Supplying IsolatedLoad 5.1 Nonreheat Turbine Supplying Isolated Load deviation from the equilibirum state causes a commensurate adjustment of-the turbine control valves. Depending on the relative strength with which the frequency and load signals are brought in, a specific inclined characteristic is obtained. This characteristic is similar to the one that can be obtained in alternative 1 by taking advantage of the setting of the pro¬ portional band of the P controller. As in alternative 1, the characteristic can be shifted by adjusting the set point setter. It is evident that in alter¬ native 2 it is always possible to reach the nominal 50 Hz frequency regard¬ less of the current load. The main features of turbine speed control have already been indicated in Fig. 7 in Chapter 3. Fig. 19 now shows two alternatives in more detail. Alternative 1 is the classical speed control. The difference between the set point and the speed signals forms the input of a proportional controller which in turn actuates the turbine inlet valves. The proportional band of the controller can be kept rather narrow (approximately 2 to 4 Hz) due to the favourable time behaviour of the controlled system. This has the effect that speed, or rather the frequency, does not fluctuate too strongly in dependence on load. Moreover, by adjusting the set point setter it is possible to associate with each load any nominal speed, as is shown in Fig. 9. With the speed controller in operation, integral action is avoided for reasons of stability. This is so because in some caces the controlled systems have no self-regulation. The dynamic performance will now be explained with the aid of the signal flow diagram on Fig. 20. (The diagram has certain peculiarities of presen¬ tation which are dealt with in the opening statement of sub-section 8.3.) The adjustment of the turbine inlet valves, y, causes the turbine drive power Na to adapt with some delay: The transient response curve is that of a 1st order system with a time constant 7) . The difference between the turbine drive power (= power requirement) NA , and the power N which is being delivered by the generator to the consumer, is used to accele rate both the turboset and the connected motors. This occurs in the transition time TA . The power Ntaken up by the consumer is composed of the power requirementJVvo and a frequency dependent feedback Ny. The amplification factor Vv (which is the consumer gain) lies between 0 and 4, its actual numerical value depending on the type of consumer units. For instance, Vy = 0 indicates a speed governed drive (i.e. a genuine ohm's consumer), Vv = 3 .. 4 is typical for pump and fan drives, etc. While alternative 1 was prevalently applied during the period when mechanical/hydraulic governors were used, alternative 2 presents a method that became feasible only through the introduction of electrical governors. In alternative 2, the load signal, the frequency signal, and the set point signal are combined at the input of a proportional-integral controller. A j ÿ --- The frequency dependent consumption of power by specific consumer-ÿ" groups has, to a certain degree, a self-regulating effect. A deficiencyln the power produced lowers the frequency, and also results in lowering the power taken up by consumers. However, this self-regulating effect should not be overestimated. Even if it used to be quite efficacious in the past, it has been recently strongly reduced by the constantly growing parti¬ cipation of speed controlled drives. In a middle sized power supply grid, a gain of Vy = 1 is currently all that can be assumed. -<&*- Alternative 1 - ED n(ÿ) (ÿ>i For large turbosets of 100 MW to 300 MW, the order of magnitude of the delay time constant T) is 0. 15 seconds. As to the transition time TA, it is generally accepted that for its calculation it is sufficient to consider only the turboset. This simplification has the advantage that it deals with the most unfavourable case which arises when the set is working without a consumer; this occurs, for instance, either during the bringing up of the load of the set, or during thesheddingÿof the load\ Alternative 2 Fig. 19 35 Alternatives of speed control in a turbine supplying isolated load. j. I r 5. 1Nonreheat Turbine Supplying Isolated Load 5 Turbine Control 34 5.1 Nonreheat Turbine Supplying Isolated Load 35 deviation from the equilibirum state causes a commensurate adjustment of-the turbine control valves. Depending on the relative strength with which the frequency and load signals are brought in, a specific inclined characteristic is obtained. This characteristic is similar to the one that can be obtained in alternative 1 by taking advantage of the setting of the pro¬ portional band of the P controller. As in alternative 1, the characteristic can be shifted by adjusting the set point setter. It is evident that in alter¬ native 2 it is always possible to reach the nominal 50 Hz frequency regard¬ less of the current load. The main features of turbine speed control have already been indicated in Fig. 7 in Chapter 3. Fig. 19 now shows two alternatives in more detail. Alternative 1 is the classical speed control. The difference between the set point and the speed signals forms the input of a proportional controller which in turn actuates the turbine inlet valves. The proportional band of the controller can be kept rather narrow (approximately 2 to 4 Hz) due to the favourable time behaviour of the controlled system. This has the effect that speed, or rather the frequency, does not fluctuate too strongly in dependence on load. Moreover, by adjusting the set point setter it is possible to associate with each load any nominal speed, as is shown in Fig. 9. With the speed controller in operation, integral action is avoided for reasons of stability. This is so because in some caces the controlled systems have no self-regulation. The dynamic performance will now be explained with the aid of the signal flow diagram on Fig. 20. (The diagram has certain peculiarities of presen¬ tation which are dealt with in the opening statement of sub-section 8.3.) The adjustment of the turbine inlet valves, y, causes the turbine drive power Na to adapt with some delay: The transient response curve is that of a 1st order system with a time constant T\ . The difference between the turbine drive power (= power requirement) NA , and the power N which is being delivered by the generator to the consumer, is used to accele¬ rate both the turboset and the connected motors. This occurs in the transition time TA. The power Ntaken up by the consumer is composed of the power requirement Ny0 and a frequency dependent feedback Ny. The amplification factor Vv (which is the consumer gain) lies between 0 and 4, its actual numerical value depending on the type of consumer units. For instance, Vy =0 indicates a speed governed drive (i.e. a genuine ohm's consumer), Vv = 3 • 4 is typical for pump and fan drives, etc. While alternative 1 was prevalently applied during the period when mechanical/hydraulic governors were used, alternative 2 presents a method that became feasible only through the introduction of electrical governors. In alternative 2, the load signal, the frequency signal, and the set point signal are combined at the input of a proportional-integral controller. A • ---- The frequency dependent consumption of power by specific consumerÿ groups has, to a certain degree, a self-regulating effect. A deficiency in the power produced lowers the frequency, and also results in lowering the power taken up by consumers. However, this self-regulating effect should not be overestimated. Even if it used to be quite efficacious in the past, it has been recently strongly reduced by the constantly growing parti¬ cipation of speed controlled drives. In a middle sized power supply grid, a gain of Vv = 1 >s currently all that can be assumed. -©•*- Alternative 1 <? 0- ;: -0- , ÿ 4 kl For large turbosets of 100 MW to 300 MW, the order of magnitude of the delay time constant 7\ is 0.15 seconds. As to the transition time TA, it is generally accepted that for its calculation it is sufficient to consider only the turboset. This simplification has the advantage that it deals with the most unfavourable case which arises when the set is working without a consumer; this occurs, for instance, either during the bringing up of the load of the set, or during theÿheddirqfof the load\ Alternative 2 Fig. 19 Alternatives of speed control in a turbine supplying isolated load. 3* 1 >Jr 5 Turbine Control 36 nlf) 5.2 Nonreheat Turbine Connected to a Power Grid Fig. 20 Signal flow diagram of a turboset without a reheater, supplying an isolated load. The simplified scheme provides some kind of an answer to the rather diffi¬ cult question of how should be constantly changing number of consumer units be incorporated into the calculations. As in other respects, the theo¬ retical design of the controllers has to be based on the least favourable case, which happens to be represented by the lowest TA. This transition time TA can be obtained from: Since the speed of a turboset connected to a large power supply grid is fixed by the frequency of the system, little emphasis is given to speed control. Instead, its place is taken up by load control. As has been already explained in paragraph 3, in this type of control it is necessary to distin¬ guish between two modes of operation, passive and active. In passive operation (see case 1, Fig. 21) the set supplies a constant load, as adjusted on the set point setter, independently of the frequency of the system. In active operation (see case 2, Fig. 21) the set participates in maintaining the frequency at its nominal value; the load set point is shifted by the frequency according to the appropriate characteristic. In modem plants the response sensitivity of the frequency measuring device is approxi¬ mately 5 mHz, which means that the basic requirement for frequency support is fully met. limit values (entry) Ta = 4tt (3) where I N0 2 1' "0 N0 ÿ r —Eh~ . . mass moment of inertia . . nominal speed . . nominal load H r— © selector ~ device | limiting of speed of change N(' case 1 The order of magnitude of TA is 10 seconds, and the value is only margin¬ ally dependent on the size of the machine. The transfer function of the speed control system then reads: (4) An(s) Ay(s) where set point _ _ i£_ (i + 7VS)-(i+pÿ-s) ' s . . the Laplace operator. limit values I [limiting of speed (entry) ÿi— -ED* —D~ selector device Should the turbine control be investigated together with boiler control, the effect of the various refinements in the above calculation would be minima. This means that in comparison to TA/Vy, Tx could be neglected. What would remain is a 1st order delay system with a time constant [of change . case 2 TJVy. Fig. 21 The alternatives of load control for a turboset connected to a power system. /J m 38 5 Turbine Control 5. 2 Nonreheat Turbine Connected to a Power Grid 39 The control scheme on Fig. 21 contains the following modules: — A speed limiter for the change of load. The load set point itself may be adjusted as quickly as convenient. However, the set point signal must be prevented from changing more rapidly than the plant could cope with. This is why the signal is routed through the limiting module lo¬ cated downstream of the set point setter. In addition, the limiter can receive signals which would block any set point change should at least one of the boundary values be attained. These signals are issued by some superimposed device such as a stress monitor or a unit control station. Tn — Instead of using signals from a set point setter located in the thermal control room, remote set point guidance signals can be used. Such sig¬ nals can originate, for instance, in the central load dispatching centre. — A selector device which is located upstream of the controller can acco¬ modate further limiting signals. Via such a module, limiting signals from steam pressure (before the turbine) or from turbine speed can be brought into the control loop. It is not possible to present the dynamic behaviour of the above control system in a form which would be as simple as that for the isolated load case. The reason for this is that nowadays it is necessary to take into con¬ sideration the slip, system self-regulation, and other factors. The complete signal flow diagram for a set connected to the system is shown on Fig. 22. It differs from the diagram shown on Fig. 20 in that it contains additional restoring torques due to the slip s which is the difference between turbine speed and system frequency. The slip signal acts, in the direction shown, both via the proportional block KD and via the resetting time block TR. In this manner it provides a direct damping moment (via KD ), as well as a which is being fed into the system (via signal equal to the surplus load Tr). The sum of the surplus load Nn and the user load ATV0 + Ny equals the load iVproduced by the generator. In its turn, the surplus load ATN acts via the system gain block KN on system frequency. Strictly speaking, the time lag involved in this action (TN) depends on the kind of consumer devices connected to the system, as well as on the loading of the network. However, since such factors are difficult to evaluate, it is expedient to assume a proportional relationship with no delays. In large generators, the order of magnitude of the damping constant KD is 25. The resetting time TR varies between approximately 1.7 ms at noload operation, and 2 ms at nominal load. The dimensional gain element jKn relating the load A7Vn to the frequency correction Af, depends on Fig. 22 Signal flow diagram of a turboset without a reheater, connected to the power grid. the ratio of the machine load to the frequency of the system load. For a very large power supply grid which is practically stiff, the value Kn = 0 should be used (i.e. load changes cause no frequency changes). In the other extreme case of an isolated load, K equals infinity. After appro¬ priate modifications this leads to the signal flow diagram shown on Fig. 20. In the case of a stiff system the signal flow diagram can be reduced — see the reduced diagram in Fig. 23. A further simplification is possible leading to the simplified diagram in Fig. 23. It is based on the knowledge of the transfer function describing the behaviour of the load Nn following a change of the turbine power requirement NA , which reads: (5) AAfN(.r) aata(s) * y= i+ÿdÿRSÿRÿA1 The insertion of numerical values leads to: (6) 1 - AATA(S) 2 ' 1 + 0,05 s + 0,02 s1 I 5.3 Single-Reheat Turbine 5 Turbine Control 40 T, 41 ÿA IP/LF Fig. 24 reduced diagram simplified diagram Fig. 23 Signal flow diagram of a turboset without a reheater, connected to a stiff power supply grid. If the turbine control is examined together with the essentially more inert boiler control, the above fine points are of minor importance, and it is adequate to represent the controlled system as a simple P element without delay. Principle design of a turbine with reheater. The adjustment of the position y of the nozzle control valve produces almost instantaneously a certain part a of the total operating power A/a in the HP stage of the turbine. The value a is calculated as follows: (7) a= Ah l A/ij A /i2 where A hi is the enthalpy drop in the FIP stage, and A h2 the drop in in the IP/LP stages. In practice, a lies between 7 and j. B 5.3 Single-Reheat Turbine In turbines with reheat the steam leaving the high-pressure stage is once more heated in the so-called reheater (generally to the same temperature as the live steam leaving the boiler) tfaFterwards, it is led to the turbine intermediate-pressure and low-pressure steam valves (seej<ig. 24). The control is performed in the same manner as control for machines without reheating, displayed on Fig. 19 and Fig. 21. Certain peculiarities, such as behaviour at minimum load, will be discussed in the next section. The reheater influences the dynamics of control to a considerable degree. This is because the volume of the reheater acts as a substantial storage, the consequence of which being that the intermediate-pressure and lowpressure stages of the turbine participate in load changes only with a delay. This can be seen from the signal flow diagram on Fig. 25. Fig. 25 Signal flow diagram of a turbine with a reheater, connected to a system. 5.3 Single-Reheat Turbine 5 Turbine Control 42 This means that the motive power produced in the IP/LP stages amounts to (1 — a) of the total production. It is produced with a certain delay given by the fact that before the steam enters the IP/LP stages it must flow through the reheater, i.e. the delay equals the required charging time of the reheater volume. The relevant time constant Tzo is calculated using the relationship: TlZU (8) _- 1+ X I K 2* Fig. 27 43 Simplified signal flow diagram of a turbine with a reheater, connected to a ÿtlThpower supply grid. '"ZU '"ZU As has already been explained, if we wish to re-examine the turbine control where adiabatic coefficient systemiolely in relation to the whole steam generating plant, we can mZ(j reheater steam flow disregard the small time constants, and arrive at simplified signal flow diagrams such as are shown on Figures 26 and 27. The corresponding transfer functions are: mZ\j steam mass stored in reheater For isolated load: For superheated steam k ÿ 1.3, i.e. (10) Tzu 555 0>9 • wzu "!ZU (9) For operation as part of a power grid system: ,yÿr' Tz o equals approximately 15 seconds, which means that it is the dominant Cj j \ time constant. nlfl -B — f vB Simplified signal flow diagram of a turboset with a reheater, supplying an isolated load. ann(i) Ay(s) Finally, the conversion of the (1 - a) share into motive power is effected in the IP/LP stages of the turbine with the time constant T2. The time constant T2 is very small, similarly to the time constant T\ (« 0. 15 s.), and afhounts)to approx. 0.25 seconds. The remaining blocks of the signal flow diagram have already been discussed in sub-section 5.2. Fig. 26 _ mt&.K- _ '"Tz"" l + a • 7z<j l + Tz\] S ÿ * We should remember that already in operation are double-reheat turbines, where the steam is being returned to the boiler from downstream of the intermediate-pressure stage (and not only from downstream of the highpressure stage). After being reheated for the second time, the steam is finally completely expanded in the low pressure stage. The introduction of a second delay disimproves the control conditions even further, and the signal flow diagrams are to be extended'accordingly., It should be pointed out that, in turbines with reheat, control valves are installed also upstream of the intermediate-pressure stage of the turbine. These valves are open when the unit operates with boiler load above minimum. If the-unit load drops below minimum boiler load, the excess steam must be diverted/via high-pressure and low-pressure reducing stations. Under suchconditions, in order to achieve the lowering of power of the IP and LP stages, it is necessary to throttle the steam flow upstream x of the intermediate-pressure stage, while the reheat steam pressure is kept constant by the low-pressure reducing stations. / / _g 5 Turbine Control 44 • 5.4 Accessory Turbine Controls 5.4 Accessory Turbine Controls . I Jl— This section will briefly cpVer some of the turbine controls that are gener¬ ally applied to complementÿthe main control loops. As the first in this group it is the inlet steam pressure governing system that should be mentioned. However, as this particular scheme has already been shown in Fig. 12 as alternative 2, and discussed in the accompanying text, no further details will be given. Its countefparl, the back-pressure control (see Fig. 28) is quite similar but for the controlled variable which in this case is the exhaust steam pressure of the turbine, i.e. the pressure in the plant steam network. The steam consumption in the back-pressure system determines both the turbine steam throughput, and the produced electrical power. Fig. 29 4 (D- When using the bled steam pressure control, both speed control and load control affect the nozzle valves in the opposite direction to the pass-out valves, whereas in the case of 'steam-grid' pressure control both control points are influenced in the same direction. This makes it possible, in the I I I -© A Fig. 28 Basic scheme for bled steam pressure control. !-ÿ Basic scheme of back-pressure control. ? rrrEbf-'-i 'I N(ÿ) fÿ> 11 Among further possibilities is the bled,steam pressure control, and the .? combined steam/power grid control. Figures 29 and 30 show the respecY yctive control diagrams. One of those control loops is required if steam for d c use in the plant is being_withdrawn from discharge (or bleeding)-po«rtsprovided in the turbine casing'. Their application is aimed at preventing the mass flow of the processsteam to pass out through the openings at uncontrolled and variable pressure (which itself is a function of steam flow). In the simpler bled steam pressure control, according to Fig. 29, there are, on the process side, interactions with controls acting on the nozzle valves, such as speed control or load control. These often have an unfavourable effect requiring an undesirably strong damping of one of the control loops. This is the reason for giving preference to the steam-grid type control loop (Fig. 30) which leads to an extensive decoupling. / 9 Fig. 30 P Basic scheme for combined steam/power grid. 45 0..ÿ'" <" 46 / ÿ \***I 5.5 Sliding Pressure Operation 5 Turbine Control latter casefto perform load changes without the bled steam pressure being appreciably affected, and to eliminate pass-out pressure fluctuations without a noticeable effect on load. When using the above methods,th£_dynamics of the controlled system accuracy, from its static 'turbine' can be derive d. with L behaviour. A further kind of supplementary turbine control is the 'import/export power' control. The term stands for control of a specified energy flow between an industrial power plant with its own consumer network, and the general grid. It can, for instance, cover contractual inputs and outputs of electrical power. The control scheme is built similarly to the schemes for the already discussed load controls (see Fig. 21). Therefore, further discussion would be superfluous 47 sufficient Reference: [211] T". 0 " < , .-CUtÿ7 5.5 Sliding Pressure Operation / In recently built plants one can find increasingly more often the so-called sliding pressure operation, when the pressure upstream of the turbine is not kept constant but'varies pmpbrnonaHy'ÿvith load. The main advantage of this mode of operation is that it minimizes temperature variations and thermal stresses in the turbine, which in turn allows_faster load changes without exceeding the turbine capacity to(stfStain fatigue) It is unfortu¬ nate that, on the other hand, the utilization of the steam storage in the boilerjsj5recludecl) so that the already inert steam generator experiences rrther delays during each load change. These are caused by the necessary ' loading and unloading of the storage. The so-called natural sliding pressure operationjsÿcharacterized either by wide open turbine input valves, or by their igbseneeÿLoad changes can be effected only by steam pressure variations. In the simplest case, it is sufficient either t o (re mrftely adjust the firing rate in the boiler (open-loop y) ÿ'" control), or to build a control loop along the lines suggested in Fig. 3 1. This figure also contains the characteristic P = f(rhj) ) which reflects the above conditions, and which is, with good approximation, a straight line. ' The main disadvantage of this approach lies in the fact that the total inertia of the boiler is introduced into the load control loop. This means that demand fluctuations cannot be counteracted quickly enough. Since the Fig. 31 Natural sliding pressure operation. storage capacity of the steam generator is not made use of, the system has no instantaneous reserve available, and an affective support of frequency is not possible. / / / Should fast load changes be required, a compromise between sliding pressure operation would have to be made. In actual operation, the turbine inlet valves would then be temporarily engaged in control (exactly as in constant pressure operation) only to return to the original fully open position when¬ ever steam pressure reaches the new value required by the variable pressure operation. The scheme for this type of pressure control is shown in Fig. 32. Here, the turbine control structure follows the already discussed guide¬ lines. The boiler steam pressure control is executed as constant steam pres¬ sure control but the set point is made variable. The signal changing the steam pressure set point is derived from the steam flow; generally, it is programmed from load demand. The two system elements built into the path of the steam flow signal (one with the inscription PTX , the other with the sign of a characteristic) have the following task: In order to give the turbine valves greater participation in load changes, the turbine inlet valves must have a certain reserve with regard to their opening. Accordingly, in the stationary state the valves are not fully open, but could allow, for in¬ stance, only 90% of full load steam flow (see the diagram on Fig. 32). Even with this partly limited opening if is possible for the pressure to be increased to the maximum value Pmax. In such a situation (i.e. with the pressure remaining constant), a further increase in load would require a wider open¬ ing of the inlet valves. Operations of this kind are marked by a characteristic similar to the one for modified sliding steam pressure, shown in Fig. 32. Naturally, pressure can¬ not be made to drop to zero. Once a fixed minimum value is reached it is held constant, and, from this point on, control is performed by the throttling action of the valves. The steam pressure set point must be made 5 Turbine Control / ÿ F l"D 5.5 Sliding Pressure Operation <|)Ns f-0HEF ,f*Eh j ÿ Pmox Fig. 32 1 & Modified sliding pressure operation. is no throttling. In other words, one must take care that the overload valve (or the last nozzle group) is really closed, the remaining nozzle groups being fully open. Due to such difficulties there are schemes where the open loop control is replaced by closed loop control, with the valve posi¬ tion yj as the control variable. The signal from a PI controller with a wide proportional band and a large integral action time constant, multiplies the pressure set point signal, and continues the correcting action until the desired position for yr is attained. However, from the point of view of automatic control engineering, the pure open loop control solution is pref¬ erable due to fewer interactions. References: [3] [11] [53] [54] [55] [60] [61] [64] [69] [83] [92] [146] [147] [157] [158] [159] [161] [227] [270] [293] 0/rÿ" yV1"1 A ÿ 49 to follow thispressure characteristic exactly. This is done by the element with the respective sign of the characteristic. The system element marked with the letters PTX represents a delay element of the 1st order; its func¬ tion is to prevent the steam pressure set point from following immediately all the changes in the load set point, which possibly could cause serious overfiring. The combustion process is namely affected by a practically permanent presence of a feedforward signal (i.e. auxiliary disturbance signal from the load set point, nqlshown in Fig. 32) which adjusts firing according to load changes. jMoreoyer, it is necessary to fill up the storage w hichliacl~alreaclyTieen drawn upon1during the constant pressure opera¬ tion (signal from steam pressure). Should at this stage appear a signal in¬ stantaneously following the steam flow, firing changes, as already pointed out, would become inadmissibly large. This is the reason for the delayed introduction of the steain pressure set point signal. As already described in the previous paragraph, in order to make the storage capacity of the boiler available for exploitation, it is necessary to provide a certain reserve in the opening of the turbine inlet valves. For this purpose, one of the nozzle groups (usually the last) can be used. Then all the nozzle group valves except one are fully open, with the valve for the reserve being fully closed. An even more frequent method for coping with this problem is to use an overload valve (see also Fig. 18). A specific problem arises if the circuit according to Fig. 32 is used: Here it is necessary to make certain that the open loop control of the pressure set point is realized in such manner that under stationary conditions there 4 Klefenz 6 Unit Master Control Such an arrangement has to disadvantage that during load changes boiler storage is not brought into play; as a result, changes in produced power are almost exclusively determined by the inertia of the boiler. The impor¬ tance of the capability of the boiler to store energy in the form of steam pressure, has already been discussed several times; the fact that it cannot be used to achieve rapid load responses is sufficient reason for not re¬ commending the application of such an arrangement. 6 Unit Master Control /lr The term unit has already been explained in paragraph 2. Unit master control simply signifies a super-imposed load-control system coordinating the operations of the boiler and of the turbine, i.e. a system in which control signals for the regulation of the boiler's firing rate and the posi¬ tioning of the turbine valves are developed simultaneously. This coordina¬ tion is necessary in order to prevent the overloading of one part of the plant. For instance, the turbine cannot take up unlimited load but must take into consideration the inertia of the firing of the steam generator, which determines the follow-up ability of the boiler. Of course, there also must be the possibility of totally decoupling the main plant parts during turbine-alternator disturbances. The individual variants of coordinated control will now be explained on the basis of the diagram on Fig. 33. Case II: Only connections a and d are used. Steam pressure is controlled by adjustments of fuel flow, while changes in the position of the turbine inlet valves control the produced power. This control scheme allows the exploitation of boiler storage, thus facilitating fast load changes. It is therefore a solution that meets the current requirements. However, one feature is still missing. Namely the above mentioned coordination between the turbine and the boiler, which would take into account the interactions between the two parts. ÿ 5ÿ S!> " v Fig. 33 Universal scheme of coordinated unit control. The controller R1 is the steam pressure controller with PI or PID control action. R2 is the fuel controller, built as a PI controller. R3 is the posi¬ tioner (P controller) for the turbine valves. Finally, the controller R4 performs the function of a power output controller, and has, generally, a PI control action. Possible connections between the individual controllers are indicated by dotted lines a, b, c, and d. Case I: Connections b and c are used; this is the classical approach in which the positioning of the turbine valves is controlled by the pressure of the superheated steam, while the power to be supplied to the system (the megawatt output) is determined by control action on the firing rate. 51 t Case III: Connections a, b, and d are used. In addition to the main control loops described under Case II, a coordinating link is provided between these, in the form of connection b. In this case, following a load increase, a signal using the path b will prevent the further opening of turbine valves should steam pressure decrease too much. The opening will be limited regardlesshgj whether the action is initiated by reason of the load change being too fast, by the boiler being prevented from complying with the increased demand due to some disturbance, or by any other reasonTTrT practice, the path b is used when certain construction and process de¬ pendent limits are to be ÿnforcÿtL ÿAsÿexglajned above, a further opening of the turbine valves is prevented, and the valves might even be made to close, if the steam pressure drops below a specified minimum value.) The described arrangement represents a definite improvement over Case II. Case IV: All connections are used. This is the most universal arrangement which permits optimum control of the thermal power unit. The connection c has primarily the task of providing a feedforward signal for the fuel controller, which is fairly standard practice with coordinated control systems. It can, for instance, be used to make the fuel flow change in the required direction immediately following a load change. The path shown in Fig. 33 is therefore to be taken only as a symbolical representation. In reality, the signal c could be a signal from the load set point, from the actual load, or, frequently, from the steam flow, and could include fre¬ vV\ quency trim. 4* \ <0 loeJL 52 - ÿboi 53 6 Unit Master Control 6 Unit Master Control There is an arrangement that almost exactly corresponds to Fig. 33. This is the so-called DEB-Method (Direct Energy Balance Method) which is primarily used in the United States. In DEB the controllers R1 and R4 act jointly and continuously on the controllers R2 and R3, which auto¬ matically brings about coordination within the thermal unit. However, power stations in Continental Europe give preference to arrangements which guarantee the fastest possible load changes under any conditions: The connections a and d are in permanent form, while c is replaced by a load demand pilot signal (disturbance-variable compensation), sometimes trimmed by transient and steady-state corrections, and b acts only as a limiting signal. Such an arrangement is shown in Fig. 34. The feedforward signal, in this case, is the steam flow signal mD which is proportional to the electrical output of the station. The arrangement according to Fig. 34 is naturally valid only for constant pressure operation. A modification according to Fig. 34.1 is necessary if variable pressure operation is to be considered. There are two important additional items to be mentioned. Firstly, since the turbine valves are almost 100% open, it is possible, following a load increase, to achieve at first only such a rise in the steam flow as will correspond to the actual extent of throttling. This would render the proportional feedforward operation inadequate, and the unit would only very slowly reach the new desired output. For this reason the Ciuiwic' ÿ power output set point is used instead of the steam flow, both for the y, feedforward operation and as a command signal for the steam pressure set point. The PTX element (delay of the first order) is again applied for dynamic adaptation. Secondly/as regards the manipulation of the pres¬ /\y sure set point, it is necessary to keep in mind that, for the reasons given above, it is the steam flow that must be the decisive factor under steady state conditions. With this in mind, the steam flow signal and the power output set point signal are compared in a maximum signal selector, where the set point signal is somewhat weakened, so that in steady state the steam flow signal can win through,. . (__ *Dt ÿ £ — © ÿ —| pi -ED~ -d) --- 0-4 ' Fig. 34 Coordinated constant pressure unit control. ÿ The unit load set point in Figures 34 and 34.1 is shown in a simplified manner. In fact, it is executed exactly like the set point in Fig. 21, Alt. 2: Here we have the possibility of introducing various limiting signals, as well as that of remote control by,the load dispatcher. Present unit control tends towards relieving the plant operators of detailed decisions on rates of load change, on maximum and minimum unit loads, etc. The aim is to leave those decisions to a central unit(guidance device which is capable of collecting all the necessary information. 1 I ÿ - ' *V P| mD (ÿ )NS 1 MQ X I 1 H V-EEH ÿ 7)—|—j/J j n? L IpidI 1 1 4* — L. ÿ -@— N Fig. 34.1 Coordinated sliding pressure unit control. 6 Unit Master Control 54 6 Unit Master Control Data to be assembled would concern: A unit manager of this kind is also of considerable value in automatic run-ups and run-downs, since it enables the plant to perform these opera¬ tions with optimum speed. An example of centrally coordinated control is shown on Fig. 35. The unit control computer receives all the necessary information regarding: — availability of feedwater pumps, — number of available coal mills or oil burners, — availability of F.D. and I.D. fans, — state of preheaters, — thermal stress in the turbine, — thermal stress in boiler parts at risk (e.g. heavy-walled headers), — checking orjlimit positions of control valves such as attemperatiort valves. On the basis of all such information the unit guidance computer (boiler/ turbine coordinator) can determine whether the target load can be produced, and, if so, with what gradient can the load be ramped to the new state. -trO— ÿ by-pass controller i— —E]— remote set point computer :: computer unit load margin ordinatoi turbine load margin cnteria T<§h J J i ! 1 fuel flow controller Fig. 35 55 Unit control incorporating a unit coordinator The load can then be automatically guided at optimum speed toward the target value, or that permitted by limiting factors. In the case of an accident, such as a breakdown of an F.D. fan, which would not allow the unit to remain at its current load level, the unit would be automatically run back to the permissible load value, i.e. to a safe level. — steam pressure, — steam pressure set point, — steam flow, — power output, — power set point (local or remote), — frequency, — factor AN/Af (required if frequency supporting operation is to be performed), the state of boiler auxiliaries, regarding — various criteria the state of turbine auxiliaries, various regarding criteria — — boiler load margin, — turbine load margin, etc. The above data is used in calculating control signals for fuel handling equipment, turbine valves, high-pressure by-pass stations, etc., and the information is fed to the respective controllers. The boiler load margin (i.e. the amount by which the load can be quickly changed without en¬ dangering the boiler) is determined from supervision data obtained for the relevant boiler parts. To this effect, stresses are calculated from tem¬ perature measurements on heavy-walled headers; the difference between the calculated and the permissible values is then used to obtain the free margin for a fire or load change. Similarly to the stress calculating in¬ strument for the boiler there is also one for the turbine. The latter device uses the characteristic wall temperatures in the wheel chamber of the high-pressure stage of the turbine, together with the current steam pres¬ sures, for the calculation of the free margin of thermal stress. The calcu¬ lated value is then translated into load margin for the turbine. Instruments of this kind are generally called turbine (or boiler) stress evaluators. Until quite recently, such unit coordinators have been constructed with analogue modules. Lately digital technology in the form of microcomputers has infiltrated power stations, and so the required computing as well as logical combinations and decisions, which constitute a superimposed part 56 6 Unit Master Control of free programming and unit control, will be carried out by a digital computer. References: [3] [7] [14] [26] [30] [33] [56] [76] [83] [90] [92] [146] [147] [189] [191] [192] [195] [209] [210] [212] [217] [228] [233] [242] [248] [260] [262] [267] [268] [269] [271] [292] [298] 7 Control of Boilers on a Busbar The main features of busbar system operation are described in section 2.2. The section also contains comments on the main disadvantages of such systems from the point of view of control. When comparing the busbar system with a single boiler, we find additional control loops unique for parallel boiler operation. The following text will cover some of the most common schemes for load control. To make it simple it will be assumed that only two boilers are participating. This is not a serious limitation since at any time the number can be easily in¬ creased. The objective of load control is to regulate the energy input into the in¬ dividual steam generators so that consumer steam requirements are met. An unequivocal measure of the balance between steam production and consumption (offtake) is the range pressure. Any unbalance causes its deviation from the set point, making this particular parameter the most suitable controlled variable for load control. Z z —'< © Pc ?" I [n] Fig. 36 Load control for busbar system operation. Alternative 1 $ .r.J i ©T <i)i 7 Control of Boilers on a Busbar 7 Control of Boilers on a Busbar Fig. 36 shows a typical variation of range pressure control. The steam pressure deviation signal forms the input to the main controller which has PI or PID action. The controller output signal branches out, and continues becoming the input signal for the fuel controllers of individual boilers. With such a set-up any pressure deviation will change both fuel inputs simultaneously. This would avoid any paralleling difficulties if the boilers were identical and designed to carry an equal load. In practice, however, the proportionate contribution of the boilers varies. The extent to which the individual boilers are affected depends on the setting of the trimming modules or ratio adjusters A that bias the respective signals. In general, it is assumed that the boilers contribute to load changes in the ratio of their maximum steam outputs. However, it is not difficult to imagine that there may be reasons for treating one of the boilers with extra consideration. This would have to be done by manipulating the biasing adjusters, thus making it possible to achieve any desired proportional participation in energy production. If and when adjusting such a bias, it should be remem¬ bered that the loop gain of the total control loop should, as far as possible, remain unchanged. The fact that each adjustment of A changes the gain in the corresponding sub-loop can lead to difficulties, unless specific pre¬ cautions are taken. These precautions consist of balancing the reduction in the share of the total gain in the one sub-loop by an equal increase in the other sub-loop, so as to revert again to optimum conditions. conveyed, the controller receives a (false) signal from the speed measuring device. 58 Two additional set point setters marked T are included in the control diagram on Fig. 36. They provide another means of trimming the output power of the boilers. Such trimming consists in pre-setting the two basic fuel flows, the adjustment affecting the ratio of the boiler loads. One dis¬ advantage of this arrangement is that the accuracy with which the load is distributed between the two boilers depends upon the accuracy with which the energy flows into these boilers are measured. There is no prob¬ lem with oil and gas firing; however, undesirable long-term errors can accumulate in the load distribution when dealing with coal firing where one has to depend on substituted measured quantities, e.g. on the speed of the coal feeder — see Fig. 36. An obvious remedy would be to provide each boiler with a separate steam flow controller, which would eliminate both real and unreal heating value fluctuations. Under the term 'unreal heating value fluctuations' are understood such disturbances as bridging of coal in the bunker. If this does occur the coal feeder continues running, and although no coal is 59 This brings us to the control scheme according to Fig. 37 (Alternative 2). Here each boiler has a steam flow controller with the set point guided by a superimposed steam pressure controller. Proportionate biasing as well as trimming, in the already described form, is likewise possible. Fig. 37 Load control for busbar system operation. Alternative 2 The advantage, in this alternative, of having a load distribution independent of fluctuations of the heating value, is to be viewed in contrast to a very definite disadvantage concerning process dynamics. Let us consider an in¬ creased load demand by the consumers: At first, steam pressure drops below set point, causing the set points of the steam flow controllers to increase. The rise is effected by a change in the output signal of the steam pressure controller. As a consequence, fuel flows increase in accordance with the steam flow set point rise. This is as it should be, but, unfortunate¬ ly, the steam flow control loops behave contrary to expectations. Namely, the increased steam flow, enforced under the above circumstances, manifests itself as an increase of the steam flow signal which, since it is applied to the input of the fuel flow controller with a negative sign, acts 60 7 Control of Boilers on a Busbar 7 Control of Boilers on a Busbar 61 against the output signal of the pressure controller. This means that the increased steam flow will tend to reduce fuel flow. measures, Alternative 1 would have better dynamics than Alternative 2, which is the reason why it should be preferred. Since both effects act against each other, in order to achieve a fast in¬ crease in firing it is necessary to make the influence of the signal from the steam pressure side appropriately more important. The limiting factor here is loop stability, i.e. a too energetic adjustment of the controller is not Finally, another alternative should be discussed, one that is limited to dram boilers. This is Alternative 3, and is presented on Fig. 38. allowed. In contrast to the change in demand, the controllers behave quite diffe¬ rently during disturbances originating in the fuel supply (such as the al¬ ready mentioned bridging of coal). During a reduction of the fuel flow both signals (i.e. the steam pressure and the steam flow signal) act as required; since both steam pressure and steam flow decrease simultane¬ ously, the signals tend to support each other in increasing the fuel flow. It is evident that an attempt should be made to implement some compro¬ mises in the design and the setting of the controllers. Without such extra Fig. 38 Load control for busbar system operation. Alternative 3 Alternative 3 consists of each boiler being equipped with a drum pressure controller, the set point of which is guided by the superimposed range pressure controller. The considerable advantage of such a control arrange¬ ment rests in its very favourable dynamic behaviour. The drum pressure controller and the range pressure controller show the same reaction to all kinds of disturbances, so that real optimization of all the controllers in¬ volved is a distinct possibility. Since each drum pressure controller can be optimized independently, there are advantages even if an inert and a fast boiler have to be used together. (For example, one boiler may be coal fired while another is oil fired). Independent optimization allows faster load changes than were possible in Alternatives 1 and 2. This means, in effect, that the faster boiler can temporarily take over part of the load of the more sluggish one, which in other arrangements is either not possible to the same degree or not possible at all. Certainly, in Alternatives 1 and 2 control must be consistent with the behaviour of the slowest boiler. Unfortunately, Alternative 3 also has its disadvantages, which becomes evident during steady-state operation. If the boilers are not uniformly loaded, the respective load shares shift with load, since there is a quadratic relationship between the rise in drum pressure and load. However, this disadvantage cannot be considered too serious, since, in general, the con¬ trolled boilers carry an evenly distributed load. In any case, the conditions are easier to judge than in the case of mutually biased boilers. References: [3] [83] [92] [127] [187] [194] [243] [275] 8.1 Types of Boilers • 8 Boiler Control Under discussion in this chapter is the control of conventionally fired steam generators. Conventional fuels are understood to include coal (black and brown), oil, and gas (natural gas, blast furnace gas, refinery gas, coke oven gas). Control of nuclear power plants will be dealt with in a separate chapter since the application of nuclear energy as well as its control are based on concepts generally different from those used in conventional power stations. economiser Fig. 39 Circulation Boilers (Drum Boilers) Once-Through Boilers (Forced-Flow Boilers ) Natural Circulation Forced Circulation Benson Boilers Sulzer Boilefs Boilers - (La Mont) Boilers While in the once-through boilers the liquid (water, steam) flows through the boiler in a direct line, in the circulation boilers considerable circulation in the area of the evaporator takes place. References: [187] [188] [217] 8.1.1 Natural Circulation Boilers The most widespread drum boiler is the natural circulation boiler, shown in outline on Fig. 39. superheater r evaporator (riser tubes) 8.1 T ypes of Boilers Since the type of boiler used decisively influences the control scheme to be applied, it is the main steam generator types that will be introduced first. Only such properties as are important for control will be looked into. One basic classification of the boilers is possible in the following manner: 63 Basic scheme of a natural circulation boiler. feedwater pump Here the feedwater pump forces the water through the economiser into the drum. From there it is supplied to the lower furnace wall headers through a system of mostly unheated downcomer tubes. Steam is gener¬ ated as the water rises through the furnace wall riser tubes exposed to heat radiation. The water/steam mixture is then transferred to the boiler drum. The circulation is maintained by the difference in the densities in the downcomers and in the risers, and is evidently caused by gravitation; this is the reason why the boilers are known as natural circulation boilers. Steam is separated from the steam/water mixture in the drum, and leaves the boiler through the superheater section. From the point of view of control technology the drum boiler is charac¬ terised by the following features: — The water level in the drum is an unequivocal measure of the feedwater which must be supplied to the boiler. — The drum strictly separates the evaporator from the superheater areas, this being advantageous from the point of view of the reaction of steam temperature control to disturbances. Changes in the feedwater flow have no effect on steam temperatures. The storage capacity which depends on the content of the drum as well as of the recirculation tubes, is relatively large, so that during load changes the inertia of firing can be successfully counteracted. — In general, since the drum keeps the evaporation end point locally fixed, the live steam temperature cannot be maintained at set point if the load drops below 40 to 50% of maximum rating. Reference: [194] — 8 Boiler Control 64 8.1 Types of Boilers 65 8.1.2 Forced Circulation Boilers In a natural circulation boiler the flow through the evaporator part is maintained by the difference between the specific gravity of the water in the downcomers, and that of the water/ steam mixture in the risers. On the other hand, in forced circulation boilers the natural circulation is sup¬ ported by a circulation pump (see Fig. 40). This boiler type is also known by the name of the LaMont boiler. The advantage of these boilers is that the circulation is guaranteed also under relatively high pressures when the density of water closely approaches that of saturated steam. From the control engineering point of view there are no apparent differences bet¬ ween the LaMont and the natural circulation boiler, which means that the points mentioned in section 8. 1.1 are also fully valid for the forced circulation drum boilers. r superheater ÿ evaporator r economiser ) feedwater pump Fig. 41 Basic scheme of a Benson boiler Reference: f2 17] superheater evaporator J circulation pump i • economiser (T) feedwater pump Fig. 40 8.1.3 Basic scheme of a forced circulation boiler. Benson Boilers Benson boilers are a sub-group of the forced-flow (once-through) boilers. The basic scheme is shown on Fig. 41. Here the liquid is being forced without any detour straight through the economiser, evaporator, and superheater. The control enigneering consequences are as follows: — The maintenance of the correct relationship between the feedwater supply and the heat supply is problematic in that we do not have an unequivocal indicator of how the required feedwater supply is met. The evaporation boundaries are not fixed. They shift with load and with any imbalance between firing rate and feedwater flow. The re¬ sulting increases and decreases of the heat accumulated in the eva¬ porator section of the boiler, accompanied by fluctuations of the heating surface area, cause disturbances in steam temperature control. The shifting of the initial and of the end points of evaporation is out¬ lined in Fig. 42 which illustrates the theoretical case of uniform heating and uniform flow in the pipework. A load increase to full load (Case d) moves the starting point and the end point of evaporation away from the point of entry to the boiler, and reduces the length of the evaporator section. The increase of steam pressure, which in turn increases boiling temperature, makes it necessary to extend the pre-heating zone. Further, higher pressure reduces the latent heat, thus bringing about the shorte¬ ning of the evaporator. These are general rules from which, however, there appear in practice many more or less serious deviations, usually associated with the variations in the construction of the combustion chamber. The amount and distribution of the steam admitted to the pipes as well as the state of the fire which may change with load, have a decisive influence on the process in the evaporation zone, and, there¬ fore, also on the dynamic behaviour of the evaporator. — The storage capacity is considerably smaller than it is in dram boilers (approximately j to -|), thus making steam pressure control more demanding. 5 Klefenz 8.1 Types of Boilers 8 Boiler Control 66 67 economiser j evaporator ; superheater U-L, --j superheater w////////ÿ/Mm° o°n° A30 W/MssA I <> J L2 I H - t3<t. - -> - 01 evaporator * l4< t, water separator ('bottle') | U-L<—Ai Fig. 42 Schematic representation of the processes in the evaporator of a Benson boiler. economiser a) Division between the economises evaporator, and superheater at partial load. b) Changed division following an increase in feedwater flow; Starting point partial load a). c) Changed division following an increase in fire power; Starting point partial load a). d) Changed division following a transition to full load. — Due to the fact that the size of the heating surface can be varied de¬ pending on boiler load, it is possible to reach the full load steam tem¬ perature even at partial loads. All that is necessary is that care be taken to ensure a sufficient increase in the superheater heating surface, and that can be achieved by appropriately raising the feedwater flow. — Benson boilers can operate with practically any steam pressure, since no circulation difficulties can occur. Supercritical pressure operation (P> 221.2 bar) is likewise possible. For the control engineer, super¬ critical operation causes no specific problems, and control can be de¬ signed along the same lines as for subcritical boilers. Further, the al¬ ready mentioned variable pressure control is possible with a Benson boiler. - feedwater pump i Fig. 43 Basic scheme of a Sulzer boiler. structural feature is that in contrast to the Benson boiler the economiser and evaporator pipes run continuously between the entry and the exit points without interposed headers. This results in there being only one input and one output header. As re¬ gards control, this feature is, however, of secondary importance in com¬ parison to the water separator which exercises a decisive influence on the dynamic behaviour of the whole boiler, in addition to its original task of salt separation. In connection with this it should be noted that the socalled bottle which is currently more frequently found in Benson boilers, does by no means perform the same function as the Sulzer water separator. The Benson separator functions, as will be subsequently explained, only during start-ups and low-load operation. In normal operation it is either dry (i.e. slightly superheated) or wet. The control of a Sulzer boiler is characterised as follows: 8.1.4 Sulzer Boilers — The level in the separator, or the moisture at the outlet of the separator, are, similarly to the level in a drum boiler, an unequivocal measure of the balance between the feedwater flow and the firing power. This makes feedwater control in a Sulzer boiler simpler to manage than in a Benson The Sulzer boiler (or the Sulzer monotube steam generator) is another forced circulation boiler. It differs from the Benson boiler in that a separator is interposed between the evaporator and the superheater (see Fig. 43). This separator is often referred to as 'the bottle'. A further — The separator localizes the evaporation end point. Since the shifting of this point is no longer possible, the disturbing interaction with the superheater, and, in particular, with the superheater temperature, becomes irrelevant. References: [197] [261] [3201 boiler. 5* 68 8 Boiler Control 8.2 Control Loops 69 — The storage capacity is somewhat larger than in a Benson boiler. — Since, as in a drum boiler, the superheater heating surface does not change with load, problems arise, from the static point of view, with the main steam temperature control at low loads. References: [11] [63] [199] [213] [214] [230] [259] [287] [288] [289] 8.2 Control Loops The detailed discussion of the individual control loops will be preceded by a short introduction giving a review of the main control loops in the various boiler types. The four main control loops in a dram boiler are shown on Fig. 44. The main steam pressure controller, also known as the firing controller, is marked as Rl. The deviations of the main steam pressure from the set point cause the controller to increase or decrease the fuel flow in parallel with the accompanying combustion air flow. This affects the evaporation rate which, in turn, restores the steam pressure to its set point value. R2 denotes the furnace pressure controller, also called the furnace draught controller. The task of this loop is to keep a certain draught in the furnace, in order to prevent leakage of the flue gases into the boiler house, through the not completely impervious boiler walls. Deviations from the set point lead to a corresponding increase or decrease of the rate of re¬ moval of the flue gas. In Fig. 44 the controller maintains the draught by acting on the control vanes of the I.D. fan that transports the gases from the boiler to the stack. With increasing frequency boiler walls are found becoming seal welded (this leads to the so-called membrane walls) so that firing operation can be carried out at positive pressure. In such cases draught control can na¬ turally be expended with. The controllers Rl and R2 are sometimes considered together under the collective name of 'external control'. This is in contrast to 'internal control' which is particularly concerned with the control of fluids, i.e. with processes within the boiler pipes and tubes. Accordingly, internal control includes the temperature and the feedwater controllers. R3 symbolizes the main steam temperature controller. In the diagram it is assumed that temperature is controlled by injecting feedwater Fig. 44 Main control loops of a drum boiler into the steam (spray type cooling, attemperation), such method being most frequently used. In large boilers several such control loops are in¬ stalled in series. The fourth main control loop in a dram boiler is the drum water level control (R4), also called feedwater control. Following a de¬ viation of the drum level from the set point, the feedwater flow into the boiler is more or less throttled. For this purpose it is possible to use either the feedwater control valve (as, for instance, in Fig. 44), or the feedwater pump, or both methods combined. Since there is no difference between the control of a natural circulation boiler and a forced circulation boiler, forced circulation boilers need not be dealt with separately. Next in line for discussion are the main control loops of a Benson boiler (see Fig. 45). The external control is the same as is the corresponding control in the drum boiler which has been discussed in reference to Fig. 44. Rl is again the main steam pressure controller, and R2 the furnace 70 8 Boiler Control I z -- 3; Fig. 45 'a-o- 1 Main control loops of a Benson boiler. draught controller. With regard to internal control, the main steam tem¬ perature controller R3 is also applied in the same manner as it would be in a dmm boiler. On the other hand, the concept of feedwater control is, out of necessity, different. One must remember that there is no water level signal: Here lies the real difficulty of Benson boiler control. The feedwater supply must be controlled so that the disturbances of the fire/ water equijibrium in the boiler are minimal, and that the attemperator water flows stay within the control range at all times. The last requirement represents a very important boundary condition that must be met. As has already been explained, it is possible to arbitrarily shift the evaporation end point (and thereby also the superheater heating surface) by a change in the feedwater flow. 8.2 Control Loops 71 This might lead to widely differing requirements on the attemperation water flows if the main steam temperature is to be kept at the set point even when the feedwater flow changes. On the other hand, it is evident that the above effect can be put to use for maintaining the attemperation water flows within the required control range by an adjustment of the feedwater flow. The problem of keeping the attemperation flows within range has many solutions the one shown in Fig. 45 represents the most frequently used approach. R4 is a flow rate controller for feedwater flow, which receives a feedforward set point signal from the steam flow. However, the steam flow signal does not combine with the feedwater flow signal in a 1:1 ratio, but is somewhat weakened by the ratio adjuster A. The effect of this is that the feedwater flow entering the evaporator is always slightly less than the main steam flow at the outlet of the boiler. This imbalance must be made good by the attemperation water flow supplied to the boiler. Such a mode of control can be considered as attemperation-water-flow/feedwater-flow ratio control, even though the controlled variable is not measured. Here the ratio of the attemperation water flow to the feedwater flow repleaces what would otherwise be the drum level which with Benson boilers is non-existent. The reheated steam temperature control loop which can be found in practically all large units, is generally regarded to be the fifth main control loop. From the many possible variants the one chosen for Fig. 45 is based on the presence of a heat exchanger between the high pressure stage and the intermediate pressure stage. High pressure steam gives off part of its heat to the intermediate pressure steam. This transfer of heat can be varied for control purposes using a by¬ pass duct equipped with a control valve, and installed on the high pres¬ sure side. Should the reheated steam temperature deviate from the set point, the controller R5 would change the opening of the by-pass valve. The main control loops of a Sulzer boiler are shown on Fig. 46. The ex¬ ternal control (controllers R1 and R2) corresponds to the external controls of a drum boiler or of a Benson boiler, and therefore need not be discussed further. Likewise, the main steam temperature control system (R3) is conceived according to the principles already described. Because of the presence of the water separator, located at the outlet of the subcritical evaporator, the feedwater controller (R4) is necessarily diffe¬ rent from its counterpart in the Benson boiler. The fact that the separator 8 Boiler Control 72 i Fig. 46 Main control loops of a Sulzer monotube boiler. fixes the evaporation end point, would make the steam moisture upstream of the evaporator a suitable variable for determining the actual feedwater flow that has to be provided. Unfortunately, no measuring method for steam moisture is available for practical application, and replacement variables have to be found. One possibility is to control the level in the separator, simultaneously ensuring that the mass of deposits blown down from the separator is proportional to load. This is due to the following relationship: (12) mA 1-X = >"D + mA j + JUD mA where X = steam content 1 - X = moisture rh\ m.j) = blow-down water flow = steam flow from the separator into the super¬ heater 8.2 Control Loops 73 If rhÿ/mA is held constant, then the moisture (1 — x) is also constant. It is evident that this can be achieved only through the cooperation of con¬ trollers R4 and R6. Controller R4 controls the water level by changing the feedwater flow, with the set point varying as function of load. The purely proportional controller R6 then regulates the blow-down making it proportional to the load dependent level. The valve characteristic is so designed that the blow-down flow is proportional to the valve position. The controller R5 is the reheat steam temperature controller. From the various possibilities of controlling the reheat steam temperature, the variant chosen for Fig. 46 is one which is often found in Sulzer boilers, and which uses the so-called Triflux heat exchanger together with water injection into the high pressure zone. With this method the reheat steam is directed through a heat exchanger where it exchanges heat with high pressure steam. Further, the heat exchanger itself is heated by flue gas. This three- flow heat exchanger (the Triflux) is basically a system of concentric tubes with high pressure steam flowing on the inside, and the reheat steam in the shell. The heat absorption by reheat steam, as well as its heat release, can be adjusted by injecting feedwater into the high pres¬ sure steam upstream of the Triflux. This whole process is controlled by controller R5 which ensures that steam temperature at the reheater outlet is kept constant. Following this summary of the most important control loops, the ensuing sections will deal in more detail with the variations of these loops. References: [3] [18] [37] [83] [92] [188] [191] [196] [204] [206] [215] [216] [217] [244] [266] [273] [274] [295] [297] [314] 8.2. 1Live Steam Pressure Control Loop 8 Boiler Control 74 75 8.2.1 Live Steam Pressure Control Loop As can be gathered from the prece«ding comments, steam pressure control does not depend on the boiler type, and therefore can be dealt with in a general manner. The control variable is the thermal energy released in the burning process, and this energy is determined by the fuel flow and the matching combustion air flow. Only the control of fuel flow will be dealt with in this sub-section; air flow control will be treated separately in the next sub-section (8.2.2). Due to the use of various fuels as well as due to the divers furnace constructions, there are naturally many variations of control; from these only the most typical will be dealt with. First in line are the oil fired boilers. Their control scheme is presented on Fig. 47. It shows a cascade control loop with a PID steam pressure controller super¬ imposed on a fuel flow controller. Here the main disturbance is the steam flow leaving the boiler, mD . A feedforward compensation seems indi¬ cated, with the steam flow signal acting as the disturbance variable. Ge¬ nerally this signal acts proportionally on the fuel flow controller. Should more than one oil control valve be needed — and there is the possibility of having a separate valve for each burner level — it would be advanta¬ geous to use a superimposed total-oil-flow controller in addition to the individual flow controllers. This way changes in the number of operating burner groups would have only a limited effect on the rest of boiler controls. The controls for gas and for pulverized coal firing are structured along very similar lines. Fig. 48 shows a scheme for pulverized coal firing using a direct firing system where coal and air pass directly from the mill to the to »- air flow control Fig. 47 Control scheme for oil firing. air flow control Fig. 48 Control scheme for pulverized coal firing. burners, and the desired firing rate is a function of the rate of pulveri¬ zation. Only two mills are shown, but should more mills be needed, the scheme could be accordingly extended. The output signal of a PID steam pressure controller, combined with a steam flow feedforward signal, pro¬ vides the set point for a cascaded PI main speed controller. The output of this master controller is fed to as many parallel P controllers as there are mills. The P controllers adjust the positioning levers of the torque variators which serve as variable speed gears for controlling the rate of feed (mostly PIV-gears). The speed of the coal feeders is assumed to be a measure of the coal flow into the boiler. Unfortunately, this signal does not reflect the disturbances caused by variations in the heating value of coal, nor those caused by in¬ terruptions of the coal flow such as might occur following the bridging of coal in the bunker. \ 76 8 Boiler Control ÿj1 8.2.1 Live Steam Pressure Control Loop p ÿ—© to combustion air control to combustion *"air control I to combustion air control (oil firing) £n (coal firing) to further mills The superimposed master pressure controller with steam flow (rhÿ) feed¬ forward compensation, provides the demand .signal for the cascaded total fuel flow controller. The output of the latter controller is led in parallel to two P controllers which in turn act on the oil control valve and on the feeder control gear. In the method outlined by the diagram both fuels are burned in parallel, i.e. each load change causes an adjustment of both oil and coal flows. Another possibility is to bum fuels in sequence: For in¬ stance, for low loads only coal and no oil is burned. Oil gets to be used only when the capacity of the coal mills is fully exhausted ; then it con¬ tinues to support firing until full load is reached. This sequential burning of the fuels can be achieved by providing a negative bias acting on the set point of the oil flow controller (in the scheme it is marked by dotted lines). Such a negative signal keeps the oil control valve shut or just barely open, until a time when the fuel flow controller output signal rises above the negative bias, and the oil flow controller receives a positive signal to open. The problems of automatic burner management, and namely of keeping a minimum oil flow for the burners in operation, have been omitted from the scheme for the sake of clarity. mD Fig. 49 Control scheme for firing mixed fuels (coal and oil). PID Before such disturbances can be corrected, they must first become effective as changes in steam pressure. Unfortunately, in practice there is still no applicable coal flow measurement that would allow for an auxiliary coal flow controller to deal with this situation. Another disturbance-variable in steam pressure control is, of course, the main steam flow. To deal with it, a signal corresponding to the steam flow is applied as a feedforward signal at the input of the coal feeder speed controller. In this manner, as a result of steam flow changes, these con¬ trollers receive signals which give them an impetus in the right direction before any changes in steam pressure are detected. The next example (Fig. 49) deals with firing mixed fuels. Here coal and oil can be burned, either without preference, or in a specified order. The build up of the diagram is in principle the same as that of the previously discussed schemes. 77 Mm to combustion air control-* — (oil firing) Fig. 50 1 combustion *air control f (gas firing) I Control scheme for firing mixed fuels (preferentially gas and oil). 8 Boiler Control 8.2. 1Live Steam Pressure Control Loop If there are several separately controlled oil burner levels it is advisable to replace the master fuel controller (common to both fuels) by two parallel controllers, one for the total oil flow, and one for the sum of the feeder speeds. This would have the advantage that all disturbances on the oil side, such as taking a burner out of service, etc., would be corrected by the oil firing alone, and would have no effect on the coal side. A corres¬ ponding consideration naturally applies to coal control. results in the output signal from the gas pressure controller becoming stronger than the one from the steam pressure controller. Consequently, a minimum signal selector blocks the former signal, and only the latter signal is switched through. Further increase in gas pressure has no effect on the gas flow which is kept at a value corresponding to boiler load. 78 burn It occurs quite frequently that one fuel is given priority in order to waste of burning the be would case typical A available. as much of it as is and utilized profitably be should which gas furnace gases, such as blast control not just flared to atmosphere. But here the main problem for boiler smooth A possible strongly fluctuate. may available is that the amount transition from one fuel to the other is therefore particularly important, if the disturbances of steam production are to be avoided. One possible solution to this problem can be that suggested by Fig. 50. If we start with the assumption that no gas is available, the result would be the activation of steam pressure control on the oil side in the manner already described in connection with Fig. 47. Here a low limit is provided to guarantee a minimum oil flow under any circumstances. This is particularly important, because an extinction of the oil flame in conditions where there is plenty of gas must be prevented at all cost. Upon the start of the gas flow, the gas pressure PG will rise and the gas pressure controller act via a minimum selector on the gas flow controller. The other signal to the selector comes from the steam pressure controller and corresponds to boiler load; it must at the beginning be stronger than the signal coming from the gas pressure controller, which starts from zero. Thus the gas pressure controller keeps increasing the set point of the gas flow controller as long as the gas flow into the furnace is below that available. This meets the requirement that the total amount of gas be burned in preference to oil. The oil flow is gradually reduced in proportion to the increasing gas flow. To by-pass the need of reducing the oil flow via the steam pressure control system, the oil flow controller receives a signal directly from the gas flow. As regards the respective polarities, the command signal for the oil flow controller is diminished by the amount representing the gas flow, thus reducing the oil flow itself. In this manner, any change in the gas flow is immediately corrected by the oil flow, without the steam pressure control loop being brought in. If the gas supply exceeds the demand determined by the boiler load, the following happens: Oil flow is reduced to the pre-set minimum value. This 79 In Fig. 50, a further set point signal having a negative sign is added to the input of the gas flow controller. The reason for this is primarily as follows: By definition, the signal provided by the superimposed controller corre¬ sponds to boiler load. It follows therefore that as long as there is enough gas, the signal is equal to the gas flow from which the constant basic oil flow value has been subtracted. As a result, the above negative set point signal (or, rather, the negative fixed command signal) corresponds to the minimum oil flow signal pre-set on the already mentioned minimum limiter. In conclusion one more common scheme for firing mixed fuels will be dis¬ cussed. This one is particularly suitable for plants having a common primary air control, and where two kinds of fuel are burned without pre¬ ference. In the schemes that have been discussed so far it was assumed that the combustion air is controllable for each fuel separately. However, furnaces exist where air is brought to the oil and natural gas burners from a common wind box. The burners are so adjusted that each receives the same air flow. This demands a control scheme like that on Fig. 51. The command signal generated by the superimposed master control (PID steam pressure controller plus proportional feedforward steam flow com¬ pensation) is again equal to the total fuel flow demand. It is simultane¬ ously used in parallel as the command variable for the total combustion air flow. The actual command signal for the oil flow controller is obtained by multiplying the fuel flow demand signal by the ratio Zq/Z, where Zq is the number of oil burners actually in operation, and Z is the total number of installed oil and gas burners. The actual command signal for the gas burners is produced by a corre¬ sponding method which uses multiplication by ZG/Z instead of by Zq/Z (Zg being the number of gas burners in operation). In this manner, the boiler load is divided between the two kinds of fuels in the ratio of the numbers of operating oil/gas burners. A change in this ratio can be effected only through a modification of the term Zq/Zg . All the burners are inevitably proportionally loaded. Should a burner be put in or taken out of service, the appropriate correction does not depend on the action of 80 8.2.1 Live Steam Pressure Control Loop 8 Boiler Control 81 control. Fig. 52 shows a variant with a correction of the fuel flow control, while a correction of the air flow control will be mentioned in sub-section 8.2.2. •+*mo <d~4 E»J jr_ zf-ÿ \ to combustion ÿair control — z# i»] to the blade-type regulating t damper-controller cyclone 2 :oil r natural gas Fig. 5 1 Control scheme for firing mixed fuels (common air). the steam pressure control loop, but is immediately provided by the fast action of the fuel flow control loop. This is so because the multiplication factors Zq/Z and Zq/Z in the feedforward signals change immediately following any burner switching (either in or out). For example, with five oil and five gas burners in operation, the relevant amounts are 100% oil flow, and jq • 100% gas flow. Following the removal of one oil burner, the feedforward signals change to • 100% oil flow and • 100% gas flow, the share of the lost burner being proportionately covered by all of the remaining burners. cyclone 1 ÿ The final example will deal with the control of coal firing in cyclonefurnaces. Here the circumstances are slightly different from those already described for pulverised coal firing (see Fig. 48) in that on multi-cyclone installations it is particularly important to maintain correct conditions in each cyclone-furnace. The combustion process as well as the melting of ash to slag react very sensitively to any deviations from optimum excess air, making a continuous oxygen correction a necessity. The automatic 02 correction can intervene both in fuel flow control and in air flow Fig. 52 Control scheme of a cyclone furnace. The command signal from the superimposed master steam pressure control¬ ler is led, after having been divided, to the coal flow controllers of the two cyclones. The oxygen content is measured downstream of each cyclone, and the corresponding signal is connected to the input of the 02-correction controller. The resulting correcting signal then multiplies the command signal to the coal flow controller, thus varying the ratio between the com¬ bustion air flow and the coal flow. Should the quality of the burned coal change, the fuel/air ratio is, after one correction, optimal for all load ranges. 6 Klefenz 82 8 Boiler Control 8.2.2 A ir Flow Control Loop The reason why a correction using a multiplier is preferred to one using an adder is that the latter requires certain action at each load change even with an unchanging quality of coal. References: [3] [7] [18] [83] [92] [103] [189] [201] [217] [220] [233] [235] [241] [257] [263] [273] [278] [289] [298] [304] [315] [319] The control scheme for a travelling grate stoker will be discussed in sub¬ section 8.2.2. Since in this kind of control the action of the steam pres¬ sure controller starts with combustion air, the topic appropriately falls under the title of air flow control. The reason for adjusting combustion air flow prior to fuel flow can be found in the improved dynamics of the process. In contrast to an increased grate speed, an increased supply of air (in ratio to the coal supply on the travelling grate) is followed imme¬ diately by an increased heat flow, so that steam production is quick to change. The sub-section will be concluded by a few basic comments on the con¬ troller parameters. In this respect, one has to distinguish between constant pressure plants and variable pressure plants. In constant pressure plants the adjustment is unequivocal to the extent that the control parameters (proportional band, integral action time, derivative action time) can re¬ main constant independently of boiler load. The optimum proportional band strongly depends on the storage capacity of the boiler, but since with constant pressure operation the capacity remains practically constant, the proportional band can also be kept unchanged over the full load range. As to the integral action time, although it might be advisable to effect a re-optimization after each load change the optimum is found to be so flat that continuous adjustments of the integral time constant are not only not critical, but appear quite superfluous. In controlled variable-pressure plants, however, conditions are quite different. In these plants storage is strongly dependent on load, and this means that the proportional band of the steam pressure controller should not be kept constant. Its adjustment is effected by the so-called open loop adaptive control where the feedforward signal is generally derived from the steam flow signal or some other load proportional signal. Whether the storage capacity increases or decreases with load depends on the design of the boiler. Whatever the case may be, the proportional band must be adjusted in proportion to the reverse value of the boiler storage capacity, i.e. it should decrease with an increase in the storage, and vice versa. As to the integral action time, the setting may be left constant over the full load range as in constant pressure operation. Experiments with the derivative action time have shown that the derivative action can remain independent on load without substantially deviating from optimum. 8.2.2 83 Air Flow Control Loop There are many types of air flow control loops, this multiplicity being necessary due to the different modes of firing, to'"divers arrangements of the burners, as well as to the various possibilities of air duct location and distribution. As a result, only the most typical arrangements can be dis¬ cussed in the following text. However, the examples chosen here can be easily used, with but minor modifications, to match practically all current conditions. The combustion air flow controls which correspond to the fuel controls covered in sub-section 8.2.1 will be discussed first. Fig. 47 shows a control scheme for oil firing. The corresponding air flow control scheme is represented on Fig. 53. The command signal for the oil flow controller, which is the output signal of the steam pressure controller, serves simultaneously as the command signal for the air flow controller. Such an arrangement has the advantage that both oil and air flows are corrected in parallel, this being the unconditional requirement for optimum firing with a possibly constant minimum 02 content in flue gas. This control concept should always be striven for. If its implementation proves difficult, as in the case of separate control of individual burner levels, then various feedforward signals at the input of the air flow controller should be used in an attempt to achieve the best possible synchronization. In Fig. 53, the ratio adjuster A maintains the correct ratio of oil flow to air flow. Marked by a dotted line is a frequently needed fixed command signal which causes a shift in the characteristic to ensure that air flow would not drop below the minimum level even when oil flow ceases (Fig. 54). It is often claimed that if a near-stoichiometric combustion is to be achieved, an automatic correction from the 02 content in flue gas or from smoke density offers a substantial advantage. However, such statements should be qualified as follows: It is essential for each individual burner to operate under optimum combustion conditions if optimum operation of the steam generator is to be attained. It is a proven fact that unburned fuel particles from one burner are not normally burned by other burners. 6* Cesser"T etescÿi" 84 L el./ ' "b "b f"J ' 5 Boiler Control 8.2.2 Air Flow Control Loop from steam pressure controller to oil controller s - i ! $ -V 4*- Or Fig. 53 Control scheme for combustion air in oil firing. This means that each burner should be adjusted individually, thus ensuring a correct oil/air ratio, a satisfactory atomisation, the simultaneous arrival of fuel and combustion air at the burner tip (which is dynamically im¬ portant), and the fulfilment of all other necessary conditions. longer optimal. The 02 trim is able to optimize the operation only when the combustion process is satisfactory on all burners, and when the sam¬ pling point is so located that the sample is fully representative for the whole area and over the whole loa4 range. Due to the flue gas stratifica¬ tion and to the danger of tratrip ait ih-leakage, this remains a difficult problem to solve. From the point of view of process dynamics, it must be acknowledged that the introduction of the new zirconium probes has at least considerably shortened the time span between the change in the air flow and the generation of the corresponding signal in the 02 meter, i.e. improved the time behaviour of the loop. While formerly delay times of 20—30 seconds were not rare, nowadays only the flue gas distance/ velocity lag and the measuring time constant of 1—3 seconds are to be taken into consideration. In spite of this improvement the 02 controller cannot be set for particularly fast action, since it is only a superimposed trimming device. This means that it cannot be very helpful during fast load changes where the only important aspect is the quality of the dynamic synchronisation of the oil flow and the air flow controllers, i.e. continuous maintenance of the proper ratio when the oil flow and the corresponding air flow reach the burner tips, which may prove rather difficult. To sum up, it can be stated that in oil firing an 02 controller presents but few advantages. It can prove useful in steady state operation providing all burners are in good working order and the 02 measurement is truely representative. However, for 02 control during load changes it is of little consequence. Similar considerations apply to trimming based on a smoke density signal. Due to the many disadvantages, expenditure on the provision of a smoke meter would be difficult to justify. air flow oil flow Fig. 54 85 Characteristic air-flow/oil-flow. It should be possible to evaluate the effectiveness of automatic oxygen correction (trimming) on the basis of the following considerations: If, for example, one burner fails to operate satisfactorily due to insufficient atomisation, the 02 meter will establish that there is a deviation from set point, and the 02 controller will attempt to correct the error. However, such an action would not be proper with regard to the remaining burners which, although in perfect order, would receive an air flow which is no The structure of combustion air control with an automatic 02 correction is shown on Fig. 55. The signal from the 02 meter (or from the smoke density meter) is compared with the set point, and the deviation is brought to the input of a PI controller. The output signal from this controller acts via a multiplier on the feedforward command signal to the air flow con¬ troller. This is basically equivalent to making the action of the adjuster A in Fig. 53 automatic. In practice, it is expedient to severely limit the in¬ fluence of this correction to some 10—15%, in order to avoid excessively large and possibly false interventions following disturbances in the 02 correction channel. Very low excess air firing as occurs with oil and gas, runs the increased risk of air deficiency following control actions caused by load changes or dis- 86 8.2.2 Air Flow Control Loop 8 Boiler Control from steam pressure controller I to oil ÿ controller or smoke density Fig. 55 Control scheme for combustion air in oil firing, with Oj correction. turbances of air supply. To offset this the safety oriented scheme according to Fig. 55.1 has proved commendable. Here the command signal from the master steam pressure controller is sent to the fuel flow and air flow controllers in parallel. The minimum and maximum selectors then ensure that no air deficiency occurs: The minimum selector upstream of the fuel flow controller compares the signal from the steam pressure controller with the air flow signal, and applies the lower one as the command variable for the fuel flow controller. On the air side, the command signal is compared with the fuel flow signal in a maximum selector, and the higher signal is let through. In this manner it is established that enough combus¬ tion air is available at all times. Should some disturbance on the air side cause the air flow to the burners to diminish, then the minimum selector would immediately cut down the fuel flow to an acceptable level. On the other hand, should some disturbance cause an increase of the fuel flow, the maximum selector would likewise increase the air flow. This kind of scheme calls for the addition of an auxiliary signal to the air flow signal in order to adjust the amount of excess air and effect the desired 02 cor¬ rection whenever the need arises (see Fig. 55.1). Next in line for discussion is the combustion air flow control when in¬ corporated into a pulverised-coal direct-firing system (see Fig. 56). The corresponding fuel flow control scheme as shown on Fig. 48 is particularly suitable for the rather inert firing systems, such as are currently used in brown coal and lignite fired plants, where frequent firing disturbances 87 occur. With coal firing, it is not possible to use the same command signal for both fuel and air flow (in the manner suggested with oil firing), be¬ cause the feeder speed does not represent a true measure of the heat in¬ put into the combustion chamber. A reasonable substitute air flow com¬ mand signal can be devised if the following points are considered: Un¬ doubtedly, in steady state, the steam flow leaving the boiler provides an adequate alternative for the required combustion air flow command signal, since it is proportional to the heat input into the boiler. Unfortuna¬ tely, in transient states, the situation is not so simple. The steam flow that is withdrawn from the boiler fully corresponds neither to the amount of the actually produced steam, nor to the pulverised coal flow directly entering the furnace. The first discrepancy is due to changes in the accu¬ mulation of mass and energy in the boiler, while the second may possibly be caused by the overriding influence of the steam pressure controller. from steam pressure controller ~l jJL |Mox 1 O2 correction_ jTT ÿ dÿJ!@ r/n a ' Fig. 55.1 Control scheme for oil firing. The considerations should further include the already mentioned need for a technologically justified extra amount of excess air at low loads. Finally, the effect of the fluctuating feedwater temperature ds (for instance, following a feed-heater outage) should be also taken into account. (The two latter points will be again omitted from further discussions for reasons of simplification.) 88 -- 8 Boiler Control £jl f — pressure controller j —j> I [7] J — to steam 1 I—-H I [ÿ] | v[ÿl] j" hf -t-L-4j <2ÿÿ !| k feedwater temperature for feedwater temperature changes) is the only signal determining the total combustion air flow. In transient conditions, the mass of the steam taken in by, or released from the boiler storage, is taken into account by the application of the signal representing the derivative of the steam pressure. Similarly, the signal representing the derivative of the sum of the feeder speeds compensates for the inherent inertia of the coal input devices. 1 r? A I 89 8.2.2 Air Flow Control Loop J i air flow load disturbance steam flow coal flow into tfieTurnace -d) °-5 xlS - [m] air flow firing rate disturbance 4 0,3i J t(min) change in calorific value of coal coal flow into the furnace • • ij r y 0 K0'' v tlmin) secondary air Fig. 56 Control scheme for combustion air in pulverized coal firing. Fig. 57 It can be proved that the total air flow command signal VL can be best expressed by the following equation: (13) VL=(Kl-K4-»s).mD+K2ÿ + K3 d~~ + Ks . at at This equation forms the basis of the air flow control scheme on Fig. 56. The command signal is derived from the steam flow mD , the steam pres¬ sure P, and the sum of the feeder speeds Under steady state conditions, all the time derivatives are zero, so that the steam flow signal (corrected Time behaviour of air flow for various air flow control configurations. Fig. 57 illustrates the behaviour of the total air flow control for a load step change and for a step disturbance in firing (change in calorific value, in feeder speed, etc.). Curve No. 1 represents the air flow which, as seen, practically matches the coal flow, both for load disturbances and firing disturbances. The result is compared with the results of two other schemes. If correction by the derivative of the steam pressure is not made use of, the resulting curves are denoted by 2. 90 8.2.2 Air Flow Control Loop 8 Boiler Control The corresponding scheme is quite often applied, and it appears that the performance is satisfactory providing fuel flow delays are not excessive, and disturbances of the firing rate not too frequent. Should a scheme be chosen that is similar to the one shown for oil firing on Fig. 53 and which has been already discussed (i.e. should the primary air and speed of the feeders be controlled in parallel by a signal from the steam pressure con¬ troller), the result would be approximated by curves No. 3. For load changes the dynamic response appears to be quite satisfactory, but since a deviation from the set point caused by firing disturbances remains uncorrected under steady state conditions, the configuration appears unsuitable for coal firing. the measuring error amounts to. If it is a question of only 1 or 2%, the correction would probably not be justified. Besides direct-fired systems there are also bin-storage systems where the coal and air from the pulverisers are separated in cyclones, and the coal is then stored in bins. In these cases the steam pressure scheme and the com¬ bustion air flow scheme are exactly the same. A special description of binstorage systems would therefore be superfluous. The scheme on Fig. 56 is based on the assumption that a single positioning of the trimming flaps and dampers always guarantees a correct distribution of the secondary air flows to all burners. The combustion air flow control includes the mill air flow control which is also known as primary air flow control. In this kind of control the cold 'tempering' air and the hot air are mixed together, before transporting the pulverised coal from the mills to the burners. There are two main control tasks: Firstly, the primary air flow VLP must be kept adequately high to ensure the transport of the pulverised fuel; secondly, the temperature i?s in the mill classifier must be kept constant. The mill classifier temperature is controlled by variations in the amount of the added cold air. To this effect, the classifier temperature is measured and compared with the set point. The system deviation is then acted upon by a PI controller which changes the position of the cold air control damper (see Fig. 56). The total primary air flow is controlled by another damper located downstream of the mixing point for the hot and the cold air. The primary air flow control scheme is somewhat dependent on the type of mills. Fig. 56 shows common arrangement. In it the feeder speed n is the master commond signal for the primary air flow controller. A fixed command signal (= con¬ stant bias) is often added to ensure a minimum flow of primary air. More¬ over, the primary air flow control can be sometimes overridden by a rate signal derived from the feeder speed. The idea is to activate the mill storage capacity when the load starts to change, so as to arrive at the new firing rate sooner. The resulting control action gives the impression that the inertia of the mills has been temporarily reduced, while, in fact, use is made of the pulverised coal storage in the mill. — While there is only one total combustion air flow control system, a primary air flow control must be installed for each mill. The air flow measurements on the hot side of the air heater must be cor¬ rected for temperature variations in order to keep the measuring errors small. Just how necessary this is depends on the change of air temperature (in degrees) caused by a given load variation, i.e. on how many per cent 91 ® —i — 11 LS Fig. 58 Control scheme for combustion air in a pulverised-coal firing system. 8 Boiler Control 8.2.2 Air Flow Control Loop There exist, of course, more sophisticated arrangements, usually based on automatically controlled dampers installed in secondary air ducts. These dampers can further be applied in order to maintain the necessary carrierair pressure in the entire load range. In some plants the latter problem is tackled by the application of primary air fans with vane control. Another solution would be to enforce the necessary air pressure by the throttling action of secondary air dampers. A possible variant of the latter control is shown on Fig. 58, where, for reasons of clarity, primary air flow control and classifier temperature control are omitted. Here the approach is si¬ milar to the one used in Fig. 56 and which has already been mentioned in connection with total air flow control. Each secondary air flow control damper forms part of a flow control loop which receives its command signal from the speed of the associated feeder. This makes it possible, should be need arise, to bias the coal mills. The air pressure PL is measured, then compared with a constant or load dependent set point, and the dif¬ ference is used as input to a PI controller. The output signal of this con¬ troller is then used to modify (via multipliers) the command signals of the secondary air flow controllers. Its effect disappears when pressure reaches the set point value. In this manner, the required primary air pressure is assured. all cost to prevent air defficiency, which might easily occur due to the effect of an unexact derivative signal during downward control. 92 Firing of mixed fuels is the next subject for discussion. The first point under consideration is the firing of coal and oil, the control scheme for which is represented by Fig. 49. Here the establishment of the right amount of air is particularly problematic since no exact measuring signal for coal flow is available. One possibility is to use an approach similar to the one already discussed in connection with simple coal firing, and namely to consider the steam flow mD as a measure for the total combustion air flow Vql + 2 Vrl- This would lead to the control scheme shown on Fig. 59. Naturally, the command signal for the total air flow can be again overridden, while the oil flow signal riiQ is being taken into account in the manner shown. The correct distribution of the total air flow between the oil and coal burners is achieved by using an independent air flow controller for oil-air, this controller being in receipt of an exact command signal. The signal has two components — a signal corresponding to the oil flow rho , plus a derivative signal which causes the proper dynamic adaptation of the air flow V(jL. The respective derivative module is often designed as a unipolar unit, i.e. its output varies only between zero and the maximum. The intention is at 1 from command signal for oil controllers En I -0- 93 . —— ÿ I —r— 4 ? EV, KL < En I V0L L g— m—.1 nmn Ji Fig. 59 Control scheme for combustion air in a pulverized coal and oil firing furnace. Coal air flow is determined by the difference between the total air flow and the oil air flow. Further division into primary and secondary air is again effected, as has already been explained, by the primary air flow control. A fundamentally different approach to combustion air flow control, which applies to oil/gas firing, is presented on Fig. 60. As the scheme shows, the F.D. fans keep the pressure downstream of the air heaters constant. The pressure control loop is accompanied by air flow control loops operating 8 Boiler Control 8.2.2 Air Flow Control Loop under command signals from the relevant fuel flow controllers, and pro¬ viding the required oil-air and gas-air flows. From the point of view of dynamics, this arrangement is not particularly satisfactory. It has the further disadvantage that the feeder speed is a somewhat unreliable measure for the coal flow, causing large and lasting deviations from the desired fuel/ air ratio. The command signals are derived from the current command signals of the respective fuel flow controllers. This meets the basic requirement that there should be a maximum of parallel controlling of fuel flow and air flow. The desired excess air for the oil burners and the gas burners can be set by the ratio adjusters Aq and AG . The primary pressure PL in the air duct downstream of the F.D. fans is controlled to ensure that the fans provide the total supply of air for the combustion of the individual fuels. The measuring point is located downstream of the fans but before the duct branches out to provide air for the combustion of the individual fuels. (Note that, as an example, Fig. 60 shows two fans operating in parallel, instead of only one fan shown in the other examples.) The control keeps Pl at a constant value. The two slave P controllers that actuate the inlet vanes of the F.D. fans receive a command signal from a master PI controller. In order to prevent undue losses in the butterfly gates when¬ ever there is a drop in the flow, it is feasible to reduce the pressure set point with a decrease of load. This can be attained by connecting a loadproportional signal to the input of the air pressure controller. 94 from the command signal of the oil flow controller 95 In addition, the gas air flow controller receives a negative fixed command signal. Naturally, this is required only if the gas flow controller likewise receives such a signal, as was the case in the control loop on Fig. 50. from the command signal of the gas flow controller Fig. 60 Control scheme for combustion air control in an oil/gas fired furnace. The air flow control scheme shown on Fig. 60 forms the counterpart to the control scheme for firing a mixture of gas and oil, which is illustrated on Fig. 50. It contains two flow control loops, one for the total oil-air flow Vol, and the other for the total gas-air flow Vgl- The next topic for discussion concerns the air flow control in a cyclone furnace starting with the variant in which the 02 corrective control (02 trim) affects the fuel flow control (see Fig. 52). According to the scheme shown on Fig. 61, the pressure of the primary air upstream of the airheater is controlled so that a constant value PL is maintained. If required, the set point for this control loop can be made variable with load. The secondary air flow VlS receives the same command signal as the fuel flow, this being possible because of the 02 trim. Blade-type regulating dampers are used as control elements. Control aimed at optimum 02 content can benefit from the addition of the derivative of the command signal to the controller input, as well as from temperature-compensation of the air flow measurement. The derivative signal is connected with a negative sign, which means that the secondary air flow can be arbitrarily delayed so that dynamically it fits the coal flow entering the cyclone. The control of the primary air is performed along the same lines as has already been described. The temperature ds is kept at a constant value by an appropriate amount of cold air. 96 8 Boiler Control 8.2.2 Air Flow Control Loop The primary air flow VLP is likewise kept constant but for the exception of load changes: During the load changes the adjustment of the set point which changes the constant control pattern, is caused by variations in the derivative signal from the feeder speed n (which is load dependent). secondary air flow controller (which controls the blade-type regulating 97 dampers). command signal n ÿ"for cyclone 2 from the command signal foi fuel flow load load Fig. 62 Fig. 61 Control scheme for combustion air in a cyclone furnace. Fig. 62 shows another variant of the cyclone furnace firing. It differs from the above discussed scheme in that direct-firing mills are used, and that due to faster control action it is appropriate to introduce the 02 trim into the combustion air flow control. When the 02 content deviates from the set point, the output signal of the trimming controller acts via a multiplier on the command signal to the Control scheme for a cyclone furnace. Last to be included in this sub-section dealing with air flow control is the travelling grate stoker. This method of firing was taken out of sub-section 8.2.1 dealing with steam pressure control, for the simple reason that the air flow control is of particular importance in maintaining steam pressure at a pre-determined value. Concerning steam production, the dynamic behaviour of this kind of firing is characterised by the fact that any action confined solely to fuel flow (i.e. to the speed of the grate) causes intoler¬ able delays in the actual firing rate. If, however, the air flow is adjusted first of all, the fire output will immediately change since there is a con¬ stant coal supply lying on the grate. 7 Klefenz 99 8 Boiler Control 8.2.3 Furnace Draught Control Loop The corresponding control scheme is shown on Fig. 63. The steam pressure controller signal, together with the steam flow feedforward signal, act on the air flow controller. The grate speed n is somewhat delayed following the air flow VL. The ratio adjuster A is used to determine the ratio of the air flow to the grate speed, and, therefore, in the last analysis, that of coal to air. The setting of this adjuster naturally depends on the quality of coal and on the depth of the fuel bed on the grate. It must therefore be manu¬ ally corrected whenever these factors change. Such a mode of operation is acceptable because grate stokers work with a substantial amount of excess air, and exact regulating of this amount is neither possible nor needed. References: [3] [7] [83] [92] [103] [107] [184] [186] [198] [207] [217] [229] [232] [233] [263] [282] [283] [289] [298] [300] [301] [315] [316] 98 P © Fig. 63 f J*I Control scheme for travelling grate stokers. Finally, it should be mentioned that for smaller travelling grate boilers the control scheme does not have to be as elaborate as the one on Fig. 63, and that adequate results can be obtained with simpler arrangements. In some cases it is even possible to dispense with the derivative action of the steam pressure controller, or to get by without the supporting (secondary) air flow controller. 8.2.3 Furnace Draught Control Loop With regard to escaping gases, it is necessary, except in gas-tight welded boilers, to maintain a moderate negative pressure (vacuum) both in the furnace and in the flue gas ducts. This is the objective of the so-called furnace pressure control which, strictly speaking, is suction control. An alternative name frequently used instead of furnace pressure control is 'induced draught control' (or simply draught control) which is derived from the controlling element being the induced draught fan (I.D. fan). Draught control is not necessary in boilers with membrane-wall furnaces, since such boilers can be operated under positive pressure. There is no danger of the flue gas escaping into the boiler house. In general, the control can be built in a very simple manner. A PI control¬ ler with disturbance variable feedforward (which mostly uses a signal from the air flow controlling element) in most cases offers a satisfactory solution. To illustrate this, Fig. 64 shows a furnace pressure control loop using an I.D. fan with vane control. A signal corresponding to the furnace pressure Pp is brought to a PI controller that adjusts the fan vanes in de¬ pendence on the deviation of the pressure signal from the set point. The feedforward disturbance-variable signal is used directly (= proportional action), and is derived from the position Hof the control vanes of the forced draught (F.D.) fan. A signal from an air-flow meter is also frequent¬ ly used to serve as an alternative feedforward disturbance signal. However, it has become apparent that this signal comes too late, due to the delay in the measuring instrument. Better success, i.e. a more exact maintenance of the furnace draught, can be achieved if the I.D. fan vanes are propor¬ tionally adjusted in parallel with the F.D. fan vanes changing position. In order to arrive at the best possible parallel adjustment of the two sets of fans, it is necessary to make certain that the maximum possible speed with which the I.D. fan inlet vanes move, is never lower than that for the F.D. fan inlet vanes. Otherwise, large pressure deviations become unavoidable for purely theoretical reasons. 100 8 Boiler Control 8.2.4 Steam Temperature Control Loop —<p— <D J 5" Fig. 64 Control scheme for furnace draught control. Large boilers usually have two I.D. fans, and their control loop can be structured similarly to the loop shown on Fig. 64. A superimposed master controller commanding two positioners is used. Certain plants are equipped with I.D. fans with speed control. However, due to the large rotating masses and the resulting inertia, this type of control cannot be recommended. A limited improvement is possible by using speed control in combination with flue gas swivel damper adjustment. In this case, the dampers are positioned first (fast action), and then con¬ fined within a favourable control range by the gradual adjustment of the speed of the L.D. fans (delayed action). As regards the overall temperature characteristic of a boiler, the relative proportions of radiant and convective superheater surfaces are normally designed to produce an increased heat flux and a rising level of the final outlet steam temperature with increasing boiler load. It follows that one possibility of keeping the outlet steam temperature constant is the use of a more or less intensive cooling (Fig. 65). In this respect, it is not necessary to differentiate between drum and Benson boilers. Although in a Benson boiler it is possible to use feedwater to affect the outlet steam temperature by shifting the end point of evaporation, the method cannot be effectively applied for any fast correction of disturbances. The dynamics of the con¬ trolled system are not favourable for such an action. The solution rests in applying the same method for a Benson boiler as is used for drum boilers, and namely that of effecting cooling between individual superheater sections. Naturally, the feedwater flow in a Benson boiler is also used for the purpose of adjusting the outlet steam temperature. However, as will be explained in the following sub-section, the action of the feedwater flow must necessarily be very slow-acting in order to contain the temperature within the control range. The common method consists of dividing the superheater into a number of stages relative to the size of the unit, and to install interstage attemperators (i.e. coolers). Depending on the size of the boiler and the required quality of control, up to three desuperheaters may be arranged in series. In the absolute majority of boilers the cooling is done by injecting feedwater directly into the steam. The off-take point for the attemperation water should, whenever possible, be downstream of the feedwater control valve. This positioning is helpful because it causes the load-dependent pressure drop accross the boiler to become the driving force for the attem¬ peration water. If, for example, the load should increase, more attempe¬ ration water will be provided even without the intervention of control. References: [3j [71 [83] [92] [106] [196] [208] [221] [249] [264] [279] [291] [298] [312] [313] [317] i3a . . outlet temperature cooling without control ds . . temperature set point 8.2.4 Steam Temperature Control Loop 100% boiler load The principal objective of live steam temperature control consists of maintaining constant steam temperature at the boiler outlet. 101 Fig. 65 Temperature characteristic of a drum boiler, i.e. of a boiler with a constant evaporation end point. -- 8 Boiler Control 102 - - ---- It is evident that the above measure supports control because it is in agreement with the already mentioned characteristic (Fig. 65). -tjx- © fuel flow 4 Ep [°] ÿ n- Fig. 66 f —ohl— boiler lo Control scheme for steam temperature control. Fig. 66 shows a typical steam temperature control loop with attemperation. The controlled variable is the superheater outlet temperature i?a, while the superheater inlet temperature i?e serves as a secondary (auxiliary) variable. The secondary control loop is necessary for the correction of temperature disturbances originating in superheaters located upstream of the measuring point for #e. The controlled system in this loop has, in comparison to the controlled system in the primary (main) loop, a very favourable dynamic behaviour. The disturbances are largely corrected, and consequently do not enter the final superheater. Incorporation of a feedforward disturbance compensation signal into the scheme may prove an advantage for the following reason: It often occurs that during a load rise the boiler is strongly overfired for the purpose of keeping the steam pressure within a relatively narrow range (see sub¬ section 8.2.1). The result is a severe heating disturbance which affects the superheater, and this disturbance can be effectively counteracted by the mentioned disturbance compensation. 8.2.4 Steam Temperature Control Loop 103 To this effect, a signal proportional to the fuel flow, is brought via a dervative (D) unit to the input of the secondary controller. Fig. 66 also shows the application of a second auxiliary signal, the boiler load signal, which should perform the following function : The set point for the temperature downstream of the cooler, i?e, should vary in agreement with the tempe¬ rature characteristic of the superheater. This means that should the heating-up process intensify with rising load, the set point for the super¬ heater inlet temperature i?e would have to decrease as a function of load, in order to keep the steam outlet temperature $a constant. Generally, these set point changes can be handled by the master PI controller. How¬ ever, the process can be effectively speeded up if the set point variations are taken up by the mentioned load proportional signal. In the cascade control loop shown on Fig. 66, the secondary controller is a proportional controller, while the master controller has proportional and integral action. This is a well proven arrangement which combines good stability and control quality with a reasonable outlay on instrumen¬ tation. It is not necessary to equip the master controller with differen¬ tial action, since due to the inertia of the controlled process the improve¬ ment in control quality would not be particularly impressive. The often used PI/PI cascade is, with regard to control quality, practically equivalent to the P/PI cascade. In the former case, however, there exists the danger of inadequate stability due to the two integral elements arranged in series. Triple-cascade arrangements were tried out, the additional auxiliary variable being the temperature measured in the middle of the superheater. It turned out that the attainable minor improvements did not justify the extra expense. Only in one case has such application been found signifi¬ cant, namely when the superheater is divided into a radiation and a con¬ vection section. Since the radiation superheater strongly reacts to heating changes, the introduction of an additional auxiliary variable could prove successful. For this very reason boiler designers are advised never to implement a radiant superheater as the last superheater in line. The introduction of a further temperature sensor cannot, of course, be considered an excuse for leaving out the thermometer downstream of the first attemperator. As has already been demonstrated, the latter is necessary to compensate, via an auxiliary signal, for the disturbances originating in the primary super¬ heater. 104 8 Boiler Control By the use of efficient digital computers, which is possible nowadays, algorithms of modern control theory can be applied. Presently, state con¬ trollers are tested on temperature controlled system in practical operation. Since the individual states, these are steam temperatures along the super¬ heater pipes, are not measurable (high cost), a so-called observer is used. The observer is nothing else than a model of a superheater where the states are continuously adapted to the actual states by feedback. The control results having obtained to this date are very promising, so that possibly in the near future larger superheaters having the same control quality can be built. This would mean a substantial cost reduction on the part of the boiler construction. The following is important with regard to the variation of the controller parameters: In the secondary loop the problem is basically one of taking into account the blend of the various contributions. Accordingly, the system dimensional gain, expressed as the ratio of the temperature t?e to the lift of the control valve, is load dependent, i.e. with increasing load the gain diminishes. Strictly speaking, this would require an increase in the controller gain with load. However, there are two reasons why this require¬ ment can be disregarded. Firstly, the dynamics of the auxiliary loop are very favourable, so that the closed loop gain and therewith the quality of control can be pushed very high. Secondly, as has already been mentioned, with the attemperation water pipe properly positioned downstream of the feedwater control valve, the injection pressure is proportional to the pressure drop in the superheater, thus increasing with boiler load. This produces an automatic disturbance feedforward action from the steam output of the boiler, which by-passes the controller and acts directly by means of the control valve. In the primary control loop, the controlled system (with the superheater inlet temperature as the input variable, and the outlet temperature as the output variable) has a constant gain, and a virtually load-independent ratio of effective dead time to build-up time. It follows that the controller gain must likewise be constant over the entire load range. However, the integral component of the controller action behaves quite differently. Since the effective dead time decreases proportionally with an increase in the steam flow, this being an inversely proportional relationship, it is in the interest of optimisation to reduce the integral action time with rising boiler load. Of course, since the optimum is rather flat, it is possible to get away with a constant integral action time in the load range of 50— 100%. Only if the boiler were to operate under automatic control at still lower 8.2.4 Steam Temperature Control Loop 105 loads, it would be recommended to make the integral action time auto¬ matically dependent on load. Such an approach is characteristic for adaptive system. Fig. 67 illustrates a steam temperature control scheme where, for the cooling of steam, a heat exchanger is used instead of a spray attemperator. Since in both cases problems are identical, the control structures appear much the same. There is, however, the difference of the time response of the inner loop being less favourable in the latter case, due to the inertia of the heat exchanger. In dram boilers, a frequent variation of the above approach consists in the heat exchanger being located in the drum. In this case, a part of the steam flow is led through a coil condenser installed in the drum, and there it is cooled by the water/ steam mixture that the drum contains. ÿ— © fuel flow Oj] [°] l_ — —6-ÿ boiler load HZH Fig. 67 Control scheme of steam temperature control. Attention has already been drawn to the fact that, for the sake of good steam temperature control in large boilers, it may prove necessary to divide the superheater into several stages, in order to create two or three dynamically favourable control loops. When a boiler has two parallel paths, then it is, of course, necessary to install the mentioned two or three control loops in series in each path. This means that a steam gene- 8 Boiler Control 8.2.4 Steam Temperature Control Loop rator may have six or more live steam temperature control loops. The arrangement of the loops in series leads to problems. A particularly im¬ portant point is to have all controllers operating in proper control range. In order to retain the second attemperation spray water flow, mE2 > within the control range during a rise in boiler load, it is necessary to reduce the set point for the steam temperature i7al upstream of the second attempera¬ tion. From the static point of view, the variation of the spray water flow mE2 with load is kept under control by the strength of the set point adjusting signal which is a steam flow proportional signal acting at the in¬ put of the 1st attemperation controller. In forced circulation boilers the general objective is to maintain a constant ratio of spray water flow to feedwater flow. This implies a linear increase of the spray water flow with steam flow, i.e. the temperature difference across the attemperator should remain approximately constant, which requires the temperature i?ai to be lowered in parallel with #e2 106 For this two distinct solutions are possible. Either the set points of the controllers are marshalled by command signals so as to correspond to the static characteristics of the individual superheaters, or all loops are brought together to form a multiple cascade in which each control loop provides the set point for the preceding loop. The two principles will be explained with the help of Figures 68 and 69. Fig. 68 shows the variant with the variable set points. Each loop is built up along the already discussed lines. The final superheater is, as can be seen from the temperature diagram, a convective superheater, i.e. the heat flux increases with load. 107 ÿ Should another attemperation be installed upstream in series, the require¬ ments would be similar to those discussed above. fuel flow boiler load 1 00% boiler load boiler load boiler load Besides the variations presented in Figures 68 and 69, there are, of course, other methods of maintaining spray water flows within the control range. 100 % boiler load Fig. 68 Another solution to the problem is presented on Fig. 69. The final spray is kept within the control range by maintaining a constant temperature difference ($al — i?e2) across the attemperator. To this effect, the con¬ troller for the temperature t?aI receives a command signal consisting of the command signal for the temperature i?e2 together with a constant value signal. Should, for instance, the boiler outlet temperature #a2 in¬ crease above the set point, the controller would lower the temperature i?e2. The current desired temperature difference At? = t?al — t?e2 can be adjusted by manipulating the already mentioned constant value. Should the boiler be equipped with another attemperation, the described arrange¬ ment could be accordingly expanded. In Benson boilers the command signal for the temperature downstream of the first attemperator, i?eJ , serves a second purpose, namely that of acting as correcting signal for feedwater control, as will be explained in the next sub-section. Control scheme for steam temperature control with two spray attemperators in series. One of them is to measure the temperature difference across the attem¬ perator, and then apply it as the controlled variable. In this case, a follow up controller is used. Another possibility is to control the position of the attemperation control valve by a control loop located immediately up¬ stream of the valve ;its set point can be either constant or variable. The basic difference between the various control schemes can be summed up as follows: While the arrangements corresponding to Fig. 69 are very 108 8 Boiler Control 8.2.5 Feedwater Control Loop advantageous from the static point of view (the spray flows are always in control range regardless of the superheater characteristics and the fire situation), they may cause difficulties from the dynamic point of view. This is in the nature of cascade loops where the primary loop necessarily reacts more slowly than the secondary loop. 109 8.2.5 Feedwater Control Loop In contrast to the control loops discussed so far, feedwater control varies depending on the type of boiler with which it is used. A drum boiler re¬ quires a different feedwater control scheme from a Benson boiler which again differs in this respect from a Sulzer boiler. The term 'feedwater control' is not quite correct, but will be retained in this book because of its general use. The feedwater flow is actually only the manipulated variable for the drum level control in a drum boiler, for the attemperationwater/feedwater ratio control in a Benson boiler, etc. Let us first consider the drum boiler. The amount of water in the drum offers a perfect measure for the supplied feedwater flow. This is the reason for the introduction of drum level control which can be found in three basic variants. The simplest kind is the so-called one-element control shown on Fig. 70. PI to further controllers Fig. 69 Control scheme for steam temperature control with two or more spray attemperators connected in series. This means that with long chains of control loops it may not be possible to adjust such optimum settings as would be achievable if the superheater stages were controlled individually. In contrast, however, the above con¬ siderations do not apply to arrangements which are based on Fig. 68 where each temperature control loop can be dynamically optimized. References: [3] [7] [38] [83] [84] [85] [92] [105] [189] [201] [217] [219] [220] [262] [288] [304] [319] Fig. 70 Control scheme for feedwater control in a drum boiler (one-element control). A signal corresponding to the level L is compared to the set point, and the difference is brought to the input of a PI controller. This controller reduces the control deviation by positioning the feedwater control valve. This being the simplest kind of level control, it is particularly suitable for small boiler units because of its low price, as well as for plants with only minor disturbances (load changes) and for plants that have no exacting demands on control quality. 110 8.2.5 Feedwater Control Loop 8 Boiler Control 111 „v.j The last case had to be specifically mentioned because the time behaviour of the controlled level system can be, on occasions, rather unfavourable. Thus, for example, an increased infliix of cold water into the drum causes condensation of steam bubbles in the drum water, and this may consider¬ ably delay the final effect of the change in supply on the drum level. L W There are times when control action must even take into account the possibility of a tranlitory change in the direction of the movement of the drum water level. Such a change occurs, for instance, following an increase in the feedwater flow, when the level at first actually drops due to thÿ,.., mentioned cooling ('shrinkage'), and starts rising only afterwards. The same effect takes place when the load is reduced because the drum pres¬ sure momentarily increases. On the other hand, when the demand for steam increases due to a rise in loading, the increased steam flow causes a fall in pressure which, in turn, leads to the expansion of the submerged steam volume in the drum and in the risers. The water swells, and the drum water level actually momentarily rises ('swell). As a result, the drum level signal causes an initial reduction of feedwater flow, and this cannot be the desired action. It is obvious that control could be improved by the introduction of a feedforward disturbance signal from the steam flow. Such a solution is shown on Fig. 71. It implements the so-called two-ele¬ ment control which differs from one-element control in that the feedwater control valve receives a signal from the steam flow, and this leads to a proportional anticipatory action. As the steam flow increases, the valve opens even further, and vice versa. However, the scheme is seldom used, because a much better one differing only very slightly, offers itself in the form of the three-element control (see Fig. 72). Fig. 72 Control scheme for feedwater control in a drum boiler (three-element control). The feedwater flow measurement is generally available, and from it a con¬ trol signal can be derived without incurring additional cost. The applica¬ tion of this feedwater flow signal mg thus offers the possibility of cor¬ rectly controlling the amount of feedwater during load changes, i.e. during disturbances of the steam flow. For instance, should the steam flow increase by 10%, the signal comparison at the input of the controller would also immediately increase the feedwater flow by 10%. In contrast to two-element control, this happens independently on the valve characte¬ ristic. Because the fine matching of the drum level to the set point cannot be guaranteed solely on the basis of equality of the steam flow and the feedwater flow, the drum level deviation is also applied to the input of the PI controller. It follows that the control loop remains in steady state only when in addition to the steam flow being equal to the feedwater flow, there is no level control deviation. The disadvantage of such an arrangement is that measurement errors in the steam flow and feedwater flow determination produce a constant level displacement. Consequently, if a shift from the set point (caused, for in¬ stance, by non-standard steam flow measurement) cannot be tolerated, a slightly modified scheme according to Fig. 73 would be preferable. Fig. 71 Control scheme for feedwater control in a drum boiler (two-element control). In this arrangement the level L is always kept at the set point regardless of the disturbances. The steam flow signal mD becomes the variable set point of the secondary controller for feedwater flow mg- This set point is further trimmed by the output signal of the superimposed level con¬ troller which corrects all the inconsistencies in the steam and the feedwater flow signals. 8 Boiler Control 8.2.5 Feedwater Control Loop Next for discussion is the feedwater flow control in a Benson boiler. The signal that Benson boilers lack is the basic signal which is used in drum boilers as a measure of the correct feedwater flow and of the proper amount of feedwater in the boiler, i.e. the drum level signal. In replace¬ ment, the ratio of the attemperation water flow to the feedwater flow is used. 5% of the feedwater flow missing. Thus, in steady state the attemperation water flow must equal 5% of the feedwater flow. On the whole, the arran¬ gement gives satisfactory results, even though it still leaves much to be 112 113 desired as regards process dynamics. Some of the deficiencies can be elim¬ inated by installing additional features (see Fig. 75) which consist of three rate signals, derived from the steam flow, from the temperature down¬ stream of the evaporator, and from the fuel flow. Control scheme for feedwater control in a drum boiler (three-element control). As has already been explained, it is possible, from the static point of view, to control the steam temperature by means of feedwater flow. However, in order to obtain dynamically favourable control results, it is further necessary to introduce spray attemperation control. Thus attemperation becomes the main method for controlling steam temperature, while con¬ trol of the feedwater input is used only for maintaining the attemperation water flow within the control range. This can be achived by using as the controlled variable for feedwater control the ratio of attemperation water flow to feedwater flow. A very simple approach is shown on Fig. 74. A feedwater flow controller receives a command signal from the steam flow. The signal is not applied fully (100%) but is reduced by a fraction corresponding to the attempe¬ ration water flow. Therefore, if only 95% of the feedwater flow signal is permitted to pass through by the ratio adjuster A, then there is always ÿ Fig. 74 =i Control scheme of feedwater control in a Benson boiler. The first signal makes it possible to override the feedwater flow signal during load changes and thus to counteract the tendency of the evapora¬ tion end point to wander. The primary function of the temperature signal from downstream of the evaporator is to promptly reflect all changes in the fire, and just as expeditiously to adjust the feedwater flow. The signal 8 Klefenz 114 8 Boiler Control contributes to the stabilization of the feedwater flow control if it is lo¬ cated downstream of, and possibly close to, the evaporation end point, this being a dynamically favourable location. Unfortunately, a dynamical¬ ly favourable temperature signal of this kind is frequently not available (planned location may not be suitable). In such a case, pre-control of feedwater flow following a change of fire can be taken over by a signal derived from the fuel flow. This means that the three rate signals indicated on Fig. 75 are mutually complementary. Usually only after commissioning of the steam generator can it be established which of the three signals should be the dominant one, and to what extent, if any, the remaining two signals are to be brought in for support. Should, for instance, the temperature signal prove to be dynamically unfavourable, it could be completely rejected by the commissioning engineer, and replaced (for precontrol during fire changes) by the derivative of the fuel flow signal. — — -ED | Fig. 75 8.2.5 Feedwater Control Loop 115 flow. Generally, the measurement of the feedwater flow causes no diffi¬ culties. However, the steam flow measurement may require a correction for pressure, which is, of course, a must in variable pressure units. In practice the frequently used control schemes are those in which the ratio of the attemperation water flow to feedwater flow is directly measured, and the measurement is used for the correction of the ratio of steam flow to feedwater flow. Fig. 76 Control scheme for feedwater flow control in a Benson boiler. 1 Control scheme of feedwater control in a Benson boiler. With this kind of control diagram it is always understood that the feed- water flow is measured downstream of the branching-off point for the attemperation flow. It is in the nature of such a scheme that the ratio of the attemperation water flow to the feedwater flow, as maintained by control, depends on the accuracy of the measurement of the steam flow and the feedwater The basic lay-out is illustrated by Fig. 76. As to the optimization of the correcting PI controller, it should be mentioned that due to the unfa¬ vourable time behaviour of the controlled system (i.e. from the adjust¬ ment of the feedwater flow to its effect, via temperature control, on the attemperation flow) both the proportional band and the integral action time must be set very high. This causes the control to act as an integral controller with a large integral time constant. It follows that the controller can maintain the precise ratio mÿ/rhs only in steady state. No assistance can be expected in transient states, such as would prevent, for example, the evaporation end point from temporarily 8* 8 Boiler Control 8.2.5 Feedwater Control Loop wandering in the wrong direction. Under certain circumstances, there may even be drawbacks caused by the fact that the correcting controller inte¬ grates all temporary deviations from the set point. Some of these deviations are indispensable and their correction could lead to unsatisfactory adjust¬ ment of the feedwater flow. For example, some temperature control re¬ quires that during a load increase the ratio mE/ms temporarily lies above the set point. This the correcting controller registers as a fault, and (erroneously) adjusts the ratio of the steam flow to the feedwater flow. This incorrect action must later be cancelled, thus leading to further disturbances of the balance between water and fire. within the control range by control action on the preceding attempera¬ tion spray, which maintained a constant temperature difference across the final attemperator. This cascade structure can be extended up to the feedwater flow level, i.e. the feedwater flow can be used to maintain a constant temperature difference across the first attemperator. This is shown on Fig. 77, the chosen example being a boiler with only one spray cooler. Initially, the feedwater flow controller receives a feedforward signal from load. This signal can be derived either from the steam flow, or from the electrical power, or from the power set point. The ratio of the load signal to the feedwater flow signal is corrected in a multiplier by a signal from a PI temperature difference controller. The respective tempe¬ rature difference is established from the measured temperature #al up¬ stream of the attemperator and the set point for the temperature i?e2 down¬ stream of the attemperator. In order to stabilize this rather inert control loop, the same approach as before is used — the temperature t?el or the enthalpy of the steam downstream of the evaporator becomes the auxil¬ iary variable. 116 9.2 ~xr~ 3»2 pi i 1 —© A3 [jo -f $ — Fig. 77 no—&•—[*>— Control scheme of feedwater control in a Benson boiler. A further scheme for feedwater control is presented on Fig. 77. It repre¬ sents an evolution from the scheme for steam temperature control shown on Fig. 69. In the latter scheme, the final attemperation spray was held 117 In the schemes so far discussed it was the feedwater valve that played the role of the controlling element. With large boiler units, however, the trend is to avoid a significant pressure drop across the feedwater control valve by using one or more feedwater pumps with speed regulation for control. In principle, the same control schemes are possible. Generally, both the feedwater control valve and the speed-controlled pumps are installed. Fig. 78 illustrates the control of a boiler with two feedwater systems. Each system has its own feedwater flow control assembled according to one of the already discussed schemes. In order to keep a low throttling loss across the valves, the speed of the feed pumps is adjusted in a way that would allow one of the valves to remain practically fully open. The residual throttling is needed to give the possibility of a fast increase of feedwater flow by fully opening both valves. In the control scheme shown, this task is solved in the following manner: The lift Hof both valves is measured, and the higher one is chosen by a maximum selector. The selected signal is then compared with the set point, and the difference is applied to the feed-pump controller. In the case of a deviation from set point, the speed of the pumps is ad¬ justed by the action of the secondary P controller. The arrangement on Fig. 78, which applies to two electrical pumps, can easily be extended to three or more electrical pumps as well as to turbine driven pumps. 118 8.2.5 Feedwater Control Loop 8 Boiler Control iÿVT+l 119 E2 P( 1) (+) -.1 I Max maximum selector J Fig. 78 Scheme for control of feedwater pumps. One variant of the above pump control consists of using signals derived from the pressure drop across the valves instead of signals derived from the valve positions. Of course, in the latter case the selector unit must choose and pass-on the lower of the two differential pressure signals. In this manner a minimum pressure difference will be maintained across one of the valves. Finally, it should be noted that both secondary controllers shown in Fig. 78 could also be replaced by two Pi-acting flow controllers for the two partial flows discharged by the pumps. A fundamentally different structure of feedwater control based on variable speed pumps is shown on Fig. 79. The actual feedwater control operates as already described above; the control signal acts on the controllable hydraulic couplings of the pumps (or on the inlet valves if turbopumps are involved), and the distribution of the feedwater flow into the individual systems is regulated by the so-called trimming or biasing control. Fig. 79 Scheme for feedwater control with speed controlled feed pumps. The trimming control keeps one of the feedwater control valves fully open at all times. End position contacts are provided for the possibility of a change-over. The secondary controller of the cascade ensures that a change of feedwater flow in one system is simulteneously accompanied by a corresponding change in the other. With the position of the switch corresponding to that indicated in Fig. 79, the control valve in system 1 tends to open in parallel with an increase of the water flow mS2. This arrangement of the feedwater control circuit plays an important part in avoiding instability on the feedwater side. Con- 120 8 Boiler Control 8.2.5 Feedwater Control Loop trol systems without this feature have often been observed to undergo swinging of the two systems in opposite directions, i.e. with the total feedwater flow remaining constant, the water flows rh$l and 2 were swinging in reverse. The primary controller ensures that the attemperation water flows in both systems are equal by biasing the feedwater flows. For instance, when the switch is in the indicated position, rhsi will increase with a simultaneous decrease in rhs2 whenever the spray water flow mE1 increases due to the shifting of the fire. It is recommended to give the superimposed controller only P action, since in the interest of the desired approximate equality of the attemperation-water/ feedwater ratios, the attemperation water flows should not be equal. The alternative polarity indicated in Fig. 79 should make it clear that polarity changes depend on which feedwater valve is to be activated. Should the left-hand side valve be acted upon (corresponding to the indicated position of the switch), the un-bracketed polarity signs should be used; the reverse applies for the right-hand side valve. This mode of operation may appear rather compli¬ cated at first, but is quite easy to implement with the use of a switching controller (a three-position controller). The polarity reversal can then be performed at the controller outlet where valve motors are actuated. A so¬ lution with a continuous controller is also possible: Connected to the output of a PI controller would be two positioners acting in opposite di¬ rections, and operating in sequence so that one valve would start to close only when the other is fully open, and vice versa. In a further variant, the control of temperature downstream of the eva¬ porator replaces the control which maintains the attemperation water flows in the two systems equal. Naturally, a point must be chosen for the temperature measurement where it is certain that the steam is always Fig. 80 Scheme for low-load and start-up feedwater control in a Benson boiler. slightly superheated. Let us now consider the low-load operation arrangement in a Benson boiler. With the lowering of load in a once- through boiler the danger exists that the required flow situation in the evaporator (i.e. the approximately ba¬ lanced admission flows in parallel tubes) cannot be guaranteed. It is there¬ fore necessary to maintain a certain minimum water flow (approx. 30%) through the evaporator, regardless of the currently withdrawn steam flow. The corresponding control scheme for such an operation, which is also applied during start-ups, is shown on Fig. 80. To separate water and steam from the mixture leaving the evaporator a vessel is inserted at its outlet. The separated water is again returned into the feedwater flow at a point upstream of the economiser. This is effected via a recirculation pump and a recirculation control valve. Such an arrangement enables more water to flow through the evaporator than is fed to the boiler. In the actual scheme, the level L in the separator is controlled by the recirculation control valve. Here importance is attached to the application of the feedforward distur¬ bance signal from load, mD, since due to the limited volume of the sepa¬ rator it is not that easy to control the level. Further, there may be stabi¬ lity problems originating in the plant; these will be discussed in sub¬ section 8.3.3. They can cause a relatively sluggish level control, in the 8 Boiler Control 8.2.5 Feedwater Control Loop course of which the application of the feedforward steam flow disturbance signal generally proves helpful. The polarity of this disturbance signal must, of course, be such that recirculation would diminish with an increase in load. The pre-set minimum flow through the evaporator must be main¬ tained. To this end a maximum selector effects a comparison of the command variable for the feedwater flow controller with the set point for the minimum feedwater flow. Should the command variable drop below the minimum set point, the feedwater flow controller would pro¬ vide a constant feedwater flow corresponding to nismjn- The separator is equipped with an additional drain for dealing with a sudden swell of water. The P acting controller has therefore only a limiting function. If the level increases beyond a specified maximum value, the drain valve begins to open. This prevents water from entering the superheater. The final topic of this sub-section is the feedwater flow in a Sulzer boiler. Due to the presence of the water separator and the resulting establishment of the evaporation end point, it is possible, as in a drum boiler, to find simple and, at that, dynamically favourable control signals for feedwater flow control. The preferable desired value would be the steam moisture at the outlet of the evaporator. 122 F& 123 A3 In Fig. 80 the controlling element for feedwater flow is marked as a valve. This stands also for all other possibilities of influencing feedwater flow, such as the use of a low load control valve, or of controllable feed pumps. To complete the description of control in Benson boilers, a brief mention should be made of the so-called auxiliary heating surface. As can be seen from Fig. 81, the term denotes a tube coil located in the furnace, through which passes a limited amount of feedwater. This partial flow is taken of the main stream with the help of a throttling device (marked as a valve) with a very low pressure loss. It was presumed that in this arrangement the measured temperature diffe¬ rence A# would provide a signal representing a reliable measure for the heat released in the furnace. It was judged that a suitable construction would provide a dynamically favourable response to the fire and feedwater changes, and that the feedwater flow in a Benson boiler could then be con¬ trolled with such a signal. Unfortunately, with only a few exceptions, practical experience has proved contrary. The variable Ad has seldom been a useful measure for heating, since the results become falsified by the dirtying-up, fire shifting, evaporation, and such like. Dynamics likewise leave much to be desired. In the few cases when the Ad signal was actually applied, it was mostly only its time derivative form that was used for anti¬ cipatory action. In modem power plants the auxiliary heating surface has consequently disappeared. Fig. 81 Auxiliary heating surface. Unfortunately, so far no method has been found for directly measuring the steam moisture content in actual plants, and indirect measurements must be used. There are two possibilities in a Sulzer boiler. The first variant uses the temperature at the separator inlet; this is the so-called 'multiple-thermostat method' or 'evaporator pilot tubes method'. The second variant uses the level of water in the separator. In the original method the controlled variable used is the temperature of the slightly superheated steam in one of the parallel evaporator tubes. To this effect, the flow through the relevant tube is lowered by throttling on the inlet side. The resulting degree of superheating then serves as a useful measure for the heat absorbed by the evaporator, i.e. of the ratio of com¬ bustion intensity to feedwater flow. Therefore, the respective temperature serves as the controlled variable signal. This control scheme is shown on Fig. 82. 8 Boiler Control 124 8.2.5 Feedwater Control Loop 125 to increase the pilot tube temperature with rising load. This is the reason why the set point is not determined by a fixed command signal, but made variable by the application of the steam flow signal. In addition, it is neces¬ sary to undertake measures which will ensure stability over the whole range. Since the gain of the controlled system is strongly load dependent (decreases with increasing boiler load), it follows that the controller gain must likewise maximum selector be adjusted in dependence on load. In Fig. 82 the finely dotted line leading to the temperature controller suggests that the controller gain must increase with load. A proportionally acting level controller is installed to take care of the dis¬ charge of the residual moisture segregated in the separator. In the case of a serious disturbance of the fire/water equilibrium in the boiler, a large amount of water can separate, giving rise to an overflow. A second discharge controller (not shown in Fig. 82) is installed to deal with such possibility, and it activates a large discharge valve; its set point lies above the set point of the level controller that is normally in operation. Fig. 82 Scheme for feedwater flow control in a Sulzer boiler. In practice, not one but several tubes are equipped with temperature sen¬ sors. This has the advantage that during normal operation the throttled tube can be replaced by another one. This arrangement proves likewise expedient if, under certain circumstances, a shifting of the fire causes one of the throttled tubes to receive too little heat while another one is overheated. is chosen by a Consequently, if the maximum guide-line temperature maximum selector, a reliable controlled variable signal is available. This signal is compared with the set point, and the deviation is fed into a PI controller. This controller, in turn, modifies the set point of the feedwater flow controller so that the deviation is eliminated. The flow controller further receives a disturbance signal derived from the steam flow mD , which instantly and perfectly adjusts the feedwater flow during load changes. In order to keep the residual moisture constant, it is necessary A further variant, predominant in modern plants, is shown on Fig. 83. In this case, the measure for the fire /water equilibrium in the boiler is the level L in the separator. A deviation of this level from the set point would accordingly change the set point of the feedwater flow controller, just as in the above mentioned variant. Anticipatory action is again provided by the disturbance variable mD. As has already been explained in section 8.2, it is necessary to raise the level whenever load increases, in order to achieve, with the help of a propor¬ tionally acting discharge controller, a blow-down flow that would likewise rise with increasing load. The equation (12) has already proven that in order to achieve a constant moisture content, the relationship between the steam flow and the blowdown flow must be kept constant. Therefore, a signal proportional to the steam flow is applied to the level controller to ensure the continuous ad¬ justment of the set point. If required, the two schemes shown on Figures 82 and 83 can be combined. In the resulting cascade the feedwater flow controller receives the command signal from the pilot tube temperature controller which, in turn, obtains its set point from the superimposed level controller. 8 Boiler Control 126 8.2.5 Feedwater Control Loop 127 it adapts itself freely to pump characteristics and relevant pressure drops. The system is so designed that circulation amounts to approximately 130 to 150% of full load flow, and is virtually independent of boiler load. n *-S normal S normal Fig. 83 Scheme for feedwater flow control in a Sulzer boiler. One of the latest types of boilers is one that fits somewhere between the once-through forced-flow boiler and the forced circulation flow boiler. It is, in fact, a once- through forced-flow boiler with superimposed circulation. The main reason for the development of this type of boiler can be found in the continuously increasing difficulty of maintaining the stability of water flow distribution in the parallel tubes of both the economiser and the evaporator. To find a solution to this problem has become more acute with operation shifting towards increasingly low partial loads, with the wide application of the variable-pressure start-up, and with the increasing use of welded furnaces carrying the implied arrangement of tubes. All this suggests an artificial increase of flow through the furnace. Considering this problem it is necessary to distinguish between boilers in which the increase is required only for the low load range, and those in which the requirement applies up to full load. One possible scheme designed for low load operation is shown on Fig. 80. Another scheme which assumes circulation throughout the entire load range, is presented on Fig. 83.1. The circulation water flow is reintroduced into the main stream beyond the economiser. The flow through the evaporator is not controlled, rather Scheme for feedwater control in a once-through forced-flow boiler. Circulation in the entire load range. The three-element control according to Fig. 83. 1 has proved quite effective. The circulation control valve is normally fully open, since the level lies above the set point L$ of the pertinent P controller. The level deviation acts upon the feedwater flow valve, while the steam flow leaving the sepa¬ rator, mD , provides an anticipatory disturbance signal. Modifications are possible, and the application of derivatives of the fuel flow and the steam flow (again in the form of anticipatory signals) has been tested in practice. To prevent the complete emptying of the separator, whenever a pre-set minimum level is reached it triggers the action of a P controller which closes the valve downstream of the circulation pump. On hand are, of course, the already discussed blow-down controllers which guard against overfeeding. These are not shown on Fig. 83.1. 8 Boiler Control 8.2.5 Feedwater Control Loop All the arrangements discussed in connection with Benson boilers can be also applied in supercritical Benson boilers. On the other hand, no schemes based on water level can be applied in supercritical Sulzer boilers since they do not use a water separator at supercritical pressures (the steam and water phases are not present together). There the principal controlled variable is derived from the temperature at the end of the transition zone (which corresponds to the evaporator in subcritical units). An outlet cor¬ responding to the blow-down pipe is available, but it is normally closed, and serves only for carrying away surplus water during heavy disturbances. with the 100% pump, controller 2 with either one or both 60% pumps depending on which are in operation. The controllers 3, 4, and 5 are the actual limiting curve controllers that act on the speed of the respective pumps via minimum value selector units. The use of selectors guarantees the effectiveness of this type of control. The limiting curve for each pump as well as the lower pressure limit are derived from the feedwater pressure Ps, and the characteristic is formed in the respective function generator (6, 7, or 8). The output of these generators is compared with the current feedwater flow, and the differences become the inputs for the limiting curve controllers. If there is a feedwater valve which is normally fully open, then it can be used for throttling whenever feedwater pressure drops excessively. In this manner action can be undertaken before the limiting curve is reached. If, for any of the pumps, the difference between the actual flow and the flow derived from the limiting curve drops to Am, controller 9 starts throttling. To achieve this, a minimum selector will choose the smallest deviation from the limiting curve. The action of con¬ troller 9 increases the resistance of the system. As a consequence, speed increases via feedwater control, thus driving the pumps out of the danger 128 129 zone. References: [3] [7] [18] [59] [83] [92] [104] [108] [114] [189] [201] [213] [259] [262] 60"/. Fig. 83.2 Scheme for feed-pump control. If the pumps are to be used for control, their pressure must not fall below a load dependent limit. To this effect they are protected by 'limiting curve control' illustrated on Fig. 83.2. To demonstrate how the control works when several pumps are involved, let us assume that one 100% pump and two 60% pumps are installed. In the diagram, controllers 1 and 2 are feedwater flow controllers, described in the preceding text. Controller 1 is used 9 Klefenz 130 8.2.6 Reheat Steam Temperature Control Loop 8 Boiler Control 13 1 8.2.6 Reheat Steam Temperature Control Loop The task of this control loop is to maintain constant steam temperature at the outlet of the reheater. As the reheaters are located towards the outlet of the boiler, i.e. in the cooler part of the gas path, they have a charac¬ teristic distinctly reflecting convection heat transfer. In other words, their heating up increases with boiler load. As already explained when discussing temperature control of high pressure steam, such a characteristic makes it possible to control temperature by injecting feedwater. The control con¬ cept thus corresponds to Fig. 66. However, it must be pointed out that it would be a serious mistake to locate the spray attemperator at the inlet of the reheater in view of the size of the reheater and the bad process dynamics connected with it. Effective control requires that attemperation be moved out as far as possible in the direction of the reheater outlet. Due to the danger of water drops reaching the turbine, and, above all, because of the increased heat consumption, injecting water into the reheater is not a particularly popular process. When investigating other methods the use of heat exchangers should be considered in the first place. In these units, heat is basically transferred from high pressure steam to low pressure steam. Figures 84 and 85 show two possibilities of control. According to Fig. 84, the adjustment is performed in the reheat (i.e. low pressure) path: The control determines how much of the total flow by-passes the heat exchanger. The polarity is chosen so that a stronger action (application of a plus signal) implies more cooling. In all aspects the cascade used is the same as that described for attemperation control of high pressure steam (see Fig. 67). load Fig. 84 high-pressure steam Scheme for reheat steam temperature control by means of a heat exchanger. by heat exchanger which is itself heated by flue gas. Control is effected Triflux; the of injecting water into the high-pressure steam side upstream this then influences the temperature of the reheat steam. The control already scheme which is conceived similarly to the schemes that have been discussed, is shown on Fig. 86. The auxiliary control variable is the temperature downstream of the mixing point, and the set point is again adjusted by boiler load, possibly by steam flow. It is also recommended to use a feedforward disturbance compensa¬ tion from the fuel flow, in the manner shown on Fig. 66. high-pressure steam In the variant according to Fig. 85, the correcting action affects the highpressure steam path. Otherwise, the scheme is the same as that on Fig. 84. From the point of view of process dynamics the controlled by-pass on the reheat steam side should be given preference above the one on the high-pressure steam side. A three-flow heat exchanger, the so-called Triflux, can be traced back to a patent by the company Gebriider Sulzer A.G. In it the heat exchange between the high-pressure steam and the reheat steam takes place in a Fig. 85 9* Scheme for reheat steam temperature control by means of a heat exchanger. 132 8 Boiler Control 8.2.6 Reheat Steam Temperature Control Loop The control scheme for gas by-passing is shown on Fig. 87. Here the backpass of the boiler is partitioned. The flue gas swivel dampers which are operated either successively or so that they rotate in opposite directions, vary the heating of the reheater. A simple PI controller, with a propor¬ tional anticipatory signal from boiler load, is adequate to control the out¬ let temperature. Of course, the adverse effect of the heating surfaces that have to be accomodated in the other part of the pass, is noticeable. high-pressure steam Fig. 86 Scheme for reheat steam temperature control by means of the Triflux. Besides heat exchanger and attemperator control, other measures are often undertaken to influence the heat absorption of the reheaters; these can be flue gas by-passing, flue gas recirculation, and tilting of burner nozzles. Satisfactory results can be obtained with flue gas by-passing if the whole reheater (or at least its end part) lies in the range of influence. - -load _J Fig. 87 133 Scheme for reheat steam temperature control by means of a flue gas by-pass. During flue gas recirculation one part of the flue gas flow at the boiler out¬ let is branched off and returned to the furnace (or to a location just up¬ stream of the furnace) in order to increase heat supply to the heating sur¬ faces. In spite of quite favourable results when this type of control is in operation, secondary effects render the method less than satisfactory. The heaviest argument on the negative side is that affected are not only the reheater heating surfaces but also all other heating surfaces. In addition, surfaces heated by radiation are affected by the supplied heat even more rapidly and more vigorously than the reheater surfaces which are heated by convection. This means that whenever flue gas recirculation is used to control reheat steam temperature, other loops, such as the final steam temperature control loop and the steam pressure control loop, are severely disturbed. This is the reason why flue gas recirculation is predominantly applied only in an open-loop mode where the flue gas flow is adjusted according to boiler load. In such an operation, the recirculation flow must be raised with decreasing load, in order to counteract the convection heat transfer characteristic of the reheater. The actual temperature control can be performed by either a spray attemperator or a heat exchanger. The use of burner tilting for control is not recommended for reasons simi¬ lar to those that apply to flue gas recirculation. Burner nozzle adjustment would not only affect the heat absorption of reheater surfaces, but of all other heating surfaces as well. Tilting burners are therefore primarily employed only for static corrections after large load changes, or when heating surfaces become dirty. Finally, it should be mentioned that repeated use is made of combining the above described control methods. For example, control using flue gas dampers (Fig. 87) can be supplemented by attemperation control. With such a combination the attemperator controls the reheat outlet tempera¬ ture as before, but its set point is set higher than the set point for flue gas 134 8.2. 7 Other Control Loops 8 Boiler Control 135 recirculation control. The spray then acts as an emergency measure, i.e. only during positive control deviations of considerable magnitude. References: [3] [7] [83] [84] [85] [92] [105] [214] [217] $r-Gh;-* A j 9 L [m] 8.2.7 Other Control Loops The preceding sub-section dealt with the main control loops of a steam generating unit. There are, of course, other control loops which, on the whole, pose no problems in the area of control technology, and therefore need not be discussed in the context of this book. The controllers used in the auxiliary loops are basically simple pressure, level, and temperature controllers, generally equipped with PI action but quite often only with simple P action. To mention just a few such applications, there are the sundry control loops in the milling plant; temperature control loops on oil heaters; atomiser steam pressure control loops on oil burners; air temperature control loops; as well as various control loops in the feedwater system. The following discussion will consider the control of pres¬ sure reducing stations, and the so-called condensate flow stop control. Fig. 88 using the usual 30-second or even 60-second stroke time. An additional requirement is that the outlet steam must be cooled in order to match the temperature level downstream of the respective turbine part. Desuperheating is effected by an injection of water, either directly into the re¬ ducing valve (Fig. 88), or into a separate cooler (Fig. 89). The tempera¬ ture controller is built-up as a PI controller; an anticipatory action from the position of the reducing valve is useful. Reducing stations can be operated in two modes, either as over-flow stations or as back-pressure stations. Accordingly, there are two basic control schemes illustrated on Figures 88 and 89. Fig. 88 shows an over¬ flow reducing station installed in parallel to the high- and low-pressure stage of the turbine, and serving as a means of protection against excessive pressure. Here the valve is normally closed, since the set point is adjusted slightly higher than the operating pressure. Should, however, the pressure Pv rise above the set point, the initial reaction would be that a rapid traverse motor (with a positioning time of approximately 5 seconds) would quickly open the reducing valve. The high-speed opening is mandatory because the pressure increases very rapidly upon load rejection. Following the initial action, control is taken over by standard PI control which maintains the inlet pressure constant Control scheme for an over-flow reducing station. -ED— A n- \k Fig. 89 Control scheme for a back-pressure reducing station. 8. 2. 7 Other Control Loops 8 Boiler Control 136 This anticipatory action causes the water injection valve to react instan¬ taneously following the initial response of the reducing station. It follows that reducing stations in plants operating with variable pressure should not have a fixed set point. The reason is that in situations when the fastresponse mode is currently used at low loads (i.e. at low steam pressures), the steam pressure would first have to be radically increased before the station could respond. Such a waste of energy can be avoided by making the set point variable with load. A simple method is to replace the up¬ stream pressure Py by the current deviation (or actuating signal) of the steam pressure controller (= firing controller), and to use as the set point the deviation signal at which the station should open. As long as the actual deviation remains below the set value, the controller keeps the station closed. On the other hand, the reducing station always opens when the set deviation is exceeded, independently of load and therefore also independently of steam pressure. 9 Fig. 89.1 to 137 not required, and can be omitted - see Fig. 89. In all other aspects the control is conceived along the exact lines as suggested for the over-flow station. One possibility of achieving fast load increases is the exploitation of the boiler storage capacity. This has already been discussed in preceeding sub-sections. A further useful measure which is, however, not as produc¬ tive, is throttling or even shutting off the bled steam flows on the turbine side. This approach makes use of the possibility to expand in the turbine, after the closure of the extraction points, the bled-steam flows which are not extracted. The increase in power can then be used during fast load raises. The manner in which the shut-down of the preheaters takes place affects the dynamic performance. Basically, it is possible to draw on the bled steam intended for high-pressure preheaters as well as low-pressure ones. If there is a choice, the taking out of service of low-pressure heaters is more advantageous. It causes no disturbances in the loading of the steam generator, and can take place independently of other measures. An example of such a control, which is sometimes called condensate flow stop control, in a unit which uses natural variable pressure operation, is presented on Fig. 89. 1. The water that accrues in the condenser is fed via a condensate roughing pump 6 into a condensate storage tank 3. This vessel serves as a buffer storage for the condensate delivered by the speedcontrolled main condensate pump 5. In plants that are not equipped with a separate condensate storage, it may be possible to use the condenser itself as a form of limited storage. By varying the speed of the main pump it is possible to vary the condensate flow between 30% and 150% of the nominal value. This has the effect that a certain amount of the bled-off steam condenses in the low-pressure preheaters 2, and thus leads to a decrease or increase of load. The control works as follows: An increase in the load set point N$ reduces, via the derivative module 10, the set point for the condensate flow controller 7 ; this action leads to the required fast increase of load. The inserted limiter 9 has the task of changing the strength of the applied signal in dependence on load, while simultaneously limiting its absolute amplitude. Scheme for condensate flow stop control. Somewhat different considerations apply to back-pressure reducing sta¬ tions where a constant steam flow is let through, for instance, as process steam. Here the anticipatory action in the temperature control loop is The rest of the scheme represents a three-element level control in the feedwater tank 1. The level controller 4 is adjusted for slow action to allow the condensate flow stop control to take effect. For the same reason the steam flow signal is applied with a delay (PT[ — module 8). In this manner it takes only a few seconds (the interval is a function of the stroke time) 139 8 Boiler Control 8.3 Signal Flow Diagrams of Controlled Systems to achieve load increases amounting to 3 to 5% of the currently produced load. This increased load can be maintained for several minutes, depending on the available storage capacity for the condensate, i.e. on the water supply in the feedwater tank. This does not exclude, in cases of expediency, the occasional use of re¬ ference variables as might occur in the calculations, particularly if such calculations are performed with the help of an analogue computer. The marked variables are, in fact, deviations from a specific stationary state, this being acceptable because dynamic behaviour is customarily described by linearised models. Strictly speaking, it follows that it would be pre¬ ferable to write An instead of n. However, the A symbol is generally left out for the sake of simplicity. 138 References: [3] [35] [83] [92] [132] [140] [224] 8.3 Signal Flow Diagrams of Controlled Systems The following sub-sections deal with the dynamics of the main systems of the control loops covered in section 8.2. The most effective approach is to use signal flow diagrams (also known as block diagrams), since these not only indicate the transfer characteristics marked into the individual blocks, but also, and above all, facilitate the recognition of the systemdependent couplings and interactions. The scope of this book does not call for a detailed description of the dynamic behaviour of controlled systems in a steam generator. In this respect the reader is advised to consult specialised literature listed in the references. However, provided are such approximations as have proved useful by tests on operating boilers. In addition, the text gives guidelines for approximate calculations of the various constants contained in the diagrams. Particular importance is attached to determining all the required factors and time constants from design and construction data. Whenever a simple approach does not work, available empirical values are indicated. Each individual sub-section deals with the respective controlled system of a specific control loop. However, it should be understood that there is al¬ ways interaction with other control loops. Whether this can be disregarded or not (i.e. to what extent can the individual control loops be considered independent on the rest of the plant), must be decided with the aim of the investigation in mind. For approximate calculations it is generally possible to consider the loops as decoupled. To provide an insight into the effects of interaction, a signal flow diagram of the entire plant will be discussed in section 8.4. As regards graphic representation, the following general comment applies: In order to make the diagrams more vivid, the lines of action are marked by the respective physical variables, such as pressure, temperature, etc. In order not to overload the signal flow diagrams by too many blocks, another simplification is used: Whenever possible, pure gain amplifications (steady state gains, proportionality factors) are not represented by inde¬ pendent blocks, but are appended to the neighbouring time behaviour blocks. For example, a block with a first order lag is characterised not only by its time constant T, but also by the steady -state gain K. 8.3. 1 Steam Pressure Controlled System in a Drum Boiler Fig. 90 shows the signal flow diagram of a controlled steam pressure system in a drum boiler. For this example, pulverised coal firing with direct firing mills has been chosen, so that feeder speed n would appear as the control variable. Blocks 1, 2, and 3 represent the firing equipment. The symbol mK indicates the pulverised coal flow that reaches the furnace. Block 1 symbolizes the transportation lag, block 2 the effect of storage in the mill. If faster beater wheel mills are involved, a single 1st order time lag is generally adequate. With large inertia mills it is, under some circumstances, necessary to add another lag. Block 3 reflects the influence of a change in the mill air flow VLP on the pulverised coal discharge. Block 4 represents the conversion of 5 signifies mK into the heat flow Q (i.e. into heat release), while block the delay of heat transfer into evaporator tubes. Since the heat flow which arrives at the inside of the tubes, causes an almost immediate change in steam production, it is possible to equate the signal at the output of block 5 with the produced steam flow rhe. The blocks 6, 7, and 8 describe the economiser. In the first instance, the firing affects the water temperature at the economiser outlet (represented by blocks 6 and 7), the steam production being influenced only subsequently. 140 8 Boiler Control 8.3 Signal Flow Diagrams of Controlled Systems "B i generally insignificant, and can be neglected. Besides, the storage capacity of the superheated steam is small in comparison to the storage capacity of the evaporator part. This makes it possible to combine the storage capacities and to represent them by a single block. It also leads to a simplified signal flow diagram according to Fig. 91. Note, however, that in this diagram oil firing and not pulverised coal firing is assumed. Fig. 91 Fig. 90 Signal flow diagram of a steam pressure controlled system in a drum boiler with forced withdrawal of steam (with a load controlled turbine). Block 8 characterizes the change in the economiser outlet temperature caused by variations of the feedwater flow ms. The representation of the economiser shown on Fig. 90 is valid only when there is no evaporation. If the boiler has an economiser with evaporation, blocks 6, 7, and 8 must be replaced by a structure corresponding to an evaporator with a fixed evaporation end point (see Fig. 97). Blocks 9, 10, 11, and 12 simulate pressure dynamics, i.e. the conversion of the produced steam flow me into the output pressure P, under the assumption of a forced withdrawal of steam (as is always the case with modern units with an active turbine). The storage capacity of the water in the evaporator and in the drum area, which is capable of boiling, the storage capacity of steam, and that of the metal masses, is represented by block 9, while the storage capacity of the superheated steam is denoted by block 12. The pressure drop between the drum pressure PK and the steam outlet pressure P is reproduced in a linearised form by block 10. The block 11 reflects the delaying effect of the metal masses, the so-called thermal inertia. The steam flow withdrawn from the turbine, mD, becomes the disturbance variable. For approximate calculations a further simplification of the above signal flow diagram is possible. The effect of the economiser (blocks 6, 7, 8) is 141 Signal flow diagram of a controlled steam pressure system in a drum boiler with forced steam withdraval (e.g. via a load-controlled turbine). Since the oil flow riiQ follows the correcting action of the control valve practically without delay, it is possible to use mg directly as the control variable. In the case of pulverised coal firing blocks 1, 2, 3 from Fig. 90 would, naturally, have to precede block 1 in Fig. 91. In other respects, block 1 corresponds to block 4 and represents the heat release, while block 2 corresponds to block 5 and implies the time delay accompanying the heat flow through the tube walls. Block 3 is the con¬ centrated storage capacity, and block 4 corresponds to a combination of blocks 10 and 11. An attempt at a precise calculation of the characteristic values for the in¬ dividual blocks from the design data is almost always accompanied by serious difficulties. These have their origin in the complexity of the com¬ bustion process, in the intricacy of the heat transfer conditions, as well as in the need to use a very demanding computing procedure. An explanation of the pertinent computing methods must be left to specialised literature, and cannot be made the subject of this book. On the other hand, an effort will be made to present recommended values and guide figures, as well as formulae leading to approximate values which have proved useful in the calculations of practical problems. Blocks 1 to 4 in Fig. 90, and block 1 in Fig. 91, are not to be determined by approximate formulae. As will be shown later, it is more expedient to establish the respective characteristic values through the application of 8 Boiler Control 142 guide values for the total effective dead time Tu. Block 2 in Fig. 91 is characterised by the time constant Tq which can be approximately calcu¬ lated as follows: ,14) 8.3 Signal Flow Diagrams of Controlled Systems where 10 8(eJ-©J) or <>5> Formula (14) is recommended if heat is transferred primarily by radiation, formula (15) is recommended if radiation and convection participate in the same order of magnitude. In the latter case it is necessary to insert for aa a replacement heat transfer coefficient which can be obtained from the heat flow transfered into the tube and the mean temperature difference between the combustion chamber and the tube. The meaning of the individual symbols is as follows: Ce specific heat of iron mE iron mass of the evaporator !?e ©E mean tube wall temperature of the evaporator $g saturated steam temperature 0p absolute furnace temperature C radiation coefficient (evaporator/furnace) Fa effective outer heating surface of the evaporator (tube/flue gas) Fi inner heating surface of the evaporator (liquid/tube) aa a, outer heat transfer coefficient for the evaporator (tube/flue gas) absolute mean tube wall temperature of the evaporator m PK0 drum pressure mi —mo (17) S = ÿK1 - pK2 This calculation method is somewhat time consuming, and is therefore used only with a computer. For estimates it is sufficient to use approxi¬ mate methods, two of which will be described below. Using any one of these methods it is necessary to have a clear idea as to the location of storage. For this purpose, there are three distinct areas in a boiler to be distinguished: The water space (from the entry of feedwater practically to the beginning of boiling), the boiling space (space filled with water/ steam mixture at saturation temperature), and the superheat space. The water space contributes to the storage (i.e. accumulator) capacity only insignificantly. On the other hand, a very important share comes from the boiling space, the contributing components being the water heated to boiling point, the saturated steam, and the iron mass. In addition, superheated steam also provides a certain contribution. The total storage capacity is therefore composed of: inner heat transfer coefficient for the evaporator (liquid/ tube) Ts=SPko n umax storage capacity (accumulation capacity) of the boiler The storage capacity of the boiler, S, denotes the mass (in kg) of steam released during a pressure drop of 1 bar, and is usually given in kg/bar. There are several methods for the calculation of this parameter. In the exact method, the content of the working medium in the total tube system, is determined, under constant heating, for two pressures PK1 and Pk2- In practice, the respective contents, m.\ and m2 , can be obtained by first determining the density of water or steam as function of the tube length, and then integrating it with respect to this length. The storage capacity can then be calculated from: Block 3 is an integral element, and is, accordingly, defined by the integral action time constant: (16) S maximum steam flow mn Umax «>£->*> 2 To = 143 (18) Syi storage capacity of boiling water Sy2 storage capacity of saturated steam SE SD storage capacity of the iron masses in the boiling space storage capacity of superheated steam S = SV1 +SV2 +(Se)+Sd- mr 144 8 Boiler Control The average capacity SE of the iron masses was put into brackets to indi¬ cate that both accumulation and release of the iron storage heat are affected by time delay. The decision on whether SE is to be considered or not depends on the problem to be solved. The following equations are used for the calculation of the individual 8.3 Signal Flow Diagrams of Controlled Systems 145 VE ~ one half of the volume of iron of the evaporator, in addition to 1/3 of the volume of the iron of the drum in drum boilers. The factors required for the multiplication of the individual volumes in order to obtain storage capacities, are calculated as follows: components: (19) SVi = a VVl (20) SV2=0.VV2 (22.1) • a = 3p' n dP PO SE =y-VE (22) SD =8- VD. (22.3) 3P 3l?s pe 7 = dP volume of saturated steam Vq volume of superheated steam volume of water at boiling temperature 3P r0 p'o ' r0 II / PO ~ Po (22.4) 5 = ÿ PO r0 p'o r0 ÿ Ceo r0 (with minimum superheat) 3P PmO PO (the more superheated the steam, the better the approximation) volume of iron in the boiling space r kg ] Lm3- barj 6 If no details about the above volumes are known, the following values can be used as first approximations: Tyj ~ in forced-flow once-through boilers, approximately one half of the volume of the evaporator; ss in drum boilers, approximately 2/3 of the volume of the evaporator, plus 1/3 of the volume of the tubes feeding the drum, plus 1/4 of the water content of the drum; I 5 \\V U \;\ 3 2 V"V2 = in forced-flow once-through boilers, approximately one half Y a 1- P of the volume of the evaporator; % II 1 p0 - PO ' 3Pn where VVi VV2 VE II / PO ~~ PO ÿ 3P (21) II p0 - PO dh" p0n + - tip 1 3/1 0 in drum boilers, approximately 1/3 of the volume of the evaporator, plus 2/3 of the volume of the tubes feeding the drum, plus the steam volume in the drum; Fig. 92 10 Kiefenz Evaporator storage characteristics. 146 8 Boiler Control 8.3 Signal Flow Diagrams of Controlled Systems The coefficients ot,fS, and 7 depend purely on steam pressure, and can be presented in the form of a diagram, as shown on Fig. 92. For higher pres¬ sures, the calculation of the coefficients is no longer accurate enough, and the storage capacity should be calculated by the method mentioned first. With superheated steam the storage capacity depends also on steam tem¬ perature. For this reason it is recommended to use a step-wise approach, an average density pm being applied in the individual steps. The symbols used in equations 22.1 to 22.4 have the / p II following meaning: density of water at boiling temperature 104 (24) S= 147 kg t/h Pk 0,38 kg/bar t/h mr In drum boilers, the main location of storage capacity is the evaporator and the drum. The superheated steam does not generally contribute more than 10 to 20% of the total. This contrasts with forced-circulation oncethrough boilers where storage capacity of superheated steam amounts to approximately one half, and with high-pressure boilers where it amounts to even more than one half of the total storage capacity. In conclusion, attention will be drawn to a condition which can make the calculation of storage capacity rather problematic, particularly in forcedflow boilers fired with a mixture of fuels. The problem arises with the position of the fire in the furnace. Generally, following a change in fuel -constituents, particularly if they are as dissimilar as coal and gas, a shift of the fire is most difficult to avoid. This is unfortunate since the shift tends to be accompanied by a change in the length of the evaporator (in forced-flow boilers). Thus in spite of a constant boiler load, a change can take place in the storage capacity, as well as in the time behaviour of the p density of saturated steam Pm average density of superheated steam Pe density of iron H h" enthalpy of water at boiling temperature r latent heat P steam pressure system. saturated steam temperature In general, in fixed pressure boilers, storage capacity is dependent on load only to a small degree. On the other hand, the dependence can be quite substantial in variable pressure plants. CE enthalpy of saturated steam specific heat of iron The second, and somewhat less accurate, method is recommended when there are virtually no design data available, and at least roughly approxi¬ mated estimates would be of help. However, it applies only to forced-flow boilers, and is based on an equation derived from the averages of many measured and calculated values of the past. It is as follows: The last block in the signal flow diagram on Fig. 91 still to be considered is block 4. It was formed by a combination of blocks 10 and 11 of Fig. 90. Block 10 characterizes the delayed storage caused by thermal inertia. The respective gain of the proportional element can be calculated in a dimensionless form from: rth »?D0 SK ' p0 ' (23) 8-fc±-W (24.1) •<„. A similar formula has been derived for drum boilers (Equation (24)). However, due to differences in circulation there exists an even greater degree of uncertainty as to its accuracy. *th = where Tth is the thermal inertia that can be calculated by equation (26). Block 11 reflects the pressure drop in the superheater. This, of course, changes with the square root of load, but for simulation it is often quite adequate to linearize the parabola for the load range under consideration. 10* 148 8 Boiler Control ,"-r*ik. For block 4, the proportional oontrol factor can be obtained by adding the proportional control factor for block 10 to the reciprocal value of the factor for block 11. P Am 8.3 Signal Flow Diagrams of Controlled Systems time response is obtained with pulverised coal firing using direct firing mills with a constant mill air flow. type of firing oil or gas firing a) Transient response to a change in the control variable Amn b) Transient response to a change in the disturbance variable. Fig. 93 149 Tu[ s] 5. . 10 pulverised coal firing, bin storage system 20 . . 30 pulverised coal firing, direct-fired system, mill-air feedforward control 20 . . 30 pulverised coal firing, direct-fired system, no feedforward control 30 ... 60 Transient responses (step responses) of the steam pressure controlled system. In conclusion, some comments will be made on transient responses, and selected guide values will be stated. Fig. 93 shows under a) the transient response to a change in the control variable, i.e. the development in time of the pressure P following a step change of the fuel flow mB. Under b) is shown the transient response to a change in the disturbance variable, i.e. the development in time of the pressure P following a step change of the steam flow mD .The transient response to a change in the correcting or manipulated variable (a) is characterised by the effective dead time Tu as well as by its integral ascent which is in turn a function of the storage capacity S. The constant K re¬ presents the static relationship between the fuel flow and the produced steam flow. The magnitude of the effective dead time Tu depends very much on the type of fuel and on the type of firing, as can be seen from the following table containing some guidance values. The shortest effective dead times can be achived with oil and gas firing, while the most sluggish Naturally, a considerable influence is borne by the type of mill used. The lower values indicated in the table can be achieved with high-speed pul¬ verizers where the circulation between the mill and the classifier results in only a small accumulation of material. In slag tab boilers effective dead times of 50 seconds and more must be assumed. With the help of the above guide values it is now possible to determine the still missing time constant of the firing process, which is needed for pre¬ liminary calculations of control processes. To this effect, the already cal¬ culated blocks are simulated on an analogue computer, the basic arrange¬ ment being supplemented by block 1 (see Fig. 91). The time constant is then varied so long as the effective dead time differs from the recom¬ mended figure. The process stops when the guide value is reached. If the applied signal flow diagram corresponds to Fig. 90, the process for deter¬ mining time constants of blocks 2 and 3 is the same. The estimate of the dead time for block 1 corresponds quite well to the time needed for the transport of coal from the feeder into the furnace. \ 8.3 Signal Flow Diagrams of Controlled Systems 8 Boiler Control 150 Listed below are a few reference values for the storage capacities of in¬ dividual boiler types. boiler type S [kg/bar] drum boiler 130 .. . 180 Ts[ s] 15 1 variable size and the shifting of the evaporator. Fig. 94 shows the respec¬ tive signal flow diagram, where pulverised coal firing is assumed. Blocks 1, 2, and 3 represent the firing equipment. These blocks have been already described in sub-section 8.3.1 together with block 4 (heat release) and block 5 (heat transfer into tubes). 150 bar; 500 t/h dmm boiler 250 .. . 300 140 ... 250 170 bar; 1000 t/h drum boiler 195 bar; 1900 t/h % once-through boiler 60 ...80 600 ÿIP- 190 bar; 500 t/h once-through boiler 140 .. . 180 60 . .. 130 200 bar; 1000 t/h once-through boiler Fig. 94 Signal flow diagram of a steam pressure controlled system in a Benson boiler with forced steam withdrawal (e.g. via a load-controlled turbine), and including the effect of feedwater. 150. . . 180 210 bar; 1800 t/h The above values show only the order of magnitude. For dynamic analysis it is recommended to calculate the storage capacities by one of the methods given earlier on. References: [6] [12] [19] [83] [94] [97] 8.3.2 Steam Pressure Controlled System in a Benson Boiler The signal flow diagram of a Benson boiler differs from the diagram of a drum boiler primarily in two points. Firstly, the role of the feedwater flow is vital, and secondly, additional storage processes occur due to the Block 6 stands for the economiser, and reflects the delaying effects of the feedwater flow rh$, or the heating Q, on the starting point of evaporation Xy3. The evaporator is simulated by blocks 7, 8, 9, and 10. In this group block 8 represents the dynamics of the action of the feedwater flow changes and of the heating changes on the length of the evaporator, AXy. Simultaneously, block 9 reflects storage processes during the shift of the starting point of evaporation. Furthermore, in blocks 8 and 9, both transient responses which are in themselves rather complicated, are approximated by straight lines. The development in time of the evapo¬ ration end point Xye is obtained by adding up the signals for the eva¬ poration starting point and the evaporation length. Block 11 displays the storage capacity of the evaporator, block 12 the delayed storage process caused by thermal inertia, block 13 the pressure drop at the superheater, and block 14 the storage capacity of the superheated steam. 152 153 8 Boiler Control 8.3 Signal Flow Diagrams of Controlled Systems As in previous examples, the signal flow diagram is designed for the typical case of forced steam withdrawal. The controlled system is without selfregulation (astatic), i.e. following a change of the feeder speed n and feedwater flow ms, the outlet pressure P does not tend towards a new stationary value, but continuously moves away from its original condition. In other words, the outlet pressure is proportional to the integral of the input signal. The same happens when the steam outflow mD is changed during a con¬ stant feed supply and constant feedwater flow. value of the time constant is determined in order to satisfy the guide value for the effective dead time Tu (see the respective table). As regards block 2, the equation for the time constant Tq was also given in sub-section 8.3.1 (Equation (15)). The expression of the delay denoted by block 3 is based on the fact that the volume of the evaporation zone changes with varia¬ tions of the feedwater flow, or with the heating. It is evident that in this case the storage process is mechanical, and it is possible to use equation (25) to approximate its time constant Tw: If it is possible to disregard the influence of the economiser, i.e. of the shifting of the starting point of evaporation, the presentation can be simplified. Further, the non-linear block 8 can be replaced, in the interest of easier manipulation, by a linear element. These changes lead to the signal flow diagram on Fig. 95, which is, in order to provide some variety, again conceived for oil firing. Blocks 1 and 2 correspond to blocks 4 and 5 in Fig. 94. Block 8 is replaced by the two blocks, 3 and 4, each of the two representing a 1st order delay. In contrast to the drum boiler, blocks 5 and 8 (corresponding to blocks 11 and 14 of Fig. 94) cannot be combined, since in a Benson boiler the evaporator storage (block 5) is not substan¬ tially larger than the superheater storage (block 8). The characteristic values of the individual blocks of Fig. 95 can be ob¬ tained from design data in the following manner: ÿ Tw = (v -v') m (25) " where V volume of the evaporator v' spec, volume of saturated water v" spec, volume of saturated steam m mass flow of the water/steam mixture (boiler load) The second delay simulated by block 4, is caused by thermal storage in the iron mass, where local changes of the evaporation process, namely the change of volume and the shift of the evaporation zone, cause temperature changes. The corresponding time constant Tth can be calculated from: mt CC • »l£ 7th = Cp (26) • m where Fig. 95 Signal flow diagram of a controlled steam pressure system (incl. the effect of feedwater) in a Benson boiler with forced steam withdrawal (e.g. via a load-controlled turbine). The time constant characteristic for block 1 (equivalent blocks for coal firing are blocks 1 to 4 in Fig. 94) can be expediently established by the method already described in sub-section 8.3.1 for drum boilers. Here the CE spec, heat of iron in the evaporator mE mass of iron in the evaporator cp spec, heat of the mixture steam/water Block 5 is determined by the integral action time constant T$ i- Ana¬ logically to the time constant T$ (see equation (16)), Tsi is determined by the following equation: 8 Boiler Control 154 Sv PkO ' TS1 = (27) ™D0 8.3 Signal Flow Diagrams of Controlled Systems 155 Finally, part (c) shows the transient response to a change in the steam flow that is withdrawn from the boiler, this being a disturbance variable. The curve shows the same PI character as was the case in drum boilers. where ÿSv = Svi + Sy2 + SE storage capacity of the evaporator Pk0 pressure in the evaporator mD0 maximum steam flow a) Transient response to a change in the correcting variable (fuel flow), with feedwater flow constant. A similar equation is used to calculate the integral action time constant for block 8, namely »B=ms (28) TS2 = SDP Am 3 = Amg ™D0 ' U-Tu where . SD storage capacity of the superheated steam P outlet steam pressure The calculation of the various storage capacities has been dealt with in detail in sub-section 8.3.1. Blocks 6 and 7 are equivalent to blocks 10 and 11 in Fig. 90, and have already been explained there. The various resulting transient responses are displayed in a qualitative manner on Fig. 96. Part (a) shows the development in time of steam pres¬ sure, following a step change in the fuel flow (accompanied by a correspnding change in the air flow). In contrast to the pertinent function for a drum boiler, pressure in a Benson boiler tends to reach a new stationary value. The reason for this being that since the feedwater flow has not changed, there cannot be a continuous production of extra steam. A tem¬ porary increase of the mentioned parameters just tends to shift the level of pressure. Only a fuel flow adjustment accompanied by a feedwater flow adjustment can result in a lasting change in the produced steam flow mE, while the steam pressure exhibits integral characteristics (see Fig. 96b). The step response is characterised by the effective dead time Tu and the storage capacity S (for guide values see the relevant tables in sub-section 8.3.1). b) Transient response to a change in the correcting variable (fuel flow), with a simultaneous change in the feedwater flow. Amp VLi Fig. 96 s c) Transient response to a change in the disturbance variable (steam flow). Transient responses of a steam pressure controlled system in a Benson boiler. References: [2] [6] [19] [21] [58] [70] [72] [75] [79] [83] [95] [102] [154] [163] [167] 8.3.3 Steam Pressure Controlled System in a Sulzer Boiler As in a Benson boiler, the adjustment of the feedwater flow in a Sulzer boiler plays a very important role, and, therefore, must be taken into account in the signal flow diagram of the steam pressure control system. 1 8.3 Signal Flow Diagrams of Controlled Systems 8 Boiler Contro I 156 A further complication is caused by the existence of the water separator which, as already explained, fixes the evaporation end point so that not only steam me but also water mSa leave the evaporator. 157 Blocks 11, 12, 13, and 14 have already been explained in detail in sub¬ section 8.3.1. Block 11 represents the storage capacity of the evaporator, block 12 the delay in storage due to thermal inertia, block 13 the pressure drop in the superheater, and block 14 the storage capacity of the super¬ heater. The signal flow diagram is again conceived for a forced withdrawal of steam, i.e. when the turbine operates with load control. Typically, the disturbance variable % corresponds to a change in the steam flow being mAb Sa withdrawn. 1= x Va mD Fig. 97 Signal flow diagram of a steam pressure controlled System (inclusive of the effect of feedwater) in a Sulzer boiler, with forced steam withdrawal (e.g. via a load-controlled turbine). The individual relationships can be observed in the signal flow diagram on Fig. 97. Oil firing was assumed, thus making the oil flow mQ the correcting (or manipulated) variable. Block 1 once again denotes the heat release, and block 2 the heat transfer into tubes. Block 3 simulates the delaying in¬ fluence of the economiser on the shift of the evaporation starting point Xya. Blocks 8 and 9 indicate the rather complicated time behaviour (here represented by straight lines) of the evaporator in relation to the shifting evaporation starting point. Block 8 represents the influence of the evapo¬ rator on the separated water flow mSa, while block 9 specifies its influence on the produced steam flow rhe. Blocks 4 and 5 show the time behaviour of the evaporator with respect to feedwater flow changes ms, blocks 6 and 7 show the same with respect to changes in the heating, Q. Block 10 is a pure integrator and simulates the time behaviour of the level in the sepa¬ rator in response to changes in the separated water flow msa and in the blow-down water flow mAb- With a Sulzer boiler a simplification of the steam pressure control system diagram is naturally even more difficult than it was with a Benson boiler. However, for a rough approximation it is possible to consider the following points: It can be accepted that feedwater flow and fire (heat input) are controlled by the control system concurrently. If this is so, then the in¬ fluence of the shift of the evaporation starting point can be disregarded. In addition, blocks 5 and 7 complement each other, so that steam pro¬ duction can start without delay. All this leads to the thoroughly simplified signal flow diagram displayed on Fig. 98. However, the diagram is useful, as has already been made abundantly clear, only for very approximate estimations. The calculation of the characteristic values for the individual blocks from design data has already been fully dealt with in the preceding sub-sections, and will not be repeated. Fig. 98 Simplified signal flow diagram of a steam pressure controlled system in a Sulzer boiler, with forced steam withdrawal. When calculating characteristic values for the blocks of Fig. 97, it is re¬ commended to consult specialized literature. The transient responses to 8 Boiler Control 8.3 Signal Flow Diagrams of Controlled Systems changes in the correcting and disturbance variables appear to correspond to those indicated in Fig. 96b and 96c. Block 1 is a first order delay, and represents the effect of a steam flow disturbance on the outlet steam temperature. Block 2 is also a first order delay, and simulates the consequences of a fire disturbance. Block 3 shows the relationship between the inlet and the outlet temperature. This lastly mentioned transient response is a rather complicated high order function the character of which very much depends on the design of the superheater. 158 References: [6] [25] [58] [72] [75] [79] [83] [97] [149] 8.3.4 Steam Temperature Controlled System 159 1 When considering systems for steam temperature control it is not necessary to differentiate between a superheater and a reheater. The signal flow dia¬ grams as well as the formulae presented in this sub-section apply, therefore, in like manner to any kind of heater. The basic signal flow diagram is dis¬ played on Fig. 99. The superheater outlet steam temperature to be con¬ trolled is marked t?a. The variables that influence this outlet temperature are the steam flow mD, the heating Q, as well as the inlet temperature i?e. In general, mD and Q are disturbances, while $e is a correcting variable since it can be changed by attemperation water flow. Unfortunately, the signal flow diagram in the form it is presented here is not particularly suitable for computer simulation. Fig. 100 Simplified signal flow diagram of a steam temperature controlled system (superheater). Fig. 101 shows a multitude of possible transient responses. Two characte¬ ristic values distinguish the transient response pertinent to a superheater: The factor xD fixes the form of the function, while TR determines the time scale. The two factors are defined as follows: aiÿi (29) cD ' mD ' IZI Fig. 99 Signal flow diagram of a steam temperature controlled system Tr=!ÿ) Fj (30) x aj • where (superheater). Should one wish independently to examine either a steam flow disturbance or a heating disturbance, difficulties might arise with reaching limits in the integrating block. Fortunately, this awkward situation can be overcome by changing the diagram to a simplified form. Fig. 100 represents a good approximate solution in this respect. Note that since dead time (which is the time needed by the steam to pass through the superheater) is insigni¬ ficant in comparison to other delays in the system, it is ignored in Fig. 100. ttj inner heat transfer coefficient (tube/steam) F\ inner tube surface Cq spec, heat of steam Ce spec, heat of tube material rhD steam flow iron mass of the superheater 160 8 Boiler Control 8.3 Signal Flow Diagrams of Controlled Systems 16 1 In general, superheaters show xD factors between 6 and 12. As regards their time behaviour, there are several possibilities of simulation. In this respect, a connection in series of n 1st order delay elements with identical time constants, has proved adequate. Fig. 101 Standardized transient responses of superheaters. Once the two characteristic values, the form factor and the time factor, are calculated from the design data, the transient response can be derived from Fig. 101. r-o,5 -1000 o i T< Fig. 102 Standardized transient responses of superheaters. Should the time standardization be based on (31) Tsr - Tr *D (32) Tsr - cD tnD Fig. 103 Diagram for determining characteristic values for a superheater simulation. ' n CE ' mE Tu • T then the difference between the individual time functions would become even more pronounced, as can be seen from Fig. 102. Tr XD 11 Klefenz number of 1st order elements effective dead time build-up time time constant of the 1st order elements time factor for standardization form factor 8. 3 Signal Flow Diagrams of Controlled Systems 8 Boiler Control 162 The required number (n) of the elements, as well as the value of the com¬ mon time constant T can be obtained from the diagram on Fig. 103. The procedure is as follows: The calculated value of xD is used to find the relationship Tu/TR (which is the standardized effective dead time) using the curve in the lower part of Fig. 103. Since TR is also known (see Equa¬ tion (30)), Tu can be directly calculated. The curve in the upper part of Fig. 103 is then used for finding the number n of the 1st order elements (left-hand side ordinate, rounding-off required), as well as the ratio Tu/T where Tu is again the effective dead time, and T the time constant to be found. Since Tu has already been calculated, T can be also determined. The ratio Tu/Tg (= effective dead time vs. build-up time) which approximately characterizes the transient response (see Fig. 104), can be established on the right-hand side ordinate. At the same time, the gain in the equation (34) can be calculated from lis 40 = ÿ= (35) - It can be seen that the gain is equal to the warm-up span of the super¬ heater. The index 0 marks the stationary state before the disturbance occured. The disturbance time constant can be obtained from the transition time TzQ ' and the gain qz . Tzq = (36) with the transition time and the gain defined by _ CE mE zq - k. F m (37) i ' ÿRmO ~ flmO 1 Glted 1: (38) rL Fig. 104 Characteristic values for a superheater simulation. V, = * = ÿeo * flaO The meaning of the symbols is as follows: In all the considerations, up till now the gain has been assumed to equal one. This is to a certain extent correct. However, a more exact figure can be obtained from the ratio of specific heats at the input and output of the superheater: (33) fjj ÿ . = Ce specific heat of the tube material mg mass of iron in the heated part of the superheater, inch relevant headers and tubes upstream of the temperature measuring point k heat transfer coefficient (flue gas/steam) F effective heating surface (outside surface) Subsequently, only transient responses to disturbances will be considered (see Fig. 100). To this effect, the following calculations are needed: i?Rm0 mean flue gas temperature in the superheater area #mo mean steam temperature in the superheater Block 2 demonstrates the time behaviour of the outlet temperature following a change in the heat flux Q. This can be represented accurately enough by a 1st order delay with the transient response given by i?a0 #eo temperature of steam leaving the superheater (34) 163 Ai3a(s) lÿZO —— = -ÿ1 + Tzq « 4g(s) ÿ temperature of steam entering the superheater Finally, block 1 simulates the reaction of the outlet temperature to changes in the steam flow mD ,which in this case are disturbances (see Fig. 100). 11* 164 8 Boiler Control 8.3 Signal Flow Diagrams of Controlled Systems For approximation the actual time behaviour can be replaced by a first order delay: velocity, the following dependences on boiler load, i.e. on the steam flow mD, can be formulated: (39) ÿZnio Atfa(f) 1+ a«dW rZniD (43) ' ÿf The gain (40) (44) 1 V,ZmD AmD/niD0 is calculated from the difference between VZQ and the gain obtained from the static superheater characteristic (shown on Fig. 105): (41) VZ mD VZQ ~ ™D0 ~ • (\Omj) ) / mD0 "DO moo) I/mD_|-0,2 lB_ = Tro Udo / 1D_= 165 8 Equation (43) shows that * d > ar|d, as a result, also the ratio Tu/Tg slightly decreases with increasing load (see Fig. 103). At the same time, according to equation (44) the time factor TR decreases with increasing load quite and TR the significantly. Because of the simultaneous decrease of effective dead time Tu changes almost proportionally with the inverse of load: (45) ™. Tu0 md The load dependence of the disturbance time constant can be expressed with sufficient accuracy by: (46) Fig. 105 Static characteristic of a superheater. The disturbance time constant can then be calculated by equation (42): (42) T_ .u — CE — 1Zmn - • CD ' '«D It should be pointed out that the gain has been established as a positive value. A raise in the steam flow is, however, accompanied by a decrease of the outlet temperature. All this has been taken into account in the signal flow diagram shown in Fig. 100 by the introduction of a minus sign at the appropriate summation point. (A variable having a minus sign goes through with a sign reversal.) It follows from the various equations that the transient response of a superheater to changes in both correcting variables and disturbance variables is determined by the characteristics y-u and TR. Considering that the heat transfer coefficient cq changes with 0.8 power of the steam f*TZO - mD For disturbances of the steam flow, the relationship given by equation (46) follows directly from equation (42). As to the corresponding time constant for firing disturbances, it should be noted that the heat transfer coefficient changes with 0.65 power of the flue gas velocity, and that, on top of that, the gain increases with rising heat supply. It has been already mentioned in sub-section 8.2.4 that in most cases temperature is controlled by an attemperator located upstream of the superheater. It follows that the signal flow diagram on Fig. 100 should be complemented by the inclusion of a simulation of such a cooler. Since its very modest time delay can be disregarded in comparison with the rather inert behaviour of the superheater, it is necessary to consider only the various gains. The designations used in the following equations are based on Fig. 106. The process gains which relate changes in the attemup¬ peration spray water flow mE , as well as in the steam temperature stream of the cooler, to the steam temperature t?2 downstream of it, can be calculated as follows: 8 Boiler Control 166 (47) (48) v aÿ2 ——— = AmE/mE0 Al?l -- 8.3 Signal Flow Diagrams of Controlled Systems i '"EO ' (*20 - *E0> cp2 ÿ 167 :-, m2o cp2 ' "*20 The letter h denotes enthalpy. The index 0 again refers to the original state. The gain in the equation (47) is specified in grad Celsius per % change of flow, while in the equation (48) it is expedient to express it in grad per grad. It would cause no difficulties should the need arise to write down the gains in a completely dimensionless form. This could be done by referring the values to the temperatures #i0 and i>2o- If there are considerable masses of iron between the attemperator and the superheater, for instance in the form of connecting pipes and headers, then it is necessary to provide still another delay element. Fig. 107 Simplified signal flow diagram of a steam temperature controlled system (superheater). Blocks 3.1 to 3.n simulate the time behaviour between the inlet and the outlet temperature, in accordance with the method already described in connection with Fig. 104. The superheated parts between the cooler and the superheater inlet are reproduced by block 4. m2 CP2 *2 ÿr m, -• --Tzq — Fig. 106 Attemperator. -TZÿd*1 The calculation can be performed with the help of equations (29) and (30), and using Fig. 101. In general, what will be produced is a transient response corresponding to ÿo-values between 0.5 and 1.0. Complementing the signal flow diagram of Fig. 100 with all that has been mentioned since, would result in Fig. 107. The blocks 1 and 2 again demonstrate the effect of changes in steam flow and in heating on the outlet temperature i?a. Fig. 108 Transient response of a steam temperature controlled system. a) Transient response to a change in nig (= correcting variable). Transient response to a change in bj (= disturbance variable). b) Transient response to a change in Q (= disturbance variable) c) Transient response to a change in nig) (= disturbance variable) 168 8 Boiler Control The proportional control factor determined by equation (48) is displayed as block 5, while that calculated by equation' (47) as block 6. The next point for discussion are the transient responses to correcting and disturbance variables, illustrated by Fig. 108. The transient response to a change in a correcting variable is presented in part a). It indicates the development of outlet temperature i?a resulting from a step change in the attemperation water flow mg .The response is characterised, as already explained, by the effective dead time Tu and the build-up time Tg. If the superheater is well designed from the dynamic point of view, Tu equals approximately 30 seconds, while the approximate value for Tg is 150 se¬ conds. However, it should be noted that neither Tu nor Tg can be directly measured. This is due to the non-negligible time constant of the temperature sensors, which amounts to some 20 seconds and is caused by the required heavy pocket for steam temperature measurements. Na¬ turally, time constants of this magnitude would considerably distort the establishment of the transient response. Such has not been the case with the previously discussed transient responses, where but for the exception of temperature measurements it is generally not necessary to take into account the time constants of the primary elements (sensors for the measurement of pressure, flow, level, etc.). Consequently, if either meas¬ urements are to be evaluated, or any dynamic investigations performed, the signal flow diagram according to Fig. 107 must be supplemented so as to incorporate the effect of the time delays in the temperature sensors. For this end, a delay element of the 1st order is inserted behind the signal position !?a ; its output then corresponds to the measured outlet tempera¬ ture. Of course, the measuring point for the inlet temperature i3e must be treated in the same manner. As to its location, the first order delay ele¬ ment must not be placed directly into the signal path leading to block 3.1;its place is in a separate signal path branch leading from i?e. 8.3 Signal Flow Diagrams of Controlled Systems already mentioned superheater with dynamically favourable ÿZQ lies between 100 and 130 seconds. Part b) shows the transient response to a disturbance of the heating, QThe outlet temperature changes, with good approximation, in conformity with a 1st order delay characterised by the time constant TZq. For the characteristics, Part c) follows to show the transient response following a change of the steam flow % (= disturbance). With the exception of the sign, the develop¬ ment of t?a is very similar to that resulting from a disturbance of heating. Even the time constant has approximately the same magnitude as Tzq. However, it would be wrong to conclude that, since during a load adjustment both heating and steam flow change, there would be practically no effect on steam temperature, and the positive and negative deviations would cancel each other. Changes in heating and in steam flow do not affect the superheater synchronously. As can be gathered from the signal flow diagrams, a considerable time delay exists between the change in the fuel supply and the change in the flow of heat, Q. Even should the fuel flow change instantaneously with the change in the steam flow (brought about by the turbine), Q would still act with a time delay; temperature changes are evidently unavoidable. On top of that, the steam pressure con¬ troller may temporarily over-control the fuel flow in order to re-fill the storage which had been partly depleted during load changes. Bearing all this in mind it should not be assumed that the effects of changes in heating and in steam flow can compensate one another. The final point to deal with concerns the approximate calculation of heat exchangers for temperature control. Attention has already been drawn to the two main control modes in sub-section 8.2.6. A controlled by-pass is either on the side of the steam the temperature of which is to be main¬ tained (see Fig. 84), or on the other side (see Fig. 85). Naturally, the signal flow diagrams differ accordingly. TzmD c3 Part a) of Fig. 108 also illustrates the time behaviour of the inlet tempe¬ rature !?e. It is easy to recognize a curve typical for low xD values. A possible disturbance by the temperature , which is the steam tempe¬ rature upstream of the attemperator, is also incorporated into part a); this is done for the simple reason that the transient response is the same as for a change of mE. 169 c *4 *2 2 / - / i TO I 1P, Fig. 109 Heat exchanger as a control element for temperature control. 170 8 Boiler Control Fig. 109 explains the notations used in the following text. The controller actsupon the three-way valve which affects the temperature i?3 by changing the distribution of the steam flow between the heat exchanger and the by¬ pass. The pertaining signal flow diagram is on Fig. 110. A slight change of the flow m through the heat exchanger varies, in the first approximation, the temperature i?2 at the outlet according to a 1st order transient reponse (block 1); the temperature drops as the flow rises. The temperature i?3 downstream of the mixing point is influenced in two ways: Firstly, i?3 changes with variations in $2 (the relationship is demonstrated by block 2), and, secondly, it changes with variations in the ratio of the "cold" by-pass steam flow to the "hot" steam flow through the heat exchanger. The last relationship is represented by block 3. Should the flow m passing through the heat exchanger increase, the by-pass flow would automatically decrease. The combined effect would cause an increase in i?3 . The time behaviour of the individual variables is shown on Fig. 111. 8.3 Signal Flow Diagrams of Controlled Systems ratio downstream of the mixing point. This makes such an arrangement particularly suitable for temperature control of reheat steam. The following equations can be used for approximating individual blocks in the signal flow diagram on Fig. 110: Block 1: A 02 A m/m0 = (49) _ O - "0 • («?20 ~ 1 n) ÿ20 - flip 1+ ÿ40 + ÿ50 ~ <?I0 - 0 20 Here m is the Nusselt exponent, which can be put approximately equal to 0.8. The time constant of the transient response is given by: (50) rp _ CE my. ' 2 cm m0 where Fig. 110 Simplified signal flow diagram of the heat exchanger displayed on Fig. 109. mE mass of iron CE specific heat of iron cm mean specific heat of heated steam mo flow of heated steam before change Block 2 : Ad3' _ c2 (51) Ai92 c3 where Fig. Ill Transient responses of a heat exchanger with by-pass according to Fig. 109. The very favourable time behaviour of temperature d3 in response to changes in m ,can be traced back to the immediate change in the mixing 171 Ci specific heat of steam downstream of the heat exchanger C3 specific heat of steam downstream of the mixing point Block 3 : (52) ' _ cm - (ÿ20 - i?i nl A mlm0 c3 8. 3 Signal Flow Diagrams of Controlled Systems 8 Boiler Control 172 173 The corresponding transient response is shown on Fig.l 14. A comparison with the transient response of the arrangement on Fig. 109 shows a less favourable time behaviour. The control action on temperature #3 is effec¬ ted with a considerable delay. m References: [1] [6] [16] [20] [23] [28] [32] [34] [36] [39] [40] [41] [42] [44] [45] [47] [48] [83] [91] [93] [96] [98] [99] [100] [101] [118] [150] for temperature Fig. 112 Heat exchanger used as correcting element control. via a heat exchanger is The second possibility of controlling temperature valve which three-way the upon shown on Fig. 112. The controller acts the control on dependence in changes the flow mH of the heating steam to tempe¬ is identical which deviation. This influences the temperature t?2 diagram flow signal simplified The rature #3 , and which is to be controlled. time the by characterised delay (Fig. 113) consists simply of one 1st order gain: following the by as well constant calculated in equation (50), as (53) Afl3 _ CHm ' mHQ - (ÿ40 - ÿ50) c3 ' m0 1ÿ heat exchanger Fig. 113 Simplified signal flow diagram of a according to Fig. 112. 8.3.5 Level Controlled System in a Drum Boiler The main problem in setting up a signal flow diagram for a level control¬ led system in a drum boiler can be found in the inhomogeneous contents of the evaporator and the drum. The filling consists of water at boiling temperature, pervaded by steam bubbles. Since the volume fraction of the steam bubbles is quite considerable, the mean specific weight of the contents is very strongly dependent on the proportion of steam. This, of course, means that the steam content also strongly influences the level in the drum. The steam content itself depends, in turn, on the load factor of the boiler, on the changes in feedwater flow, and on feedwater tem¬ perature. This is the reason for the famous phenomenon that in spite of an increased supply of water, the water level initially falls. The phenomenon can be traced back to the fact that part of the heat has to be used for heating up the extra feedwater, thus causing a decrease in steam content. This is followed by a temporary reduction of the total volume of the water/ steam mixture, accompanied by an ebb in the level. exchanger with Fig. 114 Transient response of a heat according to Fig. 112. by-pass from Fig. 112. The symbol cHm represents the The used notation is taken mean specific heat of the heating steam. In the case of an increase in fire output more water evaporates; the volume of steam increases, the water/steam mixture is driven out of the evaporator, and the drum water level temporarily rises. Fig. 115 shows the system under consideration. It consists of an economiser, a drum, and an evaporation/circulation system. The individual symbols have the following meanings: 8.3 Signal Flow Diagrams of Controlled Systems 8 Boiler Control 174 175 water flow, ms, and of the enthalpy downstream of the economiser, /ise, on the evaporation starting point, or on the length of the evaporator, AXV. Block 5 is the corresponding influence of heating on the length of the evaporator. A change in this length causes water expulsion out of the evaporator, the time behaviour corresponding to block 7. ms feedwater flow into economiser rhsz feedwater flow out of economiser mD steam flow out of drum Qe Qv heat flow into economiser L level in the drum ÿSE enthalpy downstream of economiser Pw pressure in evaporator ms heat flow into evaporator m0 h i Eco evaporator a drum boiler. Fig. 115 Plant scheme of a level controlled system in setting up a signal flow Two separate schemes must be distinguished when which is the .scheme first diagram for a controlled level system. In the the boiling to up standard one, water is not heated in the economiser supercolled less or more a in point, and, therefore, is fed into the drum so much receiving state. The second scheme is based on the economiser As a boundaries. its within heat that partial evaporation already occurs economiser the at steam result, there is saturated water and saturated outlet. feed. Block 1 Fig. 116 demonstrates the first scheme, that of supercooled evaporator, the into flow heat Qv symbolizes the relationship between the the establishes 2 Block and the water expelled from the evaporator, niwvthe and , rhÿj drum, the into flow integral relationship between the water corresponding con¬ mass of water in the drum, tfVr- Block 3 denotes the effect of the feedthe reflect 9 version into drum level L. Blocks 4, 6, and Fig. 116 Signal flow diagram of a level controlled system in a drum boiler, with supercooled drum feed. Water expulsion can, of course, also be caused by pressure changes in the evaporator. This relationship is shown by block 8. Block 10 and 11 re¬ present the economiser, and reflect the time behaviour of the enthalpy downstream of the economiser, caused by changes in feedwater flow, in heat flow, into the economiser. or A substantially more complicated signal flow diagram arises when there is an economiser with partial evaporation. The complication is caused in this case by the necessity to take into account the effects of feedwater flow and heat flow on the flow of the saturated water leaving the econo¬ miser, as well as on the shift of the evaporation starting point. The corresponding blocks have already been described in connection with Fig. 97. The sum of the outputs from blocks 4, 6, and 8 forms the water 176 8 Boiler Control 8. 3 Signal Flow Diagrams of Controlled Systems flow downstream of the economiser, and becomes the input signal ms of Fig. 116. 177 Block 1 . (54) Kul =1 (55) Ku2 m0 1+0 T* mwT0 xa0 + 0 2 Vn (56) * (57) Tj.2 = U0 - V0 T' r Block 2: (58) Pv Fig. 117 Signal flow diagram of a level controlled system in a drum boiler, with supercooled drum feed. Kx rh(\ = - ™wT0 Block 3: (59) K3 =1 4 where one half of the dram diameter has been chosen as the related variable for the drum level. Blocks 10 and 11 can be dropped, since enthalpy downstream of the eco¬ nomiser corresponds to saturated water enthalpy, and, as a result, is con¬ sidered constant. For preliminary calculations it is recommended to start with the standard case, particularly because it has superior dynamic behaviour, and should therefore always be aimed at. For this purpose it is expedient to transform the signal flow diagram so that it will correspond to Fig. 117. In the transformed diagram blocks 9, 10, and 11 have been omitted since the influence of enthalpy down¬ stream of the economiser is of minor importance. On the other hand, blocks 1 and 7 have been split into two in order to facilitate their mathe¬ matical treatment. Individually, the blocks are calculated as indicated below, with the inputs and outputs being relative (i.e. per-unit) variables: Block 4: (60) K4 /in - h,sO ,l0 ~ /!s0 Block 5: (61) Ks h0 ~ fh0 »0 - 1ho Block 6: (62) 12 Klefenz rt6 kfr Z0 »»0 " v0 • 8 Boiler Control 178 8. 3 Signal Flow Diagrams of Controlled Systems Block 7: (63) lTUfji mass -ÿ7.2 — Zq T* I1 - Xa0 m0 2 mwTO FV0 (65) ÿ ( u0 ~ vo) ' ">0 In 1 ( -— +2 +ÿ ÿ \ xa0 + (1 - Xa0)l>0 + \ / Kf 'o - uo \ / J *a0 — „ 2 *ao\ , «*>+(!" — )«*> 3/i' \ 3ft" / I">DVO ~ + '"WVO 3p I pVO ' ' mwT0 ' ("0 - fto) myjV mass of water in the evaporator Xa steam content at evaporator outlet Z revolutions per minute VpR inner volume of the downcomers xaovo Block 8 : (66) water in the drum mDV mass of steam in the drum K1A — Z0 (64) 179 In conclusion, here is the explanation of the characteristic transient response shown on Fig. 119. The response to a change in the correcting variable may show a pronounced effective dead time (of the order of 10 to 20 seconds). Quite frequently the level may even first start to move in the opposite direction to the one it will eventually take. For example: Following an increase in the feedwater flow the level may temporarily drop. The less supercooled is the feedwater entering the drum, the less unfavourable, from the control point of view, is the time behaviour of this non-minimum phase system. The behaviour following a raise in the heat flux, i.e. following a load increase, is quite similar. Here the level temporarily increases, only to subsequently gradually fall off. Fig. 118 Transient response. The transient responses of blocks 7.2 and 8 correspond to the time func¬ tion shown on Fig. 118. For practical application, the actual function can be substituted by a first order function. t Fig. 119 Transient response of a level controlled system to a correcting or disturbance variable, in a drum boiler with supercooled feed. The variables in equations (54) through (66), the meanings of which have not yet been explained, are: 12* 180 8 Boiler Control 8.4 Signal Flow Diagram of Interacting Control Loops This effect cannot be compensated by design measures. A good control of pressure, maintaining it at a pre-set value, is always helpful. References: [6] [83] [128] [130] 8.4 Signal flow Diagram of a Benson Boiler and a Turbine, Including Controls Section 8.3 covered the signal flow diagrams of the individual controlled systems of a steam generator. In this section, it will be shown on an example how the partial control systems are coupled together. The most important controllers are included in the diagram in order to demonstrate how the control loops interact. A Benson boiler and a tur¬ bine with reheat, feeding a large grid, were chosen to represent a typical unit. Fig. 120 shows the complete signal flow diagram. AO the five main control loops are displayed, namely the control loops for steam pressure, feedwater, main steam temperature, reheat steam temperature, and load. To simplify the diagram, only one attemperator is assumed for tempe¬ rature control. An expansion to two or three attemperators in series should cause no problems. The steam pressure control loop is formed by blocks 18, 19, 13, 24, 27, 32, 34, 31, and 33. The controlled system itself corresponds to Fig. 95, with blocks 6 and 7 combined into a new block 27, and need not be dis¬ cussed here in detail. Block 31 is the PID steam pressure controller, and block 33 represents the application of the disturbance signal from steam flow. The controller is, in accordance with all other controllers, presented in an idealized form. This is permissible, since in comparison with the relatively large time constants of the controlled system, it is quite feasible to neglect the positioning time of the actuator, as well as all the time constants of the controller. o3 The control scheme in Fig. 75 has been chosen as an example of feedwater control. The feedwater controller is represented by blocks 9, 10, 11, and 12. Blocks 10 and 11 denote the application of the derivative of the tempe¬ rature signal from downstream of the evaporator. In this context, block 11 simulates the dynamics behaviour of the temperature sensor. This is necessary because in contrast to all other sensors, the time behaviour of the temperature sensor cannot be neglected. A 1st order delay with a Fig. 120 Signal flow diagram of a Benson boiler with a reheat turbine and control. 181 8 Boiler Control 8.5 Quality of Control time constant of approximately 20 seconds (if thermocouples are used) is enough for the simulation. With resistance thermometers the time constant is approximately between 40 and 50 seconds. frequency fluctuations in the system. In Fig. 120, the deviation from the required frequency of 50 Hz is denoted by f. As already explained in chapter 5, the set point Ns is corrected during frequency increases. The third important variable which brings disturbances into the system, is the calorific value Hu of the fuel. While there is no need to consider changes in the calorific value in oil and natural gas fired boilers, it would be a mistake not to consider them in the case of coal furnaces (particularly those firing brown coal). The concern is not so much about changes of the 182 The main steam temperature control loop is composed of blocks 16, 17, 23, 26, 22, 25, 28, and 21. The system itself is arranged as in Fig. 107, while the cascade circuit according to Fig. 66 has been chosen for control. In the diagram, blocks 22 and 23 represent the temperature sensors for temperatures downstream of the cooler and at the boiler outlet. The fourth control loop is the reheat steam temperature control loop, reproduced by blocks 1, 2, 3, and 5. Block 2 simulates the temperature sensor, while block 1 is used for the application of a disturbance signal from the steam flow. In the assumed mode of control the reheat tempe¬ rature is regulated by the flue gas vanes: The position of these vanes is denoted by Yzd . The change in the distribution of flue gas affects not only the reheater (block 5), but also the superheater part. The time behaviour associated with superheated steam is reflected by block 6. The location where, in the signal flow diagram, the retroactive signal impacts on the main steam part, depends on the actual arrangement of the heating surfaces. In the example in hand, it is assumed that affected is the temperature upstream of the cooler, !?veThe load control loop is the last of the main control loops to be discussed. It is formed by blocks 35, 36, 37, and 38. Blocks 35 and 36 represent the controlled system (see also Fig. 27), while blocks 37 and 38 represent the control device. Block 35 simulates the proportionally acting high pressure stage of the turbine, block 36 the low pressure stage which operates with some delay due to the effect of the reheater. Both outlet signals are summated, giving the turbine power N. yT *s the opening of the turbine inlet valves. The steam flow rhD can be obtained from this value (FT) by multiplying it by a figure proportional to steam pressure P. The system can be put out of balance by the action of several variables. Firstly, there is the load set point Ns for the plant, which is being varied according to a prescribed time-schedule. The actual load must follow Ns as closely as possible and with a minimum delay. During this operation the permissible tolerances of the other controlled variables must not be exceeded. Another variable that can cause difficulties is that resulting from 183 real calorific value, but rather about changes of the so-called unreal calorific value, which cause quite a few disturbances. The latter include irregular coal feed caused, for instance, by the bridging of coal in the bunker. As can be plainly seen from Fig. 120, control of a power generating unit represents a rather complex multivariable system with many interactions. As a result, for theoretical examinations, whether aimed at optimization of control or at the establishment of control accuracy, it is always neces¬ sary to have an exact idea as to the extent the individual control loops can be considered independent on the total system. References: [20] [49] [51] [121] [122] [123] [126] [133] [134] [143] [148] [172] [174] [179] 8.5 Quality of Control Designing power plant control often involves the choice of design variables that ensure the desired transient behaviour of the system. In this context it is of interest to know what maximum control deviation can be expected following a disturbance, and how the control process is expected to settle with time. The desired output is often defined as the best that can be obtained, where the word "best" can have several connotations mostly denoting minimum overshoot, minimum settling time, and minimum tendency towards per¬ sistent oscillations. Besides these requirements widely accepted in industry, there are performance criteria (indices, figures of merit) which attempt to express quality of control as a single number. These criteria are basically integral forms of squared error, absolute error, etc., and employ a weighting factor of some kind. They have the advantage that they can be easily manipulated in theoretical investigations. On the other hand, they 8 Boiler Control 8.5 Quality of Control have the disadvantage that the "best" aimed at may not be particularly suitable as a general index of quality in practice. One of the most useful among those that have been considered appears to be the so-called ITAE criterion (ITAE = Integral of Time Multiplied Absolute Error). This criterion is particularly recommended for cases when the optimisation has to be based solely on visual observations of the control process. attached in the preceding chapters to the derivation of the simplest possible signal flow diagrams for the individual controlled systems. 184 To specify the control quality criterion is not enough. In a multivariable system it is just as important to specify all the controlled variables which it is most vital to optimize. In power generation, these are: The boiler outlet pressure, the main steam temperature, the reheat steam tempera¬ ture, and the electrical power. For instance, it would not be particularly judicious to specify very narrow tolerances for level control in a drum boiler, since this would heavily strain the feed pumps. The protection of the pumps is important enough to warrant allowances for the increased fluctuations of the water level. Further, it is necessary to have a clear understanding of the expected dis¬ turbances and manipulating variables, as well as of their development in time, i.e. whether they are step shaped, of the ramp type, etc. In a power plant, the dominant disturbance is the load the unit has to produce; there¬ fore, the overall control must be optimised for variable command control of the load set point. However, this does not exclude some of the control loops from being preferrably optimised for the effect of particular other disturbances. If one considers the complex structure of the signal flow diagram of a steam generator (see Fig. 120), it becomes evident the dynamic investi¬ gations can be successfully managed only with the help of electronic computers. Both analogue and digital computers are suitable. 185 There are three basic methods of dynamic analysis. In the first method the complete unit, i.e. the boiler and the turbine, are simulated on a computer. This inherently very exacting method is primarily required for very accurate studies, such as, for instance, for finding or testing a new control concept, or for the examination of a new boiler structure with regard to its dynamic behaviour. Such an exacting method would seldom be needed for the determination of control quality. The second method which is quite fre¬ quently employed, consists of independently simulating the individual control loops on a computer. Its advantage is that small to medium com¬ puters are adequate for the task, and that it is not too time-consuming. Naturally, when using this method it is important to be all the time aware of the effects of simplifications. In assessing control quality, all simplifi¬ cations must stay on the safe side, so that the designer is protected against unpleasant surprises later on when the plant becomes operational. Further, it is essential that the main effects of the disturbances on the respective control loops are realized and appropriately simulated. The third, and at the same time the simplest method consists of making use of rules-ofthumb and of diagrams, from which the maximum control deviation can be inferred. With this kind of approach, no data regarding the time behaviour of the controlled process are, of course, obtainable. The great advantage of an analogue computer is its high computing speed, while the digital computer has an enormous capacity allowing an un¬ limited realization of non-linearities. The originally simpler programming of the analogue computers has recently been overtaken by the creation of block oriented programming languages for digital computers. Regardless of the availability of a computer it is necessary to understand that possibilities are not boundless. Due to the necessary simplifications, the mathematical model of a physical system is always only an approxi¬ mation of reality. Simplifications are unavoidable, being caused on one hand by limiations of computing power, and on the other hand by theo¬ retical difficulties. This is the reason why such great importance has been .20 0 0,4 0j6 V> Tu Fig. 121 Per-unit (reference) maximum control deviation of the outlet steam temperature, in dependence on the ratios TJT2 and T/Tu. 8 Boiler Control 8.5 Quality of Control The respective diagrams have been produced through systematic investiga¬ tion using an analogue computer, while an effort was made to use only the data already available in design stage. Figure 121 is such a diagram, and it is intended for use in approximating the accuracy achievable in steam tem¬ perature control. The diagram refers to control of the superheater outlet temperature by attemperation water flow injected at the superheater inlet (compare with the control diagram on Fig. 66). On the abscissa is marked the ratio of the effective dead time Tu to the disturbance time constant Tz ;on the ordinate the per-unit maximum control deviation. As the para¬ meter distinguishing the curves serves the ratio T/Tu, where T is the time interval during which the disturbance acts (the disturbance is assumed to have the form of a ramp function). For instance, for a 20% load change with a gradient of 5%/min., T would be 4 minutes. Accordingly, the curve T/Tu = 0 refers to step disturbances. The remaining characte¬ ristic values can be calculated from the already given equations. In this manner, it is possible to obtain Tu from Fig. 103 after the form factor y.D had been calculated by equation (29). The disturbance time constant Tz can be found with the help of equations (36, 37, 38) and the gain Vz from equation (35). Az is the disturbance expressed in %. or 48. Strictly speaking, therefore it should be used only for approximate calculations of drum boilers. Tests proved, however, that if the diagram is used for forced-flow boilers, reasonably good results are obtained. 186 Similarly, it is then possible to calculate the maximum control deviation Mmax. It is recommended that such an estimate of the expected quality of control be obtained at the earliest opportunity, and possibly still in the design stage of the steam generator. At such an early stage it might still prove feasible to improve the quality of control by structural changes in the design of the unit. The diagram on Fig. 122 is intended for use in approximating the control deviation in a steam pressure control loop. On the abscissa (x-axis) is Tu mD ,on the ordinate (y-axis) the marked the characteristic value ÿ per-unit maximum pressure control deviation APmax which is referred to the disturbance amplitude Az. The characteristic value on the abscissa is composed of the effective dead time Tu , of the maximum steam flow %max as well as °f the storage capacity S. Indications as to the way of determining these characteristic values can be found in sub-section 8.3.1. Another variable which affects the control quality is the pressure drop from the point marking the end of saturated steam to boiler outlet. This variable is introduced as a parameter. . The diagram applies only to step disturbances. It has been calculated for a drum boiler (Fig. 91) with steam pressure control according to Fig. 47 187 Naturally, a special computer study is always preferable, if the effort can be justified within the framework of the total project, and if the required technical data are available. 2z [bar/%] 0 100 200 300 V"Dmax [ s k9/s "I ÿ S [ kg/ bar J Fig. 122 Per-unit (reference) maximum control deviation of the outlet steam pressure, in dependence on the characteristic value Tu- m pmax S What can be done if the calculated control accuracy does not meet the requirements? The dynamic behaviour of a control loop, and, as a result, the achievable control quality, is given by the time behaviour of both the controlled system and the controlling instrumentation. This means that an improvement of control quality can be based on an improvement of the dynamic behaviour of either component. As for the controller, two options are available: To adjust control parameters, and/or to choose a better control scheme. The first point, namely the optimization of the controller, is a basic pre-requisite for each calculation, and does not have 8 Boiler Control 8.5 Quality of Control to be considered any further. On the other hand, the second point needs system to be corrected even before they reach the final superheater. The basic injection must be sufficient enough (corresponding to several degrees Celsius) to counteract possible negative temperature deviations. 188 careful checking. An improvement can be often achieved by the choice of a different control structure, by the inclusion of disturbance compen¬ sation, by the use of auxiliary control loops or of derivative elements, etc. Should all the possibilities in this respect be exhausted, the only remaining option would be to improve system dynamics by suitable design changes on the boiler. There are certain indications that should be held in mind when designing steam generators. As to what these are, let us con¬ sider the following example: As can be seen from Fig. 121, the effective dead time Tu should be as small as possible, the disturbance time constant Tz as large as possible, and the gain Vz possibly small. Fig. 102 shows that Tu decreases with reduction of the time factor TSR, and equation (32) provides the information that this factor is decisively affected by the mass of iron in the superheater. Consequently, the effective dead time can be decreased by reducing the mass of iron, i.e. by making the superheater smaller. The same conclusion can be arrived at from Fig. 103 when equation (30) is used for calculating the time factor Tr . In order to achieve good control, Tu should not exceed 30 to 40 seconds. The rule-of-thumb in this case is that such favourable values are achieved whenever the weight of iron (in tons) is kept at or below 10% of the steam flow (expressed in tons per hour). For instance, the final superheater of a 400 t/h boiler should not contain more than 40 tons of iron in all. In general, the reduction of the superheater is accompanied by a reduction of Vz. As can be seen from equation (35), Vz is proportional to the tem¬ perature raise in the superheater. It can be said that temperature raises in the range of 30 °C to 50 °C should be aimed at. The disturbance time constant Tz can be influenced only to a very limited extent, since it is to a certain degree, fixed by the other two parameters. The largest Tz values can be achieved with a convective superheater. Should the final super¬ heater consist of both radiant and convective sections, then the convective part should be located at the outlet. It appears from what has been said above that large boilers should have more than one (generally two or three) attemperators connected in series; this would make it possible to subdivide the superheater into several dynamically favourable sections. Further, it is important that enough spray water be provided, particularly for the final attemperator. This will enable disturbances entering the 189 What has been said applies not only to final steam temperature control, but also to reheat steam temperature control. Here, however, the attemperation is not desirable due to the loss of efficiency, and heat exchangers are, from the point of view of automatic control, quite acceptable. The point to remember is that control is satisfactory only when the heat exchangers are not located at the cold end of the reheater but rather towards its outlet, so that the subsequent (intermediate) superheater part is relatively short. From the dynamic point of view, particularly favourable are cross-flow heat exchangers where the heating high-pressure steam flows inside the tubes of a tube bank while the reheat steam flows across the tubes on the outside. It should be mentioned that a controlled by-pass on the side of the reheat steam is to be preferred to one on the high-pres¬ sure steam side (compare Fig. 111 and 114). Good results can be also achieved with flue gas swivel dampers, if the whole reheater is located in the damper controlled gas pass. During the installation it is important to make the dampers move with sufficient ease. Unfortunately, a certain side-effect on the high-pressure surfaces cannot be avoided, and for this reason, the surfaces have to be arranged in such a manner as to minimize this effect. Control which uses either tilting burners or flue gas recirculation is to be avoided, primarily because of the above mentioned undesirable side-effect on high-pressure steam surfaces. As regards the steam pressure control system, it follows from Fig. 122 that control improves with the reduction of effective dead time Tu and with the increase of storage capacity S. Satisfactory results can be achieved with effective dead times of up to 30 seconds. The dead time depends on the time behaviour of the mills, as well as on the time behaviour of steam ge¬ neration. Particularly suitable are high-speed beater mills with a negligible circulation storage in the mill and in the classifier. The apparent effective dead time of sluggish mills can be reduced by suitable control of pressure in the classifiers, i.e. by activating the coal dust deposited in the mill. Of course, conditions must be such as to permit a sufficiently high pressure change. 190 8 Boiler Control Using mixed fuels the fastest possible firing process (for instance, the burning of gas or oil) should be chosen for control, while coal firing should be reserved for base load firing. The time behaviour of steam generation can be influenced by arranging the burners with respect to the evaporator. The fire in the furnace must be situated so that it fully sweeps the evaporator surfaces; a fire that strikes too high is as damaging as were the formerly common residual evaporators. The drum boilers have, due to their substantially higher storage capacity, a certain advantage over the Benson boilers. In this respect, the forcedflow boilers with superimposed recirculation fit somewhere between the two. Storage capacity is determined by boiler design, and cannot be chosen at will. It has been noted that high-pressure units have the disadvantage of a lower storage capacity than low-pressure ones. Before concluding attention will once again be drawn to the necessity of perfect control of combustion air. This implies the availability of a good flow measurement as well as the application of forced-draught and induced-draught fans with inlet guide vane control. If mixed fuels are burned, it is important to make sure that there is an independent control system for combustion air flow for each fuel. The above list of tips on enhancing control could be expanded further, were it not for space limitations which prohibit the inclusion of more material. Let us only emphasize the importance of securing the coopera¬ tion of a control engineer already in the planning stages of a power plant project. References: [43] [48] [52] [74] [83] [109] [168] [183] [193] [200] [205] [217] [218] [231] [246] [253] [254] [255] [256] [284] [285] [294] [310] [311] [321] 9 Combined Heat-and-Power Plant (CHP Plant) Combined heat-and-power plants are also known as CHP plants, combined district heating plants, cogeneration plants, etc. This chapter will deal with such kind of control in these plants as does not come under the heading of standard boiler control. The characteristic of a combined heat-and-power plant is that heat is pro¬ duced simultaneously with electrical energy from a single fuel source. This means that in contrast to pure heating stations there is an important coupling between electricity and heat production. Thermal energy is pro¬ duced primarily for heating purposes and for providing hot water. Heated water is used as the preferable heat-carrying medium, unless situations arise where the consumer acutally needs steam or where the use of steam is more economical. (Compare with section 2.2: Common range arrange¬ ment with the supply of process steam.) In general, the design exit (or outflow) data for supply water are 2-10 bar and 80-150 °C. The circu¬ lation water flow is kept approximately constant, and is reduced only when the minimum exit temperature of the supply water has been reached. The return water temperature should be kept as low as possible in order to keep down the cost of heat production for a given number of consu¬ mers, as well as transportation costs (minimum pipe size, water flow rates, and pumping costs). The aim is to achieve a return temperature of water not exceeding 50 °C. Either back-pressure or condensing steam turbines can be used. In the currently no longer popular simple back-pressure mode, the produced electricity depends totally on the heat load; the less heat is used by the consumers, the less electrical energy is produced. This unwanted feature can be overcome by the application of extraction back-pressure turbines (i.e. condensing turbines with controlled extraction pressure). These are more versatile than other types, and can be loaded to full throughput capacity independently of the demand on heat production. Ideally, the turbines would be back-pressure/pass-out machines with a condensing section. CHP plants have very complex and variable possibilities of design too many to be dealt with in detail in this book. Fortunately, as regards control this does not appear to be such a serious handicap, since the actual control loops 9 Combined Heat-and-Power Plant 9 Combined Heat-and-Power Plant are relatively simple and constantly recurring. The main control objective is to regulate the exit temperature of the supply water so that the water at consumer location is always available at as high a temperature as required. is adequately supplied, a minimum pressure difference at the furthest index point is maintained so that in accordance with the control deviation a pres¬ sure difference controller acts on the speed of the water supply circulating pump (or pumps). 192 To this effect the set point has to follow a command signal derived from the ambient temperature and wind velocity, as well as from the heat re¬ quired in dependence on the time of the day, and the distance/velocity lag of the heat transfer between the places of production and consump¬ tion. Further, the pumping system (consisting of circulation pumps, booster pumps, etc.) must be controlled so as to provide a sufficiently high pressure at the furthest index point of the hot water grid by over¬ coming the delivery resistance head, in other words to safeguard the supply. To this effect, either a) the pressure in a location directly up¬ stream of the consumer is measured and maintained at a constant value, or b) the outgoing pressure head at the power station is controlled, with adjustments of the set point used to equalize the pressure drops in the piping system. However, in a system with mains of different lengths going to different parts of the system, this may not be enough to provide the necessary heat flow in an awkward consumer location. If the network topography is unfavourable, for best results it may be necessary to main¬ tain a minimum pressure drop across the heating equipment of the respec¬ tive consumer (see A p in Fig. 123). Such a pressure difference could be measured directly at the location in question, but only if its value is not affected by changing operating conditions. In the latter case, differential pressure measurements should be taken at a number of consumer points particularly near the tail end of the piping system. Automatic control then maintains constant the lowest value obtained with the help of a minimum selector. It is advantageous if the lay-out of the district heating plant is such that the circulating water flow is not subject to wide variations, making consideration of changes in dead time unnecessary. 193 Fig. 123 Control scheme of a remote heating part of a district heating plant. NS i Fig. 123 illustrates a possible scheme for the remote (heating) part of a CHP plant, containing the essential control loops. For the sake of clarity the lay-out is simplified; only one heat exchanger is marked in each loop while, in reality, there may be two or three connected in series. Also omitted are such components of the plant as storage tanks and equalizing tanks, connecting pipework, etc. The diagram includes two closed water flow systems, the lower one for hot tap water supply, the upper one for heating. In the hot water loop the outflow supply water temperature Dw is kept constant. To this effect, automatic control adjusts the flow which by-passes a heat exchanger. In order that even the most remote consumer Fig. 124 Control scheme of a district heating plant. 13 Klefenz 194 195 9 Combined Heat-and-Power Plant 9 Combined Heat-and-Power Plant A further controller acts upon the speed of the return pump(s), thus keeping the absolute pressure P constant. (In no part of the return water main must the pressure exceed the value given by the design pressure condition of consumer heating equipment.) Feedforward signals from disturbances are not required because the change of the disturbance variables is usually very slow. Real difficulties may only be expected with the thoroughly coupled control loops for pressure and for pressure difference. But even these can be mastered by careful opti¬ mization of the controllers. These should be adjusted in relation to each other. Should there occur considerable fluctuations of the flow of water through the heat exchanger, it is necessary, in order to maintain a con¬ stant control loop amplification, to ensure that the controller gain changes in dependence on these fluctuations. Since the gain of the controlled system rises with a decreasing water flow, the controller gain must, in this situation, decrease. One part of the water flow branches out at the outlet of the first heat ex¬ changer (which is the lower one in Fig. 123), and by flowing through the second (higher) exchanger is brought to the temperature needed for heating purposes. This temperature is not kept at a constant value, but is made variable in dependence on outdoor temperature. Among the possible variants of water temperature control for this type of plant, the one selected for the example uses the flow of bled steam (extraction steam) into the heat exchanger. All heat exchangers are naturally equipped with condensate level controls which take care of the removal of the condensate. This control is, however, not shown. In order to safeguard the supply of hot water even for distant consumers, the pressure differences are again kept constant by the variation of the speed of circulating pumps. A third, and at the same time a rather common variant of the exit water temperature control, is based on controlled accumulation of the conden¬ sate in heat exchangers. It is obvious that in this variant there cannot operate a condensate level controller. Instead, the temperature control deviation acts directly on the condensate drain valve via a separate con¬ troller. If the temperature is too high, the drain valve throttles quite sub¬ stantially. This causes the condensate level to rise; this in turn diminishes the heating surface, and reduces steam condensation. Eventually, a new equilibrium state with a higher condensate level is reached, this being in agreement with the reduced heat requirements. Pressure in the mains network can be also maintained by establishing a steam space over the surface of the water in one of the equalizing tanks. The necessary steam is obtained from a reducing station connected to a suitable section of the steam line, and the steam influx is controlled so as to maintain pressure in the water grid. Depending on the plant concept, other temperature and pressure control loops can be used. If secondary grids are in operation, which is typical for indirect systems, booster and conversion stations should be installed between the CHP plant and the consumers. However, none of the control loops in remote heating plants cause any insurmountable difficulties, and, in general, proportional-integral controllers are quite satisfactory. In general, there is no need to simulate these control loops. Should the need unexpectedly arise, the problems would be broadly similar to any heat exchanger problems. The methods with which the respective solutions could be attempted were discussed in sub-section 8.3.4. As for the calcula¬ tions relating to heat exchangers controlled by condensate accumulation, it is necessary to refer the reader to specialised literature. In a heat-and-power plant the production of electricity and the remote heating process ififluence one another. Following an increase of the power set point, the power controller ensures that the turbine produces more power by opening the nozzle valves. Simultaneously, more heat is supplied for district heating, causing the temperature controller to act in the oppo¬ site direction. Conversely, an increase in heat supply to the district heating system is followed by an increased production of electrical energy. It would therefore be appropriate to isolate the two coupled control loops, pos¬ sibly by the application of measures shown in Fig. 124. Let us imagine that following an increased demand the energy controller causes nozzle valves to open. In such a case, the proportional element 1 would some¬ what throttle the extraction steam. On the other hand, should more heat be needed, then not only more extraction steam would be let in, but simultaneously the proportional element 2 would open the nozzle valves wider. It can be said that this principle, with suitable variations, is appli¬ cable to other variants of heat-and-power plant control. References: [3] [27] [83] [91] [92] [93] [185] [187] [234] [247] [281] [299] [307] 13* 10.1 Types of Reactors 10 Nuclear Power Plants This chapter concerns the essential differences between the automatic control of nuclear power plants and that of conventional power plants. The starting point to be dealt with is the assumption that the only diffe¬ rence between these plants is simply in the firing; that nuclear fuel is 'burned up' in one and fossil fuel in the other. However, from the simple fact that it is either chemical energy or nuclear energy that is converted into thermal energy, appreciable differences originate between the two kinds of plant. The plants differ in design as well as in time behaviour, which necessarily affects control. A substantial dissimilarity appears to exist already in the storage of fuel: While 'fuel' is stored in the reactor over the years, it has to be continuously brought to the conventional boiler. When, in addition, one realizes that the release of nuclear energy is possible in fractions of seconds, it becomes evident that with nuclear plants precautionary technological measures must be implemented and these affect both design and control. Moreover, in a conventional plant the fuel is supplied for combustion in a gaseous or quasi-gaseous state, and is burned in a relatively large furnace. On the other hand, in the reactor, energy is released in the solid fuel, and that in a very small volume. In fossil fuel fired boilers the heat transferring medium is the flue gas which is at high temperature and low pressure, while in a nuclear generator gas, water, and even liquid metal find application, and are used under various pressures and temperatures. This is another reason why the actual steam generator in a nuclear power plant bears so little similarity to the conventional boiler, the only exception being the gas-cooled reactor. Steam generators for other reactor types deviate from tradition, and ac¬ tually are heat exchangers. References: [187] [188] [203] [223] [265] [277] [280] [286] [290] [308] 197 doubt, from the economic point of view the most important is the lightwater reactor (LWR), which comes in two versions, namely as a boilingwater reactor (BWR) and as a pressurized-water reactor (PWR). The simplified plant diagrams of the two types are shown in Fig. 125 under a) and b). In a nuclear power plant using a boiling-water reactor, the steam produced is directly conducted to a saturated steam turbine. The plant is therefore of a single-loop type. In a pressurized-water reactor, on the other hand, a two-loop system is necessary. Here the required saturated steam is produced in one and possibly more heat exchangers. a) boiling-water reactor £ -© i® ¥ £ b) pressurized-water reactor -© c) gas-cooled reactor -©- Fig. 125 Fundamental structure of a nuclear power plant. 10.1 Types of Reactors An attempt to list here all the possible types of power reactors would be too involving. Instead, the types that will be dealt with are only those that have already gained some prominence in operation. Without any Gas-cooled reactors must be mentioned next, and, particularly, the two main designs. The first design (GCR, AGR, HWGCR) uses carbon dioxide for cooling. Due to the limited core gas outlet temperature, saturated steam must be produced in a heat exchanger, exactly as in the already described pressurized-water reactor. The second design (HTGR, AVR, THTR) covers the so-called high temperature reactors where helium is used as the cooling 10 Nuclear Power Plants 10.2 Control in a Nuclear Power Station gas. The substantially higher gas temperature makes it possible to produce superheated steam in a forced-circulation once-through boiler (see Fig. 125c). of water circulating in the reactor. An increased circulation diminishes the volume of bubbles and therefore increases reactivity. However, water circulation serves as the correcting variable only in the upper load range (above 60%). In the lower load range, the insertion or withdrawal of control rods are used instead. Further, it is necessary to control the level L in the reactor vessel. This is performed by three-element control which is sufficiently known from applications in conventional plants. 198 Finally, attention should be drawn to the research and development pro¬ gramme in the so-called fast breeder reactors (FBR). It remains to be seen how successful this type will become. Currently, a fast breeder is cooled by liquid sodium, which necessitates three heat transport systems con¬ nected in series (primary and secondary coolant circuits plus steam circuit). 199 10.2 Control in a Nuclear Power Station Discussion of the basic properties of control in a nuclear power plant will be limited to the three reactor types introduced in section 10.1. Since nuclear power plant control is a relatively new science, the control designs that are being applied in practice may differ from the designs correspon¬ ding to the guidelines given below. Fig. 126 shows a control scheme of a boiling-water reactor. The plant is equipped with a turbine with controlled inlet steam pressure. Steam pro¬ duction is governed by load control. At first glance the diagram looks like a retrograde step in comparison with conventional power plants. However, the justification for such an approach becomes clear once allowance is made for the speed with which steam production changes, following the adjustment of the correcting variable (which in this case happens to be either the throughput of the circulating water, or the in¬ sertion or withdrawal of control rods). The speed of steam production in a boiling-water reactor is of a higher order of magnitude (steam is pro¬ duced in just a few seconds) than in coal fired steam generators. In ad¬ dition, it is possible to fully exploit the advantages of controlling steam pressure upstream of the throttle valve. This makes it possible in a boiling-water reactor to keep steam pressure very accurately constant, which is particularly important in neutralizing the effects of pressure fluctuations on chain reactions in the reactor, and subsequently on the production of power. The controls work as follows: On changing the set point for electrical energy N$ , or that for the variation of grid frequency f, a PID controller changes the set point of the steam flow controller. In its turn, the steam flow controller governs the speed of the pumps thus changing the flow Fig. 126 Fundamental scheme of a nuclear power plant with a boiling-water reactor. Outside these main control loops there are naturally many subordinate loops, as well as various limiting and blocking circuits. The scope of this discussion does not call for their detailed explanation. The next point are the principles of control of a pressurized-water reactor power plant. Its control scheme is shown on Fig. 127. The turbine, as in a conventional plant, is equipped with load control in¬ corporating the effect of grid frequency. The required reactor load in the upper load range (above 50% MCR) is controlled by the control rods in such a manner as to keep the average temperature of the cooling agent, i\m , constant. (The average tempe¬ rature being the average of the inlet and the outlet temperatures.) This is as follows: When the turbine increases the withdrawal of power from the steam generator, the average temperature of the coolant drops, and the reactor is stimulated to a higher power production by the repositioning of control rods. 200 10 Nuclear Power Plants 10.2 Control in a Nuclear Power Station 201 The third kind of reactor is a helium-cooled high-temperature reactor. Its control is illustrated by the basic scheme on Fig. 128. The turbine load is again controlled in the already familiar manner. --- -0 czO boric acid demineralized water Fig. 127 Fundamental control scheme of a nuclear power plant with a pressurized-water reactor. Control rods are kept within the control range by additions of boron, or demineralized water for chemical shim control, which are in turn measured out by a separate controller. The introduction of small amounts of these chemicals into the coolant or the moderator influences reactivity. This has the same effect as when the so-called shim rods bring reactor power approximately to the specified level. A side-effect of keeping the average temperature of the cooling agent constant is that both steam pressure and steam temperature decrease with the increasing load. However, this does not apply to loads below 50%, where the average coolant temperature is reduced in a manner which allows for steam temperature and steam pressure to remain constant. Another controlled variable in the pressurized-water reactor is the pres¬ sure Pic of the coolant. It has to be kept within narrow limits since boiling must be prevented at all cost. A heated pressurizer is connected to the reactor coolant loop to make the task easier. As to the control itself, there are three control variables which act in sequence. These are: The heating of the pressurizer by an electric heater, the cooling of the pressurizer by a cold auxiliary spray, and the releasing of gas from the pressurizer via a release unit. The level L in the pressurizer is kept constant by controlling the volume withdrawal from the cooling loop. r Fig. 128 Fundamental control scheme of a nuclear power plant with a high-temperature reactor. The flow of the coolant through the reactor embodies the control variable for the steam pressure PD. A negative deviation of this pressure from the set point causes an increase in the speed of the helium blower. The set point for the neutron flux 4> is adjusted by a signal derived from the steam temperature $d : it may lead to a corrective action of the control rods. The helium temperature #k at the outlet of the steam generator is kept constant by control action on the feedwater flow ms- This control simultaneously maintains gas pressure. A feedforward disturbance signal from the load set point is sent to the feedwater control as well as to the neutron flux control and the steam pressure control. Other aspects of control need not be discussed since the boiler in question is a Benson boiler and its control has been fully covered at an earlier stage. Due to gas temperature being sufficiently high, superheated steam is pro¬ duced in the boiler. The relatively high gas temperature (approx. 750 °C) makes it possible to use a reheater. This is not shown in Fig. 128, since the pertinent reheat steam control offers nothing new. 10.3 Dynamic Behaviour of Nuclear Reactors 10 Nuclear Power Plants 202 Xj 10.3 Dynamic Behaviour of Nuclear Reactors For analytical treatment of control problems in a nuclear power plant it is necessary to have a mathematical model of the nuclear reactor. In contrast to the conventional steam generators fired with fossil fuels, where combustion processes as well as supply processes (such as milling of coal, etc.) can only be conceived with difficulty, nuclear desintegration (i.e. the release of energy) can be exactly described by equations. Reactor kinetics are generally so complicated that they can best be described by time- and space-dependent differential equations. However, for simplified controltechnological investigations it appears sufficient to perform the calcula¬ tions independently on spatial coordinates, i.e. independently of the con¬ figuration of the reactor. If this approach is adopted, then ordinary diffe¬ rential equations (67) and (68) can be used to describe the time dependent behaviour of the neutron density n. In the context of control, the neutron density is representative of the neutron flux <f>, i.e. of the released heat energy: £ (67) - fe(l -Ifc)-1 T1 + 2 J i i Xi -Cj+S, - Vcj. (68) production rate of neutrons k effective multiplication factor I effective lifetime of a neutron = mean time for a neutron to be removed from the reactor ft fraction of delayed neutrons of the f-th type = fraction of precursors of the f-th type produced in fission, compared to the total production of prompt neutrons and precursors of all types ; removal rate of neutrons Ci number of precursors of the f-th type (varying in time) m number of precursor types = number of delayed neutron Although there are approximately 20 types of delayed neutrons, generally only six are distinguished. For automatic control investigations it is even sufficient to combine the six types into a single one. This approach will be used in the following text, particularly since it also improves the clarity of the treatment. It should be emphasized that the simulation of all six types would cause no difficulties. The condensation of the m types is described by the following equations: m independent source rate 0= 2ft, (69) t = X- (70) p n m Customarily, the reactivity p is used in place of the multiplication factor. The relationship between these two parameters is given by P=k- The steady state of a reactor when the neutron density n remains constant, is characterised by fe = 1, and p = 0. The steady state is also known as 'critical'. This is why reactors are classified as sub-critical and super-critical, the definitions being as follows: k < 1 sub-critical reactor p = negative k = 1 critical reactor p = 0; chain reaction is sustained k > 1 super-critical reactor p = positive It follows that in practice k must always be approximately equal to one. As a result, also l/k ~ I, and equations 67 and 68 change to: (72) types S mean decay rate of precursors of the f-th type (in each group the precursors decay exponentially with a characteristic halflife that determines the rate of emission of delayed neutrons). (71) Here the symbols are as follows: 203 (73) f= £= n + X- c + S, X c. ÿ 204 10 Nuclear Power Plants 10.3 Dynamic Behaviour of Nuclear Reactors 205 These two equations completely describe the neutron kinetics. A repre¬ sentation in the form of a signal flow diagram is shown on Fig. 129. The input variables into the system are the reactivity p and the independent source rate,S. The neutron density n is the output variable. The signal flow diagram on Fig. 129 will be used in discussing the time behaviour of the neutron density n for the various operational modes. t a) The independent source plays a vital part during start-ups. Fig. 130 Transient response of neutron density in a sub-critical reactor during start-up. 1 . decrease of the negative reactivity 2 . . increase of the negative reactivity . Equilibrium before the change : (74) p0 . n0 + S -1= 0. Equilibrium in the first instant after the change: (75) (p0 + Ap) • (n0 + An) + S I - (1 An =0, ÿ ÿ It therefore follows that: (76) T=i Fig. 129 Simplified signal flow diagram of neutron kinetics. If the reactor is sub-critical, with p a negative value, then it behaves, following a step change in reactivity, as a proportional module. A very fast change at the beginning is followed by a considerably slower approach to the new steady state. An explanation based on the signal flow diagram is very simple. In the original steady state the variables p0 • n0 and S- Iare in equilibrium, since, due to the factor k = 0, the feedback shown in the lower part of Fig. 129 is nil. A change in p0 by the small amount Ap, while p remains negative, is followed by a very fast change in n. The amplitude of this change, An, is determined by the sum of the two negative feedbacks existing in the first instant, and can be calculated as follows: A" -Ap. The very fast rise of An is called the 'prompt jump', since it is based ex¬ clusively on the prompt neutrons. The delayed neutrons, or, more pre¬ cisely, the neutrons originating with a delay, do not yet participate. The prompt jump is followed by a much slower change in neutron den¬ sity. The slowing down is caused by the fading away of the feedback with , which acts via the factor j3. A The new steady state is then once more described by equation (74) with the time constant p0 and riQ replaced by the new values px and /ij . b) The independent source can be disregarded once the neutron density leaves the start-up range. Three ranges have to be distinguished depending on the magnitude of the reactivity p. According to the signal flow dia¬ gram, a negative reactivity step, applied to a steady-state for which p = 0, initially leads to the behaviour described in a) as the prompt jump. This is then followed by a slow decrease to nil, the speed of the reduction being determined by the fading feedback. It is evident that them is no new equilibrium at fixed level of neutron density (see Fig. 131). 10 Nuclear Power Plants 206 c) The application of a positive reactivity step for which, however, 10.3 Dynamic Behaviour of Nuclear Reactors (78) T, =ÿf (79) t2=- Ap<0, makes the reactor super-critical. It can be deduced from the signal flow diagram that at first there must occur a prompt jump corresponding to equation (76). This is so because the positive feedback (the upper path in Fig. 129) and the negative feedback (the lower path in Fig. 129), counteract each other, the increment An Ap being smaller than the in¬ crement An 0 of the negative feedback. At first, it appears that the tendency is to reach a new steady state. ÿ ÿ r Ap __ — -_ Ap = 0 Ap < 0 Fig. 131 Transient responses of the neutron density with a negligible source. However, this stage is soon followed by a permanent rise in the neutron density (see Fig. 131), which increases as the negative feedback fades away, i.e. as the delayed neutrons become active. After all, the fact that it is at all possible to come to grips with the control of nuclear reactors can be attributed to the phenomenon of delayed neutrons. Of course, if these neutrons are to be made use of, it is necessary to ensure that Ap is never larger than 0 (see also paragraph d). An approximate solution of equations (72) and (73) in the time domain reads as follows: with n(t) = It can be seen from equation (77) that the transient response consists of a quickly fading part together with a slowly exponentially rising part. The rise is characterised by the so-called reactor period Tl , which is the amount of time a reactor takes to change its neutron level (i.e. its power output) by the factor of e = 2.718. An approximate solution in the frequency domain leads to a transient response described by the following equation: > |3 p > Ap > 0 (77) 207 jÿ-p ((].et/Tl -p e" r/7"a) • m /om *5<i> = _?0_ *•«ÿ» K) (ÿÿ**»•) ' It is obvious that equation (80) represents a PI transfer element with a 1st order delay. This means that for approximate calculations, the si¬ mulation according to Fig. 129 can be replaced by a simple PI function. d) If the change in reactivity exceeds 0, AP > 0, then the delayed neutrons no longer play a part in sustaining the chain reaction. The reactor is supercritical solely because of the prompt neutrons. This state is called prompt supercritical. As can be seen from the signal flow diagram (Fig. 131), the neutron density rises both exponentially and very quickly, since the positive feedback strongly predominates. The reactor period then amounts to: (81) Ty = L. Control technology is no longer adequate for keeping the reactor under control. As a result, this operating range has to be avoided at all cost. A comparison between the time behaviour of the 'firing' in a nuclear reactor and the time behaviour of the conventional firing in a boiler, highlights two basic features of the reactor. Firstly, the reactor responds to a command signal (change in reactivity) by a step load change, i.e. immediately and without effective dead time. 208 10 Nuclear Power Plants Secondly, the increase of load is astatic (there is no self-regulation). -<ey — T =1 QK =P 1_ / K = aR tb. kb 10.3 Dynamic Behaviour of Nuclear Reactors increased or decreased by the already described feedbacks, depending on the sign of the partial reactivity coefficients aM , aB, etc. In general, the time behaviour of the feedbacks can be simulated by delay elements of the first order with time constants TM , TB , etc. However, the admissibi¬ lity of such a simplification must be considered in each and every case. As an example, let us approximately calculate the transient response of the inner feedback based on the temperature of the moderator. A liquid moderator in the reactor core, with a volume of VM, has a constant input and a very small but constant flow mM - If the mo¬ temperature of derator is thermally well insulated from the reactor parts, then the average (= arithmetic average of the inlet and outlet moderator temperature temperatures) which determines the reactivity, is determined solely by the absorbed radiation energy per time unit. The latter is again proportional to the reactor load, in other words, to neutron density. This leads to the following equations: 5 (82) Fig. 132 Simplified signal flow diagram of a nuclear reactor in operating range. 209 ÿ Kn-n=mM (hMa - hMe) + VM Pm cM ÿ , p = aM • (83) • ÿ ÿ • . where: On the one hand, there is a very good response to a change in the command signal; on the other hand, the danger persists that a failure of the control system or an error by the operator, can cause the released energy to in¬ crease extremely quickly and out of all bounds. Such a danger has to be nullified by an extensive safety system. In addition, the following circum¬ stances may be of help: Once reactors reach the so-called load range, the increased heating manifests itself by the appearance of thermal feedbacks that are generally negative (most power reactors have negative temperature coefficients). This changes an astatic system into a static one. Besides the thermal feedback from the fuel, the coolant, and the moderator, it is also possible to distinguish feedbacks caused by changes in the pressure and in the volume of bubbles. (Note that pressure coefficients are usually posi¬ tive, and refer to pressure changes in gas-cooled reactors. The void coeffi¬ cients, which are usually negative, refer to bubble formation in the boiling-water reactors, and to voids in the sodium-cooled reactors.) The inclusion of the above features extends the signal flow diagram. The new structure is shown on Fig. 132. The input variable of the system is now the reactivity ps as determined by the regulating rods. It can be either Kn • n total energy released from fission, per time unit 5 fraction of the fission energy released in the moderator mM ÿMa moderator flow moderator enthalpy at the outlet ÿMe moderator enthalpy at the inlet Vm moderator volume Pm moderator density cm average true specific heat (heat capacity) of the moderator ÿMa moderator temperature at the outlet #Me moderator temperature at the inlet average moderator temperature "M 14 Klefenz moderator temperature coefficient of reactivity 211 10Nuclear Power Plants 10.3 Dynamic Behaviour of Nuclear Reactors If the aim is to find the deviation from steady state, equations (82) and (83) will change into: As has been discovered by observation, the inner feedbacks have still another favourable effect which can be stated as follows: In a reactor without any inner feedback (pure neutron kinetics) the system gain would be proportional to the level of load, i.e. to the neutron density. However, the thermal feedback makes the system gain practically inde¬ pendent of load level, so that the gain of the controller may also stay constant. Finally, the following list of the orders of magnitude of the individual parameters which appear in the signal flow diagrams, should make it easier for the control engineer to obtain a numerical idea of the dynamic process in the reactor. However, should investigations concentrate on the behaviour of a specific reactor, then the characteristic values pertinent to the particular plant must be established. This is necessary due to the unfortunate pronounced scatter of characteristic values from one reactor to another. 210 (84) 5 (85) ÿ Kn An = mM . cM (Afla - Ai?e) + VM Pm cM ÿ • ÿ • dAiSM ÿ df Ap = aM • Ai?m . When combining equations (84) and (85), Laplace transformation leads to a transient response of the type (86) rsp (s) An (sj _ ~ <*M 1 + 7m ' J This is a delay element of the first order, with the following characteristic values: (87) 6 Km = 2 cM mM ÿ (88) _ PM Suggested approximate values: ÿ • Km ~ 2 mM • lmax The inner thermal feedbacks which occur in the operational range funda¬ mentally change the transient behaviour of the reactor. Since in the power plant reactor the sum of all these feedbacks has a negative sign, the system without self-regulation, i.e. the astatic system (see Fig. 131), changes into a system with self-regulation, i.e. a static one (see Fig. 133). This self-stabilizing effect to a considerable extent facilitates control. In addition to these inner feedbacks there are cooling loops with their heat exchangers or steam generators, which act as further feedbacks and also bear a stabilizing influenze. [Lcm ne2Utsr0"S 1J cm ÿmaxÿlO13 • _ 10 i r neutrons 1 [neutrons J cm3 • s p > ap > o 0 r-3 « 7,5 -10- l «10-3 X « 8 • 10-2 [s-1 ], aM = - 2 10 4 [grad aB Fig. 133 Transient response of the neutron density of a nuclear reactor in operational range. neutrons 3 cm io8 • [s], 1 ] - 2 • 10 5 [grad ']. References: [6] [31] [89] [91] [110] [111] [170] [173] 14* 11.1 Symbols 11 Appendix 11.1 Symbols The following list contains the most frequently used signs and notations. Importance has been attached to adhering to the symbols that had al¬ ready been introduced in technical literature. However, this has made it unavoidable for some symbols to cover two variables. Since the symbols are always used in different areas, a mistake is barely possible. n neutron density (nuclear reactors) N power, energy P pressure Q selfregulating factor, reciprocal gain Q heat flow, heat flux, heat flow rate r latent heat s Laplace transform operator S storage capability, capacity S independent source rate (nuclear reactors) t time T time constant c specific heat c concentration of precursors (nuclear reactors) f frequency area Tu T, effective dead time F h enthalpy u voltage H position, lift V specific volume i electrical current V volume I mass inertia moment V gain, amplification k heat transfer coefficient V volume flow k multiplication factor (nuclear reactors) proportional band K constant I effective lifetime of a neutron XP *Va *Ve end point of evaporation L m level y valve position mass z number of . . m mass flow Z revolutions per minute (rpm) m Nusselt exponent 3 impedance m number of types of precursors (nuclear reactors) a heat transfer coefficient n speed a fraction, factor build-up time, rise time starting point of evaporation 213 11Appendix 214 11.1 Symbols 215 moderator-temperature coefficient (nuclear reactors) O oil T turbine P P factor s set point, set value th thermal fraction of delayed neutrons (nuclear reactors) S feedwater u circulating water 7 factor S saturated steam 0 nominal state, original S factor S classifier A deviation, difference A deviation from original value or state d temperature 0 absolute temperature steady state adiabatic exponent = ratio of specific heat at constant pres¬ sure to that at constant volume D form factor X mean decay rate of precursors (nuclear reactors) p density p reactivity (nuclear reactors) <f> neutron flux (nuclear reactors) X steam content The graphical symbols applied in the diagrams were taken from the DIN Standards No. 2481 and 19 226, and from the VDI/VDE Guideline No. 3527. In addition, the following have been introduced: f ED controller; marked is the dynamic transfer behaviour P proportional element I integral element D derivative element Suffixes a output G gas B fuel K coal D steam K coolant e input L air E iron LP primary air E spray (attemperation) water LS secondary air F furnace m mean, average / /- controller; marked is the static transfer behaviour ratio adjuster, bias multiplier set point setter 11Appendix 216 With regard to control schemes the direction in which the signals operate, i.e. the directional flow of the signals, is made easily recognizable by the application of signs. The following rules apply: + A rising signal or a rising measured value cause the control element to open, or the command signal to rise. — A rising signal or a rising measured value cause the control element to close, or the command signal to decrease. 11.2 Bibliography [1] Acklin u. Laubli, F.: Berechnung des dynamischen Verhaltens von Warmeaustauschern mit Hilfe von Analogrechengeraten. Techn. Rundschau Sulzer, Forschungsheft I960 Dampfkesselbau. Example: X,' V -(s I Gil i. i ojo If Xi rises, the command signal x2 decreases. If the set point is increased, x2 rises as well. If the command signal x2 rises, the valve opens. If the measured variable x3 rises, the valve closes. [2] Adams, J. u. Clark, D.R. u. Louis, J.R. u. Spanbauer, J.P.: Mathematische Nachbildung der Dynamik der Durchlaufkessel. Archiv fur Energiewirtschaft (1966), 7, 277/292. [3] Bleisteiner, G. u. v.Mangoldt, W.: Handbuch der Regelungstechnik. Springer-Verlag, Berlin/Gottingen/Heidelberg 1961. [4] Bodefeld, Th. u. Sequenz, H.: Elektrische Maschinen. Springer-Verlag, Wien 1952. [5] Bouchard, R.: Betriebsoptimierung grofier Dampfkraftwerke. BWK 18 (1966) 11, S. 562/567. [6] Cermak, J., Peterka, V. u. Zavorka, J.: Dynamika regulavanych soustav v tepelne energetice a chemii (Dyna¬ mik von Regelstrecken in der warmetechnischen Energieerzeugung und in der Chemie). Academia-Verlag, Prag 1968. 1 -tM- Diekers, W. u. Valder, L.: Vergleichende Untersuchungen von Bensonkessel-Regelschaltungen . Schoppe & Faeser, Techn. Mitt. (1959) 4, 135/146. [8] DIN 2481: Warmekraftanlagen. Dez. 1954. [9] DIN 19226: Regelungstechnik und Steuerungstechnik. Mai 1968. 218 11Appendix [10] DIN 5492: Formelzeichen der Stromungsmechanik. November 1965. [11] Dolezal, R.: Durchlaufkessel, Vulkan-Verlag Dr. Classen, Essen. 11.2 Bibliography 219 [21 ] Frensch, J.: Uber das dynamische Verhalten von Bensonkesseln bei Lastschwankungen. Brennst.-Warme-Kraft 9 (1957), 1 1, 517/523. [22] Friedewald, W. u. Mork,P. u. Zwetz, H.: Einsatz von Dampfkraftwerken im Netzbetrieb als regelungstechnische Aufgabe. ETZ81 (1960), 185/193. [12] Dolezal, R. : Zeitverhalten des Verdampfers eines Wasserrohrkessels mit Umlauf bei Druckanderungen. Warme 75 (1969) 2/3,44/46. [13] DoleZal, R. : Unterdriickung der regellosen Schwankungen des Luftiiberschusses im Feuerraum. Mitteilungen der VGB (1968) 48, S. 346. [23] Friedewald, W. und Zwetz, H.: Regelung der Temperaturen im Wasser-Dampf-System von Bensonkesseln. Regelungstechnik 13 (1965) 2, S. 62/68. [14] Doleial, R : Wege zu einer raschen Leistungssteigerung im Block mit Zwischenuberhitzung. Mitteilungen der VGB (1963) 82, 21/36. [24] Gartner, R.: Regelung in der elektrischen Energieversorgung. Regelungstechnik 13 (1965) 2, S. 49/57. [15] Dolezal, R.: Betriebsverhalten des Zwangsdurchlaufkessels mit unterkritischem Druck bei Lastanderungen. Mitteilungen der VGB (1 960) 69, 413/423. [25] Gerber, H.: Der Suizer-Einrohrdampferzeuger als Regelaufgabe. Techn. Rdsch. Sulzer 51 (1969) 1, S. 27/37. [16] Dolezal, R.: Analyse des dynamischen und statischen Verhaltens als Hilfsmittel zur richtigen Gestaltung einer Ein- [26] Grasme, P.: Das Ausfahren steiler Lastspitzen durch Dampfkraftwerke mit Zwischenuberhitzung. ETZ81 (1960) A 6, 193/203. [27] Haase, M.: Einfluft der Kraft-Warme-Kopplung auf die Kraftwerkstechnik. Mitteilungen der VGB 49 (1969) 5,312/319. [28] Planus, B.: Vereinfachte Nachbildung des Regelverhaltens eines Dampfiiberhitzers am Analogrechner. Regelungstechnik 13 (1965) 1, 14/20. [29] Herbrik, R. u. Vofi, K.: Digitale Simulation der Regelsysteme von Dampferzeugern mit Hilfe blockorientierter Programmiersprachen. Brennst.-Warme-Kraft 21 (1969) 1, 13/16. [30] Hillesheim, J. u. Burger, R.: Betriebserfahrungen mit Zwangsdurchlaufkesseln fiir Braunkohle und Vergleiche mit anderen Kesselbauarten. BWK 16(1964) 10, S. 470/497. spritzanlage. Brennst.-Warme-Kraft 17 (1965) 11, 523/529. [17] [18] Franke, H. u. Stolle, W.: Zwangsdurchlaufkessel im Blockbetrieb. Schoppe & Faeser Techn. Mitt. (1957), 3, 78/88. Frensch, J. u. Klefenz, G.: Universell anwendbare Reglerschaltung fur Bensonkessel. Schoppe & Faeser Techn. Mitt. (1961) 2, 57/65. [19] Frensch, J. u. Klefenz, G.: Die Dynamik der Dampferzeugung im Bensonkessel. Brennst.-Warme-Kraft 13 (1961), 532/537. [20] Frensch, J.: Uber das dynamische Verhalten von Heiftdampf-Uberhitzern. Schoppe & Faeser Techn. Mitt. (1 960) 3, 66/72. 220 [31 ] [32] [33] 11.2 Bibliography 11Appendix Hocker, K.H. u. Weimer, K.: Lexikon der Kern- und Reak- tortechnik. Franckh'sche Verlagshandlung, Stuttgart. Hoger, R.: Regelverhalten eines Uberhitzers. Regelungstechnik 9 (1961) 6, 228/232. Hoger, R.: Beanspruchung der Dampferzeuger-Eintrittssammler durch Warmespannungen infolge Ausfalls von Hochdruckvorwarmern. Warme 75 (1969) 2/2, 60/64. 221 [41] Hermann, R.: Messung und Berechnung des regeldynamischen Verhaltens eines (jberhitzers. Fortschritt-Ber. d. VDI-Zeitschrift, Reihe 6 Nr. 9 (1965), VDI-Verlag Diisseldorf. [42] Hermann, R.: Das regeldynamische Verhalten der Uberhitzung bei Beriicksichtigung der Koppelungen mit anderen Teilen eines Dampferzeugers. Diss. TH Stuttgart 1965. [43] Hermann, R.: Vorausbestimmung der Regelgiite der Dampftemperaturregelung von Trommelkesseln mit dem Analogrechner. Regelungstechnik 14(1966) 10, 469/475; u. Nr. 11, [34] Hofmeister, W.: Kennfaktoren von Dampfiiberhitzern zur [35] Beurteilung der regeltechnischen Eigenschaften. Conti-Elektro-Ber. 12(1966) 2, 113/120. Hofmeister, W. u. Tannen, T.: Vorausbestimmung der erforderlichen Stellgeschwindigkeit und des Regelverhaltens von HD-Reduzierstationen. Conti Elektro-Berichte 1 1 (1965) 3, S. 108/113. [44] [36] Hofmeister, W.: Theoretische Analysen zur Dynamik der geregelten Rauchgasrezirkulation in Dampferzeugern. Conti Elektro-Ber. 14(1968) 2, 116/124. Hermann, R. u. Eichner, M.: Uber die Lastabhangigkeit der Dampftemperatur-Regelung des Mehrgrofien-Regelsystems ,,Trommelkessel". Brennstoff-Warme-Kraft 20 (1968) 10, 453/459. [45] [37] Hofmeister, W.: Regelschaltungen fiir Durchlauf-Dampferzeuger mit Beispielen im Transistocont-System. Conti Elektro-Ber. 13 (1967) 2, 1 17/1 28. Hermann, R.: Einfache mathematische Modelle fiir das dynamische Verhalten beheizter Rohre. Warme 75 (1969) 2/2,89/94. [46] Kindermann, W.: Predetermination of Control Results for Reheaters in Steam Generators. II, IFAC-Kongrefi Basel 1963, Butterworth-Verlag, London. [47] Klefenz, G.: Das dynamische Verhalten von HeifidampfUberhitzem. Schoppe & Faeser Techn. Mitt. (1958) 1, 17/24. [48] Klefenz, G.: Einfaches Berechnungsverfahren fiir die Dampftemperatur-Regelung von Dampferzeugern. VGB-Mitt. 72 (Juni 1961), 191/200. [49] Klefenz, G.: Regelungsdynamische Untersuchung eines Bensonkessels. Brennstoff-Warme-Kraft 17 (1965) 1 1, 532/540. [38] Hofmeister, W.: Zur optimalen Temperaturregelung an Dampfiiberhitzern. Conti Elektro-Ber. 15 (1969) 1, 32/38. [39] Isermann, R.: Das Verhalten der Dampftemperaturrege- lung des Mehrgrofeenregelsystems „Trommelkessel". IFAC-Symposium 1968, Bd. 2. [40] 519/522. Isermann, R.: Das regeldynamische Verhalten von Oberhitzern. Fortschritt-Ber. d. VDI-Zeitschrift, Reihe 6 Nr. 4 (1965), VDI-Verlag Diisseldorf. 222 [50] [51] Klefenz, G.: Charakteristische Grolien fiir die Regelung von HeiBdampferzeugern. Schoppe & Faeser Techn. Mitt. (1959) 1, 2/7. [53] [54] zustanden. BWK 20(1968) 10, S. 486/493. Klefenz, G.: Simulatoren und elektrische Modelle in Forschung und Betrieb. Elektro-Technik (1966) 38, 882/885. [63] Kleinau, W.: Regeldynamik von Dampfturbinen mit Zwischeniiberhitzung. Brennst.-Warme-Kraft 17 (1965) 6, 304/306. Michel: Gegenwartiger Entwicklungsstand des Benson¬ kessels. Energie 15 (1963) 5, S. 190/199. [64] Miller, C. u. Waldmann, H.: Eignung eines Zwangsdurchlauf-Braunkohlendampferzeugers von 960 t/h fiir das Gleitdruck/Gleittemperatur-Verfahren. BWK 21 (1969) 6, S. 305/316. [65] Oetker, R. u. Schroeder, G.: Die Regelbarkeit des Druckes von Dapipferzeugern. Brennst.-Warme-Kraft 3 (1951) 11, 361/366. [66] Opitz, W. u. Ehlers, G.: Automationstendenzen in Kraftwerken. Mefiwerte (1969), 9. 35/39. [67] Oppelt, W.: Kleines Handbuch technischer Regelvorgange. Verlag Chemie, Weinheim, III.Auflage 1960. [68] Pauli, B.: Berechnung des Ubertragungsverhaltens dampfdurchstromter Rohre unter Beriicksichtigung des tatsachlichen Eingabe-Verhaltens. BWK 1 7 (1965) 8, S. 402/403. [69] Kleinau, W.: Regeldynamik von Dampfturbinen mit Zwischeniiberhitzung. Warme 71 (1964), H. 3, S. 93/100, H. 4, S. 132/141. [56] Kohle, S.: Automatisches Anfahren von Dampferzeugern unter Beriicksichtigung zulassiger Materialspannungen. Regelungstechnik 17 (1969) 7, 293/297. [57] Laubli, F.: Zum Problem der Nachbildung des dynamischen Verhaltens von Dampferzeugern auf Analogie-Rechenmaschinen. Techn. Rundschau Sulzer (1961), 35/42. [60] Latzel, W.: Zur elektronischen Regelung von Dampfturbi¬ nen mit Zwischeniiberhitzung bei verschiedenen Betriebs- Ledinegg, M.: Das Verhalten von Zwangsdurchlaufkesseln bei Lastanderungen. Brennst.-Warme-Kraft 12(1960), 197/206. Kleinau, W.: Parallelarbeit druckgeregelter Turbinen. BWK 15 (1963) 5, 247/256. [59] 223 [62] [55] [58] [61 ] Klefenz, G.: Regelungsdynamische Untersuchung eines Bensonkessels. Dissertation TH Darmstadt (1965). [52] 11.2 Bibliography 11Appendix Laublj, F.: Dynamik durchstromter Verdampferrohre. Techn. Rdsch. Sulzer 50 (1968) 4, 181/190. Laubli, F. u. Evers, K.: Dynamik der Speisewasserregelung Perycz, S.: Zur Beurteilung der Regelschaltungen von Dampfturbinen mit Zwischeniiberhitzung, insbesondere von Einrohrkesseln mit iiberlagerter Wasser-Rezirkulation. im Blockbetrieb. Techn. Rdsch. Sulzer, Forschungsheft 1968, S. 15/21. Regelungstechnik 11 (1963), 8. 343/347; 9, 393/398. Latzel, W.: Die Frequenzgangdarstellung der Turbine und die Anpassung des elektronischen Turbinenreglers. BBC-Nachrichten 1968, H. 6, S. 291/296. [70] Peterka, V.: Analytische Ermittlung der Dampfdruckdynamik in Zwangsdurchlaufkesseln. Messen, steuern, regeln 7 (1964) 6, 229/239. 224 11Appendix [71] Pressler, G.: Regelungstechnik. [72] [73] [74] [75] [76] [77] Profos, P.: Die Regelung von Dampfanlagen. Springer-Verlag 1962. Profos, P.: Das dynamische Verhalten von Zwangslaufverdampfern bei ungleich verteilter Beheizung. Regelungstechnik 13 (1965) 2, S. 57/62. [84] Profos, P.: Ober die Glattung von Dampftemperaturschwankungen durch die Rohrleitung. Warme 75 (1969) 2/3,85/88. Profos, P. u. Gelpke, M.: Zur praktischen Durchfiihrung der Optimierung der Reglereinstellung bei stochastischer Bewegung der Storgrofie. Neue Technik 1968, A3 145/155. Profos, P. u. Bachmann, U.: Berechnung des dynamischen [85] Profos, P.: Lastabhangige Anpassung der Reglereinstellung bei (Jberhitzer-Temperaturregelung. Schweizer Bauzeitung83 (1965) 15, 241/243. Profos, P.: Untersuchungen iiber die optimale Einstellung des Oberhitzer-Temperaturreglers. Brennstoff-Warme-Kraft 18 (1966) 7, 326/332. Quack, R.: Automatisierung von Dampfkraftwerken. BWK 15 (1963) 2, 53/61. BI-Hochschultaschenbiicher 63/63a. Verhaltens von Zwangsstrom-Verdampfersystemen. Neue Technik 3 (1961), 41 1/424. Profos, P.: Betrachtungen liber kiinftige Regelaufgaben und Regelprobleme in Dampfkraftwerken. Mitteilungen der VGB (1967) 109, 224/232. Profos, P.: Grenzen der Regelungsmoglichkeiten von HochMitteilungen der VGB (1960) 67, 211/221. [79] Profos, P.: Die Regelung von Zwangsdurchlaufkesseln. Brennst.-Warme-Kraft 16 (1964) 10, 498/503. Profos, P.: Die Dynamik zwangsdurchstromter Verdampfersysteme. [86] [87] [81] [82] Profos, P.: Das dynamische Verhalten der Regelstrecke von Druckregulierungen. Schweizer Archiv 1951, 114/119. Profos, P.: Vektorielle Regeltheorie. Verlag Leemann, Zurich, I. Aufl. 1943, II. Aufl. 1954. Quack, R.: Die Dampftemperaturregelung als Teil der Ge- samtkesselregelung. Brennstoff-Warme-Kraft 19 (1967) 6, 285/286. [88] Quack, R.: Die selbsttatige Regelung von Dampferzeugeranlagen. Mitteilungen der VGB (1959) 58, 1/11. [89] Sartorius, H. u. Matuschka, H.: Grundlagen der Reaktordynamik. Regelungstechnik 4 (1956) 7, 165/171. [90] Schmid, B.: Automatischer Betrieb von Warmekraftwerken. Siemens-Zeitschrift 43 (1969) 2, S. 63/72. [91] Schone, A.: Das dynamische Verhalten von Warmetauschern. R. Oldenbourg-Verlag, Munchen - Wien. [92] Schroder, K.: Grofie Dampfkraftwerke, 3. Band, Teil B, Springer-Verlag, Berlin/Heidelberg/New York 1968. Regelungstechnik 10 (1962), 529/536. [80] 225 [83] leistungskesseln. [78] 11.2 Bibliography [93] Schulz, R.: Das dynamische Verhalten eines Kreuzstrom- Warmetauschers. Warme 76(1970) 1/2, 13/18. [94] Profos, P.: Dynamik der Oberhitzerregelung. Regelungstechnik 6 (1958) 7, 239/246. 15 Klefenz Schulz, R.: Regulace teploty a tlaku prehrate pary bubnoveho kotle. (Die Temperatur- und Druckregelung des uberhitzten Dampfes eines Trommelkessels.) Energetika 18 (1968) 9, S. 413/419. 226 [95] 11Appendix Spliethoff, H.: Das Regelverhalten leistungsgeregelter 11.2 Bibliography [105] Zwangsdurchlauf-Dampferzeuger. [96] [97] [98] [99] [100] [101] [102] [103] [104] Dissertation 1959, TH Stuttgart. Stepan, J.: Der EinfluB von Konstruktionsparametern auf die dynamischen Eigenschaften von Uberhitzern. Brennst.-Warme-Kraft 14(1962) 12, 580/584. Stoklossa, K. u. Oude-Hengel, H.: Ober das dynamische Verhalten von Wasserrohrkesseln bei plotzlichen Lastanderungen und bei Storungen. Energie 21 (1969) 7/8, 228/238. Strejc, V.: Approximation aperiodischer Obergangscharakteristiken. Acta Technica Prag 1958, Nr. 1, 1/25. Unbehauen, H.: Stabilitat und Optimierung von Kaskadenschaltungen zur Regelung der Frischdampftemperatur in Zwangsdurchlauf-Dampferzeugern. Warme 75 (1969) 2/2,68/71. Unbehauen, H.: Nachbildung der Frischdampftemperatur- [106] 227 VDI/VDE-Richtlinie 3503: Dampferzeuger-Regelung — Frischdampftemperatur-Regelung. VDI-Verlag Diisseldorf. VDI/VDE-Richtlinie 3504, Blatt 1 u. 2.: DampferzeugerRegelung; Feuerraumunterdruck-Regelung. [107] VDI/VDE-Richtlinie 3505, Blatt 1 u. 2.: DampferzeugerRegelung; Traggasstrom- und Sichtertemperatur-Regelungen in Kohlemiihlen. [108] [109] VDI/VDE-Richtlinie 3506: Dampferzeuger-Regelung — Speisewasserregelung an Durchlaufdampferzeugern. VDI-Verlag Diisseldorf. VDI/VDE-Richtlinie 3507: Abnahme von Regelanlagen fur Dampferzeuger. [110] [Ill] [112] VDI/VDE-Richtlinie 3527: Kernreaktor-Regelung. VDI/VDE-Datenblatter zur Reaktorregelung. VDI-Verlag. Winkler, D.: Untersuchung verschiedener Verfahren fiir die Regelung des Druckes von Dampferzeugern. Regelungstechnik 11 (1963) 6, 253/261. Winkler, D.: Der Einflufi der Speicherzeitkonstante auf die Regelung von Dampferzeugern. Regelungstechnik 1 1 (1963) 12, 536/543. regelung eines Dampferzeugers am Analogrechner unter Berlicksichtigung der Koppelung mit anderen Regelkreisen. AICA-Kongreft Lausanne, Session C4, 1967. [113] Unbehauen, H.: Zur Abhangigkeit der Stabilitat und Regelgute von der Last bei der vermaschten Frischdampftemperaturregelung eines Trommelkessels. Brennstoff-Warme-Kraft 20 (1968) 10, 463/469. [114] Wittchow, E.: Anfahrsysteme fur Bensonkessel. Mitteilungen der VGB 49 (1969) 5, 319/325. [115] Zwetz, H.: Verbesserung der Druckregelung bei Dampferzeugern. Brennst.-Warme-Kraft 12 (1960), 206/21 1 . Zwetz, H. u. Ernst, D.: Untersuchung der Frischdampftemperaturregelung bei Dampferzeugern mit einem Analog¬ Varcop, L.: Die Dynamik zwangsdurchstromter Verdampfersysteme unter Beriicksichtigung von Druckanderungen des Stromungsmediums. Regelungstechnik 15 (1967) 9, 404/412. VDI/VDE-Richtlinie 3501, Blatt 1 u. 2: DampferzeugerRegelung; Brennstoff- und Verbrennungsluft-Regelung. VDI/VDE-Richtlinie 3502, Blatt 1 u. 2.: Dampferzeuger- Regelung; T rommelwasserstand-Regelung. [116] rechner. [117] Brennstoff-Warme-Kraft 10 (1958) 8, 353/361 . Zimmermann, H.: Die Bedeutung der Kraftwerksregelung fiir die Netzfiihrung. VGB-Fachtagung ,,Automatisierung, Meft- und Regelungs¬ technik 1969". Mitt. d. VGB 49 (1969) 4, 263/268. 11 Appendix 228 11.2 Bibliography [126] Anneveld, H.: Simulation der Dynamik eines Zwischeniiberhitzers. VGB Kraftwerkstechnik 55 (1975) 1, 54/61. Dingier, M. u. Hofmeister, W.: Vergleich mathematischer Modelle eines Kraftwerkblockes mit dem gemessenen dynamischen Verhalten durch Simulation auf einem Analogrechner. Regelungstechnische Praxis 4 (1975) 117/1 19, Teil 1; 5 (1975) 145/151, Teil 2. [127] Bosken, W. u. Scheele, K.: Netzkennlinienregelung bei den HEW. VGB Kraftwerkstechnik 58 (1978) 4, 247/256. Dingier, M., Hofmeister, W. u. Sodeik, G.: Regelung von Dampferzeugung und Sammelschienendruck. Regelungstechnische Praxis 20 (1978) 12, 348/354. [128] Bibliography Continuation since 1970 [118] [119] [120] [121] [122] 229 Borsi, L.: Vergleichende Untersuchung liber Regelschaltungen fur Blockeinheiten mit Zwangsdurchlaufdampferzeugern. Brennstoff-Warme-Kraft 25 (1973) 3, 69/75. [129] Borsi, L., Hofmeister, W., Falgenhauer, G. u. Reichel, H.: Untersuchung liber Dynamik und Regelverhalten von Benson-Dampferzeugern. VGB Kraftwerkstechnik 58 (1978) 4, 240/246. Dolezal, R.: Zeitverhalten des Wasserstandes bei einem Dampferzeuger mit Wasserumlauf. Warme 76(1970) 5, 125/130. Dolezal, R., Klug, M. u. Plackmeyer, I.: Planung der beim Speisepumpenausfall eingreifenden Funktionsgruppen mit Hilfe eines nichtlinearen Blockmodells. VGB Kraftwerkstechnik 58 (1978) 7, 485/492. [130] Dolezaf R.: Zeitverhalten des Wasserstandes bei einem Borsi, L. u. Kallina, G.: Entkopplungsregelungs-Entwicklung und Erprobung eines neuen Regelkonzepts fur Kraft- [131] Drucks, G.: Rechnerische Simulation des dynamischen Verhaltens eines Kraftwerksblockes nach Turbinenschnellschlufi. VGB Kraftwerkstechnik 60 (1980) 1, 23/27. [132] Falgenhauer, G.: Beitragsmoglichkeiten der Speisewasser-, Kondensat- und Anzapfdampfstrome zur schnellen Leistungsanderung fossil befeuerter Kraftwerksblocke. VGB Kraftwerkstechnik 60 (1980) 1, 18/23. Franke, J., Eitelberg, E., Kallina, G., Weber, M. u. Witte, U.: Vorausberechnung des dynamischen Verhaltens eines Kraftwerksblockes. VGB Kraftwerkstechnik 59 (1979) 2, 124/128. Forschungsberichte der VdTUV (Vereinigung der Technischen Uberwachungs-Vereine): Prozefidynamik, rechn. Simulation des dynamischen Verhaltens konventioneller KW-Blocke bei Storfallen. Dampferzeuger mit Wasserumlauf. Warme 76(1970) 5, 125/130. werksblocke. VGB Kraftwerkstechnik 58 (1978) 8, 561/665. [123] Borsi, L.: Erweitertes lineares Modell eines Kraftwerksblockes mit Durchlaufdampferzeuger. Siemens Forsch.- u. Entwickl. Bericht Bd. 3 (1974) 5, 274/280, Springer-Verlag. [124] Braun, B.: FUllungsbeeinflussung von Zwangsdurchlauf DE zur Verbesserung des Temperatur- und Leistungsverhaltens. Fortschritt-Ber. d. VDI-Zeitschrift, Reilie 6 Nr. 38. [125] Buchwald, K.: Neuere Erkenntnisse auf dem Gebiet der zulassigen Anfahr- und Lastandergeschwindigkeiten von Dampfturbinen. VGB Kraftwerkstechnik 52 (1972) 5, 416/424. [133] [134] 230 [135] 11.2 Bibliography 11Appendix Glattfelder, A.H.: Reglerstrukturen zur Ausnutzung der zulassigen Lastanderungsgeschwindigkeit, untersucht an der Leistungsregelung eines Trommelkessels. [144] Isermann, R.: Einfache mathematische Modelle fur das regeldynamische Verhalten wasser- und dampfbeheizter Kreuzstromlufterhitzer in Klimaanlagen. Neue Technik 4 (1971) 167/174. [145] Kauffeld, W.: Die Manovrierfahigkeit konventioneller Kraftwerksblocke im Netzbetrieb aus der Sicht des praktischen Betriebes. VGB Kraftwerkstechnik 57 (1977) 6, 380/392. [146] Klefenz, G. und Seidel, R.: Regelverhalten eines im gesteuerten Gleitdruck betriebenen Kraftwerksblockes. VGB Kraftwerkstechnik 56 (1976) 2, 83/90. [147] Klefenz, G. und Maszuttis, K.: Drei Varianten der Blockregelung — eine vergleichende Untersuchung. Regelungstechn. Praxis u. Prozefi-Rechentechnik 1974, Brennstoff-Warme-Kraft 22 (1970) 12, 584/589. [136] Glattfelder, A.H.: Nahezu schnelligkeitsoptimale Dampfdruckregelung eines olgefeuerten Kessels. Brennstoff-Warme-Kraft 24 (1972) 6, 223/228. [137] Glattfelder, A.H.: Vereinfachte Strukturen zur beinahe schnelligkeitsoptimalen Dampfdruckregelung eines Trom¬ melkessels. Brennstoff-Warme-Kraft 25 (1973) 3, 75/79. [138] Grebe, E., Handschin, E., Haubrich, H.J. u. Traeder, G.: Dynamische Langzeitstabilitat von Netzen. Elektrizitatswirtschaft 78 (1979) 19, 725/731. [139] Hintergraber, M.: Betrachtungen zu einem Rechenmodell fur instationiire Vorgange in einer konventionellen Kraftwerksanlage. VGB Kraftwerkstechnik 52, Heft 2, 118/126. [140] Hirschfelder, G.: Ein Beitrag zur Kondensat-Leistungsregelung eines Blockkraftwerkes fur Gleitdruckbetrieb mit Kohlefeuerung. VGB Kraftwerkstechnik 5 1 (1971) 2, 151/164. [141] Hofmeister, W.: Praktische Erfahrungen in der Simulation von Regelvorgangen. Regelungstechnische Praxis 3 (1970) 87/95. [142] Hoger, R. Prof. Dr.: Das Ubergangsverhalten von Zwangsdurchlaufkesseln. Warme 77(1971)4,99/107. [143] Honig, O.: Untersuchung des dynamischen Verhaltens eines konvektiv beheizten Naturumlauf-Dampferzeugers mit einem mathematischen Modell. Fortschritt-Ber. d. VDI-Zeitschrift, Reilie 6 Nr. 67 (1980). 231 1,9/16. [148] Laubli, F., Le Febve, D. u. Palanikumar, P.: Dynamik der Blockleistungsregelung und der ubergeordneten Netzfrequenzregelung in Dampfkraftwerken. Techn. Rdsch. Sulzer, Forschungsheft 1973, 40/49. [ 149] Laubli, F. u. Svoboda, C.: Dynamik des 430 t/h-Einrohrdampferzeugers des Kohle-Ol-Kraftwerkblockes Naantali III. Techn. Rdsch. Sulzer 1 (1975) 57/64. [150] Latzel, W.: Verbesserte Nachbildung des dynamischen Verhaltens von beheizten Rohren. Warme 79(1973) 60/66. [151] Leithner, R. : Druckanderungen im Hochdruckteil und Zwischen uberhitzer eines Dampferzeugers infolge Notschaltungen. Brennstoff-Warme-Kraft 26 (1974) 6, 249/257. [152] Leithner, R.: Dynamik im Grofidampferzeugerbau. Elektrizitatswirtschaft 79 (1980) 8, 281/290. [153] Leithner, R., Herrmann, W. u. Trautmann, G.: Rauchgasdruckschwingungen im Dampferzeuger bei Ausfall der Feuerung. VGB Kraftwerkstechnik 59 (1979) 4, 305/316. 232 11Appendix 11.2 Bibliography 233 [154] Leithner, R. u. Linzer, V.: Einfaches Dampferzeugermodell. Fortschritt-Ber. d. VDI-Zeitschrift, Reihe 6 Nr. 41. [165] [155] Martin, P.: Einige Gedanken zur Wechselwirkung von Netz und Kraftwerk. VGB Kraftwerkstechnik 59 (1979) 5, 394/404. Oude-Hengel, H. v.: Druckverhalten von Grofikesselanlagen bei Lastabwurf. Warme 84(1978) 1, 19/25. [166] Oude-Hengel, H. v.: Uber das dynamische Verhalten von Wasserrohrkesseln bei plotzlichen Lastanderungen und bei Storungen. Energie 21 (69) 7/8,228/238 Energie 22 (70) 4,107/113 Energie 22 (70) 9, 275/283. [167] Profos, P. u. Bachmann, U.: Berechnung des dynamischen Verhaltens von Zwangsstrom-Verdampfersystemen. Neue Technik 3 (1961), 41 1/424. [168] Profos, P. u. Juzi, H.: Untersuchung liber die Giite der [156] Martin, P. u. Mathias, G.: Einige regeltechnische Gesichtspunkte zum Umleitbetrieb bei Blockkraftwerken. VGB Kraftwerkstechnik 54 (1974) 10, 648/657. [157] Mathias, G.: Regelungsaufgaben an Dampfturbinen. VGB Kraftwerkstechnik 59 (1979) 2, 119/124. [158] [159] [160] Mathias, G. u. Martin, P.: Regeldynamischer Vergleich von Uberlastschaltungen an einem gleitdruckgeregelten Turbosatz mit Zwischeniiberhitzung. Brennstoff-Warme-Kraft 23 (1971) 10, 429/433. Mathias, G.: Die Auswirkung von Unempfindlichkeiten im Turbinenregelkreis auf Turbine und Verbrauchernetz. VGB Kraftwerkstechnik 54 (1974) 6, 390/395. Frischdampftemperatur-Regelung bei Geradeausbetrieb. VGB Kraftwerkstechnik 50 (1970) 3, 207/21 1. [169] Mathias, G.: Zur Simulation der Wirkleistungsdynamik parallelgeschalteter elektrischer Energieversorgungsnetze. VGB Kraftwerkstechnik 57 (1977) 7, 467/473. [161] Mathias, G. : Netzlastzuschaltungen auf Kraftwerksturbosatzen nach einem Netzzusammenbruch. VGB Kraftwerkstechnik 58 (1978) 6, 397/403. [162] May, H., Meinhardt, D.,Oude-Hengel,H.u.Stute,H.: Berechnung des dynamischen Verhaltens von Feuerungen und Kesselanlagen. Sonderdruck aus VDI-Berichte Nr. 146 (1970). [163] Mayinger, F., Reineke, M., Schramm, R. u. Steinmetz, P.: Ein Rechenprogramm zur nichtlinearen Simulation der Dynamik von Benson-Dampferzeugern. Brennstoff-Warme-Kraft 30 (1978) 8, 329/333. [164] Milde, P.: Theoretische Prozefianalyse eines NaturumlaufDampferzeugers. Messen, steuern, regeln 21 (1978) 8, 432/437. Reineke, H., Schramm, R. u. Steinmetz, P.: Digitale Simu¬ lation der nichtlinearen Dynamik von Benson-Dampf¬ erzeugern. Tagung Forschung in der Kraftwerkstechnik 80 (VGB), 254/260. [170] Reinhardt, A.: Die Regelung von Siedewasserreaktoren bei unterschiedlichen Systemschaltungen. Atom u. Strom (1970) 3/4, 53/57. [171] Rosel, G. u. Roder, H.: Ermittlung eines nichtlinearen Modells fur grofie Dampferzeuger. Messen, steuern, regeln 21 (1978) 2, 73/77. [172] Schlegel, G.: Optimierung von Struktur und Parameter des Mehrgrofien-Regelsystems Naturumlauf-Dampferzeuger. VGB Kraftwerkstechnik 54 (1974) 7, 493/498. [173] Schomer, E.: Dynamische Untersuchung eines NatriumDampferzeugers. Atom u. Strom (1970) 3/4, 62/70. 234 [174] [175] 11Appendix Sekoguchi, K.: Analyses and Field Tests of Once-through Boiler Dynamics. Bulletin of the JSME 13 (1970) 63, 1084/1095. Torborg, H.M. u. Bosken, W.: Netzkennlinienregelbetrieb einer gasbefeuerten Gleitdruckanlage mit Kondensatleistungsregelung - 2 Jahre Betriebserfahrung mit Moorburg. VGB Kraftwerkstechnik 56 (1976) 12, 735/741. [ 176] Tyss0, A. : Modelling and Parameter estimation of ship boilers. 5. 1FAC Symposium of Identification and System Para¬ meter Estimation. Sept. 79 Darmstadt. [177] Unbehauen, H., Necker, P. u. Gohring, B.: Einige Moglichkeiten zur Modellbildung und Parameteroptimierung komplexer Regelungssysteme am Beispiel einer Kaskadenregelung. Messen, steuern, regeln 14 (1971) 9, 350/353. [178] [179] [180] [181] Vofi, K., Herbrik, R. u. Necker, P.: Untersuchungen der Struktur und des dynamischen Verhaltens der Regelsysteme von Durchlaufdampferzeugern. VGB Kraftwerkstechnik 50/2, 88/94. 11.2 Bibliography 235 Additionally Selected Reference Material in English [182] Anderson, P.M., Fouad, A.A.: Power System Control and Stability. Iowa State University, Ames, 1977. [ 183] Anson, D.: Availability of Fossil-Fired Steam Power Plants. EPRI FP-422-SR, June 1977. [184] Anson, D., Clarke, W.H.N., Cunningham, A.T.S., Todd, P.: Carbon Monoxide as a Combustion Control Parameter. J.Inst .Fuel 44 (197 1), April , 19 1/ 195 . [185] Anthony, E.J., Rowe, W.G.E.: Possibility for Combined Heat and Power Schemes in the U.K. IMechE C83/77 (1977), 25/32. [186] Arscottf J.A., Chew, P.E., Lawn, C.J.: Improvements in Com¬ bustion Efficiency Through the Matching of Air and Fuel on an Oil-Fired Boiler. J.Inst.Energy 53 (1980), March, 3/15. [187] Aschner, F.S.: Planning Fundamentals of Thermal Power Plants. Wiley, New York, 1978. [188] Babcock & Wilcox: Steam. Its Generation and Use. Babcock & Wilcox, New York, 1978. [189] Welfonder, E.: Regeldynamisches Zusammenwirken von Kraftwerken und Verbrauchern im Netzverbundbetrieb. Elektrizitiitswirtschaft 79 (1980) 20, 730/741. Bechey, M.A., Crump, R.F.E.: Instrumentation and Control of Modern Boiler-Turbine Units in C.E.G.B. Power Stations. Morgan, London, 1967. [190] Wilhelm, H. u. Golz, M.: Einsatz der Simulation beim Kombiblock des Kraftwerks Lausward. BBC-Nachrichten 1977, H. 1 1 , S. 458/465. Bell, E.C., Whitehead, R.W.: Basic Electrical Engineering and Instrumentation for Engineers. Granada, London, 1977. [191] Bennett, S., Linkens, D.A.: Computer Control of Industrial Pro¬ cesses. Chapter 9: Direct Digital Control in CEGB Power Station. Peter Peregrinus (IEE), Stevenage, 1982. [192] Ben-Yaacov, G.: Considerations for Applying Advanced Control Technology with Power Plant Control. ISA: Instrumentation in the Power Industry (1982), 165/172. Welfonder, E. : Berechnung und Approximation des Gesamtiibertragungsverhaltens von Zwangsdurchlaufdampferzeugern. Regelungstechnik 22 (1974) 8, 243/250, Teil 1 Regelungstechnik 22(1974) 10, 320/321, Teil 2. [193] [194] [195] [204] Chang, K.Q., deMello, F.P.: Transient Efficiencies in Electric Power Plants. EPRI EL-2439, June 1982. [205] Binstock, M.H., Criswell, R.L.: Two Boilers - One Turbine: Multiple Blending System. ISA: Instrumentation in the Power Industry (1982), 71/80. Chaussard, R., Grauvogel, J., Davoust, G.: Rational Adjustment of the Controls of a Thermal Power Station. 3rd IFAC Congress, London (1966), 21A, 1/13. [206] Cleland, P.J., Sauk, P.L.: Power Plant Control — an Overview. Joint Automatic Control Conference (1980), WA3-A, 1/6. [207] Crawford, A.R., Gregory, M.W., Manny, E.H., Bartok, W.: Magnitude of S02, NO, C02 and 02 Stratification in Power Plant Ducts. EPA (U.S. Environmental Protection Agency) — 600/2-75-053, September 1975, 1/160. [208] Daniels, J.H.: Design Considerations for Furnace Draft Control Systems. ISA: Instrumentation in the Power Industry (1977), 93/98. [209] Debelle, J., Bayens, R., Lemoine, J.C1., Van de Meulebroeke, F.: Some Applications and Trends in Automatic Control of Thermal Power Plants. 7th IFAC Congress, Helsinki (1978), 57/72. [210] Dewaele, W.: Structures of Digital Process Automation Systems. Journal 'A* 23 (1982), No. 2,51/60. [211] Diamant, R.M.E.: Total Energy. Pergamon, Oxford, 1976. [212] Dierken, W., Kiirten, H.: Unit Control Concept for Fossil-Fuel Thermal Power Stations. KWU 359-101, August 1976, 1/11. Binstock, M.H.: Total Coordinated Control of the Power Gene¬ ration Process. ISA: Instrumentation in the Power Industry (1979), 101/114. Bloom, N., Burns, E.T. (Editors): Plant Performance Testing and Evaluation Workshop. EPRI WS-78-134, November 1979. [197] Borsi, L., Hofheister, W., Falgenhauer, G., Reichel, H.: Investiga¬ tion into the Dynamics and Control Characteristics of Benson Steam Generators. VGB Kraftwerkstechnik (English Issue) 58 (1978), No. 4, 221/227. Bross, T.: Experience with Travelling Grate and Vibrating Grate Firings Using Bituminous Coal. VGB Kraftwerkstechnik (English Issue) 61 (1981), No. 10, 743/746. [199] [200] 237 Dyer, M.F., Bigeard, C., Backman, N., Billi, B., Deurvorst, Hernandez, M., Massart, R., Meclot, B.: Improvement of the Per¬ formance of Thermal Power Stations. UNIPEDE Congress, Brussels (1982), 20/D.l, 1-32. [196] [198] 11.2 Bibliography 11Appendix 236 Buzina, M.: Development Problems with Once-Through ForcedFlow Steam Generators. Combustion 49 (1977) No. 3 (September), 35/42. Carlson, J.R.: Identification of Root Causes of Plant Outages Attributed to Boiler Controls. EPRI CS-2028, September 1981. [201] C.E.G.B.: Modern Power Station Practice. Vol. 6. Instrumentation, Controls & Testing. Pergamon, Oxford, 1971. [213] Diethelm, M.: The Control of Sulzer Monotube Steam Generator Plants Operating at Supercritical Pressures. Sulzer Technical Review 4/1960, 23/29. [202] C.E.G.B.: Modern Power Station Practice. Vol. 7. Operation and Efficiency. Pergamon, Oxford, 1971. [214] Diethelm, M.: The Control of Sulzer Monotube Steam Generators with Reheating. Sulzer Technical Review 4/1959, 3/9. [203] C.E.G.B.: Modern Power Station Practice. Vol. 8. Nuclear Power Generation. Pergamon, Oxford, 1971. [215] Dixon, R.R., Kraje, N.B., Roberts, R.C.: Current Fossil Fuel Power Plant Performance Monitoring. Volume 1: Practices. EPRI EL-3339, January 1984. i 238 11Appendix 11.2 Bibliography 239 [216] Dixon, R.R., McNair, H.D.: Current Fossil Fuel Power Plant Per¬ formance Monitoring. Volume 2: Recommended R&D Programs. EPRI EL-3339, July 1984. [228] Fredericks, P.: Replacement of Analog Control System by Micro¬ processor-Based Control Systems on Utility Boilers. Proc. Am. Power Conf. 43 (1981), 478/481. [217] DoleZal, R., Varcop, L.: Process Dynamics. Automatic Control of Steam Generation Plant. Elsevier, London, 1970. [229] Gadyak, V.A.: Choosing the Cross-Section for Determining the Temperature and Composition of Flue Gases. Thermal Engineering 19 (1972), No. 10, 32/35. [218] Duel', M.A.: Criteria of Optimal Control of Generating Units. Thermal Engineering 20 (1973), No. 3, 42/48. [230] [219] Dunnett, R.M., Wells, R.: Improvements in Steam Temperature Control in a Modern Oil-Fired Power-Station Boiler. IEEProc. 127 Pt.D. (1980), No. 1, January, 7/12. Gerber, H.R.: The Sulzer Monotube Steam Generator as a Control Exercise. Sulzer Technical Review 1/1969, 27/37. [231] Gibson, J.E., Rekasius, Z.V., McVey, E.S., Sridhar, R., Leedham, C.D.: A Set of Standard Specifications for Linear Automatic Control Systems. AIEE Trans. 80 (1961), May, 65/77. [232] Grant, J.: Boiler Flue Gas — Its Analysis and Use in Burner Management and Combustion Control in Oil Fired Power Plant. Combustion 52 (1980), No. 6 (December), 10/16. [233] Hagedorn, F., Klefenz, G.: H&B Power Station Control. Part I: Unit Load Control. Part II: Combustion Control. Hartmann & Braun, Schoppe & Faeser, Monograph 3587 EN (1981), 1/11. [220] Durant, O.W., Zadiraka, A.J.: Control of Utility Pulverized-CoalFired Drum Boilers During Load Changes. Proc.Am. Power Conf. 43 (1981), 274/286. [221] Durant, O.W., Lansing, E.G.: Furnace Implosions and Explosions. Combustion 48 (1976), No. 3 (September), 12/21. [222] Elgerd, 0.: Automatic Generation Control. IFAC Symposium on Aut. Control and Protection of El. Power Systems, Melbourne (1977), 1/19. [223] Etherington, H. (Editor): Nuclear Engineering Handbook. McGraw-Hill, New York, 1958. [234] Hofer, P.: Heat and Power — Cheaper with Cogeneration. International Power Generation, July/ August 1984, 34/35. [224] Falgenhauer, G.: Possible Contributions of Feed-Water-, Conden¬ sate- and Extraction-Steam Flows to Achive Rapid Power Variations in Fossil-Fuel-Fired Power Plant Units. VGB Kraftwerkstechnik (English Issue) 60 (1980), No. 1, 18/22. [235] Hougen, J.O.: Control Strategies for Pulverized Coal-Fired Systems. ISA Transactions 19 (1080), No. 1, 29/35. [236] Fenwick, D.R., Wright, W.F.: Review of Trends in Excitation Systems and Possible Future Developments. Proc. IEE, Vol. 123 (1976), No. 5, 413/420. Hughes, F.M.: Improvement of Turbogenerator Transient Per¬ formance by Control Means. Proc. IEE 120 (1973), No. 2,233/240. [237] Fink, D.G., Carroll, J.M. (Editors): Standard Handbook for Electrical Engineers. McGraw-Hill, New York, 1968. IEEE Committee Report: Bibliography of Literature on Steam Turbine-Generator Control Systems. IEEE Trans. PAS-102 (1983), No. 9, 2959/2970. [238] IEEE Tutorial Course 77 TUDO 010-9-PWR: deMello, F.P., Undrill, J.M.: Automatic Generation Control. 1977. [239] IEEE Tutorial: Power Plant Response. 83 TH0105-7-PWR, 1983 PES Summer Meeting. [225] [226] [227] Franke, J., Eitelberg, E., Kallina, G., Weber, H., Witte, U.: Pre¬ diction of the Dynamik Behaviour of a Power Plant Unit. VGB Kraftwerkstechnik (English Issue) 59 (1979), No. 2, 112/116. 240 [240] IEEE Committee Report: Computer Representation of Excitation Systems. IEEE Trans. PAS-87 (1968), No. 6, 1460/1464. [241] Jenkins, P.H., Williams, A.H.: Self-Optimizing Combustion Control of an Oil-Fired Power Station Boiler. Proc. IEE 128 Pt.D. (1981), No. 2 (March), 50-55. [242] 11.2 Bibliography 11Appendix Jervis, M.W., Walker, R.W.: Some Design Aspects, Implementation and Experience of Distributed Computer Based Control Systems in CEGB Power Stations. 6th Thermal Generation Specialists Meeting, Madrid (1981), 1/17. 241 [252] Klefenz, G.: Dynamic control investigation of a Benson boiler. BWK 17 (1965) 11, 532/540 (English Version). [253] Koretskii, A.S., Oster-Miller, Yu.R., Foteeva, L.V., Korshun, G.D., Khaberev, N.N. : Influence of the Accuracy of Maintaining Steam Temperature on the Reliability of Gas-and-Oil Fired Steam Gene¬ rators. Thermal Engineering 22 (1975), No. 5, 64/68. [254] Kallina, G.: An Optimization Computer for Busbar Power Plants. VGB Kraftwerkstechnik (English Issue) 61 (1981), No. 2, 78/81. Koretskii, A.S., Oster-Miller, Yu.R., Rinkus, E.K., Foteeva, L.V., Khaberev, N.N.: Influence of Automatic Control on the Reliability of Steam Generators. Thermal Engineering 20 (1973), No. 10, 65/71. [255] [244] Kalnitsky, K.C., Price, C.F., Vinje, E.W.: Assessment of Control System Technology Used in Fossil-Fired Generating Plants. EPRI CS-1718, February 1981. Koretskii, A.S., Oster-Miller, Yu.R.: Economic Criterion of Control Performance. Thermal Engineering 20 (1973), No. 4, 40/44. [256] [245] Kearton, W.J.: Steam Turbine, Theory and Practice. Pitman, London, 1973. Koretskii, A.S.: Selecting a Quality Criterion for Steam Tempe¬ rature and Pressure Control Processes in Large Power Plants. [243] [246] Keeton, J.M.: Advanced Control Techniques Applied to a Fossil Fired Power Plant. 1984 American Control Conference, TP4-4:00, 931/936. [247] Kehlhofer, R., Plancherel, A.: The Combined Cycle Power Plant Series KA8 and KA13E. Brown Boveri Review 72 (1985), No. 2, 56/63. [248] Keyes, M.A., Lukas, M.P.: Direct Digital Control of the Power Generation Process. Combustion 51 (1979), No. 5 (November), 29/35. [249] Kirchmeier, W.E., Faubert, F.M., Reid, W.T.: Furnace Implosion Study Verified by Trip Test. ISA: Instrumentation in the Power Industry (1977), 75/91. [250] Klefenz, G., Seidel, R.: Control Characteristics of a power plant unit operated under controlled sliding pressure. VGB 56 (1976) 2, 75/82 (English Version). [251] Klefenz, G., Maszuttis, K.: Three Variations of unit control — A comparative investigation. Regelungstechnische Praxis und Prozefi-Rechentechnik 1974, 1, 9/16 (Englishe Version). Thermal Engineering 14 (1967), No. 7, 28/32. [257] Kortela, U., Lautala, P.: A New Concept for a Coal Power Plant. 8th IFAC Congress, Kyoto (1981), 3017/3023. [258] Kiirten, H.: Automatic Control of KWU Steam Turbine Generators. KWU 389-101, May 1977, 105/121. [259] Laubli, F., Evers, K.: Dynamic Behaviour of Automatic Feed Control on Monotube Boilers with Superimposed Water Recircu¬ lation. Sulzer Research Number (1968), 15/20. [260] Lausterer, G.K.: Improved Power Plant Control Using a Digital Process Control System. 9th IFAC Congress, Budapest (1984). [261] Lausterer, G.K., Franke, J., Eitelberg, E.: Modular Modelling Applied to a Benson Boiler. IFAC Workshop on Modelling and Control of El. Power Plants, Como (1983), 11/19. [262] Lausterer, G.K.: Optimization of Power Plant Control by Con¬ sistent Application of Mathematical Models. pa (1983), 8/17. 16 Klefenz 1 242 11 Appendix 11.2 Bibliography 243 [263] Lehtomaki, K.J., Kortela, U.K.J., Luukkanen, J.J.: New Estima¬ tion and Control Methods for Fuel Power in Peat Power Plants. 8th IFAC Congress, Kyoto (1981), 3039/3044. [275] Morton, A.J.: The Controllability of Steam Output, Pressure and Water Level in Drum Boilers. IMechE C89/77 (1977), 75/84. [264] Leithner, R., Hermann W., Trautmann, G.: Flue Gas Pressure Vibrations in Steam Generators when Firing Systems Break Down. Combustion 52 (1980), No. 1 (July), 11/22. [276] Muhlhauser, H., Eckert, W.: Steam Turbines in Power Stations for Peak and Medium Load. Brown Boveri Review 62 (1975), No. 7/8, 285/308. [265] Lewins, J.: Nuclear Reactor Kinetics and Control. Pergamon, Oxford, 1978. [277] Murray, R.L.: Nuclear Energy. Pergamon, Oxford, 1975. [266] Long, A.B. (Editor): Assessment of Technologies Essential to the Application of Advanced Systems for Process Control. EPRI NP-640, January 1978. [278] Neal, P.W., Waddington, J., Wilson, R.G.: Determination of Mill and Boiler Characteristics and their Effect on Steam Pressure [267] [268] Loreck, R., Zerrmayr, F.: Monitoring of Thermal Stresses in Steam Turbine Components with the Turbine Stress Evaluator. KWU 388-101, May 1977,87/103. [279] Loreck, R., Zerrmayr, F., Weisgerber, J.: The Turbine Stress Eva¬ luation - Advances in Stress Monitoring Techniques. ASME 74-WA/Pwr-9 (1974), 1/8. Nelson, J.G., Kirchmeier, W.G.: Modern Pneumatic Anti-Implosion Draft Control Design and Operating Considerations. Proc. Am. Power Conf. 43 (1981), 261/273. [280] Nero, A.V. Jr.: Nuclear Reactors. University of California, Berkeley, 1979. [281] Orchard, W.R.H., Sherratt, A.F.C. (Editors): Combined Heat and Power. Godwin, London, 1980. [282] Ormerod, W.G.: Automatic Trimming of Combustion Air to a Pulverized Coal Fired Boiler Using the Flue Gas Carbon Monoxide Signal. J.Inst.Energy 54 (1981), September, 174/176. [283] Ormerod, W.G., Read, A.W.: An Improved Method of Combustion Control of Coal Fired Boilers Using Flue Gas Carbon Monoxide Analysis. J.Inst.Energy 52 (1979), March, 23/26. [284] Oster-Miller, Yu.R., Koretskii, A.S., Rinkus, E.K., Foteeva, L.V.: Influence of Automatic Control on Service Life of Heating Surfaces of a Steam Generator. Thermal Engineering 21 (1974), No. 1, 52/55. [285] Oster-Miller, Yu.R., Koretskii, A.S., Rinkus, E.K., Rabovitser, I.Kh., Korshun, G.D.: Influence of Automatic Control on Steam Generator Efficiency. Thermal Engineering 20 (1973), No. 12, 68/72. [269] Loreck, R.: The Turbine Stress Evaluator. Basic Philosophy and Application. ASME 72-Pwr-9 (1972), 1/9. [270] Lovejoy, S.W., Riess, W.G.: Variable-Pressure Operation and Startup of Large Turbines in Utility Power Plants. Proc. Am. Power Conf. 33 (1971), 329/344. [271] Lukas, M.P.: Improving the Usability of Analytical Design Tech¬ niques in Industrial Control. ISA Trans. 19 (1980), No. 2, 55/64. [272] Mathias, G.: Control Operations in Steam Turbines — A Syste¬ matic Structural Examinations. VGB Kraftwerkstechnik (English Issue) 59 (1979), No. 2, 107/112. [273] [274] Control. Chemical Engineering Science 35 (1980), 2107/21 14. Metcalfe, M.J., Waddington, J., Wilson, R.G.: Operational Ex¬ perience with Fossil-Fired Generating Plant under Automatic Load Control. Proc. IEE 126 (1979), No. 4, 327/332. Moran, F.: Developments in the Control of Power Station Plant. I.Mech.E. 1979,084/79, 141/150. J r 244 [286] Poulter, D.R. (Editor): The Design of Gas-Cooled Graphite-Mo¬ derated Reactors. Oxford University, London, 1963. [287] Profos, P.: Dynamic Behaviour of Forced-Flow Evaporator Systems. Sulzer Technical Review 4/1960, 5/12. Profos, P.: Dynamics of Superheater Control. Combustion 31 (1959), No. 4 (October), 34/43. [289] Profos, P.: Dynamics of Pressure and Combustion Control in Steam Generators. Combustion 29 (1957), No. 9 (March), 34/44. [290] Ram, K.S., Ramanna, R.: Basic Nuclear Engineering. Wiley Eastern, New Delhi, 1977. [291] Robertson, D.K., Teufel, R.C.: Startup and Operational Experien¬ ces of a Retrofit Furnace Implosion Prevention Control System. Proc. Am. Power Conf. 41 (1979), 589/593. [292] Russell, T.D., Walker, R.R.: A Control Strategy for Drum Boilers Incorporating an Advance Boiler Turbine Coordinator. ISA: Instrumentation in the Power Industry (1982), 1/5. [293] Russell, T.D., Walker, R.R.: A Control Strategy for Variable Pres¬ sure Once-Through Units. ISA: Instrumentation in the Power Industry (1980), 59/64. [294] Schultz, W.C., Rideout, V.C.: The Selection and Use of Servo Performance Criteria. AIEE Trans. 77 (1958), January, 383/388. [295] Shapiro, V.I.: Optimal Maintenance of Main Steam Parameters in Accordance with Load of a Generating Unit. Thermal Engineering 24 (1977), No. 1, 31/33. [296] Sharma, D.K., White, J.C. (Editors): Workshop Proceedings: Generator Monitoring and Surveillance. EPRI EL-3564-SR, August 1984. [297] Sherry, A.: The Power Game - the Development of Conventional Power Stations 1948—1983. Proc. Inst. Mech. Eng. 198A (1984), No. 74, 1/24. [298] Singer, J.G. (Editor): Combustion. Fossil Power Systems. Combustion Engineering, Windsor, 1981. [288] 11.2 Bibliography U Appendix 245 [299] Smith, D.J. (Editor): Trends in Industrial Power Plants. Power Engineering, October 1984, 26/34. [300] Spanbauer, J.: An Operations Oriented Computer Control System for Electric Power Plants. IFAC Workshop on Modelling and Control of Electric Power Plants, Como (1983), 115/121. [301] Spanbauer, J.P.: How Advanced Boiler Control Saves Energy. Tappi 63 (1980), No. 7,29/31. [302] Stanton, K.N.: Dynamic Energy Balance Studies for Simulation of Power-Frequency Transients. Proc. 7th PICA Conference, Boston (1971), 173/181. [303] Stein, R., Hunt, W.T.: Electric Power System Components. City University of New York, New York, 1979. [304] Steltz, W.G., Rosard, D.D.: Assessment of Fossil Steam Bypass System. EPRI CS-3717, October 1984. [305] Sterling, M.J.H.: Power System Control. Peter Peregrinus (IEE), Stevenage, 1978. [306] Stodola, A., Loewenstein, L.C.: Steam and Gas Turbines. Peter Smith, New York, 1945. [307] Taneja, O.: Instrumentation & Control Aspects of Retrofitting Utility Power Plants for District Heating Purposes. ISA: Instrumentation in the Power Industry (1982), 105/123. [308] Timm, M.: System Behaviour of Nuclear Power Stations. VGB Kraftwerkstechnik (English Issue) 58 (1978), No. 9, 586/592. [309] Traister, J.E.: Handbook of Power Generation. Transformers and Generators. Prentice-Hall, Englewood Cliffs, 1983. [310] Tsaronis, G., Winhold, M.: Thermoeconomic Analysis of Power Plants. EPRI AP-3651, August 1984. [311] Tsirul'nikov, L.M.: Optimising the Furnace Process in Gas/Oil Fired Boilers. Thermal Engineering 26 (1979), No. 6, 362/363. [312] Vogliano, R.C.: Furnace Implosion Protection — an Update. ISA: Instrumentation in the Power Industry (1979), 77/84. J WW 246 [313] [314] [315] [316] [317] 11Appendix Vollmer, H.D., Undrill, J.M., Crim, H.G.: Draft Control system Design, Simulation and Test for a High Implosion Potential Boiler. Proc. Am. Power Conf. 39 (1977), 388/397. Waddindton, J., Maples, G.C.: The Control of Large Coal and Oil Fired Generating Units. CEGB Research, February 1983,3/15. Wahlstrom, F., Kortela, U.: Combustion Stabilization and Im¬ provement of the Efficiency in a Peat Power Plant. IFAC, Real Time Digital Control Applications, Guadalajara (1983), 173/181. Watson, A.: The CO-O2-CO2 Relationship in Combustion Control. ISA: Instrumentation in the Power Industry (1981), 1/7. Weber, D.S., Cornell, J.W.: A System Analysis of Furnace Pres¬ sure Control. ISA: Instrumentation in the Power Industry (1979), 91/100. [318] Weedy, B.M.: Electric Power Systems. Wiley, New York, 1979. [319] Williams, A.H., Waddington, J.: New Automatic Control Strate¬ gies for CEGB Boilers. CEGB Research, February 1983, 16/24. [320] [321] [322] Wittchow, E.: Start-up Systems for BENSON-Boilers. KWU K/10004.101 (1979), 1/6. Ziegler, J.G., Nichols, N.B.: Optimum Settings for Automatic Controllers. Trans. ASME, November 1942, 759/768. DIN 19 226 (English Translation): Control Engineering — Defi¬ nitions and Terms. May, 1968. 11.3 Subject Index A air flow control 83 attemperation (injection, spray) control 102 attemperation-water/feedwater control 115 auxiliary heating surface 122 B back-pressure control 44 back-pressure station 134 back-pressure turbine 18 Benson boiler 62,64,70 boiler (steam generator) control 62 boiler load margin 54, 55 boiling water reactor 197,199 burner tilting control 132 busbar arrangement 14 busbar control 57 c calorific value variation 58 circulation boiler 62 condensate flow stop control 136 condensing power plant 11,19 constant load operation 23 control by upstream pressure 23 control characteristics 21 convection characteristic 101 critical reactor 203 cyclone firing 81,95 D Direct Energy Balance Method 52 district heating plant 191 drum boiler 62, 68 drum level control 109 E evaporation end point 65 external control 68 I F feed-pump control 118,128 feedwater flow control 109 flue gas by-passing 132 flue gas recirculation 132 forced-circulation boiler 62, 64 forced-flow 62, 64, 66 forced-flow boiler with circulation 121 fossil fuels 11 frequency supporting operation 23 fuel flow control 74 furnace draught control 99 G gas cooled reactor 197, 201 generator control 27 grid control 44 grid operation 20 grid self-regulation 38 H heat- and -power plant, CHP plant 11, 191 heat exchanger controlled system 169 I import/export power control 46 industrial power plant 11, 16, 18 internal control 68 isolated power plant 15, 17, 19, 34 L LaMont boiler 62, 64 level control 109 level controlled system 173 live steam temperature control 100 load control 37 load margin 54, 55 low-load operation arrangement 120 248 11Appendix M mill-air control 90 moisture in steam 72 steam pressure control 74,139 steam pressure controlled system, Benson boiler 150 steam pressure controlled system, drum boiler 139 N steam pressure controlled system, Sulzer boiler 155 natural circulation boiler 62 neutron kinetics 204 normal load operation 20 nozzle group control (governing) 32 nuclear power plant 196 o steam temperature controlled system 158 storage capacity 143 subcritical reactor 203 Sulzer boiler 62,66,71 supercritical operation 128 supercritical pressure 66 supercritical reactor 203 O2 controller 84 O2 correction 81, 84, 95 one-element control 109 once-through boiler 62 outlet pressure (pass-out pressure) control 44 overflow station 134 pressure reducing station 134 pressurized water reactor 197,200 process steam 11,18 prompt supercritical reactor 207 quality of control 183 R reactor kinetics 202 reheater 40 reheat steam temperature control 130 three-element control 111 throttle governing 32 topping set 16 travelling grate stoker (firing) 82, 97 transient time 36 Triflux 73,131 trimming 118 turbine control 32 turbine load margin 54 turbine stress evaluator 55 two-element control 110 u unit arrangement 13 unit control 50 unit coordinator 54 unit guidance device 53 variation of controller parameters 82, 104, 125 sliding pressure operation 46 slip 38 smoke density meter 85 speed controlled system 36 W water seperator 66, 72, 121, 124