Recommended Generator Report - C825 D5 Project - Administration Building Comments Project Requirements Frequency, Hz : 50.0 Generators Running in Parallel : 1 Duty : Standby Site Altitude, ft(m) : 66(20) Voltage : 230/400, Series Wye Site Temperature, °C : 45 Phase : 3 Max. Altr Temp Rise, °C : 105 Fuel : Diesel Project Voltage Distortion Limit, % : 10 Emissions : No Preference Calculated Individual Generator Set Load Running and Peak Requirements Running kW : 492.5 Max. Step kW : 260.0 In Step 2 Cumulative Step kW : 492.5 Running kVA : 543.7 Max. Step kVA : 288.9 In Step 2 Cumulative Step kVA : 543.7 Running PF : 0.91 Peak kW : None Cumulative Peak kW : None Running NLL kVA : 543.7 Peak kVA : None Cumulative Peak kVA : None Alternator kW : 808.86 Pct Rated Capacity : 83.0 Generator Set Configuration Alternator BCode Excitation Voltage Range Number of Leads Reconnectable Full Single Phase Output Increased Motor Starting Extended Stack : : : : : : : : : S6L1D-D4 B681 PMG 380-415 6 Yes No No No Engine Fuel Displacement, cu in. (Litre) Cylinders Altitude Knee, ft(m) Altitude Slope, % per 1000ft(304.8m) Temperature Knee, °F(°C) Temperature Slope, % per 18°F(10.0°C) Emissions Cooling Package Set Performance : : : : : : : : : : QSK23-G3 Diesel 1413.0(23.2) 6 3937(1200) 3 104(40) 20 EPA Tier 1 High Ambient Load Requirements Running At : 83.0% Rated Capacity Max. Step Voltage Dip, % : 9 Max. Allowed Step Voltage Dip : 10 In Step 2 Max. Step Frequency Dip, % : 3 Max. Allowed Step Frequency Dip : 10 In Step 1 Peak Voltage Dip, % : Peak Voltage Dip Limit % : 10.0 Peak Frequency Dip, % : Peak Frequency Dip Limit % : 10 Site Rated Standby kW/kVA : 594 / 743 Running kW : 492.5 Running kVA : 543.7 Site Rated Max. SkW : 642 Effective Step kW : 430.1 Max. SkVA : 3030 Effective Step kVA : 543.7 Temp Rise at Full Load, °C : 163 Percent Non-Linear Load : 100.0 Voltage Distortion : 10.0 Voltage Distortion Limit : 10 Site Rated Max Step kW Limit : Max Step kW : *Note: Higher temperature rise at full rated load. *Note: All generator set power derates are based on open generator sets. Recommended Generator Report 26-Jun-2024 Page 1 Loads Summary Report Project - Administration Building Comments Project Requirements Frequency, Hz : 50.0 Generators Running in Parallel : 1 Duty : Standby Site Altitude, ft(m) : 66(20) Voltage : 230/400, Series Wye Site Temperature, °C : 45 Phase : 3 Max. Altr Temp Rise, °C : 105 Fuel : Diesel Project Voltage Distortion Limit, % : 10 Emissions : No Preference Loads Summary List *Note: Detailed Loads and Step Report available below Running Step No. Load Name Starting Peak Dip Limits, % Quantity kW kVA kW kVA kW kVA Vdip Fdip VTHD% Limit Step01 Light Load 1 1 60.0 63.16 60.0 63.16 None None 10.0 10.0 10.0 Step01 UPS Load 1 1 172.5 191.67 172.5 191.67 None None 10.0 10.0 10.0 233.0 255.0 233.0 255.0 None None 10.0 10.0 10.0 260.0 288.89 260.0 288.89 None None 10.0 10.0 10.0 260.0 289.0 260.0 289.0 None None 10.0 10.0 10.0 Step Summary Step02 AC Load 1 Step Summary 1 Running Project Summary Max Starting Cumulative Step Cumulative Peak kW kW kVA kW kVA kW kVA 492.5 543.7 260.0 288.9 492.5 543.7 0.0 kVA 0.0 Project VTHD% Limit 10.0 *Note: Detailed Loads and Step Report available below Loads and Steps Detail Report 26-Jun-2024 Page 1 Loads and Steps Detail Report Project - Administration Building Comments Project Requirements Frequency, Hz : 50.0 Generators Running in Parallel : 1 Duty : Standby Site Altitude, ft(m) : 66(20) Voltage : 230/400, Series Wye Site Temperature, °C : 45 Phase : 3 Max. Altr Temp Rise, °C : 105 Fuel : Diesel Project Voltage Distortion Limit, % : 10 Emissions : No Preference Calculated Individual Generator Set Load Running and Peak Requirements Running kW : 492.5 Max. Step kW : 260.0 In Step 2 Cumulative Step kW : 492.5 Running kVA : 543.7 Max. Step kVA : 288.9 In Step 2 Cumulative Step kVA : 543.7 Running PF : 0.91 Peak kW : None Cumulative Peak kW : None Running NLL kVA : 543.7 Peak kVA : None Cumulative Peak kVA : None Alternator kW : 808.86 Step1 Calculated Individual Generator Set Step Load Requirements Running kW : 233.0 Starting kW : 233.0 Cumulative Step kW : 233.0 Running kVA : 255.0 Starting kVA : 255.0 Cumulative Step kVA : 255.0 Running Amps : 368.0 Starting Non-linear kVA : 255.0 Running Non-linear kVA : 255.0 Alternator kW : 288.86 Voltage Distortion Limit for step : 10 Light Load 1 Category Three Phase Quantity : 1 In this Step : Light - LED Running kW : 60.0 Starting kW : 60.0 Peak kW : None Running kVA : 63.16 Starting kVA : 63.16 Peak kVA : None Running PF : 0.95 Starting PF : 0.95 Cyclic : No Running Amps : 91.27 Max. % Voltage Dip : 10.0 Max. % Frequency Dip : 10.0 Running NLL kVA : 63.16 Starting NLL kVA : 63.16 Voltage : 400 Alternator kW : 90.52 UPS Load 1 Category Running kW Loads and Steps Detail Report Three Phase Quantity : 1 In this Step : UPS : 172.5 Starting kW : 172.5 26-Jun-2024 Peak kW : None Page 2 Running kVA : 191.67 Starting kVA : 191.67 Peak kVA : None Running PF : 0.9 Starting PF : 0.9 Cyclic : No Running Amps : 276.98 Max. % Voltage Dip : 10.0 Max. % Frequency Dip : 10.0 Running NLL kVA : 191.67 Starting NLL kVA : 191.67 Voltage : 400 Alternator kW : 198.34 Output Rated kVA : 150.0 Loading Factor % : 100 Efficiency (%) : 0.9 Battery Charging Rate (%) : 15 Ramp Details : None Rectifier Type : 12 pulse THDI % : 10 THDV % : 10 Step2 Calculated Individual Generator Set Step Load Requirements Running kW : 260.0 Starting kW : 260.0 Cumulative Step kW : 493.0 Running kVA : 289.0 Starting kVA : 289.0 Cumulative Step kVA : 544.0 Running Amps : 417.0 Starting Non-linear kVA : 289.0 Running Non-linear kVA : 289.0 Alternator kW : 520.0 Voltage Distortion Limit for step : 10 AC Load 1 Three Phase Category Quantity : 1 In this Step : AC Running kW : 260.0 Starting kW : 260.0 Peak kW : None Running kVA : 288.89 Starting kVA : 288.89 Peak kVA : None Running PF : 0.9 Starting PF : 0.9 Cyclic : No Running Amps : 417.47 Max. % Voltage Dip : 10.0 Max. % Frequency Dip : 10.0 Running NLL kVA : 288.89 Starting NLL kVA : 288.89 Voltage : 400 Alternator kW : 520.0 AC Tons : 260.0 Type : Variable Frequency Drive Ramp Details : None Rectifier Type : 6 pulse THDI % : 26 EER per Ton : 12.0 THDV % : 10 Loads and Steps Detail Report 26-Jun-2024 Page 3 Steps and Dips Details Report Project - Administration Building Project Requirements Frequency, Hz : 50.0 Generators Running in Parallel : 1 Duty : Standby Site Altitude, ft(m) : 66(20) Voltage : 230/400, Series Wye Site Temperature, °C : 45 Phase : 3 Max. Altr Temp Rise, °C : 105 Fuel : Diesel Project Voltage Distortion Limit, % : 10 Emissions : No Preference Calculated Individual Generator Set Load Running and Peak Requirements Running kW : 492.5 Max. Step kW : 260.0 In Step 2 Cumulative Step kW : 492.5 Running kVA : 543.7 Max. Step kVA : 288.9 In Step 2 Cumulative Step kVA : 543.7 Running PF : 0.91 Peak kW : None Cumulative Peak kW : None Running NLL kVA : 543.7 Peak kVA : None Cumulative Peak kVA : None Alternator kW : 808.86 Generator Set Configuration Model : C825 D5 Alternator : S6L1D-D4 Engine Model : QSK23-G3 Excitation : PMG Fuel : Diesel High Ambient Step # Voltage Dip Limit (%) Step Level Dips Summary Expected Voltage Frequency Step Voltage Recovery Time Dip Limit Dip (%) (s) ** (%) 1* 10 7 * 10 3 1.2 2 10 9 * 10 3 1.2 Expected Frequency Dip (%) Frequency recovery Time (s) ** Note: Please refer to the model Spec. sheet for bandwidths used to report recovery times. For products manufactured in the United Kingdom it may be assumed that recovery times are based on ISO8528-5 G2 class bandwidths. Voltage and frequency recovery times are estimates. Typically, allow five to ten seconds between application of load steps when designing your system. *Caution: The starting PF for this step exceeds 0.8 lagging. The actual transient performance of the generator for these steps may vary compared to the results predicted by GenSize.Contact your Cummins Distributor for Guidance. **Please note that in some cases the voltage and frequency recovery time estimates are not shown in list. This is a result of "dummy" data points temporarily being used to fill data gaps in the GenSize database. Please disregard these blank results. *Note: Contact your Cummins Power Generation Distributor for Recovery Data Steps and Dips Detail Report 26-Jun-2024 Page 1 Value Step # 0 1 2 3 4 5 6 7 Step 1 8 9 10 7.0 10.0 Step 2 9.0 10.0 VDip Limit VDip Actual Value Step # 0 1 2 3 4 5 6 7 8 9 10 Step 1 3.0 10.0 Step 2 3.0 10.0 FDip Actual Steps and Dips Detail Report FDip Limit 26-Jun-2024 Page 2