1MRS757208 EN Technical Note ABB Oy, Distribution Solutions Issued: June 2010 Revision: C / 26 May 2020 High-Impedance Differential Protection Principle, calculations and CT requirements Contents: 1 Scope ..................................................................................................................... 2 2 Principle of the high-impedance differential protection .................................. 3 2.1 Requirements for the protection relay .......................................................... 6 3 Calculations and CT requirements .................................................................... 8 3.1 Calculation of the stabilizing voltage ........................................................... 8 3.2 CT knee-point requirement........................................................................... 9 3.3 Minimum possible relay operating current ................................................. 10 3.4 Calculation of the stabilizing resistor ......................................................... 10 3.5 Actual sensitivity of protection................................................................... 11 3.6 Need for Voltage Dependent resistor ......................................................... 12 4 Example calculations ......................................................................................... 13 4.1 Phase segregated high-impedance differential protection for generator .... 13 4.1.1 Stabilization voltage and CT knee-point requirement .................... 13 4.1.2 Stabilizing resistor ........................................................................... 14 4.1.3 Actual sensitivity of protection ....................................................... 15 4.1.4 Voltage Dependent Resistor ............................................................ 15 4.2 High-impedance based restricted earth-fault protection for transformer ... 15 4.2.1 Stabilization voltage and CT knee-point requirement .................... 16 4.2.2 Stabilizing resistor and actual sensitivity ........................................ 17 4.2.3 Voltage dependent resistor .............................................................. 17 5 List of symbols ................................................................................................... 19 6 List of equations ................................................................................................. 21 Document history, Disclaimer and Copyrights, Trademarks, Contact information .... 22 © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 1 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1 1MRS757208 EN Scope This document describes the high-impedance differential protection principles, calculations and CT requirements. This scheme is used both in phase segregated high-impedance differential and high-impedance based restricted earth-fault protection. Typical areas of applications are generator, motor, reactor, bus-bar and transformer protection. First the operation principle of a high-impedance scheme is studied with explanatory figures and diagrams. The need of the stabilizing and voltage dependent resistors is explained. Further, the requirements of a protection relay to be used in high-impedance scheme are listed. Next, the rules of calculating the stabilizing voltage, relay setting, stabilizing resistor etc. are presented. Finally, the calculating rules are applied in protection application examples. Both the phase segregated high-impedance differential and high-impedance base restricted earth-fault protection is handled. The rules given in this document are applicable for any high-impedance differential protection relay/function, where setting is given in current. KEYWORDS: high-impedance protection, restricted earth-fault protection, busbar protection, differential protection © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 2 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 2 1MRS757208 EN Principle of the high-impedance differential protection The high-impedance principle has been used through many years for differential protection due its capability to manage through-faults also in case of current transformer (CT) saturation. Figure 2.-1 shows an example connection of a phase segregated high-impedance differential protection scheme. The phase currents are measured from the both sides of the protected object. The current transformers (CT) secondary in each phase are connected in parallel along with a relay measuring branch. Thus the relay measures only the difference of the currents. In an ideal situation there will be differential current to operate the relay only if there is a fault between the CTs, i.e. inside of the protected zone. In case there is a fault outside of the zone, a high current can go through the protected object (known as through fault current). This can cause partial saturation in the CTs. The relay operation is avoided by means of a stabilizing resistor (Rs) in the relay measuring branch. The Rs increases the impedance of relay, hence the name high-impedance differential scheme. P1 P2 P2 P1 s1 s2 s2 s1 A B C Protected object IL1 IL2 IL3 Voltage dependent resistor Ru Stabilizing resistor Rs Id1 Id2 Id3 Three-phase differential protection Fig.2.-1. Phase segregated differential protection based on high-impedance principle. © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 3 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN Figure 2.-2 shows a single phase representation of the circuit. CT secondary winding resistances (Rin) and connection wire resistances (Rm/2) are also shown. Fig.2.-2. Single phase representation. We can further simplify the circuit to its equivalent as done in Figure 2.-3. For simplicity reasons the voltage dependent resistor (Ru) is not shown. Wiring resistances are presented as total wiring resistances (Rm1 and Rm2) and. The lower part of the figure shows the voltage balance while there is no fault in the system, and no CT saturation. Fig.2.-3. Equivalent circuit when there is no fault or CT saturation © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 4 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN As the figure 2.-3 shows, when there is no fault the CT secondary currents, and thus its emf voltages (E1 and E2) are opposite and the relay measuring branch has no voltage/current. In case of in-zone fault, the secondary currents have the same direction. The relay measures the sum of the currents as a differential and trips the circuit breaker. If the fault current goes through one CT only, its secondary emf magnetizes the other side CT, i.e. E1 E2 (Fig. 2.4). Fig.2.-4. Equivalent circuit in case of in-zone fault. Figure 2.-5 shows CT saturation at through fault (i.e. out-of-zone) situation. The magnetization impedance of a saturated CT is almost zero. Thus the saturated CT winding can be presented as a short circuit, see Fig. 2.-5. When one CT is saturated the current of the non-saturated CT has now two paths to follow: through the relay measuring branch (Rs + relay) and through the saturated CT (Rm2+Rin2). The relay should not operate during the saturation. This is achieved by increasing relay impedance by means of the stabilizing resistor (Rs) which forces the majority of the differential current to flow through the saturated CT. As a result relay operation is avoided, i.e. the relay operation is stabilized against CT saturation at through fault current. The voltage Us, known as stabilizing voltage, shown in the figure is the basis of all calculations. © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 5 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN Fig.2.-5. Equivalent circuit in case of CT saturation at through fault. Note: The CT saturation can and most likely will happen also in case of in-zone fault. This is not a problem because although the operation remains stable (non-operative) during the saturated parts of the CT secondary current waveform, the non-saturated part of the current waveform will cause the protection to operate. I Saturated part Non-saturated part Fig. 2.-6 Secondary waveform of a saturated CT. Because of the stabilizing resistance and CT saturation the secondary circuit voltage can easily exceed the isolation voltage of the CTs, connection wires and the relay. In order to limit this voltage a voltage dependent resistor (VDR, Ru) is used as shown in Figures 2.-1 and 2.-2 earlier. 2.1 Requirements for the protection relay It is commonly asked if a normal overcurrent or earth-fault relay could be used for highimpedance scheme. There are three requirements that any protection relay or function must fulfil if it is used in high-impedance scheme © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 6 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN 1. The operation must be based on the peak-to-peak measurement or have special peak detection algorithm for ensuring fast and reliable operation with disturbed secondary current of saturated CT. 2. Speed of operation. Typically very short relay operation time is required. 3. Sensitivity in current setting, i.e. relay minimum setting must be sufficient. © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 7 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 3 1MRS757208 EN Calculations and CT requirements The calculating and CT selection is usually an iterative process: - - 3.1 First a suitable looking CT is chosen. Then, the stabilization voltage is calculated and compared to the CT knee-point voltage requirement. Should the knee-point voltage of the CT be too small, another CT must be chosen, and the process is started from the beginning. Next, the relay setting and stabilizing resistor is calculated. Further, the actual sensitivity of the protection, which will be affected by CT magnetization etc, is calculated. In case the actual sensitivity is not satisfactory, a CT with bigger core (lower magnetizing current) must be chosen and the process starts again from the beginning. Finally, the need of the voltage dependent resistor (VDR) is checked. Calculation of the stabilizing voltage The sensitivity and reliability of the protection is much dependent on the characteristics of the current transformers. The CTs must have identical transformation ratio. It is further recommended that all current transformers has equal burden, characteristics and are of same type, preferably from the same manufacturing batch (i.e. identical construction should be used if possible). If the CT characteristics and burden values are not equal, calculation for each branch in the scheme should be done separately and the worst case result is then used. Consider the case as shown if figure 3.-1, CT winding resistance and burden of the branches are not equal, and hence the maximum burden equal to 3.2Ω should be used for calculating stabilized voltage. P1 P2 P2 P1 s1 s2 s2 s1 Rin1 = 1.2Ω Rin2 = 0.8Ω A B C IL1 Rm1 = 2Ω Rm2 =1.9Ω Ru Rin1 + Rm1 = 3.2Ω Rin2 + Rm2 = 2.7Ω Rs Id1 Three-phase differential protection Fig. 3.-1. Example of different CT burden value on each branch. © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 8 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN The stabilizing voltage (i.e. the voltage appearing across the measuring branch during out-ofzone fault) is calculated assuming that one of the parallel connected CT is fully saturated. The stabilizing voltage can be calculated by the formula I k max (1) ( Rin + Rm ) n where, Ikmax = the highest through-fault current in primary Amps. I.e. the highest shortcircuit or earth-fault current when the fault is outside of the protected zone n = the turns ratio of the CT Rin = the secondary winding resistance of the CT in ohms Rm = the total resistance of the secondary circuit wires in ohms US = In principle, the highest through-fault current should be known. However, when the necessary data is not available, the following approximates can be used: - Small power transformers: Ikmax = 16 x In (corresponds zk = 6% and infinite grid) - Large power transformers: Ikmax = 12 x In (corresponds zk = 8% and infinite grid) - Generators & Motors: Ikmax = 6 x In Where In = rated current and zk = short-circuit impedance of the protected object. 3.2 CT knee-point requirement The current transformers must be able to force enough current to operate the relay through the differential circuit during a fault condition inside the zone of protection. To ensure this, the knee-point voltage Ukn should be at least 2 times higher than the stabilizing voltage US. U kn 2 U S (2) The factor two in the eq.2 is used for ensuring reliable and fast operation of the protection. In some cases, it is possible to achieve stability with knee-point voltage slightly lower than stated in the formula. The conditions in the network, however, have to be known well enough to ensure the stability. • • • If Ukn >= 2 x US, fast relay operation is secured. If Ukn >= 1.5 x US and < 2 x US relay operation can be prolonged and should be studied case by case. If Ukn <1.5 x US the relay operation is jeopardized. Another CT should be chosen. © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 9 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN If other than class X CTs are used, an estimate for Ukn can be calculated from the rated accuracy limit factor Sn U kn = 0.8 Fn I 2 n Rin + 2 I 2n where, Fn = the rated accuracy limit factor of the CT I2n = the rated secondary current of the CT Rin = the secondary winding resistance of the CT Sn = the rated burden (VA rating) of the CT (3) Example: A CT 500/5, 10P20, 15VA, Rin 0.2ohm is used. I.e. the Fn=20, I2n=5A and Sn=15VA. The knee-point voltage is 15VA = 64V U kn = 0.8 20 5 A 0.2 + (5 A)2 3.3 Minimum possible relay operating current Should the protection be required to be as sensitive as possible, the following points must be checked - What is the minimum possible setting in the relay? What is the CT accuracy in through-fault case? The relay should not be set below the CT accuracy. What is the CT magnetization current (Im) at the stabilizing voltage? The relay setting should be higher than the sum of the magn. currents of all parallel connected CTs. 3.4 Calculation of the stabilizing resistor As the impedance of the protection relay alone is low, a stabilizing resistor is needed. The value of the stabilizing resistor is calculated using the formula US I relay where, Irelay = relay set operating current in secondary Amps RS = (4) The continuous power of the stabilizing resistor is P= U kn2 Rs (5) The stabilizing resistor should be capable to dissipate high energy within very short time. Therefore, a wire wound type resistor should be used. Often the manufacturer of the resistor allows 10 times rated power for 5 sec. Then the required power of the resistor can be calculated as © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 10 (22) High-Impedance Differential Protection Principle, calculations and CT requirements P= 1MRS757208 EN U kn2 Rs 10 (6) Because of possible CT inaccuracy, which might cause some current through the stabilizing resistor in normal load situation, the rated power should be 25W minimum. 3.5 Actual sensitivity of protection The relay set operating current does not directly define the selectivity of the protection, i.e. the operation point in primary Amps. This is because of the CTs magnetizing currents and the leakage current of the voltage dependent resistor. The value of the primary current (Iprim) at which the protection operates at certain setting can be calculated using the formula: I prim = n ( I relay + I u + m I m ) (7) where, n = turn ratio of the CT Irelay = relay set operation current in secondary Amps Iu = leakage current through the Voltage Dependent Resistor (VDR) at stabilizing voltage Us m = number of CTs connected in parallel in the secondary circuit Im = magnetizing current of the CT at stabilizing voltage Us Note: Typically, in CT manufacturers catalogues, the magnetizing (=excitation) current of the CT is given at knee-point voltage. - - CT magnetizing current at the stabilizing voltage can be read from the CT magnetizing curve, if available. The magnetizing current can also be measured from a real CT: when primary is open, inject AC voltage equal to stabilizing voltage to the CT secondary and measure current. Note that current will increase rapidly if injected voltage exceeds CT kneepoint voltage. Assuming linear magnetizing curve up to the knee-point, the Im can also be estimated Us Ie U kn where, Ie = excitation current of the CT at Ukn Im © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND (8) 11 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 3.6 1MRS757208 EN Need for Voltage Dependent resistor First, voltage Umax, ignoring the CT saturation during the fault is calculated as follows: I k max in I (Rin + Rm + Rs ) k max in Rs n n (9) where, Ikmaxin = maximum fault current when fault is inside the zone, in primary Amps n = turn ratio of the CT Rin = CT internal secondary winding resistance Rm = resistance of the lead wires (longest loop/highest value) Rs = resistance of the stabilizing resistor U max = Relay impedance was ignored because it is negligible in comparison the other resistances. Next the peak voltage (û), which includes the CT saturation, is estimated by using formula given by P.Mathews 1955 u = 2 2 U kn (U max − U kn ) (10) The VDR is recommended when the peak voltage û ≥ 2kV, which is the generally used insulation level of the secondary circuit. Sometimes, if the Rs would have little smaller value, the VDR could perhaps be avoided. But the value of Rs depends on the relay operation current and stabilizing voltage, thus we must either use a higher setting in the relay, or try to lower the stabilizing voltage (which depends on Rin and Rm). © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 12 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN 4 Example calculations 4.1 Phase segregated high-impedance differential protection for generator Figure 4.1.-1 shows schematically a phase segregated high-impedance differential protection. Sn = 8 MVA Un = 6 kV P1 P2 P2 P1 s1 s2 s2 s1 Rin Rin A B C IL1 Rm Rm Ru Rs Id1 Three-phase differential protection Fig. 4.1.-1. Differential protection for generator (only one phase is presented in detail). The protected generator has the following values and CT data (CTs are equal) - Generator 8 MVA, 6 kV, In = 770A - Max. Through fault current (out of zone fault) Max. fault current at in zone fault Ikmax = 6 x In = 4620A Ikmaxin = 12 x In = 9240A - CT ratio CT secondary winding resistance CT knee-point voltage CT excitation current (at knee-point voltage) n = 1000/1 A Rin = 15.3 ohm Ukn = 323 V Ie = 0.035 A @ Ukn - Required sensitivity 5% of 770 A = 38.5 A 4.1.1 Stabilization voltage and CT knee-point requirement The longest distance between the CT and relay is 100 m, giving a connection wire loop of 200 m. The area of the cross-section is 2.5 mm2 (resistance at 75 °C as 0.00865 Ω/m). Rm = 0.00865 / m 200 m 1.73 © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 13 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN First the stabilizing voltage is calculated based on eq.1 Us = 4620 A (15.3 + 1.73) 78 .7 V 1000 / 1 The requirement for the CT knee-point voltage (eq.2) is fulfilled because Ukn > 2xUs. 4.1.2 Stabilizing resistor The value of the stabilizing resistor is calculated using eq.4. The required sensitivity of protection is 38.5A in primary, 0.0385A in secondary. RS = US 78 .7V = = 2044 I relay 0.0385 A Note that this is the minimum value for Rs with relay setting 0.0385A. If suitable resistance cannot be found, somewhat higher value can be used. From the opposite point of view, Rs = 2044Ω means that 0.0385A is the lowest possible setting in the relay, i.e. setting value can be later increased but not decreased. For the purpose of checking, we calculate what would be the minimum possible setting from the CT magnetizing current point of view. Using eq.7, the magnetizing current at Us is 𝐼𝑚 = 𝑈𝑠 78.7𝑉 × 𝐼𝑒 = × 35𝑚𝐴 ≈ 8.5𝑚𝐴 𝑈𝑘𝑛 323𝑉 To obtain adequate protection stability, the setting current Irelay should be at minimum of the sum of the magnetising currents of all connected CTs. As we have two CT in parallel we get Irs = 2 8.5mA 17 mA Then the resistance of the stabilizing resistor is calculated based on eq.4 RS = 78 .7 V 4629 0.017 A By using slightly higher relay setting like 20 mA, the Rs becomes 3900 Ω. Using 2044 ohm, the power of the stabilizing resistor for continuous usage is (eq.5) P= (323V ) 2 51W 2044 Or, if the manufacturer of the resistor allows 10 times rated power for 5 sec. and using eq.6 © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 14 (22) High-Impedance Differential Protection Principle, calculations and CT requirements P= 1MRS757208 EN U kn2 = 5.1W Rs 10 Note: Because of possible CT inaccuracy, which might cause some current through the stabilizing resistor in normal load situation, the rated power should be 25 W minimum. 4.1.3 Actual sensitivity of protection The actual sensitivity of the protection depends on the relay setting, CT magnetizing currents and the leakage resistance of the VDR. The CT magnetizing current (Ie) at Us was calculated earlier 8.5 mA. Using relay setting 0.0385A, neglecting the effect of VDR (current Iu) and using eq.7 I prim = n ( I relay + I u + m I m ) = 1000 (0.0385 A + 2 0.0085 A + 0 A) ) = 55 .5 A in primary This is higher than the required sensitivity. If requested, this can be compensated by using a lower relay setting (keeping in mind the minimum possible setting). But then the value of the stabilizing resistance must be re-calculated. 4.1.4 Voltage Dependent Resistor Using eq.9 and 10 U max = 12 770 A (2044 + 15.3 + 1.73 ) 19 kV 1000 uˆ = 2 2 323V (19000V − 323V ) 7 kV In this example, the VDR (one for each phase) is a must because the voltage during the fault is much higher than 2 kV. If the VDR supplier gives the leakage current through the VDR at the stabilizing voltage the sensitivity of the protection can be re-calculated taking into account the leakage current. 4.2 High-impedance based restricted earth-fault protection for transformer Figure 4.2.-1 shows an example of high-impedance based restricted earth-fault protection of a power transformer winding. The secondary side of the power transformer system is solidly earthed. © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 15 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN Fig. 4.2.-1. Restricted earth-fault protection for transformer. The protected transformer has the following values and CT data (all CT are equal) - Transformer 20 MVA, 11 kV, In = 1050A solidly earthed network - Max. fault current (in or out of zone) Ikmax = 12 x In = 12600A - CT ratio CT secondary winding resistance CT knee-point voltage CT excitation current (at knee-point voltage) n = 1200/5A Rin = 0.47 ohm Ukn = 81 V Ie = 0.055 A @ Ukn - Required sensitivity 5% of 1050A = 52.5 A Note: The maximum fault current in this application is always the highest possible earthfault or short-circuit current, whichever is higher. This applies even though the transformer neutral would have been earthed through a neural earthing resistor (NER). 4.2.1 Stabilization voltage and CT knee-point requirement The longest distance between CT and relay is 40 m and the whole loop of connection wires being thus 80 m and the area of the cross-section is 6 mm2 (resistance at 75 °C is 0.0036Ω/m). Rm = 0.0036 / m 80 m 0.288 The stabilising voltage is calculated based on eq.1 Us = 12600 A (0.47 + 0.288 ) 40 V 1200 / 5 © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 16 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN In this case the requirement for the current transformer knee-point voltage (eq.2) is fulfilled because Ukn > 2Us. 4.2.2 Stabilizing resistor and actual sensitivity Required sensitivity is 52.5 A in primary, 0.219 A in secondary. We can already take account the effect of the CT magnetizing currents on the actual sensitivity of the protection, by subtracting the CT magnetizing currents. In this scheme, there are four CT secondary in parallel. The magnetizing current for one CT at Us is (eq.8) 𝐼𝑚 = 40𝑉 × 55𝑚𝐴 ≈ 27𝑚𝐴 81𝑉 Thus, taking into account the four CT magnetizing currents, the relay setting should be Irelay = 219 mA – 4 x 27mA = 111 mA The minimum possible setting must also be checked! To obtain adequate protection stability, the setting current Irelay should be at minimum of the sum of the magnetising currents of all connected CTs. In this example 4 x 27 mA = 108 mA The resistance of the stabilising resistor is calculated based on eq.4 RS = 40 V 360 0.111 A The continuous power of the stabilising resistor is (eq.5) P= (81V ) 2 18 W 360 Note: Because of possible CT inaccuracy, which might cause some current through the stabilizing resistor in normal load situation, the rated power should be 25 W minimum. 4.2.3 Voltage dependent resistor Using eq.9 and 10 U max = 12600 A 360 = 18 .9 kV 1200 / 5 uˆ = 2 2 81V (18900V − 81V ) 3.5 kV © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 17 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN VDR is needed because the peak voltage is higher than 2 kV. Because the Us is small, the leakage current through the VDR most likely is negligible and does not affect the actual sensitivity. © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 18 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 5 1MRS757208 EN List of symbols CT Current Transformer EF Earth-fault Fn rated accuracy limit factor of the CT I2n rated secondary current of the CT Id1, Id2, Id3 Differential currents Ie CT excitation (=magnetizing) current at Ukn Ikmax highest through-fault current when the fault is outside the protected zone Ikmaxin highest fault current when the fault is inside the protected zone IL1, IL2, IL3 CT secondary currents Im magnetizing current of the CT at CT knee-point voltage (Us) In relay rated secondary current Iprim primary current at which protection operates Irelay relay set operating current in secondary Amps Iu leakage current of the VDR at Us M number of CTs connected in parallel in the secondary circuit n CT ratio P stabilizing resistor power rating Rin CT internal secondary winding resistance Rm total secondary wiring lead resistance (known as loop resistance) Rs stabilizing resistor Ru voltage dependent resistor (VDR) Sn rated burden (VA rating) of the CT û peak voltage in the secondary Ukn CT knee-point voltage © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 19 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 1MRS757208 EN Umax theoretical maximum voltage in CT secondary (ignores CT saturation) Us stabilizing voltage VDR Voltage Dependent Resistor (Ru), also known as varistor © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 20 (22) High-Impedance Differential Protection Principle, calculations and CT requirements 6 1MRS757208 EN List of equations Number Description Equation I k max ( Rin + Rm ) n 1 Stabilizing voltage US = 2 CT knee-point requirement U kn 2 U S 3 P class CT knee-point voltage Sn U kn = 0.8 Fn I 2 n Rin + 2 I 2n 4 Stabilizing resistor RS = 5 Continuous power of the stabilizing resistor P= 6 Short time power of the stabilizing resistor U kn2 P= Rs 10 7 Actual sensitivity of protection I prim = n ( I relay + I u + m I m ) 8 CT magnetizing current at CT knee-point (Us) Im 9 CT maximum secondary voltage U max = 10 CT peak voltage during saturation u = 2 2 U kn (U max − U kn ) US I relay U kn2 Rs Us Ie U kn I k max in I (Rin + Rm + Rs ) k max in Rs n n © Copyright 2010-2020 ABB Oy, Distribution Solutions, Vaasa, FINLAND 21 (22) Document revision history Document revision/date A / 09 June 2010 B / 24 October 2019 C / 26 May 2020 History First revision - Misspelling in p.10 example corrected, Fn=20, not 5 Company name changed, last line in Scope added Chapter 3.5 some text added regarding CT magn.current Chapter 4.2.2 1st equation, typo corrected Disclaimer and Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document. In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Copyright © 2010-2019 ABB Oy All rights reserved. Trademarks ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Contact information ABB Oy, Distribution Solutions P.O.Box 699 Visiting address: Muottitie 2A FI-65101 Vaasa, FINLAND Phone: +358 10 22 11 Fax: +358 10 22 41094 www.abb.com/substationautomation