Self-Powered Protection Relay IKI-35 for Transformer-Monitoring and Protection in Distribution Networks Manual Valid for IKI-35_24V issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Tel. +49 7151 969320; M: service@kries.com Page 1/25 Index 1. 1.1 1.2 1.3 2. 8. 2.2 9.2.3 Introduction General Application Design Handling / Installation Precautions Auxiliary Energy Supply Split-Core CTs 2.4 Clamp assignment 1. Introduction 1.1 General 10. 3. 3.1 3.2 3.3 3.4 3.5 7. 5. 6. 7. 8. Indication/Setting Indication Setting Inrush rejection Selection of Tripping Coil (obsolete) Setting examples Technical Data Function Test / Maintenance Low-Power Magnet-Tripping-Coil Restrictions Appendix: Function Test En las modernas redes de distribución y Smart-Grids, los transformadores y las líneas de alta tensión del cliente deben ser vigilados y protegidos contra sobrecargas y fallas (cortocircuitos, fallas a tierra). El relé de protección autoalimentado IKI-35 es un relé de protección destinado a aplicaciones de distribución y por su diseño y facilidad de uso es el más adecuado para su uso en unidades principales de anillo y subestaciones compactas. El relé de protección autoalimentado IKI-35 es aplicable para la supervisión y protección de transformadores de red de distribución con corrientes nominales de 10 A .... 250 A. Mediante transformadores de núcleo partido se pueden detectar sobrecorrientes y corrientes de cortocircuito en las líneas de suministro eléctrico. El dispositivo ofrece una etapa de sobrecorriente (ANSI 51), una etapa de cortocircuito (ANSI 50), una etapa de disparo rápido externa y una etapa de falla a tierra (ANSI 50N y 51N) también. La etapa de sobrecorriente y la etapa de falla a tierra se pueden seleccionar como etapa de tiempo definido DMT (=UMZ) o etapa de tiempo definido inverso IDMT (=AMZ). La etapa IDMT ofrece cuatro curvas según IEC 60255-3. Las fallas a tierra pueden detectarse mediante el cálculo de la corriente residual de los sensores de corriente trifásica (ANSI 50N/51N) o mediante la instalación de un TC de núcleo homopolar opcional en la entrada E para la medición de corrientes de falla a tierra sensibles no dirigidas (ANSI 50G, 51G). El IKI-35 es alimentado por los TC y protegido por una batería de litio. issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Tel. +49 7151 969320; M: service@kries.com Page 2/25 1.2 Application The self-powered protection relay IKI-35 is mainly used for transformer-protection in distribution networks. The use of IKI-35 allows a selective fault isolation during overload and failure situation and increases the availability of the residual network. Most important features: Tripping due to: - short circuit detection on MV- or LV-side of transformer overload detection earth fault detection emergency-command or remote-command at external fast trip input - figure 1.2 Applications a) Protection of transformers with power circuit breaker Switching device: power circuit breaker or power breaker Overcurrent and short circuit stage are monitored by the IKI-35 and tripped by the magnetic coil. Substitution for load-breaker/fuse combination figure 1.2 a) b) Protection of Transformers with fuses and IKI-35 Switching device: load-breaker / fuse-combination. The IKI-35 controls the overcurrent range up to the rated current of the load breaker and trips the load breaker in case of overcurrent. The short circuit current stage of the IKI-35 is blocked. When the maximum trip current of the load breaker is exceeded, the tripping will be blocked. Hence the fuse must take over the tripping function. figure 1.2 b) issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 3/25 1.3 Design of IKI-35 The protection relay system IKI-35 consists of: base unit IKI-35 3 split-core CTs; optional: 1 balanced core CT for earth fault detection low power tripping coil or standard coil with capacitor buffer, e.g. PSU Figure 1.3 2. Handling/Installation 2.1 Precautions during Installation Durante la instalación del IKI-35 en los TC de núcleo dividido, debe desconectarse la alta tensión. Durante la instalación deben respetarse las cinco reglas de seguridad (reglas de oro). Los transformadores de corriente inyectados no instalados deben tener un cortocircuito en los extremos de sus cables de señal. Los TC de núcleo dividido sólo son adecuados para su instalación en cables de alta tensión resistentes al tacto. Para la instalación en cables de alta tensión no apantallados se dispone de TC independientes bajo pedido. 2.2 Suministro de tensión auxiliar El sistema IKI-35 funciona sin alimentación de tensión auxiliar externa. El sistema es alimentado principalmente por la corriente primaria Ip a través de los TC. Para corrientes Ip > 10 A: Los TI suministran completamente las corrientes al IKI-35 Para 1A > Ip > 10 A: Alimentación mixta entre batería y TI al IKI35 Batería: Batería de litio, diseñada para alimentar el IKI-35 durante al menos 15 años. Después de 15 años se recomienda realizar una prueba de batería, o sustituir la batería (ver capítulo 5). La vida útil calculada incluye 200 disparos. Si se desea, el IKI-35 puede alimentarse alternativamente con cualquier tensión auxiliar de 24... 230 Vac/dc. La tensión auxiliar se puede aplicar en las bornas 13, 14 y también será respaldada por la batería. En caso de que el IKI-35 esté alimentado permanentemente a través de los TC con Ip > 10 A o alimentado por una tensión auxiliar, la vida útil de la batería se ampliará a más de 20 años. issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 4/25 2.3 Split-Core CTs Para la medición de corriente se utilizan TC de núcleo partido de amplio margen que se adaptan al IKI-35. Los TC de núcleo dividido se pueden instalar en los cables de MT o mediante un adaptador en los casquillos tipo C (EN 50180). 2.3.1 Installation of Split-Core CTs For mounting and installation of the CTs please note: - El montaje es independiente de la dirección de la corriente - Los polos no tienen que estar conectados a tierra figure 2.3 Los tres TC de núcleo dividido (IKI-LUM_d92) deben montarse en los núcleos únicos del cable de alta tensión e instalarse en las abrazaderas 1-6. Los blindajes de los cables deben ser aislados y conducidos de vuelta a través de los TC (figura 2.3.1 a) para que sólo la corriente primaria fluya a través del TC. Dependiendo del tipo de cable, los terminales deben estar aislados (figura 2.3.1 b). Por medio de un TC de núcleo equilibrado en la entrada E (bornas 7, 8) también se pueden detectar faltas a tierra sensibles Ie> por debajo de 20 A o Ie> por debajo de 0,7xIn. El TC con núcleo equilibrado cubre los tres núcleos individuales. El blindaje común de un cable de tres hilos o los blindajes individuales de los cables de un hilo deben ser aislados y conducidos de vuelta a través del TC de núcleo equilibrado. Principle of leading back the shield CORRECT Three core cable for shielded single cores the cable terminations must be insulated and the shields must be leaded back through the CTs. For unshielded single cores special CTs are available on request! Single core cable the shields must be leaded back through the CTs! insulated installation CT CT IKI-30LU IKI-LUM_d92 CT CT IKI-30LU IKI-LUM_d92 FALSE! balanced core CT e.g. IKI-GSU alternatively in front of or behind separation unit figure 2.3.1a issue 2018-06-08 subject to change valid from serial-# 1805516 figure 2.3.1b balanced core CT e.g. IKI-GSU figure 2.3.1c File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 5/25 2.3.2 CT-Types for Protection Relay IKI-35 NOTA:Las entradas de medición del IKI-35 son específicas de los TC IKI-LUM_d92, es decir, la carga del relé y la potencia de salida de los TC se adaptan entre sí. Por lo tanto, no se permite la instalación de TI estándar con corrientes secundarias de 1 A o 5 A. a) Single core CT for insulated, screened single core cables CT Type IKI-LUM_d92_xxm Connecting lead xx in meters Inner diameter 92 mm Transmission ratio 10 A/0.005 A Power @ burden 0.02 VA@10A Class 10P30 together with IKI-35 Nominal frequency 50 .. 60 Hz Thermal max. current 23 kA, 5 s (34KA - 2s) Thermal max. perm. current 250 A Insulation voltage 2 kV Protecting degree IP 54 b) Single core CT for insulated, bushings CT Type IKI-LUM_d92_xxm Connecting lead xx in meters Inner diameter 92 mm Transmission ratio 10 A/0.005 A Power 0.02 VA@10 A Class 10P30 together with IKI-35 Nominal frequency 50 .. 60 Hz Thermal max. current 23 kA, 5 s (34KA - 2s) Thermal max. perm. current 250 A Insulation voltage 2 kV Protecting degree IP 54 Accessory adapter for C-type bushing; item no. 2501399 c) figure 2.3.2 a) figure 2.3.2 b) TC homopolar para cable apantallado aislado. Para detección de falla a tierra sensible Ie> por debajo de 0,7 In o por debajo de 20A CT Connecting wire: Inner diameter: Transmission ratio: Nominal frequency: Thermal max. current: Insulation Voltage: Degree of protection: issue 2018-06-08 subject to change valid from serial-# 1805516 Type: IKI-GSU_d60_314 pluggable Available standard-lengths: 3m, 5m, 10m, others on request 60mmx314mm 2000/1 50 .. 60 Hz > 30 kA, 2x10 s (IKI-35 connected) > 3 kV IP 54 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 6/25 2.4 Descripción del bornero Inputs: Clamp 1 and 2: Clamp 3 and 4: Clamp 5 and 6: Clamp 7 and 8: Clamp 9: Clamp 11 and 12: Clamp 13 and 14: Outputs: Clamp 15, 16: Clamp 17: Clamp 18, 19: Clamp 18, 20: Clamp 18, 21: All Relays: Split-core CT input for I> L1, sin polaridad Split-core CT input for I> L2, sin polaridad Split-core CT input for I> L3, sin polaridad Optional balanced core CT input E for sensitive Ie>; sin polaridad Earthing connection, max. length 3 m i se utili a esta entrada, las bornas 11/12 deben ponerse a tierra mientras la entrada no esté activada y la tensión debe aplicarse sólo cuando se vaya a reali ar la desconexión. Posibilidad de montaje opcional para tensión auxiliar externa 24... 230 VAC/DC Si se utiliza tensión auxiliar se recomienda un filtro de ferrita tipo abrazadera EMC en el cable de conexión (p. ej. Würth Elektronik tipo 742 711 32 www.we-online.de). Salida para bobina de disparo de baja potencia, alimentada por IKI-35. Adecuado para bobinas hasta 24Vcc / 0,1 Ws (CON POLARIDAD!) No se requiere tensión auxiliar externa. Sin uso. Relay 2, function and contact type (NO or NC) to be configured Relay 1, function and contact type (NO or NC) to be configured Relé de control; cerrado cuando hay tensión auxiliar y funcionamiento correcto; abierto cuando no hay tensión auxiliar. Capacidad de conmutación: 250Vac@5A; 30Vcc@5A; 220Vcc@0,3A Bloques de bornas en la parte trasera del IKI35 Bloque inferior: 14-bornas Bloque superior: 7-bornas figure 2.4 issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 7/25 The unintended unplugging of the connectors can be avoided by the fixation of the cable bundle using a cable tie and the cable tie holder. The cable-tie itself is not included in the shipment. Cable tie in cable tie holder figure 2.5 Cable tie fixes cable bundle and secures connectors against unintended drawing figure 2.6 issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 8/25 3. Indication/Settings 3.1 3.1.1 Indication Basic-Screens/Navigation Para encender la pantalla, pulse cualquier botón: 3.1.2 Indicación de estado 3.1.3 Indicación de falta después de fallo 3.1.4 Indicación detallada Pulsar y navegar Se pueden mostrar hasta 20 eventos issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 9/25 3.2 Ajustes IKI-35 permite ajustar la configuración del sistema y el comportamiento de los captadores. Dependiendo de la configuración de software y hardware, es posible que no todas las opciones estén disponibles. 3.2.1 Ajustes del IKI35 setting of tipo de los trafos de corriente (CT): Ajuste del - IKI-LUM-d92 = rango completo de los CT CT Type HC on=/ wide off -- Opción IKI-LUM-30 range CT DISPONIBLE -- ../ ../ 1A 1ANO not available Ajuste settingdeofla intensidad nominal del primario, en los setting CT In = current 10...250 A nominal primary Para la opción HC = ON range In = 10 ..25 0A for wideIn = 100...400 A range CTs Ajuste de frecuencia nominal de red: 50 / 60 Hz Ajuste de bloqueo para la intensidad de conexión: on / off Ajuste deofla etapa de defecto a tierra mediante: setting -earth-fault CT homopolar independiente d60x314 stage - CT homopolar d130 (tipo antiguo) by - Método Delta-I (sin CT) (intensidad calculada) - separate balanced core CT - delta-I-method (no sep. CT) Ajuste de la corriente más baja para mostrar en pantalla: I on Es decir, si se muestra I on, el TC mide el rango de corriente (0,1...0,5) * In issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 10/25 Configuración del tipo de contacto: N.O. (normally open) N.C. (normally closed) setting of Reset-Mode 2h, 4h, 8h, auto (auto: if primary current is detected) Ajuste del tipo de alarma: - Desactivado - Disparo - Sobrecorrientet I> o Ie> -Sobrecorriente I> - Sobrecorriente Ie> setting of menu-language - English - German - Russian Ajuste de la activación del relé de disparo: on / off Ajuste del nivel mínimo de tensión de disparo: 68%…100% setting / change of password XXXX factory setting: 1234 Ajuste para la iluminación de la pantalla: on / off Ajuste de la relación de corriente máxima hasta la cual se realizará el disparo I / In Rango: Desactivada / 0...20 Ajuste de Disparo retardado después de que la corriente cae por debajo de la corriente de conmutación máxima: YES / NO NO: Sin desconexión si se alcanza la corriente de conmutación máxima y vuelve a descender. return to factory settings Indication: Hardware-Version Software-Version Contact for Service Serial number issue 2018-06-08 subject to change valid from serial-# 1805516 confirmation ID of base firmware File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany ID of front firmware Page 11/25 3.2.2 Ajuste de los valores de disparo Se pueden establecer los siguientes valores y características en el IKI35: - I>, Sobrecorriente - I>>, Cortocircuito - I>>>, Cortocircuito 2º escalón - Ie>, Derivación a tierra 1º escalón - Ie>>, Derivación a tierra 2º escalón characteristics: DMT or IDMT (extremely, very, normal or longtime) characteristics: DMT or instantaneous (t=0) characteristics: DMT or instantaneous (t=0) characteristics: DMT or IDMT (extremely, very, normal, or longtime) characteristics: DMT or instantaneous (t=0) figure 3.2.2 3.2.2 a) Como ejemplo de los ajustes DMT o instantáneos, se describe el ajuste I>>> Nota: In = Corriente nominal a definir en el menú de ajuste del sistema. 0..32 issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 12/25 3.2.2 b) Como ejemplo para el IDMT se describe el ajuste I> : Ajuste de las curvas de disparo: - DMT - IDMT - deactivated setting of I> Type - extremely - very - normal - long-time setting of Time multiplier TMS 0,05 .. 10 step: 0,05 Ajuste de la corriente de arranque de la curva: I / In 1,1...3 The tripping time for IDMT is calculated according the following formulas: Where: t = tripping time in (sec) I = actual primary current (A) In = nominal primary setting current (A) v = TMS*sec = Time Multiplier Setting * sec figure 3.2.2 b) issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 13/25 3.3 3.3.1 Inrush rejection Inrush rejection for IL1 .. IL3 La sobrecorriente (I>) a vigilar es a menudo cercana, o algo inferior, a la corriente de entrada. Durante la corriente de conexión, el IKI-35 no debe dispararse. Generalmente el tiempo de disparo por sobrecorriente (tI>) debe ser mayor que el tiempo de conexión esperado. El valor de corriente de cortocircuito (I>>), que se desconecta después del tiempo de retardo de cortocircuito (tI>>>), debe seleccionarse siempre considerablemente por encima del valor de corriente de conexión. Los valores de las corrientes de entrada y la duración de las mismas deben ser tomados de la documentación de los fabricantes de transformadores. Además, el IKI-35 ofrece un algoritmo de rechazo de intensidad de conexión que puede activarse en el menú. Si el transformador pasa del estado de apagado (I<2A, para las tres fases) al estado de encendido, el algoritmo de rechazo de arranque supervisa si existe una condición de sobrecorriente para las tres corrientes de fase. Hay que distinguir un cortocircuito trifásico de la corriente de conexión. En el caso normal, se supone que un cortocircuito trifásico en las bornas de entrada presenta valores de corriente mayores que la puesta en servicio del transformador. Se supone que el cortocircuito trifásico, en bornas del transformador, es de 10 veces la In (las corrientes de entrada pueden alcanzar valores de hasta 7 veces ln). The inrush criterion is fulfilled if the three-phase current meets the following conditions after a currentless state: less than 10 times In less than I>> (if I>> stage active) greater than I> and longer than tI> In this case, the tripping is rejected. If after 3s the inrush criterion is still fulfilled, then tripping is executed. The inrush rejection method is activated in the setting menu of IKI-35. 3.3.2 Inrush-rejection for Ie In compensated networks it is suggested to select a long-time tIe> as inrush rejection to ensure that the inrush current is delayed before a tripping may occur. Inrush rejection for Ie is also activated in the setting menu! In solidly or low-resistive terminated networks an inrush rejection for Ie according to the following criterion is introduced. If, after a currentless state, the I0-current is less than 5 times Ie> greater than Ie> and longer than tIe>, then the tripping is rejected. If after 3s the inrush criterion is still fulfilled, then tripping is executed. The inrush rejection method is activated in the setting menu of IKI-35. The figures below show the correct position of the transformer characteristic between the three pole transformer clamp short-circuit current Isc and the inrush current. Then a separate inrush rejection should not be necessary. In these cases it is assured by the setting that the inrush current does not cause tripping whereas the three pole transformer clamp current is switched off with certainty surely. I_Trafomonitor + Fuse I_primary_protection t I_Trafomonitor I_primary_protection t Isc figure 3.3 Isc Inrush Inrush I_N I> issue 2018-06-08 subject to change valid from serial-# 1805516 I_secondary_protection I I_N I> I_secondary_protection I File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 14/25 3.5 Setting examples 3.5.1 Setting example 1: Given: Transformer-nominal power: Nominal voltage: Allowed overload: 1250 kVA 12 kV 2 x In for 5 s Requested: Instantaneous trip: Short-circuit fast trip: Overcurrent characteristic: Relay 1: Relay 2: at 20 x In with tI>> = 0,05s at 15 x In with tI>> = 0,1s acc. DMT definite minimum time characteristic activation during overcurrent (I> or Ie>) as normally closed contact, N.C. activation in case of tripping as normally closed contact, N.C. Calculation In: In = 1250kVA/(12kV *3) = 60 A Settings: Nominal current: In = 60 A Over current DMT: I>/In = 2, tI> = 5 sec. Short-circuit current DMT: I>>/In = 15; tI>> = 0,1sec. Instantaneous tripping current: I>>>/In =20; tI>>> = 0,05 sec.* Relay 1: contact: N.C., alarm: I> or Ie> Relay 2: contact: N.C., alarm: tripping 3.5.2 Setting example 2: Given: Transformer-nominal power: Nominal voltage: Allowed overload: 1250 kVA 12 kV 2 x In for 5 s Requested: Instantaneous trip: Short-circuit fast trip: Overcurrent characteristic: Relay 1: Relay 2: at 20 x In with tI>> = 0,05s at 15 x In with tI>> = 0,1 acc. IDMT Very Inverse activation during overcurrent (I>) as normally open contact, N.O. activation in case of tripping as normally open contact, N.O. Chose IDMT: type Very Inverse Calculation of In: Selection v: In = 1250kVA/(12kV*3) = 60 A I> = 2 xIn -> I>/In = 2 (Starting point of IDMT-curve) Herewith a tripping time of 5s at I>/In=2 results This is given with TMS=0,37 -> chose TMS=0,35 (calculated from formula for Very Inverse 3.2.2b) I>>=15x In -> I>>/In = 15 Since the IDMT-overcurrent curve for v=0,4 at I/In=15 only results in a tripping time of t=0,35s the additional short circuit stage with I>>/In = 15 and tI>>=0,1 must be overlaid Calculation I>>/Is: Settings: Nominal current: In = 60 A Over current IDMT: very inverse, I/In = 1,1; TMS = 0,35 Short-circuit current DMT: I>>/In = 15; tI>> = 0,1sec. Instantaneous tripping current: I>>>/In =20; tI>>> = 0,05 sec.* Relay 1: contact: N.O., alarm: I> Relay 2: contact: N.O., tripping * inherent time of IKI-35: about 20 ms must be added to the respective time issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 15/25 4. Technical Data Nominal current In Short circuit stage I>>: pickup values delay time Overcurrent stage I>: DMT-pickup delay time IDMT 1/2/3/4 initial value Time Multiplier Setting primary side nominal current selectable 10 ... 250 A for wide-range CTs, Option HC off selectable 100 ... 400 A for Option HC, details in separate datasheet ratio I>>>/In, I>>/In tI>>>, tI>> selectable 2 .. 32 or deactivated selectable 0.05* ... 2 s ratio I>/ In tI> inverse characteristics ratio I>/In TMS selectable 1.1 .. 3 selectable 0.3 .. 300 s selectable 1. extremely; 2. very; 3. normal; 4. long-time selectable 1.1 .. 3 selectable 0.05* .. 10 Earth fault stage Ie>: Earth fault pick-up value delay time Ie>_DMT-pick-up value delay time Ie>_IDMT 1/2/3/4 initial value Time Multiplier Setting ratio Ie>>/In tIe>> ratio Ie>/In tIe> inverse characteristics ratio Ie>/In TMS selectable 0.1 .. 4 or deactivated selectable 0.05* .. 2 s selectable 0.1.. 2; for values below 0.7 balanced core CT is required selectable 0.05* .. 5 s selectable 1. extremely; 2. very; 3. normal; 4. long time selectable 0.1 .. 2, for values below 0.7 balanced core CT is required selectable 0.05* .. 10 Reset ratio / time 70% to 100% of setting / 30ms Frequency Inherent time* Waiting time between 2 (external) tripping commands of network <= 20 ms 5sec with auxiliary power 15sec without aux. power Reset Alarm-Relays Auxiliary supply selectable 50/60 Hz must be added to lowest setting time for remote tripping, during function test or SOTF (switch-on-to-fault) this is the recommended time to wait for reliable tripping; if waiting time is less than 5/15 sec, IKI-35 might trip with delay compared to expected time tI>> for trip indication selectable 2 h/4 h/8 h OR autom. 20 s after current recovery (min. Ion) OR by push buttons 2 function selectable: NC/NO, selectable logic: I> + Ie>; I>; Ie>; Trip Remark: for energy-saving the relays are delayed compared to tripping output (Ie> alarming (e.g. excitation) is delayed more to avoid intermittent alarming), they are only used for alarming, not for tripping; switching capacity: 250VAC@5A; 30VDC@5A; 220VDC@0,3A CT-supplied buffered by Lithium battery ; alternatively: 24 ... 230 VAC/DC Earth fault stage by asymmetry calculation (delta-I-method) for earth fault currents above 20 A (or Ie>/In >=0.7) or with sep. balanced core CT at Input 4 for sensitive earth fault with currents below 20 A (or Ie>/In <0.7) Event Recorder Up to 20 event log entries with relative timestamp Product standard IEC 60255-1:2009 Accuracy of complete system comprising CTs and IKI Current: ±10% ± 1 digit @ 10 ... 250 A (where 1 digit is 1 A) for symmetric 3-phase load ±20% ± 1 digit @ 10 ... 40 A, ±10% ± 1 digit @ 40 ... 250 A for 1-phase excitation DMT-Time: ±10% or ± 25ms (±25% or ± 30ms @ <40A for 1-phase excitation) IDMT-Time: acc. IEC 60255-151: 62,5% for I/In = 2..5; 35.5% for I/In = 5..10; 25% for I/In > 10 Limitations: for 1 phase excitations with tI>> / tIe>> set to 0.05 s a current of at least 45 A is required. for 1 phase excitations with tI> / tIe> set to 0.3 s a current of at least 35 A is required. for 3 phase excitations with tI> / tIe> set to 0.3 s a current of at least 16 A is required. Operation/storage temperature -40 °C .. +70 °C Housing / Protection degree Dimensions / Recommended Cut front panel mounting DIN 43700 w x h x d=96 x 48 x 80 mm Current transformers connected to input 1, 2, 3: optionally to input 4: Types CTs Para bobinas de disparo de hasta 24V / 0,1Ws for mounting at MV-cable; connecting leads available with lengths 1-15m for mounting at C-cone bushing, connecting leads available with lengths 1-15m Bobina de disparo de baja potencia, 3 V, 0,02 Ws Lectura de la configuración y del registro de eventos a través del PC IKI-35_24V IKI-LUM_d92_kab IKI-LUM_d92_hul Coil IKI-30-TC Software Kries-Config / -40 °C .. +80 °C / / IP40; front IP54 92,2x45,2 mm split-core current transformer type IKI- LUM_d92 (up to 250 A nom.curr.) balanced current split-core transformer; type depending on diameter Dimensions figure 4.1 issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 16/25 5. Functional Test/Maintenance 5.1 Tests a) System Test Functions: From standard status screen the system-test menu is activated by “left” button. Function test: Display test: Current check: b) the function test allows a complete failure simulation including activation of tripping coil and relays; to perform the function test the password has to be entered. The display test will test the complete LCD- and LED-functions. The current check shows the phase currents of each phase and the residual current I0sum (sólo si se instala el transformador homopolar) Primary Current Test / Secondary Test b1) Primary Current Test: Injection of primary current into the CTs with primary current generator The Primary Current Test is performed by means of a primary current generator which is capable to simulate the required pickup currents. If the pickup currents could not be reached by the primary current generator, ampereturns can be used to reach the currents (see appendix). b2) Secondary Test: For maintenance test or installation test secondary tests can be performed. For the secondary test the CTs have to be removed from the clamps 1-8. At the CT-clamps (1-8) an AC-voltage has to be applied for simulation. The AC-voltages can be generated by means of most common AC-sources (e.g. protection testing devices) (for detailed information see appendix). 5.2 Maintenance/Battery Change: If the status of the standard menu does not show ´STATUS OK´ after awaking the display by any button, the battery must be changed. A periodic change of the battery is recommended after 15 years. For this, all leads must be disconnected from the clamps and the front cover has to be opened. Behind the front cover the battery can be accessed. Static charges on tools or body should be discharged before touching the circuit board. Subsequently the battery can be unplugged, removed from the holder and replaced by a new one; observe polarity! Replacement battery: Type LS 17500, 3.6 V, manufacturer Saft; recommended type: Kries-IKI-35-battery Unplug battery and remove from holder. Replace battery and observe polarity! 1. remove front cover issue 2018-06-08 subject to change valid from serial-# 1805516 2. open device 3. battery is placed behind circuit board File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 17/25 6. Bobina de desconexión de baja potencia La bobina de disparo de baja potencia tipo IKI-30TC fue especialmente diseñada para su aplicación con IKI-35 y se instala en las bornas 15,16. Cuando se utiliza el IKI-30TC no se requiere tensión auxiliar externa en los bornes 13,14. figure 6 7. Restrictions / Special Applications 7.1 Tripping-Coils with high power requirement La salida 15,16 del IKI-35 es adecuada para bobinas de disparo de hasta 24V, 0,1Ws (sin necesidad de alimentación de tensión auxiliar para el IKI-35). En el caso de bobinas que requieren mayor potencia, se debe instalar un relé de acoplamiento y una unidad de almacenamiento de potencia capacitiva adicional, por ejemplo, una fuente de alimentación del tipo PSU. Fuente de alimentación 10A: 6EP3334-8sb00-0ay0 UPS 24Vcc 10A: 6EP1933-2EC41 WAGO-788304 Relé 1 contacto conmutado 16A y bobina 24Vcc. SIEMENS LZS:RT3A4L24 issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 18/25 7.2 Limitación de la función Ie>IDMT Curva de disparo Ie>-IDMT Para Ie> se puede seleccionar el tipo de característica tiempo-corriente IDMT. El valor de consigna Ie> puede seleccionarse entre 0,1In y 2In. Pero para el cálculo del tiempo tIe> se utiliza la corriente nominal In. El dispositivo actúa según la característica tiempo-corriente como se muestra en la figura 7.1, una mezcla entre las características DMT e IDMT. Tiempo tIe> Característica IDMT según fórmula 0,1*In In 1,1*In Corriente Ie Figure 7.1 Característica de tiempo-corriente si se selecciona el tipo IDMT para (Ie>), por ejemplo, para el valor de arranque (Ie>) = 0,1*In issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 19/25 8. Appendix: Function-Test IKI-35 Primary Current Test/Secondary Test El relé de protección IKI-35 puede probarse mediante inyección de corriente primaria en los TI o secundaria por medio de una tensión de simulación que se aplicará en las bornas de entrada de los TI en el IKI35. Attention: - Para las pruebas primarias o secundarias de IKI-35 se recomienda desactivar la supresión de la I de conexión. - Si se quiere evitar el disparo durante la prueba, la bobina de disparo debe desactivarse en las bornas deI KI35. - Para la evaluación de la precisión de la corriente de arranque se deben observar las tolerancias según los datos técnicos de IKI-35. - Para la evaluación de la precisión del tiempo de arranque, especialmente para las curvas IDMT, la tolerancia a la corriente debe ser considerada en la fórmula del IDMT. 8.1 Primary Current Test: Injection of primary current into the CTs by means of primary current generator El ensayo de corriente primaria se realiza mediante un generador de corriente primaria capaz de simular las corrientes de captación necesarias. La corriente primaria debe inyectarse de acuerdo con la figura A/B. Si las corrientes de arranque no pueden ser alcanzadas por el generador de corriente primaria, se pueden utilizar amperios-vueltas para alcanzar las corrientes de arranque. Alternativamente, también está disponible un bobinado de prueba con giros de 50 amperios, que se puede conectar al TC. Estos devanados de prueba permiten generar una corriente primaria de hasta 1000 A (ver figura A/B). 8.2 Secondary Test: Para las pruebas de mantenimiento o de instalación se pueden realizar pruebas secundarias. Para la prueba secundaria, los TC deben retirarse en las bornas 1-8. En las bornas 1-8 del IKI35 se debe aplicar una tensión alterna para la simulación. Los voltajes de CA pueden generarse por medio de las fuentes de CA más comunes (por ejemplo, dispositivos de prueba de protección). La prueba secundaria se realiza de acuerdo con la figura C. issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 20/25 Figure A/B Primary Current Test La corriente primaria puede ser inyectada mediante amperios vuelta o mediante un bobinado de prueba opcional. A: ampere-turns B: Test-winding and IKI-Primary-Test-Box Test winding with 200 windings, max. 30A (1 sec). Typ: IKI-LUM_PW The CT type IKI-LUM_d92 can be also retrofitted with the test winding. As an option the IKI-Primary-Test-Box is available; the IKI-Primary-Test-Box offers the same shape as IKI-35 and can be also installed at a standard C-bar. The test-sockets inside the IKI-Primary-Test-Box allow to install a current source with currents of 1..30A. By means of the test-winding primary currents acc. below diagram are generated. ATTENTION: Currents above 1A must not be applied for more than 1sec.! issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 21/25 Figure C Secondary Test Test-circuit Para la prueba secundaria del IKI-35 se debe aplicar un voltaje de CA a las bornas de los TC. Los TC deberían estar en cortocircuito si hay corriente primaria disponible. Watchdog 21 N.C. 20 N. C. Relay1 19 N.C. Relay2 Note: 3V int 24Vi nt 18 17 Relay = 16 - Aplicar la tensión sólo a corto plazo - Evitar tensiones superiores a los valores mencionados en la tabla. - Reduzca la potencia de salida de su fuente de tensión alterna hasta un límite seguro. - Preste atención a su seguridad, voltajes peligrosos están presentes! - Opción HC off + Tripping Device Ausl. intern versorgt Trip internal supplied G ND 15 14 H il fse n er gi e 13 a u x vo lta g e 1 2 A us l. fe rn La conexión a tierra 9 debe abrirse durante la prueba de aislamiento! tri p r em o te 11 10 5 4 3 2 1 AC Voltage AC Voltage secondary test E AC Voltage AC Voltage CT-i nputs 6 L2 L3 E L1 L2 9 GN D 8 7 Conecte la fuente de tensión alterna ajustable a la entrada L1, L2, L3 o E del TC para probar la entrada correspondiente. Seleccione el voltaje de la fuente de tensión para simular una corriente primaria de acuerdo con las tablas que aparecen a continuación. Todos los valores son valores RMS (rootmean-square-) para una forma de onda de tensión sinusoidal. Con la ayuda del punto de menú "control de corriente" se puede comprobar que la corriente deseada se simula con la tensión seleccionada. Mediante el cambio de la tensión se puede adaptar la corriente simulada deseada. Rel.gemeins. Relay com. Ausl. extern versorgt Trip external suppli ed Ausl.gemeinam Trip common IKI-35 secondary test L1 secondary test L2 secondary test L3 Elemento del menú "Control de corriente". issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 22/25 Necessary clamp voltage to simulate primary current (L1, L2, L3) 50Hz 60Hz 16 14 Clamp voltage (V) 12 10 8 6 4 2 0 0 10 20 30 40 50 60 70 80 90 100 Current (A) Chart for secondary test at CT-input L1, L2, L3 Necessary clamp voltage to simulate primary current (L1, L2, L3) 50Hz 60Hz 44 Clamp voltage (V) 39 34 29 24 19 14 100 200 300 400 500 600 700 Current (A) Chart for Secondary-Test at CT-input L1, L2, L3 issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 23/25 Necessary clamp voltage to simulate primary current (L1, L2, L3) 50Hz 60Hz 69 Clamp voltage (V) 64 59 54 49 44 700 1200 1700 2200 2700 3200 3700 4200 4700 5200 5700 Current (A) Chart for Secondary-Test at CT-input L1, L2, L3 La tensión (>28V) se puede aplicar en las abrazaderas de entrada L1, L2, L3 durante un tiempo limitado (por favor, tenga en cuenta la tabla). Entonces, por favor, espere un tiempo de pausa de 30 segundos. 70 Time of application of clamp voltage (s) 60 50 40 30 20 10 0 25 30 35 40 45 50 55 60 65 70 Applied clamp voltage (Veff) Chart for time of application of clamp voltage There is a danger of device damage, if the time restriction is not respected. issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 24/25 Necessary clamp voltage to simulate primary current (E) 50Hz 60Hz 12 Clamp voltage (V) 10 8 6 4 2 0 0 5 10 15 20 25 30 35 40 45 50 Current (A) Chart for secondary test at CT-input E (d130) Necessary clamp voltage to simulate primary current (E) 50Hz 60Hz 24 22 Clamp voltage (V) 20 18 16 14 12 10 50 150 250 350 450 550 650 Current (A) Chart for secondary test at CT-input E (d130) Se puede aplicar una tensión <26V a las bornas de entrada E sin restricción de tiempo de aplicación. issue 2018-06-08 subject to change valid from serial-# 1805516 File IKI_35_24V_Manual_e_v_2_2018-06-08_1.doc KRIES-Energietechnik, www.kries.com; DE-71334 Waiblingen, Germany Page 25/25