Uploaded by NAD EEM

IO Points Details Typ.

advertisement
No. of Points
Soft Signal
Open/Close
DO
Start/Stop/On/Off
VDS Speed
Command
Valve Command
AO
Alarm
Status
DI
VFD Feedback
Point Description
Analog Input
Item
Temperature
AI
Totalizer (Energy
Consumption)
Points List
HV Section IO Points Details
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Typical 11KV HV Switchgear - Incomer Feeders
Frequency
Voltage
Current
Power Factor
MVA
MWH Meter
Surge Alarm
VCB Local / Remote Mode Selection
VCB ON / OFF Status
VCB Trip Status
Restricted Earth Fault Trip
Earthing Switch Open/Close
11kV VT Failure
Circuit breaker Failure trip
Overcurrent protection
Earth fault protection
VCB Out of Service Status
VCB Withdrawn Status
VCB ON (Close) Command
VCB OFF (Open) Command
B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Typical 11KV HV Switchgear - Outgoing Feeders
Frequency
Voltage
Current
Power Factor
Surge Alarm
VCB Local / Remote Mode Selection
VCB ON / OFF Status
VCB Trip Status
Restricted Earth Fault Trip
Earthing Switch Open/Close
VCB Out of Service Status
VCB Withdrawn Status
VCB ON (Close) Command
VCB OFF (Open) Command
1
1
1
1
1
1
1
1
1
1
20
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
14
1
1
1
1
1
1
Remarks
VFC: Volt Free Contact
C
1
2
3
4
5
6
7
8
9
10
11
Transformer
Buchholz protection
Oil temperature
Winding temperature
Pressure relief valve
Transformer Oil low level
Differential protection
Neutral Over-voltage protection
Tap changer upper position
Tap changer Lower position
Tap changer failure
Restricted Earth Fault Trip
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
LV Section IO Points Details
Typical LV Switchgear - Incomer Feeders
Frequency
Voltage
Current
Power Factor
MVA
MWH Meter
Surge Alarm
Main ACB Local / Remote Mode Selection
Main ACB ON / OFF Status
Main ACB Trip Status
Restricted Earth Fault Trip
Main ACB Withdrawn Status
Main ACB ON (Close) Command
Main ACB OFF (Open) Command
B
1
2
3
4
5
6
7
8
9
10
11
Typical LV Switchgear - Outgoing Feeders (160A Above or Equal)
Outgoing ACB Local / Remote Mode Selection
Outgoing ACB ON/OFF Status
Outgoing ACB Trip Status
Outgoing ACB Withdrawn Status
Outgoing ACB ON (Close) Command
Outgoing ACB OFF (Open) Command
Outgoing MCCB ON/OFF Status
Outgoing MCCB Trip Status
Outgoing MCCB Withdrawn Status
Outgoing MCCB ON (Close) Command
Outgoing MCCB OFF (Open) Command
1
1
1
1
1
1
No. of Points
Soft Signal
Open/Close
DO
Start/Stop/On/Off
VDS Speed
Command
Valve Command
AO
Alarm
Status
DI
VFD Feedback
Point Description
Analog Input
Item
Temperature
AI
Totalizer (Energy
Consumption)
Points List
11
1
1
1
1
1
1
1
1
1
1
1
1
14
1
1
1
1
1
1
1
1
1
1
1
6
1
1
1
1
1
1
1
5
Remarks
VFC: Volt Free Contact
C
1
2
Typical DC Battery & Battery Chargers
Battery Charger Alarm
Battery Charger Earth Fault
D
1
2
3
4
5
6
Typical SMDB's - Incomer Feeders
Main Breaker ON / OFF Status
Main Breaker Trip Status
Normal Source Available Feedback
Emergency Source Available Feedback
Normal Source Position Indication
Emergency Source Available Indication
E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Typical Generator
Generator Ready Status
Normal Power On/OFF Status
Engine Manual Override Status
Engine Auto Mode Status
Engine Start / Stop Command
Engine Started Feedback
Engine Failed Feedback
Engine Temperature Water Reading
Engine Oil Pressure Reading
Engine RPM Reading
Line Voltage Reading
Frequency Reading
PF Reading
Current Reading
MVA Reading
kW-H Reading
Generator Temperature Reading
Battery Charger Indicator Reading
Main CB ON / OFF Status
Main CB Trip Status
Genset Day Tank Fuel Level High Alarm
Genset Day Tank Fuel Level Low Alarm
Genset Day Tank Fuel Level Low Low Alarm
Genset ECU Status
Generator Exhaust Damper Position Feedback
Generator Exhaust Damper Open / Close Control
Generator Air Intake Damper Position Feedback
Generator Air Intake Damper Open / Close Control
1
1
No. of Points
Soft Signal
Open/Close
DO
Start/Stop/On/Off
VDS Speed
Command
Valve Command
AO
Alarm
Status
DI
VFD Feedback
Point Description
Analog Input
Item
Temperature
AI
Totalizer (Energy
Consumption)
Points List
2
1
1
1
1
1
1
6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
28
Remarks
VFC: Volt Free Contact
No. of Points
Soft Signal
Open/Close
DO
Start/Stop/On/Off
VDS Speed
Command
Valve Command
AO
Alarm
Status
DI
VFD Feedback
Point Description
Analog Input
Item
Temperature
AI
Totalizer (Energy
Consumption)
Points List
F
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Typical UPS
Battery Low Indication
Battery Fault
Rectifier Fault
Inverter Fault
System Overload
UPS in Bypass Mode
UPS in Normal Mode
UPS in Battery Mode
Battery Boost Charging
Battery Discharging
UPS Input Voltage
UPS Input Current
UPS Input Frequency
UPS Ouput Voltage
UPS Output Current
UPS Output Frequency
Battery Voltage
Battery Current
G
1
2
CCTV & Security System
Control System Power Fail Status
Security Alarm Detected Signal
1
1
2
H
1
2
Access Control System
Security Alarm
Common Fault Signal
1
1
2
I
1
Typical Lighting Control System
LCP Circuits ON/OFF Status ( each circuit)
J
1
2
3
FM 200 System
System Fault
FM200 Release
System Status
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
18
1
3
Remarks
VFC: Volt Free Contact
K
1
2
Access Control System
Security Alarm
Common Fault Signal
L
1
2
Space Temperature Sensor
Space Temperature Sensor for LV Room
Space Humidity Sensor for LV Room
M
1
2
3
4
5
6
7
8
9
Power factor capacitor panel
General Alarm
CB Status
Low Power Factor
Abnormal Power Factor
Leading Power Factor
Over Current
Over Temperature
Over Voltage
Capacitor Overload
N
1
2
2
3
3
4
4
5
5
6
6
7
Typical Pumps With VFD
Pump DPS Flow status
Pump Running status
System Local /Remote Selection
Pump trip status
Pump Emergency PB
Pump Start / Stop Command
Pump Speed Feedback (RPM)
Pump Speed Command (RPM)
Motor winding Temperature RTD-01
Motor winding Temperature RTD-02
Motor winding Temperature RTD-03
Pump Discharge Pressure
1
1
No. of Points
Soft Signal
Open/Close
Start/Stop/On/Off
DO
VDS Speed
Command
Valve Command
AO
Alarm
Status
DI
VFD Feedback
Point Description
Analog Input
Item
Temperature
AI
Totalizer (Energy
Consumption)
Points List
2
1
1
2
1
1
1
1
1
1
1
1
9
1
1
1
1
1
1
1
1
1
1
1
1
1
12
Remarks
VFC: Volt Free Contact
O
1
2
3
4
5
6
7
Typical Pen Stocks/Motorized Valves
Open Feedback
Close Feedback
System Local /Remote Selection
Fault /Healthy
Open Command
Close Command
Power On Status
P
1
2
3
4
5
6
7
8
9
10
Typical Pumps Without VFD
Pump DPS Flow status
Pump Running status
System Local /Remote Selection
Pump trip status
Pump Emergency PB status
Pump Start / Stop Command
Pump Discharge Pressure
Motor winding Temperature RTD-01
Motor winding Temperature RTD-02
Motor winding Temperature RTD-03
Q
1
Water Tanks Typical ( Each compartment)
Water Storage Tank Level Transmitter
Water Storage Tank Level Switeches with 4 probes
(HH,H, L, LL)
Inlet Flow Meter
Water Storage Tank Inlet Isolation Valve Open
Status
Water Storage Tank Inlet Isolation Valve Close
Status Storage Tank Inlet Isolation Valve Open / Close
Water
Command
2
3
4
5
6
R
1
2
3
4
5
6
7
8
9
Chlorine Dosing Package Unit
Unit Power Status
Unit auto/manual mode
PH value readings
CL ppm reading
water Temperature
Acid Tank Level Low Alarm
Chlorine Tank Level Low Alarm
Dosing Pump On / Off Status
Agitator On / Off Status
No. of Points
Soft Signal
Open/Close
DO
Start/Stop/On/Off
VDS Speed
Command
Valve Command
AO
Alarm
Status
DI
VFD Feedback
Point Description
Analog Input
Item
Temperature
AI
Totalizer (Energy
Consumption)
Points List
1
1
1
7
1
1
1
1
1
1
1
1
1
10
1
1
1
1
1
1
1
1
6
1
1
1
1
1
1
1
1
1
1
1
1
8
Remarks
VFC: Volt Free Contact
W
1
2
3
4
5
Typical Split Unit
DEU Unit Auto/ Manual
DEU Unit Running Status
DEU Unit Fault Alarm
DEU Fan Start/Stop Command
DEU Compressor Start/Stop Command
No. of Points
Weather Station
Temperature Status
Humidity Status
Soft Signal
V
1
2
Open/Close
Typical Supply/ Exhaust Fan
Air Flow Status
Rotary Switch Hand/Off/Auto Status
Damper Open/Close Status
Damper Open/Close Control
Fan Running Status
Fan Trip Alarm
SEF Serving Area Fire / Cleared Signal
Fan Start / Stop Command
Fireman Switch Status
DO
Start/Stop/On/Off
U
1
2
3
4
5
5
6
7
8
VDS Speed
Command
DW Booster Pump with Pressure Tank
System Auto / Manual Selection
Pump Trip Alarm
Pump On/Off Command
Standby Pump On/Off Command
Duty Pump Run Status
Standby Pump Run Command
Pressure Swicth Alarm
Valve Command
T
1
2
3
4
5
6
7
AO
Alarm
Typical Sump Pump ( Package System)
System Auto / Manula Selection
Pump Trip Alarm
Pump On/Off Command
Standby Pump On/Off Command
Pump Running Status
Standby Pump Running Status
High High Level Alarm
Low Low Level Alarm
Low Level Alarm
Unit Power On Status
Status
S
1
2
3
4
5
6
7
8
9
10
DI
VFD Feedback
Point Description
Analog Input
Item
Temperature
AI
Totalizer (Energy
Consumption)
Points List
1
1
1
1
1
1
10
1
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
9
1
1
1
1
1
1
1
2
1
1
5
1
1
1
Remarks
VFC: Volt Free Contact