MEDIUM VOLTAGE
E
Flexible LSZH Rubber Single Core
MV Power
19/33kV 90°C
EPR
Typical Applications
Construction
Power Cable for Mining, Industrial and
Power Utility.
Conductor Fine wire plain or tinned annealed copper to IEC 60228 and
AS/NZS 1125
Conductor Screen Semi-Conductive Cross Linked Rubber
Insulation Ethylene Propylene Rubber (EPR)
Insulation Screen Semi-Conductive Cross Linked Rubber
Metallic Screen Plain annealed copper wire
Separator Polypropylene tape
Jacket Low-Friction LSFLEX® T-10 (HFS-110-TP) Flame Retardant,
Cross Linked, Thermoset, Elastomeric, Low Smoke Zero Halogen. Splash
resistant to oil, skydrol, petrol, acid and sea water. Resists ozone and UV.
Excellent abrasion resistance. Anti-Termite/Rodent Jacket is Available.
Standard Core Configuration
1C: 1
Operating Temp
Standards
-40°C to +90°C
AS/NZS 1125
AS/NZS 1429.1
Voltage Rating
AS/NZS 3808
19000/33000 Volts
AS/NZS 1660.5.1
AS/NZS 1660.5.2
Jacket Colour
To customers specification AS/NZS 1660.5.4
AS/NZS 1660.5.6
NUMBER OF
CORES (c)
X CROSS SECTION
AREA (mm2)
1c
35
1c
50
1c
70
1c
95
1c
120
1c
150
1c
185
1c
240
1c
300
1c
400
1c
500
1c
630
MINIMUM
BENDING
RADIUS
(mm)
203
212
229
241
246
258
270
285
299
323
343
367
NOMINAL
CONDUCTOR
DIAMETER
(mm)
7.8
9.2
10.8
12.8
14.5
16.3
18.0
20.3
22.5
26.0
29.2
32.8
NOMINAL
INSULATION
THICKNESS
(mm)
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
NOMINAL
INSULATION
DIAMETER
(mm)
24.6
26.0
27.6
29.6
31.3
33.1
34.8
37.1
39.3
42.8
46.0
49.6
NOMINAL
OVERALL
DIAMETER
(mm)
33.8
35.4
38.1
40.2
41.0
43.0
45.0
47.5
49.8
53.8
57.2
61.1
APPROX
WEIGHT
(kg/km)
1312
1654
2094
2389
2643
3006
3369
3942
4589
5527
6581
7864
IEC 60228
IEC 60332-1
IEC 60332-3-22
IEC 60754-2
IEC 60502-2
IEC 61034-1&2
MAXIMUM
PULLING
TENSION
(kN)
3.5
5.0
7.1
8.3
9.6
11.1
12.8
15.6
18.6
23.6
28.6
35.1
** There is a +/-2% tolerance to the NOMINAL values due to manufacturing process variations. TriCab is not liable for any errors, omissions, etc., and reserves the right to modify specifications at any time.
NUMBER OF
CORES (c) X
CROSS SECTION
AREA (mm2)
1c
35
1c
50
1c
70
1c
95
1c 120
1c 150
1c 185
1c 240
1c 300
1c 400
1c 500
1c 630
TREFOIL IMPEDANCE
R1
X1
90°C
50 Hz
ohm/km
0.707
0.150
0.492
0.143
0.347
0.138
0.263
0.130
0.206
0.124
0.165
0.119
0.136
0.116
0.104
0.112
0.084
0.108
0.065
0.104
0.052
0.101
0.041
0.098
R0
X0
20°C
ohm/km
1.108
0.094
0.772
0.087
0.544
0.081
0.479
0.075
0.434
0.069
0.402
0.065
0.379
0.062
0.354
0.058
0.338
0.055
0.324
0.051
0.315
0.048
0.306
0.045
CAPACITANCE
CONDUCTOR
TO SCREEN
µF/km
0.153
0.169
0.186
0.207
0.225
0.244
0.262
0.285
0.308
0.344
0.377
0.414
CURRENT RATING (Amps)
BURIED BURIED IN
IN
DIRECT CONDUIT FREE AIR
15°C
15°C
30°C
188
165
195
223
195
234
271
240
291
325
287
355
369
326
407
414
366
463
466
413
527
554
478
618
601
537
703
679
611
813
763
688
929
850
776
1057
FAULT CURRENT RATING
BURIED BURIED IN
IN
DIRECT CONDUIT FREE AIR
25°C
25°C
40°C
175
154
176
207
183
211
253
224
263
303
268
320
343
304
367
385
342
417
434
386
475
516
446
557
559
501
634
633
570
732
710
642
837
791
724
952
ACTIVE
EARTH
1 SECOND 1 SECOND
kA
kA
5.0
5.0
7.2
7.2
10.0
10.2
13.6
10.2
17.2
10.2
21.5
10.2
26.5
10.2
34.3
10.2
10.2
42.9
57.2
10.2
10.2
71.5
90.1
10.2
** There is a +/-2% tolerance to the NOMINAL values due to manufacturing process variations. TriCab is not liable for any errors, omissions, etc., and reserves the right to modify specifications at any time.