Runtime Charts Eaton 93E 80-200 kVA UPS 93E 80-200 kVA UPS on-battery runtimes with different load ratings External Batteries with 93P/E and 93-BAT Large Battery Cabinets Contents 93E battery configuration .............................................................................................................................2 CSB CSB HRL 12V 280W ................................................................................................................................... 2 CSB HRL 12V 330W ................................................................................................................................... 3 CSB HRL 12V 540W ................................................................................................................................... 4 FIAMM FIAMM 12FLB250 ...................................................................................................................................... 5 FIAMM 12FLB350 ...................................................................................................................................... 6 FIAMM 12FLB400 ...................................................................................................................................... 7 FIAMM 12FLB540 ...................................................................................................................................... 8 Large battery cabinet specifications ............................................................................................................. 10 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 Page 1 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS 93E battery configuration Table 1. End of discharge voltage Blocks 36 38 40 Cells 216 228 240 Volts per cell 1.8 V/Cell 1.75 V/Cell 1.67 V/Cell The runtime calculations in this document have been done using End of discharge voltages presented in Table 1. Notice the variation in the End of discharge voltages in regard to number of cells/blocks per string. External batteries with Large Battery Cabinet CSB HRL 12V 280W Table 2. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.8 Battery 280W 280W 280W 280W 280W 280W 280W 280W 280W 280W 280W 280W Qty 1x36 1x38 1x40 2x36 2x38 2x40 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 30 35 39 76 84 96 118 133 152 164 177 197 50kVA 21 25 29 56 63 74 93 104 116 128 144 162 60kVA 15 18 22 45 50 57 76 84 96 106 115 132 80kVA 8 11 14 30 35 39 52 58 68 76 84 96 100kVA 7 10 21 25 29 39 45 50 56 63 74 120kVA 7 15 18 22 30 35 39 45 50 57 160kVA 8 11 14 19 23 27 30 35 39 200kVA 7 10 13 15 19 21 25 29 min min min min min min min min min min min min 160kVA 6 9 12 200kVA 8 min min min min min min Table 3. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.9 Battery 280W 280W 280W 280W 280W 280W Qty 1x36 1x38 1x40 2x36 2x38 2x40 40kVA 26 29 34 65 73 84 50kVA 17 20 25 49 54 62 60kVA 12 15 19 38 44 49 80kVA 6 9 12 26 29 34 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 100kVA 8 17 20 25 120kVA 5 12 15 19 Page 2 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS Battery 280W 280W 280W 280W 280W 280W Qty 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 106 115 132 146 160 176 50kVA 82 90 104 113 123 143 60kVA 65 73 84 92 102 115 80kVA 45 50 57 65 73 84 100kVA 33 38 43 49 54 62 120kVA 26 29 34 38 44 49 160kVA 15 18 22 26 29 34 200kVA 10 13 16 17 20 25 min min min min min min The battery backup table is given with end voltage according to Table 1 and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles. Note! The specifications are subject to change without a notice. CSB HRL 12V 330W Table 4. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.8 Battery 330W 330W 330W 330W 330W 330W 330W 330W 330W 330W 330W 330W Qty 1x36 1x38 1x40 2x36 2x38 2x40 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 37 43 49 89 101 116 144 159 178 192 215 242 50kVA 28 32 45 67 78 90 110 121 145 154 169 192 60kVA 22 25 29 53 60 73 89 101 116 122 140 161 80kVA 13 16 19 37 43 49 60 72 84 89 101 116 100kVA 8 10 14 28 32 45 46 54 62 67 78 90 120kVA 7 10 22 25 29 37 43 49 53 60 73 160kVA 6 13 16 19 26 29 45 37 43 49 200kVA 8 10 14 18 22 26 28 32 45 min min min min min min min min min min min min 160kVA 10 13 16 200kVA 5 8 11 min min min min min min Table 5. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.9 Battery 330W 330W 330W 330W 330W 330W Qty 1x36 1x38 1x40 2x36 2x38 2x40 40kVA 32 37 45 78 87 102 50kVA 24 28 45 57 67 79 60kVA 18 21 25 46 53 60 80kVA 10 13 16 32 37 45 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 100kVA 5 8 11 24 28 45 120kVA 8 18 21 25 Page 3 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS Battery 330W 330W 330W 330W 330W 330W Qty 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 122 140 161 170 187 216 50kVA 97 108 124 134 151 170 60kVA 78 87 102 109 119 143 80kVA 53 60 73 78 87 102 100kVA 40 47 53 57 67 79 120kVA 32 37 45 46 53 60 160kVA 22 25 29 32 37 45 200kVA 15 18 22 24 28 45 min min min min min min The battery backup table is given with end voltage according to Table 1 and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles. Note! The specifications are subject to change without a notice. CSB HRL 12V 540W Table 6. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.8 Battery 540W 540W 540W 540W 540W 540W 540W 540W 540W 540W 540W 540W Qty 1x36 1x38 1x40 2x36 2x38 2x40 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 50kVA 60kVA 80kVA 100kVA 120kVA 160kVA 200kVA 75 83 89 174 189 212 281 299 343 415 452 488 56 62 70 143 155 165 221 244 264 296 336 379 46 51 56 113 127 139 174 189 212 251 271 290 28 33 39 75 83 89 133 146 156 174 189 212 18 23 27 56 62 70 92 109 121 143 155 165 13 17 20 46 51 56 75 83 89 113 127 139 6 8 13 28 33 39 53 58 63 75 83 89 4 8 18 23 27 39 45 50 56 62 70 min min min min min min min min min min min min Table 7. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.9 Battery 540W 540W 540W 540W 540W 540W Qty 1x36 1x38 1x40 2x36 2x38 2x40 40kVA 50kVA 60kVA 80kVA 100kVA 120kVA 160kVA 200kVA 63 72 79 158 169 178 50 55 59 124 138 148 38 45 50 90 106 119 22 27 31 63 72 79 15 19 23 50 55 59 9 13 17 38 45 50 3 6 10 22 27 31 2 5 15 19 23 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 min min min min min min Page 4 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS Battery 540W 540W 540W 540W 540W 540W Qty 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 50kVA 60kVA 80kVA 100kVA 120kVA 160kVA 200kVA 251 271 290 352 394 434 184 209 231 268 287 312 158 169 178 217 240 261 113 127 139 158 169 178 81 88 100 124 138 148 63 72 79 90 106 119 46 51 56 63 72 79 31 38 43 50 55 59 min min min min min min 160kVA 8 11 13 17 19 22 25 29 32 200kVA 7 9 12 14 16 18 21 24 min min min min min min min min min min min min 160kVA 7 9 200kVA 6 min min min min min The battery backup table is given with end voltage according to Table 1 and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles. Note! The specifications are subject to change without a notice. FIAMM 12FLB250 Table 8. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.8 Battery 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 Qty 1x36 1x38 1x40 2x36 2x38 2x40 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 25 29 32 61 69 76 102 113 121 153 165 174 50kVA 18 21 24 45 52 57 78 85 90 112 121 134 60kVA 14 17 19 37 42 44 61 69 76 87 96 106 80kVA 8 11 13 25 29 32 42 47 52 61 69 76 100kVA 7 9 18 21 24 32 37 40 45 52 57 120kVA 7 14 17 19 25 29 32 37 42 44 Table 9. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.9 Battery 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 Qty 1x36 1x38 1x40 2x36 2x38 40kVA 21 24 27 53 59 50kVA 15 18 20 40 44 60kVA 11 14 16 31 36 80kVA 7 9 11 21 24 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 100kVA 6 8 15 18 120kVA 11 14 Page 5 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS 12FLB250 Battery 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 12FLB250 2x40 Qty 3x36 3x38 3x40 4x36 4x38 4x40 65 40kVA 87 96 106 130 143 154 48 50kVA 67 75 81 94 105 114 40 60kVA 53 59 65 77 84 89 27 80kVA 37 42 44 53 59 65 20 100kVA 27 31 35 40 44 48 16 120kVA 21 24 27 31 36 40 11 160kVA 14 17 19 21 24 27 8 200kVA 9 12 14 15 18 20 min min min min min min min The battery backup table is given with end voltage according to Table 1 and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles. Note! The specifications are subject to change without a notice FIAMM 12FLB350 Table 10. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.8 Battery 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 Qty 1x36 1x38 1x40 2x36 2x38 2x40 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 40 45 52 93 104 112 154 165 174 206 223 236 50kVA 29 35 40 75 81 87 117 129 140 163 174 184 60kVA 22 27 31 59 66 73 93 104 112 134 147 157 80kVA 14 18 21 40 45 52 69 76 82 93 104 112 100kVA 9 13 16 29 35 40 51 57 64 75 81 87 120kVA 6 9 12 22 27 31 40 45 52 59 66 73 160kVA 4 7 14 18 21 26 31 37 40 45 52 200kVA 4 9 13 16 19 23 27 29 35 40 min min min min min min min min min min min min 160kVA 2 5 11 15 200kVA 2 7 10 min min min min min Table 11. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.9 Battery 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 Qty 1x36 1x38 1x40 2x36 2x38 40kVA 34 40 44 83 89 50kVA 24 29 34 65 72 60kVA 19 23 27 50 57 80kVA 11 15 18 34 40 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 100kVA 7 10 13 24 29 120kVA 3 7 10 19 23 Page 6 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS 12FLB350 Battery 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 12FLB350 2x40 Qty 3x36 3x38 3x40 4x36 4x38 4x40 98 40kVA 134 147 157 178 195 210 78 50kVA 102 112 120 145 157 166 63 60kVA 83 89 98 115 127 138 44 80kVA 59 66 73 83 89 98 34 100kVA 43 50 56 65 72 78 27 120kVA 34 40 44 50 57 63 18 160kVA 22 27 31 34 40 44 13 200kVA 16 20 23 24 29 34 min min min min min min min The battery backup table is given with end voltage according to Table 1 and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles. Note! The specifications are subject to change without a notice FIAMM 12FLB400 Table 12. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.8 Battery 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 Qty 1x36 1x38 1x40 2x36 2x38 2x40 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 45 54 58 107 117 127 169 179 195 231 248 268 50kVA 34 42 44 83 89 98 134 147 157 178 195 210 60kVA 26 31 36 68 75 81 107 117 127 152 163 172 80kVA 17 21 17 45 54 58 78 84 90 107 117 127 100kVA 11 15 16 34 42 44 59 66 73 83 89 98 120kVA 8 11 14 26 31 36 45 54 58 68 75 81 160kVA 6 9 17 21 17 30 38 41 45 54 58 200kVA 5 11 15 16 22 27 31 34 42 44 min min min min min min min min min min min min 160kVA 7 14 18 200kVA 9 13 min min min min min Table 13. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.9 Battery 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 Qty 1x36 1x38 1x40 2x36 2x38 40kVA 40 48 51 91 102 50kVA 28 35 39 74 80 60kVA 22 26 30 58 65 80kVA 14 18 16 40 48 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 100kVA 9 13 15 28 35 120kVA 5 9 12 22 26 Page 7 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS 12FLB400 Battery 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 12FLB400 2x40 Qty 3x36 3x38 3x40 4x36 4x38 4x40 111 40kVA 152 163 172 203 220 233 86 50kVA 115 126 138 162 172 181 72 60kVA 91 102 111 132 145 155 51 80kVA 68 75 81 91 102 111 39 100kVA 50 57 63 74 80 86 30 120kVA 40 48 51 58 65 72 16 160kVA 26 31 36 40 48 51 15 200kVA 19 23 27 28 35 39 min min min min min min min The battery backup table is given with end voltage according to Table 1 and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles. Note! The specifications are subject to change without a notice FIAMM 12FLB540 Table 14. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.8 Battery 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 Qty 1x36 1x38 1x40 2x36 2x38 2x40 3x36 3x38 3x40 4x36 4x38 4x40 40kVA 67 89 81 154 167 177 238 261 280 338 362 393 50kVA 50 88 62 115 127 141 183 204 218 260 281 299 60kVA 39 45 51 91 102 111 154 167 177 211 228 242 80kVA 24 30 36 67 89 81 107 117 128 154 167 177 100kVA 16 21 26 50 88 62 83 90 98 115 127 141 120kVA 10 15 19 39 45 51 67 89 81 91 102 111 160kVA 8 12 24 30 36 45 88 58 67 89 81 200kVA 8 16 21 26 33 40 44 50 88 62 min min min min min min min min min min min min 160kVA 6 9 19 25 200kVA 5 12 17 min min min min min Table 15. External battery back-up table for UPS load rating of 40-200 kVA with p.f. 0.9 Battery 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 Qty 1x36 1x38 1x40 2x36 2x38 40kVA 57 89 71 133 147 50kVA 43 87 55 100 110 60kVA 32 39 44 82 90 80kVA 19 25 30 57 89 Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 100kVA 12 17 22 43 87 120kVA 8 12 16 32 39 Page 8 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS 12FLB540 Battery 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 12FLB540 2x40 Qty 3x36 3x38 3x40 4x36 4x38 4x40 159 40kVA 211 228 242 293 317 339 119 50kVA 164 177 190 226 242 263 96 60kVA 133 147 159 180 201 216 71 80kVA 91 102 111 133 147 159 55 100kVA 73 89 86 100 110 119 44 120kVA 57 89 71 82 90 96 30 160kVA 39 45 51 57 89 71 22 200kVA 27 33 39 43 87 55 min min min min min min min The battery backup table is given with end voltage according to Table 1 and temperature +25°C. The batteries are fully charged and measured after min. (5) full discharge cycles. Note! The specifications are subject to change without a notice Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 Page 9 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS Large battery cabinet specifications Table 16. Eaton 93P/E and 93-BAT Large battery cabinet specifications Cabinet (P/N) Breaker Batteries Blocks1 Used with P-105000035-001 400 A EMPTY; M6 cables For 36, 38 or 40 93E 80-120kVA P-105000035-002 400 A EMPTY; M8 cables For 36, 38 or 40 93E 80-120kVA P-105000036-001 500 A EMPTY; M6 cables For 36, 38 or 40 93E 120-160kVA P-105000036-002 500 A EMPTY; M8 cables For 36, 38 or 40 93E 120-160kVA P-105000037-001 700 A EMPTY; M6 cables For 36, 38 or 40 93E 160-200kVA P-105000037-002 700 A EMPTY; M8 cables For 36, 38 or 40 93E 160-200kVA P-105000038-001 400 A CSB HRL 12 280W 40 93E 80-120kVA P-105000038-002 400 A CSB HRL 12 330W 40 93E 80-120kVA P-105000038-003 400 A CSB HRL 12 500W 40 93E 80-120kVA P-105000039-001 700 A CSB HRL 12 280W 40 93E 160-200kVA P-105000039-002 700 A CSB HRL 12 330W 40 93E 160-200kVA P-105000039-003 700 A CSB HRL 12 500W 40 93E 160-200kVA P-105000039-003 700 A CSB HRL 12 500W 40 93E 160-200kVA 1 Amount of battery blocks that are provided with the cabinet or can be installed in the battery cabinet (if empty). Figure 1. 93P/E Large battery cabinet. Dimensions are in millimetres. Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 Page 10 of 11 Runtime Charts Eaton 93E 80-200 kVA UPS Figure 2. 93-BAT Large Battery Cabinet. Dimensions are in millimetres. Author: Kärkkäinen, Joel Updated: 07.04.2016 Document: Eaton 93E Runtime Chart for L-EBC RevC3 Page 11 of 11