File In/With: – Service Information Equipment Affected: SI0487 New 1121 YVAA, YVFA, YVAM EBMPapst Variable Speed Fan Troubleshooting Guide OVERVIEW This Service Information Letter is to provide information on the troubleshooting of the EBMPapst Variable Speed Fan. The motors used with these fans have electronics built into the motor so standard motor troubleshooting procedures may not apply. CAUTION: Do not attempt to megger the motor. The motor contains electronic components. Attempting to megger these motors will damage the motor electronic components. PROCEDURES 1. Identify the motor(s) that are not functioning. 2. Verify that power is applied to the motors. a. It may be necessary to enable fan contactors through the chiller software depending on unit options (refer to appropriate service manual for fan wiring schematics). i. Ensure Unit Switch is in OFF (0) position. ii. Press SERVICE key. Type 9675 on keypad and press ENTER (Checkmark) key. iii. Use UP and DOWN arrow keys to scroll through service screens to the OUTPUT displays. iv. Use RIGHT or LEFT arrow keys to turn ON and OFF the condenser fan outputs and use UP or DOWN arrow keys to cycle through each condenser fan output. Turn ON “SYS1 COND FAN OUT 1” through “4” or “SYS2 COND FAN OUT 1” through “4” depending on which system you are testing. NOTE: Make sure to stay in service menu to keep outputs on. Leaving the service screen will turn outputs off. Service menu will time out after a period of time. May be necessary to repeat steps if outputs turn off. Work on this equipment should only be done by properly trained personnel who are qualified to work on this type of equipment. Failure to comply with this requirement could expose the worker, the equipment and the building and its inhabitants to the risk of injury or property damage. The instructions on this service information letter are written assuming the individual who will perform this work is a fully trained HVAC & R journeyman or equivalent, certified in refrigerant handling and recovery techniques, and knowledgeable with regard to electrical lock out/tag out procedures. The individual performing this work should be aware of and comply with all Johnson Controls, national, state and local safety and environmental regulations while carrying out this work. Before attempting to work on any equipment, the individual should be thoroughly familiar with the equipment by reading and understanding the associated service literature applicable to the equipment. If you do not have this literature, you may obtain it by contacting a Johnson Controls Service Office. Should there be any question concerning any aspect of the tasks outlined in this bulletin, please consult a Johnson Controls Service Office prior to attempting the work. Please be aware that this information may be time sensitive and that Johnson Controls reserves the right to revise this information at any time. Be certain you are working with the latest information. Product Technical Support SI0487 (1121) 3. Make sure fans are not spinning before inspecting motor. It may be necessary to manually force the fans speed to zero speed. a. YVAA/YVFA i. Ensure Unit Switch is in OFF (0) position. ii. Press SERVICE key. Type 9675 on keypad and press ENTER (Checkmark) key. iii. U se UP and DOWN arrow keys to scroll through screens till you find Analog signal for System 1 or System 2 (depending on what motors were replaced). Set output to 0% using keypad to type in percentage value and press ENTER key. NOTE: Make sure to stay in service menu to keep outputs on. Leaving the service screen will turn outputs off. Service menu will time out after a period of time. May be necessary to repeat steps if outputs turn off. b. YVAM i. Ensure Unit is ready to run. ii. On OptiView Home screen, press Condenser. iii. In the Condenser screen, press Fan Control. iv. Press Set and set the value to 0 using keypad. Press Checkmark to confirm. 4. Check for broken or bent blades, struts or guard grilles. Check for locked rotor conditions due to “rubbing” between the rotor and its surroundings or foreign objects. 5. Check the status and color of the LED that is visible through the terminal box cover on the top of the motor. a. If the LED is red or yellow, or blinking, proceed to tables in Step 6. b. If the LED is not lit, proceed to Step 8. LED fault light Figure 1 - TOP OF EBM EC MOTOR LDxxxxx 2 JOHNSON CONTROLS SI0487 (1121) 6. Check the tables below for the potential fault code of the motor based on the LED: Number of pulses Fault Code (Red LED color) Comments 1 Phase failure Automatic restart once phase failure is corrected 3 Power module overheated Power cycle required 4 Internal communications error between primary/secondary controller Primary = electronics, Secondary = motor. Power cycle required. 6 Motor overheated Power cycle required 7 Hall sensor error Power cycle required 8 Motor blocked Automatic restart after blockage is cleared 9 Speed limit exceeded Automatic restart 11 Rotor position sensor calibration error Power cycle required 13 DC-link undervoltage Automatic restart after undervoltage is cleared Number of pulses Fault Code (Yellow LED color) Comments 1 Current limitation in action Current limited to prevent damage of the electronics 2 Line impedance too high DC link voltage is instable 3 Power limiter in action Derating is active 4 Output stage temperature high Temperature > 105°C 5 Motor temperature high Temperature > 130°C 6 Temperature inside electronics high Temperature > 105°C 7 DC-link voltage low DC-link < 460V 8 Braking mode Error after 20s when motor start was not possible 9 Calibration of rotor position Calibration of rotor position sensor in progress 10 Actual speed is lower than run monitoring speed limit Only if set value > 0 11 Cable break at analog or PWM input for analog set value Check wiring NOTE: This fault code may be present if the command signal to the motor is 0%. Increase command signal to check if wiring issue. 13 DC-link voltage high DC-link > 850V 15 Line-voltage high U1_peak > 850VDC 16 Shedding function active Shedding function is active and fan is blocked 7. If any of the above fault codes cannot be cleared, replace fan assembly. 8. Deenergize unit and perform lockout/tagout procedures. Verify all power has been removed from unit. 9. Check input fuses to fan motors. Replace fuses if needed. 10. Disconnect wiring from fan motor. Wring out wires to verify no wiring shorts. Replace wiring as needed. 11. Use a standard multimeter to check resistance on motor input terminals L1, L2, L3 between each phase (L1 to L2, L2 to L3, L3 to L1). Resistance should be greater than 2 ohms. a. If resistance is less than 2 ohms during any check of motor terminals, replace fan assembly. b. If resistance is greater than 2 ohms and no wiring shorts are present, secure motor terminal box, remove lockout/tagout and apply power to motor. i. Check if LED is red or yellow, or blinking. See tables in Step 6 for fault codes. ii. If no faults are shown, verify motor is operational. iii. If LED is not lit and/or fuses continue to fail, or fan is not operational, replace fan assembly. JOHNSON CONTROLS 3