Compressor Failure Modes, Symptoms and Corrections A handy for analysis of a in. lure compressor, to aid in finding cause of failure take correction action. Replacement new or remanufactured 6 compressors fail I four times the rate of original compressors indicating replacement failures are caused by system problems. Liquid Slugging Broken reeds rods, or crankshaft. Loose or broken discharge bolts. Blown gaskets. Slugging is a a result of trying to compress liquid in the cylinders. Liquid may be either refrigerant or oil or more likely a combination of both. Slugging is a a result primarily of refrigerant migration into the oil on #he off cycle. Correction: 1. Check pump down cycle operation 2. Is TXV sized and operating properly. 3. Suction line sized properly? 4. Check unloading Liquid Washout Worn Pistons and/or rings. Cylinders worn. Scored pins. Scored and/or broken rods. Worn Bearings. Scored crankshaft. This is a mutt of refrigerant washing oil off surfaces. Off cycle migration of saturated refrigerant into crankcase. Compressor starts up resulting in a mass of foam which when pumped washes bearing surfaces of oil film necessary far proper lubrication. WASHOUT is a minor condition of SLUGGING. Correction: 1. Check TXV bulb and super heat setting. 2. Is TXV oversized? 3. Check crankcase header, (On during off cycle.) Liquid Dilution Rotor Drag. Worn bearings. Scored and/or broken rods. Scored Crankshaft. This is a result of liquid refrigerant returning to compressor during running cycle. Oil becomes diluted and lubrication for oil pump and end bearing my be adequate, but as it progresses down the crankshaft insufficient oil to lubricate the rods and main bearings will occur. Correction: 1. Check TAY bulb. 2. Clock superheat setting. 3. Check defrost cycle. High Discharge Temperature Discolored valve plate (Cannot rub off). overheated or burned valve reeds. Worn rings and patent. Worn cylinders. Scored rods, bearings, and crankshaft. Spot bum in stator. This is a a result of temperatures in the compressor head and cylinders becoming to hot that the oil lam its ability to lubricate. Correction: 1. High compression ration: check far law suction and high discharge pressures. Law load and evaporator problems. 2. Check low pressure control setting 3. Check for dirty condenser, inoperative condenser fan and ambient temperature. 4. Check air flow across compressor. Lack of Lubrication Scored bearings. Broken rods. Scored crankshaft. Low oil in crankcase. This is a a result of lock of enough oil in crankcase to properly lubricate the running gear. Correction: 1. Check oil failure witch. 2. Chock pipe sizing and also for oil traps 3. Inadequate defrost. 4. Law load. 5. Eliminate shad cycling. Electrical Many motors fail as a mutt of a mechanical or lubrication failure. Many foil due to malfunctioning external electrical components. General or Uniform Burn Entire winding is uniformly overheated or burned. Correction: 1. Check far low voltage. 2. Rapid cycling of compressor, 3. Loose terminal connection. 4. Unbalanced voltage. Single Phase Burn Two phases of a three phase motor am overheated or burned. A result of not having current through the unburned phase and overloading the other two phases. Correction: 1. Check contacts in starter and contact slide mechanism for binding. 2. Terminal connections on compressor. 3. Unbalanced voltage 4. Blown fuses. Half Winding Single Phase Burn This shows as when one hall of the motor has a single phasing condition on a PART WIND MOTOR with a two contactor system. Correction: 1. Chad both contactors as we will be defective. 2. Chad timer far proper time delay. Start Winding Burn Only the start winding is burned in a single phase motor due to excessive current flowing through the start winding. Correction: 1. Check C,S, and R, wiring. 2. Starting capacitor and/or start relay. 3. Compressor overloaded. Run Winding Burn Only the run winding is burned in a single phase motor. Correction: 1. Chock relay 2. Chock run capacitors Primary Single Phase Burn This will show as only one phase burned. Other two will be O.K. A result of losing we phase in the primary of a ฦ to Y or Y to ฦ transformer. Correction: 1. Check transformer far proper voltage incoming and outgoing. CORRECTIVE MEASURE TROUBLE POSSIBLE CAUSE High condensing pressure. Air or non-condensable gas in system. Purge air from condenser. Insufficient water or air flowing through condenser. Increase quantity of water or air. Evaporative condenser clogged or limed. Clean condenser water tubes. Too much liquid in receiver, Draw off liquid into condenser tubes submerged in liquid service cylinder. refrigerant. Low condensing pressure. High suction pressure. Low suction pressure. Too much water or air flowing through condenser. Reduce quantity of water or air. Condensing water too cold. Reduce quantity of water. Liquid refrigerant flooding back from evaporator. Check expansion device adjustment, examine fastening of thermal expansion valve bulb(s). Leaky compressor discharge valve(s). Remove heads, examine valves. Replace any found defective. Overfeeding of expansion device. Regulate expansion valve, check bulb attachment and superheat adjustment. Leaky suction or discharge valves. Remove head, examine valves and replace if worn. Malfunction of compressor capacity control system. Check capacity control system. Excess load. Reduce load to normal. Restricted liquid line, or suction, strainer screens. Pump down, remove restriction, examine and clean screens. Insufficient refrigerant in system. Check for refrigerant shortage. Too much oil in system. Remove oil. Improper adjustment of expansion valve(s) or liquid control devise(s). Adjust device(s) for proper superheat approximately 10°F. Expansion valve power element dead Replace expansion or weak. valve or power element. Compressor will not run. Electric power cut off Check power supply. Fuses blown. Test fuses and renew if necessary. Overload devices tripped. Check overload devices and find cause of overload. Low voltage. Check voltage (should be within 10% of nameplate rating). Trouble in starting witch or control circuit. Close switch manually to test power supply. If OK check control circuit including temperature and pressure controls and capacity control device. Seized compressor. Repair or rebuild compressor. Compressor runs Shortage of refrigerant. continuously with insufficient reduction of Individual cylinders not loading. load temperatures. Repair leak and recharge system. Check and correct pumping ability of individual cylinders replace suction and/or discharge valves and parts as needed. Check and correct capacity control system. Incorrect control switch settings. Compressor short Presence of air or foul gas. cycles or stops on high Insufficient water or air flowing pressure cutout. through condenser, clogged condenser. Reset control switches or replace. Purge condenser. Check -to, or air Flow. Check for scaled or fouled tubes in water cooled condenser. In evaporative type, check for fouled surfaces and insufficient air or spray water. In air cooled type, check for fouled surfaces, or lack I air flow. Compressor stops on Oil Failure Switch Plugged Oil Strainer. Excessive liquid repair in sump???? Clean oil strainer. Pump down observe level. See symptoms chart. IDENTIFYING COMPRESSOR FAILURES Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures. Back to Top REFRIGERANT FLOODBACK This is a result of liquid refrigerant returning to the compressor during the running cycle. The oil is diluted with refrigerant to the point it cannot properly lubricate the load bearing surfaces. Air Cooled Compressors Worn pistons and cylinders No evidence of overheating The liquid washed the oil off the pistons and cylinders during the suction stroke causing them to wear during the compression stroke. Refrigerant Cooled Compressors Center and rear bearings worn or seized Dragging rotor, shorted stator Progressively scored crankshaft Worn or broken rods The liquid dilutes the oil in the crankcase and the refrigerant rich oil will be pumped to the rods and the bearings through the crankshaft. As the refrigerant boils off, there will not be enough oil for sufficient lubrication at the bearings farthest from the oil pump. The center and rear bearings may seize or may wear enough to allow the rotor to drop and drag on the stator causing it to short. Correction: (1) Maintain proper evaporator and compressor superheat. (2) Correct abnormally low load conditions. (3) Install accumulators to stop uncontrolled liquid return. Back to Top FLOODED STARTS Worn or scored rods or bearings Rods broken from seizure Erratic wear pattern of crankshaft This is the result of refrigerant vapor migrating to the crankcase oil during the off cycle. When the compressor starts, the diluted oil cannot properly lubricate the crankshaft load-bearing surface causing an erratic wear or seizure pattern. Correction: (1) Locate compressor in warm ambient or install continuous pump down. (2) Check crankcase heater operation. Back to Top SLUGGING Broken reeds, rods, or crankshaft Loose or broken backer bolts Blown head gaskets This is the result of trying to compress liquid refrigerant and/or oil, in the cylinders. Slugging is an extreme floodback in air-cooled compressors and a severe flooded start on refrigerant cooled compressors. Correction: (1) Maintain proper evaporator and compressor superheat. (2) Correct abnormally low load conditions. (3) Install accumulators to stop uncontrolled liquid return. (4) Locate compressor in warm ambient or install continuous pump down. Back to Top HIGH DISCHARGE TEMPERATURE Discolored valve plate Burned valve reeds Worn pistons, rings and cylinders Stator spot burn from metal debris This is the result of temperatures in the compressor head and cylinders becoming so hot that the oil loses its ability to lubricate properly. This causes rings, pistons and cylinders to wear resulting in blow by, leaking valves, and metal debris in the oil. Correction: (1) Correct abnormally low load conditions. (2) Correct high discharge pressure conditions. (3) Insulate suction lines. (4) Provide proper compressor cooling. Back to Top LOSS OF OIL All rods and bearings worn or scored Crankshaft uniformly scored Rods broken from seizure Little or nor oil in crankcase This is a result of insufficient oil in the crankcase to properly lubricate the load bearing surfaces. When there is not enough refrigerant mass flow in the system to return oil to the compressor as fast at it is pumped out, there will be a uniform wearing or scoring of all load bearing surfaces. Correction: (1) Check oil failure control operation if applicable. (2) Check system refrigerant charge (3) Correct abnormally low load conditions or short cycling. (4) Check for incorrect pipe sizes and/or oil traps. (5) Check for inadequate defrosts. Back to Top ELECTRICAL While most motors fail as a result of mechanical failures, some are true electrical failures. GENERAL OR UNIFORM BURN All windings uniformly overheated or burned. Correction: (1) Check for proper voltage. (2) Check for unbalanced voltage. (3) Check for inadequate motor cooling. SINGLE PHASE BURN Two phases of a three phase motor overheated or burned as a result of the contactor opening only one of its contacts. Correction: (1) Replace contactors with properly sized contactors. (2) Check for proper motor protection. HALF WINDING SINGLE PHASE BURN In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact. Correction: (1) Replace contactors with properly sized contactors. Back to Top HALF WINDING BURN Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening. Correction: (1) Replace contactors with properly sized contactors. (2) Check for feed back circuit holding one contactor closed. PRIMARY SINGLE PHASE BURN Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer. Correction: (1) Check primary side of a delta to wye main power transformer. START WINDING BURN The start winding only of a single phase motor is uniformly overheated or burned. Correction: (1) Check for proper wiring of compressor. (2) Check starting capacitor and/or starting relay. (3) Correct compressor overloading. SPOT BURN A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow. SHORTED TERMINALS A break down of the insulation between terminals and compressor body generally the result of over torquing terminals. Reciprocating Compressor Failure Modes 1. The following mechanically related conditions account for approximately 80% of compressor failures. Flood Back: Liquid refrigerant returning to the compressor during the running cycle. Flooded Start: Crank case oil diluted with liquid refrigerant due to off cycle vapour migration. Liquid Slugging: Liquid refrigerant or excess amounts of oil entering the cylinders during the running cycle. Excessive Discharge Temperatures: Higher than design superheated discharge gas temperatures. Compressor Oil Loss: Quantity of oil returning from the system is less than that leaving the compressor. 2. The following electrically related conditions account for approximately 10% of compressor failures. Stator burn: Improper or unbalanced voltage and poor motor cooling. Single Phase Burn: Loss of one phase on a three phase system. Half Part Wind Burn: Loss of supply to one winding set on a two winding motor(Part wound). Loose Connections: Loose electrical joins causing a voltage drop. Starting Components: Damaged starting capacitors and relays. Inpure Power Supply: Spikes or surges of current flow. Shorted Power Terminals: Over torquing power terminals. Mechanical Failures Flood Back Liquid return during the running cycle. More commonly known as refrigerant flood back. The expansion valve plays a part in all the conditions here whether directly or indirectly this is obviously because the refrigerant can only really come this route. Read More! Top A flood back would cause any of these wear patterns or any combination. Firstly, air cooled compressors, where the gas goes directly into the cylinder head suction manifold, Liquid washes oil off cylinders and pistons during the suction stroke causing cool and dry wear during the discharge stroke resulting in: 1. Worn pistons. 2. Worn cylinders and rings. 3. Metal debris falling into the oil. Then with refrigerant cooled compressors where the gas first travels over the motor before rising to the suction manifold. Liquid cannot rise to the suction manifold and instead enters the crankcase to dilute the oil. This refrigerant rich oil is then pumped through the crankshaft evaporating and washing as it goes along reslting in: 1. Conrod/crankshaft wear which worsens furthest from the oil pump therefore: 2. Centre and rear bearings worn or seized. 3. Conrods possibly broken. 4. Motor end bearing wear is greatest causing the rotor to drop and drag on the stator shorting the windings. For both air cooled and refrigerant cooled compressors any wearing will be without signs of heating due to the cooling effect given by the vaporising refrigerant. There will therefore be no discoloration or carbonisation of the metal parts or oil. The white bearing metal would normally be smeared with a lumpy appearance on opposing surfaces. Top Flooded Start Crank case oil diluted with liquid refrigerant which has migrated from other parts of the system especially from saturated areas. The migration is usually by vapour during the off cycle. Read More! Top A flooded start would cause the following damage or any combination. It must be stressed that there will be no recognised wear pattern and this in itself is the signature of a flooded start. 1 Worn pistons and rings. 2 Worn or scored connecting rods or bearings. 3 Connecting rods broken from seizure. 4 Erratic wear pattern on the crankshaft. Any wearing will be without signs of heating due to the cooling action given by the vaporising refrigerant. There will therefore be no discoloration or carbonisation of the metal parts or oil. Lumps of white metal bearing would be smeared on opposing surfaces. Two common courses of action are taken to avoid migration and they are 1. heating the oil during the off-cycle or 2. Setting a pressure switch to run the compressor intermittently with the liquid line closed to maintain a safe low crankcase pressure, this is called a pump down and the principle here is that the lower the crankcase pressure the less refrigerant found in solution. Often a combination is applied where the compressor at the off-cycle will continue running until the crankcase pressure has dropped to a predetermined pressure, after which, the compressor is locked out only to recycle on load demand while then a crankcase heater acts to keep refrigerant from settling in the oil. Locking the compressor out protects it against short cycle damage should there be an unexpected cause of this such as leaky liquid line solenoid valves. Whichever methods are used it is extremely important that a compressor is not started under flooded conditions. However, neither of these methods work to protect the compressor if there has been a power interrupt. Top Slugging Top Liquid refrigerant or excess amounts of oil entering the cylinders during the running cycle is commonly called liquid slug. This is most often the result of flood back on air cooled compressors or flooded starts with refrigerant cooled compressors. Read More A liquid slug would cause the following damage or any combination. The liquid slug can be either liquid refrigerant or oil. With air cooled compressors slugging will take place during extreme flood backs. With refrigerant cooled compressors slugging is the result of a severe flooded start. 1 Broken discharge or suction valve reeds, connecting rods or crankshaft. 2 Loosened, thread stripped, or broken discharge valve backer bolts. 3 Blown valve plate and head gaskets with the loss of charge. Maintaining correct superheat is important here. Also look out for low loads, cool compressor ambients and migration control. Top High Superheated Discharge Temperatures Top Discharge gas temperatures or superheated discharge temperatures which are higher than designed for. This is high discharge gas superheat which is the result of high suction gas superheat and/or high compression ratios. The high compression ratios can be a result of abnormally high discharge pressures, abnormally low suction pressures or a combination. Read More! High discharge temperatures would cause the following damage or any combination. Cylinder and head temperatures become so hot that the oil loses the required viscosity for proper lubrication. Resulting ring wear causes discharge gases to blow past the rings and pressurise the crankcase preventing oil return from the system. Metal debris dropping to the crankcase will eventually cause stator spot burn when arriving between the rotor and stator. 1 Discoloured valve plate which can’t be rubbed clean. 2 Burned discharge valve reeds. 3 Burned and worn pistons, rings and cylinders. 4 Stator spot burn from metal debris. Look out for a high compression ratio i.e. low suction and high discharge conditions. Check the low and high pressure control settings. On low temp systems check for proper liquid injection or head cooling air flow. Also insulate the suction lines especially those that pass through warm zones. To reduce discharge superheat it may be necessary to reduce suction superheat. Check for or install discharge thermisters or Klixons. An example of a not so obvious fault here is a refrigerant cooled compressor which has been overcharged with oil. Refrigerant cooled compressors have higher suction and discharge superheats after cooling the motor especially with low temperature applications. The higher amperage resulting from the extra power required to churn the high level oil adds to total motor heat. A shortage of oil will also cause higher amps due to increased friction. Top Loss of Compressor Oil Top Quantity of oil returning from the system is less than that leaving the compressor. Since the very parts that compress the refrigerant vapour have to be lubricated an amount of oil always leaves the compressor with the refrigerant. We find conditions where oil leaving the compressor can increase also where oil returning is decreased. Read More! A loss of crankcase oil would cause the following damage or any combination. The most common causes of poor oil return is too low a mass flow in the suction line to sweep the oil back or improper design of suction line risers. 1 All rods and bearings worn or scored. 2 Crankshaft uniformly scored and heat discoloured. 3 Rods broken from seizure. 4 Look for little or no oil in the crankcase and much discolouring. Any wearing will be of scoring in character which is very different to the wearing caused by liquid washout. There will be much evidence of overheating i.e. staining of metal parts and carbonisation of the oil. Look for a resulting dirty oil strainer Check for the following:If applicable check the oil protection. 1. System refrigerant charge or lack of. 2. Correct abnormally low load conditions or short cycling. 3. Check for oversized suction pipes or lack of oil traps. 4. Check for inadequate defrosts otherwise known as oil harvests. Top Electrical Failures General or Uniform Stator Burn. Top Improper or unbalanced voltage, poor motor cooling or poor compressor high load limiting. Read More! Check for the following most common causes: Low running voltage due to over loading of the main circuit or loose connections anywhere from the main transformer to the compressor. V loss or IR drop: ( V loss=I×R ) where R would be line resistance plus the added resistance of any poor connections. 1. Unbalanced voltage due to unbalanced phase usage. 2. Over loading of the motor i.e. motor not sized for the suction density or pressure, usually the complete condensing unit would then be undersized resulting in higher discharge pressures too. check for maximum operating pressure controls. 3. Rapid cycling of the compressor meaning there is insufficient time for heat generated by the inrush current to dissipate. Top Single Phase Burn Top Loss of one phase on a three phase system. This condition is known as single phasing. Loss of voltage on one phase results in the loss of motor torque by the loss of that winding. The rotor then slips i.e. slows down effectively loosing back emf to the remaining windings which then draw more current tending to burn those windings unless protected. If the torque demand on the motor is high then it will stall and should have tripped the breaker easily. Check for the following causes: 1. Contact damage or sticky contactor sliding mechanism. 2. Voltage imbalance. 3. Improper electrical connections along that phase right back to the transformer. 4. Blown fuse. 5. Proper motor protection. Top One Half of a Part Wound Motor is Burnt Top Loss of supply to one winding set on a two winding motor (Part wound). Squirrel cage motors will draw approximately 6 times their running current on start up due to the initial absence of inductive reactance . If the building supply cables are undersized then a voltage drop throughout that building will occur every time the compressor starts due to this IR line voltage drop. There are numerous ways to reduce this effect. Star Delta starting will limit the peak starting current to approximately 2 times running current but the starting torque is limited to 1/3 of the norm. However, part wound motors will have a starting torque proportional to the relative size that the first half winding. Unless the compressor is much unloaded, the loss of power to one half of the total winding or one of the tandem windings will result in over working and thus overheating of the remaining half winding. Check for the following causes: 1. Faulty control circuit. 2. No interlocks. 3. Blown contactor. Top Loose Connections Top Loose electrical joins cause a drop in the supply voltage reaching the motor windings meaning extra current need be drawn to compensate in the attempt to maintain motor speed. This added I2R heat production in the motor windings will cause motor overheating. Top Start Winding Burn Top Damaged starting capacitors and relays on single phase motors. These components usually blow as a result of power problems or compressor short cycling. By my experience loss of refrigerant charge and the subsequent LP switch induced compressor short cycling is the biggest cause of failure to these components. When these components do blow the compressor will often burn the run winding. However, the run winding will also burn if the compressor is overloaded causing the starting relay to repeatedly call the start winding into circuit whilst the compressor is already running. Surprisingly common is the miss wiring of compressor motors often resulting in instantaneous nuisance motor damage by burning the start winding. Top Spot Burn Top Caused by spikes or surges of current flow or more likely system or compressor debris damage. Rapid changes in a buildings electrical load can be resistive or inductive. Especially with rapid changes in high inductive loads the result is normally a spike in the voltage allowing arcing to occur through winding points of weaker insulation. Damage to the compressor is usually in the form of a spot burn. A spot burn is a localised burn which can be within a winding, between windings or from winding to ground. Remember also that a localised spot burn can be caused by metal debris finding its way between the rotor and stator. Top Shorted Compressor Terminals Top Over torquing power terminals on the compressor can damage the fuseglass otherwise known as fusite insulation resulting in shorts occurring to the compressor motor body.