Caledonian Medium Voltage Cables
Company Profile
Caledonian develops, manufactures and markets a totally integrated product line of Medium Voltage
Cables for a diverse variety of technological applications.
The company offers an unrivalled experience and vast product range developed organically at the leading
edge of technology. It manufactures a variety of products, which include medium voltage power cables,
low voltage power and control cables, instrumentation cables, pilot cables, building wires & flexible cables.
It can also offer cables with special features like flame retardant properties, low smoke & halogen free
(LSZH) properties, cables with anti-termite treatment, UV resistant outer sheath, etc, being suitable for
different types of applications or environmental conditions.
Caledonian holds several important international approvals and manufactures its products in accordance
with relevant IEC, VDE, CENELEC and British Standard. The quality management system is accredited to
ISO 9001.
Caledonian has maintained an enviable growth record year on
year. The products manufactured by Caledonian are sold not
only in Europe by also beyond to Australia, China, Japan, South
Korea, Arab countries. They have been installed in variety of
applications including power plants, oil refineries, petroleum & gas
facilities, hospitals, hotels, airports etc.
This catalogue contains technical information on all medium
voltage cables including armoured and unarmoured designs,
single and multicore constructions and different sheathing and
screening options. All cable designs outlined in this section
follow the constructions covered by IEC 60502, BS 6622 and
VDE 0276. However, Caledonian can also supply a range of
alternative designs to meet specific customer needs including
different sheathing, screening, armouring and sheath color
options, together with enhanced fire performance, water sealing
of conductors and screens, and added environmental protection.
Cables can be made to individual customer specifications or other
recognized standards. These standards include ICEA S-66-524
WC 7, AS 1429, JIS C 3606, EDF HN 33-S-23, ASTM etc.
Table Of Contents
I
II
III
IV
V
Cable Properties & Construction
03
Cable Machinery & Equipments
05
Product Testing
06
Cable Options & Ordering Information
09
II
Medium Voltage Cables to BS 6622
Single Core Cables To BS 6622
Three Core Cables To BS 6622
12
~
30
III
Medium Voltage Cables to IEC 60502
Single Core Cables To IEC 60502
Three Core Cables To IEC 60502
31
~
59
IV
Medium Voltage Cables to VDE 0276
Single Core Cables To VDE 0276
Three Core Cables To VDE 0276
60
~
86
V
Technical Information
87
I
Caledonian
Medium Voltage
Cables
I
II
I
III
IV
Cable Properties & Construction
Cable Machinery & Equipments
Product Testing
Cable Options & Ordering Information
V
Cable Properties & Construction
▓▓ Cable Properties
Special features which we can offer for MV cables:
ÌÌ Ì Watertight construction (both radial and longitudinal).
ÌÌ Ì Lead sheath available for options.
ÌÌ Ì Resistant to heavy vibration.
ÌÌ Ì Available in long delivery lengths to reduce number of joints.
ÌÌ Ì Corrosion-free screen area.
ÌÌ Ì Copper or aluminum conductor up to 2000 mm².
ÌÌ Ì Metallic sheath and radial moisture barrier made of copper wire or tape.
ÌÌ Ì Different options for outer PE jackets (LDPE, MDPE & HDPE).
ÌÌ Ì Different options for LSF, LSOH & FRPVC, being anti-termite or UV resistant as per
BS 7835, IEC 60332 etc.
ÌÌ Ì Strippable insulation screen.
ÌÌ Ì Metallic screen made of multiple layers of copper tapes or a combination of copper
wires and tapes to increase the earth fault current carrying capacity.
ÌÌ Ì Increased armour conductivity by insertion of hard drawn copper wires in armour.
▓▓ Cable Construction
Caledonian medium voltage cables are manufactured using the monosil process. Caledonian
provides the highly specialized plant, state-of-the-art research facilities and meticulous quality
control procedures that are required for the manufacturing of PVC insulated cables for use up
to 6KV and XLPE/EPR insulated cables for use at voltages up to 42 KV. The materials are all
kept in cleanliness-controlled conditions throughout the production process in order to ensure
the absolute homogeneity of the finished insulation materials.
Conductors
Either aluminium or copper conductors are used. Conductors up to 800mm² will be circular,
compacted & stranded and shall comply with IEC 60228 class 2. 1000mm² conductor will be
circular stranded type on which a layer of semi-conducting tape will be applied.
Conductor Screen
This will be an extruded layer of semi-conducting crosslinkable compound applied under
simultaneous triple extrusion process over the conductor along with the insulation and the
insulation screen. The triple extrusion is a single high precision operation that eliminates the
possibility of any contamination between the layers which could create irregularities in the
electrical field. By careful material selection and special attention to process parameters,
Caledonian produces the insulation screen layers with the required degree of stripping force
as stipulated by the applicable national or international standard.
www.addison-cables.com
03
Caledonian Medium Voltage Cables
Insulation
This will be an extruded layer of XLPE or EPR applied over conductor screen under triple
extrusion process along with conductor screen and insulation screen. PVC may be used for
1.8/3KV and 3.6/6KV cables.
Insulation Screen
This will be a layer of semi-conducting crosslinkable compound which will be applied by triple
extrusion process over the insulation.
Metallic Screen
It will consist of a layer of copper tape applied helically with overlap over insulation screen.
Other combinations of metallic screens as per customer’s requirement can also be provided
on request.
Laying-Up
In case of three core cables, the three cores are laid up with non-hygroscopic fillers like
polypropylene(PP) fillers at interstices and a binder tape is applied with an overlap. These
binder tapes can be of PVC or foamed Polyethylene.
Inner Sheath (Bedding) for Armoured Cables
Extruded layer of PVC or PE is applied over the laid up cores for armoured cables. PVC is
normally of grade ST2 and PE of grade ST7 as per IEC 60502 Part 2.
Armouring
In case of armoured cables, the armour is applied helically over inner sheath. For single core
cables, it is of aluminium wires and for multicore cables, the armour can be of one among the
following options:
a) Galvanized steel wire.
b) Galvanized steel tape.
c) Galvanized steel strip.
Oversheath
An extruded layer is applied over the armour in case of armoured cables and over laid up
cores in case of unarmoured cables. Outer sheath material can be either PVC, PE, HDPE or
MDPE. Caledonian medium voltage cables are normally supplied with red PVC oversheaths
complying with BS 6622 or IEC 60502. Other colors may be provided to suit a range of
installation considerations such as the effect of UV radiations and differing soil compositions.
Anti-termite formulations can also be supplied in addition to graphite-coated oversheaths
where on-site testing of the sheath is required.
Fire Performance on Cable Sheaths
Cables can also be supplied with special flame retardant PVC oversheaths to comply
with the IEC 60332 standard. We can also supply cables with Low Smoke Halogen
Free (LSZH) sheaths according to BS 7211 and BS 6724 standards or other equivalent
Cable Properties & Construction
international standards.
▓▓ Cable Machinery & Equipments
The MV cable manufacturing facility at Caledonian is the most modern facility available
today with the state of the art machinery & equipments. The entire MV cables manufacturing
plant at Caledonian is fully air-conditioned with humidity control to ensure contamination free
atmosphere. The heart of MV cable manufacturing facility is the CCV line. This line supplied
by Troester, Germany and which incorporates some of the most modern features like,
-- Triple extrusion head to ensure superior quality of extrusion and uniform bonding of
conductor screen, XLPE insulation and the insulation screen.
-- CDCC – Completely dry curing & cooling in an inert atmosphere of nitrogen.
-- In line X-ray machine for checking proper concentricity as well as measuring thickness
of extruded materials.
-- Fully computerized auto-cure control system, which controls all driving parameters to
achieve best curing of extruded materials.
-- Fully automatic compound handling system in a positive pressure atmosphere ensuring
a contamination free line, which is absolutely essential to achieve superior quality
product.
Some of the other machines include:
-- Drawing machine from Niehoff, Germany
-- Cable stranding machine from Mali, Austria
-- Screening machine from Ceeco, Canada
-- Five drum cabling machine from Mali, Austria
-- Armouring machine from Ceeco, Canada
-- Extruder from Troester, Germany, etc.
With the manufacturing facilities incorporating the use of latest available technology, the MV
cables offered by Caledonian provides customers with a definite advantage in terms of:
-- Compete adherence to specifications,
-- Superior overall performance,
-- Minimum risk of insulation failures,
-- Longer service life,
-- Triple head extrusion.
www.addison-cables.com
05
Caledonian Medium Voltage Cables
▓▓ Product Testing
Caledonian has made major investment in the testing facilities for its MV cables factory. We
have equipped ourselves with the latest and most advanced cable testing facility available in
the world.
Our major testing facilities include:
a) DC withstand voltage test system from Hipotronics USA.
b) Partial discharge test system from Haefely, Switzerland.
c) HV test system from Haefely, Switzerland.
d) On line conductor resistance meter from Aesa, Switzerland
Effective quality assurance procedures are essential to ensure the consistency and long term
reliability and performance of all products. Caledonian always recognises the importance
of quality assurance and this commitment is reflected in the company achievement of ISO
9001 certification. The design validation for our MV Cables has been done at recognized
international laboratories.
With the above state of the art testing facility, we can conduct all type, routine as well as
special tests mentioned in IEC 60502 Part 2, BS 6622 & other international specifications, inhouse. While 100% of the cables are tested for routine tests prior to dispatch, however upon
customers’ request, other type/special tests can be carried out in house or by any third party
laboratory.
The tests can be divided into different categories:
Type Tests
The type test is conducted by KEMA, Netherlands to validate a special cable design type.
Electrical type tests include the following:
-- Partial discharge test (IEC 60502 clause 18.1.3)
-- Bending test (IEC 60502 clause18.1.4)
-- Sheath measurement (IEC 60502 clause 18.1.5)
-- Heating cycle test (IEC 60502 clause 18.1.6)
-- Impulse withstand test followed by a.c. voltage test (IEC 60502 18.1.7)
-- High voltage test for 4 hours (IEC 60502 clause 18.1.8)
-- Resistivity of semiconducting screens (IEC 60502 clause 18.1.9)
Nonelectrical type tests include the following:
-- All nonelectrical type tests as required by IEC 60502
Routine Tests
Routine tests are carried out on each finished length of cable to control the overall quality of
the cable. They comprise:
-- Measurement of dimensions.
-- Measurement of conductor resistance: the D.C. resistance of each conductor, when
corrected to 20°C and 1 Km, shall not exceed the appropriate maximum value specified
in IEC 60228 respectively.
Cable Properties & Construction
-- Measurement of screen resistance.
-- High voltage test: an a.c. voltage of 3.5 Uo shall be applied for 5 min between each
conductor and metallic screen. No breakdown shall occur.
-- Partial discharge test: the magnitude of discharge at 1.73 Uo shall not exceed 10pC.
-- Measurement of dielectric losses and capacity.
Special Tests
Special tests are carried out on 10% of the lengths for each production lot, in any case on
one length. They are carried out if major changes in design are introduced.
They comprise:
-- Measurement of dimensions
-- Checking sheath identification
-- Testing shrinkage of PE sheath
-- Conductor examination
-- Carrying out voltage test
-- Carrying out hot set test for XLPE insulation
At Caledonian, quality assurance is an integrated part of the production process and
maintained from order entry and manufacture through to testing, packaging and shipping. All
quality assurance procedures are regularly audited by recognised quality organisations and
all routine voltage testing is carried to more stringent levels than that required by international
standards.
Specification for testing is designed in accordance to the following international standards:
-- IEC 60502
-- IEC 60811
-- BS 5368
-- DIN 56283/VDE 0273
-- EDF HN 33S23
-- AS&JIS
-- ASTM
-- etc.
We have also installed many in line devices/facilities for checking the product quality
during the manufacturing process like the X-ray machine installed in the CCV line, curing
optimization software, etc, to avoid any risk or failure & to ensure a long service life for
our products. With these modern equipment & facilities, we ensure to maintain close
manufacturing tolerances, high accuracy to customer specifications as well as effective
monitoring of the entire manufacturing process to offer a world class product.
www.addison-cables.com
07
Caledonian Medium Voltage Cables
The following In-Process testing is conducted during the cable manufacturing :
ÌÌ Ì Tandem Line
ÌÌ Ì Visual and physical tests
ÌÌ Ì Electrical tests
ÌÌ Ì Resistance & resistance unbalance tests
ÌÌ Ì Open & short circuit test
ÌÌ Ì High Voltage Test
ÌÌ Ì Group twinner
ÌÌ Ì Visual & physical tests
ÌÌ Ì Electrical tests
ÌÌ Ì Resistance & resistance unbalance tests
ÌÌ Ì Mutual capacitance test
ÌÌ Ì Open & short circuit test
ÌÌ Ì Insulation resistance test
ÌÌ Ì Sheathing
ÌÌ Ì Dimensional test
ÌÌ Ì Water penetration test
ÌÌ Ì Spark test
ÌÌ Ì Overlaps & seal bonding inspection
ÌÌ Ì Armoring
ÌÌ Ì Dimensional test
ÌÌ Ì Visual inspection
ÌÌ Ì Jacketing
ÌÌ Ì Dimensional test
ÌÌ Ì Overlap inspection
ÌÌ Ì Spark test
ÌÌ Ì Final Testing
ÌÌ Ì Routine testing
ÌÌ Ì Resistance & resistance unbalance tests
ÌÌ Ì Mutual capacitance test
ÌÌ Ì Transmission test
ÌÌ Ì Capacitance & capacitance unbalance tests ( pair to pair and pair to ground )
ÌÌ Ì Attenuation & cross talk tests.
Cable Properties & Construction
▓▓ Cable Options
It is essential that the type of cable ordered is suitable for its intended use. Cable choice
will be based on a whole range of factors including installation requirements, relevant local
regulations and the electrical characteristics of appropriate cable types. The factors to be
considered are:
ÌÌ Ì Nominal voltage of system.
ÌÌ Ì Highest voltage of system.
ÌÌ Ì Impulse withstand voltage.
ÌÌ Ì System frequency.
ÌÌ Ì Maximum rated current.
ÌÌ Ì For continous operation.
-- For cyclic operation ( a load curve is essential )
-- For overload operation, if any ( duration is essential )
ÌÌ Ì Symmetrical and asymmetrical short circuit current , both between pulses and to earth.
ÌÌ Ì Duration of fault in second.
ÌÌ Ì Required screen bonding scheme
-- Both ends bonded
-- Single point bonded
-- Cross bonded
▓▓ Ordering Informations
VDE CODE: ABCDEFGH
A. Conductor
N- Standard construction in accordance to VDE standard (copper conductor)
NA- Aluminium conductor
NFA- Standard construction for twisted cable (aluminium conductor)
B. Insulation Material
Y- PVC
2X- XLPE
3G- EPR
C. Concentric Conductor Shielding Material
C- Concentric conductors of copper wires and copper tape, helically wounded
CW- Concentric conductors of copper wires in waveconal formation and and copper tape,
helically wounded
CE- Concentric conductors of copper wires and copper tape over each individual conductor,
helically wounded
Blank- No screen
www.addison-cables.com
09
Caledonian Medium Voltage Cables
D.Shielding Material
S- Shielding of copper wires and copper tape, helically wounded
SE- Shielding of copper wires and copper tape over each individual conductor, helically
wounded
(F)- Longitudinally water proof shielding
Blank- No screen
E. Bedding Material
2Y- PE
Y- PVC
H- LSZH
K- Lead sheath
Blank- No bedding
F. Armoring Material
B- Double steel tape armouring
R- Round steel wire armouring
F- Flat steel wire armouring
Gb- Steel tape armouring
Blank- No armour
G. Jacket Material
2Y- PE
Y- PVC
H- LSZH
K- Lead sheath
H. Cable Types
J- Cables with green-yellow conductor are marked with protective conductor
O- Cables without green-yellow conductor are marked without protective conductor
Caledonian Order Code
MVA-BCDEFGH-IJ
A Cable Design Standard
6622- BS6622 standard
502- IEC60502 standard
276- VDE0276 standard
B Conductor
A- Aluminium conductor
Blank- Copper conductor
Cable Properties & Construction
C Insulation Material
Y- PVC
2X-XLPE
3G-EPR
D Concentric Conductor Shielding Material
C- Concentric conductors of copper wires and copper tape, helically wounded
CW- Concentric conductors of copper wires in waveconal formation and and copper tape,
helically wounded
CE- Concentric conductors of copper wires and copper tape over each individual conductor,
helically wounded
Blank- No screen
E Shielding Material
S- Shielding of copper wires and copper tape, helically wounded
SE- Shielding of copper wires and copper tape over each individual conductor, helically
wounded
(F)- Longitudinally water proof shielding
Blank- No screen
F Bedding Material
2Y- PE
Y- PVC
H- LSZH
K- Lead sheath
Blank- No bedding
G Armoring Material
B- Double steel tape armouring
R- Round steel wire armouring
F- Flat steel wire armouring
Gb- Steel tape armouring
Blank- No armour
H Jacket Material
2Y- PE
Y- PVC
H- LSZH
K- Lead Sheath
I No of Cores
3C- 3 Cores
J Conductor Size
185- 185 mm sq
8A- 8AWG
www.addison-cables.com
11
Caledonian
Medium Voltage
Cables
I
II
II
III
IV
Medium Voltage Cables to BS 6622
Single Core Cables To BS 6622
Three Core Cables To BS 6622
V
Medium Voltage Cables to BS 6622
Single Core Cables to BS 6622
▓▓ APPLICATIONS:
The single core cables are designed for distribution
of electrical power with nominal voltage Uo/U
ranging from 3.8/6.6KV to 19/33KV and frequency
50Hz. They are suitable for installation mostly
in power supply stations, indoors and in cable
ducts, outdoors, underground and in water as well
as for installation on cable trays for industries,
switchboards and power stations.
▓▓ STANDARD:
PVC/PE/LSZH Oversheath
Aluminium Wire Armour (optional)
Binder
XLPE/EPR Insulation Screen
Conductor
Conductor Screen
Insulation Screen
Metallic Screen
PVC/PE/LSZH Separation Sheath (optional)
BS 6622
BS 7835 (LSZH)
▓▓ CONSTRUCTION:
Conductor: Plain annealed copper or aluminium complying with IEC 60228/BS 6360. Copper
conductors shall be stranded (class 2) and aluminium conductors shall be either solid or
stranded (class 2).
Conductor Screen: Extruded layer of semi-conducting cross-linkable compound is applied
over the conductor and shall cover the surface completely. The minimum thickness is 0.3mm
and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
Insulation: Insulation is of cross-linked polyethylene compound XLPE (GP8) conforming to
BS 7655-1.3 or EPR (GP7), conforming to BS 7655-1.2.
Table 1. Insulation Thickness
Insulation Thickness at Nominal Voltage
Nom. Cross
Section Area 3.8/6.6KV (Um=7.2KV) 6.35/11KV (Um=12KV) 8.7/15KV(Um=17.5KV) 12.7/22KV(Um=24KV)
19/33KV(Um=36KV)
mm²
mm
mm
mm
mm
mm
70 – 185
2.5
3.4
4.5
5.5
8.0
240
2.6
3.4
4.5
5.5
8.0
300
2.8
3.4
4.5
5.5
8.0
400
3.0
3.4
4.5
5.5
8.0
Above 500
3.2
3.4
4.5
5.5
8.0
www.addison-cables.com
13
Caledonian Medium Voltage Cables
Insulaton Screen: Extruded layer of semi-conducting cross-linkable compound is applied
over the insulation. The extruded semi-conducting layer shall consist of bonded or cold
strippable semi-conducting compound capable of removal for jointing or terminating. As an
option, a semi- conducting tape may be applied over the extruded semi-conducting layer as a
bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity
is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and
can be easily hand stripped on site.
Metallic Layer: The metallic layer shall consist of either copper tapes or a concentric layer
of copper wires or a combination of tapes and wires. The metallic layer provides an earth
fault current path, capable of withstanding fault current to earth of 1000A for one second at
maximum temperature 160°C. Copper wires are applied over the conducting water blocking
layer with a minimum diameter of 0.5mm. And over the copper wires, copper tape with
minimum thickness of 0.1mm can be applied helically with overlap. Total cross section of
copper wire screen layer is shown in table 2.
Table 2. Minimum Total Cross Section of Copper Wire Screen & DC Resistance of the screen
Nominal Cross-Section
of Cables
Minimum Cross-Section
of Copper Wire Screen
DC Resistance of the Copper Wire Screen
at 20°C
mm²
mm²
Ω
up to 120
16
1.06
150-300
25
0.72
400-630
35
0.51
Separation Sheath (for armoured cable): The separation sheath comprises a layer of
extruded PVC, PE or LSZH. The nominal thickness is calculated by 0.02Du + 0.6mm where
Du is the fictitious diameter under the sheath in mm. The nominal separation sheath thickness
shall not be less than 1.2mm.
Armour (for armoured cable): The armour consists of round aluminium wire with diameter
specified as in Table 3.
Table 3. Armour Wire Diameter
Fictitious Diameter Under the Armour
Armour Wire Diameter
mm
mm
>
<
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15
Over Sheath: Overall sheath comprises a layer of extruded either PVC type 9 conforming
to BS 7665-4.2 or MDPE type TS2 conforming to BS 7655-10.1. LSZH can be offered as an
option. The oversheath is normally black in colour. When a DC voltage test is to be performed
on the oversheath, a semi-conducting layer such as graphite coating shall be applied over
the surface of the extruded oversheath. The nominal oversheath thickness is calculated
Medium Voltage Cables to BS 6622
by 0.035+D where D is the diameter immediately under the oversheath in mm. For cables
with the oversheath not applied over the armour, the nominal oversheath thickness shall not
be less than 1.4mm. And for cables with oversheath applied over the armour, the nominal
oversheath thickness shall not be less than 1.8mm.
▓▓ PHYSICAL PROPERTIES:
Operating Temperature: up to 90°C
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds)
Bending Radius: 12 x OD
Table 4. Nominal /Operating /Test Voltages
Rated Voltage Uo/U
Operating Voltage (Um)
Testing Voltage (rms)
3.8/6.6KV
7.2KV
15KV
6.35/11KV
12KV
25.5KV
8.7/15KV
17.5KV
35KV
12.7/22KV
24KV
51KV
19/33KV
36KV
76KV
www.addison-cables.com
15
Caledonian Medium Voltage Cables
Single Core 3.8/6.6KV (Um=7.2KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossApprox.
Nom.
Approx.
Nom.
Section Insulation Wire
Weight
Sheath
Overall
Area Thickness Screen Thickness Diameter
Area
Cu
AL
mm²
mm
mm²
mm
mm
kg/km
Aluminium Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
Cu
mm²
kg / km
mm
mm
mm
mm
Approx.
Weight
AL
25
2.5
16
1.5
20.3
750
580
3.4
1.2
1.6
1.8
26.3
1150
1000
35
2.5
16
1.6
21.3
870
650
3.6
1.2
1.6
1.8
27.3
1250
1050
50
2.5
16
1.6
22.4
1090
770
3.9
1.2
1.6
1.8
28.4
1500
1190
70
2.5
16
1.7
24.2
1310
870
4.3
1.2
1.6
1.8
30.0
1740
1300
95
2.5
16
1.7
25.8
1560
960
4.7
1.2
1.6
1.9
31.8
2030
1430
120
2.5
16
1.8
27.4
1830 1070
5.0
1.2
1.6
1.9
33.2
2310
1550
150
2.5
25
1.8
29.1
2130
1190
5.3
1.2
1.6
2.0
35.1
2660
1720
185
2.5
25
1.9
30.8
2490 1320
5.8
1.2
2.0
2.0
37.4
3120
1950
240
2.6
25
1.9
33.5
3040 1520
6.3
1.2
2.0
2.1
40.3
3740
2200
300
2.8
25
2.0
36.1
3650 1770
7.0
1.2
2.0
2.2
42.9
4400
2520
400
3.0
35
2.2
40.6
4680 2170
7.7
1.2
2.0
2.3
47.2
5490
2960
500
3.2
35
2.3
43.6
5670 2570
8.5
1.3
2.5
2.5
51.6
6760
3660
630
3.2
35
2.4
48.8
6980 2990
9.5
1.4
2.5
2.6
57.0
8200
4160
Electrical Data
Aluminium
Unarmoured
Wire
Cables
Armoured
Cables
Nom.
Short
CrossReactance
Inductance
Impedance
Short
Circuit
Short Circuit
Section
Circuit
Rating of
Rating of
DC
AC
Area
Rating of Capaci- Charging
Copper Copper Tape
Resistance Resistance
Trefoil Flat Spaced
Conductor tance Current
Flat
Flat
Wire
Screen
CU / AL
CU / AL
Trefoil
Trefoil
CU / AL
spaced
Spaced
Screen
1 sec
1 sec
Cu AL Cu AL
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
µΩ/m nH/m
nH/m
µΩ/ m
µΩ/m
25
727/1200 927/1538
3.6/2.3
263
0.32
2.6
0.4
136
194
400
590
936 1544 952 1554
35
524/868
668/1113
5.0/3.2
291
0.35
2.6
0.5
127
185
390
580
679 1121 695 1131
50
387/641
494/822
6.8/4.4
321
0.39
2.6
0.5
121
179
380
570
511 834 527 844
70
268/443
343/568
9.8/6.3
371
0.45
2.6
0.6
115
173
370
550
364 583 386 597
95
193/320
248/410
13.3/8.5
417
0.50
2.6
0.6
110
168
350
540
272 427 300 446
120
153/253
196/325
17.2/11.0
459
0.55
2.6
0.7
107
165
340
520
225 345 257 367
150
124/206
159/265
21.2/13.5
494
0.59
4.3
0.7
103
161
330
510
193 287 229 313
185
99.1/164
128/211
26.6/17.0
543
0.65
4.3
0.8
100
158
320
500
165 237 206 267
240
75.4/125
98/161
34.9/22.3
583
0.70
4.3
0.9
97
155
310
490
140 191 185 226
300
60.1/100
80/130
43.8/28.0
602
0.72
4.3
1.0
95
153
300
490
126 163 174 203
400
47.0/77.8
64/102
57.3/36.6
627
0.75
5.8
1.1
92
150
290
480
113 141 164 184
500
36.6/60.5
51/81
72.3/46.2
654
0.79
5.8
1.2
90
149
290
470
105 124 158 171
630
28.3/46.9
42/64
91.2/58.3
726
0.87
5.8
1.3
87
145
280
460
97
110 151 160
Medium Voltage Cables to BS 6622
Single Core 6.35/11KV (Um=12KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossApprox.
Nom.
Approx.
Nom.
Section Insulation Wire
Weight
Sheath
Overall
Area Thickness Screen Thickness Diameter
Area
Cu
AL
mm²
mm
mm²
mm
mm
kg/km
25
3.4
16
1.5
22.1
960
740
Aluminium Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
mm²
mm
mm
mm
mm
3.8
1.2
1.6
1.8
28.1
Approx.
Weight
Cu
AL
kg/km
1300
780
35
3.4
16
1.6
23.3
1060
790
4.1
1.2
1.6
1.8
29.1
1400 1180
50
3.4
16
1.7
24.4
1160
840
4.4
1.2
1.6
1.8
30.2
1600 1280
70
3.4
16
1.7
26.0
1370
930
4.7
1.2
1.6
1.9
32.0
1840 1400
95
3.4
16
1.8
27.8
1640 1040
5.2
1.2
1.6
1.9
33.6
2130 1530
120
3.4
16
1.8
29.2
1900
1140
5.5
1.2
1.6
2.0
35.2
2430 1670
150
3.4
25
1.9
31.1
2220 1280
5.8
1.2
1.6
2.1
37.9
2870 1930
185
3.4
25
1.9
32.6
2570 1410
6.2
1.2
2.0
2.1
39.4
3240 2080
240
3.4
25
2.0
35.3
3130 1610
6.8
1.2
2.0
2.2
42.1
3490 2330
300
3.4
25
2.1
37.5
3730 1850
7.3
1.2
2.0
2.2
44.1
4490 2560
400
3.4
35
2.2
41.4
4730 2200
8.0
1.2
2.0
2.4
48.2
5589 3040
500
3.4
35
2.3
44.0
5700 2600
8.6
1.3
2.5
2.5
52.0
6780 3680
630
3.4
35
2.4
49.2
7010 3020
9.5
1.4
2.5
2.6
57.4
8230 4200
Electrical Data
Aluminium
Unarmoured
Wire
Cables
Armoured
Cables
Nom.
Short
CrossReactance
Inductance
Impedance
Short
Short Circuit Circuit
Section
Circuit
DC
AC
Charging Rating of Rating of
Area
Rating of CapaciResistance Resistance
Current
Copper
Copper
Trefoil Flat Spaced
Conductor tance
Flat
Flat
CU / AL
CU / AL
Wire Screen
Tape
Trefoil
Trefoil
CU / AL
Spaced
Spaced
1 sec
Screen
1 sec
Cu AL Cu AL
1 sec
mm²
25
µΩ/m
µΩ/m
727/1200 927/1538
kA
pF/m
mA/m
kA
kA
µΩ/m
µΩ/m
nH/m
nH/m
µΩ/m
µΩ/m
3.6/2.3
208
0.42
2.6
0.5
146
206
440
640
936 1544 952 1554
35
524/868
668/1113
5.0/3.2
229
0.46
2.6
0.6
138
201
440
640
679 1121 695 1131
50
387/641
494/822
6.8/4.4
252
0.50
2.6
0.6
132
195
420
620
511 834 527 844
70
268/443
343/568
9.8/6.3
288
0.58
2.6
0.7
122
188
390
600
364 583 386 597
95
193/320
248/410
13.3/8.5
323
0.65
2.6
0.7
122
182
390
580
272 427 300 446
120
153/253
196//325 17.2/11.0
353
0.71
2.6
0.8
116
172
370
550
225 345 257 367
150
124/206
159/265
21.2/13.5
380
0.76
4.3
0.8
110
166
350
530
193 287 229 313
185
99.1/164
128/211
26.6/17.0
416
0.83
4.3
0.9
107
166
340
530
165 237 206 267
240
75.4/125
98/161
34.9/22.3
460
0.92
4.3
0.9
104
163
330
520
140 191 185 226
300
60.1/100
80/130
43.8/28.0
506
1.01
4.3
1.0
100
157
320
500
126 163 174 203
400
47/77.8
64/102
57.3/36.6
561
1.12
5.8
1.1
94
154
300
490
113 141 164 184
500
36.6/60.5
51/81
72.3/46.2
619
1.24
5.8
1.2
91
151
290
480
105 124 158 171
630
28.3/46.9
42/64
91.2/58.3
698
1.37
5.8
1.3
91
148
290
470
97
110 151 160
www.addison-cables.com
17
Caledonian Medium Voltage Cables
Single Core 8.7/15KV (Um=17.5kV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossNom.
Approx. Approx.
Nom.
Weight
Section Insulation Wire
Sheath
Overall
Area Thickness Screen Thickness Diameter
CU AL
Area
mm²
mm
mm²
mm
mm
25
4.5
16
1.6
23.7
940
35
4.5
16
1.7
24.9
Aluminium Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
kg/km
Approx.
Weight
CU
AL
mm²
mm
mm
mm
mm
kg/km
820
4.4
1.2
1.6
1.8
30.3
1430
1210
1140 870
4.7
1.2
1.6
1.9
31.5
1630
1310
50
4.5
16
1.7
26.6
1240 920
4.9
1.2
1.6
1.9
32.6
1730
1410
70
4.5
16
1.8
28.4
1470 1030
5.3
1.2
1.6
1.9
34.2
1970
1520
95
4.5
16
1.9
30.2
1750 1160
5.7
1.2
2.0
2.0
36.8
2370
1770
120
4.5
16
1.9
31.6
2100 1250
6.1
1.2
2.0
2.1
38.4
2670
1910
150
4.5
25
2.0
33.5
2340 1400
6.4
1.2
2.0
2.1
40.1
3020
2080
185
4.5
25
2.0
35.0
2690 1520
6.8
1.2
2.0
2.2
41.8
3420
2240
240
4.5
25
2.1
36.8
3270 1740
7.4
1.2
2.0
2.3
44.5
4050
2500
300
4.5
25
2.2
39.9
3870 1990
7.9
1.2
2.0
2.3
46.5
4680
2780
400
4.5
35
2.3
43.8
4890 2370
8.5
1.3
2.5
2.5
51.8
5970
3430
500
4.5
35
2.4
46.4
5860 2760
9.2
1.3
2.5
2.6
54.4
7010
3910
630
4.5
35
2.5
51.6
7190 3190
10.0
1.4
2.5
2.7
59.8
8480
4420
Electrical Data
Aluminium
Unarmoured
Wire
Cables
Armoured
Cables
Nom.
Short
CrossReactance
Inductance
Impedance
Short
Short
Circuit
Section
Circuit
Circuit
CapacDC
AC
Rating of
Area
Rating of
Charging Rating of
itance
Resistance Resistance
Copper
Trefoil Flat Spaced
Conductor
Current Copper Wire
Flat
Flat
CU / AL
CU / AL
Tape
Trefoil
Trefoil
CU / AL
Screen
Spaced
Spaced
Screen
1 sec
1 sec
CU AL CU AL
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
µΩ/m
nH/m
nH/m
µΩ/m
µΩ/m
25
727/1200 927/1538
3.6/2.3
171
0.47
2.6
0.6
154
217
480
680
936 1544 952 1554
35
524/868
668/1113
5.0/3.2
187
0.51
2.6
0.6
145
208
460
660
679 1121 695 1131
50
387/641
494/822
6.8/4.4
204
0.56
2.6
0.7
138
201
440
640
511
834
527
844
70
268/443
343/568
9.8/6.3
232
0.63
2.6
0.7
132
188
420
600
364
583
386
597
95
193/320
248/410
13.3/8.5
258
0.70
2.6
0.8
126
182
400
580
272
427
300
446
120
153/253
196/325
17.2/11.0
281
0.77
2.6
0.8
119
179
380
570
225
345
257
367
150
124/206
159/265
21.2/13.5
301
0.82
4.3
0.9
113
176
360
560
193
287
229
313
185
99.1/164
128/211
26.6/17.0
329
0.90
4.3
0.9
110
170
350
540
165
237
206
267
240
75.4/125
98/161
34.9/22.3
363
0.99
4.3
1.0
107
166
340
530
140
191
185
226
300
60.1/100
80/130
43.8/28.0
398
1.09
4.3
1.1
104
160
330
510
126
163
174
203
400
47/77.8
64/102
57.3/36.6
439
1.20
5.8
1.2
97
157
310
500
113
141
164
184
500
36.6/60.5
51/81
72.3/46.2
483
1.32
5.8
1.3
94
154
300
490
105
124
158
171
630
28.3/46.9
42/64
91.2/58.3
534
1.46
5.8
1.4
91
151
290
480
97
110
151
160
Medium Voltage Cables to BS 6622
Single Core 12.7/22KV (Um=24kV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossApprox.
Nom.
Approx.
Nom.
Section Insulation Wire
Weight
Sheath Overall
Area Thickness Screen Thickness Diameter
Area
CU
AL
mm²
mm
mm²
mm
mm
35
5.5
16
1.7
27.4
Aluminium Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
kg/km
1100
800
mm²
mm
mm
mm
mm
5.2
1.2
1.6
1.9
31.4
Approx.
Weight
CU
AL
kg/km
1400
1200
50
5.5
16
1.8
28.8
1330
1010
5.4
1.2
1.6
2.0
34.8
1850
1540
70
5.5
16
1.9
30.6
1570
1130
5.9
1.2
2.0
2.0
37.2
2190
1750
95
5.5
16
1.9
32.2
1840
1240
6.2
1.2
2.0
2.1
39.0
2510
1900
120
5.5
16
2.0
33.8
2120
1360
6.6
1.2
2.0
2.1
40.4
2810
2040
150
5.5
25
2.0
35.5
2440
1500
6.9
1.2
2.0
2.2
42.3
3180
2240
185
5.5
25
2.1
37.2
2810
1640
7.4
1.2
2.0
2.2
43.8
3560
2380
240
5.5
25
2.2
39.9
3390
1860
7.8
1.2
2.0
2.3
46.5
4200
2640
300
5.5
25
2.2
41.9
3990
2110
8.4
1.3
2.5
2.4
49.9
5030
3130
400
5.5
35
2.3
45.8
5100
2490
9.0
1.3
2.5
2.5
53.8
6140
3600
500
5.5
35
2.4
48.4
6000
2900
9.7
1.4
2.5
2.6
56.6
7210
4100
630
5.5
35
2.5
53.6
7340
3340
10.4
1.4
2.5
2.8
62.0
8700
4650
Electrical Data
Aluminium
Unarmoured
Wire
Cables
Armoured
Cables
Nom.
CrossSection
Area
Short
Short
Short
Circuit
Circuit
Circuit
DC
AC
Rating of
Rating of Capaci- Charging Rating of
Resistance Resistance
Copper
Conductor tance Current Copper Wire
CU / AL
CU / AL
Tape
CU / AL
Screen
Screen
1 sec
1 sec
1 sec
Reactance
Inductance
Trefoil
Flat
Flat
Trefoil
Spaced
Spaced
Impedance
Trefoil
Flat Spaced
CU AL
µΩ/m
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
µΩ/m
nH/m
nH/m
CU AL
µΩ/m
35
524/868
668/1113
5.0/3.2
162
0.7
2.6
0.7
147
207
470
620
679 1121 695 1131
50
387/641
494/822
6.8/4.4
177
0.8
2.6
0.8
141
201
450
640
511
834
527
844
70
268/443
343/568
9.8/6.3
200
0.8
2.6
0.8
135
195
430
620
364
583
386
597
95
193/320
248/410
13.3/8.5
222
0.9
2.6
0.9
129
188
410
600
272
427
300
446
120
153/253
196/325
17.2/11.0
241
0.9
2.6
0.9
122
182
390
580
225
345
257
367
150
124/206
159/265
21.2/13.5
257
1.0
4.3
1.0
116
176
370
560
193
287
229
313
185
99.1/164
128/211
26.6/17.0
280
1.0
4.3
1.0
116
173
370
550
165
237
206
267
240
75.4/125
98/161
34.9/22.3
307
1.1
4.3
1.1
110
170
350
540
140
191
185
226
300
60.1/100
80/130
43.8/28.0
336
1.2
4.3
1.2
107
166
340
530
126
163
174
203
400
470/77.8
64/102
57.3/36.6
370
1.3
5.8
1.3
100
160
320
510
113
141
164
184
500
36.6/60.5
51/81
72.3/46.2
406
1.4
5.8
1.4
97
154
310
490
105
124
158
171
630
28.3/46.9
42/64
91.2/58.3
449
1.5
5.8
1.5
94
151
300
480
97
110
151
160
www.addison-cables.com
19
Caledonian Medium Voltage Cables
Single Core 19/33KV (Um=36kV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossApprox.
Nom.
Approx.
Nom.
Section Insulation Wire
Weight
Sheath
Overall
Area Thickness Screen Thickness Diameter
Area
CU
AL
mm²
mm
mm²
mm
mm
50
70
95
120
150
185
240
300
400
500
630
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
16
16
16
16
25
25
25
25
35
35
35
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
34.2
35.8
37.6
39.0
40.9
42.4
45.1
47.3
51.2
53.8
59.0
Aluminium Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
kg/km
1580
1820
2120
2400
2740
3110
3720
4350
5410
6420
7800
1270
1380
1510
1630
1810
1950
2180
2460
2880
3320
3780
mm²
mm
mm
mm
mm
6.7
7.1
7.5
7.9
8.2
8.6
9.2
9.7
10.3
11.0
11.8
1.2
1.2
1.2
1.2
1.3
1.3
1.3
1.4
1.4
1.5
1.5
2.0
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.2
2.2
2.3
2.3
2.4
2.5
2.5
2.6
2.7
2.8
2.9
41.0
42.6
44.4
45.8
48.9
50.6
53.1
55.5
59.4
62.2
67.4
Approx.
Weight
CU
AL
kg/km
2300
2560
2890
3200
3760
4180
4830
5540
6680
7790
9290
1980
2120
2290
2430
2830
3010
3270
3630
4130
4690
5220
Electrical Data
Aluminium
Unarmoured
Wire
Cables
Armoured
Cables
Nom.
Short
Short
CrossReactance
Inductance
Impedance
Short
Circuit
Circuit
Section
Circuit
Rating of Rating of
DC
AC
Area
Rating of Capaci- Charging
Copper
Copper
Resistance Resistance
Trefoil Flat Spaced
Conductor tance Current
Flat
Flat
Wire
Tape
CU / AL
CU / AL
Trefoil
Trefoil
CU / AL
Spaced
Spaced
Screen
Screen
1 sec
CU AL CU AL
1 sec
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m µΩ/m
nH/m
nH/m
50
387/641
494/822
6.8/4.4
138
0.83
2.6
1.0
151
214
480
680
70
268/443
343/568
9.8/6.3
154
0.92
2.6
1.0
144
201
460
640
95
193/320
248/410
13.3/8.5
169
1.01
2.6
1.1
138
195
440
620
120
153/253
196/325
17.2/11.0
183
1.10
2.6
1.1
132
188
420
600
150
124/206
159/265
21.2/13.5
194
1.16
4.3
1.2
126
182
400
580
185
99.1/164
128/211
26.6/17.0
210
1.26
4.3
1.2
122
182
390
580
240
75.4/125
98/161
34.9/22.3
229
1.37
4.3
1.3
119
176
380
560
300
60.1/100
80/130
43.8/28.0
249
1.49
4.3
1.4
113
173
360
550
400
47/77.8
64/102
57.3/36.6
273
1.64
5.8
1.5
107
163
340
520
500
36.6/60.5
51/81
72.3/46.2
298
1.79
5.8
1.6
104
163
330
520
630
28.3/46.9
42/64
91.2/58.3
327
1.96
5.8
1.7
100
160
320
510
µΩ/m
µΩ/m
511 834 527 844
364 583 386 597
272 427 300 446
225 345 257 367
193 287 229 313
165 237 206 267
140 191 185 226
126 163 174 203
113 141 164 184
105 124 158 171
97 110 151 160
Medium Voltage Cables to BS 6622
Current Rating for 3.8/6.6KV (Um=7.2KV), 6.35/11KV (Um=12KV) & 8.7/15KV (Um=17.5KV)
Nom.
CrossSection
Area
Ground
Duct
Air
Trefoil
Unarm’d/Arm’d
Flat Spaced
Unarm’d/Arm’d
Trefoil
Unarm’d/Arm’d
Flat Touching
Unarm’d/Arm’d
Trefoil
Unarm’d/Arm’d
Flat Spaced
Unarm’d/Arm’d
CU
AL
CU
AL
CU
AL
CU
AL
CU
AL
CU
mm²
A
A
A
A
A
AL
A
25
160/160
120/120
170/170
125/125
165/165
125/125
165/165
125/125
170/170
130/130
230/235
180/180
35
180/180
150/150
190/190
155/15
185/185
155/155
185/185
155/155
200/200
160/160
260/265
210/210
50
220/220
170/170
230/230
175/175
225/220
175/170
220/220
170/170
235/250
180/195
295/300
230/230
70
270/270
210.210
280/280
215/215
270/260
215/210
270/270
210/210
285/310
225/240
370/370
290/290
95
320/320
250/250
335/335
260/260
320/305
255/245
325/325
250/250
360/375
280/295
455/460
350/355
120
360/360
280/280
380/380
295/295
360/340
285/275
370/370
285/285
415/430
320/355
520/530
410/410
150
410/410
320/315
430/430
330/330
400/375
315/300
415/410
320/320
470/490
365/380
600/600
465/465
185
460/455
360/355
485/485
375/375
440/410
350/335
465/460
360/360
540/550
425/435
690/690
530/530
240
530/520
415/405
560/560
440/440
505/460
405/380
540/540
420/420
640/650
500/510
820/820
640/630
300
600/580
475/455
640/640
495/495
560/500
455/420
610/610
475/470
740/740
580/580
940/940
730/730
400
680/650
540/510
730/730
570/570
610/530
510/455
690/690
540/540
840/840
670/670 1100/1100 860/860
500
750/710
610/570
830/830
650/650
680/570
570/500
790/780
620/620
940/930
790/770 1280/1280 1010/1010
630
830/760
680/640
940/940
750/750
750/620
640/550
890/890
710/700 1110/1040 910/880 1500/1480 1190/1180
Current Rating for 12.7/22KV (Um=24KV)
Nom.
CrossSection
Area
Ground
Duct
Air
Trefoil
Unarm’d/Arm’d
Flat Spaced
Unarm’d/Arm’d
Trefoil
Unarm’d/Arm’d
Flat Touching
Unarm’d/Arm’d
Trefoil
Unarm’d/Arm’d
Flat Spaced
Unarm’d/Arm’d
CU
AL
CU
AL
CU
AL
CU
AL
CU
AL
CU
mm²
A
A
A
A
A
AL
A
35
180/180
130/130
200/200
135/135
180/170
130/125
180/175
130/125
190/175
145/135
225/230
175/175
50
220/220
170/170
230/230
175/175
225/210
175/170
225/220
175/170
245/260
190/200
295/300
230/230
70
270/270
210.210
280/280
215/215
270/260
210/205
270/270
210/210
300/320
235/245
365/370
285/285
95
320/320
250/245
335/335
260/260
320/300
250/245
320/325
250/250
360/380
280/295
450/450
345/350
120
360/360
280/280
380/380
295/295
360/340
280/275
365/365
285/285
425/440
330/340
520/520
400/400
150
410/410
320/310
430/430
330/330
405/370
320/300
410/410
320/315
485/490
375/385
590/590
455/455
185
460/450
360/350
485/485
375/375
445/400
350/335
460/460
360/360
550/560
430/440
670/670
520/520
240
530/510
415/405
560/560
440/440
520/450
415/380
530/530
415/415
650/650
510/510
800/800
620/620
300
600/570
475/450
640/640
495/495
570/490
460/415
600/600
470/470
740/730
580/580
920/910
710/710
400
690/640
550/510
730/730
570/570
630/530
520/460
690/680
540/530
850/830
680/670 1070/1060 840/830
500
760/700
610/570
830/830
650/650
700/570
570/510
780/770
610/610
980/940
790/770 1250/1230 980/970
630
850/760
690/640
950/940
750/750
780/610
650/560
890/880
700/700 1130/1050 920/880 1450/1430 1060/1140
www.addison-cables.com
21
Caledonian Medium Voltage Cables
Current Rating for 19/33KV (Um=36KV)
Ground
Duct
Air
Nom.
CrossSection
Area
Trefoil
Unarm’d/Arm’d
Flat Spaced
Unarm’d/Arm’d
Trefoil
Unarm’d/Arm’d
Flat Touching
Unarm’d/Arm’d
Trefoil
Unarm’d/Arm’d
Flat Spaced
Unarm’d/Arm’d
CU
CU
CU
CU
CU
CU
mm²
A
AL
AL
A
AL
A
AL
A
AL
A
AL
A
50
220/220
170/170
230/230
175/175
225/220
175/170
225/220
175/170
245/260
190/200
295/300
230/230
70
270/270
210.210
280/280
215/215
270/260
210/205
270/270
210/210
300/320
235/245
365/370
285/285
95
320/320
250/245
335/335
260/260
320/300
250/245
320/325
250/250
360/380
280/295
450/450
345/350
120
360/360
280/280
380/380
295/295
360/340
280/275
365/365
285/285
425/440
330/340
520/520
400/400
150
410/410
320/310
430/430
330/330
405/370
320/300
410/410
320/315
485/490
375/385
590/590
455/455
185
460/450
360/350
485/485
375/375
445/400
350/335
460/460
360/360
550/560
430/440
670/670
520/520
240
530/510
415/405
560/560
440/440
520/450
415/380
530/530
415/415
650/650
510/510
800/800
620/620
300
600/570
475/450
640/640
495/495
570/490
460/415
600/600
470/470
740/730
580/580
920/910
710/710
400
690/640
550/510
730/730
570/570
630/530
520/460
690/680
540/530
850/830
680/670 1070/1060 840/830
500
760/700
610/570
830/830
650/650
700/570
570/510
780/770
610/610
980/940
790/770 1250/1230 980/970
630
850/760
690/640
940/940
750/750
780/610
650/560
890/880
700/700 1130/1050 920/880 1450/1430 1060/1140
▓▓ Current Rating Conditions:
Ground Temperature:20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W
Medium Voltage Cables to BS 6622
Three Core Cables to BS 6622
▓▓ APPLICATIONS:
The three core cables are designed for distribution
of electrical power with nominal voltage Uo/U
ranging from 3.6/6.6KV to 19/33KV and frequency
50Hz. They are suitable for installation mostly in
power supply stations, indoors and in cable ducts,
outdoors, underground and in water as well
as for installation on cable trays for industries,
switchboards and power stations.
▓▓ STANDARD:
PVC/PE/LSZH Oversheath
PVC/PE/LSZH Separation Sheath(optional)
Metallic Screen
Insulation Screen
Insulation
Conductor
XLPE/EPR Screen
Binder
Armour(optional)
BS 6622
▓▓ CONSTRUCTION:
Conductor: Plain annealed copper or aluminium complying with IEC 60228/BS 6360. Copper
conductors shall be stranded (class 2) and aluminium conductors shall be either solid or
stranded (class 2).
Conductor Screen: Extruded layer of semi-conducting cross-linkable compound is applied
over the conductor and shall cover the surface completely. The minimum thickness is 0.3mm
and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
Insulation: Insulation is of cross-linked polyethylene compound XLPE (GP8) conforming to
BS 7655-1.3 or EPR (GP7), conforming to BS 7655-1.2.
Table 1. Insulation Thickness
Nom. Cross
Section Area
Insulation Thickness at Nom. Voltage
3.8/6.6KV(Um=7.2KV) 6.35/11KV(Um=12KV) 8.7/15KV(Um=17.5KV) 12.7/22KV(Um=24KV)
19/33KV(Um=36KV)
mm²
mm
mm
mm
mm
mm
70 – 185
2.5
3.4
4.5
5.5
8.0
240
2.6
3.4
4.5
5.5
8.0
300
2.8
3.4
4.5
5.5
8.0
400
3.0
3.4
4.5
5.5
8.0
Above 500
3.2
3.4
4.5
5.5
8.0
www.addison-cables.com
23
Caledonian Medium Voltage Cables
Insulaton Screen: Extruded layer of semi-conducting cross-linkable compound is applied
over the insulation. The extruded semi-conducting layer shall consist of bonded or cold
strippable semi-conducting compound capable of removal for jointing or terminating. As an
option, a semi -conducting tape may be applied over the extruded semi-conducting layer as a
bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity
is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and
can be easily hand stripped on site.
Inner Covering & Fillers: For cables with a collective metallic layer or cables with a metallic
layer over each individual cores with additional collective metallic layers, semi-conducting
inner covering and fillers shall be applied over the laid up cores. The inner covering is made
of non hygroscopic material, except if the cable is to be made longitudinally watertight. The
inner covering shall be extruded or lapped.
The approximate thickness of extruded inner coverings is given in Table 2:
Table 2. Approximate Thickness Of Extruded Inner Coverings
Ficititous Diameter Over Laid Up Cores
Approx. Thickress of Extruded Inner Covering
mm
mm
>
<
35
45
1.0
25
35
1.2
35
45
1.4
45
60
1.6
60
80
1.8
80
-
2.0
*The approximate thickness of lapped inner coverings shall be 0.6mm.
Metallic Layer: The metallic layer shall be applied over each core or applied as a collective
screen. The metallic screen shall consist of either copper tapes or a concentric layer of
copper wires or a combination of tapes and wires. The metallic layer provides an earth
fault current path, capable of withstanding fault current to earth of 1000A for one second at
maximum temperature 160°C. Copper wires are applied over the conducting water blocking
layer with a minimum diameter of 0.5mm. And over the copper wires, copper tape with
minimum thickness of 0.1mm can be applied helically with overlap.
Total cross section of copper wire screen is shown in table 3.
Table 3. Minimum Total Cross Section Of Copper Wire Screen & DC Resistance Of The Screen
Nominal Cross-Section
Area of Cable
Minimum Cross-Section
of Copper Wire Screen Area
DC Resistance of the Copper Wire Screen
mm²
mm²
mm
up to 120
16
1.06
150-300
25
0.72
400-630
35
0.51
Separation Sheath (for armoured cable): The separation sheath comprises a layer of
extruded PVC, PE or LSZH. The nominal thickness is calculated by 0.02Du + 0.6mm where
Medium Voltage Cables to BS 6622
Du is the fictitious diameter under the sheath in mm. The nominal separation sheath thickness
shall not be less than 1.2mm.
Armour (for armoured cable): The armour consists of galvanized steel wire applied over the
inner covering with diameter specified as in Table 4.
Table 4. Armour Wire Diameter
Fictitiious Diameter Under the Armour
Armour Wire Diameter
mm
mm
>
<
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15
Over Sheath: Overall sheath comprises a layer of extruded either PVC type 9 conforming
to BS 7665-4.2 or MDPE type TS2 conforming to BS 7655-10.1; LSZH can be offered as an
option. The oversheath is normally black in colour. When a DC voltage test is to be performed
on the oversheath, a semi-conducting layer such as graphite coating shall be applied over
the surface of the extruded oversheath. The nominal oversheath thickness is calculated
by 0.035+D where D is the diameter immediately under the oversheath in mm. For cables
with the oversheath not applied over the armour, the nominal oversheath thickness shall not
be less than 1.4mm. And for cables with oversheath applied over the armour, the nominal
oversheath thickness shall not be less than 1.8mm.
▓▓ PHYSICAL PROPERTIES:
Operating Temperature: up to 90°C
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds)
Bending Radius: 15 x OD
Table 5. Nominal /Operating /Test Voltages
Rated Voltage Uo/U
Operating Voltage (Um)
Testing Voltage (rms)
3.8/6.6KV
7.2KV
15KV
6.35/11KV
12KV
25.5KV
8.7/15KV
17.5KV
35KV
12.7/22KV
24KV
51KV
19/33KV
36KV
76KV
www.addison-cables.com
25
Caledonian Medium Voltage Cables
Three Core 3.8/6.6KV (Um=7.2KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossApprox.
Nom.
Approx.
Nom.
Section Insulation Tape
Weight
Sheath
Overall
Screen
Area
Thickness Diameter
Thickness
Area
CU
AL
mm²
mm
mm²
mm
mm
kg/km
25
2.5
16
2.1
37.7
2205
35
2.5
16
2.3
41.2
2690
50
2.5
16
2.5
44.9
70
2.5
16
2.6
48.0
Steel Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
Approx.
Weight
CU
AL
mm²
mm
mm
mm
mm
kg / km
1740
3.4
1.2
2.0
2.2
44.5
3890
3465
2010
3.6
1.2
2.5
2.3
46.8
4420
3730
3340
2350
3.8
1.3
2.5
2.5
51.5
5640
4690
4050
2730
4.3
1.3
2.5
2.6
55.0
6570
5240
95
2.5
16
2.7
51.7
5000
3180
4.7
1.4
2.5
2.7
58.9
7760
5890
120
2.5
16
2.8
54.7
5890
3590
5.0
1.5
2.5
2.8
62.1
8810
6510
150
2.5
25
2.9
58.4
6960
4160
5.3
1.5
2.5
2.9
65.8
10110 7310
185
2.5
25
3.0
61.9
8160
4650
5.8
1.6
2.5
3.0
69.5
11520 7960
240
2.6
25
3.2
68.1
10210
5530
6.3
1.7
2.5
3.2
75.9
13920 9140
300
2.8
25
3.5
73.6
12380
6670
7.0
1.8
3.15
3.5
83.1
17400 11620
400
3.0
35
3.7
83.8
16190
8430
7.7
2.0
3.15
3.7
93.0
21900 13980
Electrical Data
Steel Wire
Unarmoured
Armoured
Cables
Cables
Nom.
CrossSection
Area
Current Ratings
Short
Short
Short Circuit Circuit
Ground
Circuit
Rating of Rating of
DC
AC
Rating of Capaci- Charging Copper Wire Copper Reac- InducResistance Resistance
Conductor tance Current
Screen
Tape
tance tance
CU / AL
CU / AL
CU / AL
Per Core Screen Per
CU
AL
1 sec
1 sec
Core
1 sec
Duct
CU
A
Air
AL
CU
95
145
115
A
AL
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m nH/m
25
727/1200
927/1538
3.6/2.3
272
0.33
2.6
0.4
113
370
140
115
125
A
35
524/868
668/1113
5.0/3.2
301
0.36
2.6
0.5
108
350
170
135
150
115
175
140
50
387/641
494/822
6.8/4.4
332
0.40
2.6
0.5
102
330
210
160
180
135
220
170
70
268/443
343/568
9.8/6.3
383
0.46
2.6
0.6
97
310
255
195
215
165
270
210
95
193/320
248/410
13.3/8.5
432
0.52
2.6
0.6
92
290
300
230
255
200
330
250
120
153/253
196/325
17.2/11.0
474
0.57
2.6
0.7
89
280
340
265
290
225
375
295
150
124/206
159/265
21.2/13.5
511
0.61
4.3
0.7
87
280
380
295
330
255
430
330
185
99.1/164
128/211
26.6/17.0
562
0.67
4.3
0.8
86
270
430
335
370
290
490
385
240
75.4/125
98/161
34.9/22.3
602
0.72
4.3
0.9
83
260
490
380
425
335
570
450
300
60.1/100
80/130
43.8/28.0
622
0.75
4.3
1.0
82
260
540
435
470
375
650
510
400
47.0/77.8
64/102
57.3/36.6
648
0.78
5.8
1.1
80
250
590
480
520
420
700
570
Medium Voltage Cables to BS 6622
Three Core 6.35/11KV (Um=12KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossNom.
Approx.
Nom.
Section Insulation Wire
Sheath
Overall
Area Thickness Screen Thickness Diameter
Area
Steel Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
Approx.
Weight
CU
AL
kg/km
Approx.
Weight
CU
AL
mm²
mm
mm²
mm
mm
mm²
mm
mm
mm
mm
kg / km
25
3.4
16
2.3
42.8
2600
35
3.4
16
2.3
45.3
3000
2120
3.8
1.3
2.5
2.4
50.0
4930
4400
2320
4.1
1.3
2.5
2.5
52.3
5380
4700
50
3.4
16
2.4
48.5
3630
2690
4.4
1.4
2.5
2.6
55.7
6210
5260
70
3.4
16
2.5
52.0
4440
3110
4.7
1.4
2.5
2.7
59.2
7200
5870
95
3.4
16
2.7
56.0
5440
3620
5.2
1.5
2.5
2.8
63.2
8420
6550
120
3.4
16
2.8
59.4
6370
4020
5.5
1.6
2.5
3.0
67.0
9580
7190
150
3.4
25
2.9
62.7
7430
4630
5.8
1.6
2.5
3.1
70.3
10830 8030
185
3.4
25
3.0
66.1
8680
5150
6.2
1.7
2.5
3.2
73.9
12290 8720
240
3.4
25
3.1
71.7
10690 5990
6.8
1.8
3.15
3.4
81.2
15620 10790
300
3.4
25
3.3
76.4
12770 7050
7.3
1.9
3.15
3.6
86.1
18030 12240
400
3.4
35
3.5
85.1
16460 8680
8.0
2.0
3.15
3.8
95.0
22350 14350
Electrical Data
Steel Wire
Unarmoured
Armoured
Cables
Cables
Nom.
CrossSection
Area
mm²
25
Current Ratings
Short
Short
Short Circuit Circuit
Circuit
Rating of
Rating of
DC
AC
Rating of Capaci- Charging Copper Wire Copper Reac- InducResistance Resistance
Conductor tance Current
Screen
Tape
tance tance
CU / AL
CU / AL
CU / AL
Per Core Screen Per
1 sec
1 sec
Core
1 sec
µ Ω/m
µ Ω/m
727/1200 927/1538
kA
pF/m
mA/m
kA
kA
µΩ/m nH/m
3.6/2.3
216
0.43
2.6
0.5
123
390
Ground
CU
Duct
AL
CU
115
125
A
140
Air
AL
CU
95
145
A
AL
A
115
35
524/868
668/1113
5.0/3.2
237
0.47
2.6
0.6
115
370
170
135
150
115
175
140
50
387/641
494/822
6.8/4.4
260
0.52
2.6
0.6
109
350
210
160
180
135
220
170
70
268/443
343/568
9.8/6.3
298
0.60
2.6
0.7
103
330
255
195
215
165
270
210
95
193/320
248/410
13.3/8.5
334
0.67
2.6
0.7
99
310
300
230
255
200
330
250
120
153/253
196/325
17.2/11.0
365
0.73
2.6
0.8
96
310
340
265
290
225
375
295
150
124/206
159/265
21.2/13.5
392
0.78
4.3
0.8
93
300
380
295
330
255
430
330
185
99.1/164
128/211
26.6/17.0
430
0.86
4.3
0.9
90
290
430
335
370
290
490
385
240
75.4/125
98/161
34.9/22.3
476
0.95
4.3
0.9
87
280
490
380
425
335
570
450
300
60.1/100
80/130
43.8/28.0
524
1.05
4.3
1.0
85
270
540
435
470
375
650
510
400
47.0/77.8
64/102
57.3/36.6
580
1.16
5.8
1.1
81
260
590
480
520
420
700
570
www.addison-cables.com
27
Caledonian Medium Voltage Cables
Three Core 8.7/15KV (Um=17.5KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossApprox.
Nom.
Approx.
Nom.
Section Insulation Wire
Weight
Sheath
Overall
Area Thickness Screen Thickness Diameter
Area
CU
AL
mm²
mm
mm²
mm
mm
kg/km
Steel Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
mm²
mm
mm
mm
Approx.
Weight
CU
mm
AL
kg / km
25
4.5
16
2.4
48.4
3000 2420
4.4
1.4
2.5
2.6
55.2
5600
5100
35
4.5
16
2.5
50.4
3450 2670
4.7
1.4
2.5
2.7
57.6
6130
5440
50
4.5
16
2.6
53.7
4140 3190
4.9
1.5
2.5
2.8
61.1
7010
6060
70
4.5
16
2.7
57.2
4980 3640
5.3
1.5
2.5
2.9
64.6
8030
6700
95
4.5
16
2.8
60.6
5900 4050
5.7
1.6
2.5
3.0
68.2
9160
7330
120
4.5
16
2.9
63.9
6870 4560
6.1
1.7
2.5
3.1
71.7
10340
8030
150
4.5
25
3.0
67.9
8030 5230
6.4
1.7
2.5
3.2
75.4
11730
8930
185
4.5
25
3.1
71.1
9310 5770
6.8
1.8
3.15
3.4
80.6
14170 10570
240
4.5
25
3.3
76.9
11390 6680
7.4
1.9
3.15
3.6
86.6
16670 11810
300
4.5
25
3.5
81.6
13510 7790
7.9
2.0
3.15
3.7
91.3
19140 13340
400
4.5
35
3.7
89.9
17130 9340
8.5
2.1
3.15
4.0
100.0
23360 15410
Electrical Data
Steel Wire
Unarmoured
Armoured
Cables
Cables
Nom.
CrossSection
Area
Short
Short Circuit
Circuit
Rating of
DC
AC
Rating of Capaci- Charging Copper Wire
Resistance Resistance
Conductor tance Current Screen Per
CU / AL
CU / AL
CU / AL
Core
1 sec
1 sec
Current Ratings
Short
Circuit
Rating of
Copper Reac- InducTape
tance tance
Screen
Per Core
1 sec
Ground
CU
Duct
AL
Cu
115
Air
Al
Cu
125
95
145
115
175 140
A
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
25
727/1200
927/1538
3.6/2.3
176
0.48
2.6
0.6
138
410
35
524/868
668/1113
5.0/3.2
193
0.53
2.6
0.6
123
390
170 135 150
50
387/641
494/822
6.8/4.4
211
0.58
2.6
0.7
116
370
210 160 180 135 220 170
140
A
Al
A
115
70
268/443
343/568
9.8/6.3
240
0.65
2.6
0.7
110
350
255 195 215 165 270 210
95
193/320
248/410
13.3/8.5
267
0.73
2.6
0.8
105
330
300 230 255 200 330 250
120
153/253
196//325
17.2/11.0
291
0.79
2.6
0.8
102
320
340 265 290 225 375 295
150
124/206
159/265
21.2/13.5
312
0.85
4.3
0.9
98
310
380 300 330 255 430 330
185
99.1/164
128/211
26.6/17.0
340
0.93
4.3
0.9
95
300
430 335 370 290 490 385
240
75.4/125
98/161
34.9/22.3
375
1.02
4.3
1.0
91
290
490 380 425 335 570 450
300
60.1/100
80/130
43.8/28.0
411
1.12
4.3
1.1
89
280
540 435 470 375 650 510
400
47.0/77.8
64/102
57.3/36.6
454
1.24
5.8
1.2
84
270
590 480 520 420 700 570
Medium Voltage Cables to BS 6622
Three Core 12.7/22KV (Um=24KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
CrossApprox.
Nom.
Approx.
Nom.
Section Insulation Wire
Weight
Sheath
Overall
Area Thickness Screen Thickness Diameter
Area
CU
AL
kg/km
Steel Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
Approx.
Weight
CU
AL
mm²
mm
mm²
mm
mm
mm²
mm
mm
mm
mm
kg / km
35
5.5
16
2.7
51
3750
50
5.5
16
2.8
54
4240
2880
5.2
1.5
2.5
2.8
62.3
6870
6140
3250
5.4
1.5
2.5
2.9
65.6
7710
6810
70
5.5
16
2.9
58
5050
3650
5.9
1.6
2.5
3.0
69.0
8710
7370
95
5.5
16
3.0
62
6010
4110
6.2
1.7
2.5
3.2
73.1
10000
8130
120
5.5
16
3.1
65
6990
4660
6.6
1.7
3.15
3.3
77.7
12040
9730
150
5.5
25
3.2
68
8130
5330
6.9
1.8
3.15
3.4
81.7
13550 10750
185
5.5
25
3.3
72
9410
5870
7.4
1.9
3.15
3.6
85.5
15150
240
5.5
25
3.5
79
11490 6880
7.8
2.0
3.15
3.7
91.3
17710 12840
300
5.5
25
3.7
84
13710 7890
8.2
2.0
3.15
3.9
96.0
20170 14360
400
5.5
35
3.9
91
17230 9440
9.0
2.2
3.15
4.1
104.8
24520 16480
11610
Electrical Data
Steel Wire
Unarmoured
Armoured
Cables
Cables
Nom.
CrossSection
Area
mm²
Current Ratings
Short
Short
Short Circuit Circuit
Circuit
Rating of
Rating of
DC
AC
Rating of Capaci- Charging Copper Wire Copper Reac- InducResistance Resistance
Conductor tance Current
Screen
Tape
tance tance
CU / AL
CU / AL
CU / AL
Per Core
Screen
1 sec
1 sec
Per Core
1 sec
kA
pF/m
mA/m
kA
kA
Ground
CU
µΩ/m nH/m
AL
Duct
CU
A
AL
Air
CU
A
AL
µΩ/m
µΩ/m
A
35
524/868
668/1113
5.0/3.2
168
0.67
2.6
0.7
129
410
170
135
155
120
180
145
50
387/641
494/822
6.8/4.4
183
0.73
2.6
0.8
122
390
210
160
185
140
225
175
70
268/443
343/568
9.8/6.3
207
0.83
2.6
0.8
115
370
255
195
225
170
275
215
95
193/320
248/410
13.3/8.5
229
0.92
2.6
0.9
110
350
295
230
260
205
330
260
120
153/253
196/325
17.2/11.0
249
1.00
2.6
0.9
106
340
335
260
300
235
380
300
150
124/206
159/265
21.2/13.5
266
1.06
4.3
1.0
103
330
375
290
335
265
430
335
185
99.1/164
128/211
26.6/17.0
289
1.16
4.3
1.0
100
320
420
330
380
300
490
390
240
75.4/125
98/161
34.9/22.3
318
1.27
4.3
1.1
95
300
480
380
430
345
570
460
300
60.1/100
80/130
43.8/28.0
348
1.39
4.3
1.2
93
300
530
425
480
385
650
520
400
47.0/77.8
64/102
57.3/36.6
383
1.53
5.8
1.3
87
280
590
480
520
420
700
570
www.addison-cables.com
29
Caledonian Medium Voltage Cables
Three Core 19/33KV (Um=36KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
CrossNom.
Approx.
Nom.
Weight
Section Insulation Wire
Sheath
Overall
Area Thickness Screen Thickness Diameter
CU
AL
Area
mm²
mm
mm²
mm
mm
kg/km
Steel Wire Armoured Cables
Nom.
Copper
Nom.
Approx.
Nom.
Armour
Tape
Sheath
Overall
Bedding
Wire
Screen
Thickness Diameter
Thickness
Diameter
Area
mm²
mm
mm
mm
mm
Approx.
Weight
CU
AL
kg / km
35
8.0
16
3.1
60
3750
2880
6.5
1.7
2.5
3.2
74.9
9460
8700
50
8.0
16
3.2
65
5240
4260
6.7
1.8
3.15
3.4
79.0
10620
9680
70
8.0
16
3.3
70
6120
4730
7.1
1.8
3.15
3.5
82.5
11840
10440
95
8.0
16
3.4
74
7140
5240
7.5
1.9
3.15
3.6
86.4
13200
11350
120
8.0
16
3.5
77
8080
5710
7.9
2.0
3.15
3.7
89.9
14520
12190
150
8.0
25
3.6
80
9120
6220
8.2
2.0
3.15
3.8
93.6
16070
13280
185
8.0
25
3.7
84
10440
6940
8.6
2.1
3.15
3.9
97.3
17710
14090
240
8.0
25
3.9
91
12620
8010
9.2
2.2
3.15
4.1
103.2
20370
15460
300
8.0
25
4.0
95
14690
8800
9.7
2.3
3.15
4.3
108.2
22980
17210
400
8.0
35
4.3
103
17720 10230
10.3
2.4
3.15
4.5
116.8
27480
19450
Electrical Data
Aluminium
Unarmored
Wire
Current Ratings
Cables
Armoured
Cables
Nom.
Short
Short
CrossCircuit
Circuit
Ground
Duct
Air
Short Circuit
Section
Rating of Rating of
DC
AC
Rating of
Area
Capaci- Charging Copper
Copper Reac- InducResistance Resistance Conductor
tance Current
Wire
Tape
tance tance
CU / AL
CU / AL
CU / AL
Screen
Screen
1 sec
CU AL CU AL CU AL
Per Core Per Core
1 sec
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m nH/m
A
A
A
35
524/868
668/1113
5.0/3.2
132
0.79
2.6
0.9
140
460
170 135 155 120 180 145
50
387/641
494/822
6.8/4.4
142
0.85
2.6
1.0
134
430
210 160 185 140 225 175
70
268/443
343/568
9.8/6.3
159
0.95
2.6
1.0
127
400
255 195 225 170 275 215
95
193/320
248/410
13.3/8.5
175
1.05
2.6
1.1
121
390
295 230 260 205 330 260
120
153/253
196/325
17.2/11.0
189
1.13
2.6
1.1
117
370
335 260 300 235 380 300
150
124/206
159/265
21.2/13.5
201
1.21
4.3
1.2
113
360
375 290 335 265 430 335
185
99.1/164
128/211
26.6/17.0
217
1.30
4.3
1.2
109
350
420 330 380 300 490 390
240
75.4/125
98/161
34.9/22.3
237
1.42
4.3
1.3
104
330
480 380 430 345 570 460
300
60.1/100
80/130
43.8/28.0
258
1.55
4.3
1.4
101
320
530 425 480 385 650 520
400
47.0/77.8
64/102
57.3/36.6
282
1.69
5.8
1.5
96
290
590 480 520 420 700 570
Caledonian
Medium Voltage
Cables
I
III
II
III
IV
Medium Voltage Cables to IEC 60502
Single Core Cables To IEC 60502
Three Core Cables To IEC 60502
V
Caledonian Medium Voltage Cables
Single Core Cables to IEC 60502
▓▓ APPLICATIONS:
The single core cables are designed for distribution
of electrical power with nominal voltage Uo/U
ranging from 1.8/3KV to 26/35KV and frequency
50Hz. They are suitable for installation mostly
in power supply stations, indoors and in cable
ducts, outdoors, underground and in water as well
as for installation on cable trays for industries,
switchboards and power stations.
▓▓ STANDARD:
PVC/PE/LSZH Oversheath
Aluminium Wire Armour(optional)
Binder
XLPE/EPR/HEPR Insulation Screen
Conductor
Conductor Screen
Insulation Screen
Metallic Screen
PVC/PE/LSZH Separation Sheath(optional)
IEC 60502 Part 1(1.8/3KV)
IEC 60502 Part 2(3.6/6KV to 18/30KV)
▓▓ CONSTRUCTION:
Conductor: Plain annealed copper or aluminium complying with IEC 60228 class 1 or 2.
Conductor Screen: The conductor screen consists of an extruded layer of non metallic,
semi-conducting compound firmly bonded to the insulation to exclude all air voids. The
conductor screen is not necessary for both PVC and EPR/HEPR insulated 1.8/3KV and
3.6/6KV cables.
Insulation: Insulation is of polyvinyl chloride (PVC) intended for 1.8/3KV and 3.6/6KV cables,
cross-linked polyethylene compound (XLPE) or ethylene propylene rubber (EPR/HEPR).
Table 1. Insulation Thickness Of XLPE Or EPR/HEPR Insulation
Nom.
Cross
Section
Area
1.8/3KV
(Um=3.6KV)
mm²
mm
Insulation Thickness at Nominal Voltage
XLPE/EPR
10
16
25
35
50 – 185
240
300
400
500 - 1600
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2-2.8
3.6/6KV
(Um=7.2KV)
XLPE
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
6/10KV
8.7/15KV
12/20KV
(Um=12KV) (Um=17.5KV) (Um=24KV)
mm
mm
EPR
XLPE/EPR
Unscreened Screened
3.0
2.5
3.0
2.5
3.4
3.0
2.5
3.4
3.0
2.5
3.4
3.0
2.5
3.4
3.0
2.6
3.4
3.0
2.8
3.4
3.0
3.0
3.4
3.2
3.2
3.4
18/30KV
(Um=36KV)
21/35KV
(Um=42KV)
26/35KV
(Um=42KV)
mm
mm
mm
mm
mm
XLPE/EPR
XLPE/EPR
XLPE/EPR
XLPE/EPR
XLPE/EPR
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.5
5.5
5.5
5.5
5.5
5.5
8.0
8.0
8.0
8.0
8.0
9.3
9.3
9.3
9.3
9.3
10.5
10.5
10.5
10.5
10.5
*Insulation Thickness of PVC is 3.4mm (1- 1600mm sq) for 3.6/6KV cables.
Medium Voltage Cables to IEC 60502
Insulaton Screen: The insulation screen consists of an extruded layer of non metallic, semiconducting compound extruded over the insulation. The extruded semi-conducting layer
shall consist of bonded or cold strippable semi-conducting compound capable of removal
for jointing or terminating. As an option, a semi-conducting tape may be applied over the
extruded semi-conducting layer as a bedding for the metallic layer. The minimum thickness
is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen is tightly fitted to
the insulation to exclude all air voids and can be easily hand stripped on site. The insulation
screen is not necessary for both PVC and EPR/HEPR insulated 1.8/3KV and 3.6/6KV cables.
The screen may be covered by semi-conductive water blocking swellable tape to ensure
longitudinal watertightness.
Metallic Layer: The metallic layer may be applied over the individual cores or the core
assembly collectively.
The following types of metallic layers are provided:
1) Metallic Screen
2) Concentric Conductor
3) Metallic Sheath
4) Metallic armour
The metallic screen shall consist of either copper tapes or a concentric layer of copper wires
or a combination of tapes and wires to provide an earth fault current path. The concentric
conductor is applied directly either over the insulation, or over the insulation screen or over
an inner covering. The metallic sheath consists of lead or lead alloy applied as a tightly fitting
seamless tube. The metallic armour consists of either flat wire armour, round wire armour,
and double tape armour.
Table 2. Minimum Total Cross Section Of Metallic Screen
Nom. Cross-Section
Area of Cable
Min. Cross-Section
of Metallic Screen
DC Resistance of the Copper Wire Screen
mm²
mm²
mm
up to 120
16
1.06
150-300
25
0.72
400-630
35
0.51
800-1000
50
0.35
Separation Sheath (for armoured cable): The separation sheath comprises a layer of
extruded PVC, PE or LSZH, applied under the armour .The nominal thickness is calculated
by 0.02Du + 0.6mm where Du is the fictitious diameter under the sheath in mm. For cables
without a lead sheath, the nominal separation sheath thickness shall not be less than
1.2mm. For cables where the separation sheath is applied over the lead sheath, the nominal
separation sheath thickness shall not be less than 1.0mm.
Lapped Bedding (for armoured lead sheathed cable): The lapped bedding consists of
either impregnated/synthetic compounded paper tapes or a combination of two layers of
these paper tapes followed by a few layers of compounded fabulous materials. The thickness
is around 1.5mm.
Armour (for armoured cable): The armour consists of round aluminium wire armour applied
helically over an extruded separation sheath.
Table 3. Round Armour Wire Diameter
www.addison-cables.com
33
Caledonian Medium Voltage Cables
Fictitious Diameter Under the Armour
Armour Wire Diameter
mm
mm
>
<
-
10
0.8
10
15
1.25
15
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15
Over Sheath: Overall sheath comprises a layer of extruded thermoplastic compound (PVC,
PE or LSZH can be offered as an option.) or elastomeric compound (polychlorprene CSP or
chlorosulfonated PE). The nominal oversheath thickness is calculated by 0.035D+1 where D
is the fictitiuous diameter immediately under the oversheath in mm. For unarmoured cables
and cables with the oversheath not applied over the armour, metallic screen or concentric
conductor, the nominal oversheath thickness shall not be less than 1.4mm. And for cables
with oversheath applied over the armour, metallic screen or concentric conductor, the nominal
oversheath thickness shall not be less than 1.8mm.
▓▓ PHYSICAL PROPERTIES:
Operating Temperature: up to 70°C (PVC insulation); up to 90°C (XLPE or EPR insulation)
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature( 5 seconds maximum duration ): 140-160°C (PVC insulation);
250°C (XLPE or EPR insulation)
Bending Radius: 12 x OD
Table 4. Nominal /Operating /Testing Voltages
Rated Voltage Uo/U
Operating Voltage (Um)
1.8/3KV
3.6KV
Testing Voltage (rms)
6.5KV
3.6/6KV
7.2KV
12.5KV
6/10KV
12KV
21KV
8.7/15KV
17.5KV
30.5KV
12/20KV
24KV
42KV
18/30KV
36KV
63KV
21/35KV
42KV
73.5(53)*KV
26/35KV
42KV
91(65)*KV
*21/35KV and 26/35kV power frequency voltage test can be made under the following conditions: 2.5Uo x 30mins or 3.0Uo x 15mins.
Numbers in brackets refer to the test values for 3.0Uo x 1.5mins.
Medium Voltage Cables to IEC 60502
Single Core 1.8/3KV (Um=3.6KV)
Dimensional Data
Unarmoured Cables
Steel Wire Armoured Cables
Nom.
Copper
Approx.
Approx.
CrossNom.
Approx.
Nom.
Armour
Nom.
Approx.
Nom.
Copper
Wire
Weight
Weight
Section Insulation
Sheath
Overall
Bedding Wire
Sheath
Overall
Tape
Area Thickness Thickness Screen Thickness Diameter
Thickness
Size
Thickness
Diameter
CU
AL
CU
AL
Area*
mm²
mm
mm
mm²
mm
mm
mm
mm
mm
mm
10
2.0
0.1
16
1.8
13
240
kg/km
180
1.2
1.6
1.8
18
460
kg/km
400
16
2.0
0.1
16
1.8
13
300
200
1.2
1.6
1.8
19
530
430
25
2.0
0.1
16
1.8
15
410
250
1.2
1.6
1.8
20
650
500
35
2.0
0.1
16
1.8
16
510
300
1.2
1.6
1.8
21
780
560
50
2.0
0.1
16
1.8
17
640
350
1.2
1.6
1.8
22
930
640
70
2.0
0.1
16
1.8
19
850
440
1.2
1.6
1.8
24
1170
750
95
2.0
0.1
16
1.8
20
1130
540
1.2
1.6
1.8
26
1460
870
120
2.0
0.1
16
1.8
22
1370
630
1.2
1.6
1.8
27
1730
990
150
2.0
0.1
25
1.8
23
1650
730
1.2
1.6
1.8
29
2030
1110
185
2.0
0.1
25
1.8
25
2010
860
1.2
1.6
1.9
30
2430
1280
240
2.0
0.1
25
1.8
27
2570 1050
1.2
1.6
2.0
33
3040
1530
300
2.0
0.1
25
1.8
29
3160 1250
1.2
2.0
2.1
36
3760
1860
400
2.0
0.1
35
1.9
33
3980 1560
1.2
2.0
2.2
39
4660
2230
2930
500
2.2
0.1
35
2.1
35.5
4910 1905
1.3
2.5
2.5
43
5930
630
2.4
0.1
35
2.2
39.7
6340 2420
1.4
2.5
2.6
49
7370
3430
800
2.6
0.1
50
2.3
44.5
7890 2980
1.4
2.5
2.7
52
9070
4230
1000
2.8
0.1
50
2.5
49.4
9890 3700
1.5
2.5
2.9
56
11100
4950
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Short
Reactance
Inductance
Impedance
Circuit
Circuit
Circuit Rating
Nom.
DC
AC
Rating of
Rating of Capaci- Charging of Copper
CrossTrefoil Flat Spaced
Resistance Resistance
Copper
Conductor tance Current
Wire
Section
Flat
Flat
CU / AL
CU / AL
Tape
Trefoil
Trefoil
CU / AL
Screen
Area
Spaced
Spaced
Screen
cu AL cu AL
1 sec
1 sec
1 sec
mm²
µΩ/m
µΩm
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
µΩ/ m
µΩ/ m
10
1830/3080 2330/3920
1.4/0.9
182
0.27
2.6
0.2
151
201
384
558 2332 3846 2332 3840
16
1150/1910 1460/2420
2.2/1.4
201
0.29
2.6
0.3
140
193
362
546 1462 2411 1478 2420
25
727/1200 927/1538
3.6/2.3
222
0.32
2.6
0.3
131
185
345
535
936 1544 952 1554
679 1121 695 1131
35
524/868
668/1113
5.0/3.2
251
0.35
2.6
0.4
122
178
327
524
50
387/641
494/822
6.8/4.4
281
0.39
2.6
0.4
116
172
313
514
511 834 527
844
70
268/443
343/568
9.8/6.3
341
0.45
2.6
0.5
110
165
300
495
364 583 386
597
95
193/320
248/410
13.3/8.5
397
0.50
2.6
0.5
104
160
287
485
272 427 300
446
120
153/253
196/325
17.2/11.0
430
0.55
2.6
0.6
104
159
283
480
225 345 257
367
150
124/206
159/266
21.2/13.5
464
0.59
4.3
0.6
100
156
280
475
193 287 229
313
185
99.1/164
128/211
26.6/17.0
513
0.65
4.3
0.7
98
154
274
465
165 237 206
267
240
75.4/125
98/161
34.9/22.3
573
0.70
4.3
0.9
94
150
267
459
140 191 185
226
300
60.1/100
80/130
43.8/28.0
652
0.72
4.3
1.0
91
147
260
455
128 163 174
203
400
47.0/77.8
64/102
57.3/36.6
727
0.75
5.8
1.1
90
147
253
445
113 141 164
184
500
36.6/60.5
51/81
72.3/46.2
754
0.79
5.8
1.2
89
145
248
435
105 124 158
171
630
28.3/46.9
42/64
91.2/58.3
786
0.87
5.8
1.3
86
143
245
425
97
110 151
160
800
22.1/36.7
35/55
114.4/75.0
846
0.91
8.2
1.4
85
142
243
415
92
101 147
153
1000
17.6/29.1
30/46
143.0/94.0
916
0.99
8.2
1.5
83
141
239
405
88
95
148
144
www.addison-cables.com
35
Caledonian Medium Voltage Cables
Single Core 3.6/6KV (Um=7.2KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
Nom.
Approx.
Nom.
Copper
CrossWire
Weight
Sheath
Overall
Tape
Section Insulation
Screen
Area Thickness Thickness Area* Thickness Diameter CU
AL
mm²
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
3.2
3.2
3.2
mm
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
mm²
16
16
16
16
16
16
16
16
25
25
25
25
35
35
35
50
50
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.1
2.2
2.4
2.5
mm
16
16
18
19
20
22
23
25
26
28
31
34
38
41.5
45.3
49.9
54.2
Aluminium Wire Armoured Cables
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
kg/km
320
260
390
290
500
340
610
400
750
450
970
550
1250 660
1500 760
1790 860
2150 1000
2770 1250
3400 1500
4280 1850
5325 2240
6745 2750
8290 3310
10255 3990
mm
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.3
1.4
1.5
1.5
1.6
mm
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.2
2.2
2.4
2.6
2.7
2.8
3.0
mm
22
22
23
24
26
27
29
31
32
35
38
41
46
50
56
59
63
Approx.
Weight
CU
AL
kg/km
610
550
680
580
810
660
940
730
1100
810
1350
930
1670 1080
1950 1200
2270 1350
2770 1620
3440 1930
4120 2210
5250 2820
6520 3520
7960 4020
9660 4820
11690 5540
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Reactance
Inductance
Impedance
Short
Short Circuit
Circuit
Circuit
Nom.
Rating
Rating
DC
AC
Rating of Capaci- Charging
Crossof Copper of Copper
Resistance Resistance
Trefoil Flat Spaced
Conductor tance Current
Section
Flat
Flat
Wire Screen
Tape
CU / AL
CU / AL
Trefoil
Trefoil
CU / AL
Area
Spaced
Spaced
1 sec
Screen
1 sec
CU AL CU
AL
1 sec
mm²
µΩ/m
µΩm
kA
10 1830/3080 2330/3920 1.4/0.9
16 1150/1910 1460/2420 2.2/1.4
25
727/1200 927/1538 3.6/2.3
35
524/868 668/1113 5.0/3.2
50
387/641 494/822
6.8/4.4
70
268/443 343/568
9.8/6.3
95
193/320 248/410 13.3/8.5
120
153/253 196/325 17.2/11.0
150
124/206 159/265 21.2/13.5
185
99.1/164 128/211 26.6/17.0
240
75.4/125
98/161 34.9/22.3
300
60.1/100
80/130 43.8/28.0
400 47.0/77.8 64/102 57.3/36.6
500 36.6/60.5
51/81
72.3/46.2
630 28.3/46.9
42/64
91.2/58.3
800 22.1/36.7
35/55 114.4/75.0
1000 17.6/29.1
30/46 143.0/94.0
pF/m
202
232
262
291
321
371
417
459
494
543
583
602
627
654
726
786
856
mA/m
0.26
0.29
0.32
0.35
0.39
0.45
0.50
0.55
0.59
0.65
0.70
0.72
0.75
0.79
0.87
0.91
0.99
kA
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
4.3
4.3
4.3
4.3
5.8
5.8
5.8
8.2
8.2
kA
0.4
0.4
0.4
0.5
0.5
0.6
0.6
0.7
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
µΩ/m
160
214
152
205
142
196
133
187
121
179
115
173
110
168
107
165
103
161
100
158
97
155
95
153
92
150
90
147
87
145
85
143
83
141
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
nH/m
420
610
410
600
400
590
390
580
380
570
370
550
350
540
340
520
330
510
320
500
310
490
300
490
290
480
290
470
280
460
270
460
260
450
µΩ/ m
µΩ/m
2332 3846 2345 3840
1462 2411 1478 2421
936 1544 952 1554
679 1121 695 1131
511 834 527 844
364 583 386 597
272 427 300 446
225 345 257 367
193 287 229 313
165 237 206 267
140 191 185 226
126 163 174 203
113 141 164 184
105 124 158 171
97 110 151 160
92 101 147 153
88 95 144 148
Medium Voltage Cables to IEC 60502
Single Core 6/10KV (Um=12KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
CrossNom.
Approx.
Nom.
Copper
Wire
Weight
Section Insulation
Sheath Overall
Tape
Area Thickness Thickness Screen Thickness Diameter
CU
AL
Area*
mm²
mm
mm
mm²
mm
mm
Aluminium Wire Armoured Cables
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
kg/km
mm
mm
mm
Approx.
Weight
CU
mm
AL
kg/km
16
3.4
0.1
16
1.8
18
450
350
1.2
1.6
1.8
24
770
670
25
3.4
0.1
16
1.8
20
560
400
1.2
1.6
1.8
25
910
750
35
3.4
0.1
16
1.8
21
680
460
1.2
1.6
1.8
26
1040
820
50
3.4
0.1
16
1.8
22
810
520
1.2
1.6
1.8
28
1190
900
70
3.4
0.1
16
1.8
24
1050
620
1.2
1.6
1.9
29
1470
1040
95
3.4
0.1
16
1.8
25
1320
730
1.2
1.6
2.0
31
1780
1190
120
3.4
0.1
16
1.8
27
1580
840
1.2
2.0
2.0
34
2150
1410
150
3.4
0.1
25
1.9
28
1880
960
1.2
2.0
2.1
35
2480
1560
185
3.4
0.1
25
1.9
30
2250 1100
1.2
2.0
2.1
37
2890
1730
240
3.4
0.1
25
2.0
33
2870 1350
1.2
2.0
2.2
40
3570
2050
300
3.4
0.1
25
2.1
35
3490 1580
1.2
2.0
2.3
42
4230
2330
400
3.4
0.1
35
2.2
39
4350 1920
1.3
2.5
2.4
47
5320
2890
500
3.4
0.1
35
2.2
39.9
5235 2240
1.4
2.5
2.5
51
6510
3530
630
3.4
0.1
35
2.3
43.7
6675 2765
1.5
2.5
2.6
56
7960
4050
800
3.4
0.1
50
2.5
48.6
8225 3330
1.5
2.5
2.7
59
9670
4850
1000
3.4
0.1
50
2.6
52.9
10210 4030
1.6
2.5
2.9
63
11710
5570
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Reactance
Inductance
Impedance
Short
Circuit
Circuit
Circuit
Nom.
Rating of Rating of
DC
AC
Rating of Capaci- Charging
CrossCopper
Copper
Resistance Resistance
Trefoil Flat spaced
Conductor tance Current
Section
Flat
Flat
Wire
Tape
CU / AL
CU / AL
Trefoil
Trefoil
CU / AL
Area
Spaced
Spaced
Screen
Screen
1 sec
CU AL CU AL
1 sec
1 sec
mm²
kA
pF/m
mA/m
kA
kA
16
1150/1910 1460/2420
µΩ/m
µΩm
2.2/1.4
187
0.39
2.6
0.5
152
µΩ/m
216
480
nH/m
680
1462 2411 1478 2421
µΩ/ m
µΩ/m
25
727/1200
927/1538
3.6/2.3
208
0.42
2.6
0.5
144
210
460
660
936 1544 952 1554
35
524/868
668/1113
5.0/3.2
229
0.46
2.6
0.6
136
200
440
640
679 1121 695 1131
50
387/641
494/822
6.8/4.4
252
0.50
2.6
0.6
131
195
420
620
511 834 527 844
70
268/443
343/568
9.8/6.3
288
0.58
2.6
0.7
122
188
390
600
364 583 386 597
95
193/320
248/410
13.3/8.5
323
0.65
2.6
0.7
122
182
390
580
272 427 300 446
120
153/253
196/325
17.2/11.0
353
0.71
2.6
0.8
116
172
370
550
225 345 257 367
150
124/206
159/265
21.2/13.5
380
0.76
4.3
0.8
110
166
350
530
193 287 229 313
185
99.1/164
128/211
26.6/17.0
416
0.83
4.3
0.9
107
166
340
530
165 237 206 267
240
75.4/125
98/161
34.9/22.3
460
0.92
4.3
0.9
104
163
330
520
140 191 185 226
126 163 174 203
300
60.1/100
80/130
43.8/28.0
506
1.01
4.3
1.0
100
157
320
500
400
47.0/77.8
64/102
57.3/36.6
561
1.12
5.8
1.1
94
154
300
490
113 141 164 184
500
36.6/60.5
51/81.0
72.3/46.2
619
1.24
5.8
1.2
91
151
290
480
105 124 158 171
630
28.3/46.9
42/64.0
91.2/58.3
698
1.37
5.8
1.3
91
148
290
470
97
110 151 160
800
22.1/36.7
35/55
114.4/75.0
780
1.39
8.2
1.4
88
144
280
470
92
101 147 153
1000
17.6/29.1
30/46
143.0/94.0
860
1.54
8.2
1.5
85
143
270
460
88
95
144 148
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
www.addison-cables.com
37
Caledonian Medium Voltage Cables
Single Core 8.7/15KV (Um=17.5KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
CrossNom.
Approx.
Nom.
Copper
Wire
Weight
Section Insulation
Sheath
Overall
Tape
Area Thickness Thickness Screen Thickness Diameter
CU
AL
Area*
mm²
mm
mm
mm²
mm
mm
kg/km
25
4.5
0.1
16
1.8
22
640
35
4.5
0.1
16
1.8
23
760
50
4.5
0.1
16
1.8
24
70
4.5
0.1
16
1.8
95
4.5
0.1
16
1.8
120
4.5
0.1
16
150
4.5
0.1
25
185
4.5
0.1
240
4.5
300
Aluminium Wire Armoured Cables
Approx.
Weight
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
CU
AL
mm
mm
mm
mm
kg/km
480
1.2
1.6
1.8
28
1020
540
1.2
1.6
1.9
29
1170
950
900
610
1.2
1.6
1.9
30
1340
1040
26
1140
710
1.2
1.6
2.0
32
1610
1190
27
1420
830
1.2
2.0
2.1
35
2020
1430
1.9
29
1700
950
1.2
2.0
2.1
36
2310
1570
1.9
31
1990 1070
1.2
2.0
2.2
38
2660
1740
25
2.0
32
2380 1230
1.2
2.0
2.2
39
3070
1920
0.1
25
2.1
35
3010 1490
1.2
2.0
2.3
42
3750
2240
4.5
0.1
25
2.1
37
3620 1720
1.3
2.5
2.4
46
4590
2690
400
4.5
0.1
35
2.2
41
4490 2070
1.3
2.5
2.5
49
5550
3120
500
4.5
0.1
35
2.3
43
5460 2460
1.3
2.5
2.6
52
6590
3600
630
4.5
0.1
35
2.4
48
6790 2590
1.4
2.5
2.7
57
8060
4110
800
4.5
0.1
50
2.6
52
8420 3570
1.5
2.5
2.8
61
9800
4970
1000
4.5
0.1
50
2.7
55
10330 4180
1.6
2.5
3.0
65
10850
5710
860
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Reactance
Inductance
Short
Circuit
Circuit
Circuit
Nom.
Rating of Rating of
DC
AC
Rating of Capaci- Charging
CrossCopper Copper
Resistance Resistance
Conductor tance Current
Section
Flat
Flat
Wire
Tape
CU / AL
CU / AL
Trefoil
Trefoil
CU / AL
Area
Spaced
Spaced
Screen
Screen
1 sec
1 sec
1 sec
mm²
µΩ/m
µΩm
µΩ/m
nH/m
Impedance
Trefoil
CU
AL
µΩ/ m
Flat spaced
CU
AL
kA
pF/m
mA/m
kA
kA
25
727/1200 927/1538
3.6/2.3
171
0.47
2.6
0.6
150
210
480
680
936 1544 952 1554
µΩ/m
35
524/868
668/1113
5.0/3.2
187
0.51
2.6
0.6
141
207
460
660
679 1121 695 1131
50
387/641
494/822
6.8/4.4
204
0.57
2.6
0.7
138
195
440
640
511
834
527
844
70
268/443
343/568
9.8/6.3
232
0.63
2.6
0.7
132
188
420
600
364
583
386
597
95
193/320
248/410
13.3/8.5
258
0.71
2.6
0.8
126
182
400
580
272
427
300
446
120
153/253
196/325
17.2/11.0
281
0.74
2.6
0.8
119
179
380
570
225
345
257
367
150
124/206
159/265
21.2/13.5
301
0.79
4.3
0.9
113
176
360
560
193
287
229
313
185
99.1/164
128/211
26.6/17.0
329
0.87
4.3
0.9
110
170
350
540
165
237
206
267
240
75.4/125
98/161
34.9/22.3
363
0.96
4.3
1.0
107
166
340
530
140
191
185
226
300
60.1/100
80/130
43.8/28.0
398
1.03
4.3
1.1
104
160
330
510
126
163
174
203
400
47.0/77.8
64/102
57.3/36.6
439
1.17
5.8
1.2
97
157
310
500
113
141
164
184
500
36.6/60.5
51/81
72.3/46.2
483
1.28
5.8
1.3
94
154
300
490
105
124
158
171
630
28.3/46.9
42/64
91.2/58.3
534
1.42
5.8
1.4
91
151
290
480
97
110
151
160
800
22.1/36.7
35/55
114.4/75.0
590
1.61
8.2
1.4
91
147
290
470
92
101
147
153
1000
17.6/29.1
30/46
143.0/94.0
640
1.75
8.2
1.5
88
144
280
460
88
95
144
148
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
Medium Voltage Cables to IEC 60502
Single Core 12/20KV (Um=24KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
CrossNom.
Approx.
Nom.
Copper
Wire
Weight
Section Insulation
Sheath Overall
Tape
Area Thickness Thickness Screen Thickness Diameter
Cu
AL
Area*
Aluminium Wire Armoured Cables
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
kg/km
Approx.
Weight
Cu
AL
mm²
mm
mm
mm²
mm
mm
mm
mm
mm
mm
25
5.5
0.1
16
1.8
24
720
560
1.2
1.6
1.8
29
1200
kg/km
980
35
5.5
0.1
16
1.8
25
840
620
1.2
1.6
1.9
30
1350
1070
50
5.5
0.1
16
1.8
26
990
690
1.2
2.0
2.0
33
1550
1250
70
5.5
0.1
16
1.8
28
1230
800
1.2
2.0
2.1
35
1840
1420
95
5.5
0.1
16
1.9
30
1530
940
1.2
2.0
2.1
37
2160
1570
120
5.5
0.1
16
2.0
31
1810
1050
1.2
2.0
2.2
38
2470
1730
150
5.5
0.1
25
2.0
33
2110
1190
1.2
2.0
2.2
40
2810
1890
185
5.5
0.1
25
2.1
35
2510
1360
1.2
2.0
2.3
42
3240
2090
240
5.5
0.1
25
2.1
38
3130
1610
1.3
2.5
2.4
45
4150
2580
300
5.5
0.1
25
2.2
40
3760
1860
1.3
2.5
2.5
48
4800
2890
400
5.5
0.1
35
2.3
43
4650
2220
1.4
2.5
2.6
52
5780
3350
500
5.5
0.1
35
2.4
46
5530
2545
1.5
2.5
2.7
55
6850
3850
630
5.5
0.1
35
2.5
50
6700
3100
1.5
2.5
2.9
60
8380
4400
800
5.5
0.1
50
2.6
55
8580
3690
1.6
2.5
3.0
64
10130
5270
1000
5.5
0.1
50
2.7
59
10620 4445
1.7
2.5
3.1
68
12180
6000
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Reactance
Inductance
Impedance
Short
Short Circuit Circuit
Circuit
Nom.
Rating of Rating of
DC
AC
Rating of Capaci- Charging
CrossCopper Wire Copper
Resistance Resistance
Trefoil Flat spaced
Conductor tance Current
Section
Flat
Flat
Screen
Tape
CU / AL
CU / AL
Trefoil
Trefoil
CU / AL
Area
Spaced
Spaced
1 sec
Screen
1 sec
Cu AL Cu
AL
1 sec
mm²
µΩ/m
µΩm
kA
pF/m
mA/m
kA
kA
25
727/1200
927/1538
3.6/2.3
142
0.62
2.6
0.6
162
µΩ/m
214
490
nH/m
680
35
524/868
668/1113
5.0/3.2
162
0.65
2.6
0.7
150
207
470
660
50
387/641
494/822
6.8/4.4
177
0.71
2.6
0.8
141
201
450
640
70
268/443
343/568
9.8/6.3
200
0.80
2.6
0.8
135
195
430
620
95
193/320
248/410
13.3/8.5
222
0.89
2.6
0.9
129
188
410
600
120
153/253
196/325
17.2/11.0
241
0.96
2.6
0.9
122
182
390
580
150
124/206
159/265
21.2/13.5
257
1.03
4.3
1.0
116
176
370
560
185
99.1/164
128/211
26.6/17.0
280
1.12
4.3
1.0
116
173
370
550
240
75.4/125
98/161
34.9/22.3
307
1.23
4.3
1.1
110
170
350
540
300
60.1/100
80/130
43.8/28.0
336
1.34
4.3
1.2
107
166
340
530
400
47.0/77.8
64/102
57.3/36.6
370
1.48
5.8
1.3
100
160
320
510
500
36.6/60.5
51/81
72.3/46.2
406
1.62
5.8
1.4
97
154
310
490
630
28.3/46.9
42/64
91.2/58.3
449
1.80
5.8
1.5
94
151
300
480
800
22.1/36.7
35/55
114.4/75.0
490
1.85
8.2
1.6
91
151
290
480
1000
17.6/29.1
30/46
143.0/94.0
540
2.03
8.2
1.7
87
148
280
470
µΩ/ m
µΩ/m
936 1544 952 1554
679 1121 695 1131
511 834 527
364 583 386
272 427 300
844
225 345 257
193 287 229
367
165 237 206
140 191 185
267
126 163 174
113 141 164
203
105 124 158
97 110 151
171
92 101 147
88 95 144
153
597
446
313
226
184
160
148
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
www.addison-cables.com
39
Caledonian Medium Voltage Cables
Single Core 18/30KV (Um=36KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
CrossNom.
Approx.
Nom.
Copper
Wire
Weight
Section Insulation
Sheath
Overall
Tape
Area Thickness Thickness Screen Thickness Diameter
Cu
AL
Area*
Aluminium Wire Armoured Cables
Approx.
Weight
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
kg/km
Cu
AL
mm²
mm
mm
mm²
mm
mm
mm
mm
mm
mm
50
8.0
0.1
16
2.0
31
1250
960
1.2
2.0
2.2
38
1910
kg/km
1640
70
8.0
0.1
16
2.0
34
1510
1090
1.2
2.0
2.3
41
2240
1820
95
8.0
0.1
16
2.1
35
1830
1240
1.2
2.0
2.3
42
2570
1980
120
8.0
0.1
16
2.1
37
2110
1360
1.3
2.5
2.4
45
3060
2310
150
8.0
0.1
25
2.2
38
2420
1510
1.3
2.5
2.5
47
3430
2510
185
8.0
0.1
25
2.2
40
2830
1680
1.3
2.5
2.5
50
3890
2720
240
8.0
0.1
25
2.3
43
3500
1980
1.4
2.5
2.6
52
4630
3120
300
8.0
0.1
25
2.4
45
4150
2250
1.4
2.5
2.7
54
5330
3430
400
8.0
0.1
35
2.5
49
5070
2640
1.5
2.5
2.8
58
6360
3930
500
8.0
0.1
35
2.6
52
5945
2965
1.6
2.5
2.9
61
7670
4490
630
8.0
0.1
35
2.7
56
7445
3555
1.7
2.5
3.0
65
8870
5020
800
8.0
0.1
50
2.8
61
9060
4180
1.9
2.5
3.2
69
10790 5980
1000
8.0
0.1
50
2.9
65
11140
4980
2.0
2.5
3.3
73
12860 6730
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Short
Short
Reactance
Inductance
Impedance
Short
Circuit
Circuit
Circuit
Nom.
Rating of Rating of
DC
AC
Rating of Capaci- Charging
CrossCopper
Copper
Resistance Resistance
Trefoil
Flat spaced
Conductor tance Current
Section
Flat
Flat
Wire
Tape
CU / AL
CU / AL
Trefoil
Trefoil
CU / AL
Area
spaced
spaced
Screen
Screen
1 sec
Cu AL Cu AL
1 sec
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
µΩ/ m
µΩ/ m
50
387/641
494/822
6.8/4.4
138
0.83
2.6
1.0
151
214
480
680
511
834
527
844
70
268/443
343/568
9.8/6.3
154
0.92
2.6
1.0
144
201
460
640
364
583
386
597
95
193/320
248/410
13.3/8.5
169
1.01
2.6
1.1
138
195
440
620
272
427
300
446
120
153/253
196/325
17.2/11.0
183
1.10
2.6
1.1
132
188
420
600
225
345
257
367
150
124/206
159/265
21.2/13.5
194
1.16
4.3
1.2
126
182
400
580
193
287
229
313
185
99.1/164
128/211
26.6/17.0
210
1.26
4.3
1.2
122
182
390
580
165
237
206
267
240
75.4/125
98/161
34.9/22.3
229
1.37
4.3
1.3
119
176
380
560
140
191
185
226
300
60.1/100
80/130
43.8/28.0
249
1.49
4.3
1.4
113
173
360
550
126
163
174
203
400
47.0/77.8
64/102
57.3/36.6
273
1.64
5.8
1.5
107
163
340
520
113
141
164
184
500
36.6/60.5
51/81
72.3/46.2
298
1.79
5.8
1.6
104
163
330
520
105
124
158
171
630
28.3/46.9
42/64
91.2/58.3
327
1.96
5.8
1.7
100
160
320
510
97
110
151
160
800
22.1/36.7
35/55
114.4/75.0
350
1.98
8.2
1.8
97
154
310
490
92
101
147
153
1000
17.6/29.1
30/46
143.0/94.0
380
2.15
8.2
1.9
94
149
300
490
88
95
144
148
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
Medium Voltage Cables to IEC 60502
Single Core 21/35KV (Um=42KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
CrossNom.
Approx.
Nom.
Copper
Wire
Weight
Section Insulation
Sheath
Overall
Tape
Area Thickness Thickness Screen Thickness Diameter
Cu
Al
Area*
mm²
mm
mm
mm²
mm
mm
Aluminium Wire Armoured Cables
Approx.
Weight
Nom. Armour Nom.
Approx.
Bedding Wire
Sheath
Overall
Thickness Size Thickness Diameter
kg/km
mm
mm
mm
Cu
mm
Al
kg/km
50
9.3
0.1
16
2.0
35.7
1526
1239
1.2
2.0
2.3
43.5
2331
2116
70
9.3
0.1
16
2.1
37.6
1809
1393
1.2
2.5
2.4
46.6
2680
2325
95
9.3
0.1
16
2.2
39.4
2123
1555
1.2
2.5
2.5
48.4
2981
2482
120
9.3
0.1
16
2.2
40.8
2405
1688
1.4
2.5
2.5
49.8
3487
2867
150
9.3
0.1
25
2.2
42.3
2733
1838
1.4
2.5
2.6
51.5
3870
3055
185
9.3
0.1
25
2.3
44.7
3216
2082
1.4
2.5
2.6
53.5
4420
3370
240
9.3
0.1
25
2.4
46.9
3766
2333
1.4
2.5
2.7
55.8
4981
3676
300
9.3
0.1
25
2.4
49.3
4408
2605
1.4
2.5
2.8
58.5
5661
3971
400
9.3
0.1
35
2.5
52.3
5473
3057
1.6
2.5
2.9
61.7
6865
4550
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Short
Reactance
Inductance
Impedance
Circuit
Circuit
Circuit
Nom.
Rating of Rating of
DC
AC
Rating
Capaci- Charging
CrossCopper
Copper
Resistance Resistance
of
Trefoil Flat spaced
tance Current
Section
Flat
Flat
Wire
Tape
CU / AL
CU / AL Conductor
Trefoil
Trefoil
Area
Spaced
Spaced
Screen
Screen
CU / AL
Cu Al Cu
Al
1 sec
1 sec
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
50
387/641
494/822
6.8/4.4
130
0.89
2.6
1.1
156
µΩ/m
220
495
nH/m
700
511 834 527
µΩ/ m
µΩ/ m
844
70
268/443
343/568
9.8/6.3
144
0.98
2.6
1.1
150
204
475
650
364 583 386
597
95
193/320
248/410
13.3/8.5
159
1.06
2.6
1.2
142
198
455
630
272 427 300
446
120
153/253
196/325
17.2/11.0
171
1.18
2.6
1.2
137
191
435
610
225 345 257
367
150
124/206
159/265
21.2/13.5
180
1.26
4.3
1.3
131
185
415
590
193 287 229
313
185
99.1/164
128/211
26.6/17.0
193
1.34
4.3
1.3
125
185
400
590
165 237 206
267
240
75.4/125
98/161
34.9/22.3
210
1.45
4.3
1.4
123
179
390
570
140 191 185
226
300
60.1/100
80/130
43.8/28.0
228
1.57
4.3
1.5
116
176
370
560
126 163 174
203
400
47.0/77.8
64/102
57.3/36.6
249
1.74
5.8
1.6
110
166
350
530
113 141 164
184
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
www.addison-cables.com
41
Caledonian Medium Voltage Cables
Single Core 26/35KV (Um=42KV)
Dimensional Data
Unarmoured Cables
Nom.
Copper
Approx.
CrossNom.
Approx.
Nom.
Copper
Wire
Weight
Section Insulation
Sheath
Overall
Tape
Area Thickness Thickness Screen Thickness Diameter
Cu
Al
Area*
Aluminium Wire Armoured Cables
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
kg/km
Approx.
Weight
Cu
Al
mm²
mm
mm
mm²
mm
mm
mm
mm
mm
mm
50
10.5
0.1
16
2.1
38.3
1689
1402
1.2
2.5
2.5
46.8
2580
kg/km
70
10.5
0.1
16
2.2
40.2
1980
1564
1.2
2.5
2.5
48.8
2937
2611
95
10.5
0.1
16
2.2
41.8
2283
1714
1.2
2.5
2.6
50.9
3206
2737
120
10.5
0.1
16
2.3
43.4
2588
1871
1.4
2.5
2.6
51.5
3753
3177
150
10.5
0.1
25
2.3
44.9
2923
2028
1.4
2.5
2.7
53.8
4143
3371
185
10.5
0.1
25
2.4
47.3
3415
2281
1.4
2.5
2.7
55.6
4694
3693
240
10.5
0.1
25
2.5
49.5
3975
2542
1.4
2.5
2.8
57.6
5258
4005
300
10.5
0.1
25
2.5
51.9
4625
2822
1.4
2.5
2.9
60.8
5940
4301
400
10.5
0.1
35
2.6
54.9
5704
3288
1.6
2.5
3.0
63.6
7155
4894
2395
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Short
Reactance
Inductance
Impedance
Circuit
Circuit
Circuit
Nom.
Rating of Rating of
DC
AC
Rating
Capaci- Charging
CrossCopper
Copper
Resistance Resistance
of
Trefoil Flat spaced
tance Current
Section
Flat
Flat
Wire
Tape
CU / AL
CU / AL Conductor
Trefoil
Trefoil
Area
Spaced
Spaced
Screen
Screen
CU / AL
Cu Al Cu
Al
1 sec
1 sec
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
50
387/641
494/822
6.8/4.4
126
0.95
2.6
1.2
161
µΩ/m
227
510
nH/m
720
511 834 527
µΩ/ m
µΩ/ m
844
70
268/443
343/568
9.8/6.3
138
1.04
2.6
1.2
154
207
490
660
364 583 386
597
95
193/320
248/410
13.3/8.5
151
1.13
2.6
1.3
147
202
470
640
272 427 300
446
120
153/253
196/325
17.2/11.0
161
1.24
2.6
1.3
142
194
450
620
225 345 257
367
150
124/206
159/265
21.2/13.5
169
1.36
4.3
1.4
136
188
430
600
193 287 229
313
185
99.1/164
128/211
26.6/17.0
176
1.40
4.3
1.4
128
188
410
600
165 237 206
267
240
75.4/125
98/161
34.9/22.3
192
1.51
4.3
1.5
128
183
400
580
140 191 185
226
300
60.1/100
80/130
43.8/28.0
209
1.64
4.3
1.6
119
180
380
570
126 163 174
203
400
47.0/77.8
64/102
57.3/36.6
227
1.80
5.8
1.7
114
170
360
540
113 141 164
184
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
Medium Voltage Cables to IEC 60502
Current Rating for Single Core 1.8/3KV(Um=3.6KV ) to 26/35KV(Um=42KV) XLPE Insulation
Nom.
CrossSection
Area
Buried direct in Ground
Trefoil
CU
mm²
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Flat spaced
AL
CU
59
84
108
129
152
186
221
252
281
317
367
414
470
530
600
660
720
87
113
144
172
203
246
293
332
366
410
470
524
572
672
882
1002
1112
A
84
109
140
166
196
239
285
323
361
406
469
526
590
650
700
750
800
Laid in Single Way Duct
Trefoil
AL
CU
62
88
112
134
157
192
229
260
288
324
373
419
466
546
646
756
856
78
103
132
157
186
227
271
308
343
387
447
504
564
604
654
694
724
A
Flat Touching
AL
CU
55
80
102
122
144
176
210
240
267
303
351
397
451
504
554
594
644
98
104
133
159
188
229
274
311
347
391
453
510
571
661
771
871
971
A
Laid in Air
Trefoil
AL
CU
56
81
103
123
146
178
213
242
271
307
356
402
457
537
617
717
807
103
125
163
198
238
296
361
417
473
543
641
735
845
935
1045
1145
1235
A
Flat Touching
Flat spaced
AL
CU
AL
CU
75
97
127
154
184
230
280
324
368
424
502
577
673
773
883
983
1083
106
128
167
203
243
303
369
426
481
550
647
739
837
938
1048
1148
1238
77
99
130
157
189
236
287
332
376
432
511
586
676
776
886
986
1086
122
150
196
238
286
356
434
500
559
637
745
846
938
1118
1318
1528
1738
A
A
AL
A
88
116
153
185
222
278
338
391
440
504
593
677
769
919
1089
1279
1469
Current Rating for Single Core 1.8/3KV(Um=3.6KV) to 26/35KV(Um=42KV) EPR Insulation
Nom.
CrossSection
Area
Buried direct in Ground
Laid in Single Way Duct
Trefoil
Trefoil
CU
mm²
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
AL
Flat spaced
CU
A
81
106
136
162
192
234
280
319
357
403
467
526
597
657
707
757
807
AL
CU
A
57
82
105
126
149
182
217
247
277
314
364
411
471
531
601
661
721
83
109
140
167
198
242
289
329
369
417
484
545
618
718
928
1048
1158
AL
Flat Touching
CU
A
58
84
109
130
153
188
224
256
287
325
377
426
487
567
667
777
877
74
99
128
153
181
222
266
303
341
386
449
509
580
620
670
710
740
AL
Laid in Air
Trefoil
CU
A
52
77
99
118
140
172
206
235
264
300
350
397
456
509
559
599
649
94
100
129
154
183
224
269
306
344
390
454
515
588
678
788
888
988
AL
Flat Touching
Flat spaced
CU
CU
A
53
78
100
120
142
174
208
238
267
303
354
401
462
542
622
722
812
94
116
153
186
224
280
343
398
454
522
619
712
825
915
1025
1125
1215
AL
A
68
90
119
144
174
218
266
309
352
406
483
556
651
751
862
961
1061
97
119
156
190
229
287
352
407
465
534
634
728
843
849
1054
1154
1244
AL
A
70
92
121
147
178
223
273
317
361
417
495
570
667
767
876
977
1077
110
138
181
221
266
334
409
474
540
621
736
843
977
1157
1357
1567
1777
79
107
141
171
207
259
317
368
419
484
575
659
770
920
1090
1280
1470
▓▓ Current Rating Conditions:
Ground Temperature: 20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W
www.addison-cables.com
43
Caledonian Medium Voltage Cables
Three Core Cables to IEC 60502
▓▓ APPLICATIONS:
The three core cables are designed for distribution
of electrical power with nominal voltage Uo/U
ranging from 1.8/3KV to 26/35KV and frequency
50Hz. They are suitable for installation mostly
in power supply stations, indoors and in cable
ducts, outdoors, underground and in water as well
as for installation on cable trays for industries,
switchboards and power stations.
▓▓ STANDARD:
IEC 60502 Part 1(1.8/3KV)
IEC 60502 Part 2(3.6/6KV to 18/30KV)
▓▓ CONSTRUCTION:
PVC/PE/LSZH Oversheath
PVC/PE/LSZH Separation Sheath(optional)
Metallic Screen
Insulation Screen
XLPE/EPR/HEPR Insulation
Conductor
Conductor Screen
Binder
Armour(optional)
Conductor: Plain annealed copper or aluminium complying with IEC 60228 class 1 or 2.
Conductor Screen: The conductor screen consists of an extruded layer of non metallic,
semi-conducting compound applied on top of a semi-conducting tape. The conductor screen
is applied under triple extrusion process over the conductor along with the insulation and the
insulation screen. The extruded semi-conducting compound is firmly bonded to the insulation
to exclude all air voids and can be easily hand stripped on site. The conductor screen is not
necessary for both PVC and EPR/HEPR insulated 1.8/3.6KV and 3.6/6KV cables.
Insulation: Insulation is of polyvinyl chloride (PVC) intended for 1.8/3.6KV and 3.6/6KV
cables, cross-linked polyethylene compound (XLPE) or ethylene propylene rubber (EPR/
HEPR).
Table 1. Insulation Thickness Of XLPE Or EPR/HEPR Insulation
Nom.
Cross
1.8/3kV
Section
(Um=3.6kV)
Area
mm²
mm
XLPE/EPR
10
16
25
35
50 – 185
240
300
400
500 - 1600
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2-2.8
Insulation Thickness at Nom. Voltage
3.6/6kV
6/10KV
8.7/15KV
12/20KV
18/30KV
21/35KV
26/35KV
(Um=7.2kV)
(Um=12KV) (Um=17KV) (Um=24KV) (Um=36KV) (Um=42KV) (Um=42KV)
mm
mm
mm
mm
mm
mm
mm
XLPE
EPR
XLPE/EPR XLPE/EPR XLPE/EPR XLPE/EPR XLPE/EPR XLPE/EPR
Unscreened Screened
2.5
3.0
2.5
2.5
3.0
2.5
3.4
2.5
3.0
2.5
3.4
4.5
2.5
3.0
2.5
3.4
4.5
5.5
2.5
3.0
2.5
3.4
4.5
5.5
8.0
9.3
10.5
2.6
3.0
2.6
3.4
4.5
5.5
8.0
9.3
10.5
2.8
3.0
2.8
3.4
4.5
5.5
8.0
9.3
10.5
3.0
3.0
3.0
3.4
4.5
5.5
8.0
9.3
10.5
3.2
3.2
3.2
3.4
4.5
5.5
8.0
9.3
10.5
Medium Voltage Cables to IEC 60502
Insulaton Screen: The insulation screen consists of an extruded layer of non metallic,
semi-conducting compound extruded over the insulation of each core. The extruded semiconducting layer shall consist of bonded or cold strippable semi-conducting compound
capable of removal for jointing or terminating. As an option, a semi-conducting tape may be
applied over the individual cores or core assembly as a bedding for the metallic layer. The
minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen
is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site.
The insulation screen is not necessary for both PVC and EPR/HEPR insulated 1.8/3.6KV and
3.6/6KV cables. The screen may be covered by semi-conductive water blocking swellable
tape to ensure longitudinal watertightness.
Inner Covering & Fillers: For cables with a collective metallic layer or cables with a metallic
layer over each individual cores with additional collective metallic layers, semi-conducting
inner covering and fillers shall be applied over the laid up cores. The inner covering and fillers
are made of non hygroscopic material like polypropylene, except if the cable is to be made
longitudinally watertight. The inner covering is extruded in general but may be lapped if the
interstices between the cores are filled.
The approximate thickness of extruded inner coverings is given in Table 2:
Table 2. Approximate Thickness Of Extruded Inner Coverings
Ficititous Diameter Over Laid Up Cores
Approx. Thickress of Extruded Inner Covering
mm
mm
>
<
-
25
1.0
25
35
1.2
35
45
1.4
45
60
1.6
60
80
1.8
80
-
2.0
*The approximate thickness of lapped inner coverings shall be 0.4mm for fictitious diameters over the laid up cores up to and including
40mm and 0.6mm for larger diameter.
Metallic Layer: The metallic layer may be applied over the individual cores or the core
assembly collectively. The following types of metallic layers are provided:
1) Metallic Screen
2) Concentric Conductor
3) Metallic Sheath
4) Metallic Armour
The metallic screen shall consist of either copper tapes or a concentric layer of copper wires
or a combination of tapes and wires. The concentric conductor is applied directly over the
inner covering. The metallic sheath consists of lead or lead alloy applied as a tightly fitting
seamless tube. The metallic armour consists of either flat wire armour, round wire armour,
and double tape armour.
www.addison-cables.com
45
Caledonian Medium Voltage Cables
Table 3. Minimum Total Cross Section Of Metallic Screen
Nom. Cross-Section
Area of Cable
Min. Cross-Section
of Metallic Screen
DC Resistance of the Copper Wire Screen
mm²
mm²
mm
up to 120
16
1.06
150-300
25
0.72
400-630
35
0.51
800-1000
50
0.35
Separation Sheath (for armoured cable): The separation sheath comprises a layer of
extruded PVC, PE or LSZH applied over the laid up cores under the armour. PVC is normally
of grade ST2 and PE of grade ST7. The nominal thickness is calculated by 0.02Du + 0.6mm
where Du is the fictitious diameter under the sheath in mm. For cables without a lead sheath,
the nominal separation sheath thickness shall not be less than 1.2mm. For cables where the
separation sheath is applied over the lead sheath, the nominal separation sheath thickness
shall not be less than 1.0mm.
Tabel 4. Separation Thickness
Cores Diameter
Approx. Thickress of
Inner Sheath
mm
mm
>
<
35
45
1.4
45
60
1.6
60
80
1.8
80
-
2.0
Lapped Bedding (for armoured lead sheathed cable): The lapped bedding applied to
the lead sheath consists of either impregnated/synthetic compounded paper tapes or a
combination of two layers of these paper tapes followed by a few layers of compounded
fabulous materials. The thickness is around 1.5mm.
Armour (for armoured cable): The armour is applied over the inner covering helically. It
consists of either flat galvanized steel wire armour (strip), round galvanized steel wire armour,
and double steel tape armour.
Table 5. Round Armour Wire Diameter
Fictitious Diameter Under the Armour
Armour Wire Diameter
mm
mm
>
<
-
10
1.25
10
15
1.25
15
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15
Medium Voltage Cables to IEC 60502
Table 6. Armour Tape Thickness
Fictitious Diameter Under the Armour
Galvanized Steel / Steel
Aluminum / Aluminium Alloy
mm
mm
mm
>
<
-
30
0.2
0.5
30
70
0.5
0.5
70
-
0.8
0.8
For flat wire armour and fictitious diameter under the armour greater than 15mm, the nominal
thickness of the flat steel wire diameter shall be 0.8mm.Cables with fictitious diameter under
the armour up to and including 15mm, flat wire armour will not be used. The tape armour is
applied helically in two layers so that the outer tape is approximately central over the gap
of the inner tape. If tape armour is used, the inner covering shall be reinforced by taped
bedding.
Over Sheath: Overall sheath comprises a layer of extruded either thermoplastic compound
(PVC ST3 type or PE ST7 type) or elastomeric compound (polychlorprene CSP or
chlorosulfonated PE). The nominal oversheath thickness is calculated by 0.035D+1 where D
is the fictitiuous diameter immediately under the oversheath in mm. For unarmoured cables
and cables with the oversheath not applied over the armour, metallic screen or concentric
conductor, the nominal oversheath thickness shall not be less than 1.4mm. And for cables
with oversheath applied over the armour, metallic screen or concentric conductor, the nominal
oversheath thickness shall not be less than 1.8mm.
▓▓ PHYSICAL PROPERTIES:
Operating Temperature: up to 70°C (PVC insulation); up to 90°C (XLPE or EPR insulation)
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature( 5 seconds maximum duration ): 140-160 °C (PVC insulation);
250°C (XLPE or EPR insulation)
Bending Radius: 15 x OD
Table 7. Nominal /Operating /Testing Voltages
Rated Voltage Uo/U
Operating Voltage (Um)
Testing Voltage (rms)
1.8/3KV
3.6KV
6.5KV
3.6/6KV
7.2KV
12.5KV
6/10KV
12KV
21KV
8.7/15KV
17.5KV
30.5KV
12/20KV
24KV
42KV
18/30KV
36KV
63KV
21/35KV
42KV
73.5(53)*KV
26/35KV
42KV
91(65)*KV
*21/35KV and 26/35kV power frequency voltage test can be made under the following conditions: 2.5Uo x 30mins or 3.0Uo x 15mins.
Numbers in brackets refer to the test values for 3.0Uo x 1.5mins.
www.addison-cables.com
47
Caledonian Medium Voltage Cables
Three Core 1.8/3KV (Um=3.6KV)
Dimensional Data
Unarmoured Cables
Copper
Nom.
Nom.
Approx.
Nom.
Copper
Wire
CrossSheath
Overall
Insulation
Tape
Screen
Section
Thickness Diameter
Thickness Thickness
Area*
Area
mm²
mm
mm
mm²
mm
mm
10
2.0
0.1
16
1.8
23
16
2.0
0.1
16
1.8
25
2.0
0.1
16
1.8
35
2.0
0.1
16
50
2.0
0.1
16
70
2.0
0.1
95
2.0
0.1
120
2.0
150
2.0
185
240
Steel Round-Wire Armoured Cables
Approx.
Weight
CU
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
AL
kg/km
Approx.
Weight
CU
AL
mm
mm
mm
mm
650
460
1.2
1.6
1.8
28
1480
kg/km
1290
24
840
540
1.2
1.6
1.9
29
1720
1410
26
1160
680
1.2
1.6
1.9
32
2130
1650
1.8
29
1490
820
1.2
2.0
2.1
36
2810
2140
1.9
32
1900
1000
1.2
2.0
2.2
39
3340
2450
16
2.0
36
2580
1290
1.2
2.0
2.3
42
4200
2910
16
2.2
40
3440
1640
1.3
2.5
2.4
47
5620
3820
0.1
16
2.3
43
4220
1950
1.3
2.5
2.5
51
6580
4310
0.1
25
2.4
46
5090
2290
1.4
2.5
2.7
54
7680
4870
2.0
0.1
25
2.5
50
6240
2730
1.5
2.5
2.8
58
9060
5560
2.0
0.1
25
2.7
56
8030
3430
1.6
2.5
3.0
64
11200
6600
300
2.0
0.1
25
2.8
60
9890
4100
1.6
2.5
3.1
69
13590
7500
400
2.0
0.1
35
3.1
68
12530 5150
1.8
3.15
3.4
78
17260
9880
500
2.2
0.1
35
3.3
75.7
16680 7510
1.8
3.15
3.5
84.3
21780
13025
630
2.4
0.1
35
3.5
84.9
21770 10040
1.8
3.15
3.8
94.6
27400
16050
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Steel Flat Wire Armoured Cables
Nom.
Nom.
Armour
Approx.
CrossNom.Sheath
Bedding
Wire
Overall
Section
Thickness
Thickness
Size
Diameter
Area
Double Steel Tape Armoured Cables
Approx.
Weight
CU
AL
kg/km
Nom.
Bedding
Thickness
No of Steel
Tapes x Nom
Tape
Thickness
mm
mm
mm
mm
Nom.
Approx.
Sheath
Overall
Thickness Diameter
Approx.
Weight
CU
AL
mm²
mm
mm
mm
mm
kg/km
10
1.2
0.8
1.8
24.5
1245
1065
1.2
2 x 0.2
1.8
23.6
925
16
1.2
0.8
1.8
27.1
1565
1280
1.2
2 x 0.2
1.8
26.2
1205
925
25
1.2
0.8
1.8
29.7
1975
1525
1.2
2 x 0.2
1.9
29.0
1590
1145
750
35
1.2
0.8
1.9
32.5
2420
1805
1.2
2 x 0.2
1.9
31.6
1985
1370
50
1.2
0.8
2.0
35
2860
2080
1.2
2 x 0.2
2.0
34.1
2400
1605
70
1.2
0.8
2.1
38.7
3685
2525
1.2
2 x 0.5
2.2
39.5
3570
2410
95
1.3
0.8
2.2
42.9
4695
3080
1.3
2 x 0.5
2.3
43.7
4570
2950
120
1.3
0.8
2.3
46.4
5650
3585
1.3
2 x 0.5
2.4
46.1
5510
3440
150
1.4
0.8
2.4
49.6
6630
4085
1.4
2 x 0.5
2.6
50.6
6500
3955
185
1.5
0.8
2.6
54.1
7990
4820
1.5
2 x 0.5
2.7
54.9
7825
4650
240
1.6
0.8
2.7
59.2
10060
5790
1.6
2 x 0.5
2.8
60.0
9825
5600
300
1.6
0.8
2.9
64.6
12230
6865
1.6
2 x0.5
3.0
65.4
12030
6660
400
1.8
0.8
3.1
71.0
15200
8280
1.8
2 x 0.5
3.2
71.8
14970
8055
500
1.8
0.8
3.3
79.5
19090 10255
1.8
2 x 0.8
3.5
80.5
18880 10035
630
1.8
0.8
3.6
89.8
24400 12920
1.8
2 x 0.8
3.8
92.3
25070 13620
Medium Voltage Cables to IEC 60502
Electrical Data
Short Circuit
Rating of
Conductor
CU / AL
1 sec
Nom.
DC
AC
CrossResistance Resistance
Section
CU / AL
CU / AL
Area
Capaci- Charging
tance
Current
Short Circuit
Rating of
Copper Wire
Screen Per
Core
1 sec
Short Circuit
Rating of
Copper Tape
Screen Per
Core
1 sec
Reactance
Inductance
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
10
1830/3080
2330/3920
1.4/0.9
160
0.25
2.6
0.4
101
390
16
1150/1910
1460/2420
2.2/1.4
180
0.27
2.6
0.4
98
370
25
727/1200
929/1538
3.6/2.3
220
0.29
2.6
0.4
95
350
35
524/868
668/1113
5.0/3.2
250
0.31
2.6
0.5
92
330
50
387/641
494/822
6.8/4.4
270
0.33
2.6
0.5
88
310
70
268/443
343/568
9.8/6.3
310
0.35
2.6
0.6
84
290
95
193/320
248/410
13.3/8.5
350
0.38
2.6
0.6
81
270
120
153/253
196/325
17.2/11.0
380
0.46
2.6
0.7
79
250
150
124/206
159/265
21.2/13.5
420
0.50
2.6
0.7
77
260
185
99.1/164
128/211
26.6/17.0
460
0.56
2.6
0.8
76
250
240
75.4/125
98/161
34.9/22.3
510
0.61
4.3
0.9
74
240
300
60.1/100
80/130
43.8/28.0
570
0.68
4.3
1.0
73
250
400
47.0/77.8
64/102
57.3/36.6
590
0.70
5.8
1.1
71
240
500
36.6/60.5
57/81
72.3/46.2
610
0.72
5.8
1.2
69
230
630
28.3/46.9
42/64
91.2/58.3
630
0.74
5.8
1.3
67
220
Three Core 3.8/6.6KV (Um=7.2KV)
Dimensional Data
Unarmoured Cables
Steel Round-Wire Armoured Cables
Copper
Nom.
Nom.
Approx. Approx.Weight Nom.
Armour
Nom.
Approx.
Nom.
Copper
Wire
CrossSheath
Overall
Bedding
Wire
Sheath Overall
Insulation
Tape
Screen
Section
Thickness Diameter CU
Thickness Thickness
AL Thickness Size Thickness Diameter
Area*
Area
mm²
mm
mm
mm²
mm
mm
10
2.5
0.1
16
2.0
30
16
2.5
0.1
16
2.0
31
25
2.5
0.1
16
2.1
34
35
2.5
0.1
16
2.2
37
50
2.5
0.1
16
2.3
40
70
2.5
0.1
16
2.4
95
2.5
0.1
16
2.5
kg/km
Approx.
Weight
CU
AL
mm
mm
mm
mm
kg/km
790
1.2
2.0
2.1
36
2310 2120
1190
890
1.2
2.0
2.2
38
2600 2290
1560
1080
1.2
2.0
2.3
41
3080 2600
1930
1270
1.3
2.5
2.4
45
3950 3280
2370
1480
1.3
2.5
2.5
47
4530 3630
43
3110
1820
1.4
2.5
2.6
51
5510 4210
47
4000
2200
1.5
2.5
2.8
55
6660 4860
980
120
2.5
0.1
16
2.6
50
4820
2550
1.5
2.5
2.9
59
7630 5360
150
2.5
0.1
25
2.8
54
5770
2970
1.6
2.5
3.0
62
8800 6000
185
2.5
0.1
25
2.9
58
6960
3460
1.6
2.5
3.1
66
10180 6670
240
2.6
0.1
25
3.1
65
8940
4340
1.8
3.15
3.4
75
13480 8870
300
2.8
0.1
25
3.3
70
10980
5190
1.9
3.15
3.6
81
15920 10130
400
3.0
0.1
35
3.5
79
13820
6440
2.0
3.5
3.9
90
19980 12590
500
3.2
0.1
35
3.7
87
19100 10755
2.1
3.5
4.1
98
24160 14820
630
3.2
0.1
35
4.0
95
30470 13150
2.2
3.5
4.4
107
29650 17710
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
www.addison-cables.com
49
Caledonian Medium Voltage Cables
Steel Flat Wire Armoured Cables
Nom.
CrossSection
Area
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
Double Steel Tape Armoured Cables
Approx.
Weight
CU
AL
No of Steel
Nom.
Approx.
Nom.
tapes x
Sheath
Overall
Bedding
nom tape
Thickness Diameter
Thickness
thickness
kg/km
Approx.
Weight
CU
AL
mm²
mm
mm
mm
mm
mm
mm
mm
mm
10
1.2
0.8
1.8
26.9
1415
1235
1.2
2X0.2
1.8
26
1060
kg/km
885
16
1.2
0.8
1.8
29.2
1725
1445
1.2
2X0.2
1.8
28.3
1340
1055
25
1.2
0.8
1.9
32.2
2165
1735
1.2
2X0.2
1.9
31.3
1735
1305
35
1.3
0.8
2.0
35.0
2645
2025
1.3
2X0.2
2.0
34.1
2170
1555
50
1.3
0.8
2.1
37.4
3075
2295
1.3
2X0.5
2.1
38.0
2950
2170
70
1.4
0.8
2.2
41.0
3915
2755
1.4
2X0.5
2.3
41.8
3795
2635
95
1.5
0.8
2.3
45.3
4840
3335
1.5
2X0.5
2.4
46.1
4810
3200
120
1.5
0.8
2.4
48.7
5915
3855
1.5
2X0.5
2.5
49.5
5770
3705
150
1.6
0.8
2.5
52.1
6930
4395
1.6
2X0.5
2.6
52.9
6775
4235
185
1.6
0.8
2.6
56.2
8265
5100
1.6
2X0.5
2.8
57.2
8120
4950
240
1.8
0.8
2.8
62.2
10440
6220
1.8
2X0.5
2.9
63.0
10250
6025
300
1.9
0.8
3.0
68.2
12780
7420
1.9
2X0.5
3.1
69.0
12570
7200
400
2.0
0.8
3.3
75.9
15970
9110
2.0
2X0.5
3.4
76.7
15740
8870
500
2.1
0.8
3.5
84.2
19940
11130
2.1
2X0.8
3.6
86.5
20550 11750
630
2.2
0.8
3.7
93.5
25120
13670
2.2
2X0.8
3.9
96.0
25830 14400
Short Circuit
Rating of
Copper Wire
Screen Per
Core
1 sec
Electrical Data
Nom.
CrossSection
Area
DC
AC
Resistance Resistance
CU / AL
CU / AL
Short Circuit
Rating of
Conductor
CU / AL
1 sec
Capacitance
Charging
Current
Short Circuit
Rating of
Copper Tape
Screen Per
Core
1 sec
Reactance Inductance
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
10
1830/3080
2330/3920
1.4/0.9
212
0.27
2.6
0.4
132
410
16
1150/1910
1470/2420
2.2/1.4
242
0.30
2.6
0.4
124
390
25
727/1200
927/1538
3.6/2.3
272
0.33
2.6
0.4
116
370
35
524/868
668/1113
5.0/3.2
301
0.36
2.6
0.5
108
350
50
387/641
494/822
6.8/4.4
332
0.40
2.6
0.5
102
330
70
268/443
343/568
9.8/6.3
383
0.46
2.6
0.6
97
310
95
193/320
248/410
13.3/8.5
432
0.52
2.6
0.6
92
290
120
153/253
196/325
17.2/11.0
474
0.57
2.6
0.7
89
280
150
124/206
159/265
21.2/13.5
511
0.61
4.3
0.7
87
280
185
99.1/164
128/211
26.6/17.0
562
0.67
4.3
0.8
86
270
240
75.4/125
98/161
34.9/22.3
602
0.72
4.3
0.9
83
260
300
60.1/100
80/130
43.8/28.0
622
0.75
4.3
1.0
82
260
400
47.0/77.8
64/102
57.3/36.6
648
0.78
5.8
1.1
80
250
500
36.6/60.5
51/81
72.3/46.2
668
0.82
5.8
1.2
78
250
630
28.3/46.9
42/64
91.2/58.3
758
0.92
5.8
1.3
76
240
Medium Voltage Cables to IEC 60502
Three Core 6/10KV (Um=12KV)
Dimensional Data
Unarmoured Cables
Approx.
Weight
Copper
Nom.
Nom.
Approx.
Nom.
Copper
Wire
CrossSheath
Overall
Insulation
Tape
Screen
Section
Thickness Diameter
Thickness Thickness
Area*
Area
mm²
mm
mm
mm²
mm
Steel Round-Wire Armoured Cables
CU
mm
AL
Approx.
Weight
Nom.
Armour
Nom.
Approx
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
kg/km
mm
mm
mm
CU
mm
AL
kg/km
16
3.4
0.1
16
2.2
36
1410
1110
1.2
2.0
2.4
42
3000
2700
25
3.4
0.1
16
2.3
39
1800
1320
1.3
2.5
2.5
46
3900
3430
35
3.4
0.1
16
2.3
41
2170
1500
1.3
2.5
2.6
49
4430
3770
50
3.4
0.1
16
2.4
44
2630
1730
1.4
2.5
2.7
52
5080
4190
70
3.4
0.1
16
2.6
48
3400
2110
1.5
2.5
2.8
56
6050
4750
95
3.4
0.1
16
2.7
52
4310
2510
1.5
2.5
2.9
60
7180
5380
120
3.4
0.1
16
2.8
55
5150
2890
1.6
2.5
3.0
63
8230
5960
150
3.4
0.1
25
2.9
58
6100
3300
1.7
2.5
3.1
67
9380
6580
185
3.4
0.1
25
3.0
62
7310
3810
1.7
3.15
3.3
72
11610
8110
240
3.4
0.1
25
3.2
69
9290
4680
1.8
3.15
3.5
79
14110
9510
300
3.4
0.1
25
3.3
73
11240 5450
1.9
3.15
3.7
84
16420 10630
400
3.4
0.1
35
3.6
81
14040 6660
2.0
3.5
3.9
92
20620 12880
500
3.4
0.1
35
3.7
88
17830 8450
2.1
3.5
4.0
99.
25090 16530
630
3.4
0.1
35
3.9
96
20030 10895
2.2
3.5
4.1
109
30880 19670
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Steel Flat Wire Armoured Cables
Nom.
Nom.
Armour
Nom.
Approx.
CrossBedding
Wire
Sheath
Overall
Section
Thickness Size Thickness Diameter
Area
Double Steel Tape Armoured Cables
Approx.
Weight
CU
mm²
mm
mm
mm
mm
16
1.2
0.8
2.2
39.7
2795
25
1.3
0.8
2.2
42.7
35
1.3
0.8
2.3
45.2
50
1.4
0.8
2.4
70
1.5
0.8
2.5
AL
kg/km
Nom.
Bedding
Thickness
No of Steel
Nom.
Approx.
tapes x
Sheath
Overall
nom tape
Thickness Diameter
thickness
Approx.
Weight
CU
AL
mm
mm
mm
mm
kg/km
2515
1.2
2x0.5
2.3
40.5
2680
2395
3305
2885
1.3
2x0.5
2.4
43.7
3195
2775
3835
3215
1.3
2x0.5
2.5
46.2
3720
3100
47.8
4325
3570
1.4
2x0.5
2.6
48.8
4200
3445
51.8
5320
4185
1.5
2x0.5
2.7
52.8
5185
4050
95
1.5
0.8
2.7
56.1
6450
4875
1.5
2x0.5
2.8
56.9
6280
4700
120
1.6
0.8
2.8
59.7
7545
5510
1.6
2x0.5
2.9
60.5
7360
5325
150
1.7
0.8
2.9
63.1
8610
6150
1.7
2x0.5
3.0
63.9
8420
5950
185
1.7
0.8
3.0
67.4
10120
6995
1.7
2x0.5
3.1
68.2
9910
6780
240
1.8
0.8
3.2
73.0
12430
8205
1.8
2x0.5
3.3
73.8
12200
7970
300
1.9
0.8
3.3
78.3
14775
9455
1.9
2x0.5
3.4
79.1
14530
9200
400
2.0
0.8
3.5
85.2
17950
11190
2.0
2x0.8
3.7
87.7
18600
11850
500
2.1
0.8
3.7
92.8
21970 13270
2.1
2x0.8
3.9
95.3
22680
13990
630
2.2
0.8
4.0
102.7
27480 16160
2.2
2x0.8
4.1
105.0
28200
16910
www.addison-cables.com
51
Caledonian Medium Voltage Cables
Electrical Data
Nom.
CrossSection
Area
DC
AC
Resistance Resistance
CU / AL
CU / AL
Short Circuit
Rating of
Conductor
CU / AL
1 sec
Capaci- Charging
tance
Current
Short Circuit
Rating of
Copper Wire
Screen Per
Core
1 sec
Short Circuit
Rating of
Copper Wire
Screen Per
Core
1 sec
Reactance
Inductance
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
16
1150/1910
1470/2420
2.2/1.4
186
0.40
2.6
0.5
131
410
25
727/1200
927/1538
3.6/2.3
216
0.43
2.6
0.5
123
390
35
524/868
668/1113
5.0/3.2
237
0.47
2.6
0.6
115
370
50
387/641
494/822
6.8/4.4
266
0.52
2.6
0.6
109
350
70
268/443
343/568
9.8/6.3
298
0.60
2.6
0.7
103
330
95
193/320
248/410
13.3/8.5
334
0.67
2.6
0.7
99
320
120
153/253
196/325
17.2/11.0
365
0.73
2.6
0.8
96
310
150
124/206
159/265
21.2/13.5
392
0.78
4.3
0.8
93
300
185
99.1/164
128/211
26.6/17.0
430
0.86
4.3
0.9
90
290
240
75.4/125
98/161
34.9/22.3
476
0.95
4.3
0.9
87
280
300
60.1/100
80/130
43.8/28.0
524
1.05
4.3
1.0
85
270
400
47.0/77.8
64/102
57.3/36.6
580
1.16
5.8
1.1
81
260
500
36.6/60.5
51/81
72.3/46.2
630
1.26
5.8
1.2
78
250
630
28.3/46.9
42/64
91.2/58.3
690
1.36
5.8
1.3
76
240
Medium Voltage Cables to IEC 60502
Three Core 8.7/15KV (Um=17.5KV)
Dimensional Data
Unarmoured Cables
Steel Round-Wire Armoured Cables
Approx.
Weight
Copper
Nom.
Nom.
Approx.
Nom.
Copper
Wire
CrossSheath
Overall
Insulation
Tape
Screen
Section
Thickness Diameter
Thickness Thickness
Area*
Area
CU
AL
Nom.
Armour
Nom.
Bedding
Wire
Sheath
Thickness Size Thickness
kg/km
Approx.
Overall
Diameter
Approx.
Weight
CU
AL
mm²
mm
mm
mm²
mm
mm
mm
mm
mm
mm
25
4.5
0.1
16
2.4
44
2100
1620
1.4
2.5
2.7
52
4560
kg/km
4080
35
4.5
0.1
16
2.5
46
2510
1840
1.4
2.5
2.7
54
5080
4410
50
4.5
0.1
16
2.6
49
2980
2080
1.5
2.5
2.9
57
5740
4840
70
4.5
0.1
16
2.7
53
3760
2470
1.6
2.5
3.0
62
6770
5480
95
4.5
0.1
16
2.8
57
4700
2900
1.6
2.5
3.1
65
7890
6100
120
4.5
0.1
16
3.0
60
5590
3320
1.7
2.5
3.2
69
8970
6700
150
4.5
0.1
25
3.1
64
6560
3760
1.8
3.15
3.4
74
11030
8220
185
4.5
0.1
25
3.2
67
7800
4300
1.8
3.15
3.5
78
12490
8980
240
4.5
0.1
25
3.4
74
9820
5220
1.9
3.15
3.7
84
15040
10440
300
4.5
0.1
25
3.5
79
11800 6010
2.0
3.5
3.8
90
17920
12130
400
4.5
0.1
35
3.7
86
14620 7240
2.1
3.5
4.1
98
21360
13970
500
4.5
0.1
35
3.8
93
18160 9355
2.2
3.5
4.3
106
26490
17830
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Steel Flat Wire Armoured Cables
Nom.
CrossSection
Area
mm²
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
mm
mm
mm
mm
Double Steel Tape Armoured Cables
Approx.
Weight
CU
AL
kg/km
No of Steel
Nom.
Approx.
Nom.
tapes x
Sheath
Overall
Bedding
Nom Tape
Thickness Diameter
Thickness
Thickness
mm
mm
mm
mm
Approx.
Weight
CU
AL
kg/km
25
1.4
0.8
2.4
48.0
3915
3495
1.4
2x0.5
2.5
48.8
3770
3345
35
1.4
0.8
2.5
50.8
4510
3890
1.4
2x0.5
2.6
51.6
4350
3735
50
1.5
0.8
2.6
53.3
5020
4270
1.5
2x0.5
2.7
54.1
4855
4105
70
1.6
0.8
2.7
57.0
5990
4870
1.6
2x0.5
2.8
57.8
5815
4690
95
1.6
0.8
2.8
61.2
7170
5600
1.6
2x0.5
3.0
62.2
7010
5435
120
1.7
0.8
2.9
65.1
8340
6320
1.7
2x0.5
3.1
66.1
8170
6145
150
1.8
0.8
3.0
68.3
9440
6955
1.8
2x0.5
3.2
69.3
9260
6770
185
1.8
0.8
3.2
72.8
10990
7880
1.8
2x0.5
3.3
73.6
10760
7650
240
1.9
0.8
3.3
78.3
13370
9155
1.9
2x0.5
3.4
79.1
13120
8900
300
2.0
0.8
3.5
83.7
15760 10460
2.0
2x0.8
3.6
86.0
16360
11070
400
2.1
0.8
3.7
90.5
19050 12260
2.1
2x0.8
3.9
93.0
19750
12960
500
2.2
0.8
3.9
98.2
23160 14430
2.2
2x0.8
4.1
100.7
23900
15190
www.addison-cables.com
53
Caledonian Medium Voltage Cables
Electrical Data
Nom.
DC
AC
CrossResistance Resistance
Section
CU / AL
CU / AL
Area
Short Circuit
Short Circuit
Short Circuit
Rating of
Rating of
Rating of Copper
Charging
Copper Tape
Conductor Capacitance
Wire Screen
Reactance Inductance
Current
Screen Per
CU / AL
Per Core
Core
1 sec
1 sec
1 sec
mm²
µΩm
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩm
nH/m
25
727/1200
927/1538
3.6/2.3
176
0.48
2.6
0.6
132
410
35
524/868
668/1113
5.0/3.2
193
0.53
2.6
0.6
123
390
50
387/641
494/822
6.8/4.4
211
0.58
2.6
0.7
116
370
70
268/443
343/568
9.8/6.3
240
0.65
2.6
0.7
110
350
95
193/320
248/410
13.3/8.5
267
0.73
2.6
0.8
105
330
120
153/253
196/325
17.2/11.0
291
0.79
2.6
0.8
102
320
150
124/206
159/265
21.2/13.5
312
0.85
4.3
0.9
98
310
185
99.1/164
128/211
26.6/17.0
340
0.93
4.3
0.9
95
300
240
75.4/125
98/161
34.9/22.3
375
1.02
4.3
1.0
91
290
300
60.1/100
80/130
43.8/28.0
411
1.12
4.3
1.1
89
280
400
47.0/77.8
64/102
57.3/36.6
454
1.24
5.8
1.2
84
270
500
36.6/60.5
51/81
72.3/46.2
504
1.34
5.8
1.3
78
250
Three Core12/20KV (Um=24KV)
Dimensional Data
Unarmoured Cables
Copper
Nom.
Nom.
Approx.
Nom.
Copper
Wire
CrossSheath
Overall
Insulation
Tape
Screen
Section
Thickness Diameter
Thickness Thickness
Area*
Area
Steel Round-Wire Armoured Cables
Approx.
Weight
CU
AL
kg/km
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness
Size Thickness Diameter
Approx.
Weight
CU
AL
mm²
mm
mm
mm²
mm
mm
mm
mm
mm
mm
35
5.5
0.1
16
2.7
51
2850
2180
1.5
2.5
2.9
60
5700
kg/km
5010
50
5.5
0.1
16
2.8
54
3340
2450
1.6
2.5
3.0
62
6370
5480
70
5.5
0.1
16
2.9
58
4150
2850
1.6
2.5
3.1
66
7370
6070
95
5.5
0.1
16
3.0
62
5110
3310
1.7
3.15
3.3
72
9400
7600
120
5.5
0.1
16
3.1
65
5990
3730
1.8
3.15
3.4
75
10530
8270
150
5.5
0.1
25
3.2
68
6980
4180
1.8
3.15
3.5
80
11800
8940
185
5.5
0.1
25
3.3
72
8240
4740
1.9
3.15
3.7
83
13350
9850
240
5.5
0.1
25
3.6
79
10310
5700
2.0
3.5
3.8
90
16430 11820
300
5.5
0.1
25
3.7
84
12360
6570
2.1
3.5
4.0
95
18870 13080
400
5.5
0.1
35
3.9
91
15220
7830
2.2
4.0
4.3
103
23260 15930
500
5.5
0.1
35
4.1
97
19105 10325
2.3
4.2
4.5
110
27800 19170
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Medium Voltage Cables to IEC 60502
Steel Flat Wire Armoured Cables
Nom.
CrossSection
Area
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness
Size
Thickness Diameter
Double Steel Tape Armoured Cables
Approx.
Weight
CU
mm²
mm
mm
mm
mm
35
1.5
0.8
2.7
55.7
5150
50
1.6
0.8
2.8
58.2
5675
70
1.6
0.8
2.9
61.9
95
1.7
0.8
3.0
66.4
120
1.8
0.8
3.1
150
1.8
0.8
185
1.9
0.8
240
2.0
300
2.1
400
500
AL
No of Steel
Nom.
Approx.
Nom.
tapes x
Sheath
Overall
Bedding
nom tape
Thickness Diameter
Thickness
thickness
kg/km
Approx.
Weight
CU
AL
mm
mm
mm
mm
kg/km
4530
1.5
2x0.5
2.8
56.5
4975
4355
4935
1.6
2x0.5
2.9
59.0
5495
4750
6685
5570
1.6
2x0.5
3.0
62.7
6490
5375
7945
6390
1.7
2x0.5
3.1
67.2
7735
6180
70.0
9110
7103
1.8
2x0.5
3.2
70.8
8890
6880
3.2
73.2
10240
7770
1.8
2x0.5
3.3
74.0
10010 7535
3.3
77.7
11840
8750
1.9
2x0.5
3.4
78.5
11600 8500
0.8
3.5
83.2
14270
10070
2.0
2x0.8
3.6
85.5
14870 10680
0.8
3.6
88.6
16730
11440
2.1
2x0.8
3.8
91.1
17400 12130
2.2
0.8
3.9
95.6
20130
13350
2.2
2x0.8
4.0
97.9
20820 14050
2.3
0.8
4.1
103.3
24310
15600
2.3
2x0.8
4.2
105.6
25050 16350
Short Circuit
Rating of
Copper Wire
Screen Per
Core
1 sec
Short Circuit
Rating of
Copper Tape
Screen Per
Core
1 sec
Reactance
Inductance
Electrical Data
Nom.
CrossSection
Area
DC
AC
Resistance Resistance
CU / AL
CU / AL
Short Circuit
Rating of
Conductor
CU / AL
1 sec
Capacitance
Charging
Current
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
35
524/868
668/1113
5.0/3.2
168
0.67
2.6
0.7
129
410
50
387/641
494/822
6.8/4.4
183
0.73
2.6
0.8
122
390
70
268/443
343/568
9.8/6.3
207
0.83
2.6
0.8
115
370
95
193/320
248/410
13.3/8.5
229
0.92
2.6
0.9
110
350
120
153/253
196/325
17.2/11.0
249
1.00
2.6
0.9
106
340
150
124/206
159/265
21.2/13.5
266
1.06
4.3
1.0
103
330
185
99.1/164
128/211
26.6/17.0
289
1.16
4.3
1.0
100
320
240
75.4/125
98/161
34.9/22.3
318
1.27
4.3
1.1
95
300
300
60.1/100
80/130
43.8/28.0
348
1.39
4.3
1.2
93
290
400
47.0/77.8
64/102
57.3/36.6
388
1.53
5.8
1.3
87
280
500
36.6/60.5
51/81
72.3/46.2
422
1.67
5.8
1.4
78
250
www.addison-cables.com
55
Caledonian Medium Voltage Cables
Three Core 18/30KV (Um=36KV)
Dimensional Data
Unarmoured Cables
Steel Round-Wire Armoured Cables
Copper
Nom.
Approx.
Approx.
Nom.
Approx.
Nom.
Armour
Nom.
Approx.
Nom.
Copper
Wire
CrossWeight
Weight
Sheath
Overall
Bedding
Wire
Sheath
Overall
Insulation
Tape
Screen
Section
Thickness Diameter CU
Thickness
Size
Thickness
Diameter
Thickness Thickness
AL
CU
AL
Area*
Area
mm²
mm
mm
mm²
mm
mm
kg/km
mm
mm
mm
mm
kg/km
50
8.0
0.1
16
3.2
65
4340 3460
1.8
3.15
3.5
75
8950 8080
70
8.0
0.1
16
3.3
70
5220 3930
1.9
3.15
3.6
80
10150 8860
95
8.0
0.1
16
3.4
74
6240 4440
1.9
3.15
3.7
84
11390 9590
120
8.0
0.1
16
3.5
77
7180 4910
2.0
3.5
3.8
89
13200 10860
150
8.0
0.1
25
3.6
80
8220 5420
2.1
3.5
4.0
92
14520 11720
185
8.0
0.1
25
3.7
84
9540 6040
2.1
4.0
4.1
97
17020 13510
240
8.0
0.1
25
3.9
91
11720 7110
2.2
4.0
4.3
104
19810 15200
300
8.0
0.1
25
4.0
95
13790 8000
2.3
4.5
4.5
108
23310 17470
400
8.0
0.1
35
4.3
103
16820 9430
2.4
4.5
4.7
117
27010 19620
500
8.0
0.1
35
4.5
110
21550 12880
2.5
4.5
4.9
124
31130 22610
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Steel Flat Wire Armoured Cables
Double Steel Tape Armoured Cables
No of Steel
Nom.
Approx.
Approx.
Nom.
Approx.
Nom.
Armour
Nom.
Approx.
Nom.
tapes x
CrossWeight
Weight
Sheath
Overall
Bedding
Wire
Sheath
Oveall
Bedding
nom tape
Section
Thickness
Diameter
Thickness
Size Thickness Diameter CU
Thickness
AL
CU
AL
thickness
Area
mm²
mm
mm
mm
mm
kg/km
mm
mm
mm
mm
kg/km
50
1.8
0.8
3.1
70.2
7490 6775
1.8
2x0.5
3.3
71.2
7300
6585
70
1.9
0.8
3.2
74.0
8590 7540
1.9
2x0.5
3.4
75.0
8390
7335
95
1.9
0.8
3.4
78.5
9990 8460
1.9
2x0.5
3.5
79.3
9740
8210
120
2.0
0.8
3.5
82.2
11250 9270
2.0
2x0.8
3.6
84.5
11845 9875
150
2.1
0.8
3.6
85.6
12510 10070
2.1
2x0.8
3.7
87.9
13120 10700
185
2.1
0.8
3.7
89.8
14155 11100
2.1
2x0.8
3.9
92.3
14850 11800
240
2.2
0.8
3.8
95.4
16740 12575
2.2
2x0.8
4.0
97.9
17480 13320
300
2.3
0.8
4.0
100.9
19310 14120
2.3
2x0.8
4.2
103.4
20080 14900
400
2.4
0.8
4.2
107.8
22840 16170
2.4
2x0.8
4.4
110.3
23660 17000
500
2.5
0.8
4.4
115.5
27200 18610
2.5
2x0.8
4.6
118.0
28080 19510
Electrical Data
Nom.
DC
AC
CrossResistance Resistance
Section
CU / AL
CU / AL
Area
mm²
50
70
95
120
150
185
240
300
400
500
µΩ/m
387/641
268/443
193/320
153/253
124/206
99.1/164
75.4/125
60.1/100
47.0/77.8
36.6/60.5
µΩ/m
494/822
343/568
248/410
196/325
159/265
128/211
98/161
80/130
64/102
51/81
Short Circuit
Short Circuit
Rating of
Rating of
Charging
Conductor Capacitance
Copper Wire
Current
CU / AL
Screen Per
1 sec
Core 1 sec
kA
6.8/4.4
9.8/6.3
13.3/8.5
17.2/11.0
21.2/13.5
26.6/17.0
34.9/22.3
43.8/28.0
57.3/36.6
72.3/46.2
pF/m
142
159
175
189
201
217
237
258
282
302
mA/m
0.85
0.95
1.05
1.13
1.21
1.3
1.42
1.55
1.69
1.79
kA
2.6
2.6
2.6
2.6
4.3
4.3
4.3
4.3
5.8
5.8
Short Circuit
Rating of
Copper Tape
Screen Per
Core 1 sec
kA
1.0
1.0
1.1
1.1
1.2
1.2
1.3
1.4
1.5
1.6
Reactance Inductance
µΩ/m
134
127
121
117
113
109
104
101
96
78
nH/m
430
400
390
370
360
350
330
320
290
250
Medium Voltage Cables to IEC 60502
Three Core 21/35KV (Um=42KV)
Dimensional Data
Unarmoured Cables
Copper
Nom.
Nom.
Approx.
Nom.
Copper
Wire
CrossSheath
Overall
Insulation
Tape
Screen
Section
Thickness Diameter
Thickness Thickness
Area*
Area
Steel Round-Wire Armoured Cables
Approx.
Weight
CU
mm²
mm
mm
mm²
mm
mm
50
9.3
0.1
16
3.2
73.9
5320
70
9.3
0.1
16
3.3
78.0
95
9.3
0.1
16
3.5
81.9
120
9.3
0.1
16
3.6
150
9.3
0.1
25
185
9.3
0.1
240
9.3
0.1
300
9.3
400
9.3
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness
Size Thickness Diameter
AL
kg/km
Approx.
Weight
CU
AL
mm
mm
mm
mm
kg/km
4446
1.9
3.15
3.8
87.1
10970
10090
6166
4880
2.0
3.5
3.9
91.3
12220
10750
7144
5430
2.1
3.5
4.0
94.5
13560
11780
85.1
8232
6049
2.1
4.0
4.1
97.5
14880
13650
3.7
88.6
9273
6549
2.1
4.0
4.2
100.5
16150
14060
25
3.8
93.5
10845 7392
2.2
4.0
4.3
105.5
17840
14390
25
4.0
98.2
12675 8310
2.3
4.5
4.5
111.5
20410
15870
0.1
25
4.1
103.6
14960 9362
2.4
4.5
4.6
116.5
24100
18460
0.1
35
4.3
110.0
18055 10698
2.5
4.5
4.8
124.3
28680
20560
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Steel Flat Wire Armoured Cables
Nom.
Nom.
Armour
Nom.
Approx.
CrossBedding
Wire
Sheath
Oveall
Section
Thickness Size
Thickness Diameter
Area
mm²
mm
mm
mm
mm
Approx.
Weight
CU
AL
kg/km
Double Steel Tape Armoured Cables
No of Steel
Approx.
Nom.
Approx.
Nom.
tapes x
Weight
Sheath
Overall
Bedding
nom tape
Thickness Diameter
Thickness
CU
AL
thickness
mm
mm
mm
mm
kg/km
50
1.9
0.8
3.3
80.5
9825
8986
1.9
2x0.5
3.5
82.5
9625
8786
70
2.0
0.8
3.6
85.5
11015
9769
2.0
2x0.8
3.8
87.6
10825
9569
95
2.1
0.8
3.8
88.5
12360 10580
2.1
2x0.8
3.9
90.5
12116
10327
120
2.1
0.8
3.9
91.5
13900 11715
2.1
2x0.8
4.0
94.5
13306
11110
150
2.1
0.8
4.0
94.8
15160 12440
2.1
2x0.8
4.1
97.5
14550
11830
185
2.2
0.8
4.1
99.5
17500 13450
2.2
2x0.8
4.2
101.7
16810 12765
240
2.3
0.8
4.2
104.1
19390 14890
2.3
2x0.8
4.4
107.5
18650 14150
300
2.4
0.8
4.4
109.5
21970 16280
2.4
2x0.8
4.6
112.8
21200 15500
400
2.5
0.8
4.6
116.3
25600 18430
2.5
2x0.8
4.8
118.8
24780 17600
Electrical Data
Nom.
CrossSection
Area
DC
AC
Resistance Resistance
CU / AL
CU / AL
Short Circuit
Short Circuit
Rating of
Rating of
Charging
Conductor Capacitance
Copper Wire
Current
CU / AL
Screen Per
1 sec
Core 1 sec
Short Circuit
Rating of
Copper Tape Reactance Inductance
Screen Per
Core 1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
50
387/641
494/822
6.8/4.4
135
0.91
2.6
1.1
140
450
70
268/443
343/568
9.8/6.3
151
1.01
2.6
1.1
134
415
95
193/320
248/410
13.3/8.5
166
1.11
2.6
1.2
126
405
120
153/253
196/325
17.2/11.0
179
1.21
2.6
1.2
123
385
150
124/206
159/265
21.2/13.5
189
1.29
4.3
1.3
118
375
185
99.1/164
128/211
26.6/17.0
202
1.38
4.3
1.3
114
365
240
75.4/125
98/161
34.9/22.3
221
1.49
4.3
1.4
109
345
300
60.1/100
80/130
43.8/28.0
240
1.65
4.3
1.5
105
335
400
47.0/77.8
64/102
57.3/36.6
267
1.75
5.8
1.6
101
305
www.addison-cables.com
57
Caledonian Medium Voltage Cables
Three Core 26/35KV (Um=42KV)
Dimensional Data
Unarmoured Cables
Copper
Nom.
Approx.
Nom.
Approx.
Nom.
Copper
Wire
CrossWeight
Sheath Overall
Insulation
Tape
Screen
Section
Thickness Diameter CU
Thickness Thickness
AL
Area*
Area
mm²
mm
mm
mm²
mm
mm
kg/km
Steel Round-Wire Armoured Cables
Nom.
Armour
Nom.
Approx.
Bedding
Wire
Sheath
Overall
Thickness Size Thickness Diameter
Approx.
Weight
CU
AL
mm
mm
mm
mm
kg/km
50
10.5
0.1
16
3.4
79.7
5928
5053
1.9
3.5
4.0
93.5
12050 11150
70
10.5
0.1
16
3.5
83.6
6900
5634
2.0
4.0
4.1
97.5
13150 11850
95
10.5
0.1
16
3.6
87.2
7863
6131
2.1
4.0
4.2
101.5
14800 12950
120
10.5
0.1
16
3.8
90.7
8817
6634
2.2
4.0
4.4
105.5
16050 13800
150
10.5
0.1
25
3.9
94.1
10085 7361
2.3
4.5
4.5
108.5
17420 14640
185
10.5
0.1
25
4.0
99.1
11573
8120
2.3
4.5
4.6
112
19200 15700
240
10.5
0.1
25
4.1
103.6
13387 9023
2.4
4.5
4.7
117
21050 16800
300
10.5
0.1
25
4.3
109.2
15658 10060
2.5
4.5
4.8
122.5
24900 19100
400
10.5
0.1
35
4.5
115.6
19013 11657
2.6
4.5
5.1
129
29200 21560
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Steel Flat Wire Armoured Cables
Nom.
Approx.
Nom.
Armour
Nom.
Approx.
CrossWeight
Bedding
Wire
Sheath
Oveall
Section
Thickness Size Thickness Diameter CU
AL
Area
mm²
mm
mm
mm
mm
kg/km
Double Steel Tape Armoured Cables
Nom.
No of Steel
Nom.
Approx.
Bedding
tapes x nom
Sheath
Overall
Thickness tape thickness Thickness Diameter
mm
mm
mm
mm
Approx.
Weight
CU
AL
kg/km
50
1.9
0.8
3.5
86.5
10880
9990
1.9
2x0.8
3.7
87.5
10690
70
2.0
0.8
3.6
90.5
12000 10795
2.0
2x0.8
3.8
91.4
10800 10590
9800
95
2.1
0.8
3.8
94.0
13360 11570
2.1
2x0.8
3.9
95.2
13110 11327
120
2.2
0.8
3.9
96.4
13705 12710
2.2
2x0.8
4.0
98.7
14300 12110
15550 12800
150
2.3
0.8
4.0
99.5
16160 13440
2.3
2x0.8
4.1
102.1
185
2.3
0.8
4.1
105.1
18505 14465
2.3
2x0.8
4.2
107.3
17810 13765
240
2.4
0.8
4.2
109.8
20390 15890
2.4
2x0.8
4.4
112.2
19650 15150
300
2.5
0.8
4.4
115.5
22970 17280
2.5
2x0.8
4.6
118.0
22200 16500
400
2.6
0.8
4.6
122.1
26600 19430
2.6
2x0.8
4.8
124.6
25780 18600
Electrical Data
Nom.
CrossSection
Area
DC
AC
Resistance Resistance
CU / AL
CU / AL
Short Circuit
Short Circuit
Rating of
Rating of
Charging Copper Wire
Conductor Capacitance
Current
Screen Per
CU / AL
Core
1 sec
1 sec
Short Circuit
Rating of
Copper Tape
Reactance Inductance
Screen Per
Core
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
50
387/641
494/822
6.8/4.4
131
0.97
2.6
1.2
146
470
70
268/443
343/568
9.8/6.3
145
1.07
2.6
1.2
139
430
95
193/320
248/410
13.3/8.5
158
1.18
2.6
1.3
132
420
120
153/253
196/325
17.2/11.0
169
1.26
2.6
1.3
128
400
150
124/206
159/265
21.2/13.5
178
1.36
4.3
1.4
123
390
185
99.1/164
128/211
26.6/17.0
185
1.44
4.3
1.4
118
380
240
75.4/125
98/161
34.9/22.3
203
1.57
4.3
1.5
113
360
300
60.1/100
80/130
43.8/28.0
219
1.72
4.3
1.6
109
350
400
47.0/77.8
64/102
57.3/36.6
245
1.85
5.8
1.7
105
320
Medium Voltage Cables to IEC 60502
Current Rating for Three Core 1.8/3KV(Um=7.2 )KV to 26/35KV(Um=42KV) XLPE Insulation
Unarmored
Nom.
CrossSection
Area
Buried direct in
Ground
CU
mm²
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Laid in Single Way
Duct
AL
CU
53
78
100
119
140
171
203
232
260
294
340
384
438
498
568
62
87
112
133
158
193
231
264
297
336
390
441
501
541
591
A
76
101
129
153
181
221
262
298
334
377
434
489
553
613
663
Armored
Laid in Air
Buried direct in
Ground
AL
CU
AL
CU
42
67
87
103
122
150
179
205
231
262
305
346
398
451
501
87
109
142
170
204
253
304
351
398
455
531
606
696
786
896
62
84
110
132
158
196
236
273
309
355
415
475
552
652
762
76
101
129
154
181
220
263
298
332
374
431
482
541
601
651
A
A
Laid in Single Way
Duct
AL
CU
53
78
100
119
140
171
204
232
259
293
338
380
432
492
562
63
88
112
134
158
194
232
264
296
335
387
435
492
532
582
A
Laid in Air
AL
CU
43
68
87
104
123
150
180
206
231
262
304
343
393
446
496
88
110
143
172
205
253
307
352
397
453
529
599
683
773
883
A
AL
A
63
85
111
133
159
196
238
274
309
354
415
472
545
645
755
Current Rating for Three Core 1.8/3KV(Um=7.2 )KV to 26/35KV(Um=42KV) EPR Insulation
Unarmored
Nom.
CrossSection
Area
Buried direct in
Ground
CU
mm²
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Laid in Single Way
Duct
AL
CU
51
76
97
116
137
167
200
227
255
289
335
378
432
492
562
59
84
109
130
154
189
227
258
291
330
384
434
494
534
584
A
73
98
125
150
176
216
258
292
328
371
429
482
545
605
655
Armored
Laid in Air
Buried direct in
Ground
AL
CU
AL
CU
40
65
84
101
119
147
176
201
226
257
300
340
392
445
495
82
104
135
164
195
243
296
339
385
441
519
590
678
768
878
58
80
105
127
151
189
229
263
299
343
406
462
538
638
749
73
98
125
150
177
216
257
292
327
368
424
475
534
594
644
A
A
Laid in Single Way
Duct
AL
CU
51
76
97
116
137
168
200
227
254
288
332
374
426
486
556
60
85
109
131
155
190
227
259
291
328
381
429
485
525
575
A
Laid in Air
AL
CU
41
66
85
101
120
147
176
201
226
257
299
338
387
440
490
82
104
136
164
197
244
296
339
385
439
513
583
666
756
862
A
AL
A
59
81
105
127
153
190
230
264
300
343
402
459
530
630
741
▓▓ Current Rating Conditions:
Ground Temperature: 20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8 m
Thermal Resistance of Soil: 1.5K•m/W
www.addison-cables.com
59
Caledonian
Medium Voltage
Cables
I
IV
II
III
IV
Medium Voltage Cables to VDE 0276
Single Core Cables To VDE 0276
Three Core Cables To VDE 0276
V
Medium Voltage Cables to VDE 0276
Single Core Cables to VDE 0276
▓▓ APPLICATIONS:
The single core cables are designed for distribution
of electrical power with nominal voltage Uo/U
ranging from 3.8/6.6KV to 19/33KV and frequency
50Hz. They are suitable for installation mostly
in power supply stations, indoors and in cable
ducts, outdoors, underground and in water as well
as for installation on cable trays for industries,
switchboards and power stations.
▓▓ STANDARD:
DIN VDE 0276 Part 620 -622
HD 620 S1
PVC/PE/LSZH Oversheath
Aluminium Wire Armour(optional)
Binder
XLPE Insulation
Conductor
Conductor Screen
Insulation Screen
Metallic Screen
PVC/PE/LSZH Separation Sheath(optional)
▓▓ CONSTRUCTION:
Conductor: Stranded compacted circular copper or aluminium conductors according to IEC
60228 class 2 / VDE 0276 class 2 / VDE 0295 HD 383. All internal interstices of the conductor
are filled with water blocking compound to prevent ingress of water through conductor during
storage, handing, installation and operation of the cable.
Conductor Screen: The conductor screen consists of an extruded layer of non metallic,
semi-conducting compound firmly bonded to the insulation to exclude all air voids. The screen
has a minimum thickness of 0.3mm and the maximum volume resistivity of 500 Ohm-m at
90°C.
Insulation: Insulation is of extruded XLPE compound type 2XI1 according to DIN VDE 0207
part 22 and HD 620.1 with high degree of cross-linking, free from contaminants, air voids and
heat resistant by dry cured process.
The nominal insulation wall thickness is shown in table 1.
www.addison-cables.com
61
Caledonian Medium Voltage Cables
Table 1. Insulation Thickness
Insulation Thickness at Nom. Voltage
Nom. Cross
Section Area
3.6/6KV(Um=7.2kV)
6/10kV(Um=12kV)
8.7/15kV(Um=17.5kV)
12/20kV(Um=24kV)
18/30kv(Um=36kV)
mm²
mm
mm
mm
mm
mm
35
2.5
3.4
4.5
5.5
-
50
2.5
3.4
4.5
5.5
8.0
70
2.5
3.4
4.5
5.5
8.0
95
2.5
3.4
4.5
5.5
8.0
120
2.5
3.4
4.5
5.5
8.0
150
2.5
3.4
4.5
5.5
8.0
185
2.5
3.4
4.5
5.5
8.0
240
2.6
3.4
4.5
5.5
8.0
300
2.8
3.4
4.5
5.5
8.0
400
3.0
3.4
4.5
5.5
8.0
Insulation Screen: The insulation screen consists of extruded non metallic, semi-conducting
compound extruded over the insulation. The extruded semi-conducting layer shall consist
of bonded or cold strippable semi-conducting compound capable of removal for jointing or
terminating.The minimum thickness is 0.3mm and the maximum volume resistivity of 500
Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can
be easily hand stripped on site.
Conducting Water Blocking Layer: The insulation screen may be coverd by semiconductive water blocking tape which will swell up under the influence of moisture of water to
ensure longitudinal watertightness.
Metallic Screen: Copper wires are applied over the conducting water blocking layer with a
minimum diameter of 0.5mm. And over the copper wires, copper tape with minimum thickness
of 0.1mm is applied helically with overlap. Total cross section of metallic screen layer is
shown in table 2. The screen can withstand fault current to earth of 1000 A for one second at
maximum temperature of 160°C. Minimum cross section of concentric conductor is according
to DIN VDE 0273 & 0276 as shown.
Table 2. Minimum Total Cross Section of Metallic Screen
Nominal Cross-Section Area
Of Cable
Minimum Cross-Section
of Metallic Screen
DC Resistance of the Copper Wire Screen
mm²
mm²
mm
Up to 120
16
1.06
150-300
25
0.72
400-630
35
0.51
800-1000
50
0.35
Separator / Water Blocking Layer: The metallic screen may be covered by non-conducting
water blocking tape which will swell up under the influence of moisture of water to ensure
longitudinal watertightness.
Separation Sheath (for armoured cable): The separation sheath comprises a layer of
extruded PVC, PE or LSZH, applied under the armour. Thickness of separation sheath as
shown in table 3.
Medium Voltage Cables to VDE 0276
Table 3. Separation Sheath Thickness
Core Diameter
Approx.Thickess of Inner Sheath
mm
mm
>
<
35
45
1.4
45
60
1.6
60
80
1.8
80
-
2.0
Armour (for armoured cable): The armour consists of round aluminium wire armour applied
helically over an extruded separation sheath.
Table 4. Round Armour Wire Diameter
Fictitious Diameter Under the Armour
Armour Wire Diameter
mm
mm
>
<
-
10
0.8
10
15
1.25
15
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15
Outer Sheath: Overall sheath comprises a layer of extruded PE compound DMP2 according
to HD620.1 and 2YM3 type to DIN VDE 0276 Part 3, or PVC compound DMV6 according
to HD620.1 and YM5 to DIN VDE 0276 Part 6. Normal wall thickness is 2.5mm (1/500mm
18/30sq 2.6mm), suitable for exposure to sun-light or other local atmospheric environments
and for the operating temperature of the cable.
▓▓ PHYSICAL PROPERTIES:
Operating Temperature: up to 90°C
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds)
Bending Radius: 15 x OD (Cable without metal sheath)
30 x OD (Cable with aluminium sheath)
Table 5. Nominal /Operating /Testing Voltages
Nominal Voltage Uo/U
Operating Voltage (max)
Testing Voltage
3.6/6KV
8KV
10KV
6/10KV
12KV
15KV
8.7/15KV
18KV
22.5KV
12/20KV
24KV
30KV
18/30KV
36KV
45KV
www.addison-cables.com
63
Caledonian Medium Voltage Cables
▓▓ TYPE CODES:
Cores
N
According to VDE Standard (No abbreviation for copper conductor)
A
Aluminium Conductor
2X
XLPE Insulation
Y
PVC Insulation
Screen
S
Screen of copper wires and copper tape, helically wound.
SE
Screen of copper wire plus copper tape over each individual cores, helically wound
(F)
Longitudinally waterproof screen.
Concentric Conductor Screen
C
Concentric conductor screen of copper wires and copper tape, helically wound.
CE
Concentric conductor screen of copper wire plus copper tape over each individual
cores, helically wound.
Jacket
2Y
PE Jacket
Y
PVC Jacket
H
LSZH Jacket
Medium Voltage Cables to VDE 0276
Single Core 1.8/3KV (Um=3.6KV)
Dimensional Data
Copper
Nom.
Nom.
Nom.
Nom.
Copper
Wire
CrossSheath
Overall N2XSY/
Insulation
Tape
Screen
Section
Thickness Diameter N2XSH
Thickness Thickness
Area*
Area
Cu
Approx. Weight
NA2XSY/
NA2XSH
Al
N2XS2Y
Cu
NA2XS2Y N2XS (F) 2Y NA2XS (F)
Al
Cu
2Y Al
mm²
mm
mm
mm²
mm
mm
kg / km
kg / km
kg / km
kg / km
kg / km
kg / km
25
2.0
0.1
16
1.4
13
500
180
480
140
500
230
35
2.0
0.1
16
1.4
14
620
280
600
240
620
330
50
2.0
0.1
16
1.4
15
700
380
750
290
750
430
70
2.0
0.1
16
1.5
17
900
480
800
380
1000
560
95
2.0
0.1
16
1.5
19
1200
590
1050
460
1300
670
120
2.0
0.1
16
1.6
21
1450
700
1300
550
1500
800
150
2.0
0.1
25
1.6
22
1700
800
1550
650
1800
900
185
2.0
0.1
25
1.7
24
2050
850
1900
750
2150
950
240
2.0
0.1
25
1.8
27
2550
1050
2350
900
2650
1150
300
2.0
0.1
25
1.8
29
3150
1250
2950
1050
3250
1350
400
2.0
0.1
35
1.9
32
3950
1550
3800
1450
4100
1650
500
2.2
0.1
35
2.0
35
5000
2000
4800
1800
5200
2150
630
2.4
0.1
35
2.2
38
6200
2200
6300
2100
6400
2350
800
2.6
0.1
35
2.3
44
8000
2900
7900
2800
8200
3050
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Impedance
Short
Circuit
Circuit
Circuit
Nom.
Inductance
Rating of Rating of Reactance
DC
AC
Rating of Capaci- Charging
CrossFlat
Copper Copper
Resistance Resistance
Trefoil
Conductor tance Current
Section
Spaced
Wire
Tape
CU / AL
CU / AL
CU / AL
Area
Screen Screen
1 sec
Trefoil Flat Trefoil Flat
cu AL cu AL
1 sec
1 sec
Spaced
Spaced
mm²
µΩ/m
µΩm
kA
pF/m
mA/m
kA
kA
25
727/1200
929/1538
3.6/2.3
222
0.32
2.6
0.3
131
µΩ/m
35
524/868
668/1113
5.0/3.2
251
0.35
2.6
0.4
122
178
50
387/641
494/822
6.8/4.4
281
0.39
2.6
0.4
116
172
70
268/443
343/568
9.8/6.3
341
0.45
2.6
0.5
110
165
185
nH/m
345
µΩ/ m
µΩ/ m
535
936 1544 952 1554
327
524
679 1121 695 1131
313
514
511 834 527 844
300
495
364 583 386 597
95
193/320
248/410
13.3/8.5
397
0.50
2.6
0.5
104
160
287
485
272 427 300 446
120
153/253
196/325
17.2/11.0
430
0.55
2.6
0.6
104
159
280
475
225 345 257 367
150
124/206
159/265
21.2/13.5
464
0.59
4.3
0.6
100
156
274
465
193 287 229 313
185
99.1/164
128/211
26.6/17.0
513
0.65
4.3
0.7
98
154
267
459
165 237 206 267
240
75.4/125
98/161
34.9/22.3
573
0.70
4.3
0.9
94
150
260
455
140 191 185 226
300
60.1/100
80/130
43.8/28.0
652
0.72
4.3
1.0
91
147
253
445
128 163 174 203
400
47.0/77.8
64/102
57.3/36.6
727
0.75
5.8
1.1
90
147
248
435
113 141 164 184
500
36.6/60.5
51/81
72.3/46.2
754
0.79
5.8
1.2
89
145
245
425
105 124 158 171
630
28.3/46.9
42/64
91.2/58.3
786
0.87
5.8
1.3
86
143
243
415
97
110 151 160
www.addison-cables.com
65
Caledonian Medium Voltage Cables
SIngle Core 3.6/6KV (Um=7.2 KV)
Dimensional Data
Copper
Nom.
Nom.
Nom.
Nom.
Copper
Wire
CrossSheath
Overall
Insulation
Tape
Screen
Section
Thickness Diameter
Thickness Thickness
Area*
Area
mm²
mm
mm
mm²
mm
mm
Approx. Weight
N2XSY/ NA2XSY/
N2XS2Y
N2XSH NA2XSH
Cu
Cu
Al
kg / km kg / km kg / km
NA2XS2Y N2XS (F) 2Y NA2XS (F) 2Y
Al
Cu
Al
kg / km
kg / km
kg / km
25
2.5
0.1
16
1.5
18
700
480
600
550
700
560
35
2.5
0.1
16
1.6
20
820
580
800
560
900
660
50
2.5
0.1
16
1.6
21
1000
680
900
570
1050
750
70
2.5
0.1
16
1.7
23
1200
770
1100
650
1300
850
95
2.5
0.1
16
1.7
24
1500
890
1350
760
1550
990
120
2.5
0.1
16
1.8
26
1850
1000
1700
850
1900
1150
150
2.5
0.1
25
1.8
27
2100
1100
1950
1050
2200
1250
185
2.5
0.1
25
1.9
29
2450
1250
2300
1200
2550
1300
240
2.6
0.1
25
1.9
32
3050
1550
2850
1400
3150
1650
300
2.8
0.1
25
2.0
35
3650
1850
3450
1650
3750
1950
400
3.0
0.1
35
2.1
38
4550
2250
4400
2050
4700
2350
500
3.2
0.1
35
2.3
42
5700
2700
5500
2500
5900
2850
630
3.2
0.1
35
2.4
48
7090
3020
6890
2820
7290
3200
800
3.2
0.1
35
2.5
52
8900
3700
8700
3500
9100
3850
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Reactance
Inductance
Impedance
Short
Circuit Circuit
Circuit
Rating Rating
Nom.
DC
AC
Rating of Capaci- Charging
of
of
CrossFlat
Resistance Resistance
Trefoil
Conductor tance Current Copper Copper
Section
Spaced
Flat
Flat
CU / AL
CU / AL
CU / AL
Wire
Tape Trefoil Spaced Trefoil Spaced
Area
1 sec
Screen Screen
CU AL CU AL
1 sec
1 sec
mm²
µΩ/m
µΩm
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
µΩ/ m
µΩ/m
16
1150/1910 1460/2420
2.2/1.4
232
0.29
2.6
0.4
152
205
410
600
25
727/1200
927/1538
3.6/2.3
262
0.32
2.6
0.4
142
196
400
590
1462 2411 1478 2420
936 1544 952 1554
35
524/868
668/1113
5.0/3.2
291
0.35
2.6
0.5
133
187
390
580
679 1121 695 1131
50
387/641
494/822
6.8/4.4
321
0.39
2.6
0.5
121
179
380
570
511 834 527 844
70
268/443
343/568
9.8/6.3
371
0.45
2.6
0.6
115
173
370
550
364 583 386 597
95
193/320
248/410
13.3/8.5
417
0.50
2.6
0.6
110
168
350
540
272 427 300 446
120
153/253
196/325
17.2/11.0
459
0.55
2.6
0.7
107
165
340
520
225 345 257 367
150
124/206
159/265
21.2/13.5
494
0.59
4.3
0.7
103
161
330
510
193 287 229 313
185
99.1/164
128/211
26.6/17.0
543
0.65
4.3
0.8
100
158
320
500
165 237 206 267
240
75.4/125
98/161
34.9/22.3
583
0.70
4.3
0.9
97
155
310
490
140 191 185 226
300
60.1/100
80/130
43.8/28.0
602
0.72
4.3
1.0
95
153
300
490
126 163 174 203
400
47.0/77.8
64/102
57.3/36.6
627
0.75
5.8
1.1
92
150
290
480
113 141 164 184
105 124 158 171
500
36.6/60.5
51/81
72.3/46.2
654
0.79
5.8
1.2
90
147
290
470
630
28.3/46.9
42/64
91.2/58.3
726
0.87
5.8
1.3
87
145
280
460
97
110 151 160
800
22.1/36.7
35/55
114.4/75.0
786
0.91
5.8
1.4
85
143
270
460
92
101 147 153
* For capacitance & charging current values, multiply values shown by 1.2 for EPR insulated cables.
Medium Voltage Cables to VDE 0276
Single Core 6/10KV (Um=12 KV)
Dimensional Data
Approx. Weight
Copper
Nom.
Nom.
Nom.
Nom.
Copper
Wire
CrossSheath
Overall N2XSY/ NA2XSY/ N2XS2Y NA2XS2Y N2X (F) 2Y
Insulation
Tape
Screen
Section
Thickness Diameter N2XSH NA2XSH
Thickness Thickness
Cu
Al
Cu
Area*
Area
Cu
Al
mm²
mm
mm
mm
mm
mm
kg / km
kg / km
kg / km
kg / km
NA2XS (F) 2Y
Al
kg / km
kg / km
25
3.4
0.1
16
1.6
25
820
580
720
550
900
650
35
3.4
0.1
16
1.6
25
920
680
900
570
980
750
50
3.4
0.1
16
1.7
26
1100
780
950
670
1150
850
70
3.4
0.1
16
1.7
28
1300
870
1200
750
1400
950
95
3.4
0.1
16
1.8
30
1600
990
1450
860
1650
1100
120
3.4
0.1
16
1.8
32
1950
1100
1800
950
2050
1250
150
3.4
0.1
25
1.9
33
2200
1200
2050
1150
2300
1350
185
3.4
0.1
25
1.9
34
2550
1350
2400
1300
2650
1500
240
3.4
0.1
25
2.0
36
3150
1650
2950
1500
3250
1750
300
3.4
0.1
25
2.1
38
3750
1950
3550
1750
3850
2050
400
3.4
0.1
35
2.2
43
4650
2350
4500
2150
4800
2450
500
3.4
0.1
35
2.3
45
5800
2800
5700
2600
6000
2950
630
3.4
0.1
35
2.4
50
7300
3100
7010
2950
7500
3300
800
3.4
0.1
35
2.5
50
9100
3900
8900
3700
9300
4000
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short
Short
Inductance
Impedance
Short
Circuit Circuit Reactance
Circuit
Rating Rating
Nom.
DC
AC
Rating of Capaci- Charging
of
of
CrossFlat
Resistance Resistance
Trefoil
Conductor tance Current Copper Copper
Section
Spaced
Flat
Flat
CU / AL
CU / AL
CU / AL
Wire
Tape Trefoil Spaced Trefoil Spaced
Area
1 sec
Screen Screen
CU AL CU AL
1 sec
1 sec
mm²
µΩ/m
µΩm
kA
pF/m
mA/m
kA
kA
25
727/1200
927/1538
3.6/2.3
208
0.42
2.6
0.5
144
µΩ/m
210
460
nH/m
660
35
524/868
668/1113
5.0/3.2
229
0.46
2.6
0.6
136
200
440
640
50
387/641
494/822
6.8/4.4
252
0.50
2.6
0.6
131
195
420
620
936 1544 952 1554
679 1121 695 1131
511 834 527 844
µΩ/ m
µΩ/m
70
268/443
343/568
9.8/6.3
288
0.58
2.6
0.7
122
188
390
600
364
95
193/320
248/410
13.3/8.5
323
0.65
2.6
0.7
122
182
390
580
272
120
153/253
196/325
17.2/11.0
353
0.71
2.6
0.8
116
172
370
550
225
150
124/206
159/265
21.2/13.5
380
0.76
4.3
0.8
110
166
350
530
193
185
99.1/164
128/211
26.6/17.0
416
0.83
4.3
0.9
107
166
340
530
240
75.4/125
98/161
34.9/22.3
460
0.92
4.3
0.9
104
163
330
300
60.1/100
80/130
43.8/28.0
506
1.01
4.3
1.0
100
157
400
47.0/77.8
64/102
57.3/36.6
561
1.12
5.8
1.1
94
500
36.6/60.5
51/81.0
72.3/46.2
619
1.24
5.8
1.2
630
28.3/46.9
42/64.0
91.2/58.3
698
1.37
5.8
800
22.1/36.7
35/55
114.4/75.0
780
1.39
5.8
583
386
597
427
300
446
345
257
367
287
229
313
165
237
206
267
520
140
191
185
226
320
500
126
163
174
203
154
300
490
113
141
164
184
91
151
290
480
105
124
158
171
1.3
91
148
290
470
97
110
151
160
1.4
88
144
280
470
92
101
147
153
www.addison-cables.com
67
Caledonian Medium Voltage Cables
Singke Core 8.7/15KV (Um=17.5KV)
Dimensional Data
Approx. Weight
Copper
Nom.
Nom.
Nom.
Nom.
Copper
Wire
CrossSheath
Overall N2XSY/ NA2XSY/ N2XS2Y NA2XS2Y N2XS (F) 2Y
Insulation
Tape
Screen
Section
Thickness Diameter N2XSH NA2XSH
Thickness Thickness
Cu
Al
Cu
Area*
Area
Cu
Al
mm²
mm
mm
mm
mm
mm
kg / km
kg / km
kg / km
kg / km
NA2XS (F) 2Y
Al
kg / km
kg / km
25
4.5
0.1
16
1.7
26
900
600
880
500
900
700
35
4.5
0.1
16
1.7
26
1020
700
1000
600
1060
800
50
4.5
0.1
16
1.7
27
1200
880
1050
770
1250
950
70
4.5
0.1
16
1.8
29
1400
970
1300
850
1500
1050
95
4.5
0.1
16
1.8
31
1700
1090
1550
960
1750
1200
120
4.5
0.1
16
1.9
32
2050
1200
1900
1150
2100
1300
150
4.5
0.1
25
1.9
33
2300
1400
2150
1250
2400
1500
185
4.5
0.1
25
2.0
35
2650
1650
2500
1400
2750
1750
240
4.5
0.1
25
2.1
37
3250
1750
3050
1600
3350
1850
300
4.5
0.1
25
2.1
39
3850
2050
3650
1850
3950
2150
400
4.5
0.1
35
2.3
43
4850
2550
4700
2250
5000
2550
500
4.5
0.1
35
2.3
45
5900
2900
5700
2600
6100
3050
630
4.5
0.1
35
2.5
51
7500
3200
7200
3100
8000
3400
800
4.5
0.1
35
2.6
51
9300
4200
9100
4000
9500
4300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short Short
Reactance
Inductance
Short
Circuit Circuit
Circuit
Rating Rating
Nom.
DC
AC
Rating of Capaci- Charging
of
of
CrossResistance Resistance
Conductor tance Current Copper Copper
Section
Flat
Trefoil
CU / AL
CU / AL
CU / AL
Wire
Tape Trefoil Spaced Spaced Flat
Area
1 sec
Screen Screen
1 sec 1 sec
mm²
µΩ/m
µΩm
kA
pF/m
mA/m
kA
kA
25
727/1200
927/1538
3.6/2.3
171
0.47
2.6
0.6
µΩ/m
35
524/868
668/1113
5.0/3.2
187
0.51
2.6
0.6
141
207
460
660
50
387/641
494/822
6.8/4.4
204
0.57
2.6
0.7
138
195
440
640
150
210
nH/m
480
680
Impedance
Trefoil
Flat
Spaced
CU
CU
AL
µΩ/ m
AL
µΩ/m
936 1544 952 1554
679 1121 695 1131
511 834 527 844
70
268/443
343/568
9.8/6.3
232
0.63
2.6
0.7
132
188
420
600
364
583
386
597
95
193/320
248/410
13.3/8.5
258
0.71
2.6
0.8
126
182
400
580
272
427
300
446
120
153/253
196/325
17.2/11.0
281
0.74
2.6
0.8
119
179
380
570
225
345
257
367
150
124/206
159/265
21.2/13.5
301
0.79
4.3
0.9
113
176
360
560
193
287
229
313
185
99.1/164
128/211
26.6/17.0
329
0.87
4.3
0.9
110
170
350
540
165
237
206
267
240
75.4/125
98/161
34.9/22.3
363
0.96
4.3
1.0
107
166
340
530
140
191
185
226
300
60.1/100
80/130
43.8/28.0
398
1.03
4.3
1.1
104
160
330
510
126
163
174
203
400
47.0/77.8
64/102
57.3/36.6
439
1.17
5.8
1.2
97
157
310
500
113
141
164
184
500
36.6/60.5
51/81
72.3/46.2
483
1.28
5.8
1.3
94
154
300
490
105
124
158
171
630
28.3/46.9
42/64
91.2/58.3
534
1.42
5.8
1.4
91
151
290
480
97
110
151
160
800
22.1/36.7
35/55
114.4/75.0
590
1.61
5.8
1.4
91
147
290
470
92
101
147
153
Medium Voltage Cables to VDE 0276
Single Core 12/20KV (Um=24KV)
Dimensional Data
Approx. Weight
Copper
Nom.
Nom.
Nom.
Nom.
Copper
Wire
CrossSheath
Overall N2XSY/ NA2XSY/ N2XS2Y NA2XS2Y N2XS (F) 2Y NA2XS (F) 2Y
Insulation
Tape
Screen
Section
Thickness Diameter N2XSH NA2XSH
Thickness Thickness
Cu
Al
Cu
Al
Area*
Area
Cu
Al
mm²
mm
mm
mm
mm
mm
kg / km
kg / km
kg / km
kg / km
25
5.5
0.1
16
1.8
29
1000
35
5.5
0.1
16
1.8
30
1100
kg / km
kg / km
750
900
850
1050
630
1100
850
730
1200
950
50
5.5
0.1
16
1.8
31
1250
970
1150
830
1350
1050
70
5.5
0.1
16
1.9
33
1500
1100
1350
920
1600
1200
95
5.5
0.1
16
1.9
34
1800
1200
1650
1050
1900
1300
120
5.5
0.1
16
2.0
35
2150
1350
1900
1150
2250
1450
150
5.5
0.1
25
2.0
37
2400
1500
2250
1350
2500
1650
185
5.5
0.1
25
2.1
38
2800
1700
2600
1550
2900
1800
240
5.5
0.1
25
2.1
42
3400
1900
3200
1750
3500
2050
300
5.5
0.1
25
2.2
43
4000
2200
3800
2000
4150
2300
400
5.5
0.1
35
2.3
44
4950
2600
4750
2400
5100
2800
500
5.5
0.1
35
2.4
46
6050
3000
5800
2800
6200
3200
630
5.5
0.1
35
2.5
50
8150
3600
8050
3400
8300
3750
800
5.5
0.1
35
2.6
53
9600
4400
9450
4200
9800
4300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short Short
Inductance
Impedance
Short
Circuit Circuit Reactance
Circuit
Rating Rating
Nom.
DC
AC
Rating of Capaci- Charging
of
of
CrossFlat
Resistance Resistance
Trefoil
Conductor tance Current Copper Copper
Section
Spaced
Flat
Flat
CU / AL
CU / AL
CU / AL
Wire
Tape Trefoil Spaced Trefoil Spaced
Area
1 sec
Screen Screen
Cu AL Cu AL
1 sec 1 sec
mm²
µΩ/m
µΩm
kA
pF/m
mA/m
kA
kA
25
727/1200
927/1538
3.6/2.3
142
0.62
2.6
0.6
µΩ/m
35
524/868
668/1113
5.0/3.2
162
0.65
2.6
0.7
150
207
50
387/641
494/822
6.8/4.4
177
0.71
2.6
0.8
141
201
162
214
nH/m
490
µΩ/ m
µΩ/m
680
936 1544 952 1554
470
660
679 1121 695 1131
450
640
511
834 527 844
70
268/443
343/568
9.8/6.3
200
0.80
2.6
0.8
135
195
430
620
364 583 386 597
95
193/320
248/410
13.3/8.5
222
0.89
2.6
0.9
129
188
410
600
272 427 300 446
120
153/253
196/325
17.2/11.0
241
0.96
2.6
0.9
122
182
390
580
225 345 257 367
150
124/206
159/265
21.2/13.5
257
1.03
4.3
1.0
116
176
370
560
193 287 229 313
185
99.1/164
128/211
26.6/17.0
280
1.12
4.3
1.0
116
173
370
550
165 237 206 267
240
75.4/125
98/161
34.9/22.3
307
1.23
4.3
1.1
110
170
350
540
140 191 185 226
300
60.1/100
80/130
43.8/28.0
336
1.34
4.3
1.2
107
166
340
530
126 163 174 203
400
47.0/77.8
64/102
57.3/36.6
370
1.48
5.8
1.3
100
160
320
510
113
500
36.6/60.5
51/81
72.3/46.2
406
1.62
5.8
1.4
97
154
310
490
105 124 158 171
630
28.3/46.9
42/64
91.2/58.3
449
1.80
5.8
1.5
94
151
300
480
97
110
800
22.1/36.7
35/55
114.4/75.0
490
1.85
5.8
1.6
91
151
290
480
92
101 147 153
141 164 184
www.addison-cables.com
151 160
69
Caledonian Medium Voltage Cables
Single Core 18/30KV (Um=36KV)
Dimensional Data
Copper
Nom.
Nom.
Nom.
Nom.
Copper
Wire
CrossSheath Overall
Insulation
Tape
Screen
Section
Thickness Diameter
Thickness Thickness
Area*
Area
Approx. Weight
N2XSY/
N2XSH
Cu
NA2XSY/
NA2XSH
Al
N2XS2Y NA2XS2Y N2XS (F) 2Y NA2XS (F) 2Y
Cu
Al
Cu
Al
kg / km
mm²
mm
mm
mm
mm
mm
kg / km
kg / km
kg / km
kg / km
25
8.0
0.1
16
1.9
30
1300
1050
35
8.0
0.1
16
1.9
30
1400
1150
50
8.0
0.1
16
2.0
35
1550
1250
70
8.0
0.1
16
2.0
37
1750
95
8.0
0.1
16
2.1
39
2050
120
8.0
0.1
16
2.1
41
150
8.0
0.1
25
2.2
42
185
8.0
0.1
25
2.2
240
8.0
0.1
25
2.3
300
8.0
0.1
25
400
8.0
0.1
35
500
8.0
0.1
630
8.0
0.1
800
8.0
0.1
kg / km
1100
900
1400
1150
1200
1000
1500
1250
1350
1100
1650
1350
1350
1600
1200
1900
1450
1500
1900
1300
2150
1600
2350
1600
2150
1450
2450
1750
2700
1850
2550
1650
2750
1950
44
3100
2000
2900
1800
3150
2150
46
3700
2250
3500
2050
3800
2400
2.4
49
4350
2550
4150
2300
4400
2700
2.5
52
5350
3000
5100
2750
5450
3200
35
2.6
54
6450
3450
6200
3150
6550
3650
35
2.7
59
8300
3780
8100
3600
8600
4100
35
2.8
59
9900
4500
9700
4320
10300
4800
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Short Short
Short
Circuit Circuit Reactance Inductance
Circuit
Rating Rating
Nom.
DC
AC
Rating
Capaci- Charging
of
of
CrossResistance Resistance
of
tance Current Copper Copper
Section
CU / AL
CU / AL Conductor
Wire
Tape Trefoil Flat Trefoil Flat
Area
CU / AL
Screen Screen
1 sec
1 sec 1 sec
mm²
nH/m
Trefoil
Flat spaced
Cu
Cu
AL
µΩ/ m
AL
µΩ/m
727/1200
µΩ/m
927/1538
kA
3.6/2.3
pF/m
mA/m
kA
kA
121
0.71
2.6
0.9
159
229
530
720
686
1247
759
1146
50
387/641
494/822
6.8/4.4
138
0.83
2.6
1.0
151
214
480
680
511
834
527
844
70
268/443
343/568
9.8/6.3
154
0.92
2.6
1.0
144
201
460
640
364
583
386
597
95
193/320
248/410
13.3/8.5
169
1.01
2.6
1.1
138
195
440
620
272
427
300
446
120
153/253
196/325
17.2/11.0
183
1.10
2.6
1.1
132
188
420
600
225
345
257
367
150
124/206
159/265
21.2/13.5
194
1.16
4.3
1.2
126
182
400
580
193
287
229
313
185
99.1/164
128/211
26.6/17.0
210
1.26
4.3
1.2
122
182
390
580
165
237
206
267
240
75.4/125
98/161
34.9/22.3
229
1.37
4.3
1.3
119
176
380
560
140
191
185
226
300
60.1/100
80/130
43.8/28.0
249
1.49
4.3
1.4
113
173
360
550
126
163
174
203
400
47.0/77.8
64/102
57.3/36.6
273
1.64
5.8
1.5
107
163
340
520
113
141
164
184
500
36.6/60.5
51/81
72.3/46.2
298
1.79
5.8
1.6
104
163
330
520
105
124
158
171
630
28.3/46.9
42/64
91.2/58.3
327
1.96
5.8
1.7
99
160
320
510
97
110
151
160
800
22.1/36.7
35/55
114.4/75.0
350
1.98
5.8
1.8
98
154
310
490
92
101
147
153
25
µΩ/m
Impedance
µΩ/ m
Medium Voltage Cables to VDE 0276
Current Rating for Single Core 1.8/3KV(Um=3.6KV ) to 18/30KV(Um=36KV) XLPE Insulation
Nom.
CrossSection
Area
Buried direct in Ground
Trefoil
CU
mm²
10
Flat spaced
AL
CU
59
87
A
84
Laid in Single Way Duct
Trefoil
AL
CU
62
78
A
Flat touching
AL
CU
55
98
A
Laid in Air
Trefoil
AL
CU
56
103
A
Flat Touching
Flat spaced
AL
CU
AL
CU
75
106
77
122
A
A
AL
A
88
16
109
84
113
88
103
80
104
81
125
97
128
99
150
116
25
140
108
144
112
132
102
133
103
163
127
167
130
196
153
35
166
129
172
134
157
122
159
123
198
154
203
157
238
185
50
196
152
203
157
186
144
188
146
238
184
243
189
286
222
70
239
186
246
192
227
176
229
178
296
230
303
236
356
278
95
285
221
293
229
271
210
274
213
361
280
369
287
434
338
120
323
252
332
260
308
240
311
242
417
324
426
332
500
391
150
361
281
366
288
343
267
347
271
473
368
481
376
559
440
185
406
317
410
324
387
303
391
307
543
424
550
432
637
504
240
469
367
470
373
447
351
453
356
641
502
647
511
745
593
300
526
414
524
419
504
397
510
402
735
577
739
586
846
677
400
590
470
572
466
564
451
571
457
845
673
837
676
938
769
500
650
530
672
546
604
504
661
537
935
773
938
776
1118
919
630
700
600
882
646
654
554
771
617
1045
883
1048
886
1318
1089
800
750
660
1002
756
694
594
871
717
1145
983
1148
986
1528
1279
1000
800
720
1112
856
724
644
971
807
1235
1083
1238
1086
1738
1469
www.addison-cables.com
71
Caledonian Medium Voltage Cables
Three Core Cables to VDE 0276
▓▓ APPLICATIONS:
The three core cables are designed for distribution
of electrical power with nominal voltage Uo/U
ranging from 3.6/6.6KV to 19/33KV and frequency
50Hz. They are suitable for installation mostly
in power supply stations, indoors and in cable
ducts, outdoors, underground and in water as well
as for installation on cable trays for industries,
switchboards and power stations.
▓▓ STANDARD:
DIN VDE 0276 Part 620 -622
HD 620 S1
PVC/PE/LSZH Oversheath
PVC/PE/LSZH Separation Sheath(optional)
Metallic Screen
Insulation Screen
XLPE Insulation
Conductor
Conductor Screen
Binder
Armour(optional)
▓▓ CONSTRUCTION:
Conductor: Stranded compacted circular copper or aluminium conductors according to IEC
60228 class 2 / VDE 0276 class 2. VDE 0295 HD 383. All internal interstices of the conductor
are filled with water blocking compound to prevent ingress of water through conductor during
storage, handing, installation and operating of the cable.
Conductor Screen: The conductor screen consists of an extruded layer of non metallic,
semi-conducting compound firmly bonded to the insulation to exclude all air voids. The screen
has a minimum thickness of 0.3mm and the maximum volume resistivity of 500 Ohm-m at
90°C.
Insulation: Insulation is of extruded XLPE compound type 2XI1 according to DIN VDE 0207
part 22 and HD 620.1 with high degree of cross-linking, free from contaminants, air voids and
heat resistant by dry cured process.
The nominal insulation wall thickness is shown in table 1.
Medium Voltage Cables to VDE 0276
Table 1. Insulation Thickness
Nom. Cross-Section
Area
mm²
Insulation Thickness at Nom. Voltage
3.6/6kV
(Um=7.2)kV
6/10KV
(Um=12KV)
8.7/15KV
(Um=17KV)
12/20KV
(Um=24KV)
18/30KV
(Um=36KV)
mm
mm
mm
mm
mm
XLPE
XLPE
XLPE
XLPE
XLPE
35
2.5
3.4
4.5
5.5
-
50
2.5
3.4
4.5
5.5
8.0
70
2.5
3.4
4.5
5.5
8.0
95
2.5
3.4
4.5
5.5
8.0
120
2.5
3.4
4.5
5.5
8.0
150
2.5
3.4
4.5
5.5
8.0
185
2.5
3.4
4.5
5.5
8.0
240
2.6
3.4
4.5
5.5
8.0
300
2.8
3.4
4.5
5.5
8.0
400
3.0
3.4
4.5
5.5
8.0
Insulation Screen: The insulation screen consists of extruded non metallic, semi-conducting
compound extruded over the insulation. The extruded semi-conducting layer shall consist
of bonded or cold strippable semi-conducting compound capable of removal for jointing or
terminating. The minimum thickness is 0.3mm and the maximum volume resistivity of 500
Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can
be easily hand stripped on site.
Conducting Water Blocking Layer: The insulation screen may be covered by semiconductive water blocking tape which will swell up under the influence of moisture of water to
ensure longitudinal watertightness.
Metallic Screen: Copper wires are applied over the conducting water blocking layer with
a minimum diameter of 0.5mm. And over the copper wires, copper tape with minimum
thickness of 0.1mm is applied helically with overlap. Total cross section of metallic screen
layer is shown in table 2. The screen can withstand of fault current to earth of 1000 A for one
second at maximum temperature of 160°C. Minimum cross section of concentric conductor is
according to DIN VDE 0273 & 0276 as shown.
Table 2. Minimum Total Cross Section of Metallic Screen
Nominal Cross-Section Area Of Cable
Minimum Cross-Section
of Metallic Screen
DC Resistance of the Copper Wire Screen
mm²
mm²
mm
Up to 120
16
1.06
150-300
25
0.72
400-630
35
0.51
800-1000
50
0.35
Separator / Water Blocking Layer: The metallic screen may be covered by non-conducting
water blocking tape which will swell up under the influence of moisture of water to ensure
longitudinal watertightness.
Separation Sheath (for armoured cable): The separation sheath comprises a layer of
extruded PVC, PE or LSZH, applied under the armour. Thickness of separation sheath is
shown in table 3.
www.addison-cables.com
73
Caledonian Medium Voltage Cables
Table 3. Separation Sheath Thickness
Cores Diameter
mm
>
35
45
60
80
Approx.Thickess of Inner Sheath
mm
<
45
60
80
-
1.4
1.6
1.8
2.0
Armour(for armoured cable):
The armour consists of:
1) Double layers of galvanized steel tape are applied helically with proper inner overlapping
over an extruded separation sheath. Thickness of the steel tape is shown in table 4.
Tabel 4. Galvanized Steel Tape Thickness
Inner Diameter
mm
>
30
70
Thickness of Galvanized Steel Tape
mm
<
30
70
-
0.2
0.5
0.8
2) Galvanized flat steel wires with thickness of 0.8 mm are applied helically over the surface
of inner sheath with minimum of 90% coverage. And galvanized Steel tape with nominal
thickness of 0.3 mm is applied helically with 50% coverage to cover the surface of the flat
wires.
Outer Sheath: Overall sheath comprises a layer of extruded PE compound DMP2 according
to HD620.1 and 2YM3 type to DIN VDE 0276 Part 3, or PVC compound DMV6 according
to HD620.1 and YM5 to DIN VDE 0276 Part 6. Normal wall thickness is 2.5mm (1/500mm
18/30sq 2.6mm), suitable for exposure to sun-light or other local atmospheric environments
and for the operating temperature of the cable.
▓▓ PHYSICAL PROPERTIES:
Operating Temperature: up to 90°C
Temperature Range: -5°C ( PVC sheath ); -20°C ( PE sheath )
Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds)
Bending Radius: 15 x OD (Cable without metal sheath)
30 x OD (Cable with aluminium sheath)
Table 5. Nominal /Operating /Testing Voltages
Nominal Voltage Uo/U
Operating Voltage (Um)
Testing Voltage
3.6/6KV
8KV
12.5KV
6/10KV
12KV
21KV
8.7/15KV
18KV
30.5KV
12/20KV
24KV
42KV
18/30KV
36KV
63KV
Medium Voltage Cables to VDE 0276
▓▓ TYPE CODES:
Conductor
N
According to VDE Standard (No abbreviation for copper conductor)
A
Aluminium conductor
Copper conductor
Insulation
2X
XLPE
Screen
C
Concentric conductor of copper
CE
Concentric conductor of copper over each individual core
S
Screen of copper wires & copper tape, helically wound
SE
Screen of copper wires over each individual cores
(G)
Longitudinally waterproof
Armour
F
Armour of galvanized flat steel wire
G
Counter Helix of galvanized steel tape
B
Steel tape armouring
R
Armour of galvanized round steel wire
Sheath
2Y
PE
Y
PVC
H
LSZH
K
Lead sheath
KL
Aluminium sheath
www.addison-cables.com
75
Caledonian Medium Voltage Cables
Three Core 3.6/6KV (Um=7.2KV)
N2XSEY
NA2XSEY
Dimensional Data
Nom.
CrossSection
Area
Approx.
Nom.
Conductor Insulation
Diameter Thickness
Copper
Tape
Thickness
Copper
Wire
Screen
Area*
Approx.
Insulation
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Cu
Al
Approx. Weight
mm²
mm
mm
mm
mm²
mm
mm
mm
kg / km
kg / km
25
6.05
2.5
0.1
16
12.5
1.5
37
2100
1600
35
7.10
2.5
0.1
16
13.5
1.6
39
2500
1800
50
8.25
2.5
0.1
16
14.7
1.6
42
3000
2100
70
9.90
2.5
0.1
16
16.3
1.7
46
3800
2500
95
11.7
2.5
0.1
16
18.1
1.7
50
4800
3000
120
13.1
2.5
0.1
16
19.5
1.8
53
5800
3500
150
14.3
2.5
0.1
25
20.7
1.8
56
6700
3900
185
16.3
2.5
0.1
25
22.7
1.9
60
8100
4600
240
18.7
2.6
0.1
25
25.3
1.9
66
10200
5600
300
20.9
2.8
0.1
25
27.9
2.0
72
12500
6700
400
23.7
3.0
0.1
35
31.1
2.1
80
15600
8200
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Three Core 3.6/6KV (Um=7.2KV) Galvanized Steel Tape Armoured Cables
N2XSEYBY
NA2XSEYBY
Dimensional Data
Nom.
CrossSection
Area
Approx.
Nom.
Copper
Conductor Insulation
Tape
Diameter Thickness Thickness
Copper
Wire
Screen
Area*
Approx.
Nom.
Nom.
Approx.
Insulation Armour
Sheath
Overall
Diameter Thickness Thickness Diameter
Approx. Weight
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
mm
kg / km
kg / km
25
6.05
2.5
0.1
16
12.5
0.5
2.2
39
2800
2300
35
7.10
2.5
0.1
16
13.5
0.5
2.3
42
3200
2600
50
8.25
2.5
0.1
16
14.7
0.5
2.4
45
3800
2900
70
9.90
2.5
0.1
16
16.3
0.5
2.5
49
4700
3400
95
11.7
2.5
0.1
16
18.1
0.5
2.6
53
5800
4000
120
13.1
2.5
0.1
16
19.5
0.5
2.7
56
6800
4600
150
14.3
2.5
0.1
25
20.7
0.5
2.8
59
7900
5100
185
16.3
2.5
0.1
25
22.7
0.8
2.9
64
9400
5900
240
18.7
2.6
0.1
25
25.3
0.8
3.1
70
11700
7000
300
20.9
2.8
0.1
25
27.9
0.8
3.3
76
14100
8300
400
23.7
3.0
0.1
35
31.1
0.8
3.6
85
18300
10900
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Medium Voltage Cables to VDE 0276
Three Core 3.6/6KV (Um=7.2KV) Galvanized Flat Steel wire+Steel Tape Armoured Cables
N2XSEYFGbY
NA2XSEYFGbY
Dimensional Data
Nom.
CrossSection
Area
mm²
Approx.
Nom.
Copper
Conductor Insulation
Tape
Diameter Thickness Thickness
mm
mm
mm
Copper
Wire
Screen
Area*
Approx.
Insulation
Diameter
Nom.
Armour
Thickness
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
mm²
mm
mm
mm
mm
Approx. Weight
Cu
Al
kg / km
kg / km
25
6.05
2.5
0.1
16
12.5
0.8
2.2
40
2900
2400
35
7.10
2.5
0.1
16
13.7
0.8
2.3
42
3300
2700
50
8.25
2.5
0.1
16
14.7
0.8
2.4
45
3900
3000
70
9.90
2.5
0.1
16
16.3
0.8
2.5
49
4900
3600
95
11.7
2.5
0.1
16
18.1
0.8
2.6
53
6000
4200
120
13.1
2.5
0.1
16
19.5
0.8
2.7
56
7000
4700
150
14.3
2.5
0.1
25
20.7
0.8
2.8
59
8100
5200
185
16.3
2.5
0.1
25
22.7
0.8
2.9
64
9600
6100
240
18.7
2.6
0.1
25
25.3
0.8
3.1
70
11900
7200
300
20.9
2.8
0.1
25
27.9
0.8
3.3
76
14300
8600
400
23.7
3.0
0.1
35
31.1
0.8
3.6
84
17700
10300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Nom.
DC
AC
CrossResistance Resistance
Section
CU / AL
CU / AL
Area
Short Circuit
Short Circuit
Rating of
Rating of
Charging Copper Wire
Conductor Capacitance
Current
Screen
CU / AL
Per Core
1 sec
1 sec
Short Circuit
Rating of
Copper Tape
Screen
Per Core
1 sec
Reactance
Inductance
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
25
727/1200
927/1538
3.6/2.3
272
0.33
2.6
0.4
116
370
35
524/868
668/1113
5.0/3.2
301
0.36
2.6
0.5
108
350
50
387/641
494/822
6.8/4.4
332
0.40
2.6
0.5
102
330
70
268/443
343/568
9.8/6.3
383
0.46
2.6
0.6
97
310
95
193/320
248/410
13.3/8.5
432
0.52
2.6
0.6
92
290
120
153/253
196/325
17.2/11.0
474
0.57
2.6
0.7
89
280
150
124/206
159/265
21.2/13.5
511
0.61
4.3
0.7
87
280
185
99.1/164
128/211
26.6/17.0
562
0.67
4.3
0.8
86
270
240
75.4/125
98/161
34.9/22.3
602
0.72
4.3
0.9
83
260
300
60.1/100
80/130
43.8/28.0
622
0.75
4.3
1.0
82
260
400
47.0/77.8
64/102
57.3/36.6
648
0.78
5.8
1.1
80
250
www.addison-cables.com
77
Caledonian Medium Voltage Cables
Three Core 6/10KV (Um=12KV)
N2XSEY
NA2XSEY
Dimensional Data
Approx.
Conductor
Diameter
Nom.
Insulation
Thickness
Copper
Tape
Thickness
Copper
Wire
Screen
Area*
mm²
mm
mm
mm
25
6.05
3.4
0.1
35
7.10
3.4
0.1
Nom.
CrossSection
Area
Approx.
Insulation
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
mm²
mm
mm
16
14.3
1.6
16
15.3
1.6
Approx. Weight
Cu
Al
mm
kg / km
kg / km
41
2400
1900
43
2800
2200
50
8.25
3.4
0.1
16
16.5
1.7
46
3400
2500
70
9.90
3.4
0.1
16
18.1
1.7
50
4200
2900
95
11.7
3.4
0.1
16
19.9
1.8
54
5300
3400
120
13.1
3.4
0.1
16
21.3
1.8
57
6200
3900
150
14.3
3.4
0.1
25
22.5
1.9
60
7200
4400
185
16.3
3.4
0.1
25
24.5
1.9
64
8600
5100
240
18.7
3.4
0.1
25
26.9
2.0
70
10700
6100
300
20.9
3.4
0.1
25
29.1
2.1
75
12900
7100
400
23.7
3.4
0.1
35
31.9
2.2
81
15900
8500
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Three Core 6/10KV (Um=12KV) Galvanized Steel Tape Armoured Cables
N2XSEYBY
NA2XSEYBY
Dimensional Data
Nom.
CrossSection
Area
Approx.
Conductor
Diameter
Nom.
Insulation
Thickness
Copper
Tape
Thickness
Copper
Wire
Screen
Area*
Approx.
Insulation
Diameter
mm²
mm
mm
mm
mm²
mm
mm
mm
Nom.
Nom.
Approx.
Armour
Sheath
Overall
Thickness Thickness Diameter
Approx. Weight
Cu
Al
mm
kg / km
kg / km
25
6.05
3.4
0.1
16
14.3
0.5
2.3
44
3200
2700
35
7.10
3.4
0.1
16
15.3
0.5
2.4
46
3700
3000
50
8.25
3.4
0.1
16
16.5
0.5
2.5
49
4300
3400
70
9.90
3.4
0.1
16
18.1
0.5
2.6
53
5200
3900
95
11.7
3.4
0.1
16
19.9
0.5
2.8
57
6400
4600
120
13.1
3.4
0.1
16
21.3
0.5
2.9
61
7400
5200
150
14.3
3.4
0.1
25
22.5
0.5
3.0
64
8500
5700
185
16.3
3.4
0.1
25
24.5
0.5
3.1
68
10000
6500
240
18.7
3.4
0.1
25
26.9
0.5
3.3
74
12300
7600
300
20.9
3.4
0.1
25
29.1
0.5
3.4
79
14600
8800
400
23.7
3.4
0.1
35
31.9
0.8
3.7
87
18700
11300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Medium Voltage Cables to VDE 0276
Three Core 6/10KV (Um=12KV) Galvanized Flat Steel wire Armoured Cables
N2XSEYFGbY
NA2XSEYFGbY
Dimensional Data
Nom.
Approx.
Nom.
Copper
CrossConductor Insulation
Tape
Section
Diameter Thickness Thickness
Area
Copper
Wire
Screen
Area*
Approx.
Nom.
Insulation
Armour
Diameter Thickness
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx. Weight
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
mm
kg / km
kg / km
25
6.05
3.4
0.1
16
14.3
0.8
2.3
44
3300
2800
35
7.10
3.4
0.1
16
15.3
0.8
2.4
46
3800
3100
50
8.25
3.4
0.1
16
16.5
0.8
2.5
49
4400
3500
70
9.90
3.4
0.1
16
18.1
0.8
2.6
53
5400
4100
95
11.7
3.4
0.1
16
19.9
0.8
2.8
57
6500
4700
120
13.1
3.4
0.1
16
21.3
0.8
2.9
61
7600
5300
150
14.3
3.4
0.1
25
22.5
0.8
3.0
64
8700
5900
185
16.3
3.4
0.1
25
24.5
0.8
3.1
68
10200
6800
240
18.7
3.4
0.1
25
26.9
0.8
3.3
74
12500
7900
300
20.9
3.4
0.1
25
29.1
0.8
3.4
79
14900
9100
400
23.7
3.4
0.1
35
31.9
0.8
3.7
86
18000
10600
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Nom.
CrossSection
Area
Short Circuit
DC
AC
Rating of
Charging
Resistance Resistance Conductor Capacitance
Current
CU / AL
CU / AL
CU / AL
1 sec
Short Circuit
Rating of
Copper Wire
Screen
Per Core
1 sec
Short Circuit
Rating of
Copper Wire
Screen
Per Core
1 sec
Reactance
Inductance
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
25
727/1200
927/1538
3.6/2.3
204
0.43
2.6
0.5
129
405
35
524/868
668/1113
5.0/3.2
237
0.47
2.6
0.6
115
370
50
387/641
494/822
6.8/4.4
260
0.52
2.6
0.6
109
350
70
268/443
343/568
9.8/6.3
298
0.60
2.6
0.7
103
330
95
193/320
248/410
13.3/8.5
334
0.67
2.6
0.7
99
320
120
153/253
196/325
17.2/11.0
365
0.73
2.6
0.8
96
310
150
124/206
159/265
21.2/13.5
392
0.78
4.3
0.8
93
300
185
99.1/164
128/211
26.6/17.0
430
0.86
4.3
0.9
90
290
240
75.4/125
98/161
34.9/22.3
476
0.95
4.3
0.9
87
280
300
60.1/100
80/130
43.8/28.0
524
1.05
4.3
1.0
85
270
400
47.0/77.8
64/102
57.3/36.6
580
1.16
5.8
1.1
81
260
www.addison-cables.com
79
Caledonian Medium Voltage Cables
Three Core 8.7/15KV (Um=17.5KV)
N2XSEY
NA2XSEY
Dimensional Data
Approx.
Conductor
Diameter
Nom.
Insulation
Thickness
Copper
Tape
Thickness
Copper
Wire
Screen
Area*
mm²
mm
mm
mm
25
6.05
4.5
0.1
35
7.10
4.5
50
8.25
70
9.90
Nom.
CrossSection
Area
Approx. Weight
Approx.
Insulation
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Cu
Al
mm²
mm
mm
mm
kg / km
kg / km
16
16.5
1.7
46
3500
2400
0.1
16
17.5
1.7
48
3800
2600
4.5
0.1
16
18.7
1.7
51
4400
3000
4.5
0.1
16
20.3
1.8
55
5300
3400
95
11.7
4.5
0.1
16
22.1
1.8
59
6400
4000
120
13.1
4.5
0.1
16
23.5
1.9
62
7400
4500
150
14.3
4.5
0.1
25
24.7
1.9
65
8500
5000
185
16.3
4.5
0.1
25
26.7
2.0
69
10000
5800
240
18.7
4.5
0.1
25
29.1
2.1
75
12200
6800
300
20.9
4.5
0.1
25
31.3
2.1
80
14400
7900
400
23.7
4.5
0.1
35
34.1
2.2
87
17500
9300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Three Core 8.7/15KV (Um=17.5KV) Galvanized Steel Tape Armoured Cables
N2XSEYBY
NA2XSEYBY
Dimensional Data
Nom.
Approx
Nom.
Copper
CrossConductor Insulation
Tape
Section
Diameter Thickness Thickness
Area
Copper
Wire
Screen
Area*
Approx
Nom.
Nom.
Insulation Armour
Sheath
Diameter Thickness Thickness
Approx.
Overall
Diameter
Approx. Weight
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
mm
kg / km
kg / km
25
6.05
4.5
0.1
16
16.5
0.5
2.5
49
3800
3300
35
7.10
4.5
0.1
16
17.5
0.5
2.6
51
4300
3600
50
8.25
4.5
0.1
16
18.7
0.5
2.7
54
4900
4000
70
9.90
4.5
0.1
16
20.3
0.5
2.8
58
5900
4600
95
11.7
4.5
0.1
16
22.1
0.5
2.9
62
7100
5300
120
13.1
4.5
0.1
16
23.5
0.5
3.0
66
8100
5900
150
14.3
4.5
0.1
25
24.7
0.5
3.1
69
9200
6400
185
16.3
4.5
0.1
25
26.7
0.5
3.3
74
10900
7400
240
18.7
4.5
0.1
25
29.1
0.5
3.4
79
13100
8500
300
20.9
4.5
0.1
25
31.3
0.5
3.6
86
16400
10600
400
23.7
4.5
0.1
35
34.1
0.8
3.9
93
19700
12300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Medium Voltage Cables to VDE 0276
Three Core 8.7/15KV (Um=17.5KV) Galvanized Flat Steel Wire Armoured Cables
N2XSEYFGbY
NA2XSEYFGbY
Dimensional Data
Nom.
CrossSection
Area
Approx.
Nom.
Copper
Conductor Insulation
Tape
Diameter Thickness Thickness
Copper
Wire
Screen
Area*
Approx.
Nom.
Nom.
Approx.
Insulation Armour
Sheath
Overall
Diameter Thickness Thickness Diameter
Approx. Weight
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
mm
kg / km
kg / km
25
6.05
4.5
0.1
16
16.5
0.8
2.5
49
3400
3400
35
7.10
4.5
0.1
16
17.5
0.8
2.6
51
4400
3800
50
8.25
4.5
0.1
16
18.7
0.8
2.7
54
5100
4200
70
9.90
4.5
0.1
16
20.3
0.8
2.8
58
6000
4700
95
11.7
4.5
0.1
16
22.1
0.8
2.9
62
7300
5400
120
13.1
4.5
0.1
16
23.5
0.8
3.0
66
8300
6100
150
14.3
4.5
0.1
25
24.7
0.8
3.1
69
9400
6600
185
16.3
4.5
0.1
25
26.7
0.8
3.3
74
11100
7600
240
18.7
4.5
0.1
25
29.1
0.8
3.4
79
13400
8700
300
20.9
4.5
0.1
25
31.3
0.8
3.6
85
15800
10000
400
23.7
4.5
0.1
35
34.1
0.8
3.9
91
19000
11600
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Nom.
CrossSection
Area
Short Circuit
DC
AC
Rating of
Resistance Resistance Conductor
CU / AL
CU / AL
CU / AL
1 sec
kA
Short Circuit
Rating of
Charging Copper Wire
Capacitance
Current
Screen
Per Core
1 sec
pF/m
mA/m
kA
Short Circuit
Rating of
Copper Tape
Screen
Per Core
1 sec
Reactance
Inductance
kA
µΩm
nH/m
mm²
µΩm
µΩ/m
25
727/1200
927/1538
3.6/2.3
176
0.48
2.6
0.6
132
410
35
524/868
668/1113
5.0/3.2
193
0.53
2.6
0.6
123
390
50
387/641
494/822
6.8/4.4
211
0.58
2.6
0.7
116
370
70
268/443
343/568
9.8/6.3
240
0.65
2.6
0.7
110
350
95
193/320
248/410
13.3/8.5
267
0.73
2.6
0.8
105
330
120
153/253
196/325
17.2/11.0
291
0.79
2.6
0.8
102
320
150
124/206
159/265
21.2/13.5
312
0.85
4.3
0.9
98
310
185
99.1/164
128/211
26.6/17.0
340
0.93
4.3
0.9
95
300
240
75.4/125
98/161
34.9/22.3
375
1.02
4.3
1.0
91
290
300
60.1/100
80/130
43.8/28.0
411
1.12
4.3
1.1
89
280
400
47.0/77.8
64/102
57.3/36.6
454
1.24
5.8
1.2
84
270
www.addison-cables.com
81
Caledonian Medium Voltage Cables
Three Core 12/20KV (Um=24KV)
N2XSEY
NA2XSEY
Dimensional Data
Approx.
Conductor
Diameter
Nom.
Insulation
Thickness
Copper
Tape
Thickness
Copper
Wire
Screen
Area*
mm²
mm
mm
mm
35
7.10
5.5
0.1
50
8.25
5.5
70
9.90
95
11.7
120
150
Nom.
CrossSection
Area
Approx. Weight
Approx.
Insulation
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Cu
Al
mm²
mm
mm
mm
kg / km
kg / km
16
19.7
1.8
53
3800
3100
0.1
16
20.9
1.8
56
4400
3500
5.5
0.1
16
22.5
1.9
60
5300
4000
5.5
0.1
16
24.3
1.9
64
6400
4600
13.1
5.5
0.1
16
25.7
2.0
67
7400
5200
14.3
5.5
0.1
25
26.9
2.0
70
8500
5700
185
16.3
5.5
0.1
25
28.9
2.1
75
10000
6500
240
18.7
5.5
0.1
25
31.3
2.1
80
12200
7500
300
20.9
5.5
0.1
25
33.5
2.2
85
14400
8700
400
23.7
5.5
0.1
35
36.3
2.3
91
17500
10200
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Three Core 12/20KV (Um=24KV) Galvanized Steel Tape Armoured Cables
N2XSEYBY
NA2XSEYBY
Dimensional Data
Nom.
Approx.
Nom.
Copper
CrossConductor Insulation
Tape
Section
Diameter Thickness Thickness
Area
Copper
Wire
Screen
Area*
Approx.
Nom.
Nom.
Insulation Armour
Sheath
Diameter Thickness Thickness
Approx.
Overall
Diameter
Approx. Weight
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
mm
kg / km
kg / km
35
7.10
5.5
0.1
16
19.7
0.5
2.7
57
4900
4200
50
8.25
5.5
0.1
16
20.9
0.5
2.9
60
5600
4700
70
9.90
5.5
0.1
16
22.5
0.5
3.0
64
6600
5300
95
11.7
5.5
0.1
16
24.3
0.5
3.1
68
7800
6000
120
13.1
5.5
0.1
16
25.7
0.5
3.2
71
8900
6600
150
14.3
5.5
0.1
25
26.9
0.5
3.3
74
10100
7200
185
16.3
5.5
0.1
25
28.9
0.5
3.4
79
11700
8200
240
18.7
5.5
0.1
25
31.3
0.8
3.6
86
14900
10200
300
20.9
5.5
0.1
25
33.5
0.8
3.8
91
17400
11600
400
23.7
5.5
0.1
35
36.3
0.8
4.0
98
20800
13400
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Medium Voltage Cables to VDE 0276
Three Core 12/20KV (Um=24KV) Galvanized Flat Steel Wire Armoured Cables
N2XSEYFGbY
NA2XSEYFGbY
Dimensional Data
Nom.
Approx.
Nom.
Copper
CrossConductor Insulation
Tape
Section
Diameter Thickness Thickness
Area
Copper
Wire
Screen
Area*
Approx.
Nom.
Insulation Armour
Diameter Thickness
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx. Weight
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
mm
kg / km
kg / km
35
7.10
5.5
0.1
16
19.7
0.8
2.7
57
5000
4400
50
8.25
5.5
0.1
16
20.9
0.8
2.9
60
5700
4800
70
9.90
5.5
0.1
16
22.5
0.8
3.0
64
6800
5400
95
11.7
5.5
0.1
16
24.3
0.8
3.1
68
8000
6200
120
13.1
5.5
0.1
16
25.7
0.8
3.2
71
9100
6800
150
14.3
5.5
0.1
25
26.9
0.8
3.3
74
10300
7500
185
16.3
5.5
0.1
25
28.9
0.8
3.4
79
11900
8400
240
18.7
5.5
0.1
25
31.3
0.8
3.6
85
14300
9600
300
20.9
5.5
0.1
25
33.5
0.8
3.8
90
16700
10900
400
23.7
5.5
0.1
35
36.3
0.8
4.0
97
20100
12700
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Nom.
CrossSection
Area
DC
AC
Resistance Resistance
CU / AL
CU / AL
Short Circuit
Rating of
Conductor
CU / AL
1 sec
Capacitance
Charging
Current
Short Circuit
Rating of
Copper Wire
Screen
Per Core
1 sec
Short Circuit
Rating of
Copper Tape
Screen
Per Core
1 sec
Reactance
Inductance
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
35
524/868
668/1113
5.0/3.2
168
0.67
2.6
0.7
129
410
50
387/641
494/822
6.8/4.4
183
0.73
2.6
0.8
122
390
70
268/443
343/568
9.8/6.3
207
0.83
2.6
0.8
115
370
95
193/320
248/410
13.3/8.5
229
0.92
2.6
0.9
110
350
120
153/253
196/325
17.2/11.0
249
1.00
2.6
0.9
106
340
150
124/206
159/265
21.2/13.5
266
1.06
4.3
1.0
103
330
185
99.1/164
128/211
26.6/17.0
289
1.16
4.3
1.0
100
320
240
75.4/125
98/161
34.9/22.3
318
1.27
4.3
1.1
95
300
300
60.1/100
80/130
43.8/28.0
348
1.39
4.3
1.2
93
300
400
47.0/77.8
64/102
57.3/36.6
388
1.53
5.8
1.3
87
280
www.addison-cables.com
83
Caledonian Medium Voltage Cables
Three Core 18/30KV (Um=36KV)
N2XSEY
NA2XSEY
Dimensional Data
Nom.
CrossSection
Area
Approx.
Nom.
Conductor Insulation
Diameter Thickness
Copper
Tape
Thickness
Copper
Wire
Screen
Area*
Approx. Weight
Approx.
Insulation
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
kg / km
kg / km
50
8.25
8.0
0.1
16
25.9
2.0
68
5800
4900
70
9.90
8.0
0.1
16
27.5
2.0
71
6800
5500
95
11.7
8.0
0.1
16
29.3
2.1
75
8000
6100
120
13.1
8.0
0.1
16
30.7
2.1
79
9000
6700
150
14.3
8.0
0.1
25
31.9
2.2
81
10100
7300
185
16.3
8.0
0.1
25
33.9
2.2
86
11800
8300
240
18.7
8.0
0.1
25
36.3
2.3
91
14000
9400
300
20.9
8.0
0.1
25
38.5
2.4
97
16500
10700
400
23.7
8.0
0.1
35
41.3
2.5
103
19700
12300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Three Core 18/30KV (Um=36KV) Galvanized Steel Tape Armoured Cables
N2XSEYBY
NA2XSEYBY
Dimensional Data
Nom.
Approx.
Nom.
Copper
CrossConductor Insulation
Tape
Section
Diameter Thickness Thickness
Area
mm²
mm
mm
mm
Copper
Wire
Screen
Area*
mm²
Approx.
Nom.
Nom.
Insulation
Armour
Sheath
Diameter Thickness Thickness
mm
mm
mm
Approx.
Overall
Diameter
mm
Approx. Weight
Cu
Al
kg / km
kg / km
50
8.25
8.0
0.1
16
25.9
0.5
3.2
72
7300
6400
70
9.90
8.0
0.1
16
27.5
0.5
3.3
75
8400
7100
95
11.7
8.0
0.1
16
29.3
0.5
3.5
80
9700
7900
120
13.1
8.0
0.1
16
30.7
0.8
3.6
84
11700
9400
150
14.3
8.0
0.1
25
31.9
0.8
3.7
87
12900
10100
185
16.3
8.0
0.1
25
33.9
0.8
3.9
92
14800
11300
240
18.7
8.0
0.1
25
36.3
0.8
4.0
98
17300
12600
300
20.9
8.0
0.1
25
38.5
0.8
4.2
103
20000
14100
400
23.7
8.0
0.1
35
41.3
0.8
4.4
110
23500
16000
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Medium Voltage Cables to VDE 0276
Three Core 18/30KV (Um=36KV) Galvanized Flat Steel wire Armoured Cables
N2XSEYFGbY
NA2XSEYFGbY
Dimensional Data
Nom.
CrossSection
Area
Approx.
Nom.
Copper
Conductor Insulation
Tape
Diameter Thickness Thickness
Copper
Wire
Screen
Area*
Approx.
Nom.
Insulation
Armour
Diameter Thickness
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx. Weight
Cu
Al
mm²
mm
mm
mm
mm²
mm
mm
mm
mm
kg / km
kg / km
50
8.25
8.0
0.1
16
25.9
0.8
3.2
72
7500
6600
70
9.90
8.0
0.1
16
27.5
0.8
3.3
76
8600
7300
95
11.7
8.0
0.1
16
29.3
0.8
3.5
80
10000
8100
120
13.1
8.0
0.1
16
30.7
0.8
3.6
83
11200
8900
150
14.3
8.0
0.1
25
31.9
0.8
3.7
86
12400
9500
185
16.3
8.0
0.1
25
33.9
0.8
3.9
91
14100
10600
240
18.7
8.0
0.1
25
36.3
0.8
4.0
97
16600
11900
300
20.9
8.0
0.1
25
38.5
0.8
4.2
102
19200
13400
400
23.7
8.0
0.1
35
41.3
0.8
4.4
109
22700
15300
*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as
standard.
Electrical Data
Nom.
CrossSection
Area
DC
AC
Resistance Resistance
CU / AL
CU / AL
Short Circuit
Short Circuit
Rating of
Rating of
Charging Copper Wire
Conductor Capacitance
Current
Screen
CU / AL
Per Core
1 sec
1 sec
Short Circuit
Rating of
Copper Tape
Reactance Inductance
Screen
Per Core
1 sec
mm²
µΩ/m
µΩ/m
kA
pF/m
mA/m
kA
kA
µΩ/m
nH/m
50
387/641
494/822
6.8/4.4
142
0.85
2.6
1.0
134
430
70
268/443
343/568
9.8/6.3
159
0.95
2.6
1.0
127
400
95
193/320
248/410
13.3/8.5
175
1.05
2.6
1.1
121
390
120
153/253
196/325
17.2/11.0
189
1.13
2.6
1.1
117
370
150
124/206
159/265
21.2/13.5
201
1.21
4.3
1.2
113
360
185
99.1/164
128/211
26.6/17.0
217
1.3
4.3
1.2
109
350
240
75.4/125
98/161
34.9/22.3
237
1.42
4.3
1.3
104
330
300
60.1/100
80/130
43.8/28.0
258
1.55
4.3
1.4
101
320
400
47.0/77.8
64/102
57.3/36.6
282
1.69
5.8
1.5
96
290
www.addison-cables.com
85
Caledonian Medium Voltage Cables
Current Rating for Three Core 1.8/3KV(Um=7.2KV ) to 26/35KV(Um=42KV) XLPE Insulation
Unarmored
Nom.
CrossSection
Area
Armored
Buried direct in Laid in Single Way
Ground
Duct
Laid in Air
Buried direct in Laid in Single Way
Ground
Duct
Laid in Air
CU
CU
CU
CU
mm²
AL
CU
A
AL
A
AL
A
AL
CU
A
AL
A
AL
A
10
76
53
62
42
87
62
76
53
63
43
88
63
16
101
78
87
67
109
84
101
78
88
68
110
85
25
129
100
112
87
142
110
129
100
112
87
143
111
35
153
119
133
103
170
132
154
119
134
104
172
133
50
181
140
158
122
204
158
181
140
158
123
205
159
70
221
171
193
150
253
196
220
171
194
150
253
196
95
262
203
231
179
304
236
263
204
232
180
307
238
120
298
232
264
205
351
273
298
232
264
206
352
274
150
334
260
297
231
398
309
332
259
296
231
397
309
185
377
294
336
262
455
355
374
293
335
262
453
354
240
434
340
390
305
531
415
431
338
387
304
529
415
300
489
384
441
346
606
475
482
380
435
343
599
472
400
553
438
501
398
696
552
541
432
492
393
683
545
500
613
498
541
451
786
652
601
492
532
446
773
645
630
663
568
591
501
896
762
651
562
582
496
883
755
Caledonian
Medium Voltage
Cables
I
V
II
Technical Information
III
IV
V
Caledonian Medium Voltage Cables
Technical information
▓▓ Current Ratings
The current ratings given on the previous pages are based on the standard conditions of
installation detailed bellows:
Maximum conductor temperature: 90°C
Maximum ambient temperature: In air 30°C
In ground 20°C
Ground thermal resistivity:
1.5K•m/W
Laying depth:
0.8m
Spacing between cable laid: In flat formation
2 times of cable overall diameter
In trefoil
with cable touching
Where the site conditions differ from the standard conditions mentioned, it will be necessary
to multiply the tabulated ratings by the actors given in the following tables. These factors are
for variation in ambient ground temperature, soil thermal resistivity and depth of laying. Where
more than one circuit is installed in close proximity, then will be necessary to derate further in
accordance with the group rating factors given.
▓▓ Rating Factors
Cables laid direct in ground:
Variation in ground temperatur
Ground Temperature
Cabe Type
All Cables
15
20
25
1.00
0.97
0.93
30
Rating Factor
0.89
35
40
45
0.86
0.82
0.76
Rating factor for depth of laying (To center of cable or trefoil group of cables)
Depth of laying
m
0.50
0.60
0.80
1.00
1.25
1.50
1.75
2.00
2.50
3.00 or more
1.9/3.3KV (1.8/3KV) to 19/33KV (18/30KV) Cables
Up to 300 mm²
Above 300 mm²
1.00
1.00
0.98
0.97
0.96
0.95
0.95
0.94
0.94
0.92
0.92
0.90
0.91
0.89
0.90
0.88
Technical Information
Rating factor for variation in thermal resistivity of soil depth
Nom.CrossSection Area
Soil thermal resistivity K.m/W
0.8
0.9
1.0
1.5
2.0
2.5
3.0
50
1.15
1.11
1.07
0.91
0.81
0.73
0.68
70
1.16
1.12
1.07
0.91
0.81
0.73
0.68
95
1.16
1.12
1.07
0.91
0.81
0.73
0.68
120
1.16
1.12
1.07
0.91
0.81
0.73
0.68
150
1.17
1.12
1.07
0.91
0.81
0.73
0.68
185
1.17
1.12
1.07
0.91
0.81
0.73
0.68
240
1.17
1.12
1.07
0.91
0.80
0.73
0.68
300
1.18
1.12
1.07
0.91
0.80
0.73
0.68
400
1.18
1.12
1.07
0.91
0.80
0.73
0.67
500
1.18
1.12
1.07
0.91
0.80
0.73
0.67
630
1.18
1.12
1.07
0.91
0.80
0.73
0.67
800
1.18
1.12
1.07
0.91
0.80
0.72
0.67
1000
1.18
1.12
1.07
0.91
0.80
0.72
0.67
16
1.12
1.08
1.05
0.93
0.84
0.77
0.72
25
1.13
1.09
1.05
0.93
0.83
0.77
0.71
35
1.13
1.09
1.06
0.92
0.83
0.76
0.71
50
1.13
1.09
1.06
0.92
0.83
0.76
0.71
70
1.14
1.09
1.06
0.92
0.83
0.75
0.70
95
1.14
1.09
1.06
0.92
0.83
0.75
0.70
120
1.14
1.10
1.06
0.92
0.82
0.75
0.69
150
1.14
1.10
1.06
0.92
0.82
0.75
0.69
185
1.14
1.10
1.06
0.92
0.82
0.74
0.69
240
1.15
1.10
1.07
0.92
0.82
0.74
0.69
300
1.15
1.10
1.07
0.92
0.82
0.74
0.69
400
1.15
1.10
1.07
0.92
0.82
0.74
0.69
Single
multicore
Group rating factor for circuits of three single core cables. In trefoil and laid flat touching,
horizontal formation (average values)
No. of
circuits
1.9/3.3KV(1.8/3KV)
to 12.7/22KV
(12/20KV) Cables
19/33KV(18/30KV)
Cables
Spacing of circuits
Touching
Trefoil
Laid Flat
0.15m*
0.3m
0.45m
0.6m
2
0.78
0.80
0.81
0.85
0.88
0.90
3
0.66
0.68
0.71
0.76
0.80
0.83
4
0.59
0.62
0.65
0.72
0.76
0.80
5
0.55
0.58
0.61
0.68
0.73
0.77
6
0.52
0.55
0.58
0.66
0.72
0.76
2
0.79
0.81
0.81
0.85
0.88
0.90
3
0.67
0.70
0.71
0.76
0.80
0.83
4
0.62
0.65
0.65
0.72
0.76
0.80
5
0.57
0.60
0.60
0.68
0.73
0.77
6
0.54
0.57
0.57
0.66
0.70
0.76
*This configuration, at 0.15m spacing, may not be practical for the larger size cables.
www.addison-cables.com
89
Caledonian Medium Voltage Cables
Group rating factor for multicore cables in horizontal formation (average values)
1.9/3.3KV(1.8/3KV)
to 12.7/22KV
(12/20KV) Cables
19/33KV(18/30KV)
Cables
Spacing
No. of cables
in group
Touching
0.15m
0.3m
0.45m
0.6m
2
0.80
0.85
0.89
0.90
0.92
3
0.68
0.75
0.80
0.84
0.86
4
0.62
0.70
0.77
0.80
0.84
5
0.57
0.66
0.73
0.78
0.81
6
0.55
0.63
0.71
0.76
0.80
2
0.80
0.83
0.87
0.89
0.91
3
0.70
0.73
0.78
0.82
0.85
4
0.64
0.68
0.74
0.78
0.82
5
0.59
0.63
0.70
0.75
0.79
6
0.56
0.60
0.68
0.74
0.78
Cables laid direct in single way ducts:
(The term “ducts” applies to single earthenware, fibre or plastic pipes).
Variation in ground temperature
Ground Temperature
15
20
25
1.00
0.97
0.93
Cabe Type
All Cables
30
35
40
45
0.86
0.82
0.76
Rating Factor
0.89
Rating factor for depth of laying (To center of cable or trefoil group of cables)
Depth of laying
600/1000V cables
1900/3300V to 19000/33000V cables
m
Single Core
Multicore
Single Core
Multicore
0.50
1.00
1.00
-
-
0.60
0.98
0.99
-
-
0.80
0.95
0.97
1.00
1.00
1.00
0.93
0.96
0.98
0.99
1.25
0.90
0.95
0.95
0.97
1.50
0.89
0.94
0.93
0.96
1.75
0.88
0.94
0.92
0.95
2.00
0.87
0.93
0.90
0.95
2.50
0.86
0.92
0.89
0.93
3.00 or more
0.85
0.91
0.88
0.92
Technical Information
Rating factor for variation in termal resistivity of soil depth
Nom.CrossSection Area
mm²
Soil thermal resistivity K.m/W
0.8
0.9
1.0
1.5
2.0
2.5
3.0
50
1.08
1.06
1.04
0.94
0.87
0.82
0.77
70
1.09
1.06
1.04
0.94
0.87
0.81
0.76
Single Core
95
1.09
1.06
1.04
0.94
0.87
0.81
0.76
120
1.10
1.07
1.04
0.94
0.86
0.80
0.75
150
1.10
1.07
1.04
0.94
0.86
0.80
0.75
185
1.10
1.07
1.04
0.93
0.86
0.79
0.75
240
1.11
1.07
1.05
0.93
0.86
0.79
0.74
300
1.11
1.08
1.05
0.93
0.85
0.79
0.74
400
1.11
1.08
1.05
0.93
0.85
0.78
0.73
500
1.11
1.08
1.05
0.93
0.85
0.78
0.73
630
1.12
1.08
1.05
0.93
0.84
0.78
0.72
800
1.12
1.09
1.05
0.93
0.84
0.77
0.72
1000
1.13
1.09
1.05
0.93
0.84
0.77
0.71
16
1.04
1.03
1.02
0.97
0.92
0.88
0.85
25
1.05
1.03
1.02
0.96
0.92
0.88
0.84
35
1.05
1.03
1.02
0.96
0.92
0.87
0.83
50
1.05
1.03
1.02
0.96
0.91
0.87
0.83
70
1.05
1.04
1.02
0.96
0.91
0.86
0.82
multicore
95
1.06
1.04
1.02
0.96
0.91
0.86
0.82
120
1.06
1.04
1.03
0.95
0.90
0.85
0.81
150
1.06
1.04
1.03
0.95
0.90
0.85
0.80
185
1.07
1.05
1.03
0.95
0.89
0.84
0.80
240
1.07
1.05
1.03
0.95
0.89
0.84
0.79
300
1.07
1.05
1.03
0.95
0.88
0.83
0.78
400
1.07
1.05
1.03
0.95
0.88
0.83
0.78
Group rating factor for circuits of three single core cables
In trefoil single way ducts, horizontal formation (average values)
No. of circuits
1.9/3.3KV(1.8/3KV) to
12.7/22KV(12/20KV) Cables
19/33KV(18/30KV) Cables
Spacing
Touching
0.45m
0.60m
2
0.85
0.88
0.90
3
0.75
0.80
0.83
4
0.70
0.76
0.80
5
0.67
0.73
0.77
6
0.64
0.71
0.76
2
0.85
0.88
0.90
3
0.76
0.80
0.83
4
0.71
0.76
0.80
5
0.67
0.73
0.77
6
0.65
0.71
0.76
www.addison-cables.com
91
Caledonian Medium Voltage Cables
Group rating factor for multicore cables in single way ducts, horizontal formation (average
values)
No. of ducts in group
1.9/3.3KV(1.8/3KV) to
12.7/22KV(12/20KV) Cables
19/33KV(18/30KV) Cables
Spacing
Touching
0.30m
0.45m
0.60m
2
0.88
0.91
0.93
0.94
3
0.80
0.84
0.87
0.89
4
0.75
0.81
0.84
0.87
5
0.71
0.77
0.82
0.85
6
0.69
0.75
0.80
0.84
2
0.87
0.89
0.92
0.93
3
0.78
0.82
0.85
0.87
4
0.73
0.78
0.82
0.85
5
0.69
0.75
0.79
0.83
6
0.67
0.73
0.78
0.82
Cables laid direct in free airs:
Variation in air temperature
Ground Temperature
25
30
35
Cabe Type
40
45
50
55
Rating Factor
Cables type up to 3.3KV
1.02
1.00
0.96
0.91
0.87
0.82
0.76
6.6Kv or above
1.00
0.95
0.91
0.86
0.80
0.75
0.69
Effect of grouping cables
No reduction in rating is necessary where there is free circulation of air around the circuits
providing that:
111 The horizontal clearance between circuits is not less than twice the overall diameter of an
individual cable.
222 The vertical clearance between circuits is not less than four times the diameter of an
individual cable.
333 If the number of circuits exceeds three, they are installed in a horizontal plane.
Technical Information
▓▓ Short Circuit Ratings
Short circuit rating –Copper conductor current in kiloamps
100
90
80
70
60
1000 sq mm
800 sq mm
630 sq mm
50
500 sq mm
40
400 sq mm
30
Currrnt In KiloAMPS
300 sq mm
240 sq mm
20
185 sq mm
150 sq mm
120 sq mm
10
9
8
95 sq mm
7
6
70 sq mm
5
50 sq mm
4
3
35 sq mm
25 sq mm
2
16 sq mm
1
0.1
0.2
0.3
0.4 0.5 0.6
0.8 1.0
2.0
3.0
Duration Of Short Circuit In Seconds
Basis:
1. Cable fully located at start of short circuit. (Conductor temperature: 90°C)
2. Conductor temperature at end of short circuit: 250°C
www.addison-cables.com
93
Caledonian Medium Voltage Cables
Short circuit rating –Aluminium conductor current in kiloamps
100
90
80
70
60
1000 sq mm
50
800 sq mm
40
630 sq mm
30
Currrnt In KiloAMPS
500 sq mm
400 sq mm
20
300 sq mm
240 sq mm
185 sq mm
10
9
8
150 sq mm
7
6
120 sq mm
5
95 sq mm
4
70 sq mm
3
50 sq mm
2
35 sq mm
25 sq mm
16 sq mm
1
0.1
0.2
0.3
0.4 0.5 0.6
0.8 1.0
Duration Of Short Circuit In Seconds
Basis:
1. Cable fully located at start of short circuit. (Conductor temperature: 90°C)
2. Conductor temperature at end of short circuit: 250°C
2.0
3.0
Technical Information
Armour fault current
Nom.
CrossSection
Area
mm²
Aluminium Wire Armoured Cables
3.8/6.6
(3.6/6)
KV
6.35/11
(6/12)
KV
8.7/15
KV
12.7/22
(12/20) KV
Steel Wire Armoured Cables
18/30
(19/33) KV
3.8/6.6
(3.6/6)
KV
6.35/11
(6/12)
KV
8.7/15KV
12.7/22
(12/20)
KV
25
7370
10160
11510
35
7800
10830
11960
13090
18/30
(19/33)
KV
50
6150
6660
7340
7860
12010
10380
11290
12640
13770
21500
70
6660
7170
7860
10680
12810
11290
12190
13540
14670
22580
95
7170
7690
10410
11210
13350
12190
13320
14450
19710
24010
120
7520
8030
10940
11750
13880
13090
14220
15350
20790
25090
150
8030
10680
11480
12280
18350
13770
14900
16030
21860
25810
185
10680
11480
12280
12810
19190
14900
15800
21860
23300
27240
240
11750
12280
13060
13880
20020
16480
21860
23660
25090
29030
300
12550
13080
13880
18770
21690
22580
23660
25090
26520
30830
400
13880
14150
19190
20020
22940
25090
25810
27240
28670
500
19190
19610
20440
21690
24610
630
21270
21270
22530
23360
26280
800
23360
23360
24610
25450
28790
1000
25450
25450
26700
27530
30870
Wire screen
Nom.Cross-Section Area
Maximum dc resistance at 20°C
Short Circuit Rating
mm²
Ohm/km
A
16
1.19
2040
25
0.759
3200
35
0.542
4480
Copper wire applied helically or tape screen applied individually to each screened core, or collectively over laid
up provide an earth fault current path.
www.addison-cables.com
95
Table Of Contents
I
II
III
IV
V
Cable Properties & Construction
03
Cable Machinery & Equipments
05
Product Testing
06
Cable Options & Ordering Information
09
II
Medium Voltage Cables to BS 6622
Single Core Cables To BS 6622
Three Core Cables To BS 6622
12
~
30
III
Medium Voltage Cables to IEC 60502
Single Core Cables To IEC 60502
Three Core Cables To IEC 60502
31
~
59
IV
Medium Voltage Cables to VDE 0276
Single Core Cables To VDE 0276
Three Core Cables To VDE 0276
60
~
86
V
Technical Information
87
I
Medium Voltage
Cables
Download