Page 1 of 37 INSTALLATION QUALIFICATION PROTOCOL FOR HVAC SYSTEM OF AHU-01 CUSTOMER: PROJECT: SUBMITTED BY: PHARMA ENGINEERS PLO T N O. 1 1 3 / A / 1 , L A NE 8 , P HA SE I I, I DA C HE RLA PA LL I, H YD ERA BA D - 5 0 0 0 5 1 . Te l N o.9 1 - 4 0 2 7 2 6 1 1 1 3 , 2 7 2 6 1 1 1 4 Page 2 of 37 INSTALLATION QUALIFICATION PROTOCOL APPROVAL This document is prepared by the documentation team of M/S. PHARMA ENGINEERS for AHU TAG Number : PLANT /PROJECT : CLIENT : Hence this document before being effective shall be approved by M/s Client / Customer M/s. PHARMA ENGINEERS: Name Designation Signature Date Prepared By Reviewed By CLIENT / CUSTOMER Name Reviewed By Approved By Designation Signature Date Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 3 of 37 INSTALLATION QUALIFICATION (IQ) TABLE OF CONTENT 1. OBJECTIVE ...............................................................................................................................4 2. RESPONSIBILITIES ...............................................................................................................4 3. SCOPE OF SUPPLY OF COMPONENTS: ..........................................................................5 4. VERIFICATION OF LEAKAGE IN DUCTING ...............................................................30 5. VERIFICATION OF MANIFOLD LEAK TEST (HYDRO TEST) .................................33 6. VERIFICATION OF CALIBRATION OF INSTRUMENTS: .........................................35 7. LIST OF DOCUMENTS ENCLOSED ................................................................................36 Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 4 of 37 INSTALLATION QUALIFICATION (IQ) 1. OBJECTIVE The objective of this document is to verify that the HVAC system (AHU Tag No: _____________________) is installed with due considerations as specified in DQ of HVAC System (AHU Tag No: _____________________). 2. RESPONSIBILITIES M/s. Pharma Engineers: 1. To install the system as per the specifications. 2. To provide the necessary test certificates as per technical specifications specified in DQ. 3. To Complete the hvac system qualification. 4. To perform the duct leak test (for classified areas only) as per SMACNA Standard 2012. Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 5 of 37 INSTALLATION QUALIFICATION (IQ) 3. SCOPE OF SUPPLY OF COMPONENTS: PURPOSE This test is to verify that the AHU dimensions, position and sizes of utility connections are in compliance with the design qualification and also with as-built drawing. PRE-REQUISITES 1. As built drawing 2. Measuring tape 3. Approved Design Qualification Document TEST METHOD 1. Physically check the dimension of the AHU in length, width, and height and confirm with design document. 2. Physically check and confirm the supply and return air duct sizes right from the AHU up to terminal point for every room. 3. Physically check and confirm that the dampers are marked with air flow direction and marking was mentioned for the quantity adjustment. 4. Physically check and confirm that required indications are mentioned on the AHU like cable entry, safety indication, supply air, return air and exhaust air location. 5. Physically check and confirm the condensate piping and slope being maintained. 6. Physically check and confirm the location of fire/ smoke detectors and confirm the good practice of installation. 7. Deviations or remarks may be documented along with summary of all test results Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 6 of 37 INSTALLATION QUALIFICATION (IQ) COMPONENT VERICATION: AHU (SUPPLY UNIT) / AHU (RETURN UNIT) / EXHAUST UNIT / AHU CUM DEHUMIDIFIER SR.NO 1. 2. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION CONSTRUCTIONAL DETAILS: AHU TAG Number Unit Serial Number Manufacturers name M/S PHARMA ENGINEERS Qty 01 No. Unit Model AHU-01 Capacity (CFM) 6000 CFM Static Pressure (MM) 220 mm of WC Process Blower Make KRUGER / NICOTRA GEBHARDT Process Blower Model RLO-51-4550-D38 Process Blower Speed (RPM) 2850 RPM Reactivation Blower Make NICOTRA GEBHARDT Reactivation Blower Model RLO-11-2528-D19 Process Motor Make CROMPTON GREAVES/SIEMENS Process Motor Capacity (K.W/ 11 KW / 15 HP HP) Process Motor Speed (RPM) 2900 RPM Reactivation Motor Make CROMPTON GREAVES/SIEMENS Reactivation Motor Capacity 0.75 KW/1.0 HP (K.W/ HP) Motor Make BB/CG Motor Capacity (K.W) 5.5 Poles 4 Pole / 2 Pole Motor Speed(RPM) 2900 RPM / 1440 RPM M.O.C of Drain Tray SS 304 M.O.C of Frame work Aluminum Extruded Profile M.O.C of Base of the unit 14G G.S Sheet Plain CENTRIFUGAL FAN: Serial Number Make KRUGER / NICOTRA GEBHARDT CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 7 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION Model Air Flow Static Pressure Type Fan Pulley V- Belt R.P.M 3. 4. 5. 6. 7. SPECIFICATIONS AS PER DESIGN QUALIFICATION BNB-P400 3000 CFM 210 mm of WC PLUG FAN / DIDW 3103 RPM MOTOR: Serial Number Make BB/CG/SIEMENS K. W 5.5 Motor Pulley RPM 2900 RPM / 1440 RPM Type Flame Proof / Non-Flame Proof DEHUMIDIFIER BED CONSTRUCTIONAL DETAILS: BryAir / Air Pack Manufacturers name Unit Serial Number Air flow handling capacity of dehumidifier Revolution per Hour BED MOTOR Serial Number Make Type Power RPM REACTIVATION BLOWER Type Blower Model Air Flow REACTIVATION MOTOR Serial Number Make 2000 CFM 20 T.W.T. Induction motor 90W/440V 3 Backward RLO-315 667 CFM Crompton Greaves CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 8 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 8. 9. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Type Tefc Sq cage Induction flange mounted CRITERIA FULFILLED (YES/NO) Rating 1.5 HP RPM 2880 FILTRATION SCHEME WITH IN AHU & ACD FILTRATION IN ACD REACTIVATION FILTER Make THERMODYNE / AAF Type of filter Flange type Filter Media Synthetic Compatibility of water wash Yes Filter Test method EN 779 Filter classification as per EN G-3 779 Average arrestance of synthetic 80 ≤ Am <90 dust Equivalent particle size in terms 20 micron-Un authenticated data of market language I.P.D of Filter (Approximate) 55 ± 10 Pa F.P.D of Filter (Approximate) 250 Pa Size of Filter / Rated Air flow 610 x 610 x 50 / 2000 CFM Qty Serial Number Size of Filter / Rated Air flow 610 x 305 x 50 / 1000 CFM Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 50 / 500 CFM Qty NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. FILTRATION AHU FIRST STAGE FILTRATION IN AHU THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Synthetic Compatibility of water wash Yes Filter Test method EN 779 Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 9 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION Filter classification as per EN 779 Average arrestance of synthetic dust Equivalent particle size in terms of market language I.P.D of Filter (Approximate) F.P.D of Filter (Approximate) Size of Filter / Rated Air flow Qty Serial Number Size of Filter / Rated Air flow Qty Serial Number Size of Filter / Rated Air flow Qty Serial Number SPECIFICATIONS AS PER DESIGN QUALIFICATION CRITERIA FULFILLED (YES/NO) G-3 80 ≤ Am <90 20 micron-Un authenticated data 55 ± 10 Pa 250 Pa 610 x 610 x 50 / 2000 CFM 610 x 305 x 50 / 1000 CFM 305 x 305 x 50 / 500 CFM NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. 10. FIRST STAGE FILTRATION IN AHU THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Synthetic Compatibility of water wash Yes Filter Test method EN 779 Filter classification as per EN G-4 779 Average arrestance of synthetic 90 ≤ Am dust Equivalent particle size in terms 10 micron-Un authenticated data of market language I.P.D of Filter (Approximate) 65 ± 10 Pa F.P.D of Filter (Approximate) 250 Pa Size of Filter / Rated Air flow 610 x 610 x 50 / 2000 CFM Qty Serial Number Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 10 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 11. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Size of Filter / Rated Air flow 610 x 305 x 50 / 1000 CFM Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 50 / 500 CFM Qty Serial Number NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. SECOND STAGE FILTRATION IN AHU THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Synthetic Compatibility of water wash Yes Filter Test method EN 779 Filter classification as per EN M-5 779 Average efficiency at 0.4 micron 40 ≤ Em < 60 Equivalent particle size in terms 5 micron-Un authenticated data of market language I.P.D of Filter for 150 mm thick 90 ± 10 Pa (Approximate) I.P.D of Filter for 300 mm thick 75 ± 10 Pa (Approximate) F.P.D of Filter (Approximate) 450 Pa Size of Filter / Rated Air flow 610 x 610 x 150 / 2000 CFM Qty Serial Number Size of Filter / Rated Air flow 610 x 305 x 150 / 1000 CFM Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 150 / 500 CFM Qty Serial Number Size of Filter / Rated Air flow 610 x 610 x 300 / 2000 CFM Qty Serial Number CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 11 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION Size of Filter / Rated Air flow Qty Serial Number Size of Filter / Rated Air flow Qty Serial Number 12. SPECIFICATIONS AS PER DESIGN QUALIFICATION 610 x 305 x 300 / 1000 CFM 305 x 305 x 300 / 500 CFM NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. SECOND STAGE FILTRATION IN AHU THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Synthetic Compatibility of water wash Yes Filter Test method EN 779 Filter classification as per EN M-6 779 Average efficiency at 0.4 micron 60 ≤ Em < 80 Equivalent particle size in terms 5 micron-Un authenticated data of market language I.P.D of Filter for 150 mm thick 110 ± 10 Pa (Approximate) I.P.D of Filter for 300 mm thick 90 ± 10 Pa (Approximate) F.P.D of Filter (Approximate) 450 Pa Size of Filter / Rated Air flow 610 x 610 x 150 / 2000 CFM Qty Serial Number Size of Filter / Rated Air flow 610 x 305 x 150 / 1000 CFM Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 150 / 500 CFM Qty Serial Number Size of Filter / Rated Air flow 610 x 610 x 300 / 2000 CFM Qty CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 12 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 13. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Serial Number Size of Filter / Rated Air flow 610 x 305 x 300 / 1000 CFM Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 300 / 500 CFM Qty Serial Number NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. SECOND STAGE FILTRATION IN AHU THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Synthetic Compatibility of water wash Yes Filter Test method EN 779 Filter classification as per EN F-7 779 Average efficiency at 0.4 micron 80 ≤ Em < 90 Equivalent particle size in terms 3 micron-Un authenticated data of market language I.P.D of Filter for 150 mm thick 160 ± 10 Pa (Approximate) I.P.D of Filter for 300 mm thick 120 ± 10 Pa (Approximate) F.P.D of Filter (Approximate) 450 Pa Size of Filter / Rated Air flow 610 x 610 x 150 / 2000 CFM Qty Serial Number Size of Filter / Rated Air flow 610 x 305 x 150 / 1000 CFM Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 150 / 500 CFM Qty Serial Number Size of Filter / Rated Air flow 610 x 610 x 300 / 2000 CFM Qty CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 13 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 14. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Serial Number Size of Filter / Rated Air flow 610 x 305 x 300 / 1000 CFM Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 300 / 500 CFM Qty Serial Number NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. THIRD STAGE FILTRATION IN AHU THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Micro Fiber Glass Compatibility of water wash No Filter Test method EN 779 Filter classification as per EN F-9 779 Average efficiency at 0.4 micron 95 ≤ Em Equivalent particle size in terms 1 micron-Un authenticated data of market language I.P.D of Filter for 150 mm thick 120 ± 10 Pa (Approximate) I.P.D of Filter for 300 mm thick 180 ± 10 Pa (Approximate) F.P.D of Filter (Approximate) 500 Pa Size of Filter / Rated Air flow 610 x 610 x 150 / 1000 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 610 x 305 x 150 / 500 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 150 / 247 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 610 x 610 x 300 / 2000 CFM @ 2.5 m/s Qty CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 14 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 15. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Serial Number Size of Filter / Rated Air flow 610 x 305 x 300 / 1000 CFM @ 2.5 m/s Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 300 / 500 CFM @ 2.5 m/s Qty Serial Number NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. TERMINAL STAGE FILTRATION IN AHU (PLENUM) THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Micro Fiber Glass Compatibility of water wash No Filter Test method EN 1822 Filter classification as per EN H-13 779 Average Efficiency at MPPS 99.95% Equivalent particle size in terms 0.3 micron-Un authenticated data of market language I.P.D of Filter for 150 mm thick 350 ± 10 Pa (Approximate) I.P.D of Filter for 292 mm thick 350 ± 10 Pa (Approximate) F.P.D of Filter (Approximate) 750 Pa Size of Filter / Rated Air flow 610 x 610 x 150 / 1000 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 610 x 305 x 150 / 500 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 150 / 245 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 610 x 610 x 292 / 2000 CFM @ 2.5 m/s Qty CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 15 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 16. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Serial Number Size of Filter / Rated Air flow 610 x 305 x 292 / 1000 CFM @ 2.5 m/s Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 292 / 500 CFM @ 2.5 m/s Qty Serial Number NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. TERMINAL STAGE FILTRATION IN AHU (PLENUM) THERMODYNE / AAF Make of Filter Type of filter Flange type Filter Media Micro Fiber Glass Compatibility of water wash No Filter Test method EN 1822 Filter classification as per EN H-14 779 Average Efficiency at MPPS 99.995% Equivalent particle size in terms 0.3 micron-Un authenticated data of market language I.P.D of Filter for 150 mm thick 350 ± 10 Pa (Approximate) I.P.D of Filter for 292 mm thick 350 ± 10 Pa (Approximate) F.P.D of Filter (Approximate) 750 Pa Size of Filter / Rated Air flow 610 x 610 x 150 / 1000 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 610 x 305 x 150 / 500 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 150 / 245 CFM @ 1.25 m/s Qty Serial Number Size of Filter / Rated Air flow 610 x 610 x 292 / 2000 CFM @ 2.5 m/s Qty CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 16 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 17. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Serial Number Size of Filter / Rated Air flow 610 x 305 x 292 / 1000 CFM @ 2.5 m/s Qty Serial Number Size of Filter / Rated Air flow 305 x 305 x 292 / 500 CFM @ 2.5 m/s Qty Serial Number NOTE: I.P.D & F.P.D values change based on AIRFLOW; hence customer should set the limits after commissioning. FRESH AIR FILTRATION IN AHU / PRECOOLING Make of Filter Type of filter Filter Media Compatibility of water wash Filter Test method Filter classification as per EN 779 Average efficiency at 0.4 micron Equivalent particle size in terms of market language Size of Filter / Rated Air flow Qty Serial Number 18. CRITERIA FULFILLED (YES/NO) BLEED AIR FILTRATION IN AHU Make of Filter Type of filter Filter Media Compatibility of water wash Filter Test method Filter classification as per EN 779 Average efficiency at 0.4 micron Equivalent particle size in terms of market language Size of Filter / Rated Air flow Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 17 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Qty Serial Number 19. 20. 21. 22. COOLING, HEATING WITH IN AHU / ACD COOLING COIL IN TFA M/s. Flakt Woods (India) Pvt. Ltd. Manufacturers name Hyderabad Coils Pvt Ltd Quantity 1 No. Fluid Chilled water Coil size (fin ht. x fin Length) 635 x 860 mm No. of Rows 6 Tube MOC Copper Tube Diameter 1/2” Fins MOC Aluminum COOLING COIL IN AHU M/s. Flakt Woods (India) Pvt. Ltd. Manufacturers name Hyderabad Coils Pvt Ltd Quantity 1 No. Fluid Chilled water Coil size (fin ht. x fin Length) 635 x 860 mm No. of Rows 6 Tube MOC Copper Tube Diameter 1/2” Fins MOC Aluminum HEATING COIL IN AHU M/s. Flakt Woods (India) Pvt. Ltd. Manufacturers name Hyderabad Coils Pvt Ltd Quantity 1 No. Fluid Hot water Coil size (fin ht. x fin Length) 635 x 860 mm No. of Rows 2 Tube MOC Copper Tube Diameter 1/2” Fins MOC Aluminum STEAM COIL IN ACD M/s. Flakt Woods (India) Pvt. Ltd. Manufacturers name Hyderabad Coils Pvt Ltd CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 18 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 23. 24. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Quantity 1 No. Fluid Steam Coil size (fin ht. x fin Length) 635 x 860 mm No. of Rows 6 Tube MOC Copper Tube Diameter 5/8” Fins MOC Aluminum DETAILS OF VOLUME CONTROL DAMPERS FOR AHU: M/s. Flakt Woods (India) Pvt. Ltd. Make M/s. System Air M/s. Pharma Engineers MOC Aluminum extruded aero foil design Supply Air 325x550 mm–1 No. Return Air 325x550 mm–1 No.. Fresh Air 300x600 mm– 1 No. Bleed Air 300x300 mm– 1 No. DETAILS OF FUSIBLE LINK FIRE DAMPERS FOR AHU: M/s. System Air Make M/s. Pharma Engineers Multi-blade low leakage with opposed Type blade Blades & Casing 1.6mm thick GSS / 1.6 mm thick GI sheet Fire Rating @ IP555 120min Fire Rating Melting point of fusible link 74 deg. C Limit switch Mounted on frame of damper Supply Duct 550x325 mm Return Duct 550x325 mm Exhaust Duct 550x325 mm DETAILS OF MOTORIZED FIRE DAMPERS FOR AHU: 25. MOC M/s. System Air M/s. Pharma Engineers GI Thickness 16G Rating @ IP 555 120min Fire Rated Make CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 19 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Supply Duct 550x325 mm Return Duct 550x325 mm Exhaust Duct 550x325 mm ACTUATOR FOR FIRE DAMPER: 26. 27. 28. 29. 30. 31. Make M/S. Belimo Model NFA-S2 Location Return Air Duct, Supply Duct PIPPING & MANIFOLD DETAILS CHILLED WATER MANIFOLD: Pipe Size 32 mm Pipe Material MS PIPE INSULATION Make kflex Material Elastomeric Nitrile rubber Fire performance Class ‘O’ (FM APPROVED) Thickness 25 mm Temperature range (maximum& minimum) 105°C & -40°C Thermal conductivity at 20°C 3Way Valve with Actuator Make Valve Model Number Actuator model number Size Qty Ball Valves Make Size Qty Balancing Valves Make Size Qty 0.036 w/m degK Honeywell / Siemens V5013P1010 ML74208088-E 25 mm 1no. L&T or its equivalent 32 mm 6 Nos. Advance or its equivalent 32 mm 1No. CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 20 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 32. 33. DESCRIPTION Strainer Make Size Qty Drain Valve Make Size Qty 34. 35. 36. 37. 38. 39. Air Vent Valve Make Size Test port Make Size HOT WATER MANIFOLD: Pipe Size Pipe Material PIPE INSULATION SPECIFICATIONS AS PER DESIGN QUALIFICATION Creative/Zoloto or its equivalent 32 mm 1No. Zoloto/L&T or its equivalent 20 mm 1No. Anergy or its equivalent 15 mm Anergy or its equivalent 8mm 25 mm MS Make kflex Material Elastomeric Nitrile rubber Fire performance Class ‘O’ (FM APPROVED) Thickness 25 mm Temperature range (maximum& minimum) 105°C & -40°C Thermal conductivity at 20°C 0.036 w/m degK 2 WAY VALVE WITH ACTUATOR Make Honeywell /Siemens Model Number V5011P1004 Actuator model number ML74208088-E Size 25 mm Qty 1no. Ball Valves Make L&T or its equivalent Size 25 mm CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 21 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO 40. 41. 42. 43. 44. 45. DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Qty 5 Nos. Balancing Valves Make Advance or its equivalent Size 25 mm Qty 1No. Strainer Make Creative /Zoloto or its equivalent Size 25 mm Qty 1No. Drain Valve Make Zoloto/L&T or its equivalent Size 20 mm Qty 1No. Air Vent Valve Make Anergy or its equivalent Size 15 mm Test port Make Anergy or its equivalent Size 8mm PRE-COOLIG COIL MANIFOLD Manufacturers name M/s. Hyderabad Coils Serving to AHU- FRESH AIR No. of Rows 4 Coil size (fin Width. X fin 24” X 24” height) Fins/ Inch 12 FPI Fins MOC Aluminum Size of manifold 40 NB Pipe Material of manifold Make of Ball Valves Qty Make of Strainer Size Qty Make of Balancing Valve MS or its equivalent L&T 2 Nos Marck or its equivalent 40 mm 01 No’s Advance CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 22 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Size 40 mm Qty 01 No’s POST HEATING COIL MANIFOLD 46. 47. 48. Manufacturers name Serving to No. of Rows Coil size (fin Width. X fin height) Fins/ Inch M/s. Hyderabad Coils AHU- FRESH AIR 2 Fins MOC Aluminum Size of manifold 40 NB 24” X 24” 12 FPI Pipe Material of manifold MS Make of Ball Valves L&T or its equivalent Qty 2 Nos Make of Strainer Marck or its equivalent Size 40 mm Qty 01 No’s Make of Balancing Valve Advance or its equivalent Size 40 mm Qty 01 No’s HEATERS Make Type Capacity THYRISTOR HEATING MODULE Make M/s Pharma Engineers Unit Serial Number Qty 01 No’s Type Double Skin Thermal Break Type Model TH-45 Location At service floor Overall dimensions (L X W X H) (MM) Capacity 45 KW Plenums Outer skin(MM) 0.8 mm PP GS sheet. CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 23 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Plenums Inner skin(MM) 0.6 mm PP GS sheet. Panel thickness(MM) 43±0.5 mm HVAC ELECTRICAL PANEL (CENTRALIZED) 49. Make M/s. PHARMA ENGINEERS Type Compartmental Location Cable Entry Top HVAC ELECTRICAL PANEL (STAND ALONE) Make 50. M/s. PHARMA ENGINEERS Type Location Cable Entry Top VARIABLE FREQUENCY DRIVE Make Danfoss Serial Number 51. Model VLT HVAC basic Drive FC101 VFD Capacity (KW) for supply unit 3.7 K. W VFD Capacity (KW) for return unit 3.7 K. W INSTRUMENTATION DETAILS MAGNEHELIC GAUGES 52. Make Dwyer, U.S.A. Location AHU prefilter Range 0-25mm Qty 1 No’s Serial Number Location AHU fine filter Range 0-50mm Qty 1 No’s CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 24 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Serial Number Location AHU plenum HEPA Filter Range 0-50mm Qty 1 No’s Serial Number Location Rooms Range 0-60 Pa Qty 5 No’s Serial Number SENSOR DETAILS TEMPERATURE & RH SENSOR Make 53. Model Location Qty Serial Number DPT SENSOR Make 54. Model Location Qty Serial Number VELOCITY SENSOR Make 55. Model Location Qty Serial number 56. DUCTING: CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 25 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Material Manufacturer Fabrication standard/Year Duct leak test standard (only for Classified AHU’s) Duct seal class Duct leak testing pressure Galvanized steel sheet JINDAL / TATA/SAIL/UTTAM/ESSAR IS 655/2012 Thickness of Galvanized sheet 751 to 1520 mm - 22 G SMACNA 2012 C 2” W.G Up to 750 mm - 24 G 1521 to 2285 mm - 20 G Type of Gasket Supporting Rods Duct joint Bonding/sealant Rubber based gasket 8 mm G.I threaded rod MS angle frames for Classified AHU TDF for unclassified AHU Silicone based sealant INSULATION: 57. Make Type Thermal Conductivity ‘K’ valve, Density Kg / m3 Temperature range Finishing material Fire performance Thickness THERMOBREAK Cross linked polyolefin foam 0.032 W/mK @ 23° C 25 -80 Deg.C to +100 Deg.C Aluminum foil Class “0” 19mm For Supply & 13 mm For Return Ducts SUPPLY AIR TERMINAL MODULE Make M/s PHARMA ENGINEERS 58. Module MOC Grill MOC Thickness of sheet Damper GI POWDER COATED SS 304 1.2 mm In built with housing TERMINAL HEPA FILTERS IN ROOM 59. Make of Filter Type of filter AAF Flange type CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 26 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION Filter Media Compatibility of water wash Filter Test method Filter classification as per EN 779 Average Efficiency at MPPS Equivalent particle size in terms of market language I.P.D of Filter (Approximate) F.P.D of Filter (Approximate) Hood Size HEPA Filter Size / CFM Qty SPECIFICATIONS AS PER DESIGN QUALIFICATION Micro Fiber Glass No EN 1822 H-14 99.995% 0.3 micron-Un authenticated data 250 ± 10 Pa 500 Pa Serial Number Room Name HEPA Filter Size / CFM Qty Serial Number SUPPLY AIR TERMINAL FOUR WAY DIFFUSERS Make 60. M/s SYSTEM AIR INDIA PVT LTD M/s PHARMA ENGINEERS Diffuser MOC Ceiling mounted square type horizontal air diffusion pattern Damper MOC Aluminum Room Name Diffuser Size Qty Room Name Diffuser Size Qty CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 27 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION SUPPLY AIR TERMINAL GRILLES (Linear Grilles) Make 61. M/s SYSTEM AIR INDIA PVT LTD M/s PHARMA ENGINEERS Material Of Construction Extruded Aluminum Damper MOC Al. extruded Room Name Grill Size Qty Room Name Grill Size Qty RETURN AIR TERMINAL MODULE Make M/s PHARMA ENGINEERS 62. Module MOC Grill MOC Thickness of sheet Room Name Hood Size Qty Room Name Hood Size Qty GI POWDER COATED SS 304 1.2 mm RETURN AIR TERMINAL FOUR WAY DIFFUSERS Make 63. M/s SYSTEM AIR INDIA PVT LTD M/s PHARMA ENGINEERS Diffuser MOC Ceiling mounted square type horizontal air diffusion pattern Damper MOC Aluminum Room Name Diffuser Size Qty CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 28 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION Room Name Diffuser Size Qty RETURN AIR TERMINAL GRILLES (Linear Grilles) Make 64. M/s SYSTEM AIR INDIA PVT LTD M/s PHARMA ENGINEERS Material Of Construction Extruded Aluminum Damper MOC Al. extruded Room Name Grill Size Qty Room Name Grill Size Qty RETURN AIR RAISERS Make Riser MOC Damper MOC Riser Grill MOC 65. Riser Filter Make Type of filter Filter Media Compatibility of water wash Filter Test method Filter classification as per EN 779 Average arrestance of synthetic dust Equivalent particle size in terms of market language Room Name Riser Size M/s. Pharma engineers GI Powder Coated Aluminum SS 304 M/s Pharma Engineers Flange / Box Synthetic Yes EN-779 G-4 90 ≤ Am 10 micron-Un authenticated data CRITERIA FULFILLED (YES/NO) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 29 of 37 INSTALLATION QUALIFICATION (IQ) SR.NO DESCRIPTION SPECIFICATIONS AS PER DESIGN QUALIFICATION CRITERIA FULFILLED (YES/NO) Filter Size / CFM Qty Serial Number Room Name Riser Size Filter Size / CFM Qty Serial Number ACCEPTANCE CRITERIA Dimensions and supply connections of the system should comply with DQ document and as built drawings. However, the acceptance is up to the judgment of experts if any deviations in the readings REMARKS (IF ANY): Test Conducted By Test Witnessed By Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 30 of 37 INSTALLATION QUALIFICATION (IQ) 4. VERIFICATION OF LEAKAGE IN DUCTING PURPOSE: To ensure that the ducting was Fabricated as per IS 655/2012 and leak test for classified AHU are performed as per SMACNA 2012 PRE-REQUISITES: 1. 2. 3. 4. Full tightened nut and bolts in the flanges of the erected duct network. Duct leak test machine Flexible pipe Dummy plate connector TEST PROCEDURE: 1. Before starting up the test procedure all the required instruments and tools to be arranged to the work location. 2. Fix the dummy plate connector to one end of the duct to be tested. 3. Make sure that all the flanges are tightened properly with gasket and the other end of the duct was closed with dummy sheet. 4. Now, connect one end flexible hose pipe to the connector fixed to duct and the other end to the test rig. 5. Now, switch on the leak tester and feed the required data in the HMI, like date, AHU No., area of ducting, Seal class, static Pressure and leak factor etc., 6. The test rig has two blowers, first start with one pump and increase the speed of blower gradually until it achieves the required pressure, if not switch on the second blower and increase the speed gradually until it achieves the required pressure duct pressure as specified. 7. If desired pressure is not achieved check for any leakages in duct. 8. Let the system run for 2-4 minutes to stabilize. 9. Now, print the results and observe the status in the printed data and verify the leakage falls under acceptable range and the test is passing. Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 31 of 37 INSTALLATION QUALIFICATION (IQ) 10. If the test fails, verify for any leakages at all tangential joints and tight it properly and repeat the test again as per the above steps. 11. After completion of test, remove the hose connector piece and close the opening with dummy piece at the duct end. 12. Repeat this test for main ducts. 13. Duct leak test report is enclosed with this document. Duct Pressure Class / Seal Class / Air Leakage Class as per SMACNA Standards Reprinted =Table: E-1 (HVAC AIR DUCT LEAKAGE TEST MANUAL--- 2nd Edition 2012) Duct Pressure Class 1”, 2” WG. 3” WG 4”, 6” WG Seal Class C B A Sealing Requirement All Transverse Joints All Transverse & Longitudinal Seams All Transverse Joints, Longitudinal Seams & Wall Penetrations Rectangular Duct Class 16 Class 8 Class 4 Appendix E: SMACNA -- HVAC AIR DUCT LEAKAGE TEST MANUAL Leakage Factor “Lf” - CFM / 100 Sq. ft of Duct Pressure (P) In. wg P 0.65 1.0 Leakage Class (CL) Class 2 Class 4 Class 8 Class 16 1.00 2.0 4.0 8.0 16.0 2.0 1.57 3.1 6.3 12.6 25.1 3.0 2.04 4.1 8.2 16.3 32.7 4.0 2.46 4.9 9.8 5.0 2.85 5.7 11.4 6.0 3.20 6.4 12.8 F = CL (P 0.65) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 32 of 37 INSTALLATION QUALIFICATION (IQ) Duct Pressure class is decided based on pressure generated by terminal filters. As pressure of terminal filter is 50mm. Hence 2” static pressure is selected. ACCEPTANCE CRITERIA: Result must be ‘PASS’ it ensures that the duct fabrication is satisfactory. This test must be completed for at least 60% to 70% of main ducts. REMARKS (IF ANY): Performed By Checked By Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 33 of 37 INSTALLATION QUALIFICATION (IQ) 5. VERIFICATION OF MANIFOLD LEAK TEST (HYDRO TEST) PURPOSE: To ensure that the piping manifold installed to AHU is free from leakages. PRE-REQUISITES: 1. 2. 3. 4. Full welded joints. Duly calibrated Pressure gauge Hydraulic Pump Isolation of System for performing test TEST PROCEDURE: 1. First fill up the water distribution loop with DM/Purified water. 2. Close the return line of loop by means of Blind TC/Return line valve to pressurize the distribution loop 3. Connect the Hydro pump at the supply line side with adequate range of pressure gauge 4. Pressurize the distribution loop system up to 1.5 times of design pressure with help of hydro pump 5. Observe the pressure gauge reading after achieving the required pressure in the loop 6. Hold this pressure for minimum 30 minutes. 7. Observe for any Pressure drop/Leakage in the distribution loop 8. If at all there is any leakage in the loop, Rectify the same & Repeat the Procedure 9. Release the pressure and put the loop in operation. 10. Test results are enclosed with this document. ACCEPTANCE CRITERIA: Manifold must be free from leakages it ensures that the manifold fabrication is satisfactory. However, the acceptance is up to the judgment of experts if any deviation in the readings. Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 34 of 37 INSTALLATION QUALIFICATION (IQ) TEST REPORT FOR MANIFOLD LEAKAGE (HYDRO TEST) Purpose: To determine fluid leakage in manifold Type of manifold Date of Test INSTRUMENT / EQUIPMENT USED Name of instrument / equipment Make of Master pressure gauge Make Range Serial number Calibrated on Calibration Due TEST RESULTS SR.NO Performed By START TIME END TIME PRESSURE GAUGE READING REMARKS (IF ANY) Checked By Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 35 of 37 INSTALLATION QUALIFICATION (IQ) 6. VERIFICATION OF CALIBRATION OF INSTRUMENTS: S.no. Instrument Type Location Instrument Tag Number Calibrated on Calibration Due 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. REMARKS (IF ANY): Submitted By Checked By Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 36 of 37 INSTALLATION QUALIFICATION (IQ) 7. LIST OF DOCUMENTS ENCLOSED S.No Drawing Name 1. Testing Certificate For AHU 2. Testing Certificate For Blower 3. Testing Certificate For Motor 4. Testing Certificate For Dehumidifier Bed 5. Testing Certificate For Dehumidifier Bed Blower / Motor 6. Testing Certificate For Reactivation Blower / Motor 7. Testing Certificates For Ahu Filters 8. Testing Certificate For Chilled Water Coil 9. Testing Certificate For Hot Water Coil 10. Testing Certificate For Steam Coil 11. Testing Certificate For Volume Control Damper 12. Testing Cerrticate For Fire Damper 13. Testing Cetificate For Actuator For Fire Damper Testing Certificate for Chilled Water Manifold and All Related Fitting And Accessories Testing Certificate for Hot Water Manifold and All Related Fitting And Accessories Testing Certificate For Steam Manifold And All Related Fitting And Accessories Testing Certificates For Pipe Insulation Testing Certificates For Actuators For Control Valves Testing Certificate For Thyristor Module Testing Certificates For Control Panel Testing Certificate For Variable Frequency Drive Calibration Certificate For Magnehelic Gauge Calibration Certificate For T&RH Sensor Calibration Certificate For DPT Sensor Calibration Certificate For Velocity Sensor Testing Certificate For Ducting Testing Certificate For Duct Insulation 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. Enclosed (Yes / No) Client: Supplier/ Manufacturer: PHARMA ENGINEERS, HYDERABAD Equipment: HVAC SYSTEM FOR AHU-01 Page 37 of 37 INSTALLATION QUALIFICATION (IQ) 28. 29. 30. 31. 32. 33. 34. 35. Testing Certificate For Terminal Module Testing Certificate For Terminal Filters Testing Certificates For Diffusers Testing Certificates For Grilles Testing Certificates For Risers Testing Certificate For Riser Filter Duct Leak Test Report Manifold Leak Test Report (Hydro Test) REMARKS (IF ANY): Submitted By Checked By