AC 12 Plumbing is defined as art & science of installing pipes , fixtures & other apparatus to convey the supply water in building & to discharge & dispose waste water & other liquids, gases & other substances out of building in a safe, orderly, healthy & sanitary way to ensure the health & sanitation of life & property. Plumber – is a title given to a person who is skilled in a field of sanitation Water Supply – In absence of an efficient water supply & distribution system, water was provided Through abundant rainfall, spring, well, rivers or creeks conveyed either improvised bamboo pipes or carried either by man himself or through animal drawn carts or sleds & stored in an earthen jar, wooden or bamboo containers. In those times, water was considered fit for consumption as long it was visibly clear. There was no available means to test the water form purity & free from disease causing organism. Waste Disposal – Majority of the household cannot afford plumbing installation in their homes, availed possible means of convenience for their waste disposal. Some excreted in the rivers, seashores, creeks or any water wastes behind trees, bushes or any secluded place as long as during the time they excreted, they private parts were not seen in public. Objectives of Plumbing To supply water to different parts of the building. To remove discharge human waste & other substances out of building into the public sewer septic tank. Conditions for an Effective Water Supply In Building To provide sufficient amount of water to supply each fixtures To prevent back flow of used water into the water supply system. The Drainages System, should be Accomplished by the Following Fast removal of the waste with a minimum probability of leakage & stoppage of drains To prevent the entry of house vermin & obnoxious gases into the house from piping system. Mandatory Requirements for a Drainage System All Plumbing design & installations are governed by a set of rules & limitations prescribed by the National Plumbing Code, which provides that: All drainage system must conform with a set of requirements enumerated as follows; That, all pipes joints must be well fitted & tightly connected with each other to prevent leakage of gas & liquid. That, the drainage pipe should be graded of inclined properly for a downward gravity flow of water towards the main sewer line or in the septic tank. That, the drainage pipe should be provided with adequate clean-out, accessible for repair in case of stoppage. The drainage system, must be provided with ventilation pipe that will convey gases to the atmosphere where it can do no harm to human health. That, Except for water closet, each fixtures shall be provided with suitable trap that will prevent back flow of gases. That, the drainage system must be vented , to avoid siphonage or back flow of the water seal. Waste is classified into two types Solid Waste that being discharge by water closet Liquid Waste that are coming from various fixtures Two Types of Drainage Piping Soil Pipe – those pipes that conveys waste coming from water closet Waste Pipe – Any pipe that coveys waste from various fixtures other than water closet The Drainage Installation is Sometimes Referred to as DWV D – for drainage of solid waste W – for waste coming from various fixtures than water closet V – refers to the ventilation of the piping system Definition of Terms Air Gap – in a water supply system, is the unobstructed vertical distance through the free of atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixtures, or other device & the flood level rim of the receptacle. Back flow – is the flow of water or any liquid mixture or substances into the disturbing of pipes of a portable supply of water from any source, other than its intended sorce. Back Siphonage – refers to the back flow of us terminated or polluted water from a plumbing fixtures or vessel into a water supply pipe due to a negative pressure in such pipe Battery of Fixture – Refers to any group of two more similar adjacent fixtures which discharges into a common horizontal waste pipe or soil branch Bib – is synonymous with faucet, tap, plug, etc. The word faucet is preferred. Blind Flange – a flange that closes the end of a pipe There is no opening for the passage of water Blow off – A controlled outlet on a pipeline used to surcharge water. Branch – is any part of piping system other than the main riser or stack. Branch interval – is the length of a soil or waste stack corresponding in general to a storey height , but in no case, less than 2.4m within which the horizontal branches from one floor or storey of a building are connected to the stack. Branch Vent – is a vent connecting one or more individual vents with a stack or stack vent Calking – is plugging an opening with oakum, lead or other materials that are pounded into the place or opening. Circuit Vent – is a branch vent that serves two or more traps & extends from the front of the last fixtures connection of a horizontal branch to the vent stack. Continuous vent – is the vertical vent that is a continuation of the drain to which the vent connects Combination Fixtures – is the fixtures combining the sink & tray or a two or three compartment sink or tray in on vent. Combination waste & vent system – is a specially designed system of waste piping embodying the horizontal wet venting of one or more sinks or floor drains by means of common waste & vent pipe adequately sized to provide free movement of an above the flow of the drain. Most Popular kind of Materials used in Plumbing Installation Cast Iron Soil Pipe Acid Resistant Cast Iron Pipe Asbestos Pipe Bituminous Fiber Sewer Pipe Vitrified clay Pipe Lead Pipe Galvanize Steel Pipe Galvanizes Wrought Pipe Brass Pipe Copper Pipe Plastic or synthetic pipe Stainless steel pipe The choice & kind of pipe to be installed depends upon the following considerations Quality & durability Resistance to external & internal contact with foreign matters. Resistance to acid waste & other chemical elements that will pass into it Cost of materials & labor Cast Iron Pipes The most popular & generally specified materials for drainage system in building. Durable, conveniently installed & answer to the most plumbing needs of all types of building less than 25 storey high. 25 storey high building do not specify to use of Cast Iron Pipes because on constant vibrations which causes water leak of the pipe joints. Affected by corrosion caused by carbon dioxide , sulfur oxide & methane gases forming solutions of carbonic & sulfuric acid Cast Ion Pipes has Four Varieties Standard Pipe Single Hub Pipe Double Hub Pipe Hubless Pipe Two Types of Cast Iron Pipes SV Type – which generally used for building installations XV Type – classified as extra duty pipe used for underground installations Single Hub Pipes Double Hub Pipes Hubless Pipe Pipe Fittings Acid Resistant Cast Iron Pipes Is made fro m alloy of cast iron & silicon. Widely used in chemical laboratories, industries & other installations where acid waste are being discharge Asbestos Pipe Is made from asbestos fibers & Portland Cement . The thickness of the pipe is twice as that of standard cast iron pipes. Used as soil, was, ventilation & downspout Bituminous Fiber Sewer Pipe Is cheaper among the sewer pipes Sometimes recommended for sewer & septic tank installation. Light in weight , slightly flexible which can take slightly soil movement Excessive hot water & chemical may soften or damage the pipe Vitrified Clay Pipe One of the oldest material used for sewer line s. Made out from clay , cast into length of 75 cm treated with glazing compund Lead Pipe Highly Resistant to acid & is suitable for underground installation . But because lead is poisonous & injurious to human health, it is never use to convey water for human consumption Galvanized Steel Pipe Made out from steel, drawn through a die & welded, cast into 6 meters. Easily corroded by alkaline & acid water. Deteriorate faster when used as hot water supply line. Galvanize Wrought Iron Pipe Better quality steel pipe for plumbing installation. More resistant to acid waste than the steel pipes Copper Pipe Durable & extremely corrosive resistant material; Easy to install compared to other pipes. Classified into three types K type is the heaviest, suitable for underground L type is lighter than K type available in rigid & flexible form.. Commonly used in residential water supply line & radiant heating installations M type is the thinnest & available only in rigid form. Designed for small water supply line & for radiant heating installations The collection & safe disposal of human waste was the most critical problems of environmental health. Common diseases reported such as dysentery, typhoid, diarrhea & other intestinal disorder are prevalent in areas where there is no proper & scientific Sewer Sewage Disposal. Types of Sewage System The Cesspool The Privy The Septic Tank The Public Sewer Line The Cesspool Is a hole in the ground curved with stones, bricks, chb or other materials laid in such a manner as to allow raw contaminated sewage to leach into soil. The organic waste accumulate & finally dispose of by disintefration The Privy Is a concrete sealed vault with a wooden shelter constructed for the collection raw sewage. The disintegration of excrement is accomplishment in the same manner as in a cesspool. The Septic Tank The septic tank is a device or receptacle used to expedite the decomposition of the element contained in a raw sewage waste. Raw sewage waste consist of water & a settleable solid called oirganic materials that can be percipitated in a septic tank in a very short time The Public Sewer Line Operated & Maintained by the government consisting of a sewage treatment plant that conveys the raw sewage from building to houses to a disposal system. Of these four types of sewage disposal, the cesspool & privy are obsolete. Sanitary Authorities agreed in principles For a family of 6 persons, the minimum tank capacity should be approximately 1.3 cum with a minimum size of 90 cm wide by 150 cm long & 120 cm depth. A very large tank is not advisable , because the bacterial activities would be retarded. For residential installation, the practice is to allow 5 to 6cu.ft of tank volume per person. Technical Data in Determining Volume of Septic Tank Minimum Width – 90 cm Minimum Length -150 cm Minimum Depth – 120 cm For Residential Buildings to serve larger number of people , allocate or liquid per person – 0.14 to 0.17 cum For small residential house to serve up to 12 persons, the chamber should have a liquid content of not more than - 2.0 cum For school, commercial & industrial establishments, the volume of the septic tank should not be less than - 0.057 cum nor more than – 0.86 cum per person When large amount of water waste is coming from the shower, bath, laundry & others, it is not advisable to permit entry to these waters into septic tank. All downspout collecting water from the roof should not be allowed to terminate into the septic tank. Rainwater should be conveyed to the storm drain. Sample Problem Determine the size of a septic tank to serve 200 persons in a commercial establishment Step by Step Solution To determine the volume of the septic tank , refer to the Technical Data of information . For a commercial establishment, we find a value of 0.057 cum. 200 persons x 0.057 cum = 11.4 cum Assume 1.2 meters width of the tank per 100 persons. For 200 individuals multiply: 200 persons 1.2 m = 2.40 width The maximum depth of a septic tank liquid is 1.50 meters. Solve for the length of the septic tank. L x W x depth = Volume L = (Volume / Width x depth) L = (11.40 / (2.4 x 1.50)) L = 3.20 m The value of L is only for the length of the digestion chamber. Divide by 2 then add result to the value of L to include the leaching well. (L/2)+L = (3.20m/2)+3.20m = 4.80 m Therefore, the size of a septic tank to serve 200 persons is 2.40 m wide by 4.80 m long Sample Problem 2 A motel with toilet & bath , kitchen facilities will serve a maximum of 100 persons. Determine the capacity & dimension of the septic tank. Solution Refer to table 4-2. Under motel with batch & kitchen, the waste per person per day is 50 gallons. Multiplied by 100 persons is 5000 gallons a day. Using the formula: V=1.125+0.75Q Where: V = Liquid volume of the tank in gallons Q = The Daily sewage flow in gallons. 1.125 & 0.75 is constant. Substitute, V = 1.125+(0.75 x 5000 gallons V=3,751 gallons There are 264 gallons in 1 cubic meter volume ; (3,751/264) = 14.2 cum capacity of septic tank. To find the dimensions of the septic tank if the maximum depths is 1.50 m & the width is assumed to be 3 m; L=(14.2cum)/(3m x 1.50 m) = 3.50 m Location of Septic Tank The septic tank may be located closer to the building it will serve. Providing a minimum distance of 2m from outside wall As mush as possible, the septic tank should not be located closer to the doors or windows Septic tank should be at least 15 m away from any source of water supply. The farther the better. Requirements for a Satisfactory Disposal of Human Waste There should be no contamination of ground surface that may enter into the spring or wells There should be no contamination of surface water The surface soil should not be contaminated. Excreta should not be accessible to animals, flies, cockroaches, vermin & the like There should be no odor & unslightly conditions The methods used should be simple & economical in terms of construction operation. Safety Precautions In most cases septic tanks are poorly aerated or ventilated. It lacks free oxygen. An individual entering into a septic tank for making repairs or cleaning purposes, may meet almost instant death. Septic tank may contain harmful & dangerous gases. Septic Tank may contain inflammable gases that might be ignited to cause a terrific explosion. Sewage Treatment Activated sludge process Trickling or sprinkling filter process Introduction In Study of Plumbing, it is important to know the different parts of the piping installations & their functions. The effectiveness of plumbing installation depends upon the strict observance of the natural laws of nature such as; Gravity Atmospheric Pressure Most of the failure encountered in Plumbing Installation Non Observance of these natural laws Grave abuse of its function Major Components of Drainage Installation of a Plumbing System Drainage – refers to an installation that receives & conveys discharge from water closet with or with or without waste coming from other fixtures. Waste Pipe – is any pipe in a drainage installation that receives the discharges of any fixtures except water closet & conveys the same to the soil branch, soil pipe or house drain. Fixtures refers to slop sink lavatory , urinals , bathtub & the like except water closet. Vent Pipe – functions as air passage or conduit to ventilate the drainage & waste pipe installation. Soil branch – refers to a horizontal pipe affixed by the word soil. The word soil connotes a pipe receiving discharge from water closet If this soil branch does not receive discharge from water closet but from other fixtures only. It will be classified as waste pipe. Soil Stack – is a vertical pipe installation where the soil branches terminate.. The pipe is called stack being installed vertically. The word soil is affixed because it receive human waste from the soil branch. Otherwise, it will again classified as Waste Syack General Conditions for a good Waste pipe Installation By making the right choice of material By conservative use of fittings Right location of the cleanouts Right slope or grade of the pipe line The design of the water distribution system shall conform to accepted engineering practice. Methods utilized to determine pipe sizes shall be approved. System Interconnection At the points of interconnection between the hot and cold water supply piping systems and the individual fixtures, appliances or devices, provisions shall be made to prevent flow between such piping systems. Water Distribution System Design Criteria The water distribution system shall be designed, and pipe sizes shall be selected such that under conditions of peak demand, the capacities at the fixture supply pipe outlets shall be not less than shown in Table 604.3 . The minimum flow rate and flow pressure provided to fixtures and appliances not listed in Table 604.3 shall be in accordance with the manufacturer's installation instructions. TABLE 604.3 WATER DISTRIBUTION SYSTEM DESIGN CRITERIA REQUIRED CAPACITY AT FIXTURE SUPPLY PIPE OUTLETS For SI: 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 3.785 L/m.For additional requirements for flow rates and quantities, see Section 604.4 Where the shower mixing valve manufacturer indicates a lower flow rating for the mixing valve, the lower value shall be applied. Maximum Flow and Water Consumption The maximum water consumption flow rates and quantities for all plumbing fixtures and fixture fittings shall be in accordance with Table 604.4 For SI: 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa.A hand-held shower spray is a shower head. Consumption tolerances shall be determined from referenced standards. Exceptions Blowout design water closets having a water consumption not greater than 31/2 gallons (13 L) per flushing cycle. Vegetable sprays. Clinical sinks having a water consumption not greater than 41/2 gallons (17 L) per flushing cycle. Service sinks. Emergency showers. Size of Fixture Supply The minimum size of a fixture supply pipe shall be as shown in Table 604.5. The fixture supply pipe shall terminate not more than 30 inches (762 mm) from the point of connection to the fixture. A reducedsize flexible water connector installed between the supply pipe and the fixture shall be of an approved type. The supply pipe shall extend to the floor or wall adjacent to the fixture. The minimum size of individual distribution lines utilized in gridded or parallel water distribution systems shall be as shown in Table 604.5. or SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa.Where the developed length of the distribution line is 50 feet or less, and the available pressure at the meter is 35 psi or greater, the minimum size of an individual distribution line supplied from a manifold and installed as part of a parallel water distribution system shall be one nominal tube size smaller than the sizes indicated. Variable Street Pressures Where street water main pressures fluctuate, the building water distribution system shall be designed for the minimum pressure available. Inadequate Water Pressure Wherever water pressure from the street main or other source of supply is insufficient to provide flow pressures at fixture outlets as required under Table 604.3, a water pressure booster system conforming to Section 606.5 shall be installed on the building water supply system. Water Pressure-Reducing Valve or Regulator Where water pressure within a building exceeds 80 psi (552 kPa) static, an approved water pressure-reducing valve conforming to ASSE 1003 or CSA B356 with strainer shall be installed to reduce the pressure in the building water distribution piping to not greater than 80 psi (552 kPa) static. Exception: Service lines to sill cocks and outside hydrants, and main supply risers where pressure from the mains is reduced to 80 psi (552 kPa) or less at individual fixtures. Valve Design The pressure-reducing valve shall be designed to remain open to permit uninterrupted water flow in case of valve failure. Repair and Removal Water pressure-reducing valves, regulators and strainers shall be so constructed and installed as to permit repair or removal of parts without breaking a pipeline or removing the valve and strainer from the pipeline. Water Hammer The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quickclosing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer's instructions. Water-hammer arrestors shall conform to ASSE 1010. Gridded and Parallel Water Distribution System Manifolds Hot water and cold water manifolds installed with gridded or parallel connected individual distribution lines to each fixture or fixture fitting shall be designed in accordance with Sections 604.10.1 through 604.10.3. Valves Individual fixture shutoff valves installed at the manifold shall be identified as to the fixture being supplied. Access shall be provided to manifolds with integral factory- or field-installed valves. Soil and Ground Water The installation of a water service or water distribution pipe shall be prohibited in soil and ground water contaminated with solvents, fuels, organic compounds or other detrimental materials causing permeation, corrosion, degradation or structural failure of the piping material. Where detrimental conditions are suspected, a chemical analysis of the soil and ground water conditions shall be required to ascertain the acceptability of the water service or water distribution piping material for the specific installation. Where detrimental conditions exist, approved alternative materials or routing shall be required. Lead Content of Water Supply Pipe and Fittings Pipe and pipe fittings, including valves and faucets, utilized in the water supply system shall have not more than 8-percent lead content. Lead Content of Drinking Water Pipe and Fittings Pipe, pipe fittings, joints, valves, faucets and fixture fittings utilized to supply water for drinking or cooking purposes shall comply with NSF 372 and shall have a weighted average lead content of 0.25 percent or less. Identification of Nonpotable Water Systems Where nonpotable water systems are installed, the piping conveying the nonpotable water shall be identified either by color marking, metal tags or tape in accordance with Sections 608.8.1 through 608.8.2.3. Signage Required Nonpotable water outlets, such as hose connections, open ended pipes and faucets, shall be identified with signage that reads as follows: "Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER — DO NOT DRINK." The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant waterproof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inch (12.7 mm) in height and in colors in contrast to the background on which they are applied. In addition to the required wordage, the pictograph shown in Figure 608.8.1 shall appear on the required signage. Distribution Pipe Labeling and Marking Nonpotable distribution piping shall be purple in color and shall be embossed, or integrally stamped or marked, with the words: "CAUTION: NONPOTABLE WATER — DO NOT DRINK" or the piping shall be installed with a purple identification tape or wrap. Pipe identification shall include the contents of the piping system and an arrow indicating the direction of flow. Hazardous piping systems shall also contain information addressing the nature of the hazard. Pipe identification shall be repeated at intervals not exceeding 25 feet (7620 mm) and at each point where the piping passes through a wall, floor or roof. Lettering shall be readily observable within the room or space where the piping is located. Color The color of the pipe identification shall be discernable and consistent throughout the building.