Uploaded by jmariga

GroundingBondingFactSheet

advertisement
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC®
Grounding Conductor, Equipment (EGC) — The conductive
path(s) that provides a ground-fault current path and connects
normally non-current-carrying metal parts of equipment
together and to the system grounded conductor or to the
grounding electrode conductor, or both.
Article 250 is a foundational pillar of NFPA 70®, National
Electrical Code® (NEC®), and the tables within Article 250
are critical resources for sizing the wiring for the grounding
and bonding of an electrical system. Becoming more familiar
with the proper use of these tables can help installers ensure
effective grounding and bonding on their projects and, in turn,
help ensure the safety of those within the building.
� These are often called “ground” conductors in the trade.
Section 250.119 requires these conductors to be bare,
covered, or insulated. Covered or insulated equipment
grounding conductors shall have a continuous outer finish
that is either green or green with one or more yellow stripes.
Essential NEC Terms for Understanding Article 250
Grounding Electrode — A conducting object through which a
direct connection to the earth is established.
Having a good understanding of the terms used within Article
250 is critical to understanding the grounding and bonding
requirements within the NEC®. The following definitions are
commonly used throughout Article 250, and knowing them
is essential to installing an effectively grounded and bonded
electrical system.
� Section 250.52(A)(1–8) lists the permissible grounding
electrode options. While all the available grounding
electrodes are required to be bonded per 250.50, it’s fair to
say the most common are typically rod and pipe electrodes
(i.e., ground rods), which are listed in 250.52(A)(5), and
concrete-encased electrodes, which are listed in 250.52(A)(3).
Often, concrete-encased electrodes consist of rebar that is
embedded in the concrete footings of a building.
Ground — The earth.
Grounded (Grounding) — Connected (connecting) to ground
or to a conductive body that extends the ground connection.
� An example of a conductive body that extends the ground
Grounding Electrode Conductor — A conductor used
to connect the system grounded conductor or the
equipment to a grounding electrode or to a point on the
grounding electrode system.
connection is the first 5 feet of a water pipe entering a
building. It is permitted to connect at this point even
though it is not a grounding electrode, as the first 5 feet of
the pipe is not physically in contact with the earth.
� This is the conductor that connects the grounding
Grounded Conductor — A system or circuit conductor that is
intentionally grounded.
electrodes to the electrical system.
Ground-Fault Current Path — An electrically conductive path
from the point of a ground fault on a wiring system through
normally non-current-carrying conductors, equipment, or the
earth to the electrical supply source.
� These are often regarded as “neutral” conductors in the
trade. Section 200.6 requires these conductors to be
identified as continuous white, continuous gray, or having
three continuous white or gray stripes along the conductor’s
entire length on other than green insulation. Be mindful
that grounded conductors can also be phase conductors in
certain applications.
Effective Ground-Fault Current Path — An intentionally
constructed, low-impedance electrically conductive path
designed and intended to carry current under ground-fault
1
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued
Bonding Jumper, System — The connection between the
grounded circuit conductor and the supply-side bonding
jumper, or the equipment grounding conductor, or both, at a
separately derived system.
conditions from the point of a ground fault on a wiring system
to the electrical supply source and that facilitates the operation
of the overcurrent protective device or ground-fault detectors.
� An effectively designed ground-fault current path will allow
for circuit breakers, fuses, and ground-fault detectors to
open properly when ground-fault conditions arise within the
electrical system.
Sizing Grounding Electrode Conductors
Using Table 250.66
Bonded (Bonding) — Connected to establish electrical
continuity and conductivity.
Table 250.66 of the NEC is used to size grounding electrode
conductors for alternating-current systems located at the
service, at each building or structure where supplied by a
feeder(s) or branch circuit(s), or at a separately derived
system, such as on the load side of transformers.
Bonding Conductor or Jumper — A reliable conductor to
ensure the required electrical conductivity between metal parts
required to be electrically connected.
Bonding Jumper, Equipment — The connection between two or
more portions of the equipment grounding conductor.
This table shows you how to use the size of your largest
ungrounded (hot) conductor to determine the necessary size
of your grounding electrode conductor. Where you have two or
more sets of service-entrance conductors run in parallel, the
Bonding Jumper, Main — The connection between the
grounded circuit conductor and the equipment grounding
conductor at the service.
Table 250.66 Grounding Electrode Conductor for
Alternating-Current Systems
Size of Largest Ungrounded
Conductor or Equivalent Area for
Parallel Conductors
(AWG/kcmil)
Ungrounded service
conductors
Grounded service conductor
Supply side equipment
bonding jumper
Size of Grounding
Electrode Conductor
(AWG/kcmil)
Copper
Aluminum or
Copper-Clad
Aluminum
Copper
Aluminum or
Copper-Clad
Aluminum
2 or smaller
1/0 or smaller
8
6
1 or 1/0
2/0 or 3/0
6
4
2/0 or 3/0
4/0 or 250
4
2
Over 3/0
through 350
Over 250
through 500
2
1/0
Over 350
through 600
Over 500
through 900
1/0
3/0
Grounded electrode
conductor
Over 600
through 1100
Over 900
through
1750
2/0
4/0
Main bonding jumper (may
be wire, bus, or screw)
Over 1100
Over 1750
3/0
250
Neutral bus
Notes:
1. If multiple sets of service-entrance conductors connect directly to a
service drop, set of overhead service conductors, set of underground
service conductors, or service lateral, the equivalent size of the largest
service-entrance conductor shall be determined by the largest sum of
the areas of the corresponding conductors of each set.
2. Where there are no service-entrance conductors, the grounding
electrode conductor size shall be determined by the equivalent size of
the largest service-entrance conductor required for the load to be
served.
3. See installation restrictions in 250.64.
Equipment grounding bus
Grounding electrode
A main bonding jumper installed at the service between the grounded
service conductor and the equipment grounding conductor.
2
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued
Sizing Grounding Electrode Conductors
and Bonding Jumpers
grounding electrode conductor must be sized according to the
largest sum of the corresponding conductors of each set. (See
the Application Example that follows the Table Tips.)
The exhibit below illustrates a grounding electrode conductor
(GEC) installed from service equipment or a separately
derived system to a water pipe grounding electrode. The GEC
is required by 250.66 to be sized based on the size of the
ungrounded supply conductors. The supply conductors could
be service conductors or, in the case of separately derived
systems, feeder conductors from a generator or other power
source or transformer secondary conductors.
Table Tips
1.Ensure that you are using the proper column(s) based
on the wire type you are installing—copper, aluminum, or
copper-clad aluminum.
2.Section 250.66(A) references connections to rod, pipe, or
plate electrodes. If the connection does not extend on to other
types of electrodes that require a larger size conductor, the
grounding electrode conductor is not required to be larger
than 6 AWG copper or 4 AWG aluminum wire.
The bonding jumpers that connect the other grounding
electrodes together must be sized using 250.53(C), which
refers to 250.66. GECs and bonding jumpers are permitted
to be sized based on the electrodes to which they connect,
as specified in 250.66(A), (B), or (C). However, if the GEC or
bonding jumper extends from this connection to an electrode
that is not specified in 250.66(A), (B), or (C), it must be sized
per Table 250.66.
3.Section 250.66(B) references connections to concreteencased electrodes, often referred to in the trade as “Ufer
ground.” If the connection does not extend on to other
types of electrodes that require a larger size conductor, the
grounding electrode conductor is not required to be larger
than 4 AWG copper wire.
In this exhibit, the sizes of the GEC and the bonding jumpers
are dependent on the electrode to which they are connected.
4.Section 250.66(C) references connections to ground rings.
If the grounding electrode conductor or bonding jumper
connected to a ground ring does not extend on to other
types of electrodes that require a larger size conductor, the
grounding electrode conductor is not required to be larger than
the conductor used for the ground ring.
3/0 AWG
ungrounded
service-entrance
conductors
Neutral
Service
equipment
Application Example: Parallel Conductors
A 3-phase, 800-A service is supplied using two 500 kcmil
THWN copper conductors per phase. The parallel
conductors are installed in two separate runs of rigid metal
conduit. Using Table 250.66, determine the maximum size
grounding electrode conductor required for this service.
Not required
to be larger than
6 AWG Cu
STEP 1. Determine the size of the largest ungrounded
conductor in each raceway.
4 AWG Cu grounding
electrode conductor
Not required to be
larger than 4 AWG Cu
4 AWG Cu
STEP 2. Determine the maximum size grounding
electrode conductor (GEC) required for this service.
SOLUTION. Two parallel 500 kcmil copper conductors:
Ground rod
Total equivalent area = 2 x 500 kcmil = 1000 kcmil
Then refer to Table 250.66 for the ungrounded conductor
and copper column values:
Underground metal
water pipe
Required to be not
less than 2 AWG Cu
1000 kcmil falls into the “Over 600 through 1100”
row = size 2/0 copper GEC.
Concrete-encased
electrode
Ground ring
GEC and bonding jumpers sized in accordance with 250.66 for a
service supplied by 3/0 AWG copper ungrounded conductors.
3
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued
The illustration is not intended to show a mandatory physical
routing and connection order of the bonding jumpers and
the GEC, as the NEC does not specify an order or hierarchy
for these connections. The sizes of the bonding jumpers to
the ground rod and the concrete-encased electrode shown
here are the maximum sizes required by the NEC based on
250.66(A) and (B). If the GEC from the service equipment is
run to the ground rod first and then to the water pipe, the GEC
to the ground rod is required to be sized based on Table 250.66
as if it were run to the water pipe electrode. The use of bonding
jumpers or GECs larger than those required by 250.66 is not
prohibited.
Table 250.102(C)(1) Grounded Conductor, Main Bonding
Jumper, System Bonding Jumper, and Supply-Side Bonding
Jumper for Alternating-Current Systems
Sizing Grounded (Neutral) Conductors and Bonding
Jumpers Using Table 250.102(C)(1)
Table 250.102(C)(1) is used to size the grounded conductor,
main bonding jumper, system bonding jumper, and supplyside bonding jumper for alternating-current systems. Keep
in mind that this table is for sizing grounded conductors
and the bonding jumpers listed, NOT for sizing grounding
electrode conductors, which must be done using Table
250.66.
Size of Largest Ungrounded
Conductor or Equivalent Area for
Parallel Conductors
(AWG/kcmil)
Size of Grounded Conductor
or Bonding Jumper*
(AWG/kcmil)
Copper
Aluminum or
Copper-Clad
Aluminum
Copper
Aluminum or
Copper-Clad
Aluminum
2 or smaller
1/0 or smaller
8
6
1 or 1/0
2/0 or 3/0
6
4
2/0 or 3/0
4/0 or 250
4
2
Over 3/0
through 350
Over 250
through 500
2
1/0
Over 350
through 600
Over 500
through 900
1/0
3/0
Over 600
through
1100
Over 900
through
1750
2/0
4/0
Over 1100
Over 1750
See Notes 1 and 2.
Notes:
1. If the ungrounded supply conductors are larger than 1100 kcmil
copper or 1750 kcmil aluminum, the grounded conductor or bonding
jumper shall have an area not less than 121∕2 percent of the area of the
largest ungrounded supply conductor or equivalent area for parallel
supply conductors. The grounded conductor or bonding jumper shall
not be required to be larger than the largest ungrounded conductor or
set of ungrounded conductors.
2. If the ungrounded supply conductors are larger than 1100 kcmil
copper or 1750 kcmil aluminum and if the ungrounded supply
conductors and the bonding jumper are of different materials (copper,
aluminum, or copper-clad aluminum), the minimum size of the
grounded conductor or bonding jumper shall be based on the assumed
use of ungrounded supply conductors of the same material as the
grounded conductor or bonding jumper and will have an ampacity
equivalent to that of the installed ungrounded supply conductors.
3. If multiple sets of service-entrance conductors are used as permitted
in 230.40, Exception No. 2, or if multiple sets of ungrounded supply
conductors are installed for a separately derived system, the equivalent
size of the largest ungrounded supply conductor(s) shall be
determined by the largest sum of the areas of the corresponding
conductors of each set.
4. If there are no service-entrance conductors, the supply conductor
size shall be determined by the equivalent size of the largest serviceentrance conductor required for the load to be served.
*For the purposes of applying this table and its notes, the term bonding
jumper refers to main bonding jumpers, system bonding jumpers, and
supply-side bonding jumpers.
Table 250.102(C)(1) uses the size of the largest ungrounded
(hot) conductor to determine the sizes of your grounded
(neutral) conductor and bonding jumpers. When sizing the
grounded conductor or jumper where two or more ungrounded
conductors are connected in parallel and the total equivalent
area is larger than 1100 kcmil copper or 1750 kcmil aluminum,
Table Note 1 requires the size to be not less than 12½ percent
of the area of the largest ungrounded supply conductor or the
equivalent area for parallel supply conductors.
Table Tips
1.Make sure that you are using the proper
column(s) based on the wire type that you are installing—
copper, aluminum, or copper-clad aluminum.
2.If your ungrounded conductor or equivalent parallel
conductors’ area is larger than 1100 kcmil copper or 1750
kcmil aluminum, follow Table Note 1.
3.See the Sizing Supply-Side Bonding Jumpers section and
the application example that follows on the next page.
4.See also the Sizing Main and System Bonding Jumpers
section on the next page.
4
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued
Sizing Supply-Side Bonding Jumpers
(via connection to a grounding electrode), the main and system
bonding jumpers will be placed directly in the supply-side
ground-fault current return path.
Similar to how you size the main bonding jumper per
250.28(D), supply-side bonding jumpers must be sized based
on the size of the ungrounded conductors with which they
are associated. If the ungrounded conductors are 1100 kcmil
copper or 1750 kcmil aluminum or smaller, the supply-side
bonding jumper must be selected from Table 250.102(C)(1)
based on the size of the largest ungrounded supply conductor.
If the ungrounded conductors are larger than 1100 kcmil
copper or 1750 kcmil aluminum, the size of the supply-side
bonding jumper(s) must be calculated based on 12½ percent
of the area of the largest ungrounded supply conductor or
the equivalent area of the parallel supply conductors. Where
an installation consists of multiple raceways for parallel
conductors, an individual supply-side bonding jumper can be
installed for each raceway; the jumper must be sized based on
the size of the ungrounded conductors in that raceway.
Where the largest ungrounded supply conductor exceeds
the parameters of Table 250.102(C)(1), Note 1 in the table
requires you to establish a proportional relationship between
the ungrounded conductor and the main or system bonding
jumper. Where the service-entrance conductors are larger
than 1100 kcmil copper or 1750 kcmil aluminum, the
bonding jumper must have a cross-sectional area of not less
than 12½ percent of the cross-sectional area of the largest
phase conductor or phase conductor set. In equipment such
as panelboards or switchboards that are listed for use as
service equipment, the manufacturer provides a bonding
jumper that can be installed as the main or system bonding
jumper. It is not necessary to provide an additional bonding
jumper.
Main Bonding Jumper for Service with
More Than One Enclosure
Sizing Main and System Bonding Jumpers
In a grounded system, the primary function of the main
bonding jumper and the system bonding jumper is to create
the ground-fault current link between the EGCs and the
grounded conductor. Table 250.102(C)(1) can be used to
determine the minimum size of the main and system bonding
jumpers. Unlike the GEC, which carries current to the ground
Where a service consists of more than one disconnecting
means in separate enclosures, each enclosure must
be treated separately, as depicted in the following exhibit.
Based on the 3/0 AWG ungrounded service conductors and
Table 250.102(C)(1), the minimum size of the main bonding
Application Example
A 3-phase, 1600-A service is supplied using five 400 kcmil THWN conductors per phase. The parallel conductors are
installed in five separate runs of rigid metal conduit. In accordance with 300.12, Exception No. 2, a supply-side bonding
jumper is needed for each raceway at the point at which it enters the open-bottom switchboard. Using 250.102(C)(2),
determine the necessary size of the supply-side bonding jumper.
Multiple Supply-Side Bonding Jumpers
Single Supply-Side Bonding Jumper
STEP 1. Determine the size of the largest ungrounded
conductor in each raceway.
STEP 1. Determine the equivalent area of parallel supply
conductors.
STEP 2. Determine the size of the supply-side bonding
jumper for each raceway using Table 250.102(C)(1).
STEP 2. Determine the size of the supply-side bonding
jumper using Table 250.102 (C)(1), Note 1.
SOLUTION. For 400 kcmil supply conductors, use the
“Over 350 through 600” row of Table 250.102(C)(1). This
leads you to a 1/0 AWG copper or 3/0 AWG aluminum
supply-side bonding jumper.
SOLUTION. Five parallel 400 kcmil conductors:
Total equivalent area = 5 × 400 = 2000 kcmil
This total exceeds 1100 kcmil; therefore, the total must be
multiplied by 0.125 (12.5 percent).
2000 kcmil × 0.125 = 250 kcmil copper
5
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued
jumper for the enclosure on the left is 4 AWG copper. The 1/0
AWG main bonding jumper for the enclosure on the right must
be derived from Table 250.102(C)(1) based on the 500 kcmil
ungrounded service conductors. The bonding jumper provided
by the manufacturer for listed service equipment provides the
equivalent current capacity to that of a field-fabricated bonding
jumper sized per Table 250.102(C)(1).
Sizing Equipment Grounding Conductors
Using Table 250.122
Table 250.122 is used to size the equipment grounding
conductor (EGC) for grounding raceways and equipment.
Unlike Table 250.66 and Table 250.102(C)(1), which both utilize
the size of the ungrounded conductor as the determining
factor for sizing, Table 250.122 uses the rating of the
overcurrent protective device (OCPD) ahead of the equipment
or load that is being supplied to properly size the EGC.
Separately Derived System with
More Than One Enclosure
To prevent parallel neutral current paths in raceways and
enclosures, the system bonding jumper can be either be
internal to the panelboards or installed at the separately
derived system enclosure so that it connects any supply-side
bonding jumpers to the system grounded conductor terminal.
The system bonding jumper cannot be installed at both
locations.
Table Tips
1.
In the first column, select the rating that matches the
OCPD protecting the circuit. If the rating of the OCPD that
is protecting the circuit is not shown, the next higher rating
should be chosen. For example, if the OCPD protecting the
circuit is rated at 30 A, which is not included in the table, the
Table 250.122 Minimum Size Equipment Grounding
Conductors for Grounding Raceway and Equipment
750 kcmil ungrounded conductor
Supply conductors (only one phase shown)
Minimum 2/0 AWG grounded conductor
2/0 AWG supply-side bonding jumper
Neutral terminal bus
4 AWG
grounded
conductor
3/0 AWG
ungrounded
conductor
500 kcmil
ungrounded
conductor
1/0 AWG
grounded
conductor
200-A
circuit
breaker
GarmaJon 101509
L2 Series
Manufactured LR
A
2/0 AWG
grounding
electrode
conductor
4 AWG
main
bonding
jumper
4 AWG
supply-side
bonding
jumper
400-A
circuit
breaker
GarmaJon 101509
L2 Series
Manufactured LR
A
1/0 AWG
main
bonding
jumper
1/0 AWG
supply-side
bonding
jumper
An example of the bonding requirements for service equipment.
Rating or Setting of
Automatic Overcurrent
Device in Circuit Ahead
of Equipment, Conduit,
etc., Not Exceeding
(Amperes)
Size (AWG or kcmil)
Copper
Aluminum or
Copper-Clad
Aluminum*
15
20
60
100
14
12
10
8
12
10
8
6
200
300
400
6
4
3
4
2
1
500
600
800
2
1
1/0
1/0
2/0
3/0
1000
1200
1600
2/0
3/0
4/0
4/0
250
350
2000
2500
3000
250
350
400
400
600
600
4000
5000
6000
500
700
800
750
1250
1250
Note: Where necessary to comply with 250.4(A)(5) or (B)(4), the
equipment grounding conductor shall be sized larger than given in this
table.
*See installation restrictions in 250.120.
6
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued
next higher size, which is 60 A, should be selected, resulting
in a 10 AWG copper EGC for this circuit.
Application Example
2.If the ungrounded circuit conductors are increased in size
for any reason other than temperature correction or due to
the number of current-carrying conductors in a raceway,
the EGC must be increased proportionally. For more details,
see the following section and its associated Application
Example.
A 240-V, single-phase, 250-A load is supplied by a
300-A breaker located in a panelboard 500 ft away.
The conductors are 250 kcmil copper installed in
rigid nonmetallic conduit with a 4 AWG copper EGC.
If the conductors are increased to 350 kcmil, what is
the minimum required size of the EGC based on the
proportional increase requirement?
Generally, the minimum-sized EGC is selected from Table
250.122 based on the rating or setting of the feeder or branchcircuit OCPD(s). Where the ungrounded circuit conductors
are increased in size to compensate for voltage drop, the EGCs
must be increased proportionately. This will lower the overall
impedance of the ground-fault current return path, which will
facilitate the operation of the OCPD in the event of a line-toground fault.
STEP 1. Calculate the size ratio of the new conductors to
the existing conductors:
Size ratio =
250,000 circular mils
= 1.4
STEP 2. Calculate the cross-sectional area of the new
EGC:
41,740 circular mils × 1.4 = 58,436 circular mils
According to Table 8 of Chapter 9, the size of the existing
grounding conductor, 4 AWG, has a cross-sectional area of
41,740 circular mils.
Grounded
service
conductor
Service
equipment
Grounding
electrode
conductor
350,000 circular mils
STEP 3. Determine the size of the new EGC. Again,
referring to Chapter 9, Table 8, we find that 58,436 circular
mils is too large for a 3 AWG EGC. The next larger size is
66,360 circular mils, which converts to a 2 AWG copper
EGC.
N
Main bonding
jumper
Equipment
grounding
terminal bar
bonded to
enclosure
Load
Equipment
grounding
conductor
Learn More
Grounding and bonding arrangement for grounded systems, per
250.130(A), illustrating connection of the EGC (bus) to the enclosures
and to the grounded service conductor
�Visit nfpa.org/ElectricalSolutions for more of the
latest electrical resources from NFPA, including
research, featured products, training options, and
certification opportunities.
This material contains some basic information about NFPA 70®, National Electrical Code® (NEC®). It identifies some of the
requirements in NFPA 70 as of the date of publication. This material is not the official position of any NFPA Technical Committee
on any referenced topic which is represented solely by the NFPA documents on such topic in their entirety. For free access to
the complete and most current version of all NFPA documents, please go to nfpa.org/docinfo. The NFPA makes no warranty or
guaranty of the completeness of the information in this material and disclaims liability for personal injury, property, and other
damages of any nature whatsoever, from the use of or reliance on this information. In using this information, you should rely on
your independent judgment and, when appropriate, consult a competent professional.
© 2020 National Fire Protection Association / June 2020
7
Download