KEY PLAN N N NOTES 1. ALL DIMENSIONS ARE IN MILLIMETRES AND ALL LEVELS ARE IN METERS UNLESS OTHERWISE SPECIFIED. 2. READ THIS DRAWING IN CONJUNCTION WITH RELATED MECH. AND ARCH. DRAWINGS. 3. MINIMUM CHARACTERISTIC COMPRESSIVE STRENGTH AT 28 DAYS (Fc’) AS FOLLOWS: • RC: C35 (COMPRESSIVE CYLINDER STRENGTH) • PC: C11 (COMPRESSIVE CYLINDER STRENGTH) WITH NORMAL PORTLAND CEMENT CONFORMING TO ASTM C150, UNLESS OTHERWISE SPECIFIED ON THE DRAWINGS OR SPECIFICATIONS. 4. CONCRETE COVER FOR REINFORCEMENT SHALL BE: • ISOLATED FOOTINGS = 75mm • RAFT & SLABS IN CONTACT WITH SOIL = 50mm • BEAMS = 50mm • COLUMNS = 50mm • SLABS = 25mm • WALLS = 50mm 5. MINIMUM REINFORCEMENT YIELD STRENGTH 420 MPa. 6. STEEL MATERIALS SHALL BE AS FOLLOWS: • STRUCTURAL STEEL PLATES AND ANGLES ARE CONFORMING TO ASTM A 36/A 36M HAVING A MINIMUM YIELD STRESS OF 245 N/mm2. • HOT ROLLED IPE AND H SECTIONS ARE CONFORMING TO ASTM A 572 GRADE 50 HAVING A MINIMUM YIELD STRESS OF 345 N/mm2. • CONNECTION BOLTS, NUTS, AND WASHERS: BOLTS SHALL CONFORM TO ASTM A 490M, TYPE 1 OF GRADE 10.9. • ANCHOR BOLTS SHALL BE HOT DIP GALVANIZED OF GRADE 55 CONFORMING TO ASTM F 1554, OF 380 MPA MINIMUM YIELD STRENGTH. COATING SHALL BE HOT DIP ZINC COATING CONFORMING TO ASTM A153 CLASS C. • STEEL STRUCTURES,GRATING ,CHECKERED PLATES,ETC .SHALL BE HOT DIP GALVANIZED. 7. ISOLATED FOOTINGS WERE DESIGNED BASED ON AN ALLOWABLE BEARING CAPACITY OF 300 kPa AND RAFT FOUNDATION WAS DESIGNED ON AN ALLOWABLE BEARING CAPACITY OF 225 kPa. 2 00013 1 2 3 4 5 6 7 RAMP ON GRADE 9 10 11 12 51210 UP 4115 4010 3780 220 6100 6000 6000 6000 6000 5085 3900 EL +0.50 TOC 18 UP GB2 (250 x 600) E 8 550 RAMP ON GRADE GB4 (250x600/1300) RAMP ON GRADE UP 00017 E 2016 GB20 (300 x 500) 900 STEEL STAIR IPE360 IPE360 50mm GALVANIZED STEEL GRATING 900 900 STEEL STAIR IPE360 32 50mm GALVANIZED STEEL GRATING 900 00018 50mm GALVANIZED STEEL GRATING 30 IPE360 GB16 (250 x 1300) 150 SOG 150 SOG EL -0.75 TOC 10 00016 EL +0.40 TOC EL -0.75 TOC 150 SOG 150 SOG EL +0.40 TOC EL +0.40 TOC 200 EL +0.40 TOC GB4 (250 x 1300) TOC +0.40 GB2 (250 x 1300) TOC +0.40 EL +0.40 TOC GB4 (250 x 600) GB4 (250 x 600) GB4 (250 x 600) GB4 (250 x 600) 3780 220 ROOF FLOOR PLAN 2200016406-D3-AYC-011PUB-ARCDR-00003 GROUND FLOOR PLAN 2200016406-D3-AYC-011PUB-ARCDR-00002 LOWER GROUND FLOOR PLAN 2200016406-D3-AYC-011PUB-ARCDR-00001 PUMP STATION GENERAL ARRANGEMENT SECTION DETAILS 2200016406-D3-AYC-011PUB-MECGAD-00102 PUMP STATION GENERAL ARRANGEMENT PLAN LAYOUT 2200016406-D3-AYC-011PUB-MECGAD-00101 20905 DRAWING NUMBER 1 6100 RAMP ON GRADE UP 6000 6000 6000 5085 3 4 5m SCALE 1:100 D ISSUED FOR APPROVAL 17.01.2024 MAH MES MSN C ISSUED FOR APPROVAL 19.12.2023 MAH MES MSN B ISSUED FOR APPROVAL 20.11.2023 MAH MES MSN A ISSUED FOR APPROVAL 12.04.2023 MAH MES MSN DATE DRAWN REV. DESCRIPTION CHECKED APPROVED OWNER: NATIONAL WATER COMPANY EASTERN REGION FOR PENETRATION SLEEVES REFER TO ELECTRICAL DRAWINGS 6000 2 A GB11 (250 x 600) FOR PENETRATION SLEEVES REFER TO ELECTRICAL DRAWINGS 4010 DRAWING TITLE 0 B UP 4115 3255 C 00018 00017 RAMP ON GRADE STEEL STAIR IPE360 REFERENCE DRAWINGS RAMP ON GRADE IPE360 19 900 GCB1 (250 x 1300) 5200 EL +0.40 TOC GB16 (250 x 1300) 00018 A 1630 1000 IPE360 33 GB1 (250 x 600) GB21 (300 x 500) GB12 (250 x 1300) 12 00016 900 STEEL STAIR IPE360 GB3 (250 x 1300) B 900 IPE360 EL -0.75 TOC FOR PENETRATION SLEEVES REFER TO ELECTRICAL DRAWINGS IPE360 EL +0.40 TOC 150 SOG 250 GB17 (300 x 500) IPE360 150 SOG GB6 (250 x 1300) EL +0.40 TOC GB15 (250 x 600) GB14 (250 x 600) 150 SOG 00018 GB14 (250 x 600) GB5 (250 x 600) 7055 00013 GB13 (250 x 600) 2270 D FOR PENETRATION SLEEVES REFER TO ELECTRICAL DRAWINGS IPE360 20905 1 1110 00017 IPE360 31 EL +0.40 TOC EL +0.15 TOC GB17 (300 x 500) 20 GB3 (250x1300/750)GCB1 (250 x 1300) 150 SOG 350 GB19 (300 x 500) GB1 (250 x 600) GB18 (250 x 1300) TOC +0.40 C IPE360 00016 EL +0.40 TOC 150 SOG IPE360 GCB1 (250 x 1300) IPE360 11 150 SOG 50mm GALVANIZED STEEL GRATING GB7 (250 x 1300) GB8 (250 x 600) 2200 D GB4 (250x600/1300/750) 900 IPE360 GB2 (250 x 600) EL -0.75 TOC STEEL STAIR GB10 (250 x 600) EL +0.40 TOC 150 SOG GB9 (250 x 1300) 150 SOG GB9 (250 x 1300) EL +0.40 TOC GB6 (250 x 1300) 150 SOG GB6 (250 x 600) 6450 GB11 (250 x 600) GCB1 (250 x 1300) MAIN CONSULTANT: ILF CONSULTING ENGINEERS SAUDI ARABIA Prince Sultan Bin Abdulaziz Road | Delmon Building, No. 4380 34235 Al Khobar, P.O. Box 77072 | Kingdom of Saudi Arabia 3900 51210 MAIN CONTRACTOR: 1 2 3 4 5 6 7 8 9 10 11 12 AL-YAMAMA Tel No : +966 13 82 66 444 Fax No : +966 13 82 70 089 P.O. Box No: 2210 Dammam 31451 Saudi Arabia CONTRACTOR CONSULTANT: ARTELIA Tel. No: +971 04 886 5690 Fax No: +971 04 886 5691 P.O. Box No: 18271 Dubai, U.A.E. PROJECT NAME : Water Quality Improvement Project - South Strategic Network and Reservoirs Dammam Project 3 DRAWING TITLE: DAMMAM 3 ALSHUALA PUMP STATION GROUND FLOOR FRAMING PLAN DRAWN BY: 1 PUB-00004 GROUND FLOOR FRAMING PLAN DESIGNED BY: CHECKED BY: MAH MES MAH APPROVED BY: MSN DWG NO. 2200016406-D3-AYC-011PUB-STR-DR-00004 1 : 100 SHEET NO.: SHEET 4 OF 19 SCALE: 1 : 100 DATE: 17.01.2024 REVISION SIZE D A1