Power 6302
One-bolt installation
Power 6302 offers the possibility to build a complete
site on a single rail and still maintain the same
control and visibility as in a cabinet mounted system.
The system can provide power to a complete singleband three-sector site, or to a one-sector triple-band
installation.
This power system is designed to provide AC to DC
conversion with capability of 2300 W, -48 VDC
feeding to radios in the Ericsson Radio System. This
power system is suited for non-backup installation
and/or where the distance to the power source is
long. By using our unique rail with one-bolt
installation, it can be done quickly with a reduced
number of products and that requires less space.
Convection cooled
This power system has a high efficiency rectifier, is
convection cooled and equipped with three separate
DC-ports, three separate communication ports that
interlink with the radio modules and provides
complete visibility and control of the CPRI interfaces.
Power 6302 may also be used to great advantage in
combination with an inverted solution mounted in a
nearby service cabinet. This allows for up to 300
meters of power feeding, which results in lower costs
of cables without sacrificing backup capacity and
with reduced weight on the tower.
Picture: Power 6302 installed on the right side of
three radio units in a sector configuration.
Technical Specification Power 6302
MECHANICAL SPECIFICATION
Weight:
Max 9 kg
Dimension (H x W x D):
310 x 90 x 290 mm
Mounting:
Ericsson rail mounting
ELECTRICAL SPECIFICATION
AC input:
172-275 VAC, 50-60 Hz
Single phase (L,N, PE) or Two-phase (L, L, PE)
Lightning protection 4 kA 10/350 µs
DC output:
2.3 kW -48 VDC output power
3 -48 VDC feeds for rail radios
High efficiency rectifier: >95%
3 Support Unit communication interfaces for rail radios, max 815
W per port, with max total load 2300 W
CLIMATE SYSTEM
Cooling:
Convection cooled
ENVIRONMENTAL SPECIFICATION
Temperature range:
-40° C to +60° C
Cabinet:
Outdoor class IEC/EN 60 529 IP 65 and UL 50E type 3
Safety approvals:
IEC/EN 609 50-1, IEC/EN 60 950-22
UL 60950-1 and CAN/CSA-C 22.2
EMC approvals:
EMC Directive 2014/30/EU
FCC CFR 47 Part 15 and ICES-003 Class B
Telefonaktiebolaget LM Ericsson
SE-164 80 Stockholm, Sweden