See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/304570728 Fouling of an air-cooled heat exchanger, and alternative design approach. Conference Paper · December 2009 CITATIONS READS 2 3,720 4 authors, including: Leon Liebenberg Josua P Meyer North-West University University of Pretoria 98 PUBLICATIONS 1,681 CITATIONS 908 PUBLICATIONS 15,080 CITATIONS SEE PROFILE All content following this page was uploaded by Josua P Meyer on 29 June 2016. The user has requested enhancement of the downloaded file. SEE PROFILE Fouling of an air cooled heat exchanger; an alternative design approach HJ Nel a, IF Lombaard b, L Liebenberg a, JP Meyer a* a Department of Mechanical and Aeronautical Engineering, University of Pretoria, b Sasol Technology, South Africa * Author for correspondence (jmeyer@up.ac.za) Keywords: Air cooled heat exchangers, fouling, design procedures, modelling ABSTRACT: Air cooled heat exchangers (ACHEs) are an important part of industrial heat transfer systems, especially where clean cooling water is scarce. Unfortunately, fouling of ACHEs is a serious problem since the quality of air cannot practically be controlled. To account for this at present it is standard practice to design an ACHE with fouling factors, which increase the required unit size. These fouling factors are essentially additional conductive resistances meant to model the insulating effects that the fouling layer introduces. ACHEs designed in this manner will initially over perform, but the performance will decrease over time often to levels far below design conditions. The aim of this paper, however, is to demonstrate that air-side fouling will affect performance primarily by decreasing the air-side mass flow rate due to an increased air-side pressure drop, and not principally by increasing the conductive resistances as implied by the constant fouling factor method. This will be shown by assuming a uniform fouling layer throughout an ACHE which over time increases in thickness, and by using existing pressure drop and heat transfer coefficient correlations as well as a fan curve to simulate the change in the unit’s performance. It will then be shown that performance is affected most significantly by the increase in air-side pressure drop and related decreased air-side mass flow rate. Finally, a new design procedure will be outlined that should help ACHEs to perform more consistently throughout their lifetime. 1 INTRODUCTION In the current climate of resource management and energy efficiency it is becoming increasingly important to manage available resources, especially when these resources are in short supply, such as the supply of clean water in South Africa. This makes dry cooling air-cooled heat exchangers (ACHE’s) a very attractive option since they use freely available atmospheric air as the cooling medium. Using atmospheric air has its price, however, namely that the quality and cleanliness of the air cannot easily be guaranteed. This causes the ACHE’s to foul over time and to lose performance. Unfortunately, the performance levels often drop below the fouled design conditions despite being designed according to widely acceptable industry standards (e.g. TEMA). At present the standard practice for fouled heat exchanger design is to add two additional and constant fouling factors which are based on the process fluids used. This technique is over 50 years old and is described in any classic heat transfer text, such as Çengel (2006). The main source of values for the fouling factors is the Standards of the Tubular Ex- changer Manufacturers Association (TEMA), (2007). This method effectively increases the required size of the unit in order to transfer the design thermal load under fouled conditions. Unfortunately fouling is not present at the beginning of the unit’s lifetime and consequently the unit will overperform. The unit’s performance will then also decrease over time, and, if left uncleaned, will eventually perform substantially below design conditions. One of the main assumptions of the constant fouling factor method is that it assumes conductive resistances are the only change to the unit, and that no changes in flow rates or heat transfer coefficients are expected. This is contrary to experimental measurements. Shah (2005) reports experimental measurements by Bemrose and Bott on fouling of ACHE’s using calcium carbonate particles. The Colburn-j factor for these tests decreased slightly, while the friction factor increased by 40-150%. Shah (2005) also gives Marner’s results of the fouling of a plate fin ACHE using the exhaust gasses from a turbine combusting No. 2 diesel fuel. The tests were run for eight hours and showed fouling layer thicknesses between 50 and 200 micrometers. The heat exchanger effectiveness decreased only 3% while mass flow reductions between 6-11% were measured as a result of the increased air-side pressure drop caused by the fouling layer. This clearly shows that the assumption of constant flow rates is flawed. Probably the main reason that the constant fouling factor approach has remained so widely used, despite its flaws, is that the actual process of fouling is exceedingly difficult to model accurately. Bott (1995) and Müller-Steinhagen (2000) list some of the models for the various fouling mechanisms, such as crystallisation, deposition, etc. Unfortunately, these models cannot account for the interactions between the various fouling mechanisms and they require a great deal of empirical constants and contaminant concentration information that are not available a priori to the designer. This then also means that accurate modelling of the fouling process in the design phase is not practical, and has led to the relatively simple constant fouling factor approach remaining the preferred method. Nevertheless, even though detailed modelling of the fouling process is not feasible, it is proposed here that the constant fouling factor assumption (particularly with respect to regarding no change in the flow rate), is fundamentally flawed. Below it will also be shown graphically to what degree the decrease in air-side flow rate will eventually cause performance losses greater than would be expected from the use of the TEMA (2007) fouling factors. Therefore, the aim of this paper is to present an improved design approach that can account for ACHE air side fouling. This method will then more accurately model the primary causes of reduced performance than the constant fouling factor method, and result in more consistent heat exchanger performance over any given period. 2 THEORETICAL ANALYSIS The first step used here in analysing the performance of a fouled ACHE is the identification of an appropriate fouling model. Modelling the depositional process itself is an incredibly complex task and relies on so many parameters that it cannot be readily performed. A simpler and more usable scheme will be to assume that the fouling layer thickens uniformly throughout the bundle. This is modelled by uniformly increasing the outer diameter of the tubes and the thickness of the fins with a layer of fouling. This scheme is simple and crude but has the advantage that, for thin layer thicknesses, the pressure drop and heat transfer coefficient correlations that were originally used to design the bundle can still be used to infer what operational changes the fouling layer will bring about. Thus, this scheme was implemented by first taking the design parameters of an ACHE test section (c.f. Table 1) and feeding those parameters into the Briggs and Robertson (1966) pressure drop correlation, as well as the Briggs and Young (1963) and Ganguli (1998) heat transfer coefficient correlations. The next step was to model the fouling layer by incrementally increasing the outer tube diameter and fin thickness. The new parameters were passed to the correlations to determine what performance trends could be expected. The first, and most important trend, was that the air-side pressure drop increased much faster than was initially anticipated. Figure 1 shows pressure drop curves for the unit with several different fouling layer thicknesses as well as the fan curve of a typical axial fan that would be used with this unit. It is apparent that the fouling layer has a negative effect on the pressure drop characteristics of the unit, which is in line with other measurements reported by Bott (1995). However, the most important effect is only seen once the fan curve is superimposed onto the pressure drop curves (the intersection of a pressure drop curve and the fan curve denotes the operating point of the unit). The effect of the fouling layer is to move the operating point of the unit to lower face velocities, and consequently lower mass flow rates and higher pressure drops. Table 1. Geometrical and Thermal factors for test section Factor Value Fin Material Aluminium, k = 204 W/m K Outer Fin Diameter 58 mm Fin Root Diameter 25.4 mm Fin Shape G-Fin, Mean Fin Thickness 0.46 mm Fin Pitch 2.54 mm Tube Material Steel, k = 50 W/m K Tube Outer Diameter 25.4 mm Tube Inner Diameter 19.86 mm Tube Arrangement Staggered Number of Tube Rows 6 Number of Tubes per row Actual 13 Effective 12.5 Transverse Tube Pitch 60 mm Longitudinal Tube Pitch 52 mm Length of Finned Tube 0.75 m Air Inlet Temperature 18°C Air Inlet Pressure 101 kPa Water Inlet Temperature 60°C Water Flow Rate 3.9 kg/s Next, once the various operating points were identified the performance of the unit at each point was modelled by using the Briggs and Young and Ganguli correlations to estimate the heat transfer coefficients for the modified geometry at the appropriate flow rate. The thermal insulating effect of the fouling was taken into account by adding a cylindrical thermal resistance to the bare tube surfaces. A thermal conductivity of the fouling layer was as- sumed at 1 W/m K, which is an acceptable average value, based upon data presented by MüllerSteinhagen (2000). The fin efficiency was also modified appropriately based upon work presented by Kröger (1998). The in-tube conditions were held constant for all operating conditions. All this information was used to simulate the unit’s performance using a simple effectiveness–Number of Transfer Units model, Çengel (2006), and this was compared to the decrease in performance predicted by a TEMA (2007) type air-side fouling resistance of 0.00018 m2K/W. The results in Figure 2 then illustrate the problem with simply using a constant fouling factor. The constant fouling factor method predicts a performance loss of less than 5%, while the uniform fouling thickness approach shows that a layer of only 50 micrometers would have the same effect, and that any further increase would cause significant additional performance losses. This again demonstrates the problem of using a constant thermal resistance to account for fouling. Initially the unit will overperform, but this performance will decrease with time continually to values far below design conditions. Furthermore, since most industrial processes require stable performance, both over- and underperformance are undesirable. The only way to overcome this while using the constant fouling factor approach is to adjust the fanmotor system to give the appropriate flow rate. The constant fouling factor approach will oversize the unit initially, but this does nothing to counteract the actual fouling mechanism over time. Figure 3. Decrease in maximum heat transfer There is one more parameter that needs to be investigated if a more complete understanding of the implications of air side fouling is required. This parameter is the maximum heat transfer of a unit. The maximum heat transfer of a unit is the amount of heat an infinitely large unit can transfer, subject to the fluids flow rates, specific heats and inlet temperatures. It is defined by Çengel (2006) as: (1) In the case of ACHE’s the air side should almost always have the lowest product of mass flow rate and specific heat due to air’s low density and specific heat. It has already been shown that the air side fouling will decrease the air side mass flow rate and the effect of this on the unit’s maximum heat transfer is shown in Figure 3. This shows that the effect of fouling is to reduce the maximum heat transfer the unit is capable of. The fouling factor approach, or any other approach that modifies the unit’s area, such as the cleanliness factor approach, attempts to add area to combat the loss in performance but Figure 3 shows that fouling decreases a parameter that is independent of area. While the addition of area can increase the heat transfer, it does nothing to address the underlying problem. 3 EXPERIMENTAL RESULTS Figure 1. Fouling-affected operating points Figure 2. Fouling-affected heat transfer With regards to suggested methodology the biggest problem is that it is well known that ACHE’s do not foul uniformly. The unit usually experiences heavy fouling on the first row and less fouling downstream through the bundle, although in some cases the amount of fouling does start to increase as the exit side of the bundle is reached. This means that the uniform fouling model cannot be used to give accurate performance predictions. In an attempt to test the validity of the trends predicted by the uniform fouling theory several test sections of 0.75 m by 0.75 m were prepared from severely fouled units. Unfortunately these test sec- tions lost virtually all of the fouling due to sensitivity during handling and transport. This made a controlled laboratory investigation impossible. The alternative was to performance test a fouled unit in the field, which was done on a Sasol ACHE in December 2008. The unit was heavily fouled with several areas on the front face being completely blocked. The approach taken was that since the increase in pressure drop could not accurately be measured, the face velocity at the exit would be measured at 140 points using a calibrated anemometer. The unit was then professionally cleaned by GEA Nilenca, a heat exchanger servicing company, and the measurements were taken again at the same points. The unit has a design face velocity of 3.42 m/s; prior to cleaning the unit the average face velocity was 1.66 m/s, 49% of the rated value. Furthermore the unit removed 13.5 MW of heat (with six of the 20 fans inoperative for servicing) before cleaning. After cleaning seven fans were inoperative, but the face velocity had increased to 4.2 m/s, 122% of the rated value, and the heat removal had increased to 22.4 MW, an increase of 66%. The reason the face velocity was higher than rated is due to the fact that the plant engineers had increased the fan’s blade angles over time to counteract the declining performance of the unit. This shows that the fouling had caused a significant increase in the air-side pressure drop which led to the significant decrease in air-side face velocities, as predicted by the uniform fouling approach. 4 ALTERNATIVE DESIGN PROCEDURE It is proposed that the constant fouling factor approach is fundamentally flawed, regardless of the fact that designers do not currently have access to acceptable alternative methods. The authors would like to propose a new design procedure as well as several suggestions regarding the design of ACHE’s. The first step toward designing a fouling resistant ACHE is to consider the environment in which the unit will operate and trying to eliminate or manage the fouling. Kröger (1998) gives some examples of typical fouling sources and some methods to control this. This approach can be extremely effective if a particular source is responsible for the majority of the fouling. However, it is not possible to foresee all possible fouling sources, and if the sources are identified it is not always possible to eliminate them. As a general rule the authors would advise designers to avoid very fine tube and fin pitches as these would cause higher baseline pressure drops that would make it easier for the unit to collect fouling. Bott (1995) and Müller-Steinhagen (2000) suggest that, for heat exchangers in general, fluid velocities be kept as high as possible as this will decrease the amount of deposition that occurs. Next an alternative design approach to the constant fouling factor method can be implemented as described here. The fouling factor method leads to the oversizing and the subsequent initial overperformance of the unit. One way to deal with this situation is to adjust the fan-motor system so that the flow rate is correctly modified. Once the unit’s performance has decreased below the design conditions, the operators will slowly increase the blade angle over time to combat the pressure drop increase. This procedure works until the operators have used the entire pressure margin available, after which the fan will stall and the unit would not function effectively. The authors would like to suggest that the air-side fouling factor be neglected entirely and that the fan be designed for an increased pressure drop, , which would be the baseline , plus an additional percentage pressure drop, of the baseline pressure drop, (Equation 2). This would lead to the scenario where at clean conditions the fan would supply more flow than required. This would require that, as with the fouling factor method, the blade angles be turned down during clean service and slowly increased as the unit fouls. An alternative to constantly adjusting the blade angles is to use a variable speed drive to adjust the fan speed to ensure the correct flow rate. Either of these two methods allows the operators to adjust the flow and it is up to the designer to decide which method is more appropriate for each situation. (2) The advantage of this method is that the fan would have a larger available pressure margin to deal with the fouling-induced pressure drop increase, and that the unit will be able to operate at design conditions for longer than a unit designed using the constant fouling factor approach. Hence, this results in a more efficient design. This method does require a larger fan and motor system but does not oversize the physical heat exchanger unit. The designer therefore needs to perform a full economic investigation which evaluates the cost implications of both approaches, the production losses that would result if the unit underperforms (primarily in the fouling factor method), required cleaning intervals and cost as well all other cost implications for the plant and unit design before a decision is made on which method to use. At this stage the authors can make no concrete recommendations regarding values of , however, a tentative suggestion is that values between 0.1 and 0.2 should be used depending on the level of fouling expected and the time between cleaning. Many more measurements are required to make this method accurate and efficient. The most important aspect that designers need to be made aware of is that no matter what method is used to account for fouling, the unit will still foul. This means that eventually the unit’s performance will decrease past acceptable limits. This further implies that regular cleaning of the unit will be required no matter what fouling approach is used and that cleaning of the unit should be built into the lifecycle costing of the unit. The authors therefore recommend that the designers evaluate the importance of the unit, the environment in which the unit will operate, and the service intervals for the unit. Based upon that information the appropriate design procedure should be used that will allow the unit to perform at the correct levels in the service interval. Prior to servicing the unit should be inspected to determine the level of cleaning required and the cleaning can then be performed during the service interval to minimise its effect on the process. Designers should also be aware that even though cleaning can be expensive, regular preventative cleaning will ensure minimal production losses and increase the lifetime of the unit, which should outweigh the cleaning costs. 5 CONCLUSION This paper presents an alternative to the current practice of adding a TEMA type fouling factor to the design of an ACHE. It has been shown through the uniform fouling assumption that air-side fouling will cause a dramatic reduction in the air-side mass flow rate due to the increased air-side pressure drop. This is in contrast with the fouling factor method which assumes that the flow rate remains constant. Proof of the reduction in flow rate was presented in the form of pre- and post cleaning air-side face velocity measurements. Finally, a new design procedure has been outlined that should help ACHE’s to perform more consistently throughout their lifetime, as long as they are subjected to regular cleaning. ACKNOWLEDGEMENTS This project was a final year capstone project at the University of Pretoria in the Department of Mechanical and Aeronautical Engineering and was executed by the first author. This project was made possible through the assistance of several individuals and companies: View publication stats Prof. D.G. Kröger of the University of Stellenbosch for his invaluable assistance and experience with ACHE’s and their design Mr Danie Nell of GEA Nilenca for the access to the cleaning process and measurements and as well as all the other invaluable support which made this research possible Mr Cobus Zietsman and the rest of the laboratory staff at the University of Stellenbosch Mr Warwick Hayes of Sasol for initiating the cleaning project and assisting with the measurements REFERENCES Çengel Y, 2006, Heat and Mass Transfer, 3rd Edition, McGraw Hill. Tubular Exchanger Manufacturers Association, 2007, Standards of the Tubular Exchanger Manufacturers Association, 9th Edition, Section 10. Shah R.K. and Sekulic D.P, 2003, Fundamentals of Heat Exchanger Design, John Wiley & Sons. Bott T.R, 1995, Fouling of Heat Exchangers, Elsevier. Müller-Steinhagen H, 2000, Heat Exchanger Fouling: Mitigation and Cleaning Technologies, IChemE. Briggs D.E and Robinson K.K, 1966, Pressure Drop of Air Flowing Across Triangular Pitch Banks of Finned Tubes, Chemical Engineering Progress Symposium Series, Volume 62, No. 64, pp. 177-184. Briggs D.E and Young E.H, 1963, Convection Heat Transfer and Pressure Drop of Air Flowing Across Triangular Pitch Banks of Finned Tubes, Chemical Engineering Progress Symposium Series, Volume 59, No. 41, pp. 1-10. Kröger D.G, 1998, Air-cooled Heat Exchangers and Cooling Towers, University of Stellenbosch.