C-FIX 1.121.0.0 Database version 2023.12.14.12.55 Date 20/03/2024 Grow Vertex Co., Ltd. 1 Empire Tower Fl. 47th Unit 4703 (River 38) South Sathorn Rd., Yannawa, Sathorn, Bangkok 10120 Phone: +66 2 6863461 Fax: +66 2 0266874 info@growvertex.co.th www.growvertex.co.th Design Specifications Anchor Anchor system Anchor Calculated anchorage depth Design Data fischer Bolt Anchor FAZ II Plus Bolt Anchor FAZ II Plus 16/100 R, stainless steel 125 mm Anchor design in Concrete according European Technical Assessment ETA-19/0520, Option 1, Issued 24/05/2023 Geometry / Loads / Scale units mm, kN, kNm Value of design actions (including partial safety factor for the load) Static Not drawn to scale The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the license agreement of the Software. Page 1 C-FIX 1.121.0.0 Database version 2023.12.14.12.55 Date 20/03/2024 Input data Design method Base material EN 1992-4:2018 mechanical fastener Customized, Test specimen: Cylinder 150 x 300 mm, Compressive strength = 32.0 N/mm² Cracked, dry hole No or standard reinforcement. No edge reinforcement. With reinforcement against splitting Hammer drilling Pre-positioned installation Annular gap not filled Permanent-Transient/Static Base plate with non bearing layer, e.g. grout pad., g = 15 mm calc. lever arm la = 34 mm Degree of restraint αM = 1.0 Mortar compression strength: 32.0 N/mm² 350 mm x 400 mm x 21 mm Customized profile Concrete condition Reinforcement Drilling method Installation type Annular gap Type of loading Base plate location Base plate geometry Profile type Design actions *⁾ # 1 NEd kN VEd,x kN VEd,y kN MEd,x kNm MEd,y kNm MT,Ed kNm Type of loading -12.40 6.90 0.80 1.20 20.50 0.52 Permanent-Transient/Static *⁾ The required partial safety factors for actions are included Resulting anchor forces Tensile action kN Shear Action kN Shear Action x kN Shear Action y kN 1 21.98 0.79 0.76 -0.22 2 0.00 0.90 0.76 0.49 3 21.53 1.17 1.15 -0.22 4 0.00 1.25 1.15 0.49 5 21.08 1.56 1.54 -0.22 6 0.00 1.62 1.54 0.49 Anchor no. max. concrete compressive strain : max. concrete compressive stress : Resulting tensile actions : Resulting compression actions : 0.19 6.5 64.60 77.00 ‰ N/mm² kN , X/Y position ( -135 / 2 ) kN , X/Y position ( 153 / -14 ) The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the license agreement of the Software. Page 2 C-FIX 1.121.0.0 Database version 2023.12.14.12.55 Date 20/03/2024 Resistance to tension loads Action kN Capacity kN Utilisation βN % Steel failure * 21.98 59.29 37.1 Pullout failure * 21.98 22.68 96.9 Concrete cone failure 64.60 72.24 89.4 Proof * Most unfavourable anchor Steel failure ( NRd,s ) NRk,s kN γMs NRd,s kN NEd kN βN,s % 83.00 1.40 59.29 21.98 37.1 Anchor no. βN,s % Group N° Decisive Beta 1 37.1 1 βN,s;1 2 0.0 2 βN,s;2 3 36.3 3 βN,s;3 4 0.0 4 βN,s;4 5 35.6 5 βN,s;5 6 0.0 6 βN,s;6 NRk,p kN Ψc γMp NRd,p kN NEd kN βN,p % 34.02 1.260 1.50 22.68 21.98 96.9 Pullout failure ( NRd,p ) The given Psi,c-factor may has been determined by interpolation. Anchor no. βN,p % Group N° Decisive Beta 1 96.9 1 βN,p;1 3 94.9 2 βN,p;2 5 93.0 3 βN,p;3 The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the license agreement of the Software. Page 3 C-FIX 1.121.0.0 Database version 2023.12.14.12.55 Date 20/03/2024 Concrete cone failure ( NRd,c ) Eq. (7.1) Eq. (7.2) Eq. (7.4) Eq. (7.5) Eq. (7.6) Eq. (7.7) NRk,c kN γMc NRd,c kN NEd kN βN,c % 108.36 1.50 72.24 64.60 89.4 Anchor no. βN,c % Group N° Decisive Beta 1, 3, 5 89.4 1 βN,c;1 Resistance to shear loads Proof Action kN Capacity kN Utilisation βV % Steel failure with lever arm * 1.56 3.94 39.5 Concrete pry-out failure 1.25 44.67 2.8 * Most unfavourable anchor Steel failure with lever arm ( VRd,s,M ) Eq. (7.37) The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the license agreement of the Software. Page 4 C-FIX 1.121.0.0 Database version 2023.12.14.12.55 Date 20/03/2024 Eq. (7.38) VRk,s,M kN γMs VRd,s,M kN VEd kN βVs % 4.92 1.25 3.94 1.56 39.5 Anchor no. βVs % Group N° Decisive Beta 1 20.5 1 βVs;1 2 14.7 2 βVs;2 3 30.1 3 βVs;3 4 20.4 4 βVs;4 5 39.5 5 βVs;5 6 26.4 6 βVs;6 Concrete pry-out failure ( VRd,cp ) Eq. (7.39a) Eq. (7.1) Eq. (7.2) Eq. (7.4) Eq. (7.5) Eq. (7.6) Eq. (7.7) VRk,cp kN γMc VRd,cp kN VEd kN βV,cp % 67.01 1.50 44.67 1.25 2.8 βV,cp % Group N° Decisive Beta 2.8 1 βV,cp;1 Anchor no. 4 The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the license agreement of the Software. Page 5 C-FIX 1.121.0.0 Database version 2023.12.14.12.55 Date 20/03/2024 Utilization of tension and shear loads Tension loads Utilisation βN % Shear Loads Utilisation βV % Steel failure * 37.1 Steel failure with lever arm * 39.5 Pullout failure * 96.9 Concrete pry-out failure 2.8 Concrete cone failure 89.4 * Most unfavourable anchor Resistance to combined tensile and shear loads Utilisation steel Eq. Utilisation concrete Proof successful Eq. (7.57) Base plate thickness Stress distribution pattern within the anchor plate Base plate details Anchor plate thickness Base plate material E-modulus Yield strength Safety factor Poisson's ratio Utilisation Profile type t = E Rp,0,2 γM ν η = = = = = 21 mm S 275 210,000 N/mm² 275 N/mm² 1.0 0.3 91 % Customized profile Technical remarks The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall be taken into account. As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate (if present) must be sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix. The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the license agreement of the Software. Page 6 C-FIX 1.121.0.0 Database version 2023.12.14.12.55 Date 20/03/2024 Installation data Anchor Anchor system Anchor fischer Bolt Anchor FAZ II Plus Bolt Anchor FAZ II Plus 16/100 R, stainless steel Art.-No. 564630 Accessories Blow-out pump ABG big SDS Plus-V II 16/160/210 Art.-No. 567792 Art.-No. 531827 Installation details Thread diameter Drill hole diameter Drill hole depth Calculated anchorage depth Installation depth Drilling method Borehole cleaning Installation type Annular gap Installation torque Socket size Base plate thickness Grout thickness Total fixing thickness Tfix,max M 16 d0 = 16 mm h1 = 148 mm hef = 125 mm hnom = 143 mm Hammer drilling Clear the borehole with a hand blower. Pre-positioned installation Annular gap not filled Tinst = 110.0 Nm 24 mm t = 21 mm g ≤ 15 mm tfix ≤ 36 mm tfix, max = 60 mm Base plate details Base plate material Base plate thickness Clearance hole in base plate S 275 t = 21 mm df=18 mm Attachment Profile type Customized profile Profile dimensions mm Width 175 Flange thickness 6 Anchor coordinates Anchor no. x mm y mm 1 -135 150 2 135 150 3 -135 0 4 135 0 5 -135 -150 6 135 -150 The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in the license agreement of the Software. Page 7