Question 12 (a) Three 6,6 kV, 12MVA, three phase alternators are connected to a common set of bus bars. The positive, Negative and zero sequence impedances of each alternator are 15%, 12% and 4.5% respectively. If an earth fault occurs on one busbar determine the fault current (i) If all the alternator neutrals are solidly grounded (ii) If only one of the alternator neutrals is solidly earthed (iii) If only one of the alternator neutrals is earthed through a reactance of 0.5 ohm and the others are isolated (a)The line currents in a three phase supply to an unbalanced load are Ia = 10 + j20, Ib = 12 – j10 and Ic = -3 –j5 amperes The phase sequence is abc. Determine the sequence components of the currents Question 10 If a fault occurs in a system, δ begins to increase under the influence of positive accelerating power, and the system will became unstable If δ becomes very large. There is a critical angle within which the fault must be cleared if the system is to remain stable and the equal-area criterion is to be satisfied. This angle is known as the critical clearing angle. Equal-area criterion for stability. This criterion says that stable performance requires that the accelerating area be equal to the decelerating area A1 = A2 Question 9 A delta connected resistive load is connected across an unbalanced three-phase supply shown in Fig. 5.1 Find (i) The symmetrical components of line currents. [8] (ii) Also find the symmetrical components of delta currents(NB convert delta circuit to star) [12]