Complementary technical information Influence of ambient temperature ,QÀXHQFHRIWHPSHUDWXUHRQWKHRSHUDWLRQ Devices DPN, C60H-DC, C60, C120, NG125, C60PV-DC circuit breakers iK60 circuit breakers iC60a/N/H/L circuit breakers Circuit breakers With Vigi (AC) With Vigi (A, SI) 5HÀH[L& C60H RCBO, C60H2 RCBO C60NA-DC, SW60PV-DC, C120NA-DC switch-disconnectors iID K residual current circuit breakers iID residual current AC circuit breakers A, SI Switches iSW iSW-NA Protection auxiliaries RCA, ARA control auxiliaries iCT contactors iTL impulse relays iCT, iTL auxiliaries Linergy DX Linergy FM Characteristics LQÀXHQFHGE\ temperature Temperature Min. Max. Tripping on overload -30°C +70°C Tripping on overload Tripping on overload Tripping on overload -25°C -35°C -5°C -25°C -25°C -15°C -25°C +60°C +70°C +60°C +60°C +60°C +60°C +70°C -5°C -5°C -25°C -20°C -35°C -35°C -25°C -5°C -20°C -20°C -25°C -25°C +60°C +60°C +60°C +50°C +70°C +70°C +60°C +60°C +50°C +50°C +60°C +60°C Tripping on overload Tripping on overload Maximum operating current Maximum operating current Maximum operating current Maximum operating current None None Installation conditions None None Maximum operating current Maximum operating current Note: the temperature considered is the temperature viewed through the device. Circuit breakers High temperatures b A rise in temperature causes lowering of the thermal threshold (tripping on overload). b Protection is still ensured: the tripping threshold remains lower than the current acceptable by the cable (Iz) b To prevent nuisance tripping, it should be checked that this threshold remains higher than the maximum operating current (IB RIWKHFLUFXLWGH¿QHGE\ v the rated load currents, v WKHFRHI¿FLHQWVRIH[SDQVLRQDQGVLPXOWDQHLW\RIXVH ,IWKHWHPSHUDWXUHLVVXI¿FLHQWO\KLJKIRUWKHWULSSLQJWKUHVKROGWREHFRPHORZHUWKDQ the operating current IB, switchboard ventilation should be provided for. Low temperatures b A fall in temperature increases the thermal tripping threshold of the circuit breaker. b There is no risk of nuisance tripping: the threshold remains higher than the maximum operating current of the circuit (IB) demanded by the loads. b It should be checked that the cable remains suitably protected, i.e. that its acceptable current (Iz) is higher than the values shown in the following tables (in amperes). When the ambient temperature could vary within a broad range, both these aspects must be taken into account: b the difference between the maximum operating current of the circuit (IB) and the tripping threshold of the circuit breaker for the minimum ambient temperature, b the difference between the strength of the cable (IZ) and the maximum tripping threshold of the circuit breaker for the maximum ambient temperature. 462 Version : 2.7 25/09/2013 CA908007E Complementary technical information Influence of ambient temperature (cont.) Maximum permissible current b 7KHPD[LPXPFXUUHQWDOORZHGWRÀRZWKURXJKWKHGHYLFHGHSHQGVRQWKHDPELHQW temperature in which it is placed. b The ambient temperature is the temperature inside the enclosure or switchboard in which the devices are installed. b The reference temperature is in a halftone colour for the different devices. b When several devices operating simultaneously are mounted side by side in a small enclosure, a temperature rise in the enclosure results in a reduction in the RSHUDWLQJFXUUHQW$UHGXFWLRQFRHI¿FLHQWRIZLOOWKHQKDYHWREHDVVLJQHGWRWKH rating (already derated, if applicable, depending on the ambient temperature). b Example: Depending on the ambient temperature and the method of installation, the table below shows how to determine, for an iC60, the operating currents not to be exceeded for ratings 25 A, 32 A and 40 A (reference temperature 50°C). Operating current not to be exceeded (A) Installation iC60 alone conditions (IEC 60947-2) CA908007E Ambient temperature (°C) 35°C Type Nominal rating (A) Actual rating (A) iC60 26.35 34 42.5 25 32 40 Version : 2.7 50°C Several iC60 in the same enclosure FDOFXODWHZLWKWKHUHGXFWLRQFRHI¿FLHQW indicated below) 25 32 40 65°C 23.57 29.9 37.34 25/09/2013 35°C 50°C 65°C 26.35 x 0.8 = 21 25 x 0.8 = 20 23.57 x 0.8 = 19 34 x 0.8 = 27 32 x 0.8 = 25.6 29.9 x 0.8 = 24 42.5 x 0.8 = 34 40 x 0.8 = 32 37.34 x 0.8 = 30 463 Complementary technical information Influence of ambient temperature (cont.) Household (IEC 60898-1) DPN derating table (IEC 60898-1) DPN Rating 1A 2A 3A 4A 6A 10 A 10 A 13 A 13 A 16 A 16 A 20 A 20 A 25 A 32 A 40 A Ambient temperature (°C) Curve -30 B, C, D 1.55 B, C, D 2.51 B, C, D 3.8 B, C, D 4.97 B, C, D 7.13 B 11.9 C, D 12.3 B 15.6 C, D 15.7 B, C 19 D 19.1 B 23.7 C, D 23.9 B, C, D 29.6 B, C, D 38.3 B, C, D 48.3 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 1.51 2.47 3.74 4.9 7.04 11.7 12.1 15.4 15.5 18.8 18.9 23.4 23.6 29.2 37.8 47.7 1.47 2.43 3.68 4.82 6.95 11.6 12 15.2 15.3 18.5 18.6 23.1 23.3 28.8 37.3 47 1.43 2.39 3.62 4.75 6.86 11.4 11.8 15 15.1 18.3 18.4 22.8 23 28.5 36.8 46.4 1.39 2.35 3.55 4.67 6.77 11.3 11.6 14.8 14.9 18.1 18.1 22.5 22.7 28.1 36.3 45.7 1.35 2.31 3.49 4.59 6.68 11.1 11.4 14.6 14.6 17.8 17.9 22.2 22.4 27.8 35.8 45 1.3 2.27 3.42 4.51 6.59 11 11.2 14.4 14.4 17.6 17.6 21.9 22 27.4 35.3 44.3 1.26 2.23 3.36 4.43 6.49 10.8 11 14.1 14.2 17.3 17.4 21.6 21.7 27 34.7 43.7 1.21 2.18 3.29 4.35 6.4 10.7 10.8 13.9 14 17.1 17.1 21.3 21.4 26.6 34.2 43 1.16 2.14 3.22 4.26 6.3 10.5 10.6 13.7 13.7 16.8 16.8 21 21 26.2 33.7 42.2 1.11 2.09 3.15 4.18 6.2 10.3 10.4 13.5 13.5 16.5 16.6 20.7 20.7 25.8 33.1 41.5 1.06 2.05 3.07 4.09 6.1 10.2 10.2 13.2 13.3 16.3 16.3 20.3 20.4 25.4 32.6 40.8 1 2 3 4 6 10 10 13 13 16 16 20 20 25 32 40 0.94 1.95 2.92 3.91 5.9 9.8 9.8 12.8 12.8 15.7 15.7 19.7 19.6 24.6 31.4 39.2 0.88 1.9 2.85 3.81 5.79 9.7 9.6 12.5 12.5 15.4 15.4 19.3 19.3 24.2 30.8 38.4 0.81 1.85 2.76 3.72 5.68 9.5 9.3 12.3 12.2 15.2 15.1 19 18.9 23.7 30.2 37.6 0.73 1.8 2.68 3.62 5.57 9.3 9.1 12 12 14.9 14.8 18.6 18.5 23.3 29.6 36.8 0.65 1.74 2.6 3.52 5.46 9.1 8.9 11.8 11.7 14.6 14.5 18.3 18.1 22.8 29 36 0.55 1.69 2.51 3.41 5.35 8.9 8.6 11.5 11.4 14.3 14.2 17.9 17.7 22.4 28.4 35.1 0.43 1.63 2.42 3.3 5.23 8.7 8.4 11.2 11.1 14 13.9 17.5 17.3 21.9 27.7 34.2 0.27 1.57 2.32 3.19 5.11 8.5 8.1 11 10.8 13.6 13.5 17.1 16.9 21.4 27 33.3 iK60 derating table. B curve (IEC 60898-1) iK60 Ambient temperature (°C) Rating -25 1A 2A 3A 4A 6A 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 1.19 2.45 3.69 4.92 7.44 11.9 19 23.5 29.1 37.9 47.4 59.9 76.4 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 1.17 2.41 3.63 4.84 7.32 11.8 18.7 23.2 28.8 37.4 46.7 59.1 75.3 1.15 2.37 3.57 4.77 7.2 11.6 18.5 22.9 28.4 36.9 46.1 58.2 74.1 1.14 2.34 3.51 4.69 7.07 11.4 18.2 22.6 28 36.4 45.5 57.4 73 1.12 2.3 3.45 4.61 6.95 11.3 18 22.3 27.7 35.9 44.8 56.5 71.8 1.11 2.26 3.39 4.53 6.82 11.1 17.7 22 27.3 35.3 44.2 55.6 70.6 1.09 2.22 3.33 4.44 6.69 10.9 17.4 21.7 26.9 34.8 43.5 54.7 69.4 1.07 2.17 3.27 4.36 6.56 10.8 17.1 21.4 26.6 34.3 42.8 53.8 68.2 1.05 2.13 3.2 4.27 6.42 10.6 16.9 21 26.2 33.7 42.1 52.9 66.9 1.04 2.09 3.14 4.18 6.29 10.4 16.6 20.7 25.8 33.2 41.4 52 65.6 1.02 2.04 3.07 4.09 6.14 10.2 16.3 20.4 25.4 32.6 40.7 51 64.3 1 2 3 4 6 10 16 20 25 32 40 50 63 0.98 1.95 2.93 3.91 5.85 9.8 15.7 19.7 24.6 31.4 39.3 49 61.6 0.96 1.91 2.86 3.81 5.7 9.6 15.4 19.3 24.2 30.8 38.5 48 60.3 0.94 1.86 2.78 3.71 5.54 9.4 15.1 18.9 23.8 30.2 37.7 46.9 58.8 0.92 1.81 2.71 3.61 5.38 9.2 14.8 18.6 23.3 29.6 37 45.9 57.4 0.9 1.76 2.63 3.5 5.22 9 14.5 18.2 22.9 28.9 36.2 44.8 55.9 0.88 1.71 2.55 3.39 5.04 8.8 14.1 17.8 22.5 28.3 35.3 43.6 54.3 iK60 derating table. C curve (IEC 60898-1) iK60 Ambient temperature (°C) Rating -25 1A 2A 3A 4A 6A 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 464 1.2 2.4 3.7 4.9 7.4 12.4 19.4 24 30 38.8 47.4 59.9 76.4 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 1.2 2.4 3.6 4.8 7.3 12.2 19.1 23.6 29.5 38.2 46.7 59.1 75.3 1.2 2.4 3.6 4.8 7.2 12 18.8 23.3 29.1 37.7 46.1 58.2 74.1 1.1 2.3 3.5 4.7 7.1 11.8 18.5 23 28.7 37.1 45.5 57.4 73 1.1 2.3 3.5 4.6 6.9 11.6 18.2 22.6 28.3 36.5 44.8 56.5 71.8 1.1 2.3 3.4 4.5 6.8 11.4 17.9 22.3 27.8 35.9 44.2 55.6 70.6 1.1 2.2 3.3 4.4 6.7 11.2 17.6 21.9 27.4 35.3 43.5 54.7 69.4 1.1 2.2 3.3 4.4 6.6 10.9 17.3 21.5 26.9 34.6 42.8 53.8 68.2 1.1 2.1 3.2 4.3 6.4 10.7 17 21.2 26.4 34 42.1 52.9 66.9 1 2.1 3.1 4.2 6.3 10.5 16.7 20.8 26 33.3 41.4 51.9 65.6 1 2 3.1 4.1 6.1 10.2 16.3 20.4 25.5 32.7 40.7 51 64.3 1 2 3 4 6 10 16 20 25 32 40 50 63 0.98 1.95 2.93 3.91 5.85 9.8 15.7 19.6 24.5 31.3 39.3 49 61.6 0.96 1.91 2.86 3.81 5.7 9.5 15.3 19.2 24 30.6 38.5 48 60.3 0.94 1.86 2.78 3.71 5.54 9.2 14.9 18.8 23.5 29.9 37.7 46.9 58.8 0.92 1.81 2.71 3.61 5.38 9 14.6 18.3 22.9 29.1 37 45.9 57.4 0.9 1.76 2.63 3.5 5.22 8.7 14.2 17.9 22.4 28.4 36.2 44.8 55.9 0.88 1.71 2.55 3.39 5.04 8.4 13.8 17.5 21.8 27.6 35.3 43.6 54.3 Version : 2.7 25/09/2013 CA908007E Complementary technical information Influence of ambient temperature (cont.) Household (IEC 60898-1) (cont.) iC60 derating table (IEC 60898-1) iC60 Ambient temperature (°C) Rating -35 -30 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 0.61 1.22 2.52 3.8 5.07 7.67 12.3 15.8 19.5 24.1 29.8 38.9 48.6 61.6 78.6 0.6 1.2 2.49 3.74 5 7.55 12.1 15.6 19.2 23.8 29.4 38.4 48 60.7 77.5 0.59 1.19 2.45 3.69 4.92 7.44 11.9 15.4 19 23.5 29.1 37.9 47.4 59.9 76.4 0.59 1.17 2.41 3.63 4.84 7.32 11.8 15.2 18.7 23.2 28.8 37.4 46.7 59.1 75.3 0.58 1.15 2.37 3.57 4.77 7.2 11.6 15 18.5 22.9 28.4 36.9 46.1 58.2 74.1 0.57 1.14 2.34 3.51 4.69 7.07 11.4 14.8 18.2 22.6 28 36.4 45.5 57.4 73 0.56 1.12 2.3 3.45 4.61 6.95 11.3 14.6 18 22.3 27.7 35.9 44.8 56.5 71.8 0.55 1.11 2.26 3.39 4.53 6.82 11.1 14.4 17.7 22 27.3 35.3 44.2 55.6 70.6 0.54 1.09 2.22 3.33 4.44 6.69 10.9 14.1 17.4 21.7 26.9 34.8 43.5 54.7 69.4 0.54 1.07 2.17 3.27 4.36 6.56 10.8 13.9 17.1 21.4 26.6 34.3 42.8 53.8 68.2 0.53 1.05 2.13 3.2 4.27 6.42 10.6 13.7 16.9 21 26.2 33.7 42.1 52.9 66.9 0.52 1.04 2.09 3.14 4.18 6.29 10.4 13.5 16.6 20.7 25.8 33.2 41.4 52 65.6 0.51 1.02 2.04 3.07 4.09 6.14 10.2 13.2 16.3 20.4 25.4 32.6 40.7 51 64.3 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63 0.49 0.98 1.95 2.93 3.91 5.85 9.8 12.8 15.7 19.7 24.6 31.4 39.3 49 61.6 0.48 0.96 1.91 2.86 3.81 5.7 9.6 12.5 15.4 19.3 24.2 30.8 38.5 48 60.3 0.47 0.94 1.86 2.78 3.71 5.54 9.4 12.3 15.1 18.9 23.8 30.2 37.7 46.9 58.8 0.46 0.92 1.81 2.71 3.61 5.38 9.2 12 14.8 18.6 23.3 29.6 37 45.9 57.4 0.45 0.9 1.76 2.63 3.5 5.22 9 11.8 14.5 18.2 22.9 28.9 36.2 44.8 55.9 0.44 0.88 1.71 2.55 3.39 5.04 8.8 11.5 14.1 17.8 22.5 28.3 35.3 43.6 54.3 0.43 0.86 1.65 2.47 3.28 4.87 8.5 11.2 13.8 17.4 22 27.6 34.5 42.5 52.8 0.42 0.84 1.59 2.38 3.17 4.68 8.3 10.9 13.4 17 21.5 26.9 33.6 41.3 51.1 0.5 A 1A 2A 3A 4A 6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A C60 derating table (IEC 60898-1) C60 Ambient temperature (°C) Rating -30 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 0.65 0.98 1.2 2.36 3.53 4.59 8.68 10.18 12.1 15.7 18.6 24.4 30 40.7 51.1 58.5 64.2 82.3 0.64 0.96 1.19 2.33 3.49 4.54 8.49 10.01 11.96 15.5 18.4 24.1 29.6 39.8 50.1 57.4 63 80.7 0.63 0.94 1.17 2.3 3.44 4.5 8.29 9.85 11.8 15.3 18.2 23.7 29.2 39.2 49.2 56.4 61.9 79.2 0.62 0.92 1.16 2.27 3.4 4.45 8.09 9.68 11.6 15.1 18 23.4 28.8 38.5 48.4 55.3 60.8 77.8 0.6 0.9 1.14 2.24 3.36 4.4 7.89 9.51 11.5 14.9 17.8 23 28.4 37.9 47.5 54.3 59.7 76.3 0.59 0.89 1.12 2.22 3.32 4.35 7.68 9.33 11.3 14.6 17.6 22.7 28 37.2 46.7 53.2 58.6 74.7 0.58 0.87 1.11 2.19 3.27 4.3 7.46 9.15 11.1 14.4 17.4 22.3 27.6 36.5 45.8 52.1 57.4 73.2 0.57 0.85 1.09 2.16 3.23 4.26 7.24 8.97 10.9 14.2 17.1 22 27.2 35.8 44.9 51 56.3 71.6 0.55 0.83 1.07 2.13 3.19 4.21 7.01 8.79 10.8 14 16.9 21.6 26.8 35.1 43.9 49.9 55.1 69.9 0.54 0.81 1.05 2.1 3.14 4.15 6.77 8.6 10.6 13.7 16.7 21.2 26.3 34.3 43 48.7 53.8 68.3 0.53 0.79 1.04 2.06 3.09 4.10 6.52 8.4 10.4 13.5 16.5 20.8 25.9 33.6 42 47.5 52.6 66.6 0.51 0.77 1.02 2.03 3.05 4.05 6.27 8.2 10.2 13.2 16.2 20.4 25.5 32.8 41 46.3 51.3 64.8 0.5 0.75 1 2 3 4 6 8 10 13 16 20 25 32 40 45 50 63 0.49 0.73 0.98 1.97 2.95 3.95 5.72 7.79 9.8 12.7 15.8 19.6 24.5 31.2 39 43.7 48.7 61.1 0.47 0.71 0.96 1.93 2.9 3.89 5.43 7.58 9.6 12.5 15.5 19.2 24.1 30.4 37.9 42.4 47.3 59.2 0.45 0.68 0.94 1.9 2.85 3.84 5.12 7.36 9.4 12.2 15.3 18.7 23.6 29.5 36.8 41 45.8 57.2 0.44 0.66 0.92 1.87 2.8 3.78 4.79 7.13 9.2 12 15 18.3 23.1 28.6 35.6 39.6 44.4 55.2 0.42 0.63 0.9 1.83 2.75 3.73 4.43 6.89 9 11.7 14.8 17.8 22.6 27.7 34.5 38.1 42.8 53.1 0.4 0.61 0.88 1.79 2.7 3.67 4.05 6.65 8.8 11.4 14.5 17.4 22.1 26.8 33.2 36.5 41.3 50.8 0.38 0.59 0.86 1.76 2.64 3.61 3.62 6.4 8.5 11.1 14.2 16.9 21.6 25.6 31.8 35 39.5 48.7 0.36 0.57 0.84 1.72 2.59 3.55 3.13 6.13 8.3 10.8 14 16.4 21 24.6 30.5 33.5 37.9 46.6 0.5 A 0.75 A 1A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 45 A 50 A 63 A C120 derating table (IEC 60898-1) C120 Ambient temperature (°C) Rating -30 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A 125 A 12.9 19.4 24.6 30.9 38.9 49.8 62.2 78.6 98.4 124.5 157 CA908007E -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 12.7 19.1 24.2 30.5 38.4 49.1 61.3 77.5 97 122.6 154.6 12.5 18.8 23.9 30 37.9 48.3 60.4 76.3 95.6 120.7 152.2 12.2 18.6 23.5 29.5 37.3 47.6 59.4 75 94.2 118.8 149.7 12 18.3 23.2 29.1 36.8 46.8 58.4 73.8 92.7 116.9 147.1 11.8 18 22.8 28.6 36.2 46 57.5 72.5 91.2 114.9 144.6 11.5 17.8 22.4 28.1 35.6 45.2 56.5 71.3 89.7 112.9 141.9 11.3 17.5 22 27.6 35 44.4 55.4 69.9 88.1 110.9 139.2 11 17.2 21.6 27.1 34.5 43.5 54.4 68.6 86.6 108.8 136.5 10.8 16.9 21.2 26.6 33.9 42.7 53.3 67.3 85 106.6 133.7 10.5 16.6 20.8 26.1 33.3 41.8 52.2 65.9 83.4 104.5 130.9 10.3 16.3 20.4 25.5 32.6 40.9 51.1 64.5 81.7 102.3 128 10 16 20 25 32 40 50 63 80 100 125 9.4 15.4 19.1 23.9 30.7 38.1 47.7 60 76.5 95.3 118.8 9.1 15.1 18.7 23.3 30 37.1 46.4 58.4 74.7 92.9 115.6 8.8 14.7 18.2 22.7 29.3 36.1 45.2 56.8 72.8 90.4 112.3 8.5 14.4 17.7 22.1 28.6 35.1 43.9 55.2 70.9 87.8 108.9 8.2 14 17.3 21.5 27.9 34.1 42.6 53.5 69 85.2 105.4 7.9 13.7 16.8 20.8 27.2 33 41.2 51.7 67 82.5 101.8 7.5 13.3 16.2 20.1 26.4 31.8 39.8 49.9 64.9 79.6 98 Version : 2.7 9.7 15.7 19.6 24.4 31.4 39.1 48.8 61.5 78.3 97.7 122 25/09/2013 465 Complementary technical information Influence of ambient temperature (cont.) Tertiary/Industry (IEC 60947-2) DPN derating table (IEC 60947-2) DPN Rating 1A 2A 3A 4A 6A 10 A 10 A 13 A 13 A 16 A 16 A 20 A 20 A 25 A 32 A 40 A Ambient temperature (°C) Curve -30 B, C, D 1.69 B, C, D 2.68 B, C, D 4.03 B, C, D 5.26 B, C, D 7.51 B 12.5 C, D 13 B 17 C, D 17.2 B, C 20.6 D 20.8 B 25.7 C, D 26 B, C, D 32 B, C, D 41.6 B, C, D 52.7 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 1.66 2.64 3.97 5.19 7.42 12.3 12.9 16.7 16.9 20.4 20.5 25.3 25.7 31.6 41.1 52 1.62 2.6 3.91 5.12 7.34 12.2 12.7 16.5 16.7 20.1 20.2 25 25.3 31.2 40.5 51.3 1.59 2.56 3.86 5.05 7.25 12.1 12.5 16.3 16.5 19.8 20 24.7 25 30.8 40 50.6 1.55 2.52 3.8 4.98 7.16 11.9 12.3 16.1 16.2 19.6 19.7 24.4 24.6 30.4 39.4 49.8 1.51 2.48 3.74 4.9 7.07 11.8 12.2 15.8 16 19.3 19.4 24 24.3 30 38.9 49.1 1.47 2.44 3.68 4.83 6.98 11.6 12 15.6 15.7 19 19.1 23.7 23.9 29.6 38.3 48.3 1.43 2.4 3.61 4.75 6.89 11.5 11.8 15.4 15.5 18.7 18.8 23.4 23.6 29.2 37.7 47.6 1.39 2.36 3.55 4.67 6.8 11.3 11.6 15.1 15.2 18.5 18.5 23 23.2 28.7 37.1 46.8 1.35 2.32 3.49 4.6 6.7 11.2 11.4 14.9 15 18.2 18.2 22.7 22.8 28.3 36.5 46 1.3 2.28 3.42 4.52 6.61 11 11.2 14.6 14.7 17.9 17.9 22.3 22.4 27.8 35.9 45.2 1.26 2.23 3.36 4.43 6.51 10.8 11 14.4 14.4 17.6 17.6 21.9 22 27.4 35.3 44.4 1.21 2.19 3.29 4.35 6.41 10.7 10.8 14.1 14.2 17.3 17.3 21.6 21.7 26.9 34.7 43.5 1.16 2.14 3.22 4.27 6.31 10.5 10.6 13.8 13.9 17 17 21.2 21.3 26.5 34 42.7 1.11 2.1 3.15 4.18 6.21 10.3 10.4 13.6 13.6 16.7 16.7 20.8 20.8 26 33.4 41.8 1.06 2.05 3.07 4.09 6.11 10.2 10.2 13.3 13.3 16.3 16.3 20.4 20.4 25.5 32.7 40.9 1 2 3 4 6 10 10 13 13 16 16 20 20 25 32 40 0.94 1.95 2.92 3.91 5.89 9.8 9.8 12.7 12.7 15.7 15.7 19.6 19.6 24.5 31.3 39.1 0.88 1.9 2.85 3.81 5.78 9.7 9.6 12.4 12.4 15.3 15.3 19.2 19.1 24 30.6 38.1 0.81 1.85 2.77 3.72 5.67 9.5 9.3 12.1 12.1 15 14.9 18.8 18.7 23.5 29.9 37.1 0.73 1.79 2.68 3.62 5.56 9.3 9.1 11.8 11.7 14.6 14.6 18.3 18.2 22.9 29.1 36.1 L&5HÀH[L&GHUDWLQJWDEOH ,(& iC60 Ambient temperature (°C) Rating -35 -30 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 0.66 1.32 2.79 4.21 5.62 8.55 13.3 17.1 21.1 26 31.9 42 52.6 67.1 86.3 0.65 1.3 2.75 4.15 5.54 8.42 13.2 16.9 20.8 25.7 31.6 41.5 51.9 66.3 85.1 0.64 1.28 2.71 4.08 5.46 8.29 13 16.7 20.6 25.4 31.2 41 51.3 65.4 83.9 0.63 1.27 2.67 4.02 5.37 8.16 12.8 16.4 20.3 25 30.8 40.5 50.6 64.5 82.7 0.63 1.25 2.63 3.96 5.29 8.03 12.6 16.2 20 24.7 30.4 39.9 49.9 63.5 81.4 0.62 1.23 2.58 3.89 5.2 7.89 12.5 16 19.7 24.4 30.1 39.4 49.2 62.6 80.1 0.61 1.21 2.54 3.83 5.11 7.75 12.3 15.8 19.5 24.1 29.7 38.8 48.5 61.6 78.9 0.6 1.2 2.5 3.76 5.02 7.61 12.1 15.5 19.2 23.7 29.3 38.2 47.8 60.7 77.6 0.59 1.18 2.45 3.69 4.93 7.46 11.9 15.3 18.9 23.4 28.9 37.7 47.1 59.7 76.2 0.58 1.16 2.4 3.62 4.83 7.31 11.7 15.1 18.6 23 28.5 37.1 46.4 58.7 74.9 0.57 1.14 2.36 3.55 4.74 7.16 11.5 14.8 18.3 22.7 28.1 36.5 45.6 57.7 73.5 0.56 1.12 2.31 3.48 4.64 7.01 11.3 14.6 18 22.3 27.6 35.9 44.9 56.7 72.1 0.55 1.1 2.26 3.4 4.54 6.85 11.1 14.3 17.7 21.9 27.2 35.3 44.1 55.6 70.7 0.54 1.08 2.21 3.32 4.44 6.69 10.9 14.1 17.3 21.6 26.8 34.6 43.3 54.5 69.2 0.53 1.06 2.16 3.25 4.33 6.52 10.7 13.8 17 21.2 26.4 34 42.5 53.4 67.7 0.52 1.04 2.11 3.17 4.22 6.35 10.5 13.6 16.7 20.8 25.9 33.3 41.7 52.3 66.2 0.51 1.02 2.05 3.08 4.11 6.18 10.2 13.3 16.3 20.4 25.5 32.7 40.9 51.2 64.6 0.5 1 2 3 4 6 10 13 16 20 25 32 40 50 63 0.49 0.98 1.94 2.91 3.88 5.81 9.8 12.7 15.7 19.6 24.5 31.3 39.1 48.8 61.4 0.48 0.96 1.89 2.82 3.76 5.62 9.5 12.4 15.3 19.2 24.1 30.6 38.2 47.6 59.7 0.47 0.93 1.83 2.73 3.64 5.43 9.3 12.1 14.9 18.7 23.6 29.9 37.3 46.3 57.9 0.45 0.91 1.76 2.64 3.51 5.22 9 11.8 14.5 18.3 23.1 29.1 36.4 45 56.1 0.5 A 1A 2A 3A 4A 6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 5HÀH[L& C60 derating table (IEC 60947-2) C60 Ambient temperature (°C) Rating -30 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 0.68 0.93 1.31 2.55 3.81 4.9 7.93 10.37 13.3 17 20 26.9 32.9 41.5 53.7 60.8 65 85.5 0.67 0.92 1.3 2.59 4.04 4.86 7.82 10.23 13.2 16.9 19.8 26.6 32.5 41.1 52.9 60.1 64.3 84.6 0.66 0.91 1.28 2.56 3.98 4.81 7.71 10.09 13 16.6 19.5 26.2 32.1 40.5 52.2 59.2 63.5 83.3 0.65 0.9 1.27 2.52 3.92 4.76 7.6 9.96 12.8 16.4 19.3 25.8 31.6 40 51.4 58.3 62.6 82 0.64 0.89 1.25 2.49 3.85 4.7 7.49 9.82 12.6 16.2 19.1 25.4 31.1 39.4 50.6 57.4 61.7 80.7 0.63 0.88 1.23 2.45 3.79 4.65 7.38 9.68 12.4 15.9 18.8 25 30.7 38.9 49.8 56.5 60.8 79.4 0.62 0.87 1.21 2.41 3.73 4.59 7.27 9.54 12.2 15.7 18.6 24.6 30.2 38.3 49 55.5 59.9 78 0.61 0.86 1.19 2.37 3.66 4.54 7.15 9.4 12 15.4 18.4 24.2 29.7 37.7 48.2 54.6 59 76.7 0.6 0.85 1.17 2.34 3.59 4.48 7.03 9.25 11.8 15.2 18.1 23.7 29.2 37.1 47.3 53.6 58.1 75.3 0.59 0.83 1.15 2.3 3.52 4.42 6.91 9.11 11.6 14.9 17.9 23.3 28.7 36.5 46.5 52.6 57.1 73.9 0.58 0.82 1.13 2.26 3.45 4.37 6.79 8.96 11.4 14.7 17.6 22.9 28.2 35.9 45.6 51.6 56.2 72.4 0.56 0.81 1.11 2.22 3.38 4.31 6.66 8.81 11.2 14.4 17.3 22.4 27.7 35.3 44.7 50.5 55.2 70.9 0.55 0.8 1.09 2.17 3.31 4.25 6.54 8.65 10.9 14.1 17.1 22 27.2 34.7 43.8 49.5 54.2 69.4 0.54 0.79 1.07 2.13 3.23 4.19 6.41 8.49 10.7 13.9 16.8 21.5 26.7 34 42.9 48.4 53.2 67.9 0.53 0.78 1.05 2.09 3.16 4.13 6.27 8.33 10.5 13.6 16.6 21 26.1 33.4 42 47.3 52.1 66.3 0.51 0.76 1.02 2.04 3.08 4.06 6.14 8.17 10.2 13.3 16.3 20.5 25.6 32.7 41 46.2 51.1 64.7 0.5 0.75 1 2 3 4 6 8 10 13 16 20 25 32 40 45 50 63 0.49 0.74 0.98 1.95 2.92 3.94 5.86 7.83 9.8 12.7 15.7 19.5 24.4 31.3 39 43.8 48.9 61.3 0.47 0.72 0.95 1.91 2.83 3.87 5.71 7.65 9.5 12.4 15.4 18.9 23.8 30.6 37.9 42.6 47.8 59.5 0.46 0.7 0.93 1.88 2.82 3.81 5.56 7.47 9.2 12.1 15.1 18.4 23.2 29.9 36.9 41.4 46.7 57.8 0.44 0.68 0.91 1.84 2.76 3.74 5.42 7.31 9 11.8 14.8 17.9 22.6 29.1 35.8 40.1 45.5 56 0.5 A 0.75 A 1A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 45 A 50 A 63 A 466 Version : 2.7 25/09/2013 CA908007E Complementary technical information Influence of ambient temperature (cont.) Tertiary/Industry (IEC 60947-2) (cont.) C60H-DC derating table (IEC 60947-2) C60H-DC Ambient temperature (°C) Rating -30 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 0.5 A 1A 2A 3A 4A 5A 6A 10 A 13 A 15 A 16 A 20 A 25 A 30 A 32 A 40 A 50 A 63 A 0.63 1.18 2.54 3.78 5.08 6 7.26 12.6 15.5 18.6 19.4 24.1 30.4 37.4 38.5 48.9 59.9 78.2 0.62 1.17 2.5 3.71 4.99 5.92 7.15 12.4 15.3 18.3 19.1 23.7 29.9 36.7 37.9 48.2 59.1 76.9 0.61 1.15 2.45 3.65 4.9 5.83 7.04 12.2 15.1 18 18.9 23.4 29.5 36.1 37.4 47.4 58.3 75.6 0.6 1.14 2.41 3.58 4.81 5.74 6.94 11.9 14.9 17.7 18.6 23 29 35.5 36.8 46.7 57.4 74.3 0.59 1.12 2.36 3.51 4.71 5.66 6.83 11.7 14.6 17.4 18.3 22.7 28.5 34.9 36.2 45.9 56.5 73 0.58 1.1 2.31 3.45 4.62 5.57 6.71 11.5 14.4 17.1 18 22.3 28.1 34.2 35.7 45.1 55.6 71.7 0.56 1.09 2.26 3.38 4.52 5.48 6.6 11.3 14.2 16.7 17.6 21.9 27.6 33.5 35.1 44.3 54.7 70.3 0.55 1.07 2.21 3.3 4.42 5.39 6.48 11 14 16.4 17.3 21.6 27.1 32.9 34.5 43.5 53.8 68.9 0.54 1.05 2.16 3.23 4.32 5.29 6.37 10.8 13.7 16.1 17 21.2 26.6 32.2 33.9 42.6 52.9 67.5 0.53 1.04 2.11 3.16 4.22 5.2 6.25 10.5 13.5 15.7 16.7 20.8 26.1 31.5 33.3 41.8 52 66 0.51 1.02 2.06 3.08 4.11 5.1 6.12 10.3 13.3 15.4 16.3 20.4 25.5 30.7 32.6 40.9 51 64.5 0.5 1 2 3 4 5 6 10 13 15 16 20 25 30 32 40 50 63 0.49 0.98 1.94 2.92 3.89 4.9 5.87 9.7 12.8 14.6 15.7 19.6 24.5 29.2 31.4 39.1 49 61.4 0.47 0.96 1.88 2.84 3.77 4.8 5.74 9.5 12.5 14.3 15.3 19.2 23.9 28.5 30.7 38.2 48 59.8 0.46 0.94 1.82 2.75 3.65 4.69 5.61 9.2 12.2 13.9 14.9 18.7 23.3 27.7 30 37.2 46.9 58.2 0.44 0.92 1.76 2.66 3.53 4.58 5.47 8.9 12 13.5 14.6 18.3 22.7 26.8 29.3 36.2 45.9 56.5 0.43 0.9 1.7 2.57 3.4 4.47 5.33 8.6 11.7 13 14.2 17.9 22.1 26 28.6 35.2 44.8 54.7 0.41 0.88 1.63 2.48 3.27 4.36 5.19 8.3 11.4 12.6 13.8 17.4 21.5 25.1 27.9 34.2 43.6 52.9 0.39 0.86 1.56 2.38 3.13 4.24 5.04 7.9 11.1 12.2 13.4 16.9 20.9 24.2 27.1 33.1 42.5 51.1 0.38 0.84 1.48 2.27 2.98 4.12 4.89 7.6 10.8 11.7 13 16.4 20.2 23.2 26.3 32 41.3 49.1 0.36 0.82 1.41 2.17 2.83 4 4.73 7.2 10.5 11.2 12.5 15.9 19.6 22.3 25.5 30.8 40.1 47.1 C60PV-DC derating table (IEC 60947-2) C60PV-DC Ambient temperature (°C) Rating 1A 2A 3A 5A 8A 10 A 13 A 15 A 16 A 20 A 25 A -30 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 1.18 2.54 3.78 6 9.64 12.6 15.5 18.6 19.4 24.1 30.4 1.17 2.5 3.71 5.92 9.5 12.4 15.3 18.3 19.1 23.7 29.9 1.15 2.45 3.65 5.83 9.36 12.2 15.1 18 18.9 23.4 29.5 1.14 2.41 3.58 5.74 9.22 11.9 14.8 17.7 18.6 23 29 1.12 2.36 3.51 5.66 9.08 11.7 14.6 17.4 18.3 22.7 28.5 1.1 2.31 3.45 5.57 8.93 11.5 14.4 17.1 18 22.3 28.1 1.09 2.26 3.38 5.48 8.78 11.2 14.2 16.7 17.6 21.9 27.6 1.07 2.21 3.3 5.39 8.63 11 14 16.4 17.3 21.6 27.1 1.05 2.16 3.23 5.29 8.48 10.8 13.7 16.1 17 21.2 26.6 1.04 2.11 3.16 5.2 8.32 10.5 13.5 15.7 16.7 20.8 26.1 1.02 2.06 3.08 5.1 8.16 10.3 13.2 15.4 16.3 20.4 25.5 1 2 3 5 8 10 13 15 16 20 25 0.98 1.94 2.92 4.9 7.83 9.7 12.7 14.6 15.7 19.6 24.5 0.96 1.88 2.84 4.8 7.67 9.4 12.5 14.3 15.3 19.2 23.9 0.94 1.82 2.75 4.69 7.49 9.2 12.2 13.9 14.9 18.7 23.3 0.92 1.76 2.66 4.58 7.31 8.9 12 13.5 14.6 18.3 22.7 0.9 1.7 2.57 4.47 7.13 8.6 11.7 13 14.2 17.9 22.1 0.88 1.63 2.48 4.36 6.95 8.2 11.4 12.6 13.8 17.4 21.5 0.86 1.56 2.38 4.24 6.76 7.9 11.1 12.2 13.4 16.9 20.9 0.84 1.48 2.27 4.12 6.56 7.6 10.8 11.7 13 16.4 20.2 0.82 1.41 2.17 4 6.36 7.2 10.5 11.2 12.5 15.9 19.6 C120 derating table (IEC 60947-2) C120 Ambient temperature (°C) Rating -30 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A 125 A 14.5 21.2 27 33.7 42.7 54.8 69.1 87.1 103.7 137.6 174.6 CA908007E -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 14.3 21 26.6 33.3 42.1 54 68.1 85.8 102.4 135.5 171.9 14 20.7 26.3 32.8 41.5 53.2 67 84.5 101 133.5 169.2 13.8 20.4 25.9 32.3 40.9 52.4 65.9 83.1 99.7 131.4 166.4 13.5 20.1 25.5 31.8 40.3 51.5 64.8 81.8 98.3 129.2 163.6 13.3 19.8 25 31.3 39.7 50.7 63.7 80.4 96.9 127.1 160.7 13 19.4 24.6 30.8 39 49.8 62.6 78.9 95.5 124.8 157.8 12.7 19.1 24.2 30.2 38.4 48.9 61.5 77.5 94.1 122.6 154.9 12.5 18.8 23.8 29.7 37.7 48 60.3 76 92.6 120.3 151.8 12.2 18.5 23.3 29.1 37.1 47.1 59.1 74.5 91.1 118 148.7 11.9 18.2 22.9 28.6 36.4 46.1 57.9 73 89.6 115.6 145.6 11.6 17.8 22.4 28 35.7 45.2 56.7 71.4 88.1 113.1 142.4 11.3 17.5 22 27.5 35 44.2 55.4 69.8 86.5 110.6 139.1 11 17.1 21.5 26.9 34.3 43.2 54.1 68.2 84.9 108.1 135.7 10.7 16.8 21 26.3 33.5 42.1 52.8 66.5 83.3 105.5 132.2 10.3 16.4 20.5 25.6 32.8 41.1 51.4 64.8 81.7 102.8 128.7 10 16 20 25 32 40 50 63 80 100 125 9.3 15.2 18.9 23.7 30.4 37.7 47.1 59.3 76.5 94.2 117.3 8.9 14.8 18.4 23 29.6 36.6 45.5 57.4 74.7 91.2 113.3 8.5 14.4 17.8 22.3 28.7 35.3 43.9 55.4 72.9 88.1 109.1 Version : 2.7 25/09/2013 9.7 15.6 19.5 24.4 31.2 38.9 48.6 61.2 78.3 97.2 121.2 467 Complementary technical information Influence of ambient temperature (cont.) Tertiary/Industry (IEC 60947-2) (cont.) NG125 derating table (IEC 60947-2) NG125 Ambient temperature (°C) Rating -30 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A 125 A 13.7 20.3 26 33.8 41.2 53.5 66.3 83.4 100.4 133.4 165.2 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 +65 +70 13.5 20.1 25.6 33.2 40.6 52.7 65.2 82.1 99.1 131.3 162.7 13.2 19.8 25.3 32.7 40 51.8 64.2 80.8 97.8 129.1 160.1 13 19.5 24.9 32.1 39.4 51 63.1 79.5 96.4 127 157.5 12.8 19.2 24.5 31.5 38.8 50.1 62.1 78.1 95 124.8 154.8 12.5 18.9 24 30.9 38.2 49.1 61 76.8 93.6 122.5 152.1 12.3 18.6 23.6 30.3 37.5 48.2 59.8 75.4 92.2 120.2 149.3 12 18.3 23.2 29.7 36.9 47.3 58.7 73.9 90.8 117.9 146.5 11.7 18 22.8 29.1 36.2 46.3 57.5 72.5 89.3 115.5 143.6 11.5 17.7 22.3 28.4 35.6 45.3 56.4 71 87.8 113.1 140.7 11.2 17.4 21.9 27.8 34.9 44.3 55.1 69.5 86.3 110.6 137.7 10.9 17 21.4 27.1 34.2 43.3 53.9 67.9 84.8 108 134.6 10.6 16.7 21 26.4 33.5 42.2 52.6 66.3 83.2 105.4 131.5 10.3 16.4 20.5 25.7 32.7 41.1 51.3 64.7 81.6 102.7 128.3 10 16 20 25 32 40 50 63 80 100 125 9.7 15.7 19.5 24.3 31.2 38.9 48.6 61.3 78.3 97.2 121.6 9.4 15.3 19 23.5 30.5 37.7 47.2 59.5 76.6 94.3 118.1 9 14.9 18.5 22.7 29.7 36.5 45.8 57.7 74.9 91.3 114.6 8.7 14.5 17.9 21.9 28.8 35.2 44.3 55.8 73.1 88.2 110.9 8.3 14.1 17.4 21 28 33.9 42.7 53.9 71.3 85 107 7.9 13.7 16.8 20.1 27.1 32.5 41.1 51.8 69.4 81.6 103.1 Tertiaire/Industrie (IEC 60947-3) SW60-DC derating table (IEC 60947-3) SW60PV-DC Ambient temperature (°C) Rating 50 A +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +60 +70 63 61 60 58 56 54 52 50 48 46 41 35 C60NA-DC derating table (IEC 60947-3) C60NA-DC Ambient temperature (°C) Rating +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +60 +70 63 61 60 58 56 54 52 50 48 46 41 35 50 A C120NA-DC derating table (IEC 60947-3) C120NA-DC Ambient temperature (°C) Rating 100 A +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +60 +70 113 111 110 108 106 104 102 100 98 96 91 85 Tertiary/Industry (IEC 61009-1) C60H2 RCBO derating table (IEC 61009-1) C60H2 RCBO Ambient temperature (°C) Rating -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 12.3 19.6 24.9 30.2 37.9 12.2 19.4 24.6 29.8 37.5 12 19.1 24.2 29.5 37.1 11.8 18.8 23.9 29.1 36.7 11.7 18.6 23.5 28.7 36.2 11.5 18.3 23.2 28.3 35.8 11.3 18 22.8 27.9 35.3 11.1 17.8 22.4 27.5 34.9 11 17.5 22 27.1 34.4 10.8 17.2 21.6 26.7 33.9 10.6 16.9 21.2 26.3 33.5 10.4 16.6 20.8 25.9 33 10.2 16.3 20.4 25.4 32.5 10 16 20 25 32 9.8 15.7 19.6 24.6 31.5 9.6 15.4 19.1 24.1 31 10 A 16 A 20 A 25 A 32 A C60N/H RCBO derating table (IEC 61009-1) C60H RCBO Ambient temperature (°C) Rating -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60 8.3 12.9 20.9 26.3 31.5 39.2 50.2 55.5 8.15 12.7 20.6 25.9 31 38.7 49.5 54.7 7.99 12.5 20.3 25.4 30.6 38.2 48.8 54 7.83 12.3 19.9 25 30.1 37.7 48 53.2 7.67 12.1 19.6 24.5 29.6 37.2 47.3 52.5 7.50 11.9 19.2 24.1 29.2 36.6 46.5 51.7 7.33 11.6 18.8 23.6 28.7 36.1 45.8 50.9 7.16 11.4 18.4 23.1 28.2 35.5 45 50.1 6.98 11.2 18.1 22.6 27.7 35 44.2 49.3 6.79 11 17.7 22.1 27.2 34.4 43.4 48.5 6.6 10.7 17.3 21.6 26.6 33.8 42.6 47.6 6.41 10.5 16.9 21.1 26.1 33.2 41.7 46.8 6.21 10.3 16.4 20.6 25.6 32.6 40.9 45.9 6 10 16 20 25 32 40 45 5.78 9.7 15.6 19.4 24.4 31.4 39.1 41.9 5.56 9.5 15.1 18.8 23.8 30.7 38.2 41 6A 10 A 16 A 20 A 25 A 32 A 40 A 45 A 468 Version : 2.7 25/09/2013 CA908007E Complementary technical information Influence of ambient temperature (cont.) Switches b In all cases, the switches are correctly protected against overloads by a circuit breaker with a lower or equal rating, operating at the same ambient temperature. iCT contactors DB123331 In the case of contactor mounting in an enclosure for which the interior temperature is in a range between 50°C and 60°C, it is necessary to use a spacer, cat. no. A9A27062, between each contactor. Spacer cat. no. A9A27062 CA908007E Splitter blocks In the event of a temperature higher than 40°C, the maximum acceptable current is limited to the values in the table below: Type Temperature Linergy FM 80 A Linergy DX 63 A 40°C 80 63 Version : 2.7 45°C 76 60 25/09/2013 50°C 73 58 55°C 69 55 60°C 66 53 469