Installation Instructions Original Instructions SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Catalog Numbers Low-level Coding: 440N-Z21S16A, 440N-Z21S16B, 440N-Z21S16H, 440N-Z21S16J, 440N-Z21S17A, 440N-Z21S17B, 440N-Z21S17H, 440N-Z21S26A, 440N-Z21S26B, 440N-Z21S26H, 440N-Z21S26J, 440N-Z21S17J, 440N-Z21X16H, 440N-Z21S16E, 440N-Z21S17B-PUR High-level Coding: 440N-Z21U16A, 440N-Z21U16B, 440N-Z21U16H, 440N-Z21U16J, 440N-Z21U17A, 440N-Z21U17B, 440N-Z21U17H, 440N-Z21U26A, 440N-Z21U26B, 440N-Z21U26H, 440N-Z21U26J, 440N-Z21U17J IMPORTANT Save these instructions for future use. WARNING: Do not defeat, tamper, remove, or bypass this unit. Severe injury to personnel can result. Topic Page Specifications 2 Approximate Dimensions 2 Mode of Operation 2 Installation 3 Diagnostics 3 Typical Wiring 3 Commission the Unique Coded Actuator 4 Unique Coded Diagnostic 4 OSSD Test Pulses 5 Timing Diagram 5 Troubleshooting 6 Application Wiring Examples 6 Recommended Safety Control Interfaces 11 Maintenance 11 Repair 11 Additional Resources 12 Summary of Changes This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes. Topic Page Updated Certifications 2 Added Recommended Safety Control Interfaces 11 Added Maintenance 11 Added Repair 11 Added Declaration of Conformity 12 Installation must be in accordance with the following instructions and specifications and implemented by suitable competent personnel. Adherence to the recommended maintenance instructions forms part of the warranty. ATTENTION: You must provide this device with a 24V DC PELV or SELV power supply that conforms to the requirements of 414-3 of IEC 60364-4-41 where provisions are taken. The voltage at the outgoing terminals cannot exceed 60V DC, even if there is an internal fault. Improper selection or installation of the devices affects the integrity of the safety systems. Personal injury or death, property damage, or economic loss can result. Comply with ISO 14119 including section, accessibility to the installation, arrangement, and mounting, possible substitute actuation, access to the escape release, motivation to defeat, and actuation mode. Use management controls, working procedures, training, and additional protective measures to minimize the motivation to defeat and to manage the use and availability of spare actuators. Comply with ISO 13857 and ISO 13855 for guard openings and minimum (safe) distances. Comply with ISO 13849-1 and ISO 13849-2 for functional safety. This product is intended for industrial/business application only. This product is not intended for use in residential applications, as it can cause radio interference on other residential devices. ATTENTION: Read this document and the documents that are listed in Additional Resources on page 12 before you install. Familiarize yourself with the installation and connection instructions and requirements of all applicable codes, laws, and standards. In accordance with applicable codes of practice, suitably trained personnel must implement installation, adjustments, service initiation, use, assembly, disassembly, and maintenance. Use of this equipment that is not specified by the manufacturer can impair the protection that the equipment provides. Do not use this unit as a mechanical stop. You must fit guard stops and guides. This device is intended to be part of the safety-related control system of a machine. Before installation, you must perform a risk assessment to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics. ATTENTION: Do not attempt to install this device unless you study and understand the installation instructions. This document acts as a guide for a typical installation. SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Specifications Attribute Approximate Dimensions 18 mm Plastic Actuator 30 mm Plastic Actuator 18 mm Stainlesssteel Actuator Figure 1 - 18 mm Plastic Barrel [mm (in.)] 16.84 (0.66) Safety Ratings Standards safety classification IEC 60947-5-3, Cat. 4 PLe Per ISO 13849-1, Type 4 Interlocking Device according to ISO 14119 with either low (standard) or high (unique) coding, SIL CL 3 per IEC 61508 Functional safety data PFHD = 1.32E-9 (probability of dangerous failure per hr) T1 = 20 (proof test interval) Certifications CE Marked for all applicable EU directives, UKCA Marked for all applicable regulations, cULus Listed (UL 508), and TÜV Certified rok.auto/certifications 3.17 (0.12) 22.22 (0.87) 30.40 (1.20) Ø4.57 (0.18) dia. Places 2Two places 48.92 (1.94) 19.81 (0.78) 19.81 (0.78) 30 mm Actuator 30 mm Actuator Operating Characteristics 22.22 (0.87) 48.92 (1.94) Sensing distance, assured on [mm (in.)] 15 (0.59) 25 (0.98) 10 (0.39) Sensing distance, assured off [mm (in.)] 25 (0.98) 35 (1.78) 20 (0.79) Operating voltage 24V DC 10%/-15% Class 2 SELV or PELV power supply Response time (off) 45 ms Utilization category DC-12 and DC-13 Ue: 24V le: 200 mA Frequency of operating cycle 0.25 Hz No-load supply current < 50 mA 15.42 (0.61) 36.47 (1.44) 3.17 (0.12) 19.81 (0.78) Safe state De-energized (2 x PNP, 0V), AUX energized (1 x PNP, 24V) Run state Energized (2 x PNP, 24V), AUX de-energized (1 x PNP, 0V) Load current, max 200 mA Voltage drop < 1.5V Switches connected in series Unlimited (see Timing Diagram on page 5) 67.06 (2.64) 2.03 (0.08) 15.87 (0.62) 18 mm Actuator 18 mm Actuator Outputs (OSSD) Ø4.57 (0.18) dia. Places 2Two places 13.72 (0.54) 15.87 (0.62) 36.47 (1.44) Sensor 14.43 (0.57) Ø4.57 (0.18) dia. Places 2Two places 36.47 15.87 (1.44) (0.62) Mechanical Polycarbonate Stainless steel 304 Actuator case material Polycarbonate Stainless steel 304 Sensor Figure 2 - 18 mm Stainless-steel Barrel [mm (in.)] 4.75 (0.19) Sensor case material M18x1 16.1 (0.63) Environmental Operating temperature [C° (F°)] -25…+70 (-13…+158) Operating humidity 5…95% relative Washdown rating IP66, IP67, IP69K Shock and vibration IEC 60068-2-27: 30 g, 11 ms IEC 60068-2-6: 10…55 Hz Pollution degree IEC 60947-1-3 Actuator 13.72 (0.54) Actuator 15.87 (0.62) 36.47 (1.44) 14.5 (0.57) 74.8 (2.95) 48.2 (1.90) Electromagnetic Compatibility (EMC) Electrostatic discharge ESD IEC 61000-4-2: Air discharge Per IEC 61326-1 (functional): 8 kV Per IEC 61000-6-7 (fail-safe): 8 kV IEC 61000-4-2: Contact discharge Per IEC 61326-1 (functional): 4 kV Per IEC 61000-6-7 (fail-safe): 6 kV Radiated EMF immunity IEC 61000-4-3 Per IEC 61326-1 (functional): 10V/m Per IEC 61000-6-7 (fail-safe): 20V/m Electrical fast transient/burst immunity IEC 61000-4-4 Per IEC 61326-1 (functional): 2 kV/5 kHz Per IEC 61000-6-7 (fail-safe): 2 kV/5 kHz Conducted immunity IEC 61000-4-6 Per IEC 61326-1 (functional): 10V Per IEC 61000-6-7 (fail-safe): 20V Sensor M18X1 10.4 (0.41) 44.4 (1.75) S Mode of Operation Figure 3 - Status Indicators 18 mm and 30 mm Actuator Status Indicators Rated impulse withstand voltage IEC 60947-1: 1 kV Protection Short circuit, overload, reverse polarity, overvoltage, loss of ground Status Indicator Physical Characteristics Torque settings, max [N•m (lb•in)] Switch/actuator mounting nut: 2.20 (19.5) 18 mm Plastic Barrel • • • • • 2 18 mm Actuator 18 mm Stainless-steel Barrel Actuator is supplied with the sensor Status indicator green: Door/guard closed, safety outputs active. Status indicator red: Door/guard open, safety outputs off. Status indicator flashes red: Unit failure. See Table 1 on page 3. Status indicator flashes green: Safety inputs off. Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Diagnostics Typical Wiring Table 1 - Signal from Status/Diagnostic Indicator Table 2 - 8-pin Diagram State Status Troubleshooting Off Not powered — Red OSSD not active — 3 8 4 Green OSSD active — 5 Green flash Power up test or OSSD inputs not valid Red flash Check 24V DC or OSSD inputs (yellow or red wire). 0.5 Hz flash OSSD fault OSSD fault: Check that OSSD outputs are not shorted to GND, 24V DC or each other. 2 Hz flash internal fault Cycle power. Installation IMPORTANT Do not over torque the mounting hardware. See Torque settings, max on page 2. 2 1 7 6 Pin Color Signal 1 White Auxiliary Output 2 Brown 24V DC 3 Green — (1) 4 Yellow OSSD 2 Input 5 Gray OSSD 1 Output 6 Pink OSSD 2 Output 7 Blue 0V 8 Red OSSD 1 Input The recommended mating cable is 2 m (6.5 ft) (catalog number 889D-F8AB-2). Replace the 2 with 5 (5 m [16.4 ft]) or 10 (10 m [32.8 ft]) for standard cable lengths. Use nonremovable screws, bolts, or nuts to mount the switch and actuator. Position the switch and actuator so they align with each other. (1) Figure 4 - Minimum Distance Between Sensors [mm (in.)] Shield wire for the stainless-steel version. Table 3 - 5-pin Diagram Stainless-steel Housing 1818mm mmActuator Actuator 2 5 40 (1.57) Sensor1 Sensor 1 Sensor 2 Sensor 2 1 3 Plastic Housing 1818mm mmActuator Actuator 3030mm mmActuator Actuator 40 (1.57) Sensor Sensor1 Sensor Sensor 2 1 2 60 (2.36) Sensor Sensor 2 2 Sensor1 Sensor 1 Color 1 Brown +24V 2 White Safety OSSD 1 Output Signal 3 Blue 0V 4 Black Safety OSSD 2 Output 5 Gray Auxiliary Output The recommended cordset is 2 m (6.5 ft) (catalog number 889D-F5AC-2). Replace the 2 with 5 (5 m [16 ft]) or 10 (10 m [32.8 ft]) for standard cable lengths. . IMPORTANT Figure 5 - Misalignment Curve 4 Pin If you do not require an auxiliary signal, use a 4-pin cordset (catalog number 889D-F4AC-2). The recommended patchcord for use with ArmorBlock® Guard Safety I/O is 2 m (6.5 ft) (catalog number 889D-F4ACDM-2). Replace the 2 with 0M3 (0.3 m [0.98 ft]), 1 (1 m [3.28 ft]), 5 (5 m [16.4 ft]), or 10 (10 m [32.8 ft]) for standard cable lengths. 35 30 25 IMPORTANT Do not use a 5-pin patchcord with the ArmorBlock I/O. 20 15 10 5 0 -40 -30 -20 -10 0 10 20 30 40 18 mm Plastic Barrel with 30 mm Actuator 18 mm Plastic Barrel with 18 mm Actuator 18 mm Stainless Steel Barrel Stainless-steel Barrel with with 18 18 mm mm Actuator Actuator Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 3 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Commission the Unique Coded Actuator Teach the Unique Actuator (one-time learn only; unit locked) Initial Teach of the Actuator Power the Sensor Connect the sensor to 24V DC (see Typical Wiring on page 3). IMPORTANT The unique coded sensor ships from the factory unprogrammed and must be taught a unique coded actuator, see Teach the Actuator. A unique coded sensor can only learn a unique coded actuator and cannot learn a standard coded actuator. A standard coded sensor does not work with a unique coded actuator. The unique coded sensor Status/Diagnostic indicator, flashes green eight times then repeats, which indicates that the sensor has not yet learned an actuator. You can lock the unique coded sensor so it cannot learn another actuator, see Teach the Unique Actuator. The sensor automatically starts the learn process once an actuator enters the sensing range. Table 5 - Learn Sequence Step Description 1 Target present Status/Diagnostic indicator flashes green 2 Hz rate (15 s) 2 Verifying actuator Status/Diagnostic indicator flashes green/red 1 Hz rate (15 s) 3 Program sensor Status/Diagnostic indicator flashes green/red 2 Hz rate (15 s) 4 Program locking Status/Diagnostic indicator flashes green 2 Hz rate (number of learns remaining) (15 s) 5 Remove the actuator from the sensing field Status/Diagnostic indicator changes to steady red 6 Replace the actuator back into the sensing field Status/Diagnostic indicator flashes green 2 Hz rate (number of learns that remain), this action triggers the lock function. Teach the Actuator 7 Ready state Status/Diagnostic indicator shows steady green (ability to learn an additional actuator) 8 Learn is complete Sensor is locked and cannot learn another actuator. Quick Start 1. 2. 3. Power up the sensor and bring an actuator into the sensing range. Leave the actuator in the sensing field for a minimum of 2 minutes. The learn process is complete. IMPORTANT The sensor can learn a new actuator up to eight times. The Status/Diagnostic indicator flashes the number of actuators left that a sensor can learn. Learn a New Unique Coded Actuator • • • • Ability to Learn an Additional Actuator To learn a replacement actuator, bring the actuator to be taught into the sensing range of the safety switch. The learn sequence is the same as the sequence for Teach the Actuator. A sensor cannot relearn a previously learned actuator or a standard SensaGuard™ actuator. The sensor only recognizes the most recently learned actuator. The sensor automatically starts the learn process once an actuator enters the sensing range. Unique Coded Diagnostic Table 4 - Learn Sequence Error codes for learn process. Cycle power to clear the fault. Step Table 6 - Signal from Status/Diagnostic Indicator Description 1 Target present Status/Diagnostic indicator flashes green 2 Hz rate (15 s) 2 Verifying actuator Status/Diagnostic indicator flashes green/red 1 Hz rate (15 s) 3 Program sensor Status/Diagnostic indicator flashes green/red 2 Hz rate (15 s) 4 Program complete Status/Diagnostic indicator flashes green 2 Hz rate (number of learns that remain) (15 s) 5 Ready state Status/Diagnostic indicator shows steady green 6 Learn is complete - 4 Flashes (2 Hz) Error Code Green OSSD inputs not valid. Red-red-red-green Cannot learn a standard SensaGuard actuator. Red-red-red-green-green Actuator already learned. Red-red-red-green-green-green Bad RFID. Target moved out of range. Red-red-red-green-green-green-green Exceeded learning eight actuators. Red-red-red-green-green-green-greengreen Unit locked. Cannot learn another actuator. Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions OSSD Test Pulses Individual Pulses Test pulses appear on each OSSD output. These pulses are approximately every 45 ms. The times that are shown are approximate and depend on the processing of the safety-related status. 0 450 Time (µs) Periodicity Pink Wire Gray Wire 0 20 45 Time (ms) Timing Diagram +24V DC SensaGuard Actuator SensaGuard Actuator SensaGuard Actuator SensaGuard Sensor Unit 1 SensaGuard Sensor Unit 2 SensaGuard Sensor Unit 3 S11 S12 S52 A1 Brown Pink Gray Red Yellow Blue Brown Pink Gray Red Yellow Blue Brown Red Yellow Pink Gray Blue 13 23 33 41 MSR127TP 440R-N23132 S21 S22 A2 S34 14 24 34 42 24V Common Response Time: Safety outputs turn off. Initial conditions: All actuators are in sensing distance. Actuator 1 moves out of sensing range. 00ms ms Sensor 1 OSSD outputs (gray and pink) Sensor 2 OSSD outputs (gray and pink) turn off. Sensor 1 status indicator turns turn off. Sensor 2 status indicator steady red. flashes green. 45 ms 45ms Sensor 3 OSSD outputs (gray and pink) turn off. Sensor 3 status indicator flashes green. 50 50ms ms 55 55 ms ms Response Time: Safety outputs turn on Initial conditions: Actuator 1 is out of sensing range. Sensor 1 status indicator is steady red. Actuators 2 and 3 are in sensing range. Sensor 2 and 3 status indicators flash green. Actuator 1 moves into sensing range. Sensor 2 OSSD inputs (red and yellow) transition to 24V DC from Sensor 1 OSSD outputs. Sensor 1 status indicator turns steady green. Sensor 3 OSSD inputs (red and yellow) transition to 24V DC from Sensor 2 OSSD outputs. Sensor 2 status indicator turns steady green. 00 ms ms 360 360 ms ms 378 ms ms 378 Sensor 3 OSSD outputs (gray and pink) are energized. Sensor 3 status indicator turns steady green. Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 396 396 ms ms 5 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Troubleshooting Figure 6 - Series Circuit OV DC +24V DC Power Supply Actuator 1 Actuator 2 Actuator 3 Actuator 4 Actuator 5 Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 1606-XL120D Power Supply OSSDs energize to 24V. Green status indicator is on. OSSDs energize to 24V. Green status indicator is on. Wh ite e Wh it Actuator 3 is in sensing range. Switch 3 has a fault. See Table 1 on page 3. +0V +0V Blu e Pink Gray Brown Red Yellow Actuator 2 is in sensing range. Switch 2 functions properly. +24V +24V Bl u e Pink Gray Brown Red Yellow Actuator 1 is in sensing range. Switch 1 functions properly. e Pink Gray Brown Red Yellow Pink Gray Brown Red Yellow Pink Gray Brown Red Yellow White +24V +24V Blu Wh ite Blu e Wh ite Bl u e +0V +0V Actuator 4 is in sensing range. Switch 4 functions properly. Actuator 5 is in the sensing range. Switch 5 is functioning properly. OSSD inputs are 0V. OSSDs de-energize to 0V. Green status indicator flashes to indicate that OSSD inputs are not 24V. OSSD inputs are 0V. OSSDs de-energize to 0V. Green status indicator flashes to indicate that OSSD inputs are not 24V. Application Wiring Examples Figure 7 - Wiring to MSR127 Safety Relay Driving 100S or 700S Safety Relays +24V DC Sensor Actuator +24V DC Sensor Actuator SensaGuard Sensor Unit 1 SensaGuard Sensor Unit 1 S11 S12 S52 A1 K1 13 Brown Red Yellow 23 33 41 Pink Gray Blue 13 Brown Red Yellow Pink Gray Blue S11 S12 S52 A1 23 33 41 K1 K2 MSR127RP 440R-N231xx S22 S21 A2 S34 14 K2 MSR127TP 440R-N231xx S22 S21 A2 S34 14 Reset 24 34 42 K1 K2 24V Ground One Sensor, Monitored Manual Reset +24V DC Sensor Actuator K1 K2 24V Ground One Sensor, Automatic Reset +24V DC Sensor Actuator Sensor Actuator SensaGuard Sensor Unit 1 24 34 42 Sensor Actuator SensaGuard Sensor Unit 1 SensaGuard Sensor Unit 2 SensaGuard Sensor Unit 2 Brown Red Yellow Pink Gray Blue Brown Red Yellow Pink Gray Blue Brown Red Yellow Pink Gray Blue Brown Red Yellow Pink Gray Blue 440L GuardShield™ Receiver Transmitter Brown Brown 1 2 Pink 6 Gray 5 Blue 7 Green 3 Blue 3 S11 S12 S52 A1 13 23 33 41 S11 S12 S52 A1 K1 13 23 33 41 K2 MSR127RP 440R-N231xx S22 S21 A2 S34 14 K2 MSR127RP 440R-N231xx S22 S21 A2 S34 14 Reset 24 34 42 K1 K2 24V Ground Two Sensors in Series, Monitored Manual Reset Reset 24 34 42 K1 K2 24V Ground Two Sensors and One 440L Safety Light Curtain in Series, Monitored Manual Reset IMPORTANT 6 K1 The safety light curtain must be last (farthest from the safety relay). Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 +0V +0V OSSDs are off. SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Figure 8 - Guardmaster SI or DI Safety Relay Wiring Brown +24V DC Black K2 Gate Open Reset Black White 889D-F5AC-5 Cordset Blue Gray Brown 889D-F5AC-5 Cordset White Blue Gray K1 S32 S42 S22 S12 A1 Logic 0 1 2 3 8 DI 4 7 440R-D22R2 6 5 13 23 S11 14 24 Y32 S21 L11 L12 A2 Gate Open S34 K1 K2 24V Ground White Black K1 Gray 889D-F5AC-5 Cordset Blue Brown +24V DC K2 Reset S11 S21 S22 S12 A1 Reset 13 23 S34 A2 14 24 Y32 0 AM SI 440R-S12R2 L11 24V Ground Gate Open MM K1 K2 Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 7 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Figure 9 - Guardmaster SI or DI Safety Relay Wiring Pink Pink Gray Not Connected Red Yellow K1 K2 Blue 889D-F8AB-x Cordset White Green Brown 889D-F8AB-x Cordset Yellow Gray Red Green White Blue Brown +24V DC Reset S12 S22 S32 S42 A1 13 23 S34 7 6 5 4 440R-D22R2 S11 S21 L11 L12 A2 14 24 Y32 0 Logic 8 DI 1 2 3 Gate Open Gate Open K2 K1 24V Ground IMPORTANT The green wire connects to the housing of the stainless-steel SensaGuard sensor only; it has no connection for the plastic SensaGuard sensor. +24V DC Not Connected Pink Gray Red Yellow K2 Blue 889D-F8AB-x Cordset White Green Brown K1 Reset S11 S21 S22 S12 A1 Reset 13 23 S34 A2 14 24 Y32 0 AM SI 440R-S12R2 L11 MM Gate Open 24V Ground 8 Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 K1 K2 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Figure 10 - CR30 Software Configurable Relay Wiring +24V DC Gray Pink K2 Black Safety Reset White 889D-F5AC-5 Cordset Gray Blue Brown 889D-F8AB-5 Cordset Not Green Brown Connected White Red Blue Yellow K1 00 01 02 03 04 05 06 07 08 09 10 11 CR30 440C-CR30-22BBB A1 A2 12 13 14 15 16 17 18 19 20 21 Gate Open Gate Open 100S Safety Contactor or 700S/700HPS Safety Relays K1 K2 24V Ground Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 9 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Figure 11 - 1734 POINT Guard I/O Wiring +24V DC Gray White Black Brown Safety Reset 0 1 I0 I1 I4 I5 O0 O1 O4 O5 2 3 I2 I3 I6 I7 O2 O3 O6 O7 4 5 COM COM COM COM COM COM COM COM 6 7 T0 T1 T2 T3M COM COM COM COM Gray Blue 889D-F5AC-5 Patchcord K2 Pink 889D-F8AB-5 Cordset Not Green Brown Connected White Red Blue Yellow K1 EtherNet/IP™ 1734-AENT Gate Open Gate Open 1734-IB8S 100S Safety Contactor or 700S/700HPS Safety Relays K1 K2 100S Safety Contactor or 700S/700HPS Safety Relays 24V Ground Set On -> Off Input Delay Time to 6 ms to ignore the SensaGuard OSSD output test pulses. 10 1734-OB8S Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 SensaGuard 18 mm Cylindrical Barrels (Series B Models Only) Installation Instructions Figure 12 - 1732DS/ES ArmorBlock Guard Safety I/O Wiring 1732ES-IB12XOB4 Ethernet Cat. No. 871A-TS5-DM1 5-pin Field Attachable Connector 2 3 5 1 2 4 3 Gray Blue Pink White 889D-F8AB-5 Cordset Green Brown Red Yellow X100 Power Not Connected X10 1 T1 5 T0 1 T1 2 I1 F 3C 4 I0 5 T0 1 T1 2 I1 3C C 4 I0 5 T0 1+24 2 O1 G 3C 4 O0 5C 1 T1 2 I1 3C D 4 I0 5 T0 1+24 100S Safety Contactor or 700S/700HPS Safety Relays 2 O1 3 C H 4 O0 5C 3C B K2 871A-TS5-DM1 Safety Reset 4 X1 1 T1 2 I1 E 3C 4 I0 5 T0 OSSD 4 I0 K1 1 1 T1 2 I1 3C A 4 I0 5 T0 OSSD 2 I1 Ground 889D-F4UCDM-5 Patchcord 5 Power 24V Ground 4 1 3 2 1 2 871A-TS5-DM1 K2 K1 4 3 +24V DC Figure 13 - Input and Output Configuration for the 1732ES Module Recommended Safety Control Interfaces • • • • • • Guardmaster® safety relays: - Dual-input (DI) - Dual-input solid-state output (DIS) - Single input (SI) - CR30 software configurable Minotaur™ safety relays: - MSR126 - MSR127 - MSR131 - MSR138 SmartGuard™ controller 1791DS/ES CompactBlock™ Guard I/O™ module 1732DS/ES ArmorBlock Guard I/O module 1734 POINT Guard I/O™ module Maintenance Monthly: Check the correct operation of the switching circuit. Also check for signs of abuse or alterations. Inspect the switch casing for damage. Repair If there is any malfunction or damage, do not repair. Replace the unit before you allow machine operation. Rockwell Automation Publication 440N-IN017C-EN-P - May 2023 11 Declaration of Conformity CE Conformity Additional Resources To download publications, visit rok.auto/literature and search for the following publication numbers. Resource Rockwell Automation declares that the products that are shown in this document conform with the 2014/30/EU Electromagnetic Compatibility Directive (EMC) and 2006/42/EC Machinery Directive (MD) and that the respective standards and/or technical specifications have been applied. Description Industrial Automation Wiring and Grounding Provides general guidelines for installing a Rockwell Automation® industrial system. Guidelines, publication 1770-4.1 Product Certifications website, rok.auto/ certifications Provides declarations of conformity, certificates, and other certification details. For a comprehensive CE certificate visit: rok.auto/certifications UKCA Conformity Rockwell Automation declares that the products that are shown in this document are in compliance with 2016 No. 1091 Electromagnetic Compatibility Regulations and 2008 No. 1597 Supply of Machinery (Safety) Regulations and that the respective standards and/or technical specifications have been applied. For a comprehensive UKCA certificate visit: visit: rok.auto/certifications Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. For technical support, visit rok.auto/support. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Allen-Bradley, ArmorBlock, CompactBlock, expanding human possibility, Guard I/O, Guardmaster, GuardShield, Minotaur, POINT Guard I/O, Rockwell Automation, SensaGuard, and SmartGuard are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 440N-IN017C-EN-P - May 2023 | Supersedes Publication 440N-IN017B-EN-P - April 2019 Copyright © 2023 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.