ELECTRICAL ITEC Guide to Controls 01 – December 05 WORK PART 1 Guide to Control Panel Cable Identification TECHNOLOGY MAKING The IEE consider a possible identification scheme for panel conductors as follows: Neutral or mid-point conductor Where a circuit includes a neutral or mid-point conductor identified by colour, the colour used shall be blue. Protective conductor The bi-colour combination green-and-yellow shall be used exclusively for identification of a protective conductor and this combination shall not be used for any other purpose. Single core cables that are coloured green-and-yellow throughout their length shall only be used as a protective conductor and shall not be over-marked at their terminations, except as permitted by Regulation 514-04-03. In this combination one of the colours shall cover at least 30% and at most 70% of the surface being covered, while the other colour shall cover the remained of the surface. A bare conductor or busbar used as a protective conductor shall be identified, where necessary, by equal green-and-yellow stripes, each not less than 15 mm and not more than 100 mm wide, close together, either throughout the length of the conductor or in each compartment and unit and at each accessible position. If adhesive tape is used, it shall be bi-coloured. PEN conductor A PEN conductor shall, when insulated, be marked by one of the following methods: (i) Green-and-yellow throughout its length with, in addition, blue markings at the terminations, or (ii) Blue throughout its length with, in addition, green-and-yellow markings at the terminations. Other conductors Other conductors shall be identified by colour in accordance with Table 51. The single green colour shall not be used. Bare conductors A bare conductor shall be identified, where necessary, by the application of tape, sleeve or disc of the appropriate colour prescribed in Table 51 or by painting with such a colour. Identification of conductors by letters and/or numbers The lettering or numbering system applies to identification of individual conductors and of conductors in a group. The identification shall be clearly legible and durable. All numerals shall be in strong contrast to the colour of the insulation. The identification shall be given in letters or Arabic numerals. In order to avoid confusion, unattached numerals 6 and 9 shall be underlined. Protective conductor Conductors with green-and-yellow colour identification shall not be numbered other than for the purpose of circuit identification. 1 Alphanumeric identification of cables The preferred alphanumeric system is described in table 51. Numeric Conductors may be identified by numbers, the number 0 being reserved for the neutral or mid-point conductor. Omissions of identification by colour or marking Identification by colour or marking is not required for: (i) (ii) (iii) (iv) (v) Concentric conductors of cables Metal sheath or armour of cables when used as a protective conductor Bare conductors where permanent identification is no practicable Extraneous-conductive-parts used as a protective conductor Exposed-conductive-parts used as a protective conductor. Identification of conductors Function Alphanumeric Colour Green-and-yellow Cream Protective conductors Functional earthing conductor ..a.c. power circuit (1) Phase of single-phase circuit Neutral of single-or three-phase circuit Phase 1 of a three-phase a.c. circuit Phase 2 of a three-phase a.c. circuit Phase 3 of a three-phase a.c. circuit L N L1 L2 L3 Brown Blue Brown Black Grey Two-wire unearthed d.c. power circuit Positive of two-wire circuit Negative of two-wire circuit L+ L- Brown Grey Two-wire earthed d.c. power circuit Positive (of negative earthed) circuit Negative (of negative earthed) circuit(2) L+ M Brown Blue Positive (of positive earthed) circuit(2) Negative (of positive earthed) circuit M L- Blue Grey L+ Brown LL+ M L- Grey Brown Blue Grey Control circuits, ELV and other applications Phase conductor L Neutral or mid-wire(4) N or M Brown, Black, Red, Orange, Yellow, Violet, Grey, White, Pink or Turquoise Blue Three-wire d.c. power circuit Outer positive of two-wire circuit derived from three-wire system Outer negative of two-wire circuit derived from three-wire system Positive of three-wire circuit Mid-wire of three-wire circuit(2)(3) Negative of three-wire circuit 2 NOTES: (1) (2) (3) (4) Power circuits include lighting circuits. M identifies either the mid-wire of a three-wire d.c. circuit, or the earthed conductor of a two-wire earthed d.c. circuit Only the middle wire of three-wire circuits may be earthed An earthed PELV conductor is blue BS EN 60204-1 Provides the following suggestion for the identification of conductors General requirements Conductors shall be identifiable at each termination in accordance with the technical documentation (see clause 18). Annex B question 31 may be used for an agreement between supplier and user regarding a preferred method of identification. Where colour coding is used for identification of conductors, the following colours may be used: BLACK, BROWN, RED, ORANGE, YELLOW, GREEN, BLUE (including LIGHT BLUE), VIOLET, GREY, WHITE, PINK, TURQUOISE NOTE – This list of colours is derived from IEC 60757 It is recommended that, where colour is used for identification, the colour be used throughout the length of the conductor either by the colour of the insulation or by colour markers. An acceptable alternative may consist of additional identification at selected locations. For safety reasons, the colour GREEN or the colour YELLOW should not be used where there is a possibility of confusion with the bicolour combination GREEN-AND-YELLOW (see 14.2.2). Colour identification using combinations of those colours listed above may be used provided there can be no confusion and that GREEN and YELLOW is not used except in the bicolour combination GREEN-ANDYELLOW. Identification of the protective conductors The protective conductor shall be readily distinguishable by shape, location, marking or colour. When identification is by colour alone, the bicolour combination GREEN-AND-YELLOW shall be used throughout the length of the conductor. This colour identification is strictly reserved for the protective conductor. For insulated conductors, the bicolour combination GREEN-AND-YELLOW shall be such that on any 15 mm length one of the colours covers at least 30% and not more than 70% of the surface of the conductor, the other colour covering the remainder of the surface. Where the protective conductor can easily be identified by its shape, position or construction (e.g. a braided conductor), or where the insulated conductor is not readily accessible, colour coding throughout its length is not necessary but the ends or accessible positions shall be identified by the graphical symbol 417-IEC-5019 or by the bicolour combination GREEN-AND-YELLOW. Identification of the neutral conductors Where a circuit includes a neutral conductor identified by colour, the colour shall be LIGHT BLUE (see 3.1.2 of IEC 60446). LIGHT BLUE shall not be used for identifying any other conductor where confusion is possible. Where identification colour is used, bare conductors used as neutral conductors shall be wither coloured by a LIGHT BLUE stripe, 15 mm to 100 mm wide in each compartment or unit or at each accessible position, or coloured LIGHT BLUE throughout their length. Identification of other conductors Identification of other conductors shall be by colour (either solid or with one or more stripes), number, alphanumeric, or a combination of colour and numbers or alphanumeric. When numbers are used, they shall be Arabic; letters shall be Roman (either upper or lower case). 3 It is recommended that insulated conductors be colour-coded as follows: - BLACK: a.c. and d.c. power circuits; - RED: a.c. control circuits; - BLUE: d.c. control circuits; - ORANGE: interlock control circuits supplied from an external power source. Exceptions: to the above are permitted where: - Individual devices are purchased complete with internal wiring; - Insulation is used that is not available in the colours required; or - Multicolour cable is used, but not the bicolour combination GREEN-AND-YELLOW. The British Standard 6231 specifies requirements for single-core non-sheathed cables, including flexible cables, used for the wiring of switch, control metering, relay and instrument panels of power switchgear, and for such purposes as internal connections in rectifier equipment and in motor starters and controllers. The standard gives suggestions for cable collars as follows: Type Form of Conductor Designated temperature Rated voltage AU Rigid, round, solid 700C 60 V AK BR BU BK CR CU CK 0 60 V 0 600/1 000 V 0 600/1 000 V 0 600/1 000 V 0 600/1 000 V 0 600/1 000 V 0 600/1 000 V 70 C Flexible Rigid, round, stranded 70 C 70 C Rigid, round, solid 70 C Flexible Rigid, round, stranded 90 C 90 C Rigid, round, solid 90 C Flexible Types AU and AK PVC-insulated cables Tinned annealed copper conductor Type AK 0.75 mm2 only: All other cables: PVC insulation type TI 1; PVC insulation type 2 Colours Single colours Black, blue, brown, cream, green, grey, orange, pink, red, turquoise, violet, white, yellow Bi-colours Brown/blue, Green/black, green/blue, green/brown, green/red, grey/blue, grey/brown, grey/green, grey/orange, grey/red, orange/black, orange/blue, orange/brown, orange/green, orange/red, red/black, red/blue, red/brown, white/black, white/blue, white/brown, white/green, white/grey, white/orange, white/red, white/violet, white/yellow, yellow/green, yellow/violet Types BU and BR PVC-insulated rigid cables Plain annealed copper conductor PVC insulation type TI 1 4 Colours Single colours Black, blue, brown, grey, red, white, yellow Bi-colour Green/yellow (for earthing or similar protection, see 6.3) Type BK PVC-insulated flexible cables Tinned or plain annealed copper conductor PVC insulated type TI 1 Colours Single colours Black, blue, brown, grey, red, white, yellow Bi-colour Green/yellow (for earthing or similar protection, see 6.3) Type CK PVC-insulated flexible cables Tinned or plain annealed copper conductor PVC insulation type TI 3 Colours Single colours Black, blue, brown, grey, red, white, yellow, orange, pink, violet, turquoise, green and cream Bi-colour Green/yellow (for earthing or similar protection, see 6.3) Types CU and CR PVC-insulated rigid cables Plain annealed copper conductor PVC insulation type TI 3 Single colours Black, blue, brown, grey, red, white, yellow, orange, pink, violet, turquoise, green and cream Bi-colour Green/yellow (for earthing or similar protection, see 6.3) BS EN/IEC 60439-1 gives the following guidance on cable colours Identification of the protective conductor (PE, PEN) and of the neutral conductor (N) of the main circuits The protective conductor shall be readily distinguishable by shape, location, marking or colour. If identification by colour is used, it must be green and yellow (twin-coloured). When the protective conductor is an insulated single-core cable, this colour identification shall be used, preferably throughout the whole length. NOTE: The green/yellow colour identification is strictly reserved for the protective conductor. Any neutral conductor of the main circuit should be readily distinguishable by shape, location, marking or colour. If identification by colour is used, it is recommended to select a light blue colour. The terminals for external protective conductors shall be marked according to IEC 60445. As an example see graphical symbol No. 5019 of IEC 60417. This symbol is not required where the external protective 5 conductor is intended to be connected to an internal protective conductor which is clearly identified with the colours green/yellow. Identification of the conductors of main and auxiliary circuits With the exception of the cases mentioned in 7.6.5.2, the method and the extent of the identification of conductors, for example by arrangement, colours or symbols, on the terminals to which they are connected or on the end(s) of the conductors themselves, is the responsibility of the manufacturer and shall be in agreement with the indications on the wiring diagrams and drawings. Where appropriate, the identification according to IEC 60445 and IEC 60446 shall be applied. While every care has been taken to ensure the accuracy of the information contained in this leaflet, neither the authors nor the publishers can accept liability for any inaccuracies in or omissions from the information provided or any loss or damage arising from or related to its use. 6