Absorption Chiller Matrial for Service Course (Installation, Operation, Maintenance) Model : TSA-16NK Series Contents Page Safety precautions Section 1 How does the absorption chiller works? 1-1 Why does a machine chill by giving heat? 1-2 What is latent heat ? 1-3 Principal of absorption chiller 1-4 Principal of single effect type 1-5 Principal of double effect type 1-6 Function of each section & Flow diagrams 1-7 Typical cooling cycle on Duhring diagram 1-8 Heat Balance & COP in cooling mode Section 2 Illustration of Chiller 2-2 Control panel 2-3 Sensors 2-4 Principal of purging 2-5 Internal structure 2-6 Symbol list Overview of Installation & Start-up of Chiller 3-2 Check list 3-3 Reference (1) Typical piping diagram (2) Field electric wiring diagram (3) Confirmation of inside pressure of chiller (4) Detail of interlick (5) Aging and tube surface cleaning 36 38 56 57 60 61 62 Control 4-1 Over view of control functions 4-2 Operation sequence 4-3 Capacity control & other control functions 4-4 Predication functions (Maintenance message) 4-5 Safet shut-down time chart Section 5 17 20 25 28 30 33 Installation & Start-up of Chiller 3-1 Section 4 3 4 4 5 7 10 15 16 Illustration of Chiller & Control panel 2-1 Section 3 1 63 66 69 74 77 Trouble Shooting 5-1 Chilled water outlet temp. does not go down in cooling mode 5-2 Trouble shooting at alarm in cooling mode 87 88 814-6-0510-005-00-0 Contents Page Section 6 Parts replacement & Instructions 6-1 Guidance interval of parts replacement 6-2 How to change parts 6-3 Method of absorbent solution (LiBr) analyses 6-4 Method of adjusting inhibitor content and alkalinity 6-5 Method of charging solution 6-6 How to perform de-crystallization 6-7 Reference material of tube cleaning 6-8 Solution and refrigerant sampling 6-9 Measuring concentration 6-10 Method of charging Nitrogen gas 6-11 Method of discharging Nitrogen gas 6-12 Information of signals between Chiller/Heater & Weishaupt burner 6-13 Instruction of Leak test 6-14 Instruction of inspection of purge pump 6-15 Instruction of bubble test 6-16 Instruction of refrigerant blow down 6-17 Instruction of field insulation 6-18 Instruction of function test 6-19 Instruction of set & confirmation of controls & safeties 6-20 Set of solution dampers 6-21 Scrapping 6-22 Flow switch 6-23 T.R.G. meter 6-24 How to check temperature sensors Section 7 99 100 106 109 114 115 118 123 125 127 128 128 129 131 132 134 134 135 138 169 170 171 174 175 Seasonal inspection & operation with daily maintenance 7-1 Begining cooling season 7-2 Mid cooling season 7-3 End of cooling season 7-4 Operation of Chiller 7-5 Purging procedure 7-6 Daily maintenance 7-7 Procedure for a long term shut-down 177 179 181 182 184 185 186 814-6-0510-005-00-0 Safety Precautions Please follow the safety precautions in this manual to ensure safe installation, commission, operation and servicing. WARNING Before installation and commissioning, please confirm actual operating condition of the driving heat source, the power supply and the maximum working pressures of water systems, etc., as compared with the contract specifications of Chiller to avoid unexpected problems and/or accident. Authorized personnel only can conduct installation work and relocation work including slinging work, sliding work to avoid any accidents and/or failure of Chiller. Authorized personnel only can replace any parts including electric parts in a control panels provided on Chiller and conduct any re-adjustment of a burner and Chiller to avoid any accidents and/or failure of Chiller. Overhaul of Chiller shall be conducted by authorized personnel only to avoid any accident and/or failure of Chiller due to incomplete overhaul. Authorized personnel only can conduct scrapping Chiller to avoid any accidents and/or to protect any influences to an environment. A notice, "FOR AUTHORIZED PERSONNEL ONLY" must be affixed to a door or a wall of machine room in order that any unauthorized personnel does not enter into the machine room. 1 CAUTION 1. Always turn off breakers before cleaning and checking a cooling tower including its fan, chilled/hot water pump, cooling water pump and others facilities linking with Chiller to protect from electric shocks and/or possible injury due to moving parts such as cooling tower fan. 2. Be sure to stop immediately Chiller in case of a fire, earthquake or thunderbolt to prevent an accident. 3. Do not touch switches and keys in/on control panels mounted on Chiller with wet hands to avoid electric shocks. 4. Do not touch wirings and any other electric devices in control panels on chiller with hands directly to avoid electric shocks. Especially, high voltage wirings. 5. Be sure to ventilate a machine room sufficiently to an avoid oxygen deficiency accident. 6. Do not place any flammables such as gasoline, thinner, etc. near chiller, a flue, a chimney and/or an oil tank to prevent a fire. 7. Do not touch and/or re-adjust a burner to prevent a fire and/or an oxygen deficiency accident caused by abnormal combustion. Maintenance and re-adjustment of the burner shall be conducted by authorized personnel. 8. To prevent a fire, do not operate chiller and turn on/off any switches if gas smell is being in a machine room. 9. To prevent an oxygen deficiency accident and/or abnormal combustion, be sure to inspect a flue and a chimney periodically whether there are any exhaust gas leakages and/or accumulating carbon or not. 10. Do not touch a V-belt of purge pump directly while the purge pump is running to avoid possible injury. 11. Do not climb up chiller to avoid falling down. 12. A control panels, electric wirings/piping and electric parts provided on chiller shall be protected from wet to avoid a fire, electric shocks and/or failure of chiller. 13. Be sure to stop chiller if an abnormal combustion such as black smoke is observed to prevent a fire and/or an accident. And call your service agent as soon as possible. 14. Solve all causes before restarting chiller when alarm happens. If a cause(s) is not removed, chiller can not be restarted. 15. Do not place heavy objects on chiller or a control panel to avoid possible an injury by its falling. 16. Do not change all set values of controls and safety devices except for the chilled or hot water outlet temperature setting to protect abnormal operation condition, unexpected accident, a faire and/or failure of chiller. 17. Do not touch the absorbent solution directly to prevent from skin diseases. And do not spill the absorbent solution to prevent from corrosion of metals. 18. Do not touch high temperature portions directly to prevent from burns. Caution levels are attached with high temperature portions. 19. Stop a purge pump at purge pump replacement to prevent from possible injury by a Vbelt rotating. 2 Section 1 How does the absorption chiller works? 1-1. Cooling : Why does a heating chill ? The cooling means keeping temperature in a room lower than outside temperature, As shown in Fig. 1-1, operation to carry the heat from the room with a lower temperature (ex.28 deg.C : 82.4 deg.F) to the open air with a higher temperature is required. But, in the natural world, the heat can not move from a low temperature side to a high temperature side. So, to transmit the heat as opposed to this principle, some method is necessary. That is, a heat pump (chiller) is used to pump up the heat from a low temperature one as if a water pump is used to draw a water from a deep well. Outside 32deg.C (90 deg.F) To the atmosphere 28deg.C 82 deg.F Chiller 7 deg.C (45 deg.F) Cooling tower 12 deg.C (54 deg.F) 32 deg.C (90 deg.F) Open air Cooling load 28 deg.C 32 deg.C (82 deg.F) (90 deg.F) Heat flow Fig. 1-1 Heat flow Air conditioner The typical chiller using electricity as a operation power source as a conveyer to carry the heat shown in Fig. 1-2 Lower temp. side (Cooling) Higher temp. side is an centrifugal chiller and the typical chiller using a heat Indoor energy is an absorption chiller/heater. Chilled water is made Grain of heat by using the latent heat released by a liquid as it evaporates. Outdoor Energy We can experience this principle on our daily life. For example, when having an injection, after applying alcohol on the arm, we feel this part cool. Because, applied alcohol Fig. 1-2 Heat flow at cooling took the heat from the arm when it is warmed by the body heat and evaporated. Another example is that we feel cool when sweating on a hot day or by taking exercise. Because, the body heat is cooled by the evaporation of sweat which takes the heat from the body. These chillers also use the latent heat of evaporation. But, reuse of evaporated vapor by returning to liquid is required. For this purpose, the compressor is used in a centrifugal chiller, and an absorbent is chemically used in an absorption chiller. The absorbent loses the effect. Because its concentration is diluted due to absorbing the vapor. To recover the absorbing effect, a concentrating process of absorbent by heating is needed. 3 1-2. What is latent heat ? When water is heated, the temperature rises and stops at 100 deg.C (212 deg.F). With the temperature remaining constant at 100 deg.C (212 deg.F), the water continues to evaporates as long as it is being heated. Once water reaches 100 deg.C (212 deg.F), all additional heat goes into changing it from liquid to vapor. At 100 deg.C (212 deg.F), since vapor is lighter than the surrounding air, it rises. In this case, as water changes from a liquid to a gas, the applied heat does not change the temperature but changes the state of water. Therefore the heat is said to be hidden, or latent. Thus latent heat refers to the energy absorbed by a liquid as it changes state, i.e., to a gas, without changing it's actual temperature. Sensible heat refers to heat which only results in temperature change rather than change of state. 1-3. Principal elements of absorption chiller/heater in cooling mode There are following 3 elements on the principal of the absorption chiller/heater. a. The inside of chiller/heater is vacuum condition. b. Water (H2O) is used as refrigerant ( Minimum chilled water outlet temp. is 5 deg.C=41 deg.F) c. Lithium Bromide (LiBr) water solution that has character to absorb water vapor is used as absorbent. The following descriptions are detail explanations of each elements (1) Vacuum & water The earth we live is pressed by the weight of the air of approximate 10 km (6 miles) which is surrounding the earth and this pressure is called as the atmospheric pressure. The pressure lesser than this pressure is called as the vacuum. When explaining the vacuum for the absorption chiller/heater, it is needed to know the relation between the pressure and the evaporation temperature of water. It is experienced in a daily life that the water is boiled (evaporated) at 100 deg.C (212 deg.F) in the atmospheric pressure. When pressure is higher than the atmospheric pressure, boiling temperature is higher than 100 deg.C (212 deg.F). And if the pressure is lower(vacuum), the boiling temperature is lower than 100 deg.C (212deg.F). The pressure higher than the atmospheric pressure can be experienced with a boiler. The pressure lower than the atmospheric pressure can be experienced during claming a mountain. Namely, in the mountain, as the air layer becomes weak by its height, the pressure to be applied becomes low. For this reason, the water boils at a temperature lower than 100 deg.C (212 deg.F) at the mountain. In other words, evaporation temperature of the water is depended on pressure. The inside of a chiller/heater is always kept in high vacuum. In this condition, the water evaporates at very low temperature. For example, at 0.5 kPa absolute, water evaporates at 5 deg.C (41 deg.F). (2) Lithium Bromide (LiBr) Lithium Bromide is medicine which is made from the lithium obtained from lithium ore and the bromide obtained from the sea water. This medicine is not familiar to us. But we can guess easily Lithium Bromide. That is, we usually see the salt. The another name of salt is Sodium Chloride. They are of the same elements, that is Lithium (Li) and Sodium (Na) are alkali while Bromide (Br) and Chlorine (Cl) are halogen. LiBr and NaCl are chemical materials in the same chemical group and have very similar characteristics. Especially, the both materials has the characteristic to absorb moisture (water vapor). This characteristics to absorb moisture of LiBr is stronger than NaCl. The absorption chiller uses the characteristic. The higher its concentration and lower its temperature of LiBr water solution are, the stronger the characteristic (absorption power) is. 4 1-4. Principal of single effect type water (refrigerant Closed vessel (1) Heat exchanger tubes are installed inside a closed vessel. The vessel is then evacuated to a pressure of about 0.8 kPA Vacuum (0.12 psi) absolute. Drops of water (refrigerant) are allowed toChilled water fall on the heat exchanger tubes. Water circulating heat exchanger Fig. 1-3 Evaporating process (2) Now the vessel has a vacuum of 0.8 kPa (0.12 psi) absolute. Concentrated LiBr solution Drops of refrigerant water falling on the exchanger tubes refrigerant evaporate at 5 deg.C (41 deg.F) as they remove heat from the water in the tube. Thus chilled, the water in the heat exchanger tubes can be used for cooling. Then drops of concentrated lithium bromide (LiBr) solution are allowed to Cooling water Chilled water Absorbing process fall into the vessel. The LiBr solution absorbs vaporized refrigerant. Vaporized refrigerant Fig. 1-4 Absorbing process Refrigerant vapor (3) When the LiBr solution once absorbs the vaporized refrigerant, it is diluted and loses its ability to absorb. Concentrated LiBr solution This means that concentrated LiBr solution must be fed in continuously. At this stage, the diluted solution Driving heat source refrigerant is heated by driving heat source. The heat causes the solution to release the absorbed refrigerant and Cooling water Chilled water also re-concentrates the solution. Diluted LiBr solution Abs. Fig. 1-5 Concentrating process (4) The refrigerant vapor which is released from the solution when heated, is cooled in a separate chamber (condenser) to Generator Liquid refrigerant Condenser Cooling water Driving heat source Concentrated LiBr solution become liquid refrigerant. Drops of this water are again introduce Evaporator into the vacuum vessel and recycled. Chilled water Cooling water Absorber Abs. Fig. 1-6 Condensing process 5 (5) This is the basic operational cycle of Condenser Generator the single effect type absorption chiller. Cooling water flows thru an absorber and a condenser. The cooling water Cooling water Driving heat source in the condenser cools the refrigerant vapor from the generator back into refrigerant. The cooling water in the Chilled water absorber absorbs the heat released Cooling water by the vaporized refrigerant as it is Abs. pump absorbed by the LiBr solution. Evaporator Absorber Fig. 1-7 Single effect cooling cycle 6 1-5. Principal of double effect type (1) Concept & principal of double effect type In case of the single effect type absorption chiller, all condensation heat generated when the refrigerant vapor coming from the generator is cooled and condensed in the condenser is released into the cooling water. The double effect type is designed to use this released condensation heat more effectively for improvement of energy consumption as compared with single effect type. Before explaining the principal of double effect type in detail , its concept is simply explained by using an example of power plant. The dam A has one power plant (Power plant A) and the dam B has two power plant (Power plant B-1 & B-2). Water flow rate is same at the dam A and dam B. The difference of both dams is dam height. In this conditions, generated power of Power plant B-1/B-2 is double of generated power of Power plant A. Namely, if same power is required, the water flow rate of the dam B is enough 1/2 of the water flow rate of dam A. This water flow rate is considered as energy consumption of the absorption chiller. The double effect type is designed by the same concept. In other words, the double effect type has two generators and uses high level energy as compared with the single effect type. Generally, the energy level for the single effect type is about 80 deg.C (176 deg.F) Dam height : High (High potential energy) thru 110 deg.C (230 deg.F) and for the double effect type is Water flow rate Power plant A Dam A Dam height : Low (Low potential energy) about 165 deg.C (329 deg.F) or more. Water flow rate Power plant B-2 Power plant B-1 Dam B Fig. 1-8 Concept of double effect type As a next step, difference of construction between the single effect type and the double effect type is shown in Fig.1-9. The construction of the single effect type consists of 4 heat exchangers as section 1-4. The double effect type consists of 5 heat exchangers. Comparison of names of solution, vapor and Basic Double Effect Type liquid is as follows. Basic Single Effect Type Refrigerant vapor Refrigerant vapor Condenser Liquid refrigerant Generator Liquid refrigerant Concentrated LiBr solution Low temp. Generator Condenser Intermediate LiBr solution High temp. Generator Refrigerant vapor Liquid refrigerant Concentrated LiBr solution Evaporator Absorber Refrigerant vapor Evaporator Absorber Refrigerant vapor Diluted LiBr solution Diluted LiBr solution Fig. 1-9 Construction difference 7 The absorption cooling cycle continues as follows. a) The diluted LiBr solution is sent from the absorber to the high temp. generator by the absorbent pump through the high & low heat exchangers and is heated by high level driving heat energy. b) When the diluted LiBr solution temperature reaches at its saturated temperature, refrigerant vapor is released from the diluted LiBr solution, then the diluted LiBr solution concentration increases and it becomes intermediate LiBr solution. c-1) The refrigerant vapor generated in the high temp. generator goes to the low temp. generator tube side. c-2) The intermediate LiBr solution is sent to the low temp. generator through the high temp. heat exchanger which cools the intermediate LiBr solution with the diluted LiBr solution by the pressure difference between the both generators. d-1) The refrigerant vapor releases heat to the intermediate LiBr solution and condenses in the low temp. generator tubes. It becomes liquid refrigerant. The liquid refrigerant goes to the condenser. d-2) The intermediate LiBr solution is heated again by the heat from the refrigerant vapor generated in the high temp. generator and releases again refrigerant vapor. The intermediate LiBr solution becomes concentrated LiBr solution. e-1) The refrigerant vapor generated in the low temp. generator goes to the condenser and it is cooled by the cooling water. It becomes liquid refrigerant. The both liquid refrigerant together goes to the evaporator. e-2) The concentrated LiBr solution goes to the absorber through the low temp. heat exchanger which cools the concentrated LiBr solution temperature with the diluted LiBr solution. f-1) The liquid refrigerant evaporates with receiving f-2) The concentrated LiBr solution absorbs the heat from the chilled water. The evaporated evaporated refrigerant coming from the evaporator, refrigerant (refrigerant vapor) goes to the then it becomes diluted LiBr solution. absorber. g) The above steps repeat then the absorption cooling cycle continues. Condensed temp. in H.T.Generator Temp. :98 deg.C (208 deg.F) Refrigerant vapor Low temperature generator Temp. : 90 deg.C (194 deg.F) Condenser Condensed temp. :38 deg.C (100 deg.F) o o o o o o o Cooling water o o o o o o o o o o High temperature generator Temp. : 145 deg.C (293 deg.F) Refrigerant vapor o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o Driving heat source 171 dig's (340 dig's) or more o High temperature heat exchanger Liquid refrigerant Chilled water Absorber Evaporator Cooling water Intermediate LiBr solution Concentrated LiBr solution Absorbent pump Fig. 1-10 Double effect cooling cycle Diluted LiBr solution Low temperature heat exchanger 8 (2) Comparison of driving energy consumption of single and double effect types The evaporation amount of the refrigerant in the evaporator per one (1) USRT is, Heat amount of one (1) USRT = Evaporation latent heat of refrigerant 3,024 kcal/h 594 kcal/kg = 5kg/h Namely, to achieve one (1) USRT of cooling capacity, 5 kg/h of refrigerant is required. In case of the single effect type, the generator must generates 5 kg/h of refrigerant. Therefore, driving energy amount to generate 5 kg/h of refrigerant is required. However, in case of the double effect type, 5 kg/h of refrigerant is generated in the high and low temp. generators. 3 kg/h of refrigerant is generated in the high temp. generator and 2 kg/h of refrigerant is generated in the low temp. generator. In other words, the driving energy amount of the double effect type is for 3 kg/h of refrigerant only. The driving heat amount to generate 2 kg/h of refrigerant can be saved as compared with the single effect type. Also, saving driving heat amount can save condensation heat amount in the condenser. Therefore, cooling water flow arte or cooling water temperature difference can be reduced. It means a facility of cooling water system can be minimized. Condenser Generator Cooling water outlet 5 kg/h 4320 kcal/h RT Require driving heat amount 5 kg/h 5 kg/h Absorbent flow Cooling capacity 1 USRT 5 kg/h Evaporator Single effect type Cooling water inlet Absorber 2 kg/h High temp. Generator Low temp. Generator 2520 kcal/h RT (Based on LCV) Require driving heat amount 3 kg/h Cooling capacity 1 USRT Absorbent flow 5 kg/h 5 kg/h Condenser Cooling water outlet 3 kg/h 5 kg/h Evaporator Double effect type Absorber Cooling water inlet Fig. 1-11 Comparison of single effect type & double effect type 9 1-6. Function of each section & Flow diagrams (1) Evaporator Function : To make chilled water The refrigerant coming from the condenser falls on the refrigerate trays then it disperses equally on the heat exchanger tubes (evaporator tubes). The refrigerant on the evaporator tubes evaporates with removing heat from the chilled water which flows in the evaporator tubes. As a result, the chilled water is chilled. (2) Absorber Function : To keep the pressure for evaporation temperature of the refrigerant in the lower shell (Remark : The lower shell consists of the evaporator and the absorber.) The concentrated LiBr coming from the low temp. generator through the low temp heat exchanger falls on the absorbent trays then it disperses equally on the heat exchanger tubes (absorber tubes). The concentrated LiBr solution on the absorber tubes absorbs the evaporated refrigerant coming from the evaporator. When LiBr solution absorbs moisture (refrigerant vapor), the heat named "absorbing heat" generates. If the absorbing heat is not removed, the concentrated LiBr solution temperature rises. The absorbing heat must be removed so that it causes to reduce the absorbing power of the concentrated LiBr solution. This absorbing heat is removed by the cooling water which flows in the absorber tubes. By means of absorbing the refrigerant vapor with the concentrated LiBr solution cooled, the pressure in the lower shell can be kept and the chilled water can be produced continuously. After absorbing the refrigerant vapor, the concentrated LiBr solution becomes diluted LiBr solution and accumulates in the bottom of the lower shell, then the diluted solution is pumped up to the high temperature generator by the #1 absorbent pump. (3) Low temp. heat exchanger / High temp. heat exchanger / Refrigerant drain heat exchanger Function : To rise the diluted LiBr solution temperature for improvement of driving energy consumption by the three heat exchangers To lower the concentrated LiBr solution temperature for intensification of absorption power by the low temp. heat exchanger To lower the intermediate LiBr solution temperature for reduce heat released to cooling water by the high temp. heat exchanger (in other words, it means saving driving energy consumption) To lower the refrigerant drain temperature for reduce heat released to cooling water by the refrigerant heat exchanger (in other words, it means saving driving energy consumption) The diluted LiBr solution is pumped up to the high temp. generator by the #1 absorbent pump. During it passes through the three heat exchangers, its temperature is risen with the concentrated LiBr solution, the intermediate LiBr solution and the refrigerant drain. On the other hand, the concentrated LiBr solution, the intermediate LiBr solution and the refrigerant drain are cooled with the diluted solution in the each heat exchangers. 10 (4) High temp. generator Function : To heat the diluted LiBr solution for making the intermediate LiBr solution and the refrigerant vapor for concentrating the intermediate LiBr solution in the low temp. generator. The diluted LiBr solution coming from the high temp. heat exchanger is heated by the driving heat source. When the diluted LiBr solution temperature reaches at its saturated temperature, refrigerant vapor is released form the diluted LiBr solution, then the diluted LiBr solution concentration increases and it becomes the intermediate solution. (5) Low temp. generator Function : To heat the intermediate LiBr solution for making the concentrated LiBr solution and the refrigerant vapor. The intermediate LiBr solution coming from the high temp. generator is heated by the refrigerant vapor coming from the high temp. generator under the low pressure condition as compared with the high temp. generator. Then the intermediate LiBr solution releases refrigerant vapor and it becomes the concentrated LiBr solution. (6) Condenser Function : To cool and condense the refrigerant vapor coming from the low temp. generator The refrigerant vapor coming from the low temp. generator is cooled and condensed by the cooling water which flows in the heat exchanger tubes (condenser tubes) of the condenser. 11 Pipe for non-condensable gas going from high temp. generator to condenser through low temp generator tube side Pipe for non-condensable gas going from lower shell (Abso + Evap) to purge unit Steam inlet 63H SV7 Pipe for diluted LiBr solution to purge from #1 absorbent pump to purge unit DT2 Cooling water outlet Low temp. Generator Condenser Steam control valve High temp.Generator E1-3 Pipe for non-condensable gas going from upper shell (Cond + L Gene) to lower shall (Abso + Evap) 69 PR E F DT5 PCH H L I SV9 K Purge tank DT4 Rupture disk G DT12 D4 DT3 SV8 SV5 B valve V2 D 69 CH DT1 High temp. Heat exchanger A Chilled water outlet DT6 Steam trap B Evaporator M #2 Absorbent pump Chilled water inlet Absorber D7 DT11 D6 SV3 Refrigerant blow valve D5 Refrigerant drain Heat reclaimer LiBr solution strainer D3 SV6 DT10 D1 Low temp.Heat reclaimer Return pipe for diluted LiBr solution to purge mp Cooling water inlet Intermediate LiBr solution pipe Concentrated LiBr solution pipe Refrigerant solution pipe Condensed refrigerant solution pipe Refrigerant vapor pipe Refrigerant vapor & drain pipe Steam & steam drain pipe Damper Check valve Orifice Isolation valve for Abso. & Refr. pumps Service valve Diaphragm valves DT1 : DT2 : DT3 : DT4 : DT5 : DT6 : DT7 : DT10 : DT11 : DT12 : DT13 : Chilled water outlet temp. sensor Cooling water outlet temp. sensor High temp. generator temp. sensor Low temp. generator temp. sensor Condensed refrigerant temp. sensor Chilled water inlet temp. sensor Cooling water inlet temp. sensor Diluted LiBr solution temp. sensor Refrigerant in evaporator temp. sensor Middle cooling water temp. sensor Steam drain temp. sensor C DT7 #1 Absorbent pump Purge unit Diluted LiBr solution pipe Low temp. Heat Exchanger D2 SV4 Refrigerant pump J D8 DT13 High temp. Heat reclaimer Steam drain outlet PCH : 63GH : 69PR : 69CH : E1-3 : Palladium cell heater High temp. generator pressure switch Purge tank pressure switch Chilled water flow switch High temp. generator solution level electrodes Fig. 1-12 Flow diagram (For 16NK-11 thru 61) 12 Pipe for non-condensable gas going from high temp. generator to condenser through low temp generator tube side Pipe for non-condensable gas going from lower shell (Abso + Evap) to purge unit Steam inlet 63H SV7 Pipe for diluted LiBr solution to purge from #1 absorbent pump to purge unit DT2 Cooling water outlet Low temp. Generator Condenser Steam control valve High temp.Generator E1-3 Pipe for non-condensable gas going from upper shell (Cond + L Gene) to lower shall (Abso + Evap) 69 PR E F DT5 PCH H L I SV9 K Purge tank DT4 Rupture disk G DT12 D4 DT3 SV8 SV5 B valve V2 D 69 CH DT1 High temp. Heat exchanger A Chilled water outlet DT6 Steam trap B Evaporator M #2 Absorbent pump Chilled water inlet Absorber D7 DT11 D6 SV3 Refrigerant blow valve LiBr solution strainer D5 D3 DT10 D1 Refrigerant drain Heat reclaimer SV6 J C Return pipe for diluted LiBr solution to purge mp D2 SV4 DT7 #1 Absorbent pump Cooling water inlet Refrigerant pump Purge unit Diluted LiBr solution pipe Intermediate LiBr solution pipe Concentrated LiBr solution pipe Refrigerant solution pipe Condensed refrigerant solution pipe Refrigerant vapor pipe Refrigerant vapor & drain pipe Steam & steam drain pipe Damper Check valve Orifice Isolation valve for Abso. & Refr. pumps Service valve Diaphragm valves DT1 : DT2 : DT3 : DT4 : DT5 : DT6 : DT7 : DT10 : DT11 : DT12 : DT13 : Chilled water outlet temp. sensor Cooling water outlet temp. sensor High temp. generator temp. sensor Low temp. generator temp. sensor Condensed refrigerant temp. sensor Chilled water inlet temp. sensor Cooling water inlet temp. sensor Diluted LiBr solution temp. sensor Refrigerant in evaporator temp. sensor Middle cooling water temp. sensor Steam drain temp. sensor Low temp. Heat Exchanger DT13 High temp. Heat reclaimer Steam drain outlet PCH : 63GH : 69PR : 69CH : E1-3 : Palladium cell heater High temp. generator pressure switch Purge tank pressure switch Chilled water flow switch High temp. generator solution level electrodes Fig. 1-13 Flow diagram (For 16NK-62 thru 63) 13 Pipe for non-condensable gas going from high temp. generator to condenser through low temp generator tube side Pipe for non-condensable gas going from lower shell (Abso + Evap) to purge unit Steam inlet 63H SV7 Pipe for diluted LiBr solution to purge from #1 absorbent pump to purge unit DT2 Cooling water outlet Low temp. Generator Condenser Steam control valve High temp.Generator E1-3 Pipe for non-condensable gas going from upper shell (Cond + L Gene) to lower shall (Abso + Evap) 69 PR PCH E F DT5 H L I SV9 K Purge tank DT4 Rupture disk G DT12 D4 DT3 SV8 SV5 B valve V2 D 69 CH Refrigerant blow valve DT6 Chilled water inlet High temp. Heat exchanger A A Steam trap B M B Evaporator Absorber #2 Absorbent pump DT1 Chilled water outlet D7 D6 D5 DT11 LiBr solution strainer SV3 Refrigerant pump D3 DT10 D9 D1 Refrigerant drain Heat reclaimer SV6 J C mp D2 SV4 Return pipe for diluted #1 Absorbent pump DT7 Low temp. Heat Exchanger Purge unit Diluted LiBr solution pipe Concentrated LiBr solution pipe Refrigerant solution pipe Condensed refrigerant solution pipe Refrigerant vapor pipe Refrigerant vapor & drain pipe Steam & steam drain pipe Check valve Orifice Isolation valve for Abso. & Refr. pumps Service valve Diaphragm valves PCH : 63GH : 69PR : 69CH : E1-3 : Palladium cell heater High temp. generator pressure switch Purge tank pressure switch Chilled water flow switch High temp. generator solution level electrodes Cooling water inlet Intermediate LiBr solution pipe Damper DT1 : DT2 : DT3 : DT4 : DT5 : DT6 : DT7 : DT10 : DT11 : DT12 : DT13 : Chilled water outlet temp. sensor Cooling water outlet temp. sensor High temp. generator temp. sensor Low temp. generator temp. sensor Condensed refrigerant temp. sensor Chilled water inlet temp. sensor Cooling water inlet temp. sensor Diluted LiBr solution temp. sensor Refrigerant in evaporator temp. sensor Middle cooling water temp. sensor Steam drain temp. sensor DT13 High temp. Heat reclaimer Steam drain outlet Fig. 1-14 Flow diagram (For 16NK-71 thru 81) 14 oling cycle on Duhring diagram of cooling operation cycle of the double effect type on the Duhring diagram is as follows. deg.F / deg.C (101.42kPa) 212 / 100 B B : Absorption process in the absorber : Evaporation process in the evaporator entrated LiBr solution of 62.8% at point J goes into the absorber. When the F D ted LiBr solution temperature reaches point A, it begins to absorb the vapor coming from the evaporator. The concentrated LiBr solution continues E Water vapor K (580mmHg) 588.5kPa (47.42kPa) 176 / 80 s the refrigerant, being cooled by cooling water. Then the concentrated LiBr ecomes the diluted LiBr solution of 55.3% and 34.6 deg.C (94.3 deg.F) at point B. (Refrigerant) Water LiBr : 70% ure between point A and B is 0.83 kPa which is equal to the saturation vapor of water at 4.3 deg.C (39.7 deg.F), so the chilled water at 6.7 deg.C (44 deg.F) oduced in the evaporator. Concentration of diluted LiBr solution : 55.3% (19.65kPa) 140 / 60 : Heat exchanging process in the refrigerant drain heat exchanger, & the low temp. heat exchanger (and low temp. heat reclaimer) ate 20 % of the diluted LiBr solution receives heat from the refrigerant drain in the drain heat exchanger. Approximate 80% of the diluted LiBr solution receives heat oncentrated LiBr solution in the low temp. heat exchanger. The both diluted LiBr C (7.38kPa) 104 / 40 Water vapor L (46.8mmHg) 4.9kPa Concentration of intermediate LiBr solution : 59.1% G I H of which temperatures are risen are mixed at point C. : Heat exchanging process in high temp. heat exchanger & high temp. heat reclaimer (2.34kPa) 68 / 20 d LiBr solution receives heat from the intermediate LiBr solution in the high temp. Concentration of concentrated LiBr solution : anger and its temperature rises more then reaches point D. Water vapor M F K : Heating and concentrating process of the diluted LiBr solution B (6.2mmHg) 0.83kPa A in the high temp. generator d LiBr solution at point D is heated by the driving heat source until point E. After iluted LiBr solution at point E is more heated then it releases refrigerant vapor. ntly, it is concentrated and becomes the intermediate LiBr solution of 59.1% and (0.61kPa) 32 / 0 10 20 30 40 36.9 deg.C 98.4 deg.F 4.3 deg.C 39.7 deg.F 34.6 degC 94.3 deg.F 50 J 60 70 80 90 100 92.5 deg.C 198.5 deg.F 110 120 Temperature (deg.C) 130 140 150 160 144.4 deg.C 291.9 deg.F 88.6 deg.C 191.5 deg.F .C (291.9 deg.F) at point F. Fig. 1-15 Duhring diagram in cooling cycle : Heat exchanging process in high temp. heat exchanger mediate LiBr solution releases heat to the diluted LiBr solution in the high temp. heat exchanger and its temperature lowers then reaches point G. I L : Heating and concentrating process of the intermediate LiBr solution in the low temp. generator mediate LiBr solution at point G goes into the low temp. generator and its temperature lowers by self-evaporation at point H. After that, the intermediate on at point H is heated by the refrigerant coming from the high temp. generator then it releases refrigerant vapor. Consequently, it is concentrated and he concentrated LiBr solution of 62.8% and 88.6 deg.C (191.5 deg.F) at point I. : Heat exchanging process in low temp. heat exchanger entrated LiBr solution releases heat to the diluted LiBr solution in the low temp. heat exchanger and its temperature lowers then reaches point J. cycle can continues by means of repeating the above process. 15 1-8. Heat Balance & COP in cooling mode (1) Heat balance In order to cheek whether measured data is correct or not, heat balance is useful. Basic consideration of the heat balance : Heat amount coming into a chiller = Heat amount going out from a chiller The above consideration shows by the formula : (Qa + Qc) / (Qe + Qg) = 1 Qe : Heat amount coming into a chiller from an evaporator Qg : Heat amount coming into a chiller from a high temp. generator Qa : Heat amount going out from a chiller through an absorber Qc : Heat amount going out from a chiller through a condenser CHi,CHo,COi & COo : Temperature Fg : Steam consumption (kg/h) Hs : Specific enthalpy at supply steam pressure (kcal/kg) Hd : Specific enthalpy at steam drain temperature (kcal/kg) In case of SI unit In case of US unit Qe = (CHi - CHo) X Fe X 1000 / 860 Qe = (CHi - CHo) X Fe X 500 Qg = (Hs - Hd) X Fg / 860 Qg = (Hs - Hd) X Fg Qa + Qc = (COo - COi) X Fc X 1000 / 860 Qa + Qc = (COo - COi) X Fc X 500 Example Example CHi = 12.2 deg.C Qe = 352.4 kW CHi = 54 deg.F Qe = 1,200,000 Btu CHo = 6.7 deg.C Qg = 274.7 kW CHo = 44 deg.F Qg = 3 935,400 Btu Fe = 54.5 m /h Qe + Qg = 627.0 kW Fe = 240 gpm Qe + Qg = 2,135,400 Btu COi = 29.4 deg.C Qa + Qc = 628.8 kW COi = 85 deg.F Qa + Qc = 2,140,000 Btu COo = 35.4 deg.C Heat balance = 1.00 COo = 95.7 deg.F 90.8 3 m /h Fc = 400 gpm Fg = 400.0 kg/h Fg = 880 lb/h Fc = Heat balance = 1.00 Hs = 661.93 kcal/kg at 784 kPa Hs = 1191.5 Btu/lb at 114 psig Hd = 71.40 Hd = 128.5 kcal/kg at 71.4 deg.C COo Btu/lb at 160.5 deg.F Low temp. Condense Generator Fc High temp. Generator Qc Qg Steam inlet Fg Steam drain outlet CHo Evaporator CHi Qe Absorber Fe Chilled water Qa COi Cooling water Fig. 1-16 (2) COP COP is shown by the following formula. COP of NK series is about 1.28 under the condition of the standard COP = Qe Qg specification. This value changes depending on required specifications. When a operation data is recorded, if its COP differs very much from the COP of specifications, it may be wrong data recording or insufficient cooling performance of a chiller. Remark: In case of calculating heat balance and COP, cooling water inlet temperature and cooling load shall be stable for minimum 10 to 15 minutes. Because the response of absorption chiller is not rapid as compared with a electric type chiller. 16 Section 2 Illustration of chiller & control panel 2-1. Illustration of Chiller (1) 16NK-11 thru 16NK-61 4 9 10 7 2 8 5 1 Chilled water inlet 2 Chilled water outlet 3 Cooling water inlet 4 Cooling water outlet 5 Evaporator 6 Absorber 7 Condenser 8 Control panel 9 Low temp. generator 10 High temp. generator 11 Purge pump 1 6 11 3 Fig. 2-1 12 13 14 15 16 17 18 Fig. 2-2 12 Purge unit 15 No.1 Absorbent pump 13 High temp. heat exchanger 16 Low temp. heat exchanger 14 Heat reclaimer 17 No.2 Absorbent pump 18 Steam trap 17 (2) 16NK-62 thru 16NK-63 4 9 10 7 2 8 14 5 1 1 Chilled water inlet 2 Chilled water outlet 4 Cooling water outlet 5 Evaporator 6 Absorber 7 Condenser 8 Control panel 9 Low temp. generator 10 High temp. generator 11 Purge pump 14 Heat reclaimer 6 11 Fig. 2-3 17 13 14 16 19 15 18 Fig. 2-4 13 High temp. heat exchanger 18 Steam trap 14 Heat reclaimer 19 Refrigerant pump 15 No.1 Absorbent pump 16 Low temp. heat exchanger 17 No.2 Absorbent pump 18 (3) 16NK-71 thru 16NK-81 4 9 1 Chilled water inlet 2 Chilled water outlet 3 Cooling water inlet 4 Cooling water outlet 5 Evaporator 6 Absorber 7 Condenser 8 Control panel 9 Low temp. generator 10 High temp. generator 6 11 Purge pump 1 14 Heat reclaimer 10 7 2 8 14 5 6 3 11 Fig. 2-5 13 14 15 19 16 17 18 Fig. 2-6 13 High temp. heat exchanger 14 Heat reclaimer 15 No.1 Absorbent pump 16 Low temp. heat exchanger 17 No.2 Absorbent pump 18 Steam trap 19 Refrigerant pump 19 2-2. Control panel (1) For UL 1 2 5 6 7 8 9 2 3 4 Fig. 2-7 1 Fan 2 Terminal block 3 Terminal block for power supply 4 Ground terminal 5 Display panel 6 Alarm buzzer 7 Purge indication lamp 8 Purge pump on-off switch 9 Emergency stop button CAUTION : Do not push the emergency stop button except an emergency. If push, the chiller stops without dilution operation. This may be possible to occur crystallization problem. IP No. of control panel : 54 20 11 21 12 22 13 14 13 15 13 24 16 17 23 18 19 14 20 Fig. 2-8 11 Control relay 12 Circuit protector 13 Terminal block 14 Fuse 15 I/O board 16 AC Reactor 17 DC Reactor 18 Inverter 19 Main circuit breaker 20 Electromagnetic contactor 21 Transformer (TR-1) 22 Transformer (Class 2) (TR-2) 23 Transformer (24V) (TR-3) 24 Transformer (230V) (TR-4) for using 460V only 21 (2) For CE 1 5 2 6 7 8 2 10 3 4 Fig. 2-9 1 Fan 2 Terminal block 3 Terminal block for power supply 4 Ground terminal 5 Display panel 6 Alarm buzzer 7 Purge indication lamp 8 Purge pump on-off switch 10 Main circuit breaker IP No. of control panel : 54 22 21 11 28 15 12 25 13 26 16 23 17 22 18 19 20 27 Fig. 2-10 11 Control relay 12 Circuit protector 13 Terminal block 15 I/O board 16 AC Reactor 17 DC Reactor 18 Inverter 19 Main circuit breaker 20 Electromagnetic contactor 21 Transformer (TR-1) 22 Transformer (24V) (TR-2) 23 Transformer (230V) (TR-3) 25 Circuit breaker for inverter 26 Circuit breaker for pumps 27 Filter 28 Isolator 23 (3) Display panel 8 1 1 2 3. 4 Super Absorption 2 STOP RUN 13 CHILLER #1 ABS PUMP #2 ABS PUMP REF PUMP SET BACK PURGE PUMP 14 9 10 11 REMOTE STAND BY DILUTION BUZZER STOP LOCAL 6 SAFETY CIRCUIT 13 7 OPERATIO CHILLER ALARM RUN STOP POWER Fig. 2-11 Symbol 3 Name Lamp color 1 Operation indication lamp Green 2 Stop indication lamp Orange 3 Alarm indication lamp Red 6 Remote/Local select key with lamp Green 7 Operation select key with lamp Green 8 Data display (7 segments) LED 9 Stand by indication lamp Green 10 Dilution indication lamp Green 11 Safety circuit indication lamp Green 12 Power indication lamp Orange 13 Data select key 14 Alarm buzzer stop key 24 2-3. Sensor (1) Pressure sensor (PCH : Purge tank pressure sensor) 41.3 mm(1.63inch) 41.3 mm(1.63inch) Connected pin No. Model : FSK-S16 Total accuracy : +/- 3% FS (-10 --- 50 deg.C) (12 -- 122 deg.F) Max. working pressure : 0.15 Mpa (G) 3 2 1 Volt 2 Vc 1 Connection Sensor 46mm(1.811inch) GND 3 1 Vc DC 10.5 - 28V 2 Volt 3 GND 7/16-20UNF Flare Fig. 2-12 25 (2) Temperature sensor TSA-16NK series uses 3 type temperature sensors. One is Resistance thermometer bulb, second one is Thermistor, last one is Digital sensor. Dia.5.5mm 0.2 inch a) Resistance thermometer bulb 2100±80mm / 82.68±3.15 inch 50mm / 1.97 inch Fig. 2-13 Model : AEK-23H520 Used for : Chilled water outlet temperature sensor (DT1) Resistance : 2000Ω at 0 deg.C (32 deg.F) Rating of resistance : 8.56Ω/deg.C Ex. 2256.8Ω at 30 deg.C (86 deg.F) Dia.6±0.5 mm 0.25±0.02 inch b) Thermistor 150±3 mm 5.9±0.12 inch about 36 mm 1.42 inch 2500±150mm 98.4±5.9 inch Fig. 2-14 Model : U1SC-D312-S2 Used for : High temp. generator temperature sensor (DT3) : Steam drain temperature sensor (DT13) Resistance : 1kΩ±3% at 200 deg.C (392 deg.F) Temperature & Resistance Table Temperature Resistance Deg. C Deg. F k ohm 0 32 806.5 30 86 184.1 40 104 118.7 50 122 78.3 60 140 52.8 70 158 36.3 80 176 25.4 90 194 18.1 100 212 13.1 200 392 1.0 26 Dia.7±0.5 mm 0.28±0.02 c) Digital sensor 50±2mm/1.97±0.08 inch 1000±20mm / 39.4±0.79 inch: SEC-SSH-SST01SAC-L1000 2000±50mm / 78.7±1.97 inch : SEC-SSH-SST01SAC Fig.2-15 Model : SEC-SSH-SST01SAC-L1000 & SEC-SSH-SST01SAC Used for : Cooling water outlet temperature sensor (DT2) : Low temp. generator temperature sensor (DT4) : Condenser temperature sensor (DT5) : Chilled water inlet temperature sensor (DT6) : Cooling water inlet temperature sensor (DT7) : Absorber temperature sensor (DT10) : Evaporator temperature sensor (DT11) : Middle cooling water temperature sensor (DT12) IC tip provided in the digital sensor detects temperature and send it's data to CPU board through the communication line as shown below. Addresses are provided in each digital sensors. If a digital sensor is replaced, it's address must be confirmed. Control panel Communication line CPU Board Digital sensor Digital sensor Digital sensor Fig. 2-16 Address Symbol Sensor Name 03 DT2 Cooling water outlet temperature sensor 07 DT4 Low temp. generator temperature sensor 05 DT5 Condenser temperature sensor 01 DT6 Chilled water inlet temperature sensor 02 DT7 Cooling water inlet temperature sensor 12 DT10 Absorber temperature sensor 08 DT11 Evaporator temperature sensor 04 DT12 Middle cooling water temperature sensor 27 2-4. Principal of purging (1) Purpose of the purging It is very important for the chiller to keep a vacuum. The chiller generates a few amount of Hydrogen gas during operation, and the non-condensable gases are contained in the solution. Those gases worse a vacuum condition of the chiller. It means the performance fall of the chiller. Therefore, we have to discharge them from the chiller. (2) Purge system The chiller has two purge system. One is Palladium cell for discharge Hydrogen gas from the chiller. Another is purge pump for purging non-condensable gases which correct into the tank by fluid ejector. a) Palladium cell The palladium film has a property to permeate Hydrogen gas when it is 300 - 500 deg.C (572 - 932 deg.F). Steps that Hydrogen permeates through the palladium are as follows. a-1) Hydrogen is absorbed on the surface of the palladium by an affinity. a-2) Absorbed hydrogen dissociates and loss an electron then it becomes a proton. a-3) The proton invades into the grid of palladium and it diffuses in the palladium by the difference of hydrogen density. a-4) The proton returns hydrogen gas state and goes out to outside. Other gases which can not dissociate with a proton - electron state can not permeate in the palladium film. H2 P1 P2 Permeation H2 Palladium film (heated to 200 - 300 deg.C) 392 - 572 deg.F P1 > P2 P1 : Density of hydrogen before palladium film P2 : Density of hydrogen after palladium film Fig. 2-17 28 b) Correct gases by fluid ejector When the LiBr solution gushing out from the ejector goes into the solution level B, it involves bubbles of non-condensable gas. The LiBr solution and the gas together come down to the bottom of the tank. The LiBr solution returns to the absorber, and the gas comes up and accumulates in the tank. The volume of non-condensable gases existing in the lower shell which is equal to the gas accumulated in the tank moves to A from the lower shell. By means that the above is continuously repeated during operation of the chiller, non-condensable gases existing in the chiller is accumulated in the tank, then the gas can be purged by the purge pump to the air. LiBr solution from Absorbent pump discharge Non-condensable gas from the inside of Chiller A Ejector Lower shell Tank Non-condensable gas purged by a purge pump Fluid gushing out from ejector LiBr solution B Non-condensable bubbles Fig. 2-18 29 2-5. Internal structure (1) Upper shell Tube sheet Eliminator Shell Tube support Condenser tube Purge tank Generator tube Baffle Shell Tube sheet 30 (2) Lower shell Shell Tube sheet Evaporator tube Refrigerant tray Absorbent tray Absorber tube Tube support Sight glass Eliminator Tube sheet 31 (3) Heat exchanger Baffle Shell Tube Header Tube sheet Header Tube sheet 32 2-6. Symbol list (1) Temperature sensor Symbol Name DT1 Chilled water outlet DT2 Cooling water outlet DT3 High temp. generator DT4 Low temp. generator DT5 Condensed refrigerant DT6 Chilled water inlet DT7 Cooling water inlet DT8 (Blank) DT9 (Blank) DT10 Diluted LiBr solution DT11 Refrigerant DT12 Middle cooling water DT13 Steam drain (2) Electric parts on the chiller Symbol Name PCH Palladium cell heater High temp. generator 63GH pressure switch 69PR Purge tank pressure switch 69CH Chilled water flow switch E1 High temp. generator E2 solution level electrode E3 (3) Damper Symbol Name D1 Diluted solution #1 D2 Diluted solution #2 D3 D4 D5 D6 D7 Diluted solution #3 Intermediate solution Concentrated solution Refrigerant drain Refrigerant D8 Diluted solution bypass D9 Refrigerant supply Location Chilled water outlet nozzle Cooling water outlet nozzle Solution outlet box on High temp. generator Low temp. generator outlet pipe Refrigerant pipe of condenser outlet Chilled water inlet nozzle Cooling water inlet nozzle #1 Absorbent pump outlet Refrigerant pump inlet Cooling water pipe between absorber and condenser Steam drain outlet nozzle at heat reclaimer Location Purge tank Refrigerant pipe on upper shell Purge tank Chilled water outlet nozzle Solution outlet box on High temp. generator Location #1 Absorbent pump outlet Low temp heat exchanger inlet for NK-11 thru 61 Low temp heat exchanger outlet for NK-62 thru 82 Refrigerant drain heat reclaimer inlet High temperature heat exchanger outlet Low temperature heat exchanger outlet Refrigerant drain heat reclaimer outlet Refrigerant pump outlet Bypass pipe of Low temp. heat reclaimer (NK-11 thru 61 only) Refrigerant pump outlet to refregerant overflow pipe from condenser (NK-71 - 81 only) 33 (4) Service valve Symbol Name SV1 Purge SV2 Purge SV3 Refrigerant SV4 Diluted solution SV5 Intermediate solution SV6 Concentrated solution SV7 Generator pressure SV8 Generator bottom SV9 Purge tank Location Suction pipe of purge pump Suction pipe of purge pump Refrigerant pump outlet pipe #1 Absorbent pump outlet High temperature heat exchanger outlet Low temperature heat exchanger outlet Refrigerant vapor pipe on upper shell Bottom of high temperature generator Side of purge tank (5) Diaphragm valve Symbol Name V1 Purge pump V2 Purge for purge unit V3 Purge for shell B valve Purge for purge tank Location Suction pipe of purge pump Suction pipe of purge pump Suction pipe of purge pump Suction pipe of purge pump 34 (6) Control panel (Electric wiring diagram) Symbol Name ACL AC reactor BZ Alarm buzzer CP1,2, 3 Circuit protector DCL DC reactor F1-14 Fuse FILTER EMI Filter FM Fan motor GL Purge indication lamp INV Inverter ISO Isolator MA1 #1 Absorbent pump MA2 #2 Absorbent pump MP Purge pump MR Refrigerant pump MCBM Main circuit breaker MCBA1 #1 Absorbent pump circuit breaker MCB1-3 Circuit breaker PCH Palladium cell heater TR1 - 4 Transformer 23CH1 CPU board 23CH2 Indication board 23CH3 I/O board 23CH4 Power board 4Xn Control relay 43ES Emergency stop switch 43P Purge pump ON-OFF switch 51A2 #2 Absorbent pump over current relay 51P Purge pump over current relay 51R Refrigerant pump over current relay 63GH HT generator pressure switch 69CH Chilled water flow switch 69CO Cooling water flow switch 69PR Pressure sensor for purge tank 88A2 #2 Absorbent pump magnet switch 88P Purge pump magnet switch 88R Refrigerant pump magnet switch 4Y1,2 52CH 52CO CMS CVP Remote signal Chilled water pump inter lock Cooling water pump interlock Steam control valve motor Steam control valve actuator positioner (Field supply) (Field supply) (Field supply) (Field supply) (Field supply) 35 Section 3 Installation & Start-up of chiller 3-1. Overview of Installation & chiller Start-up The following sequence gives an overview of the procedure for Installation and Chiller Start-up. (1) Installation of Chiller a Delivery inspection To check damages and/or missing parts on Chiller b Location & Space requirements To check location and service space requirements of Chiller c Confirmation of inside pressure To check the inside pressure of Chiller charged at the factory Assembly of chiller (Multiple section shipment) Leak test after assembling multiple section shipment d Leveling To conduct the leveling of chiller e Field piping connection To conduct water, steam and steam drain piping to chiller f Tightness confirmation To check tightness condition of water boxes, etc. of chiller g Field wiring connections To conduct field wirings of power and interlock wirings, etc. to chiller h Rupture disk discharge piping To provide a rupture disk vent line i Insulation To provide insulation for hot and cold surface of chiller (2) Confirmation before start-up of chiller a Chilled water system b Cooling water system c Steam and drain system d Electric wiring and power supply e Cooling load 36 (3) Start-up of chiller a Confirmation of electric system To confirm all field wirings for chiller b Confirmation of auxiliary equipments To confirm water systems and steam systems c Confirmation of inside pressure To check the inside pressure of chiller charged at the installation d Leveling verification To check the leveling of chiller e Megger test To check resistance of purge pump and solution (Abso & Refr) pumps f Inspection of purge unit To check purge pump running condition and its attained vacuum g Bubble test To check vacuum leakage of chiller by the bubble test h Setting & confirmation of controls & safeties To set and confirm settings of controls and safeties by keys on the operation board (Microprocessor) i Function test of safeties To confirm that safety functions work properly j Confirmation of valve opening conditions To confirm valve opening condition of isolation k Aging & refrigerant blow down work To clean outer surface of evaporator tubes and to conduct refrigerant blow down l Adjustment of steam control valve To adjust the valve lift m Trial run To run chiller and to check operating condition of systems including chiller. (If necessary, conduct tuning the systems and chiller) n Operating data record 37 3-2. Check list General This check list covers the installation and the start-up of Steam fired Chiller models TSA-16NK series. This check list is intended to assist the personnel with the details required with the installation and the start-up of the series. This check list should be used in conjunction with the appropriate the installation manual provided with the unit. Installation check list Job Name : Job location : Chiller model : TSA-16NK- The work is in process and : will be completed by Serial number : Date : (1) Delivery inspection : The following items shall be inspected. Correct model and serial numbers. Compare all operating specifications as outlined in the "Contract specification" with the nameplate on the chiller. Inspect for physical damage to chiller including external devices, control panel and wiring. Inspect all separate shipping boxes and components shipped with chiller. Yes No N/A 1) Specifications of Chiller ordered vs. Chiller nameplate 2) Control panel a) Display panel b) Emergency stop button (UL only) c) Purge pump ON/OFF switch d) Purge indication lamp e) Alarm buzzer f) Fan j) Main circuit breaker (CE only) 3) Purge unit a) Purge pump b) Liquid trap c) Purge tank d) Service valve (SV9) e) Purge tank pressure switch (69PR) f) Palladium cell & palladium cell heater (PCH) g) Diaphragm valves (V1,V2,V3) h) Service valves (SV1,SV2,SV9) 38 Yes No N/A 4) Main shell (upper shell, lower shell, heat exchangers) a) Water headers (evaporator, absorber, condenser) b) Connection flanges (chilled water, inlet/outlet) c) (cooling water, inlet/outlet) d) #1 absorbent pump, #2 absorbent pump, refrigerant pump e) Sensors (DT1, DT2, DT3, DT4, DT5, DT6, DT7, DT10, DT11, DT12, DT13) f) Chilled water flow switch (69CH) g) Service valves (SV3, SV4, SV5, SV6) h) Dampers (D1, D2, D3, D4, D5, D6, D7, D8) i) Refrigerant blow valve j) Rupture disk k) Absorber sight glass l) Evaporator sight glass 5) High temperature generator and heat reclaimer a) Headers for high temp. generator b) Headers for heat reclaimer c) Piping flanges d) Steam trap e) Steam control valve f) Steam shutoff valve g) Service valves (SV7, SV8) h) High temp. generator pressure switch (63GH) i) Generator solution level electrodes (E1, E2, E3) j) High temp. generator sight glass for solution level k) High temp. generator pressure gauge 6) Absorbent & Refrigerant (For multiple section shipping Chiller only) 7) Accessories (If there are shortages, record them.) 8) Spare parts (If there are shortages, record them.) 39 (2) Location & Space requirements : The following items shall be inspected. Chiller is designed for indoor application and must be installed in a space where the ambient temperature is between 5 deg.C (41 deg.F) and 40 deg.C (104 deg.F), at no time more than 90% relative humidity. Clearance must be provided at either and of to facilitate tube cleaning or removal and clearance on all other sides of Chiller for general Chiller maintenance. See DIMENSION drawings in the contract specification for clearance requirements. Yes 1) Location Basement Floor No N/A Roof 2) Foundation 3) Clearance for maintenance 4) Clearance for tube cleaning/removal (3) Confirmation of inside pressure : The following item shall be inspected. The inside pressure of Chiller must be more than 0 MPa on a gauge. It can be simply checked the following way instead of using the gauge. If nitrogen gas is powerfully and continuously released from the service valve (SV1), it can be judged that there is no-leakage on Chiller. Yes No 1) In case of one section shipping For multiple section shipping Chiller only 2) In case of multiple section shipping 3) Assembly of Chiller (Multiple section shipment Chiller only) (See "Field assembly" of INSTALLATION MANUAL.) b) Pipes beveled prior to welding c) Type of welding rod utilized d) Anti-corrosion paint applied to weld joints 4) Leak test (After assembling the multiple section shipment Chiller) (See "Instruction of leak test" described in section 6.) a) Pressurize Chiller with dry nitrogen gas to 30 kPa b) No leaks checked by soap bubble test c) Pressurize Chiller with dry nitrogen gas to 50 kPa d) No leaks checked by soap bubble test f) Leave 50 kPa for minimum 12 hours g) Comparison between P and P2 (P2 is nearly equal to P) Initial pressure (P1) : kPa Remaining pressure (P2) : kPa Calculated pressure (P) : kPa Initial ambient temp. (T1) : deg.C Ambient temp. after 12 hours (T2) : deg.C Perform tightening up flange connections and flare connections, etc. flange a) Dimension check of blank filler pipes received with Chiller h) No leaks checked by soap bubble test 40 (4) Leveling Procedure of leveling 1 Locate the leveling marks on the 4 corners of the lower shell and the high temperature generator. The leveling marks are center punch indications on the end of the lower tube sheets and highlighted with a white mark. The high temperature generator has similar marks at its 4 corners. 2 Fill a clear vinyl hose or tube with water, insuring there are no bubbles in the hose. 3 Using point A as the reference point, measure the PLUS or MINUS difference in the water level at the other points B, C, D. 4 If tolerances are not met it will be necessary to shim the appropriate points by inserting metal shims between the Chiller leg and foundation. The size of the shims should be approximately 50mm X 75mm and of various thickness. A: 0 B: mm mm C: D: mm mm Leveling calculation (A - B) / L = (B - C) / L = Tolerance (C - D) / L = (A - C) / W = (A - D) / L = (B - D) / W = Yes < = 2 mm 1000 No 1) Leveling 2) Anchor bolts L A B Evaporator side W Anchor position Absorber side C D B D A Shim positions (both side) Difference C 41 (5) Field piping connection Yes No N/A 1) Chilled water piping connection 2) Cooling water piping connection 3) Cooling tower(s) installation 4) Chilled water pump(s) installation 5) Cooling water pump installation 6) Steam piping connection 7) Steam drain piping connection (6) Tightness confirmation 1) Water headers a) Flanges of evaporator b) Flanges of absorber c) Flange of condenser 2) High temperature generator and heat reclaimer a) Flanges of headers b) Flare connection of pressure switches (63GH) c) Flanges of steam drain piping 3) Pumps a) Flanges of #1 absorbent pump b) Flanges of #2 absorbent pump c) Flanges of refrigerant pump 4) Sight glass a) Absorber sight glass b) Evaporator sight glass c) High temp. generator sight glass for solution level 5) Caps of valves & dampers a) Isolation valves for #1 absorbent pump b) Isolation valves for #2 absorbent pump c) Isolation valves for refrigerant pump d) Service valve (SV1 thru SV9) e) Dampers (D1, D2, D3, D4, D5, D6, D7, D8) 6) Purge unit a) Connection flange of purge pump b) Drain trap of liquid trap c) Flare connection of purge tank pressure switch (69PR) d) Palladium cell 7) Chilled water flow switch (69CH) 8) Sensors (DT1, DT2, DT3, DT4, DT5, DT6, DT7, DT10, DT11, DT12, D13) 9) Steam control valve 10) Flange for rupture disk 42 (7) Field wiring connections Yes No N/A 1) Power supply connection (insure Chiller main circuit breaker is "off") a) Measurement of voltage ; L1 V L2 V L3 V 2) Interlock wiring (pump starter auxiliary contacts) a) Chilled water pump interlock : 52CH (#120 - #170) b) Cooling water pump interlock : 52CO (#121 - #170) 3) Start/stop signal for auxiliary equipments from Chiller control panel a) Chilled water pump (#356 - #357) b) Cooling water pump : (#358 - #359) c) Cooling tower fan : (#360 - #361) 4) Remote operation signal for Chiller a) Signal type : Non-voltage continuous signal : 4Y1 (#323 - #324) b) Signal type : Non-voltage pulse signal 4Y1 : RUN (#323 - #324) 4Y2 : STOP (#323- #325) c) Signal type : DC/AC 24V pulse signal RUN (#324) STOP (#325) COMMON (#326-#170) Jump d) Signal type : DC/AC 24V continuous signal (#324 - #326) 5) Signal for remote indication a) Pre-alarm indicator (#334 - #335) (If a maintenance message arises, this signal is sent to a remote control panel.) b) Remote check indicator (#336 - #337) (During Chiller/Heater being in REMOTE MODE, this signal is sent to a remote control panel.) c) Operation indicator (#350- #351) (During Chiller/Heater being in operation, this signal is sent to a remote control panel.) d) Stop indicator (#352 - #353) (During Chiller/Heater being in shut-down, this signal is sent to a remote control panel.) e) Alarm indicator (#354 - #355) (If an alarm occurs, this signal is sent to a remote control panel.) f) Dilution cycle operation indicator (#368 - #369) (During Chiller/Heater being in dilution cycle operation, this signal is sent to a remote control panel.) g) Purge indicator (#384 - #385) (If purging is required, this signal is sent to a remote control panel.) 6) Signal for remote alarm buzzer (#382 - #383) 7) Answer back signal (#362 - #363) (If Chiller/Heater goes into normal operation, this signal sent to a remote control panel.) 8) Grounding / Earth (#G / PE) 9) Wiring of the palladium cell heater For 460V or 400V (#232 - #0B) / For 208V (#232 - #202) 10) Remote setting for chilled water outlet temp. (#732 - #733) 43 (8) Rupture disk discharge piping Yes No N/A 1) Provide a rupture disk vent line (9) Insulation 1) Field insulation is scheduled to be completed after completion of related start-up functions 44 Confirmation before start-up check list Before the start-up function of Chiller, the following conditions should be confirmed. Job Name : Job location : Chiller/Heater model : Date : TSA-16NK- (1) Chilled water Serial number : Yes No N/A 1) Piping complete 2) Water system filled, vented 3) Expansion tank piped into system 4) Pumps installed (rotation, strainers cleaned, pumps operational 5) System controls (3-way valves, bypass valves, etc.) operable 6) Water system operated and flow balance to meet design requirements 7) Water treatment system installed (2) Cooling water 1) Piping complete 2) Water system filled, vented 3) Expansion tank piped into system 4) Pumps installed (rotation, strainers cleaned, pumps operational 5) System controls (3-way valves, bypass valves, etc.) operable 6) Water system operated and flow balance to meet design requirements 7) Water treatment system installed 8) Freeze protection for external water line (3) Electrical 1) Power source completed to Chiller control panel 2) Interlock wiring completed 3) Necessary wiring between Chiller control panel and a remote control panel 4) Pumps installed (rotation, strainers cleaned, pumps operational 5) Cooling water temperature control 6) Wiring complies with a code requested in the installation area 45 Start-up check list Date : Job Name : Job location : Chiller/Heater model : TSA-16NK- Serial number : The work is in process and : will be completed by Date : Yes (1) Confirmation of electric system No N/A Confirm all field wirings Check all wire numbers for mounted parts on Chiller Tighten terminal screws of mounted parts Pull on wires of mounted parts to insure tightness Insure there is no voltage provided to interlocks (52CH, 52CO) 1) Power supply connection (insure Chiller main circuit breaker is "off") a) Measurement of voltage ; L1 V L2 V L3 V 2) Interlock wiring (pump starter auxiliary contacts) a) Chilled/hot water pump interlock : 52CH (#120 - #170) b) Cooling water pump interlock : 52CO (#121 - #170) 3) Start/stop signal for auxiliary equipments from Chiller control panel a) Chilled water pump (#356 - #357) b) Cooling water pump : (#358 - #359) c) Cooling tower fan : (#360 - #361) 4) Remote operation signal for Chiller a) Signal type : Non-voltage continuous signal : 4Y1 (#323 - #324) b) Signal type : Non-voltage pulse signal 4Y1 : RUN (#323 - #324) 4Y2 : STOP (#323- #325) c) Signal type : DC/AC 24V continuous signal (#324 - #326) d) Signal type : DC/AC 24V pulse signal RUN (#324) STOP (#325) COMMON (#326) 5) Signal for remote indication a) Pre-alarm indicator (#334 - #335) b) Remote check indicator (#336 - #337) c) Operation indicator (#350- #351) d) Stop indicator (#352 - #353) e) Alarm indicator (#354 - #355) f) Dilution cycle operation indicator (#368 - #369) g) Purge indicator (#384 - #385) 46 Yes No N/A 6) Signal for remote alarm buzzer (#382 - #383) 7) Answer back signal (#362 - #363) 8) Grounding / Earth (#G / PE) 9) Wiring of the palladium cell heater 10) Remote setting for chilled water outlet temp. (#732 - #733) 11) Wiring connections of mounted parts a) #1 absorbent pump b) #2 absorbent pump c) Refrigerant pump d) Purge pump e) Temperature sensors (DT1, 2, 3, 4, 5, 6, 7, 10, 11, 12, 13) f) Pressure sensors (69PR, 63GH) g) Chilled water flow switch (69CH) h) High temp. generator solution level electrodes (E1, 2, 3) (2) Confirmation of auxiliary equipment 1) Chilled water piping a) Isolation valves Inlet (open / close) Outlet (open / close) b) Air vent valve (open / close) c) Drain valve (open / close) d) Thermometers (inlet / outlet) e) Pressure gauges (inlet / outlet) f) Expansion tank 2) Cooling water piping a) Isolation valves Inlet (open / close) Outlet (open / close) b) Air vent valve (open / close) c) Drain valve (open / close) d) Thermometers (inlet / outlet) e) Pressure gauges (inlet / outlet) 3) Pump capacity a) Chilled water pump(s) Qty : HP : kW : b) Cooling water pump(s) Qty : HP : kW : Voltage : L1 : L2 : L3 : Amps : L1 : L2 : L3 : c) Pump condition Chilled water pump(s) Suction press : Cooling water pump(s) Suction press : kPa/psi Discharge press : Amps : L1 : kPa/psi Discharge press : kPa/psi L2 : Lit./h /gpm L3 : kPa/psi Lit./h /gpm 5) Cooling tower model : 47 Yes No N/A 6) 3-way tower bypass control operational 7) Chilled and cooling loops filled with water 8) Automatic blow system 9) Chilled and cooling loops chemically treated 10) Expansion door on high temp. generator able to open 11) Steam and drain piping a) Steam control valve and the wiring connection b) Lift adjustment of Steam control valve c) Steam shutoff valve and the wiring connection d) Relief valve e) Reducing valve f) Drain piping 12) Steam/drain flow meter a) Location : (3) Confirmation of inside pressure : The following item shall be inspected. The inside pressure of Chiller must be more than 0 MPa on a gauge. It can be simply checked the following way instead of using the gauge. If nitrogen gas is powerfully and continuously released from the service valve (SV1), it can be judged that there is no-leakage on Chiller. Perform tightening up flange connections, flare connections, etc. (4) Leveling verification Yes No Yes No N/A Procedure : See Page 41 Reading Leveling calculation mm Lower shell B: mm (A - B) / L1 = (B - C) / L1 = C: mm (C - D) / L1 = (A - C) / W1 = D: mm (A - D) / L1 = (B - D) / W1 = A: 0 (5) Megger test Standard : More than 10 M/ohms Procedure : Remove wires of the pumps connected at terminal strips in the control panel of Chiller/Heater. Measure insulation resistances between each wires and earth (ground) with 500V megger. a) #1 absorbent pump PE - U1: M/ohms PE - V1: M/ohms PE - W1: M/ohms b) #2 absorbent pump PE - U2: M/ohms PE - V2: M/ohms PE - W2: M/ohms c) Refrigerant pump PE - U3: M/ohms PE - V3: M/ohms PE - W3: M/ohms d) Purge pump PE - U4: M/ohms PE - V4: M/ohms PE - W4: M/ohms e) All reading are greater than 10 Meg ohms NOTE : Do not apply this test to an inverter and an electronic controller. 48 (6) Inspection of purge unit (See "Instruction of inspection of purge pump" described in Section 6.) Yes No N/A 1) No-existing moisture in a liquid trap (if existing, drain it) 2) Proper oil quantity (at the red mark in operation of the pump) 3) Oil quality (Colorless & no-contamination) 4) Rotating direction (as the arrow mark on V belt cover) 5) Tension of V belt (about 10 mm pressing by a finger) 6) No abnormal noise 7) Attained vacuum kPa (7) Bubble test (See "Instruction of bubble test" described in Section 6.) 1) Purging completed 2) Inside vacuum (below allowable vacuum curve) kPa 3) Bubble test Initial bubble rate cc/10 minutes First measurement cc/10 minutes Second measurement cc/10 minutes Third measurement cc/10 minutes Average (Less than below table) Bubble test standard The rate of gas accumulation should be an average of less 15 cc in 10 minutes for a 700 kW unit with three separate measurement. Perform Leak test : See "Instruction of leak test" described in Section 6. Yes No 49 (8) Setting & confirmation of controls & safeties without burner (See "Instruction of Set & confirmation of control & safety functions" described in Section 6.) Note : The settings with under-line have been factory set. Only confirm the settings. Yes No N/A 1) Switching-on of back-up battery of microprocessor 2) Locally mounted devices a) High temp. generator pressure switch (63GH : 0MPa) 3) Safety devices in the control panel a) #1 absorbent pump over-load relay : Rated value b) #2 absorbent pump over-load relay : Rated value c) Refrigerant pump over-load relay : Rated value d) Purge pump over-load relay : Rated value 4) Microprocessor (Confirmation & Setting menu) r t. 1 3 4. 5 Present time is indicated (14:53) a) Time setting A. Set of year Y r - S E t Input year B. Set of month & day d t - S E t Input month & day C. Set of time t n. - S E t Input time C H G S b) Change of switch functions A. Cool/Heat change-over r d - S E t B. Data recode interval S A n. - d t C. Select of local operation mode L o C A L D. Cancel of predication information S E. Change of unit u n F. Change of low select control G n t Select Cool or Heat Select 1H, 5M, 1M or 10S If local mode is required, select ON If not required, push "SET" twice Select deg.C or deg.F L o S E L Invalid function, must be passed. A P P o C H c) Set of chilled water pump n t - C H Select 1H, 5M, 1M or 10S A. Set of interlock return time B. Set of variable flow rate V C. Set of parallel operation by remote controller r - P A r A Invalid function, must be passed. V - C H Invalid function, must be passed. d) Set of inverter control of chilled water pump C H - n V Invalid function, must be passed. A P P o C o e) Set of Cooling water pump n t - C o Select 1H, 5M, 1M or 10S A. Set of interlock return time B. Set of stopping cooling water pump at low load C o S t o P Invalid function, must be passed. C. Set of cooling tower fan control C t A u t o Invalid function, must be passed. D. Set of cooling tower fan temp. control C t t E n. P Invalid function, must be passed. E. Set of differential temp. of cooling tower fan C t d F. Set of variable flow rate V F F Invalid function, must be passed. V - C o Invalid function, must be passed. f) Set of inverter control of cooling water pump C o - n V Invalid function, must be passed. 50 F g) Field set E L d Yes No N/A A. Set of cooling water temp. at maximum input B. Set of slow input time n P - t n 0 0 0 0 S C. Set of slow input temp. n P t n. P 0 0 0 C D. Set of dilution time d 0 4 n. E. Set of remote signal type r - S S t A t C F. Set of type of pulse o F - P L S G. Set of low select control temperature L o S E L E Invalid function, must be passed. H. Set of radiation temperature H E C o - n P L u - t G n Rated value P o S t - S t Invalid function, must be passed. r S - 4 8 5 Invalid function, must be passed. h) Set of SR-485 i) Version No. of microprocessor U E r 0. 9 1 Indication only j) Version No. of option board o P U 0. 0 0 Indication only 5) Microprocessor (Service mode) a) Function of switch-2 C H G S 2 A. Purge indication B. Refrigerant pump C. Pilot burner D. Control valve-1 C n. - 1 E. Control valve-1 opening C n. - 1 S t F. Control valve-2 C n. - 2 G. Control valve-2 opening C n. - 2 S t Invalid function, must be passed. H. Control valve-3 C n. - 3 I. Control valve-3 opening C n. - 3 S t Invalid function, must be passed. J. HBS address A d d H b S Invalid function, must be passed. K. High speed timer function b A L. Clear of operation data o P - r S t Fixed with "Auto", can be passed. P u r G E r E F - P A u t o P L o t Invalid function, must be passed. A u t o S o K b) Set of model Do not change. 1 0 0 Invalid function, must be passed. Invalid function, must be passed. O F F 3 Example n. o d e L A. Serial number B. Type of chiller t Y P E C. Type of control C o n D. Annual cooling operation E. d Do not change. 8 7 0 1 4 Do not change. 0 Do not change. C H - o u t Do not change. A - C o o L o F F Do not change. Automatic changeover C H A u t o n. A n u A L Do not change. F. For process use P r o C o F F Do not change. G. With purge pump n. P - o P o N Do not change. H. Oil pump o P - o P o F F Do not change. G t o 51 Yes c) Rated specification setting No N/A Example S P E C A. Chilled water outlet temp. C - t E n. P 7. 0 C Do not change. B. Hot water outlet temp. H - t E n. P 4 5. 0 C Do not change. C. Chilled water temp. deff. C - d t 6. 0 C Do not change. D. Hot water temp. deff. H - d t 4. 6 C Do not change. E. No-use (extra) F. Max. opening of cont. valve r A n k u P G. Indication of purge start A P - S t 1 0. 0 k P A H. Indication of purge stop A P - S P 7. 0 k P A S n G - k Invalid function, must be passed. 1 0 0. 0 I. No-use (extra) A P - t J. No-use (extra) E K. Crystallization temp. L E C r Y S Invalid function, must be passed. d) Input setting n. Invalid function, must be passed. C o n d Invalid function, must be passed. S P E C A. Type of control b n t y P E B. Input correction P t C o r C. Combustion interval F - n t P 0 0 e) Inverter setting D Do not change. 5 0 Do not change. n. Do not change. n V S E t A. Control estimating time 3 3 A L B. Estimating tuning 1 5 Do not change. C. Constant a1 3 3 A L - K 1. 0 Do not change. n V - A 1 1 4 8 D. Do not change. Constant a2 n V - A 2 0. 0 4 2 Do not change. E. Constant a3 n V - A 3 0. 0 6 0 Do not change. F. Constant a4 n V - A 4 3. 6 Do not change. G. Constant a5 n V - A 5 5 0 Do not change. H. Constant a6 n V - A 6 2. 3 Do not change. f) PID setting P A. P for cooling C o o L - P B. I for cooling C o o L - C. D for cooling D. P for heating E. d S E t 2. 0 Do not change. 2 0 0 Do not change. C o o L - d 5 Do not change. H E A t - P 5. 0 Do not change. I for heating H E A t - 5 0 Do not change. F. D for heating H E A t - d 3 0 Do not change. G. Sampling set S A n. P L E 1 0 Do not change. 52 Yes N/A This can be passed at start-up. C o u n t g) Operation hours & On/Off times set No Note :Items A. - N. will be set after microprocessor replacing only. A. Operation hours of Chiller/Heater u n B. #1 absorbent pump operation hours A b S 1 - t C. #2 absorbent pump operation hours A b S 2 - t D. Burner operation (firing) hours F E. Refrigerant pump operation hours r E F - t F. Purge pump operation hours P u r G - t G. #3 absorbent pump operation hours A b S 3 - t Invalid function, must be passed. H. On/Off times of Chiller/Heater u n I. On/Off times of #1 absorbent pump A b S 1 - C J. On/Off times of #2 absorbent pump A b S 2 - C K. On/Off times of burner F L. On/Off times of refrigerant pump r E F - C M. On/Off times of purge pump P u r G - C N. On/Off times of #3 absorbent pump A b S 3 - C Invalid function, must be passed. r E - t P u r G E t - C r E - C S h) Predication function setting t - t G n S t o n. A. Vacuum condition B. Absorbent concentration C. Cooling water tubes fouling condition C o - d D. Cooling water temp. C o - H E. Combustion chamber fouling condition C C - d r o F F Do not change. F. Ant freezing r u L E - 1 o F F Do not change. G. Exhaust gas temp. E o F F Do not change. H. Clear of predication data r E - S E t t H r C K Invalid function, must be passed. o n. o n. G - L o 3 i) Japanese burner controller setting S j) Tuning of temp. sensors S E n S o r G n S t Invalid function, must be passed. A. Chilled/hot water outlet temp. sensor C H o A d J 0. 0 B. Chilled/hot water inlet temp. sensor C H A d J 0. 0 C. Cooling water outlet temp. sensor C o o A d J 0. 0 D. Cooling water inlet temp. sensor C o 0. 0 E. Hot water outlet temp. sensor H o A d J Invalid function, must be passed. F. Hot water inlet temp. sensor H Invalid function, must be passed. G. Sensor option setting A d J S E n - o P A d J 1 1 1 0 0 0 k) Analog data (42 data) indication A n A L o G l) Digital input data indication d G - m) Digital output data indication d G - o n) Control state indication C o t n o Do not change. o) #3 inverter setting n V 3 Invalid function, must be passed. p) #2 inverter setting n V 2 Invalid function, must be passed. 53 Yes (9) Function test of safeties without burner side No N/A 1) J-01 Chilled water low temp. alarm 2) J-02 Chilled water pump alarm 3) J-03 Chilled water flow rate alarm 4) J-04 #1 Absorbent pump alarm Not applicable 5) J-05 #2 Absorbent pump alarm 6) J-06 Cooling water pump alarm 7) J-07 Cooling water flow rate alarm 8) J-10 Refrigerant pump alarm 9) J-12 Purge pump alarm 10) J-13 Generator high temp. alarm Not applicable 11) J-14 Generator high pressure alarm Not applicable 12) J-15 High temp. generator solution level low alarm 13) J-16 High concentration alarm Not applicable 14) J-20 Cooling water low temp. alarm 15) J-21 COP alarm Not applicable 16) J-27 Cooling tower fan alarm Not applicable 17) J-28 #3 absorbent pump alarm Not applicable 18) Sensor alarm of temperature sensor 19) Sensor alarm of flow sensor (10) Confirmation of valve opening conditions 1) Isolation valves of #1 absorbent pump (Open always) 2) Isolation valves of #2 absorbent pump (Open always) 3) Isolation valves of refrigerant pump (Open always) 4) Service valve (SV7) (Open always) (11) Aging & refrigerant blow down 1) Aging (Evaporator tube outer surface cleaning) 2) Refrigerant blow down hours Concentration : (12) Operating data record 54 Trial run data sheet Project name : Chiller model :TSA-16NK- Serial number : , date DATA-1 No. Data items Unit Ambient temperature o C/ F 2 Room temperature o C / oF 3 Chilled water inlet temperature o C / oF 4 Chilled water outlet temperature o C / oF 5 Chilled water inlet pressure kPa / psi 6 Chilled water outlet pressure kPa / psi 7 Pressure drop in evaporator kPa / psi 8 Chilled water flow rate 9 Cooling water inlet temperature 1 10 Cooling water outlet temperature time: time: DATA-3 time: o m3/h / gpm o C / oF o C / oF 11 Cooling water inlet pressure kPa / psi 12 Cooling water outlet pressure kPa / psi 13 Pressure drop in absorber & condenser kPa / psi 14 Cooling water flow rate Spec. DATA-2 m3/h / gpm 15 High temp. generator temperature o C / oF 16 High temp. generator pressure o C / oF 17 Solution level in evaporator 18 Solution level in high temp. generator n/60 mm n/2-3/8" 19 Solution level in bottom of absorber 20 Pressure in purge tank kPa Concentration of concentrated solution % 21 Specific gravity of concentrated solution Temperature of concentrated solution o Concentration of diluted solution % 22 Specific gravity of diluted solution Temperature of diluted solution C / oF - o Concentration of refrigerant C / oF % 23 Specific gravity of refrigerant o C / oF 24 Condensed refrigerant temperature o C / oF 25 *LTD (See below) o C / oF Temperature of refrigerant 26 #1 absorbent pump current A 27 #2 absorbent pump current A 28 Refrigerant pump current A 29 Purge pump current A *LTD = Condensed refrigerant temp. - Cooling water outlet temperature Note: Concentrations of concentrated and diluted solutions should be sampled with nearly full load. If part load, Concentrations indicated on the data display should be recorded. 55 3-3. Reference (1) Typical piping diagram for NK series Thermostat Pressure gauge Flow meter Strainer Valve Thermostat 8 15 9 18 20 7 16 2 1 17 11 13 12 2 14 3 4 14 19 21 5 1 2 3 4 5 6 10 6 Cooling load Chilled water pump (primary) Chilled water pump (secondary) Bypass valve Supply header Return header 7 Expansion tank 8 9 10 11 12 13 Main steam piping Cooling tower Cooling water pump Blow down valve Bypass valve Make up water supply 15 16 17 18 19 20 Reducing valve Steam shutoff valve Steam control valve Relief valve To boiler Steam trap 14 Minimum tank capacity 1 m3 21 To drain channel (35 ft3) General remarks on piping 12) Install drain valves at the lowest positions between 1) Equipment and parts outside the area surrounded by the broken line are not supplied by SANYO/Carrier. 2) For pipe connections and diameter refer to the dimensional drawings and specification tables. 13) 3) Ensure that chilled water flow rate, cooling water flow rate are in conformity with the standard value. 14) If the chilled water flow rate sinks to under 50% of the standard value, the chiller will stop. 15) 4) Position the chilled water pump, cooling water 16) pump and expansion tank correctly so that the chiller pressure does not exceed the set value. 5) For cooling water temperature control refer to the 17) drawing "Cooling water temperature control method". 6) Separate chilled and cooling water pumps should be provided for each chiller. 7) Provide a cooling water blow-down valve in the cooling tower inlet for water quality control. 18) 8) Install a filter in the chilled water and cooling water pipes (10 mesh). 19) 9) Install stop valves on the chilled and cooling water inlet and outlet. 20) 10) Provide a thermometer and pressure gauge at the chilled and cooling water inlet and outlet. 21) 11) Provide an air vent valve in each of the chilled and absorption chiller and the stop valves of the chilled water and cooling water, and pipe them to the drain channel. Provide an expansion tank at highest position in the chilled water line. Install a cooling tower away from any exhaust gas outlet. Connect the pipe from rupture disk to tank. Install stop valves between the absorption chiller and stop valves of all inlets and outlets for chemical cleaning of the water circuit system. (130 psig) The maximum allowable steam pressure is 900 kPa. Please refer to this diagram to install a relief valve to ensure that the maximum pressure is not exceed. The exhaust pipe of the relief valve should be connected to the outside. If the steam superheat exceed 10 K (18 deg F), chiller performance would deteriorate. Install a filter (100 mesh), drain water pipe and pressure gauge near the chiller steam inlet location. The back pressure of the steam drain outlet pipe should be controlled below 49 kPa (7 psig). A steam trap has been installed in the chiller and does not need to be installed by the customer. cooling water line at point higher than the header. 22) The maximum steam drain temperature is 90oC(194oF). 56 (2) Field electric wiring diagram for NK series Control panel of chiller UL CE Field supply panel G L1 L2 L3 PE L1 L2 L3 To power sauce UL : 3phase 60Hz 208V or 460V CE: 3phase 50Hz 400V Chilled water pump interlock 120 52CH (Synchronized with the pump running 170 Cooling water pump interlock 121 52C (Synchronized with the pump running 170 E 345 346 E 342 340 341 0A 344 343 Remote check signal For steam shutoff valve For operation indication For stop indication For alarm indication Run/stop signal for chilled water pump Run/stop signal for cooling water pump Run/stop signal for cooling tower fan Answer back signal For dilution indication For alarm buzzer For purge indication 334 335 336 337 347 348 350 351 352 353 354 355 356 357 358 359 360 361 362 363 368 369 382 383 384 385 + - CVP DC 4 - 20mA Open Y T Close G 3 2 Open 1 Close CMH (AC 24V) Potisioner 135 ohm Terminal strips in control panel Pre-alarm signal DC 24V 10mA In case of steam control valve positioner (Field supply) In case of steam control valve motor (Field supply) Field wiring connection 1) Wiring of power supply and earthing The chiller has MCB. Please connect power supply wire to the terminal block. And also connect wire between chiller control panel and earth at field. Earthing resistance : Local regulation Earthing cable : Annealed copper wire (Please use the wire as same the thickness as the wire of the power supply) Note) 1) Should be work the electric wiring connection by license holder. 2) Use steel conduit for electric wiring between field electric supply and control panel of the chiller. 3) Field wiring connections are all low voltage without supply voltage. 57 Remote operation signal Chiller can be operate by following signals; 1) Non-voltage Normal open contact for start & stop (DC24V 10mA) Wiring the terminal 324 and 323, connect 170 and 326. Jump 323 324 326 170 4Y1 Continuous signal 2) Non-voltage Normal open contact for start (DC24V 10mA) Wiring the terminal 324 and 323, connect 170 and 326. Non-voltage Normal open contact for stop (DC24V 10mA) Wiring the terminal 325 and 323. Jump 323 324 325 326 170 4Y1 Pulse signal 4Y2 3) Non-voltage Normal open contact for start (DC24V 10mA) Wiring the terminal 324 and 323, connect 170 and 326. Non-voltage Normal close contact for stop (DC24V 10mA) Wiring the terminal 325 and 323. Jump 323 324 325 326 170 4Y1 Pulse signal 4Y2 4) Continuous signal of DC/AC 24V for start & stop. (Initial setting at factory) Wiring the terminal 324 and 326. (Those terminals are non-polarity) 324 326 DC/AC 24V Continuous signal 5) Pulse signal of DC/AC 24V for start. Wiring the terminal 324 and 326. (Those terminals are non-polarity) Pulse signal of DC/AC 24V for stop. Wiring the terminal 325 and 326. (Those terminals are non-polarity) com 324 325 326 DC/AC 24V Pulse signal 58 Remote setting of chilled water outlet temperature Control panel of Chiller E 732 733 Terminal strips in the control panel + DC 4 - 20 mA (Field supply) Input current : Cooling mode : DC 4-20mA +0 to +5oC Ste point of chilled water outlet temperature is offset by remote control panel such as central monitoring panel. Setting mode Cooling mode : Set point + Offset dt (below the maximum set point) Cooling mode +5 +4 +3 +2 +1 0 oC Offset dt 4mA 8mA 12mA 16mA 20mA Input current 1) Should be work the electric wiring connection by license holder. 2) Use steel conduit for electric wiring between field electric supply and chiller control panel. 59 (3) Confirmation of inside pressure of Chiller We have learned from experiences that the procedure for "Confirmation of nitrogen pressure in Chiller by means of comparing the temperature and pressure between factory data and field data" is very difficult, and also not practical. Factory charge pressure is 0.02 Mpa. Accordingly, we have changed the procedure to check whether leakages exist or not as follows: a) In case that the pressure gauge shows "0" : There is a possibility of leakage. Conduct the below steps. Tighten flanges, flares → Conduct purging → Aging →Bubble test Judge whether there is a leakage or not according to the bubble test result. b) In case that the pressure gauge shows not "0" : It is thought of no-leakages. Conduct the below steps. Conduct purging → Aging →Bubble test Judge whether there is a leakage or not according to the bubble test result. c) As simple judgment way, if nitrogen gas forcefully blow out from the service valve, it is regarded as no leakage and start the procedure b) described above. The reasons we changed the procedure is as follows; Current charged N2 pressure at the factory is 20 Kpa (0.02 Mpa) and the same compound gauge as for NK has been used for charge of N2 gas in the factory(0.25~0~-0.1 Mpa, Minimum scale unit :0.01MPa). In this case, it is difficult to judge if there is a leakage or not. Please refer to below study. (Condition) Nitrogen charge pressure at the factory 0.02 Mpa Temp. at factory when N2 was charged 25 deg. C Temp. difference Calculated Difference between the factory pressure with charged pressure (MPa) and the site(deg. C) 5 10 15 20 25 30 0.022 0.024 0.026 0.028 0.030 0.032 0.002 0.004 0.006 0.008 0.010 0.012 Judgment Impossible Difficult to judge Differences are apparent (More than one scale unit at pressure gauge) 60 (4) Detail explanation of interlock and proper interlock signal type a) It is necessary to understand why interlock is in dispensable for operation of chillers. If a chilled water pump and cooling water pump are reliable to run normally and stably, and they can supply water reliably, normally and stably, interlocks of them are not required. But actually there always been possibilities of troubles like malfunction of pumps, malfunction of electrical parts of the pumps, clogging of strainers in chilled and cooling water lines and this kind of troubles cause abnormal supply of chilled and cooling water. Sudden stop of chilled water will cause troubles like freezing of tubes at the evaporator, also sudden stop of cooling water will cause generator high temperature alarm, high pressure alarm and in extreme case, if the electrical safety device and the rupture disk does not work properly, there is a possibility to damage the generator. Thus in order to operate a chiller, it is necessary to have interlock signal from pumps in order to confirm proper supply of chilled water and cooling water. b) Basically the safest interlock is to receive a signal which is sent when enough water flow is detected. In this sense, the flow switch is the best and that's why chilled water flow switch is installed as standard (Cooling water flow switch is an option because the damages of the chiller caused by stop of cooling water is less when compared to chilled water cases.) Of course there is a possibility of malfunction of the flow switch itself, so from the stand point of double safety consideration, startup confirmation signals of pumps (Usually an auxiliary contact of magnet contactor) are used as electrical interlock signal. Start signals for the pumps are not appropriate for interlock signal because even the pump does not run due to some problems, the signals will be sent to the chiller and the chiller recognizes that the pump runs. c) Basic Interlock Connection Chilled water pump start signal During operation of a chiller or after a operation of a chiller, if you operate only the cooling water pump, there is a possibility that the tubes in the evaporator will be damaged by remaining cooling capacity. You can opeate the cooling water pump only when the chilled water pump is operating. Accordingly, when the chilled water pump stops, the cooling water pump also needs to stop. CHW pump electric circuit CHW pump Auxiliary Magnet contact contactor Cooling water pump start signal Chilled water flow switch Control panel Chilled water pump Absorption chiller COW pump electric circuit COW pump Magnet contactor Cooling water pump Auxiliary contact Cooling water pump interlock These three signal are necessary for operation of the chiller. Chilled water pump interlick 61 (5) Aging & Tube surface cleaning of evaporator a) Purpose of aging process & Cleaning outer surface of evaporator tubes The purpose of the aging process is to remove any air that may have entered into Chiller during the solution charging process and dissolved oxygen in the Lithium Bromide & refrigerant solution. The purpose of the evaporator tube outer surface cleaning is to improve wetting condition of the evaporator tubes with refrigerant for increasing evaporation efficiency. b) By means that Chiller is continuously operated, the Lithium Bromide solution is circulated by #1 absorbent pump in Chiller. It can bubble out any entertained air and dissolved oxygen then the gas can be easily removed from Chiller by the purge pump. On the other hand, the refrigerant adjusted with approximately 20 % of concentration and charged in the factory is circulated by the refrigerant pump in the evaporator. It can clean the outer surface of the evaporator tubes. c) Procedure As described above, the both works can be conducted and proceeded at the same time. c-1) Run the purge pump and check the attained vacuum. Then open V1 and V3. c-2) The set value of "rAnkuP" should be changed to "0"(zero). See "Instruction of Set & confirmation of control & safety functions" described in Section 6. c-3) Run Chiller. Confirm that chilled water and cooling water is running normally. c-4) The set value of "rAnkuP" should be changed to "50". For a while, high temp. generator temperature rises gradually. c-5) Adjust fuel input by "rAnkuP" to maintain the high temp. generator temperature between 100 deg.C and 120 deg.C. c-6) Continue this operation for approximately 6 hours. c-7) Perform the refrigerant blow down. (See "Instruction of refrigerant blow down" described in Section 6.) Note 1 : During the work, often check the attained vacuum whether the attained vacuum is OK or not. If not, close V1 for approximately 30 minutes, the attained vacuum may recovers. Note 2 : If chilled water outlet temperature may go down to the temperature of stopping the refrigerant pump, more decrease the set value of "rAnkuP". Note 3 : If the refrigerant pump stops with the alarm "J-10", the reset button of the refrigerant pump overload relay mounted contactor sticks out. In this case, increase the refrigerant pump overload relay set value and push the reset button, then re-start Chiller. After completion of the work, return the set value at original value. 62 Section 4 Control 4-1. Overview of control functions (1) Block diagram of control functions The control of TSA-16NK Series consists of the following functions. Operation Start function Stop function Capacity controls Dilution cycle operation Main control method Cooling capacity is controled by PID control which modulates a steam control valvge. Maximum opening of fuel control valve changeable function (Simple name of the function is "Ranl-up") (For DJ seres) In case of the high heating capacity type, fuel input of heating mode is bigger than cooling mode. Accordingly, both fuel inputs must be differently set. The fuel input of heating mode is set at 100 % and the fuel input of cooling mode is set for the value corresponding with cooling capacity. The both maximum fuel input settings can be automatically changed by Cool/heat changeover function. The set value of the function has been set at the factory. Therefore the set shall not be basically changed on normal operation. However, this function is useful for servicing such as de-crystallization. In such case, authorized personnel only can change the set value. Slow open function of steam control valve If required, the steam control valve is slowly opened at the starting Chiller in order to achieve soft starting condition for Chiller. Maximum steam input reduction function by cooling water inlet temp. The maximum opening of steam control valve is reduced depending on cooling water inlet temp. in order to protect crystallization and excessive high of temperature and/or pressure condition in H.T.Geneator Steam input reduction function by H.T.Generator temp. If the H.T.Generator temperature reaches at 162 deg.C, the steam input is reduced in order to avoid the alarm of "generator high temp." alarm (J-13) Steam control valve close function by concentrated solution concentration If the concentrated LiBr solution concentration rises 65 %, control valve closes in order to avoid the alarm of "concentrated LiBr solution concentration high" alarm (J-16). Excessive low chilled water outlet temp. control function These conditions can be controlled by steam control valve and/or the refrigerant pump. Absorbent solution flow rate control Inverter control with solution level control in H.T.Generator for #1 absorbent pump #1 absorbent pump rotation speed is controlled by the inverter with the solution level control in H.T.Generator in order to flow suitable absorbent flow rate corresponding with required cooling load for saving steam consumption and achieving stable chilled water outlet temperature in part load. Pre-set function of chilled water outlet temperature Auto-reset function of chilled water outlet temperature setting This function is to avoid cavitations of a refrigerant pump possibly occurring under the condition that a chilled water outlet temperature setting is comparatively high and the cooling water inlet temperature is low. 63 Predication functions (Maintenance message) Purge tank high pressure : Message code H-06 Purging should be conducted from the purge unit. The purge unit will be shortly filled with non-condensable gas. Operate purge pump : Message code H-01 Purging shall be conducted from the purge tank. Cooling water tubes fouled: Message code H-07 Absorber and condenser tubes have been slightly fouled. Tube cleaning shall be planed. Clean cooling water tubes : Message code H-03 Absorber and condenser tubes have been fouled. Tube cleaning shall be conducted. Cooling water high temp. : Message code H-08 If H-08 is often indicated, check cooling water system. H-08 is lights up when the cooling water inlet temp. rises beyond the specified temp. +2 deg C. Check cooling water system. : Message code H-04 If H-04 is indicated, check cooling water system. H-04 is lights up when the cooling water inlet temp. rises beyond the specified temp. temp. + 2 deg.C. Power failure : Message code H-10 When the power resumes, this message is displayed. Safety functions For chilled water freeze protection See section 5. Trouble shooting For crystallization protection See section 5. Trouble shooting For motor protection See section 5. Trouble shooting For oxygen deficiency accident protection See section 5. Trouble shooting For combustion accident protection on Weishaupt burner Refer to Weishaupt burner manual 64 (2) Construction of devices for control is shown as below figure The control of TSA-16NK Series consists of the following functions. Control panel Display borad Open/Close signal Steam control valve : DC 4-20mA or Microprocessor (CPU) Open/Close signal Steam control valve Feedback signal Positioner 135 ohm 63GH : H.T.Generator pressure switch 69PR : Purge tank pressure switch 69CH : Chilled/hot water flow switch E1, E2, E3 : High temp generator solution level electrodes DT1 : Chilled water outlet temp. sensor DT3 : High temp. generator temp. sensor DT13 : Steam drain temp. sensor DT2 : Cooling water outlet temp. sensor DT4 : Low temp. generator temp. sensor DT5 : Condensed refrigerant temp. sensor DT5 : Condensed refrigerant temp. sensor DT7 : Cooling water inlet temp. sensor DT10 : Diluted LiBr solution temp. sensor DT11 : Refrigerant in evaporator temp. sensor DT12 : Middle cooling water temp. sensor Purge pump #1 ABS pump #2 ABS pump Ref. Pump Fig. 4-1 Construction of devices for control 65 4-2. Operation sequence The starting and shut-down sequences of Chiller are follow. (These sequences are described with the interlock system of Chiller.) (1) Starting sequence Pressing RUN key on the operation board or Remote start signal Contact of chilled water flow switch opens No J-03 After 10 min., chilled water flow rate alarm No J-01 After 10 min., chilled water low temp. alarm Yes Chilled water temp. is above 2.5 deg.C (36.5 deg.F) Yes Chilled water pump starts signal goes to chilled water pump operation circuit from control circuit of Chiller Chilled water pump starts J-02 After 10 min., chilled water pump alarm Chilled water pump interlock signal goes to control circuit of Chiller ON signal of 69CH returns to control circuit of Chiller No Yes No J-03 After 10 min., chilled water flow rate alarm Yes Cooling water pump starts signal goes to cooling water pump operation circuit from control circuit of Chiller Cooling water pump starts Cooling water pump interlock signal goes to control Cooling tower fan circuit works No J-06 After 10 min., cooling water pump alarm Yes Chiller starts #1 ABS pump starts After 5 min. #2 ABS pump starts Normal cooling operation Fig. 4-2 Start sequence 66 (2) Shut-down sequence Pressing STOP key on the operation board or Remote stop signal Steam control valve travels to close. Steam shut-off valve closes after 1 min. Refrigerant pump stops according to HT generator temp. Cooling water pump stops according to HT generator temp. Cooling tower fan stops Chilled water pump stops after 1 minute. Dilution operation #1 absorbent pump stops within 15 minutes. #2 absorbent pump stops within 15 minutes. Chiller stops entirely Fig. 4-3 Shut-down sequence in cooling mode 67 (3) Start time chart (Fig.4-4) Start signal Open Steam shut-off valve Close 100% Steam control valve 0% Run Chilled water pump Stop Run Cooling water pump Stop Run #1 Absorbent pump Stop Run #2 Absorbent pump Stop Run Refrigerant pump Stop 10 T2 min. 5 min. 15 min. (4) Stop time chart (Fig4-5) Stop signal 5 Open Steam shut-off valve 100 Gene temp. C Fig. 4-6 155 Close 100% Steam control valve 0% Run Chilled water pump Stop Run Cooling water pump Stop Run #1 Absorbent pump Stop Run #2 Absorbent pump Stop Run Refrigerant pump Stop 1 min. 1 min. T1 T2 T1 time is for GENE temp. goes down to below 100 deg.C (4 thru 20 min.) 68 4-3. Capacity control & other control functions The capacity control of TSA-16NK series is PID control. A signal of chilled water outlet temperature detected by DT1 is sent to a microprocessor then the steam control valve controls cooling capacity. (1) Max. opening of fuel control valve changeable function (Rank-Up) : (DJ series only) As mentioned Sec. 4-1, fuel input settings of cooling mode and heating mode must be changed in case of the high heating capacity type. The relation between Rank-up set value and maximum fuel control valve modulating signal is as shown in Fig. 4-7. In case of 80% of Rank-up set, the fuel control valve modulating signal for cooling mode is varies from 0% to 80% corresponding with changing cooling load. In other words, the maximum fuel control valve modulating signal is limited at 80%. (The fuel control valve modulating signal for heating mode is varies from 0% to 100%.) Do not increase Rank-up set beyond 100 % 100 Rank-up set : 100% 80 80 Fuel consumption : Heating mode = Cooling 60 60 40 40 20 20 Fuel consumption : Heating mode is 1 Rank-Up set (%) Fuel control valve modulating signal (%) 100 Example : Rank-up set : 80% Cooling mode is 0.8 0 10 20 30 40 50 60 70 80 90 100 Load (%) Fig. 4-7 Rank-Up Reference Using the function, the maximum fuel input is easily changed such as a case of de-crystallization work requiring fuel input changing many times. The maximum fuel input is limited by the set of Rank-up. The procedure of Rank-up is described in Section 6-19 "Rated specification setting". There is the same function to limit (fix) the maximum fuel input. That is the menu items 4) and 5) of (1) Function switch-2 in the service mode. But, in case of the method, it is not simple method to use the menus as compared with Rank-up, because one function by 2 menus. 69 (2) Slow open function of steam control valve The function is provided to avoid over-input at the setting of the chiller. The control valve opens gradually show below. Factory setting, setting time(Tso) is 900 seconds. This time(Tso) is variable from 0 to 1800 seconds. How to change the control valve show refer to Section 6. But, actually valve opening depended on control valve motor or actuator. Control valve opening (%) 100 70 40 20 0 Tso Tso/5 Time (sec.) (Factory setting 900 sec.) Fig. 4-8 Slow open (3) Max. steaml input reduction function by cooling water inlet temp. The maximum opening of steam control valve is reduced depending on cooling water inlet temp. in order to protect crystallization and excessive high of temperature and/or pressure condition in H.T.Geneator For crystallization protection : The steam control valve modulating signal is reduced automatically depending on the cooling water inlet temperature. The starting temperature of the reduction is the specified temperature minus 4 deg.C (7.2 deg.F) constant. For avoidance of Generator high temp. alarm (J-13) : The steam control valve modulating signal is reduced automatically depending on the cooling water inlet temperature. The starting temperature of the reduction is the specified temperature plus 2 deg.C (3.6 deg.F) constant. Fuel control valve modulating signal (%) 100% ST : Specified temperature ST is factory set. Do not change. (Refer to Page 44 / Sec.6 for setting ST at replacement of the microprocessor only) 80% 60% Avoidance of Generator high temp. alarm (J-13) Crystallization protection 0% ST-13 deg.C (ST-23.4 deg.F) ST-4 deg.C (ST-7.2 deg.F) ST ST+2 deg.C (ST+3.6 deg.F) Cooling water inlet temperature Fig. 4-9 70 (4) Steam input reduction function by H.T.Generator temp. If the H.T.Generator temperature reaches 162 deg.C due to some cause, the steam input is reduced in order to avoid the alarm of "Generator high temp." alarm (J-13). In case that H.T.Generator temperature reaches 162 deg.C, the steam control valve modulation signal reduces 80% of the present value then continues 80% for 10 minutes. Example : The steaml control valve modulating signal reduces from 90% to 72% and continue 72% for 10 min. After the action, there are 4 actions as follows. (1) IF H.T.Generator temp. goes down below 162 deg.C and the condition continues, Chiller runs normally. (2) If H.T.Generator temp. rises 162 deg.C or more within 5 minutes, Chiller stops with J-13. But (3) If H.T.Generator temp. rises 165 deg.C or more at any time, Chiller stops with J-13. (4) If H.T.Generator temp. rises 162 deg.C again and the condition continues for 10 min., Chiller stops with J-13. Fuel control valve modulating signal 90 H.T.Generator temperature 80 72 70 (3) (4) (2) 60 50 165 162 160 40 30 (1) 20 150 10 0 10 min. 5 min. 10 min. H.T.Generator temp. (deg.C) Fuel control valve modulating signal (%) 100 0 Fig. 4-10 Fuel input reduction function by H.T.Generator (5) Steam control valve close function by concentrated solution concentration If the concentrated Libr solution concentration rises 65 %, steam control valve closes in order to avoid the alarm of "concentrated LiBr solution concentration high" alarm (J-16). In case that the calculated concentrated LiBr solution concentrated rises 65%, steam control valve closes for approximately 1 miniuite and keep to close for 2 minuites, then steam control valve opens again. After the action, there are 4 actions as follows. (1) IF the concentration goes down below 65% and the condition continues, Chille runs normally. (2) If the concentration rises 65% again after just 3 minutes, Chiller stops with J-16. But (3) If the concentration rises 65% again within 1 hour, Chiller stops with J-16. (4) If the concentration rises 65.5% at any time, Chiller stops with J-16. Control Control valve Concentration % 0% 65.5 65.0 64.0 2 min. 3 min. 1 hour Fig. 4-11 71 (6) Excessive low chilled water outlet temp. control function Control for excessive low chilled water outlet temperature in cooling mode If the chilled water outlet temperature goes down below 1.5 deg.C of the set value of specified chilled water outlet temperature, combustion stops. But if the chilled water outlet temperature still goes down, the refrigerant pump stops at minus 2 deg.C of the set value of specified chilled water outlet temperature. ST : Set calue of specified chilled water outlet temp. ON(Run) Control valve OFF(Stop) ST-1.5 deg.C (ST-2.7 deg F) ST ST-1.0 deg C (ST-1.8 deg F) Fig. 4-12 (7) Absorbent solution flow rate control Absorbent solution flow rate is controlled by an inverter for #1 absorbent pump and H.T.Generator solution level control in order to flow suitable absorbent flow rate corresponding with required cooling load for saving steam consumption and achieving stable chilled water outlet temperature in part load. a) #1 absorbent pump rotation speed controlled by the inverter #1 absorbent pump rotation speed is controlled by the frequency signal sent from the inverter. The frequency signal is computed by 5 parameters shown in Fig. 4-13 depending on the signal of H.T.Generator temperature and the cooling water inlet temperature. a : To set maximum temperature for maximum frequency that is 60 Hz Parameters 1 a : To set slant of an oblique line showing change of frequency 2 a3 : To set shifting rate of the oblique line depending on cooling water inlet temperature a4 : To set an inflection point on the oblique line a5 : To set frequency used for heating mode only (fixed value) a6 : To set minimum frequency Frequency (Hz) 60 a3:0.060 50 28 deg.C 26 deg.C a4:3.6 3.6 x 12 = 43.2 24 deg.C 40 Cooling water inlet temp. 22 deg.C Constant 32 deg.C a2:0.42 30 deg.C 30 a6:2.3 2.3 x 12 = 27.6 20 80 84.0 Constant 90 100 Base temp. at minimum frequency 110 120 130 H.T.Generator temperature (deg.C) 140 150 160 a1:148 Fig. 4-13 Example ofInverter 72 b) High temperature generator solution level control In addition to the inverter control, the high temperature generator solution level control corrects the frequency signal to reduce gradually if the solution level reaches the control electrode. If the solution level rises and then it reaches E1, the inverter frequency reduces depending on the time for while the solution contacts with E1. The solution level does not go down below E1 even if the frequency is corrected by the control, #1 absorbent pump stops. If the solution level goes down below E1, #1 absorbent pump re-starts. For control of correction of inverter frequency (E1) For solution level low alarm : J-15 (E2) For earth (E3) The above explanation is only on the control. #1 absorbent pump can run continuously during normal operation condition. If the solution level goes down below E2, the solution level low alarm (J-15) occurs and then Chiller goes into safety shutdown. Solution level of J-15 Solution level electrode box Fig. 4-14 H.T.Generator solution level control (8) Pre-set function of chilled water outlet temperature Auto-reset function of chilled water outlet temperature setting This function is to avoid cavitation of a refrigerant pump possibly occurring under the condition that a chilled water outlet temperature setting is comparatively high and the cooling water inlet temperature is low. In case of the operating condition, steam input may not be required to keep required chilled water outlet temperature. No-steam causes no-generating refrigerant. Therefore, the refrigerant level in the evaporator goes down. It may cause the cavitation. In order to avoid the cavitation, this function chages low the setting of chilled water outlet temperature automatically as shown in Fig. 4-15. Chilled water setting temp. 12 deg.C (53.6 deg.F) 11 deg.C (51.8 deg.F) 10 deg.C (50.0 deg.F) 9 deg.C (48.2 deg.F) 8 deg.C (46.4 deg.F) 7 deg.C (44.6 deg.F) 22 deg.C (71.6 deg.F) 24 deg.C 26 deg.C 27 deg.C (75.2 deg.F) (78.8 deg.F) (80.6 deg.F) Cooling water inlet temp. Fig. 4-15 Pre-set function of chilled water outlet temperature 73 4-4. Predication function (maintenance message) (1) Poor vacuum condition predication function There are two cases for this function as follows. a) Judgment by the purge tank pressure The message code "H-06 : PURGE TANK HIGH PRESSURE" will be indicated when the purge tank pressure goes up to 10 kPa. The message code "H-01 : OPERATE PURGE PUMP" will be indicated when the purge tank pressure goes up to 11 kPa. b) Judgment by increasing ratio of the purge tank pressure If "H-06" is indicated, the purge tank will be filled with non-condensable gas near future. Purge should be conducted from the purge tank. If "H-01" is indicated, the purge tank will be shortly filled with non-condensable gas. Purge shall be conducted from the purge tank. Graph 4-1. Vacuum condition monitoring 1.0 Maintenance zone Pressure rising indication of storage tank The message code "H-01" or "H-06" will be indicated depending on the increasing ratio of the purge tank pressure. For example, if the purge tank pressure increases 1kPa per 1 minute, then H-01 will be indicated. This function does not work in the first 60 minutes after each startup because the purge tank pressure goes up rapidly at startup. Also this function does not work when Chiller is not operating. 0.6 Notice zone Normal zone 0 0 20 60 100 80 Storage ratio (%) Remark In case of heating mode, If H.T.Generator temperature goes up 120 deg.C, "H-01" is indicated. In this case, the purging shall be conducted after Chiller is cool down. 74 (2) Cooling water fouling predication function There are two cases for this function as follows. (1) Message code "H-07 : COOLING WATER TUBES FOUL" If "H-07" is indicated, it shows that the heat transfer tubes in the absorber and condenser are fouled which may affect fuel consumption. In this case, tube cleaning should be planed. (2) Message code "H-03 : CLEAN COOLING WATER TUBES" If "H-03" is indicated, it shows that the heat transfer tubes in the absorber and condenser are fouled which may affect an occurrence of alarms. In this case, conduct tube cleaning as soon as possible. Concept of the function Graph 4-2. Fouling of heat transfer tubes in cooling water system This messages are made based on the following temperatures. Tci : Cooling water outlet temperature at condenser Tco : Cooling water inlet temperature at condenser Tcr : Condensed refrigerant temperature in condenser During cooling operation, an area is calculated by the three temperatures at that time, and the are is compared with LTD. No-indication or "H-07" or "H-03" is depending on the comparison result between Ltd and LTD. Maintenance line Maintenance zone Fouling indicator LTD : Standard value to judge fouling condition When Chiller is new (no-fouling condition), the above temperatures are measured with enough cooling load and an area is calculated. This area is called as Ltd. This Ltd is measured for several days, and then the average is calculated from Ltd data as shown in Fig. 4-18. This average is LTD. 8 6 4 Notice zone 2 Normal line Normal zone 2 4 6 8 100 Cooling load factor (%) Ltd-x Tcr Ltd-3 Ltd-2 Averaging LTD Tco Tci Ltd-1 Fig. 4-16 LTD 75 (3) Cooling water temperature high predication function There are two cases for this function as follows. (1) Message code "H-08 : COOLING WATER HIGH TEMP" If cooling water inlet temperature is within the following value, H-08 is indicated. If H-08 is often indicated, make a schedule to check and maintain a cooling water system. 0 deg.C < PCOIT minus SCOIT = or < 2 deg.C PCOIT : Present cooling water inlet temp. SCOIT : Specified cooling water inlet temp. (2) Message code "H-04 : CHECK COOLING WATER SYSTEM" If cooling water inlet temperature is beyond the following value, H-04 is indicated. In this case, check and conduct necessary maintenance for a cooling water system as soon as possible. PCOIT - SCOIT > 2 deg.C (4) Power failure Message code : H-10 POWER FAILURE When the power resumes after power failure, this message is displayed. 76 4-5. Safety shutdown time chart Following safety shutdown functions are provide on TSA-16NK series. Chilled water freeze protection Purpose Symbol Crystallization protection Motor protection Work condition Chilled water low temp. alarm Below 2.5 deg.C J-02 Chilled water pump alarm No-chilled water pump interlock signal J-03 Chilled water flow rate alarm Below 50 % of specified chilled water flow rate J-20 Cooling water low temp. alarm Below specified cooling water inlet temp. minus 13 deg.C for 30 minutes. J-06 Cooling water pump alarm Cooling water flow rate alarm (Option) J-07 Others Name of Alarm J-01 No cooling water pump interlock signal Below 50 % of specified cooling water flow rate 162 deg.C or more for 10 minutes or 165 deg.C. (at cooling mode) In cooling mode,0 MPa for UL & CE J-13 Generator high temp. alarm J-14 Generator high pressure alarm J-15 Generator solution low level alarm Below E2 J-16 High concentration alarm 65% twice or 65.5%. J-04 #1 Absorbent pump alarm By working #1 absorbent pump overload relay J-05 #2 Absorbent pump alarm By working #2 absorbent pump overload relay J-10 Refrigerant pump alarm By working refrigerant pump overload relay J-12 Purge pump alarm By working purge pump overload relay J-11 System interlock alarm No-ventilation fan interlock signal J-21 Capacity alarm 1 deg.C or less of chilled water temp. difference at 100% fuel input. Alarm priority list Each alarm is classified depending on their risk level viewing from Chiller protection as follows. Each shutdown time chart is difference depending on the priorities. Note 1 : If two or more alarms in difference priorities occur at the same time, a higher priority alarm is indicated on the display board. Note 2 : If two or more alarms in a same priority occur at the same time, indication on the display board is as order. Priority Cooling mode 1st priority J-01, J-02, J-03 2nd priority J-04, J-05 3rd priority J-06, J-07, J-10, J-11 4th priority J-13, J-14, J-15, J-16 5th priority J-20, J-21 77 (1) Shutdown time chart of 1st priority in cooling mode a) Alarm code & name, working condition J-01 : Chilled water low temperature alarm At starting If the chilled water outlet temperature is below 2.5 deg.C and continues for 10 minutes after just starting of Chiller, the cooling system including Chiller does not proceed and J-01 is indicated on the During operation If the chilled water outlet temperature goes down below 2.5 deg.C for 2 seconds during the operation of Chiller, Chiller stops by J-01. J-02 : Chilled water pump alarm At staring If the chilled water pump interlock signal does not return Chiller within 10 minutes after just starting of Chiller, the cooling system including Chiller does not proceed and J-02 is indicated on the display During operation If the chilled water pump interlock signal is cut during the operation of Chiller, Chiller/Heater stops by J-03 : Chilled water flow rate alarm At starting If the chilled water flow rate does not increase more then 50 % of the rated flow rate for 10 minutes after just starting of Chiller, the cooling system including Chiller does not proceed and J-03 is indicated on the display board. During operation If the chilled water flow rate decreases blow 50 % of the rated flow rate during the operation of Chiller, Chiller stops by J-03. b) Time chart of 1st priority alarms happened during the operation is as follows. Alarm Steam shut-off valve Steam control valve Chilled water pump Cooling water pump #1 Absorbent pump #2 Absorbent pump Open Close 100% 0% ON OFF 1 min. ON OFF ON OFF ON OFF ON Refrigerant pump OFF T1 + 1 min. Fig. 4-17 Time chart for 1st priority alarms 78 (2) Shutdown time chart of 2nd priority in cooling mode a) Alarm code & name, working condition J-04 : #1 absorbent pump alarm At starting If #1 absorbent pump overload relay is already working, J-04 is indicated immediately when the START button is pressed or the remote start signal comes into the control circuit of Chiller, and the cooling system including Chiller does not proceed any more. During operation If #1 absorbent pump overload relay works during the operation of Chiller, Chiller stops by J-04. J-05 : #2 absorbent pump alarm At starting If #2 absorbent pump overload relay is already working, J-05 is indicated immediately when the START button is pressed or the remote start signal comes into the control circuit of Chiller, and the cooling system including Chiller does not proceed any more. During operation If #2 absorbent pump overload relay works during the operation of Chiller, Chiller stops by J-05. b) Time chart of 2nd priority alarms happened during the operation is as follows. Alarm Steam shut-off valve Steam control valve Chilled water pump Cooling water pump #1 Absorbent pump #2 Absorbent pump Open Close 100% 0% ON OFF 1 min. ON OFF 1 min. ON OFF ON OFF ON Refrigerant pump OFF T1 Fig. 4-18 Time chart for 2nd priority alarms 79 (3) Shutdown time chart of 3rd priority in cooling mode a) Alarm code & name, working condition J-06 : Cooling water pump alarm At staring If the cooling water pump interlock signal does not return Chiller within 10 minutes after just starting of Chiller, the cooling system including Chiller does not proceed and J-06 is indicated on the display During operation If the cooling water pump interlock signal is cut during the operation of Chiller, Chiller stops by J-06. J-07 : Cooling water flow alarm At starting If the cooling water flow rate does not increase more then 50 % of the rated flow rate for 10 minutes after just starting of Chiller, the cooling system including Chiller does not proceed and J-07 is indicated on the display board. During operation If the cooling water flow rate decreases blow 50 % of the rated flow rate during the operation of Chiller, Chiller stops by J-07. J-10 : Refrigerant pump alarm At starting If the refrigerant pump overload relay is already working, J-10 is indicated immediately when the START button is pressed or the remote start signal comes into the control circuit of Chiller, and the cooling system including Chiller does not proceed any more. During operation If the refrigerant pump overload relay works during the operation of Chiller, Chiller stops by J-10. J-11 : System interlock alarm At staring If the ventilation fan interlock signal does not return Chiller within 10 minutes after just starting of Chiller, the cooling system including Chiller does not proceed and J-11 is indicated on the display During operation If the ventilation fan interlock signal is cut during the operation of Chiller, Chiller stops by J-11. b) Time chart of 3rd priority alarms happened during the operation is as follows. 80 Alarm Steam shut-off valve Steam control valve Chilled water pump Cooling water pump Open Close 100% 0% ON OFF 1 min. ON OFF 1 min. #1 Absorbent pump #2 Absorbent pump ON OFF ON OFF ON Refrigerant pump OFF T1 T2 Fig. 4-19 Time chart for 3rd priority alarms 81 (4) Shutdown time chart of 4th priority in cooling mode a) Alarm code & name, working condition J-13 : Generator high temperature alarm At staring : Refer to 4-5-8 "Sensor alarm" During operation If H.T.Generator temperature reaches 162 deg.C again within 5 minutes after passing 10 minutes functioning "Steam input reduction by H.T.Generator temperature" or reaches 165 deg.C, Chiller J-14 : Generator high pressure alarm At staring : Refer to 4-5-8 "Sensor alarm" During operation If H.T.Generator pressure reaches 0 MPa, Chiller stops by J-14. J-15 : Generator solution low level alarm During operation with combustion If the H.T.Generator solution level goes down below E2, Chiller stops by J-15. J-16 : High concentration alarm During operation If the concentrated solution concentration rises 65% again at passing just 3 minutes after starting "Steam control valve close function by concentrated solution concentration" or rises 65% again within 1 hour after starting "Steam control valve close function by concentrated solution concentration" or rises 65.5%, Chiller stops by J-16. b) Time chart of 4th priority alarms happened during the operation is as follows. Alarm Steam shut-off valve Steam control valve Chilled water pump Cooling water pump Open Close 100% 0% ON OFF 1 min. ON OFF 1 min. #1 Absorbent pump #2 Absorbent pump ON OFF ON OFF ON Refrigerant pump OFF T1 T2 Fig. 4-20 Time chart for 4th priority alarms (5) Shutdown time chart of 5th priority in cooling mode 82 a) Alarm code & name, working condition Cooling water low temp. alarm watched temperature J-20 : Cooling water low temperature alarm At staring If the cooling water inlet temperature does not reach the temperature shown in Fig. 4-23 within 30 minutes after starting Chiller with continuous steam supply condition, Chiller stops by J-20. During operation If the temperature shown in Fig. 4-23 is continued for 30 minutes during the operation of Chiller with continuous steam supply, Chiller stops by J-20. 19 deg.C (66.2 deg.F) 14 deg.C (57.2 deg.F) 20 deg.C (68 deg.F) 32 deg.C (89.6 deg.F) Fig. 4-21 Specified cooling water inlet temperature J-21 : Capacity alarm During operation If the chilled water inlet/outlet temperature difference continues 1 deg.C or less for 30 minutes during the operation of Chiller under the condition that fuel input is 100% and H.T.generator is 130 deg.C or more, Chiller stops by J-21. 83 b) Time chart of 5th priority alarms happened during the operation is as follows. Alarm Steam shut-off valve Steam control valve Chilled water pump Cooling water pump Open Close 100% 0% ON OFF 1 min. ON OFF 1 min. #1 Absorbent pump #2 Absorbent pump ON OFF ON OFF ON Refrigerant pump OFF T1 T2 Fig. 4-22 Time chart for 5th priority alarms 84 (6) Sensor alarm If a sensor is broken (short/disconnection), Chiller shutdown manner and the alarm indication are as follows. Sensor symbol and name In case that sensor is already broken at starting In case that sensor is broken during operation Symbol Name of sensor Chiller is safety-shutdown by JJ-01 is indicated. Chiller can not 01. F25 can be indicated by DT1 Chilled water outlet temp. sensor F25 be run. F25 can be indicated by pressing pressing key. key. DT2 Cooling water outlet temp. sensor F3 F3 is indicated. Chiller can be run. Alarm code DT3 H.T.Generator temp. sensor J-13 is indicated. Chiller can not Chiller is safety-shutdown by JF26 be run. F26 can be indicated by 13. F26 can be indicated by pressing key. pressing key. DT4 L.T.generator temp. sensor J-16 is indicated. Chiller can not Chiller is safety-shutdown by JF7 be run. F7 can be indicated by 16. F7 can be indicated by pressing key. pressing key. DT5 Condensed refrigerant temp. sensor J-16 is indicated. Chiller can not Chiller is safety-shutdown by JF5 be run. F5 can be indicated by 16. F5 can be indicated by pressing key. pressing key. DT6 Chilled water inlet temp. sensor F1 F1 is indicated. Chiller can be run. DT7 Cooling water inlet temp. sensor J-20is indicated. Chiller can not F2 be run. F2 can be indicated by pressing key. DT10 Diluted LiBr solution temp. sensor F12 F12 is indicated. Chiller can be run. DT11 Refrigerant temp. sensor F8 F8 is indicated. Chiller can be run. DT12 Middle cooling water temp. sensor F4 F4 is indicated. Chiller can be run. DT13 Steam drain temp. sensor J-17 is indicated. Chiller can not Chiller is safety-shutdown by JF27 be run. F27 can be indicated by 17. F27 can be indicated by pressing key. pressing key. Remarks : Regarding DT2, DT6, DT10, DT11 and DT12, be sure to replace a sensor broken before operation of chiller even if Chiller can be operated. If Chiller is operated with broken sensor(s), the control except PID control and/or predication functions do not work normally. 85 (7) Other alarm (Important information at start-up procedure & replacement of a microprocessor) Remarks : At shipment of Chiller from the factory, the time setting in a microprocessor has been set as follows. But if the alphabet is displayed in LED F21 and/or F23 will be displayed. In this case, correct the time setting in accordance with Page 40 / Sec.6. Year : Month & day : 0 1 - 0 1 Time : 0 7 2 0 0 1 Example of wrong setting AM 7:00 1st January 2001 (Factory set value) 0 0 A 2 0 0 1 0 1 - 0 1 A 0 7 A 0 0 The alphabet "A" has been wrong inputted The alphabet "A" has not been reased a) F21 : CPU alarm If F21 is displayed, causes are the wrong time setting described above or malfunction of the microprocessor. If time setting is wrong, correct it. Even if the time setting is corrected, F21 does not go off, it means that the microprocessor is out of order. Replace it. b) F22 : MEMORY alarm If F22 is displayed, it means that the reading / writing function of the microprocessor is malfunction. In this case, the microprocessor must be replaced. c) F23 : TIME SET alarm If F21 is displayed, causes is the wrong time setting described above. Correct the time setting. d) F24 : CONSTANT SET alarm If F24 is displayed, causes is that wrong setting (s) is exist in some respects settings. It may be possible to happen at replacement of the microprocessor. Especially , if the set of type (see page 50 / Sec.6), this alarm code happens due to allowable setting range difference depending on models If this alarm code is displayed, correct settings in accordance with the following steps. d-1) Memory clear Turn off the power for Chiller/Heater Press & keys at the same time Under the above pressing condition, turn on the power for Chiller/Heater C L r is displayed. Two keys being pressued are once free, then press key immediately continuously for a while. is displayed. Memory clear is completed. E n d d-2) Perform necessary settings. 86 Section 5 Trouble Shooting 5-1. Chilled water outlet temperature does not go down in cooling mode No chilling Steam control valve Related each other Absorbent cycle Check Improper absorbent flow rate Control valve signal Malfunction of inverter & control Octyle alcohol is insufficient Chilled water temp controller Microprocessor malfunction Temp sensor (DT1) malfunction Cooling water inlet temp. is too high. Crystallization Poor vacuum condition Too low cooling water inlet temp Cooling water system Cooling water temp does not go down due to high humidity Cooling water flow is insufficient Fouling of tubes Refrigerant cycle Charging too much refrigerant Refrigerant leaks into absorbent side due to corrosion of refrigerant Fouling of tubes Refrigerant pump reverse rotation Water leak due to corroded pass partition plate in water box Refrigerant blow valve is not close Pass partition gasket in water box comes off Refrigerant is contaminated with LiBr Vacuum side Insulation Air leakage Improper foundation Palladium cell malfunction Improper leveling of chiller Palladium cell heater malfunction Inhibitor is insufficient Purge pump can not get attained vacuum Chilled water system Chilled water flow is too much Fouling of tubes Solution heat exchangers Water leaks due to controlled pass partition plate in water box Absorbent flow rate decreased due to tube broken Absorbent flow rate decreased due to clogging of heat exchangers Pass partition gasket in water box comes off Cooling load increased due to expansion of cooling area, etc Over load Facility Insufficient air handling unit 87 5-2. Trouble shooting at alarm in cooling mode (1) Chilled water low temp. alarm / Alarm code : J-01 / Safety device : Chilled/hot water outlet temp. sensor (DT1) J-01 In case that J-01 occurs at 2.5 deg.C(36.5 deg.F) of the chulled water outlet temp. Fuel control valve does not modulate Check signals between Chiller and Control valve DT1 malfunctions (Sensor alarm : F25) Replace DT1 The microprocessor malfunctions Replace the microprocessor If several or all of the following conditions continue. Check the cooling system 1) 2) 3) 4) 5) In case that J-01 occurs above 2.5 deg.C (36.5 deg.F) of the chilled water outlet Low cooling water inlet temp. Low chilled water flow (Min. 50%) Low cooling load condition Sudden change of cooling load Holding water quantity of chilled water is a very few DT1 malfunctions (Sensor alarm : F25) Replace DT1 The microprocessor malfunctions Replace the microprocessor (2) Chilled water pump alarm / Alarm code : J-02 / Safety device : Chilled water pump interlock signal (52CH) J-02 In case that 52CH comes into the I/O board In case that 52CH does not come into the I/O board Remark : 52CH can be checked by the service mode. I/O board malfunctions (especially, connectors) Imperfect contact of wires or connectors connected to I/O board happens Replace the I/O board Replace wires, connectors The chilled water pump stops Start the chilled water pump Power supply for remote control panel is OFF Tern on the power supply Imperfect contact happens in a remote control circuit Check & repair the contact Interlock signal wires or a connector is out of order Replace wires and the connector 88 (3) Chilled water flow rate alarm / Alarm code : J-03 / Safety device : Chilled/hot water flow switch (69CH) J-03 In case that chilled water flow rate is more than 50 % of the rated flow rate In case that chilled water flow rate is less than 50 % of the rated flow rate The flow switch malfunctions Replace the flow switch The flow switch is wrong set Re-adjust the flow switch The wire of flow switch is cut Replace wire I/O board is out of order Replace the I/O board Capacity of the chilled water pump is insufficient Resistance of chilled water circuit is too much Contact to a facility company A differential pressure control valve in the chilled water circuit malfunctions Air is exiting in the chilled water circuit Perform air vent A strainer in the chilled water circuit is clogged Clean the strainer A valve in the chilled water circuit is closed Open the valve 89 (4) #1 absorbent pump alarm / Alarm code : J-04 / Safety device : Protective functions in a inverter Note : Protective function menu & working condition of a inverter can be confirmed by a display panel on the inverter. J-04 In case that a protec-tive function of the inverter works An electronic thermal in the inverter works #1 absorbent pump is fastened (not rotating) Crystallization Foreign materials De-crystallization Remove them Insulation failure of pump motor coil Replace the stator of the pump Short of pump motor coli Ground fault of pump motor coil Too much absorbent flow rate Re-adjust absorbent flow rate by solution dampers The inverter malfunctions Replace the inverter The wrong settings of the inverter Correct the setting A protective function except for the elec-tronic thermal works In case that protective functions of the inverter do not work Refer to the manufacturer's instruction manual of inverter An alarm signal is not sent from the inverter to microprocessor The inverter malfunctions The microprocessor malfunctions Check the inverter, microprocessor and wiring of the alarm signal, then replace failure parts (5) #2 absorbent pump alarm / Alarm code : J-05 / Safety device : Thermal relay (51A2) J-05 In case that the thermal relay (51A2) functions #1 absorbent pump is fastened (not rotating) Crystallization due to too short dilution operation time De-crystallization & changing the time Addition of too much inhibitor Insulation failure of pump motor coil Short of pump motor coli Replace the stator of the pump Ground fault of pump motor coil The thermal relay (51A2) malfunctions Replace 51A2 Wrong setting of the thermal relay Correct the setting The magnet contactor (88A2) malfunctions Replace 88A2 90 (6) Cooling water pump alarm / Alarm code : J-06 / Safety device : Cooling water pump interlock (52CO) J-06 In case that 52CO comes into the I/O board In case that 52CO does not come into the I/O board Remark : 52CO can be checked by the service mode. I/O board malfunctions (especially, connectors) Imperfect contact of wires or connectors connected to I/O board happens Replace the I/O board Replace wires, connectors The cooling water pump stops Start the cooling water pump Power supply for remote control panel is OFF Tern on the power supply Imperfect contact happens in a remote control circuit Check & repair the contact Interlock signal wires or a connector is out of order Replace wires and the connector (7) Cooling water flow rate alarm / Alarm code : J-07 / Safety device : Cooling water flow switch (69CO) OPTION J-07 In case that cooling water flow rate is more than 50 % of the rated flow rate In case that cooling water flow rate is less than 50 % of the rated flow rate The flow switch malfunctions Replace the flow switch The flow switch is wrong set Re-adjust the flow switch The wire of flow switch is cut Replace the wire I/O board is out of order Replace the I/O board Capacity of the cooling water pump is insufficient Resistance of cooling water circuit is too much Contact to a facility company Air is exiting in the chilled water circuit Perform air vent A strainer in the chilled water circuit is clogged Clean the strainer A valve in the chilled water circuit is closed Open the valve 91 (8) Refrigerant pump alarm / Alarm code : J-10 / Safety device : Thermal relay (51R) J-10 In case that the thermal relay (51R) functions Refrigerant pump is fastened (Not rotating) Foreign materials Failure (insulation fault, short, ground fault, disconnection) of pump motor coil In case that the thermal relay (51R) functions Remove foreign materials Replace the stator of the pump The thermal relay (51R) malfunctions Replace 51R Wrong setting of the thermal relay Correct the setting The magnet contactor (88R) malfunctions Replace 88R Contamination of refrigerant happens Search & remove the cause Refrigerant flow rate is too much Re-adjust the flow rate The thermal relay (51R) malfunctions Replace 51R Short of thermal relay wires Replace the wires The microprocessor malfunctions Replace the microprocessor (9) System interlock alarm / Alarm code : J-11 / Safety device : Ventilation fan interlock (52F) J-11 In case that 52F comes into the I/O board I/O board malfunctions (especially, connectors) Imperfect contact of wires or connectors connected to I/O board happens In case that 52F does not come into the I/O board Remark : 52F can be checked by the service mode. Replace the I/O board Replace wires, connectors The Ventilation fan stops Start the ventilation fan Power supply for remote control panel is OFF Tern on the power supply Imperfect contact happens in a remote control circuit Check & repair the contact Interlock signal wires or a connector is out of order Replace wires and the connector 92 (10) Purge pump alarm / Alarm code : J-12 / Safety device : Thermal relay (51P) J-12 In case that the thermal relay (51P) functions Purge pump is fastened (Not rotating) Rotate the pulley of purge pump by hands. (It may occur in winter) If absorbent solution goes into the pump, the inside of pump is corroded and the pump is locked. Replace the pump motor. Failure (insulation fault, short, ground fault, disconnection) of pump motor Replace the purge pump motor The thermal relay (51R) malfunctions Replace 51R Wrong setting of the thermal relay Correct the setting The magnet contactor (88P) malfunctions Replace 88R 93 (11) Generator high temp. alarm / Alarm code : J-13 / Safety device : H.T.Generator temp. sensor (DT3) J-13 J-13 occurs at set value Poor vacuum condition H-01 is continuously displayed Perform purging immediately If OK, the cause is only insufficient purging Absorbent flow rate is Insufficient Cooling water problems J-13 occurs below set value J-13 still occurs. Attained vacuum of purge pump is not suitable. #1 abso. pump does not run (Refer to J-04) J-13 still occurs. Pd cell and/or its heater malfunction. #1 Abso. pump runs J-13 still occurs. Leakages may be possible. Perform leak test. Improper set of diluted solution dampers Re-adjust dampers Reverse rotation of #1 abso.pump Correct the wiring Crystallization De-crystallization Insufficient octyl alcohol Add octyl alcohol Insufficient solution charged Add solution Cooling water inlet temp. is higher than rated temp. Cooling water flow rate is insufficient Absorber and condenser tubes are fouled Contact to a facility company DT3 malfunctions Replace DT3 F-26 94 (12) Generator high pressure alarm / Alarm code : J-14 / Safety device : H.T.Generator pressure switch (63GHH) J-14 J-14 occurs at set value Poor vacuum condition H-01 is continuously displayed Perform purging immediately If OK, the cause is only insufficient purging J-13 still occurs. Attained vacuum of purge pump is not suitable. J-13 still occurs. Pd cell and/or its heater malfunction. Absorbent flow rate is Insufficient J-13 still occurs. Leakages may be possible. Perform leak test. #1 abso. pump does not run (Refer to J-04) #1 Abso. pump runs Cooling water problems J-14 occurs below set value Insufficient inhibitor may be considered. If inhibitor is insufficient, a lot of hydrogen gas generate. Improper set of diluted solution dampers Re-adjust dampers Reverse rotation of #1 abso.pump Correct the wiring Crystallization De-crystallization Insufficient octyl alcohol Add octyl alcohol Insufficient solution charged Add solution Cooling water inlet temp. is higher than rated temp. Cooling water flow rate is insufficient Absorber and condenser tubes are fouled Contact to a facility company 63GH malfunctions DT3 malfunctions Replace 63GH 95 (13) Generator solution level low alarm / Alarm code : J-15 / Safety device : H.T.Generator solution level elect rods (E1& E2) J-15 J-15 occurs even if solution level is normal Electrodes does not detect the solution level This can be checked by the digital input indication. E1 is ON. Disconnection of wires of electrodes Replace wires Electrode surface is fouled Replace electrodes LiBr solution bubbling in the electrode box (There is a case to occur this after long term operation) Replace LiBr solution The microprocessor malfunctions J-15 occurs due to low solution level This can be checked by the digital input indication. E2 is OFF. LiBr flow rate is insufficient Digital input signal for #1 abso. pump is sent to the inverter #1 abso. pump does not run (Refer to J-04) #1 Abso. pump runs #1 abso. pump malfunctions Check the pump. Prepare or replace it Inverter malfunctions Replace inverter Wrong settings of Inverter & microprocessor Wrong damper settings (D1, D2, D3) Tube failure of solution heat exchanger (s) Clogging solution heat exchanger (s) The check valve is locking Insufficient LiBr in absorber bottom due to crystallization, contamination, Digital input signal for #1 abso. pump is not sent to the inverter Over steam input The microprocessor malfunctions Correct them Correct them Replace failure heat exchanger Replace it Remove the cause Replace the microprocessor Re-adjust the steam input 96 (14) High concentration alarm / Alarm code : J-16 / Safety device : L.T.Generator temp. sensor (DT4) & Condensed refrigerant temp. sensor (DT5) J-16 J-16 occurs with following conditions If OK, the cause is only insufficient purging Poor vacuum condition J-13 still occurs. Attained vacuum of purge pump is not suitable. H-01 is continuously displayed Perform purging immediately Absorbent flow rate is Insufficient #1 abso. pump does not run (Refer to J-04) J-13 still occurs. Pd cell and/or its heater malfunction. Replace it (them). J-13 still occurs. Leakages may be possible. Perform leak test. Insufficient inhibitor may be considered. If inhibitor is insufficient, a lot of hydrogen gas generate. #1 Abso. pump runs Steam input is too much Cooling water problems J-16 occurs without following conditions Improper set of diluted solution dampers Re-adjust dampers Reverse rotation of #1 abso.pump Correct the wiring Crystallization De-crystallization Insufficient octyl alcohol Add octyl alcohol Insufficient solution charged Add solution Wrong adjustment of steam control valve Re-adjust steam control valve Wrong setting of microprocessor Re-set microprocessor Microprocessor malfunctions Replace microprocessor Cooling water inlet temp. is higher than rated temp. Cooling water flow rate is insufficient Absorber and condenser tubes are fouled Contact to a facility company DT4 malfunctions (F-7) Replace DT4 DT5 malfunctions (F-5) Replace DT5 Condition of occurring alarm 1. In case that concentrated solution concentration goes up 65% after 3 minutes of starting crystallization protection function 2. In case that concentrated solution concentration goes up 65% within 1 hour after starting crystallization protection function 3. In case that concentrated solution concentration goes up 65.5%. 97 (15) Cooling water low temp. alarm / Alarm code : J-20 / Safety device : Cooling water inlet temp. sensor (DT7) J-20 J-20 occurs while cooling water inlet temp. continues below rated temp. minus 13 deg.C for 30 minutes J-20 occurs even if cooling water inlet temp. above rated temp. minus 13 deg.C I/O board malfunctions (especially, connectors) Contact to a facility company Microprocessor malfunctions Replace the microprocessor DT7 malfunctions Replace DT7 (16) Capacity alarm / Alarm code : J-21 Refer to section 5-1 "Chilled water outlet temperature does not go down in cooling mode" 98 Section 6 Parts replacement & Instructions 6-1. Guidance interval of parts replacement The following intervals are guidance for replacement of parts to get stable operation. Operation time is less than 4,000 Heavy load operation, process use Replacement parts hours per year for air-conditioning. and/or continuous annual operation 1 Absorbent pump 2 Refrigerant pump 3 Purge pump 4 Generator pressure gauge 5 Palladium cell & heater 6 Sight glass & gaskets 7 Diaphragm valve gasket 8 Controller 9 Circuit breaker 10 Magnet switch 11 Temperature sensor # Rupture disk 24,000 or 6 years 24,000 or 6 years 10 years 28,000 hours or 7 years 12,000 hours or 3 years 6 years 6 years 5 years 40,000hours or 10 years 28,000 hours or 7 years 28,000 hours or 7 years 4,800 hours or 1 year 16,000 hours or 4 years 16,000 hours or 4 years 10 years 20,000 hours or 5 years 12,000 hours or 3 years 6 years 6 years 5 years 40,000hours or 10 years 28,000 hours or 7 years 28,000 hours or 7 years 4,800 hours or 1 year 99 6-2. How to change parts (1) #1 & #2 Absorbent pumps & Refrigerant pump This instruction describes the procedure to replace #1 & #2 absorbent pumps and refrigerant pump. As procedures for the absorbent pumps and the refrigerant pump are same, the procedure for #1 absorbent pump is explained in this material. a) Instrument a-1) Pan to collect spilled absorbent / refrigerant solution at disassembling them a-2) wood blocks a-3) Box wrenches Pump a-4) Adjustable wrenches a-5) Insulation tape a-6) Vinyl tape Power i Vinyl tape Terminal box Wood blocks Vinyl back Fig. 6-1 Fig. 6-2 Pan b) Procedure b-1) Be sure to confirm that the main breaker (MCBM) is turned OFF. b-2) Close the isolation valves of the pump tightly. b-3) Open the cover of terminal box. Disconnect power wires (U1, V1, W1) in the terminal box. b-4) Cover each end of wires by a vinyl tape to prevent wetting with solution then cover them by a vinyl back as shown in Fig. 6-1. At this time, record wire marks. b-5) Put the pan under the pump b-6) Put the wood block between the pan and the pump shown in Fig. 6-2. b-7) Remove bolts of the pump and pull out the pump carefully b-8) Wash the flange and the isolation valve portion mounted under the lower shell with water. (Pure water or distilled water should be used) b-9) Check if the flange surface is clean or not. If OK, mount new pump with new gasket. Be sure to tighten all bolt uniformly because it is very difficult to do leak test. Non-uniform tightening causes air leakage. b-10) Connect the power wires with confirming wire marks and cover each connected portions with the insulation tape and vinyl tape. Then close the terminal box cover. b-11) Open the isolation valves. b-12) Run the chiller to confirm the rotating direction of the pump by a rotation direction meter. Correct direction is clockwise viewing from back of the pump. If OK, stop the chiller. b-13) Perform air purging from the chiller for 1 hour (Open purge valve V1 & V3) b-14) Run the chiller with about 50% input and perform air purging from the chiller for 1 hour. b-15) If there are no- abnormality, the chiller can be run on normal operation. 100 (2) Purge pump This instruction describes the procedure to replace an purge pump with a motor. a) Instrument a-1) Adjustable wrenches a-2) Insulation tape a-3) Vinyl tape 4 bolts for flange Terminal box Sight glass 4 bolts for base Purge pump Purge pump motor Fig. 6-3 b) Procedure b-1) Be sure to confirm that the main breaker (MCBM) is turned OFF. b-2) Be sure to confirm that the purge valves (V1, V2, V3) are closed. b-3) Remove purge pump oil in the purge pump. b-4) Open the cover of terminal box. Disconnect power wires (U4, V4, W4) in the terminal box. b-5) Cover each end of wires by a vinyl tape to prevent wetting with solution then cover them by a vinyl back as shown in Fig. 6-1. At this time, record wire marks. b-6) Remove the 4 bolts for the flange and 4 bolts for the base shown in Fig. 6-3. Then remove the pump. b-7) Put new pump. b-8) Temporally tighten 4 bolts for the base. Tighten 4 bolts for the flange tightly. Then tighten 4 bolts for the base tightly. b-9) Connect the power wires with confirming wire marks and cover each connected portions with the insulation tape and vinyl tape. Then close the terminal box cover. b-10) Run the pump to confirm the rotating direction of the pump. Correct direction is shown by the arrow mark on the V-belt cover. b-11) Charge the purge pump oil up to the center of the sight glass under running of the purge pump. b-12) Check that V-belt tension is about 10 mm (0.4 inch). If not, adjust the tension by sliding the motor. b-13) Check the attained vacuum of new pump. 101 (3) Sight glass This instruction describes the procedure to replace sight glasses with gasket. a) Instrument a-1) Adjustable wrenches a-2) Bucket for solution a-3) Vacuum rubber hose with copper tube a-4) Nitrogen gas a-5) Hose for nitrogen gas a-6) Regulator for nitrogen gas b) Position of the sight glass b-1) Evaporator b-2) Bottom of the absorber Bolt Gasket Sight glass flange Sight glass Bolt Fig. 6-4 b-3) High temp. generator c) Replacement of the sight glass on the evaporator. c-1) If the refrigerant solution level is beyond the bottom of the sight glass, perform the refrigerant blow down. c-2) Charge Nitrogen gas into the chiller up to about 9.8 kPa. c-3) Discharge Nitrogen gas. (Refer to "6-12. Method of discharging Nitrogen gas") c-4) Remove 6 bolt for the sight glass and remove the sight glass and gasket. c-5) Clean the surface of the sight glass flange by dry cloth. c-6) Put new sight glass and gasket. Tighten bolts uniformly. c-7) Charge Nitrogen gas into the chiller up to about 49 kPa. c-8) Perform leak test by soap solution. c-9) Discharge nitrogen gas. Perform purging until the pressure in the chiller goes down to 1.3 kPa absolute. c-10) Run the chiller with about 50% input and perform air purging from the chiller for 1 hour. c-11) If there are no- abnormality, the chiller can be run on normal operation. d) Replacement of the sight glass on the absorber. d-1) Charge Nitrogen gas into the chiller up to about 30 kPa. d-2) Discharge LiBr solution from the service valve (SV4) until the solution level falls to the sight glass bottom. d-3) Discharge Nitrogen gas. d-4) Remove 6 bolt for the sight glass and remove the sight glass and gasket. d-5) Clean the surface of the sight glass flange by dry cloth. d-6) Put new sight glass and gasket. Tighten bolts uniformly. d-7) Charge Nitrogen gas into the chiller up to about 49 kPa. d-8) Perform leak test by soap solution. d-9) Discharge nitrogen gas. Perform purging. When the inside pressure decreases about -50kPa, charge the LiBr solution from the service valve (SV4). d-10) Continue purging until the pressure in the chiller goes down to 1.3 kPa absolute. d-11) Run the chiller with about 50% input and perform air purging from the chiller for 1 hour. d-12) If there are no- abnormality, the chiller can be run on normal operation. 102 e) Replacement of the sight glass on the high temp. generator e-1) Charge Nitrogen gas into the chiller up to about 30 kPa. (Refer to "6-11. Method of charging Nitrogen gas") e-2) Discharge LiBr solution from the service valve (SV8) until the solution level falls to the sight glass bottom. e-3) Discharge Nitrogen gas. (Refer to "6-12. Method of discharging Nitrogen gas") e-4) Remove 6 bolt for the sight glass and remove the sight glass and gasket. e-5) Clean the surface of the sight glass flange by dry cloth. e-6) Put new sight glass and gasket. Tighten bolts uniformly. (Gasket is one side only. Carefully tighten bolts.) e-7) Charge Nitrogen gas into the chiller up to about 49 kPa. e-8) Perform leak test by soap solution. e-9) Discharge nitrogen gas. Perform purging. When the inside pressure decreases about -50kPa, charge the LiBr solution from the service valve (SV4). e-10) Continue purging until the pressure in the chiller goes down to 1.3 kPa absolute. e-11) Run the chiller with about 50% input and perform air purging from the chiller for 1 hour. e-12) If there are no- abnormality, the chiller can be run on normal operation. Gasket (T/# 9090-OR) Apply Teflon sealant (T/# 9400) a) Instrument a-1) Adjustable wrenches a-2) Vacuum rubber hose with copper tube a-3) Nitrogen gas a-4) Hose for nitrogen gas a-5) Regulator for nitrogen gas a-6) Torque wrench Upper tube (4) Rupture disk This instruction describes the procedure to replace a rupture disk. b) Procedure Flanges & bolts Rupture disk b-1) Charge Nitrogen gas into the chiller up to assembly about 9.8 kPa. Fig. 6-5 b-2) Remove 4 bolts for flanges. Hold down b-3) Carefully remove the rupture disk assembly. Cap screw b-4) Remove the cap screws and disassembly the rupture disk assembly. Then take out the rupture disk. b-5) Put new rupture disk into base and the hold down and tighten Rupture disk them uniformly by the cap screws. Flow Tightening torque : 2 inch 30 Nm (22 ft lbs) Tightening torque : 3 inch 35 Nm (26 ft lbs) At this time, do not make a mistake of rupture disk direction. Cap screw b-6) Put the rupture disk assembly and gaskets with Teflon sealant Base into the flanges, and tighten them uniformly by the bolts. Fig. 6-6 Rupture disk assembly Tightening torque : 2 inch 70 Nm (52 ft lbs) Tightening torque : 3 inch 75 Nm (55 ft lbs) b-7) Charge Nitrogen gas into the chiller up to about 49 kPa. b-8) Perform leak test by soap solution. b-9) Discharge nitrogen gas. b-10) Perform purging until the pressure in the chiller goes down to 1.3 kPa absolute. b-11) Run the chiller with about 50% input and perform air purging from the chiller for 1 hour. b-12) If there are no- abnormality, the chiller can be run on normal operation. 103 (5) Palladium cell & heater This instruction describes the procedure to replace an palladium cell and heater. a) Instrument a-1) Screw driver a-2) Torque wrench a-3) Adjustable wrenches a-4) Fork terminals a-5) Heat resistance tube Fig. 6-7 Palladium cell assembly with heater b) Procedure b-1) Be sure to confirm that the main breaker (MCBM) is turned OFF. b-2) Close B valve tightly. b-3) Open and remove the palladium cell cover. b-4) Remove the heater wire screws in the connection box and remove the heat resistance tube. b-5) Remove the assembling spring and bark the adhesive tape. Then disassemble the insulations. b-6) Loosen two screws fixing the heater and take out the hater. b-7) Loosen the screw fixing the case to the mounting and take out the case. b-8) Remove the flare nut and the palladium cell. b-9) Put new palladium cell. Tighten the flare nut by the torque wrench with 59-68 Nm (522-601 lbf inch). Note : Do not touch the palladium cell by fingers directory, use clean gloves. b-10) Perform leak test by the bubble test from SV9 (Purge tank service valve) Leak rate shall be 0cc per 10 minutes. b-11) Insert the case to the mounting with palladium cell and fix them by the screw. b-12) Insert new heater into the case and fix them by the screws. b-13) Insert the heater wires into the heat resistance tube. b-14) Put the fork terminals to the heater wires and the connect the wires with fork terminals to the originals terminal positions. Then put the connection box cover. b-15) Assemble the palladium cell cover. Adhesive tape Assembling spring Insulation Case Heater Palladium cell Fig. 6-8 104 Fig. 6-9 Palladium cell Case Heater Palladium cell Flare nut Mounting for palladium cell welded on purge tank Holes of screw Fig. 6-10 105 6-3. Method of absorbent solution (LiBr) analyses This instruction described to procedure for analyses of absorbent solution. (1) Notice for analyses a) The time of analyses a-1) In case of commercial use for air conditioning (about 4000 hours operation per year), the analyses should be conducted twice per year. a-2) In case of continuously operation such as process use the analyses should be conducted four times per year. b) Sampling solution and sampling position b-1) Sampling solutio : Diluted absorbent solution b-2) Sampling positio : The service valve (SV4) at discharge pipe of the absorbent pump c) Sampling quantity Sample the absorbent solution of 100 cc twice. First sampling solution shall be abandoned. Second sampling solution shall be used for analyses. d) Sample the absorbent solution during operation of the absorbent pump. (2) Analyses items a) Concentration of inhibitor (Lithium Molybdate : Li2MoO4) b) Alkalinity (Neutralization analysis) c) All copper content and all iron content (3) Instruments a) Solution sampling tool b) Bottle for solution with a cap (100 cc) c) Pipette with scale d) Beaker (100 cc.) e) Burette] f) Syringe g) Phenolphthalein solution h) One-tenth normal Hydrochloric acid solution (HCl) i) 50% Hydrochloric acid solution (HCl) j) Aluminum nitrate (Al(NO3)3 9H2O) Aluminum nitrate is crystal. Therefore, making aluminum nitrate solution shall be required. The method of making it is as follows. Put 250 g of aluminum nitrate unto a bottle and pure water into the bottle until total volume becomes 1 liter, and then mix them. k) Pure water (4) Sampling of the absorbent solution a) Remove the absorbent solution at the service valve (SV4) during operation of the absorbent pump by the sampling tool. b) Pour the absorbent solution to the bottle from the sampling tool. 106 (5) Measurement of concentration of inhibitor (Lithium Molybdate : Li2MoO4) Standard concentration of inhibitor : 50 - 150 ppm a) Stand the bottle for about 24 hours. After 24 hours, most solids in the absorbent solution accumulates at the bottom of the bottle. b) Collect 5 milli-litter of the absorbent solution from the top of the bottle by a pipette, and then pour it into a beaker. c) Add 4 milli-litter of the aluminum nitrate solution and 1 milli-litter of 50 % hydrochloric acid solution into another beaker, and mix tem. d) Add 1 milli-litter of the solution made in the item c) into the beaker by another pipette. e) Pour 94 milli-litter of pure water into the beaker by the burette. The above procedure is to make solution for analysis. And its volume is 100 milli-litter. This means that the absorbent solution is diluted to 1/20. f) In order to measure concentration of Lithium Molybdate, "Atomic absorption spectro chemical analysis" must be required. There is no-way to simply measure it. Therefore, this check can not be done at an site. It is preferred to request the analysis to an official organization or an analysis company. g) If concentration value measured is less than its standard, add inhibitor in accordance with " Method of adjusting inhibitor content and alkali". (6) Measurement of alkalinity (Neutralization analysis) Standard of the alkalinity : 0.03 N - 0.07 N (P Alkalinity) a) Stand the bottle for about 24 hours. After 24 hours, most solids in the absorbent solution accumulates at the bottom of the bottle. b) Collect 10 milli-litter of the absorbent solution from the top of the bottle by a pipette, and the pour it into a beaker. c) Pour 50 milli-litter of pure water into the beaker by the burette. d) Add Phenolphthalein (2 -3 drops) into the beaker by the syringe. The solution is colored to pink. The above procedure is to make solution for analysis. e) Add one-tenth normal Hydrochloric acid solution little by little into the solution by a burette until its color becomes colorless. f) Calculate the alkalinity according to the following formula. N = A X 0.01 where N : Alkalinity A : Quantity of Hydrochloric acid solution added (milli-litter) g) The standard of adjustment of the alkalinity g-1) Alkalinity is 0.03 N - 0.07 N No addition is required. g-2) Alkalinity is less than 0.03 N Add LiOH g-3) Alkalinity is beyond 0.07 N Add HBr Remark : In case of absorbent with Li2MoO4 as inhibitor, its alkalinity reduces as compared with initial value of the alkalinity in proportion to operation hours of the chiller. 107 (7) Analyses of all copper content and all iron content Limitation of the all copper content : 250 ppm max. Limitation of the all iron content : 250 ppm max. a) Shake the bottle before collecting the absorbent solution. b) Collect 1 milli-litter of the absorbent solution from the top of the bottle by the pipette, and then pure it into a beaker. c) Add 1 milli-litter of one-tenth normal Hydrochloric acid solution. Into the beaker by another pipette. d) After a few hours, pour 98 milli-litter of pure water into the beaker by a burette. The above procedure is to make solution for analysis. And its volume is 100 milli-litter. This means that the absorbent solution is diluted to 1/100. e) In order to measure concentrations of the all copper and iron, "Atomic absorption spectro chemical analysis" must be required as well as the method of the measurement of inhibitor. f) If the all copper content and all iron content are beyond their limitation, all absorbent solution charged in the chiller shall be filtered. (8) Notes a) In case that the absorbent solution crystallizes, melt it first and then perform the analyses. b) In case of the analyses of the all copper and the all iron, wait for a while after hydrochloric acid solution is added. Notice for all iron & all copper If these value is beyond the limitations, it means that there is a leakage. In this case, the leak test shall be performed and repair it as soon as possible. After that, perform filtration of all absorbent solution. Then Analyze them again. 108 6-4. Method of adjusting inhibitor content and alkalinity (1) Method of adding inhibitor This instruction describes the procedure to add inhibitor. a) Instruments a-1) Inhibitor : Li2MoO4 H2O (20wt% solution) a-2) Pure water a-3) Container a-4) Vacuum rubber hose a-5) Hose band a-6) Pliers a-7) Wrench a-8) Rubber gloves b) Target value of inhibitor concentration : 150 ppm Additional volume of the inhibitor is calculated in accordance with the following formula. 150 ppm - X ppm x 0.465 x A = D 100 where X : Measured value of inhibitor concentration (ppm) A : Initial charge amount of absorbent solution D : Required volume of inhibitor (cc) For example X = 40 ppm Model : TSA-16LJ-24 A = 1,070 kg 150 ppm - 40 ppm 100 x 0.465 x 1,070 = 547 cc Table 6-1 Initial charge LiBr solution in the factory Absorbent solution(50wt%) Model TSA-16NK-** kg lbs 510 1,125 11 1,477 670 12 1,698 770 13 1,940 880 21 2,470 1,120 22 3,175 1,440 31 3,374 1,530 32 3,682 1,670 41 3,859 1,750 42 4,454 2,020 51 4,917 2,230 52 5,402 2,450 53 6,262 2,840 61 7,034 3,190 62 7,629 3,460 63 9,459 4,290 71 10,540 4,780 72 12,238 5,550 81 109 c) Procedure c-1) In order to remove air in the rubber hose, pour pure water into the hose as shown in Fig. 6-12. c-2) Connect the vacuum rubber hose to the service valve (SV3) provided on the refrigerant pump discharge and fix it by a hose band as shown in Fig. 6-11. Sampling service valve(SV3) Copper tube Solution container Refrigerant pump Vacuum rubber hose Copper tube Vacuum rubber hose Inhibitor Filled with pure water Fig. 6-11 Fig. 6-12 c-3) Pour inhibitor added into the container. c-4) Insert a copper tube into the container. c-5) perform purging from the chiller. c-6) Open the service valve (SV3) c-7) When inhibitor starts being sucked into the chiller, watch carefully to ensure that air does not leak in. c-8) Close the service valve (SV3) after charging the inhibitor. c-9) Remove the vacuum rubber hose. c-10) Wash the mouth of the service valve with water and put the bonnet and flare nut. Then place the cap of the service valve after confirming the packing inside. c-11) Wash all instruments with water. c-12) Perform refrigerant blow down after completion of the work, and run the chiller in order to circulate the inhibitor in the inside of chiller. c-13) Continue the purging at least 30 minutes after completion of this work. d) Notes d-1) Be sure to perform this work during operation of the chiller, and be sure to carry out purging from the chiller during this work. d-2) Wear rubber gloves while this work. d-3) Thoroughly wash off any inhibitor which gets on hand, skin and clothes. Take care to prevent inhibitor entering mouth and eyes. d-4) Do not spill inhibitor on a floor and do not throe it in a drain. 110 (2) Method of adding alkali This instruction describes the procedure to add Alkali (LiOH) in case that alkalinity is less than 0.03 N. a) Instruments a-1) Alkali : LiOH (powder) a-2) Pure water a-3) Container a-4) Vacuum rubber hose a-5) Hose band 6) Pliers 7) Wrench 8) Rubber gloves 9) Mask b) Target value of alkalinity : 0.07 N Additional volume of LiOH is calculated in accordance with the following formula. D = 28.6 x (0.07 -X) x A where X : Measured value of alkalinity (N) A : Initial charge amount of absorbent solution (see Table *-*) D : Required volume of alkali (g) For example X = 0.01 N Model : TSA-16LJ-24 A = 1,070 kg 28.6 x (0.07 - 0.01) x 1,070 = 1,836 (g) c) Procedure c-1) In order to remove air in the rubber hose, pour pure water into the hose as shown in Fig. 6-12. c-2) Connect the vacuum rubber hose to the service valve (SV6) provided for concentrated absorbent and fix it by a hose band as shown in Fig. 6-13. c-3) Put the alkali added into the container and melt it with pure water. c-4) Insert the copper tube into the container. c-5) Perform purging from the chiller. c-6) Open the service valve (SV6). c-7) when the alkali solution starts being sucked into the chiller, watch carefully to ensure that air does not leak in. c-8) Close the service valve after charging the alkali solution. c-9) Remove the vacuum rubber hose and wash the mouth of the service valve with water. Then put the bonnet and flare nut. And place the cap of the service valve after confirming the packing inside. c-10) wash all instrument with water. c-11) Run the chiller in order to circulate the alkali in the inside of the chiller. c-12) Continue the purging at least 30 minutes after completion of the work. d) Notes d-1) Be sure to perform this work during operation of the chiller, Sampling and be sure to carry out purging from the chiller during service valve(SV6) this work. Copper tube d-2) Be sure to check the alkalinity again after this work. Solution Vacuum d-3) Wear rubber gloves while this work. container rubber hose d-4) Thoroughly wash off any alkali which gets on hand, Alkali solution skin and clothes. Take care to prevent alkali entering mouth and eyes. Fig. 6-13 d-5) Do not spill alkali on a floor and do not throe it in a drain. d-6) Pay attention not to suck in any powder of LiOH during this work. Heat exchanger 111 (3) Method of adding Acid This instruction describes the procedure to add Acid (HBr) in case that alkalinity is 0.07 N or above. a) Instruments a-1) Acid : HBr (concentration : 47 %) a-2) Pure water a-3) Container a-4) Vacuum rubber hose x 2 pieces a-5) Hose band x 2 pieces a-6) Pliers a-7) Wrench a-8) Rubber gloves a-9) Mask a-10) PH test paper Diluted absorbent pipe Vacuum rubber hose Vacuum rubber hose SV4:Open SV4:Close SV6:Close Solution container Diluted absorbent pipe SV6:Open Heat exchanger Copper tube HBr + Absorbent Solution container Heat exchanger Copper tube HBr + Absorbent Fig. 6-14 b) Target value of alkalinity : 0.03 N Additional volume of HBr is calculated in accordance with the following formula. D = 79.2 x (X -0.03) x A where X : Measured value of alkalinity (N) A : Initial charge amount of absorbent solution (see Table 6-1) D : Required volume of acid (milli-litter) For example X = 0.09 N Model : TSA-16LJ-24 A = 1,070 kg 79.2 x (0.09 - 0.03) x 1,070 = 5,085 (milli-litter) c) Procedure c-1) In order to remove air in the rubber hose, pour pure water into the hose as shown in Fig. 6-12. c-2) Connect the vacuum rubber hose to the service valve (SV6) provided for concentrated absorbent and fix it by a hose band as shown in Fig. 6-13. c-3) Connect another vacuum rubber hose to the service valve (SV4) and fix it with a hose band. c-4) Insert two copper tubes into the container. c-5) Perform purging from the chiller. c-6) Open the service valve (SV4). c-7) Remove about 50 litters of diluted absorbent solution from the service valve (SV4) into the container when the absorbent pump is running. c-8) Close the service valve (SV4) after 50 litters of the absorbent accumulates in the container. c-9) Pour HBr little by little into the absorbent removed. At this time check PH value of the absorbent by the PH test paper. c-10) Stop to pour HBr when PH value of the absorbent has become 7 to 6. c-11) Open the service valve (SV6). c-12) When the absorbent starts being sucked into the chiller, watch carefully to ensure that air does not leak in. c-13) Close the service valve(SV6) after the absorbent in the container empties. c-14) Repeat item 6) thru item 13) until required amount of HBr is charged into the chiller. c-15) After completion to charge required amount of HBr, confirm that SV4 and SV6 are fully closed. c-16) Remove the vacuum rubber hoses and wash mouths of the service valves with water and put bonnets and flare nuts to the service valves. c-17) Place caps of the service valves after confirming the packing inside. c-18) Wash all instrument with water. c-19) Continue the purging at least 30 minutes after completion of the work. 112 d) Notes d-1) Be sure to perform this work during operation of Chiller/Heater. d-2) Be sure to check again the alkalinity after this work. d-3) Wear rubber gloves and a mask during this work. d-4) Thoroughly wash off any HBr which gets on clothes. Pay attention to handle HBr. Because HBr is very strong acid. d-5) Do not spill HBr on a floor and do not throw it in a drain. d-6) There may be case that gas is generated when HBr is mixed with absorbent. Pay attention not to inhale the gas. 113 6-5. Method of charging solution This instruction describes the procedure of charging absorbent and refrigerant into Chiller. (1) Equipment use a) Solution container (for absorbent and refrigerant) b) Vacuum rubber hose with copper tube c) Hose band d) Pliers Sampling service valve Vacuum rubber hose Copper tube Solution Lift up slightly container (2) Procedure a) Prepare the solution containers. b) Operate a purge pump and perform the purging from the chiller. c) Connect the vacuum rubber hose to the service valve where solution is charged and fix it with the hose band. d) Insert the copper tube of the vacuum rubber hose into the container. (Keep slightly high from the bottom of the container as shown in Fig. 6-15.) Fig. 6-15 e) Open the service valve. f) When the solution starts being sucked in to the chiller, watch carefully to ensure that air does not leak in. g) Before the container becomes empty, tilt it so that air does not enter into the chiller as shown in Fig.6-16. h) When the container becomes almost empty, bend the vacuum rubber hose by your hands to ensure that air does not leak in as shown in Fig.6-17, and quickly insert the copper tubes in the next container. Vacuum rubber hose Bending Solution container Fig. 6-16 Fig. 6-17 i) Repeat item f) to h) until required charging amount solution has been charged. j) After completion, close the service valve at once. k) Remove the vacuum rubber hose from the service valve and wash the mouth of the service valve with water, then put the bonnet and flare nut. And put the cap of service valve. l) wash the vacuum rubber hose, etc. with water m) Continue air purging at least 30 minutes after completion of this work. (3) Precautions a) During this work, do not spill the solution. b) Because of high vacuum condition inside the chiller, take case to ensure that air does not leak into the chiller during this work. c) Carefully wash the vacuum rubber hose used before this work with water so as to prevent dire ingress. d) Wear rubber gloves. Do not handle tools pr solution with bare hands. e) Thoroughly wash off any absorbent which gets on hands, skin or clothes. Take care to prevent absorbent entering eyes or mouth. f) If absorbent spills on metal plates, etc., thoroughly wash off with water. 114 6-6. How to perform de-crystallization Cause of crystallization Crystallization is occurred under complex conditions described blow. However there is few cases that No.3 and No.4 factors causes crystallization by suitable periodic maintenance. Usually, crystallization is occurred by No.1 and No.2 factors. No.1 factor : Too low cooling water inlet temperature No.2 factor : Insufficient vacuum condition (bad vacuum condition) No.3 factor : Over fuel input No.4 factor : Insufficient absorbent flow rate Probable location of crystallization Crystallization is occurred mostly at concentrated absorbent in the low temp. heat exchanger. If the crystallizationoccurs, the following symptoms are observed. Therefore, de-crystallization procedure at this portion is explained. 1) Chilled water outlet temperature does not go down. 2) The temperature of concentrated solution over-flow pipe increases as the pipe can not be touched. 3) The temperature of concentrated solution outlet of low temp. heat exchanger falls as the pipe can be touched. 4) Diluted solution temperature rises (more than 40 deg.C / 104 deg.F) Outline of de-crystallization Crystallization generating at the outlet of concentrated solution side in the low temp. heat exchanger is melted by means of approximate 60 deg.C (140 deg.F) of high temperature diluted solution. This high temperature cooling water is made by the operating condition with low fuel input and without cooling water. (1) De-crystallization procedure a) Close compulsorily the fuel control valve by service mode. 9 0. 0 SET 2 sec. SET + C - 2 sec. C H G S = t E n. P 2 times 5 times 1 0 0. 0 r A n K u P S P E C SET 2 sec. 0 b) Operation mode of the refrigerant pump to "ON" by service mode. 9 0. 0 1 time SET + 2 sec. r E F - P C H G S = SET 2 sec. Select "ON" O N SET 2 sec. P u r G E A u t o O F F O N Push SET O F F Push SET Select "OFF" c) Open the refrigerant blow valve and perform blow down. d) Operation mode of the refrigerant pump to "OFF" by service mode. e) Stop Chiller by "STOP" key on the operation board. f) Turn off the electric power supply of cooling water pump and cooling tower fan. 115 g) Open the control panel door and jumper terminals of cooling water pump interlock(52CO), chilled water interlock(52CH) and chilled water flow switch (69CH). h) Select the operation mode to "LOCAL". Then run Chiller. i) Perform de-crystallization by the diluted solution discharged from #1 absorbent pump at 50 - 60 deg.C (122 - 140 deg.F) with adjusting fuel control valve opening by "rAnKuP" setting and switching ON/OFF of the cooling and chilled water pumps. *Be sure not to exceed atmospheric pressure in the generator during this work. *Working time : 2 - 3 hours (This is an common value. The working time should be extended if necessary.) *If the crystallization is very strong, conduct followings together with above work. i-1) Charge pure water (if possible, use hot water) from service valve (SV6). i-2) Heat the crystallization portion by gas or oil burner. j) Check if de-crystallization is successful or not by the followings. *No-flow of concentrated solution in the overflow pipe is confirmed. (Temperature of the overflow pipe falls) *Fluid level in absorber (bottom of the lower shell) raises and #1 absorbent pump pressure increases. *The temperature of concentrated solution outlet of the high temp. heat exchanger becomes warm. k) Stop Chiller. After dilution operation, Chiller/Heater and other equipments are shut-down completely. l) Remove the jumper wire connected in item g) m) Return the operation mode of the refrigerant pump to "AUTO" by service mode. 9 0. 0 1 time SET + 2 sec. r E F - P C H G S = SET 2 sec. Select "AUTO" SET 2 sec. A u t o O F F O N P u r G E Push SET n) Return "rAnKuP" setting to"100". 9 0. 0 SET 2 sec. 2 0. 0 (Preset value) SET + C - 2 sec. t E n. P C H G S = 5 times 1 2 times r A n K u P S P E C SET 2 sec. 0 0. 0 During de-crystallization work, this value is changed approximate 0 - 50 in order that the dilution solution temperature is kept between 50 deg.C (122 deg.F) and 60 deg.C(140 deg.F) (2) After de-crystallization a) Locate and remove causes of the crystallization. b) Run Chiller and perform normal operation. *Fluid level c) Check operating conditions of Chiller for a while after restart, and check if crystallization occurs again or not. *Temperature *Pressure d) In case that a lot of water is added to do de-crystallization work, the water shall be removed from Chiller. However, in case of small amount water, water removing is not necessary. *Method of removing out water : The water (refrigerant) can be removed from the service valve (SV3) by using a small pump because the discharge pressure of the refrigerant pump is vacuum. Added water amount and removed water amount shall be equal. Record both water quantity. Check removed water specific gravity. The gravity shall be less than 1.01 (concentration :Less than 1.5%) 116 Reference : Chilled water flow and cooling water flow is necessary or not at de-crystallization Chilled water De-crystallization is to melt the crystallization occurred in the solution heat exchanger concentrated solution side by raising the diluted solution temperature by heat from driving heat source without the chilled water and the cooling water flow. It is necessary to confirm chilled water temperature during de-crystallization, and once the chilled water temperature reached 60 degree C, the chilled water pump is operated for a short time in order to prevent influence by thermal expansion to the evaporator tubes. The required running time of the chilled water pump is different depending on Chiller/Heater model, but in usual case it is around for ten several seconds to thirty seconds. The judgment to stop the chilled water pump is that the chilled water pump should be topped when chilled water box temperature becomes around 30 deg.C. In addition, the information that warm air will often blow to air conditioning area during de-crystallization work should be informed to a customer. Because, water around 60 degree C. goes to air handling units when the chilled water pump is operated. Cooling water Same as above, it is necessary to operate the cooling water pump for a short time when cooling water temperature becomes around 60 degree C. Operating time is the same as chilled water pump. In the case of cooling water, heat-resistant temperature of cooling tower filler must be confirmed from a customer beforehand. Because if the heat resistant temperature of the filler is lower than 60 deg.C, the filler may have damages by the cooling water around 60 deg.C when the cooling water pump is operated. In this case, the cooling water pump must be operated with lower temperature of the heat-resistant temperature of the filler. Even if heat-resistance temperature of the filler is low, if there is a bypass piping for the cooling tower, it is possible to conduct de-crystallization work with the cooling water of around 60 deg.C by using the bypass piping. As mentioned above, discussion with a customer should be conducted at scheduling de-crystallization work in order to avoid any trouble for auxiliary equipment. 117 6-7. Reference material of tube cleaning This instruction describes the method of tube cleaning as reference only. (1) Cleaning procedure Check scale condition Check scale adhesion condition Sample the scale Check prior to cleaning a) determine proper cleaning agent *Perform dissolving test of the scale using various cleaning agents. *determine a drainage way. Cautions a-1) Dispose, drain, and/or treat west water properly. a-2) Do not drain a hydrogen peroxide based cleaning agent into a pacifying cistern or activate sludge treatment system. a-3) Refer cleaning using a fluoride based cleaning agent to a professional. Preparation b) Determine the cleaning method. *Determine cleaning area, amount of water and chemicals. *Prepare instruments, chemicals and protective tools. Instrument It is recommended to use both chemical cleaning and brushing cleaning for tube cleaning. Make a reversible flow direction circuit Absorption chiller Cooling tower Channel A Channel B Chemical supply tank Neutralization tank Fig. 6-18 118 (2) Chemical cleaning procedure Scale / Slime Chemical cleaning Alkali agent Neutralization Drainage Cleaning with water Measure the amount of an alkali agent for neutralization. Conduct the neutralization for 30 to 60 minutes for drain out the chemical. pH value of the solution drained shall be 6 - 8. Flow the water through the channel A and B. Repeat 3 to 5 times Drainage Visual checking Check pH value and drained water transparency. Check if brush cleaning is required, Brush cleaning Visual checking Water cleaning Cooling water system is filled with new water Circulate water throughout entire cooling water system, then clean using water by continuous blowing for 2 hours or more. (Channel B) *Use alkaline water (pH 8 - 9) for rust prevention. *If there is a possibility of freezing in winter season, use anti-freeze solution having anti-corrosion agent. (3) Determining a chemical agent for cleaning (Dissolving test) Collect the scale to be cleaned. Perform the dissolving test using an available chemical agent. Determine the most suitable chemical agent. Chemical agent A B Bad Fig. 6-19 Scale C Good Put the scale into the chemical agent with the specified concentration. Then observe the condition of bubbles and the dissolving condition of the scale. The more bubbles are emitted and more scale is dissolved, the more effective the cleaning chemical agent is. The qualification must be necessary for handling of the fluoride based chemical agent. The chemical is extremely hazardous to both humans and equipments. Therefore, If the chemical is required, the professional shall be required. 119 (4) Notice for draining waste water *Sewerage : Drain waste water after conducting proper treatment *Rivers / Lakes / Swamps / Farm land / Fish farm : Do not drain *Waste water treatment facilities : The hydrogen based waste water can not be drained into a pacifying cistern or activate sludge treatment system. Waste water standard of public sewerage in Japan (Reference only) Items Standard Temperature Less than 45 deg.C (113 deg.F) Hydrogen ion concentration 5 < pH < 9 (5) Method a) Prepare water, chemical agent, neutralization agent and rust preventive. b) Confirm the area and circuit to be cleaned. c) Prepare protection tools (gloves / goggles / mask / etc.) d) Make the cleaning circuit around the pump as shown in Fig. 6-20 for reversible water flow. Inlet port or Drain port Connected with the chiller Connected with the chiller Pump Inlet port or Drain port Fig. 6-20 Use suitable capacity pump for circulating the chemical agent. The below table shows pumps as reference. Flow rate Total head Output 3 9.5 m (31 ft) 2.2 kW 3 6.5 m (21 ft) 0.4 kW 0.8 m /h (3.5 gpm) 0.2 m /h (0.9 gpm) (6) Others a) In case of the tube cleaning together with cooling tower, pay attention that a chemical cleaning agent does not splash out. b) For safety, prepare anti-chemical sheet on the working area. c) If cleaning work continues two or more days, fill the cleaning portion with clean water (ex. City water) at the end of daily work. 120 Table 6-2 Type of scale VS Cleaning chemical agent Type of scale : Iron rust scale Feature of scale Color : Red brown or black / Hard scale Suitable cleaning agent Hydrochloride acid type Neutralizing method Cautions Take the cleaning agent out of a chiller then neutralize using caustic soda. It can not be used for water heater. Ca.Mg.salt scale Feature of scale Color : Gray white / The scale is soft. It can be crashed into powder by fingers. When acid is added, bubbles are generated violently Suitable cleaning agent Neutralizing method Cautions Sulfamic acid type Take the cleaning agent out of a chiller then neutralize using caustic soda. As sulfamic acid solution will wither plants if it is drained as is, be sure to neutralize it before draining. Silicate scale Feature of scale Color : Gray white / The scale is very hard and can not be crashed into powder by fingers. Suitable cleaning agent Hydrofluoric acid type / Organic salt type Neutralizing method Cautions Take the cleaning agent out of a chiller then neutralize using slaked lime. The scale is not dissolved even if hydrochloric acid is added. A professional shall be required. Do not use an agent which contains ammonia as it may react with copper (ammonia fluoride). Slime Feature of scale Color : Green, Gray, Black, Brown , Yellowish / Extremely soft / Viscous matter Suitable cleaning agent Hydrogen peroxide type / Organic acid type Neutralizing method Cautions No need to neutralization, however clean with water sufficiently after cleaning. If the cooling water is acidly, do not use hydrogen peroxide type chemical agent. The hydrogen peroxide type waste water shall not be drained into a pacifying cistern or activated sludge treatment system. Slime & Iron scale coexist Feature of scale Color : Yellowish, Brown / Soft / Viscous matter Suitable cleaning agent Hydrogen peroxide type / Hydrochloric acid type Neutralizing method Cautions If hydrochloric acid type agent is used, neutralize it by using caustic soda. The cautions and prohibited items for cleaning of the scale where a variety of those same as those for the cleaning agents mentioned above. Iron & Silicate coexist Feature of scale Color : Yellowish, Brown / Somewhat soft Suitable cleaning agent Hydrochloric acid type + Hydrofluoric acid type Neutralizing method Cautions Take it out of the system, then neutralize it by using slaked lime. Same the above Silicate & Ca. Mg salt coexist Feature of scale Color : Grayish white / Very hard scale When hydrochloric acid is added, some bubbles are generated. Suitable cleaning agent Hydrofluoric acid type + Sulfamic acid type / Hydrofluoric acid type + Hydrochloric acid type Neutralizing method Cautions Take it out of the system, then neutralize it by using slaked lime. Same the above Scale where Iron & Ca. Mg salt coexist Feature of scale Reddish brown / Hard scale Suitable cleaning agent Hydrochloric acid type Neutralizing method Cautions Take it out of the system, then neutralize it by using slaked lime. Same the above 121 Table 6-3 Information for tube cleaning Holding water quantity Model Tube quantity Tube inner diameter Cooling water Chilled water Condenser Evaporator Abso. + Cond. Evaporator Tube length Abso. Cond. Evap. TSA16NK mm inch 11 2,066 81.3 357 137 12 3,086 121.5 304 13 3,086 121.5 21 Tubes Absorber mm inch mm inch mm inch Liter U.S.gal Liter U.S.gal 250 14.9 0.587 15.0 0.591 14.7 0.579 340 90 130 34 119 210 14.9 0.587 15.0 0.591 14.7 0.579 380 100 150 40 357 137 250 14.9 0.587 15.0 0.591 14.7 0.579 420 111 170 45 3,086 121.5 478 160 337 14.9 0.587 18.0 0.709 14.7 0.579 580 153 240 63 22 4,106 161.7 418 140 306 14.9 0.587 18.0 0.709 14.7 0.579 630 166 280 74 31 4,106 161.7 542 180 373 14.9 0.587 18.0 0.709 14.7 0.579 890 235 340 90 32 4,106 161.7 604 200 414 14.9 0.587 18.0 0.709 14.7 0.579 950 251 360 95 41 4,106 161.7 695 226 460 14.9 0.587 18.0 0.709 14.7 0.579 1110 293 460 122 42 4,106 161.7 791 251 560 14.9 0.587 18.0 0.709 14.7 0.579 1190 314 480 127 51 4,106 161.7 1,064 431 702 14.9 0.587 15.0 0.591 14.7 0.579 1870 494 650 172 52 4,648 183.0 1,064 431 702 14.9 0.587 15.0 0.591 14.7 0.579 2010 531 710 188 53 5,146 202.6 1,064 431 702 14.9 0.587 15.0 0.591 14.7 0.579 2140 565 770 203 61 4,648 183.0 1,381 579 911 14.9 0.587 15.0 0.591 14.7 0.579 2790 737 990 262 62 5,146 202.6 1,381 579 911 14.9 0.587 15.0 0.591 14.7 0.579 2960 782 1060 280 63 5,671 223.3 1,381 579 911 14.9 0.587 15.0 0.591 14.7 0.579 3140 830 1130 299 71 5,146 202.6 1,558 621 1,184 14.9 0.587 18.0 0.709 14.7 0.579 3670 970 1410 372 72 6,171 243.0 1,558 621 1,184 14.9 0.587 18.0 0.709 14.7 0.579 4110 1086 1610 425 81 6,171 243.0 1,846 715 1,368 14.9 0.587 18.0 0.709 14.7 0.579 4760 1257 1940 512 Inner shape of tubes Absorber tube Evaporator tube Condenser tube 43deg. Min.0.125mm Min.0.005inch OD :dia.16mm / dia.19mm dia.0.63inch / dia.0.748inch Groove Plane Plane Fig. 6-21 122 6-8. Solution and refrigerant sampling This instruction describes the procedure for sampling small amount of the absorbent solution. (1) Equipment use a) Sampling cylinder and attachments for service valve b) Vacuum rubber hose c) Pliers d) Vacuum gauge (0-1kPa (0-0.15psi)) (2) Precautions a) Because of high vacuum condition inside Chiller/Heater, take care to ensure that air never leak into Chiller/Heater during this work. b) Handle the vacuum valve carefully so as not to damage it. c) When solution (absorbent & refrigerant) is sampled at SV3, SV4 and SV6. Procedures at each service valve are the same manner. Position of service valves SV3, SV5, SV6 SV3 : Service valve mounted at the discharge pipe of the refrigerant pump To remove refrigerant SV4 : Service valve mounted at the discharge pipe of #1 absorbent pump To remove diluted absorbent solution SV6 : Service valve mounted at the outlet side of the low temp. heat exchanger shell To remove concentrated absorbent solution d) Pour solution sampled into another container. Do not spill/pour the solution to a sewage, etc.. (3) Procedure a) Confirm manual purge valves (V1, V2 and V3) to close. b) Remove a flare nut and a bonnet of SV1, and connect an attachment to the service valve. c) Remove a flare nut and a bonnet of SV4 where absorbent is sampled, and connect an attachment to the sampling service valve. d) Connect a vacuum rubber hose and a sampling cylinder to the attachment as shown in Fig 6-22. e) Run a purge pump and open up V1. f) Open SV1 and the vacuum valve. g) When the indication of the vacuum gauge becomes about 0.5kPa(0.07psi), close the vacuum valve. h) Remove the vacuum rubber hose from SV1, and connect it to SV4 as shown in Fig. 6-23. I) Open the vacuum valve. j) Open SV4. k) When the sampling cylinder is filled with absorbent, close SV4. l) Close the vacuum valve and remove vacuum rubber hose from SV4 service valve. m) Upon completion of this work, remove the attachment, and put the bonnets and flare nut. Also put the caps of both service valves after checking their gaskets. n) Stop the purge pump. o) Finally, wash all tools with water. 123 V2 Sampling service valve (SV3, SV4, SV6) V3 Vacuum rubber hose Attachment SV1 Vacuum rubber hose Attachment Vacuum valve V1 Vacuum valve Liquid trap Sampling cylinder Sampling cylinder Purge pump Fig. 6-23 Fig. 6-22 280(11") 54(2- 54(2-1/8") Sampling cylinder (Material : Acryl rosin) Fig. 6-24 Steel wire Rubber hose Valve Copper tube Attachment Rubber cup Flare nut Fig. 6-25 Flare nut 150(515/16") Copper tube Copper tube 150(5-15/16") Fig. 6-26 124 6-9. Measuring concentration This instruction describes the procedure to measure concentration of absorbent solution and refrigerant. (1) Equipment use a) Sampling cylinder b) Gravimeter Scale: 1.0-1.2 (for refrigerant) Scale: 1.4-1.6 (for diluted absorbent) Scale: 1.6-1.8 (for diluted and concentrated absorbent) c) Thermometer (2) Precautions a) Take care not to damage the gravimeter and thermometer. b) Be careful not to spill any solution. Do not fill the sampling cylinder any more than about 80%. c) Quickly perform this measurement. 1 77 64 63 62 Concentration Specific gravity (3) Procedure a) Fill the sampling cylinder to about 80% with solution to be measured. b) Vertically keep the sampling cylinder, and insert a gravimeter into the sampling cylinder. c) When the gravimeter stops moving up and down, read the scale of the gravimeter which shows gravity of the solution. d) Remove the gravimeter and put it aside. Then insert the thermometer into the sampling cylinder and stir the solution thoroughly. e) When the temperature is stabilized, read the scale on the thermometer. f) Remove the thermometer and put it aside. g) Store the solution in another bottle. h) Using the concentration diagram of Lithium Bromide solution, read the concentration. I) Upon completion of measurement, wash the gravimeters, thermometer and sampling cylinder with water. And store them so that they are not damaged. Example: The horizontal axis represents temperature and the vertical axis represents specific gravity. The lines going down from left to right represent fixed concentrations. For example, if the specific gravity is 1.77 and the temperature is 45oC(113oF), the concentration given by the point of intersection of lines projected from these values will be 63%, as shown in Fig. 6-27. 45oC(113oF) Temperature Fig. 6-27 125 83 82 81 1.80 79 78 77 76 75 74 73 72 71 1.70 69 68 67 66 65 64 63 62 61 1.60 59 58 57 56 55 54 53 52 51 1.50 49 48 47 46 45 44 43 42 41 1.40 1.15 14 13 12 11 1.10 9 8 7 6 5 4 3 2 1.00 99 98 97 96 95 50 10 68 20 86 30 104 40 122 50 140 60 158 70 176 80 194 90 212 oF 100 oC 66 65 64 63 62 61 60 59 58 57 56 Concentration (%) Specific gravity Temperature 32 0 55 54 53 52 51 50 49 48 47 46 45 22 20 18 16 14 12 10 8 6 4 0 10 20 30 40 50 Fig 6-28 60 70 80 90 100 oC 2 1 0 126 6-10. Method of charging Nitrogen gas This instruction describes the procedure to charge Nitrogen gas (hereinafter N2 Gas) into Chiller (1) Equipment use Table 6-4 Inner Volume a) N2 gas : required volume (See the table) TSA-16NK (Liter) (Gal) c) Pressure proof hose 11 1,850 7,000 d) Pliers 12 2,840 10,750 e) Valve key for N2 gas cylinder 13 2,780 10,520 21 3,470 13,130 22 4,840 18,320 The charged pressure can be measured by a generator pressure gauge. 31 5,710 21,610 a) For storage of a chiller : 19.6 kPa 32 5,740 21,730 b) For leak test : 49 kPa 41 7,340 27,780 d) At replacement of parts : 9.8 kPa 42 7,360 27,860 51 9,420 35,650 52 10,790 40,840 53 11,970 45,310 61 13,450 50,910 b) Connect a pressure proof hose to the outlet of the pressure regulator, 62 15,290 57,870 then slightly open a valve on the top of the cylinder in order to purge 63 16,860 63,820 air being in the hose. After purging, close the valve. 71 18,960 71,760 c) Connect the other end of the hose to SV1, and fix it with a hose band. 72 22,700 85,920 d) Check that V1, V2, V3 and SV1 are fully closed. 81 26,460 100,150 b) Pressure regulator (2) Standard (3) Procedure a) Prepare N2 gas cylinders and attach a pressure regulator to a N2 gas cylinder. e) Open V2 and then open SV1. f) Using the pressure regulator, charge a small amount of N2 gas into Chiller/Heater. g) Watch the generator pressure gauge during charging N2 gas. When the pressure in Chiller/Heater reaches to required pressure, close SV1, and then close the valve of the N2 gas cylinder. h) Remove the hose from SV1 and put the cap to SV1. i) Remove the pressure regulator. V2 V3 (4) Precautions a) Since the pressure in the N2 gas cylinder is very high (Commonly 15 Mpa), pay attention to handle it. b) Do not suddenly rise the primary and/or secondary SV1 V1 pressure of the pressure regulator. (Secondary pressure shall be maximum 0.5 Mpa.) Liquid trap c) Fix N2 Gas cylinder so that it does not fall over. d) Be sure not to open V1 and V3 during this work. Purge pump Fig. 6-29 127 6-10. Method of charging Nitrogen gas This instruction describes the procedure to charge Nitrogen gas (hereinafter N2 Gas) into Chiller (1) Equipment use Table 6-4 Inner Volume a) N2 gas : required volume (See the table) TSA-16NK (Liter) (Gal) c) Pressure proof hose 11 1,850 7,000 d) Pliers 12 2,840 10,750 e) Valve key for N2 gas cylinder 13 2,780 10,520 21 3,470 13,130 22 4,840 18,320 The charged pressure can be measured by a generator pressure gauge. 31 5,710 21,610 a) For storage of a chiller : 19.6 kPa 32 5,740 21,730 b) For leak test : 49 kPa 41 7,340 27,780 d) At replacement of parts : 9.8 kPa 42 7,360 27,860 51 9,420 35,650 52 10,790 40,840 53 11,970 45,310 61 13,450 50,910 b) Connect a pressure proof hose to the outlet of the pressure regulator, 62 15,290 57,870 then slightly open a valve on the top of the cylinder in order to purge 63 16,860 63,820 air being in the hose. After purging, close the valve. 71 18,960 71,760 c) Connect the other end of the hose to SV1, and fix it with a hose band. 72 22,700 85,920 d) Check that V1, V2, V3 and SV1 are fully closed. 81 26,460 100,150 b) Pressure regulator (2) Standard (3) Procedure a) Prepare N2 gas cylinders and attach a pressure regulator to a N2 gas cylinder. e) Open V2 and then open SV1. f) Using the pressure regulator, charge a small amount of N2 gas into Chiller/Heater. g) Watch the generator pressure gauge during charging N2 gas. When the pressure in Chiller/Heater reaches to required pressure, close SV1, and then close the valve of the N2 gas cylinder. h) Remove the hose from SV1 and put the cap to SV1. i) Remove the pressure regulator. V2 V3 (4) Precautions a) Since the pressure in the N2 gas cylinder is very high (Commonly 15 Mpa), pay attention to handle it. b) Do not suddenly rise the primary and/or secondary SV1 V1 pressure of the pressure regulator. (Secondary pressure shall be maximum 0.5 Mpa.) Liquid trap c) Fix N2 Gas cylinder so that it does not fall over. d) Be sure not to open V1 and V3 during this work. Purge pump Fig. 6-29 127 6-11. Method of discharging Nitrogen gas This instruction describes the procedure to discharge Nitrogen gas (N2 Gas) from Chiller. (1) Equipment use a) Pliers (2) Standard The pressure in the chiller becomes atmospheric pressure (0MPa). (3) Procedure a) Check that V1, V2, V3 and SV1 are fully closed. b) Open V3. c) Remove a cap and flare nut of SV1 and open it. d) When the reading of the generator pressure gauge becomes atmospheric pressure (Mpa), close SV1. (4) Precautions a) Be sure to open V1 and V2 during this work. b) During this work, ventilate the machine room adequately. 6-12. Information of signals between Chiller & Steam control valve (1) Control valve signal to valve positioner Control panel of Chiller Valve positioner of Steam valve (Field supply) E 345 + 346 - CVP DC 4 - 20mA (2) Control valve signal to valve motor Control panel of Chiller Valve positioner of Steam valve (Field supply) E Open/close signal Feed back signal Open 342 Y 340 T 341 G 0A 3 344 2 Open 343 1 Close Close 128 6-13. Instruction of leak test (1) Purpose This instruction describes the procedure for pressurized leak test by Nitrogen gas (N 2 gas) for an absorption Chiller at the following cases. a) For field welding portions of multiple section shipping Chiller b) After replacement of parts furnished with vacuum side c) At suspicion of leakages on Chiller (2) Judgment In case that any bubbles can not be appeared on tested portions of Chiller, it can be judged that the Chiller does not have leakages. (3) Equipments & Tools a) N2 gas cylinder b) Pressure regulator c) Pressure proof hose. d) Oiler (for soapy solution) e) Soapy solution f) Flashlight (4) Flow-chart Charge N2 gas up to 30kPa Tightening up Check leakage with soapy solution NG Discharge N2 gas Repair leakage by welding OK Charge N2 gas up to 49kPa Tightening up Check leakage with soapy solution NG Discharge N2 gas Repair leakage by welding OK Discharge N2 gas Perform purging 129 (5) Procedure a) Confirm that V1, V2 and V3 are fully closed. b) Confirm that isolation valves for #1& #2 absorbent pumps and refrigerant pump are fully opened. c) Make the N2 gas charge line shown as Fig. 6-31. d) Pressurize Chiller up to 30kPa. (The pressure can be checked by the high temp. generator pressure gauge.) e) Close SV1 and the N2 gas cylinder valve. f) Check following suspicious portions of leakage by soapy solution. f-1) Field welding portions (for multiple section shipping Chiller) f-2) Sight glasses f-3) Flare joints f-4) High temp. generator solution level electrodes f-5) Flange connections (absorbent pumps, refrigerant pump, etc.) f-6) Caps of isolation valves, change-over valves, dampers and service valves g) If a leakage(s) is found out, tighten it (them). If a leakage(s) is found out at field welding, discharge N2 gas then repair the leakage portion(s) by welding. h) If no-leakage, rise the pressure up to 49 kPa and check again. I) If no-leakage, keep the pressure of 49 kPa for at least 12 hours then check again. j) After completion of the leak test, discharge N2 gas. N2 gas cylinder valve Pressure regulator Pressure proof hose N2 gas cylinder SV1 V1 Fig. 6-31 130 6-14. Instruction of inspection of purge pump The purge pump is supplied with Chiller/Heater, mounted, wired and piped. The initial charge of purge pump oil is shipped as an extra item with Chiller/Heater and should be added to a level just above the bottom of the sight glass. During purge pump operation, this level should rise to approximately 1/2 sight glass. If too much oil is added, it may cause oil to spill from the discharge port when it is first turned on. The purge pump also includes a ballast that can be opened slightly to limit the amount of condensed refrigerant from entering the pump and contaminating the oil. Allowing a small amount of ballast also tends to heat the purge pump oil and exhaust the moisture out of the oil. (1) Always replace the oil if it becomes contaminated or milky in color. (2) Confirm the pumps ability to draw a vacuum. The pump also should achieve of at least 0.5 kPa abs (0.07 psi abs). If this value can not be obtained, perform the followings. a) Replace the purge pump oil. b) Check the liquid trap for water. If condensed water or moisture is apparent then it will be necessary to operate the purge pump for 1/2 hour to evaporate the moisture. c) Check the unit purge line piping for leakage by bubble testing. (3) If the purge pump will not rotate or trips the thermal overload it will be necessary to remove the belt and and manually turn the pump by hand in an attempt to loosen the pump. (4) If the pump will not rotate be hand or will not attain an adequate vacuum after performing the above tasks it may be necessary to rebuild the purge pump. Important: When first starting the purge pump, it is critical to bump start the pump and check for proper rotation as shown by an arrow on the cover. The direction of the purge pump is an indicator of the directions of the other pumps on Chiller. If the rotational direction is incorrect, the phasing adjustment should be made at the power supply to the unit not to the purge pump wiring. Remark 1: While purging work is being conducted, continuous power supply shall be required. If power interruption happens during purging, close V1 immediately in order to prevent air leaking through the purge unit. Remark 2: During purging nitrogen work, ventilate the unit room sufficiently. Drain plug Liquid trap Exhaust gas port Oli charge port Sight glass Drain cock Gas ballast valve 6-32. Purge pump 131 6-15. Instruction of bubble test This instruction describes the procedure of measuring the quantity of non-condensables being purged from the chiller. The test consists of adapting a hose from the discharge port of the purge pump and collecting the discharge gasses in an inverted graduated cylinder under water. The graduated cylinder is first filled with water and inverted so that no air is contained in the cylinder. As the non-condensable gasses are discharged into the inverted cylinder the water column in the cylinder will drop as the water is being displaced. The quantity of non-condensable gasses can then be measured based on time and volume of water displacement. This test will be performed during initial evacuating of Chiller, after the again process, during routine maintenance, and to determine if an air leak is present. The most important maintenance item on an absorption chiller is to insure the unit vacuum condition is within acceptable limits. Chiller tightness can be checked by determining the rate at which non-condensable accumulate. Some non-condensables are normally generated within Chiller, but an air leak will be indicated if the accumulation rate increases. Bubble test during unit operation During routine maintenance the bubble test can be performed to gather the non-condensable gasses that have accumulated in the purge tank. The contents of the gasses can then checked to be air or hydrogen. Air---No odor. If the unit does not pass the bubble test it is possible that a leak has developed. Hydrogen gas---Place a match or lighter at the lip of the graduated cylinder before removing the cylinder from the water. If hydrogen is apparent, the gas will ignite and cause a popping sound. If hydrogen is present it is an indicator that hydrogen production is exceeding the capacity of the palladium cells and that the inhibitor is depleted and should be replaced. Care should be taken when performing this test. (1) Procedure a) Perform purging from Chiller/Heater until inner pressure reaches allowable degree of vacuum or less. Continue purging at least one hour. See Fig. 6-33. b) Connect the vacuum gauge to SV1 and open SV1. c) Confirm that attained vacuum of the purge pump is less than 0.5 kPa abs. (0.07 psi abs.). d) Remove the discharge port cap and put the attachment to the port. Furnish the vinyl hose to the attachment. See Fig. 6-34. e) Open V1 and close V2 and V3. f) Continue to run the purge pump for one minute. Then measure volume of bubbles. During this step, keep position of the vinyl hose within 10 mm in depth. If bubbles come out, check and tighten connections in the downstream from V2 and V3. If bubbles still come out, measure its volume collected for 10 minutes. g) Open V1 and V3 and close V2. Note : The gas ballast valve and the oil discharge cock shall be closed. h) Continuing operation of the purge pump under the above condition, measure volume of bubbles for 10 minutes. This measurement shall be repeated at least three times. During measurements, attained vacuum of the purge pump shall be kept below 0.5kPa abs. (0.07 psi abs.). i) The measured value in item 6) is as "A cc", in item 8) is as "B cc". Result of bubble test value = B - C (cc) j) After the bubble test, open the gas ballast valve and replace purge pump oil. 132 0.7 0.7 5 4.4 0.6 4 Inner pressure 0.5 3 0.4 0.3 2 0.2 1 0.1 0 0 0 10 32 50 20 30 70 90 40 deg.C 104 deg.F Ambient temperature Fig. 6-33 Allowable vacuum curve The degree of vacuum should be mentioned within the allowable range. As the pressure in Chiller is variable owning to the ambient temperature, check the measured pressure by using the curve. When ambient temperature is 30 deg.C(86 deg.F), 4.4kPa abs. (0.64 psi abs.) is read as an allowable vacuum. If pressure is over 4.4kPa abs. (0.64 psi abs.), perform purging. 3/8" Copper tube Flare nut Nipple (3/8") Bushing (1-1/4") Suction port Discharge port 10mm (13/32)" Graduated cylinder Vinyl hose Purge pump Bucket Water Fig. 6-34 Bubble test 133 6-16. Instruction of refrigerant blow down (1) The following cases, refrigerant blow down should be conducted. 1) After aging with evaporator tube outer surface cleaning for trial-run in cooling mode 2) Before initial cooling operation at every cooling season (2) Procedure 1) Make sure the refrigerant pump is running and also the solution level is visible through the sight glass of the evaporator. 2) Open the refrigerant blow valve. 3) When solution level becomes invisible, close the refrigerant blow valve tightly. 4) Repeat steps 1) thru 3) until the refrigerant concentration becomes less than 3%. Note If the high temp. generator temperature is more than approximately 130 deg.C thru 140 deg.C, do not fully open the refrigerant blow valve. There is a case that refrigerant contamination may occurs. If the high temp. generator temperature is beyond the temperature, slightly open the refrigerant blow valve to blow the refrigerant gradually. 6-17. Instruction of field insulation The followings are requirements to insulate Chiller. (1) Do not insulate Chiller until the leak testing procedures have been completed. (2) The type of insulation utilized on the hot surface must be sufficient so that outer skin temperatures meet local safety codes for personnel protection. (3) Use only noncombustible materials. (4) Do not insulate following portions. a) Motor of refrigerant pump b) Sight glasses c) Expansion door on high temp. generator d) Damper heads e) Service valves f) Change-over valve handles g) Sensors h) Any other portions described in Exhibit G in Installation manual (5) Allow accessibility through the insulation to water headers and a smoke tube cleaning window. (6) To mount insulating materials, use bonding agents, wires, and bands. Do not use screws, rivets or impact type stick pins. Remark : Because of the many different insulating materials available in our industry and local code requirements or regulations that must be complied with, it is impossible to specify the insulating material types to be utilized for a specific application. The selection and installation of the insulation should be addressed by experienced personnel knowledgeable in the local requirements and regulations of this field. 134 16-18. Instruction of function test This instruction described instructions for safety functions with their sensors. This test shall be conducted under the condition that #1 absorbent pump, #2 absorbent pump, the refrigerant pump and shall steam control valve be off. And also a chilled/hot water pump, a cooling water pump and a ventilation fan are stop. (1) Battery back-up Before conducting the test, the back-up battery for the microprocessor (CPU board) shall be ON. See Fig.6-35. This figure shows positions of BACKUP BATTERY and BACKUP SWITCH (SW3) provided on the CPU board. SW3 has been set OFF at the factory to avoid consumption of battery power. When the power is supplied to the electronic controller, "F-21 (CPU alarm)" or "F-23 (Time set alarm)" is displayed on the data display if SW3 is turned off. In this case, turn on SW3 first and then set time. Note 1 : If the back-up becomes empty, "F-21" or "F-23" is displayed. Replace it. Note 2: Model of the backup battery is CR-2025. The battery can do backup for approx. 4,000 hours. LABEL SW3 :Backup switch UP : ON DOWN : OFF Backup battery Procedure : Turn off SW3 - Remove the backup battery - Put new backup battery - Conduct time setting - Turn on SW3 Fig. 6-35 Positions of Backup switch (SW3) & Backup battery 135 (2) Preparation before function test Before performing the test, prepare the followings. a) Jumper the following terminals a-1) #170 - #120 52CH Chilled/hot water pump interlock a-2) #170 - #121 52CO Cooling water pump interlock a-3) #170 - #124 52F Ventilation fan interlock a-4) #140 - #173 69CH Chilled water flow switch b) Remove the wires of #1 absorbent pump (U1, V1, W1), #2 absorbent pump (U2, V2, W2) and the refrigerant pump (U3, V3, W3) at the terminals on each magnetic contactor. c) Change "Combustion interval" from "00 n." to "-- n.". See the page 53 in section. 6. (3) Procedure of each function test a) J-01 Chilled water low temp. alarm a-1) Provide 5 liter bucket filled with water and ice. a-2) Push RUN key. a-3) After RUN LED of #1 & #2 absorbent pump and refrigerant pump light up, dip the sensor (DT1) into the bucket. a-4) Confirm whether J-01 is indicated on the data display or not. a-5) Push STOP key. Return DT1 to its sensor port. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. b) J-02 Chilled water pump alarm b-1) Remove the jumper for Chilled water pump interlock (52CH). b-2) Confirm whether J-02 is indicated on the data display or not. b-3) Push STOP key. Put the jumper. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. c) J-03 Chilled water flow rate alarm c-1) Remove the jumper for Chilled water flow switch (69CH). c-2) Confirm whether J-03 is indicated on the data display or not. c-3) Push STOP key. Put the jumper. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. d) J-05 #2 Absorbent pump alarm d-1) Push the test button (white) on the magnetic contactor. d-2) Confirm whether J-05 is indicated on the data display or not. d-3) Push STOP key. Push rest button on the magnetic contactor. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. e) J-06 Cooling water pump alarm e-1) Remove the jumper for Cooling water pump interlock (52CO). e-2) Confirm whether J-06 is indicated on the data display or not. e-3) Push STOP key. Put the jumper. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. f) J-07 Cooling water flow rate alarm (option) f-1) Remove the jumper for a cooling water flow switch (69CO). f-2) Confirm whether J-07 is indicated on the data display or not. f-3) Push STOP key. Put the jumper. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. g) J-10 Refrigerant pump alarm g-1) Push the test button (white) on the magnetic contactor. g-2) Confirm whether J-07 is indicated on the data display or not. g-3) Push STOP key. Push rest button on the magnetic contactor. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. 136 h) J-11 Ventilation fan alarm h-1) Remove the jumper for ventilation fan interlock (52F). h-2) Confirm whether J-11 is indicated on the data display or not. h-3) Push STOP key. Put the jumper. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. i) J-12 Purge pump alarm I-1) Run the purge pump I-2) Push the test button (white) on the magnetic contactor. I-3) Confirm whether J-12 is indicated on the data display or not. I-4) Stop the purge pump. j) J-15 High temp. generator solution level low alarm j-1) Remove wires connected to high temp.generator solution level electrodes (#30, #31, #32). j-2) Confirm whether J-15 is indicated on the data display or not. j-3) Push STOP key. Connect the wires. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. k) J-20 Cooling water low temp. alarm k-1) Provide 5 liter bucket filled with water and ice. k-2) Cheng "High speed time" setting from OFF to ON by the service mode. k-3) Push RUN key. After RUN LED of #1 & #2 absorbent pump and refrigerant pump light up, dip the sensor (DT7) into the bucket. k-4) After 30 seconds, confirm whether J-20 is indicated on the data display or not. k-5) Push STOP key. Return DT7 to its sensor port. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. l) J-22 High hot water temp. alarm l-1) Provide 5 liter bucket filled with hot water (more then 80 deg.C). l-2) Push RUN key. l-3) After RUN LED of #1 & #2 absorbent pump and refrigerant pump light up, dip the sensor (DT1) into the bucket. l-4) Confirm whether J-22 is indicated on the data display or not. l-5) Push STOP key. Return DT1 to its sensor port. Push BUZZER STOP key. Then Push RUN key, Chiller start again. Continue next test. Note: Remove jumpers connected at the preparation stage and wires disconnected at the preparation shall be connected. m) Sensor alarm of temperature sensor Remove wires of a temp. sensor or Jumper the terminal of the sensor, it's sensor alarm (F-**) is displayed. n) Sensor alarm of flow sensor After running of Chiller, a chilled water pump and a cooling water pump, close gradually a shot off valve provide at the inlet of the evaporator or the absorber, J-03 or J-07 is displayed when water flow rate decreases less than 50% of rated flow rate. 137 Non Note 1 1 2 3 4 5 6 7 8 9 A B C D E 10 11 12 13 14 15 or 16 17 First Stage (Main menu) Display items High temp. gene. Temp. Alarm code Chiller/Heater operation hours #1 Abso. pump operation hours #2 Abso. pump operation hours Burner operation hours Refr. pump operation hours Purge pump operation hours ON/OFF times of Chiller/Heater ON/OFF times of #1 Abso. pump ON/OFF times of #2 Abso. pump ON/OFF times of Burner ON/OFF times of Refr. pump ON/OFF times of Purge pump #3 Abso. pump operation hours ON/OFF times of #3 Abso. pump Chilled water setting temp. Hot water setting. Temp. Chilled water inlet temp. Chilled water outlet temp. Cooling water inlet temp. Condensed refrigerant temp. TJ : Steam drain temp. LJ : Driving hot water outlet temp. Purge tank pressure Second Stage (Set & Confirmation menu) Alarm record Time setting Change of switch functions Set of chilled/hot water pump Set of inverter control of chilled/hot water pump SET / BAC or Set of cooling water system Set of inverter control of cooling water pump or or Field set Set of SR-485 Version No. of Microprocessor (CPU) or Version No. of Option board or or or or SET/BACK Set of model SET/BACK Rated specification setting SET/BACK or Input setting SET/BACK Inverter setting SET/BACK PID setting SET/BACK Operation hours & On/Off times set SET/BACK Predication function setting SET/BACK or Japanese burner controller setting SET/BACK Tuning of temp. sensors SET/BACK Analog data (42 data) indication SET/BACK Digital input indications Digital output indications or State of control conditions SET / BAC SET/BACK Set of inverter-2 SET/BACK or Third Stage (Scroll by & Second Stage or Chilled water outlet temp. setting Hot water outlet temp. setting SET/BACK Set of inverter-3 (chilled/hot water temp. setting) SET BACK SET BACK ) Set rage : 4 - 20 deg.C Set rage : 40 - 95 deg.C or Remark : Maximum hot water outlet temp. setting of DJ series is 60 deg.C due to the material of evaporator. or or or Symbol SET BACK oFF, abs-po, abs-un, abs-IV, sys-po, sys-un SET/BACK oFF, on 0 - 100 % 0 - 100 % 1.0 thru 5.0 50 thru 85 0 thru 250 seconds oFF, on oFF, on 22 - 30 deg.C 1.0 - 6.0 deg.C Set of parallel operation by remote controller Chided/hot water rated flow rate setting SET/BACK Hot water rated flow rate setting Controlled variable setting Minimum frequency setting Set of interlock return time SET/BACK Set of stopping cooling water pump at low load SET/BACK Set of cooling tower fan control Set of cooling tower fan temp. control SET/BACK Set of differential temp. of cooling tower fan SET/BACK Set of variable flow rate Set of cost factor Controlled variable setting Minimum frequency setting Set of temp. for maximum input Set of slow input time Set of slow input temp. Set of dilution time Set of remote signal type Set of type of pulse Set of low select control temp. Set of radiation temp. "rS-485" is indicated SET/BACK oFF, abs-po, abs-un, abs-IV, sys-po, sys-un SET/BACK 0.05 thru 0.60 1.0 thru 5.0 40 thru 85 20 - 33 deg.C 5 - 1800 sec. 0 - 120 deg.C 4 - 20 minutes StAtiC, PuLSE PoSiti, nEGAti 60 - 95 deg.C 5 - 25 deg.C 0 thru 15 SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK Fourth Stage (scrolled by & ) Fixed to Auto Auto, oFF, on Auto, tESt Auto, n.annual 0 - 100 % Auto, n.annual 0 - 100 % Auto, n.annual 0 - 100 % 0 thru 15 oFF, on Cleared by 3 times same manner Input a number from 0 to 9 to 6 columns Depending on type of Chiller/Heater Factory set for service parts : CH-out Factory set for service parts : oFF SET/BACK Factory set for service parts : n.annual SET/BACK oFF, on Factory set for service parts : on Factory set for service parts : oFF 4.0 - 20.0 deg.C 40.0 - 95.0 deg.C 3.0 - 10.0 deg.C 3.0 - 10.0 deg.C 0.5 thru 1.5 0.0 - 200.0 % 8.0 - 16.0 kPa 4.0 - 7.0 kPa 5 thru 60 50 thru 80 2.0 thru 8.0 Pid, on-oFF, H-L-oF Third Stage Function of switch-2 or SET/BACK SET/BACK Second Stage (Service mode) SET + & BACK SET/BACK Fourth Stage (scrolled by & ) Deletion of alarm data 2001 thru 2050 Month : 1 thru 12, Day : 1 thru 31 Time : 0 thru 23, Minute : 0 thru 59 CooL, HEAt, San.E 1-H, 5-n., 1-n., 10-S on, oFF ConSEn o C, oF oFF, on 0 thru 250 seconds Third Stage Record of alarms Set of year Set of month and day Set of time Cool/Heat/Simultaneous change-over Data record interval Select of local operation mode Delete message sign Change of unit Change of low select control Set of interlock return time Set of variable flow rate The functions of the key are to go to a lower stage and to fix new set value. This key functions to be pressed for 2 seconds. or The function of the key is to return to an upper stage. This key functions to be pressed for approximately 1 seconds. The function of the key is to proceed indications. or Scrolling The function of the key is to return indications. or or Purge indication Refrigerant pump Pilot burner Control valve-1 Control valve-1 opening Control valve-2 Control valve-2 opening Control valve-3 Control valve-3 opening HBS address High speed timer function Clear of operating data Serial number Type of Chiller/Heater (Chiller) Type of control Annual cooling operation Automatic changeover For process use With purge pump Oil pump Chilled water outlet temp. Hot water outlet temp. Chilled water temp. difference Hot water temp. difference No-use (extra) SinG-k Max. opening of control valve Indication of purge start Indication of purge stop No-use (extra) AP-tin. No-use (extra) EIICond Crystallization temp. Type of control Input correction Combustion interval Control estimating time Estimating tuning Constant a1 Constant a2 Constant a3 Constant a4 Constant a5 Constant a6 P for cooling I for cooling D for cooling P for heating I for heating D for heating Sampling set SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK # # # # # # # # # # # # $ $ $ $ $ $ $ $ $ $ $ $ # # # $ $ $ SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK # # # # # # # # # # # # # # # # # # Operation hours of Chiller/Heater # #1 abso. pump operation hours # #2 abso. pump operation hours # Burner operation hours # Refr. pump operation hours # Purge pump operation hours # #3 abso. pump operation hours On/Off times of Chiller/Heater # On/off times of #1 abso. pump # On/off times of #2 abso. pump # On/Off times of burner # On/Off times of refr. pump # On/Off times of purge pump # On/off times of #3 abso. pump Vacuum condition # Absorbent concentration Cooling water tubes fouling condition # Cooling water temp. # Combustion chamber fouling condition # Ant freezing Exhaust gas temp. # Clear of predication data SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK $ SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK Set for fundamental data collection of protect-relay SET/BACK Initializing of the collected data Initializing of all data of protect-relay Chilled/hot water outlet temp. sensor # Chilled/hot water inlet temp. sensor # Cooling water outlet temp. sensor # Cooling water inlet temp. sensor # Hot water outlet temp. sensor Hot water inlet temp. sensor Sensor option setting Analog data (42 data) indication SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK (1) Key operation map of operation board Key operation of DJ Series is consists of 4 stages shown in the map. Data code 0 thru 100 0 - 10 minutes 2 thru 100 0.50 thru 2.00 60 thru 160 0.020 thru 0.060 0.000 thru 0.099 2.0 thru 4.0 30 thru 60 2.3 thru 3.5 1.0 thru 10.0 0 thru 2500 0 thru 100 1.0 thru 10.0 0 thru 2500 0 thru 100 5 thru 60 Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns Input a number from 0 to 9 to 6 columns oFF, on Fixed to oFF oFF, on oFF, on oFF, on Fixed to oFF oFF, on See the detail Omission Omission Omission -2.0 - 2.0 deg.C -2.0 - 2.0 deg.C -2.0 - 2.0 deg.C -2.0 - 2.0 deg.C -2.0 - 2.0 deg.C -2.0 - 2.0 deg.C Input 0 or 1 to 6 LED figures Digital input/output & control state indications or or Constant t1 Constant t2 Constant -n Constant -k Constant a6 Constant t1 Constant t2 Constant a6 SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK SET/BACK 100 thru 200 30 thru 100 2 thru 100 0.50 thru 2.00 2.3 thru 3.5 90 thru 160 90 thru 160 27.6 thru 42.0 137A Note 2 : Items marked with # shall be set at replacement of the microprocessor (CPU board) and sensors. Note 3 : Items marked with $ shall not be changed during operation of Chiller/Heater. 6-19 Instruction of Set & confirmation of controls & safeties Remark :Red characters in green columns are items of factory set, non-use, invalid, extra, etc.. Set values of the items shall not be changed except for replacement of the microprocessor (CPU board) & sensors and Note 1 :An alarm code is only displayed at occurring the alarm. The alarm code is cleared after re-starting Chiller/Heater with eliminating its causes. (2) First stage (Main menu) First stage consists of 22 items and the 22 items indicate operating condition of Chiller (temperatures, operating hours and on/off times of main devices). Each indication is displayed with 6 figures of 7 segment LED. The indication code and its value are shown as below. Example 1 : H.T.Generator temp. (high temperature generator temperature) (No-data code) This shows that the H.T.Generator temp. is 145.0 deg.C. 1 4 5. 0 Example 2 : Operation hours of Chiller This shows that the operation hors of Chiller is 12,355 hours. 1. 1 2 3 5 5 The data code is "1"that show operation hours of Chiller. In case that the data is 150 hours, the indications is 1. 1 5 0 Example 3 : On/Off times of burner This shows that the on/off times of burner is 0 time. A 0 The data code is "A" that show on/off times of burner. The data displays 0 time for TJ, LJ and NK series. Example 4 : Steam drain temp. / Driving hot water outlet temp. This shows that the Steam drain temp. is 70.0 deg.C. 1 6. 7 0. 0 The data code is "16" that shows Steam drain temp. for TJ and NK series, and Driving hot water outlet temp. for LJ series. Note) During the dilution operation caused by an alarm, the alarm code is indicated. If several alarms occur at the same time, most high priority alarm code is indicated. These alarm code can be indicated by & keys. However, if 4 or more alarms occur at simultaneously, three alarm codes are indicated. 138 Scroll sequence of main mane During indicating an item in the main menu except for H.T.Generator temp., the indication returns immediately to H.T.Generator temp. without scrolling by pressing the BACK key. 1 4 5. 0 :H.T. Generator temperature at present(unit : deg.C or deg.F) :Displayed at only occurring an alarm. J - 0 1 1. 1 2 3 5 4 :Operation hours of Chiller (unit : hours) 2. 1 1 2 3 5 :#1 absorbent pump operation hours (unit : hours) 3. 1 0 1 2 6 :#2 absorbent pump operation hours (unit : hours) 4. 5. 0 :Burner operation hours (unit : hours) 7 0 3 0 :Refrigerant pump operation hours (unit : hours) 6. 1 0 7 :Purge pump operation hours (unit : hours) 7. 8 5 4 :On/off times of Chiller (unit : times) 8. 8 7 1 :On/off times of #1 absorbent pump (unit : times) 9. 8 5 4 :On/off times of #2 absorbent pump (unit : times) A. 0 :On/off times of burner (unit : times) b. 1 5 2 7 :On/off times of refrigerant pump (unit : times) C. 6 0 :On/off times of purge pump (unit : times) d. 0 :#3 absorbent pump operation hours (unit : hours) E. 0 :On/off times of #3 absorbent pump (unit : times) 1 0. 7. 0 :Setting temperature of chilled water outlet temperature (unit : deg.C or deg.F) 1 1. 0 :Setting temperature of hot water outlet temperature (unit : deg.C or deg.F) 1 2. 1 1. 9 :Chilled water inlet temperature at present (unit : deg.C or deg.F) 1 3. 6. 8 :Chilled water outlet temperature at present (unit : deg.C or deg.F) 1 4. 3 1. 8 :Cooling water inlet temperature at present (unit : deg.C or deg.F) 1 5. 3 4. 7 :Condensed refrigerant temperature in condenser (unit : deg.C or deg.F) 1 6. 1 7. 0 :Driving hot water outlet temp. at present for LJ Series (unit : deg.C or deg.F) :Steam drain temp. at present for TJ and NK Series (unit : deg.C or deg.F) 8. 5 :Pressure in purge tank at present (unit : kPa) 139 (3) Second stage (Confirmation & Setting menu) The followings show the operation steps from the second stage to fourth stage. a) Alarm record : This function shows the three newest alarm code. (Alarm record menu is for confirmation purpose only.) 1st stage 1 4 5. 0 :H.T.Generator temp. at present (145.0 deg.C) SET 2nd stage BACK :This display shows the alarm record menu. A L A r n. SET BACK :The newest alarm code (Sample : J-04 #1 absorbent pump) 3rd stage C 1. J - 0 4 d 1. 0 7 2 4 :The newest alarm date (Sample : 0724 : July 24th) t 1. 0 4. 0 2 :The newest alarm time (Sample : 04.02 : 4:02 am) C 2. J - 0 7 :The alarm code in front of the one [newest] d 2. 1 0 1 6 :The alarm date in front of the one [newest] t 2. 1 4. 1 8 :The alarm time in front of the one [newest] C 3. J - 1 3 :The alarm code in front of the two [newest] d 3. 1 2 2 9 :The alarm date in front of the two [newest] t 3. 2 0. 5 3 :The alarm time in front of the two [newest] r E - S E t SET :This show the alarm clear menu. BACK 4th stage 3 SET BACK 2 SET BACK BACK 1 SET (Three times alarm data are completed to clear.) 140 b) Time setting : This has the functions to confirm and set Year, Month, Day and Time. :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 1 time 2nd stage :Present time is displayed (14:53 = 02:53 pm) r t. 1 4. 5 3 SET 3rd stage BACK :Menu to confirm and set of year Y r - S E t SET 4th stage BACK :Year set at factory is displayed. 2 0 0 1 :Blinking figures can be changed by the keys. (2001 thru 2050) 1st stage BACK 2 0 0 5 SET Y r - S E t BACK :Pressing key 4 times, the year changes from 2001 to 2005. :New set value is installed. 3rd stage d t - S E t SET BACK 4th stage 0 1 - 0 1 :Menu to confirm and set of date :Date set at factory is displayed. :Blinking figures can be changed. 1 1 - 0 5 BACK SET :Month and Date can sifted by key as follows; Month Date Month Date Figuers of month & date can be changed by key. Changeable figure of month : 1 thru 12 (Scrolling) Changeable figure of date : 1 thru 31 (Scrolling) d t - S E t BACK :New set value is installed. 3rd stage t n. - S E t SET BACK 4th stage 0 7 0 0 :Menu to confirm and set of time :Date set at factory is displayed. :Blinking figures can be changed. 1 0 - 1 7 SET BACK :Hour and Minute can sifted by key as follows; Hour Minute Hour Minute Figuers of month & date can be changed by key. Changeable figure of hour : 0 thru 23 (Scrolling) Changeable figure of minute : 0 thru 59 (Scrolling) t n. - S E t BACK :New set value is installed. 141 c) Change of switch functions : This has the functions to confirm and set of the followings. :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 2 times. 2nd stage :Set and confirmation of switch function menu. C H G S SET BACK :Operation mode for DJ series. 3rd stage r d - S E t (Cool / Heat / Simultaneous change-over) SET BACK 4th stage :Cooling mode (Factory set : COOL) C o o L 1st stage :Heating mode H E A t SET 3rd stage S A n. - d t SET BACK 4th stage 1 - H :Data record interval. : Data record interval : 1hour (Factory set : 1-H) 5 - n. : Data record interval : 5 minutes 1 - n. : Data record interval : 1 minute : Data record interval : 10 seconds 1 0 - S SET 3rd stage L o C A L SET BACK 4th stage o n :Local operation mode. :Local operation mode (Factory set : on) :Remote operation mode o F F SET 3rd stage S I :Delete message sign G n SET BACK C o n S E n SET 4th stage 3rd stage u n I :Push "SET" key for delete message sign. :Push "BACK" key for continue to message sign on display. :Change unit t SET BACK o C 4th stage :Unit : deg.C o F (Factory set : deg.C) :Unit : deg.F SET 3rd stage L o S E L :Operation mode for LJ series. (Factory set : OFF) 142 d) Set of chilled water pump : This has the functions to confirm and set of the applications for a chilled water pump. :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. Press 3 times. 2nd stage BACK :Set of chilled water pump menu. A P P o C H SET BACK :Set of interlock return time 3rd stage I n t - C H SET BACK 4th stage :The interlock return time set at present is displayed. 0 0 0 S (Factory set : "0") :Changeable from 0 to 250 sec. 2 5 0 S SET 1st stage 3rd stage V V - C H SET BACK o F F :Set of variable flow rate (Future use) (Factory set : OFF) S y S - u n S y S - P o A b S - I V A b S - u n A b S - P o SET 3rd stage r 4th stage - P A r A SET BACK o F F :Set of parallel operation by the remote controller (Future use) (Factory set : OFF) o n SET 143 e) Set of inverter control of chilled water pump : (Future use) :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. Press 4 times. 2nd stage BACK :Set of inverter control of chilled water pump menu. C H - I n V 1st stage f) Set of cooling water system : This has the functions to confirm and set of the applications for a cooling water pump. f-1) Set of interlock return time f-2) Set of stopping cooling water pump at low load f-3) Set of cooling tower fan control (Future use) f-4) Set of cooling tower fan temp. control f-5) Set of differential temp. of cooling tower fan f-6) Set of variable flow rate 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 5 times. 2nd stage A P P o C o :Set of cooling water system menu. SET BACK :Menu to set and confirm the interlock return time. 3rd stage I n t - C o SET BACK :The interlock return time set at present is displayed. 4th stage 0 0 0 S (Factory set : "0") :Changeable from 0 to 250 sec. 2 5 0 S SET 3rd stage C o S t o P :Set of stopping cooling water pump at low load menu (Future use) 3rd stage C t A u t o :Set of cooling tower fan control menu (Future use) 3rd stage C t t E n. P 3rd stage C t d I F F 3rd stage V V - C o :Set of cooling tower fan temp. control menu (Future use) :Set of differential temp. of cooling tower fan menu (Future use) :Set of variable flow rate menu (Future use) 144 g) Set of inverter control of cooling water pump : (Future use) : This function is confirmation & set of an inverter signal sent from Chiller to a cooling water pump. g-1) Set of cost factor g-2) Controlled variable setting g-3) Minimum frequency setting 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 6 times. 2nd stage C o - I n V :Set of inverter control of cooling water pump menu. (Future use) h) Field set : This has the functions to confirm and set as followings. h-1) Set of temp. for maximum input This setting is to reduce the maximum input when cooling water inlet temperature rises beyond the rated temp. (T deg.C). Starting temp. of maximum input reduction at lower cooling inlet temperature : T - 4 deg.C (fixed) h-2) Set of slow input time : This is time setting for a fuel control valve to open slowly in order to prevent over-input at Chiller starting. h-3) Set of slow input temp. : This setting is to avoid the fuel control valve slow open function in order to shorten the rise time of chiller at starting, if H.T.Generator temperature is higher than a certain temperature. h-4) Set of dilution time : This setting is for dilution operation time. h-5) Set of remote signal type : This setting is select of a remote operation (start & stop) signal. h-6) Set of type of pulse : This setting is select of the pulse signal type for operation signal. h-7) Set of low select control temp. : (Future use) h-8) Set of radiation temp. : (Future use) 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 7 times. 2nd stage F I E L d :Field set menu. SET BACK :Set of temp. for maximum input 3rd stage C o - I n P SET BACK 4th stage o C :The temp. for maximum input set at present is displayed. 2 0. 0 (Factory set : "32") o :Changeable from 20 to 33 deg.C. 3 3. 0 C SET 145 3rd stage I n P - BACK 0 0 0 0 4th stage 1 8 0 0 3rd stage :Menu to set and confirm the set of slow input time t n SET I 4th stage S SET n P t n. P SET BACK o C 0 0 0 o C SET 1 2 0 3rd stage d S I 4th stage L u - t SET BACK 0 4 2 0 3rd stage r - S 4th stage I :Menu to set and confirm the set of slow input temp. :The temp. for slow input set at present is displayed. (Factory set : "000") :Changeable from 0 to 120 deg.C. :Menu to set and confirm the set of slow input temp. n. n. SET :The time for dilution operation set at present is displayed. (Factory set : "04") :Changeable from 4 to 20 deg.C. :Menu to set and confirm the set of remote signal type G n SET BACK S t A t :The time for slow input set at present is displayed. (Factory set : "0000") :Changeable from 0 to 1800 seconds I C :The remote signal type set at present is displayed. (Factory set : "StAtiC") P u L S E SET 3rd stage o F - P L S SET BACK 4th stage P o S I t :Menu to set and confirm the set of remote signal type I or :The pulse type set at present is displayed. (Factory set : "PoSiti") n E G A t I SET 3rd stage L o S E L E 3rd stage H E - S t :Set of low select control temperature menu (Future use) :Set of radiation temperature menu (Future use) 146 i) Set of SR-485 : Invalid function, must be passed (Future use) : This function is to install addresses to plural Chiller/Heaters in order to operate them by the remote controller. 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 8 times. 2nd stage r S - 4 8 5 :Set and confirmation of set of SR-485 j) Version No. of microprocessor (indication only) :H.T.Generator temp. at present (145.0 deg.C) 1st stage 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 9 times. 2nd stage U E r 0. 9 1 :The version No. is displayed. k) Version No. of option board (indication only) :H.T.Generator temp. at present (145.0 deg.C) 1st stage 1 4 5. 0 SET BACK :First display in 2nd stage A L A r n. BACK Press 10 times. 2nd stage o P U 0. 0 0 :The version No. is displayed. 147 (4) Second stage (Service mode) The followings show the operation steps from the second stage to fourth stage. a) Function of switch-2 : This has the following items. a-1) Purge indication : This is fixed with "Auto" only. It can be passed. a-2) Refrigerant pump : Use to operate manually a refrigerant pump. There are 3 mode "AUTO", "OFF", "ON". (Factory set : AUTO) a-3) Pilot burner : Select "AUTO" or "TEST" for DJ model only. a-4) Control valve-1 : To select fuel control valve operating mode. "AUTO" or "MANUAL" (Factory set : AUTO) a-5) Control valve-1 opening : Set valve opening. a-6) Control valve-2 (Factory set : AUTO) a-7) Control valve-2 opening a-8) Control valve-3 (Factory set : AUTO) a-9) Control valve-3 opening a-10) HBS address (Factory set : 0) a-11) High speed timer function : The speed of timer function in the microprocessor increases 60 times of the regular speed. This function is useful for servicing only. In case of select "ON", alarm light blinks on and off. a-12) Clear of operating data : Use to clear operating data (192 times) filed in the microprocessor. 1st stage 1 4 5. 0 SET + BACK 2nd stage C H G S 2 SET BACK 3rd stage P U r G E SET BACK 4th stage A u t o :H.T.Generator temp. at present (145.0 deg.C) :Service mode :Purge indication menu. :This is fixed with "Auto" only. 3rd stage r E F - P SET BACK 4th stage A u t o :Refrigerant pump menu. (Factory set : Auto) :Refrigerant pump operates automatically. o F F :Refrigerant pump is stopped by force. o n :Refrigerant pump runs continuously by force. In this case, the refrigerant pump RUN lamp blinks. SET 3rd stage P I L o t :Pilot burner menu. 3rd stage C n. - 1 (Future use for DJ series) :Control valve-1 menu. (Factory set : Auto) SET 4th stage BACK A u t o n. A n u A L SET :Automatic mode. :Manual mode. 148 3rd stage C n. - 1 S t SET BACK 4th stage :Control valve-1 opening menu. 0 1 0 0 SET (Factory set : "100") :Control valve-1 opening set at present is displayed. :Changeable from 0 to 100 %. 3rd stage C n. - 2 :Control valve-2 menu. (Future use) 3rd stage C n. - 2 S t :Control valve-2 opening menu. (Future use) 3rd stage C n. - 3 :Control valve-3 menu. (Future use) 3rd stage C n. - 3 S t :Control valve-3 opening menu. (Future use) 3rd stage H d d H b S :HBS address menu. (Future use) 3rd stage b A 4th stage :High speed timer function menu. S o k SET BACK o F F (Factory set : oFF) :High speed timer function set at present is displayed. :In case of ON, the alarm lamp blinks. o n SET 3rd stage o P - r S t SET BACK 4th stage :Clear of operating data menu. 3 2 1 SET (All operation data is cleared.) 149 b) Set of model : This has the following items. b-1) Serial number b-2) Type of Chiller b-3) Type of control b-4) Annual cooling operation These settings have been set at the factory. b-5) Automatic changeover Do not change them. b-6) For process use (Resetting for replace the microprocessor only) b-7) With purge pump b-8) Oil pump 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 1 time 2nd stage n. o d E L :Set of model menu. SET BACK :Serial number menu. :Change of figure 3rd stage d SET :Movement of column 4th stage BACK 0 0 BACK 3 0 BACK 3 0 BACK 3 2 BACK 3 2 BACK 3 2 BACK 3 2 BACK 3 2 BACK 3 2 BACK 3 2 BACK 3 2 BACK 3 2 BACK 0 0 0 0 SET 0 0 0 0 SET 0 0 0 0 SET 0 0 0 0 SET 0 0 0 0 SET 5 0 0 0 SET 5 0 0 0 SET 5 1 0 0 SET 5 1 0 0 SET 5 1 8 0 SET 5 1 8 0 SET 5 1 8 4 SET :1st column blinks. Example : Press 3 times :2nd column blinks. Example : Press 2 times :3rd column blinks. Example : Press 5 times :4th column blinks. Example : Press 1 times :5th column blinks. Example : Press 8 times :6th column blinks. Example : Press 6 times 150 :Type of Chiller. 3rd stage t y p E SET BACK 4th stage : Efficiency (Future use) (Standard) (High efficency) (Future use) : Type of effect (Double effect) (Single effect) (Single & Double effect) (Double & Double effect) (Triple effect) (Future use) (Future use) (Future use) : Fuel - 1 (Gas) (Kerosene) (Diesel oil) (Steam) (High temp hot water) (low temp hot water) (Dual fuel : Gas-oil) (Future use) : Fuel - 2 (No use) (Steam) (High temp hot water) (low temp hot water) (Exhaust gas)) SET (Future use) (Future use) (Future use) (Future use) (Future use) (Future use) : Option - 1 (Standard model) (Future use) (Simultaneous model) (Low temp chilld water model) (Future use) (Additional hot water heater) (Future use) (Low temp chilld water & hot water heater) (Future use) : Option - 2 (Future use) (Standard) (Future use) (Option) 151 3rd stage C o n t 4th stage :Control by chilled water outlet or inlet o SET BACK C H - o u t C H - n SET 3rd stage A - C o o L SET BACK 4th stage o F F (Future use) (Standard) (Future use) :Option (Future use) (Standard) (Future use) o n SET 3rd stage C H A u t o SET BACK 4th stage n. A n u A L :Option (Future use) (Standard) (Future use) A u t o SET 3rd stage P r o C :Increased chilled water outlet temp to max 20 degC. SET 4th stage BACK o F F (Standard) (Possible to increase to 20 degC) o n SET 3rd stage n. P - o P SET BACK 4th stage o n :Option of purge pump. (Standard) (No option) o F F SET 3rd stage o P - o P SET BACK 4th stage o F F :Option (Future use) (Standard) (Future use) o n SET 152 c) Rated specification setting : This has the following items. c-1) Chilled water outlet temp. c-2) Hot water outlet temp. Factory set (Never change) c-3) Chilled water temp. difference c-4) Hot water temp. difference c-5) No-use (extra) SinG-k : Future use c-6) Max. opening of fuel control valve c-7) Indication of purge pump starting Factory set (Never change) c-8) Indication of purge pump stopping c-9) No-use (extra) AP-tin. : Future use c-10) No-use (extra) EIICond : Future use c-11) Crystallization temp. : Future use 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 2 times 2nd stage S P E C :Set of rated specification setting menu. SET BACK :Chilled water outlet temp. 3rd stage C - t E n. P SET BACK o C :The setting of rated chilled water outlet temp. set 4th stage 4. 0 at present is displayed. (Factory set : "7.0") : Up and down the spec temp. by the key . o C :Changeable from 4.0 to 20.0 deg.C 2 0. 0 SET 3rd stage H - 4th stage t E n. P SET BACK 4 0. 0 9 5. 0 :Hot water outlet temp. o C o C SET 3rd stage C - d t :The setting of rated hot water outlet temp. set at present is displayed. (Factory set : "55.0") : Up and down the spec temp. by the key . :Changeable from 40.0 to 95.0 deg.C :Chilled water temp. difference SET 4th stage BACK 3. 0 1 0. 0 o C o C SET :The setting of rated chilled water temp. difference set at present is displayed. (Factory set : "5.0") : Up and down the spec temp. by the key . :Changeable from 3.0 to 10.0 deg.C 153 3rd stage H - d t :Hot water temp. difference SET 4th stage BACK 3. 0 o o C SET 1 0. 0 3rd stage S C n G - k : (Future use) 3rd stage r A n K u P SET BACK 4th stage 0. 0 2 0 0. 0 SET 3rd stage A P - S t SET BACK 8. 0 k P A 1 6. 0 k P A SET 3rd stage A P - S P SET BACK 4. 0 k P A 7. 0 :The setting of rated hot water temp. difference set at present is displayed. (Factory set : "5.0") : Up and down the spec temp. by the key . :Changeable from 3.0 to 10.0 deg.C k P A SET :Max. opening of fuel control valve :The setting of max. opening of fuel control valve set at at present is displayed. (Factory set : "100.0") : Up and down the spec temp. by the key . :Changeable from 0.0 to 200.0 % :Indication of purge pump starting :The setting of indication of purge pump starting set at present is displayed. (Factory set : "10.0") : Up and down the spec temp. by the key . :Changeable from 8.0 to 16.0 kPa :Indication of purge pump stopping :The setting of indication of purge pump stopping set at present is displayed. (Factory set : "7.0") : Up and down the spec temp. by the key . :Changeable from 4.0 to 7.0 kPa n : (Future use) C o n d : (Future use) 3rd stage L E C r y S : (Future use) 3rd stage A P 3rd stage E t (Factory set : "1.0") 154 d) Input setting : This has the following items. d-1) Type of control :Factory set menu. d-2) Input correction : Factory set menu d-3) Combustion interval : Factory set menu 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 3 times 2nd stage :Set of rated specification setting menu. n P u t SET BACK :Set of type of control 3rd stage b n t y P E SET BACK 4th stage P d SET 3rd stage 4th stage 3rd stage F - 4th stage :Input correction P t C o r SET BACK 5 0 SET :Fuel interval n t SET BACK - - n. 0 0 n. 1 0 n. SET (Factory set : "0") :Changeable from 0 to 10 minutes 155 e) Inverter setting : This has the following items for #1 absorbent pump inverter. e-1) Control estimating time e-2) Estimating tuning e-3) Constant a1 e-4) Constant a2 Factory set (Never change) e-5) Constant a3 e-6) Constant a4 e-7) Constant a5 e-8) Constant a6 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 4 times 2nd stage :Set of rated specification setting menu. n V S E t SET BACK :Control estimating time 3rd stage 3 3 A L SET BACK 4th stage 1 5 SET 3rd stage 3 3 A L - K SET BACK 4th stage 1. 0 0 SET 3rd stage 4th stage 3rd stage 4th stage 3rd stage 4th stage 3rd stage 4th stage :Estimating tuning n V - A 1 SET BACK 1 4 8 SET :Constant a1 n V - A 2 SET BACK 0. 0 4 2 SET :Constant a2 n V - A 3 SET BACK 0. 0 6 0 SET :Constant a3 n V - A 4 SET BACK :Constant a4 3. 6 SET 156 3rd stage n V - A 5 SET BACK 4th stage 3rd stage 4th stage :Constant a5 5 0 SET n V - A 6 SET BACK :Constant a6 2. 3 SET 157 f) PID setting : This is PID control setting menu for capacity control of Chiller. All data has been set at the factory. Do not change them. :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 5 times 2nd stage P :PID setting menu. d S E t SET BACK :P for cooling 3rd stage C o o L - P SET BACK 4th stage 2. 0 SET 1st stage 3rd stage C o o L - I SET BACK 4th stage 2 0 0 SET :I for cooling 3rd stage C o o L - d SET BACK 4th stage :D for cooling 5 SET 3rd stage H E A t - P SET BACK 4th stage 5. 0 SET :P for heating 3rd stage H E A t - I SET BACK 4th stage 5 0 SET :I for heating 3rd stage H E A t - d SET BACK 4th stage 3 0 SET :D for heating 3rd stage S A n. P L E SET BACK 4th stage 1 0 SET :Sample time 158 g) Operation hours and ON/OFF times set : (Use for CPU replacement only) g-1) Operation hours of Chiller g-8) On/Off times of Chiller g-2) #1 abso. pump operation hours g-9) On/off times of #1 abso. pump g-3) #2 abso. pump operation hours g-10) On/off times of #2 abso. pump g-4) Burner operation hours g-11) On/Off times of burner g-5) Refr. pump operation hours g-12) On/Off times of refr. pump g-6) Purge pump operation hours g-13) On/Off times of purge pump g-7) #3 abso. pump operation hours g-14) On/off times of #3 abso. Pump 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 6 times 2nd stage C o u n t :Operation hours & ON/OFF times setting menu. SET BACK :Operation hours of Chiller :Change of figure 3rd stage u n t - t SET :Movement of column BACK :1st column blinks. 4th stage 0 0 0 0 0 0 BACK SET 0 0 0 0 0 0 BACK SET :2nd column blinks. Example : Press 4 times. 0 0 0 0 0 0 SET BACK 0 4 0 0 0 0 SET BACK :3rd column blinks. Example : Press 1 time. 0 4 0 0 0 0 BACK SET 0 4 1 0 0 0 SET BACK :4th column blinks. Example : Press 7 times. 0 4 1 0 0 0 BACK SET 0 4 1 7 0 0 SET BACK :5th column blinks. Example : Press 8 times. 0 4 1 7 0 0 BACK SET 0 4 1 7 8 0 BACK SET :6th column blinks. Example : Press 4 times. 0 4 1 7 8 0 SET BACK 0 4 1 7 8 4 159 3rd stage A b S 1 - t :#1 absorbent pump operation hour 3rd stage A b S 2 - t :#2 absorbent pump operation hour r E - t :Burner operation hour 3rd stage F 3rd stage r E F - :Refrigerant pump operation hour t 3rd stage P u r G - t :Purge pump operation hour 3rd stage A b S 3 - t :#3 absorbent pump operation hour 3rd stage u n t - C :On/OFF times of Chiller 3rd stage A b S 1 - C :ON/OFF times of #1 absorbent pump 3rd stage A b S 2 - C :ON/OFF times of #2 absorbent pump 3rd stage F r E - C :ON/OFF times of burner 3rd stage r E F - C :ON/OFF times of refrigerant pump 3rd stage P u r G - C :ON/OFF times of purge pump 3rd stage A b S 3 - C :ON/OFF times of #3 absorbent pump 160 h) Predication function setting h-1) Vacuum condition : Factory setting = ON h-2) Absorbent concentration : Invalid function, must be passed. h-3) Cooling water tubes fouling condition : Factory setting = ON h-4) Cooling water temp. : Factory setting = ON h-5) Combustion chamber fouling condition : For Japanese market only. h-6) Ant freezing : For Japanese market only. h-7) Exhaust gas temp. : For Japanese market only. h-8) Clear of predication data 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 7 times 2nd stage S :Predication function setting menu. G n S t SET BACK :Vacuum condition 3rd stage P u r G E SET BACK :Non-display 4th stage o F F :Display o n (Factory set : "on") SET 3rd stage t H C K 3rd stage C o - d 4th stage :Absorbent concentration :Cooling water tubes fouling condition r SET BACK o n :Display (Factory set : "on") :Non-display o F F SET 3rd stage C o - H :Cooling water temperature SET 4th stage BACK o n :Display (Factory set : "on") :Non-display o F F SET 3rd stage C C - d 4th stage :Combustion chamber fouling condition r SET (Future use) BACK o F F SET 161 3rd stage r u L E - 1 SET BACK 4th stage o F F :Anti freezing (Future use) :Exhaust gas temperature (Future use) SET 3rd stage E H G - L o SET BACK 4th stage o F F SET 3rd stage r E - S E t SET BACK 4th stage :Clear of predication data 3 2 1 SET i) Burner controller setting (Future use) :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 8 times 2nd stage P r y :Burner controller setting (Future use) 1st stage 162 j) Tuning of temperature sensor j-1) Chilled water outlet temp. sensor j-2) Chilled water inlet temp. sensor j-3) Cooling water outlet temp. sensor j-4) Cooling water inlet temp. sensor j-5) Hot water outlet temp. sensor j-6) Hot water inlet temp. sensor j-7) Sensor option setting 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 9 times 2nd stage S E n S o r :Tuning of temp. sensor setting menu. SET BACK :Chilled water outlet temp. sensor 3rd stage C H o A d J SET (Factory set : 0.0 deg.C) BACK :The tuning setting set at present is displayed. 4th stage - 2. 0 2. 0 SET 3rd stage C H :Chilled water inlet temp. sensor (Factory set : 0.0 deg.C) A d J SET BACK - 2. 0 4th stage 2. 0 SET 3rd stage C o o A d J SET BACK 4th stage - 2. 0 2. 0 SET 3rd stage C o :The tuning setting set at present is displayed. :Changeable from -2.0 thru 2.0 deg.C :Cooling water outlet temp. sensor (Factory set : 0.0 deg.C) :The tuning setting set at present is displayed. :Changeable from -2.0 thru 2.0 deg.C :Cooling water inlet temp. sensor (Factory set : 0.0 deg.C) A d J SET BACK - 2. 0 4th stage :Changeable from -2.0 thru 2.0 deg.C 2. 0 SET :The tuning setting set at present is displayed. :Changeable from -2.0 thru 2.0 deg.C 3rd stage H o A d J :Hot water outlet temp. sensor 3rd stage H :Hot water inlet temp. sensor A d J 3rd stage S E n - o P :Sensor option 163 k) Analog data indication : 42 data can be displayed. 1st stage 2nd stage A 3rd stage 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5 5 5 5 :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 10 times :Analog data indication menu. n A L o G SET BACK Select data :H.T.Generator temperature (deg.C) 1 4 5. 0 :Chilled water inlet temp. (deg.C) 2. 1 1. 9 :Chilled water outlet temp. (deg.C) 3. 6. 8 :Cooling inlet temp. (deg.C) 4. 3 1. 8 :Condensed refrigerant temp. (deg.C) 5. 3 4. 7 :Steam drain temp. (deg.C) 6. 8 5. 3 :Purge tank pressure (kPa) 7. 8. 5 :L.T.Generator temperature (deg.C) 8. 9 1. 5 :Cooling water mid temp. (deg.C) 9. 3 3. 5 :Cooling water outlet temp. (deg.C) 0. 3 7. 1 :Steam drain temp. (deg.C) 1. 8 5. 3 :Refrigerant temp. (deg.C) 2. 5. 9 :Diluted solution temp. at absorber outlet (deg.C) 3. 2 7. 8 :Inverter frequency (%) 4. 5 7. 5 :Fuel control valve opening output (%) 5. 0 :Fuel control valve opening input (%) 6. 0 :CVP output (%) 7. 9 6. 0 :Concentrated solution concentration (%) 8. 6 2. 5 :Diluted solution concentration (%) 9. 9 0. 0 :Remote setting input for chilled/hot water outlet temp. setting (mA) 0. 4. 0 :Invalid item 1. 0 :Invalid item 2. 0 :Low temp. heat exchanger outlet temp. (deg.C) 3. 3 5. 9 :Abnormality ratio in absorber 4. 8 5. 1 :Abnormality ratio in condenser 5. 4 5. 3 :Driving hot water inlet temp. for LJ Series (deg.C) 6. 0 :Hot water temp. at control valve outlet for LJ Series (deg.C) 7. 0 :Driving hot water outlet temp. for LJ Series (deg.C) 8. 0 :Invalid item 9. 0 :Invalid item 0. 0 :Invalid item 1. 0 :Invalid item 2. 0 :Invalid item 3. 0 :Invalid item 4. 0 :Invalid item 5. 0 :Invalid item 6. 0 :Invalid item 7. 0 :Invalid item 8. 0 :Invalid item 9. 0 :Invalid item 0. 0 :Invalid item 1. 0 :Invalid item 2. 0 :Invalid item 3. 0. 0 164 l) Digital input indication : Present digital input state is displayed. 1st stage 2nd stage d 3rd stage . :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 11 times :Digital input indication menu. G SET BACK . . . . . :Present digital input state A 1 2 3 4 5 Column number F 6 G E B C D Dp Segment number Digital input indication table Segment 1st column 2nd column 3rd column 4th column A E2: 51A2: 51AU: H.T.Generator #2 abso pump (Future use) solution level overload relay electrode (E2) NH: (Future use) 52CH: Chilled water pump interlock B E1: AUTO: H.T.Generator ABS2: solution level #2 abso pump (Future use) electrode (E1) DI1: (Future use) 52CO: Cooling water pump interlock C POW: 51A1: Power #1 abso pump resuming overload relay interlock PAS: (Future use) DI2: (Future use) 52CT: (Future use) D 69CH: 51R: Chilled water Refr pump overload relay flow switch PGSL: (Future use) DI3: 23CO: Cooling mode (Future use) E 51B: (Future use) F 63GH: generator ABS1: #1 abso pump pressure switch G REF: Refr pump 51O: (Future use) PR-11: Fuel control valve opened in force Dp BM: (Future use) OIL: (Future use) PR-10: Fuel control valve closed in force 69CO: FIRE: Cooling water Combustion flow switch M.F: Combustion alarm 5th column 6th column 52F: DI4: Ventilation fan Heating mode interlock DI5: (Future use) R-ST: Remote start signal R-SP: Remote stop signal 165 m) Digital output indication : Present digital output state is displayed. 1st stage 2nd stage d 3rd stage . :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 12 times :Digital input indication menu. G - o SET BACK . . . . . :Present digital input state A 1 2 3 4 5 Column number F 6 G E B C D Dp Segment number Digital output indication table Segment 1st column 2nd column EXT-ON: Chilled water pump is running 3rd column 4th column 5th column 6th column AL: Predication signal DO3-ON: (Future use) KISYAKU: Dilution operation B CPUMP-ON: FIRE-ON: Cooling water EX-HEAT: Ignition signal pump is (Future use) running KIDO-R: Local / Remote DO3-OFF: (Future use) COOL: Cooling mode C CMG-BK: ABS1-ON: Fuel control NH-ON: #1Abso pump valve opened (Future use) is running in force DO1: (Future use) DO4: (Future use) HEAT: Heating mode D CMG-BJ: Fuel control valve closed in force CFAN-ON: (Future use) RBV: (Future use) DO2: (Future use) ABS-RES: Abso pump reset E DS-ON: (Future use) KIDO-I: Answer back AUTOV: (Future use) RUN: Running F BM-ON: (Future use) AUTOP: (Future use) STOP: Stop G ABS2-ON: F-ON: F-RUN: #2 abso pump Ventilation fan (Future use) is running is running FAIL-1: Alarm Dp REF-ON: Refr pump is running FIRE: Combustion A PR-ON: (Future use) PV-ON: (Future use) BZ: Alarm buzzer 166 n) State of control condition : Present control condition is displayed. The following 4 function working conditions are displayed. 1) Protection function of H.T.Generator temperature excessive high 2) Protection of concentrated solution concentration excessive high 3) Maximum input control depending on cooling water inlet temp. 4) Pre-set function of chilled water outlet temperature set value 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 13 times 2nd stage C n t n o :State of control condition menu. SET BACK :Present working conditions are displayed. 3rd stage 0 0 0 0 0 0 Function Non-working Extra 0 Extra 0 Function 4) 0 Function 3) 0 Function 2) 0 Function 1) 0 o) Set of inverter-3 : 1st stage 2nd stage p) Set of inverter-2 : 1st stage 2nd stage Working 1 1 1 1 (Future use) :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 14 times :Set of inverter-3 menu. n V 3 (Future use) :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 SET + BACK :First display in 2nd stage C H G S 2 Press 15 times :Set of inverter-3 menu. n V 2 167 (5) Re-set of chilled water outlet temperature set value Purpose : In oder to save operating energy in light cooling season, the set value of chilled. 1st stage :H.T.Generator temp. at present (145.0 deg.C) 1 4 5. 0 Press 15 times or Press 8 times 2nd stage 1 0. :Chilled water outlet temperature set value is displayed. 7. 0 SET BACK 3rd stage : Present set value is blinking. 1 0. 7. 0 1 0. 1 0. 8. 0 BACK SET The set value can be chaged by the keys as required. Changeable rage in Chilled water : 4 thru 20 deg.C Changeable rage in hot water : 40 thru 95 deg.C 8. 0 BACK Note : The above changeable ranges are only in the microprocessor. 168 6-20. Set of solution dampers The following table shows the factory set value of solution dampers. Full close : 0 deg. Full open : 90 deg. Damper Damper (degree) D9 16NK D1 D2 D3 D4 D5 D6 D7 D8 11 25 45 22 68 18 35 52 31 12 35 45 22 68 18 35 52 31 13 62 50 15 65 15 45 40 52 21 38 57 33 90 49 32 48 63 22 17 60 30 44 50 32 35 65 31 60 60 45 45 52 45 32 60 32 60 60 45 45 52 45 32 60 41 90 90 90 90 53 90 30 88 42 90 90 90 90 53 90 30 88 51 42 75 65 90 40 65 45 60 52 80 75 65 50 40 60 45 65 53 84 79 68 45 41 61 45 75 61 90 80 70 45 40 60 45 60 62 41 65 65 35 37 37 90 63 45 65 65 35 40 40 90 71 50 65 65 35 40 40 90 72 55 65 65 35 40 40 90 15 81 60 65 65 35 40 40 90 15 D1 D2 D3 D4 D5 D6 D7 D8 D9 : : : : : : : : : 15 Diluted solution #1 Diluted solution #2 Diluted solution #3 Intermediate solution Concentrated solution Refrigerant drain Refrigerant Diluted solution bypass Refrigerant supply 169 6-21. Scrapping To scrap Chiller, the following remarks shall be observed. a) The scrapping shall be conducted by a licensed party in accordance with a local regulation. b) To move and lift Chiller, licensed personnel shall operate a machine for the works. c) If disassembling is required for scrapping, personnel having necessary license shall conduct the disassembling work. d) If discharging absorbent solution and refrigerant is required, refer to the following remarks because of vacuum condition inside the chiller. d-1) Nitrogen gas or air is charged through the service valve SV1 up to approximate 50 kPa. d-2) Remove absorbent solution and refrigerant from the following service valve. SV4 : Diluted absorbent solution in the lower shell SV5 : Intermediate absorbent solution in the high temperature heat exchanger SV6 : Concentrated absorbent solution in the low temperature heat exchanger SV3 : Refrigerant in the refrigerant pan SV8 : Intermediate absorbent solution in the high temperature generator d-3) The solution discharged shell be collected in proper containers. Do not pour the solution to a drain, sewage, ground, etc.. d-4) If gas cutting work is required for disassembling, the work shall be conducted after the charged gas is released. d-5) During releasing the charged gas, air ventilation shall be provided. d-6) Note that there are sections where the solution can not be discharged. The low temperature generator, the heat reclaimer, the drain heat reclaimer. And even if the solution is discharged, inside surface of Chiller/Heater is wet. Pay attention not to touch the solution directly. If touched, wash off the solution with water. e) The solution shall be chemically managed by a special company. 170 6-22. Flow switch The following is the flow switch instruction manual translated from the manufacturer's manual Model - BQS Type Manufacturer : Saginomiya Co.,Ltd. Safety precautions a) Do not open the cover of flow switch to avoid an electric shock. b) Wiring to the flow switch shall be connected with power off to avoid an electric shock. c) Do not wet the micro-switch of flow switch to avoid an electric shock. d) A load connected to the micro- switch shall be within electric rating specified blow to avoid any damages on the micro-switch contactor. e) Do not turn any screws except the set screw to avoid abnormal functioning and any other troubles. f) The flow switch shall be mounted as the arrow mark on the cover. Reverse mounting of the flow switch causes no-functioning and paddle damage. g) Any fluid which gives damages to the wetted part of flow switch shall not be used. h) Be sure to make a grounding. The grounding wire shall not be connected to a gas piping, a city water piping, an lightning conductor and telephone line. Imperfect grounding may cause an electric shock. i) Fluid speed shall be less than 2 m/sec.. Model Name Wetted part material Construction BQS-C1**P BQS-C1**PM BQS-C1**PW BQS-C1**PWM Open type Drip -proof type Ambient humidity Copper alloy Max. 80 %RH Bronze / Stainless Copper alloy Max. 95 %RH Bronze / Stainless Electric rating ( Unit : A ) Type Voltage Resistance load Lamp load Motor load AC125V 15 1.5 5 AC250V 10 1.25 3 Standard DC 30V 2 1.4 1 DC125V 0.4 0.4 0.03 10 1.5 4 For high load DC115V with DC DC230V 5 0.75 1.5 Type For very small load Voltage AC125V DC 8V DC 14V DC 30V Load 0.1 0.1 0.1 0.1 Common specification 1. Max. working pressure 0.98 Mpa 2. Allowable fluid temp. 5~80 deg.C 3. Endurance limit 100,000 times 4. Mounting screw 5. Ambient temp. (No-icing & No-dewing) Minus 25 - Plus 80 deg.C 6. Contact (Single pole & Double throw) Horizontal a Rc1 Pipe Screwed depth Specifications C Paddle Paddle Flow direction A: Normal open Paddle Flow B: Normal close A B C: Common 171 Mounting a) Minimum 5 times straight length of a pipe diameter shall be required at front and rear of the flow switch for prevention of hunting due to eddy flow. b) The flow switch is basically mounted on horizontal piping as shown in the figure. The flow switch can also be mounted on vertical piping. In this case, actual working flow rate may slightly change. It about 20 %. c) Use T-joint (JIS B3201) to mount the flow switch. If T-joint can not be available, the dimension (a) shown above figure shall be met with T-joint d) The screwed depth shall be 12Plus/Minus 1.2mm. e) The wiring for flow switch shall be in accordance with the label in the flow switch. of JIS B3201. Setting a) Unless otherwise specified, the flow switch is factory shipped with around minimum setting point. b) Turn the adjusting screw with clockwise, working point increases. Turn the adjusting screw with counter-clockwise, working point decreases. Do not over-turn the adjusting screw to achieve stable working condition. c) Be sure to confirm the functioning of micro-switch if a setting is changed. d) The screw F is for factory adjustment. Do not change it. Fluid flow direction Adjusting screw Screw F (Do not change it ) 172 Selection table of number of paddles The flow switch having generally 2 paddle is furnished on the chiller in the factory. However, in case that flow rate differs from the standard specification due to a special requirement, the number of paddles is selected as per the following table. Pipe size inch Paddle 1 Qmin. Qmax. (l/min) (l/min) 50 2 105 65 2-1/2 195 80 3 360 100 4 615 125 5 810 150 6 1,330 200 8 2,310 250 10 3,565 300 12 5,120 350 14 6,370 400 16 8,415 450 18 10,745 500 20 13,360 250 565 850 1,435 2,230 3,140 5,470 8,435 12,120 15,070 19,915 25,430 31,620 Paddle 1 + 2 Qmin. Qmax. (l/min) (l/min) Paddle 1 + 2 + 3 Qmin. Qmax. (l/min) (l/min) 50 105 170 330 510 715 1,245 1,920 2,760 3,430 4,530 5,785 7,195 200 350 530 930 1,435 2,060 2,560 3,380 4,315 5,365 150 355 480 940 1,450 2,040 3,550 5,480 7,875 9,790 12,940 16,525 20,550 600 1,120 1,700 2,960 4,565 6,560 8,160 10,780 13,770 17,120 173 6-23. T.R.G. meter T.R.G. meter can be utilized to check abrasion condition of solution pumps easily. The following explanation is the procedure to use and the guidance value to judge the absorbent condition for their maintenance. The #1 absorbent pump, #2 absorbent pump and refrigerant pump are equipped with a system of detecting bearing wear without the need for dismantling the pump. The T.R.G. system consists of two inspection coils embedded in the motor stator. As the stator energized and causes the rotor to rotate, the T.R.G. coils create an AC electromotive force. As bearings begin to wear causing the rotor to run closer to the stator the AC electro-motive force generated by the T.R.G. coils increases. Taking T.R.G. readings on a regular basis can be a great tool in determining rate of bearing wear and when the pump should be overhauled. The T.R.G. terminals are located in each pump terminal boxes and should be tested with an AC volt meter set at the 2.5 VAC scale. Initial Start-up value plus 0.0 thru 0.50 0.5 thru 0.60 0.6 thru 0.75 Over 0.75 VAC VAC VAC VAC Judgment Safe Caution Warning Maintenance Continue Operation can be done Schedule overhaul at next inspection Schedule immediately overhaul Immediate overhaul required T.R,G. (Teikoku Rotary Guardian) Note 1 In case of an absorbent pump controlled by an inverter, it's T.R.G. reading may change depending on inverter frequency. Always take readings at the same frequency. Using different meters can also result in slightly different readings. 1 TRG Inspection coil 2 Stator Note 2 If a reading reaches to the warning level, an overhaul should be immediately scheduled and conduct the overhaul as soon as possible. Generally, warning level reading may reach to over 0.75 VAC for about two weeks. TRG Inspection coil 174 6-24. How to check temperature sensors The chiller uses 3 types temperature sensors as follows. Resistance (copper) thermometer bulb DT1 : Chilled water outlet temperature sensor Thermistor DT3 : High temp. generator temperature sensor DT13 : Steam drain temperature sensor Digital sensor DT2 : Cooling water outlet temperature sensor DT4 : Low temp. generator temperature sensor DT5 : Condenser temperature sensor DT6 : Chilled water inlet temperature sensor DT7 : Cooling water inlet temperature sensor DT10 : Absorber temperature sensor DT11 : Evaporator temperature sensor DT12 : Middle cooling water temperature sensor a) How to check Resistance (copper) thermometer bulb DT1 Remove the sensor wiring from the terminal box and measure resistance between terminals of sensor itself. And then compare measured resistance value calculated by the following formula. For example, If the chilled water outlet temperature is 10 deg.C by a thermometer, the resistance value is 2,085 ohms. Charactristics of resistance : 2000Ω at 0 deg.C (32 deg.F) : Rating of resistance : 8.56Ω/deg.C Present resistance = 2000 + 8.56 x Present measured temperature 2000 + 8.56 x 10 = 2,086 ohms If DT1 is disconnection, its resistance value becomes infinity. If DT1 is short, it will be 0 ohms. In these case, J-01 next F25 are indicated in cooling mode on the display board, J-22 next F25 are indicated in heating mode on the display board. 175 b) How to check Thermistor DT3 & DT13 DT3 and DT13 are the thermisters and the low range side is used for Chiller. Accordingly, resistance value between the red lead wire and black lead wire need to be measured. (The white lead wire is the high range side, do not use it.) For example, if H.T.Ggenerator temperature measued by another thermometer (surface thermometer) is 150 degree C, resistance value is 3,161 ohms as shwon in blow table. If DT3 / DT13 is disconnection, its resistance value becomes infinity. If DT3 / DT13 is short, it will be 0 ohms. IF DT3 is disconnection or short, J-13 next F26 are indicated on the display board. If DT13 is disconnection or short, J-17 next F27 are indicated on the display board. Temperature & Resistance Table Accuracy : 1,000 ohms plus/minus 3% at 200 deg.C (392 deg.F) Temperature Resistance Temperature Resistance Temperature Resistance Deg. C Deg. F k ohm Deg. C Deg. F Ohm Deg. C Deg. F Ohm 0 32 806.5 110 230 9,585 210 410 815 10 50 478.8 120 248 7,131 220 428 669 20 68 292.9 130 266 5,374 230 446 554 30 86 184.1 140 284 4,098 240 464 461 40 104 118.7 150 302 3,161 250 482 387 50 122 78.3 160 320 2,464 260 500 326 60 140 52.8 170 338 194 270 518 277 70 158 36.3 180 356 1,542 280 536 236 80 176 25.4 190 374 1,237 290 554 202 90 194 18.1 200 392 1,000 300 572 174 100 212 13.1 c) How to check Digital sensors DT2, DT4, DT5, DT6, DT7, DT10, DT11 & DT12 Status of digital sensors cannot be judged by checking of sensor itself. Therefore, the status of a digital sensor need to be judged by a sensor alarm indicated on the display board. In case that a sensor alarm is indicated, firstly check whether there is a poor connection of connector or not. Connect the sensor to vacant connector or remove one sensor from a connector and connect the doubtful sensor to the connector. If there are multiple sensor errors, there is a possibility of plug defectiveness of connector of a trunk line of wiring. If sensor alarm is for all the sensors, connect a sensor directly and check the possibility of damage in the first trunk line. Other possibility is malfunction of the microcomputer. Address setting for digital sensor The microprocessor in Chiller control panel checks addresses of each sensor when the power supply is ON. In case that a sensor is replaced, its address is checked by the microprocessor when the power supply is just turned on then the address is recorded into the microprocessor. Note : Address of each sensor has been written at the factory before shipment. 176 Section 7 Seasonal inspection & operation with daily maintenance 7-1. Beginning cooling season Yes a) Chilled water system No N/A a-1) Check of valve open/close conditions in chilled water loop (Including secondary loop : air handling unit side) a-2) Cleaning of strainers in the chilled water loop a-3) Water filling into the chilled water loop (If necessary, new water is filled into the chilled water loop) a-4) Performing air vent from the chilled water loop a-5) Check of water leakages in chilled water loop a-6) Check of control for chilled water system a-7) Check of water circulating condition Insulation resistance of chilled water pump meg ohm Amperage of chilled water pump A Suction pressure of chilled water pump KPa / psi Discharge pressure of chilled water pump KPa / psi a-8) Independent trial run of chilled water system b) Cooling water system b-1) Check of valve open/close conditions in cooling water loop b-2) Cleaning of strainers in the cooling water loop with cooling tower b-3) Water filling into the chilled water loop (New water should be filled into the cooling water loop) b-4) Performing air vent from the cooling water loop b-5) Check of water leakages in cooling water loop b-6) Check of control for cooling water system with temp. control b-7) Check of water circulating condition Insulation resistance of cooling water pump meg ohm Amperage of cooling water pump A Suction pressure of cooling water pump KPa / psi Discharge pressure of cooling water pump KPa / psi b-8) Independent trial run of cooling water system c) Total trial run of chilled and cooling water systems 177 Yes d) Stream and drain system No N/A d-1) Check of valve open/close conditions in steam line d-2) Cleaning of strainers in the steam line d-3) Performing steam control valve d-4) Check of steam leakages in steam line d-5) Check of valve open/close conditions in steam drain line d-6) Check of steam drain leakages in steam drain line e) Check damages on the control panel, mounted parts, etc. f) Check of insulation resistance of pumps (More than 10 meg ohm) f-1) #1 absorbent pump meg ohm f-2) #2 absorbent pump meg ohm f-3) Refrigerant pump meg ohm f-4) Purge pump meg ohm g) Check of purge pump and purging g-1) No-water in the liquid trap g-2) Oil quality (oil color shall be clean) g-3) Oil quantity (up to the center of purge pump sight glass) g-4) No abnormal noise g-5) Attained vacuum (attained vacuum shall be less than 0.5 kPa abs.) g-6) Purging from the lower shell Perform purging from both the purge tank (V2) and the lower shell (V3) until the inside vacuum goes down below the allowable vacuum curve (Refer to page 133). h) Bubble test (Refer to page 132) : cc Second measuring value: cc Third measuring value : cc Average value : cc First measuring value NG Judgmen Goo d Perform leak test and repair the leakage Chiller can go into the commercial operation. i) Inspection of steam control valve and steam trap : Contrl valve : Steam trap j) Operation of Chiller k) Refrigerant blow down (Refer to page 134) Note : Before refrigerant blow down, confirm that refrigerant level can be observed through the sight glass. If not, continue the operation of Chiller and stop the refrigerant pump until refrigerant the refrigerant level is observed. l) Sampling absorbent for analyses (Refer to page 123) m) Absorbent analyses (Refer to page 106) j) Adjusting inhibitor content and alkalinity (if necessary) (Refer to106) 178 7-2. Mid cooling season Even through the cooling system runs normally, viewing from preventive maintenance of the cooling system including Chiller, the following inspections are recommended. Yes a) Chilled water system No N/A a-1) Check of valve open/close conditions in chilled water loop (Including secondary loop : air handling unit side) a-2) Cleaning of strainers in the chilled water loop a-3) Water filling into the chilled water loop (If necessary, new water is filled into the chilled water loop) a-4) Performing air vent from the chilled water loop a-5) Check of water leakages in chilled water loop a-6) Check of control for chilled water system a-7) Check of water circulating condition Insulation resistance of chilled water pump meg ohm Amperage of chilled water pump A Suction pressure of chilled water pump KPa / psi Discharge pressure of chilled water pump KPa / psi a-8) Independent trial run of chilled water system b) Cooling water system b-1) Check of valve open/close conditions in cooling water loop b-2) Cleaning of strainers in the cooling water loop with cooling tower b-3) Water filling into the chilled water loop (New water should be filled into the cooling water loop) b-4) Performing air vent from the cooling water loop b-5) Check of water leakages in cooling water loop b-6) Check of control for cooling water system with temp. control b-7) Check of water circulating condition Insulation resistance of cooling water pump meg ohm Amperage of cooling water pump A Suction pressure of cooling water pump KPa / psi Discharge pressure of cooling water pump KPa / psi b-8) Independent trial run of cooling water system c) Total trial run of chilled and cooling water systems 179 Yes d) Stream and drain system No N/A d-1) Check of valve open/close conditions in steam line d-2) Cleaning of strainers in the steam line d-3) Performing steam control valve d-4) Check of steam leakages in steam line d-5) Check of valve open/close conditions in steam drain line d-6) Check of steam drain leakages in steam drain line e) Check damages on the control panel, mounted parts, etc. f) Check of insulation resistance of pumps (More than 10 meg ohm) f-1) #1 absorbent pump meg ohm f-2) #2 absorbent pump meg ohm f-3) Refrigerant pump meg ohm f-4) Purge pump meg ohm g) Check of purge pump and purging g-1) No-water in the liquid trap g-2) Oil quality (oil color shall be clean) g-3) Oil quantity (up to the center of purge pump sight glass) g-4) No abnormal noise g-5) Attained vacuum (attained vacuum shall be less than 0.5 kPa abs.) g-6) Purging from the lower shell Perform purging from both the purge tank (V2) and the lower shell (V3) until the inside vacuum goes down below the allowable vacuum curve (Refer to page 133). 180 7-3. End of cooling season At the end of cooling season, the following inspections and maintenances should be conducted to avoid troubles during shutdown of Chiller. At the last cooling operation of the season, perform the refrigerant blow down. Then proceed the following inspections and maintenances. Yes a) Chilled water system No N/A a-1) Close shut-off valve provided at the inlet & outlet of Chiller a-2) Drain out chilled water used during cooling season from Chiller a-3) If necessary, conduct evaporator tube cleaning a-4) Fill the evaporator with new clean water a-5) Inspect & maintain chilled water system if necessary b) Cooling water system b-1) Drain out cooling water used during cooling season from Chiller b-2) If necessary, conduct absorber & condenser tube cleaning b-3) Close shut-off valve provided at the inlet & outlet of Chiller/heater b-4) Fill the absorber & condenser with new clean water b-5) Inspect & maintain cooling water system if necessary c) Check of insulation resistance of pumps (More than 10 meg ohm) c-1) #1 absorbent pump meg ohm c-2) #2 absorbent pump meg ohm c-3) Refrigerant pump meg ohm c-4) Purge pump meg ohm d) Check of purge pump and purging d-1) No-water in the liquid trap d-2) Oil quality (oil color shall be clean) d-3) Oil quantity (up to the center of purge pump sight glass) d-4) No abnormal noise d-5) Attained vacuum (attained vacuum shall be less than 0.5 kPa abs.) d-6) Purging from the lower shell Perform purging from both the purge tank (V2) and the lower shell (V3) until the inside vacuum goes down below the allowable vacuum curve (Refer to page 133). e) Bubble test (Refer to page 132) : cc Second measuring value: cc Third measuring value : cc Average value : cc First measuring value NG Judgmen Goo d Perform leak test and repair the leakage Chiller can go into the commercial operation. f) Sampling absorbent for analyses (Refer to page 123) g) Absorbent analyses (Refer to page 106) h) Adjusting inhibitor content and alkalinity (if necessary) (Refer to106) 181 7-4. Operation of Chiller This section describes the following operation procedures of Chiller. a) Start & Stop procedures b) Re-start procedure at safety shutdown c) Re-start procedure after power failure d) Purging procedure a) Start & Stop procedure of Chiller Refer to "4-2. Operation sequence" Remark The power shall be basically supplied continuously to the control circuit of Chiller by means of turning on the main circuit breakers (MCBM & MCB3) and the circuit protections (CP1 & CP2) to prevent that life of the palladium cell heater is shortened by frequent ON & OFF of the power supply. When the power is turned on again after the power supply is turned off due to a reason, the following indication is displayed on the operation board. V E r 0. 9 7 2 5. 0 This indication means the version number of the microprocessor provided in Chiller controller. And the indication is lighting up during completion of the self-diagnostic function of the microprocessor. (The version number differs depending on each unit type.) : H.T.Generator temperature b) Re-start procedure at safety shutdown If Chiller stops by an alarm, restart Chiller by the following steps after eliminating its cause. An alarm happens Its alarm code is displayed on the operation board and the alarm buzzer sounds Dilution operation Alarm buzzer stops Chiller stops completely Press "BUZZER STOP key on the operation board Locate a cause of the alarm, then eliminate it. In case of following alarms, manual reset of safety devices is necessary J-04 : #1 absorbent pump alarm --- Reset button on overcurrent relay J-02 : #2 absorbent pump alarm --- Reset button on overcurrent relay J-10 : Refrigerant pump alarm --- Reset button on overcurrent relay J-14 : Generator high pressure alarm --- Gene. pressure reset button The alarm code disappears Press "STOP" key on the operation board Restart can be done 182 c) Re-start procedure after power failure c-1) If power failure occurs during operation of Chiller, restart Chiller by the following steps after resuming the power. Power failure occurs Chiller is shutdown immediately without dilution operation The power resumes. The alarm code "H-10" is shown in the operation board. Local operation Remote operation No-voltage pulse signal or DC/AC 24V pulse signal Press "RUN" key No-voltage continuous signal or DC/AC 24V continuous signal Send the start signal H-10 goes off Chiller restarts d) Re-starting method depending on the period of power failure At power failure, Chiller stops immediately without dilution operation. Therefore, re-starting method differs depending on the period of power failure as follows. d-1) In case that the power resumes within approximate 1 hour Chiller can be restarted and then confirm that the chilled water outlet temperature goes down and goes into the control mode. If the chilled water outlet temperature does not go down, crystallization may occur at the concentrated solution side in the low temperature heat exchanger. Perform de-crystallization then restart Chiller. d-2) In case that the power resumes more than 1 hour Chiller is restarted with blow 50% fuel input and confirm that the concentrated solution outlet pipe of the low temperature heat exchanger warms and the becomes hot. If so, Chiller can be operated with 100% fuel input. If not, crystallization may occur at the concentrated solution side in the low temperature heat exchanger. Perform de-crystallization then restart Chiller. d-3) During purging If power failure occurs during purging, close the manual purge valve (V1) immediately and then run Chiller with purging at least 1 hour after resuming the power. If air may go into Chiller, stop Chiller/heater. After resuming the power, conduct purging until the inside pressure goes down blow allowable vacuum. Then start Chiller with purging at least 1 hour. 183 7-5. Purging procedure When the purge indication lamp on the control panel lights up, perform purging from the purge tank by means of the following steps. Procedure Turn on the purge pump ON/OFF switch. SV9 69 PR PCH Purge tank V3 Open V1 and V2 after 10 minutes. V2 Purge The purge pump runs. B valve Press key once Non-condensable gas coming from l h ll tDiluted solution it coming from The purge tank pressure is displayed. (data code 17) #1 absorbent pump to purge Confirm that the indicated value goes down. 69 PR SV9 PCH Purge tank Close V1 and V2. Continue the running purge pump more for 10 minutes to release moisture from the purge pump oil. Turn off the purge pump ON/OFF switch. The purge pump stops. 1 2 3 4 5 6 7 8 9 V2 V3 Attained vacuum of the purge pump is less than 0.5 kPa abs. No SV2 Purge unit Yes Continue the running purge pump more for 10 minutes. No Non-condensable gas The purge indication lamp goes off If the indicated value goes down below 7 kPa. B valve B valve shall be opened. SV1 V1 Liquid trap Yes Leakage of the palladium cell and/or 69PR may be suspected. Purge pump Diluted solution returns to Fig. 7-1 Purge unit (cooling mode) There are 2 choices. 1.Replacement of them 2.Leak test + Replacement of leakage device Replacement Close V1 & V2, and stop the purge pump. Close B valve. Open SV9 (N2 charging is better). Replace the leaked device (s). Connect SV9 & SV1 by a vacuum hose. Run the purge pump and open V1 & SV1. Conduct purging for approximately 10 min.. Close SV9, SV1 and V1. Stop the purge pump and remove the hose. Perform maintenance of the purge pump. 184 7-6. Daily maintenance Proper maintenance of Chiller will insure continuous, efficient, and trouble-free operation prolonging equipment life and reduce service requirements. Daily maintenance should be performed by user's maintenance personnel. Maintenance of auxiliary equipment is equally important and shout be handled according to the manufacturers specifications. Seasonal or periodical inspection work should be performed by qualified service personnel. (1) Daily maintenance points a) Check and recorded operating data per daily operating record sheet, temperature, pressure, etc. b) From daily data, check if there are any sudden change on the data. For example; b-1) Shortening lighting interval of the purge indication lamp : Leakage and palladium cell failure b-2) Rising diluted solution temperature : Crystallization b-3) Rising or falling cooling water inlet temperature : Malfunction of cooling water temperature control b-4) etc. c) Check for leaks in steam piping d) Abnormal noise from #1 & #2 absorbent pumps e) Abnormal noise form refrigerant pump f) There are not any hammering noise from Chiller and chilled & cooling water loop g) Auxiliary equipment is in proper working order. h) Cooling tower water is being treated properly. 185 (2) Daily operating data sheet Date : Chiller model : Serial No.: Data points Main menu Non H.T.Generator temp. Time Chiller operation hours hours 2 #1 Abso. pump operation hours hours 3 #2 Abso. pump operation hours hours 5 Refr. pump operation hours hours 6 Purge pump operation hours hours 7 ON/OFF times of Chiller times 8 ON/OFF times of #1 Abso. pump times 9 ON/OFF times of #2 Abso. pump times B ON/OFF times of Refr. pump times C ON/OFF times of Purge pump times 12 Chilled water inlet temp. deg.C 13 Chilled water outlet temp. deg.C 14 Cooling water inlet temp. deg.C 15 Condensed refrigerant temp. deg.C 16 Steam drain temp. deg.C 17 Purge tank pressure kPa 18 L.T.Generator temp. deg.C 19 Cooling water mid temp. deg.C 20 Cooling water outlet temp. deg.C 22 Refrigerant temp. deg.C 23 Diluted sol. temp. at ABS outlet deg.C Inverter frequency % 28 Concentrated solution concentrati % 33 Low temp. heat exchanger outlet Evaporator Solution level Absorber H.T.Generator Operator : : : : : : : % 25 Control valve opening output 29 Diluted solution concentration / deg.C 1 24 : / % deg.C n/60 n/60 n/60 Chilled water inlet pressure kPa Chilled water outlet pressure kPa Cooling water inlet pressure kPa Cooling water outlet pressure kPa Steam consumption rate Notes: 186 7-7. Procedure for a long term shut-down (1) Definition of a long-term shut down period: More than six months In case of Chiller using for cooling only, usual shut down period is a half year, six months. (2) Measure for a long-term shut down period a) Chiller a-1) Basically nitrogen gas (0.02MPa) shall be charged. a-2) Instead of nitrogen charge, monthly purging from the main shell for at least 30 minutes to 1 hours can be acceptable. b) Chilled water loop b-1) Basically, it is necessary to dispose all the water after the last operation and fill the evaporator tubes with fresh water. b-2) It is not necessary to fill the water fully to the whole chilled water loop. Chiller only can be filled with water by means that the shutoff valves installed near the inlet and outlet of the evaporator are closed completely. b-3) Addition of anticorrosive is recommended. Consultation by a specialized agent is recommended. In order to do this work, special knowledge and skill such as proper management of anticorrosive, heat transfer tube cleaning, etc. must be required. b-4) In case of use of brine for whole chilled water loop, contact a specialized supplier too. c) cooling water loop c-1) Basically, it is necessary to dispose all the water after the last operation and fill the absorber and the condenser tubes with fresh water. c-2) It is not necessary to fill the water fully to the whole chilled water loop. Chiller/heater only can be filled with water by means that the shutoff valves installed near the inlet of the absorber and outlet of the condenser are closed completely. c-3) Addition of anticorrosive is recommended. Consultation by a specialized agent is recommended. In order to do this work, special knowledge and skill such as proper management of anticorrosive, heat transfer tube cleaning, etc. must be required. c-4) In case of use of brine for whole chilled water loop, contact a specialized supplier too. 186 d) Dry lay up If dry lay up is required for chilled water loop and/or cooling water loop, be user to consult a specialized agent. Because, in this case, chemical treatment to make anticorrosive film inside all transfer tubes and the tubes must be dried completely after the treatment. Basic procedure for the dry lay up Discharge water used in operation Chemical tube cleaning and/or Brush tube cleaning Chemical treatment to make anticorrosive film inside tubes Discharge water using for chemical treatment Dry up tubes by dry air e) #1 & #2 absorbents and refrigerant pump It is not necessary to operate. f) Palladium cell heater During shut down period, a power supply shall be OFF continuously. (3) In the case of less than six months a) Chiller Conduct monthly purging from the main shell for 30 minutes to 1 hour. b) Chilled water loop / cooling water loop Flow chilled water and cooling water once a week for around 1 hour for equalization of a state of water in heat transfer tubes. Also check each water quality once a month. If water quality is out of the standard value, it is necessary to contact a specialized agent for management of water quality by such as injection of chemical, blow-down, to secure water quality. c) #1 & #2 absorbents and refrigerant pump It is not necessary to operate. d) Palladium cell heater During shut down period, a power supply shall be OFF continuously. Remarks: Frequent ON/OFF of the palladium cell heater will shorten the life of palladium call due to repetition thermal stress. This will cause crack on the palladium cell and infusion of the air to the chiller. 187