Uploaded by nkosinathimasiya2

Lesson 6 MTF2 Heat Exchangers 2021(1)

advertisement
HEAT EXCHANGERS
CHAPTER 22
The objective of this chapter is to:
• Recognize numerous types of heat exchangers, and classify them
• Develop an awareness of fouling on surfaces, and determine the overall heat transfer coefficient for a
heat exchanger
• Perform a general energy analysis on heat exchangers
• Obtain a relation for the logarithmic mean temperature difference for use in the LMTD method, and
modify it for different types of heat exchangers using the correction factor
• Develop relations for effectiveness, and analyze heat exchangers when outlet temperatures are not
known using the effectiveness-NTU method
Heat exchangers are devices that facilitate the exchange of heat between two fluids that are at different
temperatures while keeping them from mixing with each other. Heat exchangers are commonly used in
practice in a wide range of applications, from heating and airconditioning systems in a household to
chemical processing and power production in large plants. Heat exchangers differ from mixing chambers
in that they do not allow the two fluids involved to mix. Heat transfer in a heat exchanger usually involves
convection in each fluid and conduction through the wall separating the two fluids. In the analysis of heat
exchangers, it is convenient to work with an overall heat transfer coefficient U that accounts for the
contribution of all these effects on heat transfer. The rate of heat transfer between the two fluids at a
location in a heat exchanger depends on the magnitude of the temperature difference at that location,
which varies along the heat exchanger. Heat exchangers are manufactured in a variety of types, and thus
we start this chapter with the classification of heat exchangers.
TYPES OF HEAT EXCHANGERS
Different heat transfer applications require
different types of hardware and different
configurations of heat transfer equipment. The
attempt to match the heat transfer hardware to
the heat transfer requirements within the
specified constraints has resulted in numerous
types of innovative heat exchanger designs. The
simplest type of heat exchanger consists of two
concentric pipes of different diameters, called the
double-pipe heat exchanger. One fluid in a
double-pipe heat exchanger flows through the
smaller pipe while the other fluid flows through
the annular space between the two pipes. Two
types of flow arrangement are possible in a
double-pipe heat exchanger: in parallel flow, both
the hot and cold fluids enter the heat exchanger
at the same end and move in the same direction.
In counter flow, on the other hand, the hot and
cold fluids enter the heat exchanger at opposite
ends and flow in opposite directions.
(a) Parallel flow
(b) Counter flow
Different flow regimes and associated
temperature profiles in a double-pipe
heat exchanger
TYPES OF HEAT EXCHANGERS
Compact heat exchanger: It has a large heat
transfer surface area per unit volume (e.g., car
radiator, human lung). A heat exchanger with
the area density ๐›ฝ > 700 ๐‘š2 Τ๐‘š3 is classified as
being compact.
(a)Both fluids unmixed
Cross-flow: In compact heat exchangers, the two fluids usually move
perpendicular to each other. The cross-flow is further classified as
unmixed and mixed flow
Another type of heat exchanger, which is specifically designed to realize a large
heat transfer surface area per unit volume, is the compact heat exchanger. The
ratio of the heat transfer surface area of a heat exchanger to its volume is called
the area density β. The flow passages in these compact heat exchangers are
usually small and the flow can be considered to be laminar. Compact heat
exchangers enable us to achieve high heat transfer rates between two fluids in a
small volume, and they are commonly used in applications with strict limitations
on the weight and volume of heat exchangers. The large surface area in compact
heat exchangers is obtained by attaching closely spaced thin plate or corrugated
fins to the walls separating the two fluids. Compact heat exchangers are
commonly used in gas-to-gas and gas-to-liquid (or liquid-to-gas) heat exchangers
to counteract the low heat transfer coefficient associated with gas flow with
increased surface area. In a car radiator, which is a water-to-air compact heat
exchanger, for example, it is no surprise that fins are attached to the air side of the
tube surface.
(b) One fluid mixed, one
fluid unmixed
Different flow configurations in
cross-flow heat exchangers.
A gas-to-liquid compact heat
exchanger for a residential airconditioning system.
TYPES OF HEAT EXCHANGERS
An example of compact heat exchangers widely used today in industrial
applications such as chemical processing, fuel processing, waste heat
recovery, and refrigeration is the printed circuit heat exchanger
referred to as PCHE.
The flat metal plates that form the core of this heat exchanger are
chemically etched to a depth of 1 to 3 mm. The chemically etched plates
are then stacked together and joined by diffusion bonding.
Photograph of a ‘Core’ section
from a printed circuit heat
exchanger (Heatric,a Meggitt
Company, Dorset, UK.)
PCHEs have high surface density typically greater than 2500 m2 Τm3 . The PCHEs are usually made
from stainless steel, titanium, copper, nickel and nickel alloys and can withstand operating pressures up
to 500 bar.
The major advantages of PCHEs are their wide operating temperature range, which is from ๏€ญ250๏‚ฐC to
900๏‚ฐC, very high heat transfer coefficients, and their size, which is about four to six times smaller and
lighter than conventional heat exchangers.
One of the major disadvantages of using PCHEs is very high pressure drop and that they require very
clean fluid to be passed through them otherwise blockages can occur easily in the fine channel spacing
(0.5 to 2 mm). There may be different etching patterns on the plates to make the heat exchanger
as a parallel, counter or cross flow heat exchanger. Furthermore, unlike conventional heat exchangers
with straight flow channels, the flow channels in PCHE can be made in zigzag, S-shape, or aero foil
shape in order to induce flow turbulence and hence enhance the heat transfer coefficient.
TYPES OF HEAT EXCHANGERS
Shell-and-tube heat exchanger: The
most common type of heat exchanger
in industrial applications.
They contain a large number of tubes
(sometimes several hundred) packed in
a shell with their axes parallel to that of
the shell. Heat transfer takes place as
one fluid flows inside the tubes while
the other fluid flows outside the tubes
through the shell.
Shell-and-tube heat exchangers are
further classified according to the
number of shell and tube passes
involved.
The schematic of a shell-and-tube heat
exchanger (one-shell pass and one-tube pass).
Heat transfer takes place as one fluid flows inside the tubes while
the other fluid flows outside the tubes through the shell. Baffles
are commonly placed in the shell to force the shell-side fluid to
flow across the shell to enhance heat transfer and to maintain
uniform spacing between the tubes. Despite their widespread use,
shell-and-tube heat exchangers are not suitable for use in
automotive and aircraft applications because of their relatively
large size and weight. Note that the tubes in a shell-and-tube heat
exchanger open to some large flow areas called headers at both
ends of the shell, where the tube-side fluid accumulates before
entering the tubes and after leaving them.
TYPES OF HEAT EXCHANGERS
Regenerative heat exchanger: Involves the alternate passage of
the hot and cold fluid streams through the same flow area.
Dynamic-type regenerator: Involves a rotating drum and
continuous flow of the hot and cold fluid through different portions
of the drum so that any portion of the drum passes periodically
through the hot stream, storing heat, and then through the cold
stream, rejecting this stored heat.
(a) One-shell pass and two-tubes
passes
Condenser: One of the fluids is cooled and condenses as it flows
through the heat exchanger.
Boiler: One of the fluids absorbs heat and vaporizes.
Heat exchangers in which all the tubes make one U-turn in the shell, for
example, are called one-shellpass and two-tube-passes heat exchangers. The
static-type regenerative heat exchanger is basically a porous mass that has a
large heat storage capacity, such as a ceramic wire mesh. Hot and cold fluids
flow through this porous mass alternatively. Heat is transferred from the hot
fluid to the matrix of the regenerator during the flow of the hot fluid, and from
the matrix to the cold fluid during the flow of the cold fluid. Thus, the matrix
serves as a temporary heat storage medium. Heat exchangers are often given
specific names to reflect the specific application for which they are used. A
space radiator is a heat exchanger that transfers heat from the hot fluid to the
surrounding space by radiation.
(b) Two-shell passes and fourtube passes
Multipass flow arrangements in
shell-and-tube heat exchangers.
TYPES OF HEAT EXCHANGERS
An innovative type of heat exchanger that has found widespread use is the plate and frame (or
just plate) heat exchanger, which consists of a series of plates with corrugated flat flow passages.
Also, plate heat exchangers can grow with increasing demand for heat transfer by simply
mounting more plates. They are well suited for liquid-to-liquid heat exchange applications,
provided that the hot and cold fluid streams are at about the same pressure.
Plate and frame
(or just plate) heat
exchanger:
Consists of a series
of plates with
corrugated flat flow
passages. The hot
and cold fluids flow
in alternate
passages, and thus
each cold fluid
stream is
surrounded by two
hot fluid streams,
resulting in very
effective heat
transfer. Well suited
for liquid-to-liquid
applications.
A plate-and-frame liquid-to-liquid heat exchanger
THE OVERALL HEAT TRANSFER COEFFICIENT
•
A heat exchanger typically involves two flowing fluids
separated by a solid wall.
•
Heat is first transferred from the hot fluid to the wall by
convection, through the wall by conduction, and from the wall
to the cold fluid again by convection.
•
Any radiation effects are usually included in the convection
heat transfer coefficients.
๐‘…wall =
In ๐ท๐‘œ Τ๐ท๐‘–
2๐œ‹๐‘˜๐ฟ
๐ด๐‘– = ๐œ‹๐ท๐‘– ๐ฟ and ๐ด๐‘œ = ๐œ‹๐ท๐‘œ ๐ฟ
๐‘… = ๐‘…total = ๐‘…๐‘– + ๐‘…wall + ๐‘…๐‘œ =
1
ln ๐ท๐‘œ Τ๐ท๐‘–
1
+
+
โ„Ž๐‘– ๐ด๐‘–
2๐œ‹๐‘˜๐ฟ
โ„Ž๐‘œ ๐ด๐‘œ
The thermal resistance network associated with this heat transfer process involves
two convection and one conduction resistances. The analysis is very similar to the
material presented in Chap. 17. Here the subscripts i and o represent the inner
and outer surfaces of the inner tube. The Ai is the area of the inner surface of the
wall that separates the two fluids, and Ao is the area of the outer surface of the
wall. In other words, Ai and Ao are surface areas of the separating wall wetted by
the inner and the outer fluids, respectively.
Thermal resistance network
associated with heat transfer in a
double-pipe heat exchanger.
THE OVERALL HEAT TRANSFER COEFFICIENT
๐‘„แˆถ =
โˆ†๐‘‡
= ๐‘ˆ๐ดโˆ†๐‘‡ = ๐‘ˆ๐‘– ๐ด๐‘– โˆ†๐‘‡ = ๐‘ˆ๐‘œ ๐ด๐‘œ โˆ†๐‘‡
๐‘…
U : the overall heat transfer coefficient, WΤm2 ⋅ โ„ƒ
1
1
1
1
1
=
=
=๐‘…=
+ ๐‘…wall +
๐‘ˆ๐ด๐‘  ๐‘ˆ๐‘– ๐ด๐‘– ๐‘ˆ๐‘œ ๐ด๐‘œ
โ„Ž๐‘– ๐ด๐‘–
โ„Ž๐‘œ ๐ด๐‘œ
When
๐‘…wall ≈ 0:
1
1
1
≈ +
๐‘ˆ โ„Ž๐‘– โ„Ž๐‘œ
๐ด๐‘– ≈ ๐ด๐‘œ ≈ ๐ด๐‘  :
๐‘ˆ ≈ ๐‘ˆ๐‘– ≈ ๐‘ˆ๐‘œ
The overall heat transfer coefficient U is
dominated by the smaller convection
coefficient. When one of the convection
coefficients is much smaller than the other
(say, โ„Ž๐‘– << โ„Ž0 ), we have 1Τโ„Ž๐‘– >> 1Τโ„Ž0 , and
thus ๐‘ˆ ≈ โ„Ž๐‘– . This situation arises frequently
when one of the fluids is a gas and the
other is a liquid. In such cases, fins are
commonly used on the gas side to
enhance the product UA and thus the heat
transfer on that side.
The two heat transfer surface areas associated
with a double-pipe heat exchanger (for thin
tubes,๐ท๐‘– ≈ ๐ท๐‘œ and thus ๐ด๐‘– ≈ ๐ด๐‘œ )
In the analysis of heat exchangers, it is convenient to combine
all the thermal resistances in the path of heat flow from the
hot fluid to the cold one into a single resistance R, and to
express the rate of heat transfer between the two fluids. Note
that Ui Ai = Uo Ao, but Ui ≠ Uo unless Ai = Ao. Therefore, the
overall heat transfer coefficient U of a heat exchanger is
meaningless unless the area on which it is based is specified.
This is especially the case when one side of the tube wall is
finned and the other side is not, since the surface area of the
finned side is several times that of the unfinned side. When
the wall thickness of the tube is small and the thermal
conductivity of the tube material is high, as is usually the case,
the thermal resistance of the tube is negligible (Rwall ≈ 0) and
the inner and outer surfaces of the tube are almost identical.
THE OVERALL HEAT TRANSFER COEFFICIENT
When the tube is finned on one side to enhance heat
transfer, the total heat transfer surface area on the finned
side is
๐ด =๐ด
=๐ด +๐ด
Representative values pf the over all heat
transfer coefficient in heat exchangers
Type of heat exchanger
Water-to-water
Water-to-oil
๐‘ 
๐ฎ, ๐–/๐ฆ๐Ÿ ⋅ ๐Š ∗
850-1700
100-350
Water-to-gasoline or kerosene
300-1000
Water-to-brine
600-1200
Feedwater heaters
Steam-to-light fuel oil
Steam-to-heavy fuel oil
Steam condenser
1000-8500
unfined
For short fins of high thermal conductivity, we can use
this total area in the convection resistance relation
Rconv = 1/hAs
๐ด๐‘  = ๐ดunfinned + ๐œ‚fin ๐ดfin
To account for fin efficiency
50-200
1000-6000
300-1000
Ammonia condenser (water
cooled)
800-1400
Alcohol condensers (water
cooled)
250-700
10-40
Gas-to-brine
10-250
Oil-to-oil
50-400
Organic vapors-to-water
fin
200-400
Feron condenser(water cooled)
Gas-to-gas
total
700-1000
Organic solvents-to-organic
solvents
100-300
Water-to-air in finned tubes
(water in tubes)
30-60†
400-850†
Steam-to-air
in dinned
(steam
in
30-300
*Multiply
the listed
values
by 0.176
to convert them to Btu/h
⋅ ft 2 †⋅ โ„‰
tubes)
† Based on air-side surface area.
‡ Based on water- or steam-side surface area.
400-4000‡
Representative values of the overall heat transfer coefficient U are
given in Table 22–1. Note that the overall heat transfer coefficient
ranges from about 10 W/m2·K for gas-to-gas heat exchangers to
about 10,000 W/m2·K for heat exchangers that involve phase
changes. This is not surprising, since gases have very low thermal
conductivities, and phase-change processes involve very high heat
transfer coefficients. For short fins of high thermal conductivity, we
can use this total area in the convection resistance relation Rconv =
1/hAs since the fins in this case will be very nearly isothermal.
Otherwise, we should determine the effective surface area where
the fin efficiency can be obtained from the relationships discussed in
Chap. 17. This way, the temperature drop along the fins is accounted
for. Note that hfin = 1 for isothermal fins.
THE OVERALL HEAT TRANSFER COEFFICIENT
Fouling Factor
The fouling factor increases with the operating
temperature and the length of service and
decreases with the velocity of the fluids.
The performance of heat exchangers usually deteriorates with
time as a result of accumulation of deposits on heat transfer
surfaces. The layer of deposits represents additional resistance
to heat transfer. This is represented by a fouling factor ๐‘น๐’‡ .
๐‘…๐‘“,๐‘– ln (๐ท๐‘œ Τ๐ท๐‘– ) ๐‘…๐‘“,๐‘œ
1
1
1
1
1
=
=
=๐‘…=
+
+
+
+
๐‘ˆ๐ด๐‘  ๐‘ˆ๐‘– ๐ด๐‘– ๐‘ˆ๐‘œ ๐ด๐‘œ
โ„Ž๐‘– ๐ด๐‘–
๐ด๐‘–
2๐œ‹๐‘˜๐ฟ
๐ด๐‘œ
โ„Ž๐‘œ ๐ด๐‘œ
The most common type of fouling is the precipitation of solid deposits in a fluid
on the heat transfer surfaces. To avoid this potential problem, water in power
and process plants is extensively treated and its solid contents are removed
before it is allowed to circulate through the system. The solid ash particles in the
flue gases accumulating on the surfaces of air preheaters create similar
problems. Another form of fouling, which is common in the chemical process
industry, is corrosion and other chemical fouling. In this case, the surfaces are
fouled by the accumulation of the products of chemical reactions on the
surfaces. This form of fouling can be avoided by coating metal pipes with glass
or using plastic pipes instead of metal ones. Heat exchangers may also be fouled
by the growth of algae in warm fluids. This type of fouling is called biological
fouling and can be prevented by chemical treatment. In applications where it is
likely to occur, fouling should be considered in the design and selection of heat
exchangers. In such applications, it may be necessary to select a larger and thus
more expensive heat exchanger to ensure that it meets the design heat transfer
requirements even after fouling occurs. The periodic cleaning and the resulting
down time are additional penalties associated with fouling.
Representative fouling factors
(thermal resistanace due to
fouling for a unit surface area)
Fluid
R๐‘“ , m2 ⋅ K/W
Distilled water,
Sea-water, river water,
Boiler feedwater:
Below 50โ„ƒ
0.0001
Above 50โ„ƒ
0.0002
Fuel oil
0.0009
Transfer, lubricating
or hydraulic oil
0.0002
Quenching oil
0.0007
Vegetable oil
0.0005
Steam (oil-free)
0.0001
Steam (with oil traces)
0.0002
Organic solvent vapors,
natural gas
0.0002
Engine exhaust and
fuel gases
0.0018
Refrigerants (liquid)
0.0002
Refrigerants (vapor)
0.0004
Ethylene and methylene
glycol(antifreeze) and
amine solutions
0.00035
Alcohol vapors
0.0001
Air
0.0004
EXAMPLE 22.1
Hot oil is to be cooled in a double-tube counter-flow heat exchanger. The copper inner tubes
have a diameter of 2 cm and negligible thickness. The inner diameter of the outer tube (the
shell) is 3 cm. Water flows through the tube at a rate of 0.5 kg/s, and the oil through the shell at
a rate of 0.8 kg/s. Taking the average temperatures of the water and the oil to be 45°C and
80°C, respectively, determine the overall heat transfer coefficient of this heat exchanger.
The properties of water at 45°C are (Table A–15)
Assumptions: The thermal resistance of the
ρ = 990.1 kg/m3 Pr = 3.91
inner tube is negligible since the tube
k = 0.637 W/m.K ν = μ/ρ = 0.602 x 10-6 m2/s
material is highly conductive and its thickness
The properties of oil at 80°C are (Table A–19)
is negligible. Both the oil and water flow are
fully developed. Properties of the oil and
ρ = 852 kg/m3
Pr = 499.3
water are constant.
k = 0.138 W/m.K ν = 3.794 x 10-5 m2/s
The schematic of the heat exchanger is given in Fig. 22–11. The overall heat transfer coefficient
U can be determined from Eq. 22–5:
where hi and ho are the convection heat transfer coefficients inside and outside the tube,
respectively, which are to be determined using the forced convection relations. The hydraulic
diameter for a circular tube is the diameter of the tube itself, Dh = D = 0.02 m. The average
velocity of water in the tube and the Reynolds number are
EXAMPLE 22.1
which is greater than 10,000. Therefore, the flow of water is turbulent. Assuming the flow to be
fully developed, the Nusselt number can be determined from
Assumptions: The thermal resistance of the
inner tube is negligible since the tube
material is highly conductive and its thickness
is negligible. Both the oil and water flow are
fully developed. Properties of the oil and
water are constant.
Now we repeat the analysis above for oil.
The hydraulic diameter for the annular space is
Dh = Do - Di = 0.03 - 0.02 = 0.01 m
The average velocity and the Reynolds number in this case are
which is less than 2300. Therefore, the flow of oil is laminar. Assuming fully developed flow, the
Nusselt number on the tube side of the annular space i corresponding to Di/Do = 0.02/0.03 =
0.667 can be determined from Table 22–3 by interpolation to be
Nu = 5.45
EXAMPLE 22.1
Then the overall heat transfer coefficient for this heat exchanger becomes
Discussion: Note that U ≈ ho in this case, since hi โ‰ซ ho. This confirms our
earlier statement that the overall heat transfer coefficient in a heat
exchanger is dominated by the smaller heat transfer coefficient when the
difference between the two values is large. To improve the overall heat
transfer coefficient and thus the heat transfer in this heat exchanger, we
must use some enhancement techniques on the oil side, such as a finned
surface.
EXAMPLE 22.2
A double-pipe (shell-and-tube) heat exchanger is constructed of a stainless
steel (k = 15.1 W/mโˆ™K) inner tube of inner diameter Di = 1.5 cm and outer
diameter Do = 1.9 cm and an outer shell of inner diameter 3.2 cm. The
convection heat transfer coefficient is given to be hi = 800 W/m2.K on the
inner surface of the tube and ho = 1200 W/m2.K on the outer surface. For a
fouling factor of Rf,i = 0.0004 m2โˆ™K/W on the tube side and Rf,o = 0.0001 m2โˆ™K/W on the shell
side, determine (a) the thermal resistance of the heat exchanger per unit length and (b) the
overall heat transfer coefficients Ui and Uo based on the inner and outer surface areas of the
tube, respectively.
The schematic of the heat exchanger is given in Fig. 22–12. The thermal resistance for an
unfinned shell-and-tube heat exchanger with fouling on both heat transfer surfaces is given by
Eq. 22–8 as
where
Assumptions: The heat transfer
coefficients and the fouling
factors are constant and
uniform.
EXAMPLE 22.2
Substituting, the total thermal resistance is determined to be
Note that about 19 percent of the total thermal resistance in this case is due to fouling and
about 5 percent of it is due to the steel tube separating the two fluids. The rest (76 percent) is
due to the convection resistances.
(b) Knowing the total thermal resistance and the heat transfer surface areas, the overall heat
transfer coefficients based on the inner and outer surfaces of the tube are
Discussion: Note that the two overall heat transfer coefficients
differ significantly (by 27 percent) in this case because of the
considerable difference between the heat transfer surface areas
on the inner and the outer sides of the tube. For tubes of
negligible thickness, the difference between the two overall heat
transfer coefficients would be negligible.
ANALYSIS OF HEAT EXCHANGERS
An engineer often finds himself or herself in a position:
1. to select a heat exchanger that will achieve a specified temperature
change in a fluid stream of known mass flow rate - the log mean
temperature difference (or LMTD) method.
2. to predict the outlet temperatures of the hot and cold fluid streams in
a specified heat exchanger - the effectiveness–NTU method.
The rate of heat transfer in heat exchanger (HE is insulated):
๐‘„แˆถ = ๐‘šแˆถโ„Ž ๐ถ๐‘โ„Ž ๐‘‡โ„Ž,in − ๐‘‡โ„Ž,out
๐‘„แˆถ = ๐‘šแˆถ ๐‘ ๐ถ๐‘๐‘ ๐‘‡๐‘,out − ๐‘‡๐‘,in
๐‘šแˆถ ๐‘ , ๐‘šแˆถ โ„Ž = mass flow rate
๐ถ๐‘๐‘ , ๐ถ๐‘โ„Ž = specific heats
๐‘‡๐‘,out , ๐‘‡โ„Ž,out = outlet temperatures
๐‘‡๐‘,๐‘–๐‘› , ๐‘‡โ„Ž,in = inlet temperatures
๐‘„แˆถ = ๐ถ๐‘ ๐‘‡๐‘,out − ๐‘‡๐‘,in
heat capacity rate
๐ถโ„Ž = ๐‘šแˆถโ„Ž ๐ถ๐‘โ„Ž and
๐ถ๐‘ = ๐‘šแˆถ ๐‘ ๐ถ๐‘๐‘
๐‘„แˆถ = ๐ถโ„Ž ๐‘‡โ„Ž,in − ๐‘‡โ„Ž,out
Two fluid streams that have the
same capacity rates experience the
same temperature change in a wellinsulated heat exchanger.
The first law of thermodynamics requires that the rate of heat transfer from the hot fluid be equal to the rate of heat
transfer to the cold one. In heat exchanger analysis, it is often convenient to combine the product of the mass flow
rate and the specific heat of a fluid into a single quantity. This quantity is called the heat capacity rate and is defined
for the hot and cold fluid streams. The heat capacity rate of a fluid stream represents the rate of heat transfer needed
to change the temperature of the fluid stream by 1°C as it flows through a heat exchanger. Note that in a heat
exchanger, the fluid with a large heat capacity rate experiences a small temperature change, and the fluid with a small
heat capacity rate experiences a large temperature change. Therefore, doubling the mass flow rate of a fluid while
leaving everything else unchanged will halve the temperature change of that fluid.
ANALYSIS OF HEAT EXCHANGERS
๐‘„แˆถ = ๐‘šโ„Ž
แˆถ ๐‘“๐‘”
๐‘šแˆถ is the rate of evaporation or condensation of the fluid
โ„Ž๐‘“๐‘” is the enthalpy of vaporization of the fluid at the specified temperature or
pressure.
The heat capacity rate of a fluid during a phase-change process must
approach infinity since the temperature change is practically zero.
โˆ†๐‘‡๐‘š an appropriate mean (average) temperature difference
between the two fluids
Two special types of heat exchangers commonly used in practice are condensers and
boilers. One of the fluids in a condenser or a boiler undergoes a phase-change
process. An ordinary fluid absorbs or releases a large amount of heat essentially at
constant temperature during a phase-change process. The heat capacity rate of a
fluid during a phase-change process must approach infinity since the temperature
change is practically zero. That is, C = ๐‘šc
แˆถ p โ‰ซ ∞ when ΔT โ‰ซ 0, so that the heat
transfer rate ๐‘„แˆถ = cpΔT is a finite quantity. Therefore, in heat exchanger analysis, a
condensing or boiling fluid is conveniently modeled as a fluid whose heat capacity
rate is infinity. The rate of heat transfer in a heat exchanger can also be expressed in
an analogous manner to Newton’s law of cooling. Here the surface area As can be
determined precisely using the dimensions of the heat exchanger. However, the
overall heat transfer coefficient U and the temperature difference ΔT between the
hot and cold fluids, in general, may vary along the heat exchanger. The average value
of the overall heat transfer coefficient can be determined as described in the
preceding section by using the average convection coefficients for each fluid. It turns
out that the appropriate form of the average temperature difference between the
two fluids is logarithmic in nature.
(a) Boiler ๐ถ๐‘ → ∞
๐‘„แˆถ = ๐‘ˆ๐ด๐‘  โˆ†๐‘‡๐‘š
(b) Condenser ๐ถโ„Ž → ∞
Variation of fluid
temperatures in a heat
exchanger when one of
the fluids condenses or
boils.
THE LOG MEAN TEMPERATURE DIFFERENCE METHOD
๐›ฟ ๐‘„แˆถ = −๐‘šแˆถโ„Ž ๐‘๐‘โ„Ž ๐‘‘๐‘‡โ„Ž
๐›ฟ ๐‘„แˆถ
๐‘‘๐‘‡โ„Ž = −
๐‘šแˆถ โ„Ž ๐‘๐‘โ„Ž
๐‘‘๐‘‡โ„Ž − ๐‘‘๐‘‡๐‘ = ๐‘‘ ๐‘‡โ„Ž − ๐‘‡๐‘ = −๐›ฟ ๐‘„แˆถ
๐›ฟ ๐‘„แˆถ = ๐‘ˆ ๐‘‡โ„Ž − ๐‘‡๐‘ ๐‘‘๐ด๐‘ 
ln
๐›ฟ ๐‘„แˆถ = −๐‘šแˆถ ๐‘ ๐‘๐‘๐‘ ๐‘‘๐‘‡๐‘
๐›ฟ ๐‘„แˆถ
๐‘‘๐‘‡๐‘ =
๐‘šแˆถ ๐‘ ๐‘๐‘๐‘
แˆถ
1
1
+
๐‘šแˆถ โ„Ž ๐‘๐‘โ„Ž ๐‘šแˆถ ๐‘ ๐‘๐‘๐‘
๐‘‘(๐‘‡โ„Ž − ๐‘‡๐‘ )
1
1
= −๐‘ˆ๐ด๐‘ 
+
๐‘‡โ„Ž − ๐‘‡๐‘
๐‘šแˆถ โ„Ž ๐‘๐‘โ„Ž ๐‘šแˆถ ๐‘ ๐‘๐‘๐‘
โˆ†๐‘‡โ„Ž,out − ๐‘‡๐‘,out
1
1
= −๐‘ˆ๐ด๐‘ 
+
๐‘‡โ„Ž,in − ๐‘‡๐‘,in
๐‘šแˆถ โ„Ž ๐‘๐‘โ„Ž ๐‘šแˆถ ๐‘ ๐‘๐‘๐‘
Earlier, we mentioned that the temperature difference between the hot
and cold fluids varies along the heat exchanger, and it is convenient to have
a mean temperature difference. In order to develop a relation for the
equivalent average temperature difference between the two fluids,
consider the parallel-flow double-pipeheat exchanger. Assuming the outer
surface of the heat exchanger to be well insulated so that any heat transfer
occurs between the two fluids, and disregarding any changes in kinetic and
potential energy, an energy balance on each fluid in a differential section of
the heat exchanger can be determined. That is, the rate of heat loss from
the hot fluid at any section of a heat exchanger is equal to the rate of heat
gain by the cold fluid in that section. Solving the equations gives the log
mean temperature difference, which is the suitable form of the average
temperature difference for use in the analysis of heat exchangers. Here ΔT1
and ΔT2 represent the temperature difference between the two fluids at
the two ends (inlet and outlet) of the heat exchanger.
Variation of the fluid temperatures in
a parallel-flow double-pipe heat
exchanger.
๐‘„แˆถ = ๐‘ˆ๐ด๐‘  โˆ†๐‘‡lm
โˆ†๐‘‡lm =
โˆ†๐‘‡1 − โˆ†๐‘‡2
ln (โˆ†๐‘‡1 Τโˆ†๐‘‡2 )
log mean
temperature
difference
THE LOG MEAN TEMPERATURE
DIFFERENCE METHOD
The arithmetic mean temperature difference
1
โˆ†๐‘‡1 + โˆ†๐‘‡2
2
The logarithmic mean temperature difference ๏„Tlm is an
exact representation of the average temperature difference
between the hot and cold fluids.
Note that โˆ†๐‘‡lm is always less than โˆ†๐‘‡am . Therefore, using
โˆ†๐‘‡am in calculations instead of โˆ†๐‘‡lm will overestimate the
rate of heat transfer in a heat exchanger between the two
fluids.
When โˆ†๐‘‡1 differs from โˆ†๐‘‡2 by no more than 40 percent, the
error in using the arithmetic mean temperature difference is
less than 1 percent. But the error increases to undesirable
levels when โˆ†๐‘‡1 differs from โˆ†๐‘‡2 by greater amounts.
โˆ†๐‘‡am =
(a) Parallel-flow heat exchangers
(b) Counter-flow heat exchangers
The โˆ†๐‘‡1 and โˆ†๐‘‡2 expressions in parallelflow and counter-flow heat exchangers.
For multipass and cross-flow heat exchangers, as will be shown later,
the log mean temperature difference should be corrected through a
correction factor. The temperature difference between the two fluids
decreases from ΔT1 at the inlet to ΔT2 at the outlet. The logarithmic
mean temperature difference reflects the exponential decay of the
local temperature difference. We should always use the logarithmic
mean temperature difference when determining the rate of heat
transfer in a heat exchanger.
THE LOG MEAN TEMPERATURE DIFFERENCE METHOD
Counter-Flow Heat Exchangers
In the limiting case, the cold fluid will be heated to the inlet
temperature of the hot fluid. However, the outlet temperature
of the cold fluid can never exceed the inlet temperature of the
hot fluid.
For specified inlet and outlet temperatures, ๏„Tlm a counterflow heat exchanger is always greater than that for a parallelflow heat exchanger.
That is, โˆ†๐‘‡lm,CF > โˆ†๐‘‡lm,PF , and thus a smaller surface area
(and thus a smaller heat exchanger) is needed to achieve a
specified heat transfer rate in a counter-flow heat exchanger.
The variation of the fluid
temperatures in a counter-flow
double-pipe heat exchanger.
When the heat capacity rates
of the two fluids are equal
โˆ†๐‘‡lm = โˆ†๐‘‡1 = โˆ†๐‘‡2
The hot and cold fluids enter the heat exchanger from opposite ends, and
the outlet temperature of the cold fluid in this case may exceed the outlet
temperature of the hot fluid. The relation already given for the log mean
temperature difference is developed using a parallel-flow heat exchanger,
but we can show by repeating the analysis for a counter-flow heat
exchanger that is also applicable to counter-flow heat exchangers. It is
common practice to use counter-flow arrangements in heat exchangers. In
a counter-flow heat exchanger, the temperature difference between the hot
and the cold fluids remains constant along the heat exchanger when the
heat capacity rates of the two fluids are equal (i.e., ΔT = constant when Ch =
Cc or ๐‘šแˆถ hcph = ๐‘šแˆถ ccpc). Then we have ΔT1 = ΔT2. A condenser or a boiler can be
considered to be either a parallel- or counterflow heat exchanger since both
approaches give the same result.
THE LOG MEAN TEMPERATURE DIFFERENCE METHOD
Multipass and Cross-Flow Heat Exchangers:
Use of a Correction Factor
โˆ†๐‘‡l๐‘š = ๐น โˆ†๐‘‡l๐‘š,CF
F correction factor depends on the geometry of the heat
exchanger and the inlet and outlet temperatures of the hot and
cold fluid streams.
Heat transfer rate:
๐‘„แˆถ = ๐‘ˆ๐ด๐‘  ๐นโˆ†๐‘‡lm,CF
Where
โˆ†๐‘‡lm,CF =
โˆ†๐‘‡1 −โˆ†๐‘‡2
ln โˆ†๐‘‡1 Τโˆ†๐‘‡2
โˆ†๐‘‡1 = ๐‘‡โ„Ž,in − ๐‘‡๐‘,out
โˆ†๐‘‡2 = ๐‘‡โ„Ž,out − ๐‘‡๐‘,in
and
๐น = โ‹ฏ (Fig, 22 − 19)
The determination of the heat
transfer rate for cross-flow and
multipass shell-and-tube heat
exchangers using the correction
factor
F = 1 for a condenser or
boiler
F for common cross-flow and shell-and-tube heat exchanger
configurations is given in the figure versus two temperature
ratios P and R defined as
๐‘ƒ=
๐‘ก2 − ๐‘ก1
๐‘‡1 − ๐‘ก1
๐‘…=
๐‘š๐‘
แˆถ ๐‘
๐‘‡1 − ๐‘‡2
=
๐‘ก2 − ๐‘ก1
๐‘š๐‘
แˆถ ๐‘
tube side
shell side
1 and 2 inlet and outlet
T and t shell- and tube-side temperatures
The log mean temperature difference relation developed earlier is limited to
parallel-flow and counter-flow heat exchangers only. Similar relations are also
developed for cross-flow and multipass shell-and-tube heat exchangers, but the
resulting expressions are too complicated because of the complex flow
conditions. In such cases, it is convenient to relate the equivalent temperature
difference to the log mean temperature difference relation for the counter-flow
case. The correction factor is less than unity for a cross-flow and multipass shelland-tube heat exchanger. That is, F ≤ 1. The limiting value of F = 1 corresponds to
the counter-flow heat exchanger. Thus, the correction factor F for a heat
exchanger is a measure of deviation of the ΔTlm from the corresponding values
for the counter-flow case. Note that for a shell-and-tube heat exchanger, T and t
represent the shell- and tube-side temperatures, respectively, as shown in the
correction factor charts.
THE LOG MEAN TEMPERATURE DIFFERENCE METHOD
Multipass and Cross-Flow Heat Exchangers:
Use of a Correction Factor
Correction factor F
charts for common
cross-flow heat
exchangers.
(a) One-shell pass and 2,4,6, etc.(any multiple of 2), tube passes
(b) Two-shell passes and 4,8,12, etc. (any multiple of 4), tube passes
THE LOG MEAN TEMPERATURE DIFFERENCE METHOD
Multipass and Cross-Flow Heat Exchangers:
Use of a Correction Factor
Correction factor F
charts for common
cross-flow heat
exchangers.
(c) Single-pass cross-flow with both fluids unmixed
(d) Single-pass cross-flow with one fluid mixed and the other unmixed
THE LOG MEAN TEMPERATURE DIFFERENCE METHOD
Multipass and Cross-Flow Heat Exchangers:
Use of a Correction Factor
The LMTD method is very suitable for determining the size of a heat exchanger to realize
prescribed outlet temperatures when the mass flow rates and the inlet and outlet temperatures
of the hot and cold fluids are specified.
With the LMTD method, the task is to select a heat exchanger that will meet the prescribed heat
transfer requirements. The procedure to be followed by the selection process is:
1. Select the type of heat exchanger suitable for the application.
2. Determine any unknown inlet or outlet temperature and the heat transfer rate using an energy
balance.
3. Calculate the log mean temperature difference โˆ†๐‘‡lm, and the correction factor F, if necessary.
4. Obtain (select or calculate) the value of the overall heat transfer coefficient U.
5. Calculate the heat transfer surface area ๐ด๐‘  .
The task is completed by selecting a heat exchanger that has a heat transfer surface area equal to
or larger than ๐ด๐‘  .
It makes no difference whether the hot or the cold fluid flows through the shell or the tube. The determination of the
correction factor F requires the availability of the inlet and the outlet temperatures for both the cold and hot fluids.
Note that the value of P ranges from 0 to 1. The value of R, on the other hand, ranges from 0 to infinity, with R = 0
corresponding to the phase change (condensation or boiling) on the shell-side and R โ‰ซ ∞to phase change on the tube
side. The correction factor is F = 1 for both of these limiting cases. Therefore, the correction factor for a condenser or
boiler is F = 1, regardless of the configuration of the heat exchanger.
EXAMPLE 22.3
Steam in the condenser of a power plant is to be condensed at a temperature
of 30°C with cooling water from a nearby lake, which enters the tubes of the
condenser at 14°C and leaves at 22°C. The surface area of the tubes is 45 m2,
and the overall heat transfer coefficient is 2100 W/m2.K. Determine the mass flow rate of the
cooling water needed and the rate of condensation of the steam in the condenser.
Properties: The heat of vaporization of water at 30°C is hfg = 2431 kJ/kg and the specific heat of
cold water at the average temperature of 18°C is cp = 4184 J/kg.K (Table A–15).
The schematic of the condenser is given in Fig. 22–20. The condenser can be treated as a
counter-flow heat exchanger since the temperature of one of the fluids (the steam) remains
constant. The temperature difference between the steam and the cooling water at
the two ends of the condenser is
Assumptions: Steady operating conditions exist. The heat exchanger is
well insulated so that heat loss to the surroundings is negligible.
Changes in the kinetic and potential energies of fluid streams are
negligible. There is no fouling. Fluid properties are constant.
That is, the temperature difference between the two fluids varies from 8°C at one end to 16°C at
the other. The proper average temperature difference between the two fluids is the log mean
temperature difference (not the arithmetic), which is determined from
EXAMPLE 22.3
This is a little less than the arithmetic mean temperature difference of
½(8 + 16) = 12°C. Then the heat transfer rate in the condenser is determined
From
Therefore, steam will lose heat at a rate of 1087 kW as it flows through the condenser, and the
cooling water will gain practically all of it, since the condenser is well insulated.
The mass flow rate of the cooling water and the rate of the condensation of the steam are
determined from ๐‘„แˆถ = [๐‘šc
แˆถ p(Tout - Tin)]cooling water = (๐‘šh
แˆถ fg)steam
to be
Discussion: Therefore, we need to circulate about 72 kg of cooling
water for each 1 kg of steam condensing to remove the heat released
during the condensation process.
EXAMPLE 22.4
A counter-flow double-pipe heat exchanger is to heat water from 20°C to 80°C at a rate of 1.2
kg/s. The heating is to be accomplished by geothermal water available at 160°C at a mass flow
rate of 2 kg/s. The inner tube is thin-walled and has a diameter of 1.5 cm. If the overall heat
transfer coefficient of the heat exchanger is 640 W/m2.K, determine the length of the heat
exchanger required to achieve the desired heating.
We take the specific heats of water and geothermal fluid to be 4.18 and 4.31 kJ/kg.K,
respectively.
The schematic of the heat exchanger is given in Fig. 22–21. The rate of heat transfer in the
heat exchanger can be determined from
Noting that all of this heat is supplied by the geothermal water, the outlet temperature of the
geothermal water is determined to be
Assumptions: Steady operating conditions exist. The heat
exchanger is well insulated so that heat loss to the
surroundings is negligible. Changes in the kinetic and
potential energies of fluid streams are negligible. There is
no fouling. Fluid properties are constant.
EXAMPLE 22.4
Knowing the inlet and outlet temperatures of both fluids, the logarithmic mean temperature
difference for this counter-flow heat exchanger becomes
Then the surface area of the heat exchanger is determined to be
To provide this much heat transfer surface area, the length of the tube must be
Discussion: The inner tube of this counter-flow heat
exchanger (and thus the heat exchanger itself) needs to be
over 100 m long to achieve the desired heat transfer, which
is impractical. In cases like this, we need to use a plate heat
exchanger or a multipass shell-and-tube heat exchanger
with multiple passes of tube bundles.
EXAMPLE 22.5
A two-shell passes and four-tube passes heat exchanger is used to heat
glycerin from 20°C to 50°C by hot water, which enters the thin-walled 2-cm diameter tubes at
80°C and leaves at 40°C. The total length of the tubes in the heat exchanger is 60 m. The
convection heat transfer coefficient is 25 W/m2โˆ™K on the glycerin (shell) side and 160 W/m2โˆ™K on
the water (tube) side. Determine the rate of heat transfer in the heat exchanger (a) before any
fouling and (b) after fouling with a fouling factor of 0.0006 m2โˆ™K/W occurs on the outer surfaces
of the tubes.
The tubes are said to be thin-walled, and thus it is reasonable to assume the inner and outer
surface areas of the tubes to be equal. Then the heat transfer surface area becomes
The rate of heat transfer in this heat exchanger can be determined from
where F is the correction factor and ΔTlm,CF is the log mean temperature difference for the
counter-flow arrangement. These two quantities are determined from
Assumptions: Steady operating conditions exist. The heat exchanger is
well insulated so that heat loss to the surroundings is negligible.
Changes in the kinetic and potential energies of fluid streams are
negligible. Heat transfer coefficients and fouling factors are constant
and uniform. The thermal resistance of the inner tube is negligible
since the tube is thinwalled and highly conductive.
EXAMPLE 22.5
and
(a) In the case of no fouling, the overall heat transfer coefficient U is
Then the rate of heat transfer becomes
(b) When there is fouling on one of the surfaces, we have
and
Discussion: Note that the rate of
heat transfer decreases as a result of
fouling, as expected. The decrease is
not dramatic, however, because of
the relatively low convection heat
transfer coefficients involved.
EXAMPLE 22.6
A test is conducted to determine the overall heat transfer coefficient in an
automotive radiator that is a compact cross-flow water-to-air heat
Exchanger with both fluids (air and water) unmixed. The radiator has 40 tubes of internal
diameter 0.5 cm and length 65 cm in a closely spaced plate-finned matrix. Hot water enters the
tubes at 90°C at a rate of 0.6 kg/s and leaves at 65°C. Air flows across the radiator through the
interfin spaces and is heated from 20°C to 40°C. Determine the overall heat transfer coefficient
Ui of this radiator based on the inner surface area of the tubes.
The specific heat of water at the average temperature of (90 + 65)/2 = 77.5°C is 4.195 kJ/kg.K
(Table A–15).
The rate of heat transfer in this radiator from the hot water to the air is determined from an
energy balance on water flow:
The tube-side heat transfer area is the total surface area of the tubes, and is determined from
Knowing the rate of heat transfer and the surface area, the overall heat transfer coefficient can
be determined from
Assumptions: Steady operating conditions
exist. Changes in the kinetic and potential
energies of fluid streams are negligible. Fluid
properties are constant.
EXAMPLE 22.6
where F is the correction factor and ΔTlm,CF is the log mean temperature
difference for the counter-flow arrangement. These two quantities are
found to be
and
Substituting, the overall heat transfer coefficient Ui is determined to be
Discussion: Note that the overall heat
transfer coefficient on the air side will
be much lower because of the large
surface area involved on that side.
THE EFFECTIVENESS–NTU METHOD
A second kind of problem encountered in heat exchanger analysis is
the determination of the heat transfer rate and the outlet
temperatures of the hot and cold fluids for prescribed fluid mass flow
rates and inlet temperatures when the type and size of the heat
exchanger are specified.
Heat transfer effectiveness
๐œ€=
๐‘„แˆถ
๐‘„max
Actual heat transfer rate
=
Maximum possible heat transfer rate
แˆถ −๐‘‡
๐‘„แˆถ = ๐ถ๐‘ ๐‘‡๐‘,out
๐‘,in = ๐ถ๐‘ ๐‘‡โ„Ž,in − ๐‘‡๐‘,out
๐ถ๐‘ = ๐‘šแˆถ ๐‘ ๐‘๐‘๐‘ and ๐ถโ„Ž = ๐‘šแˆถ ๐‘ ๐‘๐‘โ„Ž
โˆ†๐‘‡max = ๐‘‡โ„Ž,in − ๐‘‡๐‘,in
Qแˆถ max = ๐ถmin ๐‘‡โ„Ž,in − ๐‘‡๐‘,in
the maximum possible heat transfer rate
๐ถmin is the smaller of ๐ถโ„Ž and ๐ถ๐‘
๐ถ๐‘ = ๐‘šแˆถ ๐‘ ๐‘๐‘๐‘
= 104.5 kW/K
๐ถโ„Ž = ๐‘šแˆถ ๐‘ ๐‘๐‘โ„Ž
= 92 kW/K
๐ถmin = 92 kW/K
โˆ†๐‘‡max = ๐‘‡โ„Ž,in − ๐‘‡๐‘,in = 110โ„ƒ
๐‘„แˆถ max = ๐ถmin โˆ†๐‘‡max = 10,120 kw
The determination of the
maximum rate of heat transfer
in a heat exchanger.
The heat transfer surface area of the heat exchanger in this case is known,
but the outlet temperatures are not. The LMTD method could still be used
for this alternative problem, but the procedure would require tedious
iterations, and thus it is not practical. To determine the maximum possible
heat transfer rate in a heat exchanger, we first recognize that the maximum
temperature difference in a heat exchanger is the difference between the
inlet temperatures of the hot and cold fluids. The heat transfer in a heat
exchanger will reach its maximum value when (1) the cold fluid is heated
to the inlet temperature of the hot fluid or (2) the hot fluid is cooled to the
inlet temperature of the cold fluid. These two limiting conditions will not
be reached simultaneously unless the heat capacity rates of the hot and
cold fluids are identical (i.e., Cc = Ch ).
EXAMPLE 22.7
Cold water enters a counter-flow heat exchanger at 10°C at a rate of 8 kg/s, where it is heated
by a hot-water stream that enters the heat exchanger at 70°C at a rate of 2 kg/s. Assuming the
specific heat of water to remain constant at cp = 4.18 kJ/kg?K, determine the maximum heat
transfer rate and the outlet temperatures of the cold- and the hot-water streams for this
limiting case. A schematic of the heat exchanger is given in Fig. 22–25. The heat capacity rates
of the hot and cold fluids are
Assumptions: Steady operating conditions exist.
The heat exchanger is well insulated so that heat
loss to the surroundings is negligible. Changes in
the kinetic and potential energies of fluid streams
are negligible. Fluid properties are constant.
which is the smaller of the two heat capacity rates. Then the maximum heat
transfer rate is determined from Eq. 22–32 to be
That is, the maximum possible heat transfer rate in this heat exchanger is 502 kW. This value
would be approached in a counter-flow heat exchanger with a very large heat transfer surface
area.
EXAMPLE 22.7
The maximum temperature difference in this heat exchanger is ΔTmax = Th,in - Tc,in = (70 - 10)°C
= 60°C. Therefore, the hot water cannot be cooled by more than 60°C (to 10°C) in this heat
exchanger, and the cold water cannot be heated by more than 60°C (to 70°C), no matter what
we do. The outlet temperatures of the cold and the hot streams in this limiting case are
determined to be
Discussion Note that the hot water is cooled to the limit of 10°C (the inlet temperature of the coldwater stream), but the cold water is heated to 25°C only when maximum heat transfer occurs in the
heat exchanger. This is not surprising, since the mass flow rate of the hot water is only one-fourth that
of the cold water, and, as a result, the temperature of the cold water increases by 0.25°C for each 1°C
drop in the temperature of the hot water. You may be tempted to think that the cold water should be
heated to 70°C in the limiting case of maximum heat transfer. But this will require the temperature of
the hot water to drop to -170°C, which is impossible. Therefore, heat transfer in a heat exchanger
reaches its maximum value when the fluid with the smaller heat capacity rate (or the smaller mass
flow rate when both fluids have the same specific heat value) experiences the maximum temperature
change. This example explains why we use Cmin in the evaluation of ๐‘„แˆถ max instead of Cmax. We can
show that the hot water will leave at the inlet temperature of the cold water and vice versa in the
limiting case of maximum heat transfer when the mass flow rates of the hot- and cold-water streams
are identical. We can also show that the outlet temperature of the cold water will reach the 70°C limit
when the mass flow rate of the hot water is greater than that of the cold water.
THE EFFECTIVENESS–NTU METHOD
Actual heat transfer rate
๐‘„แˆถ = ๐œ€ ๐‘„แˆถ max = ๐œ€๐ถmin ๐‘‡โ„Ž,in − ๐‘‡๐‘,in
if ๐ถ๐‘ = ๐ถmin :
๐œ€=
if ๐ถโ„Ž = ๐ถmin :
๐œ€=
๐‘„แˆถ
๐‘„แˆถ max
๐‘„แˆถ
๐‘„แˆถ max
=
=
๐ถ๐‘ ๐‘‡๐‘,out − ๐‘‡๐‘,in
๐ถ๐‘ ๐‘‡โ„Ž,in − ๐‘‡๐‘,in
๐ถโ„Ž ๐‘‡โ„Ž,in − ๐‘‡โ„Ž,out
๐ถโ„Ž ๐‘‡โ„Ž,in − ๐‘‡๐‘,in
=
๐‘‡๐‘,out − ๐‘‡๐‘,in
๐‘‡โ„Ž,in − ๐‘‡๐‘,in
=
๐‘‡โ„Ž,out − ๐‘‡โ„Ž,out
๐‘‡โ„Ž,in − ๐‘‡๐‘,in
๐‘„แˆถ = ๐‘šแˆถ โ„Ž ๐‘๐‘โ„Ž โˆ†๐‘‡โ„Ž
= ๐‘šแˆถ โ„Ž ๐‘๐‘๐‘ โˆ†๐‘‡๐‘
If
๐‘šแˆถ โ„Ž ๐‘๐‘โ„Ž = ๐‘šแˆถ โ„Ž ๐‘๐‘โ„Ž
then โˆ†๐‘‡โ„Ž = โˆ†๐‘‡๐‘
The determination of ๐‘„แˆถ max requires the availability of the inlet temperature
of the hot and cold fluids and their mass flow rates, which are usually
specified. Then, once the effectiveness of the heat exchanger is known, the
actual heat transfer rate ๐‘„แˆถ can be determined. The effectiveness of a heat
exchanger enables us to determine the heat transfer rate without knowing
the outlet temperatures of the fluids. The effectiveness of a heat exchanger
depends on the geometry of the heat exchanger as well as the flow
arrangement. Therefore, different types of heat exchangers have different
effectiveness relations.
The temperature rise of the cold
fluid in a heat exchanger will be
equal to the temperature drop of
the hot fluid when the heat
capacity rates of the hot and
cold fluids are identical.
THE EFFECTIVENESS–NTU METHOD
ln
๐‘‡โ„Ž,out −๐‘‡๐‘,out
๐‘‡โ„Ž,in −๐‘‡๐‘,in
=−
๐‘‡โ„Ž,out = ๐‘‡โ„Ž,in −
The effectiveness of a heat
exchanger depends on the geometry
of the heat exchanger as well as the
flow arrangement.
Therefore, different types of heat
exchangers have different
effectiveness relations.
We illustrate the development of the
effectiveness e relation for the
double-pipe parallel-flow heat
exchanger.
ln
๐‘ˆ๐ด๐‘ 
๐ถ๐‘
1+
๐ถ๐‘
๐ถโ„Ž
๐ถ๐‘
๐‘‡
− ๐‘‡๐‘,in
๐ถโ„Ž ๐‘,out
๐ถ
๐‘‡โ„Ž,in −๐‘‡๐‘,in +๐‘‡๐‘,in −๐‘‡๐‘,out − ๐‘ ๐‘‡๐‘,out −๐‘‡๐‘,in
๐ถโ„Ž
=−
๐‘‡โ„Ž,in −๐‘‡๐‘,in
ln 1 − 1 +
๐œ€=
๐‘„แˆถ
๐‘„แˆถ max
๐œ€parallel flow
๐ถ๐‘
๐‘‡๐‘,out −๐‘‡๐‘,in
๐ถโ„Ž
๐‘‡โ„Ž,in −๐‘‡๐‘,in
=
=
๐‘ˆ๐ด๐‘ 
1+
๐ถ๐‘
๐ถ๐‘ ๐‘‡๐‘,out − ๐‘‡๐‘,in
๐ถmin ๐‘‡โ„Ž,in − ๐‘‡๐‘,in
→
๐‘ˆ๐ด๐‘ 
๐ถ๐‘
1+
๐œ€parallel flow =
๐ถโ„Ž
๐ถ๐‘
๐ถโ„Ž
Tc,out − ๐‘‡๐‘,in
๐ถmin
=๐œ€
๐‘‡โ„Ž,in − ๐‘‡๐‘,in
๐ถ๐‘
๐‘ˆ๐ด
๐ถ
1 − exp − ๐ถ ๐‘  1 + ๐ถ๐‘
๐‘
โ„Ž
=
๐ถ ๐ถmin
1 + ๐ถ๐‘ ๐ถ
โ„Ž
๐‘
๐‘ˆ๐ด๐‘ 
๐ถ
1 + min
๐ถmin
๐ถmax
๐ถ
1 + min
๐ถmax
1 − exp −
๐ถ๐‘
THE EFFECTIVENESS–NTU METHOD
Effectiveness relations of the heat exchangers typically involve the dimensionless group
๐‘ˆ๐ด๐‘  Τ๐ถmin .
This quantity is called the number of transfer units NTU.
๐‘ˆ๐ด๐‘ 
๐‘ˆ๐ด๐‘ 
NTU =
=
๐ถmin
๐‘š๐‘
แˆถ ๐‘ min
๐‘=
๐ถmin
๐ถmax
For specified values of U and ๐ถmin , the value of NTU is a measure of the
surface area ๐ด๐‘  . Thus, the larger the NTU, the larger the heat exchanger.
capacity ratio
The effectiveness of a heat exchanger is a function of the number of transfer units NTU and the
capacity ratio c.
๐œ€ = function ๐‘ˆ๐ด Τ๐ถ
, ๐ถ Τ๐ถ
= function(NTU, ๐‘)
๐‘ 
min
min
max
Effectiveness relations have been developed for a large number of heat exchangers, and the results are given in Table
22–4. The effectivenesses of some common types of heat exchangers are also plotted in Fig. 22–27 on the next page.
More extensive effectiveness charts and relations are available in the literature. The dashed lines in Fig. 22–27f are for
the case of Cmin unmixed and Cmax mixed and the solid lines are for the opposite case. The analytic relations
for the effectiveness give more accurate results than the charts, since reading errors in charts are unavoidable, and
the relations are very suitable for computerized analysis of heat exchangers.
THE EFFECTIVENESS–NTU METHOD
Effectiveness relations for heat exchangers NTU = ๐‘ˆ๐ด๐‘  Τ๐ถmin and ๐‘ =
๐ถmin เต—๐ถmax = ๐‘š๐‘
แˆถ ๐‘ min เต— ๐‘š๐‘
แˆถ ๐‘ max
Heat exchanger type
Effectiveness relation
1. Double pipe:
1−exp −NTU 1+๐‘
1+๐‘
Parallel-flow
๐œ€=
Counter-flow
๐œ€ = 1−๐‘ exp −NTU
1−exp −NTU 1−๐‘
1−๐‘
NTU
๐œ€ = 1+NTU
2. Shell-and-tube:
One-shell pass 2,
4, … tube Passes
n-shell passes
2n, 4n,… tube
Passes
3. Cross-flow (singlepass) Both fluids
Unmixed
(for ๐‘ = 1)
๐œ€1 = 2 1 + ๐‘ + 1 +
๐œ€๐‘› =
1−๐œ€1 ๐‘ ๐‘›
1−๐œ€1
๐œ€ = 1 − exp
1
๐‘
(for ๐‘ < 1)
−1
NTU0.22
๐‘
1+exp −NTU1 1+๐‘ 2
๐‘2
1−exp −NTU1 1+๐‘ 2
1−๐œ€1 ๐‘ ๐‘›
1−๐œ€1
−1
−๐‘
exp −๐‘NTU 0.78
๐ถmax mixed,
๐ถmin unmixed
๐œ€=
๐ถmin mixed,
๐ถmax unmixed
๐œ€ = 1 − exp − ๐‘ 1 − exp −๐‘ NTU
4. All heat
exchangers With
๐‘=0
1 − exp −๐‘ 1 − exp −NTU
1
๐œ€ = 1 − exp(−NTU)
−1
−1
THE EFFECTIVENESS–NTU METHOD
(a) Parallel-flow
(c) One-shell pass and 2,4, 6, … tube passes
(b) Counter-flow
(d) Two-shell passes and 4, 8, 12, … tube passes
Effectiveness for
heat exchangers.
THE EFFECTIVENESS–NTU METHOD
(e) Cross-flow with both fluids unmixed
Effectiveness for heat exchangers.
(f) Cross-flow with one fluid mixed and the other unmixed
THE EFFECTIVENESS–NTU METHOD
Observations from the effectiveness relations and charts
•
The value of the effectiveness ranges from 0 to 1. It increases rapidly
with NTU for small values (up to about NTU = 1.5) but rather slowly for
larger values. Therefore, the use of a heat exchanger with a large NTU (usually larger than 3) and
thus a large size cannot be justified economically, since a large increase in NTU in this case
corresponds to a small increase in effectiveness.
•
For a given NTU and capacity ratio c = ๐ถmin Τ๐ถmax , the counter-flow heat exchanger has the
highest effectiveness, followed closely by the cross-flow heat exchangers with both fluids
unmixed. The lowest effectiveness values are encountered in parallel-flow heat exchangers.
•
The effectiveness of a heat exchanger is independent of the capacity ratio c for NTU values of
less than about 0.3.
•
The value of the capacity ratio c ranges between 0 and 1. For a given NTU, the effectiveness
becomes a maximum for c = 0 (e.g., boiler, condenser) and a minimum for c = 1 (when the
heat capacity rates of the two fluids are equal).
In industrial applications such as hot water cooling or chilled water heating pertaining to heating, ventilating, and air
conditioning (HVAC) industry, the hot or cold fluid is channelled from one location to another with the pipe
immersed in ambient environment. In such cases, since the effective change in reference temperature of the
ambient environment is virtually zero and the relative mass of the ambient environment is infinitely large, the
maximum heat capacity rate Cmax is a very large number. Once the quantities c = Cmin/Cmax and NTU = UAs/Cmin have
been evaluated, the effectiveness ε can be determined from either the charts or the effectiveness relation for the
specified type of heat exchanger. Then the rate of heat transfer and the outlet temperatures can be determined.
When all the inlet and outlet temperatures are specified, the size of the heat exchanger can easily be determined
using the LMTD method. Alternatively, it can also be determined from the effectiveness–NTU method by first
evaluating the effectiveness and then the NTU from the appropriate NTU relation in Table 22–5
THE EFFECTIVENESS–NTU METHOD
For a specified NTU and capacity ratio c, the
counter-flow heat exchanger has the highest
effectiveness and the parallel-flow the lowest
The effectiveness relation reduces to
๐œ€ = ๐œ€max = 1 − exp −NTU for all
Heat exchangers when the capacity ratio ๐‘ = 0.
For a given NTU and capacity ratio c = Cmin/Cmax, the counter-flow heat exchanger has the highest effectiveness,
followed closely by the cross-flow heat exchangers with both fluids unmixed. As you might expect, the lowest
effectiveness values are encountered in parallel-flow heat exchangers (Fig. 22–28). The value of the capacity ratio c
ranges between 0 and 1.
For a given NTU, the effectiveness becomes a maximum for c = 0 and a minimum for c = 1. The case c = Cmin/Cmax โ‰ซ 0
corresponds to Cmax โ‰ซ ∞, which is realized during a phase-change process in a condenser or boiler. All effectiveness
relations in this case reduce to ε = εmax = 1 - exp(-NTU) regardless of the type of heat exchanger (Fig. 22–29). Note that
the temperature of the condensing or boiling fluid remains constant in this case.
Effectiveness relations for heat exchangers NTU = ๐‘ˆ๐ด๐‘  Τ๐ถmin and ๐‘ =
๐ถmin เต—๐ถmax = ๐‘š๐‘
แˆถ ๐‘ min เต— ๐‘š๐‘
แˆถ ๐‘ max
Heat exchanger type
NTU relation
1. Double-pipe:
Parallel-flow
Counter-flow
NTU = −
NTU =
2. Shell-and-tube:
One-shell pass
2, 4, … tube Passes
n-shell passes
2n, 4n,…tube
passes
ln 1−๐œ€ 1+๐‘
1
๐‘−1
NTU =
1+๐‘
๐œ€−1
ln
๐œ€
๐œ€−1
NTU1 = −
for ๐‘ < 1
๐œ€๐ถ−1
(for ๐‘ = 1)
1
1+๐‘ 2
ln
2Τ๐œ€1 −1−๐‘− 1+๐‘ 2
2Τ๐œ€1 −1−๐‘+ 1+๐‘ 2
NTU๐‘› = ๐‘› NTU 1
To find effectiveness of the heat exchanger
with one-shell pass use, ๐œ€1 =
Where ๐น =
๐œ€๐‘› ๐‘−1 1Τ๐‘›
๐œ€๐‘› −1
3. Cross-flow(singlepass):
๐ถmax mixed,
๐ถmin unmixed
NTU = −ln 1 +
๐ถmin mixed,
๐ถmax unmixed
NTU = −
4. All heat exchangers
with ๐‘ = 0
When all the inlet and outlet
temperatures are specified, the
size of the heat exchanger can
easily be determined using the
LMTD method.
ln 1−๐œ€๐ถ
๐‘
ln ๐‘ ln 1−๐œ€ +1
๐‘
NTU = −ln 1 − ๐œ€
๐น−1
๐น−๐‘
Alternatively, it can be
determined from the
effectiveness–NTU method by
first evaluating the
effectiveness from its definition
and then the NTU from the
appropriate NTU relation.
Note that the relations in Table 22–5
are equivalent to those in Table 22–4.
Both sets of relations are given for
convenience. The relations in Table
22–4 give the effectiveness directly
when NTU is known, and the
relations in Table 22–5 give the NTU
directly when the effectiveness ε is
known.
EXAMPLE 22.8
A counter-flow double-pipe heat exchanger is to heat water from 20°C to 80°C at a rate of 1.2
kg/s. The heating is to be accomplished by geothermal water available at 160°C at a mass flow
rate of 2 kg/s. The inner tube is thin-walled and has a diameter of 1.5 cm. The overall heat
transfer coefficient of the heat exchanger is 640 W/m2.K. Using the effectiveness–NTU method,
determine the length of the heat exchanger required to achieve the desired heating.
In the effectiveness–NTU method, we first determine the heat capacity rates of the hot and cold
fluids and identify the smaller one.
Then the maximum heat transfer rate is determined from
EXAMPLE 22.8
That is, the maximum possible heat transfer rate in this heat exchanger is 702.8 kW. The actual rate
of heat transfer is
Thus, the effectiveness of the heat exchanger is
Knowing the effectiveness, the NTU of this counter-flow heat exchanger can be determined from Fig.
22–27b or the appropriate relation from Table 22–5 for c < 1. We choose the latter approach for
greater accuracy:
Then the heat transfer surface area becomes
To provide this much heat transfer surface area, the length of the tube must be
Discussion This problem was solved in Example 22–4 using the LMTD method. Note that we
obtained practically the same result in a systematic and straightforward manner using the
effectiveness–NTU method.
EXAMPLE 22.9
Hot oil is to be cooled by water in a one-shell-pass and eight-tube-passes
heat exchanger. The tubes are thin-walled and are made of copper with an
internal diameter of 1.4 cm. The length of each tube pass in the heat exchanger is 5 m, and the
overall heat transfer coefficient is 310 W/m2.K. Water flows through the tubes at a rate of 0.2
kg/s, and the oil through the shell at a rate of 0.3 kg/s. The water and the oil enter at
temperatures of 20°C and 150°C, respectively. Determine the rate of heat transfer in the heat
exchanger and the outlet temperatures of the water and the oil.
We take the specific heats of water and oil to be 4.18 and 2.13 kJ/kg.°C, respectively.
The outlet temperatures are not specified, and they cannot be determined from an energy
balance. The use of the LMTD method in this case will involve tedious iterations, and thus the
ε–NTU method is indicated. The first step in the ε–NTU method is to determine the heat
capacity rates of the hot and cold fluids and identify the smaller one:
Then the maximum heat transfer rate is determined
Assumptions: Steady operating conditions exist.
The heat exchanger is well insulated so that heat
loss to the surroundings is negligible. The
thickness of the tube is negligible since it is thinwalled. Changes in the kinetic and potential
energies of fluid streams are negligible. The
overall heat transfer coefficient is constant and
uniform.
EXAMPLE 22.9
That is, the maximum possible heat transfer rate in this heat exchanger is
83.1 kW. The heat transfer surface area is
Then the NTU of this heat exchanger becomes
The effectiveness of this heat exchanger corresponding to c = 0.764 and NTU = 0.854 is
determined from Fig. 22–27c to be
We could also determine the effectiveness from the third relation in Table 22–4 more accurately
but with more labor. Then the actual rate of heat transfer becomes
Finally, the outlet temperatures of the cold and the hot fluid streams are determined to be
Therefore, the temperature of the cooling water will
rise from 20°C to 66.8°C as it cools the hot oil from
150°C to 88.8°C in this heat exchanger.
PROBLEMS
21–1C Classify heat exchangers according to flow type and explain the characteristics of each
type.
22–2C When is a heat exchanger classified as being compact? Do you think a double-pipe heat
exchanger can be classified as a compact heat exchanger?
22–3C What is a regenerative heat exchanger? How does a static type of regenerative heat
exchanger differ from a dynamic type?
22–4C What is the role of the baffles in a shell-and-tube heat exchanger? How does the presence
of baffles affect the heat transfer and the pumping power requirements? Explain.
22–5C How does a cross-flow heat exchanger differ from a counter-flow one? What is the
difference between mixed and unmixed fluids in cross-flow?
22–6C What are the heat transfer mechanisms involved during heat transfer in a liquid-to-liquid
heat exchanger from the hot to the cold fluid?
22–7C Under what conditions is the thermal resistance of the tube in a heat exchanger negligible?
22–8C Consider a double-pipe parallel-flow heat exchanger of length L. The inner and outer
diameters of the inner tube are D1 and D2, respectively, and the inner diameter of the outer tube is
D3. Explain how you would determine the two heat transfer surface areas Ai and Ao. When is it
reasonable to assume Ai ≈ Ao ≈ As?
22–9C How is the thermal resistance due to fouling in a heat exchanger accounted for? How do
the fluid velocity and temperature affect fouling?
PROBLEMS
22–10C In a thin-walled double-pipe heat exchanger, when is the approximation U = hi a
reasonable one? Here U is the overall heat transfer coefficient and hi is the convection heat
transfer coefficient inside the tube.
22–11C What are the common causes of fouling in a heat exchanger? How does fouling affect
heat transfer and pressure drop?
22–12C Under what conditions can the overall heat transfer coefficient of a heat exchanger be
determined from U = (1/hi + 1/ho)-1?
22–14 A long thin-walled double-pipe heat exchanger with tube and shell diameters of 1.0 cm and
2.5 cm, respectively, is used to condense refrigerant-134a by water at 20°C. The refrigerant flows
through the tube, with a convection heat transfer coefficient of hi 5 4100 W/m2·K. Water flows
through the shell at a rate of 0.3 kg/s. Determine the overall heat transfer coefficient of this heat
exchanger. Answer: 1856 W/m2โˆ™K
22–15 Repeat Prob. 22–14 by assuming a 2-mm-thick layer of limestone (k = 1.3 W/m·K) forms
on the outer surface of the inner tube.
22–18 A jacketted-agitated vessel, fitted with a turbine agitator, is used for heating a water stream
from 10°C to 54°C. The average heat transfer coefficient for water at the vessel’s inner-wall can
be estimated from Nu = 0.76Re2/3Pr1/3. Saturated steam at 100°C condenses in the jacket, for
which the average heat transfer coefficient in kW/m2·K is ho = 13.1(Tg - Tw)-0.25. The vessel
dimensions are Dt = 0.6 m, H = 0.6 m and Da = 0.2 m. The agitator speed is 60 rpm. Calculate the
mass rate of water that can be heated in this agitated vessel steadily.
PROBLEMS
22–20 Water at an average temperature of 110°C and an average velocity of 3.5 m/s flows
through a 5-m-long stainless steel tube (k = 14.2 W/m·K) in a boiler. The inner and outer
diameters of the tube are Di = 1.0 cm and Do = 1.4 cm, respectively. If the convection heat
transfer coefficient at the outer surface of the tube where boiling is taking place is ho = 8400
W/m2·K, determine the overall heat transfer coefficient Ui of this boiler based on the inner surface
area of the tube.
22–21 Repeat Prob. 22–20, assuming a fouling factor Rf,i = 0.0005 m2·K/W on the inner surface
of the tube.
22–23 Hot engine oil with heat capacity rate of 4440 W/K (product of mass flow rate and specific
heat) and an inlet temperature of 150°C flows through a double pipe heat exchanger. The double
pipe heat exchanger is constructed of a 1.5-m-long copper pipe (k = 250 W/m·K) with an inner
tube of inside diameter 2 cm and outside tube diameter of 2.25 cm. The inner diameter of the
outer tube of the double pipe heat exchanger is 6 cm. Oil flowing at a rate of 2 kg/s through inner
tube exits the heat exchanger at a temperature of 50°C. The cold fluid, that is, water enters the
heat exchanger at 20°C and exits at 70°C. Assuming the fouling factor on the oil side and water
side to be 0.00015 m2·K/W and 0.0001 m2·K/W, respectively, determine the overall heat transfer
coefficient on inner and outer surface of the copper tube.
22–24C What are the common approximations made in the analysis of heat exchangers?
22–25C Under what conditions is the heat transfer relation
๐‘„แˆถ = ๐‘š๐ถ
แˆถ ๐‘๐‘ ๐‘‡๐‘,๐‘œ๐‘ข๐‘ก − ๐‘‡๐‘,๐‘–๐‘› = ๐‘š๐ถ
แˆถ ๐‘โ„Ž ๐‘‡โ„Ž,๐‘–๐‘› − ๐‘‡โ„Ž,๐‘œ๐‘ข๐‘ก valid for a heat exchanger?
PROBLEMS
22–26C Consider a condenser in which steam at a specified temperature is condensed by
rejecting heat to the cooling water. If the heat transfer rate in the condenser and the temperature
rise of the cooling water is known, explain how the rate of condensation of the steam and the
mass flow rate of the cooling water can be determined. Also, explain how the total thermal
resistance R of this condenser can be evaluated in this case.
22–27C What is the heat capacity rate? What can you say about the temperature changes of the
hot and cold fluids in a heat exchanger if both fluids have the same capacity rate? What does a
heat capacity of infinity for a fluid in a heat exchanger mean?
22–28C Under what conditions will the temperature rise of the cold fluid in a heat exchanger be
equal to the temperature drop of the hot fluid?
22–29 Show that the temperature profile of two fluid streams (hot and cold) that have the same
heat capacity rates is parallel to each other at every section of the counter flow heat exchanger.
Hint: Refer to the analysis presented in Secs. 22–3 and 22–4 of the textbook.
22–30C In the heat transfer relation ๐‘„แˆถ = UAs ΔTlm for a heat exchanger, what is ΔTlm called? How
is it calculated for a parallel-flow and counter-flow heat exchanger?
22–31C How does the log mean temperature difference for a heat exchanger differ from the
arithmetic mean temperature difference? For specified inlet and outlet temperatures, which one of
these two quantities is larger?
PROBLEMS
22–32C The temperature difference between the hot and cold fluids in a heat exchanger is given
to be ΔT1 at one end and ΔT2 at the other end. Can the logarithmic temperature difference ΔTlm
of this heat exchanger be greater than both ΔT1 and ΔT2 ? Explain.
22–33C Can the outlet temperature of the cold fluid in a heat exchanger be higher than the outlet
temperature of the hot fluid in a parallel-flow heat exchanger? How about in a counter-flow heat
exchanger? Explain.
22–34C Explain how the LMTD method can be used to determine the heat transfer surface area
of a multipass shelland-tube heat exchanger when all the necessary information, including the
outlet temperatures, is given.
22–35C In the heat transfer relation ๐‘„แˆถ = UAs FΔTlm for a heat exchanger, what is the quantity F
called? What does it represent? Can F be greater than one?
22–36C When the outlet temperatures of the fluids in a heat exchanger are not known, is it still
practical to use the LMTD method? Explain.
22–37C For specified inlet and outlet temperatures, for what kind of heat exchanger will the DTlm
be greatest: double-pipe parallel-flow, double-pipe counter-flow, cross-flow, or multipass shelland-tube heat exchanger?
PROBLEMS
22–38 A double-pipe parallel-flow heat exchanger is used to heat cold tap water with hot water.
Hot water (cp = 4.25 kJ/kg·K) enters the tube at 85°C at a rate of 1.4 kg/s and leaves at 50°C. The
heat exchanger is not well insulated, and it is estimated that 3 percent of the heat given up by the
hot fluid is lost from the heat exchanger. If the overall heat transfer coefficient and the surface
area of the heat exchanger are 1150 W/m2·K and 4 m2, respectively, determine the rate of heat
transfer to the cold water and the log mean temperature difference for this heat exchanger.
22–39 A stream of hydrocarbon (cp = 2.2 kJ/kg·K) is cooled at a rate of 720 kg/h from 150°C to
40°C in the tube side of a double-pipe counter-flow heat exchanger. Water (cp = 4.18 kJ/ kg·K)
enters the heat exchanger at 10°C at a rate of 540 kg/h. The outside diameter of the inner tube is
2.5 cm, and its length is 6.0 m. Calculate the overall heat transfer coefficient.
22–40 A double-pipe parallel-flow heat exchanger is to heat water (cp = 4180 J/kg·K) from 25°C to
60°C at a rate of 0.2 kg/s. The heating is to be accomplished by geothermal water (cp = 4310
J/kg·K) available at 140°C at a mass flow rate of 0.3 kg/s. The inner tube is thin-walled and has a
diameter of 0.8 cm. If the overall heat transfer coefficient of the heat exchanger is 550 W/m 2·K,
determine the length of the tube required to achieve the desired heating.
22–42 Glycerin (cp = 2400 J/kg·K) at 20°C and 0.5 kg/s is to be heated by ethylene glycol (cp =
2500 J/kg·K) at 60°C in a thin-walled double-pipe parallel-flow heat exchanger. The temperature
difference between the two fluids is 15°C at the outlet of the heat exchanger. If the overall heat
transfer coefficient is 240 W/m2·K and the heat transfer surface area is 3.2 m2, determine (a) the
rate of heat transfer, (b) the outlet temperature of the glycerin, and (c) the mass flow rate of the
ethylene glycol.
PROBLEMS
22–43 A heat exchanger contains 400 tubes with inner diameter of 23 mm and outer diameter of
25 mm. The length of each tube is 3.7 m. The corrected log mean temperature difference is 23°C,
while the inner surface convection heat transfer coefficient is 3410 W/m2·K and the outer surface
convection heat transfer coefficient is 6820 W/m2·K. If the thermal resistance of the tubes is
negligible, determine the heat transfer rate.
22–45 Consider the flow of engine oil (cp = 2048 J/kg·K) through a thinwalled copper tube at a rate of 0.3 kg/s. The engine oil that enters the
copper tube at an inlet temperature of 80°C is to be cooled by cold water
(cp = 4180 J/kg·K) flowing at a temperature of 20°C. It is desired to have
Exit temperature of the engine oil not greater than 40°C. The individual
convective heat transfer coefficients on oil and water sides are 750 W/m2·K and 350 W/m2·K,
respectively. If a thermocouple probe installed on the downstream side of the cooling water
measures a temperature of 32°C, for a double pipe parallel flow heat exchanger determine (a)
mass flow rate of the cooling water (b) log mean temperature difference, and (c) area of heat
exchanger.
PROBLEMS
22–46 In a parallel flow heat exchanger, hot fluid enters the heat
exchanger at a temperature of 150°C and a mass flow rate of 3 kg/s. The cooling medium enters
the heat exchanger at a temperature of 30°C with a mass flow rate of 0.5 kg/s and leaves at a
temperature of 70°C. The specific heat capacities of the hot and cold fluids are 1150 J/kg·K and
4180 J/kg·K, respectively. The convection heat transfer coefficient on the inner and outer side of
the tube is 300 W/m2·K and 800 W/m2·K, respectively. For a fouling factor of 0.0003 m2·K/W on
the tube side and 0.0001 m2·K/W on the shell side, determine (a) the overall heat transfer
coefficient, (b) the exit temperature of the hot fluid and (c) surface area of the heat exchanger.
22–47 Ethylene glycol is heated from 25°C to 40°C at a rate of 2.5 kg/s in a horizontal copper
tube (k = 386 W/m·K) with an inner diameter of 2.0 cm and an outer diameter of 2.5 cm. A
saturated vapor (Tg = 110°C) condenses on the outside-tube surface with the heat transfer
coefficient (in kW/m2·K) given by 9.2/(Tg - Tw)0.25, where Tw is the average outside-tube wall
temperature. What tube length must be used? Take the properties of ethylene glycol to be ρ =
1109 kg/m3, cp = 2428 J/kg·K, k = 0.253 W/m·K, μ = 0.01545 kg/m·s, and Pr = 148.5.
22–48 A counter-flow heat exchanger is stated to have an overall heat transfer coefficient of 284
W/m2·K when operating at design and clean conditions. Hot fluid enters the tube side at 93°C and
exits at 71°C, while cold fluid enters the shell side at 27°C and exits at 38°C. After a period of use,
built-up scale in the heat exchanger gives a fouling factor of 0.0004 m2·K/W. If the surface area is
93 m2, determine (a) the rate of heat transfer in the heat exchanger and (b) the mass flow rates of
both hot and cold fluids. Assume both hot and cold fluids have a specific heat of 4.2 kJ/kg·K.
PROBLEMS
22–49 A thin-walled double-pipe counter-flow heat exchanger is to be
used to cool oil (cp = 2200 J/kg·K) from 150°C to 40°C at a rate of 2 kg/s by water (cp = 4180
J/kg·K) that enters at 22°C at a rate of 1.5 kg/s. The diameter of the tube is 2.5 cm, and its length
is 6 m. Determine the overall heat transfer coefficient of this heat exchanger.
22–51 Cold water (cp = 4180 J/kg·K) leading to a shower enters a thin-walled double-pipe
counter-flow heat exchanger at 15°C at a rate of 1.25 kg/s and is heated to 45°C by hotwater (cp
= 4190 J/kg·K) that enters at 100°C at a rate of 3 kg/s. If the overall heat transfer coefficient is
880 W/m2·K, determine the rate of heat transfer and the heat transfer surface area of the heat
exchanger.
22–54 Hot exhaust gases of a stationary diesel engine are to be used to generate steam in an
evaporator. Exhaust gases (cp = 1051 J/kg·K) enter the heat exchanger at 550°C at a rate of 0.25
kg/s while water enters as saturated liquid and evaporates at 200°C (hfg = 1941 kJ/kg). The heat
transfer surface area of the heat exchanger based on water side is 0.5 m2 and overall heat
transfer coefficient is 1780 W/m2·K. Determine the rate of heat transfer, the exit temperature of
exhaust gases, and the rate of evaporation of water.
22–56 In a textile manufacturing plant, the waste dyeing water (cp = 4295 J/kg·K) at 75°C is to be
used to preheat fresh water (cp = 4180 J/kg·K) at 15°C at the same flow rate in a double-pipe
counter-flow heat exchanger. The heat transfer surface area of the heat exchanger is 1.65 m2 and
the overall heat transfer coefficient is 625 W/m2·K. If the rate of heat transfer in the heat
exchanger is 35 kW, determine the outlet temperature and the mass flow rate of each fluid
stream.
PROBLEMS
22–57 A performance test is being conducted on a doublepipe counter-flow heat exchanger that
carries engine oil and water at a flow rate of 2.5 kg/s and 1.75 kg/s, respectively. Since the heat
exchanger has been in service over a long period of time, it is suspected that the fouling might
have developed inside the heat exchanger that might have affected the overall heat transfer
coefficient. The test to be carried out is such that, for a designed value of the overall heat transfer
coefficient of 450 W/m2·K and a surface area of 7.5 m2, the oil must be heated from 25°C to 55 °C
by passing hot water at 100°C (cp = 4206 J/kg·K) at the flow rates mentioned above. Determine if
the fouling has affected the overall heat transfer coefficient. If yes, then what is the magnitude of
the fouling resistance?
22–58 In an industrial facility a counter-flow double-pipe heat exchanger uses superheated steam
at a temperature of 250°C to heat feed water at 30°C. The superheated steam experiences a
temperature drop of 70°C as it exits the heat exchanger. The water to be heated flows through the
heat exchanger tube of negligible thickness at a constant rate of 3.47 kg/s. The convective heat
transfer coefficient on the superheated steam and water side is 850 W/m2·K and 1250 W/m2·K,
respectively. To account for the fouling due to chemical impurities that
might be present in the feed water, use an appropriate fouling factor for
the water side. Determine (a) the heat exchanger area required to
maintain the exit temperature of the water to a minimum of 70°C, and
(b) what would be the required heat exchanger area in case of parallel
flow arrangement?
PROBLEMS
22–59 A test is conducted to determine the overall heat transfer coefficient in a shell-and-tube oilto-water heat exchanger that has 24 tubes of internal diameter 1.2 cm and length 2 m in a single
shell. Cold water (cp = 4180 J/kg·K) enters the tubes at 20°C at a rate of 3 kg/s and leaves at
55°C. Oil (cp = 2150 J/kg·K) flows through the shell and is cooled from 120°C to 45°C. Determine
the overall heat transfer coefficient Ui of this heat exchanger based on the inner surface area of
the tubes. Answer: 8.31 kW/m2.K
22–60 A shell-and-tube heat exchanger is used for heating 10 kg/s of oil (cp = 2.0 kJ/kg·K) from
25°C to 46°C. The heat exchanger has 1-shell pass and 6-tube passes. Water enters the shell
side at 80°C and leaves at 60°C. The overall heat transfer coefficient is estimated to be 1000
W/m2·K. Calculate the rate of heat transfer and the heat transfer area.
22–62 A shell-and-tube heat exchanger with 2-shell passes and 12-tube passes is used to heat
water (cp = 4180 J/kg·K) with ethylene glycol (cp = 2680 J/kg·K). Water enters the tubes at 22°C
at a rate of 0.8 kg/s and leaves at 70°C. Ethylene glycol enters the shell at 110°C and leaves at
60°C. If the overall heat transfer coefficient based on the tube side is 280 W/m2·K, determine the
rate of heat transfer and the heat transfer surface area on the tube side.
22–64 A shell-and-tube heat exchanger with 2-shell passes and 12-tube passes is used to heat
water (cp = 4180 J/kg·K) in the tubes from 20°C to 70°C at a rate of 4.5 kg/s. Heat is supplied by
hot oil (cp = 2300 J/kg·K) that enters the shell side at 170°C at a rate of 10 kg/s. For a tube-side
overall heat transfer coefficient of 350 W/m2·K, determine the heat transfer surface area on the
tube side. Answer: 25.7 m2
22–65 Repeat Prob. 22–64 for a mass flow rate of 3 kg/s for water.
PROBLEMS
22–66 A shell-and-tube heat exchanger with 2-shell passes and 8-tube passes is used to heat
ethyl alcohol (cp = 2670 J/kg·K) in the tubes from 25°C to 70°C at a rate of 2.1 kg/s. The heating
is to be done by water (cp = 4190 J/kg·K) that enters the shell side at 95°C and leaves at 45°C. If
the overall heat transfer coefficient is 950 W/m2·K, determine the heat transfer surface area of the
heat exchanger.
22–68C What does the effectiveness of a heat exchanger represent? Can effectiveness be
greater than one? On what factors does the effectiveness of a heat exchanger depend?
22–69C For a specified fluid pair, inlet temperatures, and mass flow rates, what kind of heat
exchanger will have the highest effectiveness: double-pipe parallel-flow, double-pipe counterflow,
cross-flow, or multipass shell-and-tube heat exchanger?
22–70C Explain how you can evaluate the outlet temperatures of the cold and hot fluids in a heat
exchanger after its effectiveness is determined.
22–71C Can the temperature of the cold fluid rise above the inlet temperature of the hot fluid at
any location in a heat exchanger? Explain.
22–72C Consider a heat exchanger in which both fluids have the same specific heats but different
mass flow rates. Which fluid will experience a larger temperature change: the one with the lower
or higher mass flow rate?
22–73C Explain how the maximum possible heat transfer rate ๐‘„แˆถ max in a heat exchanger can be
determined when the mass flow rates, specific heats, and the inlet temperatures of the two fluids
are specified. Does the value of ๐‘„แˆถ max depend on the type of the heat exchanger?
PROBLEMS
22–74C Under what conditions can a counter-flow heat exchanger have an effectiveness of one?
What would your answer be for a parallel-flow heat exchanger?
22–75C Consider a double-pipe counter-flow heat exchanger. In order to enhance heat transfer,
the length of the heat exchanger is now doubled. Do you think its effectiveness will also double?
22–76C Consider a shell-and-tube water-to-water heat exchanger with identical mass flow rates
for both the hot- and cold-water streams. Now the mass flow rate of the cold water is reduced by
half. Will the effectiveness of this heat exchanger increase, decrease, or remain the same as a
result of this modification? Explain. Assume the overall heat transfer coefficient and the inlet
temperatures remain the same.
22–77C Consider two double-pipe counter-flow heat exchangers that are identical except that one
is twice as long as the other one. Which heat exchanger is more likely to have a higher
effectiveness?
22–78C How is the NTU of a heat exchanger defined? What does it represent? Is a heat
exchanger with a very large NTU (say, 10) necessarily a good one to buy?
22–79C Consider a heat exchanger that has an NTU of 4. Someone proposes to double the size
of the heat exchanger and thus double the NTU to 8 in order to increase the effectiveness of the
heat exchanger and thus save energy. Would you support this proposal?
22–80C Consider a heat exchanger that has an NTU of 0.1. Someone proposes to triple the size
of the heat exchanger and thus triple the NTU to 0.3 in order to increase the effectiveness of the
heat exchanger and thus save energy. Would you support this proposal?
PROBLEMS
22–81 The radiator in an automobile is a cross-flow heat exchanger (UAs = 10 kW/K) that uses air
(cp = 1.00 kJ/kg·K) to cool the engine-coolant fluid (cp = 4.00 kJ/kg·K). The engine fan draws 30°C
air through this radiator at a rate of 10 kg/s while the coolant pump circulates the engine coolant
at a rate of 5 kg/s. The coolant enters this radiator at 80°C. Under these conditions, the
effectiveness of the radiator is 0.4. Determine (a) the outlet temperature of the air and (b) the rate
of heat transfer between the two fluids.
22–82 Consider an oil-to-oil double-pipe heat exchanger whose flow arrangement is not known.
The temperature measurements indicate that the cold oil enters at 20°C and leaves at 55°C, while
the hot oil enters at 80°C and leaves at 45°C. Do you think this is a parallel-flow or counter-flow
heat exchanger? Why? Assuming the mass flow rates of both fluids to be identical, determine the
effectiveness of this heat exchanger.
22–84 Hot water (cph= 4188 J/kg·K) with mass flow rate of 2.5 kg/s at 100°C enters a thin-walled
concentric tube counter-flow heat exchanger with a surface area of 23 m2 and an overall heat
transfer coefficient of 1000 W/m2·K. Cold water (cpc = 4178 J/kg·K) with mass flow rate of 5 kg/s
enters the heat exchanger at 20°C, determine (a) the heat transfer rate for the heat exchanger
and (b) the outlet temperatures of the cold and hot fluids. After a period of operation, the overall
heat transfer coefficient is reduced to 500 W/m2·K, determine (c) the fouling factor that caused the
reduction in the overall heat transfer coefficient.
PROBLEMS
22–85 Water (cp = 4180 J/kg·K) is to be heated by solarheated hot air
(cp = 1010 J/kg·K) in a double-pipe counter-flow heat exchanger. Air enters the heat exchanger at
90°C at a rate of 0.3 kg/s, while water enters at 22°C at a rate of 0.1 kg/s. The overall heat
transfer coefficient based on the inner side of the tube is given to be 80 W/m2·K. The length of the
tube is 12 m and the internal diameter of the tube is 1.2 cm. Determine the outlet temperatures of
the water and the air.
22–87 Cold water (cp = 4180 J/kg·K) leading to a shower enters a thin-walled double-pipe
counter-flow heat exchangerat 15°C at a rate of 0.25 kg/s and is heated to 45°C by hot water (cp
= 4190 J/kg·K) that enters at 100°C at a rate of 3 kg/s. If the overall heat transfer coefficient is
950 W/m2·K, determine the rate of heat transfer and the heat transfer surface area of the heat
exchanger using the ε-NTU method. Answers: 31.35 kW, 0.482 m2
22–91 In a one-shell and two-tube heat exchanger, cold water with inlet temperature of 20°C is
heated by hot water supplied at the inlet at 80°C. The cold and hot water flow rates are 5000 kg/h
and 10,000 kg/h, respectively. If the shelland-tube heat exchanger has a UAs value of 11,600
W/K, determine the cold water and hot water outlet temperatures. Assume cpc = 4178 J/kg·K and
cph = 4188 J/kg·K.
PROBLEMS
22–92 Hot oil (cp = 2200 J/kg·K) is to be cooled by water (cp = 4180 J/kg·K) in a 2-shell-passes
and 12-tube-passes heat exchanger. The tubes are thin-walled and are made of copper with a
diameter of 1.8 cm. The length of each tube pass in the heat exchanger is 3 m, and the overall
heat transfer coefficient is 340 W/m2·K. Water flows through the tubes at a total rate of 0.1 kg/s,
and the oil through the shell at a rate of 0.2 kg/s. The water and the oil enter at temperatures
18°C and 160°C, respectively. Determine the rate of heat transfer in the heat exchanger and the
outlet temperatures of the water and the oil. Answers: 36.2 kW, 104.6°C, 77.7°C
22–96 Air (cp = 1005 J/kg·K) enters a cross-flow heat exchanger at 20°C at a rate of 3 kg/s,
where it is heated by a hot water stream (cp = 4190 J/kg·K) that enters the heat exchanger at
70°C at a rate of 1 kg/s. Determine the maximum heat transfer rate and the outlet temperatures of
both fluids for that case.
22–97 A cross-flow heat exchanger with both fluids unmixed has an overall heat transfer
coefficient of 200 W/m2·K, and a heat transfer surface area of 400 m2. The hot fluid has a heat
capacity of 40,000 W/K, while the cold fluid has a heat capacity of 80,000 W/K. If the inlet
temperatures of both hot and cold fluids are 80°C and 20°C, respectively, determine the exit
temperature of the cold fluid.
22–98 A cross-flow air-to-water heat exchanger with an effectiveness of 0.65 is used to heat water
(cp = 4180 J/kg·K) with hot air (cp = 1010 J/kg·K). Water enters the heat exchanger at 20°C at a
rate of 4 kg/s, while air enters at 100°C at a rate of 9 kg/s. If the overall heat transfer coefficient
based on the water side is 260 W/m2·K, determine the heat transfer surface area of the heat
exchanger on the water side. Assume both fluids are unmixed. Answer: 52.4 m2
PROBLEMS
22–99 Cold water (cp = 4.18 kJ/kg·K) enters a crossflow heat exchanger at
14°C at a rate of 0.35 kg/s where it is heated by hot air (cp = 1.0 kJ/kg·K) that enters the heat exchanger
at 65°C at a rate of 0.8 kg/s and leaves at 25°C. Determine the maximum outlet temperature of the cold
water and the effectiveness of this heat exchanger.
22–100 Oil in an engine is being cooled by air in a crossflow heat exchanger, where both fluids are
unmixed. Oil (cph = 2047 J/kg·K) flowing with a flow rate of 0.026 kg/s enters the heat exchanger at
75°C, while air (cpc = 1007 J/kg·K) enters at 30°C with a flow rate of 0.21 kg/s. The overall heat transfer
coefficient of the heat exchanger is 53 W/m2·K and the total surface area is 1 m2. Determine (a) the heat
transfer effectiveness and (b) the outlet temperature of the oil.
22–101 Consider a recuperative cross-flow heat exchanger (both fluids unmixed)
used in a gas turbine system that carries the exhaust gases at a flow rate of
7.5 kg/s and a temperature of 500°C. The air initially at 30°C and flowing at a
rate of 15 kg/s is to be heated in the recuperator. The convective heat transfer
coefficients on the exhaust gas and air side are 750 W/m 2·K and 300 W/m2·K,
respectively. Due to long-term use of the gas turbine, the recuperative heat exchanger is subject to
fouling on both gas and air side that offers a resistance of 0.0004 m 2·K/W each. Take the properties of
exhaust gas to be the same as that of air (cp = 1069 J/kg·K). If the exit temperature of the exhaust gas is
320°C, determine (a) if the air could be heated to a temperature of 150°C, (b) the area of heat
exchanger, (c) if the answer to part (a) is no, then determine what should be the air mass flow rate in
order to attain the desired exit temperature of 150°C, and (d ) plot variation of the exit air temperature
over a temperature range of 75°C to 300°C with air mass flow rate assuming all the other conditions
remain the same.
PROBLEMS
22–102 Consider operation of a single pass cross-flow heat exchanger with water (cp = 4193 J/kg·K)
(mixed) and methanol (cp = 2577 J/kg·K) (unmixed). Water entering and exiting the heat exchanger at
90°C and 60°C, respectively, is used to heat the methanol initially at 10°C. The overall heat transfer
coefficient and the total heat transfer rate are estimated to be 650 W/m 2·K and 250 kW, respectively. In
order to achieve an effectiveness of at least 0.5, (a) what would be the mass flow rate of water and heat
exchanger surface area? (b) If the mass flow rate of water is changed within ±30% of that determined in
part (a) with the same surface area (As), plot the variation of heat transfer rate, methanol exit
temperature, overall heat transfer coefficient and the effectiveness of heat exchanger with respect to
change in the water flow rate.
22–103 Consider a cross-flow engine oil heater that uses ethylene glycol flowing at a temperature of
110°C to heat the oil initially at 10°C. The ethylene glycol enters a tube bank consisting of copper tubes
(k = 250 W/m·K) with staggered arrangement in a 0.5 m x 0.5 m plenum. The outside diameter of the
0.5-m-long copper tubes is 25 mm and has a wall thickness of 2 mm. The longitudinal and transverse
pitch of the rod bundles is 0.035 m each. The engine oil to be
heated flows inside the tubes with a mass flow rate of 4.05 kg/s.
Take the heat transfer coefficient of the oil to be 2500 W/m 2·K.
If the minimum desired exit temperature of oil is 70°C and the
measured exit temperature of ethylene glycol is 90°C, determine
(a) mass flow rate of ethylene glycol and (b) number of tube rows.
In your calculation use the following properties for the ethylene
glycol.
PROBLEMS
22–104 Water (cp = 4180 J/kg·K) enters the 2.5-cminternal-diameter tube of a double-pipe
counter-flow heat exchanger at 17°C at a rate of 1.8 kg/s. Water is heated by steam condensing
at 120°C (hfg = 2203 kJ/kg) in the shell. If the overall heat transfer coefficient of the heat
exchanger is 700 W/m2·K, determine the length of the tube required in order to heat the water to
80°C using (a) the LMTD method and (b) the ε-NTU method.
22–105 Ethanol is vaporized at 78°C (hfg = 846 kJ/kg) in a double-pipe
parallel-flow heat exchanger at a rate of 0.03 kg/s by hot oil
(cp = 2200 J/kg·K) that enters at 120°C. If the heat transfer surface area
and the overall heat transfer coefficients are 6.2 m2 and 320 W/m2·K,
respectively, determine the outlet temperature and the mass flow rate of oil using (a) the LMTD
method and (b) the ε-NTU method.
22–106 Saturated water vapor at 100°C condenses in a 1-shell and 2-tube heat exchanger with a
surface area of 0.5 m2 and an overall heat transfer coefficient of
2000 W/m2·K. Cold water (cpc = 4179 J/kg·K) flowing at 0.5 kg/s
enters the tube side at 15°C, determine (a) the heat transfer
effectiveness, (b) the outlet temperature of the cold water, and (c)
the heat transfer rate for the heat exchanger.
PROBLEMS
22–107 Steam is to be condensed on the shell side of a 1-shell-pass and
8-tube-passes condenser, with 50 tubes in each pass, at 30°C
(hfg = 2431 kJ/kg). Cooling water (cp = 4180 J/kg·K) enters the tubes at 15°C at a rate of 1800
kg/h. The tubes are thin-walled, and have a diameter of 1.5 cm and length of 2 m per pass. If the
overall heat transfer coefficient is 3000 W/m2·K, determine (a) the rate of heat transfer and (b)
the rate of condensation of steam.
22–110 Consider the flow of saturated steam at 270.1 kPa that flows through the shell side of a
shell-and-tube heat exchanger while the water flows through 4 tubes of diameter 1.25 cm at a rate
of 0.25 kg/s through each tube. The water enters the tubes of heat exchanger at 20°C and exits at
60°C. Due to the heat exchange with the cold fluid, steam is condensed on the tubes external
surface. The convection heat transfer coefficient on the steam side is 1500 W/m2·K, while the
fouling resistance for the steam and water may be taken as 0.00015 and
0.0001 m2·K/W, respectively. Using the NTU method, determine
(a) effectiveness of the heat exchanger, (b) length of the tube, and
(c) rate of steam condensation.
Download