2015 June 23 [ENERGY SIMULATION ] Singapore June 2015 Energy Simulation for Commercial Buildings Singapore Energy Simulation for Commercial Buildings Page ‐ 1 - 2015 June 22 [ENERGY SIMULATION] Carrier Corporation Software Systems Network Carrier University 2003-2015Carrier Corporation Carrier University 6540 Old Collamer Rd. S. East Syracuse, NY 13057 World Wide Web: www.carrier.com/building-solutions/en/us www.carrieruniversity.com ALL RIGHTS RESERVED. No part of this work covered by the copyright hereon may be reproduced or used in any form or by any means— graphic, electronic, or mechanical, including photocopying, recording, taping, Web distribution or information storage and retrieval systems—without the written permission of Carrier Corporation. For permission to use material from this text contact us by: Tel (800) 253-1794 Fax (315) 432.3871 e-Mail software.systems@carrier.utc.com Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 2 - 2015 June 22 [ENERGY SIMULATION] Table of Contents KEYS TO USING THIS TRAINING MANUAL ..................................................... - 7 ICONS USED IN THIS MANUAL ........................................................................ - 7 EARNING CEU CREDITS ................................................................................... - 8 Course Learning Outcomes .............................................................................................................. - 8 Continuing Education Unit Credits (CEUs) ..................................................................................... - 8 WELCOME TO ENERGY SIMULATION FOR COMMERCIAL BUILDINGS USING HAP V4.9........................................................................................................... - 9 Workbook Organization .................................................................................................................... - 9 PROJECT DEFINITION AND OUTLINE ............................................................ - 10 SECTION 1_WORKSHOP 1 INPUTS - CREATE NEW PROJECT AND LINK SIMULATION WEATHER ................................................................................. - 21 SETTING PROJECT PREFERENCES .......................................................................................................... - 21 ENTER DESIGN AND SIMULATION WEATHER PROPERTIES .................................................................... - 23 DEFINING THE HOLIDAY SCHEDULE ..................................................................................................... - 28 Weather Reports ............................................................................................................................. - 29 SECTION 1_WORKSHOP 2 – EDITING SCHEDULES ....................................... - 33 Schedule Profile Assignments Input Details ................................................................................... - 35 SECTION 2_WORKSHOP 3 - MODELING 4-PIPE FAN COIL UNIT AIR SYSTEMS USING THE EQUIPMENT WIZARD. ................................................................. - 43 SYSTEM DESIGN REPORTS ........................................................................................................................ 53 Zone Sizing Summary.......................................................................................................................... 54 Ventilation Sizing Summary ............................................................................................................ - 56 Air System Design Load Summary Report ...................................................................................... - 57 Hourly Zone Load Report Example ................................................................................................ - 58 SYSTEM SIMULATION REPORTS MONTHLY, DAILY AND HOURLY SIMULATION RESULTS .................... - 60 Monthly Air System Simulation Results .......................................................................................... - 60 Monthly Air System Simulation Graph ........................................................................................... - 61 Daily Air System Simulation Results ............................................................................................... - 62 Daily Air System Simulation Results ............................................................................................... - 64 Hourly Air System Simulation Results ............................................................................................ - 65 Hourly Air System Simulation Results Graph ................................................................................. - 67 Zone Temperature Report ............................................................................................................... - 68 SECTION 3_WORKSHOP 4 - MODELING CHILLERS, TOWERS, BOILERS AND HYDRONIC PLANTS ............................................................................................ 71 Retrieve Energy Simulation Archive 2 Unsolved ................................................................................ 71 Air Cooled Chiller Selection ............................................................................................................... 75 Entering Chiller Performance Data................................................................................................ - 77 Cooling Plant Sizing Summary Comparison Discussion ................................................................ - 85 Entering Cooling Tower Performance Data ................................................................................... - 85 SECTION 4 ...................................................................................................... - 89 C Alt 2 Chiller Plant Input Data ..................................................................................................... - 94 D Alt3 SZCV/RTU ........................................................................................................................... - 95 Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 3 - 2015 June 22 [ENERGY SIMULATION] SECTION 4_WORKSHOP 5 SOLUTIONS ......................................................... - 99 A Base Case Chiller Plant Simulation Results ................................................................................ - 99 D Alt 3 Packaged RTU D-31 RTU D5 Classroom D104 Simulation Results................................ - 105 SECTION 5_WORKSHOP 6 DEFINING AND SIMULATING BUILDINGS ......... - 111 Defining Buildings in HAP ........................................................................................................... - 111 SIMULATION RESULTS ................................................................................ - 119 Annual Emissions Summary .......................................................................................................... - 120 Annual Component Cost for C Alt 2 ............................................................................................. - 124 Annual Energy Cost ...................................................................................................................... - 125 Annual Cost HVAC and Non-HVAC ............................................................................................. - 126 Energy Budget by System Component........................................................................................... - 127 Energy Budget by Energy Source ................................................................................................. - 128 Monthly Component Cost ............................................................................................................. - 129 Monthly Energy Cost by Energy Type .......................................................................................... - 130 Monthly Energy Use by System Component ................................................................................. - 131 Monthly Energy Use by Energy Type............................................................................................ - 132 Electric Billing Details ................................................................................................................. - 133 Hourly Energy Use Profile ........................................................................................................... - 135 Hourly Energy Use Graph ............................................................................................................ - 136 APPENDIX “A” AIR SYSTEM SCHEMATICS .............................................. - 139 - APPENDIX”B” ............................................................................................... - 153 Putting Load Calculation Methods in Perspective ....................................................................... - 155 The Benefits of the Transfer Function / Heat Extraction Method ................................................. - 158 Understanding Zone Loads and Zone Conditioning ..................................................................... - 158 The Sizing Dilemma ...................................................................................................................... - 162 Which Sizing Method to Use? ....................................................................................................... - 163 Differences between Peak Coil Load CFM, Max Block CFM, Sum of Peak Zone CFM .............. - 165 Selecting Equipment When Coil CFM (L/s) Differ ....................................................................... - 168 ASHRAE 62.1-2004 and 2007 Ventilation Air Sizing in HAP ...................................................... - 169 ASHRAE Standard 62 ................................................................................................................... - 169 Defining ASHRAE Standard 62.1-2004/7 Ventilation Requirements in HAP ............................... - 170 Space Level Ventilation in ASHRAE 62.1-2004 & 2007 ............................................................... - 171 Space Usage Comparisons and Two-Part OA Requirement ......................................................... - 172 Step 1: Determining the Space Level Minimum Ventilation Requirements................................... - 174 Step 2: Determining the System Level Minimum Ventilation Requirements ................................. - 177 Minimum Supply Air (CFM) ......................................................................................................... - 180 Floor Area (sq ft) .......................................................................................................................... - 180 Required Outdoor Air (CFM/Ft²) ................................................................................................. - 180 Time Averaged Occupancy ........................................................................................................... - 180 Required Outdoor Air (CFM/Person) ........................................................................................... - 180 Air Distribution Effectiveness ....................................................................................................... - 180 Required Outdoor Air (CFM) ....................................................................................................... - 180 Uncorrected Outdoor Air (CFM) .................................................................................................. - 180 Space Ventilation Efficiency ......................................................................................................... - 181 Conclusion .................................................................................................................................... - 181 System Based Design Load Calculations ...................................................................................... - 182 APPENDIX “C” .............................................................................................. - 189 Technical White Papers ................................................................................................................ - 189 Introduction .................................................................................................................................. - 190 Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 4 - 2015 June 22 [ENERGY SIMULATION] How Traditional System Design Methods Work ........................................................................... - 190 Shortcomings of the Traditional Approach ................................................................................... - 190 System-Based Design and How It Works ...................................................................................... - 191 Benefits of System-Based Design .................................................................................................. - 192 Conclusion .................................................................................................................................... - 192 The Benefits of 8760 Hour by Hour Building Energy Analysis..................................................... - 193 Introduction .................................................................................................................................. - 193 What Is Building Energy Analysis? .............................................................................................. - 193 Requirements for High Quality Results......................................................................................... - 193 8760 Hour-By-Hour Method: How and Why? .............................................................................. - 196 Conclusion .................................................................................................................................... - 199 LIST OF FIGURES Figure 0.1 - Continuous Design Decision Cycle..........................................................- 10 Figure 0.2 – ASHRAE U.S. Climate Zone Map ...........................................................- 11 Figure 0.4 – School Exterior “A” Commons Area ........................................................- 12 Figure 0.5 – A Commons Area Floor Plan ..................................................................- 13 Figure 0.6 – “B” Classroom Wing ................................................................................- 14 Figure 0.7 – “C” – Gymnasium Wing...........................................................................- 15 Figure 0.8 – “D” Classroom Wing................................................................................- 16 Figure1.1 - Create New Project in HAP 4.9 ................................................................- 21 Figure1.2 – Setting Project Preferences .....................................................................- 22 Figure 1.3 – HAP Program Preferences Figure1.4 – View/Preferences ....- 23 Figure 1.5 – HAP Weather Wizard ..............................................................................- 24 Figure 1.6 A, B & C – Weather Wizard Input Screens ................................................- 25 Figure 1.7 – Weather Wizard Design and Simulation Properties ................................- 25 Figure 1.8 – Wizard Created Data ..............................................................................- 26 Figure 1.9 - HAP Design Weather Properties Form. ...................................................- 26 Figure 1.10 – Importing Simulation Weather Data ......................................................- 27 Figure 1.11 – Adding Holidays ....................................................................................- 28 Figure 1.12 Design and Simulation Weather Reports .................................................- 29 Figure 2.1 - Schedule - Profile Assignments-Lights Classrooms ................................- 33 Figure 2.2 - Schedule–Profile Assignments-People-Classrooms ...............................- 34 Figure 3.1 - Launching the Equipment Wizard ............................................................- 43 Figure 3.2 - Assign Spaces to Building in Wizard .......................................................- 43 Figure 3.3a - Equipment Wizard Screen 1 ..................................................................- 44 Figure 3.3b - Equipment Wizard Screen 2 ..................................................................- 45 Figure 3.3c - Equipment Wizard Screen 2 ..................................................................- 46 Figure 3.3d - Equipment Wizard Screen 3 ..................................................................- 47 Figure 3.3e - Equipment and System Wizard Data Summary ....................................- 49 Figure 3.4 - Select Print View Design Reports ............................................................- 50 Figure 3.5 - Select Air System Sizing Summary Report .............................................- 50 Figure 3.6 - Select Simulation Results Reports ..........................................................- 58 Figure 3.7 - Select Air System Simulation Results Reports ........................................- 59 Figure 3.8 - Rerun and View all Air System Simulation Results .................................- 59 Figure 4.1 - Retrieve HAPv4.9 Energy Simulation Archive 2 Unsolved .......................... 71 Figure 4.2 - Create New Chiller Plant ............................................................................. 72 Figure 4.3 - Generic Chiller Plant Sizing Details ............................................................. 72 Figure 4.4 - Add “A Base Case” Air Systems to the Generic Chilled Water Plant .......... 73 Figure 4.5 - Calculate Chiller Plant Design Load ............................................................ 73 Figure 4.6 - Select Print/View Design Results – Cooling Plant Sizing Summary ............ 74 Figure 4.7 - Chiller Plant Sizing Summary Report .......................................................... 74 Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 5 - 2015 June 22 [ENERGY SIMULATION] Figure 4.8 - Details of Chiller Selection using e-Cat Selection Software. ....................... 75 Figure 4.9a - Chiller Input Form – Import Chiller Data ................................................- 77 Figure 4.9b – Chiller Properties General Tab – Imported Chiller Data .......................- 78 Figure 4.9c - Chiller Properties Design Inputs – Imported Chiller Data ......................- 79 Figure 4.9d – Chiller Properties Performance Map – Imported Chiller Data ...............- 80 Figure 4.10 – Integrated Part Load Value ...................................................................- 81 Figure 4.11a – Define Chiller Part Load Performance ................................................- 82 Figure 4.11b – Chiller Template Design Inputs ...........................................................- 82 Figure 4.11c - Chiller Properties General Tab Template Data ....................................- 83 Figure 4.11d - Chiller Properties Design Inputs Tab ...................................................- 83 Figure 4.11e – Chiller Properties Performance Map Tab ............................................- 84 Figure 4.12 - Cooling Tower Properties for C Alt 2 WC Screw Chiller ........................- 86 Figure 4.13a Generic Service Hot Water Plant ...........................................................- 87 Figure 4.13b Link “A” Base Case Air Systems ............................................................- 87 Figure 4.13c –Define Service Hot Water Consumption ..............................................- 88 Figure 5.1 – Chiller Plants Created in WS4. ...............................................................- 91 Figure 5.2a – A Base Case Chiller Plant Data Inputs .................................................- 91 Figure 5.2b – A Base Case Air Systems .....................................................................- 92 Figure 5.2c – Base Case Plant Configuration .............................................................- 92 Figure 5.2d – Schedule of Equipment .........................................................................- 93 Figure 5.2e – Configure Plant Distribution ..................................................................- 93 Figure 5.3a – Packaged RTU-Configuration System Components –Supply Fan .......- 95 Figure 5.3b – Equipment – Central Cooling Unit.........................................................- 96 Figure 6.2 – Enter Building Data ..............................................................................- 114 Figure 6.3 – Assign Air Systems to Building Design .................................................- 114 Figure 6.4 – Misc. Energy Tab Input Details .............................................................- 115 Figure 6.5 – Building Meters Tab ..............................................................................- 116 Figure 6.6 – B Alt 1 Building Properties - Plants .......................................................- 116 Figure 6.7 – B Alt 1 Building Properties – Systems ..................................................- 116 Figure B-1. Load Estimating Methodologies ............................................................- 155 Figure B-2. Lighting Heat Gains and Loads ..............................................................- 156 Figure B-3 Stage One Calculations...........................................................................- 166 Figure B-4 Stage Two Calculations...........................................................................- 167 Figure C-1 Evolution of ASHRAE Ventilation Standards ..........................................- 169 Figure C-2 HAP Preferences ....................................................................................- 170 Figure C-3 Setting Project Preferences ....................................................................- 170 Figure C-4 HAP Space Properties Input Screen (General Tab) ...............................- 171 Figure C-5: Minimum Ventilation Rates ASHRAE 62.1-2004 ...................................- 171 Figure C-6: RETAIL Space Usage Comparison........................................................- 172 Figure C-7: EDUCATION Space Usage Comparison ...............................................- 173 Figure C-9 Space Air Distribution Effectiveness .......................................................- 176 Figure C-10 Typical VAV System and Critical Space ...............................................- 177 Figure C-11 No Critical Space Issues with Dedicated OA Unit .................................- 178 Figure C-12 Ventilation Report for VAV System .......................................................- 179 Figure D-1 VAV System Airflow Rates ......................................................................- 183 Figure D-2 Zone and Coil Load Profiles ....................................................................- 185 Figure D-3 Zone Air Temperature Profile ..................................................................- 186 Figure D-4 Loads for Varied Throttling Ranges ........................................................- 187 Figure D-5 Zone Temperatures for Varied Throttling Ranges...................................- 187 Figure E-1 Chicago Weather/September Dry Bulbs .................................................- 197 Figure E-2 Chicago Weather/September Solar.........................................................- 197 Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 6 - [ENERGY SIMULATION] 2015 June 22 Keys to Using This Training Manual Objectives - There is a listed of objectives at the beginning of each section. Detailed discussions of materials for this section are included in the text. Sample Section (Multiple Pages) Objectives ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ___________________________________Step-by-step Systematic exercises preceded by topic discussions, these exercises are the “hands-onpractice” part of this section. Summarize main points at the end of each section. Review at the end of each section ensures achievement of learning outcomes. ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ _________________________________________________ Summary ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ Review of Learning Outcomes ____________________________________________________ ____________________________________________________ ____________________________________________________ Enhanced screen shots included for additional detail Icons Used in This Manual Icon Key Valuable Information Learning Objective Hands-on Exercise The “icon key” at left depicts the four icons used throughout this manual to highlight valuable information, learning outcome objectives, hands-on exercises and additional information included on the accompanying hand- Additional Information on companion flash drive Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 7 - [ENERGY SIMULATION] 2015 June 22 Earning CEU Credits As part of our Technical Training Center, the International Associate for Continuing Education and Training (IACET) accepts and approves the E20-II software training as an Authorized Provider of Continuing Education Units (CEUs). IACET's mission is to promote and enhance quality in continuing education and training through research, education, and standard setting. IACET Authorized Providers undergo a strict evaluation of their educational processes according to the IACET Criteria and Guidelines, including two reviews by IACET's Commission and a site visit by an IACET Commissioner. Members of the organization are the educational professionals that strive to provide the highest quality in continuing education and training. Abstract Energy Simulation is a term used to describe the process of energy modeling. Recently, in the building industry the requirement for quality energy modeling has increased dramatically. This is because of the rise in energy prices coupled with new specific applications such as the LEED rating system, which places a large weighting on energy fitness for both new and existing buildings. Quality energy simulation requires consideration of many parameters such as simulation weather, energy profiles, air systems, plant performance, utility rates and analysis of multiple building design scenarios. The goal of this session is for each student to generate and interpret simulations for air systems, plants, and whole buildings and produce accurate operating cost comparison reports. Course Learning Outcomes As part of this software training, each student will learn how to use the Hourly Analysis (System Design Load) Program by completing several simple project exercises. These exercises confirm the student’s ability to understand the course learning outcomes. These are: Define and input the following o Energy simulation weather data, internal load schedules including profiles used for energy analysis, unitary packaged equipment power requirements, water chillers, boilers, cooling towers, hydronic distribution systems, electric and fuel rate structures and miscellaneous building energy use Generate and interpret simulation reports for air systems and plants Generate and interpret diagnostic reports for air systems and plants Trouble shoot air systems and plants Generate and interpret annual operating cost reports for a base and alternate design case Determine best practices from energy simulation Continuing Education Unit Credits (CEUs) One (1) IACET CEU is equal to ten (10) contact hours of participation in an organized continuing education experience under responsible sponsorship, capable direction, and qualified instruction. After successfully completing this training, the student receives an appropriate number of CEUs based on the classroom contact time. In addition, the Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 8 - 2015 June 22 [ENERGY SIMULATION] student should feel very comfortable using the eDesign Suite software to enhance their HVAC related job responsibilities. We use this IACET symbol throughout this manual to represent required learning outcomes and expect each student to comprehend the subject content by successfully demonstrating competency in these areas. NOTE: Because each state and municipality has their own rules, it is the responsibility of the participants to determine whether their agency accepts IACET CEUs toward whatever certification they are pursuing. This is not the responsibility of Carrier Corporation or its agents. Welcome to Energy Simulation for Commercial Buildings using HAP v4.9 We created this manual to assist engineers and designers in using the Hourly Analysis Program v4.9 for calculating commercial building cooling and heating loads and performing energy simulations. This manual is a companion to the hands-on training for the Hourly Analysis Program “Energy Simulations for Commercial Buildings” course facilitated by Carrier Software Systems Network. This manual includes all class exercises, workflow tips and additional helpful information related to the HAP program. Workbook Organization This section of the manual follows the logical process of the hands-on workshops and workflow. We cover the common process and special features of the HAP program. We arranged the topics of discussion in the same order as our hands-on training. The second section discusses how to use HAP to calculate a system design load. The second section follows the logical path of the program’s modules including detailed discussions and examples of the workflow process used to create a complete HAP Design Data set. This includes detailed discussions of the input forms, editing, document outputs and more. The third section of this student manual includes the following appendixes: Appendix A includes air system schematics. Appendix B contains detailed articles discussing numerous topics and frequently asked questions about HAP inputs and results. Appendix C includes several “white papers” discussing the advantages of the HAP program. These include System Based Design and the use of 8760 hourly weather profiles for calculations. Appendix D includes HAP e Help articles offering detailed explanations on frequently asked questions about HAP inputs and outputs. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 9 - 2015 June 22 [ENERGY SIMULATION] Project Definition and Outline Our project for this hands-on training is a 9-12 high school located in Singapore. There are numerous workshops and work sessions requiring use and understanding of all modules in the HAP program. Workshop #1 includes configuring the weather data, adding simulation weather data and defining annual holidays. Workshop #2 requires updating fractional and fan-thermostat schedules by adding profiles for assigning to the energy simulation of the buildings. Workshop #3 includes defining air systems for the different building types for calculating loads, selecting equipment, entering equipment performance, simulating the equipment and analyzing the results. In Workshop # 4 we calculate chiller and SWH boiler capacities, select and add chillers, towers and SWH boilers to our project library. In workshop # 5 we link the chillers, tower and SWH boilers to plants including configuring the distribution and simulate the plant operations to compare plant energy consumption for the different design scenarios. In Workshop # 6 we add the utility rates to the project library. We discuss simple and complex rate structures for electric, natural gas and remote source chilled and hot water. We also look at the Utility Rate Time of Day schedule. We then define the different building case studies, perform the energy simulation and compare the results; thus enabling us to offer the best solution to the building owner and stake holders. The objective of this projects is to provide a sustainable energy efficient 69,000 ft² (6,410 m²) one story high school building, with minimum carbon emissions. The target is to reduce energy consumption while improving the built environment. Included in our design project are recommended building envelope; fenestration optimized for daylighting; interior and exterior lighting systems; HVAC systems and controls; OA ventilation requirements and service water heating alternatives. We use an integrated, iterative continuous design and construction decision process for our building as shown in Figure 0.1 with the intention of fully coordinating best practices for sustainable design throughout the life of the building (cradle-to-cradle) as follows. Figure 0.1 - Continuous Design Decision Cycle For our school building project we selected Singapore which is located in ASHRAE Climate Zone 1A Hot and Moist, as detailed in the ASHRAE 90.1-2007 Appendix “B”. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 10 - [ENERGY SIMULATION] 2015 June 22 Marine (C) Dry (B) Moist (A) 2 All of Alaska in Zone 7 except for the following Boroughs in Zone 8: Bethel Northwest Artic Dellingham Southeast Fairbanks Fairbanks N. Star Wade Hampton Nome Yukon-Koyukuk North Slope 1 Zone 1 Includes Hawaii, Guam, Puerto Rico and the Virgin Islands Figure 0.2 – ASHRAE U.S. Climate Zone Map The following pages include floor plans of the school building. This manual contains detailed construction information for entering into the HAP program as needed for each of the work sessions. This hands-on training session also leaves ample time for participant question/answer sessions. Our goal is to make you familiar and comfortable with the input routines and the calculated and simulated results of the HAP Design Loads and Energy Simulation. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 11 - 2015 June 22 [ENERGY SIMULATION] Figure 0.4 – School Exterior “A” Commons Area Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 12 - 2015 June 22 [ENERGY SIMULATION] Figure 0.5 – A Commons Area Floor Plan Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 13 - 2015 June 22 [ENERGY SIMULATION] Figure 0.6 – “B” Classroom Wing Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 14 - 2015 June 22 [ENERGY SIMULATION] Figure 0.7 – “C” – Gymnasium Wing Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 15 - 2015 June 22 [ENERGY SIMULATION] Figure 0.8 – “D” Classroom Wing Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 16 - 2015 June 22 [ENERGY SIMULATION] We developed the school building construction using the ASHRAE Std. 90.1-2007 minimum envelope requirements and maximum “U” values for the building envelope components for each climate zone. We did not follow the 90.1 Appendix “G” modeling rules for our energy modeling. These requirements are covered in detail in our “Energy Modeling for LEED EA Cr-1” training session. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 17 - 2015 June 22 [ENERGY SIMULATION] Blank Page Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 18 - 2015 June 22 [ENERGY SIMULATION] Section 1 Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 19 - 2015 June 22 [ENERGY SIMULATION] Blank Page Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 20 - 2015 June 22 [ENERGY SIMULATION] Section 1_Workshop 1 Inputs - Create New Project and Link Simulation Weather Our first workshop focuses on expanding an existing design load analysis to include a complete energy simulation. Our first step is retrieving an archived system design load project developed in the Load Calculations for Commercial Buildings Training Seminar. The retrieval of this project includes all spaces, air systems and library items so we can focus on the additional input requirements for completing an energy analysis. Take the following steps to begin this workshop. First open windows explorer, navigate to folder B. Energy Simulation Student Handout on the flash drive, copy folder 02. Unsolved Workshop Archives to your desktop. Then launch HAP and create a new project as shown in Figure 1.1 below. Figure1.1 - Create New Project in HAP 4.9 Setting Project Preferences Once we create the New Project, HAP prompts us to choose the applicable ventilation standard for the project. This first step in our design process links our project to the appropriate database in determining the ventilation requirements for the spaces and air systems in our project. The choices include: User Defined ASHRAE 62-2001 ASHRAE 62.1-2004 Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 21 - 2015 June 22 ASHRAE 62.1-2007 ASHRAE 62.1-2010 [ENERGY SIMULATION] After assigning the appropriate ventilation standard, we assign the appropriate Energy Standard. The choices are: ASHRAE 90.1-2004 ASHRAE 90.1-2007 ASHRAE 90.1-2010 Please refer to Fig 1.2 below for additional details. Figure1.2 – Setting Project Preferences Select the ASHRAE 62.1-2007 Ventilation Standard, ASHRAE 90.1-2007 Energy Standard and Enter the appropriate Currency Symbol for our workshop and class project. Users can set HAP program preferences under the General Tab. Please refer to Figures 1.3 and 1.4 below for additional details of the General HAP program preferences. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 22 - 2015 June 22 [ENERGY SIMULATION] Figure 1.3 – HAP Program Preferences Figure1.4 – View/Preferences Note: Users can access the Program Preferences anytime by going to the View item on the menu bar and selecting Preferences as shown in Figure1.4 Retrieve Unsolved Archive 1 from B. Energy Simulation for Commercial Buildings/ Folder 02. Unsolved Archives/Singapore HAP49 EnergySim Unsolved Archive 1.E3A Enter Design and Simulation Weather Properties Next, we define the project design weather properties and link the 8760 hour simulation weather file used in energy simulations, using one of the following methods. We can assign the defaulted ASHRAE design weather properties by using the “Weather Wizard” or using the Weather Properties input forms. Let’s first look at the Weather Wizard. Go to the “Wizards” item on the menu bar and select “Weather Wizard.” When selecting the weather wizard, HAP presents the following graphical interface where the user selects the region, location and city either from the drop down or by clicking on the map. Refer to Fig 1.5 and 1.6 below for details. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 23 - 2015 June 22 [ENERGY SIMULATION] Figure 1.5 – HAP Weather Wizard Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 24 - 2015 June 22 [ENERGY SIMULATION] Figure 1.6 A, B & C – Weather Wizard Input Screens Once the user selects the Region, the next selection is Location. For our project, we selected Asia/Pacific, Singapore and finally Singapore. This defaults to the ASHRAE 0.4% summer design conditions and 99.6% winter design conditions. This step also automatically links the 8760 hourly simulation weather data. After selecting the weather properties HAP generates the following Weather Wizard Input Summary as shown in Figure 1.7. Figure 1.7 – Weather Wizard Design and Simulation Properties Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 25 - 2015 June 22 [ENERGY SIMULATION] After accepting the wizard inputs HAP converts the Wizard Data to the HAP interface as shown in Figure 1.8. Figure 1.8 – Wizard Created Data Once the Wizard Data successfully converts to HAP data, the user can return to HAP and edit any of the wizard created data by accessing the weather properties input forms as shown in Figure 1.9. Figure 1.9 - HAP Design Weather Properties Form. Note that you can edit any of the input items in the Design Parameters, Design Temperatures and Design Solar input forms. For our project, we accept the ASHRAE defaults for St. Louis IAP, Missouri. One of the major enhancements beginning with HAP 4.6 is the ability for users to import the following simulation weather data formats: ASHRAE IWEC (*.IWEC), ASHRAE IWEC2 (*.CSV), Energy Plus (*.EPW), USA TMY2 (*.TM2) or USA TMY3 (*.CSV). See Figure 1.10 Below for additional details. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 26 - 2015 June 22 [ENERGY SIMULATION] Figure 1.10 – Importing Simulation Weather Data Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 27 - 2015 June 22 [ENERGY SIMULATION] Defining the Holiday Schedule In the simulation input form under the simulation tab, configure energy simulation data for the same city. The appropriate simulation weather for Asia/Pacific_SINGAPORE_SINGAPORE_IWEC.HW1 linked when we used the wizard to define the weather properties. 1. Let us Import Simulation Weather from the Flash Drive folder 02 Unsolved Workshops as demonstrated. 2. Please change day of the week for January 1st to Thursday. 3. The next step is adding the following dates to the Holidays List by double left clicking the date on the calendar: 4. Use the Navigation buttons to change calendar month Holiday List 16-20 March 1-5, 8-12, 15-19, 22-26 June 04, 07-11 September 23-27, 30 November These dates represent typical secondary school holidays. We model the winter break in the fractional schedules for internal loads and energy use. Figure 1.11 – Adding Holidays Note: Please remember to “save early and save often” Design and simulation weather reports are displayed on the following pages. Use one of the following procedures to preview the weather input details. 1. Weather reports are available by highlighting “weather” in the left tree then left clicking on “Reports” and choosing “Print/View Input Data” or 2. Right click on < Weather Properties> and choose “Print/View Input Data”. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 28 - 2015 June 22 [ENERGY SIMULATION] Select the weather reports shown in Figure 1.12 below. HAP uses “Design” weather data in determining peak heating and cooling load calculations and sizing coils, fans and terminal equipment. HAP uses the 8760 hourly “Simulation” weather data to simulate building energy consumption and calculating annual operating cost based on the equipment sized and selected using the design weather data. Figure 1.12 Design and Simulation Weather Reports Below are just a few examples of the available weather reports. Weather Reports Design Parameters: City Name ...................................................................................................... Singapore Location ......................................................................................................... Singapore Latitude ...................................................................................................................... 1.4 Longitude .............................................................................................................. -104.0 Elevation .................................................................................................................. 52.0 Summer Design Dry-Bulb ........................................................................................ 91.0 Summer Coincident Wet-Bulb .................................................................................. 79.0 Summer Daily Range ............................................................................................... 11.3 Winter Design Dry-Bulb ............................................................................................ 73.0 Winter Design Wet-Bulb ........................................................................................... 60.9 Atmospheric Clearness Number .............................................................................. 1.00 Average Ground Reflectance ................................................................................... 0.20 Soil Conductivity .................................................................................................... 0.800 Local Time Zone (GMT +/- N hours) ......................................................................... -8.0 Consider Daylight Savings Time ................................................................................ No Simulation Weather Data ................................................................ SINGAPORE (EXT) Current Data is ...................................................................... 2001 ASHRAE Handbook Design Cooling Months ............................................................... January to December Singapore 2015 Energy Simulation for Commercial Buildings Deg. Deg. ft °F °F °F °F °F BTU/(hr-ft-°F) hours Page ‐ 29 - 2015 June 22 [ENERGY SIMULATION] Design Day Maximum Solar Heat Gains Month January February March April May June July August September October November December Month January February March April May June July August September October November December (The MSHG values are expressed in BTU/(hr-ft²) ) N NNE NE ENE 34.0 34.0 82.9 172.4 35.3 35.7 126.4 201.2 37.9 82.4 166.6 220.2 64.6 132.3 192.8 223.1 105.3 160.3 205.5 220.2 122.0 168.1 207.4 216.6 108.1 158.4 202.0 216.4 68.8 131.8 188.8 217.0 39.3 79.3 157.5 207.5 35.9 36.9 125.5 193.8 34.2 34.2 86.6 170.4 33.0 33.0 69.7 156.0 SSW SW WSW W 187.0 234.5 249.3 229.7 144.9 209.5 245.0 242.4 88.4 169.5 221.0 238.2 38.8 116.6 182.0 218.2 37.1 80.4 153.5 201.8 37.3 67.0 138.8 191.5 37.9 78.5 146.3 194.7 39.6 110.6 174.0 209.8 88.1 165.1 212.9 228.6 140.6 205.6 238.1 234.3 182.2 233.8 249.5 226.7 199.1 243.4 250.4 218.8 E 230.9 242.8 240.2 219.8 202.0 193.4 198.3 212.8 226.2 231.2 223.6 220.8 WNW 174.2 202.1 218.8 221.8 220.1 215.6 214.2 214.7 209.7 194.7 169.1 158.5 ESE 253.9 247.0 223.3 183.6 153.7 141.5 151.0 177.0 210.9 232.8 245.2 251.8 NW 86.8 129.1 165.5 192.1 205.4 207.6 202.1 187.8 159.2 123.0 83.9 70.1 SE 237.5 213.0 172.4 117.4 80.2 65.3 77.7 112.9 163.8 202.5 232.2 243.8 NNW 34.0 36.1 82.1 132.2 160.4 169.1 160.3 132.0 80.2 36.9 34.2 33.0 SSE 184.5 145.3 90.3 38.9 37.1 37.3 37.9 39.6 87.6 140.8 183.9 198.4 HOR 292.0 303.8 302.0 283.1 265.2 256.1 261.3 275.9 291.3 296.6 288.7 282.4 Mult. = User-defined solar multiplier factor. The Design Solar tab contains information about solar heat gain profiles for the currently selected city. Based on the design parameters for the city you selected, HAP constructs 24-hour profiles of solar flux and solar heat gain for all 12 months using ASHRAE procedures. Each profile represents clear sky solar conditions. Solar profiles are used for wall, roof and window load calculations. Singapore 2015 Energy Simulation for Commercial Buildings Page ‐ 30 - S 126.4 74.1 38.8 37.6 37.1 37.3 37.9 39.1 40.3 72.6 124.4 145.5 Mult 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2015 June 22 [ENERGY SIMULATION] Location: Singapore, Singapore (Dry and Wet Bulb temperatures are expressed in °F) Hr January February March DB WB DB WB DB WB 0000 71.7 69.9 73.7 71.4 76.7 73.5 0100 71.2 69.7 73.2 71.2 76.2 73.4 0200 70.6 69.5 72.6 71.1 75.6 73.2 0300 70.2 69.4 72.2 70.9 75.2 73.1 0400 69.8 69.2 71.8 70.9 74.8 73.0 0500 69.7 69.2 71.7 70.8 74.7 73.0 0600 69.9 69.3 71.9 70.9 74.9 73.0 0700 70.5 69.5 72.5 71.0 75.5 73.2 0800 71.5 69.8 73.5 71.3 76.5 73.5 0900 73.0 70.3 75.0 71.8 78.0 73.8 1000 74.7 70.9 76.7 72.2 79.7 74.3 1100 76.6 71.6 78.6 72.8 81.6 74.8 1200 78.4 72.2 80.4 73.3 83.4 75.3 1300 79.8 72.6 81.8 73.7 84.8 75.7 1400 80.7 72.9 82.7 73.9 85.7 75.9 1500 81.0 73.0 83.0 74.0 86.0 76.0 1600 80.7 72.9 82.7 73.9 85.7 75.9 1700 79.9 72.6 81.9 73.7 84.9 75.7 1800 78.6 72.2 80.6 73.3 83.6 75.4 1900 77.2 71.7 79.2 72.9 82.2 75.0 2000 75.7 71.3 77.7 72.5 80.7 74.6 2100 74.4 70.8 76.4 72.2 79.4 74.3 2200 73.3 70.5 75.3 71.9 78.3 74.0 2300 72.4 70.1 74.4 71.6 77.4 73.7 Hr July August September DB WB DB WB DB WB 0000 81.7 76.7 81.7 76.7 79.7 75.6 0100 81.2 76.5 81.2 76.5 79.2 75.5 0200 80.6 76.4 80.6 76.4 78.6 75.3 0300 80.2 76.3 80.2 76.3 78.2 75.2 0400 79.8 76.2 79.8 76.2 77.8 75.1 0500 79.7 76.1 79.7 76.1 77.7 75.1 0600 79.9 76.2 79.9 76.2 77.9 75.1 0700 80.5 76.3 80.5 76.3 78.5 75.3 0800 81.5 76.6 81.5 76.6 79.5 75.6 0900 83.0 77.0 83.0 77.0 81.0 75.9 1000 84.7 77.4 84.7 77.4 82.7 76.4 1100 86.6 77.9 86.6 77.9 84.6 76.9 1200 88.4 78.4 88.4 78.4 86.4 77.3 1300 89.8 78.7 89.8 78.7 87.8 77.7 1400 90.7 78.9 90.7 78.9 88.7 77.9 1500 91.0 79.0 91.0 79.0 89.0 78.0 1600 90.7 78.9 90.7 78.9 88.7 77.9 1700 89.9 78.7 89.9 78.7 87.9 77.7 1800 88.6 78.4 88.6 78.4 86.6 77.4 1900 87.2 78.0 87.2 78.0 85.2 77.0 2000 85.7 77.7 85.7 77.7 83.7 76.7 2100 84.4 77.4 84.4 77.4 82.4 76.3 2200 83.3 77.1 83.3 77.1 81.3 76.0 2300 82.4 76.8 82.4 76.8 80.4 75.8 Singapore 2015 Energy Simulation for Commercial Buildings April DB WB 77.7 74.6 77.2 74.4 76.6 74.3 76.2 74.1 75.8 74.1 75.7 74.0 75.9 74.1 76.5 74.2 77.5 74.5 79.0 74.9 80.7 75.4 82.6 75.9 84.4 76.3 85.8 76.7 86.7 76.9 87.0 77.0 86.7 76.9 85.9 76.7 84.6 76.4 83.2 76.0 81.7 75.6 80.4 75.3 79.3 75.0 78.4 74.8 October DB WB 77.7 74.6 77.2 74.4 76.6 74.3 76.2 74.1 75.8 74.1 75.7 74.0 75.9 74.1 76.5 74.2 77.5 74.5 79.0 74.9 80.7 75.4 82.6 75.9 84.4 76.3 85.8 76.7 86.7 76.9 87.0 77.0 86.7 76.9 85.9 76.7 84.6 76.4 83.2 76.0 81.7 75.6 80.4 75.3 79.3 75.0 78.4 74.8 May DB WB 78.7 75.6 78.2 75.5 77.6 75.3 77.2 75.2 76.8 75.1 76.7 75.1 76.9 75.1 77.5 75.3 78.5 75.6 80.0 75.9 81.7 76.4 83.6 76.9 85.4 77.3 86.8 77.7 87.7 77.9 88.0 78.0 87.7 77.9 86.9 77.7 85.6 77.4 84.2 77.0 82.7 76.7 81.4 76.3 80.3 76.0 79.4 75.8 November DB WB 74.7 72.9 74.2 72.7 73.6 72.5 73.2 72.4 72.8 72.2 72.7 72.2 72.9 72.3 73.5 72.5 74.5 72.8 76.0 73.3 77.7 73.9 79.6 74.6 81.4 75.2 82.8 75.6 83.7 75.9 84.0 76.0 83.7 75.9 82.9 75.6 81.6 75.2 80.2 74.7 78.7 74.3 77.4 73.8 76.3 73.5 75.4 73.1 June DB WB 80.7 76.7 80.2 76.5 79.6 76.4 79.2 76.3 78.8 76.2 78.7 76.1 78.9 76.2 79.5 76.4 80.5 76.6 82.0 77.0 83.7 77.4 85.6 77.9 87.4 78.4 88.8 78.7 89.7 78.9 90.0 79.0 89.7 78.9 88.9 78.7 87.6 78.4 86.2 78.0 84.7 77.7 83.4 77.4 82.3 77.1 81.4 76.8 December DB WB 72.7 70.9 72.2 70.7 71.6 70.5 71.2 70.4 70.8 70.2 70.7 70.2 70.9 70.3 71.5 70.5 72.5 70.8 74.0 71.3 75.7 71.9 77.6 72.6 79.4 73.2 80.8 73.6 81.7 73.9 82.0 74.0 81.7 73.9 80.9 73.6 79.6 73.2 78.2 72.7 76.7 72.3 75.4 71.8 74.3 71.5 73.4 71.1 Page ‐ 31 - [ENERGY SIMULATION] 2015 June 22 Simulation Weather Profile for August 27 Wednesday, August 27 Hour Dry-Bulb ( °F ) Wet-Bulb ( °F ) 0000 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 78.8 78.3 78.8 77.0 77.9 77.0 77.0 77.9 80.6 82.4 83.5 86.0 84.2 86.0 87.8 89.6 89.1 87.8 86.0 84.2 82.4 80.6 81.1 80.6 76.2 75.1 75.0 75.8 75.5 75.8 75.8 75.1 76.7 77.1 76.3 76.8 78.9 78.5 79.8 77.8 77.5 76.2 76.9 76.4 77.2 76.7 77.1 76.7 Singapore 2015 Energy Simulation for Commercial Buildings Beam Solar on Horiz. ( BTU/(hr-ft²) ) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6.6 17.9 28.3 81.1 126.9 156.9 170.5 152.1 110.2 38.1 1.3 0.0 0.0 0.0 0.0 0.0 Total Solar on Horiz. ( BTU/(hr-ft²) ) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6.3 49.1 103.5 152.2 212.0 254.0 272.6 262.7 226.6 165.0 86.0 17.5 0.0 0.0 0.0 0.0 0.0 Page ‐ 32 - 2015 June 23 [ENERGY SIMULATION ] Section 1_Workshop 2 – Editing Schedules This workshop focuses on editing the previously created schedules from our system design load calculations and were included in the retrieved archive. Please add the following hourly profiles to each schedule as noted: Lights - Classrooms Profile #4 – Energy Weekday Hours 00-06: 05% 07: 25% 08-11: 90% 12: 05% 13-15: 90% 16: 40% 17-23: 05% Profile #5 – Energy Weekend Hours 00-23: 05% On the Assignments tab, assign Profile #4 to Monday thru Friday in all months except December. Assign existing Profile #2 from the design load phase to Monday thru Friday in the month of June only. Assign existing Profile #3 to Monday thru Holiday for the month of July only. Assign Profile #5 to day types Saturday, Sunday, and Holiday for all months. Refer to Figure 2.1 for additional details. Figure 2.1 - Schedule - Profile Assignments-Lights Classrooms Singapore Energy Simulation for Commercial Buildings Page ‐ 33 - 2015 June 22 [ENERGY SIMULATION] People - Classrooms Profile #4 – Energy Weekday Hours 00-06: 00% Hour 07: 10% Hours 08-11: 90% Hour 12: 10% Hours 13-15: 90% Hour 16: 25% Hour 17: 10% Hours 18-23: 00% Profile #5 – Energy Saturday Hours 00-07: 00% Hours 08-12: 10% Hours 13-23: 00% On the Assignments tab, assign Profile #4 to day types Monday thru Friday in all months except June and December. Assign Profile #3 to day types Monday through Friday for June and December only and Profile #3 to Sunday thru Holiday in all months except December. Assign Profile #5 to day type Saturday for all months except June and December. Refer to Figure 2.2 for details. Figure 2.2 - Schedule–Profile Assignments-People-Classrooms Energy Simulation for Commercial Buildings Page ‐ 34 - [ENERGY SIMULATION] 2015 June 22 The remaining schedules were completed and included in the retrieved archive. They are shown below for reference only. Schedule Profile Assignments Input Details Lights - Classrooms (Fractional) Hourly Profiles: 1:Design Day Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Value 10 10 10 10 10 10 10 10 100 100 100 100 100 100 100 100 30 10 10 10 10 10 10 10 2:Summer School Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Value 5 5 5 5 5 5 5 5 60 60 60 60 60 25 5 5 5 5 5 5 5 5 5 5 3:Summer Shutdown Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Value 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 4:Energy Weekdays Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Value 5 5 5 5 5 5 5 25 90 90 90 90 5 90 90 90 40 5 5 5 5 5 5 5 5:Energy Weekends Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Value 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 Assignments: Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Design 1 1 1 1 1 2 3 1 1 1 1 1 Monday 4 4 4 4 4 2 3 4 4 4 4 4 Tuesday 4 4 4 4 4 2 3 4 4 4 4 4 Wednesday 4 4 4 4 4 2 3 4 4 4 4 4 Thursday 4 4 4 4 4 2 3 4 4 4 4 4 Friday 4 4 4 4 4 2 3 4 4 4 4 4 Saturday 5 5 5 5 5 5 5 5 5 5 5 5 Sunday 5 5 5 5 5 5 5 5 5 5 5 5 Holiday 5 5 5 5 5 5 5 5 5 5 5 5 Energy Simulation for Commercial Buildings Page ‐ 35 - [ENERGY SIMULATION] 2015 June 22 People - Classrooms (Fractional) Hourly Profiles: 1:Design Day Hour 00 Value 0 01 0 02 0 03 0 04 0 05 0 06 0 07 5 08 09 10 11 12 13 14 15 100 100 100 100 100 100 100 100 16 40 17 10 18 0 19 0 20 0 21 0 22 0 23 0 2:Summer School Hour 00 01 Value 0 0 02 0 03 0 04 0 05 0 06 0 07 0 08 40 09 40 10 40 11 40 12 40 13 10 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 3:Summer Shutdown Hour 00 01 02 Value 0 0 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 4:Weekday Energy Hour 00 01 Value 0 0 02 0 03 0 04 0 05 0 06 0 07 10 08 90 09 90 10 90 11 90 12 10 13 90 14 90 15 90 16 25 17 10 18 0 19 0 20 0 21 0 22 0 23 0 5:Energy Saturday Hour 00 01 Value 0 0 02 0 03 0 04 0 05 0 06 0 07 0 08 10 09 10 10 10 11 10 12 10 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 4 4 4 4 4 5 3 3 Feb 1 4 4 4 4 4 5 3 3 Mar 1 4 4 4 4 4 5 3 3 Energy Simulation for Commercial Buildings Apr 1 4 4 4 4 4 5 3 3 May 1 4 4 4 4 4 5 3 3 Jun 3 3 3 3 3 3 3 3 3 Jul 1 4 4 4 4 4 5 3 3 Aug 1 4 4 4 4 4 5 3 3 Sep 1 4 4 4 4 4 5 3 3 Oct 1 4 4 4 4 4 5 3 3 Nov 1 4 4 4 4 4 5 3 3 Page ‐ 36 - Dec 3 3 3 3 3 3 3 3 3 [ENERGY SIMULATION] 2015 June 22 People - Corridors (Fractional) Hourly Profiles: 1:Design Day Hour 00 01 Value 0 0 02 0 03 0 04 0 05 0 06 0 07 50 08 09 10 11 12 13 14 15 100 100 100 100 100 100 100 100 16 30 17 10 18 0 19 0 20 0 21 0 22 0 23 0 2:Summer School Hour 00 01 Value 0 0 02 0 03 0 04 0 05 0 06 0 07 0 08 40 09 40 10 40 11 40 12 40 13 40 14 10 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 3:Summer Shutdown Hour 00 01 02 Value 0 0 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 4:Weekday Energy Hour 00 01 Value 0 0 02 0 03 0 04 0 05 0 06 0 07 25 08 50 09 40 10 40 11 45 12 60 13 45 14 40 15 40 16 25 17 10 18 0 19 0 20 0 21 0 22 0 23 0 5:Energy Weekends Hour 00 01 02 Value 0 0 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 4 4 4 4 4 5 5 5 Feb 1 4 4 4 4 4 5 5 5 Mar 1 4 4 4 4 4 5 5 5 Energy Simulation for Commercial Buildings Apr 1 4 4 4 4 4 5 5 5 May 1 4 4 4 4 4 5 5 5 Jun 5 5 5 5 5 5 5 5 5 Jul 1 4 4 4 4 4 5 5 5 Aug 1 4 4 4 4 4 5 5 5 Sep 1 4 4 4 4 4 5 5 5 Oct 1 4 4 4 4 4 5 5 5 Nov 1 4 4 4 4 4 5 5 5 Page ‐ 37 - Dec 5 5 5 5 5 5 5 5 5 [ENERGY SIMULATION] 2015 June 22 People IT Room (Fractional) Hourly Profiles: 1:Design Day Hour 00 01 Value 0 0 02 0 03 0 04 0 05 0 06 0 07 10 08 100 09 0 10 0 11 0 12 100 13 0 14 0 15 100 16 0 17 10 18 0 19 0 20 0 21 0 22 0 23 0 2:Summer School Hour 00 01 02 Value 0 0 0 03 0 04 0 05 0 06 0 07 0 08 0 09 40 10 0 11 0 12 40 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 3:Summer Shutdown Hour 00 01 02 Value 0 0 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 1 1 1 1 1 3 3 3 Feb 1 1 1 1 1 1 3 3 3 Mar 1 1 1 1 1 1 3 3 3 Apr 1 1 1 1 1 1 3 3 3 May 1 1 1 1 1 1 3 3 3 Jun 3 3 3 3 3 3 3 3 3 Jul 1 1 1 1 1 1 3 3 3 Aug 1 1 1 1 1 1 3 3 3 Sep 1 1 1 1 1 1 3 3 3 Oct 1 1 1 1 1 1 3 3 3 Nov 1 1 1 1 1 1 3 3 3 Dec 3 3 3 3 3 3 3 3 3 Equipment IT (Fractional) Hourly Profiles: 1:design Hour 00 01 Value 25 25 02 25 03 25 04 25 05 25 06 25 07 80 08 80 09 50 10 50 11 50 12 80 13 70 14 60 15 50 16 80 17 50 18 25 19 25 20 25 21 25 22 25 23 25 2:Summer Hour 00 Value 25 02 25 03 25 04 25 05 25 06 25 07 25 08 25 09 25 10 25 11 25 12 25 13 25 14 25 15 25 16 25 17 25 18 25 19 25 20 25 21 25 22 25 23 25 01 25 Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 1 1 1 1 1 2 2 2 Feb 1 1 1 1 1 1 2 2 2 Mar 1 1 1 1 1 1 2 2 2 Energy Simulation for Commercial Buildings Apr 1 1 1 1 1 1 2 2 2 May 1 1 1 1 1 1 2 2 2 Jun 2 2 2 2 2 2 2 2 2 Jul 2 2 2 2 2 2 2 2 2 Aug 1 1 1 1 1 1 2 2 2 Sep 1 1 1 1 1 1 2 2 2 Oct 1 1 1 1 1 1 2 2 2 Nov 1 1 1 1 1 1 2 2 2 Page ‐ 38 - Dec 2 2 2 2 2 2 2 2 2 [ENERGY SIMULATION] 2015 June 22 Occupied Schedule - Classroom (Fan / Thermostat) Hourly Profiles: 1:Design Day Hour 00 01 Value U U 02 U 03 U 04 U 05 U 06 O 07 O 08 O 09 O 10 O 11 O 12 O 13 O 14 O 15 O 16 O 17 O 18 U 19 U 20 U 21 U 22 U 23 U 2:Summer School Hour 00 01 Value U U 02 U 03 U 04 U 05 U 06 O 07 O 08 O 09 O 10 O 11 O 12 O 13 O 14 U 15 U 16 U 17 U 18 U 19 U 20 U 21 U 22 U 23 U 3:Summer Shutdown Hour 00 01 02 Value U U U 03 U 04 U 05 U 06 U 07 U 08 U 09 U 10 U 11 U 12 U 13 U 14 U 15 U 16 U 17 U 18 U 19 U 20 U 21 U 22 U 23 U 4:Energy Weekdays Hour 00 01 02 Value U U U 03 U 04 U 05 U 06 O 07 O 08 O 09 O 10 O 11 O 12 O 13 O 14 O 15 O 16 O 17 O 18 U 19 U 20 U 21 U 22 U 23 U 5:Energy Saturday Hour 00 01 Value U U 03 U 04 U 05 U 06 U 07 O 08 O 09 O 10 O 11 O 12 O 13 U 14 U 15 U 16 U 17 U 18 U 19 U 20 U 21 U 22 U 23 U 02 U O = Occupied; U = Unoccupied Assignments: Design Monday Tuesday Wednesday Thursday Friday Saturday Sunday Holiday Jan 1 4 4 4 4 4 2 3 3 Feb 1 4 4 4 4 4 2 3 3 Mar 1 4 4 4 4 4 2 3 3 Energy Simulation for Commercial Buildings Apr 1 4 4 4 4 4 2 3 3 May 1 4 4 4 4 4 2 3 3 Jun 3 3 3 3 3 3 2 3 3 Jul 1 4 4 4 4 4 2 3 3 Aug 1 4 4 4 4 4 2 3 3 Sep 1 4 4 4 4 4 2 3 3 Oct 1 4 4 4 4 4 2 3 3 Nov 1 4 4 4 4 4 2 3 3 Page ‐ 39 - Dec 3 3 3 3 3 3 2 3 3 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 40 - [ENERGY SIMULATION] 2015 June 22 Section 2 Energy Simulation for Commercial Buildings Page ‐ 41 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 42 - 2015 June 22 [ENERGY SIMULATION] Section 2_Workshop 3 - Modeling 4-Pipe Fan Coil Unit Air Systems - Using the Equipment Wizard. Launch the Equipment Wizard by selecting the Wizard item on the Menu bar and clicking the Equipment Wizard on the list. See Figure 3.1 for details. Figure 3.1 - Launching the Equipment Wizard Next add the following spaces top the system. Assign spaced D100 through D114 to the building and click OK. Refer to Figure 3.2 for additional details. Figure 3.2 - Assign Spaces to Building in Wizard After assigning the spaces the following screen appears. Enter the system and equipment data as described below and detailed in the following figures. Energy Simulation for Commercial Buildings Page ‐ 43 - 2015 June 22 [ENERGY SIMULATION] Figure 3.3a - Equipment Wizard Screen 1 1. 2. 3. 4. 5. 6. 7. 8. 9. Enter Air System Name and Identifier Select 4 Pipe Hydronic Fan Coil Units from Equipment Type dropdown Select Hot Water from the Heating Type dropdown Select Fan Coil Units from the System Type dropdown Select One FCU per Zone from the Configuration dropdown Select Occupied Schedule-Classroom from the Operating Schedule dropdown Select CW Ventilation Unit from the Common Vent Unit dropdown Select Used from the DCV Control dropdown Select Energy Recovery Ventilator (ERV) from the Ventilation Reclaim dropdown Now click on the Details Button and enter the details as shown in Fig 3.3b. Energy Simulation for Commercial Buildings Page ‐ 44 - 2015 June 22 [ENERGY SIMULATION] Figure 3.3b - Equipment Wizard Screen 2 1. Enter the FCU Design SAT 58ºF Cooling and 90ºF Heating 2. Enter Terminal Unit Supply Fan Performance 0.50” wg. 3. Accept T-stat Occ/Unocc Setpoints 75º/80º F [23.89º/26.67º C] Clg and 70º/65º F [21.1º/18.3º C] Htg. 4. Accept the Operating Schedule using the T-Stat Schedule - Classrooms 5. Enter the Common Vent Unit Cooling and Heating Coil Setpoint 75º/70º F [23.89º/21.1ºC] 6. Enter the Ventilation and Exhaust fan performance of 1.50”/1.00” wg respectively. 7. Configure the DCV Base Ventilation Rate 20%, 257ppm Min. CO2, 700ppm Max CO2 differentials and 393ppm Outdoor Air CO2 levels 8. Enter 50% Ventilation Reclaim Efficiency and 0.200kW Input Power 9. Click OK when finished. 10. Click Next Button Because we are only analyzing the Wing D 4 Pipe FCU air system, we can just accept the chiller and boiler plant defaults which we will discard. The next two screens depict the chiller and boiler plant wizard input forms and are for reference only. Energy Simulation for Commercial Buildings Page ‐ 45 - 2015 June 22 [ENERGY SIMULATION] Figure 3.3c - Equipment Wizard Screen 2 Click on the Next button and enter the data detailed in Figure 3.3d Energy Simulation for Commercial Buildings Page ‐ 46 - 2015 June 22 [ENERGY SIMULATION] Figure 3.3d - Equipment Wizard Screen 3 Click Finish. Clicking the Finish button generates the following Equipment Wizard input report. Please refer to the details in Figure 3.3e below. Energy Simulation for Commercial Buildings Page ‐ 47 - 2015 June 22 [ENERGY SIMULATION] EQUIPMENT ALTERNATIVE: (C8-FCU) 4 Pipe Fan Coil Units Equipment and System Data Summary Description Name ...................................................................... 2P FCU Identifier .................................................................. 2P FCU Notes ..................................................................................... Equipment Equipment Type ............................... 2-Pipe Fan Coil Units Heating Type ............................................................... None System Type ................................................ Fan Coil Units Configuration ......................................... One FCU per Zone Operating Schedule ............ T-Stat Schedule - Classroom Key Features Common Ventilation Unit .................... CW Ventilation Unit Demand Controlled Ventilation .................................... Used Ventilation Reclaim ..... Energy Recovery Ventilator (ERV) Equipment and System Details Terminal Unit Cooling Design SAT ................................................................... 58.0 °F Terminal Unit Features Supply Fan Performance .............................................. 0.50 in wg Thermostats Cooling Setpoint, Occupied ........................................... 75.0 Cooling Setpoint, Unoccupied ....................................... 80.0 Heating Setpoint, Occupied ........................................... 70.0 Heating Setpoint, Unoccupied ....................................... 65.0 Operating Schedule ............ T-Stat Schedule - Classroom °F °F °F °F Common Ventilation Unit Type .................................................... CW Ventilation Unit Cooling Coil Setpoint ..................................................................... 75.0 °F Heating Coil Setpoint ..................................................................... 70.0 °F Fan Performance Ventilation Fan Performance ..................................... 1.50 in wg Exhaust Fan Performance ......................................... 1.00 in wg Demand Controlled Ventilation Used ........................................................................ Used Base Ventilation Rate ................................................... 20 Min. CO2 Differential .................................................. 267 Max. CO2 Differential ................................................. 700 Outdoor Air CO2 Level ............................................... 393 Energy Simulation for Commercial Buildings % PPM PPM PPM Page 48 2015 June 23 [ENERGY SIMULATION ] Ventilation Reclaim Type ........................ Energy Recovery Ventilator (ERV) Efficiency ...................................................................... 65 % Input Power .............................................................. 0.200 kW Zone Configuration No. of Floors .................................................................... 1 Use Typical Intermediate Floor? .................................. No Configuration of Spaces and Zones Building Floor 1 D100 - Computer Server D100 - Computer Server D101 - Classroom D101 - Classroom D102 - Classroom D102 - Classroom D103 - Classroom D103 - Classroom D104 - Classroom D104 - Classroom D105 - South Vestibule D105 - South Vestibule D106 - Classroom D106 - Classroom D107 - Classroom D107 - Classroom D108 - Music Room D108 - Music Room D109 - Music Practice D109 - Music Practice D110 - Music Files D110 - Music Files D111 - Music Office D111 - Music Office D112 - West Vestibule D112 - West Vestibule D113 - Corridor D113 - Corridor D114 - Corridor D114 – Corridor Figure 3.3e - Equipment and System Wizard Data Summary Open the air system and under the Vent System Components tab, Ventilation Air, select ASHRAE 62.1-2007 as the Ventilation Sizing Method. Next, calculate the air system by highlight the system on the list and select reports/print view design reports. HINT Select the Air System Sizing Summary report first to speed up the terminal air system calculations. Refer to figure 3.4 below for details Singapore Energy Simulation for Commercial Buildings Page ‐ 49 - 2015 June 22 [ENERGY SIMULATION] Figure 3.4 - Select Print View Design Reports Figure 3.5 - Select Air System Sizing Summary Report HINT: After the initial system calculations, choose to print view design results and select all reports you want to view. Refer to the following reports for details of the design load results for this air system. Energy Simulation for Commercial Buildings Page ‐ 50 - 2015 June 22 [ENERGY SIMULATION] Section 2, Workshop 3 Results Energy Simulation for Commercial Buildings Page ‐ 51 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 52 - 2015 June 22 [ENERGY SIMULATION] System Design Reports Air System Information Number of zones .......................................................... 15 Floor Area ............................................................ 9216.0 ft² Location ..................................... Singapore, Singapore 2P FCU - Whole Building................................ Equipment Class .................................. TERM Air System Type ................................... 2P-FC Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads Calculation Months .............................. Jan to Dec Sizing Data .......................................... Calculated Cooling Coil Sizing Data Total coil load .................................... 2.1 Total coil load .......................................... 25.2 Sensible coil load .................................... 25.2 Coil CFM at Aug 1500 ............................ 2902 Max coil CFM ......................................... 2902 Sensible heat ratio ................................ 1.000 Water flow @ 10.0 °F rise ....................... 5.04 Tons MBH MBH CFM CFM Load occurs at .................................................. Aug 1500 OA DB / WB ..................................................... 91.0 / 79.0 °F Entering DB / WB ............................................ 82.0 / 71.0 °F Leaving DB / WB ............................................. 74.0 / 68.6 °F Bypass Factor .......................................................... 0.100 gpm Ventilation Fan Sizing Data Actual max CFM .................................... 2902 CFM Standard CFM ........................................ 2897 CFM Actual max CFM/ft² ................................. 0.31 CFM/ft² Fan motor BHP .......................................................... 1.19 BHP Fan motor kW ............................................................ 0.95 kW Fan static ................................................................... 1.50 in wg Exhaust Fan Sizing Data Actual max CFM ..................................... 2902 CFM Standard CFM ........................................ 2897 CFM Actual max CFM/ft² ................................. 0.31 CFM/ft² Fan motor BHP .......................................................... 0.79 BHP Fan motor kW ............................................................ 0.63 kW Fan static ................................................................... 1.00 in wg Outdoor Ventilation Air Data Design airflow CFM ............................... 2902 CFM CFM/ft² .................................................... 0.31 CFM/ft² CFM/person .................................... 12.84 CFM/Person NOTE: This report is for the Dedicated Outdoor Air System (DOAS) only. For Terminal Unit Sizing data refer to the Zone Sizing Summary Report. Energy Simulation for Commercial Buildings Page 53 [ENERGY SIMULATION] 2015 April 02 Zone Sizing Summary Air System Information Air System Name ......... 2P FCU - Whole Building Number of zones .......................................................... 15 Floor Area .............................................................. 9216.0 ft² Location ....................................... Singapore, Singapore Equipment Class ................................................ TERM Air System Type ................................................. 2P-FC Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sizing ................ Sum of space airflow rates Space CFM Sizing ............ Individual peak space loads Calculation Months ..................................... Jan to Dec Sizing Data ................................................. Calculated Terminal Unit Sizing Data - Cooling Zone Name D100 - IT Room D101 - Classroom D102 - Classroom D103 - Classroom D104 - Classroom D105 - South Vestibule D106 - Classroom D107 - Classroom D108 - Music Room D109 - Music Practice D110 - Music Files D111 - Music Office D112 - West Vestibule D113 - Corridor D114 - Corridor Total Coil Load (kBTUh) 5.9 28.5 28.5 28.5 32.1 2.7 31.0 29.5 60.5 2.7 2.2 4.8 2.8 10.1 12.3 Sens Coil Load (kBTUh) 5.5 19.1 19.1 19.1 22.5 2.2 21.5 19.9 41.8 2.1 1.6 3.7 2.2 6.1 7.3 Coil Entering DB / WB (°F) 76.4 / 64.3 76.1 / 66.7 76.1 / 66.7 76.1 / 66.7 76.1 / 66.4 76.6 / 65.6 76.3 / 66.7 76.2 / 66.8 76.2 / 66.4 76.3 / 66.1 76.5 / 66.3 76.5 / 65.8 76.6 / 65.6 76.6 / 67.9 76.6 / 68.0 Coil Leaving DB / WB (°F) 58.7 / 57.6 58.2 / 57.3 58.2 / 57.3 58.2 / 57.3 58.5 / 57.6 58.6 / 57.6 58.8 / 57.9 58.5 / 57.7 58.0 / 57.1 59.0 / 58.1 58.6 / 57.7 58.8 / 57.8 58.8 / 57.8 58.0 / 57.3 58.0 / 57.3 Water Flow @ 10.0 °F (gpm) 1.17 5.70 5.70 5.70 6.42 0.54 6.21 5.89 12.11 0.55 0.44 0.96 0.55 2.03 2.47 Time of Peak Coil Load Aug 1200 Jul 1500 Jul 1500 Jul 1500 Jul 1500 Aug 1500 Aug 1500 Aug 1500 Jul 1400 Jul 1500 Aug 1500 Aug 1500 Aug 1500 Aug 1200 Aug 1300 Zone CFM/ft² 8.29 1.17 1.17 1.17 1.41 1.26 1.27 1.16 1.15 1.70 0.95 1.35 1.31 0.41 0.39 Terminal Unit Sizing Data - Heating, Fan, Ventilation Zone Name D100 - IT Room D101 - Classroom D102 - Classroom D103 - Classroom D104 - Classroom D105 - South Vestibule D106 - Classroom D107 - Classroom D108 - Music Room D109 - Music Practice D110 - Music Files D111 - Music Office D112 - West Vestibule D113 - Corridor D114 - Corridor Heating Coil Load (kBTUh) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Energy Simulation for Commercial Buildings Heating Coil Ent/Lvg DB (°F) -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 -1.0 / -1.0 Htg Coil Water Flow @20.0 °F (gpm) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Fan Design Airflow (CFM) 290 986 986 986 1184 111 1135 1040 2129 110 84 195 115 304 366 Fan Motor (BHP) 0.043 0.146 0.146 0.146 0.175 0.016 0.168 0.154 0.315 0.016 0.012 0.029 0.017 0.045 0.054 Fan Motor (kW) 0.034 0.116 0.116 0.116 0.139 0.013 0.133 0.122 0.250 0.013 0.010 0.023 0.013 0.036 0.043 OA Vent Design Airflow (CFM) 7 351 351 351 351 5 358 358 611 24 11 19 5 45 57 Page 54 [ENERGY SIMULATION] Zone Peak Sensible Loads Zone Cooling Time of Sensible Peak Sensible (kBTUh) Cooling Load 5.3 Sep 1200 18.1 Aug 1500 18.1 Aug 1500 18.1 Aug 1500 21.7 Aug 1500 2.0 Aug 1500 20.8 Aug 1500 19.1 Aug 1500 39.0 Aug 1500 2.0 Aug 1500 1.5 Aug 1500 3.6 Aug 1500 2.1 Aug 1500 5.6 Aug 1400 6.7 Aug 1400 Zone Name D100 - IT Room D101 - Classroom D102 - Classroom D103 - Classroom D104 - Classroom D105 - South Vestibule D106 - Classroom D107 - Classroom D108 - Music Room D109 - Music Practice D110 - Music Files D111 - Music Office D112 - West Vestibule D113 - Corridor D114 - Corridor Zone Heating Load (kBTUh) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Zone Floor Area (ft²) 35.0 840.0 840.0 840.0 840.0 88.0 896.0 896.0 1856.0 65.0 88.0 144.0 88.0 750.0 950.0 Space Loads and Airflows Zone Name / Space Name D100 - IT Room D100 - IT Room D101 - Classroom D101 - Classroom D102 - Classroom D102 - Classroom D103 - Classroom D103 - Classroom D104 - Classroom D104 - Classroom D105 - South Vestibule D105 - South Vestibule D106 - Classroom D106 - Classroom D107 - Classroom D107 - Classroom D108 - Music Room D108 - Music Room D109 - Music Practice D109 - Music Practice D110 - Music Files D110 - Music Files D111 - Music Office D111 - Music Office D112 - West Vestibule D112 - West Vestibule D113 - Corridor D113 - Corridor D114 - Corridor D114 - Corridor Mult. Cooling Sensible (kBTUh) Time of Load Air Flow (CFM) Heating Load (kBTUh) Floor Area (ft²) Space CFM/ft² 1 5.3 Sep 1200 290 0.0 35.0 8.29 1 18.1 Aug 1500 986 0.0 840.0 1.17 1 18.1 Aug 1500 986 0.0 840.0 1.17 1 18.1 Aug 1500 986 0.0 840.0 1.17 1 21.7 Aug 1500 1184 0.0 840.0 1.41 1 2.0 Aug 1500 111 0.0 88.0 1.26 1 20.8 Aug 1500 1135 0.0 896.0 1.27 1 19.1 Aug 1500 1040 0.0 896.0 1.16 1 39.0 Aug 1500 2129 0.0 1856.0 1.15 1 2.0 Aug 1500 110 0.0 65.0 1.70 1 1.5 Aug 1500 84 0.0 88.0 0.95 1 3.6 Aug 1500 195 0.0 144.0 1.35 1 2.1 Aug 1500 115 0.0 88.0 1.31 1 5.6 Aug 1400 304 0.0 750.0 0.41 1 6.7 Aug 1400 366 0.0 950.0 0.39 Energy Simulation for Commercial Buildings Page ‐ 55 - [ENERGY SIMULATION] 2015 June 22 Ventilation Sizing Summary 1. Summary Ventilation Sizing Method ........................................... ASHRAE Std 62.1-2007 Design Condition ................................................................. Cooling operation Occupant Diversity .................................................................................... 1.000 Uncorrected Ventilation Airflow Rate ......................................................... 2902 CFM System Ventilation Efficiency .................................................................... 1.000 Design Ventilation Airflow Rate ................................................................. 2902 CFM 2. Space Ventilation Analysis Table Space Floor Zone Name / Space Name D100 - Computer Server D100 - IT Room D101 - Classroom D101 - Classroom D102 - Classroom D102 - Classroom D103 - Classroom D103 - Classroom D104 - Classroom D104 - Classroom D105 - South Vestibule D105 - South Vestibule D106 - Classroom D106 - Classroom D107 - Classroom D107 - Classroom D108 - Music Room D108 - Music Room D109 - Music Practice D109 - Music Practice D110 - Music Files D110 - Music Files D111 - Music Office D111 - Music Office D112 - West Vestibule D112 - West Vestibule D113 - Corridor D113 - Corridor D114 - Corridor D114 - Corridor Totals (incl. Space Multipliers) Supply Air (CFM) Mult. (Vpz) Area (ft²) (Az) Area Time Outdoor Averaged Air Rate Occupancy (CFM/ft²) (Occupants) (Ra) (Pz) People Outdoor Air Air Rate Distribution (CFM/person) Effectiveness (Rp) (Ez) Space Outdoor Air (CFM) (Voz) Breathing Zone Space Outdoor Air Ventilation (CFM) Efficiency (Vbz) (Evz) 1 290 35.0 0.06 1.0 5.00 1.00 7 7 1.000 1 986 840.0 0.12 25.0 10.00 1.00 351 351 1.000 1 986 840.0 0.12 25.0 10.00 1.00 351 351 1.000 1 986 840.0 0.12 25.0 10.00 1.00 351 351 1.000 1 1184 840.0 0.12 25.0 10.00 1.00 351 351 1.000 1 111 88.0 0.06 2.0 0.00 1.00 5 5 1.000 1 1135 896.0 0.12 25.0 10.00 1.00 358 358 1.000 1 1040 896.0 0.12 25.0 10.00 1.00 358 358 1.000 1 2129 1856.0 0.06 50.0 10.00 1.00 611 611 1.000 1 110 65.0 0.06 2.0 10.00 1.00 24 24 1.000 1 84 88.0 0.12 1.0 0.00 1.00 11 11 1.000 1 195 144.0 0.06 2.0 5.00 1.00 19 19 1.000 1 115 88.0 0.06 2.0 0.00 1.00 5 5 1.000 1 304 750.0 0.06 8.0 0.00 1.00 45 45 1.000 1 366 950.0 0.06 8.0 0.00 1.00 57 57 1.000 2902 1.000 10023 Energy Simulation for Commercial Buildings Page ‐ 56 - [ENERGY SIMULATION] 2015 June 22 Air System Design Load Summary Report ZONE LOADS Window & Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions Ceiling Overhead Lighting Task Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads Zone Conditioning Plenum Wall Load Plenum Roof Load Plenum Lighting Load Exhaust Fan Load Ventilation Load Ventilation Fan Load Space Fan Coil Fans Duct Heat Gain / Loss >> Total System Loads Cooling Coil Heating Coil Terminal Unit Cooling Terminal Unit Heating >> Total Conditioning Key: DESIGN COOLING DESIGN HEATING COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 90.7 °F / 78.9 °F HEATING OA DB / WB 73.0 °F / 60.9 °F Sensible Latent Sensible Latent Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) 768 ft² 9668 768 ft² 2400 ft² 4964 2400 ft² 0 9216 ft² 24140 9216 ft² 0 768 ft² 12543 768 ft² 0 0 ft² 0 0 ft² 0 0 ft² 0 0 ft² 0 9216 ft² 0 9216 ft² 0 0 ft² 0 0 ft² 0 0 ft² 0 0 ft² 0 16430 W 43721 0 0 7657 W 22639 0 0 4809 W 15015 0 0 225 36251 27000 0 0 0 10698 23224 0 0 0 0 0 0 0% / 0% 0 0 0% 0 0 179639 50224 0 0 189940 50224 0 0 0% 0 0 0 0% 0 0 0 0% 0 0 0 2902 CFM 2152 2902 CFM -2152 2902 CFM 14933 37077 2902 CFM -7234 0 2902 CFM 3227 2902 CFM -3227 4012 -4012 0% 0 0% 0 214264 87301 -16626 0 24494 0 0 0 0 0 189771 86520 -16626 0 0 0 214264 86520 -16626 0 Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads This report represents the “block load” of this system and includes the DOAS and Terminal Units coil loads. Energy Simulation for Commercial Buildings Page ‐ 57 - [ENERGY SIMULATION] 2015 June 22 Hourly Zone Load Report Example Hour 0000 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 OA TEMP (°F) 81.7 81.2 80.6 80.2 79.8 79.7 79.9 80.5 81.5 83.0 84.7 86.6 88.4 89.8 90.7 91.0 90.7 89.9 88.6 87.2 85.7 84.4 83.3 82.4 ZONE TEMP (°F) 80.1 80.1 80.1 80.1 80.1 80.1 75.8 75.5 76.2 76.1 76.2 76.4 76.2 76.2 76.3 76.1 76.3 76.0 80.2 80.2 80.2 80.2 80.1 80.1 RH (%) 58 59 60 61 61 62 75 75 64 61 60 59 58 57 56 56 64 68 55 55 56 56 57 58 ZONE AIRFLOW (CFM) 107.3 100.8 93.5 86.9 81.0 77.5 1183.9 1183.9 1183.9 1183.9 1183.9 1183.9 1183.9 1183.9 1183.9 1183.9 1183.9 1183.9 161.0 154.4 141.7 132.3 122.7 114.2 ZONE: D104 - Classroom DESIGN MONTH: JULY ZONE SENSIBLE ZONE LOAD COND (BTU/hr) (BTU/hr) 6970.6 2558.6 6529.4 2402.7 6105.8 2229.6 5729.1 2069.9 5401.6 1929.9 5158.8 1845.1 5039.4 10398.3 5515.3 10441.6 14665.2 17540.9 16407.9 18938.8 17839.8 19844.5 19036.9 20206.2 19965.6 21428.0 20742.5 21957.1 21279.6 22114.9 21505.6 22477.8 15977.6 16423.3 13107.4 14003.5 11494.8 3852.1 10348.3 3692.1 9454.8 3387.1 8723.2 3160.2 8052.4 2929.8 7467.4 2726.0 TERMINAL COOLING COIL (BTU/hr) 4191.0 3995.7 3775.0 3567.5 3381.9 3267.7 12470.4 15108.3 25315.2 27511.7 28436.8 28643.3 30655.6 31318.3 31386.5 32100.9 22208.7 17659.7 5735.1 5551.1 5196.3 4927.9 4645.2 4397.6 TERMINAL HEATING COIL (BTU/hr) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 The Hourly Zone Load report displays zone temperatures and relative humidity values along with zone sensible load and heat extraction rate. Next, highlight the same air system and select Reports, Print/View Simulation Results and View to generate the Air System Simulation Results. Figure 3.6 - Select Simulation Results Reports Energy Simulation for Commercial Buildings Page ‐ 58 - ZONE HEATING UNIT (BTU/hr) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2015 June 22 [ENERGY SIMULATION] Figure 3.7 - Select Air System Simulation Results Reports Figure 3.8 - Rerun and View all Air System Simulation Results Energy Simulation for Commercial Buildings Page ‐ 59 - [ENERGY SIMULATION] 2015 June 22 System Simulation Reports Monthly, Daily and Hourly Simulation Results Monthly Air System Simulation Results Air System Simulation Results (Table 1) : Terminal Cooling Coil Load Ventilation Fan (kBTU) (kWh) 46860 244 Precool Coil Load (kBTU) 3660 Preheat Coil Load (kBTU) 0 February 3588 0 46287 March 3163 0 47470 Month January Vent. Reclaim Device (kWh) Exhaust Fan (kWh) 163 Terminal Fan (kWh) 366 220 147 330 54 189 126 305 47 60 April 4420 0 56257 241 161 364 59 May 4015 0 57061 233 156 363 58 June 126 0 28105 10 7 106 6 July 4107 0 55443 251 168 378 61 August 3867 0 51874 233 156 359 58 September 2880 0 41439 178 119 283 44 October 4093 0 53064 244 163 369 61 November 2331 0 38676 168 112 270 42 89 0 15367 10 7 75 6 36339 0 537901 2222 1481 3567 557 December Total Air System Simulation Results (Table 2) : Lighting (kWh) 2834 Electric Equipment (kWh) 927 February 2571 840 March 2329 832 April 2811 911 May 2734 908 Month January June 591 490 July 2931 751 August 2734 908 September 2210 796 October 2834 927 November 2109 777 December Total 611 506 27300 9575 Energy Simulation for Commercial Buildings Page ‐ 60 - [ENERGY SIMULATION] Monthly Air System Simulation Graph Precool Coil Load (kBTU) Terminal Cooling Coil Load (kBTU) 55000 50000 45000 40000 kBTU 35000 30000 25000 20000 15000 10000 5000 0 Jan Feb Mar Apr Energy Simulation for Commercial Buildings May Jun Jul Month Aug Sep Oct Nov Page ‐ 61 - Dec [ENERGY SIMULATION] 2015 June 22 Daily Air System Simulation Results Daily Air System Simulation Results for August (Table 1): Terminal Precool Coil Preheat Coil Cooling Coil Load Load Load Ventilation Fan Day (kBTU) (kBTU) (kBTU) (kWh) 1 34 0 917 3 Exhaust Fan (kWh) 2 Terminal Fan (kWh) 10 2 0 0 545 0 0 2 3 123 0 2082 10 7 14 4 169 0 1988 10 7 14 5 200 0 2224 10 7 14 6 205 0 2315 10 7 14 7 197 0 2279 10 7 14 8 39 0 1130 3 2 10 9 0 0 531 0 0 1 10 183 0 2053 10 7 14 11 189 0 2181 10 7 14 12 190 0 2231 10 7 14 13 189 0 2141 10 7 14 14 153 0 1850 10 7 14 15 37 0 883 3 2 10 16 0 0 370 0 0 1 17 102 0 1755 10 7 14 18 184 0 1976 10 7 14 19 154 0 2093 10 7 14 20 184 0 2137 10 7 14 21 155 0 2127 10 7 14 22 35 0 877 3 2 10 23 0 0 691 0 0 2 24 123 0 2025 10 7 14 25 207 0 1937 10 7 14 26 187 0 2068 10 7 14 27 181 0 2117 10 7 14 28 209 0 2132 10 7 14 29 42 0 1143 3 2 10 30 0 0 655 0 0 2 31 198 0 2422 10 7 15 Total 3867 0 51874 233 156 359 Energy Simulation for Commercial Buildings Page ‐ 62 - [ENERGY SIMULATION] 2015 June 22 Daily Air System Simulation Results for August (Table 2): Electric Lighting Equipment Day (kWh) (kWh) 1 23 16 2 20 16 3 120 35 4 120 35 5 120 35 6 120 35 7 120 35 8 23 16 9 20 16 10 120 35 11 120 35 12 120 35 13 120 35 14 120 35 15 23 16 16 20 16 17 120 35 18 120 35 19 120 35 20 120 35 21 120 35 22 23 16 23 20 16 24 120 35 25 120 35 26 120 35 27 120 35 28 120 35 29 23 16 30 20 16 31 120 35 Total 2734 908 Energy Simulation for Commercial Buildings Page ‐ 63 - [ENERGY SIMULATION] 2015 June 22 Daily Air System Simulation Results Daily Simulation Results for August Precool Coil Load (kBTU) Terminal Cooling Coil Load (kBTU) 2400 2200 2000 1800 kBTU 1600 1400 1200 1000 800 600 400 200 0 2 4 6 8 10 Energy Simulation for Commercial Buildings 12 14 16 18 Day of Month 20 22 24 26 28 Page ‐ 64 - 30 [ENERGY SIMULATION] 2015 June 22 Hourly Air System Simulation Results Precool Coil Preheat Coil Terminal Cooling Load Load Coil Load Hour (kBTU) (kBTU) (kBTU) 0000 0.0 0.0 2.0 Ventilation Fan Exhaust Fan Terminal Fan (kW) (kW) (kW) 0.0 0.0 0.0 Vent. Reclaim Device (kW 0.0 0100 0.0 0.0 2.0 0.0 0.0 0.0 0.0 0200 0.0 0.0 2.0 0.0 0.0 0.0 0.0 0300 0.0 0.0 2.0 0.0 0.0 0.0 0.0 0400 0.0 0.0 2.0 0.0 0.0 0.0 0.0 0500 0.0 0.0 2.0 0.0 0.0 0.0 0.0 0600 2.2 0.0 91.2 0.3 0.2 1.2 0.2 0700 8.9 0.0 98.2 0.9 0.6 1.2 0.2 0800 12.8 0.0 186.1 0.9 0.6 1.2 0.2 0900 14.5 0.0 197.0 0.9 0.6 1.2 0.2 1000 16.0 0.0 194.6 0.9 0.6 1.2 0.2 1100 18.9 0.0 204.7 0.9 0.6 1.2 0.2 1200 16.2 0.0 178.8 0.9 0.6 1.2 0.2 1300 18.5 0.0 209.7 0.9 0.6 1.2 0.2 1400 20.9 0.0 204.3 0.9 0.6 1.2 0.2 1500 22.3 0.0 197.3 0.9 0.6 1.2 0.2 1600 21.8 0.0 143.0 0.9 0.6 1.2 0.2 1700 13.6 0.0 115.5 0.7 0.4 1.2 0.2 1800 0.0 0.0 8.1 0.0 0.0 0.0 0.0 1900 0.0 0.0 7.4 0.0 0.0 0.0 0.0 2000 0.0 0.0 5.1 0.0 0.0 0.0 0.0 2100 0.0 0.0 4.1 0.0 0.0 0.0 0.0 2200 0.0 0.0 4.7 0.0 0.0 0.0 0.0 2300 0.0 0.0 5.8 0.0 0.0 0.0 0.0 Total 186.5 0.0 2067.6 10.4 7.0 14.3 2.4 Energy Simulation for Commercial Buildings Page ‐ 65 - [ENERGY SIMULATION] 2015 June 22 0000 Lighting (kW) 0.8 Electric Equipment (kW) 0.7 0100 0.8 0.7 0200 0.8 0.7 0300 0.8 0.7 0400 0.8 0.7 0500 0.8 0.7 0600 0.8 0.7 Hour 0700 1.6 1.8 0800 16.7 3.8 0900 16.6 3.2 1000 16.6 3.2 1100 16.6 3.2 1200 10.9 3.8 1300 10.8 2.3 1400 7.5 1.4 1500 7.6 1.2 1600 2.7 1.8 1700 1.6 1.2 1800 0.8 0.7 1900 0.8 0.7 2000 0.8 0.7 2100 0.8 0.7 2200 0.8 0.7 2300 0.8 0.7 Total 119.9 35.5 Energy Simulation for Commercial Buildings Page ‐ 66 - [ENERGY SIMULATION] Hourly Air System Simulation Results Graph Hourly Simulation Results for Tuesday, August 26 (day 238) thru Thursday, August 28 (day 240) Precool Coil Load (MBH) Terminal Cooling Coil Load (MBH) 220 200 180 160 MBH 140 120 100 80 60 40 20 0 238 239 240 Day of Year Energy Simulation for Commercial Buildings Page ‐ 67 - [ENERGY SIMULATION] 2015 June 22 Zone Temperature Report 1. Zone Temperature Statistics Occ Max Zone Temp (°F) 77.1 Occ Hours More Than 5.0 °F Above Throt. Range 0 Occ Hours 1.0 to 5.0 °F Above Throt. Range 0 Occ Cooling Setpoint plus Throt. Range (°F) 76.5 Occ Hours Within Throt. Range or Deadband 2804 Occ Heating Setpoint minus Throt. Range (°F) 68.5 D101 - Classroom 76.5 0 0 76.5 2804 68.5 0 D102 - Classroom 76.5 0 0 76.5 2804 68.5 D103 - Classroom 76.5 0 0 76.5 2804 68.5 Zone Name D100 - IT Room Occ Occ Hours Hours 1.0 to More Than 5.0 °F 5.0 °F Below Below Throt. Throt. Range Range 0 0 Occ Unocc Unocc Heating Setpoint minus Throt. Range (°F) 63.5 Unocc Max Zone Temp (°F) 80.4 Unocc Cooling Setpoint plus Throt. Range (°F) 81.5 Min Zone Temp (°F) 74.8 0 75.1 80.3 81.5 63.5 77.1 0 0 0 75.1 80.3 81.5 63.5 77.1 0 75.1 80.3 81.5 63.5 77.1 Min Zone Temp (°F) 80.3 D104 - Classroom 76.5 0 0 76.5 2804 68.5 0 0 75.0 80.4 81.5 63.5 77.1 D105 - South Vestibule 76.4 0 0 76.5 2804 68.5 0 0 75.0 80.4 81.5 63.5 75.9 D106 - Classroom 76.4 0 0 76.5 2804 68.5 0 0 75.0 80.4 81.5 63.5 76.9 D107 - Classroom 76.4 0 0 76.5 2804 68.5 0 0 75.1 80.3 81.5 63.5 77.1 D108 - Music Room 76.3 0 0 76.5 2804 68.5 0 0 75.1 80.2 81.5 63.5 77.4 D109 - Music Practice 76.6 0 0 76.5 2804 68.5 0 0 74.9 80.5 81.5 63.5 75.7 D110 - Music Files 76.5 0 0 76.5 2804 68.5 0 0 75.0 80.5 81.5 63.5 75.7 D111 - Music Office 76.5 0 0 76.5 2804 68.5 0 0 75.1 80.5 81.5 63.5 76.6 D112 - West Vestibule 76.4 0 0 76.5 2804 68.5 0 0 75.0 80.4 81.5 63.5 75.9 D113 - Corridor 76.4 0 0 76.5 2804 68.5 0 0 75.2 80.3 81.5 63.5 75.8 D114 - Corridor 76.4 0 0 76.5 2804 68.5 0 0 75.2 Note: For any occupied hours in which cooling is unavailable or scheduled off, zone temperature out of range statistics are not reported. Note: For any occupied hours in which heating is unavailable or scheduled off, zone temperature out of range statistics are not reported. 80.3 81.5 63.5 75.8 Energy Simulation for Commercial Buildings Page ‐ 68 - [ENERGY SIMULATION] 2015 June 22 Section 3 Energy Simulation for Commercial Buildings Page 69 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page 70 2015 June 22 [ENERGY SIMULATION] Section 3_Workshop 4 - Modeling Chillers, Towers, Boilers and Hydronic Plants This workshop consists of entering cooling and heating plant information including detailed performance on chillers, towers, boilers and the distribution piping and pumping. There are several ways to enter the data into HAP. One option is using the Equipment Wizard found in HAP. Utilizing this wizard creates not only the Air Systems but also the hydronic plants that connect to the air systems. When we used the Equipment Wizard to create the 4Pipe FCU air system in workshop 3 the wizard automatically created the Chiller and Boiler plants for the air system’s source of cooling and heating. Refer to Figures 3.3b and c for additional details. The wizard created plants use the “auto-size” feature when creating the chillers and boilers. We now create specific chillers, towers and boilers for our design alternatives. The first step in this workshop is retrieving the second class archive which contains all air systems for our design alternatives. Retrieve Energy Simulation Archive 2 Unsolved 1. While in the existing project, go to the menu bar; select “Project \ Retrieve HAP v 4.9 Data.” 2. Navigate to folder 02 copied to the desktop and select Energy Simulation Unsolved Archives. 3. From this Folder - retrieve the archive “Singapore_HAP49_EnergySim Archive 2_Unsolved.E3A.” Allow this retrieval to “overwrite” the data created thus far in our workshops. Be sure to click “Project, Save” to update your project files after retrieving this archive. The project now contains all required air systems for the remaining workshops. Refer to Figure 4.1 for details. Figure 4.1 - Retrieve HAPv4.9 Energy Simulation Archive 2 Unsolved Highlight and retrieve Energy Simulation Archive 2 Unsolved into the existing project and then save the project. In the previous workshop #3, we used the Equipment Wizard to create our air systems, chiller plant and boiler plant for our 2 pipe fan coil air system with a DOAS for wing D of our building. In Energy Simulation for Commercial Buildings Page 71 2015 June 22 [ENERGY SIMULATION] this workshop we create several chillers, a cooling tower and several SWH boilers for our building air systems because the wizard created plants are sized only for the previously created 2-pipe fan coil system for wing D. HAP considers all the air systems assigned to the plant in determining the peak coincident, or "block" load, taking into account diversity on several levels. Diversity is defined as the block load divided by the sum of the individual peak loads. HAP considers diversity between the zones within an air system and between systems when a plant serves multiple air systems. The plant design load calculation analyses the total plant load (sum of air system loads) for each hour and finds the largest load. This analysis includes the zone and air system diversity. When using air system multipliers for identical air systems, the resulting plant sizing includes those requirements in determining the peak plant load. HAP calculates the total building, project or campus block load accounting for diversity in sizing the plant and plant equipment. We begin the process by determining the chiller and boiler plant sizing for the “A Base Case” and “C Alt #2” design case. In the HAP main window, click on the Plant item in the tree and select “create new plant” in the detail pane. Refer to Figure 4.2 for details. Figure 4.2 - Create New Chiller Plant This opens the Plant Input form for data entry. Please refer to Figure 4.3 for A Base Case Chilled Water Plant sizing procedure. Figure 4.3 - Generic Chiller Plant Sizing Details Next click on the “Systems” tab and add the A Base Case air systems to the chilled water plant and left click on the OK button. Refer to Figure 4.4 for details. Energy Simulation for Commercial Buildings Page 72 2015 June 22 [ENERGY SIMULATION] Figure 4.4 - Add “A Base Case” Air Systems to the Generic Chilled Water Plant This takes us back to the HAP plant screen showing the newly created plant on the list. Highlight the plant and use the right mouse click then select “print/view design results” from the selection list. Refer to Figures 4.5 and 4.6 for additional details. Figure 4.5 - Calculate Chiller Plant Design Load Energy Simulation for Commercial Buildings Page 73 [ENERGY SIMULATION] 2015 June 22 Figure 4.6 - Select Print/View Design Results – Cooling Plant Sizing Summary Review the follow details for the plant sizing. Figure 4.7 - Chiller Plant Sizing Summary Report 1. Plant Information: Plant Name ................................. A Base Case A/C CW Plant Sizing Plant Type ........................................................ Generic Chilled Water Design Weather ............................................... Singapore, Singapore 2. Cooling Plant Sizing Data: Maximum Plant Load .....................................................................283.3 Tons Load occurs at ...................................................................... Aug 1500 ft²/Ton ............................................................................................ 210.2 ft²/Ton Floor area served by plant ........................................................ 59553.0 ft² 3. Coincident Air System Cooling Loads for Aug 1500 Air System Name A01 - AHU A1 - Commons/Offices A02 - AHU A2 - Classroom/Misc. A03 - AHU B1 - Classrooms A04 - Project 1 Gymnasium A05 - AHU C2 - Aerobics Gym A06 - AHU C3 - Locker Rooms A07 - AHU C4 - Office/Classroom A09 - Project 2 - Wing D PFPMXB A10 - AHU D2 - Classrooms Mult. 1 1 1 1 1 1 1 1 1 System Cooling Coil Load ( Tons ) 47.5 43.7 50.6 49.0 13.2 26.2 12.6 20.0 20.6 System loads are for coils whose cooling source is ' Chilled Water ' or ' Any '. Figure 4.7 details the chiller plant sizing summary for the A Base Design Case air systems. The resulting peak plant load for the “A Base Case” is 283.3 tons (996.37kW). This peak load includes diversity as previously discussed. For our “A Base Case” design we use two (2) air-cooled chillers in our chiller plant. Energy Simulation for Commercial Buildings Page 74 [ENERGY SIMULATION] 2015 June 22 With the maximum plant load determined, we can select specific chillers for the chiller plant. This is accomplished in one of several ways. For our exercise we selected the chiller in the e-Cat Chiller Builder program. After finalizing the selection, we exported the chiller data for use in our project. This allows us to import the actual chiller performance for a detailed energy analysis of the chiller plant. Copies of the chiller data files are on the accompanying flash drive. Air Cooled Chiller Selection Design based on the following parameters. Quantity: 2 Air-Cooled Packaged Scroll Chillers Capacity: 150 Nominal Tons at 95º F (527.55kW @35⁰C) LCHWT: 44º F (7⁰C) ECHWT: 56º F (12⁰C) Figure 4.8 - Details of Chiller Selection using e-Cat Selection Software. Run the calculations and generate the Chiller Performance Report. See following page for details. Energy Simulation for Commercial Buildings Page 75 [ENERGY SIMULATION] 2015 June 22 30RB with Greenspeed Technology TM Unit Information Tag Name:........... A Base Case CH-1 and 2 Model Number: ......................... 30RB0522B Quantity: ..................................................... 1 Manufacturing Source: ..... Shanghai, China Refrigerant:........................................ R410A Shipping Weight: .................................. 3296 Operating Weight: ................................ 3348 Unit Length: .......................................... 4798 Unit Width: ............................................ 2253 Unit Height:........................................... 2297 Evaporator Information Fluid Type:............................... Fresh Water Fouling Factor: .................................. 0.0180 Leaving Temperature: ............................. 7.0 Entering Temperature:........................... 12.0 Fluid Flow: ........................................... 25.57 Pressure Drop: ...................................... 91.6 kg kg mm mm mm Performance Information Cooling Capacity: ....................................... 536.5 Total Compressor Power: ........................... 165.7 Total Fan Motor Power: ................................ 13.0 Pump Power: ................................................ 9.53 Total Unit Power (without pump): ............... 178.7 Total Unit Power (with pump): .................... 188.2 Efficiency (without pump): ............................ 3.00 A-Weighted Sound Power Level: ..................... 94 A-Weighted Sound Pressure Level:................. 74 kW kW kW kW kW kW COP dbA dbA Accessories and Installed Options Opt. 254 Cu / Al Coil (sqm-K)/kW °C °C L/s kPa Condenser Information Altitude: ...................................................... 0 m Number of Fans: ......................................... 8 Total Condenser Fan Air Flow at 20°C:36107 L/s Entering Air Temperature: ..................... 35.0 °C Integrated Pump Information Static Head at Pump:.................................. 275.1 kPa Static Head External to Chiller: ................... 183.5 kPa Electrical Information Unit Voltage: .......................................... 380-3-50 Standby Power: ............................................ 10.4 Minimum Voltage: .......................................... 342 Maximum Voltage: ......................................... 418 Power Factor: ............................................... 0.85 Amps (Un) Max Unit Current Draw (RLA) Max Start Up Current (ICF) Nominal Unit Current Draw (A) V-Ph-Hz kW Volts Volts Electrical Circuit 1 415.0 Electrical Circuit 2 --- 629.0 --- 327.0 --- All performance efficiency data are without pump. Sound pressure level measured in accordance with JBT4330. Sound pressure level is the data when the unit is placed in a free field over a reflecting plane. Energy Simulation for Commercial Buildings Page 76 [ENERGY SIMULATION] Entering Chiller Performance Data There are three (3) ways to enter chiller data into HAP. 1. Import Chiller 2. Chiller Template 3. User Defined Chiller Type In this Workshop, we enter chiller data using method 1 and method 2. For our Air Cooled Packaged Scroll Chillers we selected using the Packaged Chiller Builder program, we exported the detailed chiller performance for use by HAP in simulating the hour-byhour operation of the chiller plant. To import the actual performance matrix of our chiller for use in our plant model we use the “Import Chiller” utility in the chiller properties input form. Refer to Figure 4.9a through Figure 4.9d for details. We placed a Chiller Export Archive file on the accompanying Flash Drive. To Import this chiller for this exercise open the chiller properties form and Double Click on the “New Default Chiller” in the chiller Library, then click on the Import Chiller button as detailed in Figure 4.9a. Figure 4.9a - Chiller Input Form – Import Chiller Data Navigate to your desktop where we copied folder 02. Unsolved Workshop Archives and select the “A Base Case CH-1 and 2.cd5.” Click the OPEN button to import the chiller into HAP. Energy Simulation for Commercial Buildings Page ‐ 77 - 2015 June 22 [ENERGY SIMULATION] Figure 4.9b – Chiller Properties General Tab – Imported Chiller Data Note: The Chiller properties are imported from the archived file and include all selection design inputs and calculated performances for IPLV and NPLV using the full operating matrix of the chiller. We can rename the default Chiller1 name to something that makes more sense i.e. “A Base Case AC Chillers” or similar. Energy Simulation for Commercial Buildings Page ‐ 78 - 2015 June 22 [ENERGY SIMULATION] Figure 4.9c - Chiller Properties Design Inputs – Imported Chiller Data Note: All data is part of the import file. Energy Simulation for Commercial Buildings Page ‐ 79 - 2015 June 22 [ENERGY SIMULATION] Figure 4.9d – Chiller Properties Performance Map – Imported Chiller Data Using the Equipment Wizard in creating our C8 2-Pipe Fan Coil Unit air system in Workshop 3 also created a chiller and tower for this design alternative. Looking at the Chiller library we see only one chiller on the list, the one from the wizard was deleted from the previous archive. When using the Wizard in creating chillers the default sizing is “Auto-Sized” meaning the chiller capacity defaults to the required capacity for the assigned air system coil loads. In order to perform an accurate comparison of actual chiller performance we need to user define the performance of this water-cooled screw chiller. We enter the chiller performance into HAP using the “Chiller Template” utility in HAP. Use the following information for modeling the water-cooled screw chiller for the C Alt 2 design. Now calculate the design load for the “C” Alt-2 chiller plant. Note: The calculated load for C Alt 2 is 225.0 tons [791.3 kW]. The chiller capacity and part load performance used in the template input are detailed in Figures 4.10 through 4.11e, and resulted from a preliminary selection from the e-Cat software and includes extra capacity. Energy Simulation for Commercial Buildings Page ‐ 80 - [ENERGY SIMULATION] 2015 June 22 Integrated Part Load Value (AHRI) IPLV:......................................................27.05 EER Unit Performance Percent Full Load Cooling Capacity, % Percent of Full Load Power, % Unloading Sequence Cooling Capacity, Tons Total Unit Power, kW Efficiency, EER Evaporator Data Fluid Entering Temperature, °F Fluid Leaving Temperature, °F Fluid Flow Rate, gpm Fouling Factor, (hr-sqft-F)/BTU Condenser Data Fluid Entering Temperature, °F Fluid Leaving Temperature, °F Fluid Flow Rate, gpm Fouling Factor, (hr-sqft-F)/BTU Figure 4.10 – Integrated Part Load Value 100 100.0 Default 274.0 162.6 20.23 75 61.6 Default 205.5 100.2 24.62 50 35.0 Default 137.0 56.8 28.93 25 17.4 Default 68.5 28.2 29.11 54.0 44.0 657.7 0.0001 51.5 44.0 657.7 0.0001 49.0 44.0 657.7 0.0001 46.5 44.0 657.7 0.0001 85.0 94.4 816.3 0.00025 75.0 81.9 816.3 0.00025 65.0 69.5 816.3 0.00025 65.0 67.2 816.3 0.00025 Certified in accordance with the AHRI Water-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI Directory at www.ahridirectory.org Sound pressure level data used to develop this program was determined in accordance with AHRI Standard 575 for water chillers in a free field and ANSI/AHRI Standard 370 for air cooled chillers. Double click “New Default Chiller” and enter the IPLV data from Figure 4.10 as detailed in Figures 4.11a through 4.11e. Energy Simulation for Commercial Buildings Page ‐ 81 - 2015 June 22 [ENERGY SIMULATION] Figure 4.11a – Define Chiller Part Load Performance Figure 4.11b – Chiller Template Design Inputs Energy Simulation for Commercial Buildings Page ‐ 82 - 2015 June 22 [ENERGY SIMULATION] Figure 4.11c - Chiller Properties General Tab Template Data Figure 4.11d - Chiller Properties Design Inputs Tab Energy Simulation for Commercial Buildings Page ‐ 83 - 2015 June 22 [ENERGY SIMULATION] Figure 4.11e – Chiller Properties Performance Map Tab Note: The above inputs are IPLV rating points based on 44/56ºF LCHWT/ECHWT, with adjusted Cooler and Condenser Water flow rates. Energy Simulation for Commercial Buildings Page ‐ 84 - 2015 June 22 [ENERGY SIMULATION] Cooling Plant Sizing Summary Comparison Discussion The maximum plant load for the water-cooled design case using air systems C1-C8 is 204 tons. Note that some of these air systems are 4 pipe fan coil units. For the air-cooled design case using air systems A01-A10, the plant load was 251.7 tons. Some of these air systems are VAV. Both plants serve identical 59,553 ft² areas. What contributes to the load difference between the plants? We find the answer by comparing the Air System Design Load Summaries for the two plant types. (Not done as part of this workshop).The air-cooled chiller plant requires more ventilation air than the water-cooled chiller plant. But the primary reason for the tonnage difference is the 4 Pipe FCU system using DOAS only tempers the outside air to 72º F while the A01-10 VAV systems temper the ventilation air to 55º F requiring an additional 47.7 tons of cooling. Sum of ventilation air amounts for A01 - A10 = 32,299 cfm or 0.542 cfm/ft² Sum of ventilation air amounts for C01 - C08 = 31,590 cfm or 0.530 cfm/ft² We selected the ASHRAE 62.1-2007 Ventilation sizing for all air systems in both plants. However, each VAV air system serves multiple zones requiring the use of the VRP and multiple space equation for VAV systems in order to satisfy the critical zones requirements and comply with ASHRAE 62.1-2007. The difference in the design cases results in a 47.7 ton ventilation air load reduction. Entering Cooling Tower Performance Data Next, we need to verify the cooling tower performance for our water-cooled chiller. Before we do, there are several important terms definitions related to cooling towers including: 1. Entering Wet Bulb temperature is an important parameter in tower selection. For most areas in North America, an entering wet bulb temperature of 78°F [25.6ºC] is common. 2. Approach is the difference between the water leaving the tower and the entering wet bulb temperature of the air. A 7°F [259.3º K] approach is common in HVAC systems with a 78°F [25.6ºC] entering wet bulb and 85°F [29.4ºC] water leaving the tower. (85°F 78°F = 7°F) [29.4ºC – 25.6ºC = 259.3ºK] 3. Range is the difference in temperature of entering and leaving condenser water. An approximate 10°F [260.9º K] range is most common in HVAC applications and reflects approximately 3 gpm/ton flow rate in the condenser loop. Check with your local cooling tower representative to confirm the design entering wet bulb and approach values for your area. The tower range must match the chiller condenser ∆T. 1. Create a new cooling tower by opening the Cooling Tower Properties form. 2. Enter the cooling tower data found under the Chiller Properties Design Input Tab in Figure 4.11 D. 3. See details in Figure 4.12. Energy Simulation for Commercial Buildings Page ‐ 85 - 2015 June 22 [ENERGY SIMULATION] Figure 4.12 - Cooling Tower Properties for C Alt 2 WC Screw Chiller 1. Enter Cooling Tower Name 2. Select Cooling Tower radio button Modeling Method 3. Select gpm and enter the water flow rate matching the chiller properties 4. Enter Cooling Tower Model performance data 5. Select Fan Control type from dropdown and define fan performance 6. Click OK when finished Energy Simulation for Commercial Buildings Page ‐ 86 - 2015 June 22 [ENERGY SIMULATION] Entering Boiler Performance Data We are now ready to size our boiler plants and add boilers to our library. We start by sizing our A Base Case boiler load as detailed in the following Figures 4.13a through 4.13d. Create a new Generic Service Hot Water Plant and link all “A” designated air systems. Figure 4.13a Generic Service Hot Water Plant Figure 4.13b Link “A” Base Case Air Systems Energy Simulation for Commercial Buildings Page ‐ 87 - [ENERGY SIMULATION] 2015 June 22 Figure 4.13c –Define Service Hot Water Consumption Save plant inputs and generate plant sizing report as detailed below. A Base Case SWH Plant Plant Type Generic Service Hot Water Design Weather Singapore, Singapore Heating Plant Sizing Data: Maximum Plant Load 36.4 MBH Maximum Pasteurization Load 25.3 Load occurs at MBH Jan 0900 Estimated Pasteurization Heater Capacity Energy Simulation for Commercial Buildings 7.4 kW Page ‐ 88 - [ENERGY SIMULATION] 2015 June 22 Section 4 Energy Simulation for Commercial Buildings Page ‐ 89 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 90 - 2015 June 22 [ENERGY SIMULATION] Section 4 - Workshop 5 - Configuring Chiller Plants We created two plants in our previous workshop, a chiller plant for our A Base Case and our C Alt 2 Design, as displayed in Figure 5.1. Figure 5.1 – Chiller Plants Created in WS4. What is a Plant? A Plant is the equipment and controls that provide cooling or heating to coils in one or more air systems. Examples include chiller plants, hot water or steam boiler plants and remote source chilled water, hot water or steam plants and service water heating plants. This workshop consists of finalizing the two chiller plants created in Workshop 4. The base design case chiller plant consists of two Carrier 30RBX150 A/C (air-cooled) packaged scroll chillers. The air systems served by this plant include all “A” designated air systems with chilled water coils. The pumping and piping distribution system is a primary only with variable speed pumping and sized for a 12T [262ºK] with 2% piping heat gain factor. The “C Alt 2” chiller plant serves the “C” designated air systems. This plant consists of one 222.5 ton Carrier 30XW water-cooled packaged screw chiller and a matching cooling tower. The pumping and piping distribution system is a primary only variable speed system sized for a 12T and 2% piping heat gain factor. For this workshop we can modify the previously created generic plants by changing the plant type from “Generic” to Chiller Plant and complete the plant inputs for both plants as shown on the following pages in Figures 5.2a through 5.2e. Figure 5.2a – A Base Case Chiller Plant Data Inputs Energy Simulation for Commercial Buildings Page ‐ 91 - 2015 June 22 [ENERGY SIMULATION] Figure 5.2b – A Base Case Air Systems Figure 5.2c – Base Case Plant Configuration Energy Simulation for Commercial Buildings Page ‐ 92 - 2015 June 22 [ENERGY SIMULATION] Figure 5.2d – Schedule of Equipment Figure 5.2e – Configure Plant Distribution Energy Simulation for Commercial Buildings Page ‐ 93 - [ENERGY SIMULATION] 2015 June 22 This completes the base case plant inputs please refer to the chiller plant input reports for C Alt 2 to configure the chiller plant. Use the same procedure for editing the plant described in the base case above for the C Alt 2 plant. Refer to the following pages for the C Alt 2 plant details. C Alt 2 Chiller Plant Input Data 1. General Details: Plant Name ..................................... C Alt 2 W/C CW Plant Sizing(1) Plant Type ...................................................................... Chiller Plant 2. Air Systems served by Plant: Air System Name C01 - 4PFCU D1 - Wing A (all) C02 - 4PFCU D1 - Wing B (all) C03 - AHU C1 - Gymnasium C04 - AHU C2 - Aerobics Gym C05 - AHU C3 - Locker Rooms C06 - 4PFCU C4 - Office/Classrms C08 - 4PFCU D1 - Wing D (all) Mult. 1 1 1 1 1 1 1 3. Configuration Equipment Sizing ........................................ User-Specified Capacities Equipment Quantity ............................................................................................ 1 Controls Plant Control .......................................................... Equal Unloading LCHWT Control ..................................................... Constant LCHWT Design LCHWT ........................................................................... 44.0 °F Features Free Cooling ........................................................................ Not Used Cooling Tower Configuration .............................................. Individual 4. Schedule of Equipment Cooling Equipment Sequence CH-1 Name Full Load Capacity (Tons) Cooler Flow Rate Condenser Flow Rate C Alt 2 W/C Chiller 274.0 657.6 gpm 822.0 gpm Totals: 274.0 657.6 gpm 822.0 gpm Cooling Tower Name C Alt 2 Cooling Tower 822.0 gpm 822.0 gpm 5. Distribution Chilled Water Distribution System Type ................................................ Primary Only, Constant Speed Cooling Coil Delta-T at Design .................................................... 12.0 °F Pipe Heat Gain Factor ................................................................... 2.0 % Energy Simulation for Commercial Buildings Tower Flow Rate Page ‐ 94 - [ENERGY SIMULATION] 2015 June 22 Fluid Properties Fluid ............................................................................... Fresh Water Density ........................................................................................ 62.4 lb/ft³ Specific Heat Capacity ................................................................ 1.00 BTU / (lb - °F) Primary Loop Pump for Eqpt. CH-1 Flow Rate Head [ft wg] 657.6 gpm 70.0 Mechanical Efficiency (%) 70.0 Electrical Efficiency (%) 94.0 6. Condenser Water Configuration Pump Control .................................. Variable Flow / Variable Speed Minimum Pump Flow ...................................................................... 80 % Static Head .................................................................................. 10.0 ft wg Pumps Pump for Eqpt. CH-1 Flow Rate Head [ft wg] 822.0 gpm 50.0 Mechanical Efficiency (%) 70.0 Electrical Efficiency (%) 94.0 D Alt3 SZCV/RTU Next let’s look at how to configure a packaged roof top unit for energy simulation. Our “D” Alternative consists of 36 single zone, constant air volume packaged rooftop air source heat pump units. Open the Air System Properties form for [D31 – RTU D5 – Classroom D104] and review the following details required for an energy. Figure 5.3a – Packaged RTU-Configuration System Components –Supply Fan Energy Simulation for Commercial Buildings Page ‐ 95 - 2015 June 22 [ENERGY SIMULATION] Figure 5.3b – Equipment – Central Cooling Unit Configure the central cooling unit air cooled DX Equipment as follows: 1. The Design OAT populates to ARI Standard conditions. Enter the 95ºF [35ºC] design conditions for St. Louis IAP, Missouri. 2. Equipment capacity defaults to auto-sized, however, we recommend entering actual selected equipment manufacturer’s performance data by selecting “User-Defined Capacity from Equipment Sizing dropdown. 3. Enter Gross Cooling Capacity from manufactures performance data 4. Select AHRI Performance Rating from dropdown and enter the SEER or EER efficiency 5. Select DX Configuration from dropdown 6. Enter Conventional Cutoff OAT 7. Uncheck Low Temperature Operation checkbox 8. Click OK to save Next open the Central Heating Unit input form and enter the following information as detailed in Figure 5.3c. After entering the plant and equipment data, we can generate the Simulation Reports for each of the four plants and packaged RTU. Please refer to the following pages for the detailed simulation reports for “A” Base Case Chiller plant, Boiler plant and D31 – RTU D5 – Classroom D104 rooftop unit. Energy Simulation for Commercial Buildings Page ‐ 96 - [ENERGY SIMULATION] 2015 June 22 Section 4 Solutions Energy Simulation for Commercial Buildings Page ‐ 97 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 98 - [ENERGY SIMULATION] 2015 June 22 Section 4_Workshop 5 Solutions A Base Case Chiller Plant Simulation Results Plant Simulation Results (Table 1) : Cooling Coil Load Month (kBTU) January 809689 Plant Load (kBTU) 829803 Chiller Output (kBTU) 829803 Chiller Input (kWh) 56318 Primary Chilled Water Pump (kWh) 2295 February 778796 798312 798312 55755 2171 March 756960 776350 776292 55159 2390 April 942290 966152 966152 70485 2522 May 950708 974822 974822 69825 2587 June 274919 282978 282978 20897 1983 July 647615 663746 663746 45599 2131 August 877203 899229 899229 62641 2430 September 672298 689520 689520 48117 2233 October 918126 941218 941218 66449 2491 November 637784 654141 654141 44515 2191 December Total 1.0M 408971 419518 419518 23705 1979 8675357 8895788 8895731 619465 27403 Cooling Coil Load (kBTU) Plant Cooling Load (kBTU) Jan May Chiller Output (kBTU) 0.9M 0.8M 0.7M kBTU 0.6M 0.5M 0.4M 0.3M 0.2M 0.1M 0.0 Feb Mar Apr Energy Simulation for Commercial Buildings Jun Jul Month Aug Sep Oct Nov Dec Page ‐ 99 - [ENERGY SIMULATION] 2015 June 22 Daily Plant Simulation Results for August (Table 1) : Cooling Coil Load Plant Load Chiller Output Day (kBTU) (kBTU) (kBTU) 1 28160 28860 28860 Chiller Input (kWh) 1878 Primary Chilled Water Pump (kWh) 77 2 2860 2989 2989 230 63 3 35007 35875 35875 2387 83 4 35368 36245 36245 2514 84 5 36802 37722 37722 2739 87 6 38001 38956 38956 2867 90 7 36102 37000 37000 2648 85 8 26333 26979 26979 1756 73 9 2717 2843 2843 215 63 10 34559 35411 35411 2467 82 11 36885 37808 37808 2720 88 12 36186 37087 37087 2661 86 13 34472 35328 35328 2536 83 14 30813 31566 31566 2115 76 15 24930 25543 25543 1693 72 16 2530 2652 2652 201 63 17 29809 30533 30533 1936 74 18 34436 35285 35285 2462 81 19 33735 34571 34571 2400 82 20 36569 37484 37484 2674 87 21 35953 36844 36844 2517 84 22 24859 25467 25467 1588 71 23 3122 3256 3256 253 63 24 32591 33392 33392 2214 79 25 32360 33157 33157 2386 79 26 33968 34807 34807 2462 82 27 34097 34939 34939 2442 81 28 33922 34758 34758 2503 81 29 26336 26981 26981 1798 72 30 3003 3135 3135 249 63 31 40716 41754 41754 3131 98 Total 877203 899229 899229 62641 2430 Energy Simulation for Commercial Buildings Page ‐ 100 - [ENERGY SIMULATION] 2015 June 22 Daily Simulation Results for August Cooling Coil Load (kBTU) Plant Cooling Load (kBTU) Chiller Output (kBTU) 0.040M 0.035M 0.030M kBTU 0.025M 0.020M 0.015M 0.010M 0.005M 0.000 2 4 6 8 Energy Simulation for Commercial Buildings 10 12 14 16 18 Day of Month 20 22 24 26 28 30 Page ‐ 101 - [ENERGY SIMULATION] 2015 June 22 Table 5.1 Hourly Plant Simulation Results for Tuesday, August 26 Cooling Coil Load Plant Load Chiller Output Hour (MBH) (MBH) (MBH) 0000 92.8 97.6 97.6 Chiller Input (kW) 7.3 Primary Chilled Water Pump (kW) 2.6 0100 93.3 98.2 98.2 7.3 2.6 0200 93.7 98.6 98.6 7.3 2.6 0300 97.7 102.7 102.7 7.5 2.6 0400 96.9 101.8 101.8 7.5 2.6 0500 99.0 104.0 104.0 7.6 2.6 0600 1922.8 1967.2 1967.2 122.2 3.2 0700 1864.7 1907.6 1907.6 119.7 3.1 0800 2470.1 2529.3 2529.3 171.6 4.0 0900 2560.3 2622.2 2622.2 184.4 4.2 1000 2501.0 2561.1 2561.1 182.1 4.1 1100 2653.0 2717.5 2717.5 202.7 4.4 1200 2795.3 2864.1 2864.1 210.4 4.8 1300 2813.7 2883.0 2883.0 217.8 4.8 1400 2996.1 3071.2 3071.2 244.3 5.4 1500 2698.9 2764.8 2764.8 217.2 4.5 1600 2500.5 2560.6 2560.6 196.9 4.1 1700 2196.5 2248.1 2248.1 164.4 3.5 1800 845.0 864.9 864.9 42.4 2.6 1900 794.2 813.0 813.0 42.0 2.6 2000 805.6 824.6 824.6 41.5 2.6 2100 772.1 790.5 790.5 41.1 2.6 2200 103.6 108.7 108.7 8.3 2.6 2300 101.1 106.1 106.1 8.0 2.6 Total 33967.9 34807.4 34807.4 2461.6 81.5 Energy Simulation for Commercial Buildings Page ‐ 102 - [ENERGY SIMULATION] 2015 June 22 Table 6.1 Hourly Plant Simulation Results for Wednesday, August 27 Cooling Coil Primary Chilled Load Plant Load Chiller Output Chiller Input Water Pump Hour (MBH) (MBH) (MBH) (kW) (kW) 0000 106.4 111.5 111.5 8.4 2.6 0100 107.9 113.1 113.1 8.5 2.6 0200 114.6 119.9 119.9 9.1 2.6 0300 107.6 112.7 112.7 8.4 2.6 0400 110.2 115.4 115.4 8.6 2.6 0500 108.6 113.7 113.7 8.5 2.6 0600 1891.1 1934.7 1934.7 122.6 3.1 0700 2056.8 2104.7 2104.7 133.1 3.3 0800 2676.8 2742.0 2742.0 189.4 4.5 0900 2873.3 2944.5 2944.5 218.2 5.0 1000 2938.1 3011.4 3011.4 223.9 5.2 1100 2935.2 3008.3 3008.3 224.3 5.2 1200 2517.3 2577.8 2577.8 190.2 4.1 1300 2523.3 2584.1 2584.1 194.6 4.1 1400 2467.3 2526.5 2526.5 187.4 4.0 1500 2477.4 2536.8 2536.8 187.1 4.0 1600 2345.1 2400.8 2400.8 172.9 3.8 1700 2251.0 2304.1 2304.1 162.7 3.6 1800 832.9 852.5 852.5 42.0 2.6 1900 823.8 843.3 843.3 41.9 2.6 2000 815.6 834.9 834.9 41.5 2.6 2100 806.6 825.7 825.7 41.5 2.6 2200 108.1 113.2 113.2 8.7 2.6 2300 102.5 107.6 107.6 8.1 2.6 Total 34097.4 34939.0 34939.0 2441.7 81.4 Energy Simulation for Commercial Buildings Page ‐ 103 - [ENERGY SIMULATION] 2015 June 22 Hourly Simulation Results for Tuesday, August 26 (day 238) thru Thursday, August 28 (day 240) 1. Unmet Load Statistics Equipment Capacity is Sufficient Month (hrs) January 744 Capacity Insufficient by 0%-5% (hrs) 0 Capacity Insufficient by 5%-10% (hrs) 0 Capacity Insufficient by >10% (hrs) 0 Total Hours with Unmet Loads 0 Total Hours with Equipment Loads 744 672 0 0 0 0 672 March 743 1 0 0 1 744 April 720 0 0 0 0 720 May 744 0 0 0 0 744 June 720 0 0 0 0 720 July 744 0 0 0 0 744 August 744 0 0 0 0 744 September 720 0 0 0 0 720 October 744 0 0 0 0 744 November 720 0 0 0 0 720 December 744 0 0 0 0 744 February Total 8759 1 0 0 1 8760 Note: Data shown in this report is for diagnostic purposes only. Values represent total unmet hours for this plant. No deductions are made when unmet hours for this plant coincide with those in another plant or system in the building. Energy Simulation for Commercial Buildings Page ‐ 104 - [ENERGY SIMULATION] 2015 June 22 D Alt 3 Packaged RTU D-31 RTU D5 Classroom D104 Simulation Results Air System Simulation Results (Table 1) : Central Central Cooling Coil Cooling Eqpt Load Load Month (kBTU) (kBTU) January 12 12 Central Unit Clg Input (kWh) 1 Supply Fan (kWh) 343 Lighting (kWh) 70 Electric Equipment (kWh) 143 February 31 31 2 323 66 119 March 69 69 5 285 59 78 April 1058 1058 80 356 72 64 May 1841 1841 130 300 62 43 June 4523 4523 345 171 41 35 July 3725 3725 315 50 16 16 August 8582 8582 641 358 73 62 September 4267 4267 315 356 72 48 October 809 809 60 314 65 55 November 251 251 18 298 62 88 December Total 0 0 0 270 57 123 25168 25167 1911 3424 715 873 : Energy Simulation for Commercial Buildings Page ‐ 105 - [ENERGY SIMULATION] 2015 June 22 Daily Air System Simulation Results for August (Table 1) : Central Central Cooling Coil Cooling Eqpt Central Unit Load Load Clg Input Day (kBTU) (kBTU) (kWh) 1 285 285 21 Supply Fan (kWh) 1 Lighting (kWh) 2 Electric Equipment (kWh) 1 2 53 53 4 0 2 1 3 476 476 34 2 11 2 4 470 470 35 2 11 2 5 513 513 39 2 11 2 6 528 528 40 3 11 2 7 509 509 39 3 11 2 8 290 290 22 1 2 1 9 39 39 3 0 2 1 10 488 488 37 3 11 2 11 510 510 38 2 11 2 12 508 508 38 2 11 2 13 492 492 37 2 11 2 14 423 423 32 2 11 2 15 273 273 21 1 2 1 16 20 20 2 0 2 1 17 408 408 29 2 11 2 18 468 468 36 2 11 2 19 474 474 35 2 11 2 20 501 501 37 2 11 2 21 493 493 36 2 11 2 22 253 253 19 1 2 1 23 83 83 7 0 2 1 24 455 455 33 2 11 2 25 456 456 36 2 11 2 26 472 472 36 2 11 2 27 478 478 36 2 11 2 28 481 481 38 3 11 2 29 297 297 23 1 2 1 30 90 90 8 0 2 1 31 579 579 43 3 11 2 Total 11865 11865 897 55 257 42 Energy Simulation for Commercial Buildings Page ‐ 106 - [ENERGY SIMULATION] 2015 June 22 0000 Central Cooling Coil Load (MBH) 0.0 Central Cooling Eqpt Load (MBH) 0.0 Central Unit Clg Input (kW) 0.0 Supply Fan (kW) 0.0 Lighting (kW) 0.1 Electric Equipment (kW) 0.0 0100 0.0 0.0 0.0 0.0 0.1 0.0 0200 0.0 0.0 0.0 0.0 0.1 0.0 0300 0.0 0.0 0.0 0.0 0.1 0.0 0400 0.0 0.0 0.0 0.0 0.1 0.0 Hour 0500 0.0 0.0 0.0 0.0 0.1 0.0 0600 25.5 25.5 1.7 0.2 0.1 0.0 0700 29.2 29.2 2.0 0.2 0.2 0.0 0800 40.3 40.3 2.8 0.2 1.6 0.3 0900 43.2 43.2 3.1 0.2 1.6 0.3 1000 47.5 47.5 3.5 0.2 1.6 0.3 1100 51.0 51.0 3.9 0.3 1.6 0.3 1200 45.0 45.0 3.5 0.2 0.9 0.3 1300 55.8 55.8 4.4 0.2 1.1 0.1 1400 57.8 57.8 4.7 0.2 0.8 0.0 1500 57.8 57.8 4.7 0.2 0.8 0.0 1600 50.2 50.2 4.1 0.2 0.3 0.0 1700 44.5 44.5 3.6 0.2 0.2 0.0 1800 0.0 0.0 0.0 0.0 0.1 0.0 1900 0.0 0.0 0.0 0.0 0.1 0.0 2000 0.0 0.0 0.0 0.0 0.1 0.0 2100 0.0 0.0 0.0 0.0 0.1 0.0 2200 0.0 0.0 0.0 0.0 0.1 0.0 2300 0.0 0.0 0.0 0.0 0.1 0.0 Total 547.8 547.8 42.2 2.2 11.4 1.7 Energy Simulation for Commercial Buildings Page ‐ 107 - [ENERGY SIMULATION] 2015 June 22 1. Unmet Load Statistics - Central Cooling Unit - Air-Cooled DX Equipment Capacity Capacity Capacity is Insufficient Insufficient Sufficient by 0%-5% by 5%-10% Month (hrs) (hrs) (hrs) January 338 0 0 February Capacity Insufficient by >10% (hrs) 0 Total Hours with Unmet Loads 0 Total Hours with Equipment Loads 338 319 0 0 0 0 319 March 392 0 0 0 0 392 April 358 0 0 0 0 358 May 392 0 0 0 0 392 June 551 0 0 0 0 551 July 374 0 0 0 0 374 August 359 0 0 0 0 359 September 336 0 0 0 0 336 October 338 0 0 0 0 338 November 334 0 0 0 0 334 December 306 0 0 0 0 306 4397 0 0 0 0 4397 Total 1. Zone Temperature Statistics Occ Occ Occ Occ Occ Occ Occ Occ Unocc Unocc Unocc Heatin Hours Hours g Hours More Hours Cooling Within Setpoi Hours More Cooling Heating Than 1.0 to Setpoint Throt. nt 1.0 to Than Setpoint Setpoint Max 5.0 °F 5.0 °F plus Range minus 5.0 °F 5.0 °F Min Max plus minus Zone Above Above Throt. or Throt. Below Below Zone Zone Throt. Throt. Zone Temp Throt. Throt. Range Dead- Range Throt. Throt. Temp Temp Range Range Name (°F) Range Range (°F) band (°F) Range Range (°F) (°F) (°F) (°F) Zone 1 74.0 0 0 74.0 2804 68.0 0 0 72.6 82.4 84.0 63.0 Note: For any occupied hours in which cooling is unavailable or scheduled off, zone temperature out of range statistics are not reported. Note: For any occupied hours in which heating is unavailable or scheduled off, zone temperature out of range statistics are not reported. Energy Simulation for Commercial Buildings Occ Page ‐ 108 - Unocc Min Zone Temp (°F) 76.0 [ENERGY SIMULATION] 2015 June 22 Section 5 Inputs Energy Simulation for Commercial Buildings Page ‐ 109 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 110 - 2015 June 22 [ENERGY SIMULATION] Section 5_Workshop 6 Defining and Simulating Buildings Defining Buildings in HAP The first step in this workshop is to retrieve Singapore_HAP49_EnergySim Archive 3_Unsolved into the project. However, before actually working with this archive, let us discuss how HAP uses the term “building”. A building in HAP is the “container” for all HVAC and non-HVAC systems for one design scenario. Performing an energy analysis calculates annual energy costs for the building’s energy consuming systems. System design load analysis in HAP, requires us to create elements, spaces, zones, air systems, and plants like in the previous workshops, while a "building" is only required for performing an energy simulation. Taken literally, a building represents one structure. However, in HAP the definition of a building is flexible. It can also represent a group of structures. For example, a "building" could represent a campus in which all the structures are served by central steam and chilled water plant equipment. Keep in mind, a design case can contain part of an actual building, a complete building, or many buildings. When using the Equipment Wizard HAP not only creates the Air Systems and Plants but also a Building. The Wizard created Building includes the plants, air systems, spaces and all items linked to the spaces like schedules, construction items etc. One exercise included in this workshop is defining the Energy Charges by creating an Electric Rate. There are several ways to create these energy rates including the Utility Rate Wizard, importing previously created rates, use the state EIA average rates or user defining the rates. For our workshop we create a complex electric rate that includes seasonal scheduling, time-ofday utility rate schedules and a demand clause. Create the Natural Gas utility rate as a simple rate structure. Use the following values for creating the electric and fuel utility rates. HTS Supplies General Details Rate Name ............................................ HTS Supplies Rate Type ..................................................... Complex Energy Units ......................................................... kWh Conversion ...................................................... 1.00000 Demand Units ......................................................... kW Customer Charge .................................................. 0.00 Minimum Charge ................................................... 0.00 Tax Rate ............................................................... 0.00 kWh/kWh $ $ % Time-Of-Day Scheduling TOD Schedule Name ............................ HTS Supplies Emissions Analysis CO2e Factor ......................................................... 1.58 lb/kWh Energy Charges Type of Energy Charge ................................. Standard Step Type Season Period Block Size Energy All Seasons Peak 9999999 Energy All Seasons Off-Peak 9999999 Energy Simulation for Commercial Buildings Block Units kWh kWh $/kWh 0.23670 0.14400 Page ‐ 111 - [ENERGY SIMULATION] 2015 June 22 Demand Charges Season All Seasons All Seasons Period Peak Off-Peak Block Size 9999999 9999999 Block Units kW kW $/kW 7.49000 7.49000 Demand Clauses No data specified. This Concludes the Utility Rate Input Energy Simulation for Commercial Buildings Page ‐ 112 - [ENERGY SIMULATION] 2015 June 22 Our next exercise in this workshop consists of creating the “Buildings” for this project. As discussed in a previous paragraph, each “Building” represents a design alternative for comparison of energy consumption etc. Our project includes the following four (4) designs: I. Building Name: A Base VAV-PFPMXB- ASHRAE 62.1-2007 Cooling Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing: (2) 30RBA150 Air-Cooled Scroll Chiller A01-A10 VAV PFPMXB, SZCV Constant ASHRAE 62.1-2007 II. Building Name: Cooling Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing: B Alt1 VAV-PFPMXB- ASHRAE 62.1-2007_DCV (2) 30RBA150 Air-Cooled Scroll Chiller B01-B10 VAV PFPMXB, SZCV Demand Controlled Ventilation ASHRAE 62.1-2007 III. Building Name: Cooling Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing: C Alt2-4PFCU-ASHRAE 62.1-2007_DOAS (1) 30 XW09002P Water-Cooled Screw Chiller C1-C8 2- Pipe Fan Coil Units, SZCV Constant (dedicated outdoor air system for 2PFCU) ASHRAE 62.1-2007 IV. Building Name: Cooling Plant: Air Systems: Air System Types: Ventilation Control: Ventilation Sizing: D Alt3 SZCV/RTU_ASHRAE 62.1-2007 None (Integral to RTU- Air Cooled DX) D01-D36 SZCV RTU Constant ASHRAE 62.1-2007 Notice the “B Alt-1” scenario is a duplicate of the “A” Base Case except the associated air systems use demand control ventilation to simulate ventilation loads. Using DCV is an energy saving strategy that reduces ventilation air requirements resulting from diverse building occupancy. The “C Alt-2” design scenario uses a water cooled screw chiller to supply chilled water to 2-pipe fan coil units and single zone air handlers. The fan coil systems utilize a common (dedicated) ventilation air system resulting in a lower peak total ventilation airflow compared to the A and B scenarios. The “D-Alt 3” scenario uses multiple packaged single zone constant volume RTU units. The rooftop units are self-contained DX cooling with air source heat pump heating and are not connected to a chilled water or hot water plant. In order to save time, the schedules and profiles applicable to the miscellaneous energy items are completed as part of archive # 3. Energy Simulation for Commercial Buildings Page ‐ 113 - 2015 June 22 [ENERGY SIMULATION] Figure 6.2 – Enter Building Data Figure 6.3 – Assign Air Systems to Building Design Energy Simulation for Commercial Buildings Page ‐ 114 - 2015 June 22 [ENERGY SIMULATION] Enter the following Miscellaneous Energy Users under the Misc. Energy Tab. Refer to Figure 6.4 for additional details. Note: the fractional schedules came as part of the archive, there is no need to create the fractional schedules for this exercise Name Energy Type Exterior Lighting Electric Kitchen Booster Heater Electric Aerobic Pool Heater Electric Aerobic Pool Circ. Pumps Electric Peak Use 20.5 kW 125 kW 175 kW 2.5 kW Schedule Parking Lot Lights People-Classroom Aerobic Pool Heater Aerobic Pool Heater Figure 6.4 – Misc. Energy Tab Input Details Energy Simulation for Commercial Buildings Page ‐ 115 - 2015 June 22 [ENERGY SIMULATION] Figure 6.5 – Building Meters Tab Highlight the “A Base Case Building” after saving it and then right mouse click and choose Duplicate. Rename the duplicate B Alt 1 VAV FPMXB DCV. Deselect the A Base Case plants and assign the B Alt 1 plants to the B Alt 1 Building under the Plants Tab. Refer to Figure 6.6 for details. Figure 6.6 – B Alt 1 Building Properties - Plants Figure 6.7 – B Alt 1 Building Properties – Systems These are the only required changes for the B Alt 1 Building design. Repeat the process for the C Alt 2 design and D Alt 3 Design. After saving these additional buildings, highlight all four design case buildings and perform the energy simulation. Energy Simulation for Commercial Buildings Page ‐ 116 - [ENERGY SIMULATION] 2015 June 22 Section 5 Solutions Energy Simulation for Commercial Buildings Page ‐ 117 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 118 - [ENERGY SIMULATION] 2015 June 22 Simulation Results Table 1. Annual Costs A Base VAVPFPMXBASHRAE 62.12007 (SGD) 60,636 B Alt 1 VAVPFPMXBASHRAE 62.12007 DCV (SGD) 60,195 Cooling 170,532 127,130 80,874 167,812 Heating 8,122 14,998 5,214 5,351 Pumps 7,705 7,457 39,826 310 0 0 19,662 0 246,996 209,780 184,888 235,797 45,052 44,799 44,143 45,328 Component Air System Fans Heat Rejection Fans HVAC Sub-Total Lights Electric Equipment Misc. Electric C Alt 2 2P FCU w/DOAS D Alt 3 PKG RTU ASHRAE62.1ASHRAE62.12007 2007 (SGD) (SGD) 39,312 62,323 20,114 19,993 19,709 20,251 182,934 181,756 179,306 184,244 Misc. Fuel Use 0 0 0 0 Non-HVAC Sub-Total 248,099 246,549 243,158 249,822 Grand Total 495,095 456,329 428,046 485,619 Table 2. Annual Cost per Unit Floor Area A Base VAVPFPMXBASHRAE 62.12007 Component (SGD/ft²) Air System Fans 0.878 B Alt 1 VAVPFPMXBASHRAE 62.12007 DCV (SGD/ft²) 0.872 C Alt 2 2P FCU w/DOAS ASHRAE62.12007 (SGD/ft²) 0.569 D Alt 3 PKG RTU ASHRAE62.12007 (SGD/ft²) 0.903 Cooling 2.469 1.841 1.171 2.430 Heating 0.118 0.217 0.076 0.078 Pumps 0.112 0.108 0.577 0.005 Heat Rejection Fans 0.000 0.000 0.285 0.000 3.577 3.038 2.677 3.415 Lights HVAC Sub-Total 0.652 0.649 0.639 0.656 Electric Equipment 0.291 0.290 0.285 0.293 Misc. Electric 2.649 2.632 2.597 2.668 Misc. Fuel Use 0.000 0.000 0.000 0.000 3.593 3.570 3.521 3.618 Non-HVAC Sub-Total Grand Total 7.169 6.608 6.198 7.032 69057.0 69057.0 69057.0 69057.0 Conditioned Floor Area (ft²) 69057.0 69057.0 Note: Values in this table are calculated using the Gross Floor Area. 69057.0 69057.0 Gross Floor Area (ft²) Energy Simulation for Commercial Buildings Page ‐ 119 - [ENERGY SIMULATION] 2015 June 22 Table 3. Component Cost as a Percentage of Total Cost A Base VAVB Alt 1 VAVPFPMXBPFPMXBASHRAE 62.1ASHRAE 62.12007 2007 DCV Component (%) (%) Air System Fans 12.2 13.2 Cooling 34.4 C Alt 2 2P FCU w/DOAS ASHRAE62.12007 (%) 9.2 D Alt 3 PKG RTU ASHRAE62.12007 (%) 12.8 27.9 18.9 34.6 Heating 1.6 3.3 1.2 1.1 Pumps 1.6 1.6 9.3 0.1 Heat Rejection Fans HVAC Sub-Total 0.0 0.0 4.6 0.0 49.9 46.0 43.2 48.6 Lights 9.1 9.8 10.3 9.3 Electric Equipment 4.1 4.4 4.6 4.2 36.9 39.8 41.9 37.9 0.0 0.0 0.0 0.0 Misc. Electric Misc. Fuel Use Non-HVAC Sub-Total 50.1 54.0 56.8 51.4 Grand Total 100.0 100.0 100.0 100.0 A Base VAVPFPMXBASHRAE 62.12007 (SGD) B Alt 1 VAVPFPMXBASHRAE 62.12007 DCV (SGD) C Alt 2 2P FCU w/DOAS ASHRAE62.12007 (SGD) D Alt 3 PKG RTU ASHRAE62.12007 (SGD) Annual Emissions Summary Table 1. Annual Costs Component HVAC Components Electric 246,991 209,776 184,886 235,807 Natural Gas 0 0 0 0 Fuel Oil 0 0 0 0 Propane 0 0 0 0 Remote HW 0 0 0 0 Remote Steam 0 0 0 0 Remote CW 0 0 0 0 246,991 209,776 184,886 235,807 248,105 246,554 243,157 249,817 Natural Gas 0 0 0 0 Fuel Oil 0 0 0 0 HVAC Sub-Total Non-HVAC Components Electric Propane 0 0 0 0 Remote HW 0 0 0 0 Remote Steam 0 0 0 0 Non-HVAC Sub-Total 248,105 246,554 243,157 249,817 Grand Total 495,095 456,331 428,042 485,625 Energy Simulation for Commercial Buildings Page ‐ 120 - [ENERGY SIMULATION] 2015 June 22 Table 2. Annual Energy Consumption A Base VAVPFPMXBASHRAE 62.1Component 2007 B Alt 1 VAVPFPMXBASHRAE 62.12007 DCV C Alt 2 2P FCU w/DOAS ASHRAE62.12007 D Alt 3 PKG RTU ASHRAE62.12007 902,991 771,644 689,880 857,339 Natural Gas (na) 0 0 0 0 Fuel Oil (na) 0 0 0 0 HVAC Components Electric (kWh) Propane (na) 0 0 0 0 Remote HW (na) 0 0 0 0 Remote Steam (na) 0 0 0 0 Remote CW (na) 0 0 0 0 Non-HVAC Components Electric (kWh) 908,085 908,085 908,056 908,046 Natural Gas (na) 0 0 0 0 Fuel Oil (na) 0 0 0 0 Propane (na) 0 0 0 0 Remote HW (na) 0 0 0 0 Remote Steam (na) 0 0 0 0 Totals Electric (kWh) 1,811,076 1,679,729 1,597,937 1,765,384 Natural Gas (na) 0 0 0 0 Fuel Oil (na) 0 0 0 0 Propane (na) 0 0 0 0 Remote HW (na) 0 0 0 0 Remote Steam (na) 0 0 0 0 Remote CW (na) 0 0 0 0 A Base VAVPFPMXBASHRAE 62.12007 2,852,450 B Alt 1 VAVPFPMXBASHRAE 62.12007 DCV 2,645,571 C Alt 2 2P FCU w/DOAS ASHRAE62.12007 2,516,779 D Alt 3 PKG RTU ASHRAE62.12007 2,780,463 Table 3. Annual Emissions Component CO2 Equivalent (lb) Energy Simulation for Commercial Buildings Page ‐ 121 - [ENERGY SIMULATION] 2015 June 22 Table 4. Annual Cost per Unit Floor Area A Base VAVPFPMXBASHRAE 62.12007 Component (SGD/ft²) HVAC Components Electric 3.577 B Alt 1 VAVPFPMXBASHRAE 62.12007 DCV (SGD/ft²) C Alt 2 2P FCU w/DOAS ASHRAE62.12007 (SGD/ft²) D Alt 3 PKG RTU ASHRAE62.12007 (SGD/ft²) 3.038 2.677 3.415 Natural Gas 0.000 0.000 0.000 0.000 Fuel Oil 0.000 0.000 0.000 0.000 Propane 0.000 0.000 0.000 0.000 Remote HW 0.000 0.000 0.000 0.000 Remote Steam 0.000 0.000 0.000 0.000 Remote CW 0.000 0.000 0.000 0.000 3.577 3.038 2.677 3.415 Non-HVAC Components Electric 3.593 3.570 3.521 3.618 Natural Gas 0.000 0.000 0.000 0.000 Fuel Oil 0.000 0.000 0.000 0.000 Propane 0.000 0.000 0.000 0.000 HVAC Sub-Total Remote HW 0.000 0.000 0.000 0.000 Remote Steam 0.000 0.000 0.000 0.000 Non-HVAC Sub-Total 3.593 3.570 3.521 3.618 Grand Total 7.169 6.608 6.198 7.032 69057.0 69057.0 69057.0 69057.0 Conditioned Floor Area (ft²) 69057.0 69057.0 Note: Values in this table are calculated using the Gross Floor Area. 69057.0 69057.0 Gross Floor Area (ft²) Energy Simulation for Commercial Buildings Page ‐ 122 - [ENERGY SIMULATION] 2015 June 22 Table 5. Component Cost as a Percentage of Total Cost A Base VAVB Alt 1 VAVPFPMXBPFPMXBASHRAE 62.1ASHRAE 62.12007 2007 DCV Component (%) (%) HVAC Components Electric 49.9 46.0 C Alt 2 2P FCU w/DOAS ASHRAE62.12007 (%) D Alt 3 PKG RTU ASHRAE62.12007 (%) 43.2 48.6 Natural Gas 0.0 0.0 0.0 0.0 Fuel Oil 0.0 0.0 0.0 0.0 Propane 0.0 0.0 0.0 0.0 Remote HW 0.0 0.0 0.0 0.0 Remote Steam 0.0 0.0 0.0 0.0 Remote CW 0.0 0.0 0.0 0.0 49.9 46.0 43.2 48.6 HVAC Sub-Total Non-HVAC Components Electric 50.1 54.0 56.8 51.4 Natural Gas 0.0 0.0 0.0 0.0 Fuel Oil 0.0 0.0 0.0 0.0 Propane 0.0 0.0 0.0 0.0 Remote HW 0.0 0.0 0.0 0.0 Remote Steam 0.0 0.0 0.0 0.0 Non-HVAC Sub-Total 50.1 54.0 56.8 51.4 Grand Total 100.0 100.0 100.0 100.0 Energy Simulation for Commercial Buildings Page ‐ 123 - [ENERGY SIMULATION] 2015 June 22 Annual Component Cost for C Alt 2 Air System Fans 9.2% 41.9% Misc. Electric Cooling 18.9% Heating 1.2% Pumps 9.3% Heat Rejection Fans 4.6% 4.6% Electric Equipment Lights 10.3% 1. Annual Costs Annual Cost (SGD) 39,312 (SGD/ft²) 0.569 Percent of Total (%) 9.2 Cooling 80,874 1.171 18.9 Heating 5,214 0.076 1.2 Component Air System Fans Pumps 39,826 0.577 9.3 Heat Rejection Fans 19,662 0.285 4.6 HVAC Sub-Total Lights Electric Equipment 184,888 2.677 43.2 44,143 0.639 10.3 19,709 0.285 4.6 179,306 2.597 41.9 0 0.000 0.0 243,158 3.521 56.8 Grand Total 428,046 6.198 Note: Cost per unit floor area is based on the gross building floor area. 100.0 Misc. Electric Misc. Fuel Use Non-HVAC Sub-Total Gross Floor Area ....................................................... 69057.0 ft² Conditioned Floor Area ............................................. 69057.0 ft² Energy Simulation for Commercial Buildings Page ‐ 124 - [ENERGY SIMULATION] 2015 June 22 Annual Energy Cost HVAC Electric 43.2% 56.8% Non-HVAC Electric 1. Annual Costs Component HVAC Components Electric Annual Cost (SGD/yr) (SGD/ft²) Percent of Total (%) 184,886 2.677 43.2 Natural Gas 0 0.000 0.0 Fuel Oil 0 0.000 0.0 Propane 0 0.000 0.0 Remote Hot Water 0 0.000 0.0 Remote Steam 0 0.000 0.0 Remote Chilled Water 0 0.000 0.0 184,886 2.677 43.2 56.8 HVAC Sub-Total Non-HVAC Components Electric 243,157 3.521 Natural Gas 0 0.000 0.0 Fuel Oil 0 0.000 0.0 Propane 0 0.000 0.0 Remote Hot Water 0 0.000 0.0 Remote Steam 0 0.000 0.0 Non-HVAC Sub-Total 243,157 3.521 56.8 Grand Total 428,042 6.198 100.0 Note: Cost per unit floor area is based on the gross building floor area. Gross Floor Area ........................................ 69057.0 ft² Conditioned Floor Area .............................. 69057.0 ft² Energy Simulation for Commercial Buildings Page ‐ 125 - [ENERGY SIMULATION] 2015 June 22 Annual Cost HVAC and Non-HVAC HVAC 43.2% 56.8% Non-HVAC 1. Annual Costs Annual Cost (SGD/yr) 184,888 (SGD/ft²) 2.677 243,158 3.521 56.8 Grand Total 428,046 6.198 Note: Cost per unit floor area is based on the gross building floor area. 100.0 Component HVAC Non-HVAC Percent of Total (%) 43.2 Gross Floor Area ....................................................... 69057.0 ft² Conditioned Floor Area ............................................. 69057.0 ft² Energy Simulation for Commercial Buildings Page ‐ 126 - [ENERGY SIMULATION] 2015 June 22 Energy Budget by System Component 1. Annual Coil Loads Component Cooling Coil Loads Load (kBTU) 6,222,422 (kBTU/ft²) 90.106 Heating Coil Loads 0 0.000 6,222,422 90.106 2. Energy Consumption by System Component Site Energy Component (kBTU) Air System Fans 501,117 Site Energy (kBTU/ft²) 7.257 Source Energy (kBTU) 1,789,704 Source Energy (kBTU/ft²) 25.916 Grand Total Cooling 1,029,636 14.910 3,677,270 53.250 Heating 66,415 0.962 237,197 3.435 Pumps 506,246 7.331 1,808,023 26.182 Cooling Towers 250,487 3.627 894,595 12.954 2,353,901 34.086 8,406,788 121.737 562,249 8.142 2,008,033 29.078 HVAC Sub-Total Lights Electric Equipment Misc. Electric 250,835 3.632 895,839 12.973 2,285,228 33.092 8,161,527 118.185 Misc. Fuel Use 0 0.000 0 0.000 Non-HVAC Sub-Total 3,098,311 44.866 11,065,398 160.236 Grand Total 5,452,212 78.952 19,472,186 281.973 Notes: 1. 'Cooling Coil Loads' is the sum of all air system cooling coil loads. 2. 'Heating Coil Loads' is the sum of all air system heating coil loads. 3. Site Energy is the actual energy consumed. 4. Source Energy is the site energy divided by the electric generating efficiency (28.0%). 5. Source Energy for fuels equals the site energy value. 6. Energy per unit floor area is based on the gross building floor area. Gross Floor Area ............................................ 69057.0 ft² Conditioned Floor Area .................................. 69057.0 ft² Energy Simulation for Commercial Buildings Page ‐ 127 - [ENERGY SIMULATION] 2015 June 22 Energy Budget by Energy Source 1. Annual Coil Loads Component Cooling Coil Loads Load (kBTU) 6,222,422 (kBTU/ft²) 90.106 Heating Coil Loads 0 0.000 6,222,422 90.106 2. Energy Consumption by Energy Source Site Energy Component (kBTU) Site Energy (kBTU/ft²) Source Energy (kBTU) Source Energy (kBTU/ft²) Grand Total HVAC Components Electric 2,353,870 34.086 8,406,680 121.735 Natural Gas 0 0.000 0 0.000 Fuel Oil 0 0.000 0 0.000 Propane 0 0.000 0 0.000 Remote Hot Water 0 0.000 0 0.000 Remote Steam 0 0.000 0 0.000 Remote Chilled Water HVAC Sub-Total Non-HVAC Components Electric 0 0.000 0 0.000 2,353,870 34.086 8,406,680 121.735 3,098,289 44.866 11,065,315 160.235 Natural Gas 0 0.000 0 0.000 Fuel Oil 0 0.000 0 0.000 Propane 0 0.000 0 0.000 Remote Hot Water 0 0.000 0 0.000 Remote Steam 0 0.000 0 0.000 Non-HVAC Sub-Total 3,098,289 44.866 11,065,315 160.235 Grand Total 5,452,159 78.952 19,471,995 281.970 Notes: 1. 'Cooling Coil Loads' is the sum of all air system cooling coil loads. 2. 'Heating Coil Loads' is the sum of all air system heating coil loads. 3. Site Energy is the actual energy consumed. 4. Source Energy is the site energy divided by the electric generating efficiency (28.0%). 5. Source Energy for fuels equals the site energy value. 6. Energy per unit floor area is based on the gross building floor area. Gross Floor Area ............................................ 69057.0 ft² Conditioned Floor Area .................................. 69057.0 ft² Energy Simulation for Commercial Buildings Page ‐ 128 - [ENERGY SIMULATION] 2015 June 22 Monthly Component Cost Air System Fans Cooling Heating Pumps Heat Rejection Fans Lights Electric Equipment Misc. Electric 18000 16000 Cost (SGD) 14000 12000 10000 8000 6000 4000 2000 0 Jan Feb Mar 1. HVAC Component Costs Air System Fans Month (SGD) January 4,194 Apr May Cooling (SGD) 7,251 Jun Jul Month Heating (SGD) 548 Aug Sep Oct Pumps (SGD) 3,430 Nov Dec Heat Rejection Fans (SGD) 1,834 HVAC Total (SGD) 17,257 February 3,796 7,226 520 3,145 1,689 16,376 March 3,337 7,199 461 3,368 1,627 15,992 April 4,083 8,910 604 3,363 1,845 18,805 May 4,055 8,990 515 3,451 1,865 18,876 June 788 3,087 34 3,110 946 7,965 July 2,157 5,171 480 3,261 1,499 12,568 August 4,060 8,126 540 3,450 1,850 18,026 September 3,217 6,408 468 3,289 1,523 14,905 October 4,191 8,466 578 3,449 1,882 18,566 November 3,029 5,909 427 3,237 1,456 14,058 December 2,405 4,129 40 3,273 1,648 11,495 Total 39,312 2. Non-HVAC Component Costs 80,874 5,214 39,826 19,662 184,888 Electric Equipment (SGD) 1,938 Misc. Electric (SGD) 17,740 Misc. Fuel Use (SGD) 0 Lights (SGD) 4,537 Month January Non-HVAC Total (SGD) 24,215 Grand Total (SGD) 41,472 February 4,162 1,780 16,316 0 22,259 38,635 March 3,775 1,693 15,308 0 20,776 36,768 April 4,496 1,916 16,841 0 23,254 42,059 May 4,399 1,894 16,364 0 22,656 41,532 June 1,142 822 7,502 0 9,465 17,430 July 3,863 1,665 9,800 0 15,329 27,897 August 4,408 1,897 16,269 0 22,575 40,601 September 3,658 1,648 14,172 0 19,478 34,383 42,003 October 4,533 1,936 16,967 0 23,437 November 3,467 1,581 14,278 0 19,326 33,384 December 1,702 938 17,748 0 20,388 31,883 44,143 19,709 179,306 0 243,158 428,046 Total Energy Simulation for Commercial Buildings Page ‐ 129 - [ENERGY SIMULATION] 2015 June 22 Monthly Energy Cost by Energy Type HVAC Electric Non-HVAC Electric 24000 22000 Cost (SGD) 20000 18000 16000 14000 12000 10000 8000 Jan Feb Mar Apr May Jun Jul Month Aug Sep Oct Nov Dec 1. HVAC Costs Electric (SGD) 17,256 Month January Natural Gas (SGD) 0 Fuel Oil (SGD) 0 Propane (SGD) 0 Remote Hot Remote Chilled Water Remote Steam Water (SGD) (SGD) (SGD) 0 0 0 February 16,376 0 0 0 0 0 0 March 15,992 0 0 0 0 0 0 April 18,805 0 0 0 0 0 0 May 18,875 0 0 0 0 0 0 June 7,965 0 0 0 0 0 0 July 12,567 0 0 0 0 0 0 August 18,026 0 0 0 0 0 0 September 14,906 0 0 0 0 0 0 October 18,565 0 0 0 0 0 0 November 14,058 0 0 0 0 0 0 December 11,495 0 0 0 0 0 0 184,886 0 0 0 0 0 0 Month January Electric (SGD) 24,214 Natural Gas (SGD) 0 Fuel Oil (SGD) 0 Propane (SGD) 0 February 22,258 0 0 0 Total 2. Non-HVAC Costs Remote Hot Water Remote Steam (SGD) (SGD) 0 0 0 0 March 20,776 0 0 0 0 0 April 23,253 0 0 0 0 0 May 22,656 0 0 0 0 0 June 9,465 0 0 0 0 0 July 15,330 0 0 0 0 0 August 22,574 0 0 0 0 0 September 19,479 0 0 0 0 0 October 23,436 0 0 0 0 0 November 19,327 0 0 0 0 0 December 20,387 0 0 0 0 0 243,157 0 0 0 0 0 Total Energy Simulation for Commercial Buildings Page ‐ 130 - [ENERGY SIMULATION] Monthly Energy Use by System Component 1. Monthly Energy Use by System Component Component Jan Air System Fans (kWh) Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 15795 14095 12394 15316 15205 2770 8172 15195 11713 15797 11118 9299 Cooling 27311 26832 26740 33423 33712 10852 19595 30410 23329 31913 21689 15963 Natural Gas (na) Electric (kWh) 0 0 0 0 0 0 0 0 0 0 0 0 Fuel Oil (na) 0 0 0 0 0 0 0 0 0 0 0 0 Propane (na) 0 0 0 0 0 0 0 0 0 0 0 0 Remote HW (na) 0 0 0 0 0 0 0 0 0 0 0 0 Remote Steam (na) 0 0 0 0 0 0 0 0 0 0 0 0 Remote CW (na) 0 0 0 0 0 0 0 0 0 0 0 0 2063 1931 1713 2264 1931 120 1819 2021 1704 2178 1567 154 Natural Gas (na) 0 0 0 0 0 0 0 0 0 0 0 0 Fuel Oil (na) 0 0 0 0 0 0 0 0 0 0 0 0 Heating Electric (kWh) Propane (na) 0 0 0 0 0 0 0 0 0 0 0 0 Remote HW (na) 0 0 0 0 0 0 0 0 0 0 0 0 Remote Steam (na) 0 0 0 0 0 0 0 0 0 0 0 0 12919 11678 12509 12615 12940 10931 12356 12913 11975 13002 11882 12653 6906 6271 6044 6921 6992 3327 5678 6922 5543 7094 5342 6373 Pumps (kWh) Clg. Tower Fans (kWh) Lighting (kWh) 17087 15455 14023 16866 16495 4014 14640 16495 13317 17087 12726 6582 Electric Eqpt. (kWh) 7299 6609 6290 7189 7101 2890 6310 7101 6000 7299 5802 3625 Misc. Electric (kWh) 66818 60584 56856 63174 61362 26370 37136 60885 51594 63958 52406 68620 0 0 0 0 0 0 0 0 0 0 0 0 Misc. Fuel Natural Gas (na) Propane (na) 0 0 0 0 0 0 0 0 0 0 0 0 Remote HW (na) 0 0 0 0 0 0 0 0 0 0 0 0 Remote Steam (na) 0 0 0 0 0 0 0 0 0 0 0 0 Energy Simulation for Commercial Buildings Page ‐ 131 - [ENERGY SIMULATION] Monthly Energy Use by Energy Type 1. HVAC Energy Use Electric Month (kWh) Jan 64,993 Natural Gas (na) 0 Fuel Oil (na) 0 Propane (na) 0 Remote HW (na) 0 Remote Steam (na) 0 Remote CW (na) 0 0 0 0 0 0 0 Feb 60,806 Mar 59,399 0 0 0 0 0 0 Apr 70,539 0 0 0 0 0 0 May 70,781 0 0 0 0 0 0 Jun 28,000 0 0 0 0 0 0 Jul 47,619 0 0 0 0 0 0 Aug 67,458 0 0 0 0 0 0 Sep 54,264 0 0 0 0 0 0 Oct 69,982 0 0 0 0 0 0 Nov 51,597 0 0 0 0 0 0 Dec 44,442 0 0 0 0 0 0 689,880 0 0 0 0 0 0 Totals 2. Non-HVAC Energy Use Electric Month (kWh) Jan 91,201 Natural Gas (na) 0 Fuel Oil (na) 0 Propane (na) 0 Remote HW (na) 0 Remote Steam (na) 0 0 0 0 0 0 Feb 82,647 Mar 77,165 0 0 0 0 0 Apr 87,227 0 0 0 0 0 May 84,957 0 0 0 0 0 Jun 33,273 0 0 0 0 0 Jul 58,092 0 0 0 0 0 Aug 84,480 0 0 0 0 0 Sep 70,914 0 0 0 0 0 Oct 88,342 0 0 0 0 0 Nov 70,936 0 0 0 0 0 Dec 78,821 0 0 0 0 0 908,056 0 0 0 0 0 Totals Energy Simulation for Commercial Buildings Page ‐ 132 - [ENERGY SIMULATION] 2015 June 22 Electric Billing Details 1. Component Charges Billing Period Jan Energy Charges Demand Charges (SGD) (SGD) 35,228 6,243 Customer Charges (SGD) 0 Taxes (SGD) 0 Total Charge (SGD) 41,471 0 0 38,635 Feb 32,376 6,259 Mar 30,600 6,169 0 0 36,769 Apr 35,694 6,364 0 0 42,058 May 35,166 6,365 0 0 41,531 Jun 12,909 4,521 0 0 17,431 Jul 23,457 4,439 0 0 27,896 Aug 34,344 6,257 0 0 40,601 Sep 28,034 6,350 0 0 34,384 Oct 35,782 6,220 0 0 42,002 Nov 27,354 6,030 0 0 33,384 Dec 27,596 4,287 0 0 31,883 358,543 69,504 0 0 428,047 Totals 2. Totals Billing Period Jan Total Charges (SGD) 41,471 Total Consumption (kWh) 156,198 Avg Price (SGD/kWh) 0.2655 Feb 38,635 143,455 0.2693 Mar 36,769 136,569 0.2692 Apr 42,058 157,768 0.2666 May 41,531 155,738 0.2667 Jun 17,431 61,273 0.2845 Jul 27,896 105,708 0.2639 Aug 40,601 151,942 0.2672 Sep 34,384 125,176 0.2747 Oct 42,002 158,327 0.2653 Nov 33,384 122,532 0.2725 31,883 123,269 0.2586 428,047 1,597,955 0.2679 Dec Totals Energy Simulation for Commercial Buildings Page ‐ 133 - [ENERGY SIMULATION] 2015 June 22 3. Consumption Totals Billing Peak Period (kWh) Jan 137,385 Mid-Peak (kWh) 0 Normal Peak (kWh) 0 Off-Peak (kWh) 18,813 Overall (kWh) 156,198 143,455 Feb 126,416 0 0 17,039 Mar 117,954 0 0 18,614 136,569 Apr 139,978 0 0 17,790 157,768 May 137,427 0 0 18,311 155,738 Jun 44,078 0 0 17,195 61,273 Jul 88,833 0 0 16,875 105,708 Aug 134,462 0 0 17,480 151,942 Sep 107,972 0 0 17,204 125,176 Oct 140,057 0 0 18,270 158,327 Nov 104,744 0 0 17,789 122,532 Dec 106,210 0 0 17,059 123,269 1,385,517 0 0 212,438 1,597,955 Totals 4. Billing Demands Billing Period Jan Peak (kW) 623.4 Mid-Peak (kW) 0.0 Normal Peak (kW) 0.0 Off-Peak (kW) 210.1 Overall (kW) 623.4 Feb 628.0 0.0 0.0 207.6 628.0 Mar 617.4 0.0 0.0 206.2 617.4 Apr 644.5 0.0 0.0 205.2 644.5 May 642.0 0.0 0.0 207.9 642.0 Jun 400.3 0.0 0.0 203.4 400.3 Jul 403.9 0.0 0.0 188.8 403.9 Aug 638.5 0.0 0.0 196.9 638.5 Sep 639.4 0.0 0.0 208.4 639.4 Oct 634.2 0.0 0.0 196.2 634.2 Nov 613.5 0.0 0.0 191.6 613.5 Dec 393.8 0.0 0.0 178.6 393.8 5. Maximum Demands Billing Period Jan Peak (kW) 623.4 Mid-Peak (kW) 0.0 Normal Peak (kW) 0.0 Off-Peak (kW) 210.1 Overall (kW) 623.4 Feb 628.0 0.0 0.0 207.6 628.0 Mar 617.4 0.0 0.0 206.2 617.4 Apr 644.5 0.0 0.0 205.2 644.5 May 642.0 0.0 0.0 207.9 642.0 Jun 400.3 0.0 0.0 203.4 400.3 Jul 403.9 0.0 0.0 188.8 403.9 Aug 638.5 0.0 0.0 196.9 638.5 Sep 639.4 0.0 0.0 208.4 639.4 Oct 634.2 0.0 0.0 196.2 634.2 Nov 613.5 0.0 0.0 191.6 613.5 Dec 393.8 0.0 0.0 178.6 393.8 Energy Simulation for Commercial Buildings Page ‐ 134 - [ENERGY SIMULATION] 2015 June 22 6. Time of Maximum Demands Billing Peak Period (m/d/h) Jan 1/26/0900 Mid-Peak (m/d/h) n/a Normal Peak (m/d/h) n/a Off-Peak (m/d/h) 1/26/0600 Overall (m/d/h) 1/26/0900 Feb 2/2/0900 n/a n/a 2/2/0600 2/2/0900 Mar 3/30/0900 n/a n/a 3/23/0600 3/30/0900 Apr 4/27/0900 n/a n/a 4/20/0600 4/27/0900 May 5/18/0900 n/a n/a 5/25/0600 5/18/0900 Jun 6/29/0800 n/a n/a 6/4/0000 6/29/0800 Jul 7/20/1100 n/a n/a 7/23/0000 7/20/1100 Aug 8/31/0900 n/a n/a 8/31/0600 8/31/0900 Sep 9/14/0900 n/a n/a 9/14/0600 9/14/0900 Oct 10/26/0900 n/a n/a 10/26/0600 10/26/0900 Nov 11/2/0900 n/a n/a 11/26/0000 11/2/0900 Dec 12/1/0800 n/a n/a 12/3/0000 12/1/0800 Hourly Energy Use Profile Hour 0000 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 Wednesday Aug 26 (kW) 58.1 58.1 58.1 58.1 47.9 37.7 158.9 338.0 592.3 562.7 541.9 561.1 500.2 470.5 422.4 437.2 369.5 178.7 133.6 130.4 131.5 139.1 64.0 58.1 Thursday Aug 27 (kW) 173.6 58.2 58.2 58.3 48.0 37.8 157.4 348.4 590.5 594.8 581.2 563.4 491.5 473.3 412.7 412.3 366.9 181.9 135.9 135.9 134.3 144.3 64.0 58.1 Friday Aug 28 (kW) 58.2 58.2 58.2 58.2 48.0 37.8 170.4 353.8 570.3 563.7 547.4 531.0 485.1 456.4 404.6 406.9 362.4 172.8 129.1 127.3 128.6 140.4 64.2 58.3 Energy Simulation for Commercial Buildings Page ‐ 135 - [ENERGY SIMULATION] Hourly Energy Use Graph Electric Use Profiles - Tuesday, August 26 (day 238) thru Thursday, August 28 (day 240) 600 550 500 450 Usage ( kW ) 400 350 300 250 200 150 100 50 0 238 239 240 Day of Year Energy Simulation for Commercial Buildings Page ‐ 136 - [ENERGY SIMULATION] Appendix “A” Energy Simulation for Commercial Buildings Page ‐ 137 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 138 - 2015 June 22 [ENERGY SIMULATION] Appendix “A” Air System Schematics Energy Simulation for Commercial Buildings Page ‐ 139 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 140 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 141 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 142 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 143 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 144 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 145 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 146 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 147 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 148 - 2015 June 22 Energy Simulation for Commercial Buildings [ENERGY SIMULATION] Page ‐ 149 - 2015 June 22 [ENERGY SIMULATION] Induction Beam System Schematic Energy Simulation for Commercial Buildings Page ‐ 150 - 2015 June 22 [ENERGY SIMULATION] Induction Beam Terminal Diagram Chilled Beam System Schematic Chilled Beam Terminal Diagram Energy Simulation for Commercial Buildings Page ‐ 151 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 152 - [ENERGY SIMULATION] 2015 June 22 Appendix”B” APPENDIX B Application Topics Energy Simulation for Commercial Buildings Page ‐ 153 - 2015 June 22 [ENERGY SIMULATION] Blank Page Energy Simulation for Commercial Buildings Page ‐ 154 - [ENERGY SIMULATION] 2015 June 22 Putting Load Calculation Methods in Perspective By Rudy Romijn, Regional Sales Manager, Carrier Software Systems Over the years our industry has used many methods for performing cooling load calculations. Comparing these methods provides a useful perspective on the benefits of the methods currently employed by engineers, and ultimately helps in understanding output data provided by engineering software like HAP. Those of us who started in this business before the age of computers can appreciate Figure 1 shown below. It illustrates the relationship between complexity and accuracy that many of us had to grapple with for five of the principal load methods used over the years. Load Estima ting M eth ods AS HRAE Heat Balance Method A C C U R A C Y ASHRAE RTS ASHRAE Transf er Functions ASHRAE CLTD/CLF Carrier E20 M ethod Instantaneous Q=U A TD INC RE AS IN G C OM P LE X IT Y Figure B-1. Load Estimating Methodologies In the past, we calculated loads by hand using the “instantaneous method” which assumed heat gains were instantly converted to cooling loads. This method was simple and fast, but was unreliable because it ignored processes such as heat storage and radiation transfer, which affect the rate at which heat gains become cooling loads. In 1960, Carrier published its System Design Manual, which included tables of Equivalent Temperature Differences (ETD) and Storage Load Factors (SLF) to predict cooling loads, which incorporated the effects of heat storage by building materials, and the effects of building orientation and occupancy cycle. Later, in the 1970s ASHRAE published its CLTD/CLF method, which incorporated the same kind of considerations. As hand calculation procedures, both methods did a good job of balancing complexity (and therefore effort) with accuracy. However, both methods lacked flexibility. Building loads are affected by a wide variety of factors involving design, construction, environment and building use. Table-based hand calculation methods typically dealt with a fixed set of basic conditions (such as envelope loads for July 16:00, 40 degrees north latitude) and then attempted to handle other conditions via correction factors. Ultimately, this approach introduced errors and reduced accuracy when compared with methods that are more complex. We needed a way of calculating loads specific to each design application. Energy Simulation for Commercial Buildings Page ‐ 155 - 2015 June 22 [ENERGY SIMULATION] The Heat Balance Method, the most rigorous method of calculating building loads, provides one solution to this problem. Heat balance is actually the foundation of all the other methods of calculating building loads. The heat balance method evaluates each conductive, convective, radiative and heat storage process that occurs in the building using the fundamental laws of heat transfer and thermodynamics. Using the heat balance method to determine building heat transfer requires an equation written for each surface and mass element considering each process involved. By solving all heat balances equations simultaneously, the total rate of heat transferred to room air can be determined and the dynamic ebb and flow of heat in the room can be successfully evaluated. The Heat Balance method can be highly accurate but it is also complex and requires powerful computer hardware, detailed inputs and long calculation time. An alternate solution is the ASHRAE endorsed Transfer Function Method of calculating loads, and which is used in the HAP, System Design Load, Block Load and Block Load Lite programs produced by Carrier. The Transfer Function Method uses some mathematical “tricks” to simplify the heat balance solution process, thereby yielding calculation times that are faster than those of the Heat Balance Method without sacrificing too much of its accuracy. The Transfer Function procedure calculates how heat gains from sources such as warm ambient air, solar radiation, lights, people, etc. are converted to cooling loads via conduction, convection, radiation and heat storage processes. The procedures therefore account for the dynamic heat transfer found in a “real world” building. Further, calculations account for specific design, construction, environmental and building usage conditions and are therefore customized to each building application. Thus, for the current state of technology of computerized engineering tools, Transfer Functions provide a good compromise between complexity and accuracy. Figure B-2. Lighting Heat Gains and Loads Energy Simulation for Commercial Buildings Page ‐ 156 - 2015 June 22 [ENERGY SIMULATION] When using programs that employ the Transfer Function Method, remember that nearly all loads involve dynamic heat flow. Heat gain received from a source such as lighting is not immediately converted to a cooling load. Rather, the portion of the heat gain that is thermal radiation is transferred to massive building elements such as floors and walls, and may be stored for a period of time before being released to air in the building. Once heat is transferred to the air, it is a load that must be removed by the air conditioning apparatus. Figure 2 shows a sample relationship between lighting heat gain and load. When the lights first come on, a significant portion of the lighting heat gain is absorbed and held by the building mass. Over time, this stored heat is discharged to air in the building, but more radiant heat is received. When the lights are turned off, the stored heat continues to be discharged. Thus, loads continue even after the heat gains cease. All heat sources that involve a radiant component exhibit similar behavior. These include loads for walls, roofs, windows, partitions, people, lights and electrical equipment. Transfer Function calculations account for these dynamic processes. Remembering this is often very helpful when analyzing load calculation outputs. The Radiant Time Series method was introduced in ASHRAE 2001 Handbook of Fundamentals. It is a dynamic way of calculating loads, but is not as complex to calculate and is easier to understand than the TFM. It is a good method to obtain sizing data for a typical building. However, it is not a good method to simulate system operation. Energy Simulation for Commercial Buildings Page ‐ 157 - 2015 June 22 [ENERGY SIMULATION] The Benefits of the Transfer Function / Heat Extraction Method The previous article (Putting Load Calculation Methods in Perspective) describes the transfer function and heat extraction procedures used to calculate loads in HAP. While the benefits of this calculation method for energy analysis are evident, customers often question whether such advanced calculation methods are worth using for system design applications, or whether simpler methods would be sufficient. Carrier feels that advanced methods such as transfer functions/heat extraction should be used because the method provides several important benefits to users. These include: 1. Accuracy. Advanced methods such as Transfer Functions account for the dynamic heat flow processes which occur in buildings and which significantly influence design loads and system behavior. Simpler methods either ignore these dynamics, or analyze them in much less detail than Transfer Functions. Advanced methods therefore can provide results that are more accurate. 2. Pull down Loads. One of the most important aspects of dynamic heat flow is the pull down load. Pulls down loads have a significant influence on system sizing results and therefore need to be considered. Advanced methods such as Transfer Functions/Heat Extraction are the only way to adequately account for pull down loads. Simpler methods can only make gross estimates of the effect of pull down loads. 3. Flexibility. Advanced methods such as Transfer Functions/Heat Extraction customize calculations to the application. Since loads are dynamic, loads in one hour are influenced by conditions in both the current hour and previous hours. The nature of 24-hour profiles of solar radiation, ambient temperature and internal heat gain need to be considered to accurately predict loads in any one hour. Transfer functions use the solar, temperature and internal gain profiles defined by the user for each specific application. Therefore, loads are customized to each application. Simpler table-based methods make assumptions, such as a standard operating profile or the use of July 40°N latitude for solar radiation. In some cases, correction factors are used to try to adjust for actual conditions. These adjustments are often not adequate and produce less accurate results than methods that customize calculations to each application. Understanding Zone Loads and Zone Conditioning Have you ever examined a HAP Air System Design Load Summary output and wondered ‘what is zone conditioning and why it differs from the total zone load?’ Judging from questions our support staff receives, many people have wondered the same thing. The answer to this question requires an explanation of the ASHRAE Transfer Function and Heat Extraction methods. Understanding the calculation methods used by computerized engineering tools is vital to the successful use of these tools. As these tools use increasingly complex analytical methods, the methods become more difficult to grasp. This article attempts to aid understanding of the load calculation method used in Carrier’s Hourly Analysis Program (HAP) by explaining the transfer function and heat extraction methods in plain language and without the use of mathematical equations. If at the end of this discussion you understand what “zone conditioning” and “zone load” refer to and why they are different, the article will have been successful. Objectives. First, we need to clarify our objectives for a load calculation tool. As HVAC system designers, we want: A calculation tool that accounts for all the processes involved with building heat flow, A tool that is fast, A tool that is easy to use, and A tool that provides accurate, reliable results. Energy Simulation for Commercial Buildings Page ‐ 158 - 2015 June 22 [ENERGY SIMULATION] Understanding the Processes at Work. Providing accurate, reliable results requires accounting for all of the complicated heat flow processes occurring in the building. For the explanations of the Transfer Function and Heat Extraction Method later in this article to make sense, we first need to provide a quick refresher on the heat flow processes that occur in a building. First, our ultimate interest is in cooling or heating loads. A “load” is the rate of heat transfer to or from the air in the building. Heat transferred to air in a room changes the room air temperature. The thermostat senses these changes and sends a signal to the HVAC equipment to provide cooling or heating. Secondly, we are all familiar with the different sources of heat gain or loss, which influence cooling or heating demands in the building. These include solar radiation, temperature gradients across walls, heat gain from lighting, people, etc. Therefore, we know where the heat originates (the sources) and we know where it ultimately ends up (in the air in the building). The challenging part of this engineering problem is analyzing how heat travels from its source to its destination. As an example, let us consider the wall component of a cooling load. First, solar radiation and ambient air warm the outside surface of the wall. This initiates heat flow across successive layers in the wall assembly. Heat does not flow instantaneously from outside to inside surfaces of the wall. Instead, it takes time. In addition, the amount of time depends on the intensity of heat flow at the outer surface plus the thickness, density, specific heat and thermal conductivity properties of material layers in the wall assembly. Ultimately, heat reaches the inside surface of the wall where it raises the wall surface temperature. At this point two things happen. First, a portion of the heat convects to air in the room, raising the air temperature. Thus, this heat becomes a cooling load. Second, a substantial portion of the heat at the wall surface transfers as thermal radiation to other wall, ceiling and floor surfaces in the room. This raises the temperature of the other surfaces and triggers convection to room air, heat storage within the material and further radiative exchanges within the room. Eventually most or all of the original heat flow becomes a cooling load, but the complete conversion of the heat gain to cooling load takes time. The same sort of thermal processes occur for heat flow through roofs, windows, doors and partitions. Heat from other sources such as solar, lighting, electrical equipment and occupants is introduced directly into the room, and once in the room it undergoes the same sort of room heat transfer processes described for walls. This is because all these heat gains are comprised of separate convective and radiative components. The convective components immediately become cooling loads. The radiative components transfer directly to surfaces in the room and then undergo further radiant, convective and heat storage processes. Another important factor governing heat flow to the air in the room is the temperature of the room air. The temperature difference between wall, ceiling and floor surfaces and the room air govern convection. Thus, for a cooling scenario, convective heat flow from warm room surfaces decreases as the room air temperature rises. As room air temperature falls, convective heat flow from warm room surfaces increases. Recognizing this is important for two reasons. First, all thermostats have a certain operating range within which they attempt to maintain room air temperature. Thus, room air temperature varies within this operating range and this influences convective heat flow. More importantly, nighttime setup control or equipment shutdown can cause room temperature to vary by 10 °F (-12.2 °C) or more during a 24-hour operating cycle. A large increase in room temperature greatly reduces convective heat flow. Heat is essentially “trapped” in the massive elements in the room, and the surface temperatures of these elements rise. In the morning when cooling equipment starts up reducing room air temperatures, there is a “rush” of convective heat flow due to the large temperature difference between room air and the surfaces in the room. We call this process “pull down load.” Energy Simulation for Commercial Buildings Page ‐ 159 - 2015 June 22 [ENERGY SIMULATION] Therefore, in summary: There are many factors involved in building heat flow. This heat flow occurs over time rather than instantaneously. Room air temperature governs heat flow from surfaces in the room to the air in the room. The nature of the thermostat control in a room influences the rooms cooling loads by affecting convective heat flow. Calculating Building Heat Flow. Now, in order to calculate realistic, accurate building loads, we need to account for all of the complicated processes we have just discussed. This is quite a challenge. One way to do this is with the “Heat Balance Method” which is essentially the “mother of all load calculation methods.” With this method, each of the heat flow processes is represented by a mathematical equation drawn from the laws of conduction, convection and radiation and from the first law of thermodynamics. The result is a large number of equations, and an equally large number of unknown quantities. Typically, no one equation can be solved directly. Instead, the whole set of equations must be solved simultaneously or by iteration. The results of this calculation are the temperatures and heat flows at each surface in the room, and ultimately the temperature and heat flow to room air, which tells us the cooling load. Currently, we cannot satisfy our original objectives of “fast” and “easy” with the Heat Balance Method because computer software using this method requires too much calculation time and too much input data. However, the day is fast approaching when this method will become feasible for everyday use on desktop computers. Until then, we need an alternate solution to our engineering challenge. That solution is the Transfer Function Method, first developed by researchers in the late 1960s. The Transfer Function Method uses several mathematical “tricks” to make solving heat balance equations much faster. While this method is faster, it continues to account for the complex processes involved in building heat flow and thus provides realistic, accurate results. Here is how it works. Within the method, there are three kinds of transfer function equations used to analyze different aspects of the building heat flow problem: HAP uses Conduction Transfer Function Equations to analyze the conductive heat flow through walls and roofs. HAP uses Room Transfer Function Equations to analyze the radiative, convective and heat storage processes for all load components once heat reaches the interior of the room. HAP uses Space Temperature Transfer Function Equations (aka. Heat Extraction Equations) to analyze the effect of changing room temperatures on convective heat flow from surfaces in the room to the room air. Included in this calculation is the behavior of the room thermostat in controlling room temperature levels and communicating demands to the cooling or heating apparatus. Using these three kinds of transfer function equations in sequence determines how heat from various heat sources converts into cooling loads in the building. However, there is one complicating factor crucial to this whole discussion. It has been said that there is “no such thing as a free lunch,” and that is certainly true in this case. As we noted earlier, the Transfer Function Method uses mathematical tricks to simplify and speed up the calculation process. The cost of increased speed is performing the calculation in two distinct stages. There are simply too many factors involved to be able to solve the entire problem in one pass when using the transfer function tricks. In the first stage of this calculation process, we use the Conduction and Room Transfer Function Equations to calculate room loads as if the room is held at precisely one temperature 24 hours a day. For a design cooling calculation, we use the cooling thermostat set point as the fixed room temperature for this calculation. Once room loads based on this simplifying assumption have Energy Simulation for Commercial Buildings Page ‐ 160 - 2015 June 22 [ENERGY SIMULATION] been determined, the second calculation stage “corrects” these loads to account for the true behavior of the building (rising and falling room temperatures) using the Space Air Transfer Function Equations. In HAP, results of these two calculation stages appear throughout the system design reports. On the Air System Design Load Summary, all the results in the top portion of the report down to and including the “Total Zone Load” are from the first stage of the calculation, which assumed constant room temperature. We use the terms “zone load” and “space load” throughout the reports to refer to results from this first stage of calculations. We use the term “Zone Conditioning” to refer to the results of the second stage of calculations. HAP corrects the “Total Zone Loads” to produce “Zone Conditioning” by accounting for room temperature and thermostat effects. As such, Zone Conditioning represents the true amount of cooling or heating a room needs and is the basis for simulating operation of system components such as coils and fans. Results from the system simulation appear in the lower part of the Air System Design Load Summary. Differences between “Zone Loads” and “Zone Conditioning” are due to room temperature effects on heat transfer such as pull down loads and temperature variations within the thermostat throttling range. Conclusion. The Transfer Function Method allows us to consider as many of the complex aspects of building heat flow as possible to provide accurate results, and at the same time provide a calculation tool that is fast and easy to use. The price for these benefits is that we must perform the calculation in two distinct stages. The first stage yields what HAP calls “zone loads” and “space loads” assuming a constant room temperature. The second stage yields what HAP calls “zone conditioning” which is derived by correcting the original zone loads to account for room air temperature effects. Zone conditioning represents the true demand for cooling or heating in a zone. Understanding this two-stage process and the results it yields is important for successfully applying program results. Energy Simulation for Commercial Buildings Page ‐ 161 - 2015 June 22 [ENERGY SIMULATION] The Sizing Dilemma In HAP, users are asked to choose among four different methods of sizing zone and space airflow rates. This discussion explains why different sizing methods are used and summarizes the four methods offered in the programs. The Sizing Dilemma. The key issue is that there is not a single “correct” way to size space airflow rates. In fact, no sizing method can guarantee comfort in all spaces at all times when a zone contains multiple spaces. The reason for this is that each zone has a single thermostat to control the comfort conditions in all the spaces in that zone. The space that contains the thermostat will maintain comfort conditions, but the other spaces in the zone will receive conditioning based on the load in the space containing the thermostat. Because of this imperfect situation, designers’ use different approaches to size space airflow rates in order to minimize conditioning problems in the spaces that do not contain the thermostat. Which approach is best varies by application. Ultimately, the choice of a sizing method depends on the designer’s judgment and experience. Sizing Method #1: Zone airflow computed using peak zone load. Space airflow computed using zone CFMft² or L/s/m². With this method, the zone airflow is computed using the maximum zone sensible cooling load. The zone airflow is divided among spaces in the zone on the basis of zone CFM/ft² (L/s/m²). Therefore, space airflow is not related to space loads unless all spaces in the zone have a consistent load density in BTU/hr/ft² (W/m²). Sizing Method #2: Zone airflow computed using peak zone load. Space airflow computed using coincident space loads. With this method the zone airflow is calculated from the maximum zone sensible cooling load. The zone airflow is divided among spaces in the zone on the basis of the ratio of coincident space sensible cooling loads to peak zone sensible load. By “coincident,” we mean the space load computed for the month and hour when the zone sensible load peaks. Sizing Method #3: Zone airflow computed using peak zone load. Space airflow computed using peak space load. With this method, the zone airflow is computed using the maximum zone sensible load. Required space airflow rates are computed using the maximum sensible load for each individual space. Note that if spaces experience peak loads at the same time the zone peak occurs, the sum of space airflow rates will equal the zone airflow rate. Otherwise, the sum of space airflows will exceed the zone airflow rate. Sizing Method #4: Zone airflow computed using sum of space airflows. Space airflow computed using peak space load. With this method, required space airflow rates are computed using the maximum sensible load for each individual space. The zone airflow rate is calculated as the sum of space airflows for all spaces in the zone. Energy Simulation for Commercial Buildings Page ‐ 162 - 2015 June 22 [ENERGY SIMULATION] Which Sizing Method to Use? By John Deal, Regional Sales Manager, Carrier Software Systems. The previous article titled The Sizing Dilemma discusses in detail the four sizing methods in HAP. The problem confronting the designer is that one of the four methods must be chosen and some thought is required to determine which method to use. The purpose of this article is to share some ideas to assist your decision on which sizing method to use. The four methods summarized in the previous article (The Sizing Dilemma) are those requested by our HAP customers. If someone has another sizing method, we certainly would like to hear about it! I think we can safely say that every designer uses one of these methods almost exclusively and probably was not aware of the three alternatives until forced by an impudent software program to make a choice. The method one uses is probably from a habit formed when a load estimating methodology and calculations were first learned or passed on from a teacher, a mentor or a boss. Methods 1 and 2 give results similar to those of “hand” calculation methodology expectations. Simplifying assumptions were made because of the amount of time it took to perform the number crunching. One could not afford the time necessary to calculate loads over a number of hours or to break up the building into numerous design zones and spaces. So, results were obtained in a simplified fashion that could be easily applied throughout the design such as CFM/ft² (L/s/m²), heat loss of BTU/hr/linear ft. (W/m) of exposure and so forth. Methods 3 and 4 give results expected of a methodology that can only be done on a computer. Calculating 12 months 24 hours a day to find peak loads for fans, coils, zones and spaces is a reasonable expectation. Crunching the numbers on hundreds of spaces collected into a hundred or more zones in a dozen air systems is a reasonable expectation. I am going to make a provocative statement to start your thought process on which methods to use. If you are doing detailed final design calculations, methods 3 and 4 are the ones to use and the type of system under design will dictate which one. Variable air volume (VAV) systems use method 3. Constant volume systems use method 4. The key function that these two methods share is that the space peak sensible load is found and reported. This gives the designer the information about the peak design parameters for every space defined. With this information, the designer can get a better handle on the magnitude of the compromises that must be made with the control zone layouts, duct design and terminal equipment sizing. Using method 3 for a VAV terminal zone sizes the “box” for a VAV diversified CFM. The spaces in the zone are sized for their peak so no matter which space the thermostat is placed in that space can be controlled. If future reworking of zones is done, the space duct and terminal sizing is still valid. The key to good zoning practice is to have spaces with similar thermal load profiles on the same thermostat. With this method the time and month that each space peaks is reported. This helps in the decision whether the spaces have similar thermal load profiles. If all the spaces in the zone peak in the same month around the same time of day, this indicates a good probability of similar thermal load profiles for the spaces. If one or more spaces peak at different times of the year than the other spaces this indicates dissimilar load profiles and some thought should be given to “re-zoning." Energy Simulation for Commercial Buildings Page ‐ 163 - 2015 June 22 [ENERGY SIMULATION] Using method 4 for constant volume systems is good practices since these types of systems are normally not sized with diversified or block load air quantities. Let us discuss one of the most common systems, the packaged rooftop unit. In HAP language, this is a single zone constant air volume system. If the designer takes the time to describe the various areas served as spaces, some valuable information can be gained. An example is the amount of air needed in different places so diffusers and the duct system can be designed with some knowledge of the actual requirements. Again, if some of the spaces were peaking at different times of the year than others this would indicate the need for better zoning (another unit if you can afford it). At least you will know that the job probably will not work very well at this stage. This method also sizes the rooftop unit CFM (L/s) undiversified. This is good since it seems you need to get all the air you can on these types of jobs. We hope that this article has helped you think about the choices of space descriptions, zoning and sizing methods you must make. Make your choices with a purpose in mind. I am sure many of you may have differing thoughts and we would like to hear them. Even with faster computers and more complex software, system design still has a lot of art and designer experience involved. Remember this old saying: If a job is to work correctly, it must be designed right one time. The problem is when! Energy Simulation for Commercial Buildings Page ‐ 164 - 2015 June 22 [ENERGY SIMULATION] Differences between Peak Coil Load CFM, Max Block CFM, Sum of Peak Zone CFM In the cooling coil section of the HAP Air System Sizing Summary printout, three coil airflow rates are listed: (1) the coil airflow for the time when the maximum coil load occurs, and (2) the maximum block airflow rate and (3) sum of the peak zone CFM (L/s). When analyzing VAV systems, these three airflow rates can often differ. This article explains why. An accompanying article provides recommendations for selecting equipment in these situations. In most cases, the coil airflow rates differ in VAV applications for one of the following two reasons: The peak cooling coil load and peak zone sensible load occur at different times, resulting in different coil airflow rates at these times. Due to the ASHRAE sizing methodology used by HAP, the two airflow rates are computed using slightly different considerations. This can introduce small differences between the two airflow values even if the coil load and zone sensible load peak at the same time. Each reason will be explained separately below. Differences Due to Timing of Peak Loads. The maximum airflow rate required for the supply fan and therefore for the central cooling coil depends on the cooling requirements in zones served by the air system. The individual component loads in the zones such as wall, roof, window, solar, lighting, people and equipment loads influence zone cooling requirements. These loads vary due to changes in outdoor air temperature, solar radiation and internal heat gains throughout the day. While the maximum cooling coil load is influenced by these same zone cooling requirements, it is also influenced by extra heat gains introduced by outdoor ventilation air, fan heat, return plenum heat, and the latent components of the coil load. Because extra factors influence the coil load, it is possible for the maximum coil load to occur at a different time than the peak zone sensible load occurs. In a VAV system, the coil airflow varies as zone cooling requirements vary. Therefore, if the peak cooling coil load and peak zone sensible load occur at different times, the coil airflow rates for the two times will differ. The following simple example illustrates how this situation can occur. Example #1. Consider a 1-zone VAV system that serves an east-facing zone. Figure B-3 shows 24-hour profiles for the total cooling coil load and the zone sensible load for this system. The zone has a large area of east-facing glass. Consequently, solar heat is the dominant load component and causes the peak zone sensible load to occur at 9 am. The total cooling coil load in this example is strongly influenced by ventilation loads, which peak during the mid-afternoon hours. Since the outdoor air temperature is relatively cool at 9 am versus mid-afternoon, the peak coil load occurs at 2 pm rather than 9 am. When the peak zone sensible load occurs at 9 am, the zone requires 5154 CFM of supply air. When the cooling coil load peaks at 2 pm, the zone sensible load has dropped to approximately 80% of its peak value and the zone requires only 4100 CFM of supply air. For such a situation, HAP will report the following data on the Air System Sizing Summary output Peak coil load occurs at: Jul 1400 Coil CFM (L/s) at Jul 1400: 4100 CFM (1935 L/s) Maximum block CFM (L/s): 5154 CFM (2432 L/s) Sum of peak zone CFM (L/s) 5369 CFM (2534 L/s) Energy Simulation for Commercial Buildings Page ‐ 165 - 2015 June 22 [ENERGY SIMULATION] The Sum of the peak zone CFM (L/s) is useful for judging diversity in VAV systems and for sizing components for special periods when all VAV box dampers are full open at the same time. Differences Due to Methodology. The ASHRAE design procedure, which utilizes the transfer function method and heat extraction techniques, requires a two-stage calculation: 1. First, zone sensible loads are computed assuming the zone is held exactly at the cooling thermostat set point 24 hours per day. Results from this analysis are used to determine peak zone airflow rates and the peak central coil airflow rate. 2. Second, the program simulates system operation. When doing so, it takes the zone loads calculated in the first stage and corrects them for the actual system operating conditions. These corrections account for the use of different thermostat set-points during occupied and unoccupied periods or the shutdown of cooling during the unoccupied times, and for the existence of a throttling range for the thermostat. Considering these real-life system-operating factors changes the thermal dynamics of the system, causing zone temperatures to vary within the thermostat throttling range and introducing pull-down load components at certain times of day. The "Max block CFM (L/s)" is calculated in stage 1 and is therefore based on the idealized zone loads computed in this stage. The coil airflow at the peak coil load time is obtained from stage 2, and is therefore based on the corrected zone loads computed considering the actual system operating conditions. Because the two airflows are computed using slightly different considerations, differences between the two airflows often occur for VAV systems. The following example illustrates these method-based effects. Figure B-3 Stage One Calculations Energy Simulation for Commercial Buildings Page ‐ 166 - [ENERGY SIMULATION] 2015 June 22 Figure B-4 Stage Two Calculations Example #2. Consider a VAV system that serves four zones. Hourly profiles of the total coil load and the zone sensible block load are shown in Figure B-4. Here "block load" refers to the sum of the sensible loads for all four zones. The maximum zone sensible block load occurs at 5 pm in July. Based on this block load, the required coil airflow rate is 13269 CFM (l/s.) The maximum cooling coil load also occurs at 5 pm in July. For this hour the coil airflow rate is 12355 CFM (l/s.) Therefore, on the Air System Sizing Summary, HAP will report: Peak coil load occurs at Jul 1700 Coil CFM (L/s) at Jul 1700 12355 CFM (L/s) Max block CFM (L/s) 13269 CFM (L/s) In this example, the 900 CFM (425 L/s) difference between airflows is due to the different considerations used to calculate the required fan airflow in stage 1 of the analysis, and the coil airflow during the system simulation in stage 2 of the analysis. Further investigation of the results showed that the zone air temperatures are close to 76° F (24.4° C), which is the upper limit of the thermostat throttling range for this example. For the initial zone loads calculated in stage 1 of the analysis, a thermostat set-point of 75° F (23.9° C) was used. The difference in zone air temperatures used in the two calculations (75° F [23.9° C] versus 76° F [24.4° C]) and its effect on zone thermal dynamics ultimately results in lower coil airflow. The important thing to recognize is airflows are computed for different purposes and therefore use different considerations. The maximum coil airflow is derived as part of the zone and fan airflow sizing calculation, which considers idealized conditions. The coil airflow at the time of the peak coil load is derived as part of the cooling coil analysis. This analysis considers all of the operating factors of the system, most notably the interaction between the zone thermostats and the VAV box dampers, and between zone air temperature and room loads. Energy Simulation for Commercial Buildings Page ‐ 167 - 2015 June 22 [ENERGY SIMULATION] Further Information. Differences between maximum coil airflow rate and coil airflow rate for the peak coil load time can also occur for Multizone, Bypass Multizone and Dual Duct CAV systems, and for single-zone constant volume systems using fan cycling. Selecting Equipment When Coil CFM (L/s) Differ The preceding article describes situations in which the maximum coil airflow rate differs from the airflow rate at the time of the peak cooling coil load. When this happens, a design engineer is faced with the dilemma of which airflow rate to use when selecting equipment. This article provides recommendations for dealing with this equipment selection situation. Central Cooling Coils in VAV Systems. First, the packaged unit or the cooling coils for a built-up unit should be selected using the airflow at the time of the peak coil load [listed as "Coil CFM (L/s) at month/hour"]. This airflow is obtained from the system simulation and corresponds to the total load, sensible load, and entering and leaving temperature conditions in the table. Thus, in order to use consistent coil performance data for selection, the "Coil CFM (L/s) at month/hour" item must be utilized. Second, use the fan motor BHP or fan motor kW data reported in the "Supply Fan Sizing Data" section of the Air System Sizing Summary to select the fan motor. Third, verify that the selected fan can operate at the maximum fan airflow rate without exceeding its maximum RPM value. The maximum fan airflow is reported in two places on the Air System Sizing Summary. It appears in the "Central Cooling Coil Sizing Data " table as "Max block CFM (L/s).” It also appears in the "Supply Fan Sizing Data” table as "Actual max CFM (L/s)". The Sum of peak zone CFM (L/s) is provided for those who wish to take further precautions. Finally, in certain applications, it may be necessary to use product literature to verify that excessive water carry-over will not occur when the coil experiences its maximum airflow rate. Recommendations for Other System Types. Differences between the maximum coil airflow and the coil airflow at the peak coil load time can also occur for Multizone, Bypass Multizone, and Dual Duct CAV systems. For these systems, the cooling coil should be selected using the airflow at the peak coil load time. Make sure the coil will not have excessive water carryover when operating at maximum airflow. To select the fan, the maximum fan airflow should be used since the fan supplies air to both cold and hot decks.¨ Energy Simulation for Commercial Buildings Page ‐ 168 - 2015 June 22 [ENERGY SIMULATION] ASHRAE 62.1-2004 and 2007 Ventilation Air Sizing in HAP This article explains how to define the ASHRAE 62.1-2004 and 2007 ventilation requirements in HAP 4.6. We also discuss differences between Standard 62.1-2004/7 and Standard 62-2001 with respect to space usage and outdoor air requirements. We also explain how HAP determines the minimum system ventilation (outdoor air) requirement per 62.1-2004/7 at the space level and then at the system level which is the OA intake of the HVAC unit. We end our discussion reviewing the HAP Ventilation Sizing Summary Report for a VAV system using ASHRAE Standard 62.1-2004/7 procedures. HAP e-Help # 006 titled “Ventilation” dated November 2, 2005 is prerequisite reading to this discussion. It examines ASHRAE Standard 62-2001, and “user defined” ventilation sizing method. It explains the hierarchy employed by the software in determining the ventilation air requirements of the HVAC system. We also explain ventilation airflow controls, which including constant, proportional, scheduled and DCV (demand controlled ventilation). ASHRAE Standard 62 Since its introduction, Standard 62 from the American Society of Heating, Refrigerating and AirConditioning Engineers (ASHRAE) has been the primary design reference affecting the ventilation aspects of HVAC systems. ASHRAE Standard 62.1-2010, is the most recent ventilation standard. As shown below, the standards for ventilation air have evolved over the years to accommodate the changing design trends in the industry. Figure C-1 Evolution of ASHRAE Ventilation Standards Energy Simulation for Commercial Buildings Page ‐ 169 - 2015 June 22 [ENERGY SIMULATION] The purpose of ASHRAE 62.1-2004/7, is to specify minimum ventilation rates to help achieve acceptable indoor air quality. Since we can dilute contaminants in indoor air by supplying the space with uncontaminated outdoor air, ASHRAE established ventilation rates in Standard 62.12004/7 based on achieving this dilution. ASHRAE 62.1-2004/7 considers these minimum dilution requirements as good design practice for achieving acceptable indoor air quality. Defining ASHRAE Standard 62.1-2004/7 Ventilation Requirements in HAP In HAP, we use the preferences option on the “View” Menu to specify preferences affecting the project operation such as ventilation. See figures C-2 and 3 below to set preferences. HAP includes the following choices for ventilation calculations: User Defined ASHREA Standard 62-2001 ASHRAE Standard 62.1-2004 ASHRAE Standard 62.1-2007 Figure C-2 HAP Preferences Figure C-3 Setting Project Preferences Energy Simulation for Commercial Buildings Page ‐ 170 - 2015 June 22 [ENERGY SIMULATION] Space Level Ventilation in ASHRAE 62.1-2004 & 2007 After choosing the ASHRAE ventilation Standard, HAP defaults to the specific Space Usage options and associated OA requirements that comply with that Standard. For example in Figure C-4, the Space Usage options displayed in the Space Properties input screen reflect specific values from ASHRAE Standard 62.1-2007. The note at the bottom of the Space Properties form serves as a reminder of the chosen ventilation standard. Figure C-4 HAP Space Properties Input Screen (General Tab) ASHRAE Standard 62.1-2004 revised the outdoor air requirements for various types of space usages. The Standard also completely overhauled the methods for determining minimum outdoor air airflow rates. Figure C-5 shows a partial table of minimum ventilation rates at the breathing zone for different occupancy categories. Let us examine the differences between Standard 622001 and Standard 62.1-2004/7. Figure C-5: Minimum Ventilation Rates ASHRAE 62.1-2004 Energy Simulation for Commercial Buildings Page ‐ 171 - [ENERGY SIMULATION] 2015 June 22 Space Usage Comparisons and Two-Part OA Requirement ASHRAE 62.1-2004/7 determines the total outdoor airflow rate for the system using the Ventilation Rate Procedure from Section 6.2 and Appendix A in the Standard. This procedure involves a two-part OA requirement. The first part determines CO2 generated pollutants or odors based on number of occupants. The second part determines pollutants generated by building materials and VOC in the space based on square feet floor area. In contrast, Standard 62-2001 requires just a one-part OA requirement as shown below. Differences exist in the space usage categories between the two Standards. Figures C-6 and C-7 offer visual comparisons between Standard 62-2001 and 62.1-2004/7 for Retail and Education space usage categories. ASHRAE 62-2001 ASHRAE 62.1-2004/2007 Figure C-6: RETAIL Space Usage Comparison Energy Simulation for Commercial Buildings Page ‐ 172 - 2015 June 22 [ENERGY SIMULATION] Figure C-7 below shows space usage comparisons in the EDUCATION category. Notice the quantity of space usage choices remained the same, but space usage names differ in Standard 62.1-2004/7 vs. 62-2001. ASHRAE 62-2001 ASHRAE 62.1-2004 Figure C-7: EDUCATION Space Usage Comparison Energy Simulation for Commercial Buildings Page ‐ 173 - [ENERGY SIMULATION] 2015 June 22 The procedure for calculating space and project level ventilation airflow in Standard 62.1-2004/7 involves two (2) major steps. The first major step considers the following three (3) steps in determining total space ventilation rates: Summing the CFM/person and CFM/ft² requirements as discussed above. Applying time averaging to space occupancy. Utilizing space air distribution effectiveness. The second major step determines how much outdoor ventilation air the central system intake requires in ensuring each space receives the required ventilation. As we will see, the ventilation airflow required at the intake can be larger than the sum of the uncorrected space OA airflows. The second item determined in step two (2) is the final total ventilation requirement at the air intake using the calculated system ventilation efficiency. Before we continue, we should clarify some terminology between HAP and ASHRAE. ASHRAE Standard 62.1-2004/7 uses “zone” to refer to what HAP identifies as a "space". To avoid confusion, this discussion adopts the HAP terminology. For example and clarity, later in this discussion the Standard refers to "zone ventilation efficiency" to which HAP refers as "space ventilation efficiency". Step 1: Determining the Space Level Minimum Ventilation Requirements 1. Summing the OA Requirements During sizing calculations for Standard 62.1-2004/7, HAP first sums the two OA requirements. However, at this point in the calculations we must apply the additional considerations mentioned above. For that reason it is difficult to say which Standard (62-2001 or 62.1-2004/7) requires the greater ventilation air volume before doing all the calculations. Using our 840ft² classrooms with 25 children from Figure C-7, the “uncorrected” ventilation air requirements are: Standard Space Usage Category Calculation Uncorrected Ventilation Air 62-2001 Classroom 25 15CFM/Person 375 CFM 62.1-2004 Classroom (ages 9+) 25 10CFM/Person 250 CFM + 0.12 CFM/ft² 840 ft² 101 CFM Standard 62-2001 requires 375 CFM of uncorrected ventilation air versus 351 CFM for 62.12004/7. Uncorrected means we must still apply additional considerations or “adjustments” as required by the Standard. Energy Simulation for Commercial Buildings Page ‐ 174 - 2015 June 22 [ENERGY SIMULATION] 2. Calculating the Time Averaging Factor If the number of people in the space fluctuates over time, Standard 62.1-2004/7 allows estimating the space population by applying a time averaging procedure. HAP applies the user’s fractional people schedule along with the equations in paragraph 6.2.6.2 of ASHRAE Standard 62.1-2004/7 to produce a “time averaging interval”. The interval length is a function of the ventilation air change for the space. HAP uses the calculated average occupant values for this interval and uses the largest average value in determining the time averaging factor. HAP uses this factor to correct the OA per person ventilation amount. For example, suppose a 2000ft² space with floor to ceiling height of 9 ft. has 10 occupants. The requirements for this space are 5 CFM/person and 0.06 CFM/ft². Using 10 occupants and 2000 ft², the uncorrected outdoor airflow is 170 CFM. The time averaging interval equation from the Standard is 3 x Space Volume / uncorrected outdoor airflow, which equals 318 minutes or 5.3 hours. HAP rounds this to 5 hours. Next, HAP calculates an average schedule factor for each group of five (5) consecutive hours in the people design day schedule. First HAP uses hours 0000 thru 0400, then 0100 thru 0500, then 0200 thru 0600, etc. If the schedule values for five consecutive hours are 60%, 80%, 100%, 100% and 100%, the average for this block is 88%. Once HAP calculates these averages for each 5-hour block in the day, HAP uses the largest average as the Time Averaging Factor. In this case, since the largest 5-hour time averaged occupancy is 88% means the people count is 0.88 X 10 = 9 occupants. If we take 5 CFM/person X 9 people, we have 45 CFM versus 50 CFM as initially determined, resulting in a reduction of 5 CFM for the space and 165 CFM instead of 170 CFM as the sum of the 2-part OA requirement. If the people schedule uses 100% for all hours, the Time Averaging Factor is 100%. Also, note HAP uses only CFM/person and CFM/ft² airflow requirements for this calculation. If you have specified a total airflow (CFM) or "% of supply airflow" ventilation requirement for the space, HAP does not consider these values in the calculation as they are outside the scope of the Standard 62.1-2004/7 Ventilation Rate procedure. The time averaging factor does not always result in a downward correction of the people occupancy and an associated decrease in ventilation airflow. It depends on the space volume, people occupancy, and profile. For example, the 840ft² classroom with 25 occupants, requires 10 CFM/person and 0.12 CFM/ft² resulting in 351 CFM uncorrected outdoor airflow. The time averaging interval from the ASHRAE equation is 3 x Space Volume / 351 CFM, which equals 60 minutes or 1 hour. In this example, the program calculates an average schedule factor for each one consecutive hour. The largest one-hour “average” in this case is 100%, so for this classroom there is no change to the original uncorrected ventilation airflow based on the time averaging factor. Energy Simulation for Commercial Buildings Figure C-8 People Profile For Classroom Page ‐ 175 - [ENERGY SIMULATION] 2015 June 22 3. Assigning Space Air Distribution Effectiveness The next consideration affecting the required space outdoor airflow amount involves the air delivery from the diffusers. The Air Distribution Effectiveness is a new concept in ASHRAE 62.12004. It is not enough to deliver ventilation air to a space, that air must also effectively reach the breathing zone of its occupants. Standard 62.1-2004/7 state, “A system that is effective at delivering air to the breathing zone requires less outdoor airflow than a less effective one for the same space”. The Standard defines the breathing zone as the area between 3 in and 72 in above the floor as shown in Figure C-9. When supply air is delivered anywhere above the breathing zone, it is considered to be the same as ceiling delivery. Since different types of systems and air terminals are more or less effective at delivering ventilation air to this breathing zone, HAP considers the effectiveness of the air distribution system in calculating ventilation requirements. Most cooling applications deliver the air through ceiling diffusers thus using an effectiveness value of 1.0. If cooling sidewall supply registers are more than 72 inches above the floor, HAP considers them the same as "ceiling supply" with an effectiveness value of 1.0. Figure C-9 Space Air Distribution Effectiveness Per ASHRAE 62.1-2004/7, systems that deliver warm air from a ceiling supply diffuser, and have supply air 15 °F above room air temperature, have an effectiveness of 0.8. Warm air supplied from a ceiling diffuser, with a temperature <5 °F above room air temperature have an effectiveness of 1.0. HAP performs the Standard 62.1-2004/7 calculations twice for each system if the system provides cooling and heating. It performs it once assuming cooling operation and again for heating operation. HAP uses the larger system ventilation airflow as the result. If heating duty results in a larger ventilation airflow, then the space air distribution effectiveness HAP uses is 0.8 (reflecting warm air supply typically 15 °F above room temperature) for all spaces in the system. Energy Simulation for Commercial Buildings Page ‐ 176 - 2015 June 22 [ENERGY SIMULATION] The outdoor air amount for the space calculation is found by dividing the uncorrected airflow by the space air distribution effectiveness, which occurs after the time averaging correction. Standard 62.1-2004/7 refers to answer as "zone outdoor airflow" after considering the space air distribution effectiveness. Step 2: Determining the System Level Minimum Ventilation Requirements Step 2 determines how much outdoor ventilation air is required at the common OA intake to ensure that each space receives its required ventilation. As we will see, the ventilation airflow required at the intake can be larger than the sum of the uncorrected space airflows due to issues related to the “critical space”. Determination of the OA amount at the unit intake also involves calculation of a space and system “ventilation efficiency” value per equations in ASHRAE 62.1-2004/7. This section develops the procedures for system level ventilation calculations, but there is also considerable discussion involving spaces. "Critical Space" involves a concept that meeting the ventilation requirements of one space may require over ventilating other spaces. The example in Figure C-10 supposes space “A” requires a total of 800 CFM supply air, which includes 200 CFM of outside air, or 25% of supply. Space "B" requires a total of 600 CFM supply air, which includes 300 CFM of outside air, or 50% of supply. Both spaces receive supply air from the same RTU. If that RTU total supply air contains 25% ventilation air, the ventilation requirement of Space “A” are met, but does not meet the ventilation requirement of Space “B”. The outdoor air fraction defines ventilation air as a percentage of supply air to the space, the higher the fraction, the more critical the space tends to be. Figure C-10 Typical VAV System and Critical Space OA SA The common supply air must contain more than 25% outdoor air in order to meet Space “B” requirements resulting in over ventilating of Space “A”. However, once Space “A” is over ventilated, there is unused or "unvitiated" ventilation air that re-circulates from Space “A” which Energy Simulation for Commercial Buildings Page ‐ 177 - [ENERGY SIMULATION] 2015 June 22 moderates the need to increase the ventilation rate to 50% of supply air. In this example, Space “B” is the critical space, as it requires a greater outdoor air fraction than any other space. The Critical Space concept existed in ASHRAE 62-2001 but the mathematics for handling it are different because in Standard 62.1-2004/7 a new term called “ventilation efficiency” is calculated and taken into account. The Standard defines a complex calculation procedure that HAP follows to determine the ventilation efficiency for each space. This calculation procedure is different depending on the system type. A dual duct or recirculation system like fan powered VAV boxes requires a more involved calculation. There is a relationship between percent OA for the space and the ventilation efficiency that HAP takes into account using the equation in ASHRAE 62.1-2004/7. The bottom line is that the procedure for finding the critical space as defined by ASHRAE 62.1-2004/7, is complex and system dependent. Both the percent of outdoor air to supply air for the space and the percent of outdoor air for the system are considered. The larger this difference, the smaller the space ventilation efficiency and the more likely the space is critical. This difference tends to get larger when a pace has a higher percent of outdoor air to supply air. The “critical” space for a system is the one having the lowest ventilation efficiency. For example, if a space requires 200 CFM of outdoor air and has a ventilation efficiency of 0.75, 200/0.75 requires 267 CFM of outdoor be introduced at the system intake to ensure that the space receives its 200 CFM of outdoor air. Therefore, the space with the lowest ventilation efficiency dictates the overall outdoor airflow for the system since it requires the largest amount of over ventilation of other spaces to ensure it receives its required airflow. HAP uses the critical “space” ventilation efficiency as the “system” ventilation efficiency thus enabling the calculation of design ventilation rate for the central system. The Standard refers to this value as "outdoor air intake." In the HAP Ventilation Sizing Summary Report, this outdoor air intake is the same as the Design Ventilation Airflow Rate in the case of the VAV system example. HAP calculates this by dividing the Uncorrected Outdoor Airflow by the System Ventilation Efficiency. Note: A dedicated OA system providing 100% outdoor air to all spaces, as shown below, sums the ventilation values for all spaces in the system and uses that sum as the total system ventilation airflow. The required air for each space is set at the diffuser and sizes the 100% OA unit for the sum. There is no “critical space” calculation required. Figure C-11 No Critical Space Issues with Dedicated OA Unit Energy Simulation for Commercial Buildings Page ‐ 178 - 2015 June 22 [ENERGY SIMULATION] Ventilation Sizing Summary Report The last section of this discussion uses the preceding information to interpret the output data from the Ventilation Sizing Summary Report in HAP. The example system is a 7-zone VAV system supplying multiple classroom spaces, small computer lab, corridor and vestibule using the ASHRAE 62.1-2004/7 ventilation procedures. The total cooling coil load for this 7-zone system is 26.4 tons occurring at August 1500 as shown below. This reflects a Design Ventilation Airflow Rate calculated by HAP based on ASHRAE 62.12004/7 requirements of 2547 CFM. Notice the Design Condition for ventilation air is at the “minimum flow (heating)”. As discussed previously, because this is a cooling and heating system, HAP does the Standard 62.1-2004/7 ventilation air calculation once for cooling and once for heating and uses the higher of the two values. In this example, heating duty was higher because the heating duty air distribution effectiveness was lower (0.80) than cooling duty (1.0) which results in 25% more ventilation air requirement to each space during the heating cycle. Figure C-12 Ventilation Report for VAV System The following discussion explains the column headings of the Ventilation Sizing Summary Report for our VAV system. Refer to Figure C-12. Energy Simulation for Commercial Buildings Page ‐ 179 - 2015 June 22 [ENERGY SIMULATION] Minimum Supply Air (CFM) This value represents the minimum supply airflow (not just the outdoor airflow) for the VAV terminal for each space. In the HAP Air System Properties under the Zone Components tab/ Supply Terminals/ Minimum Airflow, we defined the minimum supply airflow at 50% of the supply terminal airflow. Notice in this example the Design Ventilation Airflow is less than the Minimum Supply Air CFM. HAP automatically increases (overrides) the minimum Zone supply airflow when the users’ input value for minimum zone airflow does not achieve the minimum required ventilation. As an added note, this column heading only appears for VAV. For a CAV system, the column heading is “Maximum Supply Air (CFM)” because a CAV system diffuser has no minimum airflow set-point like a VAV terminal. Floor Area (sq ft) This is the space floor area used in the uncorrected ventilation airflow calculation based on CFM/Ft². Required Outdoor Air (CFM/Ft²) This represents the part two value for the OA requirement based on Space Usage in ASHRAE 62.1-2004/7. Time Averaged Occupancy This value represents the number of occupants used in the final calculations for ventilation air. HAP accounts for any headcount reductions based on the time averaging factor calculations discussed earlier. Required Outdoor Air (CFM/Person) This represents the part one value for the OA requirement based on Space Usage in ASHRAE 62.1-2004/7. Air Distribution Effectiveness This value takes into consideration the ability of the supply air from the diffusers or registers to reach the breathing zone of its occupants effectively. Our case used 0.80 because heating duty ventilation airflow (0.80 effectiveness) exceeded cooling duty ventilation airflow (1.0 effectiveness). Required Outdoor Air (CFM) This column contains the calculated outdoor air quantities after taking into account the air distribution effectiveness. The uncorrected outdoor air CFM divided by the air distribution effectiveness is the required outdoor air CFM for each space. This is not the final airflow for the common OA intake for the system. Uncorrected Outdoor Air (CFM) This column contains the part one and two outdoor air quantities before taking into account the air distribution effectiveness and critical space issues after considering the time averaging factor for occupancy. Energy Simulation for Commercial Buildings Page ‐ 180 - 2015 June 22 [ENERGY SIMULATION] Space Ventilation Efficiency HAP uses space ventilation efficiency in identifying the critical space in the system. The space with the lowest ventilation efficiency is the most critical therefore it dictates the outdoor airflow for the system to ensure it receives its required airflow. The Uncorrected Outdoor Air (1760) divided by the lowest Space Ventilation Efficiency (.691) value is the final answer called Design Ventilation Airflow Rate (2547).The Space Ventilation Efficiency is calculated by HAP using the procedures in Appendix A of the Standard, as opposed to using the more simplified method in table 6-2 of the Standard. This results in the highest level of accuracy. Conclusion ASHRAE Standard 62.1-2004/2007 requires HVAC systems to bring in outdoor air at specified minimum ventilation rates that will be acceptable to human occupants to minimize the potential for adverse health effects. Determining the ventilation airflow for each space involves summing a two-part OA requirement then applying a time averaging factor that adjusts for occupant fluctuation in the space. Differences exist in the space usage choices between Standard 62-2001 and standard 62.12004/2007. Next HAP considers the ability of the cooling/heating system to deliver air to the breathing zone per standard 62.1-2004/2007. The effectiveness value represents the required increase for space ventilation airflow to compensate for a less effective air delivery. Then HAP uses ASHRAE 62.1-2004/2007 equations in determining ventilation requirements for the central system intake to ensure each space receives its required ventilation. This process involves finding the critical space. The critical space is the one that exhibits the lowest ventilation efficiency and dictates the overall outdoor airflow for the system. The purpose of ASHRAE 62.1-2004/2007 is to specify minimum ventilation rates to help achieve acceptable indoor air quality through constant dilution using outdoor air. ASHRAE considers these minimums as good design practice for achieving acceptable indoor air quality. Energy Simulation for Commercial Buildings Page ‐ 181 - 2015 June 22 [ENERGY SIMULATION] System Based Design Load Calculations In HAP, two of the important concepts in design load calculations involve the use of the ASHRAE heat extraction method and "system-based" sizing techniques. Both are concepts that have been used since HAP 3.0, but it is useful to review them since it is important to understand the principles and procedures involved as well as their effects on results. In this article the system sizing procedures used in HAP will be explained with emphasis on the roles heat extraction calculations and system-based sizing play. Definitions. Before beginning, it will be useful to provide brief definitions of heat extraction and system-based sizing: Heat Extraction Procedures represent the second part of the two-step ASHRAEendorsed transfer function load method. The first part is the basic transfer function calculation, which accounts for the transient nature of the processes that convert heat gains to cooling loads. Heat gains usually do not instantly become cooling loads, but rather involve a time delay due to heat storage. However, the loads calculated with the basic transfer function equations are based on the idealized assumption of a constant room temperature 24 hours per day. Heat extraction procedures are used to take the calculation one step further considering the effect of varying zone temperatures during the day (such as set-up or shutdown periods at night) and how air-conditioning systems and thermostat controls respond to load conditions. The most compelling reason to include heat extraction in design calculations is that they provide a way to obtain realistic, accurate estimates of pull-down loads. System-Based Design considers system specifics when sizing systems. Many load estimating programs deal with systems in a generic manner. Thermostat set-points, supply air controls and fan characteristics are specified without being associated with a specific system control such as variable air volume (VAV) or constant air volume (CAV). However, different sizing procedures are needed for VAV and CAV. With a generic approach, it is up to the user to decide how to use program outputs to size a specific type of system. With HAP, sizing calculations and outputs are tailored to the system type specified by the user, thus making the results more accurate and easier to use. Sizing Overview. In HAP, sizing calculations are performed for all system types using the following three-step procedure: Size Zone Airflows. Zones are dealt with separately to determine peak sensible loads and required airflow rates. Size Supply Fan Airflow. Zone airflow requirements are then combined to determine the maximum supply fan airflow requirement. Size Coils. Given user specifications of air system characteristics plus the calculated zone and fan sizing data, the program simulates operation of the system for design cooling conditions each month. A simulation is also performed for the design heating condition. Coil loads resulting from these simulations are inspected to identify the maximum load for each coil in the system. These are reported on program outputs. In the paragraphs below, each of these steps are discussed in detail. Energy Simulation for Commercial Buildings Page ‐ 182 - 2015 June 22 [ENERGY SIMULATION] Step 1: Zone Airflow Sizing. The goal of this step is to identify the maximum sensible load and maximum airflow rate for each zone in the system. To do this the program deals with each zone separately. Using space and zone input data and ASHRAE transfer function procedures; the program calculates heat gains for all heat sources in a zone and converts the heat gains to "cooling loads". Per ASHRAE procedures, these cooling loads are based on the assumption that cooling equipment operates 24 hours per day and that the zone is maintained exactly at the cooling thermostat set-point. Thus, these cooling loads are idealized unless the system will actually operate this way. This simplifying assumption will be compensated for later during the coil simulations using the heat extraction procedure. After calculating loads for all design cooling months specified, the program searches the data to identify the maximum zone sensible cooling load. For a given supply air temperature, the program calculates the required airflow rate to satisfy this load. Results of the zone airflow sizing analysis appear on the Zone Sizing Summary report. Zone sensible loads from this analysis also appear on the Air System Design Load Summary, Zone Design Load Summary and Hourly Zone Design Day Loads reports. On these reports, the cooling loads are interchangeably referred to as "zone load" and "zone sensible.” Step 2: Fan Airflow Sizing. The goal of this sizing step is to determine the maximum airflow requirement for the central supply fan. This is the first calculation in which system-based sizing is involved. For a CAV system, the program adds peak CFMs (L/s) for all zones to determine the required supply fan airflow. For VAV systems, the program identifies the peak coincident CFM (L/s). This is done by first using zone sensible load data from the previous step to determine require airflow rates for each hour of the day. Hourly airflow requirements for each zone are then added together to build a fan airflow profile. Finally, the program searches this profile to find the maximum airflow rate. Figure D-1 VAV System Airflow Rates Energy Simulation for Commercial Buildings Page ‐ 183 - 2015 June 22 [ENERGY SIMULATION] Figure D-1 illustrates this calculation for a VAV system. Zone airflow rates are shown in this figure for an east-facing zone and a west-facing zone. For each hour, the sum of east and west zone airflow rates is the required fan airflow rate. In Figure 1, the east zone peaks at 0900 with a 6252 CFM (2950 L/s) requirement, the west zone peaks at 1700 with a 6989 CFM (3298 L/s) requirement, and the supply fan peaks at 1600 with a 10213 CFM (4820 L/s) requirement. Note that this VAV fan airflow is 23% less than the 13241 CFM (6248 L/s) that would be required for a CAV system. Because a VAV system can take advantage of load diversity, its design airflow can often be less than the sum of peak zone CFMs (L/s). When a VAV air system is specified in HAP, the system-based sizing procedure automatically considers this. Step 3: Coil Sizing Calculations. The goal of the final sizing step is to determine maximum loads for all coils in the air system. Performing detailed simulations of air system operation for each design cooling month and the design heating condition does this. Air system input data, the airflow rates and zone sensible load profiles calculated in steps 1 and 2, and ASHRAE heat extraction procedures are used to perform these simulations. Simulations are specific to the type of system being dealt with and consider all system components and controls specified. The zone sensible load profiles calculated in step 1 are the basis for system simulations. As noted earlier, these load profiles were calculated assuming 24-hour equipment operation and a constant zone temperature equal to the occupied cooling thermostat set-point. Consequently, these load profiles must be adjusted using the ASHRAE heat extraction equations if cooling equipment is operated for less than 24 hours, if an unoccupied period set-up temperature is used, if cooling equipment is shut down during the unoccupied period and if a thermostat throttling range other than 0º F (-17.8º C) is used. The heat extraction calculations yield the amount of heat the air conditioning system must remove each hour to maintain the zone in the thermostat throttling range. Once zone heat extraction rates have been computed, this data serves as the basis for calculations of airflow rates, temperatures and humidity at all points in the air system. Finally, these results allow loads for coils in the system to be determined. For example, the cooling coil inlet and outlet dry-bulb temperatures and the coil airflow rate are used to calculate the sensible coil load. Figure D-2 provides sample results from a design simulation for a single-zone CAV air system. The figure provides a useful comparison between zone sensible loads, heat extraction rates (called "zone conditioning") and sensible and total cooling coil loads. The "zone sensible" load profile represents sensible cooling loads assuming 24-hour equipment operation and a constant 75º F (23.9º C) zone air temperature. The "zone conditioning" profile represents heat extracted from the zone during the 6am-7pm operating period (from 8pm to 5am the cooling system is off). During this operating cycle, the zone air temperature varies within in the 75º F (23.9º C) - 78º F (25.5º C) throttling range during the 6am-7pm operating period, and floats at higher temperatures during the nighttime shutdown period. Heat extraction method estimates of zone air temperature are shown in Figure D-3. As a result of this behavior, extra load is imposed on the air conditioning equipment to pull down the zone air temperature and to remove heat that has accumulated in the building mass during the nighttime period. This pulldown load is the principal reason for differences between the zone sensible and zone conditioning profiles in Figure D-2. Note that these differences are most significant at the start of the operating period, but also continue throughout the 13-hour operating period. The coil sensible profile in Figure D-2 represents the sensible heat that must be removed at the central cooling coil. In addition to providing enough sensible cooling to meet zone-conditioning demands, the coil must also provide cooling to offset fan heat gain, sensible ventilation load and the portion of plenum heat gains that returns to the coil. These factors cause the coil sensible profile in Figure D-2 to exceed than the zone conditioning profile for all hours. Finally, the total coil load profile in Figure D-2 represents total heat removal at the cooling coil. The difference between the total and sensible coil profiles is the latent cooling provided by the coil. Energy Simulation for Commercial Buildings Page ‐ 184 - 2015 June 22 [ENERGY SIMULATION] Figure D-2 Zone and Coil Load Profiles Results from the coil sizing analysis are reported on the Air System Sizing Summary. Zone conditioning and coil load data are also provided on the Air System Design Load Summary and Hourly Air System Design Day Loads reports. Zone temperatures and zone conditioning are listed on Hourly Zone Design Day Loads reports. Implication: Performance-Based Coil Estimate. While it is useful to understand the sizing procedures used in HAP, it is even more important to recognize the implications of the procedures. The most significant of these is that the system simulation technique used yields a "performance-based" estimate of peak coil loads. By this, we mean that the calculation considers all system controls and operating variables. Perhaps most important among these is the variation of zone temperature. As noted earlier, zone temperature will vary during the unoccupied set-up or shutdown period, and within the thermostat throttling range during the occupied period. In Figure D-3, for example, zone temperatures lie toward the upper end of the 3º F (-16.1ºC) thermostat throttling range during the 13-hour occupied operating period. This is not necessarily always the case. If unoccupied cooling at a set-up temperature was provided, or 24-hour cooling was provided, the pull-down load component would be less severe or eliminated altogether and zone temperatures would tend to lie closer to the bottom of the throttling range. These temperature variations may or may not be desired by the designer. On one hand, some designers wish to consider actual operating characteristics in the calculation, including zone Energy Simulation for Commercial Buildings Page ‐ 185 - 2015 June 22 [ENERGY SIMULATION] temperature variations, and are therefore comfortable with a performance-based calculation. Others may want to use idealized conditions with the zone temperature fixed exactly at a single set-point temperature. Figure D-3 Zone Air Temperature Profile Energy Simulation for Commercial Buildings Page ‐ 186 - [ENERGY SIMULATION] 2015 June 22 Figure D-4 Loads for Varied Throttling Ranges Figure D-5 Zone Temperatures for Varied Throttling Ranges Energy Simulation for Commercial Buildings Page ‐ 187 - 2015 June 22 [ENERGY SIMULATION] While the performance-based nature of the coil simulations cannot be eliminated completely, using a throttling range of 0.1ºF (-17.7ºC) can minimize it. Note that a finite throttling range is required by the heat extraction method. Without it, the analysis cannot be performed and pulldown loads cannot be computed; 0.1ºF (-17.7ºC) is the minimum allowed by the program. Using this throttling range will have an effect both on the zone conditioning and cooling coil loads calculated, as well as the estimates of zone temperatures. Results from the single-zone CAV example for both 3 F (-16.1ºC) and 0.1ºF (-17.7ºC) throttling ranges are shown in Figures D-4 and D-5. Use of the 0.1ºF (-17.7ºC) throttling range results in a peak cooling coil load that is 4% larger than the 3ºF (-16.1ºC) throttling range case. It also results in estimated zone temperatures closer to the 75ºF (23.9ºC) cooling set-point as shown in Figure D-5. Thus, system based design using the heat extraction method offers powerful, sophisticated capabilities to user. But to successfully use the heat extraction method, a designer must understand the procedure and its implications. Energy Simulation for Commercial Buildings Page ‐ 188 - 2015 June 22 [ENERGY SIMULATION] Appendix “C” Technical White Papers Energy Simulation for Commercial Buildings Page ‐ 189 - 2015 June 22 [ENERGY SIMULATION] Introduction In 1993 Carrier incorporated system-based design features in its Hourly Analysis Program (HAP) software. At the time, system-based design was a new concept that allowed the computer to do a more complete and accurate job of sizing equipment than the traditional load estimating approach. Ten years later, this approach still yields significant benefits to HVAC system designers because of the productivity advantage it offers. And even today it still serves to differentiate HAP from other load estimating and system design software on the market. This paper explains system-based design and its benefits. First the paper discusses how traditional system design methods work and the shortcomings of the traditional approach. Next, the concept of system-based design is explained, and the benefits it offers are explored. How Traditional System Design Methods Work Many computer programs used for HVAC system design are based on a traditional approach that manual methods use. First, the engineer inputs weather data, information about the building construction, internal loads and layout, and HVAC sizing parameters. The latter includes such things as thermostat set-points, the required supply temperature and the required outdoor air ventilation rate. Using this data the program then: Computes zone sensible cooling loads for all zones for a series of design cooling months. Identifies the maximum zone sensible load for each zone in order to calculate required zone airflow rates and the required supply fan airflow rate. Calculates central cooling coil loads for the months being considered in order to identify the maximum cooling coil load. If the system also provides heating, calculations are performed to determine the maximum heating coil load. This procedure yields data useful for sizing terminal diffusers, the supply fan, the central cooling coil, and the central heating coil. Shortcomings of the Traditional Approach It is important to note the traditional approach does not explicitly consider the type of HVAC system being designed. This approach is acceptable when designing simple CAV or VAV systems. However, when an HVAC system with special features, components or aspects of operation is involved, the traditional approach has two important flaws. First, it leaves a gap between what the engineer needs to design the system fully, and what the program provides as sizing data. Different types of HVAC systems contain different components which each need to be sized. Further, different types of HVAC systems require different sizing procedures. Therefore defining the system type is necessary to determine the components to be sized and the procedures to be used. The following examples illustrate this point: A single zone CAV system requires that the supply diffusers, supply fan and the central cooling and heating coils be sized. The supply fan airflow is equal to the required airflow for the single zone. A VAV Reheat system serving multiple zones requires that supply diffusers, the supply fan, the central cooling coil and the terminal reheat coils be sized. The supply fan is sized for the Energy Simulation for Commercial Buildings Page ‐ 190 - 2015 June 22 [ENERGY SIMULATION] diversified peak airflow to zones, rather than the sum of zone airflows. The terminal reheat coils are sized using a procedure that is different from sizing a central heating coil. A VAV Fan Powered Mixing Box system serving multiple zones requires that supply diffusers, mixing box terminals, the supply fan and the central cooling coil be sized. Unlike other systems, the terminal equipment for this system includes both a fan and a reheat coil, both of which must be sized. Sizing procedures differ slightly depending on whether a series mixing box or parallel mixing box terminal is used. A 2-Fan Dual Duct VAV system serving multiple zones requires that supply diffusers, mixing box terminals, the cold deck supply fan, the hot deck supply fan, the cold deck cooling coil and the hot deck heating coil all be sized. This system contains a unique configuration of components not found in other systems. Procedures tailored to this type of system must be used to properly size the equipment. The second problem with the traditional approach involves accuracy. If the traditional approach is used to size a system such as series Fan-Powered Mixing Box or 2-Fan Dual Duct, additional hand calculations will be required to size components not addressed by the calculation. These additional hand calculations make the design more difficult, more time consuming and prone to error. In more complex situations, sizing is often approximated to save time. Thus, the traditional approach plus hand calculations is often less accurate than a computerized approach that considers system type and does a complete job. System-Based Design and How It Works The system-based design approach considers the unique features of the HVAC system being designed and then tailors the load estimating and sizing procedures to that system. It can therefore provide specific, accurate sizing information for each component of the system. If a Series Fan Powered Mixing Box system is being designed, for example, the system-based approach will provide the information necessary to size the terminal mixing boxes, their fans and heating coils. It will also consider the special operating features of the system to determine accurate primary supply fan and primary cooling coil sizes. In this way sizing methods and output data are customized to each specific system type. By providing system-specific sizing data, the system-based design approach can bridge the gap between what an engineer needs and what a computerized system design program provides. How It Works. The information a designer must supply to initiate the design process is similar to the traditional approach. The engineer must: Input weather data. Input building construction, internal heat gain and layout information. Define the HVAC system. In addition to thermostat set-points and sizing criteria, the engineer specifies exactly what type of HVAC system is involved and its attributes. For example, it could be VAV Reheat, VAV with baseboard heat, Series Fan Powered Mixing Box, Dual Duct VAV, etc... Next, the system-based design computer program calculates loads and sizes system components: Energy Simulation for Commercial Buildings Page ‐ 191 - 2015 June 22 [ENERGY SIMULATION] 1. Zone Load Calculation. The program first calculates hourly zone sensible cooling loads for all zones for the design cooling months being considered. 2. Zone Airflow Sizing. The program then identifies maximum zone sensible loads in order to determine required zone supply airflow rates and required central fan airflow rates. For some systems, such as fan powered mixing box systems, special aspects of system operation may influence the required airflow rates. 3. System Simulation. Once system airflows have been determined, the program simulates the hour-by-hour operation of the HVAC system and all its components to determine loads for all coils in the system. This mathematical simulation considers the interplay of component operation for the specific system being studied. Simulations are performed for the range of design cooling months specified by the designer and for the heating design condition. 4. Coil Sizing. Finally, the program searches results of system simulation to determine maximum required size for each component coil in the system. Benefits of System-Based Design The major benefit of the system-based design approach, of course, is that it gives the engineer exactly what is needed to design a system. Specific sizing data is provided instead of raw material for further hand calculations. The result is increased productivity for the designer because the computer is being put to work more effectively. The computer does a complete job of system sizing, not a partial job. A related benefit is that the system-based approach does a more accurate and therefore reliable job of generating sizing data. This is because sizing calculations consider the specific operating nature of the system, not the features of a simple, generic system. Further, the approach can evaluate more operating conditions than can be checked by hand, so that the approach is more thorough and comprehensive. Finally, because detailed, dynamic system simulations are part of this approach, the method can potentially be used to investigate the effect on sizing of such devices and controls as: Outdoor air ventilation energy recovery devices. Outdoor air economizers. Active dehumidification and humidification controls. Night-time free cooling controls. Previously, such controls have only been evaluated in energy analysis simulations to determine effects on operating costs. But each can also have an effect on sizing which in turn can have a significant effect the first cost of the system. Conclusion Even though the concept is no longer brand new, system-based design still represents a promising advance in the field of HVAC system design. It offers improvements in productivity and accuracy, and opens new avenues of investigation to the designer in the pursuit of the optimal design. Look for it when choosing your HVAC design tools. Energy Simulation for Commercial Buildings Page ‐ 192 - [ENERGY SIMULATION] The Benefits of 8760 Hour by Hour Building Energy Analysis Introduction As energy costs rise, building owners are becoming increasingly interested in operating costs and energy efficiency. As a result, building energy analysis (BEA) is becoming an important tool in the HVAC design field. Currently many BEA tools are available to engineers. Most are in the form of computer programs and employ a variety of methods with different benefits. Among these, BEA tools such as Carrier's HAP program that use the 8760 hour-by-hour method can offer the greatest benefits because they yield highly accurate, sophisticated system comparisons. This article will discuss the benefits of 8760 hour building energy analysis by first explaining the basics of building energy analysis and the requirements for high quality BEA system comparisons. Then, major BEA methods will be evaluated with special emphasis on the benefits of 8760 hour-by-hour versus reduced hour-by-hour methods. What Is Building Energy Analysis? Building energy analysis is the technique of estimating energy use and operating costs for a building and its energy consuming systems. In our industry, particular emphasis is placed on the energy use of a building's HVAC systems. The purpose of BEA is to compare the energy use and operating costs of alternate system designs in order to choose the optimal design. The analysis mathematically simulates the thermal performance of the building to determine cooling and heating loads. It then mathematically simulates the performance of HVAC equipment in response to these loads to determine energy use over the course of a year. Finally, energy data is used to calculate operating costs. Requirements for High Quality Results. Successful building energy analysis relies on considering as many of the physical factors influencing building loads and equipment performance as possible. The ultimate result of the analysis is a predicted operating cost. An accurate cost prediction relies on energy use data, which in turn relies on equipment simulations, which must be based on building load predictions, all of which must be accurate. Concisely stated, high quality results can be obtained when the analysis considers: 1. The Range and Timing of Weather Conditions. Varying levels of temperature, humidity and solar radiation during the year influence building loads and equipment performance. In each geographical location conditions range from hot to cold, wet to dry and sunny to cloudy in different ways. Considering the actual ranges of these conditions and when they occur on a daily, monthly and yearly basis is crucial to producing accurate energy use results. 2. The Hourly and Daily Variation in Internal Loads. Patterns of building use involving occupancy, lighting and equipment operation can change significantly from one day to the next. Considering these use patterns in their correct day-to-day sequence is important in generating accurate load data. 3. The Dynamic Nature of Building Heat Transfer. The process of converting heat gains and losses to cooling and heating loads is a transient rather than a steady-state process. Heat gains occurring during one hour often affect loads over a number of succeeding hours. Consequently, it is important to consider accurate sequences of heat gains occurring during the day. In addition, because weather conditions and building use profiles vary from day to day, sequences of heat gains can affect loads from one day to the next. Energy Simulation for Commercial Buildings Page ‐ 193 - 2015 June 22 [ENERGY SIMULATION] 4. The Response and Performance of HVAC Equipment. How controls, systems and equipment respond to demands for cooling and heating in a building, and the factors that affect part-load performance of the equipment must be considered to yield accurate equipment energy use data. 5. The Details Of How Utilities Charge For Energy Use. Often prices for energy vary by season and time of day. Further, charges are often made for peak energy usage. As a result, the analysis must not only be able to produce accurate estimates of how much energy is used, but must also accurately determine when during the day energy is used. Evaluation of BEA Methods A wide variety of building energy analysis methods are currently available to HVAC engineers and range from simple to sophisticated. The simplest methods involve the largest number of simplifying assumptions and therefore tend to be the least accurate. The most sophisticated methods involve the fewest assumptions and thus can provide the most accurate results. Generally, BEA methods are divided into three categories: a) Single Measure Methods (example: Equivalent Full Load Hours) b) Simplified Multiple Measure Methods (example: Bin Method) c) Detailed Multiple Measure Method (example: Hour by Hour) While methods in the first two categories serve a useful role in providing quick, preliminary energy estimates, the simplifications they involve impair their accuracy. Each will be briefly discussed below. The main focus of the following discussions, however, will be the different hour by hour methods contained in the third category. Single Measure Methods These methods involve one calculation of annual or seasonal energy use. The Degree-Day Method, for example, computes energy use by combining one degree-day weather value with a load value and an efficiency value to obtain seasonal or annual energy use. Similarly, the Equivalent Full Load Hour Method combines full load capacity, full load efficiency and equivalent full load hours to obtain annual energy use. In both cases, this level of simplicity is achieved by using such sweeping assumptions that the accuracy and reliability of these methods are very limited. Simplified Multiple Measure Methods These methods involve calculations of energy use at several different conditions. With the Bin Method, for example, energy use is computed at a series of outdoor air dry-bulb conditions. Results are then weighted according to the number of hours each dry-bulb condition is expected to occur to determine annual energy use. For example, the temperature 47ºF would be used to represent the range of conditions between 45ºF and 50ºF, referred to as a "bin". Building loads and equipment energy use would first be calculated for the 47ºF bin. Next, energy results would be multiplied the number of hours per year temperatures are expected to occur between 45ºF and 50ºF to determine annual energy use for that bin. Similar calculations would then be repeated for all other temperature bins for the local climate and would be summed to determine overall annual energy use. While the Bin Method provides a vast improvement in sophistication over single measure methods, it has a fatal flaw. This flaw is that it must decouple weather conditions, loads and system operation from time. For example, hours in the 47ºF bin, when the outdoor dry-bulb is Energy Simulation for Commercial Buildings Page ‐ 194 - 2015 June 22 [ENERGY SIMULATION] between 45ºF and 50ºF, occur at a variety of times of day and night, days of the week and months of the year. Because a single calculation is performed to represent energy use for all these different times it is difficult or even impossible to accurately: a) b) c) d) Link solar radiation and humidity conditions to the bin. Consider hourly and daily variations in internal loads. Consider the transient hour to hour and day to day thermal performance of the building. Predict time-of-day energy use and peak demands. Inevitably averaging assumptions must be made to shoehorn all these considerations into the framework of the bin analysis. And these assumptions impair accuracy. While the Bin Method is useful for simple, preliminary estimates of energy use and operating cost, it cannot provide the level of accuracy and sophistication offered by the detailed multiple measure methods. Detailed Multiple Measure Methods These methods perform energy calculations on an hour-by-hour basis. As a result, they have the potential to satisfy all the requirements listed earlier for high quality energy analysis results. There is, however, a certain amount of variation among different detailed multiple measure methods, leading some methods to meet the accuracy requirements better than others. Within the detailed multiple measure category are two major sub-categories worth discussing: a) The Reduced Hour-By-Hour Method b) The 8760 Hour-By-Hour Method. Reduced Hour-By-Hour Method: How & Why? This method typically uses one 24-hour profile of average weather conditions per month. Energy simulations are performed for this average profile and results are then multiplied by the number of days in the month to obtain monthly energy totals. Upon this basic foundation, different reduced hour-by-hour methods make various improvements to enhance the accuracy of results: a) Some methods analyze building operation for a typical Weekday, Saturday and Sunday each month since building use profiles differ significantly between these days. One average weather profile is still used for all three typical day simulations each month. b) Some methods also analyze equipment operation for a hot and cold day each month in an attempt to improve estimates of peak electrical demand. c) Some methods simulate building operation for one 7-day week each month to try to account for day-to-day building dynamics. However, a one average weather profile is still used for all 7 days of the simulation. The fundamental principle of this method is that building and equipment performance on hotter and colder than normal days each month averages out so that monthly energy use can be accurately predicted by simulating a small group of days using average weather conditions. The method offers the benefits of reduced calculation time and more moderate demands on computer memory and hard disk storage space. Energy Simulation for Commercial Buildings Page ‐ 195 - 2015 June 22 [ENERGY SIMULATION] 8760 Hour-By-Hour Method: How and Why? This method simulates building and equipment performance for all 8,760 hours in the year using the proper sequence of days and actual weather data. No weighting of results or simplifications are necessary. The fundamental principle is that the way to produce the most accurate energy and operating cost estimates is to mimic the real-time operating experience of a building over the course of a year. All the requirements listed earlier for high quality energy analysis results can be met with this approach. The actual weather data accounts for the range and timing of weather conditions in great detail. Further, the hourly and daily variation of building occupancy, lighting and equipment use can be easily accounted for. In addition, the full year simulation tracks the dynamic hour-tohour and day-to-day thermal behavior of the building, and the response of HVAC equipment to this behavior. The ultimate result is high-quality data that can be utilized to produce accurate, detailed data about the quantity and timing of energy use. Both are requirements for accurate operating cost estimates. Comparison of Reduced and 8760 Hour-By-Hour Methods While the Reduced Hour-By-Hour method often provides accurate results, the 8760 Hour-ByHour method can consistently provide superior accuracy and reliability. Among the reasons why, five stand out: 1. Better Estimates of Monthly Energy Use. One of the flaws in the fundamental principle of the reduced hour-by-hour method is that it relies on building and HVAC system behavior being "continuous" and "linear" during the month. Often these requirements are not met and this adversely affects accuracy "Continuous" is a mathematical term that in this context refers to a consistent mode of operation (it does not refer to constant 24-hour operation of equipment). For example, during a summer month HVAC system operation is continuous when cooling is consistently done on all days whether hot, cool or average weather conditions prevail. In this situation simulation of system performance for one 24-hour average weather profile has the best chance of approximating the total energy use for a month. However, system operation is often not "continuous" during a month, especially during intermediate seasons. For example, during an autumn month, cooling may be done on warmer than average days, economizer operation may occur on average days, and heating may occur on cooler than normal days. A simulation of one average day for such a month may indicate little or no cooling and heating because it does not consider the warmer and colder than average conditions. In moderate climates this problem can become severe when the only time heating occurs is on colder than average winter days. Because only average winter weather is considered, most or all of the heating duty for the year may be missed by an average-day simulation approach. Finally, "linear" behavior is a requirement for averaging to be accurate. For example, if cooling loads are 20% larger when the temperature is 15ºF warmer than average, and 20% smaller when the temperature is 15ºF cooler than average, cooling loads are linearly proportional to outdoor temperature. Averaging of the warm day and cool day loads will result in loads similar to those produced by simulating only the average weather day. However, loads depend on more than just outdoor temperature. Solar radiation, internal loads and hour-to-hour and day-to-day dynamic behavior also affect loads and often result in non-linear behavior. Energy Simulation for Commercial Buildings Page ‐ 196 - 2015 June 22 [ENERGY SIMULATION] Another example involves cooling equipment. If equipment input kW decreases 8% for every 10% drop in part-load ratio, input kW and load are linearly proportional. If this relationship holds true, simulation of equipment performance for one average day per month has the best chance of accurately approximating equipment performance on the collection of hot, average and cool days during the month. Unfortunately, the performance of equipment is often non-linear due to partload, entering condenser temperature and other performance factors. Consequently, the accuracy of the average day approach can be degraded when equipment behavior is non-linear. The 8760-hour method avoids these problems by simulating building and equipment operation for the entire month. Actual weather data used by the simulation consists of a collection of days, all with different combinations of temperature, humidity and sunshine. Figures E-1 and E-2 provide an example of this kind of data for the month of September in Chicago. Figure E-1 demonstrates the way dry-bulb temperatures can vary during a month. The dotted lines in this figure are the upper and lower limits of the average temperature profile for the month that would be used by the reduced hour-by-hour method. Comparison of the average and actual data shows a significant number of hours outside the range of conditions considered by the average day simulation approach. Figure E-1 Chicago Weather/September Dry Bulbs Figure E-2 Chicago Weather/September Solar Likewise, Figure E-2 demonstrates the variation of solar radiation profiles during the month. The dotted line indicates the maximum solar flux in the average day profile used by the reduced hourby-hour method. Once again, there are many conditions with greater sunshine and less sunshine than considered by the average day approach. More importantly, comparison of the peaks and Energy Simulation for Commercial Buildings Page ‐ 197 - 2015 June 22 [ENERGY SIMULATION] valleys in Figures E-1 and E-2 shows that hot days are not always sunny, and cool days are not always cloudy. The diverse collection of hot, cold, sunny, cloudy and in between conditions shown in these figures illustrates the complex nature of actual weather data and provides evidence that building loads will not be a simple linear function of outdoor air temperature. By considering a diverse collection of weather conditions each month, the 8760 hour method produces a diverse, realistic set of cooling and heating loads for the month. Further, because a full month of days are simulated, the appropriate factors influencing equipment performance are considered. There is no reliance on the assumption of "continuous" or "linear" behavior, and the estimates of monthly energy use can be highly accurate. 2. Higher Quality System Comparisons. The issues discussed under item (1) affect not only the accuracy of monthly energy estimates, but also the quality of system comparisons. This is because many of the system design alternatives commonly considered exhibit behavior that is both discontinuous and non-linear. "Discontinuous" refers to inconsistent operation. That is, operation that starts and stops rather than continuing for all operating conditions during a month. "Non-linear" refers to the fact that there is often not a simple proportional relationship between load or outdoor temperature and equipment performance, as discussed in item (1). A comparison of air handling systems with and without a non-integrated outdoor air economizer provides a good illustration of this problem. With this type of economizer control, economizer dampers open when outdoor air temperature drops below the supply air temperature. The system can then immediately use outdoor air for free cooling; mechanical cooling can be turned off. For this example, assume the supply air temperature is 57ºF and that we are simulating system operation for the weather data shown in Figure E-1. The dotted lines in this figure indicate the upper and lower limits of an average temperature profile for the month. Because this average profile ranges between 58ºF and 75ºF, a simulation using the reduced hour-by-hour approach would never find a condition when the economizer dampers opened during September; free cooling would never be available. However, with the 8760 hour method, the use of actual temperature profiles for the month result in 119 hours during 13 days when temperatures drop below 57ºF. If cooling loads exist during these times, the economizer would operate to provide free cooling. Therefore, because an economizer exhibits discontinuous operation, turning on and off at specific conditions, the reduced hour-by-hour approach may not successfully account for this operation. In our example the reduced hour-by-hour method would underestimate the benefit of the economizer. Similar situations can exist for other system components and controls that involve discontinuous, on/off behavior. Examples include ventilation heat reclaim, supply air reset, humidity control, cooling tower fan cycling, and loading and unloading of chiller networks as well as many others. 3. More Accurate Load Histories. The fact that the 8760 hour method simulates building thermal performance day to day for the entire year means it can correctly account for day to day dynamic load behavior. This results in more accurate load profiles, which ultimately lead to more accurate energy use predictions. For example, on a Monday morning in the summer, pull-down loads tend to be larger than on other days of the week due to the heat accumulated by the building mass during the weekend. In addition to resulting in larger cooling loads, these conditions can sometimes set the monthly electric demand. Energy Simulation for Commercial Buildings Page ‐ 198 - 2015 June 22 [ENERGY SIMULATION] In reduced hour-by-hour methods that do not simulate a full week of operation, each day is simulated separately from all other days. Consequently, day to day building dynamics cannot be considered, and the building load histories are more simplistic. In those reduced hour-by-hour methods that do simulate a 7-day sequence each month, results tend to be unrealistic since the same average weather profile is used for all 7 days. 4. Higher Quality Time of Use Energy Data. Because of the diverse weather conditions and operating conditions, and because of the dynamic nature of building heat transfer, 8760 hour methods can produce energy use data that not only accurately defines how much energy is used, but when during the day and week the energy is used. When energy prices vary with time of day, accuracy of the timing of energy use is critical for producing accurate operating cost data. 5. More Accurate Estimates of Peak Demand. Finally, by considering the full range of weather and operating conditions experienced by a building during a month, the 8760 hour method is able to produce more accurate estimates of peak energy demand. When utility rates include a demand charge component, a significant part of the energy cost can be due to the peak energy use rather than the quantity of energy used. Many reduced hour-by-hour methods must determine demands from average day simulations which tend to underestimate demand values. Those methods that add consideration of hot and cold day weather profiles can provide an improvement in demand estimates. However, it is important to recognize that demand will be dependent on more than just the outdoor air temperature. Solar radiation, internal loads, building use profiles and day to day building dynamics also play an important role. The 8760-hour method is the only method that can simultaneously consider all these factors. Thus, while the Reduced Hour-By-Hour Method considers many of the factors required for highquality energy estimates, certain aspects of the method are flawed and can limit the accuracy of the method. Because the 8760 hour method uses a more detailed, comprehensive approach to building simulation, it can consistently overcome these problems to provide accurate, reliable energy estimates. Conclusion This article has discussed the important benefits of the 8760 hour-by-hour building energy analysis method. This method is certainly not new. Computer programs using this method have been available for nearly three decades. However, because many of these programs were developed on mainframe computers as research tools, the programs, and by association, the 8760 hour method itself acquired a reputation of being complicated, difficult and impractical to use. It is important to note that these are problems with the implementation of the 8760 hour method, not with the method itself. If the 8760 hour method is implemented in a well-designed, well-documented microcomputer program, the 8760 hour method can be as easy to learn and use as reduced hour-by-hour methods. In developing Carrier's Hourly Analysis Program we have put two decades worth of experience in the HVAC software field to work to produce an 8760 hour energy analysis tool that is both powerful and easy to use. The resulting program maximizes the benefits of the 8760 hour method while minimizing or even eliminating costs traditionally associated with use of this method. Energy Simulation for Commercial Buildings Page ‐ 199 - [ENERGY SIMULATION] 2015 June 22 Carrier Corporation Carrier University Bynum Training Center 6540 Old Collamer Rd. S. East Syracuse, NY 13057 Singapore June 2015 Energy Simulation for Commercial Buildings_HAP4.9_Rev0.00 Energy Simulation for Commercial Buildings Page 200