Uploaded by e_momenifar

CELSA EQ90

advertisement
EQ..n Moving
Panel
Meters
PQ..nIron
Moving
Coil
Panel Meters
Description
Moving iron panel meters, EQ 48/72/96/144 n sizes are suitable for measurement of AC current & voltage in usual frequency range of
15 - 100 Hz & above 100 Hz. EQ..n meters are protected from breakage under adverses condition because of it suspended between
spring loaded saphire jewl & critical damped using. Silicon oil which protect meters from breakage under adverse condition
Features
1. Housed in glass filed polycarbonate cases.
2. Indicates true RMS value practically independent of waveform even of high harmonics.
3. Large torque to weight ratio which assures a long life of instrument.
4. Standard terminal covers IP 10. Complete protection cover on request.
5. CT operated meters has onsite interchangeable scale facility. Provision for easy replacement of front window, glass & bezel.
Applicable Standards
Nominal case & cutout dimensions for DIN 43700
indicating Electrical instruments
Scale& pointer fo r electrical
measuring instruments
DIN 43802
Connections and Terminal markings
for panel meters
DIN 43807
Terminal bolts / leads.
DIN 46200/46282
Safety requirements and protective
measures for Electrical indicating.
instruments and their accessories.
DIN 40050/8-70,
VDE 0110/ 11-72
VDE 0410/ 10-76
IEC 529 , IEC 1010
Performance specifications for direct
acting indicating analogue electrical
measuring instruments & their
accessories
IEC51/DINEN60051
DIN 43701
Environmental conditions
VDE / VDI 3540
Front frames for indicating measuring
instruments Principle dimensions
DIN 43718
UL Combustibility Class
UL 94 V-0
Comply with following European
directives
89 / 336 / EEC
(EMC Directive),73/23/EEC (low voltage directive) & ammemdment
93/68/EEC, For CE Marking.
Accuracy at Reference Conditions
Scale and Pointer
Pointer deflection
Scale characteristics
Scale length
over range:
0
0...90 Knife - edge pointer
Near Linear above 10% of nominal full
Scale value with coarse fine division
Ammeters
voltmeters for use on
Voltage transformer
EQ 48n EQ 72n EQ 96n EQ 144n
41mm 61mm 97mm 146 mm
2 times nominal current
1.2 times nominal voltage
Scale Interchangeability
Interchangeable
Accuracy class
1.5 according to
IEC 51/ DIN EN 60051
Reference conditions
Ambient temperature
Position of use
Input
Wave form
Frequency:
Other conditions
Rated value of measured quantity
sine wave, distortion factor <= 5%
45...65HZ
IEC 51/ DIN EN 60051
Barthelsmühlring, 16, D - 76870 Kandel, GERMANY.
Tel. : + 49 7275-9883-0
Fax: +497275-9883-33
E-mail : info@celsagermany.com
Web : www.celsagermany.com
EQ..n Moving
Panel
Meters
PQ..nIron
Moving
Coil
Panel Meters
MechanicalSpecifica tion
Case details
Moulded square case suitable for
mounting in Control/ Switchgear
panels, Machinery consoles.
Case material
Glass filled polycarbonate, with non drip&
flame retardant property as per UL 94 V-0
Standard Measuring Ranges
A. C. Voltage
A. C. Current
6V
100mA
10V
150mA
15V
250mA
25V
400mA
40V
600mA
Front facia
Glass
60V
1A
Position of use
Vertical
100V
1.5A
Panel fixing
Side clamp
120V
2.5A
Mounting
Stackable in a single cutout
132V
3A
Panel thickness
< 40 mm
150V
4A
200V
5A
250V
6A
300V
10A
400V
15A
500V
20A
600V
25A
750V (except EQn48)
30A
Terminals
Voltmeters and
ammeters <= 30A
Hexagon studs, M4 screws and
wire clamps E3 (DIN 46282)
Ammeters > 30A
Threaded studs M6 with Nuts.
Ammeters > 60A
Threaded Studs M8 with Nuts.
Electrical Specification
40A
50A
Measured quantity
AC voltage or current
For use on voltage transformer
Power consumption:
voltmeters
Ammeters < 15A
Ammeters > 15A
< 4.5VA
< 0.5VA
< 0.8 VA
.../100V secondary
100A(except EQ48n)
.../110V secondary
for use on current transformer
.../1A secondary
or .../5A secondary
60A
Overload capacity (acc. to IEC 51)
Continuously
1.2 times rated voltage /current
Short duration
Voltmeters
Ammeters
5 s max.
1 s max.
Enclosure code
(IEC 529)
Environmental Conditions
2 times rated voltage
max 1000V, upto max5 second.
EQn 48
EQn 72/96/144
10 times(200 A max). 10 times
-40 times
(250A max.)
IP 52 case
IP 00 for terminals without back cover
IP 20 for terminals with back cover
Insulation class
Group A according to VDE 0110
Rated insulation voltage
EQ48n:660V EQ..n 72/96/144: 1000V
Proof voltage
EQ48n: 2kV EQ..n 72/96/144: 3kV
Installation category
600 V CAT III (IEC 1010)
Insulation resistance
> 50 M W
at 500V d.c
Climatic suitability
Climate category II as per
climatic class 3 according to
VDE/VDI 3540
Operating temperature
Ambient Temperature
- 10... + 55 C
o
0...50 C
Storage temperature
Relative humidity
- 25... + 65 C
< 75% annual average,
non-condensing
15g. 11 ms
1.5 g at about 50 Hz
o
o
Shock resistance
Vibration resistance
o
Position of use
Frequency
External magnetic field:
Vertical +-5
15 ...100Hz (Voltage)
15...400Hz (current)
At 0.4 kA/m,less than 6 % of
fiducialvalue(not as a percentage
class index)
Barthelsmühlring, 16, D - 76870 Kandel, GERMANY.
Tel. : + 49 7275-9883-0
Fax: +497275-9883-33
E-mail : info@celsagermany.com
Web : www.celsagermany.com
EQ..n Moving
Panel
Meters
PQ..nIron
Moving
Coil
Panel Meters
Options
Dimensions
Case :Front facia
Colour of bezel
Red index pointer
Antiglare glass
Red, Yellow ,Blue, White, Grey
Front adjustable on site
o
On request 15 ....165
Position of use
Colour of pointer
Blank dial
Special markings
Yellow and White
With initial and end values marked.
Numbering / Lettering.
Division dials
Basic divisions without numbering.
Colour markings/bands
Red or green
144n
1 44
136
Accuracy class
Over range
(ammeters)
1 on request
No over range or 6 times over range
over nominal current
53
1 3 7 .5
Accessories
5.5
Safety Terminal Protection
138
Protection back cover to provide protection against accidental
contact (hand and fingers) acc. to VDE 0410.
Ordering Information
Moving-iran panel meter
Front dimension
48,72,96 and 144
48 mm x 48 mm
96 mm x 96 mm
Over range
(ammeters)
no over range *3
2 times nominal current
6 times nominal current
Measuring Ranges
Refer to table inside
Terminal protection
Terminal cover Back cover
72 mm x 72 mm
144 mm x 144 mm
AC Voltage (Direct connected)
*1
*3
Panel Fixing
Side clamp
Red Index Pointer
None *3
Front facia
Black *1
Red, Blue, Yellow, White *3
Colour of bezel
Black *1
Red, Blue, Yellow, White *3
Position of use
Vetical *1
On request 15... 165 0 *3
Dial
Standard scale same as measuring range
Blank dial with division *3
Additional letering on request *3
Additional numbering on request *3
Coloured merking red or green *3
Coloured sector red or green *3
*1
*3
0.4 kg.
Connections
Type EQn
Logo
+1
17
L1
N(L2)
X
AC Current (Direct connected)
17
18
L1
N(L2)
X
AC Current (for use on current
Transformer)
17
k
CELSA
Standard
Please clearly add the desired specifications while ordering
18
L1
N(L2)
k
18
l
L
X
Ordering example
Eqn 72 Measuring range 150 V, dial 0 - 150V
Barthelsmühlring, 16, D - 76870 Kandel, GERMANY.
Tel. : + 49 7275-9883-0
Fax: +497275-9883-33
E-mail : info@celsagermany.com
Web : www.celsagermany.com
Download