Routine Transformer Test Report Report Content 2. Acceptance Criteria 1. 1. Report content • Prepared according to ISO-17025 (2017) standard • • • • Title Name & address of the lab Customer name & Address Date ISO-17025(2017) 7.8.2 • Environmental Conditions • Measurement Uncertainties ISO-17025(2017) 7.8.1 • Reviewed & authorized results ISO-17025(2017) 7.1.3 • Details of the Transformer 2. Acceptance Criteria • Insulation Resistance Test Transformer Coil Rating / ( V ) Minimum Insulation Resistance Liquid Filled / (MΩ) Dry / (MΩ) 0 – 600 100 500 > 600 600 1000 • Voltage Ratio Test Allowable Deviation - ± 0.5 % • Applied potential Test • Test successful if no collapse of voltage occurs • Induced Potential Test • Test successful if no collapse of voltage occurs • No Load Loss Test • Deviation of the measured values should be less than +15 % of Guaranteed values • Load Loss Test • • • Deviation of temperature corrected Full Load loss values should be less than +15 % of Guaranteed values Deviation of temperature corrected Total Load loss values should be less than +10 % of Guaranteed values Impedance values • At principal tapping ±10 % • At any other tapping ±15 % • Oil Breakdown Voltage Test • Mean value ≥ 30 kV