UNDERSTANDING POWER QUALITY PROBLEMS IEEE Press 445 Hoes Lane, P.O. Box 1331 Piscataway, NJ 08855-1331 IEEE Press Editorial Board Robert J. Herrick, Editor in Chief J. B. Anderson P. M. Anderson M. Eden M. E. El-Hawary S. Furui A. H. Haddad S. Kartalopoulos D. Kirk P. Laplante M. Padgett W. D. Reeve G. Zobrist Kenneth Moore, Director ofI,EEE Press . Karen Hawkins, Executive Editor Marilyn Catis, Assistant Editor Anthony VenGraitis, Project Editor IEEE Industry Applications Society, Sponsor JA-S Liaison to IEEE Press, Geza Joos IEEE Power Electronics Society, Sponsor PEL-S Liaison to IEEE Press, William Hazen IEEE Power Engineering Society, Sponsor PE-S Liaison to IEEE Press, Chanan Singh Cover design: William T. Donnelly, WT Design Technical Reviewers Mladen Kezunovic, Texas A & M University Damir Novosel, ABB Power T&D Company, Inc., Raleigh, NC Roger C. Dugan, Electrotck Concepts, Inc., Knoxville, TN Mohamed E. El-Hawary, Dalhousie University, Halifax, Nova Scotia, Canada Stephen Sebo, Ohio State University IEEE PRESS SERIES ON POWER ENGINEERING P. M. Anderson, Series Editor Power Math Associates, Inc. Series Editorial Advisory Committee Roy Billington Stephen A. Sebo George G. Karady University of Saskatchewan Ohio State University Arizona State University M. E. El-Hawary Dalhousie University E. Keith Stanek University of Missouri at Rolla Mississippi State University Roger L. King Richard F. Farmer S. S. (Mani) Venkata Donald B. Novotny Arizona State University Iowa State University University of Wisconsin Charles A. Gross Atif S. Debs Auburn University Decision Systems International Raymond R. Shoults University of Texas at Arlington Mladen Kezunovic Texas A&M University Mehdi Etezadi-Amoli University 0.( Nevada John W. Lamont Antonio G. Flores P. M. Anderson Iowa State University Texas Utilities Power Math Associates, Inc. Keith B. Stump Siemens Power Transmission and Distribution UNDERSTANDING POWER QUALITY PROBLEMS Voltage Sags and Interruptions Math H. J. Bollen Chalmers University of Technology Gothenburg, Sweden IEEE Industry Applications Society, Sponsor IEEE Power Electronics Society, Sponsor IEEE Power Engineering Society, Sponsor IEEE. PRESS ~II SERIES POWER ENGINEERING ON P. M. Anderson, Series Editor +IEEE The Institute of Electrical and Electronics Engineers, lnc., NewYork ffiWILEY- ~INTERSCIENCE A JOHN WILEY & SONS, INC.,PUBLICATION e 2000 THE INSTITUTE OF ELECTRICAL AND ELECTRONICS th ENGINEERS, INC. 3 Park Avenue, 17 Floor, New York, NY 10016-5997 Published by John Wiley & Sons, Inc., Hoboken, New Jersey. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, scanning or otherwise,except as permitted under Sections 107 or 108 of the 1976 United States CopyrightAct, without either the prior written permission of the Publisher, or authorization through payment of the appropriateper-copy fee to the Copyright ClearanceCenter, 222 Rosewood Drive, Danvers, MA 01923, (978) 750-8400, fax (978) 750-4470. Requests to the Publisher for permission should be addressedto the Permissions Department, John Wiley & Sons, Inc., 111 River Street, Hoboken, NJ 07030, (201) 748-6011, fax (201) 748-6008. For genera) information on our other products and servicesplease contact our CustomerCare Departmentwithin the u.s. at 877-762-2974,outside the U.S. at 317-572-3993or fax 317-572-4002. Wiley also publishes its books in a variety of electronicformats. Some content that appears in print, however,may not be available in electronicformat. Printed in the United States of America 10 9 8 7 6 5 4 ISBN 0-7803-4713-7 Library of Congress Cataloging-in-Publication Data Bollen, Math H. J., 1960Understanding power quality problems: voltage sags and interruptions Math H. J. Bollen. p. em. - (IEEE Press series on power engineering) Includes bibliographical references and index. IBSN 0..7803-4713-7 l. Electric power system stability. 2. Electric power failures. 3. Brownouts. 4. Electric power systems-Quality control. I. Title. II. Series. IN PROCESS 621.319-dc21 99-23546 CIP The master said, to learn and at due times to repeat what one has learnt, is that not after all a pleasure? Confucius, The Analects, Book One, verse I BOOKS IN THE IEEE PRESS SERIES ON POWER ENGINEERING ELECTRIC POWER APPLICATIONS OF FUZZY SYSTEMS Edited by Mohamed E. El-Hawary, Dalhousie University 1998 Hardcover 384 pp IEEE Order No. PC5666 ISBN 0-7803-1197-3 RATING Of' ELECTRIC POWER CABLES: Ampacity Computations/or Transmission, Distribution, and Industrial Applications George J. Anders, Ontario Hydro Technologies 1997 Hardcover 464 pp IEEE Order No. PC5647 ISBN 0-7803-1177-9 ANALYSIS OF FAULTED POWER SYSTEMS, Revised Printing P. M. Anderson, Power Math Associates, Inc. 1995 Hardcover 536 pp IEEE Order No. PC5616 ISBN 0-7803-1145-0 ELECTRIC POWER SYSTEMS: Design and Analysis, Revised Printing Mohamed E. El-Hawary, Dalhousie University 1995 Hardcover 808 pp IEEE Order No. PC5606 ISBN 0-7803-1140-X POWER SYSTEM STABILITY, Volumes I, II, III An IEEE Press Classic Reissue Set Edward Wilson Kimbark, Iowa State University 1995 Softcover 1008 pp IEEE Order No. PP5600 ISBN 0-7803-1135-3 ANALYSIS OF ELECTRIC MACHINERY Paul C. Krause and Oleg Wasynczuk, Purdue University Scott D. Sudhoff, University of Missouri at Rolla 1994 Hardcover 480 pp IEEE Order No. PC3789 ISBN 0-7803-1029-2 SUBSYNCHRONOUS RESONANCE IN POWER SYSTEMS P. M. Anderson, Power Math Associates, Inc. B. L. Agrawal, Arizona Public Service Company J. E. Van Ness, Northwestern University 1990 Softcover 282 pp IEEE Order No. PP2477 ISBN 0-7803-5350-1 POWER SYSTEM PROTECTION P. M. Anderson, Power Math Associates, Inc. 1999 Hardcover 1,344 pp IEEE Order No. PC5389 ISBN 0-7803-3427-2 POWER AND COMMUNICATION CABLES: Theory and Applications Edited by R. Bartnikas and K. D. Srivastava 2000 Hardcover 896 pp IEEE Order No. PC5665 ISBN 0-7803-1196-5 Contents PREFACE xiii FTP SITE INFORMATION xv ACKNOWLEDGMENTS xvii CHAPTER 1 Overvlew of Power Quality and Power Quality Standards 1 1.1 Interest in Power Quality 2 1.2 Power Quality, Voltage Quality 4 1.3 Overview of Power Quality Phenomena 6 1.3.1 Voltage and Current Variations 6 1.3.2 Events 14 1.3.3 Overview of Voltage Magnitude Events 19 1.4 Power Quality and EMC Standards 22 1.4.1 Purpose of Standardization 22 1.4.2 The tsc Electromagnetic Compatibility Standards 24 1.4.3 The European Voltage Characteristics Standard 29 CHAPTER 2 Long Interruptions and Reliability Evaluation 35 2.1 Introduction 35 2.1.1 2.1.2 2.1.3 2.1.4 Interruptions 35 Reliability Evaluation of Power Systems 35 Terminology 36 Causes of Long Interruptions 36 2.2 Observation of System Performance 37 2.2.1 Basic Indices 37 2.2.2 Distribution of the Duration of an Interruption 40 2.2.3 Regional Variations 42 vii viii Con ten ts 2.2.4 Origin of Interruptions 43 2.2.5 More Information 46 2.3 Standards and Regulations 48 2.3.1 Limits for the Interruption Frequency 48 2.3.2 Limits for the Interruption Duration 48 2.4 Overview of Reliability Evaluation 50 2.4.1 2.4.2 2.4.3 2.4.4 Generation Reliability 51 Transmission Reliability 53 Distribution Reliability 56 Industrial Power Systems 58 2.5 Basic Reliability Evaluation Techniques 62 2.5. J 2.5.2 2.5.3 2.5.4 2.5.5 2.5.6 Basic Concepts of Reliability Evaluation Techniques 62 Network Approach 69 State-Based and Event-Based Approaches 77 Markov Models 80 Monte Carlo Simulation 89 Aging of Components 98 2.6 Costs of Interruptions 101 2.7 Comparison of Observation and Reliability Evaluation 106 2.8 Example Calculations 107 2.8.1 2.8.2 2.8.3 2.8.4 A Primary Selective Supply 107 Adverse Weather 108 Parallel Components 110 Two-Component Model with Aging and Maintenance III CHAPTER 3 Short Interruptions 115 3.1 Introduction 115 3.2 Terminology 115 3.3 Origin of Short Interruptions 116 3.3.1 3.3.2 3.3.3 3.3.4 Basic Principle 116 Fuse Saving 117 Voltage Magnitude Events due to Reclosing 118 Voltage During the Interruption 119 3.4 Monitoring of Short Interruptions 121 3.4.1 Example of Survey Results 121 3.4.2 Difference between Medium- and Low-Voltage Systems 123 3.4.3 Multiple Events 124 3.5 Influence on Equipment 125 3.5.1 3.5.2 3.5.3 3.5.4 Induction Motors 126 Synchronous Motors 126 Adjustable-Speed Drives 126 Electronic Equipment 127 3.6 Single-Phase Tripping 127 3.6.1 Voltage-During-Fault Period 127 3.6.2 Voltage-Post-Fault Period 129 3.6.3 Current-During-Fault Period 134 3.7 Stochastic Prediction of Short Interruptions 136 Contents ix CHAPTER 4 Voltage Sags-Characterization 139 4.1 Introduction 139 4.2 Voltage Sag Magnitude 140 4.2.1 Monitoring 140 4.2.2 Theoretical Calculations 147 4.2.3 Example of Calculation of Sag Magnitude 153 4.2.4 Sag Magnitude in Non-Radial Systems 156 4.2.5 Voltage Calculations in Meshed Systems 166 4.3 Voltage Sag Duration 168 4.3.1 Fault-Clearing Time 168 4.3.2 Magnitude-Duration Plots 169 4.3.3 Measurement of Sag Duration 170 4.4 Three-Phase Unbalance 174 4.4.1 Single-Phase Faults 174 4.4.2 Phase-to-Phase Faults 182 4.4.3 Two-Phase-to-Ground Faults 184 4.4.4 Seven Types of Three-Phase Unbalanced Sags 187 4.5 Phase-Angle Jumps 198 4.5.1 Monitoring 199 4.5.2 Theoretical Calculations 201 4.6 Magnitude and Phase-Angle Jumps for Three-Phase Unbalanced Sags 206 4.6.1 Definition of Magnitude and Phase-Angle Jump 206 4.6.2 Phase-to-Phase Faults 209 4.6.3 Single-Phase Faults 216 4.6.4 Two-Phase-to-Ground Faults 222 4.6.5 High-Impedance Faults 227 4.6.6 Meshed Systems 230 4.7 Other Characteristics of Voltage Sags 231 4.7.1 Point-on-Wave Characteristics 231 4.7.2 The Missing Voltage 234 4.8 Load Influence on Voltage Sags 238 4.8.1 Induction Motors and Three-Phase Faults 238 4.8.2 Induction Motors and Unbalanced Faults 24 t 4.8.3 Power Electronics Load 248 4.9 Sags due to Starting of Induction Motors 248 CHAPTER S Voltage Sags-Equipment Behavior 253 5.1 Introduction 253 5.1.1 Voltage Tolerance and Voltage-Tolerance Curves 253 5.1.2 Voltage-Tolerance Tests 255 5.2 Computers and Consumer Electronics 256 5.2.1 Typical Configuration of Power Supply 257 5.2.2 Estimation of Computer Voltage Tolerance 257 5.2.3 Measurements of PC Voltage Tolerance 261 5.2.4 Voltage-Tolerance Requirements: CBEMA and ITIC 263 5.2.5 Process Control Equipment 264 5.3 Adjustable-Speed AC Drives 265 5.3.1 Operation of AC Drives 266 5.3.2 Results of Drive Testing 267 5.3.3 Balanced Sags 272 x Con~nh 5.3.4 5.3.5 5.3.6 5.3.7 5.3.8 5.3.9 DC Voltage for Three-Phase Unbalanced Sags 274 Current Unbalance 285 Unbalanced Motor Voltages 289 Motor Deacceleration 292 Automatic Restart 296 Overview of Mitigation Methods for AC Drives 298 5.4 Adjustable-Speed DC Drives 300 5.4.1 5.4.2 5.4.3 5.4.4 5.4.5 5.4.6 Operation of DC Drives 300 Balanced Sags 303 Unbalanced Sags 308 Phase-Angle Jumps 312 Commutation Failures 315 Overview of Mitigation Methods for DC Drives 317 5.5 Other Sensitive Load 318 5.5.1 5.5.2 5.5.3 5.5.4 Directly Fed Induction Motors 318 Directly Fed Synchronous Motors 319 Contactors 321 Lighting 322 CHAPTER 6 Voltage Sags-Stochastic Assessment 325 6.1 Compatibility between Equipment and Supply 325 6.2 Presentation of Results: Voltage Sag Coordination Chart 328 6.2.1 6.2.2 6.2.3 6.2.4 6.2.5 6.2.6 6.2.7 The Scatter Diagram 328 The Sag Density Table 330 The Cumulative Table 331 The Voltage Sag Coordination Chart" 332 Example of the Use of the Voltage Sag Coordination Chart 335 Non-Rectangular Sags 336 Other Sag Characteristics 338 6.3 Power Quality Monitoring 342 6.3.,1 Power Quality Surveys 342 6.3.2 Individual Sites 357 6.4 The Method of Fault Positions 359 6.4.1 6.4.2 6.4.3 6.4.4 Stochastic Prediction Methods 359 Basics of the Method of Fault Positions 360 Choosing the Fault Positions 362 An Example of the Method of Fault Positions 366 6.5 The Method of Critical Distances 373 6.5.1 6.5.2 6.5.3 6.5.4 6.5.5 6.5.6 6.5.7 6.5.8 6.5.9 Basic Theory 373 Example-Three-Phase Faults 374 Basic Theory: More Accurate Expressions 375 An Intermediate Expression 376 Three-Phase Unbalance 378 Generator Stations 384 Phase-Angle Jumps 384 Parallel Feeders 385 Comparison with the Method of Fault Positions 387 Contents xi CHAPTER 7 Mitigation of Interruptions and Voltage Sags 389 7.1 Overview of Mitigation Methods 389 7.1.1 7.1.2 7.1.3 7.1.4 7.1.5 7.1.6 7.1.7 From Fault to Trip 389 Reducing the Number of Faults 390 Reducing the Fault-Clearing Time 391 Changing the Power System 393 Installing Mitigation Equipment 394 Improving Equipment Immunity 395 Different Events and Mitigation Methods 395 7.2 Power System Design-Redundancy Through Switching 397 7.2.1 7.2.2 7.2.3 7.2.4 Types of Redundancy 397 Automatic Reclosing 398 Normally Open Points 398 Load Transfer 400 7.3 Power System Design-Redundancy through Parallel Operation 405 7.3.1 Parallel and Loop Systems 405 7.3.2 Spot Networks 409 7.3.3 Power-System Design-On-site Generation 415 7.4 The System-Equipment Interface 419 7.4.1 7.4.2 7.4.3 7.4.4 7.4.5 7.4.6 7.4.7 7.4.8 Voltage-Source Converter 419 Series Voltage Controllers-DVR 420 Shunt Voltage Controllers-StatCom 430 Combined Shunt and Series Controllers 435 Backup Power Source-SMES, BESS 438 Cascade Connected Voltage Controllers-UPS 439 Other Solutions 442 Energy Storage 446 CHAPTER 8 Summary and Conclusions 453 8.1 Power Quality 453 8.1.1 The Future of Power Quality 454 8.1.2 Education 454 8.1.3 Measurement Data 454 8.2 Standardization 455 8.2.1 Future Developments 455 8.2.2 Bilateral Contracts 456 8.3 Interruptions 456 8.3.1 Publication of Interruption Data 456 8.4 Reliability 457 8.4.1 Verification 457 8.4.2 Theoretical Developments 457 8.5 Characteristics of Voltage Sags 458 8.5.1 Definition and Implementation of Sag Characteristics 458 8.5.2 Load Influence 458 8.6 Equipment Behavior due to Voltage Sags 459 8.6.1 Equipment Testing 459 8.6.2 Improvement of Equipment 460 8.7 Stochastic Assessment of Voltage Sags 460 8.7.1 Other Sag Characteristics 460 8.7.2 Stochastic Prediction Techniques 460 xii Contents 8.7.3 Power Quality Surveys 461 8.7.4 Monitoring or Prediction? 461 8.8 Mitigation Methods 462 8.9 Final Remarks 462 BIBLIOGRAPHY 465 APPENDIX A Overview of EMC Standards 477 APPENDIX B IEEE Standards on Power Quality 481 APPENDIX C Power Quality Definitions and Terminology APPENDIX D List of Figures APPENDIX E List of Tables INDEX 529 ABOUT THE AUTHOR 543 507 525 485 Preface The aims of the electric power system can be summarized as "to transport electrical energy from the generator units to the terminals of electrical equipment" and "to maintain the voltage at the equipment terminals within certain limits." For decades research and education have been concentrated on the first aim. Reliability and quality of supply were rarely an issue, the argument being that the reliability was sooner too high than too low. A change in attitude came about probably sometime in the early 1980s. Starting in industrial and commercial power systems and spreading to the public supply, the power quality virus appeared. It became clear that equipment regularly experienced spurious trips due to voltage disturbances, but also that equipment was responsible for many voltage and current disturbances. A more customer-friendly definition of reliability was that the power supply turned out to be much less reliable than always thought. Although the hectic years of power quality pioneering appear to be over, the subject continues to attract lots of attention. This is certain to continue into the future, as customers' demands have become an important issue in the deregulation of the electricity industry. This book concentrates on the power quality phenomena that primarily affect the customer: interruptions and voltage sags. During an interruption the voltage is completely zero, which is probably the worst quality of supply one can consider. During a voltage sag the voltage is not zero, but is still significantly less than during normal operation. Voltage sags and interruptions account for the vast majority of unwanted equipment trips. The material contained in the forthcoming chapters was developed by the author during a to-year period at four different universities: Eindhoven, Curacao, Manchester, and Gothenburg. I Large parts of the material were originally used for postgraduate and industrial lectures both "at home" and in various places around the world. The material will certainly be used again for this purpose (by the author and hopefully also by others). 'Eindhoven University of Technology, University of the Netherlands Antilles, University of Manchester Institute of Science and Technology, and Chalmers University of Technology, respectively. xiii xiv Preface Chapter 1 of this book gives an introduction to the subject. After a systematic overview of power quality, the term "voltage magnitude event" is introduced. Both voltage sags and interruptions are examples of voltage magnitude events. The second part of Chapter 1 discusses power quality standards, with emphasis on the IEC standards on electromagnetic compatibility and the European voltage characteristics standard (EN 50160). In Chapter 2 the most severe power quality event is discussed: the (long) interruption. Various ways are presented of showing the results of monitoring the number of interruptions. A large part of Chapter 2 is dedicated to the stochastic prediction of long interruptions-v-an area better known as "reliability evaluation." Many of the techniques described here can be applied equally well to the stochastic prediction of other power quality events. Chapter 3 discusses short interruptions-interruptions terminated by an automatic restoration of the supply. Origin, monitoring, mitigation, effect on equipment, and stochastic prediction are all treated in this chapter. Chapter 4 is the first of three chapters on voltage sags. It treats voltage sags in a descriptive way: how they can be characterized and how the characteristics may be obtained through measurements and calculations. Emphasis in this chapter is on magnitude and phase-angle jump of sags, as experienced by single-phase equipment and as experienced by three-phase equipment. Chapter 5 discusses the effect of voltage sags on equipment. The main types of sensitive equipment are discussed in detail: single-phase rectifiers (computers, processcontrol equipment, consumer electronics), three-phase ac adjustable-speed drives, and de drives. Some other types of equipment are briefly discussed. The sag characteristics introduced in Chapter 4 are used to describe equipment behavior in Chapter 5. In Chapter 6 the theory developed in Chapters 4 and 5 is combined with statistical and stochastical methods as described in Chapter 2. Chapter 6 starts with ways of presenting the voltage-sag performance of the supply and comparing it with equipment performance. The chapter continues with two ways of obtaining information about the supply performance: power-quality monitoring and stochastic prediction. Both are discussed in detail. Chapter 7, the last main chapter of this book, gives an overview of methods for mitigation of voltage sags and interruptions. Two methods are discussed in detail: power system design and power-electronic controllers at the equipment-system interface. The chapter concludes with a comparison of the various energy-storage techniques available. In Chapter 8 the author summarizes the conclusions from the previous chapters and gives some of his expectations and hopes for the future. The book concludes with three appendixes: Appendix A and Appendix B give a list of EMC and power quality standards published by the IEC and the IEEE, respectively. Appendix C contains definitions for the terminology used in this book as well as definitions from various standard documents. Math H. J. Bollen Gothenburg, Sweden FTP Site Information Along with the publication of this book, an FTP site has been created containing MATLAB® files for many figures in this book. The FTP site can be reached at ftp.ieee.orgjupload/press/bollen. xv Acknowledgments A book is rarely the product of only one person, and this book is absolutely no exception. Various people contributed to the final product, but first of all I would like to thank my wife, Irene Gu, for encouraging me to start writing and for filling up my tea cup every time I had another one of those "occasional but all too frequent crises." For the knowledge described in this book lowe a lot to my teachers, my colleagues, and my students in Eindhoven, Curacao, Manchester, and Gothenburg and to my colleagues and friends all over the world. A small number of them need to be especially mentioned: Matthijs Weenink, Wit van den Heuvel, and Wim Kersten for teaching me the profession; the two Larry's (Conrad and Morgan) for providing me with a continuous stream of information on power quality; Wang Ping, Stefan Johansson, and the anonymous reviewers for proofreading the manuscript. A final thank you goes to everybody who provided data, figures, and permission to reproduce material from other sources. Math H. J. Bollen Gothenburg, Sweden xvii Voor mijn ouders Overview of Power Qual ity and Power Qual ity Standards Everybody does not agree with the use of the term powerquality, but they do agree t hat it has becomeaveryimportantaspect of power delivery especially in the second half of the 1990s.There is a lotof disagreementa boutwhat power quality actually incorporates; it looks as if everyone has her or his own interpretation.In this chaptervarious ideas will be summarized to clear up some of the confusion. However,author the himself is part of the power quality world; thuspart of the confusion. After reading this book the reader might want to go to the library and form his own picture. The number of books onpower quality is still rather limited. The book "Electric Power SystemsQuality" by Dugan et al. [75] gives a useful overviewof the various power quality phenomenaand the recent developments in this field. There are two more books with the term power quality in the title: "Electric Power QualityControl Techniques" [76] and "Electric PowerQuality" [77]. But despite the general title, reference [76] mainly concentrateson transientovervoltage and[77] mainly on harmonicdistortion. But both books docontainsomeintroductorychapters on power quality. Also many recent books on electric power systems containone or more general chapterson power quality, for example,[114], [115], and [116]. Information on power qualitycannotbe found only in books; a large numberof papers have been written on the subject; overview papers as well as technical papers aboutsmall detailsof power quality. The main journals to look for technical papers are the IEEE Transactionson Industry Applications, the IEEE Transactionson Power Delivery andlEE ProceedingsGeneration,Transmission,Distribution. Other technicaljournals in the power engineering field alsocontainpapers of relevance. A journal specially dedicated to power quality is Power Quality Assurance. Overview articles can be found in many different journals;two early ones are[104] and [105]. Various sources use the term "power quality" with different meanings.Other sources use similar but slightly different terminology like "quality of power supply" or "voltage quality." What all these terms have in common that is they treat the interaction between the utility and the customer, or in technical terms between the power system and the load. Treatmentof this interaction is in itself not new. The aim of the power system has always been to supply electrical energy to the customers. 1 2 ChapterI • Overview of PowerQuality and PowerQuality Standards What is new is theemphasisthat is placedon this interaction,and the treatmentof it as a separateareaof power engineering.In Section 1.2 the various termsand interpretations will be discussedin moredetail. From the discussionwe will concludethat "power quality" is still the most suitableterm. The various power quality phenomenawill be discussedandgroupedin Section1.3. Electromagneticcompatibility and powerquality standardswill be treatedin detail in Section 1.4. But first Section 1.1 will give some explanationsfor the increasedinterestin power quality. 1.1 INTEREST IN POWER QUALITY The fact that powerquality hasbecomean issuerecently,doesnot meanthat it was not important in the past. Utilities all over the world have for decadesworked on the improvementof what is now known as power quality. And actually, even the term has been in use for arather long time already. The oldest mentioning of the term "power quality" known to the author was in a paper published in 1968 [95]. The paper detailed a study by the U.S. Navy after specificationsfor the power required by electronicequipment.That papergives a remarkablygood overview of the power quality field, including the useof monitoringequipmentandeven thesuggesteduseof a static transferswitch. Severalpublicationsappearedsoon after, which used theterm power quality in relation to airborne power systems[96], [97], [98]. Already in 1970 "high powerquality" is beingmentionedas oneof the aimsof industrial powersystem design,togetherwith "safety," "reliable service,"and "low initial and operatingcosts" [99]. At about the sametime the term "voltage quality" was used in theScandinavian countries[100], [101] and in the Soviet Union [102], mainly with referenceto slow variationsin the voltage magnitude. The recent increasedinterestin power quality can be explainedin a numberof ways. The main explanationsgiven aresummarizedbelow. Of courseit is hard to say which of these came first; some explanationsfor the interestin power quality given o f the increasedinterestin power below.. will by othersbe classified asconsequences quality. To showthe increasedintereston powerquality a comparisonwasmadefor the numberof publicationsin the INSPECdatabase[118] using theterms"voltagequality" or "power quality." For the period 1969-1984the INSPEC databasecontains 91 records containing the term "power quality" and 64 containing the term "voltage quality." The period 1985-1996resulted in 2051 and 210 records, respectively.We see thus a large increasein number of publicationson this subjectsand also a shift away from the term "voltage quality" toward the term "power quality." • Equipment has become more sensitive to voltage disturbances. Electronic and power electronicequipmenthas especiallybecomemuch more sensitivethan its counterparts10 or 20 years ago.T he paperoften cited as having introduced the term power quality (by Thomas Key in 1978 [I]) treatedthis increasedsensitivity to voltage disturbances.N ot only has equipment becomemore sensitive,companieshave alsobecomemore sensitiveto loss of productiontime due to their reducedprofit margins.On the domestic market, electricity is more and more considereda basic right, which should is that an interruptionof the supply simply alwaysbe present.Theconsequence will muchmorethan beforelead tocomplaints,even if thereare nodamagesor costsrelatedto it. An importantpapertriggering the interestin powerquality appearedin the journal BusinessWeek in 1991 [103].The article cited Jane Section 1.1 • Interestin Power Quality 3 Clemmensenof EPRI as estimating that "power-relatedproblems cost U.S. companies$26 billion a year in lost time and revenue."This value has been cited overandoveragain eventhoughit was mostlikely only a roughestimate. • Equipment causes voltage disturbances. Tripping of equipmentdue to disturbancesin the supply voltageis often describedby customersas "bad power quality." Utilities on the other side, often view disturbancesdue to end-userequipmentas themain power quality problem.Modern(power) electronicequipmentis not only sensitive tovoltage disturbances,it also causesdisturbancesfor othercustomers.The increaseduse of converter-drivenequipment(from consumerelectronicsand computers,up to adjustable-speed drives) has led to a large g rowth of voltagedisturbances, althoughfortunatelynot yet to a level wheree quipmentbecomes sensitive. The main issue here is thenonsinusoidalcurrent of rectifiers and inverters. The input current not only contains a power frequency component(50 Hz or 60 Hz) but also so-calledharmoniccomponentswith frequenciesequal to a multiple of the power frequency. Theharmonicdistortion of the currentleads to harmoniccomponentsin the supply voltage. Equipmenthas alreadyproduced harmonicdistortion for a numberof decades. But only recently has the amountof load fed via powerelectronicconvertersincreased enormously: not only large adjustable-speed drives but also smallconsumerelectronicsequipment. The latter cause a largepart of the harmonicvoltage distortion: each individual device does notgeneratemuch harmoniccurrentsbut all of them togethercause a serious d istortion of the supply voltage. • A growing need forstandardizationand performancecriteria. The consumerof electrical energy used to be viewed by most utitilies simply as a"load." Interruptionsand other voltage disturbanceswere part of the deal, and the utility decided w hat was reasonable.Any customerwho was not satisfied with the offered reliability and quality had to pay theutility for improving the supply. Todaythe utilities have totreat the consumersas"customers."Even if the n umberof voltagedisturbances,it does have utility does not need to reduce the to quantify them one 'way or theother. Electricity is viewed as aproductwith certain characteristics,which have to bemeasured,predicted, guaranteed, improved, etc. This is further triggered by the drive towards privatization and deregulationof the electricity industry. Opencompetitioncan make the situationeven more complicated.In the past a consumerwould have acontract with the local supplier who would deliver the electrical energyw ith a given reliability and quality. Nowadays the customercan buy electrical energysomewhere,the transport capacity somewhereelse and pay the local utility, for the actual connectionto the system. It is nolongerclear who isresponsiblefor reliability andpowerquality. As long as thecustomerstill has aconnectionagreementwith the local utility, one canarguethat the latter is responsiblefor the actualdelivery and thus for reliability andquality. But what aboutvoltagesags due totransmissionsystem faults? In some cases the consumeronly has acontractwith a supplier who only generatesthe electricityand subcontractstransportand distribution. One could statethat any responsibilityshould be defined bycontract,so that the generationcompany with which the customerhas a contractualagreement would be responsiblefor reliability and quality. The responsibility of the 4 Chapter1 • Overview of PowerQuality and PowerQuality Standards local distributionwould only betowardsthe generationcompanieswith whom they have acontractto deliver to givencustomers.No matter what the legal constructionis, reliability and quality will need to be well defined. • Utilities want to deliver a good product. Somethingthatis oftenforgottenin the heatof the discussion isthatmany power quality developmentsare driven by the utilities.M ost utilities simply want to deliver a goodproduct, and have beencommittedto that for many decades.Designinga system with a high reliabilityof supply, for a limited cost, is a technicalchallengewhich appealedto many in thepower industry, and hopefully still does in the future. • The power supply has become too good. Part of the interestin phenomenalike voltage sagsand harmonicdistortion is due to the highquality of the supply voltage. Long interruptionshave become rare inmost industrializedcountries(Europe, North America, East Asia), and theconsumerhas, wrongly,gottenthe impressionthat electricity is somethingthat is alwaysavailableandalwaysof high quality, or at least something that shouldalways be. The factthat there are someimperfectionsin the supplywhich are veryhard or evenimpossibleto eliminateis easilyforgotten. In countrieswhere theelectricity supply has a highunavailability, like 2 hours in per day, power quality does not appearto be such a big issue as countries with availabilitieswell over 99.9°~. • The power quality can be measured. The availability of electronicdevices tomeasureandshow waveformshas certainly contributedto the interestin power quality. Harmoniccurrentsand voltage sags were simplyhard to measureon a large scale in the past. Measurementswere restrictedto rms voltage, frequency,a nd long interruptions; phenomenawhich are nowconsideredpart of power quality, but were simply part of power systemoperationin the past. 1.2 POWER QUALITY, VOLTAQE QUALITY Therehave been(andwill be) a lot of argumentsaboutwhich term to use for theu tilitycustomer (system-load) interactions. Most people use the term"power quality" although this term is still prone to criticism. The main objection againstthe useof the term isthat one cannottalk about the quality of a physicalquantity like power. Despitethe objectionswe will use the term powerquality here, eventhoughit does not give aperfectdescriptionof the phenomenon.But it has become a widely used term and it is the best termavailableat themoment.Within the IEEE, the termpowerquality has gained some officialstatus already, e.g., through the name of see22 (Standards CoordinatingCommittee):"PowerQuality" [140]. But theinternationalstandardssetting organizationin electrical engineering(the lEe) does not yet usethe term power quality in any of its standarddocuments.Instead it uses the termelectromagnetic compatibility, which is not the same aspower quality but there is astrong overlap between the two terms. Below, numberof a different terms will be discussed. As each term has itslimitations the author feels that power quality remainsthe more general term which covers all theotherterms. But, beforethat, it is worth to give the following IEEE and lEe definitions. Section 1.2 • PowerQuality, Voltage Quality 5 The definition of power quality given in theIEEE dictionary [119] originatesin IEEE Std 1100(betterknown as theEmeraldBook) [78]: Powerquality is theconceptof poweringandgroundingsensitiveequipmentin a matter that issuitableto theoperationof thatequipment.Despitethis definition the term powerquality is clearly used in a more general waywithin the IEEE: e.g., SCC 22 also covers standardson harmonicpollution caused byloads. The following definition is given in IEC 61000-1-1:Electromagneticcompatibility is the abilityof an equipmentor system to function satisfactorilyin its electromagnetic environmentwithoutintroducing intolerable electromagneticdisturbancesto anythingin that environment[79]. Recentlythe lEe has alsostarteda project group on power quality [106] which should initially result in a standardon measurementof power quality. The following definition of powerquality was adoptedfor describingthe scopeof the project group: Setofparametersdefining thepropertiesof thepowersupply asdeliveredto the user in normaloperatingconditionsin termsofcontinuityofsupplyandcharacteristicsofvoltage (symmetry,frequency,magnitude,waveform). Obviously,this definition will not stopthe discussionaboutwhat powerquality is. The author'simpressionis that it will only increase theconfusion,e.g., becausepower quality is now suddenlylimited to "normal operatingconditions." From the many publications on this subject and the various terms used, the following terminology has beenextracted.The readershould realize that there is no generalconsensuson the useof these terms. • Voltage quality (the FrenchQualite de latension)is concernedwith deviations of the voltagefrom the ideal. The idealvoltageis a single-frequencysine wave of constantfrequencyand constantmagnitude.The limitation of this term is that it only covers technical aspects, andthat even within those technical aspectsit neglects thecurrentdistortions.The termvoltagequality is regularly used, especially inEuropeanpublications.It can beinterpretedas thequality of the productdelivered by the utility to thecustomers. • A complementarydefinition would becurrentquality. Currentquality is concernedwith deviationsof the currentfrom the ideal. The idealcurrentis again a single-frequencysine waveof constantfrequency and magnitude.An additional requirementis that this sine wave is inphasewith the supply voltage. Thus where voltage quality has to do with what the utility delivers to the consumer,current quality is concernedwith what the consumertakes from the utility. Of coursevoltage and current are strongly related and if either voltageor currentdeviates from the ideal it is h ard for the other to be ideal. • Power quality is thecombinationof voltagequality and currentquality. Thus powerquality is concernedwith deviationsof voltageand/orcurrentfrom the ideal. Note that powerquality hasnothingto do with deviationsof the product of voltageand current (the power) from any ideal shape. • Quality of supplyor quality of powersupply includes atechnicalpart (voltage quality above)plus a nontechnicalpart sometimesreferredto as "quality of service."The lattercovers theinteractionbetween thecustomerand the utility, e.g., the speed with which the utility reacts tocomplaints,or the transparency of the tariff structure.This could be a usefuldefinition as long as one does not want to include the customer'sresponsibilities.The word "supply" clearly excludes activeinvolvementof the customer. 6 ChapterI • Overview of PowerQuality and PowerQuality Standards • Quality of consumption would be the complementaryterm of quality of supply. This would containthe currentquality plus, e.g., howaccuratethe customeris in paying the electricity bill. • In the lEe standardsthe term electromagnetic compatibility (EMC) is used. Electromagneticcompatibility has to do with mutual interaction between equipmentand with interaction betweenequipmentand supply.Within electromagneticcompatibility, two importantterms are used: the "emission" is the electromagneticpollution producedby a device; the"immunity" is the device's ability to withstandelectromagneticpollution. Emission is related to the term currentquality, immunity to the term voltage quality. Based on this term, a growing setof standardsis being developedby the lEe. The variousaspectsof electromagneticcompatibility and EMC standardswill be discussed in Section 1.4.2. 1.3 OVERVIEW OF POWER QUALITY PHENOMENA We saw in theprevioussectionthat power quality isconcernedwith deviationsof the voltage from its ideal waveform (voltage quality) and deviationsof the currentfrom its ideal waveform(currentquality). Such adeviationis called a"power quality phenomenon"or a "powerquality disturbance."Powerquality phenomenacan be divided into two types, which need to be treatedin a different way. factor) is never • A characteristicof voltage orcurrent(e.g., frequency or power exactly equal to itsnominal or desired value. The small deviationsfrom the nominal or desired value are called "voltage variations" or "current variations." A property of any variation is that it has a value at anymomentin time: e.g., the frequency is never exactly equal to 50 Hz or 60 Hz; the power factor is never exactly unity.Monitoring of a variation thus has totake place continuously. • Occasionallythe voltage orcurrent deviates significantly from itsnormal or ideal waveshape. These suddendeviationsare called"events."Examples are a suddendrop to zero of the voltage due to the operationof a circuit breaker(a voltage event), and a heavily distortedovercurrentdue to switching of a nonloadedtransformer(a currentevent).Monitoring of events takes place by using a triggering mechanismwhere recordingof voltage and/or current startsthe momenta thresholdis exceeded. The classification of aphenomenonin one of these two types isn ot always unique. It may dependon the kind of problemdue to thephenomenon. 1.3.1 Voltage and Current Variations Voltage andcurrentvariationsare relatively smalldeviationsof voltage orcurrent characteristicsa roundtheir nominalor ideal values. The two basic examples are voltage magnitudeand frequency. On average, voltage magnitudeand voltage frequency are equal to theirnominal value, but they are never exactly equal. To describe the deviations in a statisticalway, the probability density or probability distribution function should be used. Figure1.1 shows a fictitiousvariation of the voltagemagnitudeas a function of time. This figure is the result of a so-calledMonte Carlo simulation(see 7 Section 1.3 • Overviewof Power QualityPhenomena 240,.----.---...,----.-~---,---, 220' -0 Figure 1.1 Simulatedvoltage magnitudeas a function of time. - ..L--- 5 - -L..- - --'-- - --'- 10 15 Time in hours - -' 20 Section2.5.5) .The underlyingdistribution was anormal distribution with an expected value of 230 V and a standarddeviation of 11.9 V. A setof independents amplesfrom this distribution is filtered by alow-passfilter to preventtoo large short-timechanges. The probability density function of the voltage magnitudeis shown in Fig. 1.2. The probability densityfunction gives theprobability that the voltagemagnitudeis within a certainrange.Of interestis mainly the probability that the voltagemagnitudeis below or above a certain value. The probability distribution function (the integral of the density function) gives that information directly. The probability distribution function for this fictitious variation is shown in Fig . 1.3. Both the probability density function and the probability distribution function will be defined more accuratelyin Section 2.5.1. An overviewof voltageandcurrentvariationsis given below. This list is certainly not complete,it merely aims at giving someexample. There is an enormousrangein end-userequipment.many with special requirementsand special problems. In the power quality field new typesof variationsand eventsappearregularly. The following list usesneither the terms used by thelEe nor the terms recommendedby the IEEE. . Also is there still Terms commonly used donot always fully describea phenomenon 0.12,.--------,----- ,- - -----.-- ---, 0.1 .~ 0.08 .g g 0.06 ~ or> £ 0.04 0.02 o ~ Figure 1.2 Probabilitydensityfunct ion of the voltage magnitudein Fig . 1.1. 220 ___' 225 __L 230 Voltage in volts _L 235 __' 240 8 Chapter I • Overview of PowerQuality and PowerQuality Standards 0.8 5 I:a U') 0.6 .~ ] 0.4 .s £ 0.2 o ...-:=="--_ _ ... 220 225 -..1- 230 Voltagein volts --'- 235 ---' 240 Figure 1.3 Probability distribution function of the voltage magnitude in Fig. 1.1. some inconsistencybetweendifferent documentsabout which terms should be used. The termsused in the list below,a ndin a similar list in Section1.3.2arenot meantas an alternativefor the lEe or IEEE definitions, but simply an attemptto somewhatclarify the situation.The readeris advisedto continueusing officially recognizedterms,where feasible. 1. Voltage magnitudevariation. Increaseand decreaseof the voltage magnitude, e.g., due to • variation of the total load of a distribution systemor part of it; • actionsof transformertap-changers; • switching of capacitorbanksor reactors. Transformertap-changera ctionsand switching of capacitorbankscan normally be traced back to load variations as well. Thus the voltage magnitudevariationsare mainly due to load variations, which follow a daily pattern. The influence of tapchangersand capacitorbanks makes that the daily pattern is not always presentin the voltage magnitudepattern. The lEe uses theterm "voltage variation" insteadof "voltage magnitudevariation." The IEEE does not appearto give a nameto this phenomenon.Very fast variation of the voltagemagnitudeis referred to as voltagefluctuation. 2. Voltage frequencyvariation. Like the magnitude,also the frequency of the supplyvoltageis not constant.Voltagefrequencyvariationis due tounbalancebetween load and generation.The term "frequency deviation" is also used.Short-duration frequency transientsdue to short circuits and failure of generatorstationsare often also included in voltagefrequencyvariations,althoughthey would betterbe described as events. The lEe uses theterm "power frequency variation"; the IEEE uses theterm "frequencyvariation." 3. Currentmagnitudevariation. On the load side, thecurrentis normally also not constantin magnitude.The variationin voltagemagnitudeis mainly due tovariationin current magnitude.The variation in currentmagnitudeplays animportantrole in the design of power distribution systems.The systemhas to bedesignedfor the maximum Section 1.3 • Overviewof PowerQuality Phenomena 9 current,where the revenueo f the utility is mainly based onaveragecurrent.The more constantthe current,the cheaperthe system per delivered energy unit. Neither lEe nor IEEE give a name for thisphenomenon. 4. Currentphasevariation.Ideally, voltageand currentwaveformsare in phase. In thatcase thepowerfactor of the loadequalsunity, and the reactivepowerconsumption is zero.Thatsituationenablesthe most efficientt ransportof (active) powerandthusthe cheapestd istribution system. Neither lEe nor IEEE give a name for thispowerquality phenomenon,a lthough the terms"power factor" and "reactivepower" describe itequally well. 5. Voltage andcurrent unbalance.Unbalance,or three-phaseunbalance,is the phenomenonin a three-phasesystem, in which the nils values of the voltagesor the phase anglesbetweenconsecutivephasesare not equal. The severityof the voltage unbalancein a three-phasesystem can be expressed innumberof a ways, e.g., • the ratio of the negative-sequence and thepositive-sequencevoltage component; and the lowestvoltage magni• the ratio of the difference between the highest tude, and the averageof the threevoltagemagnitudes;and • the difference betweenthe largest and the smallestphasedifference between consecutivephases. Thesethree severity indicatorscan bereferred to as "negative-sequence u nbalance," "magnitudeunbalance,"and "phaseunbalance,"respectively. The primary source of voltage unbalanceis unbalancedload (thus current unbalance).T his can be due to anunevenspreadof (single-phase)low-voltagecustomers over thethreephases,b ut morecommonlyunbalanceis due to a largesingle-phase load. Examplesof the latter can befound among railway traction suppliesand arc furnaces. Three-phasevoltage unbalancecan also be the resulto f capacitor bank anomalies,such as a blown fuse in one phaseof a three-phasebank. Voltageunbalanceis mainly of concernfor three-phaseloads.Unbalanceleads to additionalheatproductionin the winding of inductionandsynchronousmachines;this reduces the efficiency a nd requiresderatingof the machine.A three-phasediode rectifier will experience a largecurrent unbalancedue to a smallvoltage unbalance.The largestcurrentis in the phase with the highest voltage, thus the load hastendencyto the mitigate the voltageunbalance. The IEEE mainly recommendsthe term "voltage unbalance"although some standards(notably IEEE Std. 1159) use the term "voltage imbalance." 6. Voltage fluctuation.If the voltage magnitudevaries, thepower flow to equipment will normally also vary. If thevariationsare largeenoughor in a certaincritical frequencyrange, theperformanceof equipmentcan be affected. Cases in which voltage variation affects load behavior are rare, with theexception of lighting load. If the illumination of a lamp varies withfrequenciesbetweenabout 1 Hz and 10 Hz, our eyes are very sensitive to andabovea it certainmagnitudethe resultinglight flicker can become rather disturbing. It is this sensitivity of the human eye which explains the interestin this phenomenon.The fastvariation in voltagemagnitudeis called "voltage fluctuation," the visualphenomenonas perceived byour brain is called "light flicker." The term"voltageflicker" is confusingbut sometimesused as ashorteningfor "voltage fluctuation leadingto light flicker." 10 Chapter1 • Overview of PowerQuality and PowerQuality Standards To quantify voltagefluctuation and light flicker, aquantity called "flicker intensity" has beenintroduced[81]. Its value is an objectivemeasureof the severityof the light flicker due to acertainvoltage'fluctuation.The flicker intensitycan betreatedas a variation,just like voltagemagnitudevariation. It can beplottedas afunction of time, and probability densityand distribution functionscan beobtained.Many publications discussvoltage fluctuation and light flicker. Good overviews can befound in, among others,[141] and [142]. The terms "voltage fluctuation" and "light flicker" are used byboth lEe and IEEE. 7. Harmonic voltage distortion. The voltage waveform is never exactly a singlefrequency sine wave. Thisphenomenonis called "harmonic voltage distortion" or simply "voltage distortion." When we assumea waveform to be periodic, it can be describedas a sumof sine waves withfrequenciesbeing multiples of the fundamental frequency.The nonfundamentalc omponentsare called"harmonicdistortion." Thereare threecontributionsto the harmonicvoltagedistortion: 1. The voltage generatedby a synchronousmachineis not exactly sinusoidal due to smalldeviationsfrom the idealshapeof the machine.This is a small contribution; assumingthe generatedvoltageto be sinusoidalis a verygood approximation. 2. The power system transporting the electrical energy from thegenerator stations to the loads is not completely linear, although the deviation is small. Somecomponentsin the systemdraw a nonsinusoidalc urrent, even for a sinusoidal voltage. The classicalexample is the power transformer, where thenonlinearity is due to saturationof the magneticflux in the iron core of the transformer.A more recentexampleof a nonlinearpowersystem componentis the HVDe link. The transformationfrom ac to dcand back takesplace by usingpower-electronicscomponentswhich only conductduring part of a cycle. The amount of harmonicdistortion originating in the power system is normally small. Theincreasinguseof powerelectronicsfor control of power flow and voltage(flexible ac transmissionsystems orFACTS) carriesthe risk of increasingthe amount of harmonic distortion originating in the power system. The same technologyalso offers thepossibility of removinga large part of the harmonicdistortion originatingelsewhere in the system or in the load. 3. The main contribution to harmonicvoltage distortion is due to nonlinear load. A growing part of the load is fed throughpower-electronicsconverters drawing a nonsinusoidalcurrent. The harmoniccurrent componentscause harmonic voltage components,and thus a nonsinusoidalvoltage, in the system. Two examplesof distored voltage are shown in Figs. 1.4and 1.5. The voltage shownin Fig. 1.4containsmainly harmoniccomponentsof lower order(5,7,11,and 13 in this case). Thevoltageshownin Fig. 1.5containsmainly higher-frequencyharmonic components. Harmonicvoltagesand currentcan causea whole rangeof problems,with additional lossesand heating the main problem. The harmonicvoltage distortion is normally limited to a fewpercent(i.e., themagnitudeof the harmonicvoltagecomponents Section 1.3 • 11 Overview of PowerQuality Phenomena 400 300 200 rl 100 ($ > .5 0 0 ~ -100 co S -200 -300 -400 0 Figure 1.4 Exampleof distortedvoltage,with mainly lower-orderharmoniccomponents 5 10 15 20 15 20 Time in milliseconds [211]. 400 300 200 ~ 0 > .S 0 100 0 r -100 ~ -200 -300 Figure 1.5 Exampleof distortedvoltage,with higher-orderharmoniccomponents[211]. -400 0 5 10 Time in milliseconds is up to a fewpercentof the magnitudeof the fundamentalvoltage) in which case equipmentfunctionsasnormal.Occasionallylarge harmonicvoltage distortion occurs, problem in which can lead tomalfunction of equipment.This can especially be a big industrialpower systems, where there is a large concentrationof distortingload as well as sensitive load.Harmonicdistortionof voltage andcurrentis the subject ofhundreds of papersas well as anumberof books[77], [194], [195]. The term "harmonicdistortion" is very commonly used, and"distortion" is an lEe term referring to loadstaking harmoniccurrentcomponents.Also within theIEEE the term "distortion" is used to refer toharmonicdistortion; e.g., "distortion factor" and "voltage distortion." 8. Harmonic current distortion. The complementaryphenomenonof harmonic voltage distortion is harmoniccurrent distortion. The first is a voltagequality phenomenon,the latter a currentquality phenomenon.As harmonicvoltage distortion is mainly due to nonsinusoidalload currents,harmonic voltage andcurrent distortion are strongly linked. Harmonic current distortion requires over-rating of series components like transformersand cables. As the series resistance increases with frequency, adistorted current will cause more losses t han a sinusoidalcurrent of the same rms value. 12 Chapter I • Overview of Power Quality and Power Quality Standards 150 100 en e SO ~ cd .5 0 = ~ -so U -100 -15°0 5 10 15 Time inmilliseconds 20 Figure 1.6 Exampleof distortedcurrent, leadingto the voltagedistortionshownin Fig. 1.4 [211). Two examplesof harmoniccurrentdistortionare shown in Figs. 1.6 and 1.7.Both currents are drawn by an adjustable-speeddrive. The current shown in Fig. 1.6 is typical for modernac adjustable-speed drives. Theharmonicspectrumof the current containsmainly 5th, 7th,11th, and 13thharmoniccomponents.T he currentin Fig. 1.7 is lesscommon.The high-frequencyripple is due to the switching frequencyof the dc/ac inverter. As shown in Fig. 1.5 thishigh-frequencycurrent ripple causes a highfrequency ripple in thevoltageas well. 9. Interharmonicvoltage andcurrentcomponents. Some e quipmentproducescurrent componentswith a frequency which is not an integermultiple of the fundamental frequency. Examples are cycloconvertersand some typeso f heatingcontrollers.These " interharmoniccomponents."T heir magcomponentsof the currentare referred to as nitudeis normallysmallenoughnot to cause anyproblem,but sometimesthey can excite unexpectedresonancesbetweentransformerinductancesand capacitorbanks. More fundamental dangerousarecurrentandvoltagecomponentswith a frequency below the frequency, referred to as "sub-harmonicdistortion." Sub-harmoniccurrentscan lead to saturationof transformersand damageto synchronousgeneratorsand turbines. Anothersourceof interharmonicdistortionare arc furnaces.Strictly speakingarc furnaces do notproduce any interharmonicvoltage or current components,but a 50 -50 L - . - ._ _ - . . . J ' - -_ o 5 _ ----JL..--_ _ __ __J - - - - J ~ 10 Time inmilliseconds 15 20 Figure 1.7 Exampleof distortedcurrent, leadingto the voltagedistortionshownin Fig. 1.5 [211]. 13 Section 1.3 • Overviewof PowerQuality Phenomena numberof (integer) harmonicsplus acontinuous(voltage andcurrent)spectrum.Due to resonances in the power system some of the frequencies in thisspectrumare amplified. The amplified frequencycomponentsare normally referred to asinterharmonics due to the arc furnace. These voltage interharmonicshave recently become o f special interest as they are responsible for serious light flicker problems. A special case ofsub-harmoniccurrentsare those due to oscillations in the earthmagnetic field following a solar flare. These so-called geomagneticallyinducedcurrents have periodsaroundfive minutes and the resulting transformersaturationhas led to large-scaleblackouts[143]. 10. Periodicvoltagenotching. In three-phaserectifiers thecommutationfrom one diode or thyristor to the other creates ashort-circuitwith a duration lessthan 1 ms, which results in areductionin the supply voltage. Thisphenomenonis called"voltage notching" or simply "notching." Notching mainly results inhigh-order harmonics, of characwhich are often notconsideredin power engineering. A more suitable way terizationis throughthe depthand durationof the notchin combinationwith the point on the sine wave at which the notchingcommences. An exampleof voltagenotchingis shown in Fig. 1.8. This voltage wave shape was caused by anadjustable-speed drive in which a largereactancewas used to keep the de currentconstant. The IEEE uses the term"notch" or "line voltagenotch" in a more general way: any reductionof the voltage lasting less than half a cycle. 11. Mainssignalingvoltage.High-frequencysignals aresuperimposedon the supply voltage for thepurposeof transmissionof information in the public distribution system and tocustomer'spremises.Threetypes of signal arementionedin the European voltagecharacteristicsstandards[80]: • Ripple controlsignals: sinusoidal signals between 110 and 3000 Hz. These signals are, from avoltage-quality point-of-view, similar to harmonic and interharmonicvoltage components. • Power-line-carriersignals: sinusoidal signals between 3 and 148.5 kHz. These signals can be described both as high-frequencyvoltage noise (see below) and as high-order(inter)harmonics. • Mains markingsignals: superimposedshort time alterations (transients)at selectedpoints of the voltage waveform. 400r---------,-----,------.--------, 300 200 ZJ ~ .5 j ~ 100 0 -100 -200 -300 -400 0 Figure 1.8 Example of voltage notching[211]. 5 10 Timeinmilliseconds 15 20 14 ChapterI • Overview of PowerQuality and PowerQuality Standards Mains signalingvoltagecan interferewith equipmentusingsimilar frequencies for some audiblenoise internalpurpose.The voltages,a nd the associatedcurrents,can also cause and signals ontelephonelines. The other way around,harmonicand interharmonicvoltagesmay beinterpreted by equipmentas beingsignalingvoltages,leadingto wrong functioning of equipment. 12.High-frequencyvoltage noise. Thesupply voltagecontainscomponentswhich are not periodicat all. These can be called "noise," althoughfrom the consumerpoint of view, all above-mentionedvoltagecomponentsare in effect noise. Arcfurnacesare an important sourceof noise. But also thecombinationof many different nonlinear loadscan lead tovoltagenoise [196]. Noise can be presentbetween thephaseconductors (differential mode noise) or cause anequal voltage in all conductors(commonmode noise).Distinguishingthe noise fromothercomponentsis not always simple,but actually not really needed. Ananalysisis needed only in cases where the noise leads to some problem with power system orend-userequipment.The characteristicsof the problemwill dictatehow to measureand describethe noise. A whole rangeof voltageand currentvariationshas beenintroduced.The reader will have noticedthat the distinction between thevariousphenomenais not very sharp, e.g., voltagefluctuation andvoltagevariation show a clearoverlap.One of the tasksof future standardizationwork is to developa consistenta ndcompleteclassificationof the variousphenomena.This might look an academictask, as it doesnot directly solve any equipmentor systemproblems.But when quantifying the powerquality, the classification becomeslessacademic.A good classificationalso leads to abetterunderstanding of the various phenomena. 1.3.2 Events Eventsare phenomenawhich only happenevery once in a while. Aninterruption of the supply voltage is the best-knownexample.This can intheory be viewed as an extremevoltagemagnitudevariation (magnitudeequalto zero),andcan beincludedin the probability distribution function of the voltagemagnitude.But this would not give much usefulinformation; it would in fact give theunavailability of the supply voltage, assumingthe resolution of the curve was highenough. Instead,events can best be describedthrough the time between events, and the characteristicsof the events;both in a stochasticsense.Interruptionswill be discussed in sufficientdetail in Chapters2 and 3 and voltagesags inChapters4, 5, and6. Transientovervoltagewill be used as an examplehere. A transientovervoltagerecording is shown in Fig. 1.9: the (absolute value of the) voltagerises toabout180% of its normalmaximumfor a few milliseconds. The smoothsinusoidalcurve is acontinuationof the pre-eventfundamentalvoltage. A transientovervoltagecan becharacterizedin manydifferent ways; threeoftenusedcharacteristicsare: 1. Magnitude: the magnitudeis either the maximum voltage or the maximum voltagedeviation from the normal sine wave. 2. Duration: the durationis harderto define, as itoften takes a long time before the voltage has completelyrecovered.Possibledefinitions are: • the time in which thevoltagehas recoveredto within 10% of the magnitude of the transientovervoltage; • the time-constantof the averagedecay of the voltage; • the ratio of the Vt-integral defined below and themagnitudeof the transient overvoltage. 15 Section 1.3 • Overviewof Power Quality Phenomena 1.5,----~--~-- -~-~--~-___, 0.5 5- .5 ~ ~ - 0.5 ~ -1 Figure 1.9 Example oftransientovervoltage event: phase -to-groundvoltage due to fault clearing in one of theother phases.( Data obtained from (16].) - 1.5 I , I 60 , 20 30 40 Time in milliseconds 3. Vt-integral : theVt-integral is defined as V, = iT (l.l) V(t)dt where t = 0 is thestart of the event, and an a ppropriatevalue is chosen forT, e.g., the time in which the voltage has recovered to within 10% of the magnitude of the transientovervoltage. Again the voltageV(t) can be measured either from zero or as the deviation from the normal sine wave. Figure 1.10 gives thenumberof transientovervoltageevents per year, as obtained for the average low-voltage site in Norway [67]. The distribution function for the time 140 120 100 ~ ....0~ ~ 80 60 1.0-1.5 1.5-2.0 40 ~~ 2.0- 3.0 '-$' 'b" 20 3.0-5.0 .~ ~ ~'I> 0 5.0-10.0 Figure 1.10Numberof transient overvoltage events per year, as a function of magnitude and voltage integral. (Data obtained from [67].) 16 Chapter I • Overview of Powe r Qua lity and Power Quality Standards 1.2r-- - - - - -- - - - -- - - - -, t: o .~ E 0.8t--- -en ~ 0.6 :E 0.4 .. .0 J: 0.2 o 1.0-1.5 1.5-2.0 2.0-3.0 3.0-5.0 Magnitude range in pu 5.0-10.0 Figure 1.11Probability distribution function of the magnitude oftransient overvoltage events, accord ing to Fig. 1.10. between events has not been determ ined, but onlynumberof the events per year with of different characteristics. Notethat the average time between events is the reciprocal the number of events per year. This is the normal situation; the actual distribution function is rarelydetermined in powerquality or reliability surveys[107]. Figures 1.11 through 1.14 givestatistical informationaboutthe characteristicsof the events. Figure 1.11 gives the probability distribution function of the magnitude of the event. We see t hat almost 80% of the events have a magnitudelessthan 1.5 pu . Figure 1.12 gives thecorrespond ing densityfunction. By using alogarithmic scale the is visible. Figure 1.13 gives the numberof events in the high-magn itude rangebetter probability distribution function of the Vt-integral; Fig. 1.14 theprobability density function. 1.2r-- - - -- - - - - - - - - ---, o .u; t: ~ 0.1 g ~ 0.01 2 0.. .0 0.001 1.0-1.5 1.5-2.0 2.0- 3.0 3.0-5.0 5.0-10.0 Magnitude range in pu Figure 1.12Probability density funct ionof the magn itudeof transient overvoltage events , acco rding to Fig. 1.10. An overview of various types of powerquality events is given below. Power quality events are thephenomen a which can lead totripping of equipment, to interrupt ion of the productionor of plant operation , or endangerpower systemoperation. The treatmentof these in astochasticway is an extensionof the power system reliability field as will be discussed inC hapter2. A special classof events, the so-called "voltage magnitudeevents," will betreatedin more detail in Section 1.3.3. Voltage magnitude events are the events which are the main concernfor equipment,and they are the main subject for the resto f this book . Note that below only " voltage events" are discussed, as these canconcernto be of of "currentevents" could be added , with their end-user equipment. But similarly a list possible effects on power system equipment. Most powerquality monitors in use, continuously monitor the voltage and record an event when the voltage exceeds certain 17 Section 1.3 • Overviewof PowerQuality Phenomena 1.2.-- -- ;".s ! 0.8+-- - - - - - -- - - - - -- - - - -- ---, '" ~ 0.6 ~ 0.4+-- £ - -- - - -- 0.2 o Figure 1.13Probabilitydistribution function of the Vt-integral oftransientovervoltage events.accordingto Fig. 1.10. 0-0.005 0.8 . - - -- 0.005-0.01 0.01-0.1 Vt-integral range - 0.1-1 - - -- -- -- -- ----, .~ 0.6+ - -- - - - -- - ~ ~ 0.4+---- - - -- - J ..: 0.2 Figure 1.14Probability density functionof the Vt-integralof transientovervoltage events,accordingto Fig. 1.10. o 0.005-0.01 0.01-0.1 Vt-integral range 0.1-1 thresholds,typically voltagemagnitudethresholds. Although the currentsare often also recorded they do notnormally trigger therecording. Thus anovercurrentwithout an over- or undervoltagewill not be recorded. Of course there are no technical limitations in usingcurrentsignals to trigger therecordingprocess. In fact mostmonitorshave the option of triggering oncurrentas well. I. Interruptions. A "voltageinterruption"[IEEE Std.I159], "supply interruption" [EN 50160],or just "interruption" [IEEE Std.1250] is a condition in which the voltage at the supplyterminalsis close to zero. Close to zero is by the IEC defined"lower as than I% of the declaredvoltage" and by the IEEE as"lower than 10%" [IEEE Std. II 59]. Voltage interruptionsare normally initiated by faults whichsubsequentlytrigger protection measures .O ther causesof voltage interruption are protection operation when there is no fault present (a so-called protection maltrip), broken conductors not triggering protective measures, andoperatorintervention. A further distinction can be made between pre-arrangedand accidentalinterruptions. The former allow the end user to takeprecautionarymeasures to reduce the impact. All pre-arranged interruptionsare of course caused by operatoraction. Interruptionscan also be subdivided based on their duration, thus based on the way of restoring the supply: • automaticswitching; • manualswitching; • repair or replacementof the faultedcomponent. Cha pter I • Overviewof PowerQuality and Power QualityStandards 18 Various terminologies are in use to distinguish between these. The IEC uses the term long interruptionsfor interruptions longer than 3 minutes and the term s hort interruptions for interruptions lasting up to 3 minutes. Within the IEEE the terms momentary,temporary,and sustained are used, but different documents give different duration values. The various definitions will be discussedChapter3. in 2. Undervoltages.Undervoltages of variousduration are known under different names.Short-durationundervoltagesare called"voltage sags" or"voltagedips." The latter term is preferred by thelEe. Within the IEEE and in manyjournal and conference papers on power qua lity, the term voltage sag is used. Long-durationundervoltage is normall y simply referred to as " undervoltage." A voltage sag is areductionin the supply voltagemagnitudefollowed by a voltage recovery after ashort period of time. When a voltage magnitudereduct ion of finite duration can actually be called a voltage sag (or voltage dip in the IEC terminology) remains apoint of debate, even though the official definitions are cleara bout it. Accord ing to the IEC, a supply voltage dip is a sudden reduction in the supply voltage to a value between 90% and I % of the declared voltage, followed by a recovery between 10ms and I minuteater. l For the IEEE a voltagedrop is only a sag if the during -sag voltage is between 10% and 90% of the nominal voltage. Voltage sags are mostly caused short-circuitfaults by in the system and by starting of large motors. Voltage sags will be discussed in detail Chapters4, in 5, and 6. 3. Voltage magnitude steps. Load switching, transformer tap-changers,and switching actions in the system (e.g., capacitorbanks) can lead to a sudden change in the voltage magnitude. Such a voltagemagnitude step is called a " rapid voltage change" [EN 50160] or "voltagechange" [IEEE Std.1l59] . Normally both voltage before and after the step are in the normal operatingrange (typically 90% to 110% of the nominal voltage). An example of voltagemagnitudesteps is shown in Fig. 1.15. The figure shows a 2.5hour recording of the voltage in a 10kVistribution d system. The steps in the voltage magnitudeare due to theoperationof transformer tap-changersat various voltage levels. 4. Overvoltages. Just like with undervoltage, overvoltage events are given different names based on their duration. Overvoltages of veryshort duration, and high magnitude, are called " transient overvoltages ," "voltage spikes," or sometimes "voltage surges." The atter l term is ratherconfusingas it is sometimes used to refer to overvoltages with adurationbetweenabout 1 cycle and I minute . Thelatter event is more correctly called"voltage swell" or "temporarypower frequency overvoltage ." Longer 1.05 1.04 :l 0. 1.03 .S 1.02 ., OIl ~ 1.01 ~ 0.99 0.98 5:00:00 5:30:00 6:00:00 6:30:00 7:00:00 Clock time (HH:MM:SS) Figure 1.15 Example of voltage magnitude steps due to tran sformetap-changer r 7:30:00 operation, recorded in a10kV distribution system insouthernSweden. Section 1.3 • Overviewof PowerQuality Phenomena 19 duration overvoltagesare simplyreferredto as "overvoltages."Long and short overvoltagesoriginatefrom, amongothers,lightning strokes,switchingoperations,s udden load reduction,single-phaseshort-circuits,and nonlinearities. A resonancebetween thenonlinearmagnetizingreactanceof a transformeranda capacitance(either in the form of a capacitorbank or the capacitanceof an underground cable) can lead to a large overvoltageof long duration. This phenomenonis called ferroresonance,a nd it can lead to seriousdamageto power systemequipment [144]. 5. Fast voltage events. Voltage events with a very short duration, typically one as cycle of the power system frequency or less, are referred to"transients,""transient (over)voltages,""voltagetransients,"or "wave shapefaults." The termtransientis not fully correct, as it should only be used for thetransition between twosteadystates. Events due toswitchingactionscould underthat definition be calledtransients;events due tolightning strokescould not be calledtransientsunderthat definition. But due to the similarity in time scaleboth are referredto asvoltagetransients.Even veryshortdurationvoltagesags (e.g., due to fuse clearing)are referred to as voltagetransients,or also "notches." Fastvoltageevents can be dividedinto impulsive transients(mainly due to lightning) and oscillatory transients(mainly due to switching actions). 6. Phase-anglejumps andthree-phaseunbalance. We will see inC hapter4 that a voltage sag is often associatedwith a phase-anglejump and some three-phase unbalance.An interestingthought is whetheror not a jump in phase-anglewithout a drop in voltage magnitudeshould be called avoltagesag. Such an event could occur s hortwhen oneof two parallel feeders istakenout of operation.The same holds for a duration, three-phaseunbalancewithout changein magnitude,thus where only the phase-angleof the threevoltages changes. To get acompletepicture,also short-durationphase-angle j umpsandshort-duration unbalancesshouldbeconsideredas eventsbelongingto the familyof powerquality phenomena. 1.3.3 Overview of Voltage Magnitude Events As mentionedin the previoussection,the majority of eventscurrently of interest are associatedwith eithera reductionor an increasein the voltagemagnitude.We will refer to these as"voltage magnitudeevents." A voltage magnitudeevent is a (significant)deviation from the normal voltage magnitudefor a limited duration.The magnitudecan befound by taking the rmsof the voltageover a multiple of one half-cycleof the power-systemfrequency. (1.2) where V(t) is the voltageas afunction of time, sampledat equidistantpoints t = k Si. The rms value istaken over a period N ~t, referred to as the "window length." Alternatively, the magnitudecan bedeterminedfrom the peak voltage or from the fundamental-frequency c omponento f the voltage.Most powerquality monitorsdetermine the rmsvoltage once every cycle or once every few cycles. The momentthe rms voltagedeviates morethan a pre-setthresholdfrom its nominal value, thevoltageas a function of time is recorded(the rmsvoltage,the sampledtime-domaindata,or both). 20 Chapter 1 • Overview of Power Quality and Power Quality Standards Most events show aratherconstantrms voltagefor a certaindurationafter which the rms voltage returns to a more or less normal value. This isunderstandableif one realizesthat events are due tochangesin the system followed by therestorationof the original systemaftera certaintime. Before,during, andafter the event, the system is more or less in asteadystate.Thusthe event can be characterizedthroughoneduration and onemagnitude.We will see inChapter4 that it is not always possible touniquely determinemagnitudeand duration of a voltage magnitudeevent. For now we will assumethat this is possible, and define the magnitudeof the event as theremaining rms voltage during the event: if the rms voltaged uring the event is 170V in a 230 V system, themagnitudeof the event is~~g = 73.9%. Knowing the magnitudeand duration of an event, it can berepresentedas one point in the magnitude-durationplane. All eventsrecordedby a monitor over acertain periodcan berepresentedas ascatterof points.Different underlyingcauses may lead to events indifferent parts of the plane. Themagnitude-durationplot will come back several times in theforthcoming chapters.Various standardsgive different names to events indifferent parts of the plane. Astraightforwardclassificationis given in Fig. 1.16. The voltagemagnitudeis split into three regions: • interruption: the voltagemagnitudeis zero, • undervoltage:the voltagemagnitudeis below its nominal value, and • overvoltage:the voltagemagnitudeis aboveits nominal value. In duration,a distinction is made between: • • • • very short, correspondingto transientand self-restoringevents; short, correspondingto automaticrestorationof the pre-eventsituation; long, correspondingto manualrestorationof the pre-eventsituation; very long, correspondingto repair or replacemento f faulted components. Very short overvoltage Shortovervoltage Longovervoltage Very long overvoltage 110% Normaloperatingvoltage Very short undervoltage Shortundervoltage Longundervoltage Very long undervoltage Veryshort int. Shortinterruption Longinterruption Verylong int. }-10% 1-3 cycles }-3min Event duration 1-3 hours Figure 1.16 Suggested classification of voltage magnitudeevents. 21 Section 1.3 • Overviewof Power QualityPhenomena The various bordersin Fig. 1.16 aresomewhatarbitrary; some of the indicated lEe and IEEE values (1-3minutes,1-10%,900/0,and 110% ) are those used in existing standards.F or monitoringpurposes,strict thresholdsare needed todistinguishbetween the different events. An example is the thresholddividing betweeninterruptionsand undervoltages.This one is placed(somewhatarbitrarily) at 1% of nominalaccordingto % accordingto the.IEEE (see below). Anyothersmall value would be the IEC and at 10 equally defendable. The classificationin Fig. 1.16 is only aimed atexplainingthe different types of events: the termsmentionedin the figures are not all used in practice. Both lEe and IEEE give different namesto events in someof the regionsof the magnitude-duration plane. The IECdefinitionsaresummarizedin Fig. 1.17 and theIEEE definitionsin Fig. 1.18. Thersc definitionswereobtainedfrom CENELECdocumentEN 50160 [80], the IEEE definitions from IEEE Std.1159-1995. The methodof classifying eventsthrough one magnitudeand oneduration has information and knowledge been shown to be very useful and has resulted in aoflot about power quality. But the method also has itslimitations, which is important to Four points should be especially kept in mind. realize when using this classification. 1. ,Theduring-eventrms voltage isnot alwaysconstant,leading toambiguities ambiguitiesin in defining the magnitudeof the event. It may also lead to defining thedurationof the event. 2. Fastevents (one cycle or less duration)cannotbe in characterized,resulting in unrealistic values for magnitudeand duration or in thesedisturbances simply being neglected. 3. Repetitive events can giveerroneousresults: theyeither lead to an overof events is estimationof the numberof events (when each event in a row countedas aseparateevent), or anunder-estimationof the severityof the events (when a rowof identical events iscountedas one event). 0 =00 oS .~] Temporaryovervoltage (1)Overvoltage f-f> 0 110% Normaloperatingvoltage ? (supply)Voltagedip (1)Overvoltage 1% Shortinterruption I 0.5 cycle I, Longinterruption 3 min 1 min Eventduration EN Figure1.17 Definitions of voltage magnitude events as used in 50160. 22 Chapter1 • Overview of PowerQuality and PowerQuality Standards = Q) ';; 110% Swell ~ Overvoltage Normaloperatingvoltage c: Q) 'r;) Voltagesag I Undervoltage ~ 0 Z 100/0 Momentary 0.5 cycle I Temporary 3 sec Sustainedinterruption 1 min Eventduration Figure 1.18Definitions of voltage magnitudeevents as used in I EEE Std.11591995, 4. Equipmentis sometimessensitive toothercharacteristicsthanjust magnitude and duration. We will come back to these problemsin more detail inChapters3 and 4. Similar classificationscan beproposedfor voltagefrequency events, for voltage phase-angleevents, forthree-phasevoltage unbalanceevents, etc. But because most equipmentproblems are due to an increase or decrease in voltage magnitude, the emphasisis on voltagemagnitudeevents. 1.4 POWER QUALITY AND EMC STANDARDS 1.4.1 Purpose of Standardization Standardsthat define the quality of the supply have beenpresentfor decades already. Almost any country has standardsdefining the margins in which frequency and voltage are allowed to vary. Other standardslimit harmoniccurrent and voltage distortion, voltage fluctuations, and duration of an interruption.Thereare three reasons fordevelopingpower quality standards. l. Defining the nominalenvironment.A hypotheticalexampleof such astandard is: "The voltage shall he sinusoidal with a .frequency of 50 Hz and an rms voltageof 230 V." Such astandardis not very practical as it is technically impossible to keep voltage magnitude and frequency exactlyconstant. Therefore,existing standardsuse terms like"nominal voltage" or "declared voltage" in this context.A more practicalversion of the abovestandardtext would read as: "Thenominalfrequencyshall be 50 Hz and the nominal voltage shall be 230V," which comes close to the wording in EuropeanstandardEN 50160[80]. Section 1.4 • PowerQuality and EMC Standards 23 Defining nominal voltage and frequencydoesnot say anythingabout the actualenvironment.To do this thedeviationsfrom the nominal values have to be known. Most countrieshave astandardgiving the allowed variation in the rms voltage, a typical rangebeing betweenfrom 900/0 to 110°A». 2. Defining the terminology. Even if a standard-settingbody does not want to impose any requirementson equipment or supply, it might still want to publish power quality standards.A good example is IEEE Std.1346[22] which recommendsa methodfor exchanginginformationbetweenequipment manufacturers,utilities, and customers.T he standarddoes not give any suggestionsabout what is consideredacceptable. This group of standardsaims at giving exact definitions of the various phenomena,how their characteristicsshould be measured,a nd how equipment should be testedfor its immunity. The aim of this is to enablecommunication betweenthe various partnersin the power quality field. It ensures, e.g., that the resultsof two power quality monitors can be easilycompared and that equipmentimmunity can becomparedwith the descriptionof the environment.Hypotheticalexamplesare: "A short interruption is a situation J% ofthe nominalrms voltageforless than in which the rms voltage is less than 3 minutes."and"The durationof a voltage dip is the time during 'which the rms voltage is less than 90%of the nominalrms voltage. The durationof a voltage dip shall beexpressedin seconds. The rms voltage shall determinedevery be half-cycle," Both IEEE Std. 1159and EN 50160 give these kindo f definitions, hopefully merginginto a future lEe standard. 3. Limit the number of powerquality problems. Limiting the numberof power quality problemsis the final aim of all the work on power quality. Power quality problemscan be mitigated by limiting the amountof voltagedisturbancescausedby equipment,by improving the performanceof the supply, and by making equipmentlesssensitiveto voltage disturbances.All mitigation methodsrequiretechnicalsolutionswhich can be implementedindependently of any standardization.But proper standardizationwill provide important incentives for the implementation of the technical solutions. Proper standardizationwill also solve the problem of responsibility for power quality disturbances.H ypotheticalexamplesare: The current taken by a load exceeding 4 k VA shallnot containmore than J% ofany evenharmonic.The harmoniccontents shall be measuredas a l-second average.and Equipment shall be immune to voltage variations between85% and 110%of the terminals, nominal voltage. This shall be tested by supplying at the equipment sinusoidalvoltageswith magnitudesof 85.% and J/0% for a duration of 1 hour. If the pieceofequipment has more than one distinctiveload state,it shall be tested for each load state separately, or for what are conceivedthe most sensitive stales. In this field both IEC and IEEE lack a.good set of standardson power quality. The lEe has set up a wholeframework on electromagneticcompatibility which alreadyincludessome power quality standards.T he best example is the harmonic standardIEC-61000-2-3 which limits the amount of harmonic current produced by low-power equipment. The IEEE has a good recommendedpractice for the limitation of harmonic distortion: IEEE 519 [82] which gives limitsboth for the harmoniccurrentstaken by the customerand for the voltagesdeliveredby the utility. 24 ChapterI • Overview of PowerQuality and PowerQuality Standards 1.4.2 The IEC Electromagnetic Compatibility Standards Within the International ElectrotechnicalCommittee (IEC) a comprehensive framework of standardson electromagneticcompatibility is under development. Electromagneticcompatibility (EMC) is defined as:the ability of a device,equipment or systemto function satisfactorilyin its electromagneticenvironment without introducing intolerable electromagneticdisturbances toanything in that environment[79]. Thereare two aspects to EMC: (1) a piece ofequipmentshould be able tooperate normally in its environment,and (2) itshouldnot pollutethe environmenttoo much. In EMC terms:immunity and emission. There are standardsfor both aspects.Agreement on immunity is at first a matter of agreementbetween themanufacturerand the customer. But the IEC sets minimum requirementsin immunity standards.The third term of importanceis "electromagneticenvironment,"which gives the levelof disturbance againstwhich theequipmentshouldbe immune. Within theEMC standards,a distinction is made betweenradiated disturbancesand conducteddisturbances.Radiated disturbancesare emitted (transmitted)by one device and received by anotherwithout the need for anyconduction. Conducteddisturbancesneed aconductorto transfer from one device toanother. Theseconducteddisturbancesare within the scopeof power quality; radiated disturbances(although very important) are outside of the normal realm of power system engineering or power quality. A schematicoverview of theEMC terminologyis given in Fig. 1.19. We see that of conducteddisturbancesand radiateddisturthe emission of a device may consist bances.Radiateddisturbancescan reachanotherdevice via any medium.Normally, radiateddisturbancesonly influenceanotherdevice when it is physically close to the emitting device.Conducteddisturbancesreach anotherdevice via an electrically conductingmedium, typically thepowersystem. The device being influenced no longer has to be physically close as the power system is a very good medium for conductionof the is a device which is many typesof disturbances.Of course also here the rule that electrically closer(thereis lessimpedancebetween them) is more likely to be influenced. A device connectedto the power system is exposed to an electrical environmentnot only due to thecombinedemissionof all otherdevicesconnectedto the system but also due to all kinds of events in the power system (like switching actions, short-circuitfaults, and lightning strokes). Theimmunity of the deviceshouldbe assessed with reference to this electromagneticenvironment.A special typeof disturbances,not shown in the Powersystem Events Conducted disturbances Figure 1.19Overviewof EMC terminology. Section 1.4 • PowerQuality and EMC Standards 25 figure, are radiateddisturbanceswhich induce conducteddisturbancesin the power system. Immunity Requirements. Immunity standardsdefine theminimum level of electromagneticdisturbancethat a pieceof equipmentshall be able towithstand. Before being able todeterminethe immunity of a device, aperformancecriterion must be defined. In other words, it should be agreedupon what kind of behavior will be called a failure. Inpracticeit will often be clear when a device performssatisfactorily and when not, but when testingequipment the distinction may becomeblurred. It will all dependon the applicationwhetheror not a certain equipmentbehavioris acceptable. The basicimmunity standard[IEC-61000-4-1] gives four classes of equipment performance: • Normal performancewithin the specification limits. • Temporarydegradationor lossof function which is self-recoverable. • Temporarydegradationor loss of function which requiresoperatorintervention or system reset. • Degradationor loss of function which is not recoverabledue to damageof equipment,componentsor software,or lossof data. These classes are general as descriptionshouldbe the applicableto all kinds of equipment. Thisclassificationis further defined in thevariousequipmentstandards. Emission Standards. Emission standardsdefine themaximum amount of electromagneticdisturbancethat a pieceof equipmentis allowed to produce.Within the existing lEe standards,emission limits exist forharmonic currents[lEe 61000-3-2 and 61000-3-6], and for voltage fluctuations[lEe 61000-3-3, 61000-3-5, and 61000-37]. Most power quality phenomenaare not due to equipmentemission but due to EMC standardsonly apply operationalactionsor faults in the power system. As the to equipment, there are no"emission limits" for the power system. Events like voltage sagsand interruptions are consideredas a "fact-of-life." These events do, however,contributeto the electromagneticenvironment. The Electromagnetic Environment.To give quantitativelevels for theimmunity of equipment,the electromagneticenvironmentshould be known. Theelectromagnetic environmentfor disturbancesoriginating in or conductedthrough the power system, isequivalentto the voltagequality as defined before. ThelEC electromagnetic compatibility standardsdefine the voltagequality in three ways: I. Compatibility levels are reference values for coordinatingemissionandimmunity requirementsof equipment.For a givendisturbance,the compatibility level is in between the emission level (or the environment)and the immunity level. As both emission andimmunity are stochasticquantities,electromagnetic compatibility can never be completelyguaranteed.The compatibility level is chosen such t hatcompatibilityis achieved for mostequipmentm ostof the time: typically 95% of equipmentfor 950/0 of "the time. It isnot always possible to influenceboth emission and immunity: three cases can be distinguished: 26 ChapterI • Overview of PowerQuality and PowerQuality Standards • Both emission andimmunitycan be affected.The compatibility level can in of principle be freely chosen. But a high level will lead to high costs equipmentimmunity and a low level to high costs for limiting the emission. Thecompatibility level shouldthereforebe chosen suchthat the sum of both costs isminimal. An exampleof a disturbancewhere both emission and immunity can be affected ish armonicdistortion. A very good example of this process is described IEEE in Std.519 [82]. • The emission level cannot be affected. The compatibility level should be chosen suchthat it exceeds theenvironmentfor most equipmentmost of the time. An exampleof a disturbancewhere the emission level cannotbe of occurrencedependson the affected are voltage sags: their frequency fault frequency and on the power system, both of which cannotbe affected by theequipmentmanufacturer.N ote that the EMC standardsonly apply of to equipmentmanufacturers.We will later come back to the choice compatibility levels for these kindof disturbances. • The immunity level cannot be affected.The compatibility level should be chosen suchthat it is less than the immunity level for most equipment most of the time. An exampleof a disturbancewhere theimmunity level cannotbe affected is voltagefluctuation leading to light flicker. 2. Voltagecharacteristicsare quasi-guaranteed limits for someparameters,covering any location. Again the voltagecharacteristicsare based on a95% value, but now only in time. They hold at anylocation, and are thus an important parameterfor the customer.Voltage characteristicsare a wayof describingelectricity as aproduct. Within Europe the EN 50160standard defines someof the voltagecharacteristics.This standardwill be discussed in detail in Section 1.4.3. 3. Planning levels are specified by the supply utility and canconsideredas be internal quality objectivesof the utility. These ideas were originally developed fordisturbancesgeneratedby equipment,for which other equipmentcould be sensitive: mainlyradio frequency interference.These ideas have been extendedtowardsvariationslike harmonicdistortion or voltage fluctuations.The concepthas not yet beenappliedsuccessfullytowardsevents like voltage sags orinterruptions. EMC and Variations. Variations can be stochasticallydescribed through a probability distribution function, as shownin Fig. 1.20. The curve gives the probabilcompatibility level ity that the disturbancelevel will not exceed the given value. The can, accordingto the recommendationsin the IEC standards,be chosen at the95% percentile, asindicated in Fig. 1.20. The curve can hold for one site or for a large number of sites. When the curverepresentsa large number of sites it is important of the sites (typically950/0 of that it gives thedisturbancelevel not exceeded for most the sites).Consideras an examplethat the compatibility level of total harmonicdistortion (THO) is 0.08. Supposethe THO is measuredat 100 sitesduring 1000 10minute intervals. A compatibility level of 0.08 impliesthat at 95 sites(out of 100) at least 950THD samples (outof 1000) have a valueof 0.08 or less. In case a higher reliability isrequiredfor the successfuloperationof a device, a higher levelthan 950/0 should be chosen, e.g.,99.9%. 27 Section 1.4 • PowerQuality and EMC Standards u ~ u -; 0.75 .S ~ u ~ g 0.5 ~ o g 0.25 i .J:J Figure 1.20 Probability distribution function e ~ for a variation, with the compatibilitylevel indicated. O~~-------------------' Disturbancelevel inarbitraryunits EMC and Events. The EMC framework has not been developed for events For important power quality and its application to them has not been defined yet. phenomenalike voltage sagsand interruptions,the EMC standardscan thusnot be part why the EMC standardsare not (yet) wellknown used. This explains for a large in the powerquality field. Still an attemptshould be made atapplying the concepts of electromagneticcompatibility to events. Events onlyhappenoccasionallyand are not present allof the time;applying a 95°~ criterion is thereforeno longer possible. Animmunity to 95% of voltage sags would dependon the wayof countingthe sags.C ountingall sags below 200 V (in a 230 V supply) would give a much higher numberthancountingall sagsbelow 150 V. The immunity requirementin the latter case would be muchstricter than in the former. In some powerquality monitoringsurveys a95% criterionin space is applied. The of disturbance(numberof events) electromagneticenvironmentis defined as the level of the environmentin itself does not exceeded for950/0 of the sites. But the knowledge not sayanythingaboutequipmentimmunity requirements.The immunity requirement should be based on theminimum time between events exceeding the immunity level. Figure 1.21 shows the time between events exceeding certain a disturbancelevel as a function of the disturbancelevel (the severity of the event). The more severe the event equipment the more the time between events (the lower the event frequency). A of piece or an industrial process to which theequipmentbelongs will have acertain reliability requirement,i.e., a certain minimum time between events leading to tripping of the equipmentor interruption of the process. By using the curve in Fig. 1.21 this can be translatedinto an immunity requirement.As we will see later, theactual situation is more complicated:the severityof an event is amultidimensionalquantity as at least magnitudeand durationplaya role. A possiblecompatibilitylevel would be the levelnot exceeded morethanten times a year by95% of the customers.This can be done for anydimensionof the event, leading to amultidimensionalcompatibility level. Thisconcepthas beenappliedto the results of the Norwegianpower quality survey [67]. The frequency oftransientover950/0 site, is shown in Fig. 1.22. The 95% site is chosen such t hat voltage events, for the 95% of the sites have less transientovervoltageevents per yearthanthis site.From Fig. 1.22 we can see t hat reasonablecompatibility levels are: • 2.5 pu for themagnitudeof the transients. • 0.3 Vs for theVt-integral, 28 Chapt er I • Overview of Power Quality and Power Quality Standards 7 6 Desired reliability a:; ;;. .!! ., 5 -5 OJ) ~., ., .,o>< 4 ZJ .,<:: .,;;. .,<:: ., ~ ., ., a 3 .0 2 f:::: Disturbance level in arbitrary units Figure 1.21 Time between events as a function of the disturbancelevel. 500 400 ~.,;;. ""'d0 Z 300 1.0-1.5 200 100 2.0-3.0 3.0-5.0 0 5.0-10.0 Voltage-integral in Vs ~ . ~~ 't>~" ;s.'<S' ~~"<J 1-10 Figure 1.22 Ma ximumnumberof transientovervoltage events for 95% of the lowvoltagecustomers in Norw ay.(Data obtained from [67].) 29 Section 1.4 • PowerQuality and EMC Standards As a next step, these levels could be used as a basis for equipment immunity requirements. This concept could be worked out further by giving compatibility levels for 10 events and 1 event per year. Compatibility levelsfor 1event per year cannot be obtained from Fig. 1.22 because of the short monitoring period (about one year). 1.4.3 The European Voltage Characteristics Standard Europeanstandard50160 [80] describeselectricity as a product, including its shortcomings.I~ gives the main characteristics of the voltage at the customer's supply terminals in public low-voltage and medium-voltage networks under normal operating conditions. Some disturbances are just mentioned, for others a wide range of typical values are given, and for some disturbances actual voltage characteristics are given. Voltage Variations. Standard EN50160 gives limits for some variations. For each of these variations the value is given which shall notexceededfor be 95% of the time. The measurement should be performed with a certain averaging window. The length of this window is 10 minutes for most variations; thus very short time scales are not considered in the standard. The following limits forlow-voltage the supply are given in the document: • Voltagemagnitude:950/0 of the 10-minute averages during one week shall be within ± 10% of the nominal voltage of 230V. • Harmonicdistortion: For harmonic voltage components up to order 25, values are given which shall not be exceededduring 95% of the 10-minute averages obtained in oneweek. The total harmonic distortion shall not exceed 8% during 95% of the week. The limits have been reproduced in Table 1.1. Theselevels appear to originate from a study after harmonic distortion performed by a CIGRE working group [83], although thestandarddocument does not refer to that study. Inreference[83] two values are given for the harmonic voltage distortion: - low value: the value likely to be found in the vicinity of large disturbing loads and associated with a low probability of causing disturbing effects; highvalue: value rarely found in the network and with a higher probability of causing disturbingeffects. - TABLE 1.1 HarmonicVoltage Limits According to EN 50160 Order 3 5 7 9 II 13 RelativeVoltage 5 6% 5% 1.5% 3.5% 3% % Order Relative Voltage 15 17 19 21 0.5% 20/0 1.5% 23 25 1.5% 1.5% 0.50/0 30 ChapterI • Overview of Power Quality and PowerQuality Standards TABLE 1.2 Harmonic VoltageLevels in Europe[83J Order 3 5 7 9 II 13 Low 1.5°~ 4%) 4% 0.80/0 2.5% 2% High Order 2.5% . 6% 15 17 1% 5°AJ 19 O.8°.!cJ 1.5% 3.50/0 3% 21 23 25 Low High ~O.3°~ 2% 1.5°.!cJ ~O.30/0 0.80/0 0.8% 1.5% 1.5°AJ The valuesfound by the CIGRE working group havebeen summarizedin Table 1.2. The valuesused inEN 50160are obviously the valuesrarely exceededanywherein Europe.This is exactly what is implementedby the term "voltage characteristics." • Voltage fluctuation: 95% of the 2-hour long-term flicker severity values obtainedduring oneweek shall not exceed1. The flicker severityis an objective measureof the severity of light flicker due to voltagefluctuations (81]. • Voltageunbalance:the ratio of negative-and positive-sequence v oltageshall be obtainedas 10minute averages,95% of thoseshall not exceed2% during one week. • Frequency:95% of the 10secondaveragesshall not be outsidethe range49.5 .. 50.5 Hz. • Signaling voltages: 99% of the 3- secondaveragesduring one day shall not exceed9% for frequenciesup to 500 Hz,50/0 for frequenciesbetween1 and 10 kHz, and a thresholddecayingto 1% for higher frequencies. Events. Standard EN 50160 does not give any voltage characteristicsfor events. Most event-typephenomenaare only mentioned,but for some an indicative value of the event frequencyis given. For completenessa list of eventsmentionedin EN 50160 isreproducedbelow: • Voltage magnitudesteps: thesenormally do not exceed ±5°AJ of the nominal voltage, but changesup to ±100/o can occur a numberof times per day. • Voltagesags:frequencyof occurrenceis betweena few tensand one thousand events per year. Duration is mostly less than 1 second,and voltage drops rarely below 40%. At some places sags due to load switching occur very frequently. • Short interruptionsoccur betweena few tensand severalhundredstimes per year. The durationis in about 70% of the cases less t han 1 second. • Long interruptionsof the supply voltage:t heir frequencymay be lessthan 10 or up to 50per year. • Voltage swells (short overvoltagesin Fig. 1.16) occur under certain circumstances.Overvoltagesdue to short-circuit faults elsewherein the systemwill generallynot exceed 1.5 kV rms in a 230 V system. • Transientovervoltagewill generallynot exceed 6 kVpeak in a 230 V system. 31 Section 1.4 • PowerQuality and EMC Standards The 95% Limits. One of the recurring criticisms on the EN 50160standardis that it only gives limits for 95% of the time. Nothing is said about the remaining 5% of the time. Looking at the voltage magnitudeas an example:95% of the time the voltage is between207V and 253V (10% variation around the nominal voltage of 230V), but during the remaining 5% of the time the voltage could be zero, or 10000 V, and the voltagewould still conform with the voltagecharacteristics. The voltage magnitude(rms value) is obtainedevery 10 minutes-thatgives a total of 7 x 24 x 6 = 1008 samplesper week; all but 50 of thosesamplesshould be in the givenrange.If we only considernormal operation(as isstatedin the document)it would be very unlikely that these are far away from the ±lOOiO band. Understanding this requiressomeknowledgeof stochastictheory. In normal operation,the voltageat the customeris determinedby a seriesof voltagedropsin the system.All of thoseareof a stochasticcharacter.According to stochastictheory, a variablewhich is the sum of a sufficient numberof stochasticvariables,can be describedby a normal distribution. The normal distribution is one of the basicdistributionsin stochastictheory: its probability densityfunction is 1 (V-Il)2 f(v) = --e-J;2 (1.3) .J2ira where v is the value of the stochasticvariable, It its expectedvalue, and (1 its standard deviation. The well-known bell-shape of this function is shown in Fig. 1.23 for It = 230V and (1 = 11.7V. Thereis no analyticalexpressionfor the probability distribution function, but it can be expressedin the so-callederror function <1>: F(v) = [f(t/J)dt/J = <I>[V : /l] (1.4) The voltage characteristicsstandardgives the expectedvalue (230V) and the 950/0 interval (207 .. 253 V).Assumingthat the voltageis normally distributedwe cancalculate the standarddeviationwhich resultsin the given 95% confidenceinterval. As 95% of the voltagesamplesare between207 and 253 V, 97.50/0 is below 253 V, thus: <1>[253V ~ 230V] = 0.975 (1.5) 3.5,.--------.----,----.----.:.--.,....----, 5e ~ 3 2.5 .53 .~ a 2 -8 g 1.5 ~e ~ 0.5 O'---.:=-----L--------J~_---I~_----I--=----' Figure 1.23 Probability density function of the normal distribution. 180 200 220 240 Voltagein volts 260 280 32 Chapter 1 • Overview of Power Quality and Power Quality Standards From a table of theerror function, which can befound in almostany book on statistics or stochastictheory, we find that <1>(1.96) = 0.975 which givesa> 11.7V. Knowing expectedvalue and standarddeviation of the normal distribution, the wholedistribution is known. It is thus no longerdifficult to calculatethe probability that the voltage deviatesmore than 10% from its nominalvalue. The resultsof this calculationare given in Table 1.3. The firstcolumngives theprobability that the voltageis within the voltage range in thesecond,third, and fourth columns.The voltagerange is given instandard deviations,in volts and as a percentageof the nominal voltage. The voltage is thus between 200 and 260 V for990/0 of the time. The lastc olumn indicateshow often the voltageis outsideof the range,assumingall samplesto bestochasticallyindependent.In reality there isstrong correlation between thesampleswhich makesthat large deviations become even more unlikely. Further, there arevoltage regulation mechanisms (capacitor banks, transformertap-changers)which become active when the voltage deviatestoo much from itsnominal value. Finally, one should realize that the 95% value given in thestandarddoes not hold for the averagecustomerbut for the worstservedcustomer.All this leads to theconclusionthat voltagemagnitudevariationsof much morethan 10% are extremelyunlikely. From this reasoningone should absolutely not draw the conclusion that the voltage magnitudewill never be lowerthan a value like 80%. The mainassumption used isthat the voltage variations are due to the sumof a numberof small voltage drops. During, e.g., a voltage sag, this nolonger holds. This brings us back to the principal differencebetween"events" and "variations": for variationsthe normal distribution can be used; for events it is the time betweenevents which isof main importance. Theprobabilitiesin Table 1.3 thus only hold for voltagemagnitudevariations; absolutelynothing is said yetabout voltagemagnitudeevents. Scope and Limitations. StandardEN 50160containssome well-defined limits and measurementprotocols,but it falls short of putting responsibilitywith any party. This is of courseunderstandablewhen one realizesthat the documentdescribes the "voltage characteristics"which is the electromagneticenvironmentas it is now, not as it should be, and not even as it will be infuture. Of coursethe underlying thought is that the situation will not become worse andthat it is up to the utilities toensure this. When interpretingthis standardit is also very important to realize that it only appliesunder"normal operatingconditions."The documentspecifies a listo f situations to which the limits do not apply.T his list includes "operationafter a fault," but also "industrial actions" and such vague terms as "force majeure" and "power shortages due to externalevents."This list removes a loto f the potential value from the document. A descriptionof the electromagneticenvironmentshould include all eventsand TABLE 1.3 Probability of Voltage Exceeding Certain Levels Probability 95% 99% 99.9% 99.99% 99.999% 99.9999% Frequency Voltage Range ± 1.960' ± 2.580' /l ± 3.290' /1. ± 3.900' J.,l ± 4.420' J.,l ± 4.890' u J-L 207-253 V 200-260 V 193-268 V 184-276 V 178-282 V 173-287 V ±IO% ±13% ±17% ±200/o ±23% ±25% 50 per week 10 per week I per week 5 per year t per 2 years 1 per 20 years Section 1.4 • PowerQuality and EMC Standards 33 variationsto which acustomeris exposed, notjust those which occurduring "normal operating conditions." A voltage sagduring a severe lightningstorm (exceptional weather) is equallydamagingas a sagduring a sunnyafternoonin May. Looking at the documentin a more positive light, one can say that it only gives limits for what we have called"variations";voltage quality"events"are not covered by the document. What Next? Despite all itsshortcomings,EN 50160 is a very gooddocument. It is probably the bestthat could be achievedunder the circumstances.One should realize that it is the first time that the electromagneticenvironment has been described in such detail in an official document.Although limits are only given for some of the phenomena,and although the standardonly applies during normal operation,and althoughabsolutely noguaranteesare given, at least a first step is set. Based on thisstandardone can see a numberof developments: • Utilities all over Europehave startedto characterizetheir voltagequality by using themeasurements as defined in EN 50160; thus 10-minute averages are the etc. The takenof the rms voltage, 10-minute averages of harmonicvoltages, characterizethe values not exceeded during 95% of the time are then used to local voltage quality. Aproblemis that some utilities thencomparethe results with the EN 5160 limits and state t hat their voltagequality confirms with the Europeanstandards.Understandingthe conceptof voltagecharacteristics,it is TABLE 1.4 Voltage Characteristics as Published by Goteborg Energi Basic Level Phenomenon Voltage Variations Magnitude variations Harmonic voltages Voltage fluctuations Voltage unbalance Frequency Voltage shall be between 207 and 244 V Up to 4% for odd harmonic distortion Up to l°,.{, for even harmonic distortion Up to 60/0 THO Up to 0.30/0 for interharmonic voltages Not exceedingthe flicker curve Up to 20/0 In between 49.5 and 50.5 Hz Voltage Events Magnitude steps Voltage sags Short interruptions Long interruptions accidental planned Transients Frequent events shall be less than 3°.!cl in magnitude No limits No limits On average less than one in three years On average shorter than 20 minutes Individual interruptions shorter than 8 hours On average less than one 18 in years On average shorter than 90 minutes Individual interruptions shorter than 8 hours The utility tries to minimize size and frequency of transients whichinfluencecustomers 34 ChapterI • Overview of PowerQuality and PowerQuality Standards no surprisethat the local voltagequality is betterthan the limits given in the standard.This result should thus absolutelynot be used by a utility to show that their supply is goodenough.The statement" our supply confirms with EN 50160" isnonsense,as thestandarddoesnot give requirementsfor the supply, but only existingcharacteristicsof the worst supply in Europe. • Some utilities have come up with their own voltage characteristicsdocument, which is of coursebetter than the one described in the s tandard.The local utility in Gothenburg,Sweden hasdistributeda flyer with the limits given in Table 1.4. The term"voltage characteristics"is actually not used in the flyer; insteadthe term "basic level" is used [108]. • Measurementsare beingperformed all over Europe to obtain information about other power quality phenomena.For voltage sags,interruptions,and transient voltages no limits are given in the existing document. A voltage characteristicfor voltagesags,and for other events, ishard to give asalready mentionedbefore. An alternativeis to give themaximum numberof events below a certain severity, for 95°A, of the customers.Figure 1.22 gives this voltage characteristicfor transient overvoltage, as obtained through the NorwegianPowerQuality survey [67]. Such a choiceof voltage characteristic would be inagreementwith the useof this same950/0 level for thedefinition of the compatibility level. Long Interruptions and Reliability Evaluation 2.1 INTRODUCTION 2.1.1 Interruptions A long interruption is a power quality event during which the voltage at a customerconnectionor at theequipmentterminalsdropsto zero and does not come back automatically.Long interruptionsare one of the oldestand most severepower quality concerns.The official IEC definition mentionsthree minutesas theminimum duration of a long interruption. An interruption with a duration of less than three minutes shouldbe called a"shortinterruption."Within the IEEE standardsthe term"sustained interruption" is used forinterruptionslastinglongerthan 3 seconds[IEEE Std. 1159] or longer than2 minutes[IEEE Std. 1250]. In thischapterthe term"long interruption"will be used as aninterruption which is terminatedthroughmanualaction, thus not automatic. An interruptionterminatedthroughautomaticreclosureor switching, is called a "short interruption" and will be treatedin detail in Chapter3. 2.1.2 Reliability Evaluation of Power Systems An area of researchcalled "power system reliability" has developed,in which numberand duration of long interruptionsare stochasticallypredicted.This areahas long beenconfined to universities and to industrial power systems,but the recent interestin power quality in all its aspects hascausedincreasedactivities in reliability both at universities and in utilities. Anadditional reasonfor the increasedinterestin reliability is the availability of cheapfast computers.In the past reliability evaluation studiesof realistic power systemsrequiredlarge computers,gross simplifications,and long calculationtimes. Many ideasproposedin the pastcan only now beimplemented. Someof the basicsbehind reliability evaluationof power systems will be discussed in Sections 2.4 and 2.5; some exampleswill be presentedin Section 2.8. 35 36 Chapter2 • Long Interruptionsand Reliability Evaluation 2.1.3 Terminology In this chapterthree terms willa ppearregularly: failure,outage,and interruption. In daily life their meaningsare interchangeable,but in the reliability evaluation of power systems, there are clear and importantdifferences. • Failure. The term failure is used in the general meaningof the term: a device or system which doesn ot operateasintended.Thuswe can talkabouta failure of the protectionto clear a fault, but also of the failure oftransformer,and a even about the failure of the public supply. • Outage. An outageis the removalof a primary componentfrom the system, e.g., atransformeroutageor the outageof a generatorstation.A failure does not necessarily have to lead to an outage,e.g., the failure of the forced cooling of a transformer.And the other way around,an outageis not always due to a failure. A distinction is thereforemade between"forced outages"and "scheduled outages."The former are directly due to failures, the l atter are due to operatorintervention.Scheduledoutagesare typically to allow forpreventive maintenance,but also theaforementionedfailure of the forced cooling of a transformercould initiate the schedulingof a transformeroutage. • Interruption. The term interruption has already been used before. It is the situation in which a customeris no longer supplied with electricity due to one or moreoutagesin the supply. In reliabilityevaluationthe terminterruption is used as theconsequenceof an outage(or a number of overlapping outages),which is in most cases the same as the definition used in the power quality field (a zero-voltagesituation). 2.1.4 Causes of Long Interruptions Long interruptionsare always due tocomponentoutages.Componentoutages are due to threedifferent causes: I. A fault occurs in thepower system which leads to an intervention by the power systemprotection. If the fault occurs in apart of the systemw.hich is not redundantor of which the redundantpart is out of operationthe intervention by the protectionleads to aninterruptionfor a numberof customers or piecesof equipment.The fault is typically ashort-circuitfault, but situations like overloadingof transformersor underfrequencymay also lead to long interruptions.Although the results can be very disturbingto the affected customers,this is acorrectinterventionof the protection.Would the protection not intervene,the fault would most likely lead to an i nterruption for a damageto the electrical much largergroupof customers,as well as to serious equipment. As distribution systems are oftenoperatedradially (i.e., without redundancy) andtransmissionsystems meshed (with redundancy),faults in transof the supply, mission systems do not have much influence on the reliability but faults indistribution systems do. 2. A protectionrelay intervenesincorrectly, thus causinga componentoutage, which might again lead to a long interruption. If the incorrect tripping (or maltrip) occurs in apart of the systemwithout redundancy,it will always lead Section 2.2 • Observationof SystemPerformance 37 to an interruption. If it occurs in apart of the system withredundancythe situationis different. For a completelyrandommaltrip, the chancethat the redundantcomponentis out of operationis rather small. Randommaltrips are thus not a serious reliability concern redundantsystems. in However malt rips are often not fullyrandom, but more likely when the system is protection: a correct faulted. In that case there will be two trips by the interventionand anincorrectone. Themaltrip trips the redundantcomponent just at themomentthat redundanceis needed.Fault-relatedmaltripsare a seriousconcernin redundantsystems. 3. Operatoractionscause acomponentoutage which can also lead to a long interruption.Some actionsshouldbetreatedas abackupto the power system protection,either correct or incorrect. But an operatorcan also decide to switch off certain parts of the system for preventive maintenance.This is a very normalactionand normally not of any concern tocustomers.There is in most cases at least some level redundancyavailable of sothat the maintenance does not lead to an interruptionfor any of the customers.In some lowvoltage networksthere is noredundancypresent at all, which impliesthat preventive maintenanceand repair or changes in the system can only be performedwhen the supply to apart of the customersis interrupted.These interruptions are called "scheduledinterruptions" or "planned interruptions." The customercan take someprecautionsthat make the consequences of the interruptionlessthan for a nonscheduledinterruption.This of course assumesthat the utility informs thecustomerwell in advance,which is unfortunatelynot always the case. 2.2 OBSI!RVATION OF SYSTEM PERFORMANCE Long interruptions have long beenconsideredas somethingworth preventing: the numberand duration of long interruptionswas viewed as themeasureof how good the supply was.T oday we would call it a powerquality indicator Of, in lEe terms, a voltage characteristic. Many utilities have recordsof numberand durationof interruptions,but mostly for internal use. Theamount of publishedmaterial is relatively low. That not only makes ithard to getinformationaboutsupply performancefor educationand research purposes,but even forcustomersit is often hard to find out what the reliabilityof the supply is. The former is j ust an inconvenience, the latteris a serious concern. A positive exception to this is theprivatizedelectricity industryin the United Kingdom. The data presented in theremainderof this section has mainly been obtainedfrom the reports published by the British Officeof Electricity Regulation(OFFER) [109]. Some additional information has beenobtainedfor The Netherlands[110], [111]. 2.2.1 Basic Indices As alreadymentionedin Section 1.3.2 the mainstochasticcharacteristicof any voltagemagnitudeevent is the time between events, or (which is in effect the same) the numberof events per year. The latter is indeed oneof the maincharacteristicscollected for long interruptions.Figure 2.1 shows the average numberof interruptionsper customer for six consecutiveone-yearperiods. When the U.K. electricityindustry was privatized in December1990 there was a serious concern that the reliability of the Chapter 2 • Long Interruptions and Reliability Evaluation 38 .... E 1.2-,---- -- - - - - - -- - - - ----, o '@ o l:; ~ 0.8 c: 1 o 06 . .5 0.4 '- ~ 0.2 OJ § Z 0 90/9 1 91/92 92/93 93/94 Monitoring period 94/95 95/96 Figure 2.1 Numberof interruptionsper customer.average forGreat Britain. (Data obtainedfrom (1091.) supply woulddeteriorate. Figure 2.1 clearly shows t hat this has not been the case; the numberof supply interruptionshas stayedremarkablyconstant. Individual interruptions arecharacterizedthrough their duration,i.e., the time it takes until the supply isrestored. Often the averaged uration of an interruptionis not published but instead the total durationof all interruptionsduring one year is provided. This value is referred to as the "minuteslost perconnectedcustomer"or more correctly as theunavailability of the supply. Thedata for Great Britain (Wales,Scotland,and England)is shown in Fig. 2.2. We again see that the reliability of the supply remained constant,with the exception of the year 1990/91, during which severe blizzards made it impossible to restore the supply within a few hours. The numberof interruptionsdue to this severeweatherwas relatively small. as can be concludedfrom Fig. 2.1, but its duration had a seriousimpact on the unavailability of the supply . that The collectionof this datais less trivial thanit may look . One should realize most utilities do notautomatically become awarethat the supply to one or more customersis interrupted. It is typically the customersthat report an interruption to the utility . The startingmomentof an interruption,and thus theduration,is therefore not always easy todetermine.The total numberof long interruptionsin the service territory of a utility can beobtainedsimply by counting them , as eachinterruption requires anoperatoraction for the supply to be restored. The numberof customers affected by aninterruption requires a studyof customerrecords which is often time consuming. Some utilitiesjust assume a fixedamountof customersconnectedto each feeder, whileother utilities link the interruption records with theircustomerdatabase . 250-,---- - -- -- -- -- - -- - - --, ~ " 200 ~ :.§. :€ {j 150 100 =a g 50 ;:J o 90/9 1 91/92 92/93 93/94 Monitoring period 94/95 95/96 Figure 2.2 Unavailability of the supply. average forGreat Britain. (Data obtained from [109].) 39 Section 2.2 • Observationof SystemPerformance The calculationof the indices from the collected d atacould proceedas follows. Considera utility serving N,o, customers.During the reporting period (typically one year) a total of K outagesin the system lead to aninterruption for one or more customers.Interruption i affects N, customersand has aduration of D; minutes. The averagenumberof interruptionsper customerper yearI is given by (2.1) The underlying assumptionoften used in theinterpretationof this data is that the system average over 1 year, equals customeraverage the overmany years. Thus I would also be the expected numberof interruptionsper year for eachcustomer.But variations in customerdensity, system design and operation, and weather patterns, make that not all customersare equal from a reliabilitypoint of view. The averageunavailabilityper customerq, in minutesper year, may be calculated as K LN;D; - ;=1 q=--- »: (2.2) The averagedurationof an interruption D is (2.3) This value isredundant,as it may becalculatedfrom (2.1) and (2.2) by using the following relation: - q D== A (2.4) Utilities often publish two of these three values, X, q, D. Note that (2.3) gives theaverageduration of an interruption from a customer perspective.From a utility perspectiveanothervalue is alsoof interest: the average duration per interruption, Dint, calculatedas (2.5) This value givesinformation abouthow fast a utility is able torestorean interruption. The outcomeof (2.4) and (2.5) iscertainly not the same.I nterruptionsserving more customers,originating at higher voltage levels, tend to haveshorterduration. a Thus the averagedurationper customeris likely to beshorterthan the averagedurationper interruption.Which valueshould be used is open for discussion. 40 Chapter2 • Long Interruptionsand Reliability Evaluation 2.2.2 Distribution of the Duration of an Interruption We will later seethat the costsof an interruption increasenonlinearly with the durationof the interruption.The averagedurationof an interruptionwill thusnot give the average cost. Tocalculate the latter, information about the distribution of the durationshouldbe available.The U.K. utilities publish information aboutthe percentage of interruptions restored within 3 hours and the percentageof interruptions restoredwithin 24 hours. This is part of the so-called"overall standardsof service" which we will discuss inSection 2.3. The assumptionmade in almost all reliability evaluationstudiesis that the componentoutageduration as well as the supplyinterruption durationareexponentiallydistributed.The exponentialdistribution,also called "negative-exponentialdistribution," is the basicdistribution of most reliability evaluation techniques,as we will see in Section 2.5. The probability distribution function of the exponentialdistribution can be expressed as F(t) = I - e-t (2.6) where T is the expected value o f the stochasticvariable,which will be estimatedby the averageduration. Knowing the averageduration, e.g., from Table 2.2 and Table 2.3, the percentageof interruptionsrestoredwithin a time t} may bedeterminedas (2.7) Table2.1 gives thepercentageof interruptionsrestoredwithin 3 hoursfor a numberof British distributioncompanies.The values in thecolumnslabeled"practice" have been obtainedfrom [109], the values in thecolumnslabeled "theory" have beenobtained from (2.7) by using theaverageduration of supply interruptionsfor the same year. Using the averagedurationandassumingan exponentialdistributionwill overestimate the impact of interruptions:the numberof interruptionslonger than 3 hoursis significantly lessthanwould be expected from the measuredaverage. This is clearly a case for more detailedreportingof the distributionof the durationof both componentoutages and supplyinterruptions.It also calls forincluding nonexponentialdistributionsin the reliability evaluation. Figure 2.3 shows theprobability density function of the durationof all interrupt hat the tions obtained for The Netherlandsbetween 1991 and 1994 [112]. We see majority of interruptions has a duration between 30minutes and 2 hours, with a TABLE 2.1 Distribution of Interruption Duration, 1996/97 Values for Various British Utilities: Theory and Practice Supply Not RestoredWithin 3 Hours Company AverageDuration in Hours A 2.38 B C 1.38 D E 1.45 1.63 F G 1.62 2.27 1.38 H 1.42 Source: Data obtainedfrom [109]. Theory Practice 28.4% 11.4% 12.1o~ 12.6% 26.7% 19.3°AJ 9.8°AJ 7.3°AJ 7.0% 11.5% 8.6°AJ 13.4°AJ 11.4% 7.1% 15.90/0 15.7°~ 41 Section2.2 • Observationof SystemPerformance TABLE 2.2 Numberof Interruptions perCustomerper Year X for Some British Utilities Distribution Company A B C D E F G H ReportingYear 90/91 91/92 92/93 93/94 0.41 0.58 1.70 0.76 2.85 1.46 0.82 1.69 0.47 0.62 1.11 0.68 2.29 1.29 0.74 0.82 0.38 0.57 1.29 0.96 1.95 1.18 0.86 0.75 0.37 0.56 1.25 0.59 2.14 1.19 0.89 0.92 94/95 0.40 0.70 1.21 0.65 2.20 1.24 0.70 0.96 95/96 0.33 0.61 1.39 0.85 2.23 1.16 0.62 0.97 Source: Data obtainedfrom (109). TABLE 2.3 Distribution Company A R C D E F G H SupplyUnavailabilit~ q for Some British Ut ilities Repor ting Year 90/91 91/92 92/93 93/94 94/95 95/96 51 88 398 76 325 185 185 1004 67 75 118 65 212 176 108 87 53 52 69 144 63 200 167 121 97 58 70 128 94 212 133 102 105 54 67 151 85 233 111 88 95 77 122 91 212 184 129 87 Source:Data obtainedfrom (109). 6 Figure 2.3 Distribution ofd urationof interruption, The Netherlands , 1991- 1994. (Reproducedfrom Hen drik Boers and Frenken(112).) 50 100 150 200 250 Duration of interruption in minutes 300 long tail up to 5 hours What . is a moreimportantconclusionis that the distribution is absolutely notexponential.(The density functionof the exponentialdistribution has its maximum for zeroduration and continues to decay afterthat.) To estimate the expected costsof interruption it is important to take thisdistribution into account. However, most studies still assume exponentialdistribution. an 42 Chapter2 • Long Interruptionsand ReliabilityEvaluation 2.2.3 Regional Variations Both Fig. 2.1 and Fig. 2.2 give the average supply reliability for the whole of GreatBritain. An old questionis, how useful is thisdatafor an individual customer.No informationaboutindividual customersis available,but separatedataare availablefor each of the 12d istributioncompanies[109]. Someof this datais shownin Table2.2 and Table 2.3. In Great Britain the distribution companiesoperatethe voltage levels of 132 kV and lower. As will beshownin Table2.4 their systems are responsiblefor 97°~ of the numberof interruptions,as well as for97% of the unavailability. The comparison between thedifferent utilities can giveinformationabouthow differences in system design and operation influence the supply performance.Apart from the adverseweatheryear 90/91 thenumber of interruptionsand the supply unavailability have remained remarkably constant. An accurate stochastic prediction method should thus be capable of reproducing these numbers, an interesting challenge. We will come back to thecomparisonbetweenobservationand predictionin Section2.7. TABLE 2.4 Contributionsto the Supply Performance in Great Britain, 1995/96 Number ofInterruptions Unavailability per Customer per Customer per Year Total Low voltage (240/415 V) 6.6 and 11 kV 33 kV 132 kV Other Scheduled 1.03 0.06 0.63 0.13 0.06 0.03 0.12 158 min 22 min 81 min 12 min 7 min 4 min 32 min Average Duration of an Interruption 150min 140/0 52% 8% 4% 3% 20% 370 min 130min 90 min 120min 130 min 270 min Source: Data obtainedfrom [109]. From Table 2.2 and Table 2.3 we can also see t hat companiesC, E, and H suffered most from the severe weatherin 90/91. It is possible tocalculatethe average duration of an interruptionfor eachof the distribution companies,by using (2.4).For companyH we obtainfor the year 90/91:D = ll~: = 594minutes,almost 10hours.For the year 91/92 theaverageduration of an interruption was only 106 minutesfor the samecompany. An evenfurther subdivisionhas been made in [109]: for each so-called"operation unit" within the utility values are given forn umberof interruptionsand unavailability. Based on thisdata a probability density function has beenobtainedfor the unavailability of operationunits. The results areshown in Fig. 2.4 and Fig. 2.5. Thelatter figure includes the units with the highest unavailability. We seethat 50% of the units have anunavailability between50 and 100minutesper year.The 950/0 percentileof the distribution is at 350 minutes. It is obvious from this graph that the averageunavailability doesnot give anyinformation aboutthe unavailabilitywhich can be expected by a specificcustomer.One shouldnote that this is not thedistribution for the customers, as not all operationunits have the samenumberof customersand not all customers within one operationunit have the sameunavailability. Getting such agraph for all customerswould require a much more intensivedata collection effort than currently being done. 43 Section 2.2 • Observationof SystemPerformance 10 .§tJ 8 C+-c 6 .8 4 0 ~ 2 O~ 0 Figure 2.4 Probability density function for the averageunavailability in Great Britain. (Data obtainedfrom [109].) 0 f") I N 0 tn ; I 0 '" 1 \0 0 0\ ...!. 00 -, § ~ 0 ~ ~ ~ - -0 V) , ~ 0 '" I § Interrupted minutes ~ I 00 2 0 (5 M N ~ N f") ~ 0 V) N I ~ N 10......--...---------------------, 9 tJ 8 .~ ~o .8 7 6 5 §4 Z 3 2 1 Figure 2.SExtensionof Fig. 2.4 toward higher values. 2.2.4 Origin of Interruptions The data on numberand duration of interruptionsmight be veryinterestingby itself, especially forcustomers,but they donot directly lead to anyunderstandingof the causes ofinterruptions.For that purpose,additionaldatacollectionis required.A first step is toobtaindataon the voltage level at which the outageoccurredwhich led to the interruption. Table 2.4 gives thisdata for Great Britain over the year 1995/96. The values for other years are very similar. We see that the major contribution to the number of interruptions,as well as to theunavailability, comes from the medium voltage network (6.6 and 11kV). Anexplanationfor this is not too difficult to give. Thesenetworkshave noredundancyso thata componentoutageimmediately leads to a supply interruption. The 33 kV network is partly operatedas a loop, hence its lower contribution. The low voltage network is also operatedradially, thus without any redundancy,still its contributionis rathersmall. This is because a low voltage customer of medium voltage feederthan of low voltage is exposed to much more (kilo)meters feeder. Thus, there will thus be much more outages affectingcustomerat the medium voltagethanat low voltage. Anadditionalfactor is that a largerpart of the low voltage networkis underground,which accountsfor a lower failure rate. Thedatain Table 2.4 that an are showngraphically in Fig. 2.6 and Fig. 2.7. These figures again confirm increased reliability of the supply can only be achieved throughinvestmentat distribution level. An importantconclusionfrom Table 2.4, Fig. 2.6, and Fig. 2.7 that is the longestinterruptionsare due to scheduled outages and outages at low voltage level. But 44 Ch apt er 2 • Long Interruptions andReliability Evaluation Other 3% 33 kV 12% Figure 2.6 Contributionsto the numberof supplyinterruptionsin Great Britain . (Data obtainedfrom [109].) Other 3% 132 kV 4% Figure 2.7 Contributionsto the unavailability of the supply inGreat Britain. (Data obtainedfrom [109].) as theseoccur less oftenthan interruptionsdue tooutagesat medium voltage level, the latter make the largestcontribution to the unavailability of the supply . Surveys inother countriesconfirm that the majority of interruptionsis due to outagesat medium voltage level. Table 2.5 gives interruption data obtainedin The Netherlandsover the period 1991 through 1995 [110]. ("High voltage" is typically 150kV and 380kV, "medium voltage" 10 kV, and "low voltage" 400 V.) Here we see the somewhatremarkablephenomenonthat about one third of the interruptionsfor urban customersare due tooutagesin high voltage networks. This is due to the large consumerdensity in the cities, and due to the fact that all low voltage and medium voltage distribution is underground. The numberof outages in medium voltage networks is thereforesimply very low. The high voltagenetworksare mainly overhead, which makes themcomparableto the U.K. situation. We see 6interruptionsper 100 customersin The Netherlandsand 9 per 100customersin the U.K. ("132 kV" and "others"), indeed a similar number. Like in the U.K ., the unavailability of the power supply in TheNetherlandsis mainly due to the medium voltage distribution network. Figure 2.8 shows thecontributionsof the three voltage levels to the interruption frequency, between 1976 and 1995, for the average low voltage customerin The Netherlands.The contribution of the low voltage and medium voltage systems to the interruptionfrequency isratherconstant.The contributionof the high voltage network 45 Section 2.2 • Observationof SystemPerformance TABLE 2.5 Supply Performancein The Netherlands,1991-1995 Urban Customers High Voltage Medium Voltage Numberof interruptions 0.06/year 29% 2 minutes 15% Unavailability 26 minutes Interruptionduration 0.12/year 58% 9.5 minutes 73% 75 minutes Low Voltage Total O.OI/year 50/0 1.5 minutes 12% 198 minutes 0.21/year 13 minutes 62 minutes All Customers High Voltage Medium Voltage Low Voltage Total Numberof interruptions 0.06/year 22% Unavailability 2 minutes t 1% Interruptionduration 26 minutes 0.20/year 740/0 15 minutes 79% 75 minutes 40/0 O.OI/year 2 minutes 110/0 199 minutes 0.27/year 19 minutes 70 minutes Source: Data obtainedfrom [110]. 0.4 i' 0.35 t) >- !, 0.3 ~ 0.25 6 t 0.2 ¢:l a r .:;: 0.15 Figure 2.8 Numberof interruptionsper year for the averagelow voltagecustomerin The Netherlands,1976-1995,with contributions from low voltage(x), mediumvoltage(0), and high voltage( +) systems.(Reproducedfrom van Kruining et al. [110].) ..= 0.1 0.05 Ol..------J.------L.----....L.---~ 80 85 90 95 Year varies much more. In some years (1985, 1991)contribution its is negligible, while in other years (1990) they make up half of the numberof interruptions.This large variation is partly of a stochasticnature(the numberof outagesof high voltagecomponents leading to aninterruptionis very small)but also due toweathervariationshaving more influence on the (mainlyoverhead)high voltagenetwork than on the (mainlyunderground)mediumvoltage and lowvoltagenetworks. Figure2.9 shows theprobabilitydensityfunction for the durationof interruptions originatingat different voltage levels in The Netherlands[Ill]. For interruptionsdue to high voltage componentoutages,the majority of durations is short: about 75% is shorter than 30 minutes. Outagesin the medium voltageand low voltage networks (typically 10kV and 400 V, respectively, in The Netherlands)lead to longer interruptions. For medium voltage onlyabout 15% of the interruptionsis shorter than 30 about 5%. This has to do with the minutes, for low voltage this value is even lower: methodsused forrestorationof the supply.Outagesin the high voltage networksare normally restoredvia operatorinterventionfrom a centralcontrol room. In medium voltage and low voltage networksthere is no suchcontrol room and both fault locaFrom the density lization and restorationof the supply has to take place locally. functions in Fig. 2.9 it is clearthat 30 minutes is about the minimum time needed 46 Chapter2 • Long Interruptionsand Reliability Evaluation High voltage 60 % 50 40 30 20 10 O'---.£""""",L-L- 0-1/4 114-112 1/2-1 1-2 2-4 Duration in hours 4-8 8-16 16-32 4-8 8-16 16-32 4-8 8-16 16-32 Medium voltage 40 % 35 30 25 20 15 10 5 O'--'=L-L- 0- 1/4 1/4-1/2 1/2-1 1-2 2-4 Duration in hours Low voltage 30 % 25 20 15 10 5 o'--'"'-=L-.L._ 0-1/4 1/4·112 112-1 1-2 2-4 Duration in hours Figure 2.9 Probability den sity function for duration of interruptions,originating at three voltage levels in The Netherlandspower systems. (Reproduced from Waumans[III].) for this. Almost 100% of medium and low voltage networksin The Netherlandsare underground. Restorationof the supply takes place normally via switching in radially operatedloops . 2.2.5 More Information From recording interruption events, much moreinformation can beobtained than just averageduration and frequency . We already saw origin of the interruption and theprobability distribution of the durationas examples ofadditionalinformation. The amountof information that can beobtaineddepends on how detailed the record of the interruptionis. There are twoapplicationsfor the recordedinformation, each with their own requirements : This mainly requiresinformation about the I. Increase the quality of supply. origin of interruptions and the way in which the supply is restored. For 47 Section 2.2 • Observationof SystemPerformance example,the knowledgethat most interruptionsoriginateat mediumvoltage level teaches usthat most gain can beobtainedby improvementsthere. But supposethat for a certaincustomerinterruptioncostsare small forinterrupequipmentis supplied tion durationsup to 2 hours, e.g., because essential through a battery backup (an uninterruptablepower supply or UPS). By using Fig. 2.9 it is shownthat improvementsin the low voltage network become moreappropriate.To make such a decision it is obvious that more data is neededthanjust interruption frequencyand unavailability. 2. Serve as inputdatafor reliability evaluation studies. Thisrequiresa lot more data, not just about interruptions but also about outagesnot leading to interruptions.Most utilities and industriesdo keepinformation about outage frequenciesand durationsof components,but not much of it is openly available. Some large surveys have been performed to obtain outage frequencies: e.g., by theIEEE Industry Applications Society for industrial power systems [21], and byCIGRE for componentsof high voltage networks [197]. What is clearly still missing aredata on failure of the power system protection, and probability distributions for time betweenoutages and time to restorethe component.Especially thelatter could become very important in future reliability evaluationstudies, as theinterruption costs, and thus theinterruption duration, becomes the desired o utput. A detailed literature survey performedby the author in the early 90s resulted in suggestionsfor expectedcomponentlifetimes [107]. The resultsof that study are reproducedin Table 2.6. TABLE 2.6 SuggestedValues for Number of Component Outages and Failures Component Type Number of Outages per Number of Outages per 1000Components per Year Component per Year MV IL V transformers MV /MV transformers HV jMV transformers MV and LV circuit breakers Disconnect switches Electromagnetic relays Electronic relays (single function) Electronic relay systems Fuses Voltage and current transformers Standby generators failure to start Continuous generators UPS inverter UPS rectifier Underground ·cable (1000 meters) Cable terminations Cable joints Busses(one section) Large motors Source: [107]. Failure Probability 1-2 10-12 14-25 0.2-1 1-4 1-4 5-10 3D-100 0.2-1 0.3-0.5 20-75 0.5-20/0 0.3-1 0.5-2 30-JOO 13-25 0.3-1 0.5-2 0.5-2 30-70 48 Chapter2 • Long Interruptionsand Reliability Evaluation 2.3 STANDARDS AND REGULATIONS 2.3.1 Limits for the Interruption Frequency Long interruptions are by far themost severepower quality event; thus any documentdefining or guaranteeingthe quality of supply should contain limits on frequencyand durationof interruptions.The internationalstandardson powerquality do not yet give anylimitations for interruption frequencyor duration. The European voltage quality standardEN 50160 (see Section 1.4.3) comes closeststating by that "under normaloperatingconditionstheannualfrequencyof voltageinterruptionslonger thanthreeminutesmay be less than 10 or up to 50dependingon the area."The document also statesthat Hit is notpossibleto indicate typicalvaluesfor the annualfrequency and durations 0.[longinterruptions." Many customerswant more accurate limits for the interruption frequency. Therefore, some utilities offer their customersspecial guarantees,sometimescalled "power quality contracts."The utility guaranteesthe customerthat there will be no more than a certain number of interruptionsper year. If thismaximum number of interruptionsis exceeded in a given year, the utility will paycertainamountof a money per interruptionto the customer.This can be a fixedamountper interruption,defined in the contract,or the actualcosts and lossesof the customerdue to theinterruption. Some utilities offervariouslevelsof quality, with differentcosts. Thenumberof options is almost unlimited: customerwillingness to payextra for higher reliability and utility creativity are the maininfluencingfactors at the moment.Technicalconsiderationsdo not appearto play any role insettinglevels for themaximumnumberof interruptions or the costsof the various options. For a customerto make adecisionaboutthe best option, datashouldbe available,not only aboutthe averageinterruptionfrequencybut also on theprobability distribution of the numberof interruptionsper year. Contractualagreementsaboutthe voltagequality are mainly aimed atindustrial customers.But also fordomesticcustomers,utilities offer compensation.Utilities in the U.K. have to offer a fixedamount to each customerinterruptedfor longer than 24 hours. In The Netherlandsa court has ruled that utilities have to compensatethe customersfor all interruption costs, unless theutility can provethat they are not to blame for theinterruption.Also in Sweden some utilities offer customerscompensation for an interruption. 2.3.2 Limits for the Interruption Duration The inconvenienceof an interruptionincreasesvery fast when itsdurationexceeds a few hours.This holds especially fordomesticcustomers.T hereforeit makessense to not reduce thenumber of interruptions (which might be very expensive)b ut their duration. Limiting the durationof interruptionsis a basicphilosophyin power system design andoperationin almostany country.In the U.K., as anexample,the durationof interruptionsis limited in three ways: 1. The Officeof Electricity Regulation(OFFER)setstargetsfor the percentage of interruptionslasting longer than 3 hoursand for the percentageof interruptionslasting longer than 24 hours.These areso-called"overall standards of service" [109]. 49 Section 2.3 • Standardsand Regulations 2. Thedistributioncompanypays all customers whose supplyinterruptedfor is longer than 24 hours. This is a so-called "guaranteedstandardof service" [109]. 3. The design of the systems is such that a supplyinterruption is likely to be restored within a certain time. The OFFERregulationscontain,for eachdistributioncompany,a target for the percentage ofinterruptionsthat is restored within 3 hours, and targetfor a the percentagerestoredwithin 24 hours. At the end of each year the distributioncompaniesreport togetherwith the actual achievement. back to OFFER, which publishes the targets Table 2.7 shows targets and achievement over 1996/97 for some of the utilities. We 990/0, and seethat most utilities meet their targets. All targets for 24 hours are at least the 3-hour targets are no lower than 800/0. The maximumdurationof interruptionis also animportantpart of the designof systems. As we will see in Chapter7 the concept of" redundancy"plays a very important role in that. To achieve acertain reliability of supply, the power system should contain a certain amount of redundancy.A common rule in the design of public systems isthat the larger the number of customers that would be affected by the outage of a component,the more redundancythere should be present and the faster this redundancyshould be available. Table 2.8 summarizes the way this is implemented part of a so-called engineering recommendain the U.K. [119]. These rules used to be tion, and it has been in use in the U.K. for many years. When the utilities were privatized thisrecommendationbecamepart of the license agreement. Dependingon the load size, maximumdurationsof interruptionare given. The larger the a mountof TABLE 2.7 Performance of U.K. Utilities over1996/97 24 hours 3 hours A B C D E F G H Target Achieved Target Achieved 80°A, 85% 950/0 93% 80% 80% 85% 850/0 80.7°A, 90.2% 92.70/0 93.0% 1000/0 99% 1000/0 100% 99% 99% 99% 99% 100% 100% 99.9% 100% 100% 100% 99.3% 100% 88.50/0 91.4% 86.6% 92.9% Source: Data obtained from[109]. TABLE 2.8 DesignRecommendations for the U.K. Supply System Amount of Load Restored Load Size Immediately Within 15 Min Within 3 Hours 0-1 MW 1-12MW 12-60 MW 60-300 MW Load - 20 MW Load - 12 MW or 2/3 load Total load Source: U.K. EngineeringRecommendation P2/5 [119]. Load - I MW Tota11oad In Repair Time Total load Total load 50 Chapter 2 • Long Interruptions and Reliability Evaluation load affected, the faster the restorationof the supply. In termsof power systemoperation and design, thisrequires parallel supply for loads above 60 MW,automaticor remotemanual transferfor loads above 12MW, and local manualtransferfor loads above 1 MW. The relation between reliability andpower system design is discussed in detail in Chapter7. 2.4 OVERVIEW OF RELIABILITY EVALUATION A number of books and hundredsof papers have beenwritten on power system reliability. The most well-known books are those by Billintonand Allan [84], [85], [86], but also thebook by Endreyni [87] and the IEEE Gold Book [21] treat this subject inconsiderabledetail. Thelatter publicationdoesnot give detailedtheoretical considerations,but a useful seto f basic calculations.It also gives a seto f component outage rates, which issomewhatmissing in the other books. Interesting books on power system reliability have also been written in the German language:[88], [89], and probably in other languagesas well. An overview of publications on power system reliability in theinternational refereed literature, is published about once every five years in theIEEE Transactionson Power Systems [90], [91], [92]. Other national and sourcesof information are reportson power system reliability issued by international organizations[93], [94]. Also more and morebooks on power system analysis, design, or operation contain chapterson power system reliability. In the thoughtswill be presented remainderof this section,and in Section 2.5, some general about reliability evaluationof power systems.For more details, thereaderis referred to the literature. The power system is often divided into three functional parts,each with its own specific design andoperationproblemsand solutions: • generation • transport(transmission) • distribution In the reliability analysis asimilar distinction is made between three so-called hierarchicallevelsof reliability: • level I: generation • level II: generationand transport • level III: generation,transport,and distribution Virtually all books and paperson reliability use thisclassification,either implicitly or explicitly, but nor everybodyactually uses the term"hierarchicallevels." This being a various techniques. useful educationalconcept,it is used in this section to discuss the The conceptof hierarchicallevels remains anapproximation,as most classifications. The reliability of a generationstation dependsin part on the auxiliary supply, which must be treatedas adistribution system, thus level III. Also, asubstantialpart of the generationhas becomeembeddedin the distributionsystem, in somecountrieswell over 100AJ [120]. The amountof embeddedgenerationis likely to grow further, with more industrial combinedheat and power(CHP), a growth in the useof small-scale renewable energy and possibly so-called micro-CHPsappearingwith domesticcustomers. Section 2.4 • Overviewof Reliability Evaluation 51 Anotherdisadvantageof this conceptof hierarchicallevels isthat it is developed for the largepublic supplysystem inindustrializedcountries.For developingcountries, for small insularsystems,andfor industrial power systems,different thoughtsmight be needed. At the end o f this section anequivalentof hierarchicallevels for largeindustrial power systems will beproposed. Despitethe shortcomingsof the classificationin hierarchicallevels, it still gives a good insight into the subject. Newdevelopmentsare most likely to appearat those places where theclassificationno longer holds, but to understandthosethe classification should be understoodfirst. 2.4.1 Generation Reliability As we saw from theobservationresults presentedin Section 2.2, outagesof generatorshave no influencewhatsoeveron the interruption frequency nor on the supply availability experiencedby a customer.Thus, for a customer,level I reliability studies donot appearvery important.This conclusionis correctfor an existing, wellplanned,and well-operatedpower system. But in theplanning stage, level Istudies are extremelyimportant. In modern power systems,generationof power takes place at- the highestvoltagelevel; thus a lack of generationbecomesimmediatelya national or even internationalproblem. Such asituation should be avoided as much as possible. Because asuitable reserve in generationcapacity has beenplanned and is availableduring operation,the customerdoes not have toworry about lack of generation anymore. AnnualPeak Load. The rule that the total generationcapacityin a power system should exceed theannualpeak load is likely to be themost important planning criterion in power systems. Planning and building of large power stations take between 5and 10 years, thus decisions about these have to bem adeseveral years in advance.The most basic level Ireliability study is to calculatethe probability that the availablegenerationcapacityis lessthan the annual peak load in a certain year (e.g., 7 yearsaheadof the decision date). The i nput data for such astudy consistsof the expectedannualpeakload, the capacityof eachgeneratorunit, and its forced unavailability. The forced unavailability is the fraction of time during which a unit is not availabledue to forcedoutages,Le., during which it is in repair. The assumption to be made is that the probability that the unit is not available during the annual peak isequal to the forcedunavailability. This gives us sufficienti nformation to calculate the probability that the available capacityis lessthan the annual peak load. This probability is called the"loss of load expectation"(LOLE) of the annual peak. Note that scheduledoutagesare not consideredin peak load studies. It isassumed that preventivemaintenancewill not be scheduledduring the period of the year in which the peakload can be expected. Preventive Maintenance. Preventivemaintenanceof generatorscontributessignificantly to their unavailability. The unavailability consistsof two terms: theabovementioned"forced unavailability" and the "scheduledunavailability." The latter is the fraction of time during which a unit is not available due to scheduledoutages (Le., maintenance).The scheduledunavailability of a unit may exceed its forced unavailability. The scheduledunavailability should not be treated as a probability, like the forced unavailability. Generatormaintenancecan beplannedseveralmonths or even more than a year ahead.The maintenanceplanning will be such that the 52 Chapter 2 • Long Interruptions and Reliability Evaluation supply of the daily peak load willn ot be endangered.Typically, maintenanceis scheduled away from the a nnualpeak: if theannualpeak occurs in winter,g enerator maintenanceis done insummerand the other way around. In tropical areas, where the temperatureand thus the load do not vary much during the year, this kindof scheduling of maintenanceis not possible. Theconsequenceis that a higher LOLE needs to be accepted part of the time, or that additional units are needed. The problem can be especially stringentin small systems(insular or isolated systems) where the unit size is a largefraction of the total load. A way of including preventivemaintenancein the level Ievaluationis to split the For each period aLOLE is calculatedfor the peak year into periods of, e.g., 1 week. load overthat period. Thegenerationcapacityfor eachperiod excludes the unitsthat are in maintenance.Such a study is typicallyperformed as an aid inmaintenance scheduling. The maintenancefrequency (i.e., how oftenmaintenanceis performed)is normally assumed given in level I studies. When varying the maintenancefrequency it is very importantto realizethatthis will influence thecomponentfailure rate. Anaccurate model requires knowledge a bout the aging of thecomponentand the influence which of reliability evaluationwhich is preventivemaintenancehas on this. This is an aspect seldomconsideredin power systems. We will come back component to aging in Section 2.5.6. Load-Duration Curve. The loss-of-loadexpectation(LOLE) quantifiesthe risk that the generatorcapacityis not sufficient to supply the(annual)peak load. It does not quantify the unavailability of the supply due to insufficientgenerationcapacity. To obtain the level I contribution to the unavailability, a more detailed study is required. Not only the unavailability of each generatorunit needs to beknown, but also its outagefrequency and therepair time distribution. The load variation with time and scheduledmaintenancehave to betakeninto accounthere as well. A simple method is to use theload-durationcurve, approximatethis through a number of steps, andcalculatea LOLE for each load level. Theapplicationof such calculations is ratherlimited as they are toocomplicatedto be of use inplanningstudies, but the influence on thecustomeris too small to be of anyimportancethere. Exceptions are power systems inunderdevelopedor very fast developingcountries, where lack of generationcan seriouslycontributeto the supplyunavailability. Derated States. The simplestLOLE calculationsassume twostatesfor a generator unit: available andoutage(unavailable).In reality this is a gross oversimplification, especially for the larger units. It is very common that due to an auxiliary failure the unit will reach a so-called " deratedstate"in which it is only able to generate part of its maximum capacity.An example is the failureof one of theburnersthis limits the combustioncapacityand thus the powercapacity.Consideringsuch a failure as acompleteoutageof the unit underestimatesthe level I reliability. In the planning process this leads to an overestimationof the number of units that have to be built. As costsreduction becameimportant several years ago, the interest in derated state models increased. Anadditional factor explaining the use of more detailed models is again the availability of faster computersenablingthe implementation of these more detailed models. Operating Reserve. Reliability studies are typicallyperformed for planning purposes,where questionslike "how many generatingcapacity should be available Section 2.4 • Overview ofReliability Evaluation 53 ten years fromnow" are addressed.In that case it is assumedthat all generating plants and linesthat are not in repair or in maintenanceare availablefor generation and transport.For operationalreserve studies the situation is different: one needs to take into account only those plants that are actually running or which can be brought online at short notice and assess the riskthat the total load cannot be supplied within the next few hours. 2.4.2 Transmission Reliability Level II reliability concernsthe availability of power at so-called bulk supply points: typically transmissionsubstationswhere power istransformeddown to distribution voltage. Thepower not only has to begeneratedbut also transportedto the taken into account. customers.The availability of sufficient lines or cables has to be Level II reliability studies are much more difficult thanlevel I studies, and are still under considerabledevelopment.Some of the difficulties and suggested solutions are discussed in theremainingpartsof this section. Overloadingof Lines. Due to theoutageof a transmissionline the flow of active and reactive powert hrough the transmissionsystem changes. This can lead to overloadingof other lines. Thestandardexample is theoverloadingof a parallel line. Normally parallel lines will be rated such that the outageof one of them will not lead to overloadingof the other. Thus two lines feeding a 200 MVA loadshouldeach be able totransport200 MVA. This so-called(n - 1) criterion has been animportant part in the design of transmissionsystems: a systemconsisting of n components should be able tooperatewith any combinationof (n - 1) components,thus for any single-componentoutage. In important parts of the system, more strictcriteria are used:(n - 2), (n - 3), etc. Large transmissionnetworkshave become so complex that it is hardto realize the actual loction of the parallel paths.In systemsthat are meshed across several voltage levels,overloadingdue to anoutageis a serious risk as some recent interruptionsand "almost-interruptions" have taught us. The risk has been increasedby the growing transportof power over large distances. For level II studies in large systems, a load flow calculationhas to beperformed for each outage.Thesecalculationsmake level II studies very timeconsuming.The processingof overloadeventsdependson the policy used by the utility to rectify the overload.Typically two models for this are used in reliability studies. I. The overloadleads to anoutageof the overloadedcomponent,eitherimmediately or after a certaindelay which coulddependon the amountof overload. As this secondoutagecan lead tofurther overloadsa cascadeeffect may occur. 2. The overloadis assumed to be alleviatedthrough the sheddingof load. Reliability of the Protection. The power systemprotection'saim is to remove faulted componentsfrom the system so as to limit the damageas much as possible. Failure of the protection to remove thefaulted componentcan lead to significantly more damage,including an interruption for customerswhich would normally not be interrupted.It will be clear that the reliability of the protection is an important part of the reliability of the supply. Protectionfailure is alreadymentionedas oneof the 54 Chapter2 • Long Interruptionsand Reliability Evaluation underlying causes ofcomponentoutages.The power system protection can fail in several ways. 1. The protectionfails to operatewhen required.In that case thebackupprotection will operateand clear the fault. Thisbackupprotectionoften clears more than only the faulted componentmaking the impact on the system much bigger. As thetransmissionsystemoften has only singleredundancy, such aprotectionfailure canpotentiallyeliminatethe redundancyandlead to an unnecessaryinterruption. 2. The protectionoperateswhen not supposedto. If this happensindependently of anotherevent it will simply lead to anoutageof the protectedcomponent. The redundancyin transmissionsystems makesthat thesemaltrips do not have a biginfluenceon the reliability of the supply. 3. The powersystemprotectionshows amaltrip when anotherrelay issupposed to operate.This leads to the loss o f two componentsat the same time. The large currentsflowing throughthe systemduring a shortcircuit makethis an event which has to be consideredin the calculations.Accuratemodelsfor it have not beendevelopedyet. The main problem is that each fault can in theory lead to a malt ripof any of the other relays in thepower system. 4. The power system protection shows amaltrip due to anotherevent in the system, e.g., aswitchingaction. Although the event itself doesn ot lead to any required protectionintervention,it can still potentially eliminate the redundancy. Thereasonis that several relays willexperiencea similar disturbance and thus all might show amaltrip at the samemoment. The reliability of powersystemprotectionis often split into two aspects," dependability" and "security." The dependabilityis the degreeof certaintythat the protection will operatecorrectly (point 1 above); thesecurity is the degreeof certainty that the relay will not operateincorrectly. As shown above this neglects thedifferent aspects within the "security.' Dynamic SystemBehavior. Most componentoutagesare due toshort-circuit faults. Occurrenceand clearing of a fault lead todynamic oscillationsin the system. These can lead tooverloading or tripping of components.This so-called security aspectof level II reliability is often not taken into account. To include it, detailed dynamic models of the system are needed. In the reliability literature a distinction is made between adequacy(static evaluation) and security (dynamic evaluation). The adequacypart is taken care of by most evaluation techniques,but security is often forgotten. In a well-designedtransmissionsystem ashort circuit should not lead to loss of any generator,or overloadingof any component.But one canthink of several situationsin which the dynamic system behaviorcan have asignificant influence on the level II reliability. • The system might be secure for each short circuit in an otherwiseundisturbed system, but not for short circuits in a system in whichalreadyone or more componentsare out of operation.Both thestatesbefore andafter the fault (i.e., after removal of the faulted component)might be healthy, but the transition between the twomight not be healthydue to largedynamic oscillations.The Section2.4 • Overview of Reliability Evaluation 55 system couldappearto have double or triple redundancywhere in reality it only has singleredundancy. b ackupprotection; • Failure of the protectioncan lead to fault clearing by the this leads to a longerfault-clearing time and thus to more adverse dynamic effects. The system might be stablewhen the fault is cleared by the primary protectionbut not when the fault is cleared by the secondaryprotection. • In small power systems with two centers generation,a of fault close to a generator might lead to somegeneratorsaccelerating,while others slow down. The difference between their rotor increases very fast, leading to large instabilities.This phenomenonis especially severe for systems withtransmisa sion grid at voltagesof 10 to 30 kV with mainlyundergroundcables [113]. A reliability evaluationstudy for such a system should not just considercable outagesbut also theunderlyingshort-circuitfaults. • In industrial power systems themaximum motor load connectedto a bus is limited to a certain fraction of the short-circuit level of the bus. Theactual motor load is oftenratherclose to this limit. If in the courseof time theamount of motor load grows, some faults can lead loss-of-synchronism to of synchronous motorsor to stalling of induction motors. Common-ModeOutages. The componentsin a level II study are often considered independent,i.e., the outageof one componentdoesnot dependon the stateof the others. But sometimestwo or more componentoutagesoccur at the same time. of a tower carrying two circuits and excavation Classical examples are the collapse of the other aspectsof level II relialeading todamageof two parallel cables. Several bility studies (failure of theprotection, overloadingof a parallel line) are sometimes also consideredcommon-modefailures. For example, a malt ripof a relay during a fault on the parallel line will lead to anoutageof both lines. By modeling this as a common-modefailure, no detailedprotectionmodel is needed. Weather-RelatedOutages. The outagerate is in most studies considered- constant, but in reality this is not the case. Many outagesare weatherrelated (lightning, storm, snow) and thusstrongly time dependent.For nonredundantsystems this does not matterat all, but for parallel systems it will significantly increase the interruption rate, evenif the averagecomponentoutage rate stays the same. Some numerical examplesof this effect are given in Section 2.8. The IEEE standardfor collecting outagedata [198] recommendsto distinguish between three levels of outagerate: • normal weather • adverseweather • major storm disaster The contribution of adverseweatheron the outageof transmissionand distribution systemcomponents,for a U.K. utility, is shown in Table 2.9[199]. Different utilities will have different contributing phenomena,especially when they are indifferent climates (snowstorms are more likely in Scotland than in Texas), but the general impressionis that adverseweatherrelated outagesare the biggestc ontribution to the outagerate. 56 Chapter2 • Long Interruptionsand Reliability Evaluation TABLE 2.9 VariousContributionsto theOutageRateof Transmissionand Distribution Componerits Causeof Outage TransmissionSystem Distribution System 9% 52% 32% 50/0 2% 12% 11 % 7% 39% 21°tla 8% Lightning strikes Snowlice on lines High winds Plant failures Line interference Animal/bird strikes Adjacent loads 2°tla Source: Data obtainedfrom [199]. 2.4.3 Distribution Reliability Most publishedwork on power system reliability concernsthe generationand transmissionsystems,what has been called level and I level II before. Level III (distribution) reliability studiesare rather rare, although this is changingin the last few years. The lackof interest in distribution reliability is clearly not due to the high reliability of the distribution system. In fact,both interruptionfrequencyand unavailability are mainlydeterminedby events atdistribution level, both mediumvoltage and low voltage. A numberof reasonscan be given for the lacko f interestin distribution system reliability: • The interestin distributionsystem research is in general (much)lower thanthat in transmissionand generation. • Reliability of power transmissionand generationis of national interest,and thus requires more effort. An i nterruptionoriginatingat thetransmissionlevel will affect a largepart of the system,and is thus more likely to lead to newspaperheadlines. than in distribution systems • Investmentsin transmissionsystems are easier because there are much moreof the latter. This meansthat a reliability analysis of variousdistribution alternativesis not attractive. • Reliability studies in distribution systems are relatively simple, which make them lessattractiveto the academicworld. • A reliability analysis would only beof interestto the customerif it would give an absolutevalue of the interruption frequency oravailability. A widely held belief used to bethat the results of reliabilitystudiescan only be used in a relative sense (i.e., to c omparealternatives);such astudywould thereforebe of no use to thecustomer. But, as already said, the interest in distribution system reliability is growing, probably due to the increasingattention for the customers'interests. Distribution system reliability has its ownproblemsand solutions,some of which we will discuss below. Radial Systems. Distribution systems are mostoften radially operated.The consequenceo f this is that each componentoutagewill lead to a supply interruption. To obtain the interruption frequency one only needs to sum the outagerates of all Section 2.4 • Overviewof Reliability Evaluation 57 componentsbetween the' bulk supply point and the customer. Occasionally, parts of the system areoperatedin parallel or meshed. As this concerns small parts of the system, themathematicaldifficulties for calculatingthe interruptionfrequency remain limited. Duration of an Interruption. The main problem indistribution system reliability concerns theduration of the interruption. As we will see later, the costs of interruption increasesnonlinearly with its duration. The probability distribution function of the interruption duration is of great influence on the expected costs. Itfurther is importantto realizethat the restorationtime depends on the position in the network. The averageinterruption duration, and thus theinterruption costs, cantherefore vary significantly throughoutthe network. Theduration of an interruption consists of a numberof terms, each of which has a stochastic character.A list of contributing terms is given, e.g., in[121] and [122]; the most relevant ones are • • • • receive alarm,contactor travel to affectedsubstation; find fault location or faulted section; perform required switching actions; restore supply. A well-known law in stochastictheory isthat the sum of a sufficient number of stochasticterms has anormal distribution. Thus thedistribution of the interruption durationbecause of itsstochasticnatureis likely to benormal and notexponentialas assumed in mostcalculationmethods. This could give unrealistic values for the interruption costs. The Availabilityof the Alternative Supply. The list of terms given above, contributing to the duration of an interruption, assumesthat the alternativesupply is available. Thus, themoment the fault is located (or the faulted section is identified) the supply can be restored. But this is not always the case, as alternativesupply the can also beinterrupted,or the alternativesupply is only able to take over part of the load. In that case the supply can only be completely restored after repair or replacement of the faultedcomponent.When the supply can be restored by switching, the customerexperiences a"long interruption." When the supply can only be restored through repair/replacement,the customerexperiences a"very long interruption" as defined in Section 1.3.3. The frequency of very long interruptionswill be rathersmall in most distribution systems (with the exception o f remote rural networks), but the interruption costs may become very large, which makesimportant it that they become an essential part of the reliability evaluationresults.Another reason forputting special emphasis on very long interruptionsmay bethat the utility has to publish the number of interruptionsnot restored within acertain time, or has to pay damages for these"very long interruptions." To get exact detailsof the distribution of the duration of interruptions,complicatedstochasticmodelsof the system are needed. But a two-step approachcan be used if one is only interested in the frequency of very long interruptions. For very long interruptions,the time-scale of interest is longer thanthe time needed for the alternative supply to be made available. For the assessment of the numberof very long interruptions the switches used to restore the supply can be considered in a closed position already. Toevaluatethe reliability of the resulting system, techniques developed for 58 Chapter2 • Long Interruptionsand Reliability Evaluation transmissionsystems may be used. The models requiredfor this are muchmore complicated than for predictingthe total interruption frequency. Some of the before-mentionedaspectsof transmissionsystem reliability (common-modefailures, adverseweather,overloading)have to beincorporatedin a level III study if the number of very long interruptionsand/or the interruption duration distribution are of interest. Adverse Weather. Adverse weather not only influences thenumber of very long interruptions(by increasingthe probability that both a feeder and itsbackup are not available) but it also makesrepair much more difficult. Blizzardsand heavy thunderstormscause asubstantialfraction of outages.During the storm, repair is very difficult, if not impossible,and after the storm the largenumberof outagescan make this processmore difficult given that repair crews have tohandle the outages one after the other. Such aspectsof the reliability of the supply are extremely difficult to take into accountin a stochasticmodel. As alreadymentionedbefore, oneof the problemsis the lack of data, but certainly not the only one. But despite the mathematical difficulties, more datacollection must be encouraged.Also, the collecteddata should be madeavailablefor a wider public. Embedded Generation.The presenceof embeddedgenerationsomewhatcomplicates thereliability calculations.But the amountof embeddedgenerationis seldom large enoughto have asignificant influence on thereliability of the supply. Industrial power systems are anexception because in such cases embeddedgenerationcan be used toobtain a very high levelo f reliability. Embeddedgenerationin public distribution systems consist mainlyo f wind turof the distribution system is suchthat the binesand CHP units. In all cases the design outageof one generatorunit will not lead to anoverload,and thusnot to an interruption of the supply for any of the customers,Thereforethe presenceof the embedded generationdoesnot influence theinterruptionfrequency. Anexceptionare those cases where outageof a generatorleads to aninterruption indirectly, e.g., when theheat productionof a CHP unit is essentialfor an industrialprocess, or when caontractwith the utilities requiresload sheddingupon a generatoroutage. The presenceof embeddedgenerationcan have some influence on the availability of the alternativesupply, and thus on the frequency o f very long interruptions.The connectedto the interruptionwill normally lead to the lossof all embedded generation affected feeder.Thus the alternativesupply also has tosupply this additional load. Further, embeddedgenerationconnectedto the alternativefeeder can havetripped on the voltage sag due to the fault which led to the interruption. The speed with which this generationbecomesavailableagain will influence theprobability that the alternativesupply is able to take over allload from the affected feeder. 2.4.4 Industrial Power Systems Large industrial and commercialusers own andoperatetheir own medium voltage distribution system. Thelargestusers even own ando peratea high voltage network. The point-of-connectionto the public supply is somewhereat distribution or transmissionlevel: thecustomeris responsiblefor the further distributionto thevarious structureis pointsof utilization. In these so-calledindustrialpowersystems the general often somewhatdifferent than in public systems. Also there is no need for separate studies atseparatehierarchicallevels; all that mattersis the continuity (or whatever 59 Section2.4 • Overview of Reliability Evaluation word one likes to use)o f the supply to theequipmentessential for theproduction process. A possible listof questionsthat need to be addressed for a reliability study in an industrial power system is given below. We will only discuss interruption frecomparedto the quency below.Restorationof the supply will often take place faster time it takes torestartthe productionprocess. Of course this is not always the case, and for someindustrial systems, thequestionsneed to be modified. The list below should not be blindly followed, but be used as a basis for a specific study. starting Each of the questionsgives feedback on the design of the system. The point may be the existing system, or detailed design based on past experience. The whole "design process"is shown in Fig. 2.10. The term"layer" has been used here to distinguish from the "hierarchical levels" used for the reliability analysis o f the public supply, but in factboth terms denoteexactly the same. I. How often will the availablegenerationnot be enough to~upply the load? This layer correspondsto hierarchicallevel I in the public supply, for the which a largenumberof tools are available. Some aspects of calculations are already mentionedin Section 2.4.1. A few pointsof special interest to industrial systems need to be mentioned. • Maintenanceon generatorunits can play a veryimportant role in industrial systems. The load does not show much variation through the year, thus maintenancecannotbe scheduledduring a period of low load. This means that the generation capacity will influence the scheduling of Changegeneration Changetransportsystem Changestabilityaspects Changedistributionsystem Changeequipment immunity Changeequipmentreliability andredundancy Figure 2.10 Reliability layers in industrial power systems and their role in system design. 60 Chapter2 • Long Interruptionsand Reliability Evaluation • • • • maintenance.The lower the reserve (differencebetween loadandcapacity) the less likelythat maintenancecan beperformed. The influenceof maintenanceon aging can only be assessed ratherqualitatively as accuratemodels are still lacking.T hereforea constantfailure rate will often be used. Inthat case oneshouldrealizethat the calculation resultscannotbe used tooptimize the maintenancefrequency. Powergenerationunits may be linked, e.g.,through the useof a common steam circuit. This needs to be takeninto accountin the reliability studies as it might increasethe probability that two or more·units have anoutage at the same time. During capacity shortagesor when thecapacity margin is Iowa load sheddingpolicy is often in place. This needs to be i ncorporatedin the reliability calculations. When the plant is connectedto the public supply (which is mostly the case), itsreliability needs to beconsidered.When the plant is fed via multiple infeeds,common-modefailures need to beconsidered. 2. How often will a situation occur that the generationis available butthat it cannotbe transportedto the load? This layer correspondsto hierarchicallevel II in the public supply. The variousconsiderationsare very similar,but with somedifferencein emphasis. • Componentloading is higher in industrial systems,and more constant. Thereforeassessmentof overloadsdue to outagesbecomesmore important, but load variation often does not need to beconsidered. • Distancesbetweensubstationsare much smaller,which makessubstation failures toplayalargerrole (relatively speaking)thanin the public supply. 3. How often willtransientinstability lead to a plant trip? This is arathernewsubject,correspondingsomewhatto the securitypart of hierarchicallevel II. In industrial systems, with largemotor load, on-site generation,and short distancesbetween them,t ransientstability aspectscan play a very important role. What is needed first is aprediction of the frequencyof variousshort-circuitevents,and next an assessment of the effects of each event on the system stability. The event frequenciesfollow from earlier reliability calculations.Assessing the effects o f the event requiresa detailed model and can become a severe strain on the computer power. Performinga detailedtransientstability calculationfor a large system is no longer too difficult with modern computerspeed and memory, but for a reliability study such acalculationneeds to beperformedfor many possible systemstates(preferablyfor all possiblestates).Even amedium-sizedsystem may requirethousandsof transientstability calculations,which still places a severestrain on the computerpower. Two optionsare availableto limit the calculationtime. • Use a simplecriterion to assess the system stability, e.g., theratio between fault levelandmotor load, or the differences inrotor angles at themoment of fault clearing.For the latter, simple models can be used, e.g., change the in active power between thepre-eventand during-event steady states. Apply this simple criterion to all (or at leastmany) system states.The criteria might appeargross simplifications, which would never be accep- Section 2.4 • Overview of Reliability Evaluation 61 table for aconventionaltransient-stabilitycalculation.But all we need to know here is the sum of the frequenciesof all events leading to an unstable situation. • Use adetailedsystem model, but limit thenumberof events to bestudied. A first pruningis to look only at those events which involveshortcircuit a and for whichboth the initial steadystateand theresultingsteadystateare stable. A secondpruning is to stop looking for stateswith more components out, when astate has unstableevents associatedwith it. As an example, if a fault leads totransientinstability when two of six generators are out of operation,there is no need to study a fault when three generators are out. One shouldnote that it is not theactualinstability limit which matters, but whethergeneratorsor motorswill be tripped by their protection(undervoltage, overcurrent,reverse-power,under-or overfrequency).This can happen in systems which are in principlestill stable.Thusa detailedmodel would also requiresufficient detailsof the protectionpresentin the system. 4. How often will the distribution system fail to transportpower to the plant? Layer 4of industrial powersystem reliabilitycorrespondsto level III in the public supply. We can thus apply similar techniques,with the difference that the duration of an interruption is often not so important in industrial of the interruption duration which makes systems. As it is the assessment reliability analysis indistribution systemscomplicated,the calculationsin industrial distribution systems will be simplerthan in public systems. The distribution systemstartsat the transportsystemstudiedin layer 2 and layer 3, and ends at the equipmentterminals.The various distribution systems arenormally consideredindependentof each other. An industrial of equipmentwith distributionsystem can be extremely complex: many pieces many levelsof redundancyand importance.Some kindof pruning needs to be made before a study' can startedwith be a reasonablechanceof success. A first pruningis to only considerthe supply toequipmentwhich is essential for the operationof the plant. A decision to be madebeforehandis where thetransmissionsystemstops and thedistribution system begins. The answer to this will again dependon the detailsof the study. For smaller systems itmight be appropriateto not make anydistinction betweentransmissionand distribution, while for large systems eachplant is consideredas aseparatedistribution system. 5. How often will the plantoperationbe interrupteddue to insufficient voltage or currentquality? In this layer allother power quality phenomena(i.e., apart from interI through 4) have to be assessed. ruptions which were discussed in layers Examplesof voltage quality events to bestudiedare: • Transientovervoltages. • Voltage sagsand swells. • Notching and burstsof harmonicdistortion. • High-frequencyconducteddisturbances. To studyall these in as muchdepthas for the longinterruptionswould lead of to extremely long studieswithout much hope of useful results. The level detail againdependson the system. Anappropriatechoice is to only look at 62 Chapter2 • Long Interruptionsand Reliability Evaluation first or secondorderevents (firstordereventsare shortcircuits in the normal system,secondorder eventsare short circuits when alreadyone other componentis out of operation). Thesekind of studiesare extremelyrare,andwhere they aredonedo not contain much quantitative details. Still, even the decision to not study a certain type of event in detail becauseit is not likely to be of influence is alreadymuch better than simply forgetting aboutit. To actually determinethe number of equipmenttrips is not possible without a detailed knowledgeof equipmentimmunity. In the designphase of the system, thisinformationis simply not available.It will then be easierto determinethe electromagneticenvironmentwhich the equipmentwill experience and to proposeimmunity requirementsfor the equipmentto be used. Here it becomesimportant to distinguish between(voltage) variations and (voltage)events,as describedin Section 1.3. Currentquality eventswill not directly lead to tripping of the plant, but utility requirementsmight force a plant shutdown,e.g., when theharmonic currentdistortionexceeds acertainlevel. If such ashutdownwill have severe consequences, it needs to beconsideredin the reliability study. 6. How often will theplant operationbe interrupteddue to the failure ofessential equipment? Equipmentfailure is normally hot consideredas part of supply reliability, but in an industrial system it isequally important. There is no need to build a very reliable power system if theplant will stop twice a week due to equipmentproblems.Industrial customersoften use theterm interruptionin a more general meaning than the utility. The descriptive terms "voltage interruption" and "interruption of plant operation" indicate the difference in interpretationrather well. Detailed knowledgeof the plant processis needed toperform a study like this. Like in severalof the stepsbefore, some seriouspruning will be neededto make the study feasible. It might even bethat only a qualitative assessment is feasible. Note that there is someoverlapwith layer 4 (distribution systems)and layer 5 (equipmenttrips due to voltagequality events). Additional aspectsto be consider~d are: • redundancyof equipment,e.g., thefunction of a motor being taken over by anotherone; • "linkage betweenplantson the productionside, e.g., thesteamproduction by one plant which is neededto operateanotherplant. 2.5 BASIC RELIABILITY EVALUATION TECHNIQUES 2.5.1 Basic Concepts of Reliability Evaluation Techniques Stochastic Components.For a reliability evaluation study, the power supply system is splitinto stochasticcomponents.The choice of componentsis rather arbitrary: the whole transmissionsystem might be one component,but a single relay could be severalcomponents.Each componentcan be in at least two states:healthy and nonhealthy,the latter often referredto as theoutagestate.For a two-statecomponent,two eventscan occur: thetransition from the healthyto the nonhealthystate, Section 2.5 • 63 BasicReliability EvaluationTechniques an outageor failure event; and the reverse transition(i.e., from thenonhealthyto the healthystate), therepair or restore event. The systemstateis a combinationof all event states; if thestateof one of the componentschanges,the systemstatechanges. The system s tatefor a system withN componentscan bethoughtof as a vectorof rank N. The valueof each element is the state of the correspondingcomponent.An event is atransition between two system states, due to the changein stateof one or morecomponents. EXAMPLE Consider,as an example, the system in Fig. 2.11:generatorwith a generatortransformer,feeding into a large system via two parallel transmissionlines and atransformer. We areinterestedin the reliability of the supplyinto the large system, thus, at point C in the figure. Ll Figure 2.11 Power systemexample,for choice of stochastic components. A L2 A possiblesubdivisioninto stochasticcomponentsis as follows: 1. generatorplus generatortransformerTl 2. substationA 3. line Ll 4. line L2 5. substationB 6. transformerT2 In case adetailedstudy is neededof the generatorplus thegeneratortransformer,component1 may besubdividedinto stochasticcomponentsas follows: 1. 2. 3. 4. the mechanicalside of the generator,including the fuel availability the electrical side of the g enerator,including its protection the generatorcircuit breaker the auxiliary supply 5. the generatortransformer 6. the protectionof the generatortransformer The Interruption Criterion. For each systemstateor for each event, an"interruption criterion" is used todetermineif this state or eventshould be countedas an interruption or not. In most studies theinterruptioncriterion is rather trivial, but for more detailed studies, especially for Monte Carlo simulation, the definition of the interruption criterion becomes animportant part of the modeling effort. It is recommended to spend at least some time on defining interruption the criterion for a of interruption criteria are given reliability evaluationstudy. Some simple examples below. Note that these arejust examples, andcertainly not the only possibilities. 64 Chapter2 • Long Interruptionsand Reliability Evaluation • In a level I studya stateis an interruptionstateif the generatorc apacityis less thanthe load demand.Note that thereis only oneinterruptioncriterion for the whole system.Eachcustomeris equal at this level. • In a level II study a state is an interruption state for a given transmission substationif the maximum power that can be transportedto this substation is less than the demand. For level II studies, each substationhas its own interruptioncriterion, thus its own reliability. • In a level II security study an event is an interruption event if the transient phenomenondue to theevent leads totripping of generatorsand/orload. • In a level III study a stateis an interruptionstatefor a given customerif the voltageat the customerterminalsis zero. • In a level III power quality study an eventis an interruptioneventfor a given device if it leads to thevoltage at the device terminals to exceed certain magnitudesand durations. The GeneralComponentModel. Two quantitiesare normally used to describe the behaviorof a stochasticcomponent:the failure rate and the (expectedor average) repair time. The meaningof the term "expectedrepair time" is obvious: the expected value of the time the componentresidesin the nonhealthystate. The failure rate A gives the averageprobability that the componentwill fail in the next small period of time: . Pr(failure in period 6.t) A = I1m - - - - - - - - 6t.....0 8.1 (2.8) For componentsrepresentingprimary partsof the power system,which are the majority of the componentsin moststudies,the term outageratemight be used.Herewe shall use thegeneralterm failure rate. The definition of failure rate in (2.8) is rathermathematical.It will becomeof use below. A more practical way of defining the failure rate is through the number of failures in a population.Considera populationof N similar components(e.g.,distribution transformers).During a period n, this populationshows K componentfailures. The failure rate may be determinedas K A=nN (2.9) The two definitions of failure rate are equivalentundera numberof assumptions.T he most importantof which is that the componentis repaired(within a short time) after every failure. The definition according to (2.9) is used toobtain failure rates from observedfailures. Someother quantitieswhich are in use will bedescribedbelow. • The expectedtime to failure T is the reciprocalof the failure rate: 1 T=-A (2.10) • The repair rate {t is the reciprocalof the expectedtime to repair R: 1 {t=- R (2.11) 65 Section 2.5 • Basic Reliability Evaluation Techniques Note that expectedtime to failure can be defined in asimilar way as the expectedrepair time, and the repair rate similarly as thefailure rate according to (2.8). • The availability of the componentis the probability to find the componentin the healthystate: T p=-- (2.12) R+T • The unavailability is the probability that the componentis in the nonhealthy state: R (2.13) Q=R+T • The expectedtime betweenfailures (ETBF) is the sum of the expectedtime to failure (ETTF) and the expectedrepair time. As the repair time is normally muchsmallerthanthe time tofailure, ETBF and ETTF are aboutequalandas a consequenceoften mixed up. From a mathematicalp oint of view, this is a seriousmistake,but in engineeringthese kindof errors are commonand not consideredvery seriously. EXAMPLE A distribution company operates 7500 distribution transformers. Over a period of 10 years, 140 of these transformers fail for various reasons. A small fraction of them can be repaired, but most failures require replacement with a spare transformer. Records have been kept of the repair or replacement time needed. Adding all these for the 140 failures gives areoba total of 7360 hours. From these observation data, the values of the above parameters tained: 140 _I (2.14) A = 10 x 7500= 0.0019yr 1 T 7360 R = 140 = 52.6h Jl (2.15) = 0.0019= 530yr = 0.006yr (2.16) = ~R = 167yr-1 (2.17) 530 p = 0.006+ 530= 0.999989 0.006 (2.18) . Q = 0.006+ 530= 0.000011= 6mtn/yr (2.19) This can be interpreted in normal words,follows: as • Each transformer has a probability of 0.0019 to fail in the coming year. In the whole population, 14 transformers are expected to fail. • After such a failure, the repair or replacement of the transformer is expected to last 52.6 hours. • Each transformer will be out of operation, on average, 6 minutes per year. 66 Chapter2 • Long Interruptionsand Reliability Evaluation d atato predictfuture behavior.This is the basis for all Note that we have usedpast-performance reliability analysis: theassumptionthat the averageperformancein the past gives theexpected behaviorfor the future. The Detailed Component Model.Describinga stochasticcom-ponentby means of two quantities (e.g., failure rate and repair time) is a gross simplification of the actual situation. Still this model is usedin more than 95% of all reliability evaluation studies. To understandthe reasonsfor this, we first need to introduce the general componentmodel. The componentis again assumedto be in one of two states.The theory can be extendedto multi-statemodels, but describingthosewould not lead to better understanding.For each of the two statesa probability distribution is defined for the time the componentstaysin that state.Thereis thus one probability distribution function for the repair time (the time in the nonhealthystate) and one for the lifetime (the time in the healthystate). Let T be the lifetime (expectedtime to failure) of the component.The probability distribution function of the lifetime F(t) is the probability that the componentfails beforeit reachesan age t: F(t) = Pr(T s t) (2.20) The probability density function is the derivative of the probability distribution function: f(t) = dF = lim dt Pr(t < T :::: t + M) L\t~O ~t (2.21) The probability density function I(t) is a measurefor the probability that the component will fail aroundan age t: l(t)6.1 ~ Pr(1 < T s 1 + ~t) (2.22) The failure rate A( I) is definedas theprobability that the componentfails soonafter the age 1 assumingthat it has not failed before age t: A() t . Pr(T~t+~tIT>t) Iim - - - - - - - = L\t~O ~I (2.23) The failure rate can be calculatedfrom the probability density function I(t) and the probability distribution function F( t): A(t) = f(t) 1 - £(t) (2.24) We will discussthe failure rate and its relation to componentaging in more detail in Section2.5.6. Similar definitionscanbe given for therepairtime, resultinge.g., in the repairrate /1(t), a probability density function g(t) and a probability distribution function G(t). The Weibull Distribution. A distribution often used in stochastictheory is the so-called Wei bull distribution. The probability distribution function for a Weibull distributedvariable T is F(t) =I - ex p { -(~r} (2.25) 67 Section 2.5 • Basic Reliability Evaluation Techniques For m = 1 weobtainthe exponentialdistributiondiscussed before. We refer m to as the shapefactor and to () as thecharacteristictime of the Weibull distribution. The probability density function .(t) is nl f(t) = m t om - 1 { exp -(0)t nil (2.26) The failure rateA(t) for a Weibull distribution is obtainedfrom (2.24): r:' A(t)=m- om (2.27) m > 1 and decreases for m < 1. From a We seethat the failure rate increases for relatively simpleexpressionit is possible togeneratea whole rangeof lifetime distributions. % The ExponentialDistribution-Lifetime. As alreadystatedbefore, over 95 of reliability evaluation studies use the simple model with a single failure rate and a single repair rate. The underlying assumptionis that both repair time and lifetime are exponentially distributed. The exponential distribution (also called "negative exponentialdistribution") is defined through the following probability distribution function: F(t) = 1 - e-'At (2.28) From the aboveequationsit follows easilythat A in (2.28) is the failure rateaccording to (2.24).Thus,the negativeexponentialdistributionhas aconstantfailure (repair)rate and the generalcomponentmodel can be used. Thereare anumberof reasonswhy this distribution is almostthe only one used: • Using nonexponentialdistributions makes that most reliability evaluation techniquescurrently available can no longer be used.For many years the choice was between using the exponentialdistribution or not doing any reliability evaluationat all. nonexponentialdis• Even the smallnumberof studies which are able to use tributions(the so-calledMonte Carlo simulationswhich we will discuss below) often still useexponentialdistributions,becauseof the lackof data.Collection schemesof componentfailure data normally only provide failure rates and averagerepair times. • The lackof experience withnonexponentialdistributionsmakesthat the results of such a study areratherhard to interpret. of componentswith different ages • In an actualpower system there is a mixture for three reasons:preventive maintenanceis performed on componentsat different times; componentsare replacedafter failure; and the system is not built at once but has grown over time. The mixture of ages makesthat the systembehavior,being a kindof averageof the componentbehavior,can be described byassumingall componentsto have aconstantfailure rate. • Most componentsin use are in their so-called "useful operatingtime": they have passed the wear-in time, and have not yet reached theoftime serious wear-out.This is based on the assumptionthat the failure rateof a component versus time can be describedthrough a "bathtubcurve." During most of the Chapter 2 • Long Interruptions and Reliability Evaluation 68 operatingtime of a component,it resides in the flatpart of the bathtubcurve where the failure rate is c onstant. The ExponentialDistribution-Repair Time. For repair time distributions, the above reasoningsdo not hold. Wealreadysaw in Table 2.1that the duration of an interruption is nonexponentiallydistributed. If we assume theinterruption duration to be Weibull distributed,the shapefactor in (2.25) can becalculatedfrom the available data: In( -In(Fr3 » m= (2.29) In(~) with Fr3 the fraction of interruptionsnot restoredwithin three hours and () the characteristicrepairtime. If we take theaveragerepairtime as thecharacteristicrepairtime, we only makea smallerror as long asm > 1. Including the effectof the shapefactor on the averagerepair time would make thecalculation too complicated.The resulting shapefactors for the interruption durationsare given inTable 2.10. We find shape factors somewhatin excessof unity. The IEEE Gold Book [21] gives,amongothers,repair times for large electrical motors in an industrial environment.As both the average and the median value are given, it is again possible to estimatethe shapefactor assuminga Weibull distribution. In mostcases themedianvalue ismuchlarger thanthe average, whichindicatesa shape factor less than one. An alternativeexplanationis the combinationof two Weibull distributions,both with shapefactor greaterthan one, but with significantlydifferent characteristicor averagerepair times. More theoreticalmodelingand observationwork is needed tovalidatethe useof the exponential distribution in power system reliability evaluation. Based on the evidencepresented,the following preliminary conclusionscan bedrawn: • The exponentialmodel appearsan acceptableapproximationfor lifetime disof preventivemaintributions,with the exceptionof studies in which the effect tenanceis evaluated. • The exponentialmodel isnot correctfor the repair time. A short discussionon componentaging will be given in Section 2.5.6. TABLE 2.10 ShapeFactor for Weibull Distribution of Interruption Duration () 2.38 1.38 1.42 1.45 1.63 1.62 2.27 1.38 Fr3 ShapeFactor 0.193 0.098 0.073 0.070 0.115 0.086 0.134 0.071 2.15 1.09 1.29 1.35 1.27 1.46 2.50 1.25 69 Section 2.5 • BasicReliability EvaluationTechniques 2.5.2 Network Approach Whenusing the so-callednetworkapproach,the system ismodeledas a"stochastic network." The stochasticbehaviorof the system isrepresentedgraphicallyby means of a numberof network blocks, connectedin parallelor in series.Eachblock refers to a stochasticcomponentin the system. The model is such that the system ishealthy(i.e., the supply is available)as long as there is p aath through the network. This graphical charactero f the methodmakesit very suitableto get an overviewof the reliability of the system. An additional advantageof the network approachis the similarity with the electrical network. Electrically parallel componentsare often modeled as a parallel connectionin the stochasticnetwork. An electrical seriesconnectionin most cases results in astochasticseriesconnection. When the reliability is quantified by using a stochasticnetwork, a number of mathematicalapproximationsare needed. Thecalculationsassumethat the repair time and the lifetime areexponentiallydistributedfor all components. Each block(network element)is characterizedthrough an outagerate A and an expectedrepair time r. For each element we further define the"availability" P and the "unavailability" Q. P = I - Ar (2.30) Q=Ar (2.31) Sometimesa different form of these expressionsis used: theoutagerate is given in failures per year,a ndthe repairtime in hours,leading to the following(mathematically not fully correct,but very handy)expressionsfor availability and unavailability: Ar P = 1 - 8760 (2.32) Ar Q = 8760 (2.33) EXAMPLE Considerthe supply system in Fig. 2.12. A possible stochasticnetwork for this system is shown in Fig. 2.13 where the numbers refer to the following typesof failure: Public supply Figure 2.12Single-linediagram of a supply system. On-sitegeneration 70 Chapter2 • Long Interruptionsand Reliability Evaluation Figure 2.13Stochasticnetwork representationof the systemshownin Fig. 2.12. 1. 2. 3. 4. 5. 6. 7. outage of the public supply outage of agenerator bus outage transformeroutage circuit breakerfailure (maltrip or short circuit) circuit breakerfailure (maltrip) circuit breakerfailure (short circuit) All componentsin the network in Fig. 2.13 are stochastically independent,so that simple mathematics can be applied. Note that the capacity of one generator(5 MW) is not enoughto supply the load (7 MW). To supply the load the public supply needsbetopresent, or both on-site generatorsneed to be inoperation.In the networkdiagramthis is shown as the"public supply" in parallel with both "on-site generators"in series. Also note the difference between a circuit breakermaltrip and a short circuit in the breaker. In the lattercase theprotectionon both sides of the breakerwill trip leading to the loss of twoprimary componentsat the same time. Various methodsare availableto calculateinterruption rate and expectedinterruption durationfrom componentfailure rateandrepairtime; all thesemethodsreplace the wholenetwork by one equivalentcomponent. An obvious methodfor network reductionis to find seriesand parallel components. A parallelconnectionrepresentsredundantcomponents,where thesupplyis not interrupteduntil all of them are in theoutagestate. A seriesconnectionrepresentsthe situation where eachcomponentoutageleads to aninterruption of the supply. The correspondencewith electrical seriesand parallel connectionsis clear but not one-toone. Consideras an example twotransformersin parallel. If one of them fails theother one can take over the supply. This is clearlystochasticparallelconnection.But a if the total load is much morethan the maximumloading of one transformer,the other one Section 2.5 • 71 BasicReliability EvaluationTechniques will also soon fail or be tripped by its overload protection. In that case astochastic seriesconnectionis a betterrepresentation. Stochastic Series Connections.Considerthe seriesconnectionof two stochastic componentswith outagerates AI and A2 and repair time r and '2, as shown in Fig. 2.14. Wewant to derive expressionsfor outagerate As and repair time r s of the series connection,so that the seriesconnectioncan be replaced by one equivalentcomponent. Al rl -<. As rs A2 r2 Figure 2.14Stochasticseriesconnection. A seriesconnectionfails wheneitherof the componentsfails. The outagerate for the seriesconnectionis thus the sumof the outagerates of the components: As = Al + A2 (2.34) The seriesconnectionis not availablewhen oneof the componentsis not available, giving for the unavailability of the seriesconnection: (2.35) Using thedefinition of unavailability(2.31) gives anexpressionfor the equivalentrepair time of the seriesconnection: Air. + A2r2 r ----- Al S - + A2 (2.36) For n componentsin series, the followingexpressionscan be derived: n As= LA; (2.37) ;=1 r.s = L"'IA'" '=; I ' (2.38) LJ=I AJ In deriving the expressionsfor equivalentoutage rate and repair time a number of assumptionshave been made, all coming back to the system being availablemost of the time, thusAr « 1. Exact expressionswill be derived inSection2.5.3. StochasticParallel Connections. A parallel connectionof two stochasticcomponentsis shownin Fig. 2.15. A parallel connectionfails when one of thecomponentsis not availableand the other one fails: thus when 1 isunavailableand 2 fails or when 2 isunavailableand 1 fails. The outagerate of the parallel connectionis 72 Chapter2 • Long Interruptionsand Reliability Evaluation Figure 2.15Stochasticparallel connection. Ap = QI A2 + Q2 AI = AI A2(' 1+ '2) (2.39) The parallel connectionis not availablewhen both componentsare not available. The unavailability of the parallel connectionis o, = QI X Q2 (2.40) The repair time of the parallel connectionis obtainedfrom (2.39)and (2.40): 'p =-'1'2 - (2.41) 'I +'2 The equationscan beextendedto a system with threecomponentsin parallel by considering it as theparallel connectionof one componentand the equivalent of the parallel connectionof the two other components.This results in the following expressions for outagerate and repair time: (2.42) 1 1 1 I 'p '1 '2 '3 -=-+-+- (2.43) The same process can be repeatedseveral times, resulting in the following general expressionsfor a systemconsistingof n componentsin parallel: n n 1 -. = Il Aj'j L -: ;=1 j=1 ,} (2.44) (2.45) Minimum Cut-Sets. A secondmethodfor analysisof stochasticmethodsis the so-called "minimum-cut-setmethod." A "cut-set" is a combination of components whose combinedoutagewould lead to aninterruption. In the stochasticnetwork in Fig. 2.16 thecombinations{I, 2, 3} and {4,5} are examplesof cut-sets. Acut-setis a "minimum cut-set" if the removal of anyoneof the componentsfrom the cut-set would make it no longer a cut-set. Inother words, if the repair of anyonecomponent would restore the supply. In Fig. 2.16 thecut-set {I, 2, 3} is not a minimum Section 2.5 • 73 BasicReliability EvaluationTechniques 5 Figure 2.16 Example of stochastic network, for explaining the minimum cut-set method. cut-set becauserepair of component3 does not restore the supply, even though repair of component 1 or component 2 does. The cut-set {4, 5} is a minimum cut-set becauseboth repair of component4 and repairof component5 restore the supply. For each network there are a limitednumberof minimum cut-sets.Finding all minimum cut-sets is the first step of the minimum-cut-setmethod. The network in Fig. 2.16 has the following minimum cut-sets: {1,2} {4,5} {1,3,4} {2, 3, 5} The supply isinterruptedwhen anycombinationof thesecomponentsis not available. The systembehaviorcan thus also be described as a series connectionof four parallel connections,representingthe four minimum cut-sets. This is shown for this example in Fig. 2.17'. After having found theminimum cuts-sets, thecalculationproceedsstraightforward: outagerates andrepairtimes aredetermined,first for the parallelconnections, next for the resulting series connection.The latter gives the interruption rate and expectedinterruptionduration for the supply. 2 Figure 2.17 Alternative drawing of the network in Fig. 2.16: series connection of parallel connections. EXAMPLE Considerthe following outageratesand repair times for thenetwork ele- mentsin Fig. 2.16: AI = 1 '1 = 0.2 A2 2 '2 0.1 A] = 0.5 '3 = 0.1 A4 = 0.8 r 4 = 0.15 As = 1.5 's = 0.2 = = At') = 0.2 A2'2 = 0.2 A3'3 = 0.05 A4'4 = 0.12 AS'S= 0.3 Equations(2.44) and (2.45) giveequivalentfailure rate and repair time for the parallel connections representingthe four cut-sets. 74 Chapter2 • Long Interruptionsand Reliability Evaluation (2.46) 'cl 1)-1= 0.067 = ( -1 + '1 'c2 '('3 '('4 '2 I)-I = = ( -I + -1 + -1)-1 = 1 = ( -+'4 '5 '1 '3 1 1 '2 '3 0.086 (2.47) 0.046 '4 1)-1= 0.04 = ( -+-+'5 The failure rate A and repair time r of the whole system can be calculatedby consideringit as a seriesconnectionof the four cut-sets: (2.48) r = Ad'cl + Ac2' c2 + Ad',,3 + Ac4' c4 = 0.072 + Ac2 + Ac3 + A('4 (2.49) Ad A second example of the use of the network approachis shown in Fig. 2.18 and Fig. 2.19. The first figure showsp art of a subtransmissionsystem. Thetransmissiongrid is assumed to be fully reliable. Also substationsA, B, and C areassumednot to fail. The load of interestis connectedto substationD. The networkrepresentationfor the system in Fig. 2.18 is shown in Fig. 2.19. Component8 representsoutagesin the local substation(D) which lead to aninterruptionfor the loadof interest.This network can no longer be reducedthrough series andparallel connections,but the minimum cut-set methodcan still be used. c 6 D 7 8 Figure 2.18 Exampleof public supply, with single redundancy. Section 2.5 • 75 BasicReliability EvaluationTechniques 6 Figure 2.19 Network representationof the supply in Fig. 2.18. The following minimum cut-sets can be found for this network: {8} {6,7} {I,2,4} {I,2,5} {I, 3, 7} {2, 3,4, 6} {2, 3, 5,6} These minimum cut-sets are shown in Fig. 2.20 from where the term ..set cutbecomes clear. A cut-set cuts allpathsbetween the source and the load.minimum A cut-setcan be described as "ashortestcut." 1---------- Figure 2.20Network representationof the supply in Fig. 2.18, with minimum cut-sets indicatedas dottedlines. A third example is shown in Fig. 2.21. This supply system containsa substation with a third bus (4), aconfiguration used in industrial systems toprevent a circuit breakerfailure from leading to loss of the whole substation.The variouscomponents have beennumberedin the figure.Translatingthis to anetworkdiagramis not obvious, as component3 is in series with 1, 4, and 6, but 1 and 4 are in parallel. A possible solutionis shown in Fig. 2.22.Components3 and 5,representingbus outages,are now placed in a triangle with themselves. The network might seemsomewhatartificial, the list of minimum cut..sets can beobtainedin a normal way, resulting in 76 Chapter2 • Long Interruptionsand Reliability Evaluation {8} {1,2} {I, 5} {2,3} {3,5} {3, 7} {5,6} {6,7} {I, 4, 7} {2, 4, 6} The advantageof the networkapproachis thatit gives a fastunderstandingof the reliability of the system. It also enables reliability calculationsin large systems and provides,through minimum cut-set techniques, an insight into the weak points of the supply system.Drawing the stochasticnetwork is a useful exercise in itself, often more usefulthan the actualresults. Thedisadvantageis that approximationerrorsare made in each step of thecalculationprocess. This could lead to serious errorsin the results, 2 3 5 6 7 8 Figure 2.21 Industrial system withthree-bus substation. 2 3 5 6 7 8 Figure 2.22 Network representationof the system in Fig. 2.21. Section 2.5 • BasicReliability EvaluationTechniques 77 especially for large systems. The errorsare due to theassumptionsmade when replacing series and parallelconnectionsby one element. Theassumptionsmade arethat the t hat the elements are stochasticallyindepenunavailability of the element is small and dent. Thelatter assumptionis no longer fully correct when the seriesconnectionof minimum cut-setsis replaced by one element. As the same network componentcan appearin more than one minimum cut-set,the minimum cut-setswill becomestochastically dependent. 2.5.3 State-Based and Event-Based Approaches In the state-baseda pproachthe systembehavioris describedvia states andtransitions between states. sAtateis eitherhealthyor nonhealthy.A healthystateis a statein which the supply is available,a nonhealthystate one in which the system is not available. Theprobability of all the nonhealthystatesis calculatedand added. This sum is the probability that the supply isnot available. In addition to probability it is also possible tocalculateother parameters,like the expectednumberof interruptionsper year, or the average d urationof an interruption. of events. In the event-basedapproachthe systembehavioris described by means For each event theconsequencesfor the supply aredetermined.In case analytical of states and techniquesare used the system is often still modeled ascollection a transitions. But now the transitions are either healthy or nonhealthy.A transition between twohealthystatesis NOT necessarily healthy. A Four-State Component Model.The basiccomponentmodel for astate-based approachconsistsof two states: { inoperation}; and { not in operation}, often shortened to { in } and { out }. A more detailedmodel is shown in Fig. 2.23. This model consists of four states: {healthy}, { faulted }, { out of operationfor repair }, and { out of operationfor maintenance}. We can see from the figure t hat the component cannot fail while in maintenance,but that maintenancecan start while the compothat a faulted componentwill first be repairedbefore it nent is in repair. We also see becomes"healthy" again. The faultedstaterepresentsa short-circuit fault, the duration of which is much smallerthan of the other states.Thereforethis state is often combinedwith the repair state. But in studiesof power systemprotection,the faulted stateplays an essential role. Figure 2.23Four-statecomponentmodel. 78 Chapter 2 • Long Interruptions and Reliability Evaluation A Protective Relay. An example of astate model for a protective relay is shown in Fig. 2.24. We see the same healthy, repair, maintenance and statesas in Fig. 2.23, but now thecomponentcan fail in threedifferent ways. A maltrip leads directly to an outageof the componentto be protected,after which the relay needs to "dormantfail to trip") meansthat the relay be repaired. A hidden failure (also called will no longer trip when it needs to. This failure will only reveal itself when the relay needs to trip, thus when there isshort a circuit in the componentto be protected.A potentialmaltrip is a situationwhere the relay will send an incorrecttrip signal under certain systemconditions.Maintenancecan bring the relay from the"hidden failure" or "potential maltrip" states back to the"healthy" state. Figure 2.24 Model for protective relay,consistingof one healthy and six nonhealthy states. An Industrial Supply. Considerthe system shown in Fig. 2.25. The industrial load is fed via threeoverheadlines from two generatorunits plus the public supply. The rating of the componentsis such that one line is sufficient to supply the whole load; also onegeneratoror the public supply are sufficient. We further assumethat a failure of a line and a failure of the public supply are associatedwith a short circuit, but that a generatorfailure only involves thetripping of the unit. It is assumedthat eachcomponentcan be in one of two states. Only failures of the public supply, the on-sitegeneratorsand theoverheadlines, areconsidered.This results in the system states as shown in Fig. 2.26. The system consistscomponents, of 6 each with two states. Thenumberof system states is thereforeequal to 26 = 64, but only 23 states are shown in Fig. 2.26. By assuming that the three lines are identical, and the two Section 2.5 • 79 BasicReliability EvaluationTechniques On-sitegeneration Public supply Figure 2.25 Example of industrial supply with double redundancy. Industrial load on-site generatorsalso, states can be aggregated.For example, state 2 {I line out} representsthree basicstates{line lout, line 2 out, line 3 out}; state 5 {2 lines out} also representsthree basic states: {line 1 and line 2 out}, {line 1 and line 3 out}, {line 2 and line 3 out}. Thestateshown on top is the one with all componentsin operation. From this statethe system can reach three other states: • One line outof operation. • One generatorout of operation. • The public supplyout of operation. an An interruptionof the supply can be due to the system being inunhealthystate (e.g., three lines out), but also due to an unhealthytransition between twohealthy states. Astate-basedstudy would onlyconsiderthe states,n ot the transitionsbetween states. To includeinterruptionsdue to unhealthytransitions,an event-basedapproach is more suitable. In this system it can beassumedthat only short-circuitfaults lead tounhealthy o f the public supply. Thesepotentially transitions,thus only line failures and failures unhealthytransitionsare indicated by an arrow in Fig. 2.26. From the state{2 lines out}, again, threetransitionsare possible: • The failure of the last remainingline will anyway result in aninterruption as the final stateis an unhealthyone. Thistransitiondoesnot need to befurther studied. generatorout} • The failure of a generatorleads to the state {2 lines and one which is ahealthystate. Thetransitionis not associatedwith a shortcircuit and does not requirefurther study. • The failureof the public supply isassociatedwith a shortcircuit and it leads to a healthystate. Thistransition requiresfurther study. 80 Chapter 2 • Long Interruptions and Reliability Evaluation ,, , , ,, \ \ , \ ,, , I 8 \ "~ ~ ,, -, ... I ... , , / , I ... , I , '", " I I I / / " \\, ... , , , \\,', "" \ Figure 2.26 Statesand transitionsfor the systemshownin Fig. 2.25.The solid lines indicate transitionsbetweenhealthystates,the dotted lines indicate transitionsbetweena healthystateand anonhealthystate, the arrowsindicatetransitionsassociatedwith a short-circuitevent. 2.5.4 Markov Models Markov models are amathematicalway of calculating state probabilities and event frequencies instochasticmodels. In Markov-model calculations all lifetimes and repair times are assumed exponentiallydistributed.A Markov model consistsof a numberof states, withtransitionsin between them; several examples will be given below. One-Component Two-State Model. The simplest Markov model is shown in Fig. 2.27: atwo-statemodel of one component.In state 1 the componentis healthy, 81 Section2.5 • Basic Reliability EvaluationTechniques Figure 2.27 Two-state Markov model. in state2 it is nonhealthy.The transition rates areA and J-L, as indicated.This model will be used tointroducesomeof the basic concepts and calculationtechniques. To derive the expressions for the state probabilities, one should consider an infinite number of stochasticallyidentical systems. At a timet a fraction PI of the systems is instate 1 and afraction P2 in state 2, withPI + P2 = 1. In mathematical terms: theprobability of finding the system in state 1 is equal PI' to The transitionrate from state 1 tostate2 is A. Thus in a veryshortperiod t1t a fraction At1t of the systems J-Lt1t of the systems in state 2 in state 1transitsto state 2. In the mean time fraction a transitsto state I. The fraction of systems instate1 at time t + t1t becomes (2.50) A similar expression isobtainedfor the probabilityto find the system in state 2. Making the transitionfor !:!t ~ 0 gives the followingdifferential equationsfor the stateprobabilities: dpi -dt = -API + J-LP2 +' We seethat' dP2 dt - = JlP2 -API = 0, which isunderstandableif one realizesthat PI + P2 = 1 (2.51) (2.52) (2.53) i.e., the sumof state probabilitiesequalscertainty.To calculatethe stateprobabilities only oneof the expressions (2.51) and (2.52) is needed, togetherwith (2.53). From (2.51) and (2.53) we can solve the probability that the system is instate1, thus that the componentis healthy. It is assumed t hat the componentis healthyfor t = o which correspondsto PI (0) = 1. P (t) 1 = _Jl_ + _A_e-t(A+Jl) A+J-L (2.54) A+1l- We seethat the probability reaches aconstantvalue after anexponentiallydecaying transientwith a timeconstantA~ • For almost any engineering system we may assume that repairis much faster thanf:ilure, thus A «/1.. When we also realizethat is the averagerepair time, we seethat the probability reaches aconstantvalue within a time of interestis normally much largerthan scale equal to the repair time. The time period the repair time (years versus hours) so that we can considerthe system states and transition frequenciesconstant.This holds not only for atwo-componentmodel but for every Markov model in which repair takes place much faster than failure. k 82 Chapter2 • Long Interruptionsand Reliability Evaluation Steady-StateCalculation. As the transition between the initialcondition and the steady-stateprobabilities can be neglected, we can directly calculatethe steadystate probabilities. In steady state, the state probabilities are constantas a function of time; thus, dpi =0 dt (2.55) The equationswhich describe thestateprobabilitiesbecomealgebraicequations,which can be easily solved.For the two-statemodel weobtain o = -API + ttP2 o = API - IlP2 PI + P2 = (2.56) I One of the equationsin this set isredundant,so that only oneof the first twoequations is needed.From this one and thethird equation,the steady-stateprobability becomes PI = A +tt JL (2.57) P2 =-A- (2.58) A+1l Operating Reserve. We mentionedbefore that we can neglect thetransition to the steadystateand thuscalculatesteady-stateprobabilitiesdirectly. Two exceptions to this rule must be mentioned:one for veryshort time scales,and one with a very long repair time. When looking at a veryshort time scale theexponentiallydecaying componentof the stateprobability can nolonger be neglected. Veryshort time scales that a componentis in are of interestin operatingreserve studies, where one knows operation,and wants to know the probability that it fails within a time flt. For a two-statemodel we derived before: P2(flt) = I - Pl(flt) = _A A+Jl Assumingthat 6.t A_e-~t(A+tL) A+Jl (2.59) « h« *we obtain the following approximatedexpression: A P2(6.t) ~ -Jl6.t = A~t (2.60) JL Note that the same result is obtainedif we assumethat the componentmay fail but that it is not repairedwithin the period flt. Hidden Failures in a Protective Relay.A second example in which the exponentially decaying termcannotbe neglected is aprotectiverelay with hidden failures. Hidden failures of protective relays havealready been discussed in Section. 2.4.2. If that repair takes placeinstantawe neglect allother failures of the relay, and assume neously when thehidden failure is detected,we obtain the statemodel shown in Fig. 2.28. In state 1 the relay is healthy and a fault in the primary componentto be protected is cleared as intended.If the relay is in state2, the fault will not be cleared by this relay, but instead some backup protection needs to take over. The third state shown in Fig. 2.28 is therepair state. The failure rateA2 is the fault frequency in the primary component. We will initially assume that no preventive maintenanceis performedon the relay. Section2.5 • 83 BasicReliability EvaluationTechniques Figure 2.28 Model for relay withhidden failure (left); the relay ishealthyin stateI and containsa hiddenfailure in state2. The figure on the right gives thetwo-statemodel which is obtainedby neglectingthe repair time 11. From the three-statemodel in Fig. 2.28 weobtain the following setof equations for the stateprobabilities: (2.61) From this it is possible toobtain expressionsfor the stateprobabilitiesPI, P2, and P3 and for thetransition frequenciesAIPI, A2P2, and J-LP3' Neglectingthe transientto steadystategives the followingequationsfor the state probabilitiesin steadystate AIPI = I-tP3 = AIPI IlP3 = A2P2 PI + P2 + P3 = 1 A2P2 (2.62) (2.63) EliminatingPI andP3 from the first threeexpressionsand substitutingthis in thefourth one results in (2.64) The frequencyof fail-to-trip events insteadystateis (2.65) If we assumethat repair (the transitionfrom state3 to state1) takes placemuch faster than detectionof the hidden fault (from state2 to state3), we can neglects tate3 and obtain the two-statesystemshownon the right of Fig. 2.28. This model results in the following equations: dpi dt = PI -AIPI + P2 = 1 + A2P2 (2.66) (2.67) 84 Chapter2 • Long Interruptionsand Reliability Evaluation which correspondsto the equationsfor the two-statesingle-componentm odel in Fig. 2.27 and (2.51) through (2.53). The resultingprobability of being in the hidden-failure stateis P2(t) = AI Al +A2 [I _e- /()..I+A2>] (2.68) The fail-to-trip frequencyis equalto A2P2 and reachesits steady-statevalue with a time constant A This holds if we assumethat hidden failures only reveal themselves during a f~urt in the primary component.In case maintenanceis performed with a frequencyA3 the transition rate from state2 to state1 is A2 + A3' The probability that the relay is instate 2 becomes LA,' P2(t) = [I _e-IO'I+A2+A,l>] AI Al + A2 + A3 (2.69) Maintenancereduces the time constant with which the steady-stateprobability is reached,and (more importantly) it reducesthe steady-stateprobability. The number of fail-to-trip eventsper year nm l remain equal to A2P2, thus given by the following expression: n (1) = mt v. AI A2 Al + A2 + A3 [I' _e 3>] -t(AI +A2+ A (2.70) We seethat for maintenanceto be effective, the maintenancefrequency needsto be higher than the sum of the fault frequencyin the primary componentand the hiddenfailure rate of the relay (2.71) Two-Component Model. Considera system that consistsof two components: component1 and component2, with failure rates At and A2, and repair rates J,Lt and ~2' If we model eachcomponentthrough two states,this systemhasfour states: • • • • State 1 with State 2 with State 3 with State4 with both componentsin operation. only component2 in operation. only component1 in operation. none of the componentsin operation. The resultingstatemodelis shownin Fig. 2.29.The equationsfor the stateprobabilities are dpi dt = -(AI + A2)PI + JLIP2 + JL2P3 dP2 (2.72) dt = AIPI - (JLI + A2)P2 + JL2P4 (2.73) dP3 dt = A2PI - (J.t2 + At)P3 + J.tIP4 (2.74) dP4 dt = A2P2 PI + P2 + P3 + P4 = 1 + AIP3 - (J.tl + J,L2)P4 (2.75) (2.76) Section 2.5 • 8S BasicReliability EvaluationTechniques Figure 2.29Two-component,two-state Markovmodel. Thesecan be solvedagain like for the previousexamples,but there is an alternative solution method.We haveassumedthat the two componentsare stochasticallyindependent.This assumptionhas not beenmadeexplicitly but by making the failure and repair ratesof the componentsindependento f the stateof the othercomponent.If the componentsare stochasticallydependent,the transition rate from state 1 to state2 is not the same as the one from s tate3 to state4 (both representfailure of component1), etc. For stochasticallyindependentc omponentswe can multiply the componentstate probabilitiesto get the systemstateprobabilities.Thus, with Pidown and Piup the probabilities that componenti is in the "up" and in the "down" state, respectively, we obtain for the stateprobabilities = Plup X P2up P2 = PIc/own X P2up P3 = Plup X P2down P4 = Pldown X P2down (2.77) PI (2.78) (2.79) (2~80) Theseequationshold for eachmomentin time, thusfor the transientto steadystate,as well as for thesteadystate.Using the expressionsfor the stateprobabilitiesin the onecomponentmodel the steady-stateprobabilitiesin the two-componentmodel become /-LI/-L2 PI = 0"1 + ILI)p + 1L2) o2 (2.81) AI/-L2 P2 = pol + IL] )().o2 + IL2) P3 = po] + ILI)P'2 + 1L2) (2.82) /-L IA2 AI A2 P4 = (>"] + ILI)O'2 + 1L2) (2.83) (2.84) Series and ParallelConnections. We can use theseresults to obtain exact expressionsfor the failure rate and repair time of series and parallel connections, approximationsfor which were given inSection 2.5.2. For a seriesconnection of components1 and 2, state 1 is the healthy state. System failure is a transition from state 1 to state2, or from state 1 to state3. The systemfailure rate As is the sumof these twotransition rates: A - A s - PI I A _ + PI 2- /-L1/-L2(AI + A2) p.] + ILI)P'2 + IL2) (2.85) 86 Chapter2 • Long Interruptionsand Reliability Evaluation The systemis unavailablewhen it is not in state 1. The systemrepair time's is found from the unavailability Qs: (2.86) As's= Qs = I - PI The averagerepair time for the seriesconnectionis AI112 + A2111 + AIA2 111112(AI + A2) (2.87) ,~=------- . In a similar way expressionscan be derived for the parallel connection.For a parallel connection,states1, 2, and 3 arehealthy,and systemfailure is a transitionfrom state2 to state4 or from state3 to state4. The resulting expressionsfor failure rate Ap and repair time 'p are (2.88) (2.89) Exact Solutionof Large Markov Models. For a systemwith a large numberof states, the underlying equationscan be derived in the same way as shown in the above example. The set of differential equationscan be written in the following matrix form: -dP = AP(t) dt (2.90) with A the matrix of statetransitionsand P the vector of stateprobabilities. For the Markov model in Fig. 2.29we get (2.91) and o 112 A= JLl (2.92) -J-l1 - J-l2 The off-diagonal element Aij is the transition rate from statej to state i. The diagonal elementA ii is minus the sum of all transition ratesaway from state i: (2.93) Aij=\i A ii = - LAij (2.94) j Togetherwith an initial condition for the stateprobability vector 75(0) = Po (2.95) we obtain the following solution for this initial value problem: P(I) = Sexp[-Al]S-IPo (2.96) Section 2.5 • 87 BasicReliability EvaluationTechniques with S the matrix of eigenvectorsof A and A the diagonalmatrix of eigenvaluesof A. BecauseA is a singularmatrix (the sumof all transitionsis zero) oneof the eigenvalues is zero. That leads to aconstantterm in the solution P(t) = v: + LPie-~ (2.97) ;>1 In most cases wecan neglect thetransientsand are only interestedin the steady-state solution Note that the steady-statesolutionis independento f the initial values.The steady-statesolution can be obtaineddirectly from the transition rates by setting the time derivativesto zero: r; (2.98) (2.99) Approximate Solutionof Large Markov Models. The main problem with the exact solution of large systemsis that all stateprobabilities have to becalculatedat the same time, even those with a very low probability. For an N-state model, an N x N matrix has to beinverted to find the steady-stateprobabilities.Assumingthat all componentshave two states(up and down) an It-componentsystem requires 2n states.Thus, a IO-componentsystemalready requires 1000 states,and a 150-component model requires the inversion of a matrix of size 1045• In other words, this methodhas seriouslimitations. We might be able tosomewhatreducethe numberof states,but exact solutionsfor systemswith more than 10 componentsare in practice not possibleto obtain. To overcomethese limitations, one can use anapproximated method, which gives recursive expressionsfor the state probabilities [145]. The assumptionsmadeare as follows: • The statewith all componentsin operationhasa probability equal to one. • The repair rate of a componentis much larger than its failure rate. • The probability of a statewith k componentsout of operationis much lower than the probability of a correspondingstatewith (k - 1) componentsout of operation. All these assumptionscan be brought back to one basicassumption:the components are repaired much faster than they fail. This is a reasonableassumptionfor most engineeringsystems.An exceptionare theso-called"hiddenfailures" discussedbefore. For hidden failures the model requiressomeadjustments. Consideragain the statemodel for an industrial supply, as shown in Fig. 2.26. Partof this figure has beenreproducedin Fig. 2.30.Here A and JL arefailure and repair rates,respectively.The index 1 refers to lines, the index 2 to generators,a nd the index 3 to the public supply. The exactexpressionsfor the stateprobabilitiesof states1 through4 are (2.100) 88 Chapter2 • Long Interruptionsand Reliability Evaluation Figure 2.30 Part of a multistateMarkov model. (Reproducedfrom Fig. 2.26.) + A3 + J-tl )P2 = 3AtPI + 2J-tIPs + J-t2P6 + J-t3P7 (3AI + A2 + A3 + /l2)P3 = 2A2PI + J-ttP6 + 2J-t2PS+ J-t3P9 (3AI + 2A2 + J-t3)P4 = A3PI + /lIP7 + J-t2P9 (2AI + 2A2 (2.101) (2.102) (2.103) The approximatedmethod starts with assumingthat the system is almost certainly healthy, thus PI =1 (2.104) According to the third assumption,we neglectthe termswith Ps, P6, P7,pg, and P9 on the right-hand side of (2.101) through (2.103). That gives the following equationsfor the states2 through 4: (2AI + 2A2 + A3 + J-tl)P2 = 3AIPI (3AI + A2 + A3 + J-t2)P3 = 2A2Pt (3A) + 2A2 + J-t3)P4 = A3PI (2.105) (2.106) (2.107) As PI is known we obtain the stateprobabilitiesof thesethreestateswithout having to know the other stateprobabilities: 3AI P2=------2A) + 2A2 + A3 + J-tl 2A2 P3=------3AI + A2 + A3 + J-t2 A3 P4 = 3Al + 2A2 + J-t3 (2.108). (2.109) (2.110) A correctioncan be madeby recalculatingthe probability PI from PI = 1- LP; (2.111) ;>1 The samemethod can be applied to states5 through 15, each time resulting in an equationin which only one stateprobability is unknown. Insteadof having to solve all stateprobabilitiesat the sametime, this procedureallows solving stateprobabilities sequentially. For very large systems,not all statesare of equal interest, which can 89 Section 2.5 • Basic Reliability Evaluation Techniques further reduce thecomputationalrequirements.The recursiveprocedurecan, e.g., be stoppedwhen the stateprobability drops below acertainvalue. 2.5.5 Monte Carlo Simulation Basic Principles. In all precedingexamples, theunknown quantitieswere actually calculated. We saw several timesthat approximationsand assumptionswere needed toobtain a solution. In a Monte Carlo simulation, or simply simulation, theseassumptionsand approximationsare no longer needed. The Monte Carlo simulation methoddoes not solve theequationsdescribing the model;insteadthe stochastic behaviorof the model issimulatedand observed. The behavior of the system(stochasticprocess isactually a better term) is observed many times or for a long period of time. The averageobservationis used as anestimatefor the expectedbehaviorof the system. The basisof each Monte Carlo simulation involves using a so-calledrandomnumber generator.The random-numbergeneratoris needed to bring thestochastic element in thecalculations.One could use a physical random-numbergeneratorlike a dice or a coin, but anumericalrandom-numbergeneratoris more suitablefor computer-basedcalculations. A coin can be used to model statewith a a probability of 50% • Consideras an example athree-component system with500/0 availability for eachcomponent.The coin is used togeneratecomponentstates, with the second columnin Table2.11 the resulting sequence. Thisrepresentsthe stateof one of thecomponentsover 24consecutiveI-hour periods. The same is done for component2 and component3, resultingin columns3 TABLE 2.11 MonteCarloSimulationwith 50% Probabilities Hour I 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 Component1 Component2 Component3 SystemI System2 System3 up up down down up down up up down down up up up down down up up down up up down up down down up down down up down down up down up up up down up up down up down up down up up up down up down up up down up down up up down down down up down down up down up up down down down up up down up up down down up down up up down down up up up down down up up up down up down up down down up up up down down down up up up down down down up up down down down up up up up up up down up up down down up down up down down down dow down down down down down down down down up down up down down 90 Chapter2 • Long Interruptionsand Reliability Evaluation and 4, respectively. The column labeled"systemI" gives thestateof a system which is available if at least twocomponentsare available. One can make thisM onte Carlo simulationas complicatedas one wants. In the column labeled"system2" the system is down if less than two componentsare available for two consecutivel-hour periods, and if the system is down it remains down for at least 3 hours.For "system3" the system needs three componentsto beavailablein the hourly periods 8through 18, but only two for theother periods . As a second example consider threecomponentswhose lifetime is uniformlydistributed between 0 and 6 years. To generate the lifetime of these componentswe can use a dice. By using this we simulatethe behaviorof this three-componentsystemduring 10 years. In Fig. 2.31 three possibleoutcomesof this "experiment" are shown . Each possible outcomeis called a "sequence."During sequence 1, the firstcomponentfails after 3 years and again after 6 years; the second componentfails after 2, 6, 7, 9, and 10 years, etc. Sequence I 3 21 6 I ~~ I 4 I I 4 Sequence 2 o--L-o 6 G>>-+-~-~e 6 o~ cr--1--o--i--o--,,-6----,,.--Sequence 3 3 4 4 2 6 010 .. 4 5 0 3 --0 I 5 ; 10 years - 0 • Figure 2.31Threesequencesof a Monte Carlo simulation.The circles indicate failures followed by repair ; the numbers in between indicate times-to-failure. At time zero all threecomponentsstart their first lifetime. Upon failure they are repaired and a new lifetime determined.This is process isrepeateduntil t = 10 years is reached .F rom the outcomeof this stochasticexperiment,many different outputparameters can be chosen, for example, • Total numberof componentfailures in a IO-year period . In this case the values 11, 7, and 8 are found . • Total numberof events with two or morecomponentfailures in the same year, with values 3, 2, and 1 being found . • Probability distribution function of the componentlifetime. Numerical Random-Number Generators. In practice one never uses physical random-number generatorslike dice or coins. The reason is that it is difficult to actually use them in acomputer program and hand-calculationsof Monte Carlo simulationsare verycomplicated,as will be clearafter the preceding examples. Section 2.5 • 91 BasicReliability EvaluationTechniques A numerical random-numbergeneratorcreates a rowof integers of pseudorandom nature. The row is not really random as a numerical algorithm is used to calculateit-therefore,the term"pseudo-randomnumbergenerator."Most computer simulationsuserandom-numbergeneratorsof the following form: U;+1 = (aU;)modN (2.112) where a and N have to be chosen. The output of this is a rowof integers with values between 1 and(N - 1). EXAMPLE Considerthe values N = 11 and a = 7. That gives the following row of integers: 1,7,5,2,3,10,4,6,9,8,1,7,5,2,3,10,4,6,9,8,1, etc. The row repeatsitself after 10elements,which isunderstandable if one realizesthat thereare only 10 possibleoutcomesof (2.112). A cyclelength 10 (in general(N - 1) ) is the longestpossible value. To showthat shortercycle lengthsare also possible,considerthe random-numbergeneratorwith N = II and a = 5 which has twopossiblerows, eachof cycle length 5: 1,5,3,4,9,1 2,10,6,8,7,2 The random-numbergeneratorsin use in Monte Carlo simulationshave much longer cycles lengths, andtherefore much higher valuesof N. A popular value is N = 231 - 1 = 2 147483647.Most valuesof a give a cycle length less t han N - 1. A value of a which gives themaximumcycle length isa = 950 706376.Startingfrom U = 1 we get the following rowof integers: 1, 950706376,129027 171,I 782259899,365181143,1966843080,etc. The resulting integer is often divided by N to get arandomnumberbetween 0 and 1, which leads to a slightlydifferent version of (2.115): u _ aNU;modN ;+1- N (2.113) The resultof (2.113) is arandomdraw from the uniform distribution on the interval (0,1). Neither zero nor one can beobtainedthrough this method, which is often an advantageas it preventsdividing by zero in further processingof the result. This standarduniform distribution is the basis for allM onte Carlo simulations. For N = 11 and a = 7, (2.113) results in thefollowing row of samples: 0.09,0.63,0.45, 0.18, 0.27, 0.91, 0.36, 0.55,0.82,0.73, 0.09, etc. EXAMPLE Simulating a Probability-RandomMonte Carlo Simulation. Two types of Monte Carlo simulation can bedistinguished:random simulation and sequentialsimulation. An example of random simulation is the simulation shown in Table 2.11. In a random Monte Carlo simulation each componenthas aprobability of being in a certainstate. Thesimulation generatescombinationsof componentstates.For each resulting combination the systemstate (healthy or nonhealthy) is evaluated.This whole process isrepeateduntil a certainaccuracyis obtained. 92 Chapter 2 • Long Interruptions and Reliability Evaluation The basisof a randomMonte Carlo simulationis the probability: an eventtakes place with acertain probability, a quantity has acertain value with a certain probability, or a componentis in a certainstatewith a certainprobability. A probability is simulated by drawing a value from the standard uniform distribution introduced before. Let p be the probability that the componentis in state 8 1; otherwise, the componentwill be in state 8 2, then the Monte Carlo simulation proceedsas follows: • Draw a value U from the standarduniform distribution. • If U :s p the componentis in stateSI. • If U > P the componentis in state S2. Note that for U = p the componentstateis actually not defined. In this examplethis situationis attributedto stateSI but it could equally have beenattributedto state S2. This ambiguity has to do with our discretizationof the uniform distribution. For a continuousdistribution the probability that U =p is zero. For a random-numbergenerator with a cycle length of 231 - 1 this probability (5 x 10-1°) is small enoughto neglect in allpracticalcases. Simulating a Time Distribution. The basis of a sequentialsimulation is the time distribution. Thereforewe need amethod of obtaining other distributions than just the standarduniform distribution, Le., the uniform distribution on the interval (0,1). The uniform distribution on an interval (T1, T 2) is obtainedfrom a sampleof the standarduniform distribution U as follows: (2.114) where X is a sample from the uniform distribution on the interval (Tt , T 2) . More general:a stochasticvariable S with a distribution function F(s) is obtainedfrom (2.115) where U is a stochasticvariablewith a standarduniform distribution.To provethis, we look at the probability distribution function of the stochasticvariable S accordingto (2.115), thus at the probability that S is lessthan a certainvalue s. Pr{S < s} = Pr{F-1(U) < s} (2.116) As F is a non-decreasingfunction, we can write this as Pr{S < s} = Pr{ U < F(s)} (2.117) The stochasticvariable U has astandarduniform distribution; thus, Pr{ U < x} = x, for 0 < x < 1 (2.118) As 0 < F(s) < 1 we get theintendedexpression,which proves that S is distributed accordingto F(s). Pr{S < s} = F(s) (2.119) 93 Section 2.5 • Basic Reliability Evaluation Techniques Consideras anexample,the Weibull distribution introducedby (2.25).From (2.115) it follows that a sample W from the Weibull distribution with characteristictime 0 and shapefactor m is obtainedfrom a sampleU from the standarduniform distribution by W = Oy!-ln(l - U) (2.120) For m = 1 we obtain the exponentialdistribution as a special case o f the Weibull distribution. A sample E from the exponentialdistribution with expectedtime 0 is obtainedby E = -Oln(l - U) (2.121) Sequential Monte Carlo Simulation.The examples in Fig. 2.31 show sequena tial simulation. In a sequentialMonte Carlo simulation, the whole timebehaviorof a system issimulated,with failure and repair of componentsthe main subject in a reliability study. But alsoother events, like loadswitching and weatherchanges,can be part of the simulation. This kind of simulation offers the most opportunitiesof obtainingoutput, but it also requiresthe most programmingand computingefforts. "Thedetailsof a sequentialM onte Carlosimulationvary widely anddependon the particular application,the kind of programminglanguageavailable,and on personal tasteof the programdevelopers.Below, a possiblestructureis given which was used successfully by theauthorfor evaluatingthe reliability of industrialpowersystems[61], [62], [63]. Only onesequenceof a given length is described here. This sequence shouldbe repeateda largenumberof times to getstatisticallyrelevantresults. I. Set up an initial event list. At thestart of each sequence, times for the first event aredrawn for eachcomponent.The first event is typically a failure or start of maintenance.These events aresorted on time of occurrenceand placed in a so-called"event list." Part of an event list would typicallylook as follows: 0.15 years component2 failure 1.74 years component5 maintenance 3.26years component1 hidden failure 4.91 years component5 failure 5.67 years component2 maintenance 6.21 years componentI maltrip This event listshouldbe interpretedas follows: at t = 0.15 years,c omponent 2 will fail; at t = 1.74years,maintenanceon component5 is planned,etc. Not all events in the list willactuallyoccur. We will see belowthat events may be removedfrom the' event listand that events may beinserted.Furtheron in the simulationof this sequence, it will always be the event top on of the list which will be processed,a fter which the event list will beupdated.When the event list isempty the simulationof this sequence is over. 2. Processthe event on top of the event list. Processingof the event on topof the eventlist (thusthe next event tohappenin the system) is themain part of the simulation, which will take up most time in programmingand deciding about. This is where thestochasticmodel of the power systemand its componentsis implemented.The processingof an event typicallyconsistsof making changesin the event list and making changesin the electrical model of thepowersystem.Changesin the powersystem can be the removal 94 Chapter 2 • Long Interruptions and Reliability Evaluation of a component(e.g., due to theinterventionof the protection)or the insertion of a branch(e.g., repair of a componentor due to ashort-circuitfault). To assess the effect of the eventon the load, eitherthe newsteadystateor the electrical transientdue to theevent need to beevaluated.The interruption criterion needs to beappliedto decideif this eventleads to aninterruptionor not. The changesin the eventlist will be discussedbelow for different events. (a) Short-circuitevent. The next event after a short-circuit event will be an intervention of the protection. Some rules areneededto decide which relays will intervene: the relay or relays which need to clear this fault; thosewhich incorrectly intervene;and thosewhich take over the protection in case one orm oreof the primary relays fails totrip. For eachrelay a time until tripping needs to bedetermined.Tripping of the fault normally takesplace very soon after the short-circuit event. Thereforeone can decide totreat fault initiation (short-circuitevent)and fault clearing (protectioninterventionevent)as one event.H ere they areconsideredas two events. (b) Protectionintervention event. During the processingof this event one needs todistinguishbetweenthe last relay totrip and all the other protection interventionevents.After the last relay hastripped the repair of the faulted componentc an startand also theswitching neededto restore the nonfaultedcomponentstripped by the protection. For the Monte Carlo simulation this meansthat times to repair and times to switching need to bedetermined.Alternatively one can determineall these times when processingthe short-circuitevent. (c) Repairevent. When a componentis repaired,it can fail again.Therefore a time to failure needsto be determinedfor all its failure modes:short circuit, maltrip, hiddenfailure, etc. Different failure modeswill typically have different lifetime distributions. (d) Maltrip event. A maltrip eventis associatedwith the power systemprotection, either with a circuit breakeror with a protectiverelay. The next eventsto bedeterminedarerepairof failed componenta ndrestorationof the primary componenttripped. (e) Hidden failure event. Ahidden failure eventwill not reveal itself immediately. Thereforeit will only changethe way the relay will infuture react to a short-circuitevent. Only when ahidden failure reveals itself,either due to ashort circuit or due tomaintenance,will the repair start. (f) Start of maintenanceevent. Start of maintenancewill require the scheduling of an end of maintenanceevent. For an accuratemaintenance model, one needs tointroducean additional event called "maintenance attempt." Maintenanceattemptsare scheduledand either immediately lead to astart of maintenanceevent or to a new maintenanceattempt event. Somerules areneededto decideif the systemstateis suitablefor maintenanceto beperformed.The rules will dependamongotherson the companyrules for performingmaintenance.S omeexamplesare • Maintenancecannotbe performedat more than one componentat the same time, e.g.,becausethere is only one maintenancecrew available. • Maintenancewill not be performedif it leadsto an interruptionof the supply for any of the loads. 95 Section 2.5 • Basic Reliability Evaluation Techniques • Maintenancewill not be performedwhen aparallel or redundantcomponentis out of operation. When processingthe start of maintenanceevent, the time for an endof maintenanceevent needs to bedetermined. (g) End ofmaintenanceevent. When the maintenanceis finished a newmaintenanceattempt or start of maintenanceevent needs to bedetermined. Also some future fail events will be influenced by the maintenance. Typically the componentis assumedto be"as-good-as-new"a fter maintenance.In that case allfuture fail eventsare removedfrom the eventlist and new ones aredrawn from appropriatedistribution functions. Some additional rules might be neededto control the processingof events. One might, for instance,decidethat a componentc annotfail while it is out of operation(for any reason).One can makea checkduring a failure event to see if a componentis in operation and simply draw a new failure event without any additional processingif the componentis not in operation. One can also decide to shift all failure events belonging to a component further into the future with a time equal to the time during which it is out of operation. 3. Update the event list. All new events whichoccur before the end of the sequenceare placed in the event list; the eventjust processedis removed; the eventlist is sortedagain;after which the eventthat appearson top of the event list is processed. Errors in the Monte Carlo Simulation. An exampleof the result of a Monte Carlo simulation is shown in Fig. 2.32. The figure has beenobtainedby taking samples from the uniform distribution on the interval (0,1), followed by calculating the averageover all the proceedingsamples.For an increasingnumber of samples,the averagevalue approaches0.5. As wecan see from the figure, theerror is still rather large after 100 samples. Figure2.33 gives thebehaviorfor a much largernumberof samples.A fter 10000 samples,the error has becomelessthan 1%, but is still not zero. An importantproperty of the Monte Carlo simulation is that the error approacheszero, but never becomes zero. Figure 2.33 also showsanotherpropertyof the Monte Carlo simulation: the fact 0.4 ~ Q) ~ 0.3 I 0.2 Figure 2.32 Outcomeof a Monte Carlo simulation. 20 40 60 Samplenumber 80 100 96 Chapter2 • Long Interruptionsand Reliability Evaluation 0.55 .------~--~--~--~--_, 2000 4000 6000 Samp le number 8000 that each simulation may give a different result. The figure gives the result of 10 simulations, each using adifferent starting value of the random-numbergenerator. Note that exactly the sameresultsare obtainedif the samestarting value is used for the random-numberg enerator. The error in the result of a Monte Carlo simulationcan be estimatedby usingthe so-calledcentral-limit theorem.This theoremstatesthat the sumof a large numberof stochasticvariableshas anormal distribution. Supposethat eachsequenceof a simulation gives a value Xi for a certain stochasticvariable X. This value can be the total number of interruptionsduring 20 years, but also the fraction of interruptionswith durationsbetween1 and 3 hours.What we areinterestedin is the expectedvalueof such a variable.To estimatethe expectedvaluewe usethe averagevalue, which is astandard procedurein statistics. Let X be the averageof N samplesof Xi: (2.122) For sufficiently large N, X is normally distributedwith expectedvalue ux andstandard deviation aA" where Ilx and ax areexpectedvalue and standarddeviationof Xi' Thus, _ 'iN X is an estimatefor Ilx (the expectedvalue of X) . The error in the estimateis proportional to the standarddeviation. Note that obtainingthe valueof ux is the aim of the simulation. The Stopping Criterion. The fact that the error in a Monte Carlo simulation will never becomezero meansthat we have toaccepta certain uncertaintyin the result. This issometimesmentionedas a disadvantageof the Monte Carlo simulation, but also analytical calculationsare uncertain, due to theassumptionsand approximations madein the model. Where the error in an analytical calculationis often impossible to estimate(unless a better model is used), theuncertainty in the result of a Monte Carlo simulation can be estimated.The outcomeof any Monte Carlo simulation will be a stochasticquantity with a normal distribution. For the normal distribution we know that 95% of all values are within two standard deviations of the expectedvalue. We saw above that the standarddeviation after N samplesis equal to ~. The 95% confidenceinterval of the estimateis thus, Section 2.5 • 97 BasicReliability EvaluationTechniques - ax - ax (2.123) X-2-</lx<X+2- ./N ./N The standarddeviation of the stochastic quantity X, ax , can beestimatedthroughthe following expression: I ?=xl- [1 ax ~ N_ I N N ]2 (2.124) N?= Xi 1=1 1=1 At regular momentsduring the simulation, e.g., after every 100 sequences, error the in the estimates may be calculatedand comparedwith the required accuracy. When the required accuracy is reached the simulationcan bestopped. Note that to determine the of the sum of theXi values but also of the sum error, one needs not only keep a record of their squares . Convergence Tests.Because of the slow convergence process Monte of a Carlo simulationit is hard to recognize a case in which the average no longer converges to the expected value. Such situation a arises, e.g., when the random-numbergenerator has ashort cycle length. Consider again (2.123), which shows that error the (X - u.x ) decreases as -:fN. One can conclude from this that the function (2.125) neither converges nor diverges. The convergence parameterC has been plotted in Fig. 2.34 for 10simulationsof 10000 samples each. The underlying simulationis the same as in Figs. 2.32 and 2.33. We see that the plotted quantity remains within a bandaround /lx . zero, thusthat the averageX indeed converges to the expected value In Fig. 2.35 the same convergence parameteris plotted for a simulation which does not converge. The divergence is clearly visible. (From sample 2000onward, the random-numbergeneratorwas given a cycle length of 1000 samples.) !l 0.5 I ., ~ ~ ~ U - 0.5 Figure 2.34 Convergence p arameterfor 10 identical Monte Carlo simulations. 2000 4000 6000 Sample number 8000 10000 98 Chapter2 • ~ I Long Interruptionsand Reliability Evaluation 0.5 os 0.. g " "e!' "c> o U -0.5 , 2000 8000 10000 Figure 2.35 Con vergence parameterfor a non-con vergence case. 2.5.6 Aging of Components In most studies it is assumed that both failure rate and repair rate are constant. of dataand a lack ofevaluationtechniques. At the The underlyingreasons are a lack moment, only the Monte Carlo simulationis capableof incorporatingnonexponential nonexponendistributionsfor nontrivial systems. But despite the lack applicationof of tiallifetime distributions, it is still worthwhile to have a closer look at the variousaging phenomena.Nonexponential repair time distributions are easier to understand, althoughequally difficult to incorporatein the reliability evaluation. Two Typesof Aging. Aging is used in daily life as thephenomenonthat the failure rate of a componentincreases with its age. Here it will be used in a slightly more general sense: aging is the phenomenonthat the failure rateof a componentis dependenton: • the actual age of thecomponent. • the time since the last repair or maintenance . To quantify the dependenceof the failure rate on the age of the component,the so-called"bathtubcurve" is often used. Acommonway of drawingthe bathtubcurve is T) is called the wear-in period, after T 2 shown in Fig. 2.36. The period between 0 and the wear-out period, and betweenT) and T 2 the useful life or the periodof random failures. One should realize that the bathtubcurve is only a stylized version of whatcan be a rathercomplicatedfunction of time. The actual failure rate as a functionof time can beof completely different shapealthoughit , is likely to containat least an initial wear-in period and an overall increasingfailure rate for oldercomponents[146]. This aging effect can be included in the reliability evaluationmodels, byrepeating the calculationsfor different componentage.For each age one assumes that all failure rates areconstant.From the expressionsobtainedby usingMarkov models in Section 2.5.4, we knowthat the timeconstantwith which the system reacts to changes is of the order of the repair times. For such s hort time scales we can safely assume the failure rate to be constant.That way one can assess the aging of the system, e.g., the interruption frequency as afunction of time. When performing such a study one should 99 Section 2.5 • Basic Reliab ilityEvaluationTechniques Figure 2.36Bathtubcurve :component failure rate versus age. o Component age realize that also the repair time and the durationof maintenanceare likely to increase when thecomponentgrows older. The second type of aging, the fact that the failure rate depends on the time elapsed since the last repair maintenance, or is more difficult to consider in a reliabilityevaluationstudy. Here it is essential that nonexponentialdistributions are used for thecomponentlifetimes. Techniques like M arkov modeling and network representationscan no longer be used. For smaller systems one might use [123], [215]; for larger systems highly mathematicaltechniques like renewal theory only Monte Carlo simulation remains as a practical tool. As an exampleof the second type of aging, assume that the failure rate only depends on the time until maintenanceand that maintenanceis performed at regular intervals. The failure rate as a function of time is as shown in Fig. 2.37: the failure rate increases untilmaintenanceis performedon thecomponent,at whichinstantthe failure rate drops to its initial value again. The dotted line in Fig. 2.37 represents a kind of average failure rate . i Figure 2.37 Failure rate versus time for regular maintenanceintervals. Time - In Fig. 2.38 the failure rates of two componentsare plotted (the dashed and the It is assumed here dottedline), plus the average of the two failure rates (the solid line). that maintenanceon the secondcomponenttakes place in between two maintenance instantsfor the first component.We seethat the average of the two failure rates varies less than each of the failure rates. It is easy to imagine that the failure rate of a large number ofcomponentsbecomesconstantwhen maintenanceon them isperformedat different times. In reality the failure rate not only depends on the time elapsed since the last maintenancebut also on the time elapsed since the last maintenanceor repair. tOO Chapter2 • Long Interruptionsand Reliability Evaluation t • Avejrage .. •• . : ,',' 0. . COlmpo~ent I .. .' ..0: ",1: "" • A , ,'t o· . 0 ee Time----+ Figure 2.38 Failure rate versus time for two components. Similar reasoningsas given formaintenancecan be used for failure, with the difference that the failure instantsare lessregularly positionedthan maintenanceinstants. As-Good-As-Newor As-Bad-As-Old. In Fig. 2.37 and Fig. 2.38 it was assumed that the failure ratedropped to its original value after maintenance.This model is called maintenance(or repair) "as-good-as-new."The oppositemodel is called maintenance(or repair) "as-bad-as-old."In the latter case themaintenanceor repair has no influence on the failure rate; thus the failure rate just after maintenanceis the same asjust before. The two models are shownin Fig. 2.39.For repair as-bad-as-old the failure ratedependson the ageof the component,for repair as-good-as-newit dependson the time since last repair. The actualfailure rate isnormally a combinationbetweenas-good-as-new and asbad-as-old.This can bemodeledas the sumof two failure rate, thus twocomponentsin series: one beingrepairedas-good-as-newand theother being repairedas-bad-as-old. The latterone will lead to an average increase in failure rate which leads towear-out the phase in thebathtubcurve. i t=O As-bad-as-old As-good-as-new i Age of thecomponent-e--> Repairor maintenance Figure 2.39 Repair as-good-as-new and asbad-as-old. Failure Rate Increase due toMaintenance. Somethingthat should also be considered in reliabilityevaluationis that maintenanceand repair can lead to anactual increase in failure rate. The s tandardexampleis the screwdriverleft inside the switchgear. But alsomore subtle effects are possible. In m a aintenanceoptimization study Section 2.6 • Costsof Interruptions 101 one has to take this intoaccountone way or the other. Alsod uring maintenancethe chance of anoutage of anothercomponentis increased: itsloading is higher and there is activity in theneighborhoodwith the associatedrisk of errors. Many aspects of aging are extremely difficult quantify, to but shouldat least be consideredin a qualitative way in reliability evaluationstudies. A serious difficulty in includingcomponentaging is the lackof availabledata:not just componentfailure data is needed, but alsorepair and maintenancerecordsof all the components. Aging Data. Information on aging of power systemcomponentsis hard to publications find. A few examplesof good data are given below. There are more addressingthis problem [107], but the total amount of data is not enough to include aging with sufficient confidence into the reliability evaluation. • A number of Dutch utilities published "expert opinions" on the ageof a componentat which the failure rate significantlys tarts to increase [124]. A group of expertswas asked to give their estimationof this age forcomponents operatedunder "good circumstances,""averagecircumstances,"and "bad circumstances. " [125]. One of the • Bathtubcurves for transformersare presented in reference conclusionsis that newer generationsof transformershave not only a lower overall failure rate but also a longer useful life. The useful life is the period during which the failure rate is more or less constant.Newer productiontechwearniques have however not been able to significantly reducenumberof the in failures. • Another interestingstudy is publishedin reference[126]. By using purchasing records anassessment is madeof the age at whichtransformersfatally fail, i.e., a failure severeenoughfor them to bescrapped.It turnedout that the failure After that, rate stayedconstant,at about0.01 per year, for the first 12 years. the failure rate increased until 1 per year at an age of 29 years. • A bathtubcurve for circuit breakersis presentedin [127], based on the observation of a largenumberof breakers.The failure rate decreases from 0.2 for age zerothrough 0.05 for 8 years after which it rises to 0.15 for 10-year-old breakers. • In reference [128] the failbehaviorof circuit breakersis studiedby dividing the causeof failures into three categories: - initial failures. - randomfailures. - wear-outfailures. By plotting the failure rate as afunction of age for eachcategory,it is shown that the failure rateof random that the failure rateof initial failures decreases, failures staysconstant,and that the failure rateof wear-outfailures increases with time. 2.8 COSTS OF INT.RRUPTIONS To considerinterruptionsof the supply in the design andoperationof power systems, the inconveniencedue tointerruptionsneeds to bequantifiedone way or theother.The term inconvenienceis rather vague andbroad. Any seriousquantification requires a 102 Chapter2 • Long Interruptionsand Reliability Evaluation .....Reliability costs - - . Buildingcosts - Totalcosts Reliability Figure 2.40 Costs versus reliability: costs of building and operation(dashed curve), costs of supply interruptions(dottedcurve), and total costs (solid curve). translationof all inconvenienceinto amountof money. In theremainderof this section we will considercostsof interruptionsin dollars, but any othercurrencycan be usedof course. Many publications on costs of interruption show a graph with costs against reliability. Such a curve isreproducedin Fig. 2.40. The ideabehind this curve isthat a more reliable system is more expensive to build and operate,but the costsof intertotal costs will ruption (either over the lifetimeof the system, or per year) are less. The show aminimum, which correspondsto the optimal reliability. Even if we assumethat both cost functions can bedeterminedexactly, the curve still has some seriouslimitations. Figure 2.40 should only be used as a qualitativedemonstrationof the trade-off between costs and reliability. • Additional investmentdoesnot always give a more reliable system: an increase in the numberof componentscould even decrease the reliabiity. • Reliability is not a single-dimensionalquantity. Both interruption frequency and duration of interruption influence theinterruptioncosts. designercan choose • Thereis no sliding scaleof reliability and costs. The system between a limitednumber of design options; sometimesthere arejust two advantages options available. The choice becomes simply comparisonof a and disadvantageso f the two options. • The two cost termscannotsimply beadded.One term (building and operational costs) has a smalluncertainty,the other term (interruptioncosts) has a large uncertaintydue to theuncertaintyin the actualnumberand durationof interruptions. A more detailed risk analysis is neededthan just adding the expected, costs. The cost of aninterruption consistsof a number of terms. Each term has its own difficulty in being assessed. Again simply adding the terms toobtain the total costs of an interruptionis not the right way,but due to lackof alternativesit is often the only feasibleoption. attributableto the inter1. Direct costs.These are the costs which are directly ruption. The standardexample fordomesticcustomersis the lossof food in the refrigerator. For industrial customersthe direct costs consist,among others, of lost raw material, lost production, and salary costs during the non-productiveperiod. For commercialcustomersthe direct costs are the Section 2.6 • Costsof Interruptions 103 loss of profit and the salary costs during the non-productiveperiod. When assessing the direct costs one has towatchful be of double-counting.One shouldat first subtractthe savings made duringthe interruption.The obvious savings are in the electricity costs, but for industrial processes there is also a saving in useof raw material.An example ofdouble-countingis addingthe of the productalreadyincludes the lost salesandthe salary costs (as the price salarycosts). Also to besubtractedfrom the costsof interruptionis the lost productionwhich can be recovered later. Some plants only run part of the time. Extra salaryduring overtime needed to recover lost productionshould be addedto the direct costs. 2. Indirect costs. Theindirect costs are muchharderto evaluate,and in many casesnot simply to express inamountof money. Acompanycan losefuture orderswhen aninterruptionleads to delay in delivering paroduct.A domestic customercan decide to take an insuranceagainstlossof freezercontents. A commercialcustomermight install a battery backup. A large industrial customercould even decide to move plant a to an area with less supply interruptions.The main problem with this cost term isthat it cannot be attributed to a singleinterruption, but to the (real or perceived) quality of supply as a whole. 3. Non-material inconvenience. Someinconveniencecannot be expressed in 2 can be a serious money. Not being able to listen to the radio for hours inconvenience,but the actual costs are zero. Inindustrial and commercial environments,the non-materialinconvenience can also be big without contributing to the director indirect costs. A wayof quantifyingthese costs is to look at theamountof money acustomeris willing to pay for not having this interruption. To evaluatethe costs of supplyinterruptions,different methodshave beenproposed. For large industrial and commercial customersan inventory of all the direct and indirect costs can be made, and this can then be used in the system design and operation. Even for small customerssuch a study could be made, e.g., to decide about the purchaseof equipmentto mitigate interruptions. However, for small and domestic customersit is often the non-material inconveniencewhich has a larger influence on the decisionthan the direct orindirect costs. For a group of customers, such an individual assessment is nolonger possible. The only generally accepted method is the large surveyamong customers.Customersget asked anumber of questions. Based on the answers the average costs of interruption are estimated. These results are typically the ones used by utilities in decision making. When comparing the resultsof different surveys, it isimportant to realizethat they not all ask the samequestions.Some surveys ask a very specific question:"What are the costsof an interruption of 2 hours on a Monday afternoonin January?"Other surveys use more indirect questioning:"What is a reasonablecompensationfor an interruption" i nterruption frequency from 4 or "What would you be willing to pay to reduce the per year to 3 per year?"Different questionsobviously lead to different estimatesfor the costsof interruption. To quantify the costs of aninterruption,again differentmethodsare in use. Some values can be easily calculatedinto eachother, with some values acertainamountof care is needed. Worse that is it is not always clear from thecontext which methodis actually used. 104 Chapter 2 • Long Interruptions and Reliability Evaluation • Costsper interruption. For an individual customerthe costsof an interruption of duration d can beexpressedin dollars.Thereis no confusionpossibleabout this. For simplicity, we neglectthe fact that the costsnot only dependon the duration but on many other factors as well. The costsper interruptioncan be determinedthrough an inventory of all direct and indirect costs. • Costsper interruptedkW. Let C;(d) be thecostsof an interruptionof duration d for customeri, and L; the load of this customerwhen therewould not have been aninterruption.The costsper interruptedkW are defined as C;(d) (2.126) L; and are expressedin $jkW. For a group of customersexperiencingthe same interruption,the costsper interruptedkW are defined as theratio of the total costsof the interruptionand the total load in casetherewould not havebeen an interruption: (2.127) • Costsper kWh not delivered. Inmany studiesthe assumptionis madethat the costof an interruptionis proportionalto the durationof the interruption.The cost per kWh not deliveredis defined as C;(d) st; (2.128) andis constantunderthe assumption.T hecostper kWh is expressedin S/kWh. For a group of customersthe cost per kWh not deliveredis defined as L; C;(d) dL;L; (2.129) Someutilities obtain an averagecost per kWh not deliveredfor all their customers.This value isassumedconstantand used as areferencevaluein system operationand design. The term "value of lost load" is sometimesusedfor the cost per kWh not deliveredaveragedover all customers. • Costsof interruption rated to the peak load. A problem in surveysis that the actual load of individual customersin case there would not have been an interruption is often not known. One should realize that surveys consider hypotheticalinterruptions,rarely actual ones. For industrial and commercial customersthe peak load is much easierto obtain, as it is typically part of the supplycontract.Thecostof an interruptioncanbe divided by the peakload, to get a value in$jkW. Somecare is neededwhen interpretingthis value, as it is not the same as the cost per kW interrupted (also in $/kW). For planning purposesthe cost of interruption rated to the peak load can still be a useful value. The design of a systemis basedfor a large part on peak load, so that rating the cost to the peak load gives adirect link with the design. • Costsper interruptionratedto the annualconsumption.For domesticcustomers it is easierto obtain the annualconsumptionthan the peak load. Rating the lOS Section 2.6 • Costs ofInterruptions cost of an interruption to the annual consumptiongives a value in $/kWh. Note that this has no relation to the costs per kWh not delivered. of are given in Someof the results of a Swedish survey after costsinterruptions[200] 1993 and Figs. 2.41 and 2.42. The survey was conductedamong 4000 customers in resulted in interruption costs per kW of peak load for interruption duration of 2 2.41 gives the costs for a forced interminutes, 1hour, 4 hours , and 8 hours . Figure 120 0 • • 0 ~ o 2 min I hour 4 hours 8 hours 60 1 40 - r--" 20 f - - - - """ f--- o W _ .,.... -- J Domestic Agriculture Trade and services - f--- lJ Small industry - ~ Textile industry ,', ' ~ - --'--'=' Chemical industry Food industry Figure 2.41 Int erru ption costs in S/kW for different customers, for forced interruptions . Results from a Swedish stud y 1993 in [200). 120 0 2 min • • I hour 0 4hours 8 hours ~ 60 8 § }40 r-r- 20 o f------- --- Domestic ..r Agriculture • Trade and services --f Small industry ~ J Textile industry Chemical industry Figure 2.42 In terruption costs in S/kW for different customers. forscheduled interruptions. Res ults from a Swedish study in 1993[200). ... Food industry 106 Chapter2 • Long Interruptionsand Reliability Evaluation ruption, i.e., in case thecustomerreceives nopre-warningof the interruption. Figure 2.42 relates to scheduled i nterruptions where the customer receives sufficient prewarning. An exchange rateof 7.32 Swedishcrowns per U.S. dollar has been used and an inflation rate of 2.5% per year, toobtain the costs in 1998 dollars. The valuesindicated are averages over n aumber of customers.Surveys have shown that the range betweendifferent customersis very large, even within one type of industry. Rangesof interruptioncost within one typeof industry are given bySkof [147]. For a I-minute interruption the cost for automobilefactories varies between 0.001$/kW and 6$/kW. For a l-hour interruption the range is from 0.3 to40$/kW. of Thus, an industry averageshould be treated with care when assessing the cost interruption for a specificindustrial customer.Where possible, it isrecommendedto otherpublicausecustomer-specificdatainsteadof industrynationalaverages. Several a nd resultsof otherways toestimatethe interruptioncosts; an tions give survey results admittedlyincompletelist is [21], (129], [130], [131], [132], [216]. 2.7 COMPARISON OF OBSERVATION AND RELIABILITY EVALUATION Despite all the reliability analysis toolsavailable, simple past-performancerecords remain the main sourceof information on systemperformance.This does not imply that reliability analysis has no value. To the contrary, analysistechniquescan obtain results much fasterandwith a higher degreeo f accuracythanpastperformancerecords. This holds especially forindividual sites. For the evaluationof operationalreserve, past-performanceis simply not available.Stochasticprediction techniquesare the only option here. However,comparisonbetweenstochasticprediction techniquesand pastperformancemeasuresis a highlyundervaluedarea. Very little work has been done on this often with thejustification that it is not possible. Some kind of verification of stochasticprediction techniquesremains needed, especially asmany engineersremain, rightly or wrongly, skepticalabout the outcome of reliability evaluations.The emphasison past-performance recordsis, in the author's view, also determinedby the skepticism toward stochasticprediction techniques. A number of ways of comparingobservationsand the resultsof reliability evaluation are given in the following list: • Apply stochasticprediction techniquesto a systemthat has not changedtoo much over alongerperiod,andfor which dataare availableon thenumberanddurationsof supply interruptionsover this period. As the transmissionnetworks in most industrializedcountrieshave remainedmore or less the same over the last 10 years or so, such a verification techniquecould be used here. • Use a largenumberof observationpoints,e.g., allurbandistribution networks within one utility. Somefurther selection might be needed to get a homogeneous group of systems. Applystochasticprediction techniquesto a typical observationresultsof configurationand comparethe results with the average all existing networks.This verification techniqueis suitablefor level III (distribution) reliability studies. • Use acommondataset.Choosea system for whichinterruptiondataas well as componentfailure dataare known over a numberof years. Use the observed failure rates asinput for the stochasticprediction, thus eliminating the data uncertainty.Any differences between observed and predictednumberof interruptionscan becontributedto model limitations. 107 Section 2.8 • ExampleCalculations • Perform detailed analysis of the underlying events of interruptions. Assess whetherthese events orcombinationsof events arepart of the stochasticprediction model. Thistechniquemight be somewhattrivial for distribution systems, but itappearsespecially useful fortransmissionand generationsystems where onlymultiple events lead tointerruptions. 2.8 EXAMPLE CALCULATIONS 2.8.1 A Primary Selective Supply Consideran industrial customerwith a so-calledprimary selective supply, as shown in Fig. 2.43.P rimary selectivesuppliesand other ways of improving the reliability are discussed in detail in C hapter7. 'A,r At,r, Figure2.43 Example ofreliability calculation:primaryselectivesupply. For this example we use the following c omponentdata: • A = 5 year-I, failure rate of each of the two public supplies. • r = 0.00025 years= 2 hoursand 11minutes,averagerepair time of the public supply. • At = 0.02year-I, transformerfailure rate. • r t = 0.0114 year = 100 hours,transformerrepair time. • Ps = 30/0, transferswitch failure probability. The frequencyof interruptionsdue to overlappingoutagesis obtainedfrom the equation for the failure rateof two parallel components(2.39): Ap = 2rA2 = 2 x 0.00025X 52 = 0.0125interruptionsper year (2.130) The averageduration of an interruption is the equivalentrepair time of the parallel connectionas obtainedfrom (2.41): rp = r 2" = 0.000125 years= 1.1hours (2.131) In otherwords, the secondof two overlappingoutagesstartson averagein the middle of the first outage.From the interruption rate and theinterruption duration, we can obtain the unavailability due to overlappingoutages: Qp = Aprp = 1.56 x 10-6 = 0.014hoursper year (2.132) 108 Chapter2 • Long Interruptionsand Reliability Evaluation In a primary selective supply, atransformeroutagecan also lead to aninterruption. The transformeroutagerate (0.02year-I) is of the sameorderof magnitudeas the outagerate due to overlappingoutagesin the supply. Theduration of transformer outagesis much longer. Theunavailability due to transformeroutagesis Q, = A,r, = 2.28 x 10-4 = 2 hoursper year (2.133) When very longinterruptionsare aconcern,a secondtransformershould be placed in parallelwith the existing one and the switching shouldbe performedon secondaryside. This leads to the so-called secondaryselective supply. Theinterruptionfrequency due to overlappingtransformeroutagesis very small: A,p = 2r tA; = 9.1 x 10-6 interruptionsper year (2.134) Apart from overlappingsupply outagesand transformerfailures, interruptionscan be due to a failureof both supplies at the same time and due to a failure of the transfer switch. Failure of both supplies at the same time mainly is due to outagesat a higher voltage level, either medium voltage distribution or transmission,dependingon the supply configuration.Interruption rates associatedwith this vary significantly, with a typical range between 0.05 and 0.5 interruptionsper year. Aseparatestudy is needed for eachsupply configuration,or alternativelyinformation needs to beobtainedfrom the utility. The probability that the transferswitch fails was given as P.f = 3%, which meansthat the switch willnot transferthe loadcorrectlyin 3% of the cases for which it is supposedto do so. The frequency o f cases in which thetransferswitch issupposedto transfer the load is equal to the outagerate of one of the supplies. Theinterruption frequency due totransferswitch failure is thus, Ps x As = 0.15 per year (2.135) We seethat the transferswitch is apparentlya weak part in the supply. Toobtain a reliable supplyit is thus essential tochoosea reliabletransferswitch. Alsomaintenance on the transferswitch plays animportantrole. 2.8.2 Adverse Weather Consideragainthe primary selective supply in Fig. 2.43. We considerthe factthat the failure rate is not constantduring the year.Most overheadline outagesare due to adverseweatherlike snow, storm, or lightning. Overheadline outagesare much more likely during adverseweatherthan during normal weather.The failure rate as a function of time will look like in Fig. 2.44: the failure rate is low mostof the year,but high during a numberof short periodsof adverseweather. The adverseweatherperiodsare not fixed but stochasticin time as well. AMonte Carlo simulationwould be anappropriatetool, if sufficient dataandmodel detailswere available.To enablea simplified analysis, weconsidera two-statemodel, asshownin Fig. 2.45. The failurerate during adverseweatheris Al and during normal weatherA2' The adverseweatheris presentduring a fraction T} of the time and normal weather during a fraction T2• The average failure rate A is obtainedfrom A = Al T I + A2T2 (2.136) For both statesan interruption frequency can bedetermined,after which the annual of these two.Supposeas anexamplethat 75% of interruptionfrequency is the average supplyoutagesare due to adverse weatherwhich takesplaceduring 100hoursper year. The failure ratesduring adverseandnormalweatherare, respectively:Al = 329 per year 109 Section 2.8 • ExampleCalculations ~ Adverseweather ! Figure 2.44 Failure rate as a function of time-normaland adverse weather. Normalweather Adverse weather Averagefailure rate Normalweather A21---------------' Figure 2.45Two-statemodel with normal and adverse weather. 1 year andx, = 1.25per year. The averagefailure rateis the sameas in thepreviousexample: A = 5 per year. The repair time is also likely to beaffectedby the adverseweather.We usethe following repairtimes: '1 2.59 hour (during adverseweather)and '2 = 1 hour (during normal weather)leadingto the sameaveragerepair time as before (r=2 hours 11 min). = _ At T ,] + A2 T2'2 , = -t- - - - A]T] +A2T2 (2.137) The normal weatherinterruption rate is found by using the sameexpressionfor the parallelconnectionas before,with the exceptionthat failure rateand repairtime during normal weatherare used insteadof the averagevalues. Ap2 == 2'2A~ = 0.0003566per year (2.138) Normal weatheris presentduring a fraction T2 = ~~~~ of the year, which gives for the expectednumberof interruptionsper year due to normal weather: T2A p2 == 0.0003525interruptionsper year (2.139) The adverseweatherinterruption rate is ApI = 2,)AI = 64 per year (2.140) 110 Chapter2 • Long Interruptionsand Reliability Evaluation This is a very high value, but normal weatheris only presentduring a fraction T I = 8170~O = 0.0114of the year. The contribution of adverseweatherto the annualinterruption frequencyis TIApl = 0.73 interruptionsper year (2.141) The annualinterruptionfrequencyis thereforevery much affectedby adverseweather. Note the large differencewith the interruption frequencyfound before by assuminga constantfailure rate (0.0125 per year). It is clear that the influenceof adverseweather cannotbe neglectedin reliability evaluationstudieswith parallelconnections.F or series connectionsthe interruption rate is the sum of the componentfailure rates and the averageinterruption rate is the sum of the averagecomponentfailure rates. Only for parallel connectionsdo we need to explicitly consideradverseweather. 2.8.3 Parallel Components Considera systemconsistingof n identical componentsin parallel. Eachcomponent has an outagerate A and an averagerepair time r. The interruption rate of the systemcan be calculatedfrom expression(2.44), resulting in (Ar)" Al = n - (2.142) r Apart from interruptionsdue to theseoverlappingoutages,the systemcan be interruptedwhen a failure in onecomponentl eadsto the outageof all components.O necan think of failure of the protection, tripping of equipmenton the voltage sag or on anothertransient, or transient instability. Supposethat there is a probability ex that the underlyingfailure of a componentoutageleadsto a systeminterruption.For an ncomponentsystemwith a componentoutagerate A, this gives an additional interruption frequencyof A2 = an): (2.143) The total numberof interruptionsis given by the following expression: Ato l = A) +)...2 = an): (Ar)n + n -r - (2.144) For mostcomponents>..r « ] so that the secondterm reducesvery fast for increasingn, while the first term increaseslinearly with the numberof parallelcomponents.T he first term will rather quickly start to dominateafter which an increaseof the number of parallel componentsonly decreasesthe reliability. Assume the following component data: A 1 per year, r = 0.001 year,ex = 10/0. The resultinginterruptionratesaregiven in Table2.12. Wenotethe somewhats urprisingresult that threecomponentsin parallel is less reliable than two componentsin parallel. = TABLE 2.12 Rate Influenceof Numberof ParallelComponentson Interruption n Individual Overlapping Outages Total Interruption Frequency 1 2 3 0.0 I per year 0.02 per year 0.03 per year I per year 2 x 10-3 per year 3 x 10-6 per year 1.0I per year 0.022 per year 0.030 per year 111 Section 2.8 • ExampleCalculations To justify a three-component model,the interruptionfrequencyfor n = 3 needsto be lessthan for n = 2, thus (Ar)3 (Ar)2 3aA+ 3 - - < 2aA+ 2 - r r (2.145) resulting in the following upper bound for the probability that a componentoutage leadsdirectly to a systemoutage a < 2AY - 3(Ar)2 (2.146) For the previousexamplethis givesa < 0.002. Thus,a three-componentsystemis only justified if the protectionof the componentis very reliable,the risk of transientinstability is low, etc. 2.8.4 Two-Component Model with Aging and Maintenance To assess the effect of aging and maintenanceon a parallel connection,we consider two componentswith a time-dependento utagerate: (2.147) with t the time since lastm aintenance.F or maintenanceperformedevery 4 years,the averageoutagerate is -=4I[ A 0 A(t)dt = 0.16 outagesper year (2.148) We will calculatethe interruption frequency of the parallel connectionof these two components.We assumethat both repair time r and maintenanceduration m are on average100 hours. For eachof the modelsto be discussedwe will calculateboth the interruption rate due to overlappingoutages(AQo ) , and the interruption rate due to outageduring maintenance(Aom)' Average FailureRate-OverlappingOutages. Using the averagefailure rate for the two components,we can calculatethe interruption rate of the parallel connection due to overlappingoutages: 2 Aoo = X 2r = 5.84 x 10-4 interruptionsper year (2.149) The expectednumber of interruptions due to overlapping outagesduring a 4-year period is equal to 2.34 x 10-3 • AverageFailure Rate-OutageDuring Maintenance. When one componentis being maintained, an outage of the other componentwill lead to an interruption. One of the two componentsis in scheduledoutageduring a period 2m every 4 years. An outage during this period leads to an interruption. The expected number of outagesduring maintenanceduring a 4-year period is thus, 4Aom = Zm):- = 3.65x 10-3 outagesper4 years (2.150) Maintenance Every FourYears-OverlappingOutages. When the failure rate of the componentsis time dependent,it is still possibleto determinethe interruption 112 Chapter2 • Long Interruptionsand Reliability Evaluation rate due to overlappingoutages.The only difference with the previous case isthat the outageratesare timedependenta nd thereforethe interruption rate as well: Aoo( l ) = A(I)22r = 2.28 x 10- 6 16 interruptionsper year (2.151) 3 The averageinterruption frequency is 1.334 x 10- interruptions per year, and the maximuminterruptionfrequencyGustbeforemaintenance)is 9.34 x 10- 3 interruptions per year.The expectednumberof interruptionsdue to overlappingoutages,during a 4-yearperiod, is equal to 5.34 x 10-3 • Maintenance Every FourYears-OutageDuring Maintenance. Normally maintenancewill not be performed on both componentsat the same timebecausethat would lead to an interruption. Maintenanceis performed first on one component and then on theother. During maintenanceon the secondcomponentthe first one is as-good-as-new,has a failure rate close to zero,and the risk of an outagecan be neglected.The situation is completely different for maintenanceon the first component, becausethe other componenthas its highest failure rate. The probability that the secondcomponentwill fail while the first one is beingmaintainedis 4A om = mA(4) = 8170~0 x 0.64 = 7.31 x 10-3 interruptionsper maintenanceinterval (2.152) Maintenance Every TwoYears-OverlappingOutages. Above it was assumed that maintenanceon the two componentsis done immediately after each other. An alternative is to spread the maintenanceover time; that is, by performing maintenanceevery 2 years and each time only on one component.Supposethat maintenance has been performed on component 1 at t = 0 and on component 2 at t = -2. The componentfailure ratesbecome = 0.0113 (2.153) A2(1) = 0.01(1+ 2)3 (2.154) A) (t) The interruption rate due to overlappingoutagesis Aoo(/) = A)(t)A2(t)2r = 2.28 x 10-6t3(t + 2)3 interruptionsper year (2.155) Note that this expressionis valid betweent = 0 and t = 2 after which component1 and component2 switch roles. Theaverageinterruption rate over this 2-yearperiod is -. = ~ 1 2 Ap(t)dt= 2.18 x 10- interruptionsper year 4 (2.156) The expectednumber of interruptionsdue to overlappingoutages,during a 4-year period, is equal to 0.87 x 10-3. Maintenance Every TwoYears-OutageDuring Maintenance. Failure during maintenancecan happenfor eachof the two components.W hen maintenanceis performed on one component,the other componenthas an"age" of 2 years; thus, its failure rate is 0.08 per year.The expectednumberof outagesof the parallel component during maintenanceon the other componentis equal to mA(2) = 8170600 x 0.08 = 0.913 x 10-3 interruptionsper maintenance (2.157) 113 Section 2.8 • ExampleCalculations Such asituation occurs twiceduring a 4-year period, sothat the expectednumberof interruptionsdue to outageduring maintenance,over a 4-yearperiod, is 1.83 x 10-3. Overview. The results of thevarious models aresummarizedin Table 2.13. We seethat the aging/maintenancemodel influences theinterruption frequency over almost afactor of 10. Also notethat the numberof interruptionsdue to outages during maintenanceis, for eachof the models, higherthan the numberof interruptions due to overlappingoutages.Further optimization studies would be needed to assess if the total interruption rate can bebrought down. An obvious choice is to reduce the duration of maintenance,as the number of interruptionsdue to outagesduring maintenanceis directly proportional to the duration of maintenance.One should take a certain care with that, as thequality of the maintenancemight also become less. In the abovecalculationsit has been assumed t hat the outagerate is brought back to zero aftermaintenance,and that the outagerate of the parallelc omponentis not increasedduring the maintenance. Without any optimizationstudy, it is obvious, however, that maintenanceshould be scheduled as much as possible during periodswith low interruptioncosts. TABLE2.13 Influenceof Aging and MaintenanceModel on Interruption Rate Interruptionsdue to overlappingoutages Interruptionsdue to failure during maintenance ConstantFailure Rate MaintenanceEvery 4 Years MaintenanceEvery 2 Years 2.34 x 10-3 per 4 years 5.34 x 10-3 per 4 years 0.85 x 10-3 per 4 years 3.65 x 10-3 per 4 years 7.31 x 10-3 per 4 years 1.83X 1-0-3 per 4 years Short Interruptions 3.1 INTRODUCTION A short interruptionhas the same causes as a long interruption: fault clearing by the protection,incorrectprotectionintervention,etc. When thesupplyis restoredautomatically, the resulting event is called short a interruption. Long interruptionsand very long interruptionsresult when the supply is restoredmanually.Automatic restoration can take place by reclosing the circuit breakerwhich cleared the fault or by switching to a healthy supply. The former takes place mainlyoverhead in distributionnetworks,the latter is a typical solution in industrial systems. Shortinterruptionsin the public supply are due to a ttemptsby the utility to limit the duration of interruptions.We sawalreadyin Section 2.3that the duration of an interruptionis an importantaspectof distribution and transmissionsystem design.By using automaticreclosing theduration of an interruption can bebrought back from typically about 1 hour, to typically lessthan 1 minute. For many yearsinterruptions shorterthan severalminuteswerenot consideredas a causeof concernto most customers. Recently this has changed: more and more equipmentis sensitive to veryshort duration events, and more and more customers(domestic as well asindustrial) view short interruptionsas a seriousimperfectionof the supply. This ispart of the trends mentionedin Section 1.1 for the increased interestin power quality in general.Short interruptionsalso occur inindustrial power systems due to the operationof automatic transferswitches. We discuss this in Chapter7. 3.2 TERMINOLOGY There is some serious confusionaboutterminologyon interruptionsof different duration. Terms likeshort interruptions,momentaryinterruptions, temporary interruptions, instantaneousinterruptions, and transient outagesare all used with more or less the same meaning. The definition of short interruptionsused for thischapteris not based onduration but on themethodof restoringthe supply. Thischapter(short 115 116 Chapter3 • Short Interruptions interruptions)discussesautomatic restoration,where Chapter2 (long interruptions) discussesmanualrestoration. Below, an overview is givenof the various terms and definitions used in the EuropeanstandardEN 50160and in three IEEE standards.The definitions used in EN 50160 areidentical to the IEC definitions. • EN 50160 - Long interruption: longer than three minutes. - Short interruption: up to threeminutes. • IEEE Std.1159-1995 This standardis consideredby many as providing the basic power quality definitions. It distinguishesbetween momentary, sustained,and temporary interruptions. Note.the overlap between sustainedand temporary interruptions. - Momentaryinterruption: between0.5 cyclesand 3 seconds. - Sustainedinterruption: longer than 3 seconds. - Temporaryinterruption: between3 secondsand I minute. • IEEE Std.1250-1995 This standardwas publishedat about the same time asIEEE Std.1159-1995, but it usessomewhatdifferent definitions. The differenceis especiallystriking for interruptions. - Instantaneousinterruption: between0.5 and 30 cycles(half a second). - Momentaryinterruption: between30 cyclesand 2 seconds. - Temporaryinterruption: between2 secondsto 2 minutes. - Sustainedinterruption: longer than 2 minutes. • IEEE Std.859-1987 This somewhatolder standarddocumentgives definitions for terms relatedto power system reliability. A distinction is made between different types of outagesbased on theduration of the outage. This standarddoes not give specific timerangesbut uses therestorationmethodto distinguishthe different types. Although outages and interruptions are different phenomena(see Section2.1.3) they arerelatedclosely enoughto comparethe terminology. - Transientoutagesare restoredautomatically. - Temporaryoutagesare restoredby manualswitching. - Permanentoutagesare restoredthrough repair or replacement. 3.3 ORIGIN OF SHORT INTERRUPTIONS 3.3.1 Basic Principle Figure 3.1 shows anexampleof an overheaddistribution network. Each feeder consistsof a main feederand a numberof lateral conductors.Most faults onoverhead lines aretransient:they requireoperationof the protection,but do not causepermanent damageto the system. Atypical causeof a transientfault is a lightning stroke to an 117 Section 3.3 • Originof Short Interruptions overheadline. The lightning stroke injects a very highcurrentinto the line causinga very fast rising voltage. The lightning current varies between 2and 200 kA in peak value. Thetypical lightning currenthas apeakvalue of [peak = 20 kA which isreached within IlJ,s after its initiation. If the wave impedanceZ",ave of the line is 2000, the voltage cantheoreticallyreach a valueof Vpeak Z"'ave = -2-Ipeak = 1000 x 20 kA = 2 MV (3.1) The voltagewill never reach such a value in reality (with the possible exceptionof transmissionsystems withoperatingvoltagesof 400 kV or higher), because flashover a to groundor betweentwo phaseswill resultlong before thevoltagereachessuch a high value. The result is anarcing fault betweenone phaseand ground or between two or morephaseswith or without ground.Soonafter the protectionremoves thefaultedline from the system, the arc disappears.A utomatic reclosingwill restorethe supplywithout any permanentd amageto the system. Also, smallerobjectscausinga temporarypath to groundwill only cause atransient shortcircuit. The object(e.g., a smallb ranchfallen from a tree) willeitherdrop to the ground or evaporatedue to the highcurrentduring the fault, leaving only an arc which disappearsagainsoonafter the protectionintervenes.The durationof an interruption due to a transient fault can thus be enormouslyreduced by automatically restoringthe supply after an interruption. In caseof a fault somewhereon the feeder, the circuit breakeropensinstantaneouslyand closesagainafter a "reclosinginterval" or "dead time" ranging from lessthan one second up to several minutes.There is of coursea risk that the fault wasnot a transientone but permanent.In that case the protectionwill againnotice a largeovercurrentafter reclosureleadingto a secondtrip signal.Often the reclosergives the fault a second chanceat extinguishing,by meansof a longer tripping time and/ora longer reclosinginterval. 3.3.2 Fus.Saving A practiceassociatedwith reclosing and short interruptionsis "fuse saving." In Fig. 3.1 thelateralsaway from themain feeder areprotectedby meansof expulsion fuses. These are slow fuses which will not trigger when atransientfault is clearedby the main breaker/recloser.Thus, a transientfault will be clearedby the recloserand the supply will be automaticallyrestored. A permanentfault can also beclearedby the main breaker,but thatwould lead to a long interruptionfor all customersfed from this feeder.Instead,a permanentfault is /Lateral Recloser J Distribution substation Figure 3.1 Overheaddistribution network with fusesand reclosers. 2 tt8 Chapter3 • Short Interruptions cleared by anexpulsionfuse. To achieve this, the recloser has two settings:instanan taneoustrip and a delayed trip. Theprotectioncoordinationshould be suchthat the instantaneoustrip is faster than the expulsionfuse and the delayed trip slower, for all possible faultcurrents. From the abovedescriptionwe canconcludethat the following trade-offhas been made: ashort interruption for all customers(fed from this feeder)insteadof a long interruption for some customers.The alternativewould be more longinterruptions; however, not everyshort interruptionwould become a longinterruption. 3.3.3 Voltage Magnitude Events due to Reclosing The combination of reclosing and fuse saving, as decribed above, leads to different voltage magnitude events for different customers. Figure 3.2 shows the events due to one reclosing action as experienced by caustomeron the faulted feeder (indicatedby "1" in Fig. 3.1) and by acustomeron anotherfeeder fed from the same substationbus (indicated by "2"). In Fig. 3.2, A is thefault-clearingtime and B the reclosing interval. The customeron the faulted feeder (solid line) willexperiencea decreasein voltage during the fault, similar in causeand magnitudeto a voltagesag. The difference between the two customersis in the effectof the fault clearing.For the customeron the nonfaulted feeder, the voltage recovers to its pre-eventvalue. The For the customeron the faulted feeder, customerwill only experience a voltage sag. the voltage drops to zero. The customeron a neighboringfeeder(dashedline) will see avoltagesag with a durationequal to the fault-clearingtime. The momentthe recloseropens,the voltage recovers. If the fault is stillpresentat the first reclosure, the c ustomeron thenonfaulted feeder will experience a second voltage sag. Customerson thefaulted feeder will experience a secondshort interruption or a long interruption. Figure 3.3 [11] shows anactual recordingof a short interruption.The top figure correspondsto the dashedline in Fig. 3.2 (customeron a nonfaulted feeder). The bottom figure is for a customeron the faulted feeder (solid line in Fig. 3.2). The fault-clearing time is about two cycles, the dead timea bout two seconds. The first top figure shows avoltage sag to reclosureis not successful, the second one is. The about75% of two-cycleduration,the bottomfigure avoltagereductionto 50% for two abouttwo seconds. cycles followed by zero voltage for 1 Voltage sag f---- r ••••••••••••••••••••••••••••••••••••••••••• 1 ~ Short interruption -------. B +----..~ A Time Figure 3.2 RMS voltageduring a recJosure sequence on the faulted feeder (solid line) and on thenonfaultedfeeder(dashedline). A = fault-clearingtime; 8 = reclosing interval. 119 Section 3.3 • Originof Short Interruptions April 29, 1994at 22:14:20PQNodelocaltrigger 1472 PhaseB voltage RMSvariation E 120~ i :ft! I 60 0- ~[C -0.05-0-'-.1--0...... 15 0.2 Time(seconds) L ' - 0.25 I 0.3 Duration 0.050 s Min 65.80 Ave 90.10 Max 100.5 150 lIOO '~ 50 f 0 ~ -50 ~ -1000 25 50 75 100 125 150 175 200 Time(milliseconds) (a) Uplinemonitoringlocation April 29, 1994at 22:14:20PQNodelocaltrigger 2592 PhaseB voltage RMSvariation J lJ Jil_.. . ._..,.. . .~ : ~100 120[ o I 234 5 Duration 4.983 s Min 2.257 Ave 8.712 Max 100.2 6 Time(seconds) J_;; Figure 3.3 Recorded rms voltage during a short interruption. (Reproduced from Dugan et al. [II].) 00 0 I 25 50 75 100 125 150 175 200 Time(milliseconds) (b) Downlinemonitoringlocation When comparingFig. 3.2 and Fig. 3.3, note t hat the horizontalaxis of Fig. 3.2 is not to scale, B is much larger than A. This is the typicalsituation. The fault-clearing time (A) is only a few cycles, whereas the reclosing time (B) can be up to several minutes. Anotherexample of theinitiation of a shortinterruptionis shown in Fig. 3.4 [3]. We seethat the voltagemagnitudeinitially drops to about 25% of nominal and to almost zero after three cycles. The spikes in the voltage are due to the arc becoming instablearoundthe currentzero-crossing.Apparentlythe arc gets more stable after two cycles. 3.3.4 Voltage During the Interruption The momentthe circuit breakerin Fig. 3.1 opens, the feeder and the load fed from it are no longer supplied. The effect of this normally is that the voltagedrops to zero very fast. There are, however, situationsin which the voltagedrops to zero relatively slow, or even remains at nonzerovalue. a Thelatter would strictly speakingnot be an 120 Chapter3 • Short Interruptions 150 100 ,-... 50 ~ 0 e l! ~ -50 -100 -150 0 25 50 75 100 125 Time inmilliseconds 150 175 200 Figure 3.4 Recorded voltage during the initiation of a short interruption. (Reproduced from IEEE Std. I I 59 [3].) interruption,but the origin is similar tothat of an interruptionso that a shortdescription of the phenomenonis appropriatehere. • Inductionmotor load is able tomaintainsome voltage in the system forshort a time. This contribution is typically rather small because themotors have already been feeding into ashort circuit for a few cycles; thus,p art of the rotor field of the inductionmotorswill begone already.M ost inductionmotors will thus only give a small voltagecontributionand only for a few cycles. • Synchronousmotorsmaintain their field even when the supply voltage disappears. They will be able tom aintainsome system voltage until their load has come to astandstill, which can take several seconds. If there is a significant amountof synchronousmotor load present,its fault contributioncould make fault extinguishingdifficult. Typically synchronousmotors will be tripped by their undervoltageprotectionafter about 1 second, after which they no longer contributeto the feeder voltage. • Synchronousand inductiongeneratorsconnectedto the feeder (e.g., wind turbines orcombined-heat-and-power installations)arecapableof maintainingthe feeder voltage at n aonzerovalue evenduringa longinterruption.This could be a potential problem when largeamountsof generationare connectedto the feeder. This so-calledembedded generation is often not equippedwith any voltage or frequencycontrol (relying on the grid tomaintainvoltageand current within limits) sothat an islandingsituationcan occurin which voltage and frequency deviate significantly from their nominal values. Especially overvoltage andoverfrequencycan lead to serious damage. preventsuch To asituation, most embeddedgenerationis equippedwith a loss-of-gridprotectionthat disconnectsthe generatorwhen anunusualvoltage or frequency is detected. All this assumesthat the short-circuitfault is no longerpresenton the feeder. As long as the fault ispresent,all above-mentionedmachinesfeedinto the fault sothat the feeder voltage remains low. The fault-current contribution makes that the arc is less likely to extinguish, but after extinguishing of the arc there will be a chance of a remaining voltage on the feeder. For interruptionsdue toincorrectprotectioninterventionthere is noshort-circuit fault presenton the feeder and themachinesconnectedto the feeder may cause a 121 Section 3.4 • Monitoring of Short Interruptions temporaryor permanentnonzerovoltage. Also thecontribution of induction motors will be larger. 3.4 MONITORING OF SHORT INTERRUPTIONS As shortinterruptionsare due toautomaticswitching actions, their recording requires automaticmonitoring equipment.Unlike long interruptions,a short interruptioncan occur without anybodynoticing it. That is one of the reasons why utilities do not yet collect and publishdataon shortinterruptionson a routine basis. One of the problems in collecting thisdata on a routine basis isthat some kind ofmonitoring equipment surveys have been performedto obtain needs to be installed on all feeders.numberof A statisticalinformation aboutvoltagemagnitudevariationsand events. With those surveys,monitors were installed at anumberof nodes spreadthrough the system. The surveys will be discussed in more detail Chapter6. in As with long interruptions, interruption frequency andduration of interruption are normally presented as the outcome of the survey. Again like with long interruptionsmuch moredata analysis is possible, e.g.,interruptionfrequency versus time of day or time of year, distributions for the time between events, variation amongcustomers. 3.4.1 Example of Survey Results Figures 3.5, 3.6, and 3.7 show some results of analysis ofdataobtainedby the a large North American survey [68]. Figure 3.5 gives theinterruption frequency as a function of theinterruptionduration. Each vertical bar gives the average numberof interruptionsper year, with aduration in the given interval. The average numberof interruptionshas beenobtainedas follows: 4 j 3.5 >. 3 ~ 2.5 ! 5 ~ 8 ',= tt= ~ B ~ 2 1.5 I 0.5 - o O-Ie - - 2-3c -- . 4-5c 6-IOc 20e-0.5s 1-2s Durationof interruption • 5-108 II 30-60s 120s- Figure 3.5 Interruption frequency (number of interruptions per year) as a function of interruption duration. (After data obtained from Dorr [68].) 122 Chapter3 • Short Interruptions (3.2) where Nfl') is the numberof events in ranger observedby monitor i during a monitoring the resulting averageas plotted in Fig. 3.5. We see from Fig. 3.5 interval T;, and that the typical eventhas aduration between 1and 30 seconds.Eventsshorterthan six cycles (100 ms) are very unlikely. These "very short interruptions"are most likely due to short-circuit faults close to themonitor position. One should realize that in this survey anevent is recordedas an interruption if the rms voltage somewhereduring the eventdrops below 100~ of nominal. Note also that the horizontal scale is nonhomogeneous.F rom the data shown in Fig. 3.5 one cancalculate the probability of all densityfunction of the interruption duration by dividing each value by the sum values: FIr) N(r) f(r) = I:Fl k ) (3.3) (k) The probability distribution function of the interruptiondurationcan beobtained by addingthe valuesof the density function up to acertainduration. F(t) = I:!(r) (3.4) (")<1 The resultingprobability distribution function is presentedin Fig. 3.6. This curve gives the fraction of interruptionswith a durationnot exceeding theindicatedvalue. We see that 10% of interruptionslasts lessthan 20 cycles,and 80% of interruptionslessthan 2 minutes(thus 20% morethan2 minutes).From an equipmentpoint of view the reverse dataare of more interest,the fraction of interruptions(or the absolutenumber)lasting longer than a given duration. This will give information about the numberof times a device will trip or (for a givenmaximum trip frequency)about the immunity requirementsof the device.Figure3.7 plots the numberof interruptionsper yearlastinglonger than the indicatedvalue. Apart from a small shift (due to the discretizationof the data) 1.2,..------------------..-, s= o .~ .&J 0.8 'Een :.a ~0.6 :.0 .se 0.4 c.. 0.2 O................ -==~:::...J----'-___L.---L---Jl.._._.L...._.J..._...L._....L_..J......_.J Ic 3e 5e JOe 0.5s 2s Duration lOs 60s info Figure 3.6 Probability distribution function of interruption duration. (From the data in Fig. 3.5.) 123 Section 3.4 • Monitoring of Short Interruptions 18,..--------------------, 16 ~ r------ __ 14 g.~ 12 ~ 10 5 .~ j 8 6 4 2 Figure 3.7 Number of interruptions lasting longer than the indicated value. (From the data in Fig. 3.5.) OL--..a...-....&..-_'___....I----£--L..---L.-L----.I~J..__..&.___'___~_.I_.-L..___I Oc 2c 4c 6c 20c Is 5s 30s 120s Durationof interruption and amultiplication factor equal to thetotal numberof interruptions,the curve is the complementof the curve in Fig. 3.6. We can conclude from the figure that equipment which trips for aninterruption of 20 cycles will trip on average 14 times per year. To limit the equipmenttrip frequency to four per year, the equipmentshould be able to tolerateinterruptionsup to 30 seconds induration. 3.4.2 Difference between Medium- and Low-Yoltage Systems The numberof short interruptionshas beenobtainedby various power quality surveys.Comparisonof the numbersobtainedby each survey gives information about the average voltage quality in the variousareas. Acomparisonbetween thenumberof short interruptionscountedat various places in the system can teach us how the interruptions "propagate"in the system. Such caomparisonis madein Table 3.1 for two large North American surveys: theEPRI survey and theNPL survey [54]. TheEPRI surveymonitoredboth distribution substationsand distribution feeders. From Table 3.1 we seethat the overall trend is for thenumberof shortinterruptions to increase when moving from the source to the load. This understandable is as there are more possibletripping points the further one movestowards the load. Especially interruptions lasting several seconds and longer mainly originate in the low-voltage system.F or interruptionslessthan one second induration,the frequency remainsaboutthe same, which makes us concludethat they probablyoriginatein the distributionsubstationor even higher up in the system. The large numberof very short TABLE 3.1 Interruption Frequency (number of events per year) for Three Points in the U.S. Distribution System Duration Survey 1-6c 6-IOc lo-20c EPRI substation EPRI feeder NPL low voltage 0.2 1.6 0.2 0.1 0.1 0.3 0.4 0.2 0.8 0.7 0.8 Source: After data obtained from[54]. 20-30c 0.6 0.5-1 sec 0.5 0.5 1.2 1-2 sec 2-10 sec> 10 sec 0.9 1.1 1.5 1.1 2.3 3.3 1.3 1.7 4.2 124 Chapter3 • Short Interruptions TABLE 3.2 Interruption Frequency(per year) forPrimary and Secondary Systems inCanada Duration Survey CEA primary side CEA secondaryside 1-6c 6--IOc 10-20c 2Q-30c 0.5-1 sec 1.9 3.7 0.0 0.0 0.1 0.0 0.0 0.0 0.4 0.2 1-2 sec 2-10 sec 0.0 0.5 0.0 0.5 > 10 sec 0.7 2.1 Source: After data obtainedfrom [69]. TABLE 3.3 Interruption Frequency(per year) forDistribution and Low-voltageSystems inNorway Duration Survey 0.01-0.1 sec 0.1-0.5sec 0.5-1.0sec EFI distribution EFI low-voltage 1.5 1.1 0.0 0.7 0.0 0.0 1-3 sec 0.0 0.7 3-20 sec > 20 sec 0.5 0.9 5.2 5.9 Source: After data obtainedfrom [67]. interruptions(lessthan six cycles) ondistribution feeders ishard to explain, especially as they donot show up in the low-voltagedata. Similar conclusionscan bedrawn from the CEA survey [69] and from the E FI survey [67], some results of which are shown in Tables 3.2 and 3.3. againsee We a larger number of interruptions,mainly of 1 second and longer, forlow-voltage than for medium-voltagesystems. Both theCanadian(CEA) and theNorwegian (EFI) data show a considerablenumber of very short interruptions,for which no explanation has been found yet. 3.4.3 Multiple Events A direct consequenceo f reclosingactionsis that a customermay experience two or more events within as hortinterval. When theshort-circuitfault is still presentupon the first reclosure, thecustomersfed from the faulted feeder will experience a second event. This isanother short interruption if a second attempt at reclosing is made. Otherwisethe second event will be a long interruption. A customerfed from a nonfaulted feeder experiences two voltagesags in ashort period of time. For a few years a discussion has been goingaboutwhetherto on countthis as one event or as multiple events [20]. The most recentpublications of North American surveysconsidera l-minute or 5-minute window. If two or more events take place within such a window, they are c ountedas one event. The severity of the multiple event (i.e., magnitudeand duration)is the severity of the most severe single event within the window. Some examples of the working of a "five-minute filter" are shown in Fig. 3.8. Using such a"filter" is suitablefor assessment of the numberof equipmenttrips, as theequipmentwill trip on the most severe event or not at all. The cumulativeeffect of the events is neglected, but the general impressionis that this effect is small.T his has however not been confirmed hy measurements yet. In some cases it could still be needed to know thetotal event frequency, thus countingall events even if they come very close. Two possibleapplicationsare: (I) componentswhich show acceleratedaging due to shortundervoltageevents; and (2)equipmentwhich only tripsduring a certainfraction 125 Section 3.5 • Influence onEquipment Time i Q ~ Time Time Go) C)O ~ Q Figure3.8 Effect of a"five-minute filter" on the voltage magnitude events. The figures on the left show the recorded rms voltages;the figures on the right show the equivalent event after thefilter. ~ Time Time TABLE3.4 Number of Singleand Multiple Interruptions per Year, NPL Low-Voltage Survey Duration Survey 1-6c 6-IOc 1(}-20c 2(}-30c 0.5-1 sec No filter 0.3 5-min filter 0.2 Percent reduction 33°A. 0.3 0.3 0.8 0.7 12% 0.9 0.8 11% 1.4 1.2 14% 1-2 sec 2-10 sec 1.9 1.5 21% 4.2 3.3 21% > 10 sec 5.7 4.2 26% Source: After data obtained from[54]. of its load cycle. In thelattercase theequipmenthas aprobability to trip duringeachof the three events, and the total probability is of course largerthanthe probability to trip during the most severe event only. The NPL low-voltage datafor short interruptionshave beenpresentedwith and without the above-mentionedfilter in Table 3.4[54]. The three rows give, from top to bottom: the numberof shortinterruptionswhen each event is countedas one event no matter how close it is toanotherevent; thenumberof events when multiple events within a 5-minute interval arecountedas one event; the reductionin numberof events due to theapplicationof this filter. 3.5 INFLUENCE ON EQUIPMENT During a shortinterruptionthe voltage is zero; thus, there is no supply of power at all to the equipment.The temporaryconsequences are that there is no light,that motors 126 Chapter 3 • Short Interruptions slow down, that screensturn blank, etc. All this only lasts for a few seconds, but the of contents consequences can last much longer:disruptionof productionprocesses, loss of computermemory,evacuationof buildings due to fire alarms going off, and sometimes damagewhen the voltage comes back (uncontrolledstarting). For most sensitiveequipment,there is no strictborderbetween a voltage sag and an interruption:an interruptioncan be seen as a severe sag, i.e. one with remaining zero voltage. The effecto f voltage sags onequipmentis discussed in detail inChapter5. Many of the conclusionsin thatchapteralso hold forshortinterruptions.In this section of the load behaviorare pointedout. only some general aspects 3.5.1 Induction Motors The effectof a zero voltage on aninduction motor is simple: themotor slows down. Themechanicaltime constantof an inductionmotor plus its load is in the range of 1 to 10 seconds. With dead times of several seconds,motor the has not yet come to a standstillbut is likely to have slowed down significantly. This reductionin speedof the motorsmight disrupt the industrial process so muchthat the processcontrol trips it. The motor can re-acceleratewhen the voltage comes back, if the system strong is enough.For public distribution systemsre-accelerationis seldom aproblem. Also the settingof the undervoltageprotectionshouldbe suchthat it does not trip before the voltage comes back. This calls forcoordinationbetween a theundervoltage setting of themotor protectionand the reclosureinterval setting on the utility feeder. Induction motors fed via contactorsare disconnectedautomaticallyas the conof the load. tactordropsout. Without countermeasures this would always lead to loss In someindustrial processes the induction motorsare automaticallyreconnectedwhen the voltage comes back: either instantaneouslyor staged (the mostimportant motors first, the rest later). 3.5.2 Synchronous Motors Synchronousmotors can normally not restarton full load. They aretherefore equippedwith undervoltageprotectionto preventstallingwhen the voltage comes back. For synchronousmotors the delay timeof the undervoltageprotectionshould be less than the reclosing interval. Especially for very fast reclosure this can problem.We be a see here asituationwhere aninterruptioncauses a more serious threatto the synchronousmotorsthe faster the voltage comes back. With most otherload thesituationis the other way around: the shorterthe interruption,the less severe it is to the load. 3.5.3 Adjustable-Speed Drives Adjustable-speeddrives are very sensitive to s hort interruptions,and to voltage sags as we will see in C hapter5. They normally trip well within I second, sometimes even within one cycle; thus even the shortestinterruptionwill cause a lossof the load. Some of the moremoderndrives are able toautomaticallyreconnectthe momentthe voltage comes back. But being disconnectedfrom the supply for several seconds will often havedisruptedthe processbehindthe drive so muchthat reconnectiondoes not make much sense anymore. 127 Section 3.6 • Single-Phase Tripping 3.5.4 Electronic Equipment Without countermeasures electronics devices will trip wellwithin the reclosing interval. This leads to theinfamous"blinking-clock syndrome":clocks of video recorders, microwave ovens, and electronicalarmsstart blinking when the supply is interrupted; and they keep on blinking until manuallyreset. An easysolution is to install a small rechargeablebattery inside of the equipment,to power the internal memory during the interruption. problem. But Computersand processcontrol equipmenthave basically the same they require more than a simplebattery. An uninterruptiblepower supply (UPS) is a much-usedsolution. 3.8 SINGLE-PHASE TRIPPING Single-phasetripping is used intransmissionsystems tomaintainsynchronicitybetween both sidesof a line. Single-phasetripping is rarely used indistribution or low-voltage systems.Not only will it requiremore expensiveequipment,but it will also reduce the chanceof a successful reclosure. The fault currentcontinuesto flow via the nonfaulted phases. This reduces the chancethat the fault will extinguishand thus increases the numberof reclosureattemptsand thenumberof long interruptions.But if the reclosure is successful,single-phasetripping has clearadvantagesover three-phasetripping and thereforejustifies being discussed here. We will have a look at the voltages experienced by the customerduring single-phasetripping. A distinction is made between two distinctly different situations,both assuminga single-phase-to-ground fault followed by tripping of the faulted phase. ground (the fault) is • The low-impedancepath between the faulted phase and still presentso that the voltage in the faulted phase remains zero or close to zero. We will call this the"during-fault period." • The fault hasextinguished,the short circuit has now become an o pencircuit because thebreakerin that phase is still open. This we will call the " post-fault period." 3.8.1 Voltage-During-Pault Period The phase-to-neutralvoltages in theduring-fault period are, with a the faulted phase: Va =0 Vb = (-~-~jJ3)E (3.5) V(' = (-~+~jJ3)E with E the magnitudeof the pre-eventvoltage. It has been assumed here that the preevent voltages form a balancedthree-phaseset,andthat the voltage in thefaulted phase is exactly equal to zero. We will in most of the remainderof this book use per unit voltages, with thepre-eventvoltagemagnitudeas base. Inthat case we getE = 1 and (3.5) becomes 128 Chapter3 • Short Interruptions VlI=O Vb =V = c ~ - ~jvS (3.6) _!+!J·vS 2 2 Figure 3.9 shows thephase-to-neutralvoltages as aphasordiagram.In this and subsequentphasordiagramsthe during-eventvoltage isindicatedvia solid lines, the preevent voltage (i.e., thebalancedthree-phasevoltage) viadottedlines, if different from the during-eventvoltage. If single-phasetripping would take place in alow-voltage network, the voltages in Fig. 3.9 would be the voltages experienced bycustomers. the Only one outof three customerswould experience aninterruption. The otherswould not noticeanything. Single-phasetripping would thus reduce then umberof interruption eventsby a factor of three. Va ........................• Figure 3.9 Phase-to-neutralvoltages for single-phase tripping. For tripping taking place onmedium-voltagefeeders, thephase-to-phase voltages are of more importance.Large equipmentfed at medium-voltagelevel is in most cases connectedin delta; small single-phase equipmenttends to beconnectedbetween a phase and neutral but at a lower voltage level fed via delta-starconnectedtransformer.In a both cases theequipmentexperiences the pu value of the phase-to-phase voltage at the medium-voltagelevel. The phase-to-phasevoltages in pu areobtained from the phase-to-neutral voltages as follows: (3.7) The factor .J3 is needed because 1 pu of the line(phase-to-phase) voltage is.J3 times as big as I pu of the phase(phase-to-neutral) voltage. Themultiplication withj results in a rotationover 90° suchthat the axisof symmetryof the disturbanceremainsalongphase a and along the real axis. The transformationin (3.7) will be the basisof a detailed analysisof unbalancedvoltage sags in theforthcomingchapters.When we leave away the prime " weobtain the following expressions for the voltages due to single-phase tripping at the terminalsof delta-connectedequipment: 129 Section 3.6 • Single-PhaseTripping ~ \ .•.. ~~: A Vb / Figure 3.10Phase-to-phase voltages for single-phase tripping. / .../. ,l Va = 1 Vb = _!_!jJ3 Vc = -~+~jJ3 2 6 (3.8) Figure 3.10 again shows the voltages at the equipment terminals in phasordiagramform. Using the definitions given in the variousstandardsthis shouldnot be called ashort interruption but a voltage sag. It would again bring up the discussion betweenconsequence-based terminologyand cause-based terminology.In the first case this event would have to be called a voltage sag, in latter the case it would be ashort interruption. But no matterwhich name is given to the event, it is clearly less severe than the effect ofthree-phasetripping, when all three phase voltages go down to zero. An exception to this might have to be made for inductionmotors.The voltagesduring single-phasetripping contain a large negative sequence voltage component(0.33 pu) which may lead tooverheatingof induction motors. With a negative sequence impedance 5through 10 times as small as the positive sequence impedance,the negative sequencecurrent would become 170through 330% of the rated (positive sequence) current.It is unlikely that inductionmotor load is able towithstandsuch anunbalance for longer than several seconds. Low-voltage customersalso experience the voltages in Fig. 3.10. None of the customersexperiences a zero voltage, but two-thirds of the customersexperience an event with aduring-eventvoltage of 580/0 magnitudewith a change in voltage phaseangle of 30°. 3.8.2 Voltage-Poet-Pault Period When the fault extinguishes, the situation in the faulted phase changes from a short circuit to an open circuit. In many cases a change in voltage occurs, thus the resulting voltage is no longer equal to zero. The voltage in the faulted phasedependson considerthe coupling the typeof load connected. Tocalculatethis voltage we need to between the phases or use the theory of symmetricalcomponents.The latter, which is normally used for the analysis of nonsymmetricalfaults, isdescribedin detail in many reference books. A good and detailed descriptionof the useof symmetricalcomponents for the analysis ofnonsymmetricalfaults is, e.g., given in reference [24], and is not repeatedhere. To analyze an open circuit, the system has to be modeled as seen from the opencircuit point. This results in three equivalentcircuits: for the positive sequence, for the 130 Chapter3 • Short Interruptions ~V:J s, c~V2:J [91V0:J Figure 3.11 Sequencenetworksfor the analysisof single-phaseopen-circuitfaults: positive sequence(top), negativesequence (center),and zerosequence(bottom). negativesequence,a nd for the zero sequence.T hesethree networksare shown in Fig. 3.11: ZSb ZS2' and Zso are positive, negative, and zero-sequenceimpedanceof the source; ZL), 2 L2 , and ZLO are positive, negative,and zero-sequenceimpedanceof the load; 6 V1 , 6 V2 , and 6. Vo are positive, negative,and zero-sequence v oltagedrop' at the s ourcevoltage. Negativeand zeroopen-circuitpoint; and E 1 is the positive-sequence sequencesourcevoltagesare assumedzero, and the load is assumednot to containany sources.Below we again assumeE) = 1. Sequencevoltagesand currentsat the open-circuit point can be calculatedfor different types of open-circuit faults, by connectingthe three sequencenetworks in different ways. For a single-phaseopen circuit, the voltagedifferencein the two nonfaulted phasesis zero and the current in the faulted phaseis zero: 6. Vb =0 (3.9) 6. Vi' = 0 III =0 where a is the faulted (open-circuited)phase.Transformingtheseequationsto symmetrical componentsgives thefollowing set of equations: II + 12 + /0 = 0 = 6.V2 6. VI = 6. Vo (3.10) 6. VI Theseexpressionscorrespondto a connectionof the sequencenetworks,as shown in v oltagedrop at the open-circuitpoint Fig. 3.12. From Fig. 3.12 thepositive-sequence can bewritten as 1 6. VI = 6.V 2 = 6.Vo = 1 + 2 Ll +ZS) + Z LI ZLO and the voltagedrop in the faulted phaseis + Zso ZL2 +2 SI + ZS2 (3.11) 131 Section 3.6 • Single-PhaseTripping Figure 3.12 Connectionof the sequence networksin Fig. 3.11 for asingle-phaseopen circuit. ~ Va 3 = ~ VI + ~ V2 + ~ Vo = 1 + Z Ll + ZSI + ZLl + ZSJ ZLO + ZSO ZL2 (3.12) + ZS2 Normally the load impedance dominates over the source impedance (ZLi» ZSi' i = 0, 1, 2) sothat we can write with goodapproximation: ~Va = Z 3 (3.13) Z 1+~+~ ZLO ZL2 The voltage at the load side of the open phase is V -1- a-I 3 2 Ll +-+ZLO ZL2 which can bewritten as an expressionusing admittancesby introducing YL2 = -Zl, and YLO = -zl, resultingin L2 LO Va = I - 1 (3.14) ZLI hI 3(YL 1 + YL2 + YLO) YLI = -Zl, LI (3.15) From (3.15) the voltage experienced by the load during the interruptioncan be found for different types of load. As can be seen it is the ratio between the sequence impeimpedancedoes have a dancesof the load whichdeterminesthe voltage. The source small influence as the load c urrent will give a voltage drop between the load and the open-circuitpoint. This influence was neglected when going from (3.12) to (3.13). 3.6.2.1 Star-connected Static Load.For star-connectedstatic load, the three sequenceimpedancesare equal: YLI = YL2 = YLO, (3.15) gives (3.16) In other words, this typeof load does not affect the voltage in the openphase. Singlephase,low-voltageload cannormally be representedin this way. 3.6.2.2 Delta-connectedStatic Load. Delta-connectedstatic load is found in medium-voltagepublic distribution networks. The delta-starconnectedtransformer feeding thelow-voltagecustomerscan beconsidereda delta-connectedstatic load, as long as mainly single-phaseload is present. For this kind of load, positive and negative sequence impedancesare equal and the zero-sequenceimpedanceis infinite 132 Chapter3 • Short Interruptions va . -- .....••••••••••·••••• Figure 3.13Phase-to-groundvoltagesduring single-phase reclosure with delta-connected load . .. .. : Figure 3.14Phase-to-phase voltages during single-phase reclosure with delta-connected load. because of the lack of any r eturn path; in admittanceterms, YLI resulting in Va 1 = --2 = YL2 and YLO = 0, (3.17) In high-impedancegrounded or isolated-neutralsystems, the zero-sequence source impedanceis very large or even infinite.F rom the aboveequationsit is easy to prove thatthe resultingvoltagein the open phase is again equal to The phase voltages and the line voltages fordelta-connectedstatic load are shown in Fig. 3.13 and Fig. 3.14, respectively. -!. 3.6.2.3 Motor Load. For motor load, a typical load inindustrial systems and in some public systems, the zero-sequenceimpedanceis again infinite, and the negative sequenceimpedanceis smaller than the positive-sequence impedance: YL2 > YLI and YLO = o. The resulting expression for the open-phase voltage is, with YL2 = YYLI y-2 V =-a y+ I (3.18) -!, For y = 1, whichcorrespondsto staticdelta-connectedload, we againobtain Va = for y = 2 we obtain Va = O. A typical rangeof the-ratiobetween positive and negative sequenceimpedanceis: y = 3··· 10 resulting in Va = 0.25···0.73. When theinduction motors slow down, the negative sequence impedancestays about the same while the positive sequence impedancebecomes smaller, until they are equal when motor the has come to astandstill.From equation(3.18) we canconcludethat the open-phasevoltage decays wheny gets smaller, thus when the motorsslow down. Theopen-phasevoltage 0AJ and 700/0 of the pre-faultvoltage, for a system withmotor load is initially between 50 133 Section 3.6 • Single-Phase Tripping decaying to -50% of pre-fault voltage (i.e., 500/0 of magnitude,but with opposite phase). From the above examples, we can concludethat the voltage in the open phase V varies between-0.50 and + 0.75times thepre-faultvoltage. When we use the symbol to indicatethis voltage, we get the followingphasorexpression for the voltages in the three phases: Va = V Vb = _!_!jY'3 Vc = _!+!jY'3 2 2 2 (3.19) 2 Using the transformationas defined by (3.7), we get for the line voltages (i.e., the voltages experienced by delta-connected a load) (3.20) We seethat a delta-connectedload experiences a voltage drop in two phases, but this experiencedby a starvoltagedrop is smallerthanthe voltagedrop in the open phase as connectedload. Also the load is less influenced by single-phasetripping than by threephasetripping. 3.6.2.4 Transfer to Lower Voltage Levels. Transfer to lower voltage levels often takes placethrough delta-starconnectedtransformers.The first transformer simply changes lineinto phase voltages,resulting in expression(3.20) but for the phase voltagesinsteadof for the line voltages. To obtain the line voltagesafter a delta-starconnectedtransformer,or the phase voltages after two such transformers,the transformation(3.7) has to beapplied a second time, to (3.20), resultingin I 2 Va =-+-V 3 3 2 ) --jY'3 I Vb = - -1(1-+-V 2 3 3 (3.21) 2 1 (1-+-V 2 ) +-jY'3 1. V.=-c 2 3 3 2 The resulting voltages fordifferent types of load are summarizedin Table 3.5. The transferof this kind of voltage events to lower voltage levels is discussed muchmore in detail in Section 4.4.Therewe will denotethe voltage events in (3.19), (3.20),and (3.21) as sags of type B withmagnitudeV, of type C with magnitude + ~ V, and of type D with magnitude!+ ~ V, respectively. t Chapter3 • Short Interruptions 134 TABLE 3.5 Load Voltages Due to Single-Phase Tripping, for Various Types of Star-connected Load Induction Motor Load Delta-connected Load Initial Motor Slowed Down Voltage in the Open Phase Va=-0.5 Va =0.75 Voltages After theFirst Dy-transformer Va=O Phasors Magnitudes Va = J Va = J Vh = -!-!j~ v, =-! Vc = -!+~jJ3 V(.= 100%, 57.7%,57.7% -! 100%, 50%,50% Va = 0.25 Va = J Va = I -! - f2jJ) Vr = - ! + fijv'3 Vh = -1- !.iv'3 Vc = -! + iJv'3 Vh = 100%,87.80/0,87.80/0100%, 66.1%, 66.1% Voltages After the Second Dy-transformer =! Va=0 = -!-!jJ) Vh = -!jJ) Vh = -fi - Vr =- Vr = Va Phasors Vh VC = -~+!j~ Magnitudes 33.3%,88.20/0,88.2% !jJ3 Va =~ Va =! !jJ3 -fi + !Jv'3 Vb = -!-!JJ) Vr = -! + !jv'3 % 50%, 90.1%, 90.1% 0, 86.6%,86.60/0 83.3%, 96.1%, 96.1 3.8.3 Current-During-Fault Period As we have seen in the previous section, the voltage in the faulted phase duringthe post-fault period is not necessarily zero. Anonzerovoltage after fault extinguishing implies a nonzerocurrent while the fault is present. This makes fault extinguishing more difficult. To calculate the fault current after single-phasetripping but before the fault extinguishes, weconsider the circuit in Fig. 3.15. Source and load impedancesare indicatedby the same symbols as before. Voltages and currentsat the system side of the openpoint are indicatedas Va' Vb, etc., and at the load side as V~, V;" etc. The electricalbehavior of this system can be described through 12 equations, three equationsdescribing the source (with again £] = 1): l-ZSlI] = V] -Zs212 = V2 (3.22) -ZsoIo = Vo three equationsdescribing the load: r; = ZLll{ V~ = ZL2I~ Vo = ZLolo (3.23) 135 Section 3.6 • Single-Phase Tripping ZS2 Zso Figure 3.15 Single-phase tripping with the short circuit still present. threevoltageequationsat the open point: V~ =0 v; = Vb V; = Ve (3.24) and threecurrentequationsat the open point: =0 fb =Ib fa (3.25) t, = l~ If we neglect thesourceimpedances,the voltagesat the systemside of the open point are equalto the sourcevoltages: VI =1 (3.26) V2 =0 Vo =0 From (3.24) relationscanbe obtainedbetweenthe componentvoltageson both sidesof the openpoint: I VI = I V2 = 2 3" VI I 1 -"3 V2 - "3 Vo 1 2 1 1 2 -"3 VI +"3 V2 - "3 Vo I 1 Vo = -"3 VI (3.27) -"3 V2 + "3 Vo With (3.26), thecomponentvoltagesat the load side of the open point can be found. Togetherwith (3.23) and I~ = I~ + 11 + 12we obtain an expressionfor the fault current after single-phasetripping: , 2 1 1 I a =- - - - - - - 3ZL1 3ZL2 3ZLO (3.28) We seethat the currentdependson the load impedancesin positive, negative,and zero sequence.As these impedancesare significantly larger than the source impedances (typically a factor of 10 to 20) thecurrent becomesmuch smaller than the original fault current.This certainlyhelps theextinguishingof the fault, but still the fault is most likely to extinguishwhen thecurrentis close tozero,thuswhen: 2YLt ~ YL2 + YLO with YL l = -Zl, etc. Not surprisingly this is also thecondition for which the voltage after LO fault extinguishingis zero, accordingto (3.15). 136 Chapter3 • Short Interruptions 3.7 STOCHASTIC PREDICTION OF SHORT INTERRUPTIONS To stochasticallypredict the number of short interruptions experiencedby a customerfed from acertain feeder, the followinginput data is required: • Failure rate per km of feeder,different valuesmight be used for the mainand for the lateral conductors. • Length of the main feederand of the lateral conductors. • Successrateof reclosure,if multiple reclosureattemptsare used: success rateof the first reclosure,of the secondreclosure,etc. • Position of reclosingbreakersand fuses. We will explainthe varioussteps in astochasticpredictionby using the system shownin Fig. 3.16.Note that this is ahypotheticalsystem.Stochasticpredictionstudiesin larger, albeit still hypothetical,systems have been performedby Warren[139]. The following datais assumedfor the system in Fig. 3.16: • The failure rate of the main feeder is:0.1 faults per year per kmof feeder. • The failure rate of the lateral conductorsis: 0.25 faults per year per kmof feeder. • The success rate o f the first reclosureis 75%; thus, in25% of the cases asecond trip and reclosureare needed. • The success rate o f the secondattemptis 100/0 of the numberof faults. Thus, for 15% of the faults thesecondattemptdoesnot clear the fault.Thosefaults are "permanentfaults" leadingto a long interruption. The reclosingprocedureused is as follows: I. The circuit breakeropensinstantaneouslyon theovercurrentdue to the fault. 2. The circuit breakerremainsopen for a short time (1 sec);75% of the faults clearsin this period. 3. The circuit breakercloses. If the fault is stillpresentthe breakeragainopens instantaneouslyon overcurrent.This is requiredin 25% of the cases. 4. Thecircuit breakernow leaves alongerdeadtime (5 sec).A nother 10% of the faults clear in this period. Lateral0: 3 km Lateral C: 7 km l---- ]] km of main feeder Recloser I Lateral B: 4 km • --Fuses LateralA: 8 km Figure 3.16 Example of overhead distribution feeder, for stochastic prediction study. 137 Section 3.7 • Stochastic Prediction of Short Interruptions 5. The circuit breakercloses for asecondtime. If the fault is still presentthe breakerremainscloseduntil the fuseprotectingthe lateralconductorhashad time to blow. 6. If the fault is still present(i.e., if the current magnitudestill exceeds its threshold)after the time needed for the fuse to clear the fault, thebreaker opensfor a third time and now remainsopen. Furtherreclosurehas to take place manuallyand the whole feeder willexperiencea long interruption. The total numberof faults on the feeder is 11 km x 0.1faults/kmyear + 22 km x 0.25faults/kmyear = 6.6faults/year (3.29) Each fault will lead to a voltage magnitudeevent. There are four different events possible: • a short interruptionof 1 secondduration. • two short interruptions; one of 1 second duration and one of 5 seconds duration. • two short interruptionsfollowed by avoltagesag. • two short interruptionsfollowed by a longinterruption. Due to short-circuitfaults on this feeder, 6.6 events per year occur, of which • 750/0 = 5.0 per year needone trip, leading to one short interruption for all customers. leadingto two short interruptionsfor all • 100/0 = 0.7 per year need two trips, customers. • 15% = 1.0 per year arepermanent,leadingto two shortinterruptionsfollowed by a voltagesag or followed by a longinterruption. The numberof shortinterruptionsis equalfor everycustomerconnectedto this feeder: 5.0/yearof 1 secondduration. 0.7/yearof 1+ 5 secondsduration. The numberof long interruptionsdependson the position at the feeder. Apermanent fault on the main feeder leads to a longinterruption for all customers.A permanent fault on oneof the lateralsleads to a longinterruptiononly for customersfed from this lateral. The numberof permanentfaults is, for the different partsof the feeder: • • • • • lateral A: 8 km x 0.25faults/kmyear x 0.15= 0.3faultsperyear lateral B: 4 km x 0.25faults/kmyear x 0.15 0.15faultsper year lateral C: 7 km x 0.25faults/kmyear x 0.15= 0.26faultsper year lateral D: 3 km x 0.25faults/kmyear x 0.15= 0.11faultsper year main: 11 km x 0.1faults/kmyear x 0.15= 0.17faultsper year = The number of long interruptionsexperiencedby customersconnectedto different partsof the feeder, is 138 Chapter3 • Short Interruptions • • • • • main: 0.17/year lateral A: 0.17 + 0.3 = 0.47/year lateral B: 0.17 + 0.15 = 0.32/year lateral C: 0.17 + 0.26 = 0.43/year lateral D: 0.17 + 0.11 = 0.28/year Gettingrid of the reclosureschemeand letting a fuseclearall faults on the lateral conductorswould lead to long interruptionsonly. • • • • • main: Lljyear lateral A: 3.1/year lateral B: 2.I/year lateral C: 2.9/year lateral D: 1.9/year Table 3.6 comparesthe numberof long and short interruptionsfor systemswith and without a reclosurescheme.For equipmentor production processessensitiveto long interruptionsonly, the systemwith a reclosureschemeis clearly preferable.It leads to a reduction of the number of long interruptions by 85%. But when equipment/ productionprocessis sensitiveto short and to long interruptions,it is betterto abolish the reclosure schemeand trip permanentlyon every fault. That would reduce the number of equipmenttrips by a factor between2 and 5, dependingon the position of the load on the feeder. Inreality this decision is not that easy to make, as some customersprefermoreshortinterruptionsabovea few long ones, while forothersonly the numberof interruptionsmatters.The first group is mainly the domesticcustomers, the secondone theindustrialcustomers.A financial assessment will almostalwaysbe in the favor of the industrials.An assessment on numbersof customersor on kWh will be in favor of the domesticcustomers. TABLE 3.6 Numberof Short and Long Interruptionsper Year on an OverheadDistribution Feeder, With andWithout Automatic Reclosure Long InterruptionsOnly With Reclosure Main feeder Lateral A Lateral B Lateral C Lateral 0 0.2 0.5 0.3 0.4 0.3 Without Reclosure 1.1 3.1 2.1 2.9 1.9 All Interruptions With Reclosure Without Reclosure 6.6 6.6 6.6 6.6 6.6 3.1 2.1 2.9 1.9 1.1 Voltage SagsCharacterization 4.1 INTRODUCTION Voltage sags areshort duration reductionsin rms voltage, caused by short circuits, overloads, andstartingof largemotors.The interestin voltage sags is mainly due to the problems they cause on several typesequipment:adjustable-speed of drives, processcontrol equipment,and computersare notoriousfor their sensitivity. Some pieces of equipmenttrip when the rms voltagedrops below 900/0 for longer than one or two cycles. In this and the two following chapters,it will become clearthat such a piece of equipmentwill trip tens of times a year.I f this is theprocess-controlequipmentof a papermill, one can imaginethat the damagedue to voltage sags can be enormous.Of course a voltage sag is not damagingto as industryas a (long orshort)interruption.But as there are far more voltage sags thaninterruptionsthe total damagedue to sags is still larger. Short interruptionsand most longinterruptionsoriginatein the localdistribution network. However, voltage sags at equipmentterminalscan be due toshort-circuit faults hundredsof kilometers away in thetransmissionsystem. A voltage sag is thus much more of a"global" problem than an interruption. Reducing the number of interruptionstypically requiresimprovementson one feeder.Reducingthe numberof voltage sags requires improvementson several feeders, and often eventransmission at lines far away. An exampleof a voltage sag due to short-circuitfault a is shown in Fig. 4.1. We seethat the voltageamplitudedropsto a valueof about20% of the pre-eventvoltage for abouttwo cycles. After these two cycles the voltage comes back aboutthe to pre-sag voltage. Thismagnitudeand duration are the maincharacteristicsof a voltage sag. Both will be discussed in more detail in the forthcomingsections. We can also conclude from Fig. 4.1that magnitudeand durationdo not completelycharacterizethe sag. The during-sagvoltage containsa rather large amount of higher frequencycomponents. Also the voltage shows a small overshootimmediatelyafter the sag. directedto voltage sags due to shortMost of the currentinterestin voltage sags is of equipment circuit faults. These voltage sags are the ones which cause majority the trips. But also thestartingof inductionmotorsleads to voltage sags. Figure4.2 gives an 139 140 Chapter4 • VoltageSags-Characterization --~--~-~--~-·- - ·r ·- ·- -· · _ · - · --, o 2 3 4 Time in cycles 5 6 Figure 4.1 A voltage sag due to a shortcircuit fault-voltagein one phase in time domain. (Data obtainedfrom [16].) Phase A voltage 106 .. : : 104 .. ---_ . 5 102 ~ t I- . .. . . , I.. ............-...................1"....................-..........-...... '1'.......... .... Min: Max: 93.897 101.46 ..... , ... ........ ... ... . .+...........- . . ... . . .. 1............... Avg: 95.8598..... 5100 I- . . . ._----------_._-----------------:-----_._-------..--------·---------------1-·--------------···_--··----------------- ;' ., - 98 I- ... . ..····..··..·..··..··..·········1·........···············..··....··.......j............................... CI) 96 I- . . .. . .. .. .... .........."":;;';;;;- e ~ _ _ _ _0 - • • • • ... ------- - - --- ----~ ._ ._.- -- - -- --_ ._ -- - _. __ ._-_._-.-_.-.----- ...............j.........................................j......................................... 94 I- ..... ~ 50 100 150 Time-cycles Figure 4.2 A voltage sag due toinduction motor starting.(Data obtainedfrom ElectrotekConcepts[l9J.) example of such a voltage sag [19] . Comparingthis figure with Fig. 4.1 shows that no longer theactualvoltage as afunction of time is given but the rms voltage versus time. The rms voltage is typicallycalculatedevery cycle or half-cycleof the power system frequency. Voltage sags due induction to motor startinglast longerthan those due to short circuits. Typicaldurationsare seconds to tens of seconds. The remainderof this chapterwill concentrateon voltage sags due to shortcircuits. Voltage sags due to motor startingwill be discussed inshort in Section 4.9. 4.2 VOLTAGE SAG MAGNITUDE 4.2.1 Monitoring The magnitudeof a voltage sag can be determinedin a numberof ways. Most existing monitors obtain the sagmagnitudefrom the rms voltages . But this situation might well change in the future. There are several alternativeways of quantifying the voltage level. Two obvious examples are the magnitudeof the fundamental(power frequency)componentof the voltage and the peak voltage over each cycle or halfcycle. As long as the voltage is sinusoidal,it does not matter whether rms voltage, 141 Section 4.2 • Voltage SagMagnitude fundamentalvoltage, or peak voltage is used to obtain the magnitude sag . But especially during a voltage sag this is often not the case . 4.2.1.1 Rms Voltage. As voltage sags are initially recorded as sampled points in time, the rms voltage will have to be calculated from the sampled time-domain voltages. This is done by using the following equation: 1 -Lv? N N ;=1 (4.1) I where N is the numberof samples per cycle and V; are the sampled voltages in time domain. The algorithm described by (4.1) has been applied to the sag shown in . 4.1. Fig The results are shown in Fig..34and in Fig. 4.4. In Fig. 4.3 the rms voltage has been calculated over a window of one cycle, which was 256 samples for the record ing used. Each point in Fig. 4.3 is the rms voltage over the preceeding 256 points (the first 255 rms values have been made equal to the value for sample: 256) 1.2,--~--,--- 5.. 0.8 .S ~ 0.6 S ~ 0.4 0.2 Figure 4.3 One-cycle rms voltagefor the voltage sagshownin Fig. 4.1. 2 3 4 Time in cycles 5 1.2,--~--.,.--- 5.. 0.8 .S ~ ~ 0.6 ~ .,. 0.4 ' , Figure4.4 Half-cycle rms voltagefor the voltage sagshownin Fig. 4.1. 2 . 3 4 Time in cycles 5 6 Chapter4 • VoltageSags-Characterization 142 i=k Vrmik) = L N 1?; (4.2) i=k-N+t with N = 256. We see that the rms voltage does not immediately drop to a lower value but takes one cycle for the transition.We also seethat the rms value during the sag is not completelyconstantand that the voltage does not immediately recover after the fault. A surprisingobservationis that the rms voltage immediately after the fault is only about90% of the pre-sag voltage. We will come back to this phenomenonin Section 4.9. From Fig. 4.1 one can see that the voltage in time domain shows a small overvoltage instead. In Fig. 4.4 the rms voltage has been calculated over the preceeding 128 points, N = 128 in (4.2). Thetransition now takes place in one half-cycle. sAhorter window than one half-cycle is not useful. The window length has to be an integer multiple of one half-cycle. Anyother window length will produce an oscillation in the result with a frequency equal to twice the fundamentalfrequency.For both figures the rms voltage has been calculated after each sample. In power quality monitors,this calculationis typically made once a cycle: i=kN VrmikN) = L N v~ (4.3) i=<k-l)N+l It is thus very likely that themonitor will give one value with anintermediatemagnitude before its rms voltage value settles down. We will come back to this when discussing sagduration. 4.2.1.2 Fundamental Voltage Component. Using the fundamentalcomponent of the voltage has the advantagethat the phase-angle j ump can be determined in the same way. The phase-angle jump will be discussed in detail in Section 4.5. The fundamentalvoltagecomponentas a function of time may be calculated as ~lund(t) = -T2 j l v(r)t!Wotdr (4.4) i-r whereWo = 2; and T one cycle of thefundamentalfrequency. Notethat this results in a complex voltage as a function of time. The absolute value of this complex voltage is the voltagemagnitudeas a functionof time; its argumentcan be used toobtain the phaseangle jump. In a similar way we can obtain magnitude and phase angle ofharmonic a voltagecomponentas a function of time. This so-called "time-frequencyanalysis" is a well-developed area within digital signal processing with a large applicationpotentialin power engineering. The fundamentalcomponenthas beenobtainedfor the voltage sag shown in Fig. 4.1. The absolute value of the fundamentalcomponentis shown in Fig. 4.5. Each point represents themagnitudeof the (complex)fundamentalcomponentof the previous cycle (256 points). Thefundamentalcomponentof the voltage has been obtained through a fast-Fourier transform (fft) algorithm [148]. A comparisonwith Fig. 4.3 shows that the behavior of the fundamentalcomponentis very similar to the behavior of the rms voltage. The rms voltage has the advantagethat it can be applied easily to a half-cycle window. Obtainingthe fundamentalvoltage from a half-cycle window is more complicated. A possible solution is to take a half-cycle window and to calculate the second half-cycle by using 143 Section 4.2 • Voltage SagMagnitude cos(wt I , , 3 4 Time in cycles 2 Figure4.5 Magnitudeof the fundamental componentof the voltage sag in ig. F 4.1. 6 5 + rP + 1l') =- cos(wt + rP) (4.5) Let Vi, i = 1. . . ~ be the samplesvoltagesover a half-cycle window. Thefundamental voltage isobtainedby taking the Fourier transformof the following series: VI ... v~, -VI' .. - (4.6) v~ This algorithm has beenapplied to the voltage sagshownin Fig. 4.1, resultingin Fig. 4.6. The transition from pre-fault to during-voltageis clearly fasterthan in Fig. 4.5. Note that this method assumesthat there is no de voltagecomponentpresent.The presence of a de voltagecomponentwi11lead to anerror in the fundamentalvoltage. An alternativemethod of obtaining the fundamentalvoltage componentis discussed in Section 4.5. 4.2.1.3 Peak Voltage.The peakvoltage as afunction of time can beobtained by using the following expression: I Vpeak = 0 <max r < T v(t - r) 6. ( 1lc: 8. 0.8 E o <.> ~ 0.6 ~ ::E 0.2 0' ==l J 0.4 .~ Figure 4.6 Magnitudeof the fundamental componentof the voltage sag in Fig . 4.1, obtainedby using a half-cycle window. (4.7) I .S .E ....o ]'" I ..._.~ _ _~~I 2 345 Time in cycles 6 144 Chapter 4 • Voltage Sags-Characterization 1.2 I,---~--~-~--~-~~--, 50 0.8 .5 ~ ~ ~ 0.6 L 0.4 0.2 234 5 6 Time in cycles Figure4.7 Half-cycle peak voltage for the voltage sag shown i n Fig. 4.1. with v(t) the sampled voltage waveform and T an integer multiple of one half-cycle. In Fig. 4.7, for each sample the maximum of the absolutevalue of the voltage over the preceding half-cycle has been calculated.We seethat this peak voltage shows sharp a drop and asharprise, althoughwe will see laterthat they do not coincide with commencement and clearing of the sag. Contraryto the rms voltage, the peak voltage shows an overshootimmediately after the sag , which correspondsto the overvoltage in time domain. The two methods are comparedin Fig. 4.8. We seethat the peak voltage tends to be higher most of the time with the exception of the end of the deep part of the sag. :::l 0. 0.8 .5 ~ s ~ 0.6 0.4 ,, , ,, , ,, , ,, , ,, 0.2 2 3 Time in cycles 4 5 6 Figure4.8 Comparisonbetweenhalf-cycle peak (solid line) andhalf-cycle rms voltage (dashed line) for the voltage sag shown in Fig. 4.1. 4.2.1.4 A One-Cycle Voltage Sag . Another example of a voltage sag is shown in Fig. 4.9; contrary to Fig. 4.1, all three phase voltages are shown. The voltage is low in one phase forabout one cycle and recovers rather fast after that. Theother two phases show some transientphenomenon,but no clear sag or swell. The latter is also evident from Fig . 4.10 which gives the half-cycle rms value for the sag shown in Fig. 4.9. We see in thelatter figure that the voltage in the twonon-faultedphases shows a small swell . Due to theshort duration of the sag the rms voltage curve does not have a specific flat part. This makes the determinationof the sagmagnitude rather arbitrary. If the monitor takes one sample every half-cycle the resulting sag 145 Section 4.2 • Voltage SagMagnitude al ~ f-:~ ~ 0 I 2 3 456 al0 ~ ~- I l ' , ~ 0123456 c: .;; OIl I ' ~I VVV\IVYJ ';; OIl 0 19 - ) Figure 4.9 Time-domainplot of a one-cycle sag, plots of the three phase voltages . (Data obtainedfrom [16J.) ~ 0) 23456 Time in cycles io:~: .:I 1:l l 4 5 3 4 Time in cycles 5 ~ 00 ~ I 0 : I 2 3 4 5 ~ o 2 o 2 3 ko:I====== ~~-~'-~,~~, Figure 4.10Half-cycle rms voltages for the voltage sag shown in Fig . 4.9. 6 -'I 6 6 magnitudecan be anywhere between 26% and 70% depending onmoment the at which the sample is taken . In case a one-cycle window is used to calculate the rms voltage, thesituation becomes worse . The two alternativemethods forobtaining the sagmagnitudeversus time have also been applied to phase b of the event in Fig. .9. The 4 half-cycle peak voltage is shown in Fig. 4.11, the half-cycle fundamentalvoltage componentin Fig. 4.12. The shape of thelatter is similar to the shape of the half-cycle rms. The half-cycle peak voltage again shows a much sharpertransition than theother two methods. 4.2.1.5 Obtaining One Sag Magnitude.Until now, we havecalculatedthe sag magnitudeas a function of time: either as the rms voltage , as the peak voltage, or as the fundamentalvoltage componentobtainedover acertain window. There are various ways of obtaining one value for the sagmagnitudefrom the magnitudeas a function of time. Most monitors take the lowest value.Thinking about equipment sensitivity, this correspondsto the assumptionthat the equipment trips instantaneously when the voltage drops below a certain value. As most sags have rather a constantrms valueduring the deeppart of the sag, using the lowest value appears an acceptableassumption. 146 Chapter4 • VoltageSags-Characterization I.2 f :> 0.. 0.8 .5 1iI> 0.6 S ~ 0.4 0.2 2 3 4 5 6 Time in cycles a Figure 4.11 Half-cyclepeak voltage for phase b of the sag shown in Fig . 4.9. I [_ ~ -- ' ! .5 C ~ 8. 0.8 E o o '3 e 0.6 E .jg ~ 0.4 e- o ]" 0.2 .~ ~ 0 ~~_~ L : . _ _ ~ _ _ ~ _ _ 234 Time in cycles ~_--' 5 6 Figure 4.12 Half-cyclefundamentalvoltage F 4.9. for phase bof the sag shown in ig. So far there israther generalagreement,both about using the rms value,a nd about taking the lowest rms value todeterminethe sagmagnitude.But when the sag magnitudeneeds to bequantified in a number,the agreementis no longer there. One common practiceis to characterizethe sagthrough the remainingvoltageduring the sag.This is then given as ap ercentageof the nominal voltage. Thus, a 70% sag in a 120 volt systemmeansthat the voltagedroppedto 84 V. This methodof characterizingthe sag isrecommendedin a numberofIEEE standards(493-1998,1159-1995,1346-1998) . The confusionwith this terminologyis clear. One could be tricked into thinking that a 70% sag refers to a d rop of 70%, thus a remainingvoltageof 30%. The recommendation is thereforeto use thephrase" a sagdown to 70%" [3]. The lEC has solved this ambiguity by characterizingthe sagthroughthe actualdrop in the rmsvoltage[4]. This has somewhatbecomecommon practicein Europe. Characterizinga sag through its drop in voltagedoes not solve all problemshowever,becausethe nextquestionwill be: What is the referencevoltage? There are argumentsin favor of using the pre-fault voltage and there are arguments in favor of using the nominal voltage. The International Union of Producers and Distributors of Electrical Energy (Union International des Producteurs et Distributeurs d'Energie Electrique, UNIPEDE) 147 Section 4.2 • Voltage Sag Magnitude recommendsto use thenominal voltageas a reference(5]. As severaldefinitions are in use, it isimportantto clearly define the way in which the sag magnitudeis defined. In this book sag magnitudeis defined as theremainingvoltageduring the event. Using the remainingvoltageas the sagmagnitude,leads to someobviousconfusions. Themain sourceof confusionis thata largersagmagnitudeindicatesa less severe of terms event. In fact, a sagm agnitudeof 100% correspondsto no sag at all. The use like "large sag" and "small sag" would be extremelyconfusing. Insteadwe will talk abouta "deepsag" and a "shallow sag." A deep sag is a sag with a low magnitude;a shallow sag has a largemagnitude.When referring to equipmentbehaviorwe will also use theterms "severesag" and "mild sag." As far as magnitudeis concerned,these terms correspondto "deepsag" and "shallow sag," respectively. 4.2.2 TheoreticalC alculations Considerthe power systemshownin Fig. 4.13, where thenumbers(1 through5) indicate fault positionsand the letters (A through D) loads. A fault in the transmission network, fault position 1, will causea serioussag for both substationsbordering the faulted line. This sag isthen transferreddown to all customersfed from these two substations.As there is normally no generationconnectedat lower voltage levels, thereis nothing to keep up the voltage. The result that is a deep sag isexperiencedby all customersA, B, C, and D. The sagexperiencedby A is likely to be somewhatless deep, as thegeneratorsconnectedto that substationwill keep up thevoltage. A fault at position 2 will not causemuch voltagedrop for customerA. The impedanceof the transformersbetween the transmissionand the sub-transmissionsystem are large enoughto considerablylimit the voltagedrop at high-voltageside of the transformer. The sagexperiencedby customerA is further mitigated by the generatorsfeeding in to its local transmissionsubstation.The fault at position 2 will, however,causea deep sag at both subtransmissionsubstationsand thus for all customersfed from here (B, C, and D). 3 Figure4.13 Distribution network with load positionsand fault positions. Chapter4 • VoltageSags-Characterization 148 A fault at position 3 will cause a very deep sag for customer D, followed by a short or longinterruption when theprotectionclears the fault.CustomerC will only experience a deep sag. If fast reclosure is used indistribution the system, customer C will experience two or more sags shortly after each other forpermanentfault. a Customer B will only experience a shallow sag due to the fault at position 3, again due to thetransformerimpedance.CustomerA will probably not notice anything from this fault. Finally, fault 4 will cause a deep sag for customer C and a shallow one for customer D.For fault 5 the result is just the other way around: a deep sag for customer D and a shallow one for customer C. Customers A and B will not be influenced at all by faults 4 and 5. To quantify sag magnitude in radial systems, the voltage divider model, shown in Fig. 4.14, can be used. This might appeara rather simplified model, especially for transmission systems. But as we will see in the course of this and further chapters, it has turned out to be a rather useful model to predict some of the properties of sags. In Fig. 4.14 we see two impedances: Zs is the source impedance point-of-common at the point-of-commoncoupling and the coupling; and ZF is the impedance between the fault. The point-of-commoncoupling is the point from which both the fault and the load are fed. In other words: it is the place where the load currentbranches off from the fault current. We will often abbreviate"point-of-commoncoupling" as pee, In the voltage divider model, the load current before as well as during the fault is neglected. There is thus no voltage drop between the load and the pee. The voltage at the pee, and thus the voltage at the equipment terminals, can be found from ZF s+ Z F E v.rag=Z (4.8) In the remainder of this chapter, we will assume that the pre-event voltage is exactly 1 pu, thus E = 1. This results in the following expression for the sag magnitude v = sag ZF ZS+ZF (4.9) Any fault impedance should be included in the feeder impedance ZF' We see from (4.9) that the sag becomes deeper for faults electrically closer to the customer ZF (when becomes smaller), and for systems with a smaller fault level (when Zs becomes larger). Note that a single-phase model has been used here, whereas in reality the system is three-phase. That means that this equationstrictly speaking only holds for three-phase faults. How the voltage divider model can be used for single-phase and phase-to-phase faults is discussed in Section 4.4. Equation(4.9) can be used to calculate the sag magnitude as a function of the ZF = Z x E, with z the impedance of distance to the fault. Therefore we have to write £ the distance between the fault and the pee, leading to the feeder per unit length and E Fault Load pee Figure.4.14Voltage divider model for a voltage sag. 149 Section 4.2 • Voltage Sag Magnitude v _ sag - z£ Zs + z£ (4.10) The sagmagnitudeas afunction of the distanceto the fault has been calculatedfor a typical 11kV overheadline, resulting in Fig. 4.15. For the calculationsa 150mnr' overheadline was used and fault levels of 750 MVA, 200 MVA, and 75 MVA. The fault level is used tocalculatethe sourceimpedanceat the pee, the feeder impedanceto calculatethe impedancebetween the pee and the fault. It was assumed that the source impedanceis purely reactive, thusZs =jO.161 n for the 750 MVA source. The impedance of the 150mrrr'overheadline is 0.117+ jO.315 Q per km [10]. As expected, the sag magnitudeincreases (i.e., the sag becomes less severe) for t hat faults at increasingdistanceto the fault and forincreasingfault level. We also see tensof kilometersdistancemay still cause a severe sag. 1 0.8 :s e, .5 -8 a 75MVA I 0.6 .~ e 0.4 ~ fI) 0.2 Figure 4.15 Sag magnitude as a function of the distance to the fault, for faults on an 11 kV, 150 mnr' overhead line. 10 20 30 40 Distanceto the fault in kilometers 50 4.2.2.1 Influence of Cross Section. Overheadlines of different cross section have different impedance,and lines and cables also have different impedance.It is thus to be expectedthat the cross sectionof the line or cable influences the sag magnitude as well. To show this influence, Fig. 4.16 plots the magnitudeat sag the pee 0.8 6- .5 ] 0.6 )9---T~ 300 1/ .~ e0.4 f fI) 0.2 Figure 4.16 Sag magnitude versus distance, for 11 kV overhead lines with different cross sections. 5 10 15 20 Distanceto the fault in kilometers 25 150 Chapter 4 • VoltageSags-Characterization 50 0.8 150 8.5 300 ~ 0.6 a .~ e 0.4 ~ en 0.2 5 10 15 20 Distance to the fault in kilometers 25 Figure4.17 Sagmagnitudeversusdistance, for II kV undergroundcableswith different cross sections. as a function of the distancebetweenthe fault and the pee, for 11 kVoverheadlines with threedifferent cross sections:50, 150,and 300 mm''. A sourceimpedanceof 200 MV A has been used. Thesmaller the crosssection, the higher the impedanceof the feeder and thus the lower thevoltagedrop. For overheadlines, the influence israther small as thereactancedominatesthe impedance.For undergroundcables, the influence ismuch bigger asshown in Fig. 4.17, again for cross sectionsof 50, 150,and 300 mrrr'. The inductanceof cablesis significantly smallerthan for overheadlines, so that the resistancehas more influence on theimpedanceand thus on the sagmagnitude. Theimpedancevalues used toobtain Fig. 4.16 and Fig. 4.17 are given inTable 4.1. All impedancesare for an II kV voltage level. TABLE 4.1 Line and CableImpedancesfor 11 kV FeedersUsed in Figs. 4.16 and 4.17 Impedance CrossSection 2 50 mm 150mrrr' 300 mm2 OverheadLine Cable 0.363+ jO.351 Q 0.117 + jO.315Q 0.061+ jO.298Q 0.492 + jO.116Q 0.159+jO.097Q 0.079 +jO.087 Q Source: Data obtained from [10]. 4.2.2.2 Faults behind Transformers.The impedancebetweenthe fault and the pee in Fig. 4.14not only consistsof lines or cablesbut also of power transformers. As transformershave arather large impedance,amongothersto limit the fault level on the low-voltage side, thepresenceof a transformerbetweenthe fault and the pee will lead to relatively shallow sags. To show the influenceof transformerson the sagmagnitude,considerthe situation shownin Fig. 4.18: a 132/33kV transformeris fed from thesamebus as a132kV line. A 33 kV line is fed from thelow-voltageside of the transformer.Fault levels are 3000 MV A at the 132 kV bus,a nd 900 MV A at the 33 kV bus. Inimpedanceterms,the source impedanceat the 132 kV bus is5.81 0, and the transformerimpedanceis 13.550, both referred to the 132kV voltage level. The sensitiveload for which we lSI Section 4.2 • Voltage Sag Magnitude pee 132kV 132 kV line Load Figure 4.18Powersystem with faults at two voltage levels. 33 kV line want to calculatethe sagmagnitudeis fed from the 132kV bus viaanother132/33 kV Zs = 5.810, ZF = 13.550+ z x {" z is the transformer.We can again use (4.9), where transfeederimpedanceper unit length,and {, the distancebetween the fault and the former's secondaryside terminals. The feeder impedancemust also be referred to the k{ )2x 0.3Qjkm when the feederimpedanceis 0.3Qjkm at 33 kV. 132kV level: z= (upper The resultsof the calculationsare shown in Fig. 4.19 for faults on the 33 kV line curve) and for faults on the 132kV line (lower curve). We see that sags due to33kV Not only does the 33 kV curves tart faults are less severe thansags due to 132kV faults. off at a higher level (due to the t ransformerimpedance),it also rises much faster. The latter is due to the factt hat the feederimpedanceseen from the 132kV level is (132/3 3)2 = 16 times as high asthat seen from the 33 kV level. (lilk Faultsat 33 kV 0.8 Faultsat 132kV 0.2 I.......--_ _L . . - - _ - - J I - - - Figure 4.19 Comparisonof sag magnitude for 132 kV and 33 kV faults. --J-_ __._! __ ..•.•..._ . . . • ._.. 20 40 60 80 Distanceto thefault in kilometers 100 4.2.2.3 Fault Levels. Often the sourceimpedanceat a certain bus isnot immediately available, but insteadthe fault level is. One canof coursetranslatethe fault level into a sourceimpedanceand use (4.9) tocalculatethe sagmagnitude.But one may calculatethe sagmagnitudedirectly if the fault levelsboth at the peeand at the fault position are known. LetSFLT be the fault level at the faultposition and Spec at the point-of-commoncoupling. For a rated voltage Vn the relationsbetween fault level and sourceimpedanceare as follows: (4.11) 152 Chapter4 • VoltageSags-Characterization V,; (4.12) SPCC=- Zs With (4.9) the voltage at the pee can be written as Vsag -- I _ SFLT (4.13) Spec We use(4.13)to calculatethe magnitudeof sags behindtransformers.For this we use typical fault levels in theU.K. power system[13]: 400 V 11 kV 33 kV 132 kV 400 kV 20 MVA 200 MVA 900 MVA 3000 MVA 17000MVA Considera fault at a typical11 kV bus, i.e., with a fault levelof 200 MVA. The voltage sag at thehigh-voltageside of the 33/11kV transformeris from (4.13) v,wg = 1 - 200 MVA 0 900 MVA = 78Yo In a similar way the wholeof Table 4.2 has been filled. The zeros in this table indicatethat the fault is at the same or at a higher voltage level. The voltage dropsto a low value in such a case. We can see from Table 4.2 that sags are significantlydamped when theypropagateupwardsin the power system. In a sagstudy we typically only of have to take faults one voltage level down into account.And even those are seldom seriousconcern.An exceptionherecould be sags due to faults at 33kV with a pee at 132kV. They could lead to sags down to 70o~. TABLE 4.2 Upward Propagationof Sags Point-of-CommonCoupling Fault Point II kV 33 kV 132 kV 400 kV 400 V II kV 33 kV 132 kV 900~ 98°~ 0 0 0 78% 0 0 99% 93% 70% 0 100% 990/0 950/0 82% 4.2.2.4 Critical Distance. Equation (4.10) gives thevoltage magnitude as a function of the distanceto the fault. From this equationwe can obtain the distance at which a fault will lead to a sagof a certain magnitude.If we assumeequal X/R ratio of sourceand feeder, weobtain (4.14) We refer to thisdistanceas the criticaldistancefor a voltage V. Supposethat a pieceof equipmenttrips when thevoltagedropsbelow acertainlevel (the critical voltage). The 153 Section 4.2 • Voltage Sag M agnitude definition of critical distance is such that each fault within the criticaldistancewill cause the equipmentto trip . This concept will be used in Section 6.5 to estimate the expected numberof equipmenttrips . If we assumefurther that the numberof faults isproportional to the line length within the critical distance, we would expect that the numberof sags below a level V is conclusion. proportionalto V/( I - V) . Another assumptionis needed to arrive at this Every feeder connected to every pee needs to be infinitely long ithout w any branching off. Of course this is not the case in reality . Still this equation has beencomparedwith a number of large power quality surveys. The results are shown in Fig. 4.20. Power quality survey results in the Un ited States [IIJ, [l2J, in the U.K. [l3J and in Norway [16J are indicated as dots, the theoretical curve is shown as a solid line. The rresponco dence is good, despite the obviously serious approximationsmade. Even though (4.14) only holds for rad ial systems, it gives a generally usable relation between thenumberof voltage sags and the voltage. The expression clearly measurements . showsthat the majority of sags are shallow, a fact confirmed by most -._ - ---_._ - -- . USA [II] • USA [12] • UK [13] x Norway [16] - Theory Figure 4.20 Numberof sags versus magnitude :theoretical results (solid line) versus monitoring results (dots) . o 20 40 60 80 100 Sag magnitude in percent 4.2.3 Example of Calculation of Sag Magnitude We will apply the theoreticalconceptsdeveloped in the previous sections to the supply shown schematically in Fig. 4.21. This same example will be used again in forthcoming parts of this book. The supply shown in Fig. 4.21 is the existing supply to an indust rialcustomersomewhere in the No rth of England[15J. The sensitive load consists of several large ac and de adjustable-speed drives. The de drives are fed via dedicated transformersat 420 V, the moremodernac drives at 660 V.Most of the data used for the various calculationsbelow have been obta ined from the local utility. Where "as typical as posno data was available,d ata have been used which was considered sible." Like often in these kind of studies, the collection of datarequires the at least as much effort as theactualcalculations. In the restof this book it will always be assumed that all the requireddata is readily available. The first step in a sag analysis is to recognize the possible pee's, For any fault on one of the II kV feeders, the faultcurrent will flow through the STU-II bus, but not further towards the ·load . TheS TU-II bus is thus the pee for all faults within the the II kV network. In the same way, the ROS-33 bus is the pee for faults on of any 33 kV feeders. Theother possible pee's are PAD -I32 and PAD-400. To calculatethe sag magnitudewe need the sou rce impedanceand the feeder impedance. The source 154 Chapter 4 • VoltageSags-Characterization Slines 8 lines P ---. J\O-400 --ill r - - -_ _ EGG-400 3 feeders Figure 4.21 Example of power supply be to used for voltage sag calculations. impedanceis given in Table4.3, the feederimpedancein Table4.4. All impedancesare given for a 100 MVA base.Finally, Table 4.5 gives thetransformerconnectionand neutral grounding.This information is needed inlater sections,when unbalancedsags are discussed. For now weignore the fact that the impedancesare complexand use theabsolute values for our calculations.We will come back to thecomplex impedancesin Section 4.5 whenphase-anglejumps are discussed.F or faults at II kV we obtain for the impedances:z = 27.75% per km and Zs = 66.08%.The critical distancecan becalculated from Lcril = 2.381 x I~V' Calculationsfor the critical distancesat 33 kV and 132kV proceedin exactly the same way as for the11 kV system.The resultsof thesecalculationsare shownin Table 4.6. We seethat thereare twocolumnsfor the 400 kV system inTable4.3 and in Table 4.6. This has to do with the fact that thereare twopossiblesourcesfor the short-circuit power. If the fault issomewherebetweenPAD-400 and PEN-400the fault currentwill be delivered from thedirectionof EGG-400.Thus,for such a fault, theimpedanceZs is the sourceimpedanceas seen in thedirectionof EGG-400.The critical distancesresulting from this sourceimpedanceare shownin Table4.6 in thecolumn labeled "toward PEN-400." Note that for this the sourceimpedancein the direction of EGG-400has been used.F or faults in thedirection of EGG-400,the sourceimpedancein the direc.. tion of PEN-400has been used. Thoseresults areshownin the columnlabeled"toward EGG-400." WheninterpretingTable4.6 oneshouldrealizethat these values hold for raadial system with infinitely long lineswithout any sidebranches.In reality all feeders have a finite length. In this system themaximum distancefrom the pee for afault at 11 kV is 5 km. The distanceto the fault can thus not be more than 5 km and the magnitudeof the most shallow sag due to afault at 11 kV is ZF V:vag 5 x 0.2727 ° = Zs + ZF = 5 x 0.2727+ 0.6608= 67 Yo (4.15) Figure4.22plots sagmagnitudeversusdistancefor faults at all thevoltagelevels in Fig. 4.21. Thehorizontalscale isdeterminedby the maximumlength of the feeders att hat 155 Section 4.2 • Voltage Sag Magnitude TABLE 4.3 Source Impedance for the Supply Shown in Fig. 4.21, at a 100 MVA Base Zero Sequence II kV 33 kV 132 kV 400 kV From EGG From PEN Positive and Negative Sequence 787 + j2200/0 2510/0 0.047 + .i2.75% 4.94 + j65.90/0 1.23 + jI8.3°At 0.09 + j2.86% 0.329 + j2.273% 0.653 + j5.124% 0.084 + jl.061 % 0.132 + j1.94% TABLE 4.4 Feeder Data for the Supply Shown in Fig. 4.21 Positive and Negative Sequence II kV 33 kV 132 kV 400 kV 9.7 + j26 %/km 1.435 + j3.102°At/km 0.101 + jO.257°At/km 0.001 + jO.018%/km Zero Sequence 18.4 + jII2°At/km 2.795 + jI5.256%/km 0.23 + ]U.650/0/km 0.007 + ]U.0500/0/km Max Length 5 km 10 km 2 km > 1000km TABLE 4.5 Transformer Connections and Neutral Grounding for the Supply Shown in Fig.4.21 Voltage Level Transformer Winding Connection 400 kV 400/132 kV 132/33kV solidly grounded solidly grounded resistance grounded through zigzag transformer resistance grounded solidly grounded YY autotransformer Star - Delta Delta - Star Delta - Star 33/11 kV II kV/660 V and 11 kV/420 V Neutral Grounding at LV Side TABLE 4.6 Critical Distance Calculation for the Network Shown in Fig. 4.21, According to (4.14) z Zs V= 10°At V = 30% V = 500/0 V = 70% V = 90% II kV 33 kV 132 kV 27.27% 66.08% 0.3 km 1.0 km 2.4 km 5.6 km 21.4 km 3.418°At 18.34% 0.6 km 2.3 km 5.4 km 12.5 km 48.3 km 0.276% 2.8610/0 1.2 km 4.4 km 10.4 km 24.2 km 93.3 km 400 kV Toward 400 kV Toward PEN-400 EGG-400 0.018% 1.064% 6.6 km 25.3 km 59.1 km 138 km 532 km 0.018% 1.9440/0 12.0 km 46.3 km J08 km 252 km 972 km 156 Chapter 4 • VoltageSags-Characterization ) 11 kV faults 33 kV faults ,.-----...---, 132kV faults 400 kV faults I I: 0.5 00 1 2 o o Distanceinkilometers . 100 --.JI 200 Distanceinkilometers Figure 4.22 Magnitude versus distance for faults at various voltage levelsin the supply in Fig. 4.21. voltage level.For 400 kV a lengthof 200 km has been taken. The short length of the 132kV feeders makesthat sags due to faults at 132kV are always very deep. 4.2.4 Sag Magnitude In Non-Radial Systems In Section4.2.2 we discussed sag magnitudeversusdistancein radial systems. Radial systems arecommonin low-voltage and medium-voltagenetworks.At higher voltage levelsother supply arrangementsare common.Some typical cases will be discussed below. We will alsopresenta general way ofcalculating sag magnitudesin meshed systems. 4.2.4.1 Local Generators. The connectionof a local generatorto a distribution network, as shown in Fig.4.23, mitigates voltage sagsof the indicated load in two different ways. Thegeneratorincreases the fault level at the distribution bus, which mitigates voltage sags due to faults on the distribution feeders. This especially holds for a weak system.For a strong system, the fault levelcannot be increased much without the risk of exceeding themaximum-allowableshort-circuit current of the switchgear.The installation of local generationrequires a largerimpedanceof the feeding transformer. Rest of the system I'\v Load Local generation Figure 4.23 Connection of a local generator to a distribution bus. 157 Section 4.2 • Voltage Sag Magnitude A local generatoralsomitigatessags due to faults in the rest of the system.D uring such a fault thegeneratorkeeps up thevoltageat its local bus by feedinginto the fault. An equivalentcircuit to quantify this effect has beendrawn in Fig. 4.24: Z4 is the impedanceof the local generatorduring the fault (typically thetransientimpedance); ZI the sourceimpedanceat the pee;Z2 the impedancebetween the faultand the pce; and Z3 the impedancebetween thegeneratorbus and the pee. Note that the conceptof point-of-commoncoupling strictly speakingno longer holds. Thisconcept,which was o f fault current. By addinga introducedfor radial networks,assumes one single flow generatorclose to the load asecondflow of fault current is introduced.The pee as indicatedin Fig. 4.24 is thepoint-of-commoncoupling before theintroduction of the local generator.Without the local generatorthe voltage at theequipmentterminals would beequalto the voltageatthepee,Whena local generatoris present,the voltage at theequipmentterminalsduring the sagequalsthe voltageon thegeneratorbus. This voltage is related to thevoltageat the peeaccordingto the following equation: (1 - 2 Vvag) = Z 3+4Z 4 (1 - Vpcc) (4.16) The voltagedrop at the generatorbus isz ~z times thevoltagedrop at the pee, The voltagedrop becomes smaller forlarger imped~nce to the pee(weakerconnection) and for smallergenerationimpedance(larger generator).The fault contributionof the rest of the system at theg eneratorbus isoften mainly determinedby the impedanceof the feedingtransformer.In that case thereductionin voltage drop is approximately equal to thegeneratorcontributionto the fault level at thegeneratorbus. Thus, if the generatordelivers50% of the fault current,a sagdown to 40% at the pee(60% voltage drop) will be reducedto a sagdown to 700/0 (30% voltage drop) at the equipment terminals. From (4.16) we can alsoconcludethat there is anon-zerominimum sag magnitude.Even a fault at the pee will no longercause a sag d own to zerovoltagebut a sagof magnitude Vmin =2 3Z3 +2 4 (4.17) For the above-mentioned system, where the local generatoris responsiblefor 50% of the fault level at thegeneratorbus, the lowest sagm agnitudedue to a fault at a higher voltagelevel is 50% • During a fault not only local generatorscontributeto the fault but also induction motors. Using the abovereasoningwe can concludethat the minimum voltage at the plant bus equalsthe relative fault levelc ontribution of the induction motors. We will discussinduction motorsin more detail in Section 4.8. pee--'---.---'-Load Figure 4.24 Equivalent circuit for system with local generation. Fault 158 Chapter4 • Voltage Sags-Characterization EXAMPLE An exampleof a system withon-site generationis given in Fig. 4.25: the industrial system is fed from a 66 kV, 1700 MVAsubstationvia two 66/11 kV transformersin paraJIel. The fault level at the 11 kV bus is 720 MVA, which includes contribution the of two 20 MVA on-site generatorswith a transientreactanceof 170/0. The actual industrial load is fed from the 11 kV bus, for which we willcalculatethe sagmagnitudedue to faults at 66 kV. The feeder impedanceat 66 kV is 0.3Q/km. Public supply 66 kV, 1700MVA ---a._..........._....--a_.L--1_1_k_V,_720 Faulted feeder MVA Figure 4.25 Industrial distribution system with on-site generation. Industrial load With referenceto (4.16) and Fig. 4.24, we get the following impedancevalues for this system(referred to 66kV): Z. == 2.56Q 2 2 = 0.3 O/km x £, 2 3 = 6.42Q 2 4 = 18.SQ The calculationresults areshownin Fig. 4.26.The bottomcurvegives the sagmagnitudeat the 11 kV bus for faults at a 66 kV feeder, when the 11generatoris kV not in operation.In that case the sagm agnitudeat 11 kV equalsthe sagmagnitudeat 66 kV becauseall load currentshave t op curve gives the sagmagnitudeat the 11kV bus withon-site generator been neglected. The connected.Due to thegeneratorkeepingup thevoltageat the 11 kV bus, the sag magnitudenever drops below 260/0. Thereare two methodsto further improve the supply. One canincreasethe numberor sizeof the generators,which correspondsto decreasing2 4 in (4.16).Alternatively one can increase2 3, which leads to a lower fault level at the 11 kV bus. 0.: ~::-er-a--'t~-rs-----r----.---i .~a 0.6 I Without generators "'0' '1 ~ 0.4 ~ V} 0.2 oO~--w- 20 30 4'0 Distanceto the faultin kilometers --.J 50 Figure 4.26 Sagmagnitudeversus distance, with and without on-site generator. IS9 Section 4.2 • Voltage Sag Magnitude EXAMPLE Another exampleof the useof (4.16) is given bymeansof Fig. 4.27. This figure representshalf of the transmissionsystem part of the examplein Fig. 4.21, containing the substationsPAD-400 and EGG·400,plus 30 km of overhead400kV line in betweenthem. The impedanceshave thefollowing values (in % at a 100 MVA base), withE the distancebetween EGG-400and the fault: Zt = 1.4% Z2 = 0.OI8% / k m x £ 2 3 = 0.54% Z4 == 1.940/0 The impedance2 4 representsthe sourcecontributionfrom PEN-400at PAD-400; 2 3 represents the impedanceof 30 km line (0.018%/km); 2 2 the impedancebetweenEGG-400and the fault, and Zt the contribution through the non-faultedlines at EGG-400(excluding the contribution from PAD-400) during the fault. The latter impedanceis likely to be different for faults on different lines. In this study we assumedit to be simply equal to the contribution of all lines at EGG-400minusthe line toPAD-400.As thereare atotal of nine linesconnectedto EGG-400the error madewill not be very big. Fault Figure 4.27 Circuit diagramrepresentation of two transmissionsubstations.The sensitive load is fed from thesubstationon the left. Load For faults to the right of EGG-400we can use (4.16) tocalculatethe voltageat PAD-400, knowing the voltageat EGG-400.The latter can be obtainedfrom the voltagedivider equation with the sourceimpedanceformed by the parallel connectionof 2, and 2 3 + Z4' Note that we still neglect all loadcurrents,so that both sourcevoltagesare equal in magnitudeand in phase and can bereplacedby one source. For faults betweenPAD-400 and EGG-400'the voltage divider model will give the required voltage directly. The sourceimpedanceis now formed by 2 4; the feederimpedanceis O.018% / k m x C. with E the distancebetweenPAD-400and the fault. The resultingsag magnitudeas afunction of the distanceto the fault isshown in Fig. 4.28. For 0.8 5. .S ] 0.6 'ts 0.4 ~ r.n 0.2 Figure 4.28 Sagmagnitudeas afunction of the distanceto the fault, for transmission systems. I I , 20 I 40 60 ----1.-------': 80 100 Distance to the fault in kilometers 160 Chapter4 • VoltageSags-Characterization distances up to 30 km the sag magnitudechanges with distance like in a radial system; for larger distances themagnitudeincreases faster. Thus, the sag is less severe than for a fault at the same distance in a radial system. 4.2.4.2 SubtransmissionLoops. At subtransmissionlevel, the networks often consist of severalloops-atypical example is shown in Fig. 4.29. The transmission system isconnectedto the subtransmissionsystem through two or three transforof thesetransformersa numberof submers. From the busses at the low-voltage side stationsare fed via a loop. Such n aetwork configurationis also found inindustrial of two branchesin parallel. The mathepower systems. Often the loop only consists matical expressionsthat will be derived below can also be used calculatevoltage to sags due to faults on parallel feeders. Subtransmission Figure 4.29 Example of subtransmission loop. To calculate the sagmagnitudewe need to identify the load bus, the faulted branch, and the non-faulted branch. Knowing these theequivalent scheme in Fig. 4.30 isobtained,where Zo is the sourceimpedanceat the bus from which the loop is fed; Zl is the impedanceof the faulted branchof the loop; Z2 is the impedanceof the non-faulted branch; and p is the position of the fault on the faultedbranch (p = 0 correspondsto a fault at the bus from which the load is fed, p = 1 correspondsto a fault at the load bus). From Fig. 4.30 the voltage at the load bus can calculated,resulting be in the following expression: v _ sag - p(l-p)Zr ZO(ZI + Z2) + pZ t Z 2 + p(l - p)Z? (4.18) Fault pZl 1 (I - p)ZJ Load Figure 4.30 Equivalent circuit for subtransmission loop. 161 Section 4.2 • Voltage Sag Magn itude The voltage is zero forp = 0 (fault at the mainsubtransmissionbus) and forp = 1 (fault at the load bus) and has a maximum somewhere in between . . 4.31: a 125-km 132kV loop connectEXAMPLE Consider the system shown in Fig ing a number ofsubstations.Only the substationfeeding the load of interest is shown in the figure. This substationis located at 25 km from the main substation. The fault level at the Qjkm. Faults occur both in the point-of-supply is 5000 MVA and the feeder impedance 0.3 25 km part and in the 100 km part of the loop , so that both may form the faulted branch . For a fault on the 25 km branch we substitutein (4.18): Z\ = 25zand Z2 = 100z, with z the feeder impedance per km. For a fault on the 100 km branch , we get Z\ 100z andZ2 25z. = = ............. ........ ...... .............. 132 kV 5000MVA J--- - . .....100km ......... .....: ---, Load Figure 4.31Loop systemoperatingat 132kV. Figure 4.32gives the magnitudes of sags due to faults in the 132subtransmission kV loop. The dashed (top) curve gives the sag magnitudefor faults on the 100 km branch, the solid (bottom) curve holds for the 25 km branch. Note that the horizontal scale correspondsto 25 km for thebottomcurve and to 100 km for the top curve. Figure .33gives 4 the sag magnitudes for the 100 km and 25 km feeder as a function of the actual distance between the fault and the main 132 kV bus.For comparison, the magnitudeis also given for sags due to faults at a radial feeder from the same main 132kV bus (dottedcurve). 0.8 So = ~ 0.6 ~ 0.4 e ~ ,, en r 0.2 r ,, , ' Figure 4.32 Sagmagnitudesfor faults on a 132kV loop. 00 ~-- 0.2 0.4 0.6 Fault position 0.8 We see from Fig. 4.32 and Fig. 4.33that each fault on the loop will cause the voltage todrop below 50%of the nominal voltage. A sag due to a fault on a loop is always lower than due to a fault on a radial feeder. Faultsclose to thepoint-of-supply will lead to a deep sag . Faultsclose to the load too . Somewhere in between there is a 162 Chapter4 • VoltageSags-Characterization 5I': :g 0.6 2 '10.41 ::: .: ell . • C':.'I : , en .,. , 02 b~ o0 \1 --2·0 '"----4,.,.0--·-6 ~0:---~ 8 0---..,1 00 Fault position in kilometers Figure 4.33 Sagmagnitudeversusdistance, for faults on loops (solid anddashedlines) and on a radial feeder (dotted line). maximum magnitudeof the voltage sag due to a fault. The longer the line the higher the maximum . We see from the figure that this maximumis not necessarily in the middle of the branch. The maximum voltage has beencalculatedas a function of the system parameters . The results are shown in Fig. 4.34 and in Fig. 4.35.obtain To thesegraphs (4.18) has been rewritten as a function of ZI = and Z2 = Zt is the relative impedance of the faulted branch and Z2 of the non-faulted bran~h. Figure 4.34 gives the maximum voltage as afunction of Z2 for variousvalues of Zl and Fig. 4.35 theother way around. From both figures it follows that the sags become less severe (higher maximum) when the faultedbranch becomes longer (higherimpedance)and when the non-faulted branch becomesshorter. This can be explained as follows. A longer faulted branchmeansthat the fault can befurther away from both busses. Ashorter non-faultedbranchgivesstrongervoltage supportat the load bus. These relations can easily beunderstoodby consideringa fault in the middleof the faulted branch. The rangeof values used forboth ZI and Z2 is between I and 10.For smaller Larger values do not give realistic valuesof the sagmagnitudebecomes very small. that is proportional to the fault level at thepoint-ofsystems. One has to realize supply. Thus,Z\ and Z2 indicate the variation in fault level for different points in the system. A valueof 10 impliesthat there is at least faactor of six between the highest and the lowest fault level.(Note that the twobranchesareoperatedin parallel.)Such a large ¥ z, ¥; i 2.5 5 7.5 10 Relative impedance of non-faulted branch Figure 4.34 Mostshallow sag for a fault in a loop , as afunction of the impedanceof the non-faulted branchfor various values of the impedanceof the faulted branch. 163 Section 4.2 • Voltage Sag Magnitude Figure 4.35 Most shallow sag for a fault in a loop, as a function of the impedance of the faulted branch, for various values of the impedance of thenon-faultedbranch. 2.5 5 ~5 Relative impedance of faulted branch 10 range in fault level isratherunlikely in subtransmissionsystems, as it will lead to large variationsin voltage due to loadvariations. The generalconclusionfrom Figs. 4.34 and 4.35 is t hat faults on a loop lead to sags with amagnitudewell below 50%,irrespectiveof the voltage levels. Asmentioned ZI = Z2. For these we can before a parallel feeder is a special case of a loop: one in which concludethat the most shallow sag has magnitudebetween a 20% and 30% for most systems. 4.2.4.3 Branches from Loops.W hen a load is fed from a loop, like the ones discussed above, a fault on branch a away from that loop will also cause a sag. In that case it is often possible to model the system as shown in Fig. 4.36. The feeder to the fault does not necessarily have to be a single feeder, but could,represent e.g., the effective impedanceof another loop. The equivalentcircuit for the system in Fig. 4.36 is shown in Fig. 4.37: 21 is the source impedanceat the mainsubtransmission bus; 22 is the impedancebetweenthat bus and the bus from which the load is fed; 2 3 is the impedance between the bus from which the load is fed and the bus from which the fault is fed; 24 and 25 are the impedancesbetween thelatter bus and the main subtransmissionbus and the fault, respectively. The voltage at the load bus is found from Vsag -- ~~+~~+~~+~~ 2 122 + 2,23 + 2\24 + 2 522 + 2 523 + 2 524 + 2 422 + 2 423 Subtransmission Figure 4.36 System with b aranchaway from a loop. (4.19) 164 Chapter4 • Voltage Sags-Characterization Figure4.37 Equivalentcircuit for system with a branchaway from aloop, as in Fig. 4.36. Normally closed Normally open Fault Load Load Figure4.38 Industrial system withbreakerat intermediatevoltagelevel closed (left) and open(right). The sameexpressioncan be used to assess an industrialsystem in which bussplitting is used at anintermediatevoltagelevel. An exampleof the supplyconfigurationin a large industrial network is shown in Fig. 4.38. In the leftexample,two transformersare operatedin parallel. Typically both"transformersfeed into a different part of the substation bus, separatedthrougha circuit breaker.This enablesan uninterruptedsupply after a bus fault. In thenetwork on the right the substationconsistsof two separate busses,typically with a normally open breakerin between. In case the b reakerat an intermediatevoltage level is closed, the sag due to a fault at this voltage level will be experiencedfully by the load. In case thebreakeris open the sag will bemitigated according to (4.19). On the onehand, the source impedancewill be 'Iess when the breakeris open, leading to a deepersag at theintermediatevoltage level. But on the other hand, the sag at theload bus will be less deepthan at the faulted intermediate voltage level. EXAMPLE Considerthe systemshown in Fig. 4.38 with thefollowing voltagesand fault levels: 2500MVA at 66 kV, 500MVA at 11 kV (with the breakerclosed),and 50 MVA at 660 V. When the breakerconnectingthe two 11 kV busses iso pen, the circuit diagram in Fig. 4.37 can be used tocalculatethe sagmagnitudeat the 660 V bus for a fault at an 11kV o f various impedancescan be calculated(all feeder. From the fault levels given, the values referred to I] kV): ZI =0.048(2 Z2=4.75Q Z3 = 4.36Q 2 4 = 0.388(2 Z5 = 0.3 Q/km x £, 165 Section4.2 • Voltage Sag Magnitude Normally open Normally closed Figure 4.39 Sag magnitude versus distance to the fault, for an industrial system with and without bus-splittingapplied to the II kV bus. I 2 3 4 Distanceto the faultinkilometers 5 with £, the distancebetweenthe 11 kV busand the fault, and a feederimpedanceof 0.3 Q/km. When the 11 kV breakeris closed,the systemcan be treatedlike a radial systemwith a source impedanceequal to Z. Z4 and a feederimpedanceequalto Z5' A comparisonbetweenthese two ways of systemoperationis given in Fig. 4.39.Bus-splitting(operatingthe systemwith the 11 kV breaker normally open) clearly limits the influence of 11 kV faults on the load. The improvementis especiallylarge for nearby faults. For faults further away from the 11 kV substationthe effectbecomessmaller.But industrialmedium-voltagesystemsare seldomlargerthan a few kilometers.We will come back to this and other ways of mitigating sagsthrough system design and operationin Chapter7. +! 4.2.4.4 Parallel Operation across Voltage Levels. In many countries the subtransmissionsystem is not fed from thetransmissionsystem at onepoint but at a number of points, resulting in a systemstructuresimilar to the one shown in Fig. 4.40. Thenumberof supply points for the subtransmissionsystem varies from country to country. The 275kV systems in the U.K. are fed like this; also the 130kV sys[23]. tem in Sweden and the 150kV system in Belgium This typeof configurationcan betreatedlike a loop thatextends over two voltage levels.For a fault within the loop we can apply (4.18), for a fault on a feeder away from the loop (4.19) can be used. The equationsremain the same independentof the voltage level at which the fault takes place. The only thing that changes are theimpedance values. Transmission Figure 4.40 Parallel operation of transmission and subtransmission systems. Subtransmission 166 Chapter4 • VoltageSags-Characterization 4.2.5 Voltage Calculations In Meshed Systems When the system becomes more complicatedthan the examples discussed previously, closed expressions for the voltage during the sag get complicatedand very matrix calculations have proven to be unfeasible to handle.F or meshed systems, very efficient for computer-basedanalysis. Thecalculation of the voltagesduring a fault is based on two principles from circuit theory: Thevenin'ssuperpositiontheorem; and the nodeimpedancematrix. Both are discussed in detail in many books on power systems. Here we will only give a brief description. • According to Thevenin'ssuperpositiontheorem voltages and currentsin the systemduring a sag are the sum of two contributions:currentsand voltages before the event, and currentsand voltages due to the change in voltage at the fault position. Currentsand voltages before the fault are due to generators all across the system. Currentsand voltages due to the fault originateat a voltage source at the fault position. Allother voltage sources are considered shortcircuited during the calculationof the latter contribution. • The node impedance matrix Z relates node voltages and node currents: (4.20) V=ZI with V the vector of (complex) node voltages and I the vectorof (complex) node currents.The node voltage is the voltage between a node and the reference node (typicallyground). The nodecurrent is equal to the sumof all currents flowing toward a node. For most nodes the node c urrent is zero according to Kirchhoff's current law. The only exception aregenerator nodes, where the node current is the currentflowing from the generatorinto the system. Considera system withN nodes plus a reference node. The voltages before the fault are denoted as viO). A short-circuit fault occurs at nodef. According to Thevenin'ssuperpositiontheorem we can write the voltageduring the fault at any node k as (4.21) where t:. Vk is the change in voltage at node k due to the fault. Thislatterterm is due to a voltage source -vjO) at the fault position. To calculate VAk all othervoltage sources in the system areshort-circuited,so that nodef is the only node with anon-zeronode current.After using theinformation, (4.20) becomes l:1 Vk = Zkflf At the fault position (k =f) we know that l:1 Vf = - (4.22) vjO) so that V(O) If=_L Zff (4.23) and (4.24) 167 Section 4.2 • Voltage Sag M agnitude The pre-fault voltagesare normally close to unity, so that (4.24) can be approximated by (4.25) The moment the node impedancematrix is known, calculatingsag magnitudes becomesvery easy.The drawbackwith this methodis that the nodeimpedancematrix needs to becalculated.This can be done through a recursive procedurewhere the matrix is updatedfor each new branch added. Alternatively one can first calculate the nodeadmittancematrix from the branchimpedances.T he nodeimpedancematrix is the inverseof the nodeadmittancematrix. EXAMPLE Considerthe circuit diagram shown in Fig. 4.41. Thiscircuit represents a 275/400 kV system, with nodes 1 and representing400 2 kV substations;nodes 3, 4, and 5 representing275 kV substations;the branchesbetween 1 and 3 and betweenand 2 4 representing transformers(the latter two transformersin parallel). The impedancevalues indicated in the figure are inpercentat a 100 MVA base. Figure 4.41 Circuitdiagramrepresentationof part of a 400/275kV system. The node admittancematrix can be built easily from thebranch admittancesor impedances. Anoff-diagonalelement Yk1 of the nodeadmittancematrix is equalto minus the admittanceof the branchbetween nodesk and I. The elementis zero ifthereis no branchbetween these two nodes. Thediagonalelement Ykk equalsthe sumof all admittancesof branchesto node k including any branchbetweennode k and the reference node. For the circuit in Fig. 4.41 this calculationleads to the nodeadmittancematrix y= 2.5719 -0.9091 -0.6211 0 0 -0.9091 4.5981 -1.25 0 0 -0.6211 2.0497 0 -1.4286 0 -1.25 0 0 2.7206 -1.4706 0 -1.4286 -1.4706 2.8992 0 (4.26) The nodeimpedancematrix is obtainedby inverting the nodeadmittancematrix z= y- I = 0.5453 0.1771 0.3889 0.2548 0.3209 0.1771 0.3344 0.2439 0.3012 0.2730 0.3889 0.2439 1.2534 0.6144 0.9292 0.2548 0.3012 0.6144 0.9225 0.7707 0.3209 0.2730 0.9292 0.7707 1.1937 (4.27) The voltage at node 5 due to a fault at node 2 is = Vs = 1 - Z52 = 1 _ 0.2730 0.1836 Z22 0.3344 (4.28) Chapter4 • VoltageSags-Characterization 168 TABLE 4.7 Voltage Sagsin the System Shownin Fig. 4.41 Fault at Node Voltage at Node I 2 3 4 5 2 0 0.6753 0.2869 0.5327 0.4116 0.4704 0 0.2706 0.0993 0.1837 3 0.6897 0.8054 0 0.5098 0.2586 4 0.7238 0.6735 0.3340 0 0.1646 5 0.7312 0.7713 0.2216 0.3544 0 Table 4.7 gives the voltage at any node due to a fault atothernode. any We see, e.g., that for node 5 a fault at node 2 is more severe than a fault at node 1. This understandable is as the source at l. node 2 isstrongerthan the source at node 4.3 VOLTAQE SAG DURATION 4.3.1 Fault-Clearing Time We have seen inSection4.2 that the drop in voltageduring a sag is due to a s hort circuit being presentin the system. Themomentthe short-circuitfault is clearedby the protection,the voltagecan return to its original value. Thedurationof a sag ismainly determinedby the fault-clearingtime, but it may belongerthan the fault-clearingtime. We will come back to thisfurther on in this section. Generallyspeakingfaults in transmissionsystems arecleared fasterthanfaults in distribution systems. Intransmissionsystems thecritical fault-clearing time is rather small. Thus, fast protectionand fast circuit breakersare essential.Also transmission and subtransmissionsystems arenormally operatedas a grid,requiring distanceprotection or differential protection,both of which are ratherfast. The principal form of protectionin distribution systems isovercurrentprotection.This requiresoften some time-gradingwhich increasesthe fault-clearingtime. An exceptionare systems in which current-limiting fuses are used.Thesehave theability to clear afault within one halfcycle [6], [7]. An overview of the fault-clearing time of various protectivedevices is given in reference [8]. • • • • • • • current-limiting fuses: lessthan one cycle expulsionfuses: 10-1000 ms distancerelay with fast breaker:50-100ms distancerelay in zone 1:100-200ms distancerelay in zone 2:200-500ms differential relay: 100-300ms overcurrentrelay: 200-2000ms Some typicalfault-clearingtimes atvariousvoltagelevels for a U.S. utility are given in. reference [9]. Section4.3 I Voltage Sag Duration Voltage Level 525 kV 345 kV 230 kV 115 kV 69 kV 34.5 kV 12.47 kV 169 Best Case 33 ms 50 ms 50 ms 83 ms 50 ms 100 ms 100 ms Typical 50 ms 67 ms 83 ms 83 ms 83 ms 2 sec 2 sec Worse Case 83 ms 100 ms 133 ms 167 ms 167 ms 3 sec 3 sec From this list it becomesclear that the sag duration will be longer when a sag originates at a lower voltage level. Many utilities operatetheir distribution feedersin such a way that most faults are clearedwithin a few cycles. Such a way of operation was discussed in detail in Chapter 3. But even for those feeders,a certain percentageof faults will lead to long sags. The difference between the two ways of operation is discussedin more detail in Section 7.1.3. 4.3.2 Magnitude-Duration Plots Knowing the magnitude and duration of a voltage sag, it can be presentedby a point in a magnitude-durationplane. This way of sag characterizationhas been shown to be extremely useful for various types of studies. We will use it in forthcoming chaptersto describeboth equipmentand systemperformance.Various types of magnitude-durationplots will be discussedin Section 6.2. The magnitude-durationplot will also be usedin Chapter 6 to presentthe results of power quality surveys.An exampleof a magnitude-durationplot is shown in Fig. 4.42. The numbersin Fig. 4.42 refer to the following sag origins: 1. 2. 3. 4. 5. 6. Transmissionsystem faults Remote distribution system faults Local distribution system faults Starting of large motors Short interruptions Fuses Consider the general system configuration shown in Fig. 4.43. A short-circuit fault in the local distribution network will typically lead to a rather deep sag. This is lOO% 80% 0% Figure 4.42 Sags of different origin in a magnitude-duration plot. 0.1s ,,7--- Is Duration 170 Chapter4 • VoltageSags-Characterization Transmission network Remote distribution network Local distribution network Figure 4.43 Generalstructureof power system, withdistribution and transmission networks. Load due to the limitedlength of distribution feeders. When the fault occurs in remote a distribution network, the sag will be much moreshallowdue to thetransformerimpeFor a fault in anydistribution network, the sag dancebetween the fault and the pee. durationmay be up to a few seconds. Transmissionsystem faults are typically cleared within 50 to 100rns, thus leading to short-durationsags.Current-limitingfuses lead to· sag d urationsof one cycle or less, and rather deep sags if the fault is in the local distribution or low-voltage network. Faultsin remotenetworks,clearedby current-limitingfuses, lead toshortand shallow m otor sags,not indicatedin the figure. Finally the figurecontainsvoltage sags due to starting,shallowand long duration(see Section 4.9)and shortinterruptions,deep and long duration(seeChapter3). 4.3.3 Measurement of Sag Duration Measurementof sag duration is much less trivialthan it might appearfrom the previoussection. For a sag like in Fig. 4.1 it isobvious that the duration is about 2! cycles.However, to come up with anautomaticway for a power quality monitor to obtain the sagduration is no longer straightforward,A commonly useddefinition of sag duration is the numberof cycles during which the rms voltage is below a given threshold.This thresholdwill be somewhatdifferent for eachmonitor but typical values are around 900/0. A power quality monitor will typically calculatethe rms value once every cycle. This gives an overestimationof the sagdurationasshownin Fig. 4.44. The t t f Calculated rmsvalues X X Calculation interval ,,, I I ~ I Calculation instants Figure 4.44 Estimationof sag duration by power quality monitor for a two-cycle sag: overestimationby one cycle(uppergraph); correctestimation(lower graph). 171 Section 4.3 • Voltage Sag D uration normal situation is shown in theupper figure. The rmscalculation is performedat regular instants in time and the voltage sag starts somewhere in between two of thoseinstants.As there is nocorrelationbetween thecalculationinstantsand the sag commencement,this is the most likelysituation.We seethat the rms value is low for three samples in a row. The sag durationaccordingto the monitor will be three cycles. Here it is assumedthat the sag is deepenoughfor the intermediaterms value to be below the threshold. For shallow sagsboth intermediatevalues might beabove the thresholdand themonitor will record a one-cycle sag. The bottom curve of Fig. 4.44 shows the raresituationwhere the sagcommencement almostcoincides with one of the instantson which the rms voltage iscalculated.In that case themonitor gives the correctsagduration. Calculating the rms voltage once a· cycle, it is obvious that the resulting sag durationwill be an integernumberof cycles.For a 2!-cycle sag thecomputedduration will be either two or three cycles. But even when a sliding window is used calculate to the rms voltage as faunction of time, anerroneoussagdurationmight result. To show of this possibleerror for a measuredsag, we haveplottedin Fig. 4.45 the half-cycle rms the sag shown in Fig. 4.1, togetherwith the absolutevalueof the measuredvoltage. The "actual sag duration" obtainedfrom the suddendrop and rise in the voltage is 2.4 d urationwill be an overestimation.A 90% cycles.For largethresholdsthe recorded sag thresholdgives a 2.8 cycle sag d uration,and 80% thresholda 2.5 cyclesduration. For lower thresholdsthe recorded sagduration is an underestimation:a 60% threshold gives a 2.1 cycledurationand a400/0 thresholda 2.0 cycleduration.In reality, thresholds this low willnot be used, but the same effect will be obtainedwhen thedepthof the sag is varied and the thresholdis kept constant.The durationof deep sags will be overestimated,and thedurationof shallow onesunderestimated. As the shortest-durationwindow for calculatingthe sagmagnitudeis one halfcycle, an error up to one half-cycle must be accepted. Several methodshave been suggested tomeasuresaginitiation and voltage recovery more accurately.These methods also give a moreaccuratevalue of sag duration [134], [201], [202]. Using the fundamentalvoltage componentresults in a similartransition betweenpre-sagand during-sagvoltage, thus similarerrorsin sagduration. Using the half-cycle peak voltage will give a muchsharpertransition,as long as sag initiation and voltage recovery are close to voltagemaximum.Saginitiation and voltage recoverya roundthe voltage zero-crossingwill give a smoothertransitionand a largeruncertainlyin sagduration. 1.2r - - - - r - - - - , - - - - - - - , - - - - - - - r - - - r - - - - - , I '~I I " , I' " ,'~ I I, Q.. ' ..... I ' I ' , I II I , II I , I " I I I ~ :: 04 I I t • ;:' I I " r, ,f """ 0.2 L .: ~, Figure 4.45 Half-cycle rms voltage together with absolutevalue of the voltage(dashed line) of the sag shown inFig. 4.1. ~ I I I I I I : ,I I ,I ' " ,I • " " " " ,, " " I " " " " I I " " ,, , "I, ",I " " " "~ , I • I I I " " " ' " It' , I \, I .1 :I~: II I , I' ,,' " : ,\'l\:II,: oU o i I' I : :: : , I ,, ' :'::: 1 I " I I ," , ,1 I I I ,", '. /. I , ~ 0.6' :: ::: S r I ;'~ " " " 't : : =' 0.8 :: I s:: ",'\ ,\ '~. " I I I I I I I " " I ~ _---a....'_'-L..---L.~--...L--___L_:..____:._...:.J._l.___U.__---L-__:.J 1 234 Timein cycles 5 6 172 Chapter 4 • VoltageSags-Characterization The above-mentionederror in sagduration is only significant forshort-duration sags.For longer sags it does not really matter. But for longer sags the so-called postfault sag will give a seriousuncertaintyin sagduration. When the fault is cleared the voltage does not recover immediately. Some of this effect can be seen in Fig. 4.3 and Fig. 4.4. The rms voltage after the sag is slightly lower than before the sag. The effect can be especially severe for sags due to three-phase faults.explanationfor The this effect is as follows[17], [18]. Due to thedrop in voltage during the sag,induction motors will slow down. The torqueproducedby an induction motor is proportional to the squareof the voltage, so even rathersmall a drop in voltage can already produce a large drop intorque and thus in speed. The moment the fault is cleared and the voltage comes back, the induction motorsstart to draw a largecurrent:up to 10 times their nominalcurrent.Immediately after the sag, the air-gap field will have to be built up again . Inother words, theinduction motor behaves like ashort-circuitedtransformer. After the flux has come back into the air gap, motor the can start re-accelerating which also requires aratherlargecurrent. It is this post-faultinrush currentof induction motorswhich leads to an extended sag. The post-fault sag can last several seconds, much longer than the actual sag. Such apost-faultsag will causeuncertaintyin the sagdurationas obtainedby a power quality monitor: different monitors can give different results. This is shown schematically in Fig. 4.46. Assume that monitor I has a setting as indicated, and monitor 2 a slightly higher setting. Bothmonitors will record a sagduration much longer than the fault-clearing time. The fault-clearing time canestimated be from the duration of the deeppart of the sag. We see t hat monitor 2 will record a significantly longer duration than monitor 1. A measured sag with a long post-faultcomponentis shown in Fig. 4.47. The three phases are shown in the same figurebetterindicate to thepost-faultvoltage sag. Note that the sag isunbalancedduring the fault, but balanced after the fault. The rms voltage versus time for the sag shown in Fig. 4.47 plottedin is Fig. 4.48. We see a largedrop in voltage in two phases and a small one in third the phase. The fault-clearing time isabout four cycles; the fault leading to this sag took place at 132kV, the voltages were measured at II kV. The sag duration has been determined as the timeduring which the rms voltage is belowcertainthreshold a . Figure 4.49 plots of the phases only this durationas a function of thethreshold,for the three phases. One drops to 88% sothat any thresholdsetting below 88% will give zero sag durationfor that phase . The sag durationobtainedfor the other two phases isa boutfour cycles for thresholds below 90% , increasing fast for higher threshold settings. Duration monitor 1 Duratio n monitor 2 Time Figure 4.46 Error in sag durationdue to post-fault sag. Section 4.3 • 173 Voltage SagDu ration 0.5 o -0.5 - IL Figure4.47 Measuredsagwith a clear postfault component(Data obtainedfrom ScottishPower.) o 6- ~----:'=-----;';=---' 5 15 10 Timein cycles 0.8 .S ll> ;> 0.6 ~ en ~ 0.4 0.2 5 Figure 4.48 The rms voltagesversustime for the sagshownin Fig. 4.47. 15 10 Timein cycles 12 10 c: 0 'p ~eo oS '" -e ~ e .~ 8 6 4 \l.l 2 Figure 4.49 Sagdurationversusthreshold settingfor the threephasesof the sagshown in Figs. 4.47 and 4.48. 0 0.8 0.85 0.9 Thresholdin pu 0.95 Chapter 4 • VoltageSags-Characterization 174 4.4 THREE-PHASE UNBALANCE The analysisof sag magnitudepresentedin the previous sectionsconsidersonly one phase.For example, the voltage divider model in Fig. 4.14 was introducedfor threevalues. But phase faults: theimpedancesused inthat figure are thepositive-sequence most shortcircuits in powersystems are single phase or two phase.that In case we need to take all three phases into accountor use thesymmetricalcomponenttheory. A good and detaileddescriptionof the useof symmetricalcomponentstheory for the analysis of non-symmetricalfaults is given in reference [24] and in several otherbooks on power of the theory to system analysis and not is repeatedhere. We will only use the results calculatethe voltages in the three phases due to non-symmetrical a s hort circuit. For non-symmetricalfaults the voltage divider in Fig. 4.14 can still be used but it has to be split into its threecomponents:a positive-sequencenetwork, a negativesequencenetwork, and azero-sequencenetwork. The threecomponentnetworksare shown in Fig. 4.50, whereVI, V2, and Vo representpositive-, negative-, and zerosequence voltage, respectively, at the pee; ZSb ZS2' and Zso are the source impedance values andZFt, ZF2, and ZFO the feederimpedancevalues in the threecomponents.The three componentsof the fault current are denotedby I., 12 , and 10 , The positivesequence source denotedby is E. Thereis no source in the negative and zero-sequence networks. The threecomponentnetworks have to beconnectedinto one equivalent circuit at the faultposition.The connectionof the componentnetworksdependson the fault type. For a three-phasefault all threenetworksare shortedat the fault position. This leads to thestandardvoltage divider model for the positive sequence, and zero voltage andcurrentfor the negative and zero sequences. 4.4.1 Single-Phase Faults For a single-phasefault, the threenetworksshown in Fig. 4.50should be connected in series at the fault position. The resulting circuit for a single-phase fault in E Figure 4.50 Positive- (top), negative- (center), and zero-(bottom)sequence networks for the voltage divider shown in Fig. 4.14. 175 Section 4.4 • Three-Phase Unbalance F~gure 4.51 Equivalent circuit for a singlephase fault. phasea, isshownin Fig. 4.51.Ifwe againmakeE = 1, like in the single-phasemodelin Fig. 4.14, thefollowing expressionsare obtainedfor the componentvoltagesat the pee: VI = ZFI (2F I + ZS2 + ZF2 + Zso+ ZFO + ZF2 + 2 FO) + (2s1 + ZS2 + 2 so) (4.29) (4.30) (4.31) The voltagesin the threephasesat the peeduring the fault are obtainedby transforming back from sequencedomain to phasedomain: = VI + V2 + Vo 2 Vb = a VI + aV2 + Vo Va Vc = aVI (4.32) + a2 V2 + Vo For the faulted phasevoltage Va we get Va = ZFI (2F t + Zn + ZFO + ZF2 + ZFO) + (ZSI + ZS2 + ZSO) (4.33) We can obtain the original voltagedivider equation(4.9) by defining 2 F = 2 F l + ZF2 + ZFO and Zs = ZSl + ZS2 + Zso.Thus,the voltagedivider modelof Fig. 4.14and (4.9) still holds for single-phasefaults. The condition thereby is that the resulting voltage is the voltage in the faulted phase,and that the impedancevalues used are the sumof the positive-,negative-,andzero-sequence i mpedances.F rom(4.29) through (4.32) wecan calculatethe voltagesin the non-faultedphases,which resultsinto the following expressionsfor the three voltages: Chapter4 • VoltageSags-Characterization 176 Va = 1 _ Vb = a2 _ ZSI +ZS2 (2 F1 + 2 F2 + 2 FO) +ZSO + (2S 1+ ZS2 + ZSO) 2 + aZS2 + Zso + ZF2 + 2 FO) + (ZSI + ZS2 + ZSO) 2ZS2 aZSI + a + Zso (2 F1 + ZF2 + ZFO) + (2 S 1+ ZS2 + 2 so) a ZSI (4.34) (ZFl V c =a _ Note that the expressionfor Va has been slightlyrewritten to explicitly obtain the voltagedrop as aseparateterm. Thesevoltagesare shownas aphasordiagramin Fig. 4.52. The voltagedrop in the non-faultedphasesconsistsof three terms: s ourceimpedance,a long • a voltagedrop proportionalto the positive-sequence the direction of the pre-fault voltage. sourceimpedance,a long • a voltagedrop proportionalto the negative-sequence the direction of the pre-fault voltagein the other non-faultedphase. s ourceimpedance,a long the • a voltagedrop proportionalto the zero-sequence direction of the pre-fault voltagein the faulted phase. - a2ZS2 -aZsl -zso \..\ \\Vc \ Figure 4.52 Phaseto-groundvoltagesduring a single-phasefault. The voltage between the twonon-faultedphasesis (4.35) We seethat the changein this voltage is only due to thedifferencebetweenpositivesourceimpedances.As these two arenormally about sequenceand negative-sequence equal, the voltage betweenthe non-faultedphasesis normally not influenced by the fault. Below we will simplify the expressions(4.34) and (4.35) for two cases: • Positive-, negative-,and zero-sequence s ourceimpedancesare equal. • Positive- and negative-sequence sourceand feeder impedancesare equal. 177 Section 4.4 • Three-Phase Unbalance 4.4.1.1Solidly-GroundedSystems. In a solidly-grounded system, the source impedances in the three sequence componentsare oftenaboutequal. The three voltage drops in thenon-faultedphases now cancel, resulting in the following voltages during the fault: _ _ Va - 1 3(ZFl ZSl + ZF2 + ZFO) + ZSI 2 Vb = a (4.36) Vc =a The voltage in the faulted phase is the same as during a three-phase fault, the voltages in the non-faultedphase are not affected. 4.4.1.2 Impedance-GroundedSystems. In a resistance or high-impedance groundedsystem, the zero-sequence source impedance differs significantly from the positive and negative-sequence source impedances. We can, however, assume that the latter two are equal. Also in systems where the source impedance consists for a large part of line or cable impedances (e.g., in transmission systems) positive- and zero-sequence impedances can be significantly different. The resulting expressions for the voltages at the pee during a single-phase fault are, when ZSI = ZS2 and ZFl = ZF2: Va = 1 _ Vb = a2 _ V c =a _ Zso+ 2Zs1 (2Z F1 + 2 FO) (2ZFJ + (2ZS1 + ZSO) ZSO - 22s 1 + ZFQ) + (2Zs1 + Zso) (4.37) Zso - 2Zs1 (22F1 + ZFO) + (22s 1 + ZSO) The voltagedrop in .the non-faultedphases onlycontainsa zero-sequence component (it is the same inboth phases). We will see later that the zero-sequence componentof the voltage is rarely ofimportancefor the voltage sag as experienced equipment at terminals. Sags at the same voltage level asequipment the terminals are rare.During the transfer of the sag down to lower voltage levels, the transformersnormally block the zero-sequence componentof the voltage. Even if the fault occurs at the same voltage level as the equipment terminals, the equipmentis normally connected in delta so it will not notice the zero-sequence componentof the voltage. Thus the voltage drop in the non-faultedphases is not ofimportancefrom an equipmentpoint of view. We can therefore add a zero-sequence voltage to (4.37) such that the voltagedrop in the nonfaulted phases disappears. The resulting expressions are va, -- Va+ Zso - ZSl _ 1_ (22F 1 + ZFO) + (2Z S1 + 2 so) (2Z F l n= Vb + (2Z ZSO - ZSl F 1 + 2 FO) + (22s 1 + 2 so) = a2 3ZS1 + 2 FO) + (22s 1 + ZSO) (4 38) · ZSO -ZSI , V vc= c+ (2Z + ZFO) + (2Z + Zso) =a Ft S1 The expression for the voltage in the faulted phase is somewhat rewritten, to enable a comparisonwith (4.36): (4.39) 178 Chapter4 • VoltageSags-Characterization E Neutral point Figure 4.53Three-phasevoltage divider model. The denominatorcontainsan additional term !(Zso - 2 S1) comparedto (4.36). This can beinterpretedas anadditionalimpedancebetween the pee a nd the fault. When this > ZSI, the sag becomes more shallow. In resisimpedanceis positive, thus when Zso tance and reactance-groundedsystems, Zso» ZSl' so that even a terminal fault, ZFI + ZF2 + ZFO = 0, will lead to ashallow sag. Note that in solidly-groundedsystems, thezero-sequence sourceimpedancemay be lessthan the positive-sequence one, Zso < ZSl' so that the additionalimpedanceis negative.For nearbyfaults, we will thus obtain a negativevoltage All this might look like a mathematicaltrick to get rid of the voltagedrop in the non-faultedphases.T hereis, however, some physical significance to this. To show this, the three-phasevoltage divider is drawn in a commonly used way [24] in Fig. 4.53. From this model we cancalculatethe phase-to-neutralvoltages at the pee; with E= 1 the calculationresultsinto V-I _ 3ZS 1 an (2Z F 1 + ZFO) + (2ZS 1 + 2 so) (4.40) 2 Vbn = a V;. Vcn =a The correspondence between (4.40)a nd (4.38) isobvious. The voltages in (4.38) thus correspondto thephase-to-neutralvoltages.Note that the "neutral" in Fig. 4.53 is not a physicalneutralbut a kind of mathematicalneutral.In resistance-or high-impedancegroundedsystems the physical neutral(Le., thestarpoint of the transformer)is a good approximationof this "mathematicaln eutral."The expressionsderived not only hold for resistance-grounded systems, but for each system in which we can assume positive- andnegative-sequence impedancesequal. EXAMPLE Consider again the system shown in Fig. 4.21, and assume that a singlephase fault occurs on one of the 132 kV feeders. The 132 kV system is solidly grounded, therefore the positive- and zero-sequence source impedances are similar. For the feeders, the zerosequence impedance is about twice the positive- and negative- sequence impedance. Positiveand negative-sequence impedance are assumed equal. ZSI = ZS2 = 0.09+j2.86% Zso = 0.047+ j2.75°A> ZFt = ZF2 = 0.101 + jO.257°A>/km ZFO = 0.23+ jO.65°A>/km 179 Section 4.4 • Three-Phase Unbalance 0.8 Single-phasefault Three-phasefault Figure 4.54 Voltage in the faulted phase for single-phase and three-phase faults on a 132 kV feeder in Fig. 4.21. 10 20 30 40 50 Distanceto the fault inkilometers By using the above-given equations, the voltages in the three phases have been calculated for single-phase as well as for three-phase faults. The results for the faulted phase are shown in Fig. 4.54. The difference is mainly due to the difference in feeder impedance. Note that it is assumed here that the feeders are at least 50km long, where they are in reality only 2 km long. The zerosequence feeder impedance increases faster than the positive-sequenceimpedance, with increasing distance to the fault. Therefore single-phase faults lead to slightly smaller voltage drops than three-phase faults. As we saw from the equations above, it is the average of the three sequence impedances which determines the voltage drop due to single-phase faults. The voltages in the nonfaulted phases showed only a very small change due to the single-phase fault. EXAMPLE The voltages due to single-phase faults have been calculated for the II kV system in Fig.4.21. As this system is resistance grounded, the zero-sequence source impe- dance is considerably larger than the positive-sequence impedance. ZSI = ZS2 = 4.94+ j65.9 % Zso= 787+ j220% = 9.7 +j26%/km ZFI = ZFO = 18.4+ jI12 % / k m ZF2 Note the large zero-sequence source impedance, especially its resistive part. The voltage in the faulted phase for three-phase and single-phase faults is shown in Fig. 4.55 as a function of the distance to the fault. The larger source impedance for single-phase faults more than compensates the larger feeder impedance, which makes that single-phase faults cause deeper sags than threephase faults. In a solidly-groundedsystem the voltage in a non-faultedphase staysabout the sameduring a single-phasefault. In a resistance-grounded system the voltage in the and 4.57. Figure 4.56 non-faultedphases increases. This effect is shown in Figs. 4.56 p ath of the shows the voltagemagnitudeversusdistanceto the fault and Fig. 4.57 the voltages in the complex plane. The circles and arrowsindicatethe the complex voltages during normaloperation.The curvesindicate the path of the complex voltages with varyingdistanceto the fault. Where thefaulted phase shows d arop in voltage, the nonof faulted phases show a large increase in voltage, for one phaseincreasing170% even the nominal voltage. From Fig. 4.57 we seethat all three voltages are shifted over a Chapter 4 • VoltageS ags-Characterization 180 0.8 Three-phasefault [ .S Single-phasefault .s 0.6 ·1 ~ 0.4 f tI) 0.2 Figure 4.55 Voltage in the faulted phase for 20 single-phaseand three-phase faults on11an kV feeder in Fig. 4.21. 5 10 15 Distanceto the fault inkilometers 1.8,..-----r------.,..-------r------, 1.6 ~ 1.4 .S 1.2 t Non-faultedphases E 0.8 «) I 0.6 Faultedphase '0 :> 0.4 0.2 0 0 5 10 15 Distanceto the fault in kilometers Figure 4.56 Voltage in the faulted and nonfaulted phases for a single-phase fault on an 20 11 kV feeder in Fig. 4.21, as a function of the distance to the fault. 1.5...---....---........-----.----r----r----r-------. , ~,. «) ~ <a 1\ , \ \ \ 0.5 \ i ~ ·st , \ \~ 0 I .> I , I E I ....-0.5 / -1 '---___'___ _- ' - - _ - . . I_ _---'-_ _- ' - - ' _ - - - ' _ - - - - J -1.5 -1 -0.5 0 0.5 Realpart of voltage Figure 4.57 Complex voltages due to a fault on an 11 kV feeder in Fig. 4.21. 181 Section 4.4 • Three-PhaseUnbalance similar distance in the complex plane. The effect of this commonshift (a zero-sequence component)is that the phase-to-phase voltages do not change much. The phase-to-phase voltages have been calculated from the complex phase voltagesby using the following expressions: v _ Va - Vb .J3 ab - Vb - Vc (4.41) = .J3 VIn· _ V - Va Vca - c.J3 The factor .J3 is needed to ensure that the pre-fault phase-to-phase voltages are 1 pu. The resulting voltagemagnitudesare shown in Fig. 4.58: note the difference in vertical scalecomparedto the previous figures. We see that the phase-to-phase voltages are not much influencedby single-phase faults. The lowest voltage magnitudeis 89°/0, the highest 101°/0. Figure 4.59comparesphase-to-ground voltage, according to (4.37), and phase-toneutralvoltage,accordingto (4.40). We see t hat the drop in phase-to-neutralvoltage is 1.05r - - - - - , - - - - - - r - - - - - - . - - - - - - - , a .8 QJ ~ .~ 0.95 e j ~ Figure 4.58Phase-to-phase voltages due to a single-phase fault on an II kV feeder in Fig. 4.21, as a function of the distance to the fault. 0.9 0.85 0 5 10 15 20 Distanceto the fault inkilometers 1'-- - 0.8 a .8 ~ 0.6 .~ t 0.4 e / / I I f I ,, I (/) ,, 0.2 , , , Figure 4.59Phase-to-ground(dashed) and phase-to-neutral (solid) voltages due to singlephase faults on an II kV feeder in Fig. 4.21. I 5 10 15 Distanceto the fault inkilometers 20 182 Chapter4 • VoltageSags-Characterization very small. As explained before, this is due to the large zero-sequence source impedance. Also notethat the lowestphase-to-neutral voltage occurs for anon-zerodistance to the fault. 4.4.2 Phase-to-Phas. Faults For a phase-to-phase fault the positive- and negative-sequence networksare connected in parallel, as shown in Fig. 4.60. The zero-sequence voltages currentsare and zero for aphase-to-phase fault. E Figure 4.60 Equivalent circuit for a phase-tophase fault. The sequence voltages at the pee are =E-E VI ZSI (ZSl V 2- + 2 S2) + (2£1 + 2£2) ZS2 (4.42) (ZSI + ZS2)+ (Z£I + Z£2) Vo =0 The phase voltages can be found from (4.42) by using (4.32). This results in the following expressions, again with E = 1: Va = 1 _ ZSI - ZS2 (ZSl V 2 b V C =a =a _ + ZS2)+ (2 F1 + 2£2) a 2ZS1 - aZS2 (2s1 + ZS2)+ (2F1 + 2 F2) (4.43) 2ZS2 aZSI - a (ZSI + ZS2) + (2 F t + 2£2) In thecalculationof the componentvoltages andcurrents,it has been assumed that the fault is between the phases bandc. Thus a is thenon-faultedphase, andbandc are the 183 Section 4.4 • Three-Phase Unbalance faulted phases.F rom (4.43) we seethat the voltagedrop in the non-faulted phase depends onthe difference between the positive and negative-sequence source impedances. As these are normally equal, the voltage in the non-faultedphase will not be influenced by the phase-to-phasefault. Under the assumption, ZSI = ZS2 (4.43) becomes Va = 1 Vb = a2 _ 2 (a - a)Zsl 22s 1 + 2ZF1 (4.44) (a2 - a)Zsl Vc=a+----- 2Zs 1 +2ZF 1 We seethat the voltagedrop in the faulted phases is equal magnitude in 2Z z;~z but opposite in direction. The direction in which the two phase voltages drop iss~loJg the Vb - VC • pre-fault phase-to-phase voltage between the faulted phases, From (4.43) we can derive the following expression for the voltage between the faulted phases Vb - Vc = (ZSI ZFI + ZF2 (a2 + ZS2) + (ZFI + ZF2) a) (4.45) When we realizethat (a2 - a) is the pre-fault voltage between the two faulted phases, the resemblance with the single-phase voltage divider of Fig. 4.14 and (4.9) becomes immediately clear.t he same expressions as for the three-phasefault can be used, but for the voltages between the faulted phases; the impedances in the expression are the sum of positive and negative sequence values. faults on one of the 33 kV feeders in the system EXAMPLE Considerphase-to-phase shown in Fig. 4.21. The impedance values needed to calculate the voltages during a phase-tophase fault are as follows: ZSI ZFl = ZS2 = 1.23+j18.3% = ZF2 = 1.435+ j3.l02 %/km The resulting complex voltages are shown in Fig. 4.61. The circles and the arrows indicate the prefault voltages; the cross indicates the voltages in the faulted phases for a fault at the 33 kV bus. , ,, I',' . u , , 0.5 ,, ,, ~ ~ o i ,, , \------------~~_:.o , .. ,, 0 .i I I I ~-0.5 I I I I • I I, 1/// -1 "--------'---_ _--'---_ _ -1 -0.5 0 0.5 ....L-- Figure 4.61Complex voltages due to a phaseto-phase fault (solid line). Realpart of voltage -..J Chapter4 • VoltageSags-Characterization 184 We see how the voltages in the two faulted phases move towardeach other. Thedeviationof their path from astraight line is due to the difference in X /R ratio between source and feeder impedance. This is a subject to be discussedfurther in detail in Section 4.5. 4.4.3 Two-Phase-to-Ground Faults Single-phaseand phase-to-phase faults have beendiscussedin the two previous sections.The only asymmetricalf ault type remainingis the two-phase-to-groundfault. For a two-phase-to-ground f ault the threesequencenetworksare connectedin parallel, as shown in Fig. 4.62. It isagain possibleto calculatecomponentvoltagesand from thesecalculatevoltagesin the threephasesin the sameway asdonefor the single-phase and phase-to-phase faults. The sequencevoltagesat the pee for afault betweenphasesbandc and ground are given by thefollowing expressions: VI = 1 _ ZSI (Zso + ZFO + ZS2+ ZF2) D V = ZS2(ZSO+ ZFO) 2 D· V ZSO(ZS2+ ZF2) o D (4.46) = with (4.47) From (4.46) it is possibleto calculatethe phase-to-groundvoltagesin the threephases V-I + a- V h- V _ l' 2 a (2 S2 - 2 S1)(2so + 2 FO) D + -a+ (aZS2- ~ZSI)ZO D + (2so - 2 SI)(2s 2 + 2 F2) D 2ZSI)Z2 (ZSO - a + D (4.48) 2ZS2 (a - aZsl)Zo (Zso - aZSI)Z2 D + D E Figure 4.62 Equivalent circuit for a twophase-to-groundfault. 18S Section 4.4 • Three-PhaseUnbalance There are two effects which causechangein a voltage in thenon-faultedphase(Va): the difference between the positive- and the negative-sequence sourceimpedance;and the difference between the positive- and the zero-sequence source impedance . For both effects the non-faulted phase voltagedrops when the positive-sequenceimpedance increases. Negative- and positive-sequenceimpedanceare normally rather close, so that the second term in (4.48) may be neglected. The third term, which dependson the difference between zero- and positive-sequencesource impedance,could cause a seriouschangein voltage. As thezero-sequence sourceimpedanceis often largerthan the positive-sequenceone, we expect a rise in voltage in the non-faultedphase. Like with single-phasefaults we caneliminate this term by consideringphase-to-neutral voltagesinsteadof phase-to-groundvoltages . Looking at the voltages in the faulted phases and realizing that ZSI is close toZS2 we seethat the second term is a voltage drop in the directionof the otherfaulted phase; 2 (a - a ) is the pre-fault voltage between the faulted phases For . Zso = ZSI the third term in (4.48) is a voltagedrop towards the non-faultedphase pre-fault voltage, for Zso « ZSI the third term is adrop along the positive real axis, as shown in Fig. 4.63. The voltagedrop accordingto A in Fig. 4.63 is the same d rop as for aphase-to-phase fault. The ground-connectioncauses anadditional drop in the voltage in the two t hat all faulted phases,somewherein betweendirectionsBand C. It is assumed here impedanceshave the sameX/R ratio. . · \· · B ~ A~ ~ -. -. B·· . Figure 4.63 Voltage drops in the faulted phase during atwo-phase-to-groundfault. A: second term in (4.48); B: third term for ZSI = Zso;C: third term for ZSI « Zso. As said before, positive- andnegative-sequence impedancesare normally very close. In that case we can simplify the expressions substituting by ZSI = ZS2 and ZFt ZF2' But when we are onlyinterestedin phase-to-neutralvoltages it is easier to use thethree-phasevoltage divider modelintroducedin Fig. 4.53 for single-phase faults . For two-phase-to-groundfaults theequivalentcircuit is redrawnin Fig. 4.64. Without any further calculation we can see from Fig. 4.64 t hat the phase-toneutralvoltage in thenon-faultedphase is not influenced by the two-phase-to-ground fault. The phase-to-neutralvoltage at the faultpoint, VFN, is found from applying Kirchhoff's current law to the fault point: = 2 a - V FIV ------~ + ZSI+ZFt a - VFN V FN . =J I ZSJ-ZFI 3(Zso-Zsd+ (4.49) 3(ZFO-ZFI) Solving (4.49) leads to the following expression for the voltage at the fault point: V FN = _ (Zso + ZFO) - (ZSI + ZFt) 2(Zso + ZFO) + (ZSI + ZFI) (4.50) 186 Chapter 4 • VoltageSags-Characterization E 4----------- VF -: Figure 4.64 Three-phasevoltagedivider model for a two-phase-to-groundfault. If zero-sequenceand positive-sequenceimpedances are equal, Zso = ZSI and 2 FO = 2 F J, we find that (4.51) If the zero-sequence i mpedancebecomeslarge, like in aresistance-grounded system,the fault-point voltageis r 1 2 VF~ =-- (4.52) The latter expressioncorrespondsto the expressionobtainedfor phase-to-phase faults. This isratherobviousif we realizethat a largezero-sequence i mpedanceimplies that the fault currentthrough the earthreturn is very small.Thus, the presenceof a connection with earthduring the fault does not influence thevoltages. Pathof Vcn Pathof Vbn Figure 4.6~ Phase-to-neutralvoltagesin the faulted phasesfor a two-phase-to-ground fault. 187 Section 4.4 • Three-PhaseUnbalance The intermediatecase, whereZSI < Zso < somewhere in between these two extremes: 00, gives a voltage at the faultpoint 1 2 (4.53) - - < VFN < 0 This voltage and theresultingvoltages at the pee can be obtainedfrom Fig. 4.65. The the former for voltage at the faultp oint is locatedbetween the origin and the point equal positive- negative-, and zero-sequence impedances,the latter for very large zerosequenceimpedance.The voltage at the pee for a faulted phasesomewhere is between the voltage at the faultp oint and thepre-fault voltage in that phase. This knowledge o f three-phaseunbalancedsags.For calculating will later be used for the classification sagmagnitudesthis constructionis not of practicaluse, as thefault-to-neutralvoltage VFN dependson the fault position. -!: 4.4.4 Seven Types of Three-Phase Unbalanced Sags The voltage sags due to the various types of faults have been discussed in the previous sections:three-phasefaults in Section 4.2, single-phase faults in Section 4.4.1, phase-to-phase faults in Section 4.4.2, and finally two-phase-to-ground faults in Section 4.4.3.For each typeof fault, expressionshave been derived for the voltages at the pee. But as alreadymentioned,this voltage is not equal to the voltage at the equipment terminals. Equipmentis normally connectedat a lower voltage levelthan the level at which the fault occurs. The voltages at the equipmentterminals, therefore,not only but also on the windingconnectionof the transfordependon the voltages at the pee and the equipmentterminals. The voltages at theequipment mers between the pee terminalsfurther dependon the loadconnection.Three-phaseload is normally connected in delta butstar-connectionis also used.Single-phaseload isnormallyconnected in star (i.e., between onephaseand neutral) but sometimes indelta (between two phases).Note that we considerhere the voltage sag as experienced at terminals the of end-userequipment,not the voltage asmeasuredby monitoring equipment.The latter is typically locatedat distribution or even attransmissionlevel. In this section we will derive a classification for three-phaseunbalancedvoltage sags, based on the following assumptions: • Positive- andnegative-sequence impedancesare identical. • The zero-sequence c omponentof the voltage does notpropagatedown to the equipmentterminals,so that we can considerphase-to-neutralvoltages. • Load currents,before, during, and after the fault, can be neglected. 4.4.4.1 Single-Phase Faults.The phase-to-neutralvoltages due to a singlephase-to-groundfault are, underthe assumptionsmentioned, Va = V 1 I Vb = ----j~ 2 2 1 I V = --+-J'~ c 2 2 (4.54) 188 Chapter4 • VoltageSags-Characterization >------. Va Figure 4.66Phase-to-neutralvoltages before (dashed line) and during (solid line) a phaseto-groundfault. The resultingphasordiagramis shown in Fig. 4.66. If the load is connected in star, these are the voltages at the equipmentterminals. If the load is connected in delta, the equipmentterminal voltages are the phase-to-phase voltages. These can be obtained from (4.54) by the followingtransformation: (4.55) This transformationwill be an important part of the classification. The factor.J3 is of the pu values, sothat the normal operatingvoltage aimed at changing the base remains at 1000/0. The 90° rotation by using a factorj aims at keeping the axis of symmetry of the sag along the real axis. We will normally omit the primes from (4.55). Applying transformation(4.55) results in the following expression for the three-phaseunbalancedvoltage sag experienced bydelta-connected a load, due to a single-phase fault: (4.56) The phasordiagramfor the equipmentterminal voltages is shown in Fig. 4.67: two voltages show adrop in magnitudeand change in phase angle; the third voltage is not influenced at all.Delta-connectedequipmentexperiences a sag in two phases due to a single-phase fault. 189 Section 4.4 • Three-PhaseUnbalance \ \. \ \ ...\ .. \ Figure 4.67 Phase-to -phase voltages before (dashed line) and during (solid line) a phaseto-ground fault. 4.4.4.2 Phase-to-Phase Faults.For a phase-to-phasefault the voltages in the two faulted phases move toward each other. The expressions for the phase-to-neutral voltagesduring a phase-to-phase fault read as follows: Va = I Vb = _!_! VjJ3 V = _!+! V)'J3 2 2 c 2 2 (4.57) Like before, (4.55) can be used to calculate the voltages experienced by a phase-tophase connected load, resulting in Va = V Vb = _!2 V - !2jJ3 (4.58) 1 1 Vc = -2 V +-j"J3 2 The correspondingphasordiagramsare shown in Figs. 4.68 and 4.69. Due to a phaseto-phasefault a star-connectedload experiences adrop in two phases, a delta- )-- - - - - - . va i/ // Figure 4.68Phase-to-neutralvoltages before (dashed line) and during (solid line) a phaseto-phase fault. ,.< 190 Chapter4 • VoltageSags-Characterization "-\ Vc ..•.\\-, } - - - - . . .............................•Va '/ Vb Figure 4.69Phase-to-phase voltages before (dashed line) andduring (solid line) a phaseto-phase fault. connectedload experiences ad rop in three phases.F or the star-connectedload the maximum drop is 50%, for V = O. But for thedelta-connectedload one phase could drop all the way down to zero. Theconclusion that load could therefore best be connected.in star is wrong, however .M ost sags do notoriginateat the same voltage level as theequipment terminals. We will see later that the sag at theequipment terminals could beeither of the two types shown in Figs. 4.68 and 4.69, depending on the transformerwinding connections. 4.4.4.3 Transformer Winding Connections. Transformerscome with manydifferent winding connections, but a classification into only three types is sufficient to explain the transfer of three-phaseunbalancedsags from one voltage level to another. I. Transformersthat do notchangeanything to the voltages F . or this typeof transformerthe secondary-sidevoltages (in pu) are equal to the primary-side voltages (in pu). The only type of transformerfor which this holds is thestarstar connectedone with both star points grounded. 2. Transformersthat remove the zero-sequence voltage. The voltages on the secondaryside are equal to the voltages on the primary side minus the zero-sequencecomponent.Examplesof this transformertype are the starstar connectedtransformerwith one or both star points not grounded,and the delta-deltaconnectedtransformer. The delta-zigzag (Dz)transformeralso fits into this category. For thesetransformerseach 3. Transformersthat swap line and phase voltages. secondary-sidevoltage equals the difference between two primary-sidevoltages. Examples are the delta-star(Dy) and thestar-delta(Yd) transformeras well as thestar-zigzag(Yz) transformer. Within each of these threecategoriesthere will be transformerswith different clock number(e.g., Yd I and YdII) leading to a different phase shift between primary- and secondary-sidevoltages. This difference is not of any importancefor the voltage sags as experienced by theequipment.All that mattersis the change between the pre-fault voltages and theduring-fault voltages, inmagnitudeand in phase-angle . The whole phasordiagram, with pre-fault and during-fault phasors, can berotatedwithout any influence on theequipment.Such arotation can be seen as a shift in the zero point on 191 Section 4.4 • Three-PhaseUnbalance the time axis which of course has no influence on equipment behavior. The three transformertypes can be defined mathematicallyby meansof the following transformation matrices: T1 = T2 = [1 0 ;] 0 1 o 0 -1] ~ [-~ -1 2 -1 -1 2 -1 3 T = (4.59) ~[-: 1 0 -1 -i] (4.60) (4.61) Equation(4.59) isstraightforward:matrix T 1 is the unity matrix. Equation(4.60) c omponento f the voltage.The matrix T2 can be understood removesthe zero-sequence easily by realizing that the zero-sequence v oltageequals!(Va + Vb + Vc) ' Matrix T3 in (4.61) describesexactly the sametransformationas expression(4.55). The additional advantageof the 90°rotation is that twice applying matrix T3 gives thesameresultsas once applying matrix T2• Thus, Tf = T2 ; in engineeringterms: two Dy transformersin cascadehavethe sameeffect on the voltagesag asone Dd transformer. 4.4.3.4 Transfero f Voltage Sags across Transformers. The three types of transfaults. To formers can be applied to the sags due tosingle-phaseand phase-to-phase get an overview of the resulting sags, thedifferent combinationswill be systematically treatedbelow. • Single-phasefault, star-connectedload, no transformer. This casehas been discussedbefore,resultingin (4.54) and Fig. 4.66. We will 1 gives thesameresultsof course. refer to this sag as sag X Transformertype 1. • Single-phasefault, delta-connectedload, no transformer. The voltagesag for this case is given in (4.56) and shownin Fig. 4.67.This sag will be referredto as sag X2. • Single-phasefault, star-connectedload, transformertype 2. Transformertype 2 removesthe zero-sequence c omponentof the voltage.The zero-sequence c omponentof the phasevoltagesdue to a single-phasefault is found from (4.54) to beequalto !(V - 1). This gives thefollowing expressions for the voltages: 1 Va = 2 3+3 V Vb = - 1. -61 - -31V - -]v'3 2 1 1 (4.62) 1. Vc = ----V+-jv'3 6 3 2 This looks like a new typeof sag, but we will seelater that it is identical to the one experiencedby a delta-connectedload during a phase-to-phase fault. But for now it will be referredto as sag X3. 192 Chapter 4 • VoltageSags-Characterization • Single-phasefault, delta-connected load, transformer type 2. The phase-to-phasevoltages experienced by delta-connected a load do not contain any zero-sequencecomponent.Thus transformer type 2 does not have any influence on the sag voltages. The sag is thus still of type X2. • Single-phasefault, star-connectedload, transformer type 3. Transformertype 3 changes phase voltages into line voltages. Thus star-connected load onsecondaryside experiences the same sagdelta-connected as load on primary side. In this casethat is sag X2. • Single-phasefault, delta-connected load, transformer type 3. There are now twotransformations:from star- todelta-connectedload, and from primary to secondarysideof the transformer.Eachof thesetransformations can be describedthrough matrix T3 defined in (4.61). Two of those T2 • Thus, transformationsin cascade have the same effecttransformation as the sag experienced by this delta-connectedload is the same as by the starX3~ connectedload behind atransformerof type 2; thus, sag type • Phase-to-phase fault, star-connectedload, no transformer. This case wastreatedbefore resulting in (4.57) and Fig. 4.68. This will be sag type X4. • Phase-to-phase fault, delta-connected load, no transformer. The expression for the sag voltages reads as (4.58) and is shown in Fig. 4.69. This type will be referred to as X5. • Phase-to-phase fault, star-connectedload, transformer type 2. As phase-to-phase faults do not result in any zero-sequence voltage, transformer type 2 (which removes the zero-sequence voltage) does not have any effect. The sag thus remains of type X4. • Phase-to-phase fault, delta-connected load, transformer type 2. Like before, the sag is still of type X5. • Phase-to-phase fault, star-connectedload, transformer type 3. Star-connectedload on secondaryside of transformertype 2 experiences the same sag as delta-connectedload on primary side. This results in type X5. • Phase-to-phase fault, delta-connected load, transformer type 3. This gives again two identicaltransformationsT3 in cascade, resulting in one transformationT2 • But that one only removes the zero-sequence component and has thus no influence on sags duephase-to-phase to faults. The result is, thus, again X4. The effectof a secondtransformeron sags Xl throughX5 is shown in Table 4.8. These results can beobtainedby following the samereasoningas above. It becomes clear that TABLE 4.8 FurtherPropagationof Sags TransformerType Sag Type 2 3 X2 Xl Xl X3 X2 X2 X2 X3 X3 X3 X3 X4 X4 X4 X5 X5 X5 X2 X5 X4 193 Section 4.4 • Three-PhaseUnbalance the numberof combinationsis limited: at mostfive different sag types arepossibledue faults. to single-phaseand phase-to-phase 4.4.4.5 The Basic Types ofSags. We sawthat single-phasefaults lead to three types of sags,designatedsag Xl , sag X2, and sag X3. Phase-to-phase faults lead to sag X4and sag X5. We sawalreadyfrom the phasordiagramsin Figs. 4.67and 4.68 that single-phaseand phase-to-phase faults lead tosimilar sags.The sag voltagesfor sag type X2 are Va = 1 -~(!+! V)1J3 2 6 3 Vb = (4.63) Vc = .i, 2 (~+~ 6 3 V)'iJ3 J For sag type X4 thevoltagesare Va = 1 Vb 1 1 = ---VjJ3 2 2 V = _!+! V)·J3 2 2 c 0 (4.64) Comparingthese two setso f equationsshowsthat (4.63) can beobtainedby replacing V in (4.64)by! + j V. Ifwe define themagnitudeof sag X4 asV, then sag X2 is a sag of type X4 with magnitude!+ j V. In the same way we can c omparesag X3: I 2 Va =3+3 V Vb = V c -~ -~ V -~jJ3 6 3 2 (4.65) = -~-~ V+~joJ3 6 3 2 and sag X5: Va = V I 1. Vb = - - V - - j J 3 2 2 V c (4.66) 1 =--21 V +_joJ3 2 t Again we obtain (4.65) by replacing V in (4.66) by + ~ V. The result isthat only three types remain:X l , X4, and X5. A fourth type of sag is the sag due to threephasefaults, with all three voltagesdown the sameamount. The resulting classification is shownin Table 4.9 in equationform and in Fig. 4.70 in phasorform. All sags in Fig. 4.70 have amagnitudeof 500/0. From the discussionabout sags due to singlephaseand phase-to-phasefaults, togetherwith the definition of the four types, the origin and the propagationof the sags becomess traightforward. The results are summarizedin Table 4.10 for theorigin of sagsand in Table 4.11 for their propagation to lower voltagelevels. Thesuperscript(") behindthe sag type inTables4.10 and 194 Chapter 4 • Voltage Sags-Characterization TABLE 4.9 Four Types of Sagsin EquationForm Type A Type 8 Va = V Vb = V - !jV J3 Vc = -t V +!jvJ3 Va = V -! Vb Vc Type C Type 0 =V Vb =Vc = - Va = 1 Vb = Vc = -!-!jJ) = -! +!jJ3 Va -! -!jV~ = -!+!jvJ3 V -!jJ3 V +!jJ) TypeB ............... ~ T~C TypeD ............... ~./ Figure 4.70 Four types of sag inphasordiagramform. TABLE 4.10 Fault Type, Sag Type, andLoad Connection Fault Type Star-connectedLoad Delta-connectedLoad Three-phase Phase-to-phase Single-phase sag A sag C sag B sag A sagD sag C* TABLE 4.11 Transformationof Sag Type to Lower Voltage Levels Transformer Connection YNyn Yy, Dd, Dz Yd, Dy, Yz Sag Type A Sag Type B Sag Type C Sag Type D type A type A type A type B type D* type C* type C type C type D type D type D type C t 4.11 indicatesthat the sagmagnitudeis not equal to V but equal to + ~ V, with V the voltage in the faulted phase or between the faulted phases in Table 4.10 and the magnitudeof the sag onprimary side in Table 4.11.N ote that in effect these two definitions of V are the same. 195 Section 4.4 • Three-PhaseUnbalance 4.4.4.6 Two-Phase-to-Ground Faults.T wo-phase-to-groundfaults can be treated in the same way as single-phaseand phase-to-phase faults. We will assumethat the voltage in the non-faultedphaseis not influenced by the fault. As we have seen in Section 4.4.3 this correspondsto the situation in which positive-, negative-, and zero-sequenceimpedancesare equal. This can be seen as anextremecase. A zerosequenceimpedancelarger than the positive-sequence impedancewill shift the resulting voltagestoward thosefor a phase-to-phase fault. The phase-to-groundvoltagesat the pee due to tawo-phase-to-groundfault are Va = 1 Vb = _! V _! Vj-IJ Vc = -~ V +~ Vj../3 2 (4.67) 2 After a Dy transformeror any other transformerof type 3, thevoltagesare Va = V Vb 1 1V 1 = --j../3 - - - - Vj-IJ 3 2 6 V I. = + -J../33 c 1 (4.68) 1. - V +- V)../3 2 6 After two transformersof type 3 or after one transformerof type 2, we get 2 1 Va =3+3 V Vb = - -31 - -61 V - V = _!_~ V +! Vj'-IJ 362 c 1 (4.69) - Vj../3 2 Thesethree sags aredifferent from the four types found earlier. It is not possibleto translateone into the other. Two-phase-to-groundfaults lead tothree more types of sags,resulting in a total of seven. Thethree new types areshown in phasor-diagram form in Fig. 4.71and in equationform in Table4.12. Sags due totwo-phase-to-ground faults andsags due tophase-to-phase faults are comparedin Fig. 4.72.For a type C sag the voltageschangealong the imaginaryaxis only, for type 0 along the real axis only. TypeF .............. Figure 4.71Three-phaseunbalancedsags due to two-phase-to-groundfaults. 196 Chapter4 • VoltageSags-Characterization TABLE 4.12 Sags Due toTwo-Phase-to-GroundFaults Type F Type E Va = V Vh = -ijJ3 - Va = I Vh = Vi' = -! V - ! VjJ3 -! V +! Vjv'3 Vc = +ijv1 - V- Vjv"j V + Vjv1 Type G Va = j+i V Vh = ~V- v(' = - i! Vjv'3 i - ~ V +! VjJ3 D ~ "·""N c G ...-.- ............ c .....~ . . .. DF i"V Z-J D Figure 4.72Comparisonof three-phase unbalancedsags due totwo-phase-to-ground faults (F and G) withthree-phaseunbalanced a nd single-phasesags due tophase-to-phase to-groundfaults (C and D). The arrows indicate the direction of changein the three complexvoltagesfor the different sag types. For types F and G the voltages drop along both axis. The resulting voltages at the equipmentterminalsare lowerduring a two-phase-to-groundfault. An additionaldifference isthat all three voltagesdrop in magnitudefor a type G sag.N otealsothat for a type D and type F sag the drop in the worst-affectedphase is the same, whereas for a type C and a type G sag the drop in voltage between the two worst-affectedphases is the same. Thispropertywill be used when defining themagnitudeof measuredthreephaseunbalancedsags. Sag types F and G have been derived by assuming that positive-, negative-, and zero-sequenceimpedancesare the same. If the zero-sequence impedanceis larger than the positive-sequence impedance,the resulting sag will be somewhere in between type C and type G, or in between type D and type F. 4.4.4.7 Seven Types of Three-Phase Unbalanced Sags.Origin of sags and transof three-phaseunbalancedsags formation to lower voltage levels for all seven types of the sagtransformationto are summarizedin Tables 4.13 and 4.14. An example TABLE 4.13 Origin of Three-PhaseUnbalancedSags Fault Type Star-connectedLoad Delta-connectedLoad Three-phase Two-phase-toground Phase-to-phase Single-phase Type A Type E Type A Type F Type C Type B Type D Type C· Note: Asterisk defined as inTables4.10 and 4.11. 197 Section 4.4 • Three-PhaseUnbalance TABLE 4.14 Transformationof Sag Type to Lower Voltage Levels Transformer Connection YNyn Yy, Dd, Dz Yd, Dy, Yz Sag on Primary Side Type A Type B Type C Type D Type E Type F TypeG A A A B D* C* C C D D D C E G F F G G G F F lower voltage levels isshown in Fig. 4.73. A fault at 33 kV causes the voltage at the peeto drop to 50% of the nominal voltage. For a three-phasefault the situation is easy: at any leveland for any load connectionthe sag isof type A and with a magnitude of 50%. For a phase-to-phasefault the voltage betweenthe faulted phasesat the peedrops to 50%. For star-connectedload the resulting sags are typeC, 50% at 33 kV; type D, 50% at 11 kV; and again type C, 500/0 at 660 V. In case thefault is a single-phaseone, thevoltage in the faulted phasedrops to 50% at the pee,This correspondsto a sagof type B and magnitude50% at 33 kV. After the first Dy transformer the zero-sequencecomponent of the voltages has been removed. Starconnectedload at 11 kV will experiencea sagof type C with a magnitudeof 67%. Delta-connectedload will experiencea sagof type D with a magnitudeof 670/0. For load fed at 660 V thesituation is just the other way around: star-connectedload experiencesa sagof type D; delta-connectedload one of type C. 4.4.4.8Overview. In the beginningof this sectionwe assumedthat the zero-sequencecomponentof the voltagesdid not propagatedown to the equipmentterminals. We used thisassumptionto obtain an expressionfor the voltages during a single-phase-to-groundfault. Under this sameassumptionwe find that three-phase unbalancedsagsof type B or type E cannotoccur at the equipmentterminals.At the equipmentterminalswe only find the following five typesof three-phaseunbalanced sags: • type A due tothree-phasefaults. • type C and type D due tosingle-phaseand phase-to-phase faults. • type F and type G due totwo-phase-to-groundfaults. Iph...gnd B, 50% Figure 4.73 Example of sag transformation, for star-connectedload. n 67% 2ph 2ph-gnd 3ph C, 50% E, 50% A, 50% n 50% F, 50% At 50% C, 50% o, 50% At 50% Chapter4 • VoltageSags-Characterization 198 The latter two types can beconsideredas distortedversions of type C and D. Sags of type C and D are also distorted by the presenceof inductionmotor load. The presence of inductionmotor load makesthat positive- and negative-sequence source impedances of the effectsof this is that the voltage in the"non-faulted are no longer equal. One 100%. This has been the basis for a phase"for a type C sag is no longer equal to classification andcharacterizationof three-phaseunbalancedsags into three types, correspondingto our types A, C, and D[203], [204]. 4.5 PHASE-ANGLE JUMPS A shortcircuit in a power system not only causes adropin voltagemagnitudebut also a of the voltage. In a 50 Hz or 60 Hz system, voltage is a change in the phase angle complex quantity (a phasor)which hasmagnitudeand phase angle. A change in the system, like ashortcircuit, causes a change in voltage. This changeis not limited to the magnitudeof the phasorbut includes a change in phase angle as well. We will refer to the latter as thephase-anglejump associatedwith the voltage sag. Thephase-angle jump manifests itself as a shift in zero crossing of the instantaneousvoltage. Phaseanglejumps are not of concernfor most equipment.But power electronicsconverters using phase-angleinformation for their firing instantsmay be affected. We will come back to the effecto f phase-anglejumps on equipmentin Chapter5. j ump of +45°: theduring-fault Figure4.74 shows a voltage sag withphase-angle a voltage leads thepre-faultvoltage. A sag with aphase-anglejump of -45° is shown in Fig. 4.75: theduring-fault voltage lags thepre-fault voltage. Both sags have a magnicontinuedas a dashed tude of 70%. In both figures, thepre-fault voltages have been curve. Notethat these aresyntheticsags, notmeasurementresults. The origin of phase-anglejumpswill be explained for athree-phasefault, asthat enables us to use the single-phase model. Phase-angle j umps during three-phasefaults X /R ratio between the source and the feeder. A second are due to the difference in causeof phase-anglejumps is the transformationof sags to lower voltage levels. This phenomenonhas already been mentionedwhen unbalancedsags were discussed in Section 4.4. 0.5 -0.5 2 3 Time in cycles 4 5 Figure 4.74 Synthetic sag with a magnitude of.70°tlo and a phase-angle jump of +45°, 199 Section 4.5 • Phase-Angle Jumps 0.5 -0.5 -I L - . . - _ - - - J ' - - _ - . . . . L_ _- - - L ._ _-...L.._ _ --' o Figure4.75Syntheticsag with amagnitude of 700/0 and aphase-anglejump of -45 2 3 4 5 Time in cycles 0 • 4.5.1 Monitoring To obtainthe phase-anglejump of a measuredsag, thephase-angleof the voltage during the sagmust be comparedwith the phase-angleof the voltage before the sag. The phase-angleof the voltagecan be obtainedfrom the voltagezero-crossingor from the phaseof the fundamentalcomponentof the voltage. The complex fundamental voltagecan be obtainedby doing a Fourier transformon the signal. This enablesthe use of Fast-FourierTransform(FFT) algorithms. To explain an alternativemethod,considerthe following voltage signal: v(t) = X cos(wot)'- Y sin(wot) = Re{(X + jY)eia>ot} (4.70) with Wo the fundamental(angular)frequency.Two new signalsare obtainedfrom this signal, as follows: Vd(t) = 2v(t) x cos(Wot) (4.71) = 2v(t) x sin(wot) (4.72) vq(t) which we can write as Vd(t) = X + X cos(2wot) + Y sin(2wot) vq(t) = - y + Y cos(2wot) (4.73) + X sin(2wot) (4.74) Averaging the two resulting signalsover one half-cycle of the fundamentalfrequency gives therequiredfundamentalvoltage. (4.75) J Knowing the valuesof X and Y, the sagmagnitudecanbe calculatedas X 2 + y2 and the phase-anglejump as arctan This algorithm has beenappliedto the recordedsag in Fig. 4.1.The resultingsag magnitudeis shown in Fig. 4.76 and the phase-anglejump in Fig. 4.77. The effect of averagingVd(t) and vq(t) over one full cycleof the fundamentalfrequencyis shown in Fig. 4.78 for the sagmagnitudeandin Fig. 4.79 for thephase-anglejump. The effect of a largerwindow is that the transitionis slower,but the overshootin phase-angleis less. Which window length needs to bechosendependson the application. t. Chapter 4 • VoltageSags-Characterization 200 0.8 a .5 ~ 0.6· 2 .~ ~ 0.4 0.2 234 Timein cycles 5 6 Figure 4.76 Amplitude of the fundamental voltage versus time for the voltage sag shown in Fig. 4.I-a half-cycle window has been used. 20,-----,.------,-----r----,-----r-----, 10 fI) ~ ~ 0....-----' -8 .S -10 Q.. § -20 '--' .!! , -30 ~ ] -40' A.4 -50 234 Timein cycles a .5 6 0.8 -8 0.6 ~ 0.4 -I 5 Figure 4.77 Argument of the fundamental voltage.versustime for the voltage sag shown in Fig. 4.I-a half-cycle window has been used. , , , 234 Timein cycles . - L _.. __ . _ .. _ 5 6 Figure 4..78 Amplitude of the fundamental voltage versus time for the voltage sag shown in Fig. 4.I-a one-cyclewindow has been used. 201 Section 4.5 • Phase-Angle J umps 20..---~--~--,.---.,.-------r- 10 l f'J Ol-----..J -8 .5 -10 Q. § -20 ."""\ u l-30 u =-40 -sof Figure 4.79 Argument of the fundamental if voltage versus time for the voltage sag shown -60O'-------'------"----L------"--~ . 2 3 4 5 in Fig. 4.I-a one..cyc1ewindow has been Timein cycles used. , , I 6 4.5.2 Theoretical Calculations 4.5.2.1 Origin of Phase-AngleJumps. To understandthe origin of phase-angle jumps associated with voltage sags, the single-phase voltage divider model of Fig. 4.14 can be used again, with the difference that Zs and ZF are complexquantities which we will denote asZs and ZF. Like before, we neglect all loadcurrentsand point-of-commoncoupling (pee): assumeE = 1. This gives for the voltage at the -V ZF sag ---r: ZS+ZF (4.76) Let Zs = R s + jXs and ZF = R F + jXF . The argumentof V.mg , thus the phase-angle jump in the voltage, is given by the following expression: 11t/J = arg(Vsag)=arctan(~:) - arctan(~:: ~:) (4.77) ¥, If ~ = expression (4.77) is zero and there is no phase-angle jump. The phase-angle jump will thus be present if theX/R ratios of the source and the feeder are different. 4.5.2.2 Influenceof Source Strength. Consideragain the power system used to obtain Fig. 4.15. Insteadof the sagmagnitudewe calculatedthe phase-anglejump, resulting in Fig. 4.80. We again see that a strongersource makes the sag less severe: lessdrop in magnitudeas well as a smaller phase-angle jump. The only exception is for terminal faults. The phase-angle jump for zero distance to the fault is independent of the source strength. Note that this is only of theoreticalvalue as the phaseanglejump for zero distance to the fault, and thus for zero voltage magnitude,has no physical meaning. 4.5.2.3 Influenceof Cross Section. Figure 4.81 plots phase-angle jump versus of the distance for 11 kV overhead lines of different cross sections. The resistance source has been neglected in these calculations: Rs = O. The correspondingsag magnitudeswere shown in Fig. 4.16.From the overhead line impedance data shown in Table 4.1 we can calculate the X/R ratio of the feeder impedances: 1.0 for the 202 Chapter 4 • VoltageS ags-Characterization Or----..----~----:==:::!::::=:==:::c:=====~ -5 g -10 ~ -15 75MVA "'t' .5 ~ -20 .; -25 bb ~ -30 Go) ~ f -35 -40 -45 0 10 20 30 40 50 Distance to the fault in kilometers Figure 4.80Phase-anglejump versus 2 11kV distance, for faults on a 150 mm overheadfeeder, withdifferent source strength. _______ - - -.-: ..... -:.-:.-:.-:~:-.:-.-:-.:-.7. g-10 t c:: -20 ' .- .[ ~ -30':' = . . ~ , . G) . ~ -40: -soL , , ' o 5 10 15 20 Distance to the fault in kilometers 25 Figure 4.81Phase-anglejump versus distance,for overheadlines with cross section 300mm2 (solid line), 150mm2 (dashedline), and 50mm2 (dottedline). 50 mrrr' line, 2.7 for the 150 mm", and 4.9 for the 300 mm-; the phase-anglejump decreases for larger X/R ratio of the feeder. The results forundergroundcables are shown in Fig. 4.82. Cables with a smaller cross section have a larger phase-anglejump for small distances to the fault, but the phase-anglejump also decays faster for increasing distance. This is due to the (in absolutevalue) larger impedance per unit length. The correspondingsag magnitudes were shown in Fig. 4.17. Sagmagnitudeand phase-anglejump, i.e., magnitudeand argumentof the complex during-faultvoltage, can beplottedin onediagram.Figure 4.83 shows the voltage pathsin the complex plane, where the pre-sag voltage is in the direction of the positive real axis. Thefurther the complex voltage is from + 1 jO, the larger the change in complex voltage due to the fault. The difference between the pre-sag voltage and the actual voltage is referred to as the missing voltage. We will come back to the concept of missing voltage in Section 4.7.2. Insteadof splitting the disturbanceinto real andimaginary parts one may plot magnitudeagainst phase-anglejump as done in Fig. 4.84.F rom the figure we can conclude that the phase-anglejump increases (inabsolutevalue) when thedrop in voltage increases (thus, when the sag magnitude decreases). Both an increase in 203 Section 4.5 • Phase-AngleJumps Or------y---~---.__--__r_--__, -10 1-20 -8 .6 -30 ,/ Q. ' , § -40 .• ., .~ I-50 1::1 ~ -60 'f Q.. : ..c: ' -70 -80 0 5 10 15 20 Distance to the faultin kilometers 25 Figure 4.82Phase-anglejump versus distance, forundergroundcables with cross 2 (solid line), 150mm2 (dashed section 300mm line), and 50mm2 (dottedline). O-----,..---~----r-----r---___, ,\ I '\ '\ .s t :s " /:' , ,, " , , -0.1 '. ,, ', , \ , \ \ ,, I' I : . / I ] -0.2 c.e.. o i- 0.3 ~ .s e t)I) ..... -0.4 -0.50 -70 0.2 "'--OA- 0.6 0.8 Realpartof voltagein pu Figure 4.83Pathof the voltage in the complex plane when the distance to the fault changes, forundergroundcables with cross 2 (solid line), 150mm2 (dashed section 300mm line), and 50mm2 (dottedline). Figure 4.84Magnitudeversus phase-angle -80 I.-----'--------'----~-------------' jump, for undergroundcables with cross o 0.2 0.4 0.6 0.8 section 300mm2 (solid line), 150mm2 (dashed Sagmagnitudein pu line), and 50mnr' (dotted line). 204 Chapter 4 • VoltageSags-Characterization phase-angle j ump and a decreasein magnitudecan bedescribedas amoresevere event. Knowing that both voltage drop and phase.. angle jump increasewhen thedistanceto the fault increases,we can conclude that a fault leads to amore severe event the closer it is to thepoint-of-commoncoupling. We will later seethat this only holds for three-phasefaults. For single-phaseand phase-to-phase faults this is not always the case. 4.5.2.4 Magnitude and Phase-Angle Jump Versus Distance. To obtain expressions for magnitudeand phase-anglejump as a function of the distanceto the fault we substituteZF = z£ in (4.76) with z the complex feederimpedanceper unit length, resultingin V z.c ---- .mg - (4.78) Zs+z.c The phase-anglejump is found from arg(V.mg ) = arg(z.c) - arg(Zs + z£) (4.79) The phase-anglejump is thus equal to the angle in thecomplexplanebetweenz£ and 2 s + u: This is shownin Fig. 4.85, where</J is the phase-anglejump anda is the angle betweensourceimpedanceZs and feeder impedancez. ex = arctan(~;) - arctan(~;) (4.80) We will refer to a as the"impedanceangle;" it is positive when theX/R-ratio of the feeder islargerthan that of the source.Note that this is araresituation:the impedance angle is inmost casesnegative.Using the cosinerule twice in the lowertriangle in Fig. 4.85 gives the twoexpressions IZs + z.c12 = tz.c,2 + IZsl2 - 2lz.cIlZ l cos(180°+ a) (4.81) s 2 12s1 = IZs + zL:1 2 + IzL:1 2 - 212s + zL:llz£1 cos(-t/J) (4.82) Substituting(4.81) into (4.82) and some rewriting gives an expressionfor the phaseangle jump as afunction of distance Ar.) cos('P A + cosa = --;::::====== Jl + A2 + 2Acosa (4.83) where A = z£/Zs is a measureof the "electrical" distance to the fault and a the impedanceangle. Note that it is not so much the differencein X/R ratio which deter- Figure 4.85Phasordiagram for calculation of magnitude and phase-angle jump. 205 Section 4.5 • Phase-Angle Jumps mines the sizeof the phase-anglejump but the actualangle betweensourceand feeder X s/ Rs = 40 and a feeder withXF / RF 2 gives impedance.For example, a source with an impedanceangle of = = -25.2° a = arctan(2)- arctan(40)= 63.4° - 88.6° (4.84) = where a source withX s /Rs 3 and a feeder withXF / RF = 1 gives animpedanceangle of a = -26.6°. The latter will result in more severephase-anglejumps. The maximum angulardifference occurs forundergroundcables indistribution systems.F or a sourceX/R of 10 and a cableX/R of 0.5 weobtainan impedanceangle of about-60°. In the forthcomingsections the value of-60° is used as theworstcase. Although this is aratherrare case, it assists in showing the variousrelationships.Small positive phase-anglejumps may occur in transmissionsystems whereX/R ratio of source and feeder impedanceare similar. Impedanceangles exceeding+ 10° are very unlikely. For mostof the forthcomingstudies we will assumethat the impedanceangle varies between0 and -60°. From (4.83) we can concludethat the maximum phase-anglejump occurs for [, = 0, A = 0 and that it is equalto the impedanceangle a. The magnitudeof the sag isobtainedfrom (4.79)as v _ sag- Iz£1 Iz.c + Zsl (4.85) With (4.81)the following expressionfor the sagmagnitudeas afunction of the distance to the fault isobtained: V _ _A_ (1 + A) -;:===== 1 _ 2A(l-COS a) (4.86) sag - (t+A)2 Note that the first factor in the right-handsideof (4.86) gives the sag magnitudewhen the difference inX/R ratio is neglected(a = 0). This is the sameexpressionas (4.9) in Section4.2. The error in makingthis approximationis estimatedby approximatingthe secondfactor in (4.86) for small valuesof a: 1- 2A(l-cosa) (l+A)2 ~ 1 1- A(1-cosa)~l+ (1+,)2 - A (1 + A) A 2(1-Cosa)~1+(1+')2a 2 (4.87) I\, A The error is proportionalto a2• Thus, for moderatevaluesof a the simpleexpression without consideringphase-anglejumpscan be used tocalculatethe sagmagnitude. 4.5.2.5RangeofMagnitudeandPhase-AngleJump. The relation between magnitude and phase-anglejump is plotted for four values of the impedanceangle in Fig. 4.86.Magnitudeand phase-anglejump have beencalculatedby using (4.83)and (4.86). During a three-phasefault all three phases will experience the same changein magnitudeand phase-angle.The relation shown in Fig. 4.86 thus alsoholds for single-phaseequipment.When testingequipmentfor sags due tothree-phasefaults one of should considerthat magnitudeand phase-anglejump can reach the whole range combinationsin Fig. 4.86. 206 Chapter4 • VoltageSags-Characterization -.---- ---., --7l 10, . . - - - - : : : : - - - - - - r - - - o -~ ~ .... ' .' ... _---~--~.~.~;>; rJ ~ -10 -- -8 .8 -20 Q., § -30 I '",,"", l-40 Cl) Cl) ~ f -50 -60 0.2 Figure 4.86 Relation between magnitude and phase-angle jump for three-phase faults: impedance angles: -60 (solid curve);-35 (dashed);- I 0 (dotted);+ I0° (dash-dot). 0.4 0.6 0.8 Sagmagnitudein pu 0 0 0 EXAMPLE Magnitude and phase-anglejump have beencalculatedfor sags due to three-phasefaults at the various voltage levels in the example supply shown in Fig. 4.21. Using the data in Tables 4.3 and 4.4 we can calculatethe complex voltage at the pee for any fault in the system. Theabsolutevalue andargumentof this complex voltage are shown in Fig. 4.87. The complex voltage has been calculatedfor distances to the fault less than the maximum feeder lengthindicatedin the lastcolumn of Table 4.4. As the maximum feeder length at 132kV is only 2 km, the sagmagnitudedue to 132kV faults does not exceed 20%. We that see distribution system faults givephase-anglejumps up to 200 , with the largest ones due to 33 kV faults. Transmissionsystemfaults only cause very mild phase-angle jumps. Thesemagnitudes and phase-anglejumps hold for single-phase as well as three-phaseequipment,connected to any voltage level and irrespective of the load beingconnectedin star or in delta. rJ o --------'- - - - - =:: = = =---":'"--------- -:. ~.= ... _-....----- -0 j ..., -5 .5 Q., ~ -10 '",,"", u bo ~ -15 Cl) ~ ~ -20 0.2 0.4 0.6 0.8 Sagmagnitudein pu Figure 4.87 Magnitude and phase-anglejump for three-phase sags in the example supply in Fig. 4.21-solidline: II kV; dashed line: 33kV; dotted line: 132kV; dash-dot line: 400kV. 4.8 MAGNITUDE AND PHASE-ANGLE JUMPS FOR THREE-PHASE UNBALANCED SAGS 4.8.1 Definition of Magnitude and Phase-Angle Jump 4.6.1.1 Three Different Magnitudes and Phase-Angle Jumps. The magnitudeof a voltage sag wasdefined in Section 4.2 as the rmsvalue of the voltage during the fault. As long as thevoltage in only one phaseis consideredthis is an implementable Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-PhaseUnbalancedSags 207 definition, despite theproblems with actually obtaining the rms value.For threephase unbalancedsags theproblem becomes morecomplicated as there are now three rms values to choose from. The most commonly used definition is: The magnitude of a three-phase unbalanced sag is the rms value of the lowestof the three vol· tages.Alternativessuggested earlier are to use the average of the three rms values, or the lowest valuebut one [205]. Here we willproposea magnitudedefinition based on the analysisof three-phaseunbalanced.sags. First we need todistinguish between three different kindso f magnitudeand phase-anglejump. In all casesmagnitudeand phase-anglejump are absolutevalue and argument,respectively, of a complex voltage. • The initial complexvoltage is the voltage at thepoint-of-commoncoupling at fault the initial complex the faulted voltage level.For a single-phase-to-ground voltage is the voltage between the faulted phase groundat and the pee,For a phase-to-phase fault the initial complex voltage is the voltage between the two faulted phases.F or a two-phase-to-ground or a three-phasefault it can be either the voltage in oneof the faulted phases or between two faulted phases (as long as pu values are used). The initial magnitudeis sag the absolutevalue of the complex initial voltage; the initialphase-anglejump is the argumentof the complex initial voltage. • The characteristiccomplexvoltageof a three-phaseunbalancedsag is defined as interpretationof the the valueof V in Tables4.9 and 4.12. We will give an easy characteristiccomplex voltage later on. The characteristicsagmagnitudeis the absolutevalue of the characteristiccomplex voltage. Thecharacteristicphaseanglejump is the argumentof the characteristiccomplex voltage. These can be viewed as generalizeddefinitions of magnitudeand phase-anglejumps for three-phaseunbalancedsags. • The complexvoltages at theequipmentterminals are the valuesof Va' Vb, and Vc in Tables 4.9 and 4.12 and in several of the equationsaroundthese tables. The sagmagnitudeand phase-anglejump at the equipment terminals are absolutevalue and argument, respectively,of the complex voltages at the equipmentterminals.For single-phaseequipmenttheseare simply sag magnitude and phase-anglejump as previouslydefined forsingle-phasevoltage sags. 4.6.1.2 Obtaining theCharacteristic Magnitude. In Section 4.4 we haveintroduced seven types o f sagstogetherwith their characteristiccomplex voltage V. For type D and type F themagnitudeis the rms valueof the lowestof the three voltages. For type C and type G it is the rms value of the difference between the two lowest voltages (in pu).From this we obtain the following method of determiningthe characteristic magnitudeof a three-phasesag from the voltagesmeasuredat the equipment terminals: • Determinethe rms valuesof the three voltages. • Determinethe rms values of the three voltage differences. • The magnitudeof the three-phasesag is the lowesto f these six values. It is easy to see from the expressionsgiven earlier,that this will give the valueof IVI as used for the definitionof the three-phaseunbalancedsags. Anexceptionare sagsof type m ethodwould still give the B and type E.For sagsconformingto (4.54) and (4.67) the 208 Chapter4 • VoltageSags-Characterization exact value for themagnitude.But the difference between zero-sequence and positivethat sequence source impedancemakesthat the actualsags can deviate significantly. In case themethodis likely to give acompletelywrong picture.Anotherproblemis that for these sags the magnitudechanges when they propagateto a lower voltage level. This makes measurementsat a medium voltage level not suitable forpredicting the sag magnitudeat the equipmentterminals.This problem can be solvedby removing the zero-sequencec omponentfrom the voltage andapplying the methodto the remaining voltages. The complete procedureproceeds as follows: • obtain the three voltages as function a of time: Va(t), Vb(t),and Vc(t). • determinethe zero-sequence voltage: (4.88) • determinethe remainingvoltages aftersubtractingthe zero-sequence voltage: V~(t) = Va(t)- Vo(t) Vb(t) = Vb(t)- Vo(t) V;( t) = Vc( t) - Vo(t) • determinethe rms valuesof the voltagesV~, • determinethe three voltage differences: (4.89) Vb, and V;. (4.90) • determinethe rms valuesof the voltagesVab, Vbc' and Vcao • the magnitudeof the three-phasesag is the lowest of the six rms values. In case alsophase-anglejump and sag type are needed, it better is to use a more mathematicallycorrect method. A method based onsymmetrical componentshas recently beenproposedby Zhang[203], [204]. EXAMPLE This procedure has been applied to the voltage sag shown in Fig. 4.1. At first the rms values have been determined for the three measured phase-to-groundvoltages, resulting in Fig. 4.88. The rms value has been determined each half-cycle over the preceeding 128 samples (one half-cycle). We see the behavior typical for a single-phase fault on an overhead feeder: a drop in voltage in one phase and a rise in voltage in the two remaining phases. component,all three voltages show a drop in After subtractionof the zero-sequence magnitude (see Fig. 4.89). The phase-to-groundvoltages minus the zero-sequence are indicated through solid lines, thephase-to-phase voltagesthrough dashed lines. The lowest rms value is reached for aphase-to-groundvoltage, which indicates a sag of type D. This is not surprising as the original sag was of type B (albeit with a larger than normal zero-sequence component). After removal of the zero-sequence voltage a sag of type D remains.characteristic The magnitudeof this three-phase unbalanced sag630/0. is 209 Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-Phase UnbalancedSags 0.4 0.2 234 Time in cycles Figure 4.88The nns values of the phase-togroundvoltages for the sag shown in Fig. 4.1. 5 6 0.8 a , .S 0.6 o ~ 0.4 Figure 4.89The rms valuesof phase-to-phase (dashed lines) andphase-to-groundvoltages after removal of the zero-sequence component(solid lines) for the sag shown in Fig. 4.1. 0.2 234 Time in cycles 5 6 4.8.2 Ph••e-to-Ph.s.F .ults The impact ofphase-to-phase faults depends on the transformerwinding connections between the fault and the equipment. As shown in Section 4.4, the result is a sag either of typeCor of type D. It was shown in Section 4.4.2 that the voltage between the faulted phases can be obtainedby using the same voltage divider model as for the threephase sag. The latter has been.used to obtain expressions (4.83) and (4.86) for phaseanglejump and magnitudeversus distance. These expressions can thus also be used to calculate initialmagnitudeand initial phase-angle jump: absolute value and argument of the voltage between the faulted phases atpee, theThe three-phase unbalancedsags in Section 4.4 were all derived under the assumptionthat the initial voltage drops in magnitudewithout change in phase angle. In case of a phase-angle jump in the initial voltage, thecharacteristicvoltage of the three-phaseunbalancedsag at the pee also becomes complex. The expressions in Tables 4.9 and 4.12 still hold with the exception characteristic that the characteristicvoltage V has become a complex number. The 210 Chapter4 • VoltageSags-Characterization voltage for sag types Cand D does not changewhen they aretransformeddown to lower voltage levels, sothat the characteristiccomplex voltage remainsequal to the initial complex voltage. 4.6.2.1 Sagsof Type C. The phasordiagram for a sag of type C is shown in Fig. 4.90, where <p is the characteristicphase-anglejump and V the characteristic magnitude.Dependingon the phaseto which it is connected,single-phaseequipment will experiencea sag withmagnitude Vb and phase-anglejump ~h, a sag withmagnitude Vc and phase-anglejump ~c, or no sag at all.Due to the initial phase-angle jump <P the voltage magnitudesin the two faulted phasesare no longer equal. Note that in Fig. 4.90 <P < 0, ~h < 0, and <Pc > O. From Fig. 4.90expressionscan bederivedfor magnitudeandphase-angle j ump at the equipmentterminals.As a first step the sine ruleand the cosinerule are applied to the two trianglesindicatedin Fig. 4.90 resultingin vi = !4 + ~4 V2 - 2· !2·!2 V..[j cos(90° -l/J) sin(60° + <Ph) sin(90° - ~) -----=---V v'3 Vb ! V~c =!4 +~4 V2 sin(60° - 2.!.! V..[jcos(90° + l/J) 2 2 ~c) sin(90° + ~) -----=---- ! Vv'3 (4.91) (4.92) (4.93) (4.94) Vc from which the following desiredexpressionsare obtained: Va = 1 Vh Jt = 4- + -43 V 2 - : -1 V Vrx3 sln(f/J) 2 (4.95) 1/2 Figure 4.90Phasordiagram for a sag of type C with characteristicmagnitudeV and characteristicphase-anglejump 4>. Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-Phase Unbalanced Sags 2 3 Distancetothe fault f ....., rJ ~~ 4 -8 5 50 -------------------- 0 I _--~-------------~.s -50~~_.__ ~ 211 - - - I ._ _- - . . . I_ _ ----.J o I 2 4 3 Distanceto thefault 5 Figure 4.91Magnitude(top) and phase-angle jump (bottom) for sags of type C due to phase-to-phase faults. Dashedline: zero impedance angle (no characteristicphaseangle jump). Solid line:- 600 impedance angle (largecharacteristicphase-angle jump). tPa =0 tPh = -60 + arCSinGJ3~ COS(tP») 0 tPc = 60 0 - (4.96) arCSinGJ3~ COS(tP») Combining(4.95) and (4.96) with (4.83) and (4.86) gives the magnitudeand phaseanglejump in the three phases asfunction a of the distance to the fault. This is done in - 60°. The horizontalscalecorrespondsto Fig. 4.91 forimpedanceangles equal to 0 and A = ~£ as in (4.83). We see t hat the severity of sags decreases with increasing distance whenSthereis no characteristicphase-anglejump. The introductionof a characteristic phase-anglejump creates asymmetry between the faulted phases. We see, that e.g., the fault. voltage in oneof the phases initially decreases with increasing distance to the For one of the phases the phase-angle jump drops to zero ratherquickly, whereas for the other phase thephase-anglejump remains high much longer. Figure4.92 plotsmagnitudeversus phase-angle jump for four values of the impedance angle. We can see that the characteristicphase-anglejump significantly disturbs the symmetry between the two faulted phases. Also the voltagedrop can well below 50% , which is not possiblewithout characteristicphase-anglejump. 60 8 : .s I:' ," :''. \ , 40 ~ \ \ \ 20 \ e, § ...... 0 u "EO ; -20 M f I , -40 I -60 o 0.2 0.4 0.6 0.8 Sagmagnitudein pu Figure 4.92Magnitudeversus phase-angle jump for sag type C due tophase-to-phase - 600 (solid line), faults for impedance angle 0 0 -40 (dashed), -20 (dotted), 0 (dash-dot). 212 Chapter 4 • Voltage Sags-Characterization 4.6.2.2 Sagsof Type D. The phasordiagramfor a type D sag is shown in Fig. 4.93, wherel/J is again thecharacteristicphase-anglejump. One phasewill go down significantly with a phase-anglejump equal to the characteristicvalue. Equipment connectedto one of the two other phases will see a smalldrop in voltage and a phase-anglejump of up to 30°. Severecharacteristicphase-anglejumps can even lead to voltageswells. The twophaseswith the small voltagedrop can experience positive drop always as well asnegativephase-anglejumps. The phase with the large voltage experiences anegativephase-anglejump. From Fig. 4.93 magnitudeand phase-anglejump in the three phases can be calculatedfor a sagof type D. Applying the sine rule and the cosine rule to the two trianglesindicatedin Fig. 4.93 gives the following expressions: vI = !4 V2 + ~4 - 2 ·! V.!,J3 cos(90°+ lj) 2 2 sin(30° - l/Jb) sin(90°+ f/J) -~---=---- !V (4.98) Vb V 2 =! V 2 +~ - 2.! V· !,J3cos(90°- lj) c (4.97) 4 4 2 2 sin(30°+ tPc) sin(90° -l/J) ----=---!V Vc (4.99) (4.100) Rewriting theseexpressionsresults in Va =V Vb = ~+~ V2 +~ V,J3sin(lj) Vc = ~ + ~ V2 - ~ VJ3sin(lj) (4.101) Figure 4.93Phasordiagram for a sag of type D, with characteristicmagnitude V and phase-angle jumpt/J. 213 Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-PhaseUnbalancedSags ------------------------------- 2 3 5 4 Distanceto thefault Figure 4.94Magnitude(top) and phase-angle jump (bottom) for sagsof type D due to phase-to-phase faults. Dashedline: zero impedanceangle. Solid line:impedanceangle of -60°. o 5 234 Distanceto the fault cPa = cP f!Jb = 30 arCSin(2~b COS(f!J») f!Jc = -30 + arCSin(2~c COS(f!J») 0 (4.102) - 0 Again we can plotmagnitudeand phase-angle j ump versus distance and magnitude versus phase-angle jump. Figure 4.94 givesmagnitudeand phase-anglejump as a function of distance for impedance angles equal to zero and -60 Here we seethat the voltagedrop in the non-faultedphases israthersmall; the voltagedropsto about 75%. Thecharacteristicphase-anglejump causes anadditionaldrop in voltage at the equipmentterminals. Magnitudeversus phase-angle jump is plotted in Fig. 4.95 for four values of the impedance angle. 0 • 4.6.2.3 Rangeof Magnitude andPhase-AngleJump. As mentioned before, phase-to-phase faults lead to sags of type C or of type D. Combining the range of magnitudeand phase-angle j ump due to type C sags (Fig. 4.92) with the range due 60 " ':', I \ " \ \ '. ...........' , .... .:...:'. " - - - - - - - - - - - _. - - - - - - - - ~ ..-. ,-~. ~ . .:'. .:.:~:.-.: I / .' .: I~'~'" '" Figure 4.95Magnitudeversusphase-angle jump for sag type D due tophase-to-phase faults: impedanceangle -60° (solid line), -400 (dashed),-20° (dotted), 0 (dash-dot). -60 o 0.2 0.4 0.6 0.8 Sagmagnitudein pu , .' I ,I 214 Chapter4 • VoltageSags-Characterization 60 lj ~ ~ .9 ~ .~ u 40 20 0 .-------~ -;0 ; -20 ~ f -40 -60 o 0.2 0.4 0.6 0.8 Sag magnitude in pu Figure 4.96 Rangeof sags due tophase-tophase faults, as experienced by single-phase equipment. to type D sags (Fig. 4.95) gives the whole range of sags experienced by single-phase equipmentduring phase-to-phase faults. The merger of the twomentionedfigures is shown in Fig. 4.96, where only the outercontourof the area isindicated. Sags due tothree-phasefaults areautomaticallyincluded in Fig. 4.96. A threephase fault gives a sag with the initial magnitudeand the initialphase-angle j ump, in all the three phases. Such a sag also appearsin one of the phases for a type D sag due to a phase-to-phase fault. This is the largetriangulararea in Fig. 4.96. Sags due to singletreated phase andtwo-phase-to-ground faults havenot yet been included. These will be below. EXAMPLE: PHASE-TO-PHASEFAULTS, THREE-PHASELOAD The magnitude and phase-angle jump due to phase-to-phase faults have beencalculatedfor faults in the example supply in Fig. 4.21. The calculationshave beenperformedfor two different types of load: • three-phaseload connectedin delta at 660 V. • single-phase loadconnectedin star (phase-to-neutral)at 420 V. For a three-phaseload, we can use the classification introducedin Section 4.4 tocharacterizethe j ump of thesethree-phaseunbalancedsags are the same as sag. Themagnitudeand phase-angle those of sags due to three-phasefaults. The only difference is the type of sag.phase-to-phase A transformer fault at 11 kV will, for delta-connectedload at 11kV, lead to a sag of type D. The Dy between the fault (at11 kV) and the load (at 660 V) will change this into a type C sag. Thus, the of type delta-connectedload at 660 V will, due to aphase-to-phase fault at 11kV, experience a sag C. Thecharacteristicmagnitudeand phase-angle j ump of this three-phaseunbalancedsag will be j ump of the voltage (in any phase) due tothree-phase a equal to themagnitudeand phase-angle fault at the same position as the phase-to-phase fault. Using the same reasoning we find that phase-to-phase faults at 33kV lead to type0 sags and faults at132kVand400kV to sags of type C. The results of thecalculationsare shown in Fig. 4.97:characteristicmagnitudeand phaseanglejump of three-phaseunbalancedsags due tophase-to-phase faults. Note the similarity with Fig. 4.87. The curves are at exactly the same position; the only difference thatis the ones due to 33 kV faults are of type D and the others are of typeThree-phase C. faults at any voltage level will lead to a sag of type A. Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-PhaseUnbalancedSags 215 5r-----r-----r-----r------r-----~__. ~ 0 ~ -8 -5 .5 Q.. .[ -10 .£ bO ~Go) -15 ] Figure 4.97 Characteristicmagnitudeand phase-anglejump for sags due tophase-tophase faults in theexamplesupply in Fig. 4.21-solidline: type C sags,d ashedline: type D sags. ~ -20 0.4 0.2 0.6 0.8 Sagmagnitudein pu EXAMPLE: PHASE-TO-PHASEFAULTS, SINGLE-PHASELOAD Magnitude and phase-angle jump at the equipmentterminals due tophase-to-phase faults have been calculated for a single-phase load connected phase-to-neutralat 420 V. The classification of three-phase sags no longer fully describes the voltage atequipmentterminals. the The additional information needed is the phases between which the fault takes place. One can calculate the voltage sag in one phase for three different faults; but it is easier to calculate the voltages in the three phases for one fault. These three voltages are the voltages in one phase for the three different faults. We saw before that we do not need to calculate the whole transferof the sag from the faulted voltage level to the load terminals. All we need to do is determine whether the equipmentterminal voltagecorrespondsto phase-to-phaseor phase-to-neutralvoltage at the faulted voltage level. In this example, the equipment terminal voltagecorrespondsto phase-to-phasevoltages at II kV, 132kV, and 400 kV and tophase-to-neutralvoltages at 33kV. The resultingmagnitudeand phase-angle j ump are plotted in Fig. 4.98.Faultsat 11kV, 132kV, and 400 kV cause a three-phase unbalancedsag of type D forstar-connectedequipment. For a type D sag one voltage drops to a low value, and the two remaining voltages show a small drop with a phase-anglejump up to 30°. Note the symmetry in the sags originating at 400kV, which is not present in the sags originating at 11kV and 132kV. This is due to the large initial 60 I , f I 40 12: Figure 4.98 Magnitudeandphase-angle j ump at the equipmentterminalsdue to phase-tophasefaults in thesupply in Fig. 4.21, experiencedby single-phaseload connected phase-to-groundat 420V-solid line: 11 kV, dashedline: 33 kV, dotted line: 132 kV, dashdot line: 400 kV. \ = •••••••• _ ._~_:~ ~~ ~~~ i-20~ b ~ f -40 I , -60 o 0.2 " " " I 0.4 0.6 0.8 Sag magnitude in pu ,// V 216 Chapter4 • VoltageSags-Characterization phase-angle jump for the latter two. Faults at 33 kV cause a sag of type C, with two voltages down to about 50% and phase-angle jumps up to ±60°. 4.8.3 Single-Phase Faults For single-phase faults the situation becomes slightly more complicated. Expressions(4.83) and (4.86) can still be used to calculate magnitude and phaseangle jump of the voltage in the faulted phaseat the pee (Le., theinitial magnitude and phase-anglejump). Star-connectede quipmentat the samevoltagelevel 'as thefault would experiencea sag of type B. But as we have seen before, this is a rather rare situation.In almostall cases a sag d ueto a single-phasefault is of type Cor type D. The characteristicmagnitudeof thesethree-phaseunbalancedsags is nolongerequalto the initial magnitude.The sameholds for the phase-anglejump. 4.6.3.1 Initial and Characteristic Magnitude.To obtain an expressionfor the characteristicmagnitudeand phase-anglejump, we need to goback to the type B sag. Thevoltagesfor a type B sag are Va = V cos </J + jV sin </J Vb = _! - !j.Jj V = --+-J'../3 2 2 c 2 2 I 1 (4.103) with V the initial magnitudeand </J the initial phase-anglejump. When this three-phase unbalancedsag propagatesto lower voltage levels, the zero-sequencevoltage is lost. The zero-sequence c omponentfor (4.103) is (4.104) Subtractingthe zero-sequence v oltagefrom (4.103) gives athree-phaseunbalancedsag of type D. Characteristicmagnitudeandphase-angle j ump for a sagof type D areequal to the absolutevalue and the argumentof the complex voltage in the worst-effected phase, Va in this case. (4.105) Note that this expressioncan also beobtainedby substitutingV = V cos</J + jV sin </J in (4.62). For three-phaseunbalancedsags due to single-phasefaults the characteristic magnitudebecomes Vchar= IVai = 2 / 2 1 3'1 V +.Vcos</J+4 (4.106) with V and t/J the initial magnitudeand phase-anglejump, and Va accordingto (4.105). The characteristicphase-anglejump is 2Vsin<fJ ) tPchar = arg(Va) = arctan( 1 + 2V costP (4.107) 217 Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-Phase Unbalanced Sags For small values ofl/J these expressions can approximatedby be using sinl/J~ l/J cosl/J~ 1 arctantxe)~ xl/J, x < 1 resulting in ,12 Vchar = 3+3 V (4.108) , 2V~ l/Jchar = 1 + 2V (4.109) Figures 4.99 and 4.100 show the error made by using theapproximatedexpressions The calculationshave been (4.108)and (4.109). Theerror has been defined as-~. 1 performed forimpedanceangles equal to-60°, -40°,ci'itd -20°. Even for a system with large phase-anglejumps, an impedance angle of -60°, the errors are not very big. Only for calculatingthe characteristicphase-anglejump with deep sags mightit be needed to use the exact expression. One should realize, however, that the 0.08....----.,.-----r---...,.u 0.07 ] .1 0.06 ~ 0.05 .j 0.04 .~ (J j '" 0.03 - - .... , (J .~ 0.02 ~ Figure 4.99Transformationof sags due to ~ 0.01 " single-phase faults--errorin approximate o expressions for characteristic magnitude. o -600 (solid line); -400 Impedance angle: (dashed);- 20 (dotted). I I <; •••• •••••••••• .. ••• ........... -- =---.... 0.4 0.6 0.8 Initial magnitudein pu L . -_ _ ..&..-_~~ ............... 1_'_ _- - L . 0.2 0 0.2r----~----r------.,.-----r-----, ~ .~ 1 0.15 4) t (J 'i 0.1 J 0.05 \ \ (J Figure 4.100Transformationof sags due to single-phase f aults-errorin approximate expressions for characteristic phase-angle 0 (solid line); jump. Impedance angle: _60 0 0 -40 (dashed);- 20 (dotted). ... .s ~ J3 .......:-..-:-.:-.~"':'".:-:."""._-~.:::s.:.=::~....-.-_----1 0 o 0.2 0.4 0.6 Initial magnitudein pu 0.8 218 Chapter4 • VoltageSags-Characterization or - - - - - - - r - - - r - - r - - - - - - r - - - -.------r-----. \ \ \ -10 (/) 8 ~ -20· ~ = -30 .~ § :£-40 ~ ~ -50 f -60 0.2 Figure 4.101 Relation betweenphase-angle jump and magnitudeof sags due to singlephase faults:characteristicvalues(dashed curve) and initial values (solid curve). 0.4 0.6 0.8 Sag magnitude in pu characteristicphase-anglejump is close to zero for single-phase faults with a small initial magnitude,as can be seen from (4.107). The absoluteerror is even for an impedanceangle of -60 lessthan 1 Figure 4.101comparesinitial magnitudeand phase-angle j ump with the characbottom (solid) curve teristic values. Animpedanceangle of -60 has been used. The also gives therelation betweencharacteristicmagnitudeand phase-anglejump due to phase-to-phase and three-phasefaults. Sags due to single-phase faults are clearly less severe: inmagnitudeas well as inphase-anglejump. 0 0 • 0 4.6.3.2 Sagsof Type C and Type D. Knowing characteristicmagnitudeand phase-anglejump for the typeC or type D sag it is again possible calculatemagnito tude and phase-anglejump at the equipmentterminals.This results insimilar curves as for sags due tophase-to-phase faults. The main difference is t hat voltage sags due to single-phase faults are less severe than due to phase-to-phase faults. Figure 4.102 plots magnitudeversusphase-anglejump for sag typeC, for four valuesof the impedance angle. The lowest sag magnitudeat theequipmentterminals isabout 58°~, the largestphase-anglejump is 30 0 • 60 rJ 40 ~ "'0 .5 20 .[ 0 u bb fa -20 ~ f -40 -60 o 0.2 0.4 0.6 0.8 Sag magnitude in pu Figure 4.102 Rangeof sagsexperiencedby single-phaseequipmentfor sag type C and single-phasefault, impedanceangle: _60° (solid line), _40° (dashed),-20 (dotted), o(dash-dot). 0 219 Section 4.6 • Magnitude and Phase-Angle Jumps for Three-Phase UnbalancedSags 60 ~ I 40 ~ 20 .[ 0 ..2 eo ~ -20 f -40 ~ Figure 4.103 Range of sags experienced by single-phaseequipment for sag type D and -600 single-phasefault, impedance angle: 0 0 (solid line), -40 (dashed),- 20 (dotted), o(dash-dot). \ :.\. , ~ ..:-.- -- '-'~' - --~'~'~'~'~'- -~.: ..-:.;. . -~.~.~.~.~ ----,.~:j. ~..:~>'. ~--- /.;. ... -60 o 0.2 0.4 0.6 0.8 Sagmagnitudein pu 60 ! ,I \ \ I , I 40 ,, .... I I ~ \ .S 20 ~ .--. , ... '1 , \ \ 0 bb ; -20 ~ , \ u f ., , z -, .... .... - I -40 , I I ,I -60 . . Figure 4.104 Range of sags due to singlephase faults (solid curve) and due to phase-tophase faults (dashed curve). o t,..'" 0.2 0.4 0.6 0.8 Sagmagnitudein pu Figure 4.103 repeats this for type D sags duesingle-phase to faults. The lowest sag magnitudeis 330/0 with a maximumphase-anglejump of 19°. Sags due to type C and type D are merged into one p lot in Fig. 4.104 which gives the whole range of sags experiencedby single-phaseequipmentdue to single-phase faults. This rangeis smaller than the range due tophase-to..phasefaults, indicated by a dashedline in Fig. 4.104. EXAMPLE: SINGLE-PHASEFAULTS, THREE-PHASELOAD The calculations for phase..to..phase faults shown in the previous section have been repeated for single4.21, the sag magniphase faults.For single-phase faults at the various voltage levels in Fig. tude, phase-angle jump, and type have been calculated for delta..connected (three-phase) load at 660 V.Equations(4.108) and (4.109) have been derived for a system with equal positive, negative and zero-sequence impedance. This is a good approximationfor the (solidly grounded) 132kV system but not for the(resistance-grounded) 11 kV and 33kV systems. At 400 kV the source impedance is mainly determined by overhead lines, that sothe zero-sequence source impedance is larger than the positive-sequence value. To calculate characteristic the magnitudeof three-phase unbalanced sags due to single-phase faults, we can first calculate phase-to-neuthe tral voltage in the faulted phase according to (4.40). Characteristicvalues areobtainedfrom this by applying (4.108) and (4.109). Alternatively we can calculate the complex phase-to- 220 Chapter4 • VoltageSags-Characterization 5..-----.------r----...----.----..- l ~ o _------------- _ . ---6 -5 .S Qc g-10 ."""" ~ ; -15 j ~-20~ -25 0 . _, 0.2 _---'-_ 0.4 0.6 0.8 Sagmagnitudein pu -..L.. --L-_ _ .....L---' Figure 4.105 Characteristic magnitude and phase-angle j umpfor sags due to single-phase faults in the example supply in Fig. 4.21, experienced by three-phase load-connected phase-to-phase at 660V-solid line: II kV, dashed line: 33kV, dotted line: 132kV, dashdot line: 400kV. 2 transformerto these.A type 2 transformerreground voltages at the pee, and apply a type moves the zero-sequence voltage and results in a three-phase unbalancedsagof type D. Magnitude and phase-angle jump of the worst-affected phase are equal to characteristic the values. In other words, thecharacteristiccomplex voltage can be obtained by subtractingthe zerosequence voltage from the voltage in the faulted phase atpee. the The results are shown in Fig. 4.105. We seethat single-phase faults at11 kV and 33kV cause only a small drop in voltage, but amoderatephase-angle jump. This is due to the resistance groundingapplied at these voltage levels, Sagsoriginating in the 132kV and 400 kV networks show a much largerd rop in voltage magnitudebut a smaller phase-angle jump. Note that the curves for sags due to 400 Vkfaults do notstartat 33°A. voltage as expected for solidly-grounded systems. The reason that is the source impedance in PAD-400 mainly consists of overhead lines. For faults Therefore the zero-sequence impedance is larger thanthe positive-sequence impedance. in the direction of PEN, the source impedances ZSI are = 0.084+ jl.061, Zso =0.319+ j2.273, which gives for the initialphase-to-neutralvoltage duringa terminal fault: Van = 1 - 22 3ZS1 Z Sl + so • = 0.2185+JO.0243 (4.110) The characteristicmagnitudeat a lower voltage level is found from v.: = H·+~ VanI= 0.519 (4.111) For single-phase faults in thedirection of EGG we find: Van = 0.3535 - jO.0026 and Vchar = 0.571. This is amoderateversion of the effect which leads to very shallow sags in resistance-grounded systems. Notethat we still assume the system to be radial, which gives an erroneousresult for single-phase faults at 400 kV. This explains the difference in resulting voltage sags for a terminal fault in the two directions. The actual value is somewhere between 0.519 and 0.571. The difference is small enough to be neglected here. Figure 4.105 does not plot the sag type: faults atkV33lead to a type C sag; faults at 11kV, 132kV, and 400 kV cause a sag of type D at theequipmentterminals for delta-connected load. At the equipmentterminals it is not possible to distinguish between a sag due to a single-phase fault and a sag due to phase-to-phase a fault: they bothcause sags o f type C or type D. Therefore, we have merged Figs. 4.97 and 4.105 into one figure. The result is displayed in Fig. 4.106, showing characteristicmagnitudeand phase-angle j ump of all three-phaseunbalancedsags due to singlephase andphase-to-phase faults, as experienced bydelta-connected a three-phase load at 660 V. We seethat the equipmentexperiences the whole range of magnitudes and phase-angle jumps. These have to be considered when specifyingvoltage-tolerance the requirements of equipment. To 221 Section 4.6 • Magnitudeand Phase-AngleJumpsfor Three-PhaseUnbalancedSags ~ 0 ~ -5 tt \\ _--------- == 0 .9 c. § -10 .~ i ; -15 J ~ -20 Figure4.106Characteristicmagnitudeand phase-angle jump for three-phase unbalanced sags in Fig. 4.21, experienced by three-phase - 25O'------.L---L-----'. 0.4 0.6 0.8 0.2 delta-connectedload-solidline: type C, Sagmagnitudein pu dashed line: type D. J __ - . - - be able to fully interpret these results, twomore dimensionsare needed. At first, one has to realize that not all sags areof equalduration. Typically sags due to11 kV and 33 kV faults are of longer duration than those due to 132kV and 400kV faults. What is also different for different sags is itslikelihood. Roughly speakingone can say that deepersags are less likely than shallower sags. We will come back to probabilities in detail in Chapter 6. To include magnitude,phase-anglejump, duration,and probability in one, two-dimensional,figure is very difficult if not impossible. EXAMPLE: SINGLE-PHASE FAULTS, SINGLE-PHASE LOAD The magnitude and phase-anglejump have been calculatedfor voltage sagsdue to single-phasefaults, experiencedby single-phasestar-connectedload. For this we havecalculatedeither the phaseto-phase voltage, or the phase-to-groundvoltage minus the zero-sequencevoltage, at the faulted voltage level. For a single-phasefault at 11 kV, star-connectedload at 420 V experiences a sagof type C. The complex voltages at the equipment terminals are equal to the phase-to-phase voltagesat the pee,The samecalculationmethodcan be used forsingle-phase faults at 132 kVand at 400 kV. Single-phasefaults at 33 kV lead to sagsof type D. The complex voltagesat the equipmentterminalscan be calculatedas the phase-to-groundvoltagesat the pee minus the zero-sequencecomponent.The results of these calculationsare shown in Fig. 4.107. We seethat the voltage never drops below 500/0, and that the phase-anglejumps are between-30° and +30°. Faults at 11 kV and 33 kV again only causeshallow sags due to the system beingresistance-grounded. Due to a 33 kV fault, the load can even experiencea small voltage swell. Faults at 400kV are also somewhatdampedbecausethe zero-sequence source impedanceis about twice the positive-sequencevalue. Therefore, sags due to singlephasefaults are milder than expectedfor a solidly-groundedsystem. In the 132 kV system, the zero-sequencesource impedanceis even a bit smaller than the positive sequencevalue, thus V they appearas a typeC in which the drop in phasevoltages leadingto deep sags. But at 420 is not below 500/0. For this specificsystem,single-phasefaults do not causevery deep sags for star-connectedload. Note that this is not a generalconclusion.Had the 11 kV/420 V transformer beenof type Dd, the equipmentwould have experiencedvoltagedropsdown to 300/0 (see Fig. 4.105). To get acompletepictureof all sagsexperiencedby the single-phaseload, we havemerged Fig. 4.87 (three-phasefaults), Fig. 4.98 (phase-to-phasefaults), and Fig. 4.107 (single-phase faults), resulting in Fig. 4.108. Here we see the wholerange of values both in magnitudeand in phase-anglejump. 222 Chapter4 • VoltageSags-Characterization 60 ~ 40 Go) ~ ~ .S 20 ~ 0 '~ Go) ~ S -20 I ~ f Figure 4.107 Magnitudeand phase-angle jump for sags due tosingle-phasefaults in the examplesupply in Fig. 4.21, experiencedby single-phaseload-connectedphase-to-ground at 420V-solid line: II kV, dashedline: 33 kV, dotted line: 132kV, dash-dotline: 400kV. -40 -60 0.2 0 0.4 0.6 0.8 Sag magnitude in pu 60 , I r , I ~ 40 .S 20 j ~~ \ (\ \"" ' .~_---- ~~'_-_--~~~ ~ ~------=-,-~~~'~~-~J~-- 0 ------ Ii - 20 I /~ ~ ~ M f ...... : .......... \'" -40 ~ ,, , / / V / I I -60 I o 0.2 0.4 0.6 0.8 Figure 4.108 Magnitudeand phase-angle jump for all sags in theexamplesupplyin Fig. 4.2), experiencedby single-phaseloadconnectedphase-to-groundat 420 V-solid line: I) kV, dashedline: 33 kV, dotted line: 132kV, dash-dotline: 400kV. 4.8.4 Two-Phase-to-Oround Faults The analysisof two-phase-to-groundfaults does not differ from the treatmentof phase-to-phase faults. We saw inSection4.4.4 that two-phase-to-groundfaults lead to three-phaseunbalancedsagsof type E, type F,or type G. Type E is a rare type which f ault, the type E we will not discusshere. Like type B for the single-phase-to-ground containsa zero-sequencec omponentwhich is normally not transferredto the utility voltage,and neverseen bydelta-connectedequipment. For type F and type G we can againplot characteristicmagnitudeagainstphaseanglejump. The relation betweenthe characteristicmagnitudeandphase-angle j ump of the unbalancedthree-phasesag isidentical to the relation betweenthe initial magnitude and phase-anglejump, i.e, magnitudeand phase-anglejump of the voltage in the faulted phasesat the pee.This relation is describedby (4.83) and (4.86) and is shown in Fig. 4.86. 4.6.4.1 Sagsof Type F. A detailedphasordiagramof a sagof type F is shown in Fig. 4.109. Like with a type D sag, one phasedrops significantly in magnitude, and the other two phasesless.The differencewith the type D sag is in thelatter two Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-PhaseUnbalancedSags 223 Figure 4.109Phasordiagramfor three-phase unbalancedsag of type F with characteristic magnitudeV and characteristicphase-angle jump t/J. -! phases.With a type D sag theydrop from ± !jJ3 to ± !jJ3, but with a type F sag theydrop significantly more: to ±!jJ3. The lowest magnitudefor a type D sag is 86.60/0, whereasit is 57.7% for a type F sag. In the upper triangle indicatedin Fig. 4.109 wecan again apply the cosineand sine rule toobtain magnitudeand phase-anglejump at the equipmentterminals.Note that in Fig. 4.109, rP < 0, rPb > 0, and rPc < O. The cosinerule gives (4.112) which resultsin an expressionfor the voltagemagnitude Vc: (4.113) The sine rule in thesametriangle gives sin(30° + rPc) ! vJ3 sin(120° - rP) =----- (4.114) Vc The phase-anglejump rPc follows as 0 f/Jc = -30 + arcsin{V~Sin(120° - f/J)} (4.115) The same rules can be applied to the lower triangle, which leads to the following expressionsfor magnitude Vb and phase-anglejump rPb: (4.116) 224 Chapter 4 • VoltageSags-Characterization 60 l ~ 40 .S 20 ~ ...., 0 ---------':: u tih fa -20 . ~ ~ f -40 -60 o 0.2 0.4 0.6 0.8 Sag magnitude in pu Figure 4.110Magnitudeand phase-angle jump at theequipmentterminals for a type F sag, due to atwo-phase-to-groundfault. The curves are given for an impedance angle of 0 (dashed line) and_600 (solid line). (4.117) From theseequationswe can againcalculatemagnitudeand phase-anglejump at theequipmentterminals,e.g., as afunction of thedistanceto the fault.Figure4.110 plots magnitudeversusphase-angle j ump for a type F sag due to two-phase-to-ground a fault. We seethat one phase behaves again like the sag due three-phase to a fault. The other two phase aresomewhatlike the two phases with a shallow sag in the type D sag shown in Fig. 4.95. The difference is thatfor a type F sag the voltages show a significantly larger drop. Themaximumphase-anglejump for these two phases is again 30°. 4.6.4.2 Sagsof Type G. A detailedphasordiagramfor a type G sag is shown in Fig. 4.111. The complex voltage in phasedrops a to a valueof ~ (no drop for a bandc drop to a valueof for sag of type C); the complex voltages in phase type C). . -! (-! Figure 4.111 Detailedphasordiagram for three-phaseunbalancedsag of type G with characteristicmagnitudeV and characteristic phase-anglejump l/J. 225 Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-Phase UnbalancedSags The cosine ruleand the sine ruleapplied to the triangle on the right give the following expressions: 2 4 a 9 V = - 12 + -9 V 2 V 0 - 2 x - x - cos( 180 + cP) (4.118) = sin(-4>0) (4.119) 3 sin(180°+ 4» 3 !V Va This leadsagainto expressionsfor magnitudeand phase-anglejump at the equipment terminals. (4.120) 4>0 = arcsin(3~0 sin4>) (4.121) Repeatingthe calculationsfor the other trianglesgives expressionsfor magnitudeand phase-anglejump in the other two phases.Note the angle 1010 and the factor!../7. These originate from the triangle formed by the complex numbers 0, and -!, -!±!jv'3. (4.122) (4.123) Vc = ~J 1 + 7V2 - 2V.J7cos(lOI° + 4» 4>c = 60° - arcsinG.J7~ sin(lOlo + 4») (4.124) (4.125) The resultsfor type G sags areshownin Fig. 4.112. We seethat the type G sag is somewhatsimilar to the type C sag, as s hown in Fig. 4.92. Unlike the phase-to-phase 60 \ \ \ \ \ \ / / I Figure4.112Magnitudeand phase-angle jump at theequipmentterminals for a type G sag, due to atwo-phase-to-groundfault. The curves are given for an impedance angle of 0 (dashed line) and-600 (solid line). I I I , 0.2 , 226 Chapter4 • VoltageSags-Characterization fault, two-phase-to-groundfaults cause two voltages to drop to 33% instead of50%. For faults somedistanceaway from the pee the voltage magnitudecan even become a bit less than 33% due to the initial phase-anglejump. Another difference with the phase-to-phasefault is that all three phasesdrop in magnitude.The third phase, which is not influenced at all by aphase-to-phase fault, may drop to 67% during a two-phase-to-groundfault. 4.6.4.3 Rangeof Magnitude and Phase-Angle Jump. Merging Fig. 4.110 and Fig. 4.112 gives the whole range of magnitudesand phase-anglejumps experienced by a single-phaseload due totwo-phase-to-groundfaults. In Fig. 4.113 the area due to two-phase-to-groundfaults (solid curve) iscomparedwith the area due to phaseto-phasefaults (dashedcurve). We seethat there arecertaincombinationsof magnitude andphase-anglejump which can occur due tophase-to-phase faults but not due to two-phase-to-groundfaults, but also theother way around. These curves have beenobtainedunder the assumptionthat zero-sequence and positive-sequence impedances are equal.For a zero-sequenceimpedancelarger than the" positive-sequence sourceimpedance,the resulting sags due totwo-phase-to-groundfaults are closer toward sags due tophase-to-phasefaults. The results arethat even a larger rangeof magnitudeand phase-anglejumps can be expected. An increasing zero-sequence impedance will meanthat the area enclosed by the solid curve in Fig. 4.113 will shift toward the area enclosed by the dashedcurve. Thelatter is reached for an infinite zero-sequence impedancevalue. 60 , ... 1 / \ ~ ~ 008 .5 \ 40 \ \ , - .... \ 20 \ \ ~ Ot----~----·, , '''''''''\ «> bo ; -20 o ]a.- -40 I I -60 0.2 0.4 0.6 0.8 Sag magnitude in pu Figure 4.113Range ofmagnitudeand phaseanglejump at theequipmentterminals due to phase-to-phase (dashed curve) and twophase-to-groundfaults (solid curve). EXAMPLE: TWO-PHASE-TO-GROUNDFAULTS,SINGLE-PHASELOAD For the same example system as used before (Fig. 4.21) the complex voltages at the equipment terminals due totwo-phase-to-groundfaults have been calculated. Characteristicmagnitude and phase-angle j ump due to atwo-phase-to-groundfault are the same as due to a phase-tophase fault.For three-phasedelta-connectedequipmentwe can directly use the results obtained for phase-to-phase faults in Fig. 4.97.For two-phase-to-groundfaults, the solid lines refer to sags of type G, the dashed lines to sags of type F. two-phase-to-ground A fault at 1I kV leads to a sagof type F for delta-connectedload, according to Table 4.13. The Dy IlkV/660 V transformerchanges this into a sag of type G, according to Table 4.14. Two-phase-to-ground faults at 33 kV lead to sags of type F, and faults at 132kV and 400kV to type G. Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-Phase UnbalancedSags 227 60 I I I I -60 I o 0.2 0.4 0.6 0.8 Sagmagnitudein pu Figure 4.114 Magnitude and phase-angle jump at the equipment terminals due to twophase-to-ground faults in Fig. 4.21, experiencedby single-phase load-connected t 1 kV, phase-to-ground at 420 V - solid line: dashed line: 33 kV, dotted line: 132 kV, dashdot line: 400 kV. For star-connectedsingle-phase load, thesituation is completely different. The zerosequence source and feeder impedances influence the voltages during a two-phase-to-ground fault, but notduring a phase-to-phase fault. The voltage sags experienced by single-phase equipment are shown in Fig. 4.114. Faultsat 11kV, 132kV, and 400kV cause sags of type G, in which II kV the zero-sequence one phase shows a deep sag and the otherphases two a shallow sag. At source impedance is much larger than the positive-sequence one, due to the resistance grounding of this voltage level. The resulting sag is very close to the type D sags duephase-to-phase to a fault. The large zero-sequence impedance makes that the ground connectionof a two-phase-togroundfault does notcarrymuch current. The voltage magnitudein the two phases with shallow sags is thus only down toa bout 900/0. For faults at 132kV, which is solidlygrounded,these voltages are down toabout 55°~. The 400kV system is also solidlygrounded,but the line impedancedominatesthe source impedance, making that the zero-sequence impedance is more than twice as large as the positive-sequence impedance. In the phase with the largestdrop, voltage the voltagemagnitudeis aboutthe same for the three voltage levels. Faultsat 33 kV will cause a type G sag. As the system is resistance groundedthis sag is very close to a type C sag due to a phase-to-phase fault. 4.8.5 High-Impedance Faults In all the previouscalculationsin this chapter,we have assumed the fault impedance to be zero. The a rgumentationfor this wasthat the fault impedancecould be incorporatedin the feederimpedance,ZF in (4.9). Thisargumentstill holds as long as the magnitudeof the sag isconcerned,but the phase-anglejump can be significantly affected. We will first addressthree-phasefaults and after that single-phasefaults. High-impedancefaults are more likely forsingle-phase-to-groundfaults than for three-phasefaults. 4.6.5.1 Three-Phase Faults.Consider again the basic voltage divider expresRtit explicitly included: sion (4.9), but this time with the fault resistance V _ sag - ZF+Rfll Z s + Z F + Rfll (4.126) In many cases the source impedanceand the feederimpedanceare largely reactive, whereas the faultimpedanceis mainly resistive. The angle between source impedance 228 Chapter 4 • VoltageSags-Characterization and feeder plus fault impedance gets close to 90°, which can lead to very large phaseangle jumps. The fault resistance only noticeably affects the voltage ifF I12 « Rfll' thus for faults close to thepoint-of-commoncoupling with the load.For zero distance to the Zs =}Xs): fault we get for the complex voltage (with V - sag - ~t }Xs + Rflt (4.127) The fault resistance is normally not more than a fraction of the source reactance, in which case the sag magnitudeis the ratio of the fault and the source impedances with a phase-anglejump equal to almost 90°. To quantify the influence of the fault resistance, the complex voltage during the sag was calculated as a function of the distance to the fault for three-phase faults at 11 kV in Fig. 4.21.The calculationshave beenperformedfor a zero fault resistance and 10%,200/0, and 300/0 of the (absolutevalueof the) source for fault resistances equal to impedance. The sag magnitude(the absolutevalue of the complex voltage) plottedin is Fig. 4.115as a function of the distance to the fault. As expected the influence on the sag magnitudeis limited to small distances to the fault. The fault resistance increases the impedance between the pee and the fault, and thus reduces the voltage drop at the pee. The phase-anglejump is much more influenced, as shown in Fig. 4.116. The For increasing fault resistance the maximum phase-anglejump reaches values up to 80°. phase-anglejump does not reduce much. 4.6.5.2 Single-Phase Faults.To assess the effect of high-impedance singleof phase faults on the voltage at the equipmentterminals, we use the classification three-phaseunbalancedsags again. At first we consider solidly-groundedsystem, a for which we can 'assumethat the two non-faulted phase voltages remain at their pre-fault values. Inother words, we have a clean type B sag. The voltage in the faulted phase is influenced by the fault resistance as shown in 4.115 Figs. and 4.116. At the equipmentterminals the sag will be of type C or D. Magnitude and phaseanglejump at theequipmentterminals are shown in Fig. 4.117for a type C sag and in Fig. 4.118for a type D sag.In' Fig. 4.117we see how an increasing fault resistance increases theunbalancebetween the two affected phases. Although the characteristic 0.8 ~ .5 ~ 0.6 .E ie 0.4 ee ~ 00 1 2 3 4 Distanceto the fault inkilometers 5 Figure 4.115 Sag magnitude versus distance for three-phase faults with fault resistances equal to zero (solid line),100/0 (dashed line), 20°,lc, (dash-dot line), and30% (dotted line)of the source impedance. Section 4.6 • Magnitudeand Phase-Angle Jumps for Three-PhaseUnbalancedSags 229 o 8-10 -8~ -20 - .8 -30 I e, , , § -40 . • I ; I , , I M -60 -70 -80 anglejump for three-phase faults with fault resistances equal to zero (solid line), to°A. (dashed line),200/0 (dash-dotline), and 30% (dotted line) of the source impedance. I I u ~-50 f I , , ."""'\ Figure4.116Sagmagnitudeversus phase- I -9°0 I I I I 0.2 0.4 0.6 Sag magnitude in pu 0.8 magnitudeincreases due to the fault resistance, one of the phasesactually drops in voltage. The characteristicmagnitude is the difference between the two affected that the phase-anglejump at the equipmenttermphases in the figure. We also see inals only slightly exceeds 30°, despite the very large initial phase-anglejump. The -31.9°. largest phase-anglejump occurs for a30% fault resistance at zero distance: In Fig. 4.118 we seethat for a type D sag, the fault resistance increases the phaseangle jump in the phasewith the large voltagedrop, and that it raises oneof the 300/0 cause a small other two voltages and reduces the other. Fault resistances above swell in oneof the phases. For Figs. 4.117 and 4.118, the 11 kV system was assumed to solidlygrounded. be Therefore, the zero-sequence source impedancewas made equal to the positivesequence value. In reality this system is resistive grounded:positive- andzero-sequence source impedanceare significantly different. Thephase-to-neutralvoltage is much lower in this case. Tocalculatethe phase-to-neutralvoltage a slightly revised version of (4.38) has been used: 32s1 V-I _ an - 22F1 + ZFO (4.128) + 2Z S1 + ZSO + 3R.Jzt 30 , ,, , , \ en Q) tb 20 .5 10 ~ \ , , '\ , " '" ...... '..<:~':.., ... "":~ .. ~ e ::s .'""'\ 0 Q) bi> ; -10 Figure 4.117Magnitudeversusphase-angle jump at theequipmentterminals for singlephase faults in a solidlygroundedsystem, sag type C; fault resistances equal to zero (solid line), 10% (dashed line),20% (dash-dotline), and 300/0 (dottedline) of the source impedance. "/~~. /1, I ~ f ,1'- " 1,- -20 III," I': I , " -30 I 0 0.2 I .' : :' : 0.4 0.6 0.8 Sag magnitudein pu 230 Chapter4 • VoltageSags-Characterization 30 (I) u ~ 20 \ '\ u "T;:) .S \ ",\\ 10 . ',\\ , .. ~,~ Figure 4.118 Magnitude versus phase-angle jump at the equipment terminals for single.. phase faults in a solidly grounded system, sag type D, fault resistances equal to zero (solid line), 10% (dashed line),20% (dash-dot line), and 30% (dotted line) of the source impedance. -30 o 0.2 0.4 0.6 0.8 Sag magnitudein pu 5r----,-----.....--------.--------. .. :--.~~~'?o' " .. / ,. ~. /~:" ,1./, : 1/' i, : :'" \ \ \ \ \ " " "...' . -10 '------'--------'-------'-------' 0.95 t 1.1 0.9 1.05 Sag magnitudei ....pu Figure 4.119 Magnitude versus phase-angle jumps at the equipment terminals for single.. phase faults in a resistance-grounded system, sag type D; fault resistances equal to zero (solid line), 50% (dashed line),100% (dashdot line), and150°A. (dotted line) of the source impedance. The influence of the fault resistance is small in this case, as can be seen in Fig. 4.119. j ump at theequipmentterminalsare plottedfor a type The magnitudeand phase-angle D sag. Due to the small fault currentsarc resistances can reach much higher values in a resistance-grounded systemthanin a solidly-groundedsystem. In thecalculationsleading to Fig. 4.119 fault resistances equal to 50%, 1000/0, and 1500/0 of the positivesequence source impedanceWere used. The main effectof large fault resistances is that the sag becomes less severemagnitudeand in in phase-anglejump. 4.8.8 Meshed Systems All calculationsin Sections 4.4and 4.5 were based on the assumptionthat the system is radial; thusthat we canuniquelyidentify a point-of-commoncoupling(pee), a sourceimpedanceZs, and a feederimpedanceZF, as were shown in Fig. 4.14. From Fig. 4.14 weobtainedthe basicvoltagedivider equationfor the complex sag voltage: V-I _ sag- Zs ZS+ZF (4.129) 231 Section 4.7 • OtherCharacteristicsof Voltage Sags In case the system loaded,we is can useThevenin'ssuperpositiontheoremwhich states that the voltageduring the fault equals the voltage before the fault plus the change in voltage due to the fault: z, (0) V.vag = Vpee - Z s+ Z V(O) F f (4.130) with V~~e the pre-fault voltage at the pee andV}O) the pre-fault voltage at the fault position. Notethat the source impedance Zs includes the effecto f loads elsewhere in the system. For a meshed system we need matrix methods to calculate voltage during the fault, asintroducedin Section 4.2.5. Weobtainedthe following expression (4.24) for the voltageV k at node k due to a fault at node f: V k = V~O) _ Zkf V(O) Zff f (4.131) with ViOl the voltage at nodek before the fault andvjO) the voltage at the fault position Comparingthis before the fault, andZij element ij of the node impedance matrix. equationwith (4.129) we seethat they have the same structure.The voltage divider model can be used for meshed systems, when the following source and feeder impedances are used: z, = Zk/ ZF = Zff - (4.132) Zk/ (4.133) The main difference isthat both Zs and ZF are dependenton the fault location. Equivalentsource and feeder impedances canobtainedfor be positive-, negative-, and zero-sequence networks,and all the previously discussed analysis can still be applied. 4.7 OTHER CHARACTERISTICS OF VOLTAGE SAGS 4.7.1 Point-on-Wave Characteristics The voltage sagcharacteristicsdiscussedhitherto (magnitude, phase-angle jump, three-phaseunbalance)are all related to thefundamental-frequency componento f the voltage. They require the calculationof the rms value of the voltage or the complex voltage over aperiod of one half-cycle or longer. We saw earlier how this leads to an uncertaintyin the calculationof sagduration.To obtaina moreaccuratevalue for the sagdurationone needs to be able to determine"start" and "ending" of the sag with a higher precision.For this one needs to find the so-called "point-on-waveof sag initiation" and the "point-on-wave of voltage recovery" [38], [134]. Both require more advanced analysis techniques, which are still under development. We will see in the next chapterthat the point-on-wavecharacteristicsalso affect the behavior of some equipment. 4.7.1.1 Point-on-Waveo f Sag Initiation. The point-on-waveof saginitiation is the phase angle o f the fundamentalvoltage wave at which the voltage sag starts. This anglecorrespondsto the angle at which theshort-circuitfault occurs. As most faults are associated with a flashover, they are more likely to occur near voltage maximum than near voltage zero. In the sag shown in Fig. 4.1 point-on-waveof the sag initiation is close to voltage maximum. In Fig. 4.9 sag initiation takes placeabout 35° 232 Chapter4 • VoltageSags-Characterization after voltage maximum, at least in the phase with the largest voltage drop. In other phases the event startsat anotherangle comparedto the fundamentalvoltagein that phase. When quantifying the point-on-wavea referencepoint is needed. Theupward zero crossingof the fundamentalvoltage is anobvious choice. One is likely to use the last upward zero crossing of the pre-event voltage as reference, as this closely resembles thefundamentalvoltage. The sag shown in Fig. 4.1 partly is repeatedin Fig. 4.120: one cycle (1/60 o f a second)startingat the lastupwardzero crossing before sag initiation. We seethat the point-on-waveof saginitiation is about 275°. A closer look at the data learns that this point is between 276° and 280°. The slope at the beginningof the sagactually takes 4°, orabout 185 j.LS. This is probably due to the low-passcharacterof the measurementcircuit. was in Figure 4.12I plots all three phases of the sag for which one phase plotted Fig. 4.120.For each phase, the zero point of the horizontalaxis is the lastu pwardzero crossingbefore thestart of the event inthat phase. We see t hat the point-on-waveis different in the three phases. This obviousif is one realizesthat the eventstartsat the samemomentin time in the three phases. As the voltage zero crossings are 120° shifted, 2 --r-·_···~----·r--·---r----'-----r-1 1.5 0.5 ; ~ 0 F--------~-----ft--~--t -0.5 -1 -1.5 - 2 '----_-'--- o i_: o '-: o 50 - A . - - _ - - ' - - _ - - - ' - _ - - ' -_ _ -L..J 100 150 200 250 300 350 Angle of voltage wave in degrees 50 100 150 50 100 150 ~~::1 200 250 200 250 300 350 /1 300 350 i_:P=~ o 50 Figure 4.120Enlargemento f the sag shown in Fig. 4.1indicatingthe point-on-waveof sag initiation. 100 150 200 250 300 Angle of voltage wave in degrees Figure 4.121 Eventinitiation in the three 350 phases,comparedto the lastupward voltage zero crossing. 233 Section 4.7 • Other Characteristicsof Voltage Sags the point-on-wavevalues differ by 120 °. In casephase-to-phase voltages are used, the resultingvalues are again different. When quantifying point-on-wave it is essential to clearly define the reference . 4.7.1.2 Point-on-Waveof Voltage Recovery. The point-on-waveof voltage recovery is the phase angle of the fundamentalvoltage wave at which the main recovery takes place. We saw before that most existing powerquality monitors look for the point at which the voltage recovers to 90% or 95% of nominal the voltage. Note that there is in many cases no link between these two points . Consideras an example of this section takes again the sag shown inig. F 4.1. Voltage recovery in the meaning placeabout 2.5 cycles after sag initiation, even though the voltage does not fully- re cover for at leastanothertwo cycles, as can be seen in Fig. 4.3. Voltage recoverycorrespondsto fault clearing, which takes place currentzero at crossing. Because the power system is mainly inductive,current zero crossing corresponds to voltage maximum . Thus we expect points-on-wave of voltage recovery to be around90° and 270°. This assumes that we use the pre-event fundamentalvoltage as reference,not the during-event voltage . It is the pre-event voltage which drives the fault currentand which is thus 90 ° shiftedcomparedto the faultcurrent.The recovery of the sag in Fig. 4.120 is shown in Fig. 4.122. The recovery is, at least in this,case slower than the saginitiation. The shape of the voltage recovery correspondsto the so-called " transient recovery voltage" well-known in circuit-breakertesting. The smoothsinusoidal curve in Fig. 4.122 is the continuationof the pre-eventfundamentalvoltage. Considering thestart of the recovery , we find a point-on-waveof 52°. If we further assume this to be the moment of fault-clearing taking place currentzero, at we seethat the currentlags the voltage by 52 °, which gives anX/R ratio at the fault position equal to tan-I(52 °) = 1.3. For a two-phase-to-ground or three-phasefault, fault clearing does not take place in all three phases at the same time . This could make adeterminationof the point-onwave of voltage recovery difficult. Anunambiguousdefinition of the referencepoint and phase is needed to apply this conceptto three-phaseunbalancedsags. 1.5 0.5 j s 0 - 0.5 -I Figure 4.122 Enlargement of Fig . 4.1 showing thepoint-on-waveof voltage recovery. The smoothcurve is the continuationof the pre-sagfundamental voltage. - 1.5 o 50 100 150 200 250 Time in degrees 300 350 234 Chapter4 • VoltageSags-Characterization 4.7.2 The MI••ing Voltage The missing voltage is a nothervoltage sagcharacteristicwhich has beenproposed recently [134]. The missing voltage is a way o f describing the change in momentary voltage experienced by the equipment.The conceptbecameimportantwith the dimensioning of series-connected voltage-sourceconvertersto compensatefor the voltage drop due to the fault. We will see inChapter7 that the voltage injected by the series compensatoris equal to the missing voltage: the difference between the voltage as it would have beenwithout the sag, and theactual voltage during the sag. 4.7.2.1 The Complex Missing Voltage. One can thinkof the missing voltage as a complex voltage (aphasor),being the difference in the complex plane between the pre-event voltage and the voltage during the sag. Theabsolutevalue of this complex missing voltage can be directly read from a plot like shown in Fig. 4.83. In Fig. 4.83 the missing voltage is the distancebetween the complex voltage during the sag (which top-right corner of the diagram (the point is on one of the three curves) and the I + jO). EXAMPLE Consider a sag on a 50 mrn? undergroundcable, like in Fig. 4.83, with a sag magnitudeof 600~. If the pre-event voltage was 100%, the drop in rms value of the vola tage is40°A.. Having no furtherinformation one would be tempted to say thatcompensator should inject a voltage with an rms value equal to 40% of nominal. Looking in the complex plane, we see that a magnitudeof 60% correspondsto a complex voltageV = 0.45 - jO.39. The missing voltage is the difference between the pre-fault voltage and the voltage during the sag, thus 117- = 0.55+ jO.39. The absolute value o f the missing voltage is 67% in this example.Comparethis with the 40% drop in rms voltage. The complex missing voltage can also calculatedfrom be the magnitude V and the phase-anglejump l/J of the sag. The complex voltage during the sag is V = V cos q,+ jV sin q, (4.134) The missing voltage is simply 1- V= 1- Vcosq,-jVsinq, (4.135) =JI - (4.136) with as absolutevalue Vmiss= 11 - VI V2- 2 V cosl/J When we neglect the phase-anglejump, thus assumethat V = V, the missing voltage is simply Vmiss = 1 - V. We can assess the errormade by writing 1 - V = JI + V 2 - 2V. Comparingthis with (4.136) gives for the difference between the exact andapproxthe imate expression for the missing voltage: 2 Vmis,f - -2 V miss = 2V(1 - cosq,) (4.137) 4.7.2.2 The Missing Voltage in Time Domain. The conceptof missing voltage can become much more useful by extending it to time domain. A very first step would be to look at the difference between the fundamentalpre-event voltage and the fundamentalduring-eventvoltage. Butthat would not give any extra information comparedto the complex missing voltage. 235 Section 4.7 • Other Characteristicsof Voltage Sags 2 .-----.,..---.,.------r----,------,-----, i~ 0 -1 234 Timein cycles 5 6 2.---r---,-----.-----r-----r-----. u 01) Figure 4.123·T ime-domainvoltage measurementtogetherwith pre-event fundamentalvoltage(top curve) andthe timedomainmissing voltagebeing thedifference of those two(bottom curve). ~ ~ 0 ..............."'--'~ -1 -2 0 234 Time in cycles 5 6 In the top part of Fig. 4.123 the sag from Fig. 4.1 has been plotted again. Togetherwith the actualtime-domainvoltage wave, thefundamentalpre-event voltage has beenplotted.The latter is obtainedby applyinga fast-Fourier-transformalgorithm to the first cycle of the voltage wave form. From the complex coefficient for the fundamental term in theFourierseries Ct , the (time-domain)fundamentalcomponentof the voltage can becalculated: (4.138) This fundamentalc omponentof the pre-eventvoltage (pre-eventfundamentalvoltage, for short) is the smoothsinusoidalcurve in the toppart of Fig. 4.123. The missing voltage is calculatedas the difference between the actualvoltage and the pre-eventfundamentalvoltage: (4.139) This missing voltage isplottedin the bottompart of Fig. 4.123. Before theinitiation of the sag 'there isobviously no fundamentalcomponentpresent; during the sag the fundamentalcomponentof the missing voltage is large; after the principal sag (after fault clearing) a smallfundamentalcomponentremains. The reason for this becomes clear from theuppercurve: the voltage does not immediately fully recover to its preevent value. Figure4.124repeatsthis for the voltage in oneof the non-faultedphases, for the same event as in Fig. 4.123 and Fig. 4.1. In the top curve wethat seethe during-event voltage has alarger rms valuethan the pre-eventvoltage. In termsof rms voltages, we would call this an increase in voltage: a voltage swell. looking But at the missing voltage it is not possible to saywhetherthe underlyingevent is a swell or a sag. This might be shouldrealizethat this seen as adisadvantageof the missing voltage concept. But one conceptis not meant to replace theother ways of characterizingthe sag;instead,it should giveadditionalinformation. Finally, Fig. 4.125 plots the missing voltage in all three phases. As expected for a single-phase-to-ground fault, the missing voltage in the two non-faultedphases is the same and in phase with the missing voltage in the faulted phase. After the fault the missing voltages in the three phases form a positive sequence set. This probablydue is to the re-accelerationof induction motorsfed from the supply. 236 Chapter4 • VoltageSags-Characterization t:~ - 20 1 2 3 4 Time in cycles 5 6 f_: ~ 1 -2 0 2 3 4 Time in cycles 5 6 Figure 4.124 Measured voltage with preevent fundamentalvoltage (top curve) and missing voltage(boltom curve) during a voltage swell event. ~.:~ -2 0 I -2 0 1 - 20 I 2 3 4 5 6 ~:~ 2 3 4 5 6 ~.:~ 2 3 4 Time in cycles 5 6 Figure 4.125 Missing voltage for the three phasesof a sag due to a single-phase fault . In Figs. 4.124 and 4.125 we used the fundamentalpre-event voltage as a reference to obtain the missing voltage. The conceptof missing voltage has been introducedto quantify the deviationof the voltage from its ideal value. In otherwords: we have used the fundamentalpre-event voltage as the ideal voltage. This could become point a of discussion, as there are at least three alternatives: • Use the full pre-event waveform, including the harmonicdistortion, as a reference. One can either take the last cycle before the event or the average over a numberof cycles. Thelatter option is limited in its applicationbecause there are normally not more than one or two pre-event cycles available. • Use thefundamentalcomponentof the pre-event waveform as a reference. One can again choose between the fundamentalobtainedfrom the last cycle before the event (as was done in Fig. 4.124 and Fig. 4.125) obtain or the fundamental from a numberof pre-event cycles. • Use as a reference, sinusoidalwaveform a with the sameamplitudeand rms value as the system nominal voltage and the same phase angle as the fundamental pre-event waveform. The difference between the last two alternatives is 237 Section 4.7 • OtherCharacteristicsof Voltage Sags the same as the discussion between defining the voltage drop with reference to the pre-event rms voltage or with reference to nominal the rms voltage. Both methodshave theiradvantagesand can thus be used. But it important is to alwaysindicatewhich methodis used. 4.7.2.3 Distributionofthe Missing Voltage. An alternativeand potentially very useful wayof presentingthe missing voltage isthrough the amountof time that the missing voltage, inabsolutevalue, exceeds given values; other in words, theamount of time during which the deviation from the ideal voltage waveform is larger than a given value. In the top curveof Fig. 4.126 the missing voltage from Fig. 4.123 is shown again. But this time theabsolutevalue isplotted,insteadof the actualwaveform. We see, e.g., that this absolutevalue exceeds the value of 0.5,total a of six timesduring the event. The cumulativedurationof these six periods is 1.75 cycles. The cumulativetime during which the missing voltage in absolutevalue exceeds a given level can determinedfor be each level. The result of this calculationis shown in thebottompart of Fig. 4.126. This curve can be read as follows: the missing voltage is never larger than 1.53, isduring 1 cycle larger than 0.98, during 1.75 cycle largerthan 0.5, during two cycles largerthan 0.32, etc. The long tail in Fig. 4.126 is due to the post-faultvoltage sag as well as to the non-zeropre-event missing voltage. The latter contributioncan be removed by either using the full pre-event waveshape as a reference calculatethe to missing voltage, or by only consideringthe missing voltage samples from the instantof sag-initiationonward. Throughthe sameprocedure,distributionsof the missing voltage can be obtained for the other two phases, resulting in the curves shown in Fig. 4.127. The missing voltage in the faulted phase (solid curve) naturally is larger than in the non-faulted phases. But still, the missing voltage in the non-faultedphases is significant:during about1 cycle it exceeds a value of 0.4. We also see a small difference in missing voltage between the twonon-faultedphases: the value in phase bsomewhathigher is than in phase c. of definThe missing voltagedistributioncurve can be used as a generalized way ing the eventduration.The larger thedeviationfrom the ideal voltage one considers, the shorter the "cumulative duration" of the event. Thecumulative duration of a 2r----..---r------r----~--,-------, II) 11.5 o > .Ef 1 .~ 0.5 ~ °0 234 5 6 Timein cycles 2 r-----r---..----r---~-- Figure 4.126 Absolute value of the missing voltage (top curve) and the distributionof the missing voltage(bottom curve) for the sag shown in Fig. 4.1. 234 Cumulativetimein cycles 5 6 238 Chapter4 • VoltageSags-Characterization Cl r------r-----r---.------.---·-..----l 1.5 .2 :s ~ 1 fI'.I ~ ; ~ L .S 0.5 '- .. "" '-_'- fI'.I fI'.I - - - _-- ~ _ '_',-, .. ...., ~, .... ':..-...-_...:: :. -- ---:= "::. ----- = .... -- 0' , o 0.5 , I _L-_>______---' 1 1.5 2 Cumulative time in cycles 2.5 3 Figure 4.127 Missing voltaged istribution for phase a (solid curve), phase(dashedcurve), b and phase c(dash-dotcurve). voltage sag for a givendeviation would be defined as the t otal amountof time during which the voltage deviates more thanthe given value from the ideal voltagewaveshape. 4.8 LOAD INFLUENCE ON VOLTAGE SAGS In the calculationof sagmagnitudefor varioussystemconfigurations,in the classification of three-phasesags and in mosto f the examples, we have assumedthat the load currentsare zero. In this section we will discuss some situationsin which the load currentscan have a significant influence on the voltages during a fault. The main load having influence on the voltage during and after a sag isformed by induction and synchronousmotors as they have the largest currentsduring and after a shortcircuit fault. But we will also briefly discuss single-phase and three-phaserectifiers as they are a largefraction of the load at manylocations. 4.8.1 Induction Motors and Three-Phase Faults During a three-phasefault the voltages at the m otor terminalsdrop in magnitude. o f this drop are twofold: The consequences • The magneticflux in the air gap is no longer inbalancewith the statorvoltage. During this decay The flux decays with a timec onstantof up to several cycles. the induction motor contributesto the fault andsomewhatkeeps up the voltage at themotor terminals. • The decay in voltage causesdrop a in electrical torque: the electricaltorqueis proportional to the squareof the rms valueof the voltage. Themechanical torque in the mean time remains largely unchanged.The result isthat the motor slows down. While themotor slows down it will take alarger current with a smaller power factor. This could bring down the voltageeven more.For small voltagedrops, a new steadystatecould be reached at a lower speed, dependingon the speed-torquebehavior of the mechanicalload. For deep sags themotor will continueto slow down until it reachesstandstill, or until the voltage recovers, whichever comes first. The mechanicaltime constantof electricalmotorsis of the orderof one secondand more. Thereforethe motor will normally not have reached zero speed upon yet voltagerecovery. Section 4.8 • LoadInfluenceon Voltage Sags 239 The momentthe voltage recovers the oppositephenomenaoccur. The flux in the air gap will build up again. This causes a large inrush current, which slows down the voltage recovery. Afterthat, the motor will re-accelerateuntil it reaches its pre-event speed.During the re-accelerationthe motor againtakes a largerc urrentwith a smaller power factor, which causes post-faultvoltage a sag sometimes lasting for several seconds. The contribution of the induction motor load to the fault can be modeled as a voltage sourcebehindreactance.The voltagesource has a value o f about 1 pu at fault initiation and decays with thesubtransienttime-constant(between0.5 and 2 cycles). The reactanceis the leakagereactanceof the motor, which is between100/0 and 20% on the motor base.Note that this is not the leakagereactancewhich determinesthe starting current, but the leakagereactanceat nominal speed.For double-cageinduction machines these two can be significantly different. EXAMPLE Considera bolted fault at primary side of a 33/11 kV transformerin the supply shown in Fig. 4.21. Thetotal induction motor load connectedto the 11 kV bus is50/0 of the fault level. Theinduction motors have a leakagereactanceof 10% on the motor base. We are interestedin the voltage at secondaryside of the transformer.Consideronly the reactive part of the impedances. 33 kV and II kV fault levels:ZT The transformerimpedanceis the difference between the = 47.60/0 at a 100 MVA base. The fault level at II kV is 152 MVA, thus the total motor load is (5% of this): 7.6 MVA. The leakagereactanceof the motorsis 100/0 at a 7.6 MVA base, which is Z M = 132%at a 100MVA base. Thevoltageon secondarysideof the transformeris found from the voltage dividerequation: V/oad = Z ZT = 27% T+ Z M (4.140) To assess the increase motor in current after the fault, we use thecommon equivalentcircuit for the induction motor, consistingof the seriesconnectionof the statorresistanceRs, the leakagereactanceXL and theslip-dependentr otor resistance ~, with s the motor slip. The motor impedanceis ZM = s,+jXL + RR s (4.141) The changeof motor impedancewith slip has beencalculatedfor four induction motorsof four different sizes.Motor parametershave beenobtainedfrom [135], [136], and themotorimpedancehas beencalculatedby using(4.141). The results are shown in Fig. 4.128. For each motor, the impedanceat nominal slip is set at I pu, and the absolutevalue of the impedanceis plotted betweennominal slip and 25% slip. We m otor see for eachmotor a decrease inmotor impedance,and thus an increase in current,by a factor of aboutfive. The decrease inimpedanceis much faster for large machinesthan for smaller ones. If we assume the voltage to recover to 1immediatelyupon pu fault clearing, the currenttakenby themotoris the inverseof the impedance(bothequal to 1pu innormal operation).The path of the currentin the complex plane is shown in Fig. 4.129. The pathis given for an increase in slip from its nominalvalue to 250/0. The positive real axis is in the direction of the motor terminal voltage. For small motors we seepredominantly an increase in resistive c urrent, for large motors the main increase is in the inductive part of the current. When the slip increases further, even the resistivepart 240 Chapter4 • VoltageSags-Characterization I: 8 -ae 0.8 Jg ,: :\ , " I \ \ \ \ \ \ ", \ \ \ \ I \ \ 0.6 ~ \ ~ 0.4 'i ~ , \ \ \ 0.2 Figure 4.118Induction motor impedance 0.05 0.1 0.15 0.2 0.25 Motor slip versusslip; the impedanceat nominal slip is 1 pu; 3 hp 220 V (solid line), 50 hp 460 V (dashedline), 250 hp 2300 V(dotted line), 1500 hp 2300 V(dash-dotline). o.-------,.------r----~----.. -I '" , "" " " \ " " \ \ " : \ , I , , I -5 2 Resistivemotor current 3 4 Figure 4.129Changein induction motor currentwith increasingslip; the currentat nominalslip is 1 pu; 3 hp 220 V (solid line), 50 hp 460 V(dashedline), 250 hp 2300 V(dotted line), 1500 hp 2300 V(dashedline). of the currentstartsto decrease. The power factor of the currentdecreases significantly, especially for largemotors. The influenceof large induction motorson voltage sags is described in detail by Yalcinkaya [136]. Fig. 4.130 shows the voltage sags (top curve) and motor the slip (bottomcurve) due to athree-phasefault in an industrialsystem with a largeinduction motor load. Without induction motor load, the voltage would have been zero during the sag and 1 pu after the sag. The voltage plottedin Fig. 4.130 is theabsolutevalue of a time-dependentphasor,used in atransient-stabilityprogram.The effectof the induction motor load is that the voltageduring the fault is increased, and after the fault decreased. The slip o f all motors increases fast during the sag, and even continues to increase a bitafter fault clearing. The voltage after fault clearing, the so-called post-faultsag, shows anadditional decreaseabout 200 ms after fault clearing. Thiscorrespondsto the momentthe motor starts to re-accelerate and draws larger currents. The low voltage immediately after fault clearing is due to the large currentneeded to rebuild the air gap flux. During the fault theinduction motors significantly keep up the voltage. Even toward the endof the sag the voltage at the motor busses is still above100/0 of its pre-event value. Section 4.8 • 241 Load Influence on Voltage Sags 1.0 0.9 0.8 ::l 0. 0.7 .S 0.6 ~ 0.5 ~ '0 0.4 ::> 0.3 0.2 0.1 , 1 , ,, , 1,,,,1,,,,1 0.0 +-r-..,...,...-.-+-..,...,...- r-rr-+-r--,--,-r+-,--,-,--,-h-r-rr-T+-r-rr--r-r-rl 0.5 1.0 1.5 2.0 2.5 3.0 Time in seconds 3.5 3.0 ..: . C 2.5 ~ 8. 2.0 .S .9- 1.5 U; ;:§ 1.0 0.5 Figure 4.130 Voltage sag ( top) and induction motor slip (bottom) for three busses in an industrial power system.(Reproducedfrom Yalcinkaya (136).) 0.5 1.0 1.5 2.0 Time in seconds 2.5 3.0 One should realizethat this is a somewhat exceptional case, as motor the load connected to the system is very large. Similar but less severe effects have been noticed in othersystems.A notherphenomenonwhich contributesto the post-fault voltage sag is that the fault occurs in one of two parallel transformers. The protectionremoves the faulted transformer,so that only onetransformeris available for the supply after fault clearing. Thepost-fault fault level is thus significantly less than its pre-fault value. A similar effect occurs for a fault in one of two parallel feeders. The post-fault sag, described here for three-phase faults, has also been observed after single-phase faults. 4.8.2 Induction Motors and Unbalanced Faults The behaviorof an induction motor during an unbalanced fault is rathercomplicated . Only a network analysis programsimulating a large parto f the system can p laya give an accuratepicture of thequantitativeeffects. The following phenomena part in the interactionbetween system and induction motor during unbalanced faults. • During the first one or two cycles after fault initiation the induction motor contributesto the fault. This causes an increase in positive-sequence voltage. Negative- and zero-sequence voltage are not influenced. • The induction motor slows down, causing a decrease in positive-sequence impedance. This decrease in impedance causes an increase in current and thus adrop in positive-sequence voltage. 242 Chapter 4 • VoltageSags-Char acterization • The negative-sequence impedance of motor the is low, typically 10-20%of the nominal positive-sequence impedance . The negative-sequence voltage due to the fault will thus be significantlydampedat the motor terminals. The negative-sequence impedance independentof is the slip. The negat ive-sequence voltage will thus remain constant during the event. • The induct ion motor does not take any zero-sequence current. The zerosequence voltage will thus not be influenced by induction the motor. 4.8.2.1 Simulation Example.Simulationsof the influence ofinduction motor loads on unbalancedsags are shown in[136], [137]. Some of those results are reproduced here. The systemstudied was a radial one with large induction m otor load connectedto each of the low-voltage busses. Motor sizes andtransformerimpedances were chosen such that for each bus the fault level contribution from the source was 15 times the total motor load fed from the bus. Voltages and currents in the system werecalculated by using the transient analysis packageEMTP. All transformers in the system wereconnected star-star with both neutral points earthed .Although this is not a verycommon arrangement , it helped in understand ing the phenomena. The voltages at the terminals of one of the motors are shown of type in Fig. 4.131.Without induction motor influence we would have seen a sag B of zero magnitude: zero voltage in phase a, and no change in the voltage in - _.~--~--~--~----, ., _$ ~ 3000 2000 1000 '" 0 ~ - 1000 ..d p... - 2000 - 3000 111111111/\/\/\ 11v v v v v v v v v v v o'----o.~I---O.~2---0.3--~---' 0.4 0.5 3000 E 2000 '0 > 1000 0 ~ -1000 ..d e, -2000 -3000 .0 oL----lL.:...:--:----::'-:----:--:-0.1 0.2 0.3 0.\ --::''-:'''''- - : ' 0.4 0.5 0.4 Section 4.8 • 243 Load Influence on Voltage Sags phase b and phasec. Instead we see a smallnon-zero voltage in phase a and in the two non-faultedphasesan initial increasefollowed by a slow decay. After fault clearing the system becomes balanced again, and the three phase voltages thus equal in amplitude. The motor re-accelerationcausesa post-fault sag of about 100 ms duration. The non-zerovoltagein the faulted phaseis due to thedrop in negative-sequence voltage. We saw in (4.32) and (4.34) that the voltage in the faulted phaseduring a single-phasefault is given as (4.142) Theeffect of the inductionmotor is that V2 dropsin absolutevalue,causingan increase in voltagein the faulted phase. During the sag, thepositive-sequence v oltagealso drops,which showsup as the slow but steadydecreasein voltagein all phases. The non-faultedphasesshow an initial increasein voltage. The explanationfor this is as follows.The voltagein the non-faultedphasesduring a single-phasefault is madeup of a positive-sequence, a negative-sequence, and a zero-sequence c omponent. For phasec this summationin the complex planeis for the systemwithout induction motor load. Vc 2 = Vel + VcO + Vc2 = -a 3 1 3 1 3 - - -cl =a (4.143) Due to the induction motor load, the positive-sequencev oltage will not immediately dropfrom 1 pu to 0.67pu. The negative-sequence voltagewill jump from zeroto its new value immediately. The consequenceis that the resulting voltage amplitude slightly exceeds itspre-fault value. After a few cycles theinduction motor no longer keeps up the positive-sequencevoltage. The voltage in the non-faultedphasesdrops below its pre-eventvalue due to negative-and positive-sequencevoltagesbeing less than 33% and 67%, respectively. The currentstaken by the induction motorsare shown in Figs. 4.132and 4.133. Figure 4.132showsthe motor currentsfor a motor with a small decreasein speed.The slip of this motor increasesfrom 2% to 6% during the sag.The motor shownin Fig. 4.133 experienceda much largerdecreasein speed: its slipincreasedfrom 3% to 19°A>. This behavioris difficult to explain without consideringsymmetricalcomponents.But generallywe canobservethat the currentincreasesinitially in the faulted phase,rises to a higher value in one of the non-faultedphases,and initially drops in the other nonfaulted phase.The current in the secondnon-faultedphaserises again after a certain time, determinedby the slowing down of the motor. For the motor shownin Figs. 4.131 and 4.132the componentvoltagesand currentshavebeen plotted in Figs. 4.134and 4.135. From Fig. 4.134we seethat negative and zero-sequencevoltage remain constant during the sag, but that the positivesequencevoltageshowsa steadydecay,due to the decreasein positive-sequence impedancewhen the motor slows down. Figure 4.135clearly showsthe increasein positivesequencecurrentwhen themotor slows down. The zero-sequence c urrentis zero as the motor windings are connectedin delta. From Figs. 4.134and 4.135the positive- and negative-sequence i mpedanceof the motor load can be calculated,simply through dividing voltage by current. The resultsare shown in Fig. 4.136,where we seeagain that the negative-sequence impedanceremainsconstant,whereasthe positive-sequence impedancedrops.When the motor reachesstandstill,it is no longera dynamicelement, and positive- and negative-sequence impedancebecomeequal. 244 Chapter4 • VoltageSags-Characterization 150 J I~~ tlS M ~ 0 -50 i- IOO -150 --------'~----'''--_.-'--0.1 o 0.2 0.3 '---_--J 0.4 0.5 150 = ~ ~~ 500 ~ "11"" ~ ~ "JII'1,HflJIJlI1IJlIIlI ~ 100 -a -50 j~A~~~~1 , ~ ~ ~ ~ V~ ij. ~ V~ ~-100 -150 ~--"--o 0.1 0.2 0.3 0.4 0.2 0.3 0.4 0.1 ,,--_ _a . - - _ - - J 0.5 Time in seconds 4.8.2.2 Monitoring Example. An exampleof a three-phaseunbalancedsag was shown in Fig. 4.48. The severe post-faultsag indicatesthe presenceof induction motor load. For each of the three sampledwaveforms,the complex voltage as a function of time wasdeterminedby using themethoddescribedin Section 4.5.From the three complex voltages, positive-, negative- and zero-sequencevoltages have been calculated. Their absolutevalues areplotted in Fig. 4.137 as afunction of time. The zero-sequencecomponentis very small. The negative-sequence c omponentis zero when the fault is notpresentand non-zerobut constantduring the fault. The positive-sequence voltage is I pu before the fault, shows a slow decay during the fault, and a slow increase after the fault. This is exactly incorrespondence with the abovedescribedtheory and simulation results. 4.8.2.3 Simplified Analysis. From the simulation and monitoring results we can extractthree stages in the voltage sag: • The inductionmotor feeds into the fault, raising the positive-sequence voltage. • The positive-sequence voltage is the same as it would have been without the induction motor load. • The induction motor has sloweddown, drawing additional positive-sequence current,thus causingthe positive-sequence voltageto drop. 245 Section 4.8 • LoadInfluenceon Voltage Sags 4000 = g 3000 =' 2000 1000 ~ ]-10~ ': -2000 ~ :E - 3000 -4000 """'--_ ____'__ _- I L -_ _--'--_ _- - ' " o 0.2 0.1 0.3 0.4 0.5 4000 = 3000 ~ 2000 1000 .rJ .i -10000 II \II H\1 UIII 1111II' 1111" 11111HI H1I c: ~2000 GJ ~ -3000 - 4000 L . . -_ _ ..o.--_ _ o -'--_~__'__ ____'___ ___I 0.2 0.1 0.3 0.4 0.5 4000 = 3000 ~ 2000 ~ 1000 M 0 -1000 ':' - 2000 ~ -3000 -4000 ..d Figure 4.133Induction motor currents during and after a single-line-to-groundfault in the supply. Thismotor showeda large decrease in speed. (Reproducedfrom Yalcinkaya[136].) ~ ~ L . -_ _ - ' - -_ _ ---" o 0.1 0.2 0.3 Timein seconds 0.5 0.4 80 , . . . - - - - - - - - - - - - - - - - - - - ijo Positive-sequence voltage 60 ~ e, .5 40 i ~ 20 Figure 4.134Symmetricalcomponentsfor the voltagesshown in Fig. 4.131. (Reproducedfrom Yalcinkaya[136].) Zero-sequence voltage ----------------Negative-sequence voltage ....................... - Ot------+-----+-----+-----&-....J 100 50 150 200 250 Timeinmilliseconds fj ~ 170·.,..------------------. Negative-sequence current J50 &J30 .S 1: 110 8t: Figure 4.135 Symmetricalcomponentsfor the currentsshown in Fig. 4.132. (Reproducedfrom Yalcinkaya[136].) . .,.,..".-- ____ -- -' .,.""...-- -_.....-.---- Positive-sequence current 90 70 .....-_+-_--.-._-+-_ _--+---+---o.....--._~ 90 110 130 150 170 190 Timeinmilliseconds 210 230 250 246 Chapter 4 • VoltageSags-Characterization 6 80 () [ 60 c= .;; 40 s i 20 ~ ~gativ~s~~n~m..£e~a~e_ Figure 4.136 Positive- andnegative-sequence 230 250 impedance for an induction motor during a sag. (Reproduced from Yalcinkaya [136].) O~---i---+--+--+--+---+--+--+----' 90 110 130 150 170 190 210 Timeinmilliseconds :::s a. .;; 0.8 = J ~ 0.6 5 i= 0.4 o o 0.2 5 15 10 Timein cycles Figure 4.137 Positive-, negative- and zero.. sequence voltages for the three-phase unbalanced sag shown in Fig. 4.47. The negative-sequence v oltage is constantduring the fault, but lower than without induction motor load. To quantify the effect of induction motors, we use atwo-step v oltage calculation procedure.At first we calculate positive- and negative-sequence (V~no), V~no» for the no-load case. As we sawbefore this will lead to voltage sags of type C or type D with different characteristicmagnitude.We assumeda' zero characjump. As a secondstep the influence of the induction motor is teristic phase-angle. incorporated.For this we model the supply as a sourcegeneratinga type C or type D sag, with a finite sourceimpedance.Note that this is a three-phaseTheveninsource representationof the supplyduring the fault. Theeffect of the inductionmotor load is a difference betweenthe sourcevoltagesand the voltagesat the motor terminals, for positive as well as for negative-se~uence components.T he voltageat the motor terminals are denotedas V}/oaa) and V 2/oad). For the three above-mentioned"stages"these relationsare assumedto be as follows: 1. The drop in positive-sequencevoltage is reduced by 15%, the negativesequencevoltagedrops by 300/0. V~/oad) = 0.15 + 0.85V}no) V~/oad) = O.7 V~no) 2. The negative-sequence voltagedrops by 30%. _ V(no) V(/oad) I 1 V~load) = 0.7 vjno) Section 4.8 • 247 Load Influence on Voltage Sags 3. The positive-sequence voltage drops by dropsby 300/0. 100~, the negative-sequence voltage V~load) = 0.9V~no) V~load) = O.7 V~no) The voltages at themotor terminals are calculated from the positive- and negativeV~load) and V~load). The resulting phase voltages for the three stages sequence voltages For sag type C the voltages are shown for one of are shown in Figs. 4.138 and 4.139. the phases with a deep sag, and for the phase with a shallow sag. The more the motorsslow down, the more the voltage in this phase drops. The voltage in the worstaffected phase is initially somewhat higher due to induction the motor influence, but dropswhen themotor slows down and the positive-sequence voltage dropsin value as well. For type D we seethat the voltage in the least-affected phases dropsduring all stages of the sag. The voltage in the worst-affected phase increases initially but decreases later. Figure 4.138 Voltages at the equipment terminals, for three stages of induction motor influence for type C sags. The solid lines are without induction motor influence, the dashed lines with. ~ o.~!~~;~~-~~---~~---------~-----I ~Q~ ~ Figure 4.139 Voltages at the equipment terminals, for three stages of induction motor influence for type D sags. The solid lines are without induction motor influence, the dashed tines with. j i tOt - . . 1 ~=I O.5~_ 00 0.2 0.4 0.6 Characteristicmagnitude 0.8 I 248 Chapter4 • VoltageSags-Characterization From the curves in Figs. 4.138 a nd 4.139 we can see the following two patterns: • The lowestvoltageincreases, the highest voltage.decreases,thus the unbalance becomes less. This is understandableif we realize that the negative-sequence voltagedropssignificantly. • For longer sags all voltagesdrop. This is due to thedrop in positive-sequence voltage. 4.8.3 Power Electronics Load In systems with a largefraction of the loadformed by single-phaseor three-phase rectifiers, these can also influence the voltageduring and after the voltagesag. Below somequalitativeaspectsof the effectof rectifiers on thevoltagewill be discussedbriefly. Different aspects willdominatein different systems. Thebehaviorof powerelectronics equipmentduring voltage sags is discussed in detail in Chapter5. • Especially for longer and deepersags, a largepart of the electronicsload will trip. This will reduce theload currentand thus increasethe voltage,during as well as after the sag. • Equipment that does not trip will initially take a smaller current from the supply or even nocurrentat all because the de bus voltage is larger than the capacitorhasdischarged peakof the ac voltage.Within a few cycles the de bus sufficiently for the rectifier tostartconductingagain. Normally the total power taken by the load remainsconstantso that the accurrentwill be higher. This currenthas a highharmoniccontentsso that the harmonicvoltagedistortion during the sag will increase. • Upon voltage recovery, the dc busc apacitorswill take a large current pulse from the supply. This canpostponethe voltage recovery by up to one cycle. • For three-phaserectifiers, under unbalancedsags, thelargest current flows between the twophaseswith the largestvoltage difference. The effect isthat the voltagein thesephasesdropsand increasesin the other phase. The threephaserectifier thusreduces theunbalancebetween thephases.In this sense they behavesimilar to induction motor load. For unbalancedsags thecurrent to three-phaserectifiers containsso-called non-characteristicharmonics,noticeably a third harmoniccurrent, so that the voltage during the sagcontainsa third harmoniccomponenthigher than normal. • Three-phasecontrolled rectifiers will experiencea longer commutationperiod because thesourcevoltage is lower during the sag. This leads to m ore severe commutationtransients(notches)during the sag.Again this assumesthat the equipmentwill not trip. 4.9 SAGS DUE TO STARTING OF INDUCTION MOTORS In the previoussectionsof this chapter,we have discussedvoltage sags due toshortcircuit faults. Thesevoltagesags are the main cause of equipmentfailure and malfunction, and oneof the main reasonsfor powerquality to become an issue during the last decade.Anotherimportantcauseof voltagesags, one which has actuallybeenof much more concernto designersof industrialpowersystems in thepast,is the startingof large 249 Section 4.9 • Sags due to Startingof Induction Motors inductionmotors. Also the switching on o f otherloads will cause a voltage sag, just like the switching offof a capacitorbank. But in thoselatter cases thedrop in voltage is rather small, and the voltage onlyd rops but does not recover.Thereforethe term "voltagemagnitudestep" would be moreaccurate. During start-upan induction motor takes a largercurrentthan normal, typically five to six times as large. This currentremainshigh until themotor reaches its nominal speed, typically between several seconds and one minute.drop Thein voltage depends Zs strongly on the system parameters.Considerthe system shown in Fig. 4.140, where is the sourceimpedanceand ZM the motor impedanceduring run-up. Figure 4.140 Equivalent circuit for voltage sag due to inductionmotor starting. The voltage experienced by a load fed from the same bus as motor the is found from the voltage dividerequation: v _ .wg - ZM ZS+ZM (4.144) Like with most previouscalculations,a source voltage of 1 pu has been assumed. When a motor of rated powerSmotor is fed from a source withshort-circuitpower Ssourc:e,we can write for the source impedance: vn_ Zs = __ 2 (4.145) Ssource and for themotor impedanceduring starting _ Vn2 ZM--- (4.146) fJSmotor with fJ the ratio between the startingcurrentand the nominalcurrent. Equation(4.144) can now bewritten as v _ sag - S.fOurc:e S.'iOurc:e + /3Smotor (4.147) Of course one needs to realize that this is only anapproximation.The value can be used to estimate the sag due inductionmotorstarting,but to for anaccurateresult one needs a power system analysis package. The latter will also enable the user to incorporatethe effect of othermotorsduring startingof the concernedmotor. The drop in voltage at the other motor's terminals will slow them down and cause an additional increase in load currentand thus anadditionaldrop in voltage. 250 Chapter4 • VoltageSags-Characterization EXAMPLE Supposethat a 5 MVA motor is startedfrom a 100 MVA, 11 kV supply. The startingcurrent is six times thenominal current. This is a ratherlarge motor for a supply of this strength,as we will see soon. The voltage at the motor terminals during motor starting can beestimatedas _ 100MVA _ ° Vrag - 100MVA + 6 x 5 MVA - 77Yo (4.148) In case the voltageduring motor starting is too low for equipmentconnectedto the same bus, one can decide to usededicatedtransformer.This a leads to thenetwork shown in Fig. 4.141. Let again Zs be the sourceimpedanceat the pee,ZM the motorimpedanceduring fun-up, and ZT the transformerimpedance.The magnitudeof the voltage sag experiencedby the sensitive load is v _ sag - 2 T+ZM Zs + ZT + 2 M (4.149) Introducing,like before, theshort...circuit power of the sourceS.'iource,the rated power of the motor Smolor and assumingthat the transformerhas the same rated power of the motor and animpedancef, we get from (4.149): v (1 + 6€)Ssource _ sag - (1 + 6f)Ssource+ 6Smotor (4.150) Figure 4.141 Induction motor starting with dedicatedtransformerfor the sensitive load. EXAMPLE Considera dedicatedsupply for themotor in the previous example. The motor is fed through a 5 MVA, 5% 33/11 kV transformerfrom a 300 MVA, 33 kV supply. Note that the fault currentat the 33 kV bus is identical to the fault currentat the 11 kV in the previous example. That gives the following parameter values: Ssource= 300 MVA, Sma tor= 5 MVA, and € = 0.05, giving, from (4.150), a sag magnitudeof 930/0. Most loads will be able towithstand such a voltagereduction. Note that the reduction in sag magnitudeis mainly due to the increased fault level at the pee, not so much due totransformerimpethe dance. Neglecting the transformerimpedance(€ = 0 in (4.150»)gives Vsag = 91 % • The duration of the voltage sag due to m otor startingdepends on anumberof motor parameters,of which the motor inertia is the main one. Whendeterminingthe fun-up time, it is alsoimportantto determinethe sagmagnitudeat themotor terminals. 251 Section 4.9 • Sags due to Startingof Induction Motors The torqueproducedby themotor is proportionalto thesquareof the terminalvoltage. That makes that a sag down to90% causes adrop in torque down to 81%. It is the difference betweenmechanicalload torque and electricaltorquewhich determinesthe accelerationof the motor,andthus therun-uptime. Assumethat the mechanicalt orque is half the electricaltorqueduring most of the run-upif the terminalvoltageis nominal. This assumptionis based on the general design criterion that the pull-out torqueof an induction motor is about twice the torque at nominal operation.When the voltage drops to 90% of nominal the electrical torque drops to 81 % of nominal which is 162% of the mechanicaltorque. The acceleratingtorque, the difference between electrical and mechanicalt orquedropsfrom 100 % to 62%, a drop of 38%. EXAMPLE Consideragain the 5 MVA induction motor startedfrom a 100 MVA 11 kV supply. The voltage at the motor terminalsduring run-up drops to 770/0 as we saw before. The electrical torque drops to 590/0 of nominal which is 118% of the mechanicaltorque. The acceleratingtorquethus dropsfrom 1000/0 to only 18%, and therun-up time will increaseby a factor of 6. A dedicatedtransformeralone cannot solve this problem, as the voltage at the motor terminalsremainslow. What is needed here is strongersupply. a To limit thevoltagedrop at the motor terminalsto Vmin' the sourcestrength,from (4.147), needs to be Ssourc(! = 6Smotor V . 1- (4.151) mm A 5 MVA motor, with a minimum-permissablevoltageof 85% during starting,needs asource strengthof at least 6x~~5VA = 200 MVA. To keep thevoltage above 90%, the sourcestrength needs to be 300 MV A. From these examplesit will be clear that large voltagedrops are not only a problem for sensitive load, but that they also lead tounacceptablylong run-up times. The situation becomes even worse if more motors are connectedto the same bus, as they willf urther pull down the voltage. Voltaged ropsdue to induction motor startingare seldom deeper than 85%. Voltage SagsEquipment Behavior In this chapterwe will study theimpact of voltage sags on electrical equipment.After the introductionof some generalterminology,we will discuss three types of equipment which are perceived as most sensitive to voltage sags. 1. Computers,consumerelectronics, andprocess-controlequipmentwhich will be modeled as a single-phase diode rectifier. Undervoltageat the dc bus is the main cause of tripping. 2. Adjustable-speedac drives which arenormally fed through a three-phase rectifier. Apart from the undervoltageat the de bus,current unbalance,de voltage ripple, andmotor speed are discussed. 3. Adjustable-speedde drives which are fedthrough a three-phasecontrolled rectifier. The firing-anglecontrolwill causeadditionalproblemsdue to phaseangle jumps. Also the effect of the separatesupply to the field winding is discussed. This chaptercloses with a brief discussion of otherequipmentsensitive to voltage sags: induction and synchronousmotors,contactors,and lighting. 5.1 INTRODUCTION 5.1.1 Voltage Tolerance and Voltage-Tolerance Curves Generally speaking electrical equipmentoperatesbest when the rms voltage is constantand equal to the nominal value. In case the voltage is zero certainperiod for a of time, it will simply stop operatingcompletely. No piece of electrical equipmentcan operateindefinitelywithout electricity. Someequipmentwill stop within one second like most desktopcomputers.Other equipmentcan withstanda supplyinterruptionmuch longer; like a lap-top computerwhich is designed towithstand (intentional) power interruptions.But even alap-top computer'sbatteryonly containsenoughenergy for 253 254 Chapter5 • VoltageSags-EquipmentBehavior typically a few hours. For eachpiece of equipmentit is possibleto determinehow long it will continueto operateafter the supply becomesinterrupted.A rather simple test would give the answer.The sametestcan be donefor a voltageof 10% (of nominal),for a voltageof 20% , etc. If the voltagebecomeshigh enough,the equipmentwill be ableto operateon it indefinitely. Connectingthe points obtained by performing these tests results in the so-called"voltage-tolerancecurve." An exampleof a voltage-tolerance curveis shownin Fig. 5.1. In this caseinformationis providedfor the voltagetolerance of power stationsconnectedto the Nordic transmissionsystem[149]. The auxiliary supply should be able to toleratea voltage drop down to 25% for 250 ms. It should be able to operateon a voltage of 95% of nominal. No requirementsare given for voltagesbelow 250/0 of nominal as thesearc very unlikely for the infeed to the auxiliary supplyof a powerstation.Onemay claim that this is not a voltage-tolerancecurve, but a requirementfor the voltage tolerance.One could refer to this as avoltage-tolerance requirementand to the result of equipmenttests as avoltage-toleranceperformance. We will refer to both the measuredcurve, as well as to therequirement,as avoltagetolerancecurve. It will be clear from the context whether one refers to thevoltagetolerancerequirementor the voltage-toleranceperformance. The concept of voltage-tolerancecurve for sensitive electronic equipmentwas introduced in 1978 by Thomas Key [1]. When studying the reliability of the power supplyto military installations,he realizedthat voltagesagsand their resultingtripping of mainframecomputerscould be a greaterthreat to national security than complete interruptionsof the supply. He thereforecontactedsomemanufacturersfor their design criteria and performedsometestshimself. The resultingvoltage-tolerancec urvebecame known as the"CBEMA curve" severalyearslater. We will comeback to the CBEMA curve when discussingcomputing equipment further on. Note that curves plotting minimum voltageagainstmaximumdurationhavebeenused forsynchronousmachines for many years already, but not for electronicequipment.We will come back to the voltage toleranceof synchronousmachinesin Section5.5. The voltage-tolerancecurveis also an importantpart of IEEE standard1346 [22]. This standardrecommendsa method of comparingequipmentperformancewith the supply powerquality. The voltage-tolerancecurve is the recommendedway of presenting the equipmentperformance.T he conceptof "voltagesag coordinationchart" [20], which is at the heartof IEEE standard1346, will be presentedin detail in Section6.2. While describingequipmentbehaviorthroughthe voltage-tolerancec urve,a number of assumptionsare made. The basic assumptionis that a sag can be uniquely characterizedthrough its magnitudeand duration. We already saw in the previous 100% . 95% j I t : 25% f . - - - - - - - < ' I 0% "--_ _---'Oms 250ms .....t.-- 750ms Duration _ Figure 5.1 Voltage-tolerancerequirementfor powerstations.(Data obtainedfrom [149].) 255 Section 5.1 • Introduction chapterthat this is only anapproximation.From an equipmentpoint of view the basic assumptionbehind thevoltage-tolerancecurve is: if two sags have the same magnitude and duration then they will both lead to tripping o f the equipmentor both not lead to chapter,the definitions of tripping of the equipment.As we have seen in the previous magnitudeand durationof a sagcurrently in use are far fromunique. Further,phaseanglejumpsand three-phasevoltageunbalancecan significantly influence thebehavior of equipment.The two-dimensionalvoltage-tolerancecurve clearly has itslimitations, especially forthree-phaseequipment.We will present someextensionsto the conceptin the nextchapter. An overviewof the voltagetoleranceof currentlyavailableequipmentis presented in Table 5.1. The range in voltagetoleranceis partly due to the difference between equipment,partly due to theuncertaintiesmentionedbefore.With thesedata,as well as with the voltage-tolerancedatapresentedin the rest of thischapter,one shouldrealize that the valuesnot necessarily apply to a specific piece of equipment.As an example, Table 5.1 gives formotor startersa voltagetolerancebetween 20 ms,60% and 80 ms, 40%. Using this range to design an installation could berather unreliable; using the averagevalue even more. These values are only meantto give thereaderan impression of the sensitivity of equipmentto voltage sags, not to serve asdatabase a for those determinethe voltage designinginstallations.For the time being it is still necessary to toleranceof each criticalpart of an installationor to subject the wholeinstallationto a test. In future, voltage-tolerancerequirementsmight make thejob easier. The values in Table 5.1 shouldbe read as follows. A voltage toleranceof a rns, bOlo implies that the equipmentcan toleratea zero voltage ofa ms and a voltageof b% of nominalindefinitely. Any sag longerthan a ms and deeperthan bOlo will lead to tripping or malfunction of the equipment.In other words: the equipmentvoltage-tolerance curve isrectangularwith a "knee" at a ms, bt/«. TABLE S.1 Voltage-Tolerance Ranges of Various Equipment Presently in Use Voltage Tolerance Equipment Upper Range Average Lower Range PLC PLC input card 5 h.p. ac drive ac control relay Motor starter Personal computer 20 ms,75% 20 ms,80% 30 ms,800/0 10 ms,75% 20 ms,600/0 30 ms,800/0 260 ms,60°A» 40 ms,55°A» 50 ms,75% 20 ms,65% 50 ms,50°A» 50 ms,60% 620 ms,450/0 40 ms, 30% 80 ms,600/0 30 ms, 60% 80 ms,400/0 70 ms,500/0 Source: As given data obtained from IEEE Std.1346 [22]. This data should not be used as a basis for design of installations. 5.1.2 Voltage-Tolerance Tests The only standardthat currently describes how toobtain voltage toleranceof equipmentis lEe 61000-4-11[25]. This standard,however, doesnot mentionthe term voltage-tolerancecurve. Insteadit defines anumberof preferredmagnitudesanddurastandarduses the tions of sags for which theequipmenthas to be tested. (Note: The term "test levels," which refers to theremainingvoltageduring the sag.) Theequipment doesnot need to be tested for all these values, but onemore or of the magnitudesand 256 Chapter5 • VoltageSags-EquipmentBehavior TABLE S.2 PreferredMagnitudesand Duration for EquipmentImmunity TestingAccording to IEC-61000-4-11 [25] Duration in Cyclesof 50 Hz Magnitude 0.5 5 10 25 50 durationsmay be chosen. The preferredcombinationsof magnitudeand durationare o f the matrix shown in Table 5.2. the (empty) elements The standardin its currentform does not set any voltage-tolerancerequirements. It only defines the way in which the voltage toleranceequipmentshall of beobtained. An informative appendixto the standardmentionstwo examplesof test setups: • Use atransformerwith two outputvoltages. Make oneo utputvoltage equal to 1000/0 and theother to the requiredduring-sagmagnitudevalue. Switch very fast between the twooutputs,e.g., by usingthyristor switches. • Generatethe sag by using a waveform generatorin cascade with a power amplifier. The IEEE standard1346 [22] refers tolEe 61000-4-11for obtainingthe equipment voltagetolerance,and specificallymentionsthe switching between two supply voltages as a way ofgeneratingsags. Bothmethodsare only aimed at testing one piece ofequipmentat a time. To make a whole installationexperience acertainvoltage sag, each piece needs to be tested hoping that their interconnectiondoes not cause any unexpecteddeteriorationin performance.A methodfor testing a wholeinstallationis presentedin [56]. A three-phasedieselgeneratoris used to power the installationunder test. A voltage sag is made by reducing the field voltage. It takesabouttwo cycles for the ac voltage to settle down after a sudden change in field voltage, thatso this method can only be used for sags of five cycles and longer. 5.2 COMPUTERS AND CONSUMER ELECTRONICS The power supply of acomputer, and of most consumerelectronics equipment regulator normally consists of a diode rectifier along with an electronic voltage (de/deconverter).The power supplyof all these low-power electronic devices is similar and so is their sensitivity to voltage sags. What is different are the consequences of a sag-inducedtrip. A television will show a black screen for up to a few seconds; a compactdisc player will reset itself andstart from the beginningof the disc, orjust wait for a newcommand.Televisions and video recorders normallyhave a smallbattery to maintain power to thememory containingthe channel settings. This is to prevent loss of memory when the television is moved or unplugged for some reason. If this batteryno longercontainsenoughenergy, a sag orinterruptioncould lead to the loss of these settings. The same could happento the settingsof a microwave oven, which is often not equippedwith a battery. The process-controlcomputer of a chemical plant is rather similar in power supply to anydesktopcomputer.Thus, they willboth trip on voltage sags and inter- 257 Section 5.2 • Computersand ConsumerElectronics ruptions,within one second. But the desktopcomputer'strip might lead to the loss of 1 hourof work (typically less), where the process-controlcomputer'strip easily leads to a restartingprocedureof 48 hours plus sometimes a very dangeroussituation.It is clear thatthe first is merely an inconvenience, whereaslattershould the be avoided at any cost. 5.2.1 Typical Configuration of Power Supply A simplified configurationof the power supply to a computeris shown in Fig. 5.2. The capacitorconnected to thenon-regulatedde bus reduces the voltage ripple at the input of the voltageregulator. The voltageregulator converts thenon-regulatedde voltage of a fewhundredvolts into a regulated de voltage of the order of 10 V. If the ac voltage drops, the voltage on the de side of the rectifiernon-regulated (the de voltage) drops. The voltage regulatoris able to keep itsoutputvoltageconstantover a certainrange ofinput voltage. If the voltage at the de bus becomes too low the regulated dc voltage will alsostart to drop and ultimatelyerrors will occur in the digital electronics. Somecomputersdetect anundervoltageat theinput of the controller and give a signal for a"controlled" shutdownof the computer,e.g., byparking the hard drive. Thosecomputerswill trip earlier but in a morecontrolledway. Nonregulateddc voltage Regulated de voltage 1 230 Vac Voltage controller Figure 5.2Computerpower supply. 5.2.2 Estimation of Computer Voltage Tolerance 5.2.2.1DC Bus Voltages. As shown in Fig. 5.2, a single-phase rectifier consists of four diodes and acapacitor.Twice every cycle thecapacitoris charged to the amplitude of the supply voltage. In between the chargingpulses thecapacitordischarges via the load. The diodes only conduct when the supply voltage exceeds the de voltage. When the supply voltage drops the diodes no longerconductand thecapacitor continuesto discharge until the de voltage reaches the reduced supply voltage again. In normal operation the capacitoris charged during two small periods each cycle, and dischargesduring the rest of the cycle. In steady state, the amount of charging and discharging of thecapacitorare equal. To study the effect of voltage sags on the voltage at (non-regulated) the de bus, the power supply has been modeled as follows: • The diodesconductwhen theabsolutevalue of the supply voltage is larger than the de bus voltage. While the diodes conduct,the de bus voltage is equal to the supply voltage. • The supply voltage is a 1pu sinewave before the event and constant-amplia tude sinewaveduring the eventbut with an amplitude less than 1pu. The 258 Chapter5 • VoltageSags-EquipmentBehavior voltage only shows a -drop in magnitude,no phase-anglejump. The supply voltage is not affected by the load current. • While the diodes do not conduct, the capacitoris dischargedby the voltage regulator.The power taken by the voltageregulatoris constantand independent of the dc busvoltage. This model has been used tocalculatethe dc busvoltagesbefore,during, and after a voltagesag with amagnitudeof 50% (without phase-anglejump). The result is shown in Fig. 5.3.As a reference,the absolutevalue of the ac voltage hasbeen plotted as a dashedline. I ~ ~ ~ ~ :' I: ': ,: " II " II , ' " , 1'1 I" "" , I" " , II ~ I " I I· • II " ': , : I , , ~ I .: : I. ~ I 'I " 'I II ,I " " " I' " " " II II 'I " ,I I " I' I' ,'" " I, , " " " , " " " " I " " " " " " II " .' " " , II " " .' " 'I I' " " " " II "'I " 'I ~ , : " I, " " " , : : ! \ : : ~ • ! : ~ ~ : : 2 I I, ,I \\ ~, ~# "~ I' " I' " "I "'I".' :, I''"" ~' "~ 00 " " ,I " ,: :I " " ': I: I: " ~, ~ t, ~' 'I :" : : :; :: :1 :: :: :: I:~, :: :: ,: :: " " " t 0.2 I, I " " " :::~:::::~:~ I: :' ~ , ~ :' , , , "","'" , 0.4, " " " , ' I " : I ~: ~::::, ~ : , , ,~ f ~ (~ 'I"",' , ::::::~: I" ,: """ 0.6 : : : ~: ~: : 1! , I : ~ :: :: : ~ :: """,' , 0.8 :: :: :: : ~ ~ I I 4 6 Time in cycles , , , , ,I ",I '.,: "" " " " " " , 'I - " I' II I , , , I \ I I " " ,I I: :' -, ~, ,I \" \\ I 8 I 10 Figure 5.3 Effect of a voltage sag on de bus voltage for a single-phase rectifier: absolute value of the ac voltage (dashed line) and de bus voltage (solid line). Due to the voltage drop, the maximum ac voltage becomesless than the de voltage. Theresultingdischargingof the capacitorcontinuesuntil the capacitorvoltage drops below the maximum of the ac voltage. After that, a new equilibrium will be reached.Because aconstantpower load has beenassumedthe capacitordischarges fasterwhen the de busv oltageis lower. This explainsthe largerdc voltageripple during the sag. It is importantto realize that the dischargingof the capacitoris only determined by the load connectedto the de bus,n ot by the acvoltage.Thus all sagswill causethe same initial decay in devoltage. But the duration of the decay is determinedby the magnitudeof the sag.The deeperthe sag thelonger it takesbeforethe capacitorhas dischargedenoughto enablechargingfrom the supply. In Fig. 5.4 the sags in ac andde voltage are plotted for voltagesagsof different magnitude.The top curveshave been calculatedfor a sag in acvoltagedown to 50%, the bottomonesfor a sag in acvoltage down to 70% • The dottedlines give the rmsvoltageat ac side(thesag in acvoltage).We seethat the initial decay in de busvoltageis the samefor both sags. 5.2.2.2 Decayof the DC Bus Voltage. Within a certain rangeof the input voltage, thevoltage regulator will keep its output voltage constant,independento f the input voltage. Thus, the output power of the voltage regulatoris independento f the input voltage. If we assumethe regulator to be lossless theinput power is independent of the devoltage. Thus, the load connectedto the de buscan be consideredas a constantpower load. 259 Section 5.2 • Computersand ConsumerElectronics u EO.5 ~ 0 2 4 6 Time in cycles 8 10 2 4 6 Time in cycles 8 10 .i~ 0.5 Figure 5.4 Voltage sag at ac side (dashedline) and at the de bus (solid line) for a sag down to 50% (top) and for a sag d own to 70% (bottom). 0 As long as theabsolutevalueof the ac voltage is less than the de bus voltage, all electrical energy for the load comes from the energy stored incapacitor.Assume the that the capacitor has capacitanceC. The energy a timet after saginitiation is C{ V(t)}2, with V(t) the de bus voltage. This energy is equal to the energy at sag initiation minus the energy consumed by the load: ! 1 2 -CV2=1-CVo - Pt 2 2 (5.1) where Vo is the de bus voltage at sag initiation and P the loading of the de bus. Expression (5.1) holds as long as the de bus voltage is higher than the absolute value of the ac voltage, thus during the initial decay period in Figs. 5.3 and 5.4. Solving (5.1) gives an expression for the voltage during this initial decay period: (5.2) During normal operation,before the sag, the variation in de bus voltage is small, so that we can linearize (5.2)around V = Vo, resulting in (5.3) wheret is the time elapsed since the last recharge ofcapacitor.The the voltage ripple is defined as the difference between the maximum and the minimum value of the de bus voltage. The maximum is reached for t = 0, the minimum fort = f, with T one cycle of the fundamentalfrequency. The resulting expression for the voltage ripple is PT E= 2V2C (5.4) o The voltage ripple is often used as a design criterion for single-phase diode rectifiers. Inserting the expression for the de voltage ripple (5.4) in (5.2) gives an expression for the dc voltageduring the discharge period, thus during the initial cycles of a voltage sag: 260 Chapter5 • VoltageSags-EquipmentBehavior (5.5) where f is the numberof cycleselapsedsince saginitiation. The larger the dc voltage ripple in normal operation,the faster the devoltagedropsduring a sag. 5.2.2.3 VoltageTolerance. Tripping of a computerduring a voltage sag is attributed to the de busvoltage dropping below the minimum input voltage for which the voltagecontroller can operatecorrectly. We will refer to this voltageas Vmin. We will further assumethat in normal operation, before the sag,both ac and de bus voltage areequal to 1 pu. A sag with amagnitudeV will result in a newsteady-statede voltage which is also equal to V, if we neglect the dc voltage ripple.From this we canconcludethat the d ropsbelow computerwill not trip for V > Vmin• For V < Vmin' the dc bus voltage only Vmin if the sag duration exceeds acertain value lmax. The time tmax it takes for the voltage to reach a levelVmin can befound by solving t from (5.5) with Vo = I: I - V;';n T tmax = - - - (5.6) 4E When theminimum de bus voltage isknown, (5.6) can be used to calculatehow long it will takebefore tripping. Or in otherwords: what is themaximumsagdurationthat the equipmentcan tolerate. The dc busvoltage at which the equipmentactually trips dependson the designof the voltage controller: varying between 50% and 90% de of voltage voltage, sometimeswith additional time delay.Table 5.3 gives some values tolerance,calculatedby using (5.6). Thus, if a computertrips at 50% de bus voltage, and as the normal operationde voltage ripple is50/0, a sagof lessthan four cycles indurationwill not cause amaltrip. Any sag below50°A, for more than four cycles will trip thecomputer.A voltageabove 50% can bewithstood permanentlyby this computer.This results inwhat is called a "rectangularvoltage-tolerancec urve," as shown in Fig. 5.5. Each voltage regulatorwill have anon-zerominimum operatingvoltage. The row for zerominimum de bus voltage is only insertedas a reference. We can see from Table5.3 that the performancedoes not improve much by reducing the minimum operatingvoltage of the voltagecontroller beyond50%. When the dcvoltagehas droppedto 50°A" the capacitorhas alreadylost 75°A, of its energy. TABLE 5.3 Voltage Tolerance of Computers and Consumer Electronics Equipment:Maximum-AllowableDuration of a Voltage Sag for a Given Minimum Value of the DC Bus Voltage, for Two Values of the DC Voltage Ripple Maximum Sag Duration Minimum de Bus Voltage 0 50% 70% 900/0 5°AJ ripple 5 cycles 4 cycles 2.5 cycles I cycle I % ripple 25 cycles 19cycles 13 cycles 5 cycles 261 Section 5.2 • Computersand ConsumerElectronics 100% ~ Vmin - --.-.---..--.---------..-..-- -.-- --._-_.. ------- - - - Minimum steady-statevoltage .~ ~ Maximumduration ,/ of zerovoltage Figure 5.5 Voltage-tolerancecurve of a computer:an exampleof a rectangular voltage-tolerancecurve. Duration 5.2.3 Measurements of PC Voltage Tolerance The voltage tolerance of personal computershas been measured bynumberof a authors[28], [29], [41], [49],[50]. The voltage-tolerancecurves they present are in the same range as found from the simplified model presented in the previous section. Figure 5.6 showsmeasuredvoltages andcurrentsfor a personalcomputer.The applied voltage sag was oneof the most severe the computercould tolerate. In Fig. 5.6 we see the de bus voltage startingto drop the momentthe ac voltage drops.During the decay in de bus voltage, the input currentto the rectifier is very small. The output of the voltagecontroller remainsconstantat first. But when the de bus voltage hasdroppedbelow acertainvalue, the de voltage regulatorno longeroperates properly and itsoutput also startsto drop. In this case a new steady state is reached where the regulated de voltageapparentlystill is sufficient for the digital electronics to operatecorrectly. During the new steady state, the input current is no longer zero. Upon ac voltage recovery, the de bus voltage also recovers quickly. This is associated Slightde offsetrelated to instrumentation Regulated de voltage (l V/div) Figure 5.6 Regulatedand non-regulatedde voltages for a personalcomputer,during a 200 ms sag down to500/0: (top-to-bottom)ac voltages; accurrent; regulatedde voltage; non-regulatedde voltage.(Reproducedfrom EPRI PowerQuality Database[28].) Unregulated de voltage (100V/div) Time(SO milliseeonds/div) 262 Chapter5 • Voltage Sags--·EquipmentBehavior IOO,------r----.-----r-------, 80 20 .5 10 15 20 Duration in cycles Figure 5.7 Voltage-tolerancecurves for personalcomputers.(Data obtainedfrom EPRI PowerQuality Database[29J.) with a very largecurrentpeak chargingthe dc buscapacitor.This currentcould cause an equipmenttrip or even a longinterruption if fast-acting overcurrentprotection devices are used. The voltage-tolerancecurvesobtainedfrom various tests are shown in Fig. 5.7 and Fig. 5.8. Figure 5.7 shows the result of a U.S. study [29]. For each personal computer, the tolerance for zero voltage was determined, as well as the lowest steady-statevoltage for which thecomputerwould operateindefinitely. For one computerthe tolerance for800/0 voltage wasdetermined;all othercomputerscould tolerate this voltage indefinitely. We see t hat there is a large range in voltage tolerancefor o f the computerdid not have any influence. different computers.The age or the price The experiments wererepeatedfor various operating states of thecomputer: idle; calculating; reading; or writing. Itturned out that the operatingstate did not have any significant influence on the voltage tolerance or on the power consumption. Figure 5.7 confirms that the voltage-tolerancecurve has analmostrectangularshape. Figure 5.8 showsvoltage-tolerancecurves forpersonalcomputersobtainedfrom a Japanesestudy [49], in the sameformat and scale as the Americanmeasurements in Fig. 5.7. The general shape o f the curves is identical, but the curves in Fig. 5.7 indicate less sensitivecomputersthan the ones in Fig.5.8. 100..----,------r-----.-----, 80 20 100 200 300 Duration in milliseconds 400 Figure 5.8 Voltage-tolerancecurves for personalc omputers-Japanese tests.(Data obtainedfrom [49J.) 263 Section 5.2 • Computersand ConsumerElectronics Summarizingwe can saythat the voltagetoleranceof personalcomputersvaries over a rather wide range:30-170ms, 50-70% being the rangecontaininghalf of the 88% and 210 ms, 30%. models. The extreme values found are 8 ms, 5.2.4 Voltage-Tolerance Requirements. CBEMA and ITIC As mentionedbefore, the firstmodern'voltage-tolerance curve was introducedfor mainframecomputers[1]. This curve is shown as a solid line in Fig. 5.9. We see that its 5.5,5.7,and 5.8. shape doesn ot correspondwith the shapeof the curves shown in Figs. This can beunderstoodif one realizesthat these figures give thevoltage-tolerance performancefor one pieceof equipmentat a time, whereas Fig. 5.9 isvoltage-tolera ance requirementfor a whole range ofequipment.The requirementfor the voltagetolerance curves ofequipmentis that they should all be above thevoltage-tolerance requirementin Fig. 5.9. The curve shown in Fig. 5.9 became well-known when the ComputerBusinessEquipmentManufacturersAssociation(CBEMA) startedto use the curve as arecommendationfor its members. The curve was subsequentlytakenup in an IEEE standard[26] and became a kindo f reference forequipmentvoltage tolerof voltage sags. Anumberof softwarepackagesfor analyzance as well as for severity ing power quality data plot magnitudeand duration of the sagsagainstthe CBEMA curve. The CBEMA curve alsocontains a voltage-tolerancepart for overvoltages, which is not reproducedin Fig. 5.9. Recently a "revisedCBEMA curve" has been adoptedby the InformationTechnologyIndustryCouncil (ITIC), which is the successor of CBEMA. The new curve isthereforereferred to as theITIC curve; it is shown as a dashedline in Fig. 5.9. The ITIC curve givessomewhatstrongerrequirementsthan the CBEMA curve. This is because power quality monitoringhas shownthat there are analarmingnumber of sagsjust below theCBEMA curve [54]. 100 . . . . - - - - - - - - - - - - - - - - - - - - - - - - CBEMA 80 --- ... , +--------.---------~ I --.------~ ITIC 20 O-----._-..l.--------"'--------L.-------J 0.1 10 100 Durationin (60 Hz) cycles Figure5.9 Voltage-tolerance requirements for computing equipment: CDEMA curve (solid line) and ITIC curve (dashed line). 1000 264 Chapter 5 • VoltageSags-EquipmentBehavior 5.2.5 Process Control Equipment Processcontrol equipmentis often extremelysensitiveto voltagesags;equipment has beenreportedto trip when the voltagedropsbelow 800/0 for a few cycles [31], [37], [39], [41]. The consequences o f the tripping of processcontrol equipmentcan be enormous. For example,the tripping of a small relay can causethe shutdownof a large chemical plant, leading to perhaps$IOO~OOO in lost production.Fortunatelyall this is low-powerequipmentwhich can be fedfrom a UPS, or for which the voltagetolerance can be improved easily by addingextra capacitors,or somebackupbattery. Tests of the voltage toleranceof programmablelogic controllers (PLC's) have been performedin the sameway as the PC testsdescribedbefore [39]. The resulting voltage-tolerancecurvesfor somecontrollersare shown in Fig. 5.10. It clearly shows that this equipmentis extremelysensitiveto voltagesags. Asmost sagsare between4 and 10 cycles in duration, we can reasonablyassumethat a PLC trips for each sag below a given threshold,varying between85% and 35%. Even more worrying is that some controllers may send out incorrect control signalsbefore actually tripping. This has to do with the different voltage toleranceof the various parts of the controller. The incorrect signals could lead to dangerous processmalfunctions. Additional voltage-tolerancecurvesfor processcontrol equipment,obtainedfrom anotherstudy [41], are shown in Fig. 5.11. The numberswith the curvesrefer to the following devices: 1. Fairly commonprocesscontrollerused for processheatingapplicationssuch as controlling water temperature. 2. More complicated processcontroller which can be used toprovide many control strategiessuch as pressure/temperature compensationof flow. 3. Processlogic controller. 4. Processlogic controller, newer and more advancedversion of 3. 5. AC control relay, usedto power importantequipment. 6. AC control relay, used topower important equipment;samemanufacturer as 5. 7. AC control relay usedto power motors; motor contactor. 100 80 / 5e I 8. 60 I .5 ~ ~ / 40 ~ 20 --------- :/ Figure 5.10Voltage-tolerancecurves for 5 10 Duration in cycles 15 20 programmablelogic controllers(PLCs). (Data obtainedfrom [39].) 265 Section 5.3 • Adjustable-SpeedAC Drives 100.------r-----,..-----r--------, 80 6 20 3 Figure 5.11 Voltage-tolerancecurvesfor variousprocesscontrol equipment(41]. 5 10 Duration in cycles 15 20 This study confirmsthat processcontrol equipmentis extremely sensitive to voltage disturbances,but alsothat it is possible to buildequipmentcapableof toleratinglong and deep sags. The fact that someequipmentalready trips for half-a-cycle sags suggests a serious sensitivity to voltage transientsas well. The main steps taken to prevent control equiptripping of processcontrol equipmentis to power all essential process ment via a UPS or to ensure anotherway in that the equipmentcan withstandat least short and shallow sags. Devices 2 and 3 in Fig. 5.11 show that it is possible to make processcontrolequipmentresilient to voltage sags. But even here the costs of installing a UPS will in almost all cases be justified. Here are someotherinterestingobservationsfrom Fig. 5.11: • Device 2 is the more complicated version of device 1. Despite the higher complexity, device 2 is clearly less sensitive to voltage sags than device 1. • Device 4 is a newer and more advanced version of device 3. Note enormous the deteriorationin voltage tolerance. • Devices 5 and 6 come from the same manufacturer,but show completely different voltage tolerances. 5.3 ADJUSTABLE-SPEED AC DRIVES Many adjustable-speed drives are equally sensitive to voltage sags as process control equipmentdiscussed in the previous section. Tripping of adjustable-speed drives can occur due to several phenomena: • The drivecontroller or protectionwill detect the sudden change operating in conditionsand trip the drive to prevent damage to the power electronic components. • The drop in de bus voltage which results from the sag will cause maloperation or tripping of the drivecontroller or of the PWM inverter. • The increased ac currentsduring the sag or the post-sag overcurrentscharging the decapacitorwill cause anovercurrenttrip or blowing of fusesprotecting the power electronics components. 266 Chapter5 • VoltageSags-EquipmentBehavior • The process driven by the motor will not be able totoleratethe drop in speed or the torquevariationsdue to the sag. After a trip some drivesrestartimmediatelywhen the voltage comes back; some restart after a certaindelay time andothersonly after a manualrestart.The variousautomatic restartoptionsare only relevantwhen the processtoleratesa certainlevel of speedand torquevariations.In the restof this section we will first look at the results of equipment testing. This will give animpressionof the voltagetoleranceof drives. The effecto f the of equipmenttripping, will be disvoltage sag on the de bus voltage, the main cause cussed next.Requirementsfor the sizeof the de buscapacitorwill be formulated.The currentand on themotor terminalvoltagewill also be effect of the voltage sag on the ac of automaticrestart. Finally, a short overview of discussed, as well as some aspects mitigation methodswill be given. 5.3.1 Operation of AC Drives Adjustable-speeddrives (ASD's) are fedeither through a three-phasediode rectifier, or througha three-phasecontrolledrectifier. Generallyspeaking,the first type is We will discuss found in ac motor drives, the second in de drives and in large ac drives. small andmediumsize ac drives fedthrougha three-phasediode rectifier in this section, and de drives fedthroughcontrolled rectifiers in the next section. The configurationof mostac drives is as shown in Fig. 5.12. The three ac voltages are fed to athree-phasedioderectifier. Theoutputvoltageof the rectifier issmoothened by meansof a capacitorconnectedto the de bus. Theinductancepresentin some drives aims atsmootheningthe dc linkcurrentand soreducingthe harmonicdistortionin the current taken from the supply. The devoltageis inverted to an ac voltageof variablefrequencyand magnitude, by meansof a so-calledvoltage-sourceconverter(VSC). The most commonly used method for this is pulse-width modulation (PWM). Pulse-width modulation will be discussed briefly when we' describe the effect of voltage sags on them otor terminal voltages. The motor speed iscontrolledthroughthe magnitudeand frequencyof the output voltage of the VSC. For ac motors, the rotational speed ismainly determinedby the frequency of thestator voltages.Thus, by changingthe frequency an easy methodof speed control is obtained. The frequency andmagnitudeof the stator voltage are plotted in Fig. 5.13 as afunction of the rotor speed.For speeds up to thenominal speed,both frequency andmagnitudeare proportional to the rotational speed. The 50 Hzr-------.. ac ac Variable frequency de link dc dc ac Controlsystem '--- -.J Figure 5.12Typical ac drive configuration. 267 Section 5.3 • Adjustable-SpeedAC Drives nom Rotational speed . ,-- - -- - - - ... .. .. ._. . nom Figure 5.13 Voltage and frequency as a function of speed for an acadjustable-speed drive. nom Rotational speed maximum torque of an induction motor is proportional to the squareof the voltage magnitudeand inverselyproportionalto the squareof the frequency [53], [206] : r.: V2 ~ /2 (5.7) By increasingboth voltage magnitudeand frequency, themaximum torque remains constant.It is not possible to increase the voltage magnitudeabove itsnominal value. Furtherincrease in speed will lead to a fast drop in maximum torque. 5.3.2 Results of Drive Testing The performanceof a numberof adjustable-speed drives inrelationto voltage sag monitoring in an industrial plant is presentedin Fig. 5.14 [40]: the circlesindicate magnitudeand duration of voltage sags for which the drives trip ; for the voltage sags indicated by the crosses, the drives did not trip. Wethat seethe drives used in this plant were very sensitive to sags. The voltage toleranceof these drives is 80%of voltage for less than six cycles . The exactduration for which the drivestripped could not bedeterminedas theresolution of the monitors was only six cycles. Similar high reported in other sensitivitiesof adjustable-speeddrives to voltage sags have been studies [2],[35], [42], [48]. Using thesedataas typical foradjustable-speed drives carries a certain risk. If the drives had not been sensitive to ,sags the study would never have beenperformed. This warning holds for manypublicationsthat mention a high sensitivity of equipmentto sags. It would thus be very well possible t hat a largefraction of the adjustable-speeddrives are not sensitive to sags at all. To determinethe performance of typical drives , one needs to apply tests randomlyselected to drives. drives, selected atrandom Studies after the voltage toleranceof adjustable-speed arepresentedin [32],[47]. In oneof the studies [47] tests were performedfor 20 h.p. and 3 h.p.drives, from several different manufacturers.Eachmanufacturerprovideda 20 h.p. and a 3 h.p.drive. Each drive was tested for the following three voltage magnitudeevents: Chapter 5 • VoltageSags-EquipmentBehavior o 20 40 60 Duration in cycles 100 80 Figure 5.14 Voltage sags which led to drive tripping (0) and voltage sags which did not lead to drivetripping (x). (Data obtained from Sarmiento[40].) • zero voltage for 33 ms. • 500/0 voltage for 100ms. • 700/0 voltage for 1 sec. The driveperformanceduring the event was classified based on the three types of speed curves shown in Fig.5.15; • I: The speed of themotor shows a decrease followed by a recovery. • II: The speed of themotor reduces to zero after which the drive restartsautomatically and accelerates the motor load back to nominal speed. • III: The motorspeed becomes zero, and the drive is unable restartthe to motor. The test results are summarizedin Tables 5.4 and5.5. Eachof the columns in the tables gives thenumberof drives with the indicatedperformance.For a 500/0, lOOms sag, fourof the 20 h.p. drives showed performance a accordingto curve II in Fig. 5.15 and sevenof the drivesaccordingto curve III. Table 5.4 gives the results for drives at full load; a distinctionis made between 3 h.p. and 20 h.p. drives. Table5.5comparesthe drive behaviorat full load with the drivebehaviorat half-load. These results include 20 h.p. as well as 3 h.p. drives. Nominal speed 1············.···········.······..··-.-.·.··.···.·····... I I II II I I I I! Stand-I still i I III ···············t···········t··············.L.---......L--------- ..--.' Sag duration Time Figure 5.15 Three types of motor speed behaviorfor an adjustable-speed drive due to a sag. 269 Section 5.3 • Adjustable-SpeedAC Drives TABLE 5.4 Resultsof Voltage-ToleranceTestingof Adjustable-Speed Drives: Numberof Drives with the IndicatedPerformance.I: Only Drop in Speed; II:Automatic Restart;III: Manual Restart Drive Performance Applied Sag 00/0 33 ms 50% 100 ms 70% 1000 ms 3 h.p. drives 20 h.p. drives I 4 II 2 4 5 III 5 7 6 I 12 3 1 II III 5 4 4 7 Source: Data obtainedfrom [47]. TABLE 5.5 Influenceof Loading on Drive Voltage Tolerance:Numberof Driveswith the IndicatedPerformance.I: Only Drop in Speed; II:Automatic Restart;III: Manual Restart Drive Performance Applied Sag I 0% 33 ms 50% 100ms 700/0 1000 ms Half-Load Full Load 7 2 1 II I 4 5 III 2 4 4 I 8 3 1 II I 4 III 4 5 I 3 Source: Data obtainedfrom [47]. From the results in Tables 5.4 and 5.5 one can draw the following conclusions: • 3 h.p. drives are less sensitive than20 h.p. drives. This does not necessarily hold in all cases,a lthougha comparisonof 3 h.p. versus 20 h.p. drives for the same manufacturer,the same voltage sag, and the same drive loadinggives in 25of the cases abetterperformancefor the 3 h.p. drive; in 20 cases the performance is the same (i.e., in the same class accordingto the classification above); and only in three cases does the 20 h.p. drive perform better. • Thereis no significant difference between the full load and the half-load voltage tolerance.F or some loads theperformanceimproves, forothersit deteDoing the same riorates,but for mostit doesnot appearto have any influence. comparisonas before shows t hat in two casesperformanceis betterat full load, in four cases it isbetterat half-load,and in 24 cases the performancefalls in the sameperformanceclass.For drives falling inperformanceclass I it may bethat at full load thedrop in speed is more severe thanat half-load,but the study did not report this amountof detail. • Very shortinterruptions(0%, 33 ms) can behandledby all 3 h.p. drives and by a largepart of the 20 h.p. drives. of 100 ms and longer, • Adjustable-speeddrives have severe difficulties with sags especially as one considersthateven response I could mean a serious disruption of sensitivemechanicalprocesses. 270 Chapter5 • VoltageSags-EquipmentBehavior • The tests confirmthat adjustable-speed drives are very sensitive to sags; however, the extreme sensitivity (85%, 8 ms) mentionedby some isnot found in this test. The resultsof a similar set of tests arereportedin [32]: two different voltage sags were applied to 17 drives: • voltagedown to 50% of nominal for 100ms (6 cycles); • voltage down to70% of nominal for 167ms (10 cycles). Their results are shown in Table 5.6. The classification used is fairly similar to the one used inTables 5.4 and 5.5, with the exception t hat a class"drive kept motor speed constant" is included. This driveperformanceis indicated as class 0 inTable 5.6. Responseclasses I, II, and IIIcorrespondto the ones used before. From these studies, it is possible to obtain a kind of "averagevoltage-tolerance curve" for adjustable-speed drives. The resulting curve is shown in Fig. 5.16, with the measurementpointsindicatedas circles.Toleranceis defined here asperformance0 or I. Note that the actual drives show a largespreadin voltage tolerance: some drives o f the drivestoleratedall sags. It could not tolerateany of theappliedsags, where one has further beenassumedthat the drives couldoperateindefinitely on 85% voltage. Conrad et al. [48] obtained voltage tolerancedata for adjustable-speeddrives througha survey of drivemanufacturers.The voltagetolerancestatedby the manufacturers is shown in Fig. 5.17. The circles indicate manufacturerswhich gaveminimum voltage as well asmaximumsagduration.The othermanufacturers,indicatedby triangles in Fig. 5.17, only gave a value for the maximumsagduration.Note that 10 out of 13 d uration. manufacturersindicatethat their drives trip for sagso f three cycles or less in TABLE 5.6 Resultsof Voltage-ToleranceTestson Adjustable-SpeedDrives Responseof the Drive Sag Applied 50% 100 ms 70% 170ms o II III 2 9 5 5 II Source: Data obtainedfrom [32]. 100% ............................. 85% ~ a 70% (l;S 50% .~ ~ ......................... / 33 ms 100 ms 170 ms Duration 1000ms Figure 5.16 Averagevoltage-tolerancecurve for adjustable-speed drives. Note the nonlinear horizontalscale. Section 5.3 • Adjustable-Speed AC Drives 100 80 u 00 ~> § .5 .s ~ 271 . I I.M.. Voltage not stated - • • • • 60 40 '- 20 - 0 0 I I I 10 20 30 Maximum duration in cycles Figure s.t 7 Adjustable-speeddrive voltage tolerance,accordingto the drive manufacturer.• = Magnitudeand duration; A = durationonly. (Data obtainedfrom [48].) 5.3.2.1 Acceptance Criterion.When testing anadjustable-speed drive, without detailed knowledge of the load driven by the drive, a well-defined criterion is needed to distinguish successful from unsuccessful behavior. lEe The standard61800-3 [52] gives criteria to assess theperformanceof adjustable-speeddrives for EMC testing. Thesecriteria are given in Table 5.7; they should also be used for voltage sag testing of adjustable-speeddrives. The IEC performancecriteria can be summarizedas follows: • A: the drive operatesas intended; • B: the drive temporarily operatesoutsideof its intendedoperatingrange but recoversautomatically; • C: the drive shuts down safely. TABLE 5.7 AcceptanceCriteria for Drives According to IEC 61800-3 [52] AcceptanceCriterion A Specific performance Torque-generating behavior Operationsof power electronicsand driving circuits Information processing and sensingfunctions Operationof display and control panel No changewithin the specified tolerance Torque within tolerances No maloperationof a power semiconductor Undisturbedcommunication and data exchange No changeof visible display information B Noticeablechanges,selfrecoverable Temporarydeviation outsideof tolerances Temporarymaloperation which cannotcause shutdown Temporarydisturbed communication C Shutdown,big changes,n ot self-recoverable Loss of torque Shutdown,triggering of protection Errors in communication, loss of dataand information Visible temporarychanges Shutdown,obviously wrong of information display information 272 Chapter 5 • VoltageSags-EquipmentBehavior 5.3.3 Balanced Sags Many trips of ac drives are due to a low voltage at the de bus. The trip or maloperationcan be due to thecontroller or PWM inverter not operatingproperly when the voltage gets too low. But it can also be due tointerventionof the undervoltage protectionconnectedto the dc bus. ·Most likely, the protectionwill intervene before any equipmentmalfunction occurs. The de bus voltage is normallyobtainedfrom the three ac voltages througha diode rectifier. When the voltage at ac side drops, the rectifier will stop conductingand the PWM inverterwill be powered from thecapacitorconnectedto the de bus. This capacitor has only limited energyc ontent(relative to the powerc onsumptionof the motor) and will not be able to supply the load much longer than a few cycles. Animproved drives can be achieved by lowering the setting of voltage toleranceof adjustable-speed the undervoltageprotectionof the de bus. One shouldtherebyalways keep in mindthat the protectionshould trip before anymalfunction occurs and beforecomponentsare damaged.N ot only is theundervoltagea potentialsourceof damagebut also the overcurrentwhen the ac voltage recovers. If the drivenot is equippedwith additionalovercurrent protection, the de bus undervoltage should also protect against these overcurrents.Many drives areequippedwith fuses in series with the diodes, against large overcurrents.Theseshouldnot be used toprotectagainstthe overcurrentafter a sag.Havingto replace the fuses aftera voltage sag only causes additionalinconvenience. 5.3.3.1 Decayof the DC BusVoltage. The de bus voltage for anadjustableof a speed driveduring a sag in three phases behaves the same as the de bus voltage personalcomputer, as discussed in Section 5.2. When we consider a drive with a motor load P, a nominal de bus voltageVo, and capacitanceC connectedto the de bus, we can use (5.2) to calculatethe initial decayof the de bus voltaged uring the sag: V(t) = J 2; V6 - t (5.8) It has been assumed that the de bus voltage at sag initiation equals thenominalvoltage. We further assumed aconstantpower load. For the standardPWM invertersthis is probablynot the case. But one can translatethe constant-powerassumptioninto the assumptionthat the load on ac side of the inverter, i.e., the motor, ac does not notice anythingfrom the sag. Thus, the o utputpower of the inverteris independento f the dc bus voltage. If we neglect the increaseinverter in loss for lower de bus voltage (due to the highercurrents)we arrive at theconstant-powerassumption.The constant-power assumptionthus correspondsto assumingan ideal inverter: nodrop in voltage at the motor terminals, and no increase in losses during the sag. 5.3.3.2 VoltageTolerance. The adjustable-speed drive will trip either due to an active interventionby the undervoltageprotection(which is the mostcommonsituation), or by a maloperationof the inverter or the controller. In both cases the trip will occur when the de busvoltage reaches acertain value Vmin. As long as the ac voltage does notd rop below this value, the drive will not trip.For sags below this value, (5.8) can be used to calculatethe time it takes for the de bus voltage to reach the value Vmin: (5.9) 273 Section 5.3 • Adjustable-Speed AC Drives EXAMPLE 'Consider the example discussed[42]: in a drive with nominalde bus voltage Vo = 620V and de buscapacitanceC = 4400j.tF powers an acmotor taking an active power P = 86 kW. The drive trips when thede bus voltagedrops below Vmin = 560V. The time-to-trip obtainedfrom (5.9) is 4400j.tF ( 2 2) t = 2 x 86kW x (620V) .- (560 V) = 1.81ms (5.10) The minimum ac bus voltage for which the drive will not trip is 560/620 = 90%. This drive will 900/0. thus trip within 2 ms when the ac bus voltage drops below Supposethat it would be possible to reduce the setting of the undervoltageprotectionof the de bus, to 310 V(50°tlc»). That would enormouslyreduce thenumberof spurioustrips of the drive, because thenumberof sags below500/0 is only a small fraction of thenumberof sags below900/0. But the time-to-trip for sags below50% remains very short. Filling inVmin = 310V in (5.9) givest = 7.38 ms. In fact, bysubstituting Vmin = 0 we can seethat the capacitanceis completely empty 9.83 ms after sag initiation, assumingthat the load power remains constant. We can concludethat no matter how good the inverter, the drive will trip for any voltage interruption longer than 10 ms. The amountof capacitanceconnectedto the dc bus of anadjustable-speed drive can be expressed in I-tF/kW. If we express the de bus voltage in kV and the time in ms, (5.9) can bewritten as O.5(~)(V6 - t= V;'in) (5.11) with (C/P) in JLF/kW. With (C/P) in JLF/h.p. (5.11) becomes t = O.67(~)(V6 - V;'in) (5.12) The amountof capacitanceconnectedto the de busof modernadjustable-speed [138]. Figure 5.18 plots therelation between the drives is between 75 and 360 JLF/kW undervoltagesetting for the de bus (vertical) and the time-to-trip (horizontalscale), for capacitanceand motor sizeaccordingto (5.11). three valuesof the ratio between de bus The voltagetoleranceof the drive, for balancedsags, can beobtainedas follows: 100 ~ ... ij [ 80 .5 .tg 60 e 40 .~ -. ,, \ \ ~ 20 Figure5.18 Voltage tolerance of adjustablesizes. speed drives for different capacitor Solid line: 75J.LF/kW; dashedline: 165 I-tF/ kW; dotted line: 360J.LF/kW. \ \ \ \ \ \ \ , \ \ \ \ \ \ \ , , \ \ \ 20 40 60 Maximum timeinmilliseconds 80 274 Chapter5 • Voltage Sags-EquipmentBehavior • The setting of the de busundervoltageprotection determinesthe minimum voltage for which the drive is able to operate. • From the appropriatecurve, determinedby the capacitorsize, themaximum sag duration is found. We seethat even for very lowvaluesof the settingof the de busundervoltage,the drive will trip within a few cycles. 5.3.3.3 Capacitor Size. It is obvious from the aboveexamplesthat the amount of capacitanceconnectedto the de busof an adjustable-speed drive, is not enoughto offer any seriousimmunity againstvoltage sags. The immunity can be improved by adding more capacitanceto the de bus.To calculate the amount of capacitance neededfor a given voltage tolerance,we go back to (5.8) and assumeV(t max) = Vmin, leadingto C- 2Ptmax 2 Vo2 - Vmin (5.13) This expressiongives the amount of dc bus capacitanceneededto obtain a voltage toleranceof Vmin, tmax (Le., thedrive trips when the voltagedropsbelow Vmin for longer than tmax) . EXAMPLE Considerthe same drive as in the previousexampleWe want the drive to be able totoleratesags withdurationsup to 500 ms. Theundervoltagesetting remainsat 560 V (90% of nominal). The capacitanceneeded to achieve this is o btained from (5.13) with tmax = 500msand Vmilf = 560V: c= 286kW x 500ms = t.12F (620 V)2 - (560 V)2 (5.14) This exampleis used in [42] tocomparedifferent ways of improving the drive's voltage tolerance,including the costsof the variousoptions.The total costsof 1.12 F capacitance,with about$200,000 and to place these capacitorswould enclosures,fuses, bars, and fans, would be 2 require a space 2.5 x 18 m and 60 em high. Abattery backupwould cost "only" $15,000 and requirea spaceof 2.5 x 4 x 0.6 rrr'. Howeverthe batteryblock would requiremore maintenance than the capacitors. Assumethat an undervoltageprotectionsetting of 310 V (50%) is feasible, andthat the drive shouldbe able totoleratevoltagesags up to 200 ms in d uration.Equation(5.13) can again be used to give therequiredcapacitance,which is 119 mF. This is only one-tenthof the required capacitancefor the original inverter. The costs of installing capacitancewould still be higher than for the batteryblock but the lowermaintenance requirementsof the capacitorsmight well tip the balancetoward them. Making an inverter that can operatefor even lowervoltageswould not gain much ridethroughtime or savecapacitors. This is because the s toredenergy in acapacitoris proportionalto the squareof the voltage. It would, however, increase the current through the inverter significantly. Bringing theminimum operatingvoltage down to 25% would doublethe requiredcurrentrating of the inverter but still require95 mF of capacitance;a reductionof only 20%. 5.3.4 DC Voltage for Three-Phase Unbalanced Sags In normal operation,the debus voltageis somewhatsmoothenedby the capacitanceconnectedto the dc bus.T he largerthe capacitance,the smallerthe voltageripple. Section 5.3 • 275 Adjustable-SpeedAC Drives I "", :----,~--"o~-""""~-r"__~---r<:------,, ,, 0.98 " : , ,I , g, 0.96 .8 *' 0.94 ] 0.92 ~ ,, , ,, ,, "" \ : ", 'I I \ , I . " ': ,, ,, , \ I I ' ' , I , ' , ' ,, ,' ,, ,, I , I , ,I ,, I I " "i g 0.90 Figure 5.19 DC bus voltage behind a threephase rectifier during normal operation,for largecapacitor(solid line), smallcapacitor (dashed line) , and nocapacitorconnected to the dc bus (dotted line) . 0.88 0.2 0.8 Where with a single-phase rectifier the capacitoris only charged twice a cycle , it is chargedsix times every cycle for athree-phaserectifier. Figure 5.19 shows the de bus voltage behind athree-phaserectifier, for variouscapacitorsize. The load fed from the de bus was assumed to of bethe constant-powertype. The size of thecapacitanceswas chosen as follows: for the large capacitanceand a de bus voltage o f 100%, the initial rate of decayof the voltage is 10% per cycle when the ac side voltage drops; for the small capacitancethe initial rate of decay is 75% per cycle . We will relate this to the drive parametersfurther on. We saw in Section 4.4 that the most commonsags experienced by three-phase a load are type A, type C, and type . DFor a type A sag all three phases drop in magnitudethe sameamount.All six voltage pulses in Fig. 5.19 willdrop in magnitude and the load will empty thecapacitorconnectedto the de bus, until the de bus voltage drops below the peak of the ac voltage again . The voltagetolerancefor this case has been discussed in the previous section . 5.3.4.1 Sagsof Type C. For a three-phase .unbalancedsag of type C or type D, different phases have different voltage drops. Some phase voltages also show a jump in phase angle . The behavior of the dc bus voltage , and thusof the drive, is completely different than for a balancedvoltage sag . The upper plot in Fig. 5.20 shows the voltages at the drive terminalsfor a sagof type C. Note that these are the line-to-line voltages, as the drive is connectedin delta. We see how the voltage drops in two phases, while the sine waves move toward each other. The third phase does not drop in magnitude.A sag with acharacteristicmagnitudeof 50% and zero characteristic phase-anglejump is shown. The voltagemagnitudesat the driveterminals are 66.1% (in two phases) and 100% in the third phase; phase-anglejumps are -19.1°, +19.1°, and zero. The effect of thisthree-phaseunbalancedsag on the de bus voltage is shown in the lower plot of Fig. 5.20.The capacitorsizes used are the same as in Fig. 5.19. Wethat see even for the smallcapacitance , the de bus voltage does not drop below 70%. For the large capacitance,the dc bus voltagehardly deviates from itsnormal operatingvalue. In the lattercase, the drive will never tripduring a sag of type C, nomatterhow low the characteristicmagnitudeof the sag. As one phase remains at its pre-event ,value the three-phaserectifier simply operatesas a single-phase rectifier during the voltage sag . The drop in de bus voltage (actually : the increase in voltage ripple) is only moderate. 276 Chapter 5 • VoltageS ags-EquipmentBehavior fO:~ U-0.5 « - I j o > gj o 0.5 I 1.5 .~ , .. 2.5 --: -', -: ', I . ', ' 0.8 2 . .' · \ I '. ' , . - { " .. .. ~' ..~' ; \ ". ', : .' : ', : ; 3 ",' .o 0.6 U Cl 0.5 1.5 2 2.5 3 Time in cycles Figure 5.20 Voltage during a three-phase unbalanced sag of type C: ac side voltage (top) and dc side voltages (bottom) for large capacitor (solid line), smallcapacitor(dashed line), and nocapacitorconnected to the dc bus (dotted line). The initial behaviorremains identical to the one discussed before for the balanced t hat the de bus voltage recovers sag (due to athree-phasefault). The main difference is after one half-cycle. This is due to the one phase that remains atnominal voltage for a sag of typeC. 5.3.4.2 Sagsof Type D. The voltages on ac side and de side of the rectifier are shown in Fig. 5.21 for athree-phaseunbalancedsag of type D with characteristic magnitude50% and nocharacteristicphase-anglejump. The magnitudeof the voltages at the driveterminals is 50%, 90.14%, and 90.14%, with phase-anglejumps zero, -13.9° and +13 .9°. For a sag of type D, all three phases drop in voltage , thus there is no longer one phase which can keep up the de bus voltage. Fortunatelythe drop in voltage is moderate for twoof the three phases. Even for a terminal fault, where the voltage in one phase drops to zero, the voltage in theother two phases does notd rop below = 86%. The top curve in Fig. 5.21 shows how one phase drops significantly in voltage. Theother two phasesdrop less in voltagemagnitudeand theirmaximamove away from each other. In the b ottomcurve of Fig. 5.21 the effecto f this on the de bus 4.j3 ~ 0.5 ~ "0 > gj .0 u -0.5 -e ~ "0 > . ' 1 '1 : \" .' \ . 0.8 .. I :' , ,' ",' ]'" 0.6 - ., '\~-..ron--_J'"'...--....j .. , : '... ; . ',I , .' , , ,' " U Cl 0.5 1.5 Time in cycles 2 2.5 3 Figure 5.21 Voltage during a three-phase unbalanced sag of type D: ac side voltage (top) and dc side voltages (bottom) for large capacitor(solid line), smallcapacitor(dashed line), and nocapacitorconnected to the dc bus (dotted line). 277 Section 5.3 • Adjustable-SpeedAC Drives voltage is shown.F or not too small valuesof the dc buscapacitance,the dc bus voltage of the voltage in the two phases with the reaches a value slightly below the peak value moderatedrop. Again the effect of the sag on the de bus voltage, andthus on themotor speed andtorque,is much lessthan for a balancedsag. 5.3.4.3 Phase-Angle Jumps.In Figs. 5.20 and 5.21 it isassumedthat the characteristic phase-anglejump is zero. This makesthat two of the phasevoltages have the same peak value: the highest phases for a sag of type D (Fig . 5.21); the lowest phases for a sagof type C (Fig . 5.20). A non -zerocharacteristicphase-angle jump makesthat one of these .two voltages gets lower, and other the higher. The effecto f this is shown in Fig. 5.22 for athree-phaseunbalancedsag of type D, with acharacteristic magnitude of 50%. All phase-anglejumps are assumed negative ; positive phase-anglejumps would give exactly the same effect. When there is capacitance no connectedto the de bus(dotted line) the minimum de bus voltage isdeterminedby of the phase-anglejump is that the minimum the lowest ac side voltage. The effect de busvoltage gets lower. But for a drive with a large capacitanceconnectedto the de bus, it is the highest peak voltage which determinesthe de bus voltage.F or such a drive, the de bus voltage will increase for increasing phase-anglejump. For a than during normal phase-anglejump of -300 the de bus voltage is even higher operation. Note that a -300 phase-anglejump is an extremesituation for a sag with a characteristicmagnitudeof 50%. ~ I , ~ '0 0.8 :- ] 0.6 Q 0.4 0 o Figure 5.22 DCbus voltageduring a threephase unbalanced sag of type D, with characterist ic magnitude50% and characteristicphase-anglejump zero (top left), 10' (top right), 20' (bottomleft), and 30· (bottom right). Solid line: largecapacitance ; dashed line: smallcapacitance ; dotted line: no capacitanceconnected to the de bus. " ~ :- Q ,~ - . , " '. ,J - ' .'" 1 1 1 ,I ,, 1 1 , ,. ., , I 0.6 0.4 0 , ., ,, -, I , , 0.5 1 , , " " 0.4 0 0.5 . . 1 1 0.8 0.6 I '0 0.8 ..5"' o 1 1 i 0.8 • " 0.6 -, 1 1 ' ,I 0.4 0.5 Time in cycles 0 0.5 Time in cycles For three-phaseunbalancedsagsof type C, the de busvoltageis determinedby not drop in magnitude. The phase-anglejump has the voltage in the phase which does no influence on this value: it simply remains at 100%. Thusfor sagsof type C the de bus voltage is not influenced by the phase-anglejump, assumingthe capacitanceconnected to the de bus is largeenough. 5.3.4.4 EffectofCapacitor Size and Sag Magnitude.Some of the effectsof the size of the de buscapacitanceon the de bus voltageduring unbalancedsags are summarizedin Figs. 5.23through 5.30. In all the figures, thehorizontal axis gives the characteristicmagnitudeof the sag, the solid linecorrespondsto a largecapacitanceconnectedto the de bus, thedashedline holds for smallcapacitance,the dotted 278 Chapter5 • VoltageSags-EquipmentBehavior ~ 0.8 .5 ~ S ~ 0.6 ] .g 0.4 .1 ~ 0.2 0.2 0.4 0.6 0.8 Characteristic magnitude in pu Figure 5.23 Minimum de bus voltage as a function of the characteristicmagnitudeof three-phaseunbalancedsags of type C. Solid line: largecapacitance;dashed line: small capacitance;dotted line: no capacitance connected to the de bus. line for no capacitanceat all. Figures 5.23 through 5.26 are for three-phaseunbalancedsags of type C. Figures 5.27 through 5.30 are thecorrespondingfigures for type D. Figure 5.23 shows the influence on the minimum de bus voltage. The de bus undervoltageprotection normally uses this value as a trip criterion. There is thus a direct relation between theminimum dc bus voltageand the voltagetoleranceof the t hat the presenceof sufficient capacitancemakesthat the drive. We see from the figure dc busvoltageneverdropsbelow acertainvalue, nomatterhow deep the sag at ae side normal is. This is obviously due to the onephaseof the ac voltage which stays at its value. For a largecapacitance,the drop in de busvoltageis very small. The smaller the capacitance,the more thedrop in de bus voltage. Figure 5.24 shows the influenceof sag magnitude and capacitor size on the voltage ripple at the de bus. The largerthe capacitanceand the larger thecharacteristic magnitude,the smaller thevoltage ripple. Again a largecapacitancemitigates the voltage disturbanceat the de bus. Some drives use the voltage ripple to detect malfunctioning of the rectifier. This ismore used in controlled rectifiers where a large voltage ripplecould indicate an error in one of the firing circuits. The figure is some- I00 ~---r------r----'--r-------r-----., --0.2 0.4 0.6 0.8 Characteristic magnitude in pu Figure 5.24 Voltage ripple at the de bus as a function of thecharacteristicmagnitudeof three-phaseunbalancedsags of type C. Solid line: largecapacitance;dashed line: small capacitance;dotted line: no capacitance connected to the de bus. 279 Section 5.3 • Adjustable-SpeedAC Drives _ _ _ _ _ - -. -:-. '7'.":'.~ .-:'."": .. [ 0.8 .S i ($ 0.6 ;> j ~ Figure 5.25 Average de bus voltage as a function of the characteristic magnitude of three-phase unbalanced sagstypeC. of Solid line: large capacitance; dashed line: small capacitance; dotted line: no capacitance connected to the dc bus. 0.4 ~u .( 0.2 0.2 0.4 0.6 0.8 Characteristicmagnitudein pu what misleadingin this sense, as a large capacitancewould also make it more difficult to detectunbalancesin the rectifier (likeerrorsin the thyristor firing). In thatcase,eithera more sensitive'setting of the voltage rippledetectionshould be used (which would overrule.the gain in voltagetolerance)or the rectifiercurrentsshould be used as a detectioncriterion (which might introducemore sensitivity tounbalancedsags). The average de bus voltageshownin is Fig. 5.25, the rms value in Fig. 5.26. These that the drop determinehow themotordriven by the drive slows down in speed. We see in average or rmsvoltageis not asdramaticas thedrop in minimum voltage: although of the capacitance,the less thedrop in speed. Especially for also here, the larger the size Of course longer voltage sags, or low-inertia loads, this could be a decisive difference. one needs to assume that the inverteris able tooperateduring the voltage sag.That is more likely for largecapacitance,where the dc bus voltage remains high, thanfor small capacitance,where the de bus voltage drops to a low value twice a cycle. The results for athree-phaseunbalancedsag of type D are shown in Figs. 5.27 through5.30. We saw in Fig. 5.21 t hat for large capacitance,the new steadystatedoes not settle inimmediately.All values for the type D sag have been calculatedfor the of type D is shown in third cycleduring the sag. Theminimum de bus voltage for a sag -----------------------------~~~~~~~. [ 0.8 .S &>0 ~ 0.6 ;> ~ ..0 .g 0.4 t+- o tI.) Figure 5.26 The rms of the dc bus voltage as ~ 0.2 a function of the characteristic magnitude of three-phase unbalanced sags of type C. Solid line: large capacitance; dashed line: small capacitance; dotted line: no capacitance connected to the de bus. 0.2 0.4 0.6 0.8 Characteristicmagnitudein pu 280 Chapter5 • ::l 0. .S Voltage Sags-EquipmentBehavior 0.8 " OIl .f!0 > 0.6 ee ::l or> o -e 0.4 E ::l E '2 ~ 0.2 0 0 0.2 0.4 0.6 0.8 Characteristic magnitude in pu Figure5.27 Minimum de bus voltage as a function of thecharacteristicmagnitude of three-phase unbalanced sags of type . Solid D line: largecapacitance ; dashed line: small capacitance ; dotted line: nocapacitance connected to the de bus . 100 ;:: 80 .... "~ "0. .S "0. 60 Q. ' 1: .s" OIl 40 0 > o 0 20 00 ~. ~.. 0.2 0.4 0.6 0.8 Characteristic magnitude in pu Figure5.28 Voltage ripple at the de bus as a function of the characteristicmagnitudeof three-phase unbalanced sags of type D. Solid line: large capacitance; dashed line : small capacitance; dotted line : no capacitance connected to the dc bus. 5. 0.8 .S ~ ~ 0.6 :g or> .g 0.4 t ~ 0.2 0.2 0.4 0.6 0.8 Characteristic magnitude in pu Figure 5.29 Average de bus voltage as a function of thecharacteristicmagnitudeof three-phaseunbalancedsags of type D. Solid line: large capacitance; dashed line : small capacitance;dotted line: no capacitance connected to the de bus . 28t Section 5.3 • Adjustable-SpeedAC Drives a0.8 .s ~ ~ 0.6 . > ] ~ 0.4 C+-t o rJ) Figure 5.30 The rms of the de bus voltage as~ 0.2 a function of the characteristicmagnitudeof three-phaseunbalancedsags of type D. Solid line: large capacitance;d ashedline: small 00 capacitance;d otted line: no capacitance connectedto the de bus. 0.2 0.4 0.6 0.8 Characteristicmagnitudein pu Fig. 5.27. Comparisonwith Fig. 5.23 for type C revealsthat for a type D sag the minimum de busvoltagecontinuesto drop with lower characteristicmagnitude,even with large capacitorsize. But againan increasein capacitancecan significantly reduce the voltage drop at the de bus.For the drive with the largecapacitancethe de bus voltagedoes not drop below 80% , even for thedeepestunbalancedsag. Figure 5.28 plots' thevoltageripple for type D sags, whichshowsa similar behavior as for type C sags.T he voltage ripple is calculatedas the peak-to-peakripple related to the normal value. Therefore,the voltage ripple for the drive without capacitancedoes not reach 1000/0 for a sagof zero characteristicmagnitude. In Figs. 5.29and 5.30, showingaverageand rms valueof the de busvoltage,we seesimilar values as for sags o f type C. Again the differenceis that the de busvoltage continuesto drop for decreasingcharacteristicmagnitude.Deep sags of type D will causemore drop in motor speed than sags of the samemagnitudeof type C. For shallow sags the effect on the m otor speed will beaboutthe same. 5.3.4.5 Sizeof the DC BusCapacitance. In the previous figures, the de bus voltagewas calculatedfor threevalues of the sizeof the capacitanceconnectedto the dc bus. Thosewere referred to as "large capacitance,""small capacitance,"and "no capacitance."Large and small werequantified through the initial decayof the de bus voltage: 10% per cycle for the largecapacitance,75% per cycle for the smallcapacitance.Here we will quantify the amountof tLF to which this corresponds. The de busvoltage V(t) during the sag isgovernedby the lawof conservationof energy: the electricload P is equalto thechangein energystoredin the de buscapacitor C. In equationform this readsas 2 !!-{!CV } =p dt 2 (5.15) Let Vo be the de busvoltageat saginitiation. This gives at saginitiation dV CVo-=P dt (5.16) 282 Chapter5 • Voltage Sags-EquipmentBehavior from which the initial rateof decay of the dc busvoltagecan becalculated: dV P d(= CVo (5.17) From (5.16) we can derive an expressionfor the capacitorsizeneededto get acertain initial rate of decay of de bus voltage: p C=--cw V (5.18) oClt EXAMPLE For the same driveparametersas before (620 V, 86 kW) we can use (5.18) to calculate the required size of the capacitance.As a first step we have totranslatepercent per cycle into volts per second: 75% per cycle = 27,900Vis 100/0 per cycle = 3730Vis To obtain a rate of decay of750/0 per cycle, we need caapacitanceof 86kW C = 620 V x 27,900V/s = 4970JlF (5.19) or 57.8 /-LF/kW. Similarly we find that 37.3 mF or 433/-LF/kW correspondsto 10% per cycle. These values need to be comparedto the amountof capacitancepresentin moderndrives, which JlF/kW, accordingto [138]. We seethat the "largecapacitance"curves are is between 75 and 360 feasible withmodernadjustable-speed drives. 5.3.4.6 Load Influence. The main load influence on voltage sags is the reduction in negative-sequencevoltage due to induction motor load, as explained in Section 4.8. To see w hat the effect is onadjustable-speed drives, wereproducedtype C and type 0 sags withreducednegative-sequence voltageand calculatedde bus voltage behind a non-controlledrectifier. The three-phaseunbalancedsags with reduced negative-sequence voltage were calculatedin the same way as for Figs. 4.138 and 4.139. Theanalysiswas performedfor a three-phaseunbalancedsag with acharacteristic magnitudeof 50% and zero phase-anglejump. The voltagesat the equipment terminalsare for a 50% sag of type C: Va = 1 Vb = Vc _!2 - !j./3 4 (5.20) = -~+~j./3 and for a sagof type 0: (5.21) 283 Section 5.3 • Adjustable-SpeedAC Drives Splitting the phasevoltages in sequence componentsgives (5.22) for a sagof type C, and 3 VI =- 4 1 4 (5.23) V2 =-- for a sagof type D. A "distortedtype C" sag iscreatedby keeping the positive-sequence voltage constant,while reducingthe negative-sequence voltage. This is to simulate the drops effect of induction motor load. If we assumethat the negative-sequence voltage by a factor of {J, thus from V2 to (1 - {J) V2, we obtain the phase voltages from Va = VI +(I-fJ)V2 + a2( 1 - fJ)V2 VI + a(l - {J)V2 Vb = VI V(. = (5.24) -! where a = + !j,J3. The resulting phase voltages are usedcalculatethe to de bus voltagesduring the sag, in the same way as for the "nondistorted"sag. The results are shown in Figs. 5.31through 5.34. Figure 5.31 plots the average de bus voltage as a voltage. Notethat a drop of 50o~ in negativefunction of the drop in negative-sequence sequencevoltagerequiresa very largeinductionmotorload. We see from Fig. 5.31 that the motor load drops the minimum dc bus voltage in case capacitoris a used.For a drive without de buscapacitor,the minimum de bus voltage increases. The drop in negative-sequence voltagemakesthat the three voltages get closer magnitude,so in that the effect of acapacitorbecomes less. The same effect is seen in Fig. 5.33 for type D sags. Figs. 5.32 and 5.34 show that also the average de bus voltage dropsfor increasing motor load. [ 0.8 .S ~g 0.6 j .g 0.4 .1 ~ 0.2 Figure 5.31 Induction motor influence on minimum de bus voltage for sags of type C. Solid line: large capacitor; dashed line: small capacitor; dotted line: no capacitor connected to the de bus. 0.1 0.2 0.3 0.4 Drop innegative-sequence voltage 0.5 284 Chapter5 • VoltageSags-EquipmentBehavior ~ 0.8 .S . Go) f 0.6 -0 > :g .,D ~ 0.4 Go) <G0.2 0.1 0.2 0.3 0.4 Drop in negative-sequence voltage 0.5 Figure 5.32 Induction motor influenceon averagede busvoltage for sagsof type C. Solid line: largecapacitor;dashedline: small capacitor;dottedline: no capacitorconnected to the de bus. &e 0.8 .5 i ] 0.6 ] ~ 0.4 § :~~ 0.2 0.1 0.2 0.3 0.4 0.5 Drop in negative-sequence voltage a 0.8 ------------------_ Figure 5.33 Induction motor influenceon minimum de busvoltage for sagsof type D. Solid line: largecapacitor;dashedline: small capacitor;dottedline: no capacitorconnected to the de bus. --. .53 . ; -0 0.6 > ] ~ 0.4 -< 0.2 t 0.1 0.2 0.3 0.4 Drop in negative-sequence voltage 0.5 Figure 5.34 Induction motor influenceon averagede busvoltagefor sagsof type D. Solid line: largecapacitor;dashedline: small capacitor;dottedline: no capacitorconnected to the de bus. 285 Section 5.3 • Adjustable-SpeedAC Drives 5.3.4.7 Powering the Controllers.In older drives thecontrol electronics for the PWM inverter was powered from the supply. This made the drive very sensitive to disturbancesin the supply. Inmoderndrives thecontrol electronics is powered from the de bus which can be more constantdue to the presence of capacitors.But even here the samereasoningcan be used as for process control equipment.Controllers are essentiallylow-power equipmentwhich only require a smalla mount of stored energy to ridethrough sags. The design of the power supply to the drive controller should be suchthat the controller stays active at least as long as the power electronics or themotor do not require apermanenttrip. It should not bethat the controller becomes the weak p art of the drive. Figure 5.35 shows the typical configuration for powering the controller. The capacitanceconnected to the de bus between the rectifier and theinverter is normally not big enoughto supply themotor load and the controller during a balancedsag longerthan a few cycles. The power supply to the controller can beguaranteedin a numberof ways: • By inhibiting firing of the inverter sothat the motor no longer discharges the de buscapacitance.The power taken by the controlleris so much smallerthanthe motor load, that the capacitorcan easily power thecontroller even for long voltage sags. When the supply voltage recovers,controller the can automatically restartthe load. • Additional capacitancecan be installed on low-voltage side of the de-de switched mode power supply between the dc bus and control the circuitry. As this capacitanceonly needs to power thecontroller, a relatively small amountof capacitanceis needed. Also abatteryblock would do the job. • Some drives use the rotationalenergy from themotor load to power the controllers during a voltage sag orshortinterruption.This causes small additional drop in motor speed, smallenoughto be negligible. A special control technique for the inverter is needed, as well as methodto a detect the sag[33]. Diode rectifier PWM inverter ac motor Figure 5.35 Configurationof the power supply to the control circuitry in an adjustable-speed drive. 5.3.5 Current Unbalance 5.3.5.1 Simulations. Unbalanceof the ac voltages not only causes an increased ripple in the de voltage but also a large unbalancein ac currents.The unbalancein currentdependson the typeof sag.Considerfirst a sagof type D, where one voltage is much lower than the other two. The upperplot in Fig. 5.36 shows the ac side voltages (inabsolutevalue) comparedwith the de bus voltage (solid line near the top) during one cycle, for a sag of type D with characteristicmagnitudeequal to 50% • Here it is assumedthat the de bus voltage does not change at allduring the sag. The 286 Chapter5 • Voltage Sags -EquipmentBehavior fo:o/>:' -'> ;::>~,- >: :Jj oL~'.:-><: . . . . : _~l o~ V I ' < ; J_~1 O J}01 _ . o 0,' 0:6 A 0:' M : 0: ; 0.' 0,6 _ 0.2 . . 0.4 0.6 Time in cycles 0,' 0,' J~ 0.8 I 'I Figure 5.36 ACsideline voltages (top) and currents(phase a, b, and c from top to I bottom) for a three-phase unbalanced sag of type D. rectifier only deliverscurrent when the ac voltage (inabsolutevalue) is largerthan the dc voltage . We have assumed that this current is proportional to the difference between theabsolutevalue of the ac voltage and the de voltage . This results in the line currentsas shown in the three remainingplots in Fig. 5.36. The three voltages in the top plot of Fig. 5.36 are the voltage difference between phase a and phase (dashed),between b phase b and phase(dash-dot),and c between phase c and phase (dotted).The a first pulse occurs when the voltage between a and c exceeds the de voltage ( around t = 0.2 cycle). This results in acurrent pulse in the phases a and c. Around t = 0.3 cycle the voltage between bandc exceeds the dc voltage leading to acurrent pulse in the phases b andc. The patternrepeatsitself around t = 0.7 cycle andt = 0.8 cycle. Thecurrentsflow in oppositedirection because the ac voltages areopposite now. Whereasat t = 0.2 cycle the voltage between c and a was negative resulting in acurrent from a to c, the voltage is positive now resulting in a currentfrom c to a. The voltage between a and b has droppedso muchthat there are no currentpulses between a and b. This results in two missing pulses per cycle for phase a as well as for phase b. Whereas innormal operationthe capacitoris charged 6 times per cycle, this now only takes place four times per cycle. These four pulses must carry the sameamountof charge as the original six pulses. The consequenceis that the pulses will be up to 50% higher in magnitude. For a type C sag thesituationis even worse, as shown in the top plot of Fig. 5.37. One line voltage is much higher than the other two, so that only this voltage leads to current pulses. The resultingcurrent pulses in the three phases are shown in the three bottom plots of Fig. 5.37. Due to a sag of type C the numberof currentpulses is reduced from 6 per cycle to 2 per cycle, leading to up to 200% overcurrent.Note that a large overcurrentwould alreadyarise for a shallow sag. The momentone or two voltagesdrop below the de bus voltage, pulses will be missing and the remainingcurrentpulses will have to be higher to compensatefor this. 5.3.5.2 Measurements.Figures 5.38, 5.39, and 5.40 show measurementso f the input currents of an adjustable-speeddrive [27], [30]. Figure 5.38 shows theinput 287 Section 5.3 • Adjustable-Speed AC Dr ives Figure 5.37 AC side volta ge (top ) and cur rents (ph ase a, b, and c from top to bottom) for a three-phaseu nbalancedsag of type C. 300 200 100 .5 o ~ 3 - 100 ./ l \ I \ u -200 -300 o 0.01 300,--- , -- 0.02 0.03 0.04 Time in seconds ....,.----,---r- 0.05 0.06 ---,,--- ,---, 200 l--tHr-+tHl--1---It-Ir--+---+Ht---l ~ ~ .5 1001-t-ft-t---HUHH---ttH+---'I-Ht+----i 0 H-l...--li-'r-,.....--lo+--t""'4--l-o,--+1p.o1--jloo~ ~ 3 -100 H---t-\-Itti---t1tt-t--HH--+-IHl o - 200 JV---t-+HF-t----ftt+-t--\tPJ-Figure 5.38 Input cur rent for an ac drive in normal operation. (Reproduced from Mans oo r (27).) - 300 " -_ o +-ffi ..L-_-'-_ - - ' -_ - - "_ _" - _-'-----' 0.01 0.02 0.03 0.04 Time in seconds 0.05 0.06 currents for the drive under normal operating conditions. Only two currents ar e shown , the th ird one issimilar to one of the other two. The drive is connectedin of four pulses in delt a, so that each current pulse shows up in two phases. total A each of the threephasesimplies 6 pulsesper cycle chargingthe capacitor. Therewas a small unbalancein the supply voltage leading to the difference between thecurrent pulses. We see t hat the magnitudeof the currentpulses is between 200 and 250 A. 288 Chapter5 • VoltageSags-EquipmentBehavior 400 300 '" 200 ~ 100 ~ o .5 .\ s5 - 100 o -200 - 3000 0.01 0.02 0.03 0.04 Time in seconds 400 i n N n ru 300 200 0.05 0.06 t\ /\ 100 o .5 ~ - 100 8 -200 -300 -400 0 ~ ~ 0.01 lJ\ ~ ~I ~ 0.02 0.03 0.04 Time in seconds \~ ~ 0.05 Figure 5.39Input currentfor an ac drive with voltage unbalance(Reproduced . from 0.06 Mansoor[27].) Figure 5.40Input current for an ac drive during a single-phase fault. (Reproduced from Man soor [27).) 289 Section 5.3 • Adjustable-SpeedAC Drives Figure 5.39 showsthe samecurrents,for an unbalancein the supply voltage. The highestvoltagemagnitudewas 3.6% higher than the lowest one. This smallunbalance alreadyleads to two missing pulses both relatedto the same linevoltage.Thereare now only four pulsesleft, with a magnitudebetween300 and 350 A, confirming the 500/0 overcurrentpredictedabove. Figure 5.40 shows the rectifierinput currentfor a single-phasesag at the rectifier terminals. A measuredsag is reproducedby means of three power amplifiers. As explainedin Section4.4.4, asingle-phasefault will cause a type D sag on the terminals of delta-connectedload. The two remainingpulses per cyclea ndthe peakcurrentof 500 to 600 A confirm the 200% overcurrentpredictedabove. 5.3.6 Unbalanced Motor Voltages The de busvoltageis convertedinto an acvoltageof the requiredmagnitudeand frequency, by using a voltage-sourceconverter (VSC) with pulse-width modulation. The principle of PWM can beexplainedthrough Fig. 5.41. A carrier signal Vcr with . a frequency of typically a few hundred Hertz, is generatedand comparedwith the referencesignal Vrej (dashedcurve in the upper figure). The referencesignal is the required motor terminal voltage, with a certain magnitude, frequency, and phase angle. If the referencesignal is largerthan the carriersignal, theoutput of the inverter is equal to the positive input signal V+ and the other way around: = V+, Vout Vout = V_, V ref > Vcr (5.25) Vr~f < Vcr The resulting output voltage Vout is shown in the lower plot of- Fig. 5.41. It can be shown that the output voltage consistsof a fundamentalfrequency sine wave plus harmonicsof the switching frequency[43]. The latter can beremovedby a low-pass filter after which the requiredsinusoidalvoltageremains.If the de busvoltagevaries, both the positive and the negativeoutput voltage V+ and V_will changeproportionally. These variations will thus appearas an amplitude modulation of the output voltage. Let the requiredmotor voltagesbe ::s .e I 0.5 ~ 0 S 0-0.5 ::> -I o~----::-.L..:-----:-~--~-_.L.--_--J 0.6 1 r~ .9 0.5 0.8 r-- i Figure5.41 Principle of pulse-width modulation:carrier signal with reference signal (dashed)in the top figure; the pulsewidth modulatedsignal in the bottom figure. 0 0-0.5 ::> .....-. -1 o '-- 0.2 ~ 0.4 0.6 Timein cycles '---- 0.8 Chapter 5 • VoltageSags-EquipmentBehavior 290 = Va Vm cos(2rrfmt) Vb = Vm cos(2rr.fmt- 120°) (5.26) Vc = Vm cos(2rrfmt+ 120°) We assumethat the high-frequencyharmonicsdue to the PWM switching are all removedby the low-passfilter, but that the variationsin dc busvoltagearenot removed by the filter. The motor voltagesfor a de bus voltage Vdc(t) are the product of the requiredvoltage and the p.u. dc bus voltage: Va = Vdc(t) X Vmcos(2rrfmt) Vb = Vdc(t) X Vmcos(2rrfmt- 120°) Vc = Vdc(t) X Vmcos(2rrfmt+ 120°) (5.27) Normally the motor frequencywill not be equalto the systemfrequency,thusthe ripple in the de voltage is not synchronizedwith the motor voltages.This may lead to unbalancesand interharmonicsin the motor voltages. The motor terminal voltageshave beencalculatedfor sagsof type C and 0, for various characteristicmagnitudesand motor frequencies.A small capacitorwas connectedto the de bus. Figure 5.42showsthe resultsfor a 500/0 sag of type C (see Fig. 5.20) anda motor frequencyequalto the fundamentalf requency.We seethat the motor terminal voltagesare seriouslydistortedby the ripple in the de busvoltage.One phase dropsto 75% while anotherremainsat 100%. The de busvoltageis shownas adashed line in the figure. Figure 5.43 showsthe result for a 50% sag of type 0 and a motor frequencyof 50 Hz. The effect is similar but lessseverethan for the type C sag. Figure 5.44 plots the three motor terminal voltages for a motor frequency of 40 Hz and a supply frequency of 50 Hz. The motor frequency is now no longer an integer fraction of twice the power systemfrequency (the de ripple frequency). But two periods of the motor frequency (50 ms) correspondto five half-cycles of the power system frequency. The motor terminal voltage is thus periodic with a period of 50 ms. This subharmonicis clearly visible in Fig. 5.44. Figure 5.45 shows the unbalanceof the voltages at the motor terminals, as a function of the motor speed.The unbalanceis indicatedby showingboth the positive and the negative-sequence componento f the voltages.The largerthe negative-sequence component,the larger the unbalance.We seethat the unbalanceis largest for motor o 234 Time in cycles 5 6 Figure 5.42 Motor terminal voltagedue to a three-phaseunbalancedsag of type C with a characteristicmagnitudeof 50%, for a motor frequencyof 50 Hz. The de busvoltageis shownas adashedcurve for reference. 291 Section 5.3 • Adjustable-Speed AC Drives j 0.5 '0 > ] .~ 0 B ~ -0.5 ~ Figure 5.43 Motor terminal voltage due to a three-phase unbalanced sag of type D with a characteristic magnitude of 500/0, for a motor frequency of 50 Hz. The de bus voltage is shown as a dashed curve for reference. o ~-: ~ -: j-: Figure 5.44 Motor terminal voltages due to a three-phase unbalanced sag of type C with a characteristic magnitude of 50%, for a motor speed of 40 Hz. 5 234 Timein cycles 6 o 2 4 6 8 10 o 2 4 6 8 10 o 2 4 6 8 10 Time in cycles 0.9 ...------r----~------..---------. 0.8 ::s 0.7 Q.. .s 0.6 .t ~ 0.5 H0.4 g. 0.3 Figure 5.45 Positive- (solid) and negative- rI} 0.2 sequence component (dashed) of the motor 0.1 terminal voltages as a function of the motor ,,'--- ..... speed. A sag of type C with a characteristic °O~---.....::a....:-.;:l-----"""'O---~-~--_--J-_-----J 50 100 150 200 magnitude of500/0 was applied at the supply Motorfrequencyin Hz terminals of the adjustable-speed drive. 292 Chapter5 • VoltageSags-EquipmentBehavior TABLE 5.8 Motor Terminal and DC Bus Voltagesfor AC Drives Due to a 50% Type C Sag Positive-sequence voltage min max Small capacitance Large capacitance 88.88% 98.250/0 Negative-sequence voltage 83.44% 96.91% max 5.56% 0.81 % de busvoltage avg. rms 87.38% 97.83% 87.80% 97.84% speedsaround50 Hz. For low,speed theunbalanceis very small.Note that the voltage contains25% of negativeat the supply terminals of the drive (i.e., the type C sag) sequence and75% of positive-sequence voltage. Even for a small de bus capacitorthe unbalanceat the motor terminalsis significantly lessthan at the supply terminals. The resultsof the calculationsare summarizedin Table 5.8. Maximum andminimum positive andnegative-sequence voltageshave beenobtainedas in Fig. 5.45. (The lowestnegative-sequence voltagewas lessthan0.01% in bothcases.) The average de bus For a voltage wasobtainedas in Fig. 5.25; the rmso f the de bus voltage as in Fig. 5.26. large dc buscapacitor,the ripple in the de busvoltagebecomes very small, so that the motorterminalvoltagesremainbalanced,no matterhow big theunbalancein the supply. 5.3. 7 Motor Deacceleratlon Most ac adjustable-speed drives trip on one of thecharacteristicsdiscussed before. After the tripping of the drive, theinduction motor will simply continueto slow down until its speed getso ut of the rangeacceptablefor the process. In case the electrical part of the drive is able towithstandthe sag, thedrop in systemvoltagewill cause adrop in voltage at themotor terminals. We will estimatethe motor speed forbalancedand unbalancedsags. We will use a simplifiedm otor model: the electricalt orqueis proportional to thesquareof the voltage,but independento f the motor speed; themechanical torque is constant. 5.3.7.1 Balanced Sags.For balancedsags all threephasevoltages drop the sameamount. We assumethat the voltagesat the motor terminals are equal to the supply voltages (in p.u.),thus that the sag at themotor terminalsis exactly the same as the sag at the rectifier terminals. The de buscapacitorwill somewhatdelay the drop in voltage at the de bus andthus at the motor terminals; but we sawthat this effect is relatively small. Thevoltage drop at the motor terminals causes adrop in torque and thus adrop in speed. Thisdrop in speed candisrupt the production processrequiring an intervention by the processcontrol. The speed of amotor is governed by the energy balance: d dt (12: J w2) = w(Tel - Tm£'ch) (5.28) where J is the mechanicalmoment of the motor plus the mechanicalload, «o is the motor speed (inradiansper second),Tel is the electricaltorquesuppliedto the motor, and Tmech is themechanicall oad torque.The electricaltorque Tel is proportionalto the squareof the voltage. Weassumethat the motor is runningat steadystatefor a voltage of I pu, sothat 293 Section 5.3 • Adjustable-SpeedAC Drives = V 2 Tmech Tel (5.29) For V = 1 electricaland mechanicalt orqueare equal.The resultingexpressionfor the drop in motor speedis d to dt 2 (V - = I) Tmech J (5.30) Introduce the inertia constant H of the motor-load combinationas the ratio of the kinetic energyand the mechanicaloutput power: H= IJw2 2 (5.31) 0 lOo T,nech with lOo the angularfrequencyat nominal speed;and the slip: lOo - w s=--lOo (5.32) Combining(5.31) and (5.32) with (5.30) gives anexpressionfor the rate of changeof motor slip during a voltagesag (for w ~ wo): ds I - V 2 dt = ---:uI (5.33) Thus for a sagof duration ~t and magnitude V the increasein slip is tls ds 1 - V2 = -tlt = -2H -tlt dt (5.34) The largerthe inertia constantH, the less theincreasein slip. For processessensitive to speedvariations,the voltage tolerancecan be improved by addinginertia to the load. Figure 5.46 showsthe increasein slip as afunction of the sagmagnitudeandduration, for an inertia constantH = 0.96 sec.N ote that an increasein slip correspondsto a drop in speed.The increasein slip is given for four different sagdurations,correspondingto 2.5,5,7.5,and 10 cycles in a50Hz system.As expectedthe speed willdrop more for v oltage(PWM disabled)the drop in speed deeperandfor longersags. But even for zero is only a fewpercentduring the sag. If the maximum-allowableslip increase(slip tolerance)is equal to tlsmClx , the minimum-allowablesag magnitude Vmin for a sagduration T is found from O.I.------r----~--~----..-------.. 0.08 ~ fI.) ~ 0.06 S .S Q,) ~ j 0.04 0.02 Figure 5.46Increasein motor slip as a function of the sagmagnitudefor different sagduration: 50ms(solid curve), lOOms (dashed),150ms(dash-dot),200 ms(dotted). " ...... ...... " 0.2 0.4 0.6 Sag magnitude in pu 0.8 294 Chapter5 • VoltageSags-EquipmentBehavior vmin. -- J I - 2H f).smax T (5.35) A zero voltage, Vmin = 0, can be tolerated for a duration 2H f:1s max' The resulting voltage-tolerancecurves have beenplotted in Fig. 5.47 for H = 0.96 secand various valuesof the slip tolerancef:1s max' Theseare thevoltage-tolerancecurvesfor an adjustable-speeddrive wherethe drop in speedof the mechanicall oad is the limiting factor. Note that some of the earlier quoted tolerancesof adjustable-speeddrives are even abovethe 1% or 2% curves.This is mainly due to thesensitivity of the powerelectronicspart of the drive. Note also that it has beenassumedherethat the drive stays on-line. Temporary tripping of the drive correspondsto zero voltage at the drive terminals.This will obviously lead to alarger drop in speed. 5.3.7.2 Unbalanced Sags.The curves in Figs. 5.46and 5.47 have been calculated assumingthat the voltagesat the motor terminalsform a balancedthree-phase set. For a balancedsag this will obviously be the case. But as we have seen in the previous section, for an unbalancedsag themotor terminal voltagesare also rather balanced.The larger the de buscapacitance,the more balancedthe motor terminal voltages. The above calculations of the motor slip are still applicable. When the motor terminal voltage show a serious unbalance, the positive-sequencevoltage should be used. The effect of three-phaseunbalancedsags on themotor speed has been calculated underthe assumptionthat the positive-sequence voltageat themotor terminalsis equal to the rmsvoltageat the de bus.T his is somewhatan approximation,but we haveseen that the motor terminalvoltageis only slightly unbalancedeven for a largeunbalancein the supplyvoltage.This holdsespeciallyfor a drive with a largede buscapacitance.The de bus rmsvoltageshave been calculatedin the sameway as for Figs. 5.26and 5.30. Thesewere used tocalculatethe drop in motor speedaccordingto (5.34) and voltagetolerancecurveswere obtained,as in Fig. 5.47.T he resultsfor type C sags areshownin Figs. 5.48, 5.49,and 5.50. Figures 5.48 and 5.49 presentvoltage-tolerancecurvesfor different values of the maximum drop in speed which theload can tolerate, for no capacitanceand for a small capacitance,respectively,presentat the de bus.Even the small capacitorclearly improvesthe drive's voltage tolerance.Below a certaincharacteristic magnitudeof the sag, the rms value o f the de busvoltageremainsconstant.This 100 90 1% =80 5% G,) t 70 ]0% 0- .5 60 G,) ] 50 .~ 40 ~ 30 «I C/.) 20 10 200 400 600 800 Sag duration in milliseconds 1000 Figure 5.47 Voltage-tolerancecurvesfor adjustable-speed drives, for three-phase balancedsags, fordifferent valuesof the slip tolerance. 295 Section 5.3 • Adjustable-SpeedAC Drives 100r----r------r-====::::======::::::::~ 90 10/0 ... 80 2% [ 70 5% .S 60 u ] 50 10% .~ 40 ; 30 ~ 20 fIl 200/0 10 Figure 5.48 Voltage-tolerancecurves for sag type C, nocapacitanceconnectedto the de bus, for different values of the slip tolerance. 200 400 600 800 1000 800 1000 Sag duration inmilliseconds ... 80 5 e & .5 60 i.~ 40 e ~ fIl 1% 5% 2% 20 Figure 5.49 Voltage-tolerancecurvesfor sag type C, smallcapacitanceconnectedto ~he de bus, for different values of the slip tolerance. 200 400 600 Sag duration inmilliseconds 100----r----.,.------r----=~======l - - -- -- .; .:-- ,', :, : Figure 5.50 Voltage-tolerancecurves for sag type C, large (solid line), small(dashed),and no (dotted)capacitanceconnectedto the de bus. , I 200 400 600 Sag duration inmilliseconds 800 1000 296 Chapter5 • VoltageSags-EquipmentBehavior shows up as a vertical line in Fig. 5.49. Figure 5.50 comparesdrives with large, small, and no de buscapacitancefor a load with a slip toleranceof 1%. The capacitorsize has a very significant influence' on the drive performance. The largeimprovementin drive performancewith capacitorsize for type C sags is obviouslyrelatedto the onephaseof the acsupplywhich doesnot drop in voltage.For a largecapacitance,this phasekeeps up thesupply voltage as if almost nothing hapsmaller,as even theleast-affectedphasesdrop in pened.For type D sags, this effect is o f the capacitorsize on thevoltage voltage magnitude.Figure 5.51 shows the influence tolerancefor type D sags.T he threecurveson the left are for a sliptoleranceof 1%, the ones on the right for10% slip tolerance.The improvementfor the I % casemight look marginal,but one shouldrealizethat the majority of deepvoltagesags have aduration around100 ms. The largecapacitanceincreasesthe voltagetolerancefrom 50 to 95 ms for a 50% sag magnitude. This could imply a serious reduction in the number of equipmenttrips. From Figs. 5.48through5.51 it becomesclear that the effectof unbalancedsags to by using a large on themotor speed is small. The best way preventspeedvariationsis de buscapacitorand by keeping the drive online. The small speedvariations which would result may becompensatedby a control systemin case theycannotbe tolerated by the load. 100 .; +J e Q) ,~ 80 1% ~ 8. .5 60 /' .sa / ,, .~ 40 eu / / I e I :; ~ I ," , , en 20 :: :, :, o o 10% :''I :1 , I 200 400 I 600 Sag duration in milliseconds I 800 1000 Figure 5.51 Voltage-tolerancecurves for sag type D, for two valuesof the slip tolerance, large (solid line), small(dashed),and no (dotted)capacitanceconnectedto the de bus. 5.3.8 Automatic Restart As we saw before many drives trip on undervoltage,for a sagof only a few cycles. This tripping of the drive doeshowevernot always imply aprocessinterruption.What happensafter the tripping dependson how themotor reactswhen thevoltage comes back. A good overviewof options is given in [51], which served as a basis for the list below. • Some drives simply tripandwait for a manualrestart.This will certainlylead to a processinterruption.A drive which doesnot automaticallyrecoveraftera trip looks like aratherbad choice.Howeverthereare cases in which this is the best option. On onehandthere areprocesseswhich arenot very sensitive to a drive outage.The standardexampleis a drive used forair-conditioning.An interruption of the air flow for a fewminutesis seldomany concern.On theothersideof Section 5.3 • Adjustable-SpeedAC Drives • • • • • • 297 the spectrumone finds processes which are extremely sensitive to speed variation. If a very small speedvariation alreadyseverelydisruptsthe process, it is best tonot restartthe drive. Restartingthe drivecertainlyleads to a speed and torquetransient,which could makethe situationworse. Safetyconsiderations could dictatethat a total stoppageis preferableabove anautomaticrestart. Some drives wait a few minutesbeforethe automaticrestart.This ensuresthat the motor load has come to acompletestop. Thecontrol system simplystarts the motor in the same way it would do for an ormal start. With a delayed automaticrestart,safety measureshave to betakento ensurethat nobodycan be injured by the restartof the motor. The control system of the drive canapply electrical ormechanicalbraking to bring the load to a forcedstop, after which a normal restart takes place. Without specialcontrol measures,it is very hard to restartthe drive successfully before it has come to a standstill.Thusforced brakingcan reduce the time to recovery.The requirementis that the process driven by the drive is able to toleratethe variationsin speed andtorquedue to braking and reacceleration. Most drives are able tostart under full load, which also impliesthat they should be able to pick up thealready spinning load. The dangerof already spinningload is that it might still containsomeair-gapflux causingan opencircuit voltageon themotor terminals.Whenthe drive isrestartedwithout any synchronizationsevere electricaltransientsare likely to occur due to the residual flux. The solutionis to delay therestartfor aboutone second to allow this residual flux to decay. Thisoption will imply that the motor load will be without poweringfor one or two seconds. In this time the motor speed decays to a typical valueof 50% of the nominalspeed,dependingon the intertia of the load. Also at themomentof restartthe inverterfrequency will not beequalto the motor speed, themechanicaltransientthis causes might not be toleratedby the process. A speedidentification techniquecan be used toensurethat the inverter picks up the load at the right speed. This reduces mechanical the transienton restarts and makesthe motor recoverfaster. Thespeed-identificationprocessshouldbe enablea fastrestartof able todeterminethe motor speed within a few cycles to the drive. To seriouslylimit the drop in speed and the time to recovery, the drive needs to restartvery soonafter the voltagerecovers.For this theinvertershouldbe able to resynchronize.on the residual stator voltages. This requiresextra voltage sensors,thus increasingthe priceof the drive. Insteadof resynchronizingthe drive after the sag, it is possible tomaintain synchronizationbetween inverter and motor during the sag. This requires a more complicatedmeasurementand control mechanism. Figures5.52and 5.53showthe responseof a drive with automaticrestart.In Fig. 5.52 the driverestartssynchronouslywhich leads to adrop in speed well within 10%. The motor currentdropsto zeroduring the sag. Thisindicatesthat the operationof the inverter was disabled(by inhibiting the firing of the inverter transistors).The moment the voltagerecovered,inverteroperationwasenabledleading to the large peak in motor current.As the air-gapfield in the motor is low and not synchronizedwith the inverter voltage, it takesanother hundred milliseconds before themotor is actually able to 298 Chapter 5 • VoltageS ags-Equ ipment Behavior Motor speed (445 rpm/div) • . • • • , , . 0- 0 _ . 1. , , , . . , . , , ._----1-------[-------[------r------1-------1-------[-------[-------r-----·..··-j-·.... -l..·.. t···.. ··r....··'j'·..·· r·. ·r·..·)'· · . l. . ·. .---- . ~ -----_. ~ --_..--r---_•. -l--_ . - - - ~ - - - __ A - ! 1 , - - - _ . • - _ . - -- - ~ - ---- - 1 Motor current (20 A/div) 1 , - :- - : 1 , - - - - -~-- : I __ A - - ; - -- -- - j 1 ! - - -~ ~- --- 1 , ~- -_. - - - - - - -~ j 1 I - ! -_or -------r ---_.- , - : -- - , - - -:- . - - - - -7 --- --- ! : Figure 5.52 Drive response with synchronous restart.(Reproducedfrom Mansoor[32].) Time (30 cycles or 0.5 seconds/div) Ai Motor speed (445 rpm/div) orpm '------'-I--'----J_--'-~..i......----' , . . .. : Motor current (20 A/div) _ _ ' _ _l.._----'-_.J 4• •I ! : . , .. . _. . . ! • . . . ..... _ : ., --- ~-- - - - -- i - ---· _ · . - - - - - - -~--- _ · - -:.. - ---- · ! ! ! : ! : ! : ! ! Figure 5.53 Drive response with nonsynchronousrestart.(Reproducedfrom Mansoor[32].) reaccelerate. If the process driven by the motor is able towithstandthe variation in speed or torque, this is a successful throughfrom ride the process point of view. In Fig. 5.53 we see whathappensduring non-synchronousrestart. It now takesabout one second before the inverter is enabled, and another 500 ms for themotor to start reaccelerating. By tha t time the m otor speed hasdropped to almost zero. If the motor is used to power any kind ofproduction process this would almost certainly not be acceptable . However, if the motor is used forair-conditioningthe temporary drop in speed would not be of any concern . 5.3.9 Overview of Mitigation Methods for AC Drives 5.3.9.1 Automatic Restart.The most commonly used mitigation method is to disable theoperationof the inverter, so that themotor no longer loads the drive. Section 5.3 • Adjustable-SpeedAC Drives 299 This prevents damagedue to overcurrents,overvoltages, andtorque oscillations. After the voltage recovers the drive automaticallyrestarted.The is disadvantageof this method is that the motor load slows down morethan needed. When synchronous restartis used thedrop in speed can be somewhatlimited, but non-synchronous restartleads to very largedrops in speed or evenstandstill of the motor. An important requirementfor this type of drive is that the controller remain online.Powering of the controllersduring the sag can be from the dc bus capacitoror from separate of the mechanicapacitorsor batteries.Alternatively, one can use the kinetic energy cal load to power the de bus capacitorduring a sag orinterruption[33], [35], [150]. 5.3.9.2 Installing Additional Energy Storage.The voltage-toleranceproblem of drives is ultimately an energy problem. In manyapplicationsthe motor will slow down too much tomaintain the process. This can be solved addingadditionalcaby pacitorsor a battery block to the de bus. Also the installation of a motor generator set feeding into the de bus will give the required energy. A large amount·of stored energy is needed to ensure tolerance against three-phasesags andshort interruptions. For sags due to single-phase and phase-to-phase faults, which are the mostcommon of the ones, only a limitedamount of storedenergy is needed as at least one phase of improvsupply voltage remains at a high value. This appearsto be the easiest way ing the voltagetolerancefor the majority of sags. 5.3.9.3 Improving the Rectifier.The useof a diode rectifier ischeapbut makes control of the de bus voltage difficult. Themoment the ac voltagemaximum drops below the de bus voltage, the rectifier stops supplying energy andmotor the is powered from thecapacitor.Using acontrolled rectifier consistingof thyristors,like used in de drives, gives some control of the dc bus voltage. When the ac bus voltage drops the firing angle of thethyristors can be decreased to maintain the de bus voltage. For unbalancedsags different firing angles are needed for the three phases which could make thecontrol rather complicated.Additional disadvantagesare that the control system takes a few cycles to react and that the firing-anglecontrol makes the drive sensitive tophase-anglejumps. Anotheroption is to use someadditionalpower electronics todraw more current from the supplyduring the sag. A kind of power electronic currentsource isinstalled between the diode rectifier and the dc bus capacitor.This currentcan becontrolledin such a waythat it keeps the voltage at the de bus constantduring a voltage sag [150], [151]. By using a rectifier consisting of self-commutatingdevices (e.g.,IGBTs), complete control of the dc voltage is possible. Algorithms have beenproposedto keep the de voltage constantfor any unbalance,drop, or change in phase angle in the ac voltages [44], [45],[46]. An additionaladvantageis that theseIGBT inverters enable a sinusoidal input current,solving a lot of theharmonicproblems caused by adjustable-speed drives. The main limitation of all thesemethodsis that they have aminimum operating voltage and willcertainly not operatefor an interruption. 5.3.9.4 Improving the Inverter. Instead ofcontrolling the de bus voltage, it is also possible tocontrol the motor terminal voltage.Normally the speedcontroller assumes aconstantde bus voltage and calculates the switching instantsof the inverter from this. We saw earlierthat the effect of this isthat the de bus voltage is amplitude modulatedon the desiredmotor terminal voltages. This effect can be compensated 300 Chapter5 • VoltageSags-EquipmentBehavior by consideringthe dc busvoltage in the algorithms used to calculatethe switching instants.For this (5.25)should be revised as follows,w ith Vdc the de busvoltage: Vout = V+, Vre;f -V > V er de (5.36) Vref V - < cr Vde This in effectincreasesthe referencevoltagewhen the de busvoltagedrops(insteadof pulse-widthmodulationthis resultsin a kind of "pulse-areamodulation"). The drawback of this method is that it will result in additional harmonicdistortion, especially when the drive isoperatedclose tonominal speed.Again this methodhas aminimum voltage below which it will no longer work properly. 5.4 ADJUSTABLE-SPEED DC DRIVES DC drives havetraditionally been much better suited for adjustable-speedo peration than ac drives.The speedof ac motors is, in first approximation,proportionalto the frequencyof the voltage. The speedof dc motors is proportionalto the magnitudeof the voltage. Voltage magnitudeis much easierto vary than frequency.Only with the introductionof power transistorshavevariable-frequencyinvertersand thus ac adjustable-speeddrives becomefeasible. In thissectionwe will discuss someaspectsof the behaviorof dc drives during voltage sags.Modern de drives come in many different configurations,with different protectionandcontrol strategies.A discussionof all these is well beyondthe scopeof this book. The behaviordescribedbelow doesnot coverall types of de drivesand should be viewed as anexampleof the kind of phenomenathat occur when avoltagesag appearsat the terminalsof a de drive. 5.4.1 Operation of DC Drives 5.4.1.1 Configuration. A typical configurationof a de drive ispresentedin Fig. 5.54. The armaturewinding, which usesmost of the power, is fed via a three-phase controlled rectifier. The armaturevoltage is controlled through the firing angle of the thyristors. The more the delay in firing angle, thelower the armaturevoltage. There is normally no capacitorconnectedto the de bus.The torque produced by the de motor is determinedby the armaturecurrent, which shows almost no ripple due to Firing angle ,--_--J<.---.,. ae -----------, Armature Control system de Figure 5.54 Modern de drive with separately excited armatureand field winding. 301 Section 5.4 • Adjustable-SpeedDC Drives the largeinductanceof the armaturewinding. The field winding takes only a small amountof power; thus a single-phase rectifier is sufficient. The field winding is powered from oneof the phase-to-phase voltagesof the supply. In case field-weakening is used to extend the speed range of the dc motor, a controlled single-phase rectifier is needed. Otherwise a simple diode rectifier is sufficient. To limit the field current,a resistance is placed in series with the field winding. The resulting field circuit is therefore mainly resistive, sothat voltage fluctuations result in current fluctuations and thus in torque fluctuations. A capacitor is used to limit the voltage (andtorque) ripple. To limit thesetorque fluctuations a capacitor is used like the one used to limit the voltage ripple in single-phase rectifiers. 5.4.1.2 DC Motor Speed Control.The standardequivalent circuit for a dc motor is shown in Fig. 5.55. This circuit can only be used for normal operation, because it only considers the componentof de voltages andcurrents.A model including the inductanceof the windings will be discussed further on. The voltage Vf over the field winding causes current a If accordingto (5.37) where Rt is the resistance in the field circuit (the resistance of the winding plus any external series resistance). This field currentcreates theair-gapfield (5.38) which rotateswith a speedWm thus inducing a voltage F., the so-called "back-EMF" in the armaturewinding: E = kwmIf (5.39) This induced voltage limits the a rmaturecurrent fa: Va = E+Rafa (5.40) where Va is the voltage over the a rmaturewinding andRa the resistanceo f the armature winding. Field currentand armaturecurrenttogetherproducea torque (5.41) which accelerates the m otor up to the speed at which m otor torque and load torque balance. The designof the motor is typically suchthat the armatureresistance is low and the field resistance relatively high. Neglecting the armatureresistance gives the following expression for thearmaturevoltage: (5.42) Figure 5.55Equivalent scheme for dc m otor during normaloperation. 302 Chapter5 • VoltageSags-EquipmentBehavior Rewriting this, and using field voltage as an independentvariable, gives the basic expressionfor the speedcontrol of dc motors: (5.43) The speedof a dc motor is increasedby increasingthe armaturevoltageor by decreasing the field voltage. Speedcontrol of a de drive takesplace in two ranges: 1. Armature voltage control range. The field voltage is kept at its maximum value and the speedis controlled by the armaturevoltage. This is the preferred range. The field current is high, thus the armaturecurrent has its minimum value for a given torque. This limits the armaturelossesand the wear on the brushes. 2. Field weakeningrange. Above a certain value the armaturevoltage can no longer be increased.It is kept constantand the speed isfurther increasedby reducing the field voltage. As there is a maximum value for the armature current, the maximum torque decreaseswith increasingspeed. 5.4.1.3 Firing-Angle Control. The de componentof the output voltage of a thyristor rectifier is varied by meansof firing-angle control. The firing angle determines during which part of the cycle the rectifier conducts,and thus the averageoutput voltage. The output voltage of a non-controlledthree-phaserectifier was shown • in Fig. 5.19 in Section5.3. A diode startsconductingthe momentits forward voltage becomespositive; a thyristor conductsonly when the forward voltage is positive and a pulse isapplied to its gate. By firing the thyristor at the instant a diode would start conducting,the output voltage of a controlled rectifier is the sameas that of a noncontrolled one. This is called free-firing. The firing angle of a thyristor is the delay comparedto the free-firing point. Figure 5.56 shows the output voltage of a threephasethyristor rectifier with a firing angle of 50°. For a controlled rectifier the de bus voltage still consistsof six pulsesbut shifted comparedto the output voltage of a non-controlledrectifier. As the conductionperiod is shifted away from the voltage maximum, the averagevoltage becomeslower. 0.8 a .5 ~0.6 ~ ] 0.4 U c 100 150 200 250 Time in degrees 300 Figure 5.56 Output voltageof controlled rectifier with a firing angleof 50°. No capacitanceis connectedto the de bus. Note 350 the differencein vertical scalecomparedto Fig. 5.19. Section 5.4 • Adjustable-SpeedDC Drives 303 A firing angle a delaysconductionover a period 2Jr x T, with T one cycleof the fundamentalfrequency.The averageoutputvoltage(i.e., the dccomponent)for a firing angle a is (5.44) with Vmax the outputvoltageof a non-controlledrectifier. The voltagealso containsan alternatingcomponent,with' a frequency of six times the power system frequency: 300 Hz in a 50 Hzsystem;360 Hz in a 60 Hz system.This voltagecomponentwill not lead tolargefluctuationsin the currentand in torquedue to the largeinductanceof the armature'winding. The firing of the thyristorstakesplaceat acertainpoint of the supplyvoltagesine wave. For this the control systemneedsinformation about the supply voltage. There are different methodsof obtainingthe correctfiring instant: I. The thyristorsare fired with acertaindelay comparedto the zero-crossingof the actualsupply voltage. In normal operationthe threevoltagesare shifted 1200 comparedto eachother. Therefore,the zero-crossingof one voltageis used as areferenceand all firing instantsare obtainedfrom this reference point. This method of control is extremely sensitive to distortion of the supply voltage.Any changein zero-crossingwould lead to achangein firing angle and thus to a changein armaturevoltage. The problem is especially seriousas thyristor rectifiers are themain sourceof notching, creatinglarge distortion of the supplyvoltagesine wave [53], [55]. Onecould end up with a situation where the drive isnot immune to its own emission. 2. The output voltage of a phase-lockedloop (PLL) is used as areference.A phase-lockedloop generatesan output signal exactly in phasewith the fundamentalcomponentof the input signal. The referencesignal is no longer sensitiveto short-time variationsin the supply voltage. This slow response will turn out to be aseriouspotentialproblemduring voltage. sagsassociated with phase-anglejumps. 3. A more sophisticatedsolution is to analyzethe voltage in the so-calledsynchronouslyrotating dq-frame. In the forwardly rotating frame the voltage consists of a dc componentproportional to the positive-sequencesupply voltageanda componentw ith twice the fundamentalfrequencyproportional to the negative-sequence supplyvoltage.In the backwardlyrotatingframethe dc componentis proportionalto the negative-sequence voltage.Using a lowpassfilter will give complexpositive and negative-sequence voltageand thus all required information about the systemvoltages.The choice of the lowpass filter's cut-off frequency is again a compromisebetween speed and sensitivity to disturbances[152], [153]. 5.4.2 Balanced Sags A balancedvoltage sag leads to arathercomplicated.t ransientin the demotor, with a new steadystateat the samespeed as theoriginal one. The new steadystatewill, however,rarely be reached.Most existing drives will trip long before, mainly through the interventionof somekind of protectionin the powerelectronicconverters.But even if the drive doesnot trip, the voltagesag will typically be over well within one second. The new steadystatewill only be reachedfor long shallow sags. 304 Chapter5 • VoltageSags-EquipmentBehavior According to (5.43), themotor speed isproportional to the ratio of armature voltage and field voltage. The voltage sag in all three phases makes that armatureand field voltagedrop the sameamount;the speedshouldthus remain the same. The model behind (5.43), however, neglects thetransient effects, which are mainly due to the inductanceof the motor winding and theinertia of the load. A model of the dc motor, which is valid for transientsas well, is shown in Fig. 5.57, where La and Lf are theinductanceof armatureand field winding, respectively. 5.4.2.1 Theoretical Analysis.The qualitative behavior of the motor can be summarizedas follows, where it is assumed t hat neither thecontrol system nor the protectionintervenes. of the field-winding rectifier • Becauseof the voltage sag, the voltage on ac side will drop. This will lead to a decay in fieldcurrent. The speedof decay is determinedby the amountof energystoredin the inductanceand in thecapacitance. Typically thecapacitorwill give the dominanttime constantso that the decay in fieldcurrentcan be expressed as follows: (5.45) where If o is the initial currentand r is the timeconstantof the decay in field current.The fieldcurrentwill not decay to zero, as suggested by (5.45), but the decay will stop the momentthe field voltage reaches the ac voltageamplitude again. For a voltagedrop of 20% the fieldcurrentwill also drop 20%. This is a similar situationas discussed in Section 5.2. The only difference isthat the load is a constantimpedanceinsteadof constantpower. For small dc voltage ripple it may take 10 cycles or more for the capacitorvoltage, and thus for the field current, to decay.Note that the ripple in the fieldcurrent directly translates into a torqueripple. As thelatter is often not acceptable,a largecapacitanceis generally used. Some drives useconstant-voltage a transformerto supply the field windings. The effect is againthat the fieldcurrentdropsslowly. • The voltage sag leads to a direct drop in armaturevoltage, which leads to a decay inarmaturecurrent.The decay issomewhatdifferent from the decay in field current. The armaturecurrent is driven by the difference between the armaturevoltage and theinducedback-EMF. As this difference isnormally only a few percent,the changein armaturecurrent can be very large. The current quickly becomes zero, but not negative because the rectifier blocks that. From Fig. 5.57 weobtain the following differential equation for the armaturecurrent I a : (5.46) Figure 5.57 Equivalentcircuit for a dc motor during transients. 305 Section 5.4 • Adjustable-Speed DC Drives The solution, with /0 the armaturecurrentat time zero, is I a= E (l Va - E) n, + 0 - n, e Va - _L (5.47) f 1-. where Vais the armaturevoltageduring the sag, andT = As we saw before, the field current remains close to itspre-eventvalue for aDt least a few cycles. Because themotor speed doesnot immediatelydrop, the back-emfE remains of a drop in armaturevoltage is thusthatthe currentdrops the same. The effect toward a large negative value (Va - E)I Ra. We will estimatehow fast thearmaturecurrentreaches zero by a pproximating (5.47) for t « T. Using e-f ~ 1 - ~ gives t, ~ 10 - E-V L at (5.48) a The pre-sagsteady-statecurrent /0 may beobtainedfrom l-E /0=-- (5.49) Ra where thesteady-statearmaturevoltage is chosenequal to 1pu. The time for the currentto reach zero is, in cycles of the fundamentalfrequency: 1 t (X a) 1- E = 21l' Ra 1 - V (5.50) whereX a is thearmaturereactanceat thefundamentalfrequency.For X a/ R a = 31.4 and 1 - E = 0.05 we obtain t I = 10.25 _ V (eye es) (5.51 ) For a sag down to75% the currentdropsto zero in one cycle; for a90% sag it takes 2.5 cycles which is still very fast.T hus for the majority of sags thearmature currentand thetorquewill drop to zero within a few cycles. • The drop in armatureand in field current leads to adrop in torque which causes adrop in speed. Thedrop in speed and the d rop in field currentcause a reductionin back-EMF. II Sooneror later theback-EMFwill become smallerthan the armaturevoltage, reversing thedrop in armaturecurrent. Because speed as well as field current havedroppedthe newarmaturecurrentis higher than the pre-eventvalue. • The more the speed drops,the more theback-EMFdrops,the more thearmature current increases, the more the torque increases. Inother words, the dc motor has abuilt-in speedcontrol mechanismvia the back-EMF. • The torquebecomes higherthan the load torque and the load reaccelerates. • The load stabilizes at theoriginal speed andtorque, but for a lower field current and a higherarmaturecurrent. The drop in field current equals the drop in voltage; thearmaturecurrent increases asm uch as the fieldcurrent drops, because their product(the torque) remainsconstant. 306 Chapter5 • Voltage Sags -EquipmentBehavior 5.4.2.2 Simulationof Balanced Sags. Some simulations have beenperformed to quantify the behavior described above. The results are shown in Figs. 5.58 through 5.61. The simulated drive was configured as shown in Fig. 5.54, with a three-phaserectifier to power the armaturewinding and a single-phaserectifier for the field winding. The drive was operating at nominal speed ,thus with zero firing angle for the rectifiers. In thissystemthe time constantwas 100 ms,both for the armaturewinding and for the field wind ing . Asupply voltage of 660 V was used result. moment of ing in a pre-sagmotor power of 10 kW and a speed of 500 rpm The inertia of the load driven by themotor was 3.65 kgm/s" ,T he load torque was proportional to the speed.The simulations were performed by solving the differential equations with a step-by-stepapproximation[154]. The voltage dropped to 80% in all three phasesduring 500 ms (30 cycles).T he plots show two cyclespre-sag,30 cycles during-sag,and 88 cyclespost-sag. The armaturecurrentis shownin Fig . 5.58.The armaturecurrentdropsto zero in the a veryshorttime due to thephenomenondescribedbefore. As a directconsequence torque becomes zero also , as shown in Fig . 5.60. This inturn leads to a fastd rop in speed, asshown in Fig. 5.61. After a few cycles the fieldcurrent (Fig . 5.59) and the speed havedroppedsufficiently for the back-EMF to becomelower that the armature 2.5 50 2 .5 ~ ::l o 1.5 e a ! 0.5 0.5 1.5 2 Figure 5.S8 DCmotor armaturecurrent dur ing balanced sag. ~ t:: 0.6 ::l o .", ~ 0.4 0.2 0.5 I -~~2 Time in seconds 1.5 Figure 5.59 DCmotor field current during balanced sag. 307 Section 5.4 • Adjustable-SpeedDC Drives 2.5 0.5 0.5 Figure 5.60 Torqueproducedby de motor during balancedsag. 1 Time in seconds 2 1.5 1.15 1.1 a .S 1.05 1 .... ~ 0.95 ~ 0.9 0.85 Figure 5.61 Speedof de motor during balancedsag. 0.8 0 0.5 1 Time in seconds 1.5 2 voltage. From this momenton thearmaturecurrentand thetorquerecover and a few hundredmillisecondslater even exceed their pre-sag value. The result that is the motor picks up speed again. Upon voltage recovery,a round t = 0.5 in the figures, the opposite effect occurs. The armaturevoltage becomes much larger than the back-EMF leading to a large overcurrent,a large torque, and even a significant overspeed. The post-sag transient is overafteraboutone second. Notethat the simulated behavior was due to a sag down to 80% , a rather shallow sag. Due to the fast drop in armaturecurrent even such a shallow sag willalreadylead to a serioustransientin torqueand speed. 5.4.2.3 Interventionby the Control System. The control system of a de drive can control a numberof parameters:a rmaturevoltage, armaturecurrent, torque, or speed. In case the control system is able to keep armatureand field voltageconstant, the drive will not experience the sag. However, the control system will typically take a few cycles to react, so t hat the motor will still experience the fastd rop in armature current.The useof such acontrol system may also lead to an even more severe transient at voltage recovery. The a rmaturevoltage will suddenly become much higher than the back-emfleading to a very fast rise inarmaturecurrent, torque, and speed. 308 Chapter5 • VoltageSags-EquipmentBehavior If the motor aims at keeping themotor speedconstant,the drop in speed (as shown in Fig. 5.61) will be counteractedthrough a decrease in firing angle of the thyristor rectifier. For a deep sag the firing angle will quickly reach its minimum value. Further compensationof the drop in armaturevoltage would requirecontrol of the field voltage. But as we saw above, the field voltage is kept intentionally constantso that control is difficult. 5.4.2.4 Intervention by the Protection.The typical reason for thetripping of a dc drive during a voltagesag isthat one of the settingsof the protectionis exceeded. As shown in Figs. 5.58through 5.61, voltage,current,speed, andtorqueexperience a large transient.The protectioncould trip on anyof theseparameters,but more often than not, the protectionsimply trips on de busundervoltage. DC drives areoften used for processes in which very precise speedpositioning and are required,e.g., in robotics. Even smalldeviationsin speedcannotbe toleratedin such a case. We saw beforethat the motor torquedropsvery fast, even for shallow sags, than for an ac drive. A shallow sag so that the drop in speed will become more severe will alreadyhave the same effect on a de drive as a zero voltage on an ac drive: bothin cases thetorqueproducedby the motor dropsto zero. 5.4.3 Unbalanced Sags One of the effectsof unbalancedsags on dc drives isthat armatureand field voltage do not drop the sameamount. The armaturevoltage is obtained from a three-phaserectifier, the field voltage from a single-phase rectifier. During an unbalanced sag, thesingle-phaserectifier is likely to give adifferent outputvoltage than the three-phaserectifier. If the field voltagedropsmore than the armaturevoltage, the new steady-statespeedcould be higher than the original speed. However, initiallyboth armature and field current decrease, leading to a decrease torque in and thus in speed. The slowest speed recovery takes place when thevoltageremainsconstant. field The back-EMFonly startsto drop when themotor slows down. Thearmaturecurrent will remain zerolonger when the field voltage stays constant. • If the field voltage drops more than the armaturevoltage, theback-emfwill in quickly be lessthan the armaturevoltage, leading to an increase armature current. Also the newsteady-statespeed is higherthan the pre-eventspeed. Overcurrentin the armaturewinding and overspeed are the main risk. • If the field voltagedropslessthan the armaturevoltage, thearmaturecurrent's decay will only be limited bythe drop in motor speed. It will take a long time steady-statespeed is lowert han before themotor torquerecovers. As the new the pre-eventspeed,underspeedbecomes the main risk. Simulationshave beenperformedfor the same driveconfigurationas before. But insteadof a balancedsag, anumberof unbalancedsags were applied to the drive. The results of two sagso f type D and one sag of type C are shown here. All three sags had a durationof 10 cycles, acharacteristicmagnitudeof 50%, and zerocharacteristicphaseanglejump. Note that in this case the sag type refers to the line-to-linevoltages, not the the line-to-neutralvoltage. The rectifier isdelta-connected;thus the line-to-line voltages more directly influence the drivebehavior. 309 Section 5.4 • Adjustable-SpeedDC Drives • SAGI: a sag of type 0 with the large voltagedrop in the phasefrom which the field winding is powered.The field voltagethus drops to 50%. The results for sag I are shown in Figs. 5.62 through 5.65. • SAGII: a sagof type 0 with a small voltagedrop in the phasefrom which the field winding is powered,making the field voltage drop to about 90%. The results for sag11 are shownin Figs. 5.66through 5.69. • SAGIll: a sagof type C with the field windingpoweredfrom the phasewithout The resultsfor sag III voltage drop. The field voltage thus remains at 100%. are similar to those for sag11 and thereforenot reproducedin detail. All plots show two cycles before the sag, 10 cycles during the sag, and 48 cycles that a deep sag in the field voltage(sag I) causes afterthe sag.F romthe figures we can see a highovershootin the armaturecurrent(Fig . 5.63), in thetorque(Fig. 5.64),andin the speed (Fig. 5.65).For a shallowsag in the fieldvoltage(sag11) the armaturecurrentand torqueare zero for a long time, but with smallerovershoot(Figs a . 5.67 and 5.68); the speed shows a large drop but only a smallovershoot(Fig . 5.69).Note the ripple in the armaturecurrentduring the sag. Theunbalancein the acvoltageleads to a muchlarger , Figure 5.62 Fieldcurrentfor sag type D, with largedrop in field voltage. Figure 5.63Armaturecurrentfor sag type D, with large drop in field voltage. 0.2 0.4 0.6 Time in seconds 0.8 0.8 310 Chapter 5 • Voltage Sags -Equipment Behavior 5 4 ;> "'- .S ., eB 3 ... B 2 0 ::E 0.8 Figure 5.64Motor torque for sag type D, with large drop in field voltage. 1.3 ~-- ---,---,--~--~---, 1.25 1.2 5. .S 1.15 1l ~ 1.1 ~ 1.05 ::E 0.95 0.2 0.4 0.6 0.8 Figure 5.65Motor speed for sag type D, with large drop in field voltage. 0.8 Figure 5.66 Fieldcurrentfor sag type D, with smal1 drop in field voltage. Time in seconds ;> c, .S 0.8 C 50.6 o '" "0 u: 0.4 0.2 0.2 0.4 0.6 Time in seco nds 311 Section 5.4 • Adjustable-SpeedDC Drives 5 c----~----.---_--~-----, 4 0.4 0.6 Time in seconds Figure 5.67 Armaturecurrentfor sag type D, with small drop in field voltage . 0.8 5 4 ::l 0. .5 3 <Ll ::l go B .... 2 ~ ~ 0.4 0.6 Time in seconds Figure 5.68 Motor torque for sag type D, with small drop in field voltage . 0.8 1.15 1.1 5. .5 1.05 1 J .... ~ 0.95 ~ 0.9 0.85 Figure 5.69 Motor speed for sag type D, with small drop in field voltage . 0.2 0.4 0.6 Time in seconds 0.8 312 Chapter5 • VoltageSags-EquipmentBehavior ripple in armaturevoltage than during normal operation.This ripple disappearsupon voltagerecovery and is alsonot presentduring a balancedsag (Fig. 5.58). The maximumand minimum values forcurrent,torque, and speed are shown in Table 5.9. All values are given as percentage a of the averagepre-eventvalue.Tripping of the drive can be due to undervoltageor overcurrent.The undervoltageis similar for the three sags; thus sag I is the most severe one for the electrical part of the drive becauseof the largearmaturecurrent. The mechanicalprocess can, however, get disrupted due to torque variations and variations in speed.For a process sensitive to underspeed,sags II and III aremostsevere; for a process sensitivetorquevariations, to sag I is themostsevere one. The main conclusionis that unbalancedsagsrequiretesting for all phases; it ishardto predictbeforehandwhich sag will be most severe to the drive. TABLE 5.9 DC Drive PerformanceDuring UnbalancedSags inDifferent Phases Field Current Sag I II III Type FieldVoltage 50% 90% 100% D D C ArmatureCurrent min max min 59% 900AJ 100% 100% 100% 100% 0 0 0 max 460% 264% 229% Motor Torque min 0 0 0 max 367% 256% 229% Motor Speed min max 93% 85% 85% 124% 107% 114% 5.4.4 Phase-Angle Jumps Phase-anglejumps affect the angle at which the thyristors are fired. The firing instantis normally determinedfrom the phase-lockedloop (PLL) output, which takes at least several cycles to react to the phase-anglejump. A calculatedstepresponseof a conventionaldigital phase-lockedloop to a phaseangle jump is shown by Wang [57]. His results arereproducedin Fig. 5.70, where we can seethat it takesabout400 ms for thePLL to recover. Theerror gets smallerthan 10% after about250 ms, which is still longerthan the durationof most sags. Thus for our initial analysiswe can assumethat the firing instantsremain fixed to thepre-event voltage zero-crossings.W ith additional measures it is possible to m ake PLLs which respondfaster tophase-anglejumps, but those will be more sensitive to harmonicsand other high-frequencydisturbances. We can reasonablyassumethat the phase-locked-loopoutput does not change during the sag.The effect of the phase-anglejump is that the actual voltage is shifted 0.....--....----------------. -0.2 -0.4 -0.6 -0.8 -1 -1.2 ......-------I ~ o 0.1 0.2 0.3 0.4 0.5 Time (sec) 0.6 0.7 0.8 Figure 5.70 Stepresponseof a conventional digital phase-lockedloop. (Reproducedfrom Wang[57].) 313 Section 5.4 • Adjustable-SpeedDC Drives Firing I I I ::s 0.8 PLLoutput 0.. ,/ .S '" ,Supplyvoltage , I I ~0.6 \ I \ I S 15 \ I I ;> 0.4 \ I \ I \ t \ I \ I 0.2 , \ I \ I \ I \ I \ I \ I o Figure 5.71 Influenceofphase-lockedloop on firing angle. \ 50 250 100 150 Timeindegrees 200 Actual firing Intendedfiring ::s 0.8 e, .S ~ ~ 0.6 ;> 0.4 0.2 Figure 5.72Influenceof phase-locked loop on firing angle: with actual voltage as a reference. 0"----.A---a..---..4.-~-~-..L-----'--J o 50 100 Timeindegrees 150 200 comparedto the reference voltage. Because of this thyristors the are fired at a wrong point of the supply-voltagesine wave. This is shown in Fig. 5.71 for a negative phaseof anglejump. The during-sagvoltage lags the pre-sag voltage; thus the zero-crossing the actualsupply voltage comes later than the zero crossingo f the PLL output. In Fig. o f the actualvoltage is used as a reference: due to the negative phase5.72 the sine wave anglejump t!¢, the thyristorsare fired at an anglet!¢ earlier than intended. 5.4.4.1 Balanced Sags.For balanced sags the phase-angle jump is equal in the three phases; thus the shift in firing angle is the same for all three voltages. If the shift is lessthan the intendedfiring-angle delay, theoutput voltage of the rectifier will be higher than it would be without phase-anglejump. This assumesthat the phase-anglejump is negative, which isnormally the case. A negativephase-angle jump will thus somewhatcompensatethe drop in voltage due to the sag. For a positive phase-anglejump the output voltage would be reduced and the phase-anglejump would aggravatethe effects of the sag. For a firing angle equal toa the pre-sagarmaturevoltage equals Va = cos(a) (5.52) 314 Chapter5 • VoltageSags-EquipmentBehavior 120,------r-110 = ~ 100 8- .5 ~ 70 degrees 90 S ~ 80 :g ~ 70 o 60 30 degrees 5 10 15 20 Phase-anglejump in degrees 25 Figure5.73 Influenceof phase-anglejump on 30 the armaturevoltage,for different firing angles. The voltage is rated to thearmaturevoltage for zero firing angle.For a sag with magnitude V (in pu) and phase-anglejump !:14>, the during-eventarmaturevoltageis V~ = V x cos(a - /j.l/J) (5.53) The phase-anglejump is assumednegative, /j.(j> is its absolutevalue. The ratio between V~ and Va is the relativemagnitudeof the sag in thearmaturevoltage.This isplottedin Fig. 5.73 for firing-angle delayso f 30°, 50°, and 70°. Aduring-eventmagnitude V of 500~ has beenassumed,and the phase-anglejump is varied between zero and 30°. According to Fig. 4.86 this is the range one can expect for50% a sag. For large firing-angle delays thearmaturevoltageis low; thusa jump in phase-anglecan increase the voltagesignificantly. For a 70° firing-angle delayandphase-anglejumpsof 20° and higher theduring-eventvoltageis evenhigher than the pre-eventvoltage.Whetherthis actually makesthe sag less severe dependson the behaviorof the fieldvoltage.When a diode rectifier is used topowerthe field winding, the fieldvoltagewill not be influenced by the phase-anglejump. The consequenceof the phase-anglejump is that the field voltagedropsmorethanthe armaturevoltage,similar to sag Idiscussedin the previous section. This can lead to large overcurrentsin the armaturewinding and to overspeed. of missing pulses which would make When a controlled rectifier is used there is a risk the field voltagemuch lowerthan the armaturevoltage. If the shift is largerthan the intendedfiring-angle delay, theactualfiring will take place before the free-firingpoint. As the forward voltage over the thyristors is still negative it will not commenceconducting.How seriousthis effect isdependson the o f a shortpulse will makethe drivemoresensitive. durationof the firing pulse. The use Note that eitherthe armatureor the field rectifier isoperatedat its maximumvoltageso that at least one of them always will be proneto missing pulses. 5.4.4.2 UnbalancedSags. For unbalancedsags thesituation becomes rather complicated. In most cases thedifferent phases showpositive as well as negative phase-anglejumps. Thus for some phasesthe phase-anglejump can be animprovement, for othersnot. Somephasesmight miss their firing pulses,o thersnot. The armature winding might be influenceddifferently from the field current as wealready saw before. 315 Section 5.4 • Adjustable-SpeedDC Drives 1.1r-------.---~---- & 0.9 .~ 0.8 co 11o 0.7 > ] 0.6 ~ 0.5 0.4 0.5 Figure 5.74 DCvoltage for sag type D, with rectifier operatingat 10° firing angle. 1 1.5 2 Time in cycles 1.1....----..,-----r------r------, =' 0.9 Q. .9 08 4) • co ~ > 0.7 .8 0.6 g 0.5 0.4 Figure 5.75 DCvoltage for sag typeC, with rectifier operatingat 10° firing angle. 0.5 1 1.5 2 Time in cycles Figures5.74 and 5.75 show the dc bus voltagebeforeandduring a voltage sag, in of a case the rectifier isoperatedat a firing angleof 10°. Figure 5.74 shows the effect m agnitudethe maxtype D sagof 50% magnitude.As all three voltages go down in imum de voltage alsodrops. The two voltage pulses belonging to the least-affected phases come very close after each other. In the phasor diagram they move away from eachother, so that the voltagemaxima of the rectified voltage come closer. The consequence is that the commutationbetween these two phases takes place natural at a commutationpoint. The firing of the thyristor has taken place already before that momentin time. Thereis thus a risk for a missing pulse which would even more distort the de bus voltage.Figure 5.75 shows the effectof a type C sagof 50% magnitude. 5.4.5 Commutation Failures The momenta thyristor is fired andforwardly biased, itstartsconducting.But the of the currentthroughthe conductordoesnot immediatelyreach its full value because inductive nature of the source.Considerthe situation shown in Fig. 5.76, where the 316 Chapter 5 • VoltageSags-EquipmentBehavior L + + Figure 5.76 Origin ofcommutationdelay. currentcommutatesfrom phase1 to phase2. The driving voltagesin these twophases are shifted by 1200 : (5.54) (5.55) At time zero the two driving voltagesare the same,thus the line-to-line voltageis zero, which correspondsto the free-firing point. For a firing-delay anglea, thyristor 2 is fired at lJJot = a. This is the moment the current through thyristor I startsto rise and the currentthrough thyristor 2 startsto decay.The changein currentis describedthrough the following differential equation (note that both thyristors conduct, thus the two phasesare shorted): Vt(t) - L di, di 2 di + L di = (5.56) V2(t) with L the sourceinductance.We can assumethe armaturecurrent Ide to be constant; thus the changesin i} and i 2 compensateeachother: di 1 + di2 dt dt =0 (5.57) after which i 2 can be obtainedfrom the differential equation: di2 di= J3v sin(wot) (5.58) 2L with the following solution: ;2(t) = ~~ [cos(a) - cos(eoot)], a t>- Wo (5.59) Commutation is complete and thyristor 1 ceases to conduct when i2(t) = Ide. Commutationtakeslonger for smaller valuesof V, thus during voltage sags,and for a firing-delay anglea closerto 1800 , thus for the drive beingin regenerativemode.The maximumcurrent the supply voltage is able to cummutateis found from (5.59) as J3v I max = 2eoo (l L + cosa) (5.60) Section 5.4 • Adjustable-SpeedDC Drives 317 If this is lessthan the actual armaturecurrent, a commutationfailure occurs:both thyristors will continueto conduct,leading to aphase-to-phase fault. This will cause blowing of fuses ordamageof the thyristors.The risk ofcommutationfailure isfurther increased by the increased armaturecurrentduring and after the sag. j ump reduces theactualfiring angle, thus lowering the risk A negativephase-angle of commutationfailure. A positive phase-anglejump makes acommutationfailure more likely. Unbalancedfaults cause acombinationof positive and negative phaseanglejumps, thus increasingthe risk in at least one phase. 5.4.8 Overview of Mitigation Methods for DC Drives Making de drivestolerant againstvoltage sags is more complicatedthan for ac drives. Threepotentialsolutions,to be discussed below, are addingcapacitanceto the armaturewinding, improvedcontrol system, andself-commutatingrectifiers. 5.4.6.1ArmatureCapacitance. Installing capacitanceto the armaturewinding, on dc side of thethree-phaserectifier, makesthat the armaturevoltage no longer drops instantaneouslyupon sag initiation. Insteadthe armaturevoltage decays in a similar way to the field voltage. Toobtain a large timeconstantfor the decay of the armaturevoltage requires a large c apacitorfor the armaturewinding. Note that the power taken by thearmaturewinding is much largerthan the power taken by the field winding. For three-phaseunbalancedsags it may be sufficient to keep up the voltage during one half-cycle. Keeping up thearmaturevoltage will still not solve theproblemof missing pulses due to phase-anglejumps and commutationfailures. Another disadvantageof any amountof armaturecapacitanceis that it makes the drive react slower to the control system.Changesin motor speed areobtainedthrough changes in firing angle. The armaturecapacitanceslows down the response of the armaturecurrent and torque on a change in firing angle. When the drive applicationrequires fast changes torque in and speed, thea rmaturecapacitanceshould be small. 5.4.6.2 Improved ControlSystem. Any control system for a de driveultimately controls the firing angleof a controlled rectifier. This may be thearmaturerectifier, the field rectifier, orboth. Due to thenatureof a thyristor rectifier it is unlikely that the control system will have anopen-loop time constantless than two cycles. We saw beforethat the drop in armaturecurrent and torque takes place much faster than this. It is thus not possible toprevent the transient in armaturecurrent and torque. Two straightforwardquantitiesto becontrolledare armaturevoltage andmotor speed.Controlling the armaturevoltage enables the use of a simplecontroller with a small open-looptime constant.For the controller to work, sufficientmargin must be available in the rectifier to bring the a rmaturevoltage back to1000/0. If sags down to 50% magnitudehave to bemitigated, the normal operatingvoltage on de sideof the rectifier shouldnot exceed50°A, of maximum. The result is t hat only half of the control rangeof the rectifier can be used for speed control. The otherhalf is needed for voltagesagmitigation. Speedcontrol is thecommonly-usedmethodof control for de drives. The voltage sag will cause adrop in speed. The speed controllerdetects this and reduces the firing angle tocompensate.If the firing angle is zero thecontrollercan no longer increase the 318 Chapter5 • Voltage Sags-EquipmentBehavior speed. Speed control will not mitigate thetransientsin torque and current but it may reduce the variations in speed. A disadvantageof both control techniques isthat they will lead to a severe transient inarmaturecurrent and torque upon voltage recovery. 5.4.6.3 Improved Rectifiers. The control of the drive may be significantly imenable control of the proved by using a self-commutating rectifier. These rectifiers output voltage on a sub-cycle timescale. This will preverit the drop in armature voltage and thus the severe drop in torque. Using advancedcontrol techniquesit may also be possible to install additional enery storagewhich is only madeavailable during a reduction in the supply voltage. By using self-commutating rectifiers it may also possibleto be usea sophisticated control systemthat detects and mitigates phase-anglejumps. With such a control system, the reference signal should no longerobtainedfrom be a phase-lockedloop but from the measured supply voltage through a suitabledigital filter. 5.4.6.4 Other Solutions. Other solutionsinclude a more critical setting of the undervoltageand overcurrentprotection; the useof componentswith higher overcurrent tolerance; and disabling the firing of the t hyristors to prevent tripping on overcurrent.All these solutions are only feasible when the load can tolerate rather large variationsin speed. 5.5 OTHER SENSITIVE LOAD 5.5.1 Directly Fed Induction Motors Despite the growth in the number of adjustable-speeddrives, the majority of induction motors are still directly fed; i.e., the m otor terminals are connectedto the constantfrequency,constantvoltage, supply. It will beclear that speedcontrol of the motor is not possible. Directly fedinduction motors are rather insensitiveto voltage sags,althoughproblems could occur when too manymotorsare fedfrom the samebus. The drop in terminal voltage will cause d a rop in torquefor an induction motor. Due to this drop in torquethe motor will slow down until it reachesa new operating point. If the terminal voltage drops too much the load torque will be higher than the pull-out torque and themotor will continue to slow down. An induction motor is typically operatedat half its pull-out torque. As thepull-out torque is proportional to the square of the voltage, a voltage drop to 70% or less will not lead to a new stable operatingpoint for the induction motor. The d rop in speed isseldoma seriousconcern for directly fed induction motors. These kind motorsare of usedfor processesthat are not very sensitive to speed variations; and variation the in speedis seldommore than 10% • The effect of voltage sags on induction motors has already been discussedin Section 5.3 under the assumption that both motor and load torqueremainconstant.In motor most practical cases the load torque decreases and the torqueincreaseswhen the motor slows down. The actual drop in speed will thus be lessthan indicated. Although the inductionmotor is normally ratherinsensitiveto voltagesags,there are a few phenomena t hat could lead to process i nterruption due to a sag. • Deep sags lead to severe torque oscillationsat sagcommencementand when the voltage recovers. These could leaddamageto to the motor and to process 319 Section 5.5 • Other Sensitive Load • • • • interruptions.The recoverytorquebecomes more severe when the internal flux is out of phasewith the supply voltage, thus when the sag is associated with a phase-anglejump. At sagcommencementthe magneticfield will be driven out of the airgap. The associatedtransientcauses anadditionaldrop in speed for deep sags. During this period the motor contributesto the short-circuit current and somewhat mitigatesthe sag. This effect has been discussed in Section 4.8. When the voltage recovers, the airgapfield has to be built up again. In weaker systems this can last up to 100ms, during which the motor continuesto slow down. This could become a problem in systems where them otor load has grown over the years. Where in the past a voltage sag would notproblem, be a now "suddenly"the process can no longer withstandthe speeddrop due to a sag. As deep sags are rare it can take a long time before such problem a is discovered. Whenthe voltage recovers, the motor takes a high inrushcurrent:first to build up the airgap field (the electricalinrush), next to reaccelerate the motor (the mechanicalinrush). This inrush can cause apost-faultsag with adurationof one second or more, and lead tripping to of undervoltageand overcurrent relays. Again thisproblem is more severe for a weak supply, and can thus become aproblemwhen theamountof motor load increases. For unbalancedsags themotor is subjected to a positive sequence as well as to a negative-sequence voltage at the terminals. The negative-sequence voltage causes atorqueripple and a large negative-sequence current. 5.5.2 Directly Fed Synchronous Motors A synchronousmotor has similar problemswith voltage sags as an induction motor: overcurrents,torque oscillations, and drop in speed. But asynchronous motor can actuallylosesynchronismwith the supply. Aninductionmotor is very likely able to reaccelerateagain after the fault: it might take too long for the process, the currentmight be too high for themotor (or its protection),or the supply might be too weak, but at least it is intheorypossible. When asynchronousmotorloses synchronism it has to bestoppedand the load has to be removed before it canbroughtback be to nominal speed again. The lossof synchronismof a synchronousmotor is ruled by theequationfor the transportof power P from the supply to the motor: p = V.vupEsin </J X (5.61) with v'vup the supply voltage,E the back-EMFin the motor, </J the angle between the back-EMF and the supply voltage, andX the reactance between the supply and the reactanceof the motor and the source synchronousmotor (this includes the leakage reactanceof the supply). Thisrelationis shown in Fig. 5.77.For a givenmotor load the operatingpoint will be such that the powertaken by the load equals the power transported to the motor. This point is indicatedin Fig. 5.77 as"normal operatingpoint." When the voltagedrops,e.g.,duringa sag, the powertransportedto themotor becomes smaller than the power taken by the load. As a result the m otor slows down, which meansthat the angle</J increases. The angle will settle down at a new operatingpoint, Chapter5 • VoltageSags-EquipmentBehavior 320 Pre-sag power 0.8 Normal ::s 0.. .8 ~ ~ 0 During-sag power operating point 0.6 Operatingpoint with reduced voltage ~ 0.4 0.2 0 50 100 150 Rotor angle in degrees 0 200 Figure5.77 Powertransferto a synchronous motor as a function of the rotor angle. indicated by "operatingpoint with reducedvoltage," where again the power to the motor and the powertaken by the load are in balance. It follows from Fig. 5.77that for deep sags there is no longer a stable operating point. In that case therotor angle will continueto increase until the supply voltage the loses synchronism.Looking at recovers.If the angle has increased too much motor Fig. 5.78 we see twooperatingpoints: the normaloperatingpoint, labeled as"stable" and a secondpoint labeled as"instable."In the latterpoint, bothpower flows are again equal so themotor would be able tooperateat constantspeed. But any small deviation will make that the motor drifts away from thisoperatingpoint: either to the left (when it will end up in the stableoperatingpoint) or to the right (when it will lose synchronism). The motor losessynchronismthe moment its rotor angle exceeds this instable operatingpoint. There is a second curve plotted in Fig. 5.78, which indicates the power transfer during the sag. In this case there is no stable operatingpoint during the sag and the motor will continueto slow down until the voltage recovers. At thatmomentthemotor Operatingangle I I Critical angle I I I I I I I 0.8 I ::s I I 0.. c:: 'ii 0.6 ~ Q.c 0.4 0.2 0 0 50 100 150 Rotor angle in degrees 200 Figure5.78 Powertransferin normal situationand for a deep sag. 321 Section 5.5 • Other Sensitive Load will start to accelerate again but as it still rotates slower than the airgap field (thus slower than the frequency of the supply voltage) rotor its angle will continue to increase. The maximumrotor angle is reached the moment the motor speed comes back to nominal. As long as this angle is smaller than the angle for the instable operatingpoint, themotor does not lose synchronism. The figure shows the maximum angle at the end of the sag which does not lead to an instable situation; this angle is indicated as"critical angle." According to the so-called "equal-area-criterion"the two [207]. shadedpartsin the figure are equal in area The highest possiblesteady-staterotor angle equals 90 °-this occurs when the motor load equals the maximum power which can transportedto be the motor. If the motor load is onlyhalf this maximum value, a drop in voltage to 50% will bring the operatingpoint back to the top of the sine wave again. This 50% is, however, not the deepest sag the m otor can withstand for a long time. The drop in voltage causes the motor to slow down, thus when the r otor angle reaches 90° it does not stop but will continue to increase until the voltage recovers. The deepest long-durationsag can be found from Fig. 5.79. Again theequal-areacriteria tells usthat the two shadedparts have the same area . Operating angle I I I I 1 I I 0.8 I :s I I , 0. <: 't 0.6 ~ 0 I:l-o 0.4 0.2 Figure 5.79 Powertransferin normal situationand for the deepest long-duration sag. 0 0 50 100 150 Rotor angle in degrees 200 5.5.3 Contaetora Contactorsare a very common way of connecting motor load to the supply. The supply voltage is used to power an electromagnetwhich keeps thecontactin place. When the supply voltage fails the contactopens, preventing the m otor from suddenly restartingwhen the supply voltage comes back. This works fine for long interruptions where the unexpected starting of motors can be verydangerous.But contactorsalso drop out for voltage sags and short interruptionswhere such a behavior is not always acceptable. Test results for contactorsare presented in[34]. The measuredvoltage tolerance curve for a contactoris shown in Fig. 5.80. We see that the contactortolerates any voltage sag down to a bout70%. When the sag magnitudeis below 70% for longer than a few cycles, thecontactordrops out. We also see the remarkableeffect that the voltage tolerance becomes better for deeper sags: a zero voltage toleratedfor can be 3.5 cycles but a 50% voltage only for one cycle. This effectprobablydue is to the experimental setup. Sags were generated by switching between normal a supply and the out- 322 Chapter5 • VoltageSags-EquipmentBehavior 0.8 a ] .8 0.6 .~ «S 0.4 ~ 0.2 246 Duration in cycles 8 Figure 5.80Voltage-tolerancecurve for a contactor.(Data obtainedfrom [34].) put of a variable-outputtransformer.It is not the voltagebut the currentthrough the coil that causes the force keeping the contactorclosed. Themomentthe currentdrops below acertainvalue thecontactorwill startto drop out. For lower voltages thecurrent path through the transformeris smaller, thus there is less resistanceto damp the current. As the current dampsmore slowly for smaller voltages, the c ontactorwill not drop out as fast as for medium voltages. This shows that for contactorsthe supply characteristicscan significantly influence the voltage tolerance. The factthat it is the currentand not the voltagethatdeterminesthe droppingout of the contactorfollows also from thedependenceof the voltagetoleranceon thepointon-wave of sag commencement.The contactorof Fig. 5.80 toleratesa 3.4 cycle sag startingat voltage zero, but only a 0.5 cycle sag startingat voltagemaximum. As the contactorcoil is mainly inductivethe currenthas amaximumat voltagezero andis zero at voltage maximum. The influenceof the point-on-waveof sagcommencementhas beenfurther studied by Turner and Collins [38],reporting a voltage toleranceof 30 ms for sag comof the voltage zero crossing, reducing to less than 8 ms for sags mencements within 30° commencingat voltagemaximum. Note that all this refers to so-called ac contactors.An alternativeis to use de contactorswhich are fed from aseparatedc system with their ownbattery backup. Thesecontactorsdo normally not drop out during voltage sags.However,they require a separatede system and analternativeprotection againstunexpectedrestart of the motor. 5.5.4 Lighting Most lampsjust flicker when a voltage dip occurs. Somebodyusing the lamp will probably notice it, but it may not .beconsideredas somethingserious. It isdifferent when the lamp completely extinguishes and takes several minutesto recover. In industrial environments,in places where a large numberof people aregathered,or with street lighting, this can lead todangeroussituations. Dorr et a1. [36] havestudiedthe voltagetoleranceof high-pressuresodiumlamps. Voltage sags can extinguish the lamp, which must cool down for one to several minutes beforerestarting.The voltage-tolerancecurves for three lamps are shown in Fig. 5.81. For voltages below50% the lampsalreadyextinguishfor a sagof lessthan two cycles. 323 Section 5.5 • Other Sensitive Load 0.8 [ .s 0.6 ~ .~ 0.4 ~ 0.2 Figure 5.81 Voltage toleranceof highpressuresodium lamps. (Data obtainedfrom Dorr et al. [36].) 5 10 Duration in cycles 15 20 The lampstook aboutoneminuteto restrike, andanotherthree minutes before the full light intensity was reached again. The voltage tolerance of the lamp isfurther dependent on the age. When lamps age they need a larger voltage to operate; they will thus extinguishalreadyfor a lower drop in voltage. The minimum voltage for longer sags varied from 450/0 for new lamps to850/0 for lamps at the end of their useful life. Voltage SagsStochastic Assessment In this chapterwe discussmethodsto describe, measure, and predictthe severityof the voltagesag problem: how many times per year will the equipmenttrip. Thereare two methodsavailablethat quantify the severityof the problem: powerquality monitoring and stochasticprediction. Power quality monitoring gives mainly information about commonevents.For lesscommoneventsstochasticpredictionis more suitable. In this chapterboth are discussed in detail. After explainingthe need forstochasticassessment, the variousways of presenting the voltagesagperformanceof the supply are discussed. The chaptercontinueswith some aspectsof voltage sagmonitoring, including the resultsof a number of large surveys.Finally, two methodsfor stochasticprediction of voltage sags are discussed, togetherwith a few examples. The methodof fault positionsis suitablefor implementation in computersoftwareand is thepreferredtool for studies in meshed transmission systems.For radial distribution systems andhandcalculations,the methodof critical distancesis more suitable. 8.1 COMPATIBILITY BETWEBN EQUIPMENT AND SUPPLY Stochasticassessment of voltage sags is needed to find out whethera pieceof equipment is compatiblewith the supply. A studyof the worst-casescenariois not feasible as the of .worst-casevoltage disturbanceis a very longinterruption. In some cases, a kind "likely-worst-case-scenario"is chosen, e.g., a fault close to the equipmentterminals, clearedby the primary protection,not leading to aninterruption.But that will not give any informationaboutthe likelihood of an equipmenttrip. To obtaininformation like that, a "stochasticcompatibility assessment" is required. Such a study typically consists of three steps: 1. Obtain system performance.Information must beobtained on the system performancefor the specific supply point: the expected number of voltage sags with different characteristics.There arevarious ways to obtain this 325 326 Chapter6 • VoltageSags-Stochastic Assessment information:contactingthe utility, monitoringthe supplyfor severalmonths or years, or doing astochasticpredictionstudy. Both voltagesagmonitoring and stochasticprediction are discussed in detail in this chapter.Note that contactingthe utility only shifts theproblem, as also the utility needs to perform either monitoring or a stochasticpredictionstudy. 2. Obtain equipment voltage tolerance. Information has to beobtainedon the behaviorof the pieceof equipmentfor variousvoltagesags. Thisinformation can beobtainedfrom theequipmentmanufacturer,by doing equipmenttests, or simply by taking typical values for thevoltagetolerance.This part of the compatibility assessment is discussed in detail inC hapter5. 3. Determine expected impact. If the two types of information are availablein an appropriateformat, it is possible toestimatehow often the pieceof equipmentis expected to trip per year, and what the (e.g., financial)impactof that will be. Based on theoutcomeof this study onecandecide toopt for a better supply, for better equipmentor to remain satisfied with thesituation. An essentialcondition for this step isthat systemperformanceand equipment voltage toleranceare presentedin a suitableformat. Some possibleformats are discussed in Section 6.2. is given, based on Fig. 6.1. An exampleof a stochasticcompatibility assessment The aim of the study is to comparetwo supply alternativesand two equipmenttolerances. The twosupply alternativesare indicated in Fig. 6.1 through the expected numberof sags as afunction of the sag severity:supply I is indicatedthrougha solid line; supply II through a dashedline. We further assume the following costs to be associatedwith the two supply alternativesand the two devices (inarbitrary units): supply supply device device I II A B 200 units/year 500 units/year 100units/year 200 units/year We also assumethat the costsof an equipmenttrip are to units. 160 140 ft 120 ~ 8. 100 fI) bO ~ fI) ~ ... 80 0 U -a i 60 \ \ \ \ \ 40 \ ,, , I 20 - - __: _-_-__ -_-_-_-__ -_-_-_-__ -_-_- J o '-----'---"---'------'----'--~-~-.-j 10 20 30 40 50 60 Severityof thesag 70 80 Figure 6.1 Comparisonof two supply alternatives(solid curve: supply I, dashed curve: supplyII) and twoequipment tolerances (solid vertical line: device A, dashedline: device B). 327 Section 6.1 • Compatibility BetweenEquipmentand Supply From Fig. 6.1, one canreadthe numberof spurioustrips per year,for eachof the four designoptions, at the intersectionbetweenthe supply curve and the device (vertical) line. For device AandsupplyI we find 72.6spuriousequipmenttrips peryear,etc. The resultsare shown in Table 6.1. TABLE 6.1 Numberof SpuriousTrips per Year forFour Design Alternatives Device A Device B Supply I Supply II 72.6 14.6 29.1 7.9 Knowing the numberof trips per year, theannualcostsof eachof the four design options,andthe costsper spurioustrip, it is easy tocalculatethe total annualcosts.For the combinationof device A and supply I thesecostsare 72.6 x 10 + 100+ 200 = 1026units/year The resultsfor the four designoptionsareshownin Table6.2. From this tableit follows that the combinationof supply I and device B has thelowest annualcosts. TABLE 6.2 Total Costs per Year forF our Design Alternatives Device A Device B Supply I Supply II 1026 546 891 779 Note the stochasticcharacterof the assessment. An expectedvalue (the expected numberof equipmenttrips per year multiplied by the cost of one equipmenttrip) is addedto a deterministicvalue (the annualcost of supply and device). Assumethat the voltagetolerancefor a device is thesameunderall circumstances;the voltagetolerance is thusa deterministicquantity. But the numberof sags willvary from yearto year. We further assumethe occurrenceof a sag to beindependento f the occurrenceof other sags. Inthat case thenumberof sags inany given year follows a Poissondistribution. Let N be thenumberof sags inany given year and JL the expectednumberof sags (as indicatedin Table 6.1). The probability that N = n for a Poissondistribution is found from J1,n Pr{N = n} = e-/Ln! (6.1) For the four design alternativesin Table 6.1 this distribution has been plotted in Fig. 6.2. It follows from the figure, for example,that the number of trips of design BII (supply II in combinationwith device B)varies between2 and 18, and for design BI between7 and26. It is thusnot surethat in a given year,designBII gives lesstrips than design BI. From the probability density function for the number of trips (Fig. 6.2) the probability densityfunction for the total costsper year can be calculated,resultingin 328 Chapter6 • VoltageSags-Stochastic Assessment 0.15 BII 0.1 g ~ .,J:) e ~ AI 0.05 20 40 60 80 Numberof sags in a given year 0.15 g 100 Figure6.2 Probabilitydensityfunction of the numberof sags per year for four design alternatives. "BII 0.1 ~ £ 0.05 400 600 800 1000 Total costs in a given year 1200 Figure6.3 Probabilitydensityfunction of the costsper year forfour design alternatives. Fig. 6.3. This figure showsthat design BI is clearlybetterthan any of the otherdesign options. 6.2 PRESENTATION OF RESULTS: VOLTAGE SAG COORDINATION CHART In this section we discuss numberof a ways to presentthe supplyperformance.The discussionconcentrateson the presentationof results obtainedfrom power quality monitoring.The sametechniquecan beappliedto the resultsof a stochasticassessment study. 8.2.1 The Scatter Diagram Every power quality monitor will at least givemagnitudeand duration as an output for a sag. When the supply monitoredfor is a certainperiod of time, anumber of sags will berecorded.Each sag can be characterizedby a magnitudeand aduration and be plotted as one point in the magnitude-durationplane. An example of the resulting scatterdiagramis shown in Fig. 6.4. Thescatterdiagramis obtainedfrom 329 Section 6.2 • Presentationof Results: Voltage Sag CoordinationChart 1---------------------, 0.9 0.8 •• ! .. r, aO.7 • .~ 0.6 ~ 0.5 .~ 0.4 ~ 0.3 0.2 0.1 Figure 6.4 Seatterdiagramobtainedby one year of monitoring at an industrial site. °0 5 10 15 20 2S 30 Duration in cycles 35 40 45 Voltage swells Lower thresholdfor swells Upper threshold for sags Sags due to motor starting Voltage sags due to short circuits Figure 6.5 Scatterdiagramas obtainedfrom a large power quality survey. Short interru tions Duration one yearof monitoringat anindustrialsite [155]. For a large powerquality survey, the of the resulting scatterdiagramsof all the sites can be combined. A stylized version scatterdiagram is shown in Fig. 6.5. In this figure not only voltage sags, but also interruptionsand voltage swells are indicated. In Fig. 6.5 we see anumberof heavily populatedregions: • Voltage sags due tos hort circuits, with durationsup to a fewhundredmillisecondsand magnitudesfrom 50% upwards.Deeper and longer sags are present but rare. • Voltage sags due to m otorstarting,with durationsof a few seconds and longer, and magnitudesfrom 800~ upwards. • Short interruptionsdue to fast reclosing, with voltage magnitudezero and durationsfrom about 10 cyclesonward. • Voltage swells with similardurationsas sags due to s hortcircuits, but magnitudes up to1200/0. Next to these densely populatedareas there are scattered,long, deep sags, likely due to the errorsmade inrecordingdurationof sags with a long,post-faultsag. These long, deep sagsconsistof a short,deep sag followed by a long, shallow sag. This points to one 330 Chapter6 • VoltageSags-Stochastic Assessment of the shortcomingsof the commonly used method of sag characterization:the lowest rms value as sag magnitudeand thenumberof cycles below thethresholdas the sag duration. No reliableinformationhas been published a boutthe numberof sags with a large non-rectangularpart. It is mentionedin [156] that about 100/0 of sags in the U.S. distribution systems arenon-rectangular.Another indication that this effect is not very severe is the factthat the duration of most sagscorrespondsto typical faultclearing times in the system. 8.2.2 The Sag Density Table The scatterdiagramis very useful to give aqualitativeimpressionof the supply performance,but for aquantitativeassessment otherways ofpresentationare needed. A straightforwardway of quantifying the number of sags isthrough a table with magnitudeand duration ranges. This is done in Table 6.3 for data obtainedfrom a large powerquality survey[20]. Each element in the table gives the numberof events with magnitudeand duration within a certain range; e.g., magnitudebetween 40 and 50% and durationbetween400 and 600 ms. Each element gives the density of sags in that magnitudeand durationrange; hence the term "sagdensitytable" or "sagdensity function." A combinationof magnituderange anddurationrange is called a"magnitude-durationbin." The sag density function is typically presented as a bar chart. This is done in Fig. 6.6 for the data shown in Table 6.1. The length of each barproportional is to the numberof sags in thecorrespondingrange. From the barchart it is easier to get an impressionof the distribution of the sagcharacteristics,but for numerical values the 6.6 that the majority of sags has a table is more useful. In this case we see from Fig. magnitudeabove800/0 and adurationless than200ms. There is also caoncentrationof short interruptionswith durationsof 800 ms and over. duration ranges. In In Fig. 6.6 all magnituderanges areof equal size, so are all most cases the ranges will be of different size. There are moreofsags shortdurationand high magnitudethan sags elsewhere in the magnitude-durationplane. Therefore,the resolution is chosen higher forshorter duration sags and for shallow sags. Several examples of the density function in bar-chartform are shown in Section 6.3. TABLE 6.3 Exampleof SagDensity Table: Numberof Sags per Year Magnitude 0-200 ms 200-400ms 400-600ms 600-800ms > 800 ms 80-90% 70-80°./c, 60-70% 50-600/0 40-50% 30-40% 20-30% 10-20°./c, 0-10% 18.0 7.7 3.9 2.3 l,4 1.0 0.4 0.4 1.0 2.8 0.7 0.6 0.4 0.2 0.2 0.1 0.1 0.3 1.2 0.4 0.2 0.1 0.1 0.1 0.1 0.1 0.1 0.5 0.2 0.1 0.1 0.1 0.0 0.0 0.0 0.0 2.1 0.5 0.2 0.1 0.1 0.1 0.0 0.1 2.1 Source: Data obtainedfrom [20]. Section 6.2 • Presentationof Results : Voltage Sag C oordinationChart 331 18 16 14 ~ ..,...c, ;>.. 12 '" 10 bIl ....1J! 0 ..,... 8 § 6 .c Z 4 2 0 > 0.8s Figure 6.6 Two-dimensional bar chart of the sag density function shown in Table 6.3. 8.2.3 The Cumulative Table Of interest to thecustomeris not so much thenumberof voltage sags in a given magnitudeand duration range, but the number of times that a certainpiece of equipnumberof sags worse ment will trip due to a sag.It therefore makes sense to show the than a givenmagnitudeand duration. For this a so-called"cumulative sag table" is calculated. ElementM D of the cumulativesag table is defined as follows: (6.2) withfmd elementmd of the density table : the numberof sags in thedurationranged and the magnituderangem; and with FMD elementMD of the cumulativetable: thenumber of sags withdurationlonger thanD and magnitudelessthan M. Durationsare summed from the value upward because a longer sag is more severe; magnitudesare summed from the value down to zero because a lower magnitudeindicates a more severe sag. This is a direct consequence of the definition of sagmagnitude,where a higher magnitude indicates a less severe event. The cumulative tableobtainedfrom the density table inTable 6.3 is shown in Table 6.4. The table shows, e.g., that the rms voltage drops below 60% for longer than 200 ms, on average 4.5 times per year. If the equipmentcan only tolerate a sag 332 Chapter6 • VoltageSags-Stochastic Assessment TABLE 6.4 Example ofCumulativeSagTable, Numberof Sags per Year Magnitude 0 90% 80% 70% 60% 50% 40% 30% 20% 10% 49.9 25.4 15.8 10.9 8.0 6.2 4.9 4.2 3.5 200ms 13.9 7.4 5.5 4.5 3.8 3.4 3.1 2.8 2.5 400 ms 600 ms 8.4 4.7 3.6 3.1 2.9 2.7 2.6 2.4 2.2 6.1 3.6 2.9 2.6 2.5 2.3 2.3 2.2 2.1 800 ms 5.2 3.1 2.6 2.4 2.3 2.3 2.2 2.2 2.1 Source: Data obtainedfrom Table 6.3. below 60% for 200 ms, it will trip on average 4.5 times per year. From such a table the number ofequipmenttrips per year can be obtainedalmost directly. 6.2.4 The Voltage Sag Coordination Chart Table 6.4 is shown as a bar chart in Fig. 6.7. The values in the cumulative table belong to acontinuousmonotonefunction: the values increase toward the left-rear cornerin Fig. 6.7. The values shown Table6.4 in can thus be seen as a two-dimensional function of numberof sags versusmagnitudeand duration. Mathematicallyspeaking, 50 45 40 ~ 35 &30 ~ 25 ~ 20 ~ 15 '" 'o ~fJ.ril~~~~~ 90% ~~ 80% 70% 60% .0 10 50% 40% 30% . ,&0(, <$''bo~" llc e.,'bo 5 o Figure 6.7 Barchart of the cumulativevoltage sag table shown in Table 6.4. 333 Section 6.2 • Presentationof Results: Voltage Sag CoordinationChart 25 ~~-----l~"-'£'-+-------:~~-----t-------;- 80% J-,C--~rJ----+---7"G.-_---+-----+-------t-70% a--.,t;-----~------+-----+-------t-60% 4) ] J----~t.--_+_------+-----+_----___t_ 50% .~ 8 ~-~---+-------+-----+-------t-40% l 5 sags/year I - - - - - - - + - - - - - - - - + - - - - - - f - - - - - - - - t - 20% 1--------+-------+------+------.....-,- 10% 0.6 s 0.8 s Os 0.2 s 0.4 s Sag duration 6.4. Figure 6.8 Contourchart of the cumulativesag function, based on Table this function is defined for the whole magnitude-durationplane. Whenobtainedfrom power quality monitoring the function is not continuous.Stochasticpredictiontechniques will normally also not lead to acontinuousfunction. Whether the function is continuousor not, acommonway of presentinga two-dimensionalfunction isthrough a contour chart. This was done byConrad for the two-dimensionalcumulative sag function, resulting in Fig. 6.8[20]. The contourchartis recommendedas a"voltagesagcoordinationchart" in IEEE Standard493 [21] and in IEEE Standard1346[22]. In a voltage sagcoordinationchart thecontourchartof the supply iscombinedwith the equipmentvoltage-tolerancecurve reproduced to estimate thenumberof times theequipmentwill trip. Figure 6.8 has been in Fig. 6.9 including twoequipmentvoltage-tolerancecurves. Both curves are rectangular; i.e., theequipmenttrips when the voltage drops below certain a voltage for longer than a givenduration. Device A trips when the voltagedrops below 65% of number nominal for longer than200 ms. According to the definition given before, the of voltage sags below65% for longer than 200 ms is equal to the element of the cumulative table for 65%, 200 ms. The values in the cumulative sag table are the underlying function of the contour chart in Figs. 6.8 and 6.9. In short, the number of spurioustrips is equal to thefunction value at the kneeof the voltage-tolerance curve,indicatedas a circle in Fig. 6.9.F or device A thispoint is located exactly on the For device B, the five sags per year contour.Thus, device A will trip five times per year. knee is located between the 15 and 20 sags per yearcontours.Now we use the knowledgethat the underlyingfunction is continuousand monotone.The numberof trips will thus be between15 and 20 per year; usinginterpolationgives anestimatedvalue of 16 trips per year. For a non-rectangularequipmentvoltage-tolerancecurve, as shown in Fig. 6.10, the procedurebecomessomewhatmore complicated.Considerthis device as consisting of two components,each with arectangular.voltage-tolerancecurve. • ComponentA trips when the voltagedropsbelow 50% for longerthan 100ms; accordingto the contourchart this happenssix times per year. 334 Chapter6 • VoltageSags-Stochastic Assessment 17"~"7""""':::r-::;lI..-,.-,..,r----~-~-------r------__ 90% ..,.llIIIIIIf----..,......... DeviceB .....-----_r80% 25 r-:7'--.... -~-- 20 t7----t'7l'----tr-.--.."e-----+------4-------I-70% 15 DeviceA 10 60% ~ t----t----:r---tr-.--------+------+-------4-50% .~ 8 ~ t--""7'"t----t-------+-------+-------I-40% U) 5 t-----t-----Ir.--------+------+------4- 30% t----t----tr-.--------+------+-------I- 20% t-----t----1I----------+------f-------+. 100/0 0.2 s 0.68 0.48 08 0.88 Sag duration Figure 6.9 Voltage sag coordinationchart, reproducedfrom Fig. 6.8, with two equipmentvoltage-tolerancecurves. ~.....,.._~7"_::l~--,.,r-----~---y------~-----~ 90% B ........,.:....----~..-------+------+------~60% -8 a r---:-i==:::;~~~-------t------;-------;- 50% .~ 10 40% J---....,.r..t-----4I---------f.-------t------_+_ 51o------II-------4I---------f.-------t--------t- e tf en 30% J------tl------II---------+-------+--------t- 20% t------tI...------I'-------4-------+----------- 10% 0.28 0.6s 0.4 s 0.88 Os Sag duration Figure 6.10 Voltage sag coordinationchart, reproducedfrom Fig. 6.8, with nonrectangularequipmentvoltage-tolerancecurve. • ComponentB trips when the voltagedropsbelow 85% for longerthan200 ms, which happens12 times per year. Adding these twonumbers(6 + 12 = 18) would count double those voltage sags for which both componentstrip. Both componentstrip when thevoltagedropsbelow 50% for longer than 200 ms;aboutfour times per year. Thiscorrespondsto point C in the chart. The numberof equipmenttrips is thus equal to FA + En - Fe = 6 + 12- 4 = 14 (6.3) Section 6.2 • Presentationof Results : Voltage SagC oordination Chart 335 Note that assuming arectangularequipmentvoltage-tolerancecurve (100 rns, 85%) would have resulted in the incorrect value of 20 trips per year. By using thisprocedure,the voltage sagcoordinationchartprovidesfor a simple and straightforwardmethodto predict thenumberof equipmenttrips. 8.2.5 Example of the Use of the Voltage Sag Coordination Chart The dataobtainedfrom a large survey [68] has been usedplot to the sag density quality of the voltage at the bar chart shown in Fig. 6.11. The survey measured the terminals of low-voltageequipment(at the wall outlet) at many sites across the United States andCanada. Figure 6.11 can thus be interpretedas the average voltage quality experienced by low-voltage equipment. From Fig. 6.11, a voltage sag coordinationcharthas beenobtained,shown in Fig. indicatedby the points A, B, C, and D. 6.12. Four equipmentvoltage tolerances are The meaningof these will be explained next. Supposethat a computermanufacturerconsiders differentoptionsfor the power supply of personalcomputers. The choice is between two different de/deconverters, with minimum operatingvoltages of 100V and 78 V, and between two capacitorsizes, leading to 5% and 1% de voltage ripple. Using (5.6) we can calculate the voltage toleranceof the four designoptions. For a minimum operatingvoltage of 100V and a de voltage rippleof 5% we find a voltage tolerance of 84% (100 V) and 1.5 cycles, etc. The results are shown in column 4 of Table 6.5. The voltage tolerancefor the four options(A , B, C, and D) is indicated by the four dots in Fig. 6.12. From this voltage sag 70 60 [ .,... 50 Co '" 40 .,...o 30 OIl ~ e- .r> e z'" 20 10 6-10 c 20 c0.5s Sag duration Figure 6.11 Sag density for the average low-voltage supply in the United Statesand Canada. (Data obtainedfrom Dorr [681.) 336 Chapter6 • VoltageSags-Stochastic Assessment TABLE 6.5 Comparisonof Four Design Optionsfor the PowerSupplyof a PersonalC omputer Option Minimum Operating Voltage A de Ripple 5% 1% IOOV IOOV 78 V 78 V B C D Voltage Tolerance EstimatedTrip Frequency 84%, 1.5 cycles 84°tlo, 8 cycles 65%, 3 cycles 650/0, 15 cycles 5°tlo 10/0 10 sagsperyear A ~ t:::::::; -- r-'WB V..-- -::::: ~~ ~ 60 V 90 ......... ::-- 10- 40 30 /--- ~ -- -------/ - ~ ~ ~ .--/ --- ~ ~ I-' .."I ~ II J I..- / -~ f.-- 104V lOOV > .8 90V ] 78V /D :l (5 96V 84V J C~ 20 - ) l-/V ) IOO/year 50/year 25/year 20/year 'f f (/) , 60V 10V 1 c 2 c 3 c 4 c 5 c 6 c 10 c 20 c 0.5 sis 2 s 5 s lOs 30 s 60 s 120 s Sag duration in cycles (c) and seconds (s) Figure 6.12 Voltage sag c oordinationchart for the averagelow-voltagesupplyin the United Statesand Canada.(Obtainedfrom the sagdensitychart in Fig. 6.11.) coordination chart the trip frequency can easily be estimated,resulting in the last column of Table 6.5. 8.2.8 Non-Rectangular Sags Characterizingvoltage sagsthrough their magnitudeand duration assumes a static load, a static system, and no changes in the fault. In reality both the load and the system are dynamic and the fault can develop, e.g., from a single-phase to.. a three phase fault.Simulationsand measurements have shownthat inductionmotor load can lead to longpost-faultvoltage sags. A few examples of non-rectangularvoltage sags were shown inChapter4: Figs. 4.47,4.48,and 4.130. There are two ways o f presentingnon-rectangularsags intwo-dimensionalcharts like Figs. 6.8 and 6.12. 1. Define themagnitudeas the minimum rms voltage during the disturbance and thedurationas the timeduring which the rms voltage is below a thresh .. old, typically 90% of nominal voltage. Thismethodis used in most power quality monitors. The consequenceof this is that non-rectangularsags are characterizedas more severe t han they actually are. Alternativesare to use the average or the rms of the one-cycle rms values latter (the is a measure of the energy remainingduring the sag). 337 Section 6.2 • Presentationof Results: Voltage Sag C oordinationChart 2. Characterizethe voltagequality by the numberof times the voltage drops below a given value for longer thana given time. This again results ingraph a like Fig. 6.8, but nowwithout the need tocharacterizesags individually. Such a methodwas firstproposedin [17] and used in [18],andbecamepartof IEEE Std. 493 [21]. A similarmethodis proposedin [156] for inclusion incontracts between utility andcustomers.The argumentfor the latter proposalbeing that utilities shouldnot be overlypunishedfor non-rectangularsags. To explain the secondmethod,the cumulativetable will be introducedin a different way. We define each element ascountercountingthe a numberof sags worsethan the magnitudeand duration belonging to this element. Each sag that occurs increases the value ofpartof the elements by one. The elements whose value is increased are those for which the sag is more severe thanthe element. Inotherwords, those elements less severe than the sag; in the table, the elements above the sag. This is shown in Fig. 6.13 for a rectangularsag. o f points correspondingto the cumulativesag Figure 6.14 again shows the grid function. But this time anon-rectangularsag is shown. Theprocedureis exactly the "The function valueshouldbe increasedby one for all points above the same as before: sag." ® ® ® X X X X ® ® ® X X X X Q9 ® ® X X X X X X X X X X X X X X X X X X X X X X X X X Figure 6.13 Updateof cumulativetable for rectangularsag. Figure 6.14 Updateof cumulativetable for non-rectangularsag. Duration ® ® ® ® ® Ix X ® ® ® X X X X ® ® ® X X X X ® ® X X X X X ® ® X X X X X X X X X X X X Duration 338 Chapter6 • VoltageSags-Stochastic Assessment Using this methodit is possible toquantify the quality of the supply including non-rectangularsags. But thismethodcannotbe used tocharacterizeindividual sags. Note that this is oftennot a seriousconcernwhen one isinterestedin merelyquantifying the supply performance. Some sags will still escape quantification,as shown in Fig. 6.15. A possible choice here is tomeasurethe time the sag is in each magnituderange in the table, and then increase thepoints to the left of the table inthat magnituderange. This would lead to an equivalentsag asindicatedin Fig. 6.15. Themethodproposedin [156] treatsthese "very non-rectangularsags" in a similar way. To understandthe limitation of the method in Figs. 6.13, 6.14, and 6.15 the term " rectangularvoltage-tolerancecurve" is introduced. A piece of equipmenthas a rectangularvoltage-tolerancecurve if its tripping is determinedby one magnitude and one duration. Thus, the equipment trips when thevoltage drops below a certain magnitudefor longer than a certain duration. The actual shapeof the rms voltage versus time has no influence on the equipmentbehavior. Examplesof such equipmentare undervoltagerelays (e.g., used to protect induction motors) and mostnon-controlledrectifiers. Alsocomputersand otherconsumerelectronicsequipmentfit in this category. Manyadjustable-speed drives trip due to anundervoltage-timerelay at the dc bus or on the ac terminals. Also those can beconsideredas having a rectangularvoltage-tolerancecurve. For equipmentwith a rectangularvoltage-tolerancecurve this method directly gives the expectednumber of spurious trips. For non-rectangularvoltage-tolerance curves themethod no longer works.That might appeara seriousdisadvantageuntil one realizesthat a non-rectangularvoltage-tolerancecurve will normally be obtained for rectangularsags.Applying it directly to non-rectangularsags isproneto uncertainties anyway, nomatter which definition of magnitudeand duration is used. When assessing the influence of non-rectangularsags on a piece ofequipmentit is recommended to use a r ectangularapproximationof the voltage-tolerancecurve unless more detailedinformation on its behaviorundernon-rectangularsags is available. Q9 @ @ @ @ @I X Q9 @ Q9 @ X X X Q9 ® @ ® X X X @ X X X X X X X X X X X X X X X X X X @ X - Duration Figure 6.15 Problemsin updatingthe cumulativetable for a verynon-rectangular sag. 8.2.7 Other Sag Characteristics In the previouspart of this section, we onlyconsideredmagnitudeand durationof o ther the sags. We sawbefore that the equipmentbehaviormay also be affected by characteristics:phase-anglejump, three-phaseunbalance,point-on-waveof sag initiation. Below, somesuggestionsare given for thepresentationof the results when these 339 Section 6.2 • Presentationof Results: Voltage Sag C oordinationChart additional characteristics need to be incorporated.Note that, unlike magnitude and duration, no monitoring data are available on phase-angle jump, three-phase unbalance, and point-on-wave of sag initiation. This makes that some of the suggestions remainrather theoretical, without the chance to apply them to actual data. 6.2.7.1 Three-Phase Unbalance. We saw in Section 4.4 that three-phase unbalanced sags come in a number of types. The fundamental types were referred to as A, C, and D. The concept of voltage sag coordinationchart can be extended to three-phase unbalance by creating one chart for each type, as shown in Fig. 6.16. A contour chart is created for the number of sags more severe than a given magnitude and duration, for each type. Also the equipment voltage-tolerance curve is obtained for each type. In exactly the same way as before, the number of equipment trips can be found for each type ; in this example:N A , Nc, and ND' The total number of equipment trips N is the sum of these three values: (6.4) The method can be extended toward other types. The main problem remains to obtain the type of sag frommonitoringdata. A technique for this has been proposed in [203], [204] which requires the sampled waveforms. 6.2.7.2 Phase-Angle Jumps.Including phase-angle jumps in the compatibility assessment for single-phase equipment creates a three-dimensional problem. The three dimensions are magnitude, duration, and phase -anglejump. Next to this there are twoadditionalcomplications: Type A Duration _.. Tn'~~ Duration ._. _....!~e _~. "_ . Figure 6.16 Useof the voltagesag coordinationchart when three-phase unbalanceneeds to beconsidered. Duration . .__..._.. 340 Chapter6 • Voltage Sags -StochasticAssessment • Phase-anglejumps can beboth positive and negative, with the majority of values likely to be foundaroundzero phase-angle j ump. Using a cumulative function requires thesplitting up of the three-dimensionalspace in two halfspaces: one for positive phase-anglejump, one for negativephase-anglejump. Note that equipmentbehaviormay be completelydifferent for positive and for negative phase-angle jump. • An increasingphase-anglejump (in absolutevalue) not necessarily leads to a more severe event for the equipment.With both magnitudeand durationit was possible to indicate adirection in which the event becomes more severe (decreasingmagnitudeand increasingduration). For phase-anglejumps this is not possible. Especially thelatter complicationmakes athree-dimensionalversion of the voltage sag coordinationchartnot feasible. A possible solutionis to split thephase-angle j ump axis in a numberof ranges, e.g.,[-60°, - 30°], [-30°, - 10°], [_10°, + 10°], [+10°, + 30°], [+30 °, + 60°]. For each range then umberof equipmenttrips isdeterminedlike before. The total numberof equipmenttrips is the sum of the values obtainedfor each rangeof phase-angle j ump. A plot of magnitudeversusphase-angle j ump for single-phaseequipment was shown in Fig. 4.108. Splitting the phase-anglejump axis in a number of ranges showsthat not all charts will contain the whole rangeof magnitudevalues. Only in the rangearound zero phase-anglejump do we expectmagnitudevalues between zero and100%. The range[+30 °, + 60°] may only contain magnitudevalues around 50% of nominal. An alternativeis to split the duration axis in a numberof ranges. In astochasticprediction study this could correspondto the typical faultclearing time in differentparts of the system, e.g., atdifferent voltage levels.For eachduration range, a plot ofmagnitudeversusphase-anglejump results, similar to the oneplotted in Fig. 4.108. Within this plot, anequipmentvoltage-tolerancecurve can be drawn . Ahypotheticalexample is shown in Fig. 6.17. Note that this curve has a different shape than the voltage-tolerancecurve in themagnitude-durationplane.Note further that it is no longer possible to use cumulativefunction a for the number of events like in the voltage sag coordinationchart. Insteada density function must be used, and thenumberof eventsoutsideof the voltage-tolerancecurve added. For three-phaseequipmentthe problem becomes slightly less complicated.Using characteristicmagnitudeand phase-anglejump results in negative phase -angle jump values only. But a larger (negative) phase-anglejump could still be a less severe event for the equipment.Presentingequipmentand supplyperformancestill requiressplitting up thephase-anglejump axis or thedurationaxis. Trip No trip 0. .[ ll) 1ib 0° t - - - - - --+-- ~ ll) - - - - <:f)--Magnitude ;{l ..c c.. Figure 6.17Hypotheticalexample of the voltage-tolerance curve for magnitudeagainst phase-anglejump. The sagdurationis consideredconstant. 341 Section 6.2 • Presentationof Results: Voltage Sag C oordinationChart 6.2.7.3 Point-on-Wave. Point-on-wavecharacteristicsmay be easier to include in the compatibility assessmentthan phase-anglejumps, because thepoint-on-wave of sag initiation is likely to be independento f the other characteristics.F or here we will assumethat this is the case. Analysis o f monitoring data is needed to check this assumption. As the point-on-waveof saginitiation is independentof the sagmagnitudeand duration, there is no need for athree-dimensionaltreatment.Next to the standard contourchart of magnitudeversusduration,a one-dimensionalp lot is needed for the point-on-wave.A hypotheticalexample is shown in Fig. 6.18. Note that only values 0 are shown;o thervalues can betranslatedinto a value in this range. between zero and 90 For a number of values avoltage-tolerancecurve needs to beobtained and plotted in the standardvoltage sagcoordinationchart; see Fig. 6.19. The resulting number of equipmenttrips N; from each voltage-tolerancecurve is weightedby the fraction of sags~; with a point-on-wavevalue equal toi, and addedto get thetotal numberof equipmenttrips N: (6.5) In the example shown in Figs. 6.18 and 6.19, this total numberof equipmenttrips is obtainedfrom N = ~oNo + ~30N30 + ~6oN60 + ~90N90 Figure 6.18Hypotheticalexample of the fraction of sags with a given point-on-wave value. 30° 60° 90° Point-on-wave 0° No ~ N 30 30° N60 60° N90 Figure 6.19Hypotheticalexample of the voltage-tolerancecurves for differentpointon-wave of saginitiation. (6.6) Duration 90° 342 Chapter6 • VoltageSags-Stochastic Assessment 6.3 POWER QUALITY MONITORING A common way of obtaining an estimatefor the performanceof the supply is by recording the disturbanceevents. For interruptionsof the supply this can be done manuallyas describedin Chapter2. For voltage sags andother short-durationevents an automaticrecording method is needed. A so-called power quality monitor is an appropriatetool for that, although modern protective relays canperform the same function. Powerquality monitors come in various types and for a range of prices. A further discussionabout them isbeyondthe scope of this book. For each event themonitor recordsa magnitudeand aduration plus possibly a few othercharacteristicsand often also acertainnumberof samplesof raw data: time domainas well as rms values. This could result in enormousamountof an data,but in the end onlymagnitudeand durationof individual events are used for quantifying the performanceof the supply. Two typesof power quality monitoring need to bedistinguished: • monitoringthe supplyat a (large)numberof positionsat the same time, aimed at estimatingan "averagepower quality": a so-called powerquality survey. • monitoringthe supplyat one site, aimed at estimatingthe powerquality at that specific site. Both will be discussed inmore detail below. 8.3.1 Power Qualltv Survey. Large power quality surveys have been performedin severalcountries.Typically ten to ahundredmonitorsare installedat one or two voltage levels spread over a whole country or the serviceterritory of a utility. Because not allsubstationsand feeders can bemonitored,a selection has to be made. The selection shouldbe suchthat the average power quality, as measured,is also representativefor the substationsand feedersnot monitored.Making such a fullyrepresentativechoice is very difficult ifnot impossible. different from a sag Sites come indifferent types,but it is hard to decide which sites are viewpoint without first doing the survey. Afurther analysis ofdata from the current generationof surveys will teach us more about the differences between sites. This knowledge can be used for choosingsites infuture surveys. Some aspectsof power quality surveys and the way in which the data can be processed,are discussed below by using datafrom four surveys: • The CEA survey.A three-yearsurvey performedby the CanadianElectrical Association (CEA). A total of 550 sites wasmonitored for 25 days each. Residential,commercial, and industrial sites weremonitored at their 120V or 347 V serviceentrancepanels.Approximately10% of the sites had metering on primary side of the servicetransformerto provide an indication of the power quality characteristicsof the utility's distribution system[54], [65], [66]. • The NPL survey. A five-year surveyperformedby NationalPowerLaboratory (NPL). At 130 siteswithin the continentalUS and Canada,single-phase lineto-neutral data were connectedat the standardwall receptacle. The survey resulted in atotal of 1200monitor monthsof data[54], [68], [69]. • The EPRIsurvey. A survey performedby the Electric Power Research Institute (EPRI) between June 1993 and September1995. Monitoring took place in 343 Section 6.3 • PowerQuality Monitoring distribution substationsand on distribution feeders at voltages from 4.16 to 34.5 kV. Monitoring at 277 sites resulted in 5691 monitor monthsof data. In mostcases threemonitorswere installed for each randomlyselected feeder: one at thesubstationand two atrandomlyselected places along the feeder [54], [70]. • The EFI survey. The Norwegian Electric Power ResearchInstitute (EFI, recently renamed"SINTEF Energy Research")has measuredvoltage sags and other voltage disturbancesat over 400 sites in Norway. The majority (379) of the sites were at low-voltage (230 and 400V), 39 of them were at [67]. distribution voltages, and the rest at various voltage levels The resultsof these surveys will be presented and discussed in the following paperscited. paragraphs.For more details about the surveys refer to the various These are by far the only surveys, but they were the ones for which detailed results were available. With the exceptionof the EFI survey all the resultspresentedbelow werepublishedin the internationalliterature.Especially the paper by Dorr [54] contains very usefulinformation. The amountof results published, even in reports,is still very limited. There must still be gigabytesof very interestingmonitoring data stored at utilities all over the world, waiting to be processed.numberof A observationscan be made from thevarious surveys, someof which are mentionedbelow. To explain or check all this,further analysis of thedatais needed. 6.3.1.1 MagnitudeVersus Duration: CEA Survey. The cumulative number of 6.7 for sags per year, as o btainedfrom the CEA survey is shown in Tables 6.6 and primary as well assecondaryside of the servicetransformer.Bar charts of the sag density function are shown in Figs. 6.20 and 6.22. A voltage sag coordinationchart for the secondaryside datais shown in Fig. 6.21. TABLE 6.6 CumulativeVoltage Sag Table for CEA SecondarySide Data: Numberof Sags perYear Duration Magnitude I cycle 6 cycles 10 cycles 20 cycles 0.5 sec 1 sec 90% 80% 70% 500/0 10% 98.0 19.2 14.4 10.5 6.5 84.0 9.2 5.7 3.5 2.8 84.0 9.2 5.7 3.5 2.8 67.3 5.5 4.4 3.2 2.8 63.8 5.0 4.2 3.2 2.8 35.8 3.2 3.1 2.8 2.6 2 sec 6.6 2.3 2.3 2.2 2.1 Source: Data obtainedfrom Dorr et al. [54]. TABLE 6.7 CumulativeVoltage Sag Table for CEA Primary Side Data: Numberof Sags perYear Duration Magnitude I cycle 6 cycles 10 cycles 20 cycles 90% 80% 20.3 12.0 9.4 4.8 3.1 11.2 5.8 3.6 1.2 1.2 10.8 5.4 3.3 1.2 1.2 5.5 3.2 2.0 1.1 1.1 700~ 500/0 10% Source: Data obtainedfrom Dorr et al. [54]. 0.5 sec 5.2 3.1 1.9 1.1 1.1 I sec 1.9 0.9 0.7 0.7 0.7 2 sec 1.3 0.7 0.7 0.7 0.7 344 Chapter6 • Voltage Sags -StochasticAssessment 30.0 25.0 :a ...;"., "e, 20.0 .....0~ 15.0 '" OJ) ... '" 1 10.0 Z 5.0 .,J§' 10-50% ~'Ir~ 50-70% 0-10% Duration in seconds Figure 6.20 Sagdensityfunction for CEA secondaryside data,correspondingto Table 6.6. 80 --- ::::--::: ~ :::::::::: I----- 50 20 10 sags/year /'i/ Wi 80% / / 90% 70% t ~ 50% 17 ms lOOms 167 ms 333 ms 0.5 s Duration I s 2s 10% 10 s Figure 6.21 Voltage sag coordinationchart for CEA secondaryside data, correspondingto Table 6.6. We seethat the numberof sags onsecondaryside is significantly highert han the numberof sags onprimary side.Partof the secondaryside sagsoriginatesat secondary side, i.e., within thecustomerpremises. The largenumber of long shallow sags at secondaryside can be explained as motor starting on secondaryside. As we saw in Section 4.9, these sags are not noticeable(i.e., magnitudeabove90%) on primary side of the transformer. Section 6.3 • PowerQuality Monitoring 345 30 25 5 o Duration in seconds Figure 6.22 Sag dens ity of primary side CEA data,correspondingto Table 6.7. Anotherinterestingobservationis the largenumberof deepshortsags (0-100 ms, 0-50%). The numberis less onsecondaryside, but still significant. Acomparisonwith othersurveys showsthat this is a typical feature of the C EA survey.Furtheranalysisof the data is needed to explain this. With any interpretationof the CEA primary side data one should also consider the uncertaintyin the results. Asmentionedabove, about 10% of the 550 sites was located onprimary side of adistribution transformer. As each site wasmonitoredfor only 25 days, this resulted in only 3.7 monitoring-yearsof data.The uncertaintyin sag of two for each of the bins in the sag density table . In the frequency is at least a factor CEA secondarysidedatathe uncertaintyis smaller as theamountof datais equivalent to 38 monitor years. 6.3.1.2 MagnitudeVersus Duration: NPL Survey. The number of sags per year, asobtainedfrom the NPL survey, is shown incumulative form in Tables 6.8 and 6.9. Table 6.8 shows the original data, where eachindividual event iscounted, even if they are due to the same reclosure cycle. In Table 6.9 5-minute a filter is applied: all events within 5 minutes are countedas one event: the one with the worst magnitudebeing the onecounted.The sag densities are shown in Figs. 6.23 and 6.24 without and with filter, respectively. A voltage sag coordinationchart for the filtered data is shown in Fig. 6.25. ComparingFigs. 6.23 and 6.24, we see that there is somereductionin the number of shortinterruptions(voltage below 10%) as alreadydiscussed inChapter3. The most serious reduction is the number of long, shallow sags, the ones attributed to load switching. Apparentlyload switching sags come in clusters , with on average about 15 events within 5 minutes. This clearly distortsthe quality of supply picture asdrawn by 346 Chapter 6 • Voltage Sags-Stochast ic Assessment TABLE 6.8 Cumul ative Voltage Sag Table for NPL Data Without Filter: Numberof Sags per Yea r Duration Magnitude 1 cycle 6 cycles 351.0 59.5 31.4 20.9 15.5 259.8 32.3 23.2 18.3 15.2 87% 80% 70% 50% 10% 10 cycles 20 cycles 0.5 sec 157.9 19.0 17.1 15.4 14.1 134.0 16.2 15.2 14.1 13.2 211.9 23.7 19.4 16.8 14.9 I sec 2 sec 10 sec 108.2 13.1 12.7 12.2 11.8 90.3 10.4 10.3 10.2 9.9 13.7 5.8 5.8 5.8 5.7 Source :Data obtained from Dorr et al. [54). TABLE 6.9 CumulativeVoltage SagTable for NPL Data with 5-minute Filter : Numberof Sags per Year Duration Magnitude I cycle 6 cycles 126.4 44.8 23.1 15.9 12.2 56.8 23.7 17.3 14.1 12.0 87% 80% 70% 50% 10% 10 cycles 36.4 17.0 14.5 12.9 11.7 20 cycles 0.5 sec 27.0 13.9 12.8 11.8 11.0 23.0 12.2 11.5 10.6 10.2 2 sec I sec 18.1 10.0 9.7 9.4 9.0 14.5 8.0 7.9 7.8 7.5 Source:Data obtained from Dorr et al. [54). 80 70 ... "'" ...>- 60 '0." 50 ....0~ 40 '" l> e 30 :s Z 20 10 50-70% ..,s>"O'lJ 10-50% 0-10% o f NPL data,no filter, corresponding to Table 6.8. FIgure 6.23 Sag density ~'!1q 10 sec 5.2 4.3 4.3 4.3 4.2 Secti on 6.3 • PowerQuality Monitoring 347 80 70 Ii! ., >. .,... Co ., 60 50 bO ., '" ... '0 ~ ~ Z 40 30 20 10 o f NPL data, 5-minute filter, correspondingto Table 6.9. Figure 6.24 Sag dens ity 20 10 sags/year F-."""""'=-r"""t--,,...,:==-t----j----+-----ji"""""---t----'-----'---j 80% f--.,-:==-t--- - f - - - - + -- -+----f-1f-- - - + - - - - j 70% 1 ~ ::8 f - - - - f - - - - f - - - - +---+--+--1f----+- - - - j 50% L-_ 17 ms _ --! 100 ms --'- 167 ms -1- ...e..-.'--_ 333 ms 0.5 s Duration _ !--_ _-+ 1s 2s -' 10% 10 s Figure 6.25 NPL data: voltage sagcoordination chart, 5-minute filter, corresponding to Table 6.9. the survey.F urtherinvestigation of the datais needed to find out whether most starting events areclusteredor whetherit is all due to a smallnumberof sites. Acomparison between theNPL dataand the CEAdatashows a much larger numberof events for the former . The most likelyexplanationis the much lower lightning activity inCanadaas comparedto the United States . 348 Chapter6 • VoltageSags-Stochastic Assessmen1 6.3.1.3 MagnitudeVersusDuration: EPRI Survey. The cumulative number of and 6.11. sags per year, as o btainedfrom the EPRI survey, is shown in Tables 6.10 Table 6.11 gives the results forsubstations,while Table 6.10 isobtainedfrom measurementsalong feeders.For both tables a5-minutefilter was applied. The sag density function is shown in Figs. 6.26 and 6.28.Figures 6.27 and 6.29 give the correspondingvoltagesagcoordinationcharts. The differences between the feeder dataand thesubstationdataare small: in total only seven events per year, whichabout is 10% (this is the value in theupper-leftcorner magnitude-duraof the tables).The seven-eventdifference is found in two areas in the tion plane: • Eventsup to 10 cycles withmagnitudesbelow 700/0. Here we find 13.6 events for the feeders,b ut only 8.3 for thesubstation. substation,5.1 for the • Interruptionsof 1 second and longer: 3.4 events for the feeder. Where thetotal numberof events isremarkablysimilar, the relative difference in the numberof severe events is significant. Table6.12comparesthe numberof events below certain voltage levels, including events recordedat low voltage (NPL survey). Only events with aduration lessthan 20 cycles(about 300ms)are 'included in thecomparison: i.e.mainly events due toshort circuits. Looking at Table 6.12 we see moreinter.. ruptions and deep sags on the feeder comparedto as the substation.The increased TABLE 6.10 CumulativeVoltage Sag Table for EPRI FeederData with 5-minute Filter: Numberof Sags perYear Duration Magnitude I cycle 6 cycles 10 cycles 90% 80% 70% 50% 10% 77.7 36.3 23.9 14.6 8.1 31.2 17.4 13.1 9.5 6.5 19.7 12.4 10.3 8.4 6.4 20 cycles 13.5 9.3 8.3 7.5 6.2 I sec 2 sec 10 sec 7.4 6.4 6.2 5.9 5.1 5.4 4.9 4.8 4.6 4.0 1.8 1.7 1.7 1.7 1.7 0.5 sec I sec 2 sec 10 sec 8.6 5.6 4.9 4.4 3.9 5.4 4.3 4.0 3.8 3.4 3.7 3.2 3.0 2.9 2.5 1.5 1.4 1.4 1.4 1.4 0.5 sec 10.7 7.9 7.2 6.6 5.6 Source: Data obtainedfrom Dorr et at. [54]. TABLE 6.11 CumulativeVoltage Sag Table for EPRI SubstationData with 5-minute Filter: Numberof Sagsper Year Duration Magnitude 90% 80% 70% 50% 100/0 I cycle 6 cycles 10 cycles 70.8 29.1 16.1 7.9 5.4 28.1 14.7 9.8 6.6 5.2 17.4 10.1 7.8 6.1 5.1 Source: Data obtainedfrom Dorr et al. [54]. 20 cycles 11.4 7.1 6.0 5.3 4.7 349 Section 6.3 • Power QualityMonitoring 30 25 :a ...>. 0. ., bll ., ....0 ... .&J § Q) Q) 20 ~ 15 Q) 10 Z 5 0 Figure 6.26 EPRI feeder data : sag density function , correspond ing to Table 6.10. 50 rrT"rrrTrTTTr---r- 20 10 ...,,-- - , - , - -- - - ,r-r- - 5 sags/year - ,--....::....--n------,- 90% ~"....r£"....r£'_A----r'=-+--T+------1I-----+----(t-------j - 80% f--+--A---+~--+-----I----t-----j'+---+ 70% . ~ ] ~ :::E ~--_A---+---+-----I----t--+-+---+ 50% L -_ _ 17 ms ~ 100 ms ......L 167ms -l--_ _ 333 ms ----' 0.5 s -+-L__ _--'-_ _-----l 10% 2s 1s 10 s Duration Figure 6.27 EPRI feeder da ta: voltage sag coordination chart correspond , ing to Table 6.10. numberof interruptionsis understandable : someinterruptionsonly affect part of the feeder; the closer to the equipment,the higher thenumber of interruptionssimply because the path t hat can be interrupted is longer. For the increase in thenumberof deepshort sags there is no ready explanation.Three possibleexplanations,which will probablyall somewhatcontribute, but for which more investigations are needed to give a definiteexplanationare: Chapter6 • Voltage Sags- Stochastic Assessment 350 30 25 5 50-70% o 10-50% .J'¢) ~i' 0-10% Figure 6.28 EPRI substation data : sag density function correspond , ing to Table 6.1 1. 50 20 10 5 sags/year r-r-r=-.l'~---+'~--+----+---r""---+----+----\· 80% .g a h<:=:::..--.....,f=--- - + -- - + - - - - I - + - - - - + -- - - + - - - - \·70% '§, os ~ 1----- - - + - - - + - - - + - - + -- + - -- - + - - - - + - - - - \·50% 10% 10 s ' - - - - -- - ' - -- ---+--""'' - - - - ' - - - - ' - - - - - - ' -- - - - ' - - - --'-. 17 ms 100ms 167 ms 333 ms 0.5 s Duration 1s 2s Figure 6.29 EPRI substation data : voltage sag coord ination chart,corr esponding to Table 6.11. • Reclosing actions on the feeder beyond the point where the monitor is connected. Themonitor on the feeder will record a deeper sag than the one in the substation. This would explain the deep short sags. As thedistribution transformer is often Dy-connected, deep sags due to single-phase faults will not transfer fully to low voltage. This explains the smaller numberof deep short sags measured at low voltage (NPL survey). 351 Section 6.3 • PowerQuality Monitoring TABLE 6.12 Numberof Events with aDurationLess than20 Cycles: NPL Survey (LV) andEPRI Survey (Feeder, Substation) Events per Year Distribution Voltage Range 80-900AJ 70-800/0 50-70% 10-50% 0-10% LV 68.5 20.6 6.2 2.9 1.1 Feeder Substation 37.2 11.4 8.5 5.8 1.9 37.4 12.0 7.5 1.9 0.7 Source: Data obtainedfrom Dorr et al. [54]. • The normal operatingvoltage at the feeder is lower. As the sag magnitudeis given as apercentageof the nominalvoltage, the sag willappeardeeper at the feederthan at thesubstation.Giving the sagmagnitudeas apercentageof the pre-event voltage wouldcompensatethis effect. This may explain the increase in the numberof shallow sagsalong the feeder. • Induction motor influence.Induction motorsslow down more for deeper sags and thus reduce the positive sequence voltage. reductionin A positive sequence voltage would imply areduction(also) in the lowest phase voltage and thus a reductionin sagmagnitude. Comparinglow voltage andmedium voltage data we seethat the numberof shallow sags is much higher at low voltage thanat mediumvoltage, whereas the numberof deep sags is smaller at low voltage. 6.3.1.4 MagnitudeVersus Duration: EFI Survey. The cumulative voltage sag tables, asobtained by the EFI survey, are shown in Tables 6.13 through 6.16. The sag densityfunctions are presentedin Figs. 6.30through 6.33. Table 6.13 and Fig. 6.30 give the average results for the low-voltage sites, Table 6.14 and Fig. 6.31 refer to the distribution sites. We seethat the averagedistribution site experiencessomewhatlesslonger-duration events but clearly more s hort-durationevents. The increase numberof in interruptions for lower voltage levels isconsistentwith the findings of U.S. surveys. To TABLE 6.13 CumulativeVoltage Sag Table for EFID ata, All Low-Voltage Networks: Numberof Sags per Year Duration (sec) Magnitude 90% 700/0 40% 1% 0.01 0.1 0.5 1.0 3.0 20.0 74.7 26.3 16.6 9.3 36.5 11.9 9.8 8.2 18.5 8.2 7.5 7.5 12.1 7.5 7.5 7.5 8.6 6.8 6.8 6.8 5.9 5.9 5.9 Source: Data obtainedfrom Seljeseth[67]. 6.8 352 Chapter6 • VoltageSags-Stochastic Assessment TABLE 6.14 CumulativeVoltage Sag Table for EFI Data, All Distribution Networks: Numberof Sags perYear Duration (sec) Magnitude 90% 70% 40% 1% 0.01 0.1 0.5 1.0 3.0 20.0 112.2 40.5 15.2 7.2 39.2 16.9 7.6 5.7 15.5 11.4 6.8 5.7 7.9 6.6 6.0 5.7 6.0 6.0 5.7 5.7 5.2 5.2 5.2 5.2 20.0 Source: Data obtainedfrom Seljeseth [67]. TABLE 6.15 CumulativeVoltage Sag Table for EFI Data, 950/0 Percentile for Low-Voltage Networks: Numberof Sags perYear Duration (sec) Magnitude 0.01 0.1 0.5 1.0 3.0 90% 70% 40% 10/0 315 120 128 39 25 11 47 II 11 11 20 11 11 11 11 11 11 11 11 11 11 66 25 II Source: Data obtainedfrom Seljeseth [67). TABLE 6.16 CumulativeVoltage Sag Table for EFI Data, 95% Percentile for ·Distribution Networks: Numberof Sagsper Year Duratjo~ (sec) Magnitude 0.01 0.1 90% 70% 40% 1% 388 130 45 18 159 53 21 12 0.5 1.0 3.0 20.0 57 22 12 12 20 12 12 12 12 12 12 12 12 12 12 12 Source:Data obtainedfrom Seljeseth [67]. understandall effects, one needs to understandthe propagationof sags to lower voltage levels, for which thestudy of more individual events is needed. Tables 6.15 and 6.16 give the950/0 percentile of the sagdistribution over the various sites. A stochasticdistribution function was createdfor the total numberof sagsmeasuredat one single site. The 95% percentileof this distributionwas chosen as a 5%the sites. reference site. Then umberof sags at this site is thus exceeded by only of The 95% value was suggested in Chapter1 as a way ofcharacterizingthe electromagnetic environment(the term used by thel Ee for the quality of the supply). Thus, we could say that Table 6.15 characterizesthe electromagneticenvironment for the Norwegianlow-voltagecustomer. 6.3.1.5 Variation in Time-LightningStrokes. A large fraction of the voltage sags is due tolightning strokeson overheadlines. Two phenomenaplay a role here: short circuits due to lightning strokesand triggering ofspark gaps due to lightning- Section 6.3 • PowerQuality Monitoring 353 50 45 40 .,til .. ., 0. >. 35 ., 30 OIl ., 25 ....'" ., .. 20 § 15 0 ~ Z 70-90% 10 40-70% 5 ~q 1-40% 0 ~ ,s.'/!! 's ~ e,'bo"Jo Sag duration in seconds Figure 6.30 Sagdensity for EFI low-voltagenetworks,correspondingto Table 6.13. 50 45 40 ..~ >. .,0. ., OIl ., ....0'" ..., 35 30 25 20 ~ § Z 15 70-90% 10 40-70% 5 1-40% 0 $' e,'bo"Jo Sag duration in seconds Figure 6.31 Sagdensity for EFI distribution networks.correspondingto Table 6.14. ~ .,s.'/!! ~q Chapter6 • Voltage Sags- Stochastic Assessment 354 160 140 :.... ;... .0.... .. 120 100 VI bO ....'0" VI ..... .D 80 60 E ::l Z 70-90% 40 ~ 40-70% 20 ~'tS ~~ <$' 's 1-40% 0 ~"'~ Sag duration in seconds 20-180 Figure6.32 Sag density for 95% percentile of EF I low-voltage networks, correspondingto Table6.15. 160 140 :. ... ..... ;... 120 100 0.. VI bO ....'"0 80 ~ 60 Z 40 VI .. § 70-90% 40-70% ~ 20 .s> 1-40% 0 ~~ <$' ~"'~ Sag duration in seconds 20-180 Figure 6.33 Sag density for 95% percentile of EFI distrib ution networks, corresponding to Table 6.16. 355 Section 6.3 • Power Quality Mon itoring induced overvoltages. The effect of a lightning stroke is to induce a large overvoltage on the line. If this voltage exceeds the insulation withstand level it results in a short circuit, otherwise the voltage peak will start to propagatethrough the system. If the peak voltage is not high enough to cause a flashover on the line, it might still trigger a spark gap or a (ZnO) varistor. A sparkgap mitigates the overvoltage by creating a temporaryshort circuit, which in its turn causes a.sag of one or two cycles. A varistor will only cap the overvoltage. Aconclusionfrom one of the first power quality surveys[72] was that the number of voltagetransientsdid not increase in areas with more lightning; instead the number of voltage sags increased. For a few sites in the EPRI survey, the sag frequency comparedwith was the lightning flash density[70]. This comparisonshowedthat the correlationbetween sags and lightning was much stronger than expected. Plotting the sag frequency against the 2 flash density (numbero f lightning flashes per km per year) for five sites resulted in of almost a straight line. This justifies the conclusion that lightning is the main cause voltage sags in U.S.distribution systems. As sags are correlated with lightning and lightning activity varies with time, we expect the number of sags to vary with time. This is shown in Fig. 6.34 for the NPL survey[68]. The sag frequency is at its maximum in summer, when also the lightning activity is highest. This effect has been confirmedothercountries. in Also the distribution of sagsthroughthe day follows the lightning activity, with its peak in the evening. 18 16 14 E 12 '" > ....'"0 fl'" s:: '"g e, '" 10 OJ) 8 6 - - - .- :?i;;~ f ";). 4 2 - ~ I! .., h ~ :~~ 0 ~'.!:.-" Jan '- ff41 .~~ ,....-- f-- 1- :f\,'-!$1. Feb March April May June July Aug Month of the year Sept Oct Nov Dec Figure 6.34 Variation of voltage sag frequency through the year .(Data obtainedfrom Dorr [68J.) 6.3.1.6 Correcting for Short Monitoring Periods.The variation of the sag frequency through the year indicates that the monitoring period should be at least I year to get a good impression of the power quality at a certain site. As weather activity varies from year to year, it is even neededmonitor to several years. In case a limof the ited monitoring period is used, it is still possible to get a rough estimate [49]. To do this, faultdata are needed average number of sags over a longer period of time. over themonitoring period as well as over a longer period 356 Chapter6 • VoltageSags-Stochastic Assessment The basicassumptionbehindthe correctionmethodis that voltagesags are due to short circuits: thus that the numberof sags isproportional to the numberof shortcircuit faults. In equationform this readsas N sags Njaults N sags= ~ faults (6.7) where N.r;ag.'l and Nfaults are thenumberof sagsand faults, respectively,recordedduring the monitoring period, and Nsag.'l and Njaults the (average)number during a longer period of time. The numberof sags over alonger period of time can thus beobtained from Njaults N sags -- N sags x N- - (6.8) faults Ideally, one would like toknow the numberof faults in theareaof the system in which the sagsoriginate. Often this information is not available: one is likely to only have fault data over the whole servicearea of the utility. This method also neglects the above-mentionedshort-durationsags due totriggering of overvoltagedevices and sags due totransientfaults which are not recorded. The correction method can beimproved if the sags can betraced back to the voltage levels at which theyoriginated: N sags= L[ I Fli)] faults sags X N(') N(i) (6.9) faults with N.~2gs the numberof sagsduring the monitoring period originatingat voltage level i, etc. In most cases it will not bepossibleto traceback all sags. Only for a small number of sites thismethodmight be suitable.It has been used in [49] to q uantify the average supply performancein Japan. 6.3.1.7 Variation in Space. The basic assumptionof a large power quality survey is that the averagepower quality, over a number of sites, givesinformation aboutthe power quality for each individual site. Thus, if the conclusionof the survey is that there are onaverage25 sagswithin a certain magnitudeand duration range, this number should at least be anindication of the numberof sags at anindividual site, in an individual year. Obtaining information about the differences between different sites is difficult;partly becausemainly the averageresults have been published; partly because differences betweensites arenot always statistically significant after a short monitoring period. Someindication of the differencebetween sites iso btainedfrom the EFI survey. 95% site and the averageof all sites is very large, as can be The difference between the seen bycomparingTables6.13 and 6.15. At least5% of the sites haveaboutfour times as many sags as theaverageof all sites. For those sites theaveragevalues donot give much usefulinformation. The problem is that without a prior study it is difficult to know whetherthe averagedataappliesto a certainsite. Furthersplitting up thedataset in different types of sites, e.g., systems with mainly overheadlines and systems with mainly undergroundcables, canreducethe spreadamongthe sites within onegroup. But reducing thedataset will' also increasethe statisticalerror in the estimates. Information on the spreadin power quality amongdifferent sites is also given in [72]. Sags and someo ther voltage disturbanceswere measuredat 24 sites from May 1977through September1979,leading to a total of 270 monitor-monthsof data. The 357 Section 6.3 • PowerQuality Monitoring TABLE 6.17 Distribution Over the Sitesof the Numberof Sagsand Interruptions Maximum Numberof Sags LongerThan the IndicatedDuration Number of Sites 10% 250/0 50% 75% 900/0 I cycle 100ms 200 ms 0.5 sec I sec II 6 9 3 5 13 19 26 8 2 3 5 12 17 8 0 2 3 5 12 8 17 25 36 51 Source: Data obtainedfrom [72]. total amountof dataof this survey is not very large, but the monitor period at each site is long enoughto make some comparisonbetween the different sites. Some of the results are shown inT able 6.17. This table gives, for various minimum durations,the maximum number of sags andinterruptionsfor a certain percentageof sites. As an example:25°~ of the sites has fewerthan five events per year longer than 200 milli11 and 51 events per year longer than one seconds. Also:80% of the sites has between cycle in duration,the remaining20% of sites are outsideof that range.For about half of the sites themedianvalue is areasonableindicatorof the numberof sagsthat can be 500/0 expected. Asalreadymentionedbefore, it ishard to know if a site belongs to the average sites or not,without monitoring the supply. 8.3.2 IndividualSites Monitoring is not only usedfor large power quality surveys, it is also used for assessing thepower quality of individual sites.For harmonicsand voltagetransients, reliable results can be obtainedin a relativelyshortperiod of time. Someinterestingsite surveys inCanadianrural industry have beenperformedby Koval [58]. One of the conclusionsof his studieswas that a monitoring period of two weeks gives a good that this impressionof the power quality at a site[59]. Again it needs. to be stressed holds only for relativelyfrequentevents like voltagetransientsand motor startingsags and for phenomenalike harmonicsand voltagefluctuation. Voltage sags andinterruptions of interest for compatibility assessment have occurrence frequencies of once a month or less.Much longer monitoring periods are needed for those events. 6.3.2.1 The Required Monitoring Period.To estimate how long the monitoring period needs to be, we assume that the time-between-events exponentiallydistribuis ted. This meansthat the probability of observing an event, in let's say the next minute, is independentof the time elapsed since the last event. Thus, events occur completelyindependentfrom each other.Under that condition the numberof events capturedwithin a certain period is a stochasticvariable with a so-called Poisson distribution. numberof Let Jl be the expectednumberof events per year, then the observed eventsK, over amonitoringperiod of n years is a discrete stochasticvariablewith the following distribution: (6.10) 358 Chapter6 • VoltageSags-Stochastic Assessment This Poissondistribution has anexpectedvalue nil anda standarddeviation ..jifii. The result of monitoringis an estimateof the expectednumberof events per year,obtained as follows: K (6.11) Ilest =- n This estimatehas an expectedvalue JL (it is a true estimate)and a standarddeviation ~. For a largeenoughvalue of nil (i.e., for a sufficientnumberof observedevents)the Poissondistributioncan be approximatedby a normaldistributionwith expectedvalue J-L and standarddeviation ~. For a normal distribution with expectedvalue J-L and standarddeviation (J the so-called95% confidenceinterval is betweenIl - 1.96(1 and JL + 1.96(1,with (1 the standarddeviation.The relativeerror in the estimateof JL after n samplesis thus, 1.96(1 1.96 2 (6.12) -,;- = ..jifii ~ ,IN with N = nil the expectednumberof events inn years, i.e., in the wholeobservation period. To limit the relativeerror to E the monitoringperiod n shouldfulfill the following inequality: 2 (6.13) --<E ~ or 4 (6.14) n > -2 J-LE For an eventwith a frequencyof JL times per year, themonitoringperiod shouldbe at least ~ yearsto obtain an accuracyE. /-U Table 6.18 gives theminimum monitoring period for various event frequencies and accuracies.N ote that sag frequenciesare ultimately used topredictequipmenttrip frequencies.It showsthat site monitoringcan only giveaccurateresultsfor very sensitive equipment(high frequency of tripping events).When equipmentbecomesmore compatiblewith the supply (and thus trips lessoften) site monitoringcan no longer be used topredict the numberof trips. As mentionedbefore, the approximationof a Poissondistribution by a normal distributionholdsfor a sampleof large size.N othingwas saidaboutwhat this large size is. A more accurateexpressionfor the uncertaintyis obtainedby using theso-called Student'st-distribution. Using this distributiongivesanotherfactor in (6.12) insteadof 1.96.The deviationis small: for 10eventswe find afactor of 2.228, which is anincrease of 14%; for five eventsthe value is 2.571.F or 16 events(50 % accuracyaccordingto the TABLE 6.18 Minimum Monitoring Period Needed toObtain a Given Accuracy Event Frequency 50°At Accuracy 10% Accuracy 2% Accuracy I per day I per week I per month 1 per year 2 weeks 4 months I year 16 years I year 7 years 30 years 400 years 25 years 200 years 800 years 10,000 years Section 6.4 • TheMethod of Fault Positions 359 approximation)the Student'st-distributiongives anaccuracyof 53%. The effecto f this on Table 6.18 is small. 6.3.2.2 More Uncertainties. The abovereasoningassumes astationarysystem with exponentiallydistributed times between events, thus where events appearcompletely at random. For a stationary system it is possible toobtain the event frequency with anyrequiredaccuracy byapplying a long-enoughmonitoring period. In that monitoring results the actual situation there are two more effects which make have a limited predictive value: lightning, heavy wind, • A large fraction of voltage sags is due to bad weather: snow, etc. The sag frequency thereforenot is at all constantbut follows the annual weatherpatterns.But the amountof weatheractivity also varies significantly from year to year. Due to the relation betweenvoltage sags and adverseweather,the sags come in clusters. To getcertain a accuracyin the estimate,one needs to observe more than a minimum numberof clusters. It is obviousthat this will increase therequiredmonitoring period. To get a longterm average a long monitoringperiodis needed. Acorrectionmadeaccording to (6.8) might increase the accuracy. • Power systems themselves are not static but change continuouslyfrom year to year. This especially holds for distribution networks. The numberof feeders connectedto a substation·can change; ora notherprotectiverelay is used. Also componentfailure rates can change, e.g., due to aging; increasedloading of components;different maintenancepolicies; or because the amountof squirrels in the areasuddenlydecreases. Despite thesedisadvantages,site monitoring can be very helpful in finding and hard to predict. In solving power quality problems,as some things are simply very addition, stochasticassessment requires certain a level of understandingof voltage disturbancesand their origin. Thisunderstandingcan only be achievedthroughmonitoring. 8.4 THE METHOD OF FAULT POSITIONS 8.4.1 Stochastic Prediction Methods The great advantageof stochasticprediction as comparedto monitoring is that the required accuracyis obtained right away. With stochasticprediction it is even possible to assess the power quality of a systemthat does not yet exist; something which is impossible to achieve by power quality monitoring. Stochasticprediction methodsuse modeling techniquesto determineexpected value, standarddeviation, etc., of a stochasticvariable. With' stochasticpredictions one should not think of a prediction like a voltage sag down to35% will occur at 7:30 in the evening on July21. Instead,the kind of predictionsare more like in July one canexpect10 sags below 70%,halfofwhich areexpectedto occur between5 and 9 in the evening. Stochasticpredictionmethodshave been used for many yearspredictfrequency to and duration of long interruptionsas discussed in detail in C hapter2. For shorter duration events, the useof stochasticprediction techniquesis still very uncommon. 360 Chapter6 • VoltageSags-Stochastic Assessment Those events tend to have a higher occurrencefrequency, making monitoring more feasible. Also the required electrical models have a higher complexity than for long interruptions.A final explanationis that power quality is still very much anindustrydriven area, whereas reliability evaluationis much more auniversity-drivensubject. Stochasticpredictionmethodsare asaccurateas the model used and as accurate as thedataused. The accuracy of the models can be influenced; the accuracy of the data is often outsideour control. Any stochasticpredictionstudy in power systems requires two kinds of data:power systemdata and componentreliability data. The main data concern is thelatter one. Componentreliability data can only beobtainedthrough observing thebehavior of the component.From a stochasticpoint of view this is identical to the powerquality monitoring of one individual site we discussed earlier. Componentreliability data has therefore the sameuncertaintiesas the outcomeof power quality monitoring. One could now betempted to draw the conclusion that we did not gain anythingby usingstochasticprediction.This conclusionis fortunately not correct. Many utilities have records ofc omponentfailures over several decades. Componentsdo not need to beconsideredseparatelybut can begroupedinto "stochastically identical" types: like alldistribution transformers.This enormouslyreduces the error in the componentfailure rate. Someproblemsremain of course:maintenancemethodschange; the failure rate of new componentsis hard to assess;c omponentloading patternscan change; even weatherpatternsare prone to change. The same uncertaintiesare presentwith power quality monitoring, but with stochasticassessment one is able somewhatassess to the influence of theseuncertainties. 8.4.2 Basics of the Method of Fault Positions The method of fault positions is a straightforward method to determine the expectednumberof sags. It wasproposedindependentlyby a numberof authorsbut probablyfirst used byConrad[48] whose work has become part of IEEE Std-493 [8], [21]. The methodis also used byEdF (Electricite deFrance)to estimatethe numberof sags due to faults in their distribution systems [60]. Themethodof fault positionswas combinedwith Monte Carlo simulationby the authorin [61], [63], extendedwith nonrectangularsags due tomotor re-accelerationin [18], [62] and extendedwith generator outagesin [64]. At least onecommercialsoftwarepackageis availableusing themethod of fault positions. Morepackageswill almostcertainlyfollow as themethodis computationally very simple,althoughit often requires excessive calculationtime. The accuracy of the results can be increased increasingthe by numberof fault positions.Nonrectangularsags can betaken into account by using dynamic generatorand load models; phase-angle j umps by working with complex impedancesand voltages; threephaseunbalanceby including single-phase andphase-to-phase faults. 6.4.2.1 Outlineof the Method. The method of fault positions proceeds, schematically, as follows: • Determinethe area of the system in which short circuits will be considered. • Split this area into smallparts. Short circuits within one part should lead to voltage sags with similarcharacteristics.Each smallpart is representedby one fault position in an electriccircuit model of thepower system. 361 Section 6.4 • TheMethod of Fault Positions • For each faultposition, the short-circuitfrequency isdetermined.The shortcircuit frequency is thenumberof short-circuitfaults per year in the small part of the systemrepresentedby a fault position. • By usingthe electric circuit modelo f the power system the sag characteristics are calculatedfor each faultposition. Any power system model and any calculationmethodcan be used. The choice will depend on the availability of tools and on thecharacteristicswhich need to be calculated. • The results from the two previous steps (sag characteristicsand frequency of occurrence) arecombinedto obtainstochasticalinformationaboutthe number of sags withcharacteristicswithin certainranges. 6.4.2.2 Hypothetical Example.Considera lOOkm line as shown in Fig. 6.35. Short circuits in this part of the system arerepresentedthrougheight fault positions. The choiceof the fault positionsdependson the sagcharacteristicswhich are of interest. In this example we considermagnitudeand duration. Fault position I (representingbusbarfaults in the localsubstation)and fault position 2 (faults close to the local substation)will result in the same sag magnitude.But the fault-clearing time is different, thereforetwo fault positions have been chosen. The fault positions along the line (2, 3, 4, and 5) have similar fault-clearingtime but different sag magnitude. Fault positions6, 7, and 8 result in the same sag magnitudebut different duration. For each faultpositiona frequency, amagnitude,and adurationare determined, as shown inTable6.19. Failure ratesof eight faults per 100kmof line per year and 10 faults per 100substationsper year have been used. It should be realized that herenot all fault positions along the linerepresentan equal fraction of the line: e.g., position 5 represents 25 km (between 5/8th and 7/8th of the line) but position 6 only 12.5km 18th and 1). (between 7 The resulting sags (1 through8 in Table 6.19) are placed in bins or immediately in a cumulative form.Table6.20 shows how the various sags fit in the bins. Filling in the frequencies (failure rates) leads to Table 6.21 andcumulativeequivalentshown its in Table 6.22.Alternatively it is possible toupdatethe cumulative table after each fault 8 3 4 5 l 6 .-..--- Figure 6.35 Part of power system with fault positions. Load TABLE 6.19 Fault Positions with ResuJtingSag Magnitude and Duration Fault Position I 2 3 4 5 6 7 8 Busbar fault in local substation Fault on a line close to local substation Fault at 25%. of the line Fault at 50% of the line Fault at 75% of the line Fault at 1000/0 of local line Fault at 0% of remote line Busbar fault in remote substation Frequency Magnitude Duration O.ljyr 4jyr 2/yr 2/yr 2/yr l/yr 2/yr O.l/yr % 0 0% 320/0 180 ms 80 ms 49% 57% 105 ms 110ms 250 fiS 64% 64% 64% 90 ms 90 ms 180ms 362 Chapter6 • VoltageSags-Stochastic Assessment TABLE 6.20 Fault Positions Sorted for Magnitude and Duration Bins 60-80% 40-60% 20-40°A> 0-200/0 0-100 ms 100-200 ms 200-300ms 7 8 4 and 5 6 3 2 TABLE 6.21 Table with Event Frequencies for Example of Method of Fault Positions 60-80% 40-60% 20-40% 0-20% 0-100 IDS 100-200 ms 2.0 0.1 4.0 2.0 4.0 200-300IDS 1.0 0.1 TABLE 6.22 Cumulative Table for Example of Method of Fault Positions 800/0 600/0 40% 20o~ oIDS 100 ms 200 ms 13.2 10.1 6.1 4.1 5.2 4.1 0.1 0.1 1.0 0.0 0.0 0.0 position. As we have seen inSection6.2 this is neededanywaywhen non-rectangular sags areconsidered.Pleasenote that this is acompletelyfictitious example.No calculaobtain the magnitudeand durationsin Table 6.19. tion at all has been used to 6.4.3 Choosing the Fault Positions The first step inapplying the methodof fault positionsis the choiceof the actual fault positions. It will be obvious that to obtain more accurateresults, more fault positions are needed.But a random choice of new fault positions will probably not increasethe accuracy,only increasethe computationaleffort. Threedecisionshave to bemadewhen choosingfault positions: applying 1. In whichpart of the power system do faults need to be applied? Only faults to one feeder iscertainly not enough; applyingfaults to all feeders in the wholecountryis certainlytoo much. Some kindof compromiseis needed. This questionneeds to beaddressedfor each voltagelevel. 2. How muchdistancebetween fault positions is needed? Do we only need fault positionsin the substationsor also eachkilometeralongthe lines?Again this questionneeds to beaddressedfor eachvoltagelevel. For each fault position, different events 3. Which events need to be considered? can beconsidered.One can decide to onlystudy three-phasefaults, only 363 Section 6.4 • TheMethod of Fault Positions single-phasefaults, or all types of faults. One can considerdifferent fault impedances,d ifferent fault-clearingtimes, or different schedulingof generators, eachwith its own frequencyof occurrenceand resultingsag characteristics. Below are somesuggestionsfor the choice of the fault positions. A numberof those suggestionsare borrowed from the method of critical distancesto be discussedin Section 6.5. In this section only the results will be used; for more theoretical background one is advisedto read Section6.5 first. The main criterion in choosingfault positionsis: a fault position should represent This criterion has been short-circuit faults leading to sags with similar characteristics. applied in choosingthe fault positionsin Fig. 6.35 and Table 6.19. 6.4.3.1 DistancebetweenFault Positions. To understandhow the distancebetween fault positions influencesthe result, considerthe sagmagnitudeas a function of the distancebetweenthe fault and the substationfrom which the load is fed. The sag magnitudeis plotted in Fig. 6.36. The shapeof the curve can be obtainedfrom the equationsin Section 6.5. By choosing one fault position to representa certain rangeof possiblefaults, we make the sag magnitudefor the whole rangeequal to the sag magnitudefor that one position. The approximatedmagnitudeversusdistanceis shownin Fig. 6.37. We seethat the error is largestwhen theexactcurve is at its steepest, which is close to the load. Here we would need ahigher density of fault positions. For more remote faults, the curve becomesmore flat, and the error smaller. Furtheraway from the load, a lower density of fault positionswould be acceptable. To quantify this, considera radial systemasshownin Fig. 6.38. Aload is fed from a substationwith a nominal (phase-to-phase)voltage V nom. The fault current for a terminal fault on the indicatedfeederis [fault, thus the sourceimpedanceis Z s= Vnom (6.15) v'3 x [fault 0.8 .e~ 0.6 Q ~ c= 8 fO.4 0 ·3en r/) J:J ~ ] 0.2 .s 0 0 0.25 0.5 0.75 1 1.25 Distanceto the fault 1.5 Figure 6.36 Voltage as afunction of the distanceto the fault. 1.75 2 364 Chapter6 • Voltage Sags-Stochastic Assessment \ 0.8 ~ lO.6 ~ : 0.4 en /' ../ 0.2 ..... .... ~Approximated voltage ........~ Actualvoltage O...----I---+----t--~~---I----+-----I~---I o 0.25 0.5 0.75 1 1.25 Distanceto the fault 1.5 1.75 2 Figure 6.37Approximatedvoltage as a functionof the distanceto the fault. Source Feeder Load Figure 6.38 Faults ina radial system. The feederhasan impedancez per unit length and the distancebetweenthe substation and the fault is x, leading to a feederimpedanceof ZF = zx. The voltage at the substationduring the fault (as afraction of the pre-fault voltage)is found from V sag - ZF _ ZS+ZF - xz ~+xz (6 16) · .../31/ou11 For a given sag magnitude Vsag, we can calculatethe distanceto the fault: x = Vnom ./3Z[/ault Vsag X ------~ 1 - Vsag (6.17) Note that someapproximationsare madehere, which will be discussedin Section6.5. Consideras an example a 34.5 kV system with 10kA availablefault currentand a feederimpedanceof 0.3 O/km. This gives the following distances to the fault: • Vsag = 10%: x = 750m • Vsag = 20%: x = 1650m • v,rag = 50%: x = 6.5 km • Vsag=700;O:x=15km • Vsag = 80%: x = 27 km • Vrag = 90%: x = 60km Section 6.4 • TheMethod of Fault Positions 365 If we want to distinguish between a sag down 10% to and one down to 20%, we need fault positionsat least every kilometer. But if the bordersof the bins in the sag density table are at500~, 70%, 80%, and900~, fault positionsevery' 5 km are sufficient.Note also that the required distance between fault positionsincreases very fast when moving away from the load position. Thus, the required density of fault positionsdecreases fast for increasing distance to the fault. Equation (6.17) gives anindication of the distancebetween faultpositions for linesoriginatingin thesubstationfrom which the load is fed.For otherlines, one or two fault positions per line is normally enough, if thesubstationsare not too close. A possible strategy is to first calculate the resulting magnitudefor sag faults in the substation and to insert fault positions in between when the resulting sagmagnitudefor two neighboringsubstationsdiffers too much. Choosingtwo fault positions per line instead o f one couldactually speed up the calculationsif the fault positions are chosen at the beginningand end of the line. This way, all tinesoriginating from the samesubstationneed only one voltagecalculation. The situationbecomes morecomplicatedwhen networksare meshed across voltage levels, like thetransmissionvoltage levels in theUnited Statesand in severalo ther countries.Considera system like in Fig. 6.39. A safe strategyis to use multiple fault positions on the indicated lines and only one or two fault positionson the other lines, including 138kV, 230kV, and 345kV. Due to the multiple pathsfor the fault current not and the relatively largetransformerimpedances, faults at 138kV and higher will cause very deep sags; and the precise fault positionwill not have much influence on the sagmagnitude.For 230kV and 345kV, one faultposition per substationis probably still too much. The main problem is that no definite rules can be given for the required numberof fault positions. In case computationtime is noconcern,and the selectionof fault positionsis automatic,one might simply choose 10 or even more fault positions for each line. In the above, only the sag magnitudehas been used to determinethe numberof fault positions.Apart from the sagmagnitude,the sagduration will also have to be considered. The sag d uration depends on theprotectionused for thevarious feeders and substationcomponents.It is especiallyimportant to considerparts of the system and thus to a longer sagduration. where faults lead to longer fault-clearing time Possible examples are busbars protectedby the backup protection of the infeeding lines; faults toward the remote endof a transmissionline cleared by thedistance protectionin its zone 2. 345kV Figure 6.39Network meshed across voltage levels, with suggested fault positions. 366 Chapter6 • Voltage Sags-Stochastic Assessment 6.4.3.2 Extentof the Fault Positions. In the precedingsection, the requirements for thedistancebetween faultpositions were discussed. The resulting recommendationwas to use one or two faultpositionsper line for all but those lines which are directly feeding the load.T he next question that comes up is: How far do we have to go with this? Is it, e.g., needed considera to 345 kV substationat 1000km away?Probablynot, but howaboutone at 200 km?There are two possible ways forward, both of which arenot really satisfying: 1. Use (6.17) toestimateat which distancea fault would lead to a sag down to 90%, or anyothervalue for the"mostshallow sagof interest."For transmission voltages this will give very large values (600 km for a 345 kV system with 10 kA availablefault current),which areprobablymuch higherthanactually needed. 2. Startwith fault positionsin a restrictedarea, and look at the sag magnitudes for faults at theborderof this area.If thesemagnitudesare below900/0, the area needs to be extended.If the system isavailablein the right format for a suitablepower systemanalysispackage,this might still be the fastestmethod. 6.4.3.3 Failure of the Protection. Failure of the protection is of concern for voltage sagcalculationsbecause it leads to laonger fault-clearing time, and thus a longer sagduration. This longer sagduration, often significantly longer,could be important for the compatibility assessment. The equipmentmight toleratethe sag when the primary protection clears the fault, but not when the backup protection has to take over. To include failureof the protection,two events have to be consideredfor each fault position: onerepresentingclearing by the primary protection, the other fault clearing by thebackup.The two events will typically be givendifferent fault frequencies.Alternatively one can use a fixed failure rate of the protectionand a fixed faultclearing time forboth the primary and the backupprotection.In that case the resulting magnitudedistribution only needs to be shiftedtoward the relevantduration. 6.4.3.4 Multiple Events. The method of fault positions in its basic form only considersshort-circuit faults in an otherwisenormal system. Multiple events like a fault during the failure of anearbypower stationare normally not considered.To include these, faultcalculationsneed to beperformedfor the system with the power station out of operation.The choice of fault positions becomes even more complicated now. Only those faults need to be consideredfor which the outage of the power station influences the sag.When an automaticmethod is used, it isprobably simplest toconsiderall situations.The beststrategyappearsagain to' start with generator stationsnear the load,and move further away from the load until there is no longer any significant influence on the sag magnitude.Significant influence should be defined as likely to affectbehaviorof equipment. 8.4.4 An Example of the Method of Fault Positions In this section we discuss an exampleof the useof the methodof fault positions.A small system is used for this: the reasonbeing that the data was readilyavailableand that the data processingwas limited sothat various options could be studied in a 367 Section 6.4 • TheMethod of Fault Positions relatively short time. A study in a U.S. transmissionsystem isdescribedin [8], and a study in a large Europeantransmissionsystemin [71], [74]. 6.4.4.1 The Reliability Test System. The reliability test system(RTS) was proposedby the IEEE subcommitteeon the applicationof probability methodsto compare stochasticassessmenttechniquesfor generationand transmissionsystems [73]. The RTS has been used by Qader[64], [71] to demonstratethe method of fault positions. The reliability test system consists of 24 bussesconnectedby 38 lines and cables, as shown in Fig. 6.40. Ten generatorsand one synchronouscondenserare connectedat 138kV and at 230kV. 6.4.4.2 Voltages Due to One Fault.F igure 6.41 shows the effectof a fault halfway between busses 2and 4 on the voltages throughout the system. Only bus 4 BUS 22 230kV BUSt3 Trans. 4 BUS 10""''''''''' 138kV BUS 4 BUS 8 BUSS BUst BUS2 Figure 6.40 Reliability test system.( Reproducedfrom Qader[71].) 368 Chapter6 • VoltageSags-Stochastic Assessment Figure 6.41 Voltage sags at different busses due to a fault halfway between bus 2 and bus 4 in Fig. 6.40.(Reproducedfrom Qader [7IJ.) shows avoltage drop below 50%, but the voltagedrops below 900/0 in a large part of the 138kV system.Note that the voltagedrops to 280/0 at bus 4, but only to58% at bus 2, while theshort-circuit fault is exactly in the middleof the line between bus generatorsat bus I and bus 2 keeping up 2 and bus 4. This difference is due to the the voltage. Bus 4 is far away from any generatorstation, thus the voltagedrops to a much lower value. The dense c oncentrationof generatorstationskeeps up the voltage in most of the 230 kV system, thuspreventingmore serious voltagedrops. Also, the relatively hightransformerimpedancemakesthat the voltagedrops at 230 kV level are small. This figure shows some well-known and trivial facts which are still worth repeatinghere: • The voltagedrop is highestnearthe fault positionand decreases when moving further away from the fault. • The voltagedrop diminishesquickly when movingtoward a generatorstation. Section 6.4 • The Method ofFault Positions 369 • The voltage drop diminishes when moving acrosstransformertoward a a higher voltage level. This assumes that more generation is connected to higher voltagelevels.The high-voltage side of the transformeris closer to the source, so that the voltage drops less in magnitude. 6.4.4.3 Exposed Area.In Fig. 6.41 the fault position was fixed and voltage sags were calculated for all busses. Figure 6.42 gives the reversed situation: the voltage magnitudeis calculated for one bus but for many fault positions. In this case, the sagmagnitudeat bus 4 is calculated. Positions leading to equal magnitudes sag at bus 4 are connected through "contour lines" in Fig. 6.42.Contourlines have been plotted for sag magnitudes of30% , 50% , 60%, 70% , and 80% • The area in which faults lead to a sag below a certain voltage is called the "exposed area."The term exposed area was originally linked to equipmentbehavior. Suppose t hat the equipment Figure 6.41 Exposed area contours for bus 4. (Reproduced from Qader [71].) 370 Chapter6 • Voltage Sags-Stochastic Assessment trips when the voltagedrops below 600/0. In that case theequipmentis "exposed"to all faults within the 60% contour in the figure; hence the term exposed .area. As faults can only occur onprimary components(lines, cables,transformers,busses, etc.), the exposed area is strictly speakingnot an area, but acollection of points (the substations)and curves (the lines and cables). But drawing a closedcontourhelps to visualize the concept.Knowing which primary componentsare within the exposed area can be morevaluable information than the actual number of sags. Suppose there is anoverheadline across amountainprone to adverseweather,within the exposed area. Then it might be worth to consideradditional protection measuresfor this line, or to change the system structureso that this line no longer falls within the exposed area, or to improve equipmentimmunity so that the exposedareano longer con tains this line. From Fig. 6.42 andother exposed areacontours,the following conclusionsare drawn: • The exposed area extends further toward large concentrationsof generation, than toward partsof the systemwithout generation. • The shape of the exposed area contour near transformerstationsdependson the amount of generationpresent on theother side of the transformer.The exposed area typically extends far into higher-voltagenetworksbut rarely into lower-voltagenetworks.If the fault takes place in a lower-voltagenetwork the voltage drop over thetransformerimpedancewill be large. This assumes t hat the maingenerationis at a higher 'voltage level than the fault. Consideringthe simple network structuresin Chapter4 explains thisbehavior. 6.4.4.4 Sag Frequency.Thesecalculationscan beperformedfor all busses, resulting in a setof exposed areacontoursfor each bus.Plotting them in one figure would not result in somethingeasily interpretable.Instead Fig. 6.43 gives the expectednumberof sags to a. voltage below 80% for each bus. The average numberof sags per bus is 6.85 per year; the various percentilesare given inTable 6.23. We see that 80% of the busses has a sag frequency within 30% of the average sag frequency for all busses. Notethat we assumedthe same fault rate (in faults per km per year). for all lines. In reality some lines are more prone to faults than others, which can give larger variationsin the sag frequency. It is difficult to draw generalconclusionsaboutthe sag frequency, because each system is different.From this and otherstudies, however, one might, draw the conclusion that sag frequencies are lower towards large concentrationsof generationand higher further away from thegeneratorstations. TABLE 6.23 Percentiles of the Sag Frequency Distribution Over the Busses in the Reliability Test System Percentile 90% 75% 50% 25% 10% Sag Frequency 4.7 per 5.2 per 6.8 per 8.2 per 9.0 per year year year year year Percent of Average 700/0 75% 100% 120% 130% 371 Section 6.4 • TheMethod of Fault Positions 8.58 138kV 6.81 7.14 4.72 Figure 6.43 Voltage sag frequencyfor all busses in the RTS:numberof sags below 800/0. (Reproducedfrom Qader[71].) 6.4.4.5 Generator Scheduling.In the precedingstudy it was assumedthat all generatorswere in operation.In reality this is an unlikelysituation.We sawthat generator stations have a significant influence on the voltages in the system during a fault, and on the sag frequency. To quantify this influence, thecalculationsin the reliability test system have been repeatedfor the situation in which all 138kV substations are out of operation. The resulting sag frequency isshown in Fig. 6.44. Comparingthis figure with Fig. 6.43 showsthat the sagfrequencyis increased at all busses but most significantly at the 138kV busses. The sag frequency is very similar nearby in for all 138kV busses. The reason that is faults in the 138kV system, and· the 230kV system, makethat the voltage drops below 800/0 for all 138kV busses. If the sag frequency is defined as the number of sags below65% the differences between the 138kV busses become larger, Table see 6.24. As a next step it has been assumed that the three 138kVgeneratorsare each out of operationduring four months of the year, andthat there is nooverlap in these periods; thus there are always two 138 kV generatorsin operation.For each of these periods (i.e., for eachc ombinationof one generatorout and two in operation)the sag frequency has been calculatedin exactly the same way as before. The results for the 372 Chapter6 • VoltageSags-Stochastic Assessment 12.18 138kV 12.18 12.18 12.18 Figure 6.44 Voltage sag frequency(numberof sags per year) for all busses in the reliability test system when the 138 kV g eneratorsare out of operation. (Reproducedfrom Qader[71].) TABLE 6.24 Influenceof GeneratorSchedulingon the SagFrequencyin the Reliability Test System,Numberof Sags perYear below 65% 138 kV Bus Generator Scheduling Generatorlout Generator2 out Generator7 out Average All generatorsin All generatorsout 2 2.80 2.43 1.54 2.26 1.34 7.37 2.77 2.79 1.40 2.32 1.40 7.37 3 3.24 3.06 3.06 3.12 2.85 6.73 4 3.65 3.77 2.81 3.41 2.19 7.43 5 3.42 3.44 3.20 3.35 2.16 7.06 6 3.16 3.18 3.18 3.17 2.60 5.19 7 0.80 0.80 4.42 2.01 0.80 6.66 8 9 10 1.47 1.49 4.42 2.46 1.34 6.66 2.65 2.64 3.11 2.80 2.59 5.88 3.38 3.40 3.44 3.41 2.81 5.96 373 Section 6.5 • TheMethod of Critical Distances 138kV busses are shown in Table 6.24. The table shows numberof the sags below65% for all 138kV substations,for a number of generatorscheduling options. The sag frequency for the three4-monthperiods mentioned, is given in the rows labeled "generator lout," "generator2 out," and "generator7 out." The numberof sags per year has beencalculatedas the averageo f these three sag frequencies, and included in the the row labeled"average."For reference the sag frequency is also given for situation when all generatorsare in operation("all generatorsin") and when all three 138kV generatorsare out of operation("all generatorsout"). 8.5 THE METHOD OF CRITICAL DISTANCES The methodof critical distances does not calculate the voltage at a given fault position, but the fault position for a given voltage. By using some simple expressions, it is possible to findout where in thenetwork a fault would lead to a voltage sag down to a givenmagnitudevalue. Each fault closer to the load will cause a deeper sag. The numberof sagsmore severethan this magnitudeis the numberof short-circuitfaults closer to the loadthan the indicated positions. We first describe the basic theory and give the outline of the method. A simple exampledemonstrateshow to apply the method. In the derivationof the basic expression, anumberof approximationshave been made. More exact expressions and expresof the method are sions for non-radial systems are derived next. Finally the results comparedwith the resultsof the methodof fault positions. 8.5.1 Basic Theory The method of critical distances is based on the voltage divider model for the voltage sag, asintroducedin Fig. 4.14. Neglecting loadcurrentsand assuming the preevent voltage to be one, we obtainedfor the voltage at thepoint-of-commoncoupling (pee)during the fault: ZF Vsag = ZF + Zs (6.18) where ZF is the impedancebetween the pee and the fault, and Zs the source impedance at the pee. LetZF = z£, with z the feeder impedance per unit length and £, the distance between the peeand the fault. This results in the following expression for the sag magnitude: V:,ag = z£~ Zs (6.19) The "critical distance"is introducedas follows: themagnitudeat the peedropsbelow a critical voltage V whenever a fault occurs within the critical distance from the pee. An expression for the critical distance £'crit is easily beobtainedfrom (6.19): Zs LCrit V =---; x 1 _ V (6.20) Here it isassumedthat both source and feeder impedance are purely reactive rather (a commonassumptionin power system analysis), or more general: that the angle in the complex plane between these two impedances is zero. For three-phase Strictly speaking(6.20) only holds for a single-phase system. faults in a three-phasesystem, the expressions are valid if for Zs and z the positive- 374 Chapter6 • VoltageSags-Stochastic Assessment sequenceimpedancesare used.For single-phasefaults the sum of positive-, negative- , and zero-sequenceimpedancesshould be used; forphase-to-phasefaults the sumof positive and negativesequence.The voltage in the expressionsaboveis the phase-toneutral voltage in the faulted phasein case of a single-phasefault and thevoltage between thefaulted phasesin case of a phase-to-phase fault. We will come back to single-phasefaults and phase-to-phase faults below. Equation(6.20) can be used to e stimatethe exposed area at every voltagelevel in the supply to a sensitiveload. The exposedareacontainsall fault positionsthat lead to a voltagesagcausinga spuriousequipmenttrip . The expectednumberof spurioustrips is found by simply addingthe failure ratesof all equipmentwithin the exposed area. Transformerimpedancesare a largepart of the sourceimpedanceat any point in the system .Therefore,faults on thesecondaryside do not cause a deep sag on the primary side. To estimatethe numberof sags below acertainmagnitudeit is sufficient to add alllengthsof lines andcableswithin the critical distancefrom the pee. Thetotal length of lines and cableswithin the exposedareais called the"exposedlength." The resultingexposedlengthhas to bemultiplied by the failure rate peru nit lengthto obtain the numberof sags per year. 8.5.2 Example-Three-Phase Faults Considerthe II kV network in Fig. 6.45.The fault level at themain 11 kV bus is 151 MVA (sourceimpedance0.663 pu on a 100 MVA base), the feeder impedanceis 0.336 Q/km (0.278pu/km on the 100 MV A base). The critical distancefor different critical voltages,calculatedfrom (6.20), is given in Table 6.25.The next-to-lastcolumn (labeled"exposedlength") gives thetotal feeder length within theexposedarea.Figure 6.45 gives thecontoursof the exposed area for variouscritical voltages. Eachfault betweenthe main II kV bus (the pee) and the 50% contourwill lead to a voltagesag at the pee with magnitudebelow a 50%. All pointson the 50%contourare at adistanceof 2.4 km (seeTable6.25)of the main II kV bus. The last column in Table 6.25 gives theexpectednumberof equipmenttrips per year. A value of 0.645 faults per km per year has been used . II kV. 15 1 MVA - - ---- - - - -- - 80% - .-.. __------- 90% Figure 6.45 An II kV network used as an example for the method of critical distances. 375 Section 6.5 • The Methodof Critical Distances TABLE 6.25 Results of Method of Critical Distances, Three-Phase Faults Critical Voltage Critical Distance Exposed Length 90% 80% 21.4 km 9.6 km 5.6 km 3.6 km 2.4 km 1.6km 1.0 km 0.6 km 0.3 km 24.0 km 21.6 km 16.8 km 12.2 km 8.6 km 5.4 km 3.0 km 1.8km 0.9 km 700~ 60% 50% 40% 300/0 200/0 10% Number of Trips per Year 15.5 13.9 10.8 7.9 5.5 3.5 1.9 1.1 0.6 8.5.3 Basic Theory: More Accurate Expressions To obtain a more accurateexpression,we have toconsiderthat both the feeder and the sourceimpedanceare complex.The basicexpressionis againobtainedfrom the voltagedivider shownin Fig. 4.14,but with complexvoltageand impedances: v= ZF ZS+ZF (6.21) where Zs = Rs + jXs is the sourceimpedanceat the pee,ZF = (r + jx)£' is the impedancebetweenthe fault and the pee,.c is the distancebetweenthe fault and the pee, z = r + jx is the feeder impedanceper unit length. The load currents have been neglected; thepre-fault voltageat the peeequalsthe sourcevoltageequals 1000/0. In Section4.5 expressionshave beenderivedfor the magnitudeV and the phaseanglejump as afunction of the distancebetweenthe peeand the fault. Equation(4.87) for the magnitudeof the voltagereadsas follows: v = -1-~-A --;::;::===:::::::::::==== i 2A(l-COSa) - (6.22) (1+Ai with A = ZF = Zs Z X £, Zs (6.23) a the angle in thecomplex plane betweensourceand feeder impedance,the so-called impedanceangle: a = arctan(~~) - arctan(~) (6.24) and Zs = IRs + jXsl, Z = Ir + jxl, V = IVI, etc. To obtainan expressionfor the critical distance,A needs to besolvedfrom (6.22) for known V. Therefore,this equationis rewritten into the second-orderp olynomial equation (6.25) 376 Chapter6 • VoltageSags-Stochastic Assessment The positivesolution of this equationcan bewritten as (6.26) Togetherwith (6.23) the desiredexpressionfor the critical distanceis obtained: 2 c . _Zs x_v_[vcosa+JI-V2 sin a ] crtt Z 1- V V+ I (6.27) The first part of (6.27) (6.28) is the expression for the critical distanceobtained(6.20).For most applications(6.20) is sufficient, especially as the d ata are not alwaysavailable to calculatethe impedance angle. To assess the error made by using theapproximatedexpression the critical distance has been calculatedfor different valuesof a. Figure6.46 gives the critical length as function a of the critical voltage for 11kV overheadlines. A sourceimpedanceof 0.663 pu and a feeder impedanceof 0.278pu/km have been used. Note that these are the same values as used in the previous example (Fig. 6.45). We seethat the error only becomes significant for large impedanceangles (more than 30°). In that case moreaccurateexpressionsshould be used. In the next section a simple butaccurateapproximationfor the critical distanceis derived. 25r - - - - - - - r - - - - - - , . - - - - - , - - - - - - - , . - - - , 0.2 0.4 0.6 Critical voltage in pu 0.8 Figure 6.46 Critical distanceas afunction of the critical voltagefor impedanceangle 00 (solid line), -300 (dashedline), -600 (dashdot line). 8.5.4 An Intermediate Expression In the previous sections an exact and approximateexpression an for the critical distance have been derived: (6.27) and (6.20), respectively. The difference between these two expressions is the factor betweensquarebracketsin the right-handside of (6.27): k= Vcoscx+Jl- V2 sin 2 cx 1+ V (6.29) 377 Section 6.5 • TheMethod of Critical Distances 50 r - - - - - . , . . - - - - - . . , . - - - - - . - - - - - , - - - - , 40 d ~ 30 & .5 ~ 20 Jj ~. /' 10 Figure 6.47 Error madein the simplified expressionof critical distance;impedance angle: -200 (solid line), -400 (dashedline), and -600 (dash-dotline). 0.2 0.4 0.6 0.8 Critical voltage in pu The more thisfactor deviates from one, the larger the errormadeby using the simplified expression (6.20). This e rror has beencalculatedas (1 - k) * 100% and plotted in Fig. 6.47 for three valueso f the impedanceangle. The simplified expression (6.20) overestimates the criticaldistance(and thus thenumberof sags) as is also shown in Fig. 6.46. The error is, however, small in most cases, with the exception of systems with large impedance angles like undergroundcables indistributionsystems. A first-order correction to the simplified expression (6.20) can obtainedby be approximating(6.29)around V=O: (6.30) k ~ 1 - V(l - cosa) (6.31) The error made by usingapproximation(6.31) is shown in Fig. 6.48 for different impedanceangles. Theerror made never exceeds a few percent. An importantconclusionfrom Fig. 6.48 isthat the following expression gives the critical distance in systems with a large impedanceangle: L,crit z, =--;- x V I _ V (I - V(l - cosa)} 0 (6.32) -.......::---I -0.5 l , , -1 \ 5 -15 U . [ .S ... -2 , , , , , , \ ,, \ ~ -2.5 , , , \ ~ \ , I -3 \ I \ , I Figure 6.48 Error madeby usinga first-order approximationfor the critical distance; impedanceangle: - 20° (solid line), -400 (dashedline), and -600 (dash-dotline). -3.5 I / -4 0 0.2 0.4 0.6 Critical voltage in pu 0.8 378 Chapter6 • VoltageSags-Stochastic Assessment 6.5.5 Three-Phase Unbalance The abovereasoningapplies to three-phasefaults only. For unbalancedfaults (single-phase,phase-to-phase)the method needsadjustment.Most of the discussion below follows directly from thetreatmentof three-phaseunbalancedsags in Section 4.4. 6.5.5.1 Phase-to-PhaseFaults. Phase-to-phase faults lead to sagso f type C or type D, with a characteristicmagnitudeequal to the initial(phase-to-phase) voltage at the point-of-commoncoupling. Themethodof critical distances applies to the voltage at the pcc and can thus be used without modification for phase-to-phase faults. The impedancevalues to be used are the average of positive- and negative-sequence values. As these are normally about equal, the positive-sequence impedancecan be usedjust like for three-phasefaults. In termsof characteristicmagnitude:the critical distancefor phase-to-phase faults equals the critical distance for three-phasefaults. In case the voltage at the equipmentterminals is of interest (e.g., for single-phase equipment),the strategyis to translatethis voltage back tocharacteristicmagnitude and apply the equationsfor the critical distance to thecharacteristicmagnitude.Of importancehere is todeterminewhether a fault at acertainvoltage level leads to a type C or type D sag. Supposethat the fault leads to a type C sag. In that case of the single-phase equipmentwill not see any sag at all, where j will see a sag between 50% and 100%. Let Veq be the sagmagnitudeat theequipmentterminals andVchar the characteristicmagnitude of the three-phaseunbalancedsag. These twomagnitudesrelate accordingto t Veq = ~ j I + 3V;har (6.33) This expressionis obtainedfrom Fig. 4.90 when neglecting the characteristicphaser ather anglejump (l/J = 0). Including phase-anglejumpsis possible, but would result in complicatedexpressions. The characteristicmagnitudecan beobtainedfrom the magnitudeat the equipment terminalsby using Vchar = 1, J~ V;q - ~ (6.34) 1 For Veq < there are no sags. For < Veq < 1, (6.20) can be used to calculate the critical distance,with V = Vchar• The resulting sag frequency should be multiplied~by to accountfor the fact that one in three faults does not lead to a sag at equipment the a agnitudeof Vchar terminals. For a type D sagof magnitude Vcha" one phase has m also. The expression for the critical distance can be applied directly, but the resulting sag frequency needs to be multiplied by!. The two other phasesdrop to Veq = ~ j n: + 3 (6.35) For Veq < !"f3 this gives nocontribution.For!"f3 < Veq < 1, the critical distance can be calculatedby using (6.36) and the resulting sag frequency should be multiplied j.byNote that the two sag frequencies for the type D sag should be added. 379 Section 6.5 • TheMethod of Critical Distances 6.5.5.2 Example: Phase-to-Phase Faults. Consider the same system as in the examplefor three-phasefaults. We areinterestedin the numberof spurioustrips for phase-to-phase(delta) connectedsingle-phaseload at 660V. A Dy-connectedllkV/ 660V transformeris used.The sag type at theequipmentterminals is determinedas follows: • The phase-to-phase fault leads to athree-phaseunbalancedsag of type C for star-connectedload at 11 kV. . • For delta-connectedload at 11 kV the sag isof type D. • For delta-connectedload at 660V it is of type C. Thecalculationof the trip frequencyas afunction of the equipmentvoltagetoleranceis summarizedin Table 6.26. It proceedsas follows: • For a given critical voltage at the equipmentterminals Veq, the critical characteristicmagnitude Vchar is calculatedby using (6.37) The resultis shownin the secondcolumnof Table6.26. For Veq < 0.5 thevalue underthe squareroot is negative, whichmeansthat even for aterminal fault (distancezero), thevoltageat the equipmentterminalsis higher than the critical voltage. The contribution to the exposedlength is thus zero, hence the zeros in the first few rowsof the table. • From the critical characteristicmagnitude,the critical distanceis calculatedin the standardway, by using z, v-; (6.38) Vcru=-x--z 1 - Vchar with Zs = 0.661 pu and z= 0.278pu/km, The resultingcritical distanceis given in the third column of Table 6.26. Faults,Type C Sags TABLE 6.26 Method of Critical Distances-Phase-to-Phase Sag Magnitudeat EquipmentTerminals Characteristic Magnitude Critical Distance (km) 0 0 0.1 0.2 0 0 0 0 0 0 0 1.5 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0 0 0 0 0.38 0.57 0.72 0.86 3.2 6.1 14.7 ExposedLength (km) Trip Frequency (per year) 0 0 0 0 0 0 0 0 5.0 0 0 0 0 11.4 18.2 24 2.1 4.9 7.8 10.3 380 Chapter6 • VoltageSags-Stochastic Assessment • From the critical distance, the exposed lengthcalculatedfor is the 11kV distribution system in Fig. 6.45. The methodused for this is the same as shown in Fig. 6.45 for three-phasefaults. • Knowing the exposed length it is possible calculatethe to trip frequency. Here it is assumedthat the numberof phase-to-phasefaults is equal to thenumberof three-phase faults: 0.645 per km per year. This is not a realistic assumption,but it enables an easier comparisonof the influenceof the different typesof fault. Because the voltage is only down on two phases for a type C sag, this fault frequency has to be multiplied by j to get the trip frequency. Thelatteris given in the last rowof the table. Consider, as a second example, that the low-voltage load isconnectedin star (thus phase-to-neutralsingle-phase load). The three-phaseunbalancedsag will beof type D, with one deep sag and two shallow sags atequipmentterminals. the Acalculationof the trip frequency using themethodof critical distancesis summarizedin Table6.27. Only calculationfor critical voltages between80% and 960/0 are shown in the table. The other voltage values proceeds in a similar way. • Like for delta-connected load, thecalculationstartswith the choiceof a critical voltage at theequipmentterminals. Next,separatecalculationsare needed for the deep sag and for the shallow sag. • The calculationsfor the deep sag (labeled "lowest voltage" in Table 6.27) are almost identical to thecalculationsfor a three-phasefault. The magnitudeof the deep sag at the equipmentterminals is equal to thecharacteristicmagnitude, sothat the standardequationfor the critical distancecan be used. The only difference isthat the fault frequency needs to be divided by three to accommodatefor the fact that only one in three voltages shows a deep sag. Thus, from the viewpointo f single-phaseequipment:only one in three faults leads to a deep sag. Critical distance, exposed length, and trip frequency for the of4Table 6.27.Note that the exposed deep sag are given in columns 2, 3, and length and the trip frequency no longer increase for critical voltages above 84%. This is because the exposed area alreadyincludes the whole lengthof the 11 kV feeders. TABLE 6.27 Method of Critical Distances-Phase-to-Phase Faults,Type D Sags Lowest Voltage Magnitude Equipment Terminals (pu) Critical Distance (km) 0.80 0.82 0.84 0.86 0.88 0.90 0.92 0.94 0.96 9.5 10.9 12.5 14.7 17.5 21.5 27.4 37.4 57.2 HighestVoltage Exposed Trip Characteristic Critical Length Frequency Magnitude Distance (pu) (km) (per year) (km) 21.5 22.9 24 24 24 24 24 24 24 4.6 4.9 5.2 5.2 5.2 5.2 5.2 5.2 5.2 0 0 0 0 0.31 0.49 0.62 0.73 0.83 0 0 0 0 1.1 2.3 3.9 6.4 11.6 Trip Total Trip Exposed Length FrequencyFrequency (km) (per year) (per year) 0 0 0 0 3.4 8.2 12.8 18.4 23.6 0 0 0 0 1.5 3.5 5.5 7.9 10.1 4.6 4.9 5.2 5.2 6.7 8.7 10.7 13.1 15.3 381 Section 6.5 • TheMethod of Critical Distances • The calculationsfor the shallow sag proceed fairly similar to the calculations for thedelta-connected load. As a first step the critical voltage at the equipment terminals istranslatedinto a criticalcharacteristicmagnitude,using the following expression: (6.39) resulting in the values incolumn 5. For Veq < 0.866 thecharacteristicmagnitude is set to zero. The shallow sag at equipmentterminals the never becomes lower than this value.Calculationof critical distance, exposed length, and trip For the trip frequency, the fault frequency frequency proceeds like before. needs to be multiplied bybecause only two of the three phases show a shallow sag. The results for the shallow sag are summarized in columns through8. 5 • Finally the total trip frequency is the sum o f the trip frequency due to deep sags and the trip frequency due to shallow sags. The total trip frequency is given in the last column. 1 6.5.5.3 Single-PhaseFaults-Solidly Grounded Systems.Single-phase faults lead to sagsof type B, C, or D' at theequipmentterminals. Thetranslationfrom equipmentterminal voltages to the voltage to be used in the expressions for the critiof sag. cal distance depends on the type A type B sag only occurs in case of equipmentconnected in star and the singlephase fault at the same voltage level as equipment(or the at a higher level with only YnYn transformersbetween the fault and the equipment). For a type B sag the terminal voltage can be directly used in the expressions for the critical distance. As only one by! for single.phase drops in voltage, the resulting sag frequency should be multiplied phase equipment.F or the impedances the sum of positive-, negative-, and zerosequence values should be used. Sags of type C or type D occur in all other cases.For these thecharacteristic magnitude deviates from the initial voltage (the voltage in the faulted phase at the pee). For solidly groundeddistribution systems (where positive- and zero-sequence source impedances are equal), the following relation between characteristicmagnitude Vchar and initial magnitudeVinit has been derived (4.109): Vchar 1 2 = 3" + 3v.; (6.40) Knowing the characteristic magnitude of the three-phase unbalanced sag, and Vchar < 1, the initial voltage isobtainedfrom !< 3 V init 1 = 2 V char - 2 (6.41) The characteristicmagnitudeneeds to betranslatedto an initial magnitude,by using (6.41). In case themagnitudeat the equipmentterminals is ofimportance,a second translationhas to be made: from magnitudeat theequipmentterminals tocharacteristic magnitude. Thistranslationproceeds in exactly the same way as phase-to-phase for faults. 6.5.5.4 Example: Single-Phase Faults in a Solidly GroundedSystem. When considering single-phase faults, we need to include the zero-sequence impedance of that source and feeder.For a solidly groundeddistribution system we can assume 382 Chapter6 • VoltageSags-Stochastic Assessment positive- and zero-sequencesourceimpedanceare equal. But this cannotbe assumed for the feeder impedances.From Table 4.4 we get 1.135pu/km for the zero-sequence feeder impedance,and 0.278pu/km for the positive-sequenceimpedance.In the calculations we use the sum of positive-, negative-,and zero-sequenceimpedanceleading to Zs = 1.989pufor the sourceand z = 1.691pu/km for the feeder. The calculationof the critical distancefor single-phase'faults from a given critical characteristicmagnitudeis summarizedin Table 6.28. • The first step is the translation from the characteristicvoltage to the initial voltage,for which expression(6.41) is used.The characteristicmagnitudecannot be lessthan0.33 pu, hencethe zerosin the tablesfor lower valuesthanthis. • From the critical initial voltage,the critical distancecan be calculatedby using the standardexpression r J-crit Zs = - z X Vinit 1 - Vinit (6.42) with Zs = 1.989puand z = 1.691pu/km, • From the critical distance,the exposedlength and the trip frequencycan be calculatedlike before. For single-phasefaults againa fault frequencyof 0.645 faults per km per year has beenused. TABLE 6.28 Method of Critical Distances-Single-Phase Faults,Solidly Grounded System Characteristic Magnitude(pu) o 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 Initial Magnitude (pu) Critical Distance (km) o o o o o o o o 0.10 0.25 0.40 0.55 0.70 0.85 0.1 0.4 0.8 1.4 2.7 6.6 ExposedLength (km) o Trip Frequency (per year) o o o o o o o 0.3 1.2 2.4 4.6 9.8 0.2 0.8 1.5 18.6 12.0 3.0 6.3 6.5.5.5 Single-Phase Faults-GeneralSolutions. In resistance-groundedd istribution systems,the assumptionthat positive- and zero-sequence i mpedanceare equal no longer holds. The assumptionis also not valid when line impedancesare a large part of the sourceimpedance.This is the casein the 400kV supply in Fig. 4.21, as was shown in Fig. 4.105. To obtain a more general expressionfor the critical distance, we can use the phase-to-neutralv oltage in the faulted phase according to (4.40): V-I an - (2Z F t 3Zs 1 + Z£o) + (2ZS1 + Zso) (6.43) The phase-to-neutral voltagesin the non-faultedphasesarenot affectedby single-phase faults. We canthus treatthe phase-to-neutralvoltagesthe sameas the phase-to-ground 383 Section 6.5 • TheMethod of Critical Distances voltages in a solidlygroundedsystem. Thecharacteristicmagnitudeis related to the (initial) phase-to-neutralvoltage as follows: I 2 Vchar = 3" + '3 Van (6.44) With this knowledgeit is possible totranslatesagmagnitudesat the equipmentterminals to characteristicmagnitudesand to phase-to-neutralvoltages. It is possible to translatephase-to-neutralvoltages tophase-to-groundvoltages, but one canalternatively derive anexpressionfor the critical distancefor phase-to-neutralvoltages. For this weintroducepositive- and zero-sequence feeder impedanceper unit length,Zl and zo, respectively, and thedistanceto the fault L. Expression (6.43)changesinto 32s1 V - 1an - (2z) + zo)£ + (2ZS1 + Zso) (6.45) The distanceto the fault £erit can beobtainedfor a given (critical) phase-to-neutral voltage Van: Lcrit = (ZSI - Zso) + Van(2ZS1 + Zso) (2z1 + zo)(1 - Van) (6.46) For ZSI = Zso weobtainthe expression used for solidly groundeddistributionsystems. Note that normally ZSI < Zso so that the critical distancecan become negative for small valuesof Van' Even for aterminal fault the phase-to-neutralvoltageis not zero. Any critical voltagelessthan this minimum value will give a negative criticaldistance. This has no physicalmeaning,and for calculating the exposed length (and sag frequency) a criticaldistanceof zero should be used.Alternatively one cancalculatethe critical distancedirectly from thecharacteristicmagnitude.For this we useVchar = VI + V2 togetherwith (4.29) and (4.30) which give the positive- andnegative-sequence voltages at thepeedue to a single-phase fault. Using the same notationas before, we get the followingexpressionfor the characteristicmagnitudeas a function of the distance to the fault: v _ Z£+ZSO z£ + Zs char - (6.47) with Zs = 2Zs1+ Zso and z = 2z1+ Z00 Solving the criticaldistancegives z, Vchar £crit=-x--Z 1 - Vehar Zso z(l - Vchar) (6.48) 6.5.5.6 Example: Single-Phase Faults in Resistance-Grounded System. In a resistance-grounded system we can no longer assume that positive- andzero-sequence sourceimsourceimpedanceare equal.From Table 4.3 we get for thezero-sequence pedancea value of Zso = 8.172 pu. Thecalculationresults aresummarizedin Table 6.29. The results are only shown for critical voltages between 86% and 98%. For smaller valuesof the critical voltage, the trip frequency is zero. Single-phasefaults in resistance-grounded systems typically lead to very shallow sags. The critical distance is calculateddirectly from the critical characteristicmagnitudeby using (6.48) with Zs = 9.494pu, Zso = 8.172pu, and z= 1.691 pu/krn, Calculation of exposed area and trip frequencyproceedslike before. 384 Chapter6 • VoltageSags-Stochastic Assessment TABLE 6.29 Method of Critical Distances-Single-Phase Faults, Resistance-Grounded System CharacteristicMagnitude (pu) Critical Distance (km) ExposedLength (km) Trip Frequency (per year) 0.86 0.88 0.90 0.92 0.94 0.96 0.98 0 0.9 0 2.7 7.8 13.3 19.4 0 1.7 2.2 4.2 7.4 13.9 24 33.5 24 5.0 8.9 12.5 15.5 15.5 8.5.8 Generator Stations In Section 4.2.4 expression (4.16) was derived describingthe effectof a generator on the sagmagnitude.The equivalentcircuit used toobtain this is shown in Fig.4.24. The expression has the following form: (1 - Vsag) =2 24 3 + (6.49) Z (1 - Vpcc) 4 To obtain the voltage at the pee we have to realize that all load currentshave been neglected here.There are no pre-fault power flows, andboth generatorsin Fig. 4.24 have exactly the same outputvoltage, sothat they canbe replaced by onesourcein the equivalent scheme. The following expression for the voltage obtained is from this scheme: 2 V pee 2 = Z3 + ZIII(2 3 + Z4) (6.50) where ZAI/ZB = f~l is the parallelconnectionof ZA and ZB' Combining(6.49) and (6.50) gives thefoll~wi~g expression for theduring-sagvoltageexperiencedby the load v - 1- sag - Z1Z 4 2 2(Z I + 2 3 + 2 4) + ZI(Z3 + 2 4) (6.51) To obtain an expression for the critical distance,we substitute2 2 = Z X L. The critical distanceis obtainedby solving v,rag = Vcrit toward £. The resultingexpressionis Lail =21 { Z 24 2 1+ 2 3 + 24 X Vcrit 1 - Vcrit _ 23 } 2 1+ 23 + 24 (6.52) The critical distancein (6.52)is not thedistancebetween the faulta nd the load, but the distancebetween the fault and the main supply point. 8.5.7 Phase-Angle Jumps As we have seen inC hapter5, someequipmentis sensitive to thejump in phase angle between the pre-sag voltage and during-sagvoltage. the Inthat case it is reasonable to find an expression for the critical distanceas afunction of the "critical phaseanglejump." In otherwords, at whichdistancedoes a fault lead to a sag with a phaseangle jump equal to a given value? Too btain such an expression we start with the 385 Section 6.5 • TheMethod of Critical Distances expressionfor the phase-anglejump as afunction of the distanceto the fault: (4.84) in Section 4.5. ).. + coso cos</J = --;======= +)..2 + 2Acosa Jl (6.53) where a is the angle in thecomplexplanebetweenthe feederandthe sourceimpedance and A the ratio betweentheir absolutevalues: ZL A=- (6.54) Zs To obtain an expressionfor the critical distance,we need to solve xfrom (6.53) for given phase-anglejump f/J. Taking the squareof both sides of (6.53) and using sin2 = 1 - cos2 gives thefollowing second-orderalgebraicequationfor A: 2 + 2Acosa+ 1 = -sin2a- 2 A sin f/J (6.55) This can be solved by using the standardexpressionfor the roots of a second-order polynomial, or by further rewriting the expression.In any way it will lead to the following (positive) root: sin a A.=---cosa tanf/J (6.56) Combining(6.56) with (6.54) gives thefollowing expressionfor the critical distancefor a critical phase-anglejump cP: Leril = -z, {Sina -----:i: - cosa } z tan 'P (6.57) 8.5.8 Parallel Feeder. Voltage sags onparallel feedersand other loops have beendiscussedin Section 4.2.4. Therewe sawthat most faults on parallel feederstoward the load, lead to deep sags. It is anacceptableapproximationto makethe sagmagnitudezerofor all faults on the parallel feeders. In caseof long feeders(feederimpedancemore than two or three times the sourceimpedance)some additional calculation is needed.It is possibleto derive anexpressionfor the critical distancefor parallel feeders from (4.18)but that expressionwould be too complicatedto beof any use.Insteada simplified calculationis proposed. The voltage profile along the feedercan be approximatedas a (second-order) parabola: v.rag ~ 4Vmaxp(1 - p) (6.58) with p indicating the position of the fault along the feeder, 0~ p :5 1, and Vmax the maximumsagvoltagedue to afault anywhereon the feeder.T hereis no simpleexpression for Vmax; it needs to beobtainedgraphicallyfrom Fig. 4.34 or Fig. 4.35.W hen the maximumvalue isknown, the "critical fraction" is readily obtained: Peril ~ I - I _ Veril Vmax' (6.59) 1400 11000 !2000 j 1500 x....-=~x-~ 100 XC==40 60 8'0 800 0 0 200 400 40 60 80 Sagmagnitudein percent 20 " " ;,;z. -'II'-Z-;r 100 i 00 &1 100 .!400 ] 300 8. 200 40 60 80 40 60 I 80 I 40 60 80 Sagmagnitudein percent 20 Sagmagnitudein percent 20 i ,~, Sagmagnitudein percent 20 o x 100 100 I 100 ' s 1600 1400 2500 1500 ~ ~ e CIJ 00 500 -g 1000 .£ -=i .S 2000 ] °0 200 &400 ~ ~600 fa .S 1200 1000 ] 800 ~ 40 60 40 60 80 Sagmagnitudein percent 20 ,",z-r-*""I ~/z 1 80 Sagmagnitudein percent 20 *_*__X#.. J JX ~x 100 100 Figure 6.49 Exposedlength for nine 400 kV substations:c omparisonbetweenthe methodof fault positions(crosses)and the methodof critical distances(diamonds). ! ~ "d ]600 fo 600 500 .5 oI o 800 700 ~ ttl - 600 ~ ~ 400 Q. ~ 200 a z 00 1 1400 = 1200 ~ 1000 io 800 ] 0 0 500 1000 B 1200 Sagmagnitudein percent 20 h h r: h * 2 ~ ~. & "'0 2000 ] 1500 t 3000 ~ 2500 .s 1000 ~ 500 o0 o J ~x..~-;...x . 20 40 60 80 Sagmagnitudein percent _. 3000~--------------. 200 00 400 600 ~ 2500 ~ & ~ "'0 = 1200 :B 1000 j 800 ] 387 Section 6.5 • TheMethod of Critical Distances The contribution of the feeder to the exposed length equals the critical fraction times the feeder length.F or Veri' > Vmax the whole feedercontributesto the exposed length. 8.5.9 Comparison with the Method of Fault Positions The transmissionsystem study performed by Qader [71], [74] resulted in the number of sags as afunction of magnitudefor all substationsin the U.K. 400-kV transmissionsystem. Themethod of fault positions was used for this study. For a comparedwith the resultsobtainedby numberof substationsthose results have been using themethodof critical distances. The critical distance was calculated as a function of the sagmagnitudeV by using theapproximatedexpression z, V £crit = ~ 1 _ V (6.60) where Zs is the sourceimpedanceand z the feeder impedance per unit length. All the lines originating at the substationare assumed infinitely long; the exposed length is simply the criticaldistancetimes thenumberof lines. The sourceimpedanceZs is calculated by assuming t hat all lines contribute equally to theshort-circuitcurrent for a busbarfault. During a fault on oneof these lines, only (N - 1) out of N lines contribute to the short-circuit current. Thus, the sourceimpedancein p.u. equals z, = -.!!.-.- Sbase N - I (6.61) Sjault with N the numberof linesoriginatingat thesubstation,Sba.vethe base power, and S/auft the short-circuitpower for asubstationfault. The exposed length is found from ~ 2 r r '-exp = N x '-erit = NN_ I --z 1 _V V Slaul, (6 2) .6 The exposed length for the nine substationsis shown in Fig. 6.49, where the crosses indicate the resultsof the method of fault positions. There are obviously differences of the twomethods,with the method of fault positions viewed as the between the results most accurateone. But for themethodof fault positions a largepart of the national grid needs to be modeled. All the data needed for the method of critical distances is, from equation(6.62): • numberof lines originating from the substation; • fault level of the substation;and • feederimpedanceper unit length. All this datacan beobtainedwithout much difficulty. Another interestingobservationfrom (6.62) concerns thevariation in sag frequency among different substations.The main variation can be brought back to fault level,numberof lines originating at thesubstation,and fault frequency. Mitigation of Interruptions and Voltage Sags This chaptergives an overviewof methodsto mitigate voltagesags andinterruptions. o f the variousforms of mitigation, we concentrateon power After a general discussion system design and on mitigation equipmentto be installed between thepower system and the sensitiveequipment.Especially thelatter is underfast developmentsince a few years. Anattemptis made to give aneutraloverview of the variousoptions,knowing that new developmentsare veryhard to predict. Powersystem design is a m ore traditional area,althoughnew developmentsin power electronicsare also expected to have an impact here. 7.1 OVERVIEW OF MITIGATION METHODS 7.1.1 From Fault to Trip In the previous chapterswe discussed voltagemagnitudeevents (voltage sags, shortinterruptions,and longinterruptions)in considerabledetail: their origin,methods of characterization,monitoring and prediction,and their effects onequipment.In this chapterwe look at existing and future ways of mitigating voltagemagnitudeevents. To understandthe variouswaysof mitigation, the mechanismleading to anequipmenttrip needs to beunderstood.Figure 7.1 shows how ashort circuit leads to anequipment trip. The equipmenttrip is what makes the event problem;if a there were noequipment trips, there would not be any voltage quality problem. The underlying event of the equipmenttrip is a short-circuit fault: a low-impedanceconnectionbetween two or more phases, or between one or more phases ground. and At the fault position the voltage drops to a low value. The effecto f the short circuit at other positionsin the system is an event of caertain magnitudeand duration at the interface between the equipmentand the power system. The short-circuitfault will always cause avoltagesag for somecustomers.If the fault takes place in a radial part of the system, theprotection intervention clearing the fault will also lead to an interruption. If there is sufficient redundancypresent, theshort circuit will only lead to a voltage sag. If theresulting event exceeds caertain severity, it will cause anequipmenttrip. Admittedly, not only 389 390 Chapter7 • Mitigation of Interruptionsand Voltage Sags Reduce number of faults Improve system design Mitigate disturbance Improve equipment Figure 7.1 The voltagequality problemand ways of mitigation. shortcircuits lead toequipmenttrips, but also events likecapacitorswitching or voltage sags due tomotor starting. But the largemajority of equipmenttrips will be due to short-circuit faults. Most of the reasoningto follow also applies to anyother event potentially leading to anequipmenttrip. Figure 7.1 enables us todistinguishbetween thevariousmitigation methods: • reducing thenumberof short-circuitfaults. • reducing thefault-clearingtime. • changingthe system suchthat short-circuitfaults result in less severe events at the equipmentterminalsor at thecustomerinterface. • connectingmitigation equipment between the sensitiveequipmentand the supply. • improving the immunity of the equipment. These four types ofmitigation are discussed briefly next. Power system design and mitigation equipmentat the system-equipmentinterfaceare discussed in detail in the remainderof this chapter.Power engineers have always usedcombinationof a these mitigation methodsto ensurea reliableoperationof equipment.Classically the emphasis has been on reducing the number of interruptions, while recently emphasishas shifted toward mitigating voltagesags. 7.1.2 Reducing the Number of Faults Reducingthe numberof short-circuitfaults in a systemnot only reduces the sag frequency but also the frequency of sustainedinterruptions.This is thus a very effective way of improvingthe quality of supplyand manycustomerssuggest this as the obvious solution when a voltage sag or short interruptionproblemoccurs. Unfortunately,the solution is rarely that simple. A short circuit not only leads to a voltage sag or interruption at thecustomerinterfacebut may also causedamageto utility equipmentand plant. Thereforemost utilities will alreadyhave reduced the fault frequency as far as economically feasible. Inindividual cases therecould still be room for improvement, e.g., when themajority of trips is due to faults on one or two distribution lines. Some examples of faultmitigation are: Section 7.1 • Overview of Mitigation Methods 391 • Replaceoverheadlines byundergroundcables. A largefraction of short-circuit faults is due to adverseweatheror other external influences.U nderground cables are much less affected externalphenomena by (with the obvious exception of excavation).The fault rate on anundergroundcable is anorder of magnitudelessthan for an overheadline. The effect is a bigreductionin the number of voltage sags andinterruptions. A disadvantageof underground cables isthat the repair time is much longer. • Use covered wires foroverheadline. A recentdevelopmentis the construction of overheadlines with insulatedwires. Normally the wires of anoverheadline are bareconductors.With covered wires, theconductorsare covered with a thin layer of insulatingmaterial.Even thoughthe layer is not a fullinsulation, it has proven to be efficient inreducingthe fault rate ofoverheadlines [208], [212]. Also other types ofconductorsmay reduce the fault rate [213]. • Implementa strict policyof tree trimming.Contactbetween treebranchesand wires can be animportantcauseof short-circuitfaults, especiallyduring heavy loadingof the line. Due to theheatingof the wires their sag increases, making contactwith trees more likely.N ote that this is also the timeduring which the consequences of a short circuit are most severe. • Install additional shielding wires.Installation of one or two shielding wires reduces the riskof a fault due to lightning. The shielding wires are located such that severelightning strokesare most likely to hit a shielding wire. A lightning stroke to a shielding wire isnormally conductedto earththrougha tower. • Increasethe insulation level. This generally reduces the risk short-circuit of faults. Note that many short circuits are due toovervoltagesor due to a deteriorationof the insulation. • Increasemaintenanceand inspectionfrequencies. This again generally reduces the risk of faults. If themajority of faults are due to adverse weather, as is often the case, the effect of increasedmaintenanceand inspectionis limited. that these measures may be very expensive that and One has to keep in mind, however, its costs have to be weighted againstthe consequences of the equipmenttrips. 7.1.3 Reducing the Fault-Clearing Time Reducingthe fault-clearingtime does not reduce the numberof events but only their severity. It does not doanything to reduce thenumberor duration of interruptions. Thedurationof an interruptionis determinedby the speed with which the supply is restored.Fasterfault-clearingdoes also not affect the numberof voltage sags but it can significantly limit the sagduration. The ultimate reductionin fault-clearingtime is achieved by using current-limiting fuses [6],[7]. Current-limitingfuses are able to clear a fault within one half-cycle,that so the durationof a voltage sag will rarely exceed one cycle. If we further realizethat fuses have an extremely small chanceof fail-to-trip, we have what looks like theultimate solution. The recentlyintroducedstatic circuit breaker[171], [175] also gives a faultclearing time within one half-cycle; but it is obviously much more expensive than a current-limiting fuse. No information is availableaboutthe probability of fail-to-trip. Additionally several types offault-currentlimiters have beenproposedwhich not so 392 Chapter7 • Mitigation of Interruptionsand Voltage Sags much clear the fault, but significantly reduce the fault-currentmagnitudewithin one or two cycles. One importantrestrictionof all these devices is t hat they can only be used for lowand medium-voltagesystems. Themaximumoperatingvoltage is a few tenso f kilovolts. Staticcircuit breakersshow thepotentialto be able tooperateat higher voltage levels in the future. breakerbut also But thefault-clearingtime isnot only the time needed to open the the time needed for the p rotectionto make a decision. Here we need considertwo to significantly different types of distribution networks,both shown in Fig. 7.2. The topdrawingin Fig. 7.2 shows a system with one circuit breakerprotectingthe whole feeder.The protectionrelay with thebreakerhas acertaincurrentsetting. This not exceeded for setting is suchthat it will be exceeded for any fault on the feeder, but nor for any loadingsituation.The momentthe current any fault elsewhere in the system value exceeds thesetting (thus for any fault on the feeder) the relay instantaneously gives a trip signal to thebreaker. Upon receptionof this signal, thebreakeropens within a few cycles. Typicalfault-clearingtimes in these systems are around 100 milliseconds. To limit thenumberof long interruptionsfor the customers,reclosing is used in combination with (slow) expulsion fuses in the laterals or incombination with interruptorsalong the feeder. This typeof protectionis commonly used inoverhead systems.Reducingthe fault-clearing time mainly requires a fasterbreaker.The static circuit breakeror severalof the othercurrentlimiters would be goodoptionsfor these systems. Acurrent-limitingfuse to protectthe whole feeder is notsuitableas it makes fast reclosingmore complicated.Current-limiting fuses can also not be used for the protection of the laterals because they wouldstart arcing before the mainbreaker opens. Using a fasterclearing with the main breakerenables fasterclearing in the lateralsas well. The network in the bottom drawing of Fig. 7.2 consistsof a numberof distribution substationsin cascade. To achieve selectivity, time-grading of the overcurrent relays is used. The relays furthest away from the source tripinstantaneouslyon overcurrent.When moving closer to the source, the tripping delay increases each time with typically 500 ms. In theexamplein Fig. 7.2 the delay times would be 1000ms, 500 ms, and zero(from left to right). Close to the source, fault-clearing times can be up to several seconds. These kind of systems are typically used underground in networksand in industrial distribution systems. pr~ . . overcient Figure 7.2Distribution system with one circuit breakerprotectingthe whole feeder (top) and with anumberof substations (bottom). Section 7.1 • Overviewof Mitigation Methods 393 The fault-clearingtime can be reduced by using inverse-time overcurrentrelays. For inverse-timeovercurrentrelays, the delay time decreases for increasingfault current. But even with these schemes, fault-clearingtimes above one second are possible. The varioustechniquesfor reducingthe fault-clearingtime without loosing selectivity are discussed invariouspublicationson power systemprotection,e.g., [176] and[10]. To achieve a seriousreduction in fault-clearing time one needs to reduce the grading margin, therebyallowing a certain loss of selectivity. The relay setting rules described in mostpublicationsare based onpreventingincorrecttrips. Futureprotection settings need to be based onmaximumfault-clearingtime. a A methodof translating a voltage-tolerancecurve into atime-currentcurve is described in[167]. The latter curve can be used in c ombinationwith relay curves toobtain the varioussettings. The opening timeof the downstreambreakeris an importantterm in theexpressionfor the gradingmargin. By using fasterbreakers,or evenstatic circuit breakers,the grading margin can be significantly reduced, thus leading to a significant reduction in faultclearing time. Theimpactof staticcircuit breakersmight be bigger in these systems than in the ones with onebreakerprotectingthe whole feeder. In transmissionsystems thefault-clearingtime is often determinedby transientstability constraints.These constraintsare much more strictt han the thermal constraintsin distribution systems,requiring shorterfault-clearingtimes, rarely exceeding 200ms. This also makes t hat further reductionof the fault-clearingtime becomes much more difficult. Someremainingoptions for the reductionof the fault-clearingtime in transmissionsystems are: • In some cases faster circuit breakerscould beof help. This againnot only limits the fault-clearingtime directly but it also limits thegradingmarginfor distance protection. One should realize howeverthat faster circuit breakerscould be very expensive. • A certain reductionin grading margin is probably possible. This willnot so much reduce thefault-clearingtime in normal situations,but in case the proreducingthe grading tection failsand a backuprelay has to intervene. When margin oneshouldrealizethat lossof selectivity isunacceptablein most transmission systems as it leads to the loss of twomorecomponents or at the same time. • Fasterbackupprotectionis one of the few effective meanso f reducing faultclearing time intransmissionsystems. Possible optionsare to useintertripping for distanceprotection,and breaker-failureprotection. 7.1.4 Changing the Power System By implementingchangesin the supply system, the severity of the event can be reduced. Here again the costs can become very high, especially transmissionand for subtransmissionvoltage levels. The mainmitigation methodagainstinterruptionsis the installationof redundantcomponents. Some examples of mitigation methodsespecially directedtowardvoltage sags are: • Install a generatornearthe sensitive load. The generatorswill keep the voltage up during a sag due to aremotefault. The reductionin voltagedrop is equal to the percentagecontributionof the generatorstationto the faultcurrent.In case 394 Chapter7 • Mitigation of Interruptionsand Voltage Sags a combined-heat-and-power station is planned, it is worth to consider the position of its electricalconnectionto the supply. • Split busses orsubstationsin the supplypathto limit the numberof feeders in the exposed area. • Install current-limiting coils at strategicplaces in the system to increase the "electricaldistance"to the fault. Oneshouldrealizethat this canmakethe sag worse for other customers. • Feed the bus with the sensitive equipmentfrom two or more substations.A voltage sag in onesubstationwill be mitigated by the infeed from theother substations.The moreindependentthe substationsare themorethe mitigation effect. The bestmitigation effect is by feeding from twodifferent transmission substations.Introducing the second infeed increases the numberof sags, but reduces their severity. The numberof short interruptionscan bepreventedby connectinglesscustomersto one recloser (thus, byinstalling more reclosers), or bygetting rid of the reclosure schemealtogether.Short as well as longinterruptions are considerablyreduced in frequency byinstalling additional redundancyin the system. The costs for this are only justified for large industrial and commercialcustomers.Intermediatesolutions reduce theduration of (long) interruptionsby having a levelo f redundancyavailable within a certain time. The relations betweenpower system design,interruptions,and voltage sags are discussed in detail in Sections 7.2 and 7.3.former The mainly considers methodsof reducing thedurationof an interruption,where thelatterdiscussesrelations between sag frequency and system design. 7.1.5 Installing Mitigation Equipment The mostcommonlyappliedmethodof mitigation is theinstallationof additional equipmentat the system-equipmentinterface. Recentdevelopmentspoint toward a continuedinterest in this wayof mitigation. The popularity of mitigation equipment is explained by it being the only place where the customerhascontrolover thesituation. Both changes in the supply as well improvementof as the equipmentare often completely outsideof the control of the end-user. Some examples ofmitigation equipmentare: • Uninterruptiblepower supplies (UPSs) are extremely popularfor computers: personalcomputers,central servers, andprocess-controlequipment.For the latter equipmentthe costs of a UPS are negligible comparedto the total costs. • Motor-generatorsets are oftendepictedas noisyand as needingmuch maintenance. But inindustrial environmentsnoisy equipmentand maintenanceon rotating machines arerathernormal. Large batteryblocks alsorequiremaintenance, expertise on which is much less available. • Voltage sourceconverters (VSCs) generatea sinusoidal voltage with the required magnitudeand phase, by switching a de voltage inparticularway a over the three phases. This voltage source can be used mitigatevoltage to sags and interruptions. Mitigation equipmentis discussed in detail in Section 7.4. Section 7.1 • Overviewof Mitigation Methods 395 7.1.8 Improving Equipment Immunity Improvementof equipmentimmunity is probably the most effectivesolution against equipmenttrips due to voltage sags. But it is often not suitable as a shorttime solution. A customeroften only findsout about equipmentimmunity after the equipmenthas been installed. For consumerelectronics it is veryhardfor a customerto find out about immunity of the equipmentas he is not in directc ontact with the manufacturer.Even mostadjustable-speed drives have become off-the-shelfequipment where thecustomerhas no influence on the specifications. Only large industrial equipment is custom-madefor a certain application, which enables theincorporationof voltage-tolerancerequirements. Severalimprovementoptions have been discussed in detail Chapter5. in Some specificsolutionstoward improved equipmentare: • The immunity of consumerelectronics,computers,and controlequipment(i.e., single-phase low-powerequipment)can be significantlyimproved by connecting more capacitanceto the internal de bus. This will increase the maximum sagdurationwhich can betolerated. • Single-phase low-powerequipmentcan also beimproved by using a more sophisticatedde/de converter: one which is able to operate over a wider range ofinput voltages. This will reduce the minimum voltage for which the equipmentis able tooperateproperly. • The main source ofconcernare adjustable-speed drives. We sawthat ac drives can be made totoleratesags due to single-phase and phase-to-phase faults by adding capacitanceto the de bus. To achieve toleranceagainst sags due to three-phasefaults, seriousimprovementsin the inverteror rectifier are needed. drives is very difficult because • Improving the immunity of de adjustable-speed the armaturecurrent, and thus thetorque, drops very fast. Themitigation methodwill be very muchdependenton restrictionsimposed by theapplication of the drive. • Apart from improving (power) electronicequipmentlike drives and processcontrol computersa thorough inspection of theimmunity of all contactors, relays, sensors, etc., can also significantly improve the processridethrough. • When newequipmentis installed, information about its immunity should be obtained from the manufacturer beforehand. Where possible,immunity requirementsshould be included in theequipmentspecification. For short interruptions,equipmentimmunity is very hard to achieve; for long interruptions it is impossible to achieve. The equipmentshould in so far be immune to interruptions, that no damageis caused and nodangeroussituation arises. This is especiallyimportantwhen consideringa completeinstallation. 7.1.7 Different Events and Mitigation Methods Figure 7.3 shows themagnitudeand duration of voltage sags andinterruptions For differenteventsdifferent mitigation strategies resulting from various system events. apply. 396 Chapter7 • Mitigation of Interruptionsand Voltage Sags 100% 800/0 ] .~ ~ ~ 50% Local MVnetworks Interruptions 0% - - - - - -....- - - - - -.....- - - - - - - - - - - - - 0.1 s 1s Duration Figure 7.3 Overviewof sags andinterruptions. • Sags due toshort-circuitfaults in thetransmissionand subtransmissionsystem are characterizedby a short duration, typically up to lOOms. These sags are very hard to mitigate at the source and also improvementsin the system are seldom feasible. The only way of mitigating these sags is by improvementof the equipmentor, where thisturnsout to be unfeasible,installingmitigation equipment. For low-powerequipmenta UPS is astraightforwardsolution; for highpower equipmentand for completeinstallationsseveralcompetingtools are emerging. • As we saw in Section 7.1.3, the duration of sags due todistribution system faults dependson the typeof protectionused,rangingfrom lessthana cycle for current-limiting fuses up to several seconds for overcurrentrelays in underground or industrial distribution systems. The long sag duration makesthat equipmentcan also trip due to faults on distribution feeders fed fromanother HV/MV substation.For deep long-duration sags,equipmentimprovement becomes more difficulta nd systemimprovementeasier. Thelatter could well become thepreferredsolution, althougha critical assessment of the various options is certainly needed.Reducingthe fault-clearing time and alternative designconfigurationsshould be considered. • Sags due to faults in remotedistributionsystems and sags due motorstarting to should not lead to equipmenttripping for sags down to85%. If there are problemsthe equipmentneeds to be improved. Ifequipmenttrips occur for long-durationsags in the70%-80% magnituderange, improvementsin the system have to be consideredas anoption. improving the equipmentimmu• For interruptions,especially the longer ones, nity is no longer feasible. System improvementsor a UPS incombinationwith an emergencygeneratorare possiblesolutions here. Somealternativesare presentedin Sections 7.2 and 7.3. Section 7.2 • Power System D esign-Redundancy ThroughSwitching 397 7.2 POWER SYSTEM DESIGN-REDUNDANCY THROUGH SWITCHING This and the next section discuss some of the relationsbetweenstructureandoperation of power systemsand the numberof voltage sags andinterruptions.The reductionof interruptionfrequency is animportantpart of distributionsystem design and as such it is treatedin detail in a numberof books and in many papers.Often cited books on distribution system design are"Electricity Distribution Network Design" by Lakervi and Holmes [114] and "Electric Power Distribution SystemEngineering" by Gonen [164]. Other publicationstreatingthis subject inpart are [23], [115], [116], [165], [209], [214]. Many case studies have appearedover the years in conferences and transactions of the IEEE Industry ApplicationsSociety and to a lesser degree in the publicationsof the PowerEngineeringSociety andof the Institute of Electrical Engineers. 7.2.1 Types of Redundancy The structureof the distribution system has a big influence on the numberand durationof the interruptionsexperienced by thecustomer.The influence of thetransmission system ismuch smaller becauseof the high redundancyused. Interruptions originating in the distribution system affect lesscustomersat a time, but any given customerhas a muchhigherchanceof experiencing adistribution-originatedinterrupone. The largeimpact of interruptionsoriginating tion than a transmission-originated in the transmissionsystemmakesthat they shouldbe avoided atalmostany cost. Hence the high reliability of transmissionsystems. Number and duration of interruptionsis determinedby the amount of redundancy presentand the speed with which the redundancycan be made available. Table of redundancyand thecorrespondingdurationof the interruption. 7.1 gives some types Whetherthe supply to a certainload is redundantdepends on the time scale at which one islooking. In otherwords, on themaximuminterruptiondurationwhich the load cantolerate. When apowersystemcomponent,e.g., atransformer,fails it needs to berepaired or its function takenover byanothercomponentbefore the supply can be restored.In casethereis no redundanttransformeravailable, the faultedtransformerneeds to be repairedor a spareone has to beb roughtin. The repairor replacementprocess can take severalhours or, especially withpower transformers,even days up to weeks. Repair times of up to onemonth have beenreported. TABLE 7.1 Various Types of Redundancyin Power System Design Duration of Interruption No redundancy Redundancythroughswitching - Local manualswitching - Remotemanualswitching - Automatic switching - Solid stateswitching Redundancythrough parallel operation Typical Applications Hours throughdays Low voltage in rural areas 1 hour and more 5 to 20minutes Low voltage anddistribution Industrial systems, future public distribution Industrial systems Futureindustrial systems Transmissionsystems, industrial systems I to 60 seconds I cycle and less Voltage sag only 398 Chapter7 • Mitigation of Interruptionsand Voltage Sags In most cases the supply is n ot restored through repair or replacementbut by switching from the faulted supply to backupsupply. a The speed with which this takes place dependson the type of switching used. The various types will be discussed in detail in theremainderof this section. A smoothtransitionwithout any interruptiontakes place when two c omponents are operatedin parallel. This will however notmitigate the voltage sag due to the fault which often precedes the interruption.Various optionsand their effect on voltage sags are discussed in Section 7.3. 7.2.2 Automatic Recloslng Automatic reclosing was discussed in detail Chapter3. in Automatic reclosing after a short-circuitfault reduces thenumberof long interruptionsby changingthem into short interruptions.Permanentfaults still lead to longinterruptions,but on overhead distribution lines this is lessthan 25% of the total numberof interruptions.We saw in Chapter3 that the disadvantageof the commonly usedmethod of automatic reclosing isthat more customersare affected by a fault. A long i nterruptionfor part of a feeder ischangedinto a shortinterruptionfor the whole feeder. This is not inherentto automatic reclosing, but to themethod of fuse saving used. If all fuses would be replaced by reclosers, the numberof shortinterruptionswould be significantly reduced. A customerwould only experience ashort interruption for what would have been a long interruptionwithout reclosing. This wouldof course make the supply more expensive, which is not alwaysacceptablefor remote rural areas. 7.2.3 Normally Open Points The simplest radial system possible is shown in Fig. 7.4: number a of feeders originate from a distribution substation.When a fault occurs on one o f the feeders, the fuse will clear it, leading to an interruptionfor all customersfed from this feeder. The supply can only berestoredafter the faultedcomponenthas ·beenrepaired or replaced. Such systems can be found rural in low-voltage anddistribution systems with overheadfeeders.Protection is through fuses in thelow-voltage substations. Repair of a faulted feeder (orreplacemento f a blown fuse) can take several hours, repair or replacemento f a transformerseveral days. As the feeders are overheadthey are prone to weather influences;stormsare especiallynotoriousfor it can take days before all feeders have been repaired. A commonlyusedmethodto reduce thedurationof an interruptionis to install a normally open switch, often called"tie switch." An example is shown in Fig. 7.5. Lateral Figure 7.4 Power systemwithout redundancy. 399 Section 7.2 • Power System D esign-Redundancy ThroughSwitching 33/11 kV n/o switch ----: ~ ntc¥nto 0/0 11kvt400~ Figure 7.5 Distribution system with redundancy through manual switching. The system is stilloperatedradially; this prevents the fault level from getting too high and enables the use of (cheap)overcurrentprotection.If a fault occurs it is cleared by a circuitbreakerin the substation.The faulted section is removed, the normallyopen switch is closed, and the supply can restored.The be varioussteps in therestorationof the supply are shown in Fig. 7.6. (a) Normaloperation I Nonnallyopen point T$ $ $/' $ $ (b) Fault clearing (c) Interruption ---r- Interruptionfor these customers ____T (d) Isolatingthe fault ---r- n---~$ $ (e) Restoringthe supply Figure 7.6 Restoration procedure in a distribution system with normally open points. (a) Normal operation, (b) fault clearing, (c) interruption, (d) isolating the fault, (e) restoring the supply. 400 Chapter7 • Mitigation of Interruptionsand Voltage Sags In normal operation(a) the feeder isoperatedradially. A normally open switch is located between this feeder and anotherfeeder,preferablyfed from anothersubstation. When a fault occurs (b) the breakerprotectingthe feeder opens leading to an interruption for all customersfed from this feeder (c).After the fault is located, it is isolated from the healthypartsof the feeder (d) and the supply to these healthy partsis restored by closing the circuitbreakerand thenormally open switch (e).Repairof the feeder only startsafter the supply has been restored. . This procedurelimits the durationof an interruptionto typically one or two hours in case the switching is done locally (i.e., somebodyhas to go to the switches to open or close them). If faultlocation and switching is done remotely (e.g., in a regional control center) the supply can be restoredin several minutes.Locatingthe fault may take longer than theactualswitching. Especially in case of protectionor signaling failure, locating the fault can take a long time. Various techniques are in use for identifying the faulted section of the feeder. More precise fault location,needed for repair, can be done afterwards. The type of operationshown in Figs. 7.5 and 7.6 is very commonly used in undergroundlow-voltage and medium-voltagedistribution systems. Therepair of undergroundcables can take several days that so system operationlike in Fig. 7.4 becomes totallyunacceptable.Similar restorationtechniquesare in use for mediumvoltage overheaddistribution, especially in the moreurbanpartsof the network. The high costs for signalingequipmentand communicationlinks make remote switching only suitable for higher voltages andin industrialdistributionsystems. Whencustomer demands forshorterdurationsof interruptionscontinueto increase, remote signaling and switching will find its way into publicdistribution systems as well. The additional costs for the system in Fig. 7.5 are not only switching, signaling and communicationequipment.The feeder has to be dimensionedsuch that it can handle the extra load. Also the voltage drop over the, nowpotentially twice as long, feeder should not exceed the margins. Roughlyspeakingthe feeder can only feed half as much load. This will increase the n umberof substationsand thus increase the costs. 7.2.4 Load Transfer A commonly used and very effective way of mitigating interruptionsis transferring the load from theinterruptedsupply to ahealthysupply. Load transferdoes not affect thenumberof interruptions,but it can significantly reduce thed uration of an interruption. Load transfercan bedone automaticallyor manually; automatictransfer is faster and therefore more effective in reducing interruption the duration. An example of manual switching was discussed before. Here we will concentrateon automatictransfer of load, although the proposedschemes are equally suitable for manualtransfer. 7.2.4.1 Maximum Transfer Time. An importantcriterion in the designof any transfer scheme is themaximum interruption duration that can betolerated by the equipment.The transfershould take place within this time, otherwise the load would trip anyway. In anindustrialenvironmentthe rule for themaximum transfertime is relatively simple: theshort interruptionof the voltageshould not lead to aninterruption of plant operation.An example is apapermill, where the interruption should not lead totripping of the papermachine. Below acertain interruptionduration the machine will not trip, for interruptionslasting longer it will trip. The choice is not always that straightforward,e.g., with lighting of public buildings. A general rule is Section 7.2 • Power System D esign-Redundancy ThroughSwitching 401 that one should in all cases choose taransfer time such that the transfer does not unacceptableis lead to unacceptableconsequences.W hat should be considered as simply part of the decision process. In practice the load of a power system is not constant,and decisionsabouttransfertime may have to be revised several years later because more sensitive equipmentis being used, as, e.g., described[163]. in 7.2.4.2 Mechanical LoadTransfer. Most transfer schemes use a mechanical switch or circuit breakerto transferfrom one supplypoint to another.A typical configuration as used inindustrial distribution systems is shown in Fig. 7.7. Two transformers eachsupply part of the load. If oneof them fails, thenormally open switch is closed and thetotal load is fed from onetransformer.Each transformershould be able to supply thetotal load or a load shedding scheme should be in place. When a short circuit occurs close to thetransfer switch, it is essentialt hat the load is not transferred before the fault has been cleared: a so-called "break-before-make" scheme. A"make-before-break"scheme would spread the fault to the healthy supply leading to possibleintervention by the protectionin both feeders. In case one transformer is taken out of operation for maintenance,a (manual) make-before-break scheme can be used. This reduces the risk of a interruptiondue long to failure of the transfer switch. During the parallel operation,a short circuit could lead to serious switchgeardamage. The advantagesof this schemecomparedto parallel operationare that the protection is simpler andthat the fault currentis lower. As long as the load can toleratethe shortinterruptionduring load transfer,the reliability of the supply is similar tothat of parallel operation.As we saw in Section 2.8, load interruptionsfor a transferscheme are mainly due to failureof the transferswitch and due to any kind of common-mode effect in the two supplies. In an industrial environment,maintenanceand excavation activities could seriously effect the supply reliability. 66 kV substation Figure 7.7 Industrial power system with redundancythroughautomaticswitching. Variousindustrialload 7.2.4.3 Transfer of Motor Load. A problem with automaticswitching is the presenceof large numbersof induction motors in most industrial systems. When the supply is interrupted,the remaining airgap flux generates a voltage over the motor terminals. This voltage decays inmagnitudeand in frequency. The switching has to take placeeither very fast (before themotor voltage has shifted much in phase comparedto the system voltage) or very slow (after the motor voltage has become zero). As the first option is expensive, the second onenormally is used. 402 Chapter7 • Mitigation of Interruptionsand Voltage Sags The airgap field in a induction motor decayswith a certaintime constantwhich varies from less than one cycle for small motors up to about 100 ms for large motors. The time constantwith which the motor slows down is much larger: typically between one and five seconds. The momentthe motor is reconnected,the sourcevoltagewill normally not be in phasewith the motor voltage. In case they are in opposite phasea large current will flow. This currentcan be morethantwice thestartingcurrentof the motor. It caneasily damagethe motor or lead to tripping of the motor by the overcurrentprotection. The inducedvoltage has the following form: E = isinro! (7.1) with co the angularspeedof the motor, which decaysexponentially: (J) = Wo(1 - e-f.;) (7.2) and E dependenton the frequency and the exponentially decaying rotor current. Assume for simplicity that the magnitudeof the induced voltage remains constant and considera linear decayin motor speed: (J) ~ (J)O(1 - L) (7.3) This gives for the voltage at the motor terminals: E(t) = Sin(Wo(1 - L)r) = sin(Wot _ ~~2) (7.4) The secondterm underthe sinefunction is the phasedifferencebetweenthe supplyand the induced voltage. As long as this phasedifference is less than 60°, the voltage difference betweenthe sourceand the motor is less than 1 pu. A phasedifference of 60° (1) is reachedfor ~ t=y6KJ (7.5) For a mechanicaltime constantT:m = 1 secand a frequencyof 10 = 50 Hz an angular differenceof 60° is reachedafter 58 ms. In thecalculationit is assumedthat the motor has not slowed down during the fault. If this is also considered,the value of 60° is reachedfaster.Only very fast transferschemesareableto switch within this shorttime. A secondchanceat closing the transferswitch is when the angulardifferenceis about 360° (i.e., sourceand motor are in phaseagain). This takesplacefor & t=Yh (7.6) which is 140IDS in the aboveexample.Theseso-calledsynchronoustransferschemesare very expensiveand may still leadtotransfertimes above 100 ms. In most cases asynchronoustransfer is used where the transfer switch is only closed after the induced voltagehassufficiently decayed,leadingto transfertimes aroundonesecondor longer. For synchronousmachinesthe airgapfield decayswith the sametime 'constantas the motor speed,so that the terminal voltagemay be presentfor severalseconds.In a systemwith a large fraction of synchronousmotor load, synchronoustransferbecomes 403 Section 7.2 • Power System D esign-Redundancy ThroughSwitching more attractive. Note that asynchronoustransferwill always lead to lossof the synchronousmotor load. 7.2.4.4 Primary and Secondary Selective Supplies. Figures 7.8 and 7.9 show two ways of providing a medium-voltagecustomerwith a reliable supply. In a primary selective system (Fig. 7.8) the transfer takes place on theprimary side of the but there is a transformer.A secondaryselective system (Fig. 7.9) is more expensive much reduced chance of very long interruptionsdue to transformerfailure. A numerical analysisof such atransferscheme is given in Section 2.8. The actual transferis identical to thetransferin the industrial supply shown in Fig. 7.7: the load istransferredfrom the faulted to thehealthyfeeder as soon as possible after fault clearing. With aprimary selective supply amake-before-break scheme would directly connecttwo feeders. It is unlikelythat the utility allows this. Thetransfertakes place behind atransformerwith the secondaryselective supply. The possible consequencesof a make-before-breakscheme are less severe for the utility. With the design ofprimary and secondaryselective supplies, it is again very important to determinethe tolerance of the load to s hort interruptions.The choice for a certaintype of transferscheme should depend on this tolerance. Medium-voltage substation1 Medium-voltage substation2 . -Automatic transfer switch Industrial customer Figure 7.8 Primary selective supply. Medium-voltage substation1 Figure 7.9 Secondaryselective supply. Medium-voltage substation2 404 Chapter7 • Mitigation of Interruptionsand Voltage Sags 7.2.4.5 Static Transfer Switches.Static transfer switches have been used already for several years inlow-voltage applications,e.g., in uninterruptablepower supplies to be discussed in Section 7.4. Currently, static transfer switches are also available for medium voltages [166], [171], [173]. Astatic transfer switch consistsof two pairs of anti-parallelthyristors as shown in Fig. 7.10.During normal operation, thyristor pair I is continuouslyfired, and thus conductingthe load current. Thyristor pair II is not fired. In termsof switches,thyristor pair I behaves like a closed switch, pair II like an open switch. When adisturbanceis detectedon thenormalsupply,the firing of thyristor pair I is disabled and the firingo f thyristor pair II enabled.The effectof this is that the load currentcommutatesto the backupsupply within half a cycleof detectingthe disturbance.Actual transfertimes are lessthan 4ms [166]. The three small figures show the voltages in a stylized way. In reality voltagesare sinusoidal,but the principle remains interruptionat time I. the same.P oint A experiences adrop in voltage due to a sag or This drop in voltage is alsoexperiencedby the load at point C. We assumethat the backupsupply does not experience this. At time 2, the disturbanceis detected,the firing of thyristor pair I is disabled,andthe firing of thyristorpair II enabled.At that moment the commutationof the current from the normal supply to the backupsupply starts. During commutationthe voltage atpoints A, B, and C is equal asboth thyristor pairs are conducting.This voltage issomewherein between the twosupplyvoltages. At time 3 the commutationis complete(the thyristor currentin pair I extinguisheson the first zero crossingafter the firing beingdisabled)and thevoltageat BandC comes back to its normal value. Note that the current through the thyristors never exceeds the load current,also not for a fault close to thestatic switch. A static transfer switch can be used in any o f the transfer schemes discussed before: industrial distribution, primary selective,secondaryselective. The speed with which the transfer takes place makes .the distinction betweensynchronizedand nonsynchronizedtransferno longer relevant. Load transfer by a static transferswitch is always synchronized. To ensure very fasttransfer,any voltage sag orinterruptionin the normal supply shouldbedetectedvery fast. Thecommutationof the currentfrom onethyristorpair to the other takes lessthan half a cycle sothat we need adisturbancedetectionwhich is equally fast. Static transfer schemes can use the missing voltage or a half-cycle rms value to detect a sag or interruption. For the missingvoltage detectionscheme, the Backup supply Normal supply II ~'----Ct---+---fc~ 1 bL= 123 B Dc 23 Figure 7.10 Constructionand principle of operationof a static transferswitch. Section 7.3 • Power System D esign-Redundancy ThroughParallelOperation 405 actual voltage iscomparedon a sample-by-samplebasis with theoutput voltage of a phase-locked-loop(PLL). When the deviation becomes too large for too long, the transferis initiated. With the rms scheme,transferis initiated when the rms voltage drops below acertain threshold. The latter scheme is slower as it will lead to an additional half-cycle delay, but it has a smaller chanceincorrect of transfer. A transferscheme using a static transferswitch enables thed urationof a voltage sag to be limited tohalf a cycle by switching to thebackupsupply when a sag occurs in the normalsupply. For sensitive load, astatictransferswitch might bepreferableabove parallel operation.Voltage sagsoriginating in the transmissionsystemcannotbe mitigated by such atransfer scheme as the voltage sag is likely to be presentboth in supplies; but for sags originating in the distribution system the statictransferscheme is very effective. The mainlimitations are theunknownreliability of the transferswitch and the degree in which the two sources independent. are The notch due to loadtransfercould be aconcern,especially for the load on the healthy feeder. Whencomparingstatic transfer with parallel operation,a notch of millisecond duration replaces the voltage sags of several cyclesduration. When comparingwith the mechanicaltransferscheme, thenotchin the backupsupply constitutes a deteriorationof the voltagequality, albeit not a severedeterioration.Some utilities do not allow parallel operation of feeders, requiring a so-called"break-before-make" transfer scheme. Thestatic transfer switch as described here is essentially"makea before-break"scheme. It isimpossibleto predicthow strict utilities will apply this rule on a sub-cycle timescale. As an alternativeone could enable firing ofthyristor pair II only after the current through pair I has extinguished. Such b areak-before-make scheme willobviously make the transferslower and couldactually make the voltage transientin the healthy supplymore severe. A final potential problem with static transferis that the normal supply and the healthy supply are not exactly in phase. The phase-angledifference could lead to a small 0 phase-anglejump at the loadterminals.Values up to 6 have beenreported.As long as there are nostandardson equipmenttoleranceto phase-angle jumps,it is hardto assess the impact of this. The successful use of medium-voltagestatic transferswitches on a numberof sitesindicatesthat the equipmentis able totoleratethe transient. 7.3 POWI!R SYSTEM DI!SIGN-REDUNDANCY THROUGH PARALLI!L OPERATION 7.3.1 Parallel and Loop Systems Figure 7.11 shows a publicdistribution network with a higher nominal voltage than the one in Fig. 7.5. It serves more customersso it is worth to invest more in reliability. Partof the system is stillo peratedin a radial way withnormally open points. These are serving less densely populatedareas, and areas with less industrial activity. The majority of the 33 kV system isoperatedwith parallel feeders. Bothpathscarry part of the load. If onepathfails, the otherpathtakes over the supply instantaneously. Also the 33/1I kV transformerand the 33 kV substationbus areoperatedin parallel. The rating of eachcomponentis such that the load can be fully supplied if one componentfails. of parallel operation:two feeders in parallel and a We see in Fig. 7.11 two types loop system. Inboth cases there is single redundancy.The loop system is significantly of transformerconnections.But the voltagecontrol of loop cheaper, especially in case systems is more difficult, and the various loads are moreprone to disturbing each 406 Chapter7 • Mitigation of Interruptionsand Voltage Sags 33 kV loop 6.6kV llkV Another33kV network ~----t n/o Figure 7.11Distribution network with redundancythroughparallel operation. other'ssupply. Loop systems arethereforelesspopularin industrial systems,although somesmallerloops (three or four busses) are used to limit numberof the transformers. 7.3.1.1 Design Criteria for Parallel and Loop Systems.The design of parallel (n - 1) criterion, which statesthat the and loop systems is based on the so-called system consisting of n componentsshould be able to operate with only (n - 1) componentsin operation, thus with onecomponentout of operation. This should hold for anyonecomponentout of operation. The (n - 1) criterion is very commonly used inpower system design. It enables a high reliability without the need for stochasticassessment. In some cases (large transmissionsystems,generatorschea duling), (n - 2) or (n - 3) criteria are used. As we saw in Section 2.8,thorough trustfully use assessmento f all "common-modefailures" is needed before one can such ahigh-redundancydesign criterion. Here we will concentrateon the (n - 1) criterion, also referred to as "single redundancy."This criterion is very commonly used in the designof industrial medium-voltagedistribution as well as in publicsubtransmissionsystems. The main design rule is that no single eventshould lead to aninterruption of the supply to any of the customers.In an industrial environmentthe wording is somewhatdifferent: no single eventshouldlead to aproductionstop for any of the plants. How these basic rules are further developeddependson the kind of system. A list of things that have to be consideredis given. 1. The obviousfirst rule is that no componentoutageshouldlead to an interruption. Thereshouldthus be analternatepath for the power flowthrough any component. 2. Not only shouldthere be analternatepathfor the power flow, thisalternate path shouldalso not lead to anoverloadsituation. In the public supply the Section7.3 • Power SystemDesign-Redundancy ThroughParallel Operation 3. 4. 5. 6. 407 load demandvaries significantlyduring the day. Acertainamountof overload can betoleratedfor a few hours. Inindustrial systems the load is typically more constant,so that any overloadwould bepermanent.However in industrialsystems it is often easier to reduce the load on a time scale hours of or to start on-site generation. The power systemprotectionshouldbe able to clear any faultwithout causing an interruptionfor any of the customers. This requiresmore complicated protectionsystemsthan for radial-operatednetworks. Theseprotectionsystems require additional voltage transformersand/or communicationlinks. Also thenumberof circuit breakersincreases: two circuitbreakersare needed for eachconnectionbetween twosubstationsin a looped orparallel system. Voltage fluctuationsdue to rapid loadfluctuations and voltage sags due to motor startingshouldbe within limits for anyonecomponentout of operation. This translatesinto a minimum fault level for any load bus. The switchgearratingdictatesa maximumfault level for the system with allcomponents in operation.The optimal use of this margin betweenmaximum and minimum fault levels is oneof the main challenges in the design industrial of medium-voltagedistribution systems. The electromechanicaltransientdue to ashort circuit in the system with all componentsin operationshould not lead to loss of any load. In industrial systems with a large fraction of inductionmotor load, it must beensuredthat thesemotorsare able to re-acellerate after the fault. The voltage sag due to any fault in the system shouldnot lead to tripping of essentialload with any of the customers. From this list it becomesobviousthat the designof a parallel or loop system could be a serious challenge. But the reliability demandsof largeindustrialplantsare suchthat no radial system could deliver this. The increased reliability is more than worth the higher installationcosts and costso f operation. 7.3.1.2 Voltage Sags in Parallel and Loop Systems. Considerthe system shown in Fig. 7.12: three supplyalternativesfor an industrial plant. In theradial system on the left, theplant is fed through a 25 km overheadline; two more overheadlines originate from the samesubstation,each with a lengthof 100km. In thecenterfigure the plant is fed from a loop bymaking a connectionto the nearestfeeder. In the third alternativeon the right aseparateoverheadline has beenconstructedin parallel with the existing 25 km line. Themagnitudeof voltage sags due to faults in this system is shown in Fig. 7.13. The calculationsneeded toobtain this figure are discussed in Section 4.2.4. We will use Fig. 7.13 to assessnumberof the voltage sags experiencedby the plant for the three designalternatives. For the radial system, theplant will experienceinterruptionsdue to faults on kmline. The relation 25 km of overheadline, and voltage sags due to faults on 200 of between sagmagnitudeand distanceto the fault isaccordingto the dottedline in Fig. 7.13. Improving the voltage toleranceof the equipmentwill significantly reduce the exposed length. The exposed length for radial operation is given in Table 7.2 for different equipmentvoltage tolerances. By simplyadding the exposed lengths, it is is assumedthat the impact of interruptionsand voltage sags is the same, whichnot always the case. Even if the process trips due to a voltage sag, it mightrequire still power from the supply for a safes hutdownof the plant. 408 Chapter7 • Mitigation of Interruptionsand Voltage Sags Substation II Substation III II ] ] an an N Substation III II ] III an N N X N ] .e B § § 0 ~ lOOkm 100km 100km Figure 7.12 Threesupply alternativesfor an industrial plant: radial (left), looped (center),and parallel (right). 0.8 a .8 -8 a .~ 0.6 m 0.4 f , : f/} I .- I ........ ., " , .... 0.2 :/ :t :' \ \ :' Figure 7.13 Sag magnitudeas a function of fault position for faults in the systemshown \ in Fig. 7.12. Solid line:faults on the 25 km , branchof a 125 km loop; dashedline: faults 100 on the 100km branchof a 125km loop; dotted line: faults on aradial feeder. \ 20 40 60 80 Fault positionin kilometers TABLE 7.2 ExposedLengthfor VariousEquipmentVoltageTolerancesfor Radial Operationin Fig. 7.12 ExposedLength VoltageTolerance Trips on Trips on Trips on Trips on interruptionsonly sags below20% sags below50% sags below900/0 FeederI 25 25 25 25 km km km km FeederII FeederIII 3km 12 km 100 km 3 km 12 km 100 km Total 25 km 31km 45 km 225 km The calculationshave beenrepeatedfor loopedoperationas in thecenterdrawing in Fig. 7.12, resulting in the values shown in Table 7.3. Only equipmentimmuneto for all voltage sags will thenumberof equipmenttrips be lessthan for the radial supply. The exposed length for the variousequipmentvoltagetolerancesis given in Table 7.4 for parallel operation. For a voltage toleranceof 50% this option is preferable above loopedoperation.Knowledgeof the various costs involved is needed to decide if this reductionin trip frequency isworth the investment. Section 7.3 • Power System D esign-Redundancy Through ParallelOperation 409 TABLE 7.3 ExposedLength for Various Equipment Voltage Tolerances for Looped Operation in Fig. 7.12 Exposed Length VoltageTolerance Trips on interruptions only 200/0 Trips on sags below Trips on sags below 50°A» Trips on sags below 90°A» Feeder I Feeder II Feeder III Total 25 km 25 km 25 km 14km 100 km 100 km 3 km 12 km 100 km 42 km 137 km 225 km TABLE 7.4 Exposed Length for Various Equipment Voltage Tolerances for Parallel Operation in Fig. 7.12 Exposed Length VoltageTolerance Trips on interruptions only 20% Trips on sags below 50°A» Trips on sags below 90% Trips on sags below Feeder I 50 km 50 km 50 km Feeder II 3 km 12 km 100 km Feeder III Total 3 km 12 km 100 km 56 km 74 km 250 km 7.3.2 Spot Networks The basiccharacteristicof a spot network isthat a bus is fed from two or more different busses at a higher voltage level. In the previous section we looked at parallel and loop systems originatingat the same bus or at two busses connectedby a normally closed breaker. When a bus is fed from two different busses, the same design problems - 1) criterion remains the have to be solved as for parallel and loop systems. (n The underlying rule. Themagnitudeof voltage sags is significantly lower for spot networks, comparedto parallel networks. Also thenumber of interruptionswill be somewhat lower, but that difference will not be significant as the numberis already low. 7.3.2.1 Magnitudeof Voltage Sags. Considerthe system in Fig. 7.14: the busbar with the sensitive load is fed from two different busbarsat a higher voltage level, ZSI and ZS2 are source impedances at the higher voltage level, Ztt and Zt2 are transformer impedances, z is the feeder impedance per unit length, {, the distance between bus I and the fault. The two busses can be in the same substationor in two different substations.The reliability in thelatter case is likely to besomewhathigher, although it is hard to exactlyquantify this difference. Consider a fault on a feeder originatingfrom bus I at a distance£, from the bus. The magnitudeof the voltage at bus I is found from the voltage-dividerequation (7.7) where we neglect the effect of the second source on the voltage at bus I. This is a reasonableassumptionas the impedanceof the two transformersin series will be much higher than the source impedanceat bus I. If we assume the two sources to be 410 Chapter7 • Mitigation of Interruptionsand Voltage Sags ZSl BusI-..........- . - - - ..........--BusIl Figure 7.14 Busbarfed from two different busbarsat a higher voltage level. Fault Sensitive load completelyindependent,so that the sourcevoltageat bus II doesnot drop due to the fault, the voltageat the load bus isfound from v.wg = VI + Z II + ~tl 12 + Z (1 - VI) (7.8) SI We simplify the expressionssomewhatto be betterable to assess the effect of the double supply. Assumethat z == ZSI, which is alwayspossibleby choosingthe properdistance Z,t and ZS2 « 2 ,2, The voltageat the unit. Assumealso that Z,1 = Zt2 and that ZSl load bus is, undertheseassumptions: « t: V sag - +12 .c + 1 (7.9) and at bus I: c VI = £+ 1 (7.10) For a radially operatedsystem,without a connectionto bus II the voltageat the load bus is equal to the voltage at bus I, given by (7.10).Figure 7.15 comparesthe voltage magnitudeat the load bus for the two designalternatives.It is immediately obvious that the secondinfeed significantly reducesthe voltagedrop. The deepestsag will have a magnitudeof 50% of nominal. Here it is assumedthat the secondtransformer has the sameimpedanceas the first one. Inpractice this translatesto them having the samerating. If the secondtransformerhas asmaller rating, its impedance will typically be higher and the voltagesag will bedeeper. From the expressionsfor the voltageversusdistance,we can obtain expressions for the critical distance,like in Section6.5. For the radial systemwe obtain the same expressionas before: (7.11) For the systemwith doubleinfeed, we obtain V-! Lcrit = 1 _ ~, V ~ 0.5 (7.12) 411 Section 7.3 • Power System D esign-Redundancy Through ParallelOperation 0.8 a / .S ~ 0.6 " .a " ' .~ 8 0.4 ~ r:J) 0.2 ·Figure 7.15 Sagmagnitudeas adistanceto the fault, without (solid line) and with (dashed line) a connectionto a secondsubstationat a higher voltage level. 2 10 4 6 8 Distance to fault (arbitr. units) 10,..-----y------r-----r-----,..-..,..,....----, I I , , I I I , I I,, , , i ,, ,,' , , , , ,, , I I I I I .' .' I I I I Figure 7.16 Exposed length for radial supply (solid line) and for aconnectionto a second substationat a higher voltage level: same numberof feeders from bothsubstations (dashed line); twice as many feeders from the secondsubstation(dash-dotline). , , I " ,II / ' ". ,," "."" ., 0.2 0.4 ".:'" " 0.6 0.8 Sag magnitude in pu and L,crit = 0 for V < 0.5. From the critical distancethe exposed length can be calculated, resultingin Fig. 7.16. Themain featureis that the exposed length is zero in case i mportant the equipmentcan toleratea sag down to50% of nominal. This could be an pieceof informationin decidingaboutthe voltage-tolerancerequirementsfor the load. For higher critical voltages(more sensitiveequipment)the exposed lengthdependson the numberof feedersoriginatingfrom the two busses. Let INbe thenumberof feeders fed from busI and N 2 the numberof feeders fed from bus II. The total exposed length for the load fed from both feeders is found from (7.13) for the spot network and (7.14) double infeed is for the radial system. In case N I = N 2, the exposed length for the always lessthan for single infeed. WhenN2 > N, the double-infeedoption becomes lessattractivewhen theequipmentbecomes too sensitive. In the example shown by a 412 Chapter7 • Mitigation of Interruptionsand Voltage Sags dash-dottedline in Fig. 7.16, N2 = 2N}, the cross-overpoint is at 75% remaining voltage. It is important to realize that the second bus does not have to beanother at substation.By operatinga substationwith two bussesconnectedby a normally open breaker,the same effect is achieved. Suchconfigurationmight a not be feasible in the public supply as it reduces the reliability for customersfed from aradial feeder. But for industrial distribution systems it is an easy methodof reducing the sagmagnitude. 7.3.2.2 Public Low- Voltage Systems. An example of a low-voltagespotnetwork is shown in Fig. 7.17. A low-voltage bus is fed by two or more feeders originating from different substationsor from busses notoperatedin parallel. Theprotectionof the feeders takes place by overcurrentprotectionin the medium-voltagesubstations and by a sensitive reverse-power relay (the "network protector") at the low-voltage bus. In public systems it is not always possible to supply from different substations. This will still lead to a low numberof interruptions,but the numberof voltage sags will not be reduced, and will even be somewhatincreased due to faults on the parallel feeders. The system shown in Fig. 7.18 is also referred to as spotnetwork;otherscall a it a distributedgrid network, or simply asecondarynetwork. Suchnetworksare common in the downtown areas of large cities (NewYork, Chicago, London, Berlin). Distributedlow-voltagenetworkswith an operatingvoltage of 120 V typically use no protection against low-voltage faults. The faultcurrent is so high that every short circuit will burn itself free in a short time. For voltage levels of 200 V and higher, expulsionfuses orcurrent-limitingfuses are used. A networkprotectoris againinstalled on secondaryside of everytransformerto preventbackfeed from the low-voltage network into medium-voltagefaults. Thesedistributedlow-voltage networksoffer a high reliability. Outageson any of thedistribution feeders willnot be noticed by thecustomers. For the mitigation of sags it is essentialthat the feedersoriginate in different substations,otherwise thenumberof sags will even be increased. Any fault in the lowvoltage network will cause a sag for allcustomerssuppliedfrom this network.The use of current-limitingfuses will significantly reduce the sag duration,so that these sags are not of much concern. T Oifferent MV substations SecondaryLVfeeders Figure 7.17Low-voltage spot network. Section 7.3 • Power System D esign-Redundancy ThroughParallelOperation 413 Substation2 Substation 1 MVILV transformers Low-voltage network Substation 3 Figure 7.18 Low-voltagedistributedgrid. A comparisonof different designoptionsfor the public supply is given in[165]. Both stochastic predictiontechniques and site monitoringwere used in thecomparison. Spot networks turned out to have much less interruptionsthan any other network configuration.Looking at the sag frequency, undergroundnetworksperformedbetter of the numberof sags. The supply thanoverheadnetworks, experiencing only one third configurationhad onlyminor effect on the sag frequency. 7.3.2.3 Industrial Medium-VoltageSystems. In industrial systems spot networks are in use at almost any voltage level; the feeders are typically protectedby using differential protection. A configuration with three voltage levels is shown in Fig. 7.19. At each voltage level, a bus is fed from two different busses at a higher voltage level. These two busses might well be in the same substation,as long as they are not operatedin parallel. The effect of this supply configurationhas been discussed in Figs. 4.37, 4.38, and 4.39 in Section 4.2.4. By opening breakerin the the substationat an intermediatevoltage level, thuschangingfrom parallel operationto a spot supply, the lnfeedfrom transmission network --.-.........---.......- Medium-voltageload Figure 7.19 Industrial spot network. Low-voltage load 414 Chapter7 • Mitigation of Interruptionsand Voltage Sags magnitudeof deep sags is significantly reduced (Fig. 4.39). The effect on shallow sags is more limited. 7.3.2.4 Transmission Systems. Another example of a spot network is the 275 kV system in the UK. These systems form the subtransmissionnetwork around the big cities. Each 275 kV system consistsof about 10 busses in a loop-likestructure, fed at three to five places from the 400 kV national grid. The structureof the grid aroundManchesteris shown in Fig. 7.20: thick linesindicate400kV substationsand lines, and thin lines 275 kV. Similar configurationsare used inother Europeancountries,e.g., 150kV and 400 kV in Italy and Belgium, 150kV and 380 kV in p arts of The Netherlands,130kV and 400 kV in Sweden[23]. The number of supply points for the subtransmission systems varies from twothrough ten. In theUnited States this type ofconfiguration is in use across all voltage levels, down to 69 kV, as shown in Fig. 6.39. The effect of supplyconfigurationsas shown in Fig. 7.20 isthat faults in the 400 kV grid only cause shallow sags at the 275 kV substations.If we neglect the 275 kV line impedancescomparedto the transformerimpedances,the voltage in the 275 kV system is the average of the voltages at the 400 kV sides of transformers. the A fault close to one of thesubstationswill drop the voltage to a low value at this substation,but othersubstationswill be less affected. With ninetransformers,the shallow sags willdominate.The effect of this"averaging" is that the customerexperiences less deep but more shallow sags. To illustratethis effect, we againconsiderthe transmission system shown earlier in Fig. 4.27. The distance between thesubstationshas been increased to 100km, allother parameterswere kept the same.Figure 7.21 plots the sagmagnitudeas afunction of the fault position; position 0 is a fault insubstation1, position 100 (km) a fault insubstation2. Considernext asubtransmissionsystem fed from substation1 and substation2. The voltage in thesubtransmissionsystem is approximatedby the averagevoltagein the two transmissionsubstations;this voltage is indicated by the dotted line in Fig. 7.21. Due to thelooped operationacross the voltage levels, the deepest sags become shallower,and someof the shallow sags deeper. The disadvantageof the way of operationlike in Fig. 7.20 isthat faults in the 275 kV networks lead to deep sags. The interconnectedoperation makes that the exposed areacontainsmore lengthof lines than in caseof radial operation.If these Figure 7.20 Spot network at subtransmission level: 400 kV (thick lines) and 275 kV (thin lines) system in theNorth of England.(Data obtainedfrom [177].) 415 Section 7.3 • Power System D esign-Redundancy ThroughParallelOperation ::I '- Qc .S -8 .S t 0.6 ",, ,, /' " " 0.4 "" ",, ~ t:I} Figure 7.21Sagmagnitudein transmission and subtransmissionsystems. Solid line: transmissionsubstationI, dashed line: transmissionsubstation2, dottedline: subtransmission. , / I ,, I I ,, ,, ,, , ,, , 0.2 " '" "" ,, I I I J .PI00 -50 0 " 50 100 Faultposition 150 200 loops cross several voltage levels, like in the United States, the net effect is likely to be a reductionin sag frequency. 7.3.3 Power System Deslgn-on-slte Generation 7.3.3.1 Reasons for Installing a Generator. Local generatorsare used for two distinctly different reasons: 1. Generatingelectricity locally can becheaperthan buying it from the utility. This holds especially forcombined-heat-and-power (CHP) where the waste heat from the electricitygenerationis used in theindustrialprocess. Thetotal than in conventionalgenefficiencyof the process is typically much higher eratorstations. 2. Havingan on-sitegeneratoravailableincreases the reliabilityo f the supply as it can serve as abackupin case the supply is interrupted.Some large industrial plants have the ability tooperatecompletely in island mode. Also hospitals,schools,governmentoffices, etc., often have satandbygenerator to take over the supply when the public supplyinterrupted. is Here we onlyconsiderthe secondsituation, which might be anadditional advantage next to theeconomicand environmentalbenefits of on-sitegeneration.We first assess the effectof the generatoron the availability. Supposethat the public supply has an availability of 98%. This might soundhigh, but anunavailability of 2°~ implies that there is no supply for 175 h ourseach year, or on average 29 minutesper day, or 40 4hour interruptionsper year. Inother words, 980/0 availability is for many industrial customersunacceptablylow. We assumethat an on-sitegeneratoris installed which can take over all essential load. Supposethat the on-sitegeneratorhas anavailability of 900/0. The supply isguaranteedas long aseitherthe public supply or thegeneratorare available. Themethodsintroducedin Chapter2 can be used tocalculatethe reliability of the overall system. The resulting availability is 99.8%, or an unavailability of 18 hoursper year, four to five4-hourinterruptionsper year. In case faurther increase in reliability is needed, one can considerto install two or even threegeneratorunits. Each of these is assumed to be able to supply all the essential load. Withgenerators two we 416 Chapter7 • Mitigation of Interruptionsand Voltage Sags obtain an unavailability of 2 hours per year; with three, the unavailability is only 10 minutesperyear,neglectingall common-modeeffects. As we saw inChapter2 the latter assumptionis no longer valid for highly reliable systems.Any attempt to further increasethe reliability by adding more generatorunits is unlikely to be successful. Emergencyor standbygeneratorsare often startedwhen an interruptionof the public supply occurs. Instead of calculating unavailabilitiesit is more suitable to calculate interruption frequencies.Supposethat the public supply is interrupted40 times per year. The failure to startof an emergencygeneratoris typically somewherebetween10/0 and 5%. A valueof 5% will reducethe numberof interruptionsfrom 40 peryearto two per year. This assumesthat the generatoris alwaysavailable.In reality one hasto add anotherfew percentunavailability due to maintenanceand repair. The resultinginterruption frequencywill be aroundfive per year. Again an industrial useris likely to opt for two units, which brings the interruptionfrequencydown to lessthan one per year. 7.3.3.2 Voltage Sag Mitigating Effects.We saw inSection4.2.4 and in Section 6.4 that a generatormitigatessags near its terminals. To mitigate sags thegenerator has to be on-line; an off-line generatorwill not mitigate any voltage sags.The effect of a generatoron the sag magnitudewas quantified in Fig. 4.26 and in (4.16). The latter equationis reproducedhere: (1 - Vsag)= Z Z4 (1 - Vpcc) 3+ Z 4 (7.15) with Z3 the impedancebetween the generator/loadbus and the pee (typically the impedanceof a distribution transformer)and 2 4 the (transient)impedanceof the generator. If we further assumethat Vpcc = .c~1' with.Z the distanceto the fault, and introduce ~ =~, we get the following expressionfor the sagmagnitudeat the load bus as a functio~ of the distanceto the fault: V =1 sag 1_ _ (1 + ~)(1 + £) (7.16) This expressionhasbeenused toobtain the curvesin Fig. 7.22: the sagmagnitudeas a function of distanceis shownfor different valuesof the impedanceratio ~. A value ~ = o correspondsto no generator;increasingt; correspondsto increasinggeneratorsizeor increasingtransformerimpedance.C onsidera typical transformerimpedanceof 50/0 of 0.8 6- .5 ~ a 0.6 .~ . ,I ~ 0.4 i,' " 8 ~ ",', C/) , 0.2 Figure 7.22Sagmagnitudeversusdistance 2 4 6 8 Distance to the fault (arbitr. units) 10 for different generatorsizes. Theratio betweentransformerand generator impedanceused was 0 (solid line), 0.2 (dashed line), 0.4(dash-dotline), and 0.8(dottedline). 417 Section 7.3 • Power System D esign-Redundancy Through ParallelOperation its rated power, and a typical generatortransientimpedanceof 18%. For equal generatorandtransformerrating, we find t; = 0.28; ~ = 0.8 correspondsto a generatorsize about three times the transformerrating, thus also about three times the sizeof the load. We sawbeforethat generatorcapacityof more than threetimes theload doesnot have any improving effect on the reliability. It is thus unlikely that the generator capacity is more than three times the load. Anexception are someCHP schemes where theindustry sellsconsiderableamountsof energy to theutility. We see in Fig. 7.22 how the g eneratormitigatesthe voltage sag. The larger the generator,the more the reduction in voltage drop. From the expressionfor the sag magnitudeas afunction of distance,one canagainderive anexpressionfor the critical distance: 1 Lcrtl = (1 + ~)(1 _ (7.17) V) - 1 This expressionhas been used to calculatethe critical distancefor different generator sizes,resultingin Fig. 7.23. The curves are simply the inverse of the curvesin Fig. 7.22. We see areductionin critical distancefor each valueof the sagmagnitude.Note that the installationof an on-sitegeneratordoesnot introduceany additionalsags (with the exceptionof sags due to faults in ornear the generator,but thoseare rare). The sag frequencyfor the different alternativescan thus be comparedby comparingthe critical distances. A betterpictureof the reductionin sagfrequencycan beobtainedfrom Fig. 7.24. The various curves show the percentagereduction in sag frequency betweenthe site without generatorand the site with agenerator.Again three generatorsizes have been compared.For small sagmagnitudesthe reductionin sagfrequencyis 100%; thereare no sags left with thesemagnitudes.For higher magnitudesthe relative reduction becomesless. Thismitigation methodworks best forequipmentwhich alreadyhas a certainlevel of immunity againstsags. 10r----...----.------y-----,-----rr-..---, Figure 7.23 Critical distance versus magnitude for different generator sizes.The ratio between transformer and generator impedance used was 0 (solid line), 0.2 (dashed line),0.4 (dash-dot line), and 0.8 (dotted line). 0.2 0.4 0.6 Sagmagnitudein pu 0.8 7.3.3.3 Island Operation. On-site generatorsare fairly commonin large industrial and commercialsystems. Theon-site generationis operatedin parallel with the public supply. When the public supply fails, the on-site generatorgoes into island operation.This "island" can consistof the whole load or part of the load. The latter situation is shown in Fig. 7.25.The island systemshould be mademore reliable than 418 Chapter7 • Mitigation of Interruptionsand Voltage Sags 5 100 [ -'-'-'-,-"-'-';" \ t!= . \ \ \ \ \ .5 80 i~ , \ \ \ \ \ 60 " "'-. ~ .8 40 .s= .g 20 Figure 7.24Reductionin sag frequencydue ~ 0.2 0.4 0.6 Sag magnitude inpu Infeed from 0.8 to the installationof an on-sitegenerator.The ratio betweentransformerand generator impedanceused was 0.2(dashedline), 0.4 (dash-dotline), and 0.8 (dotted line). On-site publicsupply generation Radial network Island system (meshed) n/o Nonessential load Essential load Figure 7.25Industrial power system with islandingoption. the rest of theindustrial distribution system (e.g., by using a meshed network and differential protection).The island system also serves asbackupfor a the restof the industrial distribution system. A big problem in large industrial systems isthat islanding cannot be tested. One has to wait for an interruption to occur to seeif it works. 7.3.3.4 Emergency and StandbyGeneration. Emergencyand standbygenerators are typically started the moment an interruption is detected. They come online between one second and one minute after the start of the interruption. Note that there is no technical difference between emergency generationand standby generation. The term "emergencygeneration"is used when there is a legal obligation to have ageneratoravailable; in allother cases the term"standbygeneration"is used [26]. When installing standbygenerationto improve voltage quality it is important that essentialequipmentcan toleratethe short interruption due to thetransferto the 419 Section 7.4 • TheSystem-EquipmentInterface standby generation.Standbygenerationis often used incombination with a small amountof energystoragesupplying the essential load during the first few seconds of an interruption. 7.4 THE SYSTEM-EQUIPMENT INTERFACE The interface between the system and equipmentis the the mostcommon place to mitigate sags andinterruptions.Most of the mitigation techniques are based on the injection of active power, thuscompensatingthe lossof active power supplied by the system. Allmoderntechniques are based on power electronic devices, with the voltagesourceconverterbeing the main building block. Next we discuss the various existing and emerging technologies, withemphasis on the voltage-source converter. Terminology is still very confusingin this area, terms like"compensators,""conditioners," "controllers," and "active filters" are in use, all referring to similar kind of devices. In theremainderof this section, the term"controller" will be used, with reference toother terms in general use. 7.4.1 Voltage-Source Converter Most modernvoltage-sagmitigation methodsat thesystem-equipment interface contain a so-calledvoltage-sourceconverter.A voltage-sourceconverteris _a power electronic device which cangeneratea sinusoidalvoltage at any required frequency, magnitude,and-phase angle. We alreadysaw thevoltage-sourceconverteras an important part of ac adjustable-speed drives. In voltage-sagmitigation it is used totemporarily replace the supply voltage or to generatethe part of the supply voltage which is missing. The principle of thevoltage-sourceconverteris shown in Fig. 7.26. Athree-phase converterswith a commondc voltage-sourceconverterconsistsof three single-phase voltage. By switching the power electronic devices onoff orwith a certainpatternan ac voltage isobtained.One can use a simple squarewave or apulse-width modulated pattern. The latter gives lessharmonicsbut somewhathigher losses. Details of the / II Commondc bus with capacitor or battery block Self-commutating device (GTO/IGBT) ...----+-----0 Three-phase ac output Controllergenerating required switching pattern Figure 7.26 Three-phasevoltage-sourceconverter. 420 Chapter7 • Mitigation of Interruptionsand Voltage Sags operationand control of the voltage-sourceconvertercan be found in most books on power electronics, e.g., [53], [55]. In circuit-theorymodels,. thevoltage-sourceconvertercan simply be modeled as an ideal voltage source. To assess the effect of this on voltages andcurrents,no knowledge is neededa bout the powerelectronicdevices and thecontrol algorithms. In the forthcomingsections thevoltage-sourceconverteris modeled as an ideal voltage source to analyze themitigation effect of variousconfigurations. The samevoltage-sourceconvertertechnologyis also used for so-called "Flexible AC TransmissionSystems"or FACTS [180], [181] and for mitigation of harmonic distortion [179], [182], [183] and voltagefluctuations [170], [178]. In this chapterwe will only discuss their use formitigating voltage sags andinterruptions.The whole set of power electronicsolutions to power quality problems, including static transfer switches, activeharmonicfilters, and voltage control, is often referred to as"custom power" [184], [191]. 7.4.2 Series Voltage Controllers-DVR 7.4.2.1 Basic Principle. The series voltagecontroller consists of a voltagesourceconverterin series with the supply voltage, as shown in Fig. 7.27. The voltage at the load terminalsequalsthe sumof the supply voltage and the output voltage of the controller: (7.18) A convertertransformeris used toconnectthe output of the voltage-sourceconverter to the system. A relatively small capacitoris presenton de sideof the converter. The voltage over thiscapacitoris kept constant,by exchangingenergy with the energy storage reservoir. The requiredoutputvoltage isobtainedby using a pulse-width modulation switchingpattern.As thecontrollerwill have to supply active as well as reactive power, some kindof energy storageis needed. The termDynamic Voltage Restorer (DVR) is commonlyusedinsteadof series voltagecontroller [184], [185]. In the DVRs that are currently commercially available large capacitorsare used as a source of energy.Other potential sources are being considered: battery banks, superconducting coils, flywheels. We will for now assumethat there is some kind of energy storage available. Thevariousstorageoptionswill be discussed later. Supply voltage + Injected voltage Load voltage dcbus Energy storage Figure 7.27 Series voltagecontroller. 421 Section 7.4 • TheSystem-EquipmentInterface converter The amountof energystoragedepends on the power delivered by the and on themaximumdurationof a sag. Thecontrolleris typically designed for a certain maximum sagdurationand acertainminimum sag voltage. Some practicalaspects of a series voltagecontroller are discussed in[174]. 7.4.2.2 Active Power Injection. To assess the storage requirementswe calculate the active power deliveredby the controller, using the notation in Fig. 7.28. We assumethat the voltage at the load terminals is 1pu along the positive real axis: V/oad = 1 + OJ (7.19) The loadcurrentis 1pu in magnitude,with a lagging power factor cos ljJ: [load = cosljJ - jsinljJ (7.20) of the controllerhas amagnitudeV and phase-angle The voltage sag at the system side jump y,: Vsag = V cos1/1 + jV sin y, (7.21) The complex powertaken by the load is found from P10ad + jQload = V load7;oad = cosljJ + j sinl/J (7.22) The complexpower takenfrom the system is PsyS+ jQsys = Vsagl ;oad = V cos(l/J+ y,) + jV sin(ljJ + y,) (7.23) The active powerthat needs to begeneratedby thecontrolleris the difference between the activepower takenfrom the system and the active part of the load: P eonl = p/oad - (7.24) P syS This can bewritten as P COnl = [ 1- V cos(ljJ + 1/1)] cosf/> X Plood (7.25) For zero phase ...anglejump we obtain the following simple expression for the activepower requirementof the controller: Peon' = [1 - V]P/oad (7.26) The active powerrequirementis linearly proportionalto the drop in voltage. When phase-anglejumps are consideredthe relation is no longer linear and becomes dependent on the powerfactor also. To assess the effect of phase-angle jump and power factor, we have used the relations between sagmagnitudeand phase-angle j ump as derived in Chapter4. The active powerrequirementfor different power factor and Figure 7.28 Circuitdiagramwith power system, series controller, and load. 422 Chapter7 • Mitigation of Interruptionsand Voltage Sags Alpha=O Alpha =- 20 degrees Alpha = -40 degrees Alpha = - 60 degrees 0.5 00 0.5 1 00 0.5 1 Sag magnitude in pu Sag magnitude in pu Figure 7.29 Active powerrequirementfor a series voltagecontroller, for different impedanceangles(a=O, -20°, -40°, -60°) and different lagging power factors: 1.0 (solid lines), 0.9(dashedlines), 0.8(dash-dotlines), 0.7 (dotted lines). different phase-anglejump is shown in Fig. 7.29. Sag magnitudeand phase-anglejump have beencalculatedas a function of the distanceto the fault by using expressions j ump werecalculatedfor different values (4.84) and (4.87).Magnitudeand phase-angle of the impedanceangle and next filled in in (7.25) toobtain the active power requirement. The latter is plotted in Fig. 7.29 as afunction of the sagmagnitude V. As shown in (7.26), thepower factor of the load does not influence the active power requirementsfor sagswithout phase-anglejumps (upperleft). For unity power requirement.This is factor, the phase-anglejump somewhatinfluences the active power mainly due to the voltage over the controller no longer being equal toI-V. For decreasingpowerfactor and increasingphase-angle j ump, the active powerrequirement becomes less. One shouldnot concludefrom this that a low powerfactor is preferable. The lower thepower factor, the larger the loadcurrentfor the sameamountof active power, thus the higher therequiredrating of the converter. The reductionin active powerrequirementwith increasing (negative)phase-angle jump is explainedin Fig. 7.30. Due to thephase-angle j ump the voltage at system side of the controllers becomes more in phase with the load current. The amount of active Sag without phase-angle jump .... Load voltage , .. .. Sag with phase-angle jump Lagging load current Figure 7.30 Phasordiagramfor a series voltage controller. Dashedline: with negative phase-anglejump. Solid line: without phaseanglejump. 423 Section 7.4 • TheSystem-EquipmentInterface Alpha = - 20 degrees Alpha=O I ~ 0.5 .s> . 0 l.-- o o o L.- --J 0.5 1 Alpha = -40 degrees a .. 0.5 -" ~.,,:<~.:,:~,~ . . J " .:-~~~~:-.. 0.5 ! o L-- o --J 0.5 Sagmagnitudein pu 1 1 Alpha = - 60 degrees ~ Figure 7.31 Active power requirementfor a seriesvoltagecontroller, for different impedanceangles(a=O, -20°, -40°, -60°) and different leadingpowerfactors: 1.0(solid lines), 0.9(dashedlines), 0.8(dash-dotlines), 0.7 (dotted lines). --J 0.5 ,".v v, ,,,, '~\, o '--- o -..J 0.5 1 Sagmagnitudein pu power taken from the supply thus increases and the active power requirementof the controlleris reduced. This holds for a negative phase-anglejump and a lagging power phase-anglejump increases the active factor. For a leading power factor, a negative power requirements,as shown in Fig. 7.31. 7.4.2.3 Three-Phase Series Voltage Controllers. The seriescontrollerscurrently commercially available consist of three single-phase converterswith a commonde capacitor and storagereservoir. The power taken from the storagereservoir is the sum of the power in the three phases. For eachof the phases, (7.25) can be used to calcuto a late the active power.For a three-phase balanced sag (Le., a sag due three-phase requirementis fault) the sameamountof power is injected in each phase. The power multiplied by three. But also the active power taken by the load is three times as large, sothat (7.25) still holds, with the differencethat Pload is the total load in the three phases. To considerthe powerrequirementsfor three-phaseunbalancedsags, we write (7.25) in a somewhatdifferent form. Let the (complex)remaining voltage (the sag magnitude)be V, so that the voltage injected by thecontroller is I - V. The load currentis e-jt/J, which gives for the complex power delivered by the controller: (7.27) Considera three-phaseunbalancedsag of type C: two phases down in voltage; one phase not affected. To calculate the injected power in phase apply b, we the same lineof thoughtas leading to (7.27). The load voltage in phase b is - Vload I r:; = - -2I - -J'v 2 3 (7.28) The complex voltageduringthe sag is 1 1r: Vsag=-"2-2jVeharv3 (7.29) with Vellar the complexcharacteristicvoltage of the sag. The voltage injected by the controller is the difference between the load voltage and the sag voltage: (7.30) 424 Chapter7 • Mitigation of Interruptionsand Voltage Sags 0 The loadcurrentin phase b isshifted over 120 comparedto the currentin phase a: i.: = e-j ¢(-~ - ~jJ3) (7.31) The complex injected power in phaseb is (7.32) For phase c we find (7.33) (7.34) (7.35) (7.36) (7.37) Adding the complex powers in phaseb and phasec gives thetotal injected power (the voltage in phase a is n ot affected by the sag): - s.; -_32(1 - if/> Vchar)e (7.38) This is identical to (7.27), except for the factor j, Repeatingthe calculationsfor a threephaseunbalancedsagof type D, gives exactly the same injected power as for a type C sag. For the analysisof three-phaseunbalancedsags we have neglected the zerosequencecomponent.This is an acceptableapproximationat the terminals of enduserequipment,but not always inmedium-voltagedistribution, where DVRs are currently being installed.Adding a zero-sequence voltageto all three-phasevoltages in the above reasoningwill lead to an additional term in thecomplexpower expressions for the three phases. These additionalterms add to zero, so t hat the zero-sequence voltage does not affect thetotal active power demandof the seriescontroller. The power injectedduring a three-phasesag is three times the power injected in one phase. Bycomparing(7.38) with (7.27) we canconcludethat the power injected during a sagof type C or type D ishalf the powerinjected during a balancedsag with the samecharacteristicmagnitude,phase-anglejump, and duration. 7.4.2.4 Single-Phase Series Voltage Controllers. For single-phasecontrollers, the actual voltage in one phase (the voltage at the equipmentterminalsin the terminology from Chapter4) determinesthe amountof active power which needs to be injected. This is not onlydeterminedby the characteristicmagnitudebut also by the type of sag and the phase to which the controller is connected. of the What mattersto a single-phasecontroller are the injected powers in each three phases, i.e. the real part of Sb in (7.32) and of Sc in (7.37). Thesecalculations have beenperformedfor three-phaseunbalancedsagsof type C and type D, resulting in Figs. 7.32 and 7.33, respectively. For each sag type only two phases have been plotted: the two phases with the deep sag for type C, and the two phases with the 425 Section 7.4 • TheSystem-EquipmentInterface shallow sag for type D. Thethird phase for a type C sag does not require any injected power; the activepower requirementsfor the third phase of a type 0 sag are identical to (7.25). Both in Fig. 7.32and in Fig. 7.33 the injected power has been plotted for two valuesof the impedanceangle (0 and 30°) and four valuesof the power factorof the loadcurrent (1.0,0.9,0.8,0.7).We can conclude from the figures that the power factor has significant influence on the power injection. The characteristicphase-angle not change the jump makes that the two phases behave slightly differently, but does overall picture. For a single-phasecontroller,the characteristicvoltage does not have much practical meaning.Thereforethe activepowerrequirementshave beenplottedin a different way in Figs. ·7.34and 7.35. Thehorizontal axis is theabsolutevalue of the complex voltage during the sag; inother words, the sagmagnitudeat theequipmentterminals. The different curves in eachsubplot give the relation between sagmagnitudeand injected power for each of the phasesof a type C or type Dthree-phaseunbalanced sag. This leads to m a aximumof five curves, two from a type C sag, three from a type D sag. We seethat there is no generalrelation between the injected power and the sag Alpha =- 30 degrees Alpha = 0 t l 1 ~ 0.5 ..__"," _, , ~.:~:.~~::~.~.~ ..~.:-:.:~.. 0.5 , .. ... ~ o o ~&t 0.5 ................ o o . . . "," -·w. ~~..• ~ ... ... ~ 0.5 ' ~.~::~,... j '~':: 0"'--- 0'--- o o ---' 0.5 1 Characteristicmagnitude ~ . -- ~:~ ~~::':·?~~~2~.~.~. ~~.,. ". . ~ 0.2 ~ 0 S-O.2 o .....-J ~ o 0.5 ~ 0.6 Figure 7.33Active power requirementsfor a single-phaseseriesvoltagecontroller, for two phasesof a type D unbalancedsag, for impedanceangle zero (left) and -300 (right). Powerfactor 1.0(solid lines), 0.9(dashed),0.8 (dash-dot),0.7 (dotted). a 0.4 ~ 0.2 j -o.~ ~~~~~~.:.:.~~~~~.~~c~.,,~',.... o --' 1 Alpha = - 30 degrees . 0.4 '- ..-- 0.5 Characteristicmagnitude Alpha=O t 06 8. 0.5 1',~~>~.... Figure 7.32Active power requirementsfor a single-phaseseriesvoltagecontroller, for two phasesof a type C unbalancedsag, for impedanceanglezero (left) and -300 (right). Powerfactor 1.0(solid lines), 0.9 (dashed),0.8 (dash-dot),0.7 (dotted). " --.J ~ 0.5 I Characteristicmagnitude ~ -0.2 '-- o -.1 0.5 0.6 0.4 0.2 . 0 .. -0.2 ...:. :..~..~ ..-:-..:-:.::-.... o 0.5 I Characteristicmagnitude 426 Chapter7 • pf= 0.9 pf= 1.0 ~ Q> ~ Mitigation of Interruptionsand Voltage Sags I & t 0.5 0.5 ~ Q> > ~ 0 0 0 0.5 pf= 0.8 0 0.5 pf= 0.7 ~ QJ R t 0.5 0.5 0 0 ti .s> 0 0.5 Sag magnitude 0 pf= 1.0 ~ Go) ~ 0.5 Sag magnitude Figure 7.34Active power requirementsfor a single-phase series voltage controller as a function of the sagmagnitude-forzero impedanceangle and four values of the power factor of the loadcurrent. pf= 0.9 1 a t 0.5 0.5 J3 0 0 ii> 0 0.5 pf= 0.8 0 0.5 pf= 0.7 ~ ~ 0 c, t 0.5 0.5 ~ Go) > .s 0 0 0 0.5 Sag magnitude 0 0.5 Sag magnitude Figure 7.35Active power requirementsfor a single-phase series voltage controller as a function of the sagmagnitude-foran impedanceangle equal to - 30° and four valuesof the power factorof the loadcurrent. magnitude,especially for small values o f the power factor. Note also thatfor low power factor, a zero-magnitudesag is not the one with the highest active power requirements. Figures 7.34 and 7.35 have been reproducedin Figs. 7.36 and 7.37 with yet anotherhorizontalaxis. The active powerrequirementshave beenplottedas a function of the absolutevalueof the complex missing voltage (see Section 4.7.1). We seethat also the missingvoltage does not uniquely determinethe injected power. The load power factor and, to a lesserextent,the characteristicphase-anglejump influence the injected poweras welland shouldthus beconsideredin dimensioningthe energystorageof the controller. 7.4.2.5 Effect of the Voltage Rating. The voltage ratingof the voltage-source converter directly determinesthe maximum voltage (magnitude)which can be injected. This inturn determinesagainstwhich sags the load is protected.In the above calculations,it was assumedthat the load voltage would remain exactly at its pred rop and some phase-angle event value. This isnot strictly necessary: small voltage jump can betoleratedby the load. Figure 7.38 shows how theprotectedarea of the complex (voltage) plane can beobtained for a given voltage rating. The voltage 427 Section 7.4 • TheSystem-EquipmentInterface pf= 0.9 pf= 1.0 ... u ~ 8- 1 ~ 0.5 0.5 ~ 0 0 t:u 0 t> 0.5 pf= 0.8 0 1 ~ ... 0.5 0.5 0 0 Figure 7.36 Active power requirements for a ~ u single-phase series voltage controller as a ,....~ function of the missingvoltage-forzero impedance angle and four values of the power factor of the loadcurrent. 0 0.5 Missing voltage 0 ~ 0.5 Missing voltage pf= 0.9 pf= 1.0 t) 0.5 pf= 0.7 I 8- 0.5 b 0.5 \3 .s 0 0 0 0.5 pf= 0.8 0 0.5 pf= 0.7 ... l Figure 7.37 Active power requirements for a single-phase series voltage controlleras a function of the missingvoltage-foran -300 and four impedance angle equal to values of the power factor of the load current. 0.5 t) 0.5 i ~ 0 0 0 0.5 Missing voltage 0 0.5 Missing voltage rating of the voltage-sourceconverter is translatedto the same base as the load voltage. Theactual rating dependson the turns ratioof the convertertransformer. The voltage tolerance, as indicated in the figure, gives the lowest voltagemagnitude and the largest phase-angle j ump for which the load canoperatenormally. The sag voltage shouldnot deviate morethan the maximum injectable voltage (Le., the voltage dashedcurve, rating of the converter)from the voltage tolerance. This leads to the which givesmagnitudeand phase-angle j ump of the worst sagsthatcan bemitigatedby the controller;i.e., the voltage tolerance of the combinationof load andcontroller.The possible range of sags indicated is by a thick solid line. The rangeo f sags caneither be the range for a varietyo f supplies, like in Fig. 4.96, or for a specific supply, like in Fig. 4.108. It. is very well possible to cover the whole range of possible sags choosinga by large enoughvoltage rating. However, the numberof sags decreases for lower magnitudes, and the costs of the controller increase with increasing voltage rating. Therefore the seriescontrollerscurrentlyin use have a minimum voltage of typically 50%, so that sags with amagnitudebelow 50% of nominalare notprotected.With reducingcostsof 'power electronics, it is very well possible t hat future controllerswill cover the whole range of possible sags. 428 Chapter7 • Mitigation of Interruptionsand Voltage Sags Voltagetolerance ~ t Range of possible sags Figure 7.38 Part of the complex (voltage) plane protectedby a series voltagecontroller with the indicatedvoltage rating. 7.4.2.6 Effectofthe Storage Capacity. The voltage rating of the controller determineswhich range of magnitudeand phase-anglejump of sags can be mitigated. For a given magnitudeand phase-anglejump the active power requirementis found from (7.25). The active power requirementand the amount of energystoragedetermine the longestsag durationwhich can be mitigated. During the designof a seriescontroller, a sagmagnitudeand a sagdurationare chosen.The sagmagnitudegives thevoltagerating, the sagdurationgives therequired storagecapacity.Togetherthey determinethe "designpoint" in Fig. 7.39.The voltage toleranceof the load without controller is shownas adashedline (in this examplethe voltagetoleranceof the load is 200 ms, 90% ) . The influenceof the phase-anglejump is neglectedhere.(Including the phase-angle j ump would give arangeof voltage-tolerance curves, both with and without the controller.) Any sag with amagnitudeabove the design magnitudeand with a duration lessthan the designduration,will be mitigated by the controller: i.e., the resulting load voltage will be above the voltage-tolerance curveof the load. Sagslonger than the designdurationareonly toleratedif they do not depletethe storagecapacity.Neglectingthe phase-angle j ump, we can use (7.26) for the injected power: Peont = (1 - V)P1oad (7.39) The energyneededto ride through a sagof magnitude V and duration T is £ = (1 - V)TPload (7.40) --------------------~-----------------; 0.8 :::s Q.. .S 0.6 ] .~ 0.4 Design point ~ 0.2 2 4 6 Duration in seconds 8 10 Figure 7.39 Voltage-tolerancecurve without (dashed line) and with (solid line) series voltage controller. The designpoint gives the lowest magnitudeand the longestd uration which theload-controllercombinationis able to tolerate. 429 Section 7.4 • TheSystem-EquipmentInterface Let (To, Vo) be the designpoint. The availableenergystorageis [avail = (1 - VO)TOPload (7.41) The minimum sagmagnitudeVmin for a duration T is found from [avail = (1 - Vmin)TPload (7.42) This gives the following expression for the voltage-tolerancecurve: V min = 1- (1 - To VO)T (7.43) This is is shown in Fig. 7.39 as the curve from the design point toward the right and upward. Thevoltage-tolerancecurve of the load withcontroller gets its final shape by realizingthat any sagtoleratedwithout controllercan also betoleratedwith controller. The area between the curves is the gain in voltage tolerancedue to thecontroller. To assess thereductionin numberof trips, a sag densityc hart is needed. 7.4.2.7 Interruptions. A series voltage controller does not function during an interruption. It needs a closedpath for the load current,which is not always present during an interruption. If there is loadpresentupstreamof the controller and downstream of the circuit breaker causing the interruption, this load will form a path throughwhich theconvertercurrentcan close, as shown Fig. 7.40. The seriescontroller will aim to keep the voltageVI and thus thecurrent /load constant.The effect isthat the current[load is forced into theupstreamload impedance Z2 leading to a voltageV2 = Z2//oad on system sideof the controller, but in opposite phasecomparedto VI' Using VI = Zt[/oad we get V2 Z2 =-ZI V. (7.44) with ZI the impedanceof the load to beprotectedby the controller. If the upstream load is smallerthan the protectedload, 2 2 > Z 1, this could lead todangerousovervoltages. With the existing devices this effect is limited in two ways: • The voltage difference over the controller is V t + V2 which is significantly larger than 1pu if.Z 2 > Zt. For a controller with a maximumoutputvoltage of 0.5 pu (a typical value) the resulting voltage over the upstreamload can never be morethan 0.5 pu. Circuit breaker causing the interruption ~ ----/--r--f Upstream----...- load Figure 7.40 Series voltage c ontroller with upstreamload during an interruption. Series controller Loadprotected Jontroner 430 Chapter7 • Mitigation of Interruptionsand Voltage Sags • The energy reservoir is limited, so that this overvoltage willdisappearwithin a few seconds.Note that both the protectedload and theupstreamload will deplete the energy reservoir. This could, however, become problem a in the future when therating of voltage controllers increases,both in injected voltage and instoredenergy. The effect of the sudden inversion of the voltage on theupstreamload should be studied as well. 7.4.3 Shunt Voltage Controllers-StatCom A shunt-connected voltagecontrolleris normally not used for voltage sag mitigation but for limiting reactive powerfluctuationsor harmoniccurrentstakenby the load. Such acontroller is commonly referred to as a"Static Compensator"or "StatCom." Alternativeterms in use are"AdvancedStaticVar Compensator"(ASVC) and "Static Condensor"(StatCon).A StatComdoesnot containany active powerstorageand thus only injects or draws reactive power. Limited voltage sag mitigation is possible with the injection of reactive power only [57], [157], [210], but active power is needed both if constant. magnitudeand phase angleof the pre-eventvoltage need to be kept The principle of a shunt voltage controller is shown in Fig. 7.41. The actual controller has the sameconfigurationas the seriescontroller. But instead of injecting the voltage difference between the load and the system, current a is injected which pushes up thevoltageat the loadterminals,in a similar way to the sagmitigation by a generatordiscussed in Section 7.2. The circuit diagramused to analyze the controller'soperationis shown in Fig. 7.42. The load voltaged uring the sag can be seen as the superpositionof the voltage due to the system and the voltagechangedue to thecontroller.The former is the voltage as it would have beenwithout a controller present,the latter is the change due to the injectedcurrent. Assumethat the voltagewithout controller is V.sag = V cos1/1 + jV sin 1/1 (7.45) The load voltage is again equal to 1pu: V/oad = 1 + OJ Distribution substation Transmission system Supply transformer t----~ Load Shunt voltage controller Figure 7.41 Shuntvoltagecontroller. (7.46) 431 Section 7.4 • TheSystem-EquipmentInterface Figure 7.42Circuit diagramwith power system, series c ontroller,andload. Full circuit (top), voltageswithout controller(center), effect of thecontroller (bottom). The requiredchangein voltagedue to the injectedcurrentis the differencebetweenthe load voltage and the sag voltage: ~V =1- V cos 1/1 - jV sin 1/1 (7.47) This changein voltagemust be obtainedby injecting a currentequal to leont = P - jQ (7.48) with P the active powerand Q the reactivepowerinjectedby the controller. The active power will deterrninethe requirementsfor energystorage.Let the impedanceseen by the shuntcontroller(sourceimpedancein parallelwith the load impedance)be equalto Z=R+jX (7.49) The effect of the injected currentis a changein voltageaccordingto ~ V = leontZ = (R + jX)(P - jQ) (7.50) The requiredvoltageincrease(7.47) and the achievedincrease(7.50) haveto be equal. This gives the following expressionfor the injectedcomplex power: p _ 0Q = I - V cos"" - jV sin "" } R+jX (7.51) Splitting the complexpowerin a realandan imaginarypart, givesexpressionsfor active and reactivepower: P = R(l - V cos 1/1) - VX sin 1/1 R2 + X 2 Q = RV sin 1/1 + X(l - V cos 1/1) 2+X2 R (7.52) (7.53) The main limitation of the shuntcontroller is that the sourceimpedancebecomesvery small for faults at the samevoltagelevel close to theload. Mitigating suchsagsthrough a shuntcontroller is impractical as it would require very large currents.We therefore 432 Chapter7 • Mitigation of Interruptionsand Voltage Sags only consider faultsupstreamof the supplytransformer.The minimum value of the sourceimpedanceis the transformerimpedance. One can think of this configurationas a dedicatedsupply to a sensitive load (e.g., an automobileplant), where the task of the controller is to mitigate sagsoriginating upstreamof the transformer. The resultsof somecalculationsfor this configurationare shown in Figs. 7.43 and impedance(transformerimpedance) have 7.44. Four different values for the source For the load impedance a value of 1pu been used: 0.1, 0.05, 0.033, and 0.025 pu. resistive has been chosen. For a 0.05 pu source impedance, the fault level is 20 times the load power.Fault levels of 10 to 40 times the load are typical distribution in systems. controllerto mainFigure 7.43 shows the a mountof active power injected by the tain the voltage at its pre-event value. We see that for zero impedance angle the active power requirementis independentof the source impedance. This does not hold in general, but only for this specific case with a pure reactance in parallel with a pure resistance.F or increasingimpedanceangle we see an increase in active power, especially for smaller valuesof the source impedance. The reactive power shown in Fig. 7.44 is ratherindependento f the impedanceangle. The reactive power requirements decrease significantly with increasing source impedance. As the (reactive) source impedance Alpha = 0 Alpha = - 20 degrees 6r---------, 5.S t 4 ~ 0.5 .. ' Q) .~ < 00 0.5 I Alpha =-40 degrees 6- 8,..-----:-:-:------, .: 6 ~ Q., ~ .~ < ' 4 ... o'., .:'<": ~ : / . .. ,-° '. 10 0 " , , 2..{:"" , Alpha = -60 degrees 15r - - - - - - - - - - , .. ', ,".....:,". , \"'. 0.5 I Sag magnitude in pu Alpha = 0 40r-:-·..- - - - - - - - - , .: 30, , . ~ ~ 8. 20 .~ 10 ", . """ ", ..... ' ". 8 ~ 00 " ", .. 5 :.~.~:~ , ~ ., 00 40 ". - - - _....... '-0. " ..,\.'~'" ~" '\ 00 - -'- ,,0. .... ".-' o" ." '~ , 0.5 1 Sag magnitude in pu Alpha = - 20 degrees . 30,. '. 20 10 0.5 1 ::s Alpha = -40 degrees Q., 40rr-·.-.- -......----.., .S ". 0.5 1 Alpha = - 60 degrees 40 . l) 30 .... 30 -.-. ~ &20 -0 • .~ 10 00 " " ..... 10 ~ ~ 00 20 ...... 0.5 1 Sag magnitude in pu Figure 7.43 Activepowerinjected by a shunt voltage controller, for different impedance angles(0, -20° -40°, -60°) and different sourceimpedances:0.1pu (solid line),0.05pu (dashedline), 0.033pu (dash-dotline), 0.025pu (dottedline). 00 0.5 1 Sag magnitude in pu Figure 7.44 Reactivepower injected by a shuntvoltagecontroller, for different impedanceangles(0, -20°, -40°, -60°) and different sourceimpedances:0.1pu (solid line), 0.05pu (dashedline), 0.033pu (dash-dot line), 0.025pu (dotted line). 433 Section 7.4 • TheSystem-EquipmentInterface increases, less injected current is needed to get the same change in voltage. Note the difference in vertical scale between Figs 7.43 and 7.44. The reactive power exceeds the active power injected in all shown situations. The current rating of the controller is determinedby both active and reactive power. From (7.52) and (7.53) we find for the absolutevalue of the injected current: 1 - 2V cos1/1 + V2 R2+X2 I cont = (7.54) 1/1) increases We seethat an increasing phase-angle jump (increasing1/1, decreasing cos thecurrentmagnitude. Thecurrentmagnitudeis plottedin Fig. 7.45 in the same format as the active power in Fig. 7.43 and the reactive power in Fig. 7.44. ComparingFig. 7.45 with Fig. 7.44 showsthat the currentmagnitudeis mainly determinedby the reactive power. Like the reactive power, the current magnitudeis only marginally affected by the phase-angle jump. The large increase in active power injected with increasing phase-angle jump is explained in Fig. 7.46. The injected voltage is the requiredvoltage rise at the load due to Alpha =- 20 degrees Alpha=O 40 '. 30 a 6 20 .S u~ . .." .... ..'. 30 .. 20 10 :s ~ .S . 00 O.S 1 Alpha = -40 degrees 40 .... 30.. " .'. ". .. 0.5 1 Alpha = - 60 degrees 40··.. . 5 20 o~ ...... 10 00 Figure 7.45 Magnitudeof the currentinjected by a shuntvoltagecontroller, for different impedanceangles (0, -200 , -400 , -60°) and different sourceimpedances:0.1 pu (solid line), 0.05 pu(dashedline), 0.033 pu(dash-dot line), 0.025 pu(dotted line). 40·... ...... 30 ' , .... 20 'eo 10 '" .... 10 00 0.5 1 00 0.5 1 Sagmagnitudein pu Sagmagnitudein pu Source impedance ,"Injected . Normaloperating ....,.. voltage \ \ ,, \ ------- ,, , \ \ \ \ \ \ , \ \ Figure 7.46 Phasordiagramfor shuntvoltage controller. Solid lines: without phase-angle jump. Dashedlines: with phase-anglejump. ,, ~ Injected current voltage Sag voltage ----a.,. 434 Chapter7 • Mitigation of Interruptionsand Voltage Sags the injection of a currentinto the sourceimpedance.T his injectedvoltageis the differencebetweenthe normal operatingvoltageand the sag voltageas it would be without controller. The injectedcurrentis the injectedvoltagedivided by the sourceimpedance. In phasorterms: theargument(angle,direction)of the injectedcurrentis the argument of the injected voltageminus the argumentof the sourceimpedance.T he sourceimpedance is normally mainly reactive. In case of a sag without phase-anglejump, the injected current is also mainly reactive. A phase-anglejump causesa rotation of the injectedvoltageasindicatedin the figure. This leadsto a rotationof the injectedcurrent away from the imaginaryaxis. From the figure it becomesobviousthat this will quickly causea seriousincreasein the active part of the current (i.e., the projection of the current on the load voltage). The changein the reactive part of the current is small, so is thechangein currentmagnitude. 7.4.3.1 Disadvantagesof the Shunt Controller. It is clear from the above reasoningthat the main disadvantageof the shuntcontroller is its high active power demand. In case of a large load with a dedicatedsupply from 'a transmissionnetwork, a shunt controller might be feasible. Voltage sags in transmissionnetworks show smallerphase-anglejumps, and the transformerlossesare very small. The latter have not been taken into considerationin the above calculations,as they are rarely more than a few percentof the load. If the load is suppliedthrough an underground cable network, these lossescould dominatethe active power requirementof the controller. Another disadvantageof the shunt controller is that it not only increasesthe voltage for the local load but for all load in the system.Again for a load with a dedicatedsupply through a large transformer,this effect issmall, but for a load fed from a distribution feeder with many other customersit is not feasible to install a shunt controller. In caseof a load fed from a distribution feeder, the controller will not be able to mitigate sags originating at distribution level. The sourceimpedanceduring the sag willsimply be too small to enableany seriousincreasein voltage. The behaviorof the shuntvoltage controller during an interruption dependson the amountof load involved in the interruption. When the supply is interrupted,the injectedcurrentclosesthrough the load, and the (active and reactive)power demands are formed by the total load involved in the interruption.If this is only the load to be protected,the controllerwill haveno problemproviding this power. If a lot more load is interruptedthe controllerwill probablyreachits currentlimits or its energyreservoir will be depletedvery fast. If the controlleris able to maintainthe load during the interruption,synchronization problemscan occur when the voltage comesback. If the supply voltage differs significantly in phasewith the voltage generatedby the controller, large currentswill start to flow leadingto relay tripping and/orequipmentdamage.A phasedifferenceof 600 gives an rmsvoltageof 1pu over the terminalsof the recloser.A phasedifferenceof 1800 gives 2 puover the terminals.Considerthat the nominalsystemfrequencyis 60 Hz and that the voltage comes back after 3 seconds.If we want to limit the angular differenceto 300 , the relative error in frequencyshould not be more than: 30° = 5 X 10-4 3 s x 60cyclesjsx 360 0 jcycle (7.55) From this it follows that the frequencyneedsto be between59.97 and 60.03 Hz. To operatethe voltage-sourceconverterwithin this frequencyrangeis not a problem:modern clocksachieveaccuracieswhich areseveralordersof magnitudebetterthanthis. But the systemfrequencycaneasilydeviatemore than0.03 Hz from its nominal value. 435 Section 7.4 • TheSystem-EquipmentInterface The mainadvantageof a shuntcontrolleris thatit can also be used to improve the currentquality of the load. By injecting reactive power, the power factor can be kept at unity or voltagefluctuationsdue tocurrentfluctuations(the flickerproblem)can be kept to a minimum. Theshuntcontrollercan also be used to a bsorbthe harmoniccurrents generatedby the load. In case such controller a is present, it isworth considering the installation of some energystorageto mitigate voltage sags. It will be clear from the previouschaptersthat a stochasticassessmentof the variousoptionsis needed. 7.4.4 Combined Shunt and Serle. Controller. The seriescontroller, as discussed before, uses an energy storage reservoir to t hat the seriescontroller cannot power part of the load during a voltage sag. We saw mitigate any interruptions,and that it is normally not designed to mitigate very deep 'sags (much below50% of remaining voltage). There is thusnormally some voltage remainingin the powersystem. This voltage can be usedextractthe to required energy from the system.A series-connected converterinjects the missing voltage, and a shuntconnectedconvertertakes acurrent from the supply. The powertaken by the shunt controllermust be equal to the power injected by the series controller.The principle is shown in Fig.7.47.Series- andshunt-connected convertershave acommonde bus. The change instoredenergy in thecapacitoris determinedby the difference between the power injected by the series converterand the powertakenfrom the supplyby the shunt converter.Ensuringthat both are equal minimizes the size of the capacitance. Iseries ~ag -----. ~ load Load System o 00 Figure 7.47 Shunt-series-connected voltage controller: theshunt-connectedconverteris placed on system side of the series controller. > 7.4.4.1 Current Rating. The active powertaken from the supply by the shuntconnectedconverteris (7.56) We assumethat the shunt-connectedconvertertakes acurrent from the supply with magnitude[shunt and in phase with the system voltage IShunt = [shunt COS t/J +Jrtthunt sin t/J (7.57) where 1/1 is thephase-angle j ump of the sag.Taking the currentin phase with the system voltage minimizes thecurrent amplitude for the sameamount of active power. The active powertakenfrom the supply is Pshunt = VIshunt (7.58) 436 Chapter7 • Mitigation of Interruptionsand Voltage Sags with V the sagmagnitude.The active power injected by the series controller was calculated before, (7.25): Pseries = [ 1- V cos(¢+ 1/1)] cos ¢ Pload (7.59) The powertakenby the shunt-connected converterPshunt should be equal to the power injected by the series-connected converterP.reries' This gives the following expression for the magnitudeof the shuntcurrent: 1 cos(¢+ 1/1)] cos ¢ Plood [V- I ,rhunt = (7.60) The resultsof this equationare shown in Fig. 7.48 in the same format and with the same parametervalues as before (e.g., Fig. 7.29). The magnitude ofshunt the current has beenplottedfor values up to 4 pu, i.e. four times the active partof the loadcurrent.The influence ofphase-angle j ump and power factor is similar to their influence on the active power as shown in Fig. 7.29. But the overriding influence onshuntcurrentis the the sag magnitude.The less voltage remains in the system, the more currentis needed to get the sameamount of power. As the power requirement increases with decreasing system voltage, the fast increase current in for decreasing voltage is understandable . Alpha = 0 Alpha = - 20 degrees 4,----;-- - --='---, 3 2 00 0.5 I Alpha = - 40 degrees 4 .-.:..r-- ---='---, 4 3 \, , • '\, ~ ... :::: .'::.. ....-.;: 0.5 Sag magnitude in pu 0.5 1 Alpha = - 60 degrees I I, \ .~\ -v Figure 7.48Shuntcurrent for a shunt-series voltage controller, for different impedance angles(0, _20°, _40°, _60°)and different " .c- ~.~ ":.."'leading powerfactors: 1.0 (solid lines), 0.9 00 0.5 1 (dashed lines), 0.8 ( dash-dotlines), 0.7(dotted Sag magnitude in pu lines). 2 .~\ 00 00 .. ~ .\ , 7.4.4.2 Shunt Converter on Load Side. Figure 7.49 again shows shunt a -series controller. The difference with Fig. 7.47 is t hat the shuntcurrentis taken off the load voltage. To assess the effect of this, we again calculate the requirements for the shunt and seriescurrents.We use the same n otationas before: V load [load Vsag = = 1 + OJ COS¢- jsin¢ = V cos1/1 + jV sin 1/1 (7.61) (7.62) (7.63) 437 Section 7.4 • TheSystem-EquipmentInterface ~oad ~ag Load System Figure 7.49Shunt-seriesconnectedvoltage controller; the shunt-connectedconverteris placed on load sideo f the seriescontroller. We assumethat the shuntcurrentis taken at a lagging power factor COs~: I.vlzunt = I cos~ - jI sin ~ (7.64) The total currenttaken off the supply,throughthe series-connected converter,is [series = IShunt + [load = cosl/J + I cos~ - j sin l/J- jI sin ~ (7.65) The active power taken off the supply should be equal to the power takenby the load. The power injected by the series converteris taken off again by theshuntconverter.As there is no active power storage, the total active power still has to come off the supply. This gives the following expression: (7.66) From this the following expression for the s huntcurrentcan beobtained: I = cosl/J - V cos(l/J + 1/1) V cos(1/1 + ~) (7.67) To minimize theshuntcurrent,the angle~ is taken suchthat 1/1 + ~ = 0; thus theshunt If we further rate theshuntcurrentto the currentis in phase with the supply voltage. active part of the loadcurrent,we obtain I = -!. _cos(1/1 + e/» V cose/> (7.68) which is exactly the same currentas for a system-side shunt. 7.4.4.3 Single-PhaseController. For a single-phasecontroller, we have again calculatedthe invertercurrentas a functionof the sagmagnitudein a similar way as for Figs. 7.34 and 7.35. The results are shown in Figs. 7.50 and 7.51 for different power factor of the load current. Fig. 7.50 is for sagswithout phase-anglejumps (zero impedance angle), Fig. 7.51 for sags with a serious phase-anglejump (an impedance angle equal to -30°). The overallbehavioris dominatedby the fast increase in current for deep sags. But for small power factor, especially, phase-angle the jump also plays animportantrole. 7.4.4.4 Advantagesand Disadvantages. The main advantageof the shunt-series controller is that it does not require any energy storage. It can be designed to mitigate any sag above caertain magnitude,independentof its duration. This could result in a relatively cheap device, able to compete with the UPS (see below) for the 438 Chapter7 • Mitigation of Interruptionsand Voltage Sags 4 pf= 1.0 4 = ~ 3 :s 3 2 2 (J ~ ~ pf= 0.9 ~ .s 00 c: ~ (J ~ u 4 0.5 pC= 0.8 0 0 4 3 3 2 2 0.5 pC= 0.7 t: u > .s 0 0 0.5 0 0 Sag magnitude 4 pf= 1.0 = ~ 3 (J ~ i> 4 0.5 Sag magnitude Figure 7.50 Shuntcurrentfor a single-phase shunt-seriesv oltagecontrolleras afunction of the sagmagnitude,for zero impedanceangle and four valuesof the power factor of the load current. pC= 0.9 3 2 2 .s 00 4 d ~ (J ~ u t: 0.5 pC= 0.8 0 0 4 3 3 2 2 0.5 pf= 0.7 u ] °0 0.5 Sag magnitude 0 0 0.5 Sag magnitude Figure7.51 Shuntcurrentfor a single-phase shunt-seriesv oltagecontrolleras afunction of the sagmagnitude,for impedanceangle - 30° and four values of the power factor of the load current. protectionof low-power, low-voltageequipment.The shuntconverterof a shunt-series controller can also be used to mitigate current quality problems, as mentioned o f the shuntcontroller. above with the discussion The main disadvantageof the shunt-seriescontroller is the largecurrent rating required to mitigate deep sags. For low-power, low-voltageequipmentthis will not be a serious concern,b ut it might limit the number of large power andmedium-voltage applications. 7.4.5 Backup Power Source-SMES, BESS One of the maindisadvantagesof a seriescontroller is that it cannot operate during an interruption. A shunt controller operatesduring an interruption, but its storage requirementsare much higher. We saw that the shunt-connectedcontroller operatesperfectly when only thecontroller and the protectedload are interrupted. The controller is in that case only feeding theprotectedload. This principle can be used by creating the rightinterruption. This results in theshunt-connectedbackup power source as shown in Fig. 7.52. The configuration is very similar to the shunt 439 Section 7.4 • TheSystem-EquipmentInterface ------t System Statict--_.._-------switch Load Energy storage reservoir u 00 > Figure 7.52 Shunt-connected backup power source. _ _~ Static1 - - - . . . . , . - - - - - - ' \ System switch 1 Load Static switch 2 Figure 7.53 Series-connected backup power source. Energy storage reservoir controller. The difference is the static switch which is present between the system and the load bus. Themomentthe system voltagedropsbelow a pre-set rms value, the static switch opens and the load is supplied from the energy storage reservoir through the voltage-sourceconverter.Various formsof energy storage have been proposed.A socalled superconductingmagneticenergy storage (SMES) stores electrical energy in a superconducting coil [57], [158], [159], [160], [161], [162]. A BESSor battery energy storagesystemuses a largebatterybankto store the energy [186], [187],[188]. For small devices the energy storageis not a problem,but using a SMES, BESS, or any otherway of storage at medium voltage will put severestrainson the storage. A backup power source is only feasible if it can ride t hrough a considerablefraction of short interruptions. Looking at some statistics forshort interruptions,Figs. 3.5, 3.6, and 3.7, shows that the amountof storageshouldbe able to supply the load for 10 to 60 seconds. Less storage would not give any serious improvementin the voltage tolerance comparedto the seriescontroller. All backuppower sources suggested in the literatureuse ashuntconnection,but it aseriesconnectionas in Fig. 7.53. This device could operateas a is also feasible to use seriescontrollerfor sags and as baackuppower source forinterruptions.The moment a deep sag is detected, static switch 1 opens and static switch 2 closes. 7.4.8 Cascade Connected Voltage Controllers-UPS The main device used to mitigatevoltage sags and interruptionsat the interface is the so-calleduninterruptablepowersupply(UPS).The popularityof the UPS isbasedon its low costs and easy use. For an office worker the UPS isjust anotherpiece of 440 Chapter7 • Mitigation of Interruptionsand Voltage Sags equipmentbetween the wallo utlet and acomputer.All that is needed is to replace the batteriesevery few years, and as long as one does not power the kettle and the microwave from the same UPS, virtually a problem-freesupply iscreated. 7.4.6.1 Operationof a ups. The UPS isneither a shunt nor a series device, but what could bedescribedas acascadeconnectedcontroller. The basic configuration of a typical UPS isshown in Fig. 7.54. Itsoperationis somewhatsimilar to the drive (compareFig. 5.12): a diode rectifier converterpart of an ac adjustable-speed followed by an inverter. The main difference is the energystorageconnectedto the de bus of a UPS. In allcurrently commerciallyavailable UPSs the energy storageis in the form of a battery block. Other forms of energystoragemight become more suitablein the future. During normal operation,the UPS takes its power from the supply, rectifies the ac voltage to dc andinverts it again to ac with the same frequency and rms value. The designof the UPS is suchthat the de voltageduring normal operationis slightly above the batteryvoltageso that the batteryblock remainsin standbymode. All power comes from the source. The onlyp urposeof the batteryblock in normal operationis to keep the de busvoltageconstant.The load ispoweredthroughthe inverterwhich generates a sinusoidalvoltagetypically by using aPWM switching pattern.To preventload interruptions due to inverter failure, a static transfer switch is used. In case the inverter output drops below acertainthresholdthe load is switched back to the supply. During a voltage sag orinterruptionthe batteryblock maintainsthe voltage at the de bus for severalminutesor evenhours,dependingon the batterysize. The load will thus tolerate any voltage sag ors hort interruption without problem. For long interruptions, the UPSenablesa controlledshutdown,or the start of a backupgenerator. Bypass de ac System de Energy storage Figure 7.54 Typicalconfigurationof an uninterruptablepower supply (UPS). 7.4.6.2 Advantages and Disadvantages. The advantageof the UPS is its simple operationand control. The power electronic componentsfor low-voltage UPSs are readily availableand the costsof a UPS arecurrently not more than the costsof'.a personalcomputer.It is probably not worth installing a UPS for eachpersonalcomputer in an office (making regular backupswould be moresuitable), but when a computer(or any other low-power device) is an essentialpart of a production process the costsof the UPS are negligible. As the UPS will mitigate all voltage sags and short interruptionsa stochasticassessment is not even needed. The main disadvantageof the UPS is thenormal-operatingloss because of the two additional conversions,and the useof batteries.Contrary to general belief, batteries do needmaintenance.They should be regularly tested to ensure that they will operatein caseof an interruption; also they should not be exposed to high or low 441 Section 7.4 • TheSystem-EquipmentInterface temperaturesand sufficient cooling should be installed preventoverheating.All to this is not so much aconcernfor the small UPSs used in an office environment,but for large installationsthe maintenancecosts of a UPSinstallationcould becomeratherhigh. 7.4.6.3 Alternatives. As a long-term solution to mitigate voltage sagsand interruptions,the UPS is not the mostappropriateone. The twoadditional conversions are not really needed, as can be seen in Fig. 7.55. Thedrawing top shows the normal configuration:the ac voltage isconvertedinto de and back to ac by the UPS. In the computer the ac voltage is againconvertedinto de and nextconverted to the utilization voltage for the digital electronics. This scheme represents almost any modernconsumerelectronics device. Alternatively, one can directlyconnectthe batteryblock to the de bus inside the computer.In fact a laptop computergets its power in such a way. Some mitigation methodsfor ac adjustable-speed drives also use a direct infeed into the dc bus. From an engineeringviewpoint this is a more elegant solution than using a UPS, but the user doesnot always have the technical knowledge to do this. solutionlike A this can only be initiated by the equipmentmanufacturers. One can extend this idea further, ending up with a denetwork for an office building providing backuppower to all sensitiveequipment.By connectingan array of solar cells to this denetwork the situation could arise where the utilitysupply becomes thebackupfor the internal de network. UPS .- -. ---- -----Computer ---------.. -.... ---.. ----. f f t-----:--t _ .. i Digital electronics : - - . _ .. - __ - - I f I _ _ eI Computer Digital electronics I I I I ,. -.-- --- _--------._. Figure 7.55 Powerconversionsfor a UPS poweringa computer,and for an alternativesolution. 7.4.6.4 UPS and Backup Generators. Figure 7.56 shows a power system where both UPSs and backup generationare used to mitigate voltage sags and interruptions. The UPS is used to protect sensitive essential load against voltage sags and short interruptions.But especially for large loads, it is not feasible to have more than a few minutes energy supply stored in the batteries. In case of an interruption, the so-called "islanding switch" opens, disconnectingthe sensitive load from theutility system. During the interruption the sensitive load is completelypowered from a backup generator.This generatorcan be eitherrunning in parallel with the utility 442 Chapter7 • Mitigation of Interruptionsand Voltage Sags Utility infeed Islanding switch Nonessential load Nonsensitive essentialload Figure 7.56 UPS combined with backup Sensitive generation to mitigate voltage sags, short and essential load long interruptions. supply, or bestartedthe momentan interruption is detected. All essential load is fed from the backup generator,where only the essential load which is sensitive to sags and short interruptionsneeds to be powered from the UPS. Decreasingthe time to switch over to islandoperation decreases the energy storage requirementsin the ups. The energystoragerequirementis proportional to the switch-over time. The UPS only needs to supply the load which cannottoleratethe interruptiondue to the switch-overto islanding operation.The faster the switch-over, the less load needs to be powered from the UPS. An interestingexample of the use o f UPSs incombinationwith on-sitegenerators to achieve a high reliability is discussed [172]. in 7.4.7 Other Solutions Somemitigation equipmentis not based on thevoltage-sourceconverter;a few examples are discussed below. Motor-generatorsets andferroresonanttransformers have beenaround for many years to mitigate voltage sags; electronic tap changers form an interestingnew technique. 7.4.7.1 Motor-Generator Sets. A motor-generatorset is an oldsolution against voltage sags,making use of the energy stored in a flywheel. The basic principle is shown in Fig. 7.57: a(synchronousor induction) motor and asynchronousgenerator are connectedto a common axis together with a large flywheel. When the power supply to themotor is interrupted,the flywheel makes that the systemcontinuesto rotate and thuscontinuesto supply the load. These kind o f systems are still in use (and new ones are still being installed) industrial in installations. The ridethrough time of several seconds enables transferschemes withmechanicalswitches. The noise of a motor-generatorset and themaintenancerequirementsof the rotating machines are not a concernin most industrial environments.They do however makemotorgeneratorsetsunsuitablefor an officeenvironment. In the configurationshown in Fig. 7.57, thenormaloperationlosses are very high which makes this an expensive solution. A numberof alternativeshave beenproposed to limit the losses. Oneoption is to have themotor-generatorset operatingin no-load when the supply voltage is within its normalrange. Themomenta sag orinterruptionis detected, a (static) switch is opened and generator the takes over the supply. A possible configurationis shown in Fig. 7.58. In normal operationthe synchronousmachineoperatesas asynchronouscondensorwhich can, e.g., be used for reactive power compensationor for voltagecontrol. When the supply isinterruptedthe static switch opens and the synchronousmachine 443 Section 7.4 • The System -EquipmentInterface r-r- Flywheel- = Power system Generator ~ Motor I-- Sensitive load - Figure 7.57 Principle of motor-generatorset. Static switch Power system- - - - - I 1-----,.- - - - - - - Load Synchronous machine Flywheel Figure 7.58 Configurationof ofT-line UPS with diesel enginebackup. Diesel engine starts tooperateas asynchronousgenerator,injecting both active and reactive power . This will provide power for one or two seconds. By using a large reactance between the load and the power system,certain a level of voltage-sagmitigation is achieved. The effect is the same as for an on-site generator.By opening the static switch on an undervoltageit is even possible tooperate the synchronousmachine as abackup power sourceduring sags as well. While the flywheel provides backuppower, the diesel engine isstarted. More recentimprovementsare the use ofwritten-polemotorsand thecombination of a motor-generatorset with power electronics. Awritten-pole motor is an ac motor in which the magnetic pole pairs are not obtainedfrom windings but instead are magnetically written on therotor [193]. This enables aconstantoutputfrequency of the generator,independentof the rotationalspeed. The mainadvantagefor use in amotorgeneratorset isthat the generatorcan be used over a much larger range of speed, so that more energy can be extractedfrom the flywheel. A combinationof the motor-generatorset with power electronicconvertersis shown in Fig. 7.59. Themotor is no longer directlyconnectedto the power system, but through an adjustable-speeddrive. This enablesstarting of the flywheelwithout causing voltage sags in the system, overspeed of the flywheel increasing ridethrough the time, and lossreduction while the set is instandby.The output of the generatoris rectified to a constantde voltage which can be utilized through a series- or shuntconnected voltage-source converteror directly fed into the de buso f an adjustablespeed drive. The ac/dc converterenables theextractionof power from the flywheel over a much larger range of speed. Supposethat a normalmotor-generatorset gives anacceptableoutputvoltage for a frequency down to 45 Hz (in a 50 Hz system). A frequency of 45 Hz is reached when the speed has droppedto 90%. Theamountof energy in the flywheel is still 81% of the energy at maximum speed. This implies that only 19% of thestoredenergy is used. 444 Chapter7 • Mitigation of Interruptionsand Voltage Sags Adjustable-speed drive ac motor Power system Figure 7.59 Powerelectronicconvertersin combination with a motor-generatorset. Supposethat we cangeneratea constantde voltage for a speed down to 50% , by using an ac/dcconverter.The energythat can beextractedis 75% of the total energy, an increase by a factoro f four. The ridethroughtime is thus also increased by a factor of four-for example, from 5 to 20 seconds. The ridethroughcan befurther increased by running the acmotor above nominal speed. Byacceleratingthe flywheel slowly, the m otor can be kept small. As the kinetic energyproportional is mechanical load on the to the square of the speed,rathersmall a increase in speed can alreadygive a serious increase inridethroughtime.Supposean overspeedof 20%. which increases the energy in the flywheel to 144% of theoriginal maximum. The extraction of energy from the flywheel stops when 25% of the original maximum remains, that so the amount of energyextractedfrom the flywheel is 119%: afactor of six more thanwith the original setup . The resultingridethroughtime is 30 seconds . 7.4.7.2 Electronic TapChangers. Electronic tap changers use fast static switches to change the t ransformation rat io of a transformer. Th is can either be a distr ibution transformeror a dedicatedtransformerfor a sensitive load. The principle of its operation is shown in Fig. 7.60, in this case with three static switches. The number of turns of the fourparts of the secondarywinding are (top tobottom): 100%, 40% , 20%, and 10% of the nominal turns ratio . Byopeningor closing these three switchestransformationratios between 100% and 170% can be achieved, with 10% steps. If all three switches are closed, the turns ratio is 100%; with switch 1 closed and 2 and 3 open it is 130% , etc. By using this electronicchanger tap , the o f nominal for input voltages down to output voltage is between 95% and 105% currently available as 56% of nominal. Transformerswith electronictap changers are ..... Power system - >>- Load ..... >>>>>- >- ,'1 :'2 1'3 Static switehe Figure 7.60 Basic principleof the constructionof an electron ic tap changer. 445 Section 7.4 • TheSystem-Equ ipment Interface an additional series componentbetween the source and the load. In future it may be feasible to install electronic tap changers on distribution transformers and save the additional component. 7.4.7.3 FerroresonantTransformers. A ferroresonanttransformer,also known as aconstant-voltagetransformer,is mainly designed to maintain constantvoltage a on its output over a range of input voltage. The basic constructionof a ferroresonant transformeris shown in Fig. 7.61. The third winding of a three-winding transformer is connected to a large capacitor. Without this capacitor,the device operates as a normal transformer.The effect of thecapacitoris explainedthrough Fig. 7.62. The solid line is the relation between voltage and current for the nonlinear inductance. The dashed line holds for the capacitor. The place where the curves cross is the operating point. Note that these curves give the voltage and current magnitude for one frequency, in this case the power system frequency as that is the frequency exciting the system. Thisoperatingpoint is independent of the supply voltage, thus the flux through the iron core is independent of the supply voltage (assuming that the ferroresonantwinding has a smaller leakage than the input winding). The output voltage is related to this flux, thus also independent of the input voltage. The energy stored in the ferroresonant winding is able to provide some ridethrough during voltage dips. A disadvantage of a ferroresonant transformer is its dependence on load changes. The inrush current of the load can lead to a collapse of the flux and a long undervoltage . A modern version of the ferroresonant transformer uses power electronic converters to keep the load current at unity power factor, thus optimizing theoperation of the transformer. power~ ~sensitive 0----3 system tl LJ Figure 7.61 Basic principle of the construction of a ferroresonant transformer . Figure 7.62 Voltage versus current diagram for a saturableinductor (solid line) and for a capacitor(dashed line). ~Ioad .: Current Ferroresonant winding 446 Chapter7 • Mitigation of Interruptionsand Voltage Sags 7.4.8 Energy Storage Severalof the controllersdiscussedabove,needenergystorageto mitigate a sag. All of them needenergystorageto mitigatean interruption.Herewe comparedifferent types of energystoragewhich arecurrently being usedandconsidered.T he comparison is basedon three different time scales,relatedto threedifferent controllers. • A seriesvoltagecontrolleris only able tomitigatevoltagesags. Atypical design value is 50%, 1 second;i.e., the controller is able to deliver 50% of nominal voltagefor 1 second.In termsof energy-storagerequirementsthis corresponds to full load for 500 ms. • A (shunt-connected)b ackup power sourceis also able tomitigate interruptions. To be able toimprove the voltage tolerancesignificantly a ridethrough between10 and 60 secondsis needed.We considerthe requirement:full load for 30 seconds. • To achievevery high reliability, sensitiveload is typically poweredvia a UPS which can supply the load for 10 to 60 minutes. During this period, backup generatorscome on line to take over the supply. The third energy-storage requirementwill be full load for 30 minutes. 7.4.8.1 DC Storage Capacitors.Capacitorsare mainly used to generatereactive power on an ac system. But in a de systemthey can be used togenerateactive power. The amountof energystoredin a capacitanceC with a voltage V is (7.69) The voltagedecreaseswhen theenergyis extractedfrom the capacitor.Capacitorscan thus not be used tosupplyelectric power to a constant-voltagede bus, asneededfor a voltage-sourceconverter.A second(de/de)'converteris neededbetweenthe capacitors and the constant-voltagebus, asshown in Fig. 7.63. Alternatively, the control algorithm of the voltage-sourceconvertercan be adjustedto variablede voltage. In either case,there will be a minimum voltage below which the converteris no longerableto operate.It is thusnot possibleto extractall energyfrom the capacitors.I f the converteroperatesdown to 50% of the maximumvoltage,75% of the energycanbe extracted.A converteroperatingdown to 25% canextract 940/0 of the energy. Considera medium-voltagecontroller using 4200 V, 1500J.LF storagecapacitors. The amountof energystoredin one capacitoris (7.70) PWM voltage-source converter Storage capacitors \ de de Variable de voltage O__ _ _....J ac Power system interface Figure 7.63 Energyextractionfrom de storagecapacitors. Section 7.4 • TheSystem-EquipmentInterface 447 Supposethat the converteris able tooperatedown to 50% of voltage. Eachcapacitor unit is able tosupply: 0.75 x 13kJ= 9.75 kJ. For a 500 msridethrough,eachunit cansupply 19.5 kW of load. A small mediumvoltage load of 500 kW requires26 capacitorunits; a largemedium-voltageload of 10MWover 1000 units. For a 30secondridethrougheach unit can only power 325W of load, alreadyrequiring 1500units for a small medium-voltageload. Thus de capacitors are feasible for series controllerswith ridethroughup to about 1 second,but not for backupvoltagesourcesrequiring ridethroughof 30 secondsand more. Various energy storageoptionsfor adjustable-speed drives arecomparedin [42]. A price of $35 is given for a 4700 JtF, 325 V capacitor.The amountof energystoredin one suchcapacitoris 250J,of which 188J(75%) can be used,enoughto powera 375W load for 500 ms or a 6.25 W load for 30 seconds. To power a small low-voltageload of 1000Wduring 500msrequiresthreecapacitorscosting$105; topowerit for half a minuterequires160capacitors,c osting$5600. For a completelow-voltageinstallationof 200 kW we need 534 c apacitors($18,700) for 500msridethroughand 32,000capacitors($1,120,000) for 30seconds.T he conclusion is the same as before: capacitorstorageis suitablefor 1 secondridethroughbut not for 1 minute ridethrough. 7.4.8.2 Batteries. Batteriesare a verycommonly used method of storing electric energy. They are used in the vast majority of UPSs sold,not only in the small one used topower a single PCbut also in larger ones whichcan power a complete installation. Batteries provide a constantvoltage so that they can be directly connected to thevoltage-sourceconverter. A 5 MVA, 2.5 MWh battery energy storage system (BESS) has been installed to power critical equipment in a large chemical facility [188]. The amountof storedenergy in this system is GJ, 9 much more than in any of the aboveexamples.An even larger installation has beeninstalled in California in 1988 for load-levelingpurposes[186]. This BESS is able tosupply 10MW during 4 hours, correspondingto 144GJ of stored energy. This installation covers an areaof 4200 m2 for the batteriesonly. Looking at smallersizes,considera car batterywith a storagecapacityof 1MJ (12 V,'23 Ah) costingabout$50. This simplebatterycontainsenoughenergyto powera 2 MW load during 500 ms, a 33 kWload during 30 seconds,or a 550 Wload during 30 minutes. One car battery containsthe sameamountof energyas 77medium-voltage storagecapacitors. The limitation with a batteryis not so muchthe amountof energystoredin it, but the speed with which this energy can madeavailable.Emptyingour be car batteryin 30 secondsrequiresa currentof 2760 A. The batterywill never beableto supplythis. If we considera maximumcurrentof 200 A, the maximumload which can be suppliedfrom one battery is 2400W. The battery can power this load for 7 minutes,which can be consideredas theoptimumridethroughtime for this battery.This fits well in equipment to mitigate interruptionsfor the time until on-sitegenerationbecomesavailable. The numberof batteriesneededand the costsof these, are given inT able 7.5 for the load sizesa nd ridethroughtimes given before. Only fors hortridethroughtimes will capacitorsbe able tocompetewith batteries. Batterieshave anumber of disadvantagesc omparedto capacitors,which may compensatethe higher costs of the latter. The commonly used lead-acid battery (on which this calculationis based),containsenvironmentally unfriendlymaterials,has a limited lifetime (in numberof rechargingcycles),and requiresregularmaintenanceto ensurea high reliability. The newer typesof batteries,which arebeing developedfor use 448 Chapter7 • Mitigation of Interruptionsand Voltage Sags TABLE 7.5 Numberof Batteries (inbrackets)and CostsNeeded toPowerSeveral Load Sizes for SeveralRidethroughTimes 500 ms 30 sec 30 min I kW 200 kW 500 kW (I) S50 (I) S50 (2) stoo (84) S4200 (84) S4200 (364) SI8,000 (209) SIo,oOO (209) $10,000 (910) $46,000 IOMW (4167) $210,000 (4167) $210,000 (18182) S910,000 in electrical vehicles, do not have these disadvantagesbut they obviously have higher costs. 7.4.8.3 Supercapacitors. Supercapacitors(or double-layercapacitors)are propagated as a future solution for energy storage to improve equipmentvoltage tolerance. They have energy densities comparableto batteries, but much longer lifetime and much lessmaintenancerequirements. Theirdisadvantageis that they are only of 3.3 F, 5.5 V ismentionedin [189]. available for voltages of a few volts. A value The amountof stored energy is5 0J, only 1/5th of the4700J.l,F, 325V capacitor. Like with a battery, there is a limit to the speed with which energy be canextracted from a supercapacitor.F or the supercapacitorscurrently in operation, the discharge time cannotbe less thanabout 1 minute . This makes them somewhat faster than batteries but still much slower thancapacitors. The development ofsupercapacitorsis mainly o f electric vehicles, where the a mountof storedenergy is driven by the requirements of more importancethan the speed with which it can be extracted . 7.4.8.4 Flywheels. An alternative which is currently being investigated is the storage of energy in fast-spinning flywheels. The classicalmotor-generatorset, discussed before, already uses this principle, but the modern equivalent rotates at a much higher speed. By using magnetic bearings and vacuum sealing of rotating the [192], values up to 90,000 rpm parts , very highrotational speeds can be achieved have been reported [l90J. A possible configuration is shown in Fig. 7.64. The flywheel isbroughtup to speed by an ac adjustable-speed drive. This drive also ensures that rotational speed of theflywheel remains within a certain range during standby operation.During a voltage sag or an interruptionthe brushless de generatorextracts From the power system Brushless de generator ~ To the power ''' _ ~~~ ~~ , - - system Inertia Figure 7.64 Configurationof a flywheel energystoragesystem and itsinterfaceto the power system. 449 Section 7.4 • TheSystem-EquipmentInterface energy from the flywheela nd suppliesthis to the power system via ade/deconverter and a voltage-source(dc/ac) converter. Considera solid cylindrical pieceof materialwith a length of 50 em and a radius of 25 em. Theinertia of this pieceof material,for rotationalongthe axisof the cylinder, is J = ~mR2 (7.71) with m the massand R the radiusof the cylinder. With a specific massof 2500 kg/m" we find for the mass: m=n X 0.252 x 0.50 x 2500 = 245 kg and for the inertia: J = 2:1 x 245 x 0.252 = 7.7kgm2 The kinetic energyof an intertia J rotating with an angularvelocity (J) is £ = !J(J)2 2 (7.72) If we rotate our cylinder at the "moderate" speed of 3000 rpm (w = 21r X 3~ = 314radjs,the amountof kinetic energystoredin the rotating cylinder is 1 £ =2 x 7.7 x 3142 = 380kJ This energycannotbe extractedcompletely,as the energyconversionbecomes inefficient below acertain speed. Supposethis to be 50% of the maximum speed. The amount of useful energy is again 750/0 of total energy, in this case 0.75 x 380kJ = 285kJ. This flywheel is thus able to power a 570kW load for 500ms, a 9.5kW load for 30 seconds,o r a 160W load for 30 minutes. Increasingthe rotational speed to 25,000 rpm by using the newest technologies, increasesthe amountof storedenergyto 1 £ = 2 x 7.7 X 26182 = 26 MJ The useful energy of 0.75 x 26MJ is enoughto power a 40MW load for 500ms, a 650kW load for 30 seconds,or an II kW load for 30 minutes. 7.4.8.5 Superconducting Coils.It is well known that an inductor L, carrying a current i, containsan amountof energyin its magneticfield equal to (7.73) This would makean inductor an alternativeform of energystorage,next to thecapacitor. The reasonthat inductorstorageis not commonlyused isthat the currentcauses high losses in the wirem akingup the inductor.The losses due to current a i are equalto (7.74) with R the total seriesresistance.S upposethat we can achieve anX jR ratio of 100 for the inductor. In that case we find for the losses: 450 Chapter7 • Mitigation of Interruptionsand Voltage Sags (7.75) To compensatefor the resistivelosses,the energycontentsin the coil has to be suppliedthree times a second. A solutionsuggestedseveralyearsago is tostorethe energyin a superconducting coil. The resistanceof a superconductoris (exactly) zero sothat the current will flow forever without any reductionin magnitude.A possibleconfigurationfor sucha superconducting magnetic energy storage (SMES)is shownin Fig. 7.65.The variablecurrent through the superconductingcoil is convertedto a constantvoltage. The constantvoltage de bus isconnectedto the (ac) power system by meansof a voltage-source converter.The coil currentclosesthroughthe de/deconverterwhich causesa small loss. The configurationofSMESdevices isdiscussedin moredetail in [57], [158], [160], [162], [169]. Refrigerator Constant-voltage de bus Superconducting coil t Power system interface Figure 7.65 Energystoragein a superconductingcoil and interfacewith the power system. Oneapplication[158] uses a 1000 Acurrentthrougha 1.8 H inductor. The energy storedin the magneticfield is 1 £ == 2" x 1.8 X 10002 = 900kJ (7.76) Assumethat the de/deconverteroperatesfor currentsdown to 50% of the maximum current. The usable energy is in this case 0.75x 900kJ = 675kJ. This is enough to power a 1.35MW load for 500 ms, a 22.5 kWload for 30 seconds,or a 375 W load for 30 minutes. The device describedin [158] operatesas a shunt-connectedbackup power source;it is used tomitigatevoltagesagsand shortinterruptionswith durations up to a fewseconds. Commercialapplicationsof SMES devices arereportedfor storedenergyup to 2.4 MJ and power ratings up' to 4 MV A. The devicescurrently in operationuse lowtemperaturesuperconductors w ith liquid helium as acoolingmedium.A demonstration SMES using high-temperaturesuperconductorshas beenbuilt which is able tostore 8 kJ of energy.This is still two ordersor magnitudeaway from the devices using lowtemperaturesuperconductors,but the manufacturerexpectsto build 100 kJ devices in the nearfuture. A study after the costsof SMES devices nowand in 10 years'time, is describedby Schoenunget al. [168]. For example, a 3MW, 3 MJ unit would cost $2,200,000now, but "only" $465,000in 10 years' time. The main cost reduction is basedon the so-calledlearningcurve due to the productionof about 300 units in 10 years.By using the datain [168] the costshavebeenplotted as afunction of the stored energy,resultingin Fig. 7.66. In Table7.6 thecostsof energystoragein a SMESare comparedwith the costsof batteriesand capacitors.The costs of the power electronicconvertershave not been 451 Section 7.4 • TheSystem-EquipmentInterface 5-------------------, • Costs now in 10 years time o Costs 4 ~ 3 ~ 2 .8 o .. Figure 7.66 Costs ofsuperconducting magnetic energystorage(SMES) including the power system interface, asfunction a of the amountof stored energy.( Data obtained from [168].) TABLE 7.6 n 0 o 0 0 0 0 o .. o 0 o o o 00 0 0 00 o~_w.......:==----+----+-----+-----f 10 0.1 100 1000 Stored energy in MJ CostsComparisonof SMES, BESS andCapacitors Costs of EnergyStorage RidethroughTime Power 300 kW 3MW I sec 60 sec I sec 60 sec BESS SMES $6300 $6300 $63,000 $63,000 $183,000 $389,000 $411,000 $1,064,000 Capacitors $56,000 $3,350,000 $558,000 $33,500,000 included, as these are similar for all energy storage methods. The costsbattery of a energy storage system (BESS) is based on the same batteriesas used before: 1MJo f storage, 2400Wof power for $50. The costs of capacitorstorage is based on 188 J of storage for $35 as used before. Additional costs ofconstruction,wiring, protection, cooling, etc., have not been included for the capacitorsor for the batteries. We see that, withcurrent prices, battery storage remains by far the cheapest solution, even if we consider a factor of two to three for additional costs. But the lifetime of a battery is limited in number of discharge cycles, andbatteriescontain environmentallyunfriendly products.When the costsof SMES devices go down and the costs of batteries go up in the future, the former will become a more attractive option for high-power short-time ridethrough.For short-time ridethroughcapacitor storage is still moreattractive,especially if one realizes that we used low-voltage capacitors where medium-voltage capacitorsare likely to form acheaperoption. Note that the amountof energystoredin an SMES is similar to theamountof energy stored in abattery.The main difference isthat the energy in asuperconducting coil can be made available much faster. The units currently in operationare able to extract 1MJ of energy from the coil in 1 second. The limitation in energyextractionis the voltage over aninductor when thecurrentchanges: di V;nd dc = L Cit (7.77) The energyextraction p/oad is related to the change in currentaccordingto ~ H3 Li c} = P10ad (7.78) 452 Chapter7 • Mitigation of Interruptionsand Voltage Sags which gives for thevoltage over the inductor: . V ind - P/oad . 'de (7.79) With constantenergy extraction (constant p/oad) , the induced voltage increaseswith decreasingcurrent. For a 500 kW load and a minimum current of 500 A, the voltage over the coil is 500kW V;nd = 500A = lOOOV (7.80) For a 3MW unit we get V;nd = 6 kV. The de/de converter should be able to operatewith this voltageover its input terminals. Summary and Conclusions This chaptersummarizesthe conclusionsfrom the previouschapters.Next to that some thoughtsare givenconcerningthe future of this area of power engineering. Just like in the rest of thebook, the emphasisis on voltage sags and interruptions. 8.1 POWER QUALITY In Chapter I the term "power quality" and several related terms are defined. Power quality is shown to consistof two parts: "voltage quality" and "currentquality." The voltagequality describes the way in which the power supply affects equipment;as such it is part of the quality of supply. Current quality describes the way in which the equipmentaffects the power system and part is of the so-called"quality of consumption." The termelectromagneticcompatibility (EMC) has a largeoverlapwith "power quality" and the terms can often be used as synonyms. An overview is givenof the various types of powerquality disturbances.An important distinction is made between"variations" and "events." Variations are a continuous phenomenon, e.g., the variation of the power system frequency. Measuringvoltage andcurrentvariationsrequirescontinuousrecordingof their values. Events only occur occasionally: voltage sags and interruptionsare typical examples. Measuringvoltage andcurrentevents requires a triggering process: e.g.,ems the voltage becoming lessthan a pre-definedthreshold.These two typesof power quality disturbances also requiredifferent analysis methods: average andstandarddeviation for variations;frequencyof occurrencefor events. The main subjecto f this bookis formed by voltage sags and interruptions:the two mostimportantexamples from a familyo f voltage events known as "voltagemagnitude events." Voltage magnitudeevents aredeviationsfrom the normal magnitude(ems value) of the voltage with arather well-definedstarting and end time. Themajority of these events can be characterizedby one magnitudeand oneduration. Different initiating events and differentrestorationprocesses lead to different rangesof magnitude andduration.Based on these ranges, a classification of voltagemagnitudeevents is proposed. 453 454 Chapter8 • Summaryand Conclusions 8.1.1 The Future of Power Quality There is one questionthat always comesup when thinking about the future of powerquality: "Will the powerquality problemstill be amongus in 10 years time?" It may well bethat equipmentwill be improvedin such a waythat it no longeris sensitive to the majority of voltagedisturbancesand that it no longer producesseriouscurrent disturbances.In other words, equipmentwill have becomefully compatiblewith the power supply. At the moment, however, there is no indication that this will happen soon.Equipmentappearsto be assensitiveandpolluting as ever. Abrowsethroughthe advertisementsin power-qualityorientedjournalsshows that the emphasisis on mitigation equipment (surge suppressors,UPSs, custom power) and on power-quality measuremente quipment.Advertisementsin which equipmentwith improved voltage toleranceis offered are extremelyrare. The main drive for improved equipmentis likely to come from standards,in particular the IEC standardson electromagneticcompatibility. When the standards on harmonic currents produced by end-userequipment (lEe 61000-3-2 and -3-4) becomewidely accepted,the harmonic distortion problem may be the first one to move to thebackground. Voltage quality eventslike voltage sags will take even longer to becomepart of equipmentstandards.A t leastvoltagesags arereasonablyunderstoodnowadays(read Chapters4, 5, and 6). Higher frequencyphenomenalike switching transientsare less well understood,more difficult to model, and their statistics probably show more variations among different customers.Still they causeequipmentproblems. Highfrequencydisturbancesmay well becomethe next bigpower-qualityissue. 8.1.2 Education An importantaspectof powerquality is education:educationof those who come in touch with power quality problemsas well as newgenerationsof engineers.Power quality may bring power engineeringeducationcloser to the actual aim of power engineering:generatingelectrical energyand delivering it to electricalend-userequipment. Educatinga newgenerationof engineersis obviouslya taskfor universities. And with engineersI am not only referring to power engineers.Every studentin electrical, electronic,and mechanicalengineeringshould know aboutpotential problemsdue to the connectionof equipmentto the powersupply.Note that these are thepersonsto use electricalequipmentandto designfuture equipment.When they areawareof potential compatibility problems,they are more likely to comeup with equipmentthat is compatible with the supply. Postgraduateeducationis importantand not necessarilya task for a university. Severalcompaniesoffer good power-qualitycoursesthat enablepeoplein industry to solve the problems they encounter.However, universities are better suited to give theoreticalbackgroundsneededto solve future problems,next to providing an understandingof existing problems. 8.1.3 Measurement Data From the beginning,power quality has been anareavery much based on measurementsand observations.T he standardtools in use atuniversities,simulationsand theoreticalanalysis;are much less used in thepowerquality work. In fact, theamount of universityresearchon powerquality is still very limited. This will certainlychangein Section 8.2 • Standardization 4SS the near future; powerquality will not only find its way into educationbut also into university research.There is a serious risk herethat a gap will develop between the heavily measurement-based power-quality practice and the very much theory- and simulation-baseduniversity research. Such situation a may be preventedif utilities education.A make much moreof their data available for university research and very good example is set by IEEE Project group 1159.2. At their Website (accessible through www.standards.ieee.org) a number of voltage recordings are available for downloading.I would like to see much more utilities making d ata available in this way: not only theactual voltage andcurrent recordings but also some basic data aboutthe kind of event and the kind of power system involved. 8.2 STANDARDIZATION In the secondpart of Chapter1, power qualitystandardsare discussed. The IEC set of standardson electromagneticcompatibility offers the opportunity to seriously solve several powerquality problems.The standardsdescribe variouspower-qualitydisturbances, define testingtechniquesand give requirementsfor equipmentand system performance.A large number of standardsis still under developmentand even more arerequired to fully standardizeequipmentas far as power quality and EMC is concerned.In Chapter1 some suggestions are given for the extension of the concept "compatibility level" from variationsto events. The Europeanvoltage characteristicsstandard,EN 50160, is described in detail. The standardgives a gooddescriptionof the voltage quality forvoltage.variations,but is ratherweak for voltage events. 8.2.1 Future Developments Developmentsin this area will unfortunatelytake a long time, sothat power quality problemswill be aroundfor at least several more years. This is simply inherent to the standard-settingprocess.During my work on someIEEE standards,it became of clear that one can only take one step at a time. The first step, making people aware power quality problems,has beentakenboth within the IEC and within the IEEE. The recently publishedIEEE standardon compatibility between electronic process equipment and the power system ( IEEE Std. 1346-1998) may be the first of a long series of IEEE standardson this subject. AlsoChapter9 of the 1997 editionof the IEEE Gold Book (IEEE Std.493-1997) willcontributeto the power-qualityawareness. It is interesting to notice that both documentswere already being used and referred to several years before theyactually became accepted as standarddocuments.The same has happenedwith several IECstandards,noticeablythe one limiting theharmoniccurrent distortion by low-powerequipment(IEC 61000-3-2). BothIEEE and lEe shouldmake their draft documentsavailableto a much wider audience. This will not only widen the discussion but also speed up the acceptanceprocess of thestandard. The EuropeanvoltagecharacteristicsstandardEN 50160 is one of the first documents quantifying the voltage quality experienced by customers. Despite allshortits comings, thepublicationof this standardhas triggered morecoordinatedmeasurement campaignsthan before. Thefuture will bring the publicationof local equivalentsof EN 50160. 456 Chapter8 • Summaryand Conclusions 8.2.2 Bilateral Contracts An arearelated to powerquality standards,but likely showingmuchfaster development,is formed by thebilateral contractsbetween utilitiesand customers.Several examples arealreadyin place where the utility pays compensationto its customerswhen the quality of supply drops below a certainlevel. The typicalcontractdefines a maximum-acceptablenumberper year for each event type, e.g., two long interruptions,five shortinterruptions.When thisnumberis exceeded within acertainyear, the utility pays a predefinedamountof compensationfor eachadditional event. The initialcontracts only containedinterruptions,but voltage sags have been implementedin a numberof contractsas well. When setting up these contracts,a precise definitionof the various events is essential. Next to these bilateral contracts,utilities are likely to come up with generalcompensationschemes forcustomerswith a bad voltagequality. When utilities refuse to take these steps they may be forced into worse constructionsby political and legal developmentsoutsideof their control. The conceptof bilateralcontractsis likely to beextendedto the interfacebetween transmissionand distribution systems. At thisinterfacevoltage quality becomes even more two-directionalthan at the utility-eustomerinterface. Voltagedisturbancesmay originatein either system. 8.3 INTERRUPTIONS A long interruption is an interruption of the power supply followed by amanual restoration.When the supply isrestoredautomaticallythe result is ashortinterruption. Long interruptionsare discussed inC hapter2, short interruptionsin Chapter3. Long interruptionsare by far themostserious voltagequality disturbance.M ost utilities keep a record of frequencyand durationof long interruptions.Unfortunatelymuch of this very usefuldata is not generally accessible. A positive exceptionto this is theUnited Kingdom where utilities are obliged topublish data on the supply performance. Currently this only includesinterruption data but it is likely to beextendedto other types of events. Short interruptionsare shown to be due to combinationof a automaticreclosing and a system design aimed at limiting the numberof reclosers.Automatic reclosing a itigation makesthat a longinterruptionbecomes ashortinterruptionand is as such m method.But limiting the numberof reclosers makesthat customersexperience ashort interruptionthat otherwisewould have experienced a voltage sag. Removingthe whole the supply for somecustomersbut an improvereclosure scheme is deteriorationof a ment for others. A detailed analysis ispresentedof voltages andcurrentsassociatedwith singlephasetripping. It is shown that single-phasetripping leads to less severe voltage events at theequipmentterminals,but it may also lead to a higher percentageof second trips. A numberof pilot schemesshouldbe set up wheresingle-phasetripping is used for the first attemptand three-phasetripping for the secondattempt. 8.3.1 Publication of Interruption Data In the future more utilities will publish interruptionfrequency andsupply availability. For customersto be able to assess the compatibility betweenequipmentand supply, it is essentialthat utilities publishthe supplyperformance.As interruptiondata Section 8.4 • Reliability 457 are already available, this will be the first to be published. A likely developmentis that utilities publish more than just frequency and availability over the whole country. Details like "worst-servedcustomers,"regional variations, and distribution of the interruptiondurationwill give more insight into thequality of supply experienced by a individual customers.Publicationof more statistics will inevitably lead to comparison between different utilities and regions. To obtain a fair comparison,many years of observationmay be needed. Alternatively satandardizedreliability evaluation tool can be used to predict the supply performance.As most interruptionsoriginate in the distribution system, relatively simple techniques may be sufficient. The increase inobservationdata will probably not include data on short interruptions, at least not initially.Getting data on short interruptionsfor all customers requires an extensive monitoring effort. For short interruptions,prediction methods of getting datafor all customers. These predictionmethmay be the only suitable way ods may be"calibrated"throughmonitoring at a limitednumberof sites. 8.4 RBLIABILITY The secondpart of Chapter2 summarizes the various aspects of power system reliability and the stochastic analysis techniques currently in use: network modeling, Markov models, andMonte Carlo simulation. Various examples are given for each of these techniques. Different aspects are given for the reliability analysis of generation, transmission,and distribution systems (the three so-called "hierarchicallevels"). For the industrial power supply a systematic methodologyis given that can be used to obtain the reliability of the supply. Thismethodologyconsistsof six layers, partly correspondingto the hierarchical levels but also including power quality and equipment failure. 8.4.1 V.rlflcatlon Power system reliability has two distinctly different faces: the observed reliability of numberand and the predicted reliability. Observed reliability, i.e., keeping records durationof interruptions,is the domainof the utilities; predictedreliability, i.e., reliability evaluation,is thedomainof universities;without much overlapbetween these two sides. A comparisonbetween observed and predicted reliability is needed to move forward in reliability evaluation.For this, utilities should provide thedata and universities the analysis and prediction techniques. Only such caomparisonwill give a clear answera boutthe accuracyof the variousstochasticpredictiontechniques. Such a of stochasticpredictiontechniques and comparisonwill also lead to a wider acceptance to a wider useof them within the utilities. 8.4.2 Theoretical Developments Potentialdevelopments on the theoreticalside are the inclusionof nonexponential repair-time distributions and of common-modeeffects. In both cases thedata requirements are high. This again calls for a closer cooperationbetween utilities and universities. Muchof the theoretical work on power system reliability has been directed toward transmission systems. In the near future, distribution networks will become much more a focus of the research. The main theoretical bottleneck is again thedistribution of the interruptionduration. By using theexponentialdistribu- 458 Chapter8 • Summary andConclusions tion erroneousresults areobtained,especially for thenumberof very long interruptions. 8.5 CHARACTERISTICS OF VOLTAGE SAGS In Chapter4 the various characteristicsof voltagesags are discussed. After the more "classical"characteristics,m agnitudeand duration, two newercharacteristics,phaseanglejump and three-phaseunbalance,are treatedin considerabledetail. Techniques are presentedto calculatethese sagcharacteristicsfor a given fault and loadposition and fault type. Thetechniquesare applied to an example supplyconsistingof several voltage levels. Chapter4. Phase-angle j ump andthree-phaseunbalanceare discussed in detail in Especially three-phaseunbalanceis an important characteristic.The currently used definition of sagmagnitudeis not suitablefor three-phaseequipment.The definition of sagmagnitudeis generalized forthree-phaseunbalancedsags leading to a classificaof which two types (C and D) tion of three-phaseunbalancedsags into seven types, cover the majority of sags. A three-phaseunbalancedsag is quantified through a characteristiccomplex voltage which isindependento f voltage level or loadconnection. Magnitudeand phase-anglejump are absolutevalue andargument,respectively,of the characteristiccomplex voltage. The possible rangemagnitudeand in phase-anglejump is calculated,for single-phaseas well as forthree-phaseequipment,for the example supply as well as in general. Chapter4 concludeswith a treatmentof two additionalsagcharacteristics,pointon-wave and missing voltage, discussionaboutload a influence on voltage sags, and a brief treatmentof voltagesags due toinduction motor starting. 8.5.1 Definition and Implementation of Sag Characteristics The variouscharacteristicsdiscussed here a nd othersrecentlyintroduced,need to be applied tomeasuredvoltage sags. This will giveinformation about their statistics be these and about the rangeof values that can be expected. The next step will that additional characteristicsare implementedin commercially available power quality monitors. Before that stage isreached,it is essentialthat all sag characteristicsare uniquely defined. This willprevent confusion due to different manufacturersusing different definitions. Missingvoltagemay become acompromisebetween the different magnitudedefinitions used onboth sides of theAtlantic (voltagedrop versusremaining voltage). Thedisadvantageof using missing voltage is t hat the majority of single-phase equipmentis affected by theremainingvoltage, not by the missing voltage. The application of point-on-wavecharacteristicsmay be limitedto.a small group of equipment. But in any case, all these characteristicsdescribepart of the quality of supply and statisticalinformationaboutthem shouldbe partof the outcomeof voltage sag surveys. 8.5.2 Load Influence An areathat has beensomewhatforgottenin the variousvoltage sag studies is the effect of load on the voltage sag characteristics.A qualitativestudyof the effect of large inductionmotorsis describedin Chapter4. For a quantitativestudy of all types of load, a detailed analysisof measuredvoltage sags is needed. Such a study should include large and smallm otor and electronicload as well asembeddedgeneration.The effect of the loaddetermineshow the sagcharacteristicschangewhen a voltage sag propagates Section 8.6 • EquipmentBehaviordue to Voltage Sags 459 from high voltageto low voltage.Observationshaveshownthat a sag with amagnitude (remainingvoltage) of 40% at 132 kV is seen as a sag with magnitudeof a 60% at 400V. 8.8 EQUIPMENT BEHAVIOR DUE TO VOLTAGE SAGS In Chapter5 the effectof voltagesags onequipmentis discussed. Theemphasisis on single-phase rectifiers (computers, consumer electronics, process controllers), ac adjustable-speeddrives, and de adjustable-speeddrives. Single-phaserectifiers are affected bymagnitudeand duration of the voltage sag. They trip when thevoltage drops below acertainmagnitudefor longer than a certainduration(resultingin a socalled "rectangularvoltage-tolerancecurve"). The voltage toleranceof the equipment can easily beimprovedby addingadditionalcapacitanceto the internaldc bus. Using a elegantbut also voltage regulatorthat can operatedown to a lower voltage is a more more difficult solution. For three-phaserectifiers, as used in ac adjustable-speed drives, it is mainly the characteristicmagnitudeand the sag typethat affect the de busvoltage and thus the drive behavior.The amountof capacitancecurrentlyin use in ac drives is too small for the sagdurationto haveany influence.Making the drivetolerantagainstbalancedsags requiresseriousimprovementsin the designof the PWM inverter. For balancedsags the dc-busvoltagedropsto a lower value(equalto the sagmagnitude,in pu) within one o f the dc-buscapacitanceis very or two cycles.For three-phaseu nbalancedsags the size important. If the capacitanceis large enough(in the upper range of the amount of capacitancecurrentlyin use) thedc-busvoltagewill not drop below 80% for any threephaseunbalancedsag. If the drive is able to stay on-line, the effectof the sag on the load will be very small. DC adjustable-speed drives areshown to be very sensitive tovoltage sags. The armaturecurrent and the torque drop to zero almost immediately,even for arather shallow sag. As de drives are typically used for speed-sensitiveprocesses, thed rop in speedassociatedwith the zerotorquewill easily lead to adisruption of the process. 8.8.1 Equipment Testing An importantfuture step is thedevelopmento f a testingprotocol for equipment. This will enablethe customerto comparethe voltagetoleranceof different devices.For single-phaseequipmentit is probably sufficient to test fordifferent magnitudeand duration. Possibleexceptionsare contactors(affected by point-on-wave)and equipment with controlled rectifiers (affectedby phase-anglejump). Testingof three-phaseequipmentwill be much more complicated:even for noncontrolledrectifiers, thecharacteristicphase-anglejump affects thedc-busvoltage. For de drives the threephasesare nolongerequivalentso that the numberof testsrequired increasesby a factor of three. Three-phaseequipmentneeds to be tested for several types of three-phaseunbalancedsags and for a range of magnitude,duration, and phase-anglejump. Further analysisof monitoring results is needed too btain realistic values for therangeof characteristicsto be included in the tests. Another problem that needs to be solved is the definition of the testcriterion. Whethera certainreactionis acceptabledependsto a largeextendon the processdriven by the drive. A possiblesolution is to give the variation in speedand torque as a of the effectof the function of the sagcharacteristics.This will enablean assessment sag on theprocesswhen using acertaindrive. 460 Chapter8 • Summary and Conclusions 8.6.2 Improvement of Equipment Improvementof equipmentoffers the only long-termsolutionto the power quality problem. As shown inChapter5, the effect of the sag can be mitigated for many devices by installingadditionalcapacitance.There are somedrawbackswith this, the first being the additional costs. A risk of additional capacitanceis that the inrush of fuses current on voltage recovery becomes more severe. This may lead to blowing or to damageon power electroniccomponents. Installing additionalcapacitancehas its limits. It is not feasible for making drives toleratebalancedsags and it is in most cases not feasible at all for de drives. More advanced rectifiers, inverters, and control algorithmsare needed to achieve this. There is not yet a drivetoward improvedequipmentbut somewhere in the (hopefully not too remote) future this willhappen.Possible driving forces are standardized a testing protocol; equipmentimmunity requirementsaspartof the EMC standards;and, of course, a demandfor improvedequipmentfrom the sideof the customer. 8.7 STOCHASTIC ASSESSMENT OF VOLTAGE SAGS Chapter6 discusses the stochasticand statisticaltreatmentof the compatibility between equipmentand supply.Dataaboutthe performanceof the supply can be obtainedfrom power quality monitoringand fromstochasticpredictionstudies.Monitoring may give a more accuratepicture of the kind of disturbancesto be expected, butstochastic predictionwill give results in a muchshortertime. Different methodsare discussed to present the results of stochasticassessment a study (either powerquality monitoring or stochastic prediction). The so-called "voltage-sagcoordinationchart" is shown to be a useful instrumentfor the compatibility assessment. The results of a numberof largepower-qualitysurveys are presented and compared.One of the conclusionsis that a further treatmentis needed of the propagationof voltage sags from the faultposition to lower voltage levels. The above-mentionedeffect of load on the sag characteristicswill play an important role in such studies. Two methodsare presentedfor the stochasticprediction of voltage sags: the method of fault positionsand themethod of critical distances. Themethod of fault positionsis suited for computerizedcalculationsin large meshed(transmission)systems. Themethodof critical distancesis suitable for simplehandcalculationsand for calculationsin radial (distribution) systems. 8.7.1 Other Sag Characteristics All the techniques discussed Chapter6 in concentrateon magnitudeand duration of voltage sags. To cover a wider range equipment,new of techniques have to be developed for theother sagcharacteristics:phase-angle jump;three-phaseunbalance; point-on-wave.Some suggestions are given in the text.problemwith A theseadditional sagcharacteristicsis that the equipment'sreaction to them is not known, not even in a qualitativeway. 8.7.2 Stochastic Prediction Techniques Stochasticprediction techniques willcontinue to be further developed: both detailedcomputerizedtechniques using the methodof fault positions as well as simpli- Section 8.7 • StochasticAssessment of Voltage Sags 461 tied methodslike the methodof critical distances. These developmentswill reduce the gap between powerquality and reliability evaluation.In fact, stochasticprediction of voltage sags may be consideredaspart of the reliability evaluationof the power supply. Stochasticpredictionof voltage sags based on the methodof fault positionsis likely to become astandardpart of power-system analysis software, next to load flow, shortcircuit currentcalculations,transientstability, etc.Calculatingthe expectednumberof voltage sags may become common as as calculatingthe short-circuit current or the normal operatingvoltage. It is likely that the first commercially availableprogramswill only give results for magnitudeand duration.But soon morecharacteristicsmay becomepart of the calculation results:three-phaseunbalancebeing the most essential one. The methodof critical distances willcontinueto playarole. It may becomepart of the stochasticprediction software, e.g., to estimate the extent of and distance between the fault positions. The method of critical distances remains much more powerful than the methodof fault positionsfor fast "back-of-the-envelope"calculations. An exampleof the latter is the simple expression derived in the last section of Chapter6. This expression estimates the number of sags due to faults in a meshed transmissionsystem. Thedrawbackwith this expression isthat there is(not yet) any theoretical basis for it. Further studies andcomparisonsmay teach usabout this expression'saccuracy level. 8.7.3 Power Quality Survey. Power quality surveys will alsocontinueto be performed.In fact quite a large numberof them is going on at the moment, even thoughthe statisticsare not actually being collected in all cases. The numberof publicationsof survey results will however become less, as they are likely to show "more of the same."This is anunfortunatebut understandable development. There is a small hope however that the datawill be made available for further research, e.g., resulting in statistics for three-phaseunbalance, phase-anglejump, point-on-wave, and any other possible sagcharacteristic.Such data provide very useful results needed to assess voltage-tolerance the requirements of equipment. in reports, is still very The amount of survey results published, even internal limited. There must be gigabytes of very interestingmonitoringdatastoredat utilities all over the world, waiting to be processed. Only ten years ago it was very difficult to get power systemmeasurementsfor research purposes. Soon the situation may be that there is a surplusof data for which there are no directapplications.This should of course not stop any utility from installing monitors.The only way of getting an accurate picture of the quality of supply at any given location (i.e., not only sags and interruptionsbut the wholespectrumof disturbances)is still by meansof measuring. 8.7.4 Monitoring or Prediction? Both monitoring and stochasticpredictionare mentionedas a wayof obtaining information aboutthe supplyperformance.Monitoring is still the methodmost commonly used: it gives not onlyinformation on voltage sags but also on other voltage events andvariations.Much of thisinformationis still very hardto obtainby stochastic predictiontechniquesexist andobtainprediction.For voltage sags, however, powerful ing accurateresults through monitoring may take many years.For individual sites stochasticprediction is most suitable; toobtain the average powerquality over a 462 Chapter8 • Summary andConclusions large area (e.g., a whole country) monitoring is more suitable. Bycomparingmonitoring and prediction results thetrust in prediction techniquesis likely to grow, and the comparisoncan be used tofurther develop thepredictiontechniques. 8.8 MITIGATION METHODS In Chapter7 various methodsfor the mitigation of voltage sags andinterruptionsare discussed. This is theultimate aim of any powerquality investigation: to solve the problem. Thechapterstartswith an overviewof mitigation methods.Each methodis briefly discussed: reducing the numberof faults; reducing thefault-clearingtime; changing the power system;installing mitigation equipment; and improving equipment immunity. For different types of events,different mitigation methodsare most suitable: improving the equipmentfor short-durationevents, improving the system for longdurationevents. Power system design and mitigation equipmentare discussed in more detail. The two improvementmethodsin power system design are parallel operationof components and switching to an alternativesupply. Until a few years ago, thelatter would only besuitableas amitigation methodagainstlong interruptions.For sagmitigation only certaintypesof parallel operationwere suitable. Theintroductionof the mediumvoltagestaticswitch makes it possible to mitigatevoltage sags by very quickly switching to a healthysupply. This may make radial operationa more reliable supplyalternative than parallel operation. Several types ofmitigation equipmentare discussed in C hapter7. Theemphasisis on shunt and seriescontrollers based onpower-electronicvoltage-sourceconverters. Throughtheseconvertersit is possible tocompensatefor the drop in system voltage or even totemporarilytake over thesupplycompletely.For not too deep voltage sags it is possible tocompensatethe drop in voltage magnitudeby injecting reactivepoweronly, latter calls but for a full compensationboth reactive and active power are needed. The for a certain amountof energystorage.A numberof energystorageoptions are discussed in the last section Chapter7: of both classical ones(batteries,capacitors)as well as some of the more recently introducedones (superconductingcoils, high-speed flywheels,supercapacitors). A comparisonof the variousoptionsshowsthat batteriesand capacitorsremain themost-suitable options:capacitorsfor ridethroughtimes around one second;batteriesfor ridethroughtimes of 10 minutesand longer. The mostcommonly used method remains theinstallation of mitigating equipment at theutility-customerinterfaceor at theequipmentterminals.The uninterruptible power supply has become standardpieceof a equipmentin many installations. This simply takes away lots o f worries aboutthe quality of the supply. It is also in many cases the only possible solution: manycustomersdo not have the possibility toopt for improved equipmentor for an improved power supply. A recentdevelopmentis the installationof large mitigation equipmentat theutility-eustomerinterfaceprotectinga whole plant againstsupply disturbances.This may be thecheapestshort-termsolution, but it should not be used as an excusestop to the installationand developmentof lesssensitiveequipment. 8.9 FINAL REMARKS Powerquality is an areaof power engineeringthat did not exist only 10 years ago. Powerquality and reliability have formanyyears beenpart of power system design and operation,but they were rarelyconsideredas a separatearea. Being a new area, the Section 8.9 • FinalRemarks 463 developments in power quality are fast and difficult to predict. A new device may be inventedtomorrow solving all voltage sagproblems. A more likely developmentis that sensitiveequipmentwill stay amongus for a long time to come.Certainlyshort and longinterruptionswill remain a problem.The power quality area willfurther expandand likely develop into two new areas: a nontechnical area covering"customer-utility interactions"and a technical onethat will merge withelectromagneticcompatibility("equipment-system interactions").An additional spin-off of the developmentsin power quality will be that power system education and research will be much more measurementbasedthan in the past. Regardlessof what the future will bring, powerquality in all its varieties will offer utilities, equipmentmanufacturers,customers,and universities a very interestingfield of study, on which lots ofcooperationis needed and possible. Bibliography [I] T. S. Key, Diagnosing power-quality related computer problems, IEEE Transactions on Industry Applications, vol. 15, no. 4, July 1979, pp. 381-393. [2] M. F. McGranaghan, D. R. Mueller, and M. J. Samotej, Voltage sags in industrial power systems, IEEE Transactions on Industry Applications, vol. 29, no. 2, March 1993, pp. 397403. [3] IEEE recommended practice for monitoring electric power quality, IEEE Std. 1159-1995, New York: IEEE, 1995. [4] Electromagnetic compatibility (EMC), Part 2: Environment, Section 2: Compatibility levels for low-frequency conducted disturbances and signalling in public low-voltage power supply systems, lEe Std. 61000-2-2. [5] Measurement guide for voltage characteristics, UNIPEDE report 23002 Ren 9531. UNIPEDE documents can be obtained from UNIPEDE 28, rue Jacques Ibert, 75858 Paris Cedex 17, France. [6] R. Wilkins and M. H. J. Bollen, The role of current limiting fuses in power quality improvement, 3rd Int. Conf. on Power Quality: End-use applications and perspectives, October 1994, Amsterdam. [7] Lj. Kojovic and S. Hassler, Application of current limiting fuses in distribution systems for improved power quality and protection, IEEE Transactions on Power Delivery, vol. 12, no. 2, April 1997, pp. 791-800. [8] L. E. Conrad (chair), Proposed Chapter 9 for predicting voltage sags (dips) in revision to IEEE Std 493, the Gold Book, IEEE Transactions on Industry Applications, vol. 30, no. 3, May 1994, pp. 805-821. [9] J. A. Demcko and S. Sullivan, Power quality problems and solutions at Arizona public service company, 7th IEEE Int. Coni on Harmonics and Quality of Power (ICHPQ), Las Vegas, NV, October 1996, pp. 348-353. [10] Protective Relays Application Guide. GEC Alsthom Measurements Ltd, Stafford, U.K., 1987. [11] R. C. Dugan, L. A. Ray, D. D. Sabin, G. Baker, C. Gilker, and A. Sundaram, Impact of fast tripping of utility breakers on industrial load interruptions, IEEE Industry Applications Society Annual Meeting, Denver, CO, October 1994, pp. 2326-2333. A revised version of this paper 'appeared as "Fast tripping of utility breakers and industrial load interruptions," in IEEE Industry Applications Magazine, vol. 2, no. 3, May-June 1996, pp. 55-64. 465 466 Bibliography [12] E. W. Gunther and H. Mehta, A survey of distribution system power quality-Preliminary results, IEEE Transactions on Power Delivery, vol. 10, no. 1, January 1995, pp. 322-329. [13] L. Evans, A. Levy, D. Start, B. H. Turner, and M. J. Williams, System utilization consultancy group: Project team sul I-voltage sags, CEGB Draft Interim report, December 1987, not published. [14] H. Seljeseth, A. Pleym, K. Sand, and H. Seljeseth, The Norwegian power quality programme, 3rd Int. Con! on Power Quality: End-use applications and perspectives, October 1994, Amsterdam. KEMA, Arnhem, The Netherlands, 1994. [15] M. H. J. Bollen, T. Tayjasajant, and G. Yalcinkaya, Assessment of the number of voltage sags experienced by a large industrial customer, IEEE Transactions on Industry Applications, vol. 33, no. 6, November 1997, pp. 1465-1471. [16] The Excel file containing these measurements was obtained from a web-site with test data set up by R. L. Morgan for IEEE project group Pl159.2, with the aim of testing methods of sag characterization. http://grouper.ieee.org/groups/1159/2/index.html. [17] M. H. J. Bollen, The influence of motor reacceleration on voltage sags, IEEE Transactions on Industry Applications, vol. 31, no. 4, July 1995, pp. 667-674. [18] G. Yalcinkaya and M. H. J. Bollen, Stochastic assessment of frequency, magnitude and duration of non-rectangular sags in a large industrial distribution system, Power Systems Computation Conference, August 1996, Dresden, Germany, pp. 1028-1034. [19] This figure was obtained from the Power Quality monitoring demonstration at the Electrotek Concepts Website. http://www.electrotek.com. (20] L. E. Conrad and M. H. J. Bollen, Voltage sag coordination for rel