Uploaded by joemarie.valcarcel

Dynatechnik-Model-2

advertisement
ID#
Phase
1 or 3
Amp Load
[A]
Voltage [V]
Set of
Conductors
Cable Size
Conductor
Type
Distance
Unit
Power
Factor
Conduit
Type
R
X
Zeq
[V]
% Drop
Main
1
36
230
1
25
Copper
50
m
0.8
RMC
1.02
0.197
0.934
3.36
1.46%
Branch1
1
5
230
1
3.5
Copper
30
m
0.8
PVC
3.9
0.164
3.218
0.97
0.42%
Branch2
1
7.6
230
1
5.5
Copper
30
m
0.8
PVC
3.9
0.164
3.218
1.47
0.64%
Branch3
1
7.6
230
1
5.5
Copper
30
m
0.8
PVC
3.9
0.164
3.218
1.47
0.64%
Branch4
1
7.6
230
1
5.5
Copper
30
m
0.8
PVC
3.9
0.164
3.218
1.47
0.64%
Branch5
1
6.2
230
1
5.5
Copper
30
m
0.8
PVC
3.9
0.164
3.218
1.2
0.52%
SEAL
RA 9266
SEC 33
PROJECT TITLE:
APPROVED BY:
AS INDICATED
DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS
DULY SIGNED, STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE
ARE THE INTELECTUAL PROPERTY AND DOCUMENTS OF THE ARCHITECT
WHETHER THE OBJECT FOR WHICH THEY ARE MADE IS EXECUTED OR
NOT. IT SHALL BE UNLAWFUL FOR ANY PERSON TO DUPLICATE OR
MAKE COPIES OF SAID DOCUMENTS FOR USE IN THE REPETITION OF
PROPOSED STAFF-HOUSE
RENOVATION
SCALE
LOCATION
E
2 2
AND FOR THE OTHER PROJECTS OR BUILDINGS, WHETHER EXECUTED
PARTLY OR IN WHOLE, WITHOUT THE WRITTEN CONSENT OF ARCHITECT
OR AUTHOR OF THE SAID DOCUMENTS.
LOCATION: SAN ROQUE, BARINAUT, ILIGAN CITY
LOCATION:
MOBILE NO.:
PROJECT N0.
Download