CONTENT 1. Product Introduction ........................................................................................................5 1.1. Introduction RTU ...................................................................................................................... 5 1.2. Features ...................................................................................................................................... 6 2. Technical Specification .....................................................................................................8 2.1. Control General Specification ................................................................................................ 8 2.2. Environment Condition ........................................................................................................... 9 2.3. FRTU TECHNICAL SPECIFICATION ....................................................................................... 10 2.4. Digital Process ........................................................................................................................ 10 2.4.1. Digital Signal Controller (DSCs) ..................................................................................................................... 10 2.4.2. Analog/Digital Conversion ............................................................................................................................... 11 2.4.3. Function .................................................................................................................................................................. 11 2.5. Function Block Diagram ........................................................................................................ 12 2.6. Fault Detect and Sectionalizing Functions ........................................................................ 13 2.7. Power System Measurements .............................................................................................. 15 2.8. System Setting ........................................................................................................................ 16 2.9. Communications ..................................................................................................................... 18 2.10. Event Record ........................................................................................................................ 21 2.10.1. Event Record ......................................................................................................................................................... 21 3. Physical Description....................................................................................................... 23 4. Input/output Connector ............................................................................................... 24 4.1. Modem Power supply Input ................................................................................................ 25 4.2. Current Input ........................................................................................................................... 25 4.3. Voltage Input........................................................................................................................... 25 4.4. Remote Communication Port .............................................................................................. 25 4.5. Digital Input /Output ............................................................................................................ 26 Load Break Switch Control RT-200P 4.6. DOOR Port ............................................................................................................................... 26 4.7. AUX. DI/DO ............................................................................................................................. 26 4.8. Motor Output Port ................................................................................................................. 26 4.9. Power Supply Input (AC Input) ........................................................................................... 26 4.10. Battery Port.......................................................................................................................... 27 4.11. Main Power Switch ............................................................................................................. 27 4.12. ETHERNET Connector ......................................................................................................... 27 5. Operator Control Panel ................................................................................................. 28 5.1. Description............................................................................................................................... 28 5.2. Construction ............................................................................................................................ 32 5.2.1. Operation ............................................................................................................................................................... 32 5.2.2. Menu Control........................................................................................................................................................ 33 5.2.3. Other Control ........................................................................................................................................................ 33 5.2.4. Fault Indication ..................................................................................................................................................... 34 5.2.5. Line Status Indication......................................................................................................................................... 34 5.2.6. SECTION Status .................................................................................................................................................... 35 5.2.7. System Status ........................................................................................................................................................ 35 5.2.8. AC/HANDLE LOCKED/GAS LOW/Battery Status ....................................................................................... 36 5.2.9. CONSOL Port ........................................................................................................................................................ 36 5.3. Operation Manual (LCD instruction) .................................................................................. 37 5.3.1. LCD Screen ............................................................................................................................................................. 37 5.3.2. Control button ...................................................................................................................................................... 37 5.3.3. Menu structure tree............................................................................................................................................ 38 5.4. LCD Menu Use ........................................................................................................................ 39 5.4.1. Initial Screen .......................................................................................................................................................... 39 5.4.2. Main Menu ............................................................................................................................................................ 40 5.4.3. Setting Menu ........................................................................................................................................................ 41 6. Fault Indication ............................................................................................................... 43 6.1. Fault Indication ....................................................................................................................... 43 6.2. Cold load PickUp .................................................................................................................... 47 6.3. Operation of Inrush ............................................................................................................... 47 2 Load Break Switch Control RT-200P 6.4. SEF (Sensitive Earth Fault) Detection ................................................................................. 48 6.5. Role of the Sectionalizer(Auto Sectionalizing) ................................................................. 48 6.6. Phase Loss Detection ............................................................................................................. 50 6.7. Phase Sync. Check .................................................................................................................. 50 6.8. Sectionalizer Inhibit ............................................................................................................... 50 7. Operation Setting ........................................................................................................... 51 7.1. Operation Setting ................................................................................................................... 51 7.1.1. Phase Fault Setting ............................................................................................................................................. 51 7.1.2. Ground Fault Setting .......................................................................................................................................... 53 7.1.3. Inrush Detect Setting ......................................................................................................................................... 55 7.1.4. FI Reset Time Setting ......................................................................................................................................... 57 7.1.5. Line Open Setting ............................................................................................................................................... 57 7.1.6. Sync. Check Setting ............................................................................................................................................ 58 7.1.7. Sectionalize Setting ............................................................................................................................................ 59 7.1.8. SEF Setting ............................................................................................................................................................. 60 7.1.9. Under Frequency Setting.................................................................................................................................. 62 7.1.10. Over Frequency Setting .................................................................................................................................... 63 7.1.11. Under Voltage Setting ....................................................................................................................................... 64 7.1.12. Over Voltage Setting .......................................................................................................................................... 65 7.1.13. Inhibit Setting ....................................................................................................................................................... 66 7.2. System Config Menu ............................................................................................................. 67 7.2.1. Power Config......................................................................................................................................................... 67 7.2.2. I/O Config .............................................................................................................................................................. 69 7.2.3. Other Config ......................................................................................................................................................... 71 7.2.4. Communication Config ..................................................................................................................................... 76 7.2.5. Modem Control Setting .................................................................................................................................... 76 7.2.6. TCP Control............................................................................................................................................................ 77 7.2.7. SNTP Control ........................................................................................................................................................ 78 7.2.8. DNP Parameter Setting ..................................................................................................................................... 80 7.2.9. IEC Parameter Setting ........................................................................................................................................ 83 7.2.10. IEC 101 Parameter Setting ............................................................................................................................... 86 7.2.11. IEC 104 Parameter Setting ............................................................................................................................... 88 7.2.12. Event Clear ............................................................................................................................................................. 90 7.2.13. Time.......................................................................................................................................................................... 90 3 Load Break Switch Control RT-200P 8. Display Menu .................................................................................................................. 92 8.1. Monitoring and Metering ..................................................................................................... 93 8.2. Status view............................................................................................................................... 96 8.3. Counter view ........................................................................................................................... 97 8.4. Alarm View .............................................................................................................................. 98 This menu displays controller Fault detection. ........................................................................... 98 8.5. 9. System Information ............................................................................................................... 99 Event (Event Log) ......................................................................................................... 100 4 Load Break Switch Control RT-200P 1. Product Introduction 1.1. Introduction RTU RT-200P is embedded in Distribution Automation SF6 gas insulated load break switch (Pole mount) control box. It receives measurement information (3 phases current & voltages) and status information from Switch, and meters current and voltage, detects FI, Line cut, Live line/Dead line, Unbalance, Sectionalizer optimized for remote control and automation systems. RT-200P monitors not only electric quality of distribution line but also, provides Section operation in case of fault occurring and minimize its fault area. All events occurring in the distribution line, are saved and provides fault analysis. With using DNP3.0 Protocol, provides monitored status to SCADA for switch operation. Not only DNP3.0 Protocol, other communication protocols can be provided by user’s request. As well as, controlling a switch by receiving Control Signal from SCADA, provides Distribution Automation and minimize a fault area. 5 Load Break Switch Control RT-200P 1.2. Features Magnitude and phase angle of voltages & currents Sequence components of 3-Phase voltages & currents True RMS of voltages & currents Active, reactive and apparent power for each phase and 3-phase Measurements Energy(4-quadrant metering) Displacement Power Factor Frequency Phase difference between source-side and load-side voltage Control Interlocking Protection Status Ground Fault SEF Inrush Detect Sync. Check Sectionalize • Manual LBS Open/Close at local or remote operator Place, Battery Test • • • • • • Gas low Handle lock Operator place Control lock Sync. Fail Live Load Fault Detection (Phase and Earth Fault) SEF(Sensitive Earth Fault) Detection Cold Load protection(Pickup Adjustment) Magnetizing Inrush Restraints Open Line Detection Phase Sync. Fail Detection Switch Open/Closed/Select 6 Load Break Switch Control RT-200P Monitoring Mechanical Locked Gas Pressure Low External AC Power LBS Door Open Battery Low Local/Remote Fault Indication Open Line Detection • Event recording with time stamp F.I Event / I/O Event / System Event / Control Event / Measure Event(Demand Current & Event Record Power, Daily Max Current & Power) • Waveform Recording Storage: 8 Fault Waveforms of 10 cycles. Sampling ratio : 32 Sample/Cycle * 10 Cycles Counter Communication • Restart(Boot Count) • Switch Open Count • All Fault Count • Ch A, Ch B, Ch C, Ch N Fault Port1 : Panel Serial Port (Maintenance Port : Modbus) Port2 : Serial Port (DNP3.0, IEC60870-5-101 Protocol ) Port3 : TCP Port (IEC60870-5-104, DNP/TCP) - 7 RJ-45 2 Port (Option) Load Break Switch Control RT-200P 2. Technical Specification This section details the technical specifications of the Load Break Switch (LBS) and Control System. Provide to detail setting values of timing, current, voltage and other measurement accuracy is given 2.1. Control General Specification Maintenance interval 5 years Auxiliary supply voltage (LV AC mains supply) As Ordered +10 -20% Required auxiliary supply rating 50 VA, 120VA Battery 2 x 12V 12Ah Battery replacement interval 5 years Earthing Modem 10mm earth stud Modem may be fitted by the manufacturer or by the utility, for remote communications. Space, power and data interfaces are provided within the control cubicle. Modem Power Supply Voltage (set by user) 24V DC Modem Power Supply Continuous Current 1.3A Modem Power Supply Max Current Modem Interface Auxiliary Power supply(Internal 3A for 30 sec with 20% duty cycle RS232 Power) Supply from an external AC Source 110V or 240V Battery Charging /Control Power Transformer - Motor Power – 30VAC to 30VDC - Battery Charging/Control Power – 15VAC to 30VAC to 30VDC 15VDC Main Power – 16VAC - Battery Charging Power: 27VDC - Control Power : 24VDC 8 16VAC to 27VDC - SMPS Load Break Switch Control RT-200P 2.2. Environment Condition Environmental condition Altitude < 2,000m Wind Speed 40m/s CT Input, VT Input, Control Power Input, Fiberoptic insulation Input and Relay output Dielectric Strength Impulse Voltage AC 60㎐, 2㎸/1 minute IEEE C62.45 (1992) , 6㎸(1.2×50㎲), 3㎄(8×20㎲) of Relay System for Radio Electromagnetic Interference Transceiver. Protection relay and Relay system protection purpose IEEE C37.90.1 - 1989 IEEE SWC test (3 ㎸ Vibration1 ㎒ to 1.5 ㎒, 5 ㎸ fast saturation 1.2×50 ㎲) Surge Withstand Capability IEEE C37.90.2 - 1987 IEEE Test, Test use standard, relay system for Radio Electromagnetic Interface that comes from Transceiver, 10 V/m(150㎒ and 450㎒, 5 W transmitter 10㎝) IEC 255-21-1-1988 Electric Relay, Part 21: Metering relay and protection device vibration, impact, crash and earthquake test, Section One - Vibration tests Vibration Test (sinusoidal), Class 2 IEC 255-21-1-1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2 Control Operating Operation range : -25℃∼+70℃ (-13℉∼+158℉) Temperature LCD : -20℃∼+70℃(-4℉∼+158℉) Standard 9 Load Break Switch Control RT-200P 2.3. FRTU TECHNICAL SPECIFICATION FRTU Technical Specification Frequency 50 / 60 Hz System Power Input AC Voltage Power : 16Vac/32Vac Power Output Modem : DC 24V Max : 1A Current Transformer Input Current Input IA,IB,IC,IN,ZCT (Max : 13A) (CT: Current rate) Burden : Below than 0.5VA Input Rang : 2~6Vac 4Vrms at rated Phase Voltages Burden : Below than 0.01VA Open/Close Operate Output : 240Vac 16A, 30Vdc 16A Aux DO 1~4 : 250Vac3A, 30Vdc 3A Input 8 channel Dry Contact Input Type Capacitor Voltage Divider Inputs(CVD) Output Contacts Input 2.4. Digital Process 2.4.1. Digital Signal Controller (DSCs) DSP Processor Feature High-Performance 32-Bit CPU • • • TMS320F283X 32-Bit core FPU : 150MHz Six-Channel DMA Controller (for ADC, McBSP, – Up to 2 CAN Modules • • ePWM, XINTF, and SARAM) Harvard Bus Architecture – Up to 9 16-Bit Timers • Fast Interrupt Response and Processing (6 for ePWMs and 3 XINTCTRs) • • • Unified Memory Programming Model DMA 6CH On-Chip Memory : F28335, F28235: – One Inter-Integrated-Circuit (I2C) Bus • • • 256K x 16 Flash, 34K x 16 SARAM Up to 6 Event Capture Inputs Up to 2 Quadrature Encoder Interfaces 10 Load Break Switch Control RT-200P • Serial Port Peripherals : 2 CAN / 3 SCI(UART) / 2 McBSP / 1 SPI / 1 I2C 2.4.2. Analog/Digital Conversion ADC Feature 16 Bit A/D Converter Anti-aliasing analog filter One gain channel for each current input : effective 16 bit resolution measurements 2.4.3. Function Self-Diagnostic Watch dog Timer Control Power System RTC Self Check Logic Memory Check Logic ADC Converter Self Check Logic 11 for current Load Break Switch Control RT-200P 2.5. Function Block Diagram 12 Load Break Switch Control RT-200P 2.6. Fault Detect and Sectionalizing Functions Phase Fault Detection Phase Fault Threshold Current Setting Range 5 to 900 A (Pick up Current) Default : 400A / step : 1A Definite Time for Fault to Persist Setting Range 0.01 to 10.0 sec (Detection Time) Default : 0.02s / step : 0.01s Inrush Restraint Yes/No Default : No 100 ~ 500% Cold Load Pickup Default : 200% / step : 10% 0.1 to 180 sec Cold Load Time Default : 0.2sec / step : 0.1sec Direction Detection Enable No Use/Use Default : No Use 5 ~ 85 % Direction Voltage Pickup Default : 10% / Step : 1 % 0 ~ 359 deg Direction MTA Default : 0 deg / step : 1 deg Ground Fault Detection Earth Fault Threshold Current Setting Range 5 to 900 A (Pick up Current) Default : 60A / step : 1A Definite Time for Fault to Persist Setting Range 0.01 to 10.0 sec (Detection Time) Default : 0.02s / step : 0.01s Yes/No Inrush Restraint Default : No Direction Detection Enable No Use/Use Default : No Use 5 ~ 85 % Direction Voltage Pickup Default : 10% / Step : 1 % 0 ~ 359 deg Direction MTA Default : 0 deg / step : 1 deg Inrush Detection 5 ~ 50 % 2nd Harmonic Setting Range Default : 20 % / step : 1% 0.02 ~ 1 sec Detection Time Default : 0.02 / step : 0.01 sec 0.1~180.0 sec Inrush Time Default : 0.2 s step : 0.1 sec 100 ~ 1000 % Multiple Default : 200% / step : 10% FI Reset Time 13 Load Break Switch Control RT-200P 1~180 s FI Reset Time Default : 20s / step : 1s Line Open Detection Live Line ON Voltage Setting Range 50 ~ 90 % Default : 50% / step : 1% 10 – 75% Line OFF Voltage setting Range Default : 50% / step : 1% 0.01 ~ 30 s Detection Time setting Range Default : 0.4s / step : 0.01s Phase Sync. Check Set 5 ~ 60 deg Phase Difference Setting Range Default : 30deg / step : 1deg 0.1 ~30 s Detection Time Setting Range Default : 0.1s / step : 0.1s Sectionalizer VIT / VT Sectionalizer Mode Select Default : VIT 1 Faults to trip (Fault count) to 3 default : 2 / step : 1 20 ~ 240 s Sequence reset time Default : 30s / step : 1s SEF(Sensitive Earth Fault) Detection Sensitive Earth Fault Threshold Current Setting Range 2 to 20 A (Pick up Current) Default : 5A / step : 1A 10 ~ 80 V Pick up Voltage Setting Range Default : 30V / step : 1V 0 ~ 90 deg Angle Setting Range Default : 90deg / step : 1deg Definite Time for Fault to Persist Setting Range 0.1 to 30.0 sec Default : 0.1s / step : 0.1s Yes/No Inrush Restraint Default : No UFR (Under Frequency Relay) 45.00 to 60.00 Hz Under Frequency Pickup Level Default: 49.80Hz/step : 0.01Hz 50 ~ 85 % Pick up Voltage Setting Range Default : 80% / step : 1% 0.1 ~ 20.0 sec Delay Time Setting Range Default : 1.0s / step : 0.1s OFR (Over Frequency Relay) 14 Load Break Switch Control RT-200P 50.00 to 70.00 Hz Over Frequency Pickup Level Default: 62.20Hz/step : 0.01Hz 50 ~ 85 % Pick up Voltage Setting Range Default : 80% / step : 1% 0.1 ~ 20.0 sec Delay Time Setting Range Default : 1.0s / step : 0.1s UVR (Under Voltage Relay) 50 ~ 90 % Pick up Voltage Setting Range Default : 80% / step : 1% 0.1 ~ 20.0 sec Delay Time Setting Range Default : 1.0s / step : 0.1s OFR (Over Voltage Relay) 110 ~ 150 % Pick up Voltage Setting Range Default : 120% / step : 1% 0.1 ~ 20.0 sec Delay Time Setting Range Default : 1.0s / step : 0.1s Sectionalizer Inhibit Inhibit Yes/No Default : No 2.7. Power System Measurements Current measurement RMS(A) & Phase angle(°) Ia, Ib, Ic, In Sequence Component I1, I2, I0 2 ~ 12,500 A Reading Range ( External CT Ratio 1,000 : 1) Accuracy 2~12,000A: ±1% or ±1A Voltage Measurement Sequence Component Va, Vb, Vc, Vr, Vs, Vt [kV] Voltage Measurement Range (RMS Phase to Earth) V1s, V2s, V0s, V1L, V2L, V0L 0.38 to 26 kV Voltage Measurement Resolution ±%1 or ±0.1kV Phase angle difference(°) ∠Va - ∠Vr Power Measurement Active Power(kW) Pa, Pb, Pc, P3p Reactive Power(kVar) Qa, Qb, Qc, Q3p Apparent Power(kVA) Sa, Sb, Sc, S3p Accuracy ±1% Power Factor Measurement A phase, B Phase, C phase, 3Phase total PFa, PFb, PFc, PF3 Power Measurement Range 0-100% 15 Load Break Switch Control RT-200P Accuracy ±2% Frequency Measurement Reading range 10 ~ 100Hz Accuracy ±0.1Hz Energy measurement Reading range 0 ~ 65565 Accuracy ±2% Average Demand Current and Power Configurable demand interval Ia, Ib, Ic, Pa, Pb, Pc, P3ph, 15minutes Daily max. currents and power are stored 2.8. System Setting Power Config System Frequency 50 ~ 60 Hz / default : 50 Hz System Type 3P4L~3P3L / default : 3P4L Rated Voltage 3800 ~ 26000 V / CT Ratio 100 ~ 2000 A / default : 1000 A NCT Ratio 100 ~ 2000 A / default : 1000 A CT Direction FWD ~ REV / default : FWD Ref Phase A,B,C / default : A Phase Rotation ABC , ACB / default : ABC I/O Config 1200 ~ 5000 ms / Pulse Set (Do Pulse) default : 1200ms(Motor) DI : 1~9999ms /default 20ms DI Debounce Time AC Power : 1~60s / default : 20s Aux. DO Config Options for users User Switch Setting Other Config FI Reset Auto – Manu / default : Manu FI Clear Time 0~600 sec / default : 300sec 1) Live Load(Volt Interlock) Interlock 2_ Sync Fail (Sync Interlock) : Yes – No : Yes – No 3) Open Interlock : Yes – No Battery Test Time 1 ~ 100 h / default : 24h Power Quality Voltage Sag Level Detect Time 10 ~ 99% default 90% / step : 1% 0.5 ~ 10.0 cycle , default : 2.0 cycle / step 0.1 cycle 16 Load Break Switch Control RT-200P Voltage Swell Level Detect Time 101 ~ 150% default 120% / step : 1% 0.5 ~ 10.0 cycle , default : 2.0 cycle / step 0.1 cycle Interruption Level Detect Time 10 ~ 49% default 20% / step : 1% 0.5 ~ 10.0 cycle , default : 2.0 cycle / step 0.1 cycle 17 Load Break Switch Control RT-200P 2.9. Communications RS232C DCD(1), Rx(2), Tx(3), DTR(4), GND(5), DSR(6), 9pin Signals TRS(7), CTS(8), NC(9) Speed(Baud rate) 1200,2400,4800,9600,19200,38400 CTS,DCD signal Timeout Configurable Modem Control RTS off-delay Configurable DNP3.0 / DNP-TCP Support DNP3.0 Subset Level 2 Class of each point is settable Supports multi-frame transmission (multi-frame interval is configurable) Enable/Disable unsolicited message class Non-transmitted events are stored on non-volatile memory during communication fail Supports direct operate or select before operate (SBO) for control output Supports report by exception for analog values Protocol frame monitor was built in FRTU IEC60870-5-101 Address size is configurable. Two time tag formats are selectable. :24-bit or 56-bit Single character for NACK is supported. Cyclic update of measurements data. Class assignable for each object type. ( single point, double points, measured point, Set Points Command) Supports report by exception for updating analog values IEC60870-5-104 IEC 60870-5-104 (also known as IEC 870-5-104) is an international standard, released in 2000 by the IEC (International Electro technical Commission). As can be seen from the standard's full designation 'Network access for IEC 60870-5-101 using standard transport profiles', its application layer is based on IEC 60870-5101. IEC 60870-5-104 enables communication between control station and substation via a standard TCP/IP network. The TCP protocol is used for connection-oriented secure data transmission. 18 Load Break Switch Control RT-200P Communication DNP, IEC60870-5-101, IEC60870-5Protocol Setting Protocol Select 104, DNP/TCP Default : DNP Comm. Speed Modem Control TCP Control SNTP IEC Parameter Default : 9600pbs Comm Line 2Wire/4Wire / Default : 2Wire RTS Off Delay 10 ~ 500ms / Default : 10 ms CTS Time Out 1 ~ 255sec / default : 1 sec DCD Time Out 100 ~ 30,000ms / Default : 100 ms IP Setting Default : 192.168.010.009 Subnet Mask Default : 255.255.255.0 Gate Way Default : 192.168.10.1 LAN Port Set 1-65534 / Default : 2404 LAN Card Select 1 ~ 2 Port / Default : 1 Port SNTP Use No Use / Use / Default : Use SNTP IP Default : 192.168.010.010 UDP Port 1-65534 / Default : 123 UTC Mode UTC / Local / Default : UTC UTC Hour -12 ~ 13h / Default : 0h UTC Min 0 ~ 59 min / Default : 0min Cyclic Time 1 ~ 24 h / Default : 24h D/L Retry 0~2 / default : 0 D/L Time Out 0 ~ 255 / default : 10s Yes-No-Sometime / D/L Confirm DNP Parameter 1200/2400/4800/9600/19200 default : Sometime A/L retry 0 ~ 2 / default : 0 A/L Time Out 0 ~ 255 sec / default : 15 sec InitUnsol Yes – No / default : No Unsol Class1 Enable/Disable / default : Disable Unsol Class2 Enable/Disable / default : Disable Unsol Class3 Enable/Disable / default : Disable Unsol Delay 0 ~ 60 sec / default : 5 sec SBO Time Out 1 ~ 255 sec / default: 15 sec Master Address 0 ~ 65534 / default : 3 Slave Address 0 ~ 65534 / Default : 4 Frame Interval 100 ~ 5,000 ms / default : 100 ms A/L Cycle PRD 0 ~ 60 / default : 1 sec SBO TimeOut 1 ~ 255 / default : 15 sec M_SP Cyclic Enable/Disable / Default : Enable 19 Load Break Switch Control RT-200P IEC101 M_DP Cyclic Enable/Disable / Default : Enable M_ME Cyclic Enable/Disable / Default : Enable M_SP Address 1-10000 / default : 100 C_SC Address 1-10000 / default : 200 M_DP Address 1-10000 / default : 300 C_CD Address 1-10000 / default : 400 M_ME Address 1-10000 / default : 1000 C_SE Address 1-10000 / default : 2000 M_IT Address 1-10000 / default : 4000 LINK Address 1-254 / Default : 1 ASDU Address 1-254 / Default : 1 Originator 0-255 / Default : 1 LINK Address Size 1-2 / Default : 1 ASDU Address Size 1-2 / Default : 1 IOA Address Size 1-3 / Default : 1 COTA Address Size 0-2 / Default : 2 Unbalance/Balance Link Mode / Default: Unbalance None/cp24/cp56 Time Marker / Default : None T0 Off PRD 1 ~ 255 / default : 30 sec T1 Ack PRD 1 ~ 255 / default : 15 sec T2 S frame PRD 1 ~ 255 / default : 10 sec T3 Test PRD 1 ~ 255 / default : 20 sec Set S/W Counter S/W Count 0 ~ 65535 / default : 0 Clear Events All Events are cleared Yes / No Clear Fault All Faults are cleared Yes / No Setting Time yy-mm-dd-hh-mm-ss Setting Pass Word **** In Voltage 3,800-30,000V IEC104 Event Time Time Set Pass Word Pass Word Se Volt Calib Volt. Adjust 20 Load Break Switch Control RT-200P 2.10. Event Record 2.10.1. Event Record The event recorder feature allows the time tagging of any change of state (Event) in the relay. As an event occurs, the actual event condition is logged as a record along with a time and date stamp to a resolution of 1 millisecond. There is capacity for a maximum of 1500 event records that can be stored in the relay and when the event buffer is full any new record will over-write the oldest. All events can be uploaded over the data communications channel(s) and can be displayed in the ‘RManager’ SW package in chronological order, allowing the sequence of events to be viewed. Events are also made available spontaneously to an Modbus RTU or DPN 3.0 compliant control system. Event List I/O Event Description Max Status Change of binary Input / Output ➔ SW State ➔ Main Lock 125 ➔ GAS Low ➔ Door State F/I Event Operated status of Fault Indication ➔ Fault count : a, b ,c, n, all 250 ➔ Latest fault current, phase and time System Event Status Change of System ➔ System Reset ➔ Set Change 125 ➔ Communication Error ➔ AC Loss Control Event Controlled status of RT-200P ➔ SW Control ➔ Control 125 ➔ Locked ➔ FI Reset ➔ Battery test PQ Event Power Quality ➔ Sag 125 ➔ Swell ➔ Interruption Measure Event Measure status of RT 200P 125 * 6 1) Average 15 Total : 750 2) Day Max 21 Load Break Switch Control RT-200P Waveform Event Record Event List Waveform Description • Waveform Recording Storage: 8 Fault Waveforms of 10 cycles. Sampling ratio : 32 Sample/Cycle * 10 Cycles Max 8 fault waveforms can be captured on non-volatile memory 22 Load Break Switch Control RT-200P 3. Physical Description The RT-200P includes the following major components: ⚫ Inclusion with a local communication port and LCD display/keypad. ⚫ CPU/System Controller Board ⚫ Process I/O board ⚫ Internal mounting brackets and battery ⚫ modem options Figure 3-1. Dimension and Structure 23 Load Break Switch Control RT-200P 4. Input/output Connector RT-200P provides terminals (connector) to connect control and modem. The terminal arrangement is as Bellows. Figure 4.1 Connectors on the Side of RT-200P 24 Load Break Switch Control RT-200P The Load Break Switch is connected to the controller by the control cable. The cable plugs into compatible ports at both the controller and underside of the switch. 4.1. Modem Power supply Input - Power supply connecter has RT-200P external modem power supply terminal. - Modem power Fuse socket - DC 12V (Options) 4.2. Current Input - Current connecters with phase A and follows by B, C, N. Aux1, Aux2 is spare Aux Port and not assign. 1 2 3 4 ZCT2 ZCT1 SPARE SEF 5 6 7 8 IN IC IB IA 4.3. Voltage Input - Voltage connector has source side 3 phases(A,B,C) and load side 3 phases(R,S,T) as bellows; 1 2 3 4 5 VT VS VR VC VB 6 7 8 9 10 VA V_COM GND 24Vdc 4.4. Remote Communication Port - Modem communication port is D-SUB 9 pin male type 25 Load Break Switch Control RT-200P 4.5. Digital Input /Output • Digital Input receives 2 status signals through insulated electric contacts. • Digital Output has 2 output relays. 10 9 8 7 6 M. Lock GAS LOW 52B 52A DI_COM 5 4 3 2 1 M. Lock GAS LOW 52B 52A DI_COM 4.6. DOOR Port - DOOR OPEN SENSING PORT 4.7. AUX. DI/DO - Aux DI DO 14 13 12 11 10 9 8 DO4_2 DO3_2 DO2_2 DO1_2 DI_COM DI3 DI4 7 6 5 4 3 2 1 DO4_1 DO3_1 DO2_1 DO1_1 DI_COM DI1 DI2 4.8. Motor Output Port - MO+ / MO- : Motor connect -> Motor operating Signals. - Fuse : 15A 12 11 10 9 MO+ MO+ MO- MO- 6 5 4 3 MO+ MO+ MO- MO- 4.9. Power Supply 8 7 2 1 Input (AC Input) - Power supply connecter has RT-200P operation power supply terminal. 26 Load Break Switch Control RT-200P 4.10. Battery Port - Battery charging output port. - DC 27V +/- terminal - Fuse socket 4.11. - Main Power Switch Main Power Switch connection terminal 4.12. - ( Fuse 15A) ETHERNET Connector 10 / 100 Base-T 27 Load Break Switch Control RT-200P 5. Operator Control Panel 5.1. Description The Operator Control Panel is mounted inside the control Box on the equipment panel. The Control Panel consists of a four-line Liquid Crystal Display (LCD) and keypad with switches and Light Emitting Diodes (LEDs) which are used to select and monitor the functionality of the LBS. On the front panel, there are LED’s indicating LBS’s status, function buttons and LED’s, control buttons and LED’s, LCD buttons, and a RS232 port for maintenance. Figure 5-1: Operator Control Panel 28 Load Break Switch Control RT-200P Number Item Description (1) RUN: It indicates the operation status. In normal operation, it flicker periodically. In system problem 1 case, it is lighting or turned off. (2) ERROR: Turn on with Self-diagnosis Error & Communication Trouble. 2 DISPLAY Back-light LCD, 4 line with 40 characters per line. (1) MENU: Selects the MENU required. (2) UP: It is used to move the menu within a 3 group or to increase the setting point. (3) DOWN: It is used to move the menu or to decrease the changed value. (4) ENTER: It is used to confirm selection function, and restores original display. (1) Fault A, B, C, N PHASE, SEF (2) SYNC. FAILED 4 (3) REVERSE POWER Indicates all the Fault detection settings currently in use e.g. Fault Settings and Sectionalizing. (1) AC POWER: Indicates the external AC power supply status. (2) HANDLE LOCKED: Turn on, when the HANDLE is 5 locked. (3) GAS LOW : Turn on, when the GAS status is GAS low (4) BATTERY LOW: Turn on, when the battery status is low. (Discharged.) Indicates the external Input status and check monitor. Source side and load side live line status are indicated. More than one phase voltage is higher than an Off Level 6 of Disconnect line/Open phase, it is Live line. And all 3 phases are less than that, it is Dead line. Operator shall decide an operation. (1) ENABLE: 7 (2) TRIP: Indicates Section operation status. Indicates Sectionalizing TRIP sequence operation status. The LED is lit When the LBS is open. 29 Load Break Switch Control RT-200P 8 RX/TX/RTS LED (Red) indicates the communication state of RT-200P. This button is used for INDICATOR LED Reset (LED Off). 9 INDICATOR LED represents all the LED’s related to Protection, Reclosing, and Self-diagnosis Error It takes keying to check battery and charging circuit. 10 When pressing the button and if AC power supply is provided, charging circuit is disconnected and connects a load resister to battery and check the charging circuit. These buttons are used to locally control (Open / Close) the LBS. Before local control command, check first if the control position is Local. CONTROL SELECT button is a two-phase safety & confirmation check mechanism. To 11 manually and locally control the LBS, CONTROL SELECT button should be pushed down to make the corresponding LED on, and this CONTROL SELECT function can be expanded to the scheme of Multiple LBS Control in the future. Control Lock Button Enables or disables the LBS 12 operation. If Control Lock LED is on, LBS operation and Sectionalizing will be prohibited. To decide the control position to Remote, push this button and make the LED on. This button and LED are also 13 toggled between Remote and Local. But, the manipulation of this button is possible only in the local for operator’s safety. 14 Check first if the control position is CONTROL SELECT button/LED ON Manual open control opens the LBS and makes the Switch locked out to open. Check first if the control position is SELECT button/LED ON 15 Push CLOSE button to control the LBS manually to be closed. 16 User mapping for using group setting with user setting key 30 Load Break Switch Control RT-200P RS-232C PORT 17 RT-200 is an advanced personal computer based software package to allow off-line and on-line monitoring and control of a LBS via RS232 port. 31 Load Break Switch Control RT-200P 5.2. Construction The Operator Control Panel consists of following parts: ⚫ Operation ⚫ Menu Control ⚫ Other Control ⚫ Fault Indication ⚫ Line Status Indication ⚫ SECTION Status ⚫ System Status ⚫ AC/HANDLE LOCKED/GAS LOW/Battery Status ⚫ CONSOL Port 5.2.1. Operation Figure: Operation selection These buttons are used to locally control (Open / Close) the LBS. Before local control command, check first if the control position is Local(LED ON). CONTROL SELECT button is a two-phase safety & CONTROL SELECT confirmation check mechanism. To manually and locally control the LBS, CONTROL SELECT button should be pushed down to make the corresponding LED on, and this CONTROL SELECT function can be expanded to the scheme of Multiple LBS Control in the future. Check first if the control position is CONTROL SELECT button/LED ON OPEN Manual open control opens the LBS and makes the Switch locked out to open. INDICATION LED Switch status is indicated. Position LED is operated based on 52a contact. 32 Load Break Switch Control RT-200P 5.2.2. Menu Control 20 × 4 character LCD which has back-light support, is used for a user to operate conveniently and to check operation status clearly. Control button LCD Control button is composed of four basic keys (MENU, UP, DOWN, ENT). Following table is explanation of the keys. 5.2.3. Other Control RESET Button Normal: Press the button to check all Lamps. FI occurred: It resets FI Target by pressing the button. To test the battery and charging circuit. When pressing the button Battery TEST Button and if AC power supply is provided, charging circuit is disconnected and connects a load resister to battery and check the charging circuit. When LED is ON, Remote and Local operation are all available. When LED is OFF, only Local operation is available. Local Mode : In this mode only a local user can manually close the LBS from the controller panel. This means a user can go to the Remote CONTROL control cubicle, set local control mode and know that remote Button (Local/Remote) closing is disabled. Only a local operator can operation when the controller is in Local Mode. Remote Mode : In this mode only a remote user can manually close the LBS. Only a remote operator can operations when the controller is in Remote Mode. If the local operator is denied a close operation or a setting due to being in Remote Mode Control Lock Control Lock Select Control Lock Status : LED ON 33 Load Break Switch Control RT-200P 5.2.4. Fault Indication In case of Permanent or Instantaneous fault, corresponding LED is ON. LED lamp can be off by manually from local by pressing FI Reset button or from remote by sending a signal. Otherwise, LED lamp will be on although H.V. line becomes normal. 5.2.5. Line Status Indication Phase A,B,C Unbalance are indicated. Under condition that source side and load side are all live line and Phase Fault Indicator switch is open status, check angles, if it meets then, it is OK, LED otherwise, it is unbalanced. Although it is unbalanced, control is still available. Operator shall decide an operation. Source side and load side live line status are indicated. More than one phase voltage is higher than an Off Level of Phase Voltage Indicator Disconnect line/Open phase, it is Live line. And all 3 phases are (Live Line LED) less than that, it is Dead line. Operator shall decide an operation. When LED is ON, SEF is enabled. When LED is OFF, SEF is disabled. SEF(Enable/Disable) Although SEF is enabled, Protection is not enabled, SEF is not activated. When LED is on, T he phase angle difference between Source- SYNC. FAILED LED side voltage (Va) and Load-side voltage (Vr) is over the set value. In this case, Close control command should be inhibited. REVER POWER LED In reverse current case, the REVER POWER lamp becomes On. 34 Load Break Switch Control RT-200P 5.2.6. SECTION Status Indicates present status of set section function process. ENABLED Indicates Section operation status. Sectionalizer Indicates TRIP status. TRIP The LED is lit when the LBS is open. 5.2.7. System Status RT-200P Diagnostic is displayed. RUN LED(Green) indicates that RT-200P has passed the internal diagnostic test and does not have any problem. RX/TX/RTS LED(Red) indicates the communication state of RT-200P It indicates the control electronics normally operation status. In RUN normal operation, In system problem case, it is lighting or turned off. ERROR It indicates a fault condition. RX : Turn on when transmit data COMMUNICATION TX : Turn on when transmit data RTS : Turn on when RTS data 35 Load Break Switch Control RT-200P 5.2.8. AC/HANDLE LOCKED/GAS LOW/Battery Status The system power status of RT-200P is displayed. When RT-200P is supplying external power, AC SUPPLY LED is on. HANDLE LOCKED LED shows the HANDLE LOECKED status of RT-200P and the GAS LOW LED shows the GAS LOW status of RT-200p, the BATTERY lamp shows the battery status of RT-200P. AC POWER Indicates the external AC power supply status. Indicates the external HANDLE LOCKED status. Mechanical locking of the LBS mechanism is provided by pulling HANDLE LOCKED downwards on the Manual Lock handle with a hook stick. When locked, the mechanism cannot be tripped or closed either mechanically or electrically. GAS LOW BATTERY LOW Check that the gas low alarm is showing on the operator control panel. Turn on, when the battery status is Low. 5.2.9. CONSOL Port This connection port is for the communication with administration program. It obtains setting change, control and others events. Engineering tool RS-232 PORT to this port on for Notebook computer is connected maintenance. RS232C port for maintenance is DB9 female-type connector. Use the “null modem” cable for full-duplex (Modbus protocol) communications when connecting a RT-200P to a PC. PIN RS-232 Signal 5 GND Power GND 2 RXD Receive data input 3 TXD Transmit data output 36 Description Load Break Switch Control RT-200P 5.3. Operation Manual (LCD instruction) 5.3.1. LCD Screen 20 × 4 character LCD which has back-light support, is used for a user to operate conveniently and to check operation status clearly. 5.3.2. Control button LCD Control button is composed of four basic keys (MENU, UP, DOWN, ENT). Following table is explanation of the keys. Button Description Move to menu selection mode from display mode and move to prior menu from sub-menu. When press the button in Main Menu it is changed into display mode. When this key is operated after changed the value, all changed value are reverted to original setting value. It is used for menu selection or setting change. In menu selection screen this button is used for menu selection function. In setting change status moves to menu mode by pressing this button It is used to move the menu into above side or to increase the setting point. As all menu has circulated function, from the top menu moves into the lowest menu. In setting change case, after highest setting value comes the lowest setting value. A level is increased by pressing the button and it is increased quickly by pressing the button over 2 seconds. It is used to move the menu or to decrease the changed value. This button has circulated function for menu change/setting change as [increase] button. A level is decreased by pressing the button and it is decreased quickly by pressing the button over 2 seconds. 37 Load Break Switch Control RT-200P 5.3.3. Menu structure tree Figure. Menu Tree Structure 38 Load Break Switch Control RT-200P 5.4. LCD Menu Use 5.4.1. Initial Screen The main information of RT-200P is displayed in the initial screen, for the easy access and understanding of the user. To move to other initial screen, press [UP] [DOWN] button. Press [MENU] button in initial screen to move to Main menu. Initial Screen 1) Startup Screen Indicate the Model/version status 2) Push the UP/DOWN button and display Time status 3) Next UP/Down or Enter button to push, Indicate the Current/Voltage of each phase 4) Push the MENU button to indicate the MENU Function 39 Load Break Switch Control RT-200P 5.4.2. Main Menu In the initial menu, press [MENU] button, it is moved into Main menu. If press [MENU] button in main menu, it is moved to the initial menu. Main menu has sub-menu as below. Main Menu Screen Main menu is composed of 4 submenus. Push the submenu by using [UP][DOUN] button. Move to the submenu by pressing [ENTER] button. 40 Load Break Switch Control RT-200P 5.4.3. Setting Menu Change of Phase Pickup Current of line operating element of Primary setting. Setting Screen 1) Move to “MAIN MENU/ Function Setting/ Operate Set/ Phase Fault Set”. 2) Locate the cursor on Phase by using choose [UP] [DOWN] key and then press the [ENTER] button to change the set point. 3) Change in new setting point by using [UP] [DOWN] button. By pressing [ENTER] button, you can see the changed phase setting point. 4) To save the changed “New Set”, selected YES/NO by using [UP][DOWN] and by pressing [ENTER] button, you can changed new setting value. 41 Load Break Switch Control RT-200P 42 Load Break Switch Control RT-200P 6. Fault Indication The controller has many different detection features, described in this section. In summary it operates as follows: ⚫ The fault Detection Elements are Phase, Earth, and Sensitive Earth Fault (SEF). Each individual element can be programmed to log a fault detection depending on the relevant setting. ⚫ In addition to the Detection Settings there are Operator Settings. This group of settings is Independent of the Detection Settings and it changes the main functionality of the Load Break Switch. The phase, earth and SEF fault detection elements are monitored with independent definite time and fault current settings. A pickup event is generated for each element if the current exceeds the fault current setting for that element. A pickup normally initiates a timer which runs for the definite time setting for that element. When this timer expires a fault is said to have occurred and is reported in the Event Log. The current level at which the definite time timer starts can be modified by a multiplier in the case of Cold Load Pickup Condition and definite time timer start is restrained in the case of Inrush Condition. When all pickups have reset, a peak current event is generated for each element that have picked up. A peak current event is a record of the maximum current measured between fault pickup and fault reset. 6.1. Fault Indication Distribution power system is usually Radial Network. Recloser controller or protection relay will detect the failure of the line, and trip the circuit breaker or Recloser in a main point of power system. The installation location of the LBS located between the protections switches. LBS is resolved, the fault section and isolation from the fault section and the remaining sections of the power system can be restored. Negative Phase Sequence detection is an additional over current element and allows more reliable detection of certain types of faults. RT-200P(FRTU) is the LBS controller, and rapid section isolation of fault line and restoration of normal line by distribution automation system(DAS) which has the function of fault detection and remote communication. The following figure shows the fault detection and restoration of sequence. RT-200P(FRTU) is detected the “failure” when the line voltage is dropped below the voltage Off-Level that the measured the phase current, N-phase current over than the pickup set and maintains longer than 43 Load Break Switch Control RT-200P the corresponding detection time. Distribution automation system (DAS) may get the fault indication from the LBS controller L1 ~ L5 and Recloser R failure be detected to know through communication. Recloser lockout after a fault section, DAS indicates the fault section and isolates it by sending Open command to the controllers of LBS L3, L4. Wherein L5 is to supply power from the back of a loop Tie breaker. i) A fault detected between L3 and L4 ii) Tripped Recloser(R1) in the line and L2,L3 indicate fault at the time iii) DAS decided the fault section and opened L3,L4, then closed R1, L5 L5 may be energized from the loop tie switch backward [Fig. 6-1 ] Fault detection &restoration sequence At the temporary fault, distribution lines are restored automatically by a reclosing. The fault indication of RT-200P(FRTU) can be reset by push button on the front panel or by remote reset command. Also, it can be reset automatically when the line is energized. 44 Load Break Switch Control RT-200P [Fig. 6-2 ] Fault Indication FI PickUp OR PickUp Level Setting - IA + - IB + - IC + [Fig. 6-3] FI Pickup Scheme Fault detection of the state change is saved in the event buffer. And fault current is also attached to the each time tag is saved in the buffer. Fault waveforms data can be stored up to eight and per phase current, voltage samples which stored 10 cycles, 32 samples/cycle. FI PickUp FI Fault V + - V Low Level [Fig. 6-4] FI Fault Scheme Direction Detection Direction detection is to restrict fault indication only on faults to a designated side of the LBS. By using this function, the fault indication can respond only to fault currents from main source, not from dispersed sources in consumer area of the distribution line. As a result, the faulted section in 45 Load Break Switch Control RT-200P the line can be discriminated precisely. [Fig. 6-5] Angular relationship between sequence voltage and current 46 Load Break Switch Control RT-200P 6.2. Cold load PickUp Cold load pickup is the phenomenon that takes place when a distribution circuit is reenergized following an extended outage of that circuit. This is called Cold Load and Cold Load Pickup function is to prevent and distinguish Cold Load from the real fault current. Cold load mode, the fault detection, pickup level is changed by the times of Cold load Multiplier (1~10) and this is in the instantaneous element. . If the transient current goes down and retains below the pickup level within Cold Load Duration, then the normal sequence mode is restored. This setting phase fault and earth fault detection function is applied to. Cold Load Multiplier set to ‘0’, the function is disable to the Cold Load Pickup. I + Time - CPLD Setting PickUp Level FI Fault CLP (Cold Load PickUp) [Fig. 6-6] Cold Load Pickup Scheme [Fig. 6-7] FI Pickup Scheme 6.3. Operation of Inrush When closing onto a typical load there is always a short lived inrush current caused by, for example, transformer magnetization currents, low resistance lamp filaments and motors starting. Inrush Restraint inhibits fault detection when inrush current occurs. Inrush restraint works by raising the phase and earth Threshold Currents for a short period of time to allow the inrush to flow. The inrush time and multiplier settings are specified on: 47 Load Break Switch Control RT-200P 2nd Filter Fundamental Filter divide Level Set + - I + Run FI Inrush - FI Pickup set OCR Inst. [Fig. 6-8] Inrush Restraint Scheme 6.4. SEF (Sensitive Earth Fault) Detection On the non-grounded network, it is hard to detect fault current because ground current of nongrounded network is so small. Therefore, FTU-P200 is designed to measure zero-sequence values from either external core Balanced Current Transformer (or ZCT) or Residual Connection of 3 Phase Current Transformers to detect earth fault in the non-grounded network. This function is generally called SEF detection. In case of earth fault in the non-grounded network, since very small fault current due to line capacitance component flows into the fault point from both sides, SEF detection also considers the fault direction even in the radial network. Maximum Torque Angle is for setting the phase difference between zero-sequence voltage and zero-sequence current, and the protection zone is between 90° and +90° on the basis of Maximum Torque Angle. And it can be used for alarm. [Fig. 6-9] Phase diagram of SEF 6.5. Role of the Sectionalizer(Auto Sectionalizing) The Load Break Switch (LBS) is equipped with automatic sectionalizing logic. The sectionalizing logic opens the LBS during the dead time of an upstream Recloser after it has tripped and closed a number of times as configured by the user. It’s the function to open LBS and disconnect the faulty section from the distribution Feeder automatically before the Recloser or reclosing relay of CB lockouts. The condition to open 48 Load Break Switch Control RT-200P automatically is the fault count. FTU detects and counts the fault and opens LBS if the count reaches the setting value. The default count setting is two. It means that FTU allows the 1st reclosing success of the upstream Recloser or reclosing relay of CB without sectionalizing in case of temporary fault. [Fig. 6-10] Typical time sequence of sectionalizing Caution: Pay attention to the sectionalizer setting according to the Operation Open Time and Recloser setting of Mechanism. Sectionalizer works normally during Recloser Reclosing time Incorrect example: Recloser Reclosing Time shorter than LBS operation time. In this case, the LBS cuts off the fault current, which can cause a serious problem. Note) After Sectionalizer Trip operation, FI Reset must be done for "close" operation. 49 Load Break Switch Control RT-200P 6.6. Phase Loss Detection It’s the definite time under-voltage function only when at least one phase has normal voltage. It has hysteresis characteristics. Voltage On level, Off level, and Delay time settings are needed for this function. 6.7. Phase Sync. Check RT-200P monitors the phase angle difference between source and load side voltages of LBS. If the angle difference is larger than the setting and maintains longer than the set time, an alarm is generated. The alarm is useful to close LBS which is installed at the tie point of two feeders from the separated substation. FTU doesn’t include the result of sync. Check in the close interlock conditions. Be cautious of closing tie switch. 6.8. Sectionalizer Inhibit In the basic FI operation, when no voltage is detected by the Recloser operation of the previous stage in the current state above the pickup current, a fault indicator occurs. When Inhibit is activated, the no-voltage condition is excluded and when the current exceeds the pickup, the fault indicator is activated. At this time, the Fault Indicator condition turns off the indicator after Auto FI Reset Time. 50 Load Break Switch Control RT-200P 7. Operation Setting 7.1. Operation Setting Select “Function Setting” in the main menu, and move to this menu by pressing ENTER. “Operation Setting” menu has the following submenu. 7.1.1. Phase Fault Setting Range Step Def. Unit Min Max No Yes Pick Up Current 5 900 1 400 A Detection Time 0.01 10.00 0.01 0.02 Sec Inrush Restraint No Yes Cold Load Pick Up 100 500 10 200 % Cold Load Time 0.1 180.0 0.1 0.2 sec Direction Detection Off On On Direction Voltage Pickup 5 85 10 1 % Direction MTA 0 359 0 1 deg Function Use 51 No No Load Break Switch Control RT-200P Phase Fault / Function use Range No Use / Use Default Use Step 1) Set [Use/No Use] of direction Detection, when occurs Phase fault. 2) Display the “New Set” 3) To save the changed “New Set”, selected YES/NO by using [UP] [DOWN] and by pressing [ENTER] button, you can changed new setting value. Phase Fault / Pick Up Current Range 5 ~ 900 Default 400A Step 1A Set Pick Up Current Setting. # Fault current detection assurance range is 50A ~ 13000A. Phase Fault / Time Range 0.01 ~ 10.00 sec Default 0.02 Step 0.01 Set Detection time of Phase Fault element. Phase Fault / Cold Load Pick UP Range 100 ~ 500 % Default 200 % Step 10 % Set Cold Load Pickup Multiplier. Phase Fault / Cold Load Time Range 0.1 ~ 180.0 sec Default 0.2 52 Step 0.1 sec Load Break Switch Control RT-200P Set Cold load Time Phase Fault / Inrush Restraint Range Yes / No Default No Step Set [YES / No] of direction Detection, when occurs Inrush Restraint. Phase Fault / Direction Function use Range Yes / No Default No Step Set [YES / No] of direction Detection, when occurs Inrush Restraint. Phase Fault / Direction Reference Voltage Range 5% ~ 85% Default 10% Range 0 ~ 359 deg Default 0 Step 1% Step 1 deg Phase Fault / Direction MTA 7.1.2. Ground Fault Setting Range 53 Step Def. Unit Load Break Switch Control RT-200P Min Max Function Use No Yes Pick Up Current 5 900 1 200 A Detection Time 0.01 10.00 0.01 0.02 sec Inrush Restraint No Yes Off On On Direction Voltage Pickup 5 85 10 1 % Direction MTA 0 359 0 1 deg Direction Detection No No Ground Fault / Function use Range No Use / Use Default Use Step Set [Use / No Use] of direction Detection, when occurs Ground fault. Ground Fault / Pick-up Current Range 2 ~ 900 A Default 200 A Step 200 A Set the Ground pickup Current. # Fault current detection assurance range is 50A ~ 13000A. Ground Fault / Detection Time Range Default 0.01 ~ 10.00 sec 0.02 Step 0.01 Set Detection time of Ground Fault element. Ground Fault / Inrush Restraint Range Yes/No Default No Step Set [YES /No] of direction Detection, when occurs Inrush Restraint. 54 Load Break Switch Control RT-200P Ground Fault / Direction Function use Range Yes / No Default No Step Set [YES / No] of direction Detection, when occurs Inrush Restraint. Ground Fault / Direction Reference Voltage Range Yes / No Default No Range 0 ~ 359 deg Default 0 Step Ground Fault / Direction MTA Step 1 deg 7.1.3. Inrush Detect Setting 2nd Harmonic Setting Range Step Def. Unit Min Max Function Use No Yes 2nd Harmonic 5 50 1 20 % Detection Time 0.02 10.00 0.01 0.02 sec No 2nd Harmonic Set Range 5 ~ 50 % Default 20 % Set 2nd harmonic. 55 Step 1% Load Break Switch Control RT-200P Detection Time Set Range 0.02 ~ 1.00 sec Default 0.02 Step 0.02 Set Detection time of Inrush detect element. Function use Range Default Step Set [Use / No Use] of direction Detection, when occurs Inrush detect. Inrush Time Setting Range Step Def. Unit Min Max Inrush Time 0.1 180.0 0.1 0.2 sec Multiple 100 1000 10 500 % Function Use No Yes No Inrush Detect Set Range 0.1 ~ 180.0 sec Default 0.2 Step 0.1 sec Step 10% Inrush Detect Inrush Multiply Set Range 100 ~ 1000 % Default 500% Function use 56 Range No Use / Use Default No Use Step Load Break Switch Control RT-200P Set [Use / No Use] of direction Detection, when occurs Inrush detect. 7.1.4. FI Reset Time Setting Range FI Reset Time Min Max 1 180 Step Def. Unit 1 20 S Function use Range Default 1 ~ 180 s 20 s Step 1s The failure type is judged according to the voltage state after the FI Reset time has elapsed. 7.1.5. Line Open Setting Open Line is detected by Under Voltage characteristics at unbalanced condition. When the voltage on one or two phases drops below the ‘Volt OFF Level’ setting, the ‘Delay Time’ starts running. If the voltage on those phases stays below ‘Volt OFF Level’ setting until the ‘Delay Time’ timer expires, the Loss of Phase will be detected. If the voltage on detected phase rises to the ‘Volt ON Level’ setting, the Loss of Phase is released immediately. Range Step Def. Unit Min Max Function Use No Yes On Voltage 50 90 1 80 % Off Voltage 10 86 1 50 % Detection Time 0.1 300. 0.1 0.4 sec No Line Open / Function use Range 57 No Use / Use Load Break Switch Control RT-200P Default Use Step Set [Use / No Use] of direction Detection, when occurs Line Open detect. Line Open / Line on Voltage Set Range 50 ~ 90 % Default 50 % Step 1% Set the live Line On Voltage level. Line Open / Line off Voltage Set Range 10 ~ 75 % Default 50 % Step 1% Set line Off Voltage level. ! Setting the Off level below 35% is not recommended. Line Open / Delay Time Set Range 0.1 Default 0.4 ~ 300.0 sec Step 0.1 sec Set Delay time of Line Open detect element. 7.1.6. Sync. Check Setting Range Step Def. Unit Min Max Phase difference 5 60 1 30 Dug Detection Time 0.1 300.0 0.1 0.4 sec Function Use No Yes No Sync. Check / Function use Range 58 5 ~ 60 Deg Load Break Switch Control RT-200P Default 30 Deg Step 1 Deg Set an alarm on the source side and load-side voltage phase Sync. Check / Function use Range 0.1 ~ 300.0 sec Default 0.4 Step 0.1 sec Set Delay time of Line Sync. detect element Sync. Check / Function use Range No Use / Use Default Use Step Set [Use / No Use] of direction Detection, when occurs Sync. Check. 7.1.7. Sectionalize Setting The LBS can be configured as a sectionalizer that trips during the dead time of an upstream Reclosed after a configurable number of supply interrupts. Range Step Min Max Mode VIT VT Fault Count 1 3 1 Reset Time 20 240 1 Function Use No Yes Def. Unit VIT 2 Sec No Sectionalize / Mode Select 59 Range VIT ~ VT Default VIT Step Load Break Switch Control RT-200P Select mode to detect operation as voltage or current or voltage only Sectionalize / Fault count Set Range 1~3 Default 2 Step 1 The number of supply interrupts counted exceeds the trip after setting at counter Caution: Pay attention to the sectionbalizer setting according to the Operation Open Time and Recloser setting of Mechanism Sectionalize / Reset Time Set Range 20 ~ 240 sec Default 30 sec When sectionalizing Step is enabled, 1 sec the upstream Recloser reclose time must exceed 20 ~ 240 seconds to allow for the opening time of the LBS. Sectionalize / Fault count Set Range No Use / Use Default No Use Step Set [Use / No Use] of direction Detection, when occurs Sectionalizer. 7.1.8. SEF Setting Range Step Def. Unit Min Max I-Pick Up 2 20 1 5 A V-Pick Up 10 80 1 30 V Angle 0 90 1 90 Deg Detection Time 0.1 300.0 0.1 0.1 sec 60 Load Break Switch Control RT-200P Inrush Rest No Yes No Function Use No Yes No SEF / Pick-up Current Set Range 2 ~ 20 A Default 5A Step 1A Step 1V Step 1 deg Set Pickup current. SEF / Pick-up Voltage Set Range 10 ~ 80 V Default 30 V Set pickup voltage. SEF / Angle Set Range 0 ~ 90 deg Default 0 deg Set angle. SEF / Detection Time Set Range 0.1 ~ 300.0 sec Default 0.1 Default 0.1 sec Set Detection time of SEF element. SEF / Inrush Restraint Set Range Yes / No Default No Step Set [YES /No] of direction Detection, when occurs Inrush Restraint. 61 Load Break Switch Control RT-200P SEF / Function use Range No Use / Use Default No Use Step Set [Use / No Use] of direction Detection, when occurs Ground fault. 7.1.9. Under Frequency Setting Range Step Def. Unit Min Max F-Pick Up 45.00 60.00 0.01 49.80 Hz V-PickUp 50 85 1 80 % Delay Time 0.1 20.0 0.1 1.0 Sec Function Use No Yse No UFR / Pick-up Frequency Set Range 45.00 ~ 60.00 Hz Default 49.80Hz Step 0.01Hz Step 1% Step 0.1 s Set Pickup Frequency. UFR / Pick-up Voltage Set Range 50 ~85 % Default 80 % Set pickup voltage. UFR / Delay Time Set 62 Range 0.1 20.0 sec Default 1.0 s Load Break Switch Control RT-200P Set Delay Time UFR / Function use Range Yes / No Default No Step Set [Use / No Use] of direction Detection, when occurs Ground fault. 7.1.10. Over Frequency Setting Range Step Def. Unit Min Max F-Pick Up 50.00 70.00 0.01 62.20 Hz V-PickUp 50 85 1 80 % Delay Time 0.1 20.0 0.1 1.0 Sec Function Use No Use Use No Use OFR / Pick-up Frequency Set Range 50.00 ~ 70.00 Hz Default 62.20Hz Step 0.01Hz Step 1% Set Pickup Frequency. OFR / Pick-up Voltage Set Range 50 ~85 % Default 80 % Set pickup voltage. OFR / Delay Time Set 63 Load Break Switch Control RT-200P Range 0.2 20.0 sec Default 1.0 s Step 0.1 s Set Delay Time OFR / Function use Range No Use / Use Default No Use Step Set [Use / No Use] of direction Detection, when occurs Ground fault. 7.1.11. Under Voltage Setting Range Step Def. Unit Min Max V-PickUp 50 90 1 80 % Delay Time 0.1 20.0 0.1 1.0 Sec Function Use No Use Use No Use UVR / Pick-up Voltage Set Range 50 ~90 % Default 80 % Step 1% Set pickup voltage. UVR / Delay Time Set Range 0.3 Default 1.0 s - 20.0 sec Set Delay Time UVR / Function use Range 64 No Use / Use Step 0.1 s Load Break Switch Control RT-200P Default No Use Step Set [Use / No Use] of direction Detection, when occurs Ground fault. 7.1.12. Over Voltage Setting Range Step Def. Unit Min Max V-PickUp 110 150 1 120 % Delay Time 0.1 20.0 0.1 1.0 Sec Function Use No Use Use No Use OVR / Pick-up Voltage Set Range 110 ~150 % Default 120 % Step 1% Set pickup voltage. OVR / Delay Time Set Range 0.4 Default 1.0 s - 20.0 sec Step 0.1 s Set Delay Time OVR / Function use Range Default No Use / Use No Use Step Set [Use / No Use] of direction Detection, when occurs Ground fault. 65 Load Break Switch Control RT-200P 7.1.13. Inhibit Setting OVR / Pick-up Voltage Set Range Default Disable / Enable Disable Step No-voltage detection condition setting in Fault Indicator logic. 66 Load Break Switch Control RT-200P 7.2. System Config Menu Locate the cursor on “System Config” in the main menu, and move to this menu by pressing [ENTER]. System Config menu has the following submenu. 7.2.1. Power Config Locate the cursor on “1. Power config” in System Config menu and move to this menu by pressing [ENTER] button. In this menu, various elements related to the system can be set. It has the following submenu. Range Step Def. Unit 10 50 Hz Min Max 50 60 System Type 3P4L 3P3L Rated Voltage 3800 26000 100 13200 V CT Ratio 100 2000 10 1000 A NCT Ratio 100 2000 10 1000 A CT Direction FWD REV System Frequency Ref Phase Phase Rotation 3P4L FWD A/B/C A ABC / ACB ABC Power Config / 1. System Frequency Set Range 50 / 60 Hz Default 50 Hz Step Frequency setting. This value is used to set digital sampling ratio. 67 Load Break Switch Control RT-200P Power Config / 2. System Type Range 380 ~ 26,000 V Default 26,000 V Step 10 V In Line system, rated voltage of power supply system is set. Power Config / 3. Rated Voltage Set Range 380 ~ 26,000 V Default 26,000 V Step 10 V In Line system, rated voltage of power supply system is set. Power Config / 4. CT Ratio Set Range 100 ~ 2,000 A Default 1,000 A Step 10 A Set the CT rate. Power Config / 5. NC.T Ratio Set Range Default 100 ~ 2,000 A 1,000 A Step Set the NCT rate Power Config / 6. C.T Direction Set Range Default FWD / REV FWD Set the CT Direction 68 Step 10 A Load Break Switch Control RT-200P Power Config / 7. Ref. Phase Range A/B/C Default A Step Setting the reference phase for the transposition function Power Config / 8. Phase Rotation Range ABC / ACB Default ABC Step Setting the phase Rotation for the transposition function 7.2.2. I/O Config Range Step Def. Unit Min Max Pulse Set (OPEN) 1200 5000 1 1200 ms Pulse Set (CLOSE) 1200 5000 1 1200 ms DI Config Aux Do Config User S/W Set Group Func Enable Set I/O Config / 1. Pulse Set Range 1,000 ~ 5,000 ms Default 1,200 Step 1ms ms Set Motor Output Pulse Time. Close or Open pulse width shall be set longer than switch operating time. 69 Load Break Switch Control RT-200P I/O Config / 2. DI Config Range 1 ~ 9999 ms Default 20ms Step 1 ms The Minimum time for recognizing a status change. To prevent a false operation due to chattering of the input status. I/O Config / 3. Aux. Do Config Range Default Step Selection of the output from the AUX DO conditions ON I/O Config / 4. User S/W Set Range Default None Step Function Enable mapping for user setting switch 70 Load Break Switch Control RT-200P 7.2.3. Other Config Range Step Def. Unit Min Max Manu Auto 0 600 Interlock Live Load No Yes No Interlock Sync’ Fail No Yes No Open Inter Lock No Yes No Batt’ Test Time Set 0 100 Sag Function Use No Yes Sag Level 10 90 1 90 % Sag Detect time 0.5 10.0 0.1 2.0 cycle Swell Function Use No Yes Swell Level 101 150 1 % % Swell Detect time 0.5 10.0 0.1 2.0 cycle Interruption Function Use No Yes Interruption Level 10 49 1 20 % Interruption Detect time 0.5 10.0 0.1 2.0 cycle FI Reset Select FI Clear Time Manu 1 0 1 sec 24 h No No No Other Config / 1. FI Reset Set Range Manu / Auto Default Auto Step Auto Mode : FI reset automatically when voltage is input after FI Set Manu Mode : FI Reset button or communication FI Reset command only FI reset FI Clear Time : Clear the FI status at the set time after determining the fault type. FI Clear Time = 0 (FI CLEAR Function Disable) Other Config / 2. InterLock Set Range Yes / No Default - Step Close Interlock The following close interlock condition blocks the switch to be closed manually or automatically if it’s selected as “Yes”. 71 Load Break Switch Control RT-200P - Open Interlock : Opened under rated load (640A) Other Config / 3. Battery Test Time Range 0 ~ 100 h Default 24h Step 1h Battery test function can be initiated automatically through setting. ⚫ Power Quality Menu to set parameters for detecting the short and long term voltage variations. The alarm level and detection delay time of voltage sag, voltage swell, and outage can be set. The distribution line’s rated voltage set at system parameter becomes the base of the alarm level for voltage sag, voltage swell, and outage. - Sag A sag (also known as dip) is a reduction to between 30% and 95% in RMS voltage or current at the power frequency for a short period of time from 0.5 to 10 cycles. Voltage sags are widely recognized as among the most common and important aspects of power quality problems affecting industrial and commercial customers. They are particularly troublesome. Since they occur randomly and are difficult to predict. Voltage sags are normally associated with system faults on the distribution system, sudden increase in system loads, lightning strikes or starting of large load like induction motors. It is not possible to eliminate faults on a system. One of the most common causes of faults occurring on high-voltage transmission systems is a lightning strike. When there is a fault caused by a lightning strike, the voltage can sag to 50% of the standard range and can last from four to seven cycles. Most loads will be tripped off when encounter this type of voltage level. Other Config / 4. Power Quality / 1. Sag Use Range No Use / Use Default No Use Step Set whether to use the function 72 Load Break Switch Control RT-200P Other Config / 4. Power Quality / 1. Sag Level Range 30 ~ 95 % Default 90% Step 1% Sag detection level Other Config / 4. Power Quality / 1. Sag Detection Time Set Range 0.5 ~ 10.0 cycle Default 2.0 Step 0.1 cycle Sag detection time setting - Swell A swell (also known as momentary overvoltage) is an increase in RMS Voltage to between 105% and 150% for duration from 0.5 to 10 cycles. Swells are commonly caused by system conditions, switching off a large load or energizing a large capacitor bank. A swell can occur during a single line-to-ground fault (SLGF) with a temporary voltage rise on the unfaulted phases. They are not as common as voltage sags and are characterized also by both the magnitude and duration. During a fault condition, the severity of a voltage swell is very much dependent on the system impedance, location of the fault and grounding. The effect of the type of disturbance would be hardware failure in the equipment due to overheating. Other Config / 4. Power Quality / 2. Swell Use Range No Use / Use Default No Use Step Set whether to use the function Other Config / 4. Power Quality / 2. Swell Level Range 105 ~ 125 % Default 120 Swell detection level 73 Step 1% Load Break Switch Control RT-200P Other Config / 4. Power Quality / 3. Swell Detection Time Set Range 0.5 ~ 10.0 Cycle Default 2.0 Step 0.1 cycle Swell detection time setting – Interruption An interruption occurs when there is a reduction of the supply voltage or load current to between 10% and 49% for duration from 0.5 to 10 cycles. Possible causes would be circuit breakers responding to over load, lightning and faults. Interruption are the result of equipment failures, power system faults and control malfunction. They are characterized by their duration as the voltage magnitude is always less than 10% of the nominal. The duration of an interruption can be irregular when due to equipment malfunction or loose connections. The duration of and interruption due to a fault on the utility system is determined by the utility protective devices operating time. Voltage interruption is a large decrease in RMS voltage to less than a small percentile of the nominal voltage, or a complete loss of voltage. Momentary interruptions can cause absolute voltage loss, and they are normally the result by utilities to clear transient faults on systems. Sustained interruptions during over one minute are normally caused by permanent faults or scheduled downtime Other Config / 4. Power Quality / 3. Interruption Use Range No Use / Use Default No Use Step Set whether to use the function Other Config / 4. Power Quality / 3. Interruption Level Range 10 ~ 49 % Default 20 Interruption detection level 74 Step 1% Load Break Switch Control RT-200P Other Config / 4. Power Quality / 3. Interruption Detection Time Set Range 0.5 ~ 10.0 Cycle Default 2.0 Step Interruption detection time setting 75 0.1 cycle Load Break Switch Control RT-200P 7.2.4. Communication Config Locate the cursor on “Communication” in System Config, move to this menu by pressing [ENTER] button. In this menu, all elements related to the communication can be set and has the following submenu. Communication Config / 1. Protocol Select Range DNP/IEC-101/ IEC-104 / DNP-TCP Default DNP Step Protocol selection Menu : DNP3.0 / IEC-60870-101 / IEC-60870-104 / DNP-TCP 7.2.5. Modem Control Setting Communication Config/ 2. Modem Control /1. Comm. Speed Set Range 1200,2400,4800,9600, 19200 bps Default 9600 bps Select the Baud Rate of Port 76 Step Load Break Switch Control RT-200P Communication Config / 2. Modem Control / 2. Comm. Line Range 2Wire / 4Wire Default 2 Wire Step Modem Communication line setting. Communication Config/ 2. Modem Control / 3. RTS Off Delay Set Range 10 ~ 500 ms Default 10 ms Step 1 ms RTS Off Delay Time set the delay time of RTS sign that become Off after the data transmission. It is time delay to prevent the liss if last data after sending the data. Communication Config/ 2. Modem Control / 4. CTS Timeout Set Range 1 ~ 255 sec Default 1 sec Step 1 sec Set a Waiting time that waits Modems confirmation on RTS signal which informs that RT-200P is ready to transfer a data. CommunicationConfig/ 2. Modem Control / 5. DCD Timeout Set Range 100 ~ 30,000 ms Default 100 ms Step 100 ms Set a delay time of DCD signal timeout which determine modem status before sending RTS signal in 2 wire communication type. 7.2.6. TCP Control Communication Config / 3. TCP Control / 1. IP Setting Range Default Step When TCP / IP mode, set the IP address 77 Load Break Switch Control RT-200P Communication Config / 3. TCP Control / 2. Subnet Mask Setting Range Default Step When TCP / IP mode, set the Subnet Mask. Communication Config / 3. TCP Control / 3. Gateway Setting Range Default Step When TCP / IP mode, set the GATEWAY address Communication Config / 3. TCP Control / 4. LAN Port Setting Range 1 ~ 65534 Default 2404 Step 1 When TCP / IP mode, set the LAN Port Communication Config / 3. TCP Control / 5. LAN Card Select Range 1 ~ 2 Port Default 1 Step 1 LAN Card Port Setting (2 Port Option) 7.2.7. SNTP Control Communication Config / 3. TCP Control / 6. SNTP Setting Range No Use / Use Default Step When TCP / IP mode, set the IP address *SNTP function is not supported for products before October 20, 2020. 78 Load Break Switch Control RT-200P Communication Config / 3. TCP Control / 6. SNTP Setting Range Default Step Set time server IP address Communication Config / 3. TCP Control / 6. SNTP Setting Range 1 ~ 65534 Default 123 Step 1 Step 1 Time Server Port Settings Communication Config / 3. TCP Control 6. SNTP Setting Range UTC / Local Default UTC Select Change from UTC to Local time Communication Config / 3. TCP Control 6. SNTP Setting Range -12 ~ 13 Hour Default 0 Step 1 Change time from UTC to Local time Communication Config / 3. TCP Control 6. SNTP Setting Range 0 ~ 59 min Default 0 Step Change time from UTC to Local time 79 1 Load Break Switch Control RT-200P Communication Config / 3. TCP Control / 6. SNTP Setting Range 0 ~ 24 h Default 24h Step 1h Time synchronization interval setting 7.2.8. DNP Parameter Setting RT-200p can DNP3.0 communicate by using the communication port2. For more information refer the “DNP3.0 Protocol Manual”. Item Range Default Step 0~2 0 1 D/L Timeout 0~255 0 1 D/L Confirm Yes/ No/Sometimes No 0~2 0 1 A/L Timeout 0~255 0 1 sec Initial Unsolicited MSG Yes/No No Unsolicited Class 1 Disable/Enable Disable Unsolicited Class 2 Disable/Enable Disable Unsolicited Class 3 Disable/Enable Disable Unsolicited Delay Time 0~60 0 1 sec SBO Timeout 1~255 15 1 sec Master Address set 0~65534 3 1 Slave Address Set 0~65534 4 1 Multi Frame Interval 10~500 10 1 D/L Retries A/L Retries Unit sec ms Communication Config / 4. DNP Parameter / 1. D/L Retry Set Range Default 0~2 0 Step 1 Set the retry number of Data Link. Communication Config / 4. DNP Parameter / 2. D/L Timeout Set 80 Range 0 ~ 255 sec Default 0 Step 1 sec Load Break Switch Control RT-200P Set the waiting time of Data Link Frame transmission to the Data Link Confirm (ACK) receiving of the master side. RT-200P resends the Data Link Frame, when the Data Link Confirm has not received during the setting time and it is possible to retry the Data Link. Communication Config / 4. DNP Parameter / 3. D/L Confirm Set Range Yes, No, Sometime Default No Step Choose whether Data Link Confirm is used or not. NO : Data Link Confirm is not used. YES : Data Link Confirm is used Sometime : When set the use of Data Link Confirm, check the setting status of host and set same with the host. If the setting status is different with the host can be occur an communication error because of Data Link Reset. Communication Config / 4. DNP Parameter / 4. A/L Retry Set Range 0~2 Default 0 Step 1 set the Retry of A/L Confirm(ACK) receiving from Mast Application to Slave Application. Communication Config / 4. DNP Parameter / 5. A/L Timeout Set Range 0 ~ 255 sec Default 0 Step 1 sec In case that request Confirm during the data transmission from Slave Application to Master Application, set the maximum time of A/L Confirm (ACK) receiving from Mast Application to Slave Application. Communication Config / 4. DNP Parameter / 6. Initial Unsol Set Range 81 Yes, No Load Break Switch Control RT-200P Default No Step Select [YES/NO] of Initial Unsolicited Response Use when Power Up. YES : When Power Up, transmit the Initial Unsolicited Response Message. NO : When Power Up, do not transmit Initial Unsolicited Response Message. Communication Config / 4. DNP Parameter / 7. Unsol Delay Set Range 0 ~ 60 sec Default 0 Step 1 sec Set the delay time of Unsolicited mode event transmission to the master station. It is transmitted if new event does not happen during this time. Communication Config / 4. DNP Parameter / 8. SBO Timeout Set Range 1 ~ 255 sec Default 15 Step 1 sec Set the time interval between Select Function and Operate Function. Communication Config / 4. DNP Parameter / 9. Master address Set Range Default 82 0 ~ 65534 0 Step 1 Load Break Switch Control RT-200P Enter the DNP address of Master station. RT-200P refer this address when send Unsol message. Communication Config / 4. DNP Parameter / 10. Slave Address Set Range 0 ~ 65534 Default 999 Step 1 Set RTU Address ID. CommunicationConfig/ 4. DNP Parameter / 11. Frame Interval Set Range 10 ~ 500 ms Default 10 ms Step 1 ms Frame Interval time Setting 7.2.9. IEC Parameter Setting Communication Config / 4. IEC Parameter / 1. A/L Cyclic Period Setting Range 0 ~ 60 sec Default 1 Step 1 sec Setting the cycle time of the application layer Communication Config / 4. IEC Parameter / 2. SBO Time Out Setting Range 1-255 sec Default 15 Step 1 sec Set the time interval between Select Function and Operate Function. Communication Config / 4. IEC Parameter / 3. M_SP_Cyclic Setting 83 Load Break Switch Control RT-200P Range Enable / Disable Default Disable Step When using IEC Protocol selection, Single Point Cyclic data transmission setting. Communication Config / 4. IEC Parameter / 4. M_DP_Cyclic Setting Range Enable / Disable Default Disable Step When using IEC Protocol selection, Double Point Cyclic data transmission setting. Communication Config / 4. IEC Parameter / 5. M_ME_Cyclic Setting Range Enable / Disable Default Disable Step When using IEC Protocol selection, Measured value Cyclic data transmission setting. Communication Config/ 4. IEC Parameter / 6. M_SP_Address Setting Range 1-10000 Default 100 Step Using IEC Protocol Single Point Base address setting. Communication Config/ 4. IEC Parameter / 7. C_SC_Address Setting Range 1-10000 Default 200 Step Using IEC Protocol single command Base address setting. Communication Config/ 4. IEC Parameter / 8. M_DP_Address Setting 84 Range 1-10000 Default 300 Step Load Break Switch Control RT-200P Using IEC Protocol Double Point Base address setting. Communication Config/ 4. IEC Parameter / 9. C_DC_Address Setting Range 1-10000 Default 400 Step Using IEC Protocol Double command Base address setting. Communication Config/ 4. IEC Parameter / 10. M_ME Address Setting Range 1-10000 Default 1000 Step Using IEC Protocol Measured value Base address setting. Communication Config/ 4. IEC Parameter / 11. C_SE_Address Setting Range 1-10000 Default 2000 Step Using IEC Protocol Set Point Command Base address setting. Communication Config/ 4. IEC Parameter / 12. M_IT_Address Setting Range 1-10000 Default 4000 Step Using IEC Protocol Integrated totals Base address setting. 85 Load Break Switch Control RT-200P 7.2.10. IEC 101 Parameter Setting Communication Config / 5. IEC 101 Parameter / 1. LINK Address Range 1 ~254 Default 1 Step 1 Set the link address of the IEC 60870-5-101 slave station The setting range varies depending on the Link size. Re-confirmation after Link size is set. Communication Config / 5. IEC 101 Parameter / 2. ASDU Address Range 1 ~ 254 Default 1 Step 1 Set the ASDU(Application Service Data Units) Address. The setting range varies depending on the ASDU size. Re-confirmation after ASDU size is set. Communication Config / 5. IEC 101 Parameter / 3. Originator Address 86 Range 0 ~ 254 Default 1 Step 1 Load Break Switch Control RT-200P Set the number of bytes for the application layer “Information Object Address” field in an IEC 60870-5-101 message. Communication Config / 5. IEC 101 Parameter / 4. LINK Address Size Range 1~2 Default 1 Step Data Link Address Size. Set the number of bytes for "Link address" field in an IEC60870-5-101 Protocol. Communication Config / 5. IEC 101 Parameter / 5. ASDU Address Size Range 1~2 Default 1 Step ASDU Address Size Set the number of bytes for the application layer “ASDU Address” field in an IEC 60870-5-101 message. Communication Config / 5. IEC 101 Parameter / 6. IOA Address Size Range 1~3 Default 3 Step Information Object Address Size In IEC60870-5-104 IOA Address Size is Fixed 3. Communication Config / 5. IEC 101 Parameter / 7. COT Address Size Range 1~2 Default 2 Step COT Address Size In IEC60870-5-104 COT Address Size is Fixed 2. Communication Config / 5. IEC 101 Parameter / 8. Link Mode Setting 87 Load Break Switch Control RT-200P Range Unbalance / Balance Default Unbalance Step Set the Link mode in an IEC608705-101 Protocol. RT-200P Control only supports unbalanced mode. Communication Config / 5. IEC 101 Parameter /9. Time Marker Range None/ CP24/CP56 Default CP56 Step Time Type Setting of SP and DP Information in IEC60870-5 101/104 Protocol Communication Config / 5. IEC 101 Parameter /10. ME Data Type Range ME_NB_1 / Default ME_NB_1 ME_NC_1 Step Measurement data transmission data type setting. M_ME_NB_1 : Measured value, scaled value M_ME_NC_1 : Measured value, short floating point value 7.2.11. IEC 104 Parameter Setting Communication Config / 7. IEC 104 Parameter Range Default IEC60870-5-104 Step protocol setting menu following. Communication Config / 7. IEC 101 Parameter / 1. T0 Off Line Poll Period Range 1 ~255 Default 1 Step 1s Network connection establishment timeout Communication Config / 7. IEC 104 Parameter / 2. T1 Ack Period 88 is as Load Break Switch Control RT-200P Range 1 ~ 255 Default 1 Step 1s Response timeout Communication Config / 7. IEC 104 Parameter / 3. T2 S Frame Period Range 1 ~ 255 Default 10 Step 1s A S-format frame (ACKRSN) will be sent at the latest after this time starting from the last received telegram from the server. Communication Config / 7. IEC 104 Parameter / 4. T3 Test Period Range 1 ~ 255 Default 20 Step 1s An U-format frame (TESTFR) will be sent at the latest after this time starting from the last received telegram from the server. 89 Load Break Switch Control RT-200P 7.2.12. Event Clear This menu Maintenance and data resets. LBS Open Counter setting/reset (Maintenance) and Event data clear. Item Sub Item Range step S/W Counter 0-65535 1 Clear Event Clear all events Yes/No Clear Fault wave Clear all Faults Yes/No Clear Counter Clear all Fault Count Yes/No Clear Energy Clear all Energy Yes/No Clear all PQ Counter Yes/No Set S/W Counter Clear PQ Counter 7.2.13. Time Set present date and time Time Set Range Default Step Press [ENTER] button to select and change a setting. To change a number, use [UP] [DOWN] button and to move next item, press [ENTER] button. To save all changed setting, press [ENTER]. 7.2.14. Pass Word Setting Time Set Range Default 90 Step Load Break Switch Control RT-200P Press [ENTER] button to select and change a setting. To change a number, use [UP] [DOWN] button and to move next item, press [ENTER] button. To save all changed setting, press [ENTER]. 7.2.15. Voltage Adjust Time Set Range Default Step Press [ENTER] button to select and change a setting. To change a number, use [UP] [DOWN] button and to move next item, press [ENTER] button. To save all changed setting, press [ENTER]. 91 Load Break Switch Control RT-200P 8. Display Menu The RT-200P provides extensive and accurate metering capabilities. See Specification part for metering and power measurement accuracies. [Fig. 8-1 ] Overview Display Menu [Fig. 8-2] Overview Measurement Menu Measurement Operator can monitor all kinds of measurement values such as current, voltage, sequence value, power, etc. Real-time in I & V& Power measurement display. In this menu, indicate to measurement values. 92 Load Break Switch Control RT-200P 8.1. Monitoring and Metering Display Items Currents Displayed Values [unit] Ia, Ib, Ic, In : RMS[A] & Phase Angle [Deg] Va, Vb, Vc, Vr, Vs, Vt [kV] Zero-sequence : VoS, VoL, (S: Source-side, L: Load-side) Voltages Positive-sequence : V1S, V1L Negative-sequence : V2S, V2L :Magnitude [A] & Phase Angle [Deg] Measurements Active Power Pa, Pb, Pc, P3p [MW] Reactive Power Qa, Qb, Qc, Q3p [MVAR] Apparent Power Sa, Sb, Sc, S3p [MVA] Power factor PFa, PFb, PFc, PF3 Phase Difference ∠Va - ∠Vr Phase Difference between A-phase and R [Deg] Measure / 1. Current Current View Measure / 2. Voltage View Voltage View 93 Load Break Switch Control RT-200P Measure / 3. Phase Difference Phase Difference View Measure / 4. Power Power Meter View Measure / 5. Energy Energy View Measure / 6. Demand 94 Load Break Switch Control RT-200P The average Power and daily maximum power display Measure / 7. THD THD View Measure / 8. Harmonic View 95 Load Break Switch Control RT-200P Current A,B,C,N Voltage A,B,C,R,S,T Harmonic ingredients Measure / 9. Frequency VA Frequency View 8.2. Status view In status display, Switch and Gas Low, Handle Lock, AC Power, Battery health, Door Open, Local/Remote, FRTU address, Master address, Firmware Version information - all the status indications are displayed. 96 Load Break Switch Control RT-200P Status Switch Displays main device status. - OPEN/CLOSE,TROUBLE Gas Low LBS gas pressure status is displayed. - NORMAL/LOW Handle Lock Manual lock status is displayed. - LOCK/UNLOCK AC Power In External Power supply status is displayed. - NORMAL/OFF Battery Health Battery status is displayed. - NORMAL/LOW Discharger Display circuit and battery charging status - NORMAL/LOW Door Open Door status is displayed. - OPEN/CLOSE Local/Remote Operation control select is displayed. - REMOTE/LOCAL Control Lock FRTU Control Lock Status AUX. DI1.2.3.4 AUX. DI Status Control Fail Main Device operation fail. Temper RTU PCB Temperature System Voltage The voltage supplied by the system Batter Test Voltage Battery voltage during battery test 8.3. Counter view This menu displays counter information. It shows restart, SW Open and fault count, Phase Fault. Counter Restart RT-200P restart counter S/W Open LBS body open counter 97 Load Break Switch Control RT-200P All Fault All faults detection counter CH A,B,C,N Fault Each Phase Fault Detection Counter Number of occurrences of power quality for PQ Count each phase 8.4. Alarm View This menu displays controller Fault detection. Alarm View Fault detection status for each phase. Fault detection status latch for each phase, "FI Reset" canceled. Under Voltage Alarm View Over Voltage Alarm View Under Frequency / Over Frequency Alarm View 98 Load Break Switch Control RT-200P 8.5. System Information FRTU System Information or DNP 3.0 Slave Master Address. 99 Load Break Switch Control RT-200P 9. Event (Event Log) Event Reports and Events Recorder features simplify post-fault analysis and help improve your understanding of both simple and complex protective scheme operations. These features also aid in testing and troubleshooting relay settings and protection schemes. Select “EVENT LIST” in the main menu, and move to this menu by pressing ENTER. “EVENT LIST” menu has the following submenu. [Main Lock ] 01/128 20XX/XX/XX XX:XX:XX Status: Lock [Fault : C ] 01/128 20XX/XX/XX XX:XX:XX Ia : A Ib : A Ic : A In : A [Set Change ] 01/128 [EVENT LIST] 20XX/XX/XX XX:XX:XX Sys Config Local Pannel >1.I/O event [ 0] 2.F/I event [ 0] 3.Sys event [ 0] 4.Control evnt[0] 5.Measure evnt[ 0] [Batt Test ] 01/128 20XX/XX/XX XX:XX:XX local pannel [Average 15 ] 01/128 20XX/XX/XX XX:XX:XX Qa : A Qb : A Qc : A TT : A When the status of the control electronics or LBS changes, events are generated which are recorded in an Event Log for display to the operator. Events are viewed on the Event Log pages and can also be up-loaded and viewed with the Control Operating System. The event log display looks like this: Events are dated, time stamped to a 10ms resolution and displayed in the order in which they occurred. The DOWN key scrolls the display downward to show older events, the UP key scrolls the display upward to show more recent events. Event List I/O Event Description Max Status Change of binary Input / Output ➔ SW State 125 ➔ Main Lock F/I Event Operated status of Fault Indication ➔ Fault count : a, b ,c, n, all 250 ➔ Latest fault current, phase and time System Event Status Change of System ➔ Open / Close / Door / Handle Lock / GAS Low 100 125 Load Break Switch Control RT-200P / Battery Low /etc ➔ System Reset ➔ AC Loss ➔ Door Status ➔ Batter Low Control Event Controlled status of RT_200P ➔ Battery test / 125 ➔ SW Control (Open/Close) Measure Event ➔ Pa/Pb/Pc/TT Each 125 ➔ Qa/Qb/Qc/TT Total : 750 ➔ Ia/Ib/Ic/TT Power Quality ➔ Voltage Sag ➔ Voltage Swell 125 ➔ Interruption Event List Waveform Description • Waveform Recording Storage : 8 Fault Waveforms of 10 cycles. Sampling ratio : 32 Sample/Cycle * 10 Cycles Max 8 fault waveforms can be captured on non-volatile memory Evnet / 1. I/O Event Event status change Event / 2. F.I Event Fault history Event Event / 3. System Event 101 Load Break Switch Control RT-200P The overall state of the system such as history FRTU changes to the system and self-test Event / 4. Control Event Control command history Event Event / 5~10. Measure Event The average power and the daily peak load event. Average Current, Average Power, Average Reactive Power Day Max Current , Day Max Power, Day Max Reactive Power Event / 11. PQ Event Display of PQ type, occurrence time, phase value, and occurrence and holding time information 102