Uploaded by bảo hoàng lê

RT R200P Menual R1.5.9-211001-PQ (2)

advertisement
CONTENT
1.
Product Introduction ........................................................................................................5
1.1.
Introduction RTU ...................................................................................................................... 5
1.2.
Features ...................................................................................................................................... 6
2.
Technical Specification .....................................................................................................8
2.1.
Control General Specification ................................................................................................ 8
2.2.
Environment Condition ........................................................................................................... 9
2.3.
FRTU TECHNICAL SPECIFICATION ....................................................................................... 10
2.4.
Digital Process ........................................................................................................................ 10
2.4.1.
Digital Signal Controller (DSCs) ..................................................................................................................... 10
2.4.2.
Analog/Digital Conversion ............................................................................................................................... 11
2.4.3.
Function .................................................................................................................................................................. 11
2.5.
Function Block Diagram ........................................................................................................ 12
2.6.
Fault Detect and Sectionalizing Functions ........................................................................ 13
2.7.
Power System Measurements .............................................................................................. 15
2.8.
System Setting ........................................................................................................................ 16
2.9.
Communications ..................................................................................................................... 18
2.10.
Event Record ........................................................................................................................ 21
2.10.1.
Event Record ......................................................................................................................................................... 21
3.
Physical Description....................................................................................................... 23
4.
Input/output Connector ............................................................................................... 24
4.1.
Modem Power supply Input ................................................................................................ 25
4.2.
Current Input ........................................................................................................................... 25
4.3.
Voltage Input........................................................................................................................... 25
4.4.
Remote Communication Port .............................................................................................. 25
4.5.
Digital Input /Output ............................................................................................................ 26
Load Break Switch Control
RT-200P
4.6.
DOOR Port ............................................................................................................................... 26
4.7.
AUX. DI/DO ............................................................................................................................. 26
4.8.
Motor Output Port ................................................................................................................. 26
4.9.
Power Supply Input (AC Input) ........................................................................................... 26
4.10.
Battery Port.......................................................................................................................... 27
4.11.
Main Power Switch ............................................................................................................. 27
4.12.
ETHERNET Connector ......................................................................................................... 27
5.
Operator Control Panel ................................................................................................. 28
5.1.
Description............................................................................................................................... 28
5.2.
Construction ............................................................................................................................ 32
5.2.1.
Operation ............................................................................................................................................................... 32
5.2.2.
Menu Control........................................................................................................................................................ 33
5.2.3.
Other Control ........................................................................................................................................................ 33
5.2.4.
Fault Indication ..................................................................................................................................................... 34
5.2.5.
Line Status Indication......................................................................................................................................... 34
5.2.6.
SECTION Status .................................................................................................................................................... 35
5.2.7.
System Status ........................................................................................................................................................ 35
5.2.8.
AC/HANDLE LOCKED/GAS LOW/Battery Status ....................................................................................... 36
5.2.9.
CONSOL Port ........................................................................................................................................................ 36
5.3.
Operation Manual (LCD instruction) .................................................................................. 37
5.3.1.
LCD Screen ............................................................................................................................................................. 37
5.3.2.
Control button ...................................................................................................................................................... 37
5.3.3.
Menu structure tree............................................................................................................................................ 38
5.4.
LCD Menu Use ........................................................................................................................ 39
5.4.1.
Initial Screen .......................................................................................................................................................... 39
5.4.2.
Main Menu ............................................................................................................................................................ 40
5.4.3.
Setting Menu ........................................................................................................................................................ 41
6.
Fault Indication ............................................................................................................... 43
6.1.
Fault Indication ....................................................................................................................... 43
6.2.
Cold load PickUp .................................................................................................................... 47
6.3.
Operation of Inrush ............................................................................................................... 47
2
Load Break Switch Control
RT-200P
6.4.
SEF (Sensitive Earth Fault) Detection ................................................................................. 48
6.5.
Role of the Sectionalizer(Auto Sectionalizing) ................................................................. 48
6.6.
Phase Loss Detection ............................................................................................................. 50
6.7.
Phase Sync. Check .................................................................................................................. 50
6.8.
Sectionalizer Inhibit ............................................................................................................... 50
7.
Operation Setting ........................................................................................................... 51
7.1.
Operation Setting ................................................................................................................... 51
7.1.1.
Phase Fault Setting ............................................................................................................................................. 51
7.1.2.
Ground Fault Setting .......................................................................................................................................... 53
7.1.3.
Inrush Detect Setting ......................................................................................................................................... 55
7.1.4.
FI Reset Time Setting ......................................................................................................................................... 57
7.1.5.
Line Open Setting ............................................................................................................................................... 57
7.1.6.
Sync. Check Setting ............................................................................................................................................ 58
7.1.7.
Sectionalize Setting ............................................................................................................................................ 59
7.1.8.
SEF Setting ............................................................................................................................................................. 60
7.1.9.
Under Frequency Setting.................................................................................................................................. 62
7.1.10.
Over Frequency Setting .................................................................................................................................... 63
7.1.11.
Under Voltage Setting ....................................................................................................................................... 64
7.1.12.
Over Voltage Setting .......................................................................................................................................... 65
7.1.13.
Inhibit Setting ....................................................................................................................................................... 66
7.2.
System Config Menu ............................................................................................................. 67
7.2.1.
Power Config......................................................................................................................................................... 67
7.2.2.
I/O Config .............................................................................................................................................................. 69
7.2.3.
Other Config ......................................................................................................................................................... 71
7.2.4.
Communication Config ..................................................................................................................................... 76
7.2.5.
Modem Control Setting .................................................................................................................................... 76
7.2.6.
TCP Control............................................................................................................................................................ 77
7.2.7.
SNTP Control ........................................................................................................................................................ 78
7.2.8.
DNP Parameter Setting ..................................................................................................................................... 80
7.2.9.
IEC Parameter Setting ........................................................................................................................................ 83
7.2.10.
IEC 101 Parameter Setting ............................................................................................................................... 86
7.2.11.
IEC 104 Parameter Setting ............................................................................................................................... 88
7.2.12.
Event Clear ............................................................................................................................................................. 90
7.2.13.
Time.......................................................................................................................................................................... 90
3
Load Break Switch Control
RT-200P
8.
Display Menu .................................................................................................................. 92
8.1.
Monitoring and Metering ..................................................................................................... 93
8.2.
Status view............................................................................................................................... 96
8.3.
Counter view ........................................................................................................................... 97
8.4.
Alarm View .............................................................................................................................. 98
This menu displays controller Fault detection. ........................................................................... 98
8.5.
9.
System Information ............................................................................................................... 99
Event (Event Log) ......................................................................................................... 100
4
Load Break Switch Control
RT-200P
1. Product Introduction
1.1. Introduction RTU
RT-200P is embedded in Distribution Automation SF6 gas insulated load break switch
(Pole mount) control box.
It receives measurement information (3 phases current &
voltages) and status information from Switch, and meters current and voltage, detects FI,
Line cut, Live line/Dead line, Unbalance, Sectionalizer optimized for remote control and
automation systems.
RT-200P monitors not only electric quality of distribution line but also, provides Section
operation in case of fault occurring and minimize its fault area.
All events occurring in the distribution line, are saved and provides fault analysis. With
using DNP3.0 Protocol, provides monitored status to SCADA for switch operation. Not
only DNP3.0 Protocol, other communication protocols can be provided by user’s request.
As well as, controlling a switch by receiving Control Signal from SCADA, provides
Distribution Automation and minimize a fault area.
5
Load Break Switch Control
RT-200P
1.2. Features

Magnitude and phase angle of voltages & currents

Sequence components of 3-Phase voltages & currents

True RMS of voltages & currents

Active, reactive and apparent power for each phase and
3-phase
Measurements

Energy(4-quadrant metering)

Displacement Power Factor

Frequency

Phase difference between source-side and load-side
voltage
Control
Interlocking
Protection
Status

Ground Fault

SEF

Inrush Detect

Sync. Check

Sectionalize
•
Manual LBS Open/Close at local or remote

operator Place,

Battery Test
•
•
•
•
•
•
Gas low
Handle lock
Operator place
Control lock
Sync. Fail
Live Load

Fault Detection (Phase and Earth Fault)

SEF(Sensitive Earth Fault) Detection

Cold Load protection(Pickup Adjustment)

Magnetizing Inrush Restraints

Open Line Detection

Phase Sync. Fail Detection

Switch Open/Closed/Select
6
Load Break Switch Control
RT-200P
Monitoring

Mechanical Locked

Gas Pressure Low

External AC Power

LBS Door Open

Battery Low

Local/Remote

Fault Indication

Open Line Detection
•
Event recording with time stamp
F.I Event / I/O Event / System Event / Control Event
/ Measure Event(Demand Current &
Event Record
Power, Daily Max Current & Power)
•
Waveform Recording
Storage: 8 Fault Waveforms of 10 cycles.
Sampling ratio : 32 Sample/Cycle * 10 Cycles
Counter
Communication
•
Restart(Boot Count)
•
Switch Open Count
•
All Fault Count
•
Ch A, Ch B, Ch C, Ch N Fault

Port1 : Panel Serial Port (Maintenance Port : Modbus)

Port2 : Serial Port (DNP3.0, IEC60870-5-101 Protocol )

Port3 : TCP Port (IEC60870-5-104, DNP/TCP)
-
7
RJ-45 2 Port (Option)
Load Break Switch Control
RT-200P
2. Technical Specification
This section details the technical specifications of the Load Break Switch (LBS) and Control System.
Provide to detail setting values of timing, current, voltage and other measurement accuracy is given
2.1. Control General Specification
Maintenance interval
5 years
Auxiliary supply voltage (LV AC mains supply)
As Ordered +10 -20%
Required auxiliary supply rating
50 VA, 120VA
Battery
2 x 12V 12Ah
Battery replacement interval
5 years
Earthing
Modem
10mm earth stud
Modem may be fitted by the manufacturer or by the utility, for remote communications.
Space, power and data interfaces are provided within the control cubicle.
Modem Power Supply Voltage (set by user)
24V DC
Modem Power Supply Continuous Current
1.3A
Modem Power Supply Max Current
Modem Interface
Auxiliary Power supply(Internal
3A for 30 sec with 20% duty
cycle
RS232
Power)
Supply from an external AC Source
110V or 240V
Battery Charging /Control Power Transformer
-
Motor Power – 30VAC to 30VDC
-
Battery Charging/Control Power – 15VAC to
30VAC to 30VDC
15VDC
Main Power – 16VAC
-
Battery Charging Power: 27VDC
-
Control Power : 24VDC
8
16VAC to 27VDC
-
SMPS
Load Break Switch Control
RT-200P
2.2. Environment Condition
Environmental condition
Altitude

< 2,000m
Wind Speed

40m/s

CT Input, VT Input, Control Power Input, Fiberoptic insulation Input and Relay output
Dielectric Strength


Impulse Voltage
AC 60㎐, 2㎸/1 minute
IEEE C62.45 (1992) , 6㎸(1.2×50㎲), 3㎄(8×20㎲) of
Relay System for Radio Electromagnetic Interference
Transceiver.

Protection relay and Relay system protection purpose
IEEE C37.90.1 - 1989 IEEE SWC test (3 ㎸ Vibration1 ㎒
to 1.5 ㎒, 5 ㎸ fast saturation 1.2×50 ㎲)
Surge Withstand Capability

IEEE C37.90.2 - 1987 IEEE Test, Test use standard, relay
system for Radio Electromagnetic
Interface that comes from Transceiver, 10 V/m(150㎒
and 450㎒, 5 W transmitter 10㎝)

IEC 255-21-1-1988 Electric Relay, Part 21: Metering
relay and protection device vibration, impact, crash
and earthquake test, Section One - Vibration tests
Vibration Test
(sinusoidal), Class 2

IEC 255-21-1-1988 Electrical relays, Part 21 : Vibration,
shock, bump, and seismic tests on measuring relays
and protection equipment, Section One - Vibration
tests (sinusoidal), Class 2
Control Operating

Operation range : -25℃∼+70℃ (-13℉∼+158℉)
Temperature

LCD : -20℃∼+70℃(-4℉∼+158℉) Standard
9
Load Break Switch Control
RT-200P
2.3. FRTU TECHNICAL SPECIFICATION
FRTU Technical Specification
Frequency

50 / 60 Hz System
Power Input

AC Voltage Power : 16Vac/32Vac
Power Output

Modem : DC 24V Max : 1A
Current Transformer Input

Current Input IA,IB,IC,IN,ZCT (Max : 13A)
(CT: Current rate)

Burden : Below than 0.5VA

Input Rang : 2~6Vac

4Vrms at rated Phase Voltages

Burden : Below than 0.01VA

Open/Close Operate Output : 240Vac 16A, 30Vdc 16A

Aux DO 1~4 : 250Vac3A, 30Vdc 3A

Input 8 channel

Dry Contact Input Type
Capacitor Voltage Divider
Inputs(CVD)
Output Contacts
Input
2.4. Digital Process
2.4.1. Digital Signal Controller (DSCs)
DSP Processor Feature
High-Performance 32-Bit CPU
•
•
•
TMS320F283X 32-Bit core
FPU : 150MHz
Six-Channel DMA Controller (for ADC, McBSP, –
Up to 2 CAN Modules
•
•
ePWM, XINTF, and SARAM)
Harvard Bus Architecture – Up to 9 16-Bit
Timers
•
Fast Interrupt Response and Processing (6 for
ePWMs and 3 XINTCTRs)
•
•
•
Unified Memory Programming Model
DMA 6CH
On-Chip Memory : F28335, F28235: – One
Inter-Integrated-Circuit (I2C) Bus
•
•
•
256K x 16 Flash, 34K x 16 SARAM
Up to 6 Event Capture Inputs
Up to 2 Quadrature Encoder Interfaces
10
Load Break Switch Control
RT-200P
•
Serial Port Peripherals : 2 CAN / 3 SCI(UART) /
2 McBSP / 1 SPI / 1 I2C
2.4.2. Analog/Digital Conversion
ADC Feature

16 Bit A/D Converter

Anti-aliasing analog filter

One gain channel for each current input :
effective
16
bit
resolution
measurements
2.4.3. Function
Self-Diagnostic

Watch dog Timer

Control Power System

RTC Self Check Logic

Memory Check Logic

ADC Converter Self Check Logic
11
for
current
Load Break Switch Control
RT-200P
2.5. Function Block Diagram
12
Load Break Switch Control
RT-200P
2.6. Fault Detect and Sectionalizing Functions
Phase Fault Detection
Phase Fault Threshold Current Setting Range
5 to 900 A
(Pick up Current)
Default : 400A / step : 1A
Definite Time for Fault to Persist Setting Range
0.01 to 10.0 sec
(Detection Time)
Default : 0.02s / step : 0.01s
Inrush Restraint
Yes/No Default : No
100 ~ 500%
Cold Load Pickup
Default : 200% / step : 10%
0.1 to 180 sec
Cold Load Time
Default : 0.2sec / step : 0.1sec
Direction Detection Enable
No Use/Use Default : No Use
5 ~ 85 %
Direction Voltage Pickup
Default : 10% / Step : 1 %
0 ~ 359 deg
Direction MTA
Default : 0 deg / step : 1 deg
Ground Fault Detection
Earth Fault Threshold Current Setting Range
5 to 900 A
(Pick up Current)
Default : 60A / step : 1A
Definite Time for Fault to Persist Setting Range
0.01 to 10.0 sec
(Detection Time)
Default : 0.02s / step : 0.01s
Yes/No
Inrush Restraint
Default : No
Direction Detection Enable
No Use/Use Default : No Use
5 ~ 85 %
Direction Voltage Pickup
Default : 10% / Step : 1 %
0 ~ 359 deg
Direction MTA
Default : 0 deg / step : 1 deg
Inrush Detection
5 ~ 50 %
2nd Harmonic Setting Range
Default : 20 % / step : 1%
0.02 ~ 1 sec
Detection Time
Default : 0.02 / step : 0.01 sec
0.1~180.0 sec
Inrush Time
Default : 0.2 s step : 0.1 sec
100 ~ 1000 %
Multiple
Default : 200% / step : 10%
FI Reset Time
13
Load Break Switch Control
RT-200P
1~180 s
FI Reset Time
Default : 20s / step : 1s
Line Open Detection
Live Line ON Voltage Setting Range
50 ~ 90 %
Default : 50% / step : 1%
10 – 75%
Line OFF Voltage setting Range
Default : 50% / step : 1%
0.01 ~ 30 s
Detection Time setting Range
Default : 0.4s / step : 0.01s
Phase Sync. Check Set
5 ~ 60 deg
Phase Difference Setting Range
Default : 30deg / step : 1deg
0.1 ~30 s
Detection Time Setting Range
Default : 0.1s / step : 0.1s
Sectionalizer
VIT / VT
Sectionalizer Mode Select
Default : VIT
1
Faults to trip (Fault count)
to 3
default : 2 / step : 1
20 ~ 240 s
Sequence reset time
Default : 30s / step : 1s
SEF(Sensitive Earth Fault) Detection
Sensitive Earth Fault Threshold Current Setting Range
2 to 20 A
(Pick up Current)
Default : 5A / step : 1A
10 ~ 80 V
Pick up Voltage Setting Range
Default : 30V / step : 1V
0 ~ 90 deg
Angle Setting Range
Default : 90deg / step : 1deg
Definite Time for Fault to Persist Setting Range
0.1 to 30.0 sec
Default : 0.1s / step : 0.1s
Yes/No
Inrush Restraint
Default : No
UFR (Under Frequency Relay)
45.00 to 60.00 Hz
Under Frequency Pickup Level
Default: 49.80Hz/step : 0.01Hz
50 ~ 85 %
Pick up Voltage Setting Range
Default : 80% / step : 1%
0.1 ~ 20.0 sec
Delay Time Setting Range
Default : 1.0s / step : 0.1s
OFR (Over Frequency Relay)
14
Load Break Switch Control
RT-200P
50.00 to 70.00 Hz
Over Frequency Pickup Level
Default: 62.20Hz/step : 0.01Hz
50 ~ 85 %
Pick up Voltage Setting Range
Default : 80% / step : 1%
0.1 ~ 20.0 sec
Delay Time Setting Range
Default : 1.0s / step : 0.1s
UVR (Under Voltage Relay)
50 ~ 90 %
Pick up Voltage Setting Range
Default : 80% / step : 1%
0.1 ~ 20.0 sec
Delay Time Setting Range
Default : 1.0s / step : 0.1s
OFR (Over Voltage Relay)
110 ~ 150 %
Pick up Voltage Setting Range
Default : 120% / step : 1%
0.1 ~ 20.0 sec
Delay Time Setting Range
Default : 1.0s / step : 0.1s
Sectionalizer Inhibit
Inhibit
Yes/No Default : No
2.7. Power System Measurements
Current measurement
RMS(A) & Phase angle(°)
Ia, Ib, Ic, In
Sequence Component
I1, I2, I0
2 ~ 12,500 A
Reading Range
( External CT Ratio 1,000 : 1)
Accuracy
2~12,000A: ±1% or ±1A
Voltage Measurement
Sequence Component
Va, Vb, Vc, Vr, Vs, Vt [kV]
Voltage Measurement Range (RMS Phase to Earth)
V1s, V2s, V0s, V1L, V2L, V0L
0.38 to 26 kV
Voltage Measurement Resolution
±%1 or ±0.1kV
Phase angle difference(°)
∠Va - ∠Vr
Power Measurement
Active Power(kW)
Pa, Pb, Pc, P3p
Reactive Power(kVar)
Qa, Qb, Qc, Q3p
Apparent Power(kVA)
Sa, Sb, Sc, S3p
Accuracy
±1%
Power Factor Measurement
A phase, B Phase, C phase, 3Phase total
PFa, PFb, PFc, PF3
Power Measurement Range
0-100%
15
Load Break Switch Control
RT-200P
Accuracy
±2%
Frequency Measurement
Reading range
10 ~ 100Hz
Accuracy
±0.1Hz
Energy measurement
Reading range
0 ~ 65565
Accuracy
±2%
Average Demand Current and Power
Configurable demand interval
Ia, Ib, Ic, Pa, Pb, Pc, P3ph,
15minutes
Daily max. currents and power are stored
2.8. System Setting
Power Config
System Frequency
50 ~ 60 Hz / default : 50 Hz
System Type
3P4L~3P3L / default : 3P4L
Rated Voltage
3800 ~ 26000 V /
CT Ratio
100 ~ 2000 A / default : 1000 A
NCT Ratio
100 ~ 2000 A / default : 1000 A
CT Direction
FWD ~ REV / default : FWD
Ref Phase
A,B,C / default : A
Phase Rotation
ABC , ACB / default : ABC
I/O Config
1200 ~ 5000 ms /
Pulse Set (Do Pulse)
default : 1200ms(Motor)
DI : 1~9999ms /default 20ms
DI Debounce Time
AC Power : 1~60s / default : 20s
Aux. DO Config
Options for users
User Switch Setting
Other Config
FI Reset
Auto – Manu / default : Manu
FI Clear Time
0~600 sec / default : 300sec
1) Live Load(Volt Interlock)
Interlock
2_ Sync Fail (Sync Interlock)
: Yes – No
: Yes – No
3) Open Interlock : Yes – No
Battery Test Time
1 ~ 100 h / default : 24h
Power Quality
Voltage Sag
Level
Detect Time
10 ~ 99% default 90% / step : 1%
0.5 ~ 10.0 cycle , default : 2.0 cycle / step 0.1 cycle
16
Load Break Switch Control
RT-200P
Voltage Swell
Level
Detect Time
101 ~ 150% default 120% / step : 1%
0.5 ~ 10.0 cycle , default : 2.0 cycle / step 0.1 cycle
Interruption
Level
Detect Time
10 ~ 49% default 20% / step : 1%
0.5 ~ 10.0 cycle , default : 2.0 cycle / step 0.1 cycle
17
Load Break Switch Control
RT-200P
2.9. Communications
RS232C
DCD(1), Rx(2), Tx(3), DTR(4), GND(5), DSR(6),
9pin Signals
TRS(7), CTS(8), NC(9)
Speed(Baud rate)
1200,2400,4800,9600,19200,38400
 CTS,DCD signal Timeout Configurable
Modem Control
 RTS off-delay Configurable
DNP3.0 / DNP-TCP

Support DNP3.0 Subset Level 2

Class of each point is settable

Supports multi-frame transmission (multi-frame interval is configurable)

Enable/Disable unsolicited message class

Non-transmitted
events
are
stored
on
non-volatile
memory
during
communication fail

Supports direct operate or select before operate (SBO) for control output

Supports report by exception for analog values Protocol frame monitor was built
in FRTU
IEC60870-5-101

Address size is configurable.

Two time tag formats are selectable. :24-bit or 56-bit

Single character for NACK is supported.

Cyclic update of measurements data.

Class assignable for each object type. ( single point, double points, measured
point, Set Points Command)

Supports report by exception for updating analog values
IEC60870-5-104

IEC 60870-5-104 (also known as IEC 870-5-104) is an international standard,
released in 2000 by the IEC (International Electro technical Commission). As can
be seen from the standard's full designation 'Network access for IEC 60870-5-101
using standard transport profiles', its application layer is based on IEC 60870-5101. IEC 60870-5-104 enables communication between control station and
substation via a standard TCP/IP network. The TCP protocol is used for
connection-oriented secure data transmission.
18
Load Break Switch Control
RT-200P
Communication
DNP, IEC60870-5-101, IEC60870-5Protocol Setting
Protocol Select
104, DNP/TCP
Default : DNP
Comm. Speed
Modem Control
TCP Control
SNTP
IEC Parameter
Default : 9600pbs
Comm Line
2Wire/4Wire / Default : 2Wire
RTS Off Delay
10 ~ 500ms / Default : 10 ms
CTS Time Out
1 ~ 255sec / default : 1 sec
DCD Time Out
100 ~ 30,000ms / Default : 100 ms
IP Setting
Default : 192.168.010.009
Subnet Mask
Default : 255.255.255.0
Gate Way
Default : 192.168.10.1
LAN Port Set
1-65534 / Default : 2404
LAN Card Select
1 ~ 2 Port / Default : 1 Port
SNTP Use
No Use / Use / Default : Use
SNTP IP
Default : 192.168.010.010
UDP Port
1-65534 / Default : 123
UTC Mode
UTC / Local / Default : UTC
UTC Hour
-12 ~ 13h / Default : 0h
UTC Min
0 ~ 59 min / Default : 0min
Cyclic Time
1 ~ 24 h / Default : 24h
D/L Retry
0~2 / default : 0
D/L Time Out
0 ~ 255 / default : 10s
Yes-No-Sometime /
D/L Confirm
DNP Parameter
1200/2400/4800/9600/19200
default : Sometime
A/L retry
0 ~ 2 / default : 0
A/L Time Out
0 ~ 255 sec / default : 15 sec
InitUnsol
Yes – No / default : No
Unsol Class1
Enable/Disable / default : Disable
Unsol Class2
Enable/Disable / default : Disable
Unsol Class3
Enable/Disable / default : Disable
Unsol Delay
0 ~ 60 sec / default : 5 sec
SBO Time Out
1 ~ 255 sec / default: 15 sec
Master Address
0 ~ 65534 / default : 3
Slave Address
0 ~ 65534 / Default : 4
Frame Interval
100 ~ 5,000 ms / default : 100 ms
A/L Cycle PRD
0 ~ 60 / default : 1 sec
SBO TimeOut
1 ~ 255 / default : 15 sec
M_SP Cyclic
Enable/Disable / Default : Enable
19
Load Break Switch Control
RT-200P
IEC101
M_DP Cyclic
Enable/Disable / Default : Enable
M_ME Cyclic
Enable/Disable / Default : Enable
M_SP Address
1-10000 / default : 100
C_SC Address
1-10000 / default : 200
M_DP Address
1-10000 / default : 300
C_CD Address
1-10000 / default : 400
M_ME Address
1-10000 / default : 1000
C_SE Address
1-10000 / default : 2000
M_IT Address
1-10000 / default : 4000
LINK Address
1-254 / Default : 1
ASDU Address
1-254 / Default : 1
Originator
0-255 / Default : 1
LINK Address Size
1-2 / Default : 1
ASDU Address Size
1-2 / Default : 1
IOA Address Size
1-3 / Default : 1
COTA Address Size
0-2 / Default : 2
Unbalance/Balance
Link Mode
/ Default: Unbalance
None/cp24/cp56
Time Marker
/ Default : None
T0 Off PRD
1 ~ 255 / default : 30 sec
T1 Ack PRD
1 ~ 255 / default : 15 sec
T2 S frame PRD
1 ~ 255 / default : 10 sec
T3 Test PRD
1 ~ 255 / default : 20 sec
Set S/W Counter
S/W Count
0 ~ 65535 / default : 0
Clear Events
All Events are cleared
Yes / No
Clear Fault
All Faults are cleared
Yes / No
Setting Time
yy-mm-dd-hh-mm-ss
Setting Pass Word
****
In Voltage
3,800-30,000V
IEC104
Event
Time
Time Set
Pass Word
Pass Word Se
Volt Calib
Volt. Adjust
20
Load Break Switch Control
RT-200P
2.10.
Event Record
2.10.1.
Event Record
The event recorder feature allows the time tagging of any change of state (Event) in the relay. As an event
occurs, the actual event condition is logged as a record along with a time and date stamp to a resolution
of 1 millisecond. There is capacity for a maximum of
1500 event records that can be stored in the relay
and when the event buffer is full any new record will over-write the oldest.
All events can be uploaded over the data communications channel(s) and can be displayed in the ‘RManager’ SW package in chronological order, allowing the sequence of events to be viewed.
Events are also made available spontaneously to an Modbus RTU or DPN 3.0 compliant control system.
Event List
I/O Event
Description
Max
Status Change of binary Input / Output
➔ SW State
➔ Main Lock
125
➔ GAS Low
➔ Door State
F/I Event
Operated status of Fault Indication
➔ Fault count : a, b ,c, n, all
250
➔ Latest fault current, phase and time
System Event
Status Change of System
➔ System Reset
➔ Set Change
125
➔ Communication Error
➔ AC Loss
Control Event
Controlled status of RT-200P
➔ SW Control
➔ Control
125
➔ Locked
➔ FI Reset
➔ Battery test
PQ Event
Power Quality
➔ Sag
125
➔ Swell
➔ Interruption
Measure Event
Measure status of RT 200P
125 * 6
1) Average 15
Total : 750
2) Day Max
21
Load Break Switch Control
RT-200P
Waveform Event Record
Event List
Waveform
Description
•
Waveform Recording
Storage: 8 Fault Waveforms of 10 cycles.
Sampling ratio : 32 Sample/Cycle * 10 Cycles
Max 8 fault waveforms can be captured on non-volatile memory
22
Load Break Switch Control
RT-200P
3. Physical Description
The RT-200P includes the following major components:
⚫
Inclusion with a local communication port and LCD display/keypad.
⚫
CPU/System Controller Board
⚫
Process I/O board
⚫
Internal mounting brackets and battery
⚫
modem options
Figure 3-1. Dimension and Structure
23
Load Break Switch Control
RT-200P
4. Input/output Connector
RT-200P provides terminals (connector) to connect control and modem. The terminal arrangement is as
Bellows.
Figure 4.1 Connectors on the Side of RT-200P
24
Load Break Switch Control
RT-200P
The Load Break Switch is connected to the controller by the control cable. The cable plugs into
compatible ports at both the controller and underside of the switch.
4.1. Modem Power supply Input
-
Power supply connecter has RT-200P external modem
power supply terminal.
-
Modem power Fuse socket
-
DC 12V (Options)
4.2. Current Input
-
Current connecters with phase A and follows by B, C, N.
Aux1, Aux2 is spare Aux Port and not assign.
1
2
3
4
ZCT2
ZCT1
SPARE
SEF
5
6
7
8
IN
IC
IB
IA
4.3. Voltage Input
-
Voltage connector has source side 3 phases(A,B,C) and
load side 3 phases(R,S,T) as bellows;
1
2
3
4
5
VT
VS
VR
VC
VB
6
7
8
9
10
VA
V_COM
GND
24Vdc
4.4. Remote Communication Port
-
Modem communication port is D-SUB 9 pin male type
25
Load Break Switch Control
RT-200P
4.5. Digital Input /Output
•
Digital Input receives 2 status signals through insulated
electric contacts.
•
Digital Output has 2 output relays.
10
9
8
7
6
M. Lock
GAS LOW
52B
52A
DI_COM
5
4
3
2
1
M. Lock
GAS LOW
52B
52A
DI_COM
4.6. DOOR Port
-
DOOR OPEN SENSING PORT
4.7. AUX. DI/DO
-
Aux DI DO
14
13
12
11
10
9
8
DO4_2
DO3_2
DO2_2
DO1_2
DI_COM
DI3
DI4
7
6
5
4
3
2
1
DO4_1
DO3_1
DO2_1
DO1_1
DI_COM
DI1
DI2
4.8. Motor Output Port
-
MO+ / MO- : Motor connect
-> Motor operating Signals.
-
Fuse : 15A
12
11
10
9
MO+
MO+
MO-
MO-
6
5
4
3
MO+
MO+
MO-
MO-
4.9. Power
Supply
8
7
2
1
Input
(AC
Input)
-
Power supply connecter has RT-200P operation power
supply terminal.
26
Load Break Switch Control
RT-200P
4.10.
Battery Port
-
Battery charging output port.
-
DC 27V +/- terminal
-
Fuse socket
4.11.
-
Main Power Switch
Main Power Switch connection terminal
4.12.
-
( Fuse 15A)
ETHERNET Connector
10 / 100 Base-T
27
Load Break Switch Control
RT-200P
5. Operator Control Panel
5.1. Description
The Operator Control Panel is mounted inside the control Box on the equipment panel. The Control
Panel consists of a four-line Liquid Crystal Display (LCD) and keypad with switches and Light Emitting
Diodes (LEDs) which are used to select and monitor the functionality of the LBS.
On the front panel, there are LED’s indicating LBS’s status, function buttons and LED’s, control buttons
and LED’s, LCD buttons, and a RS232 port for maintenance.
Figure 5-1: Operator Control Panel
28
Load Break Switch Control
RT-200P
Number
Item
Description
(1) RUN: It indicates the operation status. In normal
operation, it flicker periodically. In system problem
1
case, it is lighting or turned off.
(2) ERROR:
Turn
on
with
Self-diagnosis
Error
&
Communication Trouble.
2
DISPLAY
Back-light LCD, 4 line with 40 characters per line.
(1) MENU:
Selects
the
MENU
required.
(2) UP: It is used to move the menu within a
3
group or to increase the setting point.
(3) DOWN: It is used to move the menu or to
decrease the changed value.
(4) ENTER: It is used to confirm selection function,
and restores original display.
(1) Fault A, B, C, N PHASE, SEF
(2) SYNC. FAILED
4
(3) REVERSE POWER
Indicates all the Fault detection settings currently in use
e.g. Fault Settings and Sectionalizing.
(1) AC POWER: Indicates the external AC power supply
status.
(2) HANDLE LOCKED: Turn on, when the HANDLE is
5
locked.
(3) GAS LOW : Turn on, when the GAS status is GAS low
(4) BATTERY LOW: Turn on, when the battery status is
low. (Discharged.)
Indicates the external Input status and check monitor.
Source side and load side live line status are indicated.
More than one phase voltage is higher than an Off Level
6
of Disconnect line/Open phase, it is Live line. And all 3
phases are less than that, it is Dead line. Operator shall
decide an operation.
(1) ENABLE:
7
(2) TRIP:
Indicates Section operation status.
Indicates Sectionalizing TRIP sequence
operation status. The LED is lit When the LBS is open.
29
Load Break Switch Control
RT-200P
8
RX/TX/RTS LED (Red) indicates the communication state
of RT-200P.
This button is used for INDICATOR LED Reset (LED Off).
9
INDICATOR LED represents all the LED’s related to
Protection, Reclosing, and Self-diagnosis Error
It takes keying to check battery and charging circuit.
10
When pressing the button and if AC power supply is
provided, charging circuit is disconnected and connects a
load resister to battery and check the charging circuit.
These buttons are used to locally control (Open / Close)
the LBS. Before local control command, check first if the
control position is Local.
CONTROL SELECT button is a
two-phase safety & confirmation check mechanism. To
11
manually and locally control the LBS, CONTROL SELECT
button
should
be
pushed
down
to
make
the
corresponding LED on, and this CONTROL SELECT
function can be expanded to the scheme of Multiple LBS
Control in the future.
Control Lock Button Enables or disables the LBS
12
operation. If Control Lock LED is on, LBS operation and
Sectionalizing will be prohibited.
To decide the control position to Remote, push this button
and make the LED on. This button and LED are also
13
toggled between Remote and Local. But, the manipulation
of this button is possible only in the local for operator’s
safety.
14
Check first if the control position is CONTROL SELECT
button/LED ON
Manual open control opens the LBS and makes the Switch
locked out to open.
Check first if the control position is SELECT button/LED ON
15
Push CLOSE button to control the LBS manually to be
closed.
16
User mapping for using group setting with user setting key
30
Load Break Switch Control
RT-200P
RS-232C PORT
17
RT-200 is an advanced personal computer based software
package to allow off-line and on-line monitoring and
control of a LBS via RS232 port.
31
Load Break Switch Control
RT-200P
5.2. Construction
The Operator Control Panel consists of following parts:
⚫
Operation
⚫
Menu Control
⚫
Other Control
⚫
Fault Indication
⚫
Line Status Indication
⚫
SECTION Status
⚫
System Status
⚫
AC/HANDLE LOCKED/GAS LOW/Battery Status
⚫
CONSOL Port
5.2.1. Operation
Figure: Operation selection
These buttons are used to locally control (Open / Close) the LBS.
Before local control command, check first if the control position is
Local(LED ON). CONTROL SELECT button is a two-phase safety &
CONTROL SELECT
confirmation check mechanism. To manually and locally control
the LBS, CONTROL SELECT button should be pushed down to
make the corresponding LED on, and this CONTROL SELECT
function can be expanded to the scheme of Multiple LBS Control
in the future.
Check first if the control position is CONTROL SELECT button/LED
ON
OPEN
Manual open control opens the LBS and makes the Switch locked
out to open.
INDICATION LED
Switch status is indicated. Position LED is operated based on 52a
contact.
32
Load Break Switch Control
RT-200P
5.2.2. Menu Control
20 × 4 character LCD which has back-light support, is used
for a user to operate conveniently and to check operation
status clearly.
Control button
LCD Control button is composed of four basic keys (MENU, UP, DOWN, ENT). Following table is
explanation of the keys.
5.2.3. Other Control
RESET Button
Normal: Press the button to check all Lamps.
FI occurred: It resets FI Target by pressing the button.
To test the battery and charging circuit. When pressing the button
Battery TEST Button
and if AC power supply is provided, charging circuit is
disconnected and connects a load resister to battery and check
the charging circuit.
When LED is ON, Remote and Local operation are all available.
When LED is OFF, only Local operation is available.
Local Mode : In this mode only a local user can manually close
the LBS from the controller panel. This means a user can go to the
Remote CONTROL
control cubicle, set local control mode and know that remote
Button (Local/Remote)
closing is disabled. Only a local operator can operation when the
controller is in Local Mode.
Remote Mode : In this mode only a remote user can manually
close the LBS. Only a remote operator can operations when the
controller is in Remote Mode. If the local operator is denied a close
operation or a setting due to being in Remote Mode
Control Lock
Control Lock Select
Control Lock Status : LED ON
33
Load Break Switch Control
RT-200P
5.2.4. Fault Indication
In case of Permanent or Instantaneous fault, corresponding LED is ON. LED lamp can be off by
manually from local by pressing FI Reset button or from remote by sending a signal. Otherwise,
LED lamp will be on although H.V. line becomes normal.
5.2.5. Line Status Indication
Phase A,B,C Unbalance are indicated.
Under condition that source side and load side are all live line and
Phase Fault Indicator
switch is open status, check angles, if it meets then, it is OK,
LED
otherwise, it is unbalanced.
Although it is unbalanced, control is still available. Operator shall
decide an operation.
Source side and load side live line status are indicated.
More than one phase voltage is higher than an Off Level of
Phase Voltage Indicator
Disconnect line/Open phase, it is Live line. And all 3 phases are
(Live Line LED)
less than that, it is Dead line. Operator shall decide an operation.
When LED is ON, SEF is enabled. When LED is OFF, SEF is disabled.
SEF(Enable/Disable)
Although SEF is enabled, Protection is not enabled, SEF is not
activated.
When LED is on, T he phase angle difference between Source-
SYNC. FAILED LED
side voltage (Va) and Load-side voltage (Vr) is over the set value.
In this case, Close control command should be inhibited.
REVER POWER LED
In reverse current case, the REVER POWER lamp becomes On.
34
Load Break Switch Control
RT-200P
5.2.6. SECTION Status
Indicates present status of set section function process.
ENABLED
Indicates Section operation status.
Sectionalizer Indicates TRIP status.
TRIP
The LED is lit when the LBS is open.
5.2.7. System Status
RT-200P Diagnostic is displayed. RUN LED(Green) indicates that RT-200P
has passed the internal
diagnostic test and does not have any problem. RX/TX/RTS LED(Red) indicates the communication
state of RT-200P
It indicates the control electronics normally operation status. In
RUN
normal operation, In system problem case, it is lighting or turned
off.
ERROR
It indicates a fault condition.
RX : Turn on when transmit data
COMMUNICATION
TX : Turn on when transmit data
RTS : Turn on when RTS data
35
Load Break Switch Control
RT-200P
5.2.8. AC/HANDLE LOCKED/GAS LOW/Battery Status
The system power status of RT-200P is displayed. When RT-200P is supplying external power, AC
SUPPLY LED is on. HANDLE LOCKED LED shows the HANDLE LOECKED status of RT-200P and the
GAS LOW LED shows the GAS LOW status of RT-200p, the BATTERY lamp shows the battery status
of RT-200P.
AC POWER
Indicates the external AC power supply status.
Indicates the external HANDLE LOCKED status.
Mechanical locking of the LBS mechanism is provided by pulling
HANDLE LOCKED
downwards on the Manual Lock handle with a hook stick. When
locked, the mechanism cannot be tripped or closed either
mechanically or electrically.
GAS LOW
BATTERY LOW
Check that the gas low alarm is showing on the operator control
panel.
Turn on, when the battery status is Low.
5.2.9. CONSOL Port
This connection port is for the communication with administration program. It obtains setting
change, control and others events.
Engineering tool
RS-232 PORT
to
this
port
on
for
Notebook
computer
is
connected
maintenance. RS232C port for maintenance
is DB9 female-type connector.
Use the “null modem” cable for full-duplex (Modbus protocol)
communications when connecting a RT-200P to
a PC.
PIN
RS-232 Signal
5
GND
Power GND
2
RXD
Receive data input
3
TXD
Transmit data output
36
Description
Load Break Switch Control
RT-200P
5.3. Operation Manual (LCD instruction)
5.3.1. LCD Screen
20 × 4 character LCD which has back-light support, is used for a user to operate conveniently and to
check operation status clearly.
5.3.2. Control button
LCD Control button is composed of four basic keys (MENU, UP, DOWN, ENT). Following table is explanation
of the keys.
Button
Description
Move to menu selection mode from display mode and move to prior menu from
sub-menu. When press the button in Main Menu it is changed into display mode.
When this key is operated after changed the value, all changed value are reverted
to original setting value.
It is used for menu selection or setting change. In menu selection screen this
button is used for menu selection function. In setting change status moves to
menu mode by pressing this button
It is used to move the menu into above side or to increase the setting point. As
all menu has circulated function, from the top menu moves into the lowest menu.
In setting change case, after highest setting value comes the lowest setting value.
A level is increased by pressing the button and it is increased quickly by pressing
the button over 2 seconds.
It is used to move the menu or to decrease the changed value.
This button has circulated function for menu change/setting change as [increase]
button. A level is decreased by pressing the button and it is decreased quickly by
pressing the button over 2 seconds.
37
Load Break Switch Control
RT-200P
5.3.3. Menu structure tree
Figure. Menu Tree Structure
38
Load Break Switch Control
RT-200P
5.4. LCD Menu Use
5.4.1. Initial Screen
The main information of RT-200P is displayed in the initial screen, for the easy access and understanding
of the user.
To move to other initial screen, press [UP] [DOWN] button. Press [MENU] button in initial screen to move
to Main menu.
Initial Screen
1) Startup Screen
Indicate the Model/version status
2) Push the UP/DOWN button and display Time
status
3) Next UP/Down or Enter button to push,
Indicate the Current/Voltage of each phase
4) Push the MENU button to indicate the MENU
Function
39
Load Break Switch Control
RT-200P
5.4.2. Main Menu
In the initial menu, press [MENU] button, it is moved into Main menu. If press [MENU] button in main
menu, it is moved to the initial menu. Main menu has sub-menu as below.
Main Menu Screen
Main menu is composed of 4 submenus.
Push the submenu by using [UP][DOUN] button.
Move to the submenu by pressing [ENTER] button.
40
Load Break Switch Control
RT-200P
5.4.3. Setting Menu
Change of Phase Pickup Current of line operating element of Primary setting.
Setting Screen
1) Move to “MAIN MENU/ Function Setting/
Operate Set/ Phase Fault Set”.
2) Locate the cursor on Phase by using choose
[UP] [DOWN] key and then press the [ENTER]
button to change the set point.
3) Change in new setting point by using [UP]
[DOWN] button.
By pressing [ENTER] button, you can see the
changed phase setting point.
4)
To save the changed “New Set”, selected
YES/NO by using [UP][DOWN] and by pressing
[ENTER] button, you can changed new setting
value.
41
Load Break Switch Control
RT-200P
42
Load Break Switch Control
RT-200P
6. Fault Indication
The controller has many different detection features, described in this section. In summary it operates
as follows:
⚫
The fault Detection Elements are Phase, Earth, and Sensitive Earth Fault (SEF). Each individual
element can be programmed to log a fault detection depending on the relevant setting.
⚫
In addition to the Detection Settings there are Operator Settings. This group of settings is
Independent of the Detection Settings and it changes the main functionality of the Load
Break Switch.
The phase, earth and SEF fault detection elements are monitored with independent definite time
and fault current settings.
A pickup event is generated for each element if the current exceeds the fault current setting for that
element.
A pickup normally initiates a timer which runs for the definite time setting for that element.
When
this timer expires a fault is said to have occurred and is reported in the Event Log.
The current level at which the definite time timer starts can be modified by a multiplier in the case
of Cold Load Pickup Condition and definite time timer start is restrained in the case of Inrush
Condition.
When all pickups have reset, a peak current event is generated for each element that have picked
up.
A peak current event is a record of the maximum current measured between fault pickup and fault
reset.
6.1. Fault Indication
Distribution power system is usually Radial Network. Recloser controller or protection relay will
detect the failure of the line, and trip the circuit breaker or Recloser in a main point of power
system. The installation location of the LBS located between the protections switches. LBS is
resolved, the fault section and isolation from the fault section and the remaining sections of the
power system can be restored. Negative Phase Sequence detection is an additional over current
element and allows more reliable detection of certain types of faults.
RT-200P(FRTU) is the LBS controller, and rapid section isolation of fault line and restoration of
normal line by distribution automation system(DAS) which has the function of fault detection and
remote communication.
The following figure shows the fault detection and restoration of sequence. RT-200P(FRTU) is
detected the “failure” when the line voltage is dropped below the voltage Off-Level that the
measured the phase current, N-phase current over than the pickup set and maintains longer than
43
Load Break Switch Control
RT-200P
the corresponding detection time. Distribution automation system (DAS) may get the fault
indication from the LBS controller L1 ~ L5 and Recloser R failure be detected to know through
communication.
Recloser lockout after a fault section, DAS indicates the fault section and isolates it by sending
Open command to the controllers of LBS L3, L4. Wherein L5 is to supply power from the back of
a loop Tie breaker.
i)
A fault detected between L3 and L4
ii)
Tripped Recloser(R1) in the line and L2,L3 indicate fault at the time
iii)
DAS decided the fault section and opened L3,L4, then closed R1, L5
L5 may be energized from the loop tie switch backward
[Fig. 6-1 ] Fault detection &restoration sequence
At the temporary fault, distribution lines are restored automatically by a reclosing. The fault
indication of RT-200P(FRTU) can be reset by push button on the front panel or by remote reset
command. Also, it can be reset automatically when the line is energized.
44
Load Break Switch Control
RT-200P
[Fig. 6-2 ] Fault Indication
FI PickUp
OR
PickUp Level
Setting
-
IA
+
-
IB
+
-
IC
+
[Fig. 6-3] FI Pickup Scheme
Fault detection of the state change is saved in the event buffer. And fault current is also attached
to the each time tag is saved in the buffer. Fault waveforms data can be stored up to eight and
per phase current, voltage samples which stored 10 cycles, 32 samples/cycle.
FI PickUp
FI Fault
V
+
-
V Low Level
[Fig. 6-4] FI Fault Scheme
Direction Detection
Direction detection is to restrict fault indication only on faults to a designated side of the LBS. By
using this function, the fault indication can respond only to fault currents from main source, not
from dispersed sources in consumer area of the distribution line. As a result, the faulted section in
45
Load Break Switch Control
RT-200P
the line can be discriminated precisely.
[Fig. 6-5] Angular relationship between sequence voltage and current
46
Load Break Switch Control
RT-200P
6.2. Cold load PickUp
Cold load pickup is the phenomenon that takes place when a distribution circuit is reenergized
following an extended outage of that circuit. This is called Cold Load and Cold Load Pickup function
is to prevent and distinguish Cold Load from the real fault current.
Cold load mode, the fault detection, pickup level is changed by the times of Cold load Multiplier
(1~10) and this is in the instantaneous element. . If the transient current goes down and retains
below the pickup level within Cold Load Duration, then the normal sequence mode is restored. This
setting phase fault and earth fault detection function is applied to. Cold Load Multiplier set to ‘0’,
the function is disable to the Cold Load Pickup.
I
+
Time
-
CPLD Setting
PickUp Level
FI Fault
CLP
(Cold Load PickUp)
[Fig. 6-6] Cold Load Pickup Scheme
[Fig. 6-7] FI Pickup Scheme
6.3. Operation of Inrush
When closing onto a typical load there is always a short lived inrush current caused by, for example,
transformer magnetization currents, low resistance lamp filaments and motors starting. Inrush
Restraint inhibits fault detection when inrush current occurs.
Inrush restraint works by raising the phase and earth Threshold Currents for a short period of time
to allow the inrush to flow.
The inrush time and multiplier settings are specified on:
47
Load Break Switch Control
RT-200P
2nd
Filter
Fundamental
Filter
divide
Level Set
+
-
I
+
Run FI Inrush
-
FI Pickup
set
OCR Inst.
[Fig. 6-8] Inrush Restraint Scheme
6.4. SEF (Sensitive Earth Fault) Detection
On the non-grounded network, it is hard to detect fault current because ground current of nongrounded network is so small. Therefore, FTU-P200 is designed to measure zero-sequence values
from either external core Balanced Current Transformer (or ZCT) or Residual Connection of 3 Phase
Current Transformers to detect earth fault in the non-grounded network. This function is generally
called SEF detection.
In case of earth fault in the non-grounded network, since very small fault current due to line
capacitance component flows into the fault point from both sides, SEF detection also considers the
fault direction even in the radial network. Maximum Torque Angle is for setting the phase difference
between zero-sequence voltage and zero-sequence current, and the protection zone is between 90° and +90° on the basis of Maximum Torque Angle. And it can be used for alarm.
[Fig. 6-9] Phase diagram of SEF
6.5. Role of the Sectionalizer(Auto Sectionalizing)
The Load Break Switch (LBS) is equipped with automatic sectionalizing logic. The sectionalizing logic
opens the LBS during the dead time of an upstream Recloser after it has tripped and closed a
number of times as configured by the user.
It’s the function to open LBS and disconnect the faulty section from the distribution Feeder
automatically before the Recloser or reclosing relay of CB lockouts. The condition to open
48
Load Break Switch Control
RT-200P
automatically is the fault count. FTU detects and counts the fault and opens LBS if the count reaches
the setting value. The default count setting is two. It means that FTU allows the 1st reclosing success
of the upstream Recloser or reclosing relay of CB without sectionalizing in case of temporary fault.
[Fig. 6-10] Typical time sequence of sectionalizing
Caution: Pay attention to the sectionalizer setting according to the Operation Open Time and Recloser
setting of Mechanism.
Sectionalizer works normally during Recloser Reclosing time
Incorrect example: Recloser Reclosing Time shorter than LBS operation time.
In this case, the LBS cuts off the fault current, which can cause a serious problem.
Note) After Sectionalizer Trip operation, FI Reset must be done for "close" operation.
49
Load Break Switch Control
RT-200P
6.6. Phase Loss Detection
It’s the definite time under-voltage function only when at least one phase has normal voltage. It has
hysteresis characteristics. Voltage On level, Off level, and Delay time settings are needed for this
function.
6.7. Phase Sync. Check
RT-200P monitors the phase angle difference between source and load side voltages of LBS. If the
angle difference is larger than the setting and maintains longer than the set time, an alarm is
generated. The alarm is useful to close LBS which is installed at the tie point of two feeders from
the separated substation. FTU doesn’t include the result of sync. Check in the close interlock
conditions. Be cautious of closing tie switch.
6.8. Sectionalizer Inhibit
In the basic FI operation, when no voltage is detected by the Recloser operation of the previous
stage in the current state above the pickup current, a fault indicator occurs.
When Inhibit is activated, the no-voltage condition is excluded and when the current exceeds the
pickup, the fault indicator is activated. At this time, the Fault Indicator condition turns off the
indicator after Auto FI Reset Time.
50
Load Break Switch Control
RT-200P
7. Operation Setting
7.1. Operation Setting
Select “Function Setting” in the main menu, and move to this menu by pressing ENTER.
“Operation Setting” menu has the following submenu.
7.1.1.
Phase Fault Setting
Range
Step
Def.
Unit
Min
Max
No
Yes
Pick Up Current
5
900
1
400
A
Detection Time
0.01
10.00
0.01
0.02
Sec
Inrush Restraint
No
Yes
Cold Load Pick Up
100
500
10
200
%
Cold Load Time
0.1
180.0
0.1
0.2
sec
Direction Detection
Off
On
On
Direction Voltage Pickup
5
85
10
1
%
Direction MTA
0
359
0
1
deg
Function Use
51
No
No
Load Break Switch Control
RT-200P
Phase Fault / Function use
Range
No Use / Use
Default
Use
Step
1) Set [Use/No Use] of direction Detection,
when occurs Phase fault.
2) Display the “New Set”
3) To save the changed “New Set”, selected
YES/NO by using [UP] [DOWN] and by
pressing [ENTER] button, you can changed
new setting value.
Phase Fault / Pick Up Current
Range
5 ~ 900
Default
400A
Step
1A
Set Pick Up Current Setting.
# Fault current detection assurance range is 50A
~ 13000A.
Phase Fault / Time
Range
0.01 ~ 10.00 sec
Default
0.02
Step
0.01
Set Detection time of Phase Fault element.
Phase Fault / Cold Load Pick UP
Range
100 ~ 500 %
Default
200 %
Step
10 %
Set Cold Load Pickup Multiplier.
Phase Fault / Cold Load Time
Range
0.1 ~ 180.0 sec
Default
0.2
52
Step
0.1 sec
Load Break Switch Control
RT-200P
Set Cold load Time
Phase Fault / Inrush Restraint
Range
Yes / No
Default
No
Step
Set [YES / No] of direction Detection, when occurs
Inrush Restraint.
Phase Fault / Direction Function use
Range
Yes / No
Default
No
Step
Set [YES / No] of direction Detection, when occurs
Inrush Restraint.
Phase Fault / Direction Reference Voltage
Range
5% ~ 85%
Default
10%
Range
0 ~ 359 deg
Default
0
Step
1%
Step
1 deg
Phase Fault / Direction MTA
7.1.2.
Ground Fault Setting
Range
53
Step
Def.
Unit
Load Break Switch Control
RT-200P
Min
Max
Function Use
No
Yes
Pick Up Current
5
900
1
200
A
Detection Time
0.01
10.00
0.01
0.02
sec
Inrush Restraint
No
Yes
Off
On
On
Direction Voltage Pickup
5
85
10
1
%
Direction MTA
0
359
0
1
deg
Direction Detection
No
No
Ground Fault / Function use
Range
No Use / Use
Default
Use
Step
Set [Use / No Use] of direction Detection, when
occurs Ground fault.
Ground Fault / Pick-up Current
Range
2 ~ 900 A
Default
200 A
Step
200 A
Set the Ground pickup Current.
# Fault current detection assurance range is 50A
~ 13000A.
Ground Fault / Detection Time
Range
Default
0.01 ~ 10.00 sec
0.02
Step
0.01
Set Detection time of Ground Fault element.
Ground Fault / Inrush Restraint
Range
Yes/No
Default
No
Step
Set [YES /No] of direction Detection, when occurs
Inrush Restraint.
54
Load Break Switch Control
RT-200P
Ground Fault / Direction Function use
Range
Yes / No
Default
No
Step
Set [YES / No] of direction Detection, when occurs
Inrush Restraint.
Ground Fault / Direction Reference Voltage
Range
Yes / No
Default
No
Range
0 ~ 359 deg
Default
0
Step
Ground Fault / Direction MTA
Step
1 deg
7.1.3. Inrush Detect Setting
2nd Harmonic Setting
Range
Step
Def.
Unit
Min
Max
Function Use
No
Yes
2nd Harmonic
5
50
1
20
%
Detection Time
0.02
10.00
0.01
0.02
sec
No
2nd Harmonic Set
Range
5 ~ 50 %
Default
20 %
Set 2nd harmonic.
55
Step
1%
Load Break Switch Control
RT-200P
Detection Time Set
Range
0.02 ~ 1.00 sec
Default
0.02
Step
0.02
Set Detection time of Inrush detect element.
Function use
Range
Default
Step
Set [Use / No Use] of direction Detection, when
occurs Inrush detect.
Inrush Time Setting
Range
Step
Def.
Unit
Min
Max
Inrush Time
0.1
180.0
0.1
0.2
sec
Multiple
100
1000
10
500
%
Function Use
No
Yes
No
Inrush Detect Set
Range
0.1 ~ 180.0 sec
Default
0.2
Step
0.1 sec
Step
10%
Inrush Detect
Inrush Multiply Set
Range
100 ~ 1000 %
Default
500%
Function use
56
Range
No Use / Use
Default
No Use
Step
Load Break Switch Control
RT-200P
Set [Use / No Use] of direction Detection, when
occurs Inrush detect.
7.1.4.
FI Reset Time Setting
Range
FI Reset Time
Min
Max
1
180
Step
Def.
Unit
1
20
S
Function use
Range
Default
1 ~ 180 s
20 s
Step
1s
The failure type is judged according to the voltage
state after the FI Reset time has elapsed.
7.1.5.
Line Open Setting
Open Line is detected by Under Voltage characteristics at unbalanced condition.
When the voltage on one or two phases drops below the ‘Volt OFF Level’ setting, the ‘Delay
Time’ starts running.
If the voltage on those phases stays below ‘Volt OFF Level’ setting until
the ‘Delay Time’ timer expires, the Loss of Phase will be detected.
If the voltage on detected phase rises to the ‘Volt ON Level’ setting, the Loss of Phase is
released immediately.
Range
Step
Def.
Unit
Min
Max
Function Use
No
Yes
On Voltage
50
90
1
80
%
Off Voltage
10
86
1
50
%
Detection Time
0.1
300.
0.1
0.4
sec
No
Line Open / Function use
Range
57
No Use / Use
Load Break Switch Control
RT-200P
Default
Use
Step
Set [Use / No Use] of direction Detection, when
occurs Line Open detect.
Line Open / Line on Voltage Set
Range
50 ~ 90 %
Default
50 %
Step
1%
Set the live Line On Voltage level.
Line Open / Line off Voltage Set
Range
10 ~ 75 %
Default
50 %
Step
1%
Set line Off Voltage level.
! Setting the Off level below 35% is not
recommended.
Line Open / Delay Time Set
Range
0.1
Default
0.4
~ 300.0 sec
Step
0.1 sec
Set Delay time of Line Open detect element.
7.1.6.
Sync. Check Setting
Range
Step
Def.
Unit
Min
Max
Phase difference
5
60
1
30
Dug
Detection Time
0.1
300.0
0.1
0.4
sec
Function Use
No
Yes
No
Sync. Check / Function use
Range
58
5 ~ 60 Deg
Load Break Switch Control
RT-200P
Default
30 Deg
Step
1 Deg
Set an alarm on the source side and load-side
voltage phase
Sync. Check / Function use
Range
0.1 ~ 300.0 sec
Default
0.4
Step
0.1 sec
Set Delay time of Line Sync. detect element
Sync. Check / Function use
Range
No Use / Use
Default
Use
Step
Set [Use / No Use] of direction Detection, when
occurs Sync. Check.
7.1.7.
Sectionalize Setting
The LBS can be configured as a sectionalizer that trips during the dead time of an upstream Reclosed after
a configurable number of supply interrupts.
Range
Step
Min
Max
Mode
VIT
VT
Fault Count
1
3
1
Reset Time
20
240
1
Function Use
No
Yes
Def.
Unit
VIT
2
Sec
No
Sectionalize / Mode Select
59
Range
VIT ~ VT
Default
VIT
Step
Load Break Switch Control
RT-200P
Select mode to detect operation as voltage or
current or voltage only
Sectionalize / Fault count Set
Range
1~3
Default
2
Step
1
The number of supply interrupts counted exceeds the
trip after setting at counter
Caution: Pay attention to the sectionbalizer setting
according to the Operation Open Time and Recloser
setting of Mechanism
Sectionalize / Reset Time Set
Range
20 ~ 240 sec
Default
30 sec
When
sectionalizing
Step
is
enabled,
1 sec
the
upstream
Recloser reclose time must exceed 20 ~ 240 seconds
to allow for the opening time of the LBS.
Sectionalize / Fault count Set
Range
No Use / Use
Default
No Use
Step
Set [Use / No Use] of direction Detection, when
occurs Sectionalizer.
7.1.8.
SEF Setting
Range
Step
Def.
Unit
Min
Max
I-Pick Up
2
20
1
5
A
V-Pick Up
10
80
1
30
V
Angle
0
90
1
90
Deg
Detection Time
0.1
300.0
0.1
0.1
sec
60
Load Break Switch Control
RT-200P
Inrush Rest
No
Yes
No
Function Use
No
Yes
No
SEF / Pick-up Current Set
Range
2 ~ 20 A
Default
5A
Step
1A
Step
1V
Step
1 deg
Set Pickup current.
SEF / Pick-up Voltage Set
Range
10 ~ 80 V
Default
30 V
Set pickup voltage.
SEF / Angle Set
Range
0 ~ 90 deg
Default
0 deg
Set angle.
SEF / Detection Time Set
Range
0.1 ~ 300.0 sec
Default
0.1
Default
0.1 sec
Set Detection time of SEF element.
SEF / Inrush Restraint Set
Range
Yes / No
Default
No
Step
Set [YES /No] of direction Detection, when occurs
Inrush Restraint.
61
Load Break Switch Control
RT-200P
SEF / Function use
Range
No Use / Use
Default
No Use
Step
Set [Use / No Use] of direction Detection, when
occurs Ground fault.
7.1.9.
Under Frequency Setting
Range
Step
Def.
Unit
Min
Max
F-Pick Up
45.00
60.00
0.01
49.80
Hz
V-PickUp
50
85
1
80
%
Delay Time
0.1
20.0
0.1
1.0
Sec
Function Use
No
Yse
No
UFR / Pick-up Frequency Set
Range
45.00 ~ 60.00 Hz
Default
49.80Hz
Step
0.01Hz
Step
1%
Step
0.1 s
Set Pickup Frequency.
UFR / Pick-up Voltage Set
Range
50 ~85 %
Default
80 %
Set pickup voltage.
UFR / Delay Time Set
62
Range
0.1 20.0 sec
Default
1.0 s
Load Break Switch Control
RT-200P
Set Delay Time
UFR / Function use
Range
Yes / No
Default
No
Step
Set [Use / No Use] of direction Detection, when
occurs Ground fault.
7.1.10. Over Frequency Setting
Range
Step
Def.
Unit
Min
Max
F-Pick Up
50.00
70.00
0.01
62.20
Hz
V-PickUp
50
85
1
80
%
Delay Time
0.1
20.0
0.1
1.0
Sec
Function Use
No Use
Use
No Use
OFR / Pick-up Frequency Set
Range
50.00 ~ 70.00 Hz
Default
62.20Hz
Step
0.01Hz
Step
1%
Set Pickup Frequency.
OFR / Pick-up Voltage Set
Range
50 ~85 %
Default
80 %
Set pickup voltage.
OFR / Delay Time Set
63
Load Break Switch Control
RT-200P
Range
0.2 20.0 sec
Default
1.0 s
Step
0.1 s
Set Delay Time
OFR / Function use
Range
No Use / Use
Default
No Use
Step
Set [Use / No Use] of direction Detection, when
occurs Ground fault.
7.1.11. Under Voltage Setting
Range
Step
Def.
Unit
Min
Max
V-PickUp
50
90
1
80
%
Delay Time
0.1
20.0
0.1
1.0
Sec
Function Use
No Use
Use
No Use
UVR / Pick-up Voltage Set
Range
50 ~90 %
Default
80 %
Step
1%
Set pickup voltage.
UVR / Delay Time Set
Range
0.3
Default
1.0 s
- 20.0 sec
Set Delay Time
UVR / Function use
Range
64
No Use / Use
Step
0.1 s
Load Break Switch Control
RT-200P
Default
No Use
Step
Set [Use / No Use] of direction Detection, when
occurs Ground fault.
7.1.12. Over Voltage Setting
Range
Step
Def.
Unit
Min
Max
V-PickUp
110
150
1
120
%
Delay Time
0.1
20.0
0.1
1.0
Sec
Function Use
No Use
Use
No Use
OVR / Pick-up Voltage Set
Range
110 ~150 %
Default
120 %
Step
1%
Set pickup voltage.
OVR / Delay Time Set
Range
0.4
Default
1.0 s
- 20.0 sec
Step
0.1 s
Set Delay Time
OVR / Function use
Range
Default
No Use / Use
No Use
Step
Set [Use / No Use] of direction Detection, when
occurs Ground fault.
65
Load Break Switch Control
RT-200P
7.1.13. Inhibit Setting
OVR / Pick-up Voltage Set
Range
Default
Disable / Enable
Disable
Step
No-voltage detection condition setting in Fault
Indicator logic.
66
Load Break Switch Control
RT-200P
7.2. System Config Menu
Locate the cursor on “System Config” in the main menu, and move to this menu by pressing [ENTER].
System Config menu has the following submenu.
7.2.1.
Power Config
Locate the cursor on “1. Power config” in System Config menu and move to this menu by pressing [ENTER]
button. In this menu, various elements related to the system can be set. It has the following submenu.
Range
Step
Def.
Unit
10
50
Hz
Min
Max
50
60
System Type
3P4L
3P3L
Rated Voltage
3800
26000
100
13200
V
CT Ratio
100
2000
10
1000
A
NCT Ratio
100
2000
10
1000
A
CT Direction
FWD
REV
System Frequency
Ref Phase
Phase Rotation
3P4L
FWD
A/B/C
A
ABC / ACB
ABC
Power Config / 1. System Frequency Set
Range
50 / 60 Hz
Default
50 Hz
Step
Frequency setting. This value is used to set digital
sampling ratio.
67
Load Break Switch Control
RT-200P
Power Config / 2. System Type
Range
380 ~ 26,000 V
Default
26,000 V
Step
10 V
In Line system, rated voltage of power supply
system is set.
Power Config / 3. Rated Voltage Set
Range
380 ~ 26,000 V
Default
26,000 V
Step
10 V
In Line system, rated voltage of power supply
system is set.
Power Config / 4. CT Ratio Set
Range
100 ~ 2,000 A
Default
1,000 A
Step
10 A
Set the CT rate.
Power Config / 5. NC.T Ratio Set
Range
Default
100 ~ 2,000 A
1,000 A
Step
Set the NCT rate
Power Config / 6. C.T Direction Set
Range
Default
FWD / REV
FWD
Set the CT Direction
68
Step
10 A
Load Break Switch Control
RT-200P
Power Config / 7. Ref. Phase
Range
A/B/C
Default
A
Step
Setting the reference phase for the transposition
function
Power Config / 8. Phase Rotation
Range
ABC / ACB
Default
ABC
Step
Setting the phase Rotation for the transposition
function
7.2.2.
I/O Config
Range
Step
Def.
Unit
Min
Max
Pulse Set (OPEN)
1200
5000
1
1200
ms
Pulse Set (CLOSE)
1200
5000
1
1200
ms
DI Config
Aux Do Config
User S/W Set
Group Func Enable Set
I/O Config / 1. Pulse Set
Range
1,000 ~ 5,000 ms
Default
1,200
Step
1ms
ms
Set Motor Output Pulse Time.
Close or Open pulse width shall be set longer than
switch operating time.
69
Load Break Switch Control
RT-200P
I/O Config / 2. DI Config
Range
1 ~ 9999 ms
Default
20ms
Step
1 ms
The Minimum time for recognizing a status change.
To prevent a false operation due to chattering of the
input status.
I/O Config / 3. Aux. Do Config
Range
Default
Step
Selection of the output from the AUX DO conditions
ON
I/O Config / 4. User S/W Set
Range
Default
None
Step
Function Enable mapping for user setting switch
70
Load Break Switch Control
RT-200P
7.2.3.
Other Config
Range
Step
Def.
Unit
Min
Max
Manu
Auto
0
600
Interlock Live Load
No
Yes
No
Interlock Sync’ Fail
No
Yes
No
Open Inter Lock
No
Yes
No
Batt’ Test Time Set
0
100
Sag Function Use
No
Yes
Sag Level
10
90
1
90
%
Sag Detect time
0.5
10.0
0.1
2.0
cycle
Swell Function Use
No
Yes
Swell Level
101
150
1
%
%
Swell Detect time
0.5
10.0
0.1
2.0
cycle
Interruption Function Use
No
Yes
Interruption Level
10
49
1
20
%
Interruption Detect time
0.5
10.0
0.1
2.0
cycle
FI Reset Select
FI Clear Time
Manu
1
0
1
sec
24
h
No
No
No
Other Config / 1. FI Reset Set
Range
Manu / Auto
Default
Auto
Step
Auto Mode : FI reset automatically when voltage is
input after FI Set
Manu Mode : FI Reset button or communication FI
Reset command only FI reset
FI Clear Time : Clear the FI status at the set time after
determining the fault type.
FI Clear Time = 0 (FI CLEAR Function Disable)
Other Config / 2. InterLock Set
Range
Yes / No
Default
-
Step
Close Interlock
The following close interlock condition blocks the
switch to be closed manually or automatically if it’s
selected as “Yes”.
71
Load Break Switch Control
RT-200P
-
Open Interlock : Opened under rated load
(640A)
Other Config / 3. Battery Test Time
Range
0 ~ 100 h
Default
24h
Step
1h
Battery test function can be initiated automatically
through setting.
⚫
Power Quality
Menu to set parameters for detecting the short and long term voltage variations.
The alarm level and detection delay time of voltage sag, voltage swell, and outage can be set. The
distribution line’s rated voltage set at system parameter becomes the base of the alarm level for
voltage sag, voltage swell, and outage.
- Sag
A sag (also known as dip) is a reduction to between 30% and 95% in RMS voltage or current at the
power frequency for a short period of time from 0.5 to 10 cycles.
Voltage sags are widely recognized as among the most common and important aspects of power
quality problems affecting industrial and commercial customers. They are particularly troublesome.
Since they occur randomly and are difficult to predict.
Voltage sags are normally associated with system faults on the distribution system, sudden increase
in system loads, lightning strikes or starting of large load like induction motors. It is not possible to
eliminate faults on a system. One of the most common causes of faults occurring on high-voltage
transmission systems is a lightning strike. When there is a fault caused by a lightning strike, the
voltage can sag to 50% of the standard range and can last from four to seven cycles. Most loads will
be tripped off when encounter this type of voltage level.
Other Config / 4. Power Quality / 1. Sag Use
Range
No Use / Use
Default
No Use
Step
Set whether to use the function
72
Load Break Switch Control
RT-200P
Other Config / 4. Power Quality / 1. Sag Level
Range
30 ~ 95 %
Default
90%
Step
1%
Sag detection level
Other Config / 4. Power Quality / 1. Sag Detection Time Set
Range
0.5 ~ 10.0 cycle
Default
2.0
Step
0.1 cycle
Sag detection time setting
- Swell
A swell (also known as momentary overvoltage) is an increase in RMS Voltage to between 105% and 150%
for duration from 0.5 to 10 cycles. Swells are commonly caused by system conditions, switching off a large
load or energizing a large capacitor bank. A swell can occur during a single line-to-ground fault (SLGF)
with a temporary voltage rise on the unfaulted phases. They are not as common as voltage sags and are
characterized also by both the magnitude and duration. During a fault condition, the severity of a voltage
swell is very much dependent on the system impedance, location of the fault and grounding. The effect
of the type of disturbance would be hardware failure in the equipment due to overheating.
Other Config / 4. Power Quality / 2. Swell Use
Range
No Use / Use
Default
No Use
Step
Set whether to use the function
Other Config / 4. Power Quality / 2. Swell Level
Range
105 ~ 125 %
Default
120
Swell detection level
73
Step
1%
Load Break Switch Control
RT-200P
Other Config / 4. Power Quality / 3. Swell Detection Time Set
Range
0.5 ~ 10.0 Cycle
Default
2.0
Step
0.1 cycle
Swell detection time setting
– Interruption
An interruption occurs when there is a reduction of the supply voltage or load current to between
10% and 49% for duration from 0.5 to 10 cycles. Possible causes would be circuit breakers responding
to over load, lightning and faults. Interruption are the result of equipment failures, power system
faults and control malfunction. They are characterized by their duration as the voltage magnitude is
always less than 10% of the nominal. The duration of an interruption can be irregular when due to
equipment malfunction or loose connections. The duration of and interruption due to a fault on the
utility system is determined by the utility protective devices operating time.
Voltage interruption is a large decrease in RMS voltage to less than a small percentile of the nominal
voltage, or a complete loss of voltage.
Momentary interruptions can cause absolute voltage loss, and they are normally the result by utilities
to clear transient faults on systems. Sustained interruptions during over one minute are normally
caused by permanent faults or scheduled downtime
Other Config / 4. Power Quality / 3. Interruption Use
Range
No Use / Use
Default
No Use
Step
Set whether to use the function
Other Config / 4. Power Quality / 3. Interruption Level
Range
10 ~ 49 %
Default
20
Interruption detection level
74
Step
1%
Load Break Switch Control
RT-200P
Other Config / 4. Power Quality / 3. Interruption Detection Time Set
Range
0.5 ~ 10.0 Cycle
Default
2.0
Step
Interruption detection time setting
75
0.1 cycle
Load Break Switch Control
RT-200P
7.2.4.
Communication Config
Locate the cursor on “Communication” in System Config, move to this menu by pressing [ENTER] button.
In this menu, all elements related to the communication can be set and has the following submenu.
Communication Config / 1. Protocol Select
Range
DNP/IEC-101/ IEC-104 / DNP-TCP
Default
DNP
Step
Protocol selection Menu :
DNP3.0 / IEC-60870-101 / IEC-60870-104 / DNP-TCP
7.2.5.
Modem Control Setting
Communication Config/ 2. Modem Control /1. Comm. Speed Set
Range
1200,2400,4800,9600, 19200 bps
Default
9600 bps
Select the Baud Rate of Port
76
Step
Load Break Switch Control
RT-200P
Communication Config / 2. Modem Control / 2. Comm. Line
Range
2Wire / 4Wire
Default
2 Wire
Step
Modem Communication line setting.
Communication Config/ 2. Modem Control / 3. RTS Off Delay Set
Range
10 ~ 500 ms
Default
10 ms
Step
1 ms
RTS Off Delay Time set the delay time of RTS sign
that become Off after the data transmission.
It is time delay to prevent the liss if last data after
sending the data.
Communication Config/ 2. Modem Control / 4. CTS Timeout Set
Range
1 ~ 255 sec
Default
1 sec
Step
1 sec
Set a Waiting time that waits Modems confirmation
on RTS signal which informs that RT-200P is ready to
transfer a data.
CommunicationConfig/ 2. Modem Control / 5. DCD Timeout Set
Range
100 ~ 30,000 ms
Default
100 ms
Step
100 ms
Set a delay time of DCD signal timeout which
determine modem status before sending RTS signal
in 2 wire communication type.
7.2.6.
TCP Control
Communication Config / 3. TCP Control / 1. IP Setting
Range
Default
Step
When TCP / IP mode, set the IP address
77
Load Break Switch Control
RT-200P
Communication Config / 3. TCP Control / 2. Subnet Mask Setting
Range
Default
Step
When TCP / IP mode, set the Subnet Mask.
Communication Config / 3. TCP Control / 3. Gateway Setting
Range
Default
Step
When TCP / IP mode, set the GATEWAY address
Communication Config / 3. TCP Control / 4. LAN Port Setting
Range
1 ~ 65534
Default
2404
Step
1
When TCP / IP mode, set the LAN Port
Communication Config / 3. TCP Control / 5. LAN Card Select
Range
1 ~ 2 Port
Default
1
Step
1
LAN Card Port Setting
(2 Port Option)
7.2.7.
SNTP Control
Communication Config / 3. TCP Control / 6. SNTP Setting
Range
No Use / Use
Default
Step
When TCP / IP mode, set the IP address
*SNTP function is not supported for products before
October 20, 2020.
78
Load Break Switch Control
RT-200P
Communication Config / 3. TCP Control / 6. SNTP Setting
Range
Default
Step
Set time server IP address
Communication Config / 3. TCP Control / 6. SNTP Setting
Range
1 ~ 65534
Default
123
Step
1
Step
1
Time Server Port Settings
Communication Config / 3. TCP Control 6. SNTP Setting
Range
UTC / Local
Default
UTC
Select Change from UTC to Local time
Communication Config / 3. TCP Control 6. SNTP Setting
Range
-12 ~ 13 Hour
Default
0
Step
1
Change time from UTC to Local time
Communication Config / 3. TCP Control 6. SNTP Setting
Range
0 ~ 59 min
Default
0
Step
Change time from UTC to Local time
79
1
Load Break Switch Control
RT-200P
Communication Config / 3. TCP Control / 6. SNTP Setting
Range
0 ~ 24 h
Default
24h
Step
1h
Time synchronization interval setting
7.2.8.
DNP Parameter Setting
RT-200p can DNP3.0 communicate by using the communication port2. For more information refer
the “DNP3.0 Protocol Manual”.
Item
Range
Default
Step
0~2
0
1
D/L Timeout
0~255
0
1
D/L Confirm
Yes/ No/Sometimes
No
0~2
0
1
A/L Timeout
0~255
0
1
sec
Initial Unsolicited MSG
Yes/No
No
Unsolicited Class 1
Disable/Enable
Disable
Unsolicited Class 2
Disable/Enable
Disable
Unsolicited Class 3
Disable/Enable
Disable
Unsolicited Delay Time
0~60
0
1
sec
SBO Timeout
1~255
15
1
sec
Master Address set
0~65534
3
1
Slave Address Set
0~65534
4
1
Multi Frame Interval
10~500
10
1
D/L Retries
A/L Retries
Unit
sec
ms
Communication Config / 4. DNP Parameter / 1. D/L Retry Set
Range
Default
0~2
0
Step
1
Set the retry number of Data Link.
Communication Config / 4. DNP Parameter / 2. D/L Timeout Set
80
Range
0 ~ 255 sec
Default
0
Step
1 sec
Load Break Switch Control
RT-200P
Set the waiting time of Data Link Frame transmission
to the Data Link Confirm (ACK) receiving of the
master side. RT-200P resends the Data Link Frame,
when the Data Link Confirm has not received during
the setting time and it is possible to retry the Data
Link.
Communication Config / 4. DNP Parameter / 3. D/L Confirm Set
Range
Yes, No, Sometime
Default
No
Step
Choose whether Data Link Confirm is used or not.
NO : Data Link Confirm is not used.
YES : Data Link Confirm is used
Sometime :
When set the use of Data Link Confirm, check the
setting status of host and set same with the host. If
the setting status is different with the host can be
occur an communication error because of Data Link
Reset.
Communication Config / 4. DNP Parameter / 4. A/L Retry Set
Range
0~2
Default
0
Step
1
set the Retry of A/L Confirm(ACK) receiving from
Mast Application to Slave Application.
Communication Config / 4. DNP Parameter / 5. A/L Timeout Set
Range
0 ~ 255 sec
Default
0
Step
1 sec
In case that request Confirm during the data
transmission from Slave Application to Master
Application, set the maximum time of A/L Confirm
(ACK) receiving from Mast Application to Slave
Application.
Communication Config / 4. DNP Parameter / 6. Initial Unsol Set
Range
81
Yes, No
Load Break Switch Control
RT-200P
Default
No
Step
Select [YES/NO] of Initial Unsolicited Response Use
when Power Up.
YES : When Power Up, transmit the Initial Unsolicited
Response Message.
NO : When Power Up, do not transmit Initial
Unsolicited Response Message.
Communication Config / 4. DNP Parameter / 7. Unsol Delay Set
Range
0 ~ 60 sec
Default
0
Step
1 sec
Set the delay time of Unsolicited mode event
transmission to the master station. It is transmitted if
new event does not happen during this time.
Communication Config / 4. DNP Parameter / 8. SBO Timeout Set
Range
1 ~ 255 sec
Default
15
Step
1 sec
Set the time interval between Select Function and
Operate Function.
Communication Config / 4. DNP Parameter / 9. Master address Set
Range
Default
82
0 ~ 65534
0
Step
1
Load Break Switch Control
RT-200P
Enter the DNP address of Master station. RT-200P
refer this address when send Unsol message.
Communication Config / 4. DNP Parameter / 10. Slave Address Set
Range
0 ~ 65534
Default
999
Step
1
Set RTU Address ID.
CommunicationConfig/ 4. DNP Parameter / 11. Frame Interval Set
Range
10 ~ 500 ms
Default
10 ms
Step
1 ms
Frame Interval time Setting
7.2.9.
IEC Parameter Setting
Communication Config / 4. IEC Parameter / 1. A/L Cyclic Period Setting
Range
0 ~ 60 sec
Default
1
Step
1 sec
Setting the cycle time of the application layer
Communication Config / 4. IEC Parameter / 2. SBO Time Out Setting
Range
1-255 sec
Default
15
Step
1 sec
Set the time interval between Select Function and
Operate Function.
Communication Config / 4. IEC Parameter / 3. M_SP_Cyclic Setting
83
Load Break Switch Control
RT-200P
Range
Enable / Disable
Default
Disable
Step
When using IEC Protocol selection, Single Point
Cyclic data transmission setting.
Communication Config / 4. IEC Parameter / 4. M_DP_Cyclic Setting
Range
Enable / Disable
Default
Disable
Step
When using IEC Protocol selection,
Double Point Cyclic data transmission setting.
Communication Config / 4. IEC Parameter / 5. M_ME_Cyclic Setting
Range
Enable / Disable
Default
Disable
Step
When using IEC Protocol selection,
Measured value Cyclic data transmission setting.
Communication Config/ 4. IEC Parameter / 6. M_SP_Address Setting
Range
1-10000
Default
100
Step
Using IEC Protocol Single Point Base address setting.
Communication Config/ 4. IEC Parameter / 7. C_SC_Address Setting
Range
1-10000
Default
200
Step
Using IEC Protocol single command Base address
setting.
Communication Config/ 4. IEC Parameter / 8. M_DP_Address Setting
84
Range
1-10000
Default
300
Step
Load Break Switch Control
RT-200P
Using IEC Protocol Double Point Base address
setting.
Communication Config/ 4. IEC Parameter / 9. C_DC_Address Setting
Range
1-10000
Default
400
Step
Using IEC Protocol Double command Base address
setting.
Communication Config/ 4. IEC Parameter / 10. M_ME Address Setting
Range
1-10000
Default
1000
Step
Using IEC Protocol Measured value Base address
setting.
Communication Config/ 4. IEC Parameter / 11. C_SE_Address Setting
Range
1-10000
Default
2000
Step
Using IEC Protocol Set Point Command Base address
setting.
Communication Config/ 4. IEC Parameter / 12. M_IT_Address Setting
Range
1-10000
Default
4000
Step
Using IEC Protocol Integrated totals Base address
setting.
85
Load Break Switch Control
RT-200P
7.2.10. IEC 101 Parameter Setting
Communication Config / 5. IEC 101 Parameter / 1. LINK Address
Range
1 ~254
Default
1
Step
1
Set the link address of the IEC 60870-5-101 slave
station
The setting range varies depending on the Link size.
Re-confirmation after Link size is set.
Communication Config / 5. IEC 101 Parameter / 2. ASDU Address
Range
1 ~ 254
Default
1
Step
1
Set the ASDU(Application Service Data Units)
Address.
The setting range varies depending on the ASDU
size.
Re-confirmation after ASDU size is set.
Communication Config / 5. IEC 101 Parameter / 3. Originator Address
86
Range
0 ~ 254
Default
1
Step
1
Load Break Switch Control
RT-200P
Set the number of bytes for the application layer
“Information Object Address” field in an IEC
60870-5-101 message.
Communication Config / 5. IEC 101 Parameter / 4. LINK Address Size
Range
1~2
Default
1
Step
Data Link Address Size.
Set the number of bytes for "Link address" field in
an IEC60870-5-101 Protocol.
Communication Config / 5. IEC 101 Parameter / 5. ASDU Address Size
Range
1~2
Default
1
Step
ASDU Address Size
Set the number of bytes for the application layer
“ASDU Address” field in an IEC 60870-5-101
message.
Communication Config / 5. IEC 101 Parameter / 6. IOA Address Size
Range
1~3
Default
3
Step
Information Object Address Size
In IEC60870-5-104 IOA Address Size is Fixed 3.
Communication Config / 5. IEC 101 Parameter / 7. COT Address Size
Range
1~2
Default
2
Step
COT Address Size
In IEC60870-5-104 COT Address Size is Fixed 2.
Communication Config / 5. IEC 101 Parameter / 8. Link Mode Setting
87
Load Break Switch Control
RT-200P
Range
Unbalance / Balance
Default
Unbalance
Step
Set the Link mode in an IEC608705-101 Protocol.
RT-200P Control only supports unbalanced mode.
Communication Config / 5. IEC 101 Parameter /9. Time Marker
Range
None/ CP24/CP56
Default
CP56
Step
Time Type Setting of SP and DP Information in
IEC60870-5 101/104 Protocol
Communication Config / 5. IEC 101 Parameter /10. ME Data Type
Range
ME_NB_1 /
Default
ME_NB_1
ME_NC_1
Step
Measurement data transmission data type setting.
M_ME_NB_1 : Measured value, scaled value
M_ME_NC_1 : Measured value, short floating point
value
7.2.11. IEC 104 Parameter Setting
Communication Config / 7. IEC 104 Parameter
Range
Default
IEC60870-5-104
Step
protocol
setting
menu
following.
Communication Config / 7. IEC 101 Parameter / 1. T0 Off Line Poll Period
Range
1 ~255
Default
1
Step
1s
Network connection establishment timeout
Communication Config / 7. IEC 104 Parameter / 2. T1 Ack Period
88
is
as
Load Break Switch Control
RT-200P
Range
1 ~ 255
Default
1
Step
1s
Response timeout
Communication Config / 7. IEC 104 Parameter / 3. T2 S Frame Period
Range
1 ~ 255
Default
10
Step
1s
A S-format frame (ACKRSN) will be sent at the
latest after this time starting from the last received
telegram from the server.
Communication Config / 7. IEC 104 Parameter / 4. T3 Test Period
Range
1 ~ 255
Default
20
Step
1s
An U-format frame (TESTFR) will be sent at the
latest after this time starting from the last received
telegram from the server.
89
Load Break Switch Control
RT-200P
7.2.12. Event Clear
This menu Maintenance and data resets.
LBS Open Counter setting/reset (Maintenance) and Event data clear.
Item
Sub Item
Range
step
S/W Counter
0-65535
1
Clear Event
Clear all events
Yes/No
Clear Fault wave
Clear all Faults
Yes/No
Clear Counter
Clear all Fault Count
Yes/No
Clear Energy
Clear all Energy
Yes/No
Clear all PQ Counter
Yes/No
Set S/W Counter
Clear PQ Counter
7.2.13. Time
Set present date and time
Time Set
Range
Default
Step
Press [ENTER] button to select and change a setting.
To change a number, use [UP] [DOWN] button and
to move next item, press [ENTER] button.
To save all changed setting, press [ENTER].
7.2.14. Pass Word Setting
Time Set
Range
Default
90
Step
Load Break Switch Control
RT-200P
Press [ENTER] button to select and change a setting.
To change a number, use [UP] [DOWN] button and
to move next item, press [ENTER] button.
To save all changed setting, press [ENTER].
7.2.15. Voltage Adjust
Time Set
Range
Default
Step
Press [ENTER] button to select and change a setting.
To change a number, use [UP] [DOWN] button and
to move next item, press [ENTER] button.
To save all changed setting, press [ENTER].
91
Load Break Switch Control
RT-200P
8. Display Menu
The RT-200P provides extensive and accurate metering capabilities. See Specification part for metering
and power measurement accuracies.
[Fig. 8-1 ] Overview Display Menu
[Fig. 8-2] Overview Measurement Menu
Measurement Operator can monitor all kinds of measurement values such as current, voltage, sequence
value, power, etc. Real-time in I & V& Power measurement display. In this menu, indicate to measurement
values.
92
Load Break Switch Control
RT-200P
8.1. Monitoring and Metering
Display
Items
Currents
Displayed Values [unit]
Ia, Ib, Ic, In : RMS[A] & Phase Angle [Deg]
Va, Vb, Vc, Vr, Vs, Vt [kV]
Zero-sequence : VoS, VoL, (S: Source-side, L: Load-side)
Voltages
Positive-sequence : V1S, V1L
Negative-sequence : V2S, V2L
:Magnitude [A] & Phase Angle [Deg]
Measurements
Active Power
Pa, Pb, Pc, P3p [MW]
Reactive Power
Qa, Qb, Qc, Q3p [MVAR]
Apparent Power
Sa, Sb, Sc, S3p [MVA]
Power factor
PFa, PFb, PFc, PF3
Phase Difference
∠Va - ∠Vr
Phase Difference between A-phase and R [Deg]
Measure / 1. Current
Current View
Measure / 2. Voltage View
Voltage View
93
Load Break Switch Control
RT-200P
Measure / 3. Phase Difference
Phase Difference View
Measure / 4. Power
Power Meter View
Measure / 5. Energy
Energy View
Measure / 6. Demand
94
Load Break Switch Control
RT-200P
The average Power and daily maximum power
display
Measure / 7. THD
THD View
Measure / 8. Harmonic View
95
Load Break Switch Control
RT-200P
Current A,B,C,N
Voltage A,B,C,R,S,T
Harmonic ingredients
Measure / 9. Frequency
VA Frequency View
8.2. Status view
In status display, Switch and Gas Low, Handle Lock, AC Power, Battery health, Door Open, Local/Remote,
FRTU address, Master address, Firmware Version information - all the status indications are displayed.
96
Load Break Switch Control
RT-200P
Status
Switch
Displays main device status. - OPEN/CLOSE,TROUBLE
Gas Low
LBS gas pressure status is displayed. - NORMAL/LOW
Handle Lock
Manual lock status is displayed. - LOCK/UNLOCK
AC Power In
External Power supply status is displayed. - NORMAL/OFF
Battery Health
Battery status is displayed. - NORMAL/LOW
Discharger
Display circuit and battery charging status - NORMAL/LOW
Door Open
Door status is displayed. - OPEN/CLOSE
Local/Remote
Operation control select is displayed. - REMOTE/LOCAL
Control Lock
FRTU Control Lock Status
AUX. DI1.2.3.4
AUX. DI Status
Control Fail
Main Device operation fail.
Temper
RTU PCB Temperature
System Voltage
The voltage supplied by the system
Batter Test Voltage
Battery voltage during battery test
8.3. Counter view
This menu displays counter information. It shows restart, SW Open and fault count, Phase Fault.
Counter
Restart
RT-200P restart counter
S/W Open
LBS body open counter
97
Load Break Switch Control
RT-200P
All Fault
All faults detection counter
CH A,B,C,N Fault
Each Phase Fault Detection Counter
Number of occurrences of power quality for
PQ Count
each phase
8.4. Alarm View
This menu displays controller Fault detection.
Alarm View
Fault detection status for each phase.
Fault detection status latch for each phase, "FI Reset"
canceled.
Under Voltage Alarm View
Over Voltage Alarm View
Under Frequency / Over Frequency Alarm View
98
Load Break Switch Control
RT-200P
8.5. System Information
FRTU System Information or DNP 3.0 Slave Master Address.
99
Load Break Switch Control
RT-200P
9. Event (Event Log)
Event Reports and Events Recorder features simplify post-fault analysis and help improve your
understanding of both simple and complex protective scheme operations. These features also aid in testing
and troubleshooting relay settings and protection schemes.
Select “EVENT LIST” in the main menu, and move to this menu by pressing ENTER.
“EVENT LIST” menu has the following submenu.
[Main Lock ] 01/128
20XX/XX/XX XX:XX:XX
Status: Lock
[Fault : C ] 01/128
20XX/XX/XX XX:XX:XX
Ia :
A Ib :
A
Ic :
A In :
A
[Set Change ] 01/128
[EVENT LIST]
20XX/XX/XX XX:XX:XX
Sys Config
Local Pannel
>1.I/O event [ 0]
2.F/I event [ 0]
3.Sys event [ 0]
4.Control evnt[0]
5.Measure evnt[ 0]
[Batt Test
] 01/128
20XX/XX/XX XX:XX:XX
local pannel
[Average 15 ] 01/128
20XX/XX/XX XX:XX:XX
Qa :
A Qb :
A
Qc :
A TT :
A
When the status of the control electronics or LBS changes, events are generated which are recorded in an
Event Log for display to the operator.
Events are viewed on the Event Log pages and can also be up-loaded and viewed with the Control Operating System.
The event log display looks like this: Events are dated, time stamped to a 10ms resolution and displayed
in the order in which they occurred.
The DOWN key scrolls the display downward to show older events, the UP key scrolls the display upward
to show more recent events.
Event List
I/O Event
Description
Max
Status Change of binary Input / Output
➔ SW State
125
➔ Main Lock
F/I Event
Operated status of Fault Indication
➔ Fault count : a, b ,c, n, all
250
➔ Latest fault current, phase and time
System Event
Status Change of System
➔ Open / Close / Door / Handle Lock / GAS Low
100
125
Load Break Switch Control
RT-200P
/ Battery Low /etc
➔ System Reset
➔ AC Loss
➔ Door Status
➔ Batter Low
Control Event
Controlled status of RT_200P
➔ Battery test /
125
➔ SW Control (Open/Close)
Measure Event
➔ Pa/Pb/Pc/TT
Each 125
➔ Qa/Qb/Qc/TT
Total : 750
➔ Ia/Ib/Ic/TT
Power Quality
➔ Voltage Sag
➔ Voltage Swell
125
➔ Interruption
Event List
Waveform
Description
•
Waveform Recording
Storage : 8 Fault Waveforms of 10 cycles.
Sampling ratio : 32 Sample/Cycle * 10 Cycles
Max 8 fault waveforms can be captured on non-volatile memory
Evnet / 1. I/O Event
Event status change
Event / 2. F.I Event
Fault history Event
Event / 3. System Event
101
Load Break Switch Control
RT-200P
The overall state of the system such as history FRTU
changes to the system and self-test
Event / 4. Control Event
Control command history Event
Event / 5~10. Measure Event
The average power and the daily peak load event.
Average Current, Average Power, Average Reactive
Power
Day Max Current , Day Max Power, Day Max Reactive
Power
Event / 11. PQ Event
Display of PQ type, occurrence time, phase value, and
occurrence and holding time information
102
Download