Materials System Specification 15-SAMSS-502 20 May 2020 Medium Voltage Power Cable 5 kV through 35 kV Document Responsibility: Electrical Systems Designs and Automation Standards Committee Contents 1 Scope ..................................................................... 2 2 Conflicts and Deviations ......................................... 2 3 References ............................................................. 2 4 Field Experience..................................................... 3 5 General .................................................................. 3 6 Medium Voltage Power Cable per IEC 60502-2 ..... 4 7 Medium Voltage Power Cable per AEIC CS8 ........ 6 8 Other Requirements ............................................... 8 Revision Summary ...................................................... 10 Data Sheets ............................................................... 11 Previous Issue: 01 January 2018 Revised paragraphs are indicated in the right margin Contact: Bugshan, Jamal A. (bugshaja) on phone +966-13-8809650 Next Planned Update: 20 November 2022 Page 1 of 15 ©Saudi Aramco 2020. All rights reserved. Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV 1 Scope This specification defines the mandatory requirements for dielectric insulated power cables with rated voltages from 5 kV through 35 kV, 50 or 60 Hz. Submarine, submersible pump (down hole), portable, and motor lead cables are outside the scope of this specification. 2 3 Conflicts and Deviations 2.1 Any conflicts between this document and other applicable Mandatory Saudi Aramco Engineering Requirements (MSAERs) shall be addressed to the EK&RD Coordinator. 2.2 Any deviation from the requirements herein shall follow internal company procedure SAEP-302. 2.3 The designation “Commentary” is used to label a sub-paragraph that contains comments that are explanatory or advisory. These comments are not mandatory, except to the extent that they explain mandatory requirements contained in this SAMSS. References The following is a summary of all the documents which have been mentioned within this specification. The specific part(s) of these documents which are applicable have been identified throughout this specification. 3.1 Saudi Aramco References Saudi Aramco Engineering Procedure SAEP-302 Waiver of a Mandatory Saudi Aramco Engineering Requirement Saudi Aramco Inspection Requirements Form 175-150200 3.2 Medium Voltage Power Cable 5 kV through 35 kV Industry Codes and Standards American Society for Testing and Materials ASTM B8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium Hard, or Soft ASTM B496 Compact Round Concentric-Lay-Stranded Copper Conductors Saudi Aramco: Company General Use Page 2 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV Association of Edison Illuminating Companies AEIC CS8 Specification for Extruded Dielectric, Shielded Power Cables Rated 5 through 46 kV Insulated Cable Engineers Association ICEA S-94-649 Concentric Neutral Cables Rated 5,000 - 46,000 Volts ICEA S-97-682 Utility Shielded Power Cables Rated 5,000 - 46,000 Volts International Electrotechnical Commission IEC 60038 IEC Standard Voltages IEC 60228 Conductors of Insulated Cables IEC 60332-3-23 Test for Vertical Flame Spread of VerticallyMounted Bunched Wires or Cables - Category B IEC 60502-2 Power Cables with Extruded Insulation and their Accessories for Rated Voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) Underwriters Laboratories UL 1072 4 Standard for Medium Voltage Power Cable Field Experience Designs, materials and methods of construction used in cable shall have a minimum of 6 years of verifiable, proven field experience. (Local manufacturer is exempted). Vendor shall supply a User List indicating User company name, installation site, date of installation, and characteristics similar to cable quoted. 5 General Medium Voltage Power Cable shall be manufactured and tested in accordance with International Electrotechnical Commission (IEC) 60502-2, or in accordance with Association of Edison Illuminating Companies (AEIC) CS8, as specified in the purchase order or in the Saudi Aramco Materials System Specification (SAMSS) description, with additional requirements as outlined below: 5.1 Cable manufactured to IEC 60502-2 shall meet the requirements of Sections 6 and 8 below. 5.2 Cable manufactured to AEIC CS8 shall meet the requirements of Sections 7 and 8 below. Saudi Aramco: Company General Use Page 3 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV 5.3 6 Substitution of IEC cable with AEIC cable, if IEC cable is specified, and vice versa, is prohibited. Medium Voltage Power Cable per IEC 60502-2 Cable shall be manufactured and tested in accordance with IEC 60502-2, with the following additional requirements: 6.1 The conductors shall be of Class 2 annealed copper in accordance with IEC 60228, plain or metal coated as specified. Conductor sizes shall be standard metric IEC 60228 sizes. 6.2 Insulation material shall be crosslinked polyethylene (XLPE), Tree Retardant XLPE (TRXLPE) or ethylene propylene rubber (EPR), as specified. Thermoplastic insulating compounds are not acceptable. 6.3 The rated voltage, nominal insulation thickness (as defined in IEC 60502-2) and field (commissioning) test voltage of the cable shall be in accordance with Table 1. Table 1 I II III Buyer's System Voltage Nominal/Class kV Uo/U(Um) kV Nominal Insulation Thickness mm Above 2 up to 4.16/5 6/10 (12) 3.4 Above 4.16/5 up to 13.8/15 12/20 (24) 5.5 Above 13.8/15 up to 34.5/35 18/30 (36)* 9.0 Note: * IEC standard rated voltage; cable shall be similar to 18/30 (36) kV, but with 9.0 mm insulation thickness. IEC Definitions: Uo : rated phase to ground voltage for which the cable is designed U : rated phase to phase voltage for which the cable is designed Um : highest system voltage for which the cable may be used (IEC 60038) 6.4 Conductor and insulation screening is required for all cables. 6.5 Conductor shield shall be easily removable from the conductor (to be firmly bondable to the insulation XLPE), and shall consist of either a layer of extruded Saudi Aramco: Company General Use Page 4 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV semiconducting compound, or a layer of extruded semiconducting compound over a semiconducting tape. 6.6 The non-metallic part of the insulation screen (shield) shall consist of a layer of extruded semiconducting compound or extruded thermosetting compound. Semiconducting coatings (paints) are not allowed. The extruded compound shall be removable (strippable) tested in accordance with IEC 60502-2. 6.7 The extruded semiconducting conductor shield, the insulation, and the semiconducting insulation shield shall be applied by simultaneous triple extrusion. Steam curing is not acceptable for XLPE insulated cable. 6.8 The metallic part of the insulation screen (shield) shall consist of copper tape(s), and shall be applied separately over each of the semicon-shielded, insulated conductors. Copper tape shall be a minimum of 0.1 mm thickness, applied with a minimum of 10% overlap. 6.9 If a concentric neutral conductor is specified in the purchase order, it shall consist of copper wires with the specified cross section, and shall be plain or metal coated as specified. The concentric neutral conductor shall be under the outer jacket. The concentric neutral wires may serve as, and take the place of the copper tape screen (shield) specified in paragraph 6.8. Commentary Note 6.9: The manufacturer may elect to include a copper tape screen (shield) as a means to improve the flame retardant characteristics of the cable, and meet the requirements of paragraph 6.16. In this case, the manufacturer shall notify Saudi Aramco. 6.10 IEC 60228 Class 2, stranded copper ground conductor(s) shall be provided in the interstices of the cable, if specified in the purchase order. 6.11 Fillers (extruded material or non-hygroscopic fibers) shall be used in order to ensure the cable is compact and round in cross-section. 6.12 Metallic armor, when specified in the purchase order, shall be galvanized steel double tape armor, or galvanized steel wire armor. Exception: For single conductor cables, material shall be aluminum instead of steel. 6.13 All cables shall have a continuous overall outer nonmetallic oversheath (outer jacket). 6.14 The outer jacket (oversheath) shall be polyvinyl chloride (PVC), suitable for 90°C maximum rated conductor temperature. Saudi Aramco: Company General Use Page 5 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV 7 6.15 The outer jacket (oversheath) shall be sunlight resistant and oil resistant. 6.16 The cable shall meet the retardant test when specified in the purchase order as per IEC 60332-3-23, “Test for vertical flame spread of vertically-mounted bunched wires or cables – Category B.” This is a type/qualification test – see paragraph 8.5. 6.17 All routine and sample tests shall be according IEC-60502-2. Medium Voltage Power Cable per AEIC CS8 Cable shall be manufactured and tested in accordance with AEIC CS8 and ICEA S-97-682 (cable without concentric neutral), or in accordance with AEIC CS8 and ICEA S-94-649 (concentric neutral cable), in both cases with the following additional requirements: 7.1 Insulation material shall be XLPE or EPR, as specified. Thermoplastic insulating compounds are not acceptable. 7.2 The rated voltage, nominal insulation thickness and field (commissioning) test voltage of the cable shall be in accordance with Table 2. Table 2 I Buyer's System Voltage Nominal/Class kV II Rated Voltage kV III Insulation Level % IV Nominal * Insulation Thickness mm (mils) Above 2 up to 4.16/5 5 133 2.92 (115) Above 4.16/5 up to 13.8/15 15 133 5.59 (220) Above 13.8/15 up to 34.5/35 35 100 8.76 (345) Note: * ICEA S-94-649 and ICEA S-97-682 specify insulation thickness in terms of minimum and maximum values. 7.3 The conductors shall be ASTM B8 Class B concentric-lay-stranded annealed copper, or ASTM B496 compact round concentric-lay-stranded annealed copper, plain or metal coated as specified in the purchase order. 7.4 Conductor and insulation shields are required for all cables, except 5 kV rated cable type MC can be without insulation shield if specified. 7.5 Conductor shield shall be easily removable from the conductor, and shall consist of either a layer of extruded semiconducting compound, or a layer of extruded semiconducting compound over a semiconducting tape. Saudi Aramco: Company General Use Page 6 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV 7.6 The non-metallic part of the insulation shield shall consist of a layer of extruded semiconducting compound. Semiconducting coatings (paints) are not allowed. The extruded compound shall be removable (strippable); the tension required to remove 12.5 mm strips at room temperature shall not be less than 1.4 kg (3lbs) nor more than 11 kg (24 lbs), when the stripping test of ICEA S-94-649 or ICEA S-97-682 is performed. 7.7 The extruded semiconducting conductor shield, the insulation, and the semiconducting insulation shield shall be applied by simultaneous triple dry extrusion. Steam curing is not acceptable for XLPE insulated cable. 7.8 The metallic part of the insulation shield shall consist of copper tape(s), and shall be applied separately over each of the semicon-shielded, insulated conductors. Copper tape shall be a minimum of 0.1 mm thickness, applied with a minimum of 10% overlap. 7.9 If a concentric neutral conductor is specified in the purchase order (occasionally referred to by type URD or UD cable), it shall consist of copper wires with the specified cross section, and shall be plain or metal coated as specified. Applicable standards for cables with concentric neutral are ICEA S-94-649 and AEIC CS8. The concentric neutral conductor shall be under the outer jacket. The concentric neutral wires may serve as, and take the place of the copper tape screen (shield) specified in paragraph 7.8. Commentary Note 7.9: The manufacturer may elect to include a copper tape screen (shield) as a means to improve the flame retardant characteristics of the cable, and meet the requirements of paragraph 7.16. In this case, the manufacturer shall notify Saudi Aramco. 7.10 ASTM B8 Class B concentric-lay-stranded annealed copper, or ASTM B496 compact round concentric-lay-stranded annealed copper ground conductor(s) shall be provided in the interstices of the cable, if specified in the purchase order. 7.11 Fillers (extruded material or non-hygroscopic fibers) shall be used in order to ensure the cable is compact and round in cross-section. 7.12 Metallic cover, when specified in the purchase order, shall be corrugated impervious aluminum sheath, or galvanized steel interlocked tape. The cable shall be type MC (metal clad). Exception: Steel shall not be used for single conductor cables. 7.13 All cables shall have a continuous overall outer nonmetallic jacket. Saudi Aramco: Company General Use Page 7 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV 8 7.14 The outer jacket shall be PVC, suitable for 90°C maximum rated conductor temperature. 7.15 The outer jacket shall meet the sunlight resistance, and the oil resistance I or II requirements of UL 1072. This is a type/qualification test – see paragraph 8.5. A certificate from the manufacturer that the cable has been type tested by a third party and that it meets these UL tests is acceptable in lieu of formal UL listing or certification. 7.16 The cable shall meet the vertical tray flame test specified in UL 1072. This is a type/qualification test – see paragraph 8.5. A certificate from the manufacturer that the cable has been type tested by a third party and that it meets this UL test is acceptable in lieu of formal UL listing or certification. 7.17 In addition to the marking requirements of paragraph 8.2, the cable outer jacket shall have the following markings: i) Insulation thickness (preferably), or % insulation level. ii) TYPE MV-90, or, when applicable, TYPE MV-90 OR MC, or TYPE URD, or TYPE UD. iii) OIL RES I or OIL RES II. Other Requirements 8.1 Each phase of multi-conductor cables shall be permanently identified. 8.2 Cables shall be marked by embossing in English on the outer non-metallic jacket (oversheath) at intervals not exceeding 1 m with the following information: 1) 2) 3) 4) 5) 8.3 Rated voltage Insulating compound (XLPE, TRXLPE or EPR) Number, size and material (“COPPER” or “CU”) of conductors Manufacturer's name Year of manufacture Reels shall be made of steel, or, alternatively, shall be heavy duty wood reels. Reels shall be lagged with wood, and shall be marked with a steel engrave durable label securely attached to a flange of the reel and plainly stating Buyer's Purchase Order number, length of cable on reel, number, type and size of conductors, Gross weight of cable on reel , and voltage rating. All markings shall appear on both sides of the reel. Cable ends shall be sealed and capped. Saudi Aramco: Company General Use Page 8 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV 8.4 8.5 Water Protection Requirement, if the cable is buried under water table, sabkah area, outdoor onshore locations within one kilometer from the shoreline of the Arabian Gulf or outdoor onshore locations within three kilometers from the shoreline of the Red Sea shall be apply following; 8.4.1 Longitudinal water protection, in the form of semiconducting waterblocking swellable tapes applied under and over the metallic screen or concentric neutral. 8.4.2 One of the following shall be added to 8.4.1: 1) Longitudinal water protection for the conductors, in the form of synthetic super-absorbent polymer type water swellable tape or yarns, to prevent ingress of water along the conductor. 2) Tree- Retardant XLPE (TRXLPE) instead of XLPE insulation. 3) Radial water ingress protection, in the form of plastic coated laminated aluminum or copper tape immediately under the outer jacket and firmly bonded to it. Type/Qualification Tests The manufacturer shall provide a certificate from a third party testing agency acceptable to Saudi Aramco, proving that all type or qualification tests required by applicable IEC, ICEA and AEIC standards have been successfully completed (a) prior to the placement of the first order for the type of cable ordered, and (b) prior to the placement of the first order after any major change in manufacturing processes. The certificate shall be plant-specific and shall not be extended to other plants of the same manufacturer. 8.6 Inspection Inspection shall be in accordance with this specification and Form 175-150200. Saudi Aramco: Company General Use Page 9 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV Revision Summary 4 December 2012 20 November 2017 1 January 2018 20 May 2020 Revised the Next Planned Update.” Reaffirmed the contents of the document, and reissued with minor revision that includes deletion of few requirements related to installation of the cables and also specific requirements on where to apply water protection for the cable system. Major revision to incorporate various major comments generated during the workshop attended by standard stakeholders such as CSD, Power Systems Engineering Department, FPD, SAPMT and local manufacturers. The new revision will include following main items which are: allow AC or DC high-potential tests with applied voltage values as specified in the international standards lessons learned from mega projects and operating facilities were explored to identify areas of improvements. Editorial revision to modify Section 2 (Conflicts and Deviations). Editorial revision to extend the revision cycle from 3 years to 5 years. Saudi Aramco: Company General Use Page 10 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV Data Sheets Data Sheet - Power Conductor Item No Description Reference manufacturing standard Specified IEC 60502-2/ AEIC CS8 To be completed By Vendor _______________ 01 Power Conductor Size Units mm²/kcmil Specified _________ _______________ 02 Power Conductor Insulation Type (Either XLPE or EPR) - _________ _______________ 03 Number of Cores 1C/3C _________ _______________ 04 Rated Operating Voltage (U) KV _________ _______________ 05 Max. Continuous Voltage (Umax) KV _________ _______________ 06 Max. 15 min Overvoltage KV _________ _______________ 07 Frequency Hertz 60 08 Power Requirement KVA _________ 09 Load Power Factor (lagging) - _________ 10 Cable Ampacity at 90°C A _________ _______________ 11 Max Cont. Conductor Temperature C _________ _______________ 12 Max Short Circuit Temperature C _________ _______________ 13 Required Voltage Regulation % _________ 14 Design Load Factor % _________ 15 System Fault Current: Phase to Ground A _________ Three Phase Sym. A _________ Duration Cycles _________ _______________ 16 Cable Operating Temperature at Design Load °C _______________ 17 Min. Insulation Resistance Ohm/km _______________ Saudi Aramco: Company General Use Page 11 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV 18 Max. Conductor Impedance at 60 Hertz Ohm/km _______________ 19 D.C. Resistance at 20°C Ohm/km _______________ 20 A.C. Resistance at 90°C, 60 Hz Ohm/km _______________ 21 Lead Sheath 5 – 35 kV Cables Yes/No _______________ 22 Inductive Reactance at 60 Hz Ohm/km _______________ 23 Shunt Capacitance µF/km _______________ 24 Conductor Impedance Ohm/km _______________ 25 Zero Sequence Impedance at 60 Hz Ohm/km _______________ 26 Positive Sequence Impedance at 60 Hz Ohm/km _______________ 27 Charging Current A/km _______________ 28 Water Protection Yes/No _______________ Saudi Aramco: Company General Use Page 12 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV Data Sheet - Overall Cable Item No Description Units 29 Minimum Bending Radius mm _______________ a) With tension mm _______________ b) Without tension mm _______________ a) Minimum kN _______________ b) Maximum kN _______________ Recovery of Completed Cable kN _______________ 32 Minimum Design Tension kN _______________ 33 Max Bending Radius m _______________ 33 Cable Weight a) Net (Cable) kg/km _______________ b) Gross (Cable + Reel) kg _______________ 34 Approx. Diameter of Conductor mm _______________ 35 Cable Overall Diameter mm _______________ 36 Maximum Diameter over Splices mm _______________ 37 Nominal Insulation Thickness mm _______________ 38 Total Cable Length km 30 Specified To be completed By Vendor Ultimate Breaking Strength 31 Recommended Maximum Tensile Loading for Installation/ _________ 39 Armor type and thickness (double tape / wire armor) 40 Cable Shipment Type - _______________ _______________ _________ _______________ Additional technical information or features specified by the COMPANY ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------Saudi Aramco: Company General Use Page 13 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV Figure 1 - Cross Section of 3-core Cable (example) Figure 2 - Cross Section of 3-core Cable (example of additional water protection) Saudi Aramco: Company General Use Page 14 of 15 Saudi Aramco: Company General Use Document Responsibility: Electrical Systems Designs and Automation Standards Committee 15-SAMSS-502 Issue Date: 20 May 2020 Next Planned Update: 20 November 2022 Medium Voltage Power Cable 5 kV through 35 kV Figure 3 - Cross Section of 1-core Cable (example of additional water protection) Saudi Aramco: Company General Use Page 15 of 15 Saudi Aramco: Company General Use