Uploaded by akk_lam

s-8242-00 (1)

advertisement
Intake/Exhaust Systems
Waukesha gas engines
Exhaust System Installation Guidelines
Page 1 of 6
Exhaust System Installation Guidelines
EN: 157564-01
DATE: 3/15
Ref.
S
8242
Intake/Exhaust Systems
Waukesha gas engines
FLEX CONNECTION
EXHAUST SUPPORT
STRUCTURE
-CUSTOMER SUPPLIED(SEE NOTE 14)
VHP P9394 ENGINE
Page 2 of 6
Exhaust System Installation Guidelines
EN: 157564-01
DATE: 3/15
Ref.
S
8242
Intake/Exhaust Systems
Waukesha gas engines
1. Allow for thermal expansion of the exhaust pipe
beyond the Waukesha* flex. The Waukesha
exhaust flex (when supplied) will accommodate
engine thermal expansion but cannot tolerate
movement imposed by external thermal growth.
Insulated pipes will run hotter and consequently
expand more.
COEFFICIENT OF EXPANSION
Steel
0.00065 in/in/100°F
Stainless steel
0.00099 in/in/100°F
EXAMPLE: 10 ft. of steel pipe on a L7042G with
an exhaust temperature of 1060°F will expand
based on 60°F ambient. (0.00065 in/in/100°F) (10
ft) (12 in/ft) (1060°-60°/100 ) = .78 in.
2. Remember that a flex connection has “spring
constants” (lateral, axial, radial, torsional) that
should be considered when engineering the
exhaust system. Transmission of forces to the
engine exhaust system (engine exhaust flange)
must be nil. (Any specific load or bending moment
limits shown on an engine’s installation drawing
must not be exceeded.)
3. Design the exhaust system so it will not impose
torsional forces on the exhaust flex connection.
4. The exhaust flex connection should be designed
to allow for flexing caused by engine operation,
acceleration, deceleration, starting and stopping.
The Waukesha exhaust flex (when supplied) will
accommodate engine vibrations with a solidly
mounted unit, but cannot tolerate the additional
forces/displacement imposed by mounting on
spring isolators. Additional flex capabilities will be
required when the unit is mounted on isolators.
5. Consider expected life. Cyclic flexing can lead to
premature failure by causing fatigue breakage.
6. Utilize a combination of fixed supports, rollers and
flex connections to provide a well designed
exhaust system. See sketches for additional
concepts.
7. Provide water traps/drains to prevent exhaust
condensation and/or rain from reaching the
engine. This is especially true on long pipe runs.
Use rain caps where applicable. Slope piping
away from engine.
Page 3 of 6
Exhaust System Installation Guidelines
EN: 157564-01
DATE: 3/15
Ref.
S
8242
Intake/Exhaust Systems
Waukesha gas engines
AXIAL
RADIAL
8. The minimum requirements for the design of the
exhaust system should be to contain explosions
that could be encountered during the operation of
the engine. Waukesha recommends the use of
carbon steel schedule 20 pipe as a minimum.
Stainless steel schedule 10 pipe is preferred
because of its greater strength properties at
elevated temperatures. Waukesha does not
recommend using double walled piping or slip
joints on engine exhausts.
9. Utilize smooth transition to final pipe size when a
transition in size is required. Waukesha
recommends a diverging angle of 15 degrees for
low pressure drop (see sketches for straight and
elbowed transitions).
10. Engines with two exhaust outlets combined into
one (such as 12VAT25GL engine) must have a
symmetrical design up to and including the point of
convergence of the two exhaust streams to
produce proper flow and restriction balance.
Convergence angle from the center of symmetry
must not exceed 45 degrees. The outlet area of
the y-connection must be equal to or greater than
LATERAL
TORSIONAL
the sum of the two inlet areas.
11. Size piping and silencer so that exhaust system
back pressure, as measured at the engine outlet
flange, is less than that indicated in the
specifications page in the tech data book.
12. Provide clearance to permit use of a chain hoist
for removal of heavy components.
13. For other exhaust system parameters see chapter
seven, (Exhaust System) of the “Waukesha
Installation Manual” (Form 1091.
14. For the VHP P9394 Engine, the support structure
can be built – if required. Maximum load of 240 lbs
total (60 lbs per bracket) cannot be exceeded at
any time. This includes the weight of the support
structure, Engine supplied exhaust components
and thermal growth. Loads to be equalized
between brackets. Thermal growth must be
considered and to be in direction shown
Page 4 of 6
Exhaust System Installation Guidelines
EN: 157564-01
DATE: 3/15
Ref.
S
8242
Intake/Exhaust Systems
Waukesha gas engines
The dual outlets shown below violate the symmetry requirement or have a converging
angle which exceeds 45° potentially causing high or unbalanced restriction.
Page 5 of 6
Exhaust System Installation Guidelines
EN: 157564-01
DATE: 3/15
Ref.
S
8242
Intake/Exhaust Systems
Waukesha gas engines
*Trademark of INNIO. All other trademarks are the property of their respective owners.
Page 6 of 6
Exhaust System Installation Guidelines
EN: 157564-01
DATE: 3/15
Ref.
S
8242
Download