2022 2nd International Conference on Power Electronics & IoT Applications in Renewable Energy and its Control (PARC) | 978-1-6654-3215-3/22/$31.00 ©2022 IEEE | DOI: 10.1109/PARC52418.2022.9726546 2022 2nd International Conference on Power Electronics & IoT Applications in Renewable Energy and Its Control (PARC) GLA University, Mathura, India. Jan 21-22, 2022 Frequency Spectral Analysis of 6-Pulse LCC-HVDC in Single Conductor Ground Return Configuration Using FFT Ravi Shankar Tiwari Department of Electrical Engineering, GLA University, Mathura, UP-281406, India, e-mail: ravishankar.tiwari@gla.ac.in Om Hari Gupta Department of Electrical Engineering, National Institute of Technology Jamshedpur, JH-831014, India, e-mail: omhari.ee@nitjsr.ac.in which operated then have either been scrapped or upgraded to semiconductor converter technology[6]. Semiconductors devices have been in use since the 1970s and are still a growing technology because of the high switching capacity and ability to withstand high current rating. Examples are the diode, diac, triac, thyristors, MOS-controlled thyristors (MCTs) [10], insulated-gate bipolar transistors (IGBT), and integrated gatecommutated thyristors (IGCTs), etc. [7]. This paper looks critically into the two dominant HVDC converter technologies taking into consideration. In [8], explains the modeling control and design of a 12-pulse VSC-HVDC transmission system.The detailed modeling of ± 500 kV LCC-HVDC and simulation using PSCAD/EMTDC is performed in [9]. The model includes an AC system, AC/DC filters, converter transformers, smoothing reactors, and transmission line – appropriate for various studies in HVDC transmission systems. Abstract – HVDC is one of the viable options for electrical power transmission and integration of renewable energy into the existing grid. To make an economic, controlled and efficient exchange of power HVDC uses current source converter (CSC) and voltage source converter (VSC) technologies. The 6-pulse LCC is the basic building block of CSC. The realization of flexible power flow control, asynchronous interconnection, and higher line loading is possible only because of HVDC transmission using LCC or VSC. However, the use of LCC or VSC causes the injection of harmonics in both the AC and DC sides of the system. Thismay further lead to higher losses and complexity in operation. Therefore, it is important to analyze and eliminate the dominant frequency components generated. This work performs the spectral analysis of line parameters on both AC and DC sides of each rectifier station to detect the dominant harmonic component present using FFT. The test system was developed using 6-pulse LCC-HVDC at sending station and constant load inversion mode at receiving station. The length of the HVDC transmission line is 300 km having distributed parameters supplying power to the constant load at receiving end. The MATLAB/ Simulink environment is used to develop the test system and digitalized at the sampling interval of 43μs. The spectrum analysis of the HVDC system is performed due to various reasons such as fault analysis, small signal stability analysis and to figure out the oscillatory phenomenon generated in between wind firmsand HVDC systems. The widely popular signal processing tools are Wavelet transforms (WT), discrete Fourier transforms (DFT), Fast Fourier transform (FFT), Neural Network (NW), Support vector machines (SVM), and Machine learning, etc. Stockwell transforms and mathematical morphology are the other multiresolution and non-linear signal shape-based techniques. A synthetic signal is used to facilitate didactic analysis of various transforms in[10] with the sampling frequency of 128 samples frequency of 7.268 kHz.Reference [11] reveals that harmonicbased and FFT techniques are faster and providea detailed frequency spectrum than those transforms based on timefrequency and WL. In [12], realizes dominant frequencies in DC line parameters using FFT to implement the distance protection scheme in HVDC lines. Keywords: LCC-HVDC, VSC, FFT, Graetz circuit, IGBT I. INTRODUCTION HVDC transmission makes use ofpower electronic converters for changing AC supply to DC at the sending station and convertingback to AC at the receiving station[1], [2]. These converters usually have a two 6-pulse arrangement connected in series, forming a 12-pulse converter connected in a star-star, star-delta, to the AC networks. A DC capacitor, AC filters, and inductor and are also included in the converter circuitry. The two convertersstations are linked via submarine or overhead cables at the same location for back-to-back HVDC connection. Thecontinuous advancement in HVDC systems is associatedwithadvances in the design of efficient power electronics converters[3]. Here are the two prevailing methods used for AC to DC or vice versa conversion. These methods are voltage source converter (VSC) and Line commutated converter (LCC). These technologies are successful because of the development in power electronics devices [4], [5]. Previous to the LCC or VSC, there are several attempts executed for AC to DC or vice-versa conversion but was unsuccessful due to safety reasons. The discovery of mercury-arc valves gavetransitory success to this conversion which afterward became obsolete. The mercury-arc valve 978-1-6654-3215-3/22/$31.00 ©2022 IEEE Salauddin Ansari Department of Electrical Engineering, National Institute of Technology Jamshedpur, JH-831014, India, e-mail: 2019rsee006@nitjsr.ac.in II. TEST SYSTEM DESCRIPTION AND DESIGN The layout in Fig. 1 shows the interconnection of the test system. It is operating to supply 250 kV, 2 kA, 500 MW DC supply between the rectifier andinverter stations. The sending end rectifier station is fed through a 5000 MVA AC grid operating a line voltage of 315 kV. The transformer interfacing AC system to the converters is of 6000 MVA, 315/210 kV rating. The universal bridge rectifier based on 6-pulse LCC is designed for the AC to DC conversion. A diode for unidirectional supply together with a 24 kV Dc is used to 1 Authorized licensed use limited to: Staffordshire University. Downloaded on September 09,2023 at 14:58:17 UTC from IEEE Xplore. Restrictions apply. degree in electrical and the 3rd and 2nd valves are in conduction, the instantaneous output voltage is given as (2). model the inverter station of the HVDC transmission system. The two stations are connected via a 300 km overhead transmission line of distributed parameters. Smoothening reactors and AC filters are the integral parts of either station. AC filters serve the purpose ofeliminatingdominant harmonics as well as supplying reactive power at the converter stations. The smoothing rectors of 0.5 H to 0.2 H are connected at the terminal of DC lines. For, AC filters rated at 300 MVA, tuned for 5th and 7th harmonics connected before converter transformer. Converter Station 1 Ir, Vr Pole 1 Power system 1 Vdc Converter Station 2 Ii, Vi AC filters Vh 6-PULSE (GRAETZ CIRCUIT) CONVERTER TOPOLOGY AND HARMONICS ANALYSIS In eb Va Vdc Vb ec Vc Fig. 2. Converter transform with Graetz rectifier circuit The desired voltage and current ratings are achieved by properly selecting the number of valves connected in series or parallel combinations of valve strings. If “s” valve are connected in series in a string, “r” be the number of strings connected in parallel, and “q” valves are present in a commutation group than, the total valves are given by “qrs”. Thus, the converter average DC voltage is given as (1) Vd 0 sq S Vm .Sin S q D 60 ³ D (eb ec ).dZt 3 2 S VLLCosD (3) Vd 0 2 [1 (h 2 1)sin 2 D ]1/2 h 1 2 (4) 6 nS .I p (5) WhereIp is the peak current flowing through converter valves transformer primary windings.There are various signal processing tools available to analyzethe AC/DC system parameters. Wavelet is one of the techniquesthat give information related to harmonics contents of a non-stationary, non-periodic signal generated. It provides variable window sizes without the risk of time-frequency resolution. However,the Fourier transform givesrelatively poor timefrequency resolution. The wide data window of FFT provides fine frequency and mediocretime resolution. The FFT is suitable for developing protection schemes based on the THD, DC component, or magnitude of fundamental frequency components, etc. This does not require the fine frequency resolution and provides a certain degree of flexibility in the classification of different operational states[13], [14]. Lsr ea (2) The smoothing reactor maintains the ripple-free DC line current, thus free from harmonic contents during normal operation. However, the harmonic component present in alternating current circulating through the converter valves and transformer primary windingisgiven by (5). Fig. 2 shows the schematic diagram of the Graetz circuit producing a 6-pulse output voltage. The circuit is widely used as the basic building block of HVDC converters. It provides the most use of converter unit and transformer and maintainsthe low voltage across the valves not participating in conduction. This low voltage across non-conducting valves is equal to the peak inverse voltage which valve can withstand. 3 phase AC supply 6 2S AC filters Fig. 1. six-pulse LCC-HVDC Test System III. 2VL sin(Zt 600 ) The DC output voltage (Vdc) hasa ripple frequency of six times the fundamental. Fourier series analysis technique is used to extract the order of harmonic contents existing in (3) and it would be expressed as (4). P-G fault F1 eb ec The average DC output at the terminals of HVDC lines are givens as (3) Lsi Lsr A1 Vd To analyze the voltage and current signal It has been widely recognized that wavelet transform is agood technique to analyze the non-periodic and non-stationary signal, such as voltage and current with fault transient in the power system. It offers variable window sizes without the risk of compromising time-frequency resolution. On the other hand, Short Time Fourier Transform (STFT) is relatively not known as a favorable candidate due to its poor time-frequency resolution; wide window gives finer frequency resolution but mediocre time resolution, and vice versa. Even so, STFT can still be used, granted, a certain degree of compromise is allowed. A protection system does not need a highly precise measurement of harmonics to perform effectively. Hence, for STFT to be used for the application of fault detection, it is worth paying the price for sacrificing frequency resolution in exchange for better (1) The Graetzcircuit includes the six thyristors or IGBT valves strings arranged in bride type and a converter transformeris provided with a tapping arrangement for voltage control.The transformer primary windings are connected in star with neutral grounded fed from AC. However, secondary windings may eitherbe connected in star or delta with ungrounded neutral supplying AC power to the converter bridge. When the six valve strings are fired in a definite order produces a DC supply that hassixpulses per cycle of AC. For firing angle delays by α 2 Authorized licensed use limited to: Staffordshire University. Downloaded on September 09,2023 at 14:58:17 UTC from IEEE Xplore. Restrictions apply. response of various AC system parameters during steady-state, dynamic and transient operation states are shown in Fig. 6. time information, which is far more significant. The STFT in (4) is computed by taking the Discrete Time Fourier Transform (DTFT) of each windowed block and the process illustrated in Fig. 3 0.5 -0.5 0.45 0.55 0.6 0.65 (a) Time (s) alpha degree Vdr p.u. 0 -1 0.45 0.5 2 2 1 VdL Id 1 2 -0.5 1 0.9 0.5 α0 1 0 0.5 0.6 (a) Time (s) 0.65 1 0.55 0.6 (b) Time (s) 0.65 0.55 0.6 (d) Time (s) 0.65 150 100 50 -1 0.55 30 0.6 (c) Time (s) 0.65 0 20 Fig. 5. Response of (a) DC line current (Idc), (b) DC line voltage (Vdc), (c) rectifier terminal voltage and (d) firing angle α0, after fault clearance and due to the HVDC regulator action 10 0.3 0.4 (c) Time (s) 0.55 0 50 40 0 -1 2 0.3 0.4 (b) Time (s) 0.55 0.6 0.65 (d) Time (s) 50 0 0.45 0.55 0.6 0.65 (c) Time (s) Alpha (α) 0.5 0.5 100 1.5 Vdr 0.3 0.4 (a) Time (s) 0.55 0.6 0.65 (b) Time (s) Fig. 4. Close-in fault (F2), response of (a) DC line current (Idc), (b) DC line voltage (Vdc), (c) rectifier terminal voltage and (d) firing angle α0, at rectifier 1.1 0.8 0.2 0.5 150 1 0 VdL p.u. Idc , Pref p.u. 0 0.5 0.5 1 0.5 2 1 Vdr p.u. 0.5 0 0.45 A. DC-AC line parametric response during various operational states Case (a) - The steep rise in reference power from 250 MW (0.5 p.u.) to 375 MW (0.75 p.u.) causes the DC line current changes from 1 kA (0.5 p.u.) to 1.5 kA (0.75 p.u.). This is achieved by the action of the HVDC regulator, which reduces the firing angle (α) from 300 to 150 using PI control and current regulator. The response time of the current regulator is of the order of .1 s or 6 cycles of AC fundamental. -1 0.2 1 VdL p.u. SIMULATION RESULTS AND DISCUSSION The simulation results are obtained by taking the sampling interval of 43.4 μs. A dynamic response result of the test system is obtained by applying a step-change in DC line current at 0.3 s and a DC line fault is applied at 0.5 s. The response of current regulator time is plotted for each casesuch as a) step rise inreference power of 0.25p.u, and b) close-in short circuit fault in HVDC line[15], [16]. The results of the two cases are shown in Fig. 3 and Fig. 4, respectively 0 0.2 1.5 Idc , P r ef p.u. IV. 2 1.5 0 0.2 0.3 0.4 (d) Time (s) 0.5 2 Iabc p.u. Fig. 3. Response of (a) Dc line current (Idc), (b) DC line voltage (Vdc), (c) rectifier terminal voltage and (d) firing angle α0, at the rectifier Cases (b) - The short circuit close-in fault is simulated at 0.5 s and the fault persists for a duration of 50 ms. The response of DC line parameters during close-in fault is shown in Fig. 4. A close-in short circuit at the DC line leads to a rise in fault current up to 4 kA (2 p.u.) and a rise in Id up to 2.96 kA (1.48 p.u.) within 10 ms. The regulator action activated after 10 ms to limit the fault current up to the nominal value of 2 kA. After confirmation that the rise in current is due to fault current, the protection system leads to a rise in firing angle by 300 to 1650. Thus, the operational mode of the rectifier changed into inversion mode. The DC line transient energy started to feedback into the AC network to recover system normal operation. The response of the HVDC regulator along with other DC line parameters is shown in Fig. 5. Similarly, the 1 Change in Pref 0 -1 -2 0.2 Vabc p.u. 2 Inception of F2 HVDC Regulator action 0.3 Steady state Response 0.4 0.5 (a) Time (s) 0.6 0.7 0.3 0.4 0.5 (b) Time (s) 0.6 0.7 1 0 -1 -2 0.2 Fig. 6. AC side response during steady-state, dynamic, and transient conditions with (a) three-phase current (Iabc) (b) three-phase voltage (Vabc) 3 Authorized licensed use limited to: Staffordshire University. Downloaded on September 09,2023 at 14:58:17 UTC from IEEE Xplore. Restrictions apply. B. Frequency Spectral Analysis During Steady-state, Dynamic and Transient operation of HVDC system The magnitude of fundamental and harmonic components is expressed as the percentage of DC componentsthat exists. The FFT analysis uses the sampled data of two cycles with the fundamental frequency of 60 Hz. The maximum frequency is 2 kHz and the maximum frequency selected for THD computation is Nyquist. Fig. 7 represents the steady-state FFT of AC phase voltage measured on the rectifier side of the HVDC system. The fundamental signal magnitude is 14.6e-5 % of DC components (7.007e-05). Fig. 8, represents the FFT of AC line currents (Iabc) during steady-state operation. This analysis can effectively utilize to detect the operating mode of the HVDC link using local measurements of AC-DC sides. Similarly, the FFT analysis using AC line current during the dynamic operational state of the HVDC link is shown in Fig. 9. The FFT during the transient state of HVDC lines generated due to close-faults at sending end is plotted in Fig. 10 and Fig. 11. Fig. 10, shows the FFT of line current (Iabc), while Fig. 11, indicates phase voltages. Fig. 12, indicates the FFT analysis of DC line current during the transient operational state of the HVDC line. It indicates thatvarious high-frequency components exist and can be detected based on FFT magnitude. Thus, the magnitude of the fundamental frequency component, THD, and order of harmonics can be significantly utilized to indicate variousoperational states of the HVDC system. DC = 0.02024 , THD= 4220.90% 4000 3500 Mag (% of DC) 3000 2500 2000 1500 1000 500 0 200 400 600 800 1000 Frequency (Hz) 1200 1400 1600 1800 2000 Fig. 9. Magnitude versus frequency spectrum of AC side phase current Iabc during dynamic operation state (i.e. change in power demand) DC = 0.2041 , THD= 604.69% X = 60 Y = 545 Mag (% of DC) 500 400 300 200 100 0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 Frequency (Hz) Fig. 10. Magnitude versus frequency spectrum of AC side phase current (Iabc) during close in fault at rectifier terminals DC = 7.007e-05 , THD= 1469058.81% 16x105 0 x 105 DC = 0.0004209 , THD= 229882.82% 14 2 Mag (% of DC) Mag (% of DC) 12 10 8 6 4 1.5 1 0.5 2 0 0 0 200 400 600 800 1000 1200 Frequency (Hz) 1400 1600 1800 2000 200 400 600 800 1000 1200 Frequency (Hz) 1400 1600 1800 2000 Fig. 11. FFT of AC phase voltages (Vabc) during close-in fault at HVDC line at rectifier terminal Fig. 7. Magnitude versus frequency spectrum of AC side phase voltages Vabc during steady-state operation DC = 0.000171 , THD= 356589.53% x 105 0 DC = 0.04977 , THD= 1214.18% 600 500 3 Mag (% of DC) Mag (% of DC) 3.5 2.5 2 1.5 1 300 200 100 0.5 0 400 0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 Frequency (Hz) 0 200 400 600 800 1000 1200 Frequency (Hz) 1400 1600 1800 2000 Fig. 12. FFT of DC line current (Idc) during close-in fault at HVDC line near sending end Fig. 8. Magnitude versus frequency spectrum of AC side phase current Iabc during steady-state operation 4 Authorized licensed use limited to: Staffordshire University. Downloaded on September 09,2023 at 14:58:17 UTC from IEEE Xplore. Restrictions apply. V. CONCLUSION [5] The FFT analysis of LCC-HVDC line used for interconnecting remort thermal power plants and on-shore and off-shore wind generations are performed. The spectral analysis of AC and DC-side line parameters are performed using the data window of 2 cycles. The variation of line parameters along with the frequency spectrum are used to classified the operational state of the HVDC system.The magnitude of frequency spectrum obtained is expressed relative to the magnitude of the DC component present in the line parameters. Results indicate the strength of fundamental frequency components during both steady-state and dynamics operation is much compared to the transient state operational state. It is concluded that the FFT of AC and DC line currents are more suitable than that of line voltages for the classification of various operational states such as short circuit, change in load or normal operation. During dynamic and transient states, the magnitude of DC components in line currents rises significantly compared to steady-state. Thus, FFT analysis of AC line currents or DC line current or voltage and THD calculated can clearly distinguish the operation states of the HVDC system. [6] [7] [8] [9] [10] [11] [12] REFERENCES [1] [2] [3] [4] [13] O. E. Oni, I. E. Davidson, and K. N. I. Mbangula, “A review of LCCHVDC and VSC-HVDC technologies and applications,” in EEEIC 2016 - International Conference on Environment and Electrical Engineering, Aug. 2016, pp. 1–7, doi: 10.1109/EEEIC.2016.7555677. N. Flourentzou, V. G. Agelidis, and G. D. Demetriades, “VSC-based HVDC power transmission systems: An overview,” IEEE Transactions on Power Electronics, vol. 24, no. 3. pp. 592–602, 2009, doi: 10.1109/TPEL.2008.2008441. M. H. Okba, M. H. Saied, M. Z. Mostafa, and T. M. Abdel- Moneim, “High voltage direct current transmission - A Review, Part II - Converter technologies,” in 2012 IEEE Energytech, May 2012, pp. 1–7, doi: 10.1109/EnergyTech.2012.6304651. J. Xu et al., “A Coordinated Marginal Current Control Method for LCCHVDC,” IEEE Trans. Power Syst., vol. 34, no. 6, pp. 4569–4582, 2019, [14] [15] [16] doi: 10.1109/TPWRS.2019.2912865. R. L. Sellick and M. Åkerberg, “Comparison of HVDC Light (VSC) and HVDC Classic (LCC) Site Aspects, for a 500MW 400kV HVDC Transmission Scheme,” in 10th IET International Conference on AC and DC Power Transmission (ACDC 2012), 2012, vol. 2012, no. 610 CP, pp. 23–23, doi: 10.1049/cp.2012.1945. C.-K. Kim, V. K. Sood, G.-S. Jang, S.-J. Lim, and S.-J. Lee, “Development of HVDC Technology,” HVDC Transm., pp. 1–35, 2010, doi: 10.1002/9780470822975.ch1. S. Tamai, “High power converter technologies for saving and sustaining energy,” Proc. Int. Symp. Power Semicond. Devices ICs, pp. 12–18, 2014, doi: 10.1109/ISPSD.2014.6855964. K. R. Padiyar and N. Prabhu, “Modelling, control design and analysis of VSC based HVDC transmission systems,” 2004 Int. Conf. Power Syst. Technol. POWERCON 2004, vol. 1, no. November, pp. 774–779, 2004, doi: 10.1109/icpst.2004.1460096. P. Liu, R. Che, Y. Xu, and H. Zhang, “Detailed Modeling and Simulation of ± 500kV HVDC Transmission System Using PSCAD / EMTDC,” pp. 3–5, 2015. G. N. Lopes, V. A. Lacerda, J. C. de M. Vieira, and D. V. Coury, “Analysis of Signal Processing Techniques for High Impedance Fault Detection in Distribution Systems,” IEEE Trans. Power Deliv., vol. XX, no. c, 2020, doi: 10.1109/TPWRD.2020.3042734. A. Soheili and J. Sadeh, “A New High Impedance Fault Detection Scheme : Fourier Based Approach,” 2016. J. Suonan, J. Zhang, Z. Jiao, L. Yang, and G. Song, “Distance protection for HVDC transmission lines considering frequency-dependent parameters,” IEEE Trans. Power Deliv., vol. 28, no. 2, pp. 723–732, Apr. 2013, doi: 10.1109/TPWRD.2012.2232312. K. A. Saleh, A. Hooshyar, E. F. El-saadany, H. H. Zeineldin, and S. Member, “Protection of High-Voltage DC Grids Using Traveling-Wave Frequency Characteristics,” vol. 14, no. 3, pp. 4284–4295, 2020. J. Zheng, M. Wen, Y. Chen, and X. Shao, “A novel differential protection scheme for HVDC transmission lines,” Int. J. Electr. Power Energy Syst., vol. 94, pp. 171–178, 2018, doi: 10.1016/j.ijepes.2017.07.006. X. Liu, A. H. Osman, and O. P. Malik, “Hybrid traveling wave/boundary protection for bipolar HVDC line,” 2009 IEEE Power Energy Soc. Gen. Meet. PES ’09, vol. 24, no. 2, pp. 569–578, 2009, doi: 10.1109/PES.2009.5276029. P. Jafarian and M. Sanaye-Pasand, “A traveling-wave-based protection technique using wavelet/pca analysis,” IEEE Trans. Power Deliv., vol. 25, no. 2, pp. 588–599, 2010, doi: 10.1109/TPWRD.2009.2037819. 5 Authorized licensed use limited to: Staffordshire University. Downloaded on September 09,2023 at 14:58:17 UTC from IEEE Xplore. Restrictions apply.