Plus +™ ModelKoolKare EEAC325A Recovery/Recycling/Recharging Unit Model: EEAC325A Service Manual May, 2007 (Rev. C) EEAC325A Service Manual Trademark and Copyright Information All information contained or disclosed in this document is considered confidential and proprietary by Snap-on Tools Company. All manufacturing, use, reproduction, and sales rights are reserved by Snap-on Tools Company and the information contained herein shall not be used in whole or in part without the express written consent of Snap-on Tools Company. Trademark Acknowledgments Snap-on® is a registered trademark of Snap-on Technologies, Inc. (USA and Canada) KoolKare Plus +™ is a trademark of Snap-on Tools Company. (USA and Canada) Copyright Information KoolKare Plus +™ Service Manual ©2007 Snap-on Incorporated. All rights reserved. The information, specifications and illustrations in this manual are based on the latest information available at the time of printing. Snap-on reserves the right to make changes at any time without notice. Page 2 Effective 09/2007 Table of Contents EEAC325A Service Manual Table of Contents Safety Warnings ................................................................................................... 4 Section 1 — General Information ........................................................................ 5 Introduction ....................................................................................................................... 6 Product Views ................................................................................................................... 7 Operating Guidelines ....................................................................................................... 8 Unit Specifications ............................................................................................................ 10 Maintenance Schedule .................................................................................................... 11 Section 2 — Parts & Components ...................................................................... 13 External Parts .................................................................................................................... 14 Internal Parts ..................................................................................................................... 16 Component Assemblies .................................................................................................... 18 Plumbing Diagram & Parts List ....................................................................................... 25 Main Component Descriptions ......................................................................................... 26 Alphabetical Parts List ..................................................................................................... 28 Section 3 — Diagnostics ..................................................................................... 33 Functional Check .............................................................................................................. 34 12VDC Solenoid Test Procedure ...................................................................................... 37 Service Center Menu Options .......................................................................................... 38 Output Step Test ................................................................................................................ 39 Depressurizing the Unit .................................................................................................... 39 Troubleshooting ................................................................................................................ 40 Service Instructions and Calibration ............................................................................... 50 System Wiring ................................................................................................................... 67 Component Wiring ............................................................................................................ 68 Wiring Harnesses .............................................................................................................. 71 Component Identification ............................................................................................... 82 Component Application Chart ......................................................................................... 83 Flow Diagrams .................................................................................................................. 84 Section 4 — Service Bulletins ............................................................................. 93 Section 5 — Labor Rates ..................................................................................... 101 Section 6 — Product Warranty ............................................................................ 103 Effective 09/2007 Page 3 EEAC325A Service Manual Safety Warnings SAFETY WARNINGS It is extremely important to follow the instructions in this manual. DO NOT attach any hoses or accessories until prompted by the unit. Improper setup and failure of the unit will result. Use only SNAP-ON Designated Replacement Components when servicing your equipment. Refer to the operator’s manual or this service manual for correct replacement part number(s). Always wear eye protection and protective clothing when working with refrigerants. Refrigerant can cause injury. Read and follow all warnings in the operator’s manual and this service manual before operating the unit. When replacing components, make certain the new parts are connected exactly as your instruction sheet directs you to do. If an instruction sheet was not included, connect the replacement part just like the original. Mark or label wire and plumbing disconnections so replacing the new parts will confirm the previous configuration. Disconnect hoses and tubes with extreme caution as they may contain liquid refrigerant under pressure. Always disconnect the unit from the power source before making any repairs or replacements to the components. Risk of electrical shock! Avoid the use of extension cords because the extension cord may overheat. However, if you must use an extension cord, the cord must be No. 14 AWG minimum and should not exceed more than 25 feet in length. Always depressurize the machine before servicing or replacing any components. Pressurized tanks contain liquid refrigerant. Overfilling of the tank may cause violent explosion and possible injury or death. Do not recover refrigerants into a non-refillable storage container. Federal regulations require refrigerants to be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA. Be sure that the refrigerant level in the tank does not exceed 80% of the tank volume. Failure to monitor the level could result in excessive hydrostatic pressure, causing physical injury or death. If scale assembly and UL circuit are not calibrated, scale can overfill the tank, causing possible explosion and/or vehicle overcharge. Page 4 Warnings: Use this unit only with the specified refrigerants. Cross-contamination with other refrigerant types will cause severe damage to the A/C system and to service tools and equipment. Do not mix refrigerant types through a system or in the same container! Avoid breathing A/C refrigerant and lubricant vapor or mist. Exposure may irritate eyes, nose, and throat. When removing R-134a from the A/C system, use service equipment certified to meet the requirements of SAE J2210 (R-134a recycling equipment). If accidental system discharge occurs, ventilate work area before resuming service. Make sure there is adequate ventilation in the vehicle servicing area. Keep hands away from moving parts. HFC-134a service equipment or vehicle A/C systems should not be pressure tested or leak tested with compressed air. Some mixtures of air/HFC-134a have been shown to be combustible at elevated pressures. These mixtures are potentially dangerous and may result in fire or explosion causing injury or property damage. Additional health and safety information may be obtained from refrigerant and lubricant manufacturers. Effective 09/2007 General Information EEAC325A Service Manual Section 1 - General Information Introduction .......................................................................................................... 6 Automatic Functions of the EEAC325A ............................................................................ 6 Additional Features of the EEAC325A ............................................................................. 6 Product Views ...................................................................................................... 7 Front View ......................................................................................................................... 7 Rear View .......................................................................................................................... 7 Operating Guidelines ........................................................................................... 8 Using the Control Panel ................................................................................................... 8 Setup Menu ....................................................................................................................... 9 Unit Specifications ............................................................................................... 10 Maintenance Schedule ........................................................................................ 11 Effective 09/2007 Page 5 EEAC325A Service Manual General Information INTRODUCTION The Snap-on KoolKare Plus +™ EEAC325A recovers, recycles, evacuates, leak test, and recharges R-134a quickly and accurately. The EEAC325A recovers up to 20% more refrigerant and will recharge the vehicle to within ½ ounce of the charge capacity, complying with the new SAE J-2788 standard. New ergonomic cabinet design provides additional storage areas for tools, filters, and oil bottles, including a convenient fold-down control panel. Automatic Functions of the EEAC325A Additional Features of the EEAC325A √ Automatic Operation – Allows the technician to program the unit to recover, recycle, evacuate, and recharge without user intervention. • New 2X larger display makes the EEAC325A easier than ever to use. • Large tool storage area. √ Vacuum Leak Test – Will monitor the vacuum level after an evacuation and inform the technician of a possible leak in the vehicle’s A/C system. √ Automatic Refrigerant Refill – With this latest advance, you never have to stop in the middle of a job to change refrigerant tanks. The unit maintains a user selectable amount of refrigerant in an internal vessel, and signals when it’s time to change the supply tank, so no monitoring is required. • Change between traditional & hybrid vehicle systems without fear of cross contamination with improved oil injection. • Large Gauges that are easy to read. • Heavy-duty compressor pulls from both high and low sides during recovery. √ Automatic Air Purge – Eliminates damaging air without any monitoring of gauges or opening of valves. √ The Automatic Oil Drain – The unit automatically drains system oil captured during recover, and the display reminds you to empty the bottle. Graduations on the container clearly show you how much oil needs to be replaced. √ Refrigerant Charging – Select a charge mode from either the high side, low side, or both. Accuracy features eliminate guesswork. √ Refrigerant Management System – New and improved, system displays refrigerant use and monitors remaining filter life. Prompts appear when 1/3 of filter life remains. √ Vacuum Function – Defaults to 15 minutes, but is programmable up to 99 minutes. Remaining vacuum time is displayed on the screen. Page 6 EEAC325A Unit Effective 09/2007 EEAC325A Service Manual General Information PRODUCT VIEWS Large Easy-toRead Gauges Digital Display & Control Buttons Power Switch/ Circuit Breaker Control Panel Oil Drain Bottle Oil Inject Bottle FRONT VIEW Front Panel Convenient Handle for moving unit Low- and High-Side Hose Locking Casters Pump Sightglass Tank Straps Power Cord Large Wheels for mobility across air lines, power cords, grates Electronic Scale & Calibration Device REAR VIEW Effective 09/2007 Page 7 EEAC325A Service Manual General Information OPERATING GUIDELINES Using the Control Panel Main Power Switch Turns power ON and OFF. Digital Display Visual interface between the operator and the machine. Circuit Breaker Protects unit from drawing too much current. Up / Down Arrow Keys The UP and DOWN arrow keys are used for scrolling through menu items. Low-Side Gauge Shows the A/C system’s low-side pressure. Right / Left Arrow Keys The LEFT or RIGHT arrow key are used to confirm a selection or cancel out of a screen, or to continue or stop a procedure. High-Side Gauge Shows the A/C system’s high-side pressure. Low-Side Gauge High-Side Gauge Digital Display Up / Down Arrow Keys RECOVER VACUUM AUTO (ENTER) LOW CHARGE SET-UP INJ OIL (AMOUNTS) HIGH Left / Right Arrow Keys CIRCUIT BREAKER Main Power Switch Control Panel Page 8 Effective 09/2007 EEAC325A Service Manual General Information Setup Menu Access the Setup Menu from the Main Menu at any time to change the unit’s defaults or retrieve information. Once the Setup Menu has been selected, use the UP or DOWN arrow key to scroll through the menu items. Use the UP or DOWN arrow key to scroll through choices. Use the LEFT or RIGHT arrow key to confirm a selection or cancel out of a screen. Select Language Operator may choose to have prompts displayed in one of three languages: English, Spanish, or French. Display Version Displays the revision level of the software in the unit. Select Units Operator may choose to have test results displayed in Imperial (lbs.), Imperial (lbs. and oz.), or Metric (kg.). Refrig Management Displays the amount of refrigerant recovered, charged, and replenished (for the life of the unit), and filtered (since the last filter change). Manual Refill Use to transfer refrigerant from the source tank to the internal storage vessel (ISV). Adjust Tank Fill When connected to a refrigerant source, the unit maintains a pre-set amount of refrigerant in the internal storage vessel (default is 15 lbs.). This value may be adjusted up/down to suite the user’s needs. Digital Display RECOVER VACUUM AUTO (ENTER) CHARGE SET-UP INJ OIL (AMOUNTS) Up / Down Arrow Keys Left / Right Arrow Keys Contrast Use this menu item to adjust the contrast of the LCD (the digital display) by pressing the UP or DOWN arrow key. (The default is 80.) Beeper Use this menu item to mute or adjust the unit’s audio tone. Maintain Vacuum Oil For maximum vacuum pump performance, change vacuum pump oil after every 10 hours of operation. This menu item displays how long the vacuum pump has operated since the last oil change and allows the user to reset the value once an oil change is complete. Maintain Filter The filter-drier removes acid, particulates, and moisture from the refrigerant. To meet the requirements of UL J-2788, it is mandatory to replace the filter-drier after 150 lbs. (68 kg) of refrigerant has been filtered. The menu item will show how much refrigerant has been filtered since the last filter change, and allows the user to reset the value once a filter change is complete. It will be necessary to enter a 10-digit code, which appears on the filter, to ensure compliance with UL J-2788. Calibration Check Use to verify internal scale calibration. Effective 09/2007 Page 9 EEAC325A Service Manual General Information UNIT SPECIFICATIONS EEAC325A Unit - General Information Volts: 120V * Frequency: 60 Hz Amps: 12.0A Refrigerants: R-134a 98 Class III, ARI 98 Class IV Operating Pressure: 450 PSI (max.) Pressure Range: 30inHg-300 PSI Storage Temperature Range: Operating Temperature Range: Relative Humidity: Recycling Filter-Drier: -4°F to 140°F (-20°C to 60°C) 50 to 120°F (11 to 49°C) Up to 80% non-condensing 43 cu. in. Spin-On Type Oil Drain Bottle: 12 oz. (360 ml) Oil Inject Bottle: 12 oz. (360 ml) Compressor: Vacuum Pump: Gauge Ranges: Recovery Amount: 1/3 HP, 1.5 CFM Reciprocating 1/3 HP, 3 CFM, 2 Stage High Side: 500 PSI (34 BAR) max. Low Side: 350 PSI (24 BAR) max. 30 lbs. (14 kg) max. Recovery Rate: 1 lb. per minute max. Refrigerant Charge Amount: 22 lbs. (10.0 kg) max. Unit Height: 46 in. (116.8 cm) Unit Width: 24 in. (61 cm) Unit Depth: 34 in. (86.36 cm) Shipping Weight: Certified: 235 lbs. (106.6 kg) UL Listed SAE-J2788 * The voltage at the unit must be ±10% of the unit's rated voltage. Extension cords must be a minimum of 14 AWG and kept as short as possible. (25 ft./7.6 m. or less) Page 10 Effective 09/2007 EEAC325A Service Manual General Information MAINTENANCE SCHEDULE Test Required Change vacuum pump oil. Recommended Frequency Every 10 hours of operation. Change the Filter/Drier. After recovering 150 lbs. (68 kg) of refrigerant or after recovering refrigerant from a burnedout system. Fiter/Drier Warning After recovering 100 lbs. (45 kg) of refrigerant. Check Scale (Refer to scale calibration instructions in Diagnostic Section if needed.) Monthly Check for Leaks. Monthly Clean (vacuum) condenser panel. Monthly Clean cabinet and control panel. Monthly Check casters and wheels for proper operation. Lubricate bearings and brake components if necessary. Monthly Inspect hoses and power cord for cuts and abrasions. Daily Due to normal wear and tear, the EEAC325A requires regular maintenance to guarantee safe operation and optimum performance. The above chart provides a schedule of the recommended maintenance tasks. Effective 09/2007 Page 11 EEAC325A Service Manual Page 12 General Information Effective 09/2007 EEAC325A Service Manual Parts & Components Section 2 - Parts & Components External Parts ....................................................................................................... 14 Internal Parts ........................................................................................................ 16 Component Assemblies ....................................................................................... 18 Control Panel Assembly ................................................................................................... Station Pump Assembly, 115V .......................................................................................... Compressor Assembly, 115V ............................................................................................. Manifold Assembly ............................................................................................................ Internal Tank Assembly .................................................................................................... 18 20 21 22 24 Plumbing Diagram and Parts List ....................................................................... 25 Main Component Descriptions ........................................................................... 26 Alphabetical Parts List ......................................................................................... 28 Disclosure: Although most parts are listed, some part numbers are part of an assembly available only to manufacturing. Information and part numbers contained in this publication were accurate at the time it was written. Any discrepancies should be brought to the attention of Snap-on KoolKare Plus +™ Technical Support. Phone: 1-866-769-2788 Effective 09/2007 Page 13 EEAC325A Service Manual Parts & Components EXTERNAL PARTS 3 3 4 1 7 7X 8 7X 6 5 10 2X 2 9 2X EEAC325A EXTERNAL PARTS No. 1 2 3 4 5 6 7 8 9 10 Page 14 Description BACK, EEAC325A PANEL, LEFT, EEAC325A BOTTLE, OIL DRAIN/OIL INJECT NAMEPLATE, SNAP-ON LOGO PANEL, FRONT, EEAC325A DECAL FRONT, SNAP-ON WASHER, 1/4" FLAT SCREW, 1/4 X 3/4" PLASTITE SCREW, 1/4"-20 X 3/4" SCREW, 1/4"-20 X 1/2" Qty. Part No. 1 541611 1 541613 2 EEAC325A4 1 1 541612 1 7 7 2 2 Effective 09/2007 EEAC325A Service Manual Parts & Components 2 6 7X 3 5 4 1 6 2X EEAC325A EXTERNAL PARTS No. 1 2 3 4 5 6 Effective 09/2007 Description PANEL, RIGHT, EEAC325A TOP, EEAC325A DECAL, 1-800 PHONE NUMBER DECAL, WARNING DECAL, EEAC325A UL SCREW, 1/4"-20 X 3/4" Qty. Part No. 1 541614 1 541615 1 1 1 9 Page 15 EEAC325A Service Manual Parts & Components INTERNAL PARTS 38 2X 39 65 67 SEE DETAIL A 2X 40 12 EEAC325A UNIT COMPONENTS No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Description BASE ASSY CENTER DIVIDER SHELF, VACUUM PUMP SCALE ASSEMBLY & MAGNET GROMMET, COMPRESSOR COMPRESSOR ASSEMBLY, 115V MANIFOLD ASSEMBLY, BRACKET, PUMP MOUNTING STATION PUMP, 115V, 3 CFM ISV ASSEMBLY BOLT, 1/4-20 X 1/2" FAN ASSEMBLY, 115V SLEEVE, COMPRESSOR WASHER, 1/4" ID FENDER Qty. 1 1 1 1 4 1 1 2 1 1 2 1 4 12 Part No. 541618 RA20002 RA20020 RA20018 RA20017 RA17416 EEAC325A UNIT COMPONENTS No. 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Description BOLT, 1/4-20 X 2" SERR HEAD LOCKNUT, 1/4-20 STABILIZER BRACKET BOLT, 1/4-20 X 1.5" NUT, 8-32 SEMS BRACKET, CAPACITOR SCREW, 6-32 X 3/8 CAPACITOR, 115V COMPRESSOR SCREW, 1/4"-20 X 3/4" SCREW, 8-32 X 3/8 SEMS SCREW, 1/4 X 3/4" PLASTITE MAGNET (PART OF SCALE ASSY) SCREW, 1/4-20 X 3.5 LONG SCREW, 1/4-20 X 1/2" LONG Qty. Part No. 4 10 1 1 6 1 1 1 RA19489 15 5 14 1 RA20002 1 1 NOTE: The above parts listing may refer to parts located on unit diagrams on following page. Page 16 Effective 09/2007 EEAC325A Service Manual Parts & Components COMPRESSOR SEE DETAIL B EEAC325A UNIT COMPONENTS No. 29 30 31 38 39 40 42 45 47 48 49 65 66 67 DETAIL B COMPRESSOR MOUNTING Description Qty. Part No. POWER SUPPLY, 12 VOLT 1 RA20014 SCREW, SOCKET HD CAP M3-.5 X 5 4 SUPPORT, CONTROL PANEL 1 1 BRACKET, POWER CORD BUSHING, HEYCO 1 SCREW, #10-16 X 3/4" 2 TAG, POWER CORD 1 INSERT, DIE CUT FOAM 1 PANEL, CONTROL ASSEMBLY 1 PCB ASSEMBLY, RELAY BOARD 1 RA20013 SCREW, 1/4 X 1/2" PLASTITE 2 STRAP, VELCRO 1 EDGE TRIM, RUBBER 1.67' DECAL, SERIAL NUMBER 1 DETAIL A ISV NOTE: The above parts listing may refer to parts located on unit diagrams on previous page. Effective 09/2007 Page 17 EEAC325A Service Manual Parts & Components COMPONENT ASSEMBLIES CONTROL PANEL ASSEMBLY CONTROL PANEL ASSEMBLY No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Description SWITCH, POWER CIRCUIT BREAKER 15 AMP GUAGE, LOW SIDE - GENERIC GAUGE, HIGH SIDE - GENERIC KEYPAD, EEAC325A PANEL, CONTROL CONNECTOR, 1/8 NPTF X 1/8 PCB ASSEMBLY, SD CARD SCREW, #4-40 X 3/8 P E H SCREW, 6-32 X 1/4 PE TORX PCB ASSEMBLY, CONTROL BOARD BRACKET NUT, 10-32 HEX SEMS TUBE, 1/8" RED TUBE, 1/8" BLUE Qty 1 1 1 1 1 1 2 1 4 4 1 2 4 4' 4' Part No. RA19343 518638 539955 539956 541624 RA20011 RA20012 RA20003 RA20004 NOTE: The above parts listing may refer to parts located on unit diagrams on following page. Page 18 Effective 09/2007 EEAC325A Service Manual Parts & Components CONTROL PANEL ASSEMBLY Effective 09/2007 Page 19 EEAC325A Service Manual Parts & Components STATION PUMP ASSEMBLY, 115V RA20017 3 4 2 1 5 6 7 8 STATION PUMP ASSEMBLY, 115V No. 1 2 3 4 5 6 7 8 Description STATION PUMP ASSEMBLY RESERVOIR ASSEMBLY BRASE DISCHARGE FITTING * BRASS INLET FITTING * SIGHT GLASS NUT * OIL FILL PLUG * SIGHT GLASS ASSEMBLY W/O-RING * OIL DRAIN ASSEMBLY W/CAP * Qty 1 1 1 1 1 1 1 1 Part No. RA20017 RA19950 * Items followed by an asterisk are part of the Reservoir Assembly Kit (RA19950) and are not sold separately. Page 20 Effective 09/2007 EEAC325A Service Manual Parts & Components COMPRESSOR ASSEMBLY, 115V RA20020 1 DISCHARGE SUCTION SUCTION SUCTION SUCTION DISCHARGE COMPRESSOR ASSEMBLY, 115V No. 1 Effective 09/2007 Description COMPRESSOR, 115V RELAY PROTECTOR CAPACITOR COVER BAIL BRACKETS SCREW SLEEVE GROMMET CAPACITOR WIRE Qty 1 1 1 1 1 1 1 1 4 4 2 Part No. RA20020 INC INC INC INC INC INC INC INC INC INC Page 21 EEAC325A Service Manual Parts & Components MANIFOLD ASSEMBLY RA20018 See Note Next Page B 32 5 X 2X E See Note Next Page SERVICE PORT A See Note Next Page C See Note Next Page D MANIFOLD ASSEMBLY No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Description Qty. Part No. MANIFOLD BLOCK, TOP 1 MANIFOLD BLOCK, LOWER 1 ELBOW, 1/8 MP X 3/8 PNEU COMP 3 HEAT EXCHANGER 1 O-RING 2 ACCUMULATOR SHELL 1 O-RING, PKR #SB17-119-7N 1 O-RING, PKR #SB17-143-7N 1 SEPARATOR ELEMENT 1 OIL SEPARATOR BOWL(1.5-3.0 IN LB 1 UNION, 1/8 MP X 1/8 MP X .97 2 TUBE, MANIFOLD CONN,(75 IN LBS) 1 FITTING, 1/4 MFL X 1/8 NPTF 1 SCHRADER CORE, (1.5-3.0 IN LBS) 1 CAP, 1/4 FLARE W/ O-RING 1 6X F See Note Next Page See Note Next Page MANIFOLD ASSEMBLY No. 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 32 Description Qty. Part No. SOLENOID, 12V DC DISCRETE 2 RA20009 SOLENOID, 12V DC MAN,(75 IN LBS) 12 RA20010 NUT, COMPRESSION (1/8 TUBE) 2 RA20008 ELBOW, 1/8 NPTF X 1/4 COMP 1 ACCUM TRANSDUCER 2 CHECK VALVE, (75 IN LBS) 6 RA20016 TEE, MALE BRANCH 1/8 NPTF 1 CHECK VALVE 1 RA20015 FITTING, 1/8 NPT X 1/4 COMP 2 O-RING, C0873 2-240 1 FILTER DRIER, SPIN-ON 1 EEAC325A1 ELBOW, 1/8 MP X 1/8 PNEU 1 FITTING, HALF UNION .12MP X .25 FL 2 SWITCH, HIGH PRESSURE CUT-OUT 1 RA19427 SCREW, SOCKET, (30 IN LBS) 1 BALL, MANIFOLD PLUG 5 NOTE: The above parts listing may refer to manifold parts on following page. Page 22 Effective 09/2007 EEAC325A Service Manual Parts & Components 3X NOTE A. Torque Schrader Core (item 14) to 1.5-3.0 IN. LBS. B. Torque to 30 IN LBS ±5. C. Apply Loctite 242 to threads of Manifold Connection Tube (item 12) and torque to 75 IN. LBS. D. Torque Manifold Solenoid (item 17) to manifold with 75 IN. LBS. ±5. Torque Fastener to 30 IN LBS ±5. E. Press flush ±.030 with surface. F. Torque Checkvalve (item 21) to 75 IN. LBS. (6 places) G. Use (Loctite 565) on all pipe threads. H. Lubricate all O-rings on components before assembling. NOTE: The above notes may refer to the manifold diagram on previous page. Effective 09/2007 Page 23 EEAC325A Service Manual Parts & Components INTERNAL TANK ASSEMBLY 3 4 9 5 10 8 11 2 7 12 6 13 1 NOTE: Use Loctite 565 on all pipe threads. NOTE: Tank Tare Weight: Worthington: 17.50 lbs. (7.94 kg.) Air Com: 20.50 lbs. (9.30 kg.) ISV ASSEMBLY No. 1 2 3 4 5 6 7 8 9 10 11 12 13 Page 24 Description ISV, INTERNAL FITTING, STRAIGHT SOLENOID, 12V DC DISCRETE VALVE, BALL, AIR PURGE VALVE, BALL, LIQUID PRESSURE RELIEF, 450PSI FITTING, TEE, .25FP X .25FP X .25MP VALVE, BALL, VAPOR TEMPERATURE PROBE TRANSDUCER, AIR PURGE TEE, MALE BRANCH 1/8 NPTF ORIFICE, UNION .026 MUFFLER, AIR EXHAUST Qty 1 1 1 1 1 1 1 1 1 1 1 1 1 Part No. 539477 210312 RA20009 539799 539798 RA19499 508690 540322 539472 539229 539654 539804 519605 Effective 09/2007 EEAC325A Service Manual Parts & Components PLUMBING DIAGRAM USE LOCTITE 242 OR EQUIVALENT ON THREADS CABLE TIE TUBES TO HOLE IN VACUUM PUMP SHELF TAB WITH (1) 535876. USE LOCTITE 242 OR EQUIVALENT ON THREADS VACUUM PUMP EXHAUST SHOULD PROTRUDE APPROX. 1.5” INTO OIL DRAIN BOTTLE USE LOCTITE 242 OR EQUIVALENT ON THREADS CUT END OF TUBE AT 45° AND INSERT TO BOTTOM OF BOTTLE. CABLE TIE TUBE TO HOLE IN VACUUM PUMP SHELF TAB WITH (1) 535876 RED TUBE FROM HIGH SIDE GAUGE HIGH SIDE SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT LOW SIDE SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT BLUE TUBE FROM LOW SIDE GAUGE USE LOCTITE 242 OR EQUIVALENT ON THREADS BLACK TANK FILL HOSE ROUTE THROUGH HOLE IN SIDE SUPPORT Plumbing Diagram Parts List No. Description Qty. Part No. 1 HOSE, LOW SIDE SERVICE 1 EEAC325A3 2 HOSE, HIGH SIDE SERVICE 1 EEAC325A2 3 TUBE, 1/4 OD X 0.040 ID 19" 120225 4 TUBE, 3/8" HIGH PRESSURE 16" RA20005 5 HOSE, LIQUID 1 541627 6 HOSE, VAPOR 1 541626 7 TUBE, 1/4 OD X 0.040 ID 28" 120225 8 HOSE, TANK FILL 1 541625 9 TUBE, 1/4 OD X 0.040 ID 42" 120225 10 TUBE, 3/8" HIGH PRESSURE 15" RA20005 11 TUBE, COMPRESSOR TO MANIFOLD 1 538469 12 TUBE, 3/8" HIGH PRESSURE 12" RA20005 13 TUBE, NYLON 1/8 OD X .070 ID 42" 121773 14 NUT, COMPRESSION (3/8 TUBE) 2 RA20006 15 O'RING (PKR #5-124) NEOPRENE 2 RA19916 16 NUT, COMPRESSION (1/4 TUBE) 1 RA20007 Effective 09/2007 USE LOCTITE 242 OR EQUIVALENT ON THREADS NOTE: Item # RA20005 (tube, 3/8” high pressure) comes in a length of 1.5’. Cut hose to proper length as indicated in plumbing parts list. Page 25 EEAC325A Service Manual Parts & Components MAIN COMPONENT DESCRIPTIONS 12V POWER SUPPLY — Provides 12 volts to power the circuit boards, manifold block components, and the ISV air purge solenoid. BOTTLE, OIL DRAIN — Recovers the used oil during the oil drain process. BOTTLE, OIL INJECT — Stores oil for injection into the A/C system. BREAKER, 15 AMP — Protects the unit from drawing to much current. If blown, unit is completely inoperative. CALIBRATION BALL — Calibration standard that attaches to magnet under scale assembly. Used to verify scale calibration. CASTER — 5” x 2” wheels used for maneuvering unit. CHECK VALVE — Allows flow in one direction only. GAUGE, HIGH SIDE — Monitor high-side pressure of the vehicle being serviced. GAUGE, LOW SIDE — Monitors low-side pressure of the vehicle being serviced. HIGH PRESSURE CUTOUT SWITCH — Switch opens at 435 ± 10 psi (2999 ± 69 kPa) and resets at 320 ± 20 psi (2066 ± 137 kPa). If pressure in the high side of the system exceeds 435 psi (2999 kPa), the switch opens stopping all functions. INTERNAL STORAGE VESSEL (ISV) — Storage tank that the recovered and recycled refrigerant is stored. Vapor, liquid, and air purge access is on-top of tank. KEYPAD — Touch-pad cover for the front of the control board. COMPRESSOR — Moves refrigerant from the A/C system being serviced into the internal tank on the unit. MANIFOLD BLOCK ASSEMBLY — Internal block assembly that contains solenoids, check valves and switches. Refrigerant will flow through the manifold assembly for proper distribution. COMPRESSOR CAPACITOR — Used for starting the compressor. Helps reduce the initial high current demand required by the compressor on start-up. MUFFLER, AIR EXHAUST — Disperses excessive air from the ISV. Provides effective reduction of objectionable air exhaust noise. COMPRESSOR OIL SEPARATOR — Removes the compressor oil from the refrigerant that is leaving the compressor. The stored oil is returned to the compressor when the oil return solenoid receives power. ORIFICE, UNION— Fitting used to reduce the flow rate. POWER CORD — Supplies main power to the unit. CONTROL PANEL — User interface panel for controlling refrigerant recovery, recycling and recharging. PRESSURE RELIEF VALVE, 450 PSI — Spring loaded safety valve use to releases pressure from internal tank assembly if pressure exceeds 450 psi. DISPLAY/CONTROL BOARD — Front display panel and main control of the EEAC325A. RELAY BOARD — Relay control for all 12V and 115V components. FAN, 115V — Keeps the compressor’s electrical components cool. SCALE ASSEMBLY — Measures the amount of refrigerant being charged and recovered. FILTER DRIER, SPIN-ON — Used to remove moisture and particles from refrigerant. Must be changed every time 150 lbs of refrigerant is recovered. SD CARD PCB ASSEMBLY — Used to read information from Secure Digital (SD) memory cards. SIGHTGLASS – Used to view vacuum pump oil level. Page 26 Effective 09/2007 Parts & Components SOLENOID (1), NORMAL DISCHARGE — When energized, allows refrigerant flow from the compressor to the system oil separator, then to the internal storage vessel. SOLENOID (2), HIGH-SIDE CLEAR — Energized during the high-side clearing process. SOLENOID (3), OIL INJECT — Energized during the Oil Inject process to allow A/C system oil to be replenished. SOLENOID (4), DEEP RECOVER — When energized, uses vacuum pump to perform “deep” recovery of refrigerant from the system being serviced. SOLENOID (5), HIGH-SIDE CHARGE — When energized, allows refrigerant from ISV to enter high-side of system being serviced. SOLENOID (6), LOW-SIDE CHARGE — When energized, allows refrigerant from ISV to enter low-side of system being serviced. SOLENOID (7), HIGH-SIDE INLET — Allows an open “pathway” for refrigerant flow and vacuum between the A/C system high side and the EEAC325A unit. This solenoid is powered during the Recover, Vacuum, and Leak Check process. SOLENOID (8), VACUUM — When energized, allows a vacuum or deep recovery to be pulled on the A/C system being serviced. SOLENOID (9), LOW-SIDE INLET — Allows an open “pathway” for refrigerant flow and vacuum between the A/C system low side and the EEAC325A unit. This solenoid is powered during the Recover, Vacuum and Flush process. SOLENOID (10), RECOVERY — When energized, provides the primary pathway of removing refrigerant from the system being serviced. This solenoid is also powered during the Flush process. SOLENOID (11), TANK FILL — When energized during the Tank Fill process, allows refrigerant to flow from the external supply tank to the ISV. Effective 09/2007 EEAC325A Service Manual SOLENOID (12), POWER CHARGE/FEEDBACK — Provides “feedback” pressure to assist the oil drain operation. Also, increases tank pressure to assist the charging function. SOLENOID (13), OIL RETURN — When energized, it returns compressor oil from the compressor oil separator to the compressor and equalizes the pressure on the high and low side of the compressor. SOLENOID (14), OIL DRAIN — Energized at the end of the Recover process to drain oil. SOLENOID (15), AIR PURGE — Energized to allow excessive air to be removed from the internal tank. SWITCH, POWER — Allows the unit to be turned ON and OFF. SYSTEM OIL SEPARATOR — Heat exchanger with highside coils that provide internal heat to the canister causing saturated vapor and accumulated liquid refrigerants to evaporate. This process prevents liquid refrigerant from entering the compressor and separates the refrigerant oil. TEMPERATURE PROBE — Monitors the temperature inside the internal storage vessel (ISV). TRANSDUCER, ACCUM (SYSTEM OIL SEPARATOR) — Measures the pressure within the system oil separator. TRANSDUCER, AIR PURGE — Measures the pressure within the internal storage vessel (ISV). TRANSDUCER, LOW-/HIGH-SIDE — Measures the pressure of incoming refrigerant from the A/C system. Pressure readings are then relayed to the control board. VACUUM PUMP — 115V pump designed to remove moisture and air from an A/C system. Also aids in the recovery process by performing a deep recovery of A/C system. WHEEL, PNEUMATIC 10” — Transport wheels. Page 27 EEAC325A Service Manual Parts & Components ALPHABETICAL PARTS LIST DESCRIPTION PART # 12 VOLT, POWER SUPPLY RA20014 AC POWER CORD 122770 AIR EXHAUST MUFFLER 519605 AIR PURGE TRANSDUCER 539229 BALL VALVE, AIR PURGE 539799 BALL VALVE, LIQUID 539798 BALL VALVE, VAPOR 540322 BOTTLE, OIL DRAIN / INJECT EEAC325A4 CABLE, INTERCONNECT 539995 CABLE, SD BOARD 539996 CALIBRATION WEIGHT 540066 CAPACITOR, 110V START RA19489 CASTER, 5” DIA X 2” WIDE RA19631 CHECK VALVE KIT, MANIFOLD RA20016 CHECK VALVE, VACUUM RELIEF RA20015 CIRCUIT BREAKER, 15 AMP 518638 COMPRESSOR ASSEMBLY 115 VOLTS RA20020 COMPRESSOR OIL, MSDS-POLYOL ESTER OIL RA17283 COMPRESSOR START KIT RA19489 CORE SCHRADER RA19916 COUPLER, HIGH SIDE EEAC325A5 COUPLER, LOW SIDE EEAC325A6 COUPLER SET, SERVICE (HIGH & LOW-SIDE COUPLERS) 18192 DISPLAY/CONTROL BOARD RA20012 EEAC325A, BACK 541611 EEAC325A, BASE ASSEMBLY 541618 EEAC325A, FRONT PANEL 541612 Page 28 NOTES Kit inc. 6 valves Effective 09/2007 EEAC325A Service Manual Parts & Components DESCRIPTION PART # NOTES EEAC325A, LEFT PANEL 541613 EEAC325A, RIGHT PANEL 541614 EEAC325A, TOP 541615 FAN,115V RA17416 FILTER DRIER, SPIN-ON EEAC325A1 FITTING, STRAIGHT 210312 ISV Assembly FITTING, TEE, .25FP X .25FP X .25MP 508690 ISV Assembly GAUGE, HIGH SIDE 539956 GAUGE, LOW SIDE 539955 HARNESS, COMPRESSOR PIGTAIL 539991 HARNESS, FAN COMPRESSOR 539989 HARNESS, GROUND 539993 HARNESS, HIGH PRESSURE CUTOUT 539992 HARNESS, MANIFOLD 1 539927 HARNESS, MANIFOLD 2 539987 HARNESS, POWER 539990 HARNESS, POWER SUPPLY 539994 HARNESS, TRANSDUCER 539988 HIGH PRESSURE CUT-OUT SWITCH RA19427 HOSE, HIGH SIDE SERVICE EEAC325A2 HOSE, LIQUID 541627 HOSE, LOW SIDE SERVICE EEAC325A3 HOSE, TANK FILL 541625 HOSE, VAPOR 541626 ISV TANK, INTERNAL 539477 KEYPAD, EEAC325A 541624 MAGNET & SCALE ASSEMBLY RA20002 Effective 09/2007 Page 29 EEAC325A Service Manual DESCRIPTION Parts & Components PART # MAINTENANCE KIT 13172 MANIFOLD ASSEMBLY RA20018 MANUAL, USER ZEEAC325A MUFFLER, AIR EXHAUST 519605 NUT, COMPRESSION (1/4 TUBE) RA20007 NUT, COMPRESSION (1/8 TUBE) RA20008 NUT, COMPRESSION (3/8 TUBE) RA20006 OIL, COMPRESSOR, MSDS-POLYOL ESTER OIL RA17283 OIL, PUMP - 16 OZ, SNAP-ON 542758 OIL DRAIN / INJECT BOTTLE EEAC325A4 ORIFICE, UNION .026 539804 PCB ASSY, DISPLAY/CONTROL BOARD RA20012 PCB ASSY, RELAY BOARD RA20013 PCB ASSY, SECURE DIGITAL CARD RA20011 POWER SUPPLY, 12 VOLT RA20014 PRESSURE RELIEF, 450 PSI RA19499 PROTECTOR, 110V MOTOR OVERLOAD RA19489 RELAY, 110V STARTING RA19489 RELAY BOARD RA20013 SCALE ASSEMBLY & MAGNET RA20002 SD CARD, PCB ASSEMBLY RA20011 SERVICE COUPLER HIGH SIDE (R134A) EEAC325A5 SERVICE COUPLER LOW SIDE (R134A) EEAC325A6 SERVICE COUPLER SET (HIGH & LOW-SIDE COUPLERS) 18192 SERVICE HOSE, HIGH SIDE EEAC325A2 SERVICE HOSE, LOW SIDE EEAC325A3 SOLENOID, 12V DC DISCRETE RA20009 Page 30 NOTES ISV Assembly Effective 09/2007 EEAC325A Service Manual Parts & Components DESCRIPTION PART # NOTES SOLENOID, 12V DC MANIFOLD RA20010 SWITCH, HIGH PRESSURE CUT-OUT RA19427 SWITCH, ON-OFF, (I-O) RA19343 TEE, MALE BRANCH, 1/8 NPTF 539654 TEMPERATURE PROBE 539472 TRANSDUCER, AIR PURGE 539229 TUBE 1/4 OD X 0.040 WALL 120225 Ordered by the foot TUBE, 1/8" BLUE RA20004 3 ft. TUBE, 1/8" RED RA20003 3 ft. TUBE, 3/8" HIGH PRESSURE RA20005 TUBE, COMPRESSOR TO MANIFOLD 538469 TUBE, MANIFOLD CONNECTION 537991 TUBE, NYLON 1/8 OD X .075 ID 121773 VACUUM PUMP, 115V 3 CFM RA20017 VACUUM PUMP OIL, - 16 OZ, SNAP-ON 542758 WEIGHT, CALIBRATION 540066 WHEEL, CASTER, 5” DIA X 2” WIDE RA19631 WHEEL, PNEUMATIC, 10” 19823 WIRE HARNESS, COMPRESSOR PIGTAIL 539991 WIRE HARNESS, FAN COMPRESSOR 539989 WIRE HARNESS, GROUND 539993 WIRE HARNESS, HIGH PRESSURE CUT-OUT 539992 WIRE HARNESS, MANIFOLD 1 539927 WIRE HARNESS, MANIFOLD 2 539987 WIRE HARNESS, POWER 539990 WIRE HARNESS, POWER SUPPLY 539994 WIRE HARNESS, TRANSDUCER 539988 Effective 09/2007 ISV Assembly Ordered by the foot Page 31 EEAC325A Service Manual Page 32 Parts & Components Effective 09/2007 EEAC325A Service Manual Diagnostics Section 3 - Diagnostics Functional Check ................................................................................................. 34 12VDC Solenoid Test Procedure ........................................................................ 37 Service Center Menu Options ............................................................................. 38 Output Step Test ................................................................................................... 39 Depressurizing the Unit ....................................................................................... 39 Troubleshooting ................................................................................................... 40 Unit Will Not Power-Up, No Display ................................................................................ Will Not Tank Fill .............................................................................................................. Will Not Recover (First Stage) .......................................................................................... Will Not Deep Recover (Second Stage) .......................................................................... Will Not Perform Clearing ................................................................................................ Will Not Air Purge ............................................................................................................. Will Not Drain Oil .............................................................................................................. Will Not Evacuate (Vacuum) ............................................................................................. Fails Leak Test .................................................................................................................. Will Not Inject Oil .............................................................................................................. Will Not Charge ................................................................................................................. Miscellaneous Error Messages ......................................................................................... 40 41 42 43 44 45 45 46 47 47 48 49 Service Instructions and Calibration .................................................................. 50 Replacement Compressor (RA20020) Specifications & Service .................................... Replacement Vacuum Pump (RA20017) Specifications & Service ............................... Replacement High Pressure Cut-Out Switch (RA19427) ................................................. Replacement Scale Assembly/Magnet (RA20002) .......................................................... Replacement Manifold Block (RA20018) ......................................................................... Replacement Manifold Solenoid (RA20010) ................................................................... Replacement Display Board (RA20012) ........................................................................... Replacement Relay Board (RA20013) .............................................................................. Replacement Vacuum Relief Check Valve (RA20015) .................................................... Replacement Manifold Check Valve (RA20016) .............................................................. Replacement 3/8” High Pressure Tube (RA20005) .......................................................... 50 53 54 55 56 59 60 62 64 65 66 System Wiring ...................................................................................................... 67 Component Wiring ............................................................................................... 68 Wiring Harnesses ................................................................................................. 71 Component Identification ................................................................................... 82 Component Application Chart ............................................................................. 83 Flow Diagrams ...................................................................................................... 84 Effective 09/2007 Page 33 EEAC325A Service Manual Diagnostics FUNCTIONAL CHECK Setup 1. Check to make sure all lines are correctly connected to tank and that all tank valves are open. 2. Connect the unit’s service hoses up to a test tank. 3. Plug unit into correct power source. 4. Turn main power on. 5. Unit will show “SNAP-ON KOOLKARE PLUS” and “Software Version X.XXX.” 6. Unit will display the Main Menu screen. 7. Press the RIGHT arrow key (AMOUNTS) to display recovered and charged amounts. 8. Press the LEFT arrow key (NEXT) to display tank weight, tank temperature, and tank pressure. 9. Verify there is enough refrigerant in the tank for the unit to function and that the tank temperature and pressures are within acceptable limits. 10. If any of the above are not acceptable, correct the problem before continuing. 11. Press the LEFT arrow key (NEXT) to display the filter amount used. 12. Press the LEFT arrow key (DONE) to exit this screen. If low on refrigerant, unit may display “Low Refrigerant” “Fill Tank.” Digital Display RECOVER VACUUM AUTO (ENTER) CHARGE SET-UP INJ OIL (AMOUNTS) Left / Right Arrow Keys EEAC325A Keypad Page 34 Up / Down Arrow Keys Setup unit to Display Accumulator Pressure 1. Press the UP or DOWN arrow key to move the cursor to SETUP. 2. Press the LEFT arrow key (ENTER) to confirm selection. 3. Press the UP or DOWN arrow key to move cursor to SERVICE MENU. 4. Press the LEFT arrow key (ENTER) to confirm selection. 5. Press the UP or DOWN arrow key until the number “2” is shown in the first of four places on the display. 6. Press the LEFT arrow key (ENTER) to confirm selection. 7. Press the UP or DOWN arrow key until the number “2” is shown in the second of four places on the display. 8. Press the LEFT arrow key (ENTER) to confirm selection. 9. Press the UP or DOWN arrow key until the number “0” is shown in the third of four places on the display. 10. Press the LEFT arrow key (ENTER) to confirm selection. 11. Press the UP or DOWN arrow key until the number “0” is shown in the fourth of four places on the display. 12. Display should show “2200.” 13. Press the LEFT arrow key (ENTER) to confirm selection. 14. From the SERVICE MENU, press the DOWN arrow key until “Display Accumulator Pressure” is shown on the screen. 15. Press the LEFT arrow key (ENTER) to confirm selection. 16. Unit will display “Left Changes State, Display Acc Pressure, No, Right arrow to Exit.” 17. Press the LEFT arrow key so that “No” changes to “Yes.” 18. Once it says “Yes,” press the RIGHT arrow key to exit. 19. Unit will show “Display Acc Pressure.” Effective 09/2007 EEAC325A Service Manual Diagnostics 20. Press the RIGHT arrow key (CANCEL) twice to exit. 21. Connect a calibrated gauge to the manifold test port. Vacuum 1. Press the UP or DOWN arrow key to move the cursor to VACUUM. 2. Press the LEFT arrow key (ENTER) to confirm selection. 3. Unit will display “Checking Pressure.” 4. Press the DOWN arrow key until 3-minute vacuum is displayed. 5. Press the LEFT arrow key (OK) to pull a vacuum on the test tank. 6. You will be asked if you want to do a leak test. Press the RIGHT arrow key (NO) unless the complaint was for “unit fails leak test.” 7. Unit will display “Vacuum in Progress, Time Remaining XX.XX, Stop to Pause.” 8. Once the vacuum is complete, the unit will display “Vacuum Complete, Any Key Exits.” 9. Press the LEFT arrow key to exit. 10. Unit will display the MAIN MENU. During the Vacuum process, you may hear the unit purging air, this is normal operation. Charging Test 1. Press the UP or DOWN arrow key to move the cursor to CHARGE. 2. Press the LEFT arrow key (ENTER) to confirm selection. 3. Unit will display “Charge XX.XX, Mode xxxx Side, Charge Changes Mode, Arrow Key Change Unit.” 4. Enter 02.55 lbs charge using UP arrow key. 5. Press the LEFT arrow key (OK) to continue. 6. Press the DOWN arrow key until both high and low lights are lit. To verify Oil Inject function, you will need to charge high-side only. 7. Press the LEFT arrow key (NEXT) to select. 8. Press the LEFT arrow key (START). “Charge in Progress” appears on the display. (“Purging Air Please Wait” may also show on display.) 9. “High and Low Side Charge in Progress Do Not Disturb” will show on display. When the unit gets towards the end of the charge, you will notice that it slows down and then pulses the last .10 lbs. in. This is done for charging accuracy. 10. When charging is complete, the unit will display “Charged XX.XX lbs, Press Start to Equalize Hoses.” 11. Press the LEFT arrow key (START). 12. Unit will display “Disconnect High Side HoseCouple and Connect the Low Side Hose and Start A/C Max, Start To Continue.” 13. Close both tank valves and press the LEFT arrow key (OK). 14. Unit will display “Equalizing Hoses Please Wait.” 15. When hose equalizing is completed, unit will display “Disconnect LS Hose Start to Continue.” 16. Leave all hoses connected to test tank and make sure that both tank valves are still closed. 17. Press the LEFT arrow key (OK). 18. Unit will display “Clearing Hoses Please Wait.” 19. When clearing is complete, unit will display “Charge Complete X.XX lbs.” 20. Press the LEFT arrow key to exit. 21. Unit will display the MAIN MENU. Recovery Test 1. 2. 3. 4. Make sure that the vacuum pump exhaust tube and the oil drain tube are in a capture bottle before starting the recovery test. Open both tank valves and invert test tank. Press the UP or DOWN arrow key to move the cursor to RECOVER. Press the LEFT arrow key (ENTER) to confirm selection. Unit will display “Checking Pressure.” Continued . . . Effective 09/2007 Page 35 EEAC325A Service Manual Diagnostics FUNCTIONAL CHECK — CONTINUED 5. Once the unit verifies there is enough pressure, it will then display “Recovery Clearing.” • When the recovery clearing in done, the unit will display the “Recovering Progress, Amount Recovered X.XX.” • The calibrated test gauge that is connected to the test port shows the amount of pressure (refrigerant) that is being allowed during the recovery process. It should not exceed 38 psi. As the refrigerant is recovered, this number will decrease and eventually go into a negative (inhg) number. • When the calibrated low side gauge reaches “0”, the vacuum pump will start while the compressor is still running. The amount of vacuum time depends on how long it took for the unit to complete the recovery for the amount of refrigerant recovered. • Once the vacuum pump starts, you will notice that the calibrated test gauge connect to the test port rises back to “0” inhg*. This is accomplished by opening the oil return and/or pressure feedback solenoid. The reason for this is to keep the exhaust of the vacuum pump out of a negative pressure situation so that oil is not pulled out of the vacuum pump. *During the Vacuum process the pressure will float between 3 psi and 3 inhg. 6. When the vacuum pump timer times out, the unit displays “Recovery in Progress, Recovered X.XX lbs, Clearing Please Wait.” 7. When Clearing is complete, the unit will display “Draining Oil, Accumulator Pressure XX, Please Wait.” (Accumulator Pressure will rise to 16 psi.) 8. After the oil drain is complete, the unit will display “Recovery Complete, Recovered X.XX, Empty oil drain bottle now.” 9. Press the LEFT arrow key to exit. 10. When the vacuum process is complete, turn off the Display Accumulator Pressure. Page 36 To turn off the Display Accumulator Pressure 1. Press the UP or DOWN arrow key to move the cursor to SETUP. 2. Press the LEFT arrow key (ENTER) to confirm selection. 3. Press the UP or DOWN arrow key to move cursor to SERVICE MENU. 4. Press the LEFT arrow key (ENTER) to confirm selection. 5. Press the UP or DOWN arrow key until the number “2” is shown in the first of four places on the display. 6. Press the LEFT arrow key (ENTER) to confirm selection. 7. Press the UP or DOWN arrow key until the number “2” is shown in the second of four places on the display. 8. Press the LEFT arrow key (ENTER) to confirm selection. 9. Press the UP or DOWN arrow key until the number “0” is shown in the third of four places on the display. 10. Press the LEFT arrow key (ENTER) to confirm selection. 11. Press the UP or DOWN arrow key until the number “0” is shown in the fourth of four places on the display. 12. Display should show “2200.” 13. Press the LEFT arrow key (ENTER) to confirm selection. 14. From the SERVICE MENU, press the DOWN arrow key until “Display Accumulator Pressure” is shown on the screen. 15. Press the LEFT arrow key (ENTER) to confirm selection. 16. Unit will display “Left Changes State, Display Acc Pressure, Yes, Right arrow to Exit.” 17. Press the LEFT arrow key so that “Yes” changes to “No.” 18. Once it says ‘No,” press the RIGHT arrow key to exit. 19. Unit will show “Display Acc Pressure.” 20. Press the RIGHT arrow key (CANCEL) twice to exit. Effective 09/2007 Diagnostics EEAC325A Service Manual 12VDC SOLENOID TEST PROCEDURE The solenoids that are used in the EEAC325A unit cannot be tested using the P/N 17012 magnetic solenoid tester. The solenoids in this unit are activated from a 12VDC power source and have a duty cycle of 25%. Duty Cycle is the ratio of solenoid on-time to total cycle time. In this particular scenario, the solenoid is on 25% (250μs) of the total cycle and off for 75% (750μs) of the cycle. When the solenoid is ‘first’ activated, it receives a 12VDC, 125ms pulse to energize (turn on) the solenoid coil. The solenoid is then cycled on and off rapidly at a 50ms, 25% duty cycle. Although the power to the solenoid is cycling ON and OFF, the solenoid actually sustains the “ON” state because the cycling process is happening so quickly, the solenoid doesn’t have time to turn off until the power is completely removed. Using this process to power the solenoids requires less power and increases the component’s life expectancy. The best way to verify solenoid operation is to use an oscilloscope. Viewing the solenoid’s duty cycle pattern on the oscilloscope will provide the best information on how the solenoid coil is performing. Set oscilloscope to DC mode. Set the time to .2 ms/div and voltage range to 5 volts/div. Attach the scope probe to an energized solenoid. The pattern on the oscilloscope should look similar to the sample below with amplitude of 12V. If the amplitude is not 12V, check the power supply. If the pattern is irregular or doesn’t compare to the sample below, replace the solenoid coil. If an oscilloscope is not available, a digital volt meter may be used to check power applied to the solenoid. However, do NOT expect to see 12VDC on the DVM. Because most DVM’s use RMS to read voltages, the meter will read an average voltage of 2.8 VDC due to the continuous 25% on, 75% off cycling of the solenoid. An LED light may also be used to verify that a solenoid is receiving power. Attach the leads of the 12VDC LED light across the solenoid terminals. While watching the LED, activate the solenoid from the service menu. The LED should turn-on bright for a moment (initial 12VDC, 125ms activation pulse), then dim considerably when the 25% duty cycle begins. 1 Complete Cycle Sustain Pulse, 25% Duty Cycle, 1kHz Cycle (low part of pattern is “On” time) 12V 750µs 75% 750µs 25% 250µs 125ms Activation Pulse (not to scale) Effective 09/2007 Off 250µs On 25% Duty Cycle Page 37 EEAC325A Service Manual Diagnostics SERVICE CENTER MENU OPTIONS These are the Service Options at the time of printing this service manual. Some options may be added or deleted in future circuit board revisions and software updates. Never change the default settings unless directed from the factory. Otherwise the unit may fail to operate properly. Never give the programming or service codes to customers. Service Menu At the time of writing this manual, the software version was 2.017. Software and functions are subject to change without notification. To access the Service Menu 1. Press the UP or DOWN arrow key to move the cursor to SETUP. 2. Press the LEFT arrow key (ENTER) to confirm selection. 3. Press the UP or DOWN arrow key to move cursor to SERVICE MENU. 4. Press the LEFT arrow key (ENTER) to confirm selection. 5. Press the UP or DOWN arrow key until the number “2” is shown in the first of four places on the display. 6. Press the LEFT arrow key (ENTER) to confirm selection. 7. Press the UP or DOWN arrow key until the number “2” is shown in the second of four places on the display. 8. Press the LEFT arrow key (ENTER) to confirm selection. 9. Press the UP or DOWN arrow key until the number “0” is shown in the third of four places on the display. 10. Press the LEFT arrow key (ENTER) to confirm selection. 11. Press the UP or DOWN arrow key until the number “0” is shown in the fourth of four places on the display. 12. Display should show “2200.” 13. Press the LEFT arrow key (ENTER) to confirm. Page 38 Display will show SERVICE MENU. Press the UP or DOWN arrow key to scroll though the following service options: Maintenance Counter Production Test Prepare to Ship Board Test Output Test Service Vacuum Air Purge Info Set UL Display ACC Pressure Reset Board Memory Install Routine Keypad Test Service Leak Check Set Tank Tare Display Pressure Calibrate Scale • To confirm choice, press LEFT arrow. • To cancel choice, press RIGHT arrow. To Reset Selected Choice 1. To reset the selected choice, press the arrow key (RESET) once. 2. To enter Service Code “7691,” press the UP or DOWN arrow key until the number “7” is shown in the first of four places on the display. 3. Press the LEFT arrow key (ENTER) to confirm selection. 4. Push the UP or DOWN arrow key until the number “6” is shown in the second of four places on the display. 5. Press the LEFT arrow key (ENTER) to confirm selection. 6. Push the UP or DOWN arrow key until the number “9” is shown in the third of four places on the display. 7. Press the LEFT arrow key (ENTER) to confirm selection. 8. Push the UP or DOWN arrow key until the number “1” is shown in the fourth of four places on the display. 9. Display should show “7691.” 10. Press the LEFT arrow key (ENTER) to confirm. 11. Display will show Reset (your Choice). • Press LEFT arrow key to reset. • Press RIGHT arrow key to reject 12. Press the RIGHT arrow key (DONE) to exit. 13. Either scroll to the next option by pressing the UP or DOWN arrow key, or press the RIGHT arrow key (CANCEL) to exit the SERVICE MENU. 14. Press the RIGHT arrow key (CANCEL) to exit the SETUP MENU. Effective 09/2007 EEAC325A Service Manual Diagnostics OUTPUT STEP TEST Refer to the 12VDC solenoid test procedure on page 37 to check solenoid operation during the output tests. The output test will turn on or turn off power to the specified component. Do not perform any test for an extended time period. 1. To access the Output Test, turn ON unit and proceed to SERVICE MENU. 2. Press the UP or DOWN arrow key to scroll through the menu choices until “Output Step Test” is displayed. 3. Press the LEFT arrow key (OK) to continue. 4. Press the LEFT arrow key (NEXT) to select the component. 5. After the component has been selected, press the UP or DOWN arrow keys to toggle power ON or OFF. 6. Press the LEFT arrow key (NEXT) to select next component. 7. Press the RIGHT arrow key (STOP) to exit. 8. Press the RIGHT arrow key (CANCEL) to exit the SERVICE MENU. 9. Press the RIGHT arrow key (CANCEL) to exit the SETUP MENU. OUTPUT STEP TEST Component Order Energized Component Effective 09/2007 1 Recycle Solenoid 2 Vacuum Solenoid 3 LS Inlet Solenoid 4 HS Inlet Solenoid 5 Oil Return Solenoid 6 Oil Drain Solenoid 7 Vacuum/Recover Solenoid 8 Oil Inject Solenoid 9 Tank Fill Solenoid 10 Recover Solenoid 11 LS Charge Solenoid 12 HS Charge Solenoid 13 Air Purge Solenoid 14 HS Discharge Solenoid 15 Normal Discharge Solenoid 16 Vacuum Pump 17 Compressor 18 Fan 19 Light 20 High Side LED 21 Low Side LED 22 Light DEPRESSURIZING UNIT Always wear safety goggles when working with refrigerants. Contact with refrigerant can cause eye injury. Disconnect lines and hoses with extreme caution! Pressurized refrigerant may be present in lines and hoses. Always point lines and hoses away from you and anyone nearby. Always unplug the station from the power source before removing any of the shrouding or beginning any service work. Unit is Functional 1. Perform Recovery function. 2. Close Liquid valve on ISV. 3. Turn unit off when oil drain error is displayed. 4. The only refrigerant present may be in the vapor hose between the ISV and manifold block. Unit is NOT Functional 1. Disconnect the high and low side service hoses from vehicle. Make sure the coupler valves are closed. 2. Disconnect the fill hose from the source tank. 3. Open the unit door and close the (3) ISV valves. 4. Connect an auxiliary recovery unit up to the manifold service port. 5. Start the auxiliary recovery unit and allow it to pull a 13” vacuum on the unit being serviced. 6. When the unit is pulled down to this level, turn off the auxiliary recovery unit, and disconnect from the manifold service port. 7. Carefully disconnect or remove components as there may be refrigerant present at these fittings. Page 39 EEAC325A Service Manual Diagnostics TROUBLESHOOTING Will Not Power-Up, No Display 1. Verify that unit is not plugged into an extension cord. If it is, remove extension cord. 2. Verify AC power cord is properly connected to a good AC power source at receptacle. Verify that it is wired correctly and has a good ground. 3. Turn ON the main power switch. Verify that line voltage is present at the input and output terminals of the switch. • If line voltage is not present at power switch input, check connections between power switch and AC plug. • If line voltage is present at power switch input, but not at output with switch turned ON, replace power switch. • If line voltage is present at both input and output of switch, proceed to next step. 4. Verify line voltage is present across pins 2 and 3 of connector J1 on the relay board. • If line voltage is present, proceed to next step. • If line voltage is not present, check connections between the power switch and connector J1. 5. If unit does not power up, check if the 15A circuit breaker (located on back of unit) has tripped. 15A Breaker Not Tripped 1. Switch off unit and unplug AC power cord from receptacle. 3. Perform the following voltage checks: • Verify line voltage is present across pins 3 and 4 of connector J3 on the relay board. • If line voltage is not present, check for continuity between the 15A circuit breaker and J3 on the relay board. Repair as needed. • If line voltage is present, replace the relay board. 4. If all the proceeding steps fail to repair the problem, replace the display/control board. 15A Breaker Tripped 1. Switch off unit and reset circuit breaker. Switch unit back on. If breaker trips after reset and AC power has been tested good, the circuit breaker needs to be replaced. 2. If breaker trips again after being replaced, switch off unit and unplug all connectors on the relay board except J1 (AC In) and J3 (Circuit Breaker). Switch unit back on. • If circuit breaker trips again, replace relay board. • If the circuit breaker doesn’t trip, turn off power, plug-in one connector at a time, and turn back on. Keep doing this until the circuit breaker trips. Check all components associated with the last connector attached to the relay board. 2. Check the 15A breaker for continuity. • If there is no continuity, replace circuit breaker. • If there is continuity, plug the AC power cord into the receptacle and switch unit on. Continue to next step. Page 40 Effective 09/2007 Diagnostics EEAC325A Service Manual Will Not Tank Fill Compressor Running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 10. Check the compressor for suction and discharge performance. 11. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 12. Verify that the scale is unobstructed and calibrated. 3. Verify the tank hoses are properly connected and threaded completely onto the ISV fittings. 4. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. 5. Verify the fill hose is properly connected and threaded completely onto the source tank fitting. Check quick-seal on tank fill hose. 6. Verify that there is a minimum of 8 pounds (3.6 kilograms) of refrigerant in the source tank. 7. Verify the Tank Fill and Normal Discharge solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. • Verify the operation of the Tank Fill check valve—replace as needed. The Tank Fill solenoid is controlled to maintain 35 psi in the accumulator. 8. Check the Power Charge, Recover, Oil Return, Oil Drain, Deep Recover, and High-Side Clear solenoids for bleed-through—repair as needed. Compressor does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace the compressor. If the compressor is cool and drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 6. Perform functional check and recalibrate unit. 9. Check the Clearing Discharge check valve for bleed-through—repair as needed. Effective 09/2007 Page 41 EEAC325A Service Manual Diagnostics Will Not Recover (First Stage) Compressor running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. Verify the service hoses are properly attached to the unit without any restrictions and coupler valves are open. 3. Verify that ISV valves are open and tank hoses are properly connected and threaded completely onto the ISV fittings. 4. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. 5. Verify that the Normal Discharge, Recover, HighSide Inlet and Low-Side Inlet solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. The Recover solenoid is controlled to maintain 35 psi max in the accumulator. 6. Check the High-Side Charge, Low-Side Charge, Oil Inject, Oil Return, Vacuum, High-Side Clear, Tank Fill, and Power Charge solenoids for bleedthrough and proper operation —repair as needed. 7. Check the compressor for suction and discharge performance. Page 42 8. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 9. Verify that the accumulator transducer is functioning properly. 10. If all the proceeding steps fail to repair the problem, replace the display/control board. Compressor does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace the compressor. If the compressor is cool and drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. Effective 09/2007 EEAC325A Service Manual Diagnostics Will Not Deep Recover (Second Stage) Vacuum pump running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify the service hoses are properly attached to the unit without any restrictions and coupler valves are open. 8. Check the Clearing Discharge checkvalve for bleed-through—repair as needed. 9. Check for suction at the intake of the pump. If there is none, replace the pump. 10. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 11. Verify that the accumulator transducer is functioning properly. 4. Verify that ISV valves are open and tank hoses are properly connected and threaded completely onto the ISV fittings. 12. If all the proceeding steps fail to repair the problem, replace the display/control board. 5. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. Vacuum pump does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 6. Verify that the Normal Discharge, High-Side Inlet, Low-Side Inlet, Vacuum, Deep Recover, and Power Charge (see note) solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 2. If the unit is being run through an extension cord, eliminate its use. The Power Charge solenoid is controlled to maintain 0 to 3 psi in the accumulator. 7. Check the High-Side Charge, Low-Side Charge, Oil Inject, Oil Return, Recover, Tank Fill and High-Side Clear solenoids for bleed-through and proper operation—repair as needed. 3. Check for 110V at the vacuum pump connector, pins 2 and 3. • If voltage is present, replace vacuum pump assembly. • If voltage is not present, continue to next step. 4. Check for 110 volts from the relay board on connector J6, pins 1 and 2. • If voltage is present, check wiring between the relay board and the vacuum pump. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 5. Perform functional check and recalibrate unit. Effective 09/2007 Page 43 EEAC325A Service Manual Diagnostics Will Not Perform Clearing Compressor Running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 9. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 10. If all the proceeding steps fail to repair the problem, replace the display/control board. 3. Verify the tank hoses are properly connected and threaded completely onto the ISV fittings. Compressor does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 4. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. 2. If the unit is being run through an extension cord, eliminate its use. 5. Verify the Normal Discharge, HS Clear, and Oil Return solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. • Verify the operation of the Tank Fill check valve—replace as needed. 6. Check the Power Charge, Recover, Oil Drain, Deep Recover, and Tank Fill solenoids for bleedthrough—repair as needed. 7. Check the Normal Discharge check valve for bleed-through—repair as needed. 8. Check the compressor for suction and discharge performance. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace the compressor. If the compressor is cool and drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 6. Perform functional check and recalibrate unit. Page 44 Effective 09/2007 Diagnostics Will Not Air Purge 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Check the 0.028” orifice between the ISV and air purge solenoid for debris. • If the orifice is contaminated or defective, repair or replace as needed. • If the orifice is operational, proceed to the next step. 4. Verify the Air Purge solenoid is receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 5. Verify that the tank temperature probe and pressure transducer are functioning properly. EEAC325A Service Manual Will Not Drain Oil For dye usage, please refer to Limited Warranty Statement. 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify the Oil Drain solenoid is receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 4. Verify that the accumulator transducer is functioning properly. 5. If the proceeding steps fail to repair the problem, replace the display/control board. 6. If the proceeding steps fail to repair the problem, replace the display/control board. Effective 09/2007 Page 45 EEAC325A Service Manual Diagnostics Will Not Evacuate (Vacuum) Vacuum pump running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 9. Check plumbing between vacuum pump and service hoses for loose connections or fittings. 10. Replace vacuum pump. 2. If the unit is being run through an extension cord, eliminate its use. 11. If all the proceeding steps fail to repair the problem, replace the display/control board. 3. Verify the service hoses are properly attached to the unit (valves open) without any restrictions. Vacuum pump does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 4. Be sure the two plastic vacuum lines are snug at both ends and not obstructed. Check the pneumatic fittings for leaks. 5. Check for proper vacuum oil level in the vacuum pump sight glass (oil level should be in the center of the sight glass while the pump is running). Replace vacuum pump oil if necessary. 6. Check for suction at the intake of the pump. If there is none, replace the pump. 7. Verify that the Vacuum, Low-Side Inlet and HighSide Inlet solenoids are receiving power and opening properly. • If not receiving power, check continuity of the wiring between the solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 8. Check the High-Side Charge, Low-Side Charge, Oil Inject, Recover, and Deep Recover solenoids for bleed-through and proper operation—repair as needed. Page 46 2. If the unit is being run through an extension cord, eliminate its use. 3. Check for 110V at the vacuum pump connector, pins 2 and 3. • If voltage is present, replace vacuum pump assembly. • If voltage is not present, continue to next step. 4. Check for 110 volts from the relay board on connector J6, pins 1 and 2. • If voltage is present, check wiring between the relay board and the vacuum pump. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 5. Perform functional check and recalibrate unit. Refer to vacuum pump service bulletin. Effective 09/2007 Diagnostics Fails Leak Test EEAC325A Service Manual Will Not Inject Oil 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the High-Side and Low Side Inlet solenoids are receiving power and opening properly. • If not receiving power, check continuity of the wiring between the solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 3. Verify the high-side service hose is properly attached to the unit without any restrictions and coupler valve is open. 4. Check the High-Side Charge, Low-Side Charge, Oil Inject, Recover, and Vacuum solenoids for bleed-through—repair as needed. 5. Verify that the low-side pressure transducer is functioning properly. 6. If vacuum can not be maintained, use a refrigerant detector to check all plumbing hoses and fittings for leaks—repair as needed. Refer to the Leak Test flow diagram illustrated in the Flow Charts section. 7. If all the proceeding steps fail to repair the problem, replace the display/control board. Effective 09/2007 4. Verify a deep vacuum has been pulled on the system. 5. Verify the oil injector bottle is securely attached and contains an appropriate amount of oil. 6. Verify the Oil Inject solenoid is receiving power and opening properly when the Oil Inject Button is pressed on the keyboard. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 7. Check the High-Side Inlet and High-Side Charge solenoids for bleed-through—repair as needed. 8. If the proceeding steps fail to repair the problem, replace the display/control board. Page 47 EEAC325A Service Manual Diagnostics Will Not Charge There is no component that "pumps" refrigerant into a system during the charge process. The refrigerant flows in by a pressure transfer. If the system is not in a vacuum, this unit will not charge. 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify the service hoses are properly attached to the unit without any restrictions and coupler valves are open. 4. Verify a deep vacuum has been pulled on the system being charged. 5. Check that all ISV hoses are properly installed and valves are open. Also verify that the scale is unobstructed. 6. If “INSUFFICIENT REFRIG AVAILABLE” is on the display, verify that there is a minimum of 8 pounds (3.6 kilograms) of refrigerant in the tank. If there is enough refrigerant in the tank check scale calibration and re-calibrate. 7. Verify that the control module has accepted the programmed amount. Test the operation of the keypad; replace if necessary. 8. Verify the Low-Side Charge and/or High-Side Charge solenoids (depending on user input) are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 9. Check the Low-Side Inlet, High-Side Inlet, Oil Inject, and Power Charge solenoids for bleedthrough and proper operation—repair as needed. If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stop to build tank pressure. 10. If the proceeding steps fail to repair the problem, replace the display/control board. Slow Charge: 1. Check and ensure that there is a good vacuum in the vehicle being tested. 2. Verify that there is sufficient pressure in ISV to transfer refrigerant. 3. Ensure chargeable weight is greater than desired charge. 4. Verify the charge couplers are completely open and the vehicle ports are actuated. 5. Check for debris in any of the charging circuit solenoids. Clean or replace if necessary. Page 48 Effective 09/2007 Diagnostics EEAC325A Service Manual Miscellaneous Error Messages Low Recover Pressure, Check Connections During the recovery process, the unit is sensing less than 10 psi at the Low-Side Pressure Transducer. Verify all connections before continuing. Serial Number Error The 10-digit serial number for the filter is invalid, entered incorrectly, or the filter-drier has already been used in the unit. Pressure too High for Vacuum If this message occurs during the evacuation process, the unit is sensing greater than 10 psi at the Low-Side Pressure Transducer. Perform recovery before continuing. Oil Drain Error 1 The ACC Pressure Transducer is reading accumulator pressure less than 16 psi. (Verify the Recycle solenoid is open and Oil Drain solenoid is closed.) If this message occurs during the clearing process, the unit is sensing greater than 10 psi at “any” pressure transducer. Oil Drain Error 2 The ACC Pressure Transducer is reading accumulator pressure greater than 9 psi, or accumulator pressure change is less than 0.15 psi/sec. (Verify the Recycle solenoid is closed and Oil Drain solenoid is open.) Insufficient Refrigerant Available This message is displayed if the charge amount entered will leave less than 3 lbs. (1.36 kg) of refrigerant in the ISV after charge. Add additional refrigerant to the tank. Insufficient Refrigerant for Flush There is less than 10 lbs. of refrigerant in ISV. To perform the flush routine, there must be more than 10 lbs. of refrigerant available in the tank. Add refrigerant. Insufficient ISV Pressure for Test There is less than 50 psi of pressure in the ISV. To perform the leak test routine, the tank pressure must be higher than 50 psi. Calibration Error/Calibration Rejected When the calibration check is performed, the unit measures the scale weight before and after the calibration weight has been attached to the scale. If the difference in weight is 1.18 ± 0.03 lbs., the calibration check will pass. However, if the difference is anything else, the Calibration Error/Calibration Rejected message will be displayed. UL Cal Error, Check Cal Weight UL calibration failure has occurred. Verify that scale is unobstructed and calibration weight is 43 lbs. for Worthington ISV, or 45 lbs. for the Aircom ISV. Scale or control board not responding correctly. Effective 09/2007 Flush Filter Blocked The Low-Side Pressure Transducer is reading pressure greater than 20 psi. Refrigerant Management – Invalid Password Password not entered correctly. Refrigerant Management password is “8635.” XXX lb Filtered, Lockout in XX.XX, Replace Filter Now? This is a warning that 100 lbs. (45 kg) or more of refrigerant has been recovered since the last filter-drier change. Unit will lockout at 150 lbs. XXX lb Filtered, Recover Locked Out, Replace Filter Now? 150 lbs. of (68 kg) or more of refrigerant has been recovered since the last filter-drier change. Replace filter-drier to continue Recovery. Vacuum Pump Oil Time XX:XX, Change Oil? The vacuum pump has run for 10 or more hours without an oil change. Leak Test Failed A leak was detected. Ensure that a thorough recovery and evacuation of the system is performed. Page 49 EEAC325A Service Manual Diagnostics SERVICE INSTRUCTIONS & CALIBRATION Replacement Compressor (RA20020) Specifications & Service Specifications Compressor Fittings Make: Voltage: Capacity (BTU/HR): Running Amps: Speed: Locked Rotor Amps: Oil Charge Capacity: Refrigerants: POE Oil Type: Weight w/oil: Replacements: 1/3 HP Cubigel 115V / 60Hz 5821 8.4A 3500 RPM 30.0A Initial - 13.5 oz Recharge - 11.8 oz R-12, 22, 500, 502, 134a 404a ISO 22 23.8 lbs. 110V - RA20020 Oil Return (Intake) Suction Discharge Adding Oil to Compressor Troubleshooting Compressor Due to the configuration of the Cubigel suction and discharge fittings, there is no easy method of checking or removing oil from the compressor. Compressor Will Not Run The following procedure is the recommended method for changing oil in the Cubigel compressor: 1. Connect a refrigerant supply tank to one of the compressor’s suction ports. 2. Connect a portable recovery unit to the other suction port. 3. Cap the discharge port on the compressor. 4. Run the recovery unit to completely flush all oil from the compressor. 5. Disconnect everything and add 13.5 oz. of new oil (ISO 22) to the compressor. Page 50 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace Effective 09/2007 EEAC325A Service Manual Diagnostics the compressor. If the compressor is cool and drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 6. Perform functional check and recalibrate unit. 6. Shut off the compressor. The suction and discharge values should hold for 30 seconds to one minute. If not, proceed to step-7, then repeat test. If no improvement, replace the compressor. 7. If the compressor has weak suction or discharge, check the oil level and add oil if necessary. If the oil level is okay or oil was added with no improvement, replace the compressor. Removing the Compressor 1. Disconnect the unit from its power source. 2. Remove the left side oil bottle from the unit. 3. Remove the left side panel. Suction and Discharge Pressure Test 4. Depressurize the unit. 1. Disconnect all fittings from the compressor. 5. Disconnect the copper line from the compressor. 2. Cap the intake fitting. 3. Install a low side gauge on the suction fitting. The fitting used on the suction port is a 3/8” compression fitting. Use the appropriate fitting with an R-134a manifold set. 6. Disconnect the two black tubes from the compressor. 7. Remove and save the four nuts and bolts that secure the compressor into the unit. 8. Disconnect the wires from the main wire harness. 4. Install a high pressure gauge on the discharge fitting. The fittings used on the discharge port require an o-ring fitting to seal. Use a 120063 hose (1/4” flare o-ring X 1/2” ACME Q.S.) with an R-134a manifold set. 5. Start the compressor and monitor the readings. The discharge pressure should build to 250 psi (17.24 bar). The compressor should pull a 25” (.85 bar) vacuum. Effective 09/2007 9. Remove the compressor from the unit. 10. Remove the compressor electrical box cover by releasing the spring clamp that holds it on. 11. Disconnect the wires from the electrical components. Capacitor may still be energized; remove wires with caution. Page 51 EEAC325A Service Manual Diagnostics Replacement Compressor (RA20020) Specifications & Service (continued) 12. Disconnect the two black tubes from the main block, and discard. RETAINER COMP. ELEC. BOX Installing the Replacement Compressor (Refer to Figures 1 & 2 during this installation) PROTECTOR RELAY 1. Install the four rubber mounts (included in kit) into the base of the compressor. 2. Install the electrical components. SCREW CAPACITOR LEADS 3. Connect wiring to the compressor electrical components as shown in Figure 1. CAPACITOR 4. Install the compressor electrical box cover, and secure with the existing spring clamp. Figure 1 – Compressor Wiring 5. Place the compressor into the unit. 6. Place one steel sleeve (included in kit) into each of the four rubber mounts in the base of the compressor. Manifold Assembly 7. Secure the compressor into place with the existing four nuts and bolts. 15” 8. Reconnect the compressor to the wire harness. 9. With the o-rings in place, connect the copper line to the discharge side of the unit. 10. Refer to Figure 2 and replace the two black tubes that connect the compressor to the main block (use tubing from kit RA20005 and ferrules from kit RA20006). 11. Plug unit into power source, perform a function test, and check for any leaks. 12. Replace all shrouding and oil bottle. Page 52 12” Compressor 538469 2X 105358 Use Loctite® 242 or equivalent on threads Figure 2 – Compressor Tubing Connections Effective 09/2007 EEAC325A Service Manual Diagnostics Replacement Vacuum Pump (RA20017) Specifications & Service Specifications Make: Volts: Frequency: Running Amps: Locked Rotor Amps: Flow Rate: Oil Capacity: Oil Type: 1/3 HP 2-Stage Pump 110V 60Hz 4.5 A Call Tech Support 3 cfm 7.4 oz - 219 ml Premium Vacuum Pump Oil Vacuum Pump Not Running 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Check for 110V at the vacuum pump connector, pins 2 and 3 (see figure below). • If voltage is present, replace vacuum pump assembly. • If voltage is not present, continue to next step. 4. Check for 110 volts from the relay board on connector J6, pins 1 and 2. • If voltage is present, check wiring between the relay board and the vacuum pump. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 5. Perform functional check and recalibrate unit. Removing the Vacuum Pump 1. Disconnect the unit from its power source. 2. Remove right side oil bottle. 3. Remove hood and right side panel. 4. Depressurize the unit. 5. Remove the two existing nylon lines from the vacuum pump. 6. Remove and save the bolts that fasten the vacuum pump to the unit. 7. Disconnect the vacuum pump connector from the main harness. 8. Remove the vacuum pump from the unit. Installing the Replacement Vacuum Pump 1. Insert the new vacuum pump into the unit. 2. Secure the vacuum pump to the unit with the bolts saved from the old pump. 3. Connect the electrical connector from the vacuum pump into the unit’s main harness. 4. Reconnect the two existing nylon lines. 5. Remove the brass plug from the vacuum pump oil fill port. 6. Add 5 oz. of oil to the vacuum pump. 7. Plug unit into power source, and perform the steps to start the vacuum pump. 8. While the vacuum pump is running, add more oil to the correct fill level in the sight gauge. 9. Replace the brass plug in the fill port. 10. Perform a function test, and check for any leaks. 11. Replace all shrouding and oil bottle. BLACK HOT NEUT GND WHITE FILL PORT GREEN SIGHTGLASS Vacuum Pump Assembly Effective 09/2007 DRAIN Page 53 EEAC325A Service Manual Diagnostics Replacement High Pressure Cut-Out Switch (RA19427) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. The high pressure cut-out is a normally closed sensor designed to shut off the unit if the discharge pressure reaches 435 ± 10 psi. The switch will reset and close at 320 ± 20 psi. The pressure is detected through an orifice in the base of the sensor. In the normal setting (less than 435 psi on the orifice), the 1 and 3 contacts are closed. When 435 psi is introduced to the orifice, the pressure forces up on the drive pin, which then forces the center contact to disengage the 1 and 3 contacts and engage the 1 and 2 contacts. When this happens, the unit halts operation and displays a high pressure warning on the display. Brown Wire Brown Wire Replacement Instructions Follow these steps to replace the high pressure cut-out switch on your unit. 1. Close the tank valves and depressurize the unit. 2. Turn off the MAIN POWER switch, and unplug the unit from the power source. 3. Remove the panel(s) or shroud to access the manifold block. 4. Disconnect the wires from the high pressure cutout switch. 5. Carefully remove the high pressure cut-out switch. 6. Clean the fitting by wiping away dirt, grease, and oil. Apply thread sealant to only the external pipe threads of the fittings. DO NOT apply thread sealant to any internal threads. Thread sealant contains ADHHM-128 anaerobic adhesive and methacrylic ester. If there is skin contact with the sealant, thoroughly was the skin with soap and water. 7. 8. 9. 10. 11. 12. Install the new high pressure cut-out switch. Reconnect the wires to the new switch. Plug the unit into the power source. Open the tank valves. Operate the unit and check for leaks. Replace the panel(s) or shroud. Troubleshooting the High Pressure Cut-Out High Pressure Cut-Out discontinues operation prematurely. 1. Verify that there are no discharge obstructions. 2. Replace the high pressure cut-out. High Pressure Cut-Out Switch Page 54 High Pressure CutOut does not discontinue operation of unit at or below designed pressure. 1. Check the wiring. 2. Replace the high pressure cut-out. Effective 09/2007 EEAC325A Service Manual Diagnostics Replacement Scale Assembly/Magnet (RA20002) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. If scale assembly and UL circuit are not calibrated, scale can overfill the tank, causing possible explosion and/or vehicle overcharge. Instructions These instructions outline the steps to replace the scale assembly. Removing the Scale Assembly 1. Disconnect the unit from its power source. 2. Remove the right side oil bottle from the unit. 3. Remove the hood and right side panel. 4. Close all three (3) tank valves. 5. Depressurize the unit. 6. Disconnect the liquid hose and vapor hose from the tank. 7. Disconnect the wires from the air purge solenoid, tank temperature probe, and pressure transducer. 8. Remove the two (2) bolts that secure the tank to the scale. 9. Remove the tank from the scale. 10. Remove the four (4) nuts that hold the scale in place. 11. Remove the ground wire connected to the center divider of the unit and the harness connected to the relay board. Effective 09/2007 Installing the Replacement Scale Assembly 1. Connect the ground wire from the scale to the center divider. 2. Install the scale into the unit and secure with four (4) nuts. 3. Thread wire through the center panel, and connect to the relay board. 4. Connect the unit to its power source. 5. Turn the unit on to begin calibration steps. Perform the calibration steps outlined on page63 under section “Installing the Replacement Relay Board.” 6. Install the tank on the scale, and secure with two (2) bolts. 7. Reconnect the air purge solenoid, tank temperature probe, and pressure transducer wires. 8. Reconnect the liquid hose and vapor hose to the tank. 9. Open all three (3) tank valves. 10. Perform a function test, and check for leaks. 11. Replace all shrouding and oil bottle. Page 55 EEAC325A Service Manual Diagnostics Replacement Manifold Block (RA20018) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Removing the Manifold Block 1. Disconnect the unit from its power source. 15. Remove the bolt located between the two solenoids on the top right side. 16. Remove the liquid, vapor, and tank fill hoses from the block and save. Installing the Replacement Manifold Block (Refer to Figures 1 & 2 during this installation) 1. Install the existing liquid, vapor, and tank fill hoses into the new block. 2. Install the existing bolt into the hole between the two solenoids on the top right side. 2. Remove the left side oil bottle from the unit. 3. Install the existing bolt into the hole in the left corner under the block. 3. Remove the hood and left side panel. 4. Reconnect all wiring as shown in Figure 1. 4. Close all three tank valves. 5. Reconnect the vacuum and vacuum bypass lines using new ferrules (use ferrules from kit RA20007). 5. Depressurize the unit. 7. Disconnect the three lines from the compressor. 6. Install a new tube for the oil drain line, and connect to the oil drain solenoid (use RA20005 tubing kit [cut to length], and ferrules from kit RA20006). 8. Disconnect the compressor oil return tube from the block and discard. 7. Install a new tube for the compressor suction tube, and connect it to the block. 9. Disconnect the compressor suction tube from the block and discard. 8. Reconnect the existing compressor discharge line to the block. 10. Remove the compressor discharge line from the block and save. 9. Reconnect the existing three lines to the compressor. 11. Disconnect the oil drain line from the oil drain solenoid. 10. Reconnect the existing tank liquid and vapor hoses to the block. 12. Disconnect the vacuum and vacuum bypass lines. 11. Open all three tank valves. 13. Disconnect all wires from the block. 12. Plug unit into power source, perform a function test, and check for any leaks. 14. Remove the bolt located in the left corner under the block. 13. Replace all shrouding and oil bottle. 6. Disconnect the tank liquid and vapor hoses from the tank. Page 56 Effective 09/2007 EEAC325A Service Manual Diagnostics Figure 1 – Electrical Connections to Manifold Block Connection Label Harness 539992 RB8 HPS 539991 COMP 64 66 76 539989 RB10 GND (2x) PUMP FAN FAN (2x) COMP 539990 RB9 RB6 CB (2x) GND 74 75 539994 RB7 PSJ1 PSJ2 539927 RB11 RB13 S1 S2 S5 S6 S10 S11 S15 539987 RB14 S3 S4 S7 S8 S9 S12 S13 S14 539993 GND 25 539988 RB1 Effective 09/2007 Connection Relay Board J4 High Pressure Switch PT20 S5 S6 S7 S10 S3 S12 S1 539989 Comp Comp Start Relay Compressor Thermal Compressor Ground Relay Board J6 Unit Ground Stud Vacuum Pump Pigtail Fan Ground Fan Terminals 539991 Comp S11 S2 S4 Relay Board J3 Relay Board J1 Circuit Breaker Unit Ground Stud Power Switch Terminal 1 Power Switch Terminal 2 PT21 S9 S8 Manifold Assembly (Top View) HPS Relay Board J2 Power Supply J1 Power Supply J2 Relay Board J18 Relay Board J17 Normal Discharge Solenoid High Side Clear Solenoid High Side Charge Solenoid Low Side Charge Solenoid Recover Solenoid Tank Fill Solenoid Air Purge Solenoid Relay Board J11 Oil Inject Solenoid Deep Recover Solenoid High Side Inlet Solenoid Vacuum Solenoid Low Side Inlet Solenoid Power Charge Solenoid Oil Return Solenoid Oil Drain Solenoid S13 S14 Manifold Assembly (Front View) Unit Ground Stud Power Cord Bracket Relay Board J7 All wires must be clear of moving parts, pinch points, and sharp edges. Page 57 Page 58 BLUE SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT RED SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT USE LOCTITE 242 OR EQUIVALENT ON THREADS BLUE TUBE FROM LOW SIDE GAUGE BLACK TANK FILL HOSE ROUTE THROUGH HOLE IN SIDE SUPPORT RED TUBE FROM HIGH SIDE GAUGE USE LOCTITE 242 OR EQUIVALENT ON THREADS USE LOCTITE 242 OR EQUIVALENT ON THREADS CUT END OF TUBE AT 45° AND INSERT TO BOTTOM OF BOTTLE. CABLE TIE TUBE TO HOLE IN VACUUM PUMP SHELF TAB WITH (1) 535876 USE LOCTITE 242 OR EQUIVALENT ON THREADS USE LOCTITE 242 OR EQUIVALENT ON THREADS VACUUM PUMP EXHAUST SHOULD PROTRUDE APPROX. 1.5” INTO OIL DRAIN BOTTLE CABLE TIE TUBES TO HOLE IN VACUUM PUMP SHELF TAB WITH (1) 535876. EEAC325A Service Manual Diagnostics Replacement Manifold Block (RA20018) (continued) Figure 2 – Plumbing Connections to Manifold Block Effective 09/2007 EEAC325A Service Manual Diagnostics Replacement Manifold Solenoid (RA20010) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the existing manifold solenoid. Installing the Replacement Manifold Solenoid 1. Lubricate the o-rings and threads on the new solenoid assembly. 2. Install the new solenoid assembly into the main block and hand-tighten. 3. Using a torque wrench, tighten the solenoid assembly to a torque of 75 in. lbs. (±5 in. lbs.). 4. Install the new coil on the new solenoid assembly, and secure with the fastener that holds the coil in place. 5. Using a torque wrench, tighten the coil retaining bolt to a torque of 30 in. lbs. (±5 in. lbs.). Removing the Manifold Solenoid 1. Disconnect the unit from its power source. 6. Reconnect the wires that were disconnected when removing the old solenoid assembly. 2. Remove the left side oil bottle from the unit. 3. Remove the hood and left side panel. 7. Plug unit into power source, perform a function test, and check for any leaks. 4. Depressurize the unit. 8. Replace the shrouding and oil bottle. 5. Disconnect the two wires connected to the solenoid that is being replaced. 6. Remove the fastener that holds the coil on the solenoid, and remove the coil. 7. Remove the solenoid assembly from the manifold block. 8. Check the manifold block for any debris before beginning the installation of a new solenoid. Effective 09/2007 Page 59 EEAC325A Service Manual Diagnostics Replacement Display Board (RA20012) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the existing display board. Removing the Display Board 1. 2. 3. 4. 5. Disconnect the unit from its power source. Remove the four (4) bolts securing the hood. Remove the hood. Remove the oil inject bottle. Remove the two (2) screws securing the right-side panel. 6. Remove right-side panel. 7. Disconnect all wires from the display board. 8. Remove the four (4) screws securing the display board in place. Installing the Replacement Display Board 1. Install the display board, and secure with four (4) screws. 2. Connect all wires as shown in diagram on following page. 3. Connect unit to its power source. 4. Turn the unit on to begin calibration steps. 5. Press the UP or DOWN arrow key to move the cursor to SETUP. Page 60 6. Press the LEFT arrow key (ENTER) to confirm selection. 7. Press the UP or DOWN arrow key to move the cursor to SERVICE MENU. 8. Press the LEFT arrow key (ENTER) to confirm selection. 9. Press the UP or DOWN arrow key until the number “2” is shown in the first of four places on the display. 10. Press the LEFT arrow key (ENTER) to confirm selection. 11. Press the UP or DOWN arrow key until the number “2” is shown in the second of four places on the display. 12. Press the LEFT arrow key (ENTER) to confirm selection. 13. Press the UP or DOWN arrow key until the number “0” is shown in the third of four places on the display. 14. Press the LEFT arrow key (ENTER) to confirm selection. 15. Press the UP or DOWN arrow key until the number “0” is shown in the forth of four places on the display. 16. Display should show “2200.” 17. Press the LEFT arrow key (ENTER) to confirm selection. 18. From the SERVICE MENU, press the UP arrow key until “Calibrate Tank Scale” is displayed on the screen. 19. Press the LEFT arrow key (ENTER) to confirm selection. 20. Close all three (3) tank valves. 21. Depressurize the unit. 22. Disconnect the liquid hose and vapor hose from the tank. 23. Disconnect the wires from the air purge solenoid, tank temperature probe, and pressure transducer. 24. Remove the two (2) bolts that secure the tank in place. continued . . . Effective 09/2007 EEAC325A Service Manual Diagnostics Installing the Replacement Display Board — Continued 25. Remove the tank from the scale, and verify there is no weight on the scale or anything interfering with the scale. 26. Press the LEFT arrow key (ENTER) to begin calibration. 27. Place 20 pounds on the scale when prompted; then, press (START). 28. When “Calibrate Tank Scale” appears, press the UP arrow key to “UL Calibration.” 29. Press the LEFT arrow key (START). 30. Place 43 pounds on the scale if using a Worthington tank, or 45 pounds if using an Aircom tank. 31. Press the LEFT arrow key (ENTER) to continue. 32. Wait while the unit calibrates the UL circuit and stops. 33. Remove 2 pounds when the unit prompts you. 34. When the unit shows “UL Calibration Complete,’ press the RIGHT arrow key (CANCEL) twice to return to MAIN MENU. 35. Place the tank on the scale, and secure with two (2) bolts. 36. Reconnect the tank temperature probe, air purge solenoid, and pressure transducer wires. 37. Reconnect the liquid hose and vapor hose to the tank. 38. Open all three (3) tank valves. 39. Perform a function test, and check for leaks. 40. Replace all shrouding and oil bottle. Display Board Wiring Diagram Effective 09/2007 Page 61 EEAC325A Service Manual Diagnostics Replacement Relay Board (RA20013) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Removing the Relay Board 1. Disconnect the unit from its power source. 2. Remove the right side oil bottle from the unit. 3. Remove the hood and right side panel. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. 4. Disconnect all wires from the relay board. 5. Remove the screws that secure the relay board in place. Instructions These instructions outline the steps to replace the relay board. Relay Board Wiring Diagram Page 62 Effective 09/2007 Diagnostics EEAC325A Service Manual Installing the Replacement Relay Board 1. Install the new relay board, and secure in place with screws. 2. Connect all wires as shown in diagram on previous page. 3. Connect the unit to its power source. 4. Turn the unit on to begin calibration steps. 5. Press the UP or DOWN arrow key to move the cursor to SETUP. 6. Press the LEFT arrow key (ENTER) to confirm selection. 7. Press the UP or DOWN arrow key to move the cursor to SERVICE MENU. 8. Press the LEFT arrow key (ENTER) to confirm selection. 9. Press the UP or DOWN arrow key until the number “2” is shown in the first of four places on the display. 10. Press the LEFT arrow key (ENTER) to confirm selection. 11. Press the UP or DOWN arrow key until the number “2” is shown in the second of four places on the display. 12. Press the LEFT arrow key (ENTER) to confirm selection. 13. Press the UP or DOWN arrow key until the number “0” is shown in the third of four places on the display. 14. Press the LEFT arrow key (ENTER) to confirm selection. 15. Press the UP or DOWN arrow key until the number “0” is shown in the forth of four places on the display. 16. Display should show “2200.” 17. Press the LEFT arrow key (ENTER) to confirm selection. 18. From the SERVICE MENU, press the UP arrow key until “Calibrate Tank Scale” is displayed on the screen. Effective 09/2007 19. Press the LEFT arrow key (ENTER) to confirm selection. 20. Close all three (3) tank valves. 21. Depressurize the unit. 22. Disconnect the liquid hose and vapor hose from the tank. 23. Disconnect the wires from the air purge solenoid, tank temperature probe, and pressure transducer. 24. Remove the two (2) bolts that secure the tank in place. 25. Remove the tank from the scale, and verify there is no weight on the scale or anything interfering with the scale. 26. Press the LEFT arrow key (ENTER) to begin calibration. 27. Place 20 pounds on the scale when prompted; then, press (START). 28. When “Calibrate Tank Scale” appears, press the UP arrow key to “UL Calibration.” 29. Press the LEFT arrow key (START). 30. Place 43 pounds on the scale if using a Worthington tank, or 45 pounds if using an Aircom tank. 31. Press the LEFT arrow key (ENTER) to continue. 32. Wait while the unit calibrates the UL circuit and stops. 33. Remove 2 pounds when the unit prompts you. 34. When the unit shows “UL Calibration Complete,’ press the RIGHT arrow key (CANCEL) twice to return to MAIN MENU. 35. Place the tank on the scale, and secure with two (2) bolts. 36. Reconnect the tank temperature probe, air purge solenoid, and pressure transducer wires. 37. Reconnect the liquid hose and vapor hose to the tank. 38. Open all three (3) tank valves. 39. Perform a function test, and check for leaks. 40. Replace all shrouding and oil bottle. Page 63 EEAC325A Service Manual Diagnostics Replacement Vacuum Relief Check Valve (RA20015) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the existing vacuum relief check valve. Removing the Vacuum Relief Check Valve 1. Disconnect the unit from its power source. Installing the Replacement Vacuum Relief Check Valve Use a thread sealant that is compatible with refrigerants such as Loctite® 565 or equivalent. 1. Install the compression fitting into the discharge side of the new check valve. 2. Install the check valve onto the tee fitting that is connected to the main block. 3. Connect the nylon line that was removed from the old vacuum relief check valve. 4. Plug unit into power source, perform a function test, and check for any leaks. 5. Replace all shrouding and oil bottle. 2. Remove the left side oil bottle. 3. Remove the hood and left side panel. 4. Depressurize the unit. 5. Remove the nylon line from the fitting connected to the check valve. Main Block 6. Remove the check valve connected to the tee fitting. 7. Remove the compression fitting from the check valve. Tee Fitting Vacuum Relief Check Valve (Note direction of flow arrow) Vacuum Relief Check Valve Location Page 64 Effective 09/2007 Diagnostics EEAC325A Service Manual Replacement Manifold Check Valve (RA20016) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Installing the Replacement Manifold Check Valve 1. Lubricate the o-rings on the new check valve. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. 2. Install the new check valve into the main block and hand-tighten. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. 3. Using a torque wrench, tighten the check valve to a torque of 75 in. lbs. (±5 in. lbs.). 4. Plug unit into power source, perform a function test, and check for any leaks. Instructions These instructions outline the steps to replace the existing check valve manifold. 5. Replace all shrouding and oil bottle. Removing the Manifold Check Valve 1. Disconnect the unit from its power source. 2. Remove the left side oil bottle. 3. Remove the hood and left side panel. 4. Depressurize the unit. 5. Remove the existing manifold check valve that needs to be replaced. Effective 09/2007 Page 65 EEAC325A Service Manual Diagnostics Replacement 3/8” High Pressure Tube (RA20005) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the three black 3/8” high pressure tubes. To prevent personal injury and/or equipment damage, always replace tubing that has been removed from the compressor. The process of installing and removing the tubes can stress them, causing them to leak or fail. 1. Depressurize unit. 2. Disconnect and discard the old tube and ferrule nuts. 3. Using the old tube as a guide, cut a piece of new tubing the same length. 4. With new ferrule nuts (from kit RA20006), install the new tube into the unit. Tighten the nuts until no leaks are detected. Page 66 Effective 09/2007 J9 Keyboard J11 SD Card PCB J1 Display/Control PCB Development Use Only Scale Ass’y S15-Air Purge Temp Probe Future Use J2 539988 539927 539988 539995 Power Switch J1 Relay PCB J2 Circuit Breaker Power Supply 34788 INTERCONNECT DIAGRAM 539990 Air Purge Trans 539996 539990 539994 539988 539988 ISV Ass’y 539927 539927 539987 539989 Effective 09/2007 122770 539992 539991 Fan Compressor Vacuum Pump HP Switch S1-N Discharge S2-HS Clear S5-HS Charge S6-LS Charge S10-Recover S11-Tank Fill S3-Oil Inject S4-Dp Recover S7-HS Inlet S8-Vacuum S9-LS Inlet S12-Pwr Charge S13-Oil Return S14-Oil Drain Low-Side Trans Accum Trans Manifold Ass’y Diagnostics EEAC325A Service Manual SYSTEM WIRING Page 67 EEAC325A Service Manual Diagnostics COMPONENT WIRING 3A CIRCUIT BREAKER FAN SCALE ASSEMBLY POWER CORD BRACKET ISV ASSEMBLY CB 15 AMP CIRCUIT BREAKER MAIN POWER SWITCH Page 68 EEAC325A CHASSIS Effective 09/2007 Diagnostics EEAC325A Service Manual RETAINER COMP. ELEC. BOX PROTECTOR RELAY SCREW PUMP CAPACITOR LEADS CAPACITOR VACUUM PUMP ASSEMBLY COMPRESSOR Future Use DB2 Development Use Only Keyboard DB1 DISPLAY/CONTROL BOARD RELAY BOARD SD SLOT (SD2) SD1 SD ADAPTER BOARD Effective 09/2007 POWER SUPPLY Page 69 EEAC325A Service Manual Diagnostics MANIFOLD BLOCK ASSEMBLY – TOP VIEW MANIFOLD BLOCK ASSEMBLY – FRONT VIEW Page 70 Effective 09/2007 EEAC325A Service Manual Diagnostics WIRING HARNESSES Relay Board Connector Pin-outs The following chart describes the pinouts for each connector on the relay board. The connector descriptions are: J1from power switch, J2-to 12 volt power supply, J3-to circuit breaker, J4-to high pressure switch, J5-to display/control board, J6-to vacuum pump, compressor, and fan, J7-to low-side transducer, J8-to temperature probe, J11-to manifold solenoids, J13-to accumulator transducer, J14- to air pressure transducer, J16-to scale assembly, J17-to manifold solenoids, J18-to normal discharge solenoid. Conn Pin1 Pin2 Pin3 J1 Earth Ground AC Neutral in AC Line in Pin4 J2 AC 110V to 12VPS Neutral to 12VPS Earth Ground 12V from 12VPS DC GND J3 Circuit Breaker Circuit Breaker 12V fuse 12V fuse J4 HP Switch HP Switch J5 Ground SPI SPI SPI J6 110V Output Pump Neutral Pump 110V Output Comp Neutral Comp J7 5V to LS Xducer Output from Xducer Ground J8 Temp Probe Temp Probe J11 Pwr Charge Sol Vacuum Sol J13 5V to Acc Xducer Output from Xducer Ground J14 5V to AP Xducer Output from Xducer Ground J16 Exc V to scale Diff out from scale Diff out from scale Ground J17 Tank Fill Sol Recover Sol LS Charge Sol HS Charge Sol J18 Norm Discharge Sol Aux Aux Aux LS Inlet Sol HS Inlet Sol Pin5 SPI Pin6 Pin7 Pin8 Deep Rec Sol Oil Inject Sol 12V to Ctrl Board 110V Output Fan Neutral Fan Oil Return Sol Oil Drain Sol Air Purge Sol HS Clear Sol AC Power Cord (122770) AC POWER CORD (122770) CONNECTOR # 71 72 73 Effective 09/2007 CONNECTS TO: Main Pow er SW1 - 2A Main Ground Stud Main Pow er SW1 - 1A Page 71 Manifold 1 Harness (539927) Page 72 CONNECTS TO: J-17 Relay Board J-18 Relay Board Solenoid - S1 (Tan Wires) Solenoid - S2 (Black Wires) Solenoid - S5 (Orange Wires) Solenoid - S6 (Purple Wires) Solenoid - S10 (Yellow Wires) Solenoid - S11 (Pink Wires) Solenoid - S15 (Gray Wires) MANIFOLD 1 WIRE HARNESS (539927) CONNECTOR # RB13 RB11 S1 S2 S5 S6 S10 S11 S15 EEAC325A Service Manual Diagnostics Manifold 1 Harness (539927) Effective 09/2007 Manifold 2 Harness (539987) Effective 09/2007 CONNECTOR # RB14 S3 S4 S7 S8 S9 S12 S13 S14 CONNECTS TO: J-11 Relay Board Solenoid - S3 (Blue Wires) Solenoid - S4 (Light Blue Wires) Solenoid - S7 (Yellow Wires) Solenoid - S8 (Red Wires) Solenoid - S9 (Gray Wires) Solenoid - S12 (White Wires) Solenoid - S13 (Purple Wires) Solenoid - S14 (Orange Wires) MANIFOLD 2 WIRE HARNESS (539987) Diagnostics EEAC325A Service Manual Manifold 2 Harness (539987) Page 73 Transducer Wire Harness (539988) Page 74 CONNECTOR # RB1 RB2 RB3 RB4 TS PT20 PT21 PT22 CONNECTS TO: J-7 Relay Board J-13 Relay Board J-14 Relay Board J-8 Relay Board Temperature Probe - ISV Low -Side Transducer - Manifold Accum Transducer - Manifold Air Purge Transducer - ISV TRANSDUCER WIRE HARNESS (539988) Detail A EEAC325A Service Manual Diagnostics Transducer Wire Harness (539988) Effective 09/2007 Effective 09/2007 Light Blue Brown Green/Yellow Brown Compressor/Fan Wire Harness (539989) Dark Blue Dark Blue CONNECTOR # RB10 COMP FAN FAN GND PUMP GND Green/Yellow CONNECTS TO: J-6 Relay Board To Compress Harness (539991) Fan Fan Ground Vacuum Pump Assembly Chassis Ground Brown Green/Yellow COMPRESSOR/FAN WIRE HARNESS (539989) Diagnostics EEAC325A Service Manual Compressor/Fan Wire Harness (539989) Page 75 Page 76 Brown Brown Green/Yellow Power Wire Harness (539990) Light Blue Brown CONNECTS TO: J-3 Relay Board J-1 Relay Board 15A Circuit Breaker Ground Pow er Sw itch #1 Pow er Sw itch #2 POWER WIRE HARNESS (539990) CONNECTOR # RB9 RB6 CB GRN 74 75 EEAC325A Service Manual Diagnostics Power Wire Harness (539990) Effective 09/2007 Effective 09/2007 Brown Compressor Pigtail Wire Harness (539991) CONNECTS TO: To Compressor/Fan Wire Harness (539989) Compressor Relay Compressor Protector Compressor Ground Green/Yellow Blue CONNECTOR # COMP 64 66 76 COMPRESSOR/FAN WIRE HARNESS (539991) Diagnostics EEAC325A Service Manual Compressor Pigtail Wire Harness (539991) Page 77 High Pressure Cutout Harness (539992) Page 78 Brown CONNECTOR # CONNECTS TO: RB8 J-4 Relay Board HPS High Pressure Cutout Sw itch - Manifold HIGH PRESSURE CUTOUT SWITCH (539992) EEAC325A Service Manual Diagnostics High Pressure Cutout Harness (539992) Effective 09/2007 Effective 09/2007 Gray Brown Power Supply Harness (539994) Red CONNECTOR # RB7 PSJ1 PSJ2 CONNECTS TO: J-2 Relay Board J-1 Pow er Supply J-2 Pow er Supply Blue POWER SUPPLY HARNESS (539994) Diagnostics EEAC325A Service Manual Power Supply Harness (539994) Page 79 Diagnostics EEAC325A Service Manual Interconnect Cable (539995) INTERCONNECT CABLE (539995) CONNECTOR # CONNECTS TO: RB12 J-5 Relay Board DB1 J-9 Display/Control Board SD Board Cable (539996) SD BOARD CABLE (539996) CONNECTOR # CONNECTS TO: DB2 J-11 Display/Control Board SD1 J-1 SD Card Board SD1 Page 80 DB2 Effective 09/2007 Diagnostics EEAC325A Service Manual Ground Wire Harness (539993) GROUND WIRE HARNESS (539993) CONNECTOR # CONNECTS TO: 25 Pow er Cord Bracket GND Chassis Ground Green/Yellow Capacitor Lead (516844) CAPACITOR LEAD (516844) CONNECTOR # CONNECTS TO: A Compressor Relay (1 or 2) B Compressor Capacitor A B Black Effective 09/2007 Fully Insulated Terminal Page 81 EEAC325A Service Manual Diagnostics COMPONENT IDENTIFICATION MANIFOLD BLOCK ASSEMBLY - TOP LOW SIDE TRANSDUCER HIGH-SIDE INLET LOW-SIDE SOLENOID CHARGE SOLENOID HIGH-SIDE CHARGE SOLENOID OIL INJECT SOLENOID NORMAL DISCHARGE SOLENOID S7 S3 S5 S6 S1 PT20 HIGH-SIDE CLEAR SOLENOID S2 S10 S8 POWER CHARGE SOLENOID S12 S11 S9 S4 RECOVER SOLENOID VACUUM SOLENOID PT21 HIGH PRESSURE SWITCH TANK FILL SOLENOID DEEP RECOVER SOLENOID LOW-SIDE INLET SOLENOID ACCUM TRANSDUCER AIR PURGE SOLENOID HIGH PRESSURE SWITCH UPPER BLOCK LOWER BLOCK AIR PURGE PRESSURE TRANSDUCER S15 TEMPERATURE PROBE HPS 4 PSI RELIEF FOR VACUUM PUMP COMPRESSOR OIL SEPARATOR SYSTEM OIL SEPARATOR OIL RETURN SOLENOID ISV S13 FILTER DRIER OIL DRAIN SOLENOID S14 MANIFOLD BLOCK ASSEMBLY - FRONT Page 82 ISV ASSEMBLY Effective 09/2007 Diagnostics EEAC325A Service Manual COMPONENT APPLICATION CHART Component Application Chart Norm al Discharge Solenoid (1) Tank Fill Recover ON ON Air Purge Clearing Vacuum Leak Test Inject Oil Charge / Pw r Charge* I High-Side Clear Solenoid (2) I I* Oil Inject Solenoid (3) ON Deep Recover Solenoid (4) I High-Side Charge Solenoid (5) P Low -Side Charge Solenoid (6) P High-Side Inlet Solenoid (7) ON ON Vacuum Solenoid (8) I ON Low -Side Inlet Solenoid (9) ON ON Recover Solenoid (10) I Tank Fill Solenoid (11) I Oil Return Solenoid (13) I Oil Drain Solenoid (14) I Air Purge Solenoid (15) I* I ON I Vacuum Pum p ON Com pressor ON ON ON Fan ON ON ON Effective 09/2007 ON I Pow er Charge Solenoid (12) ON ON I* ON I ON Intermittently P User Programmed * Charge/Power Charge Note: If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stop to build tank pressure. Page 83 External Tank Tank Fill Solenoid Tank Fill Checkvalve Page 84 TANK FILL During the Tank Fill process the compressor, fan, normal discharge, and tank fill solenoid are activated. The output state of the tank fill solenoid is controlled to maintain 35 psi in the accumulator. When the ISV reaches the “target” weight, all components are deactivated. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid EEAC325A Service Manual Diagnostics FLOW DIAGRAMS Tank Fill Effective 09/2007 External Tank Tank Fill Solenoid Tank Fill Checkvalve Effective 09/2007 RECOVERY PROCESS During the first stage of the recovery process, the fan, compressor, normal discharge, recover, HS and LS inlet solenoids are activated. During the second stage of the recover process, the vacuum pump, vacuum, deep recover, and power charge solenoids are activated and the recover solenoid is deactivated. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid Diagnostics EEAC325A Service Manual Recover Page 85 Page 86 Tank Fill Checkvalve AIR PURGE The air purge solenoid is activated to release excess pressure from the internal storage vessel. The air purge usually follows the Recover process. ENERGIZED Vacuum Solenoid Oil Inject Bottle Vacuum Pump Oil Return Solenoid Compressor Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE Recover Solenoid Oil Drain Solenoid Filter Drier HS Clearing Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator High Pressure Switch Normal Discharge Checkvalve Air Purge SUCTION External Tank Tank Fill Solenoid Accum Transducer Power Charge Solenoid EEAC325A Service Manual Diagnostics Air Purge Effective 09/2007 External Tank Tank Fill Solenoid Tank Fill Checkvalve Effective 09/2007 CLEARING PROCESS During the first stage of the clearing process the normal discharge solenoid and compressor are activated. The second stage of clearing deactivates the normal discharge solenoid and activates the HS clear and oil return solenoids. When the accumulator transducer reads less than 9 inHG, all outputs are deactivated. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid Diagnostics EEAC325A Service Manual Clearing Page 87 External Tank Tank Fill Solenoid Tank Fill Checkvalve Page 88 VACUUM PROCESS The default vacuum time is 10:00 minutes. When the vacuum process begins, the vacuum pump is activated. After a 5 second delay, the vacuum, HS and LS inlet solenoids are also activated. When the Low-Side transducer reads > 10 psi, you will be prompted to end the vacuum process. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clearing Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid EEAC325A Service Manual Diagnostics Vacuum Effective 09/2007 Effective 09/2007 Tank Fill Checkvalve LEAK TEST PROCESS High-Side inlet and Low-Side inlet solenoids are activated to equalize high and low sides of system being serviced. Unit checks low-side transducer for rise in vacuum. (This is not a service menu test.) ENERGIZED Vacuum Solenoid Oil Inject Bottle Vacuum Pump Oil Return Solenoid Compressor Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT Recover Solenoid Oil Drain Solenoid Filter Drier HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator High Pressure Switch Normal Discharge Checkvalve Air Purge PRESSURE External Tank Tank Fill Solenoid Accum Transducer Power Charge Solenoid Diagnostics EEAC325A Service Manual Leak Test Page 89 Page 90 Tank Fill Checkvalve INJECT OIL The inject oil button must be depressed to activate the oil inject solenoid. Release the button to deactivate the solenoid. The system being serviced must have a vacuum to pull oil from the oil inject bottle. ENERGIZED Vacuum Solenoid Oil Inject Bottle Vacuum Pump Oil Return Solenoid Compressor Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE Recover Solenoid Oil Drain Solenoid Filter Drier HS Clearing Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator High Pressure Switch Normal Discharge Checkvalve Air Purge SUCTION External Tank Tank Fill Solenoid Accum Transducer Power Charge Solenoid EEAC325A Service Manual Diagnostics Inject Oil Effective 09/2007 Effective 09/2007 External Tank Tank Fill Solenoid Tank Fill Checkvalve CHARGE PROCESS During the Charge process, the end user may select either high-side charge, low-side charge, or both. When the charge process gets close to the programmed weight, the unit slows down. It’ll charge, settle, charge again, settle, etc. When the charge process is complete, user must equalize hoses. If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stop to build tank pressure. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Normal Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Power Charge Solenoid Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer NOTE: If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stops to build tank pressure. Diagnostics EEAC325A Service Manual Charge Page 91 EEAC325A Service Manual Page 92 Diagnostics Effective 09/2007 Service Bulletins EEAC325A Service Manual Section 4 - Service Bulletins Place all service bulletins for the KoolKare Plus +™ EEAC325A in this section Effective 09/2007 Page 93 EEAC325A Service Manual Page 94 Service Bulletins Effective 09/2007 Snap-on Technical Support: (866) 769-2788 TECHNICAL SERVICE BULLETIN RA19950 Reservoir Installation Kit SUBJECT: EQUIP. AFFECTED: 3 CFM Station Pump ACTION REQUIRED: Informational HARDWARE NO: 00201-SN DATE: Nov., 2006 AUTHOR: S. Parde 3 CFM Station Pump Part Numbers RA19902 — Complete Station Pump, 115V, 60Hz 527849 — Complete Station Pump, 230V, 50Hz RA19950 — Reservoir Installation Kit (includes removal and assembly instructions) THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. Snap-on Technical Support: (866) 769-2788 TECHNICAL SERVICE BULLETIN INFORMATION New Air Com Internal Storage Vessel (ISV) SUBJECT: EQUIP. AFFECTED: Snap-on EEAC325A unit ACTION REQUIRED: Informational NO: 00203-SN DATE: July, 2007 AUTHOR: S. Parde Overview A new Internal Storage Vessel (ISV) has been approved for use in the Snap-on EEAC325A unit, which is identified as “Air Com.” For the time being, either the new Air Com ISV or the Worthington ISV can be used in the EEAC325A unit. However, there are some differences between the two ISV’s that should be noted to properly set UL and scale calibrations. Refer to tank specifications listed below and be sure you identify the proper tank and use the corresponding specs to calibrate the unit. AIR COM ISV “New” WORTHINGTON ISV Tag says “Certified by “Air Com Co. Ltd.” Port ID label has a border around its edges Tank Tare = 20.50 lbs. (9.30 kg.) UL Calibration Wt. = 45 lbs. (20.4 kg.) Tag says “Certified by WORTHJ” Port ID label has no border around its edges Tank Tare = 17.50 lbs. (7.94 kg.) UL Calibration Wt. = 43 lbs. (19.5 kg.) Figure 1 - Air Com Tank Tag Figure 2 - Worthington Tank Tag CERTIFIED BY AIR COM CO. LTD. CERTIFIED BY WORTHJ Please note this information in the Snap-on EEAC325A service manual, or download the updated service manual from the Service Center website. THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. Snap-on Technical Support: (866) 769-2788 TECHNICAL SERVICE BULLETIN HARDWARE Internal Storage Vessel (ISV) Assembly Parts SUBJECT: EQUIP. AFFECTED: Snap-on EEAC325A unit ACTION REQUIRED: Informational NO: 00204-SN DATE: Aug., 2007 AUTHOR: S. Parde Overview Engineering has recently approved a new Internal Storage Vessel (ISV) for use in the Snap-on EEAC325A unit, which is identified as “Air Com.” For the time being, either the new Air Com ISV or the Worthington ISV can be used in the EEAC325A unit. The part numbers shown in the listing below are compatible for both Air Com and Worthington tanks. If the tank itself is ordered (539477), you will receive the new Air Com tank. 3 4 5 9 10 8 11 2 7 12 6 13 1 ISV ASSEMBLY Use Loctite 565 on all pipe threads. Tank Tare Weight: Worthington: 17.50 lbs. (7.94 kg.) Air Com: 20.50 lbs. (9.30 kg.) No. 1 2 3 4 5 6 7 8 9 10 11 12 13 Description ISV, INTERNAL FITTING, STRAIGHT SOLENOID, 12V DC DISCRETE VALVE, BALL, AIR PURGE VALVE, BALL, LIQUID PRESSURE RELIEF, 450PSI FITTING, TEE, .25FP X .25FP X .25MP VALVE, BALL, VAPOR TEMPERATURE PROBE TRANSDUCER, AIR PURGE TEE, MALE BRANCH 1/8 NPTF ORIFICE, UNION .026 MUFFLER, AIR EXHAUST THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. Qty 1 1 1 1 1 1 1 1 1 1 1 1 1 Part No. 539477 210312 RA20009 539799 539798 RA19499 508690 540322 539472 539229 539654 539804 519605 Snap-on Technical Support: (866) 769-2788 TECHNICAL SERVICE BULLETIN INFORMATION Display Board Wiring Diagram Error SUBJECT: EQUIP. AFFECTED: Snap-on EEAC325A unit ACTION REQUIRED: Informational NO: 00205-SN DATE: Aug., 2007 AUTHOR: S. Parde EEAC325A Service Manual The Display Board (RA20012) wiring diagram print located on page 61 of the Snap-on EEAC325A service manual is incorrect. Please refer to the print below for correct wiring orientation. Please note these changes in the Snap-on EEAC325A service manual. Display Board Wiring Diagram THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. Snap-on Technical Support: (866) 769-2788 TECHNICAL SERVICE BULLETIN INFORMATION Part Number Corrections (Hoses) SUBJECT: EQUIP. AFFECTED: Snap-on EEAC325A unit ACTION REQUIRED: Informational NO: 00206-SN DATE: Aug., 2007 AUTHOR: S. Parde EEAC325A Service Manual A couple of errors have been noted on the “Plumbing Diagram Parts List,” which is located on page 25 of the Snap-on EEAC325A service manual. The corrected parts list is provided below, which includes updated numbers for the Low Side Service Hose, High Side Service Hose, and the Tank Fill Hose. These corrections have also been applied to pages 29 and 30 of the Alphabetical Parts section. Please note these changes in the Snap-on EEAC325A service manual. Plumbing Diagram Parts List No. Description Qty. Part No. 1 HOSE, LOW SIDE SERVICE 1 EEAC325A3 2 HOSE, HIGH SIDE SERVICE 1 EEAC325A2 3 TUBE, 1/4 OD X 0.040 ID 19" 120225 4 TUBE, 3/8" HIGH PRESSURE 16" RA20005 5 HOSE, LIQUID 1 541627 6 HOSE, VAPOR 1 541626 7 TUBE, 1/4 OD X 0.040 ID 28" 120225 8 HOSE, TANK FILL 1 541625 9 TUBE, 1/4 OD X 0.040 ID 42" 120225 10 TUBE, 3/8" HIGH PRESSURE 15" RA20005 11 TUBE, COMPRESSOR TO MANIFOLD 1 538469 12 TUBE, 3/8" HIGH PRESSURE 12" RA20005 13 TUBE, NYLON 1/8 OD X .070 ID 42" 121773 14 NUT, COMPRESSION (3/8 TUBE) 2 RA20006 15 O'RING (PKR #5-124) NEOPRENE 2 RA19916 16 NUT, COMPRESSION (1/4 TUBE) 1 RA20007 THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. EEAC325A Service Manual Page 100 Service Bulletins Effective 09/2007 Labor Rates EEAC325A Service Manual Section 5 - Labor Rates Snap-on authorizes a labor charge of 1-1/2 hours to troubleshoot and complete a full function test on units that are covered under factory warranty (including leak testing). The authorized time for parts replacement is 15 minutes per part. Some items require an additional amount of time to facilitate installation. These items and their times are listed below. If repairs are estimated to exceed two (2) hours, prior authorization from Snap-on is required. Part Number Component Total Time RA20018 RA20020 RA20017 Manifold Assembly Compressor Assembly Vacuum Pump Assembly 60 minutes 30 minutes 30 minutes Snap-on considers filters to be a consumable item; they are not covered under warranty. This includes parts and labor. Effective 09/2007 Page 101 EEAC325A Service Manual Page 102 Labor Rates Effective 09/2007 Product Warranty EEAC325A Service Manual Section 6 - Product Warranty Snap-on Tools Company Limited One (1) Year Warranty Snap-on Tools Company (the “Seller”) warrants only to the original purchaser that under normal use, care and service, the Equipment (except as otherwise provided herein) shall be free from defects in material and workmanship for one year from the date of original invoice. Items such as leads, probes, external hoses, adapters and all other attachments, supplies and consumables (except as otherwise provided herein) are warranted for 90 calendar days from the date of original invoice. Filter elements are not warranted. SELLER’S OBLIGATIONS UNDER THIS WARRANTY ARE LIMITED SOLELY TO THE REPAIR OR, AT SELLER’S OPTION, REPLACEMENT OF EQUIPMENT OR PARTS WHICH TO SELLER’S SATISFACTION ARE DETERMINED TO BE DEFECTIVE AND WHICH ARE NECESSARY, IN SELLER’S JUDGEMENT, TO RETURN THIS EQUIPMENT TO GOOD OPERATING CONDITION. NO OTHER WARRANTIES, EXPRESS OR IMPLIED OR STATUTORY, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, SHALL APPLY AND ALL SUCH WARRANTIES ARE HEREBY EXPRESSLY DISCLAIMED. This Warranty does not cover (and separate charges for parts, labor and related expenses shall apply to) any damage to, malfunctioning, inoperability or improper operation of the Equipment caused by, resulting from or attributable to (A) abuse, misuse or tampering; (B) alteration, modification or adjustment of the Equipment by other than Seller’s authorized representatives; (C) installation, repair or maintenance (other than specified operator maintenance) of the Equipment or related equipment, attachments, peripherals or optional features by other than Seller’s authorized representatives; (D) improper or negligent use, application, operation, care, cleaning, storage or handling; (E) fire, water, wind, lightning or other natural causes; (F) adverse environmental conditions, including, without limitation, excessive heat, moisture, corrosive elements, dust or other air contaminants, radio frequency interference, electric power failure, power line voltages beyond those specified for the Equipment, unusual physical, electrical or electromagnetic stress and/or any other condition outside of Seller’s environmental specifications; (G) use of the Equipment in combination or connection with other equipment, attachments, supplies or consumables not manufactured or supplied by Seller; or (H) failure to comply with any applicable federal, state or local regulation, requirement or specification governing emission analyzers and related supplies or consumables. Repairs or replacements qualifying under this Warranty will be performed on regular business days during Seller’s normal working hours within a reasonable time following purchaser’s request. All requests for Warranty service must be made during the stated Warranty period. This Warranty is nontransferable. Snap-on Tools Company Kenosha, Wisconsin 53141-1410 Effective 09/2007 Page 103 KoolKare Plus +™ EEAC325A Rev. C (09/2007) Printed in U.S.A.