UPS2000-G-3KRTLL User Manual

advertisement
UPS2000-G-3KRTLL
User Manual
Issue
02
Date
2021-06-30
HUAWEI TECHNOLOGIES CO., LTD.
Copyright © Huawei Technologies Co., Ltd. 2022. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website:
https://e.huawei.com
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
i
UPS2000-G-3KRTLL
User Manual
About This Document
About This Document
Purpose
This document describes the UPS2000-G-3KRTLL in terms of features,
performance, appearance, structure, working principle, installation, operation, and
maintenance.
NOTE
● The UPS applies only to commercial and industrial use, rather than medical facilities and
life support equipment.
● Figures provided in this document are for reference only.
Intended Audience
This document is intended for:
●
Technical support engineers
●
Hardware installation engineers
●
Commissioning engineers
●
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Indicates a hazard with a high level of risk
which, if not avoided, will result in death or
serious injury.
Indicates a hazard with a medium level of
risk which, if not avoided, could result in
death or serious injury.
Indicates a hazard with a low level of risk
which, if not avoided, could result in minor
or moderate injury.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
ii
UPS2000-G-3KRTLL
User Manual
About This Document
Symbol
Description
Indicates a potentially hazardous situation
which, if not avoided, could result in
equipment damage, data loss, performance
deterioration, or unanticipated results.
NOTICE is used to address practices not
related to personal injury.
Supplements the important information in
the main text.
NOTE is used to address information not
related to personal injury, equipment
damage, and environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue
contains all updates made in previous issues.
Issue
Date
Description
02
2022-06-30
Added figures for installing PE cables. For
details, see "Installation."
01
2020-10-26
The issue is the first official release.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
iii
UPS2000-G-3KRTLL
User Manual
Contents
Contents
About This Document................................................................................................................ ii
1 Safety Information.................................................................................................................. 1
1.1 Personal Safety.........................................................................................................................................................................2
1.2 Equipment Safety.................................................................................................................................................................... 3
1.2.1 UPS Safety.............................................................................................................................................................................. 3
1.2.2 Battery Safety........................................................................................................................................................................ 5
1.3 Electrical Safety........................................................................................................................................................................ 8
1.4 Environmental Requirements........................................................................................................................................... 10
1.5 Mechanical Safety.................................................................................................................................................................11
2 System Composition............................................................................................................. 12
2.1 Model Description................................................................................................................................................................ 12
2.2 Working Principle.................................................................................................................................................................. 13
2.3 Product Structure.................................................................................................................................................................. 13
2.4 Communication Ports.......................................................................................................................................................... 14
2.5 Battery Module...................................................................................................................................................................... 16
3 Installation..............................................................................................................................21
3.1 Installation Preparations.................................................................................................................................................... 21
3.2 Tools.......................................................................................................................................................................................... 22
3.3 Installing a UPS..................................................................................................................................................................... 26
3.4 Preparing Power Cables...................................................................................................................................................... 28
3.5 Installing Cables for a Single UPS................................................................................................................................... 28
3.6 Installing Cables for Parallel UPSs.................................................................................................................................. 32
3.7 Installing Communications Cables.................................................................................................................................. 36
3.8 Verifying the Installation.................................................................................................................................................... 38
4 Control Panel..........................................................................................................................40
4.1 LCD Introduction................................................................................................................................................................... 40
4.1.1 LCD......................................................................................................................................................................................... 40
4.1.2 Buttons.................................................................................................................................................................................. 43
4.1.3 LCD Screen Information.................................................................................................................................................. 44
4.2 LCD Character Display......................................................................................................................................................... 46
4.3 Parameter Settings............................................................................................................................................................... 48
4.4 Operating Modes.................................................................................................................................................................. 56
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
iv
UPS2000-G-3KRTLL
User Manual
Contents
4.5 Alarm Types............................................................................................................................................................................ 59
4.5.1 Critical Alarms.................................................................................................................................................................... 59
4.5.2 Minor Alarms...................................................................................................................................................................... 61
4.6 Alarm Handling..................................................................................................................................................................... 63
5 Operations.............................................................................................................................. 93
5.1 Checking Before Power-On................................................................................................................................................93
5.2 Single UPS Operations........................................................................................................................................................ 93
5.2.1 Starting a UPS.................................................................................................................................................................... 93
5.2.1.1 Start the UPS Using Mains Power............................................................................................................................ 94
5.2.1.2 Cold-Starting the UPS Using Batteries................................................................................................................... 96
5.2.2 Shutting Down a UPS...................................................................................................................................................... 98
5.2.3 Performing EPO..................................................................................................................................................................98
5.3 Parallel System Operations............................................................................................................................................... 99
5.3.1 Starting a Parallel System.............................................................................................................................................. 99
5.3.1.1 Start the UPSs Using Mains Power.......................................................................................................................... 99
5.3.1.2 Cold-Starting the UPSs Using Batteries............................................................................................................... 101
5.3.2 Shutting Down a Parallel System.............................................................................................................................. 102
5.3.3 Performing EPO............................................................................................................................................................... 103
6 UPS Maintenance................................................................................................................ 104
7 Technical Specifications..................................................................................................... 106
7.1 Physical Specifications...................................................................................................................................................... 106
7.2 Environmental Specifications......................................................................................................................................... 106
7.3 Mains Input Electrical Specifications........................................................................................................................... 107
7.4 Bypass Input Electrical Specifications.......................................................................................................................... 107
7.5 Output Electrical Specifications..................................................................................................................................... 108
7.6 Battery Electrical Specifications..................................................................................................................................... 109
7.7 ECO Specifications.............................................................................................................................................................. 110
7.8 Parallel System Specifications........................................................................................................................................ 111
7.9 Safety and EMC................................................................................................................................................................... 111
A Acronyms and Abbreviations........................................................................................... 113
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
v
UPS2000-G-3KRTLL
User Manual
1 Safety Information
1
Safety Information
Statement
Before installing, operating, and maintaining the equipment, read this document
and observe all the safety instructions on the equipment and in this document.
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this
document do not cover all the safety instructions. They are only supplements to
the safety instructions. The Company will not be liable for any consequence
caused by the violation of general safety requirements or design, production, and
usage safety standards.
Ensure that the equipment is used in environments that meet its design
specifications. Otherwise, the equipment may become faulty, and the resulting
equipment malfunction, component damage, personal injuries, or property
damage will not be covered under the warranty.
Follow local laws and regulations when installing, operating, or maintaining the
equipment. The safety instructions in this document are only supplements to local
laws and regulations.
The Company will not be liable for any consequences of the following
circumstances:
●
Operation beyond the conditions specified in this document
●
Installation or use in environments which are not specified in relevant
international or national standards
●
Unauthorized modifications to the product or software code or removal of the
product
●
Failure to follow the operation instructions and safety precautions on the
product and in this document
●
Equipment damage due to force majeure, such as earthquakes, fire, and
storms
●
Damage caused during transportation by the customer
●
Storage conditions that do not meet the requirements specified in this
document
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
1
UPS2000-G-3KRTLL
User Manual
1 Safety Information
1.1 Personal Safety
DANGER
Do not work with power on during installation. Do not install or remove a power
cable with power on. Transient contact between the core of the power cable and
the conductor will generate electric arcs or sparks, which may cause a fire or
personal injury.
DANGER
Before installing, operating, or maintaining the equipment, remove conductive
objects such as watches, bracelets, bangles, rings, and necklaces to prevent electric
shocks.
DANGER
When installing, operating, or maintaining the equipment, use dedicated insulated
tools to prevent electric shocks and short circuits.
WARNING
When installing, operating, or maintaining the equipment, wear personal
protective equipment (PPE) such as insulated gloves, safety clothing, goggles,
safety helmet, and safety shoes.
General Requirements
●
Do not stop protective devices. Pay attention to the warnings, cautions, and
precautionary measures on the equipment.
●
If there is a likelihood of personal injury or equipment damage during
operations, immediately stop, report the case to the supervisor, and take
feasible protective measures.
●
Do not power on the equipment before it is installed or confirmed by
professionals.
●
Before handling a conductor surface or terminal, measure the contact point
voltage and ensure that there is no risk of electric shock.
●
Do not touch a running fan with your fingers, components, screws, tools, or
boards before the fan is powered off or stops running.
●
In the case of a fire, immediately leave the building or the equipment area
and activate the fire alarm or call emergency services. Do not re-enter the
building or affected area until it has been deemed safe by qualified
professionals.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
2
UPS2000-G-3KRTLL
User Manual
1 Safety Information
Personnel Requirements
●
Only professionals and trained personnel are allowed to operate the
equipment.
–
Professionals: personnel who are familiar with the working principles and
structure of the equipment, trained or experienced in equipment
operations and are clear of the sources and degree of various potential
hazards in equipment installation, operation, maintenance
–
Trained personnel: personnel who are trained in technology and safety,
have required experience, are aware of possible hazards on themselves in
certain operations, and are able to take protective measures to minimize
the hazards on themselves and other people
●
Personnel who plan to install or maintain the equipment must receive
thorough training, understand all necessary safety precautions, and be able to
correctly perform all operations.
●
Only qualified professionals or trained personnel are allowed to install,
operate, and maintain the equipment.
●
Only qualified professionals are allowed to remove safety facilities and inspect
the equipment.
●
Personnel who will perform special tasks such as electrical operations,
working at heights, and operations of special equipment should possess the
required local national qualifications.
●
Only authorized professionals are allowed to replace the equipment or
components (including software).
●
Keep irrelevant people away from the equipment. Only operators are allowed
to access the equipment.
1.2 Equipment Safety
1.2.1 UPS Safety
DANGER
During installation, operation, and maintenance, prevent foreign matter from
entering the UPS. Otherwise, equipment damage, load power derating, power
failure, or personal injury may occur.
NOTICE
The category C2 UPS may cause radio interference when used in a residential
environment. Additional measures may be needed to prevent the interference.
General Requirements
●
Issue 02 (2021-06-30)
The UPS is used for commercial and industrial purposes only. It cannot be
used as a power supply for life support devices.
Copyright © Huawei Technologies Co., Ltd.
3
UPS2000-G-3KRTLL
User Manual
1 Safety Information
●
For power supply systems that are critical to significant economic interests or
public order, such as the national computing center, military command
system, emergency command center, railway signal system and control center,
civil aviation and air traffic control center, airport command center, financial
clearing center, and transaction center, the Tier 4 or 3 power architecture
specified in TIA-942 must be used. That is, two power supplies must be used
to supply power to loads.
●
If the root mean square (RMS) of the mains voltage exceeds 320 V AC, the
UPS may be damaged.
●
A UPS can be used to serve resistive-capacitive loads, resistive loads, and
micro-inductive loads. It is recommended that a UPS not be used for pure
capacitive loads, pure inductive loads, and half-wave rectification loads. A UPS
does not apply to regeneration loads.
●
The UPS can be configured with a backfeed protection dry contact to work
with an external automatic circuit breaker, preventing the voltage from
flowing back to input terminals over static bypass circuits. If the installation
and maintenance personnel do not need backfeed protection, paste labels on
external mains and bypass input switches, informing that the UPS is
connected to a backfeed protection card. Disconnect the backfeed protection
card from the UPS before operating the UPS.
Environmental Requirements
●
The UPS operating environment must meet the requirements for the climate
indicator, mechanically active substance indicator, and chemically active
substance indicator in ETSI EN 300 019-1 class 3.6.
●
Ensure that the equipment is used in an environment that meets the product
design specifications (including power grid, temperature, and humidity).
Otherwise, the equipment may become faulty, and the resulting equipment
malfunction and component damage are not covered under the warranty.
●
After unpacking the UPS, you are advised to power it on as soon as possible.
If the UPS is not in operation, take appropriate measures to prevent moisture,
dust, and foreign matter from entering the UPS.
●
Any operation on any electrical equipment in an environment that has
inflammable air can cause extreme danger. Strictly obey the operating
environmental requirements specified in related user manuals when using or
storing the equipment.
●
Do not use the UPS in the following places:
Issue 02 (2021-06-30)
–
Environments that are close to flammable or explosive materials, dust,
corrosive gases or dust, conductive or magnetic dust, abnormal vibration,
or collision
–
Rooms or outdoor environments where temperature and humidity are
not controlled (with high temperature, low temperature, moisture, direct
sunlight, or heat sources)
–
Non-confined environments near the ocean (0–3.7 km) and indoor or
semi-indoor environments where the temperature and humidity are not
controllable, such as simple equipment rooms, civil houses, garages,
corridors, and direct ventilation cabinets near the ocean; or houses with
only roofs, railway station platforms, gymnasiums, and aquariums
–
Environments that are conducive for the growth of microorganisms such
as fungus or mildew
Copyright © Huawei Technologies Co., Ltd.
4
UPS2000-G-3KRTLL
User Manual
1 Safety Information
–
Environments where rodents (such as mice) and insects exist
1.2.2 Battery Safety
Before installing, operating, or maintaining batteries, read the battery
manufacturer's instructions. Observe the safety precautions provided in this
document which are supplemental to the safety instructions provided by the
battery manufacturer.
DANGER
Do not short-circuit the positive and negative poles of batteries. Battery short
circuits can generate high instantaneous current, which may cause battery
leakage, overheating, fire, or explosion. To avoid battery short circuit, do not
maintain batteries with power on.
DANGER
Do not expose batteries at high temperatures or around heat-generating sources,
such as high-temperature sunlight, fires, transformers, and heaters. Battery
overheating caused by external heat sources may cause vent opening, leakage,
fire, or explosions.
DANGER
Protect battery modules from mechanical vibration, collision, punctures, and
strong impact. Otherwise, the modules may catch fire.
DANGER
To avoid leakage, overheating, fire, or explosions, do not disassemble, alter, or
damage batteries, for example, insert sundries into batteries, squeeze batteries, or
immerse batteries in water or other liquids.
DANGER
Do not burn batteries. Otherwise, the batteries may catch fire or explode.
DANGER
There is a risk of explosion if the model of the replaced battery is incorrect. The
battery should be replaced with a battery of the model recommended by the
manufacturer.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
5
UPS2000-G-3KRTLL
User Manual
1 Safety Information
WARNING
It is recommended that an independent battery room be used. Before installing
battery modules, prepare fire extinguishing facilities, such as firefighting sands
and liquid carbon dioxide fire extinguishers, according to the construction
regulations. Before operation, ensure that the battery room is equipped with a fire
extinguishing system that complies with local regulations.
WARNING
Before unpacking battery modules, ensure that the packing cases are intact and
correctly placed according to the labels on the packing cases during their storage
and transportation. Do not place a battery module upside down, lay it on one side,
or tilt it. Stack the battery modules according to the stacking requirements on the
packing cases. Any bumping or falling may damage the battery modules.
WARNING
After unpacking battery modules, place them in the required direction. Do not
place a battery module upside down or vertically, lay it on one side, tilt it, or stack
it with other modules. Any bumping or falling may damage the battery modules.
WARNING
Install the equipment in an area far away from liquids. Do not install it under
areas prone to condensation, such as under water pipes and air exhaust vents, or
areas prone to water leakage, such as air conditioner vents, ventilation vents, or
feeder windows of the equipment room. Ensure that no liquid enters the
equipment to prevent faults or short circuits.
CAUTION
● Battery modules should be used soon after being deployed. For battery
modules that have been stored for an extended period, recharge them
periodically according to the instructions for battery module recharge.
Otherwise, the battery modules may be damaged.
● After the battery system is installed, fully charge batteries (the SOC reaches
100%) and then put them into use. Exercise caution to replace a battery
module unless it is faulty.
● If the battery system is powered off for installation or commissioning or
batteries are not charged in time after discharge, recharge the battery cabinet
in time by referring to the instructions for recharging batteries with low SOC.
Otherwise, batteries may be damaged due to overdischarge.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
6
UPS2000-G-3KRTLL
User Manual
1 Safety Information
General Requirements
●
If a battery is accidentally exposed to water, do not install it. Move it to a safe
place for isolation and contact technical engineers in a timely manner.
●
Keep the battery switch off during installation and maintenance.
●
When installing batteries, do not place installation tools on the batteries.
After the installation is complete, clean up the objects on the batteries and
the surrounding area.
●
Use batteries of specified models. Using batteries of other models may
damage the batteries.
●
Note the polarities when installing batteries. Do not short-circuit the positive
and negative poles of the same battery or battery string. Otherwise, the
battery may be short-circuited.
●
Exercise caution when setting battery parameters. Incorrect settings will affect
the power supply and battery lifespan.
●
Do not charge a battery when the ambient temperature is below the lower
limit of the operating temperature (charging is forbidden at 0°C). Lowtemperature charging may cause crystallization, which will result in a short
circuit inside the battery.
●
Dispose of waste batteries in accordance with local laws and regulations. Do
not dispose of batteries as household waste. If a battery is disposed of
improperly, it may explode.
NOTICE
To ensure battery safety and battery management accuracy, use batteries provided
by the Company. The Company is not responsible for any battery faults caused by
batteries not provided by it.
Battery Leakage
●
If a battery leaks, wear goggles, rubber gloves, and protective clothing, power
off the equipment in a timely manner, remove the leaking battery module
from the cabinet, and contact technical support.
●
If a battery overflows, protect the skin or eyes from the leaking liquid. If the
skin or eyes come in contact with the leaking liquid, wash it immediately with
clean water and go to the hospital for medical treatment.
Flammable Gas
●
A battery module is an enclosed battery system and will not release any gases
under normal operations.
●
If a battery module is improperly treated, for example, burnt, needle-pricked,
squeezed, overcharged, or subject to other adverse conditions that may cause
battery thermal runaway, the battery may be damaged or an abnormal
chemical reaction may occur inside the battery, resulting in electrolyte
leakage or production of gases such as CO2, CO, N2, and H2. To prevent fire or
corrosion, ensure that flammable gas (such as hydrogen) is properly
exhausted.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
7
UPS2000-G-3KRTLL
User Manual
1 Safety Information
1.3 Electrical Safety
General Requirements
●
Installation, operation, and maintenance must be performed in the sequence
specified in the manual. Do not change the structure or installation sequence
of the equipment without permission.
●
When installing the equipment, use a torque wrench with a proper range to
tighten the screws. When using a wrench to tighten the screws, ensure that
the wrench does not tilt and the torque error does not exceed 10% of the
specified value.
●
Before installing or removing power cables, ensure that the switch is turned
off.
●
If the equipment has multiple inputs, disconnect all the inputs before
operating the equipment.
●
Before connecting power cables, check that cable labels are correct and cable
terminals are insulated.
●
A circuit breaker equipped with a residual current device (RCD) is not
recommended.
●
It is recommended that the three-phase loads be equalized and the neutralground voltage be kept at less than 2 V to meet power distribution
requirements.
●
To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits
to telecommunication network voltage (TNV) circuits.
●
A damaged cable must be replaced by the manufacturer or professionals to
avoid risks.
●
Check equipment connections periodically, ensuring that all screws are
securely tightened.
●
Do not use water to clean electrical components inside or outside of a
cabinet.
●
Do not scrawl, damage, or block any labels or nameplates on the equipment.
Promptly replace warning labels that have worn out.
●
For the equipment that needs to be grounded, install the ground cable first
when installing the equipment and remove the ground cable last when
removing the equipment.
●
Ensure that the equipment is connected permanently to the protective
ground. Before operating the equipment, check its electrical connection to
ensure that it is reliably grounded.
●
If a "high electricity leakage" tag is attached on the equipment, ground the
protective ground terminal on the equipment enclosure before connecting the
AC input power supply; otherwise, electric shock as a result of electricity
leakage may occur.
●
Do not operate the equipment in the absence of a properly installed ground
conductor.
Grounding
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
8
UPS2000-G-3KRTLL
User Manual
1 Safety Information
●
Do not damage the ground conductor.
●
When selecting, connecting, and routing cables, follow local safety regulations
and rules.
●
The flame spread rating of cables should meet the UL 1581 VW-1 or IEC
60332-3-22 (ZB) or higher requirements.
●
Do not route cables behind the air intake or exhaust vents of the equipment.
●
If a cable is connected to the cabinet from the top, bend the cable in a U
shape outside the cabinet and then route it into the cabinet.
●
Bind cables of the same type together. When routing cables of different types,
ensure that they are at least 30 mm away from each other.
●
When routing cables, ensure that a distance of at least 30 mm exists between
the cables and heat-generating components or areas. This prevents damage
to the insulation layer of the cables.
●
When the temperature is low, violent impact or vibration may damage the
plastic cable sheathing. To ensure safety, comply with the following
requirements:
Cabling
●
–
Cables can be laid or installed only when the temperature is higher than
0°C. Handle cables with caution, especially at a low temperature.
–
Cables stored at subzero temperatures must be stored at room
temperature for at least 24 hours before they are laid out.
Do not perform any improper operations, for example, dropping cables
directly from a vehicle. Otherwise, the cable performance may deteriorate due
to cable damage, which affects the current-carrying capacity and temperature
rise.
ESD
NOTICE
The static electricity generated by human bodies may damage the electrostaticsensitive components on boards, for example, the large-scale integrated (LSI)
circuits.
●
Wear ESD gloves or a well-grounded ESD wrist strap when touching the
device or handling boards or application-specific integrated circuits (ASICs).
●
When holding a board, hold its edge without touching any components. Do
not touch the components with your bare hands.
●
Package boards with ESD packaging materials before storing or transporting
them.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
9
UPS2000-G-3KRTLL
User Manual
1 Safety Information
Figure 1-1 Wearing an ESD wrist strap
1.4 Environmental Requirements
WARNING
Install the equipment in an area far away from liquids. Do not install it under
areas prone to condensation, such as under water pipes and air exhaust vents, or
areas prone to water leakage, such as air conditioner vents, ventilation vents, or
feeder windows of the equipment room. Ensure that no liquid enters the
equipment to prevent faults or short circuits.
General Requirements
●
Do not install or run the equipment beyond the technical specifications.
Otherwise, its performance and safety will be compromised.
●
Do not install the equipment in environments with conductive metal scraps in
the air.
●
Do not install the equipment in an environment with direct sunlight, dust,
volatile gases, infrared and other radiations, organic solvents, corrosive
materials, or salty air.
●
Do not expose the equipment to flammable or explosive gas or smoke. Do
not perform any operation on the equipment in such environments.
●
Do not install, use, or operate outdoor equipment and cables (including but
not limited to moving equipment, operating equipment and cables, inserting
connectors to or removing connectors from signal ports connected to outdoor
facilities, working at heights, and performing outdoor installation) in harsh
weather conditions such as lightning, rain, snow, and level 6 or stronger wind.
●
If any liquid is detected inside the equipment, disconnect the power supply
immediately and contact the administrator.
●
To prevent fire due to high temperature, ensure that the ventilation vents or
heat dissipation system are not blocked when the equipment is running.
●
The equipment room should have good heat insulation, and the walls and
floor should be protected against moisture.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
10
UPS2000-G-3KRTLL
User Manual
1 Safety Information
●
Install a rat guard at the door of the equipment room.
●
All cable holes should be sealed. Seal the used cable holes with sealing putty.
Seal the unused cable holes with the caps delivered with the cabinet. The
following figure shows the criteria for correct sealing with sealing putty.
●
After installing the equipment, remove idle packing materials such as cartons,
foam, plastics, and cable ties from the equipment area.
1.5 Mechanical Safety
WARNING
When pulling equipment out of a cabinet, be aware of unstable or heavy objects
in the cabinet to prevent injury.
General Requirements
●
Repaint any paint scratches caused during equipment transportation or
installation in a timely manner. Equipment with scratches cannot be exposed
to an outdoor environment for an extended period of time.
●
Before installation, ensure that the equipment is firmly anchored to the floor
or other solid objects, such as a wall or an installation rack.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
11
UPS2000-G-3KRTLL
User Manual
2 System Composition
2
System Composition
2.1 Model Description
This document describes the following UPS model:
Table 2-1 UPS model
Model
Represented By
Remarks
UPS2000-G-3KRTLL
3kVA
This model is
abbreviated to a 3 kVA
UPS in this document.
Figure 2-1 UPS model number
Table 2-2 UPS model number details
No.
Meaning
Description
1
Product
category
UPS: uninterruptible power system
2
Product
family
2000
3
Product
series
G: series name
4
Output
capacity
3K: 3 kVA
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
12
UPS2000-G-3KRTLL
User Manual
2 System Composition
No.
Meaning
Description
5
UPS type
RT: rack-mounted or tower-mounted
6
Long
backup
time model
L: long backup time model, using external largecapacity batteries that provide long backup time
7
External
battery
type
L: LFP battery
2.2 Working Principle
Figure 2-2 Conceptual diagram
2.3 Product Structure
Figure 2-3 Front and rear views of a 3 kVA UPS
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
13
UPS2000-G-3KRTLL
User Manual
2 System Composition
(1) Liquid crystal display
(LCD)
(2) Maintenance bypass (MBS)
port
(3) Optional card
slot
(4) Battery
management system
(BMS) port
(5) RS232 communications
portb
(6) RS485
communications
ports (connect to
northbound
devices)
(7) USB porta
(8) AC input and output
terminals (behind the cover)
(9) Battery input
terminal (behind
the cover)
(10) Parallel current
equalization port
(11) Emergency power-off
(EPO) port
(12) Parallel
communication
ports
(13) Battery PE terminal
NOTE
● The RS485 port supports only the Modbus RTU protocol.
● The USB port and RS232 port cannot be used at the same time.
a: The USB port supports the serial port communication protocol. The USB port can be
used to export logs and send serial port commissioning commands.
b: The RS232 port supports the serial port communication protocol. The RS232 port can
be used to export logs, send serial port commissioning commands, and upgrade the UPS
main power program online.
2.4 Communication Ports
Figure 2-4 RS232 port pins
Table 2-3 RS232 port pin definitions
Pin
Meaning
1
Reserved pin
2
UPS transmit terminal for RS232
data communication
3
UPS receive terminal for RS232
data communication
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
14
UPS2000-G-3KRTLL
User Manual
2 System Composition
Pin
Meaning
4
Reserved pin
5
Common terminal for RS232 data
communication
6–9
Reserved pin
Figure 2-5 RS485/BMS port pins
Table 2-4 Pin definitions for the RS485 port
Pin
Signal
Meaning
Description
1–3
NC
Reserved pin
4
A
Data+
Northbound port, two-wire
RS485 communication
5
B
Data–
6
NC
Reserved pin
7
NC
Reserved pin
8
GND
Signal
ground
Supports the baud rate of 9600
bit/s.
Table 2-5 Pin definitions for the BMS port
Pin
Signal
Meaning
Description
1
A
Data+
2
B
Data–
3
NC
Reserved pin
4
A
Data+
Pins 1 and 4 are short-circuited;
pins 2 and 5 are short-circuited;
communicating with the lithium
battery
Supports the baud rate of 9600
bit/s.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
15
UPS2000-G-3KRTLL
User Manual
2 System Composition
Pin
Signal
Meaning
5
B
Data–
6
NC
Reserved pin
7
NC
Reserved pin
8
GND
Signal
ground
Description
2.5 Battery Module
The UPS uses 48 V lithium battery modules to provide backup power. The 3 kVA
UPS supports the ESM-4850A3, ESM-48100B1, and ESM-48150B1.
Figure 2-6 ESM-4850A3/ESM-48100B1/48150B1 panel and ports
Table 2-6 Port pin definitions
No.
Silk Screen
Name
Description
1
GND
Protective ground
M6 screw
2
DO1
ESM dry contact
output
Reserved.
1. The ports are used for
information reporting and
communication cascading.
DO2
3
COM_ IN
Communications
port
4
COM_ OUT
Communications
port
5
RUN
Running indicator
ALM
Alarm indicator
CHG
Charge indicator
Issue 02 (2021-06-30)
2. The ports use RJ45
terminals and provide the
1000 A surge protection
capability.
For details about indicator
functions, see the LED
indicator description.
Copyright © Huawei Technologies Co., Ltd.
16
UPS2000-G-3KRTLL
User Manual
2 System Composition
No.
Silk Screen
Name
Description
DCHG
Discharge
indicator
SOC
SOC indicator
6
MANUAL
ON/OFF
Button for
manual poweron/off
This is a contact button used
for manual power-on/off
and maintenance.
7
PWR
ESMU port for
connecting to an
external power
source
Reserved.
8
+
ESM positive
terminal
-
ESM negative
terminal
Positive and negative ports
of the ESM. They are secured
by M6 screws. Appropriate
OT terminals should be used.
The required torque is 4.5–
5.5 N·m and the
recommended cable size is
25 mm2. If the ESM is used
at a temperature below
45°C, the cable size can be
smaller but should be at
least 16 mm2.
LED Indicators
Figure 2-7 LED indicators
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
17
UPS2000-G-3KRTLL
User Manual
2 System Composition
Table 2-7 LED indicator description
Silk
Screen
Meaning
Color
Description
RUN
Running
indicator
Green
Steady on: Communication is normal
(including board startup, self-check,
software loading, and board power-on
when not loaded; excluding sleep
when the power port or activation port
is energized).
Steady off: The ESM is in sleep mode.
Blinking fast: Communication is
interrupted.
ALM
Fault
indicator
Red
Steady on: There is a fault or major
alarm.
Steady off: There is no fault or major
alarm.
CHG
DCHG
Charge
indicator
Green
Discharge
indicator
Green
Steady on: The ESM is being charged.
Steady off: The ESM is open-circuited
or discharging.
Steady on: The ESM is being
discharged.
Steady off: The ESM is open-circuited
or being charged.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
18
UPS2000-G-3KRTLL
User Manual
2 System Composition
Silk
Screen
Meaning
Color
Description
SOC
SOC
indicators
Green
1. 0–24% capacity
25% indicator: blinking
Other SOC indicators: off
2. 25%–49% capacity
25% indicator: steady on
50% indicator: blinking
Other SOC indicators: off
3. 50%–74% capacity
25% indicator: steady on
50% indicator: steady on
75% indicator: blinking
Other SOC indicators: off
4. 75%–99% capacity
25% indicator: steady on
50% indicator: steady on
75% indicator: steady on
100% indicator: blinking
5. 100% capacity
The four SOC indicators are steady on.
Note:
● Major alarm: The ESM needs to be maintained immediately.
● Minor alarm: The ESM does not require maintenance, but sends a reminder
to remote maintenance personnel.
● Blinking slowly: on for 1s and then off for 1s.
● Blinking fast: on for 0.125s and then off for 0.125s
● If the SOC indicators are off and other indicators are blinking, the ESM enters
the maintenance mode.
● When the ESM is in sleep mode, the fault indicator is off except for reverseconnection protection.
Activation and Startup
An ESM can be activated in the following two modes. After being activated, the
ESM switches from sleep mode to disconnected mode.
●
Activation through the MANUAL ON/OFF button: Hold down the MANUAL
ON/OFF button on the ESM panel for at least 5s and less than 15s.
●
Activation through the power port: Supply the DC input voltage of 43.2–58 V
(50 Ah), 43.2–58 V (100 Ah), or 43.2–59 V (150 Ah) to the power terminal on
the front panel for at least 5s.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
19
UPS2000-G-3KRTLL
User Manual
2 System Composition
NOTE
● The MANUAL ON/OFF button is a contact button. The interval for pressing the button
should be greater than 0.5s; otherwise, the operation is ineffective.
● If you have powered off the ESM that is in charging, discharging, or disconnected mode
by holding down the MANUAL ON/OFF button, you need to hold down this button
again to reactivate the ESM.
● If the UPS is configured with 48 V lithium batteries, other optional components and
independent communications with lithium batteries are not supported.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
20
UPS2000-G-3KRTLL
User Manual
3 Installation
3
Installation
3.1 Installation Preparations
Floor Loading Capacity
The floor can bear the weight of the UPS and its optional components. In the case
of rack-mounted installation, ensure that the floor can also bear the weight of the
rack.
Installation Environment
●
Do not install the UPS in a high-temperature, low-temperature, or damp place
that is beyond the technical specifications.
●
Keep the UPS far away from water, heat sources, and flammable and
explosive substances. Install the UPS in an environment free of dust, volatile
gas, salt, and corrosive materials. Avoid direct sunlight.
●
Do not install the UPS in environments with conductive metal scraps in the
air.
●
The optimal operating temperatures for batteries are 20–30°C. Operating
temperatures higher than 30°C shorten the battery lifespan, and operating
temperatures lower than 20°C reduce the battery backup time.
Installation Clearances
Reserve a clearance of at least 500 mm from the front and rear of the chassis.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
21
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-1 Clearances
3.2 Tools
The onsite operation personnel can select tools based on the site requirements.
Personal protective equipment
Safety helmet
Goggles
Protective shoes
Reflective vest
ESD gloves
Insulated gloves
Protective gloves
Safety harness
-
-
-
Safety belt
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
22
UPS2000-G-3KRTLL
User Manual
3 Installation
Transportation tools
-
Manual pallet
truck
Lifting trolley
Flat-head
insulated torque
screwdriver
Phillips insulated
torque
screwdriver
Insulated torque
socket wrench
(M2.5)
(M4/M5/M6)
Electric forklift
Hardware installation tools
Adjustable torque
wrench
Including
extended sockets
(M8/M10/M12/
M16)
Hammer drill
Hammer drill bit
Claw hammer
Electric
screwdriver
Rubber mallet
Utility knife
(Φ16 mm)
Step ladder
Issue 02 (2021-06-30)
Pliers
Copyright © Huawei Technologies Co., Ltd.
23
UPS2000-G-3KRTLL
User Manual
3 Installation
Marker
-
-
Diagonal pliers
RJ45 crimping
tool
Rivet gun
Cable installation tools
Cable cutter
Wire stripper
-
Electro-hydraulic
pliers
Cord end terminal
crimping tool
Heat gun
Height gauge
Laser locator
Electroprobe
Thermometer
Clamp meter
Soft measuring
tape
Steel measuring
tape
Square
Measurement instruments
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
24
UPS2000-G-3KRTLL
User Manual
3 Installation
Level
Laptop
Level gauge
Multimeter
-
Network tester
Phase sequence
meter
Dielectric strength
tester
Machinery
-
Small cutter
Cable reel
Insulation
megohmmeter
Engineering auxiliary materials
Label
Cable tie
Heat-shrink
tubing
Issue 02 (2021-06-30)
Cotton cloth
Sandpaper
-
-
Insulation tape
Copyright © Huawei Technologies Co., Ltd.
25
UPS2000-G-3KRTLL
User Manual
3 Installation
Other tools
Electrician's knife
Hacksaw
Powder marker
Glue gun
Brush
Paint brush
Vacuum cleaner
Flashlight
-
-
-
Hole saw
3.3 Installing a UPS
Rack-Mounting a UPS
NOTE
● Reserve a space of 1 U between the UPS and batteries for routing battery power cables.
● Reserve a space of 50 mm between the battery communications port and the cabinet
for installing a communications cable.
● Reserve a space of 44 mm between the battery edge and the rack edge for installing
battery power cables.
● In rack-mounted installation scenarios, the front panels of the UPS and lithium batteries
are not on the same plane.
1.
Install the mounting ears on both sides of the UPS.
2.
Install the guide rails on the rack, and then install the UPSs and batteries with
mounting ears on the rack.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
26
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-2 Rack-mounted installation (two UPSs and two lithium batteries)
Figure 3-3 UPS mounting ear dimensions (unit: mm)
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
27
UPS2000-G-3KRTLL
User Manual
3 Installation
3.4 Preparing Power Cables
NOTICE
● You are advised to install a disconnector for the UPS input.
● A 2-pole disconnector must be used if the UPS is used to power IT systems.
● The UPS can generate large leakage currents. A circuit breaker equipped with a
residual current device (RCD) is not recommended. If leakage protection is
required, select a recommended circuit breaker.
● The leakage current of the 3 kVA UPS is less than 100 mA.
● When selecting an earth leakage circuit breaker, consider the leakage current of
the UPS and downstream loads.
● Battery cables should not be longer than 10 m.
● For the 3 kVA model, use the battery PE cable that has a cross-sectional area of
6 mm2 and 6 mm2 M4 OT terminals.
● The UPS battery input terminal has a voltage of 56 V 10 seconds before
batteries are connected.
Table 3-1 Recommended power cable specifications
Model
Wiring
Termina
l
Numb
er of
Phase
s
Rated Voltage
External
Circuit
Breaker
Cable
Crosssection
al Area
Terminal
Type
Torque
for
Tighteni
ng Bolts
3 kVA
AC input
and
output
1
220 V AC/230
V AC/240 V AC
16 A (type
D)
2.5
mm2
OT-6 mm2M5
terminal
2 N·m
Battery
input
-
48 V DC
63 A (type
D)
16 mm2
OT-16
mm2-M8
terminal
7 N·m
NOTE
● If customers purchase input and output power cables by themselves, use the cables that
comply with standards proposed by the Underwriters Laboratories (UL) or International
Electrotechnical Commission (IEC).
● When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
3.5 Installing Cables for a Single UPS
This section describes how to install cables for one UPS and two lithium batteries.
The actual situation may vary.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
28
UPS2000-G-3KRTLL
User Manual
3 Installation
Installing Power Cables
1.
Switch off the upstream AC circuit breaker for the UPS.
2.
Remove the AC input, AC output, and battery input terminal covers from the
UPS.
3.
Install AC output power cables, AC input power cables, and then battery input
cables in sequence.
Figure 3-4 AC input, AC output, and battery input wiring diagram
Installing Battery Cables
After lithium batteries are connected in parallel, connect signal cables to the BMS
ports on the UPS. Install a build-out resistor at the COM-OUT port on the last
lithium battery.
NOTE
● The UPS2000-G-3KRTLL needs to connect to external lithium batteries. Each UPS
supports a maximum of eight batteries connected in parallel. This document uses two
lithium batteries connected in parallel as an example.
● The maximum discharge current of a 50 Ah lithium battery is 4 kW.
● The maximum discharge current of a 100 Ah or 150 Ah lithium battery is 4.3 kW.
● When lithium batteries are connected, it is recommended that a DC circuit breaker (63 A
80 V DC circuit breaker for the 3 kVA UPS) be installed between the lithium batteries
and the UPS.
● Before connecting cables to the UPS, ensure that the battery circuit breakers are OFF to
prevent operations with power applied.
● If the UPS shares a battery string, the PE bar and battery busbar are configured.
● If the busbar terminals are insufficient, you can cascade busbars.
● Busbar dimensions (H x W x D): 76 mm x 465 mm x 70 mm
● In the wiring diagram, the busbar RTN+ connects to the battery BTA+, and the busbar –
48 V connects to the battery BAT-.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
29
UPS2000-G-3KRTLL
User Manual
3 Installation
CAUTION
● When installing a lithium battery power cable, ensure that the protruding part
of the OT terminal on the cable faces outwards.
● Do not connect two or more cables to the positive or negative power port of
the lithium batteries in parallel.
Figure 3-5 Installing battery power cables
Figure 3-6 Installing the battery PE cable
(1) Ground bar
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
30
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-7 Installing battery cables (rack-mounted, front view)
(1) Busbar
Figure 3-8 Installing battery cables (rack-mounted, rear view)
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
31
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-9 Busbar mounting hole dimensions (unit: mm)
3.6 Installing Cables for Parallel UPSs
NOTICE
● Before parallel running, ensure that all output circuit breakers for each UPS are
ON. Otherwise, a UPS fault (error code #72) will occur.
● Batteries must be connected for parallel running.
This section describes how to install cables for two UPSs and two lithium batteries.
The actual situation may vary.
Installing Power Cables
1.
Switch off the upstream AC circuit breaker for the UPS.
2.
Remove the AC input, AC output, and battery input terminal cover from each
UPS.
3.
Install AC output power cables, AC input power cables, and then battery input
cables in sequence.
Figure 3-10 AC input, AC output, and battery input wiring diagram (sharing
battery strings)
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
32
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-11 AC input, AC output, and battery input wiring diagram (not
sharing battery strings)
Installing Battery Cables
After lithium batteries are connected in parallel, connect signal cables to the BMS
ports on the UPS. Install a build-out resistor at the COM-OUT port on the last
lithium battery.
●
UPS sharing battery strings
Figure 3-12 Installing the battery PE cable
(1) Ground bar
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
33
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-13 Installing battery cables (rack-mounted, front view)
(1) Busbar
Figure 3-14 Installing battery cables (rack-mounted, rear view)
●
Issue 02 (2021-06-30)
UPS not sharing battery strings
Copyright © Huawei Technologies Co., Ltd.
34
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-15 Installing the battery PE cable
(1) Ground bar
Figure 3-16 Installing battery cables (rack-mounted, front view)
(1) UPS rear view
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
35
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-17 Installing battery cables (rack-mounted, rear view)
3.7 Installing Communications Cables
NOTICE
Install a build-out resistor at the COM_OUT port on the last lithium battery.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
36
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-18 Installing battery communications cables
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
37
UPS2000-G-3KRTLL
User Manual
3 Installation
Figure 3-19 Installing parallel communications cables and parallel current
equalization cables (parallel system)
(1) Parallel current equalization cables
(2) Parallel communications cables
Figure 3-20 Installing communications cables
NOTE
● The USB channel supports a serial data communications protocol between the UPS and
a PC.
● If you connect a DB9 connector to the RS232 port, the UPS can exchange data with the
PC over serial communication.
● You can use only either USB or RS232.
3.8 Verifying the Installation
Table 3-2 Post-installation checklist
No.
Item
Expected Result
1
Cable routing
Cables are routed properly according to
engineering requirements.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
38
UPS2000-G-3KRTLL
User Manual
3 Installation
No.
Item
Expected Result
2
Cable connection
All cables are connected securely and
correctly, and they are free of damage.
Bolts are tightened to specified torque
using a torque wrench.
3
Cable connection to USB,
network, and other ports
Signal cables to USB, network, and
other ports are connected securely and
correctly.
4
Cable labels
Labels are neatly attached to both
ends of each cable, and the
information on the labels is concise
and legible.
5
Ground cable connection
The UPS ground cable is securely
connected to the equipment room
ground bar. Use a multimeter to
measure the resistance between the
UPS ground cable and the equipment
room ground bar. The resistance is less
than 0.1 ohm.
6
Spacing between cable ties
Distances between cable ties are the
same, and no burr exists.
7
Operating environment
The inside and outside of the cabinet
are free from conductive dust or other
sundries.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
39
UPS2000-G-3KRTLL
User Manual
4 Control Panel
4
Control Panel
4.1 LCD Introduction
The UPS control panel is located on the front panel of the chassis. The control
panel allows you to control and operate the UPS, view the running status, set
parameters, and view alarms.
4.1.1 LCD
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
40
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Table 4-1 LCD panel description
Display
Function
Displays the input voltage, input
frequency, charge current, battery voltage,
and battery state of charge (SOC).
Vac: input voltage; Vdc: battery voltage;
Hz: input frequency; %: battery SOC
Displays the current alarm and its ID.
Displays the output voltage, output
frequency, load percentage, battery
discharge current, and AC discharge
current.
Vac: output voltage; Hz: output frequency;
%: load percentage; A: output current
Displays the current load percentage by
level:
0%–24%: Indicator 1 is steady on.
25%–49%: Indicators 1 and 2 are steady
on.
50%–74%: Indicators 1, 2, and 3 are steady
on.
75%–100%: Indicators 1, 2, 3, and 4 are
steady on.
Indicates that the mains is connected.
Indicates that batteries are discharging.
Indicates that batteries are being charged.
Indicates that the UPS is in bypass mode.
Indicates that the UPS is in ECO mode.
Indicates that the DC/AC inverter circuit is
operating.
Indicates that the output terminal is
delivering power.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
41
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Display
Function
Displays the battery SOC by level:
0%–24%: Indicator 1 is steady on.
25%–49%: Indicators 1 and 2 are steady
on.
50%–74%: Indicators 1, 2, and 3 are steady
on.
75%–100%: Indicators 1, 2, 3, and 4 are
steady on.
When batteries are connected in parallel,
this area displays the lowest SOC among
the connected batteries.
Indicates the remaining battery backup
time.
H: hour; M: minute; S: second
● Indicates the UPS parallel connection
status.
● If the icon is not displayed, the UPS is in
single-node mode.
Indicates that the UPS is muted.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
42
UPS2000-G-3KRTLL
User Manual
4 Control Panel
4.1.2 Buttons
Figure 4-1 Buttons on the UPS control panel
NOTE
● If you do not press any button on the UPS control panel and there is no alarm, the LCD
automatically turns off the backlight and goes back to the default screen after 60s.
Table 4-2 Button description
No.
Button
Function
1
ON/MUTE
● Start the UPS: Press ON/MUTE.
The UPS LCD lights up.
● Start the UPS inverter: Press and
hold ON/MUTE for more than
5s. The UPS inverter starts.
● Stop the buzzer: If there is an
alarm, press and hold ON/MUTE
for more than 2s in non-setting
mode to mute the current alarm.
When the UPS generates a new
alarm, the mute function
becomes ineffective. If you need
to mute the alarm, perform the
mute operation again.
● Go to the previous item: When
the LCD is on, press ON/MUTE
to go to the previous item.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
43
UPS2000-G-3KRTLL
User Manual
4 Control Panel
No.
Button
Function
2
SELECT
● Go to the next item: Press
SELECT in setting mode to go to
the next item.
● Go to the setting screen: Press
and hold SELECT for 1s on a
non-setting screen.
3
OFF/ENTER
● Shut down the UPS: Press and
hold OFF/ENTER for more than
5s. The UPS inverter shuts down.
The UPS transfers to bypass
mode when the mains is
available.
● Confirm: In UPS setting mode,
press OFF/ENTER to confirm
selection.
4
ON/MUTE+SELECT+OFF/ENTER
Restore the initial password: Press
and hold ON/MUTE, SELECT, and
OFF/ENTER at the same time for
3s on the password login screen.
5
ON/MUTE+SELECT
Exit: Press ON/MUTE and SELECT
at the same time to exit the current
screen (go to the upper-level menu
from the setting screen or go to the
default screen from the selection
screen).
4.1.3 LCD Screen Information
You can press SELECT to switch the information displayed on the LCD in sequence.
The information is displayed in the following sequence: input voltage, input
frequency, charge current, battery voltage, output voltage, output frequency, load
percentage, DC discharge current, battery SOH, battery SOC, AC discharge current,
and CPU version.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
44
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Table 4-3 LCD screen information
Display
Description
Input voltage/Output voltage (default
screen)
Input frequency/Output voltage
Battery voltage/Output frequency
Battery voltage/Load percentage (< 3% as
shown in the figure)
Charge current/AC discharge current
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
45
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Display
Description
Battery DC discharge current/AC discharge
current
Battery SOH
Battery SOC
CPU version, for example, 51.35
4.2 LCD Character Display
Table 4-4 LCD character display description
Abbreviation
Display
Meaning
ADS
Communication address
BP
Battery not connected
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
46
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Abbreviation
Display
Meaning
BUZ
Buzzer off
CBT
Deep discharge test
CL
Maximum charge current
COV
Battery cut-off voltage
CV
Equalized charge voltage
DCP
Discharge percentage
DIS
Disabled
DT
Battery discharge time
ECO
ECO mode
ENA
Enabled
Err
Error
ESC
Exit the setting mode
ESP
Automatically return to
the default screen
FBT
Shallow discharge test
FLV
Float charge voltage
FrE
Frequency
FrS
Manual alarm clearance
HS
Host
NE
New (not connected to
the parallel system)
NUM
Set the number of
parallel UPSs
PAS
Password input
rST
Restore factory settings
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
47
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Abbreviation
Display
Meaning
SBT
Battery string sharing
SL
Slave
VOT
Voltage
<
Less-than sign
4.3 Parameter Settings
Press and hold SELECT for 1s on a non-setting screen to access the login screen
for parameter settings. The initial password is 000001. Enter the correct password
to access the UPS setting mode. Press SELECT to select a parameter, and then
press OFF/ENTER to confirm the setting.
If you forgot the password, press and hold ON/MUTE, SELECT, and OFF/ENTER at
the same time for 3s on the password login screen to reset the password.
If you enter incorrect passwords for multiple times, the password input screen will
be locked and you cannot continue to enter the password. The following table lists
the detailed data.
Table 4-5 Mapping between incorrect password attempts and lockout duration
Incorrect
Password
Attempts
Lockout Duration
3 ≤ Attempts <
5
1 minute
5 ≤ Attempts <
10
5 minutes (4
minutes and 59
seconds are
displayed as 4, and
seconds are not
displayed.)
Issue 02 (2021-06-30)
Display
Copyright © Huawei Technologies Co., Ltd.
48
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Incorrect
Password
Attempts
Lockout Duration
10 ≤ Attempts
60 minutes (59
minutes and 59
seconds are
displayed as 59, and
seconds are not
displayed.)
Display
Figure 4-2 Password input screen
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
49
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Table 4-6 Parameter settings
Name
Display
Manual alarm
clearance
Description
DIS: Manual alarm
clearance (disabled by
default)
ENA: Enable manual
alarm clearance. Ten
seconds after you exit
the setting screen, the
device restores the
initial status of manual
alarm clearance and
cancels alarms.
Maximum charge
current
● Default value: 10 A
Output voltage
You need to shut down
the inverter before
changing the output
voltage.
● Value range: 10–30
A. The value
increases by 10 A
each time you press
SELECT.
220: indicates that the
output voltage is 220 V
AC.
230: indicates that the
output voltage is 230 V
AC (default value).
240: indicates that the
output voltage is 240 V
AC.
Set the number of
parallel UPSs
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
● Default value: 1
● Value range: 1–2
50
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Name
Display
Battery discharge
time
Description
● Default value: 0H
(this function is
disabled)
● Value range: 0H–
48H
Battery capacity
● Default value: 100
Ah; value range: 50–
2400 Ah. The value
increases by 50 Ah
each time you press
SELECT.
● Battery string
sharing enabled:
When setting the
battery capacity, set
the total battery
string capacity for
each UPS.
● Battery string
sharing disabled:
When setting the
battery capacity, set
the capacity of the
battery string
connected to each
UPS.
Output frequency
You need to shut down
the inverter before
changing the output
frequency.
● 50 Hz (default)
● 60 Hz
ECO mode
DIS: Disable ECO mode
(default). When the
mains is available, the
UPS works in normal
mode. If the mains
frequency is unstable,
the UPS works in
battery mode.
ENA: When the mains is
available, the UPS
works in ECO mode.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
51
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Name
Display
Shallow discharge
test
Description
DIS: Disable shallow
discharge test (default).
ENA: Enable shallow
discharge test. The
shallow discharge test
time is controlled by
the battery discharge
time and discharge
percentage.
Discharge
percentage
● 20% (default)
Buzzer off setting
Enable or disable the
buzzer off function.
● Value range: 10–
50%. The value
increases by 1% each
time you press
SELECT.
ENA: Enable the buzzer
off function.
DIS: Disable the buzzer
off function (disabled
by default)
Automatically
return to the
default screen
ENA: Return the default
display screen (default).
If no button is pressed
within 1 minute in any
mode, the default
screen (input voltage/
output voltage) is
displayed.
DIS: Stay on the current
screen. The display will
stay on the screen
currently turned on by
the user.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
52
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Name
Display
Description
Equalized charge
voltage
● Default value: 54.0 V
Float charge
voltage
● Default value: 54.0 V
● When the lithium
battery does not
communicate, the
value range is 53.5–
57.0 V. The value
increases by 0.1 V
each time you press
SELECT.
When the lithium
battery is
communicating, the
UPS automatically
adapts to the
equalized charging
voltage based on the
connected lithium
battery model. The
value is fixed and
cannot be changed.
● When the lithium
battery does not
communicate, the
value range is 51.0–
56.0 V. The value
increases by 0.1 V
each time you press
SELECT.
● When the lithium
battery is
communicating, the
UPS automatically
adapts to the float
charging voltage
based on the
connected lithium
battery model. The
value is fixed and
cannot be changed.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
53
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Name
Display
Description
Battery (EOD)
point
● Default value: 44.0 V
Set the
communications
address
The default
communications
address is 001, which is
used for the RS485
communications ports
(connect to northbound
devices). Set different
communications
addresses for parallel
UPSs.
Restore factory
settings
DIS: Disable the
function of restoring
factory settings
(default).
● Value range: 44.0–
46.0 V. The value
increases by 0.1 V
each time you press
SELECT. The battery
EOD threshold is
fixed at the current
value regardless of
the load percentage.
ENA: Enable the
function of restoring
factory settings. The
setting takes effect
after you exit the
setting screen. After
factory settings are
restored, the output
voltage, calibration
parameters, and log
information are not
restored.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
54
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Name
Display
LCD password
control
Description
ENA: Enable LCD
password control
(default). After the
function is enabled, a
password is required for
accessing the settings
screen.
DIS: Disable LCD
password control. After
LCD password control is
disabled, no password is
required for accessing
the setting screen.
However, other users
may have the
permission to access
the parameter setting
screen to modify
parameters.
Password setting
● Initial password:
000001
● You are advised to
change the initial
password after
installation.
● On the password
login screen, press
and hold ON/MUTE,
SELECT, and OFF/
ENTER at the same
time for 3s to restore
the initial password.
Altitude-based
derating
● Default value: 1000
m When the altitude
exceeds 1000 m, the
output power is
derated by 1% for
each additional 100
m. The power can be
derated down to
70%.
● Value range: 1000–
4000 m
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
55
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Name
Display
Deep discharge
test
Description
DIS: Disable battery
deep discharge test
(default).
ENA: Enable battery
deep discharge test.
This function can be
enabled only when the
battery SOC is 100%.
Battery string
sharing
ENA: Enable battery
string sharing (default).
DIS: Disable battery
string sharing.
Exit the setting
mode
ESC: Exit the setting
mode.
4.4 Operating Modes
NOTICE
● Standby mode: The UPS is not started, but it can charge batteries when there is
no AC output.
● Fault mode: If a critical alarm is generated due to an internal circuit fault or an
external cause such as overtemperature or output short-circuit, the UPS enters
the fault mode.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
56
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Table 4-7 Operating mode description
Operating
Mode
Description
Display
Standby
mode
The UPS does not
supply power, but it
can still charge
batteries.
Charging batteries with mains power
Not charging batteries
Bypass mode
The UPS supplies
mains power. The
mains power can be
used to charge
batteries.
Charging batteries with mains power
Not charging batteries
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
57
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Operating
Mode
Description
Display
ECO mode
The UPS supplies
mains power. The
mains power can be
used to charge
batteries.
Charging batteries with mains power
Not charging batteries
Fault mode
The UPS supplies
mains power through
the bypass.
Not charging batteries; supplying mains
power through the bypass
Not charging batteries
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
58
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Operating
Mode
Description
Display
Normal
mode
The UPS supplies
primary power. The
UPS also charges
batteries if they are
connected.
Not charging batteries
Charging batteries with mains power
Battery
mode
The UPS supplies
battery power.
Supplying only battery power
4.5 Alarm Types
4.5.1 Critical Alarms
NOTE
● The LCD backlight automatically turns on when a critical alarm is generated.
● The buzzer keeps buzzing when there is a critical alarm. If manual alarm clearance is
enabled, ten seconds after you exit the setting screen, the device restores the initial status of
manual alarm clearance and cancels critical alarms.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
59
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Table 4-8 Critical alarms
Code
Display
Meaning
02
Overtemperature
03
Battery overvoltage
05
Output short-circuit detected by
the internal converter
06
Output overvoltage
07
Download timeout
08
Bus overvoltage
09
Bus soft-start failure
50
PFC overcurrent
51
Output overcurrent
52
Bus undervoltage
53
UPS soft-start failure
55
DC overvoltage in AC output
57
Current sensor fault
58
Output undervoltage
60
Load backfeed
71
Inconsistent parallel versions
72
Parallel current equalization
fault
73
Inconsistent parallel output
voltage settings
80
Parallel CAN communication
fault
81
Parallel host signal lost
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
60
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Code
Display
Meaning
82
Parallel synchronization signal
lost
83
Inconsistent parallel battery
voltage detection
84
Inconsistent parallel mains
detection
87
EPO triggered
4.5.2 Minor Alarms
NOTE
● When a minor alarm is generated, the LCD automatically turns on the backlight and the
buzzer sounds twice every 3s.
● If there is an alarm, press ON/MUTE for more than 2s in non-setting mode to mute the
current alarm. When the UPS generates a new alarm, the mute function becomes ineffective.
If you need to mute the alarm, perform the mute operation again.
Table 4-9 Minor alarms
Code
Display
Meaning
01
Fan locked during UPS startup
04
Battery voltage below the EOD
threshold
12
Manual bypass activated
13
Phase lock failure
17
Bypass voltage or frequency
abnormal
18
Low lithium battery level
19
Abnormal mains input
20
Lithium battery high
temperature protection
21
Lithium battery low
temperature protection
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
61
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Code
Display
Meaning
23
Lithium battery low voltage
protection
24
Lithium battery overcurrent
protection
27
Battery discharge test enabled
28
The battery discharge time
reaches the maximum.
31
UPS working in bypass mode
32
UPS locked in bypass mode due
to three transfers to bypass
mode
33
Overtemperature
34
Inconsistent number of parallel
UPSs
35
Long-time inverter current
imbalance
36
Overload
37
The inverter switch is off in ECO
mode.
38
The number of started inverters
is insufficient to carry the load.
39
Output in battery mode
40
Inconsistent battery capacity
41
Lithium battery high voltage
protection
43
Lithium battery fault
44
Lithium battery exception
protection
45
Lithium battery communication
unavailable
46
Lithium battery reverse
connection protection
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
62
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Code
Display
Meaning
48
ECO missing
49
Inconsistency between lithium
battery capacity and battery
capacity setting
59
Charger circuit overcurrent
BP
Battery not connected
4.6 Alarm Handling
Table 4-10 Alarm handling
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
01
Fan blocked
Minor
The fan
automatical
ly recovers
from
blockage.
The fan
blockage
signal is at
low level
for 15s
within 30s.
The current
working
status is
not
affected. If
overtemper
ature
protection
is triggered,
the system
may
transfer to
bypass
mode.
● Possible
cause:
The fan
is
blocked.
Measure:
Check the
fan and
remove
sundries.
● Possible
cause:
The fan
is faulty.
Measure:
Replace the
fan.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
63
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
02
Overtemper
ature
Critical
Fan
blocked:
The highest
temperatur
e of
internal
component
s is lower
than 65°C.
Fan
blocked:
The highest
temperatur
e of
internal
component
s exceeds
90°C for
100 ms.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
The
temperat
ure is
too high.
Fan not
blocked:
The highest
temperatur
e of
internal
component
s is lower
than 50°C.
After the
temperatur
e is restored
to normal,
the alarm
can be
automatical
ly cleared
for three
times. After
that, you
need to
manually
clear the
alarm.
Issue 02 (2021-06-30)
Fan not
blocked:
The highest
temperatur
e of
internal
component
s exceeds
80°C for
100 ms.
Copyright © Huawei Technologies Co., Ltd.
Measure:
Decrease
the
ambient
temperatur
e or load.
● Possible
cause:
The
temperat
ure
sensor is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
64
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
03
High
battery
voltage
Critical
The alarm
is
automatical
ly cleared
when the
battery
voltage is
lower than
58 V.
The battery
voltage is
greater
than 60 V
for 3s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
The
battery
is faulty.
Measure:
Replace the
battery or
discharge
the battery
to a normal
voltage.
● Possible
cause:
The
sampling
is faulty
due to
environ
mental
factors.
Measure:
Send the
device to
the
maintenanc
e center.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
65
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
04
Low battery
voltage
Minor
The battery
voltage is
higher than
the EOD
threshold
and the
mains is
connected
properly.
The battery
voltage is
lower than
the EOD
threshold.
The system
cannot
supply
power in
battery
mode. If
this alarm
is
generated
in battery
mode, the
power
output will
be
disconnecte
d.
● Possible
cause:
The
battery
is faulty.
Measure:
Replace the
battery or
charge the
battery to a
normal
voltage.
● Possible
cause:
The
sampling
is faulty
due to
environ
mental
factors.
Measure:
Send the
device to
the
maintenanc
e center.
05
Output
short-circuit
Issue 02 (2021-06-30)
Critical
The alarm
can be
automatical
ly cleared
for three
times. After
that, you
need to
manually
clear the
alarm or
restart the
device.
The output
voltage is
lower than
50 V and
the current
is higher
than 20 A
for more
than five
cycles of
time.
Copyright © Huawei Technologies Co., Ltd.
The system
immediatel
y
disconnects
the power
output.
Possible
cause: The
load or
cable is
shortcircuited.
Measure:
Power off
the device
to locate
and rectify
the shortcircuit fault,
and then
power on
the device.
66
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
06
High output
voltage
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The output
voltage
exceeds the
rated
voltage by
20 V for 3s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
Load
energy
backfeed
occurs.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
07
Download
timeout
Issue 02 (2021-06-30)
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The output
overload
time
exceeds the
specificatio
n.
Copyright © Huawei Technologies Co., Ltd.
The system
disconnects
the power
output.
Possible
cause: The
load
exceeds the
UPS
capacity.
Measure:
Reduce the
load.
67
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
08
High bus
voltage
Critical
When the
bus voltage
is lower
than 360 V,
the alarm
can be
automatical
ly cleared
for two
times. After
that, you
need to
manually
clear the
fault or
power off
and restart
the device.
The bus
voltage is
greater
than 450 V
for 200 ms
or greater
than 470 V
for 1 ms.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
Power
grid
surge
occurs.
Measure:
Improve the
power grid
quality.
● Possible
cause:
The
parallel
cable is
disconne
cted
when
UPSs are
connecte
d in
parallel.
Measure:
Check that
the parallel
cable and
current
equalizatio
n cable are
properly
connected.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
68
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
09
Bus shortcircuit
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The bus
soft-start
time
exceeds
15s.
The system
cannot start
inverter
output and
transfers to
bypass
mode.
Possible
cause: The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
12
Manual
bypass
activated
Minor
The opencircuit
status of
the manual
bypass is
restored.
The manual
bypass port
is shortcircuited.
The system
transfers to
bypass
mode.
Restore the
open-circuit
status of
the manual
bypass port.
13
Phase lock
failure
Minor
Phase
locking is
successful
or the
bypass is
missing.
The inverter
fails in
phase
locking
within 10s.
The system
cannot start
PFC or
enter
normal
mode.
Possible
cause: The
power grid
frequency is
unstable.
17
Bypass
abnormal
Minor
The bypass
voltage or
frequency
recovers to
the normal
range.
The bypass
voltage or
frequency is
out of the
normal
range.
● The
system
cannot
transfer
to
bypass
mode
when a
critical
alarm is
generate
d.
● Check
that the
bypass
connecti
on is
normal.
● In
bypass
mode,
the
power
output is
disconne
cted.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
● Check
that the
bypass
voltage
and
frequenc
y are
within
their
normal
ranges.
69
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
18
Low lithium
battery
level
Minor
The battery
voltage is
higher than
the battery
EOD
threshold
plus 4 V
and the
SOC rises
above the
alarm
threshold.
Communica
tion is
normal. An
alarm is
generated
when the
SOC is
lower than
20% or the
battery
voltage is
lower than
the battery
EOD
threshold
plus 2 V.
The battery
level is
close to the
cutoff
threshold. If
there is no
mains
input, the
system will
shut down
after
working for
a period of
time.
Possible
cause: The
battery
charge level
is low.
Measure:
Charge the
battery.
Communica
tion is
abnormal,
and the
battery
voltage
falls to 47 V
DC.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
70
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
19
Abnormal
mains
voltage
Minor
The mains
voltage
input
recovers.
● The
mains is
disconne
cted or
fails.
The system
cannot
work in
normal
mode. If
this alarm
is
generated
in normal
mode, the
system
transfers to
battery
mode.
Check
whether
the mains
voltage
input is
normal. If
the circuit is
faulty, send
the device
to the
maintenanc
e center.
● The
mains
input
voltage
harmoni
c
exceeds
10%
(square
wave
input is
not
supporte
d).
● The
mains
frequenc
y change
rate
exceeds
the
phase
lock rate
defined
in the
specifica
tions (2
Hz/s for
a single
UPS and
1 Hz/s
for a
parallel
system).
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
71
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
20
Lithium
battery
high
temperatur
e protection
Minor
The cell
temperatur
e drops
below the
protection
threshold.
● Charge
high
temperat
ure
protectio
n: The
maximu
m cell
temperat
ure is
greater
than
60°C.
● The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
Possible
cause: The
ambient
temperatur
e of the
lithium
battery is
too high or
there are
abnormal
heat
sources
around the
lithium
battery.
● Discharg
e high
temperat
ure
protectio
n: The
maximu
m cell
temperat
ure is
greater
than
65°C.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
● The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Measure: If
the lithium
battery
cannot be
recovered
due to
protection
against
abnormality
, contact
local
Huawei
engineers
to rectify
the fault.
72
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
21
Lithium
battery low
temperatur
e protection
Minor
The cell
temperatur
e rises
above the
protection
threshold.
● Charge
low
temperat
ure
protectio
n: The
minimu
m cell
temperat
ure is
less than
0°C.
● The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
Possible
cause: The
ambient
temperatur
e of the
lithium
battery is
too low or
the heater
cannot
work
properly.
● Discharg
e low
temperat
ure
protectio
n: The
minimu
m cell
temperat
ure is
less than
–20°C.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
● The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Measure: If
the lithium
battery
cannot be
recovered
due to
protection
against
abnormality
, contact
local
Huawei
engineers
to rectify
the fault.
73
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
23
Lithium
battery low
voltage
protection
Minor
The cell
voltage and
battery
string
voltage rise
above the
respective
protection
thresholds.
The lithium
battery
voltage is
less than 44
V.
● The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
Possible
cause: The
mains
power has
failed and
not been
recovered
for a long
time. The
cell
consistency
is
abnormal.
The
capacity
attenuation
is too fast
or the
internal
resistance is
too large.
The
minimum
cell voltage
is less than
2.5 V.
● The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
Measure: If
the lithium
battery
cannot be
recovered
due to
protection
against
abnormality
, contact
local
Huawei
engineers
to rectify
the fault.
74
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
24
Lithium
battery
overcurrent
protection
Minor
The battery
discharge
current
drops
below the
protection
threshold.
Discharge
current ≥
0.93 times
of the
current
limit and
Vbus ≤ 40 V
for 15s
● The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
Possible
cause: The
UPS is
overloaded.
The
number of
working
batteries is
insufficient.
Discharge
current ≥
0.98 times
of the
current
limit and
Vbus < 17 V
for 8s
Measure:
Reduce the
load. Add
batteries.
● The ALM
indicator
on the
faulty
lithium
battery
turns
red.
27
Battery
discharge
est function
enabled
Issue 02 (2021-06-30)
Minor
The battery
discharge
test is
complete.
The shallow
or deep
discharge
function is
enabled
manually.
Copyright © Huawei Technologies Co., Ltd.
The system
transfers to
battery
mode.
Measure:
Switch off
the battery
shallow or
deep
discharge
test mode.
75
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
28
The battery
discharge
time
reaches the
maximum.
Minor
Set item 05
battery
discharge
time to 0 or
restart the
inverter.
The battery
discharge
time
reaches the
preset
value.
The system
cannot
supply
power in
battery
mode. If
this alarm
is
generated
in battery
mode, the
power
output will
be
disconnecte
d.
Check
whether
the mains
input is
normal.
31
UPS
working in
bypass
mode
Minor
The UPS
recovers the
inverter
output.
The UPS
works in
bypass
mode.
The bypass
power
output
alarm does
not affect
the system
working
status. The
power
supply will
be
disconnecte
d if the
bypass
input is
abnormal.
● Check
whether
the UPS
transfers
to
bypass
mode
due to
overload.
The system
cannot
automatical
ly switch
back to
inverter
mode.
Possible
cause: The
UPS is
overloaded.
32
UPS locked
in bypass
state
Issue 02 (2021-06-30)
Minor
The inverter
switch is
turned on
again.
The UPS
transfers to
bypass
mode more
than three
times
within 30
minutes
due to
overload.
Copyright © Huawei Technologies Co., Ltd.
● Check
whether
the
inverter
switch is
turned
on.
76
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
33
Overtemper
ature
Minor
Fan
blocked:
The highest
temperatur
e of
internal
component
s is lower
than 65°C.
Fan not
blocked:
The highest
temperatur
e of
internal
component
s is lower
than 50°C.
Fan
blocked:
The highest
temperatur
e of
internal
component
s exceeds
75°C for
100 ms.
If the
internal
temperatur
e of the
system is
close to the
overtemper
ature
protection
threshold, a
critical
overtemper
ature alarm
may be
triggered
and the
system will
transfer to
bypass
mode.
● Possible
cause:
The
temperat
ure is
too high.
The
number of
parallel
UPSs is
consistent
with the
setting.
The actual
number of
parallel
UPSs is
inconsistent
with the
setting.
The current
operating
status is
not
affected.
Check
whether
the actual
number of
parallel
UPSs is the
same as the
setting and
whether
parallel
cables are
disconnecte
d.
Suggestion:
Set the
number of
parallel
UPSs to the
actual
value.
34
Inconsistent
number of
parallel
UPSs
Issue 02 (2021-06-30)
Minor
Fan not
blocked:
The highest
temperatur
e of
internal
component
s exceeds
87°C for
100 ms.
Copyright © Huawei Technologies Co., Ltd.
Measure:
Decrease
the
ambient
temperatur
e or load.
● Possible
cause:
The
temperat
ure
sensor is
faulty.
Measure:
Send the
device to
the
mainten
ance
center.
77
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
35
Long-time
current
imbalance
Minor
The
difference
between
the UPS
load
percentage
and the
parallel
system load
percentage
is within
10% for
10s.
The
difference
between
the UPS
load
percentage
and the
parallel
system load
percentage
is greater
than 20%
for 10s.
The current
working
status is
not
affected.
The system
may
transfer to
bypass
mode if it is
overloaded.
Possible
cause: The
current
equalizatio
n sampling
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
36
Overload
Minor
The load
percentage
exceeds
10%.
The load
percentage
exceeds
105%.
The system
transfers to
bypass
mode when
the
overload
time
expires.
Possible
cause: The
UPS is
overloaded.
37
The inverter
switch is off
in ECO
mode.
Minor
The inverter
switch is
turned on.
The inverter
switch is off
in ECO
mode.
When the
mains input
exceeds the
ECO range,
the power
supply is
disconnecte
d.
The inverter
output
switch is
turned on.
38
The
number of
started
inverters is
insufficient
to carry the
load.
Minor
The inverter
switches of
other UPSs
in the
parallel
system are
turned on.
In parallel
mode, the
number of
started
inverters is
insufficient
to support
the actual
load.
The system
keeps
working in
bypass
mode and
cannot
transfer
back to
inverter
mode.
Turn on the
inverter
switches of
other UPSs.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
78
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
39
Output in
battery
mode
Minor
The mains
input
recovers.
The mains
input is
abnormal.
(Refer to
the
description
of minor
alarm 19.)
The current
working
status is
not
affected.
When the
battery
backup
time or
discharge
time
reaches the
preset
value, the
system will
disconnect
the power
output.
Check
whether
the mains
input is
normal.
Possible
cause: The
circuit is
faulty and
needs to be
returned for
repair.
40
Battery
capacity
mismatch
Minor
Increase the
lithium
battery
capacity or
reduce the
load.
The
maximum
discharge
power of
lithium
batteries is
less than
the actual
load power
of the UPS.
After the
UPS
transfers to
battery
mode, the
lithium
battery
overcurrent
protection
may be
triggered,
which
causes the
system to
power off.
Reduce the
load or add
lithium
batteries in
a timely
manner.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
79
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
41
Lithium
battery
high
voltage
protection
Minor
The cell or
battery
string
voltage
drops
below the
protection
threshold.
● The
busbar
voltage
is
greater
than
59.4 V in
charging
state.
● The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
Possible
cause: The
busbar
voltage
input is
abnormal
and exceeds
the normal
range. The
cell
consistency
is
abnormal.
The
capacity
attenuation
is too fast
or the
internal
resistance is
too large.
● The
maximu
m cell
voltage
is
greater
than 3.8
V.
NOTE
Conside
ring cell
differen
ce, the
maximu
m cell
voltage
can be
3.9 V.
● The
battery
string
voltage
is
greater
than 55
V.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
● The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Measure: If
the lithium
battery
cannot be
recovered
due to
protection
against
abnormality
, contact
local
Huawei
engineers
to rectify
the fault.
80
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
43
Lithium
battery
fault
Minor
The alarm
is not
cleared.
After
batteries
are reset,
check the
status
again.
The cell
voltage
sampling
circuit is
faulty.
● The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
Possible
cause:
sampling
fault (see
the telecom
power
manual);
cell or
equalizatio
n circuit
fault;
charger
converter
shortcircuit, relay
fault;
switch tube
fault
● The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Measure:
Restart the
lithium
battery. If
the fault
persists,
replace the
lithium
battery.
The cell
temperatur
e sampling
circuit is
faulty.
The cell
voltage is
too high or
too low.
The cell
temperatur
e increases
abnormally.
The cell
voltage is
severely
unbalanced.
BMS board
circuit fault
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
81
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
44
Lithium
battery
exception
protection
Minor
Check
again after
the fault is
rectified.
The busbar
voltage is
too high.
● The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
Possible
cause: The
UPS is
overloaded,
the host
charger is
abnormal,
or battery
cables are
incorrectly
connected.
The
temperatur
e of the
board relay
and switch
tube is too
high.
The output
is shortcircuited.
Batteries
are
reversely
connected.
45
Charger
shutdown
due to
lithium
battery
communica
tion failure
Issue 02 (2021-06-30)
Minor
Lithium
battery
communica
tion
recovers.
The output
is
overloaded.
● The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Lithium
battery
communica
tion is
unavailable
for 40s.
The SOC
data and
backup
time
displayed
are
inaccurate,
and the
BMS
function
fails
(lithium
battery
voltage
boosting
and current
limiting).
Copyright © Huawei Technologies Co., Ltd.
Measure:
Check the
cable
connection,
check the
host status,
or reduce
the load.
Check that
the
communica
tions cable
is properly
connected.
82
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
46
Lithium
battery
reverse
connection
protection
Minor
The lithium
battery
communica
tion is
interrupted
or the
alarm BP is
generated.
When the
lithium
battery
communica
tion is
normal, the
battery
voltage is
less than 10
V.
The UPS
cannot
work in
battery
mode.
Possible
cause: The
battery has
shut down
or has no
output.
Measure:
Check the
battery
switch
status and
battery
cable
connection.
47
UPS locked
in inverter
mode
Minor
The mains
is within
the ECO
range. Shut
down the
inverter and
the UPS
transfers to
bypass
mode; then
restart the
inverter and
the UPS
transfers to
ECO mode.
The UPS
exits ECO
mode for
three times
within 30
minutes.
The system
cannot
automatical
ly switch
back to
ECO mode.
Possible
cause: The
mains
exceeds the
ECO range.
48
ECO
missing
Minor
The input
voltage and
frequency
restore to
the normal
range in
ECO mode.
The input
voltage or
frequency
exceeds the
normal
operating
range in
ECO mode.
The UPS
cannot
transfer to
bypass
mode. If
the UPS is
working in
bypass
mode, it
transfers to
another
working
mode.
Possible
cause: The
ECO input
is
abnormal.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
Measure:
Check
whether
the ECO
input
voltage or
frequency
exceeds the
normal
range.
83
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
49
Inconsistenc
y between
the lithium
battery
capacity
and UPS
setting
Minor
The lithium
battery
capacity is
consistent
with as the
UPS setting,
or lithium
battery
communica
tion is
unavailable.
The lithium
battery
capacity is
inconsistent
with the
UPS setting.
The system
working
mode is not
affected. If
the actual
capacity of
lithium
batteries
connected
is
insufficient,
the battery
backup
time may
be
shortened.
● Check
that the
UPS
battery
capacity
setting
matches
the
lithium
battery
capacity.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
Power
grid
surge
occurs.
50
PFC
overcurrent
Critical
The alarm
is
automatical
ly cleared.
● Inverter
not
started:
The PFC
current
exceeds
65 A for
10 ms.
● Inverter
started:
The PFC
current
exceeds
65 A for
260 μs.
● Check
whether
abnorma
l lithium
battery
commun
ication
causes
an error
in
capacity
reading.
Measure:
Improve the
power grid
quality.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
84
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
51
Output
overcurrent
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The output
current
exceeds 80
A for 1 ms.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
The
transient
load
power is
too high.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
52
Bus
undervoltag
e
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
● Battery
mode:
The bus
voltage
is over
100 V
less than
7 times
the
battery
voltage.
● Normal
mode:
The bus
voltage
is over
80 V less
than the
peak
mains
voltage.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
The
transient
load
power is
too high.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
85
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
53
Timeout in
approachin
g rated
output
voltage
during
startup
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The inverter
voltage is
not softstarted to
the rated
output
voltage
within 10s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
Possible
cause: The
circuit is
faulty.
Excessive
DC
component
Critical
The alarm
can be
automatical
ly cleared
for three
times. After
that, you
need to
manually
clear the
fault or
power off
and restart
the device.
The DC
component
of the
output
voltage is
greater
than 200
mV for 20s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
The halfwave
load
power is
too high.
55
Measure:
Send the
device to
the
maintenanc
e center.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
57
Current
sensor fault
Issue 02 (2021-06-30)
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
In power-on
mode, the
current
sampling
deviation
exceeds
10% of the
total
sampling
range.
Copyright © Huawei Technologies Co., Ltd.
The system
cannot start
the inverter
and directly
delivers
output in
bypass
mode.
Possible
cause: The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
86
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
58
Low output
voltage
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The output
voltage is
lower than
the rated
voltage by
50 V for 3s.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
● Possible
cause:
The
transient
load
power is
too high.
Measure:
Locate the
load and
remove it.
● Possible
cause:
The
circuit is
faulty.
Measure:
Send the
device to
the
maintenanc
e center.
59
Charger
circuit
overcurrent
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The charge
current is
greater
than 105 A.
The system
shuts down
the inverter
and
transfers to
bypass
mode.
Possible
cause:
Power grid
surge
occurs.
Measure:
Improve the
power grid
quality.
Possible
cause: The
charger
circuit is
damaged.
Measure:
Replace the
charger
circuit.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
87
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
60
Load
backfeed
detected
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
When UPSs
are
connected
in parallel,
the output
backfeed
power
exceeds
1200 W for
100 ms.
The system
shuts down
the inverter
and
transfers to
bypass
mode. If
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
Possible
cause: Load
backfeed
occurs.
You need to
manually
rectify the
fault or
power off
and restart
the device.
Parallel UPS
protocols
are
inconsistent
.
If the
versions are
inconsistent
, the nonmaster UPS
exits the
parallel
system.
Otherwise,
the UPS
transfers to
bypass
mode
because the
number of
parallel
UPSs is
inconsistent
.
Possible
cause: The
UPS
software
versions are
inconsistent
.
71
Inconsistent
parallel
versions
Issue 02 (2021-06-30)
Critical
Copyright © Huawei Technologies Co., Ltd.
Measure:
Disconnect
the load
and restart
the device.
Measure:
Upgrade
the
software to
the same
version.
88
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
72
Parallel
current
equalizatio
n fault
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
Equalized
current
sampling is
abnormal.
The system
shuts down
the inverter
and
transfers to
bypass
mode. If
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
Possible
cause: The
circuit is
faulty.
You need to
manually
rectify the
fault or
power off
and restart
the device.
The output
voltage
settings of
parallel
UPSs are
inconsistent
.
If the
output
voltage
settings are
inconsistent
, the nonmaster UPS
exits the
parallel
system.
Otherwise,
the UPS
transfers to
bypass
mode
because the
number of
parallel
UPSs is
inconsistent
.
Possible
cause: The
output
settings are
inconsistent
.
73
Inconsistent
parallel
output
voltage
settings
Issue 02 (2021-06-30)
Critical
Copyright © Huawei Technologies Co., Ltd.
Measure:
Send the
device to
the
maintenanc
e center.
Measure:
Set the
output
voltages to
the same
value.
89
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
80
Parallel
CAN signal
fault
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
CAN
communica
tion signals
are lost for
6s in a
parallel
system.
The system
shuts down
the inverter
and
transfers to
bypass
mode. If
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
● Possible
cause:
The
circuit is
faulty.
The system
shuts down
the inverter
and
transfers to
bypass
mode. If
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
Possible
cause: The
circuit is
faulty.
81
Parallel UPS
host signal
fault
Issue 02 (2021-06-30)
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The UPS
host signal
is lost for
more than
60 ms in a
parallel
system.
Copyright © Huawei Technologies Co., Ltd.
Measure:
Send the
device to
the
maintenanc
e center.
● Possible
cause:
The
parallel
cable is
disconne
cted.
Measure:
Check the
cable
connection.
Measure:
Send the
device to
the
maintenanc
e center.
90
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
82
Parallel
synchroniza
tion signal
fault
Critical
You need to
manually
rectify the
fault or
power off
and restart
the device.
The
synchroniza
tion zerocrossing
signal is
lost for
more than
200 ms.
The system
shuts down
the inverter
and
transfers to
bypass
mode. If
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
Possible
cause: The
circuit is
faulty.
The voltage
difference is
less than 3
V or the
UPS is set
to
standalone
mode.
The battery
voltage
deviation
between
UPSs in a
parallel
system is
greater
than 4 V for
120 ms.
The system
shuts down
the inverter
and
transfers to
bypass
mode. If
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
Possible
cause:
Batteries
are not
shared.
83
Parallel
battery
voltage
deviation
exceeding 4
V
Issue 02 (2021-06-30)
Critical
Copyright © Huawei Technologies Co., Ltd.
Measure:
Send the
device to
the
maintenanc
e center.
Measure:
Ensure that
all UPSs
share one
battery
string.
91
UPS2000-G-3KRTLL
User Manual
4 Control Panel
Alarm ID
Alarm
Name
Severity
Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
84
Inconsistent
AC input
voltage and
frequency
Critical
The voltage
difference is
less than 20
V or the
UPS is set
to
standalone
mode.
The mains
voltage
deviation
between
UPSs in a
parallel
system
ranges from
40 V to 100
V for 120
ms.
The system
shuts down
the inverter
and
transfers to
bypass
mode. If
other UPSs
in the
parallel
system can
deliver
output in
inverter
mode, the
UPS that
has
generated
the alarm
delivers no
output.
Possible
cause: The
UPSs do
not share
one mains
supply.
Measure:
Ensure that
all UPSs
share one
mains
supply.
87
EPO
triggered
Critical
The EPO
open-circuit
status
needs to be
restored
and the
alarm
needs to be
manually
cleared.
The EPO
port is
shortcircuited.
The system
switches off
the output
and enters
the fault
mode.
Check and
restore the
EPO port
status.
BP
Battery not
connected
Minor
The battery
voltage is
higher than
36 V.
● The
battery
voltage
is lower
than 36
V.
If batteries
are not
connected,
the output
may be
interrupted
after mains
outage.
Check
whether
battery
cables are
correctly
connected.
● Batteries
are
reversely
connecte
d.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
92
UPS2000-G-3KRTLL
User Manual
5 Operations
5
Operations
5.1 Checking Before Power-On
●
AC power cable colors comply with local regulations.
●
The input and output are not short-circuited.
●
Cables and terminals are securely connected.
●
Battery cables and terminals are connected correctly, and voltages comply
with industry standards.
●
Power cables and signal cables are correctly identified.
●
Cables are neatly routed and securely bound.
●
Devices are installed and cables are routed in ways that facilitate
modification, capacity expansion, and maintenance.
●
The UPS is properly grounded.
●
The voltage between the neutral wire and the ground cable is less than 5 V
AC.
5.2 Single UPS Operations
5.2.1 Starting a UPS
NOTICE
● If no button is pressed within 20s in UPS setting mode, the LCD home screen is
displayed.
● If no batteries are connected to the UPS of the long backup time model, the
buzzer keeps buzzing.
● To prevent triggering overload protection, start the loads with higher power
and then loads with lower power.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
93
UPS2000-G-3KRTLL
User Manual
5 Operations
Figure 5-1 AC input, AC output, and battery input wiring diagram
5.2.1.1 Start the UPS Using Mains Power
Procedure
Step 1 Switch on the external battery circuit breaker (if any).
Switch on the external AC input circuit breaker Km for the UPS. The UPS will enter
the bypass mode. Press and hold SELECT for 1s on a non-setting screen to access
the login screen for parameter settings. The initial password is 000001. Enter the
correct password to access the UPS setting mode.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
94
UPS2000-G-3KRTLL
User Manual
5 Operations
Figure 5-2 Password input screen
Figure 5-3 Bypass mode
Step 2 Set the output voltage based on site requirements.
Output Voltage
Description
You need to shut down the inverter
before changing the output voltage.
220: indicates that the output voltage
is 220 V AC.
230: indicates that the output voltage
is 230 V AC (default value).
240: indicates that the output voltage
is 240 V AC.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
95
UPS2000-G-3KRTLL
User Manual
5 Operations
Step 3 Set the battery capacity.
Battery Capacity
Description
● Default value: 100 Ah
● Value range: 50–2400 Ah. The value
increases by 50 Ah each time you
press SELECT.
Step 4 Press and hold ON/MUTE for more than 5s. Release the button when you hear a
beep sound. The UPS starts to work in normal mode.
Figure 5-4 Normal mode
Step 5 After you ensure that the UPS runs properly, switch on the AC output circuit
breaker Q for the UPS to start the load.
----End
5.2.1.2 Cold-Starting the UPS Using Batteries
Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Press ON/MUTE to start the UPS. The UPS will enter the standby mode. Press and
hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 000001. Enter the correct password to
access the UPS setting mode.
Figure 5-5 Standby mode
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
96
UPS2000-G-3KRTLL
User Manual
5 Operations
Step 3 Set the output voltage based on site requirements.
Output Voltage
Description
You need to shut down the inverter
before changing the output voltage.
220: indicates that the output voltage
is 220 V AC.
230: indicates that the output voltage
is 230 V AC (default value).
240: indicates that the output voltage
is 240 V AC.
Step 4 Set the battery capacity.
Battery Capacity
Description
● Default value: 100 Ah
● Value range: 50–2400 Ah. The value
increases by 50 Ah each time you
press SELECT.
Step 5 Press and hold ON/MUTE for more than 5s. Release the button when you hear a
beep sound. The UPS starts to work in battery mode.
Figure 5-6 Battery mode
Step 6 After you ensure that the UPS runs properly, switch on the AC output circuit
breaker Q for the UPS to start the load.
----End
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
97
UPS2000-G-3KRTLL
User Manual
5 Operations
5.2.2 Shutting Down a UPS
Normal Mode
On the default screen, press and hold OFF/ENTER for more than 5s. Release the
button when you hear the buzzer buzzing. The UPS inverter is shut down. The UPS
transfers to bypass mode when the mains is available.
Battery Mode
In battery mode, press and hold OFF/ENTER for more than 5s. Release the button
when you hear the buzzer buzzing. The UPS in battery mode is shut down.
Shutting Down the Inverter to Transfer the UPS to the No Output State
Step 1 Shut down loads.
Step 2 Perform the shutdown operation on the UPS. The UPS shuts down the inverter
and transfers to bypass mode. If mains parameters are inconsistent with bypass
parameters, the UPS transfers to standby mode.
Step 3 Switch off the AC input circuit breaker Km and output circuit breaker Q for the
UPS. After all indicators turn off and fans stop, the UPS shuts down and the loads
power off.
----End
5.2.3 Performing EPO
Turn on the EPO switch (provided by the customer). The UPS enters the EPO state.
That is, the UPS shuts down the inverter, and does not transfer to the bypass
mode.
Figure 5-7 EPO cable connection on a single UPS
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
98
UPS2000-G-3KRTLL
User Manual
5 Operations
5.3 Parallel System Operations
5.3.1 Starting a Parallel System
NOTICE
● A parallel system of 3 kVA UPSs can share or not share battery strings.
● Before you start a parallel system, ensure that the output circuit breakers for
each UPS are ON. In addition, ensure that the output neutral wires of all UPSs
are connected together.
● Check that parallel system parameters have been synchronized.
● Before starting a parallel system, ensure that all circuit breakers on the output
side are OFF, and do not start loads.
● To prevent triggering overload protection, start the loads with higher power
and then loads with lower power.
Figure 5-8 AC input, AC output, and battery input wiring diagram
5.3.1.1 Start the UPSs Using Mains Power
Procedure
Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Switch on the general AC input circuit breaker Km to start the UPS. The UPS will
enter the bypass mode. Switch on the AC output circuit breaker Q1. The UPSs
enter the standby screen, and the parallel system works in bypass mode. Press and
hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 000001. Enter the correct password to
access the UPS setting mode.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
99
UPS2000-G-3KRTLL
User Manual
5 Operations
Figure 5-9 Password input screen
Step 3 Set the output voltage based on site requirements.
Output Voltage
Description
You need to shut down the inverter
before changing the output voltage.
220: indicates that the output voltage
is 220 V AC.
230: indicates that the output voltage
is 230 V AC (default value).
240: indicates that the output voltage
is 240 V AC.
Step 4 Operate the UPSs one by one to set the number of parallel output UPSs. Press
SELECT, go to the setting screen, and set parallel system parameters. Press ON/
MUTE+SELECT to return to the standby screen.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
100
UPS2000-G-3KRTLL
User Manual
5 Operations
Number of Parallel UPSs
Description
● Default value: 1
● Value range: 1–2
Step 5 Perform the startup operation on each UPS. The UPS parallel system transfers to
normal mode.
Step 6 After checking that the system runs properly, switch on the general output circuit
breaker Q and branch output circuit breakers for the parallel system to start loads
one by one.
----End
5.3.1.2 Cold-Starting the UPSs Using Batteries
Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Press ON/MUTE to start the UPSs. The UPSs will enter the standby mode. Press
and hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 000001. Enter the correct password to
access the UPS setting mode.
Step 3 Set the output voltage based on site requirements.
Output Voltage
Description
You need to shut down the inverter
before changing the output voltage.
220: indicates that the output voltage
is 220 V AC.
230: indicates that the output voltage
is 230 V AC (default value).
240: indicates that the output voltage
is 240 V AC.
Step 4 Operate the UPSs one by one to set the number of parallel output UPSs. Press
SELECT, go to the setting screen, and set parallel system parameters. Press ON/
MUTE+SELECT to return to the standby screen.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
101
UPS2000-G-3KRTLL
User Manual
5 Operations
Number of Parallel UPSs
Description
● Default value: 1
● Value range: 1–2
Step 5 Perform the startup operation on each UPS. The UPS parallel system transfers to
battery mode.
Step 6 After checking that the system runs properly, switch on the general output circuit
breaker Q and branch output circuit breakers for the parallel system to start loads
one by one.
----End
5.3.2 Shutting Down a Parallel System
Shutting Down a Single UPS in the Parallel System
Step 1 Perform the shutdown operation for a UPS in the parallel system. Then the UPS
shuts down and generates no output. Other UPSs work without being affected.
Step 2 Switch off the external battery circuit breaker (if any), or disconnect battery power
cables for the UPS. The UPS exits the parallel system.
----End
NOTE
● When one UPS in the parallel system is shut down while another UPS is still working,
the UPS that has been shut down has no output.
● To shut down a UPS without removing it from the system, perform only step 1.
Transferring the Parallel System to Bypass Mode
Perform the shutdown operation on each UPS in the parallel system. All UPSs shut
down the inverters and transfer to bypass mode.
Transferring the Parallel System to No Output Mode
Step 1 Shut down loads.
Step 2 Perform the shutdown operation on each UPS in the parallel system. All UPSs shut
down the inverters and transfer to bypass mode.
Step 3 Switch off the general AC input circuit breaker Km and the general AC output
circuit breaker Q of the UPS system. After all indicators turn off and fans stop, the
UPSs shut down, and the loads power off.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
102
UPS2000-G-3KRTLL
User Manual
5 Operations
Step 4 Switch off the external battery circuit breaker for each UPS or the general battery
circuit breaker (when all UPSs in the parallel system share a battery string). If no
external battery circuit breaker is configured, disconnect battery power cables
from each UPS.
----End
5.3.3 Performing EPO
Turn on the EPO switches (provided by the customer). The UPSs enter the EPO
state. That is, the UPSs shut down the inverters, and do not transfer to the bypass
mode.
Figure 5-10 EPO cable connection in a parallel system
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
103
UPS2000-G-3KRTLL
User Manual
6 UPS Maintenance
6
UPS Maintenance
NOTICE
● Only trained personnel are allowed to perform maintenance tasks. Before
performing operations on devices, wear ESD clothes, ESD gloves, and an ESD
wrist strap. Remove conductive objects such as jewelry and watches to avoid
electric shocks or burns.
● Use insulated tools when maintaining components inside all devices. Only
trained personnel are allowed to perform maintenance.
● Maintain UPSs regularly based on the following requirements. Otherwise, the
UPSs may fail to operate properly and the lifespan may be shortened.
● For details about how to upgrade the software version, visit https://
support.huawei.com/carrier/docview!docview?
nid=DOC1100726656&path=PBI1-7275736/PBI1-9855721/PBI1-251366627/
PBI1-251617364/PBI1-7352438 to download the upgrade guide.
Table 6-1 UPS routine maintenance
Item
Expected Result
Troubleshooting
Maintenance
Interval
Operating
environment
● Ambient
temperature:
0–40°C
● If the humidity
and
temperature
are abnormal,
check the air
conditioner
status.
Monthly
● Humidity: 0–
95% RH (noncondensing)
● If the input
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
104
UPS2000-G-3KRTLL
User Manual
6 UPS Maintenance
Item
Expected Result
Troubleshooting
Maintenance
Interval
Check the
monitoring panel.
According to the
status icons on
the LCD, all units
are operating
properly. No fault
or alarm
information is
found in the
active and
historical alarm
records.
If an alarm is
present, rectify
the fault by
checking the
device status and
parameters.
Monthly
Cleanliness
When the device
surface is wiped
using white paper,
the paper does
not turn black.
Remove the dust,
especially from
the front panel.
Quarterly
Parameter
settings
The settings of
the output
voltage level,
frequency, and
battery capacity
meet
requirements.
Reset the
parameters.
Quarterly
Power cables and
terminals
(between the UPS
and external
power distribution
equipment)
The insulation
layers of cables
are intact and
terminals are free
from noticeable
sparks.
● Replace the
cables.
Quarterly
Battery self-check
No battery alarm
is generated.
Identify the
causes based on
the alarm
information.
Issue 02 (2021-06-30)
● Secure the
output
terminals.
Copyright © Huawei Technologies Co., Ltd.
Yearly
105
UPS2000-G-3KRTLL
User Manual
7 Technical Specifications
7
Technical Specifications
7.1 Physical Specifications
Table 7-1 Physical specifications
Model
Net dimensions (H x W
x D)
Net weight
UPS2000-G-3KRTLL
88 mm x 438 mm x 480
mm (including the depth
of the front panel and
rear terminals)
15 kg
7.2 Environmental Specifications
Table 7-2 Environmental specifications
Item
Specifications
Operating
temperature
range
0–40°C, not derated
Humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is greater than 1000 m but less than
4000 m, the power should be derated. For details, see IEC
62040-3.
Storage and
transportation
temperatures
Issue 02 (2021-06-30)
–40°C to +70°C
Copyright © Huawei Technologies Co., Ltd.
106
UPS2000-G-3KRTLL
User Manual
7 Technical Specifications
Item
Specifications
Noise
< 55 dBA @ 1 m
IP rating
IP20
7.3 Mains Input Electrical Specifications
Table 7-3 Mains input electrical specifications
Item
Specifications
Rated input
voltage
220 V AC/230 V AC/240 V AC
Input voltage
range
110–280 V AC (normal startup); linearly derated when the
voltage is below 176 V AC; 50% loaded when the voltage is
110 V AC
Rated input
frequency
50 Hz/60 Hz
Input frequency
range
50 Hz/60 Hz±4 Hz
Input power
factor
≥0.98 (100% load); ≥ 0.94 (50% load); ≥ 0.86 (30% load)
THDi
< 6% (100% load); < 9% (50% load); < 14% (30% load)
Voltage detection
precision
2%
Generator input
capacity
≥ 1.5 times the UPS capacity
Inrush current
≤ five times the rated current
Static withstand
voltage
320 V AC input, no damage to the UPS (at least 2 hours)
7.4 Bypass Input Electrical Specifications
Table 7-4 Bypass input electrical specifications
Item
Specifications
Bypass input
voltage
220 V AC/230 V AC/240 V AC
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
107
UPS2000-G-3KRTLL
User Manual
7 Technical Specifications
Item
Specifications
Bypass voltage
range
176–280 V AC
Bypass frequency
50 Hz/60 Hz
Input frequency
range
50 Hz/60 Hz±4 Hz
Bypass overload
capability
Load ≤ 125%: continuous working
125% < load ≤ 150%: disconnect the output after 1 minute
150% < load: disconnect the output after 100 ms
Load in bypass mode = Output current/Rated output
current
Transient
withstand current
10 kA
Input mode
The mains input and bypass input share a power source.
7.5 Output Electrical Specifications
Table 7-5 Output electrical specifications
Item
Specifications
Rated capacity
3 kVA/2.7 kW
Output power factor
0.9
Rated output voltage
220 V AC/230 V AC/240 V AC
Output voltage precision
±1%
Output frequency
● When the mains is normal, the UPS
automatically tracks the mains frequency.
● When the mains is abnormal, the output
frequency is 50 Hz (tolerance ±0.5%).
System efficiency
● Maximum efficiency: ≥ 93%
● 100% load: ≥ 93%; 50% load: ≥ 92%; 30%
load: ≥ 90%
Waveform (battery mode)
Sine wave
THDv
● < 7% (non-resistive loads)
● < 3% (resistive loads)
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
108
UPS2000-G-3KRTLL
User Manual
7 Technical Specifications
Item
Specifications
Overload capability
● Load ≤ 105%: continuous working
● 105% < load ≤ 125%: transfer to bypass
mode after 10 min
● 125% < load ≤ 150%: transfer to bypass
mode after 1 min
● 150% < load: transfer to bypass mode after
0.1s
● If the output is short-circuited, the inverter
lasts for 100±20 ms.
Maximum bypass transfer
times
3
Transfer time
Transfer from
normal mode
to battery
mode
0 ms
Transfer from
inverter mode
to bypass
mode
● Uninterruptible transfer: 0 ms
● Interruptible transfer: < 10 ms
Average frequency tracking
rate
Single UPS: 2 Hz/s; Parallel system: 1 Hz/s
Output dynamic response
≤ 5% (0–100%, 100%–0% load change)
Output regulated voltage
precision
1%
Load detection precision
5%
7.6 Battery Electrical Specifications
Table 7-6 Battery electrical specifications
Item
Specifications
Battery type
Lithium battery (external), supported models:
ESM-4850A3, ESM-48100B1, and ESM-48150B1
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
109
UPS2000-G-3KRTLL
User Manual
7 Technical Specifications
Item
Specifications
Dimensions (H x W
x D)
ESM-4850A3/ESM-48100B1:
● 130 mm x 442 mm x 396 mm (excluding mounting
ears)
● 130 mm x 482 mm x 396 mm (including mounting
ears)
ESM-48150B1:
● 160 mm x 442 mm x 560 mm (excluding mounting
ears)
● 160 mm x 482 mm x 560 mm (including mounting
ears)
Weight
ESM-4850A3: 35 kg; ESM-48100B1: 44 kg; ESM-48150B1:
65 kg
Maximum
discharge power of
a single battery
50 Ah: ≤ 4 kW (single battery module)
Battery capacity
50–2400 Ah
Rated battery
voltage
48 V DC (50 Ah/100 Ah)
Battery quantity
Single UPS/Parallel system: A maximum of eight batteries
of the same model can be connected in parallel.
Charge current
limit
10–30 A
Equalized charge
voltage
50 Ah: 53.5 V DC
Float charge
voltage
50 Ah: 51 V DC
100 Ah/150 Ah: ≤ 4.3 kW (single battery module)
51.2 V DC (150 Ah)
100 Ah/150 Ah: 54 V DC
100 Ah/150 Ah: The battery float charge voltage is
adjusted by the DC-DC inside the BMS. The UPS does not
distinguish the equalized charge voltage from the float
charge voltage.
Operating
temperature
Charge: 0°C to 45°C; discharge: –20°C to +45°C
Humidity
5%–95% RH
7.7 ECO Specifications
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
110
UPS2000-G-3KRTLL
User Manual
7 Technical Specifications
Table 7-7 ECO specifications
3 kVA
Specifications
ECO voltage range
±10%
ECO frequency
range
±2 Hz
Parallel system
ECO
Not supported
7.8 Parallel System Specifications
Table 7-8 Parallel system specifications
Item
Specifications
Maximum number
of parallel UPSs
2
7.9 Safety and EMC
Table 7-9 Safety and EMC
Item
Standards Compliance
Conducted emission
(CE)
IEC 62040-2, C2
Radiated emission (RE)
IEC 62040-2, C2
Low-frequency signal
immunity
IEC 61000-2-2
ESD immunity
IEC 61000-4-2
Conducted
susceptibility (CS)
IEC 61000-4-6
Radiated susceptibility
(RS)
IEC 61000-4-3
Electrical fast
transient/burst
IEC 61000-4-4
Surge
IEC 61000-4-5
Power frequency
magnetic field
IEC 61000-4-8
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
111
UPS2000-G-3KRTLL
User Manual
7 Technical Specifications
Item
Standards Compliance
Harmonic current
IEC 61000-3-12
Voltage dip
IEC 61000-3-11
Impact current (surge
protection)
● IEC/EN 60240-2
● IEC/EN 61000-4-5
● YD/T 1095-2000
● YD/T 944-2007
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
112
UPS2000-G-3KRTLL
User Manual
A Acronyms and Abbreviations
A
Acronyms and Abbreviations
A
ASIC
application-specific integrated circuit
C
CAN
control area network
CPLD
complex programmable logical device
D
DSP
digital signal processing
E
EPO
emergency power-off
ECO
economy control operation
EOD
end of discharge
ESM
energy storage module
ESN
equipment serial number
H
HTTPS
Hypertext Transfer Protocol Secure
L
LCD
liquid crystal display
LSI
large-scale integrated
M
MIB
Issue 02 (2021-06-30)
management information base
Copyright © Huawei Technologies Co., Ltd.
113
UPS2000-G-3KRTLL
User Manual
A Acronyms and Abbreviations
N
NMS
network management system
P
PFC
power factor correction
PE
protective earthing
PL
parallel load
R
RS232
Recommend Standard 232
RS485
Recommend Standard 485
S
SELV
safety extra-low voltage
SSH
Secure Shell
T
THDv
total harmonic distortion of output
voltage
TNV
telecommunication network voltage
U
UPS
uninterruptible power system
USB
Universal Serial Bus
Issue 02 (2021-06-30)
Copyright © Huawei Technologies Co., Ltd.
114