VOLTAGE DROP SINGLE LINE DIAGRAM
(FD5 AND FD8)
SINGLE LINE DIAGRAM 1,000 MV (ASSUMPTION)
(FD5 AND FD8)
IMPEDANCE DIAGRAM 1,000 MVA (ASSUMPTION)
(FD5 AND FD8)
Zs
A. SERVICE ENTRANCE
Zt = 1.1%
B. BRANCH CIRCUIT
SERVICE EQUIPMENT
Assumption
25 kVA D,T.
7620/230 V
Zt = 1.1%
FARTHEST LOAD
SERVICE ENTRANCE CONDUCTORS:
2-14 mm² THW-2 COPPER WIRE IN 40 mm Ø uPVC
L = 4 METERS
SERVICE DROP WIRE IMPEDANCE (NOT READILY AVAILABLE)
Zse, L = 4 meters
60 A
100AF
60 A
100AF
FARTHEST LOAD
F1
Zbc, L = 180 meters
F2
FARTHEST LOAD
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
REGIONAL OFFICE NO. 02
ISABELA FIRST
DISTRICT ENGINEERING OFFICE
REGIONAL OFFICE NO. 02
PROJECT NAME AND LOCATION:
SHEET CONTENTS:
VOLTAGE DROP SINGLE LINE DIAGRAM
SINGLE LINE DIAGRAM
IMPEDANCE DIAGRAM
VOLTAGE DROP CALCULATION
SHORT CIRCUIT CALCULATION
ILLUMINATION LEVEL CALCULATION
DRAFTED:
REVIEWED:
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
SUBMITTED:
RECOMMENDED:
APPROVED:
SET NO.
SHEET NO.
FERDINAND B. DE GOLLO
ENGINEERING ASSISTANT
LEONARDO G. BALISI, JR.
PREPARED:
PROFESSIONAL ELECTRICAL ENGINEER CHIEF, PLANNING AND DESIGN SECTION
DATE:
ROGER ANTONIO R. MADDARA
ENGINEER II
DATE:
DEOFERIO P. VEHEMENTE, JR.
EVELYN C. COSTALES, Ph.D.
82
OIC - ASSISTANT DISTRICT ENGINEER
DISTRICT ENGINEER
DATE:
DATE:
85
VOLTAGE DROP SINGLE LINE DIAGRAM
(FD6)
SINGLE LINE DIAGRAM 1,000 MV (ASSUMPTION)
(FD6)
IMPEDANCE DIAGRAM 1,000 MVA (ASSUMPTION)
(FD6)
Zs
A. SERVICE ENTRANCE
Zt = 1.1%
B. BRANCH CIRCUIT
SERVICE EQUIPMENT
Assumption
25 kVA D,T.
7620/230 V
Zt = 1.1%
FARTHEST LOAD
SERVICE ENTRANCE CONDUCTORS:
2-14 mm² THW-2 COPPER WIRE IN 40 mm Ø uPVC
L = 4 METERS
SERVICE DROP WIRE IMPEDANCE (NOT READILY AVAILABLE)
Zse, L = 4 meters
60 A
100AF
60 A
100AF
FARTHEST LOAD
F1
Zbc, L = 180 meters
F2
FARTHEST LOAD
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
REGIONAL OFFICE NO. 02
ISABELA FIRST
DISTRICT ENGINEERING OFFICE
REGIONAL OFFICE NO. 02
PROJECT NAME AND LOCATION:
SHEET CONTENTS:
VOLTAGE DROP SINGLE LINE DIAGRAM
SINGLE LINE DIAGRAM
IMPEDANCE DIAGRAM
VOLTAGE DROP CALCULATION
SHORT CIRCUIT CALCULATION
ILLUMINATION LEVEL CALCULATION
DRAFTED:
REVIEWED:
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
SUBMITTED:
RECOMMENDED:
APPROVED:
SET NO.
SHEET NO.
FERDINAND B. DE GOLLO
ENGINEERING ASSISTANT
LEONARDO G. BALISI, JR.
PREPARED:
PROFESSIONAL ELECTRICAL ENGINEER CHIEF, PLANNING AND DESIGN SECTION
DATE:
ROGER ANTONIO R. MADDARA
ENGINEER II
DATE:
DEOFERIO P. VEHEMENTE, JR.
EVELYN C. COSTALES, Ph.D.
83
OIC - ASSISTANT DISTRICT ENGINEER
DISTRICT ENGINEER
DATE:
DATE:
85
VOLTAGE DROP SINGLE LINE DIAGRAM
(FD7)
SINGLE LINE DIAGRAM 1,000 MV (ASSUMPTION)
(FD7)
IMPEDANCE DIAGRAM 1,000 MVA (ASSUMPTION)
(FD7)
Zs
A. SERVICE ENTRANCE
Zt = 1.1%
B. BRANCH CIRCUIT
SERVICE EQUIPMENT
Assumption
25 kVA D,T.
7620/230 V
Zt = 1.1%
FARTHEST LOAD
SERVICE ENTRANCE CONDUCTORS:
2-14 mm² THW-2 COPPER WIRE IN 40 mm Ø uPVC
L = 4 METERS
SERVICE DROP WIRE IMPEDANCE (NOT READILY AVAILABLE)
Zse, L = 4 meters
60 A
100AF
60 A
100AF
FARTHEST LOAD
F1
Zbc, L = 180 meters
F2
FARTHEST LOAD
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
REGIONAL OFFICE NO. 02
ISABELA FIRST
DISTRICT ENGINEERING OFFICE
REGIONAL OFFICE NO. 02
PROJECT NAME AND LOCATION:
SHEET CONTENTS:
VOLTAGE DROP SINGLE LINE DIAGRAM
SINGLE LINE DIAGRAM
IMPEDANCE DIAGRAM
VOLTAGE DROP CALCULATION
SHORT CIRCUIT CALCULATION
ILLUMINATION LEVEL CALCULATION
DRAFTED:
REVIEWED:
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
SUBMITTED:
RECOMMENDED:
APPROVED:
SET NO.
SHEET NO.
FERDINAND B. DE GOLLO
ENGINEERING ASSISTANT
LEONARDO G. BALISI, JR.
PREPARED:
PROFESSIONAL ELECTRICAL ENGINEER CHIEF, PLANNING AND DESIGN SECTION
DATE:
ROGER ANTONIO R. MADDARA
ENGINEER II
DATE:
DEOFERIO P. VEHEMENTE, JR.
EVELYN C. COSTALES, Ph.D.
84
OIC - ASSISTANT DISTRICT ENGINEER
DISTRICT ENGINEER
DATE:
DATE:
85
VOLTAGE DROP SINGLE LINE DIAGRAM
(FD9)
SINGLE LINE DIAGRAM 1,000 MV (ASSUMPTION)
(FD9)
IMPEDANCE DIAGRAM 1,000 MVA (ASSUMPTION)
(FD9)
Zs
A. SERVICE ENTRANCE
Zt = 1.1%
B. BRANCH CIRCUIT
SERVICE EQUIPMENT
Assumption
25 kVA D,T.
7620/230 V
Zt = 1.1%
FARTHEST LOAD
SERVICE ENTRANCE CONDUCTORS:
2-14 mm² THW-2 COPPER WIRE IN 40 mm Ø uPVC
L = 4 METERS
SERVICE DROP WIRE IMPEDANCE (NOT READILY AVAILABLE)
Zse, L = 4 meters
60 A
100AF
60 A
100AF
FARTHEST LOAD
F1
Zbc, L = 180 meters
F2
FARTHEST LOAD
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
REGIONAL OFFICE NO. 02
ISABELA FIRST
DISTRICT ENGINEERING OFFICE
REGIONAL OFFICE NO. 02
PROJECT NAME AND LOCATION:
SHEET CONTENTS:
VOLTAGE DROP SINGLE LINE DIAGRAM
SINGLE LINE DIAGRAM
IMPEDANCE DIAGRAM
VOLTAGE DROP CALCULATION
SHORT CIRCUIT CALCULATION
ILLUMINATION LEVEL CALCULATION
DRAFTED:
REVIEWED:
BRANCH CIRCUIT CONDUCTORS:
2 - 22 mm² THWN/THHN - 2 COPPER WIRE IN 40 mm Ø uPVC
L = 180 METERS
SUBMITTED:
RECOMMENDED:
APPROVED:
SET NO.
SHEET NO.
FERDINAND B. DE GOLLO
ENGINEERING ASSISTANT
LEONARDO G. BALISI, JR.
PREPARED:
PROFESSIONAL ELECTRICAL ENGINEER CHIEF, PLANNING AND DESIGN SECTION
DATE:
ROGER ANTONIO R. MADDARA
ENGINEER II
DATE:
DEOFERIO P. VEHEMENTE, JR.
EVELYN C. COSTALES, Ph.D.
85
OIC - ASSISTANT DISTRICT ENGINEER
DISTRICT ENGINEER
DATE:
DATE:
85