SUPPLIER DOCUMENT REVIEW STATUS STATUS CODE 1 2 3 4 Work may proceed Revise and resubmit. Work may proceed subject to incorporation of changes indicated Revise and resubmit. Work may not proceed Review not required. Work may proceed Permission to proceed does not constitute acceptance of approval of design details, calculations, analyses, test methods, or materials developed or selected by the supplier and does not relieve supplier from full compliance with contractual obligations. Distribution to Arch Civil I&C Elec Mech PD QA Startup Reviewed by Arch Civil I&C Elec Mech PD QA Startup 0 .201 Responsible Engineer Issue Date Rev COMPANY CONTRACTOR SUB- CONTRACTOR / VENDOR Sanayi ve Ticaret A. . WEST QURNA 2 EARLY PRODUCTION FACILITIES GAS TURBINE POWER PLANT GTPP Company Doc. No ENKA Doc. No SIEMENS Doc. No 8015 0151 81 PO EZS0 0001 Q IQ303 000 PO EZS0 0001 Q 0000 0000 Sheet Rev. G77121 P 0100 U 00 25682 Test Report No 2010-47 Type Test of a 145 kV- Cable System Consisting of Two Outdoor Terminations, a Straight Joint, Compact Sealing End and XLPECable Client: Südkabel GmbH Rhenaniastr. 12-30 68147 Mannheim Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes 26 numbered pages and is only valid with the original signature. Copying of extracts is subject to the written authorization of the test laboratory. The test results concern exclusively the tested objects. 25683 1 Purpose of Test A 145 kV- Cable System consisting of two outdoor terminations, a straight joint, compact sealing end and XLPE-cable was subjected to a type test according to IEC 60840 04/2004 type test on accessories. 2 Miscellaneous Data Test object: – – – – – – Outdoor Sealing End, type EHFVC 145, 30 Sheds Drawing No 0.36.72.8a, dated 08.07.2010, Figure 2.1 Outdoor Sealing End, type EHFVC 170, 45 Sheds Drawing No 0.36.72.8a, dated 08.07.2010, Figure 2.1 Straight Joint, type: SEHDV 145 Drawing No 0.3600.35.2a, dated 04.08.2010, Figure 2.2 GIS Compact Sealing End, type EHSVS 145 Drawing no: 0.360.01.0a, dated 19.06.2009, Figure 2.3 150-kV-XLPE-cable, type 2XS(FL)2Y 1x2500RMS/220 87/150kV, cable 1, Figure 2.4 – 2.5 132-kV-XLPE-cable, type 1x2500 RMSCu/XLPE/ corr.Al/PE 76/132/145 kV, cable 2, Figure 2.6 Figure 3.1 shows the mounting of accessories on the two cables. Manufacturer: the different Cable 1 and accessories: Südkabel GmbH Rhenaniastr. 12-30 68147 Mannheim Cable 2: Taihan Electric Wire Co Ltd. Insong Building 194-15, Hoehyeon-dong 1-ga Jung-gu, Seoul, Korea Place of test: University of Karlsruhe Kaiserstraße 12 – 76128 Karlsruhe Testing dates: Delivery: Mounting: Test date: 26.07.2010 26.07. – 23.08.2010 26.08. – 29.09.2010 25684 Atmospheric conditions: Temperature: Air pressure: rel. humidity: 18°C - 25°C 980 - 1020 mbar 30% - 70% Representatives Dipl.-Ing.(FH) A. Jurtschin, Südkabel GmbH Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer Mr. O. Müller 25685 Figure 2.1: Outdoor Sealing End, Type EHFVC 25686 Figure 2.2: Straight Joint, Type SEHDV 145 25687 Figure 2.3: GIS Compact Sealing End, Type EHSVS 145 25688 Figure 2.4: XLPE-Cable 1, type 2XS(FL)2Y 1x2500RMS/220 87/150kV 25689 Figure 2.5: XLPE-Cable 1, type 2XS(FL)2Y 1x2500RMS/220 87/150kV 25690 Figure 2.6: XLPE-Cable 2, type 1x2500 RMSCu/XLPE/ corr.Al/PE 76/132/145 kV 25691 Tests: Test volume, chronological order and requirements conform to IEC 60840 04-2004 type test on accessories, subclause 14.3.2 Pos. 1 Check on insulation thickness Pos. 2 Partial Discharge Test û / 2 = 1,75 U0 = 133 kV 10 s thereafter ; û / 2 = 1,5 U0 = 114 kV no detectable discharge Pos. 3 Heating cycle voltage test Load cycle: 24 h 8h loading up to 95°C - 100 °C conductor temperature with at least 2h at 95°C-100°C 16h cooling Test voltage: û / 2 = 2,0 U0 = 174 kV Number of cycles: 20 Pos. 4 Partial Discharge Test û / 2 = 1,75 U0 = 133 kV 10 s thereafter ; û / 2 = 1,5 U0 = 114 kV no detectable discharge Pos. 5 Partial Discharge Test at elevated temperature 8h loading up to 95°C - 100 °C conductor temperature with at least 2h at 95°C-100°C û / 2 = 1,75 U0 = 133 kV 10 s thereafter ; û / 2 = 1,5 U0 = 114 kV no detectable discharge Pos.6 Lightning impulse voltage test at elevated temperature T = 95°C-100°C, at least 2h, û = 650 kV, 10 impulses each polarity Pos.7 AC-voltage withstand test during cooling period û / 2 = 2,5 U0 = 190 kV, t = 15 min Pos. 8 Cable and accessory examination 25692 3 Mounting The cable preparation, assembling and mounting of the cable system was accomplished by technicians of Südkabel GmbH. Fig 3.1 shows the test setup Fig 3.1: Schematic of test setup 25693 4 Test Setup 4.1 Check on Insulation Thickness The insulation thickness was measured as described in IEC 60811-1-1, subclause 8.1. For measuring the insulation thickness a profile projector with a magnification of 10 was used which allowed a reading of 0.001 mm. 4.2 AC Voltage Withstand Test The test voltage was generated by a 720-kVA transformer. The voltage was measured with a capacitive divider (CH = 351 pF; ratio = 10.000:1) and a peak voltmeter reading û / 2 . The primary side of the AC-transformer was connected to a motor-generator set consisting of a variable frequency DC motor and a synchronous generator with variable excitation. The generator delivers voltages from 0 ... 500 V with currents up to 1000 A. Figure 4.2: Test-setup for AC-voltage withstand test and PD measurement AC-transformer: 500V/600kV; SN = 720 kVA Voltage measurement: CH = 351 pF; ratio 10.000:1 uncertainty 3 % PD measurement: CC = 1000 pF; UN = 800 kVrms uncertainty 5 % 25694 4.3 Partial-Discharge Test The PD-measurement was performed with an analog bridge according to , Figure 4.3. External PDs producing common mode signals at the detector are rejected by the differential amplifier. Internal PDs represent differential mode signals and are amplified. The background noise level at 133 kVrms was 2,0 pC. Figure 4.3: Scheme of PD test circuit TO : Test object CC : Coupling Capacitor For balancing the bridge a calibrating impulse with qA = 1000 pC is applied between the terminals A (high-voltage) and C (ground) and the amplifier output is minimized. A pulse between the terminals A and C corresponds to an external PD. For the calibration a PD pulse, qA = 5 pC, is applied between A and B. Subsequently, the amplifier output of the PD measuring unit is adapted to the applied pulse. 25695 4.4 Cyclic Current Loading According to IEC the test objects must be heated by a current which provides the permitted service temperature of the tested cable plus 5 K - 10 K, that means 95°C - 100°C, for XLPE-cable. The required heating current I was determined via a dummy cable. A 8 m sample of the cable used for the test, was provided with a 1 mm diameter drilling hole down to the center conductor. The temperature was measured with a thermo couple NiCr-Ni. . Two other thermocuples were installed on the conductor of the reference cable 0,5 m away from the middle and 1,0 m away from the middle. The difference between the three readings was less than 1°C. Furthermore two additional thermocouples NiCr-Ni were placed on the outer sheath of the cable, one on the dummy and one on the test loop. Figure 4.4 illustrates the temperature rise at the conductor with a maximum heating current of I = 3900 A, 8h. Current inception was accomplished by two transformers (U1 = 400 V; U2 = 20 V) which used the cable as secondary winding. The current was regulated by a control unit and measured by a current transformer, 5000/1, and a digital multimeter. The measurement uncertainty was 1%. 25696 Figure 4.4: Heat cycle I = 2700..3300 A regulated, 8h; I = 0A, 16 h 1: Conductor temperature cable1; 2: Jacket temperature test loop, cable 1 3: Jacket temperature dummy, cable 1; 4: Temperature HV-laboratory 5: Conductor temperature cable 2; 6: Jacket temperature test loop, cable 2 7: Jacket temperature dummy, cable 2 25697 4.5 Lightning Impulse Voltage Test For lightning impulse testing 8 stages of a Marx generator (Haefely) with a maximum cumulative charging voltage of U = 1600 kV and a maximum impulse energy of Emax = 80 kW s were used. The crest value of the impulse voltage was measured by a damped capacitive divider and a subsequent impulse peak voltmeter (Haefely). The front time and the time to half value were evaluated from the oscillographs. CH Marx Generator RH CL IPV Oscilloscope TO RL Figure 4.5.1: Scheme of lightning impulse voltage test circuit CH: 1200 pF ; RH = 70 ; ratio: 3215; IPV: impulse-peak-voltmeter (Haefely) – measurement uncertainty 3% Oscilloscope: Tektronix TDS 3044B – measurement uncertainty 2% The waveform parameters were determined at reduced charging voltage. Figure 4.5.2 shows the front time, Figure 4.5.3 the time to half value for positive polarity each. Figure 4.5.4 shows the front time, Figure 4.5.5 the time to half value for negative polarity each. Positive impulse: : T1 = 3,81 s T2 = 55,2 s Negative impulse: T1 = 3,64 s T2 = 55,4 s 25698 Figure 4.5.2: Front time, positive polarity horiz.: 1 s/Div; vert.: 2V/Div; probe 10:1; ratio 3215:1 Figure 4.5.3: Time to half value, positive polarity horiz.: 10 s/Div; vert.: 2V/Div; probe 10:1; ratio 3215:1 25699 Figure 4.5.4: Front time, negative polarity horiz.: 1 s/Div; vert.: 2V/Div; probe 10:1; ratio 3215:1 Figure 4.5.5: Time to half value, negative polarity horiz.: 10 s/Div; vert.: 2V/Div; probe 10:1; ratio 3215:1 25700 5 Results 5.1 Check on Insulation Thickness The test was carried out as described in 4. Test date: 03.08.2010 5.1.1 Cable 1 Nominal value: 15,2 mm Measured Values: 14,52 mm 14,65 mm 15,07 mm 14,97 mm 14,08 mm 14,15 mm Average Value: 14,57 mm Result: The average value is 4,2% lower than the nominal value, so no correction was necessary 5.1.2 Cable 2 Nominal value: 20,0 mm Measured Values: 19,81 mm 19,78 mm 19,42 mm 19,87 mm 20,26 mm 19,99 mm Average Value: 19,86 mm Result: The average value is 0,7% lower than the nominal value, so no correction was necessary 25701 5.2 PD-Test The test was carried out as described in 4. Test date: 26.08.2010 Calibration pulse: qcal = 5 pC Background noise level: 2.0 pC Test voltage: û / 2 = 133 kV; t = 10 s, thereafter û / 2 = 114 kV; with pd reading PD: no detectable discharges The test was passed successfully 5.3 Heating cycle voltage test The test was carried out as described in 4. Test date: Test voltage: Heating current: 28.08. – 16.09.2010 û / 2 = 174 kV I = 2700..3300 A regulated, 8h I = 0A, 16 h Cycle: 8 h heating; 16 h cooling Number of cycles: 20 Neither breakdown nor flashover occurred. The test was passed successfully 5.4 PD-Test The test was carried out as described in 4. Test date: 21.09.2010 Calibration pulse: qcal = 5 pC Background noise level: 2.0 pC Test voltage: û / 2 = 133 kV; t = 10 s, thereafter û / 2 = 114 kV; with pd reading PD: no detectable discharges The test was passed successfully 25702 5.5 PD-Test at elevated temperature The test was carried out as described in 4. Test date: 24.09.2010 Calibration pulse: qcal = 5 pC Background noise level: 2.0 pC Heating current: I = 2700..3300 A regulated, 8h Temperature: T = 99.5°C Test voltage: û / 2 = 133kV; t = 10 s, thereafter û / 2 = 114 kV; with pd reading PD: no detectable discharges The test was passed successfully 25703 5.6 Lightning Impulse Voltage Withstand temperature Test at elevated This test was carried out as described in 4. Test date: 24.09.2010 Test voltage: û = 650 kV Heating current: I = 2700..3300 A regulated, 8h Temperature: T = 99.7°C Impulse: 1-5 s / 40-60 s Number of tests: 10 positive polarity, 10 negative polarity Neither flashover nor breakdown occurred at the test objects during all lightning impulse voltage tests. Table 5.6.1 shows the test results with positive polarity, table 5.6.2 with negative polarity. number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 charging voltage / kV 30,0 30,0 48,3 67,8 87,0 96,7 96,7 96,7 96,7 96,7 96,7 96,7 96,7 96,7 96,7 û / kV 202 202 324 456 585 651 651 651 650 650 651 650 650 650 650 Figure 5.6.1 5.6.1 5.6.1 5.6.1 5.6.1 5.6.2 5.6.2 5.6.2 5.6.2 5.6.2 remark front time, time to half value 50% 70% 90% 1. 100% 2. 100% 3. 100% 4. 100% 5. 100% 6. 100% 7. 100% 8. 100% 9. 100% 10. 100% Table 5.6.1: Lightning impulse voltage withstand test, positive polarity 25704 number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 charging voltage / kV û / kV - 30,0 - 30,0 - 48,3 - 67,8 - 87,0 - 96,7 - 96,7 - 96,7 - 96,7 - 96,7 - 96,7 - 96,7 - 96,7 - 96,7 - 96,7 - 202 - 202 - 324 - 455 - 586 - 650 - 650 - 649 - 650 - 650 - 650 - 650 - 650 - 650 - 650 Figure 5.6.3 5.6.3 5.6.3 5.6.3 5.6.3 5.6.4 5.6.4 5.6.4 5.6.4 5.6.4 remark front time, time to half value 50% 70% 90% 1. 100% 2. 100% 3. 100% 4. 100% 5. 100% 6. 100% 7. 100% 8. 100% 9. 100% 10. 100% Table 5.6.2: Lightning impulse voltage withstand test, negative polarity Figure 5.6.1: 100%-stress 1 - 5, positive polarity Hor.: 10 s/Div; Vert.: 5V/Div; probe 10:1; ü = 3215 25705 Figure 5.6.2: 100%-stress 6 - 10, positive polarity Hor.: 10 s/Div; Vert.: 5V/Div; probe 10:1;ü = 3215 Figure 5.6.3: 100%-stress 1 - 5, negative polarity Hor.: 10 s/Div; Vert.: 5V/Div; probe 10:1; ü = 3215 25706 Figure 5.6.4 100%-stress 6 - 10, negative polarity Hor.: 10 s/Div; Vert.: 5V/Div; probe 10:1; ü = 3215 5.7 AC Voltage Withstand Test during Cooling Period The test was carried out as described in 4. Test date: 25.09.2010 Temperature: 26.4°C Test voltage: û / 2 = 190 kV; t = 15 min Neither breakdown nor flashover occurred. The test was passed successfully. 5.10 Cable and Accessory Examination Test date: 27.09. – 29.09.2010 On completion of the electrical tests the XLPE insulation of the cable and the accessories were examined. There was no evidence of electrical activity. The test was passed successfully. 25707 6 Conclusion The 145 kV- Cable System consisting of 150kV-XLPE-cable, Outdoor Sealing End type EHFVC, Straight Joint type SEHDV and GIS Compact Sealing End type EHSVS, manufacturer Südkabel GmbH, passed all tests described in Chapter 2 successfully. The test object fulfilled the requirements according IEC 60840 042004, type test on accessories. Karlsruhe, 08.11.2010 Dr.-Ing. R. Badent Head of Department „High Voltage Dielectric Testing“ Dr.-Ing. B. Hoferer Vice-Head of Department „High Voltage Dielectric Testing“ 25708