TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 LINE ROUTES 2.1 2.2 2.3 2.4 3.0 Location Paralleling and Crossing Transmission Lines Paralleling and Crossing Major Highways Vertical Clearances above Ground, Road Crossings and Paralleling, Crossing of Rail Road GENERAL GUIDE LINES FOR METALLIC FACILITIES LOCATED IN PROXIMITY OF TRANSMISSION LINES ( INDUCED / CONDUCTIVE VOLTAGE INTERFERENCES) 3.1 3.2 3.3 Inductive & Conductive Voltage Requirements Paralleling Facility (Induced Voltage Case) Crossing Facility (Conductive Voltage Case) 4.0 SPACING FROM MAIN OIL FACILITIES 5.0 CONDUCTOR SPACING AND CLEARANCE 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 Clearance between Phase Conductors on the same Support Vertical Clearance between Line Conductors. Clearance of Conductor from its own Support - Basic Clearance. Clearance between Phase Conductors carried on different Supports Clearance of Conductors from other supporting Structures Clearance of Conductors from other Installations Midspan Clearance Air Gap Requirements TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 2 OF 39 TRANSMISSION ENGINEERING STANDARD 6.0 RIGHT-OF-WAY WIDTH REQUIREMENTS 6.1 6.2 6.3 6.4 6.5 7.0 TES-P-122.09, Rev. 0 General Conductor Clearance to edge of Right-of-Way Right-of-Way Width Requirements for Single Transmission Line Right-of-Way Width Requirements for Parallel Transmission Lines Example Calculation of Right-Of-Way BIBLIOGRAPHY FIGURE TE-2209-0100-00 Clearance Requirement for Conductors of Same Circuit or Different Circuit on the Same Support FIGURE TE-2209-0200-00 Clearance Requirement for Conductors from other Circuits and Right-Of-Way (ROW) for Single Transmission Line FIGURE TE-2209-0300-00 Clearance Requirement between Conductors on Different Supports and Conductors from other Supporting Structures and Right-Of-Way (ROW) for Two Parallel Transmission Lines FIGURE TE-2209-0400-00 Right-Of-Way (ROW) Requirement for Two Parallel Transmission Lines TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 3 OF 39 TRANSMISSION ENGINEERING STANDARD 1.0 TES-P-122.09, Rev. 0 SCOPE The purpose of this standard is to highlight Saudi Electricity Company (SEC), Saudi Arabia practices with respect to clearances required for various paralleling and crossing facilities and right of way requirements. 2.0 LINE ROUTES 2.1 2.2 2.3 Location 2.1.1 Transmission lines shall be located as near as possible to roads for easy accessibility during construction and later for inspection, insulator washing, maintenance and repair. Obstacles such as high hills, wadis, water flooding areas, swampy ground or poor soils shall be avoided. Selection of routes shall also take into account grade and conditions of the terrain to be traversed. 2.1.2 Selection of final route for any transmission line shall be coordinated with the concerned SEC departments. 2.1.3 Coastal or corrosive atmosphere areas shall be avoided wherever possible. Whenever it is not possible suitable protective measures shall be adopted in the design of transmission line components including foundations to combat the corrosion. Paralleling and Crossing Transmission Lines 2.2.1 Adequate clearance shall be provided between parallel and crossing transmission lines. Clearances between adjacent conductors of two parallel lines and clearances between crossing lines shall be established per equations 09-1 to 09-19. 2.2.2 Crossing lines shall be arranged so that the higher voltage line or line of higher security crosses over the line of lower voltage or lower security. It is preferable that transmission lines shall cross each other at right angles. 2.2.3 The vertical clearance between any crossing lines carried on different supporting structures shall not be less than those given in Table 09-13. Paralleling and Crossing Major Highways 2.3.1 TESP12209R0/MAA Major highways are defined as any primary or secondary roads which are normally accessible to traffic with no restriction. Minimum clearances from the nearest conductor to edge of major highways for restricted and unrestricted rights of way are given in Table 09-1. Date of Approval: December 12, 2007 PAGE NO. 4 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Table 09-1: Minimum Distance from nearest Conductor to edge of Major Highways Voltage, (kV) 69 110 115 132 230 380 2.4 Right of Way Not-Restricted, (m) Maximum Height of Transmission Line Structure Plus 5 meters Right of Way Restricted, (m) 18 25 25 25 30 40 2.3.2 Where transmission line routes cross major highways, the angle of intersection shall be as near as possible to 90 degrees and if not possible, the angle of intersection shall be between 45 to 135 degrees. The edge of the nearest transmission line structure foundation shall not be closer than a distance equal to the maximum height of the structure installed when measured from the edge of zone of major highways. 2.3.3 When paralleling roads other than major highways, especially roads in urban areas, lesser clearances than required by paragraph 2.3.1 are permissible between roads and transmission lines provided that public safety and safety & reliability of the lines are not affected. When necessary, the line structures shall be protected by providing crash barriers around them without jeopardizing access to the line for maintenance. These protective measures shall be considered individually on a project basis for their effectiveness. Vertical Clearances above Ground and Road Crossings and Paralleling, Crossing of Rail Road 2.4.1 Vertical clearance is defined as the vertical distance between the highest point on terrain (grade, road surface, rail road, rail etc.) and the lowest conductor of the overhead lines. Calculation of actual line clearance at final tension shall be based on a temperature of 80°C for ACSR & AAAC, 85°C for ACAR and 93°C for ACSR/AW conductor. Grading of existing natural ground level to meet the vertical clearance requirements shall not be acceptable unless otherwise approved by SEC. 2.4.2 The minimum vertical clearances required for SEC transmission line designs for 380 kV and below over various types of roads and terrain are given in Table 09-2 and shall be followed unless otherwise specified in the approval letters of different approval agencies involved. 2.4.3 Roads to be crossed by SEC transmission lines have been categorized as “A”, designated high clearance roads; and “B”, for other roads not requiring high clearance. 2.4.4 There are some areas where certain road crossings shall require additional clearance. The extra high clearance roads in the industrial areas such as Jubail, Dammam, Yanbu, etc. may require a vertical clearance in the range of 18-21 meters above roads or highways. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 5 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 2.4.5 The category of roads to be crossed by the transmission line shall be determined during base design stage and in case of module paths the concerned authorities shall be contacted to coordinate the vertical clearance requirements. 2.4.6 Highways and roads designated to be used for hauling heavy and oversized loads are classified as Category ‘A’. All other roads, highways and expressways are classified Category ‘B’. 2.4.7 On projects where the transmission line is determined to be extremely important (such as 230 kV and 380 kV System) and power interruption can not be tolerated, then all roads to be crossed by this line shall be considered as Category “A” roads, and the Project Scope of Work and Technical Specifications for such a project shall explicitly state this requirement. 2.4.8 The road clearances in this Standard for designated high clearance roads and expressways and highways considerably exceed the minimum requirements recommended by the NESC for vertical clearances above roadways. 2.4.9 The vertical clearances over the type of terrain not covered by Table 09-2, such as canals, waterways, terrain in the vicinity of airports or any unusual situation which might be developed, shall be resolved separately and mutually agreed to by interested parties. Table 09-2: Minimum Vertical Clearances for Roads and Terrain Crossings (see note 5) Transmission Voltage (Line to Line) Category A. B. C. D. Type of Crossing Designated High Clearance Roads (1) Expressways & Highways City Streets, Alleys Driveways, Parking Lots & Other Areas Traversed by Vehicles, Paved or Unpaved Open Terrain, Desert Areas, etc (3, 4). 69kV (m) 110kV (m) 115kV (m) 132kV (m) 230kV (m) 380kV (m) 14.0 14.0 14.0 15.0 18.0 18.0 12.0 12.0 12.0 13.0 15.0 15.0 12.0 12.0 12.0 13.0 15.0 15.0 7.5 7.5 7.5 7.5 8.0 10.0 E. Railroads (2) 15.5 15.5 15.5 16.0 18.0 18.0 F. Ground Facilities, Pipelines (Oil, Water, Gas) & Communication lines 9.5 9.5 9.5 9.5 9.5 13.5 Notes: 1. TESP12209R0/MAA Roads categorized as “A” are those specifically designated by SEC Lines Maintenance Department as roads requiring vertical clearance in excess of clearances listed in Category Date of Approval: December 12, 2007 PAGE NO. 6 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 “B” and “C”. Vehicle traffic is expected to exceed 5.5 meter height and the transmission lines need not normally be removed from service. 2. Assumed height of the rail car is 6 meters. 3. For transmission lines when located in open terrain within 5km and 2km from the boundary limits of cities/towns and villages respectively, the required clearances listed under Category “D” shall be increased by a minimum of two (2) meters. 4. When transmission lines are located in desert area affected by shifting sand dunes, the clearance listed in Category “D” shall be increased by a minimum of two (2) meters in the spans indicating shifting sand dunes. 5. The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. 2.4.10 Paralleling and Crossing Railroads a. Minimum clearances from the nearest conductor to edge of the rail track for restricted and unrestricted rights of way are given Table 09-3. b. Where transmission line routes cross railroad tracks, the angle of intersection shall preferably be 90 degrees and if not possible, the angle of intersection shall be between 70 to 110 degrees. The edge of the transmission line structure foundation shall not be closer than 50 meters on 69kV through 380kV transmission lines to the edge of the railroad track. Whenever the required crossing angle is not satisfied, the Engineer responsible for base design/detailed engineering shall perform an induced voltage study and recommend possible steps to be taken to reduce any adverse effects. c. The minimum vertical clearances required for SEC transmission lines for 69 kV to 380kV, over the railroad tracks are given in Table 09-2. Table 09-3: Minimum Clearances for Paralleling of Railroad Voltages, (kV) 69 110 115 132 230 380 TESP12209R0/MAA Right-of-Way Unrestricted, (m) Restricted, (m) 40 25 40 25 40 25 40 25 40 30 40 40 Date of Approval: December 12, 2007 PAGE NO. 7 OF 39 TRANSMISSION ENGINEERING STANDARD 3.0 TES-P-122.09, Rev. 0 GENERAL GUIDELINES FOR METALLIC FACILITIES LOCATED IN PROXIMITY OF TRANSMISSION LINES (INDUCED/CONDUCTIVE VOLTAGE INTERFERENCES) 3.1 Inductive and Conductive Voltage Requirements. The guidelines listed below shall be followed for all the requests of customer metallic facilities, such as pipelines, rail road, communication cables, cathodic protection systems, etc., (whether overhead, above-ground or under-ground) to cross and/or run in close proximity to SEC transmission lines. The following guidelines shall be applied to all facilities in a single location in case more than one facility is involved in the request. 3.1.1 3.1.2 SEC approval for allowing other parties to construct and install their projects in parallel to and/or crossing the transmission lines shall be granted if the project proponent satisfy all the following conditions: a. Accepts full liability and any consequential damages due to the electrical interference (induced/conductive voltage) effects and satisfies conditions given in Clause 3.3.1 and 3.3.2 below (for crossing only). b. Performs at his expense induced/conductive voltage study and proves to SEC’s satisfaction that the resulting touch voltages are within the limits specified in Clause 3.1.2 and 3.1.3 below and satisfies the conditions given in Clause 3.3.1 and 3.3.2 below (for crossing only). c. Satisfies the requirements specified in Clause 3.2 and 3.3. The maximum touch voltage limit to insure safety to personnel during steady-state conditions shall be as follows: Conditions Continuous Voltage Continuous Current 3.1.3 Limits 15 volts 10 milli-amperes The maximum touch voltage limit to insure safety to personnel during fault conditions shall be according to the following ANSI/IEEE 80 equation: Vtouch = 116 + (017 . ρ) t Where: ρ = Surface soil resistivity in ohms-meters t = Fault duration in seconds. This shall be taken as 0.5 seconds or backup clearing time whichever is higher. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 8 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Therefore, for 500 ohm-meter top soil resistivity and 0.5 second fault clearing time, the safe touch voltage limit is 284 volts. 3.1.4 3.2 If the proponent’s induced/conductive voltage study show the need to install mitigation to limit the touch voltage, Transmission Asset Planning Department (TAPD) shall review the case to determine that the appropriate procedures are followed. Paralleling Facility (Induced Voltage Case) When the rights of ways are unrestricted following minimum spacing between the centerlines of transmission lines and above grade or below grade metallic facility shall be maintained. In case the minimum distances cannot be maintained the request shall be referred to TAPD for review. Table 09-4: Clearances for Induced Voltage for Metallic Facility Voltage Level 69kV to 132kV 230kV and 380kV 3.3 Clearance, (m) 150 300 Crossing Facility (Conductive Voltage Case) 3.3.1 The minimum vertical clearance between the transmission lines and ground facilities shall be per Table 09-2. 3.3.2 When ground facilities cross transmission line access roads, the facility crossing shall be designed to provide safe passage of vehicular traffic. For unpaved crossing of above grade facility, refer TES-P-122.11. 3.3.3 When the facility routes cross overhead transmission line the preferred angle of intersection is 90 degrees and if not possible crossing angle between 70 to 110 degrees shall be acceptable. 3.3.4 The facility shall cross the transmission line at mid span between towers, otherwise the crossing shall be minimum 100 meters away from the nearest transmission line foundation for 230 kV and 380 kV transmission lines and minimum 50 meters away from the nearest transmission line foundation for 69kV, 110kV, 115kV and 132kV transmission lines. 3.3.5 If the facility runs parallel to the transmission line after the intersection then it shall also meet minimum distance requirements mentioned under clause 3.2 above. If the metallic facility is crossing below the grade and changing its direction at a distance less than 300 meters (for 230kV and 380kV transmission lines) and 150 meters (for 69kV, 110kV, 115kV and 132kV transmission lines) from crossing, the facility shall be grounded at the point where the direction is changing. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 9 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 If the metallic facility is crossing above the grade, the facility shall be grounded up to 100 meters along the length of the facility in both directions from the crossing point. If the facility is changing its direction at a distance greater than 100 meters and less than 300 meters (for 230kV and 380kV transmission lines) and 150 meters (for 69kV, 110kV, 115kV and 132kV transmission lines) from the crossing point, additional grounding shall be provided at the point where the direction is changing. The grounding of the metallic facility shall be to the satisfaction of the concerned party. 4.0 SPACING FROM MAIN OIL FACILITIES Horizontal spacing between the edge of the foundation of the transmission lines and edge of the main oil facilities shall be provided for safe operation and maintenance of both. Minimum spacing for 69 kV to 380 kV transmission lines to main oil facilities shall be as follows: Table 09-5 Minimum Spacing for Oil Facilities Oil Facility Type Oil Wells and GOSPs Oil Trunk Ground Flares and Burn Pits Elevated Flare Stacks Oil-Water Separators and Skimming Ponds Other Oil Process Areas 5.0 Spacing, (m) 200 150 150 60 60 60 CONDUCTOR SPACING AND CLEARANCE 5.1 Horizontal Clearance between Phase Conductors on the same Support 5.1.1 Horizontal Clearance - Fixed Support Phase conductors attached to fixed supports shall have horizontal clearances from each other not less than the larger value required by equations given below: a. Phase Conductors of the Same Circuit i. ii. b. (Eq.09-1) (Eq.09-2) Phase Conductors of Different Circuits i. ii. TESP12209R0/MAA H = 300+10 (U-8.7) F = 7.6 (U)+8 2.12 S H = 725+10 (Uo-50) F = 7.6 (Uo)+ 8 2.12 S Date of Approval: December 12, 2007 (Eq.09-3) (Eq.09-4) PAGE NO. 10 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Where: H = Basic horizontal clearance between phase conductors in mm. F = The horizontal clearance due to sag between phase conductors in mm. U = The maximum operating voltage phase to phase over 8.7 kV Uo= Maximum operating voltage between line conductors of different circuits which shall be the greater of the phasor difference between the conductor involved, or the phase-to-ground voltage of the higher voltage circuit. For circuits having the same phases and nominal voltage, either circuit may be considered to be the higher voltage circuit. S = Final unloaded sag based on computed ruling span at every day conductor temperature, no wind, in mm. A margin of 0.6m shall be added to the claculated values to account for design errors. The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. 5.1.2 Horizontal Clearance - Suspension Insulators Where suspension insulators are used and are not restrained from movement, the clearance shall be increased so that one string of insulators may swing transversely through a range of insulator swing up to its maximum design swing angle without reducing the values given in equations 09-1 to 09-4 and 09-11 to 09-16. The maximum design swing angle shall be based on 1064 N/m2 wind on the insulator. a. The insulator swing shall be calculated as follows: For maximum angle of swing: ⎡ 2T Sin (θ/2 ) + (HS x Pc ) ⎤ φ = Arc Tan ⎢ ⎥ ⎣ (VS x W c ) + Wi /2 ⎦ (Eq.09-5) For minimum angle of swing: ⎡ 2T Sin (θ / 2) − ( HS x Pc ) ⎤ φ = Arc Tan ⎢ ⎥ ⎣ ( VS x Wc ) + Wi / 2 ⎦ Where (Eq.09-6) φ = angle with the vertical through which the insulator string swings TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 11 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 θ = line angle in degrees T = conductor tension at the temperature and wind loading for which the clearance is specified, in Newtons HS = horizontal span, which is 1/2 the sum of adjacent spans, in meters VS = vertical span, which is the distance between the low point of sag in adjacent spans, in meters Pc = wind load per unit length of conductor (conductor diameter times wind pressure), in Newtons/meter Wc = weight per unit length of bare conductor, in Newtons/meter Wi = weight of insulator string divided by number of conductors per phase, in Newtons b. The horizontal swing of insulators can be obtained from the equation: B = (Insulator assembly length) Sin φ Where: φ is the maximum swing angle calculated per equation 09-5. 5.1.3 Horizontal Clearance for different Circuits where one or both Circuits exceed 98kV Phase-to-Ground a. The clearances specified in equations 09-1 to 09-4 and equations 09-5 and 09-6 may be reduced for circuits with known switching surge factors shall not be less than the clearances derived from the equation below: 1.667 ⎡ U (SSF) a ⎤ Min. clearance (H) = 1000⎢ L − L ⎥⎦ 500k ⎣ Where: ×b (Eq.09-7) UL-L = Maximum alternating current crest operating voltage between phases of different circuits. If the voltages are of the same phasor and magnitude, one phase conductor shall be considered grounded. SSF = Maximum switching surge factor expressed in per unit peak operating voltage between phases of different circuit. (SSF value shall be obtained from Transmission Asset Planning Department). a = 1.15, the allowance for three standard deviations TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 12 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 b = 1.03, the allowance for nonstandard atmospheric conditions. k = 1.4, the configuration factor for a conductor-to-conductor gap The clearance shall be increased @ 3 % for each 300m in excess of 450m above mean sea level. b. 5.1.4 5.2 The clearance derived from above equation shall not be less than the basic clearance given in equations 09-1 to 09-4. The method on how to determine the horizontal clearance between conductors of the same or different circuits on the same support is shown in Figure TE-2209-0100-00. Vertical Clearance between Line Conductors All conductors located at different levels on the same supporting structure of the same or different circuits for the same sag, shall have vertical clearances not less than required by the equations given below: 5.2.1 For Phases of the same Circuit a. Vs = 830+10 (U-50) (Eq.09-8) Where: Vs = Basic vertical clearance phase-to-phase, in mm U = Maximum operating voltage phase-to-phase, over 50 kV b. Minimum vertical clearances calculated based on the above equation are tabulated below: Table 09-6: Vertical Clearances between Line Conductors for same Circuit on the same Structure Nominal Voltage, (kV) 69 110 115 132 230 380 Vertical Clearance between Phases of the same Circuit on the same Structure, (m) 1.10 1.60 1.60 1.80 2.90 4.60 Notes: 1. A margin of 0.15m shall be added to account for design errors. TESP12209R0/MAA 2. The clearances at the supporting structures shall be increased to compensate the reduction in span clearances caused by jumping of conductors in the longer spans. 3. The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. Date of Approval: December 12, 2007 PAGE NO. 13 OF 39 TRANSMISSION ENGINEERING STANDARD 5.2.2 TES-P-122.09, Rev. 0 For different Circuits on the same Structure of different Nominal Voltage a. Vc = 830+10[(U01+U02)-50] (Eq.09-9) Where: Vc = Basic vertical clearance between circuits in mm U01 = Maximum phase-to-ground voltage of circuit at upper level, over 50 kV U02 = Maximum phase to ground voltage of circuit at lower level, over 50 kV When the circuits have the same nominal voltage, either circuit may be considered to be the higher voltage circuit. b. Minimum vertical clearances were calculated based on the above equation and tabulated below: Table 09-7: Vertical Clearance between different Circuits on the same Structure for different Voltages Nominal Circuit Voltages, (kV) 69/69 110/110 115/115 132/132 230/230 380/380 Vertical Clearance between different Circuits on the same structure of different Nominal Voltages, (m) 1.20 1.75 1.80 2.0 3.25 5.15 Notes: 1. A margin of 0.15m shall be added to account for design errors. 5.2.3 2. The clearances at the supporting structure shall be so adjusted that the clearances at any point in the span shall not be less than the values given in the table when measured with upper conductor at final unloaded sag at the maximum temperature for which the conductor is designed to operate and the lower conductor at final unloaded sag under the same ambient conditions and without electrical loading. 3. The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. Clearances for different Circuits where one or both exceed 98kV to Ground The clearances specified in equations 09-8 and 09-9 may be reduced for circuits with known switching surge factors, but shall not be less than the clearances required by the equation below: TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 14 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 ⎡ ( U (SSF) + U L ) a ⎤ Min. Clearance (V) = 1000⎢ H ⎥ 500k ⎣ ⎦ Where: 1.667 × bc (Eq.09-10) UH = Higher voltage circuit maximum crest operating voltage to ground UL = Lower voltage circuit maximum crest operating voltage to ground SSF = Higher voltage circuit maximum switching surge factor expressed in per-unit peak voltage to ground. (SSF value shall be obtained from Transmission Asset Planning Department). a = 1.15, the allowance for three standard deviations b = 1.03, the allowance for nonstandard atmospheric conditions. c = 1.2, the margin safety k = 1.4, the configuration factor for conductor-to-conductor gap The clearance shall be increased @ 3 % for each 300m in excess of 450m above mean sea level. 5.3 Clearance of Conductor from its own Support - Basic Clearance 5.3.1 Clearance in any direction from a line conductor to the surface of its own support structure shall not be less than that calculated by the following equation: Clearance ‘T’ = 330mm+5mm (U-50) (Eq.09-11) Where, U = Maximum operating voltage phase-to-phase, over 50kV Minimum clearances of phase conductor to its own supporting structure were calculated based on the above equation and tabulated below: Table 09-8: Clearance of Phase Conductor to its own Support Nominal Voltage, (kV) 69 110 115 132 230 380 Clearance of Phase Conductor to its own Support Arm and Structure, (m) No Wind Condition Maximum Wind Condition 0.69 0.50 1.30 0.70 1.30 0.75 1.50 0.80 2.1 1.35 3.50 2.20 Notes: 1. A margin of 0.15m shall be added to account for design errors. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 15 OF 39 TRANSMISSION ENGINEERING STANDARD 5.3.2 TES-P-122.09, Rev. 0 2. The clearances (maximum wind) given in the above table shall be maintained when the insulator strings and conductors swing transversely upto maximum design swing angle. 3. The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. Clearances of Conductor from its own Support-Alternate Clearances for Voltages exceeding 98kV Phase to Ground The clearances specified in Eq.09-11 may be reduced for circuits with known switching surge factor but shall not be less than the clearances derived from the equation shown below: 1.667 ⎡ U (SSF) a ⎤ Min. Clearance (T) = 1000⎢ L-G ⎥⎦ 500k ⎣ Where: ×b (Eq.09-12) UL-G = Maximum alternating current crest operating voltage to ground; SSF = Maximum switching surge factor expressed in per-unit peak voltage to ground a = 1.15, the allowance for three standard deviations with fixed insulator supports a = 1.05, the allowance for one standard deviation with free swinging insulators b = 1.03, the allowance for nonstandard atmospheric conditions; k = 1.2, the configuration factor for conductor-to-tower window. The clearance shall be increased @ 3 % for each 300m in excess of 450m above mean sea level. 5.3.3 TESP12209R0/MAA When suspension insulators are used and are not restrained for movement, the clearance shall be increased so that the insulator strings may swing up to maximum design angle without reducing the values as tabulated in Table 09-8. The maximum insulator swing angle shall be determined as outlined in equation 09-5. Date of Approval: December 12, 2007 PAGE NO. 16 OF 39 TRANSMISSION ENGINEERING STANDARD 5.4 TES-P-122.09, Rev. 0 Clearance between Phase Conductors carried on different Supports 5.4.1 Horizontal Clearance between Conductors a. Basic Clearance The horizontal clearance between adjacent conductors carried out on different supporting structures shall not be less than required by the equation below: Clearance = 1500mm+10mm [(U01+U02)-129] (Eq.09-13) Where: U01 = Maximum Phase-to-Ground Voltage of Line #1, over 50 kV U02 = Maximum Phase-to-Ground Voltage of Line #2, over 50 kV The clearance shall be maintained when one insulator string swings upto its extreme position while the string of adjacent conductors remains at rest. A margin of 0.6m shall be added to the claculated values to account for design errors. The clearance shall be increased @ 3 % for each 300m in excess of 1,000m above mean sea level. b. Alternate Clearances for Voltages exceeding 98kV Phase-to-Ground The clearances specified in equation 09-13 may be reduced for circuits with known switching surge factor but shall not be less than the clearances derived from the equation 09-7. 5.4.2 Vertical Clearance between Phase Conductors a. Basic Clearance The vertical clearance between any crossing or adjacent conductors carried on different supporting structures of the same or different nominal voltages shall not be less than that shown in Table 09-9 or as required by the following equation, whichever is larger. Clearance = 600mm+10 [(U01-22)+(U02-22)] (Eq.09-14) Where: U01 = Maximum phase-to-ground voltage of Line at upper level, over 22 kV TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 17 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 U02 = Maximum phase-to-ground voltage of Line at lower level, over 22 kV Table 09-9: Minimum Vertical Clearance between Conductors where the Conductors of one Line cross over the Conductors of another Lower Level Conductor Type of Crossing 69kV Transmission Lines 110kV Transmission Lines 115kV Transmission Lines 69kV (m) 1.10 - Upper Level Conductor Transmission Voltages (Line to Line) 110kV 115kV 132kV 230kV (m) (m) (m) (m) 1.40 2.10 1.60 - 1.70 - 2.40 380kV (m) 3.10 3.30 3.40 132kV Transmission Lines 1.90 3.50 230kV Transmission Lines 3.20 4.10 380kV Transmission Lines 5.10 Distribution Lines 0.90 1.20 1.30 1.40 2.05 3.02 (34.5kVand below) Overhead Ground Wire, 1.40 1.70 1.70 1.80 2.50 3.40 Guys and Span Wires Communication Lines 2.0 2.20 2.30 2.50 3.10 4.10 Notes: 1. Additional margins of 1.0m and 2.0m (total 3.0m) shall be added to account for design errors and wind induced dynamic conductor movement/safety during maintenance operations respectively. 2. The clearances shall be maintained under the conditions, when upper level conductors are at the final unloaded sag at maximum design temperature of conductor and lower level conductors are at the initial sag at the minimum design temperature of conductor or at final unloaded sag under the same ambient condition without electrical loading whichever results in larger difference. 3. The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. b. Alternate Clearances for Voltages exceeding 98 kV Phase-ToGround The clearances specified in equation. 09-14 may be reduced where the higher voltage circuit has a known switching surge factor but shall not be less than the clearances derived from the equation 09-10. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 18 OF 39 TRANSMISSION ENGINEERING STANDARD 5.5 TES-P-122.09, Rev. 0 Clearance of Conductors from other supporting Structures Conductors of one line passing near a lighting support, traffic signal support, or a supporting structure of a second line, without being attached thereto, shall have clearance from any part of the structure not less than calculated by the equation below: 5.5.1 Horizontal Clearance a. Clearance “G” = 1500mm+10mm (U0-50) (Eq.09-15) Where U0 is the maximum operating voltage phase-to-ground, in excess of 50kV. Minimum horizontal clearance of a line conductor to a rigid supporting structure, other than its own, based on the above equation was calculated and tabulated in Table 09-10. Table 09-10: Horizontal Clearance of Conductor from other Supporting Structure Nominal Voltage, (kV) 69 110 115 132 230 380 Minimum Horizontal Clearance of Conductor from other Supporting Structure, (m) 1.50 1.70 1.75 1.85 2.50 3.50 Note: A margin of 0.6m shall be added to account for design errors and the clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. b. These clearances have to be increased by the distance resulting from horizontal swing of the conductor and insulator assembly due to wind. i. The maximum insulator swing angle can be determined by equation. 09-5. ii. The maximum design swing angle shall be based on a 1064 N/mm2 wind on the conductor, final sag at every day temperature. The conductor swing shall be calculated as follows: φ = Arc Tan (Pc/Wc) (Eq.09-16) Where: Pc and Wc are defined in equation 09-6. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 19 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 The horizontal swing of conductors due to wind can be obtained from the equation: C = Sc x sin φ (Eq.09-17) Where: Sc is the conductor sag, shall be final sag based on computed ruling span at every day temperature, with 1064 N/mm2 wind. 5.5.2 Vertical Clearance Min. Clearance = 1700 mm + 10 mm (U0-50) (Eq.09-18) Where: U0 = Maximum operating Voltage Phase-to-Ground, in excess of 50kV. Minimum vertical clearance of a line conductor to a rigid supporting structure, other than its own, was calculated based on the above equation and given in Table 09-11. Table 09-11: Vertical Clearance of Conductor from other Supporting Structure Nominal Voltage, (kV) 69 110 115 132 230 380 Minimum Vertical Clearance of Conductor from other Supporting Structure, (m) 1.70 1.90 1.95 2.05 2.70 3.70 Note: A margin of 1.0m shall be added to account for design errors and the clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. 5.5.3 Alternate Clearance for Voltages exceeding 98kV to Ground The clearances specified in equations 09-15 and 09-18 may be reduced for circuits with known switching surge factors but shall not be less than the values derived from the following equations. a. Min. horizontal clearance in mm ⎡ U (SSF) a ⎤ = 1500 + 1000⎢ L− G ⎥ 500k ⎦ ⎣ TESP12209R0/MAA 1.667 × bc Date of Approval: December 12, 2007 (Eq.09-19) PAGE NO. 20 OF 39 TRANSMISSION ENGINEERING STANDARD b. TES-P-122.09, Rev. 0 Min. vertical clearance ⎡ U (SSF) a ⎤ = 1800 + 1000⎢ L− G ⎥ 500k ⎦ ⎣ Where: 1.667 × bc (Eq.09-20) UL-G = The maximum crest operating voltage to ground SSF = Maximum switching surge factor expressed in per-unit peak voltage to ground (SSF value shall be obtained from Transmission Asset Planning Department). a = 1.15, the allowance for three standard deviations b = 1.03, the allowance for nonstandard atmospheric conditions c = Margin of safety, 1.2 for Vertical clearances and 1.0 for horizontal clearances k = 1.15, the configuration factor for Conductor-to-Plane gap The clearances shall be increased @ 3 % for each 300m in excess of 450m above mean sea level. 5.6 Clearances of Conductors from other Installations The horizontal and vertical clearances of line conductors from other structures such as tall buildings, signs, chimneys, TV masts, lighting poles, monuments in the round-abouts,etc., shall be established as required, taking into consideration all local conditions and the latest government and owner regulations. 5.6.1 Basic Clearance Minimum clearances of wires, conductors and cables passing by, but not attached to building and other installations, shall not be less than those given in the following table. The horizontal clearance mentioned in the table shall be maintained when the conductor swings upto the design swing angle. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 21 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Table 09-12: Minimum Clearance of Conductors Adjacent to but not attached to Buildings and other Installations except Bridges (see notes 5 and 6) Clearance of Communication Cables and Grounded Guys (m) Phase Conductors 69kV (m) 110kV (m) 115kV (m) 132kV (m) 230kV (m) 380kV (m) 1.40 2.55 2.80 2.85 2.95 3.60 4.55 1.40 2.55 2.80 2.85 2.95 3.60 4.55 1.40 2.55 2.80 2.85 2.95 3.60 4.55 Above or below roof or projection not accessible to pedestrians (1) 0.90 4.05 4.30 4.35 4.50 5.10 6.10 Above or below balconies and roofs accessible to pedestrians (1) 3.20 4.35 4.60 4.65 4.80 5.40 6.35 Above roofs accessible to truck traffic (2) 3.20 4.35 4.60 4.65 4.80 5.40 6.35 4.70 5.85 6.10 6.15 6.30 6.90 7.85 0.90 2.55 2.80 2.85 2.95 3.60 4.55 Buildings (Horizontal) To wall and projections (3) To unguarded windows (4) To balconies and areas accessible to pedestrians (1) Buildings (Vertical) Above roofs accessible to vehicles but not subject to truck traffic Signs, Chimneys, radio and television antennas, lighting poles, monuments in the round-abouts tanks and other installations not classified as buildings: Horizontal Vertical above or 4.70 below 0.90 2.70 2.95 3.00 3.10 3.70 Notes: 1. A roof, balcony or area is considered accessible to pedestrians if the means of access is through a doorway, ramp, stairway or permanently mounted ladder. 2. For the purpose of this rule, trucks are defined as any vehicle exceeding 2.45 m in height. 3. This clearance may be reduced to 75 mm for the grounded portions of guys. 4. Windows not designed to open may have the clearances permitted for walls and projections. 5. 6. TESP12209R0/MAA A margin of 1.0m shall be added to account for design errors. The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. Date of Approval: December 12, 2007 PAGE NO. 22 OF 39 TRANSMISSION ENGINEERING STANDARD 5.6.2 TES-P-122.09, Rev. 0 Alternate Clearance for Voltages exceeding 98kV to Ground The clearance specified in Table 09-12 may be reduced for circuit with known switching surge factors but shall not be less than the values derived from equations 09-19 and 09-20. 5.7 Midspan Clearance The separation between the overhead ground wire and the top conductor is a function of the actual structure footing resistance, wind speed, the number of insulators in the insulator string, type of insulator, the span length and the acceptable number of outages per 100 km per year. 5.7.1 The clearance at midspan between the overhead ground wires and the conductors shall be greater than that at the structure and shall be well coordinated so that the flashover occurs at the structure. 5.7.2 Line voltages have little relationship on the required midspan clearances. The midspan clearances for SEC 69kV through 380 kV transmission lines shall not be less than those tabulated below. The clearances shall be maintained at every day temperarure, final sag with no wind and shall be satisfied for the largest span encountered in a transmission line section. The values for intermediate spans may be interpolated. Table 09-13: Midspan Clearance Conductor to OGW Span, (m) Midspan Clearance Conductor to OGW, (m) 91 2.7 122 3.1 152 3.7 183 4.6 213 6.1 244 7.3 305 9.7 350 11.3 366 11.9 427 13.7 488 15.5 549 17.4 Note: The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. 5.7.3 5.8 For spans longer than those in the above table, the final sag of the overhead ground wire with no wind at every day temperature shall about 80 per cent of conductor sag. Air Gap Requirements 5.8.1 Shielded Lines To maintain adequate clearances the air gap distance between any conductor and structure shall be correlated to the insulation levels TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 23 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 considering each of the three types of voltage stresses (lightning impulse, switching surge and power frequency) under the condition at which each is likely to govern and given in the following table. Table 09-14: Air Gap Requirement for Shielded Lines Line Voltage, (kV) Air Gaps, (m) 69 0.69 110 1.30 115 1.30 132 1.50 230 2.1 380 2.60 Note: The clearances shall be increased @ 3 % for each 300m in excess of 1,000m altitude above mean sea level. 5.8.2 Unshielded Lines For unshielded lines the following criteria shall be used to specify clearances of phase conductor to structure. Further the minimum conductor to structure and conductor to conductor clearances shall not be less than Eq. 09-1 to Eq. 09-20 or by the correlated air gap clearances to insulation levels, the larger value shall be used, for various situations. Basic clearances shall be based on the maximum system voltage under emergency conditions. 6.0 a. For the “no wind” or normal position of the insulator, the conductor clearance to structure shall be the air gap equivalent of the insulator string impulse flashover value plus ten (10) percent. b. For the 430 N/m2 wind position, the conductor clearance to structure shall be the air gap equivalent of the insulator string impulse flashover value. c. For 1064 N/m2 wind position, the conductor clearance to structure shall be the air gap equivalent of 60Hz wet flashover value of the insulator string. The air gap clearance plus the distance allowed for the swing of insulator by the maximum wind of 1064 N/m2 will determine the clearance from conductor to structure in the normal position. RIGHT-OF-WAY WIDTH REQUIREMENTS 6.1 General 6.1.1 TESP12209R0/MAA Right-of-way requirements for 69 kV, 110kV, 115 kV, 132kV, 230 kV and 380 kV transmission lines are discussed in this part. All right-of-way shall be secured before design and construction. Date of Approval: December 12, 2007 PAGE NO. 24 OF 39 TRANSMISSION ENGINEERING STANDARD 6.1.2 6.2 TES-P-122.09, Rev. 0 Right-of-way for 69kV to 380kV transmission lines shall be as shown in Tables 09-16 and 09-17, or shall be calculated using the equations 09-21 to 09-23. The larger value from these equations shall be used. Conductor Clearance to edge of Right-of-Way 6.2.1 Minimum horizontal separation between phase conductors on the same support shall be calculated by equations 09-1 to .09-4. The large value from these equations shall be used. This value shall be increased by the distance to the end of the longest insulator support on each line structure. 6.2.2 Minimum horizontal clearances from conductors to edge of right-of-way shall be based on values in Tables 09-16 and 09-17 or in accordance with the following equations. The larger value shall be used. Transmission voltages shall be based on maximum operating voltage under emergency conditions: a. Basic Clearance = 2300 mm + 10 mm (U0-22) (Eq.09-21) Where: U0 = Maximum operating voltage phase-to-ground over 22 kV. b. Alternate clearance in mm ⎡ U (SSF) a ⎤ = 1500 + 1000⎢ 0 ⎥ ⎣ 500k ⎦ Where: 1.667 × bc (Eq.09-22) U0 = Maximum alternating current crest operating voltage to ground SSF = Maximum switching surge factor expressed in per unit peak voltage to ground. (SSF value shall be obtained from Transmission Asset Planning Department). a = 1.15, the allowance for three standard deviations. b = 1.03, the allowance for nonstandard atmospheric conditions c = Margin of safety, 1.2 for Vertical clearances and 1.0 for Horizontal clearances k = 1.15, the configuration factor for Conductor-to-Plane gap. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 25 OF 39 TRANSMISSION ENGINEERING STANDARD 6.3 TES-P-122.09, Rev. 0 Right-of-Way Width Requirements for Single Transmission Line 6.3.1 Figure TE-2209-0200-00 shows the procedures to be followed to establish the right-of-way for various types of transmission line structures in restricted areas. 6.3.2 Explanation of symbols used in Figure TE-2209-0200-00 and steps to be taken to establish right-of-way requirements in restricted areas are given below: A = Distance from centerline of structure to insulator attachment in mm. φ1 = Angle of maximum swing for suspension insulator string. preferred to use the φ1 as 45° swing. It is If 45° swing is used, it will include most conditions for structures currently being used with the insulator string at maximum blowout or structure design limitations. If the minimum right-of-way is required to be obtained for a special area control then the actual conditions or φ1 may be calculated for the worst conditions of the line under consideration. B = Offset due to insulator swing for suspension insulators equal to length of insulator string plus hardware length times Sin φ1 φ2 = Angle of maximum swing for conductors is determined by multiplying the conductor diameter in meters by the wind pressure in N/mm2 on conductor and dividing by the conductor unit weight in Newtons per meter. Tan φ 2 = Conductor Dia x Wind Pressure Unit Weight (Eq.09-23) C = Offset due to conductor sag x Sin φ2. Conductor sag shall be the final sag based on computed ruling span at every day temperature with 1064 N/mm2 wind D = Horizontal clearance from conductor to edge of right-of-way at maximum swing calculated for conditions established for structure to be used (see clause 6.2.2) E = Total distance each side, from centerline to edge of right-of-way. 6.4 Right-of-Way Width Requirements for Parallel Transmission Lines 6.4.1 TESP12209R0/MAA Figures TE-2209-0300-00 and TE-2209-0400-00 show the procedures to be followed in order to establish the minimum right-of-way for typical configurations of parallel transmission lines. Date of Approval: December 12, 2007 PAGE NO. 26 OF 39 TRANSMISSION ENGINEERING STANDARD 6.4.2 TES-P-122.09, Rev. 0 Steps A through E, as in clause 6.3.2, shall be followed and the angles φ1 and φ2 shall be determined for each of the two lines that are being paralleled. Then determine the dimensions required for Items F and G. The larger of these two shall determine the distance between the parallel transmission lines. a. Separation between lines as dictated by minimum clearance between conductors carried on different Supports The horizontal clearance between a phase conductor of one line to a phase conductor of another line shall meet the following conditions: (a) both phase conductors displaced by a 1064 N/mm2 wind at every day temperature, final sag; (b) if insulators are free to swing, one shall be assumed to be displaced by a 1064 N/mm2 wind while the other shall be assumed to be unaffected by the wind (see Figure TE2209-0300-00). F = Clearance between conductors of parallel transmission lines as determined by equation 09-3 and 09-4 for phases of different circuits. b. Separation between lines as dictated by minimum clearance of conductors from one line to the supporting structure of another The horizontal clearance of a phase conductor of one line to the supporting structure of another when the conductor and insulator are displaced by a 1064 N/mm2 wind at every day temperature final sag. G = Clearance of conductor from other supporting structures, as determined by the equation 09-15. 6.4.3 6.5 The separation between lines will depend upon the spans and sags of the lines as well as how the structures of one line line-up with structures of another. In order to avoid the unreasonable task of determining the separation of the structures span-by-span, a standard separation value shall be used based on a worst case analysis. Thus if structures of one line do not always line-up with the other, the separation required by clause 6.4.2.b above shall be based on assumption that the structure of one line is located next to the mid-span point of the line that has the most sag. Example Calculation of Right-of-Way 6.5.1 Information needed to determine the right-of-way requirements for structure types of any transmission lines are tabulated on Table 09-15. 6.5.2 Typical calculations for a single 230kV double circuit steel tower with 22 units of suspension insulator per string, 402.6 mm² (795 kcmil), 26/7 strands ACSR/AW “Drake” conductor and 335 meters ruling span are: a. TESP12209R0/MAA Dimension ‘A’ Date of Approval: December 12, 2007 PAGE NO. 27 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 A = 11.9 m derived from the drawing for “Latticed Steel Delta Configuration 230 kV Double Circuit Tangent Type Tower TTN (0°-1°)”. Dimension ‘A’ depends on tower structure design and configuration. b. Dimension ‘B’ Assume φ1 = 45° Length of insulator string = 22 x 0.146 m = 3.2 m Length of hardware string = 2 x 0.400 m = 0.8 m Total length of Insulator String = 4.0 m B = Total length of Insulator String x Sin φ1 = 4.0 m x sin 45° = 2.83 m c. Dimension ‘C’ Angle of maximum swing for conductors: ⎛ 28.1 mm / 1000 x 1064 ⎞ φ2 = Arc Tan ⎜ ⎟ = 63 ° 15.2 N/m ⎠ ⎝ Sag for 335 m ruling span = 10.64 m at 27°C, final with 1064 N/mm2 wind Offset due to conductor swing: C = 10.64 m x sin 63° = 9.50 m Offset due to conductor swing for two bundled conductor: Cl = 9.5 m + d. 0.5 x Cos 63o = 9.72 m 2 Dimension ‘D’ Horizontal clearance to edge of right-of-way ⎛ 253 ⎞ D = 2300mm + 10 mm ⎜ − 22⎟ ⎝ 3 ⎠ D = 2300 mm + 1241 mm = 3541 mm, say 3.60 m or by equation 09-22 for circuit with known switching surge factors: TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 28 OF 39 TRANSMISSION ENGINEERING STANDARD ⎡ U (SSF) a ⎤ D = 1500 mm + 1000⎢ L-G ⎥⎦ 500k ⎣ e. TES-P-122.09, Rev. 0 1.667 × bc Dimension ‘E’ Distance each side of centerline to edge of right-of-way E = A+ B+ C+ D = 11.9 + 2.83 + 9.72 + 3.60 = 28.05 m Therefore, total width of right-of-way required shall be: 2 x E = 2 x 28.05 m = 56.10 m; say ROW = 56 m 6.5.3 Typical calculation for two parallel 230kV steel tower lines (Figure TE2209-0300-00) Tower configurations are the same as in clause 6.5.2. The separation between two parallel 230 kV steel tower lines shall be calculated by the two equations shown below and greater value shall be considered: Items A, B, C, D, and E to be calculated as in clause 6.5.2. a. Horizontal Clearance between different phases of different circuits according to conductor sag per equation 09-3 & 09-4 U ⎤ ⎡U F = 7.6mm ⎢ 1 + 2 ⎥ + 8 2.12S 3⎦ ⎣ 3 Where: U1 = U2 = 230 kV x 1.1 = 253kV S = Sag at 27°C, final with 1064 N/mm2 wind F = 7.6mm [146 + 146] + 8 2.12(10640) = 2220 + 1202 = 3422 mm; say 3.4 m b. Horizontal Clearance of conductor of one line to the supporting structure of another (Eq.09-15) ⎛U ⎞ G = 1500mm + 10.2⎜ 1 − 50⎟ ⎝ 3 ⎠ = 1500 + 10 (146-50) TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 29 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 = 1500 + 960 = 2,460 mm, say. 2.50 m c. Horizontal Clearance may be reduced by the equation for circuits with known switching surge factors by the (Eq.-09-18). ⎡ U(SSF) a ⎤ Min. Clearance G = 1500 + 1000⎢ ⎥ ⎣ 500k ⎦ 1.667 × bc F = 3.40 m is larger than G, therefore, it is to be considered Total right-of-way width shall be: E + A + B + C + F + A + E = 28.05+11.9+2.83+9.72+3.4+11.9+ 28.05= 95.85 m Say total ROW = 96 m Table 09-15: Sample Data for Right-Of-Way Calculation Sr. No. Description Line No. 1 & 2 1 Maximum Line Voltage 2 Type of Structure 3 Drawing for Tower Type TTN 4 Centerline distance to end of longest insulator, m 5 Number of insulators in the string 22 6 Insulator length, m 4.0 7 Insulator assembly weight, kg 127 8 Conductor Drake, ACSR/AW 9 Stranding 26/7 10 Weight per unit, kg/m 1.551 11 Diameter, mm 28.14 12 Ruling span, m 335 13 Sag at 27° with 1064 N/m2 wind, m TESP12209R0/MAA Date of Approval: December 12, 2007 253kV Lattice Steel (Delta Configuration) 11.9 10.64 PAGE NO. 30 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Table 09-16: Single Transmission Lines Right-of-Way Width Requirements Line Voltage (kV) 380 230 110/115/132 Conductor Ruling Span (m) Maximum Span (m) Normal ROW Width (m) ACAR 400 550 85 AAAC/ACA R 400 550 70/75 ACSR 400 550 50* ACSR 305-350 400 56 ACSR 305-350 400 45 ACSR 200 250 35 305-350 400 35/50 200 250 30 ACSR 260-275 320 30 ACSR 80-100 110-120 15 ACSR 305-350 400 30 Wood H-Frame, S/C ACSR 260-275 320 25 Wood/Steel Monopole, S/C & D/C ACSR 80-120 140 15 Structure Lattice Steel, S/C (Horizontal) Lattice Steel, D/C (Vertical, V-String) Lattice Steel, D/C (Vertical, I-String) Lattice Steel, D/C (Delta) Lattice Steel, D/C (Vertical) Steel Monopole, D/C (Vetical) Lattice Steel, D/C (Vertical/Delta) Steel Monopole, D/C (Vetical) Wood H-Frame, S/C Wood/Steel Monopole, S/C & D/C Lattice Steel, D/C (Vertical) 69 AAAC/ACS R ACSR/AAA C Notes: i. ROW marked with * is applicable in the Inland Area where creepage distance is 31mm/kV. ii. The figures indicated in the above Table shall be applicable when ROW is unrestricted. In case of restricted ROW the exact value shall be established based on the actual span length and the actual conductor data. iii. Wherever right-of-way is restricted and not possible to accommodate structure pads and access road per TES-P-122.11, SEC shall review the case to determine appropriate right-of-way. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 31 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Table 09-17: Parallel Transmission Lines Right-of-Way Width Requirements Line Voltage (kV) 380 380 380 380 380 Structure Lattice Steel, S/C (Horizontal) Lattice Steel, S/C (Horizontal) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical, I-String) Lattice Steel, D/C (Vertical, I-String) Lattice Steel, S/C (Horizontal) Lattice Steel, D/C (Vertical) Lattice Steel, S/C (Horizontal) Conductor Ruling Span (m) Maximum Span (m) ACAR 400 550 ACAR 400 550 ACAR/AAAC 400 550 ACAR/AAAC 400 550 ACSR 400 550 139 119 100 ACSR 400 550 ACAR 400 550 ACAR 400 550 ACAR 400 550 125 Lattice Steel, D/C (Delta) ACSR 335-350 400 380 Lattice Steel, D/C (Vertical) ACAR 400 550 230 Lattice Steel, D/C (Delta) ACSR 335-350 400 ACAR 400 550 ACSR 335-350 400 ACAR 400 550 ACSR 335-350 400 ACAR 400 550 ACSR 200 250 ACSR 400 550 230 380 230 380 230 380 132 380 132 380 115/110 380 115 Lattice Steel, S/C (Horizontal) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Steel Monopole, D/C (Vertical) Lattice Steel, D/C (Vertical, I-String) Lattice Steel, D/C (Vertical, I-String) Lattice Steel, D/C (Vertical, I-String) Steel Monopole, D/C (Vertical) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Delta) * 129 230 380 Normal ROW Width (m) 115 115 104 95 * 83 ACSR 335-350 400 ACSR 400 550 * 75 ACSR 200 250 ACAR/AAAC 400 550 ACSR/AAAC 335-350 400 ACAR 400 550 ACSR 335-350 400 93 105 * Applicable in the Inland Area where creepage distance is 31mm/kV. TESP12209R0/MAA Date of Approval: December 12, 2007 PAGE NO. 32 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Table 09-17: Parallel Transmission Lines Right-of-Way Width Requirements (Continued) Line Voltage (kV) 380 69 Structure Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Conductor Ruling Span (m) Maximum Span (m) ACAR 400 550 88 ACSR 335-350 400 Lattice Steel, D/C (Delta) ACSR 335-350 400 Lattice Steel, D/C (Delta) ACSR 335-350 400 Lattice Steel, D/C (Delta) ACSR 335-350 400 ACSR 335-350 400 ACSR 335-350 400 ACSR 335-350 400 ACSR 200 250 ACSR 200 250 230 230 230 230 Normal ROW Width (m) 96 Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Steel Monopole, D/C (Vertical) Steel Monopole, D/C (Vertical) 85 74 60 230 Lattice Steel, D/C (Delta) ACSR 335-350 400 115 Lattice Steel, D/C (Delta) ACSR 335-350 400 ACSR 335-350 400 ACSR 335-350 400 ACSR 200 250 ACSR 200 250 ACSR 200 250 ACSR 80-120 140 ACSR 335-350 400 ACSR 80-120 140 ACSR 335-350 400 ACSR 80-120 140 ACSR 335-350 400 91 230 115 230 115 230 69 230 69 230 69 132 132 TESP12209R0/MAA Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Steel Monopole, D/C (Vertical) Steel Monopole, D/C (Vertical) Steel Monopole, D/C (Vertical) Steel/Wood Monopole, D/C (Vertical) Lattice Steel, D/C (Delta) Steel/Wood Monopole, D/C (Vertical) Lattice Steel, D/C (Vertical) Steel/Wood Monopole, D/C (Vertical) Lattice Steel, D/C (Vertical, I-String) Lattice Steel, D/C (Vertical, I-String) Steel Monopole, D/C (Vertical) Steel Monopole, D/C (Vertical) 73 55 45 64 55 * 65 ACSR 335-350 400 ACSR 200 250 * 45 ACSR Date of Approval: December 12, 2007 200 250 PAGE NO. 33 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Table 09-17: Parallel Transmission Lines Right-of-Way Width Requirements (Continued) Line Voltage (kV) 132 Structure Steel Monopole, D/C (Coastal Area) Steel Monopole, D/C (Coastal Area) Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Steel Monopole, D/C (Vertical) Steel Monopole, D/C (Vertical) Conductor Ruling Span (m) Maximum Span (m) ACSR/AAAC 200 250 55 ACSR/AAAC 200 250 ACSR/AAAC 335-350 400 ACSR/AAAC 335-350 400 ACSR/AAAC 200 250 ACSR/AAAC 200 250 Lattice Steel, D/C (Delta) ACSR 335-350 400 Lattice Steel, D/C (Delta) ACSR 335-350 400 ACSR 335-350 400 ACSR 335-350 400 ACSR 200 250 ACSR 200 250 H-Frame Wood, S/C ACSR 260-275 320 H-Frame Wood, S/C ACSR 260-275 320 H-Frame Wood, S/C ACSR 260-275 320 Wood Pole, S/C ACSR 80-100 110-120 Wood Pole, S/C ACSR 80-100 110-120 Wood Pole, S/C ACSR 80-100 110-120 115 H-Frame Wood, S/C ACSR 260-275 320 69 H-Frame Wood, S/C ACSR 260-275 320 115 H-Frame Wood, S/C ACSR 260-275 320 69 Wood Pole, S/C ACSR 80-100 110-120 115 Wood Pole, S/C ACSR 80-100 110-120 69 Wood Pole, S/C ACSR 80-100 110-120 H-Frame Wood, S/C ACSR 260-275 320 H-Frame Wood, S/C ACSR 260-275 320 110 110 65-70 55 115 115 115 Normal ROW Width (m) 86 Lattice Steel, D/C (Vertical) Lattice Steel, D/C (Vertical) Steel Monopole, D/C (Vertical) Steel Monopole, D/C (Vertical) 65 55 115 60 115 38 115 23 45 37 21 69 TESP12209R0/MAA 42 Date of Approval: December 12, 2007 PAGE NO. 34 OF 39 TRANSMISSION ENGINEERING STANDARD TES-P-122.09, Rev. 0 Table 09-17: Parallel Transmission Lines Right-of-Way Width Requirements (Continued) Line Voltage (kV) Structure Conductor Ruling Span (m) H-Frame Wood, S/C ACSR 260-275 Maximum Span (m) 320 69 Normal ROW Width (m) 23 Wood Pole, S/C ACSR 80-100 110-120 Wood Pole, S/C ACSR 80-100 110-120 Wood Pole, S/C ACSR 80-100 110-120 69 20 Note: Wherever right-of-way is restricted and not possible to accommodate structure pads and access road per TES-P-122.11, SEC shall review the case to determine appropriate right-of-way. 7.0 BIBLIOGRAPHY 7.1 Design Manual for High Voltage Transmission Lines, REA Bulletin 1724E200, U.S. Department of Agriculture, 2005 Edition 7.2 Transmission Line Design Manual, U.S. Department of the Interior, Holland H. Farr 7.3 National Electrical Safety Code, American National Standard Institute, 2007 Edition 7.4 IEC 61936-1, Power Installations Exceeding 1 kV A.C.-Part 1: Common Rules 7.5 Electrical Transmission and Distribution Refence Book, Central Station Engineers (Westinghouse Electric Corporation), 1964 7.6 Estimating Lightning Performance of Transmission Lines, IEEE Transactions Volume 83, 1964, J.M. Clayton & F.S. Young 7.7 Shielding of Transmission Lines, IEEE Paper No. 63-640, J.M. Clayton, F.S. Young and A.R. Hileman 7.8 Application of Insulators in a Contaminated Environment, IEEE Transaction 7.9 Elements of Power System Analysis, William D. Stevens, Jr. TESP12209R0/MAA Date of Approval: December 12, 2007 by PAGE NO. 35 OF 39 TRANSMISSION ENGINEERING STANDARD TESP12209R0/MAA Date of Approval: December 12, 2007 TES-P-122.09, Rev. 0 PAGE NO. 36 OF 39 TRANSMISSION ENGINEERING STANDARD TESP12209R0/MAA Date of Approval: December 12, 2007 TES-P-122.09, Rev. 0 PAGE NO. 37 OF 39 TRANSMISSION ENGINEERING STANDARD TESP12209R0/MAA Date of Approval: December 12, 2007 TES-P-122.09, Rev. 0 PAGE NO. 38 OF 39 TRANSMISSION ENGINEERING STANDARD TESP12209R0/MAA Date of Approval: December 12, 2007 TES-P-122.09, Rev. 0 PAGE NO. 39 OF 39