Heat Convection Alireza Mashayekh Fall 2023 Integral Solution β Integral solution can be used to determine the actual y variation of features such as local heat flux (π″), thermal boundary layer thickness (πΏπ ), and wall jet velocity profiles β So far, we only know the order of magnitude of relevant flow and heat transfer parameters ↓ Integral Solution β Integrating the momentum equation (4.17) and the energy equation (4.8) from the wall (π₯ = 0) to a far enough plane π₯ = π in the motionless isothermal cold reservoir, we obtain the integral boundary layer equations for momentum and energy Integral Solution β The length scales of Table 4.1 are very useful in selecting the proper shapes of π£ and π profiles to be substituted into the integral equations β We must carry out the integral β analysis in two parts, for Pr > 1 and Pr < 1, as the boundary layer constitution changes dramatically across Pr ∼ 1 The other lesson learned from scale analysis is that the velocity profile shape is governed by two length scales: one for the wall shear layer, and another for the overall thickness of the moving layer of fluid Integral Solution High-Pr Fluids β A suitable set of profiles for Pr > 1 fluids compatible with Fig. 4.4a is: β Substituting these profiles in the integral equations, and setting π → ∞ yields: β where π, πΏπ , and πΏ are unknown functions of altitude (π¦), and Δπ = π0 − π∞ = ππππ π‘πππ‘ β where π is the Pr function: Integral Solution High-Pr Fluids β So, at this point, we have two (2) equations, and three (3) unknowns: π£ π¦ , πΏ π¦ , π(Pr) β The third equation, necessary for determining π, πΏ, and π uniquely, is a challenging proposition β Historically, to avoid this problem, some assumed that πΏ = πΏπ or π = 1 β However, since a great deal of the information relating to boundary layer geometry is buried in the πΏ/πΏπ function, it is instructive to do an integral analysis with πΏ ≠ πΏπ β It is up to the researcher to come up with a third equation Integral Solution High-Pr Fluids β First, we must keep in mind that integral form equations are approximate substitutes for the real equations to be satisfied β So we have the freedom to bring into the analysis any other condition (equation) that accounts approximately for conservation of momentum or conservation of energy β Since the energy equation is, in a scaling sense, less ambiguous than the momentum equation*, it makes sense to select as a third equation a force balance: One that is both clear and analytically brief is the statement that in the no-slip layer 0 < π₯ < 0+ , the inertia terms of momentum equation are zero: * Because in natural boundary layer flow, the energy equation spells πππππ’ππ‘πππ ∼ ππππ£πππ‘πππ, whereas the momentum equation spells either πππππ‘πππ ∼ ππ’ππ¦ππππ¦ or πππππ‘ππ ∼ ππ’ππ¦ππππ¦ Integral Solution High-Pr Fluids β This is to say that right next to the wall, there is no ambiguity associated with whether inertia is negligible compared with both friction and buoyancy, regardless of the Prandtl number β So, considering πΏ~π¦ 1/4 and π~π¦ 1/2 , the following three equations should be solved for π, πΏ, π Integral Solution High-Pr Fluids β The main results are the function π Pr : β In the limit Pr → ∞, the results reduce to: β And the local Nusselt number: β Which confirm the scaling laws listed in Table 4.1 Integral Solution Low-Pr Fluids β for a Pr < 1 fluid, we combine the previously assumed temperature profile with a new velocity profile: β noticing that πΏπ ∼ π¦ 1/4 , πΏπ£ ∼ π¦ 1/4 , and π1 ∼ π¦ 1/2 yields: β In the limit Pr → 0: β where π1 , πΏπ , and πΏπ£ are unknown functions of π¦ Integral Solution Low-Pr Fluids β Once again, this limiting behavior confirms within a numerical factor of order 1 the scaling laws discovered in the preceding section Integral Solution Low-Pr Fluids β The integral heat transfer results are summarized in Fig. 4.6 next to the similarity solution that will be outlined in the next section β The Nu expressions (4.49) and (4.53) match at Pr = 5/12, where the assumed velocity profiles are identical (π = 1, π1 = 1). Integral Solution Low-Pr Fluids β It should be noted that the β Nusselt number calculations depend to some extent on the choice of analytical expressions for velocity and temperature profiles This choice is always a tradeoff between what constitutes a reasonable profile shape and the function that leads to the fewest analytical complications β β β In our calculations, the choice of exponentials in the makeup of temperature and velocity profiles led to a relatively simple analysis Figure 4.6 also shows the Nusselt number predicted by Squire’s integral analysis, which assumes polynomial temperature and velocity profiles with πΏπ = πΏ Although the πΏπ = πΏ assumption is justified only for fluids with Pr~1, the Squire analysis predicts the correct Nusselt number in a wide Pr range Similarity Solution β We can think of temperature and wall jet profiles whose shape remains unchanged as both profiles occupy wider areas as π¦ increases β From Table 4.1 and the integral solution, we know that any length scale of the boundary layer region is proportional to π¦ 1/4 β The dimensionless similarity variable π(π₯, π¦) can then be constructed as π₯ divided by any of the length scales summarized in Table 4.1 β selecting the Pr > 1 thermal boundary layer thickness −1/4 π¦Raπ¦ as the most appropriate length scale, the similarity variable emerges as: Similarity Solution β Introducing the streamfunction π’ = ππ/ππ¦, π£ = −ππ/ππ₯ in place of the continuity equation, the boundary layer equations become: β From the first column of Table 4.1 we note that, in general, the dimensionless temperature profile will be a function of both π(π₯, π¦) and Pr ; let this unknown function be π(π, Pr), defined as: Similarity Solution β For the vertical velocity profile π£, from the fourth column of Table 4.1 where Pr > 1, we select the expression: β From the definition π£ = −ππ/ππ₯, we conclude that the streamfunction expression must be: 1/2 β where πΌ/π¦ Raπ¦ represents the scale of π£, and πΊ(π, Pr) is the dimensionless similarity profile of the wall jet β where πΊ = −ππΉ/ππ Similarity Solution Energy equations β Substituting Momentum equation β β β In the boundary layer equations for energy and momentum, we get this system of dimensionless equations: β where (·)′ is shorthand notation for π · /ππ These equations show once again the meaning of the Pr > 1 scaling adopted in the definition of π and πΊ (both of order 1) The energy equation is a balance between convection and conduction, while the momentum equation reduces to a balance between friction and buoyancy as Pr → ∞, that is, as the inertia effect vanishes Similarity Solution β These equations must be solved subject to the similarity formulation of the appropriate boundary conditions: Similarity Solution β Figures 4.7a and b present the solution as temperature profiles and velocity profiles in the thermal boundary layer region π = π(1) β in the limit Pr → ∞, the temperature profiles collapse onto a single curve Similarity Solution β Also, in the same limit, the β π ∼ 1 portions of the velocity profiles approach a single curve, while the dimensionless velocity peak is consistently a number of order 1 (the velocity peak falls in the region occupied by the thermal boundary layer) As Pr increases, the velocity profile extends farther and farther into isothermal fluid. All these observations support the scale analysis whose results have been summarized in Table 4.1 Similarity Solution β The local heat transfer coefficient predicted by the similarity solution is: β The numerical coefficient − π ′ π=0 is, in general, a function of the Prandtl number, as shown in Table 4.2 and Fig. 4.6 Similarity Solution β In the two Pr limits of interest, the Nusselt number approaches the following asymptotes: β Since β ∼ π¦ −1/4 the average heat transfer coefficient for a wall of height π» is β0−π» = (4/3)β(π¦ = π») β The average Nusselt number Nu0−π» = β0−π» π»/π is equal to (4/3)Nu(π¦ = π») β Therefore, the wallaveraged heat transfer results corresponding to the two Pr limits are: Similarity Solution β These conclusions are β anticipated within 30 percent by the scaling laws of Table 4.1: Such good agreement is common when the scale analysis is correct Figure 4.6 shows that despite the factor of 10 increase in the Prandtl number from air (Pr = 0.72) to water (Pr ≅ 5– 7), the Nusselt number varies by only 15 percent if the Rayleigh number is held constant UNIFORM WALL HEAT FLUX β The analyses presented so far are based on the assumption that the vertical wall is isothermal β This would be a good approximation in cases where the vertical wall is massive and highly conducting in the vertical π¦ direction β From a practical standpoint, β β however, an equally important wall model is the uniform heat flux condition π″ = ππππ π‘πππ‘ In many applications, the wall heating effect is the result of radiation heating from the other side or, as in the case of electronic components, the result of resistive heating We only outline the scale analysis for this case UNIFORM WALL HEAT FLUX β Regardless of how π″, π, and πΏπ vary with altitude π¦, the definition of wall heat flux requires that: UNIFORM WALL HEAT FLUX β Figure 4.8a illustrates this scaling law in the case of an isothermal wall, where both Δπ and the product π ″ πΏπ are independent of π¦ β Figure 4.8b shows what to expect in the case of constant π″, namely, identical Δπ and πΏπ as functions of π¦ UNIFORM WALL HEAT FLUX β To determine these π¦ functions, we make the observation that the scaling analysis starting with eq. (4.19) is general; in other words, in that analysis, πΏπ and π represent the correct order of magnitudes of thermal layer thickness and wall–ambient temperature difference along a wall of height π» β For Pr β« 1 fluids, eq. (4.26) recommends: β Recognizing that in the present problem Δπ is not given (π″ is), we use π ″ ~πΔπ/πΏπ to eliminate Δπ and solve for πΏπ UNIFORM WALL HEAT FLUX β Where Ra∗ is a Rayleigh number based on heat flux π″: β The corresponding (Pr β« 1) scale of the wall–ambient temperature difference is: β Note that both πΏπ and π are proportional to π»1/5 β Because the π»-averaged quantities are proportional to π»1/5 , the local values of πΏπ and π are proportional to π¦ 1/5 β The local Nusselt number for a constant heat flux wall is defined as: UNIFORM WALL HEAT FLUX β Therefore, in the range Pr ≥ 1, the Nusselt number must scale as: β For low-Pr number fluids, following the same steps: UNIFORM WALL HEAT FLUX β The validity of these scaling results can be tested by referring to more exact analyses published on the same topic β Sparrow carried out an integral analysis of the same type as Squire’s (i.e., assuming only one length scale πΏπ for the velocity profile) and arrived at the local Nusselt number: β β The similarity solution was reported by Sparrow and Gregg, who found that above equation is, in fact, an adequate curve fit for the similarity Nu results in the range 0.01 < Pr < 100 Thus, in the two Pr limits, the above equation yields the following local Nusselt numbers: UNIFORM WALL HEAT FLUX β Similarity solutions can be developed for an infinity of wall temperature conditions, provided that they obey either: β β β the power law: π0 − π∞ = π΄π¦ π the exponential law: π0 − π∞ = π΄π ππ¦ the line π0 − π∞ = π΄ + π΅π¦ β where π΄, π΅, and π are all constants β Thus, the π0 = ππππ π‘πππ‘ and π″ = ππππ π‘πππ‘ problems discussed so far are only two special cases of the vast analytically accessible class of problems β From an engineering standpoint, however, the π0 = ππππ π‘πππ‘ and π″ = ππππ π‘πππ‘ results are by far the most useful Conjugate Boundary Layers β There are many engineering situations in which the vertical wall that heats a buoyant boundary layer is itself heated on the back side by a sinking boundary layer β Such is the case in walls, partitions, and baffles encountered regularly in the thermal design of living quarters and insulation systems Conjugate Boundary Layers β Boundary layers form on both sides of the wall; however, the wall temperature or heat flux are not known a priori as in the simpler models considered earlier β The condition of the wall is the result of the heat transfer interaction between the two boundary layers β It is said that depending on the layer-to-layer interaction, the wall temperature “floats” to an equilibrium distribution between the two extreme temperatures maintained by the two reservoirs Conjugate Boundary Layers β β β β Wall π″ distribution is approximated satisfactorily by the π″ = ππππ π‘πππ‘ model discussed Figure 4.10 shows the Nusselt number predicted analytically in the Pr → ∞ limit based on the Oseenlinearization method This approach consists of writing integral conservation equations for both sides of the wall, with the additional complication that the wall temperature π0 (π¦) is unknown The additional equation necessary for determining π0 is the condition of heat flux continuity in the π₯ direction, from one face of the wall to the other Conjugate Boundary Layers β β β β Both the overall Nusselt number and the Rayleigh number are based on the overall temperature difference imposed by the two fluid reservoirs The heat transfer rate (hence, 1/4 the ratio Nu0–π» /Raπ» ) decreases as the wall thickness resistance parameter ω increases The dimensionless wall number proposed is: where π‘, π», π, and ππ€ are the wall thickness, wall height, fluid conductivity, and wall conductivity, respectively Vertical Channel Flow β Consider now the interaction between the boundary layers formed along two parallel walls facing each other β If the boundary layer thickness scales are much smaller than the wall-towall spacing π·, the flow along one wall may be regarded (approximately) as a wall jet unaffected by the presence of another wall Vertical Channel Flow β On the other hand, if the β boundary layer grows to the point that its thickness becomes comparable to π·, the two wall jets merge into a single buoyant stream rising through the chimney formed by the two walls It is clear from Fig. 4.12 that the channel flow departs from the wall jet description in the same way that the duct flows of Chapter 3 depart from the pure boundary layer flows of Chapter 2 Vertical Channel Flow β Here we focus on the simplest analysis of the channel flow, with the final objective of predicting the capability of this flow to cool or heat the walls of the channel β The flow part of the problem may be solved by considering the momentum equation in the π¦ direction: β The mass continuity equation, in conjunction with the assumption that the channel is long enough so that the u scale becomes sufficiently small, leads to the concept of fully developed flow, for which we have: Vertical Channel Flow β The momentum equation in the lateral direction π₯ can be used to show that the pressure in the fully developed region is a function of π¦ only, and, because both ends of the channel are open to the ambient of density π∞ : β Combining these equations and again using the Boussinesq approximation yields the much simpler momentum equation: β To solve this equation, it is necessary to derive the temperature profile π − π∞ Vertical Channel Flow β The two profiles, velocity and temperature, are coupled β Hence, momentum and the energy equation must be solved simultaneously β A much simpler solution approach is possible if we observe that in the fully developed region between two isothermal walls, the temperature difference can be approximated by π0 − π∞ ; in other words: β Based on this approximation, the right-hand side of the momentum equation becomes a constant Vertical Channel Flow β With this assumption, the velocity profile will be: β Mass flow rate per unit length normal to the plane: β Total heat transfer rate between stream and channel walls: β Average heat flux Vertical Channel Flow β Overall Nusselt number: β Note that the dimensionless group emerging from this analysis is the Rayleigh number based on wall-towall spacing β and that the Grashof number is once again absent from the discussion β This conclusion answers again the question of whether the Grashof number is a relevant dimensionless group in natural convection: It is not! Vertical Channel Flow β The fully developed flow and heat transfer solution is valid for all Prandtl numbers β The Rayleigh number range of its validity follows from the requirement that the thermal entrance length ππ be much smaller than the channel height π» β The order of magnitude of ππ follows from the observation that the thermal boundary layer thickness πΏπ becomes of order π·/2 when π¦ is of order ππ Vertical Channel Flow β Evaluating ππ from above: β In conclusion, the fully developed flow and temperature profile assumptions break down if the Rayleigh number exceeds an order of magnitude dictated by the geometric aspect ratio of the channel, π»/π· Combined Natural and Forced Convection (Mixed Convection) β So far, we assumed that the fluid in the reservoir is motionless β However, in practice, in any room there is an airconditioner that replenishes the air continuously or intermittently β Which means that air is in motion: β The reservoir is forced into and out of the room by an external agent β Depending on the strength of this forced circulation, the heat transfer from the wall to the room air may be ruled by either natural convection or forced convection or a combination of natural and forced convection Combined Natural and Forced Convection (Mixed Convection) β Due to the diversity of the natural– forced convection interaction, it is impossible to treat this subject fully β However, it is instructive to study one simple configuration and to experience the power and cost-effectiveness of pure scaling arguments Combined Natural and Forced Convection (Mixed Convection) β As is shown in Fig. 4.13, let us consider the heat transfer from a vertical heated wall (π0 ) to an isothermal fluid reservoir moving upward (π∞ , π∞ ), that is, in the same direction as the natural wall jet present when π∞ = 0 Combined Natural and Forced Convection (Mixed Convection) β Under what conditions is the combined natural– forced phenomenon characterized (approximately) by the scales of pure natural convection, and conversely, under what conditions is it characterized by the scales of pure forced convection? β If the mechanism is natural convection, the thermal distance between the heat-exchanging entities is of order: β On the other hand, if the mechanism is forced convection, the wall and the reservoir are separated by a thermal length of order: Combined Natural and Forced Convection (Mixed Convection) β The type of convection mechanism is decided by the smaller of the two distances, πΏπ ππΆ or πΏπ πΉπΆ , because the wall will leak heat to the nearest heat sink β Thus, the scale criterion for transition from natural to forced convection is: β In other words, for Pr > 1 fluids: Combined Natural and Forced Convection (Mixed Convection) β To verify the validity of this criterion, we examine the local similarity solution to the combined heat transfer problem β This solution shows that forced convection dominates at small values of the group Grπ¦ /Re2π¦ , while natural convection takes over at large values of the same parameter Combined Natural and Forced Convection (Mixed Convection) β Note, however, that the knee in each Nusselt number curve shifts to the right as Pr increases β This effect is due to the fact that the abscissa parameter used, Grπ¦ /Re2π¦ , is not the same as the dimensionless group that serves as transition parameter: Combined Natural and Forced Convection (Mixed Convection) β Figure 4.14 shows the replotting of the similarity solution using the transition parameter on the abscissa and the forced convection Nusselt number scaling on the ordinate β The sign of correct scaling is that the Pr > 1 curves fall on top of each other, and the knee of all the curves is at π(1) on the abscissa Combined Natural and Forced Convection (Mixed Convection) β In conclusion, mixed convection can be understood and predicted by intersecting its asymptotes, natural convection and forced convection β Repeating the geometric arguments as before, this time for Pr < 1 fluids, we find the following transition criterion: