equipment. Thus, the tests methods used for insulation maintenance and assessment are of primary importance to the reliable operation of power system. ELEC 4611 Power System Equipment HIGH VOLTAGE TEST TECHNIQUES AND INSULATION ASSESSMENT After the insulation is designed to be able to withstand the normal and abnormal operational conditions to which it will be subjected, the next consideration must be the long-term behaviour of the insulation under the expected long-term operational and environmental conditions. The insulation condition is the primary factor that determines the lifetime and the operating efficacy of major HV equipment plant. During its life in operating equipment, insulation deterioration will occur even under normal conditions. However, the deterioration can be accelerated greatly by a number of factors: these include (i) excessive operating temperature, (ii) excessive electric field strength, (iii) the presence of moisture or other contamination, (iv) abnormal mechanical stress or vibration, (v) environmental factors such as UV radiation. Because of this multiplicity of potential degrading factors (multi-factor ageing), insulation condition monitoring is the most important feature of asset management in relation to the large and expensive items of high voltage power systems. The asset management system involves maintenance and test procedures with the aim being to achieve the most efficient and trouble-free use of such ELEC4611: H.V. Test Techniques and Insulation Assessment p.1 The most generally used tests for insulation condition assessment in high voltage electrical power equipment are (not necessarily in order of importance): Dielectric Dissipation Factor (DDF) measurement. Dissolved gas-in-oil analysis (DGA) • For oil impregnated insulation • For paper degradation analysis • For oil circuit breakers. Insulation Resistance (IR) measurement (and derivative tests). Overvoltage Tests on equipment • Power Frequency / HVDC • Impulse (lightning and switching) Tests. Partial Discharge (PD) Tests Dielectric spectroscopy • Recovery voltage measurement (RVM) • Polarisation Depolarisation Current (PDC) Diagnostics specific to the insulation type (e.g., degree of polymerisation) ELEC4611: H.V. Test Techniques and Insulation Assessment p.2 Of the above diagnostics, the DDF, DGA and the IR measurement can be done easily on-site and usually off-line (although the actual DGA tests on oil samples taken from the equipment normally have to be performed later in a laboratory). The DDF measurement usually requires a separate high voltage test source operating either at power frequency or at some very low frequency level to reduce reactive power requirements, but some DDF tests today can be performed on-line using sophisticated test techniques to determine and record phase angle difference between the operating voltage and current for the item of equipment under test. The DGA tests are perhaps the simplest to perform in that only a small sample of oil is required for chemical analysis and this sample removal can be done while equipment is on-line. The IR and derivative tests use a DC voltage application and must be done off-line. Partial discharge (PD) tests have traditionally been done off-line or in the laboratory and generally required a separate HV source and connection to the high voltage line via a blocking capacitor. However, modern techniques with high frequency current transformers that can be used on earth connections now allow on-line monitoring of PDs, but in such cases electromagnetic interference from corona discharge and general RF background is a major problem that must be contended with. Overvoltage tests must be performed as separate source tests. Normally only power frequency OV tests can be done on-site: impulse and switching tests are normally done only in the laboratory or in the factory. It should be noted that HVDC tests of some HVAC equipment items has been relatively common ELEC4611: H.V. Test Techniques and Insulation Assessment p.3 practice for items such as cables where the reactive power requirements are large at rated voltage. However, while this has been acceptable for paper insulated equipment, the use of modern polymeric insulation with its higher propensity to store electrical charge for long periods means that HVDC is no longer able to be used in this way. 1. DDF (tan or Loss Angle) Testing No insulation material is perfect: it will exhibit some finite insulation resistance and its polarizability will cause it to generate thermal loss at AC excitation. Thus, no capacitance which is formed from any insulation dielectric material can be totally loss-free. There will always be some power loss in the dielectric due to a variety of causes, including the ohmic loss due to leakage current (which is usually very small), dielectric heating and partial discharge activity in the insulation voids and material imperfections. Dielectric heating, the electrical analogue of magnetic hysteresis loss, results from friction in the material as electric dipoles, molecular dipoles and atomic charges try to follow the changing electric field applied to the insulation. Such loss is much more dominant than ohmic loss in good insulation at high voltage. It should be noted that the presence of moisture will considerably increase dielectric loss because of the high loss factor of the water molecule. Both the leakage resistance and the dielectric loss factor are also very temperature dependent. ELEC4611: H.V. Test Techniques and Insulation Assessment p.4 The losses due to PD activity are very variable and are very voltage dependent: in good insulation they are quite low or non-existent, but they can be significant in degraded insulation. Measurement of DDF vs voltage will exhibit a “tip-up” at high voltage, which can be used as an indicator of PD activity. As a result of all such losses, the insulation in high voltage equipment cannot be modelled as a pure capacitance: instead, it is modelled by the equivalent circuit shown below with the power loss represented by a resistance R in parallel with an ideal lossless capacitor C. The resistance R is not a value measurable with an ohm-meter, but is a notional value which represents the dielectric loss magnitude and hence the quality of the insulation. It is the electrical analogy of the core loss resistance in a transformer equivalent circuit. For the parallel circuit arrangement shown above, the phasor diagram is: The power factor is cos( 90 – ) and is thus representative of the power loss and thus the insulation quality. However, a better representation of the loss and hence the quality is the angle between the total current I and the purely capacitive current Ic. Typically, the angle is of the order of milli-radians for good insulation and tens to hundreds of m.rads for poor and very poor insulation. We can write the various relations as follows: Power factor = cos( 90 – ) tan() = DDF for small While a low DDF value is necessary for high voltage insulation, it is not a major requirement at low (less than 600 V) voltage: PVC has a poor DDF value (about 0.1) but [At high frequencies, a series RC equivalent is a better simulation.] ELEC4611: H.V. Test Techniques and Insulation Assessment p.5 ELEC4611: H.V. Test Techniques and Insulation Assessment p.6 is widely used at 230/400V; but it is not used for HV insulation applications. tan is thus designated the dielectric dissipation factor (DDF) of the insulation. Its value is a very useful indicator of insulation efficacy, particularly when measured as a function of voltage from below rated voltage to above rated voltage (say 0.6–1.5 p.u.). Note that: and Ic = and thus: tan IR IR IC I V Xc = CV 1.1 DDF Measurement IR = CVtan and we have Power loss = America, the method used is to measure the DDF at some standard voltage (say 10 kV) irrespective of rated voltage and then use this value for determining trending of DDF over time. The advantage of this method is that it limits the size of test transformer required. However, the voltage variation of DDF particularly near rated voltage counts against this method and it is usual in most other countries to measure DDF at rated voltage. DDF is also very temperature dependent, and this must be taken into account when looking at trends over time. Increases of 5 or 6 times over temperature variations of 50–60 oC are possible. VIR = CV tan 2 The DDF (tan) (and the capacitance value C) are normally measured by a high voltage AC (4-terminal) bridge technique. The measurement should be done with the insulation at rated voltage to determine its efficiency at rated operational voltage, because DDF is voltagedependent. Also, because the variation of DDF with voltage is an important consideration, the test should be done over a range of voltage above and below the normal operating voltage. Usually insulation will exhibit a “turn-up” in the DDF vs. V curve just above operating voltage. If the insulation is degraded the “turn-up” may occur at a lower voltage level and this will be an indication of potential insulation problems. In some cases, particularly in North ELEC4611: H.V. Test Techniques and Insulation Assessment p.7 The most commonly used bridge arrangements for DDF measurements are the Schering Bridge and the These tests are Transformer Ratio Arm Bridge. performed with the test object held at about full rated voltage (or higher), but the variable balance impedance components (which may have to be manually adjusted for balance) are effectively at earth potential. [Modern bridges are automatically balancing and do not require manual manipulation of the dials]. Both of the above types are 4terminal bridges and thus require balance of both amplitude and phase. The Schering Bridge is described and analysed in detail here. The typical circuit used with Schering bridge DDF measurement at power frequency is: ELEC4611: H.V. Test Techniques and Insulation Assessment p.8 Earth At balance: Z1 Z2 C1 R1 Z3 Rx H.V. Z 2 R2 Test object 1 jC Z3 Z4 Note that: Z 4 Rx (i) C1 and R1 are the variable impedances (they are high precision components: R2 may sometimes also be variable). (ii) R2 is a standard non-inductive resistor, also of high precision. (iii) C is a standard high voltage precision gas capacitor with negligible losses (typically 100 pF: the gas dielectric makes it effectively lossless). (iv) Rx – Cx is the test object (represented by a series equivalent combination). The bridge is energised at the rated voltage of the equipment item, but there are only a few hundred volts at most on R1, C1 and R2, which are operated to achieve balance. ELEC4611: H.V. Test Techniques and Insulation Assessment Z2 Z4 Z1 Z 3 1 1 jC1 Z1 R1 Cx C or From the circuit diagram, we can write the following ( is the angular frequency): R2 V Z 2 Z1 Z 4 Z3 p.9 1 jC x and thus, for balance of the bridge, we have the following relationship: or: 1 1 Rx jC R2 jC1 R1 jCx R C jC1 R2 2 j Rx C R1 Cx Equating real and imaginary parts, we get: (a) R2 C R1 C x (b) R2C1 RxC R1 C R2 C i.e. Rx 1 R2 C i.e. Cx ELEC4611: H.V. Test Techniques and Insulation Assessment p.10 tan is the required result of the DDF test measurement, and is determined as follows (see the phasor diagram): tan Rx R C RC Rx Cx 2 1 1 Xx C R2 i.e. tan R1C1 where is the power frequency value, 100. Typical values of tan are milli-radians or less at 50 Hz for good insulation. Note that tan at these small values hence the units are usually milli-radians. In older documents the loss quantity used is often the power factor which is cos( 90 – ) and is, strictly speaking, different to tan. However, at the values of typical of good insulation, the two are essentially identical. Only for very high loss angles will they differ. When power factor is quoted, the units are either a number or a percentage. 0.01 0.1 0.2 0.5 tan 0.01000 0.10033 0.20271 0.5463 cos 90 0.009999 0.09983 0.19867 0.4794 % 0.01 0.5 2.0 14.0 1.2 Relevance of DDF (a) They can give a measure of impurities (particularly moisture) in the insulation. (b) DDF provides some information about partial discharge activity in insulation. (c) CV2tan gives the dielectric heat loss and this will determine, to a considerable degree, the operating temperature of insulation at high voltage. (d) Plots of tan vs. voltage below and above rated voltage will give useful information on the insulation condition. As the Schering Bridge uses a series equivalent circuit for Rx – Cx, the value of Cx may vary from that for a parallel circuit, but this only occurs for high levels of dissipation factors (DDF). One of the disadvantages of using DDF testing (or any testing that requires application of rated voltage) comes when the test object has a high capacitance, such as an HV cable. Then the off-line source has to have large reactive power capacity to energise the item to rated voltage. Two methods are used to get around this problem: (a) Use of very low frequency (about 0.1 Hz) AC excitation (b) Use of an external inductance to give resonant operation with the cable capacitance at or near power frequency. tan or DDF (and the capacitance) value C are important characteristics of high voltage insulation because of the following features: Because the reactive power requirement of a capacitance C is CV2, a simple method of reduction of the required transformer rating is to decrease the frequency. Thus if 0.1 Hz is used instead of 50 Hz the reactive power requirement is decreased by a factor of 500 and only a very small ELEC4611: H.V. Test Techniques and Insulation Assessment ELEC4611: H.V. Test Techniques and Insulation Assessment p.11 p.12 transformer is needed for the test. This, of course, relies on the 0.1 Hz setting up an AC electric field distribution in the insulation rather than a DC field and while there has been some reservation about this, it is generally accepted that such low frequencies do give an AC distribution and the tests is thus valid. The other method uses a tuneable inductor to give a circuit resonant frequency somewhere around the 40-60 Hz range. When the inductor is tuned to resonance the inductor and capacitor voltages are able to be held at rated values but cancel each other and the supply transformer is then required only to supply the power loss in the inductor winding resistance, and this is able to be made very low and the transformer very small. High temperature superconducting windings have been suggested. The following figure shows the circuit diagram of a seriesresonant system. Note that the internal leakage inductance of the transformer (not shown) also contributes to the resonance process. Thus, resonance operation is determined by the combination of the total inductance Le (tuning inductor and transformer inductance) and the load capacitance C. At resonance, 1 LeC and the load voltage V2 which appears on the capacitance load is given by: V2 j C V 1 Re j Le 1 C ELEC4611: H.V. Test Techniques and Insulation Assessment V1 ReC p.13 The phasor diagram of the system is also shown and, at resonance, it is possible that V2 V1 . The quality factor Q 1 CR Le R gives the voltage multiplication factor. Thus, depending on the values of Le and C, the load voltage can be made many times the applied voltage magnitude V1. There will be some small series resistance Re that will cause the only power loss needed to be supplied by the source. 2. Dissolved Gas Analysis (DGA) The majority of large power transformers, many older cables and many switchgear components are insulated by oil and by oil-impregnated paper. Whenever any faults occur that may cause deterioration of the oil-based insulation, the generation of gases by discharges in the oil is almost always a concurrent event. These gases are then dissolved in the oil and an analysis of the gas constituents and their quantities (and particularly their relative ELEC4611: H.V. Test Techniques and Insulation Assessment p.14 quantities) can provide very useful information about the fault. In many cases it is possible to identify the type of fault from the relative quantities (ratios) of the gas components. The gases which are generated in such oil-based insulation include: Carbon monoxide CO Carbon dioxide CO2 Hydrogen H2 Methane CH4 Ethane C 2H 6 Ethylene C2H4 Acetylene C2H 2 The above is not the full list of gases produced as many higher hydrocarbons are also generated. However the above are the ones that are best able to be used to determine any deterioration effects of the oil and to identify any particular fault types that may be causing gas generation. Also, O2 and N2 are also often monitored to give an indication of possible oxidation. The analysis is done by standard gas chromatograph (GC) methods on samples taken from the oil in the equipment item. Most utilities have GC equipment routinely available. In general, CO and CO2 are generated by hot spots such as may arise from hot metal surfaces such as the core or a magnetic shield or a winding hot spot in the transformer. Hydrogen, methane and, to a lesser extent, ethane may also be generated by such effects. Ethylene and acetylene are ELEC4611: H.V. Test Techniques and Insulation Assessment p.15 not generated by hot spots. Partial discharges will generate hydrogen, methane, ethane and ethylene. High power arcing will generate hydrogen, ethylene and acetylene. Acetylene is only generated by power arcing and is thus a general indicator for arcing when present. However arcing will occur in on load tap changers and so the presence of acetylene must be looked at carefully to determine whether it arises from OLTC operation. 2.1 DGA Analysis Methods The key gas method of association as follows: Hydrogen: Ethylene: Acetylene: CO and CO2: analysis identifies fault types by Partial discharge Overheating in oil Arcing in oil Solid insulation deterioration (usually paper) In addition there are the various ratio methods which take the ratios of the quantities of specific pairs of gases and then use these ratios to predict the type of fault. The ratio methods currently in general use include: The Rogers ratio method. The IEC (International Electrotechnical Committee) ratio method. The Dornenberg ratio method. The Duval triangle method (this analyses the data using groups of three gases). ELEC4611: H.V. Test Techniques and Insulation Assessment p.16 In addition to the above there are a number of other methods (e.g. IEEE and Laborelec) and also many in-house methods of analysis used by various utilities, based on their accumulated experience. In recent years fuzzy logic analysis has become popular for the assessment of dissolved gas data. DGA is a valuable diagnostic technique and is probably one of the most widely practiced techniques in current use. It is simple to do, does not require disconnection of equipment from supply and most utilities have the chemical analysis tools available. The problems with the technique are that there may be a delay in getting results and as it is often used as a routine maintenance technique, the data is generally not analysed as thoroughly as is warranted. The other problem is that DGA gives only a measure of the integrated effects of the fault. It does not give any information as to whether the fault has been in existence for a short or long time and thus it is not easy to identify the magnitude of the fault. It is also not able to give continuous on-line monitoring. There are some continuous on-line DGA monitors (HYDRAN monitors) available but they are restricted in the range of gases that can be identified and not so wide-ranging in identifying fault types as the full DGA laboratory tests. In addition to normal DGA, which essentially identifies mainly problems with oil, there are more sophisticated test techniques of a similar type which are used to monitor more accurately the degradation of the paper insulation. These tests look at gases generated by the chemical decomposition ELEC4611: H.V. Test Techniques and Insulation Assessment p.17 of the cellulosic structure of the paper as it ages. When the paper is degenerated by age or by some other deteriorative effect the chains of glucose molecules that make up the cellulose polymer structure break down into smaller chain lengths and the bonds between the molecules, when broken, give moisture and also gas generation. The decrease in the chain lengths (de-polymerization) also reduces the tensile strength of the cellulose material and this then means loss of any useful insulation function. The reduction in insulation efficacy can be measured either by the gases given off (not the moisture, as this masked by other effects) or by measurement of the degree of polymerization (DP) of the cellulose. Good (new) paper insulation has a DP of about 1300-1400 (the DP is essentially the number of molecules in a typical polymer chain) while paper with no insulation value has a DP of about 200-300. The gases generated in the decomposition of paper are much more complicated in structure than those generated by oil decomposition. Thus these gases are more difficult to extract and analyse than the relatively simple hydrocarbons analysed by DGA techniques. The gases produced are the so-called furans or furfuraldehyde group of gases. Their measurement requires the use of HPLC or high performance liquid chromatography, a more sophisticated technique than the GC and one which is not generally available in-house to many utilities. ELEC4611: H.V. Test Techniques and Insulation Assessment p.18 [It should be noted that the "paper" referred to above is an inclusive term which also includes pressboard and wood etc. which are cellulosic in their chemical structure]. (iii) a so-called absorption current component (Ia). It is Ia which is dielectric- dependent and thus useful for insulation condition analysis. The various transient current components are shown below: 3. Insulation Resistance (IR) Insulation resistance is a very simple test to apply and can be done very quickly and easily, but must be done off-line. The IR must be measured using DC voltage (usually between 500 V DC to 10 kV DC, depending on the rated voltage of the equipment insulation being tested). However although it is a simple test, the insulation resistance value in itself is not a particularly useful parameter except when the insulation is extremely poor and near to failure. However the time variation of the insulation resistance during the measurement is a much more useful property because the IR-t characteristic variation depends on the dielectric polarisation properties of the insulation and thus on its dielectric (insulation) condition. A number of useful parameters for insulation assessment can thus be derived from the IR vs. time variation. The transient current that flows in a dielectric material when it is subjected to a DC voltage step is made up of a number of current components, all of which are time varying. The total current (I) is composed of three components: The Ohmic leakage current (Ie) is that (constant) component which is left after a long period (one minute or more) of DC voltage application. It is determined by moisture content, and by any contamination, as well as by the intrinsic material insulation resistivity and geometry. Because of the effect of the contaminants in or on the insulation, leakage current is important for insulation condition monitoring. (i) a conduction (Ohmic leakage) current (Ie), (ii) a displacement (true capacitive) current part (Ic), and The absorption current (Ia) is affected by the nature and condition of the insulation dielectric material and is thus an important component for insulation condition monitoring. It ELEC4611: H.V. Test Techniques and Insulation Assessment ELEC4611: H.V. Test Techniques and Insulation Assessment p.19 p.20 will be representative of the intrinsic condition and degradation of the dielectric. The capacitive current (Ic) is determined only by the insulation capacitance. It is not so important for condition monitoring, although moisture can affect it. From the above, it can be seen that the leakage current and the absorption current are the two quantities which are most indicative of insulation quality and their comparative values and trends over time can give useful information about the condition of the dielectric. The insulation resistance (IR)-derived parameters which are used for assessment are: (a) Short-time Test Here, the insulation resistance is measured just once, after 60 seconds of DC voltage application. This is the simplest but least useful form of IR test. It is however extensively used on a routine basis. (b) Resistance-time variation The time variation of insulation is recorded for a period up to 10 minutes. For good insulation, resistance increases with time. This is not a specific test in itself, but the data obtained is used to derive the following quantities: (c) Polarisation Index (PI) ELEC4611: H.V. Test Techniques and Insulation Assessment p.21 This quantity is the ratio of insulation resistance measured at 10 minutes to the resistance measured at 1 minute. A value of 1-2 is characteristic of poor insulation; a value greater than 3 is representative of good insulation. (d) Step Voltage Test This test uses different DC voltage levels applied in steps: e.g. 500 V followed by 2500 V over 60 seconds. This test is used extensively on low voltage motor windings. (e) Dielectric Absorption Ratio This is a variation of the Polarisation Index parameter. Usually the absorption ratio is obtained from the IR value at 60 seconds divided by that at 30 seconds. A value less than 1.3 is characteristic of poor insulation, and a value greater than 1.5 is characteristic of good insulation. Insulation resistance is measured simply by using a “MEGGER” type tester. The tester is normally batteryoperated and should be capable of application of any voltage in the range up to 10,000 volts DC, with an accuracy of about 1-2%. In the basic form, the tester provides a reading of insulation resistance only and the values must be recorded over time and then plotted to determine the required IR-derived parameters. Modern instruments however are microprocessor-controlled to apply the chosen voltage (including the step variations if ELEC4611: H.V. Test Techniques and Insulation Assessment p.22 necessary), record the data over time and then calculate the parameters with the test result then printed out. In some tests it may be necessary to differentiate between surface and bulk (or volume) insulation resistance in the measurement and this will require the use of guard electrodes to direct the electric field application to appropriate configurations. Typical insulation resistances of high voltage equipment are in the hundreds of Mega-ohm to some Giga-ohm levels and at these levels the accuracy of measured resistances are only about 10-15% when performed in the field. Care must be taken to ensure that no surface leakage current paths are involved in the measurement as these will obscure the test result. The instrument accuracy should be checked regularly against standard high value resistors. The advantage of using parameters which involve calculation of a ratio of resistances is that any measurement errors are minimised (assuming the errors are systematic). DC test voltage requirements for IR testing for different ratings of equipment. AC Voltage rating 230 V 400 V 2,200–5,000 V 5000–15000 V more than 15000 V DC Test Voltage level 500 V 500–1000 V 2500–5000 V 5000–15000 V 10000–15000 V ELEC4611: H.V. Test Techniques and Insulation Assessment Typical IR values (at the lower end) for different voltage ratings: also showing the effects of temperature on IR. Voltage (kV) 6.6 11 33 66 IR (@200 C) (M) 400 800 1000 1200 IR (@600 C) (M) 25 50 65 75 4. Overvoltage Tests Overvoltage tests are essentially pass or fail tests and are usually performed at the final stage of manufacture in the factory for power frequency and impulse tests and again after installation in the case of the power frequency overvoltage test. These tests may also be performed on suspect equipment or on refurbished equipment. The power frequency test can be done on-site, but the impulse and switching tests are normally done in the test laboratory or factory only. Overvoltage tests can cause damage to the insulation if the tests and test voltage levels are not properly controlled. The table below shows the range of standard test voltages for power frequency and impulse voltage tests for transformers. Note that the power frequency overvoltage test requirement is about twice system voltage for one minute: the criterion of success is simply that no insulation breakdown failure p.23 ELEC4611: H.V. Test Techniques and Insulation Assessment p.24 occurs. Normally only one such test is performed. Voltage is monitored during the test to aid in identifying any insulation breakdown, as the breakdown current is limited to prevent significant damage. The impulse test level required for specific equipment varies greatly with rated voltage of the equipment. A number of impulses tests (perhaps about 5 may be required) and different polarities may also be required. The impulse voltage waveform is recorded and will indicate if any failure occurs during the test. The equipment buyer may also specify other insulation tests that must be done before the item of equipment is accepted from the manufacturer. For example an induced overvoltage test at a higher frequency may be performed on transformers. Similarly a chopped wave test may be needed in some cases. 4.1 Power Frequency Overvoltage Test of reactive power requirements. For HV power cable overvoltage tests, HV resonant test sets using tunable inductors to achieve resonant conditions with the cable capacitance are used. At resonance, the HV transformer only needs to supply the pure Ohmic losses, which are generally quite small as they arise only from leakage currents in the cable. Paper oil insulated power cables were usually tested with HVDC which required much lower rating of supply equipment. However XLPE cables cannot be tested with HVDC because of potential problems with remnant charge build up after test with DC. It can be seen from the table that a typical power frequency test voltage is about 2 per unit or 2U0. There are some reservations about imposing such a high test voltage on new equipment but the accepted standard tests require these levels. Typical test voltage levels for overvoltage tests on power transformers (AS/NZS 60076.3:2008) These are relatively simple to achieve if the necessary power supplies are available. For on-site tests this will require use of a mobile HV transformer, which may not be easily available for the full transmission voltage range of a transmission utility's operation. Generally only items with low capacitance can be tested on-site because of the problems of supplying large quantities of reactive power with low capacity mobile test transformers. Thus, only items such as transformers, instrument transformers, circuit breakers and similar equipment items can be tested at full voltage on site. Cables cannot be tested in this way because ELEC4611: H.V. Test Techniques and Insulation Assessment p.25 ELEC4611: H.V. Test Techniques and Insulation Assessment p.26 4.2 Impulse testing There are two types of transient overvoltages that must be tested for in high voltage equipment. These are: lightning overvoltages switching overvoltages Power system equipment items must be tested for their ability to withstand the effects of such transient voltages, the magnitudes of which are typical to their voltage rating, without suffering dielectric breakdown. 4.2.1 Lightning impulse testing Lightning impulses can be up to 1000 kV or more in amplitude and the associated current may be up to 100 kA in each stroke, although 10-20 kA is typical. If the actual strike is to an overhead line, a travelling wave results which then moves along the transmission line (unless it causes breakdown of the air insulation between lines). This HV propagating surge may test the electrical insulation of any equipment connected to the line and thus the equipment must be tested for its withstand ability to such transients. Even if the strike is not to a line, but occurs close to it, induced overvoltages may be coupled into the line inductively or capacitively. The test waveform used for equipment to test against lightning impulse voltage is the generally agreed shape of 1.2/50 s. The voltage rises to a peak in 1.2 s and decays ELEC4611: H.V. Test Techniques and Insulation Assessment p.27 ELEC4611: H.V. Test Techniques and Insulation Assessment p.28 to half peak in 50s. There are some tolerances allowed for the rise time and decay time when testing (typically about +/- 20%). In some cases chopped wave tests are performed where the voltage is driven to zero very quickly. This test can be used to provide tests of, for example, inter-turn insulation where the capacitive voltage coupling is enhanced by the fast chopping. If failure occurs under impulse testing, the disruptive discharge will produce something akin to a chopped wave shape. The figures below shows typical lightning impulse voltage waveshapes for (a) full wave, (b) chopped wave on decaying side and (c) chopped wave on the rise. Typical standard test voltage amplitudes are listed in the previous tables. (ii) Chopped wave (tail) Lightning impulse test waveforms (i) Standard 1.2/50 ELEC4611: H.V. Test Techniques and Insulation Assessment (iii) Chopped wave (front) p.29 ELEC4611: H.V. Test Techniques and Insulation Assessment p.30 4.2.2 Switching impulse testing Switching impulses occur as a result of operation of circuit breakers, switches etc. in the power system. Their shape is very dependent on the system parameters and there are thus very substantial variations in magnitudes and in shape of switching impulses. However their risetime is generally much slower than that of lightning impulses and their duration is also generally much longer. The amplitude of typical switching impulses is about 2-3 p.u. and is thus a little lower than lightning impulse amplitudes. However the longer duration may stress the insulation equally as much as lightning effects or even more in some cases. A standard switching impulse waveform has a risetime of about 250 s and a decay to half peak of about 2500 s. This is designated as the 250/2500 s switching waveform. There are tolerances of about 20% on the rise and fall time values in testing. Because of the variability in shape for different systems, there are other standard waveshapes which can be used if required by the test situation: these include the 100/2500 s and the 500/2500 s. The amplitudes of switching impulses are generally a little lower than lightning impulses, with the amplitude depending on the application. ELEC4611: H.V. Test Techniques and Insulation Assessment p.31 The figure above shows a typical waveshape of a switching transient test voltage. [Note that switching transients are not applied as chopped waves.] 4.2.3 Impulse voltages for LV systems and Communications systems With the increasing susceptibility of modern electronics to impulse voltages and with the increasing use of power electronics and such hard switching elements as IGBTs, there is now a need to impulse test low voltage equipment. There is also particular need to test information technology equipment for impulse voltages and in the case of IT equipment there are very many different impulse voltage waveshapes that are used for these tests. ELEC4611: H.V. Test Techniques and Insulation Assessment p.32 interconnecting NSW and Queensland and one in a cable interconnecting parts of NSW and SA. 4.3 High Voltage DC testing The use of high voltage DC testing for AC equipment with DC voltage test levels about the same as the peak AC voltage has been used for many years in testing, particularly when testing equipment with high reactive power requirements such as cables. On-site testing of power cables using HVDC was practised for many years because of the benefits of small transformer/supply power requirements. The use of HVDC to test HVAC equipment has some advantages and some disadvantages. One of the main disadvantages occurs with modern polymeric insulation. Great care must be exercised when using high voltage DC for the testing of such insulation. The very high insulation resistance means that the effective time constant of discharge of any accumulated charge and any recovered charge is very high for such material. Thus, when normal voltage is re-applied, the charge retention may cause overvoltages and damage the insulation. Modern XLPE cable insulation is prone to this problem and HVDC testing is not performed on such cables. Paper insulated cables, however, are not affected in this way and HVDC has been used for many years to test such cables. Polymeric insulation has always been considered too much of a risk to use for HVDC cables and although paperinsulated AC cables have been almost totally supplanted by XLPE, XLPE has not been used for DC applications for the above reasons. Recently however, a polymer has been produced that can be used for HVDC cables and has been used in two applications in Australia: one in a DC cable ELEC4611: H.V. Test Techniques and Insulation Assessment p.33 Advantages of HVDC Testing Can be used on equipment with high capacitance such as cables Less damaging to insulation than HVAC The duration of voltage application is thus not as critical as with HVAC Insulation resistance tests can be performed concurrently The size of the test equipment supply is much reduced from HVAC Disadvantages of HVDC testing Electric field distribution in insulation is different to that with AC stress Residual charge is a problem: there may be space charge problems Needs a longer time to perform tests than for AC HV tests Some insulation defects are not detectable with HVDC Electric field distribution is temperature (load) dependent via resistivity ELEC4611: H.V. Test Techniques and Insulation Assessment p.34 5. Partial Discharge Tests Partial discharges in insulation can cause substantial degradation of the insulation because of the very high energies and associated heat of ionized particles which are produced in the partial discharge ionization process. These ions and electrons can then change the chemical structure and composition of the insulation, thereby degrading it over time. The primary result of the chemical change is carbonisation of the insulation material. The damage due to PDs is primarily with organic insulation: mica-based insulation such as is found in large HV motor and generator winding insulation is able to withstand very high levels of partial discharge activity and heat without any significant deleterious effect on insulation properties. Because of this direct damage to insulation and because PDs can be monitored directly, PD testing and monitoring is perhaps the best insulation assessment technique available. Modern developments in computer-based data acquisition systems have allowed the development of PD testing to a stage where it can give a very sensitive measure of the insulation integrity. To this end there are very substantial programs of PD research which are aimed at: Developing continuous on-line PD monitors Development of signal processing techniques to remove interference Using PD data to determine fault type and location Using PD data to estimate the remnant life of insulation ELEC4611: H.V. Test Techniques and Insulation Assessment p.35 These are very ambitious programs and may not be fully realisable, but PD monitoring is the area where most development is occurring at present. PD monitoring covers the widest spectrum of voltages and equipment. It is used for transformers, cables, switchgear, bushings, insulators, busbars systems, SF6 gas insulated systems, instrument transformers, motors and generators. The PDs can be monitored electrically by resistive, inductive or capacitive sensors or by UHF aerial-coupling units at frequencies up to some GHz. PDs can also be monitored by using piezoelectric detectors sensitive to the ultrasonic acoustic pressure waves generated by the PDs. The major problems with the electrical detection of PDs are interference from corona discharge for example, and the difficulties in some cases of gaining access to the appropriate location for the sensor in or on the equipment item. A discharging sample may be simply represented by the equivalent circuit in the Figure below. This is known as the abc model. The applied alternating voltage V is increased until the voltage across the cavity (Cv) produces a discharge, with a subsequent pulse across the sample of Vx . CC (1) qv Cv c a Vv C C c a Cc where Vv Vx Cc Cv Vx = instantaneous applied voltage and ELEC4611: H.V. Test Techniques and Insulation Assessment p.36 The sudden change Vv will produce a voltage pulse at the sample terminals: Cc (2) Vx Vv Cc Ca and the apparent change in charge across the sample on breakdown of Cv is: CC qx Vx Ca c v Vx .Ca Vx .Cx (3) Cc Cv qv Cv Cc partial discharge dissipated in void Cc apparent partial discharge at terminal qx Cc C or: qx if Cv Cc qv c qv Cv Cc Cv i.e. the apparent (measured) PD is much smaller than the actual PD discharged in an elementary cavity for the simple case considered. [Note: Ca also includes any external capacitance that is in parallel with test object, Cx]. If Ca Cc (this is usually the case but not always, e.g. for a point-plane system) then, before breakdown of the void, equation (1) becomes: qv Cv Cc .Vv (4) and if Cv Cc [Cv assumed to be much thinner and same cross section as Cc] equation (3) becomes: qx Ca Cc .Vx Cc .Vv Ca Cc Cc Ca Cc .Vv (5) [from eq.2] (6) as measurable at terminals. Note that Cc and Vv are rarely known individually. Now from (4) and (6): ELEC4611: H.V. Test Techniques and Insulation Assessment p.37 Figure: (a) Representation of a void in a solid, (b) the abc model, and (c) possible voltage waveforms. ELEC4611: H.V. Test Techniques and Insulation Assessment p.38 The partial breakdown of the insulation causes a charge reduction and thus creates a momentary voltage collapse between the two main terminals of the test object. This gives rise to an electrical current pulse of very short duration and small amplitude. It can be detected in the external circuit connected to the test object. Note that the small voltage collapse is superimposed on the large 50 Hz supply voltage. Basically, the function of a discharge detector is to decouple the high-frequency PD signal from the supply and to amplify this signal. A conventional circuit to detect the PD current pulse is shown in the Figure below. Figure: Basic circuit for PD measurements. Cx represents the capacitance of the test specimen. Ck is the coupling (blocking) capacitor which, of course, must be discharge-free and appropriately rated for use at highvoltage. The measuring impedance Z is connected in series with Ck. Following a PD, a redistribution of the remaining charge between Cx and Ck will give rise to a corresponding current pulse flowing through Ck and the measuring impedance Z. The signal picked up by Z is fed through a ELEC4611: H.V. Test Techniques and Insulation Assessment p.39 long cable to an amplifier which is at some metres away from the HV area. In some systems, the amplifier is incorporated into Z. Measurement sensitivity is dependent on the relative values between Cx and Ck as this will determine the proportion of restoring charge flowing through Z. Preferably, Ck should be as large as possible to maximize the external charge displacement. 6. Dielectric spectroscopy Solid and liquid dielectric insulants have a response to an applied DC electric field that is determined by their intrinsic dielectric properties, including their dipole structure, electronic and ionic polarisation, interfacial polarization and many other facets, including chemical composition. The actual dielectric response of the dielectric material is thus a sensitive determinant of the insulation state and hence of its condition. Any impurities or change in structure and chemistry for example should theoretically be able to be determined by determining the dielectric response to an applied voltage of a HV insulation material. We have already discussed one version of this general method in that the capacitance and DDF of insulation measured with a Schering bridge is one part of the dielectric response. However there are other facets of the more general dielectric response that can be used to focus on particular aspects of aged materials. This includes in particular moisture in insulation and its effect on insulation level and ageing. ELEC4611: H.V. Test Techniques and Insulation Assessment p.40 When an electric field E is applied to a polar dielectric, polarisation of the material increases the electric displacement flux D by an amount P, the polarization flux and thus raises the relative permittivity to a value greater than 1: D P o E r o E We are particularly concerned with the time variation of the response as this will allow determination of dielectric response in both time and frequency domains: frequency range that is of interest to us in insulation assessment for use at power frequencies. The transformation requires the dielectric to be linear however and in some cases, such as XLPE with high water tree components, the dielectric is not linear. It should be noted that the dielectric dissipation factor (DDF) and capacitance measurements at power frequency, or whatever the test frequency used is, gives just one point on the dielectric response frequency-domain curve. D t P t o E t It is thus the polarization P(t) that is of interest. It is of interest both as the response to an applied electric field (the polarisation response) and its response when that electric field is removed (de-polarisation or relaxation response). Both of these can give useful information about the insulation condition. The response as above can be obtained in the time domain by application of a DC voltage step for a defined period of time, followed by a short-circuiting for a defined period and then followed by an open circuit relaxation period. Typically the applied DC voltage level is about 10% of the rated AC voltage. This then does not cause any damage to the dielectric and in the case of very good dielectrics does not cause any problems with residual charge on the material after the test. It is possible to obtain the response in the frequency domain by performing a Fourier Transformation of the time domain response to a step. This then gives the dielectric response over a large frequency range. However it is only the lower 7. Other Diagnostic Tests ELEC4611: H.V. Test Techniques and Insulation Assessment ELEC4611: H.V. Test Techniques and Insulation Assessment p.41 The present situation in the electrical industry is aimed at extending the life of large items of capital equipment and thus asset management and condition monitoring are now very important aspects of operation. There is a very substantial program of development of new monitoring techniques. These include, for example, Frequency response analysis (FRA) of windings. Very low frequency (VLF) testing of cables. On-line DDF monitoring systems. On-line PD monitoring of cables. Fibre-optic acoustic sensors for PDs. Degree of polymerisation testing of composite insulators. On-line leakage current monitors for insulators. Oscillating voltage tests of cable joints. p.42 UHF (up to a few GHz) PD monitoring systems for transformers. Infrared imaging techniques. Corona discharge visualisation techniques. ELEC4611: H.V. Test Techniques and Insulation Assessment p.43